Cooling Load Converting
Cooling Load Converting
Cooling Load Converting
Chiller efficiency depends on energy consumed. Absorption chillers are rated in fuel
consumption per ton cooling. Electric motor driven chillers are rated in kilowatts per ton cooling.
KW/ton = 12 / EER
KW/ton = 12 / (COP x 3.412)
COP = EER / 3.412
COP = 12 / (KW/ton) / 3.412
EER = 12 / KW/ton
EER = COP x 3.412
COP = 3.5
EER = 12
The term kW/ton is commonly used for larger commercial and industrial air-conditioning, heat
pump and refrigeration systems.
The term is defined as the ratio of energy consumption in kW to the rate of heat removal in tons
at the rated condition. The lower the kW/ton the more efficient the system.
kW/ton = Pc / Er (1)
where
The Coefficient of Performance - COP - is the basic parameter used to report efficiency of
refrigerant based systems.
The Coefficient of Performance - COP - is the ratio between useful energy acquired and energy
applied and can be expressed as
COP = Eu / Ea (2)
where
COP can be used to define both cooling efficiency or heating efficiency as for a heat pump.
Cooling - COP is defined as the ratio of of heat removal to energy input to the
compressor
Heating - COP is defined as the ratio of heat delivered to energy input to the compressor
COP can be used to define the efficiency at single standard or non-standard rated conditions, or
as a weighted average of seasonal conditions. The term may or may not include the energy
consumption of auxiliary systems such as indoor or outdoor fans, chilled water pumps, or
cooling tower systems.
COP can be treated as an efficiency where COP of 2.0 = 200% efficiency. For unitary heat
pumps, ratings at two standard outdoor temperatures of 47oF and 17oF (8.3oC and -8.3oC) are
typically used.
The Energy Efficiency Ratio - EER - is a term generally used to define cooling efficiency of
unitary air-conditioning and heat pump system.
EER = Ec / Pa (3)
where