SP1 Manual
SP1 Manual
SP1 Manual
Content
Ⅰ General information……………………………………………1
Ⅱ Product description…………………………………………… 2
Ⅲ System description…………………………………………… 3
Ⅳ Fault message………………………………………………… 9
2 Safety rules
- The controller can’t be installed in the room where easily inflammable and explosive mixtures (e.g.
gas or oil) are present or may occur.
- The controller can’t be installed in the location which exceeds its allowable environment condition.
- All operations which require opening the controller are only to be taken without the power supply.
And the operation should be carried out by a qualified specialist.
- Before connecting the electrical wire, make sure that the power supply matches the required
parameter.
- All devices connected to the controller must match the technical parameter of the controller.
- Once the controller is damaged or failure to work, please take it out of system and inform the supplier.
3 Liability waivers
- Improper installation or operation can cause damages to material and persons. The manufacturer
cannot monitor the compliance with these instructions or the circumstances and methods used
for installation, operation, utilization and maintenance of this device. Damage by mishandling or
improper installation on costumer site is immediately leading to warranty exclusion.
- As faults can never be excluded, we don’t offer a guarantee for the completeness of the drawings
and texts of this manual, they only represent some examples. They can only be used on own risk.
No liability is assumed for incorrect, incomplete or false information and the resulting damages.
- The manufacturer preserves the right to put changes to product, technical date or installation and
operation instructions without prior notice.
4 About Sensors
- Only original equipped Pt1000 temperature sensors can be matched the solar collector. It is equipped
with 1.5m silicone wire and suitable for all kinds of weather conditions. They can resist the
temperature up to 280℃. There is no need to distinguish the positive and negative charges when
connect them to the controller.
- Only original equipped NTC10K temperature sensors can be matched the storage and pipeline. It is
equipped with 1.5m PVC wire. They can resist the temperature up to 105℃. There is no need to
distinguish the positive and negative charges when connect them to the controller.
- All sensor wires can carry low voltage. In order to avoid inductive effects, the wires must not be laid
close to 230 V or 400 V cables (The min. distance should be 100mm).
- If external inductive effects exist, e.g. heavy current cables, overhead train cables, transformer
substations, radio and television devices, amateur radio stations or microwave devices, then the
wires for the sensors must be adequately shielded.
- Sensor wires can be extended to a maximum length of 100m. When it is extended to 50m, use
0.75mm 2 wire. When it is extended to 100m, use1.5 mm 2 wire.
- PT1000 and NTC10k sensors are different kinds of temperature sensors, measurement fault may
exist between these two at the same ambient temperature, but it doesn’t effect the system operation.
1
Intelligent controller series for solar water heating control system
Ⅱ Product description
1 Button
Button Function
Cancel set value
Adjust
System setting
Adjust
2 Operation regulations
- When connect to power, the default mode is system working mode.
- Press button to start the system data set mode. Press it again to convert to different set
choice. Every choice is corresponding to different signal display. Please see the description of
signals in the following instruction.
Press and buttons to adjust the set value, press button to switch on correlative
function or confirm the current set value.
Press button to cancel correlative function or cancel the current set value, then start the
system working mode.
- On the system data set mode, if not press any button within 15 seconds, the system will cancel
the current set value, start the system working mode.
- On the system working mode, press button to switch on or switch off the auxiliary heating
output. Press button to switch on or switch off the heat collecting function.
- On the system working mode, press button for 2 seconds to switch on or switch off the R1
output handily. Press button for 2 seconds to switch on or switch off the R2 output handily.
2
Intelligent controller series for solar water heating control system
Ⅲ System description
System 1
The standard split pressurized solar water heating system with 1 collector array and 1 storage.
Use electrical element as auxiliary heating device.
04:00-05:00
Three time periods Adjust the auto. working time period of auxiliary
10:00-10:00 00:00-23:50
on auxiliary heating heating
17:00-22:00
Storage keeping temp. 60℃ 45-75℃ Adjust the referenced temp. of auxiliary heating
Switch-on temp. difference 8℃ 5-20℃ Adjust the desired switch-on temp. difference
Switch-off temp. difference 4℃ 2-12℃ Adjust the desired switch-off temp. difference
When the storage reaches the desired
Overheating protection of
80℃ 50-95℃ overheating protection temp., temp. difference
storage
circulation will be switched off.
When the collector temp. is lower than the
System frost protection 3℃ 2-8℃ desired frost protection temp., this function will
be activated.
This function will be activated when a holiday is
Holiday function planed or when there is no need to use hot water
for a long time.
All the desired values (except Time display)
Factory default
can be set back to factory default.
When the collector is overheating, the system
System overheating
stops working, which to avoid the accessories
protection
to be destroyed.
To avoid the bacteria occur, the system takes
Anti-bacteria protection
the bacteria-killing process periodically.
3
Intelligent controller series for solar water heating control system
System 2
The standard split pressurized solar water heating system with 1 collector array and 1 storage.
Use gas boiler as auxiliary heating device.
