Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

CB100/CB400/CB500/CB700/CB900: 1. Product Check

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Digital Controller

1. PRODUCT CHECK
CB100/CB400/CB500/CB700/CB900
CB100
INSTRUCTION MANUAL CB400
IMCB34-E1
CB500 - - //Y
CB700 (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)(11)
Thank you for purchasing this RKC product. In order to achieve maximum performance CB900
and ensure proper operation of your new instrument, carefully read all the instructions in
this manual. Please place the manual in a convenient location for easy reference. (1) Control action
F: PID action with autotuning (Reverse action)
D: PID action with autotuning (Direct action)
WARNING W: Heat/Cool PID action with autotuning (Water cooling) 1
To prevent injury to persons, damage to instrument and equipment, A: Heat/Cool PID action with autotuning (Air cooling) 1
a suitable external protection device shall be required. (2) Input type, (3) Range code: Refer to 9. INPUT RANGE TABLE.
All wiring must be completed before power is turned on to prevent (4) First control output [OUT1] (Heat-side)
electric shock, fire or damage to instrument and equipment. M: Relay contact T: Triac V: Voltage pulse
This instrument must be used in accordance with the specifications 8: Current (4 to 20 mA DC) G: Trigger for triac driving
to prevent fire or damage to instrument and equipment. (5) Second control output [OUT2] (Cool-side)
This instrument is not intended for use in locations subject to No symbol: When control action is F or D. M: Relay contact
flammable or explosive gases. T: Triac V: Voltage pulse 8: Current (4 to 20 mA DC)
Do not touch high-voltage connections such as power supply (6) Alarm 1 [ALM1], (7) Alarm 2 [ALM2]
terminals, etc. to avoid electric shock. N: No alarm H: Process high alarm
RKC is not responsible if this instrument is repaired, modified or A: Deviation high alarm J: Process low alarm
disassembled by other than factory-approved personnel. B: Deviation low alarm K: Process high alarm with hold action
Malfunction can occur and warranty is void under these conditions. C: Deviation high/low alarm L: Process low alarm with hold action
D: Band alarm P: Heater break alarm (HBA) [CTL-6] 2
E: Deviation high alarm S: Heater break alarm (HBA) [CTL-12] 2
CAUTION with hold action R: Control loop break alarm (LBA) 3
This product is intended for use with industrial machines, test and F: Deviation low alarm V: SV high alarm
measuring equipment. (It is not designed for use with medical equipment with hold action W: SV low alarm
and nuclear energy.) G: Deviation high/low alarm with hold action
This is a Class A instrument. In a domestic environment, this instrument (8) Communication function
may cause radio interference, in which case the user may be required to N: No communication function 5: RS-485 (2-wire system)
take additional measures. (9) Waterproof/Dustproof
This instrument is protected from electric shock by reinforced insulation. N: No Waterproof/Dustproof 1: Waterproof/Dustproof
Provide reinforced insulation between the wire for the input signal and
the wires for instrument power supply, source of power and loads. (10) Case color
Be sure to provide an appropriate surge control circuit respectively for N: White A: Black
the following: (11) Version symbol
- If input/output or signal lines within the building are longer than 30 meters. No code: For Japanese domestic market /Y: For International market
- If input/output or signal lines leave the building, regardless the length. 1
No self-tuning function is provided in the W or A control action type.
This instrument is designed for installation in an enclosed instrumentation 2
Heater break alarm (HBA) cannot be specified in case of ALM1. Also, it isnt
panel. All high-voltage connections such as power supply terminals must be possible to specify when control output is current output.
enclosed in the instrumentation panel to avoid electric shock by operating 3
As control loop break alarm (LBA), only either the ALM1 or ALM2 is selected.
personnel. Check that power supply voltage is also the same as that specified
All precautions described in this manual should be taken to avoid when ordering.
damage to the instrument or equipment. <Accessories>
All wiring must be in accordance with local codes and regulations. z Mounting frame (CB100): 1 (KCA100-526)
All wiring must be completed before power is turned on to prevent
z Mounting brackets (CB400/500/700/900): 2 *(KCA400-532)
electric shock, instrument failure, or incorrect action. The power must be
z Instruction manual (IMCB34-E1): 1
turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must * For CB900 waterproof/dustproof (optional): 4 pieces
be completed before power is turned on again.
To prevent instrument damage as a result of failure, protect the power line and
the input/output lines from high currents with a suitable overcurrent protection
device with adequate breaking capacity such as a fuse, circuit breaker, etc. 2. MOUNTING
Prevent metal fragments or lead wire scraps from falling inside
instrument case to avoid electric shock, fire or malfunction. 2.1 Mounting Cautions
Tighten each terminal screw to the specified torque found in the manual (1) This instrument is intended to be used under the following environmental
to avoid electric shock, fire or malfunction. conditions. (IEC61010-1)
For proper operation of this instrument, provide adequate ventilation for [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
heat dispensation.
(2) Use this instrument within the following environment conditions:
Do not connect wires to unused terminals as this will interfere with Allowable ambient temperature: 0 to 50 C
proper operation of the instrument. Allowable ambient humidity: 5 to 95 % RH
Turn off the power supply before cleaning the instrument. (Absolute humidity: MAX. W. C 29.3 g/m3 dry air at 101.3 kPa)
Do not use a volatile solvent such as paint thinner to clean the Installation environment conditions: Indoor use, Altitude up to 2000 m
instrument. Deformation or discoloration will occur. Use a soft, dry cloth (3) Avoid the following conditions when selecting the mounting location:
to remove stains from the instrument. Rapid changes in ambient temperature which may cause condensation.
To avoid damage to instrument display, do not rub with an abrasive Corrosive or inflammable gases.
material or push front panel with a hard object. Direct vibration or shock to the mainframe.
When high alarm with hold action is used for Alarm function, alarm does Water, oil, chemicals, vapor or steam splashes.
not turn on while hold action is in operation. Take measures to prevent Excessive dust, salt or iron particles.
overheating which may occur if the control device fails. Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
NOTICE Exposure to direct sunlight.
This manual assumes that the reader has a fundamental knowledge of Excessive heat accumulation.
the principles of electricity, process control, computer technology and (4) Mount this instrument in the panel considering the following conditions:
communications. Provide adequate ventilation space so that heat does not build up.
The figures, diagrams and numeric values used in this manual are only Do not mount this instrument directly above equipment that generates large
for purpose of illustration. amount of heat (heaters, transformers, semi-conductor functional devices,
RKC is not responsible for any damage or injury that is caused as a large-wattage resistors.)
result of using this instrument, instrument failure or indirect damage. If the ambient temperature rises above 50 C, cool this instrument with a forced air
RKC is not responsible for any damage and/or injury resulting from the fan, cooler, etc. Cooled air should not blow directly on this instrument.
use of instruments made by imitating this instrument. In order to improve safety and the immunity to withstand noise, mount this
Periodic maintenance is required for safe and proper operation of this instrument as far away as possible from high voltage equipment, power lines, and
instrument. Some components have a limited service life, or rotating machinery.
characteristics that change over time. High voltage equipment: Do not mount within the same panel.
Every effort has been made to ensure accuracy of all information Power lines: Separate at least 200 mm.
contained herein. RKC makes no warranty expressed or implied, with Rotating machinery: Separate as far as possible.
respect to the accuracy of the information. The information in this For correct functioning mount this instrument in a horizontal position.
manual is subject to change without prior notice. (5) In case this instrument is connected to a supply by means of a permanent
No portion of this document may be reprinted, modified, copied, transmitted, connection, a switch or circuit-breaker shall be included in the installation. This
digitized, stored, processed or retrieved through any mechanical, shall be in close proximity to the equipment and within easy reach of the
electronic, optical or other means without prior written approval from RKC. operator. It shall be marked as the disconnecting device for the equipment.

