Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Settings: Settings P63X/Uk St/A54 Micom P631, P632, P633, P634

Download as pdf or txt
Download as pdf or txt
You are on page 1of 108

Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634

ST

SETTINGS

Date: 16th June 2006


Hardware Suffix: -305
Software Version: -610
Connection Diagrams: -404 (P631, P632, P634)
-406 (P633)
P63x/UK ST/A54 Getting Started

MiCOM P631, P632, P633, P634

ST
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-1

CONTENTS

(ST) 4-

1. SETTINGS 5
1.1 Device ID 5

1.1.1 Device identification (DVICE) 5

1.2 Configuration 9

1.2.1 Local control panel configuration (HMI) 9

1.2.2 Local front port communication configuration (PC) 10

1.2.3 Rear port communication configuration (COMM1) 12

1.2.4 2nd rear port communication configuration (COMM2) 21

1.2.5 Communication interface IEC 61850 (IEC) 23 ST


1.2.6 Communication interface GOOSE 26

1.2.7 Communication interface GSSE 31

1.2.8 Enabling IRIG-B time synchronization (IRIGB) 34

1.2.9 Opto input assignment and operating mode configuration (INP) 35

1.2.10 Temperature & DC monitoring inputs configuration (RTDmA) 37

1.2.11 Output relay assignment and operating mode configuration (OUTP) 38

1.2.12 Analog output channel configuration (mA_OP) 40

1.2.13 LED assignment and operating mode configuration (LED) 43

1.2.14 Communication and time synchronization channel assignment (MAIN) 45

1.2.15 Disturbance recorder channel configuration (OSCIL) 46

1.2.16 Cancelling a protection function 47

1.2.17 Enabling differential protection (DIFF) 47

1.2.18 Enabling restricted earth fault protection (REF_) 48

1.2.19 Enabling definite time overcurrent protection (DTOC) 48

1.2.20 Enabling inverse time overcurrent protection (IDMT) 48

1.2.21 Enabling thermal overload protection (THRM) 49

1.2.22 Enabling under/overvoltage protection (V<>) 49

1.2.23 Enabling frequency protection (f<>) 49

1.2.24 Enabling overfluxing protection (V/f) 50

1.2.25 Enabling current transformer supervision (CTS) 50

1.2.26 Enabling broken conductor detection (BC_) 50

1.2.27 Enabling temperature & DC monitoring (LIMIT) 51


P63x/UK ST/A54 Settings

(ST) 4-2 MiCOM P631, P632, P633, P634

1.2.28 Enabling phase current monitoring (LIM_) 51

1.2.29 Enabling programmable logic (LOGIC) 51

1.3 Function settings 52

1.3.1 Global 52

1.3.1.1 Front port communication blocking (PC) 52

1.3.1.2 Rear port communication blocking (COMM1) 52

1.3.1.3 Rear port communication blocking (COMM2) 52

1.3.1.4 Output relay blocking (OUTP) 53

1.3.1.5 Main global settings (MAIN) 53

1.3.1.6 Setting group selection (GROUP) 59

1.3.1.7 Self testing & diagnostics (CHECK) 59

1.3.1.8 Disturbance recorder settings (OSCIL) 60


ST 1.3.2 Common settings 61

1.3.2.1 Main common settings (MAIN) 61

1.3.2.2 Differential protection common settings (DIFF) 62

1.3.2.3 Restricted earth fault protection common settings (REF_) 63

1.3.2.4 Definite time overcurrent protection common settings (DTOC) 66

1.3.2.5 Inverse time overcurrent protection common settings (IDMT) 66

1.3.2.6 Thermal overload protection common settings (THRM) 67

1.3.2.7 Under/overvoltage protection common settings (V<>) 68

1.3.2.8 Frequency protection common settings (f<>) 68

1.3.2.9 Overfluxing protection common settings (V/f) 69

1.3.2.10 Current transformer supervision common settings (CTS) 69

1.3.2.11 Broken conductor detection common settings (BC_) 69

1.3.2.12 Temperature & DC monitoring settings (LIMIT) 70

1.3.2.13 Phase current monitoring settings (LIM_) 72

1.3.2.14 Programmable logic settings (LOGIC) 74

1.3.3 Setting group SGx (x = 1 to 4) 77

1.3.3.1 Phase reversal logic (MAIN) 78

1.3.3.2 Differential protection (DIFF) 78

1.3.3.3 Restricted earth fault protection (REF_) 81

1.3.3.4 Definite time overcurrent protection (DTOC) 83

1.3.3.5 Inverse time overcurrent protection (IDMT) 90

1.3.3.6 Thermal overload protection (THRM) 97

1.3.3.7 Under/overvoltage protection (V<>) 100


Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-3

1.3.3.8 Frequency protection (f<>) 101

1.3.3.9 Overfluxing protection (V/f) 103

1.3.3.10 Current transformer supervision (CTS) 105

1.3.3.11 Broken conductor detection (BC_) 106

ST
P63x/UK ST/A54 Settings

(ST) 4-4 MiCOM P631, P632, P633, P634

ST
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-5

1. SETTINGS

1.1 Device ID

1.1.1 Device identification (DVICE)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Device ID
DVICE: Device Type As per relay 631 762 1
000 000 Read only
The device type is displayed.
Not
DVICE: 655.35/
As per relay Measured/ 0.01
Software Version Overflow
0.00
002 120 Read only
Firmware version of the device. ST
DVICE: SW Date As per relay 01.01.97 - dd.mm.yy
002 122 Read only
Release date of the firmware.
Not
DVICE: SW Version 655.35/
As per relay Measured/ 0.01
Communic. Overflow
0.00
002 103 Read only
Firmware version of the communication module.
DVICE:
As per relay 0.0 899.9 0.1
Language Version
002 123 Read only
Language version of the device.
DVICE: Text Vers
As per relay 0 255 1
Data Model
002 121 Read only
Using the text replacement feature of S&R-103, the user can change the setting names
and descriptions contained within the data model and download them into the device. The
customized data models have a numeric “Text Version” field that can be updated to
indicate a customized data model. Standard data models have a factory-set default value
of 0.
DVICE:
As per relay 0.000000.0 - -
Serial Number
002 124 Read only
Serial number of the device.
DVICE: Order No. As per relay 00000000 - -
000 001 Read only
Order number of the device
P63x/UK ST/A54 Settings

(ST) 4-6 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DVICE: Order ext.
0 0 999 1
No. 1 (… 27)
See table below for setting addresses.
Order extension numbers of the device. These settings can be modified by sending each
value to the device individually or via the front panel display.
Setting Address Setting Address Setting Address
Order ext. No. 1 000 003 Order ext. No. 10 000 012 Order ext. No. 19 000 021
Order ext. No. 2 000 004 Order ext. No. 11 000 013 Order ext. No. 20 000 022
Order ext. No. 3 000 005 Order ext. No. 12 000 014 Order ext. No. 21 000 023
Order ext. No. 4 000 006 Order ext. No. 13 000 015 Order ext. No. 22 000 024
Order ext. No. 5 000 007 Order ext. No. 14 000 016 Order ext. No. 23 000 025
Order ext. No. 6 000 008 Order ext. No. 15 000 017 Order ext. No. 24 000 026
Order ext. No. 7 000 009 Order ext. No. 16 000 018 Order ext. No. 25 000 027

ST Order ext. No. 8 000 010 Order ext. No. 17 000 019 Order ext. No. 26 000 028
Order ext. No. 9 000 011 Order ext. No. 18 000 020 Order ext. No. 27 000 029

Module A:
Module B:
Module L:
Module N:
DVICE: Module var. slot 1 Module P:
As per relay -
(… 21) Module T:
Module V:
Module X:
Module Y:
Not fitted
See table below for setting addresses. Read only
Stock number of the module fitted in the respective slot.
Setting Address Setting Address Setting Address
Module var. slot 1 086 050 Module var. slot 8 086 057 Module var. slot 15 086 064
Module var. slot 2 086 051 Module var. slot 9 086 058 Module var. slot 16 086 065
Module var. slot 3 086 052 Module var. slot 10 086 059 Module var. slot 17 086 066
Module var. slot 4 086 053 Module var. slot 11 086 060 Module var. slot 18 086 067
Module var. slot 5 086 054 Module var. slot 12 086 061 Module var. slot 19 086 068
Module var. slot 6 086 055 Module var. slot 13 086 062 Module var. slot 20 086 069
Module var. slot 7 086 056 Module var. slot 14 086 063 Module var. slot 21 086 070
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-7

