The document discusses the design, reliability, operating principles and components of the ORTHOFLUOR FPX SF6 circuit breaker.

The main design principles are modularity, ease of installation, simplicity and flexibility to satisfy different needs.

The main factors contributing to reliability are the use of SF6 gas, innovative development and ALSTOM's quality control.

ORTHOFLUOR FPX

SF6 Circuit Breaker - 7.2 to 24 kV

T&D
Power Distribution

Summary
Design

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

Reliability

Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p. 6


. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

Description of a pole
Selection guide
Characteristics

Operating mechanism

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

Operating mechanism electrical


Size, connection and lay-out
Accessories

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

12-13

14-15-16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.

10

17

ALSTOM : Unequaled
experience
As a pioneer of SF6 switching
techniques in medium voltage,
ALSTOM has acquired unequaled
experience in this field. We thus
have more SF6 circuit breakers in
service throughout the world than
anyone else. This experience give
us a very wide expertise with this
technology. We have build on this
expertise to design our
ORTHOFLUOR FPX range with
following key points:
- Simplicity
- Reliability
- Performance.

ORTHOFLUOR FPX : Simplicity of design

An answer to all your needs


The ORTHOFLUOR FPX circuit
breaker is designed to satisfy a
wide range of needs. Designed for
indoor use, these circuit breakers
are easily and inexpensively
included in many installations such
as open substations,
compartmented or Metal-clad
cubicles, or outdoor shelters.
Our research has been guided by
two main principles:
- modular design,
- ease of installation.

cables, equipped with standard


lugs, can be connected directly to
the connections provided, without
the addition of intermediate parts.
Plug-in contacts can easily be fitted
on these connections for
installation in compartmented or
Metal-clad cubicles. Special
attention was also paid to making
easy access to the terminal block
for operating mechanism electric
circuits.
ORTHOFLUOR FPX circuit breakers
can also be supplied with a truck
that inherently provides the
necessary dielectric earthing
distances.

Modular design
The ORTHOFLUOR FPX circuit
breaker is of separate pole type.
These poles are fixed to a rigid
common frame that also supports
the operating mechanism. This
structure is used to make standard
units with different phase spacings
for the same rating, in order to
better satisfy requirements.

ORTHOFLUOR FPX circuit breaker in a


compartmented cubicle.

Ease of installation
The layout and configuration of HV
connections has been specially
designed to facilitate connection of
the circuit breaker to your
equipment primary circuit. HV

ORTHOFLUOR FPX circuit breaker in an


open substation.
3

ORTHOFLUOR FPX : Maximum reliability

Maximum circuit breaker reliability


is essential to improve service
quality and to reduce maintenance
costs.
Three major points contribute to
making ORTHOFLUOR FPX circuit
breakers extremely reliable:

SF6 gas

SF6 gas has remarkable properties:

Experience acquired by ALSTOM in

- It is an insulating gas that has a


very high dielectric strength; its
dielectric strength is 2.5 times that
of air at the same pressure;

- the use of SF6 gas,


- innovative development,
- ALSTOM Quality in complete
confidence

is now sufficient for it to fully satisfy

the field of breaking in SF6 and the


many tests carried out by large
Users such as EDF in France, show
that the reliability of SF6 switchgear
requirements, to improve service
quality and reduce operating
constraints.

- SF6 is an excellent breaking gas.


It is capable of removing a large
quantity of heat produced by an
arc;
- It cools the arc by radial thermal
conduction, from the center of the
arc towards the outside;
- Its fast and spontaneous
recombination contributes to a
rapid intercontact dielectric
strength recovery.

Low maintenance
The use of SF6 gas helps to design
switchgear requiring minimum
maintenance.
Each pole of the ORTHOFLUOR FPX
circuit breaker forms a sealed
assembly that remains sealed for
the life of the switchgear within the
limits of operation complying with
its mechanical and electrical
characteristics.
Therefore, low maintenance is
limited to simple cleaning
operations and to lubrication of the
operating mechanism.

Assembly of poles in dust free room.

Innovation
ALSTOM is ready to innovate in all
fields whenever it does any
development work, in order to
increase the reliability of its
equipment.
A number of innovations have been
made in the ORTHOFLUOR FPX
circuit breaker, including:
Lower operating forces and
energies,
Fewer parts used in breaking
components,
Standardization of components
and subassemblies.

Quality in complete
confidence
Our ORTHOFLUOR FPX circuit
breakers have been developed and
are made using our Quality
Assurance programs set up at all
levels within our Plant. Our Quality
System is certified conform to the
requirements of ISO 9001standard.
This Quality Assurance is partly
based on the very efficient
production and inspection
processes set up for the
ORTHOFLUOR FPX circuit breaker.

Note particularly:
Assembly of circuit breaker poles
in dust free rooms.
Reinforcement of individual
checks: tightness of poles,
operating speeds, contact
resistances, with computerization
of measurement systems
providing perfect traceability.
Automation of installation and
checking operations.
Moreover, before shipping, all
circuit breakers are subjected to
individual routine tests as defined in
the IEC standard.

Tightness check of circuit breaker poles.

Automatic check of contact resistances and


operating speeds.
5

Operating principle

1
2

6
3
4

5
Closed position
The current flows between
terminals 1 and 5 of the
equipment through fixed contacts
2 and 4, and mobile contact 3.

Efficient breaking:
thermopuffing
The ORTHOFLUOR FPX circuit
breaker combines two breaking
techniques, thermal expansion and
autopneumatic puffing, developed
and used by ALSTOM in its
previous circuit breaker models.
This principle optimizes the
reliability of switchgear by reducing
the SF6 filling pressure and
reducing the operating energy
necessary at the operating
mechanism.

Start of opening
The arc is initiated between
contacts 4 and 6. The energy
dissipated by the arc increases
the SF6 pressure.

During opening
The SF6 compressed in the
breaking chamber blasts the
arc in two opposite
directions.

Operating safety
ORTHOFLUOR FPX circuit breakers
operate at low pressure. The
internal rise in pressure at the time
of the break caused by compression
and increased gas temperature,
remains low. The break is clean as
a result of the thermodynamic
properties of SF6 gas and the
design of the puffing chamber.

Open position
The breaking space is
occupied by SF6,
ensuring high dielectric
strength.

throughout the life of the unit;


Breaking contacts that are not
highly stressed by the low arc
energy concerned due to:
- the low arcing time;
- instability of the arc roots thanks
to the use of hollow arcing
contacts extinguishing the arc in
different directions;
full separation of arcing contacts
and current carrying contacts.

High endurance
ORTHOFLUOR FPX circuit breakers
have a very high endurance due to:
The intrinsic qualities of the SF6
gas that are maintained
6

Furthermore, the displacement of


mechanical parts is damped by a
hydraulic absorber, such that the
number of circuit breaker
operations is much higher than that
recommended by standards.

Description of a pole

Each pole is composed of:


9

A main circuit that carries the


permanent current. It includes
fixed contacts 2 and 4 and
mobile contact 3.

11

A breaking circuit separate from


the main circuit. This circuit
includes a fixed arcing contact 7
and a mobile arcing contact 6.
These two contacts are equipped
with tungsten alloy end pieces for
long life.
An operating device transmits
energy from the operating
mechanism to the mobile contact.
It contains shaft 11 that activates
connecting rod 8. This rod with
long creepage distance ensures
that guaranteed circuit breaker
insulation values are maintained
throughout its life.
An insulating envelope 10
encloses all active parts and is
closed by cover 9. The fins form
part of the enclosure and follow
pole leakage lines, such that the
dielectric strength of
ORTHOFLUOR FPX circuit
breakers is excellent even when
used in a very polluted
atmosphere.
A pressure switch can also be
installed for each pole as an
option.

1
2

6
7
4

10

FPX 12 25 12 circuit breaker pole


6 Mobile arcing contact
7 Fixed arcing contact
8 Insulating operating rod
9 Cover
10 Pole envelope
11 Operating shaft

Legend:
1 Upper connection
2 Upper fixed contact
3 Main mobile contact
4 Lower fixed contact
5 Lower connection

Selection guide to IEC standard

Rated
voltage
kV

Withstand
voltages
Impulse
kVp

Breaking
capacity
1 min
kV rms.

7,2

60

20

12

75

17,5

24

400A

630A

800A

1250A

1600A

2000A

2500A

3150A

4000A

16
20
25
31,5
40

FPX071604
FPX072004
FPX072504
FPX073104
FPX074004

FPX071606
FPX072006
FPX072506
FPX073106
FPX074006

FPX071608
FPX072008
FPX072508
FPX073108
FPX074008

FPX071612
FPX072012
FPX072512
FPX073112
FPX074012

FPX071616
FPX072016
FPX072516
FPX073116
FPX074016

FPX071620
FPX072020
FPX072520
FPX073120
FPX074020

FPX071625
FPX072025
FPX072525
FPX073125
FPX074025

FPX071631
FPX072031
FPX072531
FPX073131
FPX074031

FPX071640
FPX072040
FPX072540
FPX073140
FPX074040

28

16
20
25
31,5
40

FPX121604
FPX122004
FPX122504
FPX123104
FPX124004

FPX121606
FPX122006
FPX122506
FPX123106
FPX124006

FPX121608
FPX122008
FPX122508
FPX123108
FPX124008

FPX121612
FPX122012
FPX122512
FPX123112
FPX124012

FPX121616
FPX122016
FPX122516
FPX123116
FPX124016

FPX121620
FPX122020
FPX122520
FPX123120
FPX124020

FPX121625
FPX122025
FPX122525
FPX123125
FPX124025

FPX121631
FPX122031
FPX122531
FPX123131
FPX124031

FPX121640
FPX122040
FPX122540
FPX123140
FPX124040

95

38

12,5
16
20
25
31,5

FPX171204
FPX171604
FPX172004
FPX172504
FPX173104

FPX171206
FPX171606
FPX172006
FPX172506
FPX173106

FPX171208
FPX171608
FPX172008
FPX172508
FPX173108

FPX171212
FPX171612
FPX172012
FPX172512
FPX173112

FPX171216
FPX171616
FPX172016
FPX172516
FPX173116

FPX171220
FPX171620
FPX172020
FPX172520
FPX173120

FPX171225
FPX171625
FPX172025
FPX172525
FPX173125

FPX171231
FPX171631
FPX172031
FPX172531
FPX173131

FPX171240
FPX171640
FPX172040
FPX172540
FPX173140

125

50

12,5
16
20
25
31,5

FPX241204
FPX241604
FPX242004
FPX242504
FPX243104

FPX241206
FPX241606
FPX242006
FPX242506
FPX243106

FPX241208
FPX241608
FPX242008
FPX242508
FPX243108

FPX241212
FPX241612
FPX242012
FPX242512
FPX243112

FPX241216
FPX241616
FPX242016
FPX242516
FPX243116

FPX241220
FPX241620
FPX242020
FPX242520
FPX243120

FPX241225
FPX241625
FPX242025
FPX242525
FPX243125

FPX241231
FPX241631
FPX242031
FPX242531
FPX243131

kA rms.

Circuit breaker reference


FPX

Rated normal current

24

25

Conformity with Standards


12

Product
range
Rated voltage (kV)

ORTHOFLUOR FPX circuit breakers


satisfy the requirements of the main
national and international
Standards such us:
NFC 64 100, IEC 56, VDE 0670,
BS 5311.

Breaking capacity at
rated voltage (kA)
Rated current (In = 1250 A)
8

Performances certified by
tests
They have been validated by type
tests performed in recognized test
laboratories. In particular the
following test have been performed:
Rated withstand voltage tests.
Breaking and closing tests.
Short time withstand current tests.
Temperature rise tests.
Mechanical endurance tests.

Characteristics

Rated voltage

7.2 kV et 12 kV

17.5 kV et 24 kV

Breaking capacity

25 kA

> 25 kA

16 kA

Rated SF6 pressure


(bar relative at 20C) (1)

1.2

2.7

1.2

> 16 kA < 31.5 kA

31.5 KA

2.7

3.5

Operating times
- opening (ms)

50

- arcing (ms)

70

- closing (ms)

50

Rated operating sequences

O - 3mn. - CO - 3mn. - CO
O - 0.3sec. - CO - 3mn. - CO
O - 0.3sec. - CO - 15sec. - CO

Mechanical endurance

10 000 C/O

(1) Circuit breaker without pressure switch.

Number of breaks
100 000

Electrical endurance
The electrical endurance of
ORTHOFLUOR FPX circuit breakers
is inversely proportional to the
square of the interrupted current.
The adjacent curve shows the
electrical endurance of the
ORTHOFLUOR FPX circuit breakers.