All Rights Reserved, Copyright 2012, RKC INSTRUMENT INC.


RKC INSTRUMENT INC.
2.2 Dimensions 2.3 Mounting Procedures
CB100 Individual Mounting CB100
<Mounting Procedures>

25
44.8
(Unit: mm)
1. Prepare the panel cutout as specified in 2.2 Dimensions.

+0.6
45 0
+0.6
2. Insert the instrument through the panel cutout.
25 45 0 25
48 9.2
3. Insert the mounting frame into the mounting from the rear of the instrument.
4. Push the mounting frame forward until the frame is firmly secured

25
to the panel. (Fig.1)
Close vertical mounting 5. Fix the instrument to the panel by using the two screws. (Fig.2)

61.6
44.8
48

L1 +0.6
0
Fig.1 Fig.2
When using the mounting

+0.6
screws, only turn one full

45 0
revolution after the screw
1 (*1) Mounting touches the panel.
8.2 100 L1=48n3 frame
n: Number of controllers (2 to 6)
Screw
Individual Mounting
CB400
25 45 +0.6
44.8

(Unit: mm)
The optional waterproof/dustproof on the front of the instrument conforms to

+0.8
IP66 when mounted on the panel. For effective waterproof/dustproof, the

0
48 9.2

92
gasket must be securely placed between instrument and panel without any
gap. If the gasket is damaged, please contact RKC sales office or the agent.

30
Fig.3
<Removal Procedures> c
1. Turn the power OFF.
91.8
107.4

Close vertical mounting


96

L1+0.6
0
2. Remove the wiring. d
3. Loosen the screw of the mounting frame.
4. Remove the mounting frame from the case. (Fig.3)
+0.8
092

1 (*1)
c
L1=48n3
8.2 100
n: Number of controllers (2 to 6) CB400/500/700/900
9.2
<Mounting Procedures>
Individual Mounting
CB500 30 92 +0.8
0
1. Prepare the panel cutout as specified in 2.2 Dimensions.
2. Insert the instrument through the panel cutout.
(Unit: mm)
3. Insert the mounting bracket into the mounting groove of the instrument.
25 45 +0.6
0
107.4
91.8

Do not push the mounting bracket forward. (Fig. 1)


4. Secure the bracket to the instrument by tightening the screw. Take
care to refrain from moving the bracket forward.
Close vertical mounting 5. Only turn about one full revolution after the screw touches the panel.
1(*1)
100 92 +0.8
0 (Fig. 2)
8.2
96
If the screw has been rotated too tight, the screw may turn idle. In such
a case, loosen the screw once and tighten it again until the instrument is
L1 +0.6
0

firmly fixed.
48

6. The other mounting bracket should be installed in the same way as


L1=48n3 described in 3. to 5.
n: Number of controllers (2 to 6)
Fig.1 Fig.2
Individual Mounting
CB700 +0.7
25 68 0
67.8

(Unit: mm)
+0.7
0 68

72 9.2
30

Close vertical mounting When the instrument is mounted, always secure with two mounting brackets
67.8
83.4
72

+0.7
L1 0 so that upper and lower mounting brackets are positioned diagonally.
The optional waterproof/dustproof (CB900: mounting bracket 4 pieces)
+0.7

on the front of the instrument conforms to IP65 when mounted on the


68 0

panel. For effective waterproof/dustproof, the gasket must be securely


1 (*1)
8.2 100 L1=72n4 placed between instrument and panel without any gap. If gasket is
n: Number of controllers (2 to 6) damaged, please contact RKC sales office or the agent.
Individual Mounting
CB900 25
+0.8 <Removal Procedures>
92 0
1. Turn the power OFF.
91.8

*2
(Unit: mm)
2. Remove the wiring.
+0.8
0

3. Loosen the screw of the mounting bracket.


92

96 9.2
4. Hold the mounting bracket by the edge (c) and tilt it (d) to remove
from the case. (Fig. 3)
30

5. The other mounting bracket should be removed in the same way as


107.4
91.8

Close vertical mounting described in 3. and 4.


96

+0.8
L1 0 6. Pull out the instrument from the mounting cutout while holding the
front panel frame of this instrument. (Fig. 4)
+0.8
92 0

1 (*1) Fig. 3 Panel Fig. 4


8.2 100 L1=96n4
n: Number of controllers (2 to 6)
Pull out
d
*1 Rubber (optional)
c
*2 Up to four mounting brackets can be used.
z For mounting of the instrument, panel thickness must be between 1 to 10 mm.
(When mounting multiple instruments close together, the panel strength should be
checked to ensure proper support.) Front panel
z Waterproof and Dustproof are not effective when instruments are closely spaced. frame

2 IMCB34-E1
3. WIRING
3.1 Wiring Cautions
For thermocouple input, use the appropriate compensation wire.
For RTD input, use low resistance lead wire with no difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from instrument power line, load lines and power lines of other electric equipment.
For the current input specification, an external resistor (250 0.02 %, 0.25 W or more, 10 ppm/C) must be connected between the input
terminals. For external resistor (shunt resistor), use the KD100-55: sold separately (RKC product). If this resistor is installed, close horizontal
mounting is not possible.
Signal connected to Voltage input and Current input shall be low voltage defined as SELV circuit per IEC 60950-1.
If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
- Shorten the distance between the twisted power supply wire pitches
to achieve the most effective noise reduction. Instrument power Twist these leadwires
- Always install the noise filter on a grounded panel. Minimize the wiring IN OUT Instrument
distance between the noise filter output and the instrument power Noise filter power
terminals
supply terminals to achieve the most effective noise reduction. Shorten distance between Minimize
- Do not connect fuses or switches to the noise filter output wiring as pitches distance
this will reduce the effectiveness of the noise filter.
Allow approximately 4 seconds for contact output when the instrument is turned on. Use a delay relay when the output line is used for an
external interlock circuit.
Power supply wiring must be twisted and have a low voltage drop.
This instrument with 24 V power supply is not provided with an overcurrent protection device.
For safety install an overcurrent protection device (such as fuse) with adequate breaking capacity close to the instrument.
- Fuse type: Time-lag fuse (Approved fuse according IEC60127-2 and/or UL248-14)
- Fuse rating: Rated current: 0.5 A
For an instrument with 24 V power supply input, supply power from "SELV" circuit defined as IEC 60950-1.
A suitable power supply should be considered in end-use equipment. The power supply must be in compliance with a limited-energy circuits
(maximum available current of 8 A).
Use the solderless terminal appropriate to the screw size. 5.5 MAX
- Screw size: M3 x 6
3.2 MIN
- Recommended tightening torque: 0.4 Nxm [4 kgfxcm]
- Specified solderless terminals: With isolation
2
- Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
Make sure that during field wiring parts of conductors can not come into contact with adjacent conductive parts. 4 mm

3.2 Terminal Configuration


Power supply Alarm output
CB100 AC L DC + 1 AC L
1 13 7
7
1 1 2 14 8 NO
24V 24V 100 to 240V 3 15 9 Alarm 2 ALM2
2 8
N 2 N
2 4 16 10
NO
5 17 11 Alarm 1 ALM1
Control output 6 18 12 9
NO: Normally open Voltage pulse Relay contact
Triac (Optional)
NC: Normally closed Current
OUT2
+
OUT2 Input
3 3 3
Trigger Triac Voltage pulse Relay contact Communication CT input RTD input TC input
Triac out OUT2 NO
OUT1 Current 10 A
T2 4 4 4 4 4 4 SG 13 Current
transformer input RTD
OUT1 Triac out OUT1 OUT1 OUT1 RS-485 +
+ + 17 11 B 11
T1 5 5 5 5 5 5 5 T/R(A) 14 TC
OUT1 NO Triac out OUT1 NO CT1
12 B 12
G 6 6
NC 6 6 6 6 T/R(B) 15 18
Current input Voltage input
F, D action types W, A action types (Optional) (Optional)
0 to 20 mA DC 0 to 5 V DC
4 to 20 mA DC 1 to 5 V DC
* Cautions for Communication terminal wiring ! : + +
Make sure that lugs or unshielded cables of the communication terminals are not touched to the screw heads, lugs, or unshielded 11 11
External
cables of the power supply terminals to prevent electric shock or instrument failure. Use additional care when two lugs are resistor
IN

screwed to one communication terminal. 12 12


It is recommended that the host computer communication line be isolated from the power supply and earth.

