CB100/CB400/CB500/CB700/CB900: 1. Product Check
CB100/CB400/CB500/CB700/CB900: 1. Product Check
CB100/CB400/CB500/CB700/CB900: 1. Product Check
1. PRODUCT CHECK
CB100/CB400/CB500/CB700/CB900
CB100
INSTRUCTION MANUAL CB400
IMCB34-E1
CB500 - - //Y
CB700 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)(11)
Thank you for purchasing this RKC product. In order to achieve maximum performance CB900
and ensure proper operation of your new instrument, carefully read all the instructions in
this manual. Please place the manual in a convenient location for easy reference. (1) Control action
F: PID action with autotuning (Reverse action)
D: PID action with autotuning (Direct action)
WARNING W: Heat/Cool PID action with autotuning (Water cooling) 1
To prevent injury to persons, damage to instrument and equipment, A: Heat/Cool PID action with autotuning (Air cooling) 1
a suitable external protection device shall be required. (2) Input type, (3) Range code: Refer to 9. INPUT RANGE TABLE.
All wiring must be completed before power is turned on to prevent (4) First control output [OUT1] (Heat-side)
electric shock, fire or damage to instrument and equipment. M: Relay contact T: Triac V: Voltage pulse
This instrument must be used in accordance with the specifications 8: Current (4 to 20 mA DC) G: Trigger for triac driving
to prevent fire or damage to instrument and equipment. (5) Second control output [OUT2] (Cool-side)
This instrument is not intended for use in locations subject to No symbol: When control action is F or D. M: Relay contact
flammable or explosive gases. T: Triac V: Voltage pulse 8: Current (4 to 20 mA DC)
Do not touch high-voltage connections such as power supply (6) Alarm 1 [ALM1], (7) Alarm 2 [ALM2]
terminals, etc. to avoid electric shock. N: No alarm H: Process high alarm
RKC is not responsible if this instrument is repaired, modified or A: Deviation high alarm J: Process low alarm
disassembled by other than factory-approved personnel. B: Deviation low alarm K: Process high alarm with hold action
Malfunction can occur and warranty is void under these conditions. C: Deviation high/low alarm L: Process low alarm with hold action
D: Band alarm P: Heater break alarm (HBA) [CTL-6] 2
E: Deviation high alarm S: Heater break alarm (HBA) [CTL-12] 2
CAUTION with hold action R: Control loop break alarm (LBA) 3
This product is intended for use with industrial machines, test and F: Deviation low alarm V: SV high alarm
measuring equipment. (It is not designed for use with medical equipment with hold action W: SV low alarm
and nuclear energy.) G: Deviation high/low alarm with hold action
This is a Class A instrument. In a domestic environment, this instrument (8) Communication function
may cause radio interference, in which case the user may be required to N: No communication function 5: RS-485 (2-wire system)
take additional measures. (9) Waterproof/Dustproof
This instrument is protected from electric shock by reinforced insulation. N: No Waterproof/Dustproof 1: Waterproof/Dustproof
Provide reinforced insulation between the wire for the input signal and
the wires for instrument power supply, source of power and loads. (10) Case color
Be sure to provide an appropriate surge control circuit respectively for N: White A: Black
the following: (11) Version symbol
- If input/output or signal lines within the building are longer than 30 meters. No code: For Japanese domestic market /Y: For International market
- If input/output or signal lines leave the building, regardless the length. 1
No self-tuning function is provided in the W or A control action type.
This instrument is designed for installation in an enclosed instrumentation 2
Heater break alarm (HBA) cannot be specified in case of ALM1. Also, it isnt
panel. All high-voltage connections such as power supply terminals must be possible to specify when control output is current output.
enclosed in the instrumentation panel to avoid electric shock by operating 3
As control loop break alarm (LBA), only either the ALM1 or ALM2 is selected.
personnel. Check that power supply voltage is also the same as that specified
All precautions described in this manual should be taken to avoid when ordering.
damage to the instrument or equipment. <Accessories>
All wiring must be in accordance with local codes and regulations. z Mounting frame (CB100): 1 (KCA100-526)
All wiring must be completed before power is turned on to prevent
z Mounting brackets (CB400/500/700/900): 2 *(KCA400-532)
electric shock, instrument failure, or incorrect action. The power must be
z Instruction manual (IMCB34-E1): 1
turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must * For CB900 waterproof/dustproof (optional): 4 pieces
be completed before power is turned on again.
