Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

LGB6 Gas Fired Boiler

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

LGB Gas–fired boiler

Control Supplement
LGB-6 to LGB-20 Series 2
– Natural gas
CSD-1 Control System

Contents
I. Installation..................... 2
II. Gas piping...................... 4
III. Water and steam trim
components..................... 5
IV. Wiring............................. 5
Sequence of operation.......8
Wiring procedure................8
V. Leak test procedure.... 10
VI. Operating instructions.11
VII. Parts list....................... 12

These terms are used throughout this Indicates presence of hazards that can cause severe personal injury, death
manual to bring attention to the presence or substantial property damage.
of hazards of various risk levels or to
important information concerning the life
of the product. Indicates special instructions on installation, operation or maintenance
that are important but not related to personal injury or property damage.

This Control Supplement must only be used by a qualified installer/service


technician. Read these instructions completely before beginning the instal-
lation. Failure to follow these instructions can cause severe personal injury,
death or substantial property damage.

Part Number 550-141-815/0314


LGB-6 to LGB-20  Series 2 – Control Supplement

I Installation

1. Assemble pilot burner and flame sensor to main burners with pilot brackets. See Figures
1 and 2 (page 3). Install ground wiring as shown in Figures 1 and 2 (page 3).
2. Reinstall burner assemblies. See Table 1, below for pilot burner and flame sensor loca-
tions.
3. Install gas controls and ignition control panel(s) as shown in Table 2, below and Figure 6
(page 12).

Table 1 Boiler Flame Sensor * Pilot Burner * Boiler Flame Sensor * Pilot Burner *
Number No. 1 No. 2 No. 1 No. 2 Number No. 1 No. 2 No. 1 No. 2
Pilot burner and flame sensor 2 --- 9 --- 2
LGB-6 LGB-14 16 13 25
locations
LGB-7 2 --- 11 --- LGB-15 2 16 13 27
LGB-8 2 --- 13 --- LGB-16 2 18 15 29
LGB-9 2 --- 15 --- LGB-17 2 18 15 31
LGB-10 2 --- 16 --- LGB-18 2 20 16 33
LGB-11 2 --- 16 --- LGB-19 2 20 16 34
LGB-12 2 --- 16 --- LGB-20 2 22 16 36
LGB-13 2 14 11 23
* From left burner.

Table 2 7.00” Inlet Pipe Size 5.00” Inlet Pipe Size


Boiler W.C. W.C.
Gas control arrangement Number Carton Left Base Right Base Carton Left Base Right Base
LGB-6 A and B 1” --- A and B 1-¼” ---
LGB-7 A and B 1” --- A and B 1-¼” ---
LGB-8 C and D 1” --- C and D 1-¼” ---
LGB-9 C and D 1” --- C and D 1-¼” ---
LGB-10 E, F and G 1-¼” --- E 1-½” ---
LGB-11 E, F and G 1-¼” --- F and G 2” ---
LGB-12 E, F and G 1-¼” --- F and G 2” ---
LGB-13 H 1” 1” H 1-¼” 1-¼”
LGB-14 I 1” 1” I 1-¼” 1-¼”
LGB-15 J 1” 1” J 1-¼” 1-¼”
LGB-16 J 1” 1” J 1-¼” 1-¼”
LGB-17 J 1” 1” J 1-¼” 1-¼”
LGB-18 K 1-¼” 1” K 1-½” 1-¼”
LGB-19 L 1-¼” 1-¼” M 1-½” 1-½”
LGB-20 L 1-¼” 1-¼” N 2” 1-½”