04:00-05:00
Three time periods on Adjust the auto. working time period of auxiliary
10:00-10:00 00:00-23:50
auxiliary heating heating
17:00-22:00
Storage keeping temp. 60℃ 45-75℃ Adjust the referenced temp. of auxiliary heating
Switch-on temp. difference 8℃ 5-20℃ Adjust the desired switch-on temp. difference
Switch-off temp. difference 4℃ 2-12℃ Adjust the desired switch-off temp. difference
When the storage reaches the desired
Overheating protection of
80℃ 50-95℃ overheating protection temp., temp. difference
storage
circulation will be switched off.
When the collector temp. is lower than the
System frost protection 3℃ 2-8℃ desired frost protection temp., this function will
be activated.
This function will be activated when a holiday is
Holiday function planed or when there is no need to use hot water
for a long time.
All the desired values (except Time display)
Factory default
can be set back to factory default.
When the collector is overheating, the system
System overheating
stops working, which to avoid the accessories
protection
to be destroyed.
To avoid the bacteria occur, the system takes
Anti-bacteria protection
the bacteria-killing process periodically.
4
Intelligent controller series for solar water heating control system
System 3
The standard split pressurized solar water heating system with 1 collector array and 1 storage.
Use electrical heater as auxiliary heating device.
5
Intelligent controller series for solar water heating control system
System 4
The standard split pressurized solar water heating system with 1 collector array and 1 storage.
Use gas boiler as auxiliary heating device to realize heat collecting function.
04:00-05:00
Three time periods on Adjust the auto. working time period of auxiliary
10:00-10:00 00:00-23:50
auxiliary heating heating
17:00-22:00
Three time periods on Whole day Adjust the auto. Working time period of heat
00:00-23:50
heat collecting working collecting function
Reference temp. of heat Adjust the base reference temp. of heat
25℃ 15-65℃
collecting collecting function
Storage keeping temp. 60℃ 45-75℃ Adjust the reference temp. of auxiliary heating
Switch-on temp. difference 8℃ 5-20℃ Adjust the desired switch-on temp. difference
Switch-off temp. difference 4℃ 2-12℃ Adjust the desired switch-off temp. difference
When the storage reaches the desired
Overheating protection of
80℃ 50-95℃ overheating protection temp., temp. difference
storage
circulation will be switched off.
When the collector temperature is lower than
System frost protection 3℃ 2-8℃ the desired frost protection temp., this function
will be activated.
This function will be activated when a holiday is
Holiday function planed or when there is no need to use hot water
for a long time.
All the desired values (except Time display)
Factory default
can be set back to factory default.
When the collector is overheating, the system
System overheating
protection stops working, which to avoid the accessories
to be destroyed.
To avoid the bacteria occur, the system takes
Anti-bacteria protection
the bacteria-killing process periodically.
6
Intelligent controller series for solar water heating control system
System 5
The standard split pressurized solar pool system with 1 collector array and 1 pool.
Switch-on temp. difference 8℃ 5-20℃ Adjust the desired switch-on temp. difference
Switch-off temp. difference 4℃ 2-12℃ Adjust the desired switch-off temp. difference
When the collector temp. is lower than the
System frost protection 3℃ 2-8℃ desired frost protection temp., this function will
be activated.
All the desired values (except Time display)
Factory default
can be set back to factory defaults.
When the collector is overheating, the system
System overheating
stops working, which to avoid the accessories
protection
to be destroyed.
7
Intelligent controller series for solar water heating control system
System 6
The standard split pressurized solar pool system with 1 collector array, pool, and heat exchanger.
Switch-on temp. difference 8℃ 5-20℃ Adjust the desired switch-on temp. difference
Switch-off temp. difference 4℃ 2-12℃ Adjust the desired switch-off temp. difference
When the collector temp. is lower than the
System frost protection 3℃ 2-8℃ desired frost protection temp., this function will
be activated.
All the desired values (except Time display)
Factory default
can be set back to factory default.
When the collector is overheating, the system
System overheating
stops working, which to avoid the accessories
protection
to be destroyed.
8
Intelligent controller series for solar water heating control system
Ⅳ Fault message
Note 1:
If there are faults on the controller, please do not repair it by yourself. It should be taken by the
qualified specialist.
If there is a problem with the controller or temperature sensor, the fault signals will be displayed on
the screen as the following:
Note 2:
Use Ohmmeter to check the resistance value of sensors. According to the comparative with the
standard value, the fault sensor can be checked out. When check the resistance value, the sensor
should be cut off from the system. Small error can be allowed when compare the test value with the
standard value.
Ⅴ Packing list
9
Appendix
3. If the IP address of the customer is not in the same net segment as the above IP address,
“Start” → “Control board” → “Internet connection” → Click the right key “Local Area
should make sure that the computer can access the IP address of this product. And the
customer should have the basic knowledge about TCP/TP, to take setup processes.
Http://192.168.0.10
→Click “ Login”
4. Browser the web page, the customer can review or setup the information about the
product, such as the operation parameter, working state, and history data, and so on.