Electrical and mechanical data
Electrical and mechanical data
LSA 47.2 - 4 Pole
SPECIALLY ADAPTED FOR APPLICATIONS
The LSA 47.2 alternator is designed to be suitable for typical generator applications, such as: stand-by,
prime power, cogeneration, marine, rental, telecommunications, etc.
R 250 Std - - - - - -
R 450 optional Std Std
D 500 - optional optional included included NA
2
LSA 47.2 - 4 Pole
Common data
Insulation class H Excitation system SHUNT (12 wire) A R E P or PMG
Winding pitch 2/3 (N° 6 or N° 6S) A.V.R. model R 250 R 450
Terminals 12 (N° 6) / 6 (N° 6S) Voltage regulation (*) ± 0,5 % ± 0,5 %
Drip proof IP 23 Sustained short-circuit current - 300% (3 IN) : 10s
Altitude " 1000 m Total harmonic TGH / THC (**) at no load < 1,5 % - on load < 2 %
Overspeed 2250 min-1 Waveform : NEMA = TIF (**) < 50
Air flow 0,9 m /s (50Hz) / 1,1 (60Hz)
3 Wave form : I.E.C. = THF(**) <2%
(*) Steady state duty. (**) Total harmonic content line to line, at no load or full rated linear and balanced load.
Y 380V 400V 415V 380V 400V 415V 380V 400V 415V 380V 400V 415V
6 wire
! 220V 230V 240V 220V 230V 240V 220V 230V 240V 220V 230V 240V
47.2 L9* kVA 600 535 630 660
kW 480 428 504 528
kW 344 368 373 396 317 336 346 366 368 392 408 424 376 408 420 436
47.2 S5 kVA 475 510 531 570 441 473 493 518 503 543 566 592 527 562 585 625
kW 380 408 425 456 353 378 394 414 402 434 453 474 422 450 468 500
47.2 M7 kVA 562 610 625 625 523 566 581 590 600 651 669 680 625 668 690 700
kW 450 488 500 500 418 453 465 472 480 521 535 554 500 534 552 560
47.2 M8 kVA 562 610 630 690 523 566 587 632 600 651 672 729 625 671 705 750
kW 450 488 504 552 418 453 470 506 480 521 538 583 500 537 564 600
47.2 L9 kVA 602 661 685 750 556 609 634 675 643 707 734 780 667 728 763 825
kW 482 529 548 600 445 487 507 540 514 566 587 624 534 582 610 660
Y 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V
6 wire
3
LSA 47.2 - 4 Pole
Efficiencies 50 Hz - P.F. : 1 / P.F. : 0,8
LSA 47.2 VS 2 LSA 47.2 M7
96% 95.4 97%
P.F. : 1 96.2 P.F. : 1
95.5 95.3
95 95.1
96 96.2 96.1
95.8
94 95 94.5
93.8 93.3 P.F. : 0,8 94.9 94.3
93.8 94.8
93 94
92.6 93 P.F. : 0,8
93.5
92 93
91.7 92.8
91 92
50 100 150 200 250 300 350 400 450 kVA 100 150 200 250 300 350 400 450 500 550 kVA
4
LSA 47.2 - 4 Pole
Transient voltage variation 400 V - 50 Hz
20 L9 20 M7
6w/12w M8
% Voltage dip
% Voltage dip
L9
15 15 6w/12w
10 10
5 5
0 0
0 100 200 300 400 500 600 700 800 kVA 0 100 200 300 400 500 600 700 800 kVA
kVA at 0,8 power factor kVA at 0,8 power factor
30% 30%
M7 M7
M8 M8
25 25
L9 L9
% Voltage irse
% Voltage irse
20 6w/12w 20 6w/12w
15 15
10 10
5 5
0 0
0 100 200 300 400 500 600 700 800 kVA 0 100 200 300 400 500 600 700 800 kVA
kVA at 0,8 power factor kVA at 0,8 power factor
% Voltage dip
20 20
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 kVA 0 200 400 600 800 1000 1200 1400kVA
kVA Locked rotor kVA Locked rotor
1) For a star
ting P.F. differing from 0,6,the starting kVA must be multiplied by (Sine Ø /0,8)
2) For voltages other than 400V(Y
) , 230V(D A must be multiplied by (400/U)2 or (230/U)2.
elta) at 50 Hz, then kV
5
LSA 47.2 - 4 Pole
Efficiencies 60 Hz - P.F. :1 / P.F. : 0,8
LSA 47.2 VS 2 LSA 47.2 M7
96% 95.3 P. F. : 1 97%
96 P. F. : 1
95 96
95.2 95.1 95.9 96
94.4
94 93.4 P. F. : 0,8
95 94.5
95.2
93.7 94.7
93 94 94.4
93.3 93.1 94.3
P. F. : 0,8
92 93
91 92
91.1 92.3
90.4 91.7
90 91
100 200 300 400 500 kVA 100 200 300 400 500 600 700 kVA
6
LSA 47.2 - 4 Pole
Transient voltage variation - 480 V - 60 Hz
% Voltage dip
6w/12w
% Voltage dip
L9
15 15 6w/12w
10 10
5 5
0 0
0 200 400 600 800 1000 kVA 0 200 400 600 800 1000kVA
kVA at 0,8 power factor kVA at 0,8 power factor
L9 L9
% Voltage irse
% Voltage irse
20 6w /12w 20 6w/12w
15 15
10 10
5 5
0 0
0 200 400 600 800 1000kVA 0 200 400 600 800 1000kVA
kVA at 0,8 power factor kVA at 0,8 power factor
30 L9 30 L9
6w/12w 6w/12w
% voltage dip
25 25
% voltage dip
20 20
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 1400 kVA 0 200 600 1000 1400 1800 kVA
Locked rotor Locked rotor
7
LSA 47.2 - 4 Pole
3 phase short-circuit curves at no load and rated speed (star connection Y)
10000
Symmetrical
Asymmetrical
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
AREP or PMG
LSA 47.2 VS3
1000
Current (A)
Symmetrical
Asymmetrical
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
1000
Current (A)
Symmetrical
Asymmetrical
100
SHUNT
10
1 10 100 1000 10000 time (ms)
8
LSA 47.2 - 4 Pole
3 phase short-circuit curves at no load and rated speed (star connection Y)
10000
1000
Symmetrical
Asymmetrical
100
SHUNT
10 time (ms)
1 10 100 1000 10000
10000
1000
Current (A)
Symmetrical
Asymmetrical
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
Symmetrical
Asymmetrical
100
SHUNT
10
time (ms)
1 10 100 1000 10000
9
LSA 47.2 - 4 Pole
Single bearing dimensions
L Y DIA, Qt
y X Eq
. Sp. on Ø U AVRaccess
LB 660
AH Xg 610 49 ß
14,5 250 17
CF
Cable
PMG Optional
512
- 0,050
Ø BX - 0,100
Ø N - 0,127
867
Ø 616
Ø 235
0
ØP
2 x Ø13
355 - 1
0
Ø 206
12
89,3
62
AIR OUTLET AIR INLET
68 50 610
28
Ø 115
Ø 110
Ø 120
Ø 115
Ø 75
Ø 75
Lr
Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
Flex plate S.A.E. 11 1/2 Flex plate S.A.E. 14 Flex plate S.A.E. 18
TYPE Xr Lr M J Xr Lr M J Xr Lr M J
LSA 47.2 VS2 432,5 1029 387 5,99 418,3 1029 387 6,12 408,5 1029 387 6,38
LSA 47.2 VS3 439.5 1029 400 6,19 425.5 1029 400 6.32 415.5 1029 442 6,59
LSA 47.2 S5 470 1089 442 6,90 456 1089 442 7,03 446 1089 442 7,29
LSA 47.2 M7 510 1189 495 7,61 496 1189 495 7,74 486 1189 495 8
LSA 47.2 M8 521 1189 514 8,01 507 1189 514 8,14 497 1189 514 8,40
LSA 47.2 L9 542 1209 547 8,52 528 1209 547 8,65 518 1209 547 8,91
10
LSA 47.2 - 4 Pole
Two bearing dimensions
L AVRaccess
LB 740
130 Xg 560 49 15
355 17
1 hole M20x42
Cable
PMG option
512
Ø 511,175 - 0,127
14
867
0
Ø 616
Ø 85 m6
Ø 713
Ø 552
Ø 235
2 x Ø13
355 - 1
0
22
472 90
12
89,3
62
AIR OUTLET 68 AIR INLET
50 610
205 130 130 130 90 710
28
130
Ø 106
Ø 115
Ø 110
Ø 120
Ø 115
Ø 85
Ø 90
Ø 75
Lr
Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
TYPE Xr Lr M J (kg)
LSA 47.2 VS2 396,4 1139 368,5 5,79
LSA 47.2 VS3 403 1139 381 5,99
LSA 47.2 S5 433,2 1199 424 6,70
LSA 47.2 M7 473 1299 476,2 7,41
LSA 47.2 M8 483,5 1299 494,9 7,81
LSA 47.2 L9 504,5 1319 528 8,32