Control Systems Guide
Control Systems Guide
Control Systems Guide
UNIVERSITY of FLORIDA
Sections written in the following format indicate a need for the consultant to edit, modify, or select for specific
project conditions [Pneumatic/Electric actuation shall be used at all reheat coils]
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. A complete microprocessor controlled BACnet compatible building automation and control
systems tested and ready for operation.
2. Automation and/or monitoring for the various systems such as but limited to:
a. Air Handlers
b. Variable Frequency Drives
c. Variable Air Terminals
d. Fan Coil Units
e. Pumps
f. Heat Exchangers
g. Air Conditioners
h. Heaters
i. Meters
Identify other appropriate major equipment contained in the construction documents and coordinate integration
requirements.
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 1 of 53
University of Florida 11/09/07
Control System Guide Specification
C. RELATED SECTIONS
1. Section 15005 - Motors
2. Section 15520 - Valves
3. Section 15550 - Vibration Isolation
4. Section 15910 - Control Sequences
5. Section 16130 - Raceway and Fittings
6. Section 16120 - Conductors and Cables
Identify other appropriate specification sections contained in the Project Manual (e.g. electrical raceways,
conductors, motor starters, VFD’s, etc.)
-------------------------------------------------------------------------------------------------------------------------------------------
1.2 REFERENCES
-------------------------------------------------------------------------------------------------------------------------------------------
1.3 DEFINITIONS
A. The following abbreviations, acronyms, and definitions apply to and are used within this Guide
Specification:
1. Actuator Control device to provide motion of valve or damper in response to control
signal.
2. AHU Air Handling Unit
3. AI Analog Input
4. AO Analog Output
5. Analog A continuously variable system or value not having discrete levels. Typically
exists within a defined range of limiting values
6. Auto-Tune Software routine used to adjust tuning parameters based on historical or
real-time data
7. ASC Application Specific Controller
8. BACnet The ASHRAE building automation and control protocol
9. BAS Building Automation System
10. BLC Building Level Controller – Supervisory control panel and the primary means
of communication outside the building. May also act as a global controller,
implementing building wide global strategies and energy management
routines.
11. Cx Commissioning Agent
Page 2 of 53
University of Florida 11/09/07
Control System Guide Specification
Page 3 of 53
University of Florida 11/09/07
Control System Guide Specification
Page 4 of 53
University of Florida 11/09/07
Control System Guide Specification
Consultant should edit list for each project. Coordinate list with University of Florida Project Manager. Some
renovation projects may require sole-source selection, meaning the renovation project control system is
intended to be an extension of an existing system. NOTE: IF THE PROJECT TEAM ELECTS TO PURSUE A
SOLE SOURCE SOLUTION FOR THE BAS, THE CONSULTANT MUST USE THE UF SOLE SOURCE
OPEN BOOK BID FORM AND PRICING AGREEMENT.
-------------------------------------------------------------------------------------------------------------------------------------------
B. Scope includes labor and materials including but not limited to:
1. Tools and other equipment
2. Software, licenses, configurations and database entries,
3. Interfaces, wiring, tubing, labeling,
4. Engineering and calculations
5. Calibration, testing, verifications, training and other services
6. Documentation, samples, submittals,
7. Permits, professional licenses, etc.
8. Other Administrative fees such as parking, shipping, handling, etc.
C. Provide a complete system and be accessible via manufacturer’s specific server system using a
web browser interface implemented over the Owner’s intranet as well as over the Internet.
-------------------------------------------------------------------------------------------------------------------------------------------
E. The BAS Network shall utilize an open architecture capable of all of the following:
1. Utilizing standard Ethernet communications and operating at a minimum speed of 10/100
Mb/sec.
2. Connecting via BACnet/IP at the Tier 1 level in accordance with ANSI/ASHRAE Standard 135-
2004. All points shall be made available for monitoring via BACnet/IP.
3. The BAS network shall support both copper and optical fiber communication media at the Tier
1 level.
Page 5 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
G. The system architecture allows complete access to the BAS system via a web browser. The thin-
client web browser or GUI will support the latest version of Microsoft and Netscape Navigator
browsers and Windows as well as non-Windows operating systems. No special software, (active-x
components or fat java clients) shall be required to be installed on the thin client PC’s / PDA’s used
to access the BAS via a web browser.
Verify the requirement to add a local operator station. Performance specifications for the operator workstation
is provided in PART 2.
-------------------------------------------------------------------------------------------------------------------------------------------
H. The BAS shall be fully expandable with addition of hardware and/or software. Expansion shall not
require removal of existing DDCP, sensors, actuators, or communication networks.
K. Provide all required system software to support a server/client architecture, designed around the
open standards of web services.
L. All electrical work required as an integral part of this section is work of this section.
M. Provide final power connections including conduit, wire, and/or control panel disconnect switches to
all control devices from appropriate electrical j-box.
Edit per project requirements and cross reference interrelated sections. Be sure to coordinate power
requirements with electrical engineer and to cross-reference responsibilities with other system designers (e.g.
HVAC, Electrical, Fire Protection, Plumbing, etc…). Coordinate power requirements for BAS system and show
on electrical drawings. The goal of the University is to insure 120 VAC power is provided within a common
area (e.g. mechanical room) adjacent to control devices. The control contractor would then be responsible for
all final power (120 VAC and >) and low voltage (24VAC and <) to all control components within the common
area. Located BAS panels on the mechanical room floor plan drawings.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 6 of 53
University of Florida 11/09/07
Control System Guide Specification
A. Provide components not specifically indicated or specified, but necessary to make system function
within the intent of contract documents.
B. All electrical products to be listed and labeled by UL and comply with NEMA Standards.
D. The Contractor shall have support services within a 10 mile radius of Project Site and comply with
the service requirement of a two hour on-site response time.
E. As evidence and assurance of the contractor’s ability to support the Owner's system with service
and parts, the contractor must have been in the BAS business for at least the last five (5) years and
have successfully completed total projects of at least 5 times, the value of this contract, in each of
the preceding five years.
H. System shall be installed by factory trained mechanical and electrical installers either in direct
employ of this Contractor or by subcontractors who are under direct supervision of this Contractor.
I. Use only manufacturer trained technicians who are skilled, experienced, trained, and familiar with
the specific equipment, software and configurations to be provided under this section.
J. Coordinate with the Owner to ensure that the BAS will perform in the Owner’s IT environment
without disruption to any of the other activities taking place on that LAN or WAN
K. Coordinate timely delivery of materials and supervise activities of other trade contractors to install
inline devices such as immersion wells, pressure tappings, any associated shut-off valves, flow
switches, level switches, flow meters, air flow stations, and other such items furnished under this
section but installed by other trades.
L. Select sensors and transducers to most closely match the expected sensing or control range.
M. Mark and detail exact location of inline devices, wells, and taps to be installed by Mechanical
Contractor on coordination drawings.
N. Instrumentation with factory J-boxes shall not be used for junction boxes.
O. Install control equipment, wiring and air piping in neat and workmanlike manner to satisfaction of
A/E, and in accordance with manufacturer's recommendations. Maintain clearances, straight length
distances, etc. required for proper operation of each device.
P. Install control devices in accessible location. Coordinate all control device locations with other
trade contractors.
Q. All safety devices shall function when VFD is in auto, hand or bypass mode.
Page 7 of 53
University of Florida 11/09/07
Control System Guide Specification
1. Wire VFD’s so that all safeties and interlocks remain operational (inclusive of isolation
dampers, isolation valves, end switches, interlocks, safeties etc) when drive is placed in
Auto, Hand or Bypass mode.
2. Safeties and interlocks shall be wired on motor side of the VFD and Bypass.
Include if VFD with by-pass is used. Remove bypass reference if VFD's are specified without Bypass.
-------------------------------------------------------------------------------------------------------------------------------------------
R. Provide weather protection cover or weatherproof control devices where required for control devices
located outdoors.
1. All control devices located outdoors shall be rated for the anticipated environment.
2. Include provisions for supplemental ventilation when control devices must be located within
these outdoor control panels.
S. All digital equipment furnished under this contract shall have been tested and made to comply with
limits for Class A computing device pursuant to Subpart J of Part 15 of FCC Rules.
Page 8 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
9. Stability of Control: Control loops shall maintain measured variable at setpoint within the
tolerances listed below:
U. Provide all points required to implement control sequences specified, whether or not they are listed
in schedules.
V. All outputs, whether sequenced or not, shall have separate programmable hardware outputs. For
air handling units, minimum outside air, maximum (economizer) outside air, return, relief air, smoke
dampers, heating valves, cooling valves, etc., shall each have separate output.
W. Point and Alarming expectations: The system includes points and alarms as the following:
1. Unless otherwise noted, provide the following Air Handling System I/O and adjustable points
listed below:
Point Alarm Notification
a. Occupied Mode No
b. Fan Command No
c. Fan Status Yes
d. Static Pressure Yes
e. Static Setpoint No
f. Fan Speed Command Yes
g. Low Static Alarm Status Yes
h. High Static Alarm Status Yes
i. Low Limit Alarm Status Yes
Page 9 of 53
University of Florida 11/09/07
Control System Guide Specification
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
AHU application.
-------------------------------------------------------------------------------------------------------------------------------------------
2. Unless otherwise noted, provide the following Air Terminal Unit System I/O and adjustable
points listed below:
Point Alarm Notification
a. Damper Output Yes
Page 10 of 53
University of Florida 11/09/07
Control System Guide Specification
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
ATU application.
-------------------------------------------------------------------------------------------------------------------------------------------
3. Unless otherwise noted, provide the following Fan Coil Unit System I/O and adjustable points
listed below:
Point Alarm Notification
a. Duct Smoke Detector Yes
b. Filter Status Yes
c. Fire Shutdown Relay Yes
d. Fan Status Yes
e. Cooling Coil Valve Yes
f. Drain Pan Float Switch Yes
g. Heating Coil Valve Yes
h. Discharge Temperature Yes
i. Space Temperature Yes
j. Heating Setpoint (+ Or - 3.0 Deg F) No
k. Cooling Setpoint (+ Or - 3.0 Deg F) No
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
FCU application.
-------------------------------------------------------------------------------------------------------------------------------------------
4. Unless otherwise noted, provide the following Chilled Water System I/O and adjustable points
listed below:
Point Alarm Notification
a. Chilled Water Flow Yes
b. Plant Chilled Water Supply Temperature Yes
c. Plant Chilled Water Supply Pressure Yes
d. Plant Chilled Water Return Temperature Yes
e. Plant Chilled Water Return Pressure Yes
Page 11 of 53
University of Florida 11/09/07
Control System Guide Specification
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
CHW application.
-------------------------------------------------------------------------------------------------------------------------------------------
5. Unless otherwise noted, provide the following Hot Water System I/O and adjustable points
listed below:
Point Alarm Notification
a. Steam Pressure Yes
b. Steam Flow Yes
c. 1/3 Steam Valve Yes
d. 2/3 Steam Valve Yes
e. Heating Hot Water Supply Temperature Yes
f. Heating Hot Water Supply Setpoint Yes
g. Pump Command No
h. Pump Status Yes
i. Pump Speed Command Yes
j. Pump Speed Feedback Yes
k. Pump Vibration Transmitter Yes
l. Pump VFD Alarm Yes
m. Heating Hot Water Flow Yes
n. Differential Pressure Yes
o. Heating Hot Water Return Temperature Yes
p. Condensate Flow Yes
q. Condensate Pump Alarm Yes
Page 12 of 53
University of Florida 11/09/07
Control System Guide Specification
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
HHW application.
-------------------------------------------------------------------------------------------------------------------------------------------
6. Unless otherwise noted, provide the following Electrical I/O and adjustable points listed below:
Point Alarm Notification
a. Building Total Elec. Consumption Yes
b. Building Instantaneous Elec. Yes
c. Building Phase A Voltage Yes
d. Building Phase A Current Yes
e. Building Phase B Voltage Yes
f. Building Phase B Current Yes
g. Building Phase C Voltage Yes
h. Building Phase C Current Yes
7. Unless otherwise noted, provide the following Exhaust System I/O and adjustable points listed
below:
Point Alarm Notification
a. System Start Up No
b. Lead Fan No
c. Redundant Fan No
d. Rotation No
e. Static Pressure Yes
f. Static Pressure Setpoint No
g. Exhaust Fan Damper Output Yes
h. Exhaust Air Damper Status Yes
i. Exhaust Fan Command Yes
j. Exhaust Fan VFD Speed Command Yes
k. Exhaust Fan VFD Speed Feedback Yes
l. Exhaust Fan VFD Alarm Yes
m. Fan Minimum On Time Yes
n. Fan Runtime Yes
Ideally points should be in drawings. Points are for a typical system Adjust points and add alarm for specific
Exhaust application.
----------------------------------------------------------------------------------------------------------------------------------
Page 13 of 53
University of Florida 11/09/07
Control System Guide Specification
1.6 COMMISSIONING
A. Assist Testing Adjust Balance Contractor in verifying system operation for all modes of operation.
B. Demonstrate the sequence of operation for each system and/or sub-system to [Commissioning
Agent (Cx) and/or Engineer]. Perform all other requirements and perform all services as required
in specification Section [(#####) Commissioning Requirements].
Edit per project requirements and cross reference other related sections. All references to commissioning
activities shall be coordinated with commissioning specification.
-------------------------------------------------------------------------------------------------------------------------------------------
1. Use either vendor specific forms or commissioning agent documentation to document the
operation and performance of all control systems.
2. Demonstrate functional tests for on each point, control strategy, and control loop.
3. Provide trends, schedules, printouts, etc to Cx as requested to document system performance.
Consultant shall confirm with University of Florida Project Manager whether this project will utilize a
Commissioning Agent. The control contractor shall provide appropriate commissioning documents as
described above, regardless of Cx participation. Edit above as appropriate.
-------------------------------------------------------------------------------------------------------------------------------------------
1.7 SUBMITTALS
A. Organized submittals based on specification numbers with major tabs to separate major sections
and a master index indicating all elements of submittal.
B. Identify specific parts and accessories proposed for project. Order submittals based on the
specification section.
Page 14 of 53
University of Florida 11/09/07
Control System Guide Specification
a.Schedules including a separate line for each valve and a column for each of the valve
attributes: Code Number, Configuration, Fail Position, Pipe Size, Valve Size, Body
Configuration, Close off Pressure, Capacity, Valve CV, Calculated CV, Design Pressure
drop, Actual Pressure drop, and Actuator Type.
b. Engineering calculations for sizing modulating control dampers including outside, return,
and relief air dampers of air handling and exhaust systems.
8. Room Schedule including a separate line for each terminal unit indicating terminal
identification, minimum/maximum cfm, box area, thermostat/sensor location, Htg/Clg
Setpoints and bias setting. The schedule shall include typical calibration factors to be filled in
by TAB contractor during startup and verification.
9. FCC compliance.
Insert appropriate requirements for project as designed.
-------------------------------------------------------------------------------------------------------------------------------------------
D. Training Plan
1. Schedule
2. Agenda
3. Classes
4. Participants
E. Integration Plan
1. Coordination of vendor protocol and pointlist submission.
2. Workflow processes to integrate systems.
3. Include communication hardware, software, and protocols to implement full systems
integration.
4. Identify proposed enhancements or deviations from project documents. Include specific
drawings or specifications impacted.
5. Provide coordination efforts to accommodate complete integration of systems including:
a. Vendor protocol requirements.
b. Vendor pointlist.
Edit integration requirements and cross reference integration requirements with other sections.
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 15 of 53
University of Florida 11/09/07
Control System Guide Specification
2. Provide product operational and maintenance data in electronic PDF format (Acrobat latest
version- 6.0 or greater) on vendor specific server, and provide means to access this data using
intuitive operator interaction (quick links from main system graphics).
a. Include name and 800 number of a 7 day a week 24 hour a day service line for needed
service during the first year of operation
G. Software Manual:
1. As part of operating and maintenance manuals, submit one software manual to UF PPD plus
one extra copy for archive use. Divide software manuals into separate parts with tabs for each
part. CD versions of this information may be provided as the archive copy
2. Include the following:
a. Complete description of operating system including all commands, configuration programs,
printouts, logs, database functions and passwords.
b. Describe general operating procedures, starting with system overview and proceeding to
detailed description of each software command feature with sample printed displays and
system function description for each option. Include instructions on verifying errors, status,
changing passwords and initiating or disabling control programs.
c. Complete description of programming language including all commands, configuration
programs, control loop functions and testing.
d. Describe general programming procedures, starting with system overview and proceeding
to detailed description of each software command feature. Include instructions on creating
or modifying any control algorithm or parameter, debugging, etc. Include all control
functions, algorithms, mathematic equations, variables, setpoints, time periods, messages,
and other information necessary to load, alter, test and execute custom or pre-written
programs.
e. Factory standard technical manuals may be provided in lieu of copied subsections.
f. Software Backup: Upon successful completion of acceptance testing, submit to Owner 2
archive copies of all accepted versions of source code and compiled code for all
application programs and data file on compact disc media. All control software must be
readily accessible by Owner using BAS server hardware and software.
H. Record Drawings:
1. Submit as-built shop drawings indicating all changes made during project.
a. Install all as-built control drawings (and associated sequence of operation) in electronic
format on specific server, and provide means to access this data using intuitive
interaction by end users.
b. Each system web page shall allow for an automatic link to the associated control diagram.
Provide operator a way to access product and as-built control information from the
associated system web page (e.g. AHU system, chilled water system, hot water system,
VAV system, etc…)
2. Mount system control diagrams (including sequence of operations), laminated and mounted
under 11X17 plexi-glass frame within associated mechanical space.
3. Mount (within control panel or in separate enclosure) control panel wiring diagrams (also
laminated) indicating all field points connected.
a. The control panel wiring diagrams shall utilize the same field device tag names used within
the associated control diagram.
b. Not required for room level controllers.
Coordinate all submittal requirements with Division 1.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 16 of 53
University of Florida 11/09/07
Control System Guide Specification
1.8 WARRANTY
A. Submit warranty documentation upon substantial completion of project or phase (if applicable) and
acceptance by Engineer and Owner.
F. Provide a minimum two year warranty for all parts provided under this section. Warranty includes all
services, materials and equipment necessary to cover defective hardware replacement, software
modifications and debugging of the entire system for a period of one year after final acceptance by
the A/E and the Owner.
rd
1. First year of warranty includes parts and labor for entire system (including 3 party equipment).
Adjust, repair, or replace, at no additional cost to the owner, Control system failures during
the 1st year.
2. Second year of warranty includes parts only.
G. Warranty response time shall be within two hours or less of being notified. The designated UF PPD
representatives representing the operations and service departments shall be the authorized callers
and will determine the required response level.
1. Emergency service - must respond within two hours of being notified.
2. Warranty service - must respond within 4 hours of being notified.
3. Scheduled service – must respond within 48 hours of being notified.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 17 of 53
University of Florida 11/09/07
Control System Guide Specification
F. Provide classroom training for XX Owner’s representatives. Include all cost (lodging, tuition, and
lab materials) required for factory training at the manufacturer's training site for one UF-PPD
employee for every 100,000 square feet of gross facility space that is partially or fully controlled by
contractor's product.
1. Site or field training does not replace factory training.
2. Factory training does not substitute for site/field training.
Coordinate all training requirements with University of Florida-PPD.
-------------------------------------------------------------------------------------------------------------------------------------------
PART 2 - PRODUCTS
2.1 SOFTWARE
Page 18 of 53
University of Florida 11/09/07
Control System Guide Specification
3. Read and display the value of any property, including all required properties, supported optional
properties, and proprietary extensions of every object located within each networked device.
4. The ability to execute custom, job-specific processes to automatically perform calculations and
special control routines.
a. Incorporate measured or calculated data from l other DDC controllers on the network.
b. Issue commands to points in other DDC controllers on the network.
c. Support 30 characters, English language point names, structured for searching and logs.
d. Directly send a text message to a specified device or cause the execution of an alarm
message at any connected thin client PC, dial-up connection to a remote device or cause
the execution of a remote connection to a remote device such as a printer, pager, PDA or
cell phone.
e. Include a HELP function key.
f. Incorporate comment lines for program clarity.
C. Alarm management
1. Monitor and direct alarm information to operator devices.
2. Generate custom written operator alarm message (to be developed by the Vendor / Installer in
conjunction with the owner) and advisories to operator I/O devices.
3. Perform distributed, independent alarm analysis and filtering to minimize operator interruptions
due to non-critical alarms, minimize network traffic and prevent alarms from being lost.
a. At no time shall the ability of the BLC/AAC to report alarms be affected by either a remote
PC, local I/O device or communications with other panels on the network.
b. All alarm or point change reports shall include the point’s English language description and
the time and date of occurrence.
4. Users shall have the ability to manually inhibit alarm reporting for each point.
5. Alarm suppression
a. Prevent abnormal alarms from occurring when associated system has been deactivated,
such as:
1) AHU shut down shall suppress low static alarm.
2) Boiler shut down shall suppress low temperature alarm.
b. Minimize alarms at sub-systems resulting from central equipment malfunction. For
example:
1) Chilled water high alarm shall suppress AHU High temperature alarm.
2) AHU low static alarm shall suppress VAV box low flow alarm.
6. Alarm destinations shall be included so that alarms are indicated and printed at a pre-defined
University of Florida reporting device, personnel, or transaction log.
a. Alarm reports and messages will be directed to a user-defined list of operator devices or
PCs based on time (after hour’s destinations) and/or based on priority.
b. Alarms shall directly send an alarm message to specified client PC destination or cause
the execution of a dial-up connection to a remote device (owner to designate) and cause
the execution of a communications connection to a remote wireless device (pager, hand
held, email or Pocket PC device).
c. Alarm messages, and point graphic assignments alarms shall have accurate descriptions
and response instructions, so that alarms may be quickly associated with appropriate
graphic display.
7. Alarm reports to multiple WEB connected PC’s, cell phones or PDA’s and shall send alarm
reports without dependence upon a central or intermediate processing device.
Page 19 of 53
University of Florida 11/09/07
Control System Guide Specification
Consultant to review requirements and edit as appropriate. Actual point alarming requirements should be
identified in point list. All alarm or point change reports shall include the point’s English language description
and the time and date of occurrence.
-------------------------------------------------------------------------------------------------------------------------------------------
D. A variety of historical data collection utilities shall be provided to manually or automatically sample,
store, and display system data for points as specified in the I/O summary.
1. Any point, physical or calculated, may be designated for trending.
2. Any point, regardless of physical location on the network, may be collected and stored in each
BLC/AAC point group.
3. Two methods of collection shall be allowed: either by a pre-defined schedule or upon a pre-
defined change of value. Sample intervals of 1 minute to 7 days shall be provided.
4. Each BLC/AAC shall have a dedicated RAM-based buffer for trend data and shall be capable of
storing a minimum of 10,000 data samples. All trend data shall be available for use in 3rd party
data manager applications (i.e. SQL, Microsoft Excel, Lotus 123).
5. BLC/AAC units shall provide high resolution sampling capability for verification of control loop
performance.
6. Operator-initiated automatic and manual loop tuning algorithms shall be provided for operator-
selected PID control loops as identified in the point I/O summary.
E. BLC/AAC units shall be capable of automatically accumulating and storing run time hours for digital
input and output points and automatically sample, calculate and store consumption totals for analog
and digital pulse input type points, as specified in the point I/O schedule.
F. The building level network shall allow the BLC/AAC units to access any data from or send control
commands and alarm reports directly to any other BLC/AAC or combination of controllers on the
network without dependence upon a central or intermediate processing device.
G. The building level network shall also allow any BLC/AAC to access, edit, modify. add, delete, back
up , and restore all system point database and all programs.
H. Failsafe hardware shall be provided such that BAS failures result in immediate return to local
control. If the controller uses database values from other controllers, and the communication
network fails or malfunctions, control loop outputs shall continue to function using last value
received from BAS.
I. The BLC/AAC shall automatically call for a new database download from the server upon loss or
corruption of a database. An operator with sufficient access privileges may in addition, activate a
database download manually from the server.
A. All cables (< 50 VAC/VDC) used within control system shall contain an overall jacket (plenum rated)
The intent of this paragraph is to hold the control contractor responsible for power wiring associated with the
various field devices (actuators, meters, intermediate power supplies, etc… In most cases the control
contractor can utilize the 120 VAC line voltage power serving the DDC panel for all field device power
requirements. It is up to the consultant to coordinate (with the electrical engineer) power points that will be
needed for the DDC system. Power must be provided for both main equipment control panels and terminal
unit controllers.
Page 20 of 53
University of Florida 11/09/07
Control System Guide Specification
Locating an BAS power junction box (w/circuit dedicated for DDC power) within a mechanical room is the
preferred method. This gives the control contractor the flexibility to run power from this j-box to wherever its
needed.
-------------------------------------------------------------------------------------------------------------------------------------------
B. Jacket Color-Coding:
1. I/O low voltage signal wire: Gray
2. Field Device Low Voltage (< 50 VAC/DC) Power Wiring: Orange
3. Communication Cable: White
-------------------------------------------------------------------------------------------------------------------------------------------
F. Communication Cable:
1. Minimum 24 AWG twisted pair cable, Category 5E, or fiber optics for communications between
control devices. Provide additional shielding and grounding per applicable manufacturer’s
recommendations and/or job site conditions. Conductors shall have UL listed plenum rated
teflon insulation.
A. Copper Tubing:
1. Type L, hard or soft seamless, ASTM B88, wrought copper soldered fittings, ANSI B16.22
except at connections to apparatus, where brass compression-type fittings shall be used.
2. Solder joints shall be made with ASTM B32, 95-5 tin-antimony solder-joint, Bridgit or Silvabrite.
B. Plastic Tubing:
1. Fire resistant virgin polyethylene, meeting stress-crack test ASTM D1693-60T.
2. Individual tube polyethylene or multi-tube instrument tubing bundle shall be classified as flame
retardant under UL 94 and polyethylene material shall be rated as self-extinguishing when
tested in accordance with ASTM D 635.
C. Isolation valves for air piping to be threaded or soldered, two piece, bronze ball valves. Valves shall
be suitable for intended service and pressure.
Page 21 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 22 of 53
University of Florida 11/09/07
Control System Guide Specification
A. Local control panels shall be constructed of steel, high strength composite, or extruded aluminum
with hinged door and keyed lock, with baked enamel finish of manufacturer's standard color.
Construction shall comply with NEMA 1 standards for interior panels, NEMA 4 for exterior panels.
Consultant should adjust per project conditions. NEMA 1 for indoor applications and NEMA 4x for outdoor
conditions.
-------------------------------------------------------------------------------------------------------------------------------------------
B. Panel mounted controlling instruments, temperature indicators, relays, switches and gauges shall
be factory installed and permanently labeled. Devices shall be located inside or flush mounted on
face of panel.
A. BACnet Router: The BAS shall use the campus Wide Area Network (WAN) for communication to
the campus vendor specific server.
B. The communication between the central server and the buildings DDC controllers shall be
BACnet/IP.
C. This router or a separate broadcast manager shall limit BACnet data traffic to within the building
level network until a remote request for information is requested or when a message must be
transmitted outside the building level network.
A. BLC units shall be a general purpose multiple application direct digital controller (DDC) used to
manage global programs, complex system control, local data storage, building level
communications, and remote server interface.
1. Controllers shall have a minimum 32-bit microprocessor. Controllers shall be capable of
operating in a stand-alone capacity or within a networked Ethernet environment.
2. Controller hardware, firmware and software shall support true, non-volatile flash memory,
input/output, 12 bit A to D conversion, hardware clock/calendar and voltage transient and
lightning protection devices.
3. Units shall be equipped with full multi-tasking, multi-user real-time digital control processors
consisting of modular hardware with plug-in enclosed processors, communication controllers
and power supplies.
4. Controller size shall be sufficient to fully meet the requirements of this specification.
B. The BLC shall perform the function of monitoring all system variables, including but not limited to:
1. Hardware points, software points and controller parameters such as setpoints.
2. Software/hardware required to interface at the campus intranet and peer to peer level (Tier 1)
using the ANSI/ASHRAE Standard 135-2001 BACnet/IP protocol.
3. The BLC shall manage and direct all information traffic on the Tier 1 network, between the Tier
1 and Tier2 networks, and to servers.
4. Each BLC shall be able to extend its performance and capacity through the use of remote
Application Specific Controllers (ASC's) and Advanced Application Controllers (AAC).
5. BLC shall provide an RS-232C serial data communication port or Ethernet RJ45 connection for
operation of local operator I/O devices independent of the LAN used for primary access, such
as industry standard printers, operator terminals, modems and portable laptop
Page 23 of 53
University of Florida 11/09/07
Control System Guide Specification
operators/terminals. BLC shall allow temporary use of portable devices without interrupting the
normal operation of permanently connected Ethernet, modems, printers or terminals.
6. Each BLC shall have sufficient memory to support its own operating system and databases,
Including:
a. Control processes
b. Energy management applications
c. Alarm management applications including custom alarm messages for each level of alarm
for each point in the system
d. Historical / trend data for points specified
e. Maintenance support applications
f. Custom processes
g. Operator I/O
h. Ethernet/Dial-up communications
i. Manual override monitoring
7. Configuration and Download: The BLC shall have the capability of receiving configuration and
program loading by means of the following: 1) locally, via a direct connect portable laptop
service tool, 2) over the network, from the portable laptop service tool, and; 3) from the server
or associated thin client PC, via the communication networks.
8. Configuration and Upload: The BLC shall have capabilities of uploading configurations
program to be archived on local operator terminal and/or remote server.
9. Each BLC shall contain both software and firmware to perform global control strategies.
10. Each BLC shall continuously perform self-diagnostics, including communication diagnosis of all
panel components. The BLC shall provide both local and remote annunciation of any detected
component failures, low battery condition or repeated failure to establish communication.
11. Isolation shall be provided at all peer-to-peer network termination’s, as well as all field point
termination’s to suppress voltage transients consistent with IEEE Standards 587-1980
12. In the event of the loss of normal power, there shall be an orderly shutdown of all BLC's to
prevent the loss of database or operating system software. Nonvolatile flash type memory shall
be incorporated for all critical controller configurations and battery backup shall be provided to
support the real-time clock and volatile memory for a minimum of 72 hours.
a. Upon restoration of normal power, the BLC shall automatically resume full operation
without manual intervention. Provide for the orderly and predefined scheduling of
controlled return to normal, automatically time scheduled, operation of controlled
equipment as a result of the auto restart processes.
b. Should BLC memory be lost for any reason, the user shall have the capability of reloading
the BLC via the local RS-232C port or from an Internet client or server PC.
c. All BLC units shall include an internal or external UPS power supply unit to insure reliability
of network communications through any power outage event. UPS shall be sized for 50%
spare capacity. The UPS shall be complete with batteries, external bypass and line
conditioning.
The consultant shall consider UPS power backup for BLC’s when a controlled shutdown/startup of equipment
is required after standby power transfer. Power for BLC controllers, AAC controllers and ASC controllers shall
be served from emergency power when controlling emergency powered equipment. Note: All supervisory
controllers located upstream of any controller powered from the emergency system in the network should be
tied to emergency power to ensure communication is maintained throughout the BAS architecture.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 24 of 53
University of Florida 11/09/07
Control System Guide Specification
13. The BLC shall be capable of direct connection to multiple field busses. Communication Speed
(Building Level Network): Local controllers shall communicate at a minimum of 115 Kbps.
A. AAC units shall be a general purpose multiple application direct digital controller (DDC) used to
manage complex system control, local data storage, and building level communications.
C. Each AAC shall be able to extend its performance and capacity through the use of remote
Application Specific Controllers (ASCs).
D. Each AAC shall provide an RS-232C serial data communication port for operation of local operator
I/O devices independent of the LAN used for primary access, such as industry standard printers,
operator terminals, modems and portable laptop operators/terminals.
1. Allow temporary use of portable devices without interrupting the normal operation of
permanently connected modems, printers or terminals.
2. As indicated in the point I/O schedule, the operator shall have the ability to manually override
DO automatic or centrally executed commands at the AAC via local terminal or controller DO
manual H/O/A point for digital control type points.
a. Switches shall be mounted either within the controller's key-accessed enclosure, or
externally mounted with each switch keyed to prevent unauthorized overrides.
b. Monitor the status of all overrides and inform the operator that automatic control has been
inhibited. The AAC shall also collect override activity information for reports.
Consultant should edit above as required. DO manual override is not necessary when starters are used and
incorporate hand-off-auto controls or when VFD’s are used with manual override. Manual override
requirements shall be identified in point lists. Terminal level controllers (VAV air terminal, FCU, FTU, reheat
etc…) do not require DO manual override.
-------------------------------------------------------------------------------------------------------------------------------------------
3. As indicated in the point I/O schedule, the operator shall have the ability to manually override
AO automatic or centrally executed commands at the AAC via local terminal or controller AO
manual Hand/Auto point for analog control type points.
a. Switches shall be mounted either within the AAC'S key-accessed enclosure, or externally
mounted with each switch keyed to prevent unauthorized overrides.
b. The AAC shall monitor the status of all overrides and inform the operator that automatic
control has been inhibited. The AAC shall also collect override activity information for
reports.
Page 25 of 53
University of Florida 11/09/07
Control System Guide Specification
Consultant should edit above as required. AO manual override is required at major equipment only (AHU’S
chillers, boilers, exhaust systems, etc…). Manual override requirements shall be identified in point lists.
Terminal level controllers (VAV air terminal, FCU, FTU, reheat etc…) do not require AO manual override.
-------------------------------------------------------------------------------------------------------------------------------------------
4. Each AAC shall have sufficient memory to support its own operating system and databases,
Including:
a. Control processes
b. Energy management applications
c. Alarm management applications including custom alarm messages for each level of alarm
for each point in the system
d. Historical / trend data for points specified
e. Maintenance support applications
f. Custom processes
g. Operator I/O
h. Manual override monitoring
5. Configuration and Download: The AAC shall have the capability of receiving configuration and
program loading by means of the following: 1) locally, via a direct connect portable laptop
service tool, 2) over the network, from the portable laptop service tool, and; 3) from the server
or associated thin client PC, via the communication networks.
6. Configuration and Upload: The AAC shall have capabilities of uploading configurations
program to be archived on local operator terminal and remote server.
7. Each AAC shall contain both software and firmware to perform full DDC Proportional, Integral,
Derivative (PID) control loops and programs.
8. Each AAC shall continuously perform self-diagnostics, including communication diagnosis of all
panel components. The AAC shall provide both local and remote annunciation of any detected
component failures, low battery condition or repeated failure to establish communication.
9. Isolation shall be provided at all peer-to-peer network termination’s, as well as all field point
termination’s to suppress voltage transients consistent with IEEE Standards 587-1980.
10. In the event of a loss of normal power, there shall be an orderly shutdown of all AAC'S to
prevent the loss of database or operating system software. Nonvolatile flash type memory shall
be incorporated for all critical controller configurations and battery backup shall be provided to
support the real-time clock and volatile memory for a minimum of 72 hours.
a. Upon restoration of normal power, the AAC shall automatically resume full operation
without manual intervention. Vendor / Installer shall add custom programming to
sequentially start all controlled equipment with a time delay between each command.
b. Should AAC memory be lost for any reason, the user shall have the capability of reloading
the controller via the local RS-232C port or from an Internet client or server PC.
c. All AAC units shall include an internal or external UPS power supply unit to insure reliability
of network communications through any power outage event. UPS shall be sized for 50%
spare capacity. The UPS shall be complete with batteries, external bypass and line
conditioning
The consultant shal consider UPS power backup for critical applications. Edit as appropriate.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 26 of 53
University of Florida 11/09/07
Control System Guide Specification
11. All AAC units shall be expandable and shall act as one control unit. In addition to the specified
I/O point requirements and capacity requirements the Contractor shall provide two spare DI’s,
DO’s, AI’s, and AO’s per panel.
12. Communication Speed (Building Level Network): Local controllers shall communicate at a
minimum of 115 Kbps.
A. Performance and capacity of AAC/BLC units shall be extended through the use of stand-alone
remote ASC’S for VAV terminals, fan coil units, unit ventilators, heat pumps, small single zone air
handlers etc.
1. Controllers shall be capable of field configuration and program uploads and downloads.
2. Controllers shall operate as a stand-alone controller capable of performing its specified control
responsibilities independently of other controllers in the network.
3. Controllers shall be a microprocessor-based, multi-tasking, real-time digital control processor.
B. Alarm Management: Each ASC shall perform its own limit and status monitoring and analysis to
maximize network performance by reducing unnecessary communications.
C. ASC’S shall include all point inputs and outputs necessary to perform the specified control
sequences. Analog outputs shall be industry standard signals such as 24V floating control, 4-20ma
proportional signals, 0-5 Vdc or 0-10 Vdc proportional signals allowing for interface to a variety of
modulating actuators.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 27 of 53
University of Florida 11/09/07
Control System Guide Specification
G. Systems Accuracy ±1% of reading from 2% to 100% of the rated current of the CTs. accomplished
by matching the CTs with a meter and calibrating them as a system
I. Electrical Services:
J. Any service where the phase A-N voltage is ≤300VAC and the phase-to-phase voltage is≤480VAC
nominal with neutral
K. Frequency 50/60Hz.
-------------------------------------------------------------------------------------------------------------------------------------------
2.11 SERVERS
A. Provide, a commercially available laptop PC with Windows operating system, standard control
system engineering tool set, all required interface cables, and at least 256 MB of RAM. LCD backlit
display and a full-featured keyboard. The laptop shall plug directly into all controllers and unitary
controllers and include one standard Ethernet connection. Provide a user-friendly, English
language-prompted interface for quick access to system information, not codes requiring look-up
charts.
1. Functionality of the portable operator’s terminal connected at any general controller:
a. Backup and /or restore controller databases for all system panels, not just the controller to
which it is connected.
b. Display all point logs.
c. Add, modify and/or delete any existing or new system point.
d. Command; change set point, enable/disable any system point.
e. Program and load custom control sequences as well as standard energy management
programs.
2. Connection of a laptop to any controller shall not interrupt nor interfere with normal network
operation in any way, prevent alarms from being transmitted to server or preclude centrally
initiated commands and system modification.
Consultant shall coordinate laptop requirements with PPD. Not all projects will require supplemental laptop
PC.. For special applications, consider upgrading requirements for on board RAM to 512 MB.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 28 of 53
University of Florida 11/09/07
Control System Guide Specification
A. General:
1. Use 2 port (normally open or closed based on sequence of operation) or 3 port globe type
control valves with equal percentage contoured throttling plugs for steam and AHU water
applications, unless otherwise noted.
2. Use 2 port (normally open or closed based on sequence of operation) or 3 port ball type valves
for terminal reheat control unless otherwise noted.
Consultant should insure control diagrams and/or valve schedules clearly indicate normally open and normally
closed requirements. UF standard is to have cooling devices fail open and heating devices fail closed.
3. Butterfly valves may be used for water system control valves 2-1/2" and larger provided that
valves meet pressure and temperature requirements.
a. High performance butterfly valves shall be used for modulating applications.
b. General-purpose butterfly valves may be used for two-position control.
B. Globe Valves:
1. Valves shall be bronze or brass body, threaded, 150 psi rating for 2" and smaller, iron body
bronze mounted, flanged, 125 psi rating for 2-1/2" and larger.
2. Valves shall have stainless steel stems, spring-loaded teflon packing, replaceable seats
and discs.
C. Ball Valves
1. Valves shall be bronze or brass body, 150 psi rating. Ball valves larger than 2” are not
permitted.
2. Valves shall have stainless steel ball and stem, valve stem seals with dual EPDM O-Rings,
rangeability must be greater than 150:1, and shall have equal percentage flow characteristics.
D. Solenoid Valves:
1. Brass or bronze body. Valves shall be selected to match required temperatures and pressure,
and shall have materials which are compatible with intended working fluid.
2. All line voltage actuators shall be Class "H" (high temperature) and listed by UL or CSA.
A. General:
1. If control damper sizes are not shown or scheduled, refer to Part 1 of this Section for sizing
criteria.
2. Unless otherwise indicated, modulating control dampers shall be opposed blade or parallel
blade type and two position (open/close) dampers shall be parallel blade type.
3. All blade linkage hardware shall have corrosion-resistant finish and be readily accessible for
maintenance.
Page 29 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
D. Smoke Dampers:
2
1. Dampers to be leakage rated at no higher than Leakage Class I (4 cfm/ft at 1" WG and 8
2
cfm/ft at 4" WG) under UL 555S at temperature category 250°F. Furnish dampers with
factory-mounted, caulked sleeve and pneumatic or electric operator. Damper shall have 16-
gauge frame with air foil-shaped blades, rated to minimum 4" WG in closed position and to
2000 fpm in open position.
Note the 2000 fpm limitation. If 4000 fpm is required, flat spec Ruskin SD60.
-------------------------------------------------------------------------------------------------------------------------------------------
2. Actuator assemblies shall be installed outside airstream, linked to damper for fail (normally)
[open/closed] operation. Actuator shall be capable of closing damper at pressures
encountered in system.
3. Size smoke dampers as close as possible to duct size, but in no case is damper size to be less
than duct size.
4. Dampers shall fully open in 15 seconds or less and fully close in not more than 15 seconds and
not less than 7 seconds when activated.
5. For pneumatic applications, provide 120 VAC E-P switches to interface with Fire Protection
System.
Verify voltage requirement of the Fire Protection System for proper E-P switch voltage.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Damper and valve actuators for major equipment [Central Utility Plant, AHU’s, Lab Exhaust Fan
Systems, etc] located in mechanical rooms shall be pneumatic type. Actuators for all remote
Page 30 of 53
University of Florida 11/09/07
Control System Guide Specification
devices [ VAV Terminal Units, Reheat Coils, FCU’s, Heat Pumps, etc…] located in spaces
outside of mechanical rooms shall be electric type.
Consultant should confirm pneumatic requirements with University of Florida Project Manager and UF-PPD.
In many cases, an existing pneumatic system may be extended to accommodate new work. The consultant
should verify the availability of campus air within existing or proposed new building site.
-------------------------------------------------------------------------------------------------------------------------------------------
B. Each actuator shall be full-proportioning or two-position type as required or specified, and shall be
provided with spring-return for fail open or fail closed position for fire, freeze, occupant safety,
equipment protection, moisture, heating or cooling protection on power interruption as indicated
and/or as required. Smoke dampers and steam valves serving pressure rated heat exchangers or
convertors shall fail closed.
C. Pneumatic Diaphragm with Spring Return: Actuators shall be same manufacturer as valve body
and shall be selected to match maximum diaphragm air pressure, fail position, stroke, shutoff
pressure, temperature, torque, etc., required for intended service. Unless otherwise scheduled,
diaphragm air pressure shall be enough to provide 100% valve shutoff at least equal to pump
shutoff head or 125% of rated flow head for water systems, or full rated pressure for steam
systems. Select spring ranges to match intended service. If valves or dampers are sequenced,
spring ranges shall not overlap.
Standard.
-------------------------------------------------------------------------------------------------------------------------------------------
D. Pneumatic Piston Actuator: Provide dual action piston actuators for large torque applications.
Actuators shall be sliding piston type with appropriate linkage and mounting hardware. Provide
units suitable for 60 to 100 psig compressed air operation, self-draining body, position indicator, and
spring return if fail position required. Body shall be aluminum or fiberglass with aluminum piston,
BUNA-N or PTFE piston seals, and open/close travel stops.
