Model 4Wg 100 - 800 HP Boilers: Table A3-8. 4Wg Low Nox Dimensions - Hot Water

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Model 4WG 100 800 HP Boilers

Table A3-8. 4WG Low NOx Dimensions - Hot Water


BOILER H.P. DIM 100 125 150 200 250 300 350 400 500 600 700/800 *800
See
LENGTHS
Note "C"
Overall Length A 176 200 189.62 223.62 229.62 253.62 250 270.63 276.63 311.63 304 331
Shell B 131 155 143 177 172.5 196.5 189.75 207.75 213.75 248.75 232.75 259.75
Base Frame C 110 124 122 156 150.13 174.13 167.25 185.25 188.25 223.25 207.25 234.25
Burner Extension D 41 41 42.62 42.62 53.12 53.12 56.25 58.88 58.88 58.88 67.25 67.25
Smokebox to Base F 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Rear Ring Flange to Base G 20.5 20.5 20.5 20.5 22 22 22 22 25 25 25 25
Smokebox to Return H 78 99 87 121 113.5 137.5 130.75 148.75 143 151.75 146.75 173.75
Smokebox to Outlet HH 103 124 112 146 139.5 163.5 156.75 174.75 179 187.75 182.75 209.75
WIDTHS
Overall Width I 82.5 76.5 80.25 80.25 89.5 89.5 99.25 99.25 116 117 122.5 122.5
I.D. Boiler J 60 60 67 67 78 78 85 85 96 96 106 106
Center to LWCO Controller K 37 37 40.75 40.75 46 46 49.5 49.5 55 55 60 60
Center to Lagging L 33 33 36.75 36.75 42 42 45.5 45.5 51 51 56 56
Base Outside M 52.5 52.5 51 51 64 64 60 60 71.88 71.88 74.75 74.75
Base Inside N 44.5 44.5 43 43 56 56 47 47 58.88 58.88 61.75 61.75
Center to Outside of FGR Duct NN 45.5 39.5 39.5 39.5 43.5 43.5 49.75 49.75 61 62 62.5 62.5
FGR Duct Size V 6 6 6 6 6 8 8 8 8 10 10 10
HEIGHTS
Base to Rear Davit OO 86.12 86.12 92.75 92.75 98.88 98.88 112.75 112.75 125.12 125.12 134.25 134.25
Base to Vent Outlet O 85 85 89.88 89.88 106 106 115 115 126 126 135.63 135.63
Base to Boiler Centerline P 46 46 50 50 56 56 61 61 67 67 71 71
Height of Base Frame Q 12 12 12 12 12 12 12 12 12 12 12 12
Base to Bottom of Boiler R 15.63 15.63 16.13 16.13 16.5 16.5 18 18 18.5 18.5 17.5 17.5
Base to Return & Outlet X 82.38 82.38 92.63 92.63 101.5 101.5 110 110 121.5 121.5 130.5 130.5
BOILER CONNECTIONS
Waterfill Connection (Both Sides) S 1.25 1.5 1.5 2 2 2 2.5 2.5 2.5 2.5 2.5 2.5
Water Return (See Note "A") T 4 6 6 6 8 8 8 10 10 12 12 12
Water Outlet (See Notes "A & B") U 4 6 6 6 8 8 8 10 10 12 12 12
Drain-Front & Rear W 1.5 1.5 1.5 2 2 2 2 2 2 2 2 2
Air Vent Y 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2
VENT STACK
Vent Stack Diameter (Flanged) BB 16 16 16 16 20 20 24 24 24 24 24 24
MINIMUM CLEARANCES
Rear Door Swing DD 36 36 40 40 46 46 50 50 55 55 60 60
Tube Removal - Front Only FF 96 120 108 142 132.5 156.5 148 166 169 204 188 215
MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM:
Thru Window or Door RD 234 258 261 295 307.5 331.5 337 355 377 412 411 438
Front of Boiler RF 263 311 291 359 351 399 388 424 438 508 481 535
WEIGHTS IN LBS
Normal Water Weight - 6,890 8,580 8,870 11,600 14,760 17,380 19,220 21,520 26,260 31,580 35,900 40,930
Approx. Shipping Weight - (30psig) - 10,860 12,080 13,090 15,260 19,110 21,050 24,760 27,640 33,295 38,150 42,320 46,300
Approx. Shipping Weight - (125psig) - 11,600 12,980 14,040 16,680 20,670 23,140 26,930 30,060 35,390 40,550 45,430 49,750

NOTES:
Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified
dimension diagram/drawing. All Connections are Threaded Unless Otherwise Indicated:
NOTE "A": ANSI 150 psig Flange
NOTE "B": Water Outlet includes 2" Dip Tube
NOTE "C": *800 hp w/ 4000 sq. ft. of heating surface

Section A3-12 Rev. 09-09


Model 4WG 100 800 HP Boilers

BOILER ALL DIMENSIONS IN INCHES


HP A B C D E
100-125 33 47 52 80 36
150-200 36.5 49 56 83 40
250-300 42 56 61 92 46
350-400 45.5 58 68 99 50
500-600 51 66 75 111 55
700-800 56 74 80 121 60

Figure A3-5. Space Required to Open Rear Head on Model 4WG

BOILER ALL DIMENSIONS IN INCHES


HP A B C D E
100 79.5 21.375 84.75 10 3
125 79.5 21.375 108.75 10 3
150 87.125 21.375 96.75 10 3
200 87.125 21.375 130.75 10 3
250 99 28.75 104.25 10 3
300 99 28.75 128.25 10 3
350 107.625 33.25 126 10 3
400 107.625 33.25 144 10 3
500 125.375 34.5 145 10 3
600 125.375 34.5 180 10 3
700-800 134.5 34.5 164 10 3
NOTE: A, B, and C dimensions may vary by 1 inch.
Figure A3-6. Model 4WG Lift Lug Locations

Section A3-13 Rev. 09-09


Model 4WG 100 800 HP Boilers

BOILER ALL DIMENSIONS IN INCHES


HP A B C D E F G X
100 6 9 110 39.5 57.5 4 44.5 8
125 6 9 124 39.5 57.5 4 44.5 8
150 6 9 122 38 56 4 43 8
200 6 9 156 38 56 4 43 8
250 6 9 150.125 51 69 4 56 11.5
300 6 9 174.125 51 69 4 56 11.5
350 6 12 167.25 41.5 65.5 6.5 47 11.5
400 6 12 185.25 41.5 65.5 6.5 47 11.5
500 6 12 188.25 53.375 77.375 6.5 58.875 10.5
600 6 12 223.25 53.375 77.375 6.5 58.875 10.5
700-800 6 12 207.25 56.25 80.25 6.5 61.75 10.5
NOTE:
6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides
increased inspection accessibility to the boiler and added height for washing down the area beneath the boiler.

Figure A3-7. Model 4WG Mounting Piers

PERFORMANCE DATA
Contact your local Cleaver-Brooks authorized representative for efficiencies.
Cleaver-Brooks 4WG boilers are available with the standard burner package, or optional
model Profire LE or Profire NT if NOx reductions of between 75 and <9 PPM on natural
gas are required, or 70 PPM on #2 oil with 0.02% fuel bound nitrogen.

Section A3-14 Rev. 09-09


Model 4WG 100 800 HP Boilers

ENGINEERING DATA
The following engineering information is provided for Model 4WG Boilers. Additional
detail is available from your local Cleaver-Brooks authorized representative.
Boiler Information
Table A3-11 shows steam volume and disengaging area for model 4WG boilers.
Table A3-12 lists quantity and outlet size for safety valves supplied on Model 4WG
steam boilers.
Table A3-13 lists quantity and outlet size for relief valves supplied on Model 4WG hot
water boilers.
Table A3-14 gives recommended steam nozzle sizes on Model 4WG Boilers.
Table A3-15 shows recommended non-return valve sizes for Model 4WG Boilers.
Blowdown Water Requirements
Some local codes require blowdown tanks to be constructed in accordance with
recommendations of the National Board of Boiler and Pressure Vessel Inspectors.
The National Boards recommendations base the size of the blowdown tank on the
removal of at least 4 inches of water from the boiler.
Table A3-9 lists the approximate quantity of water represented by 4 inches of water at
normal operating level for Cleaver-Brooks Model 4WG Boilers.
Burner/Control Information
Burner Characteristics
Maximum altitude for standard burners is shown in Table A3-16. Note that altitude
correction and burner changes are required for higher altitudes which may alter
dimensions, motor hp and gas pressures.
Gas-Fired Burners
Table A3-16 shows correction factors for gas pressure at elevations over 700 ft. above
sea level.
Table A3-17 shows minimum and maximum gas pressure requirements for Standard, FM
and IRI 4WG Boiler gas trains upstream of the gas pressure regulator.
For oversized or undersized gas trains or altitude above 2,000 feet, contact your local
Cleaver-Brooks authorized representative.
Fuel Connections - Gas
The local gas company should be consulted for requirements and authorization for
installation and inspection of gas supply piping. Installation of gas supply piping and
venting must be in accordance with all applicable engineering guidelines and regulatory
codes. All connections made to the boiler should be arranged so that all components
remain accessible for inspection, cleaning and maintenance.
A drip leg should be installed in the supply piping before the connection to the gas
pressure regulator. The drip leg should be at least as large as the inlet fitting supplied
with the boiler. Consideration must be given to both volume and pressure requirements
when choosing gas supply piping size. Refer to the boiler dimension diagram provided by
Cleaver-Brooks for the particular installation. Connections to the burner gas train should
be made with a union, so that gas train components or the burner may be easily
disconnected for inspection or service. Upon completion of the gas piping installation, the
system should be checked for gas leakage and tight shutoff of all valves.