SM KBF (E2.1) 12-2013 - en
SM KBF (E2.1) 12-2013 - en
SM KBF (E2.1) 12-2013 - en
Service Manual
Imprint
Manufacturer:
BINDER GmbH
The reproduction, distribution and utilization of this document as well as the communication of its content to
others without explicit authorization are prohibited. Offenders will be held liable for the payment of damages.
All rights reserved in the event of the grant of a patent, utility model or design.
BINDER GmbH, 2007
Table of contents
1 Preface ........................................................................................................................... 6
1.1 General guidelines .......................................................................................................... 6
1.2 Syntax ............................................................................................................................. 6
1.3 Safety instructions structure ............................................................................................ 7
2 Safety instructions ........................................................................................................ 9
2.1 Qualification of service personnel .................................................................................... 9
2.2 Dangers ........................................................................................................................ 10
3 Preparation of service tasks ....................................................................................... 12
4 Maintenance ................................................................................................................ 13
5 Troubleshooting .......................................................................................................... 17
5.1 General electrical faults ................................................................................................. 18
5.2 Faults of the heating system .......................................................................................... 20
5.3 Faults of the cooling system .......................................................................................... 21
5.4 Faults of the humidity system ........................................................................................ 22
6 Check for electrical safety .......................................................................................... 25
7 Repair work at the housing......................................................................................... 26
7.1 Replacing the housing cover at the front and the air shielding plate .............................. 26
7.2 Replacing the rear panels.............................................................................................. 28
8 Repair work at the housing door ................................................................................ 29
8.1 Testing of closeness between housing door and sealing ............................................... 29
8.2 Adjusting the housing door ............................................................................................ 29
8.3 Replacing the instrument box ........................................................................................ 31
8.4 Replacing the power switch (-1S1 ) or light switch (-9S1 ) ............................................. 33
8.5 Opening the interior side of the housing door ................................................................ 34
8.6 Replacing the door switch (-7S1 ).................................................................................. 36
8.7 Replacing the closing device of the housing door .......................................................... 37
8.8 Testing and replacing door with the heating cable (-3E2 ).............................................. 39
8.9 Replacing the housing door ........................................................................................... 41
9 Repair work at the inner chamber .............................................................................. 43
9.1 Replacing the door sealing ............................................................................................ 43
9.2 Replacing the glass doors and the catches ................................................................... 44
9.3 Replacing the fan (-3M1, -3M2 ) .................................................................................... 45
9.4 Replacing the Pt100 temperature sensor (-2B1, -2B2) .................................................. 47
9.5 Replacing the humidity sensor incl. circuit board ........................................................... 50
9.6 Replacing the inner chamber ......................................................................................... 52
9.7 Testing and replacing of the heater (-3E1… -3E3 ) ........................................................ 54
10 Repair work at electric und electronic ....................................................................... 57
10.1 Replacing the miniature fuse (-1F1) .............................................................................. 57
10.2 Replacing the power cord .............................................................................................. 58
10.3 Replacing the suppressor capacitor (-1Z1) .................................................................... 59
10.4 Replacing the temperature fuse (-1F2) .......................................................................... 60
10.5 Pulling the electric mounting plate out of the machine room .......................................... 62
10.6 Components of the electric mounting plate .................................................................... 64
10.7 Replacing the contactor (-4K2) ...................................................................................... 65
10.8 Replacing a solid state relay (-3K1, -4K1, -6K1, -6K2) ................................................... 66
10.9 Replacing the controller (-2N1, -2N2 ) ........................................................................... 67
1 Preface
1.1 General guidelines
This service manual describes the maintenance, the trouble shooting, the repair, the calibration
and the adjustment of the KBF 115, 240 and 720 with MB1 controller and humidity control board.
Sections only concerning units with options according to the BINDER pricelist are indicated.
The figures in this service manual almost show the service work at the KBF 115. The service work
of the KBF 240 and 720 is to perform analogical. In particular cases additional figures of a KBF 240
or 720 are given.
The repair of the cooling system must only be performed by service personnel having specialized
training as cooling technician and special tools must be available.
This service manual is aimed at service personnel who should maintain, repair, calibrate and adjust
a KBF.
References about the required qualification of the service personnel can be found in chap. 2.1
on page 9.
Before starting the service work at a KBF compare order and serial number of the unit with the
validity note on the front page of this service manual.
The service manual of the KBF will be updated if necessary.
Always use the latest version of the service manual.
In case of doubt about the validity of this service manual contact the Binder Service Hotline (see
Imprint).
Wiring diagrams and refrigeration cycles are published separately. The actual documents can be
ordered at the Binder Service Hotline.
All information about initial operation, normal operation, cleaning, alarm and error messages of the
KBF with controller MB1 can be found in the relevant operating manual.
1.2 Syntax
Syntax Meaning
Dangers are indicated, according to the severity and likelihood of their consequences, by a word to
attract attention, with the associated warning color and any appropriate safety symbol.
DANGER!
Indicates an imminently hazardous situation that, if not avoided, will result in
death or serious (irreversible) injury.
WARNING!
Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious (irreversible) injury.
CAUTION!
Indicates a potentially hazardous situation which, if not avoided, may result in
moderate or minor (reversible) injury.
CAUTION!
Indicates a potentially hazardous situation which, if not avoided, may result in damage of
the product and/or its functions or of a property in its ambiance.
Danger of injury!
Follow all the directions indicated by the safety symbol in order to avoid injury
or death.
Important information
2 Safety instructions
2.1 Qualification of service personnel
WARNING!
If the KBF is maintained or repaired incorrectly, there is a risk of malfunction
which could cause harm to human beings and material damage to the
equipment and samples.
CAUTION!
If the KBF is calibrated or adjusted incorrectly, there is a risk of malfunction which could
cause material damage to the samples and false test results.
To be able to carry out the service work the enforcing personnel must be qualified and familiar with
the service and the operation of the KBF.
2.2 Dangers
DANGER!
Danger of electric shock.
Danger to life.
The unit must be switched off prior to performing most of the service tasks
described below.
Disconnect the unit from the facility-side power supply to make sure that it
can not be switched on again by mistake!
If the service task requires that the unit be switched on, a second person
must be called in to switch off the unit in the case of an emergency!
DANGER!
Danger of electric shock.
Danger to life.
The unit must not be operated if the check for electrical safety fails.
The check for electrical safety has to be done during the recommended
annual maintenance work.
The check for electrical safety has to be done after every repair.
WARNING!
Contamination of the device with toxic, infectious or radioactive
substances.
Danger of intoxication.
Danger of infection.
Never service a unit with sticking toxic or radioactive substances or
sources of infection.
Never service a unit before the form “Contamination clearance certificate -
Declaration of harmlessness with regard to safety and health” is
completely filled out.
Prior to any service tasks, let the unit free from any sticking toxic or
radioactive substances or sources of infection by the operating staff.
