PV SYSTEM DESIGN USING A SOLAREDGE THREE PHASE SE15K THREE PHASE SE16K THREE PHASE
INVERTER(5)(6) AND LARGER AND LARGER FOR MV GRID
Compatible Power Optimizers P600 P600, P700 P800 P600, P700 P800
Power Optimizers 13 12 13
Minimum String Length
PV Modules 26 24 26
Power Optimizers 30
Maximum String Length
PV Modules 60
Maximum Power per String 11250(7) 13500 12750(8) 15300 W
Parallel Strings of Different Lengths or Orientations Yes
(5)
P600 and P700 can be mixed in one string. It is not allowed to mix P600/P700/P800 with P300/P370/P500/P404/P405/P505 in one string.
(6)
In a case of odd number of PV modules in one string it is allowed to install one P600/P700/P800 power optimizer connected to one PV module. When connecting a single module to the P800p seal the unused
input connectors with the supplied pair of seals.
(7)
For SE27.6K, SE50K, SE55K, SE82.8K: It is allowed to install up to 13,500W per string when 3 strings are connected to the inverter and when the maximum power difference between the strings is up to
2,000W; inverter max DC power: 37,250W.
(8)
For inverters for MV grid: It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter and when the maximum power difference between the strings is up to 2,000W; inverter
max DC power: 45,000W.
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE