Sample Diagrams
Sample Diagrams
Sample Diagrams
69 0.115 0.2 0.115 0.2 kV, 0.3/0.3 20VA/20VA 69 0.115 0.2 0.115 0.2 kV, 0.3/0.3 20VA/20VA
TERMINAL
/ ; / ; / ; / ;
UNDERGROUND CABLE
ELECTRIC REACTOR
M M FUSE CUT OUT
=E2-Q2 69kV,2000A,40kA =E4-Q2 69kV,2000A,40kA
3 3
600/300:5A 1# 5P20 30/30VA 600/300:5A 1# 5P20 30/30VA
3 3 RELAY 630A,34.5kV,25kA/1S,60Hz
600/300:5A 2# 5P20 30/30VA 600/300:5A 2# 5P20 30/30VA 50/51, 50/51N 630A 630A
CT04
CT02 3 3
600/300:5A 3# 5P20 30/30VA 600/300:5A 3# 5P20 30/30VA RING MAIN UNIT
3 3 THREE-POSITION
600/300:5A 4# 0.2 20VA 600/300:5A 4# 0.2 20VA SWITCH
DISCONNECTOR
=E2-Q0 69kV,2000A,40kA,3s =E4-Q0 69kV,2000A,40kA,3s
3 3
600/300:5A 5# 0.2 20VA 600/300:5A 5# 0.2 20VA
3 3
600/300:5A 6# 5P20 30/30VA 600/300:5A 6# 5P20 30/30VA
CT02 3 CT04 3
600/300:5A 7# 5P20 30/30VA 600/300:5A 7# 5P20 30/30VA
3 3
600/300:5A 8# 5P20 30/30VA 600/300:5A 8# 5P20 30/30VA
3 3 JDZXR8-10BG
PTR No. 1 300:5A 5P20 30VA 300:5A 5P20 30VA PTR No. 2
34.5kV NEUTRAL-POINT 34.5kV NEUTRAL-POINT 10kV/ 3/0.115/ 3/
SZ11-25/30 34.5/69kV 3 3 SZ11-25/30 34.5/69kV 0.115/3kV, 0.5/6P
SOLID GROUND ONAN/ONAF
300:5A 0.2 30VA 300:5A 0.2 30VA
ONAN/ONAF
SOLID GROUND
RXGI-1000W-1000R
600:5A 5P20 30VA 600:5A 5P20 30VA
69(+12,-8)x1.25%/34.5kV 600:5A 5P20 30VA 600:5A 5P20 30VA 69(+12,-8)x1.25%/34.5kV LZZBJ9-10E2
600:5A 5P20 30VA 3 3 600:5A 5P20 30VA 800/5,0.5/5P20
3 600:5A 5P20 30VA 600:5A 5P20 30VA 3
Ud=12.5% Dyn11 3 3 Ud=12.5% Dyn11 /5P20,20VA Project
600:5A 5P20 30VA 600:5A 5P20 30VA
OLTC 3 3 OLTC
600:5A 5P20 30VA 600:5A 5P20 30VA
Scale
SVG-GL NTS DO NOT SCALE
MATCHLINE A-A JOINS DRG. GF1508-SCSN-03-SLD-002-001 Drawn A. PALOMERO Designer P. POCHON
Drafting J. ANIEVAS Design R. MIRANDA
Check Check
Approved
RICCARDO MIRANDA
Date 14.12.15
This Drawing must not be used for Construction unless signed as Approved
Title
Original Size
Drawing No.
