Instruction Manual: Dossena S.N.C
Instruction Manual: Dossena S.N.C
Instruction Manual: Dossena S.N.C
INSTRUCTION MANUAL
T-154
DOSSENA s.n.c.
Via Federico Barbarossa s/n
26824 Cavenago di Adda
tel. +39 0371 44971
Fax: +39 0371 70202
http://www.dossena.it
R.0 02/12/01
protection relays
Dossena S.n.c
BT MT
220VAC-24VAC
PT-73
FIG.2
T-154
T-154
1 2 3 4 5 6 7 8 9 10 11
Fig.3
2 protection relays
Dossena S.n.c
1) TECHNICAL SPECIFICATIONS
INPUTS OUTPUTS
DIMENSIONS
protection relays 3
Dossena S.n.c
2) MOUNTING
3) POWER SUPPLY
The T-154 unit has a universal power supply. It can be supplied with 24 to 240 Vac or dc
without respect to polarities.
The ground cable must be fixed to terminal # 41.
ATTENTION: the unit may be damaged by overvoltage when power is supplied directly
form the secondary of the transformer it is monitoring. This may occur when the 220V is
obtained directly from the secondary winding and there are fixed capacitors online.
Take the removable terminal board off the unit before wiring.
ALARM and TRIP relays energize only when the prefixed temperature limits are reached
(NO Fail Safe) or reset when the prefixed temperature limits are reached (Fail Safe).
In order to protect the electronic apparatus, we suggest the application of the elec-
tronic dischargers of the series PT-73 mono or double phase.
Alternatively, we suggest the application of a 24 Vac or better 24 Vdc power sup-
ply.
The FAULT relay always energizes when the apparatus is powered and it resets when the
Pt100’s are damaged or when there is no power voltage.
The FAN relay can be used for fan control or else it can be included in the conditioning cir-
cuit of the transformer box.
Each Pt100 sensor has three conductors : one white and two red (CEI 75.8)
Fig.1 shows the disposition in the terminal board of the connection cables to the unit.
Channel 2 must be always referred to the central column of the transformer.
Channel 4 must be always referred to the core of the transformer or else to the ambient
Pt100 sensor, if you want to monitor the temperature of the transformer box through the
T-154 unit.
4 protection relays
Dossena S.n.c
6) MEASURE SIGNALS TRANSPORT
All the transport cables of the Pt100 measure signals must absolutely:
All units of the “T” series have the sensors linearization with a max error of 1% v.f.s..
It’s available a special cable for the measure signal transport with all the protection
requirements in accordance with CEI Norms: mod. CT-ES
In the event one of the thermometric sensors installed on the machine to protect is dam-
aged, the FAULT relay energizes immediately, the ALARM and TRIP LED’s of the dam-
aged channel (Chn) lighten and the FAULT LED is lightening.
The screen will automatically display a message showing the fault condition:
During the unit normal operation, if the Fcd/YES function has been selected, the display
show Fcd indicating that a sensor is damaged and the LED corresponding to the affected
channel will lighten (Chn).
The FAULT relay energizes giving a signal to the operator.
After the replacement of the damaged sensor, you can RESET the alarm pushing RESET
until the display shows the message RST.
8) TEMPERATURES DIAGNOSTIC
When one of the thermometric sensors surveys a temperature exceeding by 1°C the alarm
limit, after 4 seconds the ALARM relay will energize and the ALARM LED of the affected
channel (Chn) will switch on.
The same occurs when the TRIP temperature limit is detected: the TRIP relay energizes
and the TRIP LED corresponding to the affected channel is lightening.
When the surveyed temperature declines of 1°C below the prefixed limit for the ALARM
and TRIP switching , the relays de-energize and the respective LED’s switch off.
protection relays 5
Dossena S.n.c
9) COOLING-FAN CONTROL
The T-154 unit, if suitably programmed, can control the ON-OFF of the transformer fans
according to the set temperature values.
The fans of the machine can be controlled in two different ways:
• by an additonal sensor (CH4/YES) for the ambient temperature inside the transformer
box.
CHF 4
ALARM e TRIP LED Ch4 illuminated
(e.g. ON at 40°C - OFF at 30°C)
By programming (hxx) you can establish to have the fans set for 5 minutes every “xx”
hours, independently on columns or ambient temperature values.
This function has the purpose to verify periodically the fans working, when they are not in
use.
By setting h00 this functions is disabled.
By pressing DISPLAY MODE you can select one of the three display modes:
• AUTO : the display shows automatically the temperature of the hottest channel.
• MAN : each channel may be viewed manually by pressing the UP or DOWN key.
• T.MAX : the unit shows the max. temperature recorded by the sensors and any alarm
recorded after the last reset.
To review the entered values momentarily press PRG key and continue to do so advanc-
ing to each programmed value. Press ENT to return to normal operating mode.
6 protection relays
Dossena S.n.c
13) LAMP TEST
It is advisable to carry out this test on a regular basis to ensure all lamps are functioning
normally. Pressing the TEST key at any time allows the user to test all lamps.
If any lamp is not functioning the unit must be returned for repair.
Use the Scroll UP or DOWN keys to make the selection. Press the SET key to perform the
test on the selected relay. To reset press the RESET key.
To discontinue operation and revert to normal operation, press the TEST key.
At the start of the test, a timer is automatically initiated which reverts the unit to normal op-
eration if no inputs are detected for a period of five minutes.
The alarm relay will change contact state when the alarm set point temperature value is
reached. An illuminated alarm LED provides indication of the affected channel. To reset
the relay contact, press the RESET key. The alarm LED corresponding to the affected
channel will start flashing to indicate that an alarm temperature value has been reached. If
the set point alarm value is exceeded up to a value of 5 °C below the set trip threshold, the
alarm relay will change contact state again and the alarm LED will illuminate. Once again
press the RESET key to reset the relay contact. When the trip set point temperature value
is reached, the trip relay will change contact state and both the yellow alarm and the red
trip LED’s illuminate.
Before conducting the insulation test, disconnect the power supply to the unit to avoid
damage.
protection relays 7
Dossena S.n.c
17) PROGRAMMING
IMPORTANT: PROGRAM LED switched off: VISUALIZATION Mode
PROGRAM LED illuminated: PROGRAMMING Mode
8 protection relays
Dossena S.n.c
18) WARRANTY
The “T” series units are warranted for a period of 12 months from the delivery date
marked on the unit.
Warranty is limited to repair or replacement of the defective products and no contingent
liabilities will be accepted.
Warranty will be voided if the unit is found to be tampered with or when it has been dam-
aged as a result of incorrect input or power supply connections (out of the max working
limits 20+270 Vac-dc). Warranty will be voided if the unit is damaged as a result of transi-
tory overvoltages. Freight expense is not covered under warranty.
In case of dispute, the qualified FORUM is the one in Milan.
In the event program access is blocked the display will show SET and then display “noP”.
To gain access, press the ENT key and return to normal operation. Touch the PRG key
and then, press and hold the TEST key for approximately 7 seconds until the flashing
PRG screen display ends, and the message nCH is displayed.
NOTE: this procedure removes the lockout feature. To block access again, this feature
must be reprogrammed.
protection relays 9
Dossena S.n.c
TROUBLESHOOTING
The unit will not switch on, with control Check the terminal block for correct installa-
power energized tion. Check for voltage at the terminal block
Channel 4 is indicating fault and display- Wrong programming of the unit.
ing FOC (only three Pt100 sensors are Repeat programming.
connected)
One of the 3/4 channels is indicating fault Check the sensors connection.
and displaying FOC/FCC Look for damaged sensors.
Replace damaged sensor
When switching the unit on-off, the alarm Strong electrical noise is being picked up on
and trip relays energize the power line.
Install a transient suppressor (PT-73.)
Check to ensure the shield of the sensor
cable is connected to the panel ground.
Install shielded cable (Mod. CT-ES) or twist
the sensor conductors.
All the sensors are displaying FCC. Wrong wiring connections. The terminal
block is upside-down.
The temperature indicated by one or The sensors are defective.
more channels is wrong. Check the sensor resistance with an Ohme-
tre.
The unit is calibrated incorrectly.
Return for repair.
With a control power source of 24 VDC Check the input voltage is between 20-24
the unit switches off and will not switch VDC.
back on. Reconnect to a stable source of power.
Return if unit does not respond
Sudden activation of the trip relay with Sensor defective (Fcd).
normal operating temperature. Replace the sensor.
One channel caused the occurrence.
10 protection relays
Dossena S.n.c
CH 1 CH 2 CH 3 CH 4
13 14 15 16 17 18 19 20 21 22 23 24
RELAYS CONNECTION
1 2 3 4 5 6 7 8 9 10 11
Pt100
42 WHITE
POWER SUPPLY
41 24-240 VAC-VDC RED
40 RED
protection relays 11
Dossena S.n.c
N° Description
1 PC board test
2 Input test
4 Key test
5 Lamp test
7 Software test
Date of shipment:
12 protection relays