Simulação Sistema Altherma Piso Radiante
Simulação Sistema Altherma Piso Radiante
Simulação Sistema Altherma Piso Radiante
Produced on 28-01-2010 with Daikin Altherma Simulator V3.1.1 - database Central 6.8.8
Only the data published in the data book are correct. This program uses close approximations of these data.
R410A
S pace heating
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 1
1.3. Technical Details
Indoor EKHBH016BA3V3
Application
Function Heating only
Application Low temperature
Leaving water range heating 25,0 - 50,0°C
Technical data
Dimensions (WxHxD) 502x922x361 mm
Weight 48kg
Drain connection 18mm
Material Epoxy polyester painted galvanized steel
Electrical data
Power supply 230V 1ph
Fuse size 20A
Capacity electric backup heater 3,0 kW
Capacity steps 1
Outdoor ERHQ011BAW1
Performance
Nominal heating capacity 11,0 kW
COP 3,5
Operation range heating -20,0 - 35,0°C
Technical data
Dimensions (WxHxD) 900x1345x320 mm
Weight 108kg
Refrigerant R410A
Base charge 3,0kg
Sound data
Sound pressure 49dBA
Sound power 64dBA
Electrical data
Power supply 400V 3Nph
Fuse size 20A
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 2
1.4. Graphs
Required and available capacities
C apacity (kW)
16,0
12,8
E quilibrium point
9,6
6,4
3,2
System capacity:
Total heat generation capacity of the system, i.e. the sum of heat pump capacity and backup heater capacity.
Spare capacity:
The surplus in heat generation capacity when compared to the required heating capacity, i.e. the difference
between system capacity and required capacity.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 3
Heating period
Temperature (°C )
18,0
14,8
11,6
8,4
5,2
2,0 M onth
Jan F eb M ar A pr M ay Jun Jul A ug S ep O ct N ov Dec
The graph shows the simulated outdoor temperature variations within the defined heating months.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 4
Energy cost
1211
1120
840
560
292
280
The graph shows a comparison of the simulated annual running costs for Daikin Altherma, a gas boiler and an oil
boiler. The calculation is based upon the selected buildings yearly required thermal input, each systems coefficient
of performance (without pump) and the inputted energy prices.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 5
CO2 emission
7,4
5 4,6
3,5
1,6
2
The graph shows a comparison of the annual CO2 emissions for Daikin Altherma an electric heating system, a gas
boiler and an oil boiler sized to cover the yearly heat load for the simulated building. Neither Daikin Altherma nor
the electric heater will have any direct emissions. The emission from these systems is based on calculations
according to the average CO2 emission from the selected country's electricity production.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 6
Energy consumption per month
800
600
400
200
0 M onth
Jan F eb M ar A pr M ay Jun Jul A ug S ep O ct N ov Dec
H eat pump day H eat pump night E lectric heater day E lectric heater night
The graph shows the energy consumption (input) per month for the heat pump and back up heater. There is made
a separation between day and night operation to show the amount of energy consumption that falls under day and
night tariff.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 7
Energy cost per month
72
54
36
18
0 M onth
Jan F eb M ar A pr M ay Jun Jul A ug S ep O ct N ov Dec
The graph shows the running cost per month for Daikin Altherma according to the inputted electricity prices and the
power input as given in the graph "energy consumption per month".
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 8
Thermal output by source
1520
1140
760
380
0 O ut temp. (°C )
2,0 5,2 8,4 11,6 14,8 18,0
H eat pump E lectric heater
The graph shows the simulated thermal output in kWh for the heat pump and back up heater through one year. The
back up heater is only operational at low temperatures. The main portion of the output is at moderate temperatures
where the heat pump can cover the entire heating requirement.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 9
Emitted heat per m²
20
15
10
0 M onth
Jan F eb M ar A pr M ay Jun Jul A ug S ep O ct N ov Dec
The graph shows the total emitted heat per m² living surface per month. The required heat emission varies with the
buildings insulation standard and the weather conditions at the location.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 10
1.5. Supplementary Explanations
Design conditions:
The simulation is based on the assumption that the design room temperature is maintained 24h/24h. In actual
conditions, raising the room temperature setpoint above the design temperature will increase the heating demand
and thus the energy consumption. Lowering the room temperature setpoint (e.g. at night) will decrease the use of
energy.
