ACS-13A
INSTRUCTION MANUAL
Preface
Thank you for purchasing of our microcomputer based digital indicating controller ACS-13A. This manual contains
instructions for the mounting, functions, operations and notes when operating the ACS-13A. To prevent accidents
arising from the misuse of this controller, please ensure the operator receives this manual.
Characters used in this manual:
Number, / -1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
Indication
Notes
• This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or malfunction may occur.
• The contents of this instruction manual are subject to change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if there are any
doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed within a control panel. If it is not, measures must be taken to
ensure that the operator cannot touch power terminals or other high voltage sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a result of
using this product, including any indirect damage.
Safety precautions (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”. Depending on circumstances, procedures
indicated by Caution may be linked to serious results, so be sure to follow the directions for usage.
Procedures which may lead to dangerous conditions and cause death or serious
Warning injury, if not carried out properly.
Caution Procedures which may lead to dangerous conditions and cause superficial to medium
injury or physical damage or may degrade or damage the product, if not carried out
properly.
Warning
• To prevent an electric shock or fire, only Shinko or qualified service personnel may handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken
by Shinko or qualified service personnel.
Safety precautions
• To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify
correct usage after consulting the purpose of use with our agency or main office. (Never use this instrument for
medical purposes with which human lives are involved.)
• External protection devices such as protection equipment against excessive temperature rise, etc. must be installed,
as malfunction of this product could result in serious damage to the system or injury to personnel. Also proper
periodic maintenance is required.
• This instrument must be used under the conditions and environment described in this manual. Shinko Technos Co.,
Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under
conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of
mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final
use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.
2
1. Installation precautions
Caution
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not
change rapidly, and without icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing.
• No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the unit
Note • Do not install this instrument near flammable material even though the case of this
instrument is made of flame-resistant resin.
Avoid setting this instrument directly on flammable material.
2. Wiring precautions
Caution
• Do not leave bits of wire in the instrument, because they could cause fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which the M3 screw fits when wiring the
ACS-13A.
• The terminal block of this instrument is designed to be wired from the left side. The lead wire
must be inserted from the left side of the terminal, and fastened with the terminal screw.
• Tighten the terminal screw to within the specified torque. If excessive force is applied to the
screw when tightening, the terminal screw or case may be damaged.
• When using a terminal cover, pass terminal wires numbered 7 to 12 into the holes of the terminal
cover.
• This instrument does not have a built-in power switch, circuit breaker or fuse.
It is necessary to install them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• Do not apply a commercial power source to the sensor which is connected to the input terminal
nor allow the power source to come into contact with the sensor.
• Use a thermocouple and compensating lead wire according to the sensor input specifications
of this controller.
• Use the 3-wire RTD according to the sensor input specifications of this controller.
• (+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC differs from that of 0 to 1V DC.
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
• When using a relay contact output type, externally use a relay according to the capacity of the
load to protect the built-in relay contact.
• When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or load wires to
avoid external interference.
4
1. Model
1.1 Model
*1: Alarm types (9 types and No alarm action) and Energized/Deenergized can be selected by keypad.
*2: Thermocouple, RTD, DC current and DC voltage can be selected by keypad.
For DC current input, connect 50 shunt resistor (sold separately) externally.
*3: Supply voltage 100 to 240V AC is standard. When ordering 24V AC/DC, enter “1” after the input code.
(Fig.1.2-1)
5
2. Name and functions of the sections
(1)
(2)
(3) (7)
(4)
(5)
(6)
(8) (11)
(9) (10)
(12)
(Fig. 2-1)
Display
(1) PV indicator : Lights when PV is indicated in the PV/SV display mode.
(2) PV display : Indicates the PV (process variable).
(3) SV indicator : Lights when SV is indicated in the PV/SV display mode.
(4) MEMO indicator : Lights when Set value memory external selection (SM option) is added.
(5) MEMO display : Indicates the set value memory number.
(6) SV display : Indicates the SV (Main set value).
(7) Action indicators
O1 (OUT1) : Lights when control output is ON or when Heating output
(D option) is ON. For DC current output type, flashes
corresponding to the MV in 0.25 second cycles.
O2 (OUT2) : Lights when cooling output (D option) is ON.
EV1 : Lights when Alarm 1 output is ON.
EV2 : Lights when Alarm 2 output (A2 option) is ON or when Heater
burnout alarm (W, W3 option) is ON.
AT : Flashes while AT (auto-tuning) or auto-reset is performing.
T/R : Lights during Serial communication (C5 option) (TX output).
LOCK : Lights when Lock 1, Lock 2 or Lock 3 is selected.
Key operations
(8) Increase key : Increases the numeric value.
(9) Decrease key : Decreases the numeric value.
(10) Mode key : Selects the setting mode, or registers the set value.
To register the set (selected) value, press this key.
(11) OUT/OFF key : Switches control output ON/OFF or Auto/Manual control.
To release the control output ON/OFF, press this key for approx. 1sec.
(12) Console connector:
By connecting to the USB communication cable (CMA, sold separately), the following operations
can be conducted from the external computer using the Console software SWS-ACS01M.
• Reading and setting of SV, PID and various set values
• Reading of PV and action status
• Function change
6
3. Mounting to the control panel
3.1 External dimensions (Unit: mm)
(Fig. 3.1-1)
Caution
If lateral close mounting is used for the controller, IP66 specification (Dust-proof/Drip-proof)
may be compromised, and all warranties will be invalidated
+0.5
0
45
75
n x 48-3 +0.5
45 +0.5
0
0
(Fig. 3.3-1)
7
3.4 Mounting and removal to/from the control panel
Caution
As the mounting frame is made of resin, do not use excessive force while tightening
screws, or the mounting frame could be damaged.
Tighten screws with one rotation upon the screw tips touching the panel.
The torque is approximately 0.05 to 0.06 N•m.
(Fig.3.4-1) (Fig.3.4-2)
(Fig.3.4-3)
8
4. Wiring
Warning
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in severe injury
or death due to Electric Shock.
POWER SUPPLY
+ +
1 1 13 7
3A
24V AC/DC 100 to 240V AC CT1 O1 NO 250V
2 2 14 8 AC
- DC -
CT2
+
3 3A
15 9
EV1 NO 250V DC TC RTD
DI RS-485 + + A
4 AC DI2 YA(-) 16 10
+ 0 to 1V
5 DI1 YB(+) 17 4 to 20mA 11
3A B
O2/EV2 NO 250V 0 to 20mA
6 AC COM SG 18 12
- - - - B
(Fig. 4-1)
• POWERSUPPLY: For a 24V AC/DC power source, do not confuse polarity when using direct
current (DC).
• EV1 : Alarm 1 output
• O2/EV2: Cooling output (D option), Alarm 2 output (A2 option) or
Heater burnout alarm output (W, W3 option)
• O1 : Control output or Heating output (D option)
• DC : DC current, DC voltage input
(For DC voltage input, + side terminal number differs depending on the voltage input.)
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
• TC : Thermocouple input
• RTD : Resistance temperature detector input
• CT1 : CT input 1 (W, W3 option)
• CT2 : CT input 2 (W3 option)
• DI : Contact input (SM option)
• RS-485 : Serial communication RS-485 (C5 option)
5.8mm or less
(Fig. 4.2-1)
9
4.3 Terminal cover
When using a terminal cover (sold separately), pass terminal wires numbered 7 to 12 into the holes of
the terminal cover.
