Ceilector Steel Grid Installation Manual May 2015
Ceilector Steel Grid Installation Manual May 2015
Ceilector Steel Grid Installation Manual May 2015
Installation Manual
May 2015
Notes:
1. Load calculations1.1 and 1.2 are based on AS/NZS 2785:2000 Clause 3.3.5 (a). Load calculation. 1.2 is based on a minimum Service
Load of 3.0 kg/m as required by the Standard. The contractor is to confirm that this load will not be exceeded, or alter the calculation
accordingly. If Service Load U is NOT a requirement, use calculation 1.1 values only.
2. These tables apply to areas of the building that have no openings the outside, such as doors, windows, ducts etc. In all
other cases the appropriate design loading must be determined by the project structural engineer in accordance with
AS/NZS 2785:2000 Clauses 3.3.5 (b) or (c).
3. The Standard testing and installation for suspension is at 1200mm centres.
4. Heavy lighting or other mechanical service shall be supported on the main tees, included in the dead load 1.1 above, able to be supported
by the selected grid combination, and/or should be independently supported if greater than 10 kg (NZS4219).
5. All point loads shall be fixed under suspension point on Main Tees only and hanger capacity should be checked.
6. Loadings are laboratory tested in accordance with AS/NZS 2785 with a deflection limit of L/360. Maximum allowable system loads take
into account continiuous spans and are applicable for ceilings 2.4 metres or longer. For ceilings shorter than 2.4 metres use a minimum of two
hangers.
7. Seismic considerations for in-plane loads may take precedence in determining the required grid combination. Please contact us for more details.
19.9
Maximum allowable load kg / m
Dimension 600x600 mm
24 mm 24 mm 24 mm
Dimension 600x600 mm
24 mm x 24 mm 32.5 1.5
Dimension 1200x600 mm
24 mm 24 mm x
11.7
Dimension 600x600 mm
24 mm 24 mm 24 mm
Installation Overview
Main Runner
Standard installation: main runners spaced at 1200mm centres. For heavy ceiling panels main runners should be at
600mm centres (refer to Load Limits).
Cross Runner
Cross runners lock into the main runner punchings. An audible click confirms the cross runner is in place. For various
main and cross runners configurations please refer to Load Limits.
Wall Angle
Wall Angle is typically fixed up to 600mm centres (maximum) to walls or bulkheads.
Suspension
Suspension options are:
1. 5mm rod used in conjunction with the Atkar Hook Clip through the pre-punched hole
2. 2.5mm wire or 5mm galvanised rod, used in conjunction with the Atkar suspension clip
Ensure that hangers are not bent and that they are not fixed to, or closer than 150mm to the plenum services
i.e. sprinklers, ducting, pipes.
Warranty
Backed by CSR, Ceilector Steel Grid is warranted for 30 years when used as a system with OWA Ceiling Tiles.
When used alone, Ceilector Steel Grid is warranted for 15 years.
The following standards have been used in manufacturing and testing for compliance with the Australian Building Code:
AS/NZS 1170 - Structural design actions
AS 1170.4 - Earthquake loads (Australia)
AS 2946 - Suspended ceilings, recessed luminaries and air diffusers interface