User Manual
CPC 100 PTM User Manual
2 OMICRON
Contents
Contents
About this manual 6
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Conventions and symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1 Safety instructions 8
1.1 Operator qualifications and safety standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 Orderly measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Disclaimer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3.1 Automatic assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 System requirements 10
3 Introduction 11
3.1 The test set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Installing Primary Test Manager. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Starting Primary Test Manager and connecting to the CPC 100 . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3.1 Starting via the PTM icon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3.2 Starting via the CPC Start Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3.3 Connecting to the CPC 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3.4 Updating the CPC 100 embedded software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3.5 Open the device web interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Primary Test Manager licensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 Home view 17
4.1 Title bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.2 Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.1.3 About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Status bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.2.1 Connecting to a test system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.2.2 Manual connection to a test system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3 Data backup and restoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.4 Data synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4.1 Server settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4.2 Managing subscriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.4.3 Database synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5 Jobs 34
5.1 Guided test workflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2 Job overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.2.1 Job data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.2.2 Approving jobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.3 Assessment summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.4 Managing attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.3 Location view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.3.1 Location data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.2 Setting the geo coordinates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.3.3 Managing attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4 Asset view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.4.1 General asset data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.4.2 Managing attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.4.3 Transformer view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.4.4 Spare bushing view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.5 Circuit breaker view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
OMICRON 3
CPC 100 PTM User Manual
4 OMICRON
Contents
OMICRON 5
CPC 100 PTM User Manual
Related documents
The following documents complete the information covered in this manual.
Title Description
CPC 100 User Manual Contains safety and operation instructions on the CPC 100
test system.
CPC 100 Reference Manual Contains detailed hardware and software information on the
CPC 100 including relevant safety instructions.
CP TD1 Reference Manual Contains hardware and software information about the
CP TD1 test system.
CP SB1 User Manual Contains hardware and software information about the
CP SB1 transformer switch box.
6 OMICRON
About this manual
DANGER
Death or severe injury will occur if the appropriate safety instructions are not observed.
WARNING
Death or severe injury can occur if the appropriate safety instructions are not observed.
CAUTION
Minor or moderate injury may occur if the appropriate safety instructions are not
observed.
NOTICE
Equipment damage or loss of data possible
OMICRON 7
CPC 100 PTM User Manual
1 Safety instructions
Before operating Primary Test Manager and the test set, read the following safety instructions carefully.
When testing with Primary Test Manager, observe the safety rules in this chapter and all relevant safety
instructions in the technical documentation shipped with the test systems. Do not turn on or operate the
CPC 100 if you do not fully understand the safety information. If you have any questions regarding the
safety instructions, contact OMICRON before proceeding.
Before connecting any test leads to a test object, always observe the five safety rules:
► Disconnect completely
► Secure from reconnection
► Verify that the installation is dead
► Carry out grounding and short-circuiting
► Provide protection against adjacent live parts
Safety accessories
OMICRON offers a range of accessories for added safety during the operation of our test systems. For
further information and specifications, refer to the corresponding Supplementary Sheet or contact
OMICRON Support (see "Support" on page 13).
8 OMICRON
Safety instructions
1.3 Disclaimer
1.3.1 Automatic assessment
The applied auto-assessment rules (for example, indicated colors, indications) and limits within the
Program are defined according to industry standards and/or are based on the experience of industry
experts. The purpose of the auto-assessment is to indicate to the person that uses the Program – "User"
any deviation of the measured parameters from the expected values based on the recommended limits
provided by OMICRON or defined by the User. Any decision to return the apparatus to service or remove
the apparatus from service cannot be based on the results of the auto-assessment alone. This decision
is the sole responsibility of the owner or end user of the apparatus.
1.3.2 Safety
If Primary Test Manager and the test set are used in a manner not specified by the manufacturer, the
protection provided by the test systems may be impaired.
OMICRON 9
CPC 100 PTM User Manual
2 System requirements
Table 2-1: Primary Test Manager system requirements
10 OMICRON
Introduction
3 Introduction
Primary Test Manager is a management tool for testing primary assets such as power transformers,
circuit breakers, and current transformers with the OMICRON test systems. Primary Test Manager
provides a computer interface to the test set, controls the automated test procedures, and facilitates
testing of primary assets by guiding you through the test workflow.
Primary Test Manager uses the concept of jobs. A job contains all relevant information about the
location, the asset under test, and the tests. With Primary Test Manager, you can process jobs as
separate entities.
With Primary Test Manager, you can create new jobs, manage locations, assets, jobs, and reports, and
execute prepared jobs. For a specified job, you can make measurements on the asset under test by just
pressing the I/0 button on the front panel of the CPC 100 test system. After you have performed a test,
you can generate exhaustive test reports. Primary Test Manager runs on a computer and communicates
with the test set through the Ethernet connection.
OMICRON 11
CPC 100 PTM User Manual
I/0 button
Network connector
For detailed information about the test set, see the technical documentation shipped with the CPC 100,
CP TD1, and CP SB1 test systems.
12 OMICRON
Introduction
OMICRON 13
CPC 100 PTM User Manual
2. On the CPC start page, select the CPC 100 device to which you want to connect.
3. Under Tools, click Primary Test Manager.
14 OMICRON
Introduction
If you were not able to connect to your CPC 100 device and the green light is permanently on, wait a few
seconds, and then do one of the following:
► Click More (under the Connect button), then click Refresh.
► Press F5.
If the CPC 100 device to which you want to connect is not displayed in the list of available devices,
proceed as described in4.2.2 "Manual connection to a test system" on page 29.
Alternatively, you can manage the connection to CPC 100 in the Primary Test Manager status bar (see
4.2 "Status bar" on page 28).
OMICRON 15
CPC 100 PTM User Manual
License Description
PTM Standard Manual control mode with tests according to your CPC 100 license.
Additional 30 testing days with guided workflow according to your
CPC 100 license.
PTM Advanced Timely unlimited testing with guided workflow and manual tests according
to your CPC 100 license.
The PTM Advanced license key is on the CPC 100. You need to upgrade your CPC 100 on the CPC
start page (see Figure 3-3: "CPC start page" on page 14).
For detailed information, contact your OMICRON local sales representative or distributor.
16 OMICRON
Home view
4 Home view
After starting Primary Test Manager, the home view opens. In the home view, you can select different
user tasks designed to support you during diagnostic testing and management of test objects and test
data.
Primary Test Manager processes data of different workflow importance. This is indicated by balloons of
different categories as described in the following table.
OMICRON 17
CPC 100 PTM User Manual
18 OMICRON
Home view
Command Action
Home Click Home to move from any view to the home view.
Synchronize1 Click Synchronize to synchronize your local database with the Primary
Test Manager server database
(see 4.4 "Data synchronization" on page 31).
Settings Click Settings to open the Settings dialog box
(see 4.1.1 "Settings" later in this chapter).
Help Click Help to open the CPC 100 technical documentation and send data
to OMICRON Technical Support
(see 4.1.2 "Help" on page 27).
About Click About to open the About Primary Test Manager dialog box
(see 4.1.3 "About" on page 27).
1. Only enabled with the appropriate license.
4.1.1 Settings
In the Settings dialog box, you can make a number of Primary Test Manager settings to match your
regional conventions, manage the job templates, and set the Primary Test Manager server settings for
data synchronization (see 4.4 "Data synchronization" on page 31). To open the Settings dialog box,
click Settings in the title bar.
NOTICE
Equipment damage or loss of data possible
Changing the settings in the Settings dialog box affects all data in Primary Test Manager.
► Only change settings if you are qualified to do so.
► Review your changes before clicking OK.
Note: After changing a setting, you must restart Primary Test Manager for the setting to take effect.
OMICRON 19
CPC 100 PTM User Manual
General
The General tab lists the general settings of Primary Test Manager.
► To set the Primary Test Manager language, select your preferred language from the Language list.
► To set the logging level, select your preferred level from the Logging PTM and Logging Device lists.
The logging function provides information to help find the cause for an error in cooperation with an
OMICRON support engineer. Logging PTM collects information on PTM while Logging Device
focuses on your device.
Note: Log files do not contain any personal information.
► To set the types of available devices, select the respective check boxes.
Under Location settings, you can activate the Use location information check box for Grounding
system tests (see 19 "Grounding system tests" on page 192).
20 OMICRON
Home view
Under Default test device configuration, Primary Test Manager displays the default devices for testing
different assets. If more than one device is available for an asset, you can set your preferred test system
as default device for that asset.
Note: If no device is connected, Primary Test Manager will automatically compile the test list (see
section 5.5 "Test view" on page 59) for the selected default test set.
The Customer Experience Improvement Program collects information about how you use Primary
Test Manager without interrupting you. This helps OMICRON identify which features to improve. No
information collected is used to identify or contact you. We encourage you to join the program to help
improve Primary Test Manager.
Profiles
In the Profiles tab, you can set your profile, the default rated frequency, the loss index, the units of your
own profiles, and make the test system settings.
With Primary Test Manager, you can use predefined profiles and create your own profiles for naming
conventions.
Note: Primary Test Manager sets the default profile according to the regional settings of your computer.
► To set a profile, select the profile you want to use from the Profiles list.
To create your own profile:
1. Click Create custom profile.
2. In the Create custom profile dialog box, type the profile name, and then click Create.
3. Under Global settings, set the default rated frequency, the loss index, and your preferred units.
OMICRON 21
CPC 100 PTM User Manual
Profiles: Transformer
4. Under Transformer, set the transformer terminal name schemes and preferences such as the
names of some tests, the oil measure, and the short-circuit impedance abbreviation.
With Primary Test Manager, you can use predefined transformer naming conventions according to the
established standards and create your own terminal name schemes.
► To set a terminal names scheme, select the scheme you want to use from the
Terminal names scheme list.
To create your own terminal names scheme:
a) Click Create custom scheme.
b) In the Enter scheme name dialog box, type the scheme name.
c) Set the transformer terminal names, scheme options, and preferences.
► To delete your own terminal name scheme, select the scheme from the Terminal names scheme
list, and then click Delete current scheme.
22 OMICRON
Home view
OMICRON 23
CPC 100 PTM User Manual
24 OMICRON
Home view
Templates
In the Templates tab, you can edit, import and export job templates for transformers.
► For information on how to process the templates, see 5.5.4 "Processing templates" on page 68.
The right pane of the template workspace displays the template preview.
To manage the job templates, select Transformer from the Display templates for list, and then do one
of the following:
► To assign a template to a different asset type or a phase group, or to edit template properties (name,
comment), click the respective Edit button.
► Press the Delete button to delete templates from the Asset type or Phases list.
► To export a template, select the template, and click the Export button.
► To import a template, click the Import button, then browse to the template you want to import.
► To set a template as favorite, click the star icon .
Note: All future test lists with the same asset and number of phases will by default be loaded with the
tests defined in this favorite template.
OMICRON 25
CPC 100 PTM User Manual
Databases
In the Databases tab you can create, manage and switch between different databases for Primary Test
Manager. Under Properties, you can edit the database name and adjust the server settings for
DataSync. For more information, see 4.4.1 "Server settings" on page 31.
26 OMICRON
Home view
4.1.2 Help
In the Help dialog box, you can get the relevant information about CPC 100 and data synchronization,
and send data to OMICRON Technical Support. To open the Help dialog box, click Help in the title bar.
4.1.3 About
In the About Primary Test Manager dialog box, you can enter a license key to upgrade your Primary
Test Manager and enhance its functionality by installing additional features. To open the
About Primary Test Manager dialog box, click About in the title bar.
OMICRON 27
CPC 100 PTM User Manual
To activate a license, enter the license key in the About Primary Test Manager dialog box, and then
click Add license key. For detailed information about the Primary Test Manager licensing, contact your
OMICRON local sales representative or distributor.
CP SB1 connected
CP TD1 connected
In the status bar, you can connect to and disconnect from a test system, and show and refresh the test
set information.
2. In the Connect to device dialog box, select the test system from the list, and then click Connect.
28 OMICRON
Home view
If you could not connect to your CPC 100 device and the green light is permanently on, wait a few
seconds, and then proceed as follows:
1. Click More beneath the Connect button.
2. Click Refresh.
3. In the Connect to device dialog box, select the test system from the list, and then click Connect.
After you have connected to the test system, the following dialog box appears.
After you have connected to a test system, right-click the CPC 100 icon in the status bar, and then do
one of the following:
► To disconnect from a test system, click Disconnect.
► To display information about the connected test system, click Show test set information.
► To update the test set information, click Refresh test set information.
Note: You can open the Connect to device and the Connected to device dialog boxes also by double-
clicking the CPC 100 icon.
OMICRON 29
CPC 100 PTM User Manual
2. In the Host or IP box, type cpc://a.b.c.d, where a.b.c.d is the static IP address of the device.
30 OMICRON
Home view
OMICRON 31
CPC 100 PTM User Manual
DataSync on premises
► For the service URL and certificate for DataSync on premises, contact your system administrator.
2. In the Databases tab, enter the Service URL and upload the Certificate.
3. To test the connection to the server, click Test next to the Connection status.
2. In the manage view, click Manage subscriptions on the top of the workspace.
3. In the Subscriptions dialog box, select the data on the server you want to synchronize with your local
data.
