Product Specifications
PSS 2A-1F8 A
Model RTT80 I/A Series® Temperature Transmitter with HART® 7
Communication Protocol and Optional SIL Certification
The Foxboro® brand Model RTT80 is a microprocessor-based temperature transmitter with HART®
Communication Protocol. It receives input signals from thermocouples, RTDs, ohm, or millivolt sources.
FEATURES
Superior accuracy and long term stability from Optional digital indicator.
microprocessor-based technology. Available as a basic module that can mount to a
Registration to HART Protocol Revision 7 surface or DIN rail, or in explosion-proof
(HART 7) digital communications is standard. universal or dual compartment housings for
Available with or without SIL certification. remote mounting, and integral sensor and
thermowell mounting.
One unit configurable for a variety of
Thermocouple (TC) and Resistance Available with a wide selection of sensors and
Temperature Detector (RTD) inputs. thermowells.
Hot sensor backup - switches to the second Conforms to applicable European Union
sensor if the primary sensor fails. Directives (product marked with “CE” logo).
UNIVERSAL HOUSING
CODES SS AND TT CODES WW AND YY CODES LL AND MM
FOR SURFACE/PIPE MOUNTING WITH BARE SENSOR WITH SENSOR AND THERMOWELL
Single measurement or dual measurement The transmitter can also be configured for sensor
configured as average, difference, or redundant error detection. Output values are independently
measurements configurable between 3.5 and 23 mA for both
shorted and open sensor conditions. Configuration
Hot sensor backup - transmitter switches to the
selections are also provided for direct selection of
second sensor if the primary sensor fails
NAMUR 43 low (3.5 mA) and NAMUR 43 high
Temperature-dependent switching between (23 mA), both independently selectable for either
sensors that are used in different measuring shorted or open sensor conditions. Shorted sensor
ranges detection not applicable for thermocouples.
Output units can be configured for various
temperature units, ohms, or millivolts. TRANSMITTER DIAGNOSTICS
Standard available diagnostics include:
REMOTE COMMUNICATIONS Ambient operating temperature out of range
Remote digital communication is provided with detection
HART communication protocol. Internal electronics diagnostic error detection
Digital HART and 4 to 20 mA dc Protocol Wiring error detection
4 to 20 mA with HART communications allows direct Sensor cable open circuit or short circuit
analog connection to common receivers while still detection
providing full intelligent digital communications using Corrosion detection in sensor connection cables
a HART Communicator or PC-based configurator. Low supply voltage detection
Measurement over range and under range
detection
OPERATING, TRANSPORTATION, AND STORAGE PSS 2A-1F8 A
CONDITIONS Page 5
OP E R AT I N G, T RA N S P ORTAT I O N , A N D S T O R A G E C O N D I T I O N S
E L E CT RO M A G N E T I C C O M PAT I B I L I T Y ( E M C)
CE Compliance
Electromagnetic compatibility in accordance with all the relevant requirements of the EN 61326 series and
NAMUR Recommendation EMC (NE21). For details refer to the Declaration of Conformity. All tests were
passed both with and without ongoing digital HART® communication.
Table 1. Electromagnetic Compatibility (EMC) (a)
ESD (Electrostatic Charge) EN/IEC 61000-4-2 6 kV cont., 8 kV air
Electromagnetic Fields EN/IEC 61000-4-3 0.08 to 2.7 GHz 10 V/m
Burst (Fast Transients) EN/IEC 61000-4-4 2 kV
Surge (Surge Voltage) EN/IEC 61000-4-5 0.5 kV sym.
1 kV assym.
Conducted RF EN/IEC 61000-4-6 0.01 to 80 MHz 10 V
a. Maximum measured error < 1% of the measuring range.
P E R F O R M AN C E S PE CI F I C AT I O N S
In order to obtain the established values in °F, the results in °C must be multiplied by a factor of 1.8.
Response Time
The measured value update depends on the type of sensor and connection method and moves within the
ranges shown in Table 2.
Table 2. Response Time
Resistance Thermometer (RTD) 0.9 to 0.13 s (depends on the connection method 2/3/4-wire)
Thermocouples (TC) 0.8 s
Reference Temperature 0.9 s
Reference Conditions
Calibration temperature: +25°C±3 K
(+77°F±5.4°F)
Supply voltage: 24 V dc
4-wire circuit for resistance adjustment
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 7
Resistance
Thermometer (RTD)
According to Measuring Range
Standard Designation Limits Measured Error (±) Repeatability (±)
Digital (a) D/A (b) Digital (a) D/A (c)
IEC 60751:2008 Pt100 (1) ≤ 0.14 K ≤ 0.05 K (0.09°F)
–200 to +850°C (0.25°F)
Pt200 (2) (–328 to +1562°F) ≤ 0.86 K ≤ 0.13 K (0.23°F)
(1.55°F)
Pt500 (3) –200 to +500°C ≤ 0.30 K ≤ 0.08 K (0.14°F)
(–328 to +932°F) (0.54°F)
Pt1000 (4) –200 to +250°C ≤ 0.14 K ≤ 0.05 K (0.09°F)
(–328 to +482°F) (0.25°F)
JIS C1604:1984 Pt100 (5) –200 to +510°C ≤ 0.12 K ≤. 0.04 K (0.07°F)
(–328 to +950°F) (0.22°F)
DIN 43760 IPTS-68 Ni100 (6) ≤ 0.09 K ≤ 0.03 K (0.05°F)
–60 to +250°C (0.16°F) 0.03% 0.01%
Ni120 (7) (–76 to +482°F) ≤ 0.07 K ( ≙ 2 μA)
(0.13°F)
GOST Pt50 (8) –185 to +1100°C ≤ 0.30 K ≤ 0.05 K (0.09°F)
(–301 to +2012°F) (0.54°F)
Pt100 (9) –200 to +850 °C ≤ 0.14 K ≤ 0.07 K (0.13°F)
(–328 to +1562°F) (0.25°F)
OIML R84: 2003, Cu50 (10) –180 to +200°C ≤ 0.19 K ≤ 0.04 K (0.07°F)
GOST 6651-2009 (–292 to +392°F) (0.34°F)
Cu100 (11) –180 to +200°C ≤ 0.09 K ≤ 0.03 K (0.05°F)
(–292 to +392°F) (0.16°F)
Ni100 (12) –60 to +180°C ≤ 0.09 K ≤ 0.07 K (0.13°F)
(–76 to +356°F) (0.16°F)
Ni120 (13) –60 to +180°C
(–76 to +356°F)
OIML R84: 2003, Cu50 (14) –50 to +200°C ≤ 0.19 K 15 mΩ
GOST 6651-94 (–58 to +392°F) (0.34°F) ≤ 200 mΩ
Resistance Resistance Ω 10 to 400 Ω 40 Ω 15 mΩ
transmitters 10 to 2000 Ω 500 Ω ≤ 200 mΩ
a. Using HART® transmitted measured value.
b. Percentage data refer to the configured span of the analog output signal.
c. Percentage data refer to the current range of the analog output signal (20 mA).
PSS 2A-1F8 A
Page 8 PERFORMANCE SPECIFICATIONS
Thermocouples
(TC) According to Measuring Range
Standard Designation Limits (a) Measured Error (±) Repeatability (±)
Digital (b) D/A (c) Digital (b) D/A (d)
IEC 60584, part 1 Type A (W5Re- 0 to 2500 °C ≤ 1.62 K ≤ 0.52 K (0.94°F)
W20Re) (30) (+32 to + 4532°F) (2.92°F)
Type B (PtRh30- +500 to +1820°C ≤ 2.02 K ≤ 0.67 K (1.21°F)
PtRh6) (31) (+932 to +3308°F) (3.64°F)
Type E (NiCr- –40 to +1000°C ≤ 0.21 K ≤ 0.07 K (0.13°F)
CuNi) (34) (–40 to +1832°F) (0.38°F)
Type J (Fe-CuNi) –40 to +1200°C ≤ 0.26 K ≤ 0.08 K (0.14°F)
(35) (–40 to +2192°F) (0.47°F)
Type K (NiCr-Ni) –40 to +1200°C ≤ 0.32 K ≤ 0.11 K (0.20°F)
(36) (–40 to +2192°F) (0.58°F)
Type N (NiCrSi- –40 to +1300°C ≤. 0.43 K 0.03% ≤ 0.16 K (0.29°F) 0.01%
NiSi) (37) (–40 to +2372°F) (0.77°F) ( ≙ 2μA)
Type R (PtRh13- 0 to +1768°C ≤ 1.92 K ≤ 0.76 K (1.37°F)
Pt) (38) (+32 to +3214°F) (3.46°F)
Type S (PtRh10- 0 to +1768°C ≤ 1.9 K ≤ 0.74 K (1.33°F)
Pt) (39) (+32 to +3214°F) (3.42°F)
Type T (Cu- –40 to +400°C ≤ 0.32 K ≤ 0.11 K (0.20°F)
CuNi) (40) (–40 to +752°F) (0.58°F)
IEC 60584, part 1; Type C (W5Re- 0 to +2000°C ≤ 0.86 K ≤ 0.33 K (0.59°F)
ASTM E988-96 W26Re) (32) (+32 to +3632°F) (1.55°F)
ASTM E988-96 Type D (W3Re- 0 to +2000°C ≤ 1.05 K ≤ 0.41 K (0.74°F)
W25Re) (33) (+32 to +3632°F) (1.89°F)
DIN 43710 Type L (Fe-CuNi) +50 to +900°C ≤ 0.26 K ≤ 0.07 K (0.13°F)
(41) (+122 to +1652°F) (0.47°F)
Type U (Cu- +50 to +600°C ≤ 0.24 K ≤ 0.10 K (0.18°F)
CuNi) (42) (+122 to +1112°F) (0.43°F)
GOST Type L (NiCr- –200 to +800°C ≤ 2.27 K ≤ 0.15 K (0.27°F)
R8.8585-2001 CuNi) (43) (–328 to +1472°F) (4.09°F)
Voltage Millivolt -20 to 100 mV 10 μV 4 μV
transmitters transmitter (mV)
a. Ranges over which stated Error and Repeatability apply. Input may be configured to wider range. See Table 11 for Configurable
Measuring Range Limits.
b. Using HART® transmitted measured value.
c. Percentage data refer to the configured span of the analog output signal.
d. Percentage data refer to the current range of the analog output signal (20 mA).
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 9
Sample Calculation
Table 5 shows a sample calculation with Pt100, measuring range 0 to +200°C (+32 to +392°F),
ambient temperature 25°C (77°F), supply voltage 24 V.
Table 5. Sample Calculation
Measured Error Digital 0.14 K (0.25°F)
Repeatability Digital 0.05 K (0.09°F)
Measured error D/A = 0.03% of 200 K (360°F) 0.06 K (0.108°F)
Repeatability D/A = 0.01% of 200 K (360°F) 0.02 K (0.036°F)
Measured error digital value (HART): 0.15 K (0.27°F)
√ (Measured error digital² + repeatability²)
Measured error analog value (current output): 0.16 K (0.29°F)
√ (Measured error digital² + repeatability²+ Measured error D/A²)
Ambient Temperature:
Thermocouples Effect (±) When Ambient Supply Voltage: Effect (±)
(TC) According Temperature Changes by When Supply Voltage Long Term Drift: Effect (±)
to Standard Designation 1°C (1.8 °F) Changes by 1 V Per Year
Digital (a) D/A (b) Digital (a) D/A (b) Digital (a) D/A (b)
IEC 60584, Type A ≤ 0.13 K (0.23°F) ≤ 0.13 K (0.23°F) ≤ 1.3 K (2.34°F)
part 1 (W5Re-
W20Re) (30)
Type B ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 1.7 K (3.06°F)
(PtRh30-
PtRh6) (31)
Type E (NiCr- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.2 K (0.36°F)
CuNi) (34)
Type J (Fe- ≤ 0.04 K (0.07°F) ≤ 0.04 K (0.07°F)
CuNi) (35)
Type K (NiCr- ≤ 0.04 K (0.07°F) ≤ 0.04 K (0.07°F) ≤ 0.3 K (0.54°F)
Ni) (36) 0.001% 0.001% 0.017%
Type N ≤ 0.4 K (0.72°F)
(NiCrSi-NiSi)
(37)
Type R ≤ 0.01 K (0.02°F) ≤ 0.05 K (0.09°F) ≤ 1.9 K (3.42°F)
(PtRh13-Pt)
(38)
Type S
(PtRh10-Pt)
(39)
Type T (Cu- ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 0.3 K (0.54°F)
CuNi) (40)
IEC 60584, part Type C ≤ 0.08 K (0.14°F) ≤ 0.08 K (0.14°F) ≤ 0.8 K (1.44°F)
1; (W5Re-
ASTM E988-96 W26Re) (32)
ASTM E988-96 Type D ≤ 1 K (1.8°F)
(W3Re-
W25Re) (33)
DIN 43710 Type L (Fe- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.2 K (0.36°F)
CuNi) (41)
Type U (Cu- ≤ 0.02 K (0.04°F) ≤ 0.02 K (0.04°F) ≤ 0.3 K (0.54°F)
CuNi) (42)
GOST Type L (NiCr- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.4 K (0.72°F)
R8.8585-2001 CuNi) (43)
Voltage Millivolt ≤ 3μV ≤ 3μV ≤ 10μV
transmitters transmitter
(mV)
a. Using HART® transmitted measured value.
b. Percentage data refer to the configured span of the analog output signal.
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 13
Sample Calculation
Table 9 shows a sample calculation with Pt100, measuring range 0 to +200 °C (+32 to +392 °F),
ambient temperature 35 °C (95 °F), supply voltage 30 V.