Prior to any service tasks, a person in charge of the operating staff must fill
out the form “Contamination clearance certificate - Declaration of
harmlessness with regard to safety and health”.
CAUTION!
CAUTION!
Danger of burnings by hot surfaces and water!
The unit must be cooled down prior to performing of the service tasks of
the inner chamber, the interior side of the housing door, the heater and the
humidity system.
CAUTION!
CAUTION!
CAUTION!
Danger of damaging the electronic!
The instrument box must only be opened at a workstation which is equipped with all
necessary protective measures against electrostatic discharge.
Circuit boards might be damaged by electrostatic discharges, penetrating particles like
dust and touching of its components.
CAUTION!
Danger of mechanical damages!
Never let mechanical components hang at electric cables.
Electric cables are not appropriate to hold bigger components and will be damaged if
you do so.
Climatic chambers series KBF are designed for exact conditioning of harmless materials
(see chap. “Intended use” of the operating manual).
Nevertheless due to the use by the operating company it might be possible that the unit is
contaminated with toxic, infectious or radioactive substances inside and outside of the inner
chamber.
For the safety of the service personnel prior to any service tasks the unit must be freed from
any sticking toxic or radioactive substances or sources of infection by the operating staff.
Prior to any service tasks, a person in charge of the operating staff must fill out the form
“Contamination clearance certificate - Declaration of harmlessness with regard to safety and
health”.
The form can be found in chap. “Contamination clearance certificate” of the operating manual
or can be ordered at the Binder Service Hotline.
4 Maintenance
DANGER!
Danger of electric shock.
Danger to life.
The unit must not be operated if the check for electrical safety fails.
The check for electrical safety has to be done during the recommended
annual maintenance work.
The check for electrical safety has to be done after every repair.
All mechanical and electrical parts of the KBF should be visually checked, tested and maintained
by service personnel annually.
The recommended maintenance work is described in Table 1.
Table 1: Recommended annual maintenance work
Inner chamber
Door sealing Check the door sealing for wear, tight fit and damages
If necessary, replace the door sealing (chap. 9.1, page 43)
Glass door, Check the glass door, the door hinges and the catches for damages
catches Check the strength of the adhesion between the glass door and the
hinges resp. the handle
Check the adjustment of the glass door
Check the smooth-running of the glass door
If necessary, adjust the glass door and the catches (chap. 9.2,
page 44)
If necessary, replace the glass door (chap. 9.2, page 44)
Fan(-3M1, -3M2) Check the fan(s) for damages, corrosion, function and noise emission
If necessary, replace the fan (chap. 9.3, page 45)
Humidity sensor (KBF 115/240: Check the humidity sensor for fouling
-2B2 ; KBF 720: -2B3 ) If necessary, replace the filter cap of the humidity sensor
Inner chamber Check the sheet metal components of the inner chamber for
mechanical damages and corrosion
If necessary, replace the damaged sheet metal components
(chap. 9.6, page 52)
Machine room
Machine room Check the machine room for fouling, mechanical damages and
corrosion
If necessary, clean the machine room from dust and similar impurities
If necessary, check by what mechanical damages and corrosion are
caused and eliminate the causes
Electric and electronic
Power plug Check the power plug and the power cord for damages
Power cord If necessary, replace the power cord with the power plug
(chap. 10.2, page 58)
I/O-switch of humidity system Check the function of the I/O-switch
(-6S1) If necessary, replace the I/O-switch (chap. 11.1 page 69)
Electric mounting plate Check the electric mounting plate for fouling, mechanical damages
and corrosion
Check the tight fit of the components of the electric mounting plate
Check the cables being connected to the components of the electric
mounting plate for sufficient fixing and damages
If necessary, clean the electric mounting plate and its components
from dust and similar impurities
If necessary, replace components of the electric mounting plate
(chap. 10.6 ff., page 64)
Fix lose cables and replace damaged cables
Electric and electronic Check the electric and electronic components in the machine room for
components in the machine room tight fit, fouling, mechanical damages and corrosion
Check the cables being connected to the electric and electronic
components in the machine room for sufficient fixing and damages
If necessary, replace electric and electronic components in the
machine room (chap. 10, page 57)
Fix lose cables and replace damaged cables
Controller
Controller display Check the function of the controller display by entering different
menus (see operating manual)
If necessary, replace the controller (chap. 10.9, page 67)
Set point setting Key in several set points for temperature and humidity and check if
the unit starts approaching this values(see operating manual)
Execute a troubleshooting, if the unit does not start approaching the
set points (chap. 5, page 17)
Temperature control Calibrate the temperature control (chap. 14, page 89)
If necessary, adjust the temperature control (chap. 14, page 89)
If necessary, replace the Pt100 temperature sensor (chap. 9.4,
page 47)
Humidity control Calibrate the humidity control (chap. 14, page 89)
If necessary, adjust the humidity control (chap. 14, page 89)
If necessary, replace the humidity sensor (chap. 9.5, page 50)
5 Troubleshooting
Alarm and error messages as well as basic measures the operator himself may
take to clear them are described in the KBF operating manual.
Please make sure these measures have been tried before looking further for
any other possible error causes.
Error pattern
No
Faults should be found by replacing components of the unit. Usually that will be the fastest method
of troubleshooting.
The sequence of the columns describing potential causes for errors, and the remedial actions to
clear the described error patterns, is mainly intended to facilitate basic error diagnosis and
clearance.
So it is recommended to work your way from top to bottom of the diagrams.
Notations between brackets and in italics, e.g. (-1S1), behind a component refer to the respective
equipment codes for this component, as specified in the wiring diagram, and in labels on some
parts inside the apparatus.
No
Power plug (-X1) connected? Connect power plug
Yes
No
Power switch (-1S1) set to ON? Set power switch to ON
Yes
No
Facility-side power supply available? Ensure facility-side power supply
Yes
No
Plug of the cable from the No Connect plug of the cable from the controller
controller display (-2N1) connected to the display (-2N1) at the controller I/O-board
controller I/O-board (-2N2)? (-2N2) (chap. 10.9, page 67)
Yes
Controller I/O-board (-2N2) and/or controller Replace controller I/O-board (-2N2) and/or
display (-2N1) defective. controller display (-2N1) (chap. 10.9, page 67)
No
Solid state relay (-3K1) defective? Yes Replace solid state relay (-3K1)
(chap. 10.8, page 66)
No
Does the housing door fit close? No Adjusting the housing door
(chap. 8.1, page 29) (chap. 8.2, page 29)
Yes
Valve gate of solenoid valve cooling (-5Y1) Yes Let the valve gate replace
defective? (chap. 12, page 83)
No
No
No
Capillary tube (-J6) to plate evaporator cooling Yes Let capillary tube (-J6) replace
blocked? (chap. 12, page 83)
Solenoid valve dehumidification (-8Y1) or (-8Y2) Yes Replace solenoid valve dehumidification
defective? (-8Y1) or (-8Y2) (chap. 12.3, page 84)
No
Valve gates of solenoid valves dehumidification Yes Let the defective valve gate replace
(-8Y1) or (-8Y2) defective? (chap. 12, page 83)
No
Capillary tubes (-J4) or (-J4) to plate evaporators Yes Let blocked capillary tube (-J4) or (-J4)
dehumidification blocked? replace (chap. 12, page 83)
No
Yes
Controller defective? Replace controller (chap. 10.9, page 67)
No
I/O-switch (-6S1) of the humidity system Yes Replace I/O-switch (-6S1) of the humidity
defective? system (chap. 11.1, page 69)
No
Is the facility-side water supply closed? Yes Open facility-side water supply
(see operating manual)
No
Hose burst protection device interrupts the water Yes Release the hose burst protection device
supply? (see operating manual)
No
Fresh water connection of unit blocked? Yes Unscrew fresh water hose and clean
connection (see operating manual)
No
Humidity sensor incl. circuit board (-2B2) Yes Replace humidity sensor incl. circuit board
(chap. 9.5, page 50)
defective?