Terminal cover
(Fig. 4.3-1)
(13)
CT1 input Terminals
(14)
Power
supply
CT
Heater
(Fig. 4.4-1)
In the case of 3-phase (W3 option), pass any 2 lead wires of R, S, T into the CT, and connect them with
CT1 (13, 14) and CT2 terminals (14, 15). (Fig.4.4-2)
(Fig. 4.4-2)
10
5. Operation flowchart For 3 seconds after the power is turned on, the PV display
Power ON indicates the input type, and the SV display indicates input
range high limit value (TC, RTD) or scaling high limit value (DC
voltage, DC current).
Control output OFF/Manual control Control output OFF PV/SV display mode (Automatic control) (Approx. 3sec) Output MV indication
(Approx. 1sec)
Auto/Manual control
[Key operation]
• + : Press the key while pressing the key. Alarm 2 type PV color range
• + (Approx.3sec): Press the key for approx. 3 seconds while holding
down the key.
• + (Approx.3sec): Press the key for approx. 3 seconds while holding
Alarm 1 Backlight time
down the key. Energized/
• : This means that if the (MODE) key is pressed, the unit proceeds to the Deenergized
next setting mode.
[Setting item] Alarm 2 Indication
• PV display indicates setting item characters, and SV display indicates default value. Energized/ selection when
(*1) CT1 current value and character are indicated alternately. Deenergized output OFF
(*2) CT2 current value and characters are indicated alternately.
• Setting items with dotted lines (shaded) are optional, and they appear only OUT1
when the options are added. rate of change
limit
11
6. Setup
Setup should occur before using this controller, to set the Input type, Alarm type, Control action, etc.
according to the users’ conditions.
Default values: Input (K, -200 to1370 ), Alarm 1 (No alarm action), Reverse (Heating) action
If the users’ specification is the same as the default value of the ACS-13A, it is not necessary to set up the
controller. Proceed to Chapter “7. Settings”.
Sensor input
PV display SV display PV display SV display
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
Scaling high limit value
0 to 5V DC
1 to 5V DC
0 to 10V DC
12
6.3 Setup mode
To enter the Setup mode, press the key for approx. 3 seconds while holding down the key in the
PV/SV display mode.
13
PV filter time constant setting 0.0 seconds
• Sets PV filter time constant.
If the value is set too large, it affects control result due to the delay of response.
• Setting range: 0.0 to 10.0 seconds
OUT1 high limit setting 100%
• Sets the high limit value of OUT1.
Not available if OUT1 is ON/OFF action
• Setting range: OUT1 low limit value to 100%
(DC current output type: OUT1 low limit value to 105%)
OUT1 low limit setting 0%
• Sets the low limit value of OUT1.
Not available if OUT1 is ON/OFF action.
• Setting range: 0% to OUT1 high limit value
(DC current output type: -5% to OUT1 high limit value)
OUT1 ON/OFF action hysteresis setting 1.0
• Sets ON/OFF action hysteresis for OUT1.
Available only when OUT1 is ON/OFF action
• Setting range: 0.1 to 100.0 ( ), DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection.)
OUT2 action mode selection Air cooling
• Selects OUT2 action from air, oil and water cooling. OUT2 proportional band
Not available if the D option is not added or if OUT2 Air cooling
is ON/OFF action
• Air cooling (linear characteristic) Oil cooling
Water cooling
Oil cooling (1.5th power of the linear characteristic)
Water cooling (2nd power of the linear characteristic) SV setting
(Fig. 6.3-1)
OUT2 high limit setting 100%
• Sets OUT2 high limit value.
Not available if the D option is not added or if OUT2 is ON/OFF action
• Setting range: OUT2 low limit value to 100%
OUT2 low limit setting 0%
• Sets OUT2 low limit value.
Not available if the D option is not added or if OUT2 is ON/OFF action
• Setting range: 0% to OUT2 high limit value
Overlap band/Dead band setting 0.0
• Sets the overlap band or dead band for OUT1 and OUT2.
+ Set value: Dead band, –Set value: Overlap band
Available only when the D option is added
• Setting range: -100.0 to 100.0 ( ), DC voltage, current input: -1000 to 1000
(The placement of the decimal point follows the selection.)
OUT2 ON/OFF action hysteresis setting 1.0
• Sets ON/OFF action hysteresis for OUT2.
Available when the D option is added, and when OUT2 is ON/OFF control action.
• Setting range: 0.1 to 100.0 ( ), DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection.)
14
Alarm 1 type selection No alarm action
• Selects an Alarm 1 type. (Refer to “11.4 Alarm action” on p.29.)
: No alarm action
: High limit alarm
: Low limit alarm
: High/Low limits alarm
: High/Low limit range alarm
: Process high alarm
: Process low alarm
: High limit alarm with standby
: Low limit alarm with standby
: High/Low limits alarm with standby
Alarm 2 (A2) type selection No alarm action
• Selects an Alarm 2 type. (Refer to “11.4 Alarm action” on p.29.)
Available only when Alarm 2 (A2) option is added
• Selection items are the same as those of Alarm 1.
Alarm 1 Energized/Deenergized selection Energized
• Selects Energized/Deenergized status for Alarm 1. (See p.18.)
Not available if No alarm action is selected during Alarm 1 type selection
• : Energized
: Deenergized
Alarm 2 Energized/Deenergized selection Energized
• Selects Energized/Deenergized status for Alarm 2. (See p.18.)
Not available if Alarm 2 (A2) option is not added or if No alarm action is selected during
Alarm 2 type selection
• Selection items are the same as those of Alarm 1 Energized/Deenergized selection.
Alarm 1 hysteresis setting 1.0
• Sets hysteresis for Alarm 1.
Not available if No alarm action is selected during Alarm 1 type selection
• Setting range: 0.1 to 100.0 ( ), DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection.)
Alarm 2 hysteresis setting 1.0
• Sets hysteresis for Alarm 2.
Not available if Alarm 2 (A2) option is not added or if No alarm action is selected during
Alarm 2 type selection
• Setting range: 0.1 to 100.0 ( ), DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection.)
Alarm 1 action delayed timer setting 0 seconds
• Sets action delayed timer for Alarm 1.
When setting time has elapsed after the input enters the alarm output range, the alarm
is activated.
Not available if No alarm action is selected during Alarm 1 type selection
• Setting range: 0 to 10000 seconds
Alarm 2 action delayed timer setting 0 seconds
• Sets action delayed timer for Alarm 2.
When setting time has elapsed after the input enters the alarm output range, the alarm
is activated.
Not available if Alarm 2 (A2) option is not added or if No alarm action is selected during
Alarm 2 type selection
• Setting range: 0 to 10000 seconds
15
SV rise rate setting 0 /min.
• Sets SV rise rate (rising value for 1 minute).
Setting to 0 disables the function.
• Setting range: 0 to10000 /min. ( /min.)
Thermocouple, RTD input with a decimal point: 0.0 to1000.0 /min. ( /min.)
DC voltage, current input: 0 to 10000/min.
(The placement of the decimal point follows the selection.)
SV fall rate setting 0 /min.
• Sets SV fall rate (falling value for 1 minute).
Setting to 0 disables the function.
• Setting range: 0 to10000 /min. ( /min.)