A1
GF1508-SCSN-03-SLD-001
Rev. E
LEGEND:
3
CURRENT TRANSFORMER
VOLTAGE TRANSFORMER
CIRCUIT BREAKER
EARTHING SWITCH
DISCONNECTING SWITCH
INDICATOR LIGHT
LOAD BREAKER SWITCH
TRANSFORMER
ARRESTER
TERMINAL
UNDERGROUND CABLE
ELECTRIC REACTOR
FUSE CUT OUT
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
MATCHLINE B-B JOINS DRG. GF1508-SCSN-03-SLD-002-002
34.5 0.115 0.115 kV 5P20 600:5A
/ / 3
5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3
30VA P Job Project
P P P P P P ; 0.5 60VA/100VA 5P20 600:5A 3 P PNo. Revision: Drawn Manager Director Date
CORE 1
3 3 3 3 3 3 3 3 ON-SHORE CONTRACTOR:
CORE 2
0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 30VA 3 P 0.5 100:5A 15VA 0.5 100:5A 15VA
0.2S 600:5A
P O W E R S Y S T E M S I N C
M M M M M M M M M
30VA OFF-SHORE CONTRACTOR:
INCOMING 1 INCOMING 2 INCOMING 3 INCOMING 4 INCOMING 5 INCOMING 6 PT1 BUS TIE INCOMING 7 INCOMING 8
FEEDER 1 FEEDER 2 FEEDER 3 FEEDER 4 FEEDER 5 FEEDER 6 FEEDER 7 OWNER'S
FEEDER 8 ENGINEER:
ZRCY-YJV62-26/35kV
3(1X70)mm2 IS 3 IS 4 IS 6 IS 5 IS 8 IS 7 IS 9 IS 10 IS 16 IS 17
IS 1 IS 2 IS 11 IS 12 IS 13 IS 14 IS 15
630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz OWNER:
630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
630A 630A 630A 630A 630A
Date 14.12.15
This Drawing must not be used for Construction unless signed as Approved
Title
A1
Rev. E
LEGEND:
3
CURRENT TRANSFORMER
VOLTAGE TRANSFORMER
CIRCUIT BREAKER
EARTHING SWITCH
DISCONNECTING SWITCH
ZRC-YJV62-26/35kV 3(1x300)mm2
INDOOR TYPE, 40.5 kV METALCLAD SWITCHGEAR
CORE 2
34.5 0.115 0.115 kV
/ /
3
; 0.5 60VA/100VA
ISSUED FOR CONSTRUCTION
MATCHLINE B-B JOINS DRG. GF1508-SCSN-03-SLD-002-001
Job Project
No. Revision: Drawn Manager Director Date
34.5kV,1250A,31.5kA 3s,60Hz ON-SHORE CONTRACTOR:
P O W E R S Y S T E M S I N C
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
CORE 1 CORE 2
5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 100:5A 20VA 3 5P20 20:5A 7.5VA 3 5P20 300/100:5A 3
P P P P P P 20/20VA P
CORE 1
CORE 2
3 3 3 3 3 3 3 OWNER'S ENGINEER:
0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 100:5A 15VA 0.5 20:5A 7.5VA 0.5 300/100:5A
M M M M M M 15/15VA M
34.5 0.115 0.115 kV
/ /
3
; 0.5 60VA/100VA
INCOMING 7 INCOMING 8 INCOMING 9 INCOMING 10 INCOMING 11 INCOMING 12 AUX PWR SUPPLY SPARE PT2
FEEDER 8 FEEDER 9 FEEDER 10 FEEDER 11 FEEDER 12 ZRCY-YJV62-26/35kV OWNER:
3(1X70)mm2
PTR AUX TEMPORARY
IS 16 IS 17 IS 18 IS 19 IS 20 IS 21 IS 22 IS 23 S11-M-250/34.5,250kVA PWR SUPPLY
400V
IS 26 IS 25 IS 24 Ud=4%
630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz 630A,34.5kV,20kA/1S,60Hz Dyn11
630A 630A 630A 630A 630A 630A 630A 630A ZRC-YJV22-0.6/1kV ZRC-YJV22-0.6/1kV Project
RADOX 4GKW 3x3x1x240mm2 RADOX 4GKW 3x3x1x240mm2 RADOX 4GKW 3x3x1x240mm2 Title
Original Size
Drawing No.
A1
Rev. E
NOTES:
1. TERMINATION BETWEEN DISSIMILAR MATERIAL ( Cu )
SHALL BE DONE ONLY WITH BIMETALLIC LUGS SUITABLE FOR RATED
CURRENT ( WASHERS ARE NOT ACCEPTABLE )
2. THE DC CAPACITY OF THE PLANT WILL BE CALCULATED BASED ON THE
NAME PLATE RATING AND NOT ON FLASH TEST DATA.