Power supply Communication


CB400 AC L
1
DC +
1
AC L
1 1 13 SG 13
24V 24V 100 to 240V 2 14
RS-485
2 2 2 3 15
N N T/R(A) 14
4 16
Control output 5 17 T/R(B) 15
NO: Normally open Voltage pulse Relay contact 6 18
Triac
NC: Normally closed
OUT2 Current OUT2
Alarm output 7 19
(Optional)
+ 3 7 8 20 CT input
3 3 NO
Trigger Triac Voltage pulse Relay contact Triac out OUT2 NO ALM2 9 21
Alarm 2 Current
OUT1 Current transformer input
T2 4 4 4 4 4 4 8 10 22
NO
OUT1 Triac out OUT1 Alarm 1 ALM1 11 23 23
OUT1 OUT1
T1 5 5 + 5 5 5 + 5 5 9 12 24 CT1
OUT1 NO Triac out OUT1 NO (Optional) 24
6 NC
6 6 6 6 6
G
(Optional)
F, D action types W, A action types
Input
RTD input TC input Current input Voltage input
The terminal arrangement of CB500 is as shown in 13 14 15 16 17 18 19 20 21 22 23 24
10 A 0 to 20 mA DC 0 to 5 V DC
the following diagram, but the terminal configuration 4 to 20 mA DC 1 to 5 V DC
RTD
of CB500 is the same as that of CB400. + + +
11 B 11 11 11
1 2 3 4 5 6 7 8 9 10 11 12 External
TC IN
resistor
12 B 12 12 12

IMCB34-E1 3
Power supply Alarm output
CB700 AC L DC + AC L
1 1 1 1 10 10
NO
24V 24V 100 to 240V 2 11 Alarm 2 ALM2

N
2 2 2 3 12 11
Control output N NO
4 13 Alarm 1 ALM1
Triac Voltage pulse Relay contact 5 14 12
OUT2 Current OUT2 6 15 (Optional)
+ 3 3
3 7 16
Triac out OUT2 NO
Communication 8 17 CT input
4 4 4 9 18 Current
SG 7 transformer input
OUT1 OUT1
5 + 5 5 RS-485
14
Triac out OUT1 NO
T/R(A) 8
CT1
6 6 6
T/R(B) 9 15
W, A action types
(Optional) (Optional)
Trigger Triac Voltage pulse Relay contact Input
OUT1 Current
T2 4 4 4 RTD input TC input Current input Voltage input
OUT1 Triac out OUT1 16 A 0 to 20 mA DC 0 to 5 V DC
T1 5 5 + 5 5 4 to 20 mA DC 1 to 5 V DC
RTD
+ + +
OUT1 NO 17 B 17 17 17
External
6 NC IN
G
6 6 NO: Normally open TC
resistor
F, D action types NC: Normally closed 18 B 18 18 18

Power supply Communication


CB900 AC L DC + AC L
1 1 1 SG 13
1 13
24V 24V 100 to 240V 2 14 RS-485
2 2 2 T/R(A) 14
Control output N N 3 15
4 16
Triac Voltage pulse Relay contact T/R(B) 15
5 17
OUT2 Current OUT2
+ 6 18 (Optional)
3 3 3 Alarm output 7 19
Triac out OUT2 NO 8 20
7
4 4 4 NO 9 21
Alarm 2 ALM2
OUT1 OUT1 10 22
+ 8
5 5 5 Alarm 1
NO 11 23 CT input
ALM1
Triac out OUT1 NO 12 24
9 Current
6 6 6 transformer input
(Optional) NO: Normally open
W, A action types 23
NC: Normally closed
Trigger CT1
Triac Voltage pulse Relay contact Input
OUT1 Current 24
T2 4 4 4 RTD input TC input Current input Voltage input
OUT1 Triac out OUT1 10 A 0 to 20 mA DC 0 to 5 V DC (Optional)
T1 5 5 + 5 5
4 to 20 mA DC 1 to 5 V DC
RTD
+ + +
OUT1 NO 11 B 11 11 11
External
6 NC IN
G
6 6 TC resistor
F, D action types 12 B 12 12 12

Specifications Performance:
Input: Display accuracy (at the ambient temperature 23 C 2 C):
Input type: Thermocouple:
Thermocouple: K, J, R, S, B, E, T, N, PLII, W5Re/W26Re, U, L (0.3 % of display value + 1 digit) or 2 C [4 F]
Input impedance: Approx. 1 M Whichever is greater
RTD: Pt100, JPt100 R, S and B input: 0 to 399 C [0 to 799 F]
Voltage: 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Z-1010) Accuracy is not guaranteed.
Current: 0 to 20 mA DC, 4 to 20 mA DC T and U input: 199.9 to 100.0 C [199.9 to 158.0 F]
Sampling cycle: 0.5 seconds Accuracy is not guaranteed.
Input range: Refer to Input range table RTD: (0.3 % of display value + 1 digit) or 0.8 C [1.6 F]
Control method: PID control Whichever is greater
ON/OFF, P, PI, or PD actions is available Voltage/Current:
(0.3 % of Input span + 1 digit)
Control output:
Memory backup:
Relay contact output:
250 V AC, 3A (Resistive load) Backed up by Nonvolatile Memory
Electrical life: 300,000 times or more (Rated load) Number of write times: Approx. 1,000,000 times
Voltage pulse output: Data storage period: Approx. 10 years
0/12 V DC (Load resistance 600 or more)
Current output: 4 to 20 mA DC (Load resistance 600 or less) Power:
Trigger output for triac driving: Power supply voltage:
Zero cross method for medium capacity triac 85 to 264 V AC (Power supply voltage range), 50/60 Hz
driving (100 A or less) Rating: 100 to 240 V AC
Load voltage used: 100 V AC line, 200 V AC line 21.6 to 26.4 V AC (Power supply voltage range), 50/60 Hz
Load used: Resistive load Rating: 24 V AC
Triac output: Output method:
21.6 to 26.4 V DC (Power supply voltage range)
AC output (Zero-cross method)
Allowable load current: Rating: 24 V DC
0.5 A (Ambient temperature: 40 C or less) Power consumption:
Load voltage: 75 to 250 V AC 7 VA max. (at 100 V AC) 10 VA max. (at 240 V AC)
Minimum load current: 20 mA 5 VA max. (at 24 V AC) 160 mA max. (at 24 V DC)
ON voltage:
1.6 V or less (at maximum load current) Weight:
CB100: Approx. 170 g CB700: Approx. 290 g
Alarm output:
CB400/CB500: Approx. 250 g CB900: Approx. 340 g
Relay contact output:
250 V AC, 1A (Resistive load)
Electrical life: 50,000 times or more (Rated load)
4 IMCB34-E1
4. PARTS DESCRIPTION
CB100 CB400 CB500 CB700, CB900
PV PV SV
(1) PV (1) (2)
PV
(1)
SV (2) (1)
AT OUT1 OUT2 ALM1 ALM2 (3)
AT OUT1 OUT2 ALM1 ALM2 (3) SV
SET R/S
SET R/S (2)
RKC CB100 RKC CB500 SV
(2)
AT OUT1 OUT2
(4) (5) (6) (7) (3) (4) (5) (6) (7)
ALM1 ALM2
AT OUT1 OUT2 ALM1 ALM2 (3)
SET R/S SET R/S

