IV Degree of Protection :
V Enclosure :
It consists of busbars in a protective enclosure, Cables are simply insulated with multiple layers of
1 including straight lengths, fittings, devices and PVC.
accessories.
2 High Short circuit strength & high fire protection Low Short circuit strength & low fire protection
VI Termination :
Direct termination through busbars The method for cable termination is very
1
cumbersome.
Termination is simple and easy. Additional supports are required to hold the cables
2 inside the panel.
Have a highly compact structure and can be bent up Cables are generally installed in bundles & with such
3 to 90 degree. a cross section that they can not be bent tightly.
Sr No. Busbar Trunking Cables
VII Time & cost consumption :
When sizing busbars the designer only needs to It is necessary to protect each cable
make calculations on a single riser which reduces individually with a fuse and when laying the
design time and costs. cables in bundles it is necessary to anchor
1 them properly so that they can withstand the
electrodynamic forces generated in the event
of a short ckt. So, the designers have to spend
more time on calculations.
VIII Use of additional items :
1 No additional supports are required. Heavy labor is required to lay the cables
No extra holes/cutouts are required. Holes to be made in the gland plate for fixing
2
cable glands
No cable tray is required, supported on ceiling / Cable tray or the digging of the trench is
3 wall. required to lay the cables
No special tools are required. Special tool are required for crimping the
4 cable lugs
Design verified switchgear assembly, limits from Limits depend on the laying method and cable
manufacturer’s catalogue accumulation. The derating factor must be
5
determined / calculated
Bus Duct Support System
a) Horizontal Bus Duct
Horizontal busduct will be supported at every 1.5mtr interval & at 150mm of
either side at bends & offsets.
Following are the supporting accessories used as per the Busduct rating