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Version A
DVICE: Module vers. …
As per relay -
Slot 1 (… 21) Version Z
Not Fitted
See table below for setting addresses. Read only
Index letter specifying the version of the module fitted in the respective slot.
Setting Address Setting Address Setting Address
Module vers. Slot 1 086 193 Module vers. Slot 8 086 200 Module vers. Slot 15 086 207
Module vers. Slot 2 086 194 Module vers. Slot 9 086 201 Module vers. Slot 16 086 208
Module vers. Slot 3 086 195 Module vers. Slot 10 086 202 Module vers. Slot 17 086 209
Module vers. Slot 4 086 196 Module vers. Slot 11 086 203 Module vers. Slot 18 086 210
Module vers. Slot 5 086 197 Module vers. Slot 12 086 204 Module vers. Slot 19 086 211
Module vers. Slot 6 086 198 Module vers. Slot 13 086 205 Module vers. Slot 20 086 212
Module vers. Slot 7 086 199 Module vers. Slot 14 086 206 Module vers. Slot 21 086 213

DVICE:
ST
As per relay Not fitted Module A: -
Variant of Module A
086 047 Read only
Stock number of Module A in this design version.
DVICE:
As per relay Not fitted Module L: -
Variant of Module L
086 048 Read only
Stock number of Module L in this design version.
Version A
DVICE: …
As per relay -
Version of Module A Version Z
Not Fitted
086 190 Read only
Index letter specifying the version of Module A.
Version A
DVICE: …
As per relay -
Version of Module L Version Z
Not Fitted
086 191 Read only
Index letter specifying the version of Module L.
DVICE:
As per relay Not fitted Module B: -
Variant of Module B
086 049 Read only
Item number of digital bus Module B in this design version.
Version A
DVICE: …
As per relay -
Version of Module B Version Z
Not Fitted
086 192 Read only
Index letter specifying the version of the digital bus Module B.
P63x/UK ST/A54 Settings

(ST) 4-8 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DVICE: Variant of
As per relay Not fitted Module B: -
Module B (a)
086 046 Read only
Stock number of the analog bus Module B in this design version.
Version A
DVICE: Version of …
As per relay -
Module B (a) Version Z
Not Fitted
086 189 Read only
Index letter specifying the version of the analog bus Module B.
DVICE: MAC
As per relay -
Address Module A
104 061 Read only
MAC address for Ethernet module, where fitted.
ST DVICE: Customer ID
0.00 0.00 99.99 0.01
Data 1 (… 8)
See table below for setting addresses.
Customer configurable fields.
Setting Address Setting Address Setting Address
Customer ID Data 1 000 040 Customer ID Data 4 000 043 Customer ID Data 7 000 046
Customer ID Data 2 000 041 Customer ID Data 5 000 044 Customer ID Data 8 000 047
Customer ID Data 3 000 042 Customer ID Data 6 000 045

DVICE: Device ID 0 0 9999 1


000 035
Customer configurable fields.
DVICE: Substation ID 0 0 9999 1
000 036
Customer configurable fields.
DVICE: Feeder ID 0 0 9999 1
000 037
Customer configurable fields.
DVICE:
0 0 9999 1
Password Level 1
000 048
DVICE:
0 0 9999 1
Password Level 2
000 049
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-9

1.2 Configuration

1.2.1 Local control panel configuration (HMI)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
Reference English
HMI: Language -
Language Reference Language
003 020
Language in which texts will be displayed on the local control panel.
Note: This Technical Manual is based on the 2nd Language or English setting of
this field. Relays with this data model will have a -800 order code in the
model number.
HMI: Decimal Point
Decimal Point -
Decimal Separator Comma
003 021
ST
Character to be used as decimal delimiter on the HMI.
HMI: Password  - -
003 035 Displayed on HMI only (not in setting file).
The password to be used for changing settings from the HMI can be defined here. Refer to
Getting Started - GS for more information on entering/changing the password from the
HMI.
Signals from selection table
HMI: Read Key
Disabled dependent upon relay -
Assignment
configuration.
080 110
Selection of the event recording to be displayed when the read c key is pressed.
Signals from selection table
HMI:
Disabled dependent upon relay -
Operation Panel fct
configuration.
053 007 OP Fig. 83
Definition of the values to be displayed on the Measured Value Panel referred to as the
Operation Panel. This panel will be displayed during normal operation i.e. during normal
load conditions.
Signals from selection table
HMI:
Disabled dependent upon relay -
Overload Panel fct
configuration.
053 005 OP Fig. 85
Definition of the values to be displayed on the Overload Panel. This panel will be
displayed during overload conditions.
Signals from selection table
HMI: Fault Panel fct Disabled dependent upon relay -
configuration.
053 003 OP Fig. 84
Definition of the values to be displayed on the Fault Panel. This panel will be displayed
during and after fault conditions.
P63x/UK ST/A54 Settings

(ST) 4-10 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
HMI:
5s 1s 10 s 1s
Panel Hold-Time
031 075 OP Fig. 83
Setting for the time period for which a panel is displayed before the unit switches to the
next panel. This setting is only relevant if more values are selected for display than can be
shown on the LCD display at one time.
HMI:
60 s 60 s 60000 s 1s
Auto Return Time
003 014 OP Fig. 83
If the user does not press a key on the HMI during this set time period, the
change-enabling function is deactivated and the Operation Panel is called up provided that
values have been assigned to the Operation Panel and that there is no other event.
Blocked/
HMI: Backlight Time 60 s 60000 s 1s
60 s

ST 003 023
If the user does not press a key on the local control panel during this set time period, then
the backlighting of the LCD display is switched off.

1.2.2 Local front port communication configuration (PC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
ALSTOM
PC: Manufacturer ALSTOM D AEG -
ALSTOM D
003 183 OP Fig. 86
Setting for the name of the device manufacturer.
Note: This setting can be changed to ensure compatibility.
PC: Bay Address 1 0 254 1
003 068 OP Fig. 86
Bay and device addresses are used to address the device in communication via the PC
(local front EIA(RS)232 port) interface. An identical setting must be selected for both
addresses.
PC: Relay Address 1 0 255 1
003 069 OP Fig. 86
Bay and device addresses are used to address the device in communication via the PC
(local front EIA(RS)232 port) interface. An identical setting must be selected for both
addresses.
300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
PC: Baud Rate 19.2 kBaud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
115.2 kBaud
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-11

Setting Range
Menu Text Default Setting Step Size
Min. Max.
003 081 OP Fig. 86
Baud rate of the PC (local front EIA(RS)232 port) interface.
Disabled
PC: Parity Bit Even -
Even
003 181 OP Fig. 86
Set the same parity that is set at the interface of the PC connected to the P63x.
None
PC: VDEW Only
None -
Spontan. Sig. Enable VDEW + Selected Sig.
All
003 187 OP Fig. 86
Enable for the transmission of spontaneous signals via the PC interface.
Signals from selection table
PC:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration. ST
003 189 OP Fig. 86
Selection of the spontaneous signals to be transmitted via the PC interface.
Disabled
ASDU 3.1 per IEC
ASDU 3.2 per IEC
ASDU 3.3 per IEC
ASDU 3.4 per IEC
PC: Transm Enab ASDU 9 per IEC
Disabled -
Cycl Dat ILS Message
ASDU 3.1 & 3.4 IEC
ASDU 3.2 & 3.4 IEC
ASDU 3.3 & 3.4 IEC
ASDU 9 & 3.4 per IEC
ASDU 9 & ILS telegr.
003 084 OP Fig. 86
Enable for the cyclic transmission of measured values via the PC interface.
PC:
Disabled -
Cycl. Data ILS Tel.
003 185 OP Fig. 86
Selection of the measured values that are transmitted in a user-defined message via the
PC interface.
PC: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
003 055 OP Fig. 86
A measured voltage value is transmitted via the PC interface if it differs by the set delta
quantity from the last measured value transmitted.
PC: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
003 056 OP Fig. 86
A measured current value is transmitted via the PC interface if it differs by the set delta
quantity from the last measured value transmitted.
P63x/UK ST/A54 Settings

(ST) 4-12 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
PC: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
003 057 OP Fig. 86
The measured frequency value is transmitted via the PC interface if it differs by the set
delta from the last measured value transmitted.
PC:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel
003 155 OP Fig. 86
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
PC: Delta t 1 min 0 min 15 min 1 min
003 058 OP Fig. 86
All measured data are transmitted again through the PC interface after this time period has
elapsed - provided that transmission has not been triggered by the other delta conditions.

ST PC: Time-Out 1 min 1 min 60 min 1 min


003 188 OP Fig. 86
Time-out setting for the PC interface.