Table 9. Sample Calculation
Measured Error Digital 0.14 K (0.25°F)
Repeatability Digital 0.05 K (0.09°F)
Measured error D/A = 0.03% of 200 K (360°F) 0.06 K (0.108°F)
Repeatability D/A = 0.01% of 200 K (360°F) 0.02 K (0.036°F)
Influence of ambient temperature (digital), 0.02°C/K: 0.2 K (0.36°F)
(35°C - 25°C) x 0.02°C/K
Influence of ambient temperature (D/A), 0.001%/K: 0.02 K (0.036°F)
(35°C - 25°C) x (0.001% of 200°C)
Influence of supply voltage (digital), 0.02 K/V: 0.12 K (0.216°F)
(30 V - 24 V) x 0.02 K/V
Influence of supply voltage (D/A), 0.001%/V: 0.012 K (0.0216°F)
(30 V - 24 V) x (0.001% of 200°C)
Measured error digital value (HART): 0.28 K (0.50°F)
√ (Measured error digital² + repeatability² + influence of ambient temperature
(digital)² + influence of supply voltage (digital)²)
Measured error analog value (current output): 0.29 K (0.52°F)
√ (Measured error digital² + repeatability²+ influence of ambient temperature
(digital)² + influence of ambient temperature (D/A)² + influence of supply voltage
(digital)² + influence of supply voltage (D/A)²)
F U N C T I O N A L S P E C I F I C AT I O N S
Table 10. Input Types, Ranges, and Limits (RTD or Ω)
Resistance
Thermometer
(RTD) as Per Standard Designation a Measuring Range Limits Min Span
IEC 60751:2008 Pt100 (1) -200 to +850°C (–328 to +1562°F) 10 K (18°F)
Pt200 (2) 0.003851 -200 to +850°C (–328 to +1562°F)
Pt500 (3) -200 to +500°C (–328 to +932°F)
Pt1000 (4) -200 to +250°C (–328 to +482°F)
JIS C1604:1984 Pt100 (5) 0.003916 -200 to +510°C (–328 to +950°F) 10 K (18°F)
DIN 43760 IPTS-68 Ni100 (6) -60 to +250°C (–76 to +482°F) 10 K (18°F)
Ni120 (7) 0.006180 -60 to +250°C (–76 to +482°F)
GOST 6651-94 Pt50 (8) 0.003910 -185 to +1100°C (–301 to +2012°F) 10 K (18°F)
Pt100 (9) -200 to +850°C (–328 to +1562°F)
OIML R84: 2003, Cu50 (10) 0.004280 -180 to +200°C (–292 to +392°F) 10 K (18°F)
GOST 6651-2009 Cu100 (11) -180 to +200°C (–292 to +392°F)
Ni100 (12) 0.006170 -60 to +180°C (–76 to +356°F) 10 K (18°F)
Ni120 (13) -60 to +180°C (–76 to +356°F)
OIML R84: 2003, Cu50 (14) 0.004260 -50 to +200°C (–58 to +392°F) 10 K (18°F)
GOST 6651-94
Pt100 (Callendar- - The measuring range limits are 10 K (18°F)
– van Dusen) specified by entering the
limit values that depend on the
– Nickel Polynomial coefficients A to C and R0.
Copper Polynomial
Thermocou
ples (TC)
as Per Min
Standard Designation Configurable Measuring Range Limits Span
IEC 60584, Recommended temperature range: 50 K
Part 1 (90°F)
Type A (W5Re-W20Re)(30) 0 to +2500°C (+32 to +4532°F) 0 to +2500°C (+32 to +4532°F)
Type B (PtRh30-PtRh6)(31) +40 to +1820°C (+104 to +3308°F) +100 to +1500°C (+212 to +2732°F)
Type E (NiCr-CuNi) (34) –270 to +1000°C (–454 to +1832°F) 0 to +750°C (+32 to +1382°F)
Type J (Fe-CuNi) (35) –210 to +1200°C (–346 to +2192°F) +20 to +700°C (+68 to +1292°F)
Type K (NiCr-Ni) (36) –270 to +1372°C (–454 to +2501°F) 0 to +1 100°C (+32 to +2012°F)
Type N (NiCrSi-NiSi) (37) –270 to +1300°C (–454 to +2372°F) 0 to +1 100°C (+32 to +2012°F)
Type R (PtRh13-Pt) (38) –50 to +1768°C (–58 to +3214°F) 0 to +1 400°C (+32 to +2552°F)
Type S (PtRh10-Pt) (39) –50 to +1768°C (–58 to +3214°F) 0 to +1 400°C (+32 to +2552°F)
Type T (Cu-CuNi) (40) –260 to +400°C (–436 to +752°F) –185 to +350°C (–301 to +662°F)
IEC 60584, Type C (W5Re-W26Re) 0 to +2315°C (+32 to +4199°F) 0 to +2000°C (+32 to +3632°F) 50 K
Part 1; (32) (90°F)
ASTM
E988-96
ASTM Type D (W3Re-W25Re) 0 to +2315°C (+32 to +4199°F) 0 to +2000°C (+32 to +3632°F) 50 K
E988-96 (33) (90°F)
DIN 43710 Type L (Fe-CuNi) (41) –200 to +900°C (–328 to +1652°F) 0 to +750°C (+32 to +1382°F) 50 K
Type U (Cu-CuNi) (42) –200 to +600°C (–328 to +1112°F) –185 to +400°C (–301 to +752°F) (90°F)
GOST Type L (NiCr-CuNi) (43) Type L (NiCr-CuNi) (43) –200 to 0 to +750°C (+32 to +1382°F) 50 K
R8.8585- +800°C (–328 to +1472°F) (90°F)
2001
Internal cold junction (Pt100)
External cold junction: configurable value –40 to +85°C (–40 to +185°F)
Max. sensor resistance k10 kΩ (if sensor resistance is greater than 10 kΩ, an error message as per NAMUR
NE89 is output)
Voltage Millivolt Transmitter (mV) -20 to 100 mV 5 mV
Transmitter
(mV)
PSS 2A-1F8 A
Page 16 FUNCTIONAL SPECIFICATIONS
Sensor Input 1
RTD or Resistance
OK OK — OK
Transmitter, 2-Wire
RTD or Resistance
OK OK (a) — OK (a)
Transmitter, 3-Wire
Sensor Input 2
RTD or Resistance
— — — —
Transmitter, 4-Wire
Thermocouple (TC),
OK OK (a) OK (a) OK (a)
Voltage Transmitter
red red 7
red red 6
TC, mV
1
5
TC, mV
white 4
white white 3 2
Display connection
PSS 2A-1F8 A
FUNCTIONAL SPECIFICATIONS Page 17
Figure 3. Dual Compartment Housing Wiring from the Terminal Block to the Module
Purple
Blue 1
Red
Green
Yellow
Orange 2
Brown
Display connection
Characteristic Output
Analog Output 4 to 20 mA, 20 to 4 mA (can be inverted)
Signal Encoding FSK ± 0.5 mA via current signal
Data Transmission Rate 1200 baud
Galvanic Isolation U = 2 kV AC (input/output)
Linearization/Transmission Temperature-linear, resistance-linear, voltage-linear
Behavior
Network Frequency Filter 50/60 Hz
Filter 1st Order Digital Filter: 0 to 120 s
HART Version 7
Device Address in the Multi-Drop Software Setting Addresses 0 to 63
Mode (a)
Device Description Files (DD) Information and files are available
free of charge at:
www.hartcomm.org
Load (Communication Resistor) min. 250 Ω
a. Not possible in the SIL mode.
PSS 2A-1F8 A
Page 18 FUNCTIONAL SPECIFICATIONS
1098
VS - 8 Max. sensor resistance 10 kΩ (if sensor
RMAX = resistance is greater than 10 kΩ, an error
0.023
message as per NAMUR NE89 is output)
250
0 Ub
11 V 16.75 V 36.25 V 42 V
Supply Voltage (V dc)
NOTE
The transmitter will function with an output load less
than 250 Ω provided that a HART Communicator or
PC-based Configurator is not connected to it. Use of
a HART Communicator or PC-based Configurator
requires 250 Ω minimum load.
PSS 2A-1F8 A
FUNCTIONAL SPECIFICATIONS Page 19
Figure 5. HART 4 to 20 mA Output Block Diagram Figure 6. Typical W-Series and T-Series
(One Transmitter) Thermowells Shown
7
6 250 Ω MINIMUM
5 1 +
2
INDICATOR
+
4
POWER
3 + SUPPLY
RTT80
TRANSMITTER
+
HART
COMMUNICATOR,
CONTROLLER
OR PC-BASED
OR RECORDER
CONFIGURATOR
Thermowells
The thermowells listed in the Model Code are
popular selections for industrial use. In addition,
Invensys offers other high quality, polished
thermowells in a variety of configurations, materials,
and sizes. Most application requirements can be
met by choosing from the wide selection offered.
Specify Thermowell Code TX and see PSS 3-3C1 A
for Type W Thermowells, and PSS 3-3D1 A for Type
T Thermowells, or contact Invensys. See Figure 6 for
a small sample of thermowells available.
PSS 2A-1F8 A
PHYSICAL SPECIFICATIONS Page 21
P H Y S I C A L S P E C I F I C AT I O N S
Transmitter Housings
Explosion- Field Wiring
Housing Material and IEC/NEMA proof and Mounting Entrances on
Code Finish Rating Flameproof Configuration Housing
Basic Module
BB Encapsulated plastic IP20 (a) No Basic Transmitter Module (b) None
(DIN Form B package)
Universal Housing
LL Low copper aluminum IP66/67 Yes Universal housing with integral sensor 1/2 NPT (c)
alloy; epoxy coated NEMA 4X and thermowell
MM Stainless steel IP66/67 Yes Universal housing with integral sensor 1/2 NPT (c)
NEMA 4X and thermowell
SS Low copper aluminum IP66/67 Yes Universal housing for surface or pipe 1/2 NPT (c)
alloy; epoxy coated NEMA 4X mounting, remote sensor (d)
TT Stainless steel IP66/67 Yes Universal housing for surface or pipe 1/2 NPT (c)
NEMA 4X mounting, remote sensor (d)
WW Low copper aluminum IP66/67 Yes Universal housing with integral bare 1/2 NPT (c)
alloy; epoxy coated NEMA 4X sensor
YY Stainless steel IP66/67 Yes Universal housing with integral bare 1/2 NPT (c)
NEMA 4X sensor
Dual Compartment Housing
CC Low copper aluminum IP66/67 Yes Dual-compartment housing with M20
alloy; epoxy coated NEMA 4X integral bare sensor
DD Stainless steel IP66/67 Yes Dual-compartment housing with M20
NEMA 4X integral bare sensor
EE Low copper aluminum IP66/67 Yes Dual-compartment housing with M20
alloy; epoxy coated NEMA 4X integral sensor and thermowell
FF Stainless steel IP66/67 Yes Dual-compartment housing with M20
NEMA 4X integral sensor and thermowell
GG Low copper aluminum IP66/67 Yes Dual-compartment housing for surface M20
alloy; epoxy coated NEMA 4X or pipe mounting, remote sensor (d)
HH Stainless steel IP66/67 Yes Dual-compartment housing for surface M20
NEMA 4X or pipe mounting, remote sensor (d)
JJ Low copper aluminum IP66/67 Yes Dual-compartment housing with 1/2 NPT
alloy; epoxy coated NEMA 4X integral bare sensor
KK Stainless steel IP66/67 Yes Dual-compartment housing with 1/2 NPT
NEMA 4X integral bare sensor
NN Low copper aluminum IP66/67 Yes Dual-compartment housing with 1/2 NPT
alloy; epoxy coated NEMA 4X integral sensor and thermowell
PP Stainless steel IP66/67 Yes Dual-compartment housing with 1/2 NPT
NEMA 4X integral sensor and thermowell
PSS 2A-1F8 A
Page 22 PHYSICAL SPECIFICATIONS
Mounting Dimensions
The basic transmitter module can be mounted to a Refer to “DIMENSIONS – NOMINAL” on page 28
DIN rail using the optional mounting clip and self- and to the Dimensional Print DP 020-580.
tapping screw provided by Invensys. The basic
module can also be mounted to a surface using
user-supplied hardware. See “DIMENSIONS –
NOMINAL” on page 28.
The transmitter enclosed in the universal or dual
compartment housing (without integral sensors) can
be remote mounted to a surface or nominal DN 50 or
2-inch pipe using an optional mounting bracket.
PSS 2A-1F8 A
PHYSICAL SPECIFICATIONS Page 23
E L E C T R I C A L S A F E T Y S PE CI F I CAT I O N S
The transmitter has been designed to meet the Electrical Safety descriptions listed in the table below.
Contact Global Customer Support for information on status of testing laboratory approvals or certifications.
Refer to the Instruction Manual for application conditions and connectivity requirements.
Testing Laboratory, Type of Protection, and Area Classification Model Code Option
Non-hazardous area ZZ
CSA IS, I/1+2/ABCD CA
CSA NI, 1/2/ABCD CN
CSA Explosionproof, Class I, Division 1, BCD; CD
Dust-ignitionproof, Class II, Division 1, EFG, Class III, Division 1.
Also zone certified, Cl I, Zone 1, Ex d IIC (a)
ATEX II 1G Ex ia IIC T4/T5/T6 AA
ATEX II 2 G Ex d T6 Gb Ta = -40°C to 70°C AD
II 2 D Ex tb T85C Db (a)
IECEx Ex ia IIC T4/T5/T6 EA
IECEx Ex d T6 Gb Ta = -40°C to 70°C ED
Ex tb T85C Db (a)
FM IS, I/1+2/ABCD FA
FM NI, I/2/ABCD FN
FM Explosionproof, Class I, Division 1, Groups B, C, and D; FD
Dust-ignitionproof, Class II, Division 1, Groups E, F, and G,
Class III Division 1 (a)
a. Not available with the basic module (Housing and Sensor Mounting Code BB).
PSS 2A-1F8 A
MODEL CODE Page 25
M O D E L C OD E
Description Model
I/A Series Temperature Transmitter RTT80
Communications
4 to 20 mA with HART digital communications -T
Input/Output Configuration
Configured for Single Sensor Input 1
Configured for Dual Sensor Input – PV is Sensor 1 (a) 2
Configured for Dual Sensor Input – PV is average of Sensor 1 and Sensor 2 (a) 3
Configured for Dual Sensor Input – PV is difference between Sensor 1 and Sensor 2 (a) 4
Configured for Dual Sensor Input – Sensor 2 is hot backup for Sensor 1 (a) 5
Configured for Dual Sensor Input – PV is average with sensor backup (a) 6
Housing and Sensor Mounting
Basic Module for DIN Rail or Surface Mounting or Replacement BB
Dual compartment aluminum housing, 1/2 NPT conduit with sensor (b) JJ
Dual compartment ss housing, 1/2 NPT conduit with sensor (b) KK
Dual compartment aluminum housing, 1/2 NPT conduit with sensor and thermowell mounting (b) NN
Dual compartment ss housing, 1/2 NPT conduit with sensor and thermowell mounting (b) PP
Dual compartment aluminum housing, 1/2 NPT conduit for use with remote sensor (c) QQ
Dual compartment ss housing, 1/2 NPT conduit for use with remote sensor (c) RR
Dual compartment aluminum housing, M20 conduit with sensor (b) CC
Dual compartment ss housing, M20 conduit with sensor (b) DD
Dual compartment aluminum housing, M20 conduit with sensor and thermowell mounting (b) EE
Dual compartment ss housing, M20 conduit with sensor and thermowell mounting (b) FF
Dual compartment aluminum housing, M20 conduit for use with remote sensor (c) GG
Dual compartment ss housing, M20 conduit for use with remote sensor (c) HH
Universal aluminum housing for use with remote sensor (c) SS
Universal ss housing for use with remote sensor (c) TT
Universal aluminum housing with bare sensor (b) WW
Universal ss housing with bare sensor (b) YY
Universal aluminum housing with sensor and thermowell mounting (b) LL
Universal ss housing with sensor and thermowell mounting (b) MM
PSS 2A-1F8 A
Page 26 MODEL CODE
M O DE L C O D E ( C O N T I N U E D)
Description Model
Input Measurement Type (d)
Thermocouple, Type B (e) B
Thermocouple, Type C (e) C
Thermocouple, Type D (e) D
Thermocouple, Type E E
Thermocouple, Type J J
Thermocouple, Type K K
Thermocouple, Type L (e) L
Thermocouple, Type N N