2 Part Number 550-141-815/0314


CSD-1 Control System - Natural gas

I Installation – continued

Figure 1

Pilot burner assembly, typical

Figure 2

Main flame sensor assembly

Part Number 550-141-815/0314 3


LGB-6 to LGB-20  Series 2 – Control Supplement

II Gas piping

1. Size natural gas piping from Table 3, below. Size piping to provide proper inlet pressure
to gas valve when operating at rated input.
a. Inlet gas pressure to manual main shut-off gas valve —
minimum 7” W.C. standard (5” W.C. on special order) – maximum 13” W.C.
b. If pressure to gas valve exceeds 13” W.C., install 100% lock-up gas pressure regulator
upstream of hand valve.
c. To obtain approximate cubic feet per hour, divide input (Btu/hr) by 1000.
2. Size gas piping considering —
a. Diameter and length of gas supply piping.
b. Number of fittings.
c. Maximum gas consumption (including any possible future expansion).
d. Allowable pressure drop from gas meter to boiler. For pressure drops, see ANSI
Z223.1. – latest edition.
3. Remove knockout disc from jacket panel through which gas supply will be piped.
4. Follow good piping practices.
5. Pipe joint compound (pipe dope) must be resistant to corrosive action of liquefied
petroleum gases. Apply sparingly only to male ends of pipe joints.
6. Install drip leg at inlet of gas connection to boiler. Where local code/utility requires,
extend drip leg to floor.
7. Install ground joint union when required for servicing.
8. Support piping by hangers, not by boiler or its accessories.
9. Purge all air from supply piping.
10. Before operating boiler, check boiler and its gas connections for leaks.
Do not check for gas leaks with an open flame – BUBBLE TEST. Failure
to use bubble test or test for leaks can cause severe personal injury, death
or substantial property damage.

a. Close manual main shut-off valve during any pressure testing at less than 13” W.C.
b. Disconnect boiler and gas valve from gas supply piping during any pressure test
greater than 13” W.C.

Table 3 *Pipe length, in feet (Natural Gas capacities listed in MBH)


Gas pipe sizing - natural gas Pipe
(Specific gravity 0.60 @ Pressure Loss of 0.30" W.C.)
size
10 20 30 40 50 75 100 150
1-¼” 1,050 730 590 500 440 360 305 250
1-½” 1,600 1,100 890 760 670 545 460 380
2” 3,050 2,100 1,650 1,450 1,270 1,020 870 710
2-½” 4,800 3,300 2,700 2,300 2,000 1,650 1,400 1,130
3” 8,500 5,900 4,700 4,100 3,600 2,900 2,500 2,000
4” 17,500 12,000 9,700 8,300 7,400 6,000 5,100 4,100
*Include measured length of gas supply piping and allowance in feet for number and size of fittings.

4 Part Number 550-141-815/0314


CSD-1 Control System - Natural gas

III Water and steam trim components

1. Install water or steam trim components as required by CSD-1 latest edition. See the
boiler manual for tapping locations.
a. Water boilers require:
• a manual reset high temperature limit control in addition to the standard
automatic reset limit control.
• a manual reset low water cutoff.
b. Steam boilers require:
• a manual reset high pressure limit control in addition to the standard automatic
reset limit control.
• a manual reset low water cutoff in addition to the standard automatic reset low
water cutoff.

IV Wiring

For your safety, turn off electrical power supply before making any electrical
connections to avoid possible electrical shock hazard.
1. All wiring must be installed in accordance with the requirements of the National
Electrical Code and any additional national, state or local code requirements having
jurisdiction. All wiring external to boiler jacket must be N.E.C. Class 1.
2. The boiler must be electrically grounded in accordance with the National Electrical
Code, ANSI/NFPA -latest edition. Use 105 °C thermoplastic wire, or equivalent, if any
original wire must be replaced (except for pilot spark, sense and ground wires).
3. Wiring to boiler must be No. 14 gauge or heavier. Install in conduit.
4. A separate electrical circuit with a fused disconnect switch (15 amp. recommended)
should be used for the boiler.
5. Refer to wiring diagrams, Figure 3 (pages 6 and 7) and Figure 5 (page 9). See section,
“Wiring Procedure” on page 8.
6. Figure 5 on page 9 is the Field Wiring Diagram. See Figure 3, pages 6 and 7, for the
schematic and ladder wiring diagrams.