You can synchronize the data anytime.
► To synchronize the data, click Synchronize in the title bar.
After that, Primary Test Manager shows the synchronization progress.
32 OMICRON
Home view
OMICRON 33
CPC 100 PTM User Manual
5 Jobs
When creating a new job, Primary Test Manager leads you through the guided test workflow. To open
the create new job view, click the Create new job button in the home view.
In the create new job view, you can configure and execute jobs. A job contains all relevant information
about the location, the asset under test, and the tests. With Primary Test Manager, you can process jobs
as separate entities. During the guided test workflow, the job status displayed in the left pane of the
create new job view changes. The following table describes the job statuses.
Status Description
New Location has been defined.
Prepared Asset has been defined.
Partially executed At least one measurement has been executed.
Executed All tests of the job have been executed.
Approved Job has been approved.
34 OMICRON
Jobs
Note: You can anytime interrupt the test workflow and return to any view by clicking the corresponding
navigation button.
By using the commands on the menu bar, you can process jobs. The following table describes the
available operations.
Command Action
Close Closes a job displayed in the create new job view and leads you back to
home or manage view respectively.
Save job Saves the job displayed in the create new job view.
Copy test Adds another test of the same kind and with the same settings to the test
list. Results are not copied.
Take screenshot Takes screenshot of the selected area of the Primary Test Manager
workspace. The screenshot appears as attachment in the General area
and can be attached to the test report (see 11 "Generate test reports" on
page 86).
For more information about operations on the jobs, see 7 "Manage objects" on page 75.
OMICRON 35
CPC 100 PTM User Manual
Data Description
Name/WO1 Name of the job or work order
(by default generated by Primary Test Manager)
Creation date Date the job was created
Execution date Date the job was executed
Tested by Person who performed the test
Approved by Person who approved the test
Approval date Date the job was approved (see 5.2.2 "Approving jobs" later in this
section)
1. Mandatory data
36 OMICRON
Jobs
Status Description
Fail The status was automatically set to Fail by Primary Test Manager.
Manual fail The status was manually set to Fail.
Investigate The status was automatically set to Investigate by Primary Test
Manager.
Manual investigate The status was manually set to Investigate.
Pass The status was automatically set to Pass by Primary Test Manager.
Partial pass Some measurements have not been assessed.
Manual pass The status was manually set to Pass.
Manual partial pass Some measurements have not been assessed and at least one
assessment status was changed manually.
Not assessed The measurement has not been assessed.
Not rated The status was automatically set to Not Rated by Primary Test
Manager.
OMICRON 37
CPC 100 PTM User Manual
38 OMICRON
Jobs
In the Select Location dialog box, you can search for locations (see 7.1 "Search for objects" on
page 76).
Data Description
Name1 Name of the location
Region Region where the asset is located
Division Division where the asset is located
Area Area where the asset is located
Plant Plant where the asset is located
OMICRON 39
CPC 100 PTM User Manual
Data Description
Address Address of the location
City City where the asset is located
State/Province State or province where the asset is located
Postal code Postal code of the location
Country Country where the asset is located
Geo coordinates Geo coordinates of the location
(see 5.3.2 "Setting the geo coordinates" later in this section)
Location system code Location code used by maintenance planning systems
Contact Person
Name Name of the contact person
Phone no. 1 Phone number of the contact person
Phone no. 2 Alternative phone number of the contact person
E-mail E-mail address of the contact person
Company
Company Company where the asset is located
Department Department of the company
Address Address of the company
City City where the company is located
State/Province State or province where the company is located
Postal code Postal code of the company
Country Country where the company is located
Phone no. Phone number of the contact person
Fax no. Fax number of the contact person
E-mail E-mail address of the contact person
1. Mandatory data
In the location view, you can enter additional addresses of, for example, a client, owner or utility. To enter
additional addresses, click Add address under Additional addresses. For the additional address data,
see Table 5-5: "Location data" on page 39.
40 OMICRON
Jobs
2. In the Edit Coordinates dialog box, enter the latitude and longitude of the location.
OMICRON 41
CPC 100 PTM User Manual
The asset view depends on the asset you want to specify with Primary Test Manager. To specify an
asset, do one of the following:
► Enter the asset data. The asset data includes the general asset data common to all assets (see
5.4.1 "General asset data" on page 43 and the asset-specific data described in chapter 12 "Asset
data" on page 88).
Note: If you enter location or asset data for a prepared job that differ from those of the master location
or master asset, a notification bar will be displayed. In this case, choose between the following options:
► To import the previously defined location or asset data to this job, click Import from master
location or Import from master asset in the notification bar.
► To update the previously defined location or asset data with the data you have entered for this job,
click Update master location or Update master asset in the notification bar.
► For more information on operations on the jobs, see 7 "Manage objects" on page 75.
42 OMICRON
Jobs
► To load the asset data available in Primary Test Manager, click Load existing asset, and then select
the asset you want to load in the Select Asset dialog box.
In the Select Asset dialog box, you can search for assets (see 7.1 "Search for objects" on page 76) and
sort them alphabetically or in the chronological order.
Data Description
Asset1 Asset under test
Asset type Type of the asset
Serial no.1 Serial number of the asset
Manufacturer Manufacturer of the asset
Manufacturer type Type of the asset according to the manufacturer
Manufacturing year Year of the asset’s manufacturing
Asset system code Code of the asset used by the maintenance planning systems
Apparatus ID Identifier of the asset
Feeder Feeder the asset is connected to
Phase2 Phase the asset is connected to
1. Mandatory data
2. Only available for current transformers, voltage transformers and miscellaneous assets.
OMICRON 43
CPC 100 PTM User Manual
3. In the transformer view, enter the general asset data (see Table 5-6: "General asset data" on
page 43).
44 OMICRON
Jobs
4. Under Winding configuration, set the transformer’s vector group (see "Setting the vector group"
later in this section).
5. Under Ratings, Impedances and Others, enter the transformer data (see 12.1 "Transformer" on
page 88).
6. Optionally, specify the bushing mounted on the transformer (see "Bushings tab (Transformer)" on
page 47).
7. Optionally, specify the tap changers of the transformer (see "Tap changers tab" on page 48).
8. Optionally, specify the surge arresters mounted on the transformer (see "Surge arresters tab" on
page 49).
OMICRON 45
CPC 100 PTM User Manual
Note: Primary Test Manager sets the vector group of an autotransformer without tertiary winding
automatically.
46 OMICRON
Jobs
Specifying a bushing
1. From the Asset type list, select the type of the bushing.
2. Enter the bushing data (see 12.2 "Spare bushing" on page 91).
Under Copy bushing data, you can copy data of a bushing to other bushings. To copy the bushing data,
select the respective bushings from the From and To lists, and then click Copy.
OMICRON 47
CPC 100 PTM User Manual
48 OMICRON
Jobs
OMICRON 49
CPC 100 PTM User Manual
DGA Trending
DGA Trending is a licensed feature that visualizes a transformer’s historic Oil analysis data in various
charts and offers a comparison of data recorded at different points in time.
► Refer to 13.1.1 "Oil analysis" on page 105 for more detailed information on the Oil analysis test.
3. In the spare bushing view, enter the general asset data (see Table 5-6: "General asset data" on
page 43).
4. Enter the spare bushing data (see 12.2 "Spare bushing" on page 91).
50 OMICRON
Jobs
3. In the circuit breaker view, enter further general asset data (see Table 5-6: "General asset data" on
page 43).
4. In the Circuit breaker area, enter the circuit breaker data (see 12.3 "Circuit breaker" on page 92).
5. Specify the operating mechanism of the circuit breaker (see "Operating mechanism tab" on page 52).
6. Optionally, specify the bushings mounted on the circuit breaker (see "Bushings tab (Circuit breaker)"
on page 53).
7. Set the assessment limits of the circuit breaker (see "Assessment limits tab" on page 54).
OMICRON 51
CPC 100 PTM User Manual
To specify an operating mechanism, enter the operating mechanism data (see 12.3.1 "Operating
mechanism" on page 93).
52 OMICRON
Jobs
To specify a bushing:
1. From the Asset type list, select the type of the bushing for all circuit breaker’s terminals.
2. Enter the bushing data (see 12.2 "Spare bushing" on page 91).
Under Copy bushing data, you can copy data of a bushing to other bushings. To copy the bushing data,
select the respective bushings from the From and To lists, and then click Copy.
OMICRON 53
CPC 100 PTM User Manual
54 OMICRON
Jobs
2. In the current transformer view, enter the general asset data (see Table 5-6: "General asset data"
on page 43).
3. Enter the current transformer data (see 12.4 "Current transformer" on page 96).
OMICRON 55
CPC 100 PTM User Manual
3. In the voltage transformer view, enter the general asset data (see Table 5-6: "General asset data"
on page 43).
56 OMICRON
Jobs
3. In the rotating machine view, enter the general asset data (see Table 5-6: "General asset data" on
page 43).
4. In the Configuration area and the Ratings area, enter the rotating machine data (see 12.6 "Rotating
machine" on page 102).
OMICRON 57
CPC 100 PTM User Manual
2. In the miscellaneous view, enter the general asset data (see Table 5-6: "General asset data" on
page 43).
58 OMICRON
Jobs
OMICRON 59
CPC 100 PTM User Manual
For example, if the CPC 100 is connected to your computer and you configured a job with tests for the
CPC 100 and the CIBANO 500 as shown in the following figure, the symbol left next the
CIBANO 500 tests indicate that you must connect the CIBANO 500.
Figure 5-24: Job configured with test for the CPC 100 and the CIBANO 500 test systems
60 OMICRON
Jobs
If you, for example, try to perform a test for the CIBANO 500 with CPC 100 connected, a warning
message appears.
Figure 5-25: Warning message when trying to perform a test for the CIBANO 500
The optional manual tests are asset-independent. You can perform the tests for any asset described in
this User Manual, but Primary Test Manager does not guide you through the tests and provides no test
settings data. These tests offer a large amount of flexibility to define test procedures and specify test
settings according to your specific needs. For more information about the manual tests, see 8 "Create
new manual tests" on page 81.
The Selected tests area displays the tests you want to perform. By default, Primary Test Manager
displays the tests recommended by OMICRON. To add a test into the Selected tests area, click the
symbol next to the test name in the Available tests area. To add all tests of a category into the
Selected tests area, click the symbol. The Selected tests area displays the test to be performed in
the recommended order. You can change the order of the tests by dragging them or by using the and
symbols. To remove a test from the Selected tests area, click the symbol next to the test name.
The General test settings area displays the reason of the job, the global test conditions, and some asset
specific data.
OMICRON 61
CPC 100 PTM User Manual
You can also import tests in JPG, PDF and any Microsoft Office file format.
To import test data:
1. In the Selected tests area, click Add from file.
2. In the Open dialog box, browse to the file you want the import.
3. In the left pane of the test view, click the imported test.
4. In the workspace of the test view, you can change the test title and the test type.
62 OMICRON
Jobs
5. To open the test, click the Open button under Test data.
Note: To open a test, you must have installed the associated application software on your computer.
6. You can attach files as described earlier in this chapter and add comments to the test.
For information about importing and exporting jobs, see 7.6 "Import and export jobs" on page 80.
OMICRON 63
CPC 100 PTM User Manual
4. In the Assessment pane, enter the automatic assessment parameters and limits, if applicable.
64 OMICRON
Jobs
5. Connect the test setup to the asset under test according to the wiring diagram displayed in the
General pane. For information about connecting the test setup to the asset under test, see the
technical documentation shipped with the CPC 100, CP TD1, and CP SB1 test systems.
DANGER
Death or severe injury caused by high voltage or current
► Before connecting the test set to the test object, observe the five safety rules listed in
1 "Safety instructions" on page 8.
► Observe the relevant laws and internal safety standards.
OMICRON 65
CPC 100 PTM User Manual
DANGER
Death or severe injury caused by high voltage or current
The flashing lightning symbol in the Primary Test Manager test view indicates that an
output of the CPC 100 is active.
► Do not touch any of the CPC 100’s outputs or cables while the lightning symbol is
displayed.
► If in doubt, press the Emergency Stop button.
66 OMICRON
Jobs
7. Press the I/0 button on the front panel of the CPC 100.
After the measurement has been finished, Primary Test Manager displays the numeric measurement
data and the automatic assessment, if available, in the Measurements pane. To view graphical diagrams
of the measurement results, click the Plot tab.
8. Repeat steps 6 and 7 for all test measurements.
Note: Some tests support starting all measurements at once by clicking the Start all button.
Note: After the test has been performed some asset data relevant for the test configuration cannot be
edited anymore.
OMICRON 67
CPC 100 PTM User Manual
68 OMICRON
Jobs
To open a template:
1. In the Selected tests area of the test view, click Open template.
2. In the Choose Template dialog box, select the asset type, the number of phases and the template
you want to open.
Note: If you added a Microsoft Excel report template to the job template, its location is displayed
under Customized Excel report template.
3. Press Replace existing testplan to replace the tests already listed in the test list.
Press Append to existing testplan to add the tests listed in the template to the end of the existing
testplan.
