Tosvert Vf-S15 Parameter List
Tosvert Vf-S15 Parameter List
Tosvert Vf-S15 Parameter List
TOSVERT VF-S15
Parameter List
E6581949
-Connected option
Option’s name (Type-Form)
1
E6581949
Control terminal F
block R
RES
S1
S2
S3
CC
OUT
NO
P24
CC
RY
RC
FLA
FLB
FLC
VIA
VIB
VIC
PP
FM
CC
+SU
+24
Setting of slide SW1 SINK / PLC / SOURCE
switch SW2 VIB / S4
PTC / S3
2
E6581949
Minimum setting
unit User
Title Function Unit Adjustment range Default setting Reference
Panel/Communica setting
tion
Operation frequency Hz 0.1/0.01 - 0.0 3.2.2
of operation panel
2 Basic parameters
3
E6581949
Basic parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0003 Command - - 0: Terminal block 1 3.2
mode 1: Panel keypad (including 6.2.1
selection extension panel) 7.3
2: RS485 communication
3: CANopen communication
4: Communication option
0004 Frequency - - 0: Setting dial 1(save even if 0 3.2
setting mode power is off) 6.2.1
selection 1 1: Terminal VIA 6.10.1
2: Terminal VIB 5.8
3: Setting dial 2(press in 7.3
center to save)
4: RS485 communication
5: UP/DOWN from external
logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
4
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
fmsl 0005 Meter selection - - 0: Output frequency 0 5.1
1: Output current
2: Frequency command value
3: Input voltage (DC
detection)
4: Output voltage (command
value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load
factor
10: Inverter cumulative load
factor
11: PBR (Braking resistor)
cumulative load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100%
equivalent)
16: Fixed output 2
(output current 50%
equivalent)
17: Fixed output 3
(Other than the output
current)
18: RS485 communication
data
19: For adjustments ( set
value is displayed.)
20: VIC input value
21: Pulse train input value
22: -
23: PID feedback value
24: Integral input power
25: Integral output power
5
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0006 Meter - - - - 5.1
adjustment
gain
0008 Forward/revers - - 0: Forward run 0 6.2.2
e run selection 1: Reverse run
(Panel keypad) 2: Forward run (F/R switching
on extension panel)
3: Reverse run (F/R switching
on extension panel)
0009 Acceleration s 0.1/0.1 0.0-3600 (360.0) *8 10.0
time 1
5.2
0010 Deceleration s 0.1/0.1 0.0-3600 (360.0) *8 10.0
time 1
0011 Maximum Hz 0.1/0.01 30.0-500.0 80.0 5.3
frequency
0012 Upper limit Hz 0.1/0.01 0.5- *1 5.4
frequency
0013 Lower limit Hz 0.1/0.01 0.0- 0.0
frequency
0014 Base frequency Hz 0.1/0.01 20.0-500.0 *1 5.5
1
0409 Base frequency V 1/0.1 50-330 (240V class) *1 5.5
voltage 1 50-660 (500V class) 6.19.6
0015 V/F control - - 0: V/F constant *1 6.3
mode selection 1: Variable torque
2: Automatic torque boost
control
3: Vector control
4: Energy-saving
5: Dynamic energy-saving
(For fan and pump)
6: PM motor control
7: V/F 5-point setting
8: -
0016 Torque boost % 0.1/0.1 0.0-30.0 *2 6.4
value 1
0600 Motor % 1/1 10-100 100 5.6
electronic- (A) 6.29.1
thermal
protection level
1
*1: Default setting values vary depending on the setup menu setting.
*2: Default setting values vary depending on the capacity.
*8: These parameters can be changed to 0.01s unit by setting f519=1.
6
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0017 Electronic-ther - 5.6
mal protection
characteristic Setting
Overload OL stall
protection
selection 0 valid invalid
1 Standard valid valid
2 motor invalid invalid
3 invalid valid
4 valid invalid
5 VF valid valid
6 motor invalid invalid
7 invalid valid
7
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0007 Default setting - - 0: - 0 5.6
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1
(Initialization)
4: Trip record clear
5: Cumulative operation time
clear
6: Initialization of type
information
7: Save user setting
parameters
8: Load user setting
parameters
9: Cumulative fan operation
time record clears
10, 11: -
12: Number of starting clear
13: Default setting 2
(Complete initialization)
0099 Checking the - - 0: Start setup menu *1 4.4
region setting 1: Japan (read only)
*5 2: North America (read only)
3: Asia (read only)
4: Europe (read only)
0050 EASY key - - 0: Standard setting mode at 0 4.5
mode power on
selection 1: Easy setting mode at
power on
2: Easy setting mode only
- Extended - - - - - 4.2.2
parameter
starting at 100
- Extended - - - - -
parameter
starting at 200
- Extended - - - - -
parameter
starting at 300
- Extended - - - - -
parameter
starting at 400
- Extended - - - - -
parameter
starting at 500
- Extended - - - - -
parameter
starting at 600
*1: Default setting values vary depending on the setup menu setting.
*5: Set “0” to activate the setup menu.
