FIELD DEVICES – TEMPERATURE

Product Specifications

PSS 2A-1F8 A
Model RTT80 I/A Series® Temperature Transmitter with HART® 7
Communication Protocol and Optional SIL Certification

The Foxboro® brand Model RTT80 is a microprocessor-based temperature transmitter with HART®
Communication Protocol. It receives input signals from thermocouples, RTDs, ohm, or millivolt sources.

FEATURES
 Superior accuracy and long term stability from  Optional digital indicator.
microprocessor-based technology.  Available as a basic module that can mount to a
 Registration to HART Protocol Revision 7 surface or DIN rail, or in explosion-proof
(HART 7) digital communications is standard. universal or dual compartment housings for
 Available with or without SIL certification. remote mounting, and integral sensor and
thermowell mounting.
 One unit configurable for a variety of
Thermocouple (TC) and Resistance  Available with a wide selection of sensors and
Temperature Detector (RTD) inputs. thermowells.

 Supports 2-, 3-, or 4-wire RTDs.  Configurable failsafe mA value.

 Allows average or difference measurement.  Maximum/minimum temperature logging.

 Hot sensor backup - switches to the second  Conforms to applicable European Union
sensor if the primary sensor fails. Directives (product marked with “CE” logo).

 Temperature-dependent switching between  Electromagnetic compatibility in accordance


sensors used in different measuring ranges. with all relevant requirements of EN 61326 and
NAMUR NE21.
 Drift warning or alarm if the deviation between
sensor 1 and sensor 2 is less than or greater  Meets many testing agency requirements for
than a predefined limit value. hazardous area installations.

 Thermocouple cold junction compensation.  Standard two year warranty.

 Galvanic isolation 2 kV input to output.


 Rich on-board diagnostics.
PSS 2A-1F8 A
Page 2

GENERAL DESCRIPTION MULTIPLE PACKAGING CONFIGURATIONS


The RTT80 provides a wide range of packaging The transmitter is offered in a basic module package
selections, sensor types, and options along with or with universal or dual-compartment housing
HART communication protocol, thus making this selections.
transmitter suitable for most temperature
The DIN B size basic transmitter module is
measurement applications. The microprocessor-
intrinsically safe and is offered for replacement or
based electronics minimizes ambient temperature
spare parts purposes, for mounting to a surface, or
effects and results in high accuracy, repeatability,
for mounting to a DIN rail using the optional clip.
and linearization of the sensor signal. Ease of
Alternately, you can select a rugged universal
mounting and installation makes this transmitter an
housing for the RTT80, which accommodates the
extremely attractive offering.
electronics and terminations in a single
compartment, or a dual-compartment housing,
I/A Series INTELLIGENT TEMPERATURE which isolates and seals the wiring terminals from
TRANSMITTER FAMILY the electronics compartment. All three options
The RTT80 is part of the Foxboro intelligent provide built-in protection from vibration and RFI.
temperature transmitter family, which also includes
You can mount a transmitter with an integral sensor
Models RTT15 and RTT30. The RTT80 is also
(and thermowell, if desired) directly to the process.
offered with the FOUNDATION fieldbus™
Surface- and pipe-mounted configurations allow the
communication protocol; see PSS 2A-1F8 B.
transmitter to be mounted remotely from the
process. See Figure 1 for transmitter configurations.
SIL CERTIFICATION
Versions of the RTT80 are available both with and
without SIL certification per IEC 61508:2010. For the
SIL version, -S2 should be selected in the options
field of the model code. The SIL version can be
operated in either Normal mode or SIL mode.
SIL mode provides the following benefits:
 SIL 2/3 (hardware/software) Functional Safety
Assessment by TÜV Süd in accordance with
IEC 61508, ed. 2.0.
 Measuring points with one sensor or two
sensors up to SIL 2.
 Creation of two measuring points up to SIL 3
(requires 2 redundant RTT80s).
 Permanent self-monitoring.
 Permanent monitoring.
PSS 2A-1F8 A
Page 3

Figure 1. Available Housing and Sensor Mounting Codes

HOUSING AND SENSOR MOUNTING CODES


BASIC MODULE
CODE BB CODE BB CODE BB
BASIC MODULE SURFACE MOUNT DIN RAIL MOUNT

UNIVERSAL HOUSING
CODES SS AND TT CODES WW AND YY CODES LL AND MM
FOR SURFACE/PIPE MOUNTING WITH BARE SENSOR WITH SENSOR AND THERMOWELL

DUAL COMPARTMENT HOUSING


CODES GG, HH, QQ, RR CODES CC, DD, JJ, KK, CODES EE, FF, NN, PP
FOR SURFACE/PIPE MOUNTING WITH BARE SENSOR WITH SENSOR AND THERMOWELL
PSS 2A-1F8 A
Page 4

EFFICIENT AND DURABLE The RTT80 with HART communication is offered


with Device Descriptors (DDs), Emerson AMS™ file
Industrial-grade integrated circuits and sealed
and Field Device Tool DTM support.
electronics combine to make this microprocessor-
based transmitter an efficient and durable device.
RUGGED AND RELIABLE SENSORS
INPUT TYPES Foxboro supplied sensors are of high quality and
rugged construction, and provide maximum
The RTT80 is a configurable temperature field
accuracy and longevity. Sensors designed for use
transmitter with either one or two temperature
with thermowells include a spring loading
sensor inputs for 2-, 3-, and 4-wire resistance
mechanism that ensures continuous contact
temperature detectors (RTD), most popular
between the sensor tip and thermowell.
thermocouples (TC), and resistance and voltage
transmitters. The following is a general list of
transmitter input types:
GALVANIC ISOLATION
 Platinum RTDs, 2-, 3-, and 4-wire 2 kV ac Galvanic isolation is provided between input
 Nickel RTD, 3-wire and output.
 Thermocouples
 Millivolt OUT-OF-RANGE AND FAILURE CURRENT
 Ohm Low out-of-range and high out-of-range output
values are user configurable between 3.5 and
OUTPUT TYPES 23 mA. A configuration selection for NAMUR 43
RTT80 outputs include: (3.8 and 20.5 mA) is also provided.

 Single measurement or dual measurement The transmitter can also be configured for sensor
configured as average, difference, or redundant error detection. Output values are independently
measurements configurable between 3.5 and 23 mA for both
shorted and open sensor conditions. Configuration
 Hot sensor backup - transmitter switches to the
selections are also provided for direct selection of
second sensor if the primary sensor fails
NAMUR 43 low (3.5 mA) and NAMUR 43 high
 Temperature-dependent switching between (23 mA), both independently selectable for either
sensors that are used in different measuring shorted or open sensor conditions. Shorted sensor
ranges detection not applicable for thermocouples.
Output units can be configured for various
temperature units, ohms, or millivolts. TRANSMITTER DIAGNOSTICS
Standard available diagnostics include:
REMOTE COMMUNICATIONS  Ambient operating temperature out of range
Remote digital communication is provided with detection
HART communication protocol.  Internal electronics diagnostic error detection
Digital HART and 4 to 20 mA dc Protocol  Wiring error detection

4 to 20 mA with HART communications allows direct  Sensor cable open circuit or short circuit
analog connection to common receivers while still detection
providing full intelligent digital communications using  Corrosion detection in sensor connection cables
a HART Communicator or PC-based configurator.  Low supply voltage detection
 Measurement over range and under range
detection
OPERATING, TRANSPORTATION, AND STORAGE PSS 2A-1F8 A
CONDITIONS Page 5

OP E R AT I N G, T RA N S P ORTAT I O N , A N D S T O R A G E C O N D I T I O N S

Transportation and Storage Limits


Influence (a) Operative Limits (b) (c) (if different from Operative Limits)
Ambient Temperature (d)
Transmitter and optional -L1 display -40 and +85°C (-40 and +185°F) (b) -50 and +100°C (-40 and 212°F)
Relative Humidity (e) Condensation according to IEC
Transmitter and optional -L1 display 60068-2-33