RKC CB400 RKC CB900

(4) (5) (6) (7) (4) (5) (6) (7)

(1) Measured value (PV) display [Green] Control output lamps (OUT1, OUT2) [Green] (5) R / S (Shift & R/S key)
Displays PV or various parameter symbols. OUT1: Lights when control output is turned on.* Shift digits when settings are changed.
OUT2: Lights when cool-side control output is Select the RUN/STOP function.
(2) Set value (SV) display [Orange] turned on.*
Displays SV or various parameter set values (or * Lamp indication becomes as follows for (6) (DOWN key)
CT input value). current output. Decrease numerals.
For an output of less than 0 %: Extinguished
(3) Indication lamps For an output of more than 100 %: Lit (7) (UP key)
Alarm output lamps (ALM1, ALM2) [Red] For an output of more than 0 % but less than Increase numerals.
ALM1: Lights when alarm 1 output is turned on. 100 %: Dimly lit.
ALM2: Lights when alarm 2 output is turned on.
Autotuning (AT) lamp [Green] (4) SET (Set key) To avoid damage to the
Flashes when autotuning is activated. (After Used for parameter calling up and set value instrument, never use a
autotuning is completed: AT lamp will go out) registration. sharp object to press keys.

5. SETTING
5.1 Operation Menu
Power ON Parameter Setting Mode
This mode is used to set the parameters such as alarms, PID constants, etc. (Refer to page 6.)
Input type and Input range Display The following parameter symbols are displayed as the SET key is pressed.
Automatically (in 4 seconds) Current transformer Autotuning (AT) Heat-side proportioning
(CT) input value 1
PV/SV Display Mode (CT1) (ATU) (T) cycle
monitor
SET key SET key SET key
The controller will display the Measured
Press and hold Alarm 1 set value Self-tuning (ST) Cool-side proportioning
value (PV) and the Set value (SV).
the SET key (ALM1) band
The controller can be switched to RUN or (AL1) (STU) (Pc)
for 2 seconds.
STOP mode (Factory set value: RUN). SET key SET key SET key

Alarm 2 set value Proportional band Deadband


PV PV/SV monitor
(AL2) (ALM2) (P) P = 0 (0.0): (db)
SV (RUN mode) Press
SET key SET key ON/OFF action SET key
Press and hold the <R/S key the <R/S key
for 1 second. while Heater break alarm Integral time Cool-side proportioning
pressing the (HBA) 1 set value cycle
STOP character display (HbA1) (I) (t)

(STOP mode) SET key. SET key SET key SET key
SV
Control loop break Derivative time PV bias
alarm (LBA) time
Press the SET key (LbA) (D) (Pb)
SET key SET key SET key
SV Setting Mode LBA deadband Anti-reset windup Set data lock
This is the mode used to set the SV. (Lbd) (Ar) (LCK)
SET key SET key SET key
PV
Return to the first parameter
SV SV setting
Factory set value: 0 C [F] or 0.0 C [F] Parameters which are not related to existing functions on the controller are not displayed.

Communication Setting Mode


Display returns to the PV/SV display
This mode is used to set the communication parameters when specified. For details on protocol, identifiers
mode if no key operation is performed and communication setting mode, refer to the Communication Instruction Manual (IMCB03-E).
within 1 minute.

Input type and input range display


This instrument immediately confirms the input type symbol and input range following power ON.
Example: When sensor type of input is K thermocouple.
Symbol * Input Type Symbol Table
PV
Automatically
PV Input range high Symbol
SV SV
Input range low Thermocouple (TC) RTD
Voltage
Input type W5Re/ JPt Pt
Input type symbol * K J R S B E T N PL II W26Re U L 100 100 (Current)
() ()
Unit for input and SV display
(Celsius: C, Fahrenheit: F, Voltage/Current input: no character shown) (): This input type is not displayed in the Z-1021 specification.

IMCB34-E1 5
5.2 Parameter List
Parameter symbols which are not related to existing functions on the controller are not displayed.

Symbol Name Setting range Description Factory set value


Current transformer 0.0 to 100.0 A Display input value from the current
(CT) input value 1 [Display only] transformer. [Displayed only when the
monitor instrument has the Heater break alarm (HBA)]
Alarm 1 set TC/RTD inputs: Set the alarm 1 set value and alarm 2 set TC/RTD inputs:
value (ALM1) Deviation alarm, Process alarm, value. 50 (50.0)
SV alarm:
1999 to +9999 C [F] or For the alarm action type, refer to page Voltage/Current inputs:
199.9 to +999.9 C [F] 10 and 11. 5.0
Alarm 2 set Voltage/Current inputs: Alarm differential gap:
value (ALM2) Deviation alarm: TC/RTD inputs: 2 or 2.0 C [F]
Input span to +Input span (Within 9999) Voltage/Current inputs: 0.2% of Input span
Process alarm, SV alarm:
Same as input range
Heater break 0.0 to 100.0 A Alarm value is set by referring to input 0.0
alarm (HBA) 1 See *1. value from the Current transformer (CT).
set value 1 Used only for single-phase.
Control loop 0.1 to 200.0 minutes Set control loop break alarm (LBA) set 8.0
break alarm See *2. value.
(LBA) time 2
LBA TC/RTD inputs: Set the area of not outputting LBA. 0
deadband 3 0 to 9999 C [F] No LBA deadband functions with 0 set.
Voltage/Current inputs: Differential gap :
0 to 100 % of Input span TC/RTD inputs: 0.8 C [F ]
See *3. Voltage/Current inputs: 0.8 % of Input span
Autotuning 0: AT end or cancel Turns the Autotuning ON/OFF. 0
(AT) 1: AT start or execution
Self-tuning 0: Self-tuning OFF Turns the Self-tuning ON/OFF. 0
(ST) 1: Self-tuning ON

Proportional TC/RTD inputs: Set when PI, PD or PID control is performed. TC/RTD inputs:
band 1 (0.1) to Heat/Cool PID action: Proportional band 30 (30.0)
Input span or 9999 (999.9) C [F] setting on the heat-side.
Voltage/Current inputs: Voltage/Current inputs:
ON/OFF action differential gap: 3.0
0.1 to 100.0 % of Input span
TC/RTD inputs: 2 (0.2) C [F ]
0 (0.0): ON/OFF action Voltage/Current inputs: 0.2 % of Input span
Integral time 1 to 3600 seconds Set the time of integral action to eliminate 240
(0 second: PD action) the offset occurring in proportional control.

Derivative time 1 to 3600 seconds Set the time of derivative action to improve 60
(0 second: PI action) control stability by preparing for output
changes.
Anti-reset 1 to 100 % of heat-side proportional Overshooting and undershooting are 100
windup (ARW) band restricted by the integral effect.
(0 %: Integral action OFF)
Heat-side 1 to 100 seconds Set control output cycle. Relay contact output: 20
proportioning (Not displayed if the control output is Heat/Cool PID action: Voltage pulse output/
cycle current output.) Heat-side proportioning cycle Trigger output for triac
driving/Triac output: 2
Cool-side 1 to 1000 % of heat-side proportional Set cool-side proportional band when 100
proportional band. Heat/Cool PID action.
band
Deadband TC/RTD inputs: Set control action deadband between 0 or 0.0
10 to +10 C [F] or heat-side and cool-side proportional bands.
10.0 to +10.0 C [F] Minus () setting results in overlap.
Voltage/Current inputs:
10.0 to +10.0 % of Input span
Cool-side 1 to 100 seconds Set control cool-side output cycle for Relay contact output: 20
proportioning (Not displayed if the control output is Heat/Cool PID action. Voltage pulse output/
cycle current output.) Triac output: 2
PV bias TC/RTD inputs: Sensor correction is made by adding bias 0 or 0.0
1999 to +9999 C [F] or value to Measured value (PV).
199.9 to +999.9 C [F]
Voltage/Current inputs:
Input span to +Input span
Set data lock Performs set data change enable/disable. 0000
(LCK) Parameters other than SV and Alarms
0: Unlock 1: Lock
Alarms
0: Unlock 1: Lock
SV
0: Unlock 1: Lock
Initialization mode
0: Lock 1: Unlock

6 IMCB34-E1
1
Heater break alarm (HBA) function 5.3 Changing Parameter Settings
The HBA function monitors the current flowing through the load
by a dedicated Current transformer (CT), compares the measured Procedures to change parameter settings are shown below.
value with the HBA set value, and detects a fault in the heating
circuit. To store a new value for the parameter, always press the SET
Low or No current flow (Heater break, malfunction of the key. The display changes to the next parameter and the new
control device, etc.): value will be stored.
When the control output is ON and the current transformer input A new value will not be stored without pressing SET key after
value is equal to or less than the heater break determination point the new value is displayed on the display.
for the preset number of consecutive sampling cycle, an alarm is After a new value has been displayed by using the UP and
activated. DOWN keys, the SET key must be pressed within 1 minute, or
Over current or short-circuit: the new value is not stored and the display will return to the
When the control output is OFF and the current transformer input PV/SV monitor screen.
value is equal to or greater than the heater break determination
point for the preset number of consecutive sampling cycle, an
alarm is activated.
z Change the Set value (SV)
Precaution for HBA setting: Change the Set value (SV) from 0 C to 200 C
Displayed only for when HBA is selected as Alarm 2. 1. Select the SV setting mode
HBA is not available on a current output. Press the SET key at PV/SV monitor screen until SV setting
Set the set value to approximately 85 % of the maximum screen is displayed.
reading of the CT input.
Set the set value to a slightly smaller value to prevent a false
alarm if the power supply may become unstable. PV PV

When more than one heater is connected in parallel, it may be


SV SV
necessary to increase the HBA set value to detect a single
heater failure. AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2

When the current transformer is not connected, the HBA is SET

CB100
R/S SET

CB100
R/S

turned on. PV/SV monitor display SV setting display


(PV/SV display mode) (SV setting mode)
2
Control loop break alarm (LBA) function
The LBA function is used to detect a load (heater) break or a 2. Shift the high-lighted digit
failure in the external actuator (power controller, magnet relay, Press the <R/S key to high-light the hundreds digit.
etc.), or a failure in the control loop caused by an input (sensor) The high-lighted digit indicates which digit can be set.
break. The LBA function is activated when control output reaches
0 % (low limit with output limit function) or 100 % (high limit with
output limit function). LBA monitors variation of the measured PV PV

value (PV) for the length of LBA time. When the LBA time has
elapsed and the PV is still within the alarm determination range, SV SV

the LBA will be ON. AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2

SET R/S SET R/S

Precaution for LBA setting: CB100 CB100

Displayed only for when LBA is selected as Alarm 1 or Alarm 2.


No LBA function can be used at Heat/Cool PID control action. 3. Change the set value
The LBA function can not be activated when AT function is Press the UP key to change the number to 2.
turned on.
The LBA function is activated when control output reaches 0 % PV PV
or 100 %. The time required for the LBA output to turn on
includes both the time from the initial occurrence of loop failure SV SV
and the LBA setting time. Recommended setting for LBA is for
the set value of the LBA to be twice the value of the Integral AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2

time (I). SET

CB100
R/S SET

CB100
R/S

If LBA setting time does not match the controlled object


requirements, the LBA selling time should be lengthened.
If setting time is not correct, the LBA will malfunction by turning 4. Store the set value
on or off at inappropriate times or not turning on at all. Press the SET key to store the new set value. The display returns
to the PV/SV monitor screen.
3
LBA deadband function
The LBA may malfunction due to external disturbances. To PV PV

prevent malfunctioning due to external disturbance, LBA


deadband (LBD) sets a neutral zone in which LBA is not activated. SV SV

When the Measured value (PV) is within the LBD area, LBA will AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2

not be activated. If the LBD setting is not correct, the LBA will not SET R/S SET R/S

work correctly. CB100 CB100

PV/SV monitor display


LBD differential gap* (PV/SV display mode)

Alarm area A Non-alarm area B Alarm area


z Change parameters other than the Set value (SV)
Low High
Set value (SV) LBD set value The changing procedures are the same as those of example 2 to
4 in the above "z Change the Set value (SV)". Pressing the SET
A: During temperature rise: Alarm area B: During temperature rise: Non-alarm area
During temperature fall: Non-alarm area During temperature fall: Alarm area key after the setting end shifts to the next parameter. When no
B: During temperature rise: Non-alarm area
* TC and RTD inputs: 0.8 C [F] (fixed) parameter setting is required, return the instrument to the PV/SV
Voltage/Current inputs: 0.8 % of input span (fixed) display mode.

IMCB34-E1 7
6. OPERATIONS
CAUTIONS
z All mounting and wiring must be completed before the power is turned on. If the input signal wiring is disconnected or
short-circuited (RTD input only), the instrument determines that burnout has occurred.
Displays:
Upscale: Thermocouple input, RTD input (when input break)
Downscale Thermocouple input (specify when ordering), RTD input (when short-circuited), Voltage input (1 to 5 V DC),
Current input (4 to 20 mA DC)
For the voltage (0 to 5 V DC, 0 to 10 V DC*) or current (0 to 20 mA DC) input, the display becomes indefinite (display of about
zero value).
* Z-1010 specification
Outputs:
Control output: OFF (Heat/Cool control: the control output on both heat-side and cool-side is turned off)
Alarm output: Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when burnout occurs regardless of any of
the following actions taken (High alarm, low alarm, etc.). In addition, when used for any purposes other than these
alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).
z A power failure of 20 ms or less will not affect the control action. When a power failure of more than 20 ms occurs, the
instrument assumes that the power has been turned off. When power returns, the controller will retain the conditions that
existed prior to shut down.
z The alarm hold action is activated when not only the power is turned on, but also the SV is changed.