To prevent instrument damage as a result of failure, protect the power line and
the input/output lines from high currents with a suitable overcurrent protection
device with adequate breaking capacity such as a fuse, circuit breaker, etc. 2. MOUNTING
Prevent metal fragments or lead wire scraps from falling inside
instrument case to avoid electric shock, fire or malfunction. 2.1 Mounting Cautions
Tighten each terminal screw to the specified torque found in the manual (1) This instrument is intended to be used under the following environmental
to avoid electric shock, fire or malfunction. conditions. (IEC61010-1)
For proper operation of this instrument, provide adequate ventilation for [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
heat dispensation.
(2) Use this instrument within the following environment conditions:
Do not connect wires to unused terminals as this will interfere with Allowable ambient temperature: 0 to 50 C
proper operation of the instrument. Allowable ambient humidity: 5 to 95 % RH
Turn off the power supply before cleaning the instrument. (Absolute humidity: MAX. W. C 29.3 g/m3 dry air at 101.3 kPa)
Do not use a volatile solvent such as paint thinner to clean the Installation environment conditions: Indoor use, Altitude up to 2000 m
instrument. Deformation or discoloration will occur. Use a soft, dry cloth (3) Avoid the following conditions when selecting the mounting location:
to remove stains from the instrument. Rapid changes in ambient temperature which may cause condensation.
To avoid damage to instrument display, do not rub with an abrasive Corrosive or inflammable gases.
material or push front panel with a hard object. Direct vibration or shock to the mainframe.
When high alarm with hold action is used for Alarm function, alarm does Water, oil, chemicals, vapor or steam splashes.
not turn on while hold action is in operation. Take measures to prevent Excessive dust, salt or iron particles.
overheating which may occur if the control device fails. Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
NOTICE Exposure to direct sunlight.
This manual assumes that the reader has a fundamental knowledge of Excessive heat accumulation.
the principles of electricity, process control, computer technology and (4) Mount this instrument in the panel considering the following conditions:
communications. Provide adequate ventilation space so that heat does not build up.
The figures, diagrams and numeric values used in this manual are only Do not mount this instrument directly above equipment that generates large
for purpose of illustration. amount of heat (heaters, transformers, semi-conductor functional devices,
RKC is not responsible for any damage or injury that is caused as a large-wattage resistors.)
result of using this instrument, instrument failure or indirect damage. If the ambient temperature rises above 50 C, cool this instrument with a forced air
RKC is not responsible for any damage and/or injury resulting from the fan, cooler, etc. Cooled air should not blow directly on this instrument.
use of instruments made by imitating this instrument. In order to improve safety and the immunity to withstand noise, mount this
Periodic maintenance is required for safe and proper operation of this instrument as far away as possible from high voltage equipment, power lines, and
instrument. Some components have a limited service life, or rotating machinery.
characteristics that change over time. High voltage equipment: Do not mount within the same panel.
Every effort has been made to ensure accuracy of all information Power lines: Separate at least 200 mm.
contained herein. RKC makes no warranty expressed or implied, with Rotating machinery: Separate as far as possible.
respect to the accuracy of the information. The information in this For correct functioning mount this instrument in a horizontal position.
manual is subject to change without prior notice. (5) In case this instrument is connected to a supply by means of a permanent
No portion of this document may be reprinted, modified, copied, transmitted, connection, a switch or circuit-breaker shall be included in the installation. This
digitized, stored, processed or retrieved through any mechanical, shall be in close proximity to the equipment and within easy reach of the
electronic, optical or other means without prior written approval from RKC. operator. It shall be marked as the disconnecting device for the equipment.
25
44.8
(Unit: mm)
1. Prepare the panel cutout as specified in 2.2 Dimensions.
+0.6
45 0
+0.6
2. Insert the instrument through the panel cutout.
25 45 0 25
48 9.2
3. Insert the mounting frame into the mounting from the rear of the instrument.
4. Push the mounting frame forward until the frame is firmly secured
25
to the panel. (Fig.1)
Close vertical mounting 5. Fix the instrument to the panel by using the two screws. (Fig.2)
61.6
44.8
48
L1 +0.6
0
Fig.1 Fig.2
When using the mounting
+0.6
screws, only turn one full
45 0
revolution after the screw
1 (*1) Mounting touches the panel.