Thermocouple, RTD input with a decimal point: 0.0 to1000.0 /min. ( /min.)
DC voltage, current input: 0 to 10000/min.
(The placement of the decimal point follows the selection.)
Direct/Reverse control action selection Reverse (Heating)
• Selects either Reverse (Heating) or Direct (Cooling) control action
action.
• : Reverse (Heating) control action
: Direct (Cooling) control action
AT bias setting 20
• Sets bias value during PID auto-tuning. (Refer to Chapter “10. Auto-tuning” on p.27.)
Not available for DC input
• Setting range: 0 to 50 (0 to 100 )
(Thermocouple, RTD input with a decimal point: 0.0 to 50.0 (0.0 to100.0 )
SVTC bias setting 0
• SV adds SVTC bias value to the value received by the SVTC command.
Available only when the C5 option is added
• Setting range: Converted value of 20% of the input span
DC voltage, current input: 20% of the scaling span (The placement of the decimal
point follows the selection.)
Contact input function selection Set value memory external selection
• Contact input terminals DI2 can be used for a “Set value memory external selection” or for
an “OUT/OFF external selection”. See “Contact input function selection” on p.18.
If Auto/Manual control function is selected during OUT/OFF key function selection,
externally Auto/Manual control can be switched.
Available only when the SM option is added.
• : Set value memory external selection
: OUT/OFF external selection 1 (SV and SV2 can be switched)
: OUT/OFF external selection 2
Output status selection when input abnormal Output OFF
• Selects whether OUT1 (OUT2) is turned OFF or not when DC input is overscale or underscale.
Available only for DC current output type with DC input
• : Outputs OFF(4mA) or OUT1(OUT2) low limit
: Outputs a value between OFF(4mA) and ON(20mA) or between OUT1(OUT2)
low limit value and OUT1(OUT2) high limit value, depending on a deviation.
OUT/OFF key function selection OUT/OFF function
• Selects whether OUT/OFF key is used for control output “OUT/OFF function”
or for “Auto/Manual control function”.
• : OUT/OFF function
: Auto/Manual control function
16
Backlight selection All are backlit
• Selects the display to backlight.
• : All (displays and indicators) are backlit.
: Only PV display is backlit.
: Only SV display is backlit.
: Only Action indicators are backlit.
: PV and SV displays are backlit.
: PV display and Action indicators are backlit.
: SV display and Action indicator are backlit.
PV color selection Red
• Selects PV display color. See “PV display color selection” on p.19.
• : Green
: Red
: Orange
: When Alarm 1 or Alarm 2 is ON, PV color turns from green to red.
: When Alarm 1 or Alarm 2 is ON, PV color turns from orange to red.
: PV color changes continuously (Orange Green Red).
: PV color changes continuously (Orange Green Red), and
at the same time Alarm 1 or Alarm 2 is ON (Red).
PV color range setting 5.0
• When (PV color changes continuously) or (PV color changes
continuously + Alarm 1 or Alarm 2 is ON) is selected during PV color selection, the value
of green PV color range can be set. See “PV display color selection” on p.19.
• Setting range: 0.1 to 100.0 ( ), DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection.)
Backlight time setting 0 minutes
• Sets time to backlight from no operation status until backlight is switched off.
When set to 0, the backlight remains ON. Backlight relights by pressing any key while
backlight is OFF.
• Setting range: 0 to 99 minutes
Indication selection when output OFF OFF indication
• Selects the indication when control output is OFF.
• : OFF indication
: No indication
: PV indication
• : PV indication+ Alarm output (Alarm 1, Alarm 2, Heater burnout alarm) active
OUT1 rate of change limit 0%/second
• Sets changing value of OUT1 MV for 1 second.
• Not available if OUT1 is ON/OFF action, or when set to 0.
See “OUT1 rate of change limit” on p.19.
• Setting range: 0 to 100%/second
17
[Alarm action Energized/Deenergized]
When [Alarm Energized ( )] is selected, the alarm output (between terminals 3-4, or 5-6) is
conductive (ON) while the alarm output indicator is lit.
The alarm output is not conductive (OFF) while the alarm output indicator is not lit.
When [Alarm Deenergized ( )] is selected, the alarm output (between terminals 3-4, or 5-6) is
not conductive (OFF) while the alarm output indicator is lit.
The alarm output is conductive (ON) while the alarm output indicator is not lit.
High limit alarm (when Energized is set) High limit alarm (when Deenergized is set)
A1 hysteresis A1 hysteresis
ON ON
OFF OFF
SV setting + A1 set point SV setting + A1 set point
A1: Alarm 1
(Fig. 6.1-2) (Fig. 6.1-3) For Alarm 2(A2), read “A2” for “A1”.
• When OUT/OFF function ( ) is selected during OUT/OFF key function selection mode
(Table 6.3-1)
Connecting terminal No. Contact input function
Set value memory OUT/OFF external OUT/OFF external
Between 17-18 Between 16-18 selection 2
external selection selection 1
(DI1-COM) (DI2-COM)
( ) ( ) ( )
Open Open SV SV
SV
Closed Open SV2 SV2
Open Closed SV3
Control output OFF Control output OFF
Closed Closed SV4
• When Auto/Manual control ( ) is selected during OUT/OFF key function selection mode.
(Table 6.3-2)
Connecting terminal No. Contact input function
Set value memory OUT/OFF external OUT/OFF external
Between 17-18 Between 16-18 selection 2
external selection selection 1
(DI1-COM) (DI2-COM)
( ) ( ) ( )
Open Open SV SV (Automatic control)
SV (Automatic control)
Closed Open SV2 SV2 (Automatic control)
Open Closed SV3
Manual control Manual control
Closed Closed SV4
18
[PV display color selection]
(Table 6.3-3)
PV color selection PV color
Green Constantly green
Red Constantly red
Orange Constantly orange
When Alarm 1 or Alarm 2 is ON: When alarm OFF: Green
Green Red When Alarm 1 or Alarm 2 is ON, the PV color turns from
green to red.
When Alarm 1 or Alarm 2 is ON: When alarm OFF: Orange
Orange Red When Alarm 1 or Alarm 2 is ON, the PV color turns from
orange to red.
PV color changes continuously PV color changes depending on the color range setting.
• PV is lower than [SV-PV color range]: Orange
(Orange Green Red)
• PV is within [SV PV color range]: Green
• PV is higher than [SV+PV color range]: Red
Orange Green Red
(Fig. 6.3-4)
Hys SV Hys
Red Red
OFF
1sec 5sec 10sec
(Fig.6.3-6) (Fig.6.3-7)
19
7. Settings
7.1 Main setting mode
To enter the Main setting mode, press the key in the PV/SV display mode.
20
7.2 Sub setting mode
To enter the Sub setting mode, press the key while pressing the key in the PV/SV display mode.
21
Alarm 1 value setting 0
• Sets action point for Alarm 1 output.
Setting the value to 0 or 0.0 disables the function (except Process high and Process low
alarm).
Not available if No alarm action is selected during Alarm 1 type selection
• Refer to (Table 7.2-1).
Alarm 2 value setting 0
• Sets action point for Alarm 2 output.
Setting the value to 0 or 0.0 disables the function (except Process high and Process low
alarm).
Not available if Alarm 2 (A2) option is not added or if No alarm action is selected during
Alarm 2 type selection.
• Refer to (Table 7.2-1).
Heater burnout alarm value setting 0.0A
• Sets the heater current value for Heater burnout alarm.
Setting to 0.0 disables the alarm.
. , CT1 current value and character are indicated alternately on the PV display.
XX.X When OUT1 is ON, the CT1 current value is updated.
alternating When OUT1 is OFF, the ACS-13A memorizes the previous value when OUT1 was ON.
display Upon returning to set limits, the alarm will stop.
Available only when the W or W3 option is added.
• Rated current: 20A (0.0 to 20.0A), 50A (0.0 to 50.0A)
Heater burnout alarm 2 value setting 0.0A
• Sets the heater current value for Heater burnout alarm.
. , Setting to 0.0 disables the alarm.
XX.X CT2 current value and characters are indicated alternately on the PV display.
alternating When OUT1 is ON, the CT2 current value is updated.
display When OUT1 is OFF, the ACS-13A memorizes the previous value when OUT1 was ON.
Upon returning to set limits, the alarm will stop.
Available only when the W3 option is added.
• Rated current: 20A (0.0 to 20.0A), 50A (0.0 to 50.0A)
(Table 7.2-1)
Alarm type Setting range
High limit alarm -(Input span) to input span ( ) *1
Low limit alarm -(Input span) to input span ( ) *1
High/Low limits alarm 0 to input span ( ) *1
High/Low limit range alarm 0 to input span ( ) *1
Process high alarm Input range low limit value to input range high limit value *2
Process low alarm Input range low limit value to input range high limit value *2
High limit alarm with standby -(Input span) to input span ( ) *1
Low limit alarm with standby -(Input span) to input span ( ) *1
High/Low limits alarm with standby 0 to input span ( ) *1
*1: For DC voltage, current input, the input span is the same as the scaling span.
*2: For DC voltage, current input, input range low (or high) limit value is the same as scaling low (or high)
limit value.
22
7.3 Auxiliary function setting mode
To enter the Auxiliary function setting mode, press the key for 3 seconds while holding down the
key in the PV/SV display mode.
Character Name, Function, Setting range Default value
Set value lock selection Unlock
• Locks the set values to prevent setting errors.
The setting item to be locked depends on the selection.
• When Lock 1 or Lock 2 is selected, PID Auto-tuning and Auto-reset cannot be carried out.
• (Unlock): All set values can be changed.
(Lock 1): None of the set values can be changed.
(Lock 2): Only main setting mode can be changed.
(Lock 3): All set values except Input type can be changed. However, changed
values revert to their previous value after power is turned off because they are not
saved in the non-volatile memory. Do not change any setting item in Setup
mode. If any item in Setup mode is changed, it will affect other setting items
such as the SV and Alarm value.
Sensor correction setting 0.0
• Sets the correction value for the sensor.
This corrects the input value from the sensor. When a sensor cannot be set at the exact
location where control is desired, the sensor measured temperature may deviate from the
temperature in the controlled location. When controlling with plural controllers, sometimes
the measured temperatures (input value) do not concur due to differences in sensor
accuracy or dispersion of load capacities. In such a case, the control can be set at the
desired temperature by adjusting the input value of sensors.
PV= Current PV+ Sensor correction value
• Setting range: -100.0 to 100.0 ( ) DC voltage, current input: -1000 to 1000 (The
placement of the decimal point follows the selection.)
Communication protocol selection Shinko protocol
• Selects communication protocol.
• Not available if the C5 option is not added or if SM option is added
• : Shinko protocol
: Modbus ASCII mode
: Modbus RTU mode
Instrument number setting 0
• Sets the instrument number individually to each instrument when communicating
by connecting plural instruments in serial communication.
• Not available if C5 option is not added or if SM option is added
• Setting range: 0 to 95
Communication speed selection 9600bps
• Selects a communication speed equal to that of the host computer.
• Not available if C5 option is not added or if the SM option is added
• : 2400bps
: 4800bps
: 9600bps
: 19200bps
Data bit/Parity selection 7 bits/Even parity
• Selects data bit and parity.
• Not available if the C5 option is not added or if SM option is added
• : 8 bits/No parity
: 7 bits/No parity
: 8 bits/Even parity
: 7 bits/Even parity
: 8 bits/Odd parity
: 7 bits/Odd parity
Stop bit selection 1
• Selects the stop bit.
• Not available if C5 option is not added or if SM option is added
• :1
:2
23
8. Running
8.1 Starting operation
After the unit is mounted to the control panel and wiring is completed, operate the unit following the
procedures below.
(1) Turn the power supply to the ACS-13A ON.
After the power is turned on, the PV display indicates the input type, and the SV display indicates the
input range high limit value (for thermocouple, RTD input) or scaling high limit value (for DC voltage,
current input) for approximately 3 seconds. See (Table 8.1-1).
During this time, all outputs and the indicators are in OFF status.
Control will then start indicating the PV (process variable) on the PV display and SV (main set value) on
the SV display.
While control output OFF function is working, PV display indicates . (Indication of the PV display
depends on the selection during “Indication selection when output OFF” mode.)
(Table 8.1-1)
Sensor input
PV display SV display PV display SV display
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
Scaling high limit value
0 to 5V DC
1 to 5V DC
0 to 10V DC
(2) Input each set value. Input each set value. Refer to “7. Settings”.
(3) Turn the load circuit power ON.
Control action starts so as to keep the control target at the SV.
2 Set SV.
Set SV with the or key.
,
4 Control starts.
Control starts so as to keep the measuring temperature at 100 .
24
8.2 Control output OFF function (Control output OUT/OFF function)
This is a function to pause the control action or turn the control output of the unused instrument of the
plural units OFF even if the power to the instrument is supplied.
To turn the control output OFF, press the key for approximately 1 second in the PV/SV display mode.
[ ] is indicated on the PV display while the function is working.
(However, indication of the PV display depends on the selection during “Indication selection when output OFF”.)
Once the control output OFF function is enabled, the function cannot be released even if the power to the
instrument is turned OFF and ON again.
To cancel the function, press the key again for approx. 1 second.
25
8.4 Indicating output MV (manipulated variable)
To indicate output MV (manipulated variable), press the key for approximately 3 seconds in the
PV/SV display mode. The MEMO display indicates [ ].
By pressing the key again, the unit reverts to the PV/SV display mode.
PV/SV display mode (Automatic control) Output MV indication
key (approx.3sec)
key
8.5 Auto-tuning/Auto-reset Perform, Auto-tuning Cancel
In order to set each value of P, I, D and ARW automatically, the auto-tuning process should be made to
fluctuate to obtain an optimal value.
Auto-tuning/Auto-reset can be performed or cancelled in “Auto-tuning/Auto-reset selection” in the Sub
setting mode.
Auto-reset can be performed when P or PD is control action. Auto-reset ends 4 minutes after starting. It
cannot be released while performing this function.
How to perform Auto-tuning/Auto-reset
(1) To enter the Sub setting mode, press the key while pressing the key in the PV/SV display.
Auto-tuning/Auto-reset selection item appears.
(2) Select Auto-tuning/Auto-reset “Perform [ / ]” with the key, and press the key.
Auto-tuning/Auto-reset will initiate. While performing Auto-tuning/Auto-reset, the AT indicator is flashing.
When auto-tuning is not finished after 4 hours, it is automatically cancelled.
Auto-reset is cancelled in approximately 4 minutes. It cannot be released while performing this function.
How to cancel Auto-tuning
(1) To enter the Sub setting mode, press the key while pressing the key in the PV/SV display.
Auto-tuning/Auto-reset selection item appears.
(2) Select Auto-tuning/Auto-reset “Cancel [ ]” with the key, and press the key. Auto-tuning will stop.
If Auto-tuning is cancelled during this process, each value of P, I, D and ARW reverts to the values
before the Auto-tuning was performed.
AT (Auto-tuning) Perform/Cancel (PID action):
(1) Proceed to the Sub setting mode.
Press the key while pressing the key in the PV/SV display mode.
+ The unit proceeds to the Sub setting mode.
(2) Select AT Perform/Cancel.
Select “ (Perform)” with the , or select “ (Cancel)” with the .
, : AT Cancel
: AT Perform
(3) Confirm AT Perform/Cancel.
Press the key.
The unit reverts to the PV/SV display mode.
(4) AT Perform/Cancel
While AT is performing, the AT indicator flashes, and it goes off if AT is cancelled.
9. Auto-reset
Auto-reset is performed to correct the offset at the point at which PV indication is stabilized within the
proportional band during the PD action. Since the corrected value is internally memorized, it is not
necessary to perform the auto-reset again as long as the process is the same. However, when OUT1
proportional band is set to 0 or 0.0, the corrected value is cleared.
Auto-reset is performed.
SV
Offset span
Temperature
Offset is corrected.
Time (Fig. 9-1)
26
10. Auto-tuning
In order to set each value of P, I, D and ARW automatically, the auto-tuning process should be made
to fluctuate to obtain an optimal value. One of 3 types of fluctuation below is automatically selected.
For DC input, the AT process will fluctuate around the set value for conditions of [1], [2] and [3] below.
Notice
• Perform the auto-tuning during the trial run.
• During the auto-tuning, none of the setting items can be set.
• If power failure occurs during the auto-tuning, the tuning stops.
[1] In the case of a large difference between the SV and processing temperature as the
temperature is rising
When AT bias is set to 20 , the AT process will fluctuate at the temperature 20 lower than the SV.
Time
AT starting point
[2] When the control is stable or when control temperature is within 20 of the SV
The AT process will fluctuate around the SV.
SV
(1) Calculating PID constant
(2) PID constant calculated
Temperature
(3) Controlled by the PID constant
set by auto-tuning.
Time
AT starting point
(Fig. 10-2)
[3] In the case of a large difference between the SV and processing temperature as the
temperature is falling
When AT bias is set to 20 , the AT process will fluctuate at the temperature 20 higher than the SV.
Temperature 20 higher than the SV
Time
AT starting point
(Fig. 10-3)
27
11. Action explanation
11.1 OUT1 action
SV setting SV setting
7 7 7 7 7 7
Relay contact
output 8 8 8 8 8 8
Cycle action is performed according to deviation Cycle action is performed according to deviation
+ 7 + 7 + 7 + 7 + 7 + 7
Non-contact 12V DC 12/0V DC 0V DC 0V DC 0/12V DC 12V DC
voltage output 8 8 8 8 8 8
Cycle action is performed according to deviation Cycle action is performed according to deviation
+ 7 + 7 + 7 + 7 + 7 + 7
DC current 20mA DC 20 to 4mA DC 4mA DC 4mA DC 4 to 20mA DC 20mA DC
output 8 8 8 8 8 8
Indicator
(O1) Green
Lit Unlit Unlit Lit
Hysteresis Hysteresis
ON ON
Control
action
OFF OFF
SV setting SV setting
7 7 7 7
Relay contact
output
8 8 8 8
+ 7 + 7 + 7 + 7
Non-contact
12V DC 0V DC 0V DC 12V DC
voltage output
8 8 8 8
+ 7 + 7 + 7 + 7
DC current
20mA DC 4mA DC 4mA DC 20mA DC
output
8 8 8 8
Indicator
(O1) Green
Lit Unlit Unlit Lit
28
11.3 Heater burnout alarm action
ON
Output
5 5
OFF
Alarm action
Setting
6 6
Small Large Indicator
Load current
Lit Unlit
If Heater burnout alarm and Alarm 2 (A2) option are applied together, they utilize common output (EV2)
terminals.
ON ON ON
Alarm
action
ON ON ON
Alarm
action
OFF OFF OFF
A1 set point SV A1 set point A1 set point A1 set point
setting
High limit alarm with standby Low limit alarm with standby High/Low limit alarm with standby
A1 hysteresis A1 hysteresis A1 hysteresis
ON ON ON
Alarm
action
OFF OFF OFF
A1 set point SV + A1 set point A1 set point SV + A1 set point A1 set point SV A1 set point
setting setting setting
: Standby functions.
29
11.5 OUT2 (Heating/Cooling control) action
Heating P-band (Cooling P-band)
ON ON
Control Heating (Cooling
action action action)
OFF OFF
SV setting
7 7 7
Relay contact
output (OUT1)
8 8 8
Cycle action is performed according to deviation.
+ 7 + 7 + 7
Non-contact 12V DC 12/0V DC 0V DC
voltage output
(OUT1) - 8 - 8 - 8
Cycle action is performed according to deviation.
+ 7 + 7 + 7
DC current 20mA DC 20 to 4mA DC 4mA DC
output (OUT1)
- 8 - 8 - 8
Changes continuously according to deviation.
5 5 5
Relay contact
output (OUT2)
6 6 6
Cycle action is performed according to deviation.
Non-contact
+ 5 + 5 + 5
voltage output 0V DC 12/0V DC 12V DC
(OUT2) - 6 - 6 - 6
Cycle action is performed according to deviation.
Indicator
(O1)
: Alternates between ON (lit) and OFF (unlit).
Lit Unlit
: Represents Heating control action.
Indicator : Represents Cooling control action.
(O2)
Unlit Lit
OFF OFF
SV setting
7 7 7
Relay contact
output (OUT1) 8 8 8
Cycle action is performed according to deviation.
+ 7 + 7 + 7
Non-contact
12V DC 12/0V DC 0V DC
voltage output
(OUT1) - 8 - 8 - 8
Cycle action is performed according to deviation.
+ 7 + 7 + 7
DC current 20mA DC 20 to 4mA DC 4mA DC
output (OUT1)
- 8 - 8 - 8
Changes continuously according to deviation.
5 5 5
Non-contact
relay output
(OUT2) 6 6 6
Cycle action is performed according to deviation.
Non-contact
+ 5 + 5 + 5
voltage output 0V DC 12/0V DC 12V DC : Alternates between
(OUT2) - 6 - 6 - 6 ON (lit) and OFF (unlit).
Cycle action is performed according to deviation. : Represents
Heating control
Indicator (O1) action.
Lit Unlit : Represents
Cooling control
Indicator (O2) action.
Unlit Lit
30
11.7 OUT2 (Heating/Cooling control) action (When setting Overlap band)
Heating P-band
Cooling P-band
Overlap
ON band ON
Control action
Heating (Cooling
action action)
OFF OFF
SV setting
7 7 7
Relay contact
output (OUT1) 8 8 8
Cycle action is performed according to deviation.
7 7 7
Non-contact
12V DC 12/0V DC 0V DC
voltage output
8 8 8
(OUT1)
Cycle action is performed according to deviation.
DC current
7 7 7
output (OUT1) 20mA DC 20 to 4mA DC 4mA DC
8 8 8
Changes continuously according to deviation.
5 5 5
Relay contact
output (OUT2)
6 6 6
Cycle action is performed according to deviation.
Non-contact 5 5 5
voltage output 0V DC 12/0V DC 12V DC
(OUT2) 6 6 6
Cycle action is performed according to deviation.
: Alternates between ON(lit) or OFF(unlit).
Indicator (O1) : Represents Heating control action.
Lit Unlit : Represents Cooling control action.
Indicator (O2)
Unlit Lit
31
12. Specifications
12.1 Standard specifications
Mounting method : Flush
Setting method : Input system using membrane sheet key
Display PV display : 11-segment backlight LCD Red/Green/Orange, character size 12.0 x 5.4 mm (H x W)
SV display : 11-segment backlight LCD Green, character size 6.0 x 3.5 mm (H x W)
MEMO display : 11-segment backlight LCD Green, character size 4.8 x 2.8 mm (H x W)
Indicators : Backlight Orange
Accuracy (Setting and Indication):
Thermocouple : Within 0.2% of each input span 1digit, or within 2 (4 ),
whichever is greater
However R, S input, 0 to 200 (0 to 400 ): Within 6 (12 )
B input, 0 to 300 (0 to 600 ): Accuracy is not guaranteed
K, J, E, T, N input, less than 0 (32 ): Within 0.4% of input span 1digit
RTD : Within 0.1% of each input span 1digit, or within 1 (2 ),
whichever is greater
DC current : Within 0.2% of each input span 1digit
DC voltage : Within 0.2% of each input span 1digit
Input sampling period : 0.25 seconds
Input Thermocouple : K, J, R, S, B, E, T, N, PL- , C(W/Re5-26)
External resistance, 100 or less
(However, B input: External resistance, 40 or less)
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10 or less per wire)
DC current : 0 to 20mA DC, 4 to 20mA DC
Input impedance: 50 [50 shunt resistor (sold separately) must be
connected between input terminals.]
Allowable input current, 50mA or less [When 50 shunt resistor (sold
separately) is used]
DC voltage : 0 to 1V DC Input impedance (1M or more)
Allowable input voltage (5V DC or less)
Allowable signal source resistance (2k or less)
: 0 to 5V DC, 1 to 5V DC, 0 to 10V DC Input impedance (100k or more)
Allowable input voltage (15V DC or less)
Allowable signal source resistance (100 or less)
Control output or Heating output (OUT1)
Relay contact : 1a, Control capacity 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 100,000 times
Non-contact voltage (For SSR drive): 12V DC 15%, Maximum 40mA (short circuit protected)
DC current : 4 to 20mA DC, Load resistance, Maximum 550
Alarm 1 output
Action : ON/OFF action
Hysteresis : 0.1 to 100.0 ( ) (Default: 1.0 )
DC voltage, current input: 1 to 1000 (The placement of the decimal point
follows the selection.)
Output : Relay contact 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 times
32
Control action
PID action (with auto-tuning function)
PI action: When derivative time is set to 0
PD action (with auto-reset function): When integral time is set to 0
P action (with auto-reset function): When derivative and integral time are set to 0.
ON/OFF action: When proportional band is set to 0 or 0.0
OUT1 proportional band : 0 to 1000 (2000 ), 0.0 to 1000.0 (1999.9 ) or 0.0 to 100.0%
(ON/OFF action when set to 0 or 0.0) (Default: 10 )
Integral time : 0 to 1000sec. (OFF when set to 0) (Default: 200sec.)
Derivative time : 0 to 300sec. (OFF when set to 0) (Default: 50sec.)
OUT1 proportional cycle : 1 to 120sec. (Default: 30sec for Relay contact, 3sec for Non-contact voltage,
Not available for DC current)
ARW : 0 to 100% (Default: 50%)
OUT1 ON/OFF action hysteresis: 0.1 to 100.0 ( ) (Default: 1.0 )
DC voltage, current input: 1 to 1000 (The placement of the decimal point
follows the selection.)
OUT1 high limit setting : 0 to 100% (DC current: -5 to 105%) (Default: 100%)
OUT1 low limit setting : 0 to 100% (DC current: -5 to 105%) (Default: 0%)
Circuit insulation configuration
Insulated
1 13 OUT1 7
POWER
SUPPLY CT1 (Output)
2 14 CT2 8
3 15 9
CPU
EV1
TC 10
4 16 RTD
RS-485 DC
5 17 DI (Input) 11
EV2
OUT2
6 18 12
Console
When OUT1 is a non-contact voltage or DC current and OUT2 is a non-contact voltage, OUT1 is not
insulated from OUT2.
When OUT1 is a non-contact voltage or DC current, OUT1 is not insulated from RS-485, DI.
When OUT2 is a non-contact voltage, OUT2 is not insulated from RS-485, DI.
Insulation resistance: 10M or more, at 500V DC
Dielectric strength : 1.5kV AC for 1 minute between input terminal and power terminal
1.5kV AC for 1 minute between output terminal and power terminal
Supply voltage : 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation: 100 to 240V AC : 85 to 264V AC,
24V AC/DC : 20 to 28V AC/DC
Power consumption : Approx. 8VA
Ambient temperature : 0 to 50 (32 to 122 )
Ambient humidity : 35 to 85%RH (no condensation)
Weight : Approx. 120g
External dimensions : 48 x 48 x 62mm (W x H x D)
(Depth of control panel interior when gasket is used: 54.5mm)
(Depth of control panel interior when gasket is not used: 56.0mm)
Material : Flame-resistant resin (Case)
Color : Black (Case)
Dust-proof/Drip-proof : IP66
33
Attached functions:
[Power failure countermeasure]:
The setting data is backed up in the non-volatile IC memory.
[Self-diagnosis]:
The CPU is monitored by a watchdog timer, and if the CPU’s status becomes abnormal, the controller is
switched to warm-up status with all outputs OFF.
[Automatic cold junction temperature compensation] (Only thermocouple input type)
This detects the temperature at the connecting terminal between the thermocouple and the instrument,
and always maintains the same status as when the reference junction is located at 0 (32 ).
[Warm-up indication]
After the power supply to the instrument is turned on, the PV display indicates the sensor input type,
and SV display indicates input range high limit value (for thermocouple, RTD) or Scaling high limit
value (for DC input) for approximately 3 seconds.
[Indication range and Control range]
Thermocouple input: [Input range low limit value – 50 (100 )] to [Input range high limit value + 50 (100 )]
RTD input: [Input range low limit value -Input span x 1%] to [Input range high limit value + 50 (100 )]
DC current, voltage input:
[Scaling low limit value -Scaling span x 1%] to [Scaling high limit value +Scaling span x 10%]
[Burnout]
When the thermocouple or RTD input is burnt out, OUT1 and OUT2 are turned OFF (for DC current
output type, OUT1 low limit value) and the PV display flashes “ ”.
However, for the manual control, the preset MV (manipulated variable) is outputted.
When the DC current or DC voltage is disconnected, PV display flashes “ ” for 4 to 20mA DC
and 1 to 5V DC inputs, and “ ” for 0 to 1V DC input. For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC
inputs, the PV display indicates the value corresponding with 0mA or 0V input.
[Input abnormality indication]
Output status Output status
selection when Contents and OUT1 OUT2
input abnormal Indication Direct(Cooling) Reverse(Heating) Direct(Cooling) Reverse(Heating)
action action action action
Overscale ON (20mA) or ON or
Measured value OUT1 high OUT2 high
OFF (4mA) or OFF or
has exceeded limit value (*) limit value (*)
OUT1 low limit OUT2 low
Indication range OFF (4mA) or value OFF or
limit value
high limit value. OUT1 low OUT2 low
" " flashes. limit value limit value
Underscale ON (20mA) or ON or
Measured value OUT1 high limit OUT2 high
has dropped below OFF (4mA) or value (*) limit value (*) OFF or
Indication range low OUT1 low OUT2 low
OFF (4mA) or OFF or
limit value. limit value limit value
OUT1 low limit OUT2 low
" " flashes. value limit value
Only for DC input and DC current output type, [Output status selection when input abnormal] is usable.
For manual control, the preset MV (manipulated variable) is outputted.
(*) Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (or OUT2) low limit value
and OUT1 (or OUT2) high limit value, depending on deviation.
[Auto/Manual control switching]
Select “Auto/Manual control” during OUT/OFF key function selection in the Setup mode, then press
the key in the PV/SV display mode. Auto/manual control can be switched.
[Console communication]
By connecting the USB communication cable (Model CMA) to the Console connector of the ACS-13A,
the following operations can be conducted from the external computer using the Console software
SWS-ACS01M.
(1) Reading and setting of SV, PID and various set values, (2) Reading of PV and action status,
(3) Function change
Console communication and Serial communication (C5 option) cannot be used together.
Communication interface: C-MOS level
34
Accessories included:
Mounting frame 1 piece, Gasket (Front mounted to the ACS-13A) 1 piece
Instruction manual (A3 unfolded, English/Japanese) 1 copy
CT (Current transformer):
CTL-6S: 1 piece [W (20A) option] CTL-12-S36-10L1: 1 piece [W (50A) option]
CTL-6S: 2 pieces [W3 (20A) option] CTL-12-S36-10L1: 2 pieces [W3 (50A) option]
Accessories sold separately: Terminal cover,
50 Shunt resistor (for DC current input)
USB communication cable (CMA)
12.2 Optional specifications
Alarm 2 output (Option code: A2)
If this option is added, Heating/Cooling control (D option) cannot be added.
Alarm 2 and Heater burnout alarm (W, W3 option) utilize common output terminals.
Action : ON/OFF action
Hysteresis: 0.1 to 100.0 ( ) (Default: 1.0 )
DC voltage, current input: 1 to 1000 (The placement of the decimal point follows the selection.)
Output : Relay contact, 1a Control capacity, 3A 250V AC (Resistive load) Electric life, 100,000 times
Heater burnout alarm (including sensor burnout alarm) [Option code: W(20A), W(50A), W3(20A), W3(50A)]
Monitors heater current with CT (current transformer), and detects burnout.
This alarm is also activated when indication is overscale and underscale.
This option cannot be applied to DC current output type.
If this alarm is added, Heating/Cooling control (D option) cannot be added.
Heater burnout alarm and Alarm 2 (A2) option utilize common output terminals.
Rating : Single phase 20A [W(20A)], Single phase 50A [W(50A)],
3-phase 20A [W3(20A)], 3-phase 50A [W3(50A)] (Must be specified)
Detects burnout with CT1 input for single phase, with CT1 and CT2 input for 3-phase.
Setting range : 20A [W(20A)], [W3(20A)]: 0.0 to 20.0A (Off when set to 0.0)
50A [W(50A)], [W3(50A)]: 0.0 to 50.0A (Off when set to 0.0)
Setting accuracy : Within 5% of the rated value
Action : ON/OFF action
Output : Relay contact, 1a Control capacity, 3A 250V AC (resistive load), Electric life, 100,000 times
35
Serial communication (Option code: C5)
If this option is added, Set value memory external selection (SM option) cannot be added.
This option and Console communication cannot be used together.
The following operations can be carried out from the external computer.
(1) Reading and setting of the SV, PID values and various set values
(2) Reading of the PV and action status
(3) Function change
Cable length : Max. communication distance 1.2km
Cable resistance: Within 50
(Terminator is not necessary or 120 or more on one side.)
Communication interface : EIA RS-485
Communication method : Half-duplex communication start-stop synchronous
Communication speed : 2400/4800/9600/19200bps (Selectable by keypad) (Default: 9600bps)
Data bit/Parity : 7 bits, 8bits/Even, Odd and No parity (Selectable by keypad)
(Default: 7 bits/Even parity)
Stop bit : 1, 2 (Selectable by keypad) (Default: 1)
Communication protocol : Shinko protocol/Modbus RTU/Modbus ASCII (Selectable by keypad)
(Default: Shinko protocol)
Data format
Communication protocol Shinko protocol Modbus ASCII Modbus RTU
Start bit 1 1 1
Data bit 7 7 or 8 8
Parity Yes (Even) Yes (Even, Odd) No parity Yes (Even, Odd) No parity
Stop bit 1 1 or 2 1 or 2
Number of connectable units : Maximum 31 units to 1 host computer
Communication error detection: Parity, checksum (Shinko protocol), LRC (Modbus ASCII),
CRC-16 (Modbus RTU)
Digital external setting : Receives digital set values from Shinko programmable controllers
(PC-900, PCD-33A with SVTC option)
36
13. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply to the controller.
13.1 Indication
Problem Presumed cause and solution
[ ], nothing or PV is indicated • Control output OFF function is working.
on the PV display. Press the key for approx. 1 second to release the function.
[ ] is flashing on the PV • Burnout of thermocouple, RTD or disconnection of DC voltage (0 to 1V DC)
display. Change each sensor.
How to check whether the sensor is burnt out
[Thermocouple]
If the input terminals of the instrument are shorted, and if a value
around room temperature is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[RTD]
If approx. 100 of resistance is connected to the input terminals
between A-B of the instrument and between B-B is shorted, and
if a value around 0 (32 ) is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[DC voltage (0 to 1V DC)]
If the input terminals of the instrument are shorted, and if a
scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
• Check whether the input terminals of thermocouple, RTD or DC voltage
(0 to 1V DC) are securely mounted to the instrument input terminal.
Connect the sensor terminals to the instrument input terminals securely.
[ ] is flashing on the PV • Check whether input signal wire for DC voltage (1 to 5V DC) or
DC current (4 to 20mA DC) is disconnected.
display.
How to check whether the input signal wire is disconnected
[DC voltage (1 to 5V DC)]
If the input to the input terminals of the instrument is 1V DC and if
a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
[DC current (4 to 20mA DC)]
If the input to the input terminals of the instrument is 4mA DC and
if a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
• Check whether input signal wire for DC voltage (1 to 5V DC) or DC current
(4 to 20mA DC) is securely connected to the instrument input terminals.
• Check if polarity of thermocouple or compensating lead wire is correct.
• Check whether codes (A, B, B) of RTD agree with the instrument terminals.
The PV display keeps indicating • Check whether the input signal wire for DC voltage (0 to 5V DC,
the value which was set during 0 to 10V DC) and DC current (0 to 20mA DC) is disconnected.