6.1 Operation Procedures Caution for using the Autotuning (AT)


When a temperature change (UP and/or Down) is 1 C or
1. Prior to starting operation, check that the mounting and wiring less per minute during AT, AT may not be finished
have been finished, and that the SV and various parameters normally. In that case, adjust the PID values manually.
have been set. Manual setting of PID values may also be necessary if the
2. A power supply switch is not furnished with this instrument. It set value is around the ambient temperature or is close to
is ready to operate as soon as the power is turned on. the maximum temperature achieved by the load.
(Factory set value: RUN).
Requirements for AT start
This instrument holds the conditions that exist just before Start the Autotuning when all following conditions are satisfied:
the power is turned on. For example, if the power is turned
Prior to starting the AT function, end all the parameter settings
off in STOP mode, the instrument starts in STOP mode
other than PID and LBA.
when the power is turned on again.
Confirm the LCK function has not been engaged.
RUN/STOP When the Autotuning is finished, the controller will
Each time the <R/S key is pressed for 1 second, RUN/STOP automatically returns to PID control.
mode changes from RUN to STOP or STOP to RUN. If the
instrument is switched to STOP mode, its display, output, etc. Requirements for AT cancellation
become as follows. The Autotuning is canceled if any of the following conditions exist.
Display: The PV display shows (STOP). When the Set value (SV) is changed.
Output: Control output OFF, Alarm output OFF When the PV bias value is changed.
Autotuning: AT canceled (The PID constants are not updated.) When the RUN/STOP mode is changed to the STOP mode.
When the PV becomes abnormal due to burnout.
RUN/STOP display (Z-1018 specification) When the power is turned off.
When operation is changed to the STOP mode by RUN/STOP When power failure longer than 20 ms occurs.
selection, a parameter symbol to indicate the STOP mode is When the AT does not end in 9 hours after autotuning started.
displayed on the SV display. Pressing the SET key with the STOP
mode displayed can also check and change the Set value (SV). If the AT is canceled, the controller immediately changes to
PID control. The PID values will be the same as before AT
was activated.
6.2 Set Data Lock (LCK) Function When AT is completed, the controller immediately changes
The set data lock restricts parameter setting changes by key to PID control. If the control system does not allow the AT
operation. This function prevents the operator from making errors cycling process, set each PID constant manually to meet
during operation. There are 8 set data lock levels. (refer to below) the needs of the application.
Set value Parameters which can be changed
0000 All parameters [Factory set value] 6.4 Self-tuning (ST) Function
0001 SV, Alarms (ALM1, ALM2) The ST function is used to automatically calculate and set
0010 All parameters except for Alarms (ALM1, ALM2) adaptive PID constants anytime the power is turned on, the SV is
0011 SV changed or the controller detects unstable control conditions.
0100 All parameters except for SV The ST function should be turned off when the controlled
0101 Alarms (ALM1, ALM2) system is affected by rippling that occurs due to periodic
0110 All parameters except for SV and Alarms (ALM1, ALM2) external disturbances.
0111 No parameters (All Locked) The power to the controlled system must be turned on
HBA, LBA and LBD can be locked when any of 0001, 0011, 0101 and before the power to the instrument is turned on or SV is
0111 is set. changed. This is required when ST function is on.
Set data lock can be changed in both RUN and STOP To activate the ST function, the following parameters must
mode. not be set to zero: P0, I0, D0, ARW0.
Parameters protected by Set data lock function are still When Heat/Cool PID action is selected, the ST function can
displayed for monitoring. not be activated.
When the AT function is activated, the ST function can not
6.3 Autotuning (AT) Function be turned on.
Autotuning (AT) automatically measures, computes and sets the
When the ST function is activated, the PID and ARW
optimum PID and LBA constants. The following conditions are
settings can be monitored, but not changed.
necessary to carry out Autotuning and the conditions which will
cause the Autotuning to stop.
8 IMCB34-E1
7. INITIAL SETTING

! WARNING
Parameters in the Initialization mode should be set according to the application before setting any parameter
related to operation. Once the Parameters in the Initialization mode are set correctly, no further changes need to
be made to parameters for the same application under normal conditions. If they are changed unnecessarily, it
may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or
failure as a result of improper changes in the Initialization mode.

7.1 Go to Initialization Mode 7.2 Exit Initialization Mode


1. Turn on the power to this controller. The instrument goes to When any parameter setting is changed in the Initialization
the PV/SV display after confirming input type symbol and mode, check all parameter set values in SV setting mode
input range. and Parameter setting mode.
2. Press and hold the SET key for 2 seconds to go to the 1. Press the <R/S key for 2 seconds while pressing the SET key
Parameter Setting Mode from the PV/SV display. from any display in the Initialization mode. The controller goes
3. Press the SET key until LCK (Set data lock display) will be back to the operation mode and the PV/SV display will be
displayed. displayed.
4. The high-lighted digit indicates which digit can be set. Press 2. Press and hold the SET key for 2 seconds in the PV/SV display.
<R/S key to high-light the thousands digit. (The section in 3. Press the SET key until LCK (Set data lock display) will be
each image of the controller shows the digits which are not displayed.
high-lighted.) 4. The high-lighted digit indicates which digit can be set. Press
PV
<R/S key to high-light the thousands digit. (The section in
each image of the controller shows the digits which are not
SV high-lighted.)
AT OUT1 OUT2 ALM1 ALM2
5. Press the DOWN key to change 1 to 0.
SET R/S

CB100 PV

Set data lock function display


SV

5. Press the UP key to change 0 to 1. AT OUT1 OUT2 ALM1 ALM2

SET R/S

CB100
PV

Set value Set data lock function display


SV 0: Initialization mode
6. Press the SET key to store the new set value. The display
locked
AT OUT1 OUT2 ALM1 ALM2 goes to the next parameter, and the Initialization mode is
1: Initialization mode
SET

CB100
R/S
unlocked locked.
PV

6. Press the SET key to store the new set value. The display
SV
goes to the next parameter, and the Initialization mode is
The parameter displayed
unlocked. AT OUT1 OUT2 ALM1 ALM2
varies on the instrument
SET R/S

PV CB100 specification.
CT1 input value display
SV

AT OUT1 OUT2 ALM1 ALM2


The parameter displayed 7.3 Initial Setting Menu
SET R/S varies on the instrument
CB100 specification. The Cod display will be displayed when the controller goes to
CT1 input value display the Initialization mode.
Do not change to any parameter in the Initialization mode
7. Press the <R/S key for two seconds while pressing the SET which is not described in the initial setting menu above.
key to go to the Initialization mode. When the controller goes It may result in malfunction or failure of the instrument.
to the Initialization mode, Cod will be displayed.
PV/SV display mode or Parameter setting mode
Press the <R/S key while pressing the SET
PV PV
key for 2 seconds with the unlocked.
Initialization code selection
SV SV
(Cod)
Set Cod to 0000. Set Cod to 0001.
AT OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2

SET R/S SET R/S Input type selection Setting limiter high
CB100 CB100
(SL1) (SLH)
CT1 input value display Initialize code selection display
Temperature unit and Setting limiter low
of initialization mode
cooling type selection
(SL2) (SLL)

Cod SL1 (Input type selection) Refer to P. 10 Alarm1 type selection Decimal point
(SL4)
position
0000 SL2 (Temperature unit and cooling type selection) Refer to P. 10 (PGdP)
Alarm2 type selection
SL4 (Alarm 1 type selection) Refer to P. 10
(SL5)
SL5 (Alarm 2 type selection) Refer to P. 10 SV alarm type selection To PV/SV
SL11 (SV alarm type selection) Refer to P. 11 display mode
(SL11)

Cod SLH (Setting limiter [high]) Refer to P. 11


0001 SLL (Setting limiter [low]) Refer to P. 11 To PV/SV display mode Initialization code selection
PGdP (Decimal point position) Refer to P. 11 : Press the SET key, or press the SET key several times.
: Press the <R/S key while pressing the SET key for 2 seconds.