Thermocouple, Type R (e) R
Thermocouple, Type S (e) S
Thermocouple, Type T T
Thermocouple, Type U (e) U
2-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) (e) 2
3-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) Q
4-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) (f) 4
3-wire RTD, 100 ohm platinum IEC 751 (ASTM-A High Accuracy) A
4-wire RTD, 100 ohm platinum IEC 751 (ASTM-A High Accuracy) (f) 6
3-wire RTD, 100 ohm nickel DIN 43760 (e) F
Ohms input P
Millivolt input M
3-wire RTD Platinum (Callendar-van Dusen) W
Other (factory configuration for an Input Measurement Type not listed above) (g) Z
Thermowell Assembled to Housing
No Thermowell or Thermowell is supplied separately (h) NA
Thermowell Series “T-” assembled to housing; specify child thermowell (i) TK
Thermowell Series “W-” assembled to housing; specify “W-” model code (j) TX
Hazardous Area Certifications (k)
Non-hazardous area ZZ
CSA IS, I/1+2/ABCD CA
CSA NI, 1/2/ABCD CN
CSA Explosionproof, Class I, Division 1, BCD; Dust-ignitionproof, Class II, Division 1, EFG, Class III, CD
Division 1. Also zone certified, CL I, Zone 1, EX d IIC (l)
ATEX II 1G Ex ia IIC T4/T5/T6 AA
ATEX II 2 G Ex d T6 Gb (l) AD
IECEx Ex ia IIC T4/T5/T6 (l) EA
IECEx Ex d T6 Gb (l) ED
FM IS, I/1+2/ABCD FA
FM NI, I/2/ABCD FN
FM Explosionproof, Class I, Division 1, Groups B, C, and D; Dust-ignitionproof, Class II, Division 1, FD
Groups E, F, and G, Class III Division 1 (l)
Optional Selections
Housing Features
Custody Transfer Lock and Seal (l) -A1
Metric M20 Conduit Adapter (1/2 NPT by M20x1.5) (m) -A3
Housing Connection to Thermowell
Stainless Steel Union and Fittings (n) -S3
PSS 2A-1F8 A
MODEL CODE Page 27
M O DE L C O D E ( C O N T I N U E D)
Description Model
Mounting Sets
Mounting Set for Universal Housing – Painted Steel (m) -M1
Mounting Set for Universal Housing – Stainless Steel (m) -M2
Mounting Set for Dual Compartment Housing – Painted Steel (o) -M3
Mounting Set for Dual Compartment Housing – Stainless Steel (o) -M4
Mounting Set for Dual Compartment Housing – Rugged Painted Steel (p) -M5
Mounting Set for Dual Compartment Housing – Rugged Stainless Steel (p) -M6
Clip for DIN rail mounting of the basic module -D1
Other Optional Features
SIL Certification (q) -S2
Custom Database Configuration -C2
Omit FoxDoc DVD-ROM -K1
With Local Indicator -L1
Cleaned and Prepared for Oxygen Service (l) -C5
Wake Frequency Calculations (r) -WF
NACE Compliant Thermowell (r) (s) -N1
a. Input measurement must be the same for both sensors. Dual 4-wire RTD is not permitted. Only Input 1 can be configured for 4-
wire RTD.
b. This option initiates the PRMTA configurable sensor model code. If you are ordering a PRMTA configurable sensor, be sure that
the RTT80 Input Measurement Type ordered matches the PRMTA Configurable Sensor Input Measurement Type.
c. Sensor ordered separately.
d. Transmitter is factory configured for the measurement type specified whether the sensor is included or not. You can change the
configuration to a different type using appropriate configuration software for the selected protocol, or specify -C2 Option for
custom factory configuration. On dual sensor input (Sensor Input = 2), both inputs are configured the same, unless specified via
the -C2 configuration form.
e. Only available with the basic module or a module for use with a remote sensor (Housing and Sensor Mounting Codes BB, QQ,
RR, GG, HH, SS, TT).
f. Only available with single sensor input (Input/Output Configuration Code 1).
g. This option requires selection of the Custom Database Configuration (Model Code Option -C2) under “Other Optional Features”.
h. This option is required for all housing options that are not configured for thermowells (Housing and Sensor Mounting Codes BB,
JJ, KK, QQ, RR, CC, DD, GG, HH, SS, TT, WW, and YY).
i. This option allows you to select a PRMTA configurable sensor with TT, TF, TS, or TW thermowell codes.
j. Refer to PSS 3-3C1 A for available W Series thermowells.
k. Transmitter has been designed to meet the Electrical Safety descriptions listed in this table. Contact Invensys for information and
status of testing laboratory approvals or certifications
l. Not available with the basic module (Housing and Sensor Mounting Code BB).
m. Only available with universal housings (Housing and Sensor Mounting Codes SS, TT, WW, YY, LL, MM).
n. Optionally available with aluminum housings configured for sensor and thermowell mounting (Housing and Sensor Mounting
Codes NN, EE, and LL). Standard on ss housings configured for sensor and thermowell mounting (Housing and Sensor Mounting
Codes PP, FF, and MM).
o. Only available with aluminum dual compartment housings (Housing and Sensor Mounting Codes CC, EE, GG, JJ, NN, QQ).
p. Required for ss dual compartment housings (Housing and Sensor Mounting Codes KK, PP, RR, and DD) if a mounting set is
desired. Also available with aluminum dual compartment housings (Housing and Sensor Mounting Codes JJ, NN, QQ, and CC)
if a mounting set is desired.
q. SIL available only with HART Communications option (-T).
r. Requires universal or dual compartment housings with sensor and thermowell mounting options (Housing and Sensor Mounting
Codes NN, PP, EE, FF, LL, or MM).
s. Only available with Thermowell Option Code TK (“T-” thermowell assembled to housing).
PSS 2A-1F8 A
Page 28 DIMENSIONS – NOMINAL
DIMENSIONS – NOMINAL
mm
in
BASIC TRANSMITTER
HOUSING CODE BB
33.0
1.3
44.0
1.7
45.40
1.79
24.1
0.9
mm
in
UNIVERSAL HOUSING FOR SURFACE OR PIPE MOUNT WITH REMOTE SENSOR
HOUSING CODES SS AND TT
DN 50 OR HOUSING CODES
2 in PIPE 72 SS = ALUMINUM
X 1/2 NPT TT = 316 ss
(BY USER) 2.8 NOTE 1
2 PLACES
DIMENSION X (NOTE 1)
WITHOUT WITH
INDICATOR INDICATOR
87 99
109 119 3.4 3.9
4.3 4.7
NOTES
1. ALLOW 51 mm (2 in)
CLEARANCE FOR
COVER REMOVAL.
NOTE 2 2. EXTERNAL COVER
SURFACE LOCK AND GROUND
100 SCREW WHEN
MOUNTING OR PIPE
MOUNTING 3.9 APPLICABLE.
SURFACE
BRACKET
A + 35
1.38
44
U
1.75
NOTE:
U + 115 A = ELEMENT INSERTION LENGTH
4.5 U = THERMOWELL INSERTION LENGTH
T = THERMOWELL LAGGING LENGTH
mm
in
DUAL COMPARTMENT HOUSING FOR SURFACE OR PIPE MOUNT WITH REMOTE SENSOR
HOUSING CODES GG, HH, QQ, AND RR
DN 50 OR 193
2 in PIPE 7.6 HOUSING CODES
(BY USER) GG = ALUMINUM M20 HOUSING FOR
REMOTE SENSOR
HH = 316 SS M20 HOUSING FOR
83
REMOTE SENSOR
3.3
QQ = ALUMINUM 1/2 NPT HOUSING FOR
REMOTE SENSOR
198 RR = 316 SS 1/2 NPT HOUSING FOR
7.8 REMOTE SENSOR
245
9.6
SURFACE NOTES
OR PIPE 1. ALLOW 51 mm (2 in) CLEARANCE FOR
MOUNTING MOUNTING
SURFACE COVER REMOVAL.
BRACKET
2. EXTERNAL COVER LOCK AND GROUND
SCREW WHEN APPLICABLE.
103
4.0
119
4.7
PSS 2A-1F8 A
DIMENSIONS – NOMINAL Page 31
mm
in
DUAL COMPARTMENT HOUSING WITH INTEGRAL SENSOR AND/OR SENSOR AND THERMOWELL
HOUSING CODES CC, DD, EE, FF, JJ, KK, NN, AND PP
SEE HOUSING
CODES GG, HH,
1/2 NPT QQ, AND RR ABOVE
BARE SENSOR FOR DIMENSIONS
A + 35
1.38 1/2 NPT OR M20
CONDUIT CONNECTION
(FOR ILLUSTRATION PURPOSES ONLY.
SENSOR AND THERMOWELL CONDUIT CONNECTIONS SHOULD
(SEE NOTES) NOT FACE DOWNWARD.)
44
U
1.75 NOTES:
A = ELEMENT INSERTION LENGTH
U + 115 U = THERMOWELL INSERTION LENGTH
4.5 T = THERMOWELL LAGGING LENGTH
O RD E RI N G I N S T R U C T I O N S
1. Model Number
2. Configured Range
3. Tag Number
www.fielddevices.foxboro.com