8
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
- Extended - - - - - 4.2.2
parameter
starting at 700
- Extended - - - - -
parameter
starting at 800
- Extended - - - - -
parameter
starting at 900
- Extended - - - - -
parameter
starting at A
- Extended - - - - -
parameter
starting at C
- Automatic edit - - - - - 4.3.1
function
9
E6581949
3 Extended parameters
Input/output parameters 1
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0100 Low-speed Hz 0.1/0.01 0.0- 0.0 6.5.1
signal output
frequency
0101 Speed reach Hz 0.1/0.01 0.0- 0.0 6.5.3
setting
frequency
0102 Speed reach Hz 0.1/0.01 0.0- 2.5 6.5.2
detection band 6.5.3
0104 Always active - - 0-153 *6 0 (No 6.7.1
function function)
selection 1
0105 Priority - - 0: Reverse 1 6.6.1
selection (Both 1: Slowdown Stop
F and R are
ON)
0107 Analog input - - 0: 0-+10V 0 6.6.2
terminal 1: -10+10V 6.10.2
selection (VIB) 7.3
0108 Always active - - 0-153 *6 0 (No 6.7.1
function function)
selection 2
0109 Analog/logic - - 0: VIA - analog input 0 6.6.3
input selection VIB - analog input 6.7.2
(VIA/VIB) 1: VIA - analog input 6.10.2
VIB - contact input 7.2.1
2: - 7.3
3: VIA - contact input (Sink)
VIB - contact input
4: VIA - contact input (Source)
VIB-contact input
0110 Always active - - 0-153 *6 6 6.7.1
function (ST)
selection 3
0111 Input terminal - - 0-203 2 6.7.2
selection 1A (F) 7.2.1
(F)
0112 Input terminal - - 4
selection 2A (R)
(R)
0113 Input terminal - - 8
selection 3 (RES)
A(RES)
0114 Input terminal - - 10
selection 4 (SS1)
A(S1)
0115 Input terminal - - 12
selection 5 (SS2)
(S2)
*6: Refer to the instruction manual for details about input terminal function.
10
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0116 Input terminal - - 0-203 *6 14 6.7.2
selection 6 (SS3) 7.2.1
(S3)
0117 Input terminal - - 16
selection 7 (SS4)
(VIB)
Input terminal - - 8-55 *6 24
0118 selection 8 (AD2)
(VIA)
0130 Output - - 0-255 *7 4 6.7.3
terminal (LOW) 7.2.2
selection 1A
(RY-RC)
0131 Output - - 6
terminal (RCH)
selection 2A
(OUT)
0132 Output terminal - - 10
selection 3 (FL)
(FL)
0137 Output - - 255
terminal (alway
selection 1B s ON)
(RY-RC)
0138 Output - - 255
terminal (alway
selection 2B s ON)
(OUT)
0139 Output - - 0: and 0
terminal logic and
selection 1: or
(RY-RC, and
OUT) 2: and
or
3: or
or
0144 Input terminal ms 1/1 1-1000 1 6.7.2
response time 7.2.1
0146 Logic input/ - - 0: Logic input 0 6.7.2
pulse train 1: Pulse train input 6.10.5
input selection 7.2.1
(S2)
0147 Logic input/ - - 0: Logic input 0 2.3.2
PTC input 1: PTC input 6.7.2
selection (S3) 6.29.16
7.2.1
11
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0152 Input terminal - - 0-203 *6 0 6.7.2
selection 7.2.1
2B(R)
0153 Input terminal - - 0
selection
3B(RES)
0154 Input terminal - - 0
selection
4B(S1)
0155 Input terminal - - 0
selection
1C(F)
0156 Input terminal - - 0
selection
2C(R)
0167 Frequency Hz 0.1/0.01 0.0-fh 2.5 6.24
command
agreement
detection
range
*6: Refer to the instruction manual for details about input terminal function.
Basic parameter 2
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0170 Base Hz 0.1/0.01 20.0-500.0 *1 6.8.1
frequency 2
0171 Base V 1/0.1 50-330 (240V class) *1
frequency 50-660 (500V class)
voltage 2
0172 Torque boost % 0.1/0.1 0.0-30.0 *2
value 2
0173 Motor % 1/1 10-100 100 5.6
electronic-ther (A) 6.8.1
mal protection 6.29.1
level 2
0185 Stall % 1/1 10-199, 150 6.8.1
prevention (A) 200 (disabled) 6.29.2
level 2
0190 V/f5-point Hz 0.1/0.01 0.0-fh 0.0 6.3
setting V/F1 6.9
frequency
0191 V/f5-point % 0.1/0.01 0.0-125.0 0.0
setting V/F1
voltage
0192 V/f5-point Hz 0.1/0.01 0.0-fh 0.0
setting V/F2
frequency
*1: Default setting values vary depending on the setup menu setting.
*2: Default setting values vary depending on the capacity.
12
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0193 V/f5-point % 0.1/0.01 0.0-125.0 0.0 6.3
setting V/F2 6.9
voltage
0194 V/f5-point Hz 0.1/0.01 0.0-fh 0.0
setting V/F3
frequency
0195 V/f5-point % 0.1/0.01 0.0-125.0 0.0
setting V/F3
voltage
0196 V/f5-point Hz 0.1/0.01 0.0-fh 0.0
setting V/F4
frequency
0197 V/f5-point % 0.1/0.01 0.0-125.0 0.0
setting V/F4
voltage
0198 V/f5-point Hz 0.1/0.01 0.0-fh 0.0
setting V/F5
frequency
0199 V/f5-point % 0.1/0.01 0.0-125.0 0.0
setting V/F5
voltage
Frequency parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0200 Frequency - - 0: (Switchable to 0 5.8
priority by terminal input) 6.10.1
selection 1: (Switchable to
at 1.0Hz or less of
designated frequency)
0201 VIA input point % 1/1 0-100 0 6.10.2
1 setting 7.3
0202 VIA input point Hz 0.1/0.01 0.0-500.0 0.0
1 frequency
0203 VIA input point % 1/1 0-100 100
2 setting
0204 VIA input point Hz 0.1/0.01 0.0-500.0 *1
2 frequency
0205 VIA input point % 1/0.01 0-250 0 6.31
1 rate
0206 VIA input point % 1/0.01 0-250 100
2 rate
0207 Frequency - - 0-14 (Same as fmod) 1 5.8
setting mode 6.10.1
selection 2
*1: Default setting values vary depending on the setup menu setting.
13
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0209 Analog input ms 1/1 2-1000 64 6.10.2
filter 7.3
0210 VIB input point % 1/1 -100-+100 0
1 setting
0211 VIB input point Hz 0.1/0.01 0.0-500.0 0.0
1 frequency
0212 VIB input point % 1/1 -100-+100 100
2 setting
0213 VIB input point Hz 0.1/0.01 0.0-500.0 *1
2 frequency
0214 VIB input point % 1/0.01 -250-+250 0 6.31
1 rate 6.32
f215 0215 VIB input point % 1/0.01 -250-+250 100
2 rate
f216 0216 VIC input point % 1/1 0-100 20 6.10.2
1 setting 7.3
f217 0217 VIC input point Hz 0.1/0.01 0.0-500.0 0.0
1 frequency
f218 0218 VIC input point % 1/1 0-100 100
2 setting
f219 0219 VIC input point Hz 0.1/0.01 0.0-500.0 *1
2 frequency
f220 0220 VIC input point % 1/0.01 0-250 0 6.31
1 rate
f221 0221 VIC input point % 1/0.01 0-250 100
2 rate
f239 0239 Factory - - - - *3
specific
coefficient 2A
0240 Starting Hz 0.1/0.01 0.1-10.0 0.5 6.11.1
frequency
0241 Operation Hz 0.1/0.01 0.0- 0.0 6.11.2
starting
frequency
0242 Operation Hz 0.1/0.01 0.0- 0.0
starting
frequency
hysteresis
0243 Stop frequency Hz 0.1/0.01 0.0: same as f240 0.0 6.11.1
setting 0.1-30.0
0249 PWM carrier kHz 0.1/0.1 2.0-16.0 4.0 6.12.1
frequency
during DC
braking
0250 DC braking Hz 0.1/0.01 0.0-fh 0.0
starting
frequency
*1: Default setting values vary depending on the setup menu setting.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
14
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0251 DC braking % 1/1 0-100 50 6.12.1
current (A)
0252 DC braking s 0.1/0.1 0.0-25.5 1.0
time
0254 Motor shaft - - 0: Disabled 0 6.12.2
fixing control 1: Enabled
(after DC braking)
0256 Time limit for s 0.1/0.1 0: Disabled 0.0 6.13
lower-limit 0.1-600.0
frequency
operation
0257 Factory - - - - *3
specific
coefficient 2B
0258 Factory - - - - *3
specific
coefficient 2C
0259 Lower limit s 0.1/0.1 0: Disabled 0.0 6.13
frequency 0.1-600.0
reach time
limit at start-up
0260 Jog run Hz 0.1/0.01 -20.0 5.0 6.14
frequency
0261 Jog run - - 0: Deceleration stop 0
stopping 1: Coast stop
pattern 2: DC braking stop
0262 Panel jog run - - 0: Invalid 0
operation 1: Valid
mode
0264 External logic s 0.1/0.1 0.0-10.0 0.1 6.10.4
input - UP
response time
0265 External logic Hz 0.1/0.01 0.0- 0.1
input - UP
frequency
steps
0266 External logic s 0.1/0.1 0.0-10.0 0.1
input - DOWN
response time
0267 External logic Hz 0.1/0.01 0.0- 0.1
input - DOWN
frequency
steps
0268 Initial value of Hz 0.1/0.01 0.0
UP/DOWN
frequency
0269 Change of the - - 0: Not changed 1
initial value of 1: Setting of
UP/DOWN changed when power is
frequency turned off
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
15
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0270 Jump Hz 0.1/0.01 0.0- 0.0 6.15
frequency 1
0271 Jumping width Hz 0.1/0.01 0.0-30.0 0.0
1
0272 Jump Hz 0.1/0.01 0.0- 0.0
frequency 2
0273 Jumping width Hz 0.1/0.01 0.0-30.0 0.0
2
0274 Jump Hz 0.1/0.01 0.0- 0.0
frequency 3
0275 Jumping width Hz 0.1/0.01 0.0-30.0 0.0
3
0287 Preset-speed Hz 0.1/0.01 - 0.0 5.7
frequency 8
0288 Preset-speed Hz 0.1/0.01 - 0.0
frequency 9
0289 Preset-speed Hz 0.1/0.01 - 0.0
frequency 10
0290 Preset-speed Hz 0.1/0.01 - 0.0
frequency 11
0291 Preset-speed Hz 0.1/0.01 - 0.0
frequency 12
0292 Preset-speed Hz 0.1/0.01 0.0
frequency 13
0293 Preset-speed Hz 0.1/0.01 0.0
frequency 14
0294 Preset-speed Hz 0.1/0.01 0.0 5.7
frequency 15 6.30
0295 Bumpless - - 0: Disabled 0 6.16
operation 1: Enabled
selection
0297 Low voltage Hz 0.1/0.01 0.0: Disabled 0.0 6.17
operation 0.1-30.0
upper limit
frequency
0298 Low voltage Vdc 1/0.1 240V class: 72(96)-168 *11 120
operation DC 500V class: 72(120)-336 *11
voltage
*11: 240V class : 4.0kW or less : 72 to 168V, 5.5kW or more : 96 to 168V.
500V class : 4.0kW or less : 72 to 336V, 5.5kW or more : 120 to 336V.
16
E6581949
17
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0308 Dynamic Ω 0.1/0.1 1.0-1000 *2 6.19.4
braking
resistance
0309 Dynamic kW 0.01/0.01 0.01-30.00 *2
braking
resistor
capacity
0310 Factory - - - - *3
specific
coefficient 3A
0311 Reverse-run - - 0: Forward/reverse run 0 6.19.7
prohibition permitted
1: Reverse run prohibited
2: Forward run prohibited
0312 Random mode - - 0: Disabled 0 6.18
1: Random mode 1
2: Random mode 2
3: Random mode 3
0314 Factory - - - - *3
specific
coefficient 3B
0316 PWM carrier - - 0: Carrier frequency without 1 6.18
frequency reduction
control mode 1: Carrier frequency with
selection automatic reduction
2: Carrier frequency without
reduction Support for 500V
models
3: Carrier frequency with
automatic reduction.
Support for 500V models
0317 Synchronized s 0.1/0.01 0.0-3600(360.0) 2.0 6.19.2
deceleration
time (time
elapsed
between start
of deceleration
to stop)
0318 Synchronized s 0.1/0.01 0.0-3600(360.0) 2.0
acceleration
time (time
elapsed
between start
of acceleration
to achievement
of specified
speed)
0319 Regenerative % 1/1 100-160 *1 6.19.5
over-excitation
upper limit
0320 Droop gain % 0.1/0.1 0.0-100.0 0.0 6.20
*1: Default setting values vary depending on the setup menu setting.
*2: Default setting values vary depending on the capacity.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
18
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0323 Droop % 1/1 0-100 10 6.20
insensitive
torque band
0324 Droop output - 0.1/0.1 0.1-200.0 100.0
filter
0325 Brake releasing s 0.01/0.01 0.00-2.50 0.00 6.22.1
waiting time
0326 Brake % 1/1 0-100 0
releasing small
current
detection level
0327 Factory - - - - *3
specific
coefficient 3C
0328 Light-load 0:Disabled 0 6.21
high-speed 1:High-speed operation
operation speed set automatically
selection (Power running at F
command: Increase)
2:High-speed operation
speed set automatically
(Power running at R
command: Increase)
3:High-speed operation
speed set with f330
(Power running at F
command: Increase)
4:High-speed operation
speed set with f330
(Power running at R
command: Increase)
0329 Light-load - - 0: No learning 0
high-speed 1: Forward run learning
learning 2: Reverse run learning
function
0330 Automatic Hz 0.1/0.01 30.0-ul *1
light-load
high-speed
operation
frequency
0331 Light-load Hz 0.1/0.01 5.0-ul 40.0
high-speed
operation
switching
lower limit
frequency
0332 Light-load s 0.1/0.1 0.0-10.0 0.5
high-speed
operation load
waiting time
*1: Default setting values vary depending on the setup menu setting.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
19
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0333 Light-load s 0.1/0.1 0.0-10.0 1.0 6.21
high-speed
operation load
detection time
0334 Light-load s 0.1/0.1 0.0-10.0 0.5
high-speed
operation
heavy load
detection time
0335 Switching load % 1/0.01 -250 - +250 50
torque during
power running
0336 Heavy-load % 1/0.01 -250 - +250 100
torque during
power running
0337 Heavy-load % 1/0.01 -250 - +250 50
torque during
constant
power running
0338 Switching load % 1/0.01 -250 - +250 50
torque during
regenerative
braking
0339 Factory - - - - *3
specific
coefficient 3D
0340 Creeping time s 0.01/0.01 0.0-10.00 0.00 6.22.1
1
0341 Braking mode - - 0: Disabled 0
selection 1: Forward winding up
2: Reverse winding up
3: Horizontal operation
0342 Load portion - - 0: Disabled 4
torque input 1: Terminal VIA
selection 2: Terminal VIB
3: Terminal VIC
4: f343
0343 Hoisting % 1/0.01 -250 - +250 100
torque bias
input (valid
only when
f324=4)
0344 Lowering % 1/0.01 0-100 100
torque bias
multiplier
0345 Brake release s 0.01/0.01 0.00-10.00 0.05
time
0346 Creeping Hz 0.1/0.01 f240-20.0 3.0
frequency
0347 Creeping time s 0.01/0.01 0.00-10.00 0.10
2
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
20
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0348 Braking time - 1/1 0:Disabled 0 6.22.1
learning 1: Learning (0 after adjustment)
function
0349 Acceleration/ - 1/1 0:Disabled 0 6.23
deceleration 1:Parameter setting
suspend 2:Terminal input
function
0350 Acceleration Hz 0.1/0.01 0.0-fh 0.0
suspend
frequency
0351 Acceleration s 0.1/0.1 0.0-10.0 0.0
suspend time
0352 Deceleration Hz 0.1/0.01 0.0-fh 0.0
suspend
frequency
0353 Deceleration s 0.1/0.1 0.0-10.0 0.0
suspend time
0359 PID control s 1/1 0-2400 0 6.24
waiting time
0360 PID control - - 0: Disabled 0
1: Process type PID control
2: Speed type PID control
0361 Delay filter s 0.1/0.1 0.0-25.0 0.1
0362 Proportional - 0.01/0.01 0.01-100.0 0.30
gain
0363 Integral gain s-1 0.01/0.01 0.01-100.0 0.20
0366 Differential s 0.01/0.01 0.00-2.55 0.00
gain
0367 Process upper Hz 0.1/0.01 0.0-fh *1
limit
0368 Process lower Hz 0.1/0.01 0.0-f367 0.0
limit
0369 PID control - - 0: Disabled 0
feedback 1: Terminal VIA
signal 2: Terminal VIB
selection 3: Terminal VIC
4 to 6: -
0372 Process s 0.1/0.1 0.1-600.0 10.0
increasing rate
(speed type
PID control)
0373 Process s 0.1/0.1 0.1-600.0 10.0
decreasing
rate (speed
type PID
control)
0375 Factory - - - - *3
specific
coefficient 3E
0376 Factory - - - -
specific
coefficient 3F
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
21
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0378 Number of pps 1/1 10-500 25 6.10.5
pulse train
input
0380 PID forward/ - - 0: Forward 0 6.24
reverse 1: Reverse
characteristics
selection
0382 Hit and stop - - 0:Disabled 0 6.22.2
control 1:Enabled
2:-
0383 Hit and stop Hz 0.1/0.01 0.1-30.0 5.0
control
frequency
0384 Factory - - - - *3
specific
coefficient 3G
0385 Factory - - - -
specific
coefficient 3H
0386 Factory - - - -
specific
coefficient 3I
0389 PID control - - 0: fmod/f207 selected 0 6.24
reference 1: Terminal VIA
signal 2: Terminal VIB
selection 3: fpid
4: RS485 communication
5: UP/DOWN from external
logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
0390 Factory - - - - *3
specific
coefficient 3J
0391 Hysteresis for Hz 0.1/0.1 0.0-ul 0.2 6.13
lower-limit
frequency
operation
0394 Factory - - - - *3
specific
coefficient 3K
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
22
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0458 Motor specific - - - - *4
coefficient 2
0459 Load inertia Times 0.1/0.1 0.1-100.0 1.0 6.25
moment ratio
0460 Motor specific - - - - *4
coefficient 3
0461 Motor specific - - - -
coefficient 4
0462 Speed - - 0-100 35 6.25
reference filter
coefficient
0467 Motor specific - - - - *4
coefficient 5
*4: Motor specific coefficient parameters are manufacturer setting parameters. Do not change the value of these
parameters.
Input/output parameters 2
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0470 VIA input bias - 1/1 0-255 128 6.10.3
0471 VIA input gain - 1/1 0-255 128
0472 VIB input bias - 1/1 0-255 128
0473 VIB input gain - 1/1 0-255 128
0474 VIC input bias - 1/1 0-255 128
0475 VIC input gain - 1/1 0-255 128
24
E6581949
25
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0590 Shock - - 0: Disabled 0 6.28
monitoring 1: Current detection
2: Torque detection
0591 Shock - - 0: Alarm only 0
monitoring 1: Tripping
trip/alarm
selection
0592 Shock - - 0: Over-current / torque 0
monitoring detection
detection 1: Low-current / torque
direction detection
selection
0593 Shock % 1/1 0-250 150
monitoring
detection level
0595 Shock s 0.1/0.1 0.0-10.0 0.5
monitoring
detection time
0596 Shock % 1/1 0-100 10
monitoring
detection
hysteresis
0597 Shock s 0.1/0.1 0.0-300.0 0.0
monitoring
detection start
waiting time
0598 Shock - - 0: During operation 0
monitoring 1: During operation (except
detection acceleration/ deceleration)
action
selection
26
E6581949
Protection parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0601 Stall % 1/1 10-199, 150 6.29.2
prevention (A) 200 (disabled)
level 1
0602 Inverter trip - - 0: Cleared with power off 0 6.29.3
retention 1: Retained with power off
selection
0603 Emergency - - 0: Coast stop 0 6.29.4
stop selection 1: Deceleration stop
2: Emergency DC braking
3: Deceleration stop
(f515)
4: Quick deceleration stop
5: Dynamic quick
deceleration stop
0604 DC braking s 0.1/0.1 0.0-20.0 1.0
time during
emergency
stop
0605 Output phase - - 0: Disabled 0 6.29.5
failure 1: At start-up (only one time
detection after power on)
selection 2: At start-up (each time)
3: During operation
4: At start-up + during
operation
5: Detection of cutoff on
output side
0607 Motor 150% s 1/1 10-2400 300 5.6
overload 6.29.1
detection time
0608 Input phase - - 0: Disabled 1 6.29.6
failure 1: Enabled
detection
selection
0609 Small current % 1/1 1-20 10 6.29.7
detection
hysteresis
0610 Small current - - 0: Alarm only 0
trip/alarm 1: Tripping
selection
0611 Small current % 1/1 0-150 0
detection (A)
current
0612 Small current s 1/1 0-255 0
detection time
27
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0613 Detection of - - 0: Each time (standard pulse) 0 6.29.8
output 1: Only one time after power
short-circuit at on (standard pulse)
start-up 2: Each time (short pulse)
3: Only one time after power
on (short pulse)
0614 Ground fault - - 0: Disabled 1 6.29.9
detection 1: Enabled
selection
0615 Over-torque - - 0: Alarm only 0 6.29.10
trip/alarm 1: Tripping
selection
0616 Over-torque % 1/0.1 0 (disabled) 150
detection level 1-250
0616 Over-torque s 0.1/0.1 0.0-10.0 0.5
detection time
0619 Over-torque % 1/1 0-100 10
detection
hysteresis
0620 Cooling fan - - 0: ON/OFF control 0 6.29.11
ON/OFF 1: Always ON
control
0621 Cumulative 100 0.1/0.1 0.0-999.0 876.0 6.29.12
operation time hour (=10 hours)
alarm setting s
0625 Factory - - - - *3
specific
coefficient 6A
0626 Over-voltage % 1/1 100-150 *2 6.19.4
stall protection 6.19.5
level
0627 Undervoltage - - 0: Alarm only (detection level 0 6.29.13
trip/alarm 60% or less)
selection 1: Tripping (detection level
60% or less)
2: Alarm only (detection level
50% or less, input AC
reactor required)
3: -
*2: Default setting values vary depending on the capacity.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
28
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0629 Factory - - - - *3
specific
coefficient 6B
0631 Inverter - - 0: 150%-60s (120%-60s) 0 5.6
overload 1: Temperature estimation
detection
method
0632 Electronic- - - 0: Disabled (thr, f173) 0 5.6
thermal 1: Enabled (thr, f173) 6.29.1
memory 2: Disabled (thr)
3: Enabled (thr)
0633 Analog input % 1/1 0: Disabled, 0 6.29.14
break detection 1-100
level (VIC)
0634 Annual - - 1: -10 to +10C 3 6.29.15
average 2: 11-20C
ambient 3: 21-30C
temperature 4: 31-40C
(parts 5: 41-50C
replacement 6: 51-60C
alarms)
0643 Factory - - - - *3
specific
coefficient 6C
0644 Operation - - 0: Tripping 0 6.29.14
selection of 1: Alarm only (Coast stop)
analog input 2: Alarm only (f649
break frequency)
detection 3: Alarm only (Maintain
(VIC) running)
4: Alarm only (Deceleration
stop)
0645 PTC thermal - - 1: Tripping 1 6.29.16
selection 2: Alarm only
0646 PTC detection Ω 1/1 100-9999 3000
resistor value
0648 Number of 10000 0.1/0.1 0.0-999.0 999.0 6.29.17
starting times
alarm
0649 Fallback Hz 0.1/0.01 ll- 0.0 6.29.14
frequency
0650 Forced - - 0: Disabled 0 6.30
fire-speed 1: Enabled
control
selection
0656 Factory - - - - *3
specific
coefficient 6D
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
29
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0657 Overload alarm % 1/1 10-100 50 5.6
level
0660 Override - - 0: Disabled 0 6.31
addition input 1: Terminal VIA
selection 2: Terminal VIB
3: Terminal VIC
4: fc
0661 Override - - 0: Disabled 0
multiplication 1: Terminal VIA
input selection 2: Terminal VIB
3: Terminal VIC
4: f729
0663 Analog input - - 0: Frequency command 0 6.32
terminal 1: Acceleration/deceleration
function time
selection (VIB) 2: Upper limit frequency
3, 4: -
5: Torque boost value
6: Stall prevention level
7: Motor electronic-thermal
protection level
8 to 10: -
11: Base frequency
30
E6581949
Output parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0667 Integral input - - 0: 0.1kWh 1 6.33.1
power pulse 1: 1kWh
output unit 2: 10kWh
3: 100kWh
0668 Integral input s 0.1/0.1 0.1-1.0 0.1
power pulse
output width
0669 Logic - - 0: Logic output 0 6.33.2
output/pulse 1: Pulse train output
train output
selection (OUT)
0676 Pulse train - - 0:Output frequency 0
output function 1:Output current
selection 2:Frequency command value
(OUT) 3:Input voltage (DC detection)
4:Output voltage (command
value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load
factor
10: Inverter cumulative load
factor
11: PBR (Braking resistor)
cumulative load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100%
equivalent)
16: Fixed output 2
(output current 50%
equivalent)
17: Fixed output 3
(Other than the output
current)
18: Communication data
19: -
20: VIC input value
21, 22: -
23: PID feedback value
0677 Maximum kpps 0.01/0.01 0.50-2.00 0.80
numbers of
pulse train
output
0678 Pulse train ms 1/1 2-1000 64
output filter
0679 Pulse train ms 1/1 2-1000 2 6.10.5
input filter
31
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0681 Analog output - - 0: Meter option (0 to 1 mA) 0 5.1
signal selection 1: Current (0 to 20 mA) 6.33.3
output
2: Voltage (0 to 10 V) output
0684 Analog output ms 1/1 2-1000 2
filter
0691 Inclination - - 0: Negative inclination 1
characteristic (downward slope)
of analog 1: Positive inclination
output (upward slope)
0692 Meter bias % 1/1 0-100 0
0693 Factory - - - - *3
specific
coefficient 6E
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these
parameters.
32
E6581949
33
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Com setting setting
munication
0710 Initial panel - - 0: Output frequency (Hz/free unit) 0 6.34.5
display 1: Output current (%/A) 8.2.1
selection 2: Frequency command value 8.3.2
(Hz/free unit)
3: Input voltage (DC detection)
(%/V)
4: Output voltage (command value)
(%/V)
5: Input power (kW)
6: Output power (kW)
7: Torque (%)
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor)
cumulative load factor
12: Stator frequency (Hz/free unit)
13: VIA input value (%)
14: VIB input value (%)
15 to 17: -
18: Arbitrary code from
communication
19: -
20: VIC input value (%)
21: Pulse train input value (pps)
22: -
23: PID feedback value (Hz/free
unit)
24: Integral input power (kWh)
25: Integral output power (kWh)
26: Motor load factor (%)
27: Inverter load factor (%)
28: Inverter rated current (A)
29: FM output value (%)
30: Pulse train output value (pps)
31: Cumulative power on time (100
hours)
32: Cumulative fan operation time
(100 hours)
33: Cumulative operation time (100
hours)
34: Number of starting (10000
times)
35: Forward number of starting
(10000 times)
36: Reverse number of starting
(10000 times)
37: Number of trip (times)
38, 39: -
40: Inverter rated current (Carrier
frequency corrected)
41 to 51: -
52: Frequency command value/
output frequency (Hz/free
unit)
34
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0711 Status monitor 1 - -- 0: Output frequency (Hz/free 2 6.34.6
0712 Status monitor 2 - - unit) 1 8.2.
0713 Status monitor 3 - - 1: Output current (%/A) 3 8.3.2
2: Frequency command value
0714 Status monitor 4 - - 4
(Hz/free unit)
0715 Status monitor 5 - - 3: Input voltage (DC detection) 5
0716 Status monitor 6 - - (%/V) 6
0717 Status monitor 7 - - 4: Output voltage (command 27
35
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0718 Status monitor 8 - - value) (%/V) 0
5: Input power (kW)
6: Output power (kW)
7: Torque (%)
8: -
9: Motor cumulative load factor
10: Inverter cumulative load
factor
11: PBR (Braking resistor)
cumulative load factor
12: Stator frequency (Hz/free unit)
13: VIA input value (%)
14: VIB input value (%)
15 to 17: -
18: Arbitrary code from
communication
19: -
20: VIC input value (%)
21: Pulse train input value (pps)
22: -
23: PID feedback value
(Hz/free unit)
24: Integral input power (kWh)
25: Integral output power (kWh)
26: Motor load factor (%)
27: Inverter load factor (%)
28: Inverter rated current (A)
29: FM output value (%)
30: Pulse train output value (pps)
31: Cumulative power on time
(100 hours)
32: Cumulative fan operation
time (100 hours)
33: Cumulative operation time
(100 hours)
34: Number of starting (10000 times)
35: Forward number of starting
(10000 times)
36: Reverse number of starting
(10000 times)
37: Number of trip (times)
38, 39: -
40: Inverter rated current
(Carrier frequency corrected)
41 to 51: -
52: Frequency command value /
output frequency (Hz/free
unit)
36
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0719 Selection of - - 0: Clear at coast stop and 1 6.34.8
operation retained at moff.
command clear 1: Retained at coast stop and
moff.
2: Clear at coast stop and
moff.
3: 2+ clear when cmod is
changed
0720 Initial - - 0-52 (Same as f710) 0 6.34.5
extension
panel display
selection
0721 Panel stop - - 0: Deceleration stop 0 6.34.9
pattern 1: Coast stop
0724 Operation - - 0: Panel frequency () 0 5.7
frequency 1: Panel frequency () +
setting target Preset speed frequency
by setting dial
0729 Operation % 1/1 -100 - +100 0 6.31
panel override
multiplication
gain
0730 Panel - - 0: Permitted 0 6.34.1
frequency 1: Prohibited
setting
prohibition
()
0731 Disconnection - - 0: Permitted 0
detection of 1: Prohibited
extension
panel
0732 Local/remote - - 0: Permitted 1 6.16
key prohibition 1: Prohibited 6.34.1
of extension
panel
0733 Panel - - 0: Permitted 0 6.34.1
operation 1: Prohibited
prohibition
(RUN key)
0734 Panel - - 0: Permitted 0
emergency 1: Prohibited
stop operation
prohibition
0735 Panel reset - - 0: Permitted 0
operation 1: Prohibited
prohibition
0736 / - - 0: Permitted 1
f 1: Prohibited
change
prohibition
during
operation
37
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0737 All key - - 0: Permitted 0 6.34.1
operation 1: Prohibited
prohibition
0738 Password - - 0: Password unset 1-9998 0
setting 9999: Password set
()
0739 Password - - 0: Password unset 1-9998 0
verification 9999: Password set
0740 Trace - - 0: Disabled 1 6.35
selection 1: At tripping
2: At triggering
3: 1+2
0741 Trace cycle - - 0: 4ms 2
1: 20ms
2: 100ms
3: 1s
4: 10s
0742 Trace data 1 - - 0-42 0
0743 Trace data 2 - - 1
0744 Trace data 3 - - 2
0745 Trace data 4 - - 3
0746 Status monitor ms 1/1 8-1000 200 6.34.7
filter
0748 Integrating - - 0: Disabled 0 6.36
wattmeter 1: Enabled
retention
selection
0749 Integrating - - 0:1=1kWh *2
wattmeter 1:1=10kWh
display unit 2:1=100kWh
selection 3:1=1000kWh
4:1=10000kWh
0750 EASY key - - 0: Easy / standard setting 0 4.5
function mode switching function 6.16
selection 1: Shortcut key 6.37
2: Local / remote key
3: Monitor peak / minimum
hold trigger
4,5: -
0751 Easy setting - - 0-2999 3 4.5
mode (Set by communication (CMod) 6.37
parameter 1 number)
0752 Easy setting - - 4
mode (Fmod)
parameter 2
0753 Easy setting - - 9
mode (ACC)
parameter 3
0754 Easy setting - - 10
mode (dEC)
parameter 4
*2: Default setting values vary depending on the capacity.
38
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0755 Easy setting - - 0-2999 12 4.5
mode (Set by communication (UL) 6.37
parameter 5 number)
0756 Easy setting - - 13
mode (LL)
parameter 6
0757 Easy setting - - 600
mode (tHr)
parameter 7
0758 Easy setting - - 6
mode (FM)
parameter 8
0759 Easy setting - - 999
mode
parameter 9
0760 Easy setting - - 999
mode
parameter 10
0761 Easy setting - - 999
mode
parameter 11
0762 Easy setting - - 999
mode
parameter 12
0763 Easy setting - - 999
mode
parameter 13
0764 Easy setting - - 999
mode
parameter 14
0765 Easy setting - - 999
mode
parameter 15
0766 Easy setting - - 999
mode
parameter 16
0767 Easy setting - - 999
mode
parameter 17
0768 Easy setting - - 999
mode
parameter 18
0769 Easy setting - - 999
mode
parameter 19
0770 Easy setting - - 999
mode
parameter 20
0771 Easy setting - - 999
mode
parameter 21
39
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0772 Easy setting - - 0-2999 999 4.5
mode (Set by communication 6.37
parameter 22 number)
0773 Easy setting - - 999
mode
parameter 23
0774 Easy setting - - 999
mode
parameter 24
0775 Easy setting - - 999
mode
parameter 25
0776 Easy setting - - 999
mode
parameter 26
0777 Easy setting - - 999
mode
parameter 27
0778 Easy setting - - 999
mode
parameter 28
0779 Easy setting - - 999
mode
parameter 29
0780 Easy setting - - 999
mode
parameter 30
0781 Easy setting - - 701
mode (F701)
parameter 31
0782 Easy setting - - 50
mode (PSEL)
parameter 32
0790 Panel display - - 0: hello 0 6.34.10
selection at 1: f791 to f794
power on 2, 3: -
st nd
0791 1 and 2 hex - 0-FFFF 2d2d
characters of
f790
0792 3rd and 4th hex - 0-FFFF 2d2d
characters of
f790
0793 5th and 6th hex - 0-FFFF 2d2d
characters of
f790
0794 7th and 8th hex - 0-FFFF 2d2d
characters of
f790
0799 Factory - - - - *3
specific
coefficient 7A
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters
40
E6581949
Communication parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0800 Baud rate - - 3: 9600bps 4 6.38.1
4: 19200bps
5: 38400bps
0801 Parity - - 0: No parity 1
1: Even parity
2: Odd parity
0802 Inverter - 1/1 0-247 0
number
0803 Communicatio s 1/1 0: Disabled 0.0
n time-out time 0.1-100.0
0804 Communicatio - - 0: Alarm only 0
n time-out 1: Trip (Coast stop)
action 2: Trip (Deceleration stop)
0805 Communicatio s 0.01/0.01 0.00-2.00 0.00
n waiting time
f806 0806 Setting of - - 0: Slave (0 Hz command 0
master and issued in case the master
slave for inverter fails)
communicatio 1: Slave (Operation
n between continued in case the
inverters master inverter fails)
2: Slave (Emergency stop
tripping in case the master
inverter fails)
3: Master (transmission of
frequency commands)
4: Master (transmission of
output frequency signals)
f808 0808 Communicatio - - 0: Valid at any time 1
n time-out 1: Communication selection
detection of fmod or cmod
condition 2: 1 + during operation
0810 Communicatio - 1/1 0: Disabled 0 6.10.2
n command 1: Enabled 6.38.1
point selection
0811 Communicatio % 1/1 0-100 0
n command
point 1 setting
0812 Communicatio Hz 0.1/0.01 0.0-fh 0.0
n command
point 1
frequency
0813 Communicatio % 1/1 0-100 0
n command
point 2 setting
41
E6581949
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0814 Communicatio Hz 0.1/0.01 0.0-fh *1 6.10.2
n command 6.38.1
point 2
frequency
0829 Selection of - - 0: Toshiba inverter protocol 0 6.38.1
communicatio 1: Modbus RTU protocol
n protocol
0856 Number of - - 1: 2 poles 2
motor poles for 2: 4 poles
communication 3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0870 Block write - - 0: No selection 0
data 1 1: Communication command 1
0871 Block write - - 2: Communication command 2 0
data 2 3: Frequency command
value
4: Output data on the
terminal block
5: FM analog output
6: Motor speed command
0875 Block read - - 0: No selection 0
data 1 1: Status information 1
0876 Block read - - 2: Output frequency 0
data 2 3: Output current
0877 Block read - - 4: Output voltage 0
data 3 5: Alarm information
0878 Block read - - 6: PID feedback value 0
7: Input terminal monitor
data 4
8: Output terminal monitor
0879 Block read - - 0
9: Terminal VIA monitor
data 5 10: Terminal VIB monitor
11: Terminal VIC monitor
12: Input voltage (DC
detection)
13: Motor speed
14: Torque
f880 0880 Free notes - 1/1 0-65530 (65535) 0 6.38.3
f898 0898 Factory - - - *3
specific
coefficient 8A
f899 0899 Communicatio - - 0: - 0 6.38.1
n function 1: Reset (after execution: 0)
reset
*1: Default setting values vary depending on the setup menu setting.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these
parameters.
42
E6581949
PM motor parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Commu setting setting
nication
0900 Factory - - - - *3
specific
coefficient 9A
0901 Factory - - - -
specific
coefficient 9B
0902 Factory - - - -
specific
coefficient 9C
0909 Factory - - - -
specific
coefficient 9D
0910 Step-out % 1/1 1-150 100 6.39
detection
current level
0911 Step-out s 0.01/0.01 0.0: No detection 0.00
detection time 0.1-25.0
f912 0912 q-axis mH 0.01/0.01 0.01-650.0 10.00 6.25.2
inductance 6.39
f913 0913 d-axis mH 0.01/0.01 0.01-650.0 10.00
inductance
f914 0914 Factory - - - - *3
specific
coefficient 9E
f915 0915 Factory - - - -
specific
coefficient 9L
f916 0916 Factory - - - -
specific
coefficient 9F
f917 0917 Factory - - - -
specific
coefficient 9G
f918 0918 Factory - - - -
specific
coefficient 9H
f919 0919 Factory - - - -
specific
coefficient 9I
f920 0920 Factory - - - -
specific
coefficient 9J
f930 0930 Factory - - - -
specific
coefficient 9K
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of
these parameters.
43
E6581949
Traverse parameters
Minimum
Communi setting unit Default User
Title Function Unit Adjustment range Reference
cation No. Panel/Comm setting setting
unication
0980 Traverse - 1/1 0: Disabled 0 6.40
selection 1: Enabled
0981 Traverse s 0.1/0.1 0.1-120.0 25.0
acceleration
time
0982 Traverse s 0.1/0.1 0.1-120.0 25.0
deceleration
time
0983 Traverse step % 0.1/0.1 0.0-25.0 10.0
0984 Traverse jump % 0.1/0.1 0.0-50.0 10.0
step
44
E6581949
45
E6581949
46