GENERAL SPECIFICATION

FOR

AIR-CONDITIONING, REFRIGERATION, VENTILATION

AND

CENTRAL MONITORING & CONTROL SYSTEM

INSTALLATION

IN

GOVERNMENT BUILDINGS

OF

THE HONG KONG SPECIAL ADMINISTRATIVE REGION

2017 EDITION

ARCHITECTURAL SERVICES DEPARTMENT


THE GOVERNMENT OF THE HONG KONG SPECIAL ADMINISTRATIVE REGION
PREFACE

This General Specification aims to lay down the technical requirements of


materials and equipment, the standards of workmanship, the requirements on testing and
commissioning and operation and maintenance as well as requirements on document
submissions for Air-conditioning, Refrigeration, Ventilation and Central Monitoring &
Control System Installation in Government Buildings of the Hong Kong Special
Administrative Region (HKSAR).

The 2017 edition of this General Specification was developed from the 2012
edition (incorporation Corrigendum No. GSAC02-2012) by the Air-conditioning Specialist
Support Group that was established under the Building Services Branch Technical
Information and Research & Development Committee of the Architectural Services
Department (ArchSD). It incorporates updated international standards and codes as well as
technological developments which find applications in Hong Kong. To be in line with the
Departments endeavour to reduce the environmental burden on our neighbours and to help
preserving common resources while improving the quality of our service, this General
Specification puts emphasis on green features and green practices for construction as well
as initiatives for enhancement of client satisfaction on completed projects.

With the benefit of information technology, electronic version of this edition is to


be viewed on and free for download from the ArchSD Internet homepage. As part of the
Governments efforts to limit paper consumption, hard copies of this General Specification
will not be put up for sale.

The draft of the 2017 edition has been circulated to stakeholders within and
external to the Government before finalisation. Nevertheless, the ArchSD welcomes
comments on its contents at any time since the updating of this General Specification is a
continuous process for the inclusion of any developments that can help meeting the needs
of our community.
DISCLAIMER

This General Specification is solely compiled for Air-conditioning, Refrigeration,


Ventilation and Central Monitoring & Control System Installation carried out for or on
behalf of the ArchSD in Government buildings of the HKSAR.

There are no representations, either expressed or implied, as to the suitability of this


General Specification for purposes other than that stated above. Users who choose to
adopt this General Specification for their works are responsible for making their own
assessments and judgement of all information contained here. The ArchSD does not
accept any liability and responsibility for any special, indirect or consequential loss or
damages whatsoever arising out of or in connection with the use of this General
Specification or reliance placed on it.

The materials contained in this document may not be pertinent or fully cover the
extent of the installation in non-government buildings and there is no intimated or implied
endorsement of the sales, supply and installation of the materials and equipment specified
in this General Specification within the territory of the HKSAR.
TABLE OF CONTENTS

PART A - SCOPE AND GENERAL REQUIREMENTS

SECTION A1 SCOPE OF SPECIFICATION

A1.1 Installations to comply with this General Specification


A1.2 Scope of the Installations
A1.3 Terms and Definitions
A1.4 Singular and Plural

SECTION A2 STATUTORY OBLIGATIONS AND OTHER REGULATIONS

A2.1 Statutory Obligations and Other Requirements


A2.2 Case of Conflict
A2.3 Mechanical Fire Service Installation

SECTION A3 EXECUTION OF INSTALLATIONS

A3.1 The International System of Units (SI)


A3.2 Programme of Installations
A3.3 Builders Work
A3.4 Coordination of Installations
A3.5 Cooperation with Other Contractors
A3.6 Site Supervision
A3.7 Sample Board
A3.8 Advice of Order Placed
A3.9 Record of Materials Delivery
A3.10 Protection of Materials and Equipment
A3.11 Label
A3.12 Warning Notice
A3.13 Guard and Railing for Moving and Rotating Parts of
Equipment
A3.14 Service Condition
A3.15 Voltage Covered by This General Specification
A3.16 Material and Equipment
A3.17 Workmanship
A3.18 Surveys and Measurements

Table of Contents AC_GS


Page 1 of 20 2017 Edition
SECTION A4 DRAWINGS AND MANUALS

A4.1 Drawings in Electronic Format


A4.2 Installation Drawings
A4.3 As-built Drawings
A4.4 Operation and Maintenance (O&M) Manual and User
Manual

Table of Contents AC_GS


Page 2 of 20 2017 Edition
PART B - GENERAL TECHNICAL REQUIREMENTS
(INSTALLATION METHODOLOGY)

SECTION B1 AIR CLEANING EQUIPMENT

B1.1 General
B1.2 Washable Panel Filter
B1.3 Automatic Viscous Filter
B1.4 Disposable Panel Filter
B1.5 Disposable Pleated Panel Filter
B1.6 Renewable Panel Filter
B1.7 Automatic Fabric Roll Filter
B1.8 Bag Filter
B1.9 Cartridge Filter
B1.10 High Efficiency Particulate Arrestance (HEPA) Filter
B1.11 Automatic Reclean able Filter
B1.12 Automatic Reclean able HEPA Filter
B1.13 Automatic Reclean able High Voltage Electrostatic Filter
B1.14 Gas Filter
B1.15 Activated Oxygen Air Purifier
B1.16 Ultra-Violet (UV) Sterilising Light
B1.17 Water Scrubber

SECTION B2 DUCTWORK

B2.1 General
B2.2 Design and Accessories
B2.3 Hangers and Supports
B2.4 Flexible Duct Joints
B2.5 Flexible Ductwork
B2.6 Ductwork Acoustic Treatment
B2.7 Extract Hoods and Valances for Kitchens
B2.8 Grease Filter
B2.9 Ductwork Cleaning Points
B2.10 Testing

SECTION B3 AIR HANDLING AND TREATMENT

B3.1 General

Table of Contents AC_GS


Page 3 of 20 2017 Edition
B3.2 Air Handling Units (AHUs)
B3.3 Axial Flow Fans
B3.4 Ceiling Fans
B3.5 Centrifugal Fans
B3.6 Fan Coil Units
B3.7 Cassette Type Fan Coil Units
B3.8 Mixed Flow Fans
B3.9 Mechanical Roof Extract Units
B3.10 Propeller Fans
B3.11 Protectively Coated Fans and Fans for Corrosive or
Hazardous Applications
B3.12 Rotary Fans
B3.13 In-line Centrifugal Fans
B3.14 EC Plug Fans
B3.15 Jet Fans
B3.16 Conducting Fans
B3.17 Terminal Air Control Devices
B3.18 Grilles and Diffusers
B3.19 Domestic Exhaust Fans

SECTION B4 AUTOMATIC CONTROL

B4.1 Automatic Control System (ACS)


B4.2 General Requirements
B4.3 Air Cooling Control
B4.4 Air Heating Control
B4.5 Electrical/Electronic (Localised) Control System

SECTION B5 CENTRAL CONTROL AND MONITORING SYSTEM (CCMS)

B5.1 General Requirements


B5.2 System Architecture
B5.3 Electrical Wiring
B5.4 Hardware Installation
B5.5 Software Installation

SECTION B6 CENTRAL REFRIGERATION MACHINE, DIRECT


EXPANSION EVAPORATORS AND HEAT REJECTION
PLANT

Table of Contents AC_GS


Page 4 of 20 2017 Edition
B6.1 General
B6.2 Layout and Isolation of Plant Components
B6.3 Delivery of Equipment
B6.4 Refrigeration Pipework and Fittings
B6.5 Air-cooled Packaged Refrigeration Machine
B6.6 Water-cooled Packaged Refrigeration Machine
B6.7 Air-cooled Condenser
B6.8 Air-cooled Evaporator
B6.9 Cooling Tower
B6.10 Heat Recovery Chillier
B6.11 Total Energy Heat Pump
B6.12 Vibration Isolation
B6.13 Electrical Work
B6.14 Safety Ancillaries for Ammonia Refrigeration Machine
B6.15 Solar Heating System

SECTION B7 ELECTRIC MOTORS AND ELECTRICAL EQUIPMENT

B7.1 Low Voltage - General


B7.2 Low Voltage - Electric Motors
B7.3 Low Voltage - Variable Speed Drives
B7.4 Low Voltage - Motor Switchgear, Starter and Control Panels
B7.5 Low Voltage - Automatic Power Factor Correction
Capacitors
B7.6 High Voltage - Electric Equipment

SECTION B8 NOISE AND VIBRATION CONTROL

B8.1 General
B8.2 Equipment Bases
B8.3 Vibration Isolators
B8.4 Plant/Equipment Vibration Isolation
B8.5 Pipe work Vibration Isolation
B8.6 Ductwork Vibration Isolation
B8.7 Ductwork Acoustic Insulation
B8.8 Acoustic Duct lags
B8.9 Ductwork Silencers
B8.10 Acoustic Doors
B8.11 Acoustic Louvers

Table of Contents AC_GS


Page 5 of 20 2017 Edition
B8.12 Acoustic Enclosures
B8.13 Plant Room Acoustic Linings
B8.14 Floating Floors
B8.15 Specialist Manufacturer's Inspection
B8.16 Independent Inspections

SECTION B9 PIPEWORK, VALVES, COCKS AND STRAINERS

B9.1 General
B9.2 Automatic Air Vents
B9.3 Bellow Expansion Joints/Anchors and Guides
B9.4 Changes in Pipe Size
B9.5 Connections in Pipe work
B9.6 Flow Measuring
B9.7 Flushing Down and Drainage
B9.8 Joints and Fittings for Steel Pipe work
B9.9 Joints and Fittings for Copper Tubes
B9.10 Pipe work General Details
B9.11 Pipe work Layout
B9.12 Pipe work Supports, Expansion Joints and Anchor Points
B9.13 Pipe work Vibration De-couplers
B9.14 Plastic Pipe work
B9.15 Specialised Hydraulic System Balancing Valves
B9.16 'T' and 'Y' Fittings
B9.17 Supports for Pipe work
B9.18 Welding and Brazing
B9.19 Labelling and Circuit Control Diagram of Valves

SECTION B10 SYSTEM MONITORING INSTRUMENT

B10.1 General
B10.2 System Static Pressure Gauges for Air Distribution Systems
B10.3 Thermometers - Air Immersion
B10.4 Thermometers - Liquid Immersion
B10.5 Pressure Gauges for Water Systems
B10.6 Self Sealing Test Points
B10.7 Voltage and Current Readings
B10.8 Power Factor Monitoring
B10.9 Power Consumption Metering
B10.10 Liquid Flow Rate Metering

Table of Contents AC_GS


Page 6 of 20 2017 Edition
B10.11 Other Types of Metering Devices
B10.12 Provision of Metering Facilities

SECTION B11 THERMAL INSULATION

B11.1 General
B11.2 Types of Thermal Insulation Materials
B11.3 Pipe work Fittings
B11.4 Chilled Water Pumps and Accessories
B11.5 Ductwork and Air Handling Plant - Methods of Application
B11.6 Chilled Water Pipe work and Equipment - Materials and
Finishes
B11.7 Chilled Water Pipe work and Equipment - Methods of
Application
B11.8 Painting and Identification

SECTION B12 UNITARY AIR-CONDITIONER

B12.1 General
B12.2 Installation and Servicing
B12.3 Anti-Vibration Mounting
B12.4 Casing
B12.5 Compressor
B12.6 Supply Air Fan and Motor
B12.7 Cooling and Heating Coils
B12.8 Air Filter
B12.9 Air-cooled Condensers
B12.10 Electric Ductwork Heaters
B12.11 Refrigerant Piping
B12.12 Condensate Drain Pipe
B12.13 Minimum Installation Requirements of Safety and
Operational Control for Unitary Air-Conditioners
B12.14 Single Packaged Air-Conditioner
B12.15 Packaged Air-Conditioner with Remote Condenser
B12.16 Split Condensing Unit and AHU
B12.17 Variable Refrigerant Volume System
B12.18 Maintenance Servicing Platform

SECTION B13 WATER HANDLING EQUIPMENT

Table of Contents AC_GS


Page 7 of 20 2017 Edition
B13.1 General Pump Installation Requirements
B13.2 Storage
B13.3 Centrifugal Water Pumps
B13.3.1 Common Installation for Boiler Feed-water, Fresh
Water and Saline Water Pumps
B13.3.2 Sump Pumps
B13.3.3 Bore Well Pumps
B13.4 Plant Room Location
B13.5 Pump Foundation
B13.6 Pump Alignment
B13.7 Grouting of Pump Base
B13.8 Support for Piping
B13.9 Connection Piping to Pump
B13.9.1 Suction Piping
B13.9.2 Delivery Piping
B13.9.3 Pipe Flanges
B13.9.4 Expansion Joints
B13.9.5 Intake
B13.10 Suction Strainers
B13.11 Venting Valves for Pump-Set
B13.12 Drains for Pump-Set
B13.13 Instrumentation
B13.14 Feed and Expansion Tank
B13.15 Water Filters
B13.16 Plate Type Heat Exchanger
B13.17 Sea Water Strainer

Table of Contents AC_GS


Page 8 of 20 2017 Edition
PART C - GENERAL TECHNICAL REQUIREMENTS
(MATERIAL AND EQUIPMENT SPECIFICATION)

SECTION C1 AIR CLEANING EQUIPMENT

C1.1 General
C1.2 Standards
C1.3 Washable Panel Filter
C1.4 Automatic Viscous Filter
C1.5 Disposable Panel Filter
C1.6 Disposable Pleated Panel Filter
C1.7 Renewable Panel Filter
C1.8 Automatic Fabric Roll Filter
C1.9 Bag Filter
C1.10 Cartridge Filter
C1.11 High Efficiency Particulate Arrestance (HEPA) Filter
C1.12 Automatic Reclean able Filter
C1.13 Automatic Reclean able HEPA Filter
C1.14 Automatic Reclean able High Voltage Electrostatic Filter
C1.15 Gas Filter
C1.16 Activated Oxygen Air Purifier
C1.17 Ultra-Violet (UV) Sterilising Light
C1.18 Water Scrubber
C1.19 Washing Facilities for Washable Filter
C1.20 Filter Pressure Differential Measurement and Indication
C1.21 Additional Requirements (Spare Filter Media)

SECTION C2 DUCTWORK AND ACCESSORIES

C2.1 General
C2.2 Off Site Pre-Fabrication
C2.3 Specification and Standards
C2.4 Flexible Ductwork
C2.5 Ductwork for Corrosive Fumes
C2.6 Glass Fibre Ductwork
C2.7 Foam Duct Board Ductwork
C2.8 Dampers - General
C2.9 Butterfly, Bifurcating and Multi leaf Dampers
C2.10 Self-Closing (Non-Return) Dampers

Table of Contents AC_GS


Page 9 of 20 2017 Edition
C2.11 Fire, Smoke and Combined Fire and Smoke Stop Dampers
C2.12 Motorized Shut-Off Dampers
C2.13 Terminal Dampers
C2.14 Access Doors and Panels to Ductwork, Cabinets, Cold Stores
C2.15 Ductwork Flanges
C2.16 Ductwork Cleaning Points
C2.17 Test Holes
C2.18 Transfer Ductwork

SECTION C3 AIR HANDLING AND TREATMENT EQUIPMENT

C3.1 General
C3.2 Air Handling Units (AHUs)
C3.3 Axial Flow Fans
C3.4 Ceiling Fans
C3.5 Centrifugal Fans
C3.6 Fan Coil Units
C3.7 Cassette Type Fan Coil Units
C3.8 Mixed Flow Fans
C3.9 Mechanical Roof Extract Units
C3.10 Propeller Fans
C3.11 Protectively Coated Fans and Fans for Corrosive or
Hazardous Applications
C3.12 Rotary Fans (Wall or Ceiling Mounted)
C3.13 In-line Centrifugal Fans
C3.14 EC Plug Fans
C3.15 Jet Fans
C3.16 Conducting Fans
C3.17 Terminal Air Control Devices
C3.18 Grilles and Diffusers
C3.19 Energy Efficiency and Performance
C3.20 Desiccant Dehumidifiers
C3.21 Domestic Exhaust Fans
C3.22 Heat Pipe

SECTION C4 AUTOMATIC CONTROL

C4.1 Electrical Wiring


C4.2 Air Cooler Control
C4.3 Air Heater Control

Table of Contents AC_GS


Page 10 of 20 2017 Edition
C4.3.1 2-way or 3-way Modulating Valves
C4.3.2 Electric Ductwork Heaters
C4.3.3 Differential Pressure Switches
C4.4 Electrical/Electronic (Localised) Control System
C4.4.1 Standalone Direct Digital Controllers/Outstation
(DDC/O)
C4.4.2 ACMV Sub-System Controllers
C4.4.3 Control Panel
C4.4.4 ACMV Sub-system DDC Controller Resident
Software Features Energy Conversation
C4.4.5 ACMV Sub-system DDC Controller Resident
Software Features Other Features
C4.4.6 DDC Sensors
C4.4.7 Electric / Electronic Damper Actuators
C4.4.8 Control Valves
C4.4.9 Automatic Dampers
C4.4.10 Digital Temperature Display

SECTION C5 CENTRAL CONTROL AND MONITORING SYSTEM (CCMS)

C5.1 CCMS Architectural Overview


C5.2 Terminology
C5.3 Relevant Standards
C5.4 Manufacturing Standards
C5.5 CCMS Inter-Networking Standard
C5.6 CCMS Configuration
C5.7 CCMS Operator Workstation
C5.8 Uninterrupted Power Supply
C5.9 Portable Operator Terminal Hardware
C5.10 DDC Controller Hardware
C5.11 Unitary Controller Hardware
C5.12 Gateway/Interfacing Hardware
C5.13 CCMS Central Database Repository
C5.14 CCMS Software - Access Control
C5.15 CCMS Software - Input Process
C5.16 CCMS Software - Information Access
C5.17 CCMS Software - Change-Of-State (COS) and Reporting
C5.18 CCMS Software - Alarm Processing and Reporting
C5.19 CCMS Software - Event Processing
C5.20 CCMS Software - Scheduling

Table of Contents AC_GS


Page 11 of 20 2017 Edition
C5.21 CCMS Software - Graphic Display
C5.22 CCMS Software - Error Messages
C5.23 CCMS Software - Operators Messages
C5.24 CCMS Software - Report Generator
C5.25 CCMS Software - Lockout Summary
C5.26 CCMS Software - Alarm Summary
C5.27 CCMS Software - Message and Graphic Summary
C5.28 CCMS Software - Point Involvement Summary
C5.29 CCMS Software - Signal Priority
C5.30 CCMS Software - System Log
C5.31 CCMS Software - Historical Profiles
C5.32 CCMS Software - Predictor Generator
C5.33 CCMS Software - Preventive Maintenance
C5.34 Controller Software Programming Standard
C5.35 Controller Software - Input/output Processing
C5.36 Controller Software - Digital Run-Time Totalising
C5.37 Controller Software - Analogy Totalising/Averaging
C5.38 Controller Software - Time Based Control
C5.39 Controller Software - Automatic Sequence
C5.40 Controller Software - General Polynomial Curve Fit
C5.41 ACMV Sub-System Controller Software - Energy
Calculation
C5.42 ACMV Sub-System Controller Software - Duty Cycle
C5.43 ACMV Sub-System Controller Software - Power Demand
Monitoring/Load Shedding
C5.44 ACMV Sub-System Controller Software - Optimum Start
Time
C5.45 ACMV Sub-System Controller Software - Supply Air Reset
(SAR)
C5.46 ACMV Sub-System Controller Software - Chilled Water
Optimization (CHO)
C5.47 ACMV Sub-System Controllers
C5.48 ACMV Sub-System Field Device - Smart Sensors
C5.49 ACMV Sub-System Field Device - Smart Actuators
C5.50 ACMV Sub-System Field Device - Control Valves
C5.51 ACMV Sub-System Field Device - Automatic Dampers
C5.52 ACMV Sub-System Field Device - Damper Actuator
C5.53 ACMV CCMS Sub-System Field Device - VAV Box
Control
C5.54 Other CCMS Sub-system

Table of Contents AC_GS


Page 12 of 20 2017 Edition
C5.55 Schedule of Function for CCMS

Table of Contents AC_GS


Page 13 of 20 2017 Edition
SECTION C6 CENTRAL REFRIGERATION MACHINE, DIRECT
EXPANSION EVAPORATOR AND HEAT REJECTION PLANT

C6.1 General
C6.2 Absorption Units
C6.3 Cold Storage Refrigeration
C6.4 Compressors, Reciprocating Type
C6.5 Compressors, Centrifugal Type
C6.6 Compressors, Screw Type
C6.7 Compressors, Scroll Type
C6.8 Condensers, Shell and Tube (Fresh Cooling Water
Application)
C6.9 Condensers, Shell and Tube (Sea or Brackish Cooling Water
Application)
C6.10 Condensers, Shell and Tube-General Requirement
C6.11 Condensers, Air-Cooled
C6.12 Condensers, Evaporative
C6.13 Cooling Tower
C6.14 Evaporators, Shell and Tube Water Chilling
C6.15 Evaporators, Air Cooling
C6.16 Plate Type Heat Exchanger
C6.17 Liquid Receivers (Refrigerant Recovery Unit)
C6.18 Pressure Testing
C6.19 Pump Down of System
C6.20 Refrigerant Pipe work
C6.21 Refrigeration Plant Accessories and Controls
C6.22 Roof Mounted Packaged Water Chillier/Heat Pump Plants
C6.23 Heat Recovery Chillier
C6.24 Heat Pump
C6.25 Energy Efficiency Performance
C6.26 Total Energy Heat Pump
C6.27 Automatic Condenser Tube Cleaning System
C6.28 Solar Heating System

SECTION C7 ELECTRIC MOTORS AND ELECTRICAL EQUIPMENT

C7.1 Low Voltage - General


C7.2 Low Voltage - Wiring for Refrigerated Situations
C7.3 Low Voltage - Electric Equipment
C7.4 High Voltage - Electric Equipment

Table of Contents AC_GS


Page 14 of 20 2017 Edition
SECTION C8 NOISE AND VIBRATION CONTROL

C8.1 General
C8.2 Equipment Bases
C8.3 Vibration Isolators
C8.4 Plant/Equipment Vibration Isolation
C8.5 Pipe work Vibration Isolation
C8.6 Ductwork Vibration Isolation
C8.7 Ductwork Acoustic Insulation
C8.8 Acoustic Duct lag
C8.9 Ductwork Silencers
C8.10 Acoustic Doors
C8.11 Acoustic Louvers
C8.12 Acoustic Enclosures
C8.13 Plant Room Acoustic Linings

SECTION C9 PIPE MATERIAL, VALVES, COCKS AND STRAINERS

C9.1 Automatic Air Vents


C9.2 Ball Float Valves
C9.3 Butterfly Valves
C9.4 Check Valves
C9.5 Pipe work Applications
C9.6 Plug Cocks
C9.7 Pressure Reducing Valves
C9.8 Strainers
C9.9 Specialised Control Valves
C9.10 Valve Applications
C9.11 Valves and Cocks

SECTION C10 SYSTEM MONITORING INSTRUMENT

C10.1 General
C10.2 System Static Pressure Gauges for Air Distribution Systems
C10.3 Thermometers - Air Immersion
C10.4 Thermometers - Liquid Immersion
C10.5 Pressure Gauges for Water Systems
C10.6 Pitot Static Tube
C10.7 Orifice Plate Metering

Table of Contents AC_GS


Page 15 of 20 2017 Edition
C10.8 Electromagnetic and Ultrasonic Flowmeters
C10.9 Energy Meters

SECTION C11 THERMAL INSULATION

C11.1 General
C11.2 Types of Thermal Insulation Materials
C11.3 Measures to Prevent Smoke, Noxious & Toxic Fumes
Propagation in Event of Fire
C11.4 Vapour Barriers
C11.5 Insulation Thicknesses

SECTION C12 UNITARY AIR-CONDITIONER

C12.1 General
C12.2 Equipment Suitable for Local Electricity Supply
C12.3 Selection of Air-cooled Condensers and Condensing Units
C12.4 Casing of Condensing Unit
C12.5 Compressor
C12.6 Supply Air Fan and Motor
C12.7 Cooling and Heating Coils
C12.8 Air Filter
C12.9 Air-cooled Condensers
C12.10 Electric Ductwork Heater
C12.11 Refrigerant Piping
C12.12 Condensate Drain Pipe
C12.13 Safety Control
C12.14 Operational Control
C12.15 Single Packaged Air-Conditioner
C12.16 Packaged Air-Conditioner with Remote Condenser
C12.17 Split Condensing Unit and AHU
C12.18 Variable Refrigerant Volume System
C12.19 Energy Efficiency Performance

SECTION C13 WATER HANDLING EQUIPMENT

C13.1 Fresh Water Pumps


C13.1.1 Type
C13.1.2 Materials of Construction
C13.1.3 Standards

Table of Contents AC_GS


Page 16 of 20 2017 Edition
C13.2 Saline Water Pumps
C13.2.1 Type
C13.2.2 Materials of Construction
C13.2.3 Standards
C13.3 Boiler Feed Pump
C13.4 Sump Pump
C13.4.1 Materials of Construction of Dry Pit Pumps
C13.4.2 Materials of Construction of Submersible Pumps
C13.4.3 General Requirements
C13.5 Bore Well Pumps
C13.6 Pump Base Plate
C13.7 Valves
C13.8 Vibration Isolators
C13.9 Gauges
C13.10 Drain and Vent
C13.11 Flanged Connections
C13.12 Water Filters
C13.13 Sea Water Strainers and Travelling Band Screens
C13.14 Feed and Expansion Facility
C13.15.1 General
C13.15.2 Types of Cistern and Tank
C13.15 Plate Type Heat Exchangers

PART D - INDOOR AIR QUALITY (IAQ)

D1 General
D2 Outdoor Air Quality
D3 Design Parameters of Indoor Air Quality
D4 Installation - Part B: Treatment and Conditioning Process
D5 Equipment/Materials - Part C: Treatment and Conditioning
Media
D6 Conformities of IAQ Design Objective and Compliance
D7 IAQ Assessment and Methodologies
D8 Operation and Maintenance
D9 Housekeeping and Energy Efficiency Relating to IAQ Issue
D10 Training and Licensing Requirements
D11 Certification and Registration

Table of Contents AC_GS


Page 17 of 20 2017 Edition
PART E - ENERGY EFFICIENCY AND ENERGY
CONSERVATION

E1 General
E2 Minimum Coefficient of Performance (COP) of Major Air
Conditioning and Ventilation Equipment
E3 Minimum Efficiency of Fans, Pumps and Motors
E4 Thermal Insulation
E5 Sensing Device
E6 Motion Detecting Sensing Device
E7 Devices for Enthalpy Control of Free Air Cooling
E8 Automatic Condenser Tube Cleaning System
E9 Heat Pipe Installation
E10 Solar Heating Installation
E11 Dehumidifier
E12 Outdoor Air Pre-Conditioner

PART F - ACMV SYSTEM WATER TREATMENT

F1 General
F2 Form of Water Treatment
F3 Sea Water Treatment by Electrochlorinator
F4 Sea Water Treatment by Biocides
F5 Cooling Tower/Condenser Cooling Water Treatment by
Chemical Agents
F6 Cooling Tower/Condenser Cooling Water Treatment by
Ozone
F7 Close Circuit Chilled Water or Low Pressure Hot Water
Heating Systems Treatment by Chemical Agents
F8 Water Testing Equipment
F9 Training, Operation and Maintenance Facilities
F10 Pre-treatment for Dumping of Chemical Wastes

Table of Contents AC_GS


Page 18 of 20 2017 Edition
PART G - PAINTING, FINISHING AND PROTECTIVE
TREATMENT

G1 General
G2 Number of Paint Coats Required
G3 Identification of Pipelines
G4 Schedule of Colours
G5 Machinery and Pipework
G6 Copper Pipe and Fitting
G7 Pipes and Ductwork
G8 Protection of Plant, Equipment, Pipework, etc.
G9 Protective Measures against Corrosion

PART H - INSPECTION, TESTING AND COMMISSIONING DURING


CONSTRUCTION PERIOD

SECTION H1 GENERAL REQUIREMENTS

H1.1 General
H1.2 Methods and Procedures
H1.3 Notices of Inspection, Testing and Commissioning Works
H1.4 Labour and Materials
H1.5 Inspection, Measuring and Testing Equipment
H1.6 Readiness for Inspection, Testing and Commissioning
H1.7 Type-test Certificate
H1.8 Off-site Tests / Factory Tests
H1.9 Site Tests

SECTION H2 INSPECTION

H2.1 Inspection of Materials and Equipment Delivered to Site


H2.2 Visual Inspection and Checking
H2.3 Handover Inspection

SECTION H3 TESTING AND COMMISSIONING

H3.1 General
H3.2 Procedures, Standards and Requirements
H3.3 Master Programme for Testing and Commissioning Works

Table of Contents AC_GS


Page 19 of 20 2017 Edition
H3.4 Documentation and Deliverables
H3.5 Testing and Commissioning Engineer / Specialist

PART I TRAINING, INSPECTION, ATTENDANCE, OPERATION


AND MAINTENANCE DURING MAINTENANCE PERIOD

SECTION I1 GENERAL REQUIREMENT

I1.1 General
I1.2 Completion of Outstanding and Defective Works
I1.3 Repair and Maintenance Records

SECTION I2 TRAINING TO USERS AND OPERATION AND


MAINTENANCE AGENTS

I2.1 General
I2.2 Other Training Requirements

SECTION I3 INSPECTION, ATTENDANCE, OPERATION AND


MAINTENANCE REQUIREMENTS

I3.1 Response and Attendance to Emergency and Fault Calls


I3.2 Maintenance Schedule
I3.3 Inspection during Maintenance Period
I3.4 Joint Inspection at the End of Maintenance Period
I3.5 Level One Services Mandatory Responsibilities during
Maintenance Period
I3.6 Level Two Services Specified Contractors Maintenance
Responsibilities during Maintenance Period
I3.7 Spare Parts and Special Tools

ANNEX I LIST OF TECHNICAL STANDARDS QUOTED IN THIS


GENERAL SPECIFICATION

Table of Contents AC_GS


Page 20 of 20 2017 Edition
PART A - SCOPE AND GENERAL REQUIREMENTS

SECTION A1

SCOPE OF SPECIFICATION

A1.1 INSTALLATIONS TO COMPLY WITH THIS GENERAL


SPECIFICATION

The Air-conditioning, Refrigeration, Ventilation and Central Monitoring and


Control System Installation shall comply with this General Specification which
details the intrinsic properties (including materials and workmanship) of the
Installation sin so far as it is not overridden by the Conditions, Particular
Specification, Drawings and/or written instructions of the Supervising Officer.

A1.2 SCOPE OF THE INSTALLATIONS

This General Specification, Particular Specification, Tender Equipment Schedule


and Drawings detail the performance requirements of the Installations. The
Installations to be carried out in accordance with this General Specification shall
include the installation and supply of all materials necessary to form a complete
installation including any necessary tests, adjustments, commissioning and
maintenance as prescribed and all other incidental sundry components together
with the necessary labour for installing such components, for the proper operation
of the Installations.

A1.3 TERMS AND DEFINITIONS

In this General Specification, all words and expressions shall have the meaning as
assigned to them under the Conditions unless otherwise herein. The following
words or expressions shall have the meanings assigned to them except when the
context otherwise requires: -

A/C Air-conditioning

ACB Air Circuit Breaker

A/C Contractor The Nominated Sub-contractor or the Specialist


Sub-contractor employed by the Building
Section A1 AC_GS
Page 1 of 8 2017 Edition
Contractor or the contractor directly employed
by the Employer as appropriate for the
execution of the Installations in accordance with
the Contract

ACMV Air-conditioning and Mechanical Ventilation

ACRA The Hong Kong Air-Conditioning &


Refrigeration Association Ltd.

ACS Automatic Control System

AHU Air Handling Unit

AISI American Iron and Steel Institute

ANSI American National Standards Institute

ArchSD Architectural Services Department, the


Government of the Hong Kong Special
Administrative Region

ARI Air-Conditioning and Refrigeration Institute

ASHRAE American Society of Heating, Refrigerating and


Air-conditioning Engineers, Inc.

ASME American Society of Mechanical Engineers

ASTM American Society for Testing and Materials

BAC Building Automation and Control

B&ES Building and Engineering Services Association

BS British Standards, including British Standard


Specifications and British Standard Codes of
Practice, published by the British Standards
Institution

BSB The Building Services Branch of the ArchSD,


the Government of the Hong Kong Special
Administrative Region

BS EN European Standard adopted as British Standard

Building The Contractor employed by the Employer for


Contractor the execution of the Works or the Specialist
Contractor separately employed by the
Employer to execute Specialist Works as
appropriate

Section A1 AC_GS
Page 2 of 8 2017 Edition
CAV Constant Air Volume

CCMS Central Control and Monitoring System

CFC Chlorofluorocarbon

CFR Code of Federal Regulation (Department of


Transportation, USA)

CHO Chilled Water Optimisation

CHW Chilled Water

CIBSE The Chartered Institution of Building Services


Engineers

Conditions The Conditions of Contract as defined in the


Contract. For Nominated Sub-contract works,
the Main Contract Conditions and the Sub-
contract Conditions as defined in the
Nominated Sub-contract as appropriate.

COS Change-of-state

DCE Data Circuit-terminating Equipment

DDC Direct Digital Controllers

DDC/O Direct Digital Controllers/Outstations

DIDW Double Inlet Double Width

DIN German Industry Standard

DOL Direct-On-Line Starters

DOP Di-Octal Phthalate

DTE Data Terminal Equipment

EIA Electronics Industries Association

EJMA Expansion Joint Manufacturers Association

Electrical General The General Specification for Electrical


Specification Installation in Government Buildings of the
Hong Kong Special Administrative Region
issued by the ArchSD
E&M Electrical & Mechanical

EMC Electro-magnetic Compatibility

Section A1 AC_GS
Page 3 of 8 2017 Edition
EMSD Electrical and Mechanical Services Department,
the Government of the Hong Kong Special
Administrative Region

EPD Environmental Protection Department, the


Government of the Hong Kong Special
Administrative Region

EPDM Ethylene-propylene-diene elastomer

ETD Embedded Temperature Detectors

FCC Federal Communications Commission

FCU Fan Coil Unit

FDA Food and Drug Administration, USA

FRC Fire Resistance Construction

FRP Fibreglass Reinforced Polyester

FSD Fire Services Department, the Government of


the Hong Kong Special Administrative Region

G.I. Galvanised Iron

GRP Glass Reinforced Plastics

HBC High Breaking Capacity

HCFC Hydrochlorofluorocarbon

HCS Hydrous Calcium Silicate

HEPA High Efficiency Particulate Arrestance

HFC Hydrofluorocarbon

HKIE The Hong Kong Institution of Engineers

H.V. High Voltage

IAQ Indoor Air Quality

IEC International Electrotechnical Commission

IEEE Institute of Electrical and Electronics Engineers

IET The Institution of Engineering and Technology

Section A1 AC_GS
Page 4 of 8 2017 Edition
IGBTS Insulated Gated Bipolar Transistors

IIAR International Institute of Ammonia


Refrigeration

IMO International Maritime Organisation

Installations The work or services for the Air-conditioning,


Refrigeration, Ventilation and Central
Monitoring and Control System Installation
forming parts of the Works to be installed,
constructed, completed, maintained and/or
supplied in accordance with the Contract and
includes Temporary Works

I/O Input / Output

IP Index of Protection

ISO International Organisation for Standardization

ISO SQL International Organisation for Standardization,


Database Language SQL

KEMA N.V. tot Keurig van Elekrotechnische


Materialmen in Arnhem, the Netherlands

LAN Local Area Network

LCD Liquid Crystal Display

LED Light Emitting Diode

Lon talk Echelon Corporation Lon talk Protocol

LPHW Low Pressure Hot Water

LSOH Low Smoke Zero Halogen

L.V. Low Voltage

MCC Motor Control Centre

MCR Maximum Continuous Rating

MICS Mineral Insulated Copper Sheathed

NAIMA North American Insulation Manufacturers


Association

NaOCl Sodium Hypochlorite

Section A1 AC_GS
Page 5 of 8 2017 Edition
NaOH Sodium hydroxide

NC Noise Criteria

NEMA National Electrical Manufacturers Association

NES Naval Engineering Specification

NFPA National Fire Protection Association

NPSH Net Positive Suction Head

OD Outside Diameter

ODBC Open Database Connectivity

O&M Operation and Maintenance

or equivalent Means internationally recognised standards


standards acceptable to the Supervising Officer having
similar requirements and specification as
regards to the type of construction, functions,
performance, general appearance and standard
of quality of manufacture and approved by the
Supervising Officer

ORP Oxidationreduction Potential

OSHA Occupational Safety and Health Administration,


USA

Particular The specifications drawn up specifically for the


Specification Installations of a particular project

PAU Primary Air Handling Unit

PCP Polychloroprene

PFAC Pulverised Fuel Ash Cement

PID Proportional Integral Derivative

PLC Programmable Logic Controller

PN Practice Note

POT Portable Operator Terminal

Proprietary The phrase or alternative products or


brand name material shaving equivalent functions or

Section A1 AC_GS
Page 6 of 8 2017 Edition
products or performance is deemed to be included
materials wherever products or materials are
specified by proprietary brand names in the
Contract. Alternative products or materials
of different brands or manufacture having
equivalent functions or performance may
be submitted for the consideration of the
Supervising Officer.

PSTN Public Switched Telephone Network

PTFE Polytetrafluoroethylene

PTTA Partially Type-Tested Assemblies

PVC Polyvinyl Chloride

PWM Pulse Width Modulation

RAD Rapid Application Development

RAM Random Access Memory

RH Relative Humidity

r.m.s. Root Mean Square

RTC Real Time Clock

RTD Resistance Temperature Detector

SCR Silicon Controlled Rectifier

SF6 Sulphur Hexafluoride

SMACNA Sheet Metal and Air-conditioning


Contractors National Association, USA

SRC Sulphate Resisting Cement

Supervising The Supervising Officer or the


Officer Maintenance Surveyor defined in the
Contract as appropriate

TBC Total Bacteria Count

TEFC Totally Enclosed Fan Cooled

Tender The Contractors tender for the Contract or


the Nominated Sub-contractors tender for

Section A1 AC_GS
Page 7 of 8 2017 Edition
the Nominated Sub-contract as appropriate

TIA Telecommunication Industry Association

TL Transmission Loss

UL Underwriters Laboratories

UPS Uninterrupted Power Supply

UPVC Unplasticised Polyvinyl Chloride

UV Ultra-violet

VAV Variable Air Volume

VDE Verband Deutscher Elektrotechniker

V/F Voltage/Frequency

VOC Volatile Organic Compound

VRV Variable Refrigerant Flow

VSD Variable Speed Drive

WSD Water Supplies Department, the


Government of the Hong Kong Special
Administrative Region

XLPE Cross-Linked Polyethylene

XLPE/SWA/P Cross-linked polyethylene insulated, PVC-


VC sheathed, galvanised steel wire armoured
and PVC covered

A1.4 SINGULAR AND PLURAL

Words importing the singular only also include the plural and vice versa where
the context requires.

Section A1 AC_GS
Page 8 of 8 2017 Edition
SECTION A2

STATUTORY OBLIGATIONS AND OTHER REGULATIONS

A2.1 STATUTORY OBLIGATIONS AND OTHER REQUIREMENTS

The Installations shall conform in all respects with the followings: -

A2.1.1 Statutory Obligations

All Enactments and Regulations, in particular, the A/C Contractors


attention is drawn to the followings:

(a) Building (Ventilating Systems) Regulations under Buildings


Ordinance (Cap. 123);

(b) Electricity Ordinance (Cap. 406), and other subsidiary


legislation made under the Ordinance;

(c) Fire Service (Installations and Equipment) Regulations, Fire


Services Ordinance (Cap. 95), and other subsidiary legislation
made under the Ordinance;

(d) Noise Control Ordinance (Cap. 400), and other subsidiary


legislation made under the Ordinance;

(e) Water Pollution Control Ordinance (Cap. 358), and other


subsidiary legislation made under the Ordinance;

(f) Air Pollution Control Ordinance (Cap. 311), and other


subsidiary legislation made under the Ordinance;

(g) Ozone Layer Protection Ordinance (Cap. 403), and other


subsidiary legislation made under the Ordinance;

(h) Waste Disposal Ordinance (Cap. 354), and other subsidiary


legislation made under the Ordinance;

(i) Environmental Impact Assessment Ordinance (Cap. 499), and


other subsidiary legislation made under the Ordinance;

(j) Waterworks Ordinance (Cap. 102), and other subsidiary


legislation made under the Ordinance;

(k) Dangerous Goods Ordinance (Cap. 295), and other subsidiary


legislation made under the Ordinance;

(l) Places of Public Entertainment Ordinance (Cap. 172), and


other subsidiary legislation made under the Ordinance; and

Section A2 AC_GS
Page 1 of 4 2017 Edition
(m) Buildings Energy Efficiency Ordinance (Cap. 610), and other
subsidiary legislation made under the Ordinance.

(n) Energy Efficiency (Labelling of Products) Ordinance (Cap.


598)

(o) Fire Safety (Buildings) Ordinance (Cap. 572)

A2.1.2 Other Requirements

(a) Fresh Water Cooling Towers Scheme (FWCT Scheme)


published by the EMSD;

(b) Code of Practice for Fresh Water Cooling Towers published


by the EMSD;

(c) Code of Practice for the Electricity (Wiring) Regulations


published by the EMSD;

(d) Codes of Practice for Minimum Fire Service Installations and


Equipment and Inspection, Testing and Maintenance of
Installations and Equipment published by the FSD;

(e) Requirements and Circular Letters issued by the FSD;

(f) Code of Practice for Energy Efficiency of Building Services


Installation issued by the EMSD, hereinafter referred as the
Building Energy Code or BEC;

(g) General Specification for Electrical Installation in Government


Buildings of the Hong Kong Special Administrative Region,
issued by the ArchSD;

(h) General Specification for Fire Service Installation in


Government Buildings of the Hong Kong Special
Administrative Region, issued by the ArchSD;

(i) Design Manual: Barrier Free Access 2008 published by the


Buildings Department, the Government of the HKSAR;

(j) Code of Practice for Prevention of Legionnaires' Disease


issued by Prevention of Legionnaires' Disease Committee, the
Government of the HKSAR;

(k) Codes of Practice issued by the following international


institutions: -

- American National Standard Institute


- Air-conditioning and Refrigeration Institute
- American Society of Mechanical Engineers
- American Society for Testing and Materials

Section A2 AC_GS
Page 2 of 4 2017 Edition
- Committee for European Normalisation
- The Institute of Electrical and Electronic Engineers
- International Organisation for Standardization
- Japanese International Standard
- National Fire Protection Association;

(l) The Supply Rules and other requirements issued by the


relevant local electricity supplier and water authority;

(m) Technical Memorandum to issue Air Pollution Abatement


Notice to control Air Pollution from Stationary Processes,
issued by EPD;

(n) Technical Memorandum for the Assessment of Noise from


Places other than Domestic Premises, Public Places or
Construction Sites, issued by EPD;

(o) Code of Practice on the Handling, Transportation and Disposal


of Asbestos Waste, issued by EPD;

(p) Code of Practice on the Packaging, Labelling and Storage of


Chemical Wastes, issued by EPD;

(q) Technical Memorandum - Standards for Effluents Discharged


into Drainage and Sewerage Systems, Inland and Coastal
Waters, issued by EPD;

(r) Technical Memorandum on Environmental Impact


Assessment Process, issued by EPD; and

(s) Testing and Commissioning Procedure for Air-conditioning,


Refrigeration, Ventilation and Central Monitoring & Control
System Installation in Government Buildings of the Hong
Kong Special Administrative Region, issued by ArchSD.

A2.1.3 Safety Requirements

(a) Occupational Safety and Health Ordinance (Cap. 509), and


other subsidiary legislation made under the Ordinance;

(b) Factories and Industrial Undertakings Ordinance (Cap. 59),


and other subsidiary legislation made under the Ordinance;

(c) Public Health and Municipal Service Ordinance (Cap. 132),


and other subsidiary legislation made under the Ordinance;

(d) Construction Sites (Safety) Regulations, Factories and


Industrial Undertakings Ordinance (Cap. 59); and

(e) Construction Site Safety Manual issued by the Development


Bureau, the Government of the HKSAR.
Section A2 AC_GS
Page 3 of 4 2017 Edition
A2.1.4 Technical Standards

BS, BS EN, ISO Standards, IEC Standards and Codes of Practice, etc.
shall be deemed to include all amendments, revisions and standards
superseding the standards listed herein, which are published before
the date of first tender invitation for the Contractor the Nominated
Sub-contract (as appropriate) unless otherwise specified.

A summary of technical standards quoted in this General


Specification to which the Installations shall comply is listed in
Annex I.

A2.2 CASE OF CONFLICT

The documents forming the Contract are to be taken as mutually explanatory of


one another but in case of ambiguities or discrepancies the same shall be dealt
with in accordance with the Conditions.

A2.3 MECHANICAL FIRE SERVICE INSTALLATION

Mechanical fire service installation shall include ventilation/air conditioning


control system, pressurisation of staircases system and smoke extraction system.

The A/C Contractor shall be in the List of Approved Suppliers of Materials and
Specialist Contractors for Public Works in the Category of Air-conditioning
Installation to carry out works for the mechanical ventilation system, smoke
extraction system and pressurisation of staircases system in the buildings and shall
also be a Registered Fire Service Installation Contractor of relevant Class
registered with the FSD.

The A/C Contractor shall employ a Registered Professional Engineer in Hong


Kong under the Engineers Registration Ordinance (Cap. 409) in Fire, Building
Services, Mechanical or Electrical discipline (or equivalent approved professional
qualification) with proof of experience of at least 3 years in relevant design works,
who emphasises on and is specialised in mechanical ventilation and air handling
installation to the approval of the Supervising Officer to carry out the design and
supervision of the submission, installation and testing of the pressurisation of
staircases system and smoke extraction system. The professional status and
qualifications of the Registered Professional Engineer shall also be acceptable by
FSD and the Supervising Officer.

Details of the above systems can be referred to relevant section of General


Specification for Fire Service Installation in Government Buildings of HKSAR.

Section A2 AC_GS
Page 4 of 4 2017 Edition
SECTION A3

EXECUTION OF INSTALLATIONS

A3.1 THE INTERNATIONAL SYSTEM OF UNITS (SI)

The International System of Units of weights and measures shall be used for all
materials, equipment and measurements.

A3.2 PROGRAMME OF INSTALLATIONS

The A/C Contractor shall submit to the Supervising Officer a detailed programme
of the Installations within 4 weeks from the acceptance of his Tender showing the
intended method, stages and order of work execution in coordination with the
building construction programme, together with the duration he estimated for each
and every stage of the Installations. The programme shall include at least the
following: -

(a) Dates for the placement of orders for equipment and materials;

(b) Expected completion dates for builders work requirements, i.e. when
work site needs to be ready;

(c) Delivery dates of equipment and materials to the Site;

(d) Dates of commencement and completion of every stage of the


Installations in line with the building construction programme, i.e. each
floor level and/or zone area;

(e) Dates of documents/drawings submissions to relevant Government


departments to obtain the necessary approvals;

(f) Dates of requirement of temporary facilities necessary for testing &


commissioning, e.g. electricity supply, water and town gas;

(g) Dates of completion, testing and commissioning; and

(h) Short term programmes showing the detailed work schedules of coming
weeks and months shall also be provided to the Supervising Officer.
Programmes shall be regularly updated to reflect the actual progress and
to meet theA/C Contractors obligations under the Contract.

In addition, detailed submission schedules for installation drawings, equipment


and testing and commissioning shall be submitted to the Supervising Officer for
approval. The formats and information to be included in the schedules shall be as
directed by the Supervising Officer.

Section A3 AC_GS
Page 1 of 12 2017 Edition
A3.3 BUILDERS WORK

All builders work including openings or holes through building structure or


partition walls; trenches, ducts and cutting; and all plinths, concrete bases,
supports, ducts, etc. required for the Installations will be carried out as part of the
building works by the Building Contractor at the expense of the Employer
provided that the A/C Contractor has submitted full details of such requirements
within a reasonable time to the Supervising Officer for approval, so that due
consideration may be given before the Building Contractor commences the
building works in accordance with the building programme in the areas concerned.
After obtaining the said approval of the Supervising Officer, the A/C Contractor is
required to mark out at the relevant locations of the Site the exact positions and
sizes of all such works and to provide detailed information of such works to the
Building Contractor to facilitate him to carry out the builders works as the Works
proceed.

All "cutting-away" and "making-good" as required to facilitate the A/C


Contractors works will be carried out by the Building Contractor, except for
minor provisions required for the fixing of screws, raw plugs, redhead bolts, etc.
which shall be carried out by the A/C Contractor. The A/C Contractor shall mark
out on Site and/or supply drawings of all "cutting-away" to the Building
Contractor within a reasonable time.

All expenses properly incurred and losses suffered by the Employer as a result of
the A/C Contractors failure to comply with the above requirements are
recoverable by the Employer from the A/C Contractor as a debt under the
Contract or via the Building Contractor as if it is a debt liable to the Building
Contractor under the Sub-contract as appropriate.

The A/C Contractor shall ensure that such works are essential for the execution of
the Installations. In the event that any of such works is proved to be non-essential,
unnecessary and/or abortive, the A/C Contractor shall bear the full cost of such
works including but not limited to any unnecessary or incorrect cutting-away and
making-good and shall reimburse the Employer for all cost incurred in this
connection are recoverable by the Employer from the A/C Contractor as a debt
under the Contract or via the Building Contractor as if it is a debt liable to the
Building Contractor under the Sub-contract as appropriate.

Upon completion of the builders works by the Building Contractor, the A/C
Contractor shall forthwith check and examine that all builders works so executed
have been completed in accordance with his requirements. If at any time, it
becomes apparent to the A/C Contractor that any builders works completed by
the Building Contractor does not comply with his requirements in any respect
whatsoever, the A/C Contractor shall forthwith give notice in writing to the
Supervising Officer and specify in details the extents and effects of such non-
compliance in that notice. The A/C Contractor is deemed to have satisfied with
the builders works after a period of 14 days from the date of completion of the
builders works if the above notice is not served to the Supervising Officer within
such period. All additional expenditure properly incurred and all loss suffered in
this connection by the Employer in having such works re-executed and rectified
shall be recoverable by the Employer from the A/C Contractor as a debt under the

Section A3 AC_GS
Page 2 of 12 2017 Edition
Contract or via the Building Contractor as if it is a debt liable to the Building
Contractor under the Sub-contract as appropriate.

A3.4 COORDINATION OF INSTALLATIONS

The A/C Contractor shall coordinate the Installations with those works of the
Building Contractor and any other contractors and sub-contractors of the Building
Contractor.

The A/c Contractor shall note that the Drawings supplied to him only indicate the
approximate locations of the Installations. He shall make any modification
reasonably required of his programme, work sequence and physical deployment
of his work to suit the outcome of work coordination or as necessary and ensure
that all cleaning, adjustment, test and control points are readily accessible while
keeping the number of loops, cross-overs and the like to a minimum.

The A/C Contractor shall pay particular attention to the building works
programme and shall plan, coordinate and programme his works to suit and
adhere to the building works in accordance with the building programme.

Any significant problems encountered during the coordination work, which are
beyond the A/C Contractors control, shall promptly be reported to the
Supervising Officer.

A3.5 COOPERATION WITH OTHER CONTRACTORS

The A/C Contractor shall cooperate at all times with the Building Contractor and
all other contractors and sub-contractors of the Building Contractor in order to
achieve efficient workflow on the Site and keep the Site in a clean and tidy
condition.

Any significant problems beyond the A/C Contractors control shall promptly be
reported to the Supervising Officer.

A3.6 SITE SUPERVISION

The A/C Contractor shall keep on the Site a competent and technically qualified
site supervisor to control, supervise and manage all his Installations on Site. The
site supervisor shall be vested with suitable powers to receive instructions from
the Supervising Officer and his Representative.

The site supervisor shall be technically competent and have adequate site
experience for the Installations. The qualified and competent site supervisor shall
have minimum 5 years on site experience for similar type of installation works.
The A/C Contractor shall also refer to the Particular Specification for other
specific requirements, if any, on site supervision.

Approval by the Supervising Officer shall be obtained prior to the posting of the
site supervisor on Site. The A/C Contractor shall immediately replace the site

Section A3 AC_GS
Page 3 of 12 2017 Edition
supervisor whose experience, skill or competency is, in the opinion of the
Supervising Officer, found to be inadequate for the particular work.
All tradesmen must be experienced in the trade and the work carried out shall be
consistent with good practice in Hong Kong and to the satisfaction of the
Supervising Officer. In this connection, the A/C Contractors attention is drawn
to the Special Conditions of Contract under the Contract for the requirements
relating to Qualified Tradesmen/Qualified Skilled Workers and Intermediate
Tradesmen/Qualified Semi-Skilled Workers.

The A/C Contractor shall also employ a full time competent foreman on Site for
each trade. All trade foremen shall be registered tradesmen/skilled workers of the
relevant trade.

A3.7 SAMPLE BOARD

Within 6 weeks of the acceptance of his Tender and prior to the commencement
of the Installations, the A/C Contractor shall submit to the Supervising Officer for
approval a sample board of essential components proposed to be used in the
Contract. However, the A/C Contractor may request the Supervising Officer in
writing for a longer period for the submission, if 6 weeks are practically
insufficient.

Items displayed shall be deemed to be adequate for the Installations unless


otherwise clearly indicated. Each sample, with clear numbering and labelling,
shall be firmly fixed onto a rigid wooden or metal board. A list shall also be
affixed on the sample board to show the item description, make and brand,
country of origin and locations of installation (if not generally used). Samples
rejected by the Supervising Officer shall be replaced as soon as possible. Upon
approval of all items, the Supervising Officer will endorse the list on the sample
board and the A/C Contractor shall deliver the board to the site office of the
Supervising Officers Representative for reference.

The board shall contain samples of all "compact" sized materials and accessories
to be used in the Installations. Written approval of all samples and technical
details shall be obtained from the Supervising Officer before commencement of
any installation work.

In the context of this General Specification the term "compact" means any item
that will fit into a 300 mm cube.

The following items shall be included in the sample board as a minimum.

(a) Conduit and accessories;

(b) Trunking and accessories;

(c) Cable and accessories;

(d) Ductwork and accessories;

(e) Fire damper;

Section A3 AC_GS
Page 4 of 12 2017 Edition
(f) Refrigerant pipework;

(g) Vibration isolator;

(h) Acoustic and thermal insulation;

(i) Valves; and

(j) Automatic air vent.

Additional items may be required by the Supervising Officer and/or specified in


the Particular Specification.

A3.8 ADVICE OF ORDER PLACED

The A/C Contractor shall submit copies of all orders placed for major items of
equipment and materials to the Supervising Officer for record.

A3.9 RECORD OF MATERIALS DELIVERY

All materials and equipment delivered to Site shall be accurately listed and
recorded in the site record books maintained by the Supervising Officers
Representative on Site. Such materials and equipment shall not be removed from
Site without the prior approval of the Supervising Officer in writing.

Where the Building Contractor is in overall control of the Site, the Building
Contractor may also be required to record details of all incoming/outgoing
materials and equipment. In this case, the A/C Contractor shall comply with the
Building Contractors arrangements.

The A/C Contractor shall print the major technical details on equipment/materials
or supporting documents (e.g. delivery note), or else submit a written declaration
to confirm compliance of the equipment/materials with the approved technical
details so as to facilitate checking of equipment/materials delivered on site.

A3.10 PROTECTION OF MATERIALS AND EQUIPMENT

Unless the responsibility is clearly defined in the Contract that the protection on
Site for delivered equipment, materials and installations is solely by other
contractors, the A/C Contractor shall be responsible for the safe custody of all
materials and equipment as stored or installed by him. In addition, the A/C
Contractor shall protect all work against theft, fire, damage or inclement weather
and carefully store all materials and equipment received on Site but not yet
installed in a safe and secure place unless otherwise specified.

All cases of theft and fire must immediately be reported to the police, the Building
Contractor, the Supervising Officer and the Supervising Officers Representatives
on Site with full details.

Section A3 AC_GS
Page 5 of 12 2017 Edition
Where necessary the A/C Contractor shall provide lockable steel container or
other equally secure enclosures placed within a securely fenced-in compound
provided by the Building Contractor on Site for the storage of materials and
equipment.

The A/C Contractor shall co-ordinate and arrange with the Building Contractor
who shall provide clean, reasonably finished and lockable secure accommodation
for the storage of sensitive and/or expensive items before installation.

If there is no Building Contractor, all the storage facilities and spaces shall be
provided by the A/C Contractor.

A3.11 LABEL

A3.11.1 Labels and Related Instruction

In order to make cross reference to the


Operation/Maintenance/Service Manuals and Schematic Drawings,
etc., the A/C Contractor shall provide labels for marking all valves,
pipework, filtration tanks, fuses, terminals, lamps, switches, handles,
keys, instruments, gauges, control and other equipment, etc. and
elsewhere to facilitate maintenance or as directed by the Supervising
Officer with engraved multi-layer formica or similar material.
Wording shall be submitted to the Supervising Officer for approval
before manufacture.

Instructions for oiling and/or greasing of all motors, etc. shall be


attached to the relevant greasing or oiling points.

All labels shall be of adequate size as to give clearance between


lettering and fixings to ensure an aesthetic arrangement on
completion. Pipeline labels shall generally be not smaller than 100
mm x 20 mm. Where applicable, labels shall be fixed utilising non-
ferrous round head bolts and nuts or woodscrews. Adhesives or self-
tapping screws are not acceptable.

For pipelines or valves, where applicable, labels shall be fixed by


means of a key ring attached to the upper corner of the pipe mounting
bracket or the hand wheel of valves. The labels shall be suspended
from brass or stainless steel chain loops over the relevant pipe.

The A/C Contractor shall submit a schedule for all labels, notices,
identifications and instructions for the Supervising Officers approval
prior to order and installation. The information of the schedule shall
include the description of the items, height and font type of the text,
dimensions of the labels and material used.

All English lettering used on labels shall be "Bold" capitals (except


otherwise directed) with black letters on white labels for normal
purposes. Where special colours or details are required these shall be
as specified or directed.

Section A3 AC_GS
Page 6 of 12 2017 Edition
All labels and instructions shall be in English complete with
translation in Chinese characters. The Chinese translations shall be
referred to the Glossaries of Terms Commonly Used in Government
Departments issued by Civil Service Bureau of the Government of
the HKSAR. Sample of label and notice shall be submitted to the
Supervising Officer for agreement. Heights for the English lettering
shall be as follows with that for Chinese characters to match: -

(a) Pipelines, valves, motor valves, fans, doors, etc.8 mm;

(b) Greasing instructions for motors, fan bearings, etc.6 mm;

(c) Thermostats, sensors, thermometers, pressure 3 mm


gauges, general instructions, etc.

For electrical panels or other items, lettering shall be: -

- Black on white for normal purposes;


- Red letters on white where connected to essential supply; and
- Green letters on white where operated by direct current.

For electrical components, the letter heights shall be as follows: -

(a) Identifying equipment in cabinets3 mm;

(b) Door cabinets8 mm;

(c) Switches & indicators on panel faces3 mm

Where proprietary type, rail mounted terminals are utilised in


electrical cabinets, the manufacturers "clip-in" identification tabs
shall be used.

A3.11.2 Coded Labels

Where appropriate, items such as valves, sensing points, etc. may also
be identified by "Codes" on the labels which shall relate to the items
as detailed on plant room mounted diagrammatic drawings or the
mimic diagrams on operational control panels. At the diagram or
control panels, the function of each coded item shall also be detailed.
Such systems of labelling and related diagrams shall be approved by
the Supervising Officer before implementation.

Valves etc. required for emergency shutdown purposes must under all
circumstances be fully detailed at the valve.

Section A3 AC_GS
Page 7 of 12 2017 Edition
A3.12 WARNING NOTICE

Warning notices shall be provided as required by the Electricity Ordinance (Cap.


406) and the Code of Practice for the Electricity (Wiring) Regulations (Cap.
406E). In addition, the following warning notices in English and Chinese shall be
provided at the appropriate positions: -

(a) A label having minimum size of 65 x 50 mm marked with the words


DANGER - HIGH VOLTAGE in red lettering not less than 5 mm high
to be fixed on every container or enclosure of equipment for operating at
voltages exceeding "Low voltage"; and

(b) A label to be fixed in such a position that any person may gain access to
any moving parts of an item of equipment or enclosure will notice or be
warned of such a danger.

A3.13 GUARD AND RAILING FOR MOVING AND ROTATING PARTS OF


EQUIPMENT

Everything moving or rotating parts of equipment shall be provided with an


approved guard and railing complying with the Factories & Industrial
Undertakings (Guarding and Operation of Machinery) Regulations, (Cap. 59Q),
together with any amendments made thereto.

Guards shall be rigid and of substantial construction and shall consist of heavy
mild steel angle frames, hinged and latched with either heavy galvanised mild
steel wire crimped mesh securely fastened to frames or galvanised sheet metal of
1.2 mm minimum thickness. All apertures shall be such that finger access to
dangerous part is not possible. All sections shall be bolted or riveted. Railings
shall be made of 32 mm dia. galvanised mild steel pipe and railing fittings.

(a) Temporary Guards

During the execution of work, the A/C Contractor shall ensure that all moving
parts are adequately guarded by temporary guards.

Adequate temporary guard railings etc. around dangerous floor/wall openings in


the vicinity of any work for the protection shall be provided.

For the safety of workers, guard railings etc. are to be provided by the Building
Contractor, but in case they are not provided, the A/C Contractor shall
immediately report the matter to the Supervising Officer.

(b) Permanent Guards on Plant

Unless specified otherwise in the Particular Specification, the A/C Contractor


shall provide removable guards or railing for protection from moving or rotating
parts. The design and construction of safety guards for moving parts such as belt
drives shall conform to the requirements laid down in the Factories & Industrial
Undertakings (Guarding and Operation of Machinery) Regulations.

Section A3 AC_GS
Page 8 of 12 2017 Edition
A3.14 SERVICE CONDITION

The following service conditions shall apply to material and equipment

(a) Climate : Hong Kong (tropical);

(b) Ambient temperature : Peak 5oC to +40 oC (continuously 4 hours)


Average 0 oC to +35 oC (over 24 hours);

(c) Altitude : up to 2000 m above sea level; and

(d) Relative humidity : 99% maximum.

A3.15 VOLTAGE COVERED BY THIS GENERAL SPECIFICATION

Unless otherwise specified, all apparatus, equipment, materials and wiring shall
be suitable for use with a 3-phase and neutral, 4-wire, 380/220V6%, 50 Hz 2%.

A3.16 MATERIAL AND EQUIPMENT

A3.16.1 Materials and Equipment Standards

All materials, equipment and installations work shall be carried out


by adoption of the best available quality materials and workmanship
and shall, where applicable, comply with the latest edition of the
appropriate standards and/or codes of practice issued by the relevant
international Institutes and Standards and as specified in this General
Specification which are published before the date of first tender
invitation for the Contract or the Nominated Sub-contract as
appropriate. This requirement shall be deemed to include all
amendments to these standards and codes up to the date of tendering.

The standards shown in brackets for the materials and equipment in


this General Specification are also considered as acceptable standards
for the respective materials and equipment.

When material or equipment complying with other standards that are


not specified in this General Specification, the A/C Contractor shall
satisfy the Supervising Officer that the quality of the material and
equipment offered is equal to or better than that specified in this
General Specification.

A3.16.2 Compatibility of Materials and Equipment

Where different components of equipment are interconnected to form


a complete system, their characteristics of performance and capacities
shall be matched in order to ensure efficient, economical, safe and
sound operation of the complete system.

Section A3 AC_GS
Page 9 of 12 2017 Edition
A3.16.3 Equipment Catalogues and Manufacturers Specifications
The A/C Contractor shall submit catalogues and manufacturer's
specification of the proposed equipment for the examination and
approval of the Supervising Officer in writing before any equipment
is ordered.

Equipment catalogue and manufacturer's specification related to


proposed items of equipment shall be specific and shall include all
information necessary for the Supervising Officer to ascertain that the
equipment complies with the Specification and Drawings. Data and
sales catalogue of a general nature are not acceptable. Unless agreed
by the Supervising Officer in writing, all data and catalogues
submitted must be in English and in pure SI units i.e. mm, m, kPa,
m/s, Hz, kW, l/s, etc.

A3.16.4 Equipment Deviations

Subsequent to the acceptance of his Tender, and only in exceptional


circumstances where it is demonstrated in writing by the A/C
Contractor that the original equipment offered cannot be obtained, the
Supervising Officer may, subject to the Conditions, consider and
approve, in writing, alternative equipment and materials proposed by
the A/C Contractor provided always that these equipment and
materials are fully in compliance with the relevant Specifications and
Drawings and do not impose any additional contractual or financial
liabilities onto the Employer.

A3.16.5 Selection of Equipment

Selection of equipment shall be based on this the Specification and


the technical data contained in the Drawings for a particular
installation.

Where items of equipment are interconnected to form an integral part


of the complete Installations, their characteristics of performance and
capacities shall be so matched as to give safe, reliable, efficient and
economical operation of the complete Installations.

A3.16.6 Manufacturers Technical Support in Hong Kong

All equipment listed in the Equipment Schedule shall be supplied


through authorised agencies of the manufacturers in Hong Kong or
through the Hong Kong offices of the manufacturers. These local
agencies or offices shall have adequate technical staff to provide pre-
sale and after-sale services to the A/C Contractor. Unless otherwise
specified in the Particular Specification, equipment supplied directly
by the manufacturers, which do not have local agencies or offices will
not be accepted. Spare parts should also be available in the local
market easily.

Section A3 AC_GS
Page 10 of 12 2017 Edition
A3.17 WORKMANSHIP

A3.17.1 Tools and Instruments

Proper tools shall be used for the works. Adequate and accurate
testing/measuring instruments shall be used to demonstrate
compliance of the Installations with the relevant specifications and
regulations. The Supervising Officer has the right to stop any work in
which the correct tools and/or instruments are not used.

Instruments used for acceptance tests shall be calibrated at a yearly


interval unless otherwise as required in the Contract for a particular
project.

A3.17.2 Workmanship Standard

The installation works shall be in line with the good practice accepted
by the local industry and verified by commissioning and testing
results.

The installation works shall be in compliance with the Specification


and Drawings.

The Installations shall be in compliance with the statutory


requirements as specified in Section A2 of this General Specification
in respect of labour safety, fire safety, structural safety, electrical
safety and environmental protection.

Apart from those requirements as stipulated in this General


Specification and other statutory requirements, due care shall be taken
to secure public safety and health both during the execution of the
works and in the selection of equipment and materials for the
Installations.

A3.17.3 Space for Plant

The A/C Contractor shall ensure that all plants, materials and
equipment supplied by him can be accommodated and installed
within the spaces as generally shown on the Drawings with adequate
access and space for maintenance of all items supplied.

The A/C Contractor shall also ensure that access to plant is adequate
to allow for its removal and/or ultimate replacement. Where this is
considered not possible or necessary the Supervising Officer shall be
consulted for alternative arrangements.

A3.17.4 Water Proofing

Where any work requires piercing waterproofing layers or structures,


the method of installation must have prior approval, in writing, from
the Supervising Officer.

Section A3 AC_GS
Page 11 of 12 2017 Edition
Unless otherwise specified or instructed, the A/C Contractor shall
provide all necessary sleeves, puddle flanges, caulking and flashing
as appropriate to make these penetrations absolutely watertight.

A3.17.5 Quality Assurance Standards

All materials and equipment shall be manufactured by factories with


acceptable quality assurance procedures. Factories having ISO
9001:2008/Corr1:2009 certification are deemed to have acceptable
quality assurance procedures. Other similar quality assurance
standards may be accepted by the Supervising Officer on their
individual merits. Details of such other quality assurance standards
shall be submitted with the Equipment Schedule.

A3.18 SURVEYS AND MEASUREMENTS

The A/C Contractor shall relate all horizontal and vertical measurements taken
and/or applied, to establish bench marks such as design drawing grid lines,
finished floor levels, etc. and shall thus establish satisfactory lines and levels for
all works.

All works shall be installed to these established lines and levels and the A/C
Contractor shall verify all measurements on Site and check the correctness thereof
as related to the Installations.

Primary bench base line, datum level, horizontal reference grid, secondary grid
and transferred bench mark on each structural level will be provided by the
Building Contractor. The A/C Contractor shall co-ordinate with the Building
Contractor to obtain all necessary datum and reference grids prior to their surveys
and measurements.

Section A3 AC_GS
Page 12 of 12 2017 Edition
SECTION A4

DRAWINGS AND MANUALS

A4.1 DRAWINGS IN ELECTRONIC FORMAT

The A/C Contractor shall provide drawings in electronic format as required in the
following clauses. These drawings shall conform to the latest version of CAD
Standard for Works Projects (CSWP) as posted in the website of the Development
Bureau and in accordance with the latest version of CAD Manual for the ArchSD
Projects. Should any technical conflict between the CSWP and the CAD Manual
arise, the CSWP shall take precedence.

A4.2 INSTALLATION DRAWINGS

A4.2.1 Drawing Submission Schedule

The A/C Contractor shall submit a detailed installation drawing


submission schedule and programme to the Supervising Officer. The
A/C Contractor shall allow reasonable time in the programme for
vetting of the installation drawings by the Supervising Officer and for
drawing resubmissions as necessary.

The A/C Contractor shall submit to the Supervising Officer a


comprehensive Submission Schedule of installation drawings and
builders work drawings within 2 weeks after the acceptance of
Tender, taking into account of the overall programme of the
Installations including any Specialist Works and works by the utility
undertakings. No equipment shall be delivered to the Site and no
work shall be executed until the installation drawings have been
approved by the Supervising Officer. The A/C Contractor shall
ensure that the installation drawings and builders work drawings are
progressively submitted in accordance with the approved
Submission Schedule.

The A/C Contractor shall provide at least 6hard copies and one
electronic copy, unless otherwise specified in the Contract or the Sub-
contract as appropriate, of the approved installation drawings to the
Supervising Officer for distribution.

Unless otherwise indicated or instructed, the A/C Contractor shall, in


the stated or in adequate time before each section of the work
proceeds, prepare, and submit for acceptance by the Supervising
Officer, detailed installation drawings and/or shop drawings (which
may also be referred to as working drawings) to demonstrate how
they propose to install the works. These drawings shall be fully
dimensioned and shall be based on the basic intentions of the
Drawings.

Installation drawings and shop drawings in this context shall mean the

Section A4 AC_GS
Page 1 of 10 2017 Edition
drawings of items to be constructed by the A/C Contractor at a
workshop away from the Site.

A4.2.2 Size of Installation Drawings

Drawings submitted by the A/C Contractor shall only be of standard


sizes from A0 to A4 or B1 size as stipulated in ISO 5457:1999/Amd
1:2010.

A/C Contractors installation drawings and/or shop drawings shall be


prepared to such scales that will clearly show all necessary details.

A4.2.3 Contents of Installation Drawings

In accordance with the provisions of this General Specification and as


stated elsewhere in the contract documents, the installation drawings
must incorporate details of the actual plant and equipment items as
approved by the Supervising Officer.

The A/C Contractor shall ensure all installation drawings are accurate
representation of the Installations, before submitting them to the
Supervising Officer. All installation drawings shall be fully
dimensioned and suitably scaled showing construction, sizes, weights,
arrangements, operating clearances and performance characteristics.

(a) "Installation drawings" shall generally include, but not limited


to, the following: -

- Symbols and notations same as and compatible with the


Employers own Contract Drawings standard;

- Complete layout/assemblies including all necessary


minor items and accessories;

- Positions of all fixings, hangers and supports;

- Maintenance spaces for all withdrawable items, such as


coils, heater elements, thermometers, thermostats, fan
shafts and fan blowers, cleaning and replacement of
tubes, removal of guards, etc.;

- Positions & sizes of all test holes, test pockets,


thermostat pockets, thermometer pockets, bends and
fittings, clearances to allow for the removal of inserted
equipment where applicable;

- Outline of insulation and clearances to allow for


application thereof;

- Outline of valve and similar insulation boxes and the


clearances to be allowed for their removal thereof; and

Section A4 AC_GS
Page 2 of 10 2017 Edition
- Lifting points and safe working weights of each item.
Note: These may be shown on separate drawings, if
necessary, to avoid confusion.

(b) Ductwork Fabrication and Installation Drawings

The A/C Contractor shall, prior to the commencement of any


ductwork manufacture, submit to the Supervising Officer for
technical appraisal and approval the installation drawings of
the ductwork demonstrating the proposed final details of the
manufacturing and erection methods of the ductwork.

Generally, the drawings shall be drawn to a scale of not less


than 1:50 but subject to the Supervising Officers approval a
scale of 1:100 may be adopted where the installation is a
simple one.

Ductwork drawings shall indicate the length of each ductwork


section; the internal dimensions of the galvanised sheet steel or
other materials to be used as specified; dimensions of bends
and fittings; thickness of metal; sizes and positions of all
stiffeners; angle flanges, etc. including the methods of fixing
and bolting; location of all supports; outline of all insulation;
position and sizes of all access doors; test points; location &
fixings for all thermometers and other devices including
withdrawal clearances; working pressures where applicable
(e.g. for medium and high pressure systems), etc.

The details shown shall cover the provision of internal air flow
equalising ductwork bends, splitters and any other air flow
control devices such as dampers, control mechanisms, acoustic
treatment measures, flexible joints, air diffusion devices
proposed annotated with inlet or extracted airflow volumes
and velocities.

(c) Air Handling Plant Installation Drawings

Air handling unit plant installation drawings shall include


details of all plant to be installed therein including fan shaft
and runner with withdrawal clearances; cleaning spaces for
coils and eliminators; filter arrangements; detail of specialist
acoustic treatment where required in any Particular
Specification and Drawings or where provided as part of a
standard product; details of all air sealing; details of access
doors and gaskets, hinges and catches/handles with
manufacturers type and numbers for proprietary items; details
of drains, drain traps, cleanouts, and construction method to
avoid "cold bridges" etc. as well as provisions made for
hoisting of fans, motors, etc. and the necessary clearance
spaces for in-situ servicing or removal.

Section A4 AC_GS
Page 3 of 10 2017 Edition
These drawings shall also show, in outline form only, any
significant adjacent building structure and the clearances from
and other equipment and/or known services no matter whether
these elements are provided by the A/C Contractor or others.
All such known positions and/or clearances shall be
dimensioned wherever possible.

(d) Pipework Installation Drawings

Prior to the commencement of any manufacture, fabrication, or


installation, the A/C Contractor shall submit to the Supervising
Officer for technical appraisal installation drawings for the
pipework installation. Generally, the drawings shall be drawn
to a scale of not less than 1:50. Subject to the Supervising
Officers approval a scale of 1:100 may be adopted where the
installation is a simple one.

The drawings shall indicate the location, with dimensions


given, of all pipework in relation to the building structure and
other pipework and equipment. The position of all valves,
strainers, check valves, etc. shall be shown together with
clearances necessary for removal of strainer baskets, internal
parts of all valves, motors for motorised valves, solenoids, etc.

Positions and details of all hangers and supports shall be


shown and the positions dimensioned.

Positions of thermostats, thermometers, test pockets and


similar devices shall be shown and dimensioned including
clearances required for their removal.

Details and outline of insulation and insulation boxes shall be


shown including clearances required for removal of the boxes.

(e) Control and Wiring Installation Drawings

The A/C Contractor shall prepare and submit schematic


diagrams showing the control layout with each item clearly
identified with all interlocking and related facilities.

These drawings shall include logic sequence and


wiring/pneumatic diagrams showing full details including
terminal and wire numbers, colour code, etc. for all items of
electrical/electronic equipment and port designations for all
pneumatic installations. Interlocking, reset or similar facilities
shall be clearly shown.

Installation drawings shall also be prepared and submitted for


all physical wiring and pneumatic tubing systems detailing
positions, enclosures, fixings, support, protection, sizes and
number of cores/tubes for all runs.

Section A4 AC_GS
Page 4 of 10 2017 Edition
The installation drawings shall show positions in relation to
the building structure and other plant, equipment and/or
installations. In the context, the plant, equipment and/or
installations will mean to include the A/C Contractors own
installed services and those installed by others. For those
services installed by others, the A/C Contractor shall be
responsible for obtaining sufficient details of relevant
information from them in order to complete the drawings.

(f) Switchgear, Starter, Control/Instrumentation/Motor Control


Installation Drawings

Shop drawings/installation drawings shall show the physical


construction and layout, internally and externally, of all
panels/cabinets/cubicles including the physical arrangement of
all major and important components, bus-bars, phase
separation barriers, interconnecting wiring, pneumatic piping,
labels, etc.

Wiring diagrams and schematic diagrams shall show all


internal & external wiring/piping including all interlocks and
connections from the panels to external equipment.

Operation and control philosophy shall also be included in the


submission. The drawings shall include proposed full wording
of all labels to be installed in both English and Chinese
characters.

(g) Special Plant Rooms Co-ordination Work

Unless otherwise stated in the contract documents, in the case


of a plant room where the A/C Contractors equipment
constitutes the major item involved (i.e. as in the case of an
Air-conditioning plant room), the A/C Contractor shall allow
in the Tender for taking effective responsibility for the co-
ordination of other services/building details within these
specific areas. Furthermore the A/C Contractor shall carry out
this responsibility in co-operation with whoever has the
responsibility for the overall project construction stage co-
ordination.

Where necessary, the foregoing plant room co-ordination


requirement shall include the preparation of plant room co-
ordination drawings which other contractors involved in the
plant room are to comply with. The A/C Contractor shall be
responsible for the cross checking of other contractors plant
room installation drawings before work thereon proceeds.

A4.2.4 Builders Work Drawings

Unless otherwise approved by the Supervising Officer, the A/C


Contractor shall submit to the Supervising Officer in accordance with

Section A4 AC_GS
Page 5 of 10 2017 Edition
the approved Submission Schedule, 6 copies of drawings showing
details of all builders work required e.g. the weight and the load on
each support of equipment. Such drawings shall clearly indicate the
details and positions of all openings, trenches, ducts, drain and cutting
required and construction details for plinths and equipment bases.

A4.2.5 Manufacturers Shop Drawings

The manufacturers shop drawings are drawings for equipment or


plant to be manufactured by a specialist manufacturing supplier in
their own workshops and places away from the Site.

The drawings shall show detailed construction, principal dimensions,


weights and clearances for maintenance, etc. Immediately after
placing of any order or at any event within 4 weeks unless otherwise
approved in writing by the Supervising Officer, the A/C Contractor
shall forward to the Supervising Officer for comment, 4 copies of
manufacturers shop drawings indicating detailed construction,
principal dimensions and weights, clearances for withdrawals and/or
cleaning, etc. No work shall proceed on or off Site unless drawings
requiring approval are so approved in writing by the Supervising
Officer.

A4.2.6 Drawings for Submission to Other Authority

ACMV Systems with FSDs Statutory Requirements

4 sets of the preliminary installation drawings of the following


ACMV systems shall be submitted to the Supervising Officer who
will then check, endorse and return 2 sets to the A/C Contractor for
onward submission to FSD for perusal. The Installations shall only be
commenced upon the receipt of a set of drawings chopped/recorded
by FSD and written approval from the Supervising Officer. 6 sets of
all such approved drawings shall then be submitted to the Supervising
Officer.

(a) Ventilation / Air-conditioning control system; and

(b) Gas extraction system for battery room.

A4.2.7 Checking Drawings of Other Trades

The A/C Contractor shall follow the design intent of the Contract
Drawings in planning and carrying out the work and shall cross check
with other trades in order to verify the line, level, space and sequence
in which the Installations are to be installed.

If directed by the Supervising Officer, the A/C Contractor shall,


without extra charge, make reasonable adjustments to the proposed
installation drawing layouts as are necessary to prevent conflicts with
the work of other trades or for the proper sequence of and execution
of the Installations. Where such modifications are of a nature and of

Section A4 AC_GS
Page 6 of 10 2017 Edition
such unforeseen complexity that they involve unreasonably extra
work not covered by the Contract, they may be covered by variation
order to be issued by the Supervising Officer wherever such a
requirement is justified.

A4.3 AS-BUILT DRAWINGS

A4.3.1 Submission of Asbuilt Drawings

The A/C Contractor shall submit to the Supervising Officer as-built


drawings, including the draft prints and revised draft prints for
checking and the final approved drawings for record in accordance
with the requirements set out in the contract documents.

A4.3.2 Size of As-built Drawings

As-built drawings shall only be of standard sizes of A0, A1 or B1 size


as stipulated in ISO 5457:1999/Amd 1:2010. Smaller size (A2 to A4)
is accepted for installation drawings.

A4.3.3 Content of As-built Drawings

The A/C Contractor shall ensure all as-built drawings are accurate
representation of the Installations, before submitting them to the
Supervising Officer.

"As-built" drawings complete with all details such as design air and
water flow rates to be used for commissioning purposes. Any
amendments noted on these drawings during the commissioning and
test stage shall subsequently be transferred to the original "As-built"
drawings once the amendments have been accepted by the
Supervising Officer.

A4.3.4 Framed Drawings

The A/C Contractor shall provide and install in the relevant major
plant room glass-framed, non-fading prints of the following: -

(a) Valve and damper charts consisting of schematic diagrams


showing the layouts and positions and identification of all
valves and dampers with record of final settings/adjustment for
regulating devices; and

(b) Plant room record drawings showing all plant items, pipework,
ductwork, etc. including all electrical and control schematics
and diagrams.

Glazing shall be polished plate of not less than 6 mm thickness


mounted in natural finish, extruded and anodised aluminium frames
with the prints mounted on acid free mounting board and the whole
backed with marine grade plywood not less than 8 mm thick.

Section A4 AC_GS
Page 7 of 10 2017 Edition
A4.4 OPERATION AND MAINTENANCE (O&M) MANUAL AND USER
MANUAL

A4.4.1 General

The A/C Contractor shall provide two types of manuals to the


Supervising Officer with all changes made to the installation during
the course of the Contract suitably incorporated.

The O&M Manual is for use by the maintenance agent of the


completed Installations. It shall contain detailed technical
information covering both operation and maintenance aspects of the
Installations.

The User Manual seeks to give users of the completed Installations an


overview of the essential information of the Installations. The
contents of the manual should be concise and succinct for ease of
comprehension by people with a non-technical background.

A4.4.2 Presentation

All manuals shall be written in English, unless otherwise specified.


The text of descriptive parts shall be kept concise while at the same
time ensure completeness. Diagrammatic materials shall also be
supported by comprehensive descriptions.

The manuals shall comprise A4 size loose-leaf, where necessary,


A3 size folded loose-leaves. The loose-leaf shall be of good quality
paper that is sufficiently opaque to avoid "show-through". Unless
otherwise specified in the Contract, the manuals shall be bound in
durable loose-leaf 4 ring binders with hard covers. The manuals shall
have labels or lettering on the front cover and spine. The Supervising
Officers approval shall be obtained on this at the draft manual stage.
The electronic copy of manuals including the technical literatures
shall be in PDF format readable by Acrobat Reader Freeware.

A4.4.3 Checking and Approval

The A/C Contractor shall submit to the Supervising Officer the draft
of O&M Manuals and User Manual for checking and approval and
the approved O&M Manuals and User Manual for record according to
the requirements as specified in the contract documents.

A4.4.4 Structure and Contents of O&M Manual

The detailed requirements, structure and contents of the O&M


Manual shall be as specified in elsewhere in the Contract.

A4.4.5 Structure and Contents of User Manual

The detailed requirements, structure and contents of the User Manual

Section A4 AC_GS
Page 8 of 10 2017 Edition
shall include, where applicable, the following information: -

(a) Project Information

This shall include:-

Project title, site address, contract no., contract title, contract


commencement date, substantial completion date and expiry
date of Maintenance Period.

(b) System Description

- Type(s) of system(s) and equipment installed, and their


purposes;
- Locations of major plant rooms and riser ducts;
- Brief description of the operation and functions of the
systems and equipment; and
- Listing of set points which can be adjusted by the user
to suit their operation needs.

(c) Schedule of Major Plant Rooms and Installed Equipment

- Schedule of major plant rooms and riser ducts including


their locations; and
- Schedule of major equipment and plants including their
locations and serving areas.

(d) Safety Precautions for Operation

Any safety precautions and warnings signals that the users


shall be aware of in the daily operation of the various systems
and equipment in the Installations including:-

- Mandatory requirements relating to safety;


- Features or operational characteristics of the installed
systems or equipment which may cause hazard and the
related safety precautions;
- Protective measures and safety precautions for
operation; and
- List of warning signals and the related meanings that
the user shall be aware of and the actions to be taken.

(e) Operation Instructions

Instructions for the safe and efficient operation, under both


normal and emergency conditions, of the installed system
which shall comprise:-

- An outline of the operating mode;

Section A4 AC_GS
Page 9 of 10 2017 Edition
- Step by step operation instructions for systems and
equipment that are to be operated by the user, including
at least procedures for start-up and shut-down;
- Means by which any potentially hazardous situation
can be made safe; and
- Cleaning and basic maintenance procedures.

(f) List of Statutory Periodic Inspections and Tests

A schedule of periodic inspections and tests that owner and/or


user of the Installations have to arrange to achieve compliance
with the requirements stipulated in the relevant Laws of Hong
Kong. The frequency of such inspections and tests shall be
expressed in specific time intervals.

(g) Drawings

A set of selected as-built drawings which shall be able to


illustrate to the user the general layout of the completed
Installations.

(h) Photographs

A set of photographs with suitable captions to illustrate to the


user the appearance and locations of devices which require
their setting and operation.

A4.4.6 Intellectual Property Rights

The Government shall become the absolute and exclusive owner of


the Operation and Maintenance Manuals and the User Manual and all
intellectual property rights subsisting therein free from all
encumbrances.

In the event that the beneficial ownership of any intellectual property


rights subsisting in the above Manuals are vested in anyone other than
the A/C Contractor, the A/C Contractor shall procure that the
beneficial owner shall grant to the Employer a transferable, non-
exclusive, royalty-free and irrevocable licence (carrying the right to
grant sub-licences) to utilise the intellectual property rights in the
manuals for the purposes contemplated in the Contract. For the
avoidance of doubt such purposes shall, but not limited to, include
providing free copying of the materials in the manuals by any
subsequent owner or user of the Installations, and/or any party
responsible for the operation and maintenance of the Installations in
connection with any subsequent alteration, extension, operation and
maintenance of the Installations.

Section A4 AC_GS
Page 10 of 10 2017 Edition
PART B - GENERAL TECHNICAL REQUIREMENTS
(INSTALLATION METHODOLOGY)
SECTION B1

AIR CLEANING EQUIPMENT

B1.1 GENERAL

The complete air filter set for the following types of filters shall be of heavy-duty
airtight factory fabrication designed to ensure a positive seal against leakage of
unfiltered air. Generally, it shall be complete with robust enclosure, holding
frames and housing, all supplied by the same manufacturer, as below: -

B1.1.1 The robust enclosure shall be factory assembled in such a manner that
a rigid and durable enclosure for the filter packs is ensured. The
periphery of the filter pack shall be continuously bonded to the inside
of the enclosing frame to eliminate air bypass and to ensure the
optimum filtration efficiency.

B1.1.2 The holding frames, which are designed to accommodate standard


sized filters of the specified efficiency, shall be factory assembled and
manufactured by the filter manufacturer. It shall be constructed of
minimum 1.6 mm galvanised steel sheet and equipped with positive
gasket seals at the entire length of the holding frames. The gaskets
are provided to stop the air bypass between the filter cell and the
frames, between the adjacent frames, and also between the frames and
the housing. To firmly hold the filter cells against sealing gaskets,
fixtures shall be provided adequately. The above elements are to be
fully supported against the direction of airflow and become totally
rigid when installed.

B1.1.3 The housing shall be constructed of minimum 1.6 mm galvanised


sheet steel and factory assembled in accordance with the
recommended installation details of the filter manufacturer. It shall
incorporate access doors, extruded aluminium tracks, individual
holding frames and flanged joints for ductwork connections. Positive
gasket seals shall be provided to stop the air leakage between the
housing and the connected ductwork. For air conditioning application,
the housing shall be constructed of minimum 1.6 mm double skin
galvanised sheet steel with 32 mm 80 kg/m3 mineral wool insulation
or factory coated/injected with suitable thermal insulation material
approved by the Supervising Officer. The above material shall have
the insulation property same as or better than that of the air-
conditioning ductwork connected to the complete air filter set. For
filters used in corrosion resistant ductwork, the associated housing,
holding frames, enclosures and all metal surfaces in contact with the
air stream shall be applied with the same anti-corrosion coating as the
ductwork. Accessories of which the operation will be affected by the
coating shall be of AISI 316 stainless steel but with the coating
omitted. The housing shall have finishing painting with colour to

Section B1 AC_GS
Page 1 of 7 2017 Edition
match the air handling equipment. It shall be with factory punched
holes with gland plates for each stage of filter for field connections of
manufacturers and/or automatic control devices. All holes shall be
sealed after the connection work.

In any case, all components of the air filter set and its associated
accessories, which are within the air stream, shall comply with
requirements of the FSD.

To indicate the filter condition, differential pressure gauge shall be


provided for easy inspection, operation and maintenance. Facilities
for CCMS interfacing filter condition monitoring shall also be
equipped. They shall be fixed in such a position, outside the casing
that they will be accessible and easily read. The gauges shall be
properly installed with all necessary galvanised steel support brackets
and ductwork stiffeners onto the ductwork without damaging the
thermal insulation. The complete mounting assembly shall be
designed to ensure leakage-proof and to avoid condensation at any
surface in contact with the filter section.

The A/C Contractor shall provide all required new filters for all air
handling equipment at the date of the substantial completion stated in
the certificate of completion issued in accordance with the Contract.
For disposable type filters, the A/C Contractor shall provide at least 4
extra sets of each type of installed filters for spare and replacement.
The A/C Contractor shall be responsible for the replacement of filters
when necessary during the Maintenance Period. At least one set of
filters shall be handed over to the Supervising Officer at the expiry of
the Maintenance Period.

For cleanable filters, the A/C Contractor shall provide at least 1 extra
set of each type of installed filters for spare and be responsible for the
cleaning of filters when necessary during the Maintenance Period.
This set of filters shall be handled over to the Supervising Officer at
the end of the Maintenance Period.

B1.2 WASHABLE PANEL FILTER

The holding frames shall be equipped with fixtures for easy removal of the filter
cells without the use of any special tools.

For filter cells installed inside air handling unit, separate housing is not required.
However, the holding frames shall be factory mounted in the air handling unit
casing and installed to provide service from the air side.

B1.3 AUTOMATIC VISCOUS FILTER

The holding frames shall be equipped with fixtures for easy removal of filter
cells without the use of any special tools.

Section B1 AC_GS
Page 2 of 7 2017 Edition
The A/C Contractor shall provide all necessary electrical cables/accessories for
proper operation of the complete air filter set in accordance with the
manufacturers installation details.

B1.4 DISPOSABLE PANEL FILTER

The holding frames shall be equipped with fixtures for easy removal of the filter
cells without the use of any special tools.

For filter cells installed inside air handling unit, separate housing is not required.
However, the holding frames shall be factory mounted in the air handling unit
casing and installed to provide service from the air side.

B1.5 DISPOSABLE PLEATED PANEL FILTER

The holding frames shall be equipped with fixtures for easy removal of the filter
cells without the use of any special tools.

For filter cells installed inside air handling unit, separate housing is not required.
However, the holding frames shall be factory mounted in the air handling unit
casing and installed to provide service from the air side.

B1.6 RENEWABLE PANEL FILTER

The holding frames shall be equipped with fixtures for easy removal of the filter
cells without the use of any special tools.

For filter cells installed inside air handling unit, separate housing is not required.
However, the holding frames shall be factory mounted in the air handling unit
casing and installed to provide service from the air side.

B1.7 AUTOMATIC FABRIC ROLL FILTER

The holding frames shall be equipped with fixtures for easy removal of filter
cells without the use of any special tools.

The A/C Contractor shall provide all necessary electrical cables/accessories for
proper operation of the complete air filter set in accordance with the
manufacturers installation details.

B1.8 BAG FILTER

The holding frames shall be equipped with at least four heavy duty spring type
positive sealing latches for each filter cell to ensure a positive seal against
leakage of unfiltered air.

Section B1 AC_GS
Page 3 of 7 2017 Edition
For filter cells installed inside air handling unit, separate filter housing is not
required. However, the holding frames shall be factory mounted in the air
handling unit casing and installed to provide service from the air side.

B1.9 CARTRIDGE FILTER

The holding frames shall be equipped with at least four heavy duty spring type
positive sealing latches for each filter cell to ensure a positive seal against
leakage of unfiltered air.

For the filter cells installed inside air handling unit, separate filter housing is not
required. However, the holding frames shall be factory mounted in the air
handling unit casing and installed to provide service from the air side.

B1.10 HIGH EFFICIENCY PARTICULATE ARRESTANCE (HEPA) FILTER

The holding frames shall be equipped with at least four heavy duty spring type
positive sealing latches for each filter cell to ensure a positive seal against
leakage of unfiltered air.

For filters installed inside air handling unit, separate housing is not required.
However, the holding frames shall be factory mounted in the air handling unit
casing and installed to provide service from the air side.

B1.11 AUTOMATIC RECLEANABLE FILTER

The complete automatic reclean able filter set including filter cells, holding
frames and housing shall be factory fabricated and assembled.

Manufacturers installation details shall be followed and the A/C Contractor


shall provide all necessary electrical cables/accessories for proper operation of
the complete Installations.

B1.12 AUTOMATIC RECLEANABLE HEPA FILTER

The complete automatic reclean able filter set including filter cells, holding
frames and housing shall be factory fabricated and assembled.

Manufacturers installation details shall be followed and the A/C Contractor


shall provide all necessary electrical cables/accessories for proper operation of
the complete Installations.

B1.13 AUTOMATIC RECLEANABLE HIGH VOLTAGE ELECTROSTATIC


FILTER

The complete automatic reclean able high voltage electrostatic filter set
including filter cells, holding frames and housing shall be factory fabricated and
assembled.

Section B1 AC_GS
Page 4 of 7 2017 Edition
Manufacturers installation details shall be followed and the A/C Contractor
shall provide all necessary electrical cables/accessories for proper operation of
the complete Installations. The A/C Contractor shall provide all necessary safety
measures including automatic cut-off switch and high voltage warning label at
each access panel for the electrostatic filter to prevent any possibility of
electrical shock to personnel during operation, inspection and maintenance.

The operation of the electrostatic filter shall be interlocked with the fan or air
handling unit in such a way that the filter is in operation whenever the fan or air
handling unit is operated and the unit is cut off when the fan or air handling unit
is cut off.

B1.14 GAS FILTER

The holding frames shall be equipped with fixtures for easy removal of filter
cells without the use of any special tools.

Housings shall be constructed of minimum 1.6 mm thick galvanised steel with


extruded aluminium filter slide tracks. Doors, on both sides, shall be hinged
permanently and attached with positive locking latches. Gaskets shall be
provided to prevent air leakage around doors and between the doors and the
filters.

Housing shall consist of two sections, first section for housing 50mm washable
type pre-filters and second section for housing filter modules.

Media shall be contained in modules which shall be constructed of ABS grade


DGA-R thermoplastic with V-shaped cross section.

B1.15 ACTIVATED OXYGEN AIR PURIFIER

The air purifier shall be factory fabricated and assembled in accordance with the
manufacturers installation details. The A/C Contractor shall provide all
necessary electrical cables/accessories for proper and safe operation of the
complete Installations. The A/C Contractor shall provide all necessary safety
measures including automatic cut-off switch and high voltage warning label at
each access panel for the unit to prevent any possibility of electrical shock to
personnel during operation, inspection and maintenance.

The complete assembly shall be mounted onto the wall of ductwork by the
manufacturers mounting flange provided by the manufacturer with the power
generator outside the air stream and the electrode tubes within the air stream.
The glass tube electrodes shall be mounted perpendicular to the direction of air
flow and installed at a distance at least 150 mm away from any air distribution
accessories within the ductwork. The power generator shall be installed with all
necessary support brackets and ductwork stiffeners onto the ductwork and
sealed without damaging the thermal insulation and without causing air leaking.

Section B1 AC_GS
Page 5 of 7 2017 Edition
The mounting shall be designed to ensure leakage-proof and to avoid
condensation at any surface in contact with the ductwork. However, easy
withdrawal of the complete unit for routine inspection and maintenance shall be
allowed also.

The air purifier shall be installed in suitable location of the air stream as
recommended by the manufacturer for best operating efficiency using a stainless
steel mounting frame provided by the manufacturer and interlocked with the fan
or air handling unit in such a way that the unit is in operation whenever the fan
or air handling unit is operated and the unit is cut off when the fan or air
handling unit is cut off.

The air purifier shall be wired strictly in accordance with the manufacturers
wiring diagram. It shall be wired so that the units may be unplugged and
removed for regular cleaning and maintenance.

A secondary switch to automatic switch off the unit shall also be provided in
case the mechanical part of the fan failure.

B1.16 ULTRA-VIOLET (UV) STERILISING LIGHT

The ultra-violet sterilising light shall be factory fabricated and assembled in


accordance with the manufacturers installation details. The A/C Contractor
shall provide all necessary electrical cables/accessories for proper operation of
the complete Installations. The A/C Contractor shall also provide all necessary
safety measures including automatic cut-off switch, proper cover on viewing
glass and ultra-violet warning label at each access panel for the unit to prevent
direct exposure, which may cause eye and skin discomfort to personnel, during
operation, inspection and maintenance.

The complete assembly shall be mounted onto the wall of ductwork by the
manufacturers mounting flange or inside a section of the air handling unit with
the power transformer outside the air stream and the ultra-violet lamps within
the air stream. The ultra-violet lamps shall be mounted perpendicular to the
direction of air flow to allow maximum exposure. The power transformer shall
be installed with all necessary support brackets and ductwork stiffeners onto the
ductwork without damaging the thermal insulation.

The mounting shall be designed to ensure leakage-proof and to avoid


condensation at any surface in contact with the ductwork. However, easy
withdrawal of the complete unit for routine inspection and maintenance shall be
allowed also. In accordance with the manufacturers recommendation, baffle
filters may be necessary to install for those air discharge louvres or ductwork
openings near the unit to reduce the ultra-violet light intensity level in case the
safety limit of the exposure level is exceeded.

The ultra-violet sterilising light shall be installed in suitable location of the air
stream for best operating efficiency as recommended by the manufacturer and
interlocked with the fan or air handling unit in such a way that the sterilising
light is in operation whenever the fan or air handling unit is operated and the
unit is cut off when the fan or air handling unit is cut off.

Section B1 AC_GS
Page 6 of 7 2017 Edition
B1.17 WATER SCRUBBER

The complete water scrubber set shall be factory fabricated and tested. The unit
may be re-assembled on Site in accordance with the manufacturers
recommended installation details subject to the approval of the Supervising
Officer.The A/C Contractor shall provide all necessary electrical
cables/accessories for proper operation of the complete Installations.

Section B1 AC_GS
Page 7 of 7 2017 Edition
SECTION B2

DUCTWORK

B2.1 GENERAL

The zinc coating of the ducts shall not be damaged during fabrication, delivery
and installation. Any damage to the galvanised finish shall be made good with
three coats of aluminium zinc rich paint or other approved corrosion resisting
paint to the satisfaction of the Supervising Officer, in addition to any other
protective or finishing paint/coats required in the Particular Specification.

Fabrication and testing of all ductwork shall conform to DW/143:2013 - A


Guide to Ductwork Leakage Testing & DW/144:2013 - Specification for Sheet
Metal Ductwork (Low, Medium and High Pressure Velocity Air Systems)
published by B&ES and the requirements stipulated in this General
Specification.

If insulation is applied to the pre-fabricated ductwork in the factory, leakage test


of the ductwork shall be carried out before the application of insulation. Every
precaution shall be made to ensure that the insulation and vapour barriers
applied to the ductwork shall not be mechanically damaged before erection on
Site.

Any damaged ductwork found shall be replaced. All inspection tests carried out
in factory are part of the quality control process and shall in no way be treated as
substitution of the field tests required on Site.

The ducting system shall be complete with all necessary supports, access doors,
dampers, fire dampers, cleaning points and test holes.

All ducts shall be fabricated and installed so as to be rigid and free from
swinging, drumming and movement.

All material of ductwork, gasket, flexible joints, acoustic linings and sealants
shall not support bacteria growth or posing fire hazard.

B2.2 DESIGN AND ACCESSORIES

The ductwork shall be properly and correctly constructed with all necessary
accessories to minimise waste of energy and pressure losses due to eddies,
vortices, etc. and shall not create, amplify or transmit any noise or vibration.
Any necessary sound reducing linings or boxes to reduce noise transmission
shall be provided by the A/C Contractor in accordance with the requirements of
Sections B8 and C8.

Internal roughness and obstructions to air flow (other than dampers, splitter,
vanes, etc.) will not be accepted for ductwork constructed from sheet materials.
Sharp edges or corners on the outside of ductwork, fittings and supports will not
be accepted.

Section B2 AC_GS
Page 1 of 7 2017 Edition
Perforated rivets shall not be used in manufacture of ductwork. Generally, the
use of self tapping screws is not allowed. Where the use of other fastenings is
impracticable, self-tapping screws may be used subject to the written approval
of the Supervising Officer.

At each point where a duct passes through a roof or external wall, a weather
"cravat" or other purpose made arrangement shall ensure a waterproof and
weatherproof fixing.

All intake and discharge openings to the Building shall be fitted with 10 mm
galvanised mesh bird wires and is additional to any grilles or louvers indicated
for these locations.

Duct connections between individual components of an air handling unit and


connections between an assembly and a ductwork system shall be made with
angle flanged joints. Removable sections shall be provided for access of
cleaning and maintenance. All joints shall be made perfectly airtight and
proprietary duct-flange or angle duct-flange shall be used for all duct-joints and
for connection to plants.

Proprietary duct-flanges shall be installed in accordance with the manufacturers


recommendations and clamped together with screw lock clamps. Angle duct-
flanges shall be installed in accordance with DW144.

Unless otherwise specified, duct sizes given on the Drawings are all clear
internal dimensions and allowance shall be made for both internal and external
insulation on the ducts where applicable.

All ductwork shall be cleaned internally and externally before the system is set
into testing, commissioning and operation. Timing of this work shall be set such
that minimum inconvenience shall be caused to the work of other trades.

All ductwork installed in the protected areas or lobbies shall be properly


enclosed in fire-rated enclosure in according to the requirement of the FSD and
Buildings Ordinance. All fire-rated enclosure shall have fire rating meeting the
requirements of the FSD and Buildings Ordinance, but shall in no case be less
than 2 hours.

Take-off from main ducts shall be conical, bell mouth, or shoe type. Square
take-off is not permitted.

B2.3 HANGERS AND SUPPORTS

All ductwork shall be securely supported by hangers, brackets and other


appropriate forms of support as detailed in DW/144:2013 - Specification for
Sheet Metal Ductwork (Low, Medium & High Pressure Velocity Air Systems)
published by B&ES.

All supports and hangers for air duct installed shall be rigid galvanised steel rod,
angle bar or U-channel construction free from rust approved by the Supervising
Officer.

Section B2 AC_GS
Page 2 of 7 2017 Edition
All hangers shall be provided with screwed lengths drop rods with open turn
buckles for adjustment of duct level. All fixings shall be provided with washers
and lock-nuts and projecting ends of drop rods shall be cut off and protected
with plastic caps.

All ductwork shall be securely supported so as to prevent vibrations or


movements and arranged to allow expansion due to thermal stresses without
distortion of the ductwork, rupture of insulation or damage to the supporting
structure. Additional ductwork supports shall be positioned close to dampers,
diffusers and all similar equipment which are not subjected to distortion, in
addition to those hangers and supports generally required. Allowance shall be
made in ductwork construction for instrument and controls connections and
adequate local stiffening shall be incorporated to provide ridge mountings.

Noise and vibration shall not be transferred to the structure or any other element
through hangers and brackets and in this respect the requirements of Sections B8
and C8 shall apply.

Approval shall be obtained from the Supervising Officerfor hangers and


support/installation/shop drawing designs before manufacture and installation.
Furthermore, approval for the method design and calculation of fixing to the
structure shall also be obtained as this may have structural implications.

All metal mounting and fixing brackets for air ductwork shall be pre-fabricated
off-site.

B2.4 FLEXIBLE DUCT JOINTS

Flexible joints shall be provided on all in-line fan inlet and outlet connections, at
expansion joints in the building and elsewhere on ductwork where indicated.
Flexible joints shall be of the same cross-sectional area as the mating fan
inlet/outlet or duct section. The centre lines of flexible joint connections shall
be coaxial.

Flexible joints shall consist of, or be externally protected by, material having a
fire penetration time of at least 15 minutes when tested in accordance with BS
476-20:1987and shall comply with BS 476-7:1997, Section 2, Class 1 (surface
of very low flame spread).

Under no circumstances shall materials containing asbestos fibres be used. The


material used for the flexible connections shall withstand the specified
conditions of temperature and air pressure, and comply with the standard of air
tightness.

B2.5 FLEXIBLE DUCTWORK

Where flexible ductwork is indicated, or required between rigid ductwork and


items of equipment, the internal diameter of the flexible duct shall be equal to
the external diameter of the rigid duct and equipment spigot. Flexible ductwork
shall be kept to a minimum length and shall not be used between rigid sections

Section B2 AC_GS
Page 3 of 7 2017 Edition
of ductwork to change direction unless indicated or approved by the Supervising
Officer. The maximum length of any individual flexible duct shall not exceed
2000 mm unless otherwise approved by the Supervising Officer.

Joints at flexible duct connections shall be made with a sealant which


permanently retains adhesion and elasticity throughout the design working
temperature range, or shall be made with clip and complete with aluminium tape
as approved by the Supervising Officer. The installation details and method of
application of such connections shall be in accordance with the ductwork
manufacturers recommendations and as approved by the Supervising Officer.

Flexible ductwork shall be independently supported from the underside of the


concrete slab. On all circular spigots, the flexible ductwork up to and including
140 mm diameter shall be secured with a worm drive type hose clip complying
with BS 5315:1991. Ductwork over 140 mm diameter shall be secured with a
band clip. On rectangular connections, the flexible ductwork shall be held in
place by a mating flange with a backing plate, or alternatively, proprietary
material may be used, in which case the metal edge shall be held in position by
backing flat. Backing flat shall not be less than 3 mm thick. No flexible
ductwork shall be less than 50 mm long between rigid components.

The frictional resistance to air flow per unit length of flexible duct shall not
exceed 150% of the frictional resistance per unit length of galvanised steel duct
of similar diameter.

The flexible duct shall be installed in as straight a manner as possible. In situations


where bending is required, the bending radius shall be sufficient to prevent
tensioning of the bend and restriction of the throat likely to cause deformation
and/or leakage. The radius ratio R/D for bends shall be not less than 2, where R is
the centre line radius and D is the diameter of the flexible duct. In no case shall
flexible ductwork be used to correct misaligned ducts.

B2.6 DUCTWORK ACOUSTIC TREATMENT

Where specialised acoustic attenuation is required either as in-line sound


attenuator inserts or by internal duct lining acoustic treatment, these shall
comply with the requirements of Section B8.

B2.7 EXTRACT HOODS AND VALANCES FOR KITCHENS

Hoods shall be of galvanised sheet steel, stainless steel, aluminium, wired glass,
polyester resin-bonded glass fibre or PVC as indicated in the Particular
Specification. The hoods shall be rigidly formed and shall be supported
independent of the ductwork. Unless otherwise indicated, they shall be
supported either from above or from a side wall. The type and size of hood shall
be as indicated but the A/C Contractor shall check and (in consultation with the
Supervising Officer) determine its exact position in relation to the associated
item of kitchen equipment to be covered on Site.

Section B2 AC_GS
Page 4 of 7 2017 Edition
Hoods for kitchen equipment and for the extraction of condensable vapours shall
have all joints in sheets vertical and shall have a drip gutter all round with a
drain connection plugged, unless instructed by the Supervising Officer, to run a
drain to a suitable point. Hoods in high fire risk situations, such as for cooking
ranges in kitchen, shall overlap the equipment by minimum 500 mm.

Stainless steel hood shall be manufactured from minimum 1 mm thick 304 or


higher grade stainless steel with joints continuously welded; all external welds
shall be ground and polished. All stiffening and supported shall be hidden.

The stainless steel shall be free from scale and all surfaces shall be polished to
type 4 commercial (satin) finish.

Unless otherwise specified, welding of the stainless steel shall be by inert-gas


arc welding to ISO 9692-1:2013.

Kitchen exhaust hood should be completed with make-up air grilles or make-up
ductwork complete with air grilles as approved by the Supervising Officerand
constructed in such position for the best efficiency in evacuating exhausted
fumes from kitchen equipment.

Lighting fitting shall be provided within the hoods, fittings shall be bulkhead
design with die cast aluminium base and glass diffuser to IP rating of "IP54" or
better suitable for kitchen hood design. The fittings as well as the wiring for the
fittings shall be suitable for continuous use of high operating conditions over
100C temperature and 100% RH.

For kitchen hood with water scrubber design, the requirement shall be in
accordance with Clause D.5 of this General Specification.

B2.8 GREASE FILTER

Hoods and valances positioned over cooking appliances shall be fitted with
grease filters as specified in Section B1.