IMCB34-E1 9
7.4 Input Type Selection (SL1) 7.6 Alarm 1 [ALM1] Type Selection (SL4)
When any parameter setting is changed in the Initialization Alarm 2 [ALM2] Type Selection (SL5)
mode, check all parameter set values in SV setting mode If the alarm function is not provided with the instrument when
and Parameter setting mode. shipped from the factory, no alarm output is available by changing
Factory set value varies depending on the input type. SL4 and/or SL5.
Set value Input type SL4 is set to 0000 in the following cases.
0000 K When the instrument does not have ALM1 output
0001 J When Control loop break alarm (LBA) is provided and
0010 L assigned to ALM1
0011 E When the SV alarm is provided and assigned to ALM1
0100 N
0111 R Thermocouple 1 SL5 is set to 0000 in the following cases.
1000 S (TC) When the instrument does not have ALM2 output
1001 B4 When Control loop break alarm (LBA) is provided and
1010 W5Re/W26Re 4 assigned to ALM2
1011 PL II When the SV alarm is provided and assigned to ALM2
0101 T When the Heater break alarm (HBA) is provided
0110 U When the instrument has Z-168 specification
1100 Pt100 (JIS/IEC)
RTD 1 Factory set value varies depending on the instrument specification.
1101 JPt100 (JIS)
1110 0 to 5 V DC Set value Details of setting
1110 0 to 10 V DC 2 Voltage 1 0000 No alarm
1111 1 to 5 V DC 0001 Deviation high alarm
1110 0 to 20 mA DC
Current 1, 3 0101 Deviation low alarm
1111 4 to 20 mA DC
1
0010 Deviation high/low alarm
Any input change in TC&RTD group is possible. Any input change in
0110 Band alarm
Voltage & Current group except for 0 to 10 V DC input is possible. No input
change between TC&RTD group and Voltage & Current group is possible. 0011 Process high alarm
2
The input type of Z-1010 specification is fixed to 0 to 10 V DC due to the 0111 Process low alarm
hardware difference. 1001 Deviation high alarm with hold action *
3
For the current input specification, a resistor of 250 must be connected 1101 Deviation low alarm with hold action *
between the input terminals.
4 1010 Deviation high/low alarm with hold action *
W5Re/W26Re and B are not available with Z-1021 specification (Modbus
communication). 1011 Process high alarm with hold action *
1111 Process low alarm with hold action *
Change Settings * Hold action:
Example: Change the input type from K to J When Hold action is ON, the alarm action is suppressed at start-up or the
control set value change until the measured value enters the non-alarm range.
1. Set Cod to 0000, and press the SET key. The display will
go to SL1. z Alarm action type
PV PV
Both of the Alarm 1 and Alarm 2 outputs of this instrument are
turned on when burnout occurs regardless of any of the following
SV SV
actions taken (high alarm, low alarm, etc.). In addition, when used
Initialize code selection display Input type selection
for any purposes other than these alarms (event, etc.), specify the
Z-124 specification (not to be forcibly turned on).
2. Press the UP key to change the number to 1.
PV
Deviation high alarm ( : SV : Alarm set value : Alarm differential gap)
*(Alarm set value is greater than 0.)
OFF ON
SV PV
Low High
*(Alarm set value is less than 0.)
OFF ON
3. Press the SET key to store the new set value. The display Low High
PV
goes to the next parameter. Deviation low alarm
*(Alarm set value is greater than 0.)
ON OFF
PV
7.5 Temperature Unit and Cooling Type Low
*(Alarm set value is less than 0.)
High

Selection (SL2) ON OFF


PV
Low High
Inappropriate settings may result in malfunction. Deviation high/low alarm
Control type between Heat Only and Heat/Cool cannot be ON OFF ON
changed by this parameter. Low High
PV

Factory set value varies depending on the instrument specification. Band alarm
OFF ON OFF
Description Low High
PV
Set
Temperature Process high alarm
value unit Cooling type selection
OFF ON
PV
0000 C Air cooling (A type) or Heat only type (F, D type) Low High
Process low alarm
0001 F Air cooling (A type) or Heat only type (F, D type)
ON OFF
0010 C Water cooling (W type) Low High
PV

0011 F Water cooling (W type)

Change Settings Change Settings


Example: Change the ALM1 type from Deviation high alarm
Example: Change the temperature unit of the Heat only type
(0001) to Deviation low alarm (0101)
from C (0000) to F (0001)
1. Press the SET key three times at SL1 until SL4 is displayed.
1. Press the SET key until SL2 is displayed.
2. Press the <R/S key to high-light the hundreds digit.
2. Press the UP key to change the number to 1.
3. Press the UP key to change the number to 1.
PV PV
PV PV

SV SV
SV SV

3. Press the SET key to store the new set value. The display
4. Press the SET key to store the new set value. The display
goes to the next parameter.
goes to the next parameter.

10 IMCB34-E1
7.7 SV Alarm Type Selection (SL11) Factory set value varies depending on the instrument specification.
For ALM1 setting, the first digit from the right is set to 0 Setting range
in the following cases. Input type Setting limiter Setting limiter
When the instrument does not have ALM1 output. high low
When the ALM1 output is used for Process/Deviation/ U SLL to 600.0 C 199.9 to SLH C
Band alarm or Control loop break alarm (LBA). TC SLL to 999.9 F 199.9 to SLH F
L SLL to 800 C 0 to SLH C
For ALM2 setting, the third digit from the right is set to 0
SLL to 1600 F 0 to SLH F
in the following cases.
RTD Pt100 SLL to 649.0 C 199.9 to SLH C
When the instrument does not have ALM2 output.
JPt100 SLL to 999.9 F 199.9 to SLH F
When the ALM1 output is used for Process/Deviation/
Voltage 0 to 5 V DC
Band alarm, Heater break alarm (HBA) or Control loop
0 to 10 V DC * SLL to 9999 1999 to SLH
break alarm (LBA).
1 to 5 V DC (Programmable (Programmable
When Z-168 is specified.
Current 0 to 20 mA DC range) range)
To make SV alarm setting effective, set SL4 to 0000 4 to 20 mA DC
when using ALM1 for SV alarm, or set SL5 to 0000 when * Z-1010 specification
using ALM2 for SV alarm. SL4 and SL5 have priority to
SL11 setting. Change Settings
Factory set value varies depending on the instrument specification. Example: When the display range is scaled to 0.0 to 400.0 for
Alarm Details of setting a voltage input of 1 to 5 V DC.
0 SV alarm not provided 1V 5V
Alarm 1 1 SV alarm provided
[ALM1] 0 SV high alarm Factory set value 0.0 100.0
Scaling 0.0 400.0
1 SV low alarm
0 SV alarm not provided 1. Set Cod to 0001, and press the SET key. The display will go
Alarm 2 1 SV alarm provided to SLH.
[ALM2] 0 SV high alarm PV PV

1 SV low alarm
SV SV
z SV alarm action type
( : Alarm set value : Alarm differential gap) Initialize code selection display Setting limiter [high] display
SV high alarm
OFF ON 2. The high-lighted digit indicates which digit can be set. Press
SV
Low High
SV low alarm
<R/S key to high-light the first digit from the left.
PV
ON OFF
SV
Low High
SV

Change Settings
Example: Change the SV alarm type of the ALM1 from SV high 3. Press the UP key to change the number to 4.
alarm (0001) to SV low alarm (0011) PV

1. Press the SET key ten times at SL1 until SL11 is displayed. SV

2. Press the <R/S key to high-light the tens digit. Next, press
the UP key to change the number to 1.
PV PV
4. Press the SET key to store the new set value. The display
goes to SLL.
SV SV 5. Set SLL to 0.0.
High-light 6. Press the SET key to store the new set value. The display
3. Press the SET key to store the new set value. The display goes to the next parameter.
goes to the initialize code parameter.