Max. rel. humidity: 95% according to


IEC 60068-2-30
Climate Class Class C1 according to EN 60654-1
Altitude Up to 4000 m (13124 ft) above mean
sea level as per IEC 61010-1,
CAN/CSA C22.2 No. 61010-1
Ingress Protection IP 20
Measuring Category Category II as per IEC 61010-1. The
measuring category is provided for
measuring on power circuits that are
directly connected electrically with the
low-voltage network.
Degree of Contamination Pollution degree 2 as per IEC 61010-1.
Supply Voltage for HART (f) 11 and 42 V dc Not Applicable
Vibration 25 to 100 Hz for 4 “g” per GL guideline, 107 mm (42 in) drop in shipping
section 2, issue 3B, paragraph 9 and container
IEC 60068-2-27 and IEC 60068-2-6
Vibration: Housing and Sensor 19 mm (0.75 in) Double Amplitude
Mounting Codes CC, EE, GG, JJ, LL, from 5 to 9 Hz, 0 to 30 m/s2 (0 to 3 “g”)
NN, QQ, SS and WW from 9 to 500 Hz
Vibration: Housing and Sensor 10 m/s2 (1 “g”) maximum
Mounting Codes DD, FF, HH, KK, MM,
PP, RR, TT, and YY
a. Applies to Basic Transmitter Module only (Housing and Sensor Mounting Code BB) unless otherwise indicated.
b. SIL mode operation is limited to a high temperature of 70 C (158 F). Also refer to Electrical Safety Specifications section for a
restriction in ambient temperature with certain agency approvals/certifications.
c. Normal Operating Conditions and Operative Limits are defined per ANSI/ISA 51.1-1979 (R1993).
d. To ensure proper operation, the ambient temperature limits at the housing should not be exceeded. This is particularly relevant
when sensors/thermowells are directly connected to the housing and very high process temperatures are being measured. The
transfer of heat from the process to the housing can be minimized by use of thermowell extensions, or in extreme cases, by using
a remote housing installation.
e. When mounted in available housings with covers on.
f. Refer to Figure 4 for supply voltage vs. external loop load limitations graph.
PSS 2A-1F8 A
Page 6 ELECTROMAGNETIC COMPATIBILITY (EMC)

E L E CT RO M A G N E T I C C O M PAT I B I L I T Y ( E M C)
CE Compliance
Electromagnetic compatibility in accordance with all the relevant requirements of the EN 61326 series and
NAMUR Recommendation EMC (NE21). For details refer to the Declaration of Conformity. All tests were
passed both with and without ongoing digital HART® communication.
Table 1. Electromagnetic Compatibility (EMC) (a)
ESD (Electrostatic Charge) EN/IEC 61000-4-2 6 kV cont., 8 kV air
Electromagnetic Fields EN/IEC 61000-4-3 0.08 to 2.7 GHz 10 V/m
Burst (Fast Transients) EN/IEC 61000-4-4 2 kV
Surge (Surge Voltage) EN/IEC 61000-4-5 0.5 kV sym.
1 kV assym.
Conducted RF EN/IEC 61000-4-6 0.01 to 80 MHz 10 V
a. Maximum measured error < 1% of the measuring range.

P E R F O R M AN C E S PE CI F I C AT I O N S
In order to obtain the established values in °F, the results in °C must be multiplied by a factor of 1.8.

Response Time
The measured value update depends on the type of sensor and connection method and moves within the
ranges shown in Table 2.
Table 2. Response Time
Resistance Thermometer (RTD) 0.9 to 0.13 s (depends on the connection method 2/3/4-wire)
Thermocouples (TC) 0.8 s
Reference Temperature 0.9 s

When recording step responses, it must be


taken into account that the times for the
measurement of the second channel and the
internal reference measuring point are added to
the specified times where applicable.

Reference Conditions
 Calibration temperature: +25°C±3 K
(+77°F±5.4°F)
 Supply voltage: 24 V dc
 4-wire circuit for resistance adjustment
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 7

Maximum Measured Error and Repeatability


According to DIN EN 60770. The data Overall measured error of the device at current
concerning the various measured errors are output = digital measured error + measured
typical values and correspond to a standard error D/A. See Table 3 and Table 4.
deviation of ±2 s (Gaussian normal distribution).
Table 3. Maximum Measured Error and Repeatability (RTD or Ω)

Resistance
Thermometer (RTD)
According to Measuring Range
Standard Designation Limits Measured Error (±) Repeatability (±)
Digital (a) D/A (b) Digital (a) D/A (c)
IEC 60751:2008 Pt100 (1) ≤ 0.14 K ≤ 0.05 K (0.09°F)
–200 to +850°C (0.25°F)
Pt200 (2) (–328 to +1562°F) ≤ 0.86 K ≤ 0.13 K (0.23°F)
(1.55°F)
Pt500 (3) –200 to +500°C ≤ 0.30 K ≤ 0.08 K (0.14°F)
(–328 to +932°F) (0.54°F)
Pt1000 (4) –200 to +250°C ≤ 0.14 K ≤ 0.05 K (0.09°F)
(–328 to +482°F) (0.25°F)
JIS C1604:1984 Pt100 (5) –200 to +510°C ≤ 0.12 K ≤. 0.04 K (0.07°F)
(–328 to +950°F) (0.22°F)
DIN 43760 IPTS-68 Ni100 (6) ≤ 0.09 K ≤ 0.03 K (0.05°F)
–60 to +250°C (0.16°F) 0.03% 0.01%
Ni120 (7) (–76 to +482°F) ≤ 0.07 K ( ≙ 2 μA)
(0.13°F)
GOST Pt50 (8) –185 to +1100°C ≤ 0.30 K ≤ 0.05 K (0.09°F)
(–301 to +2012°F) (0.54°F)
Pt100 (9) –200 to +850 °C ≤ 0.14 K ≤ 0.07 K (0.13°F)
(–328 to +1562°F) (0.25°F)
OIML R84: 2003, Cu50 (10) –180 to +200°C ≤ 0.19 K ≤ 0.04 K (0.07°F)
GOST 6651-2009 (–292 to +392°F) (0.34°F)
Cu100 (11) –180 to +200°C ≤ 0.09 K ≤ 0.03 K (0.05°F)
(–292 to +392°F) (0.16°F)
Ni100 (12) –60 to +180°C ≤ 0.09 K ≤ 0.07 K (0.13°F)
(–76 to +356°F) (0.16°F)
Ni120 (13) –60 to +180°C
(–76 to +356°F)
OIML R84: 2003, Cu50 (14) –50 to +200°C ≤ 0.19 K 15 mΩ
GOST 6651-94 (–58 to +392°F) (0.34°F) ≤ 200 mΩ
Resistance Resistance Ω 10 to 400 Ω 40 Ω 15 mΩ
transmitters 10 to 2000 Ω 500 Ω ≤ 200 mΩ
a. Using HART® transmitted measured value.
b. Percentage data refer to the configured span of the analog output signal.
c. Percentage data refer to the current range of the analog output signal (20 mA).
PSS 2A-1F8 A
Page 8 PERFORMANCE SPECIFICATIONS

Table 4. Maximum Measured Error and Repeatability (TC or mV)

