Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Overcurrent and Overload Protection Using Protective Relays: Electricity and New Energy

Download as pdf or txt
Download as pdf or txt
You are on page 1of 73

Electricity and New Energy

Overcurrent and Overload Protection


Using Protective Relays
Courseware Sample
52173-F0
Order no.: 52173-10
First Edition
Revision level: 11/2016

By the staff of Festo Didactic

© Festo Didactic Ltée/Ltd, Quebec, Canada 2015


Internet: www.festo-didactic.com
e-mail: did@de.festo.com

Printed in Canada
All rights reserved
ISBN 978-2-89747-450-8 (Printed version)
ISBN 978-2-89747-452-2 (CD-ROM)
Legal Deposit – Bibliothèque et Archives nationales du Québec, 2015
Legal Deposit – Library and Archives Canada, 2015

The purchaser shall receive a single right of use which is non-exclusive, non-time-limited and limited
geographically to use at the purchaser's site/location as follows.

The purchaser shall be entitled to use the work to train his/her staff at the purchaser’s site/location and
shall also be entitled to use parts of the copyright material as the basis for the production of his/her own
training documentation for the training of his/her staff at the purchaser’s site/location with
acknowledgement of source and to make copies for this purpose. In the case of schools/technical
colleges, training centers, and universities, the right of use shall also include use by school and college
students and trainees at the purchaser’s site/location for teaching purposes.

The right of use shall in all cases exclude the right to publish the copyright material or to make this
available for use on intranet, Internet and LMS platforms and databases such as Moodle, which allow
access by a wide variety of users, including those outside of the purchaser’s site/location.

Entitlement to other rights relating to reproductions, copies, adaptations, translations, microfilming and
transfer to and storage and processing in electronic systems, no matter whether in whole or in part, shall
require the prior consent of Festo Didactic.

Information in this document is subject to change without notice and does not represent a commitment on
the part of Festo Didactic. The Festo materials described in this document are furnished under a license
agreement or a nondisclosure agreement.

Festo Didactic recognizes product names as trademarks or registered trademarks of their respective
holders.

All other trademarks are the property of their respective owners. Other trademarks and trade names may
be used in this document to refer to either the entity claiming the marks and names or their products.
Festo Didactic disclaims any proprietary interest in trademarks and trade names other than its own.
Safety and Common Symbols
The following safety and common symbols may be used in this manual and on
the equipment:

Symbol Description

DANGER indicates a hazard with a high level of risk which, if not


avoided, will result in death or serious injury.

WARNING indicates a hazard with a medium level of risk which,


if not avoided, could result in death or serious injury.

CAUTION indicates a hazard with a low level of risk which, if not


avoided, could result in minor or moderate injury.

CAUTION used without the Caution, risk of danger sign ,


indicates a hazard with a potentially hazardous situation which,
if not avoided, may result in property damage.

Caution, risk of electric shock

Caution, hot surface

Caution, risk of danger. Consult the relevant user documentation.

Caution, lifting hazard

Caution, hand entanglement hazard

Notice, non-ionizing radiation

Direct current

Alternating current

Both direct and alternating current

Three-phase alternating current

Earth (ground) terminal

© Festo Didactic 52173-10 III


Safety and Common Symbols

Symbol Description

Protective conductor terminal

Frame or chassis terminal

Equipotentiality

On (supply)

Off (supply)

Equipment protected throughout by double insulation or


reinforced insulation

In position of a bi-stable push control

Out position of a bi-stable push control

IV © Festo Didactic 52173-10


Table of Contents
Preface .................................................................................................................. IX
About This Manual ................................................................................................ XI
To the Instructor .................................................................................................. XIII

Introduction Overcurrent and Overload Protection Using Protective


Relays ............................................................................................ 1
DISCUSSION OF FUNDAMENTALS ....................................................... 1
Distinguishing overcurrent protection from overload
protection ................................................................................. 1
Evolution of the protective relay technology ............................ 2
Protective relay testing ............................................................ 5

Exercise 1 Overcurrent Protection ................................................................ 9


DISCUSSION ..................................................................................... 9
Introduction .............................................................................. 9
Overcurrent protection and overload protection using
fuses ...................................................................................... 10
Overcurrent protection and overload protection using LV
circuit breakers (MCBs and MCCBs)..................................... 15
Overcurrent protection and overload protection using
protective relays and HV circuit breakers .............................. 19
Instantaneous overcurrent relay ............................................ 21
Definite-time overcurrent relay .............................................. 23
Inverse definite minimum time (IDMT) overcurrent relay ...... 24
Standard time-current characteristics of IDMT
overcurrent relays .................................................................. 25
Overcurrent protection of a power transformer using a
numerical overcurrent relay ................................................... 28
Main features of protection implemented with numerical
overcurrent relays and HV circuit breakers ........................... 31
PROCEDURE .................................................................................. 32
Set up and connections ......................................................... 32
Operation of an instantaneous overcurrent relay .................. 33
Operation of a definite time overcurrent relay ....................... 39
Operation of an inverse definite minimum time (IDMT)
overcurrent relay .................................................................... 43
Overcurrent protection of a power transformer using a
numerical overcurrent relay ................................................... 49

© Festo Didactic 52173-10 V


Table of Contents

Exercise 2 Overcurrent and Overload Protection of AC Machines


and Power Transformers ........................................................... 57
DISCUSSION ................................................................................... 57
Introduction ............................................................................ 57
Thermal capability and power rating of ac machines and
power transformers ................................................................ 58
Machine or transformer thermal relays of the
temperature-sensor type ....................................................... 60
Machine or transformer thermal relays of the thermal-
replica type ............................................................................ 61
OC and OL protection of an ac machine or power
transformer using a numerical protective relay combining
the functions of ANSI devices no. 50 and no. 49 .................. 66
Using the IDMT overcurrent relay (ANSI device no. 51I)
function to achieve overload protection ................................. 69
PROCEDURE .................................................................................. 71
Set up and connections ......................................................... 71
Settings of a machine or transformer thermal relay of the
thermal-replica type ............................................................... 72
Operation of a machine or transformer thermal relay of
the thermal-replica type ......................................................... 76
Time-current characteristic of a machine or transformer
thermal relay of the thermal-replica type ............................... 83
Overcurrent protection ........................................................... 86

Exercise 3 Overcurrent Protection of Radial Feeders............................... 91


DISCUSSION ................................................................................... 91
Radial feeders........................................................................ 91
Protection of a radial feeder with overcurrent relays ............. 93
Discrimination based on coordination in current ................... 94
Discrimination based on coordination in time ........................ 98
Current settings ........................................................................ 99
Time settings ............................................................................ 99
Discrimination based on coordination in both time and
current .................................................................................. 101
Generic procedure to achieve time-current coordination
of IDMT overcurrent relays .................................................. 101
Information about the system .................................................101
Time-current characteristics of the IDMT overcurrent relays ..101
Current settings ......................................................................102
Time settings ..........................................................................102
Coordination of IDMT overcurrent relays with different
types of time-current characteristics .................................... 109
Relays with different types of time-current characteristics ......110
Coordination between an IDMT overcurrent relay and a
fuse ........................................................................................114

VI © Festo Didactic 52173-10


Table of Contents

PROCEDURE ................................................................................ 116


Set up and connections ....................................................... 116
Overcurrent protection of a radial feeder ............................. 116
Operation of relay C ............................................................... 119
Operation of relay B ............................................................... 122
Operation of relay A ............................................................... 125
Coordination verification......................................................... 128
Comparison with definite time overcurrent relays .................. 130
Ending the exercise ............................................................. 130

Appendix A Equipment Utilization Chart .................................................... 133

Appendix B Glossary of New Terms ........................................................... 135

Appendix C Introduction to the DIGSI 5 Software from Siemens ............ 139


Setting the language used in DIGSI 5 ................................. 140
Opening a project file ........................................................... 140
Displaying the single-line diagram ....................................... 142
Setting the frequency of operation of the protective relay ... 142
Setting the language used in the front panel display of
the protective relay .............................................................. 144
Accessing the settings of a specific protection function of
the relay ............................................................................... 144
Accessing the parameters of a test sequence .................... 146
Changing the ratio of current (or voltage) transformers ...... 147
Enabling/disabling fault display ........................................... 149
Loading a new configuration to the protective relay ............ 150
Restarting the protective relay in the simulation (test)
mode .................................................................................... 152
Updating the test environment............................................. 155
Starting a test sequence ...................................................... 155
Downloading a fault record from the protective relay .......... 157
Displaying the signals stored in a fault record ..................... 158
Restarting the protective relay in the process (normal
operation) mode................................................................... 161

Appendix D Protective Relay LED Identification Labels ........................... 163

Appendix E Electrical Graphic Symbols (IEC and ANSI) .......................... 165

Index .................................................................................................................. 167


Acronyms ........................................................................................................... 169
Bibliography ....................................................................................................... 171

© Festo Didactic 52173-10 VII


Preface
The production of energy using renewable natural resources such as wind,
sunlight, rain, tides, geothermal heat, etc., has gained much importance in recent
years as it is an effective means of reducing greenhouse gas (GHG) emissions.
The need for innovative technologies to make the grid smarter has recently
emerged as a major trend, as the increase in electrical power demand observed
worldwide makes it harder for the actual grid in many countries to keep up with
demand. Furthermore, electric vehicles (from bicycles to cars) are developed and
marketed with more and more success in many countries all over the world.

To answer the increasingly diversified needs for training in the wide field of
electrical energy, the Electric Power Technology Training Program was
developed as a modular study program for technical institutes, colleges, and
universities. The program is shown below as a flow chart, with each box in the
flow chart representing a course.

The Electric Power Technology Training Program.

© Festo Didactic 52173-10 IX


Preface

The program starts with a variety of courses providing in-depth coverage of basic
topics related to the field of electrical energy such as ac and dc power circuits,
power transformers, rotating machines, ac power transmission lines, and power
electronics. The program then builds on the knowledge gained by the student
through these basic courses to provide training in more advanced subjects such
as home energy production from renewable resources (wind and sunlight), large-
scale electricity production from hydropower, large-scale electricity production
from wind power (doubly-fed induction generator [DFIG], synchronous generator,
and asynchronous generator technologies), smart-grid technologies (SVC,
STATCOM, HVDC transmission, etc.), storage of electrical energy in batteries,
and drive systems for small electric vehicles and cars.

We invite readers of this manual to send us their tips, feedback, and


suggestions for improving the book.

Please send these to did@de.festo.com.


The authors and Festo Didactic look forward to your comments.

X © Festo Didactic 52173-10


About This Manual

Manual objectives

When you have completed this manual, you will be familiar with the operation
and settings of the instantaneous (ANSI device no. 50), definite-time (ANSI
device no. 51DT), and inverse definite minimum time (ANSI device no. 51I)
overcurrent relays. You will be able to adjust the settings of an overcurrent relay
to obtain a specific time-current characteristic. You will know applications where
it is common to use overcurrent relays and high-voltage circuit breakers in
conjunction to achieve overcurrent protection of electrical equipment. You will be
familiar with the operation and settings of the machine or transformer thermal
relay (ANSI device no. 49) of the temperature-sensor type or the thermal-replica
type. You will know how to combine protection functions in a numerical protective
relay to achieve overcurrent and overload protection of an ac machine or a power
transformer. You will also know how to implement overcurrent protection of a
radial feeder using either definite-time overcurrent relays or inverse definite
minimum time (IDMT) overcurrent relays. You will be able to use the internal
relay test system of a numerical protective relay to assess that the relay operates
as expected.

Safety considerations

Safety symbols that may be used in this manual and on the equipment are listed
in the Safety Symbols table at the beginning of the manual.

Safety procedures related to the tasks that you will be asked to perform are
indicated in each exercise.

Make sure that you are wearing appropriate protective equipment when
performing the tasks. You should never perform a task if you have any reason to
think that a manipulation could be dangerous for you or your teammates.

Prerequisite

As a prerequisite to this course, you should have read the manuals titled DC
Power Circuits, part number 86350, Single-Phase AC Power Circuits, part
number 86358, Single-Phase Power Transformers, part number 86377,
Three-Phase AC Power Circuits, part number 86360, and Three-Phase
Transformer Banks, part number 86379.