No
Solid state relay (-6K1) or (-6K2) defective? Yes Replace solid state relay (-6K1) or (-6K1)
(chap. 10.8, page 66)
No
Humidity controller board (-7N1) defective? Yes Replace humidity controller board (-7N1)
(chap. 11.3, page 71)
No
No
I/O-switch (-6S1) of the humidity system Yes Replace I/O-switch (-6S1) of the humidity
defective? system (chap. 11.1, page 69)
No
During the recommended annual maintenance work (chap. 3, page 12) and after every repair
(chap. 7 to 11) a check for electrical safety has to be done.
This electrical safety check has to include the following tests:
Check of the protective conductor (PE)
Measuring of the leakage current
(Measuring of the insulating resistance is not possible for technical reasons.)
BINDER recommends to perform the electrical safety check according to the German standard:
DIN VDE 0701-1 September 2000
Instandsetzung, Änderung und Prüfung elektrischer Geräte, Teil 1: Allgemeine
Anforderungen
(Repair, modification and inspection of electrical appliance, Part 1: General requirements).
Alternatively the electrical safety check can be performed according to similar national standards
which include the specified tests above.
Irrespective of the used standard for the electrical safety check the following limit values must be
observed (Table 2).
Table 2: Limit values of the electrical safety check
A B C D E F G H
Figure 1: Replacing the housing cover at the front and the air shielding plate
A B C D E
A B C D E
A B
A Lug
B Adjusting screw
CAUTION!
Danger of damaging the electronic!
The instrument box must only be opened at a workstation which is equipped with all
necessary protective measures against electrostatic discharge.
Circuit boards might be damaged by electrostatic discharges, penetrating particles like
dust and touching of its components.
CAUTION!
Danger of mechanical damages!
Never let the instrument box hang at electric cables. Electric cables are not appropriate
to hold bigger components and will be damaged if you do so.
Spare parts: Instrument box MB1 MK/KBF complete order no. 8008-0130
or
Housing instrument box MB1 with lens order no. 8500-0006
Switch mat MB1, fivefold order no. 6002-0184
Switch mat MB1, threefold MK order no. 6002-0196
Filter pane MB1 I-Box order no. 6002-0160
A B C D E F G H I J K L M
A Light switch ( -9S1) (only for units with option “Interior lighting)
B Power switch ( -1S1)
C Clips
D Connectors
ATTENTION!
Danger of damages!
Never let the interior side hang at the heating cable of the door. Electric cables are not
appropriate to hold bigger components and will be damaged if you do so.
A B C D E F
ATTENTION!
Danger of damages!
Never let the interior side hang at the heating cable of the door. Electric cables are
not appropriate to hold bigger components and will be damaged if you do so.
A B C D E F C A D
A B C D E F
KBF 115
A
B
C
D
E
F
G
H
I
J
K
KBF 240/720
A
B
C
D
E
F
G
H
I
J
K
(I) (II)
8.8 Testing and replacing door with the heating cable (-3E2 )
Spare parts: KBF 115
Housing door, interior side order no. 8003-0096
KBF 240
Housing door 240 KBF/E2, interior side right order no. 8003-0101
Housing door 240 KBF/E2, interior side left order no. 8003-0100
KBF 720
Housing door 720 KBF/E2, interior side right order no. 8003-0103
Housing door 720 KBF/E2, interior side left order no. 8003-0102
11. Install the interior side of the housing door (A) by following the steps above in reverse order.
Take care to pass the heating cable (D) through the hose (B) in the lead-through of the hinge
and to secure the passed through cables with a lacing cord.
A B C D E
A B C D E F G
1. Pull the old door sealing (B) from the edge (D) of the outer enclosure.
2. Put the new sealing (B) with the joint at which the sealing is cemented on the upper edge of
the outer enclosure
3. Push the door sealing (B) with its chamfer (C) on the edge (D) of the outer enclosure (see
and ).
4. Pass the door sealing further on the lateral edge and push the chamfer (C) on the edge.
5. Pull the door sealing downward diagonally until it can be push completely on the edge of
the outer enclosure.
6. Test if the door(s) close(s) tight by opening and closing it (them) (chap. 8.1, page 29).
C A Housing
D C Chamber
B Sealing
D Edge of outer enclosure
1. Hold on to a glass door and unscrew the screws of both door hinges.
2. Replace the glass door and screw the new door tightly at its hinges.
3. Unscrew the screw(s) of the catch.
4. Replace the catch and screw it tightly.
5. To adjust the glass door loosen the screws of both hinges a little so that the door can be
moved laterally within the slots.
6. Adjust the door and tighten all screws of the hinges.
7. To adjust the catch loosen the screw(s) of it a little so that the catch can be moved within
the slots.
8. Adjust the catch and tighten the screw(s).
The cap nut has a left-hand thread, which will be opened by turning it
clockwise to the right.
A B C D E F G H
I J K
I Electrical connectors
K Screws
J Fan motor
5. Compare the measured resistance value with the values given in Table 4 regarding the
measurement uncertainties of the thermometer and the multimeter.
If the measured value divides more than 10 % from the value in Table 4, the Pt100
temperature sensor seems to be defective and should be replaced.
6. Remove the racks out of the inner chamber.
7. Remove the fan cover (chap. 9.3, page 45).
8. Remove the insulating foam (D) which is located on the rear side of the inner chamber round
the cables of the temperature sensor (E) and the temperature fuse (F) with a knife (C) without
damaging any cable.