Scaling low limit setting. How to check whether the input signal wire is disconnected
[DC voltage (0 to 5V DC, 0 to 10V DC)]
If the input to the input terminals of the instrument is 1V DC and if
the value corresponding to 1V DC is indicated, the instrument is
likely to be operating normally, however, the signal wire may be
disconnected.
[DC current (0 to 20mA DC)]
If the input to the input terminals of the instrument is 1mA DC and
if the value corresponding to 1mA DC is indicated, the instrument
is likely to be operating normally, however, the signal wire may be
disconnected.
• Check whether the input lead wire terminals for DC voltage (0 to 5V
DC, 0 to 10V DC) or DC current (0 to 20mA DC) are securely
mounted to the instrument input terminals.
37
The indication of PV display is • Check whether sensor input or temperature unit ( or ) is correct.
abnormal or unstable. Select the sensor input and temperature unit ( or ) properly.
• Sensor correcting value is unsuitable. Set it to a suitable value.
• Check whether the specification of the sensor is correct.
• AC leaks into the sensor circuit. Use an ungrounded type sensor.
• There may be equipment that interferes with or makes noise near
the controller.
Keep equipment that interferes with or makes noise away from the
controller.
[ ] is indicated on the PV • Internal memory is defective.
display. Contact our agency or us.
13.3 Control
Problem Presumed cause and solution
Temperature does not rise. • Sensor is out of order. Replace the sensor.
• Check whether the Sensor or control output terminals are securely
mounted to the instrument input terminals.
Ensure that the sensor or control output terminals are mounted to
the instrument input terminals securely.
• Check whether the wiring of sensor or control output terminals is correct.
The control output remains in an • OUT1 or OUT2 low limit value is set to 100% or higher in Setup mode.
ON status. Set it to a suitable value.
The control output remains in an • OUT1 or OUT2 high limit value is set to 0% or less in Setup mode.
OFF status. Set it to a suitable value.
For all other malfunctions, please contact our main office or dealers.
38
14. character table
The PV display indicates setting (selection) characters, and the SV display indicates default value.
SV2
Scaling low limit to Scaling high limit
SV3
Scaling low limit to Scaling high limit
SV4
Scaling low limit to Scaling high limit
Integral time
0 to 1000sec
Derivative time
0 to 300sec
ARW
0 to 100%
39
Alarm 1 value
Alarm type Setting range
High limit alarm -(Input span) to Input span ( ) *1
Low limit alarm -(Input span) to Input span ( ) *1
High/Low limits alarm 0 to Input span ( ) *1
H/L limit range alarm 0 to Input span ( ) *1
Process high alarm Input range low limit to Input range high limit *2
Process low alarm Input range low limit to Input range high limit *2
High limit with standby -(Input span) to Input span ( ) *1
Low limit with standby -(Input span) to Input span ( ) *1
H/L limits with standby 0 to Input span ( ) *1
1: For DC voltage, current input, the input span is the same as the scaling span.
*2: For DC voltage, current input, input range low (or high) limit value is
the same as scaling low (or high) limit value.
Alarm 2 value
The setting range is the same as that of Alarm 1 value.
Communication speed
: 2400bps : 4800bps
: 9600bps : 19200bps
Data bit/Parity
: 8 bits/No parity
: 7 bits/No parity
: 8 bits/Even parity
: 7 bits/Even parity
: 8 bits/Odd parity
: 7 bits/Odd parity
Stop bit
:1
:2
40
[Setup mode]
Character Setting (Selection) item Data
Input type
: K -200 to 1370 : K -200 to 1370
: K -200.0 to 400.0 : K -200.0 to 400.0
: J -200 to 1000 : J -200 to 1000
: R 0 to 1760 : R 0 to 1760
: S 0 to 1760 : S 0 to 1760
: B 0 to 1820 : B 0 to 1820
: E -200 to 800 : E -200 to 800
: T -200.0 to 400.0 : T -200.0 to 400.0
: N -200 to 1300 : N -200 to 1300
: PL- 0 to 1390 : PL- 0 to 1390
: C(W/Re5-26) 0 to 2315 : C(W/Re5-26) 0 to 2315
: Pt100 -200.0 to 850.0 : Pt100 -200.0 to 850.0
: JPt100 -200.0 to 500.0 : JPt100 -200.0 to 500.0
: Pt100 -200 to 850 : Pt100 -200 to 850
: JPt100 -200 to 500 : JPt100 -200 to 500
: 4 to 20mA DC -2000 to 10000
: 0 to 20mA DC -2000 to 10000
: 0 to 1V DC -2000 to 10000
: 0 to 5V DC -2000 to 10000
: 1 to 5V DC -2000 to 10000
: 0 to 10V DC -2000 to 10000
Scaling high limit
Scaling low limit to Input range high limit
DC voltage, current input: -2000 to 10000
Scaling low limit
Input range low limit to Scaling high limit
DC voltage, current input: -2000 to 10000
Decimal point place
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
PV filter time constant
0.0 to 10.0sec
41
Character Setting (Selection) item Data
OUT2 high limit
OUT2 low limit to 100%
Alarm 1 Energized/Deenergized
: Energized
: Deenergized
Alarm 2 Energized/Deenergized
Selection items are the same as those of the Alarm 1
Energized/Deenergized selection
Alarm 1 hysteresis
0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000
Alarm 2 hysteresis
0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000
Alarm 1 action delayed timer
0 to 10000sec
SV rise rate
0 to 10000 /minute ( /minute)
Thermocouple, RTD input with decimal point: 0.0 to 1000.0 /minute( /minute)
DC voltage, current input: 0 to 10000/minute
SV fall rate
0 to 10000 /minute ( /minute)
Thermocouple, RTD input with decimal point: 0.0 to 1000.0 /minute( /minute)
DC voltage, current input: 0 to 10000/minute
42
Character Setting (Selection) item Data
Direct/Reverse control action
: Reverse (Heating) action
: Direct (Cooling) action
AT bias
0 to 50 (0 to 100 )
Thermocouple, RTD input with decimal point: 0.0 to 50.0 (0.0 to 100.0 )
SVTC bias
Converted value of 20% of the input span
DC voltage, current input: 20% of Scaling span
Contact input function
: Set value memory external selection
: OUT/OFF external selection 1 (SV, SV2 switchable)
: OUT/OFF external selection 2
Output status selection when input abnormal
: Outputs OFF (4mA) or OUT1 (OUT2) low limit value
: Outputs a value between OFF (4mA) and ON (20mA) or
between OUT1 (OUT2) low limit value and OUT1 (OUT2) high limit
value, depending on deviation.
OUT/OFF key function
: OUT/OFF function
: Auto/Manual control
Backlight
: All (displays and indicators) are backlit.
: Only PV display is backlit.
: Only SV display is backlit.
: Only Action indicators are backlit.
: PV and SV displays are backlit.
: PV display and Action indicators are backlit.
: SV display and Action indicator are backlit
PV color
: Green
: Red
: Orange
: When Alarm 1 or Alarm 2 is ON, PV color turns from green to red.
: When Alarm 1 or Alarm 2 is ON, PV color turns from orange to red.
: PV color changes continuously (Orange Green Red).
: PV color changes continuously (Orange Green Red).
at the same time Alarm 1 or Alarm 2 is ON (Red).
PV color range
0.1 to 100.0 ( )
For DC current, voltage input: 1 to 1000
Backlight time
0 to 99 minutes
43