BS en 1998-1 Na
BS en 1998-1 Na
BS en 1998-1 Na
NATIONAL ANNEX
UK National Annex to
Eurocode 8: Design of
structures for
earthquake resistance –
Part 1: General rules, seismic actions
and rules for buildings
ICS 91.120.25
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
© BSI 2008
Publication history
First published August 2008
Contents
Introduction 1
NA.1 Scope 1
NA.2 Nationally Determined Parameters 2
NA.3 Decisions on the status of the informative annexes 11
NA.4 References to non-contradictory complementary
information 11
Bibliography 12
List of tables
Table NA.1 – UK values for Nationally Determined Parameters
described in BS EN 1998-1:2004 2
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Summary of pages
This document comprises a front cover, an inside front cover,
pages i and ii, pages 1 to 12, an inside back cover and a back cover.
ii • © BSI 2008
Copyright British Standards Institution
This page deliberately left blank
Provided by IHS Markit under license with BSI - Uncontrolled Copy Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
No reproduction or networking permitted without license from IHS Not for Resale, 01/22/2018 00:42:04 MST
NA to BS EN 1998-1:2004
Introduction
This National Annex has been prepared by BSI Subcommittee B/525/8,
Structures in seismic regions. In the UK it is to be used in conjunction
with BS EN 1998-1:2004.
NA.1 Scope
This National Annex gives:
a) the UK decisions for the Nationally Determined Parameters
described in the following subclauses of BS EN 1998-1:2004:
NA to BS EN 1998-1:2004
UK decisions for the Nationally Determined Parameters described in
BS EN 1998-1:2004 are given in Table NA.1.
and TD defining horizontal and vertical elastic Further guidance is given in PD 6698.
response spectra in accordance with
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
3.2.2.1(4), Parameters S, TB, TC, TD defining shape of In the absence of deep geology effects, and for Type In the absence of site-specific information, the
3.2.2.2(1)P horizontal elastic response spectra. 1 spectra (where earthquakes that contribute most recommended values for Type 2 earthquakes may
to the seismic hazard defined for the site for the be used, but see also PD 6698.
purpose of probabilistic hazard assessment have a
surface-wave magnitude, Ms, greater than 5,5):
Ground type S TB (s) TC (s) TD (s)
A 1,0 0,15 0,4 2,0
B 1,2 0,15 0,5 2,0
C 1,15 0,20 0,6 2,0
D 1,35 0,20 0,8 2,0
E 1,4 0,15 0,5 2,0
In the absence of deep geology effects, and for
Type 2 spectra (where earthquakes that contribute
most to the seismic hazard defined for the site for
the purpose of probabilistic hazard assessment have
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
NA to BS EN 1998-1:2004
3.2.2.3(1)P Parameters avg, TB, TC, TD defining shape of Spectrum avg/ag TB (s) TC (s) TD (s) In the absence of site-specific information, the
vertical elastic response spectra. Type 1 0,90 0,05 0,15 1,0 recommended values for Type 2 earthquakes may
be used, but see also PD 6698.
Type 2 0,45 0,05 0,15 1,0
3.2.2.5(4)P Lower bound factor β on design spectral values. 0,2 Use the recommended value.
© BSI 2008 •
3
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
No reproduction or networking permitted without license from IHS
Provided by IHS Markit under license with BSI - Uncontrolled Copy
Copyright British Standards Institution
4 • © BSI 2008
NA to BS EN 1998-1:2004
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
4.2.3.2(8) Reference to definitions of centre of stiffness [None] Any appropriate method may be used.
and of torsional radius in multi-storey buildings Further guidance is given in PD 6698.
meeting or not conditions (a) and (b) of
BS EN 1998-1:2004, 4.2.3.2(8).
4.2.4(2)P Ratio ϕ of coefficient ψEi on variable mass Type of variable Storey Î Use the recommended values. Storeys occupied by
used in seismic analysis to combination coefficient action different tenants may be considered as
ψ2i for quasi permanent values of variable actions. independently occupied.
4.2.5(5)P Importance factor γI for buildings. Class I: γI =0,8 Where a value for the reference return
Class III: γI =1,2 period TNCR of 2 500 years has been adopted
Class IV: γI =1,4 for CC3 structures, γI=1 should be assumed.
