Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PT 100-Temperature Relay Type TR 250: Digital, 3 Sensors, 3 Limits

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Pt 100-temperature relays type TR

Pt 100-temperature relay type TR 250


digital, 3 sensors, 3 limits
The Pt 100 thermostat TR 250 Order-number: T 224190
TR 250 monitors up to 3 sensors Pt 100
(RTD), Pt 1000, KTY 83 KTY 84
or thermistors (PTC) at the same
time. Different types of sensors,
e.g. Pt 100 and PTC can be
monitored simultaneously.
The unit is especially suitable for
monitoring motors, generators
and transformers.
An other application is the use as
a 2- or 3-step-controller with addi-
tional monitoring of over- or under-
temperature. monitoring of
differences in temperatures of 2
sensors or temperature controller
for heat pumps.

• Measuring and monitoring Displays:


Function range - 199...+850°C • 3 digit 7-segment-display for temperature and
• resolution 0.1 °C selectable programming
within range -19.9...99.9 °C • 3 LEDs for sensors
• 3 relay outputs K1 to K3 with • 3 LEDs for alarms/relays
change-over contacts • °C / °F / resolution 0.1 °C can be selected
• Universal power supply AC/
DC 24-240 V Switching-Functions
• Easy setting • 3 relays
• Storing of values of MIN- and • warmest/coldest sensor switches relay
MAX- temperature • prgrammable for every relay:
• Code-lock against - hysteresis (+ or - = MIN- or MAX-function)
manipulation of settings - autoreset or electronic reclosing lock
• - delay-time for switching and switching back
- operating- or closed current-mode
3 Sensor-Inputs: - cyclic check of function
• Pt 100/1000, 2- or 3-wire • monitoring of difference in temperature
connection • 4 preset programms:
• KTY 83, KTY 84 - motor / generator
• Thermistors (PTC) each 1...6 - transformer with Pt 100
in series - transformer with PTC/Pt 100
• Monitoring of short-circuit and - 3 x 1 alarm per sensor
break

Technical data Rated supply voltage Us AC/DC 24-240 V (AC 20-264 V, DC 20-297 V), 3 VA

Sensor connection 3 x Pt 100 (DIN 43 760/IEC 751) (RTD)


3 x Pt 1000, KTY 83, KTY 84
3 x 1...6 PTC (DIN 44080/44081)
Measuring accuracy <1 % of value ±1 digit
Sensor-current <3 mA
Connection 3-wire, 2-wire, line-resistance max. 2 x 50 Ω

Measuring range -199...+850 °C


Hysteresis -99...+99 °C
Switching delay on/off 0...99 s / 0...999 s
Type of contact type 2 (see "general technical informations")
3 x change-over / alarm
Test conditions see "general technical informations"
Rated ambient temperature -20°C...+65°C
range

Dimensions (h x w x d) design V4: 90 x 70 x 58 [mm], mounting height 55 mm


Protection housing / terminals P 30 / IP 20
Weight app. 200 g
Attachment on 35 mm DIN rail or with screws M4 1.3.7
ZIEHL industrie-elektronik GmbH+Co KG, Daimlerstr. 13, D-74523 Schwäb.Hall, Tel.: +49 791504-0, www.ziehl.com