8.2 100 L1=48n3 frame
n: Number of controllers (2 to 6)
Screw
Individual Mounting
CB400
25 45 +0.6
44.8
(Unit: mm)
The optional waterproof/dustproof on the front of the instrument conforms to
+0.8
IP66 when mounted on the panel. For effective waterproof/dustproof, the
0
48 9.2
92
gasket must be securely placed between instrument and panel without any
gap. If the gasket is damaged, please contact RKC sales office or the agent.
30
Fig.3
<Removal Procedures> c
1. Turn the power OFF.
91.8
107.4
L1+0.6
0
2. Remove the wiring. d
3. Loosen the screw of the mounting frame.
4. Remove the mounting frame from the case. (Fig.3)
+0.8
092
1 (*1)
c
L1=48n3
8.2 100
n: Number of controllers (2 to 6) CB400/500/700/900
9.2
<Mounting Procedures>
Individual Mounting
CB500 30 92 +0.8
0
1. Prepare the panel cutout as specified in 2.2 Dimensions.
2. Insert the instrument through the panel cutout.
(Unit: mm)
3. Insert the mounting bracket into the mounting groove of the instrument.
25 45 +0.6
0
107.4
91.8
firmly fixed.
48
(Unit: mm)
+0.7
0 68
72 9.2
30
Close vertical mounting When the instrument is mounted, always secure with two mounting brackets
67.8
83.4
72
+0.7
L1 0 so that upper and lower mounting brackets are positioned diagonally.
The optional waterproof/dustproof (CB900: mounting bracket 4 pieces)
+0.7
*2
(Unit: mm)
2. Remove the wiring.
+0.8
0
96 9.2
4. Hold the mounting bracket by the edge (c) and tilt it (d) to remove
from the case. (Fig. 3)
30
+0.8
L1 0 6. Pull out the instrument from the mounting cutout while holding the
front panel frame of this instrument. (Fig. 4)
+0.8
92 0
2 IMCB34-E1
3. WIRING
3.1 Wiring Cautions
For thermocouple input, use the appropriate compensation wire.
For RTD input, use low resistance lead wire with no difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from instrument power line, load lines and power lines of other electric equipment.
For the current input specification, an external resistor (250 0.02 %, 0.25 W or more, 10 ppm/C) must be connected between the input
terminals. For external resistor (shunt resistor), use the KD100-55: sold separately (RKC product). If this resistor is installed, close horizontal
mounting is not possible.
Signal connected to Voltage input and Current input shall be low voltage defined as SELV circuit per IEC 60950-1.
If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
- Shorten the distance between the twisted power supply wire pitches
to achieve the most effective noise reduction. Instrument power Twist these leadwires
- Always install the noise filter on a grounded panel. Minimize the wiring IN OUT Instrument
distance between the noise filter output and the instrument power Noise filter power
terminals
supply terminals to achieve the most effective noise reduction. Shorten distance between Minimize
- Do not connect fuses or switches to the noise filter output wiring as pitches distance
this will reduce the effectiveness of the noise filter.
Allow approximately 4 seconds for contact output when the instrument is turned on. Use a delay relay when the output line is used for an
external interlock circuit.
Power supply wiring must be twisted and have a low voltage drop.
This instrument with 24 V power supply is not provided with an overcurrent protection device.
For safety install an overcurrent protection device (such as fuse) with adequate breaking capacity close to the instrument.
- Fuse type: Time-lag fuse (Approved fuse according IEC60127-2 and/or UL248-14)
- Fuse rating: Rated current: 0.5 A
For an instrument with 24 V power supply input, supply power from "SELV" circuit defined as IEC 60950-1.
A suitable power supply should be considered in end-use equipment. The power supply must be in compliance with a limited-energy circuits
(maximum available current of 8 A).