Where TNCR has been assessed on a
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
4.3.3.1(8) Threshold value of importance factor, γI, relating to [None] 3D (spatial) analysis models are recommended for
the permitted use of analysis with two planar all consequence class CC3 buildings.
models.
4.4.2.5(2) Overstrength factor γRd for diaphragms. For brittle failure modes, such as shear, γRd =1,3. Use the recommended values.
For ductile failure modes, γRd =1,1.
4.4.3.2(2) Reduction factor ν for displacements at damage Class I & II: É =0,4 In consequence class CC3 buildings, storey drifts
limitation limit state. Class III & IV: É =0,5 should be checked against the specified limits
using the recommended values of reduction factor
ν.
5.2.1(5) Geographical limitations on use of ductility classes [None] There are no geographical limitations.
for concrete buildings.
5.2.2.2(10) qo-value for concrete buildings subjected to special Adjustment to qo-value is a factor in the An adjustment factor of up to 1,2 on qo is
Quality System Plan. range 1 to 1,2, with no recommended value permitted if a formal quality plan is applied to the
within this range. design, procurement and construction. The design
quality plan should include a peer review of the
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
NA to BS EN 1998-1:2004
Buildings with 4 or more storeys:
bw, min=0,25m
hw, min=0,5m
© BSI 2008 •
5
No reproduction or networking permitted without license from IHS
Provided by IHS Markit under license with BSI - Uncontrolled Copy
Copyright British Standards Institution
6 • © BSI 2008
NA to BS EN 1998-1:2004
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
5.8.2(4) Minimum thickness t min and reinforcement ratio t min = 0,2m Use the recommended values.
ρs, min of concrete foundation slabs. ρs, min= 0,2%
5.8.2(5) Minimum reinforcement ratio ρb, min of concrete ρb, min= 0,4% ρb, min= 0,2% in top face and 0,2% in bottom face.
foundation beams.
5.11.1.3.2(3) Ductility class of precast wall panel systems. DCM Use the recommended value.
5.11.1.4 Factor kp on q-factors of precast systems. kp = 1,0 for structures with connections Use the recommended values.
conforming to BS EN 1998-1:2004, 5.11.2.1.1,
5.11.2.1.2, or 5.11.2.1.3
kp = 0,5 for structures with other types of
connection
5.11.1.5(2) Ratio Ap of transient seismic action assumed during Ap = 0,3 unless otherwise specified by special In the absence of a site-specific assessment, use the
erection of precast structures to design seismic studies recommended value.
action defined in BS EN 1998-1:2004, Section 3.
5.11.3.4(7)e) Minimum longitudinal steel ρc, min in grouted ρc, min =1% Use the recommended value.
connections.
6.1.2(1) Upper limit of q for low-dissipative structural 1,5 2
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
6.2(7) Information as to how BS EN 1993-1-10:2005 – [None] The fracture toughness and through thickness
selection of steel for fracture toughness and properties of the steel should be selected on a
through thickness properties – may be used in the project-specific basis. Further guidance is given
seismic design situation. in PD 6698.
6.5.5(7) Reference to complementary rules on acceptable [None] Complementary rules for connection design may be
connection design. developed on a project-specific basis. Further
guidance is given in PD 6698.
6.7.4(2) Residual post-buckling resistance of compression γpb = 0,3 γpb = γpb* Nb,Rd (λbar)/ Npl,Rd
diagonals in steel frames with V-bracings. (γpb* times design buckling resistance over plastic
resistance)
γpb* = 0,7 for qu2
= 0,3 for qW5
For 2uqu5, γpb* = 0,3 may be assumed or refer
to PD 6698.
Further guidance is given in PD 6698.
7.1.2(1) Upper limit of q for low-dissipative structural 1,5 2
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
behaviour concept.
Limitations on structural behaviour concept. [None] No limitations on structural behaviour concept.
Geographical limitations on use of ductility classes [None] No geographical limitations.
for composite steel-concrete buildings.
7.1.3(1),(3) Material partial factors for composite steel- Use the γs values for the persistent and transient Use the recommended values.
concrete buildings in the seismic design situation. design situations.
7.1.3(4) Overstrength factor for capacity design of γov = 1,25 Use the recommended value.
composite steel-concrete buildings.
NA to BS EN 1998-1:2004
© BSI 2008 •
7
No reproduction or networking permitted without license from IHS
Provided by IHS Markit under license with BSI - Uncontrolled Copy
Copyright British Standards Institution
8 • © BSI 2008
NA to BS EN 1998-1:2004
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
7.7.2(4) Stiffness reduction factor for concrete part of a r=0,5 In the absence of special studies, use the
composite steel-concrete column section. recommended value.
8.3(1) Geographical limits on ductility class for timber [None] No geographical limits.
buildings.
9.2.1(1) Type of masonry units with sufficient robustness. [None] Any type of masonry unit listed in
BS EN 1996-1-1:2005, Table 3.1, is acceptable.
9.2.2(1) Minimum strength of masonry units. fb,min = 5N/mm2 (normal to bedface) Use the minimum values given in
fbh,min = 2N/mm2 (parallel to bedface) BS EN 1996-1-1:2005.
9.2.3(1) Minimum strength of mortar in masonry buildings. fm,min = 5N/mm2 (unreinforced or confined Use the minimum values given in
masonry) BS EN 1996-1-1:2005.
fm,min = 10N/mm2 (reinforced masonry)
9.2.4(1) Alternative classes for perpend joints in masonry. [None] Perpend joints fully grouted with mortar or
ungrouted joints with mechanical interlocking
between masonry units may be used. Ungrouted
joints without mechanical interlock may only be
used subject to appropriate validation.
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
9.3(2) Conditions for use of unreinforced masonry [None] There are no restrictions on the use of unreinforced
satisfying provisions of BS EN 1996-1:2005 alone. masonry that follows the provisions of
BS EN 1996-1:2005 alone.
9.3(2) Minimum effective thickness tef,min of unreinforced tef,min = 240 mm tef,min = 170 mm
masonry walls satisfying provisions of tef,min = 170 mm in cases of low seismicity
BS EN 1996-1:2005 alone.
9.3(3) Maximum value of ground acceleration ag,urm for ag,urm = 0,2 g ag,urm = 0,25 g
the use of unreinforced masonry satisfying
provisions of BS EN1998-1.
9.3(4), Table q-factor values in masonry buildings. Unreinforced masonry in Unreinforced masonry in
9.1 accordance with BS EN 1998-1: q = 1,5 accordance with BS EN 1998-1: q = 2,0
Confined masonry: q = 2,0 Confined masonry: q = 2,5
Reinforced masonry: q = 2,5 Reinforced masonry: q = 3,0
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
No reproduction or networking permitted without license from IHS
Provided by IHS Markit under license with BSI - Uncontrolled Copy
Copyright British Standards Institution
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
9.3(4), Table q-factors for buildings with masonry systems which [None] Enhanced values need to be justified on a
9.1 provide enhanced ductility. case-by-case basis.
9.5.1(5) Geometric requirements for masonry shear walls. Masonry type tef,min (hef /tef)max (l/h)min Use the recommended values.
(mm)
Unreinforced, with 350 9 0,5
natural stone units
Unreinforced, with 240 12 0,4
any other type of
units
Unreinforced, with 170 15 0,35
any other type of
units, in cases of low
seismicity
Confined masonry 240 15 0,3
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
NA to BS EN 1998-1:2004
9.6(3) Material partial factors in masonry buildings in the γm = 2/3 of value specified in National Annex Use the recommended values.
seismic design situation. to BS EN 1996-1-1:2005, but not less than 1,5
γs = 1,0
© BSI 2008 •
9
No reproduction or networking permitted without license from IHS
Provided by IHS Markit under license with BSI - Uncontrolled Copy
Copyright British Standards Institution
10 • © BSI 2008
NA to BS EN 1998-1:2004
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Table NA.1 UK values for Nationally Determined Parameters described in BS EN 1998-1:2004 (continued)
Subclause Nationally Determined Parameter Eurocode recommendation UK decision
9.7.2(1) Maximum number of storeys and minimum area of Acceleration at site u0,07 u0,10 u0,15 u0,20 Use the recommended values, unless justified on a
shear walls of “simple masonry building”. ag.S k ⋅g k ⋅g k ⋅g k ⋅g project-specific basis.Further guidance is given
in PD 6698.