B2.9 DUCTWORK CLEANING POINTS

The A/C Contractor shall supply and install proprietary air duct cleaning points
to the ductwork systems. The cleaning points shall in general be installed at
maximum distance of 4 metres between centres in fully accessible locations and
shall also be fitted before and after bends, tees and other locations with
difficulties in gaining access. For fan coil units, at least one air duct cleaning
point shall be provided in each supply air duct, and any two points at 4 metres
maximum distance apart.

The maximum distance of 4 metres may be increased if the Supervising Officer


considers that the ductwork system has compatible service openings which can
serve the similar purposes as the air duct cleaning points. The A/C Contractor
shall submit the proposed layout of air duct cleaning points and services opening

Section B2 AC_GS
Page 5 of 7 2017 Edition
in the ductwork system for the Supervising Officers approval prior to the site
work.

Where the cleaning sleeve penetrates the air duct, the gap shall be sealed by an
expanded foam sealing ring held in position by secure flanges. Where the
sleeve penetrates the insulation, the vapour barrier shall be maintained. Where
the sleeve penetrates the false ceilings, the sleeve shall be secured by matching
flanges.

The cleaning sleeve shall be kept straight and shall terminate at a readily
accessible position. The termination flange shall bear an instruction plate
indicating an air conditioning and ventilation access point in both Chinese and
English. It shall incorporate a threaded port and a screw cap which when
removed shall allow the coupling of air duct inspection and cleaning probes.

Ceiling access panels requirement shall also be provided after the confirmation
of service panels and air duct cleaning points.

Ductwork conveying greasy air from kitchen hoods shall be graded downward
towards suitable drain points in order to facilitate drainage of water at which
also is the cleaning out points.

All joints shall be air tight to prevent leakage. Air leakage for cleaning points
shall comply with DW/143:2013 and all FSD requirements. The A/C
Contractor shall also provide a set of proprietary type compressed air lance,
disinfection application lance and sampling probe which shall be suitable for use
of leakage test to the cleaning points. All operating and serving instruction
manuals shall be supplied with the set of equipment.

The whole air duct installation shall be disinfected by the A/C Contractor
thoroughly using an approved disinfection agent immediately before the
complete ductwork installation is handed over to the Employer, as directed by
the Supervising Officer. The A/C Contractor shall also supply ten bottles of one
litre approved disinfection agent to the Supervising Officer before hand-over of
the ductwork installation. The disinfection agent shall be easily available
locally.

Interior of all ductwork shall be cleaned by rotating mechanical brush or


compressed air as approved by the Supervising Officer. All contaminants shall
then be removed by high efficiency vacuum pumps of sufficient degree of
vacuum to ensure removal of heavier particles.

B2.10 TESTING

All installed ductwork shall be tested to the "Building Energy Code. The
method of air leakage test shall follow Appendix A of DW/144:2013 and to the
B&ES standard DW/143:2013 and as directed by the Supervising Officer as
necessary to prove the quality of the Installations. Air leakage testing of
ductwork on any section of completed Installations shall be carried out and shall
be in accordance with Appendix A of DW/144:2013 and "Method of Testing" of
DW/143:2013. For those items not covered in DW/144:2013 and subject to the

Section B2 AC_GS
Page 6 of 7 2017 Edition
approval of the Supervising Officer, the recommendations of the "HVAC Duct
Construction Standards-Metal and Flexible":2005 and "HVAC Air Duct
Leakage Test Manual":1985 issued by the Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) of U.S.A. shall be applied. Air
ducts shall be leakage tested as necessary and any defects rectified before
applying insulation and commissioning.

Section B2 AC_GS
Page 7 of 7 2017 Edition
SECTION B3

AIR HANDLING AND TREATMENT

B3.1 GENERAL

Fans shall be installed using galvanised steel plate, supports, bolts, nuts and
washers with all "as cast" bearing surfaces for bolt heads and washers counter-
faced. Anti-vibration mountings shall be in accordance with Sections B8 and
C8.

Fans heavier than 50 kg shall be provided with eyebolts certified by an


Authorised Person (e.g. surveyor or structural engineer) for safe working load or
other purpose made lifting facilities at convenient location for fan maintenance.

Fan V-belt drives shall comply with BS 3790:2006 (or related clauses of ISO
254:2011, ISO 1081:1995, ISO 1813:2014, ISO 4183:1995, ISO 4184:1992 &
ISO 5292:1995) and shall be capable of transmitting at least the rated output
with one belt removed. Minimum two belts per drive shall be used for motor
rated higher than 4 kW unless otherwise specified. Pulleys shall be exactly
aligned. The A/C Contractor shall ensure that any holding down bolts grouted
in by builders are positioned to the correct alignment. Provision shall be made
for positive adjustment of the tension in V-belt drives.

Fan guards shall be provided for all open unprotected intakes to centrifugal fans;
for unprotected intakes to and exhausts from axial flow fans; for open
unprotected and easily accessible intakes to and exhausts from propeller fans;
for V-belt drives; for drive couplings and elsewhere as indicated. For full
specification on motor drive guards refer to relevant clauses of Section C7.

Flexible joint shall be provided for air duct connecting to the inlet and outlet of
fans.

Air flow direction, fan designation and fan number shall be clearly marked on
the fan casing.

Galvanised steel or superior materials shall be used for all supports and fixing
accessories and suitable paint shall also be applied in accordance with Part G.

B3.2 AIR HANDLING UNITS (AHUs)

Air handling unit shall be mounted on a hot dipped galvanised I beam or U-


channel mounting frame which is either fixed on concrete plinths by builder or
ceiling mounted by suspension galvanized steel hangers. Sufficient space shall
be allowed for installation of drain trap and fall of condensate drain.

For ceiling mounted air handling unit, the mounting frame and hanging rods
shall be designed to account for the operation loading of the air handling unit
and the associated ducting and piping. Hanging rods shall be threaded and

Section B3 AC_GS
Page 1 of 5 2017 Edition
completed with locking nuts for level adjustment. All AHU steel supports and
supporting accessories shall be hot dipped galvanised.
Neoprene pad shall be installed continuously between the air handling unit
mounting frame and concrete plinth as vibration absorption media.

The routing of piping, ducting, electrical, control wiring and accessories shall be
so arranged that all access panels of the air handling unit shall be free from
obstruction.

Air handling unit or individual module heavier than 50 kg shall be provided with
eyebolts or other purpose made lifting facilities nearby.

All gauges and meters other than insertion type shall not be mounted on the
casing of the air handling unit on Site to avoid breaking the thermal insulation.
All such provision required for connection must be purposely designed and
made in the factory.

Chequer plate cover shall be provided for protecting services along the access
route to the air handling unit.

B3.3 AXIAL FLOW FANS

Suitable galvanised steel mounting plates or bracket provided from the same
manufacturer shall be used for fixing the fan. The fans should be mounted on
anti-vibration mountings.

B3.4 CEILING FANS

Unless otherwise stated, ceiling fans shall be mounted no lower than 2400 mm
and no higher than 2600 mm from finished floor levels. Down rod lengths shall
be sized to meet these requirements.

In case the installed ceiling fan will be lower than 2400 mm, 400 mm sweep
rotary ceiling fans in accordance with Clause C3.12 shall be used instead.

Where ceiling heights are too high for the practical installation of ceiling fans
because the rods would be too long and unstable, 400 mm or larger sweep rotary
wall fixed fans in accordance with Clause C3.12 shall be used.

B3.5 CENTRIFUGAL FANS

For floor mounted arrangement, the fan shall be mounted on G.I. support with
anti-vibration mountings and sit on concrete plinth provided by builder.

For ceiling mounted arrangement, the fan shall sit on anti-vibration mountings
fixed on steel mounting frame supplied and installed by the A/C Contractor.
Threaded suspension rods with lock nuts shall be used for level adjustment.

Section B3 AC_GS
Page 2 of 5 2017 Edition
Anti-vibration mounting shall be selected to cater for different point load of the
fan at four corners.

B3.6 FAN COIL UNITS

B3.6.1 Threaded suspension rods with lock nut and washer shall be used for
ceiling mounted fan coil units for level adjustment.

B3.6.2 Flexible joints shall be installed for air duct, water pipe, conduit and
other services connection to the unit to isolate vibration generated by
the unit.

B3.6.3 Sufficient access panels shall be provided at the supply air duct and
the return air plenum for servicing the blower and duct heater.
Demountable return air grille of minimum dimensions 600 mm
600 mm shall be considered as an access panel subject to the approval
of the Supervising Officer.

B3.6.4 Power supply will be provided by electrical contractor and terminated


at fused connector unit with pilot light and isolation switch adjacent
to each fan coil unit, all cabling from the power source (e.g.
connector unit) to the control box of the fan coil unit and fan coil
room remote control and accessories at convenient position including
the termination shall be carried out by the A/C Contractor. G.I. metal
boxes for housing the fused connector unit and all necessary conduit
works inside ventilated ceiling or otherwise indicated shall be
supplied and installed by the A/C Contractor.

B3.6.5 The location of the local control box shall be within 600 mm from the
terminal box of the fan coil unit and the duct heater.

B3.6.6 All units shall be selected to suit the limited space within the false
ceiling, with due consideration to access for maintenance and
servicing.

B3.6.7 All blowers and motors of fan coil units shall be demountable from
the ceiling void for maintenance purpose without causing damage to
the associated ductwork and insulation.

B3.6.8 A second or additional larger stainless steel insulated drain pan shall
be provided for those air conditioning units, evaporators of direct
expansion system and alike installed in switch rooms, lift machine
rooms, UPS rooms, control rooms and other essential areas sensible
to water damage. A water overflow alarm indication shall be
equipped at conspicuous place outside the room or connected to
CCMS.

Air conditioning units, evaporators of direct expansion system and


alike and its associated piping and ducting should not be mounted
above essential electrical and control equipment such as switchboard,
lift machine, control panel, UPS, etc.

Section B3 AC_GS
Page 3 of 5 2017 Edition
B3.6.9 For unoccupied rooms and other areas sensible to water damage as
specified, an overflow detection device shall be installed inside the
drain pan or at the connection to the overflow drain pipe which fitted
at the overflow level of the drain pan. Upon water accumulating in
the drain pan due to malfunction of the condensate drain system, the
device shall be activated to shut down the corresponding fan coil unit
and trigger an overflow alarm at conspicuous place outside the room,
and/or in the CCMS.

B3.7 CASSETTE TYPE FAN COIL UNITS

Refer Clause C3.7.

B3.8 MIXED FLOW FANS

Mixed flow fans shall be mounted on a G.I. steel support. Threaded steel rod
with lock nuts shall be used for ceiling mounted purposes. Neoprene pad shall
be provided for vibration isolation.

B3.9 MECHANICAL ROOF EXTRACT UNITS

Mechanical roof extract unit shall be mounted on a vermin proof hard wood sill
and concrete curb provided by Building Contractor with dimensions according
to requirements of the manufacturer. All gaps between the mounting frame and
structural base shall be sealed up properly.

B3.10 PROPELLER FANS

Where propeller fans are mounted in a casing, the casing shall be longer than the
length of the fan and motor. The casing shall be of galvanised steel or
aluminium sheet or stainless steel as specified, and shall have flanged ends and
an inspection door. A terminal box shall be mounted externally on the casing.

B3.11 PROTECTIVELY COATED FANS AND FANS FOR CORROSIVE OR


HAZARDOUS APPLICATIONS

All steel mounting brackets, bolts, washers and nuts shall be hot dip galvanised
and painted with protective coatings to meet the appropriated corrosive
environment.

B3.12 ROTARY FANS

Refer Clause C3.12.

Section B3 AC_GS
Page 4 of 5 2017 Edition
B3.13 IN-LINE CENTRIFUGAL FANS

In-line centrifugal fans shall be mounted on G.I. steel support. Threaded steel
rod with lock nuts shall be used for ceiling mounted purposes. Neoprene pad
shall be provided for vibration isolation.

B3.14 EC PLUG FANS

Same as Clause B3.5

B3.15 JET FANS

Refer to Clause C3.15.

B3.16 CONDUCTING FANS

Refer to Clause C3.16.

B3.17 TERMINAL AIR CONTROL DEVICES

Terminal air control devices shall be mounted on a steel support. Threaded steel
rod with lock nuts shall be used for ceiling mounted purposes. Neoprene pad
shall be provided for vibration isolation.

Fixture shall be installed on the steel support to govern the lateral movement of
the unit.

The power supply to the unit shall refer to Clauses B3.6.4, B3.6.5 and B3.6.6.

Flexible duct connecting the inlet/outlet of the unit shall be fixed by omega clip
or similar approved devices.

B3.18 GRILLES AND DIFFUSERS

Grilles and diffusers shall be fixed on air duct by self-tapping stainless steel
screw or purposely made spring or locking devices. Fixing the grille or diffuser
by self-taping screw on the face panel exposed to view shall be avoided.

For linear diffuser or special made air fittings, lifting brackets or fixing devices
shall be provided to facilitate site installation.

B3.19 DOMESTIC EXHAUST FANS

The installation of domestic exhaust fans shall follow the installation instruction
of the manufacturer or refer to contract drawings. All domestic fans shall be
protected with safety guard.

Section B3 AC_GS
Page 5 of 5 2017 Edition
SECTION B4

AUTOMATIC CONTROL

B4.1 AUTOMATIC CONTROL SYSTEM (ACS)

The Automatic Control System (ACS) is the Master Control of a building that
controls and monitors the proper, effective and efficient operation of the Air-
conditioning and other Building Services System(s) in building(s). An ACS
can be a complicated Central Control & Monitoring System (CCMS) or as
simple as an electronic controller with built-in real time clock for scheduling
controls. The appropriate ACS shall be so designed to meet the requirements
and operation needs of the building operation & management team and the
operation requirements of the end users in building(s). As different equipment
and systems may have different operation schedules, the ACS shall have
adequate capacity for scheduling all the operation needs.

The ACS described below shall be applied to buildings which do not require
sophisticated CCMS (if so specified, the designed ACS shall have provisions for
the proper interfacing and direct connection to the network of the future CCMS)
for the normal operation and control of the air conditioning, refrigeration and
ventilation systems, and other building services and electrical & mechanical
(E&M) systems installed in the buildings if so specified. The main function of
an ACS is for on/off controls, optimisation, monitoring of operation status and
alarms generation of the connected systems in building(s). Comprehensive
system controls and monitoring functions of each individual system shall be
carried out by the system controller of each individual air conditioning, building
services or E&M system. The ACS shall be so designed to achieve a reliable
control in performing the control and monitoring functions set in the design
criteria and shall be of electronic or direct digital control type as specified.
Unless otherwise specified, the ACS controller shall be located inside the A/C
Supervisory Control Panel.

B4.1.1 Electronic Controller with Micro-processor and REAL Time Clock


Control

With the application of micro-processor and real time clock, all


building services systems specified shall be turned on and off in
accordance with the time schedules pre-set in the built-in program
including any holiday and special schedules so required by the users.
A monitoring and alarm system shall be incorporated in the controller
in giving audio and visual status and alarm of faults for each building
services system in the building.

For easy programming, user friendly input/output (I/O) devices shall


be provided for the setting and re-setting of the operation schedules.
To prevent malfunctioning of the real time clock and losing of
memory, back-up battery with power healthy indicator and alarm
shall be provided.

Section B4 AC_GS
Page 1 of 24 2017 Edition
B4.1.2 Direct Digital Controller (DDC)

(a) Each controller shall operate as a standalone unit capable of


performing its specified control responsibilities independently
of other controllers in the network.

(b) Portable operators terminals shall be provided for local


viewing and operation.

(c) Power Fail Protection All system set point, control algorithm
and other programmable parameter should be stored such that
power failure of any duration does not necessitate
reprogramming the DDC controller.

B4.1.3 Control of Chiller Plant

(a) General

(i) Controllers

Built-in micro-processor based electronic controller or


DDC for each chiller plus a micro-processor based
electronic controller or DDC for chiller plant
Sequential/Step/Interfacing controls. (for chillers and
chilled water pumps controls and interfacing with ACS
and other system controllers)

(ii) Start Stop Control

Make provision for the following control functions


unless otherwise specified in the Particular
Specification or Drawings:-

- Manual on/off (maintenance/manual mode);


- On/off by the Automatic Control System as
scheduled; and
- On/off by special demand overriding the pre-set
schedule for dehumidification and/or cooling
during night purging or other special duty cycles as
specified.

(iii) Faults and Abnormal Operation Controls and


Monitoring by the Chiller Controller

- High condenser pressure;


- Low refrigerant pressure/temperature;
- High motor temperature;
- Motor overload;
- Low oil pressure;

Section B4 AC_GS
Page 2 of 24 2017 Edition
- Low oil sump temperature;
- High oil sump temperature;
- Chilled water flow interlocked;
- Condenser water flow interlock (water cooled
only);
- Back-up for the low chilled water temperature
controller (if required by the chiller manufacturer);
and
- Plus other items as specified or recommended by
the chiller manufacturer.

(iv) Fault Surveillance

Fault surveillance and safety controls of chiller shall be


carried out by the built-in electronic controller or DDC
of the chiller. Interfacing shall be provided for
communication between the built-in chiller controller
and the chiller plant controller. Interfacing system shall
also be provided for the chiller plant controller in
receiving operation instructions from the ACS and
sending out chiller status and alarm signals to the ACS
and the A/C Supervisory Control Panel.

(v) Energy Conservation

If specified in the Particular Specification or Drawings,


sufficient control provision shall be allowed in the
chiller controllers for the proper operation of the
following energy systems:-

- Heat recovery condenser for the supply of heat


source as specified;
- Cycling of condenser fans by head pressure control
for energy saving;
- Variable Speed Drive for chiller. The application
of electronic speed controller in maintaining higher
chiller energy efficiency at partial load operation;
and
- Reset of supply chilled water temperature to
optimise the chiller energy efficiency.

(b) Single Chiller

(i) Capacity Control

Make provision for the following control functions plus


other special requirements specified in the Particular
Specification or Drawings:-

Section B4 AC_GS
Page 3 of 24 2017 Edition
- Chiller output capacity modulated to maintain the
pre-set supply or return chilled water temperature
(after mixing with the by-pass); and
- The chiller controller shall modulate its
refrigeration capacity to meet the cooling load
demand in the chilled water circulation system.

(c) Multiple Chillers in Parallel

(i) Capacity Control

Make provision for the following control functions plus


other special requirements specified in the Particular
Specification or Drawings:-

(1) Built-in controller of each chiller modulates


output capacity to maintain a constant supply
chilled water temperature pre-set at the outlet of
each operating chiller; and

(2) The Chiller Plant Controller shall control the


sequencing of chillers and cut-in or cut-out a
chiller in accordance with the return chilled
water (with by-passed chilled water well mixed)
temperatures pre-set in the controller. The
sequencing logic shall be as follows :-

- Chiller that has run longest since last start


is first to stop;
- Chiller that is idle for the longest time is
first to start; and
- Chiller(s) in manual or maintenance
mode shall be by-passed from the
automatic sequencing control operation.

(d) Make provision of monitoring and Alarm Signals to ACS and


the A/C Supervisory Control Panel

Other special requirement as specified in the Particular


Specification or Drawings.

B4.1.4 Control of Chilled Water Pumping System (by chiller plant controller)

Unless otherwise specified in the Particular Specification or the


Drawings, chilled water control system shall perform the following: -

(a) Circulation Pumps with Differential Pressure By-Pass

(i) For a single chiller system, the duty chilled water pump
shall be operated as long as the system is in operation
mode. During partial load condition, excessive chilled

Section B4 AC_GS
Page 4 of 24 2017 Edition
water supply shall be by-passed by the differential
pressure by-pass valve and hence lower the system
return chilled water temperature. Dropping of the
return chilled water temperature shall then call for
refrigeration capacity control in the chiller. There is
possibility that the cooling load demand is so low that
the chiller will be cut off and at idle condition for a
period of time. However it is important to keep the
chilled water pump to run continuously for sensing the
correct chilled water temperature. The pump shall only
be cut-off when the chiller plant is turned off by the
ACS;

(ii) For a multiple chiller system, the number of chillers put


into operation and chiller refrigeration capacity controls
shall be in accordance with the system return chilled
water temperature, which is affected by the amount of
chilled water by-passed by the differential pressure by-
pass valve. Each chilled water pump shall be operated
in accordance with its associated or delegated chiller.
The delegated chilled water pump shall be cut-in earlier
than the chiller in order to maintain the chilled water
flow required for the chiller operation. The same logic
of leaving at least one chilled water pump to operate for
monitoring the chilled water temperature shall be
applied; and

(iii) Manual on/off for pumps (maintenance/manual mode).

(b) Primary and Secondary Pumps (Decoupled) System

In a typical decoupled pumping system, the primary pumps are


of constant flow and the secondary system can be of all
variable flow pumps or a combination of constant and variable
flow pumps. Exact configuration shall refer to the Particular
Specification or the Drawings.

(i) Primary chilled water pump

Primary chilled water pump shall be of constant flow


type, which shall be operated with time leading its
associated or delegated chiller and cut-out when the
associated chiller is turned off. When a reverse flow is
detected in the by-pass, an additional chiller shall be cut
in and when the by-pass flow is greater than the
designed full capacity flow rate of a chiller, an
operating chiller shall be cut off. The associated
primary chilled water pumps shall then be operated in
the same arrangement. The logic of keeping at least
one pump operated in the primary circuit (when the
system is in operation mode) is still valid.

Section B4 AC_GS
Page 5 of 24 2017 Edition
(ii) Secondary chilled water pumps

Secondary chilled water pumps shall be operated to


meet the flow demand at the load side. Discharge head
pressure or differential pressure control (across supply
and return mains of the secondary loop) shall be used to
monitor the flow demand. The secondary pumps (no
matter constant or variable flow) shall be operated in
such a configuration that a constant chilled water
supply pressure (i.e. in proportion to the amount of
chilled water supplied) is maintained and hence meets
the chilled water flow demand.

For a system with constant and variable flow pumps,


the constant flow pump(s) shall only be operated as
long as the demand flow is greater than the full capacity
of that constant flow pump. The variable speed pump
shall always be operated first to handle any partial load
demand for energy saving.

(iii) Manual on/off for all pumps (maintenance/manual


mode)

(c) Variable Primary Flow System

In a typical variable primary flow system, variable flow pumps


shall be used in conjunction with chillers that adaptable to
variable flow. The number and capacity of pumps normally
match with the capacity of chillers but not necessarily. Exact
configuration shall refer to the Particular Specification or the
Drawings.

(i) Chilled water pumps shall be operated to maintain a


pre-set differential pressure at a specific point in the
system. Whenever the control valves of air terminal
units open with an increase in cooling demand, the
pressure tends to decrease. The variable speed drive of
the pumps in operation shall be increased in such a
configuration that a constant chilled water pressure
difference between supply and return is maintained;

(ii) When the chilled water demand flow reduces with the
system load to a low load condition that the minimum
evaporator flow limit of the operating chiller, the
modulating valve in the bypass pipe shall be opened to
deliver the water necessary to maintain the minimum
flow of the chiller; and

(iii) Manual on/off for pumps (maintenance/manual mode).

(iv) Other alternative control methods shall be considered


subject to the approval of the Supervising Officer.

Section B4 AC_GS
Page 6 of 24 2017 Edition
(d) Make provision of monitoring and Alarm Signals to ACS and
the A/C Supervisory Control Panel

Other special requirement as specified in the Particular


Specification or Drawings.

B4.1.5 Control of Cooling Towers and Condenser Water System (by


condenser plant controller)

Micro-processor based electronic controller or DDC for Condenser


Water Plant Sequential/Step/Condenser Water Temperature By-Pass/
Cooling Tower Fans Cycling/Interfacing controls. (for condenser
water plant controls and interfacing with the chiller plant controller
and ACS)

(a) Start-stop Control

Condenser water pumps shall be interlocked with their


associated water-cooled chillers and shall be started in advance
and turned off after their associated chillers.

(i) Manual on/off (maintenance and manual mode)


Condenser water pumps on/off are interlocked with the
chiller plant, which is started /stopped by the ACS as
scheduled.

(ii) Cooling towers and their associated control valves shall


be opened for the reticulation of condenser water.

(iii) Once the condenser water plant is turned on, its


ancillary equipment such as water treatment plant,
condenser water filtration and cleansing devices shall
be energised accordingly.

(iv) For cooling tower system installed with multiple


cooling towers and/or standby cooling tower(s),
sequence control shall be provided to allow each
cooling tower to be operated at least one hour per week.

(b) Capacity Control

(i) For energy saving, cycling of cooling tower fans shall


be used to maintain the supply condenser water
temperature entering the chillers at the designed value.

(ii) If the supply condenser water temperature drops below


the pre-set value even with all the cooling tower fans
cut off, the temperature by-pass valve shall be
modulated to by-pass condenser water leaving the
chillers from entering the cooling tower but to mix with
the condenser water supply.

Section B4 AC_GS
Page 7 of 24 2017 Edition
(iii) For a system with variable flow pumps, the speed of
pumps shall be adjusted by the temperature of
condensing water leaving the chillers or maintaining a
designed temperature difference between condensing
water supply and return to chillers. The water flow shall
be reduced with decreasing cooling demand and hence
the heat rejection capacity, while the minimum
condensing flow limit shall be satisfied at all time.

(iv) Other alternative control methods shall be considered


subject to the approval of the Supervising Officer.

(c) Faults and Abnormal Operation Controls and Monitoring by


the Condenser Water Plant Controller

(i) High condenser water temperature.

(ii) Extra high condenser water temperature. (chillers to be


cut off one by one if so specified)

(iii) Low water level of cooling towers.

(iv) Faults of cooling tower fans.

(v) Faults of condenser water pump. (associated chiller to


cut off)

(vi) Faults of water treatment plant(s).

(vii) Faults of condenser water filtration and cleansing


equipment.

(viii) Plus other items as specified or recommended by the


condenser water plant manufacturer.

(d) Make Provision of Monitoring and Alarm Signals to ACS and


the A/C Supervisory Control Panel

Other special requirement as specified in the Particular


Specification or Drawings.

B4.1.6 Control of Primary Air Handling Unit (PAU)

Micro-processor based electronic controller or DDC as specified shall


be used for the control of the PAU, its associated equipment and the
interfacing and communication with the ACS and its associated zone
AHUs, FCUs, etc. The following functions shall be provided unless
otherwise specified: -

(a) Start-stop Control

Section B4 AC_GS
Page 8 of 24 2017 Edition
(i) Automatic fire tripping as specified or required by the
FSD;

(ii) Manual on/off control (maintenance/manual mode);

(iii) On/off control by the ACS as scheduled;

(iv) On/off controls by special demand overriding the pre-


set schedule for dehumidification and/or cooling during
night purging or other special duty cycles as specified;

If so specified in the Particular Specification or the


Drawings, the demand control function in sub-clause (v)
below shall be adopted; and

(v) Demand on/off control. The operation of any AHU/


FCU served by the unit shall energise the PAU. Unit
will only be cut-out when all associated AHUs/FCUs
are turned off or the whole system is turned off by the
ACS as scheduled.

(b) Capacity Control

(i) For constant air flow design

Constant flow, full capacity at all the time during


operation.

(ii) For variable air flow design

- Air flow modulated by variable speed drive in


order to reduce the indoor CO2 level within the
specified range (applicable for single zone system
only); and

- Air flow modulated by variable speed drive to


maintain the pre-set static pressure at the main
supply air duct. Amount of fresh air supply to
each zone shall be controlled by motorised damper,
which is modulated to reduce the indoor CO2 level
at that particular zone to be within the range
specified (applicable for multi-zone system).

(c) Temperature and Relative Humidity Control

(i) Temperature Control

- Cooling (outdoor air temperature higher than the


pre-set value)

If the supply air temperature rises above the pre-set


upper temperature, chilled water flow through the

Section B4 AC_GS
Page 9 of 24 2017 Edition
cooling coil of the PAU shall be increased by a
modulating valve and vice versa when the supply
air temperature drops below the pre-set lower
temperature. The controller shall respond to
modulate the control valve in maintaining the pre-
set supply air temperature.

- Heating (outdoor air temperature lower than the


pre-set value)

The supply air temperature is maintained within


the range specified by modulating the control
valve and hence regulating the amount of hot water
(for space heating) from entering the heating coil
of the PAU or for electric heating by staging of
electric heaters to maintain the supply air
temperature specified.

(ii) Humidity Control

- Dehumidification (when the outdoor air


enthalpy/moisture content is higher than the pre-set
cut-in value)

Despite of the PAU is in cooling mode or heating


mode, the humidistat shall modulate the chilled
water control valve to open for dehumidification
until the humidity condition of the outdoor air
drops below the pre-set cut-out value. If the
supply air temperature drops below the lower limit
due to the dehumidification process, the hot water
coil or electric heaters shall be actuated for re-
heating.

If so specified in the Particular Specification or the


Drawings, the dehumidification process shall be
carried out by a separate dehumidification system
installed at the fresh air intake section.

- Humidification (outdoor air relative humidity


lower than the pre-set value)

Humidification process is not taken place in the


PAU. If the room humidity condition at the space
inside the building is lower than the value
specified, humidification by means of steam or
water spray humidifier shall be operated at the
relevant AHUs. For fan coil system, individual
room/zone humidifier or system shall be used as
specified.

(d) Filters and Air Cleaners

Section B4 AC_GS
Page 10 of 24 2017 Edition
Controller of PAU shall also control the proper operation of its
ancillary equipment such as automatic air filter, air cleaner, air
steriliser, etc. Unless otherwise specified, the following alarm
signals shall be sent to the A/C Supervisory Control Panel:-

(i) Filter clog alarms;

(ii) Filter detached from filter chamber;

(iii) Time for replacement of absorption filters; and

(iv) Status and fault alarms of air cleaner & steriliser.

(e) Make provision of monitoring and Alarm Signals to ACS and


the A/C Supervisory Control Panel

Other special requirement as specified in the Particular


Specification or Drawings.

B4.1.7 Control of Air Handling Unit (AHU)

Micro-processor based electronic controller or DDC as specified shall


be used for the control of the AHU and its associated equipment and
the interfacing and communication with the ACS and its associated
zone terminal, VAV units, etc. The following functions shall be
provided unless otherwise specified: -

(a) Start-Stop Control

(i) Same as Clause B4.1.6 (a).

If so specified in the Particular Specification or the


Drawings, the demand control function in sub-clause (ii)
below shall be adapted; and

(ii) Demand on/off control. The operation of any VAV


unit served by the unit shall energise the AHU. Unit
shall only be cut-out when all associated VAV units are
turned off or the whole system is turned off by the ACS
as scheduled.

(b) Capacity Control

(i) For Constant Air Volume System

Single zone constant volume; full flow capacity to a


single zone at all the time during operation (applicable
for single zone system only); and

Multi zone constant volume, the amount of air supplied


to each zone is still constant. However zone reheater

Section B4 AC_GS
Page 11 of 24 2017 Edition
shall be provided at each zone for temperature control
(applicable for multi zone system).

(ii) For Variable Air Volume System

Airflow modulated by variable speed drive to maintain


the pre-set static pressure at the main supply air duct.
Amount of air supplied to each zone shall be controlled
by motorised damper of each VAV unit. The VAV
damper shall be modulated to open or close in order to
maintain the room temperature/supply air flow rate to
be within the range specified.

(c) Temperature and Relative Humidity Control

(i) Temperature Control for Constant Air Volume Systems

- Cooling

If the room air temperature rises above the pre-set


upper temperature, chilled water flow through the
cooling coil of the AHU shall be increased by
opening the modulating valve and vice versa when
the room air temperature drops below the pre-set
lower temperature. By modulating the control
valve, chilled water flowing through the cooling
coil of the AHU shall be regulated to meet the
cooling demand load.

- Heating

The room air temperature shall be maintained


within the range specified by the control valve and
hence the amount of heating hot water from
entering the heating coil of the AHU or by staging
of electric heaters to maintain the room air
temperature specified.

(ii) Temperature Control for Variable Air Volume Systems

Unless otherwise specified, the supply air temperature


at the discharge of a variable air volume AHU shall be
maintained at a pre-set value by controlling the flow of
chilled/hot water entering the cooling/heating coil.
Space/room temperatures shall be controlled by the
VAV units as described in Clause B4.1.8 (b) of this
General Specification.

(iii) Humidity Control

- Dehumidification (indoor air relative humidity


higher the pre-set value)

Section B4 AC_GS
Page 12 of 24 2017 Edition
Despite of the AHU is in cooling mode or heating
mode, the humidistat shall modulate the chilled
water control valve to open for dehumidification
until the relative humidity of the room air drops
below the pre-set cut-out value. If the room air
temperature drops below the lower limit, the hot
water coil or electric heaters shall be actuated for
re-heating.

If so specified in the Particular Specification or the


Drawings, the dehumidification process shall be
carried out by a separate dehumidification system
installed at the air handling system.

- Humidification (indoor air relative humidity lower


than the pre-set value)

If the room relative humidity at the space inside


the building is lower than the value specified,
humidification by means of steam or humidifier
shall be provided at the relevant AHUs as specified.

(iv) Temperature Display

LCD or 7-bit segment (self-illuminated) digital display


of the room temperature thermostat within readable size
from three metres apart at the appropriate locations
inside the air-conditioned areas shall be provided.
Temperature display shall be setting up in steps not
coarser than 0.5K. Numbers of the display units shall
be in accordance with the air-conditioning layout
design and to be specified in the Particular
Specification.

(d) Fresh Air Supply Control

CO2 sensor at return air of AHU shall be used to modulate the


fresh air intake damper. Sufficient amount of fresh air shall be
sucked in to reduce CO2 level at all zones to be within the
range specified. If so specified, a minimum amount of outdoor
air supply shall be maintained for the proper pressurisation of
the air-conditioned areas.

(e) Filters and Air Cleaners/Sterilisers

Same as Clause B4.1.6 (d).

(f) Make provision of monitoring and Alarm Signals to ACS and


the A/C Supervisory Control Panel

Section B4 AC_GS
Page 13 of 24 2017 Edition
Other special requirement as specified in the Particular
Specification or Drawings.

B4.1.8 Control of Zone Air Distribution Units

(a) Fan Coil Unit (FCU)

Unless otherwise specified, controller for FCU shall be of


micro-processor based electronic type or DDC type as
specified. Backup battery shall be provided for all
programmable controller and controller with real time clock.
Unless otherwise specified, the control functions listed below
shall be performed by the controller:-

(i) Start-stop control

- Automatic fire tripping as specified or required by


the FSD. Automatic reset is required once the fire
signal is clear;
- Manual on/off control by the three-speed controller;
- c/w space temperature sensor; and
- Automatic on/off control by ACS as scheduled
plus manual override control located at
management office or other location as specified
(for public areas, corridor, etc.).

If so specified in the Particular Specification or the


Drawings, the following control function shall be
adopted.

Automatic on/off control by Occupancy Detector (dual


mode) plus manual override control by three-speed
controller c/w space temperature sensor.

(ii) Temperature Control

- Cooling

Motorised on/off control valve shall be turned on


and off to maintain the room temperatures pre-set
in the controller. Chilled water shall only flow
through the cooling coil of the FCU when the FCU
is turned on and the control valve is opened.

- Heating

When the controller is set to the heating mode, the


electric heater shall be turned on and off to
maintain the room temperatures set in the
controller. If hot water heating is used, a

Section B4 AC_GS
Page 14 of 24 2017 Edition
motorised on/off control valve shall be turned on
and off to maintain the room temperatures set.

- Temperature Display

LCD or 7-bit segment (self-illuminated) digital


display of the room temperature thermostat within
readable size from three metres apart inside the air-
conditioned areas shall be provided. Temperature
display shall be setting up in steps not coarser than
0.5K.

(iii) Fresh Air Supply Control

For a variable volume primary air supply system, a


zone CO2 sensor shall be used to control a modulating
damper, which will increase or decrease the amount of
fresh air supply from the PAU to a FCU or a group of
FCUs in the same control zone. The motorised damper
shall be modulated to reduce CO2 level to be within the
range pre-set. If so specified in the Particular
Specification, a minimum amount of fresh air supply
shall be maintained when individual FCU or any zone
FCU is switched off. A separate electronic controller
or DDC instead of the FCU controllers shall be used for
the control of this fresh air modulating system.

(iv) Monitoring & Alarm Control

Unless otherwise specified, the following controls shall


be incorporated in the controller of each FCU and
signals and alarms shall be sent to the zone or main
supervisory control panel as specified:-

- Filter clog alarms;


- Overheat of electric heater; and
- Room temperature outside upper and lower limits
pre-set.

(b) Variable Air Volume (VAV) Unit

Controller for VAV unit shall be of micro-processor based


electronic type or DDC type as specified. Backup battery shall
be provided for programmable controller and controller with
real time clock. Unless otherwise specified, the control
functions listed below shall be performed by the controller:-

(i) Start-Stop Control

- Automatic fire tripping as specified or required by


the FSD. Automatic reset is required once fire
signal is clear;
Section B4 AC_GS
Page 15 of 24 2017 Edition
- Manual on/off control by user; and
- Automatic on/off control by ACS as scheduled
plus manual override control located at
management office or other location as specified
(for public areas, corridor, etc.).

If so specified in the Particular Specification or the


Drawings, the following control function shall be
adopted.

Automatic on/off control by Occupancy Detector (dual


mode) plus manual override control.

(ii) Temperature Control

- Cooling

Unless otherwise specified, pressure independent


type VAV units shall be adopted.

- Pressure Independent Type

The room temperature sensor shall send signal to


the controller, which works together with the
supply air flow measuring device and shall actuate
the motorised modulating control damper to supply
the designed amount of cooled air required in
maintaining the room temperature pre-set. With
the installation of the air flow measuring device,
adjustment of the supply air quantity shall not be
affected by the fluctuation of the supply air
pressure at the distribution air duct and be well
within the design limits. There shall also be a
minimum open position in the control damper to
maintain the minimum air movement and fresh air
to the room. If the room temperature continues to
drop when the damper is already at its minimum
open position, reheat or supply temperature reset is
required as specified.

- Heating / Reheating (for VAV units with heating


and reheating)

The electric heater shall be turned on and off to


maintain the room temperatures and humidity set
in the controller. If hot water heating is used,
motorised control valve shall be turned on and off
to maintain the room temperatures set.

Section B4 AC_GS
Page 16 of 24 2017 Edition
- Temperature Display

LCD or 7-bit segment (self-illuminated) digital


display of the room temperature within readable
size from three metres apart inside the air-
conditioned areas shall be provided. Temperature
display shall be as described in B4.1.7(c)(iv) and
the numbers of the display unit required are to be
specified in the Particular Specification.

(iii) Fresh Air Supply Control

Fresh air supply control is generally carried out in the


AHU. If so specified, zone CO2 sensor shall be
installed to send a signal to the room VAV unit(s) for
higher supply air quantity (i.e. more fresh air in
proportion). Excessive cooling effect shall be offset by
reheating or reset of supply air temperature in the AHU.

(iv) Monitoring, Alarm and Other Controls

Unless otherwise specified, the following controls shall


be incorporated in the controller of each VAV unit and
signals and alarms shall be sent to the zone or main
supervisory panel as specified:-

- Flow sensor clog alarm (flow detected beyond


limits);
- Overheat of electric heater;
- Room temperature outside upper and lower limits
set; and
- Part load signal to the AHU for supply air
temperature reset.

B4.1.9 Ventilation System Control

(a) Toilet Exhaust System

(i) Start/stop

- Automatic fire tripping as specified or required by


the FSD. Automatic reset is required once fire
signal is clear.
- Manual on/off (for manual operation and
maintenance) plus
- On/off by ACS as scheduled; or
- On/off interlocked with lighting of the room if
specified.

Section B4 AC_GS
Page 17 of 24 2017 Edition
(ii) Capacity Control

Unless otherwise specified, constant exhaust air flow


rate.

(b) Printer Room Exhaust System

Same as Clause B4.1.9 (a).

(c) Plant Room Ventilation System

(i) Start/stop

- Manual on/off (for manual operation and


maintenance) plus
- On/off by ACS as scheduled; or
- On/off by thermostat or other local sensing devices
as specified.

(ii) Capacity Control

Unless otherwise specified, constant exhaust air flow


rate.

(d) Car Park Ventilation System

(i) Start/stop

- Automatic fire tripping as specified or required by


the FSD.
- Manual on/off (for manual operation and
maintenance) plus
- On/off by ACS as scheduled; or
- On/off or modulated by zone CO and/or NO2
sensors as specified.

(ii) Capacity Control

- Constant air flow rate;


- Variable air flow by staging of multi-fans; or
- Variable airflow by variable speed fans.

Unless otherwise specified, all demand ventilation


systems using CO/NO2 sensors shall be equipped with
variable speed fans for energy saving.

(e) Make Provision for the Monitoring and Alarm Signals to ACS
and the A/C Supervisory Control Panel

Section B4 AC_GS
Page 18 of 24 2017 Edition
Other special requirement as specified in Clause C5.54 of this
specification or the Particular Specification or Drawings.

B4.2 GENERAL REQUIREMENTS

B4.2.1 Control Equipment Features

Basic adjustments for original setting (such as control characteristic,


wind and sun effect settings, set-back, boost, etc.) shall be concealed
and tamper proof and housed within lockable panels. Temperature
setting scales shall be clearly marked in C.

Unregulated power supplies shall be filtered. Shielded cable shall be


used when it is necessary to install DC signal leads in the same
control wiring conduit.

Suitable support and easy access facilities shall be equipped for all
sensors, monitoring and measuring equipment. Suitable protection
guard against damage shall be provided for equipment exposed to
public contact.

B4.2.2 Sensing Elements in Liquids

(a) Elements sensing liquid temperature in pipework shall be: -

(i) Provided with means for withdrawal for calibration,


servicing, etc., without the need for draining the system;

(ii) Positioned so that the active part of the element is


wholly within the liquid;

(iii) Positioned so that the element is not less than 10 pipe


diameters downstream from a point of mixing, unless
otherwise recommended by the manufacturer;

(iv) Positioned so that sufficient length of flexible conduit


can be allowed to permit complete withdrawal of the
element; and

(v) Positioned downstream from the valve, after the pumps,


for the control of mixed flow temperature using mixing
valves.

(b) Elements sensing liquid flow in pipework shall be positioned


so that: -

(i) The element is mounted in a section of pipe where there


is a straight run of at least five pipe diameters on each
side of the flow switch;

Section B4 AC_GS
Page 19 of 24 2017 Edition
(ii) The element is mounted so that the terminals or wire
leads are easily accessible for wiring; and

(iii) The element must not be subjected to water hammering.


If a fast-closing valve is located downstream of the
element, a suitable water hammer arrester must be used.

B4.2.3 Sensing Elements in Air or Gases

(a) Elements sensing the temperature of air in room or other such


space shall be: -

(i) Positioned so that the element is not subjected to


thermal radiation and shall be away from door,
windows, and heat sources, etc.;

(ii) Positioned so that all conduit openings are sealed to


avoid false temperature measurement; and

(iii) Positioned in a representative position.

(b) Elements sensing the temperature of air in a duct shall be


positioned so that: -

(i) The element is not subjected to thermal radiation;

(ii) The active part of the element is wholly immersed in


the controlled air stream;

(iii) The element in supply air duct is fitted a few metres


downstream from the heating coil;

(iv) The element in extract air duct is fitted before the


extract fan to avoid thermal radiation influence;

(v) Temperature stratification is accounted for, (i.e.


positioning for low temperature limit sensing,
positioning for high temperature limit sensing,
positioning for average temperature sensing);

(vi) If of the capacity averaging type, it is installed on a


suitable framework and is suitably arranged for
servicing; and

(vii) If used for determining the dew point, the air adjacent
to the element is known to be saturated within
acceptable limits.

(c) Elements sensing the temperature of a solid surface shall be


positioned and fixed so as to give good thermal contact.

Section B4 AC_GS
Page 20 of 24 2017 Edition
(d) Elements sensing the temperature of air external to a building
shall be positioned: -

(i) Generally as indicated and away from the influence of


direct solar radiation and local heat gains;

(ii) Far away from the warm air outlets such as windows or
extract; and

(iii) Where special requirements are indicated (e.g. the


determination of solar gain, or wind influence), the
control sensor manufacturers recommendations for
positioning the sensors shall be followed.

(e) Humidity sensing element shall be positioned: -

(i) In a representative of the space in which the humidity is


being measured;

(ii) Such that the air velocity is within the range required
by the sensing element; and

(iii) To ensure that the air reaching the element is free from
airborne contaminants.

(f) Element sensing both temperature and humidity shall be: -

(i) Positioned so that the element is not subjected to


thermal radiation and shall be away from door,
windows, and heat sources, etc.;

(ii) Positioned so that all conduit openings are sealed to


avoid false temperature measurement; and

(iii) Positioned in a representative position.

(g) Elements sensing differential pressure of air in a duct shall be


positioned so that: -

(i) Sensor stem is fully immersed in the controlled air


stream;

(ii) Differential air switch shall be positioned where it will


not be exposed to corrosive or flammable atmosphere
or vibration;

(iii) The pressure switch shall be mounted on a vertical


surface and has two air pressure tappings which are
connected with tubing to the sensing points in the duct;

Section B4 AC_GS
Page 21 of 24 2017 Edition
(iv) The mounting method of the pressure transmitter shall
be subjected to the manufacturers recommendations;
and

(v) All sensors shall be arranged to give convenient access


for servicing the sensor.

(h) Elements sensing carbon dioxide of air in a room shall be


positioned so that: -

(i) Areas with low air exchange or close to supply air


outlets; windows, doors, etc. shall be avoided;

(ii) The sensors shall be mounted at a minimum of 2 m


above finished floor level;

(iii) All sensors for any individual installation shall be of


same appearance; and

(iv) For sensors exposed to view, the precise location shall


be approved by the Supervising Officer.

(i) Elements sensing carbon dioxide of air in a duct shall be


positioned so that: -

(i) Sensor is mounted with rigid support in the return duct


in a position far away from external heat sources;

(ii) Sensor stem shall be fully immersed in the controlled


air stream; and

(iii) All sensors shall be arranged to give convenient access


for servicing the sensor.

(j) Elements sensing carbon monoxide and nitrogen dioxide for


carpark shall be positioned so that: -

(i) The Practice Notes on Control of Air Pollution in Car


Parks issued by the Environmental Protection
Department shall be complied;

(ii) The exact quantities of sensors shall be based on the


regulation but not less than 500m2 per one detector;
and

(iii) For sensors exposed to view, the precise locations shall


be approved by the Supervising Officer.

(k) Air velocity sensors shall be: -

(i) Sensor tube made of stainless steel material carrying a


scale to indicate the immersion length; and

Section B4 AC_GS
Page 22 of 24 2017 Edition
(ii) The location and immersion length shall be in
accordance with the manufacturers recommendation.

(l) Sensing elements shall in all cases be installed in accordance


with the manufacturers recommendations and instructions.

(m) All room or space mounted sensing elements to temperature or


humidity for any individual installation shall be of the same
appearance.

(n) For sensors exposed to view, the precise location shall be


approved by the Supervising Officer.

(o) All sensors shall be arranged to give convenient access for


servicing.

B4.3 AIR COOLING CONTROL

B4.3.1 Control valves used for heating or cooling circuits shall be provided
with an isolating valve on each port. The isolating valve on the by-
pass port being of the double regulating type to enable regulation
such that the pressure drop through the by-pass can be set to equal to
that through the cooling coils.

B4.3.2 The control valves shall be quiet in operation.

B4.3.3 All valves shall operate in sequence with another valve when required
by the sequence of operations.

B4.3.4 All control valves shall be suitable for the system flow conditions and
close against the differential pressures involved.

B4.4 AIR HEATING CONTROL

B4.4.1 Control valves used for heating or cooling circuits shall be provided
with an isolating valve on each port. The isolating valve on the by-
pass port shall be of the double regulating type to enable regulation
such that the pressure drop through the by-pass can be set to equal to
that through the heating coils.

B4.4.2 Electric air heaters shall be energised in three phase-balanced stages


not exceeding 6 kW per three-phase stage. Single-phase stages shall
not be more than 2 kW each. There shall be a time lag of not less
than five seconds between successive stages on demand for heating.

B4.4.3 Arrangements shall generally be such that in the event of electrical


supply failure, or after normal shut down, the control system will
recycle to the "OFF" position. Unless otherwise specified, the control
sequence shall start automatically.

Section B4 AC_GS
Page 23 of 24 2017 Edition
A vane or differential pressure switch wired in series with the high
limit temperature cut-outs shall also be provided to switch off the
heater in the event of a fan or other failure. Any cut out on these
items shall require to be manually reset.

B4.4.4 The control valves shall be quiet in operation.

B4.4.5 All valves shall operate in sequence with another valve when required
by the sequence of operations.

B4.4.6 All control valves shall be suitable for the system flow conditions and
close against the differential pressures involved.

B4.5 ELECTRICAL/ELECTRONIC (LOCALISED) CONTROL SYSTEM

B4.5.1 The systems shall be operated at single-phase mains voltage or at


extra low voltage such as 12 or 24 V as indicated in the Particular
Specification.

B4.5.2 Where a particular manufacturers system is offered and accepted, the


Installations shall be installed to comply with that manufacturers
recommended technical details and methods of installation.

Section B4 AC_GS
Page 24 of 24 2017 Edition
SECTION B5

CENTRAL CONTROL AND MONITORING SYSTEM (CCMS)

B5.1 GENERAL REQUIREMENTS

B5.1.1 Complete Building Automation System

The system shall perform the general functions for ACMV


installation and shall incorporate the facilities for developing other
building automation systems, such as automatic fire alarm, automatic
security and access control in future without replacement of existing
equipment. Energy Management is an integral part of the CCMS;
other management functions that include self-diagnostics,
maintenance and facilities shall also be made available for future
connection. Unless otherwise specified in the Particular Specification,
a central uninterrupted power supply (UPS) with suitable capacity not
less than 60 minutes shall be equipped for the CCMS.

B5.1.2 Compliance with Various Codes/ Standards

The Installations shall comply with the standards as described below


where applicable: -

(a) International Organization for Standardization ISO/IEC 9075-


9:2008/Corr 1:2010 -Information Technology - Database
Languages - SQL Part 9: Management of External Data
(SQL/MED), ISO/IEC 9075-10:2008/Corr 1:2010
Information Technology Database Languages SQL Part
10: Object Language Bindings (SQL/OLB), ISO/IEC 9075-
13:2008/Corr 1:2010 Information Technology Database
Languages SQL Part 13:SQL Routines and Types Using
the Java TM Programming Language (SQL/JRT);

(b) International Telecommunication Union Recommendation


V.90 A digital modem and analogue modem pair for use on
the Public Switched Telephone Network (PSTN) at data
signalling rates of up to 56000 bit/s downstream and up to
33600 bit/s upstream and Recommendation X.25 Interface
between Data Terminal Equipment (DTE) and Data Circuit-
terminating Equipment (DCE) for terminals operating in the
packet mode and connected to public data networks by
dedicated circuit;

(c) ASHRAE Standard 135-2012 - A Data Communication


Protocol for Building Automation and Control Networks
(BACnet);

(d) ANSI /CEA-709.1-B - Control Network Protocol Specification


(known as Lon talk);

Section B5 AC_GS
Page 1 of 9 2017 Edition
(e) TIA/EIA 232-F, Interface Between Data Terminal Equipment
and Data Circuit Terminating Equipment Employing Serial
Binary Data Exchange;

(f) TIA/EIA 485-A (August 2008), Electrical Characteristics of


Generators and Receivers for use in Balanced Digital
Multipoint Systems;

(g) TIA/EIA 568-C.1(February 2009), Commercial Building


Telecommunications Cabling Standard;

(h) Transmission Control Protocol/Internet Protocol of Defence


Advanced Research Project Agency (TCP/IP);

(i) International Organization for Standardization ISO/IEC


1989:2014- Information Technology Programming
Languages COBOL; and

(j) International Organization for Standardization ISO/IEC 8802-


3:2014 Standard for Ethernet

B5.1.3 Expandability

The Installations shall be expandable at all levels as described in the


following sections using the same software interface that replacement
of either the workstation software or field controllers are not required.

B5.1.4 Submittals

(a) Working drawings shall be prepared in AutoCAD software of


A0 or A1 size, unless otherwise specified.

(b) Working drawing submissions shall include a block diagram


depicting locations of all controllers and workstations with
associated network wiring.

(c) Working drawing submissions shall also include schematic


diagrams for ACMV installations indicating all connected
points with reference controllers. Details and typical
installation should be shown.

(d) Manufacturers data on all hardware and software products


shall be indicated clearly. Other equipment such as valve,
damper and airflow stations shall be shown with size,
configuration, capacity and location of fixing.

(e) Software submittals shall be detailed with description of


sequences of operation, program listings, point lists and the
design of graphics, reports, alarms and configuration to be
furnished with the workstation software.

Section B5 AC_GS
Page 2 of 9 2017 Edition
(f) Operation and maintenance manual together with CAD CD
Rewritable Storage Media shall be submitted to the
Supervising Officer in accordance with the Contract
requirement.

B5.1.5 System Clean up

Upon completion, the A/C Contractor shall check and clean all
equipment pertinent to installation. Such cleaning shall extend to the
exposed surfaces of tubing, hangers and other exposed metal of
grease, plaster and other areas around the equipment.

B5.1.6 System Start-up & Commissioning

Upon complete installation prior to put into operation, the A/C


Contractor shall ensure the work as described below is being carried
out and the results are satisfactory: -

(a) All equipment shall be calibrated and the transmission media


operation shall be verified before the system is put into
operation. The work shall include testing for both hardware
and software functionality of each point in the system as well
as the sequence of operation of ACMV sub-systems under the
CCMS control;

(b) The A/C Contractor shall carry out the commissioning that
includes field testing, calibrating and adjusting and set in
operating conditions for all major installations such as chilled
water, hot water and all air handling systems under the
direction of the manufacturer or its authorised representatives;
and

(c) Operation parameters and control settings shall not be


modified without notification to the Supervising Officer.

B5.1.7 Operation and Maintenance Manual

Operation and maintenance manual together with CAD CD


Rewritable shall be submitted to the Supervising Officer in
accordance with the Contract requirement: -

(a) It shall contain all details necessary for operation, maintenance,


replacement, installation and parts procurement for the system;

(b) It shall include specific part numbers and software versions


and dates together with a complete list of spare parts;

(c) It shall include relevant as-built drawings, test certificates and


commissioning records;

(d) It shall include a copy of all application software both in


written form and on diskette;

Section B5 AC_GS
Page 3 of 9 2017 Edition
(e) It shall include step-by-step system recovery procedures for
system re-start up after fatal breakdown. Such procedures
shall be properly demonstrated to the Supervising Officers
Representatives during the T&C. Any special tools required
for system re-start shall be supplied together with the System;
and

(f) It shall include all necessary passwords to initiate functioning


of the complete CCMS to initial start-up and to work after any
modification or reprogramming.

B5.1.8 Training

Adequate training shall be provided to the operators for the day-to-


day operation and future maintenance. Unless otherwise specified,
the training should include both on-site and classroom courses with
training handouts/manuals to the designated personnel, details as
follows: -

(a) On Site Training

It shall consist of a minimum of 30 working days of hands-on


instruction geared at the operation and maintenance of the
systems. The activities shall include:-

(i) System overview;

(ii) System software and operation;

(iii) Operation sequences including start-up, shutdown,


adjusting and balancing;

(iv) Equipment maintenance; and

(v) Data logging and Alarm reporting.

(b) Classroom Training

It shall contain a comprehensive understanding of the


hardware and software course materials covering workstation
operation and controller programming. The number of
attendance and period should be agreed with the Supervising
Officer and should not be less than two weeks, unless
otherwise specified in the Particular Specification.

B5.1.9 Warranty

(a) During the Maintenance Period, the A/C Contractor shall


provide all services, materials and equipment necessary for
proper operation of the system.

Section B5 AC_GS
Page 4 of 9 2017 Edition
(b) The A/C Contractor shall be responsible for all necessary
revisions to the software as required to provide a complete and
operable system being consistent with the sequence of
operations. All updates to the manufacturers software shall
bear no extra costs.

B5.2 SYSTEM ARCHITECTURE

B5.2.1 General

It shall be either a single network or a hierarchical system architecture


that may be a multi-user computer system to allow remote access as
specified in the Particular Specification.

B5.2.2 Level 1 Network

It should be the highest level that is developed for management on a


wide area fast speed network based on open protocol.

B5.2.3 Level 2 Network

It should be a high performance peer-to-peer operation level network


that shall be able to connect to remote sites. This level shall apply for
a single network system.

B5.2.4 Level 3 Network

It should be local area network with DDC controller for


communication that shall be able to extend its performance and
capacity by using remote sub-system controllers. The sub-system
controller shall be microprocessor-based stand-alone controller
capable of operation of ACMV installations independently.

B5.2.5 Local Area Network (LAN)

The system shall be able to segment through software into multiple


local area networks distributed over a wide area network with a
standalone DDC controller and communicate with other controllers
on the network via a network controller unit.

B5.2.6 Standard Network Support

The workstations, controllers and file server, etc. shall be able to use
standard network components to utilise the existing network and/or
structural cabling system.

B5.2.7 Remote Communication

It shall be able to manage remote system via standard component of


software that is being incorporated.

Section B5 AC_GS
Page 5 of 9 2017 Edition
B5.2.8 System Expansion

The system shall be able to expand memory and enhance


programming language and to upgrade all existing controllers and
remote control units without interrupting its operation. The system
shall be able to expand 20% of the system hardware and software
points without adverse effect on the system performance.

B5.2.9 Support for Open System Protocols

The network shall be capable of integration of the open system


protocols such as BACnet, Lon Talk, etc.

B5.3 ELECTRICAL WIRING

The works shall be carried out in compliance with the requirements of the
Electrical General Specification (See Clause A2.1) and Section B7 of this
Specification and should comply with application guidelines of TIA/EIA 568-
C.1 / TIA/EIA 485-A / TIA/EIA 232-F whenever applicable.

The A/C Contractor shall provide all wiring work and electrical devices and
material necessary to complete the Controls and Instrumentation System.
Complete metal cable trays or enclosures shall be provided for conductors
throughout all systems specified. Equipment and devices, which are not
constructed with housings for mounting and enclosing all live parts, shall be
installed in metal cabinets. All equipment, enclosures, cable trays, etc., shall be
appropriate for the atmosphere and hazards encountered within their associated
areas.

"Low" and "line" voltage wiring shall be done in strict accordance with the
authority referred to this Section as mentioned above. Conduit shall be
concealed in building construction in all finished spaces. Conduit runs exposed
shall be run in a parallel manner to building surfaces. Conduit shall be
supported in approved manner. Rigid conduit shall be used in all concrete pours.
All connections from instruments shall terminate on terminal strips, properly
tagged for ease of identification, located in control centres. No splices or
junctions of wirings will be permitted in the field.

The A/C Contractor shall provide all interlock wiring required to make system
operate in accordance with the drawings and specifications. All wiring
diagrams, etc., required shall be provided and co-ordinated. Wiring shall begin
on terminals of control device and terminate on terminals of controlled device.

The term "wiring" shall include wire, conduit, wiring device, conduit
boxes/accessories and miscellaneous materials and labour required for mounting
and wiring electrical control devices and services.

Section B5 AC_GS
Page 6 of 9 2017 Edition
B5.4 HARDWARE INSTALLATION

The Installations shall comply with Statutory Requirements as specified in


Section A2.

B5.4.1 Wiring and Tubing

Unless otherwise specified, wiring shall be dedicated runs with


separate circuit breaker and each run shall include a separate neutral
and ground wire.

A proper earth system shall be provided and should be separated from


other services for dedicated run.

Wires shall be properly fixed at intervals.

Wires shall be kept away from hot water pipe, steam and condensing
piping, etc.

Wires shall not run across telephone equipment.

Unless otherwise specified, all conduits shall be of galvanised steel.

Surface conduits shall be installed in plant room or other area as


approved by the Supervising Officer.

Flexible conduits shall be adapted for connection to the equipment


and/or sensors, etc.

Control air tubing shall be in concealed run unless otherwise


approved by the Supervising Officer.

All control tubing run in surface to controls, control panels or run in


equipment rooms, plant rooms, apparatus rooms, mechanical shafts
and return air plenums, etc. shall be enclosed in metal raceway.

All control air tubing shall be thoroughly cleaned before putting the
system into operation.

B5.4.2 Field Devices

The Installations shall comply with Clause B4.2 whenever applicable.

Thermal conduction compound shall be applied to ensure good heat


transfer to the well-mounted sensor.

Sensors installed on pipeline shall be removable without shutting


down the system.

Section B5 AC_GS
Page 7 of 9 2017 Edition
The high-pressure port of the duct type static pressure sensors shall be
connected to a metal static pressure probe that shall be inserted into
the duct pointing upstream. While the low pressure port shall be left
open to the plenum area at the point that the high-pressure port is
being tapped into the air duct.

Building static sensors shall be installed with the high-pressure port to


be inserted into the space via a metal tube and the low-pressure port
to outside.

Actuators shall be installed firm and be mounted to give a positive


movement throughout 100 percent of the stroke.

The relays shall be installed such that transient suppression shall be


across all coils.

B5.4.3 Enclosures

All field interface devices shall be mounted in a panel that shall be


provided with enclosures to protect from dusts and moisture.

The panel shall be adequate for installation of power supply for


sensors, interfacing relays, contactors, safety circuits and transducers,
etc.

Sufficient heat dissipation device shall be provided to prevent over-


heat of equipment.

The panel shall be steel enclosure with hinged door, keyed lock and
earthed.

All outside mounted enclosures shall be weatherproof type.

B5.4.4 Identification

All control wires and pneumatic tubing shall be identified with


labelling tape or sleeves using word, letters, or numbers that will be
cross-reference with the as-built drawings.

All field enclosures shall be identified with nameplates.

All junction boxes shall be marked to identify for "CCMS".

All field devices mounted inside the panel shall be labelled.

All field devices outside the panel shall be identified with nameplate.

B5.4.5 Location

The panel for enclosing interface devices shall be installed


immediately adjacent to the controller panels being interfaced.

Section B5 AC_GS
Page 8 of 9 2017 Edition
Room humidity or temperature sensors shall be mounted away from
the machines that would generate heat, direct sunlight and diffuser air
streams.

Outside air sensors shall be mounted on suitable location on the north


building face directly in the outside air.

B5.5 SOFTWARE INSTALLATION

B5.5.1 General

All system software under the Contract including operating software


and the third parties software shall be installed initialised, started-up
and debugged.

B5.5.2 Database Configuration

The Installations shall comply with the schedule in Clause C5.55 and
other schedules as specified in the Particular Specification.

B5.5.3 Colour Graphic Slides

The graphic displays shall be installed in accordance with the floor


layout plans and the schematic diagrams, etc. Also, the display shall
consist of associated points identified in the point list and shall allow
for set point changes as specified.

The full list of graphic slides, legend and fonts shall be approved by
the Supervising Officer.

B5.5.4 Reports

The Installations shall configure a certain report to be issued as


specified. The A/C Contractor shall provide adequate paper for
periodic reports.

B5.5.5 Documentation

It shall cover all software being installed that shall include description
of point lists and alarm list, printouts of all reports and graphics,
application program listing, etc.

Section B5 AC_GS
Page 9 of 9 2017 Edition
SECTION B6

CENTRAL REFRIGERATION MACHINE, DIRECT EXPANSION EVAPORATORS


AND HEAT REJECTION PLANT

B6.1 GENERAL

In this section, refrigeration machine may refer to chiller or heat pump.

Refrigerants are classified in three flammability safety classification according


to ANSI/ASHRAE Standard 34-2013: Designation and Safety Classification of
Refrigerants. For refrigeration and air-conditioning system in government
building projects, only non-flammable Class 1 refrigerants such as R-134a, R-
407C and R-410A, etc. should be adopted.

Use of highly flammable hydrocarbon refrigerants under Class 3 should be


prohibited and under no circumstances should they be adopted in government
building projects.

Use of refrigerants under Class 2 (such as ammonia (R-717)) should only be


considered under special consideration on individual project basis and subject to
the conditions that such application fully complies with relevant safety
procedures and standards such as ANSI/ASHRAE 15-2013 (Packaged with
ANSI/ASHRAE 34-2013): Safety Standard for Refrigeration Systems,
Designation and Safety Classification of Refrigerants and the statutory
requirements from local authorities.

All necessary refrigerant and lubricating oil shall be supplied by the A/C
Contractor during testing and commissioning and plant operation stages until the
plant is accepted at the expiry of the Maintenance Period.

Each unit shall have an electronic/microcomputer control panel factory installed


and tested. Full automatic control function shall be provided as detailed in
Sections B4, B5, C4 and C5.

Eye wash, shower facilities and drain shall be provided by the Building
Contractor and located at the exit(s) of the A/C plant room where the central
refrigeration plant is installed.

Refrigerant leakage warning alarm in accordance with ANSI/ASHRAE


Standard 15-2013(Packaged with ANSI/ASHRAE Standard 34-2013) or BS EN
378-3:2008+A1:2012 shall be installed if the refrigeration plant is installed in
indoor environment.

The plant shall be so selected and installed with sufficient space allowed for
effective heat dissipation to surrounding air, and for easy maintenance and
servicing.

Appropriate corrosion resistant materials and assembly methods shall be used


including isolation of dissimilar metals against galvanic interaction, etc.

Section B6 AC_GS
Page 1 of 14 2017 Edition
Mounting and fixing details including details and dimensions of equipment
bases, fixing bolts, supporting steelwork, flexible connections, vibration
isolators and any special builders work requirements, etc. shall be provided by
the A/C Contractor in good time to meet the building programme.

Any damage to finishes of the equipment which may have occurred during
transit, storage, installation or other causes shall be made good in the manner
recommended by the manufacturer and to the satisfaction of the Supervising
Officer. Same type of paint shall be used for making good the damages.

Apart from the fixed maintenance platform provided by the Building Contractor
as indicated on the Drawings, removable rigid working and service platform
shall be equipped for the easy inspection and maintenance of the refrigeration
plant and associated equipment. The platform shall be assembled from
galvanised steel structure or fibreglass reinforced polyester with stainless steel
fixing bolts, nuts and washers, and accessories approved by the Supervising
Officer.

All mounting and fixing supports shall be of galvanised steel and exposed metal
surface after cutting shall be treated against corrosion and painted in accordance
with Part G.

B6.2 LAYOUT AND ISOLATION OF PLANT COMPONENTS

The plant layout shall be so arranged with physical division and valves such that
any plant component may be isolated for servicing without completely draining
the refrigerant or water circuits of the whole plant and shall follow the
ANSI/ASHRAE Standard 15-2013(Packaged with ANSI/ASHRAE Standard
34-2013) or BS EN 378-2:2008+A2:2012 to BS EN 378-3:2008+A1:2012. All
equipment shall be located within safety marking perimeter. Clear floor safety
marking in durable brilliant colour approved by the Supervising Officer shall be
provided.

Motor control centre and central monitoring and supervisory console shall be
installed inside a control room which is free from water pipes with double
glazing window for plant viewing provided by the Building Contractor.

B6.3 DELIVERY OF EQUIPMENT

All equipment delivered to Site shall be properly protected as detailed in Section


A3.

The A/C Contractor shall take into account the site constraints when planning the
delivery route of the equipment. The delivery route together with information on
the imposed loading of the equipment and/or any temporary structural openings
required shall be submitted to the Supervising Officer for agreement prior to the
transportation of the equipment to Site. Any temporary hoisting or handling
facilities and installations to facilitate the delivery of the equipment shall be
provided and removed after use by the A/C Contractor.

Section B6 AC_GS
Page 2 of 14 2017 Edition
B6.4 REFRIGERATION PIPEWORK AND FITTINGS

Joints in copper pipe shall be flanged, flared (up to 20 mm OD only), or brazed


with or without capillary fittings. Brazing shall be carried out to the
requirements of the B&ES Code of Practice - Brazing and Bronze Welding of
Copper Pipe and Sheet.

Joints in steel pipe shall be flanged or welded. Mitre or segmented bends will
not be accepted.

Screwed joints will not be accepted in refrigerant pipes except on the equipment
accessories. In such cases, the thread shall either be of taper form and used in
conjunction with PTFE tape or an anaerobic sealant, or of parallel form
associated with machined joint faces and a suitable joint.

Plastic pipe with compression fittings will be accepted for feed piping to control
cabinet door mounted pressure gauges and similar fittings. The grades of pipe
used shall withstand the test pressure applied and the effects of refrigerant and
oil. Plastic pipe will not be accepted for any other refrigerant pipework.

Compression fittings will not be accepted on refrigerant pipework.

Refrigerant pipework shall not be arranged for running compressors in parallel


(i.e. with common suction and/or discharge pipes). The use of multi-
compressors each having an independent refrigerant circuit in a common
evaporator will be permitted provided pressure tests between adjacent
refrigerant circuits in the evaporator are carried out during manufacturing.

The pipework shall be so designed that oil in the refrigerant leaving the
compressor (and passing any oil separator fitted) shall be carried through the
system and back to the compressor at the lowest stage of capacity unloading.

Pipework shall be firmly supported and secured to minimise vibration.


Vibration eliminators shall be fitted to the compressor suction and discharge
pipes to minimise transmission of vibration or noise. Where indicated, a gas
pulsation damper shall be fitted at the refrigerant discharge pipe, in the plant
room, as close as possible to the refrigeration compressor.

After completion, the refrigerant pipe work shall be pressure tested as detailed in
T&C Procedure No.1 clause 4.1.3.

All parts and components containing refrigerant shall be clean and dry before
they are connected to the system. No mill scale shall be permitted in pipes and
all pipes shall be capped on Site until welded in. Prior to charging refrigerant to
the refrigeration system, field pressure tests shall be carried out in accordance
with Part H. Any leak found shall be repaired before the system can be
considered tight.

Hangers, clips and other hanging or clamping studs shall be galvanised and they
shall not be welded to tubes and pressure vessels containing refrigerant.
Pipework and other parts shall be erected and clamped so that vibration and
noise are kept to minimum.

Section B6 AC_GS
Page 3 of 14 2017 Edition
Both insulated and uninsulated components, pipes and vessels shall be cleaned
and painted with anti-corrosion primer. Finished coatings shall be applied to
uninsulated metals. Insulated vessels shall be supported on high density
insulation material at the support cradles.

The air-conditioning installation works in connection with the handling


(including installing, commissioning and testing) of hydrofluorocarbon (HFC)
and blend type refrigerants shall be undertaken by a minimum percentage of
workers who shall have a valid certificate of completing satisfactorily the
relevant refrigerant handling training courses organised by the recognised
association as specified in the contract. Upon request, details and particulars of
these workers shall be submitted to the Supervising Officer for approval.

All installed pipework for blended refrigerant shall not be pressurised with
refrigerant and air. Blowing of the refrigerant pipework shall not be done by
means of the blended refrigerant mixed with air. The A/C Contractor shall pay
particular attention and precaution when handling the blended refrigerant
pipework installation. For charging of refrigerant to the system, the
recommendations from the supplier and the procedures stipulated in the Testing
and Commissioning Procedure for Air-conditioning, Refrigeration, Ventilation
and Central Monitoring & Control Systems Installation in Government
Buildings Hong Kong shall be followed. The work shall also be carried out by
trained and qualified persons approved by the Supervising Officer.

B6.5 AIR-COOLED PACKAGED REFRIGERATION MACHINE

B6.5.1 Installation Requirements

(a) When lifting the unit to position, clevis connectors shall be


installed through the lifting plates provided on the unit.
Required lifting beam dimensions shall comply with the
manufacturers recommendations. To prevent unit damage,
the lifting beam shall be positioned so that cables will not be in
contact with the unit or otherwise appropriate protection shall
be applied on the unit casing.

(b) If the unit is installed on spring isolators, it shall be located on


the isolators and the isolators shall be securely fixed to the
roof curb structure. The A/C Contractor shall, according to the
manufacturers advice, advise the requirements on strength of
the roof curb structure. Selection of the spring isolators shall
be submitted to the Supervising Officer for approval prior to
execution of work.

(c) The unit shall be installed so that air can circulate through the
condenser coils without any hindrance, and the air discharged
from the condenser fans is not recycled. If the unit has to be
placed near a wall or an obstacle that may prevent satisfactory
air circulation, sufficient distance as recommended by the
manufacturer shall be maintained between the unit and the
obstacle. The location to install the unit shall be submitted to

Section B6 AC_GS
Page 4 of 14 2017 Edition
the Supervising Officer for approval prior to execution of
work.

(d) Adequate clearance opposite to the evaporator connections as


recommended by the manufacturer shall be allowed so that
cleaning of the tubes and maintenance of the evaporator can be
carried out. Sufficient space shall be allowed at each end of
the unit for opening the fan access panel and the starter door.

(e) All components such as control panels, indicating lights and


gauges shall be housed in a weatherproof, watertight, and anti-
corrosion metal cabinet with lockable door. The components
shall be neatly and tidily arranged within the cabinet with
proper labelling in both English and Chinese. A clear and
precise circuit diagram, service and safety instructions for the
refrigeration machine separately enclosed in waterproof
enclosures shall be provided in a conspicuous position within
the cabinet.

(f) The A/C Contractor shall provide a rigid sun/rain shelter in


front of the control panel, starter and equipment cabinet of
each refrigeration machine unit. The shelter shall be
constructed of minimum 2 mm thick galvanised sheet steel and
reinforcement framework or FRP materials. Rim inclining
downward along the edges of the shelter or similar provision
shall be provided to prevent water from flowing to the
underside of the shelter and dripping onto the control panels or
equipment cabinets. All metal work shall be treated with
suitable anti-corrosion paintings. The shelter shall be made of
adequate sizes to cover the above-mentioned panels and
cabinets and extend at least 1 m in depth from the refrigeration
machine to provide a protective cover for the panels and
cabinets, and for the servicing personnel, to the satisfaction of
the Supervising Officer.

B6.5.2 Water Piping Connection

(a) All water piping to the unit shall be thoroughly flushed before
making the final piping connections to the unit.

(b) To avoid possible equipment damage, untreated or improperly


treated system water shall not be used.

(c) Sufficient vents shall be provided at high points in the piping


to bleed air from all water circuits. Necessary pressure gauges
shall be installed to monitor the entering and leaving water
pressures. Shutoff valves shall be provided between the
pressure tapping point and the pressure gauge to enable the
gauge to be replaced and the zero point to be checked while
the plant is running.

Section B6 AC_GS
Page 5 of 14 2017 Edition
(d) Thermometers shall be installed in the water circuits to
monitor entering and leaving water temperatures. A balancing
valve shall be installed in the leaving water line for water flow
balancing.

(e) Shutoff valves shall be installed in both the entering and


leaving water lines to the evaporator so that the evaporator can
be isolated for maintenance when required.

(f) A pipe strainer shall be installed in the entering water line to


prevent water-born debris from entering the system.

(g) Vibration eliminator shall be installed in the entering and


leaving water lines to the unit.

(h) A shutoff valve shall be installed in the drain line of the


evaporator.

(i) A water pressure relief valve shall be installed in the


evaporator water system.

B6.5.3 Installation and Connection of Temperature Sensors

(a) To enable the sensor to read a well mixed water temperature,


the sensor finger shall be positioned at a substantial distance
from the evaporator and avoid placement near elbows.

(b) Thermo-contact paste shall be put on each sensor finger before


inserting the sensor to ensure better thermal conductivity. The
bottom of the sensor shall be in touch with the sensor finger.

(c) The electrical cables connecting the temperature sensors shall


be installed in G.I. conduit.

B6.5.4 Installation of Flow Sensing Devices

(a) Flow switch or differential pressure switch with pump


interlocks shall be installed to sense system water flow. The
flow switch shall be installed in series with the pump
interlocks to protect the refrigeration machine.

(b) The flow switch shall be mounted upright, with a minimum of


5 pipe diameters straight, horizontal run on the water circuit.
The flow switch shall not be installed close to elbows, orifices
or valves.

B6.5.5 Installation of Energy Metering Devices

(a) Electricity meters and thermal energy meters shall be installed


to continuous measure, record and monitor the electricity
consumption, energy input and output, cooling/heating power,
coefficient of performance, and energy performance for each

Section B6 AC_GS
Page 6 of 14 2017 Edition
refrigeration machine. Independent electricity meters and
thermal energy meters in accordance with ASHRAE Guideline
14 and ASHRAE Guideline 22 shall be provided by the A/C
Contractor to measure the energy performance of the whole
refrigeration system.

(b) Ambient temperature sensors shall be installed to continuous


measure, record and monitor the outside air temperature,
outside air dry-bulb, and relative humidity for the whole
refrigeration system.

(c) The electricity meters in accordance with ANSI C12.1-2008,


and ANSI C12.20-2010 or IEC 62053-22:2003 IEC62058-
11:2008, IEC62058-21:2008 and IEC 62058-31:2008 shall be
installed with 10 years certified life.

(d) Thermal energy meters in accordance with ANSI C12.20-2010


and IEC 62053-21:2003, IEC62058-11:2008, and IEC62058-
21:2008 shall be installed with 10 years certified life.

(e) Type test report of the electricity meters and thermal energy
meters shall be submitted to the Supervising Officer for
approval prior to execution of work.

(f) The electricity meters and thermal energy meters shall be


connected to Central Control Monitoring System, if such system
is provided, to optimise the operation of the refrigeration system.

B6.6 WATER-COOLED PACKAGED REFRIGERATION MACHINE

B6.6.1 Installation Requirements

(a) Same as Clause B6.5.1 (a).

(b) Elastomeric isolation pads shall be installed on the foundation


for the unit to isolate the vibration of the unit. The A/C
Contractor shall advise the Supervising Officer the strength
and mass of the foundation to support the unit operating
weight.

(c) Sufficient space shall be allowed around the unit for


unrestricted free access of the Installations and maintenance
personnel to all service points. Adequate clearance as
recommended by the manufacturer shall be allowed so that
cleaning of the tubes of the evaporator and condenser and
maintenance of the various components can be carried out
effectively. Sufficient vertical clearance above the unit shall
also be allowed. No services such as ductworks and water
pipes shall be located over the compressor motor.

Section B6 AC_GS
Page 7 of 14 2017 Edition
B6.6.2 Water Piping Connection

(a) Same as Clause B6.5.2 (a).

(b) Same as Clause B6.5.2 (b).

(c) Sufficient vents shall be provided at high points in the piping


to bleed air from the water circuits. Necessary pressure
gauges shall be installed to monitor the entering and leaving
chilled or hot/condensing water pressures. Shutoff valves
shall be provided to the gauges to isolate them from the system
when required.

(d) Thermometers shall be installed in the lines to monitor


entering and leaving chilled and condensing water
temperatures. A water balancing valve shall be installed in the
leaving chilled or hot/condensing water lines for water flow
balancing.

(e) Shutoff valves shall be installed in both the entering and


leaving chilled or hot/condensing water lines so that the
evaporator and condenser can be isolated for maintenance and
servicing when required.

(f) A pipe strainer shall be installed in the entering chilled or


hot/condensing water lines to prevent water-born debris from
entering the system.

(g) Vibration eliminator shall be installed in the entering and


leaving chilled or hot/condensing water lines to the unit.

(h) A shutoff valve shall be installed in the drain line of the


evaporator and condenser.

(i) A water pressure relief valve shall be installed in the


evaporator and condenser water system.

B6.6.3 Installation and Connection of Temperature Sensors

(a) Same as Clause B6.5.3 (a).

(b) Same as Clause B6.5.3 (b).

(c) Same as Clause B6.5.3 (c).

B6.6.4 Installation of Flow Sensing Devices

(a) Flow switches or differential pressure switches with pump


interlocks shall be installed to sense system water flow. The
flow switches shall be installed in series with the pump
interlocks for either chilled or hot/condensing water circuits to
protect the machine.

Section B6 AC_GS
Page 8 of 14 2017 Edition
(b) Same as Clause B6.5.4 (b).

B6.6.5 Installation of Energy Metering Devices

Same as Clause B6.5.5

B6.7 AIR-COOLED CONDENSER

Air cooled condensers mounted outside buildings shall have weatherproof fan
motors. The units shall discharge air vertically upwards. If specified to
discharge horizontally, they shall be protected by an integral wind deflector or
purpose-made baffle. The structure and casing of units shall be constructed of
material which is either corrosion resistant or treated against corrosion after
manufacture in the factory.

The unit shall be installed on vibration isolation devices as specified in Sections


B8 and C8. The A/C Contractor shall, according to the manufacturers
recommendation, advise the requirements on strength of the roof curb structure
for supporting the unit. Selection of the vibration isolators shall be submitted to
the Supervising Officer for approval prior to execution of work.

The unit shall be installed so that air can circulate through the condenser coils
without any hindrance, and the air discharged from the condenser fans is not
recycled. If the unit has to be placed near a wall or an obstacle that may prevent
satisfying air circulation, sufficient distance as recommended by the
manufacturer shall be maintained between the unit and the obstacle.

B6.8 AIR-COOLED EVAPORATOR

The cooling unit shall be dehydrated, charged with an inert gas, pressure tested
and sealed after manufacture.

B6.9 COOLING TOWER

The fiber-reinforced plastic (FRP) warm water distribution or hot water basin
shall be covered by removable FRP covers that keep out sunlight and give a
finished appearance to the tower. The cold water basin shall be supported by a
structural beam assembly provided by the cooling tower manufacturer.
Builders work supports by the Building Contractor, exact tower orientation and
architectural aesthetic consideration shall be submitted in sufficient time
according to the building programme to the Supervising Officer for approval.
The make-up water pipe inlet shall be fitted with a strainer and flow meters
capable of being used to record the maximum rate of make-up water in m3/hr,
and the make-up water consumption in m3. Isolation valves, unions, and by-
pass valve shall be provided to facilitate meter removal for maintenance and
servicing.

Section B6 AC_GS
Page 9 of 14 2017 Edition
A bleed pipe with stop valve and flow regulating device shall be provided on
each cooling tower to the nearest builders drain.

Control and chemical or ozone treatment plants shall be located near to the
cooling towers and they shall be installed inside a covered plant room/space
with proper ventilation.

B6.10 HEAT RECOVERY CHILLER

Refer to Clause C6.23.

B6.11 TOTAL ENERGY HEAT PUMP

Refer to Clause C6.26.

B6.12 VIBRATION ISOLATION

All plants offered shall have minimum vibration and noise levels during
operation, with particular attention to the sound pressure level requirements
from different sources while all plants operating in full capacity shall comply
with the requirements of the Environmental Protection Department or other
statutory noise control requirements issued prior to tendering, whichever is more
stringent. The A/C Contractor shall be responsible for provision of adequate
vibration isolation and/or sound attenuation measures for the refrigeration plant
to meet the requirements as detailed in Sections B8 and C8 and to the
satisfaction and acceptance of the Supervising Officer.

B6.13 ELECTRICAL WORK

The A/C Contractor shall supply and install suitable power cables, cable trays,
G.I. supports, starters/motor drives, isolators, control, safety earth bonding and
all necessary accessories to connect power from the isolator to each electricity-
driven equipment. The A/C Contractor shall allow for adequate cable size for
power/control/earthing systems and protection devices to meet the current
demand, voltage drop and fault tripping requirements of the equipment offered.

B6.14 SAFETY ANCILLARIES FOR AMMONIA REFRIGERATION


MACHINE

B6.14.1 Pressure Relief Device

A pressure-relief valve connected via discharge pipe in accordance


with relevant Sections of ANSI/ASHRAE15-2013(Packaged with
ANSHI/ASHRAE 34-2013) or ANSI/IIAR Standard 2-2014 shall be
provided at both high side and low side pressure vessels of the
ammonia refrigerating system which automatically relieves pressure
of pre-determined excessive pressure due to emergency conditions. A

Section B6 AC_GS
Page 10 of 14 2017 Edition
solenoid valve shall be provided in addition to the pressure-relief
valve which is opened by means of a manual emergency switch. The
solenoid valve shall be installed in a parallel by-pass circuit of the
pressure relief valve on the pressure vessels. The required capacity of
the pressure relief valves shall be determined in accordance with
ASME Boiler and Pressure Vessel Code, 2015and the maximum
length and size of the discharge pipe shall be determined in
accordance with relevant sections as stipulated in ANSI/ASHRAE
15-2013.

An emergency discharge system including discharge pipeline size,


length, pipe route and material, valve size, common header, pipe
support, control valve box and termination diffuser, etc. shall be
designed and constructed by the A/C Contractor according to
ANSI/ASHRAE 15-2013 (Packaged with ANSI/ASHRAE 34-2013)
or ANSI/IIAR 2-2014- relevant sections. All emergency discharge
pipelines shall be connected above the liquid refrigerant level on the
high pressure side and the low pressure side of the system. The lines
shall be pitched so as to drain the system. These lines shall extend
into an emergency refrigerant control box readily accessible outside
the ammonia refrigeration machine plant room. The box shall be
locked and labelled with "Emergency Refrigerant Control Box -
Ammonia R-717". A readily accessible stop valve labelled with
"High Pressure Refrigerant Discharge Valve" and a suitable pressure
gauge shall be installed on the discharge pipes within the emergency
refrigerant control box. The emergency discharge lines shall be
connected to a common riser for discharge to the atmosphere. At the
upper extremity of the common riser, it shall be fitted with a diffuser
for mixing the refrigerant with air. The discharge termination shall be
within 600mm of one side of the discharge outlet of the emergency
ventilation fan at roof level to ensure good mixing of ammonia/air by
forced ventilation. The emergency ventilation system shall in this
case operate within 1 second after the actuation of any one of the
pressure relief devices or the manual discharge system.

The safety refrigerant relief discharge point shall be sited at a location


away from any pedestrian access as approved by the Supervising
Officer. A clear warning label shall be displayed next to the
discharge point.

B6.14.2 Emergency Apparatus

The A/C Contractor shall provide two sets of the FSD approved type
respirators and protective clothing and one First Aid Kit and one
portable ammonia detector ranged 10-1500 ppm inside a waterproof
stainless steel cabinet for use in emergency service. The equipment
shall be stored near to the entrance of the ammonia refrigeration
machine plant room or as indicated on the Drawings. The respirator
shall be full face gas mask, front head sparing or back mounted type,
with industrial size ammonia canister. The protective clothing shall
include gloves, shoe covers, and aprons impervious to ammonia. The
First Aid Kit shall contain the Saturated Solution of Sodium

Section B6 AC_GS
Page 11 of 14 2017 Edition
Thiosulsulfate, or Sterilised Water, Sterile Compresses or Dressings,
0.5% Ponto Caine Solution (with eye dropper), and Rubber Bulb
Syringe.

B6.14.3 Warning Plate

The A/C Contractor shall also provide the FSD approved type
warning plates with the words "DANGER-AMMONIA
ASPHYXIATING GAS" to be prominently displayed on each exit
doors and gas pressure relief/discharge point of the ammonia
refrigeration machine plant room in 120 mm high in both English and
Chinese characters.

B6.14.4 Ventilation

The emergency, independent mechanical ventilation of the ammonia


refrigeration machine plant room is provided by means of exhaust
ductwork constructed of stainless steel AISI 316, extraction fans and
its associated cables as shown on the Drawings. The capacity of the
extractors for emergency ventilation shall comply with the ventilation
requirement stipulated in relevant sections of ANSI/IIAR 2-2014
and/or as shown on the Drawings, whichever is greater. The
emergency ventilation system shall be actuated automatically by an
ammonia vapour detector when the concentration of ammonia
exceeds 0.03% (300 ppm) when leakage occurred or when the
pressure relieve valves are actuated or when the manual discharge
system is actuated. Manual means for actuating the emergency
ventilation system by means of emergency control switch shall be
provided and located as shown on the Drawings.

B6.14.5 Ammonia Vapour Leakage Detection System

A/C plant room where ammonia refrigeration machine is installed


shall be provided with an ammonia vapour leakage detection system
to monitor and indicate at least two concentration levels to warn the
people in the surrounding and automatically actuates the emergency
measures. The ammonia leakage detectors shall be based on
semiconductor techniques and has a stable zero point, long life time
up to 8 years and good resistance to fouling by gases containing high
concentration of ammonia. The detectors shall have an adjustable
relay output of 4-20 mA analogue signal with a range of 0-1500 ppm
for remote logic processing in the digital controllers. Fixed ammonia
leakage detectors shall be installed. The low level alarm at 0.03%
(300 ppm) by volume shall be actuated to warn the responsible
personnel in the refrigeration machine plant room and start the
emergency ventilation system automatically. The high level alarm at
0.1% (1000 ppm) by volume shall be actuated to shut down
automatically the refrigeration system. Manual emergency switches
shall also be provided immediately outside the A/C plant room. The
ammonia vapour leakage detection system shall be powered by
battery supply system with battery charger. The power supply for all
electrical consuming equipment shall be maintained for at least

Section B6 AC_GS
Page 12 of 14 2017 Edition
6 hours for pre-alarm condition and 2 hours for full alarm condition.
The ammonia detection panel shall be made of 1.2 mm thick stainless
steel sheet and located as shown on the Drawings. The indication
lamps and manual emergency buttons of the ammonia detection panel
shall also be repeated in the Main Fire Alarm Annunciation Panel
inside the Fire Services Control Centre by means of dry contacts and
relays. In addition, means shall be provided by the A/C Contractor to
interface the ammonia detection panel with the CCMS if such system
is provided.

B6.14.6 Operation of Condenser Fans and Associated Safety Protection

For air-cooled ammonia refrigeration machines, the condenser fans


shall have two operation modes. During normal application, the fans
shall run at low speed to achieve low noise level adequate for the
ventilation requirement. On detection of ammonia leakage, the fans
shall be speeded up to provide larger ventilation rate to dilute and
blow away the ammonia to the atmosphere. Water sprinkler installed
in the machine refrigerant compartment shall also be activated to
dilute and drain away the ammonia safely.

B6.15 SOLAR HEATING SYSTEM

B6.15.1 General

The installation details should be in accordance with the instruction


prepared by the manufacturer.

The plant shall be so selected and installed with sufficient space


allowed for maintenance and servicing. All mountings and fixing
supports shall be hot dip galvanised steel. Exposed metals shall be
treated to prevent corrosion and painted in accordance with Part G
(Painting, Finishing and Protective Treatment).

B6.15.2 The solar collectors shall be mounted at a tilt angle to the horizontal
and faced south to achieve maximum solar gain for the application.

B6.15.3 The A/C Contractor shall design, supply and install hot dip
galvanised steel maintenance platform, catwalk and cat ladder for
future maintenance access of the solar collector system. The A/C
Contractor shall design the fixing method and provide calculation for
the solar collector system for approval by the Supervising Officer.
The mounting brackets and supports for the solar collector system
shall be designed by a registered structural engineer to withstand the
most severe wind load conditions in Hong Kong.

B6.15.4 The Feed and Expansion tank shall be mounted at the highest point of
the solar heating system. All water pipework shall be completed with
flexible closed cell elastomeric insulation of sufficient thickness and
with coating for UV protection.

Section B6 AC_GS
Page 13 of 14 2017 Edition
B6.15.5 Operation and Maintenance

6.15.5.1 General

The operation and maintenance details should be in


accordance with the instruction recommended by the
manufacturer.

Fixed maintenance platform, including working and


access service platform, shall be made of hot dip
galvanised steel, and shall be designed and equipped for
easy inspection and maintenance of the solar heating
system and associated equipment as recommended by the
solar collector manufacturer.

6.15.5.2 Sufficient maintenance space shall be allowed for access,


servicing, and cleaning of the solar collector panels.

Section B6 AC_GS
Page 14 of 14 2017 Edition
SECTION B7

ELECTRIC MOTORS AND ELECTRICAL EQUIPMENT

B7.1 LOW VOLTAGE-GENERAL

Unless otherwise specified, the A/C Contractor shall provide and install all low
voltage electrical equipment necessary for the complete Installations under the
Contract and shall carry out all necessary wiring from the points of power
supply provided by others as indicated on the Drawings.

The A/C Contractor shall be responsible for the accuracy of all installation and
shop drawings and wiring diagram and for the correct internal wiring of all pre-
wired equipment supplied under the Contract.

All electrical equipment, wiring and installation work, and materials shall
comply with the provisions of the relevant parts of the Electrical General
Specification.

Motor arranged for automatic restart shall have a label of durable material
permanently fixed to it and in a prominent position clearly inscribed as per the
Electrical General Specification Clause B9.1.6.

B7.2 LOW VOLTAGE-ELECTRIC MOTORS

The low voltage electric motors shall comply with Clause B9.1 of the Electrical
General Specification.

B7.3 LOW VOLTAGE-VARIABLE SPEED DRIVES

The drives shall be either wall mounted or floor mounted in a well ventilated
location and in accordance with the manufacturers standard installation
recommendations.

The drives shall be located away from any nearby water pipework to avoid
possible damage by water leaking or water pipe bursting. In case that such
location could not be identified, the A/C Contractor shall provide all necessary
protective means to avoid the damage.

The distance between the drives and the controlled motors shall be within the
range as recommended by the manufacturer. The A/C Contractor shall submit
calculations including his selected interconnecting cable sizes to the Supervising
Officer to substantiate that the overall performance shall meet the design
requirements.

For essential air conditioning services subject to the approval of the Supervising
Officer and requiring to meet special building functions and clients operational
requirements, all major and essential electric motor drives in the air conditioning
systems shall be configured in such a way that there is a minimum chance of

Section B7 AC_GS
Page 1 of 2 2017 Edition
serious interruption and/or breakdown of the entire plant operation due to a
single point of failure for major and essential electric motor drives in the
systems. The A/C Contractor shall provide sufficient redundancy and/or backup
provisions such as installation of alternate motor starters as appropriate
according to the Electrical General Specification Clause C5.26.4 where
necessary for maintenance by-pass of variable speed drives in the motor control
equipment and ancillaries.

B7.4 LOW VOLTAGE-MOTOR SWITCHGEAR, STARTER AND CONTROL


PANELS

The low voltage motor switchgear, starter and control panels shall comply with
Clause B9.2 of the Electrical General Specification.

B7.5 LOW VOLTAGE-AUTOMATIC POWER FACTOR CORRECTION


CAPACITORS

The capacitor bank shall be wall or floor mounting cubicle-type, built up from
static primary capacitor unit. The capacitor bank together with its associated
equipment shall not be installed inside the switchboard, where practicable.
However, if it is not practical due to physical constraint or other justified
reasons, the equipment shall be installed in a separate compartment segregated
from the rest of the switchboard.

B7.6 HIGH VOLTAGE ELECTRIC EQUIPMENT

The high voltage electric equipment shall comply with the relevant sections of
the Electrical General Specification.

Equipment Electrical General Specification


High Voltage - General Clause B9.3
High Voltage - Electric motors Clause B9.4
High Voltage - Motor control Clause B9.5
switchboards
High Voltage - Auto-transformers Clause B9.6
High Voltage - Power factor Clause B9.7
correction capacitors
High Voltage - Power cables Clause B9.8

Section B7 AC_GS
Page 2 of 2 2017 Edition
SECTION B8

NOISE AND VIBRATION CONTROL

B8.1 GENERAL

The A/C Contractor shall install sufficient noise and vibration control measures
on the plant/equipment, the interconnected piping, ductwork and conduit so that
when the installed plant/equipment are put into operation, the resulting noise
and vibration levels at locations within the building and at adjacent or nearby
buildings shall not exceed the acceptable limits.

Unless otherwise specified in the Particular Specification, the total noise level in
occupied areas within the building, whether it be airborne, structure-borne or
ductwork-borne, shall not exceed the following limits when all the
plant/equipment installed by the A/C Contractor are put into operation: -

Table B8.1 Noise Control Criteria

Broadcasting and recording studios NC 25


Concert and opera halls NC 25
Theatres, assembly halls and churches NC 30
Cinemas NC 35
Hospital wards and operating theatres NC 35
Homes, bedrooms NC 35
Private offices, libraries, courtrooms and schoolrooms NC 35
General offices NC 40
Mechanised offices NC 45
Restaurants, bars, cafeterias and canteens NC 45
Department stores and shops NC 45
Swimming baths and sports arenas NC 50
Kitchens NC 50
Factories (light engineering) NC 65
Factories (heavy engineering) NC 75

The specified noise criteria shall apply based on fundamental principles, such as
those in ASHRAE Fundamentals SI Handbook 2013 to all areas as measured at
a level of 1.5 m above the floor and the measuring points shall be 1.5 m away
from the walls or doors of the rooms.

The Corrected Noise Level at potential Noise Sensitive Receiver in the adjacent
or nearby building, if so identified in the Contract, shall not exceed the
Section B8 AC_GS
Page 1 of 11 2017 Edition
Acceptable Noise Level stipulated in the Technical Memorandum for the
Assessment of Noise from Places other than Domestic Premises, Public Places
or Construction Sites issued by the Environmental Protection Department when
the plant/equipment installed by the A/C Contractor are put into operation.

B8.2 EQUIPMENT BASES

B8.2.1 General

Floor mounted equipment shall be installed on 100 mm high concrete


housekeeping pads provided by the Building Contractor covering the
whole floor area requirements of the equipment bases plus a
minimum of 150 mm further on each side or on inverted beams at
roof. Vibration isolators are then mounted on this concrete pad or
inverted beams.

Unless otherwise specified in the Particular Specification,


plant/equipment to be isolated shall either be supported by structural
steel bases or concrete inertia bases.

B8.2.2 Welded Structural Steel Bases

Detailed design calculation of the base and its anti-vibration isolator


arrangements plus shop drawings for each base shall be provided for
approval by the Supervising Officer before manufacture.

B8.2.3 Concrete Inertia Bases

Detailed design calculation of the base and its anti-vibration


arrangements plus shop drawings for each base shall be provided for
approval of the Supervising Officer before manufacture.

B8.3 VIBRATION ISOLATORS

The following types of vibration isolation mountings or suspensions are not


exhaustive but serve to cover the main types that shall be applied as appropriate
unless otherwise stated in the Particular Specification.

B8.3.1 Type 'A' - Free Standing Spring Mounts

Springs shall be designed and installed so that the ends of the springs
remain parallel. They shall be corrosion-protected.

Submittals for approval shall include spring diameters, "compressed"


spring height, "solid" spring height, rated capacities and rated
deflections.

B8.3.2 Type 'B' - Restrained Spring Mounts

A minimum of 10 mm clearance shall be maintained around


restraining bolts and between the housing and the spring so as not to
Section B8 AC_GS
Page 2 of 11 2017 Edition
interfere with the spring action. Limit stops shall be out of contact
during normal operations.

B8.3.3 Type 'C' - Double Deflection Neoprene Mounts

These mountings shall have a minimum static deflection of 8.5 mm.


Bolt holes shall be provided for applications where bolting down is
required. They shall be carefully positioned such that all supporting
mounts would be properly loaded and the weight load on each mount
would be evenly distributed over the entire surface.

B8.3.4 Type 'D' - Neoprene Pads

Where necessary, pads may be bolted through with bolts isolated


from the machine by neoprene grommets. Alternatively, "waffled"
neoprene pads can be used without holding down bolts where the
vibration is minimal and the weight of machine is such that the
resultant friction is adequate and the machine is unlikely ever to move.
They shall be carefully positioned such that all supporting pads will
be properly loaded and the weight load on each pad will be evenly
distributed over the entire surface.

B8.3.5 Type 'E' - Spring Hangers

Springs shall have a minimum additional travel to solid equal to 50%


of the rated deflection.

Submittals for approval shall include scale drawing of the hanger


showing its 30o to 35o swing capability.

Application - See Clause B8.5.2 for pipework vibration isolation and


Clause B8.6 for ductwork vibration isolation.

B8.3.6 Type 'F' - Spring and Double Deflection Neoprene Hangers

Submittals for approval shall include scale drawing of the hanger


showing its 30o to 35o swing capability.

Application - See Clause B8.5.2 for pipework vibration isolation and


Clause B8.6 for ductwork vibration isolation.

B8.3.7 Type 'G' - Pre-Compressed Spring Hangers

Submittals for approval shall include scale drawing of the hanger


showing its 30o to 35o swing capability.

Application - See Clause B8.5.2 for pipework vibration isolation and


Clause B8.6 for ductwork vibration isolation.

B8.3.8 Type 'H' - All Directional Anchor Units

Submittals for approval shall include rated capacities and rated


deflections.
Section B8 AC_GS
Page 3 of 11 2017 Edition
Application The units may use to provide high frequency noise and
vibration isolation for those locations where movement must be
controlled.

B8.3.9 Type 'I' - Pipe Anchors and Guides

Submittals for approval shall include rated capacities and rated


deflections.

B8.3.10 Type 'J' - Split Wall/Floor Seals

The seals shall be tightened around the pipes to eliminate clearance


between the inner sponge faces and the piping.

Concrete may be packed around the seals to make it integral with the
floors, walls or ceilings if the seals are not already in place around the
pipes prior to the construction of the building members.

Seals shall project a minimum of 25 mm past either face of the walls.

Application The seals may be used to prevent noises generated


within equipment rooms or plant rooms from leaking through the
spaces around piping which pass through walls, ceilings or floors of
these rooms.

B8.3.11 Type 'K' - Horizontal Thrust Restrains

The assembly shall be furnished with one threaded rod and two angle
brackets for attachment to both the equipment and ductwork or the
equipment and the structure. Horizontal restraints shall be attached at
the centre line of thrust and symmetrically on either side of the unit.

B8.3.12 Type 'L' - Built in Inertia Block Plant Support

Where specified, the A/C Contractor as the case may be, shall provide
plant foundations and housekeeping pads in form of large concrete
blocks recessed into the main floor slab.

B8.4 PLANT/EQUIPMENT VIBRATION ISOLATION

B8.4.1 General

All rotating or reciprocating equipment shall be mounted on vibration


isolation mountings or suspended from vibration isolation hangers.

The A/C Contractor shall ensure that there is no rigid connection in


whatever form between the isolated equipment and the building
structure which will otherwise short-circuit the vibration isolation
system and degrade its performance. This includes the necessary co-
ordination with other trades by the A/C Contractor.

Section B8 AC_GS
Page 4 of 11 2017 Edition
All isolators shall operate in the linear portion of their load versus
deflection curve. The load versus deflection curves shall be furnished
by the manufacturer, and must be linear over a deflection range of not
less than 50% above the design deflection.

All vibration isolators shall have their known undeflected heights or


calibration markings so that, after adjustment when carrying their
loads, the deflection under load can be verified, thus determining that
the load is within the proper range of the device and that correct
degree of vibration isolation is achieved according to the design.

The static deflection of the isolator at each support point shall not
differ from the design objective for the equipment as a whole by more
than 10%.

The ratio of lateral to vertical stiffness for spring shall be neither less
than 0.9 nor greater than 1.5.

The A/C Contractor shall verify that the isolation requirements are
complete, the equipment offered is correct and suitable in meeting the
design requirements on the vibration levels.

The installation of all vibration isolators, hangers and associated


equipment bases shall be carried out strictly in accordance with
Drawings, the approved manufacturers written instructions, and
where indicated under the direct supervision of the manufacturers
representative.

B8.4.2 Method of Installation

The equipment structural steel or concrete inertia base shall be placed


in position and supported temporarily by blocks or shims. The
machinery shall then be installed on the base and when that is
complete, the isolators are to be installed without raising the machine
and frame assembly.

After the entire Installations is complete and under full operational


load, the isolators shall be adjusted such that the load, are transferred
from the blocks to the isolators. When all isolators are properly
adjusted, the blocks or shims will become slightly free and can then
be removed.

The springs of vibration isolators shall in general have a loaded


working height equal to 1.0 to 1.5 times the outside diameter of the
spring and shall be capable of being compressed to approximate 50%
of their unloaded height.

Where any vibration isolation system permits equipment motion in all


directions, provide where necessary additional resilient restraints shall
be provided where necessary to flexibly limit the lateral movement of
the equipment to 6 mm at start and stop.

Section B8 AC_GS
Page 5 of 11 2017 Edition
Prior to start-up, remove all foreign matter underneath the equipment
base and verify that the vibration isolation system is not short-
circuited.

Electrical circuit connections to isolated equipment shall be looped to


allow free motion of isolated equipment.

B8.5 PIPEWORK VIBRATION ISOLATION

B8.5.1 General

Unless otherwise indicated, all piping located in mechanical


equipment room and having connection to vibrating equipment shall
be isolated from the building structure by means of noise and
vibration isolation hangers for a distance of at least 15 m or 100 times
the pipe diameter from the vibrating equipment, whichever is the
greater. At least three of the first hangers from the equipment should
provide the same deflection as the equipment isolators, with a
maximum limitation of 50 mm deflection. The first three hangers
adjacent to the equipment shall also be of "positioning" or "pre-
compressed" type, to prevent load transfer to the equipment flanges
when the piping system is filled. This "floated" pipe run shall include,
where situation permits, bends in two mutually perpendicular
directions in order to give three degrees of freedom of movement,
with approximately equal distance between successive elbows or
bends.

All piping over 50 mm in diameter and for any piping suspended


below or near noise-sensitive areas shall be suspended by vibration
isolated hangers. Hangers adjacent to noise-sensitive areas shall be
Type F.

For floor-supported piping in equipment rooms or adjacent to isolated


equipment, the vibration isolators shall be selected appropriately. The
first two adjacent floor supports shall be Type B, with a blocking
feature that prevents load transfer to equipment flanges as the piping is
filled or drained.

Where specified in the Particular Specification, all horizontal and


vertical pipework throughout the building which has connection to
vibrating equipment shall also be isolated from the building structure
by means of noise and vibration isolation guides and supports.

All piping to be isolated shall freely pass through walls and floors
without rigid connections. Penetration points shall be sleeved or
otherwise formed to allow passage of piping, and a clearance of 10 to
15 mm around the outside of the piping shall be maintained. This
clearance space shall be tightly packed with glass fibre or rock wool
and caulked airtight after installation of piping. Alternatively, factory
fabricated Type 'J' split wall/floor seals may be used.

Section B8 AC_GS
Page 6 of 11 2017 Edition
The inlet and outlet connections of all vibrating equipment shall be
fitted with either flexible connectors or flexible hoses as appropriate.

B8.5.2 Horizontal Pipe Isolation

Where horizontal pipe isolation is required, the first three pipe


hangers in the main line near the mechanical equipment shall be of
Type 'G' and the hangers for the horizontal run in all other locations
shall be of Type 'E' or Type 'F', the latter being used for more
sensitive situations where a higher degree of noise and vibration
attenuation is required.

Type 'G' hangers shall have the same static deflection as that of the
mountings under the connected equipment. Type 'E' and Type 'F'
hangers shall have a minimum deflection of 20 mm.

B8.5.3 Pipe Riser Isolation

Where pipe riser isolation is required, the pipe risers to be isolated


shall be suspended from Type 'G' hangers or supported by Type 'B'
mountings and anchored with Type 'I' pipe anchors or guided by
Type 'I' pipe guides. Steel spring deflection shall be a minimum of
20 mm except in those expansion locations where additional
deflection is required to limit deflection or load changes to within
plus or minus 25% of the initial stress.

B8.5.4 Flexible Connectors

Flexible connectors shall be fitted to the inlet and outlet connections


of all pumps, water chillers, refrigeration machine, water towers and
other centrifugal or reciprocating vibrating equipment.

Flexible connectors shall be full line size of the equipment connection


and fitted as close to the source of vibration as is practicable. Straight
connectors shall, where practicable, be installed in a position that is
parallel to the equipment shaft as equipment vibration tends to be
most severe in a direction radial to the shaft.

All flexible connectors shall be provided with end restraint to


counteract the pressure thrust.

Manufacturers recommendations on restraints, pressure, and


temperature limits shall be strictly followed during the installation.

B8.5.5 Flexible Metallic Hose

For higher operating temperatures and pressures, vibrational


movement generated by pumps, chillers, refrigeration machine, water
towers, air handling units and other centrifugal or reciprocating
vibrating equipment shall be accommodated by braided flexible

Section B8 AC_GS
Page 7 of 11 2017 Edition
metallic hoses. Allowable stress levels shall be within the units as
prescribed in PD 5500:2012 +A3:2014.
The lengths of the flexible metallic hoses shall be in accordance with
manufacturers recommendation.

Since the braid is stretched taut by the pressure in the axial direction,
hoses cannot accept axial motion. Therefore, the hoses shall be
installed on the equipment side of the shut off valves and be installed
parallel to the shaft for best performance so that the vibration
movement is perpendicular to the axis of the hose. A Type 'I' pipe
anchor capable of withstanding the deflection forces generated by the
flexible hose shall be installed immediately after the hose in order to
force the hose to flex transversely, otherwise the hose will serve little
purpose.

Two hoses at right angles to each other shall be provided when major
vibrational motions to be isolated exist in two planes.

B8.6 DUCTWORK VIBRATION ISOLATION

Flexible connections shall be provided between the vibrating equipment and the
ductwork. Thrust restraints shall be used to maintain a slack position of the
flexible ductwork connections.

Unless otherwise specified, all discharge ductwork which runs for a distance of
15m from the connected vibrating equipment with a discharge pressure of 1kPa
or above shall be isolated from the building structure by means of Type 'E'
hangers provided with top and bottom eye bolts for flat iron hanger strap and
ductwork strap respectively. Spring deflections shall be minimum 20 mm.

Except where the ductwork passing through compartment walls requires a fire
damper, all ductwork to be isolated shall freely pass through walls and floors
without rigid connections. Penetration points shall be sleeved or otherwise
formed to allow passage of ductwork, and a clearance of 20 to 32 mm around
the outside surfaces of the ductwork shall be maintained. This clearance space
shall be tightly packed with glass fibre, caulked airtight and sealed with
approval sealant after installation of ductwork.