T (°C) 0 1 2 3 4 5 6 7 8 9 10
-10 96.086 96.478 96.870 97.262 97.653 98.045 98.436 98.827 99.218 99.609 100.000
0 100.000 100.391 100.781 101.172 101.562 101.953 102.343 102.733 103.123 103.513 103.902
10 103.902 104.292 104.681 105.071 105.460 105.849 106.238 106.627 107.016 107.404 107.793
20 107.793 108.181 108.570 108.958 109.346 109.734 110.122 110.509 110.897 111.284 111.672
30 111.672 112.059 112.446 112.833 113.220 113.607 113.994 114.380 114.767 115.153 115.539
40 115.539 115.925 116.311 116.697 117.083 117.469 117.854 118.240 118.625 119.010 119.395
50 119.395 119.780 120.165 120.550 120.934 121.319 121.703 122.087 122.471 122.855 123.239
60 123.239 123.623 124.007 124.390 124.774 125.157 125.540 125.923 126.306 126.689 127.072
70 127.072 127.454 127.837 128.219 128.602 128.984 129.366 129.748 130.130 130.511 130.893
80 130.893 131.274 131.656 132.037 132.418 132.799 133.180 133.561 133.941 134.322 134.702
90 134.702 135.083 135.463 135.843 136.223 136.603 136.982 137.362 137.741 138.121 138.500
100 138.500 138.879 139.258 139.637 140.016 140.395 140.773 141.152 141.530 141.908 142.286
9. Pull the Pt100 temperature sensor (H) backward through the rear panel of the outer
enclosure with the silicon sealing (G).
Take care that the silicon sealing (G) remains in the lead-through of the inner chamber.
10. Install the new Pt100 temperature sensor by following steps 1 to 9 in reverse order without
testing the sensor.
11. Adjust the temperature control (chap. 14.3, page 90).
A B C D E F G H
(I)
(II)
(I)
(II)
(I)
(II)
A I J K E
A B C (D*) D E
7. KBF 115/240: Press the heads of the mounting nipples (E) which fix the humidity sensor board
(D) at the electric mounting plate (C) together and remove the humidity sensor board (D) from
the nipples.
KBF 720: Press the heads of the mounting nipples (E) which fix the humidity sensor board (D*) at
the KBF housing together and remove the humidity sensor board from the nipples.
8. Disconnect the wire from the connector (-20, voltage output 45mA / 24V DC) of the controller
I/O board (-2N2) (see relevant wiring diagram).
9. Disconnect the wire from the spring terminal (-11, E4 / 4-20mA) of the controller I/O board
(-2N2) (see relevant wiring diagram).
10. Loosen all fasteners of the cables as far as necessary to separate the cables to the
connectors (-3) and (-4) of the humidity board (D) from the wiring harnesses.
Please note that both cables consist of two different colored pieces.
11. Install the new humidity sensor by following steps 1 to 10 in reverse order.
12. Fill the hole in the isolation with insulating foam.
13. Adjust the humidity control (chap. 14.4, page 95).
F G H I J K L
CAUTION!
A B C D E F
6. Remove the silicon at the opening of the outer enclosure (A) between inner chamber
(B, D, E, F) and outer enclosure (A).
7. For KBF 115 go on with step 8.
For KBF 240/270 go on on with step 14.
KBF 115:
8. Unscrew the screws which fix the stop ledge (F) at the ceiling of the outer enclosure (A) and
remove it.
9. Unscrew the screws which fix the side plates (B, E) of the inner chamber at the ceiling of the
outer enclosure (A).
10. Remove the side plates (B, E) out of the outer enclosure (A).
11. Unscrew the screws which fix the bottom (D) of the inner chamber.
12. Remove the bottom (D) of the inner chamber out of the outer enclosure (A).
13. Go on with step 20.
KBF 240/720:
14. Unscrew the screws which fix the bottom (D) of the inner chamber.
15. Remove the bottom (D) of the inner chamber out of the outer enclosure (A).
16. Unscrew the screws which fix the stop ledge (F) at the ceiling of the outer enclosure (A) and
remove it.
17. Unscrew the screws which fix the side plates (B, E) of the inner chamber at the ceiling of the
outer enclosure (A).
18. Remove the side plates (B, E) out of the outer enclosure (A).
19. Go on with step 20.
KBF 115/240/720:
20. Unscrew the screws which fix the rear panel (C) of the inner chamber.
21. Remove the rear panel (C) of the inner chamber out of the outer enclosure (A).
22. Install the inner chamber by following steps 0 to 21 in reverse order.
Take care to seal the opening of the outer enclosure (A) between inner chamber (B, D, E, F)
and outer enclosure (A) with silicon. Previous remove all old silicon from the parts and ensure
that they are free of grease.
KBF 240:
If R measured = 78 Ω ±10 %, the heater is all right.
If R measured ≠ 78 Ω ±10 %, the heater is defective. Go on with next step.
KBF 720:
If R measured = 42 Ω ±10 %, the heater is all right.
If R measured ≠ 42 Ω ±10 %, the heater is defective. Go on with next step.
6. Remove silicon hoses (D) filled with silicon from the heaters connectors (A) by using a knife
without damaging the plugs or cables.
7. Remove the plugs (E) from the connectors (A) of the heater.
8. Measure the resistance of each heater between both connectors (A) by using a multimeter.
KBF 115:
If R measured = 132 Ω ±10 %, the heater is all right and one of the connecting cables is
defective.
If R measured ≠ 132 Ω ±10 %, the heater is defective. Go on with next step.
KBF 240:
If R measured = 39 Ω ±10 %, the heater is all right and one of the connecting cables is
defective.
If R measured ≠ 39 Ω ±10 %, the heater is defective. Go on with next step.
KBF 720 side heater:
If R measured = 42 Ω ±10 %, the heater is all right and one of the connecting cables is
defective.
If R measured ≠ 42 Ω ±10 %, the heater is defective. Go on with next step.
KBF 720 bottom heater:
If R measured = 21 Ω ±10 %, the heater is all right and one of the connecting cables is
defective.
If R measured ≠ 21 Ω ±10 %, the heater is defective. Go on with next step.
9. Remove the plates of the inner chamber (chap. 9.6, page 52).
10. Remove the insulating foam (B) which is located on the rear side of the outer enclosure round
the connectors (A) of the heater with a knife.
11. Remove the locking washers (C) from the connectors (A) of the heater by bending up the teeth
of the washer and pulling it from the connectors.
For fixing the new heater new locking washers has to be used.
12. Pull the heater (F) forward out of the outer enclosure.
13. Put the new heater (F) into the outer enclosure.
14. Position the heater (F) by using the spacer (G).
Take care that the spacer are mounted accurately (see Figure 21).
15. Go on by following steps 4 to 12 in reverse order without testing the heaters.
16. Insulate the connectors (A) of the heater(s) by filling the silicon hoses (D) round the
connectors with transparent silicon.
17. Fill the holes in the isolation with insulating foam.
18. Go on by following steps 1 to 3 in reverse order.
A B A C D E
Figure 20: Replacing the heater (view on rear panel of inner chamber)
F G G G
Spare parts: KBF 115: Miniature fuse 10A/250V medium time-lag 5x20mm
order no. 5006-0012
KBF 240/720: Miniature fuse 16A/250V medium time-lag 5x20mm
order no. 5006-0013
A
Figure 22: Replacing the miniature fuse
D
E
F
F G
C
D
A Power module
D Terminal strip
B Suppressor capacitor (-1Z1)
E Screws of power module
C Screw nut
A B C D E F G H
Figure 25: Replacing the temperature fuse 110 °C (left: KBF 115/240, right: KBF 720)
10.5 Pulling the electric mounting plate out of the machine room
CAUTION!