Selection conditions:
The selection conditions for the LWT are adjustable in the program. Typical values are:
30 to 35°C (at design conditions) for floor heating,
30 to 45°C (at design conditions) for fan coil units and
40 to 50°C (at design conditions) for low temperature radiators.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 11
1.6. Field Settings Report
1st 2nd Setting name Date (*) Value (*) Date (*) Value (*) Default Range Step Unit
code code value
0 User permission level
00 User permission level 3 2-3 1 -
1 Weather dependent set point
00 Low ambient temperature (Lo_A) 2 -10 -20-5 1 °C
01 High ambient temperature (Hi_A) 18 15 10-20 1 °C
02 Set point at low ambient temperature (Lo_TI) 38 40 25-55 1 °C
03 Set point at high ambient temperature (Hi_TI) 25 25 25-55 1 °C
2 Disinfection function
00 Operation interval Fri Mon-Sun, - -
All
01 Status 1 (ON) 1 (ON) 0/1 - -
02 Start time 23:00 0:00-23:00 1:00 hour
03 Set point 70 40-80 5 °C
04 Interval 10 5-60 5 min
3 Auto restart
00 Status 0 (ON) 0 (ON) 0/1 - -
4 Backup heater operation
00 Status 1 (ON) 1 (ON) 0/1 - -
01 Priority 0 (OFF) 0 (OFF) 0/1 - -
5 Equilibrium temperature and space heating priority temperature
00 Equilibrium temperature status 1 (ON) 1 (ON) 0/1 - -
01 Equilibrium temperature 4 0 -15-20 1 °C
02 Space heating priority status 1 (ON) 0 (OFF) 0/1 - -
03 Space heating priority temperatures 6 0 -15-20 1 °C
04 Set point correction for sanitary water temperature 10 10 0-20 1 °C
6 DT for sanitary water heating
00 Start 5 5 1-20 1 °C
01 Stop 0 0 0-10 1 °C
7 Sanitary water step length
00 Sanitary water step length 3 3 2-4 1 °C
8 Sanitary water heating mode timer
00 Minimum running time 5 5 0-20 1 min
01 Maximum running time 30 30 20-95 5 min
02 Anti-recycling time 3 3 0-10 0,5 hour
03 Booster heating delay time 20 20 20-95 5 min
9 Cooling and heating set point ranges
00 Heating set point upper limit 38 55 37-55 1 °C
01 Heating set point lower limit 25 25 25-37 1 °C
02 Cooling set point upper limit - - - - 20 18-20 1 °C
03 Cooling set point lower limit - - - - 5 5-18 1 °C
C Solar priority mode
00 Solar priority mode settings 0 0/1 - -
D Restricted power supply condition mode
00 Not applicable. Do not change the default value 0 - - -
01 Not applicable. Do not change the default value 0 - - -
02 Not applicable. Do not change the default value 1 - - -
Note: The preferred settings of your Daikin Altherma system are mentioned in field settings report. For more details
see installation manual.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 12
Information Fiche for Customers
Efficient operation of this heat pump will only be ensured if the system is correctly matched to the heat loss of the
building and climate zone in which it is installed!
Always consult a competent installer and ask them to complete this fiche before purchasing!
This fiche should be completed by a qualified installer to provide you with information and recommendations about
the most suitable heat pump system for your home. In this way you will obtain the benefits of the very high
efficiency of heat pumps which concentrate the heat stored in the air, ground or water.
Some systems are also reversible and can produce cooling through extracting heat and ejecting it to the immediate
surroundings. Some systems may also provide hot water for sanitary use.
Heat pumps can be selected which can be used with most distribution systems including radiators, warm air and
under floor heating, and can be retrofitted to most existing heating systems with some suitable precautions as set
out below.
If your dwelling is more than 10 years old, before choosing a heat pump, it may be cost effective to first improve
your insulation, to reduce heat loss for heating you building or heat gain if you are looking to cool it. (It is actually
more efficient to fit a smaller heat pump in a well insulated building, for example) If you accept the installer’s
recommendations for improving insulation, the heat pump you buy should then be sized appropriately.
For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult
www.kyotoinhome.info
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 13
Customer name ................................................................................
Address ................................................................................
