Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

NA2XY

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

NA2XY

NA2XY 11xx(10-500)
(10-500) mm²
mm² 0.6/1
0.6/1 kV kV
Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SPLN 43-6

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Aluminium Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban XLPE Insulation
Area approx. approx. supply networks, if mechanical damage is
mm² mm kg/km unlikely.
PVC Sheath
10 8.5 84 Special Features on Request
16 9.7 113 • Oil Resistance
• UV Resistance
25 11.3 156 • Flame Retardant Cat. A, B, C
35 12.5 196 • Flame Retardant Non Category
• Anti Termite
50 14.1 257
• Anti Rodent
70 16.2 335 • Low Smoke Zero Halogen
95 18.3 434 • Nylon Coated

120 19.8 509


150 22.5 639
Note :
185 24.5 772
Conductor Shape
240 28.0 1,008 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
300 30.5 1,208 25 - 500 sqmm supplied in non compacted circular stranded (rm) or compacted
circular stranded (cm) conductor shape
400 36.0 1,696
500 39.0 1,982 Standard Packing
10 - 500 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short
circuit current
Nom. DC AC Trefoil Flat
at
Cross Resistance Resistance formation formation in air in ground in air in ground 1 sec
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA)
10 3.08 3.949 0.336 0.382 60 71 62 72 0.94
16 1.91 2.449 0.311 0.357 81 92 84 94 1.50
25 1.20 1.539 0.302 0.348 109 118 112 121 2.35
35 0.868 1.113 0.289 0.335 134 142 138 145 3.29
50 0.641 0.822 0.279 0.325 165 168 170 172 4.70
70 0.443 0.568 0.269 0.316 211 206 218 212 6.58
95 0.320 0.411 0.265 0.312 261 245 269 253 8.93
120 0.253 0.325 0.262 0.308 303 279 313 287 11.28
150 0.206 0.265 0.258 0.304 353 313 364 323 14.10
185 0.164 0.212 0.256 0.302 410 355 423 366 17.39
240 0.125 0.162 0.253 0.299 494 412 510 426 22.56
300 0.100 0.130 0.249 0.295 571 465 590 481 28.20
400 0.0778 0.103 0.245 0.292 688 536 711 555 37.60
500 0.0605 0.081 0.245 0.291 796 609 823 631 47.00
25704-01 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NA2XY
NA2XY 22xx(10-300)
(10-300) mm²
mm² 0.6/1
0.6/1 kV kV
Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SPLN 43-6

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Aluminium Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section XLPE Insulation
industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is
mm² mm kg/km unlikely.
PVC Inner Sheath
10 17.2 347 Special Features on Request
16 19.7 460 • Oil Resistance
• UV Resistance PVC Sheath
25 22.0 587 • Flame Retardant Cat. A, B, C
35 24.5 734 • Flame Retardant Non Category
• Anti Termite
50 27.5 836 • Anti Rodent
70 31.5 1,092 • Low Smoke Zero Halogen
• Nylon Coated
95 35.5 1,433
120 39.0 1,734
150 42.5 2,040 Note :
Conductor Shape
185 48.5 2,595
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
240 53.5 3,211 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
300 59.0 3,943
Standard Packing
10 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 90°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
10 3.08 3.949 0.248 61 72 0.94
16 1.91 2.449 0.236 88 99 1.50
25 1.20 1.539 0.242 119 130 2.35
35 0.868 1.113 0.234 145 157 3.29
50 0.641 0.822 0.232 175 185 4.70
70 0.443 0.568 0.229 220 229 6.58
95 0.320 0.411 0.224 272 276 8.93
120 0.253 0.325 0.223 317 320 11.28
150 0.206 0.265 0.225 362 351 14.10
185 0.164 0.211 0.225 420 400 17.39
240 0.125 0.162 0.223 497 467 22.56
300 0.100 0.130 0.222 577 532 28.20
25704-02 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NA2XY
NA2XY 33xx(10-300)
(10-300) mm²
mm² 0.6/1
0.6/1 kV kV
Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SPLN 43-6