Note: If you click Append to existing testplan, the Microsoft Excel report template will not be added
the selected job template to the currently opened job.
OMICRON 69
CPC 100 PTM User Manual
In the chart, measurements performed with 10 kV at rated frequency are displayed as circles . All other
data are displayed as triangles .
Note: If several tests are performed on one day, the most recent test of that day is connected to the
curve in the Trending chart. The others are displayed in the same chart but are not connected.
Status Description
Fail The status was automatically set to Fail by Primary Test Manager.
Manual fail The status was manually set to Fail.
Investigate The status was automatically set to Investigate by Primary Test
Manager.
Manual investigate The status was manually set to Investigate.
Pass The status was automatically set to Pass by Primary Test Manager.
Manual pass The status was manually set to Pass.
Not assessed The measurement has not been assessed.
Not rated The status was automatically set to Not Rated by Primary Test
Manager.
70 OMICRON
Jobs
1. In the home view (see 4 "Home view" on page 17), click the Create new job button .
2. In the Create new job view, configure a job as described earlier in this chapter.
3. In the test view (see 5.5 "Test view" on page 59), select the test you want to perform.
4. In the Measurements pane, click the + Select comparison button, if available.
5. In the Select a test window, select the test you want to compare with the current test.
OMICRON 71
CPC 100 PTM User Manual
6. The Measurements pane displays the measurement results of the selected test.
72 OMICRON
Jobs
9. Primary Test Manager displays the measurement results of both tests in real time.
OMICRON 73
CPC 100 PTM User Manual
2. In the execute prepared job view, click Open job from file.
3. In the Open dialog box, browse to the .ptm file you want to import.
4. Import the job, and then go through the guided test workflow (see 5 "Jobs" on page 34).
To execute a prepared job available in Primary Test Manager:
1. In the home view, click the Execute prepared job button .
2. In the execute prepared job view, search for the job you want to execute (see 7.1 "Search for objects"
on page 76).
3. Open the job, and then go through the guided test workflow (see 5 "Jobs" on page 34).
74 OMICRON
Manage objects
7 Manage objects
In the manage view, you can manage locations, assets, jobs, and reports available in Primary Test
Manager. After you have opened a job, Primary Test Manager leads you through the guided test
workflow (see 5 "Jobs" on page 34). To open the manage view, click the Manage button in the home
view.
Note: In this chapter, the locations, assets, jobs, and reports are collectively called objects.
Note: The mounted assets are displayed in italics. To hide them, expand the Search area under Asset,
and then select the Hide mounted assets check box.
The manage view displays the objects in a hierarchical structure as follows:
• If you select a location, the manage view displays the assets, jobs, and reports associated with the
selected location.
• If you select an asset, the manage view displays the jobs and reports associated with the selected
asset.
• If you select a job, the manage view displays the reports associated with the selected job.
You can sort the objects alphabetically or in the chronological order.
► Drag and drop the column headers to rearrange the columns.
OMICRON 75
CPC 100 PTM User Manual
Data Description
Name Name of the location
Address Address of the location
City City where the asset is located
State/Province State or province where the asset is located
Postal code Postal code of the location
Country Country where the asset is located
Data Description
Asset Asset under test
Asset type Type of the asset
Serial no. Serial number of the asset
Manufacturer Manufacturer of the asset
Manufacturer type Type of the asset according to the manufacturer
Asset system code Code of the asset used by the maintenance planning systems
Apparatus ID Identifier of the asset
76 OMICRON
Manage objects
Data Description
Name/WO Name of the job or work order
Tested by Person who performed the test
Executed between Time period between the job was executed
Status Status of the job
Data Description
Name Name of the report
Client Customer for which the report is designated
Created between Time period between the report was created
OMICRON 77
CPC 100 PTM User Manual
► Click Import from master location or Import from master asset to import the location or asset
originally associated with the job (master location/asset) to the current job.
► Click Update master location or Update master asset to update the location or asset originally
associated with the job (master location/asset) with the data of the current job.
78 OMICRON
Manage objects
3. In the Relocate Asset dialog box, select the location you want to move the asset to.
4. If the asset you want to relocate is mountable, select an asset where the moved asset is to be
mounted.
Note: You can filter the locations and assets by searching for keywords (see 7.1 "Search for objects" on
page 76).
OMICRON 79
CPC 100 PTM User Manual
80 OMICRON
Create new manual tests
The workspace of the create new manual tests view depends on the selected button in the left pane (see
Figure 8-2: "Left-pane buttons" on page 82). Initially, the workspace is divided into the General and
Tests areas.
In the General area, you can manage the connection to the test system as described in4.2.1 "Connecting
to a test system" on page 28.
The Tests area displays all manual tests supported by Primary Test Manager. Only the tests that are
available for the connected test system are active and can be added to a job as described in
chapter 8.1 "Add tests to a job" on page 82. You can open a test at any time by clicking the test in the
left pane. After you opened a test, the workspace is split into the Hardware configuration area, the
Settings and conditions area and the Measurements area.
OMICRON 81
CPC 100 PTM User Manual
If you click the Tests button, the workspace displays the General area and the Tests area again.
Note: You can change the default test names. To rename a test, click the corresponding button in the
left pane, and then click the test name.
Command Action
Close Closes the current job and leads you to the Primary Test Manager home
view. Before closing the job, you can save the changes for all tests.
Save job Saves the current job. When saving for the first time, you must specify the
filename and directory of the job.
Save as Saves the current job in a newly specified directory.
Copy test Adds another test of the same kind and with the same settings to the test
list. Results are not copied.
Delete test Deletes the currently open test.
Note: Clicking Home in the title bar and Close in the menu bar have the same functionality.
82 OMICRON
Open manual tests
OMICRON 83
CPC 100 PTM User Manual
2. In the Open dialog box, browse to the file you want to open.
The open manual tests view displays the tests in the left pane. To view the test results, click the
corresponding test button. You can add new tests and generate test reports as described in 8 "Create
new manual tests" on page 81.
84 OMICRON
Control tests
10 Control tests
In the Measurements area of Primary Test Manager, you can control the test execution. The following
table describes the available commands.
Command Action
Start Starts the selected measurement of the currently open test.
Start all Starts all measurements of the currently open test.
Stop Stops the running measurement.
Stop all Stops all running measurements.
Clear all Deletes all measurement results of the currently open test.
Clear result Deletes the results of the selected measurement.
Delete measurement Deletes the selected measurement row.
Add measurement Adds a new measurement row to the currently open test.
OMICRON 85
CPC 100 PTM User Manual
The report view is divided into the New report area, the Settings area and the Existing reports area.
In the New report area, you can set the report data. The following table describes the report data.
Table 11-1: Report data
Data Description
Title Title of the report. Appears as the report header.
Report language Language the report is created in
Report ID1 Identifier of the report
Client Customer for which the report is designated
Logo Logo to appear in the report
(see "Setting the logo" later in this chapter)
Summary Text field to summarize the content of the test report in own words.
1. By default generated by Primary Test Manager.
86 OMICRON
Generate test reports
OMICRON 87
CPC 100 PTM User Manual
12 Asset data
This section describes the asset specific data.
12.1 Transformer
The following tables describe the transformer data.
Data Description
Phases Number of the transformer’s phases
Vector group Vector group of the transformer
(see "Setting the vector group" on page 46)
Unsupported vector group Vector group not supported by Primary Test Manager as text for
(for documentation) documentation
Data Description
Rated frequency Rated frequency of the transformer
Voltage ratings
Winding Transformer’s winding
Voltage L-L L-L voltage of the transformer’s winding
Voltage L-N L-N voltage of the transformer’s winding
Insul. level L-L (BIL) L-L basic impulse level rating of the transformer’s winding
Power ratings
Rated power Power rating of the transformer
Cooling class Cooling class of the transformer
Temp. rise wind. Temperature rise of the transformer’s winding
Current ratings at rated power
H/X/Y1 Maximum power frequency current of the transformer at rated power
Short-circuit rating
Max. short-circuit current Maximum short-circuit current of the transformer in kA during a given time
in seconds
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
88 OMICRON
Asset data
Data Description
Ref. temp. Reference temperature
Short-circuit impedances H - X1, H - Y1, X - Y1
Short-circuit impedance Short-circuit impedance of the transformer
Z (%)1
Base power Base power used for calculating the percent values of impedances
Base voltage Base voltage used for calculating the percent values of impedances
Load losses Pk Load loss at the transformer’s rated load
OLTC position Tap position of the OLTC
DETC position Tap position of the DETC
Zero sequence impedance
Base power Base power used for calculating the percent values of impedances
Base voltage Base voltage used for calculating the percent values of impedances
Winding Transformer’s winding
Zero sequence Zero sequence impedance of the transformer
impedance Z0 (%)
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
Data Description
Category Application category of the transformer
Status Usage status of the transformer
Tank type Type of the transformer’s tank
Insulation medium Insulation medium of the transformer
Weight Weight of the transformer’s insulation
Insulation
Volume Volume of the transformer’s insulation
Total weight Total weight of the transformer
Winding Transformer’s winding
Conductor material Conductor material of the transformer’s winding
12.1.1 Bushing
For the data of the transformer’s bushings, see 12.2 "Spare bushing" on page 91.
OMICRON 89
CPC 100 PTM User Manual
Data Description
OLTC/DETC Select the OLTC check box to set the OLTC data.
Select the DETC check box to set the DETC data.
Tap changer configuration
Winding Transformer’s winding to which the tap changer is connected
Tap scheme Notation scheme for tap identification
No. of taps Number of the tap changer’s taps
Current tap position1 Current position of the tap
Voltage table
Tap Number of the tap
Voltage Voltage on the tap
1. Only available for the DETC
Data Description
Ratings
Units in stack Number of the surge arrester’s units
Numerical positions Select the Numerical positions check box to set numerical positions of the
surge arrester.
Literal positions Select the Literal positions check box to set alphabetical positions of the surge
arrester.
Position Position of the surge arrester
Serial no. Serial number of the surge arrester
Voltage L-L Values needed to calculate the maximum test voltages
Voltage L-N
MCOV rating Maximum continuous operating voltage between the terminals of the surge
arrester
Unit catalog no. Identifier of the surge arrester unit
90 OMICRON
Asset data
Data Description
Pos.1 Terminal of the transformer’s winding to which the spare bushing is
connected
Ratings
Rated frequency Rated frequency of the spare bushing
Insul. level LL (BIL) L-L basic impulse level rating of the spare bushing
Voltage L-ground Rated line-to-ground voltage
Max. system voltage Maximum voltage between phases during normal service
Rated current Rating current of the spare bushing
Manufacturer info
Catalog no. Catalog number of the spare bushing
Drawing no. Drawing number of the spare bushing
Style no. Style number of the spare bushing
Nominal values
PF (C1)/ Power factor, dissipation factor, or tangent delta of the capacitance C1
DF (C1)/ between the top of the spare bushing and the voltage/test tap
Tanδ (C1)2
Cap. (C1) Capacitance C1 between the top of the spare bushing and the voltage/test
tap
PF (C2)/ Power factor, dissipation factor, or tangent delta of the capacitance C2
DF (C2)/ between the voltage/test tap of the spare bushing and ground
Tanδ (C2)2
Cap. (C2) Capacitance C2 between the voltage/test tap of the spare bushing and
ground
OMICRON 91
CPC 100 PTM User Manual
Data Description
Other
Insulation type Insulation type of the spare bushing
Outer insulation type Outer insulation type of the spare bushing
1. Only available for spare bushings mounted on another assets
2. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
Data Description
Circuit breaker
Number of phases Number of the circuit breaker’s phases
Number of interrupters Number of the circuit breaker’s interrupters per phase
per phase
Pole operation Pole operation of the circuit breaker
Pre-insertion resistors Select the Pre-insertion resistors (PIR) check box if the circuit breaker
(PIR) contains pre-insertion resistors.
PIR value Pre-insertion resistor value
Grading capacitors Select the Grading capacitors check box if the circuit breaker contains
grading capacitors.
Capacitor value Grading capacitor value
Interrupting medium Interrupting medium of the circuit breaker
Tank type Type of the circuit breaker’s tank
Ratings
Rated frequency Rated frequency of the circuit breaker
Rated voltage L-L Rated voltage of the circuit breaker
Rated current Rated current of the circuit breaker
Rated short-circuit Rated short-circuit breaking current of the circuit breaker
breaking current
Short-circuit nominal Nominal duration of the short-circuiting
duration
Rated insulation level Basic impulse level rating of the circuit breaker
(BIL)
Rated interrupting time Rated interrupting time of the circuit breaker
Interrupting duty cycle Interrupting duty cycle of the circuit breaker
Rated power at closing Rated power of the circuit breaker at closing
92 OMICRON
Asset data
Data Description
Rated power at opening Rated power of the circuit breaker at opening
Rated power at motor Rated power of the circuit breaker at motor charge
charge
Contact system
Total travel Total distance traveled by the contact during operation (excluding possible
overshoot)
Damping time Time in which the damping units are engaged to decelerate the circuit
breaker’s moving contacts
Nozzle length Length of the circuit breaker’s nozzle
Others
Total weight with oil/gas Total weight of the circuit breaker with oil or gas
Weight of oil/gas Weight of the circuit breaker’s oil or gas
Volume of oil/gas Volume of the circuit breaker’s oil or gas
Rated gas pressure Rated gas pressure of the circuit breaker at given temperature
Data Description
Number of trip coils Number of trip coils to operate the circuit breaker
Number of close coils Number of close coils to operate the circuit breaker
Component Operating mechanism’s component
Rated voltage Rated voltage of the operating mechanism’s component
Rated current Rated current of the operating mechanism’s component
DC Select the DC check box to set the component’s DC operation
AC Select the AC check box to set the component’s AC operation
Frequency AC operation frequency
Rated operating pressure Rated operating pressure of the operating mechanism at given
temperature
12.3.2 Bushing
For the data of the circuit breaker’s bushings, see 16 "Spare bushing data" on page 98.
OMICRON 93
CPC 100 PTM User Manual
Setting Description
Contact resistance
R min Minimum limit of the contact resistance
R max Maximum limit of the contact resistance
Operating times1
t min Minimum limit of the operating time
t max Maximum limit of the operating time
Contact travel2
d min Minimum assessment limit
d max Maximum assessment limit
Add velocity zone Click Add velocity zone to define a velocity zone for assessment of the
contact travel velocity.
Coil currents
I min Minimum limit of the coil current
I max Maximum limit of the coil current
Pickup voltage
V min Minimum limit of the pickup voltage
V max Maximum limit of the pickup voltage
1. For the definitions of the operating times, see Table 17-7: "Operating times" on page 113.
2. Only available if testing with the CB TN3 modules
The following table describes the circuit breaker’s relative assessment limits.
Setting Description
Contact resistance
R ref Reference contact resistance
R dev Allowed deviation from the reference contact resistance
Operating times1
t ref Reference operating time
–t dev Allowed negative deviation from the reference operating time
+t dev Allowed positive deviation from the reference operating time
Contact travel2
d ref Reference velocity
94 OMICRON
Asset data
Setting Description
d dev Allowed deviation from the reference velocity
Add velocity zone Click Add velocity zone to define a velocity zone for assessment of the
contact travel velocity.
Coil currents
I ref Reference coil current
–I dev Allowed negative deviation from the reference coil current
+I dev Allowed positive deviation from the reference coil current
Pickup voltage
V ref Reference pickup voltage
V dev Allowed deviation from the reference pickup voltage
1. For the definitions of the operating times, see Table 17-7: "Operating times" on page 113.
2. Only available if testing with the CB TN3 modules
OMICRON 95
CPC 100 PTM User Manual
Data Description
Standard Standard used for testing the current transformer
Rated frequency Rated frequency of the current transformer
Rated Ipn : Isn1 Rated primary- to-secondary current ratio of the current transformer
Rated Ipr : Isr 2
Primary windings Number of primary windings on the current transformer (for primary
reconnection)
IEEE C57.13
System voltage System voltage of the current transformer
Rated insulation level Basic impulse level rating of the current transformer
(BIL)
Rating factor (RF) Continuous thermal current rating factor of the current transformer
IEC 60044/IEC 61869
Um (r.m.s.) Highest voltage for equipment
U withstand (r.m.s.) Rated power-frequency withstand voltage
U lightning (peak) Rated lightning impulse withstand voltage
Icth Rated continuous thermal current
Idyn (peak) Rated dynamic current
Ith (r.m.s.) Rated short time thermal current
Duration Duration of rated short time thermal current
1. According to IEC 60444
2. According to IEC 61869 and IEEE C57.13
96 OMICRON
Asset data
Data Description
Cores Number of the current transformer’s cores
Name Inter-tap identification
Ipn1/Ipr2 Inter-tap rated primary current
Table 12-14: Specific parameters and settings displayed for IEC 60044 protection CTs
Available for
IEC 60044 Available for
Param. Description protection CTs, IEC 60044, class
class
xP xPR PX TPS TPX TPY TPZ
ALF Accuracy limiting factor. x x
Win- Specified secondary winding resistance.
ding
x x x x x x
resi-
stance
Ts Specified secondary time constant. x x x
Kx Dimensioning factor. x
Ek Rated knee point e.m.f. x
Ie Accuracy limiting current x
E1 User-defined e.m.f. to verify the excitation current at this
x
specific e.m.f.
Ie1 Maximum allowed excitation current at E1. x
Kssc Rated symmetrical short-circuit current factor. x x x x
OMICRON 97
CPC 100 PTM User Manual
Table 12-14: Specific parameters and settings displayed for IEC 60044 protection CTs
Available for
IEC 60044 Available for
Param. Description protection CTs, IEC 60044, class
class
xP xPR PX TPS TPX TPY TPZ
Tp Primary time constant. x x x x
K Dimensioning factor. x
V-al Rated equivalent excitation limiting secondary voltage. x
I-al Accuracy limiting secondary excitation current. x
Ktd Rated transient dimensioning factor. x x x
Duty Specified duty cycle. x x
t1 Duration of first current flow. The specified accuracy limit must
x x
not be reached within time tal1.
The following parameters are only displayed if the standard IEC 60044 is selected with the type
"Metering CT".
Table 12-15: Specific parameters and settings displayed for IEC 60044 metering CTs
Available for
IEC 60044
metering CTs,
Param. Description class
0.1, 0.2, 0.2s, 0.5,
0.5s, 1, 3, 5
FS Instrument security factor. x
ext. Ipn Extended current rating. x
98 OMICRON
Asset data
Table 12-16: Specific parameters and settings displayed for IEC 61869 protection CTs
Available for IEC 61869
protection CTs, class
Param. Description transient
protection
protection
xP xPR PX PXR TPX TPY TPZ
ALF Accuracy limiting factor. x x
Win- Specified secondary winding resistance.
ding
x x x x x x
resi-
stance
Ts Specified secondary time constant. x x
Kx Dimensioning factor. x x
Ek Rated knee point e.m.f. x x
E1 User-defined e.m.f. to verify the excitation current at this
x x
specific e.m.f.
Ie Accuracy limiting current. x x
Ie1 Maximum allowed excitation current at E1. x x
Kssc Rated symmetrical short-circuit current factor. x x x
Duty The accuracy class assessment has to be performed for the
cycle specific protection requirements the CT is built for. According to
spec. the standard, these requirements are normally stated by the
duty cycle and the time constants.
However, in some cases the choice of one specific duty
x x x
cycle/time constant cannot describe all protection requirements.
Therefore, Primary Test Manager offers the possibility to
specify "more general requirements" (which cover the
requirements of different duty cycles and time constants) by
entering the Ktd instead.
OMICRON 99
CPC 100 PTM User Manual
Table 12-16: Specific parameters and settings displayed for IEC 61869 protection CTs
Available for IEC 61869
protection CTs, class
Param. Description transient
protection
protection
xP xPR PX PXR TPX TPY TPZ
t-al1 Permissible time to accuracy limit for first energizing period of
the duty cycle.
x x x
Note: Only displayed if parameter "Duty cycle spec." is
"by Duty".
t1 Duration of first current flow. The specified accuracy limit must
not be reached within time tal1.
x x x
Note: Only displayed if parameter "Duty cycle spec." is
"by Duty" and "Duty" is "CO-CO".
tfr Dead time between first opening and reclosure.
Note: Only displayed if parameter "Duty cycle spec." is x x x
"by Duty" and "Duty" is "CO-CO".
t-al2 Permissible time to accuracy limit for second energizing period
of the duty cycle.
x x x
Note: Only displayed if parameter "Duty cycle spec." is
"by Duty" and "Duty" is "CO-CO".
Table 12-17: Specific parameters and settings displayed for IEC 61869 metering CTs
Available for
IEC 61869 metering
Param. Description CTs, class
0.1, 0.2, 0.2s, 0.5,
0.5s, 1, 3, 5
FS Instrument security factor. x
ext. Ipn Extended current rating. x
ext. VA Extended burden range. x
100 OMICRON
Asset data
Table 12-18: Specific parameters and settings displayed for IEEE C57.13 protection CTs
Available for
Param. Description IEEE C57.13, class
C T X K
Vb Rated secondary terminal voltage.
If the IEEE C57.13 standard is selected with the type "protection CT" (class C, K x x x
or T), the VA and Cos ϕ parameters are not accessible to the user. In this case,
the user has to enter the terminal voltage Vb instead.
Vk User-defined measuring point.
x x
Vk1 User-defined measuring point 1.
Ik User-defined measuring point.
x x
Ik1 User-defined measuring point 1.
RE(20*Isn) Ratio error at 20 * Isn. x
Winding Specified secondary winding resistance.
x
resistance
Table 12-19: Specific parameters and settings displayed for IEEE C57.13 metering CTs
Available for
IEEE C57.13
metering CTs,
Param. Description class
0.15, 0.15s, 0.3, 0.6,
1.2
RF Continuous current rating factor. x
OMICRON 101
CPC 100 PTM User Manual
Data Description
Standard Standard used for testing the voltage transformer
Rated frequency Rated frequency of the voltage transformer
Upr Rated primary voltage
Data Description
Windings Number of windings on the voltage transformer
Usr Rated secondary voltage
Rated burden Rated burden of the voltage transformer
cos φ Phase angle of the secondary burden
Data Description
Star point1 Star point connection of the rotating machine during test
Data Description
Rated frequency Rated frequency of the rotating machine
Rated voltage L-L L-L voltage of the rotating machine
Rated current Rated current of the rotating machine
Rated speed (rpm) Rated speed of the rotating machine in revolutions per minute
Rated power Rated power of the rotating machine
102 OMICRON
Asset data
Data Description
Rated power factor Rated power factor of the rotating machine
Rated thermal class Rated thermal class of the rotating machine
Rated excitation current Rated excitation current of the rotor
(rotor)
Rated excitation voltage Rated excitation voltage of the rotor
(rotor)
Data Description
Maximum grid current Parameters of the substation or test object
Maximum fault duration Maximum amount of time the fault is applied
Unlimited fault duration Activate the check box for an unlimited fault duration. Maximum fault
duration will be deactivated.
To document your measurement locations, you can add a Grounding system environment (for ground
impedance measurements) and Ground mat plan (for step and touch voltage measurements).
► To add an existing map as an image, press Select image .
► To create a snapshot from Bing Maps, press Show map .
Zoom into the desired area and press Create snapshot.
OMICRON 103
CPC 100 PTM User Manual
13 Transformer tests
In this chapter, the settings and measurement data of the transformer tests are described. Fore more
information about testing with the CPC 100, see the CPC 100 User Manual shipped with your test
system.
Note: Depending on your settings, some test names include the power factor (PF), the dissipation factor
(DF), or the tangent delta (Tanδ). The dissipation factor and the tangent delta are identical
characteristics of the primary asset under test. For your convenience, with Primary Test Manager you
can use your preferred naming. You can also select some test names to match your regional
conventions (see 4.1.1 "Settings" on page 19).
104 OMICRON
Transformer tests
Setting Description
Asset
Asset Asset under test – set in the asset data
(see chapter 12 "Asset data" on page 88)
Tank type Type of transformer tank
Insulation medium Insulation medium of the transformer – set in the asset data
(see chapter 12 "Asset data" on page 88)
Note: The DGA is only valid for the insulation medium Mineral oil.
Oil type Type of transformer oil
Test conditions
Sample date Date of sample collection
Oil sample temperature Oil temperature at the time of sampling
Measurement
Analyzed by Information on how the sample was analyzed
• Oil lab: The sample was analyzed by a laboratory.
After selecting Oil lab, you can enter the Name and Address of the
laboratory.
• Mobile DGA: The sample was analyzed using a mobile DGA device.
After selecting Mobile DGA, you can enter the device
Manufacturer/Type and its Serial number.
• Online DGA: The sample was analyzed using a permanently
installed monitoring device.
After selecting Online DGA, you can enter the device
Manufacturer/Type and its Serial number.
Use C3 hydrocarbons Activate the Use C3 hydrocarbons check box to add C3H6 and C3H8
to the list of Gas in oil values, and to activate ratio assessment
according to the MSS scheme.
Sampling point Sampling point on the transformer tank:
• Top
• Middle
• Bottom
OMICRON 105
CPC 100 PTM User Manual
Data Description
TDCG Total dissolved combustible gas
TDG Total dissolved gas
TCGe Estimation of the percentage of total combustible gas in the gas space.
It will only correspond to the actually measured value if there is a
balance between the gas blanket and the oil.
Lab. result Assessment result of the laboratory according to the IEEE or IEC
standard.
Assessment Manual Gas-in-oil analysis assessment:
• Manual pass
• Manual fail
• Manual investigate
• Not assessed
Assessment Summary
The results are assessed using the following interpretation methods:
• Duval’s triangles (see Table 13-3 below)
• IEC basic gas ratios
• Roger’s ratios
• Doernenburg’s ratios
• Key gases according to IEEE C57.104 and IEC 60599 (see Table 13-3 below)
• MSS scheme
106 OMICRON
Transformer tests
Condition 4
Condition 3
Condition 1
Indicator
Assumed fault –
see Assessment Summary
table
Duval’s triangle 1
Indicator
Indicator
OMICRON 107
CPC 100 PTM User Manual
Assessment Details
• The Table contains condition ranges and states for individual gases.
• The Ratio Table lists all used gas ratios, depending on the selected standard, and provides an
Interpretation of the recorded values.
Data Description
Table
Standard Standard used for the condition assessment
Overall assessment Condition fulfilled by the measured value of an individual gas
TDCG ppm/day Increase in TDCG per day since the last measurement
Recommendation Recommended interval for future measurements
Ratio Table
Sample Date Date of the sampling
Duval Triangle
Duval’s triangles visualize faults in a triangular coordinate system (see Table 13-3).
• Triangle 1: gases formed by faults of low to high energy
• Triangle 4: gases formed more specifically by faults of low energy or temperature
• Triangle 5: gases formed more specifically by faults of high temperature
Pattern
The key gas results are visually compared to four reference patterns. If a reference graph matches the
measured value, it is highlighted.
Data Description
Water content
H2O meas. Measured water content in oil
H2O @ 20 ºC Calculated water content in oil
Relative saturation Relative water saturation
Assessment Water content assessment
DC conductivity
Meas. value Measured DC conductivity
Test temperature Temperature of the oil during DC conductivity test
Field strength Field strength
Assessment DC conductivity assessment
108 OMICRON
Transformer tests
Data Description
Power factor
Standard Standard underlying the power factor analysis
Meas. value @ 25 ºC Power factor measured at 25 ºC
Meas. value @ 100 ºC Power factor measured at 100 ºC
Assessment Power factor assessment
Dielectric breakdown voltage
Standard Standard underlying the dielectric breakdown voltage analysis
Meas. value Measured dielectric breakdown voltage
Test temperature Oil temperature during dielectric breakdown voltage test
Assessment Dielectric breakdown voltage assessment
Chemical
Interfacial tension Interfacial tension of the oil
Neutralization value Neutralization value of the oil
Particle count Particle count of the oil
Color Color of the oil
Assessment Chemical assessment
Status Description
Prepared
Partially executed See Table 5-1: "Job statuses" on page 34.
Executed
Note: The test status set in the Oil Analysis test is displayed in the job overview (see 5.2 "Job overview"
on page 36) under Tests.
OMICRON 109
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: OMICRON expertise
• Voltage sweep: None
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
110 OMICRON
Transformer tests
Setting Description
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Top oil temperature Oil temperature at the top of the transformer’s tank
Bottom oil temperature Oil temperature at the bottom of the transformer’s tank
Average oil temperature Calculated average oil temperature of the transformer’s tank
Winding temperature Temperature of the transformer’s winding
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction temp. In the Custom list, click the correction temperature, or type the
correction temperature beneath.
Correction factor Click the Calculate button to calculate the correction factor
automatically or type the correction factor beneath.
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
Bushings compensation Select the Bushings compensation check box to activate bushings
compensation.
Note: Bushing compensation compensates the effect of the
capacitance C1 of the transformer’s bushings on the measurement
results of the test.
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
Primary Test Manager supports automatic assessment for the following insulation media:
• Natural ester
OMICRON 111
CPC 100 PTM User Manual
• Mineral oil
• Silicone
if you activated the temperature correction by selecting the Temperature correction check box.
The following table describes the automatic assessment parameters of the Overall PF/DF/Tanδ & CAP
test.
Parameter Description
Limit schema Limit schema underlying the assessment
Global assessment criteria
Min. Iout @10 kV Threshold value of the automatic assessment.
If Iout < Min. Iout @10 kV, the automatic assessment status is
Investigate.
To save the selected limit schema as the default setting for all future jobs, click Set as default.
Under Visible limits:
► Click only limits that are used for this measurement to display only limits for the selected
transformer’s insulation type.
► Click all limits to display limits for all supported transformer’s insulation types.
The following tables describe the automatic assessment limits of the Overall PF/DF/Tanδ & CAP test.
Table 13-9: Overall PF/DF/Tanδ & CAP automatic assessment limits based on Power Factor/Dissipation
Factor/Tanδ1
112 OMICRON
Transformer tests
If you selected the Use reference voltage check box Primary Test Manager performs additionally a
cross check by using the following additional limits.
Table 13-10: Overall PF/DF/Tanδ & CAP cross check limits based on Power Factor/Dissipation
Factor/Tanδ1
Table 13-11: Overall PF/DF/Tanδ & CAP cross check limits based on capacitance
OMICRON 113
CPC 100 PTM User Manual
The following table describes the Overall PF/DF/Tanδ & CAP measurement data.
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
114 OMICRON
Transformer tests
Setting Description
Measurement settings
Test frequency Test frequency
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed
within the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: OMICRON expertise
• Voltage sweep: OMICRON expertise
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
OMICRON 115
CPC 100 PTM User Manual
Table 13-13: Bushing H/X PF/DF/Tanδ & CAP – C1 test settings (continued)
Setting Description
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Top oil temperature Oil temperature at the top of the transformer’s tank
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of the measurement results
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
Primary Test Manager supports automatic assessment for the following bushing’s insulation types:
• Oil-impregnated paper
• Resin-bonded paper
• Resin-impregnated paper
For another type of the bushing’s insulation the automatic assessment cannot be done.
Note: The assessment can be done only if all bushings have the same insulation type.
116 OMICRON
Transformer tests
The following table describes the automatic assessment parameters of the Bushing H/X PF/DF/Tanδ &
CAP – C1 test.
Table 13-14: Bushing H/X PF/DF/Tanδ & CAP – C1 automatic assessment parameters
Parameter Description
Limit schema Limit schema underlying the assessment
Global assessment criteria
Min. Iout @10 kV Threshold value of the automatic assessment.
If Iout < Min. Iout @10 kV, the automatic assessment status is
Investigate.
To save the selected limit schema as the default setting for all future jobs, click Set as default.
Under Visible limits:
► Click only limits that are used for this measurement to display only limits for the selected
bushing’s insulation type and the PF (C1)/DF (C1)/Tanδ (C1)1 nameplate values (if entered) or the
absolute limits.
► Click all limits to display limits for all supported bushing insulation types and the
PF (C1)/DF (C1)/Tanδ (C1)1 nameplate values (if entered) or the absolute limits.
The following tables describe the automatic assessment limits of the Bushing H/X PF/DF/Tanδ & CAP –
C1 test.
Table 13-15: Bushing H/X PF/DF/Tanδ & CAP – C1 automatic assessment limits based on Power
Factor/Dissipation Factor/Tanδ1
OMICRON 117
CPC 100 PTM User Manual
Table 13-16: Bushing H/X PF/DF/Tanδ & CAP – C1 automatic assessment limits based on capacitance
The following table shows the Primary Test Manager assessment logic.
118 OMICRON
Transformer tests
If you change the following nameplate data relevant for the assessment:
• PF (C1)/DF (C1)/Tanδ (C1)1
• Cap. (C1)
• PF (C2)/DF (C2)/Tanδ (C2)1
• Cap. (C2)
• Bushing’s insulation type
After a measurement has been assessed and you reopen the test, the following message appears.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
OMICRON 119
CPC 100 PTM User Manual
Table 13-18: Bushing H/X PF/DF/Tanδ & CAP – C1 measurement data (continued)
Data Description
PF ref/ Reference power factor, dissipation factor, or tangent delta
DF ref/
Tanδ ref1
Cap. meas Measured capacitance
Cap. ref Reference capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Top oil temperature Oil temperature at the top of the transformer’s tank
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
120 OMICRON
Transformer tests
Table 13-19: Bushing H/X PF/DF/Tanδ & CAP – C2 test settings (continued)
Setting Description
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
Primary Test Manager supports automatic assessment for the following bushing’s insulation types:
• Oil-impregnated paper
• Resin-bonded paper
• Resin-impregnated paper
For another type of the bushing’s insulation the automatic assessment cannot be done.
Note: The assessment can be done only if all bushings have the same insulation type.
The following table describes the automatic assessment parameters of the Bushing H/X PF/DF/Tanδ &
CAP – C2 test.
Table 13-20: Bushing H/X PF/DF/Tanδ & CAP – C2 automatic assessment parameters
Parameter Description
Limit schema Limit schema underlying the assessment
Global assessment criteria
Min. Iout @10 kV Threshold value of the automatic assessment.
If Iout < Min. Iout @10 kV, the automatic assessment status is
Investigate.
To save the selected limit schema as the default setting for all future jobs, click Set as default.
Under Visible limits:
► Click only limits that are used for this measurement to display only limits for the selected
bushing’s insulation type and the PF (C2)/DF (C2)/Tanδ (C2)1 nameplate values (if entered) or the
absolute limits.
► Click all limits to display limits for all supported bushing insulation types and the
PF (C2)/DF (C2)/Tanδ (C2)1 nameplate values (if entered) or the absolute limits.
OMICRON 121
CPC 100 PTM User Manual
The following tables describe the automatic assessment limits of the Bushing H/X PF/DF/Tanδ & CAP –
C2 test.
Table 13-21: Bushing H/X PF/DF/Tanδ & CAP – C2 automatic assessment limits based on Power
Factor/Dissipation Factor/Tanδ1
Table 13-22: Bushing H/X PF/DF/Tanδ & CAP – C2 automatic assessment limits based on capacitance
122 OMICRON
Transformer tests
The following table shows the Primary Test Manager assessment logic.
OMICRON 123
CPC 100 PTM User Manual
The following table describes the Bushing H/X PF/DF/Tanδ & CAP – C2 measurement data.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Temperature corrected power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
PF ref/ Reference power factor, dissipation factor, or tangent delta
DF ref/
Tanδ ref1
Cap. meas Measured capacitance
Cap. ref Reference capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
124 OMICRON
Transformer tests
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Top oil temperature Oil temperature at the top of the transformer’s tank
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
OMICRON 125
CPC 100 PTM User Manual
The following table describes the Bushing H/X – Energized Collar measurement data.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Assessment Measurement assessment
Setting Description
Tap changer settings
Type of tap changer Tap changer (OLTC/DETC) whose taps are changed during the test
Number of taps Number of taps of the tap changer
Start tap Start tap position of the test
Stop tap Stop tap position of the test
DETC position/ Tap position of the DETC or OLTC
OLTC position1
Measurement settings
Test voltage Test voltage
Test mode Test mode according to the IEEE Std 62-1995
Test phase Phase of the winding under test
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
126 OMICRON
Transformer tests
Setting Description
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Correction factors
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
1. Only available if the transformer has both the OLTC and DETC tap changers and depends on the selected type of the tap
changer.
Data Description
Tap Tap changer position
V out Measured output voltage
I out Measured output current
I phase Measured primary current per phase
Watt losses Measured losses
Reactance Measured reactance
Assessment Measurement assessment per tap position
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
OMICRON 127
CPC 100 PTM User Manual
Table 13-29: Insulating fluids PF/DF/Tanδ & CAP test settings (continued)
Setting Description
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Oil temperature Temperature of the oil
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Insulating Fluids PF/DF/Tanδ & CAP measurement data.
Data Description
No. Number of the measurement
Specimen Oil sample under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
128 OMICRON
Transformer tests
Table 13-30: Insulating fluids PF/DF/Tanδ & CAP measurement data (continued)
Data Description
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
OMICRON 129
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CP TD1 filter bandwidth
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test Conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Top oil temperature Oil temperature at the top of the transformer’s tank
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
130 OMICRON
Transformer tests
The following table describes the Surge Arrester Watt Losses H/X measurement data.
Data Description
Measurement Terminal name of the surge arrester under test
Position Surge arrester unit under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Assessment Measurement assessment
Setting Description
Measurement settings
Test current Test current
OLTC position Tap position of the OLTC
DETC position Tap position of the DETC
3Ph equiv. test
Perform test Select the Perform test check box if you want to perform the
3Ph equiv. test.
Show FRSL results Select the Show FRSL results check box to show the FRSL results of
the 3Ph equiv. test.
Per-phase test
Perform test Select the Perform test check box if you want to perform the Per-
phase test.
Show FRSL results Select the Show FRSL results check box to show the FRSL results of
the Per-phase test.
OMICRON 131
CPC 100 PTM User Manual
Setting Description
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Winding temperature Temperature of the transformer’s winding
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Reference temp. Reference temperature to be used for temperature correction
Corr. factor Temperature correction factor
Primary Test Manager supports automatic assessment of the Leakage Reactance H–X test. The
relevant data are grouped in the Assessment pane.
The automatic assessment is only possible if you have completed the steps below:
► Enter the following transformer nameplate data:
– Leakage Reactance Z (%)
– Base power:
Primary Test Manager determines the base power used for assessment using the following
information in the specified order:
1.The base power entered in the table of the Leakage Reactance field of the transformer
nameplate
2.The base power entered in the Zero sequence impedance field of the transformer nameplate
– Base voltage
Primary Test Manager determines the base voltage used for assessment using the following
information in the specified order:
1.The base voltage entered in the Leakage Reactance table in the transformer nameplate
2.The voltage of the tap (if a tap changer is available)
3.The base power entered in the Zero sequence impedance field of the transformer nameplate
► Activate the temperature correction by selecting the Temperature correction check box.