Thermocouples
(TC) According to Measuring Range
Standard Designation Limits (a) Measured Error (±) Repeatability (±)
Digital (b) D/A (c) Digital (b) D/A (d)
IEC 60584, part 1 Type A (W5Re- 0 to 2500 °C ≤ 1.62 K ≤ 0.52 K (0.94°F)
W20Re) (30) (+32 to + 4532°F) (2.92°F)
Type B (PtRh30- +500 to +1820°C ≤ 2.02 K ≤ 0.67 K (1.21°F)
PtRh6) (31) (+932 to +3308°F) (3.64°F)
Type E (NiCr- –40 to +1000°C ≤ 0.21 K ≤ 0.07 K (0.13°F)
CuNi) (34) (–40 to +1832°F) (0.38°F)
Type J (Fe-CuNi) –40 to +1200°C ≤ 0.26 K ≤ 0.08 K (0.14°F)
(35) (–40 to +2192°F) (0.47°F)
Type K (NiCr-Ni) –40 to +1200°C ≤ 0.32 K ≤ 0.11 K (0.20°F)
(36) (–40 to +2192°F) (0.58°F)
Type N (NiCrSi- –40 to +1300°C ≤. 0.43 K 0.03% ≤ 0.16 K (0.29°F) 0.01%
NiSi) (37) (–40 to +2372°F) (0.77°F) ( ≙ 2μA)
Type R (PtRh13- 0 to +1768°C ≤ 1.92 K ≤ 0.76 K (1.37°F)
Pt) (38) (+32 to +3214°F) (3.46°F)
Type S (PtRh10- 0 to +1768°C ≤ 1.9 K ≤ 0.74 K (1.33°F)
Pt) (39) (+32 to +3214°F) (3.42°F)
Type T (Cu- –40 to +400°C ≤ 0.32 K ≤ 0.11 K (0.20°F)
CuNi) (40) (–40 to +752°F) (0.58°F)
IEC 60584, part 1; Type C (W5Re- 0 to +2000°C ≤ 0.86 K ≤ 0.33 K (0.59°F)
ASTM E988-96 W26Re) (32) (+32 to +3632°F) (1.55°F)
ASTM E988-96 Type D (W3Re- 0 to +2000°C ≤ 1.05 K ≤ 0.41 K (0.74°F)
W25Re) (33) (+32 to +3632°F) (1.89°F)
DIN 43710 Type L (Fe-CuNi) +50 to +900°C ≤ 0.26 K ≤ 0.07 K (0.13°F)
(41) (+122 to +1652°F) (0.47°F)
Type U (Cu- +50 to +600°C ≤ 0.24 K ≤ 0.10 K (0.18°F)
CuNi) (42) (+122 to +1112°F) (0.43°F)
GOST Type L (NiCr- –200 to +800°C ≤ 2.27 K ≤ 0.15 K (0.27°F)
R8.8585-2001 CuNi) (43) (–328 to +1472°F) (4.09°F)
Voltage Millivolt -20 to 100 mV 10 μV 4 μV
transmitters transmitter (mV)
a. Ranges over which stated Error and Repeatability apply. Input may be configured to wider range. See Table 11 for Configurable
Measuring Range Limits.
b. Using HART® transmitted measured value.
c. Percentage data refer to the configured span of the analog output signal.
d. Percentage data refer to the current range of the analog output signal (20 mA).
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 9

Sample Calculation
Table 5 shows a sample calculation with Pt100, measuring range 0 to +200°C (+32 to +392°F),
ambient temperature 25°C (77°F), supply voltage 24 V.
Table 5. Sample Calculation
Measured Error Digital 0.14 K (0.25°F)
Repeatability Digital 0.05 K (0.09°F)
Measured error D/A = 0.03% of 200 K (360°F) 0.06 K (0.108°F)
Repeatability D/A = 0.01% of 200 K (360°F) 0.02 K (0.036°F)
Measured error digital value (HART): 0.15 K (0.27°F)
√ (Measured error digital² + repeatability²)
Measured error analog value (current output): 0.16 K (0.29°F)
√ (Measured error digital² + repeatability²+ Measured error D/A²)

Table 6. Physical Input Measuring Range of Sensors


10 to 400 Ω Cu50, Cu100, polynomial RTD, Pt50, Pt100, Ni100, Ni120
10 to 2000 Pt200, Pt500, Pt1000
–20 to 100 mV Thermocouples type: A, B, C, D, E, J, K, L, N, R, S, T, U

In the SIL mode, other measured errors are applied.


PSS 2A-1F8 A
Page 10 PERFORMANCE SPECIFICATIONS

Sensor Adjustment 1-point adjustment (offset)

Sensor Transmitter Matching Shifts the sensor value


2-point adjustment (sensor trimming)
RTD sensors are one of the most linear temperature
measuring elements. Nevertheless, the output must Correction (slope and offset) of the measured
be linearized. To significantly improve temperature sensor value at transmitter input
measurement accuracy, the device allows the use of
two methods: Content Output Adjustment
 Callendar-Van-Dusen coefficients (Pt100 Correction of the 4 or 20 mA current output value
resistance thermometer) (not possible in the SIL mode).
The Callendar-Van-Dusen equation is described
as: Operational Influences
RT = R0[1+AT+BT²+C(T-100)T³] The data concerning the various measured errors
The coefficients A, B and C are used to match are typical values and correspond to a standard
the sensor (platinum) and transmitter in order to deviation of ±2 s (Gaussian normal distribution).
improve the accuracy of the measuring system. Over-all measured error of the device at current
The coefficients for a standard sensor are output = digital measured error + measured error
specified in IEC 751. If no standard sensor is D/A. See Table 7.
available or if greater accuracy is required, the
Considered operational influences:
coefficients for each sensor can be determined
specifically with the aid of sensor calibration. -Long term drift
 Linearization for copper/nickel resistance -Influence of ambient temperature
thermometers (RTD)
-Influence of the supply voltage
The polynomial equation for copper/nickel is as
follows:
RT = R0(1+AT+BT²)
The coefficients A and B are used for the
linearization of nickel or copper resistance
thermometers (RTD). The exact values of the
coefficients derive from the calibration data and
are specific to each sensor. The sensor-specific
coefficients are then sent to the transmitter.
Sensor transmitter matching using one of the
methods explained above significantly improves the
temperature measurement accuracy of the entire
system. This is because the transmitter uses the
specific data pertaining to the connected sensor to
calculate the measured temperature, instead of
using the standardized sensor curve data.
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 11

Table 7. Operational Influences (RTD or Ω)

Resistance Ambient Temperature:


Thermometer Effect (±) When Ambient Supply Voltage: Effect (±)
(RTD) According Temperature Changes by When Supply Voltage Long Term Drift: Effect (±)
to Standard Designation 1°C (1.8 °F) Changes by 1 V Per Year
2-, 3-, 4-wire RTD Digital (a) D/A (b) Digital (a) D/A (b) Digital (a) D/A (b)
IEC 60751:2008 Pt100 (1) ≤ 0.02 K (0.04 ≤ 0.02 K (0.04°F) ≤ 0.16 K (0.29°F)
°F)
Pt200 (2) ≤ 0.03 K (0.05 °F ≤ 0.03 K (0.05°F) ≤ 0.5 K (0.9°F)
Pt500 (3) ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 0.2 K (0.36°F)
Pt100 (4) ≤ 0.1 K (0.18°F)
JIS C1604:1984 Pt100 (5) ≤ 0.14 K (0.25°F)
DIN 43760 IPTS- Ni100 (6) ≤ 0.1 K (0.18°F)
68 Ni120 (7)
0.001% 0.001% 0.017%
GOST 6651-94 Pt50 (8) ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.4 K (0.72°F)
Pt100 (9) ≤ 0.02 K (0.04°F) ≤ 0.02 K (0.04°F) ≤ 0.16 K (0.29°F)
OIML R84: 2003, Cu 50 (10) ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 0.23 K (0.41°F)
GOST 6651-2009 Cu100 (11) ≤ 0.12 K (0.22°F)
Ni100 (12) ≤ 0.12 K (0.22°F)
Ni120 (13) ≤ 0.09 K (0.16°F)
OIML R84: 2003, Cu50 (14) ≤ 0.23 K (0.41°F)
GOST 6651-94
Resistance 10 to 400 Ω ≤ 6 mΩ ≤ 6 mΩ 48 mΩ
transmitters 10 to 2000 Ω ≤ 30 mΩ ≤ 30 mΩ 290 mΩ
a. Using HART® transmitted measured value.
b. Percentage data refer to the configured span of the analog output signal.
PSS 2A-1F8 A
Page 12 PERFORMANCE SPECIFICATIONS

Table 8. Operational Influences (TC or mV)

Ambient Temperature:
Thermocouples Effect (±) When Ambient Supply Voltage: Effect (±)
(TC) According Temperature Changes by When Supply Voltage Long Term Drift: Effect (±)
to Standard Designation 1°C (1.8 °F) Changes by 1 V Per Year
Digital (a) D/A (b) Digital (a) D/A (b) Digital (a) D/A (b)
IEC 60584, Type A ≤ 0.13 K (0.23°F) ≤ 0.13 K (0.23°F) ≤ 1.3 K (2.34°F)
part 1 (W5Re-
W20Re) (30)
Type B ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 1.7 K (3.06°F)
(PtRh30-
PtRh6) (31)
Type E (NiCr- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.2 K (0.36°F)
CuNi) (34)
Type J (Fe- ≤ 0.04 K (0.07°F) ≤ 0.04 K (0.07°F)
CuNi) (35)
Type K (NiCr- ≤ 0.04 K (0.07°F) ≤ 0.04 K (0.07°F) ≤ 0.3 K (0.54°F)
Ni) (36) 0.001% 0.001% 0.017%
Type N ≤ 0.4 K (0.72°F)
(NiCrSi-NiSi)
(37)
Type R ≤ 0.01 K (0.02°F) ≤ 0.05 K (0.09°F) ≤ 1.9 K (3.42°F)
(PtRh13-Pt)
(38)
Type S
(PtRh10-Pt)
(39)
Type T (Cu- ≤ 0.01 K (0.02°F) ≤ 0.01 K (0.02°F) ≤ 0.3 K (0.54°F)
CuNi) (40)
IEC 60584, part Type C ≤ 0.08 K (0.14°F) ≤ 0.08 K (0.14°F) ≤ 0.8 K (1.44°F)
1; (W5Re-
ASTM E988-96 W26Re) (32)
ASTM E988-96 Type D ≤ 1 K (1.8°F)
(W3Re-
W25Re) (33)
DIN 43710 Type L (Fe- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.2 K (0.36°F)
CuNi) (41)
Type U (Cu- ≤ 0.02 K (0.04°F) ≤ 0.02 K (0.04°F) ≤ 0.3 K (0.54°F)
CuNi) (42)
GOST Type L (NiCr- ≤ 0.03 K (0.05°F) ≤ 0.03 K (0.05°F) ≤ 0.4 K (0.72°F)
R8.8585-2001 CuNi) (43)
Voltage Millivolt ≤ 3μV ≤ 3μV ≤ 10μV
transmitters transmitter
(mV)
a. Using HART® transmitted measured value.
b. Percentage data refer to the configured span of the analog output signal.
PSS 2A-1F8 A
PERFORMANCE SPECIFICATIONS Page 13

Sample Calculation
Table 9 shows a sample calculation with Pt100, measuring range 0 to +200 °C (+32 to +392 °F),
ambient temperature 35 °C (95 °F), supply voltage 30 V.
Table 9. Sample Calculation
Measured Error Digital 0.14 K (0.25°F)
Repeatability Digital 0.05 K (0.09°F)
Measured error D/A = 0.03% of 200 K (360°F) 0.06 K (0.108°F)
Repeatability D/A = 0.01% of 200 K (360°F) 0.02 K (0.036°F)
Influence of ambient temperature (digital), 0.02°C/K: 0.2 K (0.36°F)
(35°C - 25°C) x 0.02°C/K
Influence of ambient temperature (D/A), 0.001%/K: 0.02 K (0.036°F)
(35°C - 25°C) x (0.001% of 200°C)
Influence of supply voltage (digital), 0.02 K/V: 0.12 K (0.216°F)
(30 V - 24 V) x 0.02 K/V
Influence of supply voltage (D/A), 0.001%/V: 0.012 K (0.0216°F)
(30 V - 24 V) x (0.001% of 200°C)
Measured error digital value (HART): 0.28 K (0.50°F)
√ (Measured error digital² + repeatability² + influence of ambient temperature
(digital)² + influence of supply voltage (digital)²)
Measured error analog value (current output): 0.29 K (0.52°F)
√ (Measured error digital² + repeatability²+ influence of ambient temperature
(digital)² + influence of ambient temperature (D/A)² + influence of supply voltage
(digital)² + influence of supply voltage (D/A)²)

Influence of the Reference Junction (Internal Cold Junction)


Pt100 DIN IEC 60751 Cl. B (internal cold junction with thermocouples TC).
PSS 2A-1F8 A
Page 14 FUNCTIONAL SPECIFICATIONS

F U N C T I O N A L S P E C I F I C AT I O N S
Table 10. Input Types, Ranges, and Limits (RTD or Ω)

Resistance
Thermometer
(RTD) as Per Standard Designation a Measuring Range Limits Min Span
IEC 60751:2008 Pt100 (1) -200 to +850°C (–328 to +1562°F) 10 K (18°F)
Pt200 (2) 0.003851 -200 to +850°C (–328 to +1562°F)
Pt500 (3) -200 to +500°C (–328 to +932°F)
Pt1000 (4) -200 to +250°C (–328 to +482°F)
JIS C1604:1984 Pt100 (5) 0.003916 -200 to +510°C (–328 to +950°F) 10 K (18°F)
DIN 43760 IPTS-68 Ni100 (6) -60 to +250°C (–76 to +482°F) 10 K (18°F)
Ni120 (7) 0.006180 -60 to +250°C (–76 to +482°F)
GOST 6651-94 Pt50 (8) 0.003910 -185 to +1100°C (–301 to +2012°F) 10 K (18°F)
Pt100 (9) -200 to +850°C (–328 to +1562°F)
OIML R84: 2003, Cu50 (10) 0.004280 -180 to +200°C (–292 to +392°F) 10 K (18°F)
GOST 6651-2009 Cu100 (11) -180 to +200°C (–292 to +392°F)
Ni100 (12) 0.006170 -60 to +180°C (–76 to +356°F) 10 K (18°F)
Ni120 (13) -60 to +180°C (–76 to +356°F)
OIML R84: 2003, Cu50 (14) 0.004260 -50 to +200°C (–58 to +392°F) 10 K (18°F)
GOST 6651-94
Pt100 (Callendar- - The measuring range limits are 10 K (18°F)
– van Dusen) specified by entering the
limit values that depend on the
– Nickel Polynomial coefficients A to C and R0.

Copper Polynomial

Type of connection: 2-wire, 3-wire or 4-wire connection, sensor current: ≤ 0.3 mA


With 2-wire circuit, compensation of wire resistance possible (0 to 30 Ω)
With 3-wire and 4-wire connection, sensor wire resistance up to max. 50 Ω per wire
Resistance Transmitter Resistance Ω 10 and 400 Ω 10 Ω
10 and 2000 Ω 10 Ω
PSS 2A-1F8 A
FUNCTIONAL SPECIFICATIONS Page 15

Table 11. Input Types, Ranges, and Limits (TC or mV)

Thermocou
ples (TC)
as Per Min
Standard Designation Configurable Measuring Range Limits Span
IEC 60584, Recommended temperature range: 50 K
Part 1 (90°F)
Type A (W5Re-W20Re)(30) 0 to +2500°C (+32 to +4532°F) 0 to +2500°C (+32 to +4532°F)
Type B (PtRh30-PtRh6)(31) +40 to +1820°C (+104 to +3308°F) +100 to +1500°C (+212 to +2732°F)
Type E (NiCr-CuNi) (34) –270 to +1000°C (–454 to +1832°F) 0 to +750°C (+32 to +1382°F)
Type J (Fe-CuNi) (35) –210 to +1200°C (–346 to +2192°F) +20 to +700°C (+68 to +1292°F)
Type K (NiCr-Ni) (36) –270 to +1372°C (–454 to +2501°F) 0 to +1 100°C (+32 to +2012°F)
Type N (NiCrSi-NiSi) (37) –270 to +1300°C (–454 to +2372°F) 0 to +1 100°C (+32 to +2012°F)
Type R (PtRh13-Pt) (38) –50 to +1768°C (–58 to +3214°F) 0 to +1 400°C (+32 to +2552°F)
Type S (PtRh10-Pt) (39) –50 to +1768°C (–58 to +3214°F) 0 to +1 400°C (+32 to +2552°F)
Type T (Cu-CuNi) (40) –260 to +400°C (–436 to +752°F) –185 to +350°C (–301 to +662°F)
IEC 60584, Type C (W5Re-W26Re) 0 to +2315°C (+32 to +4199°F) 0 to +2000°C (+32 to +3632°F) 50 K
Part 1; (32) (90°F)
ASTM
E988-96
ASTM Type D (W3Re-W25Re) 0 to +2315°C (+32 to +4199°F) 0 to +2000°C (+32 to +3632°F) 50 K
E988-96 (33) (90°F)

DIN 43710 Type L (Fe-CuNi) (41) –200 to +900°C (–328 to +1652°F) 0 to +750°C (+32 to +1382°F) 50 K
Type U (Cu-CuNi) (42) –200 to +600°C (–328 to +1112°F) –185 to +400°C (–301 to +752°F) (90°F)
GOST Type L (NiCr-CuNi) (43) Type L (NiCr-CuNi) (43) –200 to 0 to +750°C (+32 to +1382°F) 50 K
R8.8585- +800°C (–328 to +1472°F) (90°F)
2001
Internal cold junction (Pt100)
External cold junction: configurable value –40 to +85°C (–40 to +185°F)
Max. sensor resistance k10 kΩ (if sensor resistance is greater than 10 kΩ, an error message as per NAMUR
NE89 is output)
Voltage Millivolt Transmitter (mV) -20 to 100 mV 5 mV
Transmitter
(mV)
PSS 2A-1F8 A
Page 16 FUNCTIONAL SPECIFICATIONS

Table 12. Input Wiring Types

Sensor Input 1

RTD or RTD or RTD or


Resistance Resistance Resistance Thermocouple
Transmitter, Transmitter, Transmitter, (TC), Voltage
2-wire 3-wire 4-wire Transmitter

RTD or Resistance
OK OK — OK
Transmitter, 2-Wire

RTD or Resistance
OK OK (a) — OK (a)
Transmitter, 3-Wire
Sensor Input 2
RTD or Resistance
— — — —
Transmitter, 4-Wire

Thermocouple (TC),
OK OK (a) OK (a) OK (a)
Voltage Transmitter

a. Wiring types are permitted in SIL mode.

Figure 2. Input Connections – Basic Transmitter and Universal Housing

Sensor Input 2 Sensor Input 1 Bus connection


RTD, Ω: 3- and 2-wire RTD, Ω: 4-, 3- and 2-wire and supply voltage

red red 7

red red 6
TC, mV
1
5
TC, mV

white 4

white white 3 2

Display connection
PSS 2A-1F8 A
FUNCTIONAL SPECIFICATIONS Page 17

Figure 3. Dual Compartment Housing Wiring from the Terminal Block to the Module

Purple
Blue 1
Red
Green

Yellow
Orange 2
Brown
Display connection

Table 13. Output Signal

Characteristic Output
Analog Output 4 to 20 mA, 20 to 4 mA (can be inverted)
Signal Encoding FSK ± 0.5 mA via current signal
Data Transmission Rate 1200 baud
Galvanic Isolation U = 2 kV AC (input/output)
Linearization/Transmission Temperature-linear, resistance-linear, voltage-linear
Behavior
Network Frequency Filter 50/60 Hz
Filter 1st Order Digital Filter: 0 to 120 s

HART Protocol Data


Protocol-Specific Data

HART Version 7
Device Address in the Multi-Drop Software Setting Addresses 0 to 63
Mode (a)
Device Description Files (DD) Information and files are available
free of charge at:
www.hartcomm.org
Load (Communication Resistor) min. 250 Ω
a. Not possible in the SIL mode.
PSS 2A-1F8 A
Page 18 FUNCTIONAL SPECIFICATIONS

Write Protection for Device Parameters


Hardware: Write protection for head transmitter Sensor Types
on optional display using DIP switch
Though all of the sensors listed under Input Types in
Software: Write protection using password Table 4 are supported, the following sensors can be
Switch-On Delay ordered factory-mounted to the transmitter housing
(see PSS 3-3e1 a).
– Until start of HART communication,
approximately 10 s), with switch-on delay = – Thermocouple, Type E
Ia≤ 3.8 mA. – Thermocouple, Type J
– Until the first valid measured value signal is – Thermocouple, Type K
present at the current output, approximately – Thermocouple, Type N
28 s, with switch-on delay = Ia≤ 3.8 mA.
– Thermocouple, Type T
Supply Voltage Requirements and External Loop – 3-wire RTD, 100 ohm platinum IEC 751
Load Limitations (ASTM-B standard accuracy)
HART 4 to 20 mA Output with a Superimposed – 4-wire RTD, 100 ohm platinum IEC 751
Digital Signal (ASTM-B standard accuracy)
– 3-wire RTD, 100 ohm platinum IEC 751
Nominal Supply Voltage:
(ASTM-A high accuracy)
 Normal mode: 11 - 42 V dc
– 4-wire RTD, 100 ohm platinum IEC 751
 SIL mode: 11 - 32 V dc
(ASTM-A high accuracy)
See Figure 4 for a plot of supply voltage vs
– 3-wire RTD, Callendar-van Dusen
output load.
Figure 4. HART 4 to 20 mA Output Supply Voltage vs. Thermocouple Cold Junction Compensation
Output Load  Internal cold junction (Pt100)
 External cold junction: configurable value –
1348
40 to +85°C (–40 to +185°F)
Output Load, Ohms

1098
VS - 8  Max. sensor resistance 10 kΩ (if sensor
RMAX = resistance is greater than 10 kΩ, an error
0.023
message as per NAMUR NE89 is output)
250
0 Ub
11 V 16.75 V 36.25 V 42 V
Supply Voltage (V dc)

NOTE
The transmitter will function with an output load less
than 250 Ω provided that a HART Communicator or
PC-based Configurator is not connected to it. Use of
a HART Communicator or PC-based Configurator
requires 250 Ω minimum load.
PSS 2A-1F8 A
FUNCTIONAL SPECIFICATIONS Page 19

Sensor/Transmitter Matching NOTE


RTD sensors are one of the most linear When the factory-mounted Callendar-van Dusen
sensor option is ordered with the RTT80,
temperature measuring elements.
coefficients will be configured in the transmitter at
Nevertheless, the output must be linearized.
the factory.
To significantly improve temperature
measurement accuracy, the device allows Multidrop Mode (Fixed Current)
the use of two methods:
This mode supports communications with up to
– Callendar-Van-Dusen coefficients (Pt100 15 transmitters on a single pair of signal/power
resistance thermometer) wires. The output signal is updated 4 times per
The Callendar-Van-Dusen equation is second. A minimum loop load of 250 ohms is
described as: required.
RT = R0[1+AT+BT²+C(T-100)T³]
Table 14. HART Communication Parameters
The coefficients A, B and C are used to HART
match the sensor (platinum) and transmitter
in order to improve the accuracy of the Parameter Analog Mode Multidrop Mode
measuring system. The coefficients for a Remote HART Communicator
standard sensor are specified in IEC 751. If Configurator or PC-based Configurator
no standard sensor is available or if greater Communication 1200 baud 1200 baud
accuracy is required, the coefficients for Rate
each sensor can be determined specifically Communication 3050 m (10 000 ft) 1525 m (5000 ft)
with the aid of sensor calibration. Distance (Rated)
– Linearization for copper/nickel resistance
thermometers (RTD)
The polynomial equation for copper/nickel is
as follows:
RT = R0(1+AT+BT²)
The coefficients A and B are used for the
linearization of nickel or copper resistance
thermometers (RTD). The exact values of
the coefficients derive from the calibration
data and are specific to each sensor. The
sensor-specific coefficients are then sent to
the transmitter.
Sensor transmitter matching using one of
the methods explained above significantly
improves the temperature measurement
accuracy of the entire system. This is
because the transmitter uses the specific
data pertaining to the connected sensor to
calculate the measured temperature,
instead of using the standardized sensor
curve data.
PSS 2A-1F8 A
Page 20 FUNCTIONAL SPECIFICATIONS

Figure 5. HART 4 to 20 mA Output Block Diagram Figure 6. Typical W-Series and T-Series
(One Transmitter) Thermowells Shown
7
6 250 Ω MINIMUM
5 1 +
2
INDICATOR
+
4
POWER
3 + SUPPLY
RTT80
TRANSMITTER

+
HART
COMMUNICATOR,
CONTROLLER
OR PC-BASED
OR RECORDER
CONFIGURATOR

Thermowells
The thermowells listed in the Model Code are
popular selections for industrial use. In addition,
Invensys offers other high quality, polished
thermowells in a variety of configurations, materials,
and sizes. Most application requirements can be
met by choosing from the wide selection offered.
Specify Thermowell Code TX and see PSS 3-3C1 A
for Type W Thermowells, and PSS 3-3D1 A for Type
T Thermowells, or contact Invensys. See Figure 6 for
a small sample of thermowells available.
PSS 2A-1F8 A
PHYSICAL SPECIFICATIONS Page 21

P H Y S I C A L S P E C I F I C AT I O N S
Transmitter Housings
Explosion- Field Wiring
Housing Material and IEC/NEMA proof and Mounting Entrances on
Code Finish Rating Flameproof Configuration Housing

Basic Module
BB Encapsulated plastic IP20 (a) No Basic Transmitter Module (b) None
(DIN Form B package)
Universal Housing
LL Low copper aluminum IP66/67 Yes Universal housing with integral sensor 1/2 NPT (c)
alloy; epoxy coated NEMA 4X and thermowell
MM Stainless steel IP66/67 Yes Universal housing with integral sensor 1/2 NPT (c)
NEMA 4X and thermowell
SS Low copper aluminum IP66/67 Yes Universal housing for surface or pipe 1/2 NPT (c)
alloy; epoxy coated NEMA 4X mounting, remote sensor (d)
TT Stainless steel IP66/67 Yes Universal housing for surface or pipe 1/2 NPT (c)
NEMA 4X mounting, remote sensor (d)
WW Low copper aluminum IP66/67 Yes Universal housing with integral bare 1/2 NPT (c)
alloy; epoxy coated NEMA 4X sensor
YY Stainless steel IP66/67 Yes Universal housing with integral bare 1/2 NPT (c)
NEMA 4X sensor
Dual Compartment Housing
CC Low copper aluminum IP66/67 Yes Dual-compartment housing with M20
alloy; epoxy coated NEMA 4X integral bare sensor
DD Stainless steel IP66/67 Yes Dual-compartment housing with M20
NEMA 4X integral bare sensor
EE Low copper aluminum IP66/67 Yes Dual-compartment housing with M20
alloy; epoxy coated NEMA 4X integral sensor and thermowell
FF Stainless steel IP66/67 Yes Dual-compartment housing with M20
NEMA 4X integral sensor and thermowell
GG Low copper aluminum IP66/67 Yes Dual-compartment housing for surface M20
alloy; epoxy coated NEMA 4X or pipe mounting, remote sensor (d)
HH Stainless steel IP66/67 Yes Dual-compartment housing for surface M20
NEMA 4X or pipe mounting, remote sensor (d)
JJ Low copper aluminum IP66/67 Yes Dual-compartment housing with 1/2 NPT
alloy; epoxy coated NEMA 4X integral bare sensor
KK Stainless steel IP66/67 Yes Dual-compartment housing with 1/2 NPT
NEMA 4X integral bare sensor
NN Low copper aluminum IP66/67 Yes Dual-compartment housing with 1/2 NPT
alloy; epoxy coated NEMA 4X integral sensor and thermowell
PP Stainless steel IP66/67 Yes Dual-compartment housing with 1/2 NPT
NEMA 4X integral sensor and thermowell
PSS 2A-1F8 A
Page 22 PHYSICAL SPECIFICATIONS

Transmitter Housings (Continued)


Explosion- Field Wiring
Housing Material and IEC/NEMA proof and Mounting Entrances on
Code Finish Rating Flameproof Configuration Housing
QQ Low copper aluminum IP66/67 Yes Dual-compartment housing for surface 1/2 NPT
alloy; epoxy coated NEMA 4X or pipe mounting, remote sensor (d)
RR Stainless steel IP66/67 Yes Dual-compartment housing for surface 1/2 NPT
NEMA 4X or pipe mounting, remote sensor (d)
a. The basic module, although encapsulated, has exposed terminals not protected from the environment.
b. The basic module is typically used for replacement and spares purposes; it can also be mounted to a surface or to a DIN rail using a
clip (Option -D1).
c. Optional conduit threads available; see Model Code.
d. Surface or pipe mounted using mounting set options -M1 or -M2.

Mounting Dimensions
The basic transmitter module can be mounted to a Refer to “DIMENSIONS – NOMINAL” on page 28
DIN rail using the optional mounting clip and self- and to the Dimensional Print DP 020-580.
tapping screw provided by Invensys. The basic
module can also be mounted to a surface using
user-supplied hardware. See “DIMENSIONS –
NOMINAL” on page 28.
The transmitter enclosed in the universal or dual
compartment housing (without integral sensors) can
be remote mounted to a surface or nominal DN 50 or
2-inch pipe using an optional mounting bracket.
PSS 2A-1F8 A
PHYSICAL SPECIFICATIONS Page 23

Approximate Transmitter Mass


Approximate Mass
Direct or Standard With Optional Display
Housing Housing Remote
Codes Material Mounting kg lb kg lb

Basic Transmitter Module


BB N/A N/A 0.05 0.11 0.01 0.02
Universal Housing
LL (a) Aluminum Direct
WW (b) 1.4 3.1 1.4 3.1
SS (c) Remote
MM (a) 316 ss Direct
YY (b) 3.2 7.1 3.2 7.1
TT (c) Remote
Dual Compartment Housing
EE and NN (a) Aluminum Direct
1.3 2.8 1.3 2.8
CC and JJ (b)
GG and QQ (c) Remote 1.3 2.8 1.3 2.9
FF and PP (a) 316 ss Direct
2.9 6.4 2.9 6.5
DD and KK (b)
HH and RR (c) Remote 2.9 6.5 3.0 6.6
a. Includes module, but sensor and thermowell mass and connecting hardware not included.
b. Includes module, but bare sensor mass and connecting hardware not included.
c. Surface or pipe mount housing; remote sensor.
PSS 2A-1F8 A
Page 24 ELECTRICAL SAFETY SPECIFICATIONS

E L E C T R I C A L S A F E T Y S PE CI F I CAT I O N S
The transmitter has been designed to meet the Electrical Safety descriptions listed in the table below.
Contact Global Customer Support for information on status of testing laboratory approvals or certifications.
Refer to the Instruction Manual for application conditions and connectivity requirements.
Testing Laboratory, Type of Protection, and Area Classification Model Code Option
Non-hazardous area ZZ
CSA IS, I/1+2/ABCD CA
CSA NI, 1/2/ABCD CN
CSA Explosionproof, Class I, Division 1, BCD; CD
Dust-ignitionproof, Class II, Division 1, EFG, Class III, Division 1.
Also zone certified, Cl I, Zone 1, Ex d IIC (a)
ATEX II 1G Ex ia IIC T4/T5/T6 AA
ATEX II 2 G Ex d T6 Gb Ta = -40°C to 70°C AD
II 2 D Ex tb T85C Db (a)
IECEx Ex ia IIC T4/T5/T6 EA
IECEx Ex d T6 Gb Ta = -40°C to 70°C ED
Ex tb T85C Db (a)
FM IS, I/1+2/ABCD FA
FM NI, I/2/ABCD FN
FM Explosionproof, Class I, Division 1, Groups B, C, and D; FD
Dust-ignitionproof, Class II, Division 1, Groups E, F, and G,
Class III Division 1 (a)
a. Not available with the basic module (Housing and Sensor Mounting Code BB).
PSS 2A-1F8 A
MODEL CODE Page 25

M O D E L C OD E
Description Model
I/A Series Temperature Transmitter RTT80
Communications
4 to 20 mA with HART digital communications -T
Input/Output Configuration
Configured for Single Sensor Input 1
Configured for Dual Sensor Input – PV is Sensor 1 (a) 2
Configured for Dual Sensor Input – PV is average of Sensor 1 and Sensor 2 (a) 3
Configured for Dual Sensor Input – PV is difference between Sensor 1 and Sensor 2 (a) 4
Configured for Dual Sensor Input – Sensor 2 is hot backup for Sensor 1 (a) 5
Configured for Dual Sensor Input – PV is average with sensor backup (a) 6
Housing and Sensor Mounting
Basic Module for DIN Rail or Surface Mounting or Replacement BB
Dual compartment aluminum housing, 1/2 NPT conduit with sensor (b) JJ
Dual compartment ss housing, 1/2 NPT conduit with sensor (b) KK
Dual compartment aluminum housing, 1/2 NPT conduit with sensor and thermowell mounting (b) NN
Dual compartment ss housing, 1/2 NPT conduit with sensor and thermowell mounting (b) PP
Dual compartment aluminum housing, 1/2 NPT conduit for use with remote sensor (c) QQ
Dual compartment ss housing, 1/2 NPT conduit for use with remote sensor (c) RR
Dual compartment aluminum housing, M20 conduit with sensor (b) CC
Dual compartment ss housing, M20 conduit with sensor (b) DD
Dual compartment aluminum housing, M20 conduit with sensor and thermowell mounting (b) EE
Dual compartment ss housing, M20 conduit with sensor and thermowell mounting (b) FF
Dual compartment aluminum housing, M20 conduit for use with remote sensor (c) GG
Dual compartment ss housing, M20 conduit for use with remote sensor (c) HH
Universal aluminum housing for use with remote sensor (c) SS
Universal ss housing for use with remote sensor (c) TT
Universal aluminum housing with bare sensor (b) WW
Universal ss housing with bare sensor (b) YY
Universal aluminum housing with sensor and thermowell mounting (b) LL
Universal ss housing with sensor and thermowell mounting (b) MM
PSS 2A-1F8 A
Page 26 MODEL CODE

M O DE L C O D E ( C O N T I N U E D)
Description Model
Input Measurement Type (d)
Thermocouple, Type B (e) B
Thermocouple, Type C (e) C
Thermocouple, Type D (e) D
Thermocouple, Type E E
Thermocouple, Type J J
Thermocouple, Type K K
Thermocouple, Type L (e) L
Thermocouple, Type N N
Thermocouple, Type R (e) R
Thermocouple, Type S (e) S
Thermocouple, Type T T
Thermocouple, Type U (e) U
2-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) (e) 2
3-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) Q
4-wire RTD, 100 ohm platinum IEC 751 (ASTM-B Standard Accuracy) (f) 4
3-wire RTD, 100 ohm platinum IEC 751 (ASTM-A High Accuracy) A
4-wire RTD, 100 ohm platinum IEC 751 (ASTM-A High Accuracy) (f) 6
3-wire RTD, 100 ohm nickel DIN 43760 (e) F
Ohms input P
Millivolt input M
3-wire RTD Platinum (Callendar-van Dusen) W
Other (factory configuration for an Input Measurement Type not listed above) (g) Z
Thermowell Assembled to Housing
No Thermowell or Thermowell is supplied separately (h) NA
Thermowell Series “T-” assembled to housing; specify child thermowell (i) TK
Thermowell Series “W-” assembled to housing; specify “W-” model code (j) TX
Hazardous Area Certifications (k)
Non-hazardous area ZZ
CSA IS, I/1+2/ABCD CA
CSA NI, 1/2/ABCD CN
CSA Explosionproof, Class I, Division 1, BCD; Dust-ignitionproof, Class II, Division 1, EFG, Class III, CD
Division 1. Also zone certified, CL I, Zone 1, EX d IIC (l)
ATEX II 1G Ex ia IIC T4/T5/T6 AA
ATEX II 2 G Ex d T6 Gb (l) AD
IECEx Ex ia IIC T4/T5/T6 (l) EA
IECEx Ex d T6 Gb (l) ED
FM IS, I/1+2/ABCD FA
FM NI, I/2/ABCD FN
FM Explosionproof, Class I, Division 1, Groups B, C, and D; Dust-ignitionproof, Class II, Division 1, FD
Groups E, F, and G, Class III Division 1 (l)
Optional Selections
Housing Features
Custody Transfer Lock and Seal (l) -A1
Metric M20 Conduit Adapter (1/2 NPT by M20x1.5) (m) -A3
Housing Connection to Thermowell
Stainless Steel Union and Fittings (n) -S3
PSS 2A-1F8 A
MODEL CODE Page 27

M O DE L C O D E ( C O N T I N U E D)
Description Model
Mounting Sets
Mounting Set for Universal Housing – Painted Steel (m) -M1
Mounting Set for Universal Housing – Stainless Steel (m) -M2
Mounting Set for Dual Compartment Housing – Painted Steel (o) -M3
Mounting Set for Dual Compartment Housing – Stainless Steel (o) -M4
Mounting Set for Dual Compartment Housing – Rugged Painted Steel (p) -M5
Mounting Set for Dual Compartment Housing – Rugged Stainless Steel (p) -M6
Clip for DIN rail mounting of the basic module -D1
Other Optional Features
SIL Certification (q) -S2
Custom Database Configuration -C2
Omit FoxDoc DVD-ROM -K1
With Local Indicator -L1
Cleaned and Prepared for Oxygen Service (l) -C5
Wake Frequency Calculations (r) -WF
NACE Compliant Thermowell (r) (s) -N1
a. Input measurement must be the same for both sensors. Dual 4-wire RTD is not permitted. Only Input 1 can be configured for 4-
wire RTD.
b. This option initiates the PRMTA configurable sensor model code. If you are ordering a PRMTA configurable sensor, be sure that
the RTT80 Input Measurement Type ordered matches the PRMTA Configurable Sensor Input Measurement Type.
c. Sensor ordered separately.
d. Transmitter is factory configured for the measurement type specified whether the sensor is included or not. You can change the
configuration to a different type using appropriate configuration software for the selected protocol, or specify -C2 Option for
custom factory configuration. On dual sensor input (Sensor Input = 2), both inputs are configured the same, unless specified via
the -C2 configuration form.
e. Only available with the basic module or a module for use with a remote sensor (Housing and Sensor Mounting Codes BB, QQ,
RR, GG, HH, SS, TT).
f. Only available with single sensor input (Input/Output Configuration Code 1).
g. This option requires selection of the Custom Database Configuration (Model Code Option -C2) under “Other Optional Features”.
h. This option is required for all housing options that are not configured for thermowells (Housing and Sensor Mounting Codes BB,
JJ, KK, QQ, RR, CC, DD, GG, HH, SS, TT, WW, and YY).
i. This option allows you to select a PRMTA configurable sensor with TT, TF, TS, or TW thermowell codes.
j. Refer to PSS 3-3C1 A for available W Series thermowells.
k. Transmitter has been designed to meet the Electrical Safety descriptions listed in this table. Contact Invensys for information and
status of testing laboratory approvals or certifications
l. Not available with the basic module (Housing and Sensor Mounting Code BB).
m. Only available with universal housings (Housing and Sensor Mounting Codes SS, TT, WW, YY, LL, MM).
n. Optionally available with aluminum housings configured for sensor and thermowell mounting (Housing and Sensor Mounting
Codes NN, EE, and LL). Standard on ss housings configured for sensor and thermowell mounting (Housing and Sensor Mounting
Codes PP, FF, and MM).
o. Only available with aluminum dual compartment housings (Housing and Sensor Mounting Codes CC, EE, GG, JJ, NN, QQ).
p. Required for ss dual compartment housings (Housing and Sensor Mounting Codes KK, PP, RR, and DD) if a mounting set is
desired. Also available with aluminum dual compartment housings (Housing and Sensor Mounting Codes JJ, NN, QQ, and CC)
if a mounting set is desired.
q. SIL available only with HART Communications option (-T).
r. Requires universal or dual compartment housings with sensor and thermowell mounting options (Housing and Sensor Mounting
Codes NN, PP, EE, FF, LL, or MM).
s. Only available with Thermowell Option Code TK (“T-” thermowell assembled to housing).
PSS 2A-1F8 A
Page 28 DIMENSIONS – NOMINAL