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Aluminium Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban XLPE Insulation
Area approx. approx. supply networks, if mechanical damage is
mm² mm kg/km unlikely.
PVC Inner Sheath
10 18.0 382 Special Features on Request
16 21.0 510 • Oil Resistance
PVC Sheath
• UV Resistance
25 23.5 660 • Flame Retardant Cat. A, B, C
35 26.0 830 • Flame Retardant Non Category
• Anti Termite
50 28.0 828
• Anti Rodent
70 32.5 1,126 • Low Smoke Zero Halogen
95 36.0 1,422 • Nylon Coated

120 39.0 1,716


150 44.0 2,113
Note :
185 48.5 2,577
Conductor Shape
240 54.5 3,279 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
300 59.0 3,963 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 90°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
10 3.08 3.949 0.248 52 60 0.94
16 1.91 2.449 0.236 75 84 1.50
25 1.20 1.539 0.242 100 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 149 156 4.70
70 0.443 0.568 0.229 189 193 6.58
95 0.320 0.411 0.224 233 232 8.93
120 0.253 0.325 0.223 271 268 11.28
150 0.206 0.265 0.225 310 296 14.10
185 0.164 0.211 0.225 359 336 17.39
240 0.125 0.162 0.223 429 429 22.56
300 0.100 0.130 0.222 496 447 28.20
25704-03 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NA2XY
NA2XY 44xx(10-300)
(10-300) mm²
mm² 0.6/1
0.6/1 kV kV
Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SPLN 43-6

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Aluminium Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
approx. approx. XLPE Insulation
Area supply networks, if mechanical damage is
mm² mm kg/km unlikely.
PVC Inner Sheath
10 19.5 446 Special Features on Request
16 23.0 601 • Oil Resistance
PVC Sheath
• UV Resistance
25 25.5 787 • Flame Retardant Cat. A, B, C
35 28.5 994 • Flame Retardant Non Category
• Anti Termite
50 32.5 1,058 • Anti Rodent
70 36.5 1,431 • Low Smoke Zero Halogen
• Nylon Coated
95 40.5 1,820
120 45.5 2,275
150 51.5 2,749 Note :
Conductor Shape
185 56.0 3,336
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
240 62.5 4,243 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
300 68.0 5,131
Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 90°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
10 3.08 3.949 0.248 52 60 0.94
16 1.91 2.449 0.236 75 84 1.50
25 1.20 1.539 0.242 110 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 149 156 4.70
70 0.443 0.568 0.229 189 193 6.58
95 0.320 0.411 0.224 233 232 8.93
120 0.253 0.325 0.223 271 268 11.28
150 0.206 0.265 0.225 310 296 14.10
185 0.164 0.211 0.225 359 336 17.39
240 0.125 0.162 0.223 429 393 22.56
300 0.100 0.130 0.222 496 447 28.20
25704-04 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NA2XY
NA2XY 55xx(10-50)
(10-50) mm²
mm² 0.6/1
0.6/1 kV kV
Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SPLN 43-6

Construction Data
Application :
Nom. Overall Cable PVC Filler
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations, Aluminium Conductor
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is
XLPE Insulation

mm² mm kg/km unlikely.


PVC Inner Sheath
10 21.5 521 Special Features on Request
16 24.5 709 • Oil Resistance
PVC Sheath
• UV Resistance
25 27.5 935 • Flame Retardant Cat. A, B, C
35 31.0 1,187 • Flame Retardant Non Category
• Anti Termite
50 36.0 1,479
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 90°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
10 3.08 3.949 0.248 52 60 0.94
16 1.91 2.449 0.236 75 84 1.50
25 1.20 1.539 0.242 100 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 144 156 4.70
25704-05 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification