Altistart 48 - ATS48C21Q
Altistart 48 - ATS48C21Q
Altistart 48 - ATS48C21Q
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product Altistart 48
Product or component type Soft starter
Product destination Asynchronous motors
Product specific application Heavy duty industry and pumps
Device short name ATS48
[Us] rated supply voltage 230...415 V (- 15...10 %)
Motor power kW 55 kW at 230 V (connection in the motor supply line) for standard applications
90 kW at 230 V (connection to the motor delta terminals) for severe applications
90 kW at 400 V (connection in the motor supply line) for severe applications
110 kW at 230 V (connection to the motor delta terminals) for standard applications
110 kW at 400 V (connection in the motor supply line) for standard applications
132 kW at 400 V (connection to the motor delta terminals) for severe applications
160 kW at 400 V (connection to the motor delta terminals) for standard applications
45 kW at 230 V (connection in the motor supply line) for severe applications
Power dissipation in W For severe applications 468 W
For standard applications 580 W
Utilisation category AC-53A
Type of start Start with torque control (current limited to 5 In)
IcL starter rating 210 A (connection in the motor supply line) for severe applications
364 A (connection to the motor delta terminals) for severe applications
364 A (connection to the motor delta terminals) for standard applications
210 A (connection in the motor supply line) for standard applications
IP degree of protection IP00
Complementary
Assembly style With heat sink
Function available External bypass (optional)
Supply voltage limits 195...456 V
Supply frequency 50...60 Hz (- 5...5 %)
Network frequency 47.5...63 Hz
Device connection In the motor supply line
To the motor delta terminals
Factory setting current 195 A
[Uc] control circuit voltage 220 - 15 % to 415 + 10 %, 50/60 Hz
Control circuit consumption 50 W
Environment
Electromagnetic compatibility Conducted and radiated emissions conforming to IEC 60947-4-2 level A
Damped oscillating waves conforming to IEC 61000-4-12 level 3
Electrostatic discharge conforming to IEC 61000-4-2 level 3
Immunity to electrical transients conforming to IEC 61000-4-4 level 4
Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3 level 3
Voltage/Current impulse conforming to IEC 61000-4-5 level 3
Standards EN/IEC 60947-4-2
Product certifications CCC
CSA
C-Tick
DNV
GOST
NOM 117
SEPRO
TCF
UL
Vibration resistance 1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27
2
Noise level 54 dB
Pollution degree Level 3 conforming to IEC 60664-1
Relative humidity 0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation 40...60 °C with current derating of 2 % per °C
-10...40 °C without derating
Ambient air temperature for storage -25...70 °C
Operating altitude <= 1000 m without derating
> 1000...2000 m with current derating of 2.2 % per additional 100 m
Contractual warranty
Warranty period 18 months
3
Product data sheet ATS48C21Q
Dimensions Drawings
Dimensions
4
Product data sheet ATS48C21Q
Mounting and Clearance
Clearance