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
The automatic assessment is based on the selected limit schema. You can use predefined limit schemes
according to the established standards or set customer specific limits. In the Limit schema box, select
the limit schema you want to use for the assessment. To assign the selected limit schema to the asset
under test, click Set as default. The automatic assessment limits differ depending on the number of the
transformer’s phases.
132 OMICRON
Transformer tests
Single-phase transformers
The following table describes the automatic assessment limits for the single-phase transformer.
Table 13-34: Leakage Reactance H–X automatic assessment limits for single-phase transformer
During the test, Primary Test Manager calculates the Zk meas (%) value1. For the automatic
assessment, Primary Test Manager compares Zk meas (%) with the nameplate value Zk leakage
reactance (%). If the deviation is less than the default limit, the assessment is set to Pass, otherwise to
Fail.
Three-phase transformers
The following table describes the automatic assessment limits for the three-phase transformer.
Table 13-35: Leakage Reactance H–X automatic assessment limits for three-phase transformer
During the 3Ph equiv. measurement, Primary Test Manager calculates one Zk meas (%) value for all
phases. For the automatic assessment, Primary Test Manager compares Zk meas (%) with the
nameplate value Zk ref (%). If the deviation is less than the default limit the assessment status is set to
Pass, otherwise to Fail.
During the Per-phase measurement, Primary Test Manager calculates the Zk meas (%) values for each
phase. For the automatic assessment, Primary Test Manager compares Zk meas (%) with the average
of Zk meas (%) across all phases. If the deviation is less than the default limit, the assessment status is
set to Pass, otherwise to Fail.
You can assess the test at two points in the process:
• Assessment during the measurement
To assess the test while the measurements are running, activate the
Assess during measurements check box. After this, the test is locked, and you can only change
assessment-relevant data, for example, the nominal values.
• Manual assessment after all measurements have been finished
To assess the test manually, click Assess measurements. After that, the test is locked, and you can
only change assessment-relevant data, for example, the nominal values.
To set new data in the test or to change the test settings, click Clear all assessments.
You can overwrite the Primary Test Manager automatic assessment manually. To do so, click the arrow
next to the automatic assessment, and then select a manual assessment from the list.
Note: The automatic assessment is stored in the Assessment box for documentation purposes.
1. In the Transformer area of the Settings dialog box, you can change the Short-circuit impedance (Leakage reactance)
abbreviation (see "Profiles: Transformer" on page 22).
OMICRON 133
CPC 100 PTM User Manual
Data Description
Phase Phase under test
I AC Measured current
V1 AC Measured voltage
V1 AC phase Phase angle of the voltage V1 AC
Watt losses Measured losses
Zk Measured leakage reactance
Rk Real part of the measured Zk
Xk Imaginary part of the measured Zk
(leakage reactance)
Lk Measured leakage inductance
Data Description
Phase Phase under test
Zk meas (%) Measured leakage reactance in percent
Zk avg (%) Average of Zk meas (%) across all phases
Zk dev (%) Deviation of the Zk meas (%) from the Zk ref (%) in percent
Xk meas (%) Measured reactance in percent
Xk avg (%) Average of Xk meas (%) across all phases
Xk dev (%) Deviation of the Xk meas (%) from the Xk ref (%) in percent
Assessment Measurement assessment
Data Description
Rk avg Average value of the per phase Rk
Rk dev (%) phase A Deviation of the measured Rk of the phase A from the average value
Rk dev (%) phase B Deviation of the measured Rk of the phase B from the average value
Rk dev (%) phase C Deviation of the measured Rk of the phase C from the average value
Assessment Measurement assessment
134 OMICRON
Transformer tests
Measurements: per-phase
The following table describes the leakage reactance results (Zk).
Data Description
Phase Phase under test
I AC Measured current
V1 AC Measured voltage
V1 AC phase Phase angle of the voltage V1 AC
Watt losses Measured losses
Zk Measured leakage reactance
Rk Real part of the measured Zk
Xk Imaginary part of the measured Zk
(leakage reactance)
Lk Measured leakage inductance
Data Description
Phase Phase under test
Zk meas (%) Measured impedance in percent
Zk ref (%) Reference impedance in percent
(Corresponds to the nameplate value Z %.)
Zk dev (%) Deviation of the measured impedance from the reference impedance in
percent
Xk meas (%) Measured reactance in percent
Xk ref (%) Reference reactance in percent
Xk dev (%) Deviation of the Xk meas (%) from the Xk ref (%) in percent
Dominance order Order of the Zk dev (%) values:
1 for the highest value
2 for the middle value
3 for the lowest value
Assessment Measurement assessment
OMICRON 135
CPC 100 PTM User Manual
Data Description
Rk avg Average value of the per phase Rk
Rk dev (%) phase A Deviation of the measured Rk of the phase A from the average value
Rk dev (%) phase B Deviation of the measured Rk of the phase B from the average value
Rk dev (%) phase C Deviation of the measured Rk of the phase C from the average value
Assessment Measurement assessment
136 OMICRON
Transformer tests
Setting Description
Measurement settings
Test current Current of the test
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Winding temp. Temperature of the transformer’s winding
Reference temp. Reference temperature to be used for temperature correction
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Corr. factor Temperature correction factor
Type of tap changer Tap changer (OLTC/DETC) whose taps are changed during the test
Number of taps Number of taps of the tap changer
DETC position/ Tap position of the DETC or OLTC
OLTC position1
Assessment settings
Manual Click Manual to select the manual assessment settings.
Automatic Click Automatic to select the automatic assessment settings
(see "Editing automatic assessment settings" later in this section).
1. Only available if the transformer has both the OLTC and DETC tap changers and depends on the selected type of the tap
changer.
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
OMICRON 137
CPC 100 PTM User Manual
2. In the Edit automatic assessment limits dialog box, enter the deviation of the Z0 (%) from the
Z0 ref (%) in percent.
The following table describes the Zero Sequence Impedance H/X measurement data.
Data Description
Tap Tap changer position
V1 AC Measured voltage
V1 AC phase Phase angle of the voltage V1 AC
I AC Measured current
Z meas Measured impedance
Z corr Temperature corrected impedance
Z0 Measured zero sequence impedance
Z0 (%) Measured zero sequence impedance in percent
Z0 ref (%) Reference zero sequence impedance in percent
Z0 dev (%) Deviation of the Z0 (%) from the Z0 ref (%) in percent
Assessment Measurement assessment
138 OMICRON
Transformer tests
Setting Description
Tap changer settings
Type of tap changer Tap changer (OLTC/DETC) whose taps are changed during the test
Number of taps Number of taps of the tap changer
Start tap Start tap position of the test
Stop tap Stop tap position of the test
DETC position/ Tap position of the DETC or OLTC
OLTC position1
CP SB1 settings
Use CP SB1 Select the CP SB1 check box to perform the test by using the CP SB1
switch box.
Auto switching of phases Phases are switched automatically;
Switching through taps is done manually.
Auto switching of taps and Switching through taps and phases is both done automatically.
phases
Auto switching of phases Phases are switched automatically;
Switching through taps is done manually.
Tap time Time for the automatic tap change between two positions
Impulse time Duration of the impulse for the automatic tap change
IEC 61378-12 Select the IEC 61378-1 check box to perform the test according to the
IEC 61378-1 standard.
Measurement settings
Test voltage Test voltage
Test phase Phase of the winding under test
Ratio Choose between TTR (transformer turns ratio) and VTR (voltage ratio)
to be displayed in the Measurements table.
Assessment settings
Manual Click Manual to select the manual assessment settings.
Automatic Click Automatic to select the automatic assessment settings
(see "Editing automatic assessment settings" later in this section).
1. Only available if the transformer has both the OLTC and DETC tap changers and depends on the selected type of the tap
changer.
2. The CP SB1 and Automatic tap control check boxes must be selected.
OMICRON 139
CPC 100 PTM User Manual
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
2. In the Edit automatic assessment limits dialog box, enter the deviation of the measured
transformer ratio from the nominal transformer ratio in percent.
The following table describes the TTR H–X measurement data.
Data Description
Tap Tap changer position
Nominal ratio Nominal transformer ratio
V prim Measured primary voltage
I prim1 Measured primary current
140 OMICRON
Transformer tests
Setting Description
Tap changer settings
Type of tap changer Tap changer (OLTC/DETC) whose taps are changed during the test
Number of taps Number of taps of the tap changer
Start tap Start tap position of the test
Stop tap Stop tap position of the test
DETC Position/ Tap position of the DETC or OLTC
OLTC Position1
CP SB1 settings
Use CP SB1 Select the CP SB1 check box to perform the test by using the CP SB1
switch box.
Mode Switching mode for taps and phases
Manual Switching through taps and phases is both done manually.
Auto switching of phases Phases are switched automatically;
Switching through taps is done manually.
Auto switching of taps Taps are switched automatically;
Switching through phases is done manually.
Auto switching of taps and Switching through taps and phases is both done automatically.
phases
Tap time Time for the automatic tap change between two positions.
Impulse time Duration of the impulse for the automatic tap change.
Up/Down test Select the Up/Down test check box to run the test in two directions (up
and down). Up means from the lowest tap to the highest tap while down
means from the highest tap to the lowest tap.
Measurement settings
CPC output DC current output of the CPC 100
Test current Current of the test
Test phase Phase of the winding under test
Automatic result Select the Automatic result check box to stop the measurement
automatically depending on the tolerance R dev and the settling time.
Tolerance R dev Tolerance of the deviation of consecutive measurement results within
the settling time
Settling time (∆t) Time within which the deviation of consecutive measurement results is
evaluated. If the deviation is less than the tolerance R dev, the
measurement stops.
OMICRON 141
CPC 100 PTM User Manual
Setting Description
Show TRTapCheck results Select the Show TRTapCheck results check box to display information
about the condition (ripple and slope) of the tap changer mechanisms
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Winding temperature Temperature of the transformer’s winding
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Reference temp. Reference temperature to be used for temperature correction
Corr. factor Temperature correction factor
1. Only available if the transformer has both the OLTC and DETC tap changers and depends on the selected type of the tap
changer.
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
Primary Test Manager supports automatic assessment of the DC Winding Resistance H/X test.
The following table describes the automatic assessment parameters of the DC Winding Resistance H/X
test.
Parameter Description
Limit schema Limit schema underlying the assessment
To save the selected limit schema as the default setting for all future jobs, click Set as default.
The following table describes the automatic assessment limits of the DC Winding Resistance H/X test.
During the automatic assessment, Primary Test Manager compares the R corr values of all phases to
each another. If a deviation is greater than the default limit the assessment status is set to Fail.
You can assess the test:
• During measurement
To assess the test while the measurements are running, select the Assess during measurements
check box.
• Manually after all measurements have been finished
To assess the test manually, click Assess measurements.
142 OMICRON
Transformer tests
After a measurement has been assessed, the test settings and the assessment parameters are locked.
To change the test data, the test settings or the assessment parameters, click Clear all assessments.
You can overwrite the Primary Test Manager automatic assessment manually. To do so, click the arrow
next to the automatic assessment, and then select a manual assessment from the list.
Note: The automatic assessment is stored in the Assessment box for documentation purposes.
The following table describes the DC Winding Resistance H/X measurement data.
Data Description
Tap Tap changer position
I DC Measured current
V DC Measured voltage
Time Time between the start and stop of a measurement
R meas Measured resistance
R dev Deviation of two successive measurement results at the time the test was
stopped
R corr Corrected measured resistance
Ripple1 Highest current ripple during the tap changer operation
Slope1 Highest measured falling edge slope of the test current during the tap
changer operation
Assessment Measurement assessment per tap position
1. Only available if an OLTC is specified and the Show TRTapCheck results check box is selected
Note: If you did not select the Automatic result check box to stop the measurement automatically, you
can stop the measurement by clicking the Keep results button.
OMICRON 143
CPC 100 PTM User Manual
Setting Description
Tap changer settings
Number of taps Number of taps of the tap changer
Start tap Start tap position of the test
Stop tap Stop tap position of the test
CP SB1 settings
Mode Switching mode for taps
Manual switching of taps Taps are switched manually.
Auto switching of taps Taps are switched automatically.
Tap time Time for the automatic tap change between two positions
Impulse time Duration of the impulse for the automatic tap change
Measurement settings
CPC output DC current output of the CPC 100
Test current Current of the test
Recording time The time of the switching cycle that shall be recorded
Tolerance R dev Tolerance of the deviation of consecutive measurement results within
the settling time
Settling time (∆t) Time within which the deviation of consecutive measurement results is
evaluated. If the deviation is less than the tolerance R dev, the
measurement stops.
Noise suppression Select the Noise suppression check box to activate an interference
filter.
Dynamic shorting Dynamic short-circuit of low-voltage windings on single- and three-
phase transformers.
Only selectable for two- and three-winding transformers with an OLTC
on the high-voltage winding.
144 OMICRON
Transformer tests
Measurements pane
The Measurements pane in the workspace displays the measurement results in table and graph format.
► Highlight a line to indicate the corresponding graph and vice versa.
► Use the Assessment drop-down box to manually assess the test results.
► To view graphical diagrams of the measurement results, click the Plot tab.
Filters
The following table describes the filters available for the Dynamic OLTC-Scan:
Filter Description
Phase Only results from the currently selected phase are displayed.