Danger of damaging the electronic!
The electric mounting plate must only be serviced at a workstation which is equipped
with all necessary protective measures against electrostatic discharge.
Circuit boards might be damaged by electrostatic discharges, penetrating particles like
dust and touching of its components.
A B C D E
Figure 26: Pulling the electric mounting plate out of the machine room
J I H
A Contactor
B Terminal strips
C Top hat rail
Spare parts: Solid state relay (1S / 25A) 280VAC order no. 5011-0036
former: solid state relay (1S / 50A) 230VAC order no. 5011-0035
(both types of relay can be combined in one KBF)
A B C D E F G
J I H
CAUTION!
Danger of damaging the electronic!
The controller boards must only be serviced at a workstation which is equipped with all
necessary protective measures against electrostatic discharge.
Circuit boards might be damaged by electrostatic discharges, penetrating particles like
dust and touching of its components.
Controller display (-2N1) and controller I/O-board (-2N2) should basically be replaced together.
In particular cases it might be sufficient to replace only one of the boards.
After replacing the controller the unit must be adjusted (chap. 14, page 89).
A Screws
B Screw with ground wire
C Connector
D Controller display (-2N1)
A B C D E
I H G F
A B C D
CAUTION!
Danger of damaging the electronic!
The humidity control board must only be serviced at a workstation which is equipped with
all necessary protective measures against electrostatic discharge.
Circuit boards might be damaged by electrostatic discharges, penetrating particles like
dust and touching of its components.
A B
CAUTION!
1. Connect the waste water connection of the unit to a drain connection or a receptacle with 5
liters capacity minimum by a suitable hose (see operating manual).
2. Close the facility-side water supply, if the unit it connected to such.
3. Disconnect the unit from the facility-side water supply.
4. Set the 0/I-switch (-6S1) of the humidity system to I.
5. Switch the unit OFF and ON at the power switch.
During the start-up the water is pump out of the steam cylinder within 45 seconds. After that
the pump is switched off automatically.
6. Switch off the unit at the power switch after pumping dry the steam cylinder and disconnect it
from the power supply.
When disconnecting the hose from the connector of the valve (D) remaining
water can run out. Take care to collect this water!
A BC D
E
F
A
B
1. Remove the water from the steam cylinder (chap. 11.4, page 72).
2. Disconnect the unit from the power supply.
3. Disconnect the unit from the facility-side water supply.
4. Remove the lower rear panel of the housing (chap. 7.2, page 28).
5. Draw the plugs from the electrode connectors (B, D).
F
A
B G
B
D
C H
E
I
J
K
6. Loosen the hose clamp of the hose (E) and disconnect the hose from the cover (F) of the
steam cylinder.
7. Loosen the lower hose clamp (C) of the steam hose (A).
8. Disconnect the steam hose (A) from the connection port of the cover (F) of the steam cylinder.
For pulling off, the steam cylinder (H) can be folded a little sideward.
9. Pull the steam cylinder (H) out of the support foot (K).
When pulling the steam cylinder (H) out of the support foot (K) remaining water
can run out. Take care to collect this water!
10. Pull the o-ring (I) from the connection port of the steam cylinder (H).
Please note the mounting order when connecting the steam cylinder (H) with
the support foot (K). Otherwise the connection will not close tight.
11. Put the o-ring (I) into the groove (J) inside the support foot (K).
12. Put the connection port of the steam cylinder (H) into the support foot (K)
13. Adjust the steam cylinder (H) so that the tappet (G) is placed over the lateral support plate of
the collecting tray (L).
14. Push the connection port of the steam cylinder (H) into the support foot (K) and the tappet (G)
over the support plate.
15. Go on by following steps 1 to 8 in reverse order.
16. Remove all water from the collecting tray (L).
CAUTION!
A
B
Optional
If necessary small holes can be drilled into the separating plate to get an
optimal current flow.
B
C
11.10 Cleaning the drainage pump (-8M1) and replacing the pump
sealings
1. Remove the water from the steam cylinder (chap. 11.4, page 72).
2. Disconnect the unit from the power supply.
3. Disconnect the unit from the facility-side water supply.
4. Remove the lower rear panel of the housing (chap. 7.2, page 28).
When pulling adapters or hoses from the drainage pump remaining water can
run out. Take care to collect this water!
5. Pull the pump adapter (C) from the pump cover (E).
If the o-ring (D) of the pump adapter is damaged replace it by a new one.
6. Loosen the hose clamp (B).
A B C D E E F G H
Figure 41: Cleaning the drainage pump
7. Pull the waste water hose (A) from the connector of the pump cover (E).
8. The pump cover (E) is equipped with a circlip (F) on its lower side. Pull the circlip (F) forward
and turn the pump cover (E) clockwise to the right until you can remove it.
9. Clean the inside of the pump and replace the o-ring (G) of the pump.
10. Assemble the pump by following steps 0 to 8 in reverse order.
11. Remove all water from the collecting tray.
1. Remove the water from the steam cylinder (chap. 11.4, page 72).
2. Disconnect the unit from the power supply.
A
B
E
C F
D
G
H
I
When pulling adapters or hoses from the drainage pump remaining water can
run out. Take care to collect this water!
M
Figure 43: Replacing the drainage pump
14. Unscrew the screws (M) and remove the pump (F).
15. Remove all water from the collecting tray (K).
16. Install the new pump by following steps 1 to 14 in reverse order.
Seal the screws (L) and (M) with silicon.
The plugs (E) can be connected to the connectors of the pump (F) in any order.
WARNING!
If the cooling system of the KBF is maintained or repaired incorrectly, there is
a risk of malfunction which could cause harm to human beings and material
damage to the equipment and samples.
The cooling system of the KBF should only be repaired by qualified persons.
To avoid any repair trails by unqualified people, the repair of the cooling
system is not described in this service manual.
To be able to carry out the repair of the cooling system the enforcing personnel must have
specialized training as cooling technician and be familiar with the service and the operation of
the KBF.
As sole exception the replacement of the solenoid valves (-5Y1, -8Y1, -8Y2) can be performed
by normal service personnel (chap. 12.3, page 84).
DANGER!
Danger of electric shock. Danger to life.
This testing methods require that the unit is switched on.
Therefore, a second person is required to switch off the unit in case of an
emergency!
In this chapter a procedure is described how the error pattern of the cooling system described in
the troubleshooting can be tested easily (chap. 0, page 21, chap. 5.4, page 22).
For positions of the components see Figure 45, page 100 or Figure 46, page 101.
1. Remove both rear panels of the housing (chap. 7.2, page 28)
2. Remove the housing cover at the front (chap. 7.1, page 26).
3. Switch off the I/O switch of the humidity system.
4. Switch on the unit.
5. Set the temperature to -10 °C and the humidity to 90% r.H.
6. Switch off the unit.
7. Switch on the unit.
8. A few seconds after starting the unit the condenser fan (-5M2) and the compressor (-5M1)
starts working. The solenoid valve cooling (-5Y1) opens which can be felt and heard.
9. Let the unit operate for about 10 minutes.
10. Feel or measure the temperature of the following tubes:
The temperature of the tube between the compressor and the condenser should be at
about 75 °C to 90 C. If not, the compressor does not work sufficient.
The temperature of the tube between condenser and the solenoid valve cooling (-5Y1)
should be at about ambient temperature to approx. 35 °C.
If not, the condenser does not work sufficient.
The temperature of the tube between the capillary tube and the cooling evaporator under
the isolation should be at about -10 °C to -25 °C.
If not, the capillary tube may be blocked.
11. Switch on the I/O switch of the humidity system.
One of the solenoid valves dehumidification (-8Y1) or (-8Y2) opens which can be felt and
heard.
12. Let the unit operate for further 10 minutes.
13. Feel or measure the temperature of the tube between the capillary tube and the related
dehumidification evaporator under the isolation. It should be at about -10 °C to -25 °C.
If not, the capillary tube may be blocked.
14. Switch over the active dehumidification evaporator by DIP switch 6 of the humidity control
board (see Table 5, page 105). The up to now closed solenoid valve dehumidification (-8Y1)
or (-8Y2) opens which can be felt and heard.
13 Spare parts
Name of spare part Order No. Installation
Air shielding plate
KBF 115
Air shielding plate 115 KBF/E2 4001-0353
KBF 240 chap. 7.1, page 26
Air shielding plate 240 KBF/E2 4001-0366
KBF 720
Air shielding plate 720 KBF/E2 4001-0368
Contactor (3H/1Ö) 230VAC – 2.2kW 5011-0008 chap. 10.7, page 65
At the calibration the temperature and humidity values measured and displayed by the KBF are
compared with values measured and displayed by an external reference measuring instrument.
If the deviations of the temperature or humidity values of the KBF and the reference measuring
instruments exceed defined values, called confidence criteria, the temperature or the humidity
control of the KBF have to be adjusted.
The reference measuring instruments for temperature and humidity must have a valid calibration
certificate which has been approved by a recognized standards or calibration authority or
regulatory body.
The measuring uncertainty of the reference measuring instrument for the temperature should be
below 0.5 K.
The measuring uncertainty of the reference measuring instrument for the humidity should be below
2 % RH
The adjustment of the temperature control is carried out as a single point adjustment.
Choose the most common operating temperature or a temperature situated in the middle of the
most common used temperature range as calibrating and adjusting point.
The adjustment of the humidity control is carried out as a dual point adjustment.
Choose the values which limit the most common used humidity range as calibrating and adjusting
points.
Before the unit can be re-adjusted the current adjustment has to be reset and the input value
correction has to be switched off.
1. Starting from the basic display push <CONFIG>.
W X
Config uration 1
Parameters
Choose variation
+02802
“
4. Use the buttons or to select the menu item
“Service Level“ and confirm with <ENTER>.
Config uration 2
Analog ue inputs
Analog ue outputs
Limit comperators
Donor-functions
Controller
Service Level
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limituecomperators
Analog Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin.Service
OutputsLevel
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
Limit comperators
Analog ue input 1
Donor-functions
Analog ue input 2
Analog Controller
ue input 3
Analog Service
ue input Level
4
Analog ue input 5
Safety controller
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog ue input 1
Donor-functions
8. Use the buttons , , and to key in the Analog ue input 2
State
Analog Controller
ue
Start Value X input 3
Off
+ 0.0
Service Level
values given below and confirm with <ENTER>. Analog ue
Start Value W input 4 + 0.0
EndAnalog
Value Xue input 5 +1000.0
EndSafety
Value controller
W +1000.0
State: Off
Start value X: 0.0
Start value W: 0.0
End value X: 1000.0
End value W: 1000.0
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
10. For KBF 720: Analog Limit comperators
ue input 1
Donor-functions
Repeat step 6 to 9 with menu item “Analogue Analog ue input 2
Analog Controller
ue input 3
Input 2“ Analog Service
ue input Level
4
Analog ue input 5
Safety controller
11. Use the buttons or to select the menu item
“Safety controller“ and confirm with <ENTER>.
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input 1
Safety controller
Donor-functions
13. Use the buttons , , and to key in the Analog ue input 2
State
StartAnalog
Controller
ValueueX input 3
Off
+ 0.0
Service Level
values given below and confirm with <ENTER>. StartAnalog
ValueueW input 4 + 0.0
EndAnalog
Value Xue input 5 +1000.0
EndSafety
Value controller
W +1000.0
State: Off
Start value X: 0.0
Start value W: 0.0
End value X: 1000.0
End value W: 1000.0
Config uration 2
Analog ue inputs
Analog ue outputs
Limit comperators
Donor-functions
Controller
Service Level
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limituecomperators
Analog Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin.Service
OutputsLevel
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
Analog ue inputs
Service Level
“2.”. Analog Analog ue outputs
ue Inputs
1. Limit comperators +20.791
2. Donor-functions + 0.0
3. Controller - 12.5
4. Service Level +65.317
5. - 12.5
Config uration 2
Config uration 1
Parameters
Choose variation
User-Settings
Instrument data
Contrast 22
Displ. power down
Contin. operation
User level
Safety controller.Set + 55.0 °C
Safety controller.Act + 22.7 °C
8. Note down the displayed temperature value of the reference measuring instrument
(e.g. +21.6).
9. Compare the values of the noted controller parameters “1.” (KBF 720: also “2.”) and “Safety
control.Act” with the displayed temperature value of the reference measuring instrument.
10. Adjust the main and the safety temperature controller if the deviation of the values of the
controller parameters “1.”, (KBF 720: also “2.”) resp. “Safety control.Act” and the reference
measuring instrument is found to be larger than 0.5 K (confidence criteria) (chap. 14.3.3,
page 94). In case the reference measuring instrument has a measuring uncertainty larger
than 0.5 K (see its calibration certificate), this is the confidence criteria (e.g. 0.75 K).
If the deviation is found to be larger than 2 K replace the Pt100 temperature sensor
(chap. 9.4, page 47)
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limituecomperators
Analog Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin. OutputsLevel
Service
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input 1
Donor-functions
Analog ue input 2
Controller
Analog ue input 3
Analog Service
ue input Level
4
Analog ue input 5
Safety controller
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog ue input
Donor-functions
4. Use the buttons , , and to key in the Analog ue input 2
State
StartAnalog
Controller
ValueueX input 3
On
+ 0.0
Service Level
values given below and confirm with <ENTER>. StartAnalog
Valueue
Analog
W input 4
ue input 5
+ 0.0
End Value X + 20.8
Safety
End Value Wcontroller + 21.6
State: On
Start value X: 0.0
Start value W: 0.0
End value X: Value of “Analogue Inputs.“/“1.”