Part Number 550-141-815/0314 5


LGB-6 to LGB-20  Series 2 – Control Supplement

6 Part Number 550-141-815/0314


CSD-1 Control System - Natural gas

Figure 3
Wiring diagram

Part Number 550-141-815/0314 7


LGB-6 to LGB-20  Series 2 – Control Supplement

IV Wiring - continued

Sequence of operation 1. Operating control begins startup sequence.


a. Limit control contacts are closed.
2. Pilot proving module energized.
a. Pilot solenoid opens.
b. Pilot ignition spark begins.
c. Pilot ignites.
d. Pilot proves.
On failure to sense pilot flame, the pilot-proving module will wait 5
minutes, then retry for ignition. Upon 2 consecutive pilot flame failures,
the control will lockout and illuminate the red lockout light.
3. Main flame proving module energized from pilot proving module.
a. Secondary gas valve opens.
b. Main gas valve opens to low fire position.
c. Main burners ignite at low fire.
d. Main flame sensor proves low fire carryover.
e. Main gas valve opens to high fire position.
f. Main burners increase to high fire.
On failure to sense main flame, the main flame-proving module will
lockout and illuminate the red lockout light.
4. For dual base assembly - operating control energizes controls for each base assembly at the
same time. See steps 1 through 3 above.
5. Boiler shuts down when operating control satisfied.
If the boiler locks out, the alarm contacts on the terminal strip (terminals
A1 and A2) close. These contacts are rated to 15 amps, 250 V. To reset the
boiler, push the red lockout button.

Wiring procedure 1. Determine right or left electrical supply wiring.


Figure 4
2. Attach electrical junction box(es) to inside jacket end
panel. Screws and nuts are provided. For dual base Junction box assembly
boilers, use offset nipples (provided) to connect junction dual base boilers
boxes together (as at right), then hang junction boxes
by screwing top box to boiler jacket. See Figure 4.
3. Attach control transformer(s) to junction box(es).
4. Drill 1/8” hole in interior jacket panel midway between
ignition control panel and left jacket panel. Mount wire
support clip using sheet metal screw (furnished).
5. Complete wiring per diagrams, Figure 3 (pages 6 and 7)
and Figure 5 (page 9). Terminate at secondary gas valve
in valve junction box with wirenuts and strain relief
provided.
“Hot” side of line voltage to boiler
must be wired directly to limit
circuit, then fed to transformer
primary(ies).
Dual Base: “R” terminal of
secondaries are to supply power to
bases independently of each other.
Do not wire “R” terminals together.
6. Install pilot proving and main flame proving ground
connections as shown in Figures 1 and 2 and wiring
diagram. Route wires through wire support clip.

8 Part Number 550-141-815/0314


CSD-1 Control System - Natural gas

Figure 5

Field wiring diagram

Part Number 550-141-815/0314 9


LGB-6 to LGB-20  Series 2 – Control Supplement

V Leak test procedure

1. Remove red (MV) and blue (PV) wires from main gas valve.
2. Close main test firing valve attached to the manifold.
3. Check that both leak test valves are closed and remove plugs.
4. Attach manometer to first leak test valve.
5. Open first leak test valve and check for pressure.
6. Close first leak test valve and remove manometer.
7. Attach manometer to second leak test valve.
8. Apply call for heat to boiler.
9. Check that electronic pilot proves.
10. Open second leak test valve and check for pressure.
11. Close second leak test valve and remove manometer.
12. Remove call for heat to boiler.
13. Reinstall plugs on leak test valves.
14. Connect wiring to main gas valve.
15. Open main test firing valve attached to the manifold.

When checking for pressure at the leak test valves, any small pressure
reading is normal. If the pressure continues to increase after opening the
leak test valve, the upstream valve is leaking and should be replaced.

10 Part Number 550-141-815/0314


CSD-1 Control System - Natural gas

VI Operating instructions
A. This boiler is equipped with an ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the boiler area for gas. Be
sure to smell next to the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electric switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Do not use this appliance if any part has been under water. Im
mediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any gas
control, which has been under water.

This document is intended only as a supplement to the LGB Gas-Fired


Boiler Manual. Follow all instructions in the Manual, including those
regarding start-up (found in Section 8, “Placing boiler in operation”).

Starting boiler 1. STOP! Read the safety information above.


2. Set the Operating control to lowest setting.
3. Turn off all electrical power to the appliance.
4. Remove Front panel.
5. This appliance is also equipped with an ignition device which automatically lights the
second pilot. Do not try to light this pilot by hand.
6. Close the Pilot shut-off valve connected to the Manual main shut-off valve. Close the
Manual main shut-off valve.
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If
you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas,
go to the next step.
8. Open the Pilot shut-off valve. Open the Manual main shut-off valve.
9. Turn on all electric power to the appliance.
10. Set Operating control to desired setting.
11. If the appliance will not operate, turn off gas to the boiler by closing the Pilot shut-off
valve and the Manual main shut-off valve. Turn off all electrical power. Call your service
technician or gas supplier.
12. Replace Front panel.

Part Number 550-141-815/0314 11


LGB-6 to LGB-20  Series 2 – Control Supplement

VII Parts
list
Figure 6

Item No. Description Size Supplier/Part Number Weil-McLain Part Number


1 Main flame sensor Honeywell 392956 511-724-274
Main burner with pilot bracket Weil-McLain 512-200-055
2
Main flame sensor bracket Weil-McLain 423-300-420
1" Kinco-Balon 500 511-246-325
1 ¼" Kinco-Balon 600 511-246-330
3 Manual main shut-off valve
1 ½" Conbraco 50-603 511-246-300
2" Conbraco 50-703 511-246-305
1" Honeywell V8943A1003 511-044-191
4 Secondary gas valve 1 ¼" Honeywell V8943A1111 511-044-192
1 ½" Honeywell V8943A1129 511-044-193
1" Honeywell V8944N1053 511-044-214
5 Main gas valve 1 ¼" Honeywell V8944N1061 511-044-215
1 ½" Honeywell V8944N1079 511-044-216
Main burner with pilot bracket Weil-McLain 512-200-055
6
Pilot burner bracket Weil-McLain 460-005-624
7 Pilot proving module United Technologies 1003-615 511-330-086
8 Main flame proving module United Technologies 1003-60A 511-330-085
9 Impulse relay Potter-Brumfield S89R-11ABD1-24 510-350-226
Honeywell AML21CBA2AA
10 Push-button switch 511-624-580
Eaton Controls 221K11810
Honeywell AML51-C10R
11 Lens cover 511-624-581
Eaton Controls 220PM02A
12 Light bulb TI-¾ #85 (Available at Local Supply House)
Honeywell V8046C1014
13 Pilot solenoid 511-044-039
Johnson Controls H91ABG
14 Pilot shut-off valve Kinco-Balon P2R 511-246-340
15 Pilot Regulator Maxitrol RV20L 510-933-195
Johnson Controls Q90GE-1
16 Pilot burner 511-330-164
Beckett Gas E48A1
1" Watts 1 FBV-3C 511-246-290
17 Firing valve 1 ¼" Watts 1 ¼ FBV-3C 511-246-282
1 ½" Watts 1 ½ FBV-3C 511-246-294
18 Leak test valve Kinco-Balon P2R 511-246-340
19 Pilot tubing, alum. ¼ O.D. x .032-20" long (Available at Local Supply House)
*Contact local Weil-McLain distributor/agent for current replacement part and order number.

12 Part Number 550-141-815/0314

You might also like