SITRANS T
measuring instruments
for temperature
3/74 Accessories
3/2 Product overview 3/74 - Measuring inserts, not explosion
3/6 Transmitter for mounting in sensor protected
head 3/76 - Measuring inserts, explosion
3/6 SITRANS TH100, two-wire system protected
(Pt100) 3/77 - Welding-type protective tubes,
3/9 SITRANS TH200, two-wire system neck tubes and connection heads
universal 3/79 Thermocouples
3/15 SITRANS TH300, two-wire system 3/79 Technical description
universal, HART
3/83 Temperature transmitters for moun-
3/21 SITRANS TH400, fieldbus transmitter ting in the connection head
3/26 Transmitter for rail mounting 3/84 Questionnaire for temperature sen-
3/26 SITRANS TR200, two-wire system sors (resistance thermometers and
universal thermocouples)
3/32 SITRANS TR300, two-wire system 3/85 Straight thermocouples
universal, HART 3/85 - to DIN 43733, with connection head
3/38 SITRANS TW, four-wire system, 3/86 - Individual parts and accessories
universal, HART 3/88 Jacket thermocouples
3/88 - with extension lead
3/50 Transmitter for field mounting with 3/89 - with connection head, form B
temperature sensor
3/90 - with socket
3/50 SITRANS TF2, Digital display ther-
3/87 Individual parts
mometer
3/92 Accessories
3/53 SITRANS TF, two-wire system
3/92 - Cold junction with built-in power
3/53 Field indicator supply unit
3/53 SITRANS TF, Field indicator for 4 to 3/93 - Cold junction thermostat for
20 mA 6 or 12 measuring points
3/94 - Cold junction thermostat for
3/60 Resistance thermometers 12 or 24 measuring points
3/60 Technical description
3/62 Protective tubes, installation 3/95 Resistance thermometers for food,
3/64 Temperature transmitters for moun- pharmaceuticals and
ting in the connection head biotechnology
3/65 Questionnaire for temperature sen- 3/95 Resistance thermometers for instal-
sors (resistance thermometers and lation in pipelines and tanks
thermocouples) 3/99 Resistance thermometers with
3/66 Flue gas resistance thermometers, clamp-on system
with connection head
3/67 Low-pressure screw-in resistance
thermometers, with connection head
3/67 - without neck tube
3/68 - with neck tube
3/69 High-pressure screw-in resistance
thermometers
3/70 High-pressure welding-type resis-
tance thermometer
3/71 Flange-type resistance thermometer
3/71 - with connection head You can download all instructions, cata-
logs and certificates for SITRANS T free
3/72 - with reduced response time, with
of charge at the following Internet
connection head
address:
3/73 Resistance thermometers for damp
www.siemens.com/sitranst
rooms
Siemens FI 01 · 2008
© Siemens AG 2007
■ Overview
Application Mounting of transmitter with Page Software for
Ex protection parameterization
Transmitters for temperature for mounting in sensor heads
Transmitter Sensor
3
SITRANS TH100 Zone 2, Zone 2, 3/6 SIPROM T
Transmitters for Pt100 zone 1 zone 1,
zone 0
• Mounting in sensor head
SITRANS TH400 Zone 2, Zone 2, 3/21 SIMATIC PDM for TH 400 with
Transmitters for connection to zone 1, zone 1, PROFIBUS PA
resistance thermometers, resis- zone 21 zone 0,
tance-based sensors, thermocou- zone 21,
ples and DC voltages up to 0.9 V zone 20
• Fieldbus transmitter
• PROFIBUS PA
• FOUNDATION Fieldbus
3
• SITRANS TH200/TH300
• SITRANS TH100
Flue gas resistance thermometers -50 ... +600 °C (-58 ... +1112 °F) 3/66
High-pressure screw-in resistance thermo- -50 ... +600 °C (-58 ... +1112 °F) 3/69
meters
High-pressure welding-type resistance ther- -50 ... 550 °C (-58 ... +1022 °F) 3/70
mometers
Flange-type resistance thermometers -50 ... +600 °C (-58 ... +1112 °F) 3/71
Resistance thermometers for damp rooms -30 ... +60 °C (-22 ... +140 °F) 3/73
3
Straight thermocouples 0 ... 1250 °C (32 ... 2282 °F) 3/85
Jacket thermocouples with extension lead 0 ... 1100 °C (32 ... 2012 °F) 3/88
Jacket thermocouples with connection 0 ... 1100 °C (32 ... 2012 °F) 3/89
head, form B
Jacket thermocouples with socket 0 ... 1100 °C (32 ... 2012 °F) 3/90
■ Overview ■ Application
Used in conjunction with Pt100 resistance thermometers, the
SITRANS TH100 transmitters are ideal for measuring tempera-
tures in all industries. Due to its compact size it can be installed
in the connection head type B (DIN 43729) or larger.
The output signal is a direct current from 4 to 20 mA that is pro-
3
portional to the temperature.
Parameterization is implemented over the PC using the parame-
terization software SIPROM T and the modem for SITRANS
TH100/TH200. If you already have a "modem for SITRANS TK"
(Order No. 7NG3190-6KB), you can continue using this to pa-
rameterize the SITRANS TH100.
Transmitters of the "intrinsically-safe" type of protection can be
installed within potentially explosive atmospheres. The devices
comply with the Directive 94/9/EC (ATEX), as well as FM and
CSA regulations.
■ Function
The SITRANS TH100 dispenses with electrical isolation and uni- Mode of operation
versal sensor connection to provide a low-cost alternative for
Pt100 measurements. The measured signal supplied by a Pt100 resistance thermome-
ter (2, 3 or 4-wire system) is amplified in the input stage. The volt-
For the parameterization, the SIPROM T software is used in com- age, which is proportional to the input variable, is then converted
bination with the modem for SITRANS TH100/TH200. into digital signals by a multiplexer in an analog/digital converter.
Its extremely compact design makes the SITRANS TH100 ideal They are converted in the microcontroller in accordance with the
for the retrofitting of measuring points or for the use of analog sensor characteristics and further parameters (measuring
transmitters. range, damping, ambient temperature etc.).
The transmitter is available as a non-Ex version as well as for use The signal prepared in this way is converted in a digital/analog
in potentially explosive atmospheres. converter into a load-independent direct current of 4 to 20 mA.
An EMC filter protects the input and output circuits against elec-
■ Benefits tromagnetic interferences.
• Two-wire transmitter
• Assembly in connection head type B (DIN 43729) or larger, or
on a standard DIN rail
• Can be programmed, which means that the sensor connec-
tion, measuring range, etc. can also be programmed
• Intrinsically-safe version for use in potentially explosive areas
8UHI Input
,F 3W 5HVLVWDQFHWKHUPRPHWHU
(0&B ,QSXWOHYHOZLWKSURWHFWLYHFRPSRQHQWV
,& &RQVWDQWFXUUHQWVRXUFH
08; 0XOWLSOH[HU
$' $QDORJGLJLWDOFRQYHUWHU
$' Output
3W (0&B '$ 'LJLWDODQDORJFRQYHUWHU
8, 9ROWDJHWUDQVIRUPHUVFXUUHQW
08;
WUDQVIRUPHUVFRQVWDQWYROWDJH
¦& DQGUHIHUHQFHYROWDJHVRXUFH
(0&B 2XWSXWOHYHOZLWKSURWHFWLYHFRPSRQHQWV
8DX[ $X[LOLDU\SRZHUVXSSO\
,RXW 2XWSXWFXUUHQW
'$
Microcontroller
˩& /LQHDUL]DWLRQIXQFWLRQVDQGVWRUDJH
8UHI RIDOOGDWD
8 (0&B P$ 8DX[,RXW
,
Measured span 25 ... 1050 °C (77 ... 1922 °F) PC operating system: Windows ME, 2000 and XP;
also Windows 95, 98 and 98SE,
Unit °C or °F but only in connection with
Offset programmable: RS-232 modem.
-100 ... +100 °C (-180 ... +180 °F) Factory setting:
Line resistance Max. 20 Ω (total from feeder and • Pt100 (IEC 751) with three-wire circuit
return conductor)
• Measuring range: 0 ... 100 °C (32 ... 212 °F)
Noise rejection 50 and 60 Hz • Error signal in the event of sensor breakage: 22.8 mA
Output • Sensor offset: 0 °C (0 °F)
• Damping 0.0 s
Output signal 4 ... 20 mA, two-wire
Power supply 8.5 ... 36 V DC (30 V for Ex) ■ Selection and Ordering data Order-No.
Max. load (Uaux - 8.5 V)/0.023 A SITRANS TH100 temperature
Overrange 3.6 ... 23 mA, continuously adjust- transmitters for Pt100
able (default value: For installation in the connection
3.84 ... 20.5 mA) head, Type B (DIN 43729)
Two-wire system 4 ... 20 mA, pro-
Error signal (in the event of sensor 3.6 ... 23 mA, continuously adjust-
grammable, without electrical iso-
breakage) able (default value: 3.6 mA or
lation
22.8 mA)
• Without explosion protection } 7NG3211-0NN00 C)
Damping time 0 ... 30 s (default value: 0 s)
• With explosion protection,
Protection Against reversed polarity
"Intrinsic safety" and for zone 2
Resolution 12 bit
- to ATEX } 7NG3211-0AN00 C)
Accuracy at 23 °C (73.4 °F) < 0.1% of span
- to FM (cFMUS) } 7NG3211-0BN00 C)
Temperature effect < 0.1%/10 °C (0.1%/18 °F)
Further designs Order code
Effect of auxiliary power < 0.01% of span/V Please add "-Z" to Order No. and
Effect of load impedance < 0.025% of max. span/100 specify Order code(s)
3
44 (1.73) ,QWHUQDOGLDPHWHU
&HQWHUKROH
33 (1.3)
59,6 (2.35)
DQG $X[LOLDU\SRZHUVXSSO\8DX[RXWSXWFXUUHQW,2XW
DQG 3WVHQVRUIRUFRQQHFWLRQVHH
6HQVRUFRQQHFWLRQDVVLJQPHQW
■ Schematics
DIN rail adaptor, dimensions in mm (inch)
7ZRZLUHV\VWHP 7KUHHZLUHV\VWHP
SDUDPHWHUL]DEOHOLQH
UHVLVWDQFH
8DX[
)RXUZLUHV\VWHP &RQQHFWLRQRIDX[LOLDU\
SRZHUVXSSO\8DX[
■ Application
SITRANS TH200 transmitters can be used in all industrial sec-
tors. Due to their compact size they can be installed in the con-
3
nection head type B (DIN 43729) or larger. The following sen-
sors/signal sources can be connected over their universal input
module:
• Resistance thermometers (two, three or four-wire system)
• Thermocouple elements
• Resistance-based sensors and DC voltage sources
The output signal is a direct current from 4 to 20 mA in accor-
dance with the sensor characteristic.
Transmitters of the "Intrinsically-safe" type of protection can be
Ultra flexible - with the universal SITRANS TH200 transmitter installed within potentially explosive atmospheres (zone 0). Type
• Two-wire devices for 4 to 20 mA of protection Ex n (zone 2) can also be achieved. Explosion-
• Mounting in the connection head of the temperature sensor proof versions for Europe, USA and Canada are also available.
• Universal input for virtually any type of temperature sensor
• Configurable over PC
■ Function
The SITRANS TH200 is configured over a PC. A USB or RS 232
■ Benefits modem is linked to the output terminals for this purpose. The
configuration data can now be edited using the SIPROM T soft-
• Compact design ware tool. The configuration data are then permanently stored in
• Flexible mounting and center hole allow you to select your pre- the non-volatile memory (EEPROM).
ferred type of installation Once the sensors and power supply have been correctly con-
• Electrically isolated nected, the transmitter outputs a temperature-linear output sig-
• Test sockets for multimeters nal and the diagnostics LED displays a green light. In the case
of a sensor short-circuit, the LED flashes red, an internal device
• Diagnostics LED (green/red) fault is indicated by a steady red light.
• Sensor monitoring
open circuits and short-circuits The test socket can be used to connect an ammeter at any time
for monitoring purposes and plausibility checks. The output cur-
• Self-monitoring rent can be read without any interruption, or even without ope-
ning the current loop.
6,75$167+7+
7HVW
7&57'
VHQVRU
$ '
µ& µ& P$ 8DX[,RXW
' $
3
• to IEC 60751 Pt25 to Pt1000 measuring errors")
• to JIS C 1604; a = 0.00392 K-1 Pt25 to Pt1000 Characteristic curve Resistance-linear or special cha-
• to IEC 60751 Ni25 to Ni1000 racteristic
• Two-wire system Parameterizable line resistance • Type T Cu-CuNi to DIN IEC 584
≤ 100 Ω (loop resistance) • Type U Cu-CuNi to DIN 43710
• Three-wire system No balancing required Units °C or °F
• Four-wire system No balancing required Connection
Sensor current ≤ 0.45 mA • Standard connection 1 thermocouple element (TC)
Response time ≤ 250 ms for 1 sensor with open- • Generation of average value 2 thermocouple elements (TC)
circuit monitoring
• Generation of difference 2 thermocouple elements (TC)
Open-circuit monitoring can be switched off TC1 – TC2 or TC2 – TC1)
Short-circuit monitoring can be switched off (value is Response time ≤ 250 ms for 1 sensor with open-
adjustable) circuit monitoring
Measuring range Parameterizable (see table "Digi- Open-circuit monitoring can be switched off
tal measuring errors")
Cold junction compensation
Min. measured span 10 °C (18 °F)
• Internal With integrated Pt100 resistance
Characteristic curve Temperature-linear or special thermometer
characteristic
• External With external Pt100 IEC 60571
Resistance-based sensors (2-wire or 3-wire connection)
Measured variable Actual resistance • External fixed Cold junction temperature can be
Sensor type Resistance-based, potentiome- set as fixed value
ters Measuring range Parameterizable (see table "Digi-
Units Ω tal measuring errors")
Connection Min. measured span Min. 50 ... 100 °C (90 ... 180 °F)
(see table "Digital measuring
• Normal connection 1 resistance-based sensor (R) in errors")
2-wire, 3-wire or 4-wire system
Characteristic curve Temperature-linear or special
• Generation of average value 2 resistance-based sensors in characteristic
2-wire system for generation of
average value mV sensor
3
teristic ignitable and has limited energy"
type of protection
Output
Explosion protection to FM for USA
Output signal 4 ... 20 mA, 2-wire and Canada (cFMUS)
Auxiliary power supply 11 ... 35 V DC (to 30 V with EEx) • FM approval PID 3024169
Max. load (Uaux – 11 V)/0.023 A • Degree of protection IS Cl I, II, III, Div 1, GP ABCDEFG
Overrange 3.6 ... 23 mA, infinitely adjustable T4/T5/T6
(default range: IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6
3.84 mA ... 20.50 mA) NI Cl I, II, III, Div 2, GP ABCDFG
T4/T5/T6
Error signal (e.g. in the event of sen- 3.6 ... 23 mA, infinitely adjustable Cl I, ZN2, GP IIC T4/T5/T6
sor breakage) (default value: 22.8 mA)
Software requirements for
Sample cycle 0.25 s nominal SIPROM T
Damping Software filter 1st order 0 ... 30 s PC operating system Windows ME, 2000 and XP; also
(parameterizable) Windows 95, 98 and 98 SE, but
Protection Against reversed polarity only in connection with RS 232
modem.
Electrically isolated Input against output (1 kVeff)
Factory setting:
Measuring accuracy
• Pt100 (IEC 751) with three-wire circuit
Digital measuring errors See Table "Digital measuring
errors" • Measuring range: 0 ... 100 °C (32 ... 212 °F)
Reference conditions • Fault current: 22.8 mA
• Auxiliary power supply 24 V ± 1 % • Sensor offset: 0 °C (0 °F)
• Load 500 Ω • Damping 0.0 s
• Ambient temperature 23 °C
• Warming-up time > 5 min Digital measuring errors
Error in the analog output (digi- < 0.1 % of span Resistance thermometer
tal/analog converter)
Input Measuring range Min. measu- Digital
Error due to internal cold junction < 0.5 °C (0.9 °F) red span accuracy
Temperature effect < 0.1 % of max. span/10 °C °C (°F) °C (°F) °C (°F)
(18 °F)
to IEC 60751
Power supply effect < 0.005 % of span/V
Pt25 -200 ... +850 10 (18) 0,2 (0.36)
Effect of load impedance < 0.012 % of span/100 Ω (-328 ... +1562)
Long-term drift Pt50 -200 ... +850 10 (18) 0,15 (0.27)
• in the first month < 0.02 % of max. span (-328 ... +1562)
• after one year < 0.03 % of max. span Pt100 ... Pt200 -200 ... +850 10 (18) 0,1 (0.18)
(-328 ... +1562)
• after 5 years < 0.04 % of max. span
Pt500 -200 ... +850 10 (18) 0,15 (0.27)
Rated conditions (-328 ... +1562)
Ambient conditions Pt1000 -200 ... +350 10 (18) 0,15 (0.27)
Ambient temperature range -40 ... +85 °C (-40 ... 185 °F) (-328 ... +662)
Storage temperature range -40 ... +85 °C (-40 ... 185 °F) to JIS C1604-81
Relative humidity < 98 %, with condensation Pt25 -200 ... +649 10 (18) 0,2 (0.36)
(-328 ... +1200)
Electromagnetic compatibility acc. to EN 61326 and NE21
Pt50 -200 ... +649 10 (18) 0,15 (0.27)
Construction (-328 ... +1200)
Material Molded plastic Pt100 ... Pt200 -200 ... +649 10 (18) 0,1 (0.18)
(-328 ... +1200)
Weight 50 g (0.11 lb)
Pt500 -200 ... +649 10 (18) 0,15 (0.27)
Dimensions See "Dimensional drawings" (-328 ... +1200)
Cross-section of cables Max. 2.5 mm² (AWG 13) Pt1000 -200 ... +350 10 (18) 0,15 (0.27)
Degree of protection to IEC 60529 (-328 ... +662)
• Enclosure IP40 Ni 25 to Ni1000 -60 ... +250 10 (18) 0,1 (0.18)
(-76 ... +482)
• Terminals IP00
3 Thermocouple elements
isolation
• Without explosion protection } 7NG3211-1NN00
C)
Input Measuring Min. measured Digital
• With explosion protection,
range span accuracy
"Intrinsic safety" and zone 2
°C (°F) °C (°F) °C (°F)
- acc. to ATEX } 7NG3211-1AN00
Type B 0 ... 1820 100 (180) 2 (5.40) C)
(32 ... 3308) - acc. to FM (cFMUS) } 7NG3211-1BN00
Type C (W5) 0 ... 2300 100 (180) 2 (3.60) C)
(32 ... 4172) Further designs Order code
Type D (W3) 0 ... 2300 100 (180) 2 (3.60) Please add "-Z" to Order No. and
(32 ... 4172) specify Order code(s)
Type E -200 ... +1000 50 (90) 1 (1.80) Customer-specific setting of oper- Y01
(-328 ... +1832) ating data (specify operating data
Type J -210 ... +1200 50 (90) 1 (1.80) in plain text)
(-346 ... +2192) with test protocol (5 measuring C11
Type K -230 ... +1370 50 (90) 1 (1.80) points)
(-382 ... +2498) Accessories Order No.
Type L -200 ... +900 50 (90) 1 (1.80) Modem for SITRANS TH100,
(-328 ... +1652) TH200 and TR200 incl.
Type N -200 ... +1300 50 (90) 1 (1.80) SIPROM T parameterization
(-328 ... +2372) software
Type R -50 ... +1760 100 (180) 2 (3.60) • With USB connection } 7NG3092-8KU
(-58 ... +3200) C)
Type S -50 ... +1760 100 (180) 2 (3.60) • With RS 232 connection } 7NG3092-8KM
(-58 ... +3200) C)
Type T -200 ... +400 40 (72) 1 (1.80) CD for measuring instruments } A5E00364512
(-328 ... +752) for temperature G)
(1)
(1)
3
(2) (2)
59,6 (2.35)
0[
DQG $X[LOLDU\SRZHUVXSSO\8DX[RXWSXWFXUUHQW,2XW
DQG 3WVHQVRUIRUFRQQHFWLRQVVHH6HQVRU
FRQQHFWLRQDVVLJQPHQW
7HVW7HVW 0HDVXUHPHQWRIWKHRXWSXWFXUUHQWZLWKDPXOWLPHWHU DIN rail adaptor, dimensions in mm (inch)
7HVWWHUPLQDO
0RXQWLQJVFUHZ0[
/('IRURSHUDWLRQLQGLFDWLRQ
,QWHUQDOGLDPHWHURIFHQWHUKROH
■ Schematics
Connection of auxiliary
Voltage measurement Current measurement power supply (Uaux)
8DX[
■ Application
3
SITRANS TH300 transmitters can be used in all industrial sec-
tors. Due to their compact size they can be installed in the con-
nection head type B (DIN 43729) or larger. The following sen-
sors/signal sources can be connected over their universal input
module:
• Resistance thermometers (two, three or four-wire system)
• Thermocouple elements
• Resistance-based sensors and DC voltage sources
The output signal is a direct current from 4 to 20 mA in accor-
dance with the sensor characteristic, superimposed by the digi-
tal HART signal.
Transmitters of the "Intrinsically-safe" type of protection can be
"HART" to beat - the universal SITRANS TH300 transmitter installed within potentially explosive atmospheres (zone 0). Type
• Two-wire devices for 4 to 20 mA, HART of protection Ex n (Zone 2) can also be achieved. Explosion-
proof versions for Europe, USA and Canada are also available.
• Mounting in the connection head of the temperature sensor
• Universal input for virtually any type of temperature sensor ■ Function
• Configurable over HART
The SITRANS TH300 is configured over HART. This can be done
■ Benefits using a handheld communicator or even more conveniently with
a HART modem and the SIMATIC PDM parameterization soft-
• Compact design ware. The configuration data are then permanently stored in the
non-volatile memory (EEPROM).
• Flexible mounting and center hole allow you to select your pre-
ferred type of installation Once the sensors and power supply have been correctly con-
• Electrically isolated nected, the transmitter outputs a temperature-linear output sig-
nal and the diagnostics LED displays a green light. In the case
• Test sockets for multimeters of a sensor short-circuit, the LED flashes red, an internal device
• Diagnostics LED (green/red) fault is indicated by a steady red light.
• Sensor monitoring The test socket can be used to connect an ammeter at any time
open circuits and short-circuits for monitoring purposes and plausibility checks. The output cur-
• Self-monitoring rent can be read without any interruption, or even without ope-
• Configuration status stored in EEPROM ning the current loop.
6,75$167+7+
7HVW
7&57'
VHQVRU
$ '
µ& µ& P$ 8DX[,RXW
' $
3
• to IEC 60751 Pt25 to Pt1000 measuring errors")
• to JIS C 1604; a = 0.00392 K-1 Pt25 to Pt1000 Characteristic curve Resistance-linear or special cha-
• to IEC 60751 Ni25 to Ni1000 racteristic
• Two-wire system Parameterizable line resistance • Type T Cu-CuNi to DIN IEC 584
≤ 100 Ω (loop resistance) • Type U Cu-CuNi to DIN 43710
• Three-wire system No balancing required Units °C or °F
• Four-wire system No balancing required Connection
Sensor current ≤ 0.45 mA • Standard connection 1 thermocouple (TC)
Response time ≤ 250 ms for 1 sensor with open- • Generation of average value 2 thermocouples (TC)
circuit monitoring
• Generation of difference 2 thermocouples (TC) TC1 – TC2
Open-circuit monitoring can be switched off or TC2 – TC1)
Short-circuit monitoring can be switched off (value is Response time ≤ 250 ms for 1 sensor with open-
adjustable) circuit monitoring
Measuring range Parameterizable (see table "Digi- Open-circuit monitoring can be switched off
tal measuring errors")
Cold junction compensation
Min. measured span 10 °C (18 °F)
• Internal With integrated Pt100 resistance
Characteristic curve Temperature-linear or special thermometer
characteristic
• External With external Pt100 IEC 60571
Resistance-based sensors (2-wire or 3-wire connection)
Measured variable Actual resistance • External fixed Cold junction temperature can be
Sensor type Resistance-based, potentiome- set as fixed value
ters Measuring range Parameterizable (see table "Digi-
Units Ω tal measuring errors")
Connection Min. measured span Min. 50 ... 199 °C (90 ... 180 °F)
(see table "Digital measuring
• Normal connection 1 resistance-based sensor (R) in errors")
2-wire, 3-wire or 4-wire system
Characteristic curve Temperature-linear or special
• Generation of average value 2 resistance-based sensors in characteristic
2-wire system for generation of
average value mV sensor
3
teristic ignitable and has limited energy"
type of protection
Output
Explosion protection to FM for USA
Output signal 4 ... 20 mA, 2-wire with communi- and Canada (cFMUS)
cation to HART Rev. 5.9
• FM approval PID 3024169
Auxiliary power supply 11 ... 35 V DC (to 30 V with EEx)
• Degree of protection IS Cl I, II, III, Div 1, GP ABCDEFG
Max. load (Uaux – 11 V)/0.023 A T4/T5/T6
Overrange 3.6 ... 23 mA, continuously adjus- IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6
table (default range: NI Cl I, II, III, Div 2, GP ABCDFG
3.84 mA ... 20.50 mA) T4/T5/T6
Cl I, ZN2, GP IIC T4/T5/T6
Error signal (e.g. in the event of sen- 3.6 ... 23 mA, continuously adjus-
sor breakage) table (default value: 22.8 mA) Factory setting:
Sample cycle 0.25 s nominal • Pt100 (IEC 751) with three-wire circuit
Damping Software filter 1st order 0 ... 30 s • Measuring range: 0 ... 100 °C (32 ... 212 °F)
(parameterizable)
• Fault current: 22.8 mA
Protection Against reversed polarity • Sensor offset: 0 °C (0 °F)
Electrically isolated Input against output (1 kVeff) • Damping 0.0 s
Measuring accuracy
Digital measuring errors See Table "Digital measuring
errors" Digital measuring errors
Reference conditions Resistance thermometer
• Auxiliary power supply 24 V ± 1% Input Measuring range Min. measu- Digital accu-
red span racy
• Load 500 Ω
°C (°F) °C (°F) °C (°F)
• Storage temperature 23 °C
to IEC 60751
• Warming-up time > 5 min
Pt25 -200 ... +850 10 (18) 0.2 (0.36)
Error in the analog output (digi- < 0.1% of span
(-328 ... +1562)
tal/analog converter)
Pt50 -200 ... +850 10 (18) 0.15 (0.27)
Error due to internal cold junction < 0.5 °C (0.9 °F)
(-328 ... +1562)
Temperature effect < 0.1% of max. span/10 °C
Pt100 ... Pt200 -200 ... +850 10 (18) 0.1 (0.18)
(18 °F)
(-328 ... +1562)
Power supply effect < 0.005% of span/V
Pt500 -200 ... +850 10 (18) 0.15 (0.27)
Effect of load impedance < 0.012% of span/100 Ω (-328 ... +1562)
Long-term drift Pt1000 -200 ... +350 10 (18) 0.15 (0.27)
(-328 ... +662)
• in the first month < 0.02% of max. span
to JIS C1604-81
• after one year < 0.03% of max. span
Pt25 -200 ... +649 10 (18) 0.2 (0.36)
• after 5 years < 0.04% of max. span (-328 ... +1200)
Rated conditions Pt50 -200 ... +649 10 (18) 0.15 (0.27)
Ambient temperature (-328 ... +1200)
Ambient temperature range -40 ... +85 °C (-40 ... 185 °F) Pt100 ... Pt200 -200 ... +649 10 (18) 0.1 (0.18)
(-328 ... +1200)
Storage temperature range -40 ... +85 °C (-40 ... 185 °F)
Pt500 -200 ... +649 10 (18) 0.15 (0.27)
Relative humidity < 98%, with condensation (-328 ... +1200)
Electromagnetic compatibility acc. to EN 61326 and NE21 Pt1000 -200 ... +350 10 (18) 0.15 (0.27)
Construction (-328 ... +662)
Material Molded plastic Ni 25 to Ni1000 -60 ... +250 10 (18) 0.1 (0.18)
(-76 ... +482)
Weight 50 g (0.11 lb)
Dimensions See "Dimensional drawings"
Cross-section of cables Max. 2.5 mm² (AWG 13)
Degree of protection to IEC 60529
• Enclosure IP40
• Terminals IP00
3 Thermocouples
HART, with electrical isolation
• Without explosion protection } 7NG3212-0NN00
C)
Input Measuring Min. measured Digital
• With explosion protection;
range span accuracy
type of protection:
°C (°F) °C (°F) °C (°F) "Intrinsic safety" and EEx n
Type B 0 ... 1820 100 (180) 2 (5.40) - acc. to ATEX } 7NG3212-0AN00
(32 ... 3308) C)
Type C (W5) 0 ... 2300 100 (180) 2 (3.60) - acc. to FM (cFMUS) } 7NG3212-0BN00
(32 ... 4172) C)
Type D (W3) 0 ... 2300 100 (180) 2 (3.60) Further designs Order code
(32 ... 4172) Please add "-Z" to Order No. and
Type E -200 ... +1000 50 (90) 1 (1.80) specify Order code(s)
(-328 ... +1832) Customer-specific setting of oper- Y01
Type J -210 ... +1200 50 (90) 1 (1.80) ating data (specify operating data
(-346 ... +2192) in plain text)
Type K -230 ... +1370 50 (90) 1 (1.80) with test protocol (5 measuring C11
points)
(-382 ... +2498)
Accessories Order No.
Type L -200 ... +900 50 (90) 1 (1.80)
(-328 ... +1652) CD for measuring instruments } A5E00364512
for temperature G)
Type N -200 ... +1300 50 (90) 1 (1.80)
(-328 ... +2372) with documentation in German,
English, French, Spanish, Italian,
Type R -50 ... +1760 100 (180) 2 (3.60) Portuguese and SIPROM T
(-58 ... +3200) parameterization software
Type S -50 ... +1760 100 (180) 2 (3.60) HART modem
(-58 ... +3200)
• With RS 232 connection } 7MF4997-1DA
Type T -200 ... +400 40 (72) 1 (1.80) D)
(-328 ... +752)
• With USB connection } 7MF4997-1DB
Type U -200 ... +600 50 (90) 2 (3.60) D)
(-328 ... +1112)
SIMATIC PDM operating See Section 9
software
DIN rail adapters for head } 7NG3092-8KA
mV sensor
transmitters
Input Measuring Min. measured Digital (Quantity delivered: 5 units)
range span accuracy
} Available ex stock.
mV mV µV C) Subject to export regulations AL: N, ECCN: EAR99.
mV sensor -10 ... +70 2 40 D) Subject to export regulations AL: N, ECCN: EAR99H.
G) Subject to export regulations AL: N, ECCN: 5D992B1.
mV sensor -100 ... +1100 20 400 Power supply units see "SITRANS I supply units and isolation amplifiers".
The digital accuracy is the accuracy after the analog/digital con-
version including linearization and calculation of the measured
value.
An additional error is generated in the output current 4 to 20 mA
as a result of the digital/analog conversion of 0.1% of the set
span (digital-analog error).
The total error under reference conditions at the analog output is
the sum from the digital error and the digital-analog error (poss.
with the addition of cold junction errors in the case of thermo-
couple measurements).
(1)
(1)
3
(2) (2)
SITRANS TH300, mounting of transmitter on DIN rail
(3)
14 (0.55) 50,5 (1.99)
33 (1.30)
(4)
59,6 (2.35)
0[
DQG $X[LOLDU\SRZHUVXSSO\8DX[RXWSXWFXUUHQW,2XW
DQG 3WVHQVRUIRUFRQQHFWLRQVVHH6HQVRU
FRQQHFWLRQDVVLJQPHQW
7HVW7HVW 0HDVXUHPHQWRIWKHRXWSXWFXUUHQWZLWKDPXOWLPHWHU DIN rail adapter, dimensions in mm (inch)
7HVWWHUPLQDO
0RXQWLQJVFUHZ0[
/('IRURSHUDWLRQLQGLFDWLRQ
,QWHUQDOGLDPHWHURIFHQWHUKROH
■ Schematics
Connection of auxiliary
Voltage measurement Current measurement power supply (Uaux)
8DX[
■ Overview ■ Application
• Linearized temperature measurement with resistance ther-
mometers or thermocouple elements
• Differential, mean-value or redundant temperature measure-
ment with resistance thermometers or thermocouple elements
• Linear resistance and bipolar millivolt measurements
• Differential, mean-value or redundant resistance and bipolar
millivolt measurements 3
■ Function
Features
common
• Mounting in connection head, type B, to DIN 43729, or larger
• Polarity-neutral bus connection
• 24-bit analog-digital converter for high resolution
• Electrically isolated
SITRANS TH400 fieldbus transmitters • Intrinsically-safe version for use in potentially explosive areas
• Special characteristic
Versions:
• Sensor redundance
• for FOUNDATION Fieldbus and
Transmitter with PROFIBUS PA communication
• for PROFIBUS PA
• Function blocks: 2 x analog
The SITRANS TH400 temperature transmitter is a small field bus
transmitter for mounting in the connection head of form B. Exten- Transmitter with FOUNDATION Fieldbus communication
sive functionality enables the temperature transmitter to be pre- • Function blocks: 2 x analog and 1 x PID
cisely adapted to the plant’s requirements. Operation is very • Functionality: Basic or LAS
simple in spite of the numerous setting options. Thanks to its uni-
versal concept it can be used in all industries and is easy to in- Mode of operation
tegrate in Totally Integrated Automation applications.
The following function plan explains the mode of operation of the
Temperature transmitters with type of protection "Intrinsic safety" transmitter.
may be installed within potentially explosive atmospheres
(zone 1) or in zone 0. The devices have an EC type test certifi- The only difference between the two versions of the SITRANS
cate and meet the appropriate harmonized European standards TH400 (7NG3214-... and 7NG3215-...) is the type of fieldbus
(ATEX). In addition they offer approvals for USA (FM) and Can- protocol used (PROFIBUS PA or FOUNDATION fieldbus).
ada (CSA).
Installing SITRANS TH400 in temperature sensors turns them
into complete, bus-capable measuring points; compact - and in
a single device.
7UDQVIRUPHU
,QSXW
,QSXW
2SWLRQDOLQSXWV 'LIIHUHQWLDO
0HDQYDOXH
5HVLVWDQFHWKHUPRPHWHU 5HGXQGDQF\
7HUPLQDOWHPSHUDWXUH
7KHUPRFRXSOH (QJLQHHULQJXQLWV
P9VHQVRU 'LDJQRVWLFIXQFWLRQV
7DEOHOLQHDUL]DWLRQ
5HVLVWDQFHEDVHG 3RO\QRPLDOOLQHDUL]DWLRQ
3URFHVVFDOLEUDWLRQ
(OHFWULFDOO\
LVRODWHG
([SRZHUFLUFXLW
,QSXW
$'
FRQYHUWHU &38 &RPPXQLFDWLRQ %XVFRQQHFWLRQ
,QSXW
3
FRXSOHU
• Type N
• Type R
-180 ... +1300 °C (-292 ... 2372 °F)
-50 ... +1760 °C (-58 ... +3200 °F)
s
6,75$16
7+3$ • Type S -50 ... +1760 °C (-58 ... +3200 °F)
• Type T -200 ... +400 °C (-328 ... +752 °F)
%XVFRQQHFWLRQ to DIN 43710
• Type L -200 ... +900 °C (-328 ... +1652 °F)
%XV • Type U -200 ... +600 °C (-328 ... +1112 °F)
WHUPLQDWRU )281'$7,21)LHOGEXV
to ASTM E988-90
6HJPHQW • Type W3 0 ... 2300 °C (32 ... 4172 °F)
FRXSOHU • Type W5 0 ... 2300 °C (32 ... 4172 °F)
to IEC 60751
s
6,75$16
7+)) • External cold junction compen- -40 ... +135 °C (-40 ... +275 °F)
sation
Sensor fault detection
%XVFRQQHFWLRQ
• Sensor break detection Yes
SITRANS TH400, communication interface • Sensor short-circuit detection Yes, < 3 mV
Temperature transmitter
SITRANS TH400
for installation in the sensor head, with
electrical isolation, order instruction
manual separately.
3
• Bus-capable to PROFIBUS PA
- without explosion protection, } 7NG3214-0NN00
EEx n for zone 2
- with explosion protection „intrinsic } 7NG3214-0AN00
safety to ATEX/FM/CSA“
• Bus-capable to FOUNDATION Fieldbus
- without explosion protection, } 7NG3215-0NN00
EEx n for zone 2
- with explosion protection „intrinsic } 7NG3215-0AN00
safety to ATEX/FM/CSA“
Further designs Order code
Please add „-Z“ to Order No. and specifiy
Order code (s) and plain text.
• Customer-specific setting of operating Y011)
data (specify in plain text)
• With test protocol (5 measuring points) C111)
Accessories Order No.
CD for measuring instruments for } A5E00364512
temperature G)
with documentation in German, English,
French, Spanish, Italian, Portuguese and
SIPROM T parameterization software
SIMATIC PDM operating software see chapter 9
For additional PA components see catalog IK PI
} Available ex stock.
1)
For TH400 FF available soon.
G) Subject to export regulations AL: N, ECCN: 5D992B1.
■ Dimensional drawings
s
1 2
0[
3 6
3-W
4 + - 5
7HUPLQDOV)LHOGEXVFRQQHFWLRQ
7HUPLQDOV6HQVRUFRQQHFWLRQ
■ Schematics
3
7ZRZLUHV\VWHP ,QWHUQDO 7ZRZLUHV\VWHP
FROGMXQFWLRQFRPSHQVDWLRQ
Voltage measurement
0HDQYDOXHGLIIHUHQWLDORU 0HDQYDOXHGLIIHUHQWLDORU
UHGXQGDQF\JHQHUDWLRQ UHGXQGDQF\JHQHUDWLRQDQG
VHQVRULQWZRZLUHV\VWHP FROGMXQFWLRQFRPSHQVDWLRQ
VHQVRULQWKUHHZLUHV\VWHP ZLWKLQWHUQDO3W
LQWZRZLUHV\VWHP 2QHYROWDJHVRXUFH
3URJUDPPDEOHOLQHUHVLVWDQFHIRUWKHSXUSRVHRIFRUUHFWLRQ
0HDVXUHPHQWRIPHDQYDOXHGLIIHUHQWLDODQG
UHGXQGDQF\ZLWKYROWDJHVRXUFHV
■ Overview ■ Application
SITRANS TR200 transmitters can be used in all industrial sec-
tors. Their compact design enables simple mounting on stan-
dard DIN rails on-site in protective boxes or in control cabinets.
The following sensors/signal sources can be connected over
their universal input module:
3
• Resistance thermometers (two, three or four-wire system)
• Thermocouple elements
• Resistance-based sensors and DC voltage sources
The output signal is a direct current from 4 to 20 mA in accor-
dance with the sensor characteristic.
Transmitters of the "Intrinsically-safe" or Ex nAL (zone 2) type of
protection can be installed within potentially explosive atmos-
pheres.
■ Function
The SITRANS TR200 is configured over a PC. A USB or RS 232
Ultra flexible - with the universal SITRANS TR200 transmitter modem is linked to the output terminals for this purpose. The
configuration data can now be edited using the SIPROM T soft-
• Two-wire devices for 4 to 20 mA ware tool. The configuration data are then permanently stored in
• Enclosure for rail mounting the non-volatile memory (EEPROM).
• Universal input for virtually any type of temperature sensor Once the sensors and power supply have been correctly con-
• Configurable over PC nected, the transmitter outputs a temperature-linear output sig-
nal and the diagnostics LED displays a green light. In the case
■ Benefits of a sensor short-circuit, the LED flashes red, an internal device
fault is indicated by a steady red light.
• Compact design
The test socket can be used to connect an ammeter at any time
• Electrically isolated for monitoring purposes and plausibility checks. The output cur-
• Test sockets for multimeters rent can be read without any interruption, or even without ope-
ning the current loop.
• Diagnostics LED (green/red)
• Sensor monitoring
open circuits and short-circuits
• Self-monitoring
• Configuration status stored in EEPROM
• Expanded diagnostic functions, such as slave pointer, opera-
ting hours counter, etc.
• Special characteristic
• Electromagnetic compatibility to EN 61326 and NE21
6,75$167575
7
1
7HVW
6HQVRU
7&57' 2 3
$ '
µ& µ& P$ 8DX[,RXW
' $
4
5 6
■ Technical specifications Response time T63 ≤ 250 ms for 1 sensor with open-
circuit monitoring
Input Open-circuit monitoring Always active (cannot be disab-
Resistance thermometer led)
Measured variable Temperature Short-circuit monitoring Can be switched off (value is
adjustable)
Sensor type
Measuring range Parameterizable, max.
0 ... 2200 Ω (see Table "Digital
3
• to IEC 60751 Pt25 to Pt1000
• to JIS C 1604; a=0.00392 K-1 Pt25 to Pt1000 measuring errors")
• to IEC 60751 Ni25 to Ni1000 Min. measured span 5 ... 25 Ω (see Table "Digital
measuring errors")
• Special type Over special characteristic (max.
30 points) Characteristic curve Resistance-linear or special cha-
racteristic
Sensor factor 0.25 ... 10 (adaptation of the
basic type, e.g. Pt100 to version Thermocouple elements
Pt25 ... Pt1000) Measured variable Temperature
Units °C or °F Sensor type (thermocouples)
Connection • Type B Pt30Rh-Pt6Rh to DIN IEC 584
• Standard connection 1 resistance thermometer (RTD) • Type C W5%-Re to ASTM 988
in 2-wire, 3-wire or 4-wire system
• Type D W3%-Re to ASTM 988
• Generation of average value 2 identical resistance thermome-
ters in 2-wire system for genera- • Type E NiCr-CuNi to DIN IEC 584
tion of average temperature • Type J Fe-CuNi to DIN IEC 584
• Generation of difference 2 identical resistance thermome- • Type K NiCr-Ni to DIN IEC 584
ters (RTD) in 2-wire system
(RTD 1 – RTD 2 or RTD 2 – RTD 1) • Type L Fe-CuNi to DIN 43710
Interface • Type N NiCrSi-NiSi to DIN IEC 584
• Two-wire system Parameterizable line resistance • Type R Pt13Rh-Pt to DIN IEC 584
≤ 100 Ω (loop resistance)
• Type S Pt10Rh-Pt to DIN IEC 584
• Three-wire system No balancing required
• Type T Cu-CuNi to DIN IEC 584
• Four-wire system No balancing required
• Type U Cu-CuNi to DIN 43710
Sensor current ≤ 0.45 mA
Units °C or °F
Response time T63 ≤ 250 ms for 1 sensor with open-
circuit monitoring Connection
Open-circuit monitoring Always active (cannot be disab- • Standard connection 1 thermocouple element (TC)
led) • Generation of average value 2 identical thermocouple ele-
Short-circuit monitoring Can be switched off (value is ments (TC)
adjustable) • Generation of difference 2 identical thermocouple ele-
Measuring range Parameterizable (see table "Digi- ments (TC) TC1 – TC2 or
tal measuring errors") TC2 – TC1
Min. measured span 10 °C (18 °F) Response time T63 ≤ 250 ms for 1 sensor with open-
circuit monitoring
Characteristic curve Temperature-linear or special
characteristic Open-circuit monitoring Can be switched off
Thermocouple elements
• Without explosion protection }
D)
7NG3032-0JN00
3
• With explosion protection to } 7NG3032-1JN00
Input Measuring Min. measured Digital ATEX; type of protection: "Intrin- D)
range span accuracy sic safety" EEx ia/ib, non-arcing
°C °C (°F) °C (°F) (nA), limited energy (nL)
(°F) Further designs Order code
Type B 0 ... 1820 100 (180) 2 (3.60)1) Please add "-Z" to Order No. and
(32 ... 3308) specify Order code(s)
Type C (W5) 0 ... 2300 100 (180) 2 (3.60) Customer-specific setting of oper- Y01
(32 ... 4172) ating data (specify operating data
in plain text)
Type D (W3) 0 ... 2300 100 (180) 1 (1.80)2)
(32 ... 4172) with test protocol (5 measuring C11
points)
Type E -200 ... +1000 50 (90) 1 (1.80)
(-328 ... +1832) Accessories Order No.
Type J -210 ... +1200 50 (90) 1 (1.80) Modem for SITRANS TH100,
(-346 ... +2192) TH200 and TR200 incl. SIPROM
T parameterization software
Type K -230 ... +1370 50 (90) 1 (1.80)
(-382 ... +2498) • With USB connection } 7NG3092-8KU
C)
Type L -200 ... +900 50 (90) 1 (1.80)
(-328 ... +1652) • With RS 232 connection } 7NG3092-8KM
C)
Type N -200 ... +1300 50 (90) 1 (1.80)
(-328 ... +2372) CD for measuring instruments } A5E00364512
for temperature G)
Type R -50 ... +1760 100 (180) 2 (3.60)
(-58 ... +3200) with documentation in German,
English, French, Spanish, Italian,
Type S -50 ... +1760 100 (180) 2 (3.60) Portuguese and SIPROM T
(-58 ... +3200) parameterization software
Type T -200 ... +400 40 (72) 1 (1.80) } Available ex stock.
(-328 ... +752)
C) Subject to export regulations AL: N, ECCN: EAR99.
Type U -200 ... +600 50 (90) 2 (3.60) D) Subject to export regulations AL: N, ECCN: EAR99H.
(-328 ... +1112) G) Subject to export regulations AL: N, ECCN: 5D992B1.
1) Power supply units see "SITRANS I supply units and isolation amplifiers".
The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is
3 °C (5.4 °F).
2) The digital accuracy in the range 1750 to 2300 °C (3182 to
4172 °F) is 2 °C (3.6 °F).
mV sensor
Input Measuring Min. measured Digital
range span accuracy
mV mV µV
mV sensor -10 ... +70 2 40
mV sensor -100 ... +1100 20 400
3
4..20mA
SIEMENS
8
4
SITRANS
TR200
7
3
1 2 3 4
6
2
TEST
TEST 4..20mA
5
1
SIEMENS
SITRANS
TR200
Made in Croatia
3W RTD CJC
with external
2W RTD CJC
with external
U sensor
int./fixed CJC
5 6 7 8
TC sensor TC sensor TC sens. with
+
+ + +
8 7 6 5 8 7 6 5 8 7 6 5
8 7 6 5 8 7 6 5 8 7 6 5
$VVVLJQPHQWV
8 7 6 5 TEST +UB -
Connection Plan
s
DQG 7HVWWHUPLQDOV7HVWIRUPHDVXUHPHQWRIWKHRXWSXW
FXUUHQWZLWKDPXOWLPHWHU
DQG 3RZHUVXSSO\8DX[2XWSXWFXUUHQW,RXW
DQG 6HQVRUDVVLJQPHQWVHHVFKHPDWLFV
3
5 7&
57'
7&
57' 5 57'
7&
57' 5
57'
)RXUZLUHV\VWHP )RXUZLUHV\VWHP &ROGMXQFWLRQFRPSHQVDWLRQZLWK
H[WHUQDO3WLQWKUHHZLUHV\VWHP
5
57'
7& 7&
57' 5
8DX[
$
5
8
,
■ Application
SITRANS TR300 transmitters can be used in all industrial sec-
tors. Their compact design enables simple mounting on stan-
dard DIN rails on-site in protective boxes or in control cabinets.
3 The following sensors/signal sources can be connected over
their universal input module:
• Resistance thermometers (two, three or four-wire system)
• Thermocouple elements
• Resistance-based sensors and DC voltage sources
The output signal is a direct current from 4 to 20 mA in accor-
dance with the sensor characteristic, superimposed by the digi-
tal HART signal.
Transmitters of the "Intrinsically-safe" or Ex nAL (zone 2) type of
protection can be installed within potentially explosive atmos-
pheres.
"HART" to beat - the universal SITRANS TR300 transmitter
• Two-wire devices for 4 to 20 mA, HART ■ Function
• Device for rail mounting The SITRANS TR300 is configured over HART. This can be done
• Universal input for virtually any type of temperature sensor using a handheld communicator or even more conveniently with
a HART modem and the SIMATIC PDM parameterization soft-
• Configurable over HART ware. The configuration data are then permanently stored in the
non-volatile memory (EEPROM).
■ Benefits Once the sensors and power supply have been correctly con-
• Compact design nected, the transmitter outputs a temperature-linear output sig-
• Electrically isolated nal and the diagnostics LED displays a green light. In the case
of a sensor short-circuit, the LED flashes red, an internal device
• Test sockets for multimeters fault is indicated by a steady red light.
• Diagnostics LED (green/red)
The test socket can be used to connect an ammeter at any time
• Sensor monitoring for monitoring purposes and plausibility checks. The output cur-
open circuits and short-circuits rent can be read without any interruption, or even without ope-
• Self-monitoring ning the current loop.
• Configuration status stored in EEPROM
• Expanded diagnostic functions, such as slave pointer, opera-
ting hours counter etc.
6,75$167575
7
1
7HVW
6HQVRU
7&57' 2 3
$ '
µ& µ& P$ 8DX[,RXW
' $
4
5 6
6HQVRUVXFKDVUHVLVWDQFHWKHUPRPHWHU
6HQVRUZLH:LGHUVWDQGVWKHUPRPHWHU *DOYDQLVFKH7UHQQXQJ
(OHFWULFDOLVRODWLRQ 8DX[8 DX[ +LOIVHQHUJLH
$X[LOLDU\SRZHUVXSSO\
7KHUPRHOHPHQW:LGHUVWDQGVJHEHU
WKHUPRFRXSOHUHVLVWDQFHEDVHG 0LNURFRQWUROOHU3ULP¦UVHLWH
0LFURFRQWUROOHUSULPDU\FLUFXLW ,RXW ,RXW$XVJDQJVVWURP
2XWSXWFXUUHQW
0LOOLYROWJHEHU
VHQVRUP9VHQVRU 'LJLWDO$QDORJ:DQGOHU
'LJLWDODQDORJFRQYHUWHU 7HVW 7HVW3U¾INOHPPHQ]XPNXU]]HLWLJHQ
7HVWWHUPLQDOVIRUWHPSRUDU\
$QDORJ'LJLWDO:DQGOHU
$QDORJGLJLWDOFRQYHUWHU /('
/(' $QVFKOXVVHLQHV6WURPPHVVJHU¦WV
FRQQHFWLRQRIDQDPSHUHPHWHU
0LNURFRQWUROOHU6HNXQG¦UVHLWH
0LFURFRQWUROOHUVHFRQGDU\FLUFXLW
3
• to IEC 60751 Pt25 to Pt1000 measuring errors")
• to JIS C 1604; a=0.00392 K-1 Pt25 to Pt1000 Characteristic Resistance-linear or special cha-
• to IEC 60751 Ni25 to Ni1000 racteristic
• Two-wire system Parameterizable line resistance • Type T Cu-CuNi to DIN IEC 584
≤ 100 Ω (loop resistance) • Type U Cu-CuNi to DIN 43710
• Three-wire system No balancing required Units °C or °F
• Four-wire system No balancing required Connection
Sensor current ≤ 0.45 mA • Standard connection 1 thermocouple (TC)
Response time T63 ≤ 250 ms for 1 sensor with open- • Generation of average value 2 thermocouples (TC)
circuit monitoring
• Generation of difference 2 thermocouples (TC) TC1 – TC2
Open-circuit monitoring can be switched off or TC2 – TC1
Short-circuit monitoring can be switched off (value is Response time ≤ 250 ms for 1 sensor with open-
adjustable) circuit monitoring
Range Parameterizable (see table "Digi- Open-circuit monitoring Can be switched off
tal measuring errors")
Cold junction compensation
Min. measured span 10 °C (18 °F)
• Internal With integrated Pt100 resistance
Characteristic Temperature-linear or special thermometer
characteristic
• External With external Pt100 IEC 60571
Resistance-based sensors (2-wire or 3-wire connection)
Measured variable Actual resistance • External fixed Cold junction temperature can be
Sensor type Resistance-based, potentiome- set as fixed value
ters Range Parameterizable (see table "Digi-
Units Ω tal measuring errors")
Connection Min. measured span Min. 50 ... 199 °C (90 ... 180 °F)
(see table "Digital measuring
• Normal connection 1 resistance-based sensor (R) in errors")
2-wire, 3-wire or 4-wire system
Characteristic Temperature-linear or special
• Generation of average value 2 resistance-based sensors in characteristic
2-wire system for generation of
average value mV Sensor
3
teristic ignitable and has limited energy"
type of protection
Output
• Type of protection, "equipment is II 3G EEx nA T6/T4
Output signal 4 ... 20 mA, 2-wire non-arcing"
Communication acc. to HART
Rev. 5.9 • Type of protection, "associated II (1)GD [EEx ia] IIC T6/T4
equipment"
Power supply 11 ... 35 V DC (to 30 V with EEx)
Explosion protection to FM for USA
Max. load (Uaux – 11 V)/0.023 A and Canada (cFMUS)
Overrange 3.6 ... 23 mA, continuously adjus- • FM approval PID 3024169
table (default range:
3.84 ... 20.50 mA) • Degree of protection IS Cl I, II, III, Div 1, GP ABCDEFG
T4/T5/T6
Error signal (e.g. in the event of sen- 3.6 ... 23 mA, continuously adjus- IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6
sor breakage) table (default value: 22.8 mA) NI Cl I, II, III, Div 2, GP ABCDFG
T4/T5/T6
Sample cycle 0.25 s nominal Cl I, ZN2, GP IIC T4/T5/T6
Damping Software filter 1st order 0 ... 30 s Software requirements for
(parameterizable) SIPROM T
Protection Against reversed polarity PC operating system: Windows ME, 2000 and XP; also
Electrically isolated Input against output (1 kVeff) Windows 95, 98 and 98 SE, but
only in connection with RS 232
Measuring accuracy modem.
Digital measuring errors See Table "Digital measuring
errors" Factory setting:
Reference conditions • Pt100 (IEC 751) with three-wire circuit
• Power supply 24 V ± 1%
• Measuring range: 0 ... 100 °C (32 ... 212 °F)
• Fault current: 22.8 mA
• Load 500 Ω
• Sensor offset: 0 °C (0 °F)
• Storage temperature 23 °C
• Damping 0.0 s
• Warming-up time > 5 min
Error in the analog ouput (digi- < 0.1 % of span
tal/analog converter) Digital measuring errors
Error due to internal cold junction < 0.5 °C (0.9 °F) Resistance thermometer
Temperature effect < 0.1% der max. span/10°C
input Range Min. measu- Digital accu-
(18 °F)
red span racy
Power supply effect < 0.005% of span/V
°C (°F) °C (°F) °C (°F)
Effect of load impedance < 0.012% of span/100 Ω
to IEC 60751
Long-term drift
Pt25 -200 ... +850 10 (18) 0.2 (0.36)
• in the first month < 0.02% of max. span (-328 ... +1562)
• after one year < 0.03% of max. span Pt50 -200 ... +850 10 (18) 0.15 (0.27)
(-328 ... +1562)
• after 5 years < 0.04% of max. span
Pt100 ... Pt200 -200 ... +850 10 (18) 0.1 (0.18)
Rated conditions (-328 ... +1562)
Ambient temperature Pt500 -200 ... +850 10 (18) 0.15 (0.27)
Storage temperature -40 ... +85 °C (-40 ... 185 °F) (-328 ... +1562)
Functional temperature -40 ... +85 °C (-40 ... 185 °F) Pt1000 -200 ... +350 10 (18) 0.15 (0.27)
(-328 ... +662)
Relative humidity < 98%, with condensation
to JIS C1604-81
Electromagnetic compatibility acc. to DIN EN 61326 and NE21
Pt25 -200 ... +649 10 (18) 0.2 (0.36)
Construction (-328 ... +1200)
Material Molded plastic Pt50 -200 ... +649 10 (18) 0.15 (0.27)
Approx. weight 50 g (0.11 lb) (-328 ... +1200)
Dimensions See "Dimension drawings" Pt100 ... Pt200 -200 ... +649 10 (18) 0.1 (0.18)
(-328 ... +1200)
Cross-section of cables Max. 2.5 mm² (AWG 13)
Pt500 -200 ... +649 10 (18) 0.15 (0.27)
Degree of protection to EN 60529 (-328 ... +1200)
• Enclosure IP40 Pt1000 -200 ... +350 10 (18) 0.15 (0.27)
(-328 ... +662)
• Terminals IP00
Ni 25 to Ni1000 -60 ... +250 10 (18) 0.1 (0.18)
(-76 ... +482)
Thermocouple elements
• Without explosion protection }
D)
7NG3033-0JN00
3
• With explosion protection to } 7NG3033-1JN00
input Range Min. measured Digital accu- ATEX; type of protection: "Intrin- D)
span racy sic safety" EEx ia/ib, non-arcing
°C °C (°F) °C (°F) (nA), limited energy (nL)
(°F) Further designs Order code
Type B 0 ... 1820 100 (180) 2 (5.4) Please add "-Z" to Order No. and
(32 ... 3308) specify Order code(s)
Type C (W5) 0 ... 2300 100 (180) 2 (3.6) Customer-specific setting of oper- Y01
(32 ... 4172) ating data (specify operating data
in plain text)
Type D (W3) 0 ... 2300 100 (180) 2 (3.6)
(32 ... 4172) with test protocol (5 measuring C11
points)
Type E -200 ... +1000 50 (90) 1 (1.8)
(-328 ... +1832) Accessories Order No.
Type J -210 ... +1200 50 (90) 1 (1.8) CD for measuring instruments } A5E00364512
(-346 ... +2192) for temperature G)
mV Sensor
input Range Min. measured Digital accu-
span racy
mV mV µV
mV Sensor -10 ... +70 2 40
mV Sensor -100 ... +1100 20 400
3
4..20mA
SIEMENS
8
4
SITRANS
TR300
7
3
1 2 3 4
6
2
TEST
TEST 4..20mA
5
1
SIEMENS
SITRANS
TR300
Made in Croatia
3W RTD CJC
with external
2W RTD CJC
with external
U sensor
int./fixed CJC
5 6 7 8
TC sensor TC sensor TC sens. with
+
+ + +
8 7 6 5 8 7 6 5 8 7 6 5
8 7 6 5 8 7 6 5 8 7 6 5
3
5 7&
57'
7&
57' 5 57'
7&
57' 5
57'
)RXUZLUHV\VWHP )RXUZLUHV\VWHP &ROGMXQFWLRQFRPSHQVDWLRQZLWK
H[WHUQDO3WLQWKUHHZLUHV\VWHP
5
57'
7& 7&
57' 5
8DX[
$
5
8
,
TC
RTD 9
8
4 10
The user-friendly transmitters for the control room HART modem/
D communicator
The SITRANS TW universal transmitter is a further development A 5
µC Output
of the service-proven SITRANS T for the 4-wire system in a 11
U or I
mounting rail housing. With numerous new functions it sets new D A
1 2 6 12
standards for temperature transmitters. A Current test
0/4 ... 20 mA
Power
With its diagnostics and simulation functions the SITRANS TW EEPROM supply 13
provides the necessary insight during commissioning and oper- UH
3 unit
ation. And using its HART interface the SITRANS TW can be 7
conveniently adapted with SIMATIC PDM to every measurement
task.
All SITRANS TW control room devices are available in a non-in- The signal output by a resistance-based sensor (two-wire, three-
trinsically safe version as well as in an intrinsically safe version wire, four-wire system), voltage source, current source or ther-
for use with the most stringent requirements. mocouple is converted by the analog-to-digital converter
(1, function diagram) into a digital signal. This is evaluated in the
■ Application microcontroller (2), corrected according to the sensor character-
istic, and converted by the digital-to-analog converter (6) into an
The SITRANS TW transmitter is a four-wire rail-mounted device output current (0/4 to 20 mA) or output voltage (0/2 to 10 V). The
with a universal input circuit for connection to the following sen- sensor characteristics as well as the electronics data and the
sors and signal sources: data for the transmitter parameters are stored in the non-volatile
• Resistance thermometers memory (3).
• Thermocouple elements AC or DC voltages can be used as the power supply (13). Any
• Resistance-based sensors/potentiometers terminal connections are possible for the power supply as a re-
• mV sensors sult of the bridge rectifier in the power supply unit. The PE con-
ductor is required for safety reasons.
• As special version:
- V sources A HART modem or a HART communicator permit parameteriza-
- Current sources tion of the transmitter using a protocol according to the HART
specification. The transmitter can be directly parameterized at
The 4-wire rail-mounted SITRANS TW transmitter wire is de- the point of measurement via the HART output terminals (10).
signed for control room installation. It must not be mounted in po-
tentially explosive atmospheres. The operation indicator (4) identifies a fault-free or faulty operat-
ing state of the transmitter. The limit monitor (9) enables the sig-
All SITRANS TW control room devices are available in a non-in- naling of sensor faults and/or limit violations. In the case of a cur-
trinsically safe version as well as in an intrinsically safe version rent output, the current can be checked on a meter connected
for use with the most stringent requirements. to test socket (12).
3
Resistance thermometer
SIMATIC PDM
Measured variable Temperature
ET 200M Measured range Parameterizable
Control system
Measured span Min. 25 °C (45 °F) x 1/scaling fac-
UH or tor
A Sensor type
4...20 mA Load
SITRANS TW • DIN IEC 751 Pt100 (DIN IEC 751)
transmitter
• Acc. to JIS C 1604-81 Pt100 (JIS C1604-81)
• Acc. to DIN 43760 Ni100 (DIN 43760)
PC/laptop with
HART HART SIMATIC PDM
communi- modem • Special type (RRTD ≤ 500 Ω) Multiples or parts of the defined
cator or characteristic values can be
RS-232-C parameterized (e.g. Pt500, Ni120)
Voltage measurement Temperature-linear, resistance-lin-
Possible system configurations ear or customer-specific
The SITRANS TW transmitter as a four-wire rail-mounted device Type of connection • Normal connection
can be used in a number of system configurations: as a stand- • Sum or parallel connection
alone version or as part of a complex system environment, e.g. • Mean-value or differential con-
with SIMATIC S7. All device functions are available via HART nection
communication.
Connection 2, 3 or 4-wire circuit
Communication options through the HART interface: Measuring range limits Depending on type of connected
• HART communicator thermometer (defined range of
resistance thermometer)
• HART modem connected to PC/laptop on which the appropri-
ate software is available, e.g. SIMATIC PDM Sensor breakage monitoring Monitoring of all connections for
open-circuit (function can be
• HART-compatible control system (e.g. SIMATIC S7-400 with switched off)
ET 200M)
Sensor short-circuit monitoring Parameterizable response thresh-
old (function can be switched off)
Resistance-based sensors,
potentiometers
Measured variable Ohmic impedance
Measured range Parameterizable
Measured span Min. 10 Ω
Voltage measurement Resistance-linear or customer-
specific
Type of connection • Normal connection
• Differential connection
• Mean-value connection
Connection 2, 3 or 4-wire circuit
Input range 0 ... 6000 Ω;
with mean-value and difference
circuits: 0 ... 3000 Ω;
Sensor breakage monitoring Monitoring of all connections for
open-circuit (function can be
switched off)
Sensor short-circuit monitoring Parameterizable response thresh-
old (function can be switched off)
3
DIN IEC 751 Type C 0 ... +2300 2 (3.6)
• Pt10 -200 ... +850 20 3.0 (5.4) (+32 ... +4172)
(-328 ... +1562) Type D 0 ... +2300 1 (1.8)
• Pt50 -200 ... +850 50 0.6 (1.1) (+32 ... +4172)
(-328 ... +1562) Type E -200 ... +1000 1 (1.8)
• Pt100 -200 ... +850 100 0.3 (0.5) (-328 ... +1832)
(-328 ... +1562) Type J -210 ... +1200 1 (1.8)
• Pt200 -200 ... +850 100 0.6 (1.1) (-346 ... +2192)
(-328 ... +1562) Type K -200 ... +1372 1 (1.8)
• Pt500 -200 ... +850 100 1.0 (1.8) (-328 ... +2502)
(-328 ... +1562)
Type L -200 ... +900 2 (3.6)
• Pt1000 -200 ... +850 100 1.0 (1.8) (-328 ... +1652)
(-328 ... +1562)
Type N -200 ... +1300 1 (1.8)
JIS C 1604-81 (-328 ... +2372)
• Pt10 -200 ... +649 20 3.0 (5.4) Type R -50 ... +1760 2 (3.6)
(-328 ... +1200) (-58 ... +3200)
• Pt50 -200 ... +649 50 0.6 (1.1) Type S -50 ... +1760 2 (3.6)
(-328 ... +1200) (-58 ... +3200)
• Pt100 -200 ... +649 100 0.3 (0.5) Type T -200 ... +400 1 (1.8)
(-328 ... +1200) (-328 ... +752)
DIN 43760 Type U -200 ... +600 2 (3.6)
(-328 ... +1112)
• Ni50 -60 ... +250 50 0.3 (0.5)
(-76 ... +482) 1)
Accuracy data refer to the largest error in the complete measuring range
• Ni100 -60 ... +250 100 0.3 (0.5)
(-76 ... +482) Voltage/current sources
• Ni120 -60 ... +250 100 0.3 (0.5) Input Measuring range Digital error
(-76 ... +482)
mV sources (linear) mV µV
• Ni1000 -60 ... +250 100 0.3 (0.5)
(-76 ... +482) -1 ... +16 35
-3 ... +32 20
Resistance-based sensors -7 ... +65 20
-15 ... +131 50
Input Measured Max. permissi- Digital error
range ble line resis- -31 ... +262 100
tance -63 ... +525 200
Ω Ω Ω -120 ... +1000 300
3
The default settings can be obtained from the list of parame-
• with explosion protection ATEX
terizable operating data (see "Special operating data"). The
7NG3242-1AA00
• 230 V AC/DC power supply presets can be modified by the customer to match the require-
(stock item)
• current output ments precisely.
• without sensor fault/limit monitor
- Sensor PT100, three-wire circuit X
• Operating data set on delivery according to customer require-
ments:
- Measuring range 0 ... 150 °C X
Supplement the Order No. by "-Z" and add the Order code
- Temperature-linear characteristic X
"Y01". The operating data to be set can be obtained from the
- Filter time 1 s X list of parameterize operating data. The Order codes A 7 7 to
- Output 4 ... 20 mA, line filter 50 Hz X K 7 7 for operating data to be set need only be specified in the
- Output driven to full-scale in event X order if they deviate from the default setting.
of like breakage The default setting is used if no Order code is specified for op-
Example 2: erating data.
SITRANS TW, The selected parameters are printed on the transmitter's rating
transmitter in four-wire system
plate.
Y01 + S76 + A05 + Y30 + H10
• Voltage output
• Sensor fault/limit monitor
- Rating plate in English S76
- Sensor NiCr/Ni, type K A05
- Cold junction internal X
- Measuring range 0 ... 950 °C Y30
- Temperature-linear characteristic X
- Filter time 1 s X
- Output 0 ... 10 V, line filter 50 Hz H10
- Output driven to full-scale in event X
of like breakage
- Limit monitoring switched off X
Example 3:
Y01 + A40 + Y32 + G07 + H11 + J03
SITRANS TW,
transmitter in four-wire system
Y32: MA=0; ME= 5; D=V
Selection and Ordering data Order No. Selection and Ordering data Order No.
SITRANS TW universal transmitter } 7 NG 3 2 4 2 - 77777 Accessories
for rail mounting, in four-wire system Instruction Manual for SITRANS TW
(order instruction manual separately)
• German/English } A5E00054075
Explosion protection • French/Italian/Spanish } A5E00064515
• without } 0
• for inputs [EEx ia] or [EEx ib] } 1 Cold junction terminal } 7NG3092-8AV
3 Power supply
• 115/230 V AC/DC } A
U/I plug
(-1.2 ... +10 V DC pr -12 ... +100 mA)
} 7NG3092-8AW
mV, V and µA, mA sensors 9) A 4 0 Meas. range with Order No. 7NG 3242 - 7 7 7 7 7 -Z Y01 E50
0 -120 ... +1000 mV
1 -1,2 ... +10 V 10)
1) n = number of thermocouple elements to be connected in series 2 -12 ... +100 V 10)
2)
See „Circuit diagrams“ for meaning of type circuit 3 -120 ... +140 V 10)
3)
Line resistance of channels 1 and 2, for max. permissible line resistance see 4 -12 ... +100 µA 10)
„Technical specifications“ (only with C32, not with C33 and C34)
4) 5 -120 ... +1000 µA 10)
n = number of resistance thermometers to be connected in series
5) 6 -1,2 ... +10 mA 10)
1/n = number of resistance thermometers to be connected in parallel
6) 7 -12 ... +100 mA 10)
Combination of series and parallel connection of resistance thermometers
7) 8 -120 ... +1000 mA 10)
Operating data: see „Special operating data“
8) Special range 7) Y 3 2
This range does not apply to mean-value and difference circuits.
9)
The max. permissible currents and voltages according to conformity cer-
tificate must be observed in devices with explosion protection.
10) Without detection of line breakage
B: Pt30%Rh/ 0 ... 1820 °C A00 Temperature- F 0 0 0s G0 0 4 ... 20 mA/ with line break- Limit monitor- K 0 0
C:W5%Re 0 ... 2300 °C A01 linear 0.1 s G0 1 2 ... 10 V age/fault: ing ineffective
D:W3%Re 0 ... 2300 °C A02 Voltage- F10 0.2 s G0 2 with line filter: (but sensor
E:NiCr/CuNi -200 ... +1000 °C A03 linear 0.5 s G0 3 50 Hz H00 to full scale J 0 0 fault signalling
J:Fe/CuNi (IEC) -210 ... +1200 °C A04 1s G0 4 60 Hz H01 to start of scale J 0 1 with closed-
K:NiCr/Ni -200 ... +1372 °C A05 2s G0 5 10 Hz 4) H02 hold last value J 0 2 circuit opera-
tion)
L: Fe/CuNi (DIN) -200 ... +900 °C A06 5s G0 6 0 ... 20 mA/
N:NiCrSi/NiSi -200 ... +1300 °C A07 10 s G0 7 0 ... 10 V no monitoring J03
R:Pt13%Rh/Pt -50 ... +1760 °C A08 20 s G0 8 with line filter: Effective 5) Y70
S:Pt10%Rh/Pt -50 ... +1760 °C A09 50 s G0 9 50 Hz H 1 0 Safety value 5) Y60
T:Cu/CuNi (IEC) -200 ... +400 °C A10 100 s G1 0 60 Hz H11
U:Cu/CuNi (DIN) -200 ... +600 °C A11 Special Y50 10 Hz H12
time 5)
Pt100 (DIN IEC) -200 ... +850 °C A 2 0 Temperature- F 0 0 with line break-
Pt100 (JIS) -200 ... +649 °C A 2 1 linear age/fault:
Ni100 (DIN) -60 ... +250 °C A 2 2 Resistance- F 2 0 to full scale J00
linear to start of scale J01
hold last value J02
no monitoring J03
no monitoring J13
no monitoring J03
Y10 TV=.
N = 5/3 = 1.667;
2. Example: Ni120: N = 1.2
Temperature TV of the fixed cold junction
3
D= Dimension; range of values: C, K, F, R
Y11 RL=. Line resistance RL in Ω for compensation of
cold junction line of external Pt100
DIN IEC 751
Range of values: 0.00 to 100.00
Y20 RL1=. Line resistances RL of channel 1 (RL1) and
RL2=. channel 2 (RL2) in Ω if the resistance ther-
mometer or the resistance-based sensor is
connected in a two-wire system
Range of values depending on type of sen-
sor: 0.00 to 100.00
Y30 MA=. Start-of-scale value MA and full-scale value
ME=. ME for thermocouples and resistance ther-
mometers
(Range of values depending on type of sen-
sor)
D= Dimension, range of values: C, K, F, R)
Y31 MA=. Start-of-scale value MA and full-scale value
ME=. ME for resistance-based sensors or potenti-
ometers in Ω
Range of values: 0.00 to 6,000.00
Y32 MA=. Start-of-scale value MA and full-scale value
ME=. ME for mV, V, µA and mA sources
Range of values depending on type of sen-
sor: -120.00 to 1,000.00
D= Dimension (mV entered as MV, V as V,
µA as UA, mA as MA)
Y50 T63=. Response time T63 of software filter in s
Range of values: 0.0 to 100.0
Safety value S of signal output in mA or in V
corresponding to the set type of output.
Range of values
- with current output: -0.50 to 23.00
- with voltage output: -0.25 to 10.75
Y60 S= . Safety value S with line breakage of sensor
Y61 S=. Safety value S with line breakage or short-
circuit of sensor
Y70 UG=. Lower limit value (dimension as defined by
measuring range)
OG=. Upper limit value (dimension as defined by
measuring range)
H=. Hysteresis (dimension as defined by mea-
suring range)
K= Switch on/off combination of limit function
and sensor fault detection; J=on; N=off
(standard: J)
A= Type of relay output: A=open-circuit opera-
tion; R=closed-circuit operation (standard: R)
T=. Switching delay T of relay output in s
Range of values: 0.0 to 10.0 (standard: 0.0)
■ Schematics
Sensor input connections
1 2 3 4
4 3 2 1 4 3 2 1
3
4 3 2 1 4 3 2 1
5 6 7 8
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
- + - + Pt100 - + TC1
Pt100
TC TC
4 1 - + TC2
- +
TC 7NG3092-8AV
9 10 11
4 3 2 1 4 3 2 1 4 3 2 1
- + - + - +
-120 ... 1000 mV
12 13
4 3 2 1 4 3 2 1
U+ U- I+ I-
+ - - +
7NG3092-8AW
-1,2 ... 10 V -12 ... 100 mA
14 13 12 11 10 9 8 7 6 5 4 3 2 1
~ ~ + -
+U- Relay output HART
3
H
1 to 4 Signal input (see "Sensor input connections" for possible types of connection)
5, 6 Analog output (U or I output parameterizable using plug-in jumpers)
7, 8 Connection with HART communication for local parameterization
9 to 11 Output for sensor fault/limit monitor as relay contact
(see below for possible parameterization)
12 PE connection
13, 14 Power supply input (protected against reverse polarity)
■ Dimensional drawings
■ Overview ■ Design
The SITRANS TF2 has a stainless steel housing (diam. 80 mm)
with protective glass. The stainless steel protective tube with
screw socket contains the temperature sensor Pt100. By using
stainless steel for the protective tube it displays high chemical
resistance, which means that the temperature sensor is well pro-
tected against external effects
3 The protective tube is supplied as standard in lengths of 170 mm
or 260 mm; a customer-specific version is also possible. Simi-
larly, the protective tube can be supplied in the material of the
customer’s choice.
At the rear of the housing is the electrical connection for the volt-
age supply using a current loop of 4 to 20 mA. The connection
is made with plug connectors to EN 175301-803A.
At the front of the housing is the 5-digit display behind a glass
cover. Underneath the display are the 3 keys for parameterizing
the SITRANS TF2. Above the display are a green and a red LED
for indicating the operating status.
The SITRANS TF2 is available in two versions (see "Dimensional
drawings“):
• In the radial version (type A) the display is fitted in parallel with
the protective tube. The display can be rotated by up to ±120°
relative to the protective tube.
• In the axial version (type B) the display is at right angles to the
The temperature transmitter SITRANS TF2 integrates three ele- protective tube. The display can be rotated by 360° relative to
ments in one device: the protective tube.
• a Pt100 resistance thermometer in a stainless steel protective
tube, ■ Function
• a stainless steel housing with a high degree of protection, and
Mode of operation
• a built-in transmitter with LCD and three keys for parameter-
ization.
Green LED Red LED
It is used to indicate and monitor the temperature measured at IK LCD
the point of installation.
The SITRANS TF2 is available in an axial and a radial version. 200.00
RTD µC °C
A/D
■ Benefits
• Robust stainless steel housing with two connection versions
• High measuring accuracy 3 keys
EEP RO M
• Precise display with a resolution of 1/100 °C in the highest mea- UK
EMV
suring range +
D/A UA U I 4 ... 20 mA UH, IA
• Measuring ranges from -50 to +200 °C (-58 ... +392 °F) pa- -
rameterizable
3 keys Configuring of parameters
• Customer-specific lengths and materials possible for the pro- A/D Analog-to-digital converter
tective tube D/A Digital-to-analog converter
EEPROM Memory for all parameters
• Stainless steel protective tube with high resistance to chemi- EMC Output stage with protective components
IA Current output
cals IK Constant-current source
LCD Display of measured values with dimension
• Signaling of limit violation in the LCD as well as with a red LED Green LED Display of normal mode
Red LED Display of error messages or limit violation
■ Application RTD
UH
µC
Pt100 resistance thermometer
Power supply
Microcontroller for computing functions ond monitoring
The SITRANS TF2 is used for indicating and monitoring a tem-
perature variable at the point of installation. Applications are all The outside lying temperature sensor Pt100 is supplied with cur-
process engineering branches, e.g.: rent from the constant current course Ik. A temperature-related
• Chemical industry voltage drop is thus created over the sensor.
• Energy industry The voltage drop is converted on the analog/digital converter
(A/D) into a digital signal.
• Long-distance heating
• Water supply In the microcontroller (µC) the digital signal is linearized and
evaluated in accordance with the data saved in the EEPROM.
• Sewage works The processed data are shown in the display.
• Food industry
In addition the values are converted on the digital/analog con-
• Steelworks and the cement industry verter (D/A) and the voltage/current transformer (U/I) into a tem-
• Pharmaceutical industry perature-linear current signal IA (4 to 20 mA).
• Biotechnology
Min. measured span 50 K (90 °F) Measuring insert Length to fit the ordered protec-
tive tube, stainless steel
Output
Connection of display to the protec- radial (type A), can be swiveled
Output signal 4 ... 20 mA, 2-wire tive tube by max. ±120° (α)
Lower current limit min. 3.6 mA axial (type B), can be swiveled by
max. ± 360°
Upper current limit max. 23 mA
Length of the protective tube(U1) see Ordering data
Output protected against reversed polarity, overvoltage and
short-circuiting Electrical connection Using 2-pole plug connector
made of plastic with
max. load (UH – 12 V) / 0.023 A M16x1.5-cable entry to
Voltage measurement Temperature-linear EN 175301-803A or ½“-14 NPT
Measuring accuracy Power supply
Error in measurement at 23 °C ± 5 K < ± (0.45 K + 0.2% of full-scale Terminal voltage on temperature 12 ... 30 V DC
(73.4 ± 9 °F) value in K + 1 digit in K) transmitter (UH)
(< ± (0.81 °F + 0.2% of full-scale Operating limits
value in °F + 1 digit in °F)
Pressure max. 40 bar (580 psi)
Measuring cycle time ≤ 100 ms
Temperature effect < ± 0.15%/10 K (< ± 0.15%/18 °F)
Power supply effect < ±0,01% of full-scale value/V
Vibration influence < ±0.05%/g to 500 Hz in all direc-
tions (to IEC 68-2-64)
Selection and ordering data Order No. Order code Selection and ordering data
Temperature transmitter SITRANS TF2, 7 NG 3 1 4 0 - Further design Order code
field device
Manufacturer’s test certificate M to DIN C11
Temperature transmitter with LCD in stain- 7777 0 777 55340, Part 18 and ISO 8402 (calibration
less steel housing, degree of protection certificate 3 points), add "-Z" to Order No.
IP65, stainless steel protective tube, and Order code.
resistance thermometer with Pt100 sensor,
Order No.
3
measuring range -50 ... +200 °C
(-58 ... +392 °F), local parameterization,
output signal 4 ... 20 mA Manufacturer’s test certificate M to DIN 7MF1564-8CC11
55340, Part 18 and ISO 8402 (calibration
Display/cable entry certificate 1 point) supplied later,
• Radial version (type A), } 1 specify factory no. of transmitter.
parallel to protective tube/M16x1.5 Additional data Order code
• Axial version (type B), 2
at right angles to protective tube/M16x1.5 Add „-Z“ to Order No. and specify Order
code and plain text
• Radial version (type A), 3
parallel to protective tube/½"-NPT Measuring range to be set Y01
• Axial version (type B), 4 Y01: .......................
at right angles to protective tube/½"-NPT Measuring point label made of stainless Y15
Process connection steel, please specify inscription in plain text.
• Connection shank G½B } A
• Connection shank ½"-14 NPT B
■ Schematics
• Other version (on request) Z J1Y
add Order code and plain text:
connection shank: ...
Length of the protective tube (U1)
• 170 mm (6.70 inch) } A 1 (+)
• 260 mm (10.24 inch) } B 1 I0 +
• 4.5" (114 mm) K UB
• 7.5" (190 mm) P 2 (-) RL
• 10.5" (266 mm) T 2
• Other version (on request) Z K1Y
add Order code and plain text:
length: ...
Material of the protective tube UB Power supply
• Stainless steel (mat. No. 1.4571/316Ti) } 0 RL Load
• Other version (on request) 9 L1Y I0 Output current
add Order code and plain text:
mat. No.: ...
SITRANS TF2, connection diagram
} Available ex stock
■ Dimensional drawings
Ø 82 (3.23) Ø 82 (3.23)
45 (1.77)
M16x1.5
67 (2.64)
or
½"-NPT
M16x1.5
SW 27 or
½"-NPT
SW 27
G½B
or
½"-14 NPT G½B
or
½"-14 NPT
Ø 14 (0.55)
U1
U1
Type A Type B
■ Overview ■ Function
Configuration
The communication capability over the HART protocol V 5.9 of
the SITRANS TF with an integrated SITRANS TH300 permits pa-
rameterization using a PC or HART communicator (hand-held
communicator). The SIMATIC PDM makes it easy.
Parameterization is carried out using a PC for SITRANS TF - with
the integrated and programmable SITRANS TH200. Available
3
for this purpose are a special modem and the software tool
SIPROM T.
Mode of operation
Mode of operation of SITRANS TF as temperature transmitter
The sensor signal, whether resistance thermometer, thermocou-
ple or Ω and/or V signal, is amplified and linearized. Sensor and
output side are electrically isolated. An internal cold junction is
integrated for measurements with thermocouples.
The device outputs a temperature-linear direct current of 4 to
20 mA. As well as the analog transmission of measured values
from 4 to 20 mA, the HART model also supports digital commu-
nication for online diagnostics, measured value transmission
and configuration.
SITRANS TF automatically detects when a sensor should should
be interrupted or is indicating a short-circuit. The practical test
Our field devices for heavy industrial use terminals allow direct measurement of 4 to 20 mA signals over
• HART, Universal an ammeter without interrupting the output current loop.
• 4 to 20 mA, universal Mode of operation of SITRANS TF as field indicator
• Field indicator for 4 to 20 mA signals Any 4 to 20 mA signal can be applied to the generous terminal
The temperature transmitter SITRANS TF works where others block. As well as a range of predefined measurement units, the
feel uncomfortable. adjustable indicator also supports the input of customized units.
This means that any 4 to 20 mA signal can be represented as
■ Benefits any type of unit, e.g. pressure, flow rate, filling level or tempera-
ture.
• Universal use
- as transmitter for resistance thermometer, thermoelement, Power supply
SITRANS TF
Ω or mV signal
0000
- as field indicator for any 4 to 20 mA signals Sensor SITRANS TH300 8
00°C
TC RTD 1 3 4 9 5
• Local sensing of measured values over digital display 2
A D
µP Load
• Rugged two-chamber enclosure in die-cast aluminium or D A
stainless steel
• Type of protection IP68 7
• Test terminals for direct read-out of the output signal without 6
breaking the current loop 1 Analog-to-digital converter
2 Electrical isolation
• Can be mounted elsewhere if the measuring point 3 Microprocessor
- is not easily accessible 4 Digital-to-analog converter
- is subject to high temperatures 5 Power supply
- is subject to vibrations from the system 6 PC/Laptop
- or if you want to avoid long neck tubes and/or protective 7 HART modem
8 Digital display (option)
tubes 9 Test connector
• Can be mounted directly on American-design sensors
• Wide range of approvals for use in potentially explosive atmo-
spheres. "Intrinsically safe, non-sparking and flameproof" type Operating principle: SITRANS TF with an integrated transmitter and
of protection, for Europe and USA. digital display
■ Application
SITRANS TF can be used everywhere where temperatures need
to be measured under particularly adverse conditions, or where
a convenient local display is ideal. Which is why users from all
industries have opted for this field device. The rugged enclosure
protects the electronics. The stainless steel model is even resis-
tant to sea water and other aggressive elements The inner work-
ings offer high measuring accuracy, universal input and a wide
range of diagnostic options.
3
• to IEC 60751 Pt25 to Pt1000
• to JIS C 1604; a=0.00392 K-1 Pt25 to Pt1000 Measured variable Temperature
• to IEC 60751 Ni25 to Ni1000 Sensor type (thermocouples)
Units °C and °F • Type B Pt30Rh-Pt6Rh to DIN IEC 584
Connection • Type C W5%-Re to ASTM 988
• Normal connection 1 resistance thermometer (RTD) • Type D W3%-Re to ASTM 988
in 2-wire, 3-wire or 4-wire system • Type E NiCr-CuNi to DIN IEC 584
• Generation of average value Series or parallel connection of • Type J Fe-CuNi to DIN IEC 584
several resistance thermometers • Type K NiCr-Ni to DIN IEC 584
in a two-wire system for the gen-
eration of average temperatures • Type L Fe-CuNi to DIN 43710
or for adaptation to other device • Type N NiCrSi-NiSi to DIN IEC 584
types • Type R Pt13Rh-Pt to DIN IEC 584
• Generation of difference 2 resistance thermometers (RTD) • Type S Pt10Rh-Pt to DIN IEC 584
in 2-wire system (RTD 1 – RTD 2 • Type T Cu-CuNi to DIN IEC 584
or RTD 2 – RTD 1)
• Type U Cu-CuNi to DIN 43710
Interface
Units °C or °F
• Two-wire system Parameterizable line resistance
Connection
≤ 100 Ω (loop resistance)
• Standard connection 1 thermocouple (TC)
• Three-wire system No balancing required
• Generation of average value 2 thermocouples (TC)
• Four-wire system No balancing required
• Generation of difference 2 thermocouples (TC)
Sensor current ≤ 0.45 mA
(TC 1 – TC 2 or TC 2 – TC 1)
Response time ≤ 250 ms for 1 sensor with open-
Response time ≤ 250 ms for 1 sensor with open-
circuit monitoring
circuit monitoring
Open-circuit monitoring Can be switched off
Open-circuit monitoring Can be switched off
Short-circuit monitoring Can be switched off (value is
Cold junction compensation
adjustable)
• Internal With integrated Pt100 resistance
Measuring range Parameterizable (see table "Digi-
thermometer
tal measuring errors")
• External With external Pt100 IEC 60571 (2-
Min. measured span 10 °C (18 °F)
wire or 3-wire connection)
Characteristic Temperature-linear or special
• External fixed Cold junction temperature can be
characteristic
set as fixed value
Resistance-based sensors
Measuring range Parameterizable (see table "Digi-
Measured variable Actual resistance tal measuring errors")
Sensor type Resistance-based, potentiome- Min. measured span Min. 50 ... 100 °C (90 ... 180 °F)
ters (see table "Digital measuring
errors")
Units Ω
Characteristic Temperature-linear or special
Connection characteristic
• Normal connection 1 resistance-based sensor (R) in mV Sensor
2-wire, 3-wire or 4-wire system
Measured variable DC voltage
• Generation of average value 2 resistance-based sensors in
2-wire system for generation of Sensor type DC voltage source (DC voltage
average value source possible over an exter-
nally connected resistor)
• Generation of difference 2 resistance-based sensor in
2-wire system (R 1 – R 2 or Units mV
R 2 – R 1)
Response time ≤ 250 ms for 1 sensor with open-
Interface circuit monitoring
• Two-wire system Parameterizable line resistance Open-circuit monitoring Can be switched off
≤ 100 Ω (loop resistance)
Short-circuit monitoring Can be switched off (value is
• Three-wire system No balancing required adjustable)
• Four-wire system No balancing required Measuring range -10 ... +70 mV
-100 ... +1100 mV
Sensor current ≤ 0.45 mA
Min. measured span 2 mV or 20 mV
Response time ≤ 250 ms for 1 sensor with open-
circuit monitoring Overload capacity of the input -1.5 ... +3.5 V DC
Open-circuit monitoring Can be switched off Input resistance ≥ 1 MΩ
Short-circuit monitoring Can be switched off (value is Characteristic Voltage-linear or special charac-
adjustable) teristic
Units Any (max. 5 char.) - EC type test certificate ZELM 99 ATEX 0007
Resistance-based sensors
mV sensors
Input Measuring range Min. mea- Digital
sured span accuracy Input Measuring range Min. mea- Digital
sured span accuracy
Ω Ω Ω
mV mV µV
Resistance 0 ... 390 5 0,05
mV sensors -10 ... +70 2 40
Resistance 0 ... 2200 25 0,25
mV sensors -100 ... +1100 20 400
■ Dimensional drawings
13 (0.51) 144 (5.67) 55 80 (3.15)
15* (0.59) 138* (5.43) (2.17) b 100* (3.94)
(0.79)
52 (2.05) 28 6 2
20
50* (1.97) (1.10)
(1.97)
3
50
80 (3.15)
117 (4.61)
a
237 (9.33)
8 5 4
68 (2.68)
120 (4.72)
1
36,5 (1.44)
72 (2.83)
105 (4.13)
1 Sensor connection (screwed gland M20x1,5 or ½-14 NPT)
2 Blanking plug 6 Protective cover (without function)
3 Electrical connection (screwed gland M20x1,5 or ½-14 NPT) 7 Mounting bracket (option) with clamp for
4 Terminal side, output signal securing to a vertical or horizontal pipe
5 Terminal side, sensor 8 Cover with window for digital display
Selection and Ordering data Order No. Selection and Ordering data Order No.
Temperature transmitter in field housing D) 7 NG 3 1 3 7 - 77777 Accessories
Two-wire system 4 ... 20 mA, with electrical Modem for SITRANS TH200
isolation, with documentation on incl. parameterization software T
CD-ROM
• with USB interface } 7NG3092-8KU
Integrated transmitter C)
• SITRANS TH200, programmable
3 - without Ex protection
- with EEx ia
5
5
0
1
• with RS 232 interface } 7NG3092-8KM
C)
■ Schematics
■ Design ■ Function
A resistance thermometer comprises Measuring resistor
• the measuring resistor (metal; platinum, Pt or nickel, Ni) and Measuring resistors Measuring resistors are suit-
• the mounting and connection parts required in each case. able for temperatures from
In the standard version, the measuring resistors are embedded Made of platinum -200 ... +850 °C
(-328 ... +1562 °F)
in ceramic. In the case of special vibration resistance require-
3 ments, the Pt measuring resistors are double-wound and fused
into glass.
Made of nickel -60 ... +150 °C (-76 ... 302 °F),
briefly up to 180 °C (356 °F)
• Measuring resistors of class B are supplied. A range of resis- The measuring resistor changes with the temperature in accor-
tors of class A or 1/3 to 1/10 class B is available on request. dance with a certain reproducible series of calibration data (see
• Single and double resistance thermometers are available. the table "Calibration data for platinum measuring resistors (to
DIN EN 60751)“ under "Technical data“).
The changes in resistance are transmitted as changes in voltage
to indicators, recorders or controllers directly via copper wires or
via transmitters. The type of measuring circuit depends on the
instrument to be connected and the required measuring range.
The measuring resistors are balanced at 0 °C (32 °F) to
100 Ω ± 0.12 Ω . The calibration values of the resistors (i.e. the
dependence of the resistor on the temperature) and the permis-
sible deviations are specified in DIN EN 60751 (IEC 751) (see
the table "Error limits according to DIN EN 60751“ under "Tech-
nical Specifications“).
Measuring resistors of class B are supplied. A range of resistors
of class A or 1/3 to 1/10 class B is available on request.
Measuring principle of the resistance temperature measure-
ment
The thermometer is heated up by the thermometer current com-
pared to the material to be measured. The heating-up error thus
produced increases with the square of the thermometer current
and linearly with the resistance of the measuring resistor. Apart
from the magnitude of the thermometer current, the error de-
pends on the design of the thermometer and on the heat transfer
between the protective tube and the medium. A high measuring
power is required for output instruments operating according to
the deflection method. To keep the heating-up error within per-
missible limits, the thermometer current should not be greater
than 10 mA in this case.
When measuring the temperature of gases with very small flow
velocities, a considerably greater heating-up error occurs than
in measurements with very fast gases or liquids. The heating-up
error is negligibly small with high flow velocities.
Components and circuitry of a resistance thermometer
Protection fitting/protective tubes
To protect the measuring resistor for industrial measurements
and to enable easy replacement, it is fixed in a measuring insert Suitable protective fittings are used for installation in pipelines,
(4) which in turn is fitted in a protective tube (5). The measuring tanks etc. depending on the mechanical or chemical require-
insert is spring-mounted in the connection head (1) of the pro- ments.
tective tube using two screws. The internal conductor (10) in the The materials for the protective tubes or combinations of differ-
measuring insert connects the measuring resistor (11) to the ter- ent protective tube materials must be carefully selected in order
minals on the terminal block. to meet the requirements due to static pressure, flow and tem-
perature Furthermore, the indication response should be as fast
Depending on the measuring range and the accuracy required, as possible.
the thermometers are connected in two-wire, three-wire or four-
wire systems to the output devices. Installation examples with the suitable protective tube materials
can be found under "Technical data" in the table "Installation ex-
The measuring inserts are therefore available with two, three or amples and material of protective tubes".
four internal conductors. If the resistance of the internal conduc-
tor is negligibly small, measuring inserts with only two internal The type of installation of the protective tubes depends on the
conductors can be used for the three-wire and four-wire sys- application. The protective tubes are screwed into the pipelines
tems. in the case of operating pressures up to approx. 90 bar. Tapered
protective tubes which can be welded in are available for higher
Exact balancing of the internal conductor under operating con- pressures. Thermometers for measuring furnace temperatures
ditions is only possible with three conductors. If the resistance of are fixed using flanges.
the internal conductor is greater than 0.2 Ω, its magnitude is in-
dicated on the mounting flange of the measuring insert. Owing to the different operating conditions, no guarantee can be
given for protective fittings. The manufacturer is responsible for
damages and measuring errors caused by wrong installation in
compliance with the General Terms of Delivery if the instruments
have been installed by the manufacturer and if the specifications
for the operating conditions furnished by the customer were cor-
rect and sufficiently detailed.
■ Integration
Instrument combination for measuring and controlling tem-
perature
Sense
Resistance thermometer
3
Match
Electric transmitter
Catalog FI 01
controller MP 31
Flue gas 550 (1022) St 35.8, enamelled 1.0305 Brewing water 80 (176) Bronze Sn Bz 6 or X 6 2.1020
CrNiTi 18 10
Pulverized coal/air mix- 100 (212) St 35.8 (with baffle rod) 1.0305
ture line Mash
Water treatment 30 (86) X 6 CrNiTi 18 10 or 1.4541 • Hot wort 100 (212) Bronze or X 6 CrNiTi 18 1.4541
X 6 CrNiMoTi 17 122 1.4571 10
3 -160
-140
(-256)
(-220)
35.34
43.88
1)
|t| is the numerical value of the temperature in °C without consideration of
the sign
-120 (-184) 52.11
-100 (-148) 60.26 ■ Integration
-80 (-112) 68.33
-60 (-76) 76.33 Protective tubes in a pipeline
-40 (-40) 84.27
-30 (-22) 88.22
-20 (-4) 92.16
-10 (14) 96.09
0 (32) 100.00
10 (50) 103.90
20 (68) 107.79
30 (86) 111.67
40 (104) 115.54
50 (122) 119.40
60 (140) 123.24
80 (176) 130.90
100 (212) 138.51
120 (248) 146.07
140 (284) 153.58
160 (320) 161.05
180 (356) 168.48
200 (392) 175.86 Flue gas resistance thermometer
220 (428) 183.19
240 (464) 190.47
260 (500) 197.71
280 (536) 204.90
300 (572) 212.05
320 (608) 219.15
340 (644) 226.21
360 (680) 233.21
380 (716) 240.18
400 (752) 247.09
420 (788) 253.96
440 (824) 260.78
460 (860) 267.56
480 (896) 274.29
500 (932) 280.98
520 (968) 287.62
540 (1004) 294.21
560 (1040) 300.75
580 (1076) 307.25
600 (1112) 313.71
620 (1148) 320.12
640 (1184) 326.48
660 (1220) 332.79
700 (1292) 345.28
750 (1382) 360.64
800 (1472) 375.70
850 (1562) 390.48
In a pulverized coal line, with baffle rod Top: Wall thickness ≤ 35 mm; mounting using welded coupling; bottom:
Wall thickness > 35 mm
Welding-type protective tubes, mounted
At top for low-pressure, with screw socket G½; at bottom for high-pres-
sure, with screw socket G1
It must be possible to weld the pipe coupling and pipeline. Ma-
terial according to data provided by pipeline or vessel manufac-
turer.
3
To order the sensor with a built-in
temperature transmitter, add "-Z" to
the Order No. of the sensor, and
supplement by the following Order
code:
• SITRANS TH100
- without Ex T10
- EEx ia IIC and EEx n for zone 2 T11
- FM T13
• SITRANS TH200
- without Ex T20
- EEx ia IIC and EEx n for zone 2 T21
The following temperature transmitters are available for mount-
- FM (IS, I, NI) T23
ing in the connection head:
• SITRANS TH300
SITRANS TH100
- without Ex T30
Programmable two-wire temperature transmitter (4 to 20 mA),
- EEx ia IIC und EEx n for zone 2 T31
without electrical isolation, only for Pt100 resistance thermome-
ters. - FM (IS, I, NI) T33
■ General information
Customer: ....................................................................................
Address: ......................................................................................
Contact partner: .........................................................................
Purchasing dept.: ........................................................................ Tel.: ...........................................................................
Sales dept.: ................................................................................. Tel.: ........................................................................... 3
Process dept.: ............................................................................. Tel.: ...........................................................................
Inquiry:.........................................................................................
Quotation: ....................................................................................
Place and date: ...........................................................................
2. Location:...........................................................................
■ Sensor design
(e.g. pipe bend, tank)
1. Measuring element...........................................................
3. Mounting position:............................................................ (type and standard) (e.g. Pt100 or TC type K)
(e.g. vertical, 45° against flow)
1.1. Tolerance:.........................................................................
4. Temperature (measuring point): ......................................
1.2. Design: .............................................................................
Operating temperature:....................................................
(e.g. Pt100 or 2, 3 or 4-wire system)
Temperature range: .........................................................
1.3. Degree of protection/type of protection: ..........................
5. Medium: ...........................................................................
2. Protective fitting:...............................................................
6. Pressure: ..........................................................................
Nominal pressure: ............................................................ 2.1. Protective tube: ................................................................
Operating pressure: ......................................................... (dimensions/material)
7. Flow: ................................................................................. 2.2. Mounting: .........................................................................
(dimensions/material)
8. Vibrations: ........................................................................
2.3. Neck tube:........................................................................
9. Miscellaneous: .................................................................
(dimensions/material)
(e.g. vessel or pipe materials, PTFE lining)
2.4. Mounting length/nominal length:......................................
■ Ambient conditions 3. Material certificates: .........................................................
(e.g. seawater atmosphere, chemical plant)
4. Connection: ......................................................................
Definition:.................................................................................
4.1. Connection head/box:......................................................
.................................................................................................
4.2. Cable:...............................................................................
.................................................................................................
(dimensions/insulation/standard)
■ Special information 4.3. Other: ...............................................................................
1. Mounting of temperature transmitter in connection head: .........................................................................................
......................................................................................... 5. Tests: ................................................................................
......................................................................................... .........................................................................................
2. Packaging regulations: .................................................... 6. Accessories:.....................................................................
......................................................................................... .........................................................................................
.........................................................................................
7. Supplementary requirements:..........................................
.........................................................................................
3 mm (inch):
• 500 (19.7)
• 710 (28.0)
kg (lb):
0.9 (1.98)
1.1 (2.43)
7 MC 1 0 0 0
7 MC 1 0 0 0
-
-
1 BA 2 7
2 BA 2 7
• 1000 (39.4) 1.5 (3.31) 7 MC 1 0 0 0 - 3 BA 2 7
• 1400 (55.1) 1.9 (4.19) 7 MC 1 0 0 0 - 4 BA 2 7
• 2000 (78.7) 2.7 (5.95) 7 MC 1 0 0 0 - 5 BA 2 7
Connection head, form B,
The flue gas resistance thermometer with connection head is made of cast light alloy,
suitable for the temperature range from -50 to +600 °C with 1 cable inlet and
(-58 to +1112 °F) and can also be supplied with a built-in tem- • screw cover 1
perature transmitter. • standard hinged cover 4
Please order mounting flange or threaded sleeve separately. • high hinged cover 6
Further designs Order code
■ Technical specifications Please add "-Z" to Order No. and specify
Order code(s) and plain text.
Design According to DIN 43764:
Thermometer without mount • Different design (mounting length, protec- Y01
tive tube material etc.), specify in plain text.
Protective tube • TAG plate made of stainless steel Y15
• Form 1, DIN 43772; cylindrical, 15 mm specify TAG No. in plain text
diameter (0.59 inch), wall thick- • Calibration carried out at one point, specify Y33
ness 3 mm (0.12 inch), seamless desired temperature in plain text (order
equivalent number of times for several cal-
• Material St 35.8, mat. No. 1.0305, enam- ibration points).
elled
Accessories Order No.
• Loading capacity 1 bar (14.5 psi) above atmo-
spheric, to DIN 43772 Mounting flange 7 MC 2 9 9 8 - 5 C A
Adjustable, to DIN 43734;
Measuring insert Replaceable, with measuring
Material: GTW 35, mat. No. 0.8035,
insert tube (8 mm diameter
for protective tube diameter
(0.31 inch)) made of stainless
15 mm (0.59 inch),
steel; terminal block with clamp-
0.3 kg (0.66 lb)
ing springs
Gas-tight threaded sleeve
■ Dimensional drawings Material: 9 SMnPb 28
Material No. 1.0718,
for protective tube diameter
15 mm (0.59 inch),
0.4 kg (0.88 lb)
• G¾ internal thread with gasket 7 MC 2 9 9 8 - 5 D A
• G½ internal thread with gasket 7 MC 2 9 9 8 - 5 D C
To order a temperature transmitter installed in the connection head,
see "Temperature transmitters for installation in the connection
head" (page 3/64).
Individual parts: Measuring inserts, see "Accessories".
Low-pressure screw-in resistance thermometer with neck tube, dimen- Individual parts: Measuring inserts and connection heads, see "Acces-
sions in mm (inches) sories".
• In air with flow velocity v = 1 m/s t 0.5 = 2.2 min, t0.9 = 6.8 min Individual parts: Measuring inserts and connection heads, see "Acces-
(3.28 ft/s) sories".
■ Dimensional drawings
■ Overview
u
The resistance thermometer for damp rooms is suitable for a Resistance thermometer for
damp rooms
temperature range from -30 to +60 °C (-22 to +140 °F).
stainless steel protective tube
Protective tube Made of stainless steel • with two Pt100 measuring resistors 7MC1027-1AB
Connection head Made of cast light alloy, with
cable bushing; made of plastic on
0.1 kg (0.22 kg)
Further designs Order code
3
request Please add "-Z" to Order No. and specify
Measuring insert 1 or 2 Pt measuring resistors to Order code(s) and plain text.
DIN EN 60751, connection in • Different design (mounting length, protec- Y01
three-wire or two-wire system, tive tube material etc.), specify in plain text.
class B • TAG plate made of stainless steel Y15
Degree of protection IP65 acc. to DIN EN 60529 specify TAG No. in plain text
• Calibration carried out at one point, specify Y33
■ Dimensional drawings
desired temperature in plain text (order
equivalent number of times for several
calibration points).
} Available ex stock
To order a temperature transmitter installed in the connection head,
see "Temperature transmitters for installation in the connection
head" (page 3/64).
Note:
Additional fitting of head mounted transmitter of SITRANS TH series is
possible.
3 ■ Design
Resistance of internal conductor Per measuring circuit, i.e. for both
conductors of the two-wire sys-
tem: 0.17 Ω/m measuring insert
The measuring resistor is fitted in a 60 mm (2.36 inch) long stain- Resistance of measuring insert ≥ 1000 MΩ at room temperature
less steel sleeve with an outer diameter of 6 mm (0.24 inch). The
sleeve and the sheath of the supply cable are welded. The Outer diameter of sleeve 6 mm (0.24 inch)
sheath of the supply cable is also made of stainless steel, and Explosion protection II 2G EEx ia IIC T4/T6
its outer diameter is 5 mm (0.2 inch).
The conductors are made of special copper and are embedded
in highly compacted magnesium oxide powder. The connection ■ Dimensional drawings
points between the measuring resistor and the conductors are
additionally isolated. The conductors are potted in the terminal
base.
The rating plate is located underneath the retaining plate.
3 Mounting
length U
Protective tube
length L
Weight
mm (inch)
mm (inch) mm (inch)
• 65 (2.56) 140 (5.51) 0.3 (0.66) 7MC1905-1GA
• 65 (2.56) 200 (7.87) 0.5 (1.1) 7MC1905-2GA
• 125 (4.92) 200 (7.87) 0.5 (1.1) 7MC1905-3GA
• 125 (4.92) 260 (10.24) 0.6 (1.32) 7MC1905-4GA
Up to 550 °C (1022 °F)
Protective tube to DIN 43772, form 4 made of 6 CrNiMoTi 17122, mat. No. 1.4571
Mounting Protective tube Weight
length U length L kg (lb)
mm (inch) mm (inch)
• 65 (2.56) 140 (5.51) 0.3 (0.66) 7MC1905-1DA
• 65 (2.56) 200 (7.87) 0.5 (1.1) 7MC1905-2DA
• 125 (4.92) 200 (7.87) 0.5 (1.1) 7MC1905-3DA
• 125 (4.92) 260 (10.24) 0.6 (1.32) 7MC1905-4DA
■ Integration
Instrument combination for measuring and controlling temperature, with thermocouple element as sensor
Sense Thermocouple
3
Match Cold junction thermostat Cold junction with power supply unit
Catalog FI 01 Catalog FI 01
Electric transmitter
Catalog FI 01
controller MP 31
Furnace cham- 1350 (2462) Pt 10% Rh/Pt Outside: Silicon car- Preheated air 700 (1292) Ni Cr/Ni As above
ber bide behind recuper-
inside: KER 710 ator
Measuring Permissible Thermocou- Protective tube Measuring Permissible Thermocou- Protective tube
point operating ple point operating ple
temperature temperature
°C (°F) °C (°F)
6. Annealing furnace, roller-hearth furnace 11.2 In hardening shop baths
(protective tubes bored from the solid are recommended)
Furnace cham-
ber
800 (1472) Ni Cr/Ni X 10 CrAl 24,
mat. No. 1.4762,
dished
Salt and nitre 550 (1022) Ni Cr/Ni Soft iron,
mat. No. 1.1003
3
Exhaust gas 600 (1112) Ni Cr/Ni As above Cyanogen 950 (1742) Ni Cr/Ni Soft iron or
duct X 15 CrNiSi 24 19,
mat. No. 1.4841
7. Bell-type anneal. furn.
Baths contain- 1050 (1922) Pt 10% Rh/Pt Outside: X 10 CrAl
Directly heated 950 (1742) Ni Cr/Ni X 10 CrAl 24, ing chloride 24,
furnace mat. No. 1.4762, mat. No. 1.4762,
dished inside: KER 710
Stack for tin 600 ... 900 Ni Cr/Ni Special design, bare Lead baths 1200 (2192) Pt 10% Rh/P Outside: Chromium
plates (1112 ... 1652) thermocouple ele- nickel alloy
ment with thermal NiCr 60 15,
contact plate mat. No. 2.4867,
Stack for motor- 700 ... 920 Ni Cr/Ni As above inside: KER 710;
car body sheet (1292 ... 1688) bored from the solid
Protective gas 650 (1202) Ni Cr/Ni Bare thermocouple Barium chloride 1300 (2372) Pt 10% Rh/Pt Outside: Chromium
element baths nickel alloy
NiCr 60 15,
8. Sinter belts mat. No. 2.4867,
(Sucking boxes) 400 (752) Fe/Cu Ni (Jacket thermocou- inside: KER 710;
ple element) B. Metallurgical plants (only limited life time in molten metals)
X 10 CrAl 24,
mat. No. 1.4762 Copper melt 1250 (2282) Pt 10% Rh/Pt Outside: X 10 CrSi
29, mat. No. 1.4772,
For temperature 400, 500 Fe/Cu Ni As above, with dou- bored from the solid
maximum com- (752, 932) ble thermocouple inside: KER 710
puting circuit
Exhaust of cop- 1300 (2372) Pt 10% Rh/Pt Outside: Silicon car-
9. Tinning plants per melting fur- bide
Palm nut oil, 650 (1202) Ni Cr/Ni St 35.8, naces inside: KER 710
pickling vat, tin mat. No. 1.0305, Brass melts 900 (1652) Ni Cr/Ni X 10 CrAl 29,
bath seamless, enamelled mat. No. 1.4772,
10. Zinc coating plants bored from the solid
Zinc bath 480 (896) Fe/Cu Ni St 35.8, Aluminium melts 700 (1292) Ni Cr/Ni Pearlite iron GG 22,
mat. No. 1.0305, bored from the solid
seamless Die-casting, 700 (1292) Ni Cr/Ni Soft iron,
11. Heat treatment plants magnesium mat. No. 1.1003,
bored from the solid
11.1 In gases
Bearing metal, 600 (1112) Fe/Cu Ni St 35.8,
Tempering fur- 550 (1022) Ni Cr/Ni St 35.8, lead and tin mat. No. 1.0305,
naces mat. No. 1.0305, melting houses seamless, enamelled
seamless
Lead foundries 700 (1292) Fe/Cu Ni Chromium nickel
Annealing in oxi- 1050 (1922) Pt 10% Rh/Pt Outside: X 10 CrAl alloy
dizing gases (Ni Cr/Ni) 24, NiCr 60 15,
containing sul- mat. No. 1.4762, mat. No. 2.4867,
phur and car- dished bored from the solid
bon inside: KER 710
Zinc foundries 480 (878) Fe/Cu Ni St 35.8,
1200 (2192) Pt 10% Rh/Pt Outside: X 10 CrAl mat. No. 1.0305,
24, seamless
mat. No. 1.4762,
dished 600 (1112) Fe/Cu Ni Silicon carbide
inside: KER 710 Exhaust gases 1300 (2372) Pt 10% Rh/Pt Outside: Silicon car-
Annealing in 1200 (2192) Pt 10% Rh/Pt As above of zinc melting bide
reducing gases furnaces inside: KER 710
containing sul- C. Ceramic industry
phur
Ring kiln for 800 ... 1100 Ni Cr/Ni X 10 CrAl 24,
Annealing in 1200 (2192) Pt 10% Rh/Pt Outside: standard bricks (1472 ... 2012) mat. No. 1.4762,
nitrogen-con- X 15 CrNiSi 24 19, dished
taining gases mat. No. 1.4841,
poor in oxygen, dished; Ring kiln for clin- 1200 ... 1300 Pt 10% Rh/Pt Outside and inside:
also nitriding inside: KER 710 kers, retort fur- (2192 ... 2372) KER 710
furnaces with nace, tunnel
ammonia furnace, glaz-
ing kiln
Measuring Permissible Thermocou- Protective tube Measuring Permissible Thermocou- Protective tube
point operating ple point operating ple
temperature temperature
°C (°F) °C (°F)
D. Glass industry G. Steam power parts
Sulphur com- to 1500 (2732) Pt 30% Rh/ Pt Outside: Silicon car- Cu/Cu Ni Type T
bustion fur- 6% Rh bide Fe/Cu Ni Type J
naces, pyrite inside: KER 710
burnerr Ni Cr/Ni Type K
Behind waste 600 (1112) Ni Cr/Ni X 10 CrAl 24, Ni Cr Si-NiSi Type N
heat boiler mat. No. 1.4762 Pt 10% Rh/Pt Type S
Pt 13% Rh/Pt Type R
Pt 30% Rh/ Pt 6% Rh Type B
3
To order the sensor with a built-in
temperature transmitter, add "-Z" to
the Order No. of the sensor, and
supplement by the following Order
code:
• SITRANS TH200
- without Ex T20
- EEx ia IIC and EEx n for zone 2 T21
- FM (IS, I, NI) T23
• SITRANS TH300
- without Ex T30
- EEx ia IIC und EEx n for zone 2 T31
The following temperature transmitters are available for mount-
- FM (IS, I, NI) T33
ing in the connection head:
• SITRANS TH400 PA
SITRANS TH200
- without Ex T40
Programmable two-wire temperature transmitter (4 to 20 mA),
- EEx ia T41
electrical isolation for resistance thermometers and thermocou-
ple elements. • SITRANS TH400 FF
■ General information
Customer: ....................................................................................
Address: ......................................................................................
Contact partner: .........................................................................
Purchasing dept.: ........................................................................ Tel.: ...........................................................................
3 Sales dept.: ................................................................................. Tel.: ...........................................................................
Process dept.: ............................................................................. Tel.: ...........................................................................
Inquiry:.........................................................................................
Quotation: ....................................................................................
Place and date: ...........................................................................
2. Location:...........................................................................
■ Sensor design
(e.g. pipe bend, tank)
1. Measuring element...........................................................
3. Mounting position:............................................................ (type and standard) (e.g. Pt100 or TC type K)
(e.g. vertical, 45° against flow)
1.1. Tolerance:.........................................................................
4. Temperature (measuring point): ......................................
1.2. Design: .............................................................................
Operating temperature:....................................................
(e.g. Pt100 or 2, 3 or 4-wire system)
Temperature range: .........................................................
1.3. Degree of protection/type of protection: ..........................
5. Medium: ...........................................................................
2. Protective fitting:...............................................................
6. Pressure: ..........................................................................
Nominal pressure: ............................................................ 2.1. Protective tube: ................................................................
Operating pressure: ......................................................... (dimensions/material)
7. Flow: ................................................................................. 2.2. Mounting: .........................................................................
(dimensions/material)
8. Vibrations: ........................................................................
2.3. Neck tube:........................................................................
9. Miscellaneous: .................................................................
(dimensions/material)
(e.g. vessel or pipe materials, PTFE lining)
2.4. Mounting length/nominal length:......................................
■ Ambient conditions 3. Material certificates: .........................................................
(e.g. seawater atmosphere, chemical plant)
4. Connection: ......................................................................
Definition:.................................................................................
4.1. Connection head/box:......................................................
.................................................................................................
4.2. Cable:...............................................................................
.................................................................................................
(dimensions/insulation/standard)
■ Special information 4.3. Other: ...............................................................................
1. Mounting of temperature transmitter in connection head: .........................................................................................
......................................................................................... 5. Tests: ................................................................................
......................................................................................... .........................................................................................
2. Packaging regulations: .................................................... 6. Accessories:.....................................................................
......................................................................................... .........................................................................................
.........................................................................................
7. Supplementary requirements:..........................................
.........................................................................................
3
1 thermocouple
Leg diameter 2 mm (0.08 inch)
Weight: 1.1 ... 2.9 kg (2.4 ... 6.4 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 D C 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 D C 0 7
• 1000 (39.4) 7 MC 2 0 0 0 - 3 D C 0 7
2 thermocouples
The straight thermocouple together with a metal protective tube Leg diameter 2 mm (0.08 inch)
is suitable for temperatures from 0 to 1250 °C (32 to 2282 °F) and Weight: 1.1 ... 3.2 kg (2.4 ... 7.0 lb)
can be supplied with a built-in temperature transmitter. Nominal length in mm (inch)
• 500 (19.7) 7 MC 2 0 0 0 - 1 D D 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 D D 0 7
■ Technical specifications • 1000 (39.4) 7 MC 2 0 0 0 - 3 D D 0 7
Thermocouples Ni Cr/Ni type K to 1100 °C (2012 °F)
X 18 CrN28, material No. 1.4749
• Number 1 or 2 26 mm Ø x 4 mm (1.02 inch x 0.16 inch)
• Leg diameter 2 ... 3 mm (0.08 ... 0.12 inch) 1 thermocouple
Leg diameter 3 mm (0.12 inch)
• Insulation of legs Insulating beads Weight: 1.3 ... 2.2 kg (2.7 ... 4.8 lb)
Protective tube Metal Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 E C 0 7
Connection head Form A, DIN 43729; made of cast • 710 (28.0) 7 MC 2 0 0 0 - 2 E C 0 7
light alloy, with one cable bushing • 1000 (39.4) 7 MC 2 0 0 0 - 3 E C 0 7
2 thermocouples
■ Dimensional drawings Leg diameter 3 mm (0.12 inch)
Weight: 1.4 ... 2.4 kg (3.1 ... 5.3 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 E D 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 E D 0 7
• 1000 (39.4) 7 MC 2 0 0 0 - 3 E D 0 7
to 1200 °C (2192 °F)
X 15 CrNi Si 24 19, material No. 1.4841
22 mm Ø x 2 mm (0.87 inch x 0.079 inch)
1 thermocouple
Leg diameter 2 mm (0.08 inch)
Weight: 1.7 ... 2.9 kg (3.7 ... 6.4 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 F C 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 F C 0 7
Straight thermocouple, dimensions in mm (inches) • 1000 (39.4) 7 MC 2 0 0 0 - 3 F C 0 7
2 thermocouples
■ Design Leg diameter 2 mm (0.08 inch)
Weight: 1.9 ... 3.1 kg (4.2 ... 6.8 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 F D 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 F D 0 7
• 1000 (39.4) 7 MC 2 0 0 0 - 3 F D 0 7
To 1250 °C (2282 °F)
CrAl 205 (Megapyr), material No. 1.4767
22 mm Ø x 2 mm (0.87 inch x 0.079 inch)
1 thermocouple
Leg diameter 3 mm (0.12 inch)
Weight: 1 ... 2.9 kg (2.2 ... 6.4 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 H C 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 H C 0 7
• 1000 (39.4) 7 MC 2 0 0 0 - 3 H C 0 7
Straight thermocouple with base-metal element Ni Cr/Ni with metal pro- 2 thermocouples
tective tube Leg diameter 3 mm (0.12 inch)
Weight: 1.1 ... 3.2 kg (2.4 ... 7.0 lb)
Nominal length in mm (inch):
• 500 (19.7) 7 MC 2 0 0 0 - 1 H D 0 7
• 710 (28.0) 7 MC 2 0 0 0 - 2 H D 0 7
• 1000 (39.4) 7 MC 2 0 0 0 - 3 H D 0 7
Connection head, form A,
• made of cast light alloy,
with 1 cable inlet and
- screw cover 1
- high hinged cover 6
Selection and Ordering data Order No. Selection and Ordering data Order No.
Straight thermocouple with Thermocouples elements for straight
Ni Cr/Ni thermocouple (type K) thermocouple according to DIN 43733
for temperatures to 1250 °C (2282 °F);
with metallic protective tube Base-metal thermocouple with insulating
beads
Further designs Order code Wire diameter 3 mm (0.12 inch)
Please add "-Z" to Order No. and specify Ni Cr/Ni, to 1000 °C (maximal 1300 °C),
3
Order code(s) and plain text. (to 1832 °F (max. 2372 °F))
• Different design (mounting length, protec- Y01 0.55 ... 2.10 kg (1.21 ... 4.63 lb)
tive tube material etc.), specify in plain text. Nominal Thermocouple
• TAG plate made of stainless steel Y15 length L1 in length L2 in
specify TAG No. in plain text mm (inch): mm (inch):
• Calibration carried out at one point, specify Y33 • 500 (19.7) 540 (21.3) 7MC2903-1CA
desired temperature in plain text (order • 710 (28.0) 750 (29.5) 7MC2903-2CA
equivalent number of times for several cal- • 1000 (39.4) 1040 (40.9) 7MC2903-3CA
ibration points).
To order a temperature transmitter installed in the connection head,
see "Temperature transmitters for installation in the connection
head" (page 3/83).
Installation of a transmitter is only possible here in the versions with a
high hinged cover (7MC2000-....6).
■ Dimensional drawings
Mounting flange to DIN 43734 (left) and threaded sleeve (right) for install-
ing straight thermocouples, dimensions in mm (inches)
The jacket thermocouple with extension lead is suitable for a Jacket thermocouple element
with extension lead
temperature range from 0 to 700, 1000 or 1100 °C (32 to 1292,
1832 or 2012 °F); a temperature of 80 to 260 °C (176 to 500 °F) Maximum temperature of medium 700 °C
is permissible for the extension lead. (1292 °F), jacket outer diameter 0.5 mm
(0.02 inch)
3
Jacket thermocouple with connection head, form B, made of cast light al-
loy, dimensions in mm (inches)
Selection and Ordering data Order No.
Jacket thermocouple element
The jacket thermocouple with connection head, form B is suit- with connection head, form B
able for the temperature range from 0 to 800 or 1,100 °C Fe/Cu Ni type J thermocouple
(32 to 1472 or 2012 °F) and can also be supplied with a built-in Jacket made of X 6 CrNiTi 18 10, material No.
temperature transmitter. 1.4541, temperature up to 800 °C (1472 °F)
1 thermocouple
■ Technical specifications Jacket outer diameter/mm (inch):
• 3.0 (0.12) 7MC2021-2CE-Z
Jacket thermocouple with connection head, form B • 6.0 (0.24) 7MC2021-4CE-Z
2 thermocouples
Thermocouple Fe/Cu Ni, Fe-CuNi or Ni Cr/Ni Jacket outer diameter/mm (inch):
Jacket Measuring junction insulated from base of • 3.0 (0.12) 7MC2021-2CF-Z
jacket • 6.0 (0.24) 7MC2021-4CF-Z
• Material X 6 CrNiTi 18 10, mat. Inconel Fe/Cu Ni type L thermocouple
No. 1.4541 Jacket made of X 6 CrNiTi 18 10, material No.
1.4541, temperature up to 800 °C (1472 °F)
• Temperature Up to 800 °C (1472 °F) Up to 1100 °C 1 thermocouple
(2012 °F) Jacket outer diameter/mm (inch):
Connection head Form B to DIN 43729 • 3.0 (0.12) 7MC2021-2CA-Z
• 6.0 (0.24) 7MC2021-4CA-Z
• Material Cast light alloy 2 thermocouples
• Temperature -30 ... +100 °C (-22 ... +212 °F) is permissible Jacket outer diameter/mm (inch):
• 3.0 (0.12) 7MC2021-2CB-Z
• Cable inlet For cables up to 15 mm (0.59 inch) diameter • 6.0 (0.24) 7MC2021-4CB-Z
• Terminal block Without clamping springs Ni Cr/Ni type K thermocouple
Jacket made of Inconel,
Thermocouple temperature up to 1,100 °C (2012 °F)
• Insulation resistance between conductors and jacket: 1 thermocouple
≥ 1000 MΩ/m at 20 °C (≥ 305 MΩ/ft at 68 °F) Jacket outer diameter/mm (inch):
• 3.0 (0.12) 7MC2021-2LC-Z
• Minimum bending radius: 5 x outer diameter of jacket • 6.0 (0.24) 7MC2021-4LC-Z
• Leak resistance of measuring junction: 2 thermocouples
Tested at 40 bar (580 psi) Jacket outer diameter/mm (inch):
• 3.0 (0.12) 7MC2021-2LD-Z
Thermo- Jacket No. of Thermo- Resis- • 6.0 (0.24) 7MC2021-4LD-Z
couple thermo- couple tance (for Further designs Order code
Outer Wall couples wire double
diameter thickness Please specify Order code(s) and plain text.
diameter conduc-
tor) • Length L in m (ft)
- 0.25 (0.82) A01
mm (inch) mm (inch) mm (inch) Ω/m (Ω/ft) - 1 (3.28) A02
Fe/Cu Ni 3.0 (0.12) 0.42 1 0.54 (0.02) 2.7 (8.9) - 5 (16.4) A03
(type J) and (0.017) - 10 (32.8) A04
Fe-CuNi • Different design (mounting length, protec- Y01
(type L) 0.42 2 0.48 (0.02) 3.5 (11.5) tive tube material etc.), specify in plain text.
(0.017) • TAG plate made of stainless steel Y15
6.0 (0.24) 0.55 1 1.07 (0.04) 0.66 (2.2) specify TAG No. in plain text
(0.022) • Calibration carried out at one point, specify Y33
desired temperature in plain text (order
0.89 2 0.81 (0.03) 1.14 (3.7) equivalent number of times for several cal-
(0.035) ibration points).
Ni Cr/Ni 3.0 (0.12) 0.42 1 0.54 (0.02) 4.3 (14.1) To order a temp. transmitter installed in the connection head, see
(type K) (0.017) "Temp. transm. for installation in the connection head" (page 3/83).
0.42 2 0.48 (0.02) 5.5 (18.0) Note: SITRANS T3K PA can only be used in a connection head with high
(0.017) hinged cover. Can be ordered als special version (...-Z Y01).
6.0 (0.24) 0.55 1 1.07 (0.04) 1.12 (3.7) Example of ordering:
(0.022)
The following is required:
0.89 2 0.81 (0.03) 1.94 (6.4) • Jacket thermocouple element
(0.035) jacket made of X 6 CrNiTi 18 10; outer diameter 3.0 mm (0.12 inch);
- with 1 Fe/Cu Ni thermocouple, type J; nominal length 5 m (16.4 ft)
Order as follows:
1 jacket thermocouple 7MC2021-2CE-Z A03
The sensor is suitable for a temperature range from 0 to 800, Jacket thermocouple element
with coupling socket
1000 or 1100 °C (32 to 1472, 1832 or 2012 °F); a maximum tem-
Ni Cr/Ni type K thermocouple
perature of 130 °C (266 °F) is permissible for the plug connec-
tion. Jacket material No. 1.4541
Temperature of medium 800 °C (1472 °F)
■ Technical specifications 1 thermocouple
3 Thermocouple Ni Cr/Ni
Jacket outer dia./
mm (inch):
Length L/m (ft):
3
Number of conductors and cross-section:
2 x 0.22 mm² (2 x 0.00034 inch²)
Temperature range -20 ... +80 °C
(-4 ... +176 °F)
Outer diameter 4 mm (0.16 inch) 7MC2921-2AC-Z
Silicone-silicone isolation d D l L SW
Number of conductors and cross-section:
2 x 0.22 mm² (2 x 0.00034 inch²) mm (inch) mm (inch) mm (inch)
Silicone-silicone isolation 1,5 (0.06) M8x1 8 (0.3) 32 (1.3) 12
Temperature range -40 ... +180 °C
(-40 ... +356 °F) 3,0 (0.12) M8x1 8 (0.3) 32 (1.3) 12
Outer diameter 6 mm (0.24 inch) 7MC2921-3AC-Z 6,0 (0.24) G¼ 10 (0.4) 48 (1.9) 19
PVC isolation
Compression joint with M8 x 1 or G¼ thread dimensions in mm (inches)
Number of conductors and cross-section:
4 x 0.22 mm² (2 x 0.00034 inch²)
Temperature range -20 ... +80 °C
(-4 ... +176 °F)
Outer diameter 6 mm (0.24 inch) 7MC2921-4AC-Z
Silicone-silicone isolation
Number of conductors and cross-section:
4 x 0.22 mm² (2 x 0.00034 inch²)
Temperature range -40 ... +180 °C
(-40 ... +356 °F)
Coupling socket, dimensions in mm (inches)
Further designs Order code
Please specify Order code(s) and plain text. Selection and Ordering data Order No.