Use the solderless terminal appropriate to the screw size. 5.5 MAX
- Screw size: M3 x 6
3.2 MIN
- Recommended tightening torque: 0.4 Nxm [4 kgfxcm]
- Specified solderless terminals: With isolation
2
- Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
Make sure that during field wiring parts of conductors can not come into contact with adjacent conductive parts. 4 mm
IMCB34-E1 3
Power supply Alarm output
CB700 AC L DC + AC L
1 1 1 1 10 10
NO
24V 24V 100 to 240V 2 11 Alarm 2 ALM2
N
2 2 2 3 12 11
Control output N NO
4 13 Alarm 1 ALM1
Triac Voltage pulse Relay contact 5 14 12
OUT2 Current OUT2 6 15 (Optional)
+ 3 3
3 7 16
Triac out OUT2 NO
Communication 8 17 CT input
4 4 4 9 18 Current
SG 7 transformer input
OUT1 OUT1
5 + 5 5 RS-485
14
Triac out OUT1 NO
T/R(A) 8
CT1
6 6 6
T/R(B) 9 15
W, A action types
(Optional) (Optional)
Trigger Triac Voltage pulse Relay contact Input
OUT1 Current
T2 4 4 4 RTD input TC input Current input Voltage input
OUT1 Triac out OUT1 16 A 0 to 20 mA DC 0 to 5 V DC
T1 5 5 + 5 5 4 to 20 mA DC 1 to 5 V DC
RTD
+ + +
OUT1 NO 17 B 17 17 17
External
6 NC IN
G
6 6 NO: Normally open TC
resistor
F, D action types NC: Normally closed 18 B 18 18 18
Specifications Performance:
Input: Display accuracy (at the ambient temperature 23 C 2 C):
Input type: Thermocouple:
Thermocouple: K, J, R, S, B, E, T, N, PLII, W5Re/W26Re, U, L (0.3 % of display value + 1 digit) or 2 C [4 F]
Input impedance: Approx. 1 M Whichever is greater
RTD: Pt100, JPt100 R, S and B input: 0 to 399 C [0 to 799 F]
Voltage: 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Z-1010) Accuracy is not guaranteed.
Current: 0 to 20 mA DC, 4 to 20 mA DC T and U input: 199.9 to 100.0 C [199.9 to 158.0 F]
Sampling cycle: 0.5 seconds Accuracy is not guaranteed.
Input range: Refer to Input range table RTD: (0.3 % of display value + 1 digit) or 0.8 C [1.6 F]
Control method: PID control Whichever is greater
ON/OFF, P, PI, or PD actions is available Voltage/Current:
(0.3 % of Input span + 1 digit)
Control output:
Memory backup:
Relay contact output:
250 V AC, 3A (Resistive load) Backed up by Nonvolatile Memory
Electrical life: 300,000 times or more (Rated load) Number of write times: Approx. 1,000,000 times
Voltage pulse output: Data storage period: Approx. 10 years
0/12 V DC (Load resistance 600 or more)
Current output: 4 to 20 mA DC (Load resistance 600 or less) Power:
Trigger output for triac driving: Power supply voltage:
Zero cross method for medium capacity triac 85 to 264 V AC (Power supply voltage range), 50/60 Hz
driving (100 A or less) Rating: 100 to 240 V AC
Load voltage used: 100 V AC line, 200 V AC line 21.6 to 26.4 V AC (Power supply voltage range), 50/60 Hz
Load used: Resistive load Rating: 24 V AC
Triac output: Output method:
21.6 to 26.4 V DC (Power supply voltage range)
AC output (Zero-cross method)
Allowable load current: Rating: 24 V DC
0.5 A (Ambient temperature: 40 C or less) Power consumption:
Load voltage: 75 to 250 V AC 7 VA max. (at 100 V AC) 10 VA max. (at 240 V AC)
Minimum load current: 20 mA 5 VA max. (at 24 V AC) 160 mA max. (at 24 V DC)
ON voltage:
1.6 V or less (at maximum load current) Weight:
CB100: Approx. 170 g CB700: Approx. 290 g
Alarm output:
CB400/CB500: Approx. 250 g CB900: Approx. 340 g
Relay contact output:
250 V AC, 1A (Resistive load)
Electrical life: 50,000 times or more (Rated load)
4 IMCB34-E1
4. PARTS DESCRIPTION
CB100 CB400 CB500 CB700, CB900
PV PV SV
(1) PV (1) (2)
PV
(1)
SV (2) (1)
AT OUT1 OUT2 ALM1 ALM2 (3)
AT OUT1 OUT2 ALM1 ALM2 (3) SV
SET R/S
SET R/S (2)
RKC CB100 RKC CB500 SV
(2)
AT OUT1 OUT2
(4) (5) (6) (7) (3) (4) (5) (6) (7)
ALM1 ALM2
AT OUT1 OUT2 ALM1 ALM2 (3)
SET R/S SET R/S
(1) Measured value (PV) display [Green] Control output lamps (OUT1, OUT2) [Green] (5) R / S (Shift & R/S key)
Displays PV or various parameter symbols. OUT1: Lights when control output is turned on.* Shift digits when settings are changed.