3. Primary heating
Heat pump manufacturer Daikin
Model ERHQ011BAW1
Heat source air
Distribution medium
Refrigerant R410A
Heat capacity (kW) 11,0
Heat output / electricity input 3,5
Seasonal efficiency over year 4,5
Capable of supplying domestic hot water? Yes
Auxiliary heating
Type EKHBH016BA3V3
Heat capacity (kW) 3,0
Cooling (if required)
Cooling capacity (kW)
Cold output / electricity input
Annual demands and emissions
Renewable energy (kWh)
Energy consumption (kWh) 3412
Carbon dioxide emissions (tonnes CO2) 1,6
Carbon dioxide savings (%) 78
Qualifications ..................................................
Company ..................................................
Address ................................................................................
Date ..................................................
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 14
Information Fiche for Installers
Efficient operation of this heat pump requires a competent installer to design the heating system to match the heat
loss of the building and climate zone and to install the system in accord with the manufacturers instructions.
Heat pumps have a very high efficiency because they only use energy to concentrate the heat present in the
ground, water or air. Some models can also operate in reverse mode and produce cooling by rejecting heat from a
dwelling. The information contained in this fiche will enable you to ensure that the benefits of the heat pump unit
are carried over to the collector and distribution systems and to complete the fiche which shall be given to the
customer to explain your choice.
Manufacturer Daikin
Model ERHQ011BAW1
Heat collector Brazed plate heat exchanger
Heat distribution medium
Heating capacity (kW) 14,0
Cooling capacity (kW) 11,7
Hot water supply Yes
Refrigerant type R410A / GWP = 1975
Noise level (dbA) 49
Parts available from date of sale (years) 10
Coefficient of performance (heating) 3,5
Specifying inlet and outlet temperatures (°C) LWC=34 (DT=5)
Energy efficiency ratio (cooling) 2,8
Specifying inlet and outlet temperatures (°C) LWE=18 (DT=5)
For retrofitting to existing heating systems, the heat pump should be selected to match the existing distribution
system which may be ducted warm air, hot water via radiators or underfloor heating. As the outlet temperature may
be lower than that of the boiler it will replace, it is essential to identify ways of reducing the heat loss or solar gain in
order to maintain the same size of distribution system.
Definitions
Coefficient of performance (COP) is the ratio of heat output to electricity input for a specified source and output
temperature.
Energy efficiency ratio (EER) is the ratio of cold output to electricity input for a specified source and output
temperature.
Seasonal coefficient of performance (SCOP) is the coefficient of performance averaged over the length of the
heating season for the heat pump system at a specified location.
Seasonal energy efficiency ratio (SEER) is the energy efficiency ratio averaged over the length of the cooling
season for the heat pump system at a specified location.
The primary energy ratio (PER) is given by: COP × 0,40 (or COP/2,5) for heat pumps with electrically driven
compressors and by COP × 0,91 (or COP/1,1) for heat pumps with gas driven compressors, where 0,40 is the
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 15
current European average electricity power generation efficiency including grid losses and 0,91 is the current
European average gas efficiency including distribution losses.
The manufacturer shall provide programs, tools and guidelines to help you perform the following calculations.
Climatic data should be appropriate for the geographical location of the building.
If the dwelling is more than 10 years old, then it will probably be cost effective to reduce the heat loss by increasing
the insulation level and to reduce the solar gain by restricting the direct rays of the sun during the summer. If the
customer accepts your recommendations then the system should be sized for the reduced heat loss and solar gain.
For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult
www.kyotoinhome.info
The heat loss of the building shall be calculated in accordance with national practice or using a suitable validated
computer program based on EN 832, the Euronorm for calculating heat loss. This heat loss should then be
compared with the current values required by building codes. For existing buildings, it is generally cost effective to
bring the insulation standard closer to current values before sizing the heat pump for the reduced heat loss.
If the system can also produce cooling then the solar gain of the building shall be calculated in accordance with
national practice or using a validated computer program. This gain should then be compared with the current
values required by building codes. For existing buildings, it is generally cost effective to reduce the solar gain
before sizing the heat pump for the reduced solar gain.
Page 16
Primary Energy Ratio (PER) and Annual CO2 emissions
The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the
calculation. CO2 emissions and savings to be calculated based on the primary energy usage.
Suitable courses are available in most Member States to enable installers to obtain appropriate national or
European accredited qualifications. Manufacturers shall either organise their own courses to assist installers with
using their equipment or work with local training institutes to provide such information as part of their courses.
For ground source heat pumps where a vertical bore hole is required, suitable courses for drillers are available in
some Member States.
The present report is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this report to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content. Specifications and prices are
subject to change without prior notice. Daikin explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or
interpretation of this report.
Page 17