In case where fire damper is required, ductwork to be isolated shall be fitted


with a flexible joint on the side of the fire damper where the vibration is
originated.

B8.7 DUCTWORK ACOUSTIC INSULATION

Acoustic linings shall not be applied to the interior of the ductwork unless
otherwise specified.

Transverse joints of the ductwork liner board shall be neatly butted and there
shall be no gap in between the board shall be cut to assure tight, overlapped
corner joints. Board shall be adhered to the sheet metal ductwork with 100%

Section B8 AC_GS
Page 8 of 11 2017 Edition
coverage of adhesive conforming to ASTM C916-85(2007), and all exposed
edges and joints shall also be coated with adhesive. Board shall be additionally
secured with mechanical fasteners which shall start with 75 mm of the upstream
transverse edges and 75 mm from the longitudinal joints and be spaced at a
maximum of 150 mm centres around the perimeter of the ductwork and 100 mm
from corner joints. Elsewhere the fasteners shall be spaced at a maximum of
150 mm centres in the direction across width of ductwork and 400 mm centres
in the direction along length of ductwork and not more than 75 mm from
longitudinal joints and 100 mm from corner joints. Entering and leaving edges
of the ductwork liner boards shall be provided with continuous sheet metal edge
protectors.

Ductwork internal linings shall not be installed within 1 m of the fire damper.

Dimensions of lined ductwork are to be clear inside dimensions after lining has
been installed.

B8.8 ACOUSTIC DUCTLAG

Acoustic duct lag shall be applied, only where indicated, to the exterior of the
work to prevent noise break-in or breakout through the duct wall.

The acoustic duct lag shall be installed in such a way that the material is
completely decoupled from the vibrating duct wall. The A/C Contractor shall
submit installation details to the Supervising Officer for approval prior to
installation.

B8.9 DUCTWORK SILENCERS

Ductwork silencers shall be supplied and installed as indicated in the Particular


Specification or Drawings.

Mani folded silencers shall be installed with continuous metallic nosing crimped
in place. Nosing pieces and tails shall be provided as per manufacturers design.

Before ordering ductwork silencers, the A/C Contractor shall submit for the
Supervising Officers approval the proposed manufacturers certified test data
for pressure drop and insertion loss ratings.

The silencers shall be located at least three ductwork equivalent diameters from
fans, coils, elbows, branch take offs, or other ductwork elements.

B8.10 ACOUSTIC DOORS

The A/C Contractor shall supply and install proprietary made acoustic doors to
plant rooms only where specified in the Particular Specification or Drawings.

Section B8 AC_GS
Page 9 of 11 2017 Edition
B8.11 ACOUSTIC LOUVRES

The A/C Contractor shall supply and install acoustic louvres to the external
walls of plant rooms only where specified in the Particular Specification or
Drawings.

B8.12 ACOUSTIC ENCLOSURES

B8.12.1 General

Where specified for in the Particular Specification or Drawings,


double-wall, insulated, and air-pressure-tight acoustic enclosures for
housing noisy plant or machinery shall be provided as specified and
installed in strict accordance with the installation details and
instructions from the specialist manufacturer in order to achieve the
published standards of construction and performance.

B8.12.2 Access Doors and Louvres

When required as shown on the Drawings, access doors and louvres


forming part of the complete acoustic enclosures shall be of acoustic
type and be so fixed and installed without degrading the acoustical
performance.

B8.12.3 Openings and Sealing

All openings with dimensions greater than 150 mm shall be


factory/workshop cut and framed.

The clearance space between the acoustic enclosure and any


ductwork, pipes, or conduits passing through the enclosure shall be
tightly packed with glass fibre or rock wool and sealed with approved
sealant. Both ends of the opening shall then be covered up by 1.2 mm
thick sheet steel and sealed airtight by high pressure ductwork sealer.

B8.13 PLANT ROOM ACOUSTIC LININGS

Where specified in the Particular Specification or Drawings, the A/C Contractor


shall supply and install acoustic linings to walls and / or ceilings of the plant
rooms in order to reduce the reverberant noise levels of the plant rooms.

The wall liner board shall be secured by 1.5 mm thick galvanised steel 'z' or
channel sections of 50 mm deep which shall be firmly fixed to the wall surfaces
at 600 mm intervals. The wall liner boards shall be protected by 0.8 mm thick
galvanised perforated metal plates which shall be secured by self-tapping screws
to the galvanised steel sections. The perforated metal plates shall be removable
to enable future maintenance.

Section B8 AC_GS
Page 10 of 11 2017 Edition
B8.14 FLOATING FLOORS

In cases where machines are adequately mounted to reduce vibration transfer but
emit transmittable noise into the air space of the plant room which is above a
noise-sensitive area, it may be necessary to mount all the plant in the room on a
floating floor.

Unless the situation is one of incorrect plant selection by the A/C Contractor, the
detailed design and construction for the floating floor will be provided to the
A/C Contractor. In such cases the A/C Contractor shall avoid any action that
may subsequently undermine the acoustic performance of the air space formed
under the floating floor.

In such situations, it is likely that the walls and ceiling will also be required to
be acoustically treated by the specialist or Building Contractor. Again, the A/C
Contractor shall avoid any action that will undermine the acoustic programme of
the acoustic absorption membrane.

B8.15 SPECIALIST MANUFACTURERS INSPECTION

On completion of the installation of all noise and vibration control devices, the
(local or overseas) representative of the acoustic and vibration
equipment/materials manufacturer shall inspect the completed system and report
in writing to the A/C Contractor concerning any installation errors, improperly
selected isolation devices, and/or other faults that could adversely affect the
overall performance of the system.

The A/C Contractor shall then submit a report to the Supervising Officer in
which the report shall include all findings of the manufacturers representative
and confirmation of the satisfaction completion of all isolation work together
with any remedial actions proposal.

Where remedial action has to be taken by the A/C Contractor, further


inspections shall be carried out until all faults are rectified.

The A/C Contractor shall allow the cost of visiting the Site by the (local or
overseas) representative of the noise and vibration equipment/materials
manufacturer for this purpose.

B8.16 INDEPENDENT INSPECTIONS

In addition to the inspection of the A/C Contractors works by the specialist


manufacturers representative, independent parallel inspections and tests may be
carried out by others under direct instructions of the Supervising Officer. Any
deficiencies revealed by these inspections and tests shall be rectified by the A/C
Contractor at no additional cost to the Employer.

Section B8 AC_GS
Page 11 of 11 2017 Edition
SECTION B9

PIPEWORK, VALVES, COCKS AND STRAINERS

B9.1 GENERAL

This section covers pipework for: -

B9.1.1 Chilled or hot water circulation, vent & drain.


B9.1.2 Condensate drainage.
B9.1.3 Condenser cooling - fresh water circulation.
B9.1.4 Condenser cooling - sea or brackish water circulation.
B9.1.5 Make-up cold water supplies.

Note:Pipework fitting and accessories for refrigerant systems shall read in


conjunction with Section B6 of this General Specification.

Pipework and valves for pneumatic control systems will be fully specified in the
Particular Specification. When mild steel or malleable iron support and fixing
accessories are called for, they shall be hot dip galvanised.

B9.2 AUTOMATIC AIR VENTS

Automatic air vents shall be provided at all high points in the pipework. They
shall be installed in the highest points of the sections where they are intended for
venting.

Air bottles shall be made from 50 mm size tube, each approximately 230 mm
long, fitted with a cap and 8 mm size air cock; they shall be fitted to equal tees
or have 50 mm size connections if the main is 50 mm or above. Where an air
bottle is fixed out of reach, an 8 mm extension tube shall be run from the cap to
within 1.5 m of the floor and terminated with an 8 mm size needle-seated key-
operated air cock.

B9.3 BELLOW EXPANSION JOINTS/ANCHORS AND GUIDES

B9.3.1 General

Movements of the pipework due to changes in temperature shall be


accommodated by the natural flexibility of the pipework run or by
bellow expansion joints, in either case allowable stress levels should
not be exceeded.

Where expansion joints are utilised, they shall be manufactured in


accordance with the design philosophy for thin walled bellow
membranes as laid down by the Expansion Joint Manufacturers
Association (EJMA).
Section B9 AC_GS
Page 1 of 15 2017 Edition
B9.3.2 Axial Movement Pattern

Axial movement bellow expansion joints on all services shall


comprise thin wall multi-plied omega formed convoluted bellows of
stainless steel material to BS EN 10029:2010, BS EN 10051:2010
and BS EN ISO 9445:2006 of appropriate type. Bellows should be
argon arc welded to carbon steel end fittings utilising a stainless steel
seal ring to reinforce the bellow cuff end.

The bellow expansion joint shall be provided with a close fitting


stainless steel internal liner to reduce turbulent flow.

End termination to be carbon steel threaded male to ISO 7-


1:1994/cor1:2007 or carbon steel flanges to ISO 7005-1:2011
Standard to suit the line pressures.

For copper or non-ferrous pipework systems expansion joints shall be


manufactured in stainless steel throughout. The bellow expansion
joints shall be installed with pre-cold setting to their required length
to suit the temperature condition at the time of installation. The joints
shall be rated suitable for the required amount of designed axial
movement and shall be capable of performing the required cycles
within the working life of the pipework. Mild steel outer protection
sleeves shall be fitted to the bellows only when the units are open to
the environment and exposed to risk of damage or when it is
necessary to carry lagging over the joint.

Units should be installed in strict accordance with the manufacturers


recommendations. Manufacturers of expansion joints should be
approved to ISO 9001:2008/Corr1:2009.

B9.3.3 Angular or Lateral Movement Pattern

These bellow expansion joints shall generally comply with the


requirement as specified in this General Specification. Hinge and
shackle or centre joining tube, tie bars and spherical nut arrangement
shall be carbon steel to ISO 9692-1:2013 fully designed to contain the
pressure thrust. End termination to be flanged to ISO 7005-1:2011
Standard to suit the line pressures.

The joints shall be designed to meet the required angular movement


or the required movement in all directions perpendicular to the axis of
the bellows.

B9.3.4 Provision for Anchors and Guides

Anchors and guides shall be installed according to the


recommendations of the expansion joint manufacturer and the details
shall be submitted to the Supervising Officer for approval before
manufacture commences.

Section B9 AC_GS
Page 2 of 15 2017 Edition
(a) Anchors

Allowances shall be made for anchors capable of withstanding


the maximum stresses created within the pipework system, and
have adequate safety margin. These shall be positioned as
indicated on the layout drawings or as necessary shop
drawing/details introduced by the A/C Contractor.

On steel pipework, the pipe shall be welded to the anchors via


heavy steel straps. On copper pipework, the pipe shall be
brazed to the anchors via heavy copper straps.

(b) Guides - Axial Movement Pattern

The pipework shall be guided along its length and the guides
shall be capable of withstanding not less than 15% of the
maximum stresses created within the pipework system and
have an adequate safety margin.

Guides shall be adjustable in both directions in the lateral


plane, so that pipework can be accurately aligned with the
expansion joint.

Each guide shall not be less than 2 pipe diameters long and
shall have a minimum manufacturing clearance of the pipe
diameter.

The distance from the expansion joint to the first guide must
not be greater than 4 pipe diameters, and the distance between
the first guide and the second guide must not be more than 14
pipe diameters. Guides thereafter should be spaced in
accordance with normal pressure performance requirements as
a minimum standard.

(c) Guides - Angular or Lateral Movement Pattern

Directional guiding shall apply, such as side plates, local to the


expansion joint, the remainder of the pipework should be
supported in the nominal way, by roller or frictional supports,
or pipework hangers.

A combination of axial, angular or lateral movement guides


shall not be permitted.

B9.4 CHANGES IN PIPE SIZE

Changes in pipe size can be facilitated at tees by reduction on branch or outlet.

Reduction on bend elbows or by bushes is not permitted without prior


permission of the Supervising Officer.

Section B9 AC_GS
Page 3 of 15 2017 Edition
Reduction by means of straight through reducing sockets is permitted.

Care must be taken in carrying out reductions to ensure that air is not entrapped
at high points. In such case, it shall be necessary to install eccentric reducing
sockets with the "flat" at the top for horizontal pipework and concentric reducer
for vertical pipe riser.

B9.5 CONNECTIONS IN PIPEWORK

For non-welded pipework, connections shall be by means of screwed fittings,


mechanical couplings, flanges or unions. The use of "long screws" shall not be
permitted, unless otherwise approved by the Supervising Officer.

Unless otherwise specified, flanges complete with appropriate gaskets, nuts,


bolts and washers shall be used to connect up all plant and equipment such that
it can easily be removed for servicing or replacement.

B9.6 FLOW MEASURING

Methods for measuring flow rates in chilled or hot water and/or other liquid
circuits shall be in accordance with Section C10 of this General Specification.

B9.7 FLUSHING DOWN AND DRAINAGE

15 mm diameter key-operated drain cocks with hose unions shall be fitted to the
lowest accessible points of the system pipework and also on individual items of
plant to ensure complete drainage.

20mm or above drain cocks shall be required for rapid flushing down in
connection with water treatment and dead legs or stagnant water corners of
chilled water or condensing water circulation pipework.

B9.8 JOINTS AND FITTINGS FOR STEEL PIPEWORK

B9.8.1 Joints on all permanently concealed pipework and all pipework over
100 mm size shall be welded unless otherwise agreed by the
Supervising Officer. The other pipework may be of screwed or
welded joints. Mechanical coupling joints may be used for joints
under the conditions as stated in Clause B9.8.5. When the A/C
Contractor chooses to use screwed joints at least one of the two
engaging components shall be taper-threaded to ISO 7-1:
1994/Cor1:2007 or BS EN 10226-1:2004 and the joints between them
shall be made with approved jointing material, selected to suit the
appropriate type of services. For pipework without anti-rust threaded
joints, it shall be patched up with galvanised painting or anti-
corrosion paint before making such joints.

Section B9 AC_GS
Page 4 of 15 2017 Edition
B9.8.2 At dismantling points or where the pipework is connected to an
appliance, ground-in spherical seated unions shall be used for
pipework up to 50 mm size and flanges shall be used for pipework at
65 mm size and above. The flanges shall be to ISO 7005-1:2011 of
appropriate type or another acceptable national/international standard,
such as BS, EN or BSEN. Flanged joints shall be made with flat ring
gaskets suitable for the pressure and temperature and extending to the
inside of the bolt circles.

B9.8.3 Screwed fittings, other than sockets, shall be malleable cast iron,
banded or beaded pattern. Standard but welding fittings shall be used
on welded pipework. Use of mixed joints shall be prohibited.

B9.8.4 Flanges for mild steel pipework shall be forged steel and machined
over the raised or flat faces. Headers shall be of flanged mild steel
tube with flanged outlets welded on and spare outlets shall be blanked
off with bolted flanges.

B9.8.5 Where specified, and/or subject to the Supervising Officers written


agreement, mechanical pipe couplings may be employed for pipe
connection (except for connections to units incorporating
reciprocating compressors or where the water temperature exceeds
93oC, unless the couplings are suitable for these conditions and
acceptable to the Supervising Officer.)

Mechanical pipe couplings shall be self-centred, engaged and locked


in place onto the grooved or shouldered pipe and pipe fitting ends.
The pipe connection shall result in a positive watertight couple, where
flexible types shall provide reasonable allowance for angular pipe
deflection, contraction and expansion, and where rigid types shall
provide no joint movement, angular pipe deflection, contraction or
expansion. The coupling housing clamps shall consist of two or more
malleable or ductile iron castings or rolled steel segment holdings
with a composition water sealing gasket of suitable working
temperatures, so designed that the internal water pressure will
increase the water tightness of the seal. The coupling assembly shall
be securely held together by two or more oval-neck heat treated
carbon steel track head bolts and nuts. All pipe fittings connected to
mechanical pipe couplings shall have groove and shouldered ends and
shall be malleable or ductile iron castings. Flanged or threaded end
valves may be used with grooved adapters.

Before couplings are assembled, pipe ends and outsides of gaskets


shall be lightly coated with grease or graphite paste to facilitate
installation.

Pipe grooving shall be in accordance with the pipe coupling


manufacturers specifications. Pipes may be cut-grooved or roll-
grooved as recommended by the manufacturer. The cut-grooving
shall be roll-grooved without the removal of any metal.

Section B9 AC_GS
Page 5 of 15 2017 Edition
The entire coupling installation shall be in accordance with
manufacturers recommendations.
B9.8.6 Couplings or flange adapters for plain ended pipework shall be cast
iron or steel, slip-on type as approved by the Supervising Officer: -

Coupling shall consist of: -


(a) Sleeve (without centre register);
(b) End flanges;
(c) Sealing rings; and
(d) Bolts and nuts.

Flange adapter shall consist of: -


(a) End flanges/sleeves;
(b) Sealing rings; and
(c) Studs and nuts.

To provide hard and durable protection against impact, abrasion,


chemicals and low temperature, all couplings and flange adapters
shall be coated with Rilsan Nylon 11 by either a dip process giving a
coating thickness of 250 - 375 microns or an electrostatic spray
process giving a coating thickness of 150 - 250 microns.

B9.9 JOINTS AND FITTINGS FOR COPPER TUBES

Fittings for copper pipework shall be as follows: -

B9.9.1 Size up to and including 65 mm shall be of the capillary or


compression type to ISO 2016:1981 or BS EN 1254-1 to BS EN
1254-4 for water distribution purpose and ASME B16.22 for
refrigeration copper fittings for refrigerant distribution purpose. Size
of the 76 mm and 108mm shall be the flanged to ISO 7005-1:2011,
ISO 7005-2:1988 and ISO 7005-3:1988. Size for pipework above
108 mm shall be flanged or welded.

B9.9.2 Pipework shall be arranged with adequate connection points to allow


easy dismantling. Connection points in copper pipework size up to
and including 65 mm size shall be unions or screwed and for
pipework of size 76mm and above shall be flanged.

B9.10 PIPEWORK GENERAL DETAILS

B9.10.1 Pipework shall follow the contours of walls and shall be suitably
graded not less than 1 in 500 to ensure proper venting and draining.
Generally, the clearance between pipework (or the lagging) and the
wall and any other fixtures shall be not less than 25 mm. Pipework
shall not run near to or above electrical appliances, cables, trunkings
and conduits.
Section B9 AC_GS
Page 6 of 15 2017 Edition
B9.10.2 Where two or more pipe runs follow the same route, all pipes shall
run parallel with one another and to the building structure without
prejudice to the necessary allowances for venting, drainage or other
reasonable restrictions. Any pipework which requires subsequent
insulation shall be adequately spaced to allow for individual finish.

B9.10.3 Purpose-made sets or springs may be used where it is necessary to


deviate from a straight run in ungalvanised pipework.

B9.10.4 Sets or springs in tubes of 50 mm size and above shall be heat-treated


and the tubes shall remain circular after setting. In galvanised
pipework, no deviations shall be formed from standard fittings.

B9.10.5 Tubes shall be reamed after cutting and shall be free from burrs, rust,
scale and other defects and shall be thoroughly cleaned before
erection. Pipe ends left open during the progress of work shall be
temporarily closed with purpose-made metal or plastic plugs or caps,
or blank metal flanges and protect from corrosion.

B9.10.6 Joints shall not be made in the thickness of any wall, floor or ceiling
and pipework shall not be embedded in the structure of floors unless
otherwise instructed by the Supervising Officer. Where pipework
passes through walls, floors or ceilings, sleeves shall be provided.
Pipework passing through floors shall, where specified, be provided
with approved type floor and ceiling plates and fastened securely to
the sleeve. Sleeves shall be of the same metal as the pipe, unless
otherwise accepted by the Supervising Officer. The space between
pipework and sleeve shall be sealed with an approved fire resisting
material having FRP of not less than that of the wall and floor and in
compliance with relevant regulations and code of practices.

B9.10.7 All entry and exit holes to or from a building for a pipework services
shall be sealed and plugged. The sealant shall be a mastic compound
or silicone rubber. Where the pipework enters the building through a
large hole or duct, a mild steel blanking plate not less than 6 mm
thick shall be built into the wall of the hole or duct. The service pipes
shall pass through clearance sockets welded to the plate. The space
between pipe exterior and socket interior shall be sealed and plugged
with rockwool or equivalent material having an FRP of not less than
that of the wall and in compliance with the relevant regulations and
code of practices, all to the approval of the Supervising Officer.

B9.10.8 All fittings shall, as far as practicable, be the same size as the tubes
and pipes connected to them. Bushed outlets will only be accepted if
the required outlet size of a fitting is not of standard manufacture.
Eccentric bushings and square tees shall be used where concentric
bushings and pitcher tees may cause air to be trapped in the system.

B9.10.9 Elbows shall be used, where practicable, in preference to bends.


However, square elbows will not be permitted. Unless otherwise

Section B9 AC_GS
Page 7 of 15 2017 Edition
specified, long radius elbows shall be used in order to minimise
hydraulic resistance.

B9.10.10 In the event of the bends being formed in the lengths of pipe, a
hydraulic bender shall be used to have "shoes" of the correct size for
the relevant pipe. Flattening or distortion of the bore will not be
accepted.

B9.10.11 For forming bends in small bore, copper pipe up to size 25 mm pipe
bending springs may be used but again there must be no distortion of
the pipe involved.

B9.10.12 In the case of all bends formed in the pipe, these shall constitute long
radius bends.

B9.10.13 All centrifugally cast ductile iron buried mains shall be coated
externally with zinc. Metallic zinc shall be used with a zinc content of
not less than 99.9% by mass. The zinc shall be applied at the
manufacturers works to the oxide skin of the pipe surface which
shall be dry, free from dust, non-adhering particles, oil or grease. The
zinc coating shall cover the external surface of the pipe to a mean
density of 130 g/m2. Spiral appearance is permissible only if there is
no bare patch.

B9.10.14 On pipework up to and including 50 mm nominal bore, minor type


fittings shall be provided to make up to valves, expansion pieces,
loops and items of plant.

B9.10.15 Short radius elbows shall only be used at the discretion of the
Supervising Officer where long radius elbows will not fit or are not
manufactured.

B9.10.16 Where pipes are ordered galvanised, the zinc content shall be not less
than 98.5% by weight of zinc and at a temperature suitable to produce
a complete uniformly adherent coating of zinc.

B9.10.17 Pipes which are to be screwed shall be galvanised before servicing.


Pipes which are to be fitted with welded flanges shall be flanged
before galvanising. Galvanised treatment on all welding joints shall
be required after welding.

B9.11 PIPEWORK LAYOUT

The Drawings indicate the size and general layout of the required pipework.
The exact position may not be indicated on the Drawings as for the purpose of
clarity, they are generally shown as separately spaced out from one another as if
they were at the same plan level. The A/C Contractor shall accurately set out the
various pipelines in the Installations in compliance with the provisions of
Clauses A3.16 and A4.3 of this General Specification.

Section B9 AC_GS
Page 8 of 15 2017 Edition
B9.12 PIPEWORK SUPPORTS, EXPANSION JOINTS AND ANCHOR POINTS

B9.12.1 Where the Employers Guide Drawings& Details for pipework


supports and brackets, expansion joints and anchor points are issued
with the Contract or have previously been issued to approved
contractors for general application on the Employers projects, these
standard details shall be followed "in-principle" but adjusted as to the
detail in order to suit the particular circumstances. Such adjustments
shall be indicated on the A/C Contractors own Installation/Shop
Drawing and loading calculation Submissions and be approved by the
Supervising Officer before work commences.

B9.12.2 Pipework shall be supported so as to permit free movement due to


expansion and contraction. Pipework supports shall be installed as
near as practicably possible to joints and changes in direction. Each
support shall take its due proportion of the load. The spacing of the
supports shall not exceed the centres given in Tables B9.17-(1),
B9.17-(2) and B9.17-(3) under Clause B9.17. Where there are two or
more pipes, the spacing shall be based on the centres required by the
smallest bore pipework.

B9.12.3 Vertical rising pipework shall be supported at the base or, as indicated,
to withstand the total weight of the riser. Branches from risers shall
not be used as a means of support for the riser. If such base has to be
rested on an intermediate floor slab, the A/C Contractor must draw
particular attention to the Supervising Officer for structural
reinforcement to the floor slab and also allow for additional treatment
to the base as required by the Supervising Officer.

B9.12.4 Where pipework up to 50 mm size is fixed to solid wall, brackets may


be of the screw-on or long shank built-in type in case the walls are
plastered, only the long shank built-in type shall be used. For fixing
to woodwork and lightweight partitions or walls, brackets shall be of
the screw-on pattern of adjustable two-piece type. Brackets for mild
steel and plastic pipework shall be mild steel or malleable iron;
brackets for copper pipework shall be brass or gunmetal. The upper
half of the pipe clip shall be detachable without disturbing the fixing.

B9.12.5 Brackets screwed to walls shall be secured by expanding plugs.


Other purpose designed fixing devices or softwood plugs will not be
permitted.

B9.12.6 Pipework of 65 mm size and larger, subjected to expansion and


contraction and hung from supports shall be suspended on swivel
hangers unless otherwise agreed by the Supervising Officer.

B9.12.7 Unless otherwise specified, hangers for horizontal pipework at high


level shall be supported from galvanised mild steel angle or channel
sections or approved proprietary devices supplied by the A/C
Contractor, suitable for building-in or otherwise securing to the
structure by the Building Contractor. Adjustable mild steel hangers
shall be used. Pipe rings shall be of malleable cast iron or fabricated

Section B9 AC_GS
Page 9 of 15 2017 Edition
steel, made in halves and secured by bolts or screws. Alternatively,
malleable iron hinged pipe rings may be used. Calliper type hooks
will not be permitted.

B9.12.8 Where pipework is fitted in service duct or trenches or where it is of


65 mm size or greater and supported from walls, the design of the
pipe supports, guides and anchors shall be in accordance with the
Drawings. Otherwise, the A/C Contractor shall submit details and
proposal to the Supervising Officer for approval. Where roller
supports are required, they shall be of an approved type. The
performed insulation shall be kept free of the rolling surface. Load-
bearing insulation at supports, where required, shall be fitted by the
A/C Contractor at the time of erecting the pipework.

B9.12.9 For copper pipework, the anchors shall be provided by wide copper
straps secured to the pipework in such a manner that the pipe is not
damaged.

B9.12.10 The A/C Contractor shall supply, and fix in position ready for
building-in, all cleats, brackets and steelwork required for anchor
points. Anchor steelwork secured to the bottoms of ducts or trenches
shall be coated with hot-poured bitumen to inhibit future corrosion.

B9.12.11 Supports for plastics pipework may be of any approved pattern that
prevents free axial movement of pipe at all temperatures and have
radial edges to prevent cutting into the pipe. The entire bearing
surface must be sufficiently wide to prevent indentation.

Heavy "in-line" equipment must be supported independently. Valves


and meters must also be supported independently, where necessary.

Supports for pipes carrying water at a maximum temperature of 15oC


and covered with lightweight insulation shall be spaced in accordance
with Table B9.17-(3) under Clause B9.17. Alternatively, the
pipework may be continuously supported, provided that the thermal
insulation covering the pipework is sufficiently rigid to ensure that no
compression or deformation of the insulation occurs.

B9.12.12 Provision for movement due to expansion and contraction shall be


generally as indicated and/or shall be by changes in direction of the
pipework, by loops or by other approved expansion devices.

B9.12.13 Supports and guides shall be arranged to ensure that all movement is
taken up by the change in direction of the pipework or by the loop or
device.

B9.12.14 The spacing of supports for steel, copper and plastic pipework shall
be in accordance with Tables B9.17-(1), B9.17-(2) and B9.17-(3)
under Clause B9.17.

B9.12.15 Cold bridge should be prevented between the insulated pipework and
the associated hangers and pipework supports.

Section B9 AC_GS
Page 10 of 15 2017 Edition
B9.12.16 All metal mounting and fixing brackets for water pipework shall be
pre-fabricated off-site.

B9.13 PIPEWORK VIBRATION DE-COUPLERS

Pipework connections to the suction and delivery outlets of pumps and other
vibrating machines shall be isolated from such sources of vibration by means of
anti-vibration couplings as detailed in Sections B8 & C8 of this General
Specification.

The vibration de-couplers shall be capable of attenuating the vibration of the


plant such that the bulk of the vibrations are prevented from being transferred to
the pipework.

Wherever vibration de-couplers are installed, the adjacent pipework shall be


adequately supported by guide type brackets.

B9.14 PLASTIC PIPEWORK

Fittings for plastics pipework shall be as follows: -

B9.14.1 Fittings shall be of the same material as the pipework to which they
are joined. They shall be made or approved by the pipe
manufacturers and suitable for the solvent welding process. Where
screw threads are required (e.g. at connections to metal valves,
strainers, etc.), a factory made threaded adapter shall be used.
Adapters shall be made from heavy weight tube with an appropriate
thread at one end; the other end shall form part of a socket and spigot
solvent welded to the plastic pipe. As a general rule UPVC pipe
should only be made threaded and screwed into metal "Female"
threaded fittings.

B9.14.2 Joints between pipe and pipe fittings shall be made by the solvent
welding process. No cleaning fluid or solvent cement other than that
supplied or recommended by the pipe manufacturer shall be used.

B9.14.3 Where it is required to form a spring in the pipe run, the pipe shall be
softened by immersion in (or by pouring on) heated brine, glycerine
oil or water as recommended by the pipe manufacturer. The use of a
naked flame on the pipe surface will not be accepted.

B9.14.4 Unless otherwise specified, connections to items of plant such as


pumps or air cooler batteries shall be made by means of flanged joints.
The plastic pipe shall terminate with a socket flange of the full face or
stub type welded on by the solvent process and having a loose metal
backing ring; the ring and the flange shall be drilled to match the
mating flange. The joint shall be made with a neoprene or similar
gasket.

Section B9 AC_GS
Page 11 of 15 2017 Edition
B9.14.5 Where UPVC is used for condenser cooling circuits and for the inlet
and outlet to pumps, it must be effectively isolated from the vibration
of the machine. This shall be achieved by the insertion of flanged
synthetic rubber vibration de-couplers installed between UPVC
pipework and plant on all connections.

B9.15 SPECIALISED HYDRAULIC SYSTEM BALANCING VALVES

B9.15.1 In addition to those specified, the A/C Contractor shall allow


providing necessary hydraulic valves at all points on the system
where circulation flow balancing must be carried out in order that the
system balancing can be done.

B9.15.2 These valves shall be of manufacture approved by the Supervising


Officer and be designed to: -

(a) Allow measurement of pressure differences across the valve;


(b) Allow measurement of flow through the valve;
(c) Allow for proportional balancing of the system;
(d) Provide shut off;
(e) Provide for venting (where required); and
(f) Provide for draining (where required).

B9.15.3 Construction

10 - 50 mm Gunmetal Working pressure up to 2 MPa


( to BS EN 1982:2008 )
65 - 300 mm Cast Iron Working pressure up to 1.6 MPa
( to BS EN 1561:2011 and
ISO 185:2005 )

The valve will be constructed with angled seat and valve handle
complete with two plug type pressures tapping on each side of the
valve seat.

Drain or vent plug valve

Valves 10 - 50 mm with screwed ISO 7-1:1994/Cor1:2007 and 7-


2:2000 connections.

Valves 65 - 300 mm with flanged ISO 7005-1:2011, ISO 7005-


2:1988 and ISO 7005-3:1988 connections.

B9.15.4 Commissioning and Testing Equipment

One set (or more if specified) of electronic measuring equipment for


use with hydraulic balancing valves shall be provided by the A/C

Section B9 AC_GS
Page 12 of 15 2017 Edition
Contractor for initial balancing and commissioning of the system
where hydraulic balancing valves are installed.

At completion of the work, one new set of test equipment shall be


handed over to the Supervising Officer for subsequent monitoring and
adjustment by the Employers operation and maintenance staff.

See also Part H of this General Specification.

B9.16 'T' AND 'Y' FITTINGS

Except at vent and drain points, all tees and 'Y' fittings shall be of the swept type.
The sweep radius being at least equal to that of the medium bend but where
specified as a long sweep it shall then be equal in radius to the long bend.

B9.17 SUPPORTS FOR PIPEWORK

Table B9.17 - (1) Supports for Steel Pipework

Supports with suitable load spreader for the pipework shall be provided.

Intervals for Intervals for


Horizontal runs Vertical runs
Size of tube Bare Lagged Bare and Lagged
mm m m m
15 1.8 1.8 2.4
20 2.4 2.4 3.0
25 2.4 2.4 3.0
32 2.7 2.4 3.0
40 3.0 2.4 3.7
50 3.0 2.4 3.7
65 3.7 3.0 4.6
80 3.7 3.0 4.6
100 4.0 3.0 4.6
125 4.5 3.7 5.5
150 5.5 4.5 5.5
200 8.5 6.0 8.5
250 9.0 6.5 9.0
300 10.0 10.0 10.0

Section B9 AC_GS
Page 13 of 15 2017 Edition
Table B9.17 - (2) Supports for Copper Pipework

Intervals for Intervals for


horizontal runs vertical runs
Size of tube Bare Lagged Bare and lagged
mm m m m
15 1.2 1.2 1.8
22 1.2 1.2 1.8
28 1.8 1.5 2.4
35 2.4 1.8 3.0
42 2.4 1.8 3.0
54 2.7 1.8 3.0
65 3.0 2.4 3.7
76 3.0 2.4 3.7
108 3.0 2.4 3.7
133 3.7 3.0 3.7
159 4.5 3.7 3.7

Table B9.17 - (3) Supports for Plastics Pipework

Nominal Intervals for Intervals for


Bore horizontal runs Vertical Runs
of Pipe
mm m m
15 0.75 1.5
22 to 28 1 1.8
28 to 35 1 2
42 1.2 2.4
53 to 65 1.4 2.8
76 1.8 3.5
108 and over 2 4

B9.18 WELDING AND BRAZING

The procedure and the competence of the operative shall be in accordance with
the recommendations contained in the following B&ES publications: -

B9.18.1 "Welding of Mild Steel Pipework"

B9.18.2 "Code of Practice - Brazing and Bronze Welding of Copper Pipework


and Sheet"
Section B9 AC_GS
Page 14 of 15 2017 Edition
Welding operations which are beyond the scope of (a) and (b) shall
comply in particular with: -

B9.18.3 ISO 9692-1:2013 and ISO 15609-1:2004 -relevant subsections for


metal-arc welding (steel pipe)

B9.18.4 ISO 9692-1:2013 and ISO 15609-2:2001 -relevant subsections for gas
welding (steel pipe)

B9.18.5 ISO 5187:1985 - Brazing (copper pipe)

Where the visual inspection and tests reveal those welding joints which are
reasonably believed to be unacceptable, the Supervising Officer shall be entitled
to have such welding examined by radiography or other approved inspection
method and independently assessed. The A/C Contractor shall be responsible
for the cost of the tests and subsequently remedy the work to the satisfaction of
the Supervising Officer if tests prove the welding joints to be non-compliance
with the specification.

B9.19 LABELLING AND CIRCUIT CONTROL DIAGRAM OF VALVES

All plant room valves and circuit control valves shall be provided with approved
plastic labels in compliance with Clauses A3.13.1 or A3.13.2.

A circuit control diagram showing the location of each isolating, regulating and
control valve shall be provided and fixed in a glazed hardwood frame in a
position indicated by the Supervising Officer or as specified in Clause A4.4.4.

Section B9 AC_GS
Page 15 of 15 2017 Edition
SECTION B10

SYSTEM MONITORING INSTRUMENT

B10.1 GENERAL

Clauses related to electrical control shall be read in conjunction with Sections


B4, B5 and B7.

All instruments, gauges and devices with indication scales shall be mounted in
such a position that they can be accessed and read easily.

B10.2 SYSTEM STATIC PRESSURE GAUGES FOR AIR DISTRIBUTION


SYSTEMS

System static pressure gauges shall be provided as per following table B10.12
(1). Two gauges shall be provided for each fan and arranged to indicate system
static pressure on the intake and discharge sides.

The gauges shall be connected into the system at points where the static
pressures are steady. On completion of commissioning, the suction and delivery
static pressures indicated by the gauges shall be indelibly marked adjacent to
them to serve as system reference points.

B10.3 THERMOMETERS - AIR IMMERSION

Two 12 mm diameter test holes shall be provided for the insertion of


thermometers (for measuring both dry and wet bulb temperatures at the same
time) in each of the following locations of each air handling unit (fan coil units
excluded): -

B10.3.1 Outdoor air connection

B10.3.2 Return air connection

B10.3.3 Supply air connection

B10.3.4 Mixed air connection

B10.3.5 Before and after each air cooling coil/heater bank

B10.3.6 Before and after each humidifying device

Sealing plugs shall be provided and fitted to all test holes. Test holes shall be
positioned so that thermometers are not affected by thermal radiation.

Permanent thermometers shall be inserted in test holes for systems as in table


B10.12 (1).

Section B10 AC_GS


Page 1 of 7 2017 Edition
For systems with flow rate less than 5 m3/s, four nos. of thermometers or in
quantity equivalent to 10% of the total numbers of the test holes, whichever is
greater, shall be provided with each individual packed in protective casings and
to facilitate identification of correct location, and handed to the Supervising
Officer. Each thermometer shall be complete with a pierced plug to fit the test
hole and each wet bulb thermometer shall be provided with a fabric sleeve.

B10.4 THERMOMETERS - LIQUID IMMERSION

Thermometer pockets shall be provided adjacent to the flow and return


connections to/from each heating coil and cooling coil as per following table
B10.12 (1). The location and depth of thermometer pockets shall be
determined to assure correct reading of liquid temperature. Each pocket shall be
filled with sufficient approved heat conducting medium.

Cylindrical brass case, mercury-in-glass thermometers of straight or angle type


shall be provided and permanently installed in pockets.

B10.5 PRESSURE GAUGES FOR WATER SYSTEMS

Pressure gauges shall be provided as per following table B10.12 - (1). Pressure
gauges shall be fitted with lever handle cocks and shall have siphon pipes,
pigtail with 2 complete turns minimum or pulsating damper, fitted between them
and the system pipework.

B10.6 SELF SEALING TEST POINTS

Self-sealing test plugs suitable for temperature and pressure measurement can be
provided to substitute the thermometer pockets and pressure gauges for systems
with capacities or flow rates less than the values mentioned in Clauses B10.2,
B10.4 and B10.5.

The test plugs shall be fitted with captive caps for sealing them when not in use
and shall have internal self-sealing devices. The plugs and probes shall be of
materials suitable for the respective application and shall be submitted to the
Supervising Officer for approval prior to ordering or installation.

Valve pressure tapping shall be provided for water systems.

Four thermometers and four pressure gauges for each range of temperatures and
pressures, suitable for use with the test plugs, shall be packed in a protective
casing and handed to the Supervising Officer together with adequate supply of
all necessary insertion lubricant.

B10.7 VOLTAGE AND CURRENT READINGS

As detailed in Section B7 and following table B10.12 (1) of this General


Specification or specified in the Contract, the A/C Contractor shall provide

Section B10 AC_GS


Page 2 of 7 2017 Edition
instruments to monitor the supply voltage, and/or current to individual or groups
of refrigeration plant.

B10.8 POWER FACTOR MONITORING

Where indicated elsewhere in this General Specification or in the Contract, the


A/C Contractor shall provide instruments to monitor the power factor of the
equipment provided and installed under the Contract as individual items or
groups of plant.

B10.9 POWER CONSUMPTION METERING

Power Consumption (kWh) metering devices shall be installed for the following
plants and equipment as per following table B10.12 (1).

B10.10 LIQUID FLOW RATE METERING

Appropriate type of flowmeters shall be installed for the following plants and
equipment as per following table B10.12 (1).

B10.11 OTHER TYPES OF METERING DEVICES

B10.11.1 Pitot Static Tube

The device shall provide differential pressure reading through: -

(a) The high pressure velocity head sensor, with interpolating tube
to continuously average velocity pressure, facing the flow; and

(b) A low pressure sensor which detects the static pressure.

The resultant differential pressure can be transmitted through


the instrument head to a differential pressure flow responder
meter.

The sensor shall not be inserted near any bends or other


fittings likely to affect the water flow by turbulence or
differential velocities across the pipe. The distance from any
such fitting upstream of the measuring point shall not be less
than 10 diameters of the pipe.

Where indicated, flow measurement as displayed on the


responder meter shall be capable of transmitting to central
control and monitoring system or simpler control system
through electronic relay amplifier.

B10.11.2 Water Consumption Meters

Section B10 AC_GS


Page 3 of 7 2017 Edition
WSD approved impeller type water meter complete with inlet/outlet
isolating valve unions and a strainer shall be provided to measure the
makeup water consumption rate.

B10.11.3 Hour Run Meters

The meter system shall be of reputable and proven manufacturers


make. Where required, it shall be suitable for working with central
control and monitoring system.

B10.11.4 Energy Meters

Where specified in the Contract, energy meters for chilled (or hot)
water system shall be provided. The energy meter shall consist of
temperature sensors for both flow and return water circuits,
electrostatic or ultrasonic flowmeter, flow transmitter/converter unit
and a calculator unit.

B10.12 PROVISION OF METERING FACILITIES

Referring to the following table B10.12 - (1), the types of metering functions
and extent of metering provisions are listed as follows and shall be provided by
A/C Contractor:

Table B10.12 - (1) Provision of Metering Facilities

Type of Metering
Type of Load Extent of Provision
Function
1. Refrigeration
(i) Chillers/ Heat a. Current (three phases To be provided except for small split
Pump/ Unitary and neutral) units below 7kW.
Air-conditioner/
Condensing b. kWh (Energy Input) )
Units/ Chilled or ) To be provided if the cooling/
Heated Water c. kWh (Cooling/ ) heating capacity exceeds
Plant Heating Energy ) 200kW, in addition to item a.
Output) ) The power metering should
) incorporate an accumulative
d. kW (Power Input) ) function for the measured data
) over time and analytical
e. kW (Cooling/ ) function to convert the power
Heating Energy ) over successive time intervals
Output) ) into energy terms for adding
) up to give the cumulative
f. Coefficient of ) energy value
Performance )

g. Hour Run To be provided if the cooling


capacity of chiller/ condensing unit/
heat pump exceeds 70kW

Section B10 AC_GS


Page 4 of 7 2017 Edition
h. Chilled Water Flow To be provided for chilled water
Rate circuit with a cooling capacity of
200kW or above. Test points shall be
provided if the cooling capacity is
less than 200kW. (See Note 1)

i. Chilled/ Hot Water Thermometers shall be provided for


Supply & Return cooling/ heating capacity exceeding
Temperature 30kW. For systems with cooling/
heating capacity not exceeding
30kW, test points shall be provided.

j. Sea Water Flow Rate )


) To be provided for sea water
k. Sea Water Intake & ) mains.
Discharge )
Temperature )

(ii) Cooling Tower a. Current (three phases )


& neutral) )
) To be provided for all fans and
b. kW ) pumps.
)
c. kWh )

d. Condensing Water ) To be provided when the total


Flow Rate ) motor power of cooling tower
) exceeds 40kW. If the total motor
e. Condensing Water ) power is less than 40kW, test
Supply & Return ) points shall be provided, in
Temperature ) addition to items a, b and c.

f. Water Volume Flow To be provided for all cooling towers.


for Make-up Water
and Bleed-off Water

2. Chilled/ Sea/
Condensing
Water
Distribution

(i) Chilled Water/ a. kWh and Current ) To be provided for all chilled
Water Pumps (three phases and ) water, sea water and condensing
(including sea neutral) ) water pumps.
water and )
condensing water b. kW (Power Input) )
pumps)

Section B10 AC_GS


Page 5 of 7 2017 Edition
c. Water Flow Rate ) To be provided for chilled/ hot
) water circuit when water flow
d. Water Supply and ) exceeds 9 L/s. Test points shall
Return Temperature ) be provided if the water flow is
) less than 9 L/s,
) in addition to items a and b
(equivalent to a cooling capacity of
about 200kW)

e. Pressure To be provided at suction and


discharge sides when the water flow
exceeds 1.3 L/s. Test points shall be
provided if the water flow is less than
1.3 L/s, in addition to items a and b.
(equivalent to a cooling capacity of
about 30kW)

(ii) Chilled Water Differential Pressure Commissioning valve to be provided


Distribution at least at each main circuit branch-
Pipework off to facilitate water balancing.

3. Air
Distribution
AHU/ PAU/ Fans a. kWh and kW (energy To be provided if motor power
and power input) exceeds 5kW.

b. Pressure To be provided at fan intake and


discharge side when fan power
exceeds 3kW.

c. Supply Air & Return Thermometers shall be provided for


Air Temperature systems with air volume flow rate of
greater than 5m3/s. Test holes shall be
provided for systems with air volume
flow rate of less than 5m3/s.

4. Central Hot a. Water Supply & Thermometers shall be provided for


Water System Return Temperature hot water system with capacity
exceeding 40kW. For systems with
capacity not exceeding 40kW, test
points shall be provided.

b. Water Flow Rate To be provided when hot water flow


exceeds 9L/s. Test points shall be
provided if the water flow is less than
9L/s. (See Note 1)

Section B10 AC_GS


Page 6 of 7 2017 Edition
Notes:

1. For measuring energy/ water consumption, A/C Contractor should


provide sufficient metering facilities for data monitoring, measuring,
logging and manipulations for different reporting entities, with
consideration on factors like system identity, different division/ group of
users and size of accommodations, etc. For joint user buildings, separate
metering facilities shall be provided to suit the organisational boundaries
or operational boundaries of the reporting entities. Particular attention
shall also be paid on the sharing mechanism among the users on
quantification and reporting the energy consumption associated with the
communal and/ or central services or facilities.

Section B10 AC_GS


Page 7 of 7 2017 Edition
SECTION B11

THERMAL INSULATION

B11.1 GENERAL

The thermal insulation works shall be undertaken by a minimum required


percentage of workers who shall have a valid certificate of completing
satisfactorily the thermal insulation training courses organised by the recognised
association as specified in the contract. Upon request, details and particulars of
these workers shall be submitted to the Supervising Officer for approval.

In general, all ductwork and equipment shall be insulated if the air conveyed
within the ductwork and the air external to it have a temperature difference
which may cause an unwanted condensation or heat loss either on the duct
surface or within the ductwork or result in unwanted thermal exchange between
the external and inside air of the ductwork.

Thermal insulation shall be applied to chilled or hot water pipework distribution


systems and to components within distribution systems such as valves, storage
vessels, strainer and accessories.

All insulation shall fit tightly to surfaces to be covered, and all slabs and
sections shall be built up close, butting edges being mitred, chamfered or shaped
as necessary. Any minor interstices left in insulation shall be filled and sealed
with granules embedded in suitable and approved adhesive compound.

Insulated pipes and ducts shall be supported on the outside of the insulation,
with load spreading galvanised iron or corrosion treated steel metal plates of
suitable size and thickness between the insulation and supports to prevent the
insulation being crushed. A higher density load bearing quality insulation or
hard wood block should be used at support points as recommended by the
insulation manufacturer and as directed by the Supervising Officer.

At the point of support, specially prepared blocks of hardwood or Styrofoam


material must be positioned to ensure the integrity of the vapour barrier and
cladding where applicable by bonding the supports to the insulation.

All materials delivered to Site shall be new, and where appropriate, colour
coded and labelled at the factory to identify different grades, sizes and types.
The insulation shall be protected from damage or deterioration before, during
and after fixing. Damaged or compressed insulation should be replaced.

Immediately before applying insulation, clean all surfaces until these are free of
rust, scale and grease, and are thoroughly dry. Under no circumstances should
the insulation be applied to wet surfaces.

Any surface to be insulated, which shows any sign of rusting or damage, shall,
prior to insulating, be thoroughly scrapped and wire brushed as necessary to
remove all rust, scale, etc. Surfaces shall then be cleaned with appropriate
solvent to remove all oil, grease and dirt prior to the application of two coats of

Section B11 AC_GS


Page 1 of 12 2017 Edition
grey epoxy primer paint and insulation. Only clean and dry insulation shall be
applied in any case, and it shall be free from damage before application.

All materials including the thermal insulation itself, together with adhesives,
paint, bands, sheeting, etc. shall be supplied with a reasonable margin for cutting,
wastage and making good damage and loss. All materials shall be stored in a
suitable manner so as to prevent them from damage or deterioration before
fixing.

All insulation shall be applied so as to give a smooth, homogeneous and linear


surface. All rigid sections shall be concentric, and accurately matched for
thickness. Steps and undulations in the surfaces are not acceptable. Any
sections or slabs having damaged ends will be rejected.

Continuous insulation shall be provided through all sleeves and insulation joints
shall be staggered with respect to joints on the associated pipework or ductwork
systems.

Insulation damaged for whatever reasons will be rejected.

Where thermal insulation is applied to the outside of piped and ducted services,
equipment and plant used to convey, store or generate fluids or gases at
temperatures lower than the design ambient dew point temperature indicated, a
water vapour barrier shall be provided unless it can be demonstrated that the
insulation material itself provide adequate barrier throughout its thickness to the
approval of the Supervising Officer. The separate type vapour barrier where
employed shall not be pierced or otherwise damaged by supports or by the
application of external cladding.

Where relevant, moisture and vapour barriers, whether applied to the ductwork,
hangers or projections, shall be continuous and completely provided throughout
the surface of the insulation, and the insulation complete with the barrier shall
be properly and firmly bound on the duct or pipe surface by appropriate fixing
provisions. Such fixing provisions shall in no way impair the insulation or the
vapour barrier. The A/C Contractor shall be responsible for any damages on the
insulation or barrier due to improper installation and shall make good or replace
the damaged insulation as appropriate and any subsequent wetting of the
insulation due to improper installation or material shall be replaced by the A/C
Contractor at his own cost.

Flexible connections on air conditioning ductwork shall be insulated with


flexible blanket made from non-flammable material. The insulated blanket is to
be wrapped with vapour barrier that conforming to Clause C11.4. The blanket
shall be wrapped around the flexible connection, overlapped and secured in
place by metal bands at both ends to the rigid ducts.

B11.2 TYPES OF THERMAL INSULATION MATERIALS

B11.2.1 Phenolic Foam Insulation


For pipe insulation and pipe support, the phenolic foam joint shall be
of unique Z-shape slip along the longitudinal joint sealed with

Section B11 AC_GS


Page 2 of 12 2017 Edition
adhesive and shall be provided with shiplap joints (male and female
joint) at both circumference ends. The shiplap joints shall be a
minimum width and depth of 10mm respectively in contact with each
other for thermal lock purpose and sealed with adhesive.

Rigid cut sections shall be used with factory applied Class 'O' facing
for pipework. "Butt-joints" of slabs shall be sealed with minimum
75 mm wide matching Class 'O' self-adhesive tape as recommended
by the insulation manufacturer. Overlap of factory applied Class 'O'
facing for cut pipe sections shall be sealed with manufacturers
recommended adhesive tape. All tapes shall be conformed to Clause
C11.4.

Factory-preformed insulated fittings formed to suit standard radius


elbows, long bends and tees shall be used wherever available,
otherwise, the Supervising Officers permission shall be sought to
neatly cut and mitre the insulation to fit around fittings. In the latter,
great care must be taken to ensure that all mitred joints are a close fit
and the aluminium foil adhesive tape is neatly applied as a finish
coating.

Flanges and other protrusions shall be insulated by factory-fabricated


oversized sections ordered to suit the diameter of the flange or
adjacent pipe insulation whichever is the greatest. The oversized
section shall overlap on to the adjacent pipe insulation by a minimum
of 75 mm width on each side.

Pipe supports shall fit around the outside of the insulation. The
insulation at the support points shall be made of heavy density load
bearing phenolic foam in preformed sections of same thickness as the
adjacent pipe insulation. This shall be complete with the same
external finish to Class 'O' as used on the adjacent standard pipe
insulation.

Reference shall be made to the insulation manufacturer recommended


support details to ensure the load bearing and dimensions of high
density foam and associated galvanised metal plate supports are
correctly inserted to spread the point loads involved.

B11.2.2 Fibreglass Insulation

All fibreglass insulation shall be completely sealed by effective


vapour barrier and self-adhesive foil tape as required by Clause C11.4.

All fibreglass insulation shall be completely sealed at all joints. All


holes, tears, punctures, etc. made in the vapour barrier shall be
completely sealed with the same specified foil tape. If damage in a
definite insulation area exceeds 5% of the insulation surface or duct
or pipe, the A/C Contractor shall be responsible for replacement with
new one.

Section B11 AC_GS


Page 3 of 12 2017 Edition
When pins are required to be used to support the fibreglass blanket,
all the pins must be fire resistant and sealed by same specified foil
tape after installation.

The material shall be adhered to the ducts with moisture and fire
resistant adhesive of an approved type. Where preformed fibreglass
sheets are to be adhered to flat surfaces such as ductwork the method
of fixing shall be approved by the Supervising Officer before the
commencement of work.

B11.2.3 Flexible Closed Cell Elastomeric Insulation

The flexible closed cell elastomeric insulation sheet shall be supplied


in rolls in dimensions recommended by the manufacturer for
application over ductwork so that the top, adjacent and bottom sheets
lapped with adjacent sheets edges and corners. Adhesives shall be
applied evenly to the entire contact surfaces if the elastomeric
insulation sheet is not a self-adhesive sheet with adjacent sides lapped
to maintain a uniform thickness at corners.

When shifting large bore flexible closed cell elastomeric tube which
has become elliptical during storage, the slit shall be made in the
flattened surface.

If the Flexible Closed Cell Elastomeric Insulation is exposed to


weather, inside plant room or services duct, protection finish coating
recommended by the insulation manufacturer shall be applied.

All coatings must be supplied by the original insulation manufacturer


and application shall strictly follow the manufacturers installation
manual to obtain the required result.

B11.2.4 Polystyrene Insulation

Unless otherwise instructed by the Supervising Officer, polystyrene


insulation shall be covered with 25 mm square wire netting of 1 mm
diameter galvanised steel wire netting reinforcement and coated on
the top with 15 mm cement plaster smoothed and finished with
painting to be completed as Clause B11.8.

B11.2.5 Pre-insulated Panel of Foam Insulation with No Ozone Depleting


Substances for Construction of Air Ducts

Whenever the foam insulation is used for pre-insulated duct system


without galvanised iron sheet metal, the following guidelines should
be followed: -

Wherever necessary, the ducts must be provided with appropriate


reinforcements to guarantee sufficient mechanical seal against a
maximum internal pressure of 500 Pa during operation. The
maximum deformation of the duct must not exceed 3% of its width or
30 mm in any case.

Section B11 AC_GS


Page 4 of 12 2017 Edition
The joints between one duct and adjacent one shall be performed
using flanges with unexposed bayonet coupling and shall be ensured
for the appropriate pneumatic and mechanical seal. Elbows shall be
provided with turning vanes wherever indicated.

The ducts shall be supported by appropriate supports at intervals of


no more than 4m whenever the greater side of the duct is less than
1 m, and intervals of no more than 2m whenever the greater side of
the duct is more than 1 m.

Accessories such as volume dampers, fire barriers or duct


heater/heating coil/cooling coil and etc., shall be provided with
independent support in such a way that their weights are not imposed
on the ducts.

The ducts shall be provided with appropriate test points for the
sensors and inspection doors for cleaning and inspection all along the
route.

B11.3 PIPEWORK FITTINGS

Unless otherwise specified, all valves, flanges, strainers, expansion joints, etc.,
are to be insulated in conformity with the pipework in which they are
incorporated, and of the same thickness. All such items where proper treatment
on pipework connected to the puddle flanges in tunnel and trench is required
shall be provided with relevant insulation filled 0.8 mm thick hammered
aluminium split boxes, arranged for easy removal, the box to enclose up to valve
handle and to have a lid for valve access. The insulation on the pipes
immediately adjacent to flanges, etc., shall be neatly swaged off to allow the
insulated boxes to be removed without damage to the pipe insulation.

All valves, flanges, strainers, glands, etc. are to be provided with insulation of
similar type to that employed on the rest of system (if appropriate to this
purpose) fitted into galvanised steel or aluminium sheet split boxes arranged for
easy removal so that access to the valves, flanges, etc. can readily be gained
without damaging the general run of insulation.

For all chilled water fittings and accessories such as valves, strainers, etc., there
shall be external protection of a box constructed with 0.8 mm thick hammer
aluminium cladding. The box shall be hinged at a point and fastened together
on the other side with a quick action snap catches.

B11.4 CHILLED WATER PUMPS AND ACCESSORIES

All chilled water pumps and their accessories shall be insulated with split box
arrangement for easy maintenance without damaging the insulation. Lids of
water boxes on chillers and similar places shall be provided so that easy access
can be obtained for maintenance without damaging the insulation.

Section B11 AC_GS


Page 5 of 12 2017 Edition
B11.5 DUCT WORK AND AIR HANDLING PLANT - METHODS OF
APPLICATION

B11.5.1 Thermal insulation shall be applied to air distribution ductwork and to


components within distribution systems such as fans, heater, heating
coil, cooling coil casings which convey conditioned air within plant
rooms and up to and including all terminal points in the system.

Air distribution systems conveying conditioned, warmed or chilled air


through conditioned spaces shall be insulated. Exhaust, ventilation or
outdoor air passing any conditioned space should also be insulated.

All ductwork (including re-circulation ductwork) conveying warmed


or chilled air through unconditioned spaces or the open air shall be
insulated.

Distribution systems conveying untreated outdoor air and exhaust air


need not be insulated unless such air distribution interconnecting with
heat recovery system/device or passing through conditioned space.

B11.5.2 Fixing methods for insulation shall minimise direct metal paths which
thermally bridge the insulation, particularly when the insulation is
metal faced. The full insulating effect shall be maintained at
connections and access openings and panels including the edges of
such openings, fasteners and stiffeners either by means of purposely
made boxes or by increasing the general thickness of insulation.
Where insulation is applied in layers, all joints in all layers shall be
staggered.

B11.5.3 At all points of support, the insulation and outer covering and vapour
seal shall be continuous and shall not be pierced or protruded by the
supports. The insulation at supports shall be of the material with
sufficient compressive strength to take up the loads transmitted to the
supports.

B11.5.4 Pre-formed sheet insulation shall be applied with adjacent sides


lapped at joints and corners to maintain a uniform thickness. The
insulation shall be fixed securely with adhesives conforming to
NFPA-90A:2012 and by impaling on fasteners which must be
galvanised iron metal studs split prongs, plastics studs or other
approved devices fixed to the thickness and weight of the insulating
materials and finishes to be applied and shall be spaced at
approximately 300 mm centres. Fastenings shall be finished flush
with the surface of the insulation to which they are applied.
Adhesives shall be compatible with the insulation and in their dry
state be non-flammable. Under no circumstances shall adhesives be
used which attack or dissolve the ductwork or insulation.

B11.5.5 Aluminium foil or plastics faced preformed sheet insulation materials


shall be placed on the outside of ductwork with adjacent sides lapped
to maintain a uniform thickness at joints and corners. All joints shall

Section B11 AC_GS


Page 6 of 12 2017 Edition
be sealed with foil tape as indicated in Clause C11.4 and held in place
with contact adhesive. The adhesive shall be suitable for the range of
ambient temperature and humidity encountered.

B11.5.6 Reinforcement of self-setting cement shall be 25 mm spaced wire


mesh of 1 mm diameter galvanised steel wire netting reinforcement.
Cement finishes applied to thermal insulation shall always be
completely dry before the application of any sealing primer and final
decorative coating. Cement application shall be planned and
executed in sections to avoid joints between wet cement and cement
already dried.

B11.5.7 Where thermal insulation is protected against the effects of weather


by plastics sheet or roofing felt, particular care shall be taken to
ensure a watertight seal at all joints. The sheet material shall be
adhered to the external surface of the insulation and all joints shall be
lapped, secured and sealed by adhesives or solvent welding. All
jointing and sealing materials and methods of application shall be to
the recommendations of the sheet supplier. Poly-isobutylene sheet
shall be not less than 0.8 mm thick and have a tensile strength not less
than 3.4MN/m2.

B11.5.8 Where an insulated duct passes through an external building element,


adequate precautions shall be taken to prevent the entry of rainwater
from the outside into the building. Details shall be submitted to the
Supervising Officer for approval well before the construction starts.

B11.5.9 Flexible insulation shall have all circumferential and longitudinal


joints sealed with tape of the same material or highly compatible with
the main insulation facing. The external surface of the insulation
shall be wrapped over with 25 mm mesh spaced wire mesh of 1 mm
diameter galvanised steel wire netting reinforcement and the netting
joints shall be secured with a lacing of 1 mm galvanised wire. Care
shall be taken to ensure that the insulation material is not crushed
during this application.

B11.5.10 Thermal insulation and/or acoustic insulation materials shall be


applied to the inside of ductwork only where specified by the
Particular Specification or Drawing. The insulation material shall be
cut to accurately fit the internal duct surfaces. The insulation shall be
fastened to the duct using adhesive spread over the entire surface in
combination with piercing fasteners finished flush with the insulation
surface. Particular care shall be taken to ensure that the edges of all
internal insulating materials, whether exposed or butted against
similar edges, are sealed and secured to the internal surfaces of the
duct. They shall be protected with galvanised iron channel sheet
metal of not less than 0.8 mm thickness and 13 mm width.
Alternatively, they may be provided with other approved means of
protection to prevent erosion and peeling. All materials shall have
adequate strength and ability to resist erosion at the maximum design
air velocity and shall not produce dust. The provisions of Clauses
B8.9 and B8.11 shall also apply where applicable.

Section B11 AC_GS


Page 7 of 12 2017 Edition
B11.5.11 Unless otherwise specified in Particular Specification, fibreglass
insulation with scrim glass fibre cloth face finish or elastomeric
insulation shall be used for internal lining material.

B11.6 CHILLED WATER PIPEWORK AND EQUIPMENT - MATERIALS


AND FINISHES

All thermal insulating materials and finishes shall be as specified in Clause


C11.2 subject to the requirements of fire properties (Clause C11.1) and vapour
barriers (Clause C11.4).

B11.6.1 Inside buildings for services concealed from view; the insulation shall
be provided as specified above and shall be finished as follows: -

(a) In normally non-accessible situations such as ducts, voids and


chases, etc., factory applied aluminium foil or plastic film
secured by adhesive self-overlaps or by matching tape
preformed sections secured by external vapour seal and left
unpainted. Where necessary on site vapour sealing compound
shall be applied to ensure a 100% seal; and

(b) In all accessible ducts, voids, chases, etc. and where indicated,
self-setting cement not less than 15 mm final thickness applied
"in-situ" to preformed sections over 25 mm spaced wire mesh
of 1 mm diameter galvanised steel wire netting reinforcement,
sealed and left unpainted. Alternatively, the insulation shall be
vapour sealed as in Clause C11.4 and then protected with
neatly applied external aluminium sheet cladding of not less
than 0.8 mm thickness with all joints sealed.

B11.6.2 Inside buildings for services exposed to view but not readily
accessible; the following shall be applied or as indicated: -

(a) Pliable plastics, elastomeric sheets or rigid plastics, not less


than 0.35 mm thick either factory applied to preformed
sections and lapped and sealed with adhesive or supplied loose
and wrapped on Site with lapped and sealed joints. The sheets
shall be either self-coloured or if required by the Supervising
Officer finally painted; or

(b) Aluminium foil faced preformed sections secured and sealed


by the application of minimum 100 mm wide matching self-
adhesive tape over all longitudinal and circumferential joints.

In both of the above cases, the integrity of the required vapour


seal must be maintained.

B11.6.3 Services in plant rooms and elsewhere where specified in the


Particular Specification or Drawing, shall receive the following

Section B11 AC_GS


Page 8 of 12 2017 Edition
treatment in order to avoid possible mechanical damage or make
necessary provision as otherwise indicated: -

(a) Enclosed in fabricated sheet hammer clad aluminium casings.


The casing shall be not less than 0.8 mm thick for pipework of
150 mm and above measured over the insulation and not less
than 0.6 mm thick on smaller pipework;

(b) Be insulated as indicated under Clause C11.2, covered as


Clause B11.5.5 and finally painted in accordance with Clause
B11.8; and

(c) Be treated with an effective high quality water based vapour


barrier coating, Class 'O' surface to BS 5422:2009.

The vapour barrier coating must be non-flammable and safe to


transport, store and use. Thixotropic consistency provides
easy application with pinhole free, smooth finish, even when
bridged over rough substrates. The dried film must be tough,
flexible, washable and resistant to acids and alkalis for a long
service life.

Glass fibre reinforcing mesh shall also be applied in between


coat. The reinforcing mesh should incorporate a thread of
10 strands by 10 strands per 650 mm2 into its construction.
When tested according to ASTM D579/D579M-10, the
materials should have a tensile strength warp of 50 g/mm2 and
fill of 50 g/mm2.

B11.6.4 Outside buildings, services exposed to the weather; either of the


following weather-proof covering shall be provided as indicated: -

(a) Enclosed in fabricated sheet hammer clad aluminium casings.


The casing shall be not less than 0.8 mm thick for pipework of
150 mm and above measured over the insulation and not less
than 0.6 mm thick on smaller pipework;

(b) Enclosed in roofing felt, sealed with adhesive with overlaps of


at least 50 mm, wrapped with 25 mm spaced wire mesh of 1
mm thick, galvanised steel wire netting reinforcement, laced
with 1 mm thick galvanised wire and painted two coats of
bituminous paint or application with 15 mm thick cement
plaster and paint;

(c) Enclosed in poly-isobutylene sheet not less than 0.8 mm thick


of tensile strength not less than 3.4 MN/m2, lapped and sealed
at all joints; or

(d) Be treated with two coats of elastomeric polymer-based heavy


duty mastic with reinforcing membrane to give a weather
resistant finish.

Section B11 AC_GS


Page 9 of 12 2017 Edition
The product shall meet the requirement of NFPA-90A:2012.
The non-combustible shall be in accordance with NFPA-
220:2012. Dry Film Fire Hazard requirements meet GSA and
the product should be tested by ASTM E84-14 (Standard Test
Method for Surface Burning Characteristics of Building
Materials).

B11.6.5 Pre-insulated pipes where specified in the Particular Specification or


Drawing, shall be of the following requirement or otherwise
indicated:-

(a) All pre-insulated pipe shall be pre-fabricated and pre-insulated


in off-site factory. All pre-insulated pipe shall consist of (i)
carrier pipe/ service pipe, (ii) thermal insulation and (iii)
external jacket/ cladding. The pre-fabrication and pre-
insulation system shall include pipe fittings.

B11.7 CHILLED WATER PIPEWORK AND EQUIPMENT - METHODS OF


APPLICATION

B11.7.1 Thermal insulation shall be applied to pipework of chilled water or


hot water distribution systems, pipework of thermal fluids of heat
recovery systems, cold condensate drain pipes, and all components
within distribution systems such as valves and storage vessels, etc.

B11.7.2 Pipework insulation shall also be deemed to include all open vents,
cold feeds, chilled/hot water tanks, expansion tanks, valves, flanges,
fittings, pumps, accessories, other chilled water plant and hot water
plant items whether specifically mentioned or not.

B11.7.3 The insulation shall fit closely to the pipework and other surfaces
without gaps between joints. Each section of preformed insulation
shall be secured to the pipe by means of circumferential bands of non-
ferrous metal, plastics fabric, or adhesive tape. Preformed sheet
materials shall be secured to chilled water containers and flat surfaces
in the same manner as specified for ductwork. Valves, flanges and
other fittings shall be insulated with "oversize" sections, around
valves fittings shall be filled with fibrous material, pieces of shaped
insulation or other approved infill. Covers which are to be removable
shall be separately secured. Two vapour barriers shall be provided,
one to totally enclose the main insulation and the other to cover the
removable insulation.

B11.7.4 At all points of support, both insulation and outer covering shall be
continuous and shall not be punctured or fouled by the supports. The
insulation at supports shall be material of sufficient compressive
strength to take the loads transmitted to the supports. The load-
bearing insulation shall be extended on each side of the supports.

B11.7.5 At entries into buildings the weather-proofed insulation shall extend


not less than 150mm beyond the inner face of the wall and be sealed

Section B11 AC_GS


Page 10 of 12 2017 Edition
to prevent the entry of water from the outside into the building to the
satisfaction of the Supervising Officer.

B11.7.6 Pre-fabricated and pre-insulated pipe section shall be used and


provided for long straight run pipes, such as riser pipes, headers and
pipes in plant rooms, etc. as specified in the Particular Specification.

B11.7.7 Unless otherwise indicated, pre-fabrication and pre-insulation shall


include but not limit to pipework, valve, flanges, fittings and all
accessories.

B11.7.8 The pre-insulated pipes shall be delivered to site with 100mm


exposed ends to facilitate field joining. All joints shall be insulated by
the same material using foam injection method on site. All foam-in-
situ (on site foaming) shall be limited to pipe length below 1 meter.
All pipework longer than 1 meter requiring insulation shall be pre-
insulated, no on site foaming is allowed except for pipe joints and
other piping accessories approved by the Supervising Officer. The
insulation shall be applied following the contour of pipework and
adhere tightly and evenly with the pipework surface.

B11.7.9 The A/C Contractor shall follow the approved manufacturers method
statement on installation of pre-insulated pipes and in-situ foaming of
pipe joints. Details shall be submitted to the Supervising Officer for
approval.

B11.7.10 Pre-insulated pipe supplier shall be engaged to provide training by


recognised trainer to the Supervising Officers Representative, project
installers and inspectors to enable them to understand and familiarise
with the installation and to ensure the pre-insulated piping system will
be properly installed.

B11.8 PAINTING AND IDENTIFICATION

B11.8.1 Thermal insulation exposed to view (including that within plant


rooms) shall be painted the colour of which shall be approved or is
acceptable to the Supervising Officer where insulation is protected by
aluminium foil or self-coloured sheet, plastics film or a weather-proof
finish and is in concealed space, painting will not be required.

An undercoat and not less than two finishing coats shall be applied.
Absorbent surfaces shall also receive an initial coat of priming paint.
All paints shall be compatible with the surfaces to which they are
applied.

B11.8.2 Painting shall be carried out generally as detailed in Part G. The


colour(s) of paint(s) shall be to the requirements of Part G and/or the
instructions of the Supervising Officer and shall be selected from the
range contained in BS 4800:2011.

Section B11 AC_GS


Page 11 of 12 2017 Edition
B11.8.3 All distribution services shall be colour coded and provided with
symbols for identification purposes. Identification coding for
ductwork, including thermal insulation, shall be in accordance with
B&ES Standard DW/144:2013. For pipework, including thermal
insulation, the basic colour and colour coding shall be in accordance
with BS 1710:2014.

B11.8.4 Uninsulated pipework or ductwork and thermal insulation which are


painted or unpainted shall be identified by bands at least 25 mm wide
or colour triangles of at least 150 mm side. The bands or triangles
shall be spaced and located to permit ready identification of the
services particularly adjacent to equipment positions and at service
junctions and wall penetrations.

B11.8.5 In addition to colour bands or triangles all pipework and ductwork in


plant rooms and service areas, whether insulated or not, shall be
legibly marked with black or white letters and triangles to show the
type of service and the direction of fluid flow.

Services shall be shown as follows: -

Chilled water CHW


Condensing water CONDW
Hot water HW
Supply air SA
Returned or recirculated air RA
Outdoor air OA
Exhaust air EA

The letters F and R shall be added to piped distribution to show


"flow" and "return" respectively.

Section B11 AC_GS


Page 12 of 12 2017 Edition
SECTION B12

UNITARY AIR-CONDITIONER

B12.1 GENERAL

B12.1.1 Unitary air-conditioners shall include

(a) Single package unit;


(b) Packaged unit and remote condenser;
(c) Condensing unit and blower coils;
(d) Condensing unit with variable refrigerant flow control and
indoor fan coil units;
(e) Multi-split system; and
(f) Water-cooled package and water pump package.

B12.1.2 Unitary air-conditioners shall be factory fabricated and assembled.


The equipment shall be rated and tested in the same country of
manufacture and meet the requirements of the International
Organisation for Standardisation (ISO) Standards 5151:2010 (non-
ducted air-conditioners and heat pumps) or 15042:2010 (multiple split
system air-conditioners and air-to-air heat pumps testing and rating
for performance) or 13253:2011 (ducted air-conditioners and air-to-
air heat pumps) or 13256-1 & -2:1998 (water-to-air and water-to-
water heat pumps) or other internationally recognised quality
assurance standards approved by the Supervising Officer.

B12.1.3 The most energy efficient model in the series shall be selected for
submission and shall be referred to Clause C12.19 of this General
Specification.

B12.1.4 Refrigerants adoption for refrigeration and air-conditioning system in


government building projects shall comply with flammability safety
classification in accordance with Clause B6.1 of this General
Specification.

B12.2 INSTALLATION AND SERVICING

Installation and servicing of unitary air-conditioners shall comply with the


practice set out in the ISO13261-1:1998 &ISO13261-2:1998 and the
manufacturers recommendation.

B12.3 ANTI-VIBRATION MOUNTING

Vibration mounting shall be installed in accordance with relevant clauses of


Section B8.

Section B12 AC_GS


Page 1 of 4 2017 Edition
B12.4 CASING

Removable panel for casings shall be provided to give access to all working
components, parts, and connections for installation and service. The casing of
condensing unit shall be rigid G.I. Sheets and painted in accordance with
relevant clauses of Part G. The compartment housing for the direct-expansion
coil and blower shall be adequately insulated to prevent water condensation and
shall contain a suitable drip pan in accordance with Clause B3.6.8 with a drain
connection. The compartment housing for the compressor shall be treated for
effective sound insulation to ensure that the noise emitted is within the limits as
specified in the Particular Specification.

B12.5 COMPRESSOR

Each compressor shall form a separate refrigerant circuit with its own condenser,
evaporator and controls except multi-split system and VRF.

B12.6 SUPPLY AIR FAN AND MOTOR

All fans shall be statically and dynamically balanced. Fans shall be equipped
with permanently lubricated bearings suitable for the installed altitude of the fan.
Motors shall be installed in accordance with the relevant clauses of Sections B7
& C7.

B12.7 COOLING AND HEATING COILS

Adequate water collecting tray for run off and removal of the condensation shall
be provided. Each coil or circuit shall be controlled by a separate thermal
expansion device.

B12.8 AIR FILTER

Air filters shall be installed in accordance with the relevant clauses of Sections
B1 & C1 for air duct connection unit.

B12.9 AIR-COOLED CONDENSERS

Condenser fan shall be of propeller type arranged for either horizontal or


vertical discharge that shall be specified in the Particular Specification.

B12.10 ELECTRIC DUCTWORK HEATERS

Electric ductwork heaters shall be installed in accordance with Clause C3.2.14.

Section B12 AC_GS


Page 2 of 4 2017 Edition
B12.11 REFRIGERANT PIPING

Refrigerant piping and insulation shall be installed in accordance with relevant


Sections in B6, C6, B11 and C11.

B12.12 CONDENSATE DRAIN PIPE

Condensate drain pipe shall lead to the nearest convenient drain in the building
or as indicated on the Drawings or as directed by the Supervising Officer on Site.

B12.13 MINIMUM INSTALLATION REQUIREMENTS OF SAFETY AND


OPERATIONAL CONTROL FOR UNITARY AIR-CONDITIONERS

Table B12.13 Standard Provision

Associated Unit Cooling Capacity


Components/facilities
Up to 7kW 7kW-14kW over 14kW
1. Self-contained safety Yes Yes Yes
and operational
components of factory
standard
2. Pressure gauges c/w - Yes Yes
stop valves, sight glass
3. Renewable filter-drier - Yes Yes
c/w accessories
4. Externally mounted - Yes Yes
adjustable Hi-Lo
pressure cut out with
hand reset for High side
5. Anti-recycling device Yes Yes Yes
6 Emergency Stop Switch Yes Yes Yes
7. Crankcase Heater - Yes Yes
8 Pump down function - - Yes
and facilities
9. Refrigerant R407C/R410a R407C/R410a R407C/R410a
10. Mechanical and weather Yes Yes Yes
protection to thermal
insulation which
exposed to view

Note: Room coolers are not covered in this table, relevant clauses in General
Specification for Electrical Installation in Government Buildings shall be
referred to.

Section B12 AC_GS


Page 3 of 4 2017 Edition
B12.14 SINGLE PACKAGED AIR-CONDITIONER

The entire single packaged air-conditioner shall be housed in a weather-proof


and galvanised iron sheet metal casing of robust construction yet painted with
attractive appearance.

B12.15 PACKAGED AIR-CONDITIONER WITH REMOTE CONDENSER

The remote condenser shall be air-cooled/water-cooled and installed outside the


building. The interconnecting refrigerant piping shall be field connected.

B12.16 SPLIT CONDENSING UNIT AND AHU

The Split Condensing Unit shall be air-cooled/water-cooled and installed outside


the building. The interconnecting refrigerant piping between condensing unit
and air handling units (AHU) shall be field connected.

B12.17 VARIABLE REFRIGERANT VOLUME SYSTEM

The entire system completed with all necessary piping and accessories shall be
supplied and designed by a single proprietary manufacturer who has proven
record for its product. The A/C Contractor shall submit their calculation to prove
the performance of the equipment with the required length and level difference
for approval.

B12.18 MAINTENANCE SERVICING PLATFORM

Where unitary air-conditioners are installed at levels that are normally


inaccessible from ground, an adequately sized service platform complete with
railings and steel cat ladder with safety wings shall be provided. Such platforms
shall be of reasonable substantial rigid galvanised metal construction and shall
be well protected against corrosion. The design must be approved by the
Supervising Officer before installation.

Under the Labour Department Ordinance, it is required to provide working


platform for activity over 3 metres. This maintenance servicing platform
requirement shall apply to all equipment and installation.

Section B12 AC_GS


Page 4 of 4 2017 Edition
SECTION B13

WATER HANDLING EQUIPMENT

B13.1 GENERAL PUMP INSTALLATION REQUIREMENTS

The installation details should be in accordance with the instruction prepared by


the manufacturer.

Pumps shall be "Type-tested" in accordance with the requirement of BS EN ISO


9906:2012. Test certificates with performance curves shall be submitted to the
Supervising Officer.

Pumps and their drives shall be segregated such that failure of pump seals shall
not result in damage to the drive motors.

B13.2 STORAGE

The equipment should be stored in a dry space when they are delivered to Site.
Special rust preventive measures to protect the internal parts of pumps shall be
applied if the equipment must be stored for an extended period of time. Such
provisions shall be removed completely before final installation and the bearings
should then be re-lubricated.

B13.3 CENTRIFUGAL WATER PUMPS

B13.3.1 Common Installations for Boiler Feed-water, Fresh Water and Saline
Water Pumps

(a) Driving Arrangements

The pump and motor shall be direct coupled and mounted on a


substantial machined bedplate; accurately aligned, and fitted
with guards. The whole assembly including the bedplate shall
be designed and supplied by the pump manufacturer.
Coupling with spacer shall be used for end suction pumps so
that the impeller may be dismantled from the motor side for
servicing without neither disrupting the pipe-work nor
dismounting the motor.

The pump and motor for vertical multi-stage pump for potable
application shall be of close-coupled type.

(b) Stand-By Pumps Arrangement

Where stand-by pumps are specified with automatic


changeover provision, the changeover shall be initiated by
means of flow sensing devices of an approved pattern. The

Section B13 AC_GS


Page 1 of 7 2017 Edition
necessary non-return valves shall be incorporated in the pipe-
work to interconnect such pumps.

B13.3.2 Sump Pumps

The sump pumps shall be of vertical centrifugal design and suitable


for dry sump or wet sump installation. Each pump shall be
constructed with double mechanical shaft seal and close-coupled to a
submersible electric motor.

The sump pumps should operate automatically under level control


with an alarm to alert the operator when high water level is being
exceeded.

Each pump shall be equipped with factory built-in suspension device


and a factory mounted discharge elbow should be provided for wet
sump installation, and cast iron or steel base for dry sump installation
to provide correct pump alignment for wet sump pump installation,
the disconnection shall simply consist of easy removal of each
pumping unit for inspection, repairs and services. The pumps when
lowered into the pits shall automatically be connected to the discharge
piping. There shall be no need for the maintenance or operation
personnel to enter the wet well to carry out the work. Each pump
shall be complete with guide bars, cable supports and lifting chains.

The pump discharge shall be fitted with a resilient seal that provides a
positive hydraulic seal for maximum pump efficiency. Each impeller
shall be trimmed to meet the specified flow requirements.

For installation in flammable zones, each sliding guide bracket shall


have non-sparking material to prevent ignition of explosive wet well
gases.

B13.3.3 Bore Well Pumps

The bore well pumps shall be vertical multi-stage centrifugal


construction that is suitable for submersible bore well installation.
Each pump shall be of a single shaft and non-shaft coupling type in
which a submersible electric motor is coupled at the bottom of the
pump. The pump suction shall complete with a perforated strainer
located between the submersible motor and the first stage impeller
bowl. The pump bearings shall be water lubricated and shall not
cause any contamination to the water handled. The submersible
motor shall be cooled by water moving around the motor casing.

Each pump shall be equipped with an impact non-return valve located


between the pump discharge and rising main to prevent from the flow
back of the water in the rising main. A level switch shall be provided
for the automatic cut-off of the pump as dry running protection when
the water level inside the pit falls below the pump safety suction lift.
The level switch shall be maintenance free mercury type.

Section B13 AC_GS


Page 2 of 7 2017 Edition
The bore well pump shall be installed vertically into the pit. No
foundation shall be required for the pump on the bottom of the pit.
Instead, the pump shall be hung from the pit cover which seals the pit
and absorbs all stress resulting from the weight of the bore well pump,
cable, rising main and water column. The length of each section of
the rising main shall be limited to 3 m long to facilitate the
withdrawal of the pump from the pit for maintenance.

B13.4 PLANT ROOM LOCATION

The A/C Contractor shall check and assure that adequate working space must be
provided to access for maintenance and sufficient headroom to lift the parts for
repairing is provided. For large pumps, a hoist with travelling crane or other
facility shall be provided over the pump location.

For an open loop system, the location of pump should be sited so that it will use
the shortest and most direct suction and smallest vertical lift. Where possible,
the pump centreline should be placed below the level of the liquid in the suction
tank.

The A/C Contractor shall take all precautions against flooding when pumps are
located in pits or other places liable to flooding. The pumps shall be of the
vertical spindle type with the motor mounted above the potential flooding level.
Motor and pump shall form one unit being joined by a common stool. Where
shaft extension is required, the pump shall be driven through a flexible shaft that
consists of a universal joint at each of the drive and driven end and the slip
joined at centre of travel.

B13.5 PUMP FOUNDATION

The foundation for a pump should be of sufficient size and rigidity to properly
support the full area of the base-plate, to absorb any normal strains and to
maintain correct alignment. The minimum mass of inertia block of concrete
shall be not less than 2.5 times the mass of the pump assembly with at least
100 mm thick and 150mm wider than the pump base-plate.

The space between the pump unit and the foundation bolts should be allowed in
accordance with the manufacturers recommendation. Each foundation bolt
should be installed in a pipe sleeve type holder and should be cast before the
concrete foundation is being poured.

Unless otherwise specified, pump base shall be mounted on the raised


housekeeping plinth using appropriate anti-vibration spring mountings. Each
spring shall be individually selected according to load distribution and shall
have an additional free travel equal to one half of the rated deflection. Spring
mounts shall have a levelling bolt and shall be mounted to the concrete inertia
block via height saving brackets that allows a base clearance of 50 mm.

A curb ring or soleplate should be used as a bearing surface for mounting of a


vertical wet-pit pump. The mounting face of the curb ring or soleplate should be

Section B13 AC_GS


Page 3 of 7 2017 Edition
machined for pump alignment. Tie rods should be installed to secure the pump
that is designed to discharge below ground.

B13.6 PUMP ALIGNMENT

The pump unit should be accurately aligned in accordance with the


manufacturers instructions prior to operation. The unit should be supported
over the foundation by strips of steel plate close to the foundation bolts,
allowing a space of 20 to 50 mm between the bottom of the base-plate and the
top of the foundation for grouting. The alignment shall be rechecked after the
suction and discharge piping have been bolted to the pump to test the effect of
piping strains.

The pump and driver alignment should be rechecked and adjusted correct at the
expiry of the Maintenance Period.

B13.7 GROUTING OF PUMP BASE

The base-plate shall be grouted before piping connections are made and pump
alignment is finally rechecked. Grouting by Building Contractor should be
properly done with concrete that shall compose of one part of pure cement and
two parts building sands or be a proprietary non-shrink grout to the acceptance
of the Supervising Officer to prevent lateral shifting of the base-plate. Grout
holes shall be allowed in the base-plate to serve as vents for air escape. The
expose surface of the grout shall be covered with wet burlap to prevent cracking
from drying too rapidly. The pump alignment should be rechecked thoroughly
after the grouting has hardened for a period that should not be less than 72 hours.

B13.8 SUPPORT FOR PIPING

Suction and delivery pipes shall be supported independently of the pump. The
connecting pipes to a pump should not strain the pump. Pipes installation
should match up to the respective flanges without being strained into position.
The faces of the coupling should be checked with a straight edge to make sure
that they are parallel and concentric.

B13.9 CONNECTION PIPING TO PUMP

B13.9.1 Suction Piping

The suction piping shall be properly installed for a satisfactory pump


operation. This shall be achieved by keeping as direct and as short as
practicably possible with a minimum number of bends. The
installations should be laid out such that a continuous fall can be
maintained from the pump to water source to prevent air pockets
forming. Concentric reducers should not be used on suction branch.
The size of the suction pipe shall be larger than the pump inlet and
eccentric reducers shall be used. If the source of supply is located

Section B13 AC_GS


Page 4 of 7 2017 Edition
below the pump centreline, the reducer shall be installed straight side
up. If the source of supply is above the pump, the straight side of the
reducer shall be at the bottom.

A straight section piping at least 4 to 6 diameters long at the pump


inlet and long radius bend shall be used for suction pipeline
installations to create less friction and provide more uniform flow
distribution.

B13.9.2 Delivery Piping

Unless otherwise specified, the size of the delivery pipe shall be at


least one size larger than the pump delivery and the velocity shall be
kept around 2 metre per second for pumping water over long distance.
The check valve shall be installed between the pump and the gate
valve. The gate valve should be installed close to the pump discharge
for pump priming and repairing. Provision such as a sprocket rim
wheel and chain shall be provided for manually operated valves that
are difficult to access.

Air release valves shall be installed at the highest points on each rise
to allow accumulated air or vapour or other gases to escape from the
pipe.

A 'Y' type branch connection shall be used for distribution of more


than one-discharge points.

A taper piece with the included angle between 10-13 degrees shall be
used for reduction of pipe diameter.

Adequate support and anchorage shall be provided if the pipes are


laid above or below ground. For this purpose, it is acceptable to have
thrust blocks in either corner type or puddle flange type that are
designed to absorb reactions or turning forces to ensure no
mechanical and hydraulic forces imposed on the pump.

B13.9.3 Pipe Flanges

Pipe flanges should match with the sizes of pump flanges with full-
face gaskets.

B13.9.4 Expansion Joints

Expansion joints shall be installed in suction and delivery pipelines to


avoid transmitting any piping strains caused by expansion when
handling hot liquid. A suitable pipe anchor shall be installed between
the expansion joint and the pump.

If expansion joints are not specified, expansion loops that are formed
by looping the pipe shall be provided to prevent the transmission of
strains to the pump.

Section B13 AC_GS


Page 5 of 7 2017 Edition
B13.9.5 Intake

The installation work should be carried out properly to prevent air


being entrained as bubble within the water. The intake pipe shall run
well below the sump tank level to prevent from forming air gulps.

High level entry into the sump should be avoided as air may be
entrained by the falling jet.

Vortex inhibitor shall be installed to prevent air being drawn from


bottom of vortex into the intake.

B13.10 SUCTION STRAINERS

The suction strainer shall be installed as close as practicably possible to the


pump. This suction pipe strainer should not be used for flushing the pipe. A
temporary strainer fitted with a finer mesh than the permanent strainer should be
used for flushing all piping and cleaning thoroughly all possible mill scale and
other foreign matter. The temporary strainer shall be removed afterwards.

B13.11 VENTING VALVES FOR PUMP-SET

Venting valves shall be installed at one or more points of the pump-casing


waterway to provide a means to escape for air or vapor trapped in the casing.
These valves shall be connected so as not to endanger the operation staff in
handling toxic, inflammable or corrosive liquid.

B13.12 DRAINS FOR PUMP-SET

All drain and drip connections shall be piped to a point where the leakage can be
disposed of or collected for reuse if specified.

B13.13 INSTRUMENTATION

Each pump installation shall include pressure gauges and a gas cock to measure
the system pressures and pressure drop.

All measuring and isolation instruments, such as the pressure gauges, check
valves, globe valves, gate valves and strainers, etc., or as specified in the
Particular Specification shall be installed properly to maintain a close check on
control on the performance and condition of the pumps.

Instruments shall be mounted in a suitable location so that they can be easily


observed.

B13.14 FEED AND EXPANSION TANK

The tank shall be provided and installed on the roof or other location as
specified, on a stand if necessary, to suit the NPSH of the pump being selected.
Section B13 AC_GS
Page 6 of 7 2017 Edition
The tank shall be complete with ball float valve, valve, overflow, drain facilities
and quickly fill valve, etc. In addition, hinged access door with gasket and
rotating hinged bolt-securing device shall also be provided.

Overflow pipe shall be at least TWICE the diameter of the inlet pipe or 32 mm
whichever the greater and shall discharge to a conspicuous location outside the
building.

Connections to a mild steel tank shall be made by means of bossed, screwed


flanges or pads and studs and should be welded before galvanising. Openings
for connections to steel tank of other material may be made on site complete
with back nuts and plastics that are compatible with the liquid being handled.

Unless otherwise specified, the installation shall include the final connection of
the main cold water supply to the ball float valve from a valve point.

B13.15 WATER FILTERS

Unless otherwise specified, water filters shall be provided for the Installations
with details as follows: -

B13.15.1 Suitable and approved coarse and fine filters shall be fitted on all non-
re-circulating cooling or flushing water supply water system e.g. sea
water system.

B13.15.2 For re-circulating systems of the water tower type, fine filters and
sludge traps shall be provided.

B13.15.3 For close re-circulating system, filters need only be provided for the
"make-up" water if it is drawn from the well or stream water and
likely to be contaminated with sediment.

B13.15.4 For the installation of a seawater pump house, in addition to the


intake coarse filter, the strainer or the motorised travelling band
screen in the plant room shall be an automatic self-cleaning and
approved type. The strainers or the motorised travelling band screen
in the plant room shall comprise a motorised continuously rotating
inner drum, and have an automatic backwash arrangement. Proper
drainage facility should be provided by the builder.

B13.16 PLATE TYPE HEAT EXCHANGER

The installation shall be in accordance with the manufacturers


recommendations and shall be easily accessed for maintenance and repair.

B13.17 SEA WATER STRAINER

The installation shall be in accordance with the manufacturers


recommendations and shall be easily accessed for maintenance and repair.

Section B13 AC_GS


Page 7 of 7 2017 Edition
PART C - GENERAL TECHNICAL REQUIREMENTS
(MATERIAL AND EQUIPMENT SPECIFICATION)
SECTION C1

AIR CLEANING EQUIPMENT

C1.1 GENERAL

Filters shall be of proprietary product and have the specified performance and fire
property in accordance with the test methods of one or more of the standards
stated hereinafter.

For filters used in corrosion resistant ductwork, the associated housing, holding
frames, enclosures and all metal surfaces in contact with the air stream shall be
applied with the same coating as the ductwork. Accessories, of which the
operation will be affected by corrosive, shall be of AISI 316 stainless steel with
the coating omitted.

Unless otherwise stated, the design air velocity at the face of filters shall not
exceed 2.5 m/s. Product test reports for the listed efficiency including all details
as prescribed in the testing methods of one or more of the standards shall be
provided.

To improve indoor air quality and protect air conditioning equipment, outdoor air
and re-circulated indoor air shall be filtered to remove dust, bacteria, pollens,
insects, soot and dirt particles before it enters the air conditioning system. The
following air cleaning devices, dependent on their compatibility with the general
air conditioning system, shall be incorporated into the system as in-duct devices
or stand-alone devices.

C1.1.1 Particulate Filter

Particulate filters are the most commonly used air cleaning devices in
buildings. They are classified into two general categories, pre-filters
and final filters, according to the size of the particulate, which they
catch and the energy required to circulate air through them. One or a
combination of the filters shall be selected depending on the physical
characteristics and levels of the dust to be removed, the capacity of
the system to overcome the associated pressure drop across the filter
and the degree of indoor air cleanliness required :-
Table C1.1.1 (1) Types of Filters
Stage Nature Filter Type
Pre-filters Washable Washable Panel Filters
Automatic Viscous Filters
Disposable Disposable Panel Filters
Disposable Pleated Panel Filters
Renewable Renewable Panel Filters
Automatic Fabric Roll Filters
Section C1 AC_GS
Page 1 of 24 2017 Edition
Final Disposable Bag Filters
Filters Cartridge Filters
High Efficiency Particulate Arrestance
(HEPA) Filters
Renewable Automatic Reclean able Filters
Automatic Reclean able HEPA Filters

The filters shall be cleaned or replaced on a regular basis according to


the manufacturers recommendations or when the specified maximum
pressure drop is reached. To prolong service life, two stages of
filtration with the minimum efficiency reporting value (MERV) by
ANSI/ASHRAE Standard 52.2-2012 as shown in Table C1.1.1-(2)
are recommended for buildings designed with a central air handling
system to prevent premature clogging and frequent replacement of the
high efficiency filter: -

Table C1.1.1 (2) Filter Efficiency

Conditions Pre-filters Final filters


General occupied areas Required MERV 11 - 12
Heavy dirt loading areas Required MERV 13
Sensitive areas Required MERV 14

For critical clean air requirements, such as health care facilities, three
filtration stages may be employed with High Efficiency Particulate
Arrestance (HEPA) Filter as the third stage.

C1.1.2 Electrostatic Filter

For conditions where low pressure drop, energy saving and minimum
servicing are concerned, electrostatic filters shall be used which can
also deal with odour of low concentration level.

C1.1.3 Gas Filter

Gas filters are designed to remove gaseous pollutants from the air.
Solid sorbents including activated carbons, molecular sieves, silica
gel and activated alumina, each of which has a different adsorbing
characteristic, shall be used to remove various gaseous pollutants.

C1.2 STANDARDS

C1.2.1 Performance of Air Filter

The performance of air filters shall comply with one or more of the
following standards: -

Section C1 AC_GS
Page 2 of 24 2017 Edition
(a) ANSI/ASHRAE Standard 52.2-2012 Method of Testing
General Ventilation Air Cleaning Device for Removal
Efficiency by Particle Size;

(b) Underwriters Laboratories UL 586:2009 High Efficiency,


Particulate, Air Filter Units;

(c) European Standard BS EN-13779:2007 - Particulate Air


Filters for General Ventilation;

(d) European Standard BS EN1822-1:2009 to BS EN 1822-3:2009


and BS EN 1822-4:2009 to BS EN 1822-5:2009 High
Efficiency Air Filters (EPA, HEPA and ULPA); or

(e) Any other standards equivalent to the standards above and


approved by the Supervising Officer to suit particular project
requirements.

C1.2.2 Fire Property of Air Filter

The fire property of air filters and its associated accessories shall
comply with one of the following standards as well as the
requirements of the FSD: -

(a) British Standard Institution BS 476-4:1970 - Non-


Combustibility Test for Materials;

(b) British Standard Institution BS 476-6:1989+A1:2009 - Fire


tests on building materials and structures. Method of Test for
Fire Propagation for Products, with Indices "I" 12 and "i1"
6;

(c) Underwriters Laboratories UL 900:2004 - Standard for Air


Filter Units, Class 1 or Class 2; or

(d) European Standard DIN 53438-3:1984 - Response to Ignition


by A Small Flame, Surface Ignition, Class F1.

C1.3 WASHABLE PANEL FILTER

This type of filter shall be constructed of aluminium to withstand washing by


water or steam. The filter panel shall be constructed from multiple layers of
expanded aluminium mesh or glass, natural or synthetic fibre, with the layers
being corrugated or plain and arranged alternately at right angle at one another.
Filter media shall be supported on both sides with a rigid and thicker aluminium
expanded metal mesh.

Filters shall be 50, 25 or 12.5 mm thick with a rolled or extruded aluminium


frame. The frame section shall be ribbed for stiffness and its inner edges treated
to prevent sharpness and increase strength. Corners shall be mitred and riveted
where it is necessary. Folding handles shall be applied to the short side of all

Section C1 AC_GS
Page 3 of 24 2017 Edition
washable filter panels for easy removal and cleaning. The filter support frame
shall be suitable for the installation of either side.

It shall have the minimum efficiency reporting value (MERV) by


ANSI/ASHRAE Standard 52.2-2012 and initial resistance at 2.5 m/s face
velocity as shown in Table C1.3-(1) below, unless otherwise specified in the
Particular Specification. The filter shall operate to a final resistance of 150, 100
or 75 Pa for 50, 25 or 12.5 mm thick panels respectively.

Table C1.3 - (1) MERV and Initial resistance of washable panel filter

Thickness MERV Not Less Than Initial Resistance Not Exceeding


50 mm 5 50 Pa
25 mm 4 30 Pa
12.5 mm 3 25 Pa

Where coated filtration media is specified, each layer of expanded aluminium


shall be furnished with a thixotropic flame resistant filter coating before
assembly into a pack. The adhesive shall have a flash point exceeding 180 oC
Performance data for expanded aluminium filter panels oiled with a thixotropic
adhesive shall have the minimum efficiency reporting value by ANSI/ASHRAE
Standard 52.2-2012 and initial resistance at 2.5 m/s face velocity as shown in
Table C1.3-(2) below, unless otherwise specified in the Particular Specification.
The filter shall operate to a final resistance of 150, 100 or 75 Pa for 50, 25 or
12.5 mm thick panels respectively.

Table C1.3 (2) MERV and Initial resistance of coated washable panel filters

Thickness MERV Not Less Than Initial Resistance Not Exceeding


50 mm 6 55 Pa
25 mm 5 35 Pa
12.5 mm 4 30 Pa

C1.4 AUTOMATIC VISCOUS FILTER

The filter shall comprise a frame or enclosure, filter plates, motor, drive and
fluid tank. There shall be access to the tank containing the fluid to facilitate
maintenance and the tools and containers required for the removal of sludge
shall also be provided. It shall have the minimum efficiency reporting value not
less than 7 by ANSI/ASHRAE Standard 52.2-2012, unless otherwise specified
in the Particular Specification. The design air velocity at the face of the filter
shall not exceed 2.5 m/s and operating resistance shall not exceed 125 Pa at the
design air volume flow rate. To ensure that there is no carry-over of fluid from
freshly wetted surfaces the rate of drive shall be suitably adjusted and set or
otherwise the filter shall incorporate shielding devices.

Section C1 AC_GS
Page 4 of 24 2017 Edition
C1.5 DISPOSABLE PANEL FILTER

The filter shall be of glass or synthetic fibres media panel type. It shall have the
minimum efficiency reporting value not less than 6 by ANSI/ASHRAE
Standard 52.2-2012 and initial resistance not exceeding 75 Pa at 2.5 m/s face
velocity, unless otherwise specified in the Particular Specification. The filter
shall operate to 250 Pa final resistance.

The glass or synthetic filter media shall be supported between two media
retainers inside a reinforced cardboard retaining frame. The media retainers
shall be suitably designed and fabricated to provide adequate support, such as
combined metal mesh and grilles, throughout its whole working life, the filter
element shall be bonded together with a cured resin, with a light adhesive
coating, and suitably treated such that the filter media are not affected by air
moisture, vermin proof and resistant to fungal growth.

C1.6 DISPOSABLE PLEATED PANEL FILTER

The extended surface pleated filter shall be of similar design for disposal panel
filter but it shall be used when higher air cleaning efficiency and higher air flow
rate are required. It shall have the minimum efficiency reporting value not less
than 7 by ANSI/ASHRAE Standard 52.2-2012 and initial resistance not
exceeding 75 Pa at 2.5 m/s face velocity, unless otherwise specified in the
Particular Specification. The filter shall operate to 250 Pa final resistance. The
pleated media shall be bonded to the expanded wire mesh to maintain its high
efficiency and constant air flow rate.

C1.7 RENEWABLE PANEL FILTER

It shall be used for heavy dust loading condition when the maintenance cost is
the main decision factor. The filter media shall be of glass or synthetic fibre
with a thickness of 50 mm unless otherwise specified. The filter media shall be
replaceable and held in position in permanent wire basket, which shall be
designed for easy filter element replacement. It shall have the minimum
efficiency reporting value not less than 6 by ANSI/ASHRAE Standard 52.2-
2012 and initial resistance not exceeding 75 Pa at 2.5 m/s face velocity, unless
otherwise specified in the Particular Specification. The filter shall operate to
250 Pa final resistance.

C1.8 AUTOMATIC FABRIC ROLL FILTER

The filter shall comprise the complete assembly of filter frame, motor, drive,
filter blockage sensor and filter media. All sheet metal parts shall be of
corrosion resistant galvanised steel construction. The filter media, supplied in
roll form and 50 mm in thickness, shall be automatically across the face of the
filter, while the used dirty media shall be rewound onto a roll drum at the other
end. Each media roll shall not be less than 20 m long for sufficient service life
before replacement is required. The filter shall operate automatically to
maintain the design operating resistance of the filter media and the required

Section C1 AC_GS
Page 5 of 24 2017 Edition
operating efficiency. The filter shall advance the filter media automatically on
the command from a pressure switch, timer, or light-transmission control device.
The control circuit must operate to ensure uniform feeding of the filter media for
constant dirt condition and loading. It shall not require re-calibration if the
actual working condition differs from design or if the system is of variable air
volume type. Visual or audible warning to notify filter media replacement shall
be provided. The driving motor shall be automatically switched off when the
filter media end is reached and a filter stop alarm shall be generated to alert
maintenance personnel for filter replacement. The controls shall be factory
wired and arranged to insure fail safe operation. The filter shall be designed and
constructed to enable continuous operation during routine servicing and
maintenance of the filter. The filter media shall be provided with an effective
seal to minimise air bypass. A spare roll of filter media shall be provided for
each unit.

The initial resistance of the filter shall not exceed 45 Pa and a mean of 85 Pa
under designed operating conditions. The air velocity through the filter media
shall not exceed 2.5 m/s. It shall have the minimum efficiency reporting value
not less than 6 by ANSI/ASHRAE Standard 52.2-2012, unless otherwise
specified in the Particular Specification.

C1.9 BAG FILTER

The air filter shall be of high efficiency, extended area, deep pleated, disposable
type. The media shall be of microfine glass fibre and reinforced by a laminated
synthetic backing. It shall have a nominal thickness of 600 mm and the
minimum efficiency reporting value shall not less than 13 by ANSI/ASHRAE
Standard 52.2-2012 and initial resistance not exceeding 100 Pa at 2.5 m/s face
velocity, unless otherwise specified in the Particular Specification. The air filter
shall be designed for air velocity of 1.0 to 3.5 m/s and shall operate to 250 Pa
final resistance.

The filter package shall be factory assembled as a complete set readily for site
installation. The filter assembly shall consist of a holding frame, sealer frame,
media retainer, and the disposable element.

The sealer frame shall be constructed of galvanised steel of sufficient thickness


and equipped with suitable airtight sealing gasket and sealing mechanism on the
sealer frame flange. The media retainer shall be designed to match the filter
elements to provide sufficient support for the multiple pleats of the filter element
against the direction of the airflow. The media retainer shall be suitably coated
and designed to totally eliminate the possibility of oscillation and sagging. The
bag or packer shall inflate fully, shall not sag or flutter or be obstructed by contact
with other filter faces or ductwork surfaces when operating between 60 - 110% of
design air volume flow rate for constant volume system.

C1.10 CARTRIDGE FILTER

This type of filter shall work reliably in the range of medium and high cleaning
efficiency. It shall have the minimum efficiency reporting value not less than 13

Section C1 AC_GS
Page 6 of 24 2017 Edition
by ANSI/ASHRAE Standard 52.2-2012 and initial resistance not exceeding 100
Pa at 2.5 m/s face velocity, unless otherwise specified in the Particular
Specification. The filter shall operate to 250 Pa final resistance and shall consist
of water-resistant media of ultra-fine glass fibres. The media shall be pleated
and have suitable separators to maintain the uniform spacing between pleats.
The filter assembly shall be of rigid cartridge design, which shall consist of a
steel header and cell box to form a supported pleat media pack for various
difficult operating conditions. The filter set shall be, unless otherwise specified,
of 300 mm nominal thickness disposable extended surface cartridge type. The
media shall be water resistant and shall be made of ultra-fine glass fibres formed
into thin mate, which shall be supported by suitable corrugated separators and
sturdy enough to operate in a VAV system. The filter panel shall be constructed
of galvanised steel sheet folded and reverted to form a rigid frame.

C1.11 HIGH EFFICIENCY PARTICULATE ARRESTANCE (HEPA) FILTER

The HEPA filter shall have minimum efficiency of 99.97% in removing small
particles of sizes larger than 0.3 micrometre from air by Underwriters
Laboratories UL 586:2009. This makes use of a high efficiency glass paper
medium and great surface area of medium per cross-sectional area of the filter.
It shall reach this rated efficiency when the velocity of the air passing through
the media is 2.5 m/s. Unless otherwise specified in the Particular Specification, a
normal HEPA filter of a size 600 mm square with 300 mm thickness, shall have
a rated flow of 0.75 m3/s, at a pressure drop not exceeding 250 Pa, and about
23 m2 of filtering media surface area. The filter shall operate to 600 Pa final
resistance.

Filter shall be constructed with the media pack folded over separators to form
closely spaced pleats, the whole being sealed into a casing with hard setting
synthetic resin cement. This shall enable slower media velocity and increased
efficiency. The media of space filter paper produced wholly from glass micro
fibres, shall be inert, non-hygroscopic, vermin proof and shall not support
bacteria growth. The filter media shall be treated with organic binder materials
to provide binder, fungicidal and waterproofing properties.

For clean rooms and clean zones, the HEPA filter shall be selected to meet class
5 of air cleanliness by ISO Standard 14644-1:1999 Clean rooms and
Associated Controlled Environment-Classification of Air Cleanliness, unless
otherwise specified in the Particular Specification.

C1.12 AUTOMATIC RECLEANABLE FILTER

The filter system shall include filter media, air compressor unit, air jet nozzles,
controller, automatic dust collection unit, etc.

Filter media shall be made of reinforced fibre-glass or other suitable synthetic


medium mounted on a rotary tube or a fixed drum. When the pre-set differential
pressure between dirty and clean airsides of the filter is exceeded, the cleaning
operation shall be initiated. For the rotary tube design, the carrier tube shall
rotate and suction nozzle with vibrator motor shall move along the filtering

Section C1 AC_GS
Page 7 of 24 2017 Edition
surfaces. For the fixed drum design, an air valve installed at the downstream of
the filter shall induce compressed air pulse-jets opposite to normal air flow
direction. As a result, dirt particles will be pulsed away from the filter and
collected in concentrated form inside a collection chamber, or an external
vacuum cleaner, or a central vacuum cleaning system connected outside the
filter chamber.

Cleaning shall be carried out both during downtimes of the air-


conditioning/ventilation system and during plant operation. It shall have the
minimum efficiency reporting value not less than 14 by ANSI/ASHRAE
Standard 52.2-2012. The initial resistance across the whole unit shall not
exceed 250 Pa at design air flow volume rate and the final resistance shall not be
more than 500 Pa, unless otherwise specified in the Particular Specification.

The internal surfaces of the filter set shall be absolutely smooth and the bottom
shall be in trough form with drain so that water can be drained away in case of
wet cleaning.

The construction of the service door shall be identical to the casing panel. Non-
aging steel-inlaid labyrinth seal shall be integrated into the door leaf. Each door
shall be fitted with at least two double lever locks with bolts. Safety cams or
chains shall be provided for pressure side doors. All the surfaces of the casing
shall be protected against atmospheric corrosion by plastic powder coating.

The whole cleaning cycle shall be activated and controlled by a sequence


controller with the following basic operations: -

(a) Reverse blowing by air pulses;

(b) Allow a few minutes time interval for the dust and other contaminant
particles to settle at the collector trap;

(c) Operation of the vacuum cleaner/central vacuum cleaning system for a


few minutes; and

(d) Actuate alarm for disposal of the contaminant particles when the
collecting bag is 80% full.
The filter media shall be selected to suit wet conditions such as market areas and
poultry areas.

The controller shall be provided with two operation modes, "Auto" and
"Manual". Under the "Auto" mode, the filter media shall be auto-cleaned by the
compressor air from the air jet nozzles whenever the pressure difference across
the filter media is in excess of the pre-set value. The filter system shall be
arranged to connect to CCMS system and operated in accordance with a time
schedule which can be set from the CCMS.

An automatic dust collection unit shall be provided to collect dust inside the
filter section after each auto cleaning operation.

All of the operation status and fault signals shall be monitored by the CCMS.

Section C1 AC_GS
Page 8 of 24 2017 Edition
The air compressor shall be tested and certified by the accredited laboratory in
accordance with relevant statutory requirements.

C1.13 AUTOMATIC RECLEANABLE HEPA FILTER

The whole unit shall be of heavy duty proprietary made air-tight construction. It
shall be coated with polyester powder to protect from atmospheric corrosion and
to minimise internal friction. By modular construction, each filter chamber of
the unit shall be able to be isolated from the air stream without affecting the
operation of the unit while cleaning or replacing the filter cartridges within a
particular filter chamber. The filter cartridge shall be designed as drawers by
sliding in or pulling out for replacement and repairing services from the front
panel and entirely from the clean air side. There shall be no contamination on
the filter unit and the environment during the replacement. At the bottom, dust
collection containers shall be mounted to each filter chamber by clamps via
inter-connecting funnel sections.