Type of Number Minimum sum of
construction of cross-sections areas of
storeys horizontal shear walls in
(n)** each direction, as
percentage of the total
floor area per storey
(pA,min)
Unreinforced 1 2,0% 2,0% 3,5% n/a
masonry 2 2,0% 2,5% 5,0% n/a
3 3,0% 5,0% n/a n/a
4 5,0% n/a* n/a n/a
Confined 2 2,0% 2,5% 3,0% 3,5%
masonry 3 2,0% 3,0% 4,0% n/a
4 4,0% 5,0% n/a n/a
Not for Resale, 01/22/2018 00:42:04 MST
Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Bibliography
Standards publications
BS EN 1993-1-10:2005, Eurocode 3 – Design of steel structures –
Part 1-10: Material toughness and through-thickness properties
BS EN 1996-1-1:2005, Eurocode 6 – Design of masonry structures –
Part 1-1: General rules for reinforced and unreinforced masonry
structures
BS EN 1998-1:2004, Eurocode 8 – Design of structures for
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
earthquake resistance – Part 1: General rules, seismic actions and
rules for buildings
PD 6698:2008, Background paper to the UK National Annexes
to BS EN 1998-1, BS EN 1998-2, BS EN 1998-4, BS EN 1998-5 and
BS EN 1998-6
Other publications
[1] Institution of Structural Engineers: Manual for the seismic design
of steel and concrete buildings to Eurocode 8, London: publication
expected 2008.
12 • © BSI 2008
Copyright British Standards Institution
Provided by IHS Markit under license with BSI - Uncontrolled Copy Licensee=Aurecon - Bangkok, Thailand/5968556003, User=Wang, Thomas
No reproduction or networking permitted without license from IHS Not for Resale, 01/22/2018 00:42:04 MST
NA to BS EN 1998-1:2004
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---
Revisions
British Standards are updated by amendment or revision. Users of British Standards
should make sure that they possess the latest amendments or editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using this
British Standard would inform the Secretary of the technical committee responsible,
the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000 Fax: +44 (0)20 8996 7400
BSI offers members an individual updating service called PLUS which ensures that
subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001
Fax: +44 (0)20 8996 7001 Email: orders@bsigroup.com
You may also buy directly using a debit/credit card from the BSI Shop on the
Website http://www.bsigroup.com/shop.
In response to orders for international standards, it is BSI policy to supply the BSI
implementation of those that have been published as British Standards, unless
otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and international
standards through its Library and its Technical Help to Exporters Service. Various
BSI electronic information services are also available which give details on all its
products and services. Contact the Information Centre. Tel: +44 (0)20 8996 7111
Fax: +44 (0)20 8996 7048 Email: info@bsigroup.com
Subscribing members of BSI are kept up to date with standards developments and
receive substantial discounts on the purchase price of standards. For details of these
and other benefits contact Membership Administration. Tel: +44 (0)20 8996 7002
Fax: +44 (0)20 8996 7001 Email: membership@bsigroup.com
Information regarding online access to British Standards via British Standards Online
can be found at http://www.bsigroup.com/BSOL.
Further information about BSI is available on the BSI website at
http://www.bsigroup.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of
the publications of the international standardization bodies. Except as permitted
under the Copyright, Designs and Patents Act 1988 no extract may be reproduced,
stored in a retrieval system or transmitted in any form or by any means – electronic,
BSI Group Headquarters photocopying, recording or otherwise – without prior written permission from BSI.
389 Chiswick High Road, This does not preclude the free use, in the course of implementing the standard, of
London W4 4AL, UK necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
Tel +44 (0)20 8996 9001 written permission of BSI must be obtained.
Fax +44 (0)20 8996 7001 Details and advice can be obtained from the Copyright & Licensing Manager.
www.bsigroup.com/standards Tel: +44 (0)20 8996 7070 Email: copyright@bsigroup.com
--`,,`,,,,`,``,```,`,,`,,,``,```-`-`,,`,,`,`,,`---