Manual Servicio Generator DQCC
Manual Servicio Generator DQCC
Manual Servicio Generator DQCC
Generator Set
QSK23G7 Engine with PowerCommand 3201 Control
English
Original Instructions 7-2016 960−0521 (Issue 18)
California
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects, and
other reproductive harm.
Table of Contents
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
ABOUT THIS MANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
TEST EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
HOW TO OBTAIN SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
AMPSENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. CONTROL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
CONTROL PANEL POWER ON/OFF MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
CONTROL PANEL ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
READING FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
MENU DISPLAY AND SWITCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
LANGUAGE/UNITS SELECTION MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
MAIN MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
ENGINE SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
ALTERNATOR SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
CONTROL SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
HISTORY/ABOUT SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
HISTORY/ABOUT SUBMENUS (CONT.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
PARALLEL DATA SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
POWER TRANSFER MAIN/SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
UTILITY (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
STATUS (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
TRANSFER CONTROL (PWR TRAN) SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
GENSET (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
LS-16L
iv Copyright 2016 Cummins Inc.
Important Safety Instructions
SAVE THESE INSTRUCTIONS − This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator set and Provide an adequate exhaust system to properly
batteries. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
ator, service personnel, or the equipment.
birth defects, and other reproductive harm.
This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or un-
moving parts.
safe practice which can result in severe person-
al injury or death. Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or un- connect starting batteries, negative (−) cable first.
safe practice which can result in personal injury This will prevent accidental starting.
or product or property damage. Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.
LS-16L
Copyright 2016 Cummins Inc. iii
ELECTRICAL SHOCK CAN CAUSE Keep multi-class ABC fire extinguishers handy.
SEVERE PERSONAL INJURY OR DEATH Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
Remove electric power before removing protective and flammable liquid fuels and gaseous fuels; Class
shields or touching electrical equipment. Use rub- C fires, live electrical equipment. (ref. NFPA No. 10).
ber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around Make sure that rags or combustible material are not
electrical equipment. Do not wear damp clothing left on or near the generator set.
(particularly wet shoes) or allow skin surface to be
damp when handling electrical equipment. Do not Make sure generator set is mounted in a manner to
wear jewelry. Jewelry can short out electrical con- prevent combustible materials from accumulating
tacts and cause shock or burning. under or near the unit.
Use extreme caution when working on electrical
components. High voltages can cause injury or Remove all unnecessary grease and oil from the
death. DO NOT tamper with interlocks. unit. Accumulated grease and oil can cause over-
heating and engine damage which present a poten-
Follow all applicable state and local electrical tial fire hazard.
codes. Have all electrical installations performed by
a qualified licensed electrician. Tag and lock open Keep the generator set and the surrounding area
switches to avoid accidental closure. clean and free from obstructions. Remove any de-
DO NOT CONNECT GENERATOR SET DIRECT- bris from the set and keep the floor clean and dry.
LY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set Do not work on this equipment when mentally or
into the utility line. This creates a potential for elec- physically fatigued, or after consuming any alcohol
trocution or property damage. Connect only or drug that makes the operation of equipment un-
through an approved isolation switch or an ap- safe.
proved paralleling device.
Substances in exhaust gases have been identified
GENERAL SAFETY PRECAUTIONS by some state or federal agencies as causing can-
Coolants under pressure have a higher boiling point cer or reproductive toxicity. Take care not to breath
than water. DO NOT open a radiator or heat ex- or ingest or come into contact with exhaust gases.
changer pressure cap while the engine is running. Do not store any flammable liquids, such as fuel,
To prevent severe scalding, let engine cool down
cleaners, oil, etc., near the generator set. A fire or
before removing coolant pressure cap. Turn cap
explosion could result.
slowly, and do not open it fully until the pressure has
been relieved. Wear hearing protection when near an operating
Used engine oils have been identified by some state generator set.
or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil, To prevent serious burns, avoid contact with hot
take care not to ingest, breathe the fumes, or con- metal parts such as radiator system, turbo charger
tact used oil. system and exhaust system.
LS-16L
iv Copyright 2016 Cummins Inc.
1. Introduction
ABOUT THIS MANUAL WARNINGIncorrect service or replacement of
parts can result in severe personal injury or
This manual provides PowerCommand Control death, and/or equipment damage. Service per-
3201 (PCC) calibration and adjustment procedures, sonnel must be trained and experienced to per-
control operation, alternator test and repair proce- form electrical and mechanical service. Read
dures. and follow Important Safety Instructions, on
pages iii and iv.
Operating and maintenance instructions are in the
applicable Operator’s Manual. Generator set trou- AMPSENTRY
bleshooting and repair (control and engine) infor-
mation is provided in the following manual.
Breakerless Conductor Connections
Troubleshooting and Repair Manual PowerCom-
mand Control QSX15, (QSK23), QSK45, QSK60 Overload and Short Circuit Protection of
Generator Sets, Bulletin No. 402-1419 (Not shown
on front cover, but includes QSK23 information.)
Generator
Read Important Safety Instructions and carefully NFPA 70: National Electrical Code compliant gen-
observe all instructions and precautions in this erator sets are required to be protected from an
manual. overload. Cummins Power Generation generator
sets with UL Listed AmpSentry Protective Relay as
TEST EQUIPMENT a standard feature do not require a circuit breaker or
other protective device for NEC compliance or UL
To perform the test procedures in this manual, the
2200 Listing.
following test equipment must be available
True RMS meter for accurate measurement of small CEC: Each conductor between the generator termi-
AC and DC voltages. nal and the point where load receives supply of gen-
Battery Hydrometer erator current must be protected by an overcurrent
Jumper Leads device in accordance with the requirement of CEC
Tachometer or Frequency Meter 14−100: Overcurrent Protection of Conductor.