Automatic cleaning is conducted by using a counter-current compressed air


purge sequence. Filter shall be cleaned periodically by compressed air, which is
blown in counter-flow direction to the filter cells from nozzles actuated by
pneumatic system from the clean air side. A digital measuring and indication
device shall be provided to show the differential pressure of all filter cells in one
filter chamber.

The controller shall provide two operation modes, "Auto" and "Manual". Under
the "Auto" mode, the filter media shall be auto cleaned by the compressor air
from the air jet nozzles whenever the pressure difference across the filter media
is in excess of the pre-set value. The filter system shall be arranged to connect
to CCMS system and operated in accordance with a time schedule which can be
set from the CCMS.

An automatic dust collection unit shall be provided to collect dust inside the
filter section after each auto cleaning operation.

All of the operation status and fault signals shall be monitored by the CCMS.

The air compressor shall be tested and certified by the accredited laboratory in
accordance with relevant statutory requirements.

Filter media shall be made of reinforced fibre-glass or other suitable synthetic


medium with minimum efficiency of 99.97% in removing small particles of
sizes larger than 0.3 micrometre from air by Underwriters Laboratories UL
586:2009. It shall reach the rated efficiency when the velocity of the air passing
through the media is 2.5 m/s. For a nominal HEPA filter of a size 600 mm
square with 300 mm thickness, it shall have a rated flow of 0.75 m3/s and about
23 m2 of filtering media.

The initial resistance across the whole unit shall not exceed 1500 Pa at design
air flow volume rate and the final resistance shall not be more than 2400 Pa,
unless otherwise specified in the Particular Specification.

Section C1 AC_GS
Page 9 of 24 2017 Edition
C1.14 AUTOMATIC RECLEANABLE HIGH VOLTAGE ELECTROSTATIC
FILTER

The automatic reclean able high voltage electrostatic filter shall be able to
control odours in the conditioned space and reduce the permanent deposition of
contaminants in the space served. It shall have the minimum efficiency reporting
value not less than MERV 14 by ANSI/ASHRAE Standard 52.2-2012 and an
initial resistance not exceeding 120 Pa at design air flow volume rate, unless
otherwise specified in the Particular Specification. The whole unit shall be
tested to meet Underwriters Laboratories UL867:2011 - Electrostatic Air
Cleaners and of a type approved by the Director of Fire Services. It shall not be
used in hazardous locations or for handling hazardous gases/mixtures.

For kitchen applications, it shall comply with the requirements of the


Environmental Protection Department on the treatment of gas fired kitchen
exhaust air and the unit shall be leakage proof to avoid oil dripping. It shall have
oil mist removal efficiency not less than 90%, odour removal efficiency not less
than 50% and an initial resistance not exceeding 120 Pa at design air flow
volume rate, unless otherwise specified in the Particular Specification. Oil mist
removal performance shall be verified by recognised testing laboratory. The
whole unit shall be tested to meet Underwriters Laboratories UL710:2012 -
Exhaust Hoods for Commercial Cooking Equipment (for Fire and Burnout Test
only). Filter performance shall be tested according to ANSI/ASHRAE Standard
52.2-2012 and equipment shall be tested to meet Underwriters Laboratories
UL867:2011 - Electrostatic Air Cleaners.

The unit shall consist of an ioniser-collector section power generator, an


aluminium washable panel filters section against over-spray and a washer and
adhesive applicator section. All parts shall be factory assembled into a
sectioned housing having an overall depth not greater than 1000 mm in direction
of airflow. Each section of the galvanised steel housing assembly shall
incorporate a pair of hinged, quick opening access doors permitting access for
servicing of all internal components; and a watertight, all welded, galvanised
steel, drain pan having drain connections. Access doors shall be sealed against
leakage by continuous perimeter gaskets of closed cell neoprene.

C1.14.1 Each ioniser-collector section shall be furnished with the required


number of one-piece or multi-piece cells of all aluminium
construction. Each cell shall be fitted with stainless steel slides for
mounting on the tracks, which form an integral component of the side
access housing and to facilitate removal of cells for servicing. Cell
support framework shall be completely open beneath the ioniser-
collector cells to ensure complete drainage of wash water and excess
adhesive, minimising the possibility of short circuits when high
voltage power is restored following completion of the wash cycle.
Cells shall be designed so that high voltage input terminals and their
high volt rated insulators are located completely out of contact with
the moving air-stream to avoid build-up of dirt which could permit
dissipation of high voltage charge and reduce air cleaning efficiency.
The high voltage bus bars and contactors shall be inherent to the
design of each cell and shall permit cell removal without

Section C1 AC_GS
Page 10 of 24 2017 Edition
disconnecting any high voltage wiring. Insulators shall be fully
exposed, for ease of cleaning, when cells are removed for service.
Cells shall be designed for full-face ionisation and shall have
completely flat collector plates to prevent build-up of residual,
inaccessible dirt accumulations.

C1.14.2 Dual voltage power packs which are designed to provide high voltage
to the ioniser circuit and to the plate circuit respectively shall be
connected to each ioniser-collector section. The power packs shall be
of solid state design to include "fail-safe" low voltage relays to
interrupt power to the ioniser circuit in the event of a malfunction in
the plate circuit. High voltage connections between the high voltage
output terminals and the bus bar terminals mounted on the
ioniser-collector section access door shall be adequately installed.
Each power pack covers shall include a circuit breaker, a manual reset
button and / or automatic reset. Safety type door interlock switches,
with suitable length of safety chain and wiring in series circuit for the
power pack, shall be furnished to cut-off the power supply whenever
the door is opened.

C1.14.3 Each washer and adhesive applicator section shall incorporate slide-in
type, perforated, galvanised steel air distribution baffles and a swing
or fixed header assembly. The header assembly shall be connected to
the inlet water solenoid valve and to the adhesive pump. Washer
arms shall be equipped with 360ofixed washer spray nozzles against
reactive force to the high inlet water pressure. The removable brass
adhesive nozzles shall be mounted on a separate, fixed, vertical
header forming an integral component of the assembly. The filter
adhesive shall be cold water soluble and non-flammable. A rotary
gear adhesive pump with bronze impeller and sufficient adhesive for
at least four reconditioning cycles shall be furnished.

C1.14.4 The washer supply water solenoid valve, manifold drive motor,
manifold limit switch and adhesive pump shall be pre-wired to an
accessible, internally mounted terminal box. The washer control
panel shall incorporate a status light to indicate when the
reconditioning cycle is energised and the reconditioning cycle is in
operation. The complete automatic cleaning by reversing the polarity
of the filter element, wet washing by water spray and adhesive
application shall be initiated manually or automatically through a
push button actuated, internally fused, all solid state and program
timer control. The controller shall be provided with two operation
modes, "Auto" and "Manual". Under the "Auto" mode, the
electrostatic filter shall be automatically cleaned on the timer of pre-
set value and cleaning operations shall not be energised when the
exhaust fan is in running status. The filter system shall be arranged to
connect to CCMS and operated in accordance with a time schedule
set from the CCMS.

All of the operation status and fault signals shall be monitored by the
CCMS.

Section C1 AC_GS
Page 11 of 24 2017 Edition
C1.15 GAS FILTER

The gas filters shall remove gas pollutants from the air by absorption or
adsorption. It shall comprise a robust enclosure inserted with module banks
which contain evenly disposed chemical media. The complete unit is to be
factory assembled and manufactured by the same manufacturer. All joints
between the robust enclosure and the module banks shall be effectively sealed to
eliminate air bypass and to ensure the optimum removal efficiency. Their
supports shall be constructed from steel protected against corrosion and
designed to provide mechanical protection to the module banks. The chemical
media shall be of uniform thickness packed to ensure that compacting does not
occur in use.

The chemical media shall consist of solid sorbents including activated carbons
for common volatile organic compounds in indoor air and activated alumina
suitably impregnated with potassium permanganate for formaldehyde and other
gaseous contaminants. The combined media shall be able to operate normally at
temperatures 0 oC to 45 oC and relative humidity 10 to 95%. It shall be
inorganic, non-toxic, non-flammable and shall not support bacterial or fungal
growth.

The gas filters shall be selected to give the removal efficiency not less than the
following value and an initial resistance not exceeding 140 Pa at 2.5 m/s face
velocity, unless otherwise specified in the Particular Specification: -

With 0.0283 cubic metre of media per and 0.472 cubic metre per second of air,
media shall have a scrubbing efficiency of not less than 99.95% at 0.5 ppm
hydrogen sulphide or ammonia inlet challenge concentration for a period of
3600 hours.

Impregnated alumina media shall meet the following removal capacities: -

Hydrogen Sulphide - 8% min. by weight


Sulphur Dioxide - 3.5% min. by weight
Nitric Dioxide - 2.5% min. by weight
Nitrogen Dioxide - 1.0% min. by weight

Impregnated carbon media shall meet the below removal capacity: -

Ammonia Gas - 5% min. by weight

Media in the modules shall be manufactured from a combination of activated


alumina impregnated with 4% potassium permanganate by weight in such a
manner that the impregnate is available for reaction. The media shall be
inorganic, non-toxic, non-flammable and shall not support bacterial or fungal
growth.

Laboratory analysis report on media samples to establish life cycles and


remaining life shall be submitted to the Supervising Officer for approval.

Section C1 AC_GS
Page 12 of 24 2017 Edition
C1.16 ACTIVATED OXYGEN AIR PURIFIER

The air purifier shall be capable of reducing odours of bacterial, organic and
chemical origin and shall also be capable of reducing airborne bacteria and
particulates in the treated areas.

All components of the air purifier, which are within the air stream, shall comply
with the requirement of the Fire Service Department. The air purifier shall
conform to BS EN 61000-6-1:2007, BS EN 61000-6-2:2005, BS EN 61000-6-
3:2007+A1:2011 and BS EN 61000-6-4:2007+A1:2011 or similar international
standards on Electro-Magnetic Compatibility (EMC) compliance.

The air purifier shall have removal efficiency of not less than 95% of Total
Bacteria Count (TBC) Test, 95% of airborne particulates of 0.5 micron to 2.0
micron, 95% of cigarette smoke particles, 80% of odours, and 95% of hydrogen
sulphide, unless otherwise specified in the Particular Specification. Independent
laboratory test reports and certificates to show the removal efficiency of the unit
shall be submitted to the Supervising Officer for approval.

The air purifier shall not generate ozone in the treated areas in excess of the
safety standards as specified by the Occupational Safety and Hygienic
Association (OSHA), USA or other recognised international standards. A proper
control device to shut off part or the whole unit is required when excessive
ozone is detected over the limit of OSHA. A site test shall be carried out to
verify that the ozone level in the occupied zone does not exceed the specified
level.

The air purifier shall be suitable for ductwork mounting and shall consist of a
power generator and screw-in or snap-on electrodes. The power generator shall
be able to operate at 220 V 50 Hz single phase supply, equipped with on/off
switch, on/off indicator lamps, over load circuit breaker (fuses) and electrode
tube sockets. Indication lamp for individual ionisation tube shall be provided.
The side in contact to air stream of the power generator housing shall be
insulated by double skin panel with proper means of thermal insulation in order
to prevent condensation.

There shall be a minimum of 1 transformer for every 2 tubes. The output of the
transformer shall be at 2800V whenever ionisation is being called for.
For air purifier installed in the exhaust air plenum, the plenum shall be of min.
300 mm length after the exhaust fan and using a stainless steel mounting flange
provided by the manufacturer. It shall be interlocked with the respective
ventilation fan so that it switches on/off with the air handling unit or ventilation
fan.

Energy of each electrode tube shall be good enough for ionising 0.045 litre/s/W
oxygen.

The electrode tubes shall consist of screw-in base and a glass tube. The
electrode tube shall be covered with a stainless steel mesh and shall be
electrically earthed by means of an earth clip or an earth screw securely

Section C1 AC_GS
Page 13 of 24 2017 Edition
connected to the power generator. The required number of electrode tubes shall
be in accordance with the manufacturers recommendation.

A control unit shall be supplied to guarantee stable and situation referred


ionisation process without generating excessive ozone for this application.
Ozone monitoring device shall be provided. The unit shall be able to control
several purifiers by either Auto or Manual mode.

Under Auto mode, the control unit shall moderate the output intensity of the
purifiers in accordance with the information concerning adaptation, total power
consumption, air flow, relative humidity, VOC concentration and also ozone
level for human safety. Adaptation values are depending on the application.
Control signals shall be provided by relevant duct mounted sensors. Ionisation
intensity can be moderated in the range of 0 to 99% in steps of 1%.

The control unit shall be able to switch off the air purifier when the air flow is
below the pre-set value in the control unit in order to prevent the accumulation
of ozone inside the system.

The control unit shall be able to reduce 50% and 10% intensity of the computed
value when the ozone level of supply air is exceeded 30 ppb and 50 ppb,
respectively. It shall stop the unit if the ozone level detected in the first supply
air outlet is greater than 61 ppb.

Under Manual mode, the intensity of the purifiers shall be in accordance with
the pre-set (adaptation) value at the control unit and independent of the sensor
values.

The control unit shall include a LCD display or other display device as approved
by the Supervising Officer for sensing values, hour counter and an error / alarm
logger record of malfunction. All configuration setting shall be adjustable by
using keypads and further protected by a password against unauthorised access
of untrained staff.

For purposes of monitoring and remote control, the received signals from the
sensors, system parameters and alarm status shall be able to be monitored and
set by using the CCMS via a RS232 interface. The time interval of signals is at
least 2 seconds. A dry contract for system alarm shall be provided for local /
remote monitoring of system operation. Causes of the alarm shall include the
failure of sensors and the air flow & humidity exceeding the pre-set values.

The air purifier shall be UL listed and tested to comply with Underwriters
Laboratories UL 867:2012 Electrostatic Air Cleaners.

C1.17 ULTRA-VIOLET (UV) STERILISING LIGHT

The UV steriliser light shall be provided to disinfect the supply air and eliminate
any health hazard from the mechanical ventilation and air-conditioning system.
It shall be mounted within the air handling unit, return air duct or other
appropriate locations as specified in the Particular Specification.

Section C1 AC_GS
Page 14 of 24 2017 Edition
The complete system shall consist of UV tubes, tube fitting set, electric supply
unit and monitoring unit. It shall be designed for achieving a minimum bacteria
removal efficiency of 90%. Equipment shall be selected on basis of UV lethal
dosage requirement, not less than 5,000Ws/cm2, for bacteria removal.
Relevant selection method and independent laboratory test reports and
certificates to show the removal efficiency of the unit shall be submitted to the
Supervising Officer for approval.

The UV steriliser light shall not generate substances in excess of the safety
standards as specified by the Occupational, Safety & Hygienic Association
(OSHA), USA or other recognised international standards.

The UV irradiation sections shall be provided with access door, inspection


window and safety switch. The A/C Contractor shall ensure sufficient access
space is allowed for maintenance purpose. A permanent warning notice shall be
placed at the access door to alert personnel the danger of direct sight at the UV
lamps.

The UV steriliser light shall be suitable for operation under supply voltage of
220V/50Hz. It shall be of high grade, non-corrosive materials. The housing
shall be of high quality stainless steel and lamps shall be made from quartz glass
with ceramic bases.

The electric supply unit shall be allowed to mount inside the irradiation chamber.
System components exposed under moist air or condensation shall be of IP68.
It shall have an implemented safety switch-off after lamp breakdown.

The working range of the electronic ballast shall be linear throughout a wide
range of temperature. It shall have an implemented over voltage cut-out to
improve safety and material protection. It shall not emit at a temperature above
40 oC during operation.

The UV steriliser light shall start and work properly even under unexposed,
unfavourable working temperatures.

The emitter shall consist of electrodes and high quartz glass tube with ceramic
bases. Each tube shall consume not more than 36W but emit pure UVC
irradiation at wavelength 253.7nm of not less than 120W/cm2 measured at 1 m
distances from the source after 100 hours under 25oC.

Life span shall be not less than 12,000 hours with residual output of 75 5% of
the original output, measured after 100 hours under 25oC.

The UV output of the lamps shall be highly stable over an air temperature range
of 5 oC 25 oC and in no case the output fluctuation shall be greater than 30%
of its nominal value within this temperature range. The UV output reduction
shall not be any higher than 10 5% of its nominal value after 2000 hrs of
burning in air.

The monitoring unit shall be an independent wall mounted unit installed in the
vicinity of the sterilisation section. It shall be enclosed with casing of at least
IP54.

Section C1 AC_GS
Page 15 of 24 2017 Edition
The monitoring unit shall consist of any easy to reach circuit breaker, an on/off
3-way switch (auto/off/manual), a leakage current protective switch, a good
visible general malfunctioning alarm lamp and shall have an indication display
with at least two coloured functioning LEDs for each connected ultraviolet
system.

The monitoring unit shall be able to give information about used life span and
lamp replacements for any connected system. It shall be able to monitor up to
42 lamps.

The monitoring unit shall be equipped with an RS 232 interface for external
communication via CCMS. All of the operation status and fault signals shall be
monitored by the CCMS.

The UV steriliser light shall be UL listed and tested to comply with


Underwriters Laboratories UL Standards 153:2014 Standard for Portable
Electric Luminaires, UL 1598:2008 Luminaires &UL 1995:2011Heating and
Cooling Equipment respectively.

C1.18 WATER SCRUBBER

The water scrubber shall be provided for applications such as Refuse Collection
Point (RCP), Cooked Food Centre (CFC), Poultry Stalls, serving as the exhaust
systems for central air treatment of odour, gas, liquid and solid contaminants
prior to discharge to the atmosphere. Three of the major components of
contaminants in the RCP application are hydrogen sulphide, mercaptans and
aldehydes. Whereas oil mist will be present in the foul air source of the CFC or
poultry stalls.

All components of the water scrubber shall be compatible to each other in all
aspect and wholly imported, factory built and assembled as complete units
before shipping. The only field connections required on site shall comprise only
external control circuitry, pipework, fan and ductwork connections. For very
big unit or due to site constraint that on site assembly is necessary, prior
approval shall be obtained and installation method statement shall be submitted
to the Supervising Officer for approval and as required per the Electrical
General Specification.

The manufacturer shall have at least five years experience and proven record in
the design and manufacturing of water scrubber equipment and has considerable
amount of job references and installations for similar applications.

Certificates and documentary evidence of excellent chemical resistance of all


materials, components and equipment adopted for operation with the selected
chemicals and specified application shall be submitted to the Supervising
Officer for approval. In addition, the following detailed information and
calculations shall be provided: -

(a) Chemical reaction formulation and design criteria;

Section C1 AC_GS
Page 16 of 24 2017 Edition
(b) Selection of the type and depth of packing, mist eliminators, nozzles, etc.
with manufacturers test data or recognised standards;

(c) Scrubber overall height & dimensions, packing depth, mist eliminators
depth, etc.;

(d) Selection of water recycle pump head and flow rate in accordance with
the system design and configuration to meet specified performance;

(e) Design of maximum air velocity at specified air flow rate and selection
of fan duties with respect to the design flow and pressure drop in
ductworks, fittings, silencers, scrubber section, etc.;

(f) Dosing rate of chemicals required and feed-in water /bleed-off rate; and

(g) Equipment sound level calculation and acoustic treatment offered for
compliance with the specified acceptable noise levels.

All materials, fabrication procedures, manufacturing tolerances, workmanship,


tests and product quality shall conform to the U.S. National Bureau of Standards
PS 15-69:1969 - Custom Contact Moulded Reinforced Polyester Chemical-
Resistant Process Equipment. Product Standard for Custom Contact Moulded
Reinforced Polyester Chemical Resistant Process Equipment or equivalent
recognised standards as approved by the Supervising Officer.

Before the scrubber is despatched from the factory, the manufacturer shall
obtain a certificate from a reputable independent inspection company such as
Bureau Veritas, Lloyd or SGS United States Testing Company Inc., etc. The
certificate shall state whether the scrubber assembly is standard manufactured
product, list the major equipment and materials for construction and advise
whether they comply with our specification.

Each complete scrubbing system shall comprise a scrubber housing, a scrubber


section with knockdown baffles/packing, mist eliminator, scrubbing liquid
distribution system, chemical feed pumps, fan, chemical tanks, silencers,
instrumentation, acoustic enclosure and all necessary controls as well as any
other accessories required to build up a functional plant to the satisfaction of the
Supervising Officer.

All material and components adopted in the scrubbing system shall be suitable
for operation with the selected chemicals including sodium hypochlorite,
sodium hydroxide and the resulting by-products of scrubbing.

Those items specified to be constructed of FRP shall be fire retardant grade to


Class 1 of BS 476- 7:1997 Method of Test to Determine the Classification of
the Surface Spread of Flame of Products and shall be stabilised against
ultraviolet degradation. The type of resin to be used shall be approved by the
Supervising Officer.

Acoustic treatment shall be provided to ensure the sound level at site boundaries
complies with the latest requirements of the Environmental Protection
Department.

Section C1 AC_GS
Page 17 of 24 2017 Edition
C1.18.1 Performance Requirement

(a) Application

Removal of odour, gas, liquid and solid contaminants of foul


air source at the RCP, CFC, Poultry Stalls or other specified
areas through water scrubbing, absorption and chemical
oxidation of malodorous compounds in the exhausted air.

(b) Odour Removal Efficiency

- Not less than 99% based on hydrogen sulphide at 25


ppm, mercaptans, aldehydes and other airborne
contaminants; or

- Not less than 60% for kitchen exhaust.

(c) Oil Mist Removal Efficiency

Not less than 99% for 4m oil particles.

(d) Chemical Selected for Operation

Sodium hydroxide, sodium hypochlorite, or other chemicals as


specified in the Particular Specification.

C1.18.2 Construction

The scrubber shell shall be constructed of fibreglass reinforced


polyester resin (FRP).

Scrubber section of horizontal draw-through non-clogging venturi


type shall be used for exhaust air treatment from kitchens of CFC. A
series of knockdown baffles of FRP or other approved equivalent type
shall be placed directly following the venturi section. The
knockdown baffles shall be designed to remove 90% liquid coming
from the venturi section and entering the mist eliminator.

Scrubber section of horizontal draw through cross-flow packed tower


bed type shall be used for exhaust air treatment from RCP or Poultry
Stalls. The packing shall have a free volume of 95% and minimum
100 square metres of surface area per cubic metre of packing.
Pressure drop per metre of packing shall not exceed 165 Pa. The
packing shall be made of polypropylene or other approved equivalent
type. All packing support shall be made from heavy duty FRP
construction. The packing depth, recirculation rate, and recirculation
solution shall be designed to meet the required performance and
efficiency.

Each scrubber shall include a scrubber housing, internal structural


members, scrubber section with knockdown baffles/packing, mist

Section C1 AC_GS
Page 18 of 24 2017 Edition
eliminator, scrubbing liquid distribution system, chemical feed pumps,
fan, chemical tanks, silencers, instrumentation, acoustic enclosure,
lifting and hold down lugs, etc. All components and accessories shall
have sufficient mechanical strength and designed to withstand the
extremely corrosive continuous operating environment and pressure
even with the absence of chemical dosing.

Sufficient access manholes/panels and facilities shall be provided for


inspection, removal and maintenance of all internal parts. Panels
shall be completed with handles and neoprene gaskets secured with
wing nuts to avoid spill out of water from the scrubber. The whole
assembly shall be supported on structural members made of FRP or
other approved equivalent material with mechanical strength and
properties compatible with conventional steel members.

The mist eliminator section shall be replaceable, corrosion resistant,


mesh type or other approved type fabricated of FRP or equivalent as
approved and capable of removing not less than 90% of the entrained
moisture in the air exhausting through the scrubber. The eliminator
section shall be in modular form of adequate surface area and strength
to withstand the handling air flow rate and pressure and placed in last
section of the scrubber.

The scrubbing liquid distribution system shall be of the spray type or


other approved type, sized for the flow rate to suit the design of the
scrubber system to meet specified performance. No liquid
distributors shall be permitted. Material of construction shall be
polypropylene or FRP of same material as the shell.

Spray nozzles shall be constructed of polypropylene or other


approved equivalent material.

Each scrubber shall be designed with a sump for collecting the


recirculated scrubbing liquid. It shall be finished with three nos. of
recycle pumps, one of which as standby. Manual selection switch
shall be provided to enable selection of either one of them as standby
pump. The pumps shall be direct coupled to TEFC motors, self-
priming, horizontal end suction, corrosive resistant, centrifugal type.
Accessories such as pressure gauges, stop and vent cocks shall be
provided for each pump. The flow rate shall be determined by the
A/C Contractor to suit the performance specification with adequate
flow rate and pump heads to cater for the piping and scrubber plant
friction losses. The pump casing, impeller shall be of rigid PVC and
the impeller shaft shall be of stainless steel or equivalent corrosion
resistance materials approved by the Supervising Officer.

Corrosive resistant flexible connectors shall be provided between all


ductwork joints of the water scrubber.

All pipework, fittings and valves shall be made of UPVC or other


approved equivalent material. All internal and external bolts and

Section C1 AC_GS
Page 19 of 24 2017 Edition
fasteners, including anchor bolts and flange bolts shall be of high
grade 316 stainless steel.

The scrubber shall be suitable for application involving hot gas


streams containing relatively high particulate loadings.

C1.18.3 Chemical Feed System

Each scrubber system shall be provided with a complete chemical


feed system for storing and feeding the chemicals required. The A/C
Contractor shall provide all adequate provisions for the storage,
installation and operation of the chemical solutions in compliance
with the Fire Services Regulations as the scrubbing chemical
solutions used are in the list of Dangerous Goods Category. The
Chemical feed system shall comprise chemical storage tank and feed
pump for each scrubbing chemical solution, piping and valves, and all
necessary controls.

Chemical storage tanks shall be vertical flat bottom type made of FRP
with scale and lockable screw lid and shall be suitable for storing the
scrubbing chemical solution. Each tank shall have a minimum
effective capacity of holding the exempted quantity at specified
concentration allowable by the FSD, typically of 250 litres. One set
of protective goggles, gloves and overalls shall be provided for each
scrubber.

Chemical metering pumps shall be solenoid operated diaphragm


pump for the type of weatherproof protection. The pumps shall be
operated on 220 V/single phase/50 cycles. Housing and liquid end
shall be corrosion proof as well as dust and waterproof to protection
Class IP65. Housing shall be die cast light-metal alloy. Solenoid
shall be proofed against overload and excessive counter pressure such
that it will not result in failure. Pumping capacity shall be adjusted in
ratio of 1:10 through stroke length and 1:25 through stoke frequency,
accessories shall include PVC dosing valve and foot valve.

C1.18.4 pH and ORP Control

Each scrubber shall be provided with pH and ORP probes suitably


located for analysing the contents in the scrubber sump. Probes shall
meet the following specifications: -
pH Probe ORP Probe
Range 0 to 14 pH 0 to 990 mV
Stability 0.03 pH units 0.5 MV per 24 hr. per
day, non-cumulative
Temperature 0 oC to 40 oC 0 oC to 40 oC
Pressure Rating 4.83 kPa 4.83 kPa
Wetted Materials Glass Glass
Accuracy Sensitivity 0.1 pH unit 5 HV

Section C1 AC_GS
Page 20 of 24 2017 Edition
Each probe shall be supplied with analyser and level alarm at the
local and remote control panels and they shall be actuated when the
chemical levels at chemical tanks are lower than the pre-set values.

C1.18.5 Fan

Motor driven fans shall be provided for each scrubber unit and shall
be of sufficient capacity and horsepower, as indicated in the
Equipment Schedule to deliver the required volume of air against the
total pressure losses in the air intake, duct pickup systems, packed
bed, mist eliminator, silencers and exit ducting, etc.

Fans shall be of high efficiency and low speed backward curved


aerofoil types with lowest noise level suitable for outdoor application.
Sound power level spectrum shall be submitted for approval and the
data shall be verified on Site as specified.

Fan housings, flanges and impellers shall be constructed of FRP


laminate as approved by the Supervising Officer.

Inlet connections shall be Neoprene slip type flex connector with


stainless steel draw-bands. Outlet connection shall be a rectangular
undrilled flange.

Each of the blowers shall have V-belt drive with a minimum service
factor of 1.5 times the rated brake horsepower of the fan motor and
shall be equipped with heavy-duty, self-aligning sealed ball bearings.

Fan shafts shall be carbon steel and sized to run below critical speed.
A steel hub encapsulated with FRP shall be provided to a point flush
with the housing. Wheel and shaft assemblies shall be statically and
dynamically balanced in 2 directions according to recognised
international standards.

The fan base shall be made of corrosion resistant material of


sufficient strength or carbon steel treated with anti-corrosion coatings
as approved by the Supervising Officer. No metal parts shall be
exposed to the corrosive air stream.

Fan shall be completed with motor, drive, belt, FRP motor and drive
canopy, housing drains, access doors and flexible connectors for inlet
and outlet, etc.

C1.18.6 Motor

Unless otherwise specified in the Equipment Schedule each fan shall


be provided with a horizontal squirrel cage induction type motor of
sufficient power such that no point on the fan curve requires more
than the horsepower of the motor plus a 15% spare capacity.

Section C1 AC_GS
Page 21 of 24 2017 Edition
Each electric motor shall be suitable for 380 V, 3 phase, 50 Hz and
24 hours continuous operation.

The motor enclosure shall be totally enclosed, fan cooled and suitable
for outdoor application.

The motors shall be designed, constructed and tested in conformance


with all the requirements of the applicable standards of the IET,
NEMA and ANSI and as required in the Electrical General
Specification.

The A/C Contractor shall be responsible for calculating and


submitting for approval the fan static pressure to suit the ducting
configuration and proposed equipment with calculations.

Acoustic treatment, such as silencers and acoustic enclosures shall be


provided to ensure the noise break out to adjacent areas is at an
acceptable level complying with Government Authorities regulations.

Silencers shall be of pack less type or be completed with adequate


coating and shall be suitable for the chemical corrosive environment.

C1.18.7 Control

The water scrubber system shall be capable of both automatic and


manual operation. In "DDC/auto" mode, the central exhaust fan shall
be started or stopped automatically by the DDC system. The scrubber
exhaust fan shall be interlocked with the recycle pumps operation
such that it will not be operative unless the pumps are operating. A 2-
way motorised valve and flow regulating valve at water feed-in pipe
shall be provided and interlocked with the fan.

Chemical feed pumps shall dose proportionately to maintain the


desired concentration of the scrubbing liquid. NaOH shall be
controlled with pH analyser to maintain a pH value of 8 to 9 while
NaOCl shall be controlled with oxidation-reduction-potential (ORP)
analyser to maintain an ORP value of 300 to 400 mV or to values as
recommended by the manufacturer in order to comply with the
specification.

Low level sensors in the water scrubber chamber shall be provided


and installed to give audio and visual warning signals at the local &
remote control panels and to stop the circulating pumps when the pre-
set extra low water level condition is reached.

Corrosion resistance low level sensors shall be provided and installed


for each of the chemical tanks to give audio and visual warning
signals at the local & remote control panels during low chemical level
condition.

Flow switch shall be provided and installed at the feed-in water pipe
to give audio and visual warning signals at the local & remote panels
during "no flow" condition.
Section C1 AC_GS
Page 22 of 24 2017 Edition
In "manual" mode, the fan and pumps shall be operated by means of
start/stop buttons at the water scrubber control panel.

Emergency stops shall be provided adjacent to each of the pump and


fan unit.

Local and remote control panels shall be provided for the water
scrubber systems at location as shown on the Drawings.
Local/remote selector switch shall be provided at the local panels for
choice of control mode. In "remote" mode, the water scrubber system
shall be started or stopped via manual push buttons at the remote
control panel. The scrubber exhaust fan shall be interlocked with the
recycle pumps operation such that it will not be operative unless the
recycle pumps are operating.

In "Local" mode, the fan and pumps shall be operated by means of


start/stop buttons at the local control panel.

The following minimum facilities shall be provided at the local


control/starter panel: -

- Power on indication green;

- Local/remote selector;

- Recycle pumps sequence selector;

- Start and stop push buttons for fan and pumps;

- Hour run meters for fan;

- Running (blue) and fault (red) indication for fan and pumps;

- Ammeters for fan;

- Low level alarms (red) for each chemical tank;

- Low level alarm (red) for the water scrubber chamber; and

- No flow alarm (red) for the feed-in water pipe section.

C1.19 WASHING FACILITIES FOR WASHABLE FILTER

Where washable filters are provided, the A/C Contractor shall provide one set of
duplicate cleaning tanks (one to wash, one to rinse). These tanks shall be big
enough to accommodate the various filters sizes provided, subject to the
approval of the Supervising Officer or if the A/C Contractor wishes several sets
of tanks may be provided to accommodate the various filter sizes provided.

Section C1 AC_GS
Page 23 of 24 2017 Edition
The filter cleaning tanks shall be constructed of at least 1 mm thick stainless
steel of AISI 316 and suitably stiffened around the top edges by continuous
external turned over inverted "U" sections. The tanks shall be 0.4 m deep. They
shall be supplied with 18 mm drain down cock for emptying but shall also have
external handles to facilitate turning over to clear sludge.

C1.20 FILTER PRESSURE DIFFERENTIAL MEASUREMENT AND


INDICATION

A differential pressure gauge of the inclined manometer type shall be provided


for each filter bank.

The gauge shall incorporate a graduated scale on which the reading of maximum
pressure drop shall occur in not less than 75% of the total scale length.

C1.21 ADDITIONAL REQUIREMENTS (SPARE FILTER MEDIA)

The A/C Contractor shall replace all filters used during testing and
commissioning stage and in addition provide the following to the Supervising
Officer for use by Employers operation staff during Maintenance Period: -

(a) For disposable type filters, one complete set of unused filter cells;

(b) For washable type filters, 20% in number of each size of filter cells
provided. These shall be new and in good condition. Besides, 10 litres
of the approved cleaning detergent per filter installation shall be provided.
Regarding filters of viscous type, a drum or drums of fluid amounting to
one complete change or 10 litres per filter installation where thixotropic
coatings are used shall be provided;

(c) For renewable type filters, one complete set of unused filter media; or

(d) For gas filters, one complete set of unused filter cells.

Within one month before expiry of the Maintenance Period, all the filter
cells/media shall be replaced with new ones. In addition, 10 litres of the
approved cleaning detergent per washable filter installation shall be provided.
Regarding filters of viscous type, a drum or drums of fluid amounting to one
complete change or l0 litres per filter installation where thixotropic coatings are
used shall be provided.

Section C1 AC_GS
Page 24 of 24 2017 Edition
SECTION C2

DUCTWORK AND ACCESSORIES

C2.1 GENERAL

Ductwork shall be off site pre-fabricated according to the requirement as


specified in the Particular Specification. The ductwork shall be fabricated from
good quality full sized zinc coated hot dipped galvanised flat steel sheet to BS
EN 10346:2009, Grade DX51D+Z, coating type Z275 unless otherwise
specified in the Particular Specification or the Drawings.

C2.2 OFF SITE PRE-FABRICATION

The development of components for round, oval and rectangular ductwork shall
be carried out by a computer software which can produce all development plans
from the proposed ductwork layouts including all type of ductwork fittings and
accessories. The software shall be able to work out the development plans with
utilisation factor not less than 94%.

The above utilisation factor is based on a ratio of the Standard Size Straight
Ductwork: Ductwork Fittings, which is 7 : 3. For standard straight ductwork,
the utilisation factor is about 100% and that for fittings is about 80%. If the
ratio of Ductwork to Fittings is not 7 : 3, the overall utilisation factor shall be
submitted to the approval of the Supervising Officer.

The remaining materials that cannot be used for fabrication of ductwork shall be
used for other purpose or at least to be recycled instead of being disposed of as
scraps. The software used shall also be linked to the Numerical Control Cutting
Machines, such as the Plasma Cutting System for the cutting, development and
forming of the required ductwork components and accessories.

Automatic or semi-automatic machines shall be employed for the bending,


folding and assembly of ductwork from sheet metal components developed.
Proper machines are required for the manufacturing of all ductwork accessories
including flanges, stiffeners, splitter dampers, etc. in order to enhance quality.

Construction and materials used for ductwork, fittings and accessories shall be
inert, non-hygroscopic, vermin and moisture proof, asbestos and CFC free, and
shall not support growth of bacteria.

Bends and branch vanes, dampers, etc. shall be of the same material as used for
the ductwork and/or of heavier gauge, securely mounted.

C2.3 SPECIFICATION AND STANDARDS

Ductwork shall comply with the following B&ES publications with additions or
amendments as required by this General Specification and/or elsewhere in the
Contract.

Section C2 AC_GS
Page 1 of 15 2017 Edition
(a) DW/144:2013
Specification for sheet metal ductwork (Low, medium and high pressure
/velocity air systems);

(b) DW/154:2000
Specification for plastics ductwork; and

(c) DW/191:1973
Code of Practice for ductwork made from resin-bonded glass fibre.

Where any part of the Installations is not covered by the above, the
recommendations of the "HVAC Duct Construction Standards-Metal and
Flexible" issued by the Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) of USA shall be applied.

C2.4 FLEXIBLE DUCTWORK

Flexible ductwork shall be provided as connections between vibration


generating equipment and/or ductwork and where air duct passing across
building expansion joint. Flexible connection shall be fitted with acceptable
alignment and effective length suitable for the elimination of vibration
transmission.

The flexible ductwork shall have a liner and a cover of tough tear-resistant
fabric equal in durability and flexibility to glass fibre fabric. The fabric shall be
impregnated and coated with plastics. It shall be reinforced with a bonded
galvanised spring of stainless steel or other approved wire helix between the
liner and the cover. An outer helix of glass fibre cord or equal shall be bonded
to the cover to ensure regular convolutions. Flexible ductwork without a liner
may not be used.

In no cases shall material containing asbestos fabric be used.

Alternatively, flexible ductwork shall consist of flexible corrugated metal tubing


of stainless steel, aluminium, tin plated steel or aluminium coated steel. The
metal surface(s) may be coated with a plastics material.

The leakage from any section of flexible ductwork shall not exceed 1% of the
local design air flow rate at the local maximum static pressure.

Flexible ductwork shall be suitable for the air velocity, pressure and an
operating temperature range of -5C to 90C and shall comply with BS 476-
12:1991, Rating Class P; BS 476-6:1989+A1:2009 having an index of
performance not exceeding 12 of which not more than 6 should derive from the
initial period of test; Part 7 Class 1 (surface of very low flame spread) and
current requirements of the FSD unless otherwise indicated.

Section C2 AC_GS
Page 2 of 15 2017 Edition
C2.5 DUCTWORK FOR CORROSIVE FUMES

Ductwork used to carry corrosive fumes shall be of non-corrosive material.


Where PVC material is used, the minimum thickness shall be 2.4 mm.

Plastic ductwork and all associated moulded or extruded sections, angles and
fittings shall be unaffected by the range of substances conveyed and under the
conditions indicated. Unless otherwise indicated, and providing the
requirements above can be met, sheet material shall be pressed unplasticised
PVC sheet complying with ISO 6453:1985.

Where PVC ductwork is thermally insulated or is not readily visible, Type A3


sheet shall be used; elsewhere Type Al shall be used.

Any plastic ductwork system incorporating a heater battery shall be installed


such that no part of the system is impaired by the heating effects of the battery
or its casing.

Circular ductwork up to 300 mm shall preferably be fabricated from


unplasticised PVC pipe complying with relevant ISO and BS EN standards.
Unless otherwise indicated, the colour of sheet and pipe shall be industrial grey.
Ductwork shall be constructed (thickness, angles, stiffness, etc.) in accordance
with Specification DW/154:2000.

Where any part of the Installations is not covered by "DW/154", then the
recommendations of the "Thermoplastic Ductwork (PVC) Construction Manual"
issued by the Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) of USA shall apply.

The methods of construction recommended in B&ES Specification


DW/154:2000 shall be used, i.e. cemented joints shall be used for circular (pipe)
jointing and hot gas/filler rod, welding shall be used for all other fabrication.
For circular ductwork constructed from pipe, sufficient angle joints shall be
provided to enable the ductwork to be dismantled in the space available. Where
so directed by the Supervising Officer, all welders shall carry out the test
detailed in B&ES Specification DW/154:2000.

The requirements of B&ES Specification DW/154:2000 with regard to


expansion joints, ductwork supports, access doors and gaskets shall be met.

Extruded or moulded sections, angles and fittings shall be of the same plastic
materials and colour as the sheet or tube.

PVC ductwork shall not be used in situations where it will be subjected to


temperatures of 50 oC and above. Where heater batteries are required in the
system, the PVC ductwork shall be isolated from these by a suitable length of
stainless steel ductwork, generally as described for glass fibre ductwork in
Clause C2.6.

Section C2 AC_GS
Page 3 of 15 2017 Edition
C2.6 GLASS FIBRE DUCTWORK

C2.6.1 General

Where specified in the Particular Specification or the Drawings, glass


fibre ductwork made from 25 mm/38 mm thick resin bonded glass
fibre in rigid board form may be used. The board shall have an
integral external vapour barrier of hard grade, flame retardant,
damage-resistant reinforced aluminium foil and an internal smooth,
durable acrylic coating that isolates the glass fibre substrate from the
air stream and inhibits penetration of the insulation by dirt, dust,
microorganisms and other pollutants.

Special attention shall be paid to ensure that the material


itself/fabrication/erection of the ductwork does not contribute towards
suspected health hazard.

Thickness of the ductwork board to be used shall be selected in


accordance with manufacturers ductwork sizes, static pressure and
reinforcement schedule and recommendation.

C2.6.2 Specification and Standards

Specification and Standards for glass fibre ductwork shall comply


with the recommendations of the B&ES Publication DW/191:1973
Code of Practice for ductwork made from resin-bonded glass fibre, or
the "Fibrous glass Ductwork Construction Standards" issued by the
Sheet Metal and Air Conditioning Contractors National Association,
Inc. USA. The flexural rigidity rating of the rigid glass fibre board
shall be 8OOE1 (33.7 kg/m2) as defined in the above Standards.
Glass fibre ductwork shall meet with the requirements of NFPA-
90A:2012 and 90B:2012 by complying with the requirements of
Under-writers Laboratories Standard for safety UL 181:2013 for
Class 0 ductwork.

Glass fibre ductwork to be used shall resist fungal or bacterial growth


when subjected to microbial attack described in Standard Practices
ASTM G21-13(fungus test).

Glass fibre ductwork shall be easily cleanable using methods and


equipment described in North American Insulation Manufacturers
Association (NAIMA) Publication AH-122, Cleaning Fibrous Glass
Insulated Ductwork Systems.

C2.6.3 Mounting Fittings

Where the following items are installed in a ductwork, a suitably


sized section of galvanised sheet ductwork shall be installed
completed with independent supports and insulation: -

(a) Electric or hot water, etc. ductwork heaters and access panels;
(b) Volume control dampers;

Section C2 AC_GS
Page 4 of 15 2017 Edition
(c) Fire dampers and access panel; and
(d) Fan and access panel.

C2.6.4 Mountings of Instruments

All control/metering probes, etc. which requires mounting in fibre


glass ductwork shall be adequately supported by a sheet metal panel
securely fixed to the internal face of the ductwork. The A/C
Contractor shall fix a removable insulated cover over the complete
probe to ensure condensation will not occur on any exposed metal
surfaces.

C2.6.5 Special Tools and Manufacturers Fabrication Instructions

The construction and installation including all cutting tools employed


to fabricate the ductwork shall be strictly in accordance with the
recommendations of the fibre glass ductwork manufacturers
instructions issued for the correct installation of their product.
Fabrication and installation by any method other than that endorsed
by the fibre glass ductwork manufacturer may be rejected by the
Supervising Officer.

C2.7 FOAM DUCTBOARD DUCTWORK

C2.7.1 Phenolic Foam Duct Board Ductwork

C2.7.1.1 General - Where specified in the Particular Specification


or the Drawings, pre-insulated ductwork made from
20 mm thick rigid closed cell phenolic foam in rigid board
form may be used and should be approved or accepted by
the FSD.

C2.7.1.2 The ductwork material shall be covered with a layer of


vapour barrier on both board facing. The vapour barrier
shall be of minimum 20 micron thick aluminium foil.
The circumferential and longitudinal seams of the vapour
barrier foils shall be sealed with self-adhesive foil tape as
specified in Clause C11.4.3.

C2.7.1.3 All material shall have a class 'O' fire rating and approved
or accepted by the FSD. Details refer to Clause C11.2.1.
Low smoke emission shall comply with BS EN ISO
5659-2:2012 and shall be CFC free.

C2.7.1.4 The flange system for the phenolic foam ductwork shall
be designed to eliminate the effect of "Cold Bridge" and
for the purpose of sealing, the flanges shall be coated with
fire resistant gaskets and securely mounted with sufficient
bolts, nuts and clips. An established joining system shall
be employed in connecting the ductwork and accessories

Section C2 AC_GS
Page 5 of 15 2017 Edition
such as air outlets and dampers. The joining system shall
be approved by the Supervising Officer.

C2.7.1.5 Where the following items are installed in the ductwork,


they shall be adequately supported by a sheet metal panel
securely fixed to the internal face of the ductwork with
due consideration to ensure that condensation will not
occur on any exposed metal surface: -

- Ductwork heaters;
- Volume control dampers;
- Fire dampers; and
- Fans & access panels.

C2.7.1.6 The construction and installation including all cutting


tools, adhesives, flange system shall be strictly in
accordance with the recommendations of the phenolic
foam duct board manufacturer's instruction.

C2.7.1.7 Unless specified in the Particular Specification or the


Drawings, the width and length of pre-insulated ductwork
made from phenolic foam in rigid board form shall not
exceed 500 mm.

C2.7.2 Polyurethane Foam Duct Board Ductwork

C2.7.2.1 General - Where specified in the Particular Specification


or the Drawings, pre-insulated ductwork made from
20 mm thick rigid polyurethane foam in rigid board form
may be used and should be approved or accepted by the
FSD.

C2.7.2.2 The ductwork material shall be covered with a layer of


vapour barrier on both board facing. The vapour barrier
shall be of minimum 60 micron thick aluminium foil.
The circumferential and longitudinal seams of the vapour
barrier foils shall be sealed with self-adhesive foil tape as
specified in Clause C11.4.3.

C2.7.2.3 All material shall have a class 'O' fire rating and approved
or accepted by the FSD. Details refer to Clause C11.2.1.
Low smoke emission shall comply with BS EN ISO
5659-2:2012 and shall be CFC free.

C2.7.2.4 The flange system for the polyurethane foam ductwork


shall be designed to eliminate the effect of "Cold Bridge"
and for the purpose of sealing, the flanges shall be coated
with fire resistant gaskets and securely mounted with
sufficient bolts, nuts and clips. An established joining
system shall be employed in connecting the ductwork and
accessories such as air outlets and dampers. The joining
system shall be approved by the Supervising Officer.

Section C2 AC_GS
Page 6 of 15 2017 Edition
C2.7.2.5 Where the following items are installed in the ductwork,
they shall be adequately supported by a sheet metal panel
securely fixed to the internal face of the ductwork with
due consideration to ensure that condensation will not
occur on any exposed metal surface: -

- Ductwork heaters;
- Volume control dampers;
- Fire dampers; and
- Fans & access panels.

C2.7.2.6 The construction and installation including all cutting


tools, adhesives, flange system shall be strictly in
accordance with the recommendations of the polyurethane
foam duct board manufacturer's instruction.

C2.7.2.7 Unless specified in the Particular Specification or the


Drawings, the width and length of pre-insulated ductwork
made from polyurethane foam in rigid board form shall
not exceed 500 mm.

C2.8 DAMPERS - GENERAL

The respective functions, types and general constructional requirements of


dampers shall be in accordance with the B&ES ductwork specification
DW/144:2013 CIBSE Commissioning Code Series A and BSRIA Application
Guide where appropriate unless otherwise indicated, sufficient dampers shall be
provided to regulate and balance the system. Dampers on grilles or diffusers
shall be used for fine control only.

All dampers shall be of flanged type with independent housing and control
mechanism for connection to ductwork and shall be sufficiently rigid to prevent
fluttering and comply with BS EN 1751:2014.

Air volume control dampers shall be of the aerofoil, double skin, opposed blade
low leakage type with seals on blade edges and casing jambs, low pressure drop
and noise regeneration characteristics. Damper blades in rectangular ductwork
shall not exceed 225 mm in width and 1500 mm in length. Blades shall be of
hollow section constructed from the same material of the ductwork or of
stainless steel encapsulating an internal double contoured steel longitudinal
reinforcing bar, mounted on square section steel spindles. The units shall be of
low-leakage design by incorporation of synthetic trailing edge seals and a
peripheral gasket which shall be tested according to BS 476-6:1989+A1:2009
and BS 476-7:1997 and shall be approved or accepted by the FSD. All
manually and automatically operated dampers shall be fitted with position
indicators provided externally and the final setting position shall be permanently
marked. Manual dampers shall include a device for positioning and locking the
damper blades. Damper handles shall be equipped with device for padlocking in
the final balanced position.

Section C2 AC_GS
Page 7 of 15 2017 Edition
Each air volume control damper in the ductwork shall be fitted with a non-
corrodible label stating the actual air flow in m3/s when in the fully open
position, its overall cross sectional area, and the degree to which the damper has
been closed in order to achieve the design or actual air flow.

Unless otherwise indicated, quadrants and operating handles shall be of die-cast


aluminium or other material approved by the Supervising Officer with the words
"OPEN" and "SHUT" cast on the quadrant.

Quadrants shall be securely fixed and the damper spindles shall be closely fitted
in the quadrant hubs to prevent any damper movement when the damper levers
are locked.

Access openings with readily removable air sealed covers shall be provided
adjacent to all dampers except the volume control dampers of which the
adjustment can be made outside the ductwork. Subject to limitations of
ductwork size the dimensions of access openings shall not be less than 300 mm
x 300 mm and they shall be located within 300 mm of each damper so as to
afford easy access for inspection and maintenance.

C2.9 BUTTERFLY, BIFURCATING AND MULTILEAF DAMPERS

Butterfly dampers shall each consist of 2 plates, edge seamed, of at least the
same thickness as the material from which the associated ductwork is made, and
rigidly fixed to each side of a mild steel operating spindle, the ends of which
shall be turned and housed in non-ferrous bearings.

Bifurcating dampers shall be of 2 mm thick sheet for sizes up to 450 mm square,


for larger sizes the thickness shall be as specified. The damper blades shall be
rigidly fixed to square section mild steel spindles, the ends of which shall be
turned and housed in non-ferrous bearings.

Each leaf of a multi leaf damper shall consist of 2 plates of material of the same
thickness as the associated ductwork and rigidly fixed to each side of an
operation spindle, the ends of which shall be housed in brass, nylon, oil
impregnated sintered metal, PTEE impregnated or ball bearings. The ends of
the spindles shall be linked so that one movement of the operating handle shall
move each leaf for an equal amount. The mechanism shall be located outside
the air stream.

For system, static pressure below 1000 Pa or ductwork velocity below 12 m/s,
blade of at least 50 mm wide shall be used. For static pressure at or above
1000 Pa, at least 100 mm wide blade shall be used. Central blade reinforcement
bar shall be provided for damper span longer than 1500 mm. Single module of a
damper shall not exceed 2000 mm width and 1000 mm height.

Alternatively, multi leaf damper blades may be of a single plate, at least 1.6 mm
thick and suitably stiffened, and the blade linkages may be within the ductwork.
These dampers shall have bearings and inspection doors as specified in Clause
C2.8.

Section C2 AC_GS
Page 8 of 15 2017 Edition
C2.10 SELF-CLOSING (NON-RETURN) DAMPERS

Self-closing dampers shall present a minimum resistance to air flow under


running conditions and take up a stable position in operation. Maximum
resistance shall be presented under reverse air flow conditions such that they
will be forced to close and remain so. Resilient strips or other purpose made
devices shall be provided to prevent the damper from rattling and as an aid to air
sealing under reverse flow conditions.

Blades shall be rigidly constructed of steel or aluminium sheet of not less than
0.8 mm (22 gauge) and shall be free of all buckles. Blades of less than 300 mm
in height shall be fitted with a 3 mm (10 gauge) bright steel spindle at each end.
Blades of 300 mm and over in height shall be fitted with an 8 mm bright steel
spindle at each end. Spindles shall be carried by sealed ball bearings. Bearing
shall be accessible for cleaning and lubrication and shall be mounted in a rigid
galvanised steel frame. The maximum length of each blade without a central
bearing shall be 1000 mm.

C2.11 FIRE, SMOKE AND COMBINED FIRE AND SMOKE STOP DAMPERS

C2.11.1 Fire and Smoke Stop Dampers

Fire or Smoke dampers shall be provided in ductwork in the


following locations: -

(a) Wherever a ductwork passes through a floor slab or a fire


resisting wall which is expressly built for the purpose of
preventing the spread of fire;

(b) Other locations where requirements of compartmentalisation


are stipulated in the Code of Practice for Fire Safety in
Building 2011 under the Buildings Ordinance of HKSAR; and

(c) Other locations as required by the Particular Specification and


the Drawings.

Fire or Smoke dampers used singly or in combination shall have an


overall fire resistance rating not less than that indicated and certainly
not less than that for the wall or floor slab in which they are situated.

In all cases, evidence of fire rating in accordance with ISO 10294-


1:1996/Amd 1:2014 Classification E (BS 476-20:1987 to BS 476-
23:1987) or NFPA-90A:2012 with 2-hour UL fire damper label shall
be provided by an independent testing organisation approved by the
Supervising Officer. All Fire or Smoke dampers shall also be
approved or accepted by the FSD.

Fire or Smoke damper blades of proprietary made shall be


constructed to the approved and recognised testing authority and

Section C2 AC_GS
Page 9 of 15 2017 Edition
possess a rating equivalent to the fire resistance of the structure it
protects.

Local made fire or smoke damper blades shall comply with the
requirements of the Circular Letters issued by the FSD and the
Buildings Ordinance of HKSAR. These blades shall be housed in a
corrosion resistant casing constructed to avoid distortion due to stress
in fire conditions. Stainless steel spring tempered flexible gasket
shall be inserted between the blade and the casing for elimination of
closing friction and retardation of smoke. Provision shall be made to
accommodate expansion of the damper blades within the casing in
fire conditions to prevent jamming and to retard the spread of smoke.
A Fire or Smoke damper installation frame supplied by the same
manufacturer shall also incorporate provision for expansion within
the surrounding structure together with masking flange for building
into the structure.

Fire or Smoke damper assemblies for installations in corrosive


environments shall be fabricated from suitable materials resistant to
the corrosive substances and environments indicated. Alternatively,
the material may be coated with a protective finish to produce the
same effect.

Power fail-safe remote electromagnet release or electro thermal link


(ETL) shall be provided to explosion hazardous areas. The
electromagnet shall normally not consume more than 10 mA by 220
V AC supply or 120 mA by 24 V AC/DC supply. The A/C
Contractor shall be responsible for the power fail-safe fire dampers to
the fire control relay at the fire service control panel.

Each Fire or Smoke damper casing shall be air tight, continuously


welded and clearly marked with a permanent indication of the
direction of air flow and the side at which the access/maintenance
opening is located.

The folded continuous interlocked blade type of damper may be used


for vertical or horizontal ductwork applications. The closing force for
these types of dampers shall be provided by stainless steel spring or
springs. An automatic locking device shall be provided to ensure that
the blades are held in the closed position after release.

Spring actuated pivoted single-bladed or multi-bladed dampers may


be used for vertical or horizontal ductwork applications.

Multi-bladed dampers shall be provided with a means to ensure that


all the blades close simultaneously.

Gravity operated multi-bladed fire dampers shall not be used in


vertical ductwork.

Section C2 AC_GS
Page 10 of 15 2017 Edition
Gravity operated single bladed dampers may be used for horizontal
ductwork provided means are incorporated which ensure reliable and
positive closure when operating in maximum air flow rate conditions.

Locally fabricated gravity fire dampers shall be provided with a


coaming or casing of the same material and shall be physically bolted
to the structure through which the ductwork penetrates.

Fire or Smoke dampers shall be rated in accordance with the fire


resistance rating of the wall, ceiling or floor, etc. as shown in the
drawings and the Particular Specification, to the requirements of the
FSD and approved by the Supervising Officer.

For locally fabricated fire dampers, the thickness of metal for the
dampers shall comply with the Circular Letters issued by the FSD and
the Buildings Ordinance of HKSAR.

Where gravity acting, off-centre pivoted dampers incorporate spindle


bearings long term corrosion effects shall be minimised by the choice
of suitable materials. Bearings shall be sealed or capped to exclude
dirt and dust. Damper blades shall close to comply with the stability
and integrity requirements of ISO 10294-1:1996/Amd 1:2014
Classification E (BS 476- 20:1987 to BS 476-23:1987).

For high velocity air systems, fire/smoke dampers shall provide 100%
free area when damper blades are in the open position to give
minimum interference to the air flow.

Unless otherwise indicated, each Fire or Smoke damper shall be held


in the open position by a corrosion resistant retaining device
incorporating a fusible element which shall operate at a temperature
of 69oC, unless otherwise indicated.

Fire or Smoke dampers shall be located in a position and be of a type


which could facilitate periodic 1 handed manual release and re-setting
for test purpose.

Proprietary access doors shall be installed adjacent to each Fire or


Smoke damper and, in the case of conditioned air or kitchen exhaust
ductwork, the access doors shall be encapsulated and pre-insulated.

C2.11.2 Combined Fire and Smoke Stop Dampers

Combined fire and smoke stop dampers shall be tested to ISO 10294-
1:1996/Amd 1:2014 Classification ES and approved by the FSD.

The dampers shall be of stainless steel, aerofoil bladed construction


with the blades held in stainless steel bearings and framed in stainless
steel spring tempered flexible gasket. The blades shall have trailing
edges forming an interlocking metal to metal seal when the blades are
closed, providing tight, low leakage closure of the air path and

Section C2 AC_GS
Page 11 of 15 2017 Edition
maximum impedance to the passage of smoke and products of
combustion from either flow direction.

The blades shall be driven by externally mounted and totally enclosed


stainless steel gearbox and drive mechanism providing accurate blade
control with minimum torque and without accumulative backlash.

The damper casing shall be of double-skin galvanised steel


construction with continuously welded corners and integral spigot
connections. The dampers shall be supplied completed with the
manufacturer-installed frames.

Each damper shall have an externally replaceable combination


thermal actuator and fusible link completely exposed to the air stream.

In addition to the thermal actuation/fusible link, the damper shall be


normally held by actuator. The damper shall be released to the closed
or fail-safe position by a closure spring on loss of power supply,
either by genuine power failure or by the zone fire signal actuated by
the smoke detection system. The time for closing the damper shall
meet the requirements laid down by the FSD.

The damper shall be automatically reset on resumption of power


supply by built-in motor of 220 V AC or 24 V AC/DC.

The whole control mechanism and actuation shall be of the same


manufacturer and mounted inside a totally enclosed casing for
protection against airborne contamination and to ensure unique
reliability.

For smoke extraction at 250 oC for 1 hour application, damper control


actuator shall be totally shielded by a proprietary thermal insulation
jacket. The whole damper assembly shall have undergone a high
temperature operation test followed by a leakage test at 1500 Pa
differential pressure and ultimately approved by the FSD.

Leakage rate shall be tested in accordance with UL555S:2014.

Fire rating shall be to BS 476-20:1987 and the whole damper


assembly shall have undergone a temperature exposure test by an
independent laboratory in accordance with the temperature and
duration as indicated in BS 476-20:1987. Test report shall be
submitted to the Supervising Officer for reference.

C2.12 MOTORISED SHUT-OFF DAMPERS

Motorised shut-off dampers shall be similar to fire/smoke dampers and shall be


open or close by motorised mechanism. Each of the dampers shall be in "Open"
position normally, but shall be closed when there is a fire or the air handling unit
is shut off. The motorised mechanism shall be actuated by associated automatic

Section C2 AC_GS
Page 12 of 15 2017 Edition
fire control. Air leakage rate for motorised shut-off dampers shall be tested
according to BS EN 1751:2014.

C2.13 TERMINAL DAMPERS

Grilles and air diffusers with rectangular neck connections shall be provided
with an opposed blade damper, screwed or riveted to the neck connection and
designed specially to facilitate final balancing of the system.

Damper frames, blades and operating mechanism shall be constructed from an


aluminium alloy or, alternatively, formed mild steel suitably finished to give
protection to the material during the design working life.

Blades shall be made of solid section material and shall be firmly held in
position by a spring steel retaining mechanism. The blade setting mechanism
shall be accessible through the grille or diffuser blades and shall be suitable for
operation with an "Allen" key. Where dampers are visible through the grille or
diffuser they shall be finished with a matt black paint.

C2.14 ACCESS DOORS AND PANELS TO DUCTWORK, CABINETS, COLD


STORES

Unless otherwise indicated, locally fabricated Access Doors or Panels shall be


constructed of marine plywood on hardwood in accordance with the Supervising
Officers issued Standard Details, suitably insulated where necessary and
finished with at least three coats of shellac, lacquered and polished.

The insulation in the door shall be equal to that of the ductwork or cabinet into
which it is installed. When closed, the door shall be effectively vapour sealed.

On doors through which a man can pass, the opening handle must also be
operable from the inside of the door.

Access doors and panels on factory made equipment shall be approved by the
Supervising Officer.

All fittings and screws shall be made of brass.

Access doors or panels to ductwork heaters shall be constructed in accordance


with the Supervising Officers issued Standard Details for ductwork heaters.

Access doors shall be of proprietary manufacture, double-skin, 25 mm sandwich


G.I. construction with fibreglass or CFC-free foam insulation infill. Access
doors shall be of lift off type having a minimum of 4 cam-lock action retaining
locks for fixing to ductwork frame. Gaskets shall conform to DW/144:2013
&DW/143:2013. Access doors shall be supplied and fitted with retaining chain
tied back to the frame. Multiple screw fixings shall not be allowed.

Section C2 AC_GS
Page 13 of 15 2017 Edition
C2.15 DUCTWORK FLANGES

All rectangular ductwork shall be flange joints. Flanges shall be of a proprietary


type, tested and certified for air leakage and deflection to DW/144:2013.
Certificates must be submitted during the equipment submission period.

The proprietary ductwork flanges shall be roll-formed from zinc coated hot-
dipped galvanised sheet metal to BS EN 10346:2009 Grade DX51D+Z, coating
type ZF180. Flanges shall be constructed with prefabricated flange profile
consisting of manufacturer provided integral sealant with corner joints inserted
into the end of the flange profiles and the whole frame shall be firmly secured
including the corner component. The already established ductwork flange shall
be fastened into the associated ductwork with spot welding. Gaskets strip to BS
476-7:1997, Class 1 and ductwork sealant to BS 476-7:1997, Class 2 shall be
applied at the flange joints and corner joints respectively to ensure maximum
leakage-proof. All sealant used shall be fire proof and vermin proof, non-toxic
and acceptable to the FSD.

Sealant and gaskets shall be provided as recommended by the flange


manufacturer.

C2.16 DUCTWORK CLEANING POINTS

The ductwork cleaning point shall generally be of a type consisting of a 50 mm


diameter metal flange with a 20 mm diameter hole closed with an air-tight
screwed plug through which inspection, cleaning and disinfection of the
ductwork can be carried out.

The ductwork cleaning point shall be of proprietary product, so constructed and


installed that no cold bridge which causes condensation will occur.

All ductwork shall be constructed to facilitate cleaning to be carried out.


Ductwork fixings shall not intrude within the ductwork and all sharp edges shall
be provided with protective finishing to the approval of the Supervising Officer.

When specified in the particular specification, ductwork support shall be


designed to support the weight of a person and industrial vacuum cleaner.
Similarly, provisions for injecting steam or detergent cleaning devices and
access panels shall be provided wherever specified.

C2.17 TEST HOLES

Test holes shall be provided according to B&ES ductwork specification


DW/144:2013, CIBSE Commissioning Code Series A, BSRIA Application
Guide, etc. wherever necessary for effective balancing and testing, whether
these provisions are shown in the Drawings or not. Test holes shall be of 25 mm
diameter and fitted with an effective removable sealed cap made of plastic plugs
or die cast metal cupped blanking plates. Test points shall be provided for all
dampers and items of equipment to enable fan duties and items to be assessed
and for the commissioning of the system.

Section C2 AC_GS
Page 14 of 15 2017 Edition
Test holes shall be positioned at points with stable air flow and not affected by
upstream and downstream fittings or obstructions. Test holes shall be located at
the inlet and discharge of all fans and air handling units to measure static
pressure, before and after air heaters and cooling coils, filters to measure
temperature and pressure differentials and other points required for regulating
and commissioning of the air distribution system.

C2.18 TRANSFER DUCTWORK

The internal lining material shall be in accordance with Clause C8.7 of this
General Specification.

Section C2 AC_GS
Page 15 of 15 2017 Edition
SECTION C3

AIR HANDLING AND TREATMENT EQUIPMENT

C3.1 GENERAL

C3.1.1 Air handling units shall be type tested in accordance to a


recognised standard, such as Euro vent, AMCA, ISO, etc., and shall
meet the minimum requirements as stipulated in Clause C3.2.1.

C3.1.2 All fans should be constructed to a fully developed design and shall
be capable of withstanding the pressures and stresses developed
during continuous operation at the selected duty. Additionally, all
belt driven fans shall be capable of running continuously at the range
of 10% to 15% in excess of the required duty speed.

C3.1.3 Fans shall be selected to give the air volume flow rates and sound
power levels specified in the Contract. Fan performance curves
giving values of sound power levels and fan efficiency at the selected
duty shall be submitted to the Supervising Officer for approval.
Values of resistance to airflow of items of equipment, ductwork
and/or the total distribution system indicated in the Contract are based
on basic design assumptions, the A/C Contractor shall verify these
values based on the actual equipment offered and installed and to
provide fans capable of delivering the required air volume when
operating against the actual total installed system resistance.

C3.1.4 Fan Construction

(a) Centrifugal fans having dimensions over 1000 mm in any


direction shall have split casing or by other means for easy
removal and repair.

(b) The shaft and impeller assembly of all centrifugal, axial flow
and mixed flow fans shall be statically and dynamically
balanced. All propeller fans shall be statically and
dynamically balanced. Limits of vibration severity shall be in
accordance with BS ISO 10816-1:1995+A1:2009 or another
acceptable standard, such as AMCA, as appropriate.

(c) Fan shall be equipped with self-aligning bearings suitable for


the installed altitude of the fan. They shall be of the grease/oil
ball and/or roller type or alternatively oil lubricated sleeve
type. All bearing housings shall be precisely located in
position and arranged so that bearings may be replaced
without the need for realignment. Bearing housings shall be
protected against the ingress of dust and, where fitted with
greasing points, they shall be designed to prevent damage from
over-greasing. For grease lubricated systems the bearings
shall be provided with grease of the amount and quality as
recommended by the bearing manufacturer. For oil lubricated

Section C3 AC_GS
Page 1 of 34 2017 Edition
systems the housings shall provide an adequate reservoir of oil
and shall include a filling plug and be oil tight and dust proof.
Systems other than total loss types shall include an accessible
drain plug. All bearing lubricators shall be located to facilitate
maintenance. Extended lubricators outside the fan casing shall
only be required if sealed for life bearings are not incorporated.

C3.1.5 Fan and motor for smoke extraction and staircase pressurisation
ventilation system shall be suitable for continuous operation at 250 oC
for at least 1 hour. All control and power cables shall be of the fire
resistance type complying with BS 6387:2013 or IEC 60331-21:1999
Category CWZ or AWX where appropriate. The requirements
specified by the FSD shall also be complied.

C3.2 AIR HANDLING UNITS (AHUs)

C3.2.1 General

Each type of AHU offered shall be the product of a manufacturer who


has made similar product for a period of at least five years.

Individual components forming part of the air handling unit shall, in


addition to this section, comply with the appropriate sections
contained elsewhere in this General Specification.

Air handling unit shall comply with the manufacturers own ISO
9001:2008/Corr1:2009 quality assurance standard in respect of design
and manufacturing and be "type" tested to the following minimum
requirements:- (i) air leakage test to HVAC Standard DW/144:2013
Class B or BS EN 1886:2007 Class L2; (ii) thickness of casing
according to Table C3.2.2; (iii) conductivity of thermal insulation not
greater than 0.02W/moC rating at the operating temperature; and (iv)
insertion loss through panels at 125 Hz and 250 Hz of 20 dB and
20 dB reduction respectively.

The A/C Contractor shall submit technical information of each unit


together with the above "type" test certificates for the Supervising
Officers approval.

The entire construction of the AHU should have following


mechanical characteristics in accordance with the BS EN 1886:2007.
Mechanical Characteristics (minimum requirement)
Characteristics Class
Casing strength D2
Casing air leakage under -400 Pa L2
Casing air leakage under +700 Pa L2
Filter bypass leakage F9
Thermal transmittance T2
Thermal bridging factor TB2
Section C3 AC_GS
Page 2 of 34 2017 Edition
Alternatively, the entire construction of the AHU should have
mechanical characteristics not lower than the above table in
accordance with AHRI-1350.

C3.2.2 Construction

AHU assemblies shall be of rigid double skin fully modular


construction with each section having matching cross sectional
dimensions and same construction type. All individual components
and sections shall be assembled using proprietary and approved
fastening techniques. Locking devices shall be used with all
fastenings which are subject to vibration.

Each module shall be supported by rigid galvanised steel post frame


or extruded aluminium alloy framework or other composite material
frame as specified with thermal break design and flush mounted with
dismountable sandwich panel, corrosion resistant treated and
strengthened where necessary to prevent minimum deflection and
drumming even at 2500 Pa differential pressure. The post frame and
corner pieces shall be fixed together to provide strength equal to
welding. The removal of the side panel shall not affect the structural
integrity of the unit.

The construction of the unit shall be such that the inner surface of the
unit is thermally broken from the outside surface without any cold
bridge formed. The frame member and corner piece shall be filled
with injected foam insulation or other approved insulation.

The double skin or sandwich panel shall be no less than 50 mm thick


with injected expanded polyurethane foam insulation or other
approved insulation encapsulated by epoxy or approved coated
finishing solid sheet steel. Non-hydroscopic sealing shall be provided
between the panel and the framework. The width of the frame
member & corner piece shall be the same as the thickness of the panel.

The whole construction shall be hygienically designed and the


internal surface shall be smooth to avoid any framework protrusion
inside the casing.

Casing material shall not be less than the thickness as shown in Table
C3.2.2 unless otherwise specified in the Particular Specification.

Table C3.2.2 Minimum material thickness for AHU casing

Component Minimum material thickness (mm)


Casing framework 2.0
Cooling coil casing 1.6
Panel for polyurethane 0.8
insulation (each face)
Other 1.2
Section C3 AC_GS
Page 3 of 34 2017 Edition
For sections with UV equipment installed, the casing material of the
internal surface shall be aluminium alloy, stainless steel 304 or better.

C3.2.3 Fan

All fans shall be backward curved centrifugal fans, double inlet,


double width, or single inlet, single width unless alternative
requirement is specified in the particular specification and/or
equipment schedule. All fans shall be mounted together with their
motors on a galvanised steel base frame isolated from the main casing
by means of 98% efficient spring vibration isolators. The vibration
isolators shall have a minimum deflection of 25 mm.

The fan discharge shall be isolated from the casing by a flexible


connection. Fan shall be direct driven or driven by at least two-belt
arrangement for motor rated higher than 4kW. Selection of fan and
motor shall be at their peak operating efficiency. Fan motor shall be
supplied and installed by the AHU manufacturer unless otherwise
specified.

C3.2.4 Access Doors

These shall generally be as detailed for acoustically treated doors


described in the relevant content of Section C8. They shall also meet
with the insulation requirements stated in the relevant content of
Sections B11 & C11. The access doors shall be no less than 400 mm
wide and vertically sized for the full height of the unit or no less than
400 mm wide by no less than 1550 mm high where the unit height
exceeds 1900 mm. Quick access doors shall be provided for filter
section, coil section, transfer section, humidifying section, damper
section, etc. Heavy duty double hinges and two quick release
fasteners shall be provided for all quick access doors.

Where return or fresh air ductwork connects to air handling units,


access to the filters shall be through side access panels at the filter
chambers.

C3.2.5 Access Sections

Access section shall be provided between heating and cooling coils to


allow air blasting or steam blasting of coils for cleaning and/or
sterilising purposes. Adequate access must be provided both
upstream and downstream of coils to facilitate cleaning and sterilising.

C3.2.6 Anti-Corrosion Treatment

For outdoor or other specified applications, all metal surfaces must be


properly treated and suitably painted. Galvanised sheet metal finish
is not acceptable. All external metallic surfaces of the units shall be
painted with two coats of undercoat, and two coats of anti-corrosion
epoxy based paint with each layer dry film thickness of 150 microns;

Section C3 AC_GS
Page 4 of 34 2017 Edition
or other approved finishing applied in the factory. Field painting after
the installation is not accepted. Finishing coating shall be non-toxic.
For indoor applications, all metal surfaces shall be suitably painted
with anti-corrosion paint.

C3.2.7 Thermal and Acoustic Insulation

The unit shall be cold bridge free without sweating as per the
specified Thermal Bridging Factor TB2 Class BS EN1886:2007.
Thermal insulation shall be expanded polyurethane foam or other
approved material meeting the thermal transmittance factor T2 Class
to BS EN 1886:2007. The insulation shall provide a high degree of
noise attenuation.

Thermal insulation shall be securely fixed to or built into all sections


of plant and equipment handling heated or cooled air. Thermal and/or
acoustic insulation characteristics and fixings shall be in accordance
with Sections B11 & C11 and B8 & C8.

Special surface protection shall be provided as specified to avoid


damage in sections having walk-in access. Adequate lighting
completed with door operated switch equipped at the factory shall be
provided for AHUs with handling capacity greater than 5 m3/s.

C3.2.8 Air Filters

The filter section shall be provided by the air handling unit


manufacturer or specialist manufacturer of filter holding frame
approved by the Supervising Officer. The construction of filter
section shall comply with the requirements of Clause C3.2.2 and shall
ensure that there will not be bypass of un-filtered air. The filter
section consisting of the filter elements and the filter fixing frames
must have a positive means of sealing off the unfiltered air by-passing
the filter elements.

Intermediate bag filter or HEPA filter with 50 mm thick permanent


washable pre-filter shall be provided as specified. HEPA filter and
bag filter cartridges shall be mounted on non-corrosive aluminium or
stainless steel tightness proof holding frame for side service or front
release depending on the restriction of access. Neoprene gaskets shall
be provided along the contact surfaces of the filter element and the
holding frame. Filter cartridges shall be clamped against the slide
rails with spring type clamping devices.

Each individual filter section in the AHU shall be completed with a


dedicated pair of copper tuber pressure tapings, adequately sealed for
filed connection of differential pressure sensor. Each individual filter
section shall also be connected to a dedicated manometer mounted on
outside for local indication.

Sections B1 and C1 shall also be referred for the quantity of spare


filters required, construction of filter holding frames, type-test

Section C3 AC_GS
Page 5 of 34 2017 Edition
certificates requirement and the standards of various types of air
filters.

The filter section shall not be located closer than 500 mm to any
electric heaters or water heating battery.

The following air filters shall be provided in accordance with the


application of the air handling systems or as specified: -

Table C3.2.8 (1) Pre-filter


Arrestance % (A)
Application
BS EN 779:2012
For use where grease or moisture is 80 > A 65
prevalent
General ventilation system suitable for 90 > A 80
sport halls, swimming pools, ice rinks,
garages, plant rooms, laundries
General ventilation system suitable for A 90
office, auditoria, law courts, TV
studios, hall and lobby, kitchens,
station concourses, etc.

Table C3.2.8 (2) Intermediate filters


Efficiency % (E)
Application BS 3928:1969 (or EN
779:2012)
General ventilation system for church, 80 > E 60
hotel
General ventilation systems suitable 90 > E 80
for foyer, dressing room, bar/lounge,
restaurant, library, office, building
society, department store,
supermarket, airport
General ventilation system suitable for 95 > E 90
museum/art gallery, computer room
General ventilation system suitable for E 95
hospital, research laboratory

Table C3.2.8 (3) High efficiency and HEPA filter


Efficiency % (E)
Application BS 3928:1969 (or
EUROVENT 4/4 & 4/5)
Special ventilation systems for 99.999 > E 95
hospital, clean room, research
laboratory

Section C3 AC_GS
Page 6 of 34 2017 Edition
Special air by-pass prevention devices and testing facilities with the
following components and requirements shall be provided by the A/C
Contractor where specified in the Particular Specification.

(a) Volumetric flow meters to measure leakage flow rates;

(b) Hand-pump;

(c) Connection for external compressed air system (max. 1.1 bar);

(d) Pressure gauge for hand-pump and external system;

(e) Connection tube linking the testing device and the tightness
proof frame;

(f) Throttle valve; and

(g) A test groove shall be provided on the filter seat of the holding
frame of each filter element with a testing port for the
connection to the above portable tightness testing device.

C3.2.9 Identification Plate

All AHU shall bear the manufacturers nameplate giving


manufacturers name, serial and model number, and date of
manufacturing; and an identification plate showing the AHU
equipment number and essential performance data as indicated on the
Equipment Schedule.

C3.2.10 Air Cooling Coils

(a) General

Cooling coils shall be mounted on non-corrosive aluminium or


stainless steel slide rails. Coil sections shall be arranged to
provide removal of coils from the access side of the section.
Cooling coil casing shall equip with flanged ends drilled and
corrosion treated to receive counter flanges on connecting
ductwork or other associated equipment.

Cooling coils shall utilise the full unit available cross sectional
area. Cooling coils shall be constructed from one of the
following combinations:-

(i) Copper tubes expanded into aluminium fins;


(ii) Copper tubes expanded into copper fins;
(iii) Copper tubes expanded into tinned copper fins; and
(iv) Copper tubes expanded into epoxy coated aluminium
fins.

Section C3 AC_GS
Page 7 of 34 2017 Edition
Tube thickness shall not be less than 0.4 mm. Fin thickness
shall not be less than 0.13 mm with suitable fin spacing.

(b) The resistance to airflow through a coil section shall not


exceed 125 Pa taking into account the wet air condition. The
face velocity of airflow shall not exceed 2.5 m/s. for primary
air handling unit, the face velocity shall not exceed 2.2 m/s.

(c) Access doors with air seals shall be provided on both the
upstream and downstream of the cooling coils.

(d) Cooling coils shall be factory tested and certified to at least


one and a half times the working pressure.

(e) The number of rows of coil for primary air handling unit and
other air handling units shall be optimised. Detail calculations
to determine the number of rows required to meet the
performance with safety margin shall be submitted for
Supervising Officers approval.

(f) All coil capacities, pressure drops and selection procedures


shall be rated in accordance with AHRI 410:2001.

C3.2.11 Drain Pan

(a) Drain pan shall be made of insulated 1.2 mm thick AISI 304
stainless steel. Water shall not be carried over from a cooling
coil into the remainder of the system and an eliminator section
shall be provided, wherever necessary or indicated. The
eliminator shall be readily removable for cleaning.

(b) The drain pan serving the cooling coil shall be extended or a
separate tray be provided to collect water from the eliminator.
Drain pan shall be sloped towards a bottom drain connection
and pipework shall be installed from each connection to the
nearest sump or gully. The drain pan shall be accessible for
cleaning and disinfecting without the coil having to be
removed.

(c) The drain pipework shall include a water trap of minimum 50


mm deep depends on the maximum fan pressure at the rated
speed to prevent entry or exit of air to or from the system. On
stacked coil, intermediate drain troughs shall be provided. All
drain pans shall be adequately insulated with durable, non-
smell and non-peeling under cooling/heating and air flow
design conditions. Sealing devices shall be provided at tops
and bottoms of coils to minimise air by-pass and water carry-
over.

Section C3 AC_GS
Page 8 of 34 2017 Edition
C3.2.12 Chilled Water Connections to Cooling Coils

The flow and return connections and headers shall be made of heavy
gauge seamless flanged copper tube or steel tube with external
coating. Provision shall be made for thermal expansion of the tubes,
for effective venting of the coils and their connections and for the
draining of the headers and tubes.

Coil connections shall be arranged so as to enable same side


connections to the flow and return pipework, and to have the supply
and return connections to headers to give counter flow of air and
water. Equal flow of water shall be through all the tubes in the coils.

(a) Up to and including 50 mm bore connections may be made


using ground-in spherical seated unions. Pipework of 65 mm
bore and above shall be connected using flanged joints.
Isolating valves shall be provided on flow and return
connections and arranged so as to facilitate easy removal of
the coils.

(b) For the connection between the coil header and the external
G.I. or black steel pipe work, suitable fitting/device or
methodology approved by the Supervising Officer to prevent
galvanic corrosion effect of different pipe materials jointing
together shall be provided.

C3.2.13 Hot Water Air Heating Coils

(a) General

The construction of casing coil mounting method and access


door requirements are same as air cooling coils.

(b) The heating coil shall be constructed from one of the following
types: -

(i) Copper tubes expanded into aluminium fins;

(ii) Copper tubes expanded into copper fins;

(iii) Copper tubes expanded into tinned copper fins; and

(iv) Copper tubes expanded into epoxy coated aluminium


fins.

(c) The performance of heating coils shall be as specified and the


method of testing for rating of the coils shall be in accordance
with BS 5141-2:1977 or AHRI 410:2001; or

(d) Coils connection shall be same as for cooling coils.

Section C3 AC_GS
Page 9 of 34 2017 Edition
C3.2.14 Electric Type Air Heaters

(a) Electric air heaters shall consist of a number of sheathed


heating elements of the enclosed type mounted in a sheet steel
casing. The elements shall be so installed that they can be
removed for cleaning or renewal without dismantling
ductwork. The surface temperature of the elements shall not
exceed 400 oC when measured in an air flow of 2.5 m/s at
ambient temperature. A high temperature limit cut-out device
with hand reset button shall be incorporated such that the limit
device sensor is nearest to and above the heating elements
which are energised by the first control step. The device shall
operate within two minutes at a temperature of 68.5 oC.

(b) The control of electric air heaters, except for remote boosters,
shall be interlocked with the fan motor starters and an air flow
control of the pressure or sail switch type so that the heaters
cannot operate unless the fan is running.

(c) Electric air heaters which are installed as boosters in branch


ducts remote from the fans shall have an air flow control of the
pressure or sail switch type which shall isolate the heating
elements from the electricity supply in the event of the failure
of air flow.

(d) The number of elements in the heater shall be the same as or a


multiple of the number of steps in the controller, or using
modulating power controller alternatively. All heaters and
heater sections of more than 3 kW loading shall be balanced
over 3-phases and the complete heater bank shall be arranged
for balanced operation on a 3-phase 4-wire system.

(e) The connections from each element shall be taken to a readily


accessible terminal box arranged for conduit entry. Each
heater section shall be separately fused and the neutral point of
all 3-phase star-connected sections shall be brought out to a
link in the terminal box. Near hot areas the wiring insulation
shall be of a quality suitable for the maximum working
temperature.

(f) The total resistance of the heaters to airflow shall not exceed
15 Pa and the face velocity shall not exceed 6 m/s.

Note for energy efficiency design: - Heating by hot water from waste
heat reclaim or from heat pump system aiming for high operating
efficiency should be considered.

C3.2.15 Humidification Equipment

Steam humidifiers shall be used. They shall be of the steam injection


type using electric elements/electrodes or be of the evaporative pan

Section C3 AC_GS
Page 10 of 34 2017 Edition
type with a minimum efficiency of 95%. Steam available from a
central plant may also be used.

It shall be possible to isolate the electrical supply from the


elements/electrodes and they shall be arranged to facilitate removal
for maintenance and replacement. Electric heating elements shall
incorporate a high temperature cut-out and shall be interlocked to
break the electrical circuit on low water level. Steam injection
distribution pipes shall be provided for condensate return and be so
designed and installed that free moisture is not carried over into the
air stream. Steam generating equipment, other than remote central
plant, shall be an integral part of a purpose-made humidifying unit
and shall incorporate automatic water-level control, overflow
protection and drain connections. Automatic intermittent or
continuous blowdown shall be incorporated as appropriate.

The evaporative pan type humidifier shall be positioned so that it is


not affected by the radiant heat from heater batteries.

C3.2.16 Additional Modular Sections

Additional modular sections shall be provided with ease for the


accommodation of ultra-violet steriliser, heat wheel or other devices
as specified for the improvement of air quality and energy efficiency.

C3.3 AXIAL FLOW FANS

C3.3.1 Axial flow fans shall be of either the single-stage type or the multi-
stage contra-rotating type with each impeller mounted on an
independent motor.

C3.3.2 Fans shall be tested for air performance and sound ratings in
accordance with ANSI/AMCA Standards 210-07 and 300-14, ISO
5801:2007/Cor 1:2008 or equivalent recognised standards as
approved by the Supervising Officer.

C3.3.3 Casing shall be rigidly constructed of mild steel stiffened and braced
to obviate drumming and vibration. Cast iron or fabricated steel feet
shall be provided where necessary for bolting to the base or supports.
Inlet and outlet ducts shall terminate in flanged rings for easy removal.

C3.3.4 The length of the duct casing shall be greater than the length of the
fan(s) and motor(s) in order that the complete section may be
removed without disturbing adjacent ductwork.

C3.3.5 Electrical connections to the motor(s) shall be through an external


terminal box secured to the casing.

C3.3.6 Impellers shall be of galvanised steel or aluminium alloy; the blades


shall be secured to the hub or the blades and the hub shall be formed
in one piece. The hub shall be keyed to a substantial mild steel shaft

Section C3 AC_GS
Page 11 of 34 2017 Edition
carried in two bearings and the whole statically balanced. Unless
otherwise indicated blades shall be of aerofoil section.

C3.3.7 Where axial flow fans are driven by a motor external to the fan casing
the requirements of the relevant content in Sections B7 & C7 for
pulleys and for V-belt drives and guards shall be met. An access door
of adequate size to facilitate inspection, cleaning and other
maintenance shall be provided.

C3.3.8 Axial flow fans of the bifurcated type shall be used on application for
greasy gases, hot gases or vapours. Motors shall be out of the air-
stream and shall normally be placed between the two halves of the
bifurcated casing in the external air. The motor and the bearings shall
be suitable for operation at the temperature they may experience. The
bifurcated section containing the motor shall be mounted vertically in
order to maximise convection air flow over the motor.

C3.3.9 Special design multi vanes to reduce turbulence and increase fan
efficiency shall be provided as specified in the Particular
Specification.

C3.4 CEILING FANS

C3.4.1 Dimensions

The sweep diameter of the units shall be 1200 mm or as otherwise


indicated.

C3.4.2 Capacity

The 1200 mm unit shall be capable of an air delivery of 3.9 m3/s or as


otherwise stated.

C3.4.3 Duty

(a) The unit shall be suitable in all respects for operation under
ambient air conditions of 40C and 95% RH.

(b) The unit shall be suitable for operation in 220 V, 50 Hz single


phase AC mains.

(c) The unit shall be designed for heavy duty commercial and
domestic usage.

(d) The fan shall operate without generating unnecessary noise at


all speeds.

C3.4.4 Motor

(a) The motor shall be a totally enclosed, capacitor run induction


motor, with internal stator and external squirrel cage rotor.

Section C3 AC_GS
Page 12 of 34 2017 Edition
(b) The rotor shall be mounted in grease lubricated ball bearings.

(c) The power factor shall not be less than 0.85 at any speed.

(d) The motor shall be rated for continuous operation under


ambient air conditions of 40C and 95% RH and the
temperature of the windings shall not exceed 50C after
2 hours of continuous operation.

(e) All electrical components, cables, etc. shall conform to the


appropriate specifications or shall be of fully equivalent
quality and capacity.

C3.4.5 Blades

(a) The fan shall be fitted with three blades. "Twisted" blades are
preferred.

(b) The blade assemblies shall consist of blades manufactured


from heavy gauge aluminium securely riveted to steel blade
carriers.

(c) The blade carriers shall be manufactured from mild steel plate
of not less than 3 mm in thickness and of not less than 40 mm
width at the narrowest point, pressed to shape.

(d) Where the blade carriers are twisted to give the required angle
of incidence to the blades, there shall be large radius bends to
prevent stress concentrations in the blade carriers.

(e) Anti-vibration bushes shall be installed between the blades and


blade carriers.

(f) The blade carriers shall be securely fastened to the frame of


the motor by machine screws and spring washers, the whole
assembly shall be designed and constructed to ensure that
there is no possibility of a blade becoming detached during
operation.

C3.4.6 Terminals and Capacitor

(a) The plastic terminal block and capacitor shall be mounted in a


ferrous metal connecting piece, located between the fan and
the down-rod. The leads from the stator windings shall be
connected to the terminal block. An earthing terminal,
consisting of a round head brass, screw and washer, shall be
provided on the connecting piece. All exposed metal parts of
the fan unit shall be connected to this earthing terminal.

(b) The bottom portion of the connecting piece shall be screwed


on to the shaft of the motor. The connecting piece shall be

Section C3 AC_GS
Page 13 of 34 2017 Edition
tightened onto a shoulder formed on the motor shaft. A 4 mm
minimum thickness steel hexagonal lock-nut with lock bracket
underneath shall then be fitted and tightened in position. The
connecting piece shall additionally be screwed in the fully
tightened position by two hardened steel grub screws. These
screws shall engage in shallow depressions drilled in the shaft
after the connecting piece has been tightened in place to ensure
positive locking.

C3.4.7 Down-Rod Assembly

(a) The down-rod assembly shall consist of a down rod and a steel
shaft with a hard rubber roller for suspension of the fan. The
down rod shall be supplied to the length indicated for the job
which shall be measured from the top of the connecting piece
to the centre of the pin in the shackle at the top.

(b) The down-rod shall be manufactured from 12 mm bore


standard mild steel pipe of not less than 3 mm wall thickness,
having an external diameter of approximately 20 mm. It shall
be accurately threaded at one end and shall be screwed into the
top portion of the fan connecting piece (capacitor housing)
from which it shall protrude by a minimum of 2 mm.

(c) It shall be locked in position by two hexagonal steel lock nuts,


having a minimum thickness of 6 mm, tightened onto the
upper machined surface of the fan connecting piece.

(d) The down-rod shall also be locked to the fan connecting piece
by means of a steel split-pin, of not less than 5 mm diameter,
passing through both the fan connecting piece and the down-
rod.

(e) The split-pin holes in the fan connecting piece shall be of such
a diameter that the split-pin is a light push fit there-in. The
matching split-pin holes in the down-rod shall be just
sufficiently large so that the split-pin shall be a light push fit,
when the hole is in its worst position relative to the threading.
All burrs and sharp edges shall be removed from the split-pin
holes both in the fan connecting piece and the down-rod.

(f) The steel suspension shackle shall be welded to the down-rod.


Welding shall be of good quality and to the satisfaction of the
Supervising Officer. The rubber roller shall be mounted on an
8 mm diameter steel clevis pin secured by a split-pin.
(g) The ends of the down-rod shall be rounded off and free from
burrs. There shall be no sharp edges which could cause
damage to the insulation of the wiring.

Section C3 AC_GS
Page 14 of 34 2017 Edition
C3.4.8 Suspension Joints and Threaded Parts

(a) Joints along the suspension rod must be of double-locking


design, i.e. at least two independent positive locking devices
must be employed to prevent a joint from loosening itself.

(b) The maximum clearance between threaded mating parts must


not exceed 1% of their mean diameter.

(c) The direction of rotation of the fan shall be such that all screw
joints tend to be tightened when the fan is in operation.

C3.4.9 Canopies

Two canopies manufactured from plastic or pressed steel sheet shall


be provided and fitted over the upper and lower ends of the down-rod.
They shall be fixed to the down-rod grub screws.

C3.4.10 Balance

(a) All fans shall be fully balanced after assembly, with any
necessary adjustment being made to ensure that they shall not
oscillate due to out-of-balance forces.

(b) All blades shall be given a single identification number, or


letter, permanently stamped on the supply side, with a
corresponding mark stamped on the motor body so that the fan
blades may be reassembled in the correct position.

C3.4.11 Finish

The whole fan shall be finished in high quality stove-enamel, white,


ivory or other colour where required by the Supervising Officer.

C3.4.12 Speed Regulator

(a) Solid-state speed regulator shall be with five speeds and an


"OFF" position in white or ivory or another colour to match
the fan.

(b) An earth terminal shall be provided on the base with an earth


wire permanently connected to the steel core of the choke unit.

(c) The speed regulator shall move smoothly and easily between
positions.

C3.4.13 Inspection

At least one typical unit for those to be supplied for a given Contract
shall be submitted for an acceptance test carried out for the
Supervising Officer before delivery of any quantity is made to the
Contract Site.

Section C3 AC_GS
Page 15 of 34 2017 Edition
The test units shall be provided and collected by the A/C Contractor
at no extra cost to Supervising Officer.

C3.5 CENTRIFUGAL FANS

C3.5.1 Centrifugal fans for high-velocity high-pressure systems as defined


within B&ES Standard DW/144:2013 shall be of the backward
bladed type.

C3.5.2 Centrifugal fans with motor brake power of 5 kW or more shall be of


the backward bladed type having a fan total efficiency not less than
75%.

C3.5.3 Fans shall be tested for air performance and sound ratings in
accordance with ANSI/AMCA Standards 210-07 and 300-14, ISO
5801:2007/Cor 1:2008 or equivalent recognised standards as
approved by the Supervising Officer.

C3.5.4 Fan casings shall be constructed to permit withdrawal of the fan


impeller after fan installation. Fans other than those in factory
constructed air handling units (AHUs) shall be provided with flanged
outlet connections and spigot inlet connections suitable for flexible
joint connections except those for use with negative pressures greater
than 500 Pa in which case inlet connections shall be flanged.

C3.5.5 Except for factory constructed AHUs, all fan casings of 900 mm
diameter or greater shall be provided with removable access panels
which shall incorporate purpose-made air seals. The sizes of access
panels shall be such as to facilitate cleaning and maintenance of the
impeller and shall not be less than 300 mm x300 mm.

C3.5.6 For all kitchen extract ventilation fans an access door, for inspection
and cleaning, shall be fitted to the scroll casing in an accessible
position; it shall be of full width of the impeller. A plugged drain
point shall be fitted at the lowest point of the fan.

C3.5.7 Permanent indication shall be provided to show the correct direction


of rotation of the fan impeller.

C3.5.8 Impellers shall be of galvanised steel or aluminium alloy where


indicated, of riveted or welded construction, with spiders or hubs of
robust design, and shall be capable of running continuously at 10% in
excess of normal speed. Impellers shall be keyed to a substantial
mild steel shaft and the impeller completed with shaft shall be
statically and dynamically balanced and tested for satisfactory
overspeed performance before leaving the makers works.

C3.5.9 Fan shaft shall enable pulley to be mounted at both ends. Shaft
bearings of belt driven single inlet fans shall be truly aligned and
rigidly mounted on a pedestal common to both bearings. Double inlet,

Section C3 AC_GS
Page 16 of 34 2017 Edition
double width fans shall have a pedestal mounted bearing at each side
of the fan. Fan bearings shall be of the ring oiling sleeve type, or the
ball or roller type. Where silence is important the bearing pedestal
shall not be attached to the fan casing, instead ring oiling sleeve type
bearings shall be supplied.

C3.5.10 Centrifugal fans shall be driven by electric motors through V-belt


drives complying with the relevant content in Sections B7 &C7.

C3.5.11 Three phase powered variable flow centrifugal fans where specified
shall be variable speed driven. Variable speed drive shall be in
accordance with Sections B7 & C7 of this General Specification.

C3.6 FAN COIL UNITS

C3.6.1 General

Fan coil units shall comply with the manufacturers own ISO
9001:2008/Corr1:2009quality standard in respect of design and
manufacturing and be type-tested to BS 4856-2:1975 or other
acceptable standards, such as ANSI/AHRI, Euro vent, GB/T, etc., for
thermal volumetric and acoustic performance.

Fans, filters, cooling coils, heating coils, motors, thermal and acoustic
insulation shall comply with the appropriate sections of this General
Specification and the following requirements: -

(a) Fans shall be of the Double Inlet Double Width (DIDW)


forward curved centrifugal or tangential flow types and shall
be of galvanised/mild steel, aluminium, reinforced glass fibres
or rigid plastic material as specified in Particular Specification;

(b) Air filters shall be as indicated in the relevant content of


Section C1 but with an efficiency of not less than 50% when
tested in accordance with BS EN 779:2012;

(c) Motors shall be quiet running and have sleeve or ball bearings
factory lubricated for life. Motor windings and electrical
components shall be impregnated or protected to avoid trouble
from condensation;

(d) The fan motor shall be of the single phase permanent split
capacitor type provided with three speed tapped windings, or
brushless direct current (BLDC) type provided with low noise
pulse width modulation for variable speed control as specified
in the Particular Specification;

(e) BLDC type fan motor shall comply with the following
requirements:

Section C3 AC_GS
Page 17 of 34 2017 Edition
(i) The motor shall consist of hall magnetic pole sensing
elements and be controlled by pulse width modulation
(PWM) of modulating speed with minimum speed
setting;

(ii) The motor shall be totally enclosed in an aluminium


alloy casing, complete with 8-pole (or above) coil,
permanent magnet rotor and permanently lubricated
ball bearing;

(iii) The motor shall be insulated with class B (or above)


with built-in thermal cut-out protection;

(iv) The motor converter and driver shall be enclosed and


complete with overload, start and stall protection;

(v) The motor shall be capable to deliver over a speed


range of 30% to 100% continuously and smoothly; and

(vi) The power factor and total harmonic distortion shall


have performance not less than permanent split
capacitor type.

(f) All fan coil units capacity and air flow rate shall be selected
based on the performance of the units at optimum fan speed;
and

(g) In selecting the fan coil units, allowance shall be made for the
actual resistance imposed on the air flow of the units due to
ducts and grilles. The added resistance is to be applied to all
fan coil units whether shown to have ducts connected or not,
and shall be taken as not less than 30 Pa external to the unit.

C3.6.2 Casings

Casings shall be of G.I. sheet metal with thickness not less than
1.0 mm suitably stiffened to minimise drumming and vibration and
shall be protected against corrosion and, for those exposed to view,
finished i outside with stove primer. All corners shall be rounded off
without sharp edges. Casings shall be lined with material to act as
both thermal and acoustic insulation which shall comply with the
relevant of Sections B11, C11, B8 & C8. Casings shall include space
for pipework connections and valves, and there shall be ready access
to the fan and motor, filter, damper, drain pan, pipework connections
and valves, for maintenance purposes.

The motor and fan shall be mounted on a detachable mounting


chassis that can be removed from the fan coil enclosure as one
assembly (with extended cables) to facilitate fan and motor cleaning.
It shall then also be possible to remove the fan impeller scroll casing
in order to properly clean the fan blades. Fan and motor assemblies
shall be completed with neoprene rubber anti-vibration mountings.

Section C3 AC_GS
Page 18 of 34 2017 Edition
C3.6.3 Coils

(a) Cooling coils shall be minimum two-row and shall include an


air vent cock and drain valve.

(b) The chilled water cooling coil shall be rated in accordance


with AHRI 410:2001 and constructed from seamless copper
tubes mechanically bonded to aluminium fins.

(c) Each coil shall be provided with motorised 2-way solenoid


control valve and isolation valves. Flexible pipe connectors
completed with union joints to facilitate removal of the entire
unit shall be provided. The connector shall be copper or
stainless steel braided polymer tubing limited to 300 mm long
and suitable for the system pressure.

(d) Working pressure of coils shall suit specific requirements.

C3.6.4 Components

(a) All units shall include an easily removable filter capable of


treating the total air volume. Filters shall, unless otherwise
specified, be washable. It shall be supported in a stiff
aluminium/stainless steel detachable frame.

(b) Drain pans shall be made of 1 piece stamped stainless steel


sheet with no weld and protected against corrosion, or made of
plastics or reinforced glass fibre materials insulated with a
minimum of 10 mm thick flexible closed cell elastomeric
insulation. Drain pans shall be large and deep enough to
collect all condensate from the coil, return bends and pipework
connections. The pan shall be removable and have a slight fall
to the drain connection. For units whose loads include a high
proportion of latent cooling the fall to the drain point and the
size of the drain connection shall be adequate to deal with the
condensed moisture.

C3.6.5 Controls, Dampers and Grilles

Fan coil units shall have a combined room temperature sensor


completed with 3-speed controller with heating/cooling mode selector
as required for standalone control, or connected to CCMS as specified.
For BLDC motor, the control logic shall include the modulation of
fan speed and control valve to provide feedback control in response to
the difference between the room temperature and the set point.
Where indicated they shall have connections for both fresh and
recirculated air and shall include a damper which shall be adjustable
to give up to 25% of the fan capacity drawing from the fresh air
source. Outlet grilles shall be capable of adjusting the direction of
airflow without adversely affecting pressure drop. On floor mounted
units, supply grilles shall be on the top of the unit.

Section C3 AC_GS
Page 19 of 34 2017 Edition
C3.6.6 Noise level

The noise data provided shall include an octave band analysis of the
sound power level of each unit when operating at its full or the stated
design speed.

C3.6.7 Electric Heaters for Fan Coils

Electric heaters shall be of maximum 2 kW capacity of the black heat


sheathed element type, plain or finned, and shall be provided with a
safety cut-out thermostat set to operate at 50 oC.

Sail switch is to be fitted for each heater battery and is to be


connected in series with the safety cut-out thermostat to switch off the
heater in the event of reduced air flow.

The mounting, arrangement and terminals, etc. for Electric Duct


Heaters shall be in accordance with Drawings or other installation
standard approved by the Supervising Officer.

C3.7 CASSETTE TYPE FAN COIL UNITS

C3.7.1 Generally, the cassette fan coil units shall comply with Clause C3.6
of this General Specification.

C3.7.2 The fan coil unit shall be of integrated cassette type which combines
the supply air slot, return air grille, fan, casing, cooling coil, heating
coil or electric heater (if required) into a single unit. No connection
of ductwork is allowed except for fresh air.

C3.7.3 Fan coil units shall be selected at design duty and specified noise
level with fan running at medium speed.

C3.7.4 Remote control unit shall be provided as specified.

C3.7.5 Cooling coil shall be constructed with copper tubes and shall be
arranged horizontally. Tubes shall have brazed copper return bends.
Fins shall have smooth drawn collars of length equal to fin spacing
and mechanically bonded to tubes. Fins shall be of the plate type,
corrugated to ensure maximum air contact. All coils shall have an air
release valve and a drain valve. Working pressure of coil shall be of
a minimum of 1200 kPa and to suit system pressure design.
Connection of water piping shall refer to Clause C3.6.3(c).

C3.7.6 Each fan coil unit shall be provided with a drain pan made of high
grade AISI 316 stainless steel or any corrosion resistant material
complying with relevant fire safety requirements situated beneath the
cooling coil and arranged so that all moisture will collect in and drain
from the pan. Drain pans shall be insulated externally with a
minimum of 25 mm approved type foamed plastic. Each drain pan

Section C3 AC_GS
Page 20 of 34 2017 Edition
shall be fitted with a drain pipe which shall be connected via suitable
runs (correctly laid to fall) to the drainage system. Drain pans shall
have copper male connectors for connection to the condensate drain.
The connector shall be positioned to ensure rapid discharge of
moisture from the pan.

C3.7.7 Built-in condensate pump shall be provided for the removal of


condensate. A water sensing system with low, high and warning
limits shall be provided which actuates the running of condensate
pump at high water limit and trigger the alarm system at warning
level. When water level reaches the warning limit, the sensing
system shall cut off the unit operation. An alarm signal shall be given
locally. The signal shall be connected to CCMS or remote indication
system as specified. Condensate pump shall be designed to run
continuously at some essential areas as specified. The power source
for condensate pump and the associated control system shall be
independent from that of the fan coil unit such that the pump can still
be operated after the units have been switched off.

C3.7.8 The filter media shall be of the washable type and shall be enclosed in
a one-piece formed frame made of stainless steel or any corrosion
resistant material with covers flush mitred and reinforced by a die-
formed inverse bead.

C3.7.9 Fan shall be of the quiet running direct driven centrifugal type with
blades made of aluminium or any corrosion resistant material
mounted to a solid steel shaft. Fan motors shall be of the "split
capacitor" type suitable for single phase electrical supply, or BLDC
type in accordance with Clause C3.6.1(e). The motor shall be
resiliently mounted to the fan tray or scrolls. The motor/fan tray
assembly itself shall also be resiliently mounted to the casing
structure.

C3.7.10 Adjustable louvres for directional airflow shall be provided for supply
air slot in each fan coil unit. Options shall be given to choose from 2-
way, 3-way or 4-way supply air discharge.

C3.8 MIXED FLOW FANS

Mixed flow fan casings shall be rigidly constructed of mild steel, or aluminium
alloy stiffened and braced where necessary to obviate drumming and vibration.
Mounting feet shall be provided where necessary for bolting to a base or
supports. Inlet and outlet shall terminate in flanges to facilitate removal. Stator
vanes shall be of mild steel or aluminium alloy. The unit shall be designed to
facilitate access to the impeller. Where motors are mounted external to casings,
drives and guards shall be provided in accordance with Sections B7 & C7. An
access panel with purpose-made air seal shall be provided in the fan casing; the
access panel shall be sized and so positioned as to facilitate maintenance.

Section C3 AC_GS
Page 21 of 34 2017 Edition
C3.9 MECHANICAL ROOF EXTRACT UNITS

The fans used in roof extract units shall meet with the appropriate requirements
of the preceding content relating to fans generally and in particular to the types
of fans involved. The materials of cowls and bases shall be resistant to weather,
solar radiation and appropriate to the location of the unit and type of fan
installed. Casings shall be formed to facilitate a weatherproof fixture to the
building structure. Adequate access to electrical supply terminals and
lubrication points shall be provided by means of hinged cowls or otherwise as
appropriate. Back-draught dampers and/or fire release dampers shall be
provided where indicated. Bird entry preventive guards of not greater than 25
mm mesh shall be provided as an integral part of the unit.

C3.10 PROPELLER FANS

Impellers shall be of steel or aluminium; the blades shall be fastened to the hub
or the blades and hub shall be formed in one piece. The bearings may be ball,
roller, or sleeve type. Propeller fans may be ring mounted, diaphragm mounted
or diaphragm mounted in a casing, as indicated.

The tip speed of propeller fans shall, unless otherwise indicated, not exceed 20
m/s. All ring mounted propeller fans which are exposed, i.e. not installed within
a ductwork or other enclosure, shall be adequately protected by safety guards.

C3.11 PROTECTIVELY COATED FANS AND FANS FOR CORROSIVE OR


HAZARDOUS APPLICATIONS

Where fans are required to handle toxic, corrosive, flammable, explosive or high
temperature gases, the materials and form of construction shall be selected and
suit the particular application. Protectively coated fans shall meet with the
appropriate requirements of the previous content relating to fans generally and
to particular types of fans; the form of protection shall be as indicated. Where a
protective coatings is required for use with corrosive gases, the coating shall
cover all parts of the complete fan, motor and casing assembly which will be in
contact with the corrosive gases. No fan shall be installed if the protective
coating has been damaged in any way. Impellers shall be of coated steel,
stainless steel, aluminium or fire-proof plastic as indicated.

Where fans are installed in a potentially explosive atmosphere, the EU ATEX


100a directive shall be complied.

C3.12 ROTARY FANS (WALL OR CEILING MOUNTED)

C3.12.1 Capacity

The unit shall be capable of an air delivery of not less than 1.1 m3/s.

C3.12.2 Dimension

Section C3 AC_GS
Page 22 of 34 2017 Edition
The blade sweep diameter of the unit shall be 400 mm.

C3.12.3 Duty

(a) The unit shall be suitable in all respects for operation in


ambient air conditions of 35C and 95% RH.

(b) The unit shall be suitable for operation on 220 V, 50 Hz, single
phase AC supply.

(c) The fan shall not require periodic lubrication.

C3.12.4 Construction

(a) These units shall be of deluxe and pleasing appearance with


smooth safe edges and of "easy-to-disassemble" design for
cleaning. Units not considered of suitable appearance may be
rejected by the Supervising Officer.

(b) The fan shall have high quality aluminium or plastic blades.

(c) The fan shall be fully balanced after assembly.

(d) The blades shall be enclosed by a high quality chromium


plated metal wire-mesh metal guard. The gap in between the
guard wires shall not be greater than 15 mm at any point.

(e) The fan shall be provided with rotary mechanism for a


rotational sweep of 360 when mounted on the ceiling for
rotary ceiling fan or for a swing of 150o when mounted on a
wall or column for rotary wall fan.

(f) The whole unit shall be finished to manufacturers standard


light colour or as otherwise approved by the Supervising
Officer.

C3.12.5 Electrical

(a) All electrical components, cables, etc. shall conform to the


appropriate standards and specifications stipulated in Sections
B7 & C7.

(b) All exposed metal parts of the unit shall be suitably earthed via
the 3 core flexible cable.
(c) The fan shall be provided with speed regulator and be capable
of being switched on and off by a remote 5A DP switch.

(d) The fan shall be provided with an adequate length of 0.75 mm2
3 cores PVC insulated and sheathed flexible cable and
connected to the associated socket outlet. Where provided but
not fixed, the cable provided shall be 2 m in length.

Section C3 AC_GS
Page 23 of 34 2017 Edition
C3.12.6 Inspection

As Clause C3.4.13.