7.9 Decimal Point Position (PGdP)


7.8 Setting Limiter High (SLH) Use to select a Decimal point position of the input range (voltage
Setting Limiter Low (SLL) input and current input). PGdP is displayed only for voltage or
For voltage or current input, set scaling within the input range. current input.
Refer to Input range table (P. 12) Inappropriate settings may result in malfunction.
Factory set value varies depending on the instrument specification.
Set Description
Setting range value
Input type Setting limiter Setting limiter 0000 No decimal place ()
high low
0001 One decimal place (.) [Factory set value]
K SLL to 1372 C 0 to SLH C 0002 Two decimal places (.)
SLL to 2502 F 0 to SLH F
0003 Three decimal places (.)
J SLL to 1200 C 0 to SLH C
SLL to 2192 F 0 to SLH F
R SLL to 1769 C 0 to SLH C Change Settings
S SLL to 3216 F 0 to SLH F Example: Change the Decimal point position from One
B SLL to 1820 C 0 to SLH C
SLL to 3308 F 0 to SLH F
decimal place (0001) to No decimal place (0000)
TC E SLL to 1000 C 0 to SLH C 1. Press the SET key two times at SLH until PGdP is displayed.
SLL to 1832 F 0 to SLH F
N SLL to 1300 C 0 to SLH C
2. Press the DOWN key to change the number to 0.
SLL to 2372 F 0 to SLH F PV PV

T SLL to 400.0 C 199.9 to SLH C


SLL to 752.0 F 199.9 to SLH F SV SV

W5Re/W26Re SLL to 2320 C 0 to SLH C


SLL to 4208 F 0 to SLH F
PLII SLL to 1390 C 0 to SLH C 3. Press the SET key to store the new set value. The display
SLL to 2534 F 0 to SLH F goes to the next parameter.

IMCB34-E1 11
8. ERROR DISPLAYS
Error display

RAM failure (Incorrect set data write, etc.) Turn off the power at once. If an error occurs
after the power is turned on again, please
contact RKC sales office or the agent.

Over-scale and Underscale


Measured value (PV) PV is outside of input range. WARNING
!
[Flashing]
To prevent electric shock, always
Over-scale: turn off the power before replacing
PV is above the high input display range limit. the sensor.
[Flashing]
Check Input type, Input range and
Underscale:
connecting state of sensor. Confirm that
PV is below the low input display range limit.
[Flashing] the sensor or wire is not broken.

9. INPUT RANGE TABLE


Input type Model Input type Model Input type Model Input type Model Input type Model
code code code code code
0 to 200 C K 01 0 to 800 F J A1 0 to 1200 C N 01 *2 - 199.9 to +100.0 C U 02 -100.0 to +100.0 F D A4
0 to 400 C K 02 0 to 1600 F J A2 0 to 1300 C N 02 0.0 to 400.0 C U 03 -100.0 to + 300.0 F D A5
J N
0 to 600 C K 03 0 to 2192 F J A3 0 to 2300 F N A1 U *2 - 199.9 to +999.9 F U A1
Pt100
0.0 to 100.0 F D A6
0 to 800 C K 04 0 to 400 F J A6 0 to 2372 F N A2 - 100.0 to +200.0 F U A2 0.0 to 200.0 F D A7
0 to 1000 C K 05 0 to 300 F J A7 *2 -199.9 to +400.0 C T 01 0.0 to 999.9 F U A3 0.0 to 400.0 F D A8
0 to 1200 C K 06 *1 0 to 1600 C R 01 *2 -199.9 to +100.0 C T 02 0 to 400 C L 01 0.0 to 500.0 F D A9
0 to 1372 C K 07 *1 0 to 1769 C R 02 -100.0 to +200.0 C T 03 0 to 800 C L 02 -199.9 to +649.0 C P 01
K L
0 to 100 C K 13 R *1 0 to 1350 C R 04 0.0 to 350.0 C T 04 0 to 800 F L A1 -199.9 to +200.0 C P 02
0 to 300 C K 14 *1 0 to 3200 F R A1 T *2 -199.9 to +752.0 F T A1 0 to 1600 F L A2 -100.0 to + 50.0 C P 03
0 to 450 C K 17 *1 0 to 3216 F R A2 -100.0 to +200.0 F T A2 -199.9 to + 649.0 C D 01 -100.0 to +100.0 C P 04
0 to 500 C K 20 *1 0 to 1600 C S 01 -100.0 to +400.0 F T A3 -199.9 to +200.0 C D 02 JPt100 -100.0 to +200.0 C P 05
0 to 800 F K A1 *1 0 to 1769 C S 02 0.0 to 450.0 F T A4 -100.0 to + 50.0 C D 03 0.0 to 50.0 C P 06
S
0 to 1600 F K A2 *1 0 to 3200 F S A1 0.0 to 752.0 F T A5 -100.0 to + 100.0 C D 04 0.0 to 100.0 C P 07
0 to 2502 F K A3 *1 0 to 3216 F S A2 W5Re/ 0 to 2000 C W 01 -100.0 to + 200.0 C D 05 0.0 to 200.0 C P 08
20 to 70 F K A9 400 to 1800 C B 01 W26Re 0 to 2320 C W 02 0.0 to 50.0 C D 06 0.0 to 300.0 C P 09
0 to 200 C J 01 B *1 0 to 1820 C B 02 ( *3 ) 0 to 4000 F W A1 Pt100 0.0 to 100.0 C D 07 0.0 to 500.0 C P 10
0 to 400 C J 02 ( *3 ) 800 to 3200 F B A1 0 to 1300 C A 01 0.0 to 200.0 C D 08 0 to 5 V DC 4 01
0 to 600 C J 03 *1 0 to 3308 F B A2 0 to 1390 C A 02 0.0 to 300.0 C D 09 0 to 10 V DC ** 0.0 5 01
J 0 to 800 C J 04 0 to 800 C E 01 PL 0 to 1200 C A 03 0.0 to 500.0 C D 10 1 to 5 V DC to 6 01
0 to 1000 C J 05 0 to 1000 C E 02 0 to 2400 F A A1 - 199.9 to + 999.9 F D A1 0 to 20 mA DC 100.0 7 01
0 to 1200 C J 06 E 0 to 1600 F E A1 0 to 2534 F A A2 -199.9 to + 400.0 F D A2 4 to 20 mA DC 8 01
0 to 450 C J 10 0 to 1832 F E A2 U *2 -199.9 to +600.0 C U 01 - 199.9 to + 200.0 F D A3 **Z-1010 specification
*1 0 to 399 C /0 to 799 F: Accuracy is not guaranteed. *2 -199.9 to -100.0 C /-199.9 to -158.0 F: Accuracy is not guaranteed.
*3 This input type can not be selected in the Z-1021 specification.

10. REMOVING THE INTERNAL ASSEMBLY


Usually, this instrument is not necessary to remove the internal assembly from the case. When removing the internal assembly without
disconnecting the external wiring, take the following steps.

! WARNING
z To prevent electric shock or instrument failure, only qualified personnel should be allowed to pull out the
internal assembly.
z To prevent electric shock or instrument failure, always turn off the power before pulling out the internal assembly.
z To prevent injury or instrument failure, do not touch the internal printed wiring board.

Lock (upper) Apply pressure very carefully when removing internal assembly
to avoid damage to the frame.
To conform to IEC61010-1 requirements for protection from electric
shock, the internal assembly of this instrument can only be removed
with an appropriate tool.
Recommended tool: Unlocking points (marked with {) depend on the model as follows:
Slotted screwdriver CB400 CB100 CB900
(Tip width: CB500
CB700
6 mm or less)
Lock (lower)
Unlock using such a slotted screwdriver.
Gently press down on handle for the upper lock and
lift up for the lower lock.
The first edition: JAN. 2012 [IMQ00]

HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN


RKC INSTRUMENT INC. PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp
Website: http://www.rkcinst.com/ FAX: 03-3751-8585 (+81 3 3751 8585)
IMCB34-E1 JAN. 2012

You might also like