Systems of units

Units are expressed using the International System of Units (SI) followed by units
expressed in the U.S. customary system of units (between parentheses).

© Festo Didactic 52173-10 XI


To the Instructor
You will find in this Instructor Guide all the elements included in the Student
Manual together with the answers to all questions, results of measurements,
graphs, explanations, suggestions, and, in some cases, instructions to help you
guide the students through their learning process. All the information that applies
to you is placed between markers and appears in red.

Accuracy of measurements

The numerical results of the hands-on exercises may differ from one student to
another. For this reason, the results and answers given in this manual should be
considered as a guide. Students who correctly performed the exercises should
expect to demonstrate the principles involved and make observations and
measurements similar to those given as answers.

Detailed procedure in Exercise 1

It is recommended to perform the exercises in the order proposed in this manual,


as Exercise 1 features more detailed explanations than the rest of the exercises.

© Festo Didactic 52173-10 XIII


Introduction

Overcurrent and Overload Protection Using Protective Relays

MANUAL OBJECTIVE When you have completed this manual, you will be familiar with the operation
and settings of the instantaneous (ANSI device no. 50), definite-time (ANSI
device no. 51DT), and inverse definite minimum time (ANSI device no. 51I)
overcurrent relays. You will be able to adjust the settings of an overcurrent relay
to obtain a specific time-current characteristic. You will know applications where
it is common to use overcurrent relays and high-voltage circuit breakers in
conjunction to achieve overcurrent protection of electrical equipment. You will be
familiar with the operation and settings of the machine or transformer thermal
relay (ANSI device no. 49) of the temperature-sensor type or the thermal-replica
type. You will know how to combine protection functions in a numerical protective
relay to achieve overcurrent and overload protection of an ac machine or a power
transformer. You will also know how to implement overcurrent protection of a
radial feeder using either definite-time overcurrent relays or inverse definite
minimum time (IDMT) overcurrent relays. You will be able to use the internal
relay test system of a numerical protective relay to assess that the relay operates
as expected.

DISCUSSION OUTLINE The Discussion of Fundamentals covers the following points:

ƒ Distinguishing overcurrent protection from overload protection


ƒ Evolution of the protective relay technology
ƒ Protective relay testing

DISCUSSION OF Distinguishing overcurrent protection from overload protection


FUNDAMENTALS
The objective of overcurrent protection is to prevent excessive current flow in
an electric power circuit from damaging the circuit or from initiating fire in the
circuit that could lead to more serious damage and even endanger people's lives.
In this statement, the term “excessive current flow” refers to the flow of a current
whose value greatly exceeds the nominal full-load current of the circuit, like the
current resulting from a short-circuit. Overcurrent protection works by first
detecting excessive current flow in the protected circuit and then opening the
path through which the excessive current flows as quickly as possible.

The objective of overload protection is to prevent damage to a component in an


electric power circuit when this component is subjected to prolonged overload.
When a component (e.g., a power transformer, an induction motor) is
overloaded, the value of the current flowing in the component exceeds the
nominal full-load current of the component to a certain extent. Consequently, the
heating effect due to current flow in the component (this effect is proportional
to I2) is increased and the component starts to overheat, causing its temperature
to increase. Operation under overload conditions for an extended period causes
the component's temperature to eventually increase beyond safe limits and
cause damage to the component. The larger the severity of the overload (i.e., the
more the nominal full-load current of the component is exceeded), the lower the

© Festo Didactic 52173-10 1


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

time required for overheating to cause damage to the component. Overload


protection can be achieved by first detecting when the current flowing through the
protected component exceeds the nominal full-load current and then
disconnecting the component from the power source before overheating causes
damage to the component (i.e., before the component's temperature goes
beyond safe limits).

a An overload is a form of overcurrent since it causes the value of the current


flowing through a component to exceed the nominal full-load current of the
component. In the rest of this manual, however, the term overcurrent is used
only to refer to current flow that greatly exceeds the nominal full-load current of
a circuit (e.g., current flow due to a short-circuit), unless otherwise notified.

With the objective of overcurrent protection being different from that of overload
protection, it is common to apply these two types of protection to the same
electric power circuit. Overcurrent protection can be achieved using a variety of
means: fuses, low-voltage (LV) circuit breakers like miniature circuit breakers
(MCBs) and molded-case circuit breakers (MCCBs), protective relays used in
conjunction with high-voltage (HV) circuit breakers, etc. Overload protection can
be achieved using a contactor operated by a device including a thermal-overload
detection function as well as by using any one of the means mentioned above.
The means selected to achieve overcurrent and/or overload protection in a
particular application mainly depends on the technical requirements of the
application as well as on economical considerations. This manual focuses on
overcurrent protection and overload protection achieved with protective relays
used in conjunction with HV circuit breakers.

Evolution of the protective relay technology

A single-line diagram is a A protective relay is an intelligent device that detects faults or abnormal operating
simplified means of repre- conditions (e.g., an overload) in an electric power circuit and makes an HV circuit
senting a three-phase elec- breaker (or several HV circuit breakers) open to isolate the faulty portion of the
tric power circuit in which circuit and avoid or limit damage to the circuit. To detect a fault or an abnormal
each three-phase connec- operating condition, the protective relay generally measures currents in the
tion is represented by a electric power circuit via current inputs. However, some protective relays
single line instead of three measure both currents and voltages in the electric power circuit via current and
lines and each three-phase voltage inputs while some other protective relays measure only circuit voltages
(three-pole) device is repre- via voltage inputs. Control (opening) of the HV circuit breaker is achieved by
sented by its single-pole actuating a set of contacts in the protective relay upon detection of a fault or an
symbol instead of its three- abnormal operating condition in the electric power circuit. Figure 1 is a simplified
pole symbol. Single-line single-line diagram showing the connection of a protective relay and an HV
diagrams are thus simpler circuit breaker used in conjunction to protect a three-phase electric power circuit.
than conventional diagrams, Notice that the current and voltage inputs of the protective relay are connected to
and consequently, make it the electric power circuit via current and voltage transformers. These
easier to understand the transformers are required to match the current and voltage levels in the electric
various paths for power
power circuit with the current and voltage ratings of the protective relay inputs.
flow.

2 © Festo Didactic 52173-10


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

Current HV circuit breaker


transformers
From
power To load
source

Voltage
transformers Operating
mechanism

Open
command

Control
Current unit
inputs Protective
relay

Trip
output

Voltage
inputs

Figure 1. Connection of a protective relay and HV circuit breaker to a three-phase electric


power circuit.

The use of protective relays to protect electric power circuits dates back to the
beginning of the 20th century. The first protective relays were electromechanical
units. In any electromechanical protective relay, the protection function (e.g., the
time-current characteristic of an overcurrent protective relay) is implemented
using electromechanical devices. The operation of an electromechanical
protective relay can be summarized as follows: currents and/or voltages
measured in an electric power circuit via current transformers and/or voltage
transformers are applied to coils mounted on magnetic cores in the relay to
produce a mechanical force. This force is used to actuate the relay contacts.
When the mechanical force produced in the relay is strong enough to overcome
a counteracting force in the relay (e.g., the force provided by a spring), the relay
contacts are actuated.

Electromechanical relays, though reliable, had a few weaknesses. They applied


a high load (burden) on the current transformers and/or voltage transformers.
They had a long operating time due to the inertia of the moving parts used in the
relay. They also had a high maintenance cost. In the early 1960s, static
protective relays appeared and gradually replaced most of the electromechanical
relays in service, mainly because they provided shorter operating times than
electromechanical protective relays and reduced the load applied to current
transformers and/or voltage transformers. In a static protective relay, the
protection function is implemented with solid-state analog circuits (i.e., electronic
circuits with no moving parts) instead of electromechanical components. The
improved operating times and the reduction in the load applied to current
transformers and/or voltage transformers achieved in static protective relays are
largely due to this change in relay technology.

© Festo Didactic 52173-10 3


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

Static protective relays, though considered more efficient than electromechanical


protective relays, also have weaknesses of their own. Their operation requires a
highly reliable source of electric power and is sensitive to both interference and
ambient temperature. Some static protective relays are still in use today, but
replacement of these relays began in the middle of the 1980s when the first
digital protective relays became available. In a digital protective relay, the
measured currents and/or voltages are first sampled and converted to digital
form, then a microprocessor is used to implement the protection function instead
of electromechanical devices or solid-state analog circuits. The use of a
sophisticated algorithm in the microprocessor allows the protection function to be
implemented with greater accuracy and generally results in a wider range of
settings. Also, the presence of a microprocessor in a digital protective relay
allows communication with a computer for relay programming, analysis of
recorded data, etc. In other words, digital protective relays are clearly superior to
electromechanical and static protective relays in terms of both performance and
functionality. Because of these advantages, many digital protective relays are
currently in use to protect electric power circuits of all kinds. However, digital
protective relays should eventually be superseded by numerical protective relays.

The numerical protective relays are the natural evolution of the digital protective
relays resulting from progress in computer technology. A numerical protective
relay (see Figure 2) uses at least one digital signal processor (DSP) instead of
a single microprocessor to implement the protective relay function. This results in
operating times shorter than those that can be achieved using digital protective
relays. Furthermore, this allows several protection functions (e.g., overcurrent
protection and overload protection) to be implemented in the same protective
relay. This also allows the implementation of logic functions (e.g., interlocking
between a circuit breaker and its associated disconnecting switches in an electric
power substation) in the protective relay. In short, numerical protective relays
provide high-performance protection while being cost effective since several
protection functions can be performed by a single unit. Consequently, numerical
protective relays are now commonly selected to replace older protective relays in
existing installations as well as to implement protection systems in new
installations.

Figure 2. Numerical protective relay.

4 © Festo Didactic 52173-10


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

Protective relay testing

The main task of a protective relay is to protect a particular element in an electric


power system (e.g., a synchronous generator, a power transformer, a
transmission line) against specific faults and/or abnormal operating conditions.
Various settings in the protective relay must be adjusted to properly adapt the
protection to the characteristics of both the electric power system and the
element to be protected. Once this is done, protective relay testing should be
performed before the relay is definitely put into service. In short, protective relay
testing consists of conducting the tests necessary to assess that the protective
relay operates properly under certain specific faults and/or abnormal operating
conditions. Traditionally, this task is achieved using a relay test system.

A relay test system is an instrument which mainly consists of several (generally 3


to 6) ac current sources and several (generally 3) ac voltage sources. These
sources are able to supply ac currents and voltages of the magnitude required to
drive the current and voltage inputs of protective relays of any type of technology.
Furthermore, the magnitude and phase angle of the current produced by each ac
current source can be adjusted. Similarly, the magnitude and phase angle of the
voltage produced by each ac voltage source can be adjusted. A generic
procedure for protective relay testing using a relay test system is summarized
below.
x The current and/or voltage inputs of the protective relay to be tested are
connected to ac current sources and/or ac voltage sources of the relay
test system. Figure 3 shows the connection of a relay test system to a
protective relay having three current inputs and three voltage inputs.
x The relay test system is used to produce currents and/or voltages whose
magnitudes and phase angles are identical to those that the protective
relay would measure under a specific fault condition or abnormal
operating condition.
x The response of the protective relay to the test currents and/or voltages
is recorded, then analyzed to assess that the protective relay operates
properly (i.e., as expected according to the set characteristic of the
protection function).

© Festo Didactic 52173-10 5


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

Relay test system Protective relay

Phase A

AC
current Phase B Current
sources inputs

Phase C
Trip
output

Phase A

AC
voltage Phase B Voltage
sources inputs

Phase C

Figure 3. Connection of a relay test system to a protective relay.

The procedure above should be repeated for each of the specific fault conditions
or abnormal operating conditions for which the protective relay should operate
(i.e., actuate its trip output contacts).

Some numerical protective relays (e.g., relays from the Siemens SIPROTEC® 5
series) include an internal relay test system. This allows protective relay testing
to be performed without the need for an external relay test system, which is
generally expensive. The simplified block diagram of a numerical protective relay
including an internal relay test system is shown in Figure 4.