10 000

1 000

100
25
10

1
1

10

25 31,5 40

100 kA

BRH : An efficient operating mechanism

ORTHOFLUOR FPX circuit breakers


are equipped with a BRH type
operating mechanism. This
mechanism uses energy stored in
springs. It may be delivered with a
manual or electrical reset. This

control mechanism is particularly


suitable for circuit breakers
intended to ensure a cycle of fast
reclosing operation generally
followed by a cycle of slow closing
operation.

BRH mechanism electrical equipment


Standard
Manual tripping and closing

Optical position indicator (circuit breaker


and closing spring position)

Terminal block of
LV auxiliaries

Re-arming motor

Fuses for motor

Options

Closing coil

Shunt trip coil

Second shunt trip coil

Undervoltage tripping coil

K1-3 stricker coil

Auxiliary contacts of
spring position (1 NO/1 NC free)

16 auxiliary contacts (5NO/6NC free)

24 auxiliary contacts (9NO/10NC free)

Anti-pumping relay

Operating counter

Heating resistor

Interlock of the closing by lock

10

Simple and reliable operation


The closing spring is kept armed by
a latch-in. Manual or electrical
release of this latch-in causes:
The closing spring to fully
expand,
the circuit breaker to close
the tripping spring to be charged.
The closing spring can thus be
charged again, with the circuit
breaker closed, which authorizes a
fast reclosing cycle
(0 - 0.3 sec - CO -15 sec - CO).

Easy operation

Operating mechanism electrical specifications

Closing and opening operations


take place:
manually, using a mechanically
operating button located on the
front of the mechanism (1);
electrically, by closing and
tripping coils;
A operating mechanism with an
electrical reset can be reset
manually (2). An indicator on the
front of the operating mechanism
shows:
the position of the circuit breaker
open or closed (3);
the state of the closing spring (4)
armed or not.
An operation counter (5) and the
circuit breaker name plate (6) are
also located on the front of the
operating mechanism.




Rated power supply voltages (V)

Vdc

Vac

48 - 60

120 - 230

110 - 125 - 220


Re-arming motor
Voltage variation range

85 to 110%

85 to 110%

Input power

300 W

300 VA

Start up peak (A)

4 x In

4 x In

Reset time

< 10 s

< 10 s

Voltage variation range

85 to 110%

85 to 110%

Input power

300 W

300 VA

Minimum impulse duration

100 ms

100 ms

Voltage variation range

70 to 110%

85 to 110 %

Input power

80 W

80 VA

Minimum impulse duration

100 ms

100 ms

Voltage range for closing

35 to 85 %

35 to 85 %

Voltage range for tripping

70 to 35 %

70 to 35 %

Input power

24 W

24 VA

Rated current (A)

10

10

Breaking capacity (A)

220V : 2A (L/R 20ms) 10

Closing coil

Tripping coil :
Shunt trip

Undervoltage

Auxiliary contacts

48V : 10A (L/R 10ms)


Heating resistor
Rated voltage

220 Vac

Input power

30 VA

11

BRH mechanism electrical schematic diagram

The schematic diagram shows the circuit breaker in the open position, with closing spring armed.
Re-arming of springs

Items

Fuses
for motor

Motor

Closing coil

Hearting resistor

Earthing

G/Y

17

3
K1

2
S5

9
S5

10

13
14

1
S5

M
11
S5

2
K1

Y1

S1

2
1

1
S4 2
S1

12

10
A

K1

Terminal
block marks X0

24

Tripping

Shunt trip
coil

Anti-pumping

Fm 1

Fm 2

Closing

Spring positions
indication
23
25

Terminal
block marks X0

Second shunt
trip coil
9

26

18

Undervoltage

Stricker coil

11

SF6 pressure control


1st threshold

13

2nd threshold

19

21

11 11 11
S6

S7 S8
12 12 12
21 21 21

13
S1

14

3
S1

S1

Y2

1
Y4
2
10

S7 S8
22 22 22

12

Y3
2

S6

11

1
Y5
2

2
12

14

12

20

22

Terminal block
420

Wiring passage

70

Connection to the terminal

Signalling auxiliary contacts

Standard
27 29

1
S1

3
4

5
6

7
8

31

33 37 41 45

11 13 15

10 12 14 16

28 30

32

Fm : Fuses for motor


K1 : Anti-pumping relay
M1 : Re-arming motor
R : Heating resistor
S1 - S2 - S3 : Auxiliary contacts

Nota : The optional equipments are


represented in red. The items 
and  can not be chosen
simultaneously.

Connection to the terminal


The terminal block is made of
screw-on connection terminals. The
terminals can accept a wire with a
section of maximum 4 mm2.

1
S2

5
6

Option
49 53 57 61

43 39 35 47

34 38 42 46

11 13 15

10 12 14 16

S3

44 40 36 48

In (A)

10 12 14 16

50 54 58 62

S4 : Closing interlock contact


S5 : Spring position contact
S6 - S7 - S8 : SF6 pressure contact
X0 : Terminal block
Y1 : Closing coil

Phases
spacings
X (mm)

51 55 59 63

11 13 15

52 56 60 64

Y2 : Tripping coil
Y3 : Second tripping coil
Y4 : Undervoltage tripping coil
Y5 : K 1-3 stricker coil

3150

3150 < In 4000

180

120

51.5

35

70

210

135

51.5

35

70

250

135

51.5

35

70

254

204

64.5

35

170

300

135

51.5

35

70

350

135

51.5

35

70

13

Size, connection and lay-out

Size
Circuit breaker on frame
x = Phase spacings
x
x

For
circuit breaker
1600 A
620

340

35
(see nota)

A
Size of the reset handle

Circuit breaker on truck

620
340
Reset handle
370

315
70

450

B -10

590

Dimensions in mm

HV connection
Dimensions in mm
Connections
1600 A : Silver-plated copper
1600 A : Silver-plated aluminium
4000 A : Silver-plated copper

In

20
63

1600 A

1600 A

25

20

122 35
35
12,5

12,5
10

18

14

In

3150 A

3150 A

In

27

60
12,5
102
15 30 30 28

4000 A

Possible phase spacings X


Rated
voltage
kV

7.2

In
A

180
mm

210
mm

1600

1600 < In 3150

Phase spacings X
250
254
mm
mm

300
mm

350
mm

3150 < In 4000

1600

1600 < In 3150

12

3150 < In 4000

1600
17.5

1600 < In 3150


3150 < In 4000

1600
24

1600 < In 3150

Un 24 kV
In (A)

Phases
spacings
X (mm)

1600
A

1600 < In 3150

3150 < In 4000

180

644 540

210

644 630

665 630

38

250

644 710

665 710

38

77

42

254

720 756

300

644 810

665 810

38

350

644 910

665 910

38

15

Lay-out
Circuit breaker on frame

4 setting
points E
HM 8 mm

Circuit breaker on truck

Earthing
12 mm
H
G

4 setting
points D
12 mm

Setting
E

Earthing
12 mm
295

165

30

20
Setting
F

1 mm

260

(1)

Blocks (not supplied)

(1) After setting, the running wheels must be


free in rotation

Dimensions in mm
In (A)
Phase
spacings
X (mm)

1600
E

1600 < In 3150


H

3150 < In 4000


J

180

500 478 170 136.5 51.5

500 478 170 136.5 51.5

210

590 568 170 136.5 51.5

590 568 170 136.5 51.5

250

670 648 170 136.5 51.5

670 648 170 136.5 51.5

254

716 694 150 103.5 71.5

300

770 748 170 136.5 51.5

770 748 170 136.5 51.5

350

870 848 170 136.5 51.5

870 848 170 136.5 51.5

Force on floor
< 750 daN on each setting point.

Approximate weights (kg)


1600

1600 < In 3150

3150 < In 4000

Frame

150

210

330

Truck

170

230

350

16

Accessories

Reset handle
This handle is used to manually
reset the operating mechanism.

SF6 filling kit


In some cases in which
ORTHOFLUOR FPX circuit breakers
are delivered by air, the nominal
pressure in poles must be reduced
to below 0.5 bars. This kit is used
to adjust the circuit breaker pole
pressure.

17

A052 - AMT - 09/2002 - - ALSTOM 2000 - The logo ALSTOM and their frameworks are trademarks and service trademark applications of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies - COMIMPRESS - 03 85 32 25 40 - Only documents supplied on order confirmation will be considered binding for manufacturing purposes.

ALSTOM Transmission & Distribution - Appareillage moyenne tension - Boulevard de la Rsistance - B.P. 4019 - 71040 Mcon Cdex 9