Parity Only results from taps with even/odd numbers are displayed.
Direction Only results from one direction of the OLTC’s movement are displayed.
Note: The Dynamic OLTC-Scan is restricted to 50 taps at once. For OLTCs with more than 50 taps,
enter the appropriate Start tap and Stop tap to define which set of 50 taps you would like to examine.
Notification Description
! Data corruption: A disturbance has been detected. This result is invalid.
Repeat the measurement.
!! Time out: No switching operation has been detected during the Tap time.
OMICRON 145
CPC 100 PTM User Manual
Setting Description
Measurement settings
CPC output DC current output of the CPC 100
Test current Current of the test
Saturation criteria
Saturation level Saturation level of the transformer
Data Description
No. Number of the measurement
Measurement Name of the measurement
Stage Test status:
• Wiring check
• Saturating
• Discharging
• Canceled
• Demagnetizing
• Test stopped
• Core is demagnetized1
I DC Measured current
Min. neg. remanence Maximum remanence in negative direction of the hysteresis curve
Max. pos. remanence Maximum remanence in positive direction of the hysteresis curve
Remanence Measured remanence
Initial remanence Measured remanence at start of the test
Assessment Measurement assessment
1. If the measured remanence < 1%.
146 OMICRON
Transformer tests
OMICRON 147
CPC 100 PTM User Manual
148 OMICRON
Transformer tests
OMICRON 149
CPC 100 PTM User Manual
150 OMICRON
Spare Bushing tests
OMICRON 151
CPC 100 PTM User Manual
Table 14-1: Spare Bushing PF/DF/Tanδ & CAP – overall test settings
Setting Description
Measurement settings
Test frequency Test frequency
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: OMICRON expertise
• Voltage sweep: none
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
152 OMICRON
Spare Bushing tests
Table 14-1: Spare Bushing PF/DF/Tanδ & CAP – overall test settings (continued)
Setting Description
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Spare Bushing PF/DF/Tanδ & CAP – Overall measurement data.
Table 14-2: Spare Bushing PF/DF/Tanδ & CAP – overall measurement data
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
OMICRON 153
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Perform inverted C1 test Select the Perform inverted C1 test check box to include the inverted
C1 measurement in the test.
Sweep settings
Frequency sweep Sweep frequency profile:
None, OMICRON expertise (recommended), or CPC template.
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: OMICRON expertise
• Voltage sweep: none
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
154 OMICRON
Spare Bushing tests
Table 14-3: Spare Bushing PF/DF/Tanδ & CAP – C1 test settings (continued)
Setting Description
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Spare Bushing PF/DF/Tanδ & CAP – C1 measurement data.
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
OMICRON 155
CPC 100 PTM User Manual
Table 14-4: Spare Bushing PF/DF/Tanδ & CAP – C1 measurement data (continued)
Data Description
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
PF ref/ Reference power factor, dissipation factor, or tangent delta
DF ref/
Tanδ ref1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
156 OMICRON
Spare Bushing tests
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Spare Bushing PF/DF/Tanδ & CAP – C2 measurement data.
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
OMICRON 157
CPC 100 PTM User Manual
Table 14-6: Spare Bushing PF/DF/Tanδ & CAP – C2 measurement data (continued)
Data Description
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
PF ref/ Reference power factor, dissipation factor, or tangent delta
DF ref/
Tanδ ref1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
158 OMICRON
Spare Bushing tests
Table 14-7: Spare Bushing PF/DF/Tanδ & CAP – C1+C2 test settings
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Spare Bushing PF/DF/Tanδ & CAP – C1+C2 measurement data.
Table 14-8: Spare Bushing PF/DF/Tanδ & CAP – C1+C2 measurement data
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
OMICRON 159
CPC 100 PTM User Manual
Table 14-8: Spare Bushing PF/DF/Tanδ & CAP – C1+C2 measurement data (continued)
Data Description
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Cap. meas Measured capacitance
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
160 OMICRON
Spare Bushing tests
Setting Description
Measurement settings
Test frequency Test frequency
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Spare Bushing – Energized Collar measurement data.
Data Description
No. Number of the measurement
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
OMICRON 161
CPC 100 PTM User Manual
Data Description
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Assessment Measurement assessment
162 OMICRON
Circuit breaker tests
OMICRON 163
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Frequency of the test
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: None
• Voltage sweep: None
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
164 OMICRON
Circuit breaker tests
Table 15-1: Circuit Breaker PF/DF/Tanδ & CAP test settings (continued)
Setting Description
Test conditions
Custom test conditions Select the Custom test conditions check box to set the test
conditions different from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Circuit Breaker PF/DF/Tanδ & CAP measurement data.
Data Description
No. Number of the measurement
Measurement Tested insulation
Position Contact position of the breaker
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Cap. meas Measured capacitance
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
OMICRON 165
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: None
• Voltage sweep: None
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
166 OMICRON
Circuit breaker tests
Setting Description
Test conditions
Custom test conditions Select the Custom test conditions check box if you want to set test
conditions different from the job conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Bushing PF/DF/Tanδ & CAP – C1 measurement data.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Cap. meas Measured capacitance
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
OMICRON 167
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Test voltage Test voltage
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Select the Custom test conditions check box if you want to set test
conditions different from the job conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Bushing PF/DF/Tanδ & CAP – C2 measurement data.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
168 OMICRON
Circuit breaker tests
Data Description
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Cap. meas Measured capacitance
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
OMICRON 169
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Test frequency
Test voltage Test voltage
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Select the Custom test conditions check box if you want to set test
conditions different from the job conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the Bushing – Energized Collar measurement data.
Data Description
No. Number of the measurement
Measurement Terminal name of the bushing under test
Test mode Test mode according to the IEEE Std 62-1995
V test Test voltage
Freq. Test frequency
170 OMICRON
Circuit breaker tests
Data Description
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Assessment Measurement assessment
Setting Description
Measurement settings
Test frequency Test frequency
Test voltage Test voltage
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Oil temperature Temperature of the oil
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
OMICRON 171
CPC 100 PTM User Manual
The following table describes the Insulating Fluids PF/DF/Tanδ & CAP measurement data.
Data Description
No. Number of the measurement
Specimen Oil sample under test
Test mode Test mode according to the IEEE Std 62-1995
V Test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
Watt losses Measured losses
Cap. meas Measured capacitance
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
Setting Description
Measurement settings
Test current Test current
Manual input of V DC Select the Manual input of V DC check box to enter the V DC
manually instead of measuring it.
Automatic result Select the Automatic result check box to stop the measurement
automatically depending on the tolerance R dev and the settling time.
Tolerance R dev Tolerance of the deviation of consecutive measurement results within
the settling time
Settling time (∆t) Time within which the deviation of consecutive measurement results is
evaluated. If the deviation is less than the tolerance R dev, the
measurement stops.
172 OMICRON
Circuit breaker tests
Setting Description
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Assessment settings
Manual Click Manual to select the manual assessment settings.
Automatic Click Automatic to select the automatic assessment settings
(see "Editing automatic assessment settings" later in this section).
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
2. In the Edit automatic assessment limits dialog box, enter the absolute or relative limits.
The following table describes the Contact Resistance measurement data.
Data Description
Main contact Main contact of the circuit breaker under test
I DC Measured current
V DC Measured voltage
OMICRON 173
CPC 100 PTM User Manual
Data Description
R meas Measured resistance
R min Minimum assessment limit
R max Maximum assessment limit
Assessment Measurement assessment
Note: If you did not select the Automatic result check box to stop the measurement automatically, you
can stop the measurement by clicking the Keep results button.
174 OMICRON
Current transformer tests
OMICRON 175
CPC 100 PTM User Manual
Setting Description
Measurement settings
Test frequency Frequency of the output signal
HV-shield connectable Select the HV-shield connectable check box if the HV screen or shield
of the current transformer is accessible.
Sweep settings
Frequency sweep Sweep profile:
None, OMICRON expertise (recommended), or CPC template
• None: no frequency sweep
• OMICRON expertise: sweep frequencies dynamically distributed
within the CPC 100 frequency range for optimum results
• CPC template: sweep frequencies specified by the CPC 100 test
templates
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a frequency or voltage sweep
profile.
► Add up to 30 measurement points with individual output voltages or
frequencies. Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles None, OMICRON expertise and
CPC template cannot be edited or deleted.
The default sweep profiles for this test are:
• Frequency sweep: OMICRON
• Voltage sweep: None
Sweep settings
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
176 OMICRON
Current transformer tests
Setting Description
If this setting is active, the measurement will not be performed at the
Test frequency set in the Measurement section. Primary Test
Manager will instead measure two values at frequencies below and
above the entered Test frequency and calculate the median of those
Avoid test frequency
two values.
The Avoid test frequency setting is predefined for the selected test.
► Only change the default setting for special applications.
Device settings
Enable shield check Select the Enable shield check check box if you want that the
CPC 100 checks whether the shield of the high-voltage cable is
connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
CT oil temperature Oil temperature of the current transformer
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage Select the Use reference voltage check box to extrapolate the I out
and Watt losses results for the specified reference voltage.
Reference voltage Reference voltage for extrapolation of measurement results
The following table describes the CT PF/DF/Tanδ & CAP measurement data.
Data Description
Measurement Arrangement of the measurement
Test mode Test mode according to the IEEE Std 62-1995
Sweep Swept variable: frequency, voltage, or none
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I out Measured output current
OMICRON 177
CPC 100 PTM User Manual
Data Description
Watt losses Measured losses
Cap. meas Measured capacitance
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Assessment Measurement assessment
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
16.2 CT Ratio
The following table describes the CT Ratio test settings.
DANGER
Death or severe injury caused by high voltage or current
► When injecting current into the CT’s primary winding, make sure that no other
secondary windings are open.
Setting Description
Measurement settings
CPC output Selected output range for the current transformer test
Manual measurement I sec Select the Manual measurement I sec check box to enter the I sec
manually, for example, if I sec was measured with an external current
clamp not connected to the CPC 100.
Use current clamp Select the Use current clamp check box if you want to use current
clamp.
I clamp Current of the clamp
Clamp factor Ratio of the clamp
Assessment settings
Manual Click Manual to select the manual assessment settings.
Automatic Click Automatic to select the automatic assessment settings
(see "Editing automatic assessment settings" later in this section).
178 OMICRON
Current transformer tests
NOTICE
Equipment damage or loss of data possible
► Before making a decision based on the Primary Test Manager automatic assessment, read the
disclaimer 1.3.1 "Automatic assessment" on page 9.
2. In the Edit automatic assessment limits dialog box, enter the assessment limits.
The following table describes the CT Ratio measurement data.
Data Description
Tap Identification of the tap under test
Ipn1/Ipr2 Rated primary current of the current transformer
OMICRON 179
CPC 100 PTM User Manual
Data Description
Polarity Polarity status
Measure burden Select the Measure burden check box to measure the connected
secondary burden in VA.
Manual input V sec Select the Manual input V sec check box to enter the measured
secondary voltage at the burden manually, for example, if it is measured
with an external device.
V sec Measured secondary voltage on the burden
Burden Measured burden in VA related to the rated secondary current
Burden nom. Rated power of the current transformer
Phase burden Phase angle of the complex secondary burden
cos φ Phase angle of the complex rated secondary burden
In use Tap on which the CT is operated
Assessment Measurement assessment
1. According to IEC 60444
2. According to IEC 61869 and IEEE C57.13
180 OMICRON
Current transformer tests
DANGER
Death or severe injury caused by high voltage or current
► Never open the measuring circuit while current flows.
► Make sure that no other secondary windings are open.
► Check whether the red warning light “I” and the discharge LED are off before
disconnecting the device under test.
► Before disconnecting from the CPC 100, connect the device under test on both ends
to protective earth.
Setting Description
Temperature compensation for Cu
Winding temperature Temperature of the transformer’s winding
Reference temperature Reference temperature to be used for temperature correction
Note: The transformer’s core is magnetized after the measurement. Demagnetization can be done using
the CTExcitation test (see 16.4 "CT Excitation" on page 182).
Setting Description
Tap Identification of the tap under test
Ipn1/Ipr2 Rated primary current of the current transformer
OMICRON 181
CPC 100 PTM User Manual
16.4 CT Excitation
The following table describes the CT Excitation test settings.
Note: The CT Excitation test is only available for current transformers conforming to IEC 60044 and
IEEE C57.13.
DANGER
Death or severe injury caused by high voltage or current
Feeding test voltage to a tap of a CT can cause life-threatening voltages on other taps
with higher ratios.
► Do not touch tapped windings.
► Make sure that no other secondary windings are open.
Setting Description
Measurement settings
Test frequency Frequency of the output signal
Noise suppression Select the Noise suppression check box to activate an interference
filter.
Setting Description
Tap Identification of the tap under test
Ipn Rated primary current of the current transformer
Isn Rated secondary current of the current transformer
I max Maximum test current
V max Maximum test voltage
I knee Knee point current
V knee Knee point voltage
Knee point calculation Method used for the knee point calculation
In use Tap on which the CT is operated
Assessment Measurement assessment
► Click the Plot tab to view the excitation curve diagram.
► Use the Tab check boxes to hide/unhide individual curves.