C3.13 IN-LINE CENTRIFUGAL FANS

Fans shall be rigidly constructed and fabricated from heavy gauge galvanised
sheet. Fan housings shall have flange on the suction and discharge side for
connection of flexible joints and ducting. Impellers shall be made of galvanised
steel or aluminium, single inlet backward inclined or forward curved centrifugal
type. Removable access panels with purpose made air seal shall be provided
with sufficient size to permit easy access to all internal components. Motors
shall be completed with permanently lubricated ball bearings and being removed
from the fan assembly for maintenance.

C3.14 EC PLUG FANS

C3.14.1 Fans shall be direct driven single inlet centrifugal fans. Fans shall be
backward bladed type unless alternative requirement is specified in
the particular specification and/or equipment schedule. Fan total
efficiency shall not less than 75%.

C3.14.2 Fans shall be tested for air performance and sound ratings in
accordance with ANSI/AMCA Standards 210-07 and 300-14, ISO
5801:2007/C or 1:2008 or equivalent recognised standards as
approved by the Supervising Officer.

C3.14.3 Fan casings shall be constructed to permit withdrawal of the fan


impeller after fan installation. Fans other than those in factory
constructed air handling units (AHUs) shall be provided with flanged
outlet connections and spigoted inlet connections suitable for flexible
joint connections except those for use with negative pressures greater
than 500 Pa in which case inlet connections shall be flanged.

C3.14.4 Except for factory constructed AHUs, all fan casings of 900 mm
diameter or greater shall be provided with removable access panels
which shall incorporate purpose-made air seals. The sizes of access
panels shall be such as to facilitate cleaning and maintenance of the
impeller and shall not be less than 300 mm x 300 mm.

C3.14.5 Impellers shall be made of aluminium, air foil type with rotation
diffuser mounted on electronically commutated external-rotor motors
with variable speed drives.

C3.15 JET FANS

Fans shall be direct driven and manufactured in unidirectional as standard with


option of fully reversible operation, providing almost same duty in either
direction where specified. Fans shall be constructed of either single nozzle or

Section C3 AC_GS
Page 24 of 34 2017 Edition
multi nozzle type with each impeller mounted on an independent motor. Fan
casings shall be integrated with sound attenuator. Casing materials shall not be
less than 0.8 mm galvanised steel, coated with powder to protect from
atmospheric corrosion. Fans shall be rigidly constructed and correctly
proportioned to allow optimum fan performance. Fan motor assembly shall be
designed for easy maintenance and shall be capable of being slide out without
dismounting the complete attenuator. Impellers shall be of galvanised steel or
aluminium with high efficiency pitch adjustable at unidirectional flow.

C3.16 CONDUCTING FANS

Fans shall consist of 3 to 10 modules of fans in parallel and operate without duct
connection. Each module shall consist of aerodynamically shaped aluminium
alloy housing with built-in guide vanes and rotor unit. Fan casings shall be
made of aluminium alloy and coated with powder. Fan inlets shall be completed
with mild steel wire or rod powdered coated protective screen. Mounting
brackets and legs shall be of powdered coated rigid steel sheet and shall be
installed by means of suspension bolts from ceilings or walls. Mounting legs
shall have at least 8 adjustment angles from horizontal to vertical positions.
Impellers shall be made of aluminium sheet, axial type and dynamically
balanced. Fans shall be compatible for connection with remote controller or
field made control panel for remote on/off and high/low speed operation.

C3.17 TERMINAL AIR CONTROL DEVICES

C3.17.1 General

(a) Terminal units shall be factory fabricated and tested in


accordance with British Standard BS 4954-1:1973, BS 4954-
2:1978, BS 4857-1:1972, BS 4857-2:1978 where appropriate.

(b) Casing of the unit shall be manufactured from galvanised steel


sheet of thickness comply with DW/144:2013.

(c) Noise including in-duct sound power level, which emitted


through the unit casing shall not exceed the value as indicated
and/or as stated in Sections B8 & C8 of this General
Specification.

(d) The entire unit shall be internally lined with thermal and
acoustic insulation in compliance with the relevant content in
Sections B11 & C11 and B8 & C8 enclosed in a galvanised
perforated metal liner. The lining shall be securely fixed and
shall be proof against erosion by the air flow. The acoustic
and thermal insulation shall comply with NFPA-90A:2012,
UL 181:2013 and BS 476-4:1970, BS 476-12:1991, BS 476-
6:1989+A1:2009 & BS 476-7:1997 standards (or the related
content of ISO 1182:2010and the requirements of the FSD.

Section C3 AC_GS
Page 25 of 34 2017 Edition
C3.17.2 Induction Units

(a) Filters, cooling coils, heating coils and thermal and acoustic
insulation shall comply with the appropriate sections of this
General Specification, with the following exceptions or
alternatives: -

Air filters shall be as specified in Clause C3.6.1(b) for fan coil


units.

Unless otherwise indicated, cooling coils and/or heating coils


shall be formed of copper primary surface tubes with
aluminium secondary surfaces.

(b) Casings shall include space for pipework connections and


ductwork as necessary, and there shall be ready access to the
filter, the primary air nozzles and any valves and controls.

(c) Primary air plenums shall be treated with thermal and acoustic
insulation which shall comply with the relevant content of
Sections B11 & C11 and B8 & C8. Units shall be completed
with a suitable device to regulate primary air pressure and air
volume flow rate. Primary air nozzles shall be arranged to
induce an even secondary circulation across the cooling and/or
heating coils. The unit air outlet shall incorporate means of
directional control of air supply where indicated.

(d) Cooling/heating coils shall include an air cock and shall be


effectively sealed to prevent air by-pass around the coil. Drain
pans of cooling coils shall be of a material which is resistant to
corrosion or is protected against corrosion and shall have a
slight fall to a drain connection.

C3.17.3 Single Duct Constant Air Volume (CAV) Terminal Units

(a) Unit shall be constructed in accordance with Clause C3.13.2


where appropriate.

(b) Units shall incorporate a self-acting constant flow rate device.


The pressure drop across the unit at design air volume flow
rate shall not exceed 250 Pa.

C3.17.4 Single Duct Variable Air Volume (VAV) Terminal Units

(a) Unit shall be constructed in accordance with Clause C3.13.2


where appropriate.

(b) Unit shall be rated in accordance with ANSI/ASHARE


Standard 70-2006 and Air Diffusion Council Test Code
1062R4. The performance data shall be certified by a
recognised laboratory approved by the Supervising Officer.
The casing of the VAV terminal unit, re-heater box and multi-

Section C3 AC_GS
Page 26 of 34 2017 Edition
outlet box shall be manufactured from galvanised steel sheet
of thickness comply with DW/144:2013.

(c) Unit shall be of the pressure independent type throughout the


entire range and shall be capable of resetting the air flow to
5% of the nominal air flow regardless of the change in the
system pressure.

(d) The unit shall be capable of being reset to any airflow between
zero and the rated air volume automatically to compensate for
duct pressure fluctuation.

(e) The air velocity sensor shall measure the true velocity across
the inlet of the unit and be unaffected by changes in duct air
temperature and humidity. The sensor shall be field
replaceable without opening the associated ductwork.

(f) The entire package shall be calibrated and factory-set for the
maximum and minimum flow rates as specified but shall be
capable of easy re-adjustment in the field. Each terminal box
shall be provided with factory-calibrated, direct reading air
flow indicator. Separate gauge taps shall be provided for field
re-calibration and commissioning.

(g) The velocity controller and the damper actuator shall be of an


integral unit directly mounted onto the damper shaft. The
actuator shall be capable of operating in the stalled position
without overheating or mechanical damage. Mechanical limit
switch will not be accepted. The damper shall remain in a
fixed position when electrical power source is interrupted.
The control equipment must be easily accessible through an
access door provided with quick-release fasteners.

(h) The damper shall be made of heavy gauge galvanised steel


with peripheral gasket, pivoted in self-lubricating bearing. In
the fully closed position air leakage past the closed damper
shall not exceed 2% of the nominal rating at 250 Pa inlets
static pressure.

(i) VAV terminal unit shall be pneumatic, electronic or DDC


controlled as specified. One thermostat shall be provided for
each VAV terminal unit unless otherwise specified. The
thermostat offered shall match the unit and include
temperature set point and velocity adjustment point located
inside.

The thermostat shall have a calibrated scale showing set point


temperature with a constant approximately 1 oC proportional
band regardless of minimum and maximum velocity settings.
Air flow set point shall be adjusted by screw and voltmeter tap
in the thermostat or by other approved means for both high

Section C3 AC_GS
Page 27 of 34 2017 Edition
and low air volume limits. The location of the thermostat shall
be determined on Site.

(j) The unit shall not be selected at the top of the catalogue range
in order to ensure it meets with the specified room noise level
requirement.

(k) Circular connection spigot of insertion dimensions, with self-


sealing rubber gasket shall be provided at both the inlet and
outlet of the unit. Each multi-outlet section shall be completed
with at least one spare outlet, capped for future use.

(l) Unit shall be completed with a mixing attenuator section


where specified.

The attenuator shall be factory-fitted to the basic unit and of a


length not less than 900 mm. The casing shall be constructed
as the terminal unit, but with acoustic insulation of mineral
wool with a minimum density of 70 kg/m3.

(m) Unit shall be completed with electric heater section where


specified. All sections within one metre of the heating
elements shall be constructed by double skin casing. The
internal insulation shall be lined with minimum 0.7 mm thick
galvanised steel sheet. The heater shall be easily withdrawn
from the casing for servicing and maintenance. Heating
element shall be of the sheathe and black heat type. The
heater shall be controlled by contactor and step controller fully
interlocked with a sail switch and duct type overheat
thermostat with fail safe feature and manual reset. The heating
element shall be switched off when the mean temperature
inside the air duct exceeds 50 oC10% and within 90 seconds
of reaching this temperature.

(n) VAV terminal unit completed with VAV section (air


measuring station, modulation damper with actuator and
controller), re-heater section, attenuator section and supply air
section shall be supplied by the same manufacturer.

C3.17.5 Dual Duct Terminal Units

Dual duct terminal units shall be constructed as single duct CAV unit
and VAV unit and shall incorporate devices for varying the
proportions of hot and cold air and for providing thorough mixing of
the air.

Section C3 AC_GS
Page 28 of 34 2017 Edition
C3.18 GRILLES AND DIFFUSERS

C3.18.1 General

(a) The grilles and diffusers shall be rated in accordance with


ANSI/ASHRAE standard 70-2006 and Air Diffusion Council
Test Code 1062R4.

(b) All grilles and diffusers shall have concealed fixing system
and shall have quick release frame to facilitate cleaning.

(c) All supply grilles and diffusers shall be mounted on substantial


frame and shall be provided with soft rubber or felt joining
ring inserted under the frame to prevent air leakage and the
formation of condensate on the fitting.

(d) All grilles and diffusers shall not be less than the size indicated;
where no size is given they shall be capable of handling the air
flows and distribution indicated without producing
unacceptable air flow noise. The A/C Contractor shall select
the supply air grilles and diffusers to achieve good air
distribution and adequate air movement in the conditioned
space.

(e) In order for the ceiling grilles and diffusers to match with the
false ceiling layout pattern, the actual size of the grilles and
diffusers shall be confirmed by the Supervising Officer before
ordering.

For all grilles and diffusers which are smaller than the ceiling
tile on which they are installed, they shall be located in the
centre of the ceiling tile. The exact location of the ceiling
grilles and diffusers shall be co-ordinated with other services.
The A/C Contractor shall confirm the exact location with the
Supervising Officer before works commence.

Where grilles and diffusers are to be incorporated into false


ceilings before any grilles or diffusers are installed into
ductwork or fan coils, the A/C Contractor shall ensure that the
Building Contractor marks out the ceiling line on the adjacent
plastered walls or columns and also indicates where ceiling tee
bars line up or the ceiling joints occur in order that such datum
can be worked to.

(f) The finishing colour of the grilles and diffusers shall be


approved by the Supervising Officer as different colour may
be specified in different areas. The A/C Contractor shall co-
ordinate with the Building Contractor and other specialist
contractors especially the ceiling and electrical contractor for
the integration of the air diffuser into the ceiling and luminaire
(for light troffer diffuser).

Section C3 AC_GS
Page 29 of 34 2017 Edition
C3.18.2 Grilles

(a) Grilles shall be of steel, aluminium, PVC or as otherwise


indicated. Steel grilles shall be protected against rusting and
supplied in fully finished stove-enamelled or otherwise
specified condition.

(b) Each supply air grille shall have 2 sets of separately adjustable
louvres, 1 set horizontal and 1 set vertical, and shall be
completed with an opposed blade multi-leaf damper.
Alternatively, in lieu of the opposed blade multi-leaf damper a
rhomboidal air controller may be provided; this air controller
shall control both the volume of air passing and the
distribution of air across the grille face. The louvre and the
damper or air controller shall be adjustable from the front of
the grille. For up to 10 grilles, 1 set of tools required for
adjusting the louvre and dampers or air controllers shall be
provided. From eleven to 24 grilles, 2 sets and above 25
grilles, 3 sets of tools shall be provided.

(c) Return air grilles shall have either a single set of louvre or bars
(either vertical or horizontal) or a lattice, egg crate or
expanded metal front.

Each return air grille shall be completed with an opposed blade


multi-leaf damper or a rhomboidal air controller operable from
the front.

Where return air grilles are fitted for fan coil units, they shall
be arranged such that the central core of the grille is hinged
and demountable for access to the filter for cleaning.
Mounting frames for these grilles shall include provision for
fixing the filter in position.

C3.18.3 Diffusers

(a) Diffusers shall be of steel or aluminium. Steel diffusers shall


be protected against rusting and shall be stove enamelled for
finished colour approved by the Supervising Officer.
Diffusers shall incorporate an edge seal; diffusers mounted on
ceilings shall have anti-smudge rings. Pan type diffusers shall
be provided except where cone type diffusers are indicated.

Diffusers shall be provided with volume control dampers of


the iris, flap or sleeve type which shall be adjustable from the
front of the diffuser. Where the length of a vertical duct to a
diffuser is less than twice the diameter of the diffuser an
equalising deflector shall be fitted.

The design of the supply air diffuser shall be capable to induce


adequate air movement and provide the throw to cover the

Section C3 AC_GS
Page 30 of 34 2017 Edition
entire air-conditioning space without causing air turbulence
and cold draft.

(b) Linear diffusers shall be constructed of extruded aluminium


section and include a control damper at the rear of the vanes
giving volume control down to complete shutoff and operated
from the face of the diffuser. Linear diffusers for supply air
shall have adjustable blades to give directional control of air
flow. The linear diffuser shall be capable of maintaining a
horizontal discharge pattern at a turn down ratio down to 20%
of the maximum specified air volume without air dumping.

The linear diffuser shall be completed with factory fabricated


plenum with suitable inlet connection for flexible ductwork.
The plenum and diffuser neck shall be constructed of
galvanised steel sheets internally lined with 25 mm 48 kg/m3
glass cloth faced fibreglass insulation enclosed in galvanised
perforated metal liner.

The insulation shall comply with NFPA-90A:2012, UL


181:2013 and BS 476-4:1970, BS 476-12:1991, BS 476-
6:1989+A1:2009 & BS 476-7:1997 standards ( or related
content of ISO 1182:2010).

Where linear diffusers are mounted in a continuous line there


shall be means of ensuring alignment between consecutive
diffusers and of equalising pressure behind the vanes. The
dummy portion of the diffuser shall be internally covered by a
demountable galvanised metal enclosure to block the view into
the ceiling void from below.

(c) The square face diffuser for VAV system shall be constructed
of aluminium and with large turn down ratio.

Each ceiling mounted square face diffuser shall have a factory


assembled diffuser and an air plenum. The air plenum shall be
provided with dividing plates such that the diffuser back is
divided into an annulus area and a square central area. In the
entry to the diffuser plenum, the flow cross section shall also
be divided into two parts, one part serving as a bypass and the
other equipped with a self contained, weight balance damper.
The damper shall be balanced with a weight in such a way that
the horizontal outlet jet velocity remains nearly constant over a
flow rate range of 100 to 20% of maximum in order to prevent
stagnant area, wide temperature gradient and drop of air jet in
the conditioned area.

(d) The linear slot diffuser shall be constructed of extruded


anodised aluminium, with multiple slots for the required air
flow rate.

Section C3 AC_GS
Page 31 of 34 2017 Edition
Each diffuser shall be completed with a factory fabricated
plenum of the same construction as the linear diffuser.

C3.19 ENERGY EFFICIENCY AND PERFORMANCE

(a) The efficiency of fan and motor used for all air treatment equipment
shall be in accordance with Section C7 of this General Specification
and Section 6.7 under the Building Energy Code.

(b) The type of insulation used shall have optimised thermal conductivity,
and the design of the insulation thickness for pipe, drain pan,
ductwork, panel enclosure, etc. of the air handling equipment shall be
in accordance with Section C11 of this General Specification.

(c) The A/C Contractor shall submit relevant factory test certificates and
field test records for calculation and assessment by the Supervising
Officer.

C3.20 DESICCANT DEHUMIDIFIERS

C3.20.1 Wheel Type Desiccant Dehumidifier

(a) The dehumidifier shall be of the absorption or adsorption type


and completed with rotor, electric or gas type reactivation
heater, process air fan, reactivation fan, process air prefilter,
reactivation air prefilter, control panel and all other accessories
for a complete unit. The heater shall be fitted in a factory built
unit casing.

(b) Rotor shall be impregnated with desiccant such as lithium


chloride, silica gel, aluminium oxide or other specified type.
The desiccant shall be incombustible, resistant to chemicals
and non-dusting. The rotor shall have a service life of
minimum 8 years with non-stop operation. The seals between
the process and reactivation airflows shall be designed to good
standards, and their low frictional properties shall guarantee
long and continuous service life.

(c) The casing of the dehumidifier shall be constructed of sheet


steel with oven-curved enamel coating to minimise corrosion.
Casing shall comply with leakage standard to Eurovent
Document 2/2 1996, Class B and the leakage volume shall be
of maximum 0.81 l/s per cu. metre at 1000 Pa.

(d) A control panel shall be provided for the control of the


dehumidifier. The control panel shall include control mode
switch for switching between manual and humidistat operation.
Indicators for power on, unit running, alarm (for high
temperature cut-out, fan motor overload unit, trip and high
humidity, etc.), reactivation fan running, reactive heater on,

Section C3 AC_GS
Page 32 of 34 2017 Edition
rotor drive motor running, process fan running, humidity
normal, and any other control indication requirements as
specified. There shall also be digital displays for fan speeds,
humidity level, and reactivation temperature readings, etc.

(e) The heater control shall be of multi-step. The dehumidifier


shall be capable of operating with the services conditions as
specified under Clause A3.11 of this General Specification.

(f) The unit shall be capable of local or remote control, and be


completed with interlock control for operation with the
connecting air handling unit. The unit itself shall be
completed with built-in direct digital controller (DDC) for all
control and monitoring functions.

(g) The following safety devices shall be provided as a minimum


requirement: -

- Electric safety interlock to prevent the dehumidifier


from running with the electric control panel open or the
mechanical access panels removed;

- Automatic shutdown in case the control system


detected a fault; and

- Two independent thermostats for the heater shall be


provided to trigger automatic shutdown in accordance
with IEC regulation.

C3.20.2 Liquid Type Desiccant Dehumidifier

(a) The unit shall employ an approved liquid type desiccant as the
dehumidification media.

(b) The unit shall comprise three separate operation sections (i.e.
collection, heat pumping and regeneration).

(c) In the collection operation, liquid desiccant shall be


continually added to the top of a honey comb cellulose
material which shall form a flowing liquid film. The untreated
air (i.e. process air) shall be cooled and dehumidified when
flowing through the liquid desiccant.

(d) The heat pump section shall transfer the heat of the liquid
desiccant absorbed during collection operation to the
regeneration operation.

(e) The liquid desiccant shall be heated in the regeneration section.


The moisture previously collected shall be removed by the
regeneration air stream following the same operation
principles in collection section.

Section C3 AC_GS
Page 33 of 34 2017 Edition
(f) The equipment shall be a single compact unit of weatherproof
design.

C3.21 DOMESTIC EXHAUST FANS

The exhaust fan shall be completed with a safety front grille at suction side and
shall be suitable for installation on wall or window opening. Cord control is not
acceptable.

Electrical operated shutter blades, covered by internal grilles, shall be


overlapped and interlocked for maximum back-draught protection.

Each fan shall be fitted with quiet motor. The shutter mechanism shall be of
quiet and vibration free operation.

C3.22 HEAT PIPE

Heat pipe coils shall be provided for humidity control process of the AHU as
specified and indicated in the drawings. The heat pipe coils shall be installed
into the AHU and tested in the factory.

The heat pipe coil act as a humidity control coil forms a "wrap-around"
configuration which wrap around the chilled water cooling coil inside the AHU,
with one section of the heat pipe coil upstream and one section downstream.
The heat pipe system is being driven entirely by the temperature difference
between the two air steams. There are no moving parts and no external power
required.

The heat pipe coils shall be at least 2 rows and are partially filled with a suitable
working fluid such as R134a or R407C, and hermetically sealed.

Section C3 AC_GS
Page 34 of 34 2017 Edition
SECTION C4

AUTOMATIC CONTROL

C4.1 ELECTRICAL WIRING

Refer to Section C7 for Electrical wiring & cable material specification.

C4.2 AIR COOLER CONTROL

Unless otherwise specified, the output of chilled water cooler batteries shall be
controlled by modulating two or three-way valves having a valve authority as
indicated in the Particular Specification or Drawings.

(a) All valves shall be sized in accordance with the recommendations of the
manufacturer to assure fully modulating operation.

(b) Valves shall be sized on fully open pressure drop equal to the pressure
drop of coil under 120% of design flow.

(c) Control valves smaller than 20mm diameter shall be normally closed,
electrically operated, cage-guided, stainless steel trim, flanged cast-steel
body.

(d) Valve opting pointer shall be provided at each valve actuator for direct
indication of valve opening.

(e) Valve actuators shall be mounted directly on the control valve without
the need for separate linkage and the need for any adjustment of the
actuator stroke. Actuators shall have a manual operation capability.

(f) All valve actuators with valve size over 20 mm diameter shall maintain
its last position for fail-safe operation.

C4.3 AIR HEATER CONTROL

C4.3.1 2 -Way or 3-Way Modulating Valves

(a) Unless otherwise specified, the output of hot water air heater
batteries shall be controlled by modulating valves having an
authority as indicated in the Particular Specification or
Drawings.

(b) All valves shall be sized in accordance with the


recommendations of the manufacturer to assure fully
modulating operation.

(c) Control valves smaller than 20mm diameter shall be normally


closed, electrically operated, cage-guided, stainless steel trim,
flanged cast-steel body.
Section C4 AC_GS
Page 1 of 12 2017 Edition
(d) Valves shall be sized on fully open pressure drop equal to the
pressure drop of coil under 120% of design flow.

(e) Valve opting pointer shall be provided at each valve actuator


for direct indication of valve opening.

(f) A manual override device together with auto/manual switch


and automatic change-over relay shall be provided as the
manual setting facility for the control valve opening and back-
up in case of local controller outage.

(g) Valve actuators shall be mounted directly on the control valve


without the need for separate linkage and the need for any
adjustment of the actuator stroke. Actuators shall have a
manual operation capability.

(h) All valve actuators with valve size over 20 mm diameter shall
maintain its last position.

C4.3.2 Electric Ductwork Heaters

Specifications for the electric ductwork heaters shall be referred to


Clause C3.2.14. They shall also comply with the requirements of the
FSD.

C4.3.3 Differential Pressure Switches

Differential pressure switches shall be able to de-energise the heaters


when the air flow stops.

Differential pressure switches are designed for use only as operating


controls. A/C Contractors are responsible to add devices (safety,
limit controls) or systems (alarm, supervisory systems) to protect
against control failure.

The operating temperature range of the pressure switches shall be


from 40 oC to 75 oC.

The diaphragm housing shall be made of cold rolled steel with zinc
plating.

Sensors shall comply with relevant standards of UL or BS/EN/BSEN


or other international standards.

C4.4 ELECTRICAL/ELECTRONIC (LOCALISED) CONTROL SYSTEM

The systems shall be operated at single phase mains voltage or at extra low
voltage such as 12 V or 24 V as indicated in the Particular Specification.

Section C4 AC_GS
Page 2 of 12 2017 Edition
Where a particular manufacturers system is offered and accepted, the
Installations shall be installed to comply with that manufacturers recommended
technical details and methods of installation.

C4.4.1 Standalone Direct Digital Controllers/Outstation (DDC/O)

Unless otherwise specified, the direct digital controllers shall have


sufficient memory to support its own operating system and databases.

(a) Each controller shall have sufficient memory to support its


own operating system and database including: -

- Control Processes;
- Energy Management Applications;
- Alarm Management;
- Historical / Trend Data for all points;
- Maintenance Support Applications;
- Operator I/O; and
- Manual Override Monitoring.

The memory board shall be expandable to a larger size as


needs grow.

(b) Communication Ports

Each controller shall be equipped with at least two


communication ports for simultaneous operation of multiple
operator I/O devices such as modems, printers, personal
computers, and portable operators terminals.

The controller shall have provisions to allow temporary use of


portable devices without interrupting the normal operation of
the permanently connected modems, printers or network
terminals.

(c) Network Communication

The automation network shall be based on PC industry


standard of Ethernet TCP/IP. The network shall be capable of
operating at a communication speed of 100 Mbps.

Switches shall be provided for manual override on digital and


analogue outputs, to allow the user to manually control the
position of the end device.

(d) Expandability

Each outstation shall be factory pre-wired comprising a factory


fabricated metal enclosure, hinged door with master lock and
name plate holder. The outstation shall be of modular design
Section C4 AC_GS
Page 3 of 12 2017 Edition
with standard function modules or similar to accept plug in
printed circuit cards.

Each outstation shall contain interface hardware modules to


accept a plug-in portable operator terminal (POT) with visual
display and analogue facility to enable commissioning and
fault finding to be achieved.

(e) The direct digital controller shall provide local LED status
indication for each digital input and output. Status indication
shall be visible without opening the panel door.

(f) Real Time Clock (RTC)

The real time clock shall be able to display in the forms of


year, month of the year, day of the month, hour of the day, and
minutes.

(g) Automatic Start After Power Failure

The control station shall be provided with a power fail safe


and restart feature.

An orderly restart controlled from the data processing


controller shall occur on resumption after a power failure
without manual intervention.

There shall be no loss of system memory on power failure.

(h) Battery Backup

Battery shall be able to support the real time clock, programme,


and all volatile memory for a minimum of 72 hours.

When the battery replacement is necessary, the open processor


shall illuminate a "battery low" status LED and shall send an
alarm message to the selected printer or terminals.

(i) Time Scheduling

The following commands shall be able to be time-scheduled


for issue at a later day and time:-

- Start and stop a point;


- Change alarm limits, warning limits or set-point;
- Lock/unlock point reporting or point control;
- Demand limit target setting; and
- Alarm summary.

Separate schedules shall be stored for:-

Section C4 AC_GS
Page 4 of 12 2017 Edition
- Regular weeks;
- Special weeks; and
- Holidays.

After recovery from a power failure, the system shall


determine any time-scheduled commands which should have
been issued during the period that the power was off. These
commands shall automatically be issued.

The system shall allow holidays to be scheduled with a


minimum of one year in advance.

(j) Alarm Management

Each analogue point shall have the following defined:-

- High Alarm Limit;


- High Warning Limit;
- Low Warning Limit;
- Low Alarm Limit; and
- Differential.

When an analogue point goes outside the High Warning or


Low Warning Limit for more than one minute, a user defined
warning message shall be sent to the appropriate alarm printers.

When a binary point goes into alarm, a user defined alarm


message shall be sent to the appropriate alarm printers.

When a point returns to normal, the event shall be recorded in


the printer output.

When the point module is placed in override, an alarm shall be


sent to the output of the printers.

C4.4.2 ACMV Sub-System Controllers

Temperature/humidity/pressure controllers shall have separate zero


and proportional band adjustments. Local display and keypad shall
be provided for viewing and controlling each output. Analogue
output of controllers shall be available with either 0 to 10V or 0/4 to
20 mA DC proportional output, two positions, or any combination.
Controller shall have internal switches for each output to change the
output signal to either direct or reverse. Controller shall be available
with integral electronic circuit for absolute high or low limit control.

Air contamination controllers shall be available in one or two stages.


Controller shall close its contacts to initiate ventilation system when
the air contamination exceeds its set point.

Section C4 AC_GS
Page 5 of 12 2017 Edition
Chilled water reset controller shall have integral reset action to
eliminate sustained system offset and be capable of receiving signals
from chilled water and outdoor air sensors to control chilled water
supply temperature according to an adjustable reset schedule. The
controller shall have an adjustable set point for absolute high limit.
Controller shall have an indicating lamp that will vary in intensity
with the controller output. Controller shall be available with either
proportional or 3-point floating output.

Rate/reset controller shall be of the proportional type with adjustable


integral and derivative actions. The controller shall be field
adjustable for either direct or reverse action and shall be supplied
with a switch to eliminate the integral and derivative functions for
calibration purposes. The output of the controller shall be 0-20V or
0/4 to 20 mA DC. An indicating lamp shall be provided which will
vary in intensity as the output varies.

Constant temperature controller shall be of the proportional type with


integral reset action to eliminate sustained system offset. The
controller shall have capability to adjust the integral reset times.

C4.4.3 Control Panel

The Control Panel shall be installed in the A/C Control Room of the
building at location as shown in the Drawings with a sub-panel, if
required, for monitoring and data logging in location as specified.

The panel shall be constructed with 1.5 mm thick hairline finished


stainless steel sheets c/w all flush galvanised iron (G.I.) supports and
accessories. All the lettering shall be in English and Chinese
characters and to be engraved on the panel. All lettering and
characters shall be approved by the Supervising Officer before
fabrication. The front cover shall be of 2 mm thick hairline finished
stainless steel with sectional recessed hinged cover for easy
inspection and maintenance.

The panel shall include the following: -

(a) Indicating lights, ammeters, gauges, control switches, push


buttons, control wiring and other necessary equipment to
enable remote operation and monitoring of all A/C equipment;

(b) The running and alarm indicating lights for a particular


equipment shall be fitted onto the panel as standard module
blocks; and

(c) An alarm chime shall be provided to sound an alarm condition


when any of the alarm indicating lights is energised. An alarm
mute button shall also be provided to acknowledge the alarm
by the operator. Alarm indicating lights shall remain on until
the conditions causing the alarms are returned to normal state.

Section C4 AC_GS
Page 6 of 12 2017 Edition
C4.4.4 ACMV Sub-System DDC Controller Resident Software Features
Energy Conversation

For full specification of the energy calculation feature of the DDC


controller, refer to Clause C5.41.

C4.4.5 ACMV Sub-System DDC Controller Resident Software Features


Other Features

(a) Power Demand Monitoring / Load Shedding

For full specification of the power demand monitoring / load


shedding feature of the DDC controller, refer to Clause C5.43.

(b) Optimum Start Time

For full specification of optimum start time feature of the DDC


controller, refer to Clause C5.44.

(c) Supply Air Reset

For full specification of supply air reset feature of the DDC


controller, refer to Clause C5.45.

(d) Chilled Water Optimisation (CHO)

For full specification of chilled water optimisation feature of


the DDC controller, refer to Clause C5.46.

C4.4.6 DDC Sensors

All sensors specified in this Clause shall meet with the requirements
in the Guidance Notes for Management of IAQ in Offices and Public
Places and the Guide for Participation in the IAQ Certification
Scheme published by HKSAR Government.

(a) Temperature Sensors

Temperature sensors shall be either of the thermister (NTC)


type with a high linear resistance change versus temperature
change or Platinum (PT1000) to ensure good resolution and
accuracy.

Sensors shall be factory calibrated and shall be connected to


remote controller by means of suitable cables.

Sensors shall not require compensation for cable length etc.

For immersion temperature sensors, sensors shall be provided


with immersion pocket. The sensing range shall be selected
according to its application.

Section C4 AC_GS
Page 7 of 12 2017 Edition
For room / wall mounted temperature sensors, sensors shall
have a connection plate to permit easy removal of the sensor
during decorations etc. The sensing range shall be of 0 C to
40 C. The accuracy shall be within 0.5%. There shall be
option for temperature display at 0.5K interval in the sensors.

For ductwork type temperature sensors, sensors shall have a


separate mounting flange with snap-on connection to permit
sensor adjustment.

For outdoor temperature sensors, the sensing range shall be of


-40 C to 40 C. The accuracy shall be within 0.5%.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(b) Humidity Sensors

Humidity sensors shall be of the capacitance type with


operating range of 5% to 95% and the accuracy shall be within
3% R.H. between 23C and 25C. Sensors shall be suitable
for use on the duty expected.

The sensors shall vary the output voltage with a change in


relative humidity.

Humidity sensors shall be available for room or ductwork


mounting.

Sensors shall be connected to remote controller by means of


suitable cables. Sensors shall not require compensation for
cable length etc.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(c) Absolute Humidity (Dew Point) Sensors

Absolute humidity (dew point) sensors shall utilise an active


element to sense the actual quantity of water vapour per
volume of dry air when the relative humidity is from 12 to 100
percent.

Sensors shall be highly repeatable and change resistance with


a change of moisture content in the air.

Sensors shall be connected to remote controller by means of


suitable cables. Sensors shall not require compensation for
cable length etc.

Accuracy of the sensors shall be within 3% R.H. between


23C and 25C.

Section C4 AC_GS
Page 8 of 12 2017 Edition
All sensors shall comply with relevant standards of UL or
BS/EN/BSEN or other international standards.

(d) Combined Type Humidity and Temperature Sensors

Sensors shall have elements mounted in a common enclosure


and be able to be connected to remote controller by means of
suitable cables.

Sensors shall not require compensation for cable length etc.

Accuracy of the sensors shall be within 3% R.H. between


23C and 25C for temperature and humidity control
respectively.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(e) Differential Pressure Sensors

Differential pressure sensors shall vary the output voltage with


a change in differential pressure.

Sensors shall be connected to the remote controller by means


of suitable cables, and sensors shall not require compensation
for cable length etc.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(f) Carbon Dioxide Sensors

Non-dispersive technology with sensing range of 0 to 2000


ppm shall be used for carbon dioxide sensors.

The accuracy shall be within 5%.

Carbon dioxide sensors shall be available for room or


ductwork mounting.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(g) Carbon Monoxide Sensors

Carbon monoxide sensors shall be factory assembled units,


designed to continuously monitor and indicate the level of
carbon monoxide in parts per million on its meter with 4 mA
to 20 mA or 0V to 10V DC output and to activate the alarm
circuit, alarm horn and warning light when the carbon
monoxide concentration reaches the alarm point and deactivate

Section C4 AC_GS
Page 9 of 12 2017 Edition
the alarms when the carbon monoxide concentration drops
below the alarm point.

The alarm point shall be factory set at 200 ppm and shall be
internally or through CCMS adjustable from 10 to 300 ppm.
Sensor response shall be 90% of maximum reading within 20
seconds with 200 ppm carbon monoxide concentration.

The sensor coverage shall be based on the requirements of the


appropriate regulations but not be less than 500 m2 per one
sensor.

Unit shall be designed for operation with either 24 V DC, or


220 V AC, single phase supply and shall have solid-state
circuitry, terminal strip with contacts for recorder, alarm and
fault outputs, replaceable factory-matched pair of catalytic,
semi-conductor sensors, meter calibrated 0 to 300 ppm,
illuminated ON, PURGE, ALARM ON, FAULT/TEST
switches, momentary ALARM RESET switch and an alarm
horn, all mounted on the units cover or through CCMS to
display.

Unit shall have environment-proof, fibreglass polyester case


with hinged, latched and lockable cover. Alarm light shall be
mounted on the top of the case and conduit connector or
opening and a test gas connector at the bottom of the case.

Sensors should have at least a life time of three years.


Replacement shall consist of replacing the detector head and
filter.

Sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international regulations / standards for
gas monitoring.

(h) Nitrogen Dioxide Sensors

Nitrogen dioxide sensors shall be factory assembled units,


designed to continuously monitor and indicate the level of
nitrogen dioxide in parts per million on its meter with 4 mA to
20 mA or 0V to 10V DC output.

Electrochemical type sensor with resolution of 0.1 ppm shall


be used for the nitrogen dioxide sensors.
The sensing range of 0 to 5 ppm shall be used.

Unit shall have environment-proof, fibreglass polyester case


with hinged, latched and lockable cover. Alarm light shall be
mounted on the top of the case and conduit connector or
opening and a test gas connector at the bottom of the case.

Section C4 AC_GS
Page 10 of 12 2017 Edition
Sensors should have at least a life time of three years.
Replacement shall consist of replacing the detector head and
filter.

Sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international regulations / standards for
gas monitoring.

(i) Air Velocity Sensors

Air velocity sensors shall be capable of linear indication of the


velocity of air in a ductwork from 0 to 15 m/s, and shall vary
its output voltage with a change in air velocity.

Sensors shall have range selection for low velocities.

Accuracy of the air velocity sensors shall be within 1% of the


range.

Sensors shall be connected to the remote controller by means


of suitable cables, and sensors shall not require compensation
for cable length etc.

All sensors shall comply with relevant standards of UL or


BS/EN/BSEN or other international standards.

(j) Contamination Sensors

Contamination sensors shall vary the conductivity as the


degree of gas or smoke concentration changes.

The sensor shall be connected to the remote controller by


means of suitable cables, and sensors shall not require
compensation for cable length etc.

(k) Flow Sensors

Flow sensors shall be of the electromagnetic or ultrasonic type.

Sensors shall be capable of measuring range suitable for the


application.

Electrodes shall be of stainless steel or other approved material


suitable for the liquid to be measured.

Energy saving function for external battery power supply shall


be provided as required.

Complete self diagnostic function of the measurement system


(sensor and converter) shall be provided.

Accuracy of the flow sensors shall be within 1% of the range.

Section C4 AC_GS
Page 11 of 12 2017 Edition
(l) Flow Switches

Flow switches shall be electric and two-position with snap


action.

Operating pressure of the switches shall conform to the


requirement of the Installations and shall not be less than 1000
kPa.

Switches shall be adjustable for sensitivity to flow and the


adjustment range shall include flow valves applicable to the
equipment protected by the flow switches.

C4.4.7 Electric / Electronic Damper Actuators

For full specification of the electric / electronic damper actuator, refer


to Clause C5.52.

C4.4.8 Control Valves

For full specification of the control valve, refer to Clause C5.50.

C4.4.9 Automatic Dampers

For full specification of the automatic damper, refer to Clause C5.51.

C4.4.10 Digital Temperature Display

For full specification of the temperature digital display, see Clause


B4.1.7.

Section C4 AC_GS
Page 12 of 12 2017 Edition
SECTION C5

CENTRAL CONTROL AND MONITORING SYSTEM (CCMS)

C5.1 CCMS ARCHITECTURAL OVERVIEW

The CCMS shall consist of a Server with terminal, keyboard and other necessary
peripherals, User/Operator Workstations if specified, router, gateway and/or
interfacing unit, CCMS Sub-systems to be integrated, General Purpose
Controllers, Unitary Controllers, Analogue/Digital Input and Output devices
such as sensors, actuators, etc. of each CCMS Sub-system interconnected via
Local Area Network, Field Bus and / or Remote Communication.

CCMS Sub-systems that are required in the Particular Specification to be


integrated in the CCMS shall include, but not be limited to, the followings: -

- ACMV Monitoring and Control;


- Electrical System Monitoring;
- Lighting Control;
- Energy Conservation Programmes;
- Emergency Electrical System Monitoring;
- Fire Installation Monitoring;
- Security Installation Monitoring;
- Lift Programme Control and Monitoring;
- Garage CO Monitoring and Control where required;
- Mechanical Pumping and Plumbing Control and Monitoring;
- Normal, Emergency and Preventive Maintenance Notification and works
ordering; and
- IAQ measurement where necessary.

The CCMS shall comply with all the operational requirements as indicated in
the drawings, specifications or point schedule.

The CCMS shall be a distributed system, any single point failure shall not
impair the operation of the whole system.

Each CCMS Sub-system shall be self-contained and be able to continue to


perform all Sub-system control and monitoring functions in the event of failure
of the CCMS server.

Each General Purposes Controller or Unitary Controllers shall have intelligence


and be able to continue to operate all local control functions in the event of
failure of any higher hierarchy control systems.

Section C5 AC_GS
Page 1 of 40 2017 Edition
C5.2 TERMINOLOGY

Operator Workstation is the operators window into a system. While it is


primarily used for the operation of a system, it may be used for configuration
activities. It is not intended to perform direct digital control.

General Purpose Controller/Building Controller is a device for the regulation or


management of a system or component. General Purpose Controller/Building
Controller is a general purpose, field programmable device capable of carrying
out a variety of building automation and control tasks.

Advanced Application Controller is a control device with limited resources


relative to General Purpose Controller/Building Controller. It is intended for
specific applications and supports some degree of programmability.

Application Specific Controller is a controller with limited resources relative to


Advanced Application Controller. It is intended for use in a specific application
and supports limited programmability.

Unitary Controller is a device for controlling or monitoring a single piece of


equipment.

Gateway/Interfacing Unit is a device that connects two or more dissimilar


networks, most likely with different communication protocols permitting
information exchange between them.

Smart Actuator is a simple control device with limited resources and designed for
specific applications.

Smart Sensor is a simple sensing device with very limited resources.

C5.3 RELEVANT STANDARDS

Where applicable standards exist, the products provided shall comply with the
standards etc. of the relevant authorities as stated in Section A2 of this General
Specification or equivalent standard, and the list below where applicable: -

(a) ASHRAE. Standard 135-2012 - A Data Communication Protocol for


Building Automation and Control Networks (BACnet);

(b) International Organization for Standardization ISO/IEC 9075-


9:2008/Corr 1:2010 -Information Technology - Database Languages
SQL Part 9 : Management of External Data (SQL/MED);

(c) ANSI /CEA-709.1-B:2002 - Control Network Protocol Specification


(known as Lontalk);

(d) TIA/EIA 232-F Interface Between Data Terminal Equipment and Data
Circuit Terminating Equipment Employing Serial Binary Data Exchange;

Section C5 AC_GS
Page 2 of 40 2017 Edition
(e) TIA/EIA 485-A (August 2008) - Electrical Characteristics of Generators
and Receivers for use in Balanced Digital Multipoint Systems;

(f) TIA/EIA 568-C.1 (February 2009) - Commercial Building


telecommunications Cabling Standard;

(g) Transmission Control Protocol/Internet Protocol of Defence Advanced


Research Project Agency (TCP/IP);

(h) International Organization for Standardization ISO/IEC 1989:2014-


Information Technology Programming Languages - COBOL; and

(i) International Organization for Standardization ISO/IEC 8802-3:2014


Standard for Ethernet.

C5.4 MANUFACTURING STANDARDS

The system shall be built from standard packages. The estimated amount of
customisations to suit the requirements of the Particular Specification shall be
specified in the tender submission.

All materials and equipment used shall be standard components, regularly


manufactured and not custom designed specifically for the project. All systems
and components shall have been thoroughly tested and proven in actual field use
for at least 6 months and with at least 3 relevant job references locally either
private sector or with government.

The CCMS shall be a fully integrated system of computer-based building


automation. The system shall be modular, permitting expansion by adding
hardware and software without changes in communication or processing
equipment. The CCMS, while "on-line" must be capable of adding, modifying,
deleting points and inter-lock sequences without changes to "hardware" and
field wiring or control devices. These changes shall be input through various
input/output devices incorporated into the CCMS.

All CCMS server and associated devices shall be able to operate properly under
environmental conditions as specified in Clause A3.11. The CCMS Server and
peripheral devices shall not be installed until the operating area is air
conditioned and reasonably free of dust and other contaminants which could
impair their operation.

All controllers cubicles shall be supplied factory pre-wired and terminated for
connection to the field devices.

Controllers electronics shall be solid state, utilising distributed processing


techniques, and of the plug-in circuit board type. Separate fusing shall be
provided for all control voltages.

Construction standards for panels, racks, cabinets and other equipment provided
shall meet with the following minimum standards:-

Section C5 AC_GS
Page 3 of 40 2017 Edition
(a) Racks and panels shall comply with ANSI/EIA-310-D:1992 or
equivalent standard;

(b) Panels shall be made of steel, suitably reinforced and braced so as to


provide flat-surfaced, rigid construction;

(c) Material surfaces shall be free of scale, welding slag and dirt;

(d) Panel surfaces shall be flat and free from waviness;

(e) Stiffness and bracing shall be provided as required;

(f) Handling during installation shall be such that the panels will not suffer
distortion or buckling; and

(g) Cut outs shall be square with consoles to ensure that the controls shall be
installed level and square. Finished cut outs and holes shall be free of
burrs and sharp edges and fitted with rubber grommets to prevent cable
insulation damage.

C5.5 CCMS INTER-NETWORKING STANDARD

The CCMS Server, Workstations shall be inter-connected with Local Area


Network (LAN) or remote communication. Each CCMS Sub-system shall be
connected to the LAN through a gateway, router or remote communications.

The General Purposes Controller, Unitary Controller, Smart Actuator and Smart
Devices of each Sub-system shall be inter-connected with field bus.

The LANs physical and data link layer shall comply with ISO/IEC 8802-3:2014
standard with a minimum speed of 100 Mbps.

The Remote Communications physical layer shall comply with TIA/EIA 232-F
standard.

The field buss physical layer shall comply with TIA/EIA 485-A (August 2008)
standard with a minimum speed of 19200 bps.

The communication protocol of CCMS Server and Workstations with CCMS


Sub-systems shall comply with BACnet Standard. The CCMS Server and
Workstation shall conform to BACnet Operator Workstation (B-OWS) or
Advanced Operator Workstation (B-AOWS).

The CCMS Server and Workstations shall comply with ANSI/ASHRAE


standard 135-2008 - A Data Communication Protocol for Building, Automation
and Control Networks (BACnet) and support BACnet/IP with BTL listed.

The communication protocol of General Purposes Controllers, Unitary


Controllers, Building Controllers, Advanced Application Controllers,

Section C5 AC_GS
Page 4 of 40 2017 Edition
Application Specific Controllers, Smart Devices in field bus shall comply with
either BACnet and BTL listed or LonWork standard.

General Purposes Controllers, Unitary Controllers, Smart Devices in field bus


complying with LonWork standard shall conform to the LonMark
interoperability guidelines.

Building Controllers complying with BACnet shall conform to BACnet


Building Controller (B-BC).

Advanced Application Controller complying with BACnet shall conform to


BACnet Advanced Application Controller (B-BAAC).

Application Specific Controller complying with BACnet shall conform to


BACnet Application Specific Controller (B-ASC).

Smart Actuators complying with BACnet shall conform to BACnet Smart


Actuator (B-SA).

Smart Sensors complying with BACnet shall conform to BACnet Smart Sensor
(B-SS).

C5.6 CCMS CONFIGURATION

The central control monitoring system shall comprise a central and satellite
operator workstation, controllers, Gateway/interfacing unit, communication
network for signal/data transmission among controllers and various field support
hardware to form a true "Distributed Intelligence Techniques".

C5.7 CCMS OPERATOR WORKSTATION

The operator workstation shall be an operators terminal and comprise the


followings: -

- Computer capable to meet the requirement of the CCMS software and


expandability in Clause B5.1.3;
- Mouse and keyboard;
- Minimum 21" monitor;
- Alarm printer capable of handling continuous papers;
- A3 ink/laser printer;
- UPS capable of backup for more than 1 hour of operation for the PC,
monitor, printer as well as other UPS connected equipment; and
- A 16-bit/full duplex audio system c/w speakers.

All equipment, where applicable, should have obtained a Recognition Type


Energy Label under the Energy Efficiency Labelling Scheme of EMSD.

Section C5 AC_GS
Page 5 of 40 2017 Edition
C5.8 UNINTERRUPTED POWER SUPPLY

The CCMS Server, Operator Workstation and all connected peripherals shall be
backed up by an Uninterrupted Power Supply (UPS) against voltage surge and
spike.

In case of power failure, the UPS shall invoke alarms to all operators and supply
power for more than one hour.

In the event that the unit is shut down due to prolonged power failure, CCMS
shall receive input signal from the UPS to trigger the shutdown procedure
automatically. All information contained within the CCMS server and
workstation shall be backed up to hard disk.

Upon restoration of the power supply, the CCMS Server, Operator Workstation
and connected peripherals shall automatically restart, reloading all data
including time and date automatically at high speed. No operator action shall be
necessary for this process.

C5.9 PORTABLE OPERATOR TERMINAL HARDWARE

Portable Operator Terminal (POT) hardware shall meet with the following
requirements: -

- Weight of less than 2 kg;


- Run on rechargeable battery;
- Capable of retrieving and storing information to and from CCMS server
and controllers; and
- Input method can be keyboard, touch screen, track point and/or mouse.

C5.10 DDC CONTROLLER HARDWARE

The Direct Digital Control (DDC) Controller shall include General Purposes
Controller, Unitary Controller, Building Controller, Advanced Application
Controller and Application Specific Controller.

The DDC Controller shall have blinking LEDs to identify malfunction for
speedy replacement without changing or undoing wiring.

Any Analogue/Digital Inputs and Outputs shall be relayed or optically isolated.

The DDC Controller shall be capable of complete standalone operation.

The firmware shall be upgradable through uploading of software.

The EPROM/Flash Ram containing the firmware shall be socketed for easy site
replacement.

Section C5 AC_GS
Page 6 of 40 2017 Edition
RAM and the clock shall be provided with power backup of 72 hours instant
recharged capacitor or 12-hour trickle recharged batteries. The real time clock
shall be automatically synchronised upon system recovery.

The DDC Controller shall be automatically reinitialised upon restart or power


restoration.

The DDC Controller shall provide universal inputs (0-10VDC, 4-20 mA, 100
kOhm, Dry Contact Closure, Voltage Level Transitions, and Pulse Accumulator
Inputs) capable to accept information on any point in the above form with only a
programming command for differentiation between the input types. No
hardware changes shall be required. The Analogue Inputs shall have a
resolution of 50 mV or 0.08 mA and a digital buffer for interrogation. The
Analogue to Digital conversion shall have a minimum resolution of 12 bits. The
pulse accumulator input shall accept pulses at a minimum of 2 per second and
up to 25 MHz.

The DDC Controller shall provide universal outputs (0-10VDC or 4-20 mA),
digital outputs (contact closure for momentary and maintained operation for
devices) and pulse width modulation capable to give information on any point in
the above form with only a programming command for differentiation between
the output types. No hardware changes shall be required. Analogue outputs
shall have a minimum incremental resolution of 1% of the operating range of the
controlled device. Output pulse width shall be selectable between 0.1 and 3200
seconds with a minimum resolution of 0.1 seconds. All contact rating shall have
a minimum of 2 amps of 240VA/C. Manual/Off/Auto switch shall be provided
for each digital output for temporary override control during start-up and service.
An LED shall be provided to indicate the state of each digital output.

C5.11 UNITARY CONTROLLER HARDWARE

The processor speed of Unitary Controller shall be at least 10 MHz with a


minimum of 512 Kbytes RAM.

C5.12 GATEWAY/INTERFACING HARDWARE

The Gateway/Interfacing unit shall basically resemble the hardware of the DDC
Controller without the necessary controllers functional components. The
processor speed shall be at least 16.7 MHz with a minimum of 20 MBytes RAM.
The Gateway, which also acts as a Controller, shall have the same
Analogue/Digital Input and Output points.

The Gateway/Interfacing unit shall have network connection to LAN and field
bus.

The amount of data records for the hardware i.e. binary points and analogy
points before the memory of the DDC controller is full and start losing data is
specified in the Particular Specification.

Section C5 AC_GS
Page 7 of 40 2017 Edition
C5.13 CCMS CENTRAL DATABASE REPOSITORY

A CCMS Central Database Repository shall reside in the CCMS Server.

The database server shall use client/server technology and comply with
Microsoft Open Database Connectivity (ODBC) and support ISO/IEC 9075-
9:2008/Corr 1:2010.

The central database repository shall maintain an image of the network


configuration of every device, controllers, and router on the network. It shall be
able to serve installation, maintenance, monitoring and control applications by
storing the communication attributes of network variables, messages tags and
other system objects.

The central database repository shall support multiple concurrent client


read/write access, allowing installation and maintenance to proceed
independently at any number of workstations, POTs and controllers distributed
around the network.

C5.14 CCMS SOFTWARE - ACCESS CONTROL

The software shall be capable of restricting any operator commands to any point
at any specified device.

There shall be a minimum of 200 System Accounts, each individually


identifiable and each changeable through keyboard entry.

There shall be a minimum of 3 access levels, defined as: -

(a) User - view all applications and acknowledge alarms, but cannot modify
database;

(b) Operator - all privileges except system configuration; and

(c) Administrator - all configuration privileges.

Operator inputs executed under valid system request shall be logged. This
record shall contain the operator command and the time and date of input
execution.

The system shall automatically terminate all operator-input capability that is


previously available by valid system access after a predetermined time from the
execution of the last operators input requiring a valid system access request.

The system shall have a Graphic User Interface for adding, changing or deleting
the system user accounts and assigning the access levels for administrator.

Section C5 AC_GS
Page 8 of 40 2017 Edition
C5.15 CCMS SOFTWARE - INPUT PROCESS

The operator shall be able to select applications based upon the password
clearance. Those applications not available to the operator by the password
clearance shall not be displayed.

The operator shall be able to enter memory changes through a Graphic User
Interface. The inputs shall be checked for accuracy by the CCMS and prompted
for operator review prior to execution. Operator input assistance shall be
provided whenever a command cannot be executed because of operator input
errors.

Where the command requires data such as limits, set point, and time, the value
shall be entered in the same engineering units as the controlled variable.

A Help Mode (prompting) shall prompt the operator through each step showing
the available options.

A Direct Mode shall allow the experienced operator to input, thereby executing
the command with a minimum of keystrokes.

The Edit Mode shall be used for data base generation and update. Data base
modification and generation shall be done while the system is on-line.

An operator input shall not inhibit change-of-state (COS) reporting.

All edit information shall be permanently stored on central database repository.

The system shall be capable of dumping and loading selected or all data base
parameters (such as seasonal limits, programmed start/stop, etc.).

C5.16 CCMS SOFTWARE - INFORMATION ACCESS

The System shall be capable of attaining point status information from any
designated output device with a specified access command. The point status
shall consist of a points identification, numerical value (analogy points) and
associated engineering units, and individual function labels indicating that the
point is locked out/unlocked, on-line/off-line, detected failure of sensor, and is
in the alarm (off-normal)/normal condition.

The output following such a command shall contain the status of a single point,
or all points grouped under that command.

The output following such a command shall also contain the date and the time of
command execution.

C5.17 CCMS SOFTWARE - CHANGE-OF-STATE (COS) AND REPORTING

The CCMS server shall poll the points in all CCMS-Systems and detect any
change in each points status as specified and be able to report this change-of-
state to the operator.
Section C5 AC_GS
Page 9 of 40 2017 Edition
All COS outputs shall contain a descriptor, system formatted point identity ID,
point data, engineering units, and date and time.

The System shall output an alarm message, minimum 256 characters in length,
for each point specified as having an alarm message or maintenance message
capability in the point list. The associated message text shall be printed
immediately after the standard alarm notification printout for the point.

The alarm messages shall not be restricted by word lists or any other pre-coding
method. These messages shall be generated by the operator on-line, using his
choice of text. Composition of any one alarm message shall not restrict the
composition of any subsequent alarm message of text.

Summaries of message content and points assigned to messages shall be displayed


on the operators terminal or printed on command.

The System shall be able to assign a system application or a user defined


application to any point upon a COS detection.

The System shall have the capability of directing the COS output for a point to
an operator station.

Change-of-state reporting shall be provided during the output of operator


requested logs and summaries.

When multiple change-of-states are received, they shall be output and or printed
chronologically.

The administrator shall be able to specify whether a change-of-state requires


acknowledgement or not.

The system shall inhibit the reporting of associated analogy COS upon a CCMS
Sub-system shutdown. Upon restarting of the Sub-system, the analogy alarm
reporting for associated points shall remain inhibited for an operator
predetermined time. If any of these points are still in alarm after the time delay,
they shall report as specified in the point chart.

C5.18 CCMS SOFTWARE - ALARM PROCESSING AND REPORTING

C5.18.1 Alarm Scanning

The Controllers shall continuously scan all points connected to them


and update the Central Database Repository on binary changes of
state and significant analogy changes. The degree of significance of
an analogy change necessary to require database update shall be
assigned from a table in the Central Database Repository through the
operators terminal and downloaded to the appropriate controller.
The system shall compare any change of state or analogy update to
establish parameters and determine if the point is in an alarm
condition. Alarms shall be queued for reporting and under no

Section C5 AC_GS
Page 10 of 40 2017 Edition
circumstances shall any alarm go undetected due to multiple alarms.
A response time of 3 seconds. (or as otherwise specified shall be
provided for the period between alarm detection and reporting for
typical and worst case situations)

C5.18.2 Alarm Levels

(a) General

Alarmable points shall be assigned to one of three levels. The


levels shall be emergency, critical, and maintenance alarms.
The assigning of alarm levels shall be accomplished at point
definition and shall be able to be modified on a per-point basis
at any time through the operators terminal.

(b) Emergency Alarm

Emergency alarms shall be printed on the alarm printer and


initiate an audible alarm. The alarm shall be muted when the
alarm is acknowledged. Emergency alarms shall be reprinted
at a selectable time interval until corrected. The reprinting
shall not re-start the audible alarm.

(c) Critical Alarm

Critical alarms shall be reported in the same manner as


emergency alarms except that the reprinting cycle shall stop on
alarm acknowledgement.

(d) Maintenance Alarm

Maintenance alarms shall be printed as described below, but


shall not actuate the audible alarm. They shall not be reprinted
on a periodic time increment and shall not be required to be
acknowledged.

(e) Returns to Normal

On return to normal, the reprinting cycle on emergency alarms


shall stop. The return to normal message shall be printed for
all three alarm levels.

(f) Alarm Acknowledge

Alarms shall be acknowledged by entering the acknowledge


command. Points in critical or emergency alarms shall be
displayed in the order of detection. An alarm shall be
acknowledged when an affirmative response is received from
the operator.

Section C5 AC_GS
Page 11 of 40 2017 Edition
C5.18.3 Alarm Reporting

Each individual point shall be reported on and the condition for


reporting shall be determined at the time the point is defined and shall
be able to be modified any time thereafter. Conditions for reporting
shall be: -

(a) No report under any circumstance;

(b) Reporting of alarms and returns to normal only;

(c) Reporting of all change of state regardless if the state is an


alarm;

(d) Alarms shall be printed or displayed in English language


including descriptions of the location, system and point, the
status or value, and the alarm condition (for example, high,
low and so forth). The report shall also include time and date;
and

(e) Format of the alarm report shall be configurable through the


report generator.

C5.18.4 Alarm Messages

The system shall be able to provide capability to create and assign to


any point a message to be printed at the time of alarm similar to the
COS alarm message.

C5.18.5 The System shall be able to assign a system application or a user


defined application to any point upon an alarm detection.

C5.18.6 Alarm Recording

A minimum of the last 200 alarms or return to normal messages shall


be kept in storage and displayed or printed on command. The
operator shall be able to select for listing of all alarms, those alarms in
a particular location, alarms in a particular system, or the alarm
history of a particular point. The operator shall also be able to restrict
the summary to those alarms occurring after an operator-selected time
and date. The summary shall include the time and date of occurrence,
the location, system and point descriptor, value or status at the time of
alarm and alarm condition (for example, high, low, return to normal,
etc.). The recording of alarms on specific points shall be able to be
"enabled" or "disabled" on command. A summary of points disabled
for alarm recording shall be provided.

C5.19 CCMS SOFTWARE - EVENT PROCESSING

The system shall provide a Wizard where the operator can define an event
algorithm utilising multiple conditions, arithmetic logic, and Boolean logic for a
particular event.
Section C5 AC_GS
Page 12 of 40 2017 Edition
The algorithms shall consist of a minimum of up to five-level deep logical
statement.

The functions that may be initiated if the conditions are met shall include, but
not be limited to, the following: -

- Initiate a binary command;


- Reset an analogy point to a specified value;
- Reset an analogy point by a specified increment or decrement;
- Change the point access control status (for example, enable, disable,
lockout, off-line);
- Initiate or cancel a trend;
- Change analogy alarm limits;
- Reassign the alarm reporting device;
- Print a report;
- Print an operator defined message; and
- Initiate a user-written programme.

The operator shall be able to display or print a summary of any event defined.

The operator shall be able to "enable" or "disable" specific event algorithms


through the operators terminal and request a summary of disabled algorithms.

C5.20 CCMS SOFTWARE - SCHEDULING

The system shall automatically initiate equipment or system commands based


on a preselected time schedule for those points specified as programmable in the
point list. This time schedule shall provide programme times for each day of the
week (Monday through Sunday) on a per point basis.

The operator shall be capable of entering, on-line changing or deleting


programme times. The programme shall have 1 minute resolution on-line. COS
reporting shall not be inhibited while making on-line changes to programme
parameters.

The System shall provide time schedules for each time programmable point
unless specified otherwise.

Any point not responding to a programme function command shall


automatically generate a change-of-state output as herein before defined.

An additional time programme day shall be provided for holidays. The System
shall be provided with the capacity to handle a minimum of 366 consecutive
holidays.

The start of a holiday programme shall be programmable up to 31 days in


advance.
Section C5 AC_GS
Page 13 of 40 2017 Edition
C5.21 CCMS SOFTWARE - GRAPHIC DISPLAY

The system shall provide graphic filter to import AutoCAD drawing, JPEG
graphic file, Compuserve GIF graphic file, Corel Draw graphic file, Microsoft
Bitmap graphic file, Microsoft PC Paintbrush graphic file, Microsoft Metafile
graphic file, Adobe Photoshop graphic file, HP Graphic Language graphic file,
Postscript graphic file and other common graphic formats for graphic display.

The system shall provide a series of tools which support the creation,
modification, cataloguing, and subsequent display of real-time colour
schematics which shall represent a process, equipment, or geographical areas.

Graphics shall be created via mouse and keyboard selection of graphic library
stored symbols and system profiles. The system shall provide, in addition, the
capability to create custom symbols, system profiles, floor plans, buildings, etc.,
and to store them in the graphic library.

The schematics shall dynamically present the current state and/or values of
operator-selected field or calculated points. These status or values shall be
overlaid at the appropriate location on the schematic.

When the operator calls for the colour graphics tools, a tool box shall
automatically appear on the screen. The tool box shall allow the operator to
select a number of commands. The commands shall include, but not be limited
to, the following: -

- Master Schematic Display;


- Schematic Index Display;
- Direct Access to Schematics by Schematic Number;
- Direct Access to Schematics by Point Acronym;
- Add or Change Schematics Titles and Labels;
- Add or Modify Schematics;
- Add or modify Real-Time Data to Schematics;
- Develop New Schematic Symbols; and
- Return to the Operating System.

The operator shall be able to select desired command by the use of the terminal
keyboard or mouse.

The displaying of the master schematic shall allow the operator to use a
hierarchical method to display areas of increasing scale sequentially. The
master schematic shall be an overview of the entire facility. The schematic shall
be broken up into zones which represent logical areas for display. The operator
shall be able to select a particular zone he wishes to view. The graphic files of
the selected zone shall also be able to be broken up into smaller geographical
areas of larger scale. The number of hierarchical tiers shall not be limited and
the hierarchical selection shall be bi-directional.

Section C5 AC_GS
Page 14 of 40 2017 Edition
Selecting the "index to schematics" command from the tool box shall cause the
first page of the schematic index to appear automatically. The index shall
consist of the schematic number followed by the schematic title. The operator
shall be able to select previewing the schematic in a preview windows. The
operator shall be able to select a schematic display, roll to the next page of the
index, or exit back to the master index.

The direct access to schematics command shall allow the operator to display a
schematic by entering the schematic number or by entering an acronym of a
point on a schematic.

The operator shall be able to create new graphic symbols by calling using
Graphical drawing tools or imported from other format graphic files.

The operator shall be able to assign real-time data to the schematics. The
different types of points shall include, but not be limited to: -

- Start/Stop;
- Start/Stop/Auto;
- Off/High/Low;
- Analogue Inputs;
- Binary Inputs; and
- Calculated Points.

When the schematic is displayed, real-time data shall appear on the screen
automatically. The data shall include analogy values with engineering units and
binary statuses (on, off, open close, etc.). The status of the point shall be
indicated by the colour code. Unless otherwise specified, colour codes shall be
as follows: -

- On/Normal Green;
- Off/Normal Yellow;
- Disabled or Locked Out White; and
- Alarm - flashing Red.

Real-time data shall be automatically updated on the screen at least once a


minute or as stated in the Particular Specification.

The operator shall be able to issue commands by utilising the keyboard or


mouse. Once a schematic is displayed, the operator shall be able to call up an
individual point and a menu shall appear on the page indicating the commands
available for that point. At the same time, additional information on the point
shall appear on the screen. This information shall include the full English
language description of the selected point. Commands shall include, but not be
limited to, the following: -

- Start;
- Stop;

Section C5 AC_GS
Page 15 of 40 2017 Edition
- Auto;
- High;
- Low;
- Change Set point and Alarm Limits;
- Disable;
- Enable;
- Lockout;
- Restore;
- Alarm Message Display;
- Plot graph of totalised or averaged values for the last 24 hour; and
- Initiate Program.

Only those commands applicable to the selected point type shall be displayed in
the menu. The results of the command shall be displayed on the screen when
updated. Commands that are not within the operators security range shall not
be available to the operator.

The operation of the colour graphics tools shall not interfere in any way with the
operation of the rest of the system.

C5.22 CCMS SOFTWARE - ERROR MESSAGES

The system shall report error messages for operator diagnostic and operation
assistance.

C5.23 CCMS SOFTWARE - OPERATORS MESSAGES

Operators shall be able to transmit messages from one operators terminal to


POT or any future additional operators terminal. The message shall be up to 70
characters long. The message shall be able to go to all terminals or be restricted
to a specific terminal.

C5.24 CCMS SOFTWARE - REPORT GENERATOR

A wizard featuring Microsoft Word processing tools for the creation of custom
building reports.

Report can be of any length and shall be able to contain any points for the
CCMS Sub-system.

The report generator shall have access to Arithmetic function, Boolean logic,
String function, Date time function to perform mathematical calculations inside
the body of the report, control the display output of the report, or prompt the
operator for additional information for the report.

Section C5 AC_GS
Page 16 of 40 2017 Edition
C5.25 CCMS SOFTWARE - LOCKOUT SUMMARY

A lockout summary shall be provided which contains the point status of all
points specified by the operator and in the locked out condition.

The system shall be capable of automatically initiating a lockout summary based


on a pre-selected time schedule.
Upon operator request, the System shall output a lockout summary that shall list
only those presently in the locked out condition. In addition, all logs and
summaries shall display a locked out indicator for those points.

Lockout summaries shall indicate on a per-point basis the lock-unlock status of


each point through the use of special characters or flags.

C5.26 CCMS SOFTWARE - ALARM SUMMARY

An alarm summary shall be provided which contains the point status of all
points in the alarm condition.

The system shall be capable of automatically initiating an alarm summary based


on a pre-selected time schedule.

C5.27 CCMS SOFTWARE - MESSAGE AND GRAPHIC SUMMARY

A summary shall be provided which details the contents of any and all messages
within the system.

A summary shall be provided detailing the instruction listing for any and all
dynamic colour graphics.

C5.28 CCMS SOFTWARE - POINT INVOLVEMENT SUMMARY

The system shall provide the capability of displaying or printing all of the
routines application that a particular point is involved in. The point and display
or print selection shall be input by the operator.

C5.29 CCMS SOFTWARE SIGNAL PRIORITY

Alarm signals shall have break-in priority over all other process that may be in
progress. All other processes running shall resume to normal after completion
of the alarm signal. Within the alarm level, all signals shall be successive, non-
interfering in operation with break-in as defined above. All other routines shall
occur on a successive non-interfering basis.

Section C5 AC_GS
Page 17 of 40 2017 Edition
C5.30 CCMS SOFTWARE - SYSTEM LOG

A system log shall be provided which contains the point status of all points
associated with each CCMS Sub-system. This system shall not be limited or
restricted by any hardware grouping. All systems, therefore, shall be of
software groupings only.

The CCMS server shall be capable of automatically initiating system log based
on a pre-selected time schedule.
Selection Log - As designated by the operator the system shall be able to printout
or display full information on the following: -

- A single specified point;


- All points within a specified group;
- All points within units of a similar type;
- All points within a specified building or zone within a building; and
- All points within a CCMS Sub-system.

Status Log the system shall be able to indicate full information on a motor or
other electro-mechanical or control device in the system: -

- Point indication;
- Contact status of the point - On-Off;
- Alarm - Normal status; and
- Operating Mode.

Trend Log the system shall be able to provide a means of producing a printout
of selected points on a periodic time basis. The operator shall also be able to
trend record to a hard disk for later retrieval and print out. Points shall be
capable of being added or deleted and time intervals selected through the
operators terminal. Time intervals shall be able to be assigned from 1 minute to
120 minutes as a minimum. The operator shall be able to list a summary of
points on trend along with the trend interval and current value or status.

C5.31 CCMS SOFTWARE - HISTORICAL PROFILES

The system shall provide the capability for the operator to build historical
profiles through the operators terminal and initiate the profile immediately,
automatically at some future specified time of day and/or automatically on a
time increment. Profile shall be displayed on the operators terminal or printed
as selected by the operator. Any averaged or totalised point shall be able to be
assigned to a profile. Multiple profiles shall be able to be defined and multiple
points assigned to a single profile. Unless otherwise indicated, minimum profile
formatting shall be as follows: -

- Last 12 Months, by Month or accounting period;


- Last 30 Days, by Day;
- Last 24 Hours, by Hour;
Section C5 AC_GS
Page 18 of 40 2017 Edition
- Last Hour, by Five Minute Intervals;
- Last Ten Minutes, by Minute;
- Hourly-to-Hour for Today;
- Day-by-Day for Current Accounting Period;
- Total/Average for Today, so far;
- Total/Average for Last Accounting Period;
- Total/Average for Year-to-Date;
- Total/Average for Hour, so far; and
- Total/Average for Last Ten Minutes Only.

The accounting period shall be defined by the operator through the operators
terminal.
The operator shall be able to obtain a summary of defined profiles on the
operators terminal or on the printer as selected by the operator.

C5.32 CCMS SOFTWARE - PREDICTOR GENERATOR

The system shall provide a wizard to extrapolate historical data. The data shall
be stored in files in the following format: -

- Last 12 Months, by Month;


- Last 30 Days, by Day;
- Last 24 Hours, by Hour;
- Last Hour, by 5 Minute Increments; and
- Last 10 Minutes, by Minute.

The operator shall be able to obtain extrapolated data up to one-half the time
increment of the historical data. For example, if the operator selects historical
data composed of the last hour in five minute increments, it shall be possible to
extrapolate the data up to one half hour. The operator shall be able to request
extrapolated data for any time period within the allowable time increment.

The operator shall also be able to select the degree of curve fit up to degree 4.
The data shall be displayed or printed on the printer by operator request.

The data shall include the point descriptor, current value, current time and date,
historical values, extrapolated value and in the case of a graphic plot request, the
ordinate, abscissa and curve. The curve shall include the historical data and the
extrapolated data out to the maximum. The ordinate shall be defined as a value
range and the abscissa shall be scaled in proportion to the display data.

C5.33 CCMS SOFTWARE - PREVENTIVE MAINTENANCE

C5.33.1 General

Section C5 AC_GS
Page 19 of 40 2017 Edition
The system shall be provided where required in the Particular
Specification. It shall provide a comprehensive preventive
maintenance application which shall allow the operator to schedule
preventive maintenance on any item regardless of whether the item is
monitored by the CCMS.

C5.33.2 Maintenance Point Definition

The system shall allow the operator to define items to be scheduled


for preventive maintenance through a graphic user interface. The
definition process shall be interactive similar to the definition of
monitored points. The operator shall be prompted to input the
following data to define a maintenance point: -

- Location of the item to be maintained;


- Item description;
- Task to be performed;
- Maintenance point acronym consisting of building, item
description and number, location, trade, service interval;
- Acronym of monitored point accumulating run-time; and
- Maintenance remarks.

C5.33.3 The data shall be displayed for verification before final definition.
The operator shall be able to display on the operators terminal or
print on the printer the defined point data. The data shall be able to
be modified or deleted through the operators terminal at any time.

C5.33.4 The maintenance data shall be stored in the CCMS Central Database
Repository.

C5.33.5 Maintenance Schedule

The system shall schedule preventive maintenance based on the last


date serviced, the service interval accumulated run-time of the
equipment (if applicable), and assigned priority. The system shall
assign a priority level to the maintenance point when scheduled. The
initial priority of the point shall be level four. On the maintenance
due date the priority shall change to level three. If the point is not
updated after the due date with a new last service date, within the
number of days defined as the notification interval, the priority shall
change to level two. If not updated by an additional notification
interval the priority shall be changed to level one. If a maintenance
point has an assigned run-time limit either the point shall be
rescheduled on reaching the run-time limit or a choice offered to the
operator to decide whether maintenance should take place
immediately or on the regular calendar schedule. The option shall be
selected by the operator at maintenance point definition.

Section C5 AC_GS
Page 20 of 40 2017 Edition
C5.33.6 Service Update

The system shall provide a command to enter the new date last
serviced whenever maintenance of a point is completed. The system
shall request the maintenance point acronym and the date serviced.
The scheduler shall then calculate a new service date.

C5.33.7 Maintenance Points Summary

The system shall provide a summary of all maintenance points within


each trade category. The summary shall be able to be further
restricted to building, room, service interval, equipment type, or
individual point. The summary shall include all defined parameters.

C5.33.8 Maintenance Worklist

The operator shall be able to obtain on command a printed worklist


for all maintenance points or for an individual trade category. The
worklist shall be able to be restricted to those points due (or overdue)
for maintenance or a listing of all points whether currently due or not.
The operator shall also be able to restrict the list to the number of man
hours available for each trade category. The available hours shall be
input by the operator. The list shall include the acronym, description,
current priority level, date last serviced, due date of next service, and
number of days service is overdue, if any. The list shall be sorted by
priority level. Points within the same area serviced by different trades,
due for servicing at the same time shall be summarised separately as
congruent points.

C5.34 CONTROLLER SOFTWARE PROGRAMMING STANDARD

The General Purpose Controller shall have a Rapid Application Development


(RAD) tool for programming of the controller. The RAD tool shall present a
high-level view of the functionality available by creating a graphical or language
based programming environment into which the user may place high-level
function blocks or program statements and inter-connect them to create the
desired system capability. The programming tools shall take this high-level
representation, and transform it into application code running on the controller.

C5.35 CONTROLLER SOFTWARE - INPUT/OUTPUT PROCESSING

The system shall provide continuous update of input and output values and
conditions. All connected points shall be updated at a minimum of 1 second
intervals.

Analogue to digital conversion, scaling and offset, correction of sensor non-


linearity, sensing no response or failed sensors, and conversion of values to
32 bit floating point format shall be provided.

Section C5 AC_GS
Page 21 of 40 2017 Edition
The system shall be able to assign proper engineering units and status condition
identifiers to all analogy and digital input and outputs.

Proportional Integral Derivative Feedback control for Analogue Input and


Output shall also be provided.

C5.36 CONTROLLER SOFTWARE - DIGITAL RUN-TIME TOTALISING

The system shall provide the capability to totalise the number of hours that any
binary point in the system is in the "on" condition. The point may be a motor,
etc. Every binary point shall be able to be totalised on operator assignment.

The operator shall be able to set limits associated with run-time. The system
shall provide capability to have a limit with every binary point. Limits shall be
set through the operators terminal. The system shall print an alarm when the
run-time of a point reaches the run-time limit. Run-time totals and limits shall
be able to be reset from the operators terminal on command.

The operator shall be able to list a summary of run-time totals and each
associated limit, if any. The summary shall be of all binary points or restricted
to a particular location, system or point. The summary shall also be able to be
restricted to those points that have reached the run-time limit.

C5.37 CONTROLLER SOFTWARE - ANALOGUE TOTALISING/


AVERAGING

Any analogy or calculated point in the system shall be able to be assigned to the
totaliser and/or average programme. The points assigned shall be totalised or
averaged a minimum of once a minute. The following totals and averages for
each point assigned shall be kept in storage: -

- Last 12 Months, by Month;


- Last 30 Days, by Day;
- Last 24 Hours, by Hour;
- Last Hour, by Five Minute Increment; and
- Last Ten Minutes, by Minutes.

C5.38 CONTROLLER SOFTWARE - TIME BASED CONTROL

Any commendable point in the system shall be able to be assigned a specific


command by time of day and day(s) of week through the operators terminal.
The number of commands per point, per day, shall be limited only by the
amount of memory available in the respective controller. The following
commands shall be available: -

- Start;
- Stop;

Section C5 AC_GS
Page 22 of 40 2017 Edition
- Auto;
- Low;
- High;
- Change set point;
- Change high limit; and
- Change low limit.

Points shall be assigned time frame in which the assigned command is valid.
Points shall be able to be assigned different time frame each day of the week
plus a holiday schedule. A means of deleting points from the time schedule by
day(s) and time frame shall be provided.

The system shall provide a time delay between start and within an individual
controller, and the time delay shall be adjustable on per-point basis.

Time schedules shall be able to be down-loaded from CCMS Central Database


Repository to the respective controller for implementation. Loss of
communication with the central computer shall not affect the operation of
downloaded time schedules. Any changes made by a time schedule shall update
the Central Database Repository.

The operator shall be able to list summaries of time schedules on the operators
terminal or printer. The summary shall indicate the point and the various time
windows assigned for that particular day. The summary shall be able to be
restricted to a particular location, system, system type, point type, or point as
well as to those days of the week desired.

A means of scheduling holidays 1 year in advance shall be provided. The


system shall recognise scheduled holidays and run the holiday schedule for that
day or days. The holidays shall be defined through the operators terminal.

A means shall be provided to extend the time of equipment operation in a


particular zone. The extended time shall be initiated from the operators
terminal or from a binary input request from the zone itself. The extension shall
be for 1 day only by default and the system shall automatically use the normal
schedule the next day. The zone, equipment within the zone (motors, etc.) and
the length of the time extension shall be defined through the operators terminal.
A summary of zone parameters and a summary of zones currently operating
under extended time shall be provided.

C5.39 CONTROLLER SOFTWARE - AUTOMATIC SEQUENCE

The system shall be a high level tool to define an automatic sequence algorithm
based on occurrence of specified changes in the status of any binary, analogy, or
calculated point to initiate a controllers command or a user defined programme.
The following changes in status shall be able to generate an automatic sequence:

- Change of binary status from 1 to 0 or 0 to 1;


- Reaching run-time limit;
Section C5 AC_GS
Page 23 of 40 2017 Edition
- High analogy alarm;
- Low analogy alarm; and
- Analogue return to normal.

Each input point in the system shall be able to initiate an automatic sequence
and any number of points shall be able to initiate the same automatic sequence.

Points initiating user defined programme shall pass a number of parameters to


the user defined programme. These parameters shall include the following: -

- Acronym of the point;


- Pointer to the point in the Central Database Repository;
- Current status; and
- Last value.

Automatic sequence shall be assigned to points through the operators terminal.


Assignments shall be able to be modified at any time.

The operator shall be able to request a summary of all automatic sequences with
point assignments.

C5.40 CONTROLLER SOFTWARE - GENERAL POLYNOMIAL CURVE FIT

A programme shall be provided for polynomial curve fitting of factors up to the


ninth order form with operator-entered curve coordinates. The operator shall be
able to enter up to 1000 pairs of coordinates. The programme shall fit the curve
defined by the coordinates to a polynomial of the order requested by the
operator. The resultant parameters shall be used in polynomials in user written
programmes or in the calculation programme.

C5.41 ACMV SUB-SYSTEM CONTROLLER SOFTWARE ENERGY


CALCULATION

C5.41.1 Energy Calculation shall perform the following functions: -

(a) Air Flow Rate

Calculate airflow rate from air flow meter or on differential


pressure in supply and return ductwork.

(b) Liquid Flow

Calculate flow rate from differential pressure across an orifice


or venturi, or from an annubar sensor or Electro-magnetic flow
sensor. Sensor acronym and type shall be input by the
operator.

Section C5 AC_GS
Page 24 of 40 2017 Edition
(c) Fluid Energy Rate

Based on flow and differential temperature.

(d) Zone Cooling Energy and Zone Heating Energy

Calculate total cooling or heating energy in a zone based on


supply and return air dry bulb and either wet bulb or relative
humidity and the volume flow rate of the space.

(e) Electrical Power

Calculate electrical power based on voltage and amperage, or


on pulse meter input.

C5.41.2 The operator shall be able to determine the time increment for
performing calculations on a resolution of 1 minute.

C5.41.3 Calculated points shall be defined through the operators terminal in


the same manner as for sensed points with additional information
requested as required. The calculated point shall appear to the
operator as any real point (with a sensor) and the operator shall be
able to use the acronym of the calculated point in the same manner as
a real point.

C5.42 ACMV SUB-SYSTEM CONTROLLER SOFTWARE - DUTY CYCLE

The operator shall be able to assign through the operators terminal any
controlled load in the system to the duty cycle programme and define associated
parameters. Parameters shall be individually assigned per load. Parameters
shall be at least as follows: -

(a) Acronym of load start/stop point;

(b) Acronym of Space temperature point that will feedback space conditions
to the programme. If no space temperature point exists, this parameter
shall not have to be defined;

(c) The minimum on and off times for the load required for equipment
protection from damages;

(d) The beginning and ending times of the duty cycle periods. Capability of
up to seven unique cycle periods per load shall be provided;

(e) The maximum allowable off time per load individually defined per
period;

(f) The time resolution for cycling within each period. The resolution shall
be, as a minimum, selectable on 1 minute increments between 1 and 120
minutes;

Section C5 AC_GS
Page 25 of 40 2017 Edition
(g) The percentage "off" time within each time resolution. The percentage
shall be selected, as a minimum, on 5% increments between 5 and 95%;
and

(h) The commanded status of the load on a high alarm and the commanded
status of the load on a low alarm of the space temperature feedback.

The operator shall be able to modify any parameter on an individual basis at any
time.

Each load assigned to the duty cycle shall be cycled based on the individual
parameters assigned to it. The load shall be "off" for the percentage of time
defined for each time resolution, but never for more than the maximum "off"
time for any one time. Space temperature alarm shall command the load to its
defined status. In no case shall the load ever be put "on" or "off" for less time
than the minimum "on" or "off" time defined.

The operator shall be able to display or print all the parameters associated with a
load assigned to the duty cycler on request. Summaries shall be able to be
requested for all points or restricted to a particular location or load by operator
choice.

Loads shall be able to be locked out from or restored to the Duty Cycler by the
operator at any time.

C5.43 ACMV SUB-SYSTEM CONTROLLER SOFTWARE POWER


DEMAND MONITORING/LOAD SHEDDING

The operator shall be able to assign through the operators terminal on-line any
controlled load in the system to the load shed programme and define associated
parameters. Parameters shall be individually assigned per load. Parameters
shall be at least as follows: -

(a) Acronym of the load start/stop point;

(b) Acronym of the space temperature point that will feedback space
conditions to the programme. If no space temperature point exists, this
parameter shall not have to be defined;

(c) The minimum on and off times for the load required for equipment
protection from damage;

(d) The kilowatt rating of the load;

(e) The acronym of the electric meter that the load is associated with; and

(f) The priority level of the load. Providing capability of 16 priority levels.

The operator shall be able to modify any load parameter on an individual basis
at any time.

Section C5 AC_GS
Page 26 of 40 2017 Edition
The operator shall be able to display or print all of the parameters associated
with a load assigned to the load shedding programme on request. Summaries
shall be able to be requested for all points, or restricted to a particular location or
load by operator choice.
Demand meters shall be defined by the operator through the operators terminal.
Parameters associated with demand meters are as follows: -

- Acronym of the meter;


- The demand limit to begin shedding loads;
- The demand at which loads shall begin to be restored;
- The number of priority levels associated with the meter; and
- The demand interval length.

The operator shall be able to modify any meter parameters on an individual


basis at any time.

The operator shall be able to display or print all parameters associated with a
particular demand meter on request.

The power demand programme shall operate on a sliding window basis. Each
minute shall be considered to be in the middle of the cycle interval. The
demand data shall be gathered each minute. The data from the last N minutes
(where N equals one-half the interval length) shall then be used to create a best
fit first-degree polynomial curve. The curve shall then be examined at what
would be the end of the interval (N minutes ahead). If this value is greater than
the shed limit, the power demand programme shall calculate the excess load and
initiate load shedding. The shedding shall begin with the lowest priority loads
and shall be governed by the points minimum "on" time, maximum "off" time,
point disability, and status of the space temperature point (if one has been
defined). If the point has not satisfied (continuously) its minimum "on" time, if
the maximum "off" time has already been reached, if the point is disabled, or if
the space temperature point is in alarm, the load initially shall not be shed. If
the power demand programme finds that it has examined all loads in all
priorities and more shedding is still necessary, according to the predicted load, it
shall go back to the lowest level and re-examine the points, this time
overlooking the maximum "off" time criteria. If the power demand programme
finds itself again not able to adequately shed enough load to prevent the
predicted power peak, it shall again go through the loads in order of priority and
disregard the status of space temperature points. If it is still unable to
adequately reduce the load level, the operator shall be informed of the number
of kilowatts still needed to be shed. Under no circumstances shall the system
shed a load if the points minimum "on" time has not been reached or if the
points are disabled.

If at any time after load shedding has been initiated, the system forecasts the end
of cycle consumption to be below the restore limit, the power demand
programme shall begin starting up the loads in order to bring the system back
into the state in which it was operating before the shedding began. Load
restoration shall be performed in reverse order from that observed in the
shedding process. The first group of points to be restored shall consist of those
whose sample area is in alarm. The second group shall be the remainder of the
Section C5 AC_GS
Page 27 of 40 2017 Edition
power demand monitored points that are currently "off" and have met their
minimum "off" time. Under no circumstances shall the power demand
programme restore a point that is either disabled or has not yet satisfied its
minimum "off" time. The starts shall be performed in an efficient manner, each
being delayed by the amount of time specified by the preceding point within the
same controller. When enough load has been restored so that the forecasted
consumption is above the restore limit, the power demand programme shall
discontinue the restoration process.

Points that are both duty cycled and power demand monitored may be shed by
the power demand programme, but shall only be started up by the duty cycler.
If the duty cycler deems it necessary to start such a point, it shall determine
whether the point is off due to load shedding or normal cycling. If the point was
shed and an entire power demand programme interval has not elapsed since the
time of the shed, the duty cycler shall then locate and shed enough other load to
allow the original point to be started, without affecting the total system power
consumption.

A power demand profile shall be available to the operator upon request. The
profile shall be displayed or printed by operator selection. The profile shall
include the demand meter description, the time, date, demand limit, restore limit,
interval length, current demand, highest demand today and time of occurrence,
highest demand yesterday and time of occurrence, highest demand during
current building period with time and date of occurrence, and the highest
demand for the last 11 billing periods by billing period with time and date of
occurrence. Billing periods shall be able to be defined by the operator through
the operators terminal.

C5.44 ACMV SUB-SYSTEM CONTROLLER SOFTWARE - OPTIMUM


START TIME

The optimum start programme shall calculate the latest start time for air
handling units in each operator-defined zone. The calculations shall consider
occupancy time, outdoor temperature, indoor temperature, desired indoor
temperature at occupancy, and the capacity of the air handlers.

The programme shall run at a reschedule interval of no more than five minutes
before the start-up time for all of the optimum start zones. The programme shall
examine each zone at the frequency defined for that zone.

When the programme determines that the optimum start time has been reached,
it shall start all of the air handling units included in the zone definition.

At the zone occupancy time, the system shall record the actual zone temperature
and any deviation from desired temperature. If any unit within the zone was
found to have been off-line between the start-up time and the occupancy time,
the data shall be flagged as invalid.

Optimum start zones shall be defined by the operator through the operators
terminal. Parameters shall include as a minimum the following: -

Section C5 AC_GS
Page 28 of 40 2017 Edition
- Occupancy time for each day of the week;
- Desired temperature at occupancy;
- Acronym of outdoor temperature sensor;
- Acronym of indoor temperature sensor;
- Acronyms of air handlers to be started; and
- Acronym of the zone.

The operator shall be able to modify the parameters at any time. A summary of
the zone parameters shall be available on command. The summary shall be
displayed on the operators terminal or printed on the printer. The summary
shall be of all zones or an individual zone.

An optimum start performance summary shall be available to the operator on


request. The summary shall be able to be displayed on the operators terminal
or printed on the printer. This summary shall detail the conditions presented to
the optimum start programme as well as the results of the optimum start function
for one week. The information, output by zone, shall include the difference
between the target temperature and both the inside and outside air temperatures
at the zone start time, the difference between the target temperature and the
actual room temperature at occupancy time, and the start time measured in
minutes before occupancy. Performance summaries shall be able to be
requested for individual or multiple zones.

C5.45 ACMV SUB-SYSTEM CONTROLLER SOFTWARE - SUPPLY AIR


RESET (SAR)

The SAR programme shall monitor status and adjust the supply air temperature
set point, and shall ensure that space temperature conditions are maintained and
that the space relative humidity upper limit is not exceeded. The system
operator shall be able to define, modify and delete the following parameters: -

- Areas to be enabled/disabled for SAR;


- High and low rest limits; and
- Sampled time interval.

A log shall be provided detailing each parameter associated with supply air reset
area.

C5.46 ACMV SUB-SYSTEM CONTROLLER SOFTWARE - CHILLED


WATER OPTIMISATION (CHO)

The automation system shall include a software programme to perform chilled


water reset, soft loading and chiller sequence. The CHO programme shall
optimise the use of chilled water in either one of the two ways - the chilled
water supply reset shall be based on either maintaining a constant return
temperature or supply sufficient cooling to satisfy zone requirements.

Section C5 AC_GS
Page 29 of 40 2017 Edition
(a) When the CHO programme is based on maintaining a constant chilled
water return temperature, the software shall incrementally adjust the
supply water set point to achieve the desired space conditions. It shall be
possible to individually monitor and control each chilled water loop; or

(b) When the CHO programme is based on supplying sufficient cooling to


satisfy zone requirements, the software shall incrementally adjust the
chilled water set point upwards until at least one zone is requiring
additional cooling.

The system operator shall be able to define, modify and delete the
following parameters:-

- Loops to be enabled/disabled for CHO;


- High and low reset limits;
- Incremental adjustment magnitude;
- Sampled time interval; and
- Sequence patterns based on building load in kW.

A log shall be provided detailing each parameter associated with a chilled


water optimisation loop.

C5.47 ACMV SUB-SYSTEM CONTROLLERS

Temperature/humidity/pressure controllers shall be of the plug-in proportional


type with integrated circuits. Controllers shall be capable of having up to 3
separate outputs. Each shall have separate zero and proportional band
adjustments. Indicating lamps shall be provided for each output which will vary
in intensity to indicate the amount of output. Controllers shall be available with
either 0 to 20V DC proportional output, two-position output, or any combination.
Controller shall have internal switches for each output to change the output
signal to either direct or reverse. Controller shall be available with integral
electronic circuit for absolute high or low limit control.

Air contamination controllers shall be available in one or two stages. Controller


shall close its contacts to initiate ventilation system when the air contamination
exceeds its set point.

Chilled water reset controller shall have integral reset action to eliminate
sustained system offset and be capable of receiving signals from chilled water
and outdoor air sensors to control chilled water supply temperature according to
an adjustable reset schedule. The controller shall have an adjustable set point
for absolute high limit. Controller shall have an indicating lamp that will vary in
intensity with the controller output. Controller shall be available with either
proportional or 3-point floating output.

Rate/reset controller shall be of the proportional type with adjustable integral


and derivative actions. The controller shall be field-adjustable for either direct
or reverse action and shall be supplied with a switch to eliminate the integral
and derivative functions for calibration purposes. The output of the controller
Section C5 AC_GS
Page 30 of 40 2017 Edition
shall be 0-10V DC. An indicating lamp shall be provided which will vary in
intensity as the output varies.

Constant temperature controller shall be of the proportional type with integral


reset action to eliminate sustained system offset. The controller shall have a
switch for selecting long or short integral reset times. Controller shall have an
indicating lamp that will vary in intensity with controller output.

C5.48 ACMV SUB-SYSTEM FIELD DEVICE SMART SENSORS

The smart sensors shall include but not limit to temperature sensors, humidity
sensors, absolute humidity (Dew Point) sensors, combined type humidity and
temperature sensors, differential pressure sensors; air velocity sensors,
contamination, flow sensors, carbon monoxide monitor/alarm sensors, carbon
dioxide sensors and nitrogen dioxide sensors, etc.

Data Sharing

The smart sensors shall be able to provide values upon request.

The performance of smart sensors shall be same as specified in Clause C4.4.6 of


this General Specification.

C5.49 ACMV SUB-SYSTEM FIELD DEVICE SMART ACTUATORS

The smart actuators shall include but not limit to control valves, automatic
damper as well as actuator and VAV box, etc.

Data Sharing

The smart actuators shall be able to provide values upon request and allow
modification of some or all of its control objects by another device.

C5.50 ACMV SUB-SYSTEM FIELD DEVICE - CONTROL VALVES

Valves used in conjunction with a CCMS for control of chilled water shall be of
the modulating type with a turn down ratio of at least 50 to 1. Valve bodies
shall be cast gunmetal, brass cast iron or as otherwise indicated. Seat and inner
valve material shall be brass, stainless steel or as otherwise indicated. Valve
sizes 50 mm and smaller shall be screwed and supplied with union fittings.
Valve sizes 65 mm and larger shall be flanged. Valves shall be of the straight-
through type as required by the sequence or shown on the drawings. Valves
actuator shall be equipped with manual opener to allow manual positioning of
valve in the absence of control power. Valves shall have authority of at least 0.5
(50%) and shall have suitable actuator to close against full pump head. Valve
body shall be rated for differential pressure stroke < 20 mm.

For valves used for fan coil unit, valve body and seat body shall be bronze. The
inner valve and stem material shall be stainless steel. The valve shall be of the

Section C5 AC_GS
Page 31 of 40 2017 Edition
2-way type have authority of 0.5 (50%), with body rated for differential pressure,
actuator closed against full pump head, and stroke < 5 mm.

Valves shall otherwise comply with Sections B9 & C9 of this General


Specification.

Valves schedules for all valves modulations/on-off shall be submitted detailing


the maximum allowed and actual pressure drops, authority, turndown ratio, max.
pressure the actuator will close against and other valve data.

C5.51 ACMV SUB-SYSTEM FIELD DEVICE - AUTOMATIC DAMPERS

Automatic operated dampers for application in conjunction with a CCMS shall


have frames of a minimum of 3.5 mm galvanised steel not less than 50 mm in
width and aerodynamically formed blades of not less than 1.5 mm galvanised
steel sheet. Dampers shall be adequately braced to form a rigid assembly. No
damper shall have blades more than 200 mm wide. Length of blades shall be
not more than 1220 mm. Blades shall be secured to 13 mm diameter zinc plated
axles by zinc plated bolts and nuts. All blade bearings shall be nylon or bronze.
Teflon coated thrust bearings shall be provided at each end of every blade to
minimise torque requirements and insure smooth operation. All blade linkage
hardware shall be constructed of corrosion resistant, zinc plated steel and brass.

For all dampers incorporated as part of a CCMS controlled systems, the control
damper manufacturer shall submit leakage and flow characteristics plus a size
schedule for all controlled dampers.

Supply and exhaust dampers for building systems incorporating a CCMS shall
be of the low leakage types and shall be generally as described below.

C5.51.1 Standard Applications

Dampers shall be of the parallel or opposed blade design (as selected


by the manufacturers application techniques) with replaceable butyl,
spring stainless steel or closed cell neoprene edging. (Reference shall
also be made to Section C2 of this General Specification where
relevant.)

C5.51.2 Low Leakage Applications (Intake, Exhaust & Recirculation


Dampers)

Dampers shall be of the parallel or opposed blade design (as selected


by the manufacturers application techniques). Frames and blades
shall be of 3 mm extruded aluminium. Blades shall be of the single
unit "Pin- Lock" design, 150 mm wide, with the "Pin-Lock" an
integral section within the blade centre axis. Frames shall be of
100 mm extruded aluminium channel and angle, with reinforcing
bosses and groove inserts for vinyl seals. Minimum size dampers
shall have 50 mm by 15 mm aluminium frames. Pivot rods shall be
of 13 mm diameter extruded aluminium, "Pin-Lock" design
interlocking into blade section. Bearings shall be of the "Double-

Section C5 AC_GS
Page 32 of 40 2017 Edition
Sealed" type with Colcon inner bearing on rod riding in Marlon
Polycarbonate outer bearing inserted in frame so that outer bearing
cannot rotate (no metal-to-metal or metal-to-bearing riding surfaces).
Blade linkage hardware shall be installed out of air stream. All
hardware shall be of non-corrosive reinforced material or cadmium
plated. Interconnecting linkage shall have separate Colcon bearing to
eliminate friction in linkage. Dampers shall be of the overlap design
with extruded vinyl seals in both frames and blades for minimum air
leakage. All dampers in excess of 1 m free area shall have reinforced
corners. Curves shall be based on a velocity of 10 m/s. Opposed
blade dampers shall have less than 1/2 of 1% leakage at 0.5 kPa static
pressure. Parallel blade dampers shall have less than 1% leakage at
0.5 kPa static pressure. Parallel blade dampers shall have less than
1% leakage at 0.5 kPa static pressure.

C5.51.3 Two-Position Control Dampers

Dampers shall be sized for minimum pressure drop at the indicated


ductwork size.

C5.51.4 Modulating and Proportioning Dampers

Dampers shall be sized for an effective linear air flow control


characteristic within the angle of rotation and maximum pressure
drops specified.

C5.51.5 Dampers at Louvres

Dampers located immediately adjacent to intake and exhaust louvres


shall be furnished in sizes as indicated because of reduced free area at
louvres.

C5.51.6 Isolation Dampers

Dampers shall provide tight shut-off with negligible leakage, and


shall withstand the applied pressure, velocities and turbulence in the
open position.

C5.51.7 Fire and Smoke Dampers

Fire and Smoke Dampers shall meet all requirements as specified in


Section C2. Dampers shall be of the all metal, low leakage
construction, with metal-to-metal seals at blades and frame, designed
to operate automatically as specified in Section C2.

C5.52 ACMV SUB-SYSTEM FIELD DEVICE - DAMPER ACTUATOR

Actuators shall be of the linear or rotary type for either modulating or two-
positioning control. Actuators shall have a manual opener for power failure.
Control voltage shall be either 24 V DC or 220 V AC as required by the
application, product of clutch, micro-switch shall not be accepted.

Section C5 AC_GS
Page 33 of 40 2017 Edition
C5.53 ACMV CCMS SUB-SYSTEM FIELD DEVICE - VAV BOX CONTROL

C5.53.1 Fan Powered

Unless otherwise specified, a stand-alone control system shall be


provided to individually control each fan powered box as a pressure
independent system.

C5.53.2 Electronic controls consisting of sensors, microprocessor controller


and damper actuator shall be factory mounted. Room sensor shall be
field mounted.

C5.53.3 Each box controller shall communicate individually with the central
processing unit. Should any part or all of the central energy
management system experience downtime, each and all of the boxes
shall maintain room control. Set point of room control shall reside
within the individual room controller.

C5.53.4 Two-way communication to the CCMS Server shall be provided for


setting the following functions: -

(a) Fan operating point - resettable from Server;


(b) Cooling set point - Resettable from central processing unit;
(c) Room Temperature;
(d) Supply ductwork velocity;
(e) Minimum velocity setting - Resettable from Server;
(f) Maximum velocity setting - Resettable from Server;
(g) Night setback command - Resettable from Server; and
(h) Damper position.

C5.53.5 Non-Fan Powered

Similar to above.

C5.54 OTHER CCMS SUB-SYSTEM

The equipment listed below shall be monitored for operation conditions at


intervals not to exceed 30 seconds. However, the typical equipment to be
supervised and the actual requirements are indicated in the Particular
Specification: -

(a) Emergency Generator : On-Off, Fail to Start, Trouble.


(b) Sprinkler Valve : Open-Closed.
(c) Fire Pumps: Unit On-Off, Fail to Start, Trouble.
(d) Domestic Water Pressure : Normal or Low.
(e) Lift or Escalator Failures
Section C5 AC_GS
Page 34 of 40 2017 Edition
C5.55 SCHEDULE OF FUNCTION FOR CCMS

Schedule of Functions monitored and / or controlled by CCMS shall be in


accordance with Code of Practice for Energy Efficiency of Building Services
Installation (2015 edition) and as follows: -

C5.55.1 Chiller/Heating Water Circuit

(a) Chilled/Heating water supply temperature;


(b) Chilled/Heating water return temperature;
(c) Chilled/Heating water flow rate in each main circuit (normal
hour, 24 hrs,);
(d) Chiller/Heating water circuit supply/return pressure;
(e) Building cooling demand (chilled water flow rate, supply
temperature, return temperature);
(f) Energy demand of each floor (chilled water flow rate, supply
temperature, return temperature);
(g) On/off control/status of all motorised on/off valves;
(h) Valve opening control/status of modulating valves;
(i) External enthalpy/dry bulb/RH; and
(j) Plant efficiency (total electrical power/total cooling load)

C5.55.2 Chiller

(a) On/off status;


(b) On/off control;
(c) Trip/fault status;
(d) Open/close status of on/off control valve;
(e) Operating current
(f) Compressor frequency;
(g) Power input;
(h) Water failure alarm;
(i) Evaporator refrigerant pressure/temperature;
(j) Condenser refrigerant pressure/temperature;
(k) Chilled water inlet/outlet temperature;
(l) Heating water inlet/outlet temperature;
(m) Condenser water flow rate;
(n) Chiller water flow rate;
(o) Chilled water set point;
(p) On/off status of each condenser fan;
(q) Trip/fault alarm of each condenser fan;
Section C5 AC_GS
Page 35 of 40 2017 Edition
(r) Local/CCMS selector status;
(s) Cooling capacity (chilled water flow rate, supply temperature,
return temperature);
(t) Heating capacity for heat recovery chillers (heating water flow
rate, supply temperature, return temperature);
(u) Chiller efficiency (cooling capacity/power input);
(v) Refrigeration leakage alarms (2 stage); and
(w) All safety alarms.

C5.55.3 Cooling Tower

(a) On/off status;


(b) On/off control;
(c) Trip/fault status;
(d) Open/close status of on/off control valve;
(e) Open/close control of on/off control valve;
(f) Condensing water inlet/outlet temperature;
(g) For fan with frequency inverter: -
- Running status;
- Trip/fault status;
- Inverter speed control/status; and
- Local/CCMS status.

C5.55.4 Primary/Secondary Chilled Water Pump, Sea Water Pump, Heating


Water Pump

(a) On/off status;


(b) On/off control;
(c) Trip/fault status;
(d) Supply/return pressure;
(e) flow rate;
(f) Supply/return temperature;
(g) 3-phase operating currents;
(h) Power input (kWh);
(i) Water failure alarm;
(j) Local/CCMS selector status; and
(k) For pump with frequency inverter: -
- Running status;
- Trip/fault status;
- Inverter speed control/status; and

Section C5 AC_GS
Page 36 of 40 2017 Edition
- Local/CCMS status.

C5.55.5 Motor Control Centre (MCC)

(a) 3-phase voltage, 3-phase + N current, p.f., THD and kWh of


each incoming cable;
(b) 3-phase voltage, 3-phase + N current and kWh of each outgoing
cable to each chiller, chilled water pumps, heating water pumps,
control circuit;
(c) ON/OFF and trip status of each incoming or outgoing or
interlocking ACB; and
(d) Battery charger failure alarm.

C5.55.6 AHU, PAU

(a) Supply/return air fan on/off status;


(b) Supply/return air fan on/off control;
(c) Trip/fault status;
(d) Local/CCMS status;
(e) Filter clog alarm;
(f) Supply air temperature;
(g) Return air temperature;
(h) Ductwork static pressure for control of fan speed;
(i) Fresh air flow rate;
(j) Outdoor temperature/Enthalpy;
(k) Chilled water valve control;
(l) Chilled water valve position;
(m) Heating water valve control;
(n) Heating water valve position;
(o) Return air damper control;
(p) Return air damper position;
(q) Fresh air damper control;
(r) Fresh air damper position;
(s) Loss of air flow alarm;
(t) Fire trip alarm;
(u) Power input;
(v) CO2 concentration for demand control; and
(w) For AHU/PAU with frequency inverter: -
- Running status;
- Trip/fault status;

Section C5 AC_GS
Page 37 of 40 2017 Edition
- Inverter speed control/status; and
- Local/CCMS status.

C5.55.7 Ventilation fan

(a) Fan On/off status;


(b) Fan Trip/fault status;
(c) Local/CCMS status;
(d) Damper control;
(e) Damper position;
(f) Filter clog (if any);
(g) CO level (for carpark exhaust);
(h) Loss of air flow alarm;
(i) Fire trip alarm;
(j) Power input; and
(k) For fan with frequency inverter: -
- Running status;
- Trip/fault status;
- Inverter speed control/status; and
- Local/CCMS status.

C5.55.8 VAV/CAV boxes

(a) Room temperature;


(b) Room temperature set point;
(c) PIR sensor;
(d) Air flow rate;
(e) Heating water valve (if any) modulating control;
(f) Damper position control/monitoring; and
(g) Time schedule by real-time clock w/battery.

C5.55.9 FCU

(a) On/off control of each FCU;


(b) Room temperature;
(c) Room temperature set point;
(d) Chilled water valve modulating control;
(e) Heating water valve (if any) modulating control;
(f) Ductwork heater (if any) stage control;
(g) 3-position fan speed;

Section C5 AC_GS
Page 38 of 40 2017 Edition
(h) filter clog alarm; and
(i) Power input of group of FCU (department basis).

C5.55.10 Computer Room Air Conditioner

(a) On/off control and status;


(b) Trip/fault status;
(c) Local/CCMS status;
(d) Room temperature;
(e) Room humidity;
(f) Room temperature set point;
(g) Room humidity set point;
(h) Chilled water valve modulating control/status;
(i) Heating water valve (if any) modulating control/status;
(j) Ductwork heater (if any) stage control;
(k) Humidifier (if any) on/off control/status;
(l) filter clog alarm;
(m) Loss of air flow alarm;
(n) Fire trip alarm; and
(o) Power input.

C5.55.11 Gas Tight Damper, Fire Damper, Smoke/Fire Damper

(a) Closure alarm.

C5.55.12 Chilled Water/Heating Water F&E (closed type)

(a) High level alarm;


(b) Low level alarm; and
(c) Pump fault/trip status.

C5.55.13 Water Treatment

(a) On/off status;


(b) Trip/fault status;
(c) Conductivity sensor reading/set point;
(d) Bleed off valve position/control; and
(e) Bleed off flowrate.

C5.55.14 Room Condition Monitoring for Critical Rooms, such as Computer


Room, Network Room, PBX Room, etc.

(a) High temperature alarm;

Section C5 AC_GS
Page 39 of 40 2017 Edition
(b) High humidity alarm;
(c) Room temperature; and
(d) Room humidity.

C5.55.15 Cooling Energy Monitoring

(a) Energy meters reading. The energy meters shall be located at


the main tee-off at each floor for both normal and 24-hours
CHW system.

Section C5 AC_GS
Page 40 of 40 2017 Edition
SECTION C6

CENTRAL REFRIGERATION MACHINE, DIRECT EXPANSION


EVAPORATOR AND HEAT REJECTION PLANT

C6.1 GENERAL

In this section, refrigeration machine may refer to chiller or heat pump.

The refrigeration plant for air conditioning purposes shall generally be of the
mechanical, vapour compression type.

The refrigeration machine shall be factory assembled and tested complete


"packaged" units which may have reciprocating, centrifugal, screw or scroll type
compressors and as specified in the Particular Specification. The testing of the
cooling/heating capacity of the refrigeration machine shall be carried out in
accordance with AHRI Standard 550/590:2012, BS EN 14511-12013to BS EN
14511-42013 or other international recognised standards.

The plant shall include any accessories necessary to ensure continuous and
reliable automatic operation and remote monitoring and control. Power supply
voltage-dip ride-through devices shall be provided to delay the protective shut
down of refrigeration machine. Fast restart to allow the refrigerant machine to
restart and going to a postlude operational mode shall be required for
minimising downtime.

Each unit shall be capable of running continuously at the lowest step of cooling
or heating capacity provided without any adverse effect.

Compressor and motor speeds shall not exceed 50 revolutions per second for
reciprocating type and for screw type. For non-oil-free centrifugal type, the
motor speed shall not exceed 50 revolutions per second and the compressor
speed shall not exceed 250 revolutions per second. For oil-free centrifugal type,
both motor and compressor speed shall not exceed 800 revolutions per second.
Energy efficient motor to optimise the system coefficient of performance shall
be required. The noise level of the refrigeration machine shall comply with the
requirements as specified in the Particular Specification or the relevant
environmental protection ordinances whichever is more stringent. If acoustic
silencer is required in order to achieve the required noise level, it shall be
factory-built and shall not de-rate the machine efficiency and capacity as
specified in the Particular Specification.

