FPX
FPX
FPX
T&D
Power Distribution
Summary
Design
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
Reliability
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
Description of a pole
Selection guide
Characteristics
Operating mechanism
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
12-13
14-15-16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .p.
10
17
ALSTOM : Unequaled
experience
As a pioneer of SF6 switching
techniques in medium voltage,
ALSTOM has acquired unequaled
experience in this field. We thus
have more SF6 circuit breakers in
service throughout the world than
anyone else. This experience give
us a very wide expertise with this
technology. We have build on this
expertise to design our
ORTHOFLUOR FPX range with
following key points:
- Simplicity
- Reliability
- Performance.
Modular design
The ORTHOFLUOR FPX circuit
breaker is of separate pole type.
These poles are fixed to a rigid
common frame that also supports
the operating mechanism. This
structure is used to make standard
units with different phase spacings
for the same rating, in order to
better satisfy requirements.
Ease of installation
The layout and configuration of HV
connections has been specially
designed to facilitate connection of
the circuit breaker to your
equipment primary circuit. HV
SF6 gas
Low maintenance
The use of SF6 gas helps to design
switchgear requiring minimum
maintenance.
Each pole of the ORTHOFLUOR FPX
circuit breaker forms a sealed
assembly that remains sealed for
the life of the switchgear within the
limits of operation complying with
its mechanical and electrical
characteristics.
Therefore, low maintenance is
limited to simple cleaning
operations and to lubrication of the
operating mechanism.
Innovation
ALSTOM is ready to innovate in all
fields whenever it does any
development work, in order to
increase the reliability of its
equipment.
A number of innovations have been
made in the ORTHOFLUOR FPX
circuit breaker, including:
Lower operating forces and
energies,
Fewer parts used in breaking
components,
Standardization of components
and subassemblies.
Quality in complete
confidence
Our ORTHOFLUOR FPX circuit
breakers have been developed and
are made using our Quality
Assurance programs set up at all
levels within our Plant. Our Quality
System is certified conform to the
requirements of ISO 9001standard.
This Quality Assurance is partly
based on the very efficient
production and inspection
processes set up for the
ORTHOFLUOR FPX circuit breaker.
Note particularly:
Assembly of circuit breaker poles
in dust free rooms.
Reinforcement of individual
checks: tightness of poles,
operating speeds, contact
resistances, with computerization
of measurement systems
providing perfect traceability.
Automation of installation and
checking operations.
Moreover, before shipping, all
circuit breakers are subjected to
individual routine tests as defined in
the IEC standard.
Operating principle
1
2
6
3
4
5
Closed position
The current flows between
terminals 1 and 5 of the
equipment through fixed contacts
2 and 4, and mobile contact 3.
Efficient breaking:
thermopuffing
The ORTHOFLUOR FPX circuit
breaker combines two breaking
techniques, thermal expansion and
autopneumatic puffing, developed
and used by ALSTOM in its
previous circuit breaker models.
This principle optimizes the
reliability of switchgear by reducing
the SF6 filling pressure and
reducing the operating energy
necessary at the operating
mechanism.
Start of opening
The arc is initiated between
contacts 4 and 6. The energy
dissipated by the arc increases
the SF6 pressure.
During opening
The SF6 compressed in the
breaking chamber blasts the
arc in two opposite
directions.
Operating safety
ORTHOFLUOR FPX circuit breakers
operate at low pressure. The
internal rise in pressure at the time
of the break caused by compression
and increased gas temperature,
remains low. The break is clean as
a result of the thermodynamic
properties of SF6 gas and the
design of the puffing chamber.
Open position
The breaking space is
occupied by SF6,
ensuring high dielectric
strength.
High endurance
ORTHOFLUOR FPX circuit breakers
have a very high endurance due to:
The intrinsic qualities of the SF6
gas that are maintained
6
Description of a pole
11
1
2
6
7
4
10
Legend:
1 Upper connection
2 Upper fixed contact
3 Main mobile contact
4 Lower fixed contact
5 Lower connection
Rated
voltage
kV
Withstand
voltages
Impulse
kVp
Breaking
capacity
1 min
kV rms.
7,2
60
20
12
75
17,5
24
400A
630A
800A
1250A
1600A
2000A
2500A
3150A
4000A
16
20
25
31,5
40
FPX071604
FPX072004
FPX072504
FPX073104
FPX074004
FPX071606
FPX072006
FPX072506
FPX073106
FPX074006
FPX071608
FPX072008
FPX072508
FPX073108
FPX074008
FPX071612
FPX072012
FPX072512
FPX073112
FPX074012
FPX071616
FPX072016
FPX072516
FPX073116
FPX074016
FPX071620
FPX072020
FPX072520
FPX073120
FPX074020
FPX071625
FPX072025
FPX072525
FPX073125
FPX074025
FPX071631
FPX072031
FPX072531
FPX073131
FPX074031
FPX071640
FPX072040
FPX072540
FPX073140
FPX074040
28
16
20
25
31,5
40
FPX121604
FPX122004
FPX122504
FPX123104
FPX124004
FPX121606
FPX122006
FPX122506
FPX123106
FPX124006
FPX121608
FPX122008
FPX122508
FPX123108
FPX124008
FPX121612
FPX122012
FPX122512
FPX123112
FPX124012
FPX121616
FPX122016
FPX122516
FPX123116
FPX124016
FPX121620
FPX122020
FPX122520
FPX123120
FPX124020
FPX121625
FPX122025
FPX122525
FPX123125
FPX124025
FPX121631
FPX122031
FPX122531
FPX123131
FPX124031
FPX121640
FPX122040
FPX122540
FPX123140
FPX124040
95
38
12,5
16
20
25
31,5
FPX171204
FPX171604
FPX172004
FPX172504
FPX173104
FPX171206
FPX171606
FPX172006
FPX172506
FPX173106
FPX171208
FPX171608
FPX172008
FPX172508
FPX173108
FPX171212
FPX171612
FPX172012
FPX172512
FPX173112
FPX171216
FPX171616
FPX172016
FPX172516
FPX173116
FPX171220
FPX171620
FPX172020
FPX172520
FPX173120
FPX171225
FPX171625
FPX172025
FPX172525
FPX173125
FPX171231
FPX171631
FPX172031
FPX172531
FPX173131
FPX171240
FPX171640
FPX172040
FPX172540
FPX173140
125
50
12,5
16
20
25
31,5
FPX241204
FPX241604
FPX242004
FPX242504
FPX243104
FPX241206
FPX241606
FPX242006
FPX242506
FPX243106
FPX241208
FPX241608
FPX242008
FPX242508
FPX243108
FPX241212
FPX241612
FPX242012
FPX242512
FPX243112
FPX241216
FPX241616
FPX242016
FPX242516
FPX243116
FPX241220
FPX241620
FPX242020
FPX242520
FPX243120
FPX241225
FPX241625
FPX242025
FPX242525
FPX243125
FPX241231
FPX241631
FPX242031
FPX242531
FPX243131
kA rms.
24
25
Product
range
Rated voltage (kV)
Breaking capacity at
rated voltage (kA)
Rated current (In = 1250 A)
8
Performances certified by
tests
They have been validated by type
tests performed in recognized test
laboratories. In particular the
following test have been performed:
Rated withstand voltage tests.
Breaking and closing tests.
Short time withstand current tests.
Temperature rise tests.
Mechanical endurance tests.
Characteristics
Rated voltage
7.2 kV et 12 kV
17.5 kV et 24 kV
Breaking capacity
25 kA
> 25 kA
16 kA
1.2
2.7
1.2
31.5 KA
2.7
3.5
Operating times
- opening (ms)
50
- arcing (ms)
70
- closing (ms)
50
O - 3mn. - CO - 3mn. - CO
O - 0.3sec. - CO - 3mn. - CO
O - 0.3sec. - CO - 15sec. - CO
Mechanical endurance
10 000 C/O
Number of breaks
100 000
Electrical endurance
The electrical endurance of
ORTHOFLUOR FPX circuit breakers
is inversely proportional to the
square of the interrupted current.
The adjacent curve shows the
electrical endurance of the
ORTHOFLUOR FPX circuit breakers.
10 000
1 000
100
25
10
1
1
10
25 31,5 40
100 kA
Terminal block of
LV auxiliaries
Re-arming motor
Options
Closing coil
Auxiliary contacts of
spring position (1 NO/1 NC free)
Anti-pumping relay
Operating counter
Heating resistor
10
Easy operation
Vdc
Vac
48 - 60
120 - 230
85 to 110%
85 to 110%
Input power
300 W
300 VA
4 x In
4 x In
Reset time
< 10 s
< 10 s
85 to 110%
85 to 110%
Input power
300 W
300 VA
100 ms
100 ms
70 to 110%
85 to 110 %
Input power
80 W
80 VA
100 ms
100 ms
35 to 85 %
35 to 85 %
70 to 35 %
70 to 35 %
Input power
24 W
24 VA
10
10
Closing coil
Tripping coil :
Shunt trip
Undervoltage
Auxiliary contacts
220 Vac
Input power
30 VA
11
The schematic diagram shows the circuit breaker in the open position, with closing spring armed.
Re-arming of springs
Items
Fuses
for motor
Motor
Closing coil
Hearting resistor
Earthing
G/Y
17
3
K1
2
S5
9
S5
10
13
14
1
S5
M
11
S5
2
K1
Y1
S1
2
1
1
S4 2
S1
12
10
A
K1
Terminal
block marks X0
24
Tripping
Shunt trip
coil
Anti-pumping
Fm 1
Fm 2
Closing
Spring positions
indication
23
25
Terminal
block marks X0
Second shunt
trip coil
9
26
18
Undervoltage
Stricker coil
11
13
2nd threshold
19
21
11 11 11
S6
S7 S8
12 12 12
21 21 21
13
S1
14
3
S1
S1
Y2
1
Y4
2
10
S7 S8
22 22 22
12
Y3
2
S6
11
1
Y5
2
2
12
14
12
20
22
Terminal block
420
Wiring passage
70
Standard
27 29
1
S1
3
4
5
6
7
8
31
33 37 41 45
11 13 15
10 12 14 16
28 30
32
1
S2
5
6
Option
49 53 57 61
43 39 35 47
34 38 42 46
11 13 15
10 12 14 16
S3
44 40 36 48
In (A)
10 12 14 16
50 54 58 62
Phases
spacings
X (mm)
51 55 59 63
11 13 15
52 56 60 64
Y2 : Tripping coil
Y3 : Second tripping coil
Y4 : Undervoltage tripping coil
Y5 : K 1-3 stricker coil
3150
180
120
51.5
35
70
210
135
51.5
35
70
250
135
51.5
35
70
254
204
64.5
35
170
300
135
51.5
35
70
350
135
51.5
35
70
13
Size
Circuit breaker on frame
x = Phase spacings
x
x
For
circuit breaker
1600 A
620
340
35
(see nota)
A
Size of the reset handle
620
340
Reset handle
370
315
70
450
B -10
590
Dimensions in mm
HV connection
Dimensions in mm
Connections
1600 A : Silver-plated copper
1600 A : Silver-plated aluminium
4000 A : Silver-plated copper
In
20
63
1600 A
1600 A
25
20
122 35
35
12,5
12,5
10
18
14
In
3150 A
3150 A
In
27
60
12,5
102
15 30 30 28
4000 A
7.2
In
A
180
mm
210
mm
1600
Phase spacings X
250
254
mm
mm
300
mm
350
mm
1600
12
1600
17.5
1600
24
Un 24 kV
In (A)
Phases
spacings
X (mm)
1600
A
180
644 540
210
644 630
665 630
38
250
644 710
665 710
38
77
42
254
720 756
300
644 810
665 810
38
350
644 910
665 910
38
15
Lay-out
Circuit breaker on frame
4 setting
points E
HM 8 mm
Earthing
12 mm
H
G
4 setting
points D
12 mm
Setting
E
Earthing
12 mm
295
165
30
20
Setting
F
1 mm
260
(1)
Dimensions in mm
In (A)
Phase
spacings
X (mm)
1600
E
180
210
250
254
300
350
Force on floor
< 750 daN on each setting point.
Frame
150
210
330
Truck
170
230
350
16
Accessories
Reset handle
This handle is used to manually
reset the operating mechanism.
17
A052 - AMT - 09/2002 - - ALSTOM 2000 - The logo ALSTOM and their frameworks are trademarks and service trademark applications of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies - COMIMPRESS - 03 85 32 25 40 - Only documents supplied on order confirmation will be considered binding for manufacturing purposes.