Cablesizer Cable Sizing To IEC and NEC Standards PDF
Cablesizer Cable Sizing To IEC and NEC Standards PDF
Cablesizer Cable Sizing To IEC and NEC Standards PDF
Help
New Cable
1. Introduction
Cable (or conductor) sizing is the process of selecting appropriate sizes for electrical power cable
conductors. Cable sizes are typically decribed in terms of cross-sectional area, American Wire Gauge
(AWG) or kcmil, depending on geographic region.
The proper sizing of cables is important to ensure that the cable can:
Operate continuously under full load without being damaged
Provide the load with a suitable voltage (and avoid excessive voltage drops)
Withstand the worst short circuits currents flowing through the cable
Cable sizing methods do differ across international standards (e.g. IEC, NEC, BS, etc) and some standards
emphasise certain things over others. However the general principles that underpin all cable sizing
calculation do not change. When sizing a cable, the following general process is typically followed:
Gather data about the cable, its installation conditions, the load that it will carry, etc
Determine the minimum cable size based on ampacity (continuous current carrying capacity)
Determine the minimum cable size based on voltage drop considerations
Determine the minimum cable size based on short circuit temperature rise
Select the cable based on the highest of the sizes calculated in the steps above
2. Data Gathering
The first step is to collate the relevant information that is required to perform the sizing calculation.
Typically, you will need to obtain the following data:
(1) Basic cable data - the basic characteristics of the cable's physical construction, which includes:
Conductor material - e.g. copper or aluminium
Insulation or cable type - e.g. PVC, XLPE, EPR (for IEC cables), TW, THHW, XHH, etc (for NEC cables)
Number of cores - single core or multicore (e.g. 2C, 3C or 4C)
(2) Load data - the characteristics of the load that the cable will supply, which includes:
(3) Cable installation - how the cable will be installed, which includes:
Installation method - e.g. cable tray / ladder, in conduit / raceways, against a wall, in air, directly
buried, etc
Ambient or soil temperature at the installation site
Cable grouping, i.e. the number of other cables that are bunched together or installed in the same
area
Cable spacing, i.e. whether cables are installed touching or spaced
Soil thermal resistivity (for underground cables)
For single core three-phase cables, are the cables installed in trefoil or laid flat?
For example, suppose a cable had an ambient temperature derating factor of kamb = 0.94 and a grouping
derating factor of kg = 0.85, then the overall derating factor kd = 0.94x0.85 = 0.799. For a cable with a
base ampacity of 42A, the installed / derated ampacity would be I c = 0.799x42 = 33.6A.
A cable's conductor can be seen as an impedance and as a result, whenever current flows through a cable,
there will be a voltage drop across it, derived by Ohm's Law (i.e. V = IZ). The voltage drop will depend on
two things:
Current flow through the cable - the higher the current flow, the higher the voltage drop
Impedance of the conductor - the larger the impedance, the higher the voltage drop
The impedance of the cable is a function of the cable size (cross-sectional area) and the length of the
cable. Most cable manufacturers will quote a cable's resistance and reactance in Ohms/km or Ohms/ft.
For AC systems, the method of calculating voltage drops based on load power factor is commonly used.
Full load currents are normally used, but if the load has high startup currents (e.g. motors), then voltage
drops based on starting current (and power factor if applicable) should also be calculated.
For a three phase system:
Maximum voltage drops are typically specified because load consumers (e.g. appliances) will have an input
voltage tolerance range. This means that if the voltage at the appliance is lower than its rated minimum
voltage, then the appliance may not operate correctly.
In general, most electrical equipment will operate normally at a voltage as low as 80% nominal voltage.
For example, if the nominal voltage is 230VAC, then most appliances will run at >184VAC. Cables are
typically sized for a more conservative maximum voltage drop, in the range of 5 to 10% at full load.
During a short circuit, a high amount of current can flow through a cable for a short time. This surge in
current flow causes a temperature rise within the cable. High temperatures can trigger unwanted reactions
in the cable insulation, sheath materials and other components, which can prematurely degrade the
condition of the cable. As the cross-sectional area of the cable increases, it can dissipate higher fault
currents for a given temperature rise. Therefore, cables should be sized to withstand the largest short
circuit that it is expected to see.
The minimum cable size due to short circuit temperature rise is typically calculated with an equation of the
form:
As a rough guide, the following temperatures are common for the different insulation materials:
PVC 75 160
EPR 90 250
XLPE 90 250