182 OMICRON
Current transformer tests
16.5 CT Ratio V
The following table describes the CT Ratio V test settings.
DANGER
Death or severe injury caused by high voltage or current
Feeding test voltage to a tap of a CT can cause life-threatening voltages on other taps
with higher ratios.
► Do not touch tapped windings.
► Make sure that no other secondary windings are open.
Setting Description
Measurement settings
Test frequency Frequency of the output signal
Setting Description
Tap Identification of the tap under test
Ipn1/Ipr2 Rated primary current of the current transformer
Note: If the transformer’s knee point voltage is approximated or exceeded due to the transformer’s
saturation, the measurement results are not correct anymore. If the knee point is significantly exceeded,
the transformer can even be damaged. Therefore, the knee point voltage should be known or measured
beforehand. Generally, it is advisable to set the test voltage to 75 % of the knee-point voltage. The
frequency should be set between 15 and 20 Hz off the mains frequency to avoid interferences by life
systems in the neighborhood.
OMICRON 183
CPC 100 PTM User Manual
16.6 CT Burden
The following table describes the CT Burden test settings.
Setting Description
Measurement settings
Test frequency Frequency of the output signal
Setting Description
Tap Identification of the tap under test
Ipn1/Ipr2 Rated primary current of the current transformer
184 OMICRON
Current transformer tests
Setting Description
CT Excitation Measurement Settings
Test frequency Frequency of the output signal
Noise suppression Select the check box to activate an interference filter.
CT Winding Resistance Sec Measurement Settings
Perform winding resistance Activate the check box to perform a supplementary winding resistance
measurement measurement (optional for IEEE C57.13).
Temperature compensation for Cu1
Winding temperature Temperature of the transformer’s winding
Reference temperature Reference temperature to be used for temperature correction
Assessment settings
Manual Select for manual assessment of the measurement results
Automatic According to IEEE C57.13 the measurement will be assessed as failed
if:
Composite error @ Isr > 3 %
or
Composite error @ 20 x Isr > 10 %.
1. Only available if Perform winding resistance measurement check box is activated
Setting Description
Tap Identification of the tap under test
Ipr Rated primary current of the current transformer
Isr Rated secondary current of the current transformer
CPC output DC current output of the CPC 100
I test Test current at the primary side of the current transformer
I DC Measured current
V DC Measured voltage
OMICRON 185
CPC 100 PTM User Manual
Setting Description
R meas Measured resistance
R corr Corrected measured resistance
In use Tap on which the CT is operated
Assessment Measurement assessment
1. Only available if Perform winding resistance measurement check box is activated
Setting Description
Tap Identification of the tap under test
Ipr Rated primary current of the current transformer
Isr Rated secondary current of the current transformer
I max Maximum test current
V max Maximum test voltage
I knee Knee point current
V knee Knee point voltage
Knee point calculation Method used for the knee point calculation
In use Tap on which the CT is operated
Assessment Measurement assessment
Setting Description
Tap Identification of the tap under test
Ipr Rated primary current of the current transformer
Isr Rated secondary current of the current transformer
Composite error @ Isr Composite error at rated secondary current
Calculated on the basis of the excitation curve measurement and the
asset’s Isr and Vb values.
Composite error @ 20 x Isr Composite error at 20 x rated secondary current
Assessment Measurement assessment
186 OMICRON
Voltage transformer tests
Data Description
Upn Rated primary voltage of the voltage transformer
Usn Rated secondary voltage of the voltage transformer
V test Test voltage at the primary side of the voltage transformer
Test frequency Test frequency of the output signal
OMICRON 187
CPC 100 PTM User Manual
Data Description
V prim Measured voltage at the primary side of the voltage transformer
V sec Measured secondary voltage of the voltage transformer
Ratio Measured ratio of the voltage transformer
Ratio dev Deviation of the measured ratio from the rated ratio
Phase Measured phase displacement between the primary and secondary
voltage
Polarity Polarity status
Assessment Measurement assessment
Setting Description
Measurement settings
Test frequency Test frequency
Setting Description
Upn Rated primary voltage of the voltage transformer
Usn Rated secondary current of the voltage transformer
V test Test voltage
V meas Measured burden voltage
I meas Measured burden current
Phase Measured phase displacement
Burden (@ Vtest) Burden based on Vtest
Burden (@ Usn) Burden based on Usn
cosφ Cos φ of phase angle
Assessment Measurement assessment
188 OMICRON
Rotating machine tests
Setting Description
Detect capacitance ► Click Yes if you do not know the test objects capacitance and want
to measure it before testing.
This will add the Capacitance tab to the Measurements section. In this
tab you can perform a measurement to detect the capacitance before
performing the Stator Winding test.
Capacitance of test object ► Enter the test object’s capacitance.
If you measure the capacitance before the test (see
Detect capacitance above), this field will be filled in automatically after
the measurement is completed.
Number of CP CR500 coils (at <test frequency>)
► Enter the number of available coils, depending on the number and types of CP CR500 available.
The CP CR500 comes with one of the following inductor combinations:
a) 2 x 40 H
b) 1 x 40 + 1 x 80 H
c) 2 x 80 H
Example:
1 x CP CR500 type a
1 x CP CR500 type b
= inductances of 3 x 40 H and 1 x 80 H
If freq. = 50 Hz, test capacitance = 250 nF and max. Vtest = 10 kV:
Primary Test Manager recommendation: connection of 1 x 40 H coil.
OMICRON 189
CPC 100 PTM User Manual
Table 18-2: Stator Winding PF/DF & CAP – Settings and conditions
Setting Description
Measurement settings
Test frequency ► Enter the test frequency.
This value is also used for the calculation of the necessary number of
CP CR500 coils.
Sweep settings
Voltage sweep (tip-up) Sweep profile:
None or OMICRON expertise
• None: no voltage sweep
• OMICRON expertise: sweep voltages dynamically distributed within
the asset-dependent voltage range for optimum results
Sweep profiles ► Click the pen button to create a voltage sweep profile.
► Add up to 30 measurement points with individual output voltages.
Double-click a value to change it.
► Mark a favorite to use it as the default sweep profile for future
tests.
Note: The predefined profiles cannot be edited or deleted.
The default voltage sweep profile is OMICRON expertise.
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Device settings
Enable shield check ► Activate the check box if you want the CPC 100 to check whether the
shield of the high-voltage cable is connected.
Use beeper ► Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Custom test conditions ► Activate the check box to set test conditions differing from the global
test conditions.
Winding temperature Temperature of the machine’s winding
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
190 OMICRON
Rotating machine tests
Setting Description
Capacitance1
Measurement Measurement procedure
Test mode Test mode according to IEEE Std 62-1995
Sweep Disabled for the capacitance measurement
V test Test voltage
Freq. Test frequency
V out Measured output voltage
I tot Measured current in the parallel resonance circuit
Watt losses Measured losses
PF meas/ Measured power factor/dissipation factor
DF meas2, 3
Cap. meas3 Measured capacitance
Measurements
Measurement Measurement procedure
Test mode Test mode according to IEEE Std 62-1995
Sweep Setting selected under Sweep settings
V test Test voltage
I out Measured output current
Watt losses Measured losses
PF meas/ Measured power factor/dissipation factor
DF meas2, 3
Cap. meas3 Measured capacitance
Assessment Measurement assessment
1. Only available if Detect capacitance is set to Yes.
2. Depending on the standard selected in the Primary Test Manager settings (see 4.1.1 "Settings" on page 19)
3. According to IEC 60034-27-33 and IEEE 286
OMICRON 191
CPC 100 PTM User Manual
Setting Description
Frequency Frequency of the input signal
Current Input current
Reduction factor Value specific to the site
► Measure the reduction factor on site or enter 1 as the worst-case
value.
Input source OMICRON input device with or without accessories
► To mark the injection line on the map, press Draw injection line.
Setting Description
Distance Distance to the reference point
Voltage Voltage at nominal frequency
Details
Z Impedance at nominal frequency
VStep Step voltage
V Voltage
192 OMICRON
Grounding system tests
Setting Description
Frequency Frequency of the input signal
Current Input current
Reduction factor Value specific to the site
► Measure the reduction factor on site or enter 1 as the worst-case
value.
Add. considered resistance Additional resistance considered for the measurement (e. g. clothes,
floor conditions), depending on the applicable standard
Standard Standard applicable for the measurement
Body current limit acc.1 Standard applicable for the body current limit
Input source OMICRON input device with or without accessories
Req. input impedance
Perm. body current
Perm. touch voltage
Required/permitted values depending on the settings above
Perm. step voltage1
Perm. hand-to-hand
voltage1
1. Only for Standard IEEE 80/81
► To mark the injection line on the map, press Draw injection line.
Setting Description
Location Id Location number for reporting
Location Description field for the measurement location
Input impedance Input impedance on the HGT1
Scenario Type of measurement per measurement point
Permissible touch voltage
Permissible step voltage Required/permitted values depending on the Settings and conditions
(Table 19-3 above)
Permissible hand-to-hand
touch voltage
Voltage Voltage at nominal frequency
OMICRON 193
CPC 100 PTM User Manual
DANGER
Death or severe injury caused by high voltage or current
Wrong test settings and/or a faulty test procedure may damage the test set and the asset
under test and can result in personal injury or death of the operating staff.
► Thoroughly review planned steps and test settings before performing a manual test.
Note: Depending on your settings, some test names include the power factor (PF), the dissipation factor
(DF), or the tangent delta (Tanδ). The dissipation factor and the tangent delta are identical
characteristics of the primary asset under test. For your convenience, with Primary Test Manager you
can use your preferred naming. You can also select some test names to match your regional
conventions (see 4.1.1 "Settings" on page 19).
194 OMICRON
Optional manual tests
Setting Description
Test conditions
Test object temperature Temperature of the test object
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Calculations
PI calculation Calculation of polarization index
Time 1 In the standard PI calculation, the testing device is applied and insulation
resistance measurements are taken after 60 seconds (Time 1) and 600
Time 2
seconds (Time 2).
The polarization index (PI) is calculated as follows:
R 600
PI = -----------
R 60
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction temp. Temperature correction factor
OMICRON 195
CPC 100 PTM User Manual
Setting Description
Test data To import a file containing test data:
► Press Add to browse your PC and add data from a file.
To directly import data from a measurement file:
► Open the file on your computer.
► In the file press CTRL+A to mark all content, then press CTRL+C to
copy.
► In Primary Test Manager press Paste from clipboard.
The results may take a few seconds to load.
Measurement Name or number of the measurement
PI Polarization index
DAR Dielectric absorption ratio
Time Time at which the given values were recorded
Voltage
Voltage and current values recorded at the Time specified in the first
V DC
column
I DC
196 OMICRON
Optional manual tests
Setting Description
Measurement settings
Default frequency Default test frequency
Show results Select the results you want to display from the list.
All measurement results are stored and can be displayed by selecting
them from the list.
Noise suppression settings
Averaging (no. points) Number of averaged measurements
Bandwidth CPC 100 filter bandwidth
Device settings
Enable shield check Select the Enable shield check check box if you want that the CPC 100
checks whether the shield of the high-voltage cable is connected.
Use beeper Select the Use beeper check box if you want to use the CP TD1’s
beeper during the measurement.
Test conditions
Ambient temperature Ambient temperature on site
Test object temperature Temperature of the test object
Humidity Relative ambient humidity
Weather Weather during the test
Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction factor Temperature correction factor
Use reference voltage1 Select the Use reference voltage check box to extrapolate the I out and
Watt losses results for the specified reference voltage.
Reference voltage1 Reference voltage for extrapolation of measurement results
OMICRON 197
CPC 100 PTM User Manual
The following tables describe the TanDelta – PF/DF/Tanδ & CAP measurement data.
Data Description
No.1 Number of the measurement
Note: To add a measurement point to a measurement, click Add meas. point. To add a measurement
to the TanDelta – PF/DF/Tanδ & CAP test, click Add measurement.
Table 20-5: TanDelta – PF/DF/Tanδ & CAP common measurement data (PF/DF/Tanδ, Cap., watt
losses)
Data Description
Watt losses Measured losses
PF meas/ Measured power factor, dissipation factor, or tangent delta
DF meas/
Tanδ meas1
PF corr/ Corrected measured power factor, dissipation factor, or tangent delta
DF corr/
Tanδ corr1
Cap. meas Measured capacitance
1. Set by the regional conventions (see 4.1.1 "Settings" on page 19).
198 OMICRON
Optional manual tests
Data Description
Z phase Phase of the measured impedance
Z abs Magnitude of the measured impedance
Data Description
Reactive power Measured reactive power Q
Apparent power Measured apparent power S
Table 20-8: TanDelta – PF/DF/Tanδ & CAP measurement data (Cp, Rp)
Data Description
Cp Measured parallel capacitance
Rp Measured parallel resistance
Data Description
Cp Measured parallel capacitance
Quality factor Measured quality factor
Table 20-10: TanDelta – PF/DF/Tanδ & CAP measurement data (Ls, Rs)
Data Description
Ls Measured series inductance
Rs Measured series resistance
Data Description
Ls Measured series inductance
Quality factor Measured quality factor
OMICRON 199
CPC 100 PTM User Manual
Support
When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
200 OMICRON