NYA 1.5 - 400 mm2
NYA 1.5 - 400 mm2
NYA 1.5 - 400 mm2
Copper Conductor
PVC Insulation
APPLICATION :
For building wire installed in conduit in dry location and interwiring in swich board and control panel. Can be used as grounding cable,
inherently flame retardant in compliance with IEC 60332.
Construction Data
Nom.
mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Cross Sect.
Overall diameter
mm 3.0 3.6 4.2 4.7 6.1 7.0 8.8 9.9 11.8 13.5 15.7 17.2 19.1 21.5 24.9 27.3 30.7
(Approx.)
Bending radius mm 18 22 25 28 36 42 53 59 71 81 94 103 114 129 149 164 184
Cable Weight (Approx.) kg/km 22 34 50 69 116 171 275 366 508 702 953 1,178 1,444 1,831 2,407 2,951 3,772
Electrical Data
Conductor Insulation Current-Carrying Short
Nom. DC AC Insulation Capacity circuit current
o
Cross Resistance Resistance Resistance at 30 C Inductance at
o o o
Sect. at 20 C at 70 C at 70 C in pipe in air 1 sec
Max. Max. Min. Max. Max. Max.
(mm²) (Ω/km) (Ω/km) (M.Ω.km) (A) (A) (mH/km) (kA)
1.5 12.1 14.5 0.010 15 24 0.315 0.17
2.5 7.41 8.87 0.009 20 32 0.304 0.29
4 4.61 5.52 0.0077 25 43 0.285 0.46
6 3.08 3.69 0.0065 33 54 0.271 0.69
10 1.83 2.19 0.0065 45 74 0.269 1.15
16 1.15 1.38 0.0050 61 98 0.255 1.84
25 0.727 0.870 0.0050 83 140 0.255 2.88
35 0.524 0.627 0.0040 104 159 0.247 4.03
50 0.387 0.464 0.0045 132 198 0.248 5.75
70 0.268 0.321 0.0035 166 247 0.238 8.05
95 0.193 0.232 0.0035 198 293 0.236 10.93
120 0.153 0.184 0.0032 236 345 0.230 13.80
150 0.124 0.150 0.0032 - 391 0.230 17.25
185 0.0991 0.121 0.0032 - 449 0.232 21.28
240 0.0754 0.0935 0.0032 - 529 0.232 27.60
300 0.0601 0.0752 0.0030 - 609 0.228 34.50
400 0.0470 0.0600 0.0028 - 726 0.228 41.20