1.2.3 Rear port communication configuration (COMM1)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
COMM1: Remote
Disabled Disabled Enabled -
Comms Port1
056 026
Enabling the COMM1 function or disabling it in the configuration. If the function is
disabled, then all associated settings and signals are hidden, with the exception of this
setting.
COMM1: General
No No Yes -
Enable USER
OP Fig. 88,
003 170 89, 90, 91,
92
Disabling or enabling the communication interface.
COMM1:
No No Yes -
IEC870-5 Enabled
003 215 OP Fig. 87
Common settings for enabling all protocols based on IEC 870-5-xxx.
COMM1:
No No Yes -
Addit. -101 Enable
003 216 OP Fig. 87
Enabling additional settings that are relevant for the protocol based on IEC 870-5-101.
COMM1:
No No Yes -
Addit. ILS Enable
003 217 OP Fig. 87
Enabling additional settings that are relevant for the ILS protocol.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-13

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
No No Yes -
MODBUS Enable
003 220 OP Fig. 87
Enabling settings relevant for the MODBUS protocol.
COMM1:
No No Yes -
DNP3 Enable
003 231 OP Fig. 87
Enabling settings relevant for the DNP 3.0 protocol.
COMM1:
No No Yes -
COURIER Enable
103 040 OP Fig. 87
Enabling settings relevant for the Courier protocol.
Signals from selection table
COMM1:
Communicat Protocol
Disabled dependent upon relay
configuration.
- ST
003 167 OP Fig. 87
Select the communication protocol that shall be used for the communication interface.
COMM1: ALSTOM
ALSTOM -
MODBUS Variant ALSTOM D
MODBUS protocol only OP Fig. 91
Select between the ALSTOM D and the ALSTOM variant of the MODBUS protocol.
COMM1: Light Off / Low
Light On / High -
Line Idle State Light On / High
003 165 OP Fig. 88,
89, 90, 91,
92
Setting for the line idle state indication.
300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
COMM1: Baud Rate 19.2 kBaud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
64.0 kBaud
OP Fig. 88,
003 071 89, 90, 91,
92
Baud rate of the communication interface.
Disabled
COMM1: Parity Bit Even Odd -
Even
003 171 OP Fig. 88,
89, 90, 91,
92
Set the same parity that is set at the interface of the control unit connected to the P63x.
P63x/UK ST/A54 Settings

(ST) 4-14 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Dead Time
Yes No Yes -
Monitoring
003 176 OP Fig. 88,
89, 90, 91,
92
The P63x monitors message transmission to make sure that no pause within a message
exceeds 33 bits. This monitoring function can be disabled if it is not required. This setting
is only necessary for modem transmission.
COMM1: Blocked/
25 s 254 s 1s
Mon. Time Polling 3s
003 202 OP Fig. 88,
89, 90, 91,
92
The time between two polling calls from the communication master must be less than the
time set here.

ST COMM1: Octet
Comm. Address
1 0 254 1

003 072 OP Fig. 88,


89, 90, 92
The communication address and the ASDU address are used to identify the device in
communication via the interface. An identical setting must be selected for both addresses.
COMM1: Octet 2
0 0 255 1
Com.Add DNP3
DNP3 protocol only
In the DNP 3.0 protocol, a 16 bit address is used to identify the devices. The address set
here is the higher-order octet. The address set under COMM1: Octet Comm. Address is
the lower-order octet of the DNP address.
COMM1:
No No Yes -
Test Monitor On
OP Fig. 88,
003 166 89, 90, 91,
92
Setting specifying whether data shall be recorded for service activities.
ALSTOM
COMM1:
ALSTOM D AEG -
Manufacturer
ALSTOM D
003 161 IEC 870-5 protocol only OP Fig. 88,
89, 90
Setting for the name of the device manufacturer.
COMM1:
1 0 255 1
Octet Address ASDU
003 073 IEC 870-5 protocol only OP Fig. 88,
89, 90
The communication address and the ASDU address are used to identify the device in
communication via the interface. An identical setting must be selected for both addresses.
None
COMM1: VDEW Only
All -
Spontan. Sig. Enable VDEW + Selected Sig.
All
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-15

Setting Range
Menu Text Default Setting Step Size
Min. Max.
003 177 IEC 870-5 protocol only OP Fig. 88,
89, 90
Enable for the transmission of spontaneous signals via the communication interface.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration.
003 179 IEC 870-5 protocol only OP Fig. 88
Selection of the spontaneous signals to be transmitted via the COMM1 interface.
COMM1: Transm Disabled
Disabled -
Enab Cycl Dat ILS Message
003 074 IEC 870-5 protocol only OP Fig. 88,
89, 90
Enabling of cyclic transmission of measured values via the communication interface.
Signals from selection table
COMM1:
Cycl. Data ILS Tel.
Disabled dependent upon relay - ST
configuration.
003 175 IEC 870-5 protocol only OP Fig. 88,
89, 90
Selection of the measured values transmitted in a user-defined message via the
communication interface.
COMM1: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
003 050 IEC 870-5 protocol only OP Fig. 88,
89, 90
A measured voltage value is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
003 051 IEC 870-5 protocol only OP Fig. 88,
89, 90
A measured current value is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
003 052 IEC 870-5 protocol only OP Fig. 88,
89, 90
The measured frequency is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel
003 150 IEC 870-5 protocol only OP Fig. 88,
89, 90
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
COMM1: Delta t 1 min 0 min 15 min 1 min
003 053 IEC 870-5 protocol only OP Fig. 88,
89, 90
All measured data are transmitted again through the communication interface after this
time period has elapsed - provided that transmission has not been triggered by the other
delta conditions.
P63x/UK ST/A54 Settings

(ST) 4-16 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Blocked/
Blocked 9000 s 1s
Contin. General Scan 10 s
003 077 IEC 870-5 protocol only OP Fig. 88,
89, 90
A continuous or background general scan means that the P63x transmits all settings,
signals, and monitoring signals through the communication interface during slow periods
when there is not much activity. This ensures that there will be data consistency with a
connected control system. The time to be set defines the minimum time difference
between two messages.
COMM1: Comm.
1 Byte 1 Byte 2 Byte 1 Byte
Address Length
003 201 IEC 870-5-101 protocol only OP Fig. 89
Setting for the communication address length.
COMM1:
0 0 255 1
Octet 2 Comm. Addr.
ST 003 200 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the higher-order communication address.
COMM1: Cause W/o Source Address
W/o Source Address -
Transm. Length With Source Address
003 192 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the cause of transmission.
COMM1: Address
1 Byte 1 Byte 2 Byte 1 Byte
Length ASDU
003 193 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the common address for identification of message structures.
COMM1:
0 0 255 1
Octet 2 Addr. ASDU
003 194 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the common higher-order address for identification of message
structures.
COMM1:
2 Byte 2 Byte 3 Byte 1 Byte
Addr. Length Inf.Obj
003 196 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the address for information objects.
COMM1:
0 0 255 1
Oct.3 Addr. Inf.Obj.
003 197 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the higher-order address for information objects.
COMM1:
No No Yes -
Inf.No.<-> Funct.Type
003 195 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether information numbers and function type shall be reversed in the
object address.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-17

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
3 Byte 3 Byte 7 Byte 1 Byte
Time Tag Length
003 198 IEC 870-5-101 protocol only OP Fig. 89
Setting for the time tag length.
COMM1:
Single Channel
ASDU1/ASDU20 Single Channel -
Dual Channel
Conv.
003 190 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether message structure 1 or 20 shall be converted as a single signal
or double signal.
Single Channel
COMM1:
Single Channel Dual Channel -
ASDU2 Conversion
Protection Event
003 191 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether message structure 2 shall be converted as a single signal or ST
double signal.
COMM1:
Yes No Yes -
Initializ Signal
003 199 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether an initialization signal shall be issued.
COMM1:
No No Yes -
Balanced Operation
003 226 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether communication shall be operated in full duplex mode
(simultaneous transmission and reception).
COMM1: Direction Bit 0 0 1 1
003 227 IEC 870-5-101 protocol only OP Fig. 89
Setting for the control direction. As a rule, this value should be set to ‘1’ in the control
center and to ‘0’ in the substation.
COMM1:
0.40 s 0.10 s 2.55 s 0.01 s
Time-out Interval
003 228 IEC 870-5-101 protocol only OP Fig. 89
Setting for the maximum time before the status signal is issued for the acknowledge
command.
Signals from selection table
COMM1: Reg.asg.
Disabled dependent upon relay -
Selec. Cmds
configuration.
003 210 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 00301 to 00400 are assigned to the selected commands.
Assignment is made in the order of selection. This means that the first command is given
the register no. 00301, the second the register no. 00302, etc.
P63x/UK ST/A54 Settings

(ST) 4-18 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Reg.asg. Selec. Sig.
configuration.
003 211 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 10301 to 10400 are assigned to the selected signals.
Assignment is made in the order of selection. This means that the first signal is given the
register no. 10301, the second the register no. 10302, etc.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Reg.asg. Sel. m.val.
configuration.
003 212 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 30301 to 30400 are assigned to the selected measured
values. Assignment is made in the order of selection. This means that the first measured
value is given the register no. 30301, the second the register no. 30302, etc.
Signals from selection table
ST COMM1:
Reg.asg. Sel. Param.
Disabled dependent upon relay -
configuration.
003 213 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 40301 to 40400 are assigned to the selected parameters.
Assignment is made in the order of selection. This means that the first measured value is
given the register no. 40301, the second the register no. 40302, etc.
COMM1:
5s 1s 120 s 1s
Delta t (MODBUS)
003 152 MODBUS protocol only OP Fig. 91
All MODBUS registers are transmitted again through the communication interface after this
time has elapsed.
COMM1: Autom
Disabled Disabled Enabled -
Event Confirm.
003 249 MODBUS protocol only OP Fig. 91
Setting as to whether an event confirmation by the master is necessary to delete an event
from the “event queue“.
COMM1:
0 Bit 0 Bit 254 Bit 1 Bit
Phys. Charact. Delay
003 241 DNP3 protocol only OP Fig. 92
Number of bits to be awaited from receiving the "Requests" to sending the "Response".
COMM1:
40 Bit 0 Bit 254 Bit 1 Bit
Phys. Char. Timeout
003 242 DNP3 protocol only OP Fig. 92
Number of bits that can be missing in the message without receive interrupt.
Never
COMM1: Multi-Frame
Multi-Frame Fragment -
Link Confirm. Mode Fragment
All Frames
003 243 DNP3 protocol only OP Fig. 92
Setting for the acknowledgement mode for confirmation within the link layer.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-19

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
0.10 s 0.05 s 2.54 s 0.01 s
Link Confirm.Timeout
003 244 DNP3 protocol only OP Fig. 92
Setting for the link layer timeout period. Within the link layer, the master needs to
acknowledge (confirm) within this period.
COMM1:
2 1 10 1
Link Max. Retries
003 245 DNP3 protocol only OP Fig. 92
Number of repetitions performed within the link layer after the occurrence of errors during
transmission (such as failure to acknowledge).
COMM1:
5.0 s 0.5 s 25.4 s 0.1 s
Appl Confirm.Timeout
003 246 DNP3 protocol only OP Fig. 92
Setting for the application layer timeout period. Within the application layer, the master
needs to acknowledge (confirm) within this period. ST
COMM1:
60 s 5s 254 s 1s
Appl Need Time Del.
003 247 DNP3 protocol only OP Fig. 92
Within the time interval set here, the slave cyclically issues a clock synchronization request
to the master.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. bin. Inputs
configuration.
003 232 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 1 - binary inputs. Indices are assigned
in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. bin.Outputs
configuration.
003 233 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 10 - binary outputs. Indices are
assigned in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. Analog Inp.
configuration.
003 235 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 30 - analog inputs. Indices are
assigned in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. Analog Outp
configuration.
003 236 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 40 - analog outputs. Indices are
assigned in the sequence of the selection and beginning with 0.
P63x/UK ST/A54 Settings

(ST) 4-20 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Ph-Ph
16 0 255 1
Meas v. (DNP3)
003 250 DNP3 protocol only OP Fig. 92
Initialization value of the thresholds for the transmission of measured data in object 30.
The threshold values may be changed separately by the master for each measured value
by writing to object 34, "Analog Input Reporting Deadband".
COMM1: Phase
5s 1s 120 s 1s
Phase t (DNP3)
003 248 DNP3 protocol only OP Fig. 92
Cycle time of updating the DNP objects 30 (analog inputs).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Command Selection
configuration.
103 042 Courier protocol only OP Fig. 93
ST This setting is used to select from an “m out of n” selection table all the binary commands
(read/write) which are to be made available to the Courier master (e.g. ’Device online’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Signal Selection
configuration.
103 043 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the binary signals (read
only) which are to be made available to the Courier master (e.g. ’Starting I>’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Meas. val. Selection
configuration.
103 044 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the analog
measurements (read only) which are to be made available to the Courier master (e.g.
’Running time’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Parameter Selection
configuration.
103 045 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the analog settings
(read/write) which are to be made available to the Courier master (e.g. ’tI>’).
COMM1:
5s 1s 120 s 1s
Delta t (COURIER)
103 046 Courier protocol only OP Fig. 93
All Courier registers are transmitted again through the communication interface after this
time has elapsed.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-21

1.2.4 2nd rear port communication configuration (COMM2)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings/Configuration
COMM2: Remote
Disabled Disabled Enabled -
Comms Port2
056 057
Enabling the COMM2 function or disabling it in the configuration. If the function is
disabled, then all associated settings and signals are hidden, with the exception of this
setting.
COMM2: General
No No Yes -
Enable USER
103 170 OP Fig. 95
Disabling or enabling the communication interface.
COMM2: Light Off/Low
Light On/High -
Line Idle State Light On/High ST
103 165 OP Fig. 95
Setting for the line idle state indication.
300 Baud
600 Baud
1200 Baud
2400 Baud
COMM2: Baud Rate 19.2 kBaud 4800 Baud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
103 071 OP Fig. 95
Baud rate of the communication interface.
Disabled
COMM2: Parity Bit Even Odd -
Even
103 171 OP Fig. 95
Set the same parity that is set at the interface of the control unit connected to the P63x.
COMM2: Dead Time
Yes No Yes -
Monitoring
103 176 OP Fig. 95
The P63x monitors message transmission to make sure that no pause within a message
exceeds 33 bits. This monitoring function can be disabled if it is not required. This setting
is only necessary for modem transmission.
COMM2:
25 s Blocked/3 s 254 s 1s
Mon. Time Polling
103 202 OP Fig. 95
The time between two polling calls from the communication master must be less than the
time set here.
P63x/UK ST/A54 Settings

(ST) 4-22 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: Octet
1 0 254 1
Comm. Address
103 072 OP Fig. 95
The communication address and the ASDU address are used to identify the device in
communication via the interface. An identical setting must be selected for both addresses.
ALSTOM
COMM2:
ALSTOM D AEG -
Manufacturer
ALSTOM D
103 161 OP Fig. 95
Setting for the name of the device manufacturer.
COMM2:
1 0 255 1
Octet Address ASDU
103 073 OP Fig. 95
The communication address and the ASDU address are used to identify the device in
ST communication via the interface. An identical setting must be selected for both addresses.
None
COMM2: VDEW Only
All -
Spontan. Sig. Enable VDEW + Selected Sig.
All
103 177 OP Fig. 95
Enable for the transmission of spontaneous signals via the communication interface.
Signals from selection table
COMM2:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration.
103 179 OP Fig. 95
Selection of the spontaneous signals to be transmitted via the COMM1 interface.
Disabled
ASDU 3.1 per IEC
ASDU 3.2 per IEC
ASDU 3.3 per IEC
ASDU 3.4 per IEC
COMM2: Transm ASDU 9 per IEC
Disabled -
Enab Cycl Dat ILS Message
ASDU 3.1 & 3.4 IEC
ASDU 3.2 & 3.4 IEC
ASDU 3.3 & 3.4 IEC
ASDU 9 & 3.4 per IEC
ASDU 9 & ILS telegr.
103 074 OP Fig. 95
Enable for the cyclic transmission of measured values via the COMM2 interface.
Signals from selection table
COMM2:
Disabled dependent upon relay -
Cycl. Data ILS Tel.
configuration.
103 175 OP Fig. 95
Selection of the measured values that are transmitted in a user-defined message via the
COMM2 interface.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-23

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
103 050 OP Fig. 95
A measured voltage value is transmitted via the COMM2 interface if it differs by the set
delta quantity from the last measured value transmitted.
COMM2: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
103 051 OP Fig. 95
A measured current value is transmitted via the COMM2 interface if it differs by the set
delta quantity from the last measured value transmitted.
COMM2: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
103 052 OP Fig. 95
The measured frequency value is transmitted via the COMM2 interface if it differs by the
set delta from the last measured value transmitted.
COMM2:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel ST
103 150 OP Fig. 95
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
COMM2: Delta t 1 min 0 min 15 min 1 min
103 053 OP Fig. 95
All measured data are transmitted again through the COMM2 interface after this time
period has elapsed - provided that transmission has not been triggered by the other delta
conditions.