For non-oil-free chiller, each compressor shall form a separate oil circuit with its
own oil separator, oil filter and positive lubrication oil safety control circuit
equipped to ensure proper functioning of each compressor and accessories.

All units shall comply, where applicable, with the following codes: ISO
5149:2014, ASHRAE Standard 90.1: 2013, ASHRAE Standard 189.1-2014,
ANSI / ASHRAE Standard 15 -2013 (Packaged with ANSI/ASHRAE 34-2013);
AHRI Standard 550/590:2012 Testing and Ratings; BS EN 14511-1:2013 to BS
EN 14511-4:2013 Testing and Ratings and Code of Practice for Electricity

Section C6 AC_GS
Page 1 of 33 2017 Edition
(Wiring) Regulations and Code of Practice for Energy Efficiency of Building
Services Installation.

Refrigerants adoption for refrigeration and air-conditioning system in


government building projects shall comply with flammability safety
classification in accordance with Clause B6.1 of this General Specification.

Characteristic curves shall show the energy consumption in kilowatts, pressure


drop through the evaporator, chilled or hot water flow rates and temperatures,
condenser fan speeds, etc., for each unit at 25%, 50%, 75% and 100% of full
capacity.

Performance characteristics, Integrated Part Load Value (IPLV) and Non-


standard Part Load Value (NPLV), to shown the performance rating of
refrigeration system while operating at various capacities shall be measured in
accordance with the latest edition of AHRI Standard 550/590:2012.

Sound pressure level characteristic curves shall be in dB measured in


accordance with ANSI/AHRI standard 575:2008 for 25%, 50%, 75% and 100%
of full capacity.

The testing of the cooling/heating capacity of the refrigeration machine shall be


carried out in accordance with AHRI Standard 560:2000, BS EN 14511-1:2013
to BS EN 14511-4:2013 or other international recognised standards.

C6.2 ABSORPTION UNITS

Absorption refrigeration units if required will be fully specified in the Particular


Specification. They are not commonly used for general refrigeration
applications in place of conventional reciprocating, centrifugal or screw types in
Hong Kong due to its less favourable energy performance.

C6.3 COLD STORAGE REFRIGERATION

Independent refrigeration circuits shall be supplied and installed at the cold


storage room and shall comprise an air-cooled refrigeration system with semi-
hermetic reciprocating compressor connected to each room unit cooler. The unit
cooler shall be of the ceiling type, drawn through direct expansion with
distributor, heat exchanger for better efficiency, and electric defrost heaters.
Requirements for cold storage facilities will be fully detailed in the Particular
Specification for specific application. The cold storage refrigeration shall be
factory assembled and tested in accordance with BS 2502:1979, ASHRAE 62.1-
2013 and requirements of the International Association for Cold Storage
Construction (IACSC) and the International Association of Refrigerated
Warehouses.

Section C6 AC_GS
Page 2 of 33 2017 Edition
C6.4 COMPRESSORS, RECIPROCATING TYPE

C6.4.1 Hermetic compressors will be acceptable where either: -

(a) The entire refrigeration system is completed and charged with


refrigerant at the manufacturers works; or

(b) The condensing unit incorporating the hermetic compressor


has a hold charge of refrigerant or inert gas on arrival at Site.

C6.4.2 Crankshafts or eccentric shafts of all open or semi-hermetic


compressors shall be balanced and, if having an input power greater
than 2.25 kW, run in replaceable bearings.

C6.4.3 Pistons greater than 50 mm diameter shall be fitted with either: -

(a) Compression and/or oil control rings; or

(b) A combination of compression rings and a piston ring


specially shaped to act as an oil scraper.

C6.4.4 All open and semi-hermetic compressors having an input power in


excess of 350 kW shall have: -

(a) Removable cylinder liners; and

(b) Side or end covers which will enable servicing or repair of the
unit to be carried out "in-situ".

C6.4.5 Open type compressors shall have a rotary mechanical seal fitted to
the driving shaft which effectively prevents leakage of refrigerant or
oil. Direct coupled type units shall be driven through flexible
coupling units. Compressors with an input power greater than 25.0
kW shall be of a type which will enable the shaft seal to be removed
without moving compressor or motor.

C6.4.6 Open and semi-hermetic compressors of 6.0 kW input power and


above shall have: -

(a) A crankshaft driven oil pump used to force feed lubricant via a
strainer to the main and big end bearings and the shaft seal;

(b) An oil pressure relief valve or bleed device provided between


the oil pump discharge and the crankcase;

(c) Provision for draining oil from the suction manifold into the
crankcase and for venting refrigerant gas (but not oil) in the
opposite direction; and

(d) A crankcase heater arranged to operate while the compressor


is at rest.

Section C6 AC_GS
Page 3 of 33 2017 Edition
C6.4.7 All types of compressor, with the exception of hermetic units or
factory sealed systems, shall have the following fittings provided and
connected: -

(a) Stop valves on refrigerant suction and discharge connections;

(b) Refrigerant pressure gauges, not less than 75 mm diameter and


fitted with means of isolation, on suction and discharge.
Gauges shall have pressure and saturation temperature scales
for the refrigerant being used. Alternatively, gauges with
pressure scale only may be used in conjunction with a
pressure/saturation temperature conversion table fixed nearby;

(c) Refrigerant monitor to display the concentration level of


refrigerant;

(d) Oil pressure gauge, not less than 75 mm diameter, with means
of isolation (compressors with oil pump only);

(e) Crankcase oil level sight glass;

(f) High and low refrigerant pressure safety cut-outs with


adjustable differential pressure set point. Protection settings
shall be pre-set in accordance with manufacturers
recommendations;

(g) Low oil pressure safety cut-out with hand reset (compressors
with oil pump only);

(h) Suction refrigerant strainer; and

(i) All instruments shall be mounted in a neat instrument panel


mounted on the package unit or on a varnished teak frame
mounted panel near to the machine being served and to a
design acceptable to the Supervising Officer.

Alternatively, pressure measurements read from the display panel of


the chiller is acceptable to the Supervising Officer

C6.4.8 All compressors having a refrigeration duty in excess of 35 kW shall


have capacity control by means of cylinder unloading. Compressors
shall be arranged so that they start unloaded.

The hot gas by-pass or injection system of capacity control will not be
accepted.

C6.4.9 All compressors shall be mounted on vibration isolators.

Section C6 AC_GS
Page 4 of 33 2017 Edition
C6.5 COMPRESSORS, CENTRIFUGAL TYPE

C6.5.1 For non-oil-free type centrifugal compressor, the following features


shall be equipped: -

(a) Open type centrifugal compressors shall have a rotary seal


fitted to the driving shaft which effectively prevents leakage of
refrigerant or oil. Open compressors shall be driven through a
flexible coupling of a type which enables the shaft seal to be
removed without moving the compressor or motor.

(b) The lubrication system shall be arranged with an interlock to


ensure adequate oil pressure at all bearings before the
compressor starts and during the "coast down" period. A
replaceable or cleanable filter shall be positioned in the oil
delivery pipe. Where an oil cooler is used, it shall be
thermostatically controlled. A hand reset pressure or flow
switch shall stop the compressor on a lubrication system
failure. The oil sump shall have a thermostatically controlled
electric heater which operates while the compressor is at rest.

(c) The compressor shall have automatic capacity regulation


which will control at any point from 25 to 100% of full duty
by inlet guide vane (for constant motor speed) or inlet guide
vane and variable speed control (for variable motor speed)
without inducing a surge condition. The compressor shall
always start in the unloaded condition.

The hot gas by-pass or injection system of capacity control


will not be accepted.

(d) The motor of a semi-hermetic compressor which is refrigerant


gas cooled shall have in-built protection against inadequate
cooling.

(e) The compressor shall have lubrication oil management system


which will ensure appropriate and sufficient lubrication to the
bearings during the compressor operation and to minimise
refrigerant dilution in the oil. The lubrication oil management
system shall comprise differential oil switch and oil
temperature sensors to perform safety checks and manage the
operation of oil pump and oil heater.

(f) The following fittings shall be provided and connected: -

(i) Refrigerant pressure gauges as Clause C6.4.7(b);

(ii) Oil pressure gauge as Clause C6.4.7(d);

(iii) Oil sump or reserve level sight glass;

(iv) Pressure safety cut-outs as Clause C6.4.7(f);

Section C6 AC_GS
Page 5 of 33 2017 Edition
(v) Low oil pressure or flow switch with manual reset;

(vi) High oil temperature cut-out with reset;

(vii) Instrument mounting as Clause C6.4.7(i); and

(viii) Stop valve on refrigerant discharge and suction.

Alternatively, pressure measurements read from the display panel of


the chiller is acceptable.

C6.5.2 For oil-free type centrifugal compressor, the following features shall
be equipped.

(a) The compressor shall be of semi-hermetic type and directly


driven and powered by pulse width modulating voltage supply.
The motor shall be compatible with high-speed variable
frequency operation that affords high speed efficiency,
compactness and soft start capability. The motor shall have a
thermistor integrated into the windings providing real time
feedback of core motor temperature allowing accurate control
of liquid motor cooling. The motor cooling shall be provided
by an integrated liquid refrigerant injection system with
individual refrigerant stop valves at suction and discharge line.

(b) The rotor shaft of the compressor shall be supported by oil-


free magnetic bearings. The rotor shaft and the impellers of the
compressor shall levitate during rotation and float on a
magnetic cushion. The rotor shaft of the compressor shall be
self-corrected and maintained at centred rotation during
operation constantly. Bearing sensors shall be provided to
ensure real-time feedback on the orbit of the shaft and to
control the magnetic bearings. When the compressor is not
under operation (not rotating), the rotor shall be supported by
touchdown bearings made from durable materials.

(c) Adequate radial and axial magnetic bearings shall be provided


to withstand the radial and axial force so created during
compression.

(d) Each compressor shall have a bank of capacitors used for


energy storage and filtering DC voltage fluctuations. In case of
power failure, the capacitors shall continue to provide power
to the bearings to keep them levitated, allowing the motor to
turn into a generator and to power itself down to a stop.

(e) The compressor motor shall be a permanent magnet


synchronous motor, with its completely integrated variable
speed drive, which shall provide efficiency not less than 96%
at full load.

Section C6 AC_GS
Page 6 of 33 2017 Edition
The compressor motor speed shall be regulated by a variable
frequency drive according to the load condition. The variable
speed drive shall have suitable rating to operate the unit at any
loading by proportionately increasing or decreasing the motor
speed without surging.

(f) The motor shall be suitable for 380V, 3 phase, 50 Hz and 24


hours continuous operation. Otherwise, transformer shall be
provided for rated voltage and frequency by the compressor
manufacturer and factory assembled. The isolation transformer
shall comply with IEC60076-1:2011 with copper primary and
secondary wings. The transformer shall be designed to operate
at 50Hz and capacities at least 20% higher than the required
power rating of the chiller and its components. Efficiency shall
be over 98% at full load and isolation class shall be minimum
Class H. Each transformer shall be housed in a metal enclosure
with minimum IP55 rating. Protective devices for overcurrent
and earth fault shall be provided. Properly rated fast-acting
fuses shall be installed in the line before each compressors
AC input terminals. UL-approved EMI/EMC filter device shall
be provided on the input power line. Each compressor shall
equip with built-in current limiting device to restrict the start-
up current.

(g) The compressor shall be provided with Electromagnetic


Interface and Electromagnetic Compatibility EMI/EMC filter
upstream of the compressor power input. The EMI/EMC filter
shall be approved to UL 1283 and comply BS EN 60939-
2:2005 or CSA 22.2 No. 8-13. The rated voltage shall be up to
480V AC 50 Hz as minimum. A short, heavy, stranded
conductor from the filter chassis to the main ground of the
chiller unit shall be provided for grounding.

Each compressor shall provide with surge suppression device


parallel to power input line for protect against electrical surge
by the manufacturer. The surge protection device for chiller
shall be cabled to performance under a standard test wave of
20 kV 1.5/50 s voltage impulse and 10kA 8/20s current
impulse.

Built-in voltage dip protection device shall provide for whole


system, sensing instrument and devices of the chiller unit and
shall be factory assembled in compliance with IEC61000-4-
11:2004 and IEC61000-4-34:2005.

Each compressor circuit shall equip with a line reactor to


protect against incoming power surges and reduce harmonic
distortion. The line reactor shall comply with the following
requirements:

Sustain up to at least 600V 3 Phase 50 Hz,

Section C6 AC_GS
Page 7 of 33 2017 Edition
UL Standard 58 with dielectric strength tests at
2.2kVAC for 1 minute,
CSA certified and CE marked or equivalent, and
National Electrical Manufacturers Associated
Insulation Class H or better.

(h) Cabinet shall be made of galvanised steel sheet and painted to


provide a high resistance to corrosion.

(i) The compressor motor speed shall be regulated by a variable


frequency drive according to the load condition. The variable
speed drive shall have suitable rating to operate the unit at any
loading by proportionately increasing or decreasing the motor
speed without surging. The capacity of the compressor shall be
controlled by the variable speed drive and the inlet guide vanes
at any point from 25% capacity to full capacity. The
compressor shall start unload and current inrush less than 5
amps.

(j) The compressor shall equip with discharge and suction shutoff
or isolating valves. Check valve shall be fitted in the discharge
line of each compressor to protect against refrigerant backflow.
Integrated valves to achieve the requirements are acceptable.

(k) The compressor speed shall reduce as condensing temperature


and/or heat load reduces optimising energy performance
through the entire range from 100% to 25% below of full load
capacity of teach compressor given AHRI unloading condition.

(l) Inlet guide vanes shall be built-in to further trim the


compressor capacity in conjunction with the variable speed
control to optimise compressor performance at low load.

(m) The compressor shall include a microprocessor controller


capable of controlling magnetic bearings, inlet guide vanes,
and speed control. The controller shall be capable for
providing commissioning assistance, energy outputs, operation
trends, and fault codes via a high level interface.

The compressors shall be controlled by staged one-by-one by


staging the compressors depending on the system load and
demand. The lead compressor should start and load up close to
its full capacity before the next compressor is brought on line.
Prior to energising any lap compressor, the lead compressor
should run in a stable condition for a few minutes and demand
should be checked to see if there is still enough load to justify
staging an additional compressor. The load must be high
enough to ensure that the compressor(s) online plus the
compressor being added shall not over shoot and/or surge.
During the staging operation, the compressors shall in full
vane away from surge and choke lines as far as possible. If

Section C6 AC_GS
Page 8 of 33 2017 Edition
additional compressors need to be brought online after going
through the above process, the operating compressor(s) must
be unloaded (slowed down) to decrease the discharge pressure
and increase the suction pressure. Continue to reduce the
pressure ratio to less than 2.4, then start the next compressor.
Operate all energised compressors in parallel and load them
equally. A staging valve shall be provided to minimise the
influence of the check valve and facilitate the smooth staging
process.

The service valves shall be equipped at the inlet and outlet of


each compressor and condenser. Service valves shall be
accessible whilst the chiller is in operation.

Compressor(s) shall be mounted directly on the base frame of


the chiller. Each compressor shall be able to field isolated and
removed from both refrigerant and electrical circuits for
maintenance without interrupting the chiller operation. The
removal of compressor shall not require any soldering,
welding or cutting woks on the chiller.

(n) Each compressor shall have one refrigerant circuit including:


1 or 2 compressors
Electronic expansion valve
Evaporator
1 or 2 (1 for each compressor) safety valve(s) on
suction side
Manometers on evaporator and condenser
Condenser
Safety valve on evaporator and condenser
Water pressure differential switch on evaporator and
condenser
Refrigerant pressure gauges (not less than 75mm
diameter and fitted with means of isolation, on suction
and discharge. Gauges shall have pressure and
saturation temperature scales for the refrigerant being
used. Alternatively, gauge with pressure scale only may
be used in conjunction with a pressure/saturation
temperature conversion table fixed nearby)
Pressure safety cut-outs (high and low refrigerant
pressure safety cut-outs with adjustable differential set
point. Settings of the protection shall be pre-set at the
manufacturers recommended settings by the
manufacturer at factory)
Instrument mounting (all instruments shall be mounted
in a neat instrument panel mounted on the package unit
or on a varnished teak frame mounted panel near to the
Section C6 AC_GS
Page 9 of 33 2017 Edition
machine being served and to be design acceptable to
the Supervising Officer.)
Soft-start controller board
EMI filter for compressor
Silicon controlled rectifier module
DC-link Capacitor Board
DC/C converter
IGBT Inverter
Bearing Motor Compressor Controller
Driver module
Compressor I/O Board
Fast acting fuse

(o) Automatic correction action to reduce unnecessary cycling


shall be provided through pre-emptive control of low
evaporator or high discharge pressure conditions to keep the
chiller operating through abnormal transient conditions. The
chiller shall allow +25% and -50% of chiller water flow rate.

(p) The oil free centrifugal chiller unit shall be factory assembled
and tested in the manner completed whole unit. The testing of
cooling capacity, coefficient of performance (COP) and
Integrated Part Load Valve (IPLV) of the chiller unit shall be
carried out in accordance with BS EN 14511-1:2013 to BS
EN14511-4:2013, AHRI 550/590:2012, or other international
recognised standards as considered acceptable to the
Supervising Officer. The characteristic curves shall show the
energy consumption in kilowatts, pressure drop through the
evaporator, chilled or hot water flow rates and temperatures,
condenser fan speeds, etc., for each unit at 25%, 50%, 75%
and 100% of full capacity.

(q) Built-in or standalone active harmonic filter shall be


assembled and tested in the factory for the whole unit.

(r) Control panel

Microprocessor-based control panel shall be provided consist


of touch-screen operator interface and a unit controller. Power
and control shall locate in two sections of the main panel to
ensure protection against all weather conditions. The control
panel shall be IP54 and internally protected with panel against
possible accidental contract with electrical component IP20.
The main panel shall be fitted with a main switch interlocked
door.

(s) The control system shall be touched screen panel to provide


clear, real time and adaptive type, and concise information on
Section C6 AC_GS
Page 10 of 33 2017 Edition
the chiller status, alarms, trends, and set point adjustment. The
compressor controllers shall continue uninterrupted operation
of the chiller whilst the touch screen become inoperable. The
touch-screen shall display the chiller operating parameters, set
point changes with multi-level password protected, and can be
capable of resetting faults and alarms. The control system shall
be capable to quick re-start the chiller automatically after
power failure within 30 seconds. The following parameters,
but not limited, shall be displayed on the home screen and
trend curves on the trend screen.

Entering and leaving chilled water temperatures, chilled


water supply temperature reset point, ambient air
temperature, time, date, operating hours, system
demand, chiller status, alarm, fault, etc.
Compressor information including compressor
maximum speed, actual speed, percent of full speed per
compressor, compressor demand, alarm, fault, suction
pressure, discharge pressure, pressure ration, power
demand, actual power input, 3-phase current, voltage,
surge RPM, choke RPM, liquid line temperature etc.
Entering and leaving condenser water temperatures,
Condenser saturated refrigerant pressure, condenser
water in and out temperatures, refrigerant pressure and
temperature, etc.
Evaporator water in and out temperatures, refrigerant
pressure and temperature, liquid line temperature, etc.
Trending log data Including entering and leaving
chilled water temperatures, ambient air temperature,
actual power input, number of compressor operating,
etc. all data shall have time stamp for analysis

(t) Each chiller shall have control panel, interface port, and
interface cable. The control panel shall contain USB port(s) for
downloading the units history, major parameter trends, alarms,
fault history, and unit operating manual that is stored in the
microprocessor. The fault history shall be displayed with date
and time stamped. The alarm and fault history shall be
downloadable from the chillers USB port(s).

(u) The control panel shall connect to the Central Control and
Monitoring System. The chiller manufacturer shall provide all
required hand-held tools with licensed software for the
interfacing to chiller and chiller control system. Access code at
client level shall be provided for the proprietary monitoring
software.

(v) The following fittings shall be provided and connected: -

(i) Refrigerant pressure gauges as Clause C6.4.7(b);

Section C6 AC_GS
Page 11 of 33 2017 Edition
(ii) Pressure safety cut-outs as Clause C6.4.7(f);

(iii) Instrument mounting as Clause C6.4.7(i); and

(iv) Stop valve on refrigerant discharge and suction.

Alternatively, pressure measurements read from the display


panel of the chiller is acceptable.

C6.6 COMPRESSORS, SCREW TYPE

C6.6.1 Screw compressors shall have quiet operation with oil injection
lubrication system. Open compressors shall have a rotary seal fitted
to the driving shaft which effectively prevents leakage of refrigerant
or oil. Open compressors shall be driven through a flexible coupling
of a type which enables the shaft seal to be removed without moving
compressor or motor.

C6.6.2 A device shall be fitted to prevent the pressure differential across the
compressor causing backward rotation at a normal or emergency stop.

C6.6.3 The lubrication system shall be arranged with an interlock to ensure


adequate oil pressure at all bearings before the compressor starts. A
hand reset pressure or flow switch for stopping the compressor shall
be fitted at an appropriate location from the oil pump delivery pipe to
the oil sump. A replaceable or thermostatically controlled oil cooler
shall be used to remove the heat gained by the oil in the rotor
chamber or the chiller manufacturer shall select and confirm that the
lubrication oil used can be operated at a temperature higher than the
rotor chamber. The oil sump shall have a thermostatically controlled
electric heater which operates while the compressor is at rest.

C6.6.4 The compressor shall have automatic capacity control equipment


which will control at any point between 25% and 100% of full duty
via control of the compressor speed by variable speed drive or slide
valve. For compressor with stepped capacity loader control, each
chiller shall have capacity control steps as specified in Particular
Specification and the minimum step capacity shall be maximum 25%
of full load. The compressor shall be fitted with a device which
ensures that it cannot start unless in the fully unloaded condition.

The hot gas by-pass or injection system of capacity control will not be
accepted.

The motor of a semi-hermetic compressor which is refrigerant gas


cooled shall have in-built protection against inadequate cooling.

The following fittings shall be provided and connected: -

(a) Stop valves on refrigerant discharge and suction;

Section C6 AC_GS
Page 12 of 33 2017 Edition
(b) Refrigerant pressure gauges as Clause C6.4.7(b);

(c) Oil pressure gauge as Clause C6.4.7 (d);

(d) Oil sum or reservoir level sight glass;

(e) Pressure safety cut-outs as Clause C6.4.7(f);

(f) Low oil pressure or flow switch with manual reset;

(g) High oil temperature cut-out with manual reset; and

(h) Instrument mounting as Clause C6.4.7(i).

Alternatively, pressure measurements read form the display of the


chiller is acceptable.

C6.6.5 Screw compressor for ammonia chiller

(a) The casing of screw compressor for ammonia chiller shall be


designed to maximise strength to weight ratio and properly
gasket to prevent leakage. The compressor shall be designed
for a maximum allowable working pressure higher than 2600
kPa. Suction filter and oil filter shall be provided. A check
valve shall be provided at the suction side to prevent the
counter rotation due to pressure equalisation.

(b) The screw compressor unit shall be completed with a variable


volume ratio pressure equalisation device to maintain the
highest efficiency under all working conditions on both the
evaporator load side and the condenser cooling medium side.
Control shall take place in two stages high and low volume
ratio. The device shall consist of one control and one
regulating piston. The unit is connected to the compressor
high, intermediate and low pressure systems. These pressures
act on different surfaces of the control piston and according to
the internal ratio between the pressures the piston will open or
close the flow of high pressure oil to the regulating piston.
When the high pressure oil acts on this piston, it partly closes
the compressor discharge port, which produces a high volume
ratio. When the high pressure oil is drained, the reverse
actions apply and the regulating piston opens part of the
discharge port, giving a low volume ratio.

C6.7 COMPRESSORS, SCROLL TYPE

C6.7.1 Scroll compressor shall be fully hermetic, directly driven by suction


gas-cooled electric motor of speed not exceeding 50 revolutions per

Section C6 AC_GS
Page 13 of 33 2017 Edition
second. Each compressor shall be complete with internal motor
protection against overloads, positive lubrication, mufflers, crankcase
heater and vibration isolation.

C6.7.2 The following fittings shall be provided and connected: -

(a) Stop valves on refrigerant discharge and suction;

(b) Refrigerant pressure gauges as Clause C6.4.7(b);

(c) High and low pressure safety cut-outs as Clause C6.4.7(f);

(d) Filter dryer; and

(e) Instrument mounting as Clause C6.4.7(i).

Alternatively, pressure measurements read from the display panel of


the chiller is acceptable.

C6.8 CONDENSERS, SHELL AND TUBE (FRESH COOLING WATER


APPLICATION)

C6.8.1 Condensers shall be of the manually cleanable type capable of being


re-tubed "in-situ".

C6.8.2 For fresh water condenser cooling applications, the condenser shall be
of steel and the water boxes/end covers shall be of steel or cast iron.

C6.8.3 The tubes shall be of copper, aluminium brass, cupro-nickel, AISI


316 stainless steel or as otherwise indicated in the Particular
Specification. The tube plates may be of the same alloys of the tubes
or alternatively made in mild steel.

C6.8.4 Internal baffles and other fittings in either water or refrigerant circuits
shall be made of material such that they will not corrode or set up
corrosion or permit electro-chemical action with the liquids and/or
other materials used in the condensers.

C6.8.5 End water boxes shall be designed to provide adequate space for
water movement such that there is no erosion of the tube ends. In
general, this requires the water box end to be domed rather than flat.
The water boxes shall be epoxy resin coated internally to prevent
corrosion.

C6.8.6 End box covers shall be removable, and allow easy access for
cleaning the tubes. Means shall be provided for venting and draining
of the water side of the unit.

C6.8.7 The design fouling factor on the water side of the tubes shall be
0.000044 m2 oC/W for cooling tower fresh water.
Section C6 AC_GS
Page 14 of 33 2017 Edition
C6.9 CONDENSERS, SHELL AND TUBE (SEA OR BRACKISH COOLING
WATER APPLICATION)

C6.9.1 Condensers shall be of the manually cleanable type capable of being


re-tubed "in-situ".

C6.9.2 For sea water or brackish water condenser cooling applications, the
condenser shell shall be of steel and the water box/end covers shall be
of steel or cast iron.

C6.9.3 The tubes shall be of titanium and the tube plate shall be of titanium
clad steel.

C6.9.4 Ditto as Clause C6.8.4.

C6.9.5 Ditto as Clause C6.8.5 In addition the water boxes shall be provided
internally with a sacrificial zinc anode at both ends.

C6.9.6 Ditto as Clause C6.8.6.

C6.9.7 Ditto as Clause C6.8.7 except that the design fouling factor shall be
0.000088 m2 oC/W.

C6.10 CONDENSERS, SHELL AND TUBE-GENERAL REQUIREMENT

C6.10.1 The positioning of the condenser shall be such that removal or


maintenance of the tubes is not obstructed by walls, pipework, valves,
etc.

C6.10.2 Means shall be provided for the controlled venting of non-


condensable from the refrigerant side of the condenser. For machine
using R-134a, this may be manually controlled.

C6.10.3 Automatic control of the condensing pressure shall be incorporated.

C6.10.4 The refrigerant and water systems shall be pressure tested at the
manufacturers work in accordance with Part H.

C6.11 CONDENSERS, AIR-COOLED

C6.11.1 Air cooled condensers shall have tube-and-fin or micro-channel


configuration as approved by the Supervising Officer.

For tube-and-fin design, the condenser shall have copper tubes with:

-Aluminium fin coated with corrosion protection coating;


-Electro-tinned copper fins;
- Copper fin; or

Section C6 AC_GS
Page 15 of 33 2017 Edition
-Type of fin as otherwise indicated in the Particular Specification.

Corrosion protection coating of the condenser fins shall be applied in


factory by the chiller manufacturer. Fins with minor damage shall be
combed straight. Units with extensive damage to fins will not be
accepted. Provision shall be made for the purging of non-
condensable from the condenser.

For micro-channel design, the condenser shall have overall aluminium


structure in construction with corrosion protection coating which shall
be applied in factory by the chiller manufacturer.

C6.11.2 Air cooled condensers mounted outside buildings shall have weather-
proof fan motors. The units shall discharge air vertically upwards.

C6.11.3 Automatic control of the condensing pressure shall be incorporated.


Modulation of air flow shall be by staging of condenser fans or by
variable speed devices and the fan motor shall be selected for this
application and de-energised when necessary.

C6.11.4 Fans shall comply with limitations on permitted noise levels where
indicated in the Particular Specification. Fans shall have sufficient
static pressure to cater for the additional acoustic treatment such as
silencer, if any, in order to meet the noise requirements, set out in
Section C8 and the Particular Specification.

C6.11.5 The complete condenser coil shall be pressure tested at the


manufacturers work in accordance with Part H.

C6.12 CONDENSERS, EVAPORATIVE

These are not normally used in Hong Kong. Should such equipment be required,
it will be fully detailed in the Particular Specification.

C6.13 COOLING TOWER

C6.13.1 Cooling towers shall be of the type with induced or forced draught
fans as indicated. The entering and leaving water temperatures and
the water flow rate shall be suitable for peak heat rejection rate at the
maximum ambient wet bulb temperature indicated in the Particular
Specification. The performance of the cooling towers shall be
certified by the Cooling Tower Institute (CTI) in accordance with CTI
STD-201 RS:2015.

C6.13.2 Casings shall be of glass reinforced plastics (GRP), or as indicated.


The casing shall have a treatment to minimise corrosion or decay and
suitable for the casing material used. The casing and structure shall
withstand extreme typhoon gale force winds from any direction. All
hardware with the exception of the supporting grillage shall be
fabricated of AISI 316 stainless steel. This shall include the

Section C6 AC_GS
Page 16 of 33 2017 Edition
mechanical equipment support structure, fan guards and all bolts, nuts
and fasteners used in the construction of the tower.

C6.13.3 The water distribution system shall be easily cleanable to minimise


collection of deposits and growth of algae which might encourage the
growth of "legionella pneumophila" bacteria, and also be protected by
a strainer. Open distribution pans or troughs shall be fitted with
coarse mesh grids to exclude debris.
C6.13.4 Fill shall be of the film-type and vacu-formed PVC, with louvres and
drift eliminators formed as part of the fill sheets. The PVC fill shall
be self-extinguishing for fire resistance with a flame spread of less
than 25 per ASTM E84-14. Fill sheets shall be individually
suspended from stainless steel structural tubing, or by other suitable
methods, supported by the tower columns and intermediate stainless
steel panels, and shall be elevated above the floor of the cold water
basin to facilitate cleaning. Air inlet faces of the tower shall be free
of water splash-out, and guaranteed drift losses shall not exceed
0.005% of the design water flow. All packing shall be resistant to
corrosive attack by algae, fungal growth, the type of condenser water
used or the chemicals used to treat the condenser water.

C6.13.5 Where the tower is to circulate sea water, treated wastewater effluents
or brackish well water, all components must be capable of
withstanding the corrosive effects of these liquids. All metal parts
shall be of zinc free bronze or suitable grades of stainless steel coated
after installation by heavy bituminous or suitable epoxy resin coatings.
Measures shall also be taken against insect and fungus attack. The
packing material shall not distort in any manner which would obstruct
the air or water flow.

C6.13.6 The cooling tower "basin" shall be provided in reinforced concrete to


a specified standard by the Building Contract. Alternatively, if
specified to be provided in the Specialist Services Contract, it shall be
of AISI 316 stainless steel, GRP or as otherwise indicated. Sheet
mild steel basins if specified (for fresh water applications only) shall
be hot dipped galvanised after manufacture and have two coats of an
approved anti-corrosion paint applied.

C6.13.7 The AISI 316 stainless steel or GRP as specified hot water
distribution basin shall be equipped with metering orifice-type
nozzles to deliver incoming water by gravity to the fill. Nozzles shall
be easily removable and replaceable.

C6.13.8 The GRP cold water basin shall be sealed watertight, and shall
include a float-operated mechanical make-up valve, a 100 mm
diameter overflow connection and a depressed GRP sump completed
with a debris screen made of stainless steel or other suitable corrosion
resistant material. The assembly shall be hot-dip galvanised after
fabrication and painted.

C6.13.9 The capacity of the basin shall be sufficient to prevent overflow when
the tower is at rest. There shall be adequate and easy access for
cleaning out the basin.
Section C6 AC_GS
Page 17 of 33 2017 Edition
C6.13.10 Fans shall be of the axial type mounted to provide a vertical upwards
air discharge. In circumstances where centrifugal units are required,
these will be fully specified in the Particular Specification.

Particular attention must be given to the limitations on permitted


noise levels, where indicated. However, where not indicated, noise
levels must be restricted and must be stated with the plant offered.
Plant likely to generate unacceptable noise will not be accepted.

Fan casings and impellers shall either be made of corrosion resistant


material or proofed against corrosion after manufacture. Fan motors
shall be totally enclosed and weatherproofed, TEFC, 1.15 service
factor, mounted outside the humid interior of tower. Fan motors on
induced draught units shall have suitable protective treatment as they
will be mounted in the moist air stream.

Belt or gear drives shall be readily accessible but fully protected


against the weather and personnel. Anti-vibration "cut-out" devices
shall be provided to protect the fans drive, etc. Warning of a "cut-
out" shall be wired back to the plant room in order to draw attention
to any such problem.

C6.13.11 A bleed-off pipe with stop valve and flow regulating device shall be
provided on each cooling tower. The bleed-off water shall be re-used
after treatment free from bacteria for buildings flushing water
connection.

C6.13.12 Where indicated, chemical treatment equipment for maintenance of


cooling water quality shall be provided generally in accordance with
Part F.

C6.14 EVAPORATORS, SHELL AND TUBE WATER CHILLING

C6.14.1 Evaporators shall be of the shell and tube type, capable of being re-
tubed "in-situ". Where an evaporator which cannot be re-tubed "in-
situ" is required, it shall have the refrigerant and water connections
flanged and be mounted on the packaged unit in a manner which
permits easy removal. The design fouling factor on the closed
circulation water side of the tubes shall be 0.000018 m2 oC/W.

C6.14.2 For flooded type evaporator, the evaporator shell and tube plates shall
be of steel and the water boxes/end covers shall be of steel or cast
iron. The tubes shall be of copper, aluminium brass, cupro-nickel,
AISI 316 stainless steel or as otherwise indicated in the Particular
Specification. The water box/end covers shall be removable and the
plant components arranged such that the space for tube removal is not
obstructed.

C6.14.3 The flow of refrigerant to a multiple circuit dry expansion evaporator


shall be controlled by an externally equalised thermostatic or

Section C6 AC_GS
Page 18 of 33 2017 Edition
electronic expansion valve which shall not "hunt" at any step of
compressor unloading. The design of the refrigerant passages in
direct expansion type evaporators shall be such that any oil present is
always carried back to the compressor at the lowest stage of capacity
reduction.

C6.14.4 Where a fixed orifice expansion system is used with a semi-flooded


evaporator, a durable nameplate shall be permanently fixed adjacent
to the sight glass, in the refrigerant liquid pipe feeding the orifice,
with wording as follows: -

"Bubbles" do not always indicate refrigerant undercharge. The A/C


Contractor shall refer to special charging instructions by the
manufacturer for refrigerant changing.

C6.14.5 Provision shall be made on flooded and semi-flooded evaporators for


returning oil from the evaporator to the compressor. If the system
uses and passes oil-rich refrigerant into the compressor suction pipe it
shall not damage the compressor or cause foaming of the oil in the
sump.

C6.14.6 The refrigerant and water systems shall be pressure tested at the
manufacturers works in accordance with Part H.

C6.15 EVAPORATORS, AIR COOLING

C6.15.1 Air coolers using direct expansion of primary refrigerant shall be


provided with refrigerant distributors. Connections to the tubes shall
be designed to ensure equal flow of refrigerant to each tube.

C6.15.2 The flow of refrigerant to a multiple circuit with dry expansion


evaporator shall be controlled by an externally equalised thermostatic
or electronic expansion valve which shall not "hunt" at any step of
compressor unloading.

C6.15.3 The design of the refrigerant passages in direct expansion type


evaporation shall ensure that the return (or suction) connections are
arranged such that any oil present is always carried back to the
compressor even at the lowest stage of capacity reduction.

C6.16 PLATE TYPE HEAT EXCHANGER

C6.16.1 Heat exchangers shall consist of most energy efficient metal plates
pressed into a corrugated pattern and securely clamped between
nitrile rubber gaskets by the pressure end plates of the mild steel
framework. Plates shall be stainless steel 316 for fresh water or
titanium for sea/well water. The plates shall be suspended from the
top bar of the framework and located on the bottom guide bar. No
part of the mild steel framework shall be in contact with the heat
transfer fluids.

Section C6 AC_GS
Page 19 of 33 2017 Edition
C6.16.2 Heat transfer plates shall be clamped by lateral bolts between a
stationary frame plate and a movable pressure plate such that opening
of the plate heat exchangers can be done without removing any
connecting pipes.

C6.16.3 Heat exchanger shall be designed to give a high heat transfer


efficiency to achieve close approach temperatures as low as 3C.

C6.16.4 Heat exchanger frame shall be of mild steel and shall be suitable for
bolting to a horizontal deck. The frames shall be arranged such that
when the tie bars are loosened, full access to all plate surfaces is
provided for cleaning and maintenance. The entire framework and all
parts of the units shall be factory treated to prevent corrosion such
that the heat exchanger shall be capable of corrosive environment.
All holding down bolts shall be of high tensile carbon steel with
plastic tube protection. Each shall be equipped with bearing boxes
and a locking washer enables the bolts to be opened from the fixed
cover. No welded parts are allowed.

C6.16.5 Inlet and outlet ports shall be metal lined constructed on the fixed
frame plate only. Metal lining shall be of the same material as the
plates.

C6.16.6 The heat transfer plates for fresh water application shall be of
stainless steel and in a corrugated pattern with thickness of 0.6 mm
minimum, and pressing depth of about 3.20 mm with pressure rating
a minimum of 1000 kPa or other rating to suit system design as
specified. Maximum plate pack length shall not exceed 45% of the
total framework length. Double gaskets shall be provided around the
bypass port on each plate, with a drain hole between the gaskets to
facilitate leak detection.

C6.16.7 Distribution area shall be with regular pattern and the flow pattern
shall be "counter flow". Gasket shall be on every plate to eliminate
inter leakage between media.

C6.16.8 The heat exchanger units shall be pressure tested in the factory prior
to delivery. The plate heat exchanger shall have a working pressure
not less than 1000 kPa and shall be tested with a minimum pressure
of 1.5 times the working pressure for 24 hours suitable to the system
design application as specified. The manufacturer shall guarantee the
heat exchanger free from leakage for 5 years.

C6.16.9 The heat exchanger for chilled or hot water application shall be
properly insulated with optimum efficiency and robust insulation
against heat loss. The insulation panels shall be of the double skin
aluminium/stainless steel cladded type with handles suitable for easy
removable for plates access for inspection and maintenance. An
insulated stainless steel drip tray shall also be equipped for chilled
water application.

Section C6 AC_GS
Page 20 of 33 2017 Edition
C6.17 LIQUID RECEIVERS (REFRIGERANT RECOVERY UNIT)

C6.17.1 A separate refrigerant recovery unit (RRU) shall be provided for


chiller units. Combination of condenser / receiver is not acceptable.
At least one RRU shall be provided for the largest size of chiller unit
for each chiller plant room. The RRU shall be complete with a
compressor, condenser, liquid/gas transfer valve, pressure relief valve
and all other necessary fittings and accessories.

C6.17.2 The RRU shall have a capacity of not less than 1.2 times the
refrigerant charge of the largest chiller unit. A factory test certificate
for the pressure vessel safety operation issued by the manufacturer
shall be provided.

C6.18 PRESSURE TESTING

C6.18.1 The units previously mentioned shall have a strength and leakage
pressure test after manufacture. The pressure applied on the
refrigerant side shall be as indicated in the table in Part H.

C6.18.2 A pressure test equal to the low side test pressure quoted in Clause
C6.18.1 mentioned above for the refrigerant being used, shall be
applied to the field-erected refrigerant system after all piping has been
fitted. This test shall be in addition to the pressure test on each unit at
completion of manufacture.

C6.18.3 Pressure tests for condenser water circuits from and to cooling towers
or other sources shall be in accordance with Part H of this General
Specification.

C6.19 PUMP DOWN OF SYSTEM

C6.19.1 The control system for reciprocating compressors in direct expansion


systems shall be so arranged that, on the compressor stop circuit
being actuated, the compressor will automatically pump down the
system before it stops running. The following features shall therefore
be incorporated: -

(a) A discharge line check valve; and

(b) The low pressure cut-out shall be set at the pressure


corresponding to the following temperatures for air
conditioning applications: -

Table C6.19.1(b) Cut In/Out Temperature

Cut out Cut in


R134a -15C -3.9C

Section C6 AC_GS
Page 21 of 33 2017 Edition
R407c -2C 0.2C
Ammonia -2.2C 0.2C

C6.19.2 Pump down will not be required: -

(a) Where the compressor is stopped by a safety cut-out when its


driving power will be immediately terminated; or
(b) On fully manually operated systems.

C6.20 REFRIGERANT PIPEWORK

C6.20.1 Pipework for refrigerant systems shall be of copper or steel, which


shall be internally degreased and cleaned.

C6.20.2 For all chloro-fluoro-methane or ethane compounds: -

(a) All pipes from up to 108 mm OD shall be of copper complying


with BS EN 12735-1:2010 and BS EN 12735-2:2010 or
another international recognised standard.

(b) All pipes over 108 mm OD shall be of black extra heavy


seamless steel pipe to BS EN 10216-1:2013 grade 1.0255 or
another international recognised standard.

(c) On fully packaged refrigeration machine, pipework other than


copper, i.e. steel fitted and tested in the factory as standard
production for the units, will be acceptable subject to
notification and written approval by the Supervising Officer.

C6.20.3 For ammonia system: -

Steel - whatever size is technically necessary or as specified in the


Particular Specification.

All materials used in the refrigerant circuit shall be suitable for use in
the presence of ammonia refrigerant or lubricating oil, or a
combination of both, and comply with ANSI/IIAR Standard 2-2014
ANSI / ASME Code B31.5:2013 or ASME Boiler and Pressure
Vessel Code2013, and meet with system pressure-temperature
requirement so that they will not corrode or cause corrosion when in
contact with the fluids conveyed.

C6.20.4 Size of Refrigerant Piping: -

Refrigerant piping shall be sized to avoid excessive pressure drop of


the fluids or gases they carry. The recommendations of the CIBSE
and/or ASHRAE /or other reputable/factory standards approved by
the Supervising Officer on the sizing of refrigerant piping shall be
complied with.

Section C6 AC_GS
Page 22 of 33 2017 Edition
C6.21 REFRIGERATION PLANT ACCESSORIES AND CONTROLS

C6.21.1 Every refrigeration system shall be protected by a pressure relief


device unless it is so constructed that pressure due to fire conditions
would be safely relieved. The equipment provided shall comply with
ANSI/ASHRAE -15-2013 (Packaged with ANSI/ASHRAE 34-2013
or BS EN 378-2:2008+A2:2012 as appropriate and the outlet piped to
discharge outside the building.

C6.21.2 Systems using a thermostatic expansion valve shall have the


following items preceding it in the refrigerant liquid pipe: -

- A solenoid valve;
- A sight glass;
- A refrigerant drier (replaceable);
- A refrigerant strainer; and
- A capped refrigerant charging valve.

C6.21.3 An evaporator pressure regulating valve where fitted shall be


protected by a strainer, and an evaporator pressure gauge shall be
provided, up-stream of the valve, fitted with means of isolation.

C6.21.4 Units having a direct expansion evaporator at a higher level than the
compressor shall operate on a pump down cycle. On water chilling
installation, the chilled water pump shall be kept running during this
process.

C6.21.5 Refrigerant stop valves which incorporate a spindle gland shall be of


the back seat type. The spindle gland shall be serviceable with the
valve "in-situ".

C6.21.6 A flow switch shall be provided in the chilled water pipeline to each
shell and tube evaporator to prevent the compressor starting or
continuing to run if the water flow is below the minimum stipulated
by the evaporator manufacturer.

C6.21.7 A low temperature thermostat with manual reset shall be provided for
each shell and tube evaporator to stop the compressor(s) if the chilled
water flow temperature falls below +3 oC. For other settings as
recommended by the manufacturer shall be submitted for approval.

C6.21.8 Full flow driers with strainers shall be supplied for all refrigerant
liquid lines and shall be completed with isolating valves and bypass
arrangements. Driers shall be of the renewable cartridge type.

A suitable sight glass shall be provided, either built-in to the drier, or


as a separate component installed adjacent to the drier to show
through a suitable glass eye whether the moisture content of the
refrigerant is within permissible limits.

Section C6 AC_GS
Page 23 of 33 2017 Edition
C6.21.9 Strainers shall be provided before all expansion valves, float valves,
solenoid valves, etc. Except where the expansion valve is fitted just
downstream of a solenoid valve, only one strainer needs to be fitted.

C6.21.10 Full flow strainers of the cleanable and renewable type shall be fitted
at the suction of all compressors.

All strainers and driers shall be easily and readily accessible for
cleaning or replacement of cartridges.

C6.21.11 Full flow oil filters shall be incorporated in all force-feed lubricating
system.

C6.21.12 Where oil separation equipment is to be provided, it shall be


completed with traps, strainers, floats, receivers and gauges.

The oil separator shall be a fabricated steel shell with dished steel
endplates and ample and accessible cleaning handholes. The oil
return control floats shall not be fitted inside the shell. No pipes shall
be fitted inside the shell. No pipes shall be connected through the lids
of cleaning or access holes. Adequate provision shall be made for
purifying and flushing the system.

C6.21.13 Energy meters shall be provided for chilled (or hot) water system for
energy audit purposes. The specification/requirement of the energy
meters shall be as described in Section C10.

C6.22 ROOF MOUNTED PACKAGED WATER CHILLER / HEAT PUMP


PLANTS

C6.22.1 The Units shall include the number and type of compressors indicated
in the Particular Specification, with air cooled condenser coils,
condenser fans and motors, shell and tube direct expansion evaporator
water chiller/heat pump.

C6.22.2 Expansion valves controls and safety devices shall all be housed in a
substantial weatherproofed casing.

C6.22.3 Where specified in the Particular Specification, units shall have full
noise suppression treatment with outlet silencers generally as covered
in Sections B8 and C8.

C6.22.4 Unitary package chiller/ heat pump units shall conform to and shall
have rated and tested capacity to the requirements of AHRI
210/240:2008 or other equal Internationally Recognised Standard
accepted by the Supervising Officer.

Section C6 AC_GS
Page 24 of 33 2017 Edition
C6.23 HEAT RECOVERY CHILLER

C6.23.1 Heat recovery chiller unit shall be completed with a heat recovery
condenser and condensing unit, three-way valve, receivers, etc. The
exact configuration of these devices shall follow the details
recommended by the chiller manufacturer. The heat which is
normally rejected to the air-cooled or water-cooled condenser shall be
reclaimed and made available through the heat recovery condenser
and other provisions as specified, for a variety of uses aiming to
optimise the building energy performance.
C6.23.2 Waste heat shall be reclaimed by adding a heat recovery condenser,
refrigerant control valve, liquid line receiver and controls to the
standard air-cooled or water-cooled chiller, making it as a heat
recovery chiller. The heat recovery chiller shall have only one
refrigerant control valve which makes its operation reliable, simple to
control and easy to maintain.

C6.23.3 During operation in the cooling mode, the hot refrigerant gas shall be
condensed only in the normal air-cooled or water-cooled condenser,
the system cooling load heat and the heat of compression shall be
rejected to the atmosphere via this condenser. The system shall sub-
cool the liquid refrigerant which shall increase the capacity of the
machine by up to 12 percent without increasing power consumption.
The condenser fans shall operate in a cycle according to the outside
temperature. Suitable air dampers/head pressure control devices shall
be equipped to maximise the machine heating or cooling output
efficiency.

C6.23.4 Under heat recovery mode, the refrigerant gas shall condense in the
shell-and-tube or plate type heat recovery condenser. The high
pressure and temperature refrigerant gas shall flow into the heat
recovery condenser and the heat released from the cooling load and
heat of compression shall be rejected to the heating water circuit.

C6.23.5 The flow modulation device shall control refrigerant flow or


condensing water flow through the heat recovery unit and normal air-
cooled or water-cooled condensers. It shall be controlled by the
system heating requirements. The unit shall operate with 0 to 100
percent heat recovery, so that part of the heat shall be rejected and
part recovered for system water heating or room relative humidity
(RH) control application.

C6.23.6 The heat reclaim condenser shell shall be of carbon steel. For shell
and tube type design, water boxes at a minimum of 1050 kPa or to
suit system design shall be provided which shall have steel pipe stub
connections grooved for couplings.

C6.23.7 The heat exchanger tubes shall be of seamless copper tubing rolled
into tube header sheets. Other energy efficient heat exchange
equipment/devices may be accepted subject to the approval of the
Supervising Officer.

Section C6 AC_GS
Page 25 of 33 2017 Edition
C6.24 HEAT PUMP

C6.24.1 Heat pump shall be of the air-to-water or water-to-water type as


specified in the Particular Specification.

C6.24.2 Air-to-water heat pump shall be operating in reverse refrigeration


cycle whilst water-to-water heat pump makes use of the building
cooling load as a heat source for water heating. Each heat pump shall
include compressor, compressor motor, evaporator, condenser,
lubrication system, capacity control, solid state control centre and
indication accessories. Relevant content of Section C6 concerning
various components of a normal packaged chiller shall also be applied
where applicable.

C6.24.3 The refrigerant circuit shall be leak tested at factory, evacuated and
pumped up with a holding charge of refrigerant under positive
pressure prior to the delivery of the unit. If this holding charge is lost
on arrival, the system will not be accepted.

C6.24.4 The unit shall consist of factory assembled, charged, wired, insulated
and tested system using an environmental friendly refrigerant.

C6.24.5 The capacity control of the heat pump shall be based on the leaving
hot water temperature sensing in order to maintain constant leaving
water temperature.

C6.24.6 A water flow switch shall be installed in the water piping line to
prevent the unit from starting when water is not circulation through
the evaporator.

C6.25 ENERGY EFFICIENCY PERFORMANCE

The refrigeration plant shall be accepted with a minimum coefficient of


performance as specified in the following Tables and comply with the
requirements stipulated in Code of Practice for Energy Efficiency of Building
Services Installation. The values of minimum coefficient of performance shall
comply with Code of Practice for Energy Efficiency of Building Services
Installation (2015 edition).

For heat pump and heat recovery equipment/applications, the equipment/system


coefficient of performance shall comply with Code of Practice for Energy
Efficiency of building Services Installation (2015 edition).

The minimum coefficient of performance for direct or indirect sea water cooled
chiller at peak load condition should be indicated in Particular Specification.

Details of energy efficiency assessments shall be submitted before the


equipment is accepted. Factory test and field test reports shall be provided to
substantiate the equipment design and performance.

Section C6 AC_GS
Page 26 of 33 2017 Edition
Ample time approved by the Supervising Officer shall be allowed for the
submission in order to meet with the installation programme.

C6.26 TOTAL ENERGY HEAT PUMP

C6.26.1 The total energy heat pump unit shall serve as a normal chiller unit
and hot water plant, and capable to produce chilled water and hot
water to meet both the cooling and heating demand simultaneously
for the air-conditioning system. The unit shall be either a proprietary
product, or specially developed and manufactured by a manufacturer
which have sound experiences in developing such system /equipment
in the past. The A/C Contractor shall submit all relevant information,
including but not limited to, the schematic design, components sizing,
components selections, technical calculations, materials uses,
operation features, system performances under full load and part load
conditions, etc. to the Supervising Officer for approval prior to
ordering.

C6.26.2 Each unit shall be factory built, assembled, piped, wired, refrigerant
charged and fully tested before shipment as complete sets supplied
from a single manufacturer. The only field connections required on
site shall comprise only external control circuitry, system water
piping and electrical power supply. Facilities for connection and
working under the control of the CCMS system shall be provided.

C6.26.3 The total energy heat pump shall be manufactured to cater for using
ambient air as media for residual cooling /heating energy dissipation
and suitable for operating with ambient temperature down to 4C and
higher than 40C.

C6.26.4 The total energy heat pump shall be designed to cool chilled water
from 12.5C to 7C and to heat hot water from minimum 40C to
45C simultaneously with dual setting for both chilled and hot water
temperature available in order to suit the varying cooling and heating
demand. The minimum chilled water-out temperature shall be 5C at
cooling mode and the maximum hot water-out temperature shall be
60C at heating mode.

C6.26.5 The total energy heat pump unit shall consist of compressors, air-
cooled heat exchanger (condenser coil), two nos. of water-side heat
exchangers for chilled water and hot water respectively, necessary
numbers of electronic expansion valves and 3-way electronic
refrigerant flow control valves and all necessary accessories.

C6.26.6 Depending on the demand and priority on cooling and heating loads,
the total energy heat pump shall be switched among the following
five operating modes freely during system operation by varying the
refrigerant flow path: -

(a) Heating Mode

Section C6 AC_GS
Page 27 of 33 2017 Edition
The refrigeration circuit shall be arranged to operate as an air-
cooled heat pump when there is no cooling requirement. The
air-cooled heat exchanger (acting as evaporator) shall absorb
heat energy from the ambient air. The system heat energy
shall be recovered by the heat exchanger at hot-water side so
as to provide hot water source for the connected hot water
system. In this mode, the heat exchanger at chilled-water side
is isolated from the refrigerant circuit.

(b) Heat Recovery Mode


The refrigerant circuit shall be arranged to provide chilled
water as well as uncontrolled hot water simultaneously. The
heat exchanger at chilled water side (acting as evaporator)
absorbs building heat energy (to provide cooling to the
building) and the system heat energy shall be recovered by the
heat exchanger at hot-water side (act as heat recovery
condenser) so as to provide uncontrolled hot water for heating
purposes. In this mode, the air-cooled heat exchanger is
isolated from the refrigerant circuit.

(c) Cooling Mode


The refrigerant circuit shall be arranged to operate as a normal
air-cooled package chiller when there is no heating
requirement. The refrigeration circuit shall be arranged to
absorb the buildings heat energy (i.e. to provide cooling to the
building) by the heat exchanger at chilled-water side (acting as
evaporator) and to reject the heat energy by the air-cooled heat
exchanger (act as condenser) to the atmosphere through the
refrigeration process.

(d) High Cooling and Small Heating Mode


The refrigeration circuit shall be arranged to operate such that
the heat exchanger at chilled-water side (acting as evaporator)
absorbs the buildings heat energy (i.e. to provide cooling to
building). The system heat energy shall be partially recovered
by the heat exchanger at hot-water side to provide hot water
source for the connected hot water system. The surplus heat
energy shall be rejected to the atmosphere via the air-cooled
heat exchanger (acting as condenser) at the same time.

(e) Small Cooling and High Heating Mode


The refrigeration circuit shall be arranged to operate such that
the heat exchanger at chilled-water side (acting as evaporator)
absorbs the buildings heat energy (i.e. provide cooling to the
building) and, at the same time, the air-cooled heat exchanger
absorbs the heat energy from the ambient air in order to meet
the total heat load. The system heat energy shall be recovered
by the heat exchanger at hot-water side to provide the required
heating load.

Section C6 AC_GS
Page 28 of 33 2017 Edition
The operation of the 3-way electronic valves and other
refrigerant flow control valves shall be arranged to achieve the
above five operating modes.

C6.27 AUTOMATIC CONDENSER TUBE CLEANING SYSTEM

C6.27.1 Automatic condenser tube cleaning system shall be provided for each
water-cooled condenser of the refrigeration machine as specified and
indicated on the drawings and particular specification. The system
shall comprise of rubber sponge balls, ball injector, ball
strainer/collector, programmable control panel, inspection chamber,
control valves, associated pipework and all necessary accessories to
form a complete fully automatic condenser tube cleaning system.
The A/C Contractor shall ensure the refrigeration plant arrangement
shall accommodate the automatic condenser tube cleaning system
installation.

C6.27.2 The sponge balls shall be injected to into the condenser inlet pipe by
the ball injector. The balls shall then flow through the condenser
tubes in a random distribution manner within the stream to wipe away
any fouling deposits that are present so as to maintain at or near the
peak design heat transfer coefficient of the condenser. After passing
through the condenser tubes, the sponge balls will be collected at the
ball collector and ready to be injected to the condenser in the next
cleaning cycle. The cleaning cycle shall be programmable from 30 to
120 minutes. The system shall be operated on-line and shall not
disrupt the normal operation of the refrigeration machine.

C6.27.3 The sponge balls shall have a certain oversize compared to the inner
condenser tube diameter. The density of the sponge balls shall be
equivalent to the density of the condenser water and the material, size
and quantity of the balls shall be selected as per manufacturers
recommendation and shall be approved by the Supervising Officer.

C6.27.4 The control system shall be connected to the CCMS via appropriate
interface to monitor the operation of the system and to make
adjustment to the parameters.

C6.28 SOLAR HEATING SYSTEM

C6.28.1 General

The Solar Heating system shall include solar collector system, water
pipework system, automatic controls, water treatment system,
brackets/support, access walkway system, thermal insulation, hot
water storage calorifier, water circulation pumps, valves and
accessories. All the components and parts shall be compatible to each
other to provide best performance.

Section C6 AC_GS
Page 29 of 33 2017 Edition
Individual components forming part of the solar heating system shall,
in addition to this section, comply with the appropriate sections
contained elsewhere in this General Specification. The A/C
Contractor shall submit information on the make and type of each
unit together with the test certificate of solar collector panels
complying with BS EN 12975-2+A1:2010 or approved equivalent for
the Supervising Officers approval.

C6.28.2 Overall Performance

The solar heating system shall include solar collector panels, hot
water storage calorifier, circulation pumps, pipework & valves,
accessories, water treatment plant, automatic controls and accessories,
etc. The solar heating system shall be capable to withstand potable
water with temperature up to 99oC during stagnation. Solar collector
panel shall have a minimum efficiency as specified in the Clause
C6.28.3.

C6.28.3 Construction of Solar Collector

Solar collector shall be either flat plate design or evacuated-tube


design.

(a) Flat Plate Type Solar Collector Panel:

The solar collector panel shall be of flat plate design. Solar


collector panels shall be connected in series and/or parallel and
installed on appropriate supporting framework with sufficient
maintenance access facilities as recommended by the
manufacturer.

A copper tube matrix that contains potable water shall be


mechanically bonded to a 0.8 mm thick aluminium absorber
plate or 0.2 mm thick copper absorber plate and sealed with
high transference thermal paste or soldered copper to copper.
The absorber plate shall be coated in black carbon surface or
approved equivalent offering up to 35% absorption. The
minimum solar absorptance at normal incidence shall be 0.93
where the emittance of coating at normal incidence shall 0.03.
The solar collector panel system shall be designed and
manufactured to BS EN 12975-1:2006+A1:2010& BS EN
12975-2:2006, BS EN 12976-1:2006 & BS EN 12976-2:2006,
AS/NZS 2712:2007 Amd 3:2014 or approved equivalent.

Each collector shall have an insulated casing that houses a


copper tube matrix for transporting the collector fluid. A
copper or aluminium absorber plate with appropriate coating
shall be mechanically bonded or soldered to the headers. The
top of the collector shall be glazed with a glass cover to
prevent heat losses and protect from the adverse weather
conditions.

Section C6 AC_GS
Page 30 of 33 2017 Edition
Tempered solar glass glazing shall be used to seal the top of
the collector and a high strength black casing protecting all the
components. The glazing shall be minimum 3 mm thick, with
glazing transmittance of 0.88 minimum and with appropriate
strength to withstand high wind load and hail. The casing
shall be constructed of metal with oven baked paint finish for
protection against the weather and with high outdoor durability.
Panel efficiency shall be minimum 65% at 30K temperature
difference between average fluid temperature and ambient
temperature with solar irradiation 1000W/m2 based on
aperture area.

Thermal insulation of appropriate thickness shall be provided


under and around the side of the absorber plate, to prevent
solar panel heat loss.

The solar collector system shall be designed for either potable


water or treated water to temperature up to 99 oC under normal
operating conditions. Solar collector panels shall be mounted
at a tilt angle to the horizontal to achieve maximum solar gain
for the application. Each solar collector panel shall produce
minimum 650 W per sq. metre based on 1000 W per sq. metre
irradiation and difference of average fluid temperature and
ambient temperature (i.e. tm-ta = 30K) of 30K without wind.
The solar collector panel shall give a yield of 2.3 kWh per sq.
metre of solar collector aperture area per day calculated on a
yearly average for the region.

(b) Solar Evacuated-Tube Collector Panel:

Solar Evacuated-Tube Collector Panel should consist of single


tubes which are connected to a header pipe. All evacuated
collector tubes shall either have tubes with flow of heat
transfer fluid through the absorber or tubes with heat transfer
between the absorber and heat transfer fluid of the collector
cycle using the heat-pipe principle. The absorber surface
should be contained inside a glass tube. The glass tube
enclosing the absorber surface and heat transfer tubes shall be
evacuated and permanently sealed off. The glass tube should
be tempered glass and designed to withstand the pressure
difference between the atmospheric pressure and the internal
vacuum. The absorber of the collector should be coated with
appropriate selective coating.

Solar collector panels shall be connected in series and/or


parallel and installed on appropriate supporting framework
with sufficient maintenance access facilities as recommended
by the manufacturer. Each solar collector panel shall produce
minimum 700 W per sq. metre, i.e. 70% efficiency at 30K
temperature different between average fluid temperature and
ambient temperature with solar irradiation = 1000 W/m2 based
on aperture area. The transmittance of glass tube shall be

Section C6 AC_GS
Page 31 of 33 2017 Edition
minimum 0.91 and solar absorptivity of absorber shall be
minimum 0.93. The emissivity (at 80C) of absorber material
shall not exceed 0.06. The solar collector panel shall give a
yield of 2.4 kWh per sq. metre of solar collector aperture area
per day calculated on a yearly average for the region.
The solar collector panel shall have an impact resistance and
cyclone resistant as approved by the Supervising Officer.

C6.28.4 Thermal Storage Hot Water Calorifier

The thermal storage hot water calorifier (calorifier) shall be used to


store up the thermal energy delivered by the solar panels. The
calorifier could be provided either with electric or gas fired auxiliary
heater or hooked up with heat pump system. The calorifier shall be
constructed of mild steel with appropriate coating or stainless steel.
The venting requirements of the calorifier shall comply with the
requirements of local Water Supplies Regulations. The calorifier
shall be fitted with closed circuit flow and return lines capable of
receiving thermal energy from solar collectors hot water flow. The
calorifier (unless open vented type) shall be fitted with pressure and
temperature relief valve and in accordance with local regulations.
Calorifier with immersed auxiliary heaters shall be fitted with a
manual reset over temperature thermostat that is adjustable between
40-99 oC. The calorifier shall be completed with insulation of
minimum 50 mm thickness mineral wool insulation or appropriate
insulation as recommended by the manufacturer. The calorifier shall
be completed with temperature gauge, temperature sensors, drain pipe,
heating circuit in/outlet, utility circuit in/outlet, copper coil and etc.

The calorifier shall be factory designed & manufactured to comply


with PD 5500:2012+A3:2014 or AS 3498:2009 or approved
equivalent. Copper coil shall be designed with a maximum pressure
of 10 Bars and a temperature of 200 oC. Temperature sensor shall be
provided for electronic controller of the solar collector system for
automatic control. Manufacturer working and test pressure certificate
shall be submitted for approval.

C6.28.5 Circulation Pump

Circulation pump shall be of canned rotor type, i.e. pump and motor
for an integral unit without shaft seal and with only 2 gaskets for
sealing. The bearings are lubricated by the pumped fluids. The
materials of rotor, shaft and casing shall comply with Section C13-
Water Handling Equipment of the A/C General Specification.

C6.28.6 Automatic Control and Monitoring

The solar collector system shall be provided with a temperature


monitoring system built into a differential controller, which will give
temperature at different points in the circuit. Moreover, the solar
collector system shall be provided with measurement and

Section C6 AC_GS
Page 32 of 33 2017 Edition
measurement devices suitable for remote monitoring and control by
DDC controller/Programmable Logic Controller to

(a) Monitor operating status, alarm, flowrate, temperature and


energy level; and
(b) Control the operating set points of the system.

The solar heating system shall be provided with a data logging system
for automatic generation of the following information: -

(a) Monthly mean in-plane solar irradiation (MJ/sq.m/month);

(b) Monthly mean solar energy absorbed by system (MJ/month);


and

(c) Monthly electrical energy consumption of circulating pump


(kWh/month).

The system shall also be provided with a data logging system to


record the temperature and energy performance of the system.
Interfacing devices shall also be provided for connection to the
CCMS system.

Section C6 AC_GS
Page 33 of 33 2017 Edition
SECTION C7

ELECTRIC MOTORS AND ELECTRICAL EQUIPMENT

C7.1 LOW VOLTAGE - GENERAL

The mains for the low voltage electrical motors and equipment shall be suitable
for a supply as specified in Clause A3.12.

Unless otherwise indicated, all electrical equipment shall be tropicalised and


suitable for use in service conditions as specified in Clause A3.11. Equipment
shall be protected against atmospheric corrosion, including that caused by salt-
laden air. Materials used shall not be susceptible to mould growth or attack by
vermin.

Cables for power circuits shall not be less than 2.5 mm2 copper conductors and
cables for control circuit shall not be less than 1.5 mm2 copper conductors.

C7.2 LOW VOLTAGE - WIRING FOR REFRIGERATED SITUATIONS

All electric wiring to be installed into refrigerated situations where the


temperature is to be maintained at or below 0 oC shall be either MICS or
elastomeric cables that are applicable for the designed operating environment.

C7.3 LOW VOLTAGE - ELECTRIC EQUIPMENT

The low voltage electric equipment shall comply with the relevant sections of
the Electrical General Specification.

Equipment Electrical General Specification


Electric motor Clause C5.25
Variable speed drives Clause C5.19
Motor switchgear, starter and control Clauses C5.18 and C5.26
Panels
Automatic power factor correction Clause C5.22
Capacitors

C7.4 HIGH VOLTAGE - ELECTRIC EQUIPMENT

The high voltage electric equipment shall comply with the relevant sections of
the Electrical General Specification.

Equipment Electrical General Specification


High Voltage - General Clause C13.1
High Voltage - Electric motor Clause C13.3
Section C7 AC_GS 2017 Edition
Page 1 of 2
High Voltage - Motor control Clause C13.4
switchboards
High Voltage - Auto-transformers Clause C13.5
High Voltage - Power factor correction Clause C13.5
capacitors
High Voltage - Power cables Clause C13.7

Section C7 AC_GS 2017 Edition


Page 2 of 2
SECTION C8

NOISE AND VIBRATION CONTROL

C8.1 GENERAL

This section of the Specification intends to direct the A/C Contractor to select
the appropriate and sufficient noise and vibration control measures on the
plant/equipment, the interconnected piping, ductwork and conduit so that when
the installed plant/equipment are put into operation, the resulting noise and
vibration levels at locations within the building and at the adjacent or nearby
buildings shall not exceed the acceptable limits as promulgated by the statutory
requirements of the Environmental Protection Department.

The Corrected Noise Level at potential Noise Sensitive Receiver in the adjacent
or nearby building, if so identified in the Particular Specification and/or
Drawings, shall not exceed the Acceptable Noise Level stipulated in the
Technical Memorandum for the Assessment of Noise from Places other than
Domestic Premises, Public Places or Construction Sites issued by the
Environmental Protection Department when the plant/equipment installed by the
A/C Contractor are put into operation.

The noise assessment shall be carried out for air-cooled chillers / condensing
units / condensers and/or water-cooled chillers / cooling towers and chilled
water / condensing water pumps or external ventilating fan intakes/outlets to
ensure compliance with the statutory requirements of the Environmental
Protection Department.

C8.2 EQUIPMENT BASES

C8.2.1 General

Floor mounted equipment shall be installed on 100 mm high concrete


housekeeping pads provided by the Building Contractor covering the
whole floor area requirements of the equipment bases plus a
minimum of 150 mm further on each side or on inverted beams at the
roof. Vibration isolators shall be mounted on this concrete pad or
inverted beams.

C8.2.2 Welded Structural Steel Bases

Bases shall be constructed of adequate "I" or channel hot dipped


galvanised steel members reinforced as required to prevent the bases
from flexing at start-up and from misalignment of drive and driven
units.

All perimeter members shall be of steel sections with a minimum


depth equal to 1/10th of the longest dimension of the base but need
not exceed 350 mm provided that the deflection and misalignment are

Section C8 AC_GS
Page 1 of 15 2017 Edition
kept within acceptable limits as determined by the equipment
manufacturer.

Height saving brackets shall be employed in all mounting locations to


provide a base clearance of 50 mm.

C8.2.3 Concrete Inertia Bases

Concrete inertia bases shall be formed within a structural steel beam


or channel frame reinforced as required to prevent flexing,
misalignment of the drive and driven units or transferral of stresses
into equipment. The base shall be completed with height saving
brackets, concrete reinforcement and equipment bolting down
provisions.

In general, the thickness of concrete inertia bases shall be of a


minimum of 1/12th of the longest dimension of the base but never be
less than 150 mm. The base depth needs not exceed 300 mm unless
specifically required.

As an indication of the standards required, minimum thickness of the


inertia base shall generally comply with the following table or be
1/12th of the longest dimension of the base, whichever is the larger: -

Table C.8.2.3 Minimum Thickness of Inertia Base

Motor Size (kW) Minimum Thickness


3.7 - 11 150 mm
15 - 37 200 mm
45 - 55 250 mm
75 - 185 300 mm

Base forms shall include minimum concrete reinforcement consisting


of 13 mm bars or angles welded in place on 150 mm centres running
both ways in a layer of 40 mm above the bottom, or additional steel
as is required by the structural conditions.

Unless otherwise specified, concrete inertia bases shall weigh from 2


to 3 times the combined weight of the equipment/plant to be installed
thereon.

Base forms shall be furnished with drilled steel members and with
anchor-bolt sleeves welded below the holes where the anchor bolts
fall in concrete locations.

Height saving brackets shall be provided in all mounting locations to


maintain a base clearance of 50 mm.

Section C8 AC_GS
Page 2 of 15 2017 Edition
C8.3 VIBRATION ISOLATORS

The following types of vibration isolation mountings or suspensions are not


exhaustive but serve to cover the main types that shall be applied as appropriate
unless otherwise stated in the Particular Specifications.

C8.3.1 Type "A" - Free Standing Spring Mounts

These shall be free standing and laterally stable without any housing
and completed with a minimum of 6.0 mm neoprene acoustical
friction pads between the base plate and the support.

All mountings shall have levelling bolts that must be rigidly bolted to
the equipment.

Spring diameters shall be no less than 80% of the compressed height


of the spring at rated load with a horizontal spring stiffness 1.1 times
the rated vertical spring stiffness.

Springs shall have a minimum additional travel to "solid" (fully


compressed) equal to 50% of the rated deflection.

Springs shall be so designed that the ends of the springs remain


parallel.

The springs selected for any given application shall be non-resonant


with the equipments or support structures natural frequencies. This
shall apply to all springs hereafter described.

C8.3.2 Type "B" - Restrained Spring Mounts

Equipment with operating weight different from the installed weight


such as chillers, boilers, etc. and equipment exposed to the wind such
as cooling towers and other roof mounted plants shall be mounted on
spring mountings as Type 'A' but a housing shall be used that includes
vertical limit stops to prevent spring extension when some of the
weight is removed, i.e. when the system is drained or lifted by
abnormal wind pressure.

C8.3.3 Type "C" - Double Deflection Neoprene Mounts

These mountings shall have a minimum static deflection of 8.5 mm.


All metal surfaces shall be neoprene covered to avoid corrosion and
shall have friction pads on both the top and the bottom so that they
need not be bolted to the floor. Bolt holes shall be provided for
applications where bolting down is required.

C8.3.4 Type "D" - Neoprene Pads

These mountings shall consist of "waffle" form neoprene pads of


8.0 mm thickness. Where required these shall be adhesive cemented
to 3 mm steel plate of similar area so as to form a sandwich.

Section C8 AC_GS
Page 3 of 15 2017 Edition
The area of pad to be used and the number of layers shall be
determined for each application in accordance with the
manufacturers recommendations.

C8.3.5 Type "E" - Spring Hangers

These shall contain a steel spring located in a neoprene cup


manufactured with a grommet to prevent short circuiting of the
hanger rod.

The cup shall contain a steel washer designed to properly distribute


the load on the neoprene and prevent its extrusion.

Spring diameters and hanger box lower hole sizes shall be large
enough to permit the hanger rod to swing through a 30o to 35o arc
before contacting the edge of the hole and short circuiting the spring.

Springs shall have a minimum additional travel to solid equal to 50%


of the rated deflection.

C8.3.6 Type "F" - Spring and Double Deflection Neoprene Hangers

These shall be as Type "E" but incorporate an 8 mm deflection


neoprene element at the top of the hanger box.

The neoprene element shall be moulded with a rod isolation bushing


that passes through the upper part of the hanger box.

C8.3.7 Type "G" - Pre-Compressed Spring Hangers

These shall be as Type "F" but shall be pre-compressed to the rated


deflection so as to keep the piping or equipment at a fixed elevation
during installation.

The hangers shall be designed with a release mechanism to free the


spring after the installation is completed and the hanger is subjected
to its full load.

Deflection shall be clearly indicated by means of a scale.

C8.3.8 Type "H" - All Directional Anchor Units

These units shall consist of a telescopic arrangement of two sizes of


steel tubing separated by a minimum 13 mm thickness of heavy duty
neoprene isolation material for horizontal restraints.

Vertical restraints shall be provided by similar material arranged to


prevent vertical travel in either direction.

Section C8 AC_GS
Page 4 of 15 2017 Edition
C8.3.9 Type "I" - Pipe Anchors and Guides

Resilient pipe anchor shall be formed by welding a steel pipe clamp


to the pipe and the clamp in turn supported at its two ends by a pair of
Type "H" all directional anchor units. In this way, both the radial and
axial motion of the pipe are controlled.

Resilient pipe guide shall be formed by welding localised longitudinal


guide ribs around the pipe at location over which slides fit the
oversized pipe clamp which is in turn supported at its two ends by a
pair of Type 'H' all directional anchor units. In this way, radial
motion of pipe is controlled while axial motion of pipe is guided.

C8.3.10 Type "J" - Split Wall/Floor Seals

These shall consist of two bolted pipe halves with 19 mm or thicker


neoprene sponge bonded to the inner faces.

Seals shall project a minimum of 25 mm past either face of the walls.

Where temperatures exceed 115C, fibreglass shall be used in lieu of


the sponge.

C8.3.11 Type "K" - Horizontal Thrust Restrains

Air handling equipment shall be protected where necessary against


excessive displacement, which might result from high air thrusts in
relation to the equipment weight.

The horizontal thrust restraint shall consist of a spring element


located in a neoprene cup manufactured with a grommet to prevent
short circuiting of the threaded rod. The thrust assembly shall be so
designed that the spring element can be pre-set for thrust at the
factory and adjusted at the site to allow for a maximum of 6 mm
movement at start and stop.

The assembly shall be furnished with one threaded rod and two angle
brackets for attachment to both the equipment and ductwork or the
equipment and the structure. Horizontal restraints shall be attached at
the centre line of thrust and symmetrically on either side of the unit.

C8.3.12 Type "L" - Built in Inertia Block Plant Support

Where specified in the contract document, the Building Contractor


shall provide plant foundations and housekeeping pads in the form of
large concrete blocks recessed into the main floor slab.

Unless otherwise indicated, the sides and bottom of the embedded


portion of the concrete block shall be lined with a minimum of 50
mm thick "load bearing" cork pad to the following specification.

Section C8 AC_GS
Page 5 of 15 2017 Edition
Table C8.3.12 Density of Vibration Isolators

Density Density Loading


Designation (kg/m3) (kg/m2)
Light 3.0 4.5 250 - 2500
Medium 5.5 6.0 2500 - 20000
Heavy 7.0 7.5 15000 - 30000

C8.4 PLANT/EQUIPMENT VIBRATION ISOLATION

C8.4.1 General

All vibration isolators shall have their known undeflected heights or


calibration markings so that, after adjustment when carrying their
loads, the deflection under load can be verified, thus determining that
the load is within the proper range of the device and that correct
degree of vibration isolation is being achieved according to the design.

The static deflection of the isolator at each support point shall not
differ from the design objective for the equipment as a whole by more
than 10%.

The ratio of lateral to vertical stiffness for spring shall be not less than
0.9 nor greater than 1.5.

All neoprene mountings shall have hardness of 40 to 65 durometers,


after minimum aging of 20 days or corresponding over-aging.

In order to resist corrosion, all vibration isolation mountings and


hangers shall be treated as follows: -

(a) Springs to be neoprene coated or hot dip galvanised;

(b) Wearing hardware to be cadmium plated steel or stainless steel


of an appropriate grade; and

(c) All other metal parts to be hot dip galvanised.

For any Contract, all vibration isolators and associated equipment


bases shall whenever possible be of the product of a single
manufacturer. Acceptable manufacturers systems shall strictly
comply with the design intent of this and/or the Particular
Specification.

Section C8 AC_GS
Page 6 of 15 2017 Edition
C8.4.2 Selection Guide for Equipment Base and Vibration Isolator

Unless otherwise specified, the selection of the type of equipment


base and vibration isolator (mounting/hanger) for different
plant/equipment and on different floor spans and levels shall follow
the requirements as indicated in the Selection Guide for Vibration
Isolation (Table 47 in the Chapter 48 for "Sound and Vibration
Control" of the ASHRAE Applications Handbook) and the static
deflection of the vibration isolator selected shall either provide a
minimum isolation efficiency of 90% in ground floor areas and 95%
in upper level areas or be not less than the corresponding values
shown in Table 47. However, the A/C Contractor shall be
responsible to ensure that the selected vibration isolation system is
suitable for the specific plant/equipment and the specific building
structure on which the plant/equipment is mounted.

The A/C Contractor shall provide more efficient isolation than those
suggested in Table 47 in case if the adjacent occupied space is a noise
critical area such as board room and executive office. Advice from
vibration isolator manufacturer shall be sought if necessary.

C8.5 PIPEWORK VIBRATION ISOLATION

C8.5.1 Flexible Connectors

Flexible connector shall consist of a single or twin-sphere body


manufactured with reinforced rubber, the ends of which are raised
and wire reinforced to form the cuffs for sealing purposes. The cuffs
shall be backed by floating steel flanges.

The rubber body shall be reinforced by multi-layered nylon tire cord


fabric.

Flexible connectors shall have a life in excess of 10 years under the


design working conditions.

The rubber membranes shall have an indelible identification system


to clearly identify the model and hence suitability for the application
and working conditions and have the date of manufacture moulded
into the cover to ensure that no units that have exceeded the
recommended shelf life are used.

Straight connectors shall be of the twin-sphere construction whilst


elbow connectors shall be of the single-sphere construction.

Straight connectors connected to resiliently supported equipment


shall be equipped with acoustical control cables to prevent excessive
elongation of the connectors if the system operating pressure is in
excess of the value recommended by the manufacturer for use without
control cables.

Section C8 AC_GS
Page 7 of 15 2017 Edition
Acoustical control cable assembly shall consist of four large triangle
anchor plates, two control cables with large swedged-on end fittings
and 13 mm thick acoustical washer bushings of sufficiently large load
bearing area to isolate the end fittings, axially and laterally.

C8.5.2 Flexible Metallic Hose

Allowable stress levels should be within PD 5500:2012+A3:2014.

The corrugated seamless hose body shall be of the annular and close
pitched type.

For all ferrous applications, the hose body and the braid shall be
manufactured from stainless steel material to BS EN 10095:1999
Type X8CrNi25-21. End terminations shall be carbon steel threaded
male nipples to ISO 7-1:1994/Cor1:2007 for 65 mm size and below
and flanges to BS EN 1092-1:2007+A1:2013 Standard for 75 mm and
above.

For copper or non-ferrous pipework systems, the hose body and the
braid shall be manufactured in bronze throughout. End terminations
shall be copper female ferules suitable for soldering.

The lengths of the flexible metallic hoses shall be in accordance with


the manufacturers recommendation.

C8.6 DUCTWORK VIBRATION ISOLATION

They shall be made of approved materials such as lead vinyl or similar of


minimum surface density of 5 kg/m2 and installed such that airflow is not
obstructed. The material used shall be approved or accepted by the FSD.

C8.7 DUCTWORK ACOUSTIC INSULATION

Unless otherwise specified, the acoustic ductwork liner shall conform to the
requirements of ASTM C1071-12. It shall be composed of long textile-type
glass fibres firmly bonded together with a thermosetting resin into a rigid board
of 50 mm thickness and 48 kg/m3 density. The air stream surface shall be
overlaid with a fire-resistant black acrylic coating which adds strength to the
product during fabrication, installation and system operation. The
manufacturers product identification shall appear on the air stream surface.

All components of the acoustic insulation including coverings and adhesive


shall have a fire hazard classification with a flame spread rating of not over 25,
and a smoke developed rating of not over 50. Ratings shall be as established by
the tests conducted in accordance with UL 723:2008, ASTM E84-14 or NFPA
255:2006 or BS 476-4:1970. The A/C Contractor shall certify in writing, before
any insulation is installed, that the products to be used meet with the above
criteria.

Section C8 AC_GS
Page 8 of 15 2017 Edition
The acoustic linings shall have the following minimum sound absorption
coefficients when tested in accordance with ASTM C423-09a.

Table C8.7 Minimum Sound Absorption Coefficient

Octave Band
125 250 500 1k 2k 4k
Centre Freq. (Hz)

Sound Absorption
0.12 0.67 0.99 0.97 0.91 0.87
Coefficient

C8.8 ACOUSTIC DUCTLAG

Unless otherwise specified, the acoustic duct lag shall consist of 50 mm thick
glass fibre/lead sheet or barium loaded vinyl sheet/glass fibre with a factory
applied aluminium vapour-barrier jacket which shall also be used for thermal
insulation of ductwork.

The fibre glass shall have a density of 24 kg/m3 and thermal conductivity of
0.032 W/mC or lower. The lead sheet shall have a surface weight of 5 kg/m2.

Duct lag shall have the following minimum sound transmission loss when tested
in accordance with ASTM E90-09.

Table C8.8 Minimum Sound Transmission Loss

Octave Band
125 250 500 1k 2k 4k
Centre Freq. (Hz)

Sound Transmission
15 17 19 24 30 33
Loss (dB)

C8.9 DUCTWORK SILENCERS

Outer casing of rectangular ductwork silencers shall be fabricated from


galvanised steel not thinner than 0.8 mm in accordance with the recommended
practices that specified in Clause C2.3. Seams shall be "lock-formed" and
mastic filled. Each silencer shall be provided with flanged inlet and outlet. The
internal baffles or splitters shall be of galvanised perforated steel not thinner
than 0.5 mm and having a nominal open area of 30%.

All internal components shall be spot welded in place with welds on centres not
exceeding 100 mm. All spot welds shall be treated after with anti-corrosive
epoxy resin or other approved coating.

Mani folded silencers shall be provided with continuous metallic nosing


crimped in place. Nosing pieces and tails shall be as per the manufacturers
design. The filler material shall be of inorganic mineral or glass fibre of a

Section C8 AC_GS
Page 9 of 15 2017 Edition
density sufficient to obtain the specified acoustic performance and be packed
under not less than 5% compression to eliminate voids due to vibration and
settling. Material shall be inert, vermin and moisture proof.

Combustion rating for the silencer acoustic in-fill shall not exceed the following
when tested in accordance with ASTM E84-14, NFPA Standard 255:2006 or UL
723:2008 or BS 476-4:1970.

- Flame Spread 25
- Smoke Developed 15
- Fuel Contributed 20

The silencer shall be leak-proof at a differential air pressure of 2 kPa.

Unless otherwise specified, ductwork silencers shall have the following


minimum Dynamic Insertion Loss under forward and reverse flow conditions of
10 m/s: -

Table C8.9 - (1)Insertion Loss (dB) - for Lowest Pressure Drop Silencer

Silencer Octave Band Centre Freq. (Hz)


Length
(mm) 125 250 500 1k 2k 4k
900 5 9 14 23 24 14
1500 7 13 21 29 39 20
2100 13 18 28 40 47 26

Table C8.9 - (2)Insertion Loss (dB) - for Low Pressure Drop Silencer

Silencer Octave Band Centre Freq. (Hz)


Length
(mm) 125 250 500 1k 2k 4k
900 5 10 17 17 13 10
1500 8 15 28 30 21 14
2100 12 20 36 38 28 18

Table C8.9 - (3)Insertion Loss (dB) - for Medium Pressure Drop Silencer

Silencer Octave Band Centre Freq. (Hz)


Length
(mm) 125 250 500 1k 2k 4k
900 7 12 19 23 23 18
1500 10 18 30 42 34 23
2100 14 24 36 48 44 31

Section C8 AC_GS
Page 10 of 15 2017 Edition
Table C8.9 - (4)Insertion Loss (dB) - for Standard Pressure Drop Silencer

Silencer Octave Band Centre Freq. (Hz)


Length
(mm) 125 250 500 1k 2k 4k
900 10 15 25 34 35 28
1500 16 22 38 45 46 41
2100 17 34 44 49 49 45

Unless otherwise specified, ductwork silencers shall have the following


maximum self-generated sound power level (dB re 10-12 Watt) under the flow
conditions of 10 m/s: -

Table C8.9 - (5) Maximum Self-Generated Sound Power Level

Silencer Octave Band Centre Freq. (Hz)


Length
(mm) 125 250 500 1k 2k
Lowest 51 51 49 47 50
Low 52 46 43 42 45
Medium 54 52 50 47 48
Standard 69 63 64 61 63

Before ordering ductwork silencers, the A/C Contractor shall submit for the
Supervising Officers approval the proposed manufacturers certified test data
(from an approved laboratory) for pressure drop and insertion loss ratings.

C8.10 ACOUSTIC DOORS

Door leaf shall be at least 65 mm thick, fabricated from 1.5 mm steel and filled
with sound-absorbing and damping materials. Door frame shall be fabricated
from 1.5 mm steel and furnished in two inside and outside mitred and welded
pieces.

Doors shall be fully gasket, hinged and secured by approved latch mechanism.

Door hinges shall be of cam-lift type which shall raise or lower as the door is
opened or closed respectively.

Side and head of door and frame shall receive two sets of self-aligning
compression seals. Acoustic labyrinth shall be created when the door is in the
closed position. Bottom of door leaf shall contain continuous compression seal
and the gravity action of the cam hinges shall cause the door to compress the
bottom seal tightly against the floor every time the door is closed.

Unless otherwise specified, the door shall be 1-hour fire rated and the
compression seals shall be fire-resistant to BS 476-20:1987 to BS 476-22:1987.

Section C8 AC_GS
Page 11 of 15 2017 Edition
The acoustic door shall have the following minimum sound transmission loss
when tested in accordance with ASTM E90-09.
Table C8.10 Minimum Sound Transmission Loss (Door)

Octave Band
125 250 500 1k 2k 4k
Centre Freq. (Hz)

Sound Transmission
26 42 43 47 52 56
Loss (dB)

C8.11 ACOUSTIC LOUVRES

Unless otherwise specified in the Particular Specifications, the acoustic louvres


to be installed to the external walls of plant rooms when specified shall be not
less than 300 mm thick.

Outer casings shall be made of 1.6 mm thick galvanised sheet steel. The noise
absorbing surfaces of the louvre blades shall be made of 0.8 mm thick
perforated galvanised sheet steel and all other surfaces of the louvre blades shall
be made of 0.8 mm thick galvanised sheet steel.

Louvre blades shall be filled with glass fibre of density 48 kg/m3.

The acoustic louvres shall have the following minimum Transmission Loss (TL).

Table C8.11 Minimum Transmission Loss (Louvre)

Octave Band
125 250 500 1k 2k 4k 8k
Centre Freq. (Hz)

Insertion Loss
7 11 12 13 14 12 9
(dB)

Static pressure drop of louvres shall not exceed 50 Pa at a face velocity of 2.2
m/s.

C8.12 ACOUSTIC ENCLOSURES

C8.12.1 General

Where required for in the Contract, double-wall, insulated, and air-


pressure-tight acoustic enclosures for housing noisy plant or
machinery shall be constructed as specified below and supplied by a
specialist manufacturer of insulated housings and casings, with
published standards of construction and performance.

Section C8 AC_GS
Page 12 of 15 2017 Edition
C8.12.2 Panel Construction

The outer surface of the panel shall be made of 1.2 mm thick


galvanised solid sheet steel and the inside surface shall be made of
0.8 mm thick perforated galvanised sheet steel. Interior panel
perforation shall be of 2.4 mm round holes on 4.8 mm staggered
centres.

Panels shall be 100 mm thick or as otherwise indicated and be filled


with glass fibre insulation, 40 kg/m3 minimum density, with
following UL Composite Fire Resistance Ratings or to BS 476-
20:1987 to BS 476-22:1987.

- Flame Spread 15
- Smoke Developed 0
- Fuel Contributed 0

Mineral wool to a comparable specification would also be accepted.

The insulation material shall be non-hygroscopic, inert and vermin-


proof. It shall not settle, shed or dust.

Panel joints shall be of the joiner and connector type construction


such that the adjacent panels are held rigidly in position, effective
both on the inside and outside.

Mechanical joints shall be made leak-proof with ductwork sealer,


which shall be retained between adjoining flat metal surfaces. Panel
construction shall hold the assembly motionless to avoid sealer
displacement. Sufficient sealer shall be used to allow extrusion of
surplus sealer to give visible evidence of sealer. Assembled structure
shall have deflection under load limited to 1/240 of span at 3.0 kPa
pressure.

For spans greater than 3000 mm, additional and approved structural
reinforcement shall be installed to provide for structural rigidity.

Connection of roof to wall panels shall be by suitably sized angles


held by approved screws, and using an approved sealer to provide an
airtight seal.

C8.12.3 Access Doors and Louvres

Where required under the Contract, access doors and louvres forming
part of the complete acoustic enclosures shall be of the acoustic type
design.

Access door shall be 600 mm wide x 1500 mm high or 900 mm wide


x 1800 mm high as specified in the Drawings or otherwise indicated.
Each door shall be factory/workshop installed in its panel opening
which shall be reinforced with 3.4 mm thick galvanised sheet steel
channel of suitable width to suit the wall thickness of the panel. The
Section C8 AC_GS
Page 13 of 15 2017 Edition
doors shall be constructed of 1.2 mm thick galvanised solid sheet
steel and they shall be 100 mm thick and of the overlapping seal type.
Each door shall be equipped with single continuous air/acoustic seals
around the sill, jambs and head and shall have 2 hinges and 2 latches
with an inside release handle.

C8.12.4 Openings and Sealing

All openings with dimensions greater than 150 mm shall be


factory/workshop cut and framed.

The clearance space between the acoustic enclosure and any


ductwork, pipes, or conduits passing through the enclosure shall be
tightly packed with glass fibre or rock wool. Both ends of the
opening shall then be covered up by 1.2 mm thick sheet steel and
sealed airtight by high pressure ductwork sealer.

C8.12.5 Acoustic Test Data for Panels

The minimum allowable Transmission Loss (TL) of the panel,


including all components, when tested in accordance with ASTM
E90-09, shall be as stated below: -

Table C8.12.5 - (1) Minimum Transmission Loss (Panel)

Octave Band
125 250 500 1k 2k 4k 8k
Centre Freq. (Hz)

Sound
Transmission 23 30 42 51 59 58 58
Loss (dB)

The composite panel assembly when tested in accordance with


ASTM C423-09a, shall have minimum sound absorption coefficients
as follows: -

Table C8.12.5 - (2) Minimum Sound Absorption Coefficients

Octave Band
125 250 500 1k 2k 4k 8k
Centre Freq. (Hz)

Sound Absorption
0.89 1.20 1.16 1.09 1.01 1.03 0.93
Coefficient

Section C8 AC_GS
Page 14 of 15 2017 Edition
C8.13 PLANT ROOM ACOUSTIC LININGS

Where required under the Contract, the acoustic linings to walls and/or ceilings
of the plant rooms are used to reduce the reverberant noise levels of the plant
rooms. The material and the sound absorption coefficients of the acoustic wall
lining shall comply with Clause C8.7.

Section C8 AC_GS
Page 15 of 15 2017 Edition
SECTION C9

PIPE MATERIAL, VALVES, COCKS AND STRAINERS

C9.1 AUTOMATIC AIR VENTS

Automatic air vents shall be used where indicated. They shall have gunmetal or
brass bodies, non-ferrous or stainless steel floats and guides, corrosion
resistance valves and seats. Each automatic air vent shall be controlled by a
lock-shield valve. Air release pipes shall be run to discharge at the nearest
suitable and visible point and agreed by the Supervising Officer.

C9.2 BALL FLOAT VALVES

Ball float valves shall be of the sizes indicated and shall suit the fill and
expansion cisterns or tanks specified. Ball float valves for use with feed and
expansion cisterns shall be of the long arm type arranged to shut off when the
cistern contains 150 mm depth of water. Floats shall be of the vacated plastic or
solid polystyrene construction and provided with a non-ferrous threaded in built
connector.

C9.3 BUTTERFLY VALVES

C9.3.1 Butterfly valves shall be installed where indicated. These shall have
resilient seats which are (in-the-field) replaceable with moulded-in 0-
rings to serve as a flange gasket. For sizes of 50 mm dia. to 150 mm
dia. inclusive, a notched plate handle shall be provided for the control
of the valve and indication of disk position. For sizes of 200 mm dia.
and above, gear actuator shall be used. All butterfly valves shall be
capable of bubble tight shut off. Butterfly valves shall comply with
the recognised international standards (e.g. ISO or BS EN).

C9.3.2 Butterfly valves in connection with wafer, full-lug, flange or grooved


ends may also be accepted. The valves shall be in accordance with
the following: -

(a) Grooved ends butterfly valves shall be bubble tight complying


to ISO 5208:2008 or BS EN 593:2009 +A1:2011 standard,
enabling quick assembly with mechanical grooved coupling on
ISO standard pipes;

(b) The manufacturer shall provide independent laboratory tests


for pressure rating. All testing records and data shall be
submitted to the Supervising Officer for approval;

Section C9 AC_GS
Page 1 of 9 2017 Edition
(c) Bodies shall be made of ductile iron grade 400-18 or ASTM
A536 grade 65-45-12, completely coated with polyamide or
products having equivalent functions or performance against
corrosion, suitable for the temperature range of 0C to 50C.
The valve shall provide dead end service at maximum rating;

(d) The discs shall be made of ductile iron, stainless steel,


aluminium bronze or brass ASTM B124, with protective
coating for fresh water application;

(e) The shafts stems shall be made of Type 420 stainless steel;

(f) The control handles and the gear operators shall be suitable for
locking in any position. The micro switches shall be built in
the actuators and factory adjusted at full open and full closure.
Manufacturer shall provide certificate of factory adjustment;

(g) Valve electric operators shall be mounted on valves and tested


at factory; and

(h) The valves shall have marking tag in accordance with ISO
5209:1977 standard.

C9.4 CHECK VALVES

The body of the check valves shall be made of cast iron to BS EN 1561:2011or
ISO 185:2005 or ductile iron to ASTM A536 while the flaps/discs shall be made
of Bronze to ISO 197-4:1983 or ductile cast iron. The discs of swing check
valves shall be of light construction and pivot on a spindle secured by two
phosphor-bronzed hangers. Each valve shall be fitted with a stop to prevent
undue movement of the flap and shall be as silent as possible in operation.

The discs of lift check valves shall be provided with means of guiding the discs
and preventing components from becoming detached in service.

Recoil check valves with size 100 mm and above should have removable cover
on top of the outlet body casing to facilitate inspection of bearings and
movement door.

Section C9 AC_GS
Page 2 of 9 2017 Edition
C9.5 PIPEWORK APPLICATIONS

Except as may otherwise be specified in Particular Specification, the application


of pipework types to the various systems shall be as stated in Table C9.5. All
pipes and fittings shall comply with the relevant Standard and shall have
suitable markings to indicate the Standard.

Table C9.5 - (1) Chilled Water and Low Pressure Hot Water Circulation
(Closed System)

Size Type Treatment

(i) Up to 150 mm Steel to ISO 65:1981 Black mild steel


(BS EN 10255: 2004) of (painted external before
medium grade insulation)

(ii) Over 150 mm up to Steel to ISO 9330-1 to Black mild steel


and including ISO 9330-3 (BS EN (painted external before
300 mm 10217-1 to 10217-7) insulation)
with wall thickness not
less than 6 mm

Note: For pipe sizes of over 300 mm, the requirements, including the pipe wall
thickness, will be fully detailed in the Particular Specification.

Table C9.5 - (2) Chilled Water Drain, Vent and Overflow

Size Type Treatment

(i) Up to 150 mm Steel to ISO 65:1981 Galvanised


(BS EN 10255: 2004) of
medium grade

Table C9.5 - (3) Chilled Water Condensate Drains

Size Type Treatment

(i) Up to 150 mm Steel to ISO 65:1981 Galvanised


(BS EN 10255: 2004) of
medium grade

(ii) Over 150 mm up to UPVC to BS EN ISO Self-finish


and including 1452-1 to 1452-5 or BS
300 mm 3505:1986

Note: For pipe sizes of over 300 mm, the requirements, including the pipe wall
thickness, will be fully detailed in the Particular Specification.

Section C9 AC_GS
Page 3 of 9 2017 Edition
Table C9.5 - (4) Condenser Circulation Pipework, Fresh Water Closed
System with Air/Water Heat Exchanger

Size Type Treatment

(i) Up to 150 mm Steel to ISO 65:1981 Black mild steel


(BS EN 10255: 2004) of (painted external before
medium grade insulation)

(ii) Over 150 mm up to Steel to ISO 9330-1 to Black mild steel


and including 9330-3 (BS EN 10217-1 (painted external before
300 mm to 10217-7) with wall insulation)
thickness not less than
6 mm

Note: For pipe sizes of over 300 mm, the requirements, including the pipe wall
thickness, will be fully detailed in the Particular Specification.

Table C9.5 - (5) Condenser Circulation Pipework, Fresh Water passing


through Cooling Tower

Size Type Treatment

(i) Up to 150 mm Steel to ISO 65:1981 Galvanised


(BS EN 10255: 2004) of
medium grade

(ii) Over 150 mm up to UPVC to BS EN ISO Self-finish


and including 1452-1 to 1452-5 or BS
300 mm 3505:1986

(iii) Over 150 mm up to Ductile iron to External Coating:


and including BS EN 545:2010 of Metallic zinc covered
300 mm appropriate grade by a finishing layer of
bitumen paint
For screw-on flanges
connection, thickness Internal Lining:
grade of Class K12 Cement Mortar as in
Note 4 below

Note: For pipe sizes of over 300 mm, the requirements, including the pipe wall
thickness, will be fully detailed in the Particular Specification.

Section C9 AC_GS
Page 4 of 9 2017 Edition
Table C9.5 - (6) Condenser Circulation Pipework for Sea Water Treated
Effluent Water and Brackish Well Water (Cooling tower or
once through systems)

Size Type Treatment

(i) Up to 150 mm UPVC to BS EN ISO Self-finish


1452-1 to 1452-5 or BS
3505:1986

(ii) Over 150 mm up to Ductile iron or UPVC as As ductile iron


and including for fresh water at Table treatment as in Table
300 mm C9.5 - (5)(iii) C9.5- (5) (iii)

Note: For pipe sizes of over 300 mm, the requirements, including the pipe wall
thickness, will be fully detailed in the Particular Specification.

Table C9.5 - (7) Cold Water Make-up Supply to Air-conditioning Plant Cold
Feed

Size Type Treatment

(i) Up to 150 mm UPVC to BS 3505: 1986 Self-finish


or BS EN ISO 1452-1 to
1452-5 of
appropriate grade

Where copper pipe work is indicated, the tubes shall be of the following types: -

(a) Light gauge copper to BS EN 1057:2006+A1:2010. Refrigeration copper


tubes to BS EN 12735-1 (tubes for piping system) or 12735-2 (tubes for
equipment) for refrigerant distribution purpose;
(b) Where buried underground tubes shall be to BS EN 1057:2006; and
(c) Tubes shall be suitably joined by capillary or compression fittings to ISO
2016:1981 or to BS EN ISO 6708:1996 and ISO 7268: 1983/Amd 1:1984
(BS EN 1254-1 to 1254-4). For jointing screwed copper tubes, cast
copper alloy fittings to ISO 7-1:1994/Cor1:2007 (BS EN 1254-1 to 1254-
4) shall be used.

Note 1: Expansion and contraction due to condenser water temperature


changes must be adequately accommodated particularly for UPVC
pipework.

Note 2: UPVC pipe has several pressure ratings, i.e. appropriate grade for BS
EN ISO 1452-1 to 1452-5 or BS 3505:1986. If pressure ratings are
not indicated in the Drawing or Particular Specification, A/C
Contractor shall provide pipes with pressure ratings equal to twice the
actual working pressure to which the pipes are being subjected.

Section C9 AC_GS
Page 5 of 9 2017 Edition
Note 3: Where UPVC pipe is likely to be exposed to sunlight, it shall be
protected against the effects of ultra violet light by a suitable paint
work coating material or other form of protection to be agreed with
the Supervising Officer.

Note 4: All pipes and fittings shall be cement mortar lined in accordance with
BS EN 545:2010, BS EN 598:2007+A1:2009, BS EN 969:2009,
Type A - Portland pulverised fuel ash cement (PFAC) in accordance
with BS EN 197-1:2011 with a minimum pulverised fuel ash content
of 25%; or Type B - sulphate resisting cement (SRC).

Note 5: UPVC pipework to BS 3505:1986 or BS EN ISO 1452 shall be in


accordance with BS EN ISO 1452-1:2009, BS EN ISO 1452-2:2009,
BS EN ISO 1452-3:2010, BS EN ISO1452-4:2009 and BS EN ISO
1452-5:2009.

C9.6 PLUG COCKS

Plugs for gland cocks shall be ground in. A loose key of mild steel forged to
shape shall be provided for each gland cock.

Air cocks shall be nickel or chrome plated, of the spoutless pattern and with
screwed taper thread. Two loose keys shall be provided for each installation
having up to ten air cocks and one loose key shall be provided for every
additional ten air cocks.

Three-way cocks shall be of the 'T' ported type, the position of the ports being
clearly grooved on the square end of the plug. A loose key shall be provided for
each three-way cock.

C9.7 PRESSURE REDUCING VALVES

Where indicated pressure reducing valves shall be installed. Unless otherwise


specified they shall be as follows: - Valves of up to 50 mm size shall have
bronze or malleable iron bodies and may have taper screwed ends. Valves of
65 mm size and over shall have cast iron bodies with ends flanged. Flanges for
bronze and iron valves shall be to ISO 7005-2:1988 & ISO 7005-3:1988, each
according to the maximum working pressure. Valves shall be of the following
types, as indicated: -

(a) Valves for reducing pressure to apparatus not designed to withstand the
maximum pressure of a high-pressure line shall be of an approved spring-
loaded relay operated type. The valve seats and discs shall be of nickel-
alloy or stainless steel and shall be renewable. Each valve shall be
capable of maintaining a reduced outlet gauge pressure within 3.5 kPa of
the set pressure and shall be installed with an excess pressure isolating
protection valve on the low pressure side; and

Section C9 AC_GS
Page 6 of 9 2017 Edition
(b) Where the apparatus on the low-pressure side is capable of withstanding
the maximum pressure of the high-pressure line, valves shall be of the
single-seated spring-loaded diaphragm type. They shall be adjustable
within the specified low-pressure range and shall be installed with a
safety or relief valve on the low pressure side.

Each reducing valve shall be installed with an isolating valve and strainer
on the high-pressure side, excess pressure isolating valve or relief valve
on the low pressure side, pressure gauge with mild steel siphon and
bronze cock followed by down-stream side isolating valve.

Unions shall be provided on the pressure reducing valve side of both


isolation valves in order to facilitate removal of the pressure reducing
valve set for servicing or replacement. Where indicated, a bypass valve
shall also be installed.

C9.8 STRAINERS

Strainers shall be of the single or the double type as indicated with connections
screwed thread for bores of up to and including 50 mm and flanged for bores of
65 mm and over.

Strainers of up to 50 mm shall be of gunmetal or bronze. The bodies of single


strainers of 65 mm bore and above and all double strainers shall be of cast iron
or ductile iron.

Straining cages and their supporting structure shall be of non-ferrous metal or


stainless steel with 1.5 mm diameter perforations or finer if indicated. Cage
shall be at least five times the cross-sectional area of the pipe or Y-type strainer
of appropriate size as approved by the Supervising Officer.

Double strainers shall incorporate a changeover device to enable either strainer


to be selected and to isolate the idle strainer from the fluid flow.

C9.9 SPECIALISED CONTROL VALVES

Motorised control valves, and solenoid valves used for automatic control
purposes shall be as specified in Clause C5.50 or as indicated in the Particular
Specification. Mixing valves shall comply with BS EN 1287:1999.

C9.10 VALVE APPLICATIONS

C9.10.1 For fresh and chilled water; gate valves shall be used except where
regulation is required in which case globe valve shall be installed but
they must be positioned so as not to prevent drainage of the piping.

C9.10.2 For fresh water service valve both the gate and globe type shall be
constructed of cast iron body with bolted cast iron bonnet, malleable
iron hand wheel, bronze wedge and seat, forged manganese bronze or

Section C9 AC_GS
Page 7 of 9 2017 Edition
high tensile bronze spindle, with graphited packing and compressed
fibre.

C9.10.3 Sea water services valves installed in the sea water pump house
and/or inside the air conditioning plant room shall be constructed of
cast iron body with zinc free bronze trim, bolted cast iron bonnet,
malleable iron hand wheel, zinc free bronze stuffing box, gland,
thrust, plate, yoke, wedge, seat and yoke sleeve with nickel alloy
faces, stainless steel spindle with outside screw of rising stem or
inside screw of non-rising stem (whichever is specified), gunmetal
nuts, and graphited packing compressed fibre packing.

C9.11 VALVES AND COCKS

C9.11.1 Valves, cocks, taps and other accessories shall be of the type and
working pressure suitable for the applied system and shall be
supported by valid documents with approval from the appropriate
authority. They shall also bear the appropriate ISO Standard with
marks. See also Clauses B9.5 and B9.10.

C9.11.2 Bodies of valves and cocks of up to and including 50 mm size shall


be of cast gunmetal or bronze; approved valves having hot-pressed
bodies may be offered as an alternative.

C9.11.3 Unless otherwise specified, bodies of valves of 65 mm size and larger


shall be of cast iron or ductile iron. Castings and pressings shall be of
good quality, clean and smooth and free from scale or flaws.

C9.11.4 All working parts shall be of gunmetal or chrome nickel alloy. Holes
in covers or in gates for screwed portions of spindles shall have full
threads of a length not less than the diameter of the spindle over the
threads. Glands shall be machined to provide a naming fit between
the spindle and the stuffing box. Stuffing boxes shall be properly
packed, or fitted with 'O' rings which shall be located in plastic
bushes.

C9.11.5 Gate valves shall have split or solid wedge gates. Disc valves shall
have renewable discs free to rotate on the spindle.

C9.11.6 Valves and cocks on mild steel pipework of up to and including


50 mm size shall have taper screwed ends, and of 65 mm size and
above shall have flanged ends.

Valves and cocks on copper pipework shall have connecting


generally as for fittings.

C9.11.7 Wheel valves where exposed to view on appliances such as fan coil
units and induction units shall have union ends and either: -

(a) Composition hand-wheels shaped to enclose the stem and


gland; or

Section C9 AC_GS
Page 8 of 9 2017 Edition
(b) Easy clean polished lock shields and composition hand-wheels.

Valves not normally exposed to view shall be fitted with cast metal
hand wheel or lock shields.

C9.11.8 Straight pattern valves shall be of the full-way gate type. Angle
valves shall have domed discs designed to offer minimum resistance
to flow.

C9.11.9 Regulating valves on circuits shall have characterised plugs and a


lockable spindle with an indicator to show the proportional opening.

C9.11.10 Lock-shield valves shall have easy-clean shields or enclosures to


match with the inlet valves; a minimum of 2 loose keys shall be
provided for each size of valve spindle used on the Contract. Where
indicated, the lock-shield valves shall have characterised plugs as for
the regulating valves.

C9.11.11 Isolating valves, lockable where indicated, shall be of the following


types: -

(a) Full way gate type except for valves with side pressure tapping
of up to 50 mm size which shall be of the oblique type; and

(b) Parallel or taper plug type.

C9.11.12 Full way gate valves shall have metal wheel handles. Wedge gates
and all seating, including the top of the wedge and the associated
back seat of the bonnet facing, shall be accurately machined, or
alternatively designed to provide a back seating. Plug valves shall be
arranged for 90 operation with stops on the valve body to limit
movement. Lubricated plug valves shall incorporate a check device
in the plug for the retention of lubricant applied under pressure. A
spare charge of lubricant shall be provided for each valve.

Section C9 AC_GS
Page 9 of 9 2017 Edition
SECTION C10

SYSTEM MONITORING INSTRUMENT

C10.1 GENERAL

The content related to electrical control shall be read in conjunction with


Sections C4, C5 and C7.

The system monitoring instrument in this Section shall also meet with the
requirements as stipulated in the Guidance Notes for Management of IAQ in
Offices & Public Places and the Guide for Participation in the IAQ Certification
Scheme published by the HKSAR Government.

