Pile Cap Design Ori
Pile Cap Design Ori
Pile Cap Design Ori
References:
Y
Reinforced Concrete
Designer's Handbook
10th Editon
Reynolds/Steedman
X q X Table 194, Page 421
B
p Pile Design &
Construction Practice,
L 4th Edition
Pilecap sizing Y MJ Tomlinson
Fig 7.12, Page 285
Diameter/width of pile, dia = 450 All units in kN , mm
Spacing Factor, distance between pile , k = 3 unless stated
Length of pile cap, L = 750 dia + 300
Width of pile cap, B = 750 dia + 300
Minimum depth of pile cap, Hmin = 1000 if dia < 550
Depth of pile cap used, H = 1000 H = 2xdia + 100, else
Assume maximum error in positioning pile, e = 75 H = 0.333(8xdia -600)
For single pile cap, critical shear section directly on pile. Therefore no critical shear
section on pile cap.
For single pile cap, punching shear directly on pile. Therefore no punching shear
at perimeter of stanchion.
CALCULATION SHEET Rev
Subject RB6199-UTP TNB&CONSUMER SSU Project No. RB 6199
Typical Pilecap design for 2(two) Pile Group
PC2-450 Calculation No.
By KAK Chk ARR Appr SBT Date 3-Jul-17 Sheet
References:
Reinforced Concrete
Y
Designer's Handbook
10th Editon
Reynolds/Steedman
X Table 194, Page 421
X B q
p
Pile Design &
Construction Practice,
k* dp
4th Edition
Pilecap sizing L MJ Tomlinson
Fig 7.12, Page 285
Y
Diameter/width of pile, dia = 450 All units in kN , mm
Spacing Factor, distance between pile , k = 3 unless stated
Length of pile cap, L = 2100 (k+1) x dia + 300
Width of pile cap, B = 750 dia + 300
Minimum depth of pile cap, Hmin = 1000 if dia < 550
Depth of pile cap used, H = 1000 H = 2xdia + 100, else
Assume maximum error in positioning pile, e = 75 H = 0.333(8xdia -600)
T References:
Y Reinforced Concrete
Designer's Handbook
10th Editon
Reynolds/Steedman
q B X Table 194, Page 421
X
p F Pile Design &
E
Construction Practice,
4th Edition
Pilecap sizing L MJ Tomlinson
Fig 7.12, Page 285
Y
Diameter/width of pile, dia = 450 All units in kN , mm
Spacing Factor, distance between pile , k = 3 unless stated
Length of pile cap, L = 2100 (k+1) x dia + 300
Width of pile cap, B = 1920 ((6/7)k+1) x dia + 300
Height of vertical section, E = 750 dia + 250
Distance to centre of stanchion, F = 765 ((2/7)k+1/2) x dia + 150
Width of pile cap top section, T = 750 dia + 300
Minimum depth of pile cap, Hmin = 1000 if dia < 550
Depth of pile cap used, H = 1000 H = 2xdia + 100, else
Assume maximum error in positioning pile, e = 75 H = 0.333(8xdia -600)
References:
Reinforced Concrete
Y
Designer's Handbook
10th Editon
Reynolds/Steedman
X Table 194, Page 421
X B q k* dp
References:
Reinforced Concrete
Y
Designer's Handbook
10th Editon
Reynolds/Steedman
X Table 194, Page 421
X B q 1.414k* dp
References:
Reinforced Concrete
Y Designer's Handbook
10th Editon
Reynolds/Steedman
X B p q k* dp X Table 194, Page 421
References:
Y
Reinforced Concrete
Designer's Handbook
10th Editon
Reynolds/Steedman
X B q X Table 194, Page 421
p
Pile Design &
Construction Practice,
k* dp
4th Edition
Pilecap sizing L Y MJ Tomlinson
Fig 7.12, Page 285
Diameter/width of pile, dia = 450 All units in kN , mm
Spacing Factor, distance between pile , k = 3 unless stated
Length of pile cap, L = 3500 (2k+1) x dia + 300
Width of pile cap, B = 3100 (k+1) x dia + 300
Minimum depth of pile cap, Hmin = 1000 if dia < 550
Depth of pile cap used, H = 1300 H = 2xdia + 100, else
Assume maximum error in positioning pile, e = 75 H = 0.333(8xdia -600)
X k* dp X
B
q
p
L
Pilecap sizing Y
Calculation No.
Sheet
References:
Reinforced Concrete
Designer's Handbook
10th Editon
Reynolds/Steedman
Table 194, Page 421
Area = 491
Area = 491
H - cb - dy/2
H - cb - dy/2 - dy
At Column face
2509.904
Lever Arm, La
Layy=(k x dia-p/2+e)
Laxx=((k x dia)/2-p/2+e)
BS8110 Part 1
Cl 3.4.4
la = 0.95
z= 1271
Asmin =0.0013xBxH 12.0
Asmin = 4840
Asprov= 5892
Astop= 0.0013xBxH
4840
la = 0.95
z= 1247
Asmin =0.0013xLxH 17.0
Asmin = 8314
Asprov= 8347
Astop= 0.0013xLxH
8314
BS8110 Part 1
Cl 3.11.4.3
Cl 3.11.4.4
Cl 3.11.4.4
Table 3.9 1
Cl 3.11.4.5
120 - SAILING SPORT TAINING CETRE OF EXCELLENT
400by400 col size
250by250 RC PILE Capacity 560 kN
H= 300 600
PC1 PC2
pilecap 2.18 10.3
soil wt 2.71 10.55
COLUMN LOAD COLUMN LOAD COLUMN LOAD
NO. COLUMN COLUMN (DL) (LL) Design load Foundation type Design load
GRID MARK (TOTAL) PC1 (TOTAL)
(kN) (kN)