1.2.5 Communication interface IEC 61850 (IEC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IEC: IEC
Disabled Disabled Enabled -
Communication
056 059
Enabling or disabling Ethernet IEC 61850 communication. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
IEC: General Enable
No No Yes -
USER
104 000
Enabling and disabling IEC 61850.
IEC: Don’t Execute
Don’t Execute -
Enable Configuration Execute
104 058
This setting can only be sent individually. In order to maintain consistency of all settings in
the function groups IEC, GSSE and GOOSE, they are all enabled mutually by this
parameter.
P63x/UK ST/A54 Settings

(ST) 4-24 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: Inactivity Timer 15 min 1 min 30 min 1 min
104 050
Additional communication monitor for Ethernet. Should a logged-on client issue no further
request message, after this time period has elapsed that client will automatically be
logged-off, i.e. no further reports will be issued to it. To re-establish communication the
client is required to perform a new log-on procedure with the device (IED).

IEC: Ethernet Media Copper


Copper -
Fiber
104 056
Selecting the physical communication channel from either wired (RJ45) or optical fiber
(ST/SC connector depending on ordering option).

IEC: IED Name Text string up to 20


Template -
characters
104 057
ST Name of the device (IED has server function). This device name serves as device
identification in the IEC 61850 system, it is included in the Logical Device Name in the IEC
data model and must therefore be unambiguous. All devices logged-on to the network
should have non-recurring IED names.
255.255.255
IEC: IP Address 0.0.0.0 0.0.0.0 -
.255
104 001
IP address for the device (IED has server function).
255.255.255
IEC: Subnet Mask 0.0.0.0 0.0.0.0 -
.255
104 005
The subnet mask defines which part of the IP address is addressed by the sub-network
and which part by the device that is logged-on to the network.
IEC:
0 0 4 1
Number of Routes
104 010
Number of network routes, that can be contacted outside of the sub-network, between the
device (IED) and a client or server, communicating with this device, and situated in an
exterior target network.
Such a configuration is required only then when this device must contact an external
client/server direct without having its own network router to convert an IP address.
Addressing of the router and the target network however are always necessary.
Up to four such external target networks can be contacted.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 1 .255
104 011
IP address of network router # 1.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 1 .255
104 015
IP address of target network # 1.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-25

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 2 .255
104 019
IP address of network router # 2.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 2 .255
104 023
IP address of target network # 2.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 3 .255
104 027
IP address of network router # 3.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 3 .255 ST
104 031
IP address of target network # 3.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 4 .255
104 035
IP address of network router # 4.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 4 .255
104 039
IP address of target network # 4.
IEC: SNTP Operating Request from Request from Server
-
Mode Server Broadcast
104 200
Operating mode for the time synchronization telegram. When set to Broadcast
synchronization occurs cyclically with the clock server transmitting a broadcast signal and,
when set to Request from Server each device (IED has client function) individually
requests a synchronization signal after its own cycle time.
IEC: SNTP Poll Cycle
60 s 20 s 600 s 1s
Time
104 201
Device (IED) poll cycle time for time synchronization when operating mode is set to
Request from Server.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
SNTP Server 1 IP .255
104 202
IP address of the first synchronizing clock server.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
SNTP Server 2 IP .255
104 202
IP address of the second synchronizing clock server.
P63x/UK ST/A54 Settings

(ST) 4-26 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: Diff. Local Time 0 -1440 min + 1440 min 1 min
104 206
Time difference between UTC (Coordinated Universal Time/GMT) and local time at
installation site.
IEC:
60 min -1440 min + 1440 min 1 min
Diff. Dayl. Sav. Time
104 207
Time difference when changing to daylight saving time.
IEC: Deadband Value 100 0 10000 1
104 051
Setting to calculate the filter value for all measured value Report Control Blocks (RCB)
except the measured value for energy. Should a change occur in one of the measured
values, which is greater than the filter value, the RCB is again sent to all clients.

ST IEC:
Update Cycle Energy
Blocked 10 3600 1

104 060
Cycle time to send energy value by Report Control Block (RCB). No RCB transmission
with setting to blocked!

1.2.6 Communication interface GOOSE

Setting Range
Menu Text Default Setting Step Size
Min. Max.
GOOSE:
Disabled Enabled/Disabled -
Gen.Obj.Or.SubstEvent
056 068
The parameters of this function group are only active if function group IEC has been
configured and is activated, and if the parameters of this function group have been
activated through the parameter IEC: Enable configuration or by switching the device
off-line/on-line.
GOOSE: General
No No/Yes -
Enable USER
106 001
Enabling and disabling function group GOOSE.
GOOSE:
01-0C-CD-01-00-00 - -
Multic. MAC Address
106 003
Multicast MAC address to provide identification of GOOSE to the receiving clients (IED).
The default MAC address entered is suggested as a standard according to IEC 61850.
The multicast MAC address entered in GOOSE may be modified so as to increase
transmission security or to reduce the number of "GOOSE Messages" to be read by
receiving clients (IED).
GOOSE:
12288 0…16383 1
Application ID
106 004
Application ID of GOOSE being sent by this device (IED).
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-27

Setting Range
Menu Text Default Setting Step Size
Min. Max.
GOOSE: GOOSE ID - - -
106 002
GOOSE ID being sent by this device (IED). GOOSE includes a Dataset with 32 binary and
configurable virtual outputs and 10 two-pole states to the maximum of 10 monitored
external devices.
GOOSE:
0 0…4094 1
VLAN Identifier
106 006
VLAN identifier of GOOSE being sent by this device (IED). The VLAN identifier makes it
possible to have switches in the network filter messages, if the switches support such a
function. Because so-called multicast MAC addresses are applied, switches are unable to
filter messages in the network if they do not include a VLAN identifier.
GOOSE:
4 0…7 1
VLAN Priority
106 007
ST
VLAN priority of GOOSE being sent by this device (IED). The VLAN priority makes it
possible to have switches in the network filter messages, if the switches support such a
function.
GOOSE: GOOSE Signals from selection table
Out 1 (… 32) Disabled dependent upon relay -
fct.assig. configuration.
See table below for setting addresses.
Function assignment of a binary logical state signal to the virtual GOOSE outputs. The
signal configured here is sent with the permanently configured Dataset of GOOSE.
Setting Address Setting Address Setting Address
GOOSE Out 1 GOOSE Out 12 GOOSE Out 23
106 011 106 033 106 055
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 2 GOOSE Out 13 GOOSE Out 24
106 013 106 035 106 057
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 3 GOOSE Out 14 GOOSE Out 25
106 015 106 037 106 059
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 4 GOOSE Out 15 GOOSE Out 26
106 017 106 039 106 061
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 5 GOOSE Out 16 GOOSE Out 27
106 019 106 041 106 063
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 6 GOOSE Out 17 GOOSE Out 28
106 021 106 043 106 065
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 7 GOOSE Out 18 GOOSE Out 29
106 023 106 045 106 067
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 8 GOOSE Out 19 GOOSE Out 30
106 025 106 047 106 069
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 9 GOOSE Out 20 GOOSE Out 31
106 027 106 049 106 071
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 10 GOOSE Out 21 GOOSE Out 32
106 029 106 051 106 073
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 11 GOOSE Out 22
106 031 106 053
Fct.assig. Fct.assig.
P63x/UK ST/A54 Settings

(ST) 4-28 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Blocked dependent upon relay -
1 (… 16) Applic. ID
configuration.
See table below for setting addresses.
Application ID for GOOSE, which is to be received by this device (IED) for the virtual binary
GOOSE input.
Setting Address Setting Address
GOOSE Inp 1 Applic. ID 107 000 GOOSE Inp 12Applic. ID 107 110
GOOSE Inp 2 Applic. ID 107 010 GOOSE Inp 13Applic. ID 107 120
GOOSE Inp 3 Applic. ID 107 020 GOOSE Inp 14 Applic. ID 107 130
GOOSE Inp 4 Applic. ID 107 030 GOOSE Inp 15 Applic. ID 107 140
GOOSE Inp 5 Applic. ID 107 040 GOOSE Inp 16 Applic. ID 107 150
GOOSE Inp 6 Applic. ID 107 050
GOOSE Inp 7 Applic. ID 107 060
ST GOOSE Inp 8 Applic. ID 107 070
GOOSE Inp 9 Applic. ID 107 080
GOOSE Inp 10 Applic. ID 107 090
GOOSE Inp 11 Applic. ID 107 100

Signals from selection table


GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) GOOSE ID
configuration.
See table below for setting addresses.
GOOSE ID for GOOSE, which is to be received by this device (IED) for the virtual binary
GOOSE input.
Setting Address Setting Address
GOOSE Inp 1 GOOSE ID 107 001 GOOSE Inp 12 GOOSE ID 107 111
GOOSE Inp 2 GOOSE ID 107 011 GOOSE Inp 13 GOOSE ID 107 121
GOOSE Inp 3 GOOSE ID 107 021 GOOSE Inp 14 GOOSE ID 107 131
GOOSE Inp 4 GOOSE ID 107 031 GOOSE Inp 15 GOOSE ID 107 141
GOOSE Inp 5 GOOSE ID 107 041 GOOSE Inp 16 GOOSE ID 107 151
GOOSE Inp 6 GOOSE ID 107 051
GOOSE Inp 7 GOOSE ID 107 061
GOOSE Inp 8 GOOSE ID 107 071
GOOSE Inp 9 GOOSE ID 107 081
GOOSE Inp 10 GOOSE ID 107 091
GOOSE Inp 11 GOOSE ID 107 101
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-29

