Jurop Pump PN Series
Jurop Pump PN Series
Jurop Pump PN Series
,167$//$7,2186($1'
0$,17(1$1&(0$18$/
PN Series
5HY
Index
1. General advises
1.1 Introduction
This booklet contains the necessary instructions for a correct It is recommended to:
installation, running test, normal use and maintenance of the pump
as well as practical suggestions for safe operating. - read and apply closely the instructions before running the pump.
The knowledge of the following will give trouble free operation for - keep the booklet at hand and have it known to all operators.
a long time.
To avoid mistakes when ordering the spare parts make sure Example:
you indicate:
10 -- 0.04
0.02
111 B
5 + 0.18
34.87 - 0.05
0
H
78
DIN 96 11 A
1"3/8
123
M10
L
C
I
ø77
D E M
G F N
A O
Dimensions in mm.
Model A B C D E F G H I L M N O
PN 23D 466 276 98 16 60 92 226 60 135 408 170 195 215
PN 33D 546 306 98 16 60 160 226 60 135 415 170 195 215
PN 45D 426 206 98 16 50 140 131 60/76/80 150 508 240 270 275
PN 58D 486 226 98 16 80 190 136 60/76/80 175 538 240 270 275
PN 84D 586 276 98 16 80 190 186 60/76/80 150 518 240 270 275
PN 106D 676 321 98 16 70 290 181 60/76/80 175 538 250 285 290
L
Asae 1" 3 8
Din 9611 A
I
D E M
G F N
A O
Dimensions in mm.
Model A B C D E F G H I L M N O
PN 23M 475 280 87 16 60 92 235 60 58 408 170 195 215
PN 33M 555 320 87 16 60 160 235 60 58 415 170 195 215
PN 45M 535 310 87 16 50 140 240 60/76/80 50 508 240 270 275
PN 58M 595 340 87 16 80 190 245 60/76/80 72 538 240 270 275
PN 84M 695 390 87 16 80 190 295 60/76/80 50 518 240 270 275
PN 106M 785 435 87 16 70 290 290 60/76/80 72 538 250 285 290
H
B
G2"
C
L
Din 9611 A
Asae 1" 3 8
I
D E M
G F N
A O
Dimensions in mm.
Mod. A B C D E F G H I L M N O
PN 45FL 535 310 87 16 50 140 240 145 50 315 240 270 275
PN 58FL 595 340 87 16 80 190 245 145 72 345 240 270 275
PN 84FL 695 390 87 16 80 190 295 145 50 325 240 270 275
PN 106FL 785 435 87 16 70 290 290 145 72 345 250 285 290
SHELL Morlina Oil 46 Morlina Oil 150 SHELL Omala oil 220
- Ordinary and extraordinary maintenance has to be done while - Be aware that during operation the pump’s body can reach
the unit is stopped and the drive disconnected. temperature of over 60° centigrade.
Possibility of burnings if this warning is missacted.
- Interventions on pneumatic plants have to be done after
disconnecting pressure/vacuum from the same.
- Vacuum pumps of the PN-series used for the suction of liquids non-continuous duty; suggested uninterrupted working-time:
are foreseen for a max pressure of + 1,5 bar (2,5 for “FL” model) about 15 minutes (free air).
and a max vacuum rate of 92 %. Overheating of the pump will cause serious damages of the
As cooling is given by atmospheric air, pumps are foreseen for same and/or blocking of the rotor.
4. Installation
4.1 Checking at arrival
- upon receipt check that the pump and related accessories are - Check that the rotor/shaft is not blocked.
not damaged.
- The pump must be installed so that it is easely accessible for - When using the belts and pulley, the pulley can be mounted
inspection and maintenance. directly on the rotor shaft.
Fig. 1
16 - 20 mm
15°
V-belts must be
exactly in line
Flange must be
perfectly parallel
4.3 Layout of vacuum line
Fig. 2 Fig. 3
6 6
1 2 1 2
3 3
MIXER
6
6
5 5
4 4
The application of a safety relief valve and a vacuum relief valve on the tank or along the suction line must be foreseen.
5. Starting-up instructions
5.1 Oil level checking
- Before starting-up the pump, check by the oil dip-stick the level
of the oil (fig. 4). If refill is needed only the recommended oils Fig. 4
must be used (see par. 2).
Also the oil level in the gear box must be checked and it must
reach the oil level check-nut.
MAX
MIN
- When the pump is running, check the correct flow of the oil
through the sight glasses of the drip oilers (oil drops must flow adjusting pin on the drip oiler counterclockwise and will
regulary). decrease by turning it clockwise).
In case of oil djustement, the flow will increase by turning the For oil consumption see paragraph 2.
5.3 Vacuum / Pressure changeover valve As the pump can be connected to the vacuum tank
with both the front (drive side) connection or the
- Rotating the handle of the 4 way valve (pos. 1÷2 - See following rear (oil tank side) connection in order to avoid
figure) the pump changes over from vacuum to pressure (or mistakes see the following table "Vacuum-Pressure"
viceversa).
- JUROP pumps are normally assembled to be connected to the - Left hand drive means counterclockwise rotation and Right hand
tank by the front connection (see fig. 2-3 page 8). drive means clockwise rotation, looking at the pump from the
shaft side.
In case the pump is connected to the tank with the Be aware not to place the handle in neutral position
rear connection (oil tank side) the functions "Vacuum (half way between the two end positions)otherwise
- Pressure" will be reversed. the pump will be by-passed (actually runs idle)
9
6. Maintenance
6.1 Ordinary maintenance
a) Re-fill periodically the lubrication oil tank. d) Check that the drive protections are properly fixed.
b) Change at least once a year the oil in the reduction-box and/or e) On direct-drive models grease the front ball-bearing (see pos.
gear-box (see chart at point 2). 1 fig. 6-7-8).
Changing of the sliding-vanes: c. Replace all the gaskets and seals (ask for the suitable "Gasket
a. Remove the front flange as shown in fig. 6-7 and 8. Kit").
b. Lubricate the new vanes and insert them after removal of the old
ones.
DISASSEMBLY OF PUMPS
1
1
6.3 Trouble-shooting
Troubles