Wheatstone Bridge or Digital Ohmmeter
UL label indicate to the Authority Having Jurisdiction
Variac
(AHJ) that the generator set incorporates a UL
Load Test Panel Listed Protective Relay that provides overload and
Megger or Insulation Resistance Meter short circuit protection for the generator and its
InPower Service Tool (PC based genset service conductors. The generator set does not require
tool) use of a circuit breaker or other protective device
HOW TO OBTAIN SERVICE for NFPA 70: National Electrical Code compliance
or UL 2200 Listing.
Always give the complete Model, Specification and
Serial number of the generator set as shown on the AmpSentry Labels
nameplate when seeking additional service infor-
mation or replacement parts. The nameplate is lo- These are typical labels for compliant generator
cated on the side of the generator output box. sets produced after January 2012.
The power on/off modes of the control panel and op- If Sleep mode is enabled in Auto mode, Sleep mode
erating software are Power On, Screen Saver and is activated when there are no unacknowledged
Sleep/Awake. faults and Screen Saver mode is active.
GRAPHICAL 0/MANUAL/AUTO
DISPLAY SWITCH
DISPLAY MENU EXERCISE MANUAL
SELECTION BUTTON & RUN/STOP
BUTTONS (1 OF 6) INDICATOR BUTTON &
INDICATOR
Warning Status Indicator: This yellow lamp is lit 0 (Off) position prevents the starting of the set (local
whenever the control detects a warning condition. or remote). If moved to 0 during set operation, will
After the condition is corrected, warning indicators cause an immediate engine shutdown (bypasses
can be reset by pressing the Fault Acknowledge cool-down timers). This hot shutdown should be
button. (It is not necessary to stop the generator set avoided, if possible, to help prolong the life of the en-
if the fault becomes inactive during genset opera- gine. Hot shutdowns are logged by the system soft-
tion.) ware.
Warning LED:
Reading Fault codes Using Warning/Shutdown
blink (2 seconds)
Indicators: If the Warning or Shutdown status indi-
cator is lit, press and hold the Fault Acknowledge The light will display the fault codes (active or inac-
button and release after one second or more. After tive) in succession, starting with the most recent. Up
one second, the Shutdown lamp will begin to blink to 32 (unacknowledged) fault codes can be stored in
the active fault code(s) as follows. control panel memory.
The Warning lamp is used to indicate the start of a To return the control to the most recent fault code,
new code. The Warning lamp will remain on for 2 press and release the Fault Acknowledge button
seconds, followed by the Shutdown lamp blinking (less than one second) and repeat procedure.
the fault code. This sequence occurs three times for
each code. The fourth flash of the Warning lamp in- When the fault code is acknowledged and cor-
dicates the beginning of the second fault code. rected, the recorded fault will be deleted from the
LED fault log, but will remain in a data log that main-
There are distinct pauses between repetitions of the tains a fault code history. (The InPower service tool
code blink transmissions of the Shutdown lamp. is required to view this data log.)
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA
GRAPHICAL
DISPLAY
MENU MENU
BUTTONS BUTTONS
ENGINE MORE>>
PAGE ALTERNATOR POWER TRAN OR _\_ PAGE
2-11 CONTROL HISTORY/ABOUT 2-16
PAGE PAGE
2-12 2-13
MENU B
SECTIO
N3
ADJUST
PARALLEL DATA PAGE
SETUP BACK<< 2-15
GRAPHICAL
SECTIO DISPLAY MENU
N3 A
MANF TEMP 75 F
MANF PRESS ABS 180 INHG Y
RAIL PRESS ABS 180 PSI
PUMP PRESS ABS 291 PSI B
FUEL INLET TEMP 172 F
COOLANT PRESSURE 59 PSI
If you press the “CONTROL” button in Menu A, the location. This button sequentially lights the LEDs to
Control submenu will appear (Figure 2-7). test the bar graph display.
MODEL 1750DQKB Y
VOLTAGE 416 WYE
FREQUENCY 60 B
RATING STANDBY
CONTROLLER VERSION
RTOP DN30008.DFA Y
BATS APR 23 1999
OP PANEL VERSION B
RTOP 1.09 AUG 17 1999
BATS 1.02 MAY 6 1999
PARALLEL DATA STATUS LINE: The top line of With the control panel 0/Manual/Auto switch in the
the graphical display is used to indicate the follow- Auto position, the opening and closing of the CB is
ing PARALLEL DATA status: controlled by the control system software. The CB
symbol will indicate an open or closed CB, but the
− STANDBY: Indicates no paralleling activity is occur- button will be inactive when the control is in Auto.
ring at present.
− DEAD BUS CLOSE: Indicates first genset in system In the Manual position, the CB must be closed by
to close to bus. this button. When manually closed and the CB
− SYNCHRONIZE: Genset is synchronizing to bus. opens, it must be closed again by using this button.
− LOAD SHARE: Genset has closed to bus and is To close the CB, press and hold the button until the
sharing load with other gensets in system. symbol indicates a closed CB. (CB close will occur
− LOAD GOVERN: Genset closed to bus in parallel only when setup conditions allow − dead bus or gen-
with utility (mains). erator synchronized with bus.)
BUS Voltage L-L: The BUS voltage Line-to-Line
(L1, L2 and L3) are measured between L1 to L2, L2
PARALLEL DATA
to L3 and L3 to L1, respectively.
If you press the “POWER TRANS” button in Menu The symbol displayed in the middle of the Power
A, the Power Transfer main menu will appear (Fig- Transfer main menu indicates which breaker (utility
ure 2-10). The Power Transfer Control (PTC) fea- or genset) is closed/opened to the load. The symbol
ture must be installed to display this menu. presently shown indicates that the utility breaker is
closed and supplying power to the load.
The PTC feature enables the PCC to monitor the
utility voltage (mains) and frequency for failure and The Power Transfer main menu also indicates if the
control the opening and closing of the contacts (cir- utility and the generator set are available to accept
cuit breakers) for the utility (S1) and the genset (S2). load. When the control detects that either source is
ready to accept load, UTILITY and/or GENSET will
If utility fails, the control will initiate the genset start- be displayed in inverse video.
ing sequence, open S1 and close S2 to the load.
When utility returns, the load is retransferred to the The Power Transfer main menu has four submenu
utility (S1 closes/S2 opens) and the control initiates groups. Refer to the page numbers shown in Figure
the genset shutdown sequence. 2-10 for the Power Transfer submenu descriptions.
MENU MENU
BUTTONS PAGE PTC STATUS LINE PAGE BUTTONS
2-18 2-21
B UTILITY GENSET B
PAGE STATUS
2-19 TRANSFER CONTROL
DEG −123 SYNCHRONIZING
PAGE MENU
2-20 A
If you press the “Status” button in the Power Trans- Retransfer inhibit is controlled by connecting a re-
fer Main menu, the Status submenus will appear mote contact between TB3-64 and TB3-65. Closing
(Figure 2-12). the contact enables the feature and opening the
contact disables it. When enabled, the event is dis-
Connected: Indicates which source(s) is con- played on the graphical display.
nected to the load.
SOFTWARE CALIBRATIONS The Setup and Adjust submenus allow you to cali-
brate the graphical display meters and to adjust sys-
If the base card has software assembly A026 F566 tem parameters, customer defined faults, generator
v1.0 on the U33 flash memory chip, you must use
set voltage/frequency and paralleling applications.
the latest software calibration for the control. If you
load an earlier software calibration onto a base card
with software assembly A026 F566 v1.0, the soft- CAUTIONImproper calibration or adjustment
ware calibration will fail, and the board will lock up
of the control can cause equipment malfunction
permanent-
ly. or damage. Calibration and adjustment must be
performed by technically qualified personnel
only.
+ OR − BUTTON + OR − BUTTON
MENU A MENU B
MENU
ENGINE MORE>> B ADJUST
ALTERNATOR POWER TRAN OR _\_ PARALLEL DATA
MENU
CONTROL HISTORY/ABOUT SETUP BACK<<
A
SETUP MENU 1
PAGE MENU
3-4 B
GOVERNING/VOLT REG Y
PAGE CUSTOMER FAULTS B NEXT
3-5 MENU
CALIBRATION
PAGE MENU
3-6 A
SETUP MENU 2
PAGE ABOVE
3-12 MENU
PAGE MENU
3-11 A
If you press the “CUSTOMER FAULTS” button in Use the button to move to each character position
the Setup menu, the Customer Faults submenus within the fault message line.
will appear (Figure 3-5).
With the desired character position selected, use +
There are a total of four customer fault inputs. or − buttons to select the appropriate character.
(Faults 3 and 4 paralleling only.) The message dis-
played at the bottom of the menu can be modified for Note: If these messages are changed, you should
note these changes in the Troubleshooting section
each of these faults in addition to selecting the fol-
of the Operator’s manual for this generator set.
lowing operating parameters for each fault.
Enable − On or Off
CUSTOMER FAULTS
Active − Closed or Open
Response − Shutdown, Cooldown, Derate or
Warning
Shutdown: Genset will immediately shut down. CUSTOMER FAULT1:
Normally used for engine faults. + ENABLE ON Y
ACTIVE CLOSED
Cooldown: Cooldown sequence will be initiated be- − B
RESPONSE WARNING
fore shutdown. Should not be used for engine faults.
Derate: Used to lower kW output of genset for warn- ***CUSTOMER FAULT1 *******
ings such as pre-high coolant temperature, etc. Par-
alleling application − controller will reduce precen-
tage of kW load sharing on the set. Non-paralleling
application − controller will lower percentage of kW
load by operating load shed relay contacts.
CUSTOMER FAULT2:
Warning: Display message, genset continues to + Y
operate.
− B
RESPONSE WARNING
Note: The Enable and the Active fields apply to the
Fault 1 and 4 submenus only. ***CUSTOMER FAULT2 ********
If you press the “ISOLATED BUS” button in the Set- PERM WIN-TIME: Adjusts the time period (in sec-
up menu, the Isolated BUS submenus will appear onds) for which the generator set must be synchro-
(Figure 3-7). nized with the system bus, before a breaker close
signal is issued by the PowerCommand control.
Note: Use the + and − buttons to increase or decrease Available range is 0.5 to 5 seconds. Recommended
the values in the following fields. Use the arrow () value for PowerCommand generator sets is 0.5 sec-
button to move the cursor within a field or to the next onds for isolated bus applications.
field. Exit menu to safe changes.
If you press the “UTILITY” button in the Setup menu, ABLE” function descriptions in wiring diagram, page
the Utility submenus will appear (Figure 3-8). 5-8.)
Note: Use the + and − buttons to increase or decrease KW GOVERN GAIN: This controls the rate that the
the values in the following fields. Use the arrow () generator set kW load is increased after the genera-
button to move the cursor within a field or to the next tor set has closed to the system bus when utility
field. Exit menu to safe changes. (mains) paralleled. Decreasing this value will result
in slower loading of the generator set.
BASE LOAD (%): This controls the maximum kW
load level that the generator set will operate at when KVAR GOVERN GAIN: This controls the rate that
paralleled with the utility (mains). The value shown the generator set kVAR load is increased after the
indicates the steady state load on the generator as a generator set has closed to the system bus when
percent of the generator set standby rating. utility (mains) paralleled. Decreasing this value will
result in slower loading of the generator set.
Check generator set ratings for maximum load level
at which the generator set should operate when par-
alleled with the utility (mains). Extended operation UTILITY
at load levels in excess of the generator set rating
can cause abnormal engine wear or premature en-
gine failure.
UTILITY:
PF LEVEL: Adjusts the power factor that the gener- + BASE LOAD 80% Y
ator set will run at when paralleled to the utility PF LEVEL 1.00
− RAMP LOAD 3 B
(mains). Recommended setting is 1.0.
RAMP UNLD 20
MODE MULTIPLE
RAMP LOAD TIME: This is the ramp time from
present set load to level determined by the load set
analog input. This is active when the control first en-
ters the load govern mode.
UTILITY:
RAMP UNLOAD TIME: This is the ramp time from + KW GOVERN GAIN 1.00 Y
present set load to 0 kW. This ramp is active when KVAR GOVERN GAIN1.00
−
the load set analog input is less than 0.5 volts.
UTILITY SENSORS Y
PAGE GENSET SENSORS B NEXT
3-15 MENU
TIMERS
PAGE
3-17
PTC MAIN MENU 2
PAGE
TEST/EXERCISE Y
3-18
If you press the “UTILITY SENSORS” button in the U CT RATIO: Enter the CT Ratio of the Utility L2 CT.
PTC Main Menu 1, the Utility Sensors submenus This is the Ratio to 1 Amp. Range: 1−18000 (1A).
will appear (Figure 3-10).
CAUTION This CT must be rated for 1 Amp out-
The following field descriptions show the valid field
put (e.g. NOT 5 Amp). Be sure CT secondary cir-
entries and default value (shown in parenthesis) for
cuit has burden resistor or a shorting jumper in
each field.
place before putting power through the CT. Ex-
Note: Use the + and − buttons to increase or decrease ample: CT Ratio = 2650:1. Thus enter 2650.
the values in the following fields. Use the arrow ()
button to move the cursor within a field or to the next U SENSOR TYPE: Enter the line-to-line (L-N) for 3
field. Exit menu to save changes. phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap-
U PT VOLT LL: Enter the value of the utility line-to-
plies to both the utility undervoltage and overvoltage
line voltage which yields 100% voltage at the termi-
sensors. Range: L−L, L−N (L−N).
nals of the utility (bus) PT module.
Range: 1−15000V, adjustable by standard nominal U <wye> <delta>: Enter utility connection type.
voltage values, 100V, 10V and 1V increments (1V). Range: Delta, Wye (Wye).
The 100% voltages for each of the four possible util- U UNLOADED KW: Enter the kW on utility Line 2 at
ity (bus) PT modules are as follows, based on mod- which the utility is considered as unloaded. This is
ule dash number: the L2 kW level at which a closed transition soft
−01 = 208 volts LL transfer will disconnect from the utility.
−02 = 416 volts LL
−03 = 600 volts LL UTILITY UNDERVOLTAGE: Non-adjustable field,
−04 = 120 volts LL always enabled.
Example 1: Nominal Utility voltage is 480V. This
means that utility (bus) PT module number −02 UTILITY OVERVOLTAGE, FREQUENCY: Used to
should be used. The voltage which will yield 100% enable or disable menu function. Choose Enabled
volts at this PT module is 416 per the above table. or Disabled (Enabled).
Thus enter 416V.
UV PICKUP: Enter a number between 85 and 100%
Example 2: Nominal Utility voltage is 4160V. A pri- of the nominal voltage (90%).
mary stage transformer with a ratio of 4200/240 is
used. This means that utility (bus) PT module num- UV DROP OUT: Enter a number between 75 and
ber −01 should be used. The voltage which will yield 98% of the under-voltage pick-up percentage
the 100% volts (208V from above table) is calcu- (90%).
lated as follows:
208 x (4200/240) = 3640. Thus enter 3640V.
UV DELAY: Enter a time between 0.1 and 5.0 sec-
U NOM VOLT LL: Enter the nominal utility line-to- onds (0.5 seconds).
line voltage. For example, 480, 4160, etc.. Range:
1−15000 V, adjustable by standard nominal voltage UV MIN PHASE: Displays the lowest line voltage of
values, 100V, 10V and 1V increments (1V). the three utility phases.
If you press the “GENSET SENSORS” button in the G RAMP UNLOAD: Enter the ramp time for the
PTC Main Menu 1, the Genset Sensors submenus genset ramp unload rate during a closed transtion
will appear (Figure 3-11). soft load retransfer. Ramp rate is −100%kW divided
by this time setting. Range: 0−900 seconds (20
The following field descriptions show the valid field sec).
entries and default value (shown in parenthesis) for
each field. G UNLOADED KW: Enter the %kW (based on
standby rating) that the genset is considered un-
Note: Use the + and − buttons to increase or decrease loaded. This is the %kW level at which a closed tran-
the values in the following fields. Use the arrow () sition soft retransfer will disconnect from the genset.
button to move the cursor within a field or to the next Range: 0−100% (5%).
field. Exit menu to save changes.
GEN UNDERVOLTAGE: Non-adjustable field, al-
G NOM VOLT LL: Non-adjustable field, displays
ways enabled.
current setting of genset nominal voltage. (See Ad-
just submenu to adjust the output voltage 5%.) GEN OVERVOLTAGE, FREQUENCY: Used to en-
able or disable menu function. Choose Enabled or
G SENSOR TYPE: Enter the line-to-line (L-N) for 3
Disabled (Enabled).
phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap- UV PICKUP: Enter a number between 85 and 100%
plies to both the genset undervoltage and overvol- of the nominal voltage (90%).
tage sensors. Range: L−L, L−N (L−N).
UV DROP OUT: Enter a number between 75 and
G BASE LOAD: Enter the maximum load the gen- 98% of the under-voltage pick-up percentage
set will carry during a closed transition. Range: (90%).
0−100% (80%).
UV DELAY: Enter a time between 0.1 and 5.0 sec-
G RAMP LOAD: Enter the ramp time for the genset onds (4 seconds).
ramp load rate during a closed transition soft load
transfer. Ramp rate is +100%kW divided by this time UV MIN PHASE: Displays the lowest line voltage of
setting. Range: 0−900 seconds (20 sec). the three genset phases.
If you press the “TIMERS” button in the PTC Main RETRANSFER: In a Emergency to Normal transfer
Menu 1, the Timers submenu will appear (Figure this function allows the utility to stabilize before the
3-12). load is applied.
If you press the “TEST/EXERCISE” button in the (TEST) switch, to operate with or without load. De-
PTC Main Menu 2, the Test/Exercise submenu will fault: OFF
appear (Figure 3-13).
EXER WITH LOAD: Feature allows genset Exer-
The following field descriptions show the valid field cise sequence, which is initiated through control
entries and default value (shown in parenthesis) for panel Exercise button to operate with or without
each field. load. Default: OFF
Changes are automatically saved when you exit this FREQUENCY: Used to adjust the frequency 3 Hz.
menu.
VOLTAGE/SPEED DROOP: These two submenus
If the generator set is operating in parallel with a sys- apply to a genset that has the paralleling option and
tem bus, the voltage and frequency adjustments are is configured to operate in droop mode.
MENU A
ADJUST:
MENU
ENGINE MORE>> + START DELAY 5 SEC Y
B STOP DELAY 11 SEC
ALTERNATOR _\_ − VOLTAGE 208 1.2% B
CONTROL HISTORY/ABOUT FREQ 60.0 HZ -0.0HZ
MENU B
ADJUST:
+ STANDBY Y
VOLTAGE DROOPOFF
ADJUST − BUS L1 480 B
BUS DATA POWER FACTOR 0.80
MENU VOLT 4.99 %
SETUP BACK<<
A
ADJUST:
+ STANDBY Y
SPEED DROOPOFF
− BUS FREQ 60.0 HZ
TOTAL KW 300 KW
FREQ 60.0 0.40 HZ
CONTROL
BOX DOOR
OPTIONAL OPTIONAL
RUN RELAYS SHUTDOWN
ALARM RELAY K16 CONTROL WIRING
K11, K12 & K13
ACCESS
TB8
CARD CAGE
CUSTOMER
K11, K12, K13
CONNECTIONS
NO NO NO
NC NC NC
COIL TB3-7
TB3-5
(SWITCHED B+) COM (GND)
K16
CUSTOMER
K16
CONNECTIONS
K16
K16
SHUTDOWN ALARM
NO
NC
COIL TB3-18
TB3-17
(COM ALARM) COM (GND)
MAGNETIC
PICKUP
SENSOR
ENGINE
FLYWHEEL
RING GEAR
In the event of an engine shutdown fault (red Shut- WARNING Accidental starting of the generator
down lamp), the control will stop the engine immedi- set can cause severe personal injury or death.
ately; an alternator shutdown fault, the engine will Prevent accidental starting by disconnecting
stop after the cool-down timer has timed out. If the the negative (−) cable from the battery terminal.
generator set is stopped for this reason, the opera-
tor can restart the set after making adjustments or When troubleshooting a set that is shut down, make
corrections. This section lists the warning and shut- certain the generator set cannot be accidentally re-
down codes/messages (Table 4-1), and suggests started as follows:
troubleshooting procedures (Table 4-2).
1. Move the O/Manual/Auto switch on the control
panel to the O (off) position.
Note: Displayed error codes that are not listed in 2. Turn off or remove AC power from the battery
Table 4-2 will require an authorized service represen- charger.
tative to correct the fault. Contact an authorized ser-
vice center for assistance. 3. Remove the negative (−) battery cable from the
generator set starting battery.
FAULT
ACKNOWLEDGE
BUTTON
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU
DISPLAY AREA
OPERATOR SWITCH
GRAPHICAL
PANEL PANEL
DISPLAY
Category B Fault Codes: Consist of faults that can Category E Fault Codes: Indicates non-critical op-
affect genset performance or cause engine, alter- erational status of generator set, external faults, or
nator, or connected equipment damage. Oper- customer fault inputs. May require repair by quali-
ate genset only when it is powering critical loads and fied service personnel.
B 554 Wrng Fuel rail pressure sensor B 1319 Wrng High alternator temp
B 555 Wrng Blowby pressure C 1321 Wrng Common warning driver
A 556 Shtdn Blowby pressure A 1322 Shtdn Load gov kW setpoint oor hi
A 586 Shtdn Run/Stop switch A 1323 Shtdn Load gov kW setpoint oor lo
A 587 Shtdn Run/Stop switch B 1324 Wrng Load gov kVAR oor hi
D 611 Wrng Engine hot B 1325 Wrng Load gov kVAR oor lo
D 688 Shtdn High oil level alarm B 1326 Wrng Backup starter disconnect
B 689 Wrng Crank shaft sensor A 1327 Shtdn Load gov kW analog oor
B 719 Wrng Blowby pressure sensor D 1328 Wrng Genset CB tripped
B 729 Wrng Blowby pressure sensor B 1329 Wrng AVR DC power failure
B 731 Wrng Cam/Crank misalignment A 1331 Shtdn AVR driver shorted
B 778 Wrng Camshaft sensor A 1332 Shtdn Manual switch oor lo
C 1118 Wrng Prelube relay driver A 1333 Shtdn Manual switch oor hi
B 1121 Wrng Failed to Disconnect A 1334 Shtdn Critical scaler oor
C 1219 Wrng Utility CB tripped
B 1335 Wrng Non critical scaler oor
C 1222 Wrng Power transfer not in auto
E 1336 Cooldown complete
C 1223 Wrng Utility frequency sensor
E 1337 None Network wink
C 1224 Wrng Gen over voltage sensor
E 1341 Shtdn Load demand stop
C 1225 Wrng Gen under voltage sensor
A 1342 Shtdn Slot 0 card
C 1226 Wrng Genset frequency sensor
A 1343 Shtdn Slot 1 card
E 1311 Shtdn/ Customer input #1
Wrng A 1345 Shtdn Slot 3 card
E 1312 Shtdn/ Customer input #2 A 1346 Shtdn Slot 4 incorrect
Wrng C 1351 Wrng Slot 4 / network enabled
E 1313 Shtdn/ Network Fault 1 C 1414 Wrng Run relay contact
Wrng
C 1415 Wrng Run relay driver
E 1314 Shtdn/ Network Fault 2
Wrng D 1416 Wrng Fail to shutdown
E 1315 Shtdn/ Network Fault 3 D 1417 Wrng Power down error
Wrng
B 1419 Wrng Fuel rail driver
E 1316 Shtdn/ Network Fault 4
B 1421 Wrng Timing rail driver #1
Wrng
B 1422 Wrng Timing rail driver #2
E 1317 Shtdn/ Customer input #3
Wrng C 1424 Wrng High side driver
E 1457 Wrng Fail to synchronize C 1498 Wrng Exercise run LED driver
E 1458 Wrng Phase rotation C 1499 Wrng Remote start LED driver
CODE: 146 Indicates engine is operating Check for the following condi-
LAMP: near cooling system capacity. tions:
Warning Increase in load or higher am- a. Make sure both ball
MESSAGE: bient temperature may cause valves in heater coolant
HIGH COOL- High Coolant Temp (151) shut- lines are open.
ANT TEMP down. Review 151 correction b. Coolant heater not con-
WARNING list for other possible causes. nected to power supply.
Check for blown fuse or
CODE: 151 Indicates engine has over- disconnected heater cord
LAMP: heated (coolant temperature and correct as required.
Shutdown has risen above the shutdown c. Check for low jacket wa-
MESSAGE: trip point). Allow engine to cool ter coolant level and re-
HIGH COOL- down completely before pro- plenish if required. Look
ANT TEMP ceeding with the following for possible coolant leaks
ALARM checks: and repair as required.
a. Check coolant level and
replenish if low. Look for CODE: 197 Indicates engine coolant level
coolant leaks and repair if LAMP: has fallen to an unacceptable
necessary. Warning level. If generator is powering
b. Check for obstructions to MESSAGE: critical loads and cannot be
cooling airflow and cor- COOLANT shut down, wait until next shut-
rect as necessary. LEVEL down period, then follow 235
c. Check fan belt and repair WARNING Coolant Level Alarm proce-
or tighten if necessary. dure. If engine can be stopped,
follow 235 procedure.
d. Check blower fan and cir-
culation pumps on re-
mote radiator installa-
tions.
e. Reset control and restart
after locating and correct-
ing problem.
EXCITER
RECONNECTION
STATOR
TERMINALS
END BRACKET
PMG
STATOR
END
STATOR BEARING
BLOWER PMG
ROTOR
COUPLING
EXCITER
ROTOR
ROTATING
RECTIFIER
ASSEMBLY
DRIVE ROTOR
DISCS
FRAME
END BRACKET/ENGINE
ADAPTOR
AIR DISCHARGE
PRESSURE COVERS
ROTOR
PLATE
SHAFT
FIGURE 5-1. TYPICAL GENERATOR
SURGE SUPPRESSER
REMOVE TO TEST
WINDING SCHEMATIC
WHEATSTONE
BRIDGE
MAIN STATOR
FRAME EXCITER EXCITER MAIN
MODEL WINDING WINDING WINDING WINDING
SIZE STATOR ROTOR ROTOR
11 12 17 07
5C 17 0.174 1.55 0.0068 N/A 0.0105 N/A
DFEG 5D 17 0.174 1.77 0.0057 N/A 0.0079 N/A
thru
DFEK 5E 17 0.174 1.96 0.0043 N/A 0.0068 N/A
5F 17 0.174 2.16 0.0037 N/A 0.0049 N/A
6G 17 0.158 1.44 0.0037 0.0148 N/A 0.011
DQCA 6H 17 0.158 1.54 0.0027 0.0108 N/A 0.0072
thru
DQCC 6J 17 0.158 1.73 0.0024 0.0096 N/A 0.006
6K 17 0.158 1.95 0.0019 0.0076 N/A 0.0052
TESTING THE PMG 2. Start the engine at the set and let the speed stabi-
lize.
WARNING HAZARDOUS VOLTAGE.
3. Measure voltage across lead pairs J10-1 & J10-4,
Touching uninsulated parts inside the con- J10-4 & J10-5, and J10-5 & J10-1. Voltage should
trol housing and power output boxes can be at least 150 VAC for 50 Hz sets and at least 180
result in severe personal injury or death. VAC for 60 Hz sets, and should be approximately the
Measurements and adjustments must be same for each set of leads. If the voltages are low or
done with care to avoid touching hazardous uneven, check all the leads and connections be-
voltage parts. tween the voltage regulator output stage module
and the PMG and repair as necessary before disas-
Stand on a dry wooden platform or rubber sembling the PMG.
insulating mat, make sure your clothing and
shoes are dry, remove jewelry and use tools 4. Stop the set and measure electrical resistance
across lead pairs J10-1 & J10-4, J10-4 & J10-5, and
with insulated handles. J10-5 & J10-1 with a Wheatstone bridge or digital
1. Disconnect plug J10 from the voltage regulator out- ohmmeter. Each winding should have a resistance
put stage module. of approximately 2.6 ohms.