OUT2: Lights when cool-side control output is Select the RUN/STOP function.
(2) Set value (SV) display [Orange] turned on.*
Displays SV or various parameter set values (or * Lamp indication becomes as follows for (6) (DOWN key)
CT input value). current output. Decrease numerals.
For an output of less than 0 %: Extinguished
(3) Indication lamps For an output of more than 100 %: Lit (7) (UP key)
Alarm output lamps (ALM1, ALM2) [Red] For an output of more than 0 % but less than Increase numerals.
ALM1: Lights when alarm 1 output is turned on. 100 %: Dimly lit.
ALM2: Lights when alarm 2 output is turned on.
Autotuning (AT) lamp [Green] (4) SET (Set key) To avoid damage to the
Flashes when autotuning is activated. (After Used for parameter calling up and set value instrument, never use a
autotuning is completed: AT lamp will go out) registration. sharp object to press keys.
5. SETTING
5.1 Operation Menu
Power ON Parameter Setting Mode
This mode is used to set the parameters such as alarms, PID constants, etc. (Refer to page 6.)
Input type and Input range Display The following parameter symbols are displayed as the SET key is pressed.
Automatically (in 4 seconds) Current transformer Autotuning (AT) Heat-side proportioning
(CT) input value 1
PV/SV Display Mode (CT1) (ATU) (T) cycle
monitor
SET key SET key SET key
The controller will display the Measured
Press and hold Alarm 1 set value Self-tuning (ST) Cool-side proportioning
value (PV) and the Set value (SV).
the SET key (ALM1) band
The controller can be switched to RUN or (AL1) (STU) (Pc)
for 2 seconds.
STOP mode (Factory set value: RUN). SET key SET key SET key
(STOP mode) SET key. SET key SET key SET key
SV
Control loop break Derivative time PV bias
alarm (LBA) time
Press the SET key (LbA) (D) (Pb)
SET key SET key SET key
SV Setting Mode LBA deadband Anti-reset windup Set data lock
This is the mode used to set the SV. (Lbd) (Ar) (LCK)
SET key SET key SET key
PV
Return to the first parameter
SV SV setting
Factory set value: 0 C [F] or 0.0 C [F] Parameters which are not related to existing functions on the controller are not displayed.
IMCB34-E1 5
5.2 Parameter List
Parameter symbols which are not related to existing functions on the controller are not displayed.
Proportional TC/RTD inputs: Set when PI, PD or PID control is performed. TC/RTD inputs:
band 1 (0.1) to Heat/Cool PID action: Proportional band 30 (30.0)
Input span or 9999 (999.9) C [F] setting on the heat-side.
Voltage/Current inputs: Voltage/Current inputs:
ON/OFF action differential gap: 3.0
0.1 to 100.0 % of Input span
TC/RTD inputs: 2 (0.2) C [F ]
0 (0.0): ON/OFF action Voltage/Current inputs: 0.2 % of Input span
Integral time 1 to 3600 seconds Set the time of integral action to eliminate 240
(0 second: PD action) the offset occurring in proportional control.
Derivative time 1 to 3600 seconds Set the time of derivative action to improve 60
(0 second: PI action) control stability by preparing for output
changes.
Anti-reset 1 to 100 % of heat-side proportional Overshooting and undershooting are 100
windup (ARW) band restricted by the integral effect.
(0 %: Integral action OFF)
Heat-side 1 to 100 seconds Set control output cycle. Relay contact output: 20
proportioning (Not displayed if the control output is Heat/Cool PID action: Voltage pulse output/
cycle current output.) Heat-side proportioning cycle Trigger output for triac
driving/Triac output: 2
Cool-side 1 to 1000 % of heat-side proportional Set cool-side proportional band when 100
proportional band. Heat/Cool PID action.
band
Deadband TC/RTD inputs: Set control action deadband between 0 or 0.0
10 to +10 C [F] or heat-side and cool-side proportional bands.
10.0 to +10.0 C [F] Minus () setting results in overlap.
Voltage/Current inputs:
10.0 to +10.0 % of Input span
Cool-side 1 to 100 seconds Set control cool-side output cycle for Relay contact output: 20
proportioning (Not displayed if the control output is Heat/Cool PID action. Voltage pulse output/
cycle current output.) Triac output: 2
PV bias TC/RTD inputs: Sensor correction is made by adding bias 0 or 0.0
1999 to +9999 C [F] or value to Measured value (PV).