Scale ranges shall be appropriate for indicating the extreme values, on and off
state, of the plant. The design maximum operating condition shall be indicated
at not less than 75% of the total scale length.

Where required in the Particular Specification, all signals generated from the
instruments and devices shall be suitable to work in conjunction with a Central
Control and Monitoring System (CCMS).

C10.2 SYSTEM STATIC PRESSURE GAUGES FOR AIR DISTRIBUTION


SYSTEMS

System static pressure gauges shall be of the single limb inclined manometer
type with an accuracy of 3%.

C10.3 THERMOMETERS - AIR IMMERSION

Thermometers shall be of the mercury-in-glass type of at least 150 mm long


with accuracy of 0.5C.

C10.4 THERMOMETERS - LIQUID IMMERSION

Thermometers shall be of the mercury or alcohol-in-glass type of at least 150


mm long with accuracy of 0.5C.

Unless otherwise specified, material of thermometer pocket shall be of stainless


steel AISI 316.

C10.5 PRESSURE GAUGES FOR WATER SYSTEMS

Pressure gauges shall comply with BS EN 837-1:1998 calibrated in kPa from


zero to not less than 1.3 times and not more than twice the operating pressure of
the respective equipment/system and shall be accurate to 1.5% of full scale
reading, unless otherwise specified.

Section C10 AC_GS


Page 1 of 3 2017 Edition
The dials of gauges shall not be less than 100 mm diameter and the cases shall
be of polished brass or chromium-plated or anti-corrosive painted mild steel
with optical sight glass.

Pressure gauges used solely to indicate the head and pressure of water shall be
provided with an adjustable red pointer set to indicate the normal working
pressure or head of the system.

C10.6 PITOT STATIC TUBE

The flow sensing device shall be of the annubar type in compliance with BS ISO
3966:2008 and BS ISO 7194:2008, inserted through the wall of the pipe via
suitable bush supplied by the sensing devices manufacturer.

The equipment shall be manufactured by a reputable and proven manufacturer


and shall receive the Supervising Officers approval before installation.

Each pitot static sensor shall be permanently marked externally with the
direction of flow.

C10.7 ORIFICE PLATE METERING

Where these are to be installed the orifice plates shall be of stainless steel and of
the well-established manufacturers make with proven performance
characteristics in compliance with ISO 5167-1:2003 or BS 7350:1990. The
resistance across the plant orifice shall not exceed 5 kPa (0.05 bar).

The plate shall have two-valves tappings for connection to manometer or


responder meter, etc., similar to that described in Clause C10.6 above.

C10.8 ELECTROMAGNETIC AND ULTRASONIC FLOWMETERS

The flowmeter shall be of the direct reading type, i.e. in l/s, and shall be suitable
for the chemical and physical properties of the fluids to be measured and
suitable for both horizontal and vertical installations.

Each flowmeter shall consist of the flow sensor, an integral signal converter/
transmitter and a digital display unit. The flow sensor shall be installed in the
water pipework without obstructing the flow. The protection class of the sensor
and converter/transmitter housing shall be at least to IP 67 and IP 65
respectively. The flowmeter shall have a constant accuracy to a maximum error
of 0.5% of the actual flow for flow velocity of greater than or equal to 0.5 m/s.
The installation of the flowmeter shall be as per the manufacturers
recommendation with sufficient length of straight pipe run both at the upstream
and downstream piping.

The flowmeter shall conform to BS EN 61000-6-1:2007, BS EN 61000-6-


2:2005, BS EN 61000-6-3:2007+A1:2011 and BS EN 61000-6-4:2007+A1:2011

Section C10 AC_GS


Page 2 of 3 2017 Edition
or similar international standards on Electro-magnetic Compatibility (EMC)
compliance for industrial and commercial applications.

C10.9 ENERGY METERS

The calculator unit of an energy meter shall calculate and display digitally the
water enthalpy consumption in kWh with an accuracy to a maximum error of
1.5% throughout the range of measurement. The number of digits of
accumulated enthalpy consumption display shall not be less than six. The
housing protection for the microprocessor and calculator unit shall not be less
than IP 54. The requirement for the temperature sensors and the flowmeter shall
be as specified elsewhere in this General Specification.

Signal connection facilities to the CCMS shall be provided for displaying the
energy consumption computed and the flow rate and temperature readings.

Section C10 AC_GS


Page 3 of 3 2017 Edition
SECTION C11

THERMAL INSULATION

C11.1 GENERAL

C11.1.1 Thermal insulation shall comply with the requirements of BS


5422:2009 and BS 5970:2012 or other statutory standards such as
IEC, ISO and etc. or equivalent.

C11.1.2 Unless otherwise indicated, all thermal insulating materials used


within any building shall, with fire performance of Class O as
stipulated in BS 5422: 2009. The definition of Class O (national
class) shall be referred to Annex E of BS 5422:2009. A class O
(national class) material is one which: -

(a) has a Class 1 surface spread of flame rating in accordance with


BS 476-7:1997 and has a fire propagation index of (I) of not
more than 12.0 and a sub-index (i1) of not more than 6.0 in
accordance with BS 476-6:1989+A1:2009; or

(b) is of limited combustibility in accordance with Materials of


limited combustibility (E.2 of Annex E, BS 5422:2009); or

(c) is non-combustible in accordance with Non-combustible


materials (E.1 of Annex E, BS 5422:2009).

Test reports to substantiate the fire properties of the insulation


material shall be issued by laboratories accredited by HOKLAS or
other laboratory accreditation bodies recognised by HOKLAS.

C11.1.3 The insulation used for the air conditioning installation is "air"
insulation which shall satisfy the following: -

(a) Adequate strength and rigidity to maintain the thickness of air;

(b) Creating adequate number of closed air cells within the


material to minimise heat loss due to convection and
conduction; and

(c) Covered on exposed surface with good quality foil to stop heat
loss from radiation.

C11.1.4 Insulation materials and their finishes shall be free from asbestos.
Where any work is carried out on existing insulation material or
finish which contains asbestos in any form the A/C Contractors
attention is drawn to the responsibilities under the provisions of the
Asbestos Regulations current in the Hong Kong SAR at the time of
the works. The A/C Contractor shall also notify the Supervising
Officer should the presence of asbestos be suspected.

Section C11 AC_GS


Page 1 of 9 2017 Edition
C11.1.5 Insulation materials and finishes shall be inherently proof against
rotting, mould and fungal growth and attack by vermin, be non-
hygroscopic and in all respects, be suitable for continuous use
throughout the range of operating temperatures and for the
environment indicated.

C11.1.6 Insulation materials and their finishes shall be with the following
hazardous substances as impurities shall not exceed the following: -
Volatile Organic Compounds (VOCs): 500g/m2/hr
Arsenic: 50ppm
Cadmium: 10ppm
Hexavalent chromium: 10ppm
Lead: 300ppm
Mercury: 10ppm
Selenium: 20ppm
PBDEs (polybrominated diphenyl ether): 100ppm
PBBs (polybrominatedbyphenyls): 100ppm

C11.1.7 The A/C Contractor shall bear the cost and provide relevant
certificates from an approved testing laboratory in order to prove the
physical properties of the insulation to be used in the projects are
conforming to the specification.

C11.2 TYPES OF THERMAL INSULATION MATERIALS

The type of insulation required for a particular installation will generally be


indicated in the Particular Specification. Where this is not so the A/C
Contractor shall include for the types described herein: -

C11.2.1 Type "A" - CFC & HCFC Free Phenolic Foam Insulation

(a) Temperature range: sub-zero to 120C;

(b) Density: 40 kg/m3;

Except at pipe, ductwork and other support points where a


higher density load bearing quality insulation shall be used in
accordance with the manufacturers recommendations. In
general, phenolic foam sections with 80 kg/m3 for pipe sizes of
up to 125 mm and 120 kg/m3 for pipe sizes of 150 mm or
above and made to the same thickness as the adjacent pipe
insulation;

(c) Compressive Strength: 140 kN/m2(BS EN ISO 844:2014);

Section C11 AC_GS


Page 2 of 9 2017 Edition
(d) Thermal Conductivity: 0.022 W/mC at 20C mean
temperature (BS EN ISO 4590:2003 and BS ISO 1922:2012 or
ISO 8302:1991);

(e) Closed Cell Content: 90% minimum (BS EN ISO 4590:2003


and BS ISO 1922:2012 or BS EN ISO 4590:2003);

(f) Vapour Transmission: 10 micron gram meter/Nh at 38C 88%


RH (BS EN ISO 4590:2003 and BS ISO 1922:2012 or ISO
1663:2007); and
(g) Fire Rating: shall have class "O" fire rating and test certificate
from independent laboratory accredited by HOKLAS or other
laboratory accreditation bodies recognised by HOKLAS.

The above properties shall be tested independent of facings


which shall be factory applied Class "O" double sided
reinforced foil vapour barrier for both condensation control
and mechanical protection. The external side shall be of white
antiglare coating and the internal side shall be of aluminium
foil fully adhered to the phenolic foam. Facing with all service
jackets on the outside is also acceptable. The surface
emittance of the all service jackets shall be 0.7 or greater when
tested with ASTM E408-13. In addition, the performance of
both vapour barriers and all service jacket shall comply with
the requirement stipulated at Clause C11.4.2.

The manufacturer shall provide proof if required by the


Supervising Officer, that the above properties of the material
supplied remains constant or are stable enough throughout the
working life.

C11.2.2 Type "B" - Preformed Rigid Fibreglass Insulation

Where specified the A/C Contractor shall supply and install


preformed fibreglass sections of the appropriate size to fit hot water
pipework only and capable of accommodating the temperature range
for the system without structural failure of the fibres or the bonding
agency.

Preformed fibre glass sections shall have a density of not less than 64
kg/m3 and a minimum length of 0.9 m. Butt joint tape not less than
75 mm shall be used to ensure perfect sealing of the joints between
sections.

The thermal conductivity (k value) of the fibreglass shall not be more


than 0.033 W/mC at a mean temperature of 20C. The fibre
diameter of the fibreglass shall be of 4 to 10 micron and fibre length 3
to 6 cm.

All fibreglass insulation shall be completely sealed at all joints. All


holes, tears, punctures, etc. made in the vapour barrier shall be
completely sealed with the same specified foil tape.

Section C11 AC_GS


Page 3 of 9 2017 Edition
C11.2.3 Type "C" - Flexible (Semi Rigid) Glass Fibre Blanket Type Insulation

This form of insulation shall not be used on pipework.

Insulation used for ductwork shall be semi rigid having a density of


not less than 32 kg/m3 and thickness not less than 38 mm. The fibre
diameter of the fibreglass shall be of 4 to 10 micron and fibre length
shall be of 3 to 6 cm.

The thermal conductivity (k value) of the fibreglass shall not be more


than 0.036 W/mC at a mean temperature of 20C. The thermal
resistance (R value) shall be more than 1.08 m2C/W.

C11.2.4 Type "D" - Flexible Closed Cell Elastomeric Insulation

Flexible closed Cell Elastomeric Insulation shall be CFC free, in


continuous lengths, with factory applied talc coating or on-site
applied talc coating on inner surface. Flexible Closed Cell
Elastomeric Insulation shall comply with the following requirements:

(a) Thermal Conductivity (at 20 oC mean temperature):


<0.04 W/m oC;

(b) Density:65 kg/m3 5%;

(c) Water Vapour Permeability (without additional vapour barrier


foil): 0.28 micron gram meter/Nh;

(d) Maximum Operating Temperature: > 80 oC;

(e) No putrefaction and mildew shall form on the insulation


material. The water absorption properties of the insulation
shall be of not more than 1.5% after 28 days;

(f) The material, including adhesives and all accessories shall


have fire properties to Class 'O' as stipulated in BS 5422: 2009.
The insulation material shall be a "built-in" vapour barrier and
achieve condensation control without any additional vapour
barrier foil;

(g) Smoke Visibility (ISO 5659-2:2012); and


The mean specific optical density, Dm shall be less than 500
under all test conditions. The thickness of the test specimen
shall be 25 mm and the Dm shall be the maximum value of the
specific optical density (Ds10) of the three tests computed at 10
minutes time interval.

(h) Smoke Toxicity:


The results shall comply and in accordance with either of the
following standards or equivalent: -

Section C11 AC_GS


Page 4 of 9 2017 Edition
- International Maritime Organisation (IMO)
International Code for Application of Fire Test
Procedure: Part 2 Smoke and Toxicity Test, IMO
MSC 61(67); or

- Naval Engineering Specification (NES) 713 (Issue 3)


Determination of the Toxicity Index of the Products of
Combustion from Small Specimens of Material.

C11.2.5 Type 'E' - Polystyrene Insulation

Only where specified or approved preformed or slab polystyrene may


be used.

Under all circumstances, the material shall be of the type which is


defined as "non-self combustible" in order to meet with the
requirements of Clause C11.3.

C11.2.6 Type "F" - Hydrous Calcium Silicate (HCS) and Rock Wool Pipe
Insulation.

This material is more appropriate to the insulation of hot pipework


and other hot metallic surfaces.

Where specified or approved, this material shall be provided in the


preformed sections having a top density of 200 kg/m3 of chemically-
reacted calcium silicate combined with mineral fibre, with factory
applied jacket.

C11.2.7 Type "G" - Magnesia Insulation

Where specified or approved, this material is appropriate to the


insulation of hot pipework and other hot surfaces. It shall consist of
85% magnesia with 15% cement bonding agent applied wet to the hot
surfaces allowed to dry out and when the appropriate thickness has
been achieved smoothed off, covered with 25 mm spaced wire mesh
of 1 mm diameter galvanised steel wire netting reinforcement,
covered further with smoothly trowelled cement plaster of 15 mm
thickness and painted to an approved colour when dry as described in
Clause B11.8.

C11.2.8 Type "H" Pre-insulated Panel of Foam Insulation with No Ozone


Depleting Substances for Construction of Air Ducts

(a) Temperature range : Sub-zero to 80 oC;


(b) Density : 48 kg/m3 minimum;
(c) Compressive strength : 245kN/m2 (BS EN ISO 844:2014);
(d) Thermal Conductivity : 0.024W/m oC at 20 o
C mean
Temperature; and

Section C11 AC_GS


Page 5 of 9 2017 Edition
(e) Close cell content : 90% minimum (BS EN ISO
4590:2003 and BS ISO 1922:2012
or BS EN ISO 4590:2003).
(f) Flexural Rigidity : Class R3 (BS EN 13430)

The insulation panel shall be laminated at factory with a minimum of


60-micron thick aluminium foils on both sides. The aluminium foil
shall be embossed and coupled with a 2g/m2 layer of polyester paint.

The aluminium foil shall comply with the following requirement: -

(a) Aluminium with pureness : 98.8% (Aluminium Alloy ISO


8079:1984);
(b) Thickness :60m;
(c) Tensile strength (DIN 50154:1980) : > 60N/m2; and
(d) Elongation (DIN 50154:1980) : > 8%.

The insulation panel together with the above-specified aluminium


foils shall achieve condensation control without any additional vapour
barrier foil as stated in Clause C11.4.

C11.2.9 Type "I" Foaming for Pre-insulated Pipes

Foam insulation used shall be CFC, HCFC and HFC free.

The thermal conductivity (k value) of the foam insulation shall not be


more than 0.026 W/moC at a mean temperature of 20 oC. Density
shall not be less than 35 kg/m3.

Galvanised Steel or other materials such as aluminium, stainless steel,


etc. approved by the Supervising Officer shall be applied as external
jacket/ cladding of the pre-insulated pipe. Treatment, such as epoxy
coating, shall be applied to jacket/ cladding to protect against rusting
if necessary when use in outdoor areas.

Approved pipe sleeves and pipe collars, and approved fire rated pipe
sleeves, collars or barriers shall be provided where necessary and
applicable, or the pre-insulated pipes itself having a fire penetration
time not less than the structure through which it passes when tested in
accordance with BS 476 20:1987 for all pre-insulated pipes passing
through compartments, walls, floors and any structural openings in
compliance with relevant regulations and code of practices. The fire
barriers shall have the same fire resisting rating as the structure
through which the pre-insulated pipe passes.

Section C11 AC_GS


Page 6 of 9 2017 Edition
C11.3 MEASURES TO PREVENT SMOKE, NOXIOUS & TOXIC FUMES
PROPAGATION IN EVENT OF FIRE

When requested by the Supervising Officer, proof of fire classification, obtained


from an approved testing laboratory, shall be provided by the A/C Contractor in
order to certify that materials in compliance with Clause C11.1.

Under circumstances, where insulation materials have been permitted which do


not strictly meet with the fire properties stated in Clause C11.1, the materials
shall not be construed as acceptance unless for the following exceptional
conditions: -

(a) The sections are secured to the pipework or ductwork with non-
flammable or toxic smoke producing adhesives; or

(b) They are wrapped over by 25 mm spaced wire mesh, of 1 mm diameter


galvanised steel netting reinforcement, covered further with smoothly
trowelled self-netting cement plaster of 15 mm thickness and if required
(because they are exposed) painted in accordance with Part G.

Such insulation shall similarly be sealed above the ductwork that is fitted
tight and adjacent to the ceilings and beams or at the points near other
obstructions.

Where total sealing by 1 mm diameter galvanised steel wire netting


reinforcement and cement plaster of 15 mm thickness cannot be achieved,
then any form of permission expressed shall not be construed as if such
forms of insulation have been permitted.

Permission to use insulation materials that must be sealed with cement


plaster in order to avoid generation of toxic fumes and smoke in the event
of a fire will only be given under such circumstance that their
applications are considered safe by the Supervising Officer.

C11.4 VAPOUR BARRIERS

C11.4.1 Where thermal insulation is applied to the outside of pipework and


ductwork, equipment and plant used to convey, store or generate
fluids or gases at temperatures lower than the design ambient dew
point temperature indicated, a water vapour barrier shall be provided
unless the Particular Specification states otherwise. The vapour
barrier where deployed shall be applied such that it is continuous and
gives protection to the whole surface of the insulation which it
protects.

It shall not be pierced or otherwise damaged by supports or by the


application of external cladding.

The insulation on continuous pipework and ductwork shall be


sectionalised by vapour barriers to be applied at a maximum of 5 m

Section C11 AC_GS


Page 7 of 9 2017 Edition
intervals to isolate condensation problems caused by perforation of
external barrier to the affected section.

C11.4.2 Aluminium foil vapour barriers used for insulation of all pipework
and ductwork shall conform to the following requirements: -

(a) Machine Direction Tensile Strength (BS EN ISO 1942-2:2008)


12 kN/m;
(b) Cross Direction Tensile Strength (BS EN ISO 1942-2:2008)
9 kN/m;
(c) Bursting Force (AS2001.2.19:1988) 120N or Bursting
Strength 6 kg/cm2(BS EN ISO 2758:2014);
(d) Water Vapour Permeance (ASTM E96/E96M-14) 1.0g/Ns;
and
(e) Surface emittance of external surface (ASTM E408-13) 0.7.

C11.4.3 All joints shall be either factory or on job site fabricated. All joints
shall allow for 50 mm overlap of vapour barrier and the joints shall be
completely sealed using foil tape with a minimum width of 75 mm
conforming to the following specifications: -

(a) Tape thickness minimum 38 microns without release paper;


(b) Machine and Cross Direction Tensile Strength (ASTM D882-
12) 2.0 kN/m;
(c) Peel Adhesion to steel (ASTM D3330/D3330M-04:2010)
10N/25 mm;
(d) Shear adhesion (BS7116:1990): 311; and
(e) Surface Emittance (ASTM E408-13) 0.7.

Any and all punctures, holes, tears, etc. that can be seen or occur on
the job site shall be completely sealed with the same tape as specified
above.

C11.4.4 The material chosen for the vapour barrier and its method of
application shall be compatible with the thermal insulation on which
it is to protect. The following shall be used: -

(a) Wet-applied vapour barriers of the cut-back bitumen type,


bitumen emulsions with or without elastomer latex, vinyl
emulsions and solvent based polymers;

(b) Elastomer sheets with all joints adequately overlapped and


continuously sealed;

(c) Polyvinyl chlorides, polyethylene, polyisobutylene or other


plastics tapes or sheets;

(d) Epoxide and polyester resins;

Section C11 AC_GS


Page 8 of 9 2017 Edition
(e) Sheet metal with all joints adequately overlapped and
continuously sealed to a vapour-tight condition; or

(f) Metal foil used alone or laminated to building paper, building


sheet or plastics film with all joints adequately lapped and
continuously vapour sealed.

Facing materials used on insulation materials to provide vapour


barrier shall not be more than 0.8 mm thick. All metal foil vapour
barrier and foil tape used shall be of Class 'O' as stipulated in BS
5422: 2009.

C11.5 INSULATION THICKNESSES

C11.5.1 Chilled Water Pipe

All chilled water pipes should be insulated with minimum insulation


thickness in accordance with Code of Practice for Energy Efficiency
of Building Services Installation.

C11.5.2 Refrigerant Pipe

All refrigerant pipes on suction side of refrigeration cycle should be


insulated with minimum insulation thickness in accordance with Code
of Practice for Energy Efficiency of Building Services Installation.

C11.5.3 Ductwork and/or Plant Equipment Carrying Warmed or Chilled Air

All Ductwork and/or Plant Equipment Carrying Warmed or Chilled


Air should be insulated with minimum insulation thickness in
accordance with Code of Practice for Energy Efficiency of Building
Services Installation.

Section C11 AC_GS


Page 9 of 9 2017 Edition
SECTION C12

UNITARY AIR-CONDITIONER

C12.1 GENERAL

Unitary air-conditioners shall include: -

(a) Single package unit;


(b) Packaged unit and remote condenser;
(c) Condensing unit and blower coils;
(d) Condensing unit with variable refrigerant volume flow and indoor fan
coil units;
(e) Multi-split system; and
(f) Water-cooled package and water pump package.

Unitary air-conditioners shall be factory fabricated and assembled. The


equipment shall be rated and tested in the same country of manufacture and
meet the requirements of internationally recognised quality assurance standards
approved by the Supervising Officer.

The most energy efficient model in the series shall be selected for submission
and shall be referred to Clause C12.19 of this General Specification.

Refrigerants adoption for refrigeration and air-conditioning system in


government building projects shall comply with flammability safety
classification in accordance with Clause B6.1 of this General Specification.

C12.2 EQUIPMENT SUITABLE FOR LOCAL ELECTRICITY SUPPLY

Unless otherwise specified, electrical equipment of the unitary air-conditioners


shall be suitable for use with 3-phase and neutral, 4-wire, 380/220 V, 50 Hz
source neutral earthed system with provision of bonding.

Transformer may be used for equipment designed for operation on voltages


other those specified above. Whenever possible, these shall be installed within
the unit.

C12.3 SELECTION OF AIR-COOLED CONDENSERS AND CONDENSING


UNITS

Air-cooled condensers and condensing units of unitary air-conditioners shall be


selected to give rated capacity with condensing temperature not exceeding 50C
for the ambient condition as specified under Clause A3.11 of this General
Specification.

Section C12 AC_GS


Page 1 of 4 2017 Edition
C12.4 CASING OF CONDENSING UNIT

Casings of condensing unit of unitary air-conditioners shall be constructed of


rigid galvanised sheet steel and painted in accordance with Part G, suitably
reinforced with channels and sections to form a robust cabinet. Casing for
outdoor installation shall be of weatherproof finish, preferably galvanised,
painted or anodised aluminium.

C12.5 COMPRESSOR

Compressors shall be rotary, scroll or reciprocating of either the hermetically


sealed type or the semi hermetically sealed type. Compressor shall be complete
with internal motor protection, lubrication, crankcase heater, and internal and
external vibration isolation.

C12.6 SUPPLY AIR FAN AND MOTOR

Supply air fans shall be centrifugal type of ample sized for operation against the
specified static pressure. Fan motors shall be permanently lubricated and have
adequate power so as to be non-overloading throughout the range of the fan
characteristic. The motor shall be high efficiency motor.

C12.7 COOLING AND HEATING COILS

Cooling coils shall be of the direct expansion type and constructed with copper
tubes and aluminium fins to give high heat transfer performance. The coils shall
have sufficient number of rows of tubes to provide efficient dehumidification of
the air in addition to its cooling.

Heating coil shall be constructed with copper tubes and aluminium fins to give
high heat transfer performance.

C12.8 AIR FILTER

Air filters shall unless otherwise specified be of the washable panel type. The
filter performance of air duct connection unit shall be referred to Clause C1.
Higher filter efficiency shall be adopted to meet with the IAQ objective
designed.

C12.9 AIR-COOLED CONDENSERS

Air-cooled condensers shall unless otherwise specified be suitable for outdoor


installation with ample capacity to dissipate heat from the air conditioning
system. Condenser coils shall be constructed with copper tube and aluminium
fins. Special corrosion resistant treatment for the condenser coils and fins shall
be considered for the equipment to be located on corrosive environment.

Section C12 AC_GS


Page 2 of 4 2017 Edition
C12.10 ELECTRIC DUCTWORK HEATER

Electric ductwork heaters shall be provided for winter heating or re-heating and
designed in accordance with Clause C3.2.14.

C12.11 REFRIGERANT PIPING

External refrigerant piping when required shall include all necessary valves,
fitting and insulation. All insulation shall be properly protected with mechanical
means such as metallic cladding or cement plastering and painting. Size of the
refrigerant pipe and fittings shall be in accordance with the recommended
standards as stated in Sections B6 and C6.

C12.12 CONDENSATE DRAIN PIPE

Condensate drain pipe shall be adequate insulated and mechanical protected in


accordance with Sections B11 and C11 of this General Specification.

C12.13 SAFETY CONTROL

Controls shall be factory wired. Field wiring in conduit or trunking shall be


limited to interconnections between separate pieces of equipment and power
wiring. Each unit shall be protected and controlled by a factory built control
panel incorporating all necessary devices, switches, indicator, etc. Functions
required shall include those such as isolating switches and emergency stop
facilities.

Safety protections shall include low pressure cut out, high pressure cut out, low
refrigerant temperature cut out, high compressor discharge temperature cut out,
and other protections necessary for the proper and safe operation of the unit.
Overload protections shall be provided as well.

C12.14 OPERATIONAL CONTROL

For a conventional split type A/C unit, a wired or wireless remote controller
shall be provided for the selection of room temperature setting, fan speed and
timer setting. For an advance multi-zone modular split type, the remote
controller shall be of the liquid crystal display (LCD) type with an on-off switch
for operational features such as speed selection, timer setting, temperature
setting, self-diagnosis function and auto restart function.

C12.15 SINGLE PACKAGED AIR-CONDITIONER

Single package unit shall be of the completely self-contained type with factory
wired controls and factory assembled components and piping. The unit shall
include one/two rotary, scroll or reciprocating compressors of either the
hermetically sealed or semi-hermetically sealed type, condenser coil, condenser

Section C12 AC_GS


Page 3 of 4 2017 Edition
fan and motor, direct expansion cooling coil, blower, air filters, drier of the
renewable cartridge type completed with isolating valve, expansion valve,
controls and safety devices all housed in a weather-proof and metal casing of
robust construction yet attractive appearance.

C12.16 PACKAGED AIR-CONDITIONER WITH REMOTE CONDENSER

The unit shall contain all components factory assembled, (as the single packaged
unit with the exception of the condenser), in a sturdy painted G.I. metal casing
arranged for vertical or horizontal mounting inside the building.

C12.17 SPLIT CONDENSING UNIT AND AHU

The condensing unit shall include rotary, scroll or reciprocating compressors,


air-cooled condensing coils, fans and motors control and safety devices, piping
and all necessary accessories factory assembled in a weatherproof painted G.I.
casing. The refrigerant circuit shall be field connected to the matched AHU or
fan coil units each completed with direct expansion cooling coil, expansion
valve, blower with motor and the necessary number of air filters in a well-
insulated, sturdy G.I. metal casing with paint to an attractive appearance.

C12.18 VARIABLE REFRIGERANT FLOW SYSTEM

The air conditioning system shall be of the multi-zone modular split type. Each
zone shall consist of one air-cooled outdoor condensing unit connected to a
group of indoor fan coil units in one single refrigerant circuit. For multi
compressors outdoor unit, one shall be inverter control compressor. The
inverter compressor shall be incorporated with a frequency inverter control to
achieve the optimum flow of refrigerant in response to the actual load.

C12.19 ENERGY EFFICIENCY PERFORMANCE

All unitary air conditioners shall be selected aiming for the highest operation
efficiency. The minimum Coefficient of Performance (COP) for Air-Cooled
Unitary Air Conditioner and Water-Cooled Unitary Air Conditioner shall
comply with the requirement as specified in Code of Practice for Energy
Efficiency of Building Services Installation (2015 Edition).

Section C12 AC_GS


Page 4 of 4 2017 Edition
SECTION C13

WATER HANDLING EQUIPMENT

C13.1 FRESH WATER PUMPS

C13.1.1 Type

(a) Pumps for chilled water circulation or other fresh water


pumping duties unless otherwise specified, shall be of one of
the following types: -

(i) Centrifugal type with volute casing split on the


centreline of the shaft with suction and delivery
connections flanged and fitted to the non-removable
half of the casing;
(ii) End suction type, the pump set shall be installed with
spacer type coupling so that the pump impeller can be
dismantled from the motor side for servicing without
disruption of the pipe-work nor dismounting the motor;
or
(iii) Vertical spindle type centrifugal pump installed on
pump plinth or supported by pipework.

(b) Where large static heads have to be pumped against, type (a)(ii)
or (a)(iii) shall be used in multi-stage configurations.
Generally, the type of pump required will be specified in the
Particular Specifications and/or in the Tender Drawings.
However, if this is not so, the type as detailed in (a)(ii) above
shall be installed if suitable.

C13.1.2 Materials of Construction

Unless otherwise specified, the materials of construction of the pumps


shall be as follows: -
(a) Casing : Cast iron
(b) Impeller : Stainless Steel / Zinc free bronze
(*cast iron or stainless steel)
(c) Shaft : Carbon steel (*stainless steel)
(d) Sleeves : Bronze (*stainless steel)
(e) Casing rings : Bronze (*stainless or cast iron)
(f) Shaft nuts : Bronze
(g) Stuffing box housing : Cast iron

*Alternative materials subject to the approval of the Supervising


Officer
Note 1: Stainless steel shall be used for water with temperature >28oC.

Section C13 AC_GS


Page 1 of 8 2017 Edition
C13.1.3 Standards

(a) Casing Material

Unless otherwise specified for the above types of pumps, cast


iron shall comply with BS EN 1561:2011 or ISO 185:2005.

(b) Impellers & Guide Rings

The impeller shall be of the enclosed type and be of stainless


steel, Leaded Gunmetal to BS EN 1982:2008 or ISO 197-
4:1983, keyed to the shaft. Renewable guide rings shall be
bronze and shall be provided in the casing, keyed to prevent
rotation.

(c) Shaft, Sleeves and Glands

Stainless steel shall be to BS EN 10095:1999, BS EN


10084:2008 and BS EN 10087:1999, ground and polished.

Bronze sleeves shall comply with BS EN 1982:2008 or ISO


197-4:1983 and shall be provided through the sealing glands to
protect the shaft from wear. The sleeves shall be keyed to
prevent rotation and secured against axial movement.

(d) Stuffing Boxes and Drain Piping

Cast iron stuffing boxes housing shall comply with BS EN


1561:2011 or ISO 185:2005 and shall be of ample length with
bronze lined gland and neck bush, fitted with approved
packing and lantern ring water seal. Drain piping to the
nearest builders drain to remove gland leakage shall be
provided. Alternatively, a mechanical seal may be offered.
Mechanical seals shall be of leak free operation. The
mechanical seal shall be the product of specialist proprietor
and the materials used shall be suitable for the pumped liquid.

C13.2 SALINE WATER PUMPS

C13.2.1 Type

(a) These pumps shall be utilised for pumping seawater, brackish


well water, or treated effluent water wherever these
applications apply.

(b) Unless otherwise specified, the configuration of saline water


pumps inside a building plant rooms shall be of the split casing
type as specified in Clause C13.1.1 (a)(i) while for installation
in the primary harbour side sea water pump chamber, pumps
shall generally be of the vertical spindle type as specified in
Clause C13.1.1 (a)(iii).

Section C13 AC_GS


Page 2 of 8 2017 Edition
C13.2.2 Materials of Construction

Unless otherwise specified, the materials of construction for saline


water pump shall be as follows: -

(a) Casing:Stainless Steel


(b) Impeller:Stainless Steel
(c) Shaft:Stainless steel
(d) Sleeves:Stainless steel
(e) Casing rings:Stainless steel
(f) Shaft nuts:Stainless Steel
(g) Stuffing box housing:Stainless Steel
(h) Glands:Carbon steel
(i) Lantern rings:Bronze

Note 1:Stainless steel shall be used for water with temperature >28oC.

C13.2.3 Standards

(a) Casing

Unless otherwise indicated, the casing shall be of cast iron to


BS EN 1561:2011 or ISO 185:2005 or better and approved.

(b) Impeller and Shaft Sleeve

Impeller and shaft sleeve of saline water pumps shall be of one


of the materials as below:-

(i) Zinc-free bronze to BS EN 1982:2008 Grade PB1; or


Grade CT1; or ISO 197-4:1983;

(ii) Austenitic cast iron to BS EN 13835:2012 Grade F1; or


ISO 2892: 2007/Cor 1:2009; or

(iii) Stainless steel to BS EN 10095:1999, AISI 316.

(c) For pumping seawater in harbour area, items (b) (i) & (ii)
above shall not be used.

(d) The shaft shall be of stainless steel to BS EN 10095:1999, BS


EN 10084:2008 and BS EN 10087:1999, AISI 316, ground
and polished.

(e) Stuffing Boxes and Drain Piping

Stuffing boxes shall be of cast iron housing and ample length


completed with bronze lined gland and necks bushes, fitted
with approved packing and bronze lantern ring water seal.
Section C13 AC_GS
Page 3 of 8 2017 Edition
Drain piping to the nearest builders drain for gland leakage
shall be provided. Alternatively, a mechanical seal may be
offered. Mechanical seals shall be of leak free operation. The
mechanical seal shall be the product of specialist proprietor
and the materials used shall be suitable for the pumped liquid.

C13.3 BOILER FEED PUMP

Unless otherwise specified, all feed pumps for boilers handling hot water at
175C and above shall have the major parts, i.e. casing, impeller, shaft and
wearing rings made of stainless steel to AISI 316.

C13.4 SUMP PUMP

C13.4.1 Materials of Construction of Dry Pit Pumps

Unless otherwise specified, the materials for dry pit non-clog pumps
areas shall be as follows: -

(a) Pump casing:Cast iron


(b) Impeller:Cast iron (*stainless steel)
(c) Shaft:Stainless steel
(d) Shaft sleeve:Stainless steel (*bronze)
(e) Packing gland:Ductile iron (*bronze)
(f) Casing bolts:Steel
(g) Cap screw and :Stainless Steel washer, impeller
(h) Key, impeller:Steel

*Alternative materials subject to the approval of the Supervising


Officer

C13.4.2 Materials of Construction of Submersible Pumps

Unless otherwise specified, the materials for submersible non-clog


pumps shall be as follows: -

(a) Pump casing:Cast iron


(b) Impeller:Cast iron (*stainless steel)
(c) Motor casing:Cast iron
(d) Shaft:Stainless steel
(e) Impeller screw:Stainless steel
(f) Mechanical seals:Carbon (*ceramic faces)
(g) Base plate:Steel
(h) Discharge elbow:Cast iron

Section C13 AC_GS


Page 4 of 8 2017 Edition
(i) O-ring seal:Neoprene

*Alternative materials subject to the approval of the Supervising


Officer

C13.4.3 General Requirements

All bolts nuts and fasteners shall be of stainless steel and electric
cable entry shall be of watertight construction.

Sump pumps for rainwater application shall generally be of materials


complying with Standards as specified in Clause C13.1.3. Sump
pumps for pumping other fluids shall be of materials compatible with
the fluid that are being handled. If sea water is pumped, the pump
materials shall comply with Standards as specified in Clause C13.3.3.
The sump pumps shall operate automatically by float level control.

The guide bars and brackets for wet sump installation shall be of
stainless steel to AISI 316.

Cable supports shall be of stainless steel. A safety provision shall be


incorporated for automatic electrical disconnection of the supply in
case of cable entry seal failure.

Pumps for flammable zones shall be equipped with flameproof


submersible motor in compliance with BS EN 60079-
0:2012+A11:2013 and BS EN 60079-1:2014.

C13.5 BORE WELL PUMPS

All bolts, nuts and fasteners shall be of stainless steel and electric cable entry
shall be of watertight construction.

Bore well pumps unless otherwise specified shall be of all stainless steel
construction. The stainless steel shall be of Grade 304 for fresh water
application while AISI 316 stainless steel shall be used for other water
applications.
The level switch shall be of the maintenance free mercury type or electrode type.

C13.6 PUMP BASE PLATE

The based plate shall be made of cast iron or fabricated mild steel. Couplings
shall be flexible of the steel pin and synthetic rubber bushing type, and fitted
with steel guards.

C13.7 VALVES

Automatic air valves, butterfly valves, check (non-return) valves and float ball
valves, etc., shall be as specified in Section C9.

Section C13 AC_GS


Page 5 of 8 2017 Edition
C13.8 VIBRATION ISOLATORS

The bases shall be mounted on the raised housekeeping plinth using appropriate
anti-vibration spring mountings that shall be individually selected according to
load distribution and shall have an additional free travel equal to one half of the
rated deflection as specified in Clause C8.3.

C13.9 GAUGES

Gauges shall be in accordance with Clause C10.5.

C13.10 DRAIN AND VENT

The drain vent shall be built-in completed with a drain plug except where the
pump is inherently self-venting, the drain and drip connection valves and air
cock shall comply with Section C9.

C13.11 FLANGED CONNECTIONS

Pumps shall have flanged connections conforming to the Table of BS EN 1515-


1:2000, BS EN 1092-1:2007+A1:2013, BS EN 1092-2:1997, ISO 7005-1:2011
or ISO 7005-2:1988 as appropriate to the maximum working pressure. Taper
pieces shall be provided where necessary for connection to pipe-work.

C13.12 WATER FILTERS

The materials used in water filters shall not corrode or cause corrosion in the
water and shall generally be as specified for water-cooled condensers and water
chillers.

C13.13 AUTO STRAINERS

The strainer shall be completed with a motor-controlled continuously rotating


inner drum or stationary drum and equipped with an automatic backwash
arrangement.

The unit body shall be provided with an inspection opening for visual checking.
In addition, a drain opening with drain valve shall be provided at the lower part
and connected to the nearest floor drain.

The straining element /screening drum shall be of stainless steel AISI 316 and
shall be of the type and size suitable for removal of captured materials as
specified in the Drawing/Particular Specification. A drip proof squirrel cage
motor shall drive the inner drum, if the strainer is a rotating drum design, or to
drive the rotating backwash arm if the strainer is a stationary drum design, with
suitable geared facilities that shall be mounted on the top of the strainer body.

Section C13 AC_GS


Page 6 of 8 2017 Edition
The body of the auto-strainer shall be of stainless steel AISI 316 cast iron to BS
EN 1561:2011, ISO 185:2005, ASTM A278 Class 40 or carbon steel to BS EN
10095:1999, BS EN 10084:2008 or BS EN 10087:1999. Body of carbon steel
shall be provided with internal coating or lining recommended by the strainer
manufacturer and with zinc sacrificial anodes. It houses a rotating tapered drum
attached to stainless steel shaft of AISI 316 or a stationary drum with rotating
arm driven by stainless steel shaft of AISI 316 and backwash mechanism. The
unit shall be suitable in operation under a pressure of 1034 kPa. Auto-strainer
for handling sea water shall have its body of duplex stainless steel to ASTM
A240 or EN 1.4410 or austenitic grey cast iron to ASTM A436 Grade 1B, or
otherwise the materials of construction as specified in the Particular
Specification of the Contract.

The automatic control of backwash arrangement shall comprise a motor-


controlled valve on the outlet and an adjustable timer and differential pressure
switch set to a maximum pressure drop allowed to regulate the frequency of
backwash. Such control shall interface with the Central Control and Monitoring
System (CCMS) if available.

C13.14 FEED AND EXPANSION FACILITY

C13.14.1 General

For the purpose of this General Specification, the following


definitions shall apply: -

(a) Cistern - An open top vessel; and

(b) Water Tank - A closed vessel.

C13.14.2 Types of Cistern and Tank

(a) Cisterns and tanks shall be of one of the following types as


below: -

(i) Welded or riveted mild steel, to BS 417-2:1987 Grade


A, hot-dip galvanised after manufacture;
(ii) Pressed steel sectional to BS 1564:1975, heavily
galvanised after manufacture; or
(iii) Fibre-glass or plastics, for cisterns not exceeding 500
litre capacity to BS 4213:2004.

(b) Pressed steel tanks shall be of the externally flanged type and
completed with all necessary tie rods. Galvanised mild steel
cisterns and pressed steel tanks shall be cleaned and painted
internally with two coats of an approved bituminous or epoxy
solution or shall receive other such internal treatment as
indicated in the contract Drawings or Particular Specification.

Section C13 AC_GS


Page 7 of 8 2017 Edition
(c) Covers to Cisterns

Each cistern shall be provided with a loose cover formed in


sections not exceeding 2 m long and 1 m wide. Covers for
plastic or fibre-glass cisterns shall be of the same material as
the cistern body.

(d) Connections

Connections to mild steel cisterns and tanks shall be made by


means of bossed, screwed flanges or pads and studs.
Connections on mild steel cisterns shall be welded before
galvanising. Flanges shall comply with BS EN 1092-
1:2007+A1:2013 PN6 to PN40 as appropriate or ISO 7005-
1:2011, ISO 7005-2:1988 and ISO 7005-3:1988.

C13.15 PLATE TYPE HEAT EXCHANGERS

The specification of plate type heat exchangers shall be in accordance with


Clause C6.16 of this General Specification.

Section C13 AC_GS


Page 8 of 8 2017 Edition
PART D - INDOOR AIR QUALITY (IAQ)

D1 GENERAL

The specifications stated in this section shall be the cleanliness standard of


outdoor air to be introduced into the building, the requirements on the indoor air
quality objectives suitable for different types and uses of buildings and for
different levels of comfort and health for the occupants, the treatment and
conditioning processes of air, the equipment/materials for treatment and
conditioning, the testing and commissioning of the system, the methodologies of
assessing indoor air quality, the licensing/registration requirement, the training
requirements of qualified IAQ workers, the operation and maintenance relating
IAQ issues, and the housekeeping and energy efficiency relating to IAQ issues.

This General Specification shall apply to all buildings or totally enclosed areas
provided with air-conditioning and mechanical ventilation installations (ACMV)
for human comfort.

The requirements of the specification shall in any case fulfil the requirements as
published by the Environmental Protection Department.

The specifications shall not in any way provide exemption from existing legal
obligations relating to indoor air quality. Legal provisions on ventilation and
certain other factors affecting indoor air quality in buildings are contained in the
following Regulations: -

- Building (Planning) Regulations, under the Buildings Ordinance (Cap.


123);
- Ventilation of Scheduled Premises Regulation, under the Public health
and Municipal Services Ordinance (Cap. 132);
- Places of Public Entertainment Regulations (Cap. 172);
- Air Pollution Control Ordinance (Cap. 311);
- Smoking (Public Health) (Amendment) Ordinance (Cap. 371);
- Consumer Goods Safety Ordinance (Cap. 456);
- Ozone Layer Protection Ordinance (Cap. 403);
- Pesticides Ordinance (Cap. 133); and
- Occupational Safety & Health Ordinance (Cap. 509).

The overall quality of indoor air is influenced by thermal acceptability and air
contaminants. The thermal acceptability includes temperature, humidity and air
movement. The air contaminants include airborne particles (Respirable
Suspended Particulates), volatile organic compounds (VOC), tobacco smoke,
asbestos, formaldehyde, radon, combustion gases, ozone, respiratory products
and body odours, and micro-organisms.

A building fitted with air-conditioning and mechanical ventilation (ACMV)


system shall be provided with a natural or mechanical ventilation system to
introduce and distribute outdoor air with acceptable quality. For these buildings,

Part D AC_GS
Page 1 of 30 2017 Edition
the factors which determine the adequacy and quality of the air supplied by the
ACMV system are: -

- The quality of outdoor air;


- The outdoor air intake rate;
- The performance of air filters and cleaners;
- Siting of ventilation equipment;
- The recirculation rate;
- Thickness and thermal value of insulation;
- Effectiveness of air distribution systems;
- Variable air volume system controls on minimum fresh air intake rate;
- Ventilation controls;
- Humid climatic conditions;
- The ventilation rate of pollution-emitting activities; and
- Ventilation rates.

The list shown above is not exhaustive and the A/C Contractor shall assess the
site condition and compile a check list for ventilation for submission to the
Supervising Officer for endorsement.

The level of emission and design parameters of indoor air quality shall meet the
requirements as generally described in Clauses D3 and D4. The paints and
painting works for air-duct and finishes shall comply with IAQ relevant
requirements and standards.

IAQ control and sensor requirements shall be as detailed under Part E: Energy
Efficiency and Energy Conservation; Section B4: Installation Methodology of
Automatic Control and Section C4: Material and Equipment specification of
Automatic Control.

To prevent the ingress of containment from outside, a net positive pressure


should be maintained inside the building. The exact requirement of
pressurisation shall be in according to the specific requirements as stipulate in
the Particular Specification. Unless otherwise specified in the Particular
Specification, pressure sensors shall be installed on each floor of the building to
monitor and control the fan output so as to maintain the specified positive
pressure. Such requirements are exempted for those buildings where negative
inside pressure is required and specified in the Particular Specification.

Unless otherwise stated in the Particular Specification and/or Drawings, for


single chiller system, at least one condensing circuit shall incorporate heat
reclaim function. For multi-chillers, at least one chiller shall perform as heat
pump. For only heat pumps arrangement, the heat pumps shall have both
heating and chilling functions. For VRV units alone, the VRV units shall cover
both heating and chilling functions.

All internal surfaces including walls, floors, ceiling and equipment plinth of
AHU and fan rooms shall be treated with epoxy paint. All sealing with
Part D AC_GS
Page 2 of 30 2017 Edition
fibreglass/rock wool for vibration isolation sealing across structural
wall/floor/ceiling shall be caulked airtight and properly sealed with approved
means.

D2 OUTDOOR AIR QUALITY

The A/C Contractor shall select air cleaning and air treatment equipment for the
control of IAQ based on the measured outdoor air quality as stated in the
Particular Specification, or as indicated in Table D2, whichever is worse. Prior
to selection of equipment for the Installations as specified in the Particular
Specification, the outdoor air quality shall be verified again an independent
party appointed by the A/C Contractor. In case of discrepancy, the A/C
Contractor shall submit proposal for approval to rectify the outdoor air
conditions in meeting the minimum standard as shown in Table D2.

Table D2 Outdoor Air Quality Objectives


(Maximum Acceptable Concentration Level)

Concentration in micron gram/m3(i) (vii)


Pollutant
Averaging Time
1 hr (ii) 8 hrs (iii) 24 hrs (iii) 1 yr (iv)
Respirable Suspended 180 55
Particulate (PM10)(v)
Nitrogen Dioxide 300 150 80
Carbon Monoxide 30,000 10,000
Photochemical 240
Oxidants (as ozone)
(vi)

(i) Measured at 298K (25C) and 101.325 kPa (one atmosphere)


(ii) Not to be exceeded more than three times a year
(iii) Not to be exceeded more than once per year
(iv) Arithmetic means
(v) Respirable suspended particulates mean particles suspended in air with a
nominal aerodynamic diameter of 10 micron meter or less
(vi) Photochemical oxidants are determined by measurement of ozone only
(vii) Formula for conversion from micron gram/m3 to ppm for gases is as
follows: -

( g )/m 3 x 24.45
ppm =
1000 x MW

where MW = molecular weight of gas

Part D AC_GS
Page 3 of 30 2017 Edition
The outdoor air intakes shall be located where the air induced shall be the
cleanest taking into account any sources of contaminants which are close to or at
upwind of the intake. No rectification work is required if outdoor air data
measured is below concentration level shown in Table D2.

D3 DESIGN PARAMETERS OF INDOOR AIR QUALITY

The indoor air quality objectives and levels of achievement shall be in following
the Guidance Notes as published by the Environmental Protection Department
or other recognised Authority as specified in the particular specification.

The indoor air quality objectives will not be applicable to any part of the
building such as plant rooms and switch rooms or places where only mechanical
ventilation is specified.

D4 INSTALLATION PART B: TREATMENT AND CONDITIONING


PROCESS

Air cleaning is usually most effective when used in conjunction with either
source control or ventilation. Most air cleaning in large buildings is aimed
primarily at preventing contaminant buildup in ACMV equipment and
enhancing equipment efficiency. Air cleaning equipment intended to provide
better indoor air quality for occupants must be properly selected and designed
for the particular pollutants being treated.

Table D4 Treatment and Conditioning Processes for achieving different IAQ


Parameters

IAQ Parameters Treatment and Conditioning Processes


Carbon Dioxide Dilution by Outdoor Air
Carbon Monoxide Dilution by Outdoor Air
Respirable Suspended Particulate Filtration
Particulate Electrostatic Precipitation
High Efficiency Filtering
Nitrogen Dioxide Electronic Air Cleaner
Ozone Dilution/Purging by Outdoor Air
Activate Carbon Filter
Formaldehyde Electronic Air Cleaner
Total Volatile Organic Electronic Air Cleaner
Compound
Radon Purging by Outdoor Air
Activate Carbon Filter
Airborne Bacteria Germicidal Ultraviolet Air Steriliser
Room Temperature Heating /Cooling
Relative Humidity Dehumidifier / Humidifier

Part D AC_GS
Page 4 of 30 2017 Edition
D4.1 Particulate Filtration

Particulate filtration removes the air-borne respirable suspended


particulates. In order to achieve the required level of filtration, it is
necessary to combine filters in different stages to achieve multi-stage
filtration. There are usually three stages: - the first stage or primary,
the secondary, and the final stage in which high efficiency particulate
arrestee (HEPA) filters are used to capture fine particles smaller than
1.0 micron meter.
The primary filter is normally exposed to the full velocity of the air
stream and is normally dry panel or a panel consisting of washable
filter elements. The secondary stage which normally comprises roll
or bag filters covers an extended surface area to reduce air velocity
through the media to about 0.12 m/s. The final stage comprises
HEPA filters which are normally pleated to increase surface area so
as to reduce the air velocities through the media to about 0.03 m/s.

This multi-stage filtration is used not only because of the cleanliness


of air required but it also prolongs the life of the filter unit of each
stage hence reduces the maintenance cost of the filtration system.

D4.2 Electrostatic Precipitation

Electrostatic precipitation uses the attraction of charged particles to


oppositely charged surfaces to collect airborne particulates. In this
process, the particles are charged by ionising the air with an electric
field. The charged particles are then collected by a strong electric
field generated between oppositely charged electrodes. Electrostatic
precipitation provides relatively high efficiency filtration of small
respirable particulates at low air pressure losses. Electrostatic
precipitators may be installed in air distribution equipment or in
specific usage areas.

D4.3 Germicidal Ultraviolet Air Steriliser

Germicidal, or short-wave ultraviolet has wavelength band between


200 nm and 300 nm. Germicidal ultraviolet is primarily intended for
the destruction of bacteria and other micro-organisms, like mould and
spores in the air or on exposed surfaces. The exposure of germicidal
ultraviolet necessary to kill bacteria is proportional to exposure time
and the intensity of ultraviolet. The inverse square law applies to the
germicidal ultraviolet, that is, the killing power decreases as the
distance from the lamps increases.

D4.4 Electronic Air Cleaners

Electronic air cleaners work on the principle of ionisation created by


an electromagnetic field known as corona discharge. In the ionisation
process, neutral oxygen atoms or molecules are electrically charged
and converted to negative and positive ions. The negative ions help

Part D AC_GS
Page 5 of 30 2017 Edition
to reduce or eliminate airborne micro-organisms, organic smells and,
volatile organic components. Electronic air cleaners should maintain
purification efficiency of not less than 85% total bacteria count.

D4.5 Physical Adsorbers on Ozone and Radon

Adsorption is a surface phenomenon, similar in many ways to


condensation. Pollutant gas molecules that strike a surface and
remain bound to it for an appreciable time. The adsorbers are in
granular of fibrous form to increase the gross surface exposed to an
airstream. The surface of the adsorber is treated to develop pores of
microscopic dimensions, which greatly increase the area available for
molecular contacts. Typical adsorber media are treated activated
alumina and carbon.

Activated carbon adsorbs ozone readily, both reacting with it and


catalysing its conversion to oxygen.

Radon is a radioactive gas that decays by alpha-particle emission,


eventually yielding individual atoms of polonium, bismuth, and lead.
These atoms form extremely fine aerosol particles called radon
daughters or radon progeny, which are also radioactive; they are
especially toxic in that they lodge deep in the human lung where they
emit cancer-producing alpha particles. Radon progeny, both attached
to larger aerosol particles and unattached, can be captured by
particulate air filters. Radon gas itself may be removed with activated
carbon but in ACMV systems, this method costs too much for the
benefit derived. Control of radon emission at the source and
ventilation is the preferred method of radon control.

D5 EQUIPMENT/MATERIALS PART C: TREATMENT AND


CONDITIONING MEDIA

D5.1 Outdoor Air Pre-conditioner

All dehumidifiers specified in the Particular Specification shall


comply with the minimum energy efficiency as specified in this
General Specification unless otherwise specified in the Particular
Specification. The outdoor air pre-conditioner system employing
wasted energy recovery equipment shall conform to the followings: -

D5.1.1 Specification of Desiccant Type Outdoor Air Pre-


conditioner

(a) General

The pre-conditioner shall comprise a 3 molecular


sieve Potassium Aluminosilicate coated total
energy wheel, an exhaust fan, an outdoor air fan
and air filters in both fresh and exhaust streams
(upstream of the fan). These components shall be

Part D AC_GS
Page 6 of 30 2017 Edition
housed in a common insulated casing and shall be
suitable for mounting in any orientation.

(b) Casing

(i) The casing shall be constructed from 1 mm


(Gauge 20) galvanised steel sheet with
epoxy powder coating. The interior shall be
insulated with at least 12 mm thick
insulation material in order to prevent
condensation on the interior and exterior of
the casing.
(ii) Removable access panel of suitable size
shall be provided for replacement of filters
and inspection of fans and wheel. The
access panels shall be perfectly sealed and
hinged to the casing.

(iii) Four sets of 230 mm diameter flanged


collars shall be provided for the connection
of fresh air, supply air, return air and
exhaust ductworks.

(iv) A control panel shall be provided in the


casing, together with termination blocks,
for the connection of electricity supply.

(c) Fan and Motor

(i) The outdoor air and exhaust air fans shall


be single inlet, single width, forward curve
centrifugal fans. The blades shall be
designed for maximum efficiency and quiet
operation. Impellers shall be statically and
dynamically balanced. The exhaust air fan
and the fresh air fan shall be driven by the
same motor on a common shaft.

(ii) The motor shall be standard NEMA frame


with open drip-proof enclosure and shall be
suitable for 220V, single phase, 50 Hz
electricity supply.

(iii) The motor shall have the minimum


efficiency complying to Section C7 of this
General Specification.

(d) Total Heat Recovery Wheel

(i) The total heat recovery wheel shall be in the


form of a disc and of rotating type. The
wheel is the media for sensible and latent
heat transfer between fresh air and exhaust
Part D AC_GS
Page 7 of 30 2017 Edition
air. The wheel shall be driven by a motor
and rotate across the intake and exhaust air
streams.

(ii) The wheel shall be made from aluminium


and coated with a layer of ceramic material
to resist corrosion; and a layer of desiccant
type non-migrating permanently bonded
inorganic solid adsorbent.

(iii) The desiccant coating shall be sprayed on


or dip-coated and shall not be required to
re-apply onto the surface over the life of the
wheel. The coating shall not support the
growth of bacteria.

(iv) The desiccant shall be able to adsorb water


vapour. The internal pore diameter
distribution inherent in the desiccant being
provided shall limit adsorption to materials
not larger than the diameter of a water
molecule (2.8 Angstroms). The desiccant
shall be potassium aluminosilicate and have
a 3 molecular sieve. Other materials will
not be accepted.

(v) The transfer media coated shall have equal


sensible and latent effectiveness and the
recovery efficiency shall be clearly
documented through an independent test
certification programme conducted in
accordance with ANSI/ASHRAE Standard
84-2013 and AHRI-1060:2005 standards.
The molecular sieve shall have high water
pick up rate at both high and low relative
humidity so as to give a constant
effectiveness over the entire relative
humidity range and to allow the wheel to be
effective at high face velocities up to
5.5 m/s.

(vi) The media shall be able to be cleaned with


low pressure steam or hot water without
degrading or damaging the latent heat
recovery and shall maintain a non-
deliquescent state at all times. The pores of
the desiccant shall be small enough to
prevent from cross contamination.

(vii) The media shall be designed to induce


laminar flow under all conditions inside the
flutes and to enable the flutes to be self-
cleaning (e.g. purging).
Part D AC_GS
Page 8 of 30 2017 Edition
(viii) The wheel shall be independently tested;
shall conform with the requirements of
NFPA-90A:2012 and shall have a flame
spread less than 25 and a smoke developed
less than 50 when both rated in accordance
with ASTM E84-14.

(ix) The cross leakage of wheel shall not be


greater than 5% of total air flow.
(e) Filter

(i) The filter shall be of washable type and


about 25 mm in thickness.

(ii) The filter shall be listed by Underwriters


laboratories as Class 2 and the filter
efficiency shall be 30% to ANSI/ASHRAE
Standard 52.2-2012.

(f) Purge Sector

(i) A purge sector shall be provided in the


wheel so that the exhaust air shall not be
carried over to the supply air.

D5.1.2 Specification of Paper Plate Type Outdoor Air Pre-


conditioner

(a) The paper plate type outdoor air pre-conditioner


shall be the product from a manufacturer holding
the quality assurance standards of ISO 9001:2008/
Corr1:2009 or products having equivalent
functions or performance.

(b) The pre-conditioner shall comprise supply air fan,


exhaust air fan and resin net (washable) filter.
Each pre-conditioner shall comprise a non
flammable heat exchange element as the media for
the enthalpy exchange between outdoor air intake
and exhaust air. The pre-conditioner shall be
designed for cross flow type with a high durability
and reliability, a high performance and low
pressure loss type.

(c) The pre-conditioner shall transfer both sensible


and latent heat with same effectiveness and shall
not support bacteria growth.

(d) The pre-conditioner shall comprise indoor and


outdoor temperature sensors to detect indoor and
outdoor air temperature in order to determine
bypass or enthalpy exchange mode.

Part D AC_GS
Page 9 of 30 2017 Edition
(e) The pre-conditioner shall have 3-steps air flow rate
changeover.

(f) The ON/OFF operation shall be controlled from


the double poles switch installed at the entrance of
the room under the electrical work of the Contract.
However, the remote controller supplied with the
fresh air pre-treated unit shall be installed adjacent
to the unit for maintenance use. The unit shall
have automatic ventilation mode changeover
controlled by the air temperature sensor.

(g) The casing shall be made of galvanised steel plate.


The pre-conditioner shall be insulated with fire
retardant, closed cell, flexible elastomeric thermal
insulation in continuous length, factory applied on
the inner surface. The insulation shall comply
with the requirements as stipulated in Sections B11
and C11 of this General Specification.

(h) The energy efficiency of the motor of the pre-


conditioner shall comply to the requirements as
specified in Section C7 of this General
Specification.

D5.1.3 Specification for Polyester (P.E.) Fibre Type Fresh Air


Pre-conditioner

(a) The Polyester fibre type fresh air pre-conditioner


shall comprise a rotary wheel as the media for
sensible and latent heat transfer between the
outdoor air and the exhaust air.

(b) The wheel shall be fabricated from corrosion


resistant material and supported by bearings,
which can be maintained or replaced without the
removal of the rotor from its casing. It shall be
driven by an electric motor with or without a
gearbox and shall rotate across the two air streams
to achieve the heat transfer. The energy efficiency
of the motor of the pre-conditioner shall comply to
the requirements as specified in Section C7 of this
General Specification.

(c) The casing shall be fabricated from galvanised


steel or equivalent material. Two aluminium filters
shall be fitted on the air inlets of the casing.

(d) The heat transfer media in the rotary wheel shall


be P.E. fibre of 25 to 150 m in diameter with a
surface density of 3.6 kg/m2. The media shall not

Part D AC_GS
Page 10 of 30 2017 Edition
support the growth of bacteria. The efficiencies of
sensible and latent heat recovery shall not be less
than 80% and 50% respectively, based on
ANSI/AHRI 1060:2005.

(e) The media shall be securely held by a structural


spoke system and shall be removable and washable.
It can be cleaned with low pressure steam, water or
light detergent without degrading the heat recovery
effectiveness.
(f) The unit shall have been tested to BS 476 Part 6 or
equivalent and satisfied all stipulated requirements.

(g) The unit shall have a sound pressure level less than
40 dBA at high flow measured at 1.5 m from the
supply air discharge.

D5.2 Rotary Solid Desiccant Dehumidifiers

All technical requirements shall comply with the requirements


stipulated in Clause D5.1 of this General Specification. The type of
reactivation power shall be as specified in the Particular Specification.
Liquid desiccant type dehumidifier shall be submitted for Supervising
Officers approval.

D5.3 Desiccant Type Dehumidifier Air Handling Unit

(a) General

The dehumidifier AHU shall be a combination of desiccant


heat recovery rotor and refrigeration dehumidification system.
Humid inlet process air shall firstly be cooled and dried by the
evaporator and further dried by the desiccant rotor, or
alternative arrangement to be specified in the Particular
Specification. The rotor shall be regenerated by hot air after
the condenser in the heat pump refrigeration circuit, or by
room air as to meet the system design as specified. The
desiccant dehumidifier shall maintain the specified room
relative humidity and temperature when cooling system is
turned off at night time.

Each dehumidifier AHU shall be a complete unit comprising


cabinet, desiccant rotor, heat pump, process air fan,
reactivation air fan, air filters, control panel, access panels, etc.
with a standard and specification same as the air handling unit.
The casing shall be of insulated double skin construction same
as the air handling unit.

(b) Rotor

Rotor shall be high efficiency silica gel or lithium chloride.


The rotor matrix is manufactured from alternative layers of flat

Part D AC_GS
Page 11 of 30 2017 Edition
and corrugated sheets of silica gel or lithium chloride,
chemically bonded into a tissue of inorganic fibres. Rotor
material shall be robust construction, incombustible, non-toxic
and washable. Rotor shall be suitable for non-stop operation
and the service life is minimum 10 years. The rotor shall be
controlled by a variable speed motor in order to maintain the
specified room condition. Rotor shall not have any loose
powder in its structure.

(c) Heat Pump System

Heat pump refrigeration system where specified shall be


integrated into the dehumidifier AHU to pre-cool the process
air and regenerate the rotor. The heat pump system shall
include at least evaporator, condenser, compressor and
throttling device. Refrigerant shall be R-407C, R134a or other
non-CFC refrigerant. The compressor shall be screw or rotary
type with an electric motor. To avoid short cycling, the
compressor shall be protected by a time delay during start up.
Both the condenser and the evaporator coil shall be
manufactured from copper tube with aluminium fins.

(d) Fan

The fan shall be centrifugal type. Fan motor shall be mounted


within the dehumidifiers cabinet. The process air fan and the
reactivation air fan shall provide sufficient static pressure for
the application.

(e) Control

The compressor, process air fan and reactivation fan shall be


cycled on when the outside relative humidity or temperature or
the enthalpy is higher than the pre-set values. The speed of
rotary desiccant wheel shall be varied to control the room
temperature and humidity. Carbon dioxide sensors shall be
installed at the return air stream of AHU to determine the state
of occupancy. When humidification is specified in the
Particular Specification, the humidification process shall be
operated by means of steam humidifier.

D5.4 Electrostatic Precipitators

Electrostatic precipitators shall comply with the FSDs requirements


and shall be of the type under the FSDs approved material list.
Average efficiency of the auto clean electrostatic filter shall not be
less than 90% rated at ANSI/ASHRAE 52.2-2012 "Method of Testing
General Ventilation Air-Cleaning Devices for Removal Efficiency by
Particle Size". Auto clean electrostatic filter shall consist of a
washer/adhesive applicator section and an ioniser-collector section,
with overspray filters, all factory assembled into a sectioned housing
of overall depth not greater than 1 m in direction of airflow. Each

Part D AC_GS
Page 12 of 30 2017 Edition
section of the galvanised steel housing assembly shall incorporate a
pair of hinged, quick opening access doors permitting access for
servicing of all internal components; and a watertight, all welded,
galvanised steel, drain pan and drain connections. Access doors shall
be sealed against air leakage by continuous perimeter gaskets of
closed cell neoprene.

Each ioniser-collector section shall be finished with the required


number of one-piece or multi-piece cells of aluminium construction.
Each cell shall be fitted with stainless steel slides for mounting on the
tracks which form an integral component of the side access housing
and to facilitate removal of cells for servicing. Cell support
framework shall be completely open beneath the ioniser-collector
section to ensure complete drainage of wash water and excess
adhesive, minimising the possibility of short circuits when high
voltage power is restored following completion of the wash cycle.
Cells shall be designed so that high voltage input terminals and the
high volt rated glass or ceramic fill polyseal insulators are located
completely out of contact with the moving air-stream to avoid buildup
of dirt which could permit dissipation of high voltage charge and
reduce air cleaning efficiency. The high voltage bus-bars and
terminals (contactors) shall be inherent to the design of each cell and
shall permit cell removal without disconnecting any high voltage
wiring. Insulators shall be fully exposed, for ease of cleaning, when
cells are removed for service. Cells shall be designed for full face
ionisation and have completely flat collector plates to prevent buildup
of residual, inaccessible dirt accumulations.

Each washer/adhesive applicator section shall incorporate slide-in


type, perforated, galvanised steel air distribution baffles and a header
assembly which connected to the inlet water solenoid valve and to the
adhesive pump by means of copper piping and/or non-snag, expanded
PVC hose with a braided polyester exterior protective cover. Washer
rams, each equipped with multi-directional, 360o washer spray
nozzles, shall be driven by reactive force from inlet water pressure.
The removable brass adhesive nozzles shall be mounted on a separate,
fixed, vertical header forming an integral component of the assembly.
The filter adhesive shall be cold water soluble and non-flammable.
The A/C Contractor shall supply a rotary gear adhesive pump with
bronze impeller and sufficient adhesive for reconditioning cycle.

The washer supply water solenoid valve, the manifold drive motor,
and the manifold limit switch shall be pre-wired to an accessible,
internally mounted. Program timer control, with field adjustable
timer and a timer bypass switch shall be provided to control the
washing cycles. The washer control enclosure access door shall
incorporate a status light to indicate when the reconditioning cycles is
energised. An internal panel is to be equipped with a combination of
LED status lights and display unit to indicate which part of the
reconditioning cycle is in operation. The display unit is to be visible
through a window in the control cover.

Part D AC_GS
Page 13 of 30 2017 Edition
The power shall be of solid state design, having single or multi steps,
relays for remote indication of status of the power and solid state
voltage supply, and "fail-safe" low voltage relays to interrupt power
to the ioniser circuit in the event of a malfunction in the plate circuit.
Power pack covers shall each include neon glow lamps to indicate
status of the power and solid state voltage supply. The power pack
shall also include safety provisions of a circuit breaker, a reset button,
safety type door interlock switches.

D5.5 Electronic Air Cleaners

The electronic air cleaner shall be capable of removing odours of


bacteria, organic and chemical origin and shall also be capable of
reducing airborne bacteria and particulate in the treated area as
specified.

The electronic air cleaner shall be tested by independent laboratory to


show the removal efficiency to be not less than 95% of airborne
bacteria (total count), 95% of airborne particulate of 0.5 micron to 5.0
micron, 95% of cigarette smoke particles, 80% of odours and 95% of
hydrogen sulphide.

The maximum output voltage of the electronic air cleaner shall be


less than 3,000 volts.

The electronic air cleaner shall not generate ozone in excess of 0.05
part per million by volume(ppmv) of air circulating through the air
cleaner according to the standards specified by the Food & Drug
Authority (FDA) of USA.

A stainless steel mounting flange shall be provided for mounting the


electronic air cleaner to the air plenum of the air handling equipment.
The electronic air cleaner shall be interlocked with the respective
blower electrically and mechanically so that it can be safely switched
off when the fan of the blower stops. The electronic air cleaner shall
be wired so that the units may be unplugged and removed for regular
servicing. The electrical wiring shall conform to the relevant safety
standards.

The electronic air cleaner shall consist of a power generator and


screw-in electrode tubes. The length of each electrode shall not be
less than 400 mm. The number of electrodes required shall be able to
handle maximum return air of system application design.

The power generator of the electronic air cleaner shall be able to


operate on the single phase mains power supply. The power
generator shall be equipped with built-in regulator for output
adjustment. The power generator shall also be fitted with on/off
switch, on/off indicator lamps, output regulating rotary switch,
overload circuit breaker and electrode tube sockets.

The electrode tubes shall consist of screw-in base and a glass tube.
The electrode tube shall be protected with a stainless steel mesh and
Part D AC_GS
Page 14 of 30 2017 Edition
shall be earthen by means of a firmly fixed grounding wire to the
power generator.

The air purifier shall be controlled in auto or manual mode. In auto


mode, the electronic air cleaner shall be switched on/off at a pre-
determined time period.

The electronic air cleaner shall not generate ozone in excess of 0.05
part per million by volume(ppmv) of air circulating through the air
cleaner.
All materials used in the air supply stream shall not emit any harmful
if case of fire and shall be tested to surface flammability test UL 94-
5VA and BS 476 Part 6.

D5.6 Germicidal Ultraviolet Air Steriliser

Air steriliser shall be of ductwork mount type. Each steriliser shall


consist of ultraviolet lamps, transformer with enclosure, lamp
supporting rods and inspection glass window. Air steriliser shall be
operated on 220V/1ph/50Hz.

Air steriliser shall have one-pass bacteria removal efficiency at least


90%. The selection of UV air steriliser shall be based on face air
velocity, temperature and ductwork size. Detail selection methods
shall be submitted to the Supervising Officer for approval.

The UV lamps shall be manufactured of special short-wave


transmitting glass or quartz. The UV lamps shall emit UV at the 200
nm to 300 nm mercury spectral line, known as germicidal, or
shortwave ultraviolet. Each lamp shall not consume power more than
40W but emit pure UVC irradiation not less than 120 micron
meter/cm2 measured at 1 metre from source after 100 hours burning
at 25 oC. The total UV light intensity shall be not less than 360
micron W/cm2 per 1.0 m3/s airflow measured at 1.0 m from source.

To prevent eye and skin injuries, sources of UV light must be


conspicuously labelled with a warning attached to the housing of the
source. The warning sign should state: -

WARNING

DO NOT EXPOSE EYES AND SKIN TO ULTRA-VIOLET


LIGHT
RAYS ARE HARMFUL TO UNPROTECTED EYES AND SKIN

Part D AC_GS
Page 15 of 30 2017 Edition
The UV steriliser lamps shall be positioned perpendicular to the air
flow at velocity less than 5.0 m/s to allow maximum exposure.
Access door with safety current-cut switch shall be provided to access
the UV lamps. Suitable inspection window shall be provided on the
equipment. Baffle type filters on the ductwork openings shall be
provided in case that direct UV light may be emitted out of the
ductwork openings. Safety labels shall be provided on the ductwork
access panel. Additional water-tight metal enclosure shall be
provided to house the transformer enclosure if there is a chance of
water spraying into the equipment.
The operating life of the UV lamps shall be at least 10,000 hours.
The operation of the UV air steriliser shall be interlocked with the
blower/air handling unit such that the UV air steriliser is operated
when the blower/air handling unit is operated. The steriliser shall be
switched off with an indicator light on when the maintenance access
is opened.

The generated ozone from the air steriliser shall be at a level less than
0.05 ppmv of air circulating through the air steriliser according to the
standards specified by the Food & Drug Authority (FDA).

Safety precautions shall be taken in the installation and maintenance


of the air steriliser to prevent the leakage of UV light. When the UV
exposure level exceeds 0.2 micron W/cm2 over 8 hours, baffle filters
shall be installed for those air discharge louvres to reduce UV light
intensity level.

Remote control panel shall consist of circuit breaker, auto-off-manual


switch, hour run meter, ampere meter, pilot lamp and fine-wire fuse.

On-site performance test shall be conducted to verify: -

- The total bacteria count (TBC) removal efficiency;


- Background UV intensity; and
- Ozone level.

Pressure sensors shall be located at both upstream and downstream


across filter section for PAU/AHU. When comparing the pressure
differential of the upstream and downstream with reference to a
reference value, the controller shall send either one of the following
signals to the control panel: -

- Filter normal;
- Filter leakage and alarm signal; or
- Filter clog and alarm signal.

D5.7 Water Scrubbers

(a) General

Part D AC_GS
Page 16 of 30 2017 Edition
(i) Horizontal cross flow fibreglass reinforced polyester
(FRP) foul air water scrubber system shall be supplied
and installed for central air treatment of odour, gas,
liquid and solid contaminants prior to discharge to
outside of the building.

(ii) The water scrubber systems shall be outdoor type


tailor-made and designed by a single recognised
scrubber specialist as a complete package to suit the
available space and in accordance with the specified
performance and requirements in the Particular
Specification. Every major components such as the fan,
recycle pumps, scrubber section completed with
packing, mist eliminator and nozzle shall be compatible
in all aspect and wholly imported, factory built and
assembled as complete units before shipping. The only
field connections required on Site shall comprise only
external control circuitry, pipeworks, fan and ductwork
connections.

(iii) Scrubber section shall be of horizontal draw-through


cross-flow packed tower bed type with mist eliminator
at the last section of the scrubber. Each complete
scrubbing system shall comprise a scrubber section
with recycle pumps, chemical feed pumps, fan,
chemical tanks, silencers, instrumentation, acoustic
enclosure and all necessary controls as well as any
other accessories required to build up a functional plant
to the satisfaction of the Supervising Officer.

(iv) All material and components adopted in the scrubbing


system shall be suitable for operation with selected
chemicals including sodium hypochlorite, sodium
hydroxide and the resulting by-products of scrubbing.

(v) Those items specified to be constructed of fibreglass


reinforced polyester (FRP) resin shall conform to
relevant BS or ASTM standards and shall be stabilised
against ultraviolet degradation. This shall apply to the
scrubbers and fan. The resin shall be Duracor 6000-6
series or products having equivalent functions or
performance and approved.

(vi) All internal wetted bolts and fasteners, and all external
bolts and fasteners including anchor bolts and flange
bolts shall be high grade AISI 316 stainless steel or
products having equivalent functions or performance.

(vii) Scrubber section shall be finished with three nos. of


recycle pumps, one of which as standby. Manual
selection switch shall be provided to enable selection of
either one of them as standby pump. The pumps shall

Part D AC_GS
Page 17 of 30 2017 Edition
be direct coupled to TEFC motor, self-priming,
horizontal end suction, corrosion resistant and
centrifugal type. Accessories such as pressure gauges,
stop and vent cocks shall be provided for each pump.
The flow rate shall be determined by the A/C
Contractor to suit the performance specification with
adequate flow rate and pump heads to cater for the
piping and scrubber paint friction losses.
The pump casing, impeller shall be of rigid PVC and
the impeller shaft shall be of stainless steel to be
approved by the Supervising Officer.

(viii) A detail design report on the offered water scrubber


system shall be submitted for agreement with
Supervising Officer. Full technical details shall be
provided including at least the followings:-

I) Certificates and documentary evidence of


excellent chemical resistance of all material,
component and equipments adopted for the
operation with the selected chemicals and
specified application; and

II) Detail information and calculations on:-

- Chemical reaction formulation and


design criteria;

- Selection of the type and depth of


packing, mist eliminators, nozzles, etc.
with manufactures test data or
recognised standards; and

- Scrubber overall height and dimension,


packing depth, mist eliminators depth, etc.

(b) Construction

(i) The mist eliminator section shall be replaceable,


corrosion resistant packing, mesh type or other
approved type fabricated of fibreglass reinforced
polyester or products having equivalent functions or
performance and approved. The eliminator section
shall be in modular form of adequate surface area and
strength to withstand the handling air flow area and
pressure.

(ii) The scrubbing liquid distribution system shall be the


spray type or other approved type, sized for the flow
rate to suit the design of the scrubber system to meet
specified performance. Material of construction shall
be fibreglass reinforced polyester.

Part D AC_GS
Page 18 of 30 2017 Edition
(c) Control

(i) The water scrubber system shall be capable of both


automatic and manual operation. In "auto" mode, the
central exhaust fan shall be started or stopped
automatically. The scrubber exhaust fan shall be inter-
locked with the recycle pumps operation such that it
will not be operative unless the pumps are operating.
The 2-way motorised valve and flow regulating valve at
water feed-in pipe shall be provided and interlocked
with the fan.

(ii) Chemical feed pumps shall dose proportionately to


maintain the desired concentration of the scrubbing
liquid. NaOH shall be controlled with pH analyser to
maintain a pH value of 8 to 9 while NaOC1 shall be
controlled with oxidation-reduction-potential (ORP)
analyser to maintain an ORP value of 300 to 400 mV or
to values recommended by the manufacturer in order to
comply the performance specification.

(iii) Low level sensors in the water scrubber chamber shall


be provided and installed to give audio and visual
warning signals at the local & remote control panels
and to stop the circulating pumps during low water
level condition.

(iv) Corrosion resistance low level sensors shall be


provided and installed for each of the chemical tanks to
give audio and visual warning signals at the local &
remote control panels during low chemical level
condition.

(v) Flow switch shall be provided and installed at the feed-


in water pipe to give audio and visual warning signals
at the local & remote panels during "no flow" condition.

(vi) In "manual" mode, the fan and pumps shall be operated


by means of start/stop buttons at the water scrubber
control panel.

(vii) Local and remote control panels shall be provided for


the water scrubber systems as specified in the Particular
Specification. Local/remote selector switch shall be
provided at the local panels for choice of control mode.
In "remote" mode, the water scrubber system shall be
started or stopped via manual push buttons at the
remote control panel. The scrubber exhaust fan shall be
interlocked with the recycle pumps operation such that
it will not be operative unless the recycle pumps are
operating.

Part D AC_GS
Page 19 of 30 2017 Edition
(viii) In "Local" mode, the fan and pumps shall be operated
by means of start/stop buttons at the local control panel.

(ix) Provision shall be provided for roller shutter for refuse


collection point, poultry scalding room and other areas
as specified in Particular Specification to interlock the
operation of the roller shutter with the scrubber
operation.

(x) The remote panel for the water scrubber system shall be
of constructions as specified in the Particular
Specification or products having equivalent functions
or performance as approved and weather-proof suitable
for outdoor installation.

(d) Fan

(i) Motor driven fans shall be provided for each scrubber


unit and shall be of sufficient capacity and horsepower,
as indicated in the Particular Specification to deliver the
required volume of air against the total pressure losses
in the air intake, duct pickup systems, packed bed, mist
eliminator, silencers and ducting.

Fans shall be of high efficiency and low speed


backward curved types with lowest noise level suitable
for outdoor application. Sound power level spectrum
shall be submitted for approval and the data shall be
verified on Site as specified.

(ii) Fan housings, flanges and impellers shall be


constructed of a fibreglass reinforced polyester (FRP)
laminate using Duracor 6000-6 series or products
having equivalent functions or performance as
approved.

(iii) Inlet connections shall be Neoprene slip type flex


connector with stainless steel draw-bands. Outlet
connection shall be a rectangular undrilled flange.

(iv) Each of the blowers shall have V-belt drive with a


minimum service factor of 1.5 times the rated brake
horsepower of the fan motor and shall be equipped with
heavy-duty, self aligning sealed ball bearings.

(v) Fan shafts shall be carbon steel and oversized to run


above critical speed. A steel hub encapsulated with
FRP shall be provided to a point flush with the housing.
Wheel and shaft assemblies shall be statically and
dynamically balanced in two directions according with
recognised international standards.

Part D AC_GS
Page 20 of 30 2017 Edition
(vi) The fan base shall be made of corrosion material of
sufficient strength or carbon steel treated with anti-
corrosion coatings approved by the Supervising Officer.
No metal parts including bearing supports shall be
exposed to the corrosive air stream.

(vii) Fans shall come completed with motors, drives, belts,


FRP motor and drive canopy, housing drains, access
doors and flexible connectors for inlet and outlet.

(viii) Each fan shall be provided with a horizontal squirrel


cage induction type motor of sufficient power such that
no point on the fan curve requires more than the
nameplate horsepower of the motor furnished.

(ix) Each electric motor shall be suitable for 380 V,


3-phase, 50 Hz continuous 24 hours operation.

(x) The motor enclosure shall be totally enclosed, fan


cooled and suitable for outdoor application.

(xi) The motors shall be designed, constructed and tested in


accordance with all the requirements of the applicable
standards of the IEEE, NEMA and ANSI.

(xii) The fan static pressure to suit the ducting configuration


and proposed equipment with calculations shall be
submitted for Supervising Officers approval.

(xiii) Acoustic treatment, such as silencers and acoustic


enclosure, shall be provided to ensure the noise break
out to adjacent areas is at an acceptable level complied
with the requirement of the Environmental Protection
Department.

(xiv) Silencers shall be of packless type or to be completed


with adequate coating and shall be suitable for the
chemical corrosive environment. The exhaust fan and
driving motor shall be housed in an acoustic G.I. sheet
enclosure as specified in the Particular Specification.

(e) Chemical Feed System

(i) Each scrubber system shall be provided with a


complete chemical feed system for storing and feeding
the chemicals required. All adequate provisions shall
be provided for the storage, installation and operation
of the chemical solutions in compliance with the Fire
Services Regulations as the scrubbing chemical
solutions used are in the list of Dangerous Goods
Category. The Chemical feed system shall comprise

Part D AC_GS
Page 21 of 30 2017 Edition
chemical storage tank and feed pump for each
scrubbing chemical solution, piping and valves, and all
necessary controls.

(ii) Chemical storage tanks shall be vertical flat bottom


type made of FRP with scale and lockable screw lid and
shall be suitable for storing the scrubbing chemical
solution. Each tank shall have a minimum effective
capacity of holding the exempted quantity at specified
concentration allowable by the FSD, typically of 250
litres.

(iii) Chemical metering pumps shall be solenoid - operated


diaphragm pump for the type of weatherproof
protection. The pumps shall be operated on 220
V/single phase/50 cycles. Housing and liquid end shall
be corrosion proof as well as dust and waterproof to
protection Class IP65. Housing shall be light-metal
alloy die. Solenoid shall be proof against over-load and
excessive counter pressure such that it will not result in
failure. Pumping capacity shall be adjusted in ratio of
1:10 through stroke length and 1:25 through stroke
frequency, accessories shall include PVC dosing valve
and foot valve.

(iv) pH and ORP Control

Each scrubber shall be provided with pH and ORP


probes suitably located for analysing the contents in the
scrubber sump. Probes shall meet the following table:-

Table D5.7 Technical Requirement of Measuring


Probes
pH Probe ORP Probe
Range 0 to 14pH 0 to 990 mV
Stability 0.03pH units per 0.5 mV per 24
day, non- hours, non-
cumulative cumulative
Temperature 0 to 60 oC 0 to 60 oC
Pressure Rating 4.8 kPa 4.8 kPa
Wetted Glass Glass
Materials
Accuracy 0.1 pH unit 5 mV
Sensitivity

Each probe shall be supplied with analyser and level


alarm at the local and remote control panels and they
shall be actuated when the chemical levels at chemical
tanks are lower than the present values.

Part D AC_GS
Page 22 of 30 2017 Edition
D6 CONFORMITIES OF IAQ DESIGN OBJECTIVE AND COMPLIANCE

One or more software tools for predicting the performance of the IAQ
equipment and system shall be proposed by the A/C Contractor and submitted to
the Supervising Officer for approval. The proposed tool shall demonstrate the
conformities of IAQ objectives performed by the IAQ equipment and system.

Testing and commissioning of IAQ equipment and system shall be carried out
for the conformities of IAQ design objective and to the satisfaction of the
Supervising Officer or to meet the requirements as stated in the Particular
Specification.

The details of T&C work are detailed in T&C Procedure No.1 clause 4.2.5
IAQ Equipment and System Test under Part H: Inspection, Commissioning and
Testing. Upon satisfactory completion of all the tests, a certificate of IAQ
compliance level of building according to the format and detailed requirements
as specified in the Particular Specification shall be submitted to the Supervising
Officer for approval.

D7 IAQ ASSESSMENT AND METHODOLOGIES

IAQ assessment shall be performed as the last part of the testing and
commissioning process upon completion of the ACMV installation. Further
assessments shall be done six months after the building has been occupied and at
two months before the expiry of the Maintenance Period, i.e.

(a) First Assessment - After testing & commissioning

(b) Second Assessment - Six months after the date of occupation of


the building or substantial completion

(c) Third Assessment - Two months before the expiry of the


Maintenance Period

IAQ compliance shall be proved by results of measurements. In addition, an


end user satisfaction survey shall be conducted before expiry of the Maintenance
Period.

The A/C Contractor shall provide recommendation to improve the indoor air
quality condition for the approval of the Supervising Officer should any one of
the three assessments fail to meet the requirement.

The details of measurements, assessment and methodologies are described in


T&C Procedure No.1 clause 4.2.5 IAQ Equipment and System Test under
Part H: Inspection, Commissioning and Testing.

Part D AC_GS
Page 23 of 30 2017 Edition
D8 OPERATION AND MAINTENANCE

D8.1 O & M Matters

In addition to the contractual requirements of training, operation and


maintenance as described in Part I: Operation and Maintenance
Requirements for the ACMV installation, similar requirements for
Indoor Air Quality installation as mentioned below shall be met.
D8.2 Training Requirements

Facilities familiarisation and training programme shall be provided to


ensure that the owners operation and maintenance staff acquire full
knowledge and appreciation of all aspects of the design, operation,
breakdown attendance, routine maintenance and diagnosis of
installation, which have effects on the indoor air quality.

A training proposal shall be submitted to the Supervising Officer for


approval at least three months prior to completion of the ACMV
installation. Training shall include both aspects of operation and
maintenance as well as trouble shooting procedures and the use of
special tools.

D8.3 Operation and Maintenance Requirements

Full responsibility shall be held for the following, in addition to those


required for O&M of ACMV installation mentioned elsewhere in the
specification, within the Maintenance Period: -

(a) Instruction to Employers O&M Staff

Training shall be provided to Employers staff involved in


operation and maintenance to understand the design intent, to
operate and to maintain the IAQ system correctly, to achieve
and maintain the designed IAQ parameters. An O&M manual
shall be prepared by qualified personnel.

(b) Attendance to Faults and Complaints

IAQ faults and complaints shall be attended and rectified for


arising from defective work and materials. Report shall be
submitted to the Supervising Officer for these incidents.

(c) Periodical IAQ Audit with Logs and Records

Periodical IAQ audit shall be carried out as specified to


ascertain the status of the IAQ parameters and submit
records/logs with details such as date, results of audit,
measurements and name of person conducting the audit to the
Supervising Officer.

(d) IAQ Assessment as Specified with Logs and Records

Part D AC_GS
Page 24 of 30 2017 Edition
In addition to the IAQ assessment during testing and
commissioning, IAQ assessment shall be carried out six
months after building occupation and at the expiry of the
Maintenance Period. IAQ compliance shall be proved by
results of measurements. In addition, a satisfaction end user
survey report shall be submitted to the Supervising Officer for
endorsement. According to the agreed end user report, an end
user satisfaction survey shall be conducted before the expiry of
the Maintenance Period.

D8.4 Maintenance Concept

IAQ maintenance should be an on-going exercise consisting of


periodic IAQ assessment, identification of IAQ problems and
deficiencies as well as follow-up IAQ improvement scheme to bring
the IAQ to the designed and acceptable standard. The following are
general maintenance items that need to be carried out regularly during
the Maintenance Period: -

Service requirements shall include functional inspection, cleaning,


adjustment, sample test and rectification. The detailed arrangement
shall be: -

(a) Monthly Services: -

(i) Outdoor air intake equipment including screens and


louvres;
(ii) Air pre-filters;
(iii) Cooling coils and heating coils;
(iv) All trays and sumps;
(v) Condensate drains and water traps;
(vi) Water cooling towers;
(vii) Water treatment system; and
(viii) Boiler and Humidifier.

(b) Quarterly Services: -

(i) Air dampers;


(ii) All types of filters including HEPA filters, electrostatic
filters, chemical filters, carbon filters;
(iii) Air Cleaners;
(iv) UV light chambers; and
(v) Check system performance.

(c) Half-yearly Services: -

(i) IAQ sensors such as thermostat, humidistat,


pressurestat, CO2 sensors, air movement sensors;
Part D AC_GS
Page 25 of 30 2017 Edition
(ii) Humidifiers, dehumidifiers;
(iii) Inspect all components of the ventilation system for
cleanliness and microbial growth, and clean them as
necessary; and
(iv) Volume control dampers.

(d) Annual Services (before the expiry of Maintenance Period): -

(i) Inspect and clean as necessary accessible parts of


ductwork and air grilles;
(ii) Fans, fan wheels, fan blades, belt drives;
(iii) AHUs, fan coil units, VAV boxes and terminal units;
(iv) Supply and return air plenums;
(v) Variable speed drive control for fans; and
(vi) Inspect aluminium foil, paints or other concrete sealing
layers and wall surface which are meant to stop radon
gas emission and touch up if applicable.

D9 HOUSEKEEPING AND ENERGY EFFICIENCY RELATING TO IAQ


ISSUE

Indoor air quality is affected by the quality of maintenance and the materials
used and procedures in operating and maintaining the building components
including the ACMV system. Contractors are required to familiarise with
building systems in general and with the features of the building in particular
which are important resources in preventing and resolving indoor air quality
problems in the Maintenance Period.

To best respond to indoor air quality concerns, the A/C Contractor shall have
good understanding on how the building activities affect indoor air quality. The
housekeeping procedures in relation to the following items shall be carried out: -

D9.1 Equipment Operating Schedules

(a) Confirm that the timing of occupied and unoccupied cycles is


compatible with actual occupied periods, and that the building
is flushed by the ACMV system before occupants arrive;

(b) Maintain essential ventilation or suitable air treatment in areas


with long unoccupied periods to prevent mould growth in hot
humid climates; and

(c) Check control and use free air cooling mode at mild season.

D9.2 Control of Odours and Contaminants

(a) Maintain appropriate pressure relationships between building


usage areas;

Part D AC_GS
Page 26 of 30 2017 Edition
(b) Avoid recirculating air from areas that are strong sources of
contaminants (e.g. smoking lounges, chemical storage and
printing areas);

(c) Ensure adequate local exhaust depending on different Sites


and as specified in the Particular Specification for activities
that produce odours, dust, or contaminants, or confine those
activities to locations that are maintained under negative
pressure (relative to adjacent areas);

(d) Make sure paints, solvents and other chemicals not being
stored in the ACMV plant rooms;

(e) Maintain regular maintenance depending on different Sites and


as specified in the Particular Specification on local filter traps
and adsorbents; and

(f) Carry out routine cleansing with dry steam only.

D9.3 Ventilation Quantities

Compare outdoor air quantities to the building design goal and the
IAQ targets, and make adjustments as necessary and the adjustments
should be carried out without compromising the IAQ objectives.

D9.4 ACMV Equipment Maintenance Schedules

(a) Inspect all equipment regularly as per manufacturers


recommended maintenance schedule to ensure that they are in
good condition and are operating as designed (i.e. as close to
the design set points for controls as possible); and

(b) Provide scrupulous maintenance on components that are


exposed to water, e.g. drainage pans, coils, cooling towers,
humidifiers, etc. to prevent microbiological growth and the
entry of undesired microbiological organisms or chemicals
into the indoor airstream.

D9.5 ACMV Inspection

(a) Prepare checklists for thorough inspection of the ACMV


equipment in the building to avoid missing items such as small
exhaust fans which may operate independently from the rest of
the ACMV system and are often ignored during inspections;

(b) Maintain proper records on alteration/addition/removal of the


ACMV installation for reference on IAQ impact due to
changes in function, capacity, or operating schedule;

(c) Maintain proper records on occupant complaints on ACMV


services for easy comparison if IAQ problems arise; and

(d) Change in occupancy/space function.


Part D AC_GS
Page 27 of 30 2017 Edition
D9.6 Building Maintenance Schedule

(a) Schedule maintenance activities that interfere with ACMV


operation or produce odours and emissions (e.g. painting, false
ceiling or roofing operations) so that they are executed when
the building is unoccupied; and

(b) Inform occupants when such activities are scheduled and, if


possible, use ventilation to ensure that ductwork and odours
are confined to the work area.

D9.7 Preventive Maintenance

Provide adequate preventive maintenance and prompt attention to


repairs of the ACMV equipment in order to maintain the ACMV
systems in suitable control conditions so as to deliver good indoor air
quality.

(a) General elements of preventive maintenance plan shall include:


-

(i) Periodic inspections, cleaning, and service as warranted;


(ii) Adjustment and calibration of control system
components; and
(iii) Maintenance equipment and replacement parts that are
of good quality and properly selected for intended
function.

(b) Critical ACMV system components that require preventive


maintenance in order to maintain comfort and deliver adequate
ventilation air shall include: -

- Outdoor air intake opening;


- Damper control;
- Air filters;
- Drip pans;
- Cooling and heating coils;
- Fan belts;
- Humidification and dehumidification equipment and
controls;
- Distribution system; and
- Exhausts, exhaust fans and pressure relief fans.

Provide adequate training to the maintenance staff to ensure


that they have adequate understanding of the overall system
design, its intended function, and its limitations.

Part D AC_GS
Page 28 of 30 2017 Edition
D10 TRAINING AND LICENSING REQUIREMENTS

Training and licensing are required for IAQ workers carrying out IAQ
installation, testing and commissioning, assessment and measurement, operation
and maintenance or personnel supervising these works.

Recognised training includes training and certificates from the following: -

- Relevant professional or academic institutions;


- Vocational Training Council;
- Equipment supplier; and
- Other training organisations recognised and accepted by the Supervising
Officer.

Installation, testing, commissioning, assessment, measurement, operation and


maintenance shall be carried out by IAQ licensed personnel who must have
recognised training or adequate experience accepted by the Supervising Officer.

D11 CERTIFICATION AND REGISTRATION

IAQ assessment shall be carried out upon completion of ACMV installation, six
months after date of occupation of the building or substantial completion of the
Works stated in the certificate of completion issued in accordance with the
Contract and at the expiry of the Maintenance Period. After each assessment, a
report will be issued by the A/C Contractor recording the measurement made
and the readings taken from the IAQ parameters as specified in the Particular
Specification. Before expiry of Maintenance Period, in addition, the A/C
Contractor shall also carry out an IAQ satisfaction survey to ascertain the
situation of the IAQ in the building and the feedback of the occupants. Quantity
of survey and report on satisfaction survey shall be submitted to the Supervising
Officer for approval.

For each of the three assessments, the methods of measurement, the models and
serial numbers of the instruments with date of calibration used in the
measurement and assessment, the locations of assessment and sampling as well
as the results of the assessment (IAQ compliance or not) and the readings
obtained shall be reported. The report forms shall be submitted and approved by
the Supervising Officer one month before the measurement and assessment
proceed. These Forms shall be endorsed by the responsible personnel of the
A/C Contractor, who must be qualified personnel under any one of the following
categories. Endorsed Forms (verifying IAQ compliance) shall be submitted to
the Supervising Officer who will then verify that the Installations comply with
the relevant IAQ requirements.

Recognised qualified personnel for assessing and verifying IAQ compliance


shall be: -

D11.1 Registered Professional Engineer in building services or mechanical


discipline under the Engineers Registration Ordinance (Cap. 409) or

Part D AC_GS
Page 29 of 30 2017 Edition
D11.2 Person with other approved and recognised qualification and/or
experience as accepted by the Supervising Officer.

After verification of IAQ compliance, A/C Contractor shall submit a certificate


signed by recognised qualified personnel and guidelines for maintaining IAQ
level to the Employer.

Part D AC_GS
Page 30 of 30 2017 Edition
PART E - ENERGY EFFICIENCY AND ENERGY CONSERVATION

E1 GENERAL

All equipment provided by the A/C Contractor for the Installations shall
conform to the highest efficient rating of energy efficiency and energy
conservation requirement as stipulated in this General Specification, and/or the
Building Energy Code.

In case of any non-compliance, the A/C Contractor shall submit full justification
with technical data supporting the deviation from the requirements as specified
in this General Specification and the Building Energy Code.

The A/C Contractor shall also refer to other Sections of this General
Specification for the energy saving provisions.

E2 MINIMUM COEFFICIENT OF PERFORMANCE (COP) OF MAJOR


AIR CONDITIONING AND VENTILATION EQUIPMENT

All major air conditioning and ventilation equipment shall have the minimum
COP for both cooling and heating meeting the requirement as stipulated in this
General Specification and the Building Energy Code.

The A/C Contractor shall submit documents and calculation showing the
minimum COP for both cooling and heating of the following major air
conditioning and ventilation equipment: -

- Air-cooled unitary air conditioner;


- Water-cooled unitary air conditioner;
- Air-cooled water chiller or heat pump with reciprocating compressor;
- Air-cooled water chiller or heat pump with centrifugal compressor;
- Air-cooled water chiller or heat pump with screw or scroll compressor;
- Water-cooled water chiller or heat pump with reciprocating compressor;
- Water-cooled water chiller or heat pump with centrifugal compressor;
- Water-cooled water chiller or heat pump with screw or scroll compressor;
- Total energy heat pumps utilising both cooling and heating output; and
- A/C Equipment with simultaneous cooling and heating.

The A/C Contractor shall note that the system energy shall be the main sources
of energy in achieving the HKSARs IAQ Objectives as specified under Part D
of this General Specification. Energy discharged to the environment shall be
kept to minimum. Energy reclaim from the heat dissipating condenser and from
the air conditioning exhaust shall be incorporated wherever practical. Electric
reheat or re-heating using only hot water boilers without recapturing the wasted
energy shall not be accepted. The A/C Contractor shall refer to the Contract
Drawings and Particular Specification for exact requirements and details. The
Part E AC_GS 2017 Edition
Page 1 of 5
A/C Contractor shall also check with the major equipment manufacturers and
submit proposal in relating to the wasted energy reclaim as specified in the
Contract Drawings and Particular Specification to the Supervising Officer for
consideration.

E3 MINIMUM EFFICIENCY OF FANS, PUMPS AND MOTORS

The minimum energy efficiency of all electrical driven motors shall comply
with the requirements as specified in Sections C5 and C13 of the Electrical
General Specification and the Building Energy Code.

The minimum efficiency of pumps and fans shall comply with the requirement
as specified in Sections C3 and C13 of this General Specification.

The A/C Contractor in selecting fans for the air-conditioning and ventilation
system(s) shall comply with the total fan motor power requirements as stipulated
in the Building Energy Code.

The A/C Contractor shall note that the minimum efficiency specified in this
General Specification shall be the absolute minimum requirement. All enhanced
or higher quality of products shall be offered if available.

E4 THERMAL INSULATION

The A/C Contractor in selecting the thermal insulation for chilled water pipes,
refrigerant pipes, air ductworks and air handling units shall comply with the
minimum thickness requirements as specified in Clause C11.5.

E5 SENSING DEVICE

All sensing device for monitoring the air quality shall comply with Clause
C4.4.6 of this General Specification.

E6 MOTION DETECTING SENSING DEVICE

In case of motion detecting system controlling the air conditioning supply to the
conditioned space is specified, the motion detection sensor shall meet the
following requirements: -

E6.1 Movement detectors shall be of passive infrared microwave verified


type which shall detect movement by passive infrared technology and
also by microwave technology. Reaction of A/C control system shall
only be activated if both the passive infrared and microwave
components of the sensor have been activated within a specified time.

E6.2 For the passive infrared component, the detectors shall keep constant
monitoring of the "thermal pattern" of the controlled area. Any
change of the infrared energy within the controlled area shall trigger
Part E AC_GS 2017 Edition
Page 2 of 5
the control of the passive infrared component. The infrared beam
shall not penetrate glass, thin wall or plastics.

E6.3 The microwave component shall keep constant monitoring of the


controlled area by detecting the Doppler shift of microwave emitted
from the detector. The detector shall generate "K" band microwave
frequency of around 24 GHz and emit it as unmodulated
electromagnetic field to the controlled area or space.

E6.4 The range of detection shall be adjustable from 6 m to 20 m, the


pattern of detection shall be 90o adjustable 45o horizontally and -7o
vertically. The velocity of the target to be detected shall be 0.15 3m
per second.

E6.5 The sensitivity of the passive infrared component shall be 2 oC at a


target velocity of 0.6 m per second.

E6.6 The electronic circuit of the detectors shall have immunity to radio
frequency interference and electromagnetic interference, and shall be
insensitive to thermal and optical source of interference.

E6.7 LED signals indicating trouble shall be lit upon

(a) Excessive temperature;

(b) Fall in input voltage below the correct performance of the


detector is assured; and

(c) Interruption of microwave operation, e.g. due to masking or


failure of the microwave component.

E6.8 A LED shall be provided to indicate on/off status of the walk test
mode.

E6.9 The detector shall be one piece and shall be housed in a tamper-proof
housing with tampering switches. Alarm signal shall be sent to
Intelligent Local Controller when the housing is tampered.

E7 DEVICES FOR ENTHALPY CONTROL OF FREE AIR COOLING

In case of free air cooling and enthalpy control is specified, the system shall
meet the following requirements: -

E7.1 The free air cooling control system shall be energised to monitor the
system conditions when the supply air fan of air handling unit is
turned on.

E7.2 The system shall have an exhaust air fan extracting return air under
free air cooling operation.

Part E AC_GS 2017 Edition


Page 3 of 5
E7.3 Motorised control exhaust air damper shall be installed at the exhaust
air outlet and normally opened at pre-set position. This exhaust
damper shall be interlocked with the exhaust air fan and fully opened
under the free air cooling operation.
E7.4 Motorised control damper shall be provided in the returned air path
for isolating the return air side and supply air side under the free air
cooling mode. This isolating damper shall be normally opened and
fully closed under the free air cooling operation.

E7.5 Motorised outdoor air supply damper shall have minimum setting to
provide the minimum outdoor air supply to the system and shall be
fully opened under the free air cooling operation.

E7.6 Temperature and humidity sensing devices shall be provided in the


outdoor air supply intake to monitor the outdoor air conditions.
These sensing devices shall provide all necessary information to the
system controller which shall determine and operate the free air mode
when conditions meet with the specified criteria.

E7.7 Temperature and humidity sensing devices shall also be installed in


the downstream of the supply air fan to monitor the supply air
conditions. The control system shall allow the top priority to these
sensing devices to override the signal of free air cooling when the
conditions of the supply air fails to meet with the specified condition.

E7.8 All sensing devices shall comply with the requirement as stipulated
under Clause C4.4.6 of this General Specification.

E7.9 The details and final configuration of free air cooling system shall
comply with the criteria specified under the Particular Specification.

E8 AUTOMATIC CONDENSER TUBE CLEANING SYSTEM

For automatic condenser tube cleaning system, refer to Clause C6.27.

E9 HEAT PIPE INSTALLATION

For heat pipe installation, refer to Clause C3.18.

E10 SOLAR HEATING INSTALLATION

In case solar heating installation for providing low pressure hot water is
specified, all materials and standard of performance shall comply with Clauses
B6.15 and C6.28 of this General Specification.

Part E AC_GS 2017 Edition


Page 4 of 5
E11 DEHUMIDIFIER

All dehumidifiers specified in the Particular Specification shall comply with the
minimum energy efficiency as specified in this General Specification unless
otherwise specified in the Particular Specification. Desiccant type and paper
type outdoor air pre-conditioner systems employing wasted energy recovery for
the latent heat transfer in the exhaust air and outdoor air in the air-conditioning
system shall conform the specification in Clause D5.

The equipment with rated dehumidifying capacity not exceeding 35 litres per
day shall have obtained a Grade 1 Energy Label under the Energy Efficiency
Labelling scheme of the EMSD.

E12 OUTDOOR AIR PRE-CONDITIONER

For outdoor air pre-conditioner installation, refer to Clause D5.1.

Part E AC_GS 2017 Edition


Page 5 of 5
PART F - ACMV SYSTEM WATER TREATMENT
F1 GENERAL

Water treatment for air conditioning water systems as follows shall be carried
out to maintain water in proper "balance" condition (pH, hardness, total
dissolved solids, total alkalinity, etc.) and to comply with the "COP" issued by
the EMSD for requirement not indicated in the General Specification.: -

F1.1 Treatment of sea water for condenser cooling to kill or inhibit marine
growth and to inhibit the formation of scale, slime and foam in the
pumps, pipework and condensers;

F1.2 Treatment of water being circulated between condensers and cooling


towers including the water in the tower;

(a) To inhibit corrosion, scaling, slime and foam formation; and

(b) To sterilise the water to prevent biofouling and the growth of


pathological bacteria such as Legionella Pneumophila.

F1.3 Treatment of chilled water or low pressure hot water in circulation


system to inhibit corrosion, formation of foam, scale and slime in the
pipework and evaporator tubes.

The design, installation, commissioning, testing and operation of the water


treatment system shall be carried out by a water treatment specialist who has at
least five years local water treatment experience in compliance with the
Particular Specification, this General Specification, the relevant parts of the
Code of Practice for Fresh Water Cooling Towers issued by the EMSD, Code of
Practice for Prevention of Legionnaires' Disease issued by Prevention of
Legionnaires' Disease Committee, the Government of the HKSAR, other
currently in force Legislation and Subsidiary Legislation in Hong Kong and
subject to the approval of the Supervising Officer.

F2 FORM OF WATER TREATMENT

Where the types of treatment and plant are specified in the Particular
Specification, the A/C Contractor shall install the plant and equipment as
required.

Where no specific system or treatment is mentioned in the Particular


Specification, the A/C Contractor shall provide a basic water treatment system
in accordance with Clauses F1, F.4, F5 or F7 as appropriate.

The A/C Contractor shall submit drawings and technical information detailing
the set-up of the proposed water treatment equipment, the type of chemicals
used and the treatment proposal to the Supervising Officer for approval prior to
ordering of the equipment.

Part F AC_GS
Page 1 of 13 2017 Edition
The water treatment proposal shall include water specification, method of
analysis and testing recommended by water treatment specialist together with
the testing report format. Bacteria count and identification of existence of
pathological bacteria such as Legionella Pneumophila shall be included in the
water analysis for cooling tower.

The A/C Contractor shall supply the necessary labour, testing equipment and
chemicals for testing and commissioning, pre-cleaning and day-to-day water
treatment of the systems within the Contract Period. In addition, the A/C
Contractor shall also allow for continuing the treatment for the whole
Maintenance Period (including costs for the sampling exercises and laboratory
tests required) until the maintenance certificate is issued.

During the above-mentioned periods, the A/C Contractor shall employ the water
treatment specialist to carry out on-site water treatment service and water
analysis at least once a month to prove that the performance of the treatment
system is satisfactory and conforming to the approved treatment proposal.
Monthly report on the details of water treatment service and water analysis
including tests, water treatments, consumption of chemicals, etc. shall be
forwarded to the Supervising Officer each month.

F3 SEA WATER TREATMENT BY ELECTROCHLORINATOR

Systems designed for the injection of sodium hypochlorite solution produced


on-site by an Electrochlorinator shall only be installed by the A/C Contractor
where required and specified in the Particular Specification. Such system shall
take water under pressure upstream of the main sea water pump (usually in
pump chamber) and after passing through the Electrochlorinator, inject the
solution back into the pump inlet side immediately after the first (primary) sea
water inlet valve from the sea. The operation of the Electrochlorinator shall be
interlocked to work or stop as the seawater pumps.

The resulting concentration of free chlorine residue at this point shall be


between 1 ppm minimum and 6 ppm maximums. Facilities shall also be
provided at the same point to input a supercharge of concentrated liquid sodium
hypochlorite or other suitable chemical to achieve periodic "super-chlorination"
of the system.

The water to the Electrochlorinator equipment must be passed through coarse


and fine strainers installed in its supply pipework, to ensure minimum fouling up
of the equipment cells. Duplicate Electrochlorinator plant shall be provided to
ensure continued treatment when one unit is "off-line" for maintenance.

The electrodes shall be made of high corrosion resistant material, in particular,


anodes shall be made of titanium substrate coated with protective oxide.

Integral safety facilities in the electrolytic cells such as water flow switch and
cell voltage imbalance detector shall be provided to prevent build-up of
hydrogen gas by-product. Vent and other necessary facilities shall be provided
to dilute and disperse the hydrogen gas from the degas tank or degas cyclone to

Part F AC_GS
Page 2 of 13 2017 Edition
outdoor safely according to the requirements specified in the Particular
Specification and the FSDs statutory requirements.

Unless otherwise specified in the Particular Specification, an adequate electrical


supply point will be made available to the equipment plant room by others. The
electrical supply requirement and its connection to the Electrochlorinator shall
be carried out by the A/C Contractor.

F4 SEA WATER TREATMENT BY BIOCIDES

Where no other system is specified and unless otherwise instructed by the


Supervising Officer, this method shall be provided by the A/C Contractor as the
basic form of treatment for condenser with sea water cooling applications.

