possible configuration of ALARM and FAULT re-


lays parallel connection

1 2 3 4 5 6 7 8 9 10 11

Fig.3

2 protection relays
Dossena S.n.c

1) TECHNICAL SPECIFICATIONS

AUXILIARY POWER SUPPLY

• Rated voltage 24-240 Vac-dc


• Maximum ratings 20-270 Vac-dc

INPUTS OUTPUTS

• 3 or 4 inputs RTD Pt100 sensors-3 • 2 alarm relays (ALARM-TRIP)


wires • 1 alarm relay for fan control (FAN)
• removable rear terminals • 1 alarm relay for sensor fault or working
• input channels protected against elec- anomaly (FAULT)
tromagnetic noises and spikes • output contacts capacity: 5A-250 Vac
• sensors length cables compensation up res.
to 500 m (1mm²)
TEST AND PERFORMANCES DISPLAYING AND DATA MANAGEMENT

• Assembling in accordance with CE • 1 display 13 mm high with 3 digits for


rules displaying temperatures
• Protection against electrical and mag- • LED for displaying reference channel
netic noises: CEI-EN50081-2/50082-2 • LED indicating alarm or trip channel
• Dielectric strength: 2500 Vac for 1 min. • LED indicating fault
from relays to sensors, relays to power • Temperature monitoring from 0-200°C
supply, power supply to sensors • 2 alarm thresholds
• Accuracy: ± 1% full scale, ±1 digit • 2 alarm ON-OFF thresholds for fan con-
• Ambient operating temperature: -20°C trol
to 60°C • Sensors diagnostic (Fcc-Foc-Fcd)
• Humidity: 90% non-condensing • Entering the programming by frontal
• ABS self-extinguishing housing-NORYL push button
94VO • Automatic output from programming cy-
• Opt. Frontal plastic protection cle after 1 minute of no operation
• Opt. Protection treatment of electronic • Wrong programming automatic display
part • Programmed data call out
• Frontal polycarbonate-IP65 • Possibility of setting automatic channel
• Burden: 3VA scanning, hottest channel, manual scan-
• Data storage: 10 years minimum ning
• Digital linearity of sensors signal • Maximum temperatures and alarms stor-
• Self-diagnostic circuit age

DIMENSIONS

• 96x96 mm-DIN43700- depth 140mm


(with rear terminals)

protection relays 3
Dossena S.n.c
2) MOUNTING

Make a hole with the dimensions of 92x92 mm in the panel plate.


Fasten firmly the unit by the fixing blocks included with each unit.

3) POWER SUPPLY

The T-154 unit has a universal power supply. It can be supplied with 24 to 240 Vac or dc
without respect to polarities.
The ground cable must be fixed to terminal # 41.

ATTENTION: the unit may be damaged by overvoltage when power is supplied directly
form the secondary of the transformer it is monitoring. This may occur when the 220V is
obtained directly from the secondary winding and there are fixed capacitors online.

4) ALARMS AND FAN CONTROL ELECTRICAL CONNECTIONS

Take the removable terminal board off the unit before wiring.
ALARM and TRIP relays energize only when the prefixed temperature limits are reached
(NO Fail Safe) or reset when the prefixed temperature limits are reached (Fail Safe).

In order to protect the electronic apparatus, we suggest the application of the elec-
tronic dischargers of the series PT-73 mono or double phase.
Alternatively, we suggest the application of a 24 Vac or better 24 Vdc power sup-
ply.

The FAULT relay always energizes when the apparatus is powered and it resets when the
Pt100’s are damaged or when there is no power voltage.
The FAN relay can be used for fan control or else it can be included in the conditioning cir-
cuit of the transformer box.

5) THERMOMETRIC SENSORS CONNECTION

Each Pt100 sensor has three conductors : one white and two red (CEI 75.8)
Fig.1 shows the disposition in the terminal board of the connection cables to the unit.
Channel 2 must be always referred to the central column of the transformer.
Channel 4 must be always referred to the core of the transformer or else to the ambient
Pt100 sensor, if you want to monitor the temperature of the transformer box through the
T-154 unit.

4 protection relays
Dossena S.n.c
6) MEASURE SIGNALS TRANSPORT

All the transport cables of the Pt100 measure signals must absolutely:

• be divided from the power ones


• be realized with shielded cable with twisted conductors
• have a section of min 0.5 mm²
• be twisted if you have no shield
• be firmly fixed in the terminal board
• have tinned or silvered conductors

All units of the “T” series have the sensors linearization with a max error of 1% v.f.s..

It’s available a special cable for the measure signal transport with all the protection
requirements in accordance with CEI Norms: mod. CT-ES

7) THERMOMETRIC SENSORS DIAGNOSTIC

In the event one of the thermometric sensors installed on the machine to protect is dam-
aged, the FAULT relay energizes immediately, the ALARM and TRIP LED’s of the dam-
aged channel (Chn) lighten and the FAULT LED is lightening.
The screen will automatically display a message showing the fault condition:

• Fcc sensor is short circuited


• Foc sensor is open

During the unit normal operation, if the Fcd/YES function has been selected, the display
show Fcd indicating that a sensor is damaged and the LED corresponding to the affected
channel will lighten (Chn).
The FAULT relay energizes giving a signal to the operator.
After the replacement of the damaged sensor, you can RESET the alarm pushing RESET
until the display shows the message RST.

8) TEMPERATURES DIAGNOSTIC

When one of the thermometric sensors surveys a temperature exceeding by 1°C the alarm
limit, after 4 seconds the ALARM relay will energize and the ALARM LED of the affected
channel (Chn) will switch on.
The same occurs when the TRIP temperature limit is detected: the TRIP relay energizes
and the TRIP LED corresponding to the affected channel is lightening.
When the surveyed temperature declines of 1°C below the prefixed limit for the ALARM
and TRIP switching , the relays de-energize and the respective LED’s switch off.

protection relays 5
Dossena S.n.c
9) COOLING-FAN CONTROL

The T-154 unit, if suitably programmed, can control the ON-OFF of the transformer fans
according to the set temperature values.
The fans of the machine can be controlled in two different ways:

• using the temperatures surveyed by the sensors on the three columns


Channel 1.2.3
ALARM and TRIP LED CH1.2.3 illuminated
(e.g. ON at 80°C - OFF at 70°C)

• by an additonal sensor (CH4/YES) for the ambient temperature inside the transformer
box.
CHF 4
ALARM e TRIP LED Ch4 illuminated
(e.g. ON at 40°C - OFF at 30°C)

Press UP or DOWN key to select this function.

10) FAN TEST

By programming (hxx) you can establish to have the fans set for 5 minutes every “xx”
hours, independently on columns or ambient temperature values.
This function has the purpose to verify periodically the fans working, when they are not in
use.
By setting h00 this functions is disabled.

11) DISPLAY MODE

By pressing DISPLAY MODE you can select one of the three display modes:

• AUTO : the display shows automatically the temperature of the hottest channel.
• MAN : each channel may be viewed manually by pressing the UP or DOWN key.
• T.MAX : the unit shows the max. temperature recorded by the sensors and any alarm
recorded after the last reset.

12) WORKING PROGRAM CONTROL

To review the entered values momentarily press PRG key and continue to do so advanc-
ing to each programmed value. Press ENT to return to normal operating mode.

6 protection relays
Dossena S.n.c
13) LAMP TEST

It is advisable to carry out this test on a regular basis to ensure all lamps are functioning
normally. Pressing the TEST key at any time allows the user to test all lamps.

If any lamp is not functioning the unit must be returned for repair.

14) ALARM RELAYS TEST

All relays may be tested using the following procedure.


Press and hold the TEST key for 5 seconds. Initially all LED’s illuminate, changing to the
main screen display flashing TST.
Release the test key when the yellow relay test LED illuminates.
The screen display will show the relay selected for testing and the respective LED will be
illuminated.
The relays to test will be indicated on the display by:

• “Fan” :cooling relay


• “Flt” :Pt100 fault relay
• “Alr” :alarm relay
• “trP” :trip relay

Use the Scroll UP or DOWN keys to make the selection. Press the SET key to perform the
test on the selected relay. To reset press the RESET key.
To discontinue operation and revert to normal operation, press the TEST key.
At the start of the test, a timer is automatically initiated which reverts the unit to normal op-
eration if no inputs are detected for a period of five minutes.

15) ALARM RELAY EXCLUSION

The alarm relay will change contact state when the alarm set point temperature value is
reached. An illuminated alarm LED provides indication of the affected channel. To reset
the relay contact, press the RESET key. The alarm LED corresponding to the affected
channel will start flashing to indicate that an alarm temperature value has been reached. If
the set point alarm value is exceeded up to a value of 5 °C below the set trip threshold, the
alarm relay will change contact state again and the alarm LED will illuminate. Once again
press the RESET key to reset the relay contact. When the trip set point temperature value
is reached, the trip relay will change contact state and both the yellow alarm and the red
trip LED’s illuminate.

16) IMPORTANT NOTICE

Before conducting the insulation test, disconnect the power supply to the unit to avoid
damage.

protection relays 7
Dossena S.n.c
17) PROGRAMMING
IMPORTANT: PROGRAM LED switched off: VISUALIZATION Mode
PROGRAM LED illuminated: PROGRAMMING Mode

N° KEY DISPLAY NOTES


To begin programming press and hold
PRG/SET.
1 PRG/SET PRG will flash for 7 sec. When PRG Program LED will light
stops flashing, default alarm setpoint will
appear on display.

2 Enter the desired Limit setpoint.

3 PRG/SET TRIP set T° appears

4 Enter the desired Trip setpoint.

5 PRG/SET “FAN” appears on display

YES: FAN contacts enabled


6 Enter FAN YES or NO
NO: FAN contacts disabled

7 PRG/SET OFF appears on display

8 PRG/SET The OFF T° appears


only if YES was chosen at step
9 Enter desired setpoint for fan to turn off
6.

10 PRG/SET ON appears on display

11 PRG/SET The ON T° appears


Enter the desired temperature for fan to only if YES was chosen at step
12
turn on 6.

13 PRG/SET CH4 appears on the display

YES: Ch4 enabled


14 Enter CH4 YES or NO
NO: CH4 disabled
Status of FAN control will appear on the
15 PRG/SET
display as CHF
16 set up CH 1,2,3, or CH4 respective LED alight
Status of FAN control TEST will appear
17 PRG/SET
on the display as h00
only if at step 6 you chose YES
18 set up the number of hours
h00 = function disabled
19 PRG/SET Fcd appears on display
Fcd YES = unit will indicate
20 Enter Fcd YES or NO damaged sensor. Fcd NO =
indicator off.

21 PRG/SET PRG appears on display

Prg NO = program cannot be


22 set up Prg YES or no
changed
ENT Programming is completed. Press ENT to The unit will perform the light
23
PRG/SET return to normal operating mode. test.

8 protection relays
Dossena S.n.c
18) WARRANTY

The “T” series units are warranted for a period of 12 months from the delivery date
marked on the unit.
Warranty is limited to repair or replacement of the defective products and no contingent
liabilities will be accepted.
Warranty will be voided if the unit is found to be tampered with or when it has been dam-
aged as a result of incorrect input or power supply connections (out of the max working
limits 20+270 Vac-dc). Warranty will be voided if the unit is damaged as a result of transi-
tory overvoltages. Freight expense is not covered under warranty.
In case of dispute, the qualified FORUM is the one in Milan.

19) PT100 EXTENSION CABLE: TECHNICAL SPECIFICATIONS

Cable 20xAWG 20/19 cu/stg


Section 0.55 mm²
Antiflame Insulation PVC105
In accordance with CEI 20.35 IEC 332.1
Max. working temperature: 105°C
Conformation : 4 terns of the numbered conductors (1-1-1.........4-4-4)
RRW twisted and coloured conductors
Shield cu/stg
PVC Antiflame protecting covering
External diameter 9.0 mm
Skeins of 100 m

20) PROGRAMMING REHABILITATION IN CASE OF BLOCK (Prg no)

In the event program access is blocked the display will show SET and then display “noP”.
To gain access, press the ENT key and return to normal operation. Touch the PRG key
and then, press and hold the TEST key for approximately 7 seconds until the flashing
PRG screen display ends, and the message nCH is displayed.
NOTE: this procedure removes the lockout feature. To block access again, this feature
must be reprogrammed.

protection relays 9
Dossena S.n.c
TROUBLESHOOTING

PROBLEMS CAUSES / SOLUTIONS

The unit will not switch on, with control Check the terminal block for correct installa-
power energized tion. Check for voltage at the terminal block
Channel 4 is indicating fault and display- Wrong programming of the unit.
ing FOC (only three Pt100 sensors are Repeat programming.
connected)
One of the 3/4 channels is indicating fault Check the sensors connection.
and displaying FOC/FCC Look for damaged sensors.
Replace damaged sensor
When switching the unit on-off, the alarm Strong electrical noise is being picked up on
and trip relays energize the power line.
Install a transient suppressor (PT-73.)
Check to ensure the shield of the sensor
cable is connected to the panel ground.
Install shielded cable (Mod. CT-ES) or twist
the sensor conductors.
All the sensors are displaying FCC. Wrong wiring connections. The terminal
block is upside-down.
The temperature indicated by one or The sensors are defective.
more channels is wrong. Check the sensor resistance with an Ohme-
tre.
The unit is calibrated incorrectly.
Return for repair.
With a control power source of 24 VDC Check the input voltage is between 20-24
the unit switches off and will not switch VDC.
back on. Reconnect to a stable source of power.
Return if unit does not respond
Sudden activation of the trip relay with Sensor defective (Fcd).
normal operating temperature. Replace the sensor.
One channel caused the occurrence.

10 protection relays
Dossena S.n.c

FIG.1 T-154 ELECTRICAL CONNECTION

Pt100 SENSORS CONNECTION

CH 1 CH 2 CH 3 CH 4

13 14 15 16 17 18 19 20 21 22 23 24

RELAYS CONNECTION

1 2 3 4 5 6 7 8 9 10 11

ALARM TRIP FAULT FAN

Pt100

42 WHITE
POWER SUPPLY
41 24-240 VAC-VDC RED
40 RED

protection relays 11
Dossena S.n.c

T154 TEST DESCRIPTION

The unit was submitted to the following tests during production:

N° Description

1 PC board test

2 Input test

3 Test of relay contacts and outputs

4 Key test

5 Lamp test

6 Calibration at 100 and 200°C (for temperature monitoring units)

7 Software test

8 Burn-in minimum 24h