199.9 to +999.9 C [F]
Voltage/Current inputs:
Input span to +Input span
Set data lock Performs set data change enable/disable. 0000
(LCK) Parameters other than SV and Alarms
0: Unlock 1: Lock
Alarms
0: Unlock 1: Lock
SV
0: Unlock 1: Lock
Initialization mode
0: Lock 1: Unlock
6 IMCB34-E1
1
Heater break alarm (HBA) function 5.3 Changing Parameter Settings
The HBA function monitors the current flowing through the load
by a dedicated Current transformer (CT), compares the measured Procedures to change parameter settings are shown below.
value with the HBA set value, and detects a fault in the heating
circuit. To store a new value for the parameter, always press the SET
Low or No current flow (Heater break, malfunction of the key. The display changes to the next parameter and the new
control device, etc.): value will be stored.
When the control output is ON and the current transformer input A new value will not be stored without pressing SET key after
value is equal to or less than the heater break determination point the new value is displayed on the display.
for the preset number of consecutive sampling cycle, an alarm is After a new value has been displayed by using the UP and
activated. DOWN keys, the SET key must be pressed within 1 minute, or
Over current or short-circuit: the new value is not stored and the display will return to the
When the control output is OFF and the current transformer input PV/SV monitor screen.
value is equal to or greater than the heater break determination
point for the preset number of consecutive sampling cycle, an
alarm is activated.
z Change the Set value (SV)
Precaution for HBA setting: Change the Set value (SV) from 0 C to 200 C
Displayed only for when HBA is selected as Alarm 2. 1. Select the SV setting mode
HBA is not available on a current output. Press the SET key at PV/SV monitor screen until SV setting
Set the set value to approximately 85 % of the maximum screen is displayed.
reading of the CT input.
Set the set value to a slightly smaller value to prevent a false
alarm if the power supply may become unstable. PV PV
CB100
R/S SET
CB100
R/S
value (PV) for the length of LBA time. When the LBA time has
elapsed and the PV is still within the alarm determination range, SV SV
the LBA will be ON. AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2
CB100
R/S SET
CB100
R/S
When the Measured value (PV) is within the LBD area, LBA will AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2
not be activated. If the LBD setting is not correct, the LBA will not SET R/S SET R/S
IMCB34-E1 7
6. OPERATIONS
CAUTIONS
z All mounting and wiring must be completed before the power is turned on. If the input signal wiring is disconnected or
short-circuited (RTD input only), the instrument determines that burnout has occurred.
Displays:
Upscale: Thermocouple input, RTD input (when input break)
Downscale Thermocouple input (specify when ordering), RTD input (when short-circuited), Voltage input (1 to 5 V DC),
Current input (4 to 20 mA DC)
For the voltage (0 to 5 V DC, 0 to 10 V DC*) or current (0 to 20 mA DC) input, the display becomes indefinite (display of about
zero value).
* Z-1010 specification
Outputs:
Control output: OFF (Heat/Cool control: the control output on both heat-side and cool-side is turned off)
Alarm output: Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when burnout occurs regardless of any of
the following actions taken (High alarm, low alarm, etc.). In addition, when used for any purposes other than these
alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).
z A power failure of 20 ms or less will not affect the control action. When a power failure of more than 20 ms occurs, the
instrument assumes that the power has been turned off. When power returns, the controller will retain the conditions that
existed prior to shut down.
z The alarm hold action is activated when not only the power is turned on, but also the SV is changed.
! WARNING
Parameters in the Initialization mode should be set according to the application before setting any parameter
related to operation. Once the Parameters in the Initialization mode are set correctly, no further changes need to
be made to parameters for the same application under normal conditions. If they are changed unnecessarily, it
may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or
failure as a result of improper changes in the Initialization mode.
CB100 PV
SET R/S
CB100
PV
CB100
R/S
unlocked locked.
PV
6. Press the SET key to store the new set value. The display
SV
goes to the next parameter, and the Initialization mode is
The parameter displayed
unlocked. AT OUT1 OUT2 ALM1 ALM2
varies on the instrument
SET R/S
PV CB100 specification.
