EJX530A
EJX530A
EJX530A
STANDARD SPECIFICATIONS
Refer to GS 01C25T02-01E for Fieldbus communica-
tion type marked with “.”
Ambient Temperature Effects per 28˚C (50˚F)
SPAN AND RANGE LIMITS Change
(For EJX510A, values are in absolute and lower ⫾(0.15% of Span + 0.15% of URL)
range limits are 0.) Stability (All normal operating condition)
Measurement ⫾0.1% of URL per 1 year
Span/Range MPa psi (/D1) bar (/D3) kgf/cm2 (/D4)
Power Supply Effects
Span 8 to 200 kPa 1.16 to 29 0.08 to 2 0.08 to 2 ⫾0.005% per Volt (from 21.6 to 32 V DC, 350 ⍀)
A
Range –100 to 200 kPa –14.5 to 29 –1 to 2 –1 to 2 Vibration Effects
Span 0.04 to 2 5.8 to 290 0.4 to 20 0.4 to 20 Amplifier housing code 1:
B
Range –0.1 to 2 –14.5 to 290 –1 to 20 –1 to 20 Less than 0.1% of URL when tested per the require-
Span 0.2 to 10 29 to 1450 2 to 100 2 to 100 ments of IEC60770-1 field or pipeline with high
C vibration level (10-60 Hz, 0.21 mm peak to peak
Range –0.1 to 10 –14.5 to 1450 –1 to 100 –1 to 100
Span 1 to 50 145 to 7200 10 to 500 10 to 500 displacement/60-2000 Hz 3 g)
D Amplifier housing code 2:
Range –0.1 to 50 –14.5 to 7200 –1 to 500 –1 to 500
T01E.EPS
Less than ±0.1% of URL when tested per the
requirements of IEC60770-1 field with general
PERFORMANCE SPECIFICATIONS application or pipeline with low vibration level (10-60
Zero-based calibrated span, linear output, wetted Hz 0.15mm peak to peak displacement /60-500 Hz
parts material code ‘S’ and silicone oil, unless 2g)
otherwise mentioned. Mounting Position Effects
For Fieldbus communication type, use calibrated Rotation in diaphragm plane has no effect. Tilting up
range instead of span in the following specifications. to 90 degree will cause zero shift up to 0.21 kPa
Specification Conformance (0.84 inH2O) which can be corrected by the zero
EJX series ensures specification conformance to at adjustment.
least ⫾3. Response Time (All capsules) “”
Reference Accuracy of Calibrated Span 90 msec
(includes the effects of terminal-based linearity, When software damping is set to zero and including
hysteresis, and repeatability) dead time of 45 msec (nominal)
Measurement span A B C D
Reference Span ⭌ X ⫾0.1% of Span
accuracy Span ⬍ X ⫾(0.01+0.009 URL/Span) % of Span
20 kPa 0.2 MPa 1 MPa 5 MPa
X
(2.9 psi) (29 psi) (145 psi) (720 psi)
URL 200 kPa 2 MPa 10 MPa 50 MPa
(Upper range limit) (29 psi) (290 psi) (1450 psi) (7200 psi)
T02E.EPS
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Aug. 31, 2005-00
<<Contents>> <<Index>> 3
Minimum Pressure Limit
See graph below
100(750)
600
E-10.5
R=
0.0244 Digital
External Communication
load range
10(75) BRAIN and HART
resistance
250
2.7(20)
Working R (⍀)
pressure Applicable range
kPa abs 1(7.5)
(mmHg abs)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Aug. 31, 2005-00
<<Contents>> <<Index>> 4
HART < Related Instruments>
Communication Distance Power Distributor: Refer to GS 01B04T01-02E or
Up to 1.5 km (1 mile) when using multiple twisted pair GS 01B04T02-02E
cables. Communication distance varies depending on BRAIN TERMINAL: Refer to GS 01C00A11-00E
type of cable used.
< Reference >
Use the following formula to determine cable length 1. Hastelloy; Trademark of Haynes International Inc.
for specific applications: 2. HART; Trademark of the HART Communication
Foundation.