(e.g. +20.8) (step 3, chap. 14.3.2 page 93).
End value W: Value of reference measuring
instrument (e.g. +21.6) (step 8, chap. 14.3.2,
page 94).
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
6. For KBF 720: Analog Limit comperators
ue input 1
Donor-functions
Repeat step 2 to 5 with menu item “Analogue Input Analog ue input 2
Analog Controller
ue input 3
2“ Analog Service
ue input Level
4
Analog ue input 5
Safety controller
7. Use the buttons or to select the menu item
“Safety controller“ and confirm with <ENTER>.
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input 1
Safety controller
Donor-functions
9. Use the buttons , , and to key in the Analog ue input 2
State
StartAnalog
Controller
ValueueX input 3
On
+ 0.0
Service Level
values described below and confirm with StartAnalog
ValueueW input 4 + 0.0
EndAnalog
Value Xue input 5 + 22.7
<ENTER>. EndSafety
Value controller
W + 21.6
State: On
Start value X: 0.0
Start value W: 0.0
End value X: Value of “Safety controller“/“1.”
(e.g. +22.7) (step 7, chap. 14.3.2 page 93).
End value W: Value of reference measuring
instrument (e.g. +21.6) (step 8, chap. 14.3.2,
page 94).
10. Push <EXIT> four times to return to the basic
W X
display.
The corrected value appears on the controller
display after 5 seconds.
11. Compare the displayed temperature values of the
controller display and the reference measuring
instrument. The deviation must be less than the
confidence criteria (chap. 14.3.2, page 92).
Before the unit can be re-adjusted the current adjustment has to be reset and input value
correction has to be switched off.
1. Enter the menu “Inp.Val. correct.“
(see steps 1 to 5, chap. 14.3.1, page 90)
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limituecomperators
Analog Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin. OutputsLevel
Service
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input 1
Donor-functions
Analog ue input 2
Controller
Analog ue input 3
Analog Service
ue input Level
4
Analog ue input 5
Safety controller
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input
4 1
Analog ue input
Donor-functions
4. Use the buttons , , and to key in the Analog ue input 2
State
StartAnalog
Controller
ValueueX input 3
Off
+ 0.0
Service Level
values described below and confirm with StartAnalog
Valueue
Analog
W input 4
ue input 5
+ 0.0
End Value X +1000.0
<ENTER>. Safety
End Value Wcontroller +1000.0
State: Off
Start value X: 0.0
Start value W: 0.0
End value X: 1000.0
End value W: 1000.0
Config uration 2
Analog ue inputs
Analog ue outputs
Limit comperators
Donor-functions
Controller
Service Level
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limit comperators
Analog ue Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin.Service
OutputsLevel
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
4. Note down the displayed humidity value of the Analog ue inputs
Service Level
Analog Analog ue outputs
ue Inputs
reference measuring instrument (e.g. 67.5% RH). 1. Limit comperators +21.041
2. Donor-functions + 0.0
3. Controller - 12.5
4. Service Level +65.307
5. - 12.5
Config uration 2
9. Enter the menu “Analogue Inputs.“ (see steps Analog ue inputs
Service Level
Analog Analog ue outputs
ue Inputs
1and 2) 1. Limit comperators +21.041
2. Donor-functions + 0.0
Controller
10. Note down the actual value of “4.” (e.g. +39.972). 3.
4. Service Level
- 12.5
+39.972
5. - 12.5
11. Note down the displayed humidity value of the
reference measuring instrument (e.g. 42.2% RH).
12. Compare the values of the noted controller parameter “4.” at both set humidities with
the displayed humidity values of the reference measuring instrument at the
corresponding set points.
13. Adjust the humidity controller if the deviation of one of the values of the controller
parameter “4.” and the reference measuring instrument is found to be larger than
2 % RH (confidence criteria) (chap. 14.4.3, page 98).
In case the reference measuring instrument has a measuring uncertainty larger than
2 % RH (see its calibration certificate), this is the confidence criteria (e.g. 2.5 % RH).
If the deviation is found to be larger than 5 % RH replace the humidity sensor
(chap. 9.5, page 50)
Config uration 2
Analog ue inputs
Service Level
Analog
Inp.Val. ue outputs
correct.
Limit comperators
Analog ue Inputs
Donor-functions
Analog ue Outputs
Bin.Controller
Inputs
Bin. OutputsLevel
Service
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
Config uration 2
Analog ue inputs
Service Level
Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input 1
Donor-functions
Analog ue input 2
Controller
Analog ue input 3
Analog Service
ue input Level
4
Analog ue input 5
Safety controller
Config uration 2
Analog ue inputs
Service Level
For each menu item a submenu will be opened. Inp.Val.Analog ue outputs
correct.
Analog Limit comperators
ue input
4 1
Analog ue input
Donor-functions
Use the buttons , , and to key in the
Analog ue input 2
State Off
4. StartAnalog
Controller
ValueueX input 3
Service Level
+ 40.0
Analog ue input 4
values described below and confirm with Start Value W
EndAnalog
Value Xue input 5
+
+
42.2
65.3
EndSafety
Value controller
<ENTER>. W + 67.5
State: On
Start value X: Value of “Analogue Inputs.“/“4.”
at the lower set humidity (e.g. +40.0)
(step 10, chap. 14.4.2, page 98).
Start value W: Value of reference measuring
instrument at the lower set humidity
(e.g. 42.2) (step 11, chap. 14.4.2, page 98).
End value X: Value of “Analogue Inputs.“/“4.”
at the higher set humidity (e.g. +65.3)
(step 3, chap. 14.4.2, page 97).
End value W: Value of reference measuring
instrument at the higher set humidity
(e.g. 67.5) (step 4, chap. 14.4.2, page 97).
5. Push <EXIT> four times to return to the basic
W X
display.
The corrected value appears on the controller
display after 5 seconds.
6. Compare the displayed humidity values of the
controller display and the reference measuring
instrument. The deviation must be less than the
confidence criteria (chap. 14.4.2, page 97).
-J4
-J6 -J9
-5Y1 B
A -5M1
-J3 C
-8Y1 -5M2
-J6 A
-J4 -J13
A -J12
-5Y1 B
-J3 C
-8Y1 -5M1
The system for controlling the humidity in the KBF consists of following components:
I/O-switch of the humidity system (-6S1)
Humidity control board (-7N1)
2 Solid state relays (-6K1, -6K2)
Steam generation unit (see Figure 47)
Humidity sensor incl. humidity sensor board (KBF 115/240: -2B2; KBF 720: -2B3)
2 Plate evaporators dehumidification (KBF 115/240: -J7 or -J8 (see Figure 45);
KBF 720: -J8 or -J9 (see Figure 46)).