CT1 input value display
SV
SET R/S SET R/S Input type selection Setting limiter high
CB100 CB100
(SL1) (SLH)
CT1 input value display Initialize code selection display
Temperature unit and Setting limiter low
of initialization mode
cooling type selection
(SL2) (SLL)
Cod SL1 (Input type selection) Refer to P. 10 Alarm1 type selection Decimal point
(SL4)
position
0000 SL2 (Temperature unit and cooling type selection) Refer to P. 10 (PGdP)
Alarm2 type selection
SL4 (Alarm 1 type selection) Refer to P. 10
(SL5)
SL5 (Alarm 2 type selection) Refer to P. 10 SV alarm type selection To PV/SV
SL11 (SV alarm type selection) Refer to P. 11 display mode
(SL11)
IMCB34-E1 9
7.4 Input Type Selection (SL1) 7.6 Alarm 1 [ALM1] Type Selection (SL4)
When any parameter setting is changed in the Initialization Alarm 2 [ALM2] Type Selection (SL5)
mode, check all parameter set values in SV setting mode If the alarm function is not provided with the instrument when
and Parameter setting mode. shipped from the factory, no alarm output is available by changing
Factory set value varies depending on the input type. SL4 and/or SL5.
Set value Input type SL4 is set to 0000 in the following cases.
0000 K When the instrument does not have ALM1 output
0001 J When Control loop break alarm (LBA) is provided and
0010 L assigned to ALM1
0011 E When the SV alarm is provided and assigned to ALM1
0100 N
0111 R Thermocouple 1 SL5 is set to 0000 in the following cases.
1000 S (TC) When the instrument does not have ALM2 output
1001 B4 When Control loop break alarm (LBA) is provided and
1010 W5Re/W26Re 4 assigned to ALM2
1011 PL II When the SV alarm is provided and assigned to ALM2
0101 T When the Heater break alarm (HBA) is provided
0110 U When the instrument has Z-168 specification
1100 Pt100 (JIS/IEC)
RTD 1 Factory set value varies depending on the instrument specification.
1101 JPt100 (JIS)
1110 0 to 5 V DC Set value Details of setting
1110 0 to 10 V DC 2 Voltage 1 0000 No alarm
1111 1 to 5 V DC 0001 Deviation high alarm
1110 0 to 20 mA DC
Current 1, 3 0101 Deviation low alarm
1111 4 to 20 mA DC
1
0010 Deviation high/low alarm
Any input change in TC&RTD group is possible. Any input change in
0110 Band alarm
Voltage & Current group except for 0 to 10 V DC input is possible. No input
change between TC&RTD group and Voltage & Current group is possible. 0011 Process high alarm
2
The input type of Z-1010 specification is fixed to 0 to 10 V DC due to the 0111 Process low alarm
hardware difference. 1001 Deviation high alarm with hold action *
3
For the current input specification, a resistor of 250 must be connected 1101 Deviation low alarm with hold action *
between the input terminals.
4 1010 Deviation high/low alarm with hold action *
W5Re/W26Re and B are not available with Z-1021 specification (Modbus
communication). 1011 Process high alarm with hold action *
1111 Process low alarm with hold action *
Change Settings * Hold action:
Example: Change the input type from K to J When Hold action is ON, the alarm action is suppressed at start-up or the
control set value change until the measured value enters the non-alarm range.
1. Set Cod to 0000, and press the SET key. The display will
go to SL1. z Alarm action type
PV PV
Both of the Alarm 1 and Alarm 2 outputs of this instrument are
turned on when burnout occurs regardless of any of the following
SV SV
actions taken (high alarm, low alarm, etc.). In addition, when used
Initialize code selection display Input type selection
for any purposes other than these alarms (event, etc.), specify the
Z-124 specification (not to be forcibly turned on).
2. Press the UP key to change the number to 1.
PV
Deviation high alarm ( : SV : Alarm set value : Alarm differential gap)
*(Alarm set value is greater than 0.)
OFF ON
SV PV
Low High
*(Alarm set value is less than 0.)
OFF ON
3. Press the SET key to store the new set value. The display Low High
PV
goes to the next parameter. Deviation low alarm
*(Alarm set value is greater than 0.)
ON OFF
PV
7.5 Temperature Unit and Cooling Type Low
*(Alarm set value is less than 0.)
High
Factory set value varies depending on the instrument specification. Band alarm
OFF ON OFF
Description Low High
PV
Set
Temperature Process high alarm
value unit Cooling type selection
OFF ON
PV
0000 C Air cooling (A type) or Heat only type (F, D type) Low High
Process low alarm
0001 F Air cooling (A type) or Heat only type (F, D type)
ON OFF
0010 C Water cooling (W type) Low High
PV
SV SV
SV SV
3. Press the SET key to store the new set value. The display
4. Press the SET key to store the new set value. The display
goes to the next parameter.
goes to the next parameter.
