N2XCY
N2XCY
N2XCY
id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Conductor Inductance Current - Carrying Capacity at 30 C * Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
Trefoil
formation
(mH/km)
Flat
formation
(mH/km)
in air
Max.
(A)
in ground
Max.
(A)
in air
Max.
(A)
in ground
Max.
(A)
1.5 / 1.5 12.1 15.429 0.551 0.597 29 33 30 34 0.21
2.5 / 2.5 7.41 9.449 0.510 0.557 39 43 40 44 0.36
4 / 4 4.61 5.878 0.474 0.520 51 55 52 57 0.57
6 / 6 3.08 3.927 0.446 0.492 64 69 66 71 0.86
10 / 10 1.83 2.333 0.413 0.459 87 92 90 95 1.43
16 / 16 1.15 1.466 0.390 0.436 116 118 119 122 2.29
25 / 16 0.727 0.927 0.365 0.411 154 153 158 157 3.58
35 / 16 0.524 0.668 0.348 0.394 188 183 193 188 5.01
50 / 25 0.387 0.494 0.336 0.383 230 217 236 223 7.15
70 / 35 0.268 0.342 0.323 0.369 289 265 297 271 10.01
95 / 50 0.193 0.247 0.313 0.360 355 316 363 322 13.59
120 / 70 0.153 0.196 0.310 0.356 412 357 419 361 17.16
150 / 70 0.124 0.159 0.304 0.351 468 398 476 402 21.45
185 / 95 0.0991 0.128 0.300 0.346 536 444 540 445 26.46
240 / 120 0.0754 0.098 0.292 0.338 625 503 625 499 34.32
300 / 150 0.0601 0.079 0.287 0.333 703 552 698 543 42.90
400 / 185 0.0470 0.063 0.287 0.334 791 602 780 588 57.20
500 / 240 0.0366 0.051 0.283 0.330 881 651 867 634 71.50
630 / 300 0.0283 0.041 0.280 0.326 983 703 969 685 90.09
800 / 400 0.0221 0.035 0.279 0.325 1085 754 1081 743 114.40
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
1.5 / 1.5 9.7 114
2.5 / 2.5 10.2 135
4 / 4 10.8 170
6 / 6 11.3 214
10 / 10 12.4 304
16 / 16 13.8 431
25 / 16 15.5 548
35 / 16 16.6 650
50 / 25 18.8 892
70 / 35 21.0 1,207
95 / 50 23.5 1,600
120 / 70 26.0 2,045
150 / 70 28.0 2,320
185 / 95 30.5 2,942
240 / 120 34.0 3,761
300 / 150 37.0 4,591
400 / 185 41.5 5,830
500 / 240 46.0 7,450
630 / 300 52.0 9,561
800 / 400 58.0 12,290
N2XCY 1 x (1.5-800) mm 0.6/1 kV
N2XCY 1 x (1.5-800) mm 0.6/1 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Construction Data
Application :
For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted
circular stranded (cm) conductor shape
Standard Packing
1.5 - 240 sqmm supplied in wooden drum @ 1000 m
300 - 800 sqmm supplied in wooden drum on available length
Length Tolerance per drum 2%
Electrical Data
Non-hygroscopic Tape
Copper Tape Screen
Copper Wire Screen
Copper Conductor
PVC Inner Sheath
PVC Sheath
XLPE Insulation
1
4
5
3
3
-
0
1
R
e
v
.
2
.
0
/
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XCY 2 x (1.5-300) mm 0.6/1 kV
N2XCY 2 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
1.5 / 1.5 13.0 198
2.5 / 2.5 13.9 239
4 / 4 15.0 304
6 / 6 16.2 384
10 / 10 18.1 546
16 / 16 21.0 766
25 / 16 24.0 1,030
35 / 16 26.0 1,283
50 / 25 29.5 1,631
70 / 35 33.0 2,247
95 / 50 37.5 3,028
120 / 70 42.0 3,817
150 / 70 46.0 4,526
185 / 95 51.0 5,694
240 / 120 57.0 7,302
300 / 150 63.0 9,049
Construction Data
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
1.5 / 1.5 12.1 15.429 0.315 30 35 0.21
2.5 / 2.5 7.41 9.449 0.293 39 46 0.36
4 / 4 4.61 5.878 0.275 52 60 0.57
6 / 6 3.08 3.927 0.263 66 75 0.86
10 / 10 1.83 2.334 0.248 90 100 1.43
16 / 16 1.15 1.467 0.238 120 131 2.29
25 / 16 0.727 0.927 0.240 159 168 3.58
35 / 16 0.524 0.669 0.233 195 203 5.01
50 / 25 0.387 0.494 0.232 238 241 7.15
70 / 35 0.268 0.342 0.229 299 295 10.01
95 / 50 0.193 0.247 0.224 365 352 13.59
120 / 70 0.153 0.196 0.223 425 400 17.16
150 / 70 0.124 0.160 0.224 484 448 21.45
185 / 95 0.0991 0.128 0.225 552 502 26.46
240 / 120 0.0754 0.099 0.223 650 578 34.32
300 / 150 0.0601 0.080 0.221 736 643 42.90
XLPE Insulation
PVC Sheath
PVC Inner Sheath
Copper Conductor
Copper Wire Screen
Copper Tape Screen
Non-hygroscopic Tape
1
4
5
3
3
-
0
2
R
e
v
.
2
.
0
/
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XCY 3 x (1.5-300) mm 0.6/1 kV
N2XCY 3 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
1.5 / 1.5 13.5 218
2.5 / 2.5 14.5 270
4 / 4 15.7 348
6 / 6 16.9 446
10 / 10 19.0 645
16 / 16 22.0 916
25 / 16 25.0 1,260
35 / 16 27.5 1,597
50 / 25 30.0 1,919
70 / 35 34.0 2,697
95 / 50 37.5 3,608
120 / 70 41.5 4,531
150 / 70 46.5 5,459
185 / 95 51.0 6,820
240 / 120 57.5 8,834
300 / 150 62.5 10,899
Construction Data
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
1.5 / 1.5 12.1 15.429 0.315 25 29 0.21
2.5 / 2.5 7.41 9.449 0.293 33 38 0.36
4 / 4 4.61 5.878 0.275 44 50 0.57
6 / 6 3.08 3.927 0.263 56 63 0.86
10 / 10 1.83 2.334 0.248 76 84 1.43
16 / 16 1.15 1.467 0.238 102 110 2.29
25 / 16 0.727 0.927 0.240 135 141 3.58
35 / 16 0.524 0.669 0.233 166 170 5.01
50 / 25 0.387 0.494 0.232 207 207 7.15
70 / 35 0.268 0.342 0.229 258 251 10.01
95 / 50 0.193 0.247 0.224 317 302 13.59
120 / 70 0.153 0.196 0.223 369 343 17.16
150 / 70 0.124 0.160 0.224 421 383 21.45
185 / 95 0.0991 0.128 0.225 484 431 26.46
240 / 120 0.0754 0.099 0.223 570 495 34.32
300 / 150 0.0601 0.080 0.221 648 552 42.90
XLPE Insulation
PVC Sheath
PVC Inner Sheath
Copper Conductor
Copper Wire Screen
Copper Tape Screen
Non-hygroscopic Tape
1
4
5
3
3
-
0
3
R
e
v
.
2
.
0
/
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XCY 4 x (1.5-300) mm 0.6/1 kV
N2XCY 4 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
1.5 / 1.5 14.3 250
2.5 / 2.5 15.4 315
4 / 4 16.8 406
6 / 6 18.1 523
10 / 10 20.5 772
16 / 16 23.5 1,100
25 / 16 27.5 1,541
35 / 16 30.0 1,976
50 / 25 33.5 2,428
70 / 35 38.5 3,418
95 / 50 42.5 4,583
120 / 70 48.0 5,807
150 / 70 54.0 6,992
185 / 95 58.5 8,704
240 / 120 65.5 11,283
300 / 150 71.5 13,920
Construction Data
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
1.5 / 1.5 12.1 15.429 0.315 28 32 0.21
2.5 / 2.5 7.41 9.449 0.293 37 42 0.36
4 / 4 4.61 5.878 0.275 48 55 0.57
6 / 6 3.08 3.927 0.263 61 68 0.86
10 / 10 1.83 2.334 0.248 84 91 1.43
16 / 16 1.15 1.467 0.238 112 118 2.29
25 / 16 0.727 0.927 0.240 150 153 3.58
35 / 16 0.524 0.669 0.233 185 184 5.01
50 / 25 0.387 0.494 0.232 217 211 7.15
70 / 35 0.268 0.342 0.229 271 257 10.01
95 / 50 0.193 0.247 0.224 335 309 13.59
120 / 70 0.153 0.196 0.223 389 350 17.16
150 / 70 0.124 0.160 0.224 451 395 21.45
185 / 95 0.0991 0.128 0.225 512 442 26.46
240 / 120 0.0754 0.099 0.223 603 508 34.32
300 / 150 0.0601 0.080 0.221 685 566 42.90
Non-hygroscopic Tape
Copper Tape Screen
Copper Wire Screen
Copper Conductor
PVC Inner Sheath
PVC Sheath
XLPE Insulation
1
4
5
3
3
-
0
4
R
e
v
.
2
.
0
/
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
PVC Filler
Non-hygroscopic Tape
Copper Tape Screen
Copper Wire Screen
Copper Conductor
PVC Inner Sheath
PVC Sheath
XLPE Insulation
1.5 / 1.5 15.2 291
2.5 / 2.5 16.4 365
4 / 4 17.9 476
6 / 6 19.5 617
10 / 10 22.5 909
16 / 16 25.5 1,300
25 / 16 29.5 1,844
35 / 16 32.5 2,390
50 / 25 37.0 3,120
N2XCY 5 x (1.5-50) mm2 0.6/1 kV
N2XCY 5 x (1.5-50) mm
2
0.6/1 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum 2%
Construction Data
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
1.5 / 1.5 12.1 15.429 0.315 29 33 0.21
2.5 / 2.5 7.41 9.449 0.293 38 43 0.36
4 / 4 4.61 5.878 0.275 50 56 0.57
6 / 6 3.08 3.927 0.263 63 70 0.86
10 / 10 1.83 2.334 0.248 87 93 1.43
16 / 16 1.15 1.467 0.238 116 120 2.29
25 / 16 0.727 0.927 0.240 156 156 3.58
35 / 16 0.524 0.669 0.233 191 186 5.01
50 / 25 0.387 0.494 0.232 231 218 7.15
1
4
5
3
3
-
0
5
R
e
v
.
2
.
0
/
2
0
0
9