Standard with large butterfly valve.
-------------------------------------------------------------------------------------------------------------------------------------------
F. Analog Electronic:
1. Actuators shall be electric motor/gear drives which respond proportionally to analog voltage or
current input. Stroke time for major equipment shall be 90 seconds or less for 90° rotation.
Stroke time for terminal equipment shall be compatible with its associated local controller, but
no more than 6 minutes.
2. Provide spring return feature for fail open or closed positions as required by control sequence
and for critical applications such as outside, return, or exhaust dampers, heating and cooling
coils on major air handling units, humidifiers, heat exchangers, and flow control for major
equipment items such as chillers, cooling towers, boilers, etc.
3. Reheat terminal units - Utilize factory assembled ball valve with horizontal mount; non-spring
return proportional actuator (0-10 Vdc, 0-5Vdc, or 4-20ma). Electric actuator installed on ball
valves shall have a separate and distinct operating handle used to position the valve into any
Page 31 of 53
University of Florida 11/09/07
Control System Guide Specification
desired position once power is removed or a valve failure occurs. Similar to Belimo B2 CCV
Series valve/actuators
4. Actuators for terminal heating/cooling equipment do not require spring return feature.
5. Provide standard cable from actuator to controller unit.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Pressure Gauges:
Standard for projects with pneumatic actuators.
-------------------------------------------------------------------------------------------------------------------------------------------
1. Air pressure indicating gauges to be at least 1-1/2" diameter. Gauge faces to be marked with
range of unit being controlled.
2. Pressure gauges used for panel-mounted indicators shall be marked in appropriate units and
with appropriate range of values. Panel mounted indicators shall be minimum 4-1/2" in
diameter and have accuracy of 1% of scale range.
A. General:
1. Electrical devices, switches, and relays shall be UL listed and of type meeting current and
voltage characteristics of the project.
2. Outdoor unit enclosures shall be NEMA 4 with concealed adjustment.
3. Ratings of normally open and closed contacts shall be adequate for applied load (Minimum 5
amps at 240 volts).
4. Accuracy of devices shall be ± 1% of scale with adjustable offset unless otherwise specified.
Page 32 of 53
University of Florida 11/09/07
Control System Guide Specification
3. Thermostats with remote sensing bulb shall have liquid filled sensing element and exposed
setpoint adjustment.
4. Wall mounted space thermostat enclosure shall have concealed sensing element and exposed
setpoint adjustment.
5. Unless otherwise stated, space thermostat covers shall be factory standard cover.
Consultant should coordinate with Architect regarding special cover material or finish color requirement.
Some executive offices may require special covers.
-------------------------------------------------------------------------------------------------------------------------------------------
D. Relays:
1. Equal to IDEC type RH2B-U, miniature 8 blade pilot relay with DPDT silver cadmium oxide
contacts rated at 15A, 30 VDC, or 120 VAC or RIB series with H-O-A switch option. Coil shall
match control circuit characteristics. Rectangular base socket mount with blade type plug-in
terminals and polycarbonate dust cover.
2. Control relays with self contained HOA circuit shall satisfy DO HOA requirement for major
equipment start/stop control points.
3. Provide DIN rail mountable (Snap type) mounting sockets equal to IDEC SH2B-05.
E. Pressure Switches:
1. Adjustable set point, differential pressure type. Select switches for accuracy, ranges (20 to
80% of operating range) and dead-band to match process conditions, electrical requirements
and to implement intended functions.
2. Pressure differential switches for air systems shall have pressure rating of at least 10" WG.
3. Pressure indicating differential switches for air systems shall be equal to Dwyer Series 3000
photohelic gauge.
4. Pressure differential switches for water systems shall be rated for 150 psig unless otherwise
noted. Chilled water pressure differential switches shall be provided with totally sealed vapor
tight switch enclosure on 300 psi body. Differential pressure switches to have 3-valve manifold
for servicing.
a. Maximum Temperature Rating: 300°F
b. Repeatability: ± 1%
Page 33 of 53
University of Florida 11/09/07
Control System Guide Specification
b. Repeatability: ±1%
c. Pressure Rating: 300 psi for chilled water
150 psi for other applications
Do not use target type flow switches at pump discharges.
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 34 of 53
University of Florida 11/09/07
Control System Guide Specification
J. Current Switches:
1. Induction type sensor clamped over a single phase of AC electrical power conductor shall be
solid-state sensor with adjustable threshold and normally open contacts. Each current switch
shall be selected for proper operating range of current.
2. VFD and NON-VFD Applications (Similar to Hawkeye Model 904,934)
a. The sensor shall be capable of detecting motor belt or coupling loss when mounted on the
load side of variable frequency drives
b. The current sensor shall be factory programmed to detect motor undercurrent situations
(belt or coupling loss) on variable or constant volume loads, no calibration required
c. The current sensor shall store the motor current operating parameters in non-volatile
memory.
d. The current sensor shall have a push button reset to clear the memory if the operating
parameters change or the sensor is moved to a different load.
e. Transition current: 75 mA at 1 A setpoint
2.5 A at 10 A setpoint
f. Hysteresis: 0.015 A at 1 A setpoint
0.20 A at 10 A setpoint
g. Response Time: less than 0.5 seconds
Page 35 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
Page 36 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
2. Thermistors will be acceptable in lieu of platinum or nickel RTD provided thermistor carries 5
year guarantee that device will maintain its accuracy within tolerance of ± 0.36°F between 32°F
and 150°F, and 0.5°F between -20°F and 212°F.
Thermistors are used by some commercial control vendors as part of their standard solution.. Specify these
as project requires.
3. Unless otherwise stated, space sensor covers shall be factory standard cover
-------------------------------------------------------------------------------------------------------------------------------------------
E. Room Thermostats
1. Setpoint shall be resettable only from remote BAS or from any server/client PC. Temperature
sensors shall be compatible with the associated controlled devices (e.g. DDC air terminal
controller). Mounting box shall be recessed type unless otherwise indicated, or required by the
building construction materials.
2. Room Temperature Sensors shall incorporate a thermistor/RTD element and a portable
operator terminal plug-in port under the cover.
3. Temporary override push-button/timers shall be installed at locations indicated on plans. When
an override controls more than one zone, an 8 ½ x 11 inch framed and laminated map shall be
located adjacent to the override device indicating control zone served. The intent of this
requirement is to ensure the occupants understand the zoning where it is not obvious what the
override device controls or what zones it serves.
4. Where local setpoint is required, provide warmer/cooler setpoint adjustment. Minimum and
maximum adjustable range shall be set through the BAS only.
5. Unless otherwise stated, Room Thermostat covers shall be factory standard cover
Note: Standard UF policy is to have no remote set-point. There are some instances when local set-point is
needed. In these cases consultant shall get UF PPD approval for all proposed locations.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 37 of 53
University of Florida 11/09/07
Control System Guide Specification
a. Wells mounted in pipe 3" and larger may be installed in horizontal or vertical lines provided
element is always in flow (for condensate and other gravity return lines, install in bottom of
pipe).
b. Wells mounted in pipe 2-1/2" and smaller shall be installed at a 90° pipe junction consisting
of tee fitting (2" minimum size) and appropriate reducing fittings.
c. Install sensor well pointed upstream in tee.
Thermistors are used by some commercial control vendors as their standard.. Specify this as project requires.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 38 of 53
University of Florida 11/09/07
Control System Guide Specification
Page 39 of 53
University of Florida 11/09/07
Control System Guide Specification
M. Ducted Air System Static Pressure and Differential Pressure (Velocity) Transmitters:
1. Manufacturers: Modus, Setra, Ashcroft XLDP.
2. Provide transducers/transmitters to convert velocity pressure differential or static duct pressure
relative to sensor location into electronic signal.
3. Unit shall be capable of transmitting linear 4 to 20 mA DC output signal proportional to the
differential (total minus static or static minus ambient) pressure input signals with the following
minimum performance and application criteria:
a. Span: Not greater than twice duct static or velocity pressure at
maximum flow rate, nor more than 16 times velocity
pressure at minimum flow rate.
b. Accuracy: ± 1.0% of span or 1.0% of full scale
c. Dead Band: Less than 0.5% of output
d. Hysteresis: Within 0.5% of span or within 0.5% of full scale
e. Linearity: Within 1.0% of span or within 0.5% of full scale
f. Repeatability: Within 0.5% of output
g. Response: Less than 1 second for full span input
4. Return and exhaust air system static pressure transducers/transmitters shall be furnished with
protective integral air filters on pressure sensing lines from the static pressure sensing stations,
and static air probes to prevent migration of moisture or particulate matter into transducers.
Supply air system sensors do not require integral air filters.
Page 40 of 53
University of Florida 11/09/07
Control System Guide Specification
PART 3 - EXECUTION
3.1 SOFTWARE
A. Coordinate graphics and points for consistency with existing campus system.
B. Continuously archive all data in standard database platform Microsoft Data Engine or Microsoft
SQL. Including but not limited to:
1. I/O points
2. Software points such as
a. Alarm limits
b. Setpoints
c. Parameters
3. Schedules
4. Alarm messages
5. Reports
6. Trends/History
-------------------------------------------------------------------------------------------------------------------------------------------
D. Graphic Displays
1. Provide a color graphic system flow diagram display for each system with all points as indicated
on the point list.
2. Provide graphics for using floor plans of the building as a minimum. Coordinate with the
Architect/Engineer (A/E). Size graphics to allow the operator to read room numbers and
descriptions. Incorporate the capability to navigate section to section as required to view entire
floor and to navigate floor to floor.
3. Color shall be used to indicate normal and alarm conditions within all spaces. Color or
common border lines shall be used to link HVAC equipment with zone(s) served.
4. User shall be able to access the various system schematics and floor plans via a graphical
penetration scheme and/or menu selection.
Page 41 of 53
University of Florida 11/09/07
Control System Guide Specification
a.
User shall be able to penetrate from floor plan to associated HVAC system text based
display.
5. Create enhanced alarm programs for all system points. These points shall be programmed for
appropriate seasonal high or low alarm limits.
Verify with UF project manager the level of graphics needed on a specific project. Floor plan graphics are
minimum requirements. Additional system graphics (AHU’s VAV’s FCU’s) shall be specified for each project
as required by UF PPD and UF Project Manager.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Provide all electrical wiring required for a complete and functional control system, including power
circuit to control panels and field devices in accordance with all applicable local codes and the latest
version of National Electric Code and NFPA when applicable.
B. Sizing of cable, conduit, and raceways to accommodate system with 25% spare copacity.
C. Labeled wiring with unique tag to match I/O device identifier tag (e.g. sensor TE-1 wire shall be
labeled at panel and device as “TE-1”). Communication cable shall be labeled with Loop/Trunk #,
previous and destination device (e.g. L1VAV101/VAV102 would be used to label the loop 1
communication bus between VAV101 and VAV102)
D. Low voltage wiring concealed above accessible ceilings does not require raceway, however, cables
run above accessible ceilings shall be run within a j-hook pathway system spaced no more than 4 ft
apart. Cables run in concealed areas or within un-accessible spaces shall be installed in EMT. Run
pathways and cables parallel and perpendicular to building structure.
Verify with pathway requirements with Owner.
-------------------------------------------------------------------------------------------------------------------------------------------
E. Flexible Metal Conduit shall be used for vibration isolation and shall be limited to 3 feet in length
when terminating to vibrating equipment. Flexible Metal Conduit shall be UL listed.
F. Run direct current instrument conductors separately from alternating current conductors. Where
allowed by NEC wiring classification, AC-DC route crossings shall be at 90 degrees. Install special
sensor to converter cables in accordance with drawings or in compliance with manufacturer's
instructions. Extra precautions shall be taken when pulling and shortening these "vendor furnished"
cables. Any extra length on these cables shall be neatly coiled into minimum 3" diameter coils and
installed into junction box.
H. All control wiring located in mechanical or exposed spaces shall be run in EMT.
Page 42 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
J. Control panels and operator's terminals serving equipment fed by emergency power shall also be
served by emergency power. Locate LOT and its UPS where shown on plans.
Consultant should coordinate with electrical designer for power source for for DDC controller.
-------------------------------------------------------------------------------------------------------------------------------------------
K. Power wiring to control compressors and dryers shall be as indicated on electrical power plans.
Provide field mounted starters to Electrical Contractor for installation and supervise installation.
Consultant should coordinate with electrical designer for power source for both compressors and dryer.
-------------------------------------------------------------------------------------------------------------------------------------------
L. Raceway Identification. All the covers to junction and pull boxes of the BAS raceway system shall
be painted white.
If no electrical specification is included in contract documents and paragraph 1.1 RELATED WORK included
herein is not applicable, Consultant should include appropriate specifications for electrical work in place of the
above paragraph.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Conceal all piping, except for piping in mechanical rooms and other areas where mechanical
system piping is exposed.
B. Install exposed piping and conduit parallel to or at right angles to building structure and support
adequately at uniform intervals. Use only tool-made bends.
C. Polyethylene tubing not exceeding 18" may be used for final connection to instrument or actuator.
D. Install polyethylene tubing with no concealed splices and number code all tubing.
-------------------------------------------------------------------------------------------------------------------------------------------
F. Provide cartridge type desiccant dryers for air lines passing through outside air stream or through
unheated spaces where space temperatures can be below 30°F.
Page 43 of 53
University of Florida 11/09/07
Control System Guide Specification
Specify entire air piping to be hard copper if engineered smoke control system is designed for the project. For
additions to existing engineered smoke control systems, verify with Owner if entire system needs to be hard
copper.
-------------------------------------------------------------------------------------------------------------------------------------------
3. Exposed Spaces:
a. Use hard copper tubing or,.
b. Polyethylene tubing may be used if run in fully enclosed EMT raceway where environment
is within temperature limits of polyethylene tubing.
c. Use PVC coated copper tubing for wet environments.
4. Concealed:
a. Use hard copper, soft copper or polyethylene tubing.
Standard choice.
-------------------------------------------------------------------------------------------------------------------------------------------
5. Concrete Buried:
a. Use hard copper, soft copper or polyethylene tubing in metal or plastic conduit.
This is intended for areas such as greenhouses where tubing has to run through concrete slab.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Provide an appropriate air pressure reducing station connected to the existing piping system and
providing a new refrigerated air dryer assembly for the piping extension, all having the required
system capacity to serve the devices included in the Vendor / Installer’s work.
Consultant should confirm pneumatic requirements with University of Florida Project Manager and UF-PPD.
In many cases, the existing campus pneumatic air system can be extended to accommodate new work. In the
event pneumatic air is not available via the central plant system, the consultant shall include the appropriate
compressor specifications (see below).
-------------------------------------------------------------------------------------------------------------------------------------------
C. Install air dryer assembly where indicated on drawings or suitable location adjacent to air
compressor assembly.
1. Mount air dryer on wall with suitable supports.
2. Pipe unit drain to nearest floor drain.
A. Provide local control panel for each system where more than one control device requires field
mounting (air handling units, miscellaneous control system including pump controls, etc.). Single
devices may be mounted exposed on piping or ductwork. Install local control panel where indicated
on drawings or suitable location adjacent to system served. Do not mount panels on equipment.
Page 44 of 53
University of Florida 11/09/07
Control System Guide Specification
B. Mount panel on wall with suitable brackets or on floor with self-supporting stand.
1. Mount top of panel no higher than 6 feet above floor.
2. Install panels so front cover door can swing full open without interference and maintain a
minimum of 36" clearance.
C. Unless otherwise indicated, mount controllers, adjusting switches, pressure gages, temperature
indicators and other indicating or manually operated devices inside panel with permanent labels
identifying device and controlled device or function.
D. In-line pneumatic gages shall be hard mounted to back panel and shall include permanent labels
identifying end device. Other factory standard labeling methods are acceptable as long as the
device name and function is clearly identified and is permanent. Labels shall correspond to control
drawing tags and identifiers.
A. Provide router as required, to bridge BACnet/IP and the data link used between the controllers
(BACnet ARCNET, BACnet MS/TP).
B. Proprietary networks (networking between buildings and central server) and proprietary protocols
are not acceptable.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Provide all processors, power supplies and communication controllers so that the implementation of
a point only requires the addition of the appropriate point input/output termination module and wiring.
B. Size controller to meet the requirements of this specification and the project point I/O schedule
+15% additional capacity.
Coordinate power requirements with Electrical
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 45 of 53
University of Florida 11/09/07
Control System Guide Specification
A. Furnish power meter as shown on drawings and/or as required to perform control sequence
specified.
-------------------------------------------------------------------------------------------------------------------------------------------
3.11 SERVERS
A. Archive all historical data such as trends, alarm and event histories, and transaction logs on existing
server.
Consultant should confirm server requiements for this project.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Provide, a commercially available laptop PC with Windows operating system, standard control
system engineering tool set, all required interface cables, and at least 256 MB of RAM. LCD backlit
display and a full-featured keyboard. The laptop shall plug directly into all controllers and unitary
controllers and include one standard Ethernet connection. Provide a user-friendly, English
language-prompted interface for quick access to system information, not codes requiring look-up
charts.
A. Furnish control valves as shown on drawings and/or as required to perform control sequence
specified.
C. Control valves furnished by this contractor shall be installed by [Division 15XXX Contractor] under
coordinating control and supervision of this Contractor.
Use this paragraph only if the Vendor / Installer is to size valves. Valve sizing is a function of many variables,
many are not known until coil data is submitted. If Consultant sizes valves, be sure that coil data is fixed, or
that sizing is redone after coil submittals have been approved.
Page 46 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
D. Sizing:
1. Select control valves to meet their intended service without cavitations. Provide cavitation
calculations for modulating globe control valves over 250°F and all modulating butterfly valves
over 60°F.
2. Valve body ratings indicated in Part 2 are minimum required. Valve body, trim and packing
selected shall be designed to withstand maximum pressure and temperature encountered in
the systems.
3. Submit engineering calculations used for sizing modulating control valves. Control valves
serving terminal devices may be sized based on flow ranges for each pump system.
4. Calculations for sizing modulating valves shall be based on actual characteristics of equipment
and system being installed.
a. Valve calculations shall include information such as pump head or available pressure;
branch piping circuit losses including all pipe, fittings, valves, and coils; flow rates; and
pressure losses of other in-line devices.
b. Obtaining adequate system information necessary for sizing valves.
5. Design criteria for sizing modulating valves shall be based on two port, fail open or fail closed,
as shown on plans, equal percentage valves unless otherwise specified.
6. Heating control valves shall be full port ball valve or globe valve and shall be selected for a
minimum of 25% of equipment subcircuit pressure drop, but not more than maximum available
pump head allowing minimum 2 psi drop for balance valve.
7. Size three-way mixing or diverting valves not directly associated with pump sub-circuit, for 3-5
psi pressure drop.
8. Terminal reheat control valves shall be ball type and shall be selected for a minimum of 25% of
equipment subcircuit pressure drop, but not more than maximum available pump head allowing
minimum 2 psi drop for balance valve.
9. Cooling control valves may be full port ball, globe or butterfly type and shall be selected for
minimum of 10% of equipment subcircuit pressure drop, but not more than maximum available
pump head allowing minimum 2 psi drop for balance valve.
10. Select control valves based on pressure drop calculations using Cv values at 100% stroke.
11. Subcircuit is defined as all branch supply and return piping to terminal device, including all
valve, coil, control valves, and balance valve.
Verify all pressure parameters.
-------------------------------------------------------------------------------------------------------------------------------------------
E. Steam Valves
1. Modulating steam control valves shall be straight-through globe type with linear characteristics
for 90% of closing stroke and equal-percentage for final 10%.
2. For steam inlet pressure less than 15 psig, size valves for pressure drop equal to 75 to 80% of
gauge inlet steam pressure.
3. For steam inlet pressure of 15 psig or greater, size valves for pressure drop equal to 50% of
absolute inlet pressure.
A. Furnish control dampers as shown on drawings and/or as required to perform control sequence
specified except those furnished with other equipment.
Page 47 of 53
University of Florida 11/09/07
Control System Guide Specification
C. Control dampers furnished by this Contractor will be installed by [Division 15XXX Contractor] under
coordinating control and supervision of this Contractor.
D. Blank-off plates or transitions required to facilitate dampers will be provided by the [Division 15XXX
Contractor].
Consultant to edit spec references as appropriate. Coordinate control dampers with AHU specification. If
control dampers are to be provided with the AHU then the AHU specification should include this requirement.
-------------------------------------------------------------------------------------------------------------------------------------------
A. Provide actuator for each automatic damper or valve with sufficient capacity to operate damper or
valve under all conditions. Select actuators to provide tight shut off against maximum system
temperatures and pressure encountered.
B. Provide pilot positioners for pneumatic modulating valves and dampers for major equipment such
as air handling unit coils, humidifiers, heat exchangers, converters, major water system
temperature controls, etc.
Consultant shall include valve and damper schedule on drawings and indicate specific valves/dampers
requiring pilot positioners. Pilot positioners are typically needed on control valves exceeding 2 inches and/or
when multiple valves are controlled from one control signal. Pilot positioners could also be needed when large
dampers are used as a modulating device..
-------------------------------------------------------------------------------------------------------------------------------------------
C. Provide pilot positioners for all sequenced devices, and devices which require adjustable operating
speeds.
D. Provide pilot positioners for modulating outside and return air dampers and fan volume control
devices such as fan inlet dampers where used.
E. Provide pilot positioners for modulating valve and damper operators when torque required by
controlled devices exceeds 50% of torque capacity of operator.
F. Pilot positioners are not required for terminal heating/cooling equipment or booster humidifiers.
G. Valve and damper operating speeds shall be selected or adjusted so operators will remain in step
with controller without hunting regardless of load variations.
H. Provide proper linkage and brackets for mounting and attaching actuators to devices. Design
mounting and/or support to provide no more than 5% hysteresis in either direction (actual
movement of valve stem/damper shaft/ideal movement) due to deflection of actuator mounting.
I. Sizing
University of Florida standard is to require the Consultant to size all dampers using this criteria. Damper sizes
should be shown on drawings or scheduled. Consultant should delete the following requirements for the
Vendor / Installer to submit calculations if sizes are provided by consultant.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 48 of 53
University of Florida 11/09/07
Control System Guide Specification
1. Calculations for sizing dampers shall be based on actual characteristics of ductwork system
being installed.
2. Opposed blade dampers shall be sized for minimum of 10% of duct section pressure drop.
Parallel blade dampers shall be sized for minimum of 30% of duct section pressure drop. Duct
section is defined as ductwork containing flow control damper starting with inlet or branch tee
and ending with outlet or branch tee.
3. Calculate actual duct pressure drops for each duct section containing modulating damper using
latest version of ASHRAE Handbook of Fundamentals.
4. If control system fixes pressure drop, use those pressure setpoints. Use duct blank-offs to
provide additional pressure drop as required to obtain linear damper response.
5. Contractor is responsible for obtaining adequate system information necessary for sizing.
6. Contractor to provide dampers as shown on drawings or as scheduled.
Consultant should delete above only if Vendor / Installer is required to submit engineering calculations.
-------------------------------------------------------------------------------------------------------------------------------------------
7. Two position dampers shall be sized as close as possible to duct size, but in no case is damper
size to be less than duct area.
A. General
1. Terminate at terminal blocks inside enclosures unless otherwise specified.
2. Include auxiliary contact for remote status indication of safety devices.
Page 49 of 53
University of Florida 11/09/07
Control System Guide Specification
1. Install low limit controls where indicated on drawings or as specified. Unless otherwise
indicated, install sensing element at downstream side of heating coils.
2. Distribute sensing element across entire area of medium being sensed. Install controls at
accessible location with suitable mounting brackets and element duct collars where required.
3. Serpentine sensing element, starting at the lowest point (6” above coil bottom) of the coil being
protected. Operation of low limit trip shall provide protection to associated coils.
4. Low limit trip activation shall cause all water coils to be overridden to full flow.
D. Relays:
1. Provide control relays where indicated on drawings or as required to accomplish sequences.
2. Provide DIN mounted relays in control panels.
3. Provide RIB type relays for field control devices.
4. Mount relay for easy accessibility.
5. Mount relay for easy visual accessibility.
E. Pressure Switches:
1. Provide pressure switches where indicated on drawings or as required to accomplish
sequences.
2. Coordinate installation of flow switches for proper location and installation.
Consultant to edit spec references as appropriate. Consultant to coordinate installation of pressure switches
with appropriate mechanical piping section if used in large pipe.
-------------------------------------------------------------------------------------------------------------------------------------------
G. Flow Switches:
1. Furnish flow switches as required.
2. Coordinate installation of flow switches for proper location and installation.
Consultant to edit spec references as appropriate. Consultant to coordinate installation of paddle and flow
switches with appropriate mechanical piping section..
-------------------------------------------------------------------------------------------------------------------------------------------
K. Current Switches:
1. Provide current switches where indicated on drawings or as required to accomplish sequences.
Page 50 of 53
University of Florida 11/09/07
Control System Guide Specification
-------------------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------------------------------------------
Page 51 of 53
University of Florida 11/09/07
Control System Guide Specification
E. Room Thermostats
1. Install space thermostats where indicated, as required to perform specified controls, or directed
to meet job site conditions.
2. Mount thermostats at 4 ft above floor unless otherwise indicated.
3. Any room thermostat mounted on exterior walls shall be mounted on thermally insulated sub-
base.
4. Relocate room thermostats if required due to draft, interferences with cabinets, chalkboards,
etc., or improper sensing.
5. Provide thermostats in gymnasium, locker rooms and [XXX] heavy-duty cast and die formed
guard.
6. Provide a conduit from thermostat box to above the ceiling where it shall stub out into an
accessible area parallel with the ceiling.
-------------------------------------------------------------------------------------------------------------------------------------------
Page 52 of 53
University of Florida 11/09/07
Control System Guide Specification
M. Ducted Air System Static Pressure and Differential Pressure (Velocity) Transmitters:
1. Provide transducers/transmitters to convert velocity pressure differential or static duct pressure
relative to sensor location into electronic signal.
2. Mount transducers in control panels.
3. Terminate transducers directly to the controller that is implementing control loop.
END OF SECTION
Page 53 of 53