6 © Festo Didactic 52173-10


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

Trip
DSP output

Mode
selector To communication port
Normal Test
Internal relay test system
AC current inputs

Phase A A
A/D

From
secondaries Phase B B Digitized-output
of current A/D ac current
transformers sources

Phase C C
A/D

AC voltage inputs

Phase A A
A/D

From Digitized-output
Phase B B
secondaries A/D ac voltage
of voltage sources
transformers

Phase C C
A/D

To DSP

Communication port

External computer

Figure 4. Simplified block diagram of a numerical protective relay including an internal relay
test system.

© Festo Didactic 52173-10 7


Introduction – Overcurrent and Overload Protection Using Protective Relays  Discussion of Fundamentals

The numerical protective relay shown in Figure 4 has three current inputs and
three voltage inputs. In normal operation (Mode selector in the Normal position),
the current or voltage at each input is sampled at regular time intervals and
converted to digital format by six analog-to-digital (A/D) converters. A continuous
stream of data is thus obtained for each of the currents and voltages applied to
the inputs of the numerical protective relay. Data coming from all A/D converters
is routed to a digital signal processor (DSP) which implements the protection
function(s).

To perform relay testing, the protective relay is switched to the test mode (Mode
selector in the Test position in Figure 4). In test mode, data produced by the
internal relay test system is routed to the DSP instead of data coming from the
A/D converters. The internal relay test system consists of three ac current
sources and three ac voltage sources. The output of each of these sources is
readily in digital format and is routed to the digital signal processor (DSP). An
external computer connected to the protective relay is used to control the
magnitude and phase angle of each of the currents and voltages produced by the
sources in the internal relay test system. This allows currents and voltages
whose magnitudes and phase angles are identical to those of the currents and
voltages measured under any specific fault condition or abnormal operating
condition to be easily reproduced. The response of the protection function(s)
implemented in the DSP to the currents and voltages generated by the internal
relay test system is sent to the external computer connected to the numerical
protective relay for display purposes. Analyzing this response allows verifying
whether or not the numerical protective relay operates as expected.

8 © Festo Didactic 52173-10


Sample Exercise
Extracted from
the Student Manual
and the Instructor Guide
This page should be left blank
Exercise 1

Overcurrent Protection

EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with overcurrent and
overload protection of power lines, power transformers, and ac motors
implemented with fuses or low-voltage circuit breakers. You will know the
operation and settings of the instantaneous (ANSI device no. 50), definite-
time (ANSI device no. 51DT), and inverse definite minimum time (ANSI
device no. 51I) overcurrent relays. You will be able to adjust the settings of an
overcurrent relay to obtain a specific time-current characteristic. You will know
applications where it is common to use overcurrent relays and high-voltage
circuit breakers in conjunction to achieve overcurrent protection of electrical
equipment. You will be able to use the internal relay test system of a numerical
protective relay to assess that the relay operates as expected.

DISCUSSION OUTLINE The Discussion of this exercise covers the following points:

ƒ Introduction
ƒ Overcurrent protection and overload protection using fuses
ƒ Overcurrent protection and overload protection using LV circuit breakers
(MCBs and MCCBs)
ƒ Overcurrent protection and overload protection using protective relays
and HV circuit breakers
ƒ Instantaneous overcurrent relay
ƒ Definite-time overcurrent relay
ƒ Inverse definite minimum time (IDMT) overcurrent relay
ƒ Standard time-current characteristics of IDMT overcurrent relays
ƒ Overcurrent protection of a power transformer using a numerical
overcurrent relay
ƒ Main features of protection implemented with numerical overcurrent
relays and HV circuit breakers

DISCUSSION Introduction

As mentioned in the introduction of this manual, overcurrent protection and


overload protection each can be achieved using a variety of means: fuses,
low-voltage (LV) circuit breakers like miniature circuit breakers (MCBs) and
molded-case circuit breakers (MCCBs), protective relays used in conjunction with
high-voltage (HV) circuit breakers, etc. Each of these three means of achieving
overcurrent protection and overload protection are examined in this discussion.
However, note that due to the abundance of material, the present discussion
focuses on overcurrent protection implemented with overcurrent relays.
Combined overcurrent and overload protection using protective relays is
discussed more extensively in the next exercise of this manual.

© Festo Didactic 52173-10 9


Exercise 1 – Overcurrent Protection  Discussion

Overcurrent protection and overload protection using fuses


A fuse is a two-terminal electric component. The two terminals of the fuse are
interconnected by a fusible element that consists of a metallic (nickel-chrome and
silver are both commonly used) wire or strip, enclosed in an insulating sleeve
(generally cylindrical). The fusible element has very low resistance, thereby
allowing the fuse to be connected in series with a component in an electric power
circuit without perturbing the circuit operation. However, when the current flowing
through the fuse exceeds a certain value, the fusible element heats up
considerably and eventually starts to melt. After a certain time, the fusible
element has melted completely, thereby breaking the electric path between the
fuse terminals and interrupting current flow. This feature enables a fuse
connected in series with an electric power circuit to protect the circuit against
overcurrent, and possibly, against overload too. Once the fusible element in a
fuse has melted completely, the fuse is said to have blown. After the cause of
overcurrent or overload has been corrected, the blown fuse must be replaced
with a new unit having the same specifications. Figure 5 shows fuses of various
sizes used for different applications.

Figure 5. Fuses of different sizes. The small ones are typically used in electronic devices,
whereas the larger one is more characteristic of a power utility application.

The time required for the fusible element in a fuse to melt completely and the
electric path to break, which is commonly referred to as the total clearing time,
decreases with the magnitude of the current flowing through the fuse.
Consequently, the greater the current flowing through the fuse, the shorter the
total clearing time. Figure 6 shows an example of the time-current characteristic
of a fuse, i.e., the relationship between the current flowing through a fuse and the
total clearing time. The time-current characteristic of a fuse is also commonly
referred to as the inverse-time characteristic or simply the inverse characteristic
of the fuse because the total clearing time varies inversely with the value of the
current flowing through the fuse. Note that the total clearing time becomes infinite
when the current decreases to a certain value. This is because below this value,
the current flowing through the fuse is not sufficient to make the fusible element
melt, thereby preventing the fuse from interrupting current. The minimum value of
current required for the fusible element to start melting is known as the minimum
melting current. The current rating of the fuse, i.e., the maximum value of current
that can flow through the fuse continuously without causing the fuse to blow, is
necessarily lower than the minimum melting current of the fusible element.

10 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

100

10

Total clearing time (s)

0.1

0.01
10 100 1000 10 000
Current (A)

Figure 6. Time-current characteristic of a 30 A fuse.

Fuses are commonly used to protect power lines in distribution networks and
industrial applications. In this case, the fuse provides overcurrent protection of
the power line only. For this purpose, the current rating of the fuse should be
several times the nominal full-load current of the power line to be protected (e.g.,
5 times [500%] the nominal full-load current). Power lines in distribution networks
and industrial applications generally have a radial structure and are powered at
one end only. Such power lines are commonly referred to as radial feeders.
Overcurrent protection of radial feeders using protective relays is covered in
Exercise 3 of this manual.

Fuses are also commonly used to protect power transformers in distribution


networks and industrial applications. For instance, a single fuse connected in
series with the primary winding of a single-phase power transformer can be used
(minimally) to provide both overcurrent (OC) and overload (OL) protection of the
transformer, as shown in Figure 7. Figure 8 shows a pole-mounted secondary
distribution transformer with its OC fuse.

© Festo Didactic 52173-10 11


Exercise 1 – Overcurrent Protection  Discussion

To achieve proper overload protection, the current rating of the fuse must be
selected carefully, i.e., it must be kept as close as possible to the nominal full-
load current of the primary winding (generally, not more than 1.25 times [125%]
of the nominal full-load current). Overload protection is gradually sacrificed as the
selected current rating exceeds the nominal full-load current of the primary
winding more and more. Note that the fuse selected must be of the slow-blow
type to ensure that it can sustain, without blowing, the magnetizing current
inrush that occurs when voltage is applied to the power transformer. Also, note
that protecting a power transformer using a fuse at the primary winding only is
applicable only to transformers having a single secondary winding.

Current rating of fuse generally selected


for both OC and OL protection

To source Primary Secondary To load

Figure 7. Overcurrent and overload protection of a single-phase power transformer using a


single fuse (at the primary winding).

Figure 8. Pole-mounted secondary distribution transformer with its OC fuse (shown with a
white arrow).

It is also common to protect a single-phase power transformer with two fuses, as


shown in Figure 9. One fuse is connected in series with the primary winding and
another fuse is connected in series with the secondary winding. The current
rating of the fuse at the secondary winding is generally selected to provide both
overcurrent and overload protection of the winding as described earlier in the
discussion. On the other hand, the current rating of the fuse at the primary

12 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

winding is selected to provide overcurrent protection against faults in the power


transformer windings, with overload protection being generally provided by the
fuse at the secondary winding. Note that when a power transformer has multiple
secondary windings, a fuse is connected in series with each secondary winding
and the current rating of each of these fuses is generally selected to provide both
overcurrent and overload protection of the winding.

Current rating of fuse selected Current rating of fuse generally selected


for OC protection only for both OC and OL protection

To source Primary Secondary To load

Figure 9. Overcurrent and overload protection of a single-phase power transformer using


fuses at the primary and secondary windings.

Similarly, it is common to protect a three-phase power transformer with fuses


connected at the primary and secondary windings, as shown in Figure 10. In this
case, a fuse is connected with each power line going to and coming from the
power transformer. The three fuses at the primary windings must have the same
current rating. The same applies for the three fuses at the secondary windings.

Current rating of fuses selected Current rating of fuses generally selected


for OC protection only for both OC and OL protection

Primary Secondary

To source To load

Figure 10. Overcurrent and overload protection of a three-phase power transformer using
fuses at the primary and secondary windings.

Fuses are also commonly used to protect ac motors in industrial applications


(generally induction motors, though synchronous motors may also be protected
with fuses). Figure 11 shows how fuses can protect the stator windings of a
three-phase induction motor. In this case, the fuses provide overcurrent
protection of the induction motor only. This is because the current which any
induction motor draws when voltage is applied to its stator windings (starting-
current inrush) can reach 3 to 8 times the nominal full-load current of the motor
(also known as full-load amps or FLA). Furthermore, the starting-current inrush
lasts until the motor approaches its nominal speed, with the duration being
dependent on the motor power rating and load inertia (the duration can be any

© Festo Didactic 52173-10 13


Exercise 1 – Overcurrent Protection  Discussion

value between a fraction of a second and several minutes). These considerations


preclude the use of fuses having a current rating close to the induction
motor FLA, a requirement to achieve proper overload protection of the induction
motor. Consequently, the current rating of the fuses is selected for overcurrent
protection only. For instance, if the starting-current inrush has a value
of 5 times (500%) the FLA, fuses having a current rating of about 6 times (600%)
the FLA would be appropriate to achieve overcurrent protection of the induction
motor. To provide overload protection of the three-phase induction motor, a
three-phase contactor and an overload detection unit are often connected in
series with the fuses, as shown in Figure 11. The unit detects when the motor is
overloaded and then opens the three-pole contactor before excessive
overheating causes damage to the motor.

Current rating of fuses selected


for OC protection only Three-pole Induction motor
contactor stator windings

To source

Overload Contactor
detection Open/Close coil
unit command

Figure 11. Overcurrent and overload protection of a three-phase induction motor


implemented using fuses and a three-phase contactor controlled by an overload detection
unit.

ANSI is the common abbre- The first column in Table 3 (located at the end of this discussion) summarizes the
viation used to refer to the main protection features implemented with fuses. Fuses can operate at voltages
American National Stand- up to 161 kV. They are available at current ratings up to 6000 A and can interrupt
ards Institute. currents up to 200 kA. Fuses have an inverse time-current characteristic and
their minimum operating time can be less than 0.01 s. The latter feature puts
fuses among the fastest devices available for overcurrent protection. Fuses have
some drawbacks: they cannot be reset (once blown, a fuse has to be replaced),
their nominal current and operating time cannot be adjusted, and their inverse-
time characteristic is sensitive to ambient temperature. Devices holding fuses
(commonly referred to as fuse holders) generally allow electric power circuits to
be closed or opened manually. Finally, from a protective relaying perspective
(i.e., referring to ANSI standard C37.2), fuses are equivalent to the function
performed by standard device no. 51 (ac time overcurrent relay). The function of
standard device no. 51 is discussed later in this manual.