DIMENSIONS – NOMINAL

mm
in
BASIC TRANSMITTER
HOUSING CODE BB

33.0
1.3

44.0
1.7

45.40
1.79

24.1
0.9

WITHOUT LCD INDICATOR WITH LCD INDICATOR


PSS 2A-1F8 A
DIMENSIONS – NOMINAL Page 29

mm
in
UNIVERSAL HOUSING FOR SURFACE OR PIPE MOUNT WITH REMOTE SENSOR
HOUSING CODES SS AND TT

DN 50 OR HOUSING CODES
2 in PIPE 72 SS = ALUMINUM
X 1/2 NPT TT = 316 ss
(BY USER) 2.8 NOTE 1
2 PLACES
DIMENSION X (NOTE 1)
WITHOUT WITH
INDICATOR INDICATOR
87 99
109 119 3.4 3.9
4.3 4.7
NOTES
1. ALLOW 51 mm (2 in)
CLEARANCE FOR
COVER REMOVAL.
NOTE 2 2. EXTERNAL COVER
SURFACE LOCK AND GROUND
100 SCREW WHEN
MOUNTING OR PIPE
MOUNTING 3.9 APPLICABLE.
SURFACE
BRACKET

UNIVERSAL HOUSING WITH INTEGRAL SENSOR AND/OR SENSOR AND THERMOWELL


HOUSING CODES LL, MM, WW, AND YY

1/2 NPT SEE HOUSING


BARE SENSOR CODES SS AND TT
ABOVE FOR
DIMENSIONS
A

A + 35
1.38

1/2 NPT CONDUIT


SENSOR AND THERMOWELL CONNECTION
(SEE NOTE)

44
U
1.75
NOTE:
U + 115 A = ELEMENT INSERTION LENGTH
4.5 U = THERMOWELL INSERTION LENGTH
T = THERMOWELL LAGGING LENGTH

SENSOR AND THERMOWELL HOUSING CODES


WITH LAGGING
LL = ALUMINUM HOUSING WITH
(SEE NOTE)
SENSOR AND THERMOWELL
44
U T MM = 316 SS HOUSING WITH
1.75
SENSOR AND THERMOWELL
WW = ALUMINUM HOUSING WITH BARE SENSOR
U + T + 115 YY = 316 SS HOUSING WITH BARE SENSOR
4.5
PSS 2A-1F8 A
Page 30 DIMENSIONS – NOMINAL

mm
in
DUAL COMPARTMENT HOUSING FOR SURFACE OR PIPE MOUNT WITH REMOTE SENSOR
HOUSING CODES GG, HH, QQ, AND RR

DN 50 OR 193
2 in PIPE 7.6 HOUSING CODES
(BY USER) GG = ALUMINUM M20 HOUSING FOR
REMOTE SENSOR
HH = 316 SS M20 HOUSING FOR
83
REMOTE SENSOR
3.3
QQ = ALUMINUM 1/2 NPT HOUSING FOR
REMOTE SENSOR
198 RR = 316 SS 1/2 NPT HOUSING FOR
7.8 REMOTE SENSOR

245
9.6
SURFACE NOTES
OR PIPE 1. ALLOW 51 mm (2 in) CLEARANCE FOR
MOUNTING MOUNTING
SURFACE COVER REMOVAL.
BRACKET
2. EXTERNAL COVER LOCK AND GROUND
SCREW WHEN APPLICABLE.

103
4.0
119
4.7
PSS 2A-1F8 A
DIMENSIONS – NOMINAL Page 31

mm
in
DUAL COMPARTMENT HOUSING WITH INTEGRAL SENSOR AND/OR SENSOR AND THERMOWELL
HOUSING CODES CC, DD, EE, FF, JJ, KK, NN, AND PP
SEE HOUSING
CODES GG, HH,
1/2 NPT QQ, AND RR ABOVE
BARE SENSOR FOR DIMENSIONS

A + 35
1.38 1/2 NPT OR M20
CONDUIT CONNECTION
(FOR ILLUSTRATION PURPOSES ONLY.
SENSOR AND THERMOWELL CONDUIT CONNECTIONS SHOULD
(SEE NOTES) NOT FACE DOWNWARD.)

44
U
1.75 NOTES:
A = ELEMENT INSERTION LENGTH
U + 115 U = THERMOWELL INSERTION LENGTH
4.5 T = THERMOWELL LAGGING LENGTH

SENSOR AND THERMOWELL


WITH LAGGING
(SEE NOTES)
HOUSING CODES
44 CC = ALUMINUM M20 HOUSING
U T
1.75 WITH BARE SENSOR
DD = 316 SS M20 HOUSING
U + T + 115 WITH BARE SENSOR
4.5 EE = ALUMINUM M20 HOUSING WITH
SENSOR AND THERMOWELL
FF = 316 SS M20 HOUSING WITH
SENSOR AND THERMOWELL
JJ = ALUMINUM 1/2 NPT HOUSING
WITH BARE SENSOR
KK = 316 SS 1/2 NPT HOUSING
WITH BARE SENSOR
NN = ALUMINUM 1/2 NPT HOUSING
WITH SENSOR AND THERMOWELL
PP = 316 SS 1/2 NPT HOUSING
WITH SENSOR AND THERMOWELL
PSS 2A-1F8 A
Page 32

O RD E RI N G I N S T R U C T I O N S
1. Model Number
2. Configured Range
3. Tag Number

OTHER FOXBORO PRODUCTS


The Foxboro product lines offer a broad range of measurement
and instrument products, including solutions for pressure, flow,
analytical, temperature, positioning, controlling, and recording.
For a list of these offerings, visit our web site at:

www.fielddevices.foxboro.com

Invensys Systems, Inc. Copyright 2012-2014 Invensys Systems, Inc.


10900 Equity Drive All rights reserved.
Houston, TX 77041
United States of America Invensys, Foxboro, and I/A Series are trademarks of
http://www.invensys.com Invensys Limited, its subsidiaries, and affiliates. All
other trademarks are the property of their
respective owners.
Global Customer Support
Inside U.S.: 1-866-746-6477 Invensys is now part of Schneider Electric.
Outside U.S.:1-508-549-2424
Website: http://support.ips.invensys.com 1114

You might also like