MODULE TO BE PLANNED ACCORDINGLY
3. NEGATIVE TERMINAL OF DC SYSTEM SHALL BE GROUNDED INVERTER
THROUGH GFDI KIT.
4. REFER TO GF1508-SCSN-03-SLD-002 FOR THE CONFIGURATION OF THE MVSG.
IS - 1 TO 2 (TYP) LEGEND:
CENTRAL INVERTER
RELAY
50/51, 50/51N
INVERTER TRANSFORMER
THREE-POSITIONS FOUR WINDINGS
SWITCH DISCONNECTOR
NOTE 4
TRANSFORMER
1.8MVA
34.5KV/0.405-0.405KV 10kVA 405/400V
Dy11y11 Dyn5
TOTAL NO. OF STRINGS = 177 ( 310Wp) TOTAL NO. OF STRINGS = 177 ( 310Wp)
TOTAL NO. OF MODULES = 3717 (310WP) TOTAL NO. OF MODULES = 3717 (310WP)
IM IM
V V
Job Project
No. Revision: Drawn Manager Director Date
ON-SHORE CONTRACTOR:
FUSE 400A FUSE 400A P O W E R S Y S T E M S I N C
OFF-SHORE CONTRACTOR:
OWNER'S ENGINEER:
OWNER:
1 1 1 1 1 1 1 1 Project
XLPO/XLPO Cu
XLPO\XLPO Cu
XLPO/XLPO Cu
XLPO\XLPO Cu
SPARE
SPARE
21 21 21 21 21 21 21 21
Title
A1
Rev. C
NOTES:
1. TERMINATION BETWEEN DISSIMILAR MATERIAL ( Cu )
SHALL BE DONE ONLY WITH BIMETALLIC LUGS SUITABLE FOR RATED
CURRENT ( WASHERS ARE NOT ACCEPTABLE )
2. THE DC CAPACITY OF THE PLANT WILL BE CALCULATED BASED ON THE
NAME PLATE RATING AND NOT ON FLASH TEST DATA.
MODULE TO BE PLANNED ACCORDINGLY
3. NEGATIVE TERMINAL OF DC SYSTEM SHALL BE GROUNDED INVERTER
THROUGH GFDI KIT.
4. REFER TO GF1508-SCSN-03-SLD-002 FOR THE CONFIGURATION OF THE MVSG.
IS - 3 TO 26 (TYP)
LEGEND:
RELAY
50/51, 50/51N CENTRAL INVERTER
THREE-POSITIONS
SWITCH DISCONNECTOR INVERTER TRANSFORMER
FOUR WINDINGS
NOTE 4
TO AUXILIARY SUPPLY
TRANSFORMER
1.8MVA
34.5KV/0.405-0.405KV 10kVA 405/400V
Dy11y11 Dyn5
IM IM
V V
Job Project
No. Revision: Drawn Manager Director Date
ON-SHORE CONTRACTOR:
FUSE 400A FUSE 400A P O W E R S Y S T E M S I N C
OFF-SHORE CONTRACTOR:
OWNER'S ENGINEER:
OWNER:
1 1 1 1 1 1 1 1 Project
XLPO/XLPO Cu
XLPO\XLPO Cu
XLPO/XLPO Cu
XLPO\XLPO Cu
SPARE
SPARE
21 21 21 21 21 21 21 21
Scale NTS DO NOT SCALE
Drawn A. OCAMPO Designer P.J. POCHON
21 STRINGS WITH 21 (310Wp) 6 STRINGS WITH 21 (310Wp) 21 STRINGS WITH 21 (310Wp) 6 STRINGS WITH 21 (310Wp) Drafting Design
MODULES PER STRING MODULES PER STRING MODULES PER STRING MODULES PER STRING Check J. ANIEVAS Check R. MIRANDA
Approved
R. MIRANDA
TOTAL 24 MVPS Date 24.11.2015
This Drawing must not be used for Construction unless signed as Approved
Title
A1
Rev. C