B
B
G
H
C
I
E
J
K
F
The steam is generated in the steam cylinder (-6A1, C) by means of an alternating current flow
between the electrodes (-6A1, D) through the water of the cylinder.
The steam generation unit operates optimal if the steam cylinder is ½ or ¾ filled. The leveling of
the water in the steam cylinder is controlled automatically by means of the current flow between
the electrodes (see chap. 15.2.3).
Water type: Tap water with conductivity of 200 µS/cm to 500 µS/cm (tolerance range
100 µS/cm to 800 µS/cm).
If the conductivity is between 100 µS/cm to 200 µS/cm large electrodes (order no. 5005-0056)
have to be installed (chap. 11.8, page 77).
If the conductivity is between 500 µS/cm to 800 µS/cm a separating plate
(order no. 6002-0088) has to be installed between the electrodes (chap. 11.9, page 79).
If the conductivity is outside of the range of 100 µS/cm to 800 µS/cm contact the BINDER
Service Hotline.
Total hardness 28.4 mg Ca/l up to 56.8 mg Ca/l
In this range of hardness the conductivity is normally between 200 µS/cm to 500 µS/cm.
In cases of lower hardness the conductivity is normally too low.
In cases of higher hardness the conductivity might be too high. Furthermore the steam
generator calcifies faster and shorter service intervals are necessary.
But in all cases the conductivity has to be measured as described before. It is possible that the
conductivity is in the range of 200 µS/cm to 500 µS/cm and the unit can be operated although
the hardness differs.
Amount of chloride in the water: <100 mg/l
High amounts of chloride and free chlorine, e.g. from water disinfection, causes strong
abrasion of the electrodes.
De-mineralized or distilled water cannot be used with the steam generation unit. The water
must be able to conduct electricity at a certain level (see above), which is not attainable from
de-mineralized or distilled water.
1. After switching on the humidity system at the I/O-switch (-6S1) the humidity control board
(-7N1) switches on the drainage pump (-8M1, J) for 45 seconds in order to remove water out
of the steam cylinder (-6A1, C).
2. After pumping off the water the humidity control board connects through the solid state relays
(-6K1, -6K2) and the electrodes for steam generation (-6A1, D) are supplied with voltage.
3. The humidity control board opens the fresh water valve (-8Y3, M) and let water flow into the
steam cylinder until the water reaches the level sensor (-6A1, G) or a current of 3 A flows
between the electrodes.
4. The humidity control board measures and stores the value of the current flowing at the
maximum liquid level.
5. The humidity control board switches on the drainage pump until so much water is pumped
off that the current flow between the electrodes is 85% of the maximum flow.
1. The active dehumidification plate evaporator dehumidifies the air of the inner chamber.
2. The humidity sensor (KBF 115/240: -2B2; KBF 720: -2B3) measures the humidity in the inner
chamber and sends the result to the controller (-2N2).
3. If the humidity in the inner chamber falls below the set point the controller ask the humidity
control board (-7N1) for higher humidity.
4. The humidity control board connects through the solid state relays (-6K1, -6K2) and the
electrodes for steam generation (-6A1, D) are supplied with voltage until the humidity in the
inner chamber meets the set point.
5. During the steam generation the current flow between both electrodes is measured by the
humidity control board in short intervals.
6. If the current flow is below 85% of the current having flown at the maximum liquid level the
fresh water valve (-8Y3, M) is opened until the 85% current flow is reached.
If the current exceeds 3 A or the water reaches the level sensor (-6A1, G) the water is pumped
off completely, replaced by new one and the 85% mark is determined new.
7. The opening of the door housing is recorded by the humidity control board (-7N1) via the door
switch (-7S1).
If the housing door is opened periodically, the water of the steam cylinder is changed
every two days
If the housing door is not opened, the water of the steam cylinder is changed every
30 days
8. Because of the dehumidification, ice builds up at the active dehumidification plate evaporator.
Therefore after 3-days permanent operation the active dehumidification plate evaporator is
switched off automatically by closing the related solenoid valve and the up to now passive
dehumidification plate evaporator takes over the dehumidification.
The ice at the switched off evaporator thaws and flows into the steam cylinder.
9. If the steam generation unit leaks so that the water flows into the collecting tray (F) the float
switch (-8S1, I) closes the fresh water valve (-8Y3, M).
Some functions of the humidity control board (-7N1) can be switched on and off manually
(see Table 5).
At delivery all DIP switches of the KBF are set to "Off" which is the standard operating state.
Table 5: Functions of the DIP switches of the humidity control board (-7N1)
1 No function No function
2 No function No function
Automatic switch on of drainage pump Immediate switch on of drainage pump
3 If the housing door is opened periodically, the The water of the steam cylinder is changed
water of the steam cylinder is changed every immediately.
two days
If the housing door is not opened, the water
of the steam cylinder is changed every
30 days
4 (never
Standard operation Reset of service display
switch)
Automatic switch over of dehumidification plate Manual switch over of dehumidification plate
5
evaporator evaporator
Dehumidification plate evaporator 1 on, 2 off Dehumidification plate evaporator 1 off, 2 on
6
(Only if DIP 5 = ON) (Only if DIP 5 = ON)
7 (never
Standard operation Calibration current sensor
switch)
8 (never
Standard operation Controller reset
switch)
Table 6: Functions of the LED of the humidity control board (see Figure 48)
LED 2 On Input 24V DC of terminal strip -X1, 24 V supply unit (-1T1) supplies voltage
LED 4 On Input BE2 of terminal strip -X3 is powered
LED 8 On Input BE6 of terminal strip -X10 door switch is closed (-7S1), door is opened
LED 9 On Input BE7 of terminal strip -X10 is powered, controller inquires humidity
Output BA1 of terminal strip -X6 is triggered
LED 11 On
solenoid valve (-8Y1) of dehumidification plate evaporator is opened
Output BA2 of terminal strip -X6 is triggered
LED 12 On
solenoid valve (-8Y2) of dehumidification plate evaporator is opened
LED 13 On Output BA3 of terminal strip -X6 is triggered, fresh water valve(-8Y3) is opened
LED 14 On Output BA4 of terminal strip -X6 is triggered, drainage pump (-8M1) is switched on
Output BA5 of terminal strip -X7 is triggered
LED 15 On
solid state relays (-6K1) and (-6K1) are connected through
X1 X5 X10 6 5 4 3 2 1 4 3 2 1 X4
1 1
2 2 LED 2
3 3
4 4
LED 9 LED 8 LED 7 LED 6 LED 5
X2
1
2
3
LED 11
X6
1
X3
1 LED 3 LED 12 2
2 3
LED 17 LED 16 LED 15
3 4
4 LED 13 5
5 LED 4
LED 14
6 5 4 3 2 1 X7
Figure 48: Terminal strips and LED of the humidity control board (-7N1)
16 Revision history
Issue Modification/Amendment
04-2007