14 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Overcurrent protection and overload protection using LV circuit breakers


(MCBs and MCCBs)

A single-pole, low-voltage (LV) circuit breaker, such as an MCB or an MCCB, is a


two-terminal electric component which consists of a current sensor, an actuation
mechanism, and a pair of contacts, all enclosed in a plastic case. Figure 12
shows the arrangement of the current sensor, actuation mechanism, and
contacts in a single-pole LV circuit breaker. The current sensor and contacts
have very low resistance, thereby allowing the circuit breaker to be connected in
series with an electric power circuit without perturbing the circuit operation. When
the current flowing through the circuit breaker exceeds a certain value, the
current sensor triggers the actuation mechanism to make the contacts open. This
breaks the electric path between the circuit breaker terminals and interrupts
current flow. This feature enables an LV circuit breaker connected in series with
an electric power circuit to protect the circuit against overcurrent, and possibly,
against overload too. However, contrary to the fuse, the LV circuit breaker does
not need to be replaced with a new unit once open. The contacts are simply
reclosed using a reset lever in the actuation mechanism, as shown in Figure 13.

Contacts
Current
sensor

Actuation
mechanism

Reset / Manual actuation

Figure 12. Arrangement of the current sensor, actuation mechanism, and contacts in a single
pole, LV circuit breaker.

Figure 13. Contrary to the fuse, the circuit breaker does not need to be replaced with a new
unit once open. The contacts may be reclosed using a reset lever.

© Festo Didactic 52173-10 15


Exercise 1 – Overcurrent Protection  Discussion

The actuation mechanism and contacts of an LV circuit breaker can rapidly


extinguish the arc that strikes when the contacts are opened, thereby providing
the unit with a high current-interrupting capability. Figure 14 shows the symbols
that are commonly used to represent a single-pole circuit breaker in circuit
diagrams.

(a) (b) (c)

Figure 14. Circuit diagram symbols for a single-pole circuit breaker.

The operating time of LV The current sensor in an LV circuit breaker can be of the thermal type. In this
circuit breakers is common- case, the circuit breaker is referred to as a thermal circuit breaker. A thermal-type
ly referred to as the tripping current sensor is basically a small bi-metallic element that heats up significantly
time. when the current flowing through the circuit breaker exceeds the current rating of
the circuit breaker. The heat produced eventually triggers the actuation
mechanism of the circuit breaker. The more the current flowing through the circuit
breaker exceeds the current rating of the circuit breaker, the higher the heating
effect and consequently, the shorter the time required to trigger the actuation
mechanism. In other words, the operating time of a thermal circuit breaker varies
inversely with the value of current, thereby leading to an inverse time-current
characteristic similar to that of a fuse. Thermal circuit breakers can thus be used
the same way as fuses to achieve overcurrent protection and overload
protection, as discussed in the previous section of this discussion.

The current sensor in an LV circuit breaker can also be of the magnetic type. In
this case, the circuit breaker is referred to as a magnetic circuit breaker. A
magnetic-type current sensor is basically a solenoid that triggers the actuation
mechanism of the circuit breaker as soon as the current flowing through the
circuit breaker reaches a predetermined value (e.g., 5 times the current rating of
the circuit breaker). Figure 15 shows the resulting time-current characteristic.
Such a characteristic is commonly referred to as an instantaneous time-current
characteristic because the tripping time of the circuit breaker is minimum. In fact,
the tripping time is reduced to the time required for the circuit breaker contacts to
open. The time-current characteristic of magnetic circuit breakers makes them
perfectly suited for overcurrent protection since any short-circuit current is
interrupted in a minimum time. However, they are not suitable for overload
protection.

16 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

It is common practice to
express current in the time-
current characteristic of 100
circuit breakers as multiples
of the current rating of the
circuit breaker.

10

Tripping time (s)


1

0.1

0.01
1 10 100
Current (multiples of current rating)

Figure 15. Time-current characteristic of a magnetic circuit breaker.

It is common to combine a thermal-type current sensor with a magnetic-type


current sensor in the same LV circuit breaker. In this case, the LV circuit breaker
is referred to as a thermal-magnetic circuit breaker. Figure 16 shows the resulting
time-current characteristic. The thermal-type current sensor provides overload
protection similar to that obtained with a fuse while the magnetic-type current
sensor provides overcurrent protection with a minimum tripping time.

© Festo Didactic 52173-10 17


Exercise 1 – Overcurrent Protection  Discussion

100
Magnetic action

Thermal action

Tripping time (s) 10

0.1

0.01
1 10 100
Current (multiples of current rating)

Figure 16. Time-current characteristic of a thermal-magnetic circuit breaker.

On certain thermal-magnetic circuit breakers, like electronic MCCBs, the


thermal portion of the characteristic is adjustable in current and time (i.e., it can
be shifted left and right as well as up and down) while the magnetic portion of the
characteristic is adjustable in current (i.e., it can be shifted left and right). This
allows both the overload protection and the overcurrent protection to be
optimized for a specific application. For instance, a three-pole, thermal-magnetic
electronic MCCB connected in series with a three-phase induction motor can
provide both overcurrent protection and overload protection when properly
adjusted. This is shown in Figure 17.

18 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Three-pole,
thermal-magnetic
electronic MCCB Induction motor
stator windings

To source

Figure 17. Overcurrent and overload protection of a three-phase induction motor


implemented using a three-pole, thermal-magnetic electronic MCCB.

The second row in Table 3 summarizes the main protection features


implemented with LV circuit breakers. LV circuit breakers can operate at voltages
lower than 1 kV, which is much less than fuses and HV circuit breakers. They are
available at current ratings up to 3200 A and can interrupt currents up to 200 kA.
LV circuit breakers have an inverse and/or instantaneous time-current
characteristic and their minimum operating time can be less than 0.01 s. The
latter feature makes LV circuit breakers as fast as fuses for overcurrent
protection. LV circuit breakers, contrary to fuses, are re-usable, i.e., they can be
reset after tripping. Also, LV circuit breakers allow electric power circuits to be
closed or opened manually, though motorized units are available to allow remote
switching of circuits. LV circuit breakers have a few drawbacks: their nominal
current and operating time cannot be adjusted and their inverse-time
characteristic is sensitive to ambient temperature. Note that electronic MCCBs do
not have such drawbacks. Finally, from a protective relaying perspective (i.e.,
referring to ANSI standard C37.2), most LV circuit breakers are equivalent to the
combination of the functions performed by standard device no. 50 (instantaneous
overcurrent or rate-of-rise relay) and standard device no. 51 (ac time overcurrent
relay). The functions of these ANSI standard devices are discussed later in this
manual.

Overcurrent protection and overload protection using protective relays and


HV circuit breakers

It is common to use fuses or LV circuit breakers to implement overcurrent


protection of power lines in distribution networks and industrial applications. It is
also common practice to use fuses or LV circuit breakers to implement
overcurrent and overload protection of power transformers and ac motors. In
both cases, using fuses or LV circuit breakers is a solution that provides
satisfactory protection while being cheaper than opting for protective relays used
in conjunction with high-voltage (HV) circuit breakers. However, protection that is
more efficient and flexible is generally required as the importance or monetary
value of the equipment to be protected increases. Such performance and
flexibility can be achieved with protective relays used in conjunction with HV
circuit breakers. Consequently, it is common to use overcurrent protective relays
in conjunction with HV circuit breakers to implement overcurrent protection of any
important or valuable power lines in distribution networks and industrial

© Festo Didactic 52173-10 19


Exercise 1 – Overcurrent Protection  Discussion

applications. Similarly, it is common to use an overcurrent protective relay in


conjunction with an HV circuit breaker to implement overcurrent and overload
protection of any important or valuable power transformer or ac motor. Note that
an overcurrent protective relay is commonly referred to as an overcurrent relay.

Figure 18 is a simplified diagram showing the connections of an overcurrent relay


and a three-pole HV circuit breaker used to protect a three-phase power circuit.
The relay has three current inputs to measure each of the line currents in the
three-phase power circuit. Recall that current transformers are required to match
the value of the line currents with the current rating of the overcurrent relay
inputs, which is generally either 1 A or 5 A.

Three-pole
Current transformers HV circuit breaker

To load
To source (power transformer,
ac motor, etc.)

Operating
mechanism

Current Open
inputs A B C command
Control
unit
Overcurrent relay

Trip output
(relay contact)

Figure 18. Protection of a three-phase power circuit using an overcurrent relay and an HV
circuit breaker.

Figure 19 is a single-line diagram that corresponds to the circuit shown in


Figure 18. Note that the number inside the protective relay symbol indicates the
exact function performed by the relay as per ANSI standard C37.2. In this
particular case, number 50 indicates that the protective relay is an instantaneous
overcurrent relay. ANSI device numbers related to overcurrent relays are
discussed later in the manual.

20 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Current HV circuit
transformers breaker
To load
To source (power transformer,
ac motor, etc.)

Instantaneous
50
overcurrent relay

Figure 19. Single-line diagram representing the circuit in Figure 18.

Instantaneous overcurrent relay

Three types of overcurrent relay are commonly available: instantaneous, definite


time, and inverse definite minimum time (IDMT). Each of these three types of
overcurrent relay has its own time-current characteristic. These three types of
overcurrent relays are described in this section as well as in the next two
sections of this discussion.

The adjustable current An overcurrent relay can have an instantaneous time-current characteristic very
threshold of an overcurrent similar to that of a magnetic-type MCB or MCCB, as shown in Figure 20. The
relay is commonly referred operating time is fixed and has a minimum value limited by the time required for
to as the current setting. the overcurrent relay contacts to close (i.e., for the overcurrent relay to actuate its
trip output). Contrary to most MCBs and MCCBs, the current threshold (i.e., the
Also, the operating time of current at which the relay trips) can be adjusted in an overcurrent relay. An
an overcurrent relay is overcurrent relay with an instantaneous time-current characteristic is commonly
sometimes called the trip referred to as an instantaneous overcurrent relay. An instantaneous overcurrent
time. relay is referred to as a device no. 50 as per ANSI standard C37.2. In this
standard, device no. 50 is termed “instantaneous overcurrent or rate-of-rise
relay” and is defined as “a relay that functions instantaneously on an excessive
value of current or on an excessive rate of current rise, thus indicating a fault in
the apparatus or circuit being protected”.

© Festo Didactic 52173-10 21


Exercise 1 – Overcurrent Protection  Discussion

100

10

Operating time (s)

Current threshold
can be adjusted
(current setting)
1

0.1

Operating time is
fixed and minimal
0.01
10 100 1000
Current (A)

Figure 20. Time-current characteristic of an instantaneous overcurrent relay (ANSI


device no. 50).

Instantaneous overcurrent relays are ideally suited to implement overcurrent


protection since any short-circuit current is interrupted in a minimum time.
Instantaneous overcurrent relays are commonly used as the main protection of
power transformers of up to about 5 to 10 MVA and ac motors. It is also common
to use instantaneous overcurrent relays to provide backup protection of various
types of electric devices such as synchronous generators, power transformers
larger than about 5 to 10 MVA, busses in an electric power substation,
transmission lines, etc. Note that the ANSI device no. 50 function is seldom used
alone in overcurrent relays: it is generally combined with other ANSI device
functions to obtain more complete equipment protection. This is discussed later
in this manual.

22 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Definite-time overcurrent relay

The adjustable operating An overcurrent relay can have a time-current characteristic similar to that of an
time of an overcurrent relay instantaneous overcurrent relay in which the operating time can be adjusted (to a
is commonly referred to as value higher than the minimum operating time of the overcurrent relay) in
the time setting. addition to the current threshold (current setting), as shown in Figure 21. Such a
time-current characteristic is commonly referred to as a definite time
characteristic because the operating time of the overcurrent relay has a
predetermined value that is independent of the magnitude of current. An
overcurrent relay with a definite time characteristic is commonly referred to as a
definite-time overcurrent relay. A definite-time overcurrent relay is referred to as
a device no. 51 as per ANSI standard C37.2. In this standard, device no. 51 is
termed “AC time overcurrent relay” and is defined as “a relay with either a
definite or inverse time characteristic that functions when the current in an ac
circuit exceeds a predetermined value”. Note that the letters “DT” (standing for
definite time) are sometimes added to device no. 51 to make clear the nature of
the time-current characteristic of the overcurrent relay.

100

Current threshold
can be adjusted
(current setting)
10
Operating time (s)

0.1 Operating time


can be adjusted
(time setting)

0.01
10 100 1000
Current (A)

Figure 21. Time-current characteristic of a definite-time overcurrent relay (ANSI device


no. 51DT).

© Festo Didactic 52173-10 23


Exercise 1 – Overcurrent Protection  Discussion

Definite-time overcurrent relays are commonly used to implement overcurrent


protection of radial feeders. A definite-time overcurrent relay can also be used to
implement backup overcurrent protection of the low voltage side (secondary side)
of a power transformer (for transformers up to about 5 to 10 MVA). Overcurrent
protection of radial feeders using overcurrent relays is discussed in Exercise 3 of
this manual. Overcurrent protection of power transformers using overcurrent
relays is discussed later on.

Inverse definite minimum time (IDMT) overcurrent relay

An overcurrent relay can have an inverse time-current characteristic similar to


that of a fuse or a thermal circuit breaker. In an overcurrent relay, however, the
inverse time-current characteristic is adjustable in current and time (via current
and time settings, respectively), i.e., it can be shifted left and right as well as up
and down. This is shown in Figure 22. An overcurrent relay with an inverse time-
current characteristic is commonly referred to as an inverse definite minimum
time (IDMT) overcurrent relay. An IDMT overcurrent relay is referred to as a
device no. 51 as per ANSI standard C37.2. In this standard, device no. 51 is
termed “AC time overcurrent relay” and is defined as “a relay with either a
definite or inverse time characteristic that functions when the current in an ac
circuit exceeds a predetermined value”. Note that the letter “I” (standing for
inverse) is sometimes added to device no. 51 to make clear the nature of the
time-current characteristic of the overcurrent relay.

The current transformers that feed the inputs of any overcurrent relay no longer
operate linearly when they are subjected to high current levels (e.g., currents
exceeding 20 times the current setting of the relay), thereby leading to a
significant error in the measured value of current. Such an error in the measured
value of current leads directly to a significant error in the operating time of any
IDMT overcurrent relay. To avoid errors in the relay operating time at high current
levels, most digital or numerical IDMT overcurrent relays stop following their
inverse characteristic and pass to a definite time characteristic when the current
reaches about 20 to 30 times the current setting of the relay. For instance, the
time-current characteristic of Figure 22 shows that the IDMT overcurrent relay
stops following the inverse characteristic and passes to a definite time
characteristic when the current reaches 20 times the current setting of the relay.
The time setting of the definite time characteristic (i.e., the definite minimum time)
is equal to the time value calculated using the equation of the inverse
characteristic and a current value of 20 times the current setting of the relay. In
short, these overcurrent relays combine an inverse characteristic with a definite
time characteristic, hence the name inverse definite minimum time (IDMT)
overcurrent relay.

24 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Current
setting
100

Adjusting the current setting


moves the characteristic
left or right
10
Operating time (s)

Adjusting the time setting Definite


moves the characteristic minimum
up or down time

0.1
1 10 100 1000
Current (A)

Figure 22. Time-current characteristic of an inverse definite minimum time (IDMT) overcurrent
relay (ANSI device no. 51I).

IDMT overcurrent relays are commonly used to implement overload protection of


AC motors. In fact, this is an alternative to the use of a thermal-magnetic
electronic MCCB. IDMT overcurrent relays are also commonly used to implement
overcurrent protection of radial feeders. Overload protection of an ac motor using
an IDMT overcurrent relay is discussed in Exercise 2 of this manual. Overcurrent
protection of radial feeders using overcurrent relays is discussed in Exercise 3 of
this manual.

Standard time-current characteristics of IDMT overcurrent relays

IEC is the common abbrevi- Standard time-current characteristics of IDMT overcurrent relays have been
ation used to refer to the defined by IEC and ANSI. Figure 23 shows the time-current characteristics for
International Electrotech- IDMT overcurrent relays defined in IEC standard 60255. Table 1 provides the
nical Commission. equations that define these time-current characteristics. Various types of inverse
time-current characteristics have been defined to provide protection engineers
with a means to address a large variety of applications. For instance, the
Standard Inverse (SI) characteristic is well suited for overload protection. On the
other hand, the Extremely Inverse (EI) characteristic is well suited in overcurrent
protection applications mixing IDMT overcurrent relays with fuses because it is
similar to the time-current characteristic of various fuses.

© Festo Didactic 52173-10 25


Exercise 1 – Overcurrent Protection  Discussion

The time-current character-


istics of IDMT overcurrent
relays defined in IEC stand- 100
ard 60255 are mainly used Standard Inverse (SI)
in Europe (except Germany)
Very Inverse (VI)
as well as elsewhere in the
world. Extremely Inverse (EI)

Long-Time Inverse (LTI)

10
Operating time (s)

0.1
1 10 100
Current (multiples of current setting)

Figure 23. Time-current characteristics for IDMT overcurrent relays defined in IEC
standard 60255 (TMS = 1.0).

Table 1. Equations of the time-current characteristics of IDMT overcurrent relays defined in


IEC standard 60255.

Characteristic Equation

ͲǤͳͶ
Standard Inverse (SI) ‫ ݐ‬ൌ ܶ‫ ܵܯ‬ή
‫ܫ‬௥଴Ǥ଴ଶ െ ͳ

ͳ͵Ǥͷ
Very Inverse (VI) ‫ ݐ‬ൌ ܶ‫ ܵܯ‬ή
‫ܫ‬௥ െ ͳ
ͺͲ
Extremely Inverse (EI) ‫ ݐ‬ൌ ܶ‫ ܵܯ‬ή
‫ܫ‬௥ଶ െ ͳ
ͳʹͲ
Long-Time Inverse (LTI) ‫ ݐ‬ൌ ܶ‫ ܵܯ‬ή
‫ܫ‬௥ െ ͳ

Ir = Multiple of relay current setting, TMS = Time multiplier setting of relay

Figure 24 shows the time-current characteristics for IDMT overcurrent relays


defined by ANSI. Table 2 provides the equations that define these time-current
characteristics.

26 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

The time-current character-


istics of IDMT overcurrent
relays defined by ANSI are 100
mainly used in North Ameri- IEEE Moderately Inverse
ca.
IEEE Very Inverse

IEEE Extremely Inverse (EI)

US CO8 Inverse

US CO2 Short-Time Inverse


10

Operating time (s)

0.1
1 10 100
Current (multiples of current setting)

Figure 24. Time-current characteristics for IDMT overcurrent relays defined by ANSI (TD = 7).

Table 2. Equations of the time-current characteristics of IDMT overcurrent relays defined by


ANSI.

Characteristic Equation

ܶ‫Ͳ ܦ‬ǤͲͷͳͷ
IEEE Moderately Inverse ‫ݐ‬ൌ ቈቆ ଴Ǥ଴ଶ ቇ ൅ ͲǤͳͳͶ቉
͹ ‫ܫ‬௥ െ ͳ

ܶ‫ͻͳ ܦ‬Ǥ͸ͳ
IEEE Very Inverse ‫ݐ‬ൌ ൤൬ ൰ ൅ ͲǤͶͻͳ൨
͹ ‫ܫ‬௥ଶ െ ͳ

ܶ‫ʹ ܦ‬ͺǤʹ
IEEE Extremely Inverse (EI) ‫ݐ‬ൌ ൤൬ ൰ ൅ ͲǤͳʹͳ͹൨
͹ ‫ܫ‬௥ଶ െ ͳ

ܶ‫ ܦ‬ͷǤͻͷ
US CO8 Inverse ‫ݐ‬ൌ ൤൬ ൰ ൅ ͲǤͳͺ൨
͹ ‫ܫ‬௥ଶ െ ͳ

ܶ‫Ͳ ܦ‬ǤͲʹ͵ͻͶ
US CO2 Short-Time Inverse ‫ݐ‬ൌ ቈቆ ଴Ǥ଴ଶ ቇ ൅ ͲǤͲͳ͸ͻͶ቉
͹ ‫ܫ‬௥ െ ͳ

Ir = Multiple of relay current setting, TD = Time dial setting of relay

© Festo Didactic 52173-10 27


Exercise 1 – Overcurrent Protection  Discussion

The time-current characteristic of an IDMT overcurrent relay can be moved left or


right as mentioned earlier in this discussion. This is achieved by decreasing or
increasing the current setting of the IDMT overcurrent relay. The current setting
determines the value of the minimum current that must be exceeded to make the
IDMT overcurrent relay trip (this is similar to the melting current of a fuse). For
example, adjusting the current setting of an IDMT overcurrent relay to 10 A sets
the vertical asymptotic line toward where the inverse characteristic converges
to 10 A.

The time-current characteristic of an IDMT overcurrent relay can also be moved


up or down, as mentioned earlier in this discussion. This is achieved by
increasing or decreasing the time setting of the IDMT overcurrent relay. This
setting is referred to as the time multiplier setting (TMS) in IEC standard 60255
and the time dial setting (TD) by ANSI. Increasing the TMS (or TD) value moves
the characteristic up, thereby increasing the operating time of the IDMT
overcurrent relay for any given value of current. Conversely, decreasing the TMS
(or TD) value moves the characteristic down, thereby decreasing the operating
time of the IDMT overcurrent relay for any given value of current. Note that
adjusting the TMS (or TD) of an IDMT overcurrent relay in fact sets the value of
the TMS (or TD) constant in the equations of the time-current characteristics
given in the two tables above.

Overcurrent protection of a power transformer using a numerical overcurrent


relay

Overcurrent protection is commonly used as the main protection of power


transformers of up to about 5 to 10 MVA. An instantaneous overcurrent relay
(ANSI device no. 50) is well suited to implement overcurrent protection of a
power transformer. Also, backup overcurrent protection of the low-voltage side
(secondary side) of a power transformer is sometimes added to enhance the
overall protection of power transformers up to about 5 to 10 MVA. A definite-time
overcurrent relay (ANSI device no. 51DT) can be used to implement backup
overcurrent protection of the low-voltage side of a power transformer. Both the
main overcurrent protection of the power transformer and the backup overcurrent
protection of the low-voltage side of the power transformer can be performed
using a single numerical overcurrent relay that combines the functions of ANSI
devices no. 50 and no. 51DT. This is illustrated in the single-line diagram of
Figure 25.

a In the diagram of Figure 25, the power of the ac power source is rated
as 175 MVA SC, SC standing for short-circuit. This value refers to the power
which the source can supply when subjected to a symmetrical fault.

28 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

8 MVA
120 kV / 25 kV
120 kV 7%
175 MVA SC
To load

AC power
source F1 F2
50
51DT

Figure 25. Overcurrent protection of a power transformer using a numerical overcurrent relay
that combines the functions of ANSI devices no. 50 and no. 51DT.

The nominal value of the line currents at the primary of the power transformer in
Figure 25 (i.e., the value of the line currents when the power transformer load
is 8 MVA) is 38.5 A. When a symmetrical fault occurs at the transformer primary
(fault F1 in Figure 25), the value of the line currents at the transformer primary
can reach up to 842 A. On the other hand, when a symmetrical fault occurs at the
low-voltage side (secondary) of the power transformer (fault F2 in Figure 25) and
the protection at the transformer secondary (not shown in Figure 25) fails to
operate, the value of the line currents at the transformer primary can reach up
to 333 A.

