Phosphate Dissolves All The Suspended Solids by Making Soluble Complex Compounds Which May Precipitate at PH Higher Than 11

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

Phosphate dissolves all the suspended solids by making soluble complex compounds which may

precipitate at pH higher than 11.


Boiler feedwater systems using demineralized or evaporated makeup or pure condensate may be
protected from caustic attack through coordinated phosphate/pH control. Phosphate buffers the boiler
water, reducing the chance of large pH changes due to the development of high caustic concentrations.
Excess caustic combines with disodium phosphate and forms trisodium phosphate. Sufficient disodium
phosphate must be available to combine with all of the free caustic in order to form trisodium
phosphate.
Disodium phosphate neutralizes caustic by the following reaction:
Na2HPO4 + NaOH ® Na3PO4 + H2O
trisodium
disodium phosphate sodium hydroxide water
phosphate
This results in the prevention of caustic buildup beneath deposits or within a crevice where leakage is
occurring. Caustic corrosion (and caustic embrittlement, discussed later) does not occur, because high
caustic concentrations do not develop
Different forms of phosphate consume or add caustic as the phosphate shifts to the proper form. For
example, addition of monosodium phosphate consumes caustic as it reacts with caustic to form
disodium phosphate in the boiler water according to the following reaction:
NaH2PO4 + NaOH ® Na2HPO4 + H2O
monosodium sodium disodium
water
phosphate hydroxide phosphate
Conversely, addition of trisodium phosphate adds caustic, increasing boiler water pH:
Na3PO4 + H2O ® Na2HPO4 + NaOH
sodium
trisodium phosphate water disodium phosphate
hydroxide
Control is achieved through feed of the proper type of phosphate to either raise or lower the pH while
maintaining the proper phosphate level. Increasing blowdown lowers both phosphate and pH.
Therefore, various combinations and feed rates of phosphate, blowdown adjustment, and caustic
addition are used to maintain proper phosphate/pH levels.
Elevated temperatures at the boiler tube wall or deposits can result in some precipitation of phosphate.
This effect, termed "phosphate hideout," usually occurs when loads increase. When the load is
reduced, phosphate reappears.
Clean boiler water surfaces reduce potential concentration sites for caustic. Deposit control treatment
programs, such as those based on chelants and synthetic polymers, can help provide clean surfaces.
Where steam blanketing is occurring, corrosion can take place even without the presence of caustic,
due to the steam/magnetite reaction and the dissolution of magnetite. In such cases, operational
changes or design modifications may be necessary to eliminate the cause of the problem.
New boiler water treatment was developed using the alkalinity derived from phosphate alone,
eliminating sodium hydroxide – The sodium to phosphate ratio determines the pH of the water (3:1) –
Ratio of trisodium to monosodium or disodium phosphate is adjusted to desired pH and phosphate
levels can be attained without creating free caustic (3:1) – As trisodium phosphate hydrolyzes in the
water it produces a hydroxyl ion (OH) which controls the pH level – Monosodium or disodium phosphate
do not produce OH – Use of two different phosphates prevented complete program control at times.