65 ⫻ 106 (Cf + 10,000) 3. FOUNDATION Fieldbus; Tradmark of Fieldbus
L= -
(R ⫻ C) C Foundation.
Other company names and product names used in this
Where: material are registered trademarks or trademarks of
L = length in meters or feet their respective owners.
R = resistance in ⍀ (including barrier resistance)
C = cable capacitance in pF/m or pF/ft
Cf = maximum shunt capacitance of receiving devices
in pF/m or pF/ft
EMC Conformity Standards ,
EN 61326, AS/NZS CISPR11
European Pressure Equipment Directive 97/23/EC
Sound Engineering Practice (for all capsules)
PHYSICAL SPECIFICATIONS
Wetted Parts Materials
Diaphragm, Process Connector
Refer to “MODEL AND SUFFIX CODE.”
Non-wetted Parts Materials
Housing
Low copper cast aluminum alloy with polyurethane,
mint-green paint (Munsell 5.6BG 3.3/2.9 or its
equivalent) or ASTM CF-8M Stainless Steel
Degrees of Protection
IP67, NEMA4X, JIS C0920
Pipe
Polypropylene
Cover O-rings
Buna-N
Name plate and tag
304 SST
Fill Fluid
Silicone, fluorinated oil (option)
Weight
Capsule A, B and C: 1.1 kg (2.4 lb)*
Capsule D: 1.3 kg (2.9 lb)*
*: Without integral indicator and mounting bracket.
Add 1.5 kg (3.3lb) for Amplifier housing code 2.
Connections
Refer to “MODEL AND SUFFIX CODE.”
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Aug. 31, 2005-00
<<Contents>> <<Index>> 5
MODEL AND SUFFIX CODES
# The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use
of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for
details.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Feb. 10, 2006-00
<<Contents>> <<Index>> 6
OPTIONAL SPECIFICATIONS (For Explosion Protected type) “”
Item Description Code
FM Explosionproof Approval *1
Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1, FF1
Groups E, F and G, in Hazardous locations, indoors and outdoors (NEMA 4X)
Temperature class: T6, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F)
FM Intrinsically safe Approval *1*2
Factory Applicable Standard: FM3600, FM3610, FM3611, FM3810
Mutual Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
(FM) Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2, FS1
Groups F & G, and Class III, Division 1, Class I, Zone 2, Group IIC, in Hazardous Locations
Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: –60 to 60⬚C (–75 to 140⬚F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0 H
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0 H
Combined FF1 and FS1 *1*2 FU1
CENELEC ATEX (KEMA) Flameproof Approval *1
Applicable Standard: EN 50014, EN 50018, EN 50281-1-1
Certificate: KEMA 03ATEX2570
II 2G,1D EExd IIC T4, T5, T6 Type of protection : IP66 and IP67
Amb. Temp. (Tamb) for gas-proof : KF2
T4 ; –50 to 75°C (–58 to 167°F), T5; –50 to 80⬚C (–58 to 176⬚F), T6; –50 to 70°C (–58 to 158°F)
Max. process Temp.(Tp): T4; 120⬚C (248⬚F), T5; 100⬚C (212⬚F), T6; 85⬚C (185⬚F)
Max. surface Temp. for dust-proof : T80°C (Tamb: –40 to 40⬚C, Tp:80⬚C),
CENELEC T100°C (Tamb: –40 to 60⬚C, Tp:100⬚C), T120°C (Tamb: –40 to 80⬚C, Tp:120⬚C)
ATEX CENELEC ATEX (KEMA) Intrinsically safe Approval *1*2
Applicable Standard: EN 50014, EN 50020, EN 50284, EN 50281-1-1
Certificate: KEMA 03ATEX1544X
II 1G, 1D EEx ia IIC T4 Type of protection : IP66 and IP67
KS2
Amb. Temp.(Tamb) for gas-proof: –50 to 60⬚C (–58 to 140⬚F)
Maximum Process Temp.(Tp) for gas-proof :120⬚C
Electrical data : Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=10 nF, Li=0 mH
Max. surface Temp. for dust-proof : T85°C (Tamb: –40 to 60⬚C, Tp:80⬚C),
T100°C (Tamb: –40 to 60⬚C, Tp:100⬚C), T120°C (Tamb: –40 to 60⬚C, Tp:120⬚C)
Combined KF2, KS2 and Type n *1*2
Type n
Applicable Standard: EN 50021, EN 60529 KU2
II 3G EEx nL IIC T4, Amb. Temp.: –50 to 60⬚C (–50 to 140⬚F)
Ui=30 V DC, Ci=10 nF, Li=0 mH
T04E.EPS
*1: Applicable for electrical connection code 2, 4, 7, and 9.
*2: Not applicable for option code /AL.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Feb. 10, 2006-00
<<Contents>> <<Index>> 7
Item Description Code
CSA Explosionproof Approval *2
Certificate: 1589701
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
C22.2 No.94
Explosion-proof for Class I, Groups B, C and D. CF1
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: TYPE 4X, Temp. Code: T6...T4
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-1
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66 and IP67
Canadian Max.Process Temp.: T4;120⬚C(248⬚F), T5;100⬚C(212 ⬚F), T6; 85⬚C(185⬚F)
Standards Amb.Temp.:–50 to 75⬚C(–58 to 167⬚F) for T4, –50 to 80⬚C(–58 to 176⬚F) for T5,
Association –50 to 70⬚C(–58 to 158⬚F) for T6
(CSA)
CSA Intrinsically safe Approval *2*3
Certificate: 1606623
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.154,
C22.2 No.213, C22.2 No.1010.1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups E, F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.:–50 to 60⬚C(–58 to 140⬚F)
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 CS1
[Nonincendive] Vmax=30V, Ci=10nF, Li=0
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-11, CAN/CSA E60079-15,
IEC 60529:2001-02
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66 and IP67
Amb. Temp.:–50 to 60⬚C(–58 to 140⬚F), Max. Process Temp.: 120⬚C(248⬚F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0
[Ex nL] Ui=30V, Ci=10nF, Li=0
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Aug. 31, 2005-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATIONS
Item Description Code
Amplifier cover only *14 P
Color change
Painting Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating *1*14 X2
Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically
safe type, 9 to 32 V DC for Fieldbus communication type.) A
Lightning protector
Allowable current: Max. 6000 A ( 1⫻40 s ), Repeating 1000 A ( 1⫻40 s ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Transistor output (sink type)
Status output *2 AL
Rating: 10.5 to 30 V DC, 120 mA DC (max) Low level: 0 to 2 V DC
Degrease cleansing treatment K1
Oil-prohibited use *13 Degrease cleansing treatment and with fluorinated oilfilled capsule.
K2
Operating temperature –20 to 80°C (–4 to 176°F)
Capsule fill fluid Fluorinated oil filled in capsule K3
P calibration (psi unit) D1
Calibration units *3 (See Table for Span and
bar calibration (bar unit) D3
Range Limits.)
M calibration (kgf/cm2 unit) D4
Failure alarm down-scale: Output status at CPU failure and hardware error is –5%,
C1
3.2mA DC or less.
Output limits NAMUR NE43 Compliant Failure alarm down-scale: Output status at CPU
C2
and failure operation *4 Output signal limits: 3.8mA to failure and hardware error is –5%, 3.2mA DC or less.
20.5 mA Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Stainless steel tag plate 304 SST stainless steel tag plate wired onto transmitter N4
Data configuration for HART communication type Software damping, Descriptor, Message CA
Data configuration at factory *5
Data configuration for BRAIN communication type Software damping CB
PED 97/23/EC
European Pressure Equipment
Category III, Module H, Type of Equipment: Pressure Accessory-Vessel, PE3
Directive *15
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Material certificate*6 Process Connector M15
Test Pressure: 200 kPa (29 psi) *7 T05
Pressure test Test Pressure: 2 MPa (290 psi) *8 *11 T06
Nitrogen(N2) Gas or Water
/Leak test certificate *12 Test Pressure: 10 MPa (1450 psi) *9 Retention time: one minute T07
Test Pressure: 50 MPa (7200 psi) *10 T08
T05.EPS
*1: Not applicable with color change option.
*2: Check/External indicator terminals cannot be used when this option code is specified. Not applicable for output signal
code F and amplifier housing code 2.
*3: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes
D1, D3, and D4.
*4: Applicable for output signal codes D and E. The hardware error indicates faulty amplifier or capsule.
*5: Also see ‘Ordering Information’.
*6: Material traceability certification, per EN 10204 3.1 B.
*7: Applicable for capsule code A.
*8: Applicable for capsule code B.
*9: Applicable for capsule code C.
*10: Applicable for capsule code D.
*11: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*12: The unit on the certificate is always kPa/MPa regardless of selection of option code D1, D3 and D4.
*13: Applicable for wetted parts material code S.
*14: Not applicable for amplifier housing code 2.
*15: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Aug. 31, 2005-00
<<Contents>> <<Index>> 9
DIMENSIONS
Model EJX510A and EJX530A
With process connections code 7 Unit: mm (Approx. inch)
95(3.74)
60(2.36)*2 188(7.4)
ø77(3.03)
(2.72)
(0.23)
ø69
Integral
129(5.08)
indicator
110(4.33)
163(6.42)
169(6.65)
(optional)
Pipe for
open to
atmosphere*1
2-inch pipe
Mounting (O.D. 60.5mm)
bracket 129(5.08)
(optional) 12*3
(0.47)
174(6.85)
5(0.20)
ø6(0.23)
F04.EPS
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Feb. 10, 2006-00
<<Contents>> <<Index>> 10
● Wiring Example for Analog Output and Status Output
Connection Description
Analog output EJX electrical terminal
Distributor
+ 24V DC
SUPPLY +
– 250Ω
–
CHECK +
F06.EPS
< Ordering Information > “” < Factory Setting > “”
Specify the following when ordering
Tag number As specified in order
1. Model, suffix codes, and option codes
2. Calibration range and units Software
damping *1 ‘2.00 sec’ or as specified in order
1) Calibration range can be specified with range
value specifications up to 5 digits Calibration range
(excluding any decimal point) for low or high range lower range value As specified in order
limits within the range of -32000 to 32000. When Calibration range As specified in order
reverse range is designated, specify Lower Range upper range value
Value (LRV) as greater than Upper Range Value [EJX530A]
(URV). Selected from mmH2O, mmH2O(68˚F),
2) Specify only one unit from the table, ‘Factory mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
Settings’ when shipped.’ kPa, MPa, mbar, bar, gf/cm2, kgf/cm2,
inH2O, inH2O(68˚F), inHg, ftH2O,
3. Display scale and units (for transmitters equipped
ftH2O(68˚F) or psi. (Only one unit can be
with integral indicator only) Calibration range specified)
Specify either 0 to 100 % or engineering unit scale units
and ‘Range and Unit’ for engineering units scale: [EJX510A]
Scale range can be specified with range limit Torr, Pa abs, hPa abs*2, kPa abs, MPa
specifications up to 5 digits (excluding any decimal abs, mbar abs, bar abs, kgf/cm2 abs,
mmH2O abs, mmH2O abs(68°F),
point) for low or high range limits within the range of
mmHg abs, inH2O abs, inH2O abs(68°F),
-32000 to 32000. The unit display consists of 6-digit, inHg abs, ftH2O abs, ftH2O abs(68°F),
therefore, if the specified unit is longer than 7 psia, atm.
characters excluding ‘/’, the first 6 characters will be
displayed on the unit display. Designated value specified in order.
Display setting
4. Tag Number (if required) (% or user scaled value.)
For BRAIN communication type, specify upto 16 T06E.EPS
letters. The specified letters will be written in the *1: To specify these items at factroy, /CA or /CB option
is required.
amplifier memory and engraved on the tag plate. *2: Not available for HART protocol type.
For HART communication type, specify software tag
(up to 8 letters) to be written on the amplifier memory
and Tag number(up to 16 letters) to be engraved on
the tag plate seperately.
5. Other factory configurations (if required)
Specifying option code CA or CB will allow further
configuration at factory. Following are configurable
items and setting range.
[/CA: For HART communication type]
1) Descriptor(up to 16 characters)
2) Message (up to 30 characters)
3) Software damping in second (0.00 to 100.00)
[/CB: For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25F01-01E Jan. 05, 2005-00