10 IMCB34-E1
7.7 SV Alarm Type Selection (SL11) Factory set value varies depending on the instrument specification.
For ALM1 setting, the first digit from the right is set to 0 Setting range
in the following cases. Input type Setting limiter Setting limiter
When the instrument does not have ALM1 output. high low
When the ALM1 output is used for Process/Deviation/ U SLL to 600.0 C 199.9 to SLH C
Band alarm or Control loop break alarm (LBA). TC SLL to 999.9 F 199.9 to SLH F
L SLL to 800 C 0 to SLH C
For ALM2 setting, the third digit from the right is set to 0
SLL to 1600 F 0 to SLH F
in the following cases.
RTD Pt100 SLL to 649.0 C 199.9 to SLH C
When the instrument does not have ALM2 output.
JPt100 SLL to 999.9 F 199.9 to SLH F
When the ALM1 output is used for Process/Deviation/
Voltage 0 to 5 V DC
Band alarm, Heater break alarm (HBA) or Control loop
0 to 10 V DC * SLL to 9999 1999 to SLH
break alarm (LBA).
1 to 5 V DC (Programmable (Programmable
When Z-168 is specified.
Current 0 to 20 mA DC range) range)
To make SV alarm setting effective, set SL4 to 0000 4 to 20 mA DC
when using ALM1 for SV alarm, or set SL5 to 0000 when * Z-1010 specification
using ALM2 for SV alarm. SL4 and SL5 have priority to
SL11 setting. Change Settings
Factory set value varies depending on the instrument specification. Example: When the display range is scaled to 0.0 to 400.0 for
Alarm Details of setting a voltage input of 1 to 5 V DC.
0 SV alarm not provided 1V 5V
Alarm 1 1 SV alarm provided
[ALM1] 0 SV high alarm Factory set value 0.0 100.0
Scaling 0.0 400.0
1 SV low alarm
0 SV alarm not provided 1. Set Cod to 0001, and press the SET key. The display will go
Alarm 2 1 SV alarm provided to SLH.
[ALM2] 0 SV high alarm PV PV
1 SV low alarm
SV SV
z SV alarm action type
( : Alarm set value : Alarm differential gap) Initialize code selection display Setting limiter [high] display
SV high alarm
OFF ON 2. The high-lighted digit indicates which digit can be set. Press
SV
Low High
SV low alarm
<R/S key to high-light the first digit from the left.
PV
ON OFF
SV
Low High
SV
Change Settings
Example: Change the SV alarm type of the ALM1 from SV high 3. Press the UP key to change the number to 4.
alarm (0001) to SV low alarm (0011) PV
1. Press the SET key ten times at SL1 until SL11 is displayed. SV
2. Press the <R/S key to high-light the tens digit. Next, press
the UP key to change the number to 1.
PV PV
4. Press the SET key to store the new set value. The display
goes to SLL.
SV SV 5. Set SLL to 0.0.
High-light 6. Press the SET key to store the new set value. The display
3. Press the SET key to store the new set value. The display goes to the next parameter.
goes to the initialize code parameter.
IMCB34-E1 11
8. ERROR DISPLAYS
Error display
RAM failure (Incorrect set data write, etc.) Turn off the power at once. If an error occurs
after the power is turned on again, please
contact RKC sales office or the agent.
! WARNING
z To prevent electric shock or instrument failure, only qualified personnel should be allowed to pull out the
internal assembly.
z To prevent electric shock or instrument failure, always turn off the power before pulling out the internal assembly.
z To prevent injury or instrument failure, do not touch the internal printed wiring board.
Lock (upper) Apply pressure very carefully when removing internal assembly
to avoid damage to the frame.
To conform to IEC61010-1 requirements for protection from electric
shock, the internal assembly of this instrument can only be removed
with an appropriate tool.
Recommended tool: Unlocking points (marked with {) depend on the model as follows:
Slotted screwdriver CB400 CB100 CB900
(Tip width: CB500
CB700
6 mm or less)
Lock (lower)
Unlock using such a slotted screwdriver.
Gently press down on handle for the upper lock and
lift up for the lower lock.
The first edition: JAN. 2012 [IMQ00]