F4.1 Basic Requirements

The biocides used shall inhibit the growth of marine organisms


throughout the system. It shall also inhibit the formation of scale and
slime by acting as an efficient dispersant. This shall be achieved by
the appropriate biocide treatment being carried out at 2 to 3 day
intervals such that on these occasions the whole system shall contain
a 6-ppm concentration of biocide solution for approximate 1 hour,
which is sufficient to kill all organisms. Continuous dosages shall not
be applied at lower ppm levels lest they allow the organisms to build
up immunity.

The biocidal and dispersing agents for sea water condenser cooling
systems shall have the following properties: -

- Strong biocidal properties;


- Dispersing effect on deposits;
- Filming properties providing a protective film to internal of
pipework;
- pH value of 6.8;
- Specific gravity of 0.98;
- Non-flammable;
- Easily dosed by chemical metering pump with or without
dilution; and
- Being sufficiently bio-degradable such that they do not cause
environmental difficulties for the marine life. In that respect,
they must be of a type acceptable and approved by the
HKSAR Environmental Protection Department or relevant
Government Authorities.

F4.2 System Sizing and Design

Advice of the approved water treatment specialist shall be sought on


the dosages required, together with calculation, for a specified system
water volume.
Part F AC_GS
Page 3 of 13 2017 Edition
In case the cooling system is running with fixed sea water flow rate,
the metering pump(s)of the water treatment system can be set for a
particular input rate to achieve the appropriate dosage and duration
which is usually possible to pump biocide direct from its supply
container.

Where the cooling system is running with variable flow rate of sea
water, the metering pump(s) concerned shall have the facility to
automatically vary the amounts of chemicals dosing in proportion
with the actual sea water flow. This can be achieved by metering
pump(s) which can respond to the reading of a flow meter measuring
the total sea water flow. Arrangement of variable chemical pumping
rates shall be required where the sea water pump(s)is/are "stage"
controlled or of "variable speed" control.

For stage controlled sea water pump(s), each sea water pump can
be supplied with fixed biocide input from one metering pump. The
inlet point shall be arranged before the pump and as near as possible
to the primary inlet sea water gate valve. Such metering pump(s)
would be controlled by the individual pump circuit such that they
only operate when the respective pump is operated.

As an alternative, the sea water pump set(s) can also be supplied with
a single source variable metering pump which is controlled by a flow
measuring device placed after the outlet of main header. In such case,
the chemical injection shall be distributed to all pump inlets via
solenoid valves. Each solenoid valve shall be opened when the
respective main sea water pump is switched on.

F4.3 Flow Measurement and Control

The flow measuring device shall be of a low flow interference


inserted velocity / static differential headed type as described in more
details in Section C10.

The unit shall be inserted through and across the centre of the pipe in
which the fluid flow is to be measured. It shall be inserted with water
tight glands at a position not less than a length of 12 pipe diameters
downstream from any bend or any turbulence creating feature. The
position chosen shall also be one that best assures an even velocity
cross section flow of the fluid to be measured.

F4.4 Biocide Storage

Apart from the necessity to periodically replenish the biocide supply,


the Installations shall be capable of catering for minimum 4 weeks
unmanned automatic operation. Chemical tanks shall be provided to
meet the requirement as specified in Clause F4.5.

Part F AC_GS
Page 4 of 13 2017 Edition
F4.5 Chemical Tanks

The A/C Contractor shall supply and install two chemical mixing
tanks which made of ultra violet resistant round moulded fibre glass
or polyethylene. The capacity of each tank shall not be less than 180
litres.

The tanks shall be completed with cover of high rigidity fibre glass or
polyethylene having suitable moulded recessed or other approved
arrangements to support mountings of metering pump, agitator and
liquid level controller switch.

The tanks shall be graduated in 10 litre steps and shall have the
maximum storage capacity with its chemical name labelled on the
tank body for easy identification.

The tanks shall be suitable for mixing the specified chemicals and be
suitable for solutions at temperatures of up to 40 oC.

Each tank shall have a strong flat bottom providing adequate support
when full such that the outer perimeter of the tank shall not be forced
up by water pressure causing the bottom to bulge.

F4.6 Chemical Tube Connection to the Circulation System

Unless otherwise instructed by the Supervising Officer, the A/C


Contractor shall allow for drilling and tapping into the delivery pipe
at points near to the sea water intake and installing a suitable sized
PVC valve completed with connectors for attachment of the chemical
tubes from the metering pumps.

F4.7 Make Up Water Supply to Chemical Tanks

Unless otherwise specified, this shall take the form of an 18 mm bib


tap situated over each chemical tank. The A/C Contractor shall
provide a suitable supply to these bib taps with pipework securely
fixed to the walls. A 25 mm mains valve supply will be provided by
others within a 30 metres pipe run of the tanks. The A/C Contractor
shall also supply sufficient lengths of chemical resistant flexible hose
from bib taps to the tanks to facilitate the filling operation.

F4.8 Chemical Metering Pump

In conjunction with the chemical tanks, the A/C Contractor shall


provide panel or tank-top mounted high efficiency metering pumps
one per tank capable of pumping from 2 litres to 90 litres of solution
each in 1 hour. Metering pumps exceeding 90 litres/hour will be
considered subject to approval by the Supervising Officer. Chemical
pump shall have ON/OFF switch and protection fuse.
The pumps shall be suitable for 100 : 1 output range facilitated by
means of independently variable stroke length and stroke frequency.

Part F AC_GS
Page 5 of 13 2017 Edition
Pump housing shall be of corrosion resistant glass fibre reinforced
polypropylene and all electrical/electronic components shall be
encapsulated. If necessary, anti-siphon/pressure release valve
mechanisms shall be provided to ensure anti-siphon protection plus
priming ease, even under pressure.

The pumps shall have an acrylic/polypropylene pump head,


PVC/polypropylene fittings, ceramic valve balls, metal reinforced
Teflon diaphragm, Teflon seal rings and liquiform face, anti-siphon
mechanism. The discharge tubes shall be 10 mm internal diameter
and of suitable PVC to transport the solutions involved.

The pump suctions shall be mounted into the tank using an UPVC
suction tube assembly that will prevent the suction tube becoming
wrapped around the agitator shaft. The end of the pump suction tube
shall not extend beyond the bottom of the UPVC tube shield.

F4.9 Chemical Tank Agitator

The A/C Contractor shall supply and install into the provisions made
on the chemical mixing tank cover one agitator assembly per mixing
tank.

This shall consist of a fractional HP motor driving a stainless steel


shaft and neoprene with bronze hub impeller. The shaft shall be of
suitable length to suit the depth of the solution in the mixing tank.

The motor casing and screws shall be manufactured in nonferrous


metal.

F4.10 Chemical Tank Liquid Level Switch

In order to prevent the metering pump and agitator from running if


the chemical solution drops below a pre-set low level, the A/C
Contractor shall supply and install into each tank cover a suitable
liquid level switch and control system. A visual and audio alarm
shall also be provided at the control/indication panel.

The level switch shall be contained in a corrosion resistant assembly


of glass reinforced polypropylene. It shall have PVC float tube,
foamed polypropylene float and encapsulated reed switch.

In each case, there shall be a float protector to prevent false actuation


due to turbulence. An extra low voltage transformer shall be
incorporated to provide the supply to the reed switch for safety.

The liquid level switch casing shall be manufactured from corrosion


resistance material.

F4.11 Electricity Supply

Unless otherwise specified, the electricity supply for the metering


pumps, agitators and level switch assemblies shall be operated with
Part F AC_GS
Page 6 of 13 2017 Edition
220 V single phase 50 Hz supply and connected by the A/C
Contractor from the supply point within the plant room to the water
treatment equipment.

F5 COOLING TOWER/CONDENSER COOLING WATER TREATMENT


BY CHEMICAL AGENTS

Where no other system is specified in the Particular Specification, this method


shall be provided by the A/C Contractor as the basic form of treatment for water
recirculation between cooling tower and condenser applications. The minimum
provisions shall be follows: -

F5.1 Pre-cleaning and Flushing Out Operation

(a) The entire cooling tower/condenser cooling water system shall


be flushed out using appropriate chemical dispersant, detergent
and de-foamed of type and strength recommended by a
reputable chemical water treatment manufacturer and
guaranteed in writing by that company as suitable in every
respect for the application in question.

(b) The chemicals shall remain in the system for 48-72 hours
including a minimum of 24 hours with the pumped circulation
in operation, unless otherwise recommended by the supplier
with free technical support accepted by the Supervising
Officer.

(c) The system shall then be completely drained and flushed until
tests at all drain points show that traces of suspended matter
have been substantially removed to the Supervising Officers
approval.

(d) The system water shall be completely drained as rapid as


possible and the A/C Contractor shall provide temporary
50 mm valve drain outlets on all points where the main
pipework is 50 mm or over.

(e) The A/C Contractor shall ascertain that there is adequate


drainage nearby to discharge to by large hose in order to
ensure flooding of low level areas will not occur. It is the
responsibility of the A/C Contractor to ensure that the
discharge to the building drainage system and public sewer are
in full compliance with the requirements of the Drainage
Services Department and the Environmental Protection
Department. If pre-treatment is required, Clause F10 shall be
referred.

(f) Subsequent to the flushing out operations, the large drain


down points shall be reduced to 15 mm valves or cocks or the
sizes as indicated on the Drawings. The system shall be

Part F AC_GS
Page 7 of 13 2017 Edition
refilled and flushed as necessary to achieve the required water
quality level.

F5.2 Chemical Treatment to Prevent Corrosion, Sludge Formation and


Microbiological Activity (Open System)

The chemical agent employed shall be a combination of chemicals


which will provide corrosion protection, scaling and microbiological
inhibition to the metal pipe lines and the construction material within
condensers and cooling towers.

The chemical agent shall be non-flammable liquid chemicals such as


molybdate or phosphate based agent blended with anti-foulant and
amine based biocide. The agent shall be guaranteed by the chemical
manufacturer as suitable in every respect for the application.

F5.3 Chemical Dosage System

The chemical dosage system shall be a fully automatic system


comprising the following minimum equipment: -

(a) Chemical metering pump as specified in Clause F4.8 and


control panel constructed to IP 54 to BS EN
60529:1992+A2:2013 completed with system status indication,
visual and audio alarm, timer, etc. as required to facilitate ease
of operation and maintenance of the water treatment system;

(b) Chemical tanks as specified in Clause F4.5; and

(c) Chemical tank liquid level switch as specified in Clause F4.10.

F6 COOLING TOWER/CONDENSER COOLING WATER TREATMENT


BY OZONE

This method of water treatment for fresh (including well water) or sea water
circulating between cooling tower and condenser shall only be installed by the
A/C Contractor where required and fully detailed in the Particular Specification.
The minimum provisions shall be follows: -

F6.1 Pre-cleaning and Flushing Out Operation

As specified in Clause F5.1.

F6.2 Ozone Generation System for Cooling Water Treatment

The ozone generation system shall include all major ozone generating
equipment, circulating pumps, interconnecting piping, pipe fittings,
enclosure, wiring, accessories, controls and instrumentation to form a
compatible and complete working system. Weather-proof enclosure
with self-contained lighting and ventilation shall be provided for the
system that is susceptible to weather or outdoor conditions.

Part F AC_GS
Page 8 of 13 2017 Edition
A complete ozone piping system separated from the main cooling
tower/condenser cooling water system shall be provided to take water
from the recirculating pump discharge side of the cooling water
circuit, through the in-line ozone injector /contactor for ozone dosing,
a solid separator and then recirculated into the sump of the water
cooling tower or tank. The system operation and ozone dosing shall
be fully automatic with programmable direct digital real time control
incorporated. Multiple injection points shall be adopted for cooling
systems with turnover rate not more than four times per hour.

Unless otherwise specified, the A/C Contractor shall be fully


responsible for the design of the system, selection of equipment and
ozone dosage rate for the particular fresh/sea water cooling water
system with specific recirculation rate and system volume. The
ozone dosage rate shall not be less than 0.1 mg/l in any case. The
system shall be suitably oversized to satisfy the ozone demand at the
initial stage for cleaning and descaling of the cooling water system
for a period of not more than two weeks period. Detailed system
design and equipment selection proposal with all relevant design
criteria, data, parameter, calculations and system schematic diagrams
shall be submitted to the Supervising Officer for approval before
placing order and actual commencement of installation works.

Each ozone generation system shall be constructed in modular form


which shall comprise major equipment modules of pressure swing
absorption type oxygen generator, high frequency ozone generator,
ozone injector/contactor, solid particle separator, circulating pumps,
piping, pipe fittings, all necessary accessories, wiring, controls and
instrumentation. The modular enclosure shall be designed for ease of
maintenance and safe operation with demountable panels, hinged
doors, visual panels and adequate electrical segregation for the high
voltage section.

The ozone generation system shall be easily connected to ozone-in-air


monitor and other control instrument for automatic stopping and
control of the entire system. Visual and audio alarm shall be
incorporated as specified. Ozone-in-air monitors shall be fixed at
locations as indicated in the Drawings if specified in the Particular
Specification and properly connected to the ozone generation system.

All components in contact with ozone produced shall be made of


ozone resistant material designed for continuous and prolonged usage
without deterioration or damage. Unless otherwise specified in the
Particular Specification, all system components in contact with
ozonated water shall be made of stainless steel to AISI 316. In
particular, Teflon tubing shall be used for connecting ozone generator
and in-line injector, Polyflo tubing for oxygen conveying pipe, UPVC
piping and fittings for other interconnecting pipework.

Major ozone generating equipment shall comprise, inter alia, the


following component: -

Part F AC_GS
Page 9 of 13 2017 Edition
(a) Pressure Swing Absorption Oxygen Generator

The oxygen generator comprises a built-in oil-free compressor


for air compression, air dryer pre-chiller, an automatic high
efficient desiccant air dryer with marcoporous drying agent, a
nitrogen absorption tank to produce constant and stable supply
of oxygen with purity 85% 5%. Regeneration shall be
accomplished by heating the desiccant material and purging it
with a small flow of dried air to expel moisture when they are
saturated with moisture.

A dewpoint monitoring system shall be incorporated, which


comprises a control unit and measuring probe situated within
the pipework leading from the air dryer to the ozone generator.
The monitoring system shall automatically stop the ozone
production with an visual and audible alarm in case of an
increase in dewpoint over a preset value in order to prevent
failure or damage to the ozone generator.

Air dryer pre-chiller shall reduce the incoming air temperature


to approximately 10C or other optimum operating
temperature recommended by the manufacturer to suit the type
of desiccant used.

(b) Ozone Generator

The ozone generator unit shall comprise independent solid-


state high frequency ozone generator modules, air-cooled plate
type and constructed of either sandwich heat dissipating
structure with ceramic coated steel plate discharge electrodes
or cylindrical concentric ozone generating tube.

Each module shall be equipped with built-in safety circuit to


give visual and audible alarm and to switch off the generator
when abnormal operation of the generator occurs. Relevant
type-test or factory test certificates of the generators high
voltage transformer section as listed below shall be submitted
for verification of safe operation:-

(i) Voltage ratio and phase relationship test;


(ii) Induced over-voltage withstand test;
(iii) Insulation resistance test; and
(iv) High voltage withstand test.

Minimum safety controls shall be provided as follows:-

Door mechanically interlocked with the main isolating switch;


Over current cut-out;
High temperature cut-out;

Part F AC_GS
Page 10 of 13 2017 Edition
Low air flow or low cooling water cut-out as appropriate;
High dew point cut-out;
High/low voltage cut-out;
External fault cut-out (if external devices connected); and
Isolation of power supply when panel doors or side panels are
opened.

Unless otherwise specified, water-cooled type ozone generator


shall be offered; air-cooled type modules shall only be offered
for low capacity ozone generator unit as specified in the
Particular Specification. The cooling water shall be taken
from the chilled water system of the building as indicated in
the Drawings or at nearest A/C plant room. Pressure reducing
valve, regulating valve and connecting chilled water piping
shall be provided to maintain the design constant operating
conditions of the modules.

(c) In-line Injector/Contactor

The in-line injector shall be venturi type completed with


double check valves fabricated of Kynar or products having
equivalent functions or performance.

(d) Solid Particle Separator

The separator shall be fabricated of Noryl plastic or products


having equivalent functions or performance selected to suit
system flow rate and requirements.

(e) Circulating Pump

The circulating pump shall be compatible with the ozone


system and supplied by the same ozone equipment supplier.
The pump shall comply with relevant sections of this General
Specification.

(f) Test Kit and Ozone Monitoring Equipment

Sampling points in the system together with a complete set of


test kit for residual ozone testing shall be provided to facilitate
daily inspection and assessment of ozone content.

A portable ozone-in-air monitor with range 0 - 9.5 ppm and


4-digit LCD shall also be provided.

The above test kit and monitor shall be handed over to the
operating staff prior to the expiry of Maintenance Period.

(g) On Site Operational Training

Part F AC_GS
Page 11 of 13 2017 Edition
Familiarisation of equipment and on-site training of the whole
ozone water treatment system shall comply with the
requirements in Clause F9. In addition, a competent specialist
of the ozone system shall hold the on-site training of the water
treatment system.

F7 CLOSE CIRCUIT CHILLED WATER OR LOW PRESSURE HOT


WATER HEATING SYSTEMS TREATMENT BY CHEMICAL AGENTS

Where no other system is specified in the Particular Specification, this method


shall be included for by the A/C Contractor as the basic form of water treatment
for the close circuit chilled water or hot water heating system applications.

The minimum provisions shall be as follows: -

F7.1 Pre-cleaning and Flushing Out Operations

As specified in Clause F5.1.

F7.2 Chemical Treatment to Prevent Corrosion, Scaling and Sludge


Formation

The chemical agent shall be a combination of chemicals guaranteed


by the manufacturer as appropriate in every respect to prevent
corrosion, scaling and sludge formation.

The agent should be liquid chemicals such as molybdate or nitrite


based agent blended with corrosion inhibitor which can provide such
protection to the metal of closed circuit pipe lines, system and
equipment.

Chemicals used within chilled water or low pressure hot water


(LPHW) heating system shall, unless otherwise recommended by the
supplier with full technical support and accepted by the Supervising
Officer, have the following characteristics: -

Suitable for the application, system operation conditions and fluid;


Non-flammable; and
Low toxicity.

F7.3 Chemical Dosage Equipment

As specified in Clause F5.3.

F8 WATER TESTING EQUIPMENT

Unless otherwise specified in the Particular Specification, water testing


equipment corresponding to the type of water treatment system and chemical
used shall be provided to monitor and verify the performance of the water

Part F AC_GS
Page 12 of 13 2017 Edition
treatment system offered and shall be handed over to the operation and
maintenance staff prior to the expiry of Maintenance Period.

The equipment shall be of portable type suitable for field sampling and testing.
For chlorine residual concentration testing, plain tablets and colour disc shall be
provided. For pH value testing, pH meter or phenol red solution and colour disc
shall be provided. Other relevant test kits shall include but not limited to total
dissolved solid and corrosion inhibitor level tester.

F9 TRAINING, OPERATION AND MAINTENANCE FACILITIES

No matter which type of water treatment system is offered, adequate on-site


operational training and demonstration of the water treatment system shall be
provided to the operation and maintenance staff prior to handover of the system
or after completion of the Installations. It shall include but not limit to the
following: -

F9.1 Familiarisation of equipment and system including function of each


dosing chemical.

F9.2 Water treatment equipment set-up/adjustment.

F9.3 On-site training of water sampling and testing, equipment and system
operation and maintenance procedures.

F9.4 Precautions in handling the chemicals and the remedial actions


following a spillage and accidental human contact.

Competent persons from the approved water treatment specialist and


equipment suppliers shall conduct the on-site training with full day
in-hand training. The exact training requirement shall be submitted
by the A/C Contractor to the Supervising Officer for endorsement.

The A/C Contractor shall provide prominent warning notices, goggles,


gloves and necessary accessories for handling the chemicals.

Sufficient number of sampling points in the pipework or equipment


for water analysis, routine inspection and testing shall be provided.

F10 PRE-TREATMENT FOR DUMPING OF CHEMICAL WASTES

All chemical wastes generated by the A/C Contractor shall be handled, collected
and disposed of in accordance with the Waste Disposal (Chemical Waste)
(General) Regulation. The A/C Contractor shall register as a Chemical Waste
Producer with the Environmental Protection Department and the wastes shall be
collected by a licensed Chemical Waste Collector for disposal at an approved
facility.

Part F AC_GS
Page 13 of 13 2017 Edition
PART G - PAINTING, FINISHING AND PROTECTIVE TREATMENT

G1 GENERAL

All surfaces except otherwise specified in the particular specification, other than
those indicated to be left self-finished such as stainless steel, anodized
aluminium, shall be finished in first class paint work. All metallic surfaces shall
be wire-brushed and cleaned to make it free from rust, scale, dirt and grease
prior to painting. Primer shall be applied to metal surface on the same day as
they have been clean. All work shall be carried out by qualified
tradesmen/skilled workers.

All paints shall be submitted for the approval of the Supervising Officer. The
volatile organic compound (VOC) content, in grams per litre, of all paint and
primer shall not exceed the prescribed limit under the Air Pollution Control
(Volatile Organic Compounds) Regulation or the limit set by EPD, whichever is
more stringent.

VOC content of paint shall be determined by methods stipulated in Air Pollution


Control (Volatile Organic Compounds) Regulation or other methods acceptable
to EPD.

All painting works shall be completed and left in ventilated environment for at
least one week, or the curing period recommended by the paint manufacturer
whichever is longer, before occupation or handover of the renovated area to
minimise VOC exposure.

All surfaces shall be painted and finished as specified in the Particular


Specification to meet and match the aesthetic architectural design as required.

All internal surfaces including cladding walls, floors, ceiling and equipment
plinth of AHU and fan rooms or plant rooms affecting IAQ shall be painted as
specified in D.1 of this General Specification.

G2 NUMBER OF PAINT COATS REQUIRED

All painted surfaces are to receive at least one primer coat and two coats of the
finishing colour. For external installation / equipment installation, polyurethane
paint shall be used for finishing colour to provide better UV resistance unless
otherwise specified. Ferrous surfaces shall receive one coat of rust inhibiting
primer, one under-coat and two finishing coats.

Where painting is carried out in occupied areas with central air-conditioning or


areas without good natural ventilation, pre-painting preparation and primer coat
shall be carried out off-site and only the finishing coats shall be painted on-site.

Part G AC_GS
Page 1 of 6 2017 Edition
G3 IDENTIFICATION OF PIPELINES

All pipework in the plant/machinery rooms shall be finished generally in


accordance with ISO 3864-1:2011. All pipework, where exposed on surfaces
outside the plant/machinery room, shall be painted either as in the
plant/machinery room or to match the surrounding surface with distinguishing
colour code bands plus flow arrows in the specified colour scheme as directed
by the Supervising Officer.

Pipes and pipelines shall be painted in colours either in accordance with ISO
3864-1:2011 or as directed by the Supervising Officer completed with the
identification colour code indicators. The basic identification colour or the
decoration colour shall be applied over the whole length of the pipe with colour
code indicators placed at all junctions, at both sides of valves, service appliances,
bulkheads, wall penetrations and at any other places where identification is
necessary as directed by the Supervising Officer.

Valves may be painted in the same colour as the associated pipework. However,
if the pipeline is part of the fire services installation and has been coded only
with the safety colour, the valves involved shall be fully painted "safety-red".

The direction of flow of fluid shall be indicated by an arrow over the basic
identification colour and painted white or black in order to contrast clearly with
the basic identification colour.

Colour code numbers are those of BS 4800:2011. The schedule of colour for
ready mixed paints and BS colour reference shall be as Clause G4, in table G4-
(1) and G4-(2).

Part G AC_GS
Page 2 of 6 2017 Edition
G4 SCHEDULE OF COLOURS

Colour schedule as stated below are those of BS 4800:2011 for ready mixed
paints.

Table G4 (1) Schedule of Colours

Description of Basic Colour Code Indication Basic


Services Colour 100 mm approx. Colour
Pipework:
Drinking Green Blue Green
Cooling
Green White Green
(Primary)
Boiler Feed Green Crimson White Crimson Green
Emerald
Condensate Green Crimson Crimson Green
Green
Emerald
Chilled Green White White Green
Water Green
Mains supply,
Green White Blue White Green
Cold
Mains supply,
Green White Crimson White Green
Hot
Sea, river
Green
Untreated
Fire Fighting Green Safety Red Green
In either
gaseous or
Gases liquefied Yellow ochre
condition
(exception)
Compressed Air Light blue
Steam Silver grey
Oil Lubricating Brown Emerald Green Brown
Yellow Yellow
Gas Town Emerald Green
ochre ochre
Yellow Yellow
Natural Yellow
ochre ochre
Drainage Black
Acids &Alkaline Violet Black & Yellow Stripes Violet
Equipment:
Plant Opaline Green
Electrical Conduits &
Orange
Ductwork
Ductwork White

Part G AC_GS
Page 3 of 6 2017 Edition
Table G4 (2) BS Colour Reference

BS 4800:1989
(1) Basic Identification Colours
Green 12D45
Silver grey 10A03
Brown 06C39
Yellow ochre 08C35
Violet 22C37
Light blue 20E51
Black 00E53
Orange 06E51
(2) Safety Colour
Red 04E53
Yellow 08E51
Auxiliary blue 18E53
(3) Code Indication Colour
Crimson 04D45
Emerald green 14E53
Yellow 10E53

G5 MACHINERY AND PIPEWORK

All machinery, unless otherwise specified, shall be finished in a colour as


instructed by the Supervising Officer at the time of installation. The A/C
Contractor shall seek the Supervising Officers instructions in good time to
obtain the materials required. In the event that no instruction is given, the plant
shall be painted in opaline green with black relief on flanges in accordance with
BS EN 60073:2002.

G6 COPPER PIPE AND FITTING

Copper pipes and fittings for refrigerant, which are not insulated shall be
polished bright by sanding, wiped with mineral spirits and coated with an
approved heat resisting clear synthetic varnish.

G7 PIPES AND DUCTWORK

The final external treatment for insulated pipes and ductwork shall be as
specified in Section C11 of this General Specification or as indicated in the
Particular Specification or as directed on Site by the Supervising Officer.

Pipes and ductwork concealed in false ceiling or ductwork not normally


accessible need not be painted, unless otherwise specified in the Particular
Specification but appropriate colour code identifications shall be applied.

Part G AC_GS
Page 4 of 6 2017 Edition
Insulated pipes and ductwork running in visual positions shall be plastered or
otherwise finished as specified. They shall be painted in the appropriate
identifying colour or as directed by the Supervising Officering another colour
plus identifying colour code bands.

Uninsulated pipes and ductwork running in visual areas shall be painted in the
appropriate colour throughout or painted in another colour as directed by the
Supervising Officer but identified with appropriate colour code bands.

G8 PROTECTION OF PLANT, EQUIPMENT, PIPEWORK, ETC.

G8.1 Temporary Dehumidifiers and/or Air Conditioners

For temperature and/or humidity sensitive electrical or electronic


control panels and equipment, the A/C Contractor shall where
necessary protect them against high humidity and/or temperature by
operating portable or temporary dehumidifiers and/or air conditioners
in the enclosures containing this equipment.

In order to protect this equipment against dust infiltration, the A/C


Contractor shall store them in a dust free room or enclose them in
heavy duty PVC sheets or bags. Where necessary, filters shall be
provided in the temporary air conditioning systems.

G8.2 Metal Surface

All stainless steel parts shall be covered with PVC wrapper of tape
until handover. All ferrous parts shall be painted or greased
(whichever is most suitable). All bright parts (chrome plates,
polished stainless steel or aluminium, etc.) which are liable to
deterioration shall be covered with tallow or a suitable protective
coating during the progress of work. Upon completion of work, the
protective coating shall be removed and the parts polished as
appropriate.

Any damage to the primer or protective coatings shall be made good.


When it is necessary to remove, or partly remove the protection for
installation or making connections, the A/C Contractor shall ensure
that the standard of protection provided originally is re-applied at the
earliest possible time.

G8.3 Rust and Foreign Matter

All plants, pipes valves, and fittings shall be, as far as possible,
thoroughly cleaned and cleared of rust and other foreign matters both
before erection and before subjection to pressure tests.

Part G AC_GS
Page 5 of 6 2017 Edition
G9 PROTECTIVE MEASURES AGAINST CORROSION

Where normal painting is not practicable, all possible measures to prevent


corrosion to the plant shall be applied such as special protective coverings,
special anti-corrosive paints, etc. as recommended by the supplier or specified in
the Particular Specification.

For protection against system internal corrosion, chemical treatment of the


internal water as described in Part F of this General Specification shall be
applied. The provision of sacrificial anodes and bonding to eliminate
electrolytic action shall also be applied wherever applicable.

Part G AC_GS
Page 6 of 6 2017 Edition
PART H - INSPECTION, TESTING AND COMMISSIONING
DURING CONSTRUCTION PERIOD

SECTION H1

GENERAL REQUIREMENTS

H1.1 GENERAL

The inspection, testing and commissioning shall be carried out in accordance


with the requirements specified in this Part and Testing and Commissioning
Procedure for A/C Installation in Government Buildings which shall be referred
to and adopted where appropriate.

Throughout the execution of the Installations, the A/C Contractor shall be


responsible for ensuring compliance with the statutory and related requirements
included in Section A2, manufacturers recommendations and specifications and
shall notify the Supervising Officer of any infringement which directly or
indirectly detracts from the safe and satisfactory operation of the Installations
whether or not such infringement relates to the works covered in the
Installations or to those associated with others. All sub-standard works or
defects found during inspection, testing and commissioning shall be rectified or
replaced to the satisfaction of the Supervising Officer.

H1.2 METHODS AND PROCEDURES

The A/C Contractor is required to submit detailed inspection, testing and


commissioning methods and procedures together with report formats for
reporting the inspection, testing and commissioning results for the Supervising
Officers approval at least four months before commencement of the testing and
commissioning works, or four months after the acceptance of his Tender,
whichever is earlier.

H1.3 NOTICES OF INSPECTION, TESTING AND COMMISSIONING


WORKS

For items to be witnessed by the Supervising Officer or his Representative, the


A/C Contractor is required to provide advanced notice for inspection, testing
and commissioning works, together with details of date, time and list of items to
be inspected or tested, unless otherwise specified in the Conditions: -

(a) Off-site Inspection and Test

An advanced notice of at least one week before commencement of the


inspection or test shall be provided.

(b) On-site Inspection, Testing and Commissioning


An advanced notice of at least 3 days before commencement of
inspection, testing or commissioning of any part or parts of the
Installations shall be provided.
Part H AC_GS
Page 1 of 10 2017 Edition
H1.4 LABOUR AND MATERIALS

The A/C Contractor is responsible for provision of all labour and both
consumable and non-consumable materials for carrying out the inspection,
testing and commissioning works at their expenses. Unless otherwise indicated
in the Conditions, all electricity supply, water supply, chemicals, and other fuels,
such as diesel, LP gas and town gas necessary for the operation of the plant
during preliminary runs and for full adjustments and inspection and
commissioning tests shall also be arranged and provided at no cost by the A/C
Contractor unless otherwise specified in the Contract. The A/C Contractor shall
also properly drain the water and exhaust the gas during and after the inspection,
testing and commissioning works as required. The A/C Contractor shall provide
and adopt measures to avoid damage to the building, Installations, decorations
and fixtures during the inspection, testing and commissioning works for any of
the Installations.

The A/C Contractor shall also provide all necessary equipment, apparatus and
tools for carrying out the inspection, testing and commissioning works.

The A/C Contractor shall despatch competent and experienced commissioning


personnel to carry out the inspection, testing and commissioning works.

H1.5 INSPECTION, MEASURING AND TESTING EQUIPMENT

The A/C Contractor is required to supply the calibrated equipment and


instrument for the inspection, testing and commissioning works in accordance
with the requirements as specified in the Particular Specification for supply of
inspection, measuring and testing equipment. Certified true copy of calibration
certificates shall be submitted. The period between calibration and testing shall
not exceed the calibration period as recommended by the equipment/instrument
manufacturer or 12 months whichever is shorter.

H1.6 READINESS FOR INSPECTION, TESTING AND COMMISSIONING

The A/C Contractor is required to check the completion of the works to be


inspected, tested or commissioned, the associated builders works, the
associated building services installations and all other prerequisites to ensure
that inspection, testing and commissioning can be preceded in a safe and
satisfactory manner without obstruction.

H1.7 "TYPE-TEST" CERTIFICATE

"Type-test" for materials and equipment, where specified, shall be carried out at
the manufacturers works, recognised institutions or accredited laboratories, or
elsewhere as approved in order to demonstrate their compliance with the
specified requirements. "Type-test" certificates together with the corresponding
drawings, sketches, reports and any other necessary documents shall be
submitted to the Supervising Officer for approval before delivery of the
materials and equipment. Cases where appropriate, type-test certificates will
be accepted are as follows:
Part H AC_GS
Page 2 of 10 2017 Edition
(a) Fans: type-test certificates showing fan characteristic curves (ISO
5801:2007/Cor 1:2008), "type-tests" Certificates for sound power levels
(BS EN ISO 5136: 2010), fan dynamic balancing test Certificates
completed with a method of statement from manufacturer on testing to
Grade 2.5, 4 & 6.3 on appropriate fan types in accordance with ISO
1940-1:2003/Corr 1:2005 and ISO 21940-14:2012.
(b) Pumps: "type-test" certificates for head, discharge, speed and power
input (BS EN ISO 9906:2012 as appropriate).
(c) Electric motors: "type-test" certificates in accordance with BS EN 60034-
1:2010 and/or IEC 60072-1:1991, IEC 60072-2:1990 & IEC 60072-
3:1994.
(d) Low voltage starter switchgear and control gear assembly: "type-test"
certificates for starter (e.g. auto-transformer) and control panels assembly
as a whole in accordance with IEC 61439-1:2011.
(e) High voltage switchgear and motor control switchboard: "type-test"
certificates for high voltage switchgear and switchboard in accordance
with IEC 62271-100:2008+AMD1:2012.
(f) Other electrical equipment, such as air heaters (but excluding
thermostatic control equipment): "type-test" certificates in accordance
with BS EN 60335-1:2012+A11:2014, BS EN 60669-1:1999+A2:2008,
BS 5733:2010+A1:2014 and BS EN 60670-22:2006.
(g) Refrigeration plant: "type-tests" Certificates for hydraulic and air
pressure testing at works in accordance with BS EN 378-
1:2008+A2:2012, BS EN 378-2: 2008+A2:2012, BS EN 378-
3:2008+A1:2012and BS EN 378-4:2008+A1:2012

H1.8 OFF-SITE TESTS / FACTORY TESTS

Factory tests and off-site tests as required shall be carried out at the
manufacturers works, laboratories by independent regulatory/testing bodies,
independent accredited laboratories or elsewhere as approved. This shall include
quality control tests and general inspection tests in factory recommended by the
manufacturer or for compliance with relevant standards.

Where collection of test samples on the Site is required for the off-site tests, i.e.
indoor air quality test and water quality test for fresh water cooling tower, the
A/C Contractor shall submit the sampling and analysis methodology, including
but not limited to the proposed independent accredited laboratory and the
procedures for collection and analysis of test samples and submission of test
results, for the Supervising Officers approval. The A/C Contractor shall notify
in advance the date for collection of test samples to the Supervising Officers
Representative, who shall supervise the sampling, transport and delivery of the
test samples. Collection of test samples shall be conducted by the independent
accredited laboratory unless otherwise agreed by the Supervising Officer. The
collected test samples shall be kept in sealed and locked containers inaccessible
to unauthorised persons at all times. The test results in sealed envelope shall be
submitted by the independent accredited laboratory to the Supervising Officer
directly.
Part H AC_GS
Page 3 of 10 2017 Edition
Where specified, performance tests shall be carried out in factory for each or
some of the offered equipment before delivery. After the performance tests,
factory test report/certificate certified by a qualified factory engineer shall be
submitted in duplicate to the Supervising Officer for approval immediately after
the tests and before the equipment is dispatched from the manufacturers works.

Factory tests shall be witnessed by an independent approved agency where


specified. The A/C Contractor shall note that the Supervising Officer may
require witnessing the tests and inspection of locally and/or overseas
manufactured equipment during construction at the manufacturers works.

H1.9 SITE TESTS

The A/C Contractor shall carry out site tests for all static systems during
construction period for individual components and/or part of the installed works
to ensure safe and proper operation of the complete installation according to the
specified requirements. Such tests shall include integrity test of welds and
pressure test on the hydraulic systems where applicable. Any component or
equipment set to operate at or below the test pressure shall be isolated or
removed prior to applying the pressure test. Site tests for electrical works in the
Installations shall comply with the COP for the Electricity (Wiring) Regulations
unless otherwise specified. Registered or suitably qualified workers shall be
deployed to conduct site tests, where applicable, for the Installations.

Works to be permanently covered up shall be subject to inspection and testing


before covering up. If the Supervising Officer or his Representative discovers
any work that has been covered up before inspection and testing, this work shall
be uncovered for inspection and testing to the satisfaction of the Supervising
Officer or his Representative. The cost involved in uncovering the work,
inspecting, testing and re-concealing the work together with any consequential
losses shall be paid by the A/C Contractor at no additional cost to the Employer.

In particular, the following arrangements shall also be included:

(a) The A/C Contractor shall carry out "on-site" tests in respect of all static
systems to ensure safe and proper operation as conforming to the design
intent. Such tests shall include test of welds and pressure tests on the
hydraulic systems.

(b) On completion of cleaning operations described in Clauses 3.6.1 and


4.1.5.5 of the Testing and Commissioning Procedure for Air-conditioning,
Refrigeration, Ventilation and Central Monitoring &Control Systems
Installation, each water distribution system shall be re-charged with clean
water and then subjected to a hydraulic test as required by Clause 4.1.5.7
of T&C Procedure for Air-conditioning, Refrigeration, Ventilation and
Central Monitoring &Control Systems Installation.

Any items of equipment set to operate at or below the test pressure shall
be isolated or removed prior to applying this test.

(c) All ductwork shall be tested for air leakage in accordance with Clause
B2.10.
Part H AC_GS
Page 4 of 10 2017 Edition
SECTION H2

INSPECTION

H2.1 INSPECTION OF MATERIALS AND EQUIPMENT DELIVERED TO


SITE

The A/C Contractor shall provide details of materials and equipment delivered
to the Site including, but not limited to, brand name, model number, country of
origin (if specified), their tested standards and record of Supervising Officers
approval, purchase order, delivery order, record of delivery, payment vouchers,
ex-factory certificate and shipping voucher, and all other relevant documents as
applicable to the Supervising Officer for identification and verification of the
materials and equipment delivered to the Site are in compliance with the
approved submissions.

H2.2 VISUAL INSPECTION AND CHECKING

The A/C Contractor shall be responsible for arranging adequate provisions to


facilitate visual inspections and checking of the work in progress to be carried
out by the Supervising Officer or his Representative from time to time during
the construction period. The A/C Contractor shall keep such inspection record
for checking from time to time. Any defective works or sub-standard works
found during visual inspection and checking shall be rectified or replaced before
proceeding with further tests.

Visual inspection and checking shall include but not limited to the inspection
and verification of the installed equipment being the approved brands and
models and checking of any visible damages (such as scratches or dents, or
painting problems) found on the equipment surface.

H2.3 HANDOVER INSPECTION

The A/C Contractor shall carry out detailed inspections for all components and
equipment installed by him and make all necessary checking including
operational settings for all equipment and systems in accordance with the
instructions and recommendations from the manufacturer and to the satisfaction
of the Supervising Officer before the handover of the Installations.

If it is considered difficult or impossible to gain access to a part or parts of the


complete installation for dismantling or maintenance purposes, the A/C
Contractor shall be required to carry out demonstrations on dismantling and
assembling those parts/components of the installation to confirm the provisions
are adequate. The A/C Contractor shall be responsible for carrying out all
necessary modification work at no additional cost to the Employer to alleviate
the difficulties associated with dismantling or maintenance access.

The A/C Contractor shall note that the Installations cannot be handed over until
all the foregoing requirements where applicable have been carried out to the
satisfaction of the Supervising Officer.
Part H AC_GS
Page 5 of 10 2017 Edition
The A/C Contractor shall provide the following documents and data before the
handover inspection: -

(i) Test Certificates

Test records/certificates where applicable shall be provided: -

(a) Copies of manufacturers works test records/certificates on plant


items comprising heat generating plant, heat exchangers, chillers
units, packaged air-conditioning units, tanks, vessels, motors, fans,
pumps, etc.;

(b) Copies of hydraulic and pressure test records/certificates for


works carried out on site;

(c) Copies of boiler and/or refrigeration plant efficiency test/record


certificate;

(d) Copies of Registered Surveyors test/record certificates for


pressure vessels (if any);

(e) Copies of performance test/record certificate including water


balancing, air balancing, room conditions, etc. These certificates
shall be accompanied with all appropriate charts and diagrams;

(f) Copies of all noise test/survey records on every noise emitting


plant and machineries, individual room/space and a statement of
compliance with the statutory requirements under the current
Noise Control Ordinance (Cap. 400); and

(g) Copies of works completion certificates for electrical works;

(ii) "As-built" Drawings

"As-built" drawings as detailed in the contract documents shall be


provided.

(iii) Operation and Maintenance Manuals and User Manual

O&M Manuals and User Manual as detailed in the contract documents


shall be provided.

(iv) Manufacturers Name Plate

Every item of plant/equipment/apparatus supplied by a manufacturer, if


any, shall be fitted with a clearly engraved, stamped or cast
manufacturers name plate properly secured to the
plant/equipment/apparatus and showing: -

- Manufacturers Name;
- Serial and/or Model No.;

Part H AC_GS
Page 6 of 10 2017 Edition
- Date of Supply;
- Rating/Capacity; and
- Test and Working Pressure (where applicable).

(v) Labels and Related Instructions

Labels and the related instructions shall be provided according to


relevant clause(s) of this General Specification.

Part H AC_GS
Page 7 of 10 2017 Edition
SECTION H3

TESTING AND COMMISSIONING

H3.1 GENERAL

Where testing and commissioning works for the Installations are required to be
witnessed by the Supervising Officer or his Representative, the A/C Contractor
shall carry out the proper testing and commissioning works to his satisfaction
before inviting them to witness the works. The A/C Contractor shall arrange to
enable the Supervising Officer or his Representative to witness the complete
testing and commissioning. Unless otherwise approved by the Supervising
Officer, testing and commissioning works carried out by the A/C Contractor in
the absence of the Supervising Officer or his Representative shall not be
accepted as the approved test record.

Any defects of alignment, adjustment, workmanship, materials and performance


or other irregularities which become apparent during commissioning or testing
shall be rectified by the A/C Contractor and the relevant part of the
commissioning or testing procedure shall be repeated at the A/C Contractors
own expense.

For the purpose of this General Specification the following definitions shall
apply: -

(i) Commissioning: the advancement of an installation from the stage of


static completion to full working conditions and to meet the specified
requirements. This will include setting into operation and regulation of
the Installations.

(ii) Setting to work: the process of setting a static system into motion.

(iii) Off-site Tests: tests carried out on items of equipment at manufacturers


works or elsewhere to ensure compliance with the requirements of
Specifications and/or relevant Standards or Codes of Practice (or other
standards specified).

(iv) Site Tests: tests on static plant and systems (e.g. inspection and testing of
welds, hydraulic testing of pipe work, etc.) to ensure correct and safe
installation and operation.

(v) Regulation: the process of adjusting the rates of fluid flow and heat
transfer in a distribution system within specified tolerances as stated in
the relevant CIBSE Commissioning Code.

(vi) Performance Testing: the measuring and recording of the performance of


the commissioned installation.

Part H AC_GS
Page 8 of 10 2017 Edition
H3.2 PROCEDURES, STANDARDS AND REQUIREMENTS

The A/C Contractor shall follow relevant approved standards, procedures,


guidelines in the testing and commissioning works, which shall include but not
limited to:-

(a) Statutory obligations and requirements, specifications and standards


specified in Part A;

(b) Testing and Commissioning Procedure for Air-conditioning,


Refrigeration, Ventilation and Central Monitoring & Control System
Installation in Government Buildings of the Hong Kong Special
Administrative Region issued by BSB, ArchSD;

(c) Detailed inspection, testing and commissioning methods and procedures


approved by the Supervising Officer; and

(d) Equipment manufacturers recommendations and specifications, if any.

H3.3 MASTER PROGRAMME FOR TESTING AND COMMISSIONING


WORKS

The A/C Contractor is required to submit a programme for testing and


commissioning works within the first three months after acceptance of his
Tender. The programme shall indicate the tentative dates of all tests and
commissioning works that will be carried out throughout the Conditions and all
necessary submissions and approval relating to testing and commissioning. The
A/C Contractor shall ensure that the testing and commissioning programme
matches the master programme for construction and that all testing and
commissioning works are complete before the prescribed or extended date for
completion of the Works. The programme shall also be updated as the
Installations progress towards completion.

The programme shall detail the types of testing and commissioning works
required, the breakdown of the programme into floor-by-floor and/or area-by-
area basis, the tests that are required during construction and before completion
of the Installations, the period of each test with float time allowed, the milestone
dates for the key activities of works etc. Critical path programme shall be
submitted. The A/C Contractor shall plan the programme so as to minimise the
overlapping of different tests arranged simultaneously in different locations of
the Site.

A detailed checklist of all the Installations to be commissioned and tested shall


be submitted at the same time. The checklist will be used for progress
monitoring and shall be updated from time to time as the Installations progress
towards completion.

Part H AC_GS
Page 9 of 10 2017 Edition
H3.4 DOCUMENTATION AND DELIVERABLES

The A/C Contractor shall submit full commissioning and testing report to the
Supervising Officer within 14 days after completion of the commissioning and
testing of the Installations. The report shall be in accordance with the
requirements approved by the Supervising Officer.

H3.5 TESTING AND COMMISSIONING ENGINEER / SPECIALIST

Where specified in the Particular Specification, the A/C Contractor shall appoint
a competent and experienced testing and commissioning engineer/specialist
responsible for overall planning, organising, coordinating, supervising and
monitoring of the testing and commissioning works and also certifying all
results and reports from the testing and commissioning works. The A/C
Contractor shall submit, after the acceptance of his Tender, information
detailing the qualification and experience of the testing and commissioning
engineer/specialist for the Supervising Officers approval.

Part H AC_GS
Page 10 of 10 2017 Edition
PART I TRAINING, INSPECTION, ATTENDANCE, OPERATION
AND MAINTENANCE DURING MAINTENANCE PERIOD
SECTION I1

GENERAL REQUIREMENTS

I1.1 GENERAL

Unless otherwise specified in the Particular Specification, the A/C Contractor


shall provide training, inspection, attendance and operation and maintenance
services for the Installations during maintenance period as specified in this
General Specification.

The A/C Contractor shall supply and install, without additional cost to the
Employer, replacements for any equipment or parts thereof, which may, in the
opinion of the Supervising Officer, become unserviceable, especially where the
causes are attributable to faulty materials, workmanship, or inadequate
performance.

In the execution of servicing and maintenance, repair and operation work on site,
apart from transportation, necessary labour, tools, equipment and testing
instruments, the A/C Contractor shall also be responsible for keeping adequate
stocks of spare parts/equipment and other items necessary to maintain all
emergency repair in an efficient, satisfactory and safe operation condition at all
time.

The interruption of electricity supply and functioning of the Installations during


execution of works shall be kept to the minimum. Such interruption shall only
be allowed with the prior approval of the Supervising Officer or his
Representative.

The A/C Contractor shall provide all the Level One Services as specified in this
General Specification for all installation works.

Level Two Services detailed in this General Specification shall only be carried
out if specified in the Particular Specification. The specified Level Two
maintenance responsibilities shall be priced separately in the Tender with cost
for each individual item.

I1.2 COMPLETION OF OUTSTANDING AND DEFECTIVE WORKS

After receiving the list of defects and outstanding works issued with the
Certificate of Completion, the A/C Contractor shall complete the outstanding
works and rectify the defects concerned to the satisfaction of the Supervising
Officer within the agreed time frame during the Maintenance Period. The A/C
Contractor shall also rectify as soon as practicable any defects identified within
the Maintenance Period.

Part I AC_GS
Page 1 of 17 2017 Edition
The A/C Contractor shall submit periodic report on the progress of outstanding
and defective works to the Supervising Officer and attend inspection with the
Supervising Officers Representatives to verify satisfactory completion of the
outstanding and defective works.

I1.3 REPAIR AND MAINTENANCE RECORDS

The A/C Contractor shall be responsible for maintaining a log book in each of
the specific locations (e.g. switch room, plant room, etc.) as agreed with the
Supervising Officer or his Representative. Every attendance and details of work
done for the Installations including but not limited to repair, servicing and
maintenance shall be entered into the log book by the A/C Contractor so as to
form a comprehensive record of attendance and works done. The log book may
be completed in either English or Chinese. In addition, the A/C Contractor shall
also keep repair and maintenance records for the Installations in his own office
and shall be required to forward such records for checking if so requested by the
Supervising Officer.

Part I AC_GS
Page 2 of 17 2017 Edition
SECTION I2

TRAINING TO USERS AND OPERATION AND MAINTENANCE AGENTS

I2.1 GENERAL

Training for the operation and maintenance of system and equipment shall be
provided and arranged by the A/C Contractor. The training shall include all
training facilities, material and handouts etc. The A/C Contractor shall submit a
Training Schedule at least 3 months prior to the prescribed or extended date
for the completion of Works for the Supervising Officers approval. The
schedule shall include but not limited to the following requirements:

(i) The A/C Contractor shall provide facilities and training programme to
ensure that the Employers operation and maintenance staff acquire full
knowledge and operation, breakdown and routine maintenance, diagnosis
and hence operate and maintain reasonably effectively and efficiently the
system/equipment including Central Control and Monitoring System
offered. The training proposal shall include all aspects of operation and
maintenance of the plant including the use of special tools. Besides,
equipment portfolio for the installations offered shall be submitted
together with the training proposal. The equipment portfolio shall
include quantity of equipment, equipment cost, recommended serviceable
life by the manufacturer and cycle of major overhaul;

(ii) A training proposal for such service shall be included in the Tender;

(iii) The training proposal shall also include details and duration of the
training course(s), qualifications of the instructor and the qualification
requirements for the trainee(s);

(iv) Whenever possible, the training courses shall be held before or during the
commissioning period and shall be in Hong Kong.

The A/C Contractor shall submit full details of the training syllabus for
approval by the Supervising Officer;

(v) To reach the required depth of appreciation, the principles and theory and
practical "hands-on" demonstration shall be lectured; and

(vi) The operation and maintenance training of the IAQ equipment shall also
be included in the training programme. Any manual for the IAQ
equipment shall be prepared by qualified personnel.

Part I AC_GS
Page 3 of 17 2017 Edition
I2.2 OTHER TRAINING REQUIREMENTS

The training course shall contain, but not limited to, the following:-

(i) General description of the system and its associated equipment as a


whole;

(ii) Start-up and shut-down procedures;

(iii) Safety precautions during start-up and shut-down;

(iv) A detailed description of the functions of all switches and indicators on


control console;

(v) Trouble shooting procedures;

(vi) Preventive and corrective maintenance requirements to ensure proper


operation of a system or equipment under the maintenance programme;

(vii) Identification of all the operating parameters which affects the


performance of the plant;

(viii) Adjustment of the operating parameters to achieve optimum operating


conditions;

(ix) Check-list of all the periodic inspection and servicing of the plant;

(x) Illustration of the construction of major components of the plant by


sectional views;

(xi) Dismantling and reassembling procedures during a major repair;

(xii) Critical dimensions such as bearing clearance, wearing ring clearance,


thrust clearance, torque table for bolts and nuts, etc.;

(xiii) The use of special tools;

(xiv) Calibration for testing equipment, measurement, record and performance


assessment; and

(xv) Any other items as found necessary.

Part I AC_GS
Page 4 of 17 2017 Edition
SECTION I3

INSPECTION, ATTENDANCE, OPERATION AND MAINTENANCE


REQUIREMENTS

I3.1 RESPONSE AND ATTENDANCE TO EMERGENCY AND FAULT


CALLS

The A/C Contractor shall attend to emergency, fault and complaint calls arising
from defective work materials and/or system operation within one hour at any
time during the Maintenance Period and rectify all defects leading to fault or
breakdown of the equipment and/or system within the time as specified in
contract documents. The costs for the attendance, labour, materials and spare
parts for repair, submission of fault/breakdown reports, etc. are deemed to have
been allowed for in the Tender.

I3.2 MAINTENANCE SCHEDULE

The A/C Contractor shall prepare and submit the maintenance programme
before the commencement of the Maintenance Period for the approval of the
Supervising Officer.

Upon the approval of the above maintenance programme and before the
commencement of the Maintenance Period, the A/C Contractor shall prepare a
comprehensive maintenance schedule for all installations and indicate dates for
routine and periodic inspection, servicing and maintenance of the installations.

I3.3 INSPECTION DURING MAINTENANCE PERIOD

The A/C Contractor shall, in addition to the routine servicing and maintenance,
make further inspections for the Installations to check and, if necessary, re-
adjust the equipment/systems to meet the actual operation conditions and to test
the installations to meet statutory requirements including the submission of test
reports and certificates.

I3.4 JOINT INSPECTION AT THE END OF MAINTENANCE PERIOD

The A/C Contractor shall attend inspections to the Installations at the expiry of
the Maintenance Period in order to facilitate the acceptance and handing over of
the Installations to the Employers operation and maintenance agents. The A/C
Contractor shall conduct site checking and make necessary adjustments to the
equipment/systems one month before expiry of the Maintenance Period to
ensure that the Installations are in good working order, safe and satisfactory
operation condition for handover. If the Installations are unacceptable by the
Supervising Officer, the works covered in above Clauses I3.3 and I3.4 may have
to be repeated at the A/C Contractors expenses.

Part I AC_GS
Page 5 of 17 2017 Edition
I3.5 LEVEL ONE SERVICES MANDATORY RESPONSIBILITIES
DURING MAINTENANCE PERIOD

The A/C Contractor shall also be fully responsible for the following within the
Maintenance Period, in addition to the related aspects as stipulated in other
clauses under Part I:-

(i) Instruction to Employers Operation and Maintenance Staff

After the Works has been successfully handed over and put into
operation, the A/C Contractor shall provide full time attendance for a
period of at least 20 consecutive days or as stated in the Particular
Specifications, by a qualified operator(s) who shall be fully conversant
with the operation and maintenance of the plant. Their duties shall be to
operate the systems and to guide and instruct the Employers operation
staff such that they will become fully conversant with the operation of
the complete Installations.

Note: This commitment shall be carried out where the operational


responsibilities are to be immediately transferred to the Employers own
staff or at the end of Levels Two Services operational arrangements.

(ii) Completion of Any Outstanding Work

The A/C Contractor shall complete all outstanding works listed thereon
and rectify any defects that have arisen up to that time according to time
frame as specified in the list of defects and outstanding works issued
together with the letter of substaintial completion.

(iii) Servicing, Replacement and Replenishment

During the Maintenance Period, the A/C Contractor shall supply and
install, without additional charge to the Employer, replacements for all
and any equipment or parts thereof or liquids or gases, which may, in the
opinion of the Supervising Officer, became unserviceable, especially
where the causes are attributable to faulty materials, workmanship, or
inadequate performance. The A/C Contractor shall, at his own cost,
cover replacement of liquids or gases, oils and refrigerant which may be
lost by leakage or become contaminated or in other respects
unserviceable.

(iv) Supervising Officer to be informed

No replacement of plant or parts of plant shall be carried out at any time


unless the Supervising Officer has previously been notified and approved.

(v) Annual inspection and submission of maintenance certificate

Before the expiry of the Maintenance Period, the A/C Contractor shall
carry out and submit the annual inspection and submission of ventilation
certificate for the ventilating system as required under Building

Part I AC_GS
Page 6 of 17 2017 Edition
(Ventilating Systems) Regulations to the Director of Fire Services of the
completed Installations.

I3.6 LEVEL TWO SERVICES SPECIFIED CONTRACTORS


MAINTENANCE RESPONSIBILITIES DURING MAINTENANCE
PERIOD

Where specifically required in the Contract, the A/C Contractor shall allow for
and carry out full and comprehensive maintenance of the Installations during the
Maintenance Period. The works shall in addition to those required under the
LEVEL ONE SERVICES include also the followings: -

I3.6.1 The A/C Contractor shall be fully responsible for the following within
the Maintenance Period: -

(a) Inspection, checking, servicing, maintenance and repair


including replacement of parts and components due to normal
tears and wears;

(b) Emergency inspection, checking and servicing, repair and


rectification work;

(c) Provide skilled craftsmen to assist the start-up, control,


performance monitoring and shut-down of the plant;

(d) Test and commissioning of the Installations after the


completion of services, maintenance and repair; and

(e) Submission of services record and test report.

I3.6.2 The A/C Contractor shall provide labour, minor spare parts,
components and consumable materials in the following services
during the Maintenance Period: -

(a) Consumable materials such as re-filling of refrigerant and


lubricant, renewal of v-belts for blower motor as and when
required/necessary;

(b) All cutting and waste, packing, carriage, risk, moving, hoisting
and fixing at the required position;

(c) Repairs including first line attendance, emergency and


miscellaneous repairs, plants, tools, vehicles for transportation
of material for purposes of execution of work; and

(d) Preparation and submission of records/reports, in compliance


with miscellaneous requirements.

Upon substantial completion of the Works being certified by the


Supervising Officer, the A/C Contractor shall provide competent,
experienced and qualified staff and workshop facilities to undertake

Part I AC_GS
Page 7 of 17 2017 Edition
the Level Two maintenance works during the Maintenance Period.
Detailed information of the organisation, workshop facilities and list
of contact persons of the A/C Contractors maintenance team shall be
submitted to the Supervising Officer one month before the anticipated
substantial completion.

I3.6.3 A/C Contractors Responsibilities for Breakdown Call-out

(a) The A/C Contractor shall offer efficient and prompt response
to breakdown call-out for the installation/equipment failure.
The expedition of response shall be in accordance with the
following categories: -

(i) VERY URGENT for Installations breakdown including


failure of chiller, compressor, circulation pump, pipe
burst, water dripping, fire alarm and electricity power
failure, the A/C Contractor shall respond and attend to
the Very Urgent calls within 30 minutes;

(ii) URGENT for abnormality of equipment operation, the


A/C Contractor shall respond and attend to the Urgent
calls within 1 hour from the receipt of the calls; or

(iii) NON URGENT for abnormal room air condition, the


A/C Contractor shall respond and attend the fault
within 4 hours.

Investigation report and proposal for


repair/improvement/ modification shall be submitted
timely with time frame as instructed by Supervising
Officer or his Representative.

(b) The A/C Contractor shall promptly complete any repair


necessary for resuming the breakdown installation. In case
immediate permanent repair is not possible due to safety
related reason, the following "time for repair" targets counted
from the receipt of breakdown or fault call shall be complied
with: -

(i) Complete temporary repair for resumption of the


suspended or breakdown services to a safe operating
condition within 24 hours; and

(ii) Complete permanent rectification works within 3


working days unless long component and parts delivery
time is required.

I3.6.4 Maintenance Programme and Schedule

The A/C Contractor shall prepare, submit and seek endorsement on


the maintenance program before the anticipated commencement of
the Contract Maintenance Period. The maintenance programme

Part I AC_GS
Page 8 of 17 2017 Edition
should include Monthly Routine Service, Half-Yearly Service and
Annual Maintenance.

Upon the approval of the above maintenance program, the A/C


Contractor shall prepare a comprehensive maintenance schedule for
all installations and indicate dates for routine maintenance of the
Installations before the anticipated substantial completion.

I3.6.5 Co-ordination

The A/C Contractor shall co-operate and co-ordinate with the


Supervising Officers Representatives, user department, user
departments maintenance agent or EMSD, utility supply companies
and the public authorities for the smooth execution of maintenance
works.

I3.6.6 Plant Log and Breakdown/Fault Call Report

The A/C Contractor shall submit daily record of the following


documentation and reports at three months intervals: -

(a) Record of current status of plant and major equipment, all


services, maintenance and repair/replacement carried out for
the plant and equipment including the following details: -

(i) supply and return chilled water temperature;

(ii) lubrication oil pressure gauge readings;

(iii) refrigerant pressure gauge readings;

(iv) system chilled water flow rate and its percentage


against designed value;

(v) circulation pump suction and discharge pressure;

(vi) refrigerant compressor suction and discharge pressure;

(vii) dry and wet bulb temperature of supply air at designed


offices, function and conference rooms and that of
return air at system return and outdoor air condition;
and

(viii) IAQ audit report with monthly measurements of all


IAQ parameters.

(b) Equipment Breakdown Report

Equipment breakdown report shall be submitted after the


rectification work and shall have full details of findings during
investigation/examination on cause of breakdown, account of

Part I AC_GS
Page 9 of 17 2017 Edition
repair/replacement work needed, suggested precaution and/or
action required to prevent the recurrence of similar incident.

I3.6.7 Monthly Works

(a) General

(i) To check the general condition of the plant and


equipment such as chillers, compressors, condensers,
heat recovery equipment, heat pumps, IAQ equipment,
coils, chilled water pumps, make-up water tanks, air
handling units, fan coil units, water treatment
equipment and the associated electrical, electronic,
mechanical controls and circuit boards. To ensure that
the plant and equipment are satisfactorily operating
within design conditions;

(ii) To drain and clean the pre-filter and after-filter of the


pneumatic control system, and clean the refrigerated
drier and after-cooler, if any;

(iii) To check the lubricating system of all running pumps,


cooling fans, fan blowers, compressors, control
mechanisms and any other running parts; cleaning,
greasing and oiling where necessary;

(iv) To check any water leakage from the pipework and to


repair if required;

(v) To keep all supply and return grilles and louvers clean;

(vi) To check the corrosion of metal surface, framework


and support/mounting brackets, etc., and to reinstate the
surface by removing rust and repaint if necessary;

(vii) To check the operating conditions of water cooling


tower including the running current, water refilling rate,
water quality and other important operating parameters;
to conduct water quality and bacterial test; and to make
all necessary submission to the regulating authority
(including monthly operational records in Form CT3 to
EMSD); and

(viii) To check and ensure that the operation conditions of


the water treatment system are in accordance with the
Specifications and recommendation by the
manufacturer.

(b) Refrigerant Compressors, Chillers, Condensers and Heat


Pumps

Part I AC_GS
Page 10 of 17 2017 Edition
(i) To check for proper operation of the refrigeration
machines and related controls, control circuit, and
detect any abnormal noise and vibration, repair or
adjust as necessary;

(ii) To check and record on log sheets and where


appropriate on system performance sheet the refrigerant
compressor suction and discharge pressures, chilled
water inlets and outlet temperature, condenser air inlet
and outlet temperature and motor current;

(iii) To check condition of operating refrigerant, liquid level


and lubrication level, refill or renew as necessary;

(iv) To examine the condition of joints, stop valves, covers


and seals for leaks, repair as necessary;

(v) To remove debris and maintain the condenser in clean


and tidy condition;

(vi) To check driving belts for proper tension and correct


alignment, adjust and renew belts and lubricate
bearings; and

(vii) To check the vibration of machines as compare to the


recommendations by the manufacturer for future
baseline monitoring and maintenance.

(c) Motors for all motorised devices and equipment

(i) To clean motor casing, grease and lubricate;

(ii) To check and report any abnormal running noise and


vibration. Replace the bearings, perform megger test
on motor and repair as necessary; and

(iii) To check, adjust and rectify/repair defect on circuit


protective devices such as starters, control relay and
indicators.

(d) Pumps

(i) To visually inspect the pumps, check for abnormal


running noise and vibration;

(ii) To check and record on log sheets and where


appropriate on system performance sheet the water
pump suction and discharge pressure and motor current;

(iii) To check condition of gland for excessive wear.


Replace if necessary;

Part I AC_GS
Page 11 of 17 2017 Edition
(iv) To check drains are not clogged and rectify if necessary;

(v) To check pump bearing temperature thermostat and


repair if necessary;

(vi) To operate the vent valves once;

(vii) To check for proper operation of flow switch control


system and safety device, rectify if necessary;

(viii) To clean suction strainer;

(ix) To check for proper function of makeup system to the


chilled water or hot water circuit, rectify if necessary;
and

(x) To check for correct alignment of the motor and pump,


rectify if necessary.

(e) Air Handling Units

(i) To check that the air handling units and related controls
and control circuits are operating properly. Repair or
renew if necessary;

(ii) To check and record on log sheets and where


appropriate on system performance sheet the air
handling units operating conditions including motor
current, chilled or hot water inlet and outlet
temperatures, return and mix air temperatures, off coil,
and supply air temperature and humidity;

(iii) To check condensing water drain pan, drain pipe and


floor drain to ensure no clogging and flooding. Rectify
if necessary;

(iv) To clean and renew air filter as required;

(v) To check driving belts for proper tension and correct


alignment, adjust and renew belts and lubricate
bearings as required;

(vi) To check the operation of control valves and isolating


valves, rectify as required;

(vii) To clean the fresh air inlet, exhaust air louvers, air
dampers, accessible internal ductwork surfaces and fan
blades; and

(viii) To check the heaters for proper operation. Rectify if


necessary.

Part I AC_GS
Page 12 of 17 2017 Edition
(f) Fan Coil Units

(i) To check that the fan coil units and its control/sensing
devices are functioning properly and inspect drain pipes
to ensure no clogging and flooding. Rectify if
necessary;

(ii) To check and clean the condensing water drain pan,


drain pipes to ensure no clogging and flooding. Rectify
if necessary;

(iii) To clean the supply and return air grilles and filters;
and

(iv) To check the heaters and their control/protective


devices for proper operation. Rectify if necessary.

(g) Heat Exchanger (include calorifier)

(i) To check on all joints for leak. Rectify if necessary;

(ii) To examine all mountings (gauge, pressure relief valve,


etc.) to see that they are not damaged or leak and ensure
that they are in working order; and

(iii) To check the temperature settings and functioning of


the controls and ensure compliance with manufacturers
standards.

(h) Mechanical Ventilation System

(i) To clean fan blade and blades for wear and damage;

(ii) To check and if necessary to lubricate fan and motor


bearings;

(iii) To check the fan belt and to adjust and replace it, if
necessary;

(iv) To check flexible connections and that anti-vibration


mountings are free to move, and function properly;

(v) To clean the air filters, supply and return air grilles and
to renew air filters if necessary;

(vi) To check the operation and function of the control


devices;

(vii) To check all electrical wiring and connections and


circuit protection devices including switchgears and
starters. Rectify if required; and

Part I AC_GS
Page 13 of 17 2017 Edition
(viii) To clear the vanes in the ductwork.

(i) Equipment

(i) To check and service all IAQ equipment including air


cleaner, UV light chambers and other filtration and
sterilising system and equipment for IAQ; and

(ii) The A/C Contractor shall take measurements of IAQ


parameters and submit records to the Supervising
Officer.

I3.6.8 Half-Yearly Works

Half-yearly service and maintenance shall include the following items:


-

(a) To inspect the condition of pipe fittings, supports, ductwork,


hangers, etc., for sign of corrosion. Remove the rust and
repaint with primer and finish coating as necessary;

(b) To check the performance of controls and safety cut-outs and


check all control panel indication lamps, rectify as required;

(c) To clean electrical panels including wiring terminals and


connection points;

(d) To touch up with finish-coating where there is any rust or sign


of corrosion of the equipment by first removing the
rust/corrosion;

(e) To check and adjust, if necessary, the air flow in the air-
ductwork system;

(f) To clean all the air-cooled condenser coils by high-pressure


water or steam jet with approved cleaning detergent to ensure
that high heat transfer efficiency is maintained;

(g) To clean the cooling/heating coils (excluding fan coil units) by


high-pressure water or steam jet with approved cleaning
detergent to ensure that high heat transfer efficiency is
maintained;

(h) To check and serve all IAQ control and sensing equipment
including CO2 sensors, air movement sensors, thermostat,
humidifiers, dehumidifiers, humidistat, pressurestat and
volume control dampers;

(i) To inspect all components of ventilation system for cleanliness


and microbial growth and clean them as; and

Part I AC_GS
Page 14 of 17 2017 Edition
(j) To clean, dislodge and disinfect cooling towers as per
requirements stipulated in the Code of Practice for Fresh
Water Cooling Towers published by the EMSD.

I3.6.9 Annual Works

(a) To inspect the condition of pipe fittings, supports, ductwork,


hangers, etc., for sign of corrosion. Remove the rust and
repaint with primer and finish coating as necessary;

(b) To check the condition of pipe work and ductwork.


Recondition and if instructed, replace the deteriorated portion
in accordance with the Specification, acceptable engineering
practice and standard;

(c) To refit the isolating valves, change the valve gland and gasket,
and recondition the globe valves, etc. if necessary;

(d) To examine, check and maintain the proper operation of


associated electrical panels in the plant room. Repair and
renew as appropriate;

(e) To check, test and recalibrate or replace as necessary, all


control and safety devices;

(f) To check inlet guide vane of centrifugal compressor;

(g) To check, test, adjust, clean and repair/rectify defects if


required for all electronic circuit boards and control/ sensing/
detection devices including building automation system if
available in the system;

(h) To inspect and clean all internal surface of ductwork including


the supply and return air plenums. The cleaning of ductwork
shall not affect the normal operation of the building. The A/C
Contractor shall arrange the cleaning work after the building
office hour;

(i) To inspect aluminium foil, paints or other concrete sealing


layers and wall surface which meant to stop radon gas
emission and provide all necessary touch up work;

(j) To check and re-tighten any loose bolts and nuts in proper
sequence; and

(k) To arrange conducting of an annual operation and maintenance


audit for fresh water cooling towers by an independent auditor
as per requirements stipulated in the Code of Practice for Fresh
Water Cooling Towers published by the EMSD prior to expiry
of the 12 months Maintenance Period, and ensure submission
of an annual audit report to EMSD.

Part I AC_GS
Page 15 of 17 2017 Edition
I3.7 SPARE PARTS AND SPECIAL TOOLS

For plant and/or equipment included in the Contract, the A/C Contractor shall
provide the types of spare parts generally wherever these are appropriate to the
plant and/or equipment involved plus any additional items for the particular
plant and/or equipment.

Unless otherwise specified, within four months of the acceptance of the Tender,
or in such period of time as has been agreed by the Supervising Officer in
writing, the A/C Contractor shall submit in respect of the proposed plant and/or
equipment a list of the manufacturers recommended spare parts that are likely
to prove necessary to service the plant and/or equipment during the first years
operation and parts required immediately following the expiry of the
Maintenance Period.

The spare parts submission shall include diagrams or catalogue details of the
parts concerned. Unless specified in detail, the criteria by which the A/C
Contractor shall judge the need for spare parts to be included in the list shall be
any part or component of the plant or equipment that is subject to frictional wear,
vibration or temperature fatigue, rupturable to safety (or otherwise), corrosion,
erosion, unacceptable deposits and/or saturation by contaminants (such as for
filters), normal fair wear and tear and is likely to fail or reach an unacceptably
low performance level within a period of three years or less from its
commencement of operation.

The list shall include at least the following items where they are part of the
Installations: -

- Springs, valves, valve rings, valve plates, etc.;


- Bearings or bearing bushes;
- Electric carbon brushes;
- Electrical main and arcing contacts;
- Driving belts in matched sets;
- Standard and special replaceable type air or liquid filter media;
- Gaskets and jointing;
- Seals, gland packings, etc.;
- Rupturable safety devices;
- Replaceable heat exchanger tubes;
- Sight glasses;
- Plug in relays;
- Indicator light lamps;
- Non-standard fuse cartridges;
- Overload heaters/coils; and
- Flexible hoses and similar.

Part I AC_GS
Page 16 of 17 2017 Edition
Any of the above spare parts and/or disposable items which are required to
replace defective or prematurely worn out parts that arise during the
Maintenance Period shall be replaced by the A/C Contractor at no cost to the
Employer before the Maintenance Certificate is issued. The above items shall
not be exhaustive. The A/C Contractor shall be responsible for the replacement
of other parts and components for normal operation of the Installations.

Additionally, the A/C Contractor shall submit within the same period a priced
schedule for the supply of any special tools necessary for servicing and
maintenance of any part of the Installations.

Instructions for purchase of any special tool shall be issued separately but the
basis for charging shall be similar to that for the A/C Contractors equipment
manufacturers recommended spare parts.

The purchase of the needed spare parts and tools shall be secured by Supervising
Officers instruction.

The exact types and quantities shall be determined by the Supervising Officer
based on the A/C Contractors best advice and at the most appropriate time
during the Contract Period when requirements can be most realistically assessed
taking account of the Installations as installed or still being installed.

Part I AC_GS
Page 17 of 17 2017 Edition
ANNEX I
LIST OF TECHNICAL STANDARDS QUOTED IN THIS GENERAL
SPECIFICATION

Part and
Standard Description
Clause No.
AHRI 210/240:2008 Performance Rating of Unitary Air-Conditioning C6.22.4
& Air-Source Heat Pump Equipment

AHRI 410:2001 Forced-Circulation Air-Cooling and Air-Heating C3.6.3(b),


Coils C3.2.10(f),
C3.2.13(c)

AHRI 550/590: 2012 Performance Rating of Water Chilling Packages C6.1


Using the Vapor Compression Cycle

AHRI 560:2000 Absorption Water Chilling and Water Heating C6.1


Packages

AHRI 575:2008 Method of Measuring Machinery Sound Within C6.1


an Equipment Space

AHRI 1060:2005 Performance Rating of Air-To-Air Heat D5.1.1(d)(v)


Exchangers for Energy Recovery Ventilation
Heat Equipment

ANSI/AMCA Laboratory Methods of Testing Fans for Certified C3.3.2, C3.5.3


Standards 210-07 Aerodynamic Performance Rating

ANSI/AMCA Reverberant Room Method for Sound Testing of C3.3.2, C3.5.3,


Standards 300-14 Fans C3.14.2

ANSI/ASHRAE 15- Safety Standard for Refrigeration Systems, and B6.1, B6.2,
2013 (Packaged with Design and Safety Classification of Refrigerants B6.14.1, C6.1,
ANSI/ASHRAE 34- C6.21.1
2013)

ANSI/ASHRAE Method of Testing General Ventilation Air- C1.1.1,


52.2-2012 Cleaning Devices for Removal Efficiency by C1.2.1(a),
Particle Size C1.3, C1.4,
C1.5, C1.6,
C1.7, C1.8,
C1.9, C1.10,
C1.12, C1.14,
D5.1.1(e)(ii),
D5.4

ANSI/ASHRAE Method of Testing the Performance of Air Outlets C3.18.1(a),


70-2006 and Air Inlets C3.17.4(b)

Annex I AC_GS
Page 1 of 19 2017 Edition
Part and
Standard Description
Clause No.
ANSI/ASHRAE Method of Testing Air-to-Air Heat Exchangers D5.1.1(d)(v)
84-2013

ANSI/ASHRAE Energy Standard for Buildings Except Low-Rise C6.1


90.1-2013 Residential Buildings

ANSI/ASHRAE BACnet(r): A Data Communication Protocol for B5.1.2(c),


135-2012 Building Automation and Control Networks C5.3(a)

ANSI/ASHRAE Standard for the Design of High-Performance C6.1


189.1-2014 Green Buildings

ANSI/ASME Code Refrigeration Piping and Heat Transfer C6.20.3


B31.5: 2013 Components

ANSI C12.1:2008 American National Standard for Electric Meters B6.5.5 (c),
Code for Electricity Metering

ANSI C12.20:2010 Electricity Meters 0.2 and 0.5 Accuracy Classes B6.5.5(c),
B6.5.5 (d)

ANSI/CEA-709.1- Control Network Protocol Specification C5.3(c)


B:2002

ANSI/EIA 310-D: Mechanical Core Specifications for C5.4(a)


1992 Microcomputers Using IEC 603-2 Connectors

ANSI/IIAR Standard American National Standard the Safe Design of B6.14.1,


2-2014 Closed Circuit Ammonia Refrigeration Systems B6.14.4,
C6.20.3

AS 3498:2009 Authorization requirements for plumbing C6.28.4


products - Water heaters and hot-water storage
tanks

AS/NZS 1301.403s: Methods of test for pulp and paper - Bursting C11.4.2
2006 strength of paper (c)

AS/NZS 2712:2007 Solar and Heat Pump Water Heaters - Design and C6.28.3(a)
Construction

ASHRAE 62.1-2013 Ventilation for Acceptable Indoor Air Quality C6.3

ASHRAE Guideline Measurement of Energy and Demand Savings B6.5.5


14

ASHRAE Guideline Instrumentation for Monitoring Central Chilled- B6.5.5


22 Water Plant Efficiency

Annex I AC_GS
Page 2 of 19 2017 Edition
Part and
Standard Description
Clause No.
ASME Boiler and 2013 ASME Boiler and Pressure Vessel Code, B6.14.1,
Pressure Vessel Section II - Materials C6.20.3
Code: 2013

ASTM A278/ Standard Specification for Grey Iron Castings for C13.13
A278M-01: 2011 Pressure-Containing Parts for Temperatures Up to
650 F (350 C)

ASTM A436-84: Standard Specification for Austenitic Grey Iron C13.13


2011 Castings

ASTM B124/ Standard Specification for Copper and Copper C9.3.2(d)


B124M-14a Alloy Forging Rod, Bar, and Shapes

ASTM C423-09a Standard Test Method for Sound Absorption and C8.7, C8.12.5
Sound Absorption Coefficients by the
Reverberation Room Method

ASTM C916-14 Standard Specification for Adhesives for Duct B8.7


Thermal Insulation

ASTM C1071-12 Standard Specification for Fibrous Glass Duct C8.7


Lining Insulation (Thermal and Sound Absorbing
Material)

ASTM Standard Specification for Greige Woven Glass B11.6.3(c)


D579/D579M-10 Fabrics

ASTM D882-12 Standard Test Method for Tensile Properties of C11.4.3(b)


Thin Plastic Sheeting

ASTM D3330/ Standard Test Method for Peel Adhesion of C11.4.3(c)


D3330M-04(2010) Pressure-Sensitive Tape

ASTM E84-14 Standard Test Method for Surface Burning B11.6.4(d),


Characteristics of Building Materials C6.13.4, C8.7,
C8.9,
D5.1.1(d)(viii)

ASTM E90-09 Standard Test Method for Laboratory C8.8, C8.12.5,


Measurement of Airborne Sound Transmission C8.10
Loss of Building Partitions and Elements

ASTM E96/E96M- Standard Test Methods for Water Vapour C11.4.2(d)


14 Transmission of Materials

ASTM E408-13 Standard Test Methods for Total Normal C11.2.1(g),


Emittance of Surfaces Using Inspection-Meter C11.4.2(e),
Techniques C11.4.3(e),

Annex I AC_GS
Page 3 of 19 2017 Edition
Part and
Standard Description
Clause No.
ASTM G21-13 Standard Practice for Determining Resistance of C2.6.2
Synthetic Polymeric Materials to Fungi

BS 417-2:1987 Specification for galvanized low carbon steel C13.14.2(a)(i)


cisterns, cistern lids, tanks and cylinders. Metric
units

BS 476-4:1970 Fire tests on building materials and structures. C1.2.2(a), C8.7,


Non-combustibility test for materials C8.9,
C3.17.1(d),
C3.18.3(b)

BS476-6:1989 Fire tests on building materials and structures. C1.2.2(b),


+A1:2009 Method of test for fire propagation for products C2.4, C2.8,
C3.17.1(d),
C3.18.3(b),
C11.1.2(a)

BS 476-7:1997 Fire tests on building materials and structures. B2.4, C1.18,


Method of test to determine the classification of C2.8, C2.15,
the surface spread of flame of products C3.17.1(d),
C3.18.3(b),
C11.1.2(a)

BS 476-12:1991 Fire tests on building materials and structures. C2.4,


Method of test for ignitability of products by C3.17.1(d),
direct flame impingement C3.18.3(b),

BS 476-20:1987 Fire tests on building materials and structures. B2.4, C2.11.1,


Method for determination of the fire resistance of C2.11.2, C8.10,
elements of construction (general principles) C8.12.2,
C11.2.9

BS 476-21:1987 Fire tests on building materials and structures. C2.11.1, C8.10,


Methods for determination of the fire resistance C8.12.2
of loadbearing elements of construction

BS 476-22:1987 Fire tests on building materials and structures. C2.11.1,


Methods for determination of the fire resistance C2.11.2, C8.10,
of non-loadbearing elements of construction C8.12.2

BS 476-23:1987 Fire tests on building materials and structures. C2.11.1,


Methods for determination of the contribution of
components to the fire resistance of a structure

BS 1564:1975 Specification for pressed steel sectional C13.14.2(a)(ii)


rectangular tanks

BS 1710:2014 Specification for identification of pipelines and B11.8.3


services

Annex I AC_GS
Page 4 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS 2502:1979 Specification for manufacture of sectional cold C6.3
rooms (walk-in type)

BS 3790:2006 Specification for belt drives. Endless wedge belts, B3.1


endless V-belts, banded wedge belts, banded V-
belts and their corresponding pulleys

BS 3928:1969 Method for sodium flame test for air filters (other C3.2.8
than for air supply to I.C. engines and
compressors)

BS 4213:2004 Cisterns for domestic use. Cold water storage and C13.14.2(a)(iii)
combined feed and expansion (thermoplastic)
cisterns up to 500 l. Specification

BS 4766:1989 Fire tests on building materials and structures. C1.2.2(b),


+A1:2009 Method of test for fire propagation for products C2.4, C2.8,
C3.13.1(d),
C3.14.3(b),
C11.1.2,
C11.1.2(a)

BS 4800:2011 Schedule of paint colours for building purposes B11.8.2, G3,


G4

BS 4856-2:1975 Methods for testing and rating fan coil units, unit C3.6.1
heaters and unit coolers. Thermal and volumetric
performance for cooling duties: without
additional ducting

BS 4857-1:1972 Methods for testing and rating terminal reheat C3.17.1(a)


units for air distribution systems. Thermal and
aerodynamic performance

BS 4857-2:1978 Methods for testing and rating terminal reheat C3.17.1(a)


units for air distribution systems. Acoustic testing
and rating

BS 4954-1:1973 Methods for testing and rating induction units for C3.17.1(a)
air distribution systems. Thermal and
aerodynamic performance

BS 4954-2:1978 Methods for testing and rating induction units for C3.17.1(a)
air distribution systems. Acoustic testing and
rating

BS 5141-2:1977 Specification for air heating and cooling coils. C3.2.13(c)


Method of testing for rating of heating coils

BS 5315:1991 Hose clamps (worm drive type) for general B2.5


purpose use (metric series)

Annex I AC_GS
Page 5 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS 5422:2009 Method for specifying thermal insulating B11.6.3,
materials for pipes, tanks, vessels, ductwork and C11.1.1,
equipment operating within the temperature range C11.1.2,
-40C to +700C C11.2.4,
C11.4.4

BS 5733:2010 + A1: Specification for general requirements for H1.7


2014 electrical accessories

BS 5970:2012 Thermal insulation of pipework, ductwork, C11.1.1


associated equipment and other industrial
installations in the temperature range of -100C
to +870C. Code of practice.

BS 6387:2013 Specification for performance requirements for C3.1.5


cables required to maintain circuit integrity under
fire conditions

BS 7116:1990 Specification for double sided pressure sensitive C11.4.3(d)


adhesive tapes

BS EN 197-1:2011 Cement. Composition, specifications and C9.5


conformity criteria for common cements

BS EN 378-1: Refrigerating systems and heat pumps. Safety and H1.7


2008+A2:2012 environmental requirements. Basic requirements,
definitions, classification and selection criteria

BS EN 378-2: Refrigerating systems and heat pumps. Safety and B6.2, C6.21.1,
2008+A2:2012 environmental requirements. Design, H1.7
construction, testing, marking and documentation

BS EN 378-3: Refrigerating systems and heat pumps. Safety and B6.1, B6.2,
2008+A1:2012 environmental requirements. Installation site and H1.7
personal protection

BS EN 378-4: Refrigerating systems and heat pumps. Safety and H1.7


2008+A1:2012 environmental requirements. Operation,
maintenance, repair and recovery

BS EN 545:2010 Ductile iron pipes, fittings, accessories and their C9.5


joints for water pipelines. Requirements and test
methods

BS EN 598: Ductile iron pipes, fittings, accessories and their C9.5


2007+A1:2009 joints for sewerage applications. Requirements
and test methods

BS EN 779:2012 Particulate air filters for general ventilation. C3.2.8,


Determination of the filtration performance C3.6.1(b)

Annex I AC_GS
Page 6 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS EN 837-1:1998 Pressure gauges. Bourdon tube pressure gauges. C10.5
Dimensions, metrology, requirements and testing

BS EN 969:2009 Ductile iron pipes, fittings, accessories and their C9.5


joints for gas pipelines. Requirements and test
methods

BS EN 1057:2006 + Copper and copper alloys. Seamless, round C9.5,


A1: 2010 copper tubes for water and gas in sanitary and
heating applications

BS EN 1092-1:2007 Flanges and their joints. Circular flanges for C8.5.2, C13.11,
+ A1:2013 pipes, valves, fittings and accessories, PN C13.14.2(d)
designated. Steel flanges

BS EN 1092-2:1997 Flanges and their joints. Circular flanges for C13.11


pipes, valves, fittings and accessories, PN
designated. Cast iron flanges

BS EN 1287:1999 Mixing valves. Specification for thermostatic C9.9


mixing valves

BS EN 1515-1:2000 Flanges and their joints. Bolting. Selection of C13.11


bolting

BS EN 1561:2011 Founding. Grey cast irons B9.15.3, C9.4,


C13.1.3(a),
C13.1.3(d),
C13.2.3(a),
C13.13

BS EN 1751:2014 Ventilation for buildings. Air terminal devices. C2.8, C2.12


Aerodynamic testing of dampers and valves

BS EN 1822-1:2009 High efficiency air filters (EPA, HEPA and C1.2.1(d)


ULPA). Classification, performance testing,
marking

BS EN 1822-2:2009 High efficiency air filters (EPA, HEPA and C1.2.1(d)


ULPA). Aerosol production, measuring
equipment, particle counting statistics

BS EN 1822-3:2009 High efficiency air filters (EPA. HEPA and C1.2.1(d)


ULPA). Testing flat sheet filter media

BS EN 1822-4:2009 High efficiency air filters (EPA, HEPA and C1.2.1(d)


ULPA). Determining leakage of filter element
(scan method)

Annex I AC_GS
Page 7 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS EN 1822-5:2009 High efficiency air filters (EPA, HEPA and C1.2.1(d)
ULPA). Determining the efficiency of filter
element

BS EN 1886:2007 Ventilation for buildings. Air handling units. C3.2.1, C3.2.7


Mechanical performance

BS EN 1982:2008 Copper and copper alloys. Ingots and castings C13.1.3(b),


C13.1.3(c),
C13.2.3(b)(i)

BS EN 10029:2010 Hot-rolled steel plates 3 mm thick or above. B9.3.2


Tolerances on dimensions and shape.

BS EN 10051:2010 Continuously hot-rolled strip and plate/sheet cut B9.3.2


from wide strip of non-alloy and alloy steels.
Tolerances on dimensions and shape

BS EN 10084:2008 Case hardening steels. Technical delivery C13.1.3(c),


conditions C13.2.3(d),
C13.13

BS EN 10087:1999 Free cutting steels. Technical delivery conditions C13.1.3(c),


for semi-finished products, hot rolled bars and C13.2.3(d),
rods C13.13

BS EN 10226- Pipe threads where pressure tight joints are made B 9.8.1
1:2004 on the threads. Taper external threads and parallel
internal threads. Dimensions, tolerances and
designation

BS EN 12975- Thermal solar systems and components. Solar C6.28.3(a)


1:2006 +A1:2010 collectors. General requirements.

BS EN 12975- Thermal solar systems and components. Solar C6.28.1,


2:2006 collectors. Test methods C6.28.3(a)

BS EN 12976- Thermal solar systems and components. Factory C6.28.3(a)


1:2006 made systems. General requirements

BS EN 12976- Thermal solar systems components. Factory made C6.28.3(a)


2:2006 systems. Test methods

BS EN 13835:2012 Founding. Austenitic cast irons C13.2.3(b)(ii)

BS EN 14511-1: Air conditioners, liquid chilling packages and C6.1, C6.5.2(p)


2013 heat pumps with electrically driven compressors
for space heating and cooling

Annex I AC_GS
Page 8 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS EN 14511-2: Air conditioners, liquid chilling packages and C6.1, C6.5.2(p)
2013 heat pumps with electrically driven compressors
for space heating and cooling. Test conditions

BS EN 14511-3: Air conditioners, liquid chilling packages and C6.1, C6.5.2(p)


2013 heat pumps with electrically driven compressors
for space heating and cooling. Test methods

BS EN 14511-4: Air conditioners, liquid chilling packages and C6.1, C6.5.2(p)


2013 heat pumps with electrically driven compressors
for space heating and cooling. Operating
requirements, marking and instructions

BS EN 60034-1: Rotating electrical machines. Rating and H1.7


2010 performance

BS EN 60073:2002 Basic and safety principles for man-machine G5


interface, marking and identification. Coding
principles for indicators and actuators.

BS EN 60079-0: Explosive atmospheres. Equipment. General C13.4.3


2012 + A11:2013 requirements

BS EN 60079-1: Explosive atmospheres. Equipment protection by C13.4.3


2014 flameproof enclosures d

BS EN 60335-1: Household and similar electrical appliances. H1.7


2012 + A11: 2014 Safety. General requirements

BS EN 60529:1992 Specification for degrees of protection provided F.5.3(a)


+ A2: 2013 by enclosures (IP code).

BS EN 60669-1: Switches for household and similar fixed H1.7


1999 + A2:2008 electrical installations. General requirements

BS EN 60670-22: Boxes and enclosures for electrical accessories H1.7


2006 for household and similar fixed electrical
installations. Particular requirements for
connecting boxes and enclosures

BS EN 60939-2: Passive filter units for electromagnetic C6.5.2(g)


2005 interference suppression. Sectional specification:
passive filter units for which safety tests are
appropriate. Test methods and general
requirements

BS EN 61000-6-1: Electromagnetic compatibility (EMC). Generic C1.16, C10.8


2007 standards. Immunity for residential, commercial
and light-industrial environments

Annex I AC_GS
Page 9 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS EN 61000-6-2: Electromagnetic compatibility (EMC). Generic C1.16, C10.8
2005 standards

BS EN 61000-6-3: Electromagnetic compatibility (EMC). Generic C1.16, C10.8


2007+A1:2011 standards. Emission standard for residential,
commercial and light-industrial environments

BS EN 61000-6-4: Electromagnetic compatibility (EMC). Generic C1.16, C10.8


2007+A1:2011 standards. Emission standard for industrial
environments

BS EN ISO 844: Rigid cellular plastics -- Determination of C11.2.1(c),


2014 compression properties. C11.2.8(c)

BS EN ISO 1452-1: Plastics piping systems for water supply and for C9.5
2009 buried and above ground drainage and sewerage
under pressure Unplastized poly (vinyl chloride)
(PVC-U) Part 1: General

BS EN ISO 1452 Plastics piping systems for water supply and for C9.5
2: 2009 buried and above ground drainage and sewerage
under pressure Unplastized poly (vinyl
chloride) (PVC-U) Part 2: Pipes

BS EN ISO 1452 Plastics piping systems for water supply and for C9.5
3: 2010 buried and above ground drainage and sewerage
under pressure Unplastized poly (vinyl
chloride) (PVC-U) Part 3: Fittings

BS EN ISO 1452 Plastics piping systems for water supply and for C9.5
4: 2010 buried and above ground drainage and sewerage
under pressure Unplastized poly (vinyl
chloride) (PVC-U) Part 4: Valves

BS EN ISO 1452 - 5: Plastics piping systems for water supply and for C9.5
2010 buried and above ground drainage and sewerage
under pressure Unplastized poly (vinyl
chloride) (PVC-U) Part 5: Fitness

BS EN ISO 4590: Rigid cellular plastics. Determination of the C11.2.1 (e),


2003 volume percentage of open cells and of closed
C11.2.8(e)
cells

BS EN ISO 5136: Acoustics -- Determination of sound power H1.7


2010 radiated into a duct by fans and other air-moving
devices -- In-duct method

BS EN ISO 5659-2: Plastics -- Smoke generation -- Part 2: C2.7.1.3,


2012 Determination of optical density by a single- C2.7.2.3,
chamber test C11.2.4(g)

Annex I AC_GS
Page 10 of 19 2017 Edition
Part and
Standard Description
Clause No.
BS EN ISO 6708: Pipework components -- Definition and selection C9.5
1996 of DN (nominal size)

BS EN ISO 9445: Continuously cold-rolled stainless steel narrow B9.3.2


2006 strip, wide strip, plate/sheet and cut lengths.
Tolerances on dimensions and form

BS EN ISO 9906: Rotodynamic pumps. Hydraulic performance B13.1, H1.7


2012 acceptance tests. Grades 1, 2 and 3.

BS ISO 1922:2012 Rigid cellular plastics. Determination of shear C 11.2.1,


strength C11.2.8

BS ISO 3966:2008 Measurement of fluid flow in closed conduits. C 10.6


Velocity area method using Pitot static tubes

BS ISO 7194:2008 Measurement of fluid flow in closed conduits. C 10.6


Velocity-area methods of flow measurement in
swirling or asymmetric flow conditions in
circular ducts by means of current-meters or Pitot
statics tubes

BS ISO 10816- Mechanical vibration. Evaluation of machine C3.1.4(b)


vibration by measurements on non-rotating parts.
1:1995+A1:2009
General guidelines

CSA 22.2 No. 8-13 Electromagnetic interference (EMI) filters C6.5.2(g)

CTI- STD-201 Standard for the Certification of Water Cooling C6.13.1


RS:2015 Tower Thermal Performance

DIN 50154:1980 Tensile test without extensometer on foils and C11.2.8(c), (d)
strips of aluminium and wrought aluminium
alloys with a thickness up to 0.179 mm

DIN 53438-3:1984 Testing of combustible materials; response to C1.2.2(d)


ignition by a small flame; surface ignition

DW/143:2013 Guide to Ductwork Leakage Testing B2.1, B2.9,


B2.10, C2.14

DW/144:2013 Specification for Sheet Metal Ductwork Low C2.3(a), C2.8,


Medium & High Pressure Velocity Air Systems C2.14, C2.15,
C2.17, C3.2.1,
C3.5.1,
C3.17.1(b),
C3.17.4(b),
B2.1, B2.3,
B2.10, B11.8.3

DW/154:2000 Specification for plastics ductwork C2.3(b), C2.5


Annex I AC_GS
Page 11 of 19 2017 Edition
Part and
Standard Description
Clause No.
DW/191:1973 Guide to good practice glass fibre ductwork C2.3(c), C2.6.2

Eurovent Document Air Leakage rate in Sheet Metal Air Distribution C3.20, 1(c)
2/2 1996 Systems

IEC60072-1:1991 Dimensions and output series for rotating H1.7


electrical machines - Part 1: Frame numbers 56 to
400 and flange numbers 55 to 1080

IEC60072-2:1990 Dimensions and output series for rotating H1.7


electrical machines - Part 2: Frame numbers 355
to 1000 and flange numbers 1180 to 2360

IEC60072-3:1994 Dimensions and output series for rotating H1.7


electrical machines - Part 3: Small built-in motors
- Flange numbers BF10 to BF50

IEC60076-1:2011 Power transformers Part 1: General - Edition C6.5.2(f)


3.0

IEC61000-4-11:2004 Testing and measurement techniques Voltage C6.5.2(g)


dips, short interruptions and voltage variations
immunity tests

IEC61000-4-34:2005 Testing and measurement techniques Voltage C6.5.2(g)


dips, short interruptions and voltage variations
immunity tests for equipment with mains current
more than 16A per phase

IEC 61439-1:2011 Low-voltage switchgear and control gear H1.7


assemblies - Part 1: General rules

IEC 62053-21:2003 Electricity metering equipment (a.c.) Particular B6.5.5(d)


requirements Part 21: Static meters for active
energy (classes 1 and 2) - Edition 1.0

IEC 62053-22:2003 Electricity metering equipment (a.c.) Particular B6.5.5(c)


requirements Part 22: Static meters for active
energy (classes 0,2 S and 0,5 S) - Edition 1.0

IEC 62058:2008 Electricity metering equipment (AC) B6.5.59(c),


Acceptance inspection B6.5.5(d)

IEC 62271-100: High-voltage switchgear and controlgear Part H1.7


2008 + AMD1:2012 100: Alternating current circuit-breakers

IMO MSC 61(67) Smoke and toxicity test C11.2.4(h)

ISO 7-1: 1994/Cor Pipe threads where pressure-tight joints are made B9.8.1, C8.5.2,
1:2007 on the threads -- Part 1: Dimensions, tolerances B9.3.2, C9.5,
and designation B9.15.3

Annex I AC_GS
Page 12 of 19 2017 Edition
Part and
Standard Description
Clause No.
ISO 65:1981 Carbon steel tubes suitable for screwing in C9.5
accordance with ISO 7-1

ISO 185:2005 Grey cast irons -- Classification B9.15.3, C9.4,


C13.1.3(a),
C13.1.3(d),
C13.2.3(a),
C13.13

ISO 197-4:1983 Copper and copper alloys -- Terms and C9.4,


definitions -- Part 4: Castings C13.1.3(b),
C13.1.3(c),
C13.2.3(b)(i)

ISO 254:2011 Belt drives -- Pulleys -- Quality, finish and B3.1


balance

ISO 1081:1995 Belt drives -- V-belts and V-ribbed belts, and B3.1
corresponding grooved pulleys -- Vocabulary

ISO 1182:2010 Reaction to fire tests for products. Non- C3.17.1(d),


combustibility test C3.18.3(b)

ISO 1663:2007 Rigid cellular plastics -- Determination of water C11.2.1(f)


vapour transmission properties

ISO 1813:2014 Belt drives -- V-ribbed belts, joined V-belts and B3.1
V-belts including wide section belts and
hexagonal belts -- Electrical conductivity of
antistatic belts: Characteristics and methods of
test

ISO 1940-1: 2003/ Mechanical vibration -- Balance quality H1.7


Corr1: 2005 requirements for rotors in a constant (rigid) state -
- Part 1: Specification and verification of balance
tolerances

ISO 2016:1981 Capillary solder fittings for copper tubes -- B9.9.1, C9.5
Assembly dimensions and tests

ISO 2892: 2007/Cor Austenitic cast irons -- Classification C13.2.3(b)(ii)


1:2009

ISO 3864-1:2011 Graphical symbols -- Safety colours and safety G.3


signs -- Part 1: Design principles for safety signs
in workplaces and public areas

ISO 4183:1995 Belt drives -- Classical and narrow V-belts -- B3.1


Grooved pulleys (system based on datum width)

Annex I AC_GS
Page 13 of 19 2017 Edition
Part and
Standard Description
Clause No.
ISO 4184:1992 Belt drives -- Classical and narrow V-belts -- B3.1
Lengths in datum system

ISO 5149-1:2014 Refrigerating systems and heat pumps - Safety C6.1


and environmental requirements - Part 1:
Definitions, classification and selection criteria

ISO 5149-2:2014 Refrigerating systems and heat pumps - Safety C6.1


and environmental requirements - Part 2: Design,
construction, testing, marking and documentation

ISO 5149-3:2014 Refrigerating systems and heat pumps - Safety C6.1


and environmental requirements - Part 3:
Installation site

ISO 5149-4:2014 Refrigerating systems and heat pumps - Safety C6.1


and environmental requirements - Part 4:
Operation, maintenance, repair and recovery

ISO 5151:2010 Non-ducted air conditioners and heat pumps -- B12.1.2


Testing and rating for performance

ISO 5167-1:2003 Measurement of fluid flow by means of pressure C10.7


differential devices inserted in circular cross-
section conduits running full -- Part 1: General
principles and requirements

ISO 5187:1985 Welding and allied processes -- Assemblies made B9.18.5


with soft solders and brazing filler metals --
Mechanical test methods

ISO 5208:2008 Industrial valves -- Pressure testing of valves C9.3.2(a)

ISO 5209:1977 General purpose industrial valves -- Marking C9.3.2(h)

ISO 5292:1995 Belt drives -- V-belts and V-ribbed belts -- B3.1


Calculation of power ratings

ISO 5457:1999/ Technical product documentation -- Sizes and A4.3.2, A4.2.2


Amd 1: 2010 layout of drawing sheets

ISO 5801: 2007/Cor Industrial fans -- Performance testing using C3.3.2, C3.5.3,
1:2008 standardized airways H1.7

ISO 6453:1985 Polymeric materials, cellular flexible -- C2.5


Polyvinylchloride foam sheeting -- Specification

Annex I AC_GS
Page 14 of 19 2017 Edition
Part and
Standard Description
Clause No.
ISO 7005-1:2011 Pipe flanges -- Part 1: Steel flanges for industrial B9.3.2, B9.3.3,
and general service piping systems B9.8.2, B9.9.1,
B9.15.3,
C13.11,
C13.14.2(d)

ISO 7005-2:1988 Metallic flanges -- Part 2: Cast iron flanges B9.9.1,


B9.15.3, C9.7,
C13.11,
C13.14.2(d)

ISO 7005-3:1988 Metallic flanges -- Part 3: Copper alloy and B9.9.1,


composite flanges B9.15.3, C9.7,
C13.14.2(d)

ISO 7268: 1983/ Pipe components -- Definition of nominal C9.5


Amd 1:1984 pressure

ISO 8079:1984 Aerospace process -- Anodic treatment of C11.2.8(a)


aluminium alloys -- Sulfuric acid process, dyed
coating

ISO 8302:1991 Thermal insulation -- Determination of steady- C11.2.1(d)


state thermal resistance and related properties --
Guarded hot plate apparatus

ISO 9001: 2008/ Quality Management systems -- Requirements A3.17.5,


Corr1: 2009 B9.3.2, C3.2.1,
C3.6.1,
D5.1.2(a)

ISO 9330-1:1990 Welded steel tubes for pressure purposes -- C9.5


Technical delivery conditions -- Part 1:
Unalloyed steel tubes with specified room
temperature properties

ISO 9330-2:1997 Welded steel tubes for pressure purposes -- C9.5


Technical delivery conditions -- Part 2: Electric
resistance and induction welded unalloyed and
alloyed steel tubes with specified elevated
temperature properties

ISO 9330-3:1997 Welded steel tubes for pressure purposes -- C9.5


Technical delivery conditions -- Part 3: Electric
resistance and induction welded unalloyed and
alloyed steel tubes with specified low temperature
properties

Annex I AC_GS
Page 15 of 19 2017 Edition
Part and
Standard Description
Clause No.
ISO 9692-1:2013 Welding and allied processes -- B2.7, B9.3.3,
Recommendations for joint preparation -- Part 1: B9.18.3,
Manual metal-arc welding, gas-shielded metal-arc B9.18.4
welding, gas welding, TIG welding and beam
welding of steels

ISO 10294-1:1996/ Fire resistance tests -- Fire dampers for air C2.11.1,
Amd 1:2014 distribution systems -- Part 1: Test method C2.11.2

ISO 10816-1: 1995/ Mechanical vibration -- Evaluation of machine C3.1.4(b)


Amd 1:2009 vibration by measurements on non-rotating parts -
- Part 1: General guidelines

ISO 13253: 2011 Ducted air-conditioners and air-to-air heat pumps B12.1.2
-- Testing and rating for performance

ISO 13256-1:1998 Water-source heat pumps -- Testing and rating for B12.1.2
performance -- Part 1: Water-to-air and brine-to-
air heat pumps

ISO 13256-2:1998 Water-source heat pumps -- Testing and rating for B12.1.2
performance -- Part 2: Water-to-water and brine-
to-water heat pumps

ISO 13261-1:1998 Sound power rating of air-conditioning and air- B12.2


source heat pump equipment -- Part 1: Non-
ducted outdoor equipment

ISO 13261-2:1998 Sound power rating of air-conditioning and air- B12.2


source heat pump equipment -- Part 2: Non-
ducted indoor equipment

ISO 14644-1:1999 Cleanrooms and associated controlled C1.11


environments -- Part 1: Classification of air
cleanliness

ISO 15609-1:2004/ Specification and qualification of welding B9.18.3


Corr 1:2005 procedures for metallic materials welding
procedure specification - Part 1: Arc welding

ISO 15609-2:2001 Specification and qualification of welding B9.18.4


procedures for metallic materials welding
procedure specification - Part 2: Gas welding

ISO 21940-14:2012 Mechanical Vibration Rotor Balancing Part 14: H1.7


Procedures for assessing balance errors

ISO/IEC 1989: 2014 Information technology -- Programming B5.1.2(i),


languages -- COBOL C5.3(h)

Annex I AC_GS
Page 16 of 19 2017 Edition
Part and
Standard Description
Clause No.
ISO/IEC 8802-3: Standard for Ethernet B5.1.2(j),
2014 C5.3(i), C5.5

ISO/IEC 9075-9: Information technology -- Database languages -- B5.1.2(a),


2008/Corr 1:2010 SQL -- Part 9: Management of External Data C5.3(b), C5.13
(SQL/MED)

ISO/IEC 9075-10: Information technology -- Database languages -- B5.1.2(a)


2008/Corr 1:2010 SQL -- Part 10: Object Language Bindings
(SQL/OLB)

ISO/IEC 9075-13: Information technology -- Database languages -- B5.1.2(a)


2008/Corr 1:2010 SQL -- Part 13: SQL Routines and Types Using
the Java TM Programming Language (SQL/JRT)

NAIMA Publication Cleaning Fibrous Glass Insulated Duct Systems - C2.6.2


AH-122 Recommended Practices

(NES) 713 (Issue 3) Determination of the Toxicity Index of the C11.2.4(h)


Products of Combustion from Small Specimens
of Material

NFPA-90A:2012 Standard for the Installation of Air-Conditioning B11.5.4,


and Ventilating Systems B11.6.4(d),
C2.6.2,
C2.11.1,
C3.17.1(d),
C3.18.3.(b),
D5.1.1(d)(viii)

NFPA-90B:2012 Standard for the Installation of Warm Air Heating C2.6.2


and Air-Conditioning Systems

NFPA 220:2012 Standard on Types of Building Construction B11.6.4(d)

NFPA 255:2006 Standard Method of Test of Surface Burning C8.7, C8.9


Characteristics of Building Materials

PD 5500: 2012 + A3: Specification for unfired fusion welded pressure B8.5.5,
2014 vessels. C6.28.4, C8.5.2

TIA/EIA 232-F Interface Between Data Terminal Equipment and B5.1.2(e), B5.3,
Data Circuit-Terminating Equipment Employing C5.3(d), C5.5
Serial Binary Data Interchange

TIA/EIA 485-A Electrical Characteristics of Generators and B5.1.2(f), B5.3,


(August 2008) Receivers for Use in Balanced Digital Multipoint C5.3, C5.5
Systems

Annex I AC_GS
Page 17 of 19 2017 Edition
Part and
Standard Description
Clause No.
TIA/EIA 568-C.1 Commercial Building Telecommunications B5.1.2(g),
(February 2009) Cabling Standard B5.3, C5.3(f)

UL 58:1996 Standard for Steel Underground Tanks for C6.5.2(g)


Flammable and Combustible Liquids

UL 153:2014 Standard for Portable Electric Luminaires C1.17

UL 181:2013 Factory-Made Air Ducts and Air Connectors C2.6.2,


C3.17.1(d),
C3.18.3(b)

UL 555S:2014 Smoke Dampers C2.11.2

UL 586:2009 High-Efficiency, Particulate, Air Filter Units C1.2.1(b),


C1.11, C1.13

UL 710:2012 Exhaust Hoods for Commercial Cooking C1.14


Equipment

UL 723:2008 Test for Surface Burning Characteristics of C8.7, C8.9


Building Materials

UL 867:2012 Electrostatic Air Cleaners C1.14, C1.16

UL 900:2004 Safety Air Filter Units C1.2.2(c)

UL 1283:2015 Standard for Electromagnetic Interference Filters C6.5.2(g)

UL 1598:2008 Luminaires C1.17

UL 1995:2011 Heating and Cooling Equipment C1.17

Annex I AC_GS
Page 18 of 19 2017 Edition
Part and
Year Title of Codes of Practice / Guideline
Clause No.
2005 Code of Practice on the Handling, Transportation and A2.1.2(o)
Disposal of Asbestos Waste
2005 Code of Practice on the Packaging, Labelling and A2.1.2(p)
Storage of Chemical Wastes
2008 Design Manual Barrier Free Access 2008 A2.1.2(i)
2012 Code of Practice for Energy Efficiency of Building A2.1.2(f),
Services Installation C5.55, C6.1,
C6.25, C11.5,
C12.19
2012 Codes of Practice for Minimum Fire Service A2.1.2(d)
Installations and Equipment and Inspection, Testing
and Maintenance of Installations and Equipment
2013 ASHRAE Fundamentals SI Handbook 2013 B8.1
2015 Code of Practice for the Electricity (Wiring) A2.1.2(c),
Regulations A3.12, C6.1,
H1.9
2016 Code of Practice for Fresh Water Cooling Towers A2.1.2(b), F1,
published by the EMSD I3.6.8(j),
I3.6.9(k)
2016 Code of Practice for Prevention of Legionnaires' A2.1.2(j), F1
Disease issued by Prevention of Legionnaires' Disease
Committee, the Government of HKSAR
2016 Fresh Water Cooling Towers Scheme (FWCT A2.1.2 (a)
Scheme) published by the EMSD.

Annex I AC_GS
Page 19 of 19 2017 Edition