UPPER FRONT
PANEL
LOWER BACK
PANEL
LOWER FRONT SIDE
PANELS PANEL
CONTROL HOUSING
CONTROL HOUSING
ACCESS COVERS
(BOTH SIDES)
STATOR ROTOR
ASSEMBLY ASSEMBLY
LIFT LIFT
USE FORKLIFT OR
OTHER ADEQUATE
LIFTING DEVICE TO
SLIGHTLY LIFT
ROTOR SHAFT UNTIL
ROTOR CAN BE
SUPPORTED BY
HOIST/SLING.
BLOCKING UNDER
STATOR MOUNTING FEET ROTOR ENGINE FLYWHEEL
ASSEMBLY BRACKETS ASSEMBLY HOUSING
PMG
STATOR
END
STATOR BEARING
BLOWER PMG
ROTOR
COUPLING
EXCITER
ROTOR
ROTATING
RECTIFIER
ASSEMBLY
DRIVE ROTOR
DISCS
FRAME
END BRACKET/ENGINE
ADAPTOR
AIR DISCHARGE
PRESSURE COVERS
ROTOR
PLATE
SHAFT
STATOR LIFT
(EXAMPLE)
ROTOR LIFT
(EXAMPLE)
34. Carefully remove the capscrews and flat wash- FIGURE 5-10. GENERATOR LIFTING POSITIONS
ers that secure the drive discs to the engine fly-
wheel.
33. Lift slightly on endbracket and remove wooden 43. Connect the negative (-) battery cable and test
shims holding rotor on center with stator. the generator set for operation. If objectionable
vibration is present, refer to Aligning Generator
34. Securely tighten the endbracket fasteners. with Engine procedure later this section.
SEE DETAIL A
CLAMP DIAL
INDICATOR
FLEX
DISCS
GENERATOR
MOUNTING BOLT
AND ENGINE AXIAL
TO DISC
CRANKSHAFT ALIGNMENT, SEE
MEASUREMENT
CENTERLINE FIGURE 4-13
DETAIL A
SHIMS
+.010 +.010
MEASURED AT
BOLT CIRCLE
DIAMETER
-.002
-.004
10.7
IN.
-.010
-.010
-.015 -.015
ANGULAR ALIGNMENT,
SEE FIGURE 4-11
GENERATOR
SHAFT HUB
DIAL
INDICATOR
GENERATOR AND
ENGINE CLAMP
CRANKSHAFT SEE DETAIL A FAN HOUSING
CENTERLINE
DETAIL A
FUEL TRANSFER
CONTROL
FUEL ALARM
PANEL
EXTERNAL
FUEL FILL BOX
FUEL FILL
(INTERNAL)
OVERFLOW
PREVENTIVE
VALVE (OFPV)
(OPTIONAL)
EXTERNAL
FUEL FILL BOX
The following paragraphs describe the operation of The Solenoid Override Button is only provided on
the external alarm panel components. the Alarm Panel when the optional overflow preven-
tive valve (Figure 7-3) is provided with the external
Overfill Indicator/Horn/Mute Button fill box feature.
FUEL
GAUGE
OVERFILL
INDICATOR
SOLENOID OVERRIDE
BUTTON (OPTIONAL) HORN
The rupture basin leak detect switch (Figure 7-5) is 3. Activate leak detect switch (move float up-
provided with sub-base fuel tanks used with the op- ward).
tional enclosure. This switch should be checked
once a year to make sure switch is properly operat- 4. Check control display for Rupture Basin fault
ing. In some areas, weekly inspections may be re- message. If no indication of fault, repair defec-
quired by safety code regulations. tive circuit. Refer to Enclosure/Options Wiring
(DQCA−DQCC) diagram in Section 7.
To test the leak detect switch:
1. Remove the pipe fitting/switch assembly from 5. Apply thread sealant to pipe fitting and install
the rupture basin tank. switch assembly.
INTERNAL FUEL
ALARM PANEL
Overfill Indicator/Horn/Silence Button Indicates the amount of fuel that is contained in the
sub-base tank.
The overfill alarm Indicates that the fuel has Test Button
reached an abnormally high level (95%). Immedi-
ately stop adding fuel. It also indicates a possible Press the TEST switch to test the indicator light and
failure of the “pump-off” float gauge for fuel systems the horn. The test will remain active for as long as
that contain the fuel transfer pump. the button is pressed.
OVERFILL
INDICATOR/ FUEL
TEST BUTTON GAUGE
HORN
HORN
SILENCE
BUTTON
HORN SILENCE/
TEST BUTTON
The rupture basin leak detect switch (Figure 6-4) is 3. Activate leak detect switch (move float up-
provided with sub-base fuel tanks used with the op- ward).
tional enclosure. This switch should be checked
once a year to make sure switch is properly operat- 4. Check control display for Rupture Basin fault
ing. In some areas, weekly inspections may be re- message. If no indication of fault, repair defec-
quired by safety code regulations. tive circuit. Refer to Enclosure/Options Wiring
(DQCA−DQCC) diagram in Section 7.
To test the leak detect switch:
1. Remove the pipe fitting/switch assembly from 5. Apply thread sealant to pipe fitting and install
the rupture basin tank. switch assembly.
ENCLOSURE
SUB-BASE
LEAK DETECT FUEL TANK
SWITCH ASSEMBLY
GENERAL
This section consists of the schematic and connection wiring diagrams referenced in the text. The following
drawings are included.
Page 9−3 through 9−4, AC RECONNECT WIRING DIAGRAM
Page 9−5 through 9−15 DC POWER AND STARTER WIRING (DFEG−DFEK)
Page 9−16 through 9−18 ALARM PANEL WIRING, WITH FUEL PUMP CONTROL (DFEG−DFEK)
Page 9−19 through 9−25 DC POWER AND STARTER WIRING (DQCA−DQCC)
Page 9−26 through 9−27 ENCLOSURE/OPTIONS WIRING (DQCA−DQCC)
Page 9−28 through 9−29 NEC ENTRANCE BOX OPTION INSTALLATION DRAWING
Page 9−30 through 9−43 GENSET INSTALLATION DRAWINGS
Page 9−36 through 9−48 PC 3201 WIRING
9-2
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
No. 625-3100 sh 1 of 2
Rev. H
Modified 2/22/2011
AC RECONNECT WIRING DIAGRAM (Sh 1 of 2)
No. 625-3100 sh 2 of 2
Rev H
Modified 2/22/2011
AC RECONNECT WIRING DIAGRAM (Sh 2 of 2)
No. 630-2592 sh 1 of 11
Rev. F
Modified 7/05
DC POWER AND STARTER WIRING (DFEG−DFEK)
No. 630-2592 sh 2 of 11
Rev. F
Modified 7/05
ALARM PANEL WIRING (DFEG−DFEK)
No. 630-2592 sh 3 of 11
Rev. F
Modified 7/05
CUSTOMER CONNECTIONS TERMINAL STRIP (DFEG−DFEK)
No. 630-2592 sh 4 of 11
Rev. F
Modified 7/05
ENGINE SENSORS (DFEG−DFEK)
No. 630-2592 sh 5 of 11
Rev. F
Modified 7/05
CONTROL WIRING (DFEG−DFEK)
No. 630-2592 sh 6 of 11
Rev. F
Modified 7/05
GENERATOR/BUS CONNECTIONS (DFEG−DFEK)
No. 630-2592 sh 7 of 11
Rev. F
Modified 7/05
CUSTOMER CONNECTIONS (DFEG−DFEK)
No. 630-2592 sh 8 of 11
Rev. F
Modified 7/05
CUSTOMER CONNECTIONS (DFEG−DFEK)
No. 630-2592 sh 9 of 11
Rev. F
Modified 7/05
CUSTOMER CONNECTIONS (DFEG−DFEK)
No. 630-2592sh 10 of 11
Rev. F
Modified 7/05
No. 630-2592sh 11 of 11
Rev. f
Modified 7/05
FUEL TANK WIRING, ENCLOSURE
No. 541-1066 sh 2 of 4
Rev. C
Modified 9/04
ALARM PANEL WIRING, WITH FUEL PUMP CONTROL (DFEG−DFEK)
No. 541-1066 sh 3 of 4
Rev. C
Modified 9/04
ALARM PANEL WIRING, WITHOUT FUEL PUMP CONTROL (DFEG−DFEK)
No. 541-1066 sh 4 of 4
Rev. C
Modified 9/04
ALARM PANEL WIRING, REVISED WITH FUEL PUMP CONTROL (DFEG−DFEK)
No. 630-2878 sh 1 of 7
Rev. D
Modified 5/27/2011
DC POWER AND STARTER WIRING (DQCA−DQCC)
No. 630-2878 sh 2 of 7
Rev. D
Modified 5\27\2011
ENGINE SENSORS (DQCA−DQCC)
No. 630-2878 sh 3 of 7
Rev. D
Modified 5/27/2011
CONTROL WIRING (DQCA−DQCC)
No. 630-2878 sh 4 of 7
Rev. D
Modified 5/27/2011
GENERATOR/BUS CONNECTIONS (DQCA−DQCC)
No. 630-2878 sh 5 of 7
Rev. D
Modified 5/27/2011
CUSTOMER CONNECTIONS (DQCA−DQCC)
No. 630-2878 sh 6 of 7
Rev. D
Modified 5/27/2011
No. 630-2878 sh 7 of 7
Rev. D
Modified 5/27/2011
CUSTOMER CONNECTIONS (DQCA−DQCC)
No. A034P810 sh 1 of 13
Rev F
Modified 5/04/2015
ENGINE TO GENERATOR SET HARNESS CONNECTIONS (Sh 1 of 13)
No. A034P810 sh 2 of 13
Rev. F
Modified 5/04/2015
OPERATOR PANEL TO CONTROL BOARD CONNECTIONS (Sh 2 of 13)
No. A034P810 sh 3 of 13
Rev F
Modified 5/04/2015
ENGINE HARNESS AND ECM CONNECTIONS (Sh 3 of 13)
No. A034P810 sh 4 of 13
Rev. F
Modified 5/04/2015
ENGINE HARNESS AND ECM (Sh 4 of 13)
No. A034P810 sh 5 of 13
Rev F
Modified 5/04/2015
LOW VOLTAGE P80 ALTERNATOR CONNECTIONS (Sh 5 of 13)
No. A034P810 sh 6 of 13
Rev. F
Modified 5/04/2015
MEDIUM/HIGH VOLTAGE P80ALTERNATOR CONNECTIONS (Sh 6 of 13)
No. A034P810 sh 7 of 13
Rev F
Modified 5/04/2015
MEDIUM/HIGH VOLTAGE P80 ALTERNATOR CONNECTIONS (Sh 7 of 13)
No. A034P810 sh 8 of 13
Rev. F
Modified 5/04/2015
GENERATOR AND CUSTOMER HARNESS (Sh 8 of 13)
No. A034P810 sh 9 of 13
Rev F
Modified 5/04/2015
CUSTOMER HARNESS CONNECTIONS (Sh 9 of 13)
No. A034P810 sh 10 of 13
Rev. F
Modified 5/04/2015
GENERATOR SET UTILITY BUS VOLTAGE AND CURRENT SENSING (Sh 10 of 13)
No. A034P810 sh 11 of
13
Rev F
Modified 5/04/2015
GROUND FAULT RELAY, AUDIBLE ALARM (Sh 11 of 13)
No. A034P810 sh 12 of
13
Rev. F
Modified 5/04/2015
CONGFIGURABLE AND CIRCUIT BREAKER RELAYS (Sh 12 of 13)
No. A034P810 sh 13 of
13
Rev F
Modified 5/04/2015
CONTROL BOX WIRING DIAGRAM (Sh 13 of 13)