The values of current above are the values measured by the numerical
overcurrent relay (via the current transformers) under normal and abnormal
operating conditions. These values of current are used to determine the value at
which the current threshold of the ANSI device no. 50 function in the numerical
overcurrent relay should be set to ensure that the main overcurrent protection of
the power transformer works properly. These values of current are also used to
determine the value at which the current threshold of the ANSI device no. 51DT
function in the numerical overcurrent relay should be set to ensure that the
backup overcurrent protection of the low-voltage side of the power transformer
works properly. For instance, setting the current threshold of the ANSI device
no. 50 function to 400 A makes the main overcurrent protection of the power
transformer sensitive enough to faults at the transformer primary (fault currents at
primary are up to 842 A) and insensitive to faults at the transformer secondary
(fault currents at primary are up to 333 A). Similarly, setting the current threshold
of the ANSI device no. 51DT function to about 190 A makes the backup
overcurrent protection of the low-voltage side of the power transformer sensitive
enough to faults at the transformer secondary (fault currents at primary are up
to 333 A) and insensitive to the nominal value (38.5 A) of the transformer primary
current. The time-current characteristic of the numerical overcurrent relay that
results from these current settings is shown in Figure 26.

© Festo Didactic 52173-10 29


Exercise 1 – Overcurrent Protection  Discussion

Nominal Primary current Primary current


primary with fault with fault
current at secondary at primary
(38.5 A) (333 A) (842 A)
100

ANSI device no. 51DT


function (backup
overcurrent protection
10 of transformer
low-voltage side)
Operating time (s)

ANSI device no. 50


function (main
overcurrent protection
0.1 of transformer)

0.01
10 100 1000
Current (A)

Figure 26. Time-current characteristic of the numerical overcurrent relay used for overcurrent
protection of the power transformer in Figure 25.

Note that the time setting of the ANSI device no. 51DT function in the numerical
overcurrent relay is adjusted to the lowest value (1 s in the present case) that
allows sufficient time for the protection at the power transformer secondary to
operate when a fault occurs at the transformer secondary. Also note that the
numerical overcurrent relay does not protect the power transformer from
overload since it does not operate for primary currents ranging from the nominal
primary current (38.5 A) of the power transformer to 190 A. Another protection
function (ANSI device no. 49 function: machine or transformer thermal relay) is
required in the numerical overcurrent relay to achieve overload protection of the
power transformer. This is discussed further in the next exercise of this manual.

30 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Discussion

Main features of protection implemented with numerical overcurrent relays


and HV circuit breakers

The third row in Table 3 summarizes the main protection features implemented
with numerical overcurrent relays used in conjunction with HV circuit breakers.
HV circuit breakers can operate at voltages up to 1200 kV, which is much higher
than fuses and LV circuit breakers. They are available at current ratings up
to 5000 A (this is a little less than fuses) and can interrupt currents up to 90 kA
(this is significantly less than fuses and LV circuit breakers). HV circuit breakers,
contrary to fuses, are re-usable, i.e., they can be reclosed after tripping. Also, HV
circuit breakers allow electric power circuits to be closed or opened either
manually or through remote control. Numerical overcurrent relays can have any
combination of instantaneous, definite, and inverse time-current characteristics.
The time-current characteristic of numerical overcurrent relays is adjustable in
current and time, and is not temperature sensitive.

Protection implemented with an overcurrent relay used in conjunction with an HV


circuit breaker has one drawback: the minimum operating time is about 0.05 s,
which is significantly longer than the minimum operating time (<0.01 s) of fuses
and LV circuit breakers. This makes overcurrent relays used in conjunction with
HV circuit breakers slower than fuses and LV circuit breakers.

Finally, from a protective relaying perspective (i.e., referring to ANSI standard


C37.2), numerical overcurrent relays generally combine functions of two or more
of the following ANSI devices: no. 50 (instantaneous overcurrent or rate-of-rise
relay), no. 51 (ac time overcurrent), and no. 49 (machine or transformer thermal
relay).

Table 3. Summary of the main features of current-based protective devices.

Numerical
LV circuit
overcurrent
Device type Fuse breaker
relay with HV
(MCB, MCCB)
circuit breaker

Voltage rating Up to 161 kV Less than 1 kV Up to 1200 kV

Current rating Up to 6000 A Up to 3200 A Up to 5000 A

Current interrupting capability Up to 200 kA Up to 200 kA Up to 90 kA

Minimum operating time < 0.01 s < 0.01 s ~ 0.05 s

Instantaneous
Instantaneous and/or definite
Time-current characteristic Inverse
and/or inverse time and/or
inverse

No
Adjustable in current No (Yes, electronic Yes
MCCB)

No
Adjustable in time No (Yes, electronic Yes
MCCB)

© Festo Didactic 52173-10 31


Exercise 1 – Overcurrent Protection  Procedure Outline

Numerical
LV circuit
overcurrent
Device type Fuse breaker
relay with HV
(MCB, MCCB)
circuit breaker

No
Temperature sensitive Yes (Yes, electronic No
MCCB)

No (blown fuse
Reset capability Yes Yes
to be replaced)

Manual and Manual and


Circuit switching Manual
remote remote

No Yes Yes
Combined protection functions
(51 only) (50 + 51) (50 + 51 + 49)

PROCEDURE OUTLINE The Procedure is divided into the following sections:

ƒ Set up and connections


ƒ Operation of an instantaneous overcurrent relay
ƒ Operation of a definite time overcurrent relay
ƒ Operation of an inverse definite minimum time (IDMT) overcurrent relay
ƒ Overcurrent protection of a power transformer using a numerical
overcurrent relay

PROCEDURE a You might need more than one laboratory period to perform the following
exercise procedure if you are not already familiar with the DIGSI ® 5 software
from Siemens. Appendix C of this manual provides information on how to use
software DIGSI 5 to perform various tasks related to SIPROTEC 5 protective
relays. You should read this appendix before performing the exercise
procedure.

Set up and connections

In this section, you will set up a protective relay so that it can be programmed
and tested using a host computer.

1. Refer to the Equipment Utilization Chart in Appendix A to obtain the list of


equipment required to perform this exercise.

Install the Numerical Directional Overcurrent Relay (Model 3812) and the
host computer on your work surface.

a This exercise can also be performed using the Numerical Distance


Relay (Model 3813) or the Numerical Differential Protective
Relay (Model 3819). The term protective relay is used throughout the
remainder of this exercise procedure to refer to the protective relay that is used
to perform the exercise.

Insert the LED identification label for Exercise 1 into the front panel of the
protective relay. The identification labels can be found in Appendix D.

32 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

2. Connect the protective relay and the host computer to an ac power wall
outlet.

Turn the protective relay on. Wait for the protective relay to complete its
initialization routine (this generally takes about 45 s).

3. Connect the USB port of the protective relay to a USB port of the host
computer.

4. Turn the host computer on, then start the DIGSI 5 software.

Operation of an instantaneous overcurrent relay

In this section, you will verify the operation of an instantaneous overcurrent relay
(ANSI device no. 50).

5. In DIGSI 5, open project file Overcurrent Relay Settings and Operation.dp5v6


created for the protective relay that you are using to perform the exercise. A
project file contains the complete configuration of the protective relay for a
particular application. By default, the project files required to perform the
exercises in this manual should be located in the following folder:
C:\ProgramData\Festo Didactic\Manual 52173, OC and OL Protection\...

a Appendix C of this manual provides a series of short procedures, with each


procedure describing how to use software DIGSI 5 to perform a specific task
related to SIPROTEC 5 protective relays. You can refer to this appendix to
learn how to perform the task required in most manipulations of this exercise
procedure.

6. In DIGSI 5, display the single-line diagram showing the connection of the


protective relay to the electric power circuit. Observe that in this project, the
current inputs of the protective relay are connected to the electric power
circuit (a feeder in an electric power substation) via current transformers
having a 1000 A/1 A ratio.

7. In DIGSI 5, set the frequency of operation (Rated frequency parameter) of


the protective relay to the frequency of your local ac power network.

Set the language used in the front panel display of the protective relay to the
language used in DIGSI 5.

8. In DIGSI 5, access the settings of the overcurrent protection function of the


protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1. Figure 27 shows the settings of
the overcurrent protection function that should be displayed in the working
area of DIGSI 5.

© Festo Didactic 52173-10 33


Exercise 1 – Overcurrent Protection  Procedure

Figure 27. Settings of the overcurrent protection function of the protective relay displayed in
the working area of DIGSI 5.

9. Observe that, in this project, the overcurrent protection function of the


protective relay can be a combination of three different time-current
characteristics (instantaneous overcurrent, definite-time overcurrent, and
inverse-time overcurrent). These time-current characteristics are named
Definite-T1, Definite-T2, and Inverse-T1 in DIGSI 5. Observe that time-
current characteristic Definite-T1 is on (Mode parameter set to on) and that
time-current characteristics Definite-T2 and Inverse-T1 are off (Mode
parameter set to off). Consequently, the overcurrent protection function of the
protective relay is now entirely defined by time-current characteristic
Definite-T1.

Observe that the protective relay is set to operate as an instantaneous


overcurrent relay (ANSI device no. 50 function) because the time setting
(parameter Operate delay in time-current characteristic Definite-T1) is set
to 0.00 s.

34 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Observe that the current setting of the protective relay (parameter Threshold
in time-current characteristic Definite-T1) is currently set to 8000 A.

Observe that time-current characteristics Definite-T1, Definite-T2, and


Inverse-T1 are displayed in the working area of DIGSI 5. However, since
time-current characteristics Definite-T2 and Inverse-T1 are off, uncheck the
corresponding check boxes under the time-current characteristic displayed in
DIGSI 5 to show the time-current characteristic of the overcurrent protection
function resulting from the above settings.

a The x-axis in the diagram showing the time-current characteristic of the


protection function is graduated with values of current at the secondary
windings of the current transformers. These values of current must be
multiplied by the ratio of the current transformers (1000 A/1 A in the currently-
open project) to obtain values of current at the primary windings of the current
transformers (i.e., values of current in the electric power circuit).

10. In DIGSI 5, change the current setting of the protective relay by editing the
value of the Threshold parameter in time-current characteristic Definite-T1.
Observe that the time-current characteristic of the protective relay displayed
in the working area of DIGSI 5 is automatically updated after each change of
the current setting.

Set the current setting of the protective relay back to its original
value (8000 A).

11. In DIGSI 5, access the parameters of test sequence Symmetrical fault. This
test sequence is part of the project file currently open in DIGSI 5 and can be
used to test the overcurrent protection function of the protective relay using
its internal relay test system. Figure 28 shows the parameters of test
sequence Symmetrical fault that should be displayed in the working area of
DIGSI 5.

Figure 28. Parameters of test sequence Symmetrical fault displayed in the working area of
DIGSI 5.

© Festo Didactic 52173-10 35


Exercise 1 – Overcurrent Protection  Procedure

a In all test sequences, the magnitudes are expressed as secondary values, i.e.,
the values at the secondary windings of the current transformers.

12. Make the following observations about test sequence Symmetrical fault.
x The test sequence consists of two steps.
x The first step (step 1) has a duration of 10.0 s.
x During the first step, the internal relay test system emulates balanced
currents of 1.00 A at the current inputs of the relay. This is equivalent to
balanced currents of 1000 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.
x The second step (step 2) has a duration of 2.0 s.
x During the second step, the internal relay test system emulates balanced
currents of 10.00 A at the current inputs of the relay. This is equivalent to
balanced currents of 10 000 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.
x By default, the frequency of the balanced currents emulated by the
internal relay test system during both steps of the sequence is set
to 50 Hz.

Set the frequency of the balanced currents emulated during both steps of test
sequence Symmetrical fault to the frequency of your local ac power network.

13. Load the configuration (i.e., the content of the project file currently open in
DIGSI 5) to the protective relay using DIGSI 5. Loading the configuration to
the protective relay generally takes some time.

14. In DIGSI 5, restart the protective relay in the simulation mode to allow the
overcurrent protection function of the protective relay (i.e., protection function
50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 in protection function group VI 3ph 1)
to be tested using the internal relay test system. Once the restart process is
completed, the test environment for the protective relay that you are using
should be displayed in DIGSI 5 (see Figure 29). Also, the front panel display
of the protective relay should indicate that the unit is operating in the
simulation mode (the words Simulation mode should appear briefly on the
display at regular intervals).

a The Error LED on the front panel of the protective relay lights up when the unit
is in simulation mode. This is normal. Do not be concerned about this error
indication.

a During this procedure, if you notice that DIGSI 5 lags relay operation, press the
Clear list button at the top of the test environment. This should restore normal
operation of DIGSI 5.

36 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Figure 29. Test environment displayed in DIGSI 5.

15. Observe that test sequence Symmetrical fault is available in the test
environment displayed in DIGSI 5. This test sequence originates from the
project file currently open in DIGSI 5. It emulates balanced line currents
of 1000 A during 10 s then a symmetrical fault producing line currents
of 10 000 A during 2 s.

16. In DIGSI 5, start test sequence Symmetrical fault, then observe the front
panel of the protective relay to see how it responds to the currents emulated
by its internal relay test system. Notice that the protective relay displays the
value (1000 A) of the balanced line currents during 10 s, then four LED
indicators on the relay front panel light up to indicate that the relay picked up
and tripped. In this project, LED indicators 1 to 3 (top three LED indicators on
the left-hand side of the relay front panel) light up to indicate that the relay
picked up on phases A, B, and C, i.e., to indicate that the current
setting (8000 A) of the protective relay has been exceeded on phases A, B,
and C. Also, LED indicator 16 (bottom LED indicator on the left-hand side of
the relay front panel) lights up to indicate that the relay tripped.

Also notice that information (protective function that picked up and tripped
the relay, relay pickup time, relay trip time, etc.) about the response of the
protective relay to the test sequence is displayed on the front panel display.
Use the up and down arrow buttons on the relay front panel to scroll through
this information.

© Festo Didactic 52173-10 37


Exercise 1 – Overcurrent Protection  Procedure

17. Whenever the protective relay trips, input signals (i.e., the currents at the
three current inputs) as well as internal signals (e.g., relay pickup
occurrences, the circuit breaker trip command, etc.) are recorded in the relay.
The signals recorded in the protective relay after any trip event are referred
to as a fault record. DIGSI 5 can be used to download a fault record from the
protective relay and display the signals contained in the fault record in
SIGRA. SIGRA is a Siemens application that displays the signals contained
in a fault record on time charts. These time charts are useful to analyze the
protective relay response to the fault.

A fault record has been created in the protective relay when it tripped earlier
in this exercise. Use DIGSI 5 to download the latest fault record from the
protective relay and display the signals contained in this fault record in
SIGRA. Figure 30 shows the signals (time charts) that should be displayed in
SIGRA.

Figure 30. Signals contained in the fault record downloaded from the protective relay
displayed in SIGRA.

38 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Observe the signals in the time charts displayed in SIGRA. Notice that when
the value of the currents emulated at the relay inputs passed from 1000 A
to 10 000 A, the protective relay picked up on all three phases and issued a
circuit breaker trip command immediately.

Does the fault record confirm that the protective relay operated as expected?

Yes, because the protective relay is currently set to operate as an


instantaneous overcurrent relay with a current setting of 8000 A.

18. Reset the protective relay by momentarily depressing the Reset button
located just below the 16 LED indicators on the left-hand side of the relay
front panel. The LED indicators should go out and the front panel display
should resume normal information display (i.e., it should display the values of
the line currents).

Operation of a definite time overcurrent relay

In this section, you will verify the operation of a definite time overcurrent relay
(ANSI device no. 51DT).

19. In DIGSI 5, access the settings of the overcurrent protection function of the
protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1.

Turn time-current characteristic Definite-T1 off, turn time-current


characteristic Definite-T2 on, and make sure that time-current characteristic
Inverse-T1 is turned off. These settings cause the overcurrent protection
function of the protective relay to be entirely defined by time-current
characteristic Definite-T2.

Observe that the protective relay is set to operate as a definite-time


overcurrent relay (ANSI device no. 51DT function) because the time setting
(parameter Operate delay in time-current characteristic Definite-T2) is set
to 3.00 s. Also, observe that the current setting of the protective relay
(parameter Threshold in time-current characteristic Definite-T2) is currently
set to 3000 A.

In the working area of DIGSI 5, check the Definite-T2 check box and uncheck
the Definite-T1 check box to show the time-current characteristic of the
overcurrent protection function resulting from the above settings.

20. In DIGSI 5, change the current and time settings of the protective relay by
editing the values of the Threshold and Operate delay parameters in time-
current characteristic Definite-T2. Observe that the trip area of the protective
relay (i.e., the lightly shaded area in the time-current characteristic of the
protective relay displayed in the working area of DIGSI 5) is reduced when
either one of these two parameters is increased, and vice versa.

© Festo Didactic 52173-10 39


Exercise 1 – Overcurrent Protection  Procedure

Set the current setting of the protective relay back to its original
value (3000 A).

Set the time setting of the protective relay back to its original value (3.00 s).

21. Load the configuration (i.e., the content of the project file currently open in
DIGSI 5) to the protective relay using DIGSI 5. This is necessary because
the settings of the overcurrent protection function of the protective relay have
been modified.

22. In DIGSI 5, access the parameters of test sequence Symmetrical fault. Set
the duration of step 2 to 2.9 s. Also, set the value of the balanced currents
emulated by the internal relay test system during step 2 to 5.00 A. This is
equivalent to balanced currents of 5000 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.

23. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay to see how it responds to the currents emulated by its
internal relay test system.

Briefly describe the response of the protective relay to the test sequence.

The protective relay picked up on all three phases (LED indicators 1 to 3 on


the relay front panel lit up) but did not trip (LED indicator 16 on the relay front
panel remained off).

24. A fault record has been created in the protective relay when it picked up. Use
DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA.

Observe the signals displayed in SIGRA, then briefly explain why the
protective relay did not trip.

The test sequence emulated balanced currents of 5000 A (this value


exceeds the current setting of the relay) during 2.9 s which is a little less than
the time setting of the protective relay. Consequently, the relay picked up
during 2.9 s but did not trip.

The following figure shows the signals that should be displayed in SIGRA.

40 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

25. Reset the protective relay by momentarily depressing the Reset button
located just below the 16 LED indicators on the left-hand side of the relay
front panel.

26. In DIGSI 5, access the parameters of test sequence Symmetrical fault. Set
the duration of step 2 to 3.3 s.

27. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay to see how it responds to the currents emulated by its
internal relay test system.

© Festo Didactic 52173-10 41


Exercise 1 – Overcurrent Protection  Procedure

Did the protective relay trip?

‰ Yes ‰ No

Yes

28. A fault record has been created in the protective relay when it tripped. Use
DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA.

Observe the signals displayed in SIGRA, then briefly explain why the
protective relay tripped.

The test sequence emulated balanced currents of 5000 A (this value


exceeds the current setting of the relay) during 3.3 s which is a little more
than the time setting of the protective relay. Consequently, the relay picked
up during 3.3 s which is sufficient to make it trip.

The following figure shows the signals that should be displayed in SIGRA.

42 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

29. Reset the protective relay.

Operation of an inverse definite minimum time (IDMT) overcurrent relay

In this section, you will verify the operation of an inverse definite minimum time
(IDMT) overcurrent relay (ANSI device no. 51I).

30. In DIGSI 5, access the settings of the overcurrent protection function of the
protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1.

© Festo Didactic 52173-10 43


Exercise 1 – Overcurrent Protection  Procedure

Turn time-current characteristic Definite-T2 off, turn time-current


characteristic Inverse-T1 on, and make sure that time-current characteristic
Definite-T1 is turned off. These settings cause the overcurrent protection
function of the protective relay to be entirely defined by time-current
characteristic Inverse-T1.

Observe that the protective relay is set to operate as an IDMT overcurrent


relay (ANSI device no. 51I function) having an IEC standard inverse (SI)
time-current characteristic (parameter Type of character. curve in time-
current characteristic Inverse-T1 set to IEC normal inverse).

Observe that the current setting of the protective relay (parameter Threshold
in time-current characteristic Inverse-T1) is currently set to 1000 A. Also,
observe that the time setting of the protective relay (parameter Time dial in
time-current characteristic Inverse-T1) is currently set to 1.50.

In the working area of DIGSI 5, check the Inverse-T1 check box and uncheck
the Definite-T2 check box to show the time-current characteristic of the
overcurrent protection function resulting from the above settings.

31. In DIGSI 5, change the current setting of the protective relay by editing the
value of the Threshold parameter in time-current characteristic Inverse-T1.
Observe that the time-current characteristic of the protective relay displayed
in DIGSI 5 is displaced horizontally whenever the current setting is changed.
Set the current setting of the protective relay back to its original
value (1000 A).

In DIGSI 5, change the time settings of the protective relay by editing the
value of the Time dial parameter in time-current characteristic Inverse-T1.
Observe that the time-current characteristic of the protective relay displayed
in DIGSI 5 is displaced vertically whenever the time setting is changed. Set
the time setting of the protective relay back to its original value (1.50).

In DIGSI 5, select a different time-current characteristic for the protective


relay by changing the setting of parameter Type of character. curve in time-
current characteristic Inverse-T1. Observe that the shape of the time-current
characteristic of the protective relay displayed in DIGSI 5 changes whenever
another type of characteristic curve is selected. Set parameter Type of
character. curve in time-current characteristic Inverse-T1 back to IEC normal
inverse.

32. Load the configuration (i.e., the content of the project file currently open in
DIGSI 5) to the protective relay using DIGSI 5. This is necessary because
the settings of the overcurrent protection function of the protective relay have
been modified.

33. In DIGSI 5, access the parameters of test sequence Symmetrical fault. Set
the duration of step 2 to 50.0 s. Also, set the value of the balanced currents
emulated by the internal relay test system during step 2 to 1.25 A. This is
equivalent to balanced currents of 1250 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.

44 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

34. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay for the complete duration of the test sequence (60 s). The
protective relay should trip after a certain time.

Use DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA. Use the displayed
signals to determine the trip time of the protective relay when the value of the
emulated currents is 1250 A.

The trip time of the protective relay is about 46.3 s when the value of the
emulated currents is 1250 A.

The following figure shows the signals that should be displayed in SIGRA.

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

35. Reset the protective relay.

© Festo Didactic 52173-10 45


Exercise 1 – Overcurrent Protection  Procedure

36. In DIGSI 5, access the parameters of test sequence Symmetrical fault. Set
the duration of step 2 to 30 s. Also, set the value of the balanced currents
emulated by the internal relay test system during step 2 to 2.50 A. This is
equivalent to balanced currents of 2500 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.

37. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay for the complete duration of the test sequence (40 s). The
protective relay should trip after a certain time.

Use DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA. Use the displayed
signals to determine the trip time of the protective relay when the value of the
emulated currents is 2500 A.

The trip time of the protective relay is about 11.3 s when the value of the
emulated currents is 2500 A.

The following figure shows the signals that should be displayed in SIGRA.

46 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

38. Reset the protective relay.

39. In DIGSI 5, access the parameters of test sequence Symmetrical fault. Set
the duration of step 2 to 15 s. Also, set the value of the balanced currents
emulated by the internal relay test system during step 2 to 5.00 A. This is
equivalent to balanced currents of 5000 A in the electric power circuit
because 1000 A/1 A current transformers are used in this project.

40. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay for the complete duration of the test sequence (25 s). The
protective relay should trip after a certain time.

© Festo Didactic 52173-10 47


Exercise 1 – Overcurrent Protection  Procedure

Use DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA. Use the displayed
signals to determine the trip time of the protective relay when the value of the
emulated currents is 5000 A.

The trip time of the protective relay is about 6.4 s when the value of the
emulated currents is 5000 A.

The following figure shows the signals that should be displayed in SIGRA.

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

41. Do the trip times (operating times) that you recorded in steps 34, 37, and 40
confirm that the protective relay operates as an IDMT overcurrent relay with
an IEC standard inverse (SI) characteristic, a current setting of 1000 A, and a
time setting (time multiplier setting) of 1.50? Explain briefly.

48 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

a Refer to the equations presented in Table 1 of the discussion to calculate the


operating times of the protective relay that are expected.

Yes, because the time-current characteristic of an IDMT overcurrent relay


with an IEC standard inverse (SI) characteristic, a current setting of 1000 A,
and a time setting (time multiplier setting) of 1.50 indicates that the relay
should trip in 47.0 s, 11.4 s, and 6.4 s at values of current of 1250 A, 2500 A,
and 5000 A, respectively.

42. Reset the protective relay.

Overcurrent protection of a power transformer using a numerical overcurrent


relay

In this section, you will configure the numerical protective relay to implement
overcurrent protection of a power transformer and backup overcurrent protection
of the low-voltage side (secondary side) of the power transformer. You will then
perform relay testing using the internal relay test system of the protective relay to
make sure that the transformer overcurrent protection operates properly.

43. Figure 31 shows the example of a power transformer protected by a


numerical overcurrent protective relay that has been presented in the last
section of the discussion. In the next steps of this exercise, you will configure
the protective relay that you are using to implement overcurrent protection of
this power transformer and backup overcurrent protection of the low-voltage
side (secondary side) of this power transformer.

8 MVA
120 kV / 25 kV
120 kV 7%
175 MVA SC
To load

AC power
source F1 F2
50
51DT

Figure 31. Overcurrent protection of a power transformer using a numerical overcurrent relay
that combines the functions of ANSI devices no. 50 and no. 51DT.

44. The nominal value of the line currents at the primary of the power
transformer in the figure above is 38.5 A. Consequently, let us assume that
current transformers with a ratio of 40 A/1 A are used to measure the line
currents flowing through the transformer primary windings.

© Festo Didactic 52173-10 49


Exercise 1 – Overcurrent Protection  Procedure

In DIGSI 5, set the ratio of the current transformers to 40 A/1 A.

a Changing the ratio of the current transformers creates some inconsistencies in


the project. The presence of inconsistencies in the project is indicated by stop
icons in the Project tree. Do not be concerned about these icons as the
inconsistencies in the project will be removed later in the exercise.

45. In DIGSI 5, access the settings of the overcurrent protection function of the
protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1.

Turn time-current characteristic Inverse-T1 off, then turn time-current


characteristics Definite-T1 and Definite-T2 on. These settings cause the
overcurrent protection function of the protective relay to be a combination of
time-current characteristics Definite-T1 and Definite-T2.

In the working area of DIGSI 5, check the Definite-T1 and Definite-T2 check
boxes and uncheck the Inverse-T1 check box to show the time-current
characteristic of the overcurrent protection function resulting from the above
settings.

46. In DIGSI 5, adjust the current setting of the instantaneous overcurrent


protection of the protective relay to 400 A (same value as in the next to last
section of the discussion) by editing the value of the Threshold parameter in
time-current characteristic Definite-T1. Make sure that the Operate delay
parameter in time-current characteristic Definite-T1 is set to 0 s.

In DIGSI 5, adjust the current and time settings of the definite-time


overcurrent protection of the protective relay to 190 A and 1 s (same values
as in the next to last section of the discussion) by editing the values of the
Threshold and Operate delay parameters, respectively, in time-current
characteristic Definite-T2.

Notice that the project no longer contains inconsistencies.

Observe that time-current characteristic of the overcurrent protection function


displayed in the working area of DIGSI 5 is the same as the one shown in the
last section of the discussion.

a The x-axis in the diagram showing the time-current characteristic of the


protection function is graduated with values of current at the secondary
windings of the current transformers. These values of current must be
multiplied by the ratio of the current transformers (40 A/1 A in the currently-
open project) to obtain values of current at the primary windings of the current
transformers (i.e., values of current in the electric power circuit).

47. Load the configuration (i.e., the content of the project file currently open in
DIGSI 5) to the protective relay using DIGSI 5. This is necessary because
several settings of the protective relay have been modified.

50 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

48. In DIGSI 5, access the parameters of test sequence Symmetrical fault.

Set the value of the balanced currents emulated by the internal relay test
system during step 1 to 0.96 A. This is equivalent to balanced currents
of 38.4 A in the electric power circuit because 40 A/1 A current transformers
are used in this project.

Set the duration of step 2 to 5.0 s. Also, set the value of the balanced
currents emulated by the internal relay test system during step 2 to 21.05 A.
This is equivalent to balanced currents of 842 A in the electric power circuit
because 40 A/1 A current transformers are used in this project. Step 2 of test
sequence Symmetrical fault is now set to emulate the symmetrical fault at the
primary of the power transformer shown in Figure 31.

49. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay for the complete duration of the test sequence (15 s). The
protective relay should trip after a certain time.

50. Use DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA. Use these signals
to describe how the protective relay responded to the symmetrical fault at the
transformer primary emulated with the internal relay test system.

The instantaneous overcurrent function picked up as soon as the value of the


emulated currents passed from 38.4 A to 842 A because the current
setting (400 A) of the function is exceeded. This caused the protective relay
to trip immediately.

© Festo Didactic 52173-10 51


Exercise 1 – Overcurrent Protection  Procedure

Is the protective relay set to achieve proper overcurrent protection of the


power transformer?

Yes, the protective relay trips immediately when a symmetrical fault occurs at
the transformer primary.

The following figure shows the signals that should be displayed in SIGRA.

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

51. Reset the protective relay.

52. In DIGSI 5, access the parameters of test sequence Symmetrical fault.

Set the value of the balanced currents emulated by the internal relay test
system during step 2 to 8.33 A. This is equivalent to balanced currents
of 333 A in the electric power circuit because 40 A/1 A current transformers

52 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Procedure

are used in this project. Step 2 of test sequence Symmetrical fault is now set
to emulate the symmetrical fault at the secondary of the power transformer
shown in Figure 31.

53. In DIGSI 5, display the test environment for the protective relay that you are
using. Start test sequence Symmetrical fault, then observe the front panel of
the protective relay for the complete duration of the test sequence (15 s). The
protective relay should trip after a certain time.

54. Use DIGSI 5 to download the latest fault record from the protective relay and
display the signals contained in this fault record in SIGRA. Use these signals
to describe how the protective relay responded to the symmetrical fault at the
transformer secondary emulated with the internal relay test system.

The definite-time overcurrent function picked up as soon as the value of the


emulated currents passed from 38.4 A to 333 A because the current
setting (190 A) of the function is exceeded. After a delay of 1 s, the protective
relay tripped because the value of the emulated currents still exceeded the
current setting of the definite-time overcurrent function. On the other hand,
the instantaneous overcurrent protection did not pick up because the value of
the emulated currents never exceeded the current setting (400 A) of the
function.

© Festo Didactic 52173-10 53


Exercise 1 – Overcurrent Protection  Procedure

Is the protective relay set to achieve proper backup overcurrent protection of


the low-voltage side (secondary) of the power transformer?

Yes, the protective relay trips after a certain time delay (1 s in the present
case) when a symmetrical fault occurs at the low voltage side (secondary) of
the power transformer. The time delay is intended to provide enough time for
any protection at the transformer secondary to act before the backup
overcurrent protection of the low-voltage side of the power transformer trips.

The following figure shows the signals that should be displayed in SIGRA.

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

55. Reset the protective relay.

56. In DIGSI 5, restart the protective relay in the process mode to allow normal
operation of the unit. Once the restart process is completed, the display of

54 © Festo Didactic 52173-10


Exercise 1 – Overcurrent Protection  Conclusion

the protective relay no longer indicates that the unit is operating in the
simulation mode (the words Simulation mode no longer appear on the
display).

57. Close the project open in DIGSI 5 without saving the changes you made to
this project.

Close DIGSI 5.

Turn the protective relay off, then disconnect it from the host computer.

Delete the copy of the project file that you opened at the beginning of this
exercise.

CONCLUSION In this exercise, you saw that fuses or low-voltage circuit breakers (MCBs or
MCCBs) can be used to implement overcurrent and overload protection of power
lines, power transformers, and AC motors. You became familiar with the
operation and settings of the instantaneous (ANSI device no. 50), definite-time
(ANSI device no. 51DT), and inverse definite minimum time (ANSI device
no. 51I) overcurrent relays. You learned how to adjust the settings of an
overcurrent relay to obtain a specific time-current characteristic. You saw
applications where it is common to use overcurrent relays and high-voltage
circuit breakers in conjunction to achieve overcurrent protection of electrical
equipment. You learned how to use the internal relay test system of a numerical
protective relay to assess that the relay operates as expected.

REVIEW QUESTIONS 1. Describe the objective of overcurrent protection and the objective of overload
protection.

The objective of overcurrent protection is to prevent the flow of excessive


current in an electric power circuit (i.e., current whose value greatly exceeds
the nominal full-load current of the circuit) from damaging the circuit or from
initiating fire in the circuit that could lead to more serious damage and even
endanger people's lives. On the other hand, the objective of overload
protection is to prevent damage to a component in an electric power circuit
when this component is subjected to prolonged overload (i.e., to the flow of a
current whose value exceeds the nominal full-load current of the component
to a moderate extent).

2. Briefly explain what protective relay testing is.

In short, protective relay testing consists of conducting the tests necessary to


assess that the protective relay operates properly under certain specific
faults and/or abnormal operating conditions.

© Festo Didactic 52173-10 55


Exercise 1 – Overcurrent Protection  Review Questions

3. Briefly describe how the settings of an IDMT overcurrent relay affects its
time-current characteristic.

The type-of-characteristic parameter determines the shape of the time-


current characteristic of the IDMT overcurrent relay. The current setting
allows the time-current characteristic to be moved right or left (i.e., to
increase or decrease the current threshold of the relay). The time setting
(i.e., the time dial setting or the time multiplier setting) allows the time-current
characteristic to be moved up or down (i.e., to increase or decrease the
operating times of the relay).

4. Name applications where it is common to use overcurrent relays in


conjunction with HV circuit breakers to protect electrical equipment.

It is common to use overcurrent relays in conjunction with HV circuit breakers


to implement overcurrent protection of an important or valuable power line in
distribution networks and industrial applications. Similarly, it is common to
use an overcurrent protective relay in conjunction with an HV circuit breaker
to implement overcurrent and overload protection of an important or valuable
power transformer or ac motor.

5. Briefly describe how a single numerical overcurrent relay that combines the
functions of ANSI devices no. 50 and no. 51DT can be used to provide both
main overcurrent protection of a power transformer and backup overcurrent
protection of the low-voltage side of the power transformer.

The instantaneous overcurrent function (ANSI devices no. 50 function)


provides main overcurrent protection of the power transformer. Its current
setting is set to a value that makes the main overcurrent protection sensitive
enough to faults at the transformer primary and insensitive to faults at the
transformer secondary. The definite-time overcurrent function (ANSI devices
no. 51DT function) provides backup overcurrent protection of the low-voltage
side of the power transformer. Its current setting is set to a value that makes
the backup overcurrent protection sensitive enough to faults at the
transformer secondary and insensitive to the nominal value of the
transformer primary current. Its time setting is adjusted to the lowest value
that allows sufficient time for the protection at the power transformer
secondary to operate when a fault occurs at the transformer secondary.

56 © Festo Didactic 52173-10


Bibliography
Blackburn, J. Lewis and Domin, Thomas J., Protective Relaying, Principles and
Applications, 3rd ed., Taylor & Francis Group, 2007, ISBN 978-1-57444-716-3.

Russel Mason, C., The Art & Science or Protective Relaying, Wiley, 1964.

Westinghouse Electric Corporation, Applied Protective Relaying, 1976, Library of


Congress Card Number 76-8060.

GEC Alsthom Measurements Limited, Protective Relays – Application Guide,


3rd ed., 1987.

Institution of Electrical Engineers, Power System Protection - Volume 2, Systems


and Methods, The Electricity Training Association, 1995, ISBN 0-85296-836-1.

Alstom Grid, Network Protection & Automation Guide, 1st ed., 2011,
ISBN 978-0-9568678-0-3.

© Festo Didactic 52173-10 171

You might also like