General Specifications: EJX610A and EJX630A Absolute and Gauge Pressure Transmitter
General Specifications: EJX610A and EJX630A Absolute and Gauge Pressure Transmitter
General Specifications: EJX610A and EJX630A Absolute and Gauge Pressure Transmitter
STANDARD SPECIFICATIONS
Refer to GS 01C25T02-01EN for Fieldbus
communication type marked with “◊.”
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 3
Advanced Diagnostics (optional) “◊” Minimum Pressure Limit
Applicable for Output signal code E and F. See graph below
• Impulse line blockage detection
The impulse line condition can be calculated and 100(750)
detected by extracting the fluctuation component
from the static pressure signal.
• Heat trace monitoring
The change of the process connection temperature
calculated by using the two temperature sensors 10(75)
built in the EJX enables to detect the heat trace
breakage or the abnormal temperature due to the
failure. 2.7(20)
Signal Characterizer (Output signal code D and E) Working
User-configurable 10-segment signal characterizer pressure Applicable range
kPa abs 1(7.5)
for 4 to 20 mA output. (mmHg abs)
Status Output (optional, output signal code D
and E)
One transistor contact output (sink type) to output 0.13(1)
the status of user configurable high/low alarm for 0.1(0.75)
pressure.
Rating: 10.5 to 30 V DC, 120 mA DC max.
Note: A check meter cannot be connected when status
output option (/AL) is specified.
Refer to ‘Wiring Example for Analog Output and 0.013(0.1)
0.01(0.075) -40 0 40 80 120 (248)
Status Output.’
(-40) (32) (104) (176) 85
SIL Certification
(185)
EJX series transmitters except Fieldbus Process temperature °C (°F)
communication type are certified by TÜV in F01E.ai
compliance with the following standards;
IEC 61508: 2000; Part1 to Part 7 Figure 1-1. Working Pressure and Process
Functional Safety of Electrical/electronic/ Temperature [For EJX610A]
programmable electronic related systems; SIL 2
capability for single transmitter use, SIL 3 capability
for dual transmitter use. 100(14.5) Atmospheric
pressure
□ NORMAL OPERATING CONDITION Working
(Selected features may affect limits.) pressure
kPa abs
Ambient Temperature Limits (psia)
−40 to 85°C (−40 to 185°F)
Applicable range
−30 to 80°C (−22 to 176°F) with LCD display
10(1.4)
Process Temperature Limits
−40 to 120°C (−40 to 248°F)
Ambient Humidity Limits
0 to 100% RH 2.7(0.38)
Maximum Over Pressure
Values are in absolute pressure for EJX610A. 1(0.14)
-40 0 40 80 120
Capsule Pressure (-40) (32) (104) (176) (248)
A 4 MPa (580 psi)
Process temperature °C (°F)
B 16 MPa (2300 psi)
F02E.ai
C 25 MPa (3600 psi)
D 105 MPa (15200 psi) Figure 1-2. Working Pressure and Process
Temperature [For EJX630A]
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits
Values are in absolute pressure for EJX610A.
Capsule Pressure
A 200 kPa (29 psi)
B 2 MPa (290 psi)
C 10 MPa (1450 psi)
D 70 MPa (10150 psi)
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 4
Supply & Load Requirements □ PHYSICAL SPECIFICATIONS
(Output signal code D and E. Optional features
or approval codes may affect electrical Wetted Parts Materials
requirements.) Diaphragm, Process Connector
With 24 V DC supply, up to a 550Ω load can be Refer to “MODEL AND SUFFIX CODES.”
used. See graph below. Non-wetted Parts Materials
Housing
Low copper cast aluminum alloy with polyurethane,
mint-green paint (Munsell 5.6BG 3.3/2.9 or its
600 equivalent), or ASTM CF-8M Stainless Steel
R=
E-10.5 Degrees of Protection
External 0.0244 Digital IP66/IP67, NEMA4X
load Communication
resistance
Pipe
range
Polypropylene
BRAIN and HART
Cover O-rings
250
Buna-N, fluoro-rubber (optional)
Name plate and tag
R (Ω) 316 SST
Fill Fluid
Silicone, Fluorinated oil (optional)
10.5 16.6 25.2 42
Weight
Power supply voltage E (V DC)
F03E.ai Capsule A, B and C: 1.2 kg (2.6 lb)*
Capsule D: 1.4 kg (3.1 lb)*
Figure 2. Relationship Between Power Supply *: Without integral indicator and mounting bracket.
Voltage and External Load Resistance Add 1.5 kg (3.3 lb) for Amplifier housing code 2.
Supply Voltage “◊” Connections
10.5 to 42 V DC for general use and flameproof type. Refer to “MODEL AND SUFFIX CODES.”
10.5 to 32 V DC for lightning protector
(option code A). < Related Instruments>
10.5 to 30 V DC for intrinsically safe, type n, non- Power Distributor: Refer to GS 01B04T01-02E or
incendive or non-sparking type. GS 01B04T02-02E
Minimum voltage limited at 16.6 V DC for digital BRAIN TERMINAL: Refer to GS 01C00A11-00E
communications, BRAIN and HART
Load (Output signal code D and E) < Reference >
0 to 1290Ω for operation 1. Hastelloy; Trademark of Haynes International Inc.
250 to 600Ω for digital communication 2. HART; Trademark of the HART Communication
Communication Requirements “◊” Foundation.
(Approval codes may affect electrical requirements.) 3. FOUNDATION Fieldbus; Tradmark of Fieldbus
Foundation.
BRAIN
Other company names and product names used in
Communication Distance this material are registered trademarks or trademarks
Up to 2 km (1.25 miles) when using CEV of their respective owners.
polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on type of
cable used.
Load Capacitance
0.22 µF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
EMC Conformity Standards ,
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
European Pressure Equipment Directive 97/23/EC
Sound Engineering Practice (for all capsules)
With option code /PE3 (for D capsule)
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 5
MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJX610A ............................... Absolute pressure transmitter
EJX630A ............................... Gauge pressure transmitter
Output signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication (HART protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C25T02-01EN)
Measurement A . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 to 200 kPa (0.3 to 29 psi)
span (capsule) B . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.01 to 2 MPa (1.5 to 290 psi)
C . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.05 to 10 MPa (7.3 to 1450 psi)
D . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.35 to 70 MPa (50.8 to 10150 psi)
Wetted parts Process connection Diaphragm
material *4 S . . . . . . . . . . . . . . . . . . . . . . . . . 316L SST# Hastelloy C-276 *1#
H . . . . . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 *1# Hastelloy C-276 *1#
Process connections 4 . . . . . . . . . . . . . . . . . . . . . . 1/2 NPT female
7 . . . . . . . . . . . . . . . . . . . . . . 1/2 NPT male
8 . . . . . . . . . . . . . . . . . . . . . . G1/2 DIN 16 288 male *2
9 . . . . . . . . . . . . . . . . . . . . . . M20×1.5 DIN 16 288 male *2
─ N . . . . . . . . . . . . . . . . . . . Always N
─ -0 . . . . . . . . . . . . . . . . . Always 0
Amplifier housing ► 1 . . . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties *7
2 . . . . . . . . . . . . . . ASTM CF-8M stainless steel *5
Electrical connection 0 . . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . . G1/2 female, two electrical connections with a blind plug*6
7 . . . . . . . . . . . 1/2 NPT female, two electrical connections with a blind plug*6
9 . . . . . . . . . . . M20 female, two electrical connections with a blind plug*6
A . . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . . Digital indicator
E . . . . . . . . Digital indicator with the range setting switch *3
► N . . . . . . . . (None)
Mounting bracket L . . . . . . 316 SST 2-inch pipe mounting
► N . . . . . . None
Optional Codes / Optional specification
The “►” marks indicates the most typical selection for each specification. Example: EJX630A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*5: Not applicable for electrical connection code 0, 5, 7 or 9.
*6: Material of a blind plug is aluminum alloy or 304 SST.
*7: Not applicable for electrical connection code 0, 5, 7, 9 and A. Content rate of copper in the material is 0.03% or less and
content rate of iron is 0.15% or less.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 6
OPTIONAL SPECIFICATIONS (For Explosion Protected type) “◊”
Item Description Code
Factory Mutual FM Explosionproof Approval *1
(FM) Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1,
FF1
Groups E, F and G, in Hazardous locations, indoors and outdoors (NEMA 4X)
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Temperature class: T6, Amb. Temp.: –40 to 60°C (–40 to 140°F) *3
FM Intrinsically safe Approval *1*2
Applicable Standard: FM3600, FM3610, FM3611, FM3810
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
FS1
Groups F & G, and Class III, Division 1, Class I, Zone 2, Group IIC, in Hazardous Locations
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –60 to 60°C (–75 to 140°F) *3
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
Combined FF1 and FS1 *1*2 FU1
ATEX ATEX Flameproof Approval *1
Applicable Standard: EN 60079-0, EN 60079-1, EN 60079-31
Certificate: KEMA 07ATEX0109 X
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db IP6X
Degree of protection: IP66 and IP67 KF22
Amb. Temp. (Tamb) for gas-proof :
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Max. process Temp. for gas-proof (Tp): T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: 85°C) *3
ATEX Intrinsically safe Approval *1*2
Applicable Standard: EN 60079-0, EN 60079-11, EN 60079-26, EN 61241-11
Certificate: DEKRA 11ATEX0228 X
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Degree of protection: IP66 and IP67
KS21
Amb. Temp. (Tamb) for EPL Ga: –50 to 60°C (–58 to 140°F)
Maximum Process Temp. (Tp) for EPL Ga:120°C
Electrical data: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 μH
Amb. Temp. for EPL Db: –30 to 60°C *3
Max. surface Temp. for EPL Db: T85°C (Tp: 80°C), T100°C (Tp: 100°C), T120°C (Tp: 120°C)
Combined KF22, KS21 and Type n *1*2
Type n
Applicable Standard: EN 60079-0, EN 60079-15 KU22
II 3G Ex nL IIC T4 Gc, Amb. Temp.: –30 to 60°C (–22 to 140°F) *3
Ui=30 V DC, Ci=10 nF, Li=0 mH
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 7
Item Description Code
Canadian CSA Explosionproof Approval *1
Standards Certificate: 2014354
Association Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
(CSA) C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1-04
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: TYPE 4X, Temp. Code: T6...T4
Ex d IIC T6...T4 Enclosure: IP66 and IP67 CF1
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *3
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1*2
Certificate: 1606623
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.154,
C22.2 No.213, C22.2 No.1010.1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups E, F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *3
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0
[Nonincendive] Vmax=30V, Ci=10nF, Li=0
CS1
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-11, CAN/CSA E60079-15,
IEC 60529:2001-02
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66 and IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0
[Ex nL] Ui=30V, Ci=10nF, Li=0
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*2 CU1
IECEx IECEx Flameproof Approval *1
Scheme Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66 and IP67 SF2
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *3
IECEx Intrinsically safe, type n and Flameproof Approval *1*2
Intrinsically safe and type n
Applicable Standard: IEC 60079-0:2000, IEC 60079-11:1999, IEC 60079-15:2001
Certificate: IECEx CSA 05.0005
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66 and IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0
[Ex nL] Ui=30V,Ci=10nF, Li=0 SU2
Flameproof
Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66 and IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *3
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
*2: Not applicable for option code /AL.
*3: Lower limit of ambient temperature is –15°C (5°F) when /HE is specified.
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATIONS
Item Description Code
High Accuracy type *19 Reference accuracy: ±0.025% of Span HAC
Painting Color change Amplifier cover only*13 P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*1*13 X2
316 SST exterior parts 316 SST zero-adjustment screw and setscrews*15 HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically safe type,
9 to 32 V DC for Fieldbus communication type.)
A
Allowable current: Max. 6000 A ( 1×40 µs ), Repeating 1000 A ( 1×40 µs ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output*2 Transistor output (sink type)
AL
Rating: 10.5 to 30 V DC, 120 mA DC (max) Low level: 0 to 2 V DC
Oil-prohibited use Degrease cleansing treatment K1
Degrease cleansing treatment with fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C (−4 to 176°F)
Capsule fill fluid Flourinated oil filled in capsule
K3
Operating temperature −20 to 80°C (−4 to 176°F)
Calibration units*3 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Output limits and failure Failure alarm down-scale : Output status at CPU failure and hardware error is −5%, 3.2mA DC
C1
operation*4 or less.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant C2
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
3.8 mA to 20.5 mA Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Gold-plated diaphragm *18 Surface of isolating diaphragms are gold plated, effective for hydrogen permeation. A1
Wired tag plate 316 SST tag plate wired onto transmitter N4
Data configuration at factory*5 Software damping, Descriptor,
Data configuration for HART communication type CA
Message
Data configuration for BRAIN communication type Software damping CB
Advanced diagnostics*16 Multi-sensing process monitoring
• Impulse line blockage detection *17 DG6
• Heat trace monitoring
European Pressure PED 97/23/EC
Equipment Directive*14 Category: III, Module: H, Type of Equipment: Pressure Accessory-Vessel, PE3
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Material certificate*6 Process Connector M15
Pressure test/ Test Pressure: 200 kPa (29 psi) *7 T05
Leak test certificate*12 Test Pressure: 2 MPa (290 psi) *8 Nitrogen(N2) Gas or Water*11 T06
Test Pressure: 10 MPa (1450 psi) *9 Retention time: one minute T07
Test Pressure: 70 MPa (10150 psi) *10 T15
*1: Not applicable with color change option.
*2: Check/External indicator terminals cannot be used when this option code is specified. Not applicable for output signal code F.
*3: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*4: Applicable for output signal codes D and E. The hardware error indicates faulty amplifier or capsule.
*5: Also see ‘Ordering Information’.
*6: Material traceability certification, per EN 10204 3.1 B.
*7: Applicable for capsule code A.
*8: Applicable for capsule code B.
*9: Applicable for capsule code C.
*10: Applicable for capsule code D.
*11: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*12: The unit on the certificate is always kPa/MPa regardless of selection of option code D1, D3 and D4.
*13: Not applicable for amplifier housing code 2 and 3.
*14: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
*15: 316 or 316L SST. The specification is included in amplifier code 2.
*16: Applicable only for output signal code -E.
*17: The change of pressure fluctuation is monitored and then detects the impulse line blockage. See TI 01C25A31-01E for
detailed technical information required for using this function.
*18: Applicable for wetted parts material code S.
*19: Refer to “PERFORMANCE SPECIFICATIONS”. Applicable only for EJX630A.
Not applicable for the combination of measurement span code A and wetted parts material code H.
Not applicable for option code K2, K3 or A1.
When specified range value includes minus value for A capsule, the accuracy shall be the standard accuracy even if high
accuracy option (/HAC) is specified.
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 9
DIMENSIONS
Unit: mm (approx.inch)
Model EJX610A and EJX630A
95(3.74) 188(7.40)
60(2.36)*2 Integral indicator
(optional) Zero 110(4.33)
Extenal indicator adjustment 12 39
Conduit connection Conduit connection
(0.47) (1.54)
(optional)
Shrouding bolt
ø78(3.07)
(for flame-proof type)
(2.76)
ø70
126(4.96)
54
110(4.33)
159(6.26)
(2.13)
(6.50)
6
165
(0.24)
Ground terminal
2-inch pipe
Mounting bracket 12*3 (O.D. 60.5 mm) 129(5.08)
(optional) (0.47)
(6.77)
172
ø6
5(0.20)
(0.23)
F04E.ai
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 10
● Wiring Example for Analog Output and Status Output
Connection Description
Analog output EJX electrical terminal
Distributor
+ + 24V DC
SUPPLY
– 250Ω
CHECK + –
– – 250Ω
If shield cable is not
used, communication ALARM +
is not possible.
Magnetic
External power supply valve
30V DC, 120mA max
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
<<Contents>> <<Index>> 11
< Ordering Information > “◊” < Factory Setting > “◊”
Specify the following when ordering
Tag number As specified in order
1. Model, suffix codes, and option codes
2. Calibration range and units Software
‘2.00 sec’ or as specified in order
1) Calibration range can be specified with range damping *1
value specifications up to 5 digits (excluding any Calibration range
As specified in order
decimal point) for low or high range limits within lower range value
the range of -32000 to 32000. When reverse Calibration range
range is designated, specify Lower Range upper range As specified in order
Value (LRV) as greater than Upper Range Value value
(URV). When specified range value includes [EJX630A]
minus value for A capsule, the accuracy shall Selected from mmH2O, mmH2O(68°F),
mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
be the standard accuracy even if high accuracy
kPa, MPa, mbar, bar, gf/cm2, kgf/cm2,
option (/HAC) is specified. inH2O, inH2O(68°F), inHg, ftH2O,
2) Specify only one unit from the table, ‘Factory ftH2O(68°F) or psi. (Only one unit can be
Settings’ when shipped.’ specified)
Calibration range
3. Display scale and units (for transmitters equipped units
with integral indicator only) [EJX610A]
Torr, Pa abs, hPa abs*2, kPa abs,
Specify either 0 to 100 % or engineering unit scale
MPa abs, mbar abs, bar abs, kgf/cm2 abs,
and ‘Range and Unit’ for engineering units scale: mmH2O abs, mmH2O abs(68°F),
Scale range can be specified with range limit mmHg abs, inH2O abs, inH2O abs(68°F),
specifications up to 5 digits (excluding any decimal inHg abs, ftH2O abs, ftH2O abs(68°F),
point) for low or high range limits within the range psia, atm.
of -32000 to 32000. The unit display consists of Designated value specified in order.
6-digit, therefore, if the specified unit is longer than Display setting
(%, or user scaled value.)
7 characters excluding ‘/’, the first 6 characters will
be displayed on the unit display. *1: To specify these items at factroy, /CA or /CB
4. Tag Number (if required) option is required.
*2: Not available for HART protocol type.
For BRAIN communication type, specify upto 16
letters. The specified letters will be written in the
amplifier memory and engraved on the tag plate. < Material Cross Reference >
For HART communication type, specify software
ASTM JIS
tag (up to 8 letters) to be written on the amplifier
memory and Tag number(up to 16 letters) to be grade 316 SUS316
engraved on the tag plate seperately. grade 316L SUS316L
5. Other factory configurations (if required) grade 304 SUS304
Specifying option code CA or CB will allow further
configuration at factory. Following are configurable
items and setting range.
[/CA : For HART communication type]
1) Descriptor (up to 16 characters)
2) Message (up to 30 characters)
3) Software damping in second (0.00 to 100.00)
[/CB : For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 01C25F05-01EN Apr. 16, 2012-00
Subject to change without notice.