• Length of extension lead in m (ft) Screw nipple
- 0.25 (0.82) A01 for soldering jacket thermocouple elements
- 1 (3.28) A02 The screw nipple has a centering hole and must be
- 5 (16.4) A03 drilled according to the outer diameter of the jacket
thermocouple element.
- 10 (32.8) A04 The thermocouple must be protected from exces-
sive heat when soldering (e.g. by blowing with air).
■ Other individual parts • with M8 x 1 thread, for jacket outer diameter up to 7MC2922-1EA
• Screw nipple 3.0 mm (0.12 inch); 0.01 kg (0.02 lb)
• Compression joint • with G¼ thread, for all jacket outer diameters list- 7MC2922-1FB
ed in the catalog, 0.02 kg (0.04 lb)
• Coupling socket
Compression joint, gas-tight
• Coupling plug Temperature up to 350 °C (662 °F)
Pressure-tight up to 80 bar (1160 psi)
■ Dimensional drawings Subsequent release and movement is not possible,
material X6 CrNi Mo Ti 17–122, material No 1.4571;
tapered ring like compression joint
• Thread M8 x 1; 0.03 kg (0.06 lb)
- jacket outer diameter 1.5 mm (0.06 inch) 7MC2922-3AA
- jacket outer diameter 3.0 mm (0.12 inch) 7MC2922-3BA
• Thread G¼; 0.04 kg (0.08 lb)
- jacket outer diameter 6 mm (0.24 inch) 7MC2922-3DB
Coupling socket
of jacket thermocouple 7MC2028 (one per element); 7MC2922-4BB
for Ni Cr/Ni thermocouple element, type K; 0.05 kg
(0.11 lb)
Screw nipple with M8 x 1 thread (left) or G¼ (right), dimensions in mm
(inches) Coupling plug
matching the jacket thermocouple 7MC2028 with 7MC2922-4BD
socket; one plug is required per thermocouple ele-
ment; for Ni Cr/Ni thermocouple, type K; 0.05 kg
(0.11 lb)
■ Dimensional drawings
■ Technical specifications
Signal input For thermocouple elements acc. to
DIN IEC 584 and DIN 43710
Ref. temperature 0 or 20 °C (32 or 68 °F)
Error limits 0.5 K (0.9 °F)
Temperature error <0.1 K / 10 K change (0.18°F/18 °F)
Connection diagram of cold junction
■ Function
The temperature of the aluminium block is held constant at a ref-
erence temperature of 50, 60 or 70 °C (122, 140 or 158 °F) by an
electronic two-step controller with low hysteresis.
With a constant cold junction temperature, the difference be-
tween the voltage of the measuring element and that of the ref-
erence element is a measure of the temperature at the measur-
ing point. The thermocouples are electrically isolated from one
another and from the power supply.
Cold junction thermostat 7MC2933, dimensions in mm (inches)
■ Technical specifications
Number of measuring 6 or 12 ■ Schematics
points
Ref. temperature 50, 60 or 70 °C (122, 140 or 158 °F)
• Error limits 0.5 °C (0.9 °F)
Effect of ambient tempera- 0.2 °C / 10 K (0.36 °F/18 °F) temperature
ture change
Error limits of control 0.05 °C (0.09 °F)
Permissible ambient tem- -20 ... +45 °C (-4 ... +113 °F)
perature
Power supply (depending Warm-up time
on version)
48 ... 63 Hz,
24, 110 or 220 VAC ± 15%,
• Approx. 30 VA Approx. 10 min
• 24 V DC, approx. 30 W Approx. 10 min
• 24 V DC, approx. 17 W Approx. 20 min
Degree of protection IP54 to DIN 40050
Resistance to vibration Frequency Acceleration Test period
Cold junction thermostat 7MC2933, connection diagram
5 ... 55 Hz 1 g, constant 4 min
30 Hz 10 g 1 min
Weight Approx. 9.5 kg (20.9 lb)
3 Thermocouple
Fe-CuNi Type L A
Ni Cr/Ni Type K B
Pt10% Rh/Pt Type S C
Cu-CuNi Type U D
Number of cold junctions
12 A
The cold junction thermostat is used to keep the cold junction
24 B
temperature constant when measuring temperature using ther-
mocouples. Power supply
220 V AC 1
■ Design 110 V AC 2
24 V AC 3
The cold junction thermostat consists of an aluminium block in 24 V DC 4
which 12 or 24 reference elements are fitted, a controller, a
heater and a power supply unit. Temperature control
The aluminium block, controller, heater and power supply unit with resistance thermometer;
electronic monitoring of the temperature
are designed as crystal modules. In this manner, uniform tem-
perature distribution and protection against external effects are • in the thermostat
ensured. - with relay output 1
A Pt100 resistance thermometer or an electronic monitoring unit - without 24 V DC output 2
with relay output or 24 V DC output are fitted to permit checking
of the temperature in the aluminium block (thermostat). The mon-
itoring unit is triggered when the maximum or minimum temper-
■ Dimensional drawings
ature of the cold junction block is violated or if the power supply
fails.
A signalling lamp "Operation" is present in the door.
The cold junction thermostat has a sheet-steel housing.
■ Function
The temperature of the aluminium block is held constant at a ref-
erence temperature of 50, 60 or 70 °C (122, 140 or 158 °F) by an
electronic two-step controller with low hysteresis.
With a constant cold junction temperature, the difference be-
tween the voltage of the measuring element and that of the ref-
erence element is a measure of the temperature at the measur-
ing point. The thermocouples are electrically isolated from one
another and from the power supply.
3
stainless steel 1.4301, IP67
• Form B, cover with 2 slotted
screws,
aluminium, IP54, standard
• Form B, screw cover,
plastic, IP54 (BK)
• Form B, hinged cover with slot-
The resistance thermometer is designed for installation in tanks ted screws,
and pipelines as well as for the measurement of temperature aluminium, IP65 (BUZ)
with hygiene requirements. The usual process connections are • Form B, hinged cover with
available. The rugged design means that it is suitable for a wide quick-release,
range of process applications in the food, pharmaceutical and aluminium, IP65 (BUS)
biotechnology industries. The resistance thermometer is also • Form B, high hinged cover with
available with a built-in transmitter. A versatile range of head slotted screw,
transmitters is available for this application. aluminium, IP65 (BUZH)
■ Design
Protective tube Stainless steel 1.4404/316L 6 or
9 mm (0.24 or 0.35 inch) diam.,
optionally with tapered tip, see
• Pt100 measuring resistor Selection and Ordering data for
• Stainless steel measuring insert mounting length U1
• Replaceable measuring insert Measuring insert Stainless steel, replaceable
• Process connections for food/pharmaceuticals/biotechnology Pt100 measuring resistor to
• Hygiene version, design corresponds to EHEDG recommen- DIN 43762
dations Rigid design or as jacket element
• Fast response available with reduced tip (mineral-insulated, flexible,
increased vibration resistance)
• Transmitter can be integrated (4 to 20 mA or PROFIBUS PA)
Accuracy of measuring resistor Class A according to
The resistance thermometer has a replaceable measuring in- DIN EN 60751
sert. The measuring insert contains either one or two Pt100 mea- Integration of transmitter Suitable Pt100 transmitters for
suring resistors which are connected to the base in the connec- head mounting can be fitted in
tion head with a two-wire, three-wire or four-wire system. The the connection head, see Selec-
change in resistance dependent on the measured temperature tion and Ordering data
can be recorded by a transmitter and converted into a standard- Process connections • DIN 11851 with slotted union nut
ized signal.
• Clamp connection to DIN 32676
• Clamp connection to ISO 2852
• Tri-clamp
• Varivent
• Neumo BioControl
• Spherical welding-type sleeve
cyl./sph. 30 x 40 mm
(1.18 x 1.57 inch)
• Aseptic connections
The gasket is not included in the
standard scope of delivery! Fur-
ther process connections on
request. Process connection
material: Stainless steel
1.4404/316L
Surface properties
• Standard Surface roughness Ra < 1.5 µm
(5.9 x 10-5 inch)
• Hygiene Surface roughness Ra < 0.8 µm
(3.1 x 10-5 inch)
• Welded seam < 1.5 µm (5.9 x 10-5 inch)
Selection and Ordering data Order No. Order code Selection and Ordering data Order No. Order code
Pt100 resistance thermometer for food, 7 MC 8 0 0 5 - Pt100 resistance thermometer for food, 7 MC 8 0 0 5 -
pharmaceuticals and biotechnology pharmaceuticals and biotechnology
7777 0 - 777 0 777 7777 0 - 777 0 777
Connection head Neck tube length M
• Form B, cast light alloy, screw cover, 1 • 80 mm (3.15 inch) 1
IP54, cable gland • 145 mm (5.71 inch) 2
3
• Form B, plastic, screw cover, 2 • Special version: 9 N1Y
IP54, cable gland (add Order code and plain text)
• Form BUZ, cast light alloy, screw cover, 3
IP65, cable gland Mounting length U1
• Form BUZH, cast light alloy, high hinged 4 • 15 mm (0.59 inch) B
cover, IP 65, cable gland • 35 mm (1.38 inch) C
• Form B, stainless steel, standard, IP67, 5 • 50 mm (1.97 inch) D
cable gland • 100 mm (3.94 inch) E
• Special version: 9 H1Y • 160 mm (6.30 inch) F
(add Order code and plain text) • 250 mm (9.84 inch) G
Process connection, material 1.4404/316L • 400 mm (15.75 inch) H
• Milk pipe union to DIN 11851 with slotted • 4 inch J
union nut and nominal diameter/pressure • 6 inch K
- DN 25 / PN 40 AA • 9 inch L
- DN 32 / PN 40 AB • Special version: Z P1Y
- DN 40 / PN 40 AC (add Order code and plain text)
- DN 50 / PN 25 AD Sensor
• Clamp connection: Thin-film technology:
ISO 2852 DIN Tri-Clamp Outer dia- measuring range -50 ... +400 °C
32676 meter D (-58 ... +752 °F)
• 1 x Pt100, class A, three-wire F
– – ½“/ ¾“ 25.0 mm CA • 2 x Pt100, class A, three-wire G
DN 25/ DN 1“, 1½“ 50.5 mm CB • 1 x Pt100, class A, four-wire H
33.7/38 25/32/40
• Special version: Z Q1Y
DN 40/51 DN 50 2“ 64.0 mm CC (add Order code and plain text)
DN 63.5 – 2½“ 77.5 mm CD
DN 88.9 DN 80 – 106.0 mm CE Further designs Order code
• Varivent connection (Tuchenhagen) Add "-Z" to Order No. and
add Order code.
- D = 50 mm (1.97 inch), KU
for Varivent housing DN 25 and DN 1" • Process connection completely electropol- P01
- D = 68 mm (2.68 inch), KV ished
for Varivent housing DN 40 ... DN 125 • Hygiene version H01
and 1½" ... 6" (Ra < 0.8 µm (3.1 x 10-5 inch))
• Welding piece LA • Certificates
(sphere diameter 30 x 40 mm - Roughness depth measurement Ra C18
(1.2 x 1.6 inch) long) certified by factory certificate to
• Special version: ZA J1Y EN 10204-3.1B
Type of screwed gland and nominal diame- - Material certificate to EN 10204-3.1 C19
ter (add Order code and plain text)
• Specify special version in plain text Y01
Protective tube Measuring insert
• TAG plate made of stainless steel Y15
• Ø F1=6 mm Ø 3/3.2 mm, 1 specify TAG No. in plain text
(0.24 inch) (0.12/0.13 inch)
miner. insul. • Test report (at 0, 50 and 100%) Y33
specify measuring range in plain text
• Ø F1=9 mm Ø 6 mm (0.24 inch) 2
(0.35 inch) To order a temperature transmitter installed in the connection head,
• Ø F1=9 mm Ø 6 mm (0.24 inch) 3 see "Temperature transmitters for installation in the connection
(0.35 inch) miner. insul. head" (page 3/64).
• Ø F1=9 mm Ø 3/3.2 mm, 4
(0.35 inch) (0.12/0.12 inch)
tapered tip miner. insul.
F3=5 Ø x 20 mm
(0.2 x 0.79 inch)
• Special version: 9 L1Y
(add Order code and plain text)
■ Dimensional drawings
Connection heads
)RUP%KLJKKLQJHGFRYHUZLWK
)RUP%VFUHZFRYHU
VORWWHGVFUHZDOXPLQLXP
)RUP%FRYHUZLWK ,3%8=+
VORWWHGVFUHZV SODVWLF,3%.
DOXPLQLXP,3 0[IRUFDEOHGLDP
0[ 0[ 3
DSSUR[
IRUFDEOHGLDP IRUFDEOHGLDP
DSSUR[
DSSUR[
DSSUR[
DSSUR[
DSSUR[
DSSUR[
0
0
0
)RUP%VWDQGDUGVFUHZFRYHU
VWDLQOHVVVWHHO,3
&DEOHJODQG
SODVWLF0[
º IRUFDEOH
DSSUR[
DSSUR[
0
1HFNWXEHOHQJWK0XSWRVHDOLQJIDFH
Process connections
7
DSHUHGQLSSOHZLWKVORWWHGQXW &ODPSFRQQHFWLRQ 6SKHULFDOZHOGLQJW\SHVOHHYH
',1RUDVHSWLF WR',1 6SKHUH[PP[LQ
WR',1 RU,6275,FODPS
'1WRರWRರ '1WR
ರWRರ
0
0
0
GLDP'
8
8
8
3URWHFWLYHWXEHEDVHGRQ',1
9DULYHQWFRQQHFWLRQ 1HXPD%LR&RQWURO
'IRU9DULYHQWKRXVLQJ'1DQGರ 6L]H'GLDP
'IRU9DULYHQWKRXVLQJ'1WR'1 6L]H'GLDP )RUP 6LPLOLDUWRIRUP
DQGರWRರ 6L]H'GLDP WDSHUHGWLS
GLDP)
0
0
8
GLDP' GLDP'
8
8
8
8
■ Schematics
PT100 two-wire PT100 three-wire PT100 four-wire 2xPT100 two-wire 2xPT100 three-wire
1 2 6 2 1 1 2 4 3 1 2 3 4 1 5 2 4 6 3
yellow
yellow
yellow
yellow
yellow
black
black
3 red
red
red
red
red
red
Connection diagram
T2
Result
The pipe collar provides almost
40 (104) identical results compared
to an inline temperature
0 (32)
0 30 60 90 120 Time
[sec]
The temperature sensor with pipe collar is used for temperature Results with steam as measured medium
monitoring, particularly for sterile applications in the food and
pharmaceutical industries.
Temperature measurement is possible following simple, fast as-
sembly on any existing pipeline system. It is not necessary to in-
T2
terrupt the pipeline or to carry out welding. Assembly on the
pipeline is simply carried out by adapting the two halves of the
collar.
Medium T3
The device can be optionally supplied with an integral transmit-
ter.
■ Function T1
Features
• Temperature measurement free of dead space
• Can be retrofitted onto existing pipelines Schematic representation
• Matches all common nominal pipe diameters The result for the actual temperature of the medium T3 depends
on several parameters:
• Optimum temperature measurement using metallic pressing
system • Heat transfer of temperature sensor/pipe
• Insulating collar made of temperature-resistant plastic, easy to • Conductivity of medium
clean • Flow velocity
• Measuring range -20 to +200 °C (-4 to +392 °F) • Pipe wall thickness
• Replaceable Pt100 measuring insert; thus no changes in mea- • Pipe material
suring setup
• Ambient temperature
• Calibration possible
Installation and operating instructions
• Transmitter can be integrated (4 to 20 mA or PROFIBUS PA)
Assembly of the two halves of the pipe collar to the pipe is car-
Mode of operation ried out simply and rapidly by connection of the two M6 hexagon
The temperature measurement is carried out using a Pt100 mea- screws. Any positioning is possible, but the Pt100 measurement
suring element. An integral metallic pressing system guarantees should preferably be made "underneath" the pipeline to achieve
optimum heat transfer between the pipeline and Pt100. The an optimum result.
measuring insert is protected by an insulating sleeve made of Following mounting on the pipeline, the complete Pt100 housing
temperature-resistant plastic. unit can be dismounted on site by loosening a clamping screw.
The complete Pt100 unit can be easily dismounted at any time It is not necessary to disconnect the cable during the usual cal-
for calibration; it is not necessary to disconnect the cables from ibration procedures.
the sensor.
The temperature sensor with pipe collar is available with all stan-
dard DIN connection heads.
■ Technical specifications Selection and ordering data Order No. Order code
Design with connection head Measuring insert in connection Pipe collar Pt100 thermometer 7 MC 8 0 1 5 -
head with neck tube as one unit Stainless steel pressing system 777 0 0 - 7A7 0 777
for insertion into pipe collar.
All standard DIN connection Connection head
heads are available, see Selec- • Form B, cast light alloy, screw cover, 1
tion and Ordering data. IP54, cable gland
■ Dimensional drawings
Connection heads
&RQQHFWLRQKHDGIRUP% &RQQHFWLRQKHDGIRUP%8=+
DOXPLQLXP DOXPLQLXP
DSSUR[
0[ 0[
DSSUR[
DSSUR[
DSSUR[
5RXQGFRQQHFWRUZLWK
VFUHZW\SHFDS0[
DSSUR[
DSSUR[
DSSUR[
)RUP%VWDQGDUGVFUHZFRYHU
VWDLQOHVVVWHHO,3
&DEOHJODQG
SODVWLF0[
º IRUFDEOH
DSSUR[
DSSUR[
0
DSSUR[
0RXQWLQJVFUHZV
&ODPSLQJVFUHZ RIFROODU 3WPHDVXUHPHQW
3WWKUHHZLUH
ഋ; 3LSH2' ZLWKRSWLPL]HGKHDW
WUDQVIHU
3LSH2'
■ Schematics
yellow
black
black
3
red
red
red
red
4 3 5
6 4
7 3
J
1 2
1 2
J J