To Be Verified From Soil Report To Be Verified From Soil Report
To Be Verified From Soil Report To Be Verified From Soil Report
To Be Verified From Soil Report To Be Verified From Soil Report
SECTION
ELEMENTS TO BE CHECKED REMARKS
DATA
1.0 GEOTECHNICAL DATA
1.1 SOIL INVESTIGATION RESULT Provided, under review
1.2 PROPOSED TYPE OF FOUNDATION Pile
1.3 BUILDING LOCATION Swampy, water logged
1.4 WATER TABLE To be verified from soil report
1.5 SOIL BEARING CAPACITY / PILE CAPACITIES To be verified from soil report
1.6 WIND TUNNEL TEST IF ANY Not Applicable
1.7 THIRD PARTY REPORT IF ANY
1.8 ARCHITECTURE DRAWINGS Provided, Under Review
1.9 WIND PARAMETERS Expert verification Required
1.10 SEISMIC PARAMETERS
1.11 GRADE OF CONCRETE OK
1.12 GRADE OF STEEL 360N/mm specified, 460N/mm2
2
recommended
LOADING
DEAD LOAD, DL Concrete desnsity of 26kN/m3
specified. OK
LIVE LOAD, LL OK
WIND LOAD, W Wind Pressure of 0.58kN/m2
specified .Expert verification
required
SEISMIC LOAD, E Not Available
UPLIFT LOAD Not Available
TEMPERATURE T Not applicable
LOAD COMBINATIONS
ULTIMATE LIMIT STATE No calculation sheet provided,
could not be verified
SERVICEABILITY LIMIT STATE No calculation sheet provided,
could not be verified
SPECIAL COMBINATIONS
ANALYSIS / DESIGN
APPROPRIATE CODES AND STANDARDS HAVE BEEN
EMPLOYED