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) DataSetRef
configuration.
See table below for setting addresses.
'DataSetReference' for GOOSE, which is to be received by this device (IED) for the virtual
binary GOOSE input. 'DataSetReference' consists of a chain of characters including the
full path of the state value from the device (IED) with which the P63x corresponds with the
logical device/logical node/data object/data attribute. If a path is made up of more than 20
characters, then only the first 20 characters are to be entered.
Setting Address Setting Address
GOOSE Inp 1 DataSetRef 107 002 GOOSE Inp 12 DataSetRef 107 112
GOOSE Inp 2 DataSetRef 107 012 GOOSE Inp 13 DataSetRef 107 122
GOOSE Inp 3 DataSetRef 107 022 GOOSE Inp 14 DataSetRef 107 132
GOOSE Inp 4 DataSetRef 107 032 GOOSE Inp 15 DataSetRef 107 142
GOOSE Inp 5 DataSetRef 107 042 GOOSE Inp 16 DataSetRef 107 152
GOOSE Inp 6 DataSetRef 107 052
ST
GOOSE Inp 7 DataSetRef 107 062
GOOSE Inp 8 DataSetRef 107 072
GOOSE Inp 9 DataSetRef 107 082
GOOSE Inp 10 DataSetRef 107 092
GOOSE Inp 11 DataSetRef 107 102

Signals from selection table


GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) DataObj Ind
configuration.
See table below for setting addresses.
Data object index of a Dataset for GOOSE, which is to be received by this device (IED) for
the virtual binary GOOSE input. A data object index indicates which data object element in
the Dataset is to be evaluated.
Setting Address Setting Address
GOOSE Inp 1 DataObj Ind 107 003 GOOSE Inp 12 DataObj Ind 107 113
GOOSE Inp 2 DataObj Ind 107 013 GOOSE Inp 13 DataObj Ind 107 123
GOOSE Inp 3 DataObj Ind 107 023 GOOSE Inp 14 DataObj Ind 107 133
GOOSE Inp 4 DataObj Ind 107 033 GOOSE Inp 15 DataObj Ind 107 143
GOOSE Inp 5 DataObj Ind 107 043 GOOSE Inp 16 DataObj Ind 107 153
GOOSE Inp 6 DataObj Ind 107 053
GOOSE Inp 7 DataObj Ind 107 063
GOOSE Inp 8 DataObj Ind 107 073
GOOSE Inp 9 DataObj Ind 107 083
GOOSE Inp 10 DataObj Ind 107 093
GOOSE Inp 11 DataObj Ind 107 103
P63x/UK ST/A54 Settings

(ST) 4-30 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) DatAttr Ind
configuration.
See table below for setting addresses.
Data attribute index of a Dataset for GOOSE, which is to be received by this device (IED)
for the virtual binary GOOSE input. A data attribute index indicates which data attribute
element in the data object is to be evaluated.
Setting Address Setting Address
GOOSE Inp 1 DatAttr Ind 107 004 GOOSE Inp 12 DatAttr Ind 107 114
GOOSE Inp 2 DatAttr Ind 107 014 GOOSE Inp 13 DatAttr Ind 107 124
GOOSE Inp 3 DatAttr Ind 107 024 GOOSE Inp 14 DatAttr Ind 107 134
GOOSE Inp 4 DatAttr Ind 107 034 GOOSE Inp 15 DatAttr Ind 107 144
GOOSE Inp 5 DatAttr Ind 107 044 GOOSE Inp 16 DatAttr Ind 107 154
GOOSE Inp 6 DatAttr Ind 107 054

ST GOOSE Inp 7 DatAttr Ind 107 064


GOOSE Inp 8 DatAttr Ind 107 074
GOOSE Inp 9 DatAttr Ind 107 084
GOOSE Inp 10 DatAttr Ind 107 094
GOOSE Inp 11 DatAttr Ind 107 104

Signals from selection table


GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) default
configuration.
See table below for setting addresses.
Default for the virtual binary GOOSE input. The state of a virtual binary GOOSE input will
revert to default as soon as the continuously monitored communication link to a GOOSE
sending device (IED situated on the opposite side) is in fault or has disappeared
altogether.
Setting Address Setting Address
GOOSE Inp 1 default 107 005 GOOSE Inp 12 default 107 115
GOOSE Inp 2 default 107 015 GOOSE Inp 13 default 107 125
GOOSE Inp 3 default 107 025 GOOSE Inp 14 default 107 135
GOOSE Inp 4 default 107 035 GOOSE Inp 15 default 107 145
GOOSE Inp 5 default 107 045 GOOSE Inp 16 default 107 155
GOOSE Inp 6 default 107 055
GOOSE Inp 7 default 107 065
GOOSE Inp 8 default 107 075
GOOSE Inp 9 default 107 085
GOOSE Inp 10 default 107 095
GOOSE Inp 11 default 107 105
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-31

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) fct.assig.
configuration.
See table below for setting addresses.
Function assignment of the virtual binary GOOSE input to a binary logical state signal on
the device (IED) so that it can be processed further by the protection, control or logic
functions. The signal configured at this point will receive the state of the data attribute, as
configured above, and which was received with the Dataset of GOOSE.
Setting Address Setting Address
GOOSE Inp 1 fct.assig. 107 006 GOOSE Inp 12 fct.assig. 107 116
GOOSE Inp 2 fct.assig. 107 016 GOOSE Inp 13 fct.assig. 107 126
GOOSE Inp 3 fct.assig. 107 026 GOOSE Inp 14 fct.assig. 107 136
GOOSE Inp 4 fct.assig. 107 036 GOOSE Inp 15 fct.assig. 107 146
GOOSE Inp 5 fct.assig. 107 046 GOOSE Inp 16 fct.assig. 107 156
GOOSE Inp 6 fct.assig. 107 056
ST
GOOSE Inp 7 fct.assig. 107 066
GOOSE Inp 8 fct.assig. 107 076
GOOSE Inp 9 fct.assig. 107 086
GOOSE Inp 10 fct.assig. 107 096
GOOSE Inp 11 fct.assig. 107 106

1.2.7 Communication interface GSSE

Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE:
Disabled Enabled/Disabled -
Gen.Subst.Stat.Event
056 060
GSSE:
No No/Yes -
General Enable User
104 049
GSSE:
10 ms 1 ms 60 ms 1 ms
GSSE Min. Cycle
104 052
GSSE:
1s 1s 60 s 1s
GSSE Max. Cycle
104 053
GSSE:
900 0 999 1
GSSE Increment
104 054
GSSE: Promiscuous
Promiscuous -
GSSE Startup Broadcast
104 055
P63x/UK ST/A54 Settings

(ST) 4-32 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
No selection/
GSSE: IED 0
IED 0 -
GSSE IED Name …
IED 32
104 057
No selection/
GSSE: GSSE Out 1 User Bit Pair 01
No selection -
(… 32) BitPair …
User Bit Pair 96
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Out 1 BitPair 104 101 GSSE Out 12 BitPair 104 134 GSSE Out 23 BitPair 104 167
GSSE Out 2 BitPair 104 104 GSSE Out 13 BitPair 104 137 GSSE Out 24 BitPair 104 170
GSSE Out 3 BitPair 104 107 GSSE Out 14 BitPair 104 140 GSSE Out 25 BitPair 104 173

ST GSSE Out 4 BitPair


GSSE Out 5 BitPair
104 110
104 113
GSSE Out 15 BitPair
GSSE Out 16 BitPair
104 143
104 146
GSSE Out 26 BitPair
GSSE Out 27 BitPair
104 176
104 179
GSSE Out 6 BitPair 104 116 GSSE Out 17 BitPair 104 149 GSSE Out 28 BitPair 104 182
GSSE Out 7 BitPair 104 119 GSSE Out 18 BitPair 104 152 GSSE Out 29 BitPair 104 185
GSSE Out 8 BitPair 104 122 GSSE Out 19 BitPair 104 155 GSSE Out 30 BitPair 104 188
GSSE Out 9 BitPair 104 125 GSSE Out 20 BitPair 104 158 GSSE Out 31 BitPair 104 191
GSSE Out 10 BitPair 104 128 GSSE Out 21 BitPair 104 161 GSSE Out 32 BitPair 104 194
GSSE Out 11 BitPair 104 131 GSSE Out 22 BitPair 104 164

Signals from selection table


GSSE: GSSE Out 1
Disabled dependent upon relay -
(… 32) fct.assig.
configuration.
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Out 1 GSSE Out 12 GSSE Out 23
104 102 104 135 104 168
fct.assig. fct.assig. fct.assig.
GSSE Out 2 GSSE Out 13 GSSE Out 24
104 105 104 138 104 171
fct.assig. fct.assig. fct.assig.
GSSE Out 3 GSSE Out 14 GSSE Out 25
104 108 104 141 104 174
fct.assig. fct.assig. fct.assig.
GSSE Out 4 GSSE Out 15 GSSE Out 26
104 111 104 144 104 177
fct.assig. fct.assig. fct.assig.
GSSE Out 5 GSSE Out 16 GSSE Out 27
104 114 104 147 104 180
fct.assig. fct.assig. fct.assig.
GSSE Out 6 GSSE Out 17 GSSE Out 28
104 117 104 150 104 183
fct.assig. fct.assig. fct.assig.
GSSE Out 7 GSSE Out 18 GSSE Out 29
104 120 104 153 104 186
fct.assig. fct.assig. fct.assig.
GSSE Out 8 GSSE Out 19 GSSE Out 30
104 123 104 156 104 189
fct.assig. fct.assig. fct.assig.
GSSE Out 9 GSSE Out 20 GSSE Out 31
104 126 104 159 104 192
fct.assig. fct.assig. fct.assig.
GSSE Out 10 GSSE Out 21 GSSE Out 32
104 129 104 162 104 195
fct.assig. fct.assig. fct.assig.
GSSE Out 11 GSSE Out 22
104 132 104 165
fct.assig. fct.assig.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-33

Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE: GSSE Inp 1
No selection
(… 32) bit pair
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Inp 1 bit pair 105 001 GSSE Inp 12 bit pair 105 056 GSSE Inp 23 bit pair 105 111
GSSE Inp 2 bit pair 105 006 GSSE Inp 13 bit pair 105 061 GSSE Inp 24 bit pair 105 116
GSSE Inp 3 bit pair 105 011 GSSE Inp 14 bit pair 105 066 GSSE Inp 25 bit pair 105 121
GSSE Inp 4 bit pair 105 016 GSSE Inp 15 bit pair 105 071 GSSE Inp 26 bit pair 105 126
GSSE Inp 5 bit pair 105 021 GSSE Inp 16 bit pair 105 076 GSSE Inp 27 bit pair 105 131
GSSE Inp 6 bit pair 105 026 GSSE Inp 17 bit pair 105 081 GSSE Inp 28 bit pair 105 136
GSSE Inp 7 bit pair 105 031 GSSE Inp 18 bit pair 105 086 GSSE Inp 29 bit pair 105 141
GSSE Inp 8 bit pair 105 036 GSSE Inp 19 bit pair 105 091 GSSE Inp 30 bit pair 105 146
GSSE Inp 9 bit pair 105 041 GSSE Inp 20 bit pair 105 096 GSSE Inp 31 bit pair 105 151
GSSE Inp 10 bit pair 105 046 GSSE Inp 21 bit pair 105 101 GSSE Inp 32 bit pair 105 156
ST
GSSE Inp 11 bit pair 105 051 GSSE Inp 22 bit pair 105 106

GSSE: GSSE Inp 1


No selection
(… 32) IED name
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Inp 1 GSSE Inp 12 GSSE Inp 23
105 002 105 057 105 112
IED name IED name IED name
GSSE Inp 2 GSSE Inp 13 GSSE Inp 24
105 007 105 062 105 117
IED name IED name IED name
GSSE Inp 3 GSSE Inp 14 GSSE Inp 25
105 012 105 067 105 122
IED name IED name IED name
GSSE Inp 4 GSSE Inp 15 GSSE Inp 26
105 017 105 072 105 127
IED name IED name IED name
GSSE Inp 5 GSSE Inp 16 GSSE Inp 27
105 022 105 077 105 132
IED name IED name IED name
GSSE Inp 6 GSSE Inp 17 GSSE Inp 28
105 027 105 082 105 137
IED name IED name IED name
GSSE Inp 7 GSSE Inp 18 GSSE Inp 29
105 032 105 087 105 142
IED name IED name IED name
GSSE Inp 8 GSSE Inp 19 GSSE Inp 30
105 037 105 092 105 147
IED name IED name IED name
GSSE Inp 9 GSSE Inp 20 GSSE Inp 31
105 042 105 097 105 152
IED name IED name IED name
GSSE Inp 10 GSSE Inp 21 GSSE Inp 32
105 047 105 102 105 157
IED name IED name IED name
GSSE Inp 11 GSSE Inp 22
105 052 105 107
IED name IED name
P63x/UK ST/A54 Settings

(ST) 4-34 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE: GSSE Inp 1
0
(… 32) default
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Inp 1 default 105 003 GSSE Inp 12 default 105 058 GSSE Inp 23 default 105 113
GSSE Inp 2 default 105 008 GSSE Inp 13 default 105 063 GSSE Inp 24 default 105 118
GSSE Inp 3 default 105 013 GSSE Inp 14 default 105 068 GSSE Inp 25 default 105 123
GSSE Inp 4 default 105 018 GSSE Inp 15 default 105 073 GSSE Inp 26 default 105 128
GSSE Inp 5 default 105 023 GSSE Inp 16 default 105 078 GSSE Inp 27 default 105 133
GSSE Inp 6 default 105 028 GSSE Inp 17 default 105 083 GSSE Inp 28 default 105 138
GSSE Inp 7 default 105 033 GSSE Inp 18 default 105 088 GSSE Inp 29 default 105 143
GSSE Inp 8 default 105 038 GSSE Inp 19 default 105 093 GSSE Inp 30 default 105 148
GSSE Inp 9 default 105 043 GSSE Inp 20 default 105 098 GSSE Inp 31 default 105 153

ST GSSE Inp 10 default 105 048 GSSE Inp 21 default 105 103 GSSE Inp 32 default 105 158
GSSE Inp 11 default 105 053 GSSE Inp 22 default 105 108

GSSE: GSSE Inp 1


Disabled
(… 32) fct.assig.
See table below for setting addresses.
Addres
Setting Address Setting Setting Address
s
GSSE Inp 1 fct.assig. 105 004 GSSE Inp 12 fct.assig. 105 059 GSSE Inp 23 fct.assig. 105 114
GSSE Inp 2 fct.assig. 105 009 GSSE Inp 13 fct.assig. 105 064 GSSE Inp 24 fct.assig. 105 119
GSSE Inp 3 fct.assig. 105 014 GSSE Inp 14 fct.assig. 105 069 GSSE Inp 25 fct.assig. 105 124
GSSE Inp 4 fct.assig. 105 019 GSSE Inp 15 fct.assig. 105 074 GSSE Inp 26 fct.assig. 105 129
GSSE Inp 5 fct.assig. 105 024 GSSE Inp 16 fct.assig. 105 079 GSSE Inp 27 fct.assig. 105 134
GSSE Inp 6 fct.assig. 105 029 GSSE Inp 17 fct.assig. 105 084 GSSE Inp 28 fct.assig. 105 139
GSSE Inp 7 fct.assig. 105 034 GSSE Inp 18 fct.assig. 105 089 GSSE Inp 29 fct.assig. 105 144
GSSE Inp 8 fct.assig. 105 039 GSSE Inp 19 fct.assig. 105 094 GSSE Inp 30 fct.assig. 105 149
GSSE Inp 9 fct.assig. 105 044 GSSE Inp 20 fct.assig. 105 099 GSSE Inp 31 fct.assig. 105 154
GSSE Inp 10 fct.assig. 105 049 GSSE Inp 21 fct.assig. 105 104 GSSE Inp 32 fct.assig. 105 159
GSSE Inp 11 fct.assig. 105 054 GSSE Inp 22 fct.assig. 105 109

1.2.8 Enabling IRIG-B time synchronization (IRIGB)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IRIGB:
Disabled Disabled Enabled -
IRIG-B Time Synch
056 072
Enabling the IRIGB function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
IRIGB: General
No No Yes -
Enable USER
023 200 OP Fig. 97
Disabling and enabling the IRIG-B interface function.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-35

1.2.9 Opto input assignment and operating mode configuration (INP)


The P63x has optical coupler (opto) inputs for processing binary signals from the system.
The number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams in the Installation - IN section.
The P63x identifies the fitted modules during startup. If a given binary I/O module is not
fitted or has fewer binary signal inputs than the maximum number possible at this slot, then
the configuration addresses for the missing binary signal inputs are automatically hidden in
the menu tree.
When configuring binary inputs one should keep in mind the fact that the same function can
be assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals must
persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage shall
be interpreted as the logic ‘1’ signal.

Setting Range
Menu Text Default Setting
Min. Max.
Step Size ST
Settings\Configuration
Signals from selection table
INP: Fct. U 701
Disabled dependent upon relay -
(… 2004) Assign
configuration.
See table below for setting addresses. OP Fig. 98
Assignment of opto inputs to internal relay signals. Any of the available signals can be
configured to any of the opto inputs. The addresses for opto input function assignment are
displayed in the following table:
Setting Address Setting Address Setting Address
Fct. U 701 Assign 152 109 Fct. U 821 Assign 184 082 Fct. U 1409 Assign 190 034
Fct. U 702 Assign 152 112 Fct. U 822 Assign 184 086 Fct. U 1410 Assign 190 038
Fct. U 703 Assign 152 115 Fct. U 823 Assign 184 090 Fct. U 1411 Assign 190 042
Fct. U 704 Assign 152 118 Fct. U 824 Assign 184 094 Fct. U 1412 Assign 190 046
Fct. U 705 Assign 152 121 Fct. U 901 Assign 152 145 Fct. U 1413 Assign 190 050
Fct. U 706 Assign 152 124 Fct. U 902 Assign 152 148 Fct. U 1414 Assign 190 054
Fct. U 801 Assign 184 002 Fct. U 903 Assign 152 151 Fct. U 1415 Assign 190 058
Fct. U 802 Assign 184 006 Fct. U 904 Assign 152 154 Fct. U 1416 Assign 190 062
Fct. U 803 Assign 184 010 Fct. U 1001 Assign 152 163 Fct. U 1417 Assign 190 066
Fct. U 804 Assign 184 014 Fct. U 1002 Assign 152 166 Fct. U 1418 Assign 190 070
Fct. U 805 Assign 184 018 Fct. U 1003 Assign 152 169 Fct. U 1419 Assign 190 074
Fct. U 806 Assign 184 022 Fct. U 1004 Assign 152 172 Fct. U 1420 Assign 190 078
Fct. U 807 Assign 184 026 Fct. U 1005 Assign 152 175 Fct. U 1421 Assign 190 082
Fct. U 808 Assign 184 030 Fct. U 1006 Assign 152 178 Fct. U 1422 Assign 190 086
Fct. U 809 Assign 184 034 Fct. U 1201 Assign 152 199 Fct. U 1423 Assign 190 090
Fct. U 810 Assign 184 038 Fct. U 1202 Assign 152 202 Fct. U 1424 Assign 190 094
Fct. U 811 Assign 184 042 Fct. U 1203 Assign 152 205 Fct. U 1601 Assign 192 002
Fct. U 812 Assign 184 046 Fct. U 1204 Assign 152 208 Fct. U 1602 Assign 192 006
Fct. U 813 Assign 184 050 Fct. U 1401 Assign 190 002 Fct. U 1603 Assign 192 010
Fct. U 814 Assign 184 054 Fct. U 1402 Assign 190 006 Fct. U 1604 Assign 192 014
Fct. U 815 Assign 184 058 Fct. U 1403 Assign 190 010 Fct. U 1605 Assign 192 018
P63x/UK ST/A54 Settings

(ST) 4-36 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Fct. U 816 Assign 184 062 Fct. U 1404 Assign 190 014 Fct. U 1606 Assign 192 022
Fct. U 817 Assign 184 066 Fct. U 1405 Assign 190 018 Fct. U 2001 Assign 153 087
Fct. U 818 Assign 184 070 Fct. U 1406 Assign 190 022 Fct. U 2002 Assign 153 090
Fct. U 819 Assign 184 074 Fct. U 1407 Assign 190 026 Fct. U 2003 Assign 153 093
Fct. U 820 Assign 184 078 Fct. U 1408 Assign 190 030 Fct. U 2004 Assign 153 096

INP: Oper. Mode U Active Low


Active High -
701 (… 2004) Active High
See table below for setting addresses. OP Fig. 98
Selection of the operating mode for the opto inputs. The addresses for opto input
operating mode are displayed in the following table:
Setting Address Setting Address Setting Address
Oper. Mode U 701 152 110 Oper. Mode U 821 184 083 Oper. Mode U 1409 190 035
Oper. Mode U 702 152 113 Oper. Mode U 822 184 087 Oper. Mode U 1410 190 039

ST Oper. Mode U 703


Oper. Mode U 704
152 116
152 119
Oper. Mode U 823
Oper. Mode U 824
184 091
184 095
Oper. Mode U 1411
Oper. Mode U 1412
190 043
190 047
Oper. Mode U 705 152 122 Oper. Mode U 901 152 146 Oper. Mode U 1413 190 051
Oper. Mode U 706 152 125 Oper. Mode U 902 152 149 Oper. Mode U 1414 190 055
Oper. Mode U 801 184 003 Oper. Mode U 903 152 152 Oper. Mode U 1415 190 059
Oper. Mode U 802 184 007 Oper. Mode U 904 152 155 Oper. Mode U 1416 190 063
Oper. Mode U 803 184 011 Oper. Mode U 1001 152 164 Oper. Mode U 1417 190 067
Oper. Mode U 804 184 015 Oper. Mode U 1002 152 167 Oper. Mode U 1418 190 071
Oper. Mode U 805 184 019 Oper. Mode U 1003 152 170 Oper. Mode U 1419 190 075
Oper. Mode U 806 184 023 Oper. Mode U 1004 152 173 Oper. Mode U 1420 190 079
Oper. Mode U 807 184 027 Oper. Mode U 1005 152 176 Oper. Mode U 1421 190 083
Oper. Mode U 808 184 031 Oper. Mode U 1006 152 179 Oper. Mode U 1422 190 087
Oper. Mode U 809 184 035 Oper. Mode U 1201 152 200 Oper. Mode U 1423 190 091
Oper. Mode U 810 184 039 Oper. Mode U 1202 152 203 Oper. Mode U 1424 190 095
Oper. Mode U 811 184 043 Oper. Mode U 1203 152 206 Oper. Mode U 1601 192 003
Oper. Mode U 812 184 047 Oper. Mode U 1204 152 209 Oper. Mode U 1602 192 007
Oper. Mode U 813 184 051 Oper. Mode U 1401 190 003 Oper. Mode U 1603 192 011
Oper. Mode U 814 184 055 Oper. Mode U 1402 190 007 Oper. Mode U 1604 192 015
Oper. Mode U 815 184 059 Oper. Mode U 1403 190 011 Oper. Mode U 1605 192 019
Oper. Mode U 816 184 063 Oper. Mode U 1404 190 015 Oper. Mode U 1606 192 023
Oper. Mode U 817 184 067 Oper. Mode U 1405 190 019 Oper. Mode U 2001 153 088
Oper. Mode U 818 184 071 Oper. Mode U 1406 190 023 Oper. Mode U 2002 153 091
Oper. Mode U 819 184 075 Oper. Mode U 1407 190 027 Oper. Mode U 2003 153 094
Oper. Mode U 820 184 079 Oper. Mode U 1408 190 031 Oper. Mode U 2004 153 097
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-37

1.2.10 Temperature & DC monitoring inputs configuration (RTDmA)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
RTDmA: RTD, Curr.
Disabled Disabled Enabled -
Loop mA IN
056 030
Enabling the RTDmA function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
RTDmA: General
No No Yes -
Enable USER
011 100 OP Fig. 99
Disabling or enabling temperature and DC monitoring inputs.
RTDmA: 0.000 IDC, 0.200 IDC, 0.001 IDC,
0.000 IDC, nom
Enable IDC p.u. nom nom nom
037 190 OP Fig. ST
101, 102
Setting for the minimum current that must flow in order for the P63x to display a measured
value > 0 (zero suppression).
RTDmA: Blocked/
3.0mA 10.0 mA 0.1 mA
IDC< Open Circuit 0.0 mA
037 191 OP Fig.
102
If the input current falls below the set threshold, the P63x will issue an ‘open circuit’ signal.
IDC 1 =
0.000 IDC, nom
Blocked/
RTDmA: IDC 1 IDC 2 … 19 = 0.200 IDC, 0.001 IDC,
0.000 IDC,
(… 20) Blocked nom nom
nom
IDC 20 =
1.200 IDC, nom
See table below for setting addresses. OP Fig.
100, 101,
102
Setting for the input currents IDC xx that will pair up with the linearized values IDC, lin xx to
form the interpolation points of the characteristic for the linearization of direct current
inputs.
Note: IDC 1 and IDC 20 are the two end points of the characteristic and can not
be blocked.
Setting Address Setting Address Setting Address
RTDmA: IDC 1 037 150 RTDmA: IDC 8 037 164 RTDmA: IDC 15 037 178
RTDmA: IDC 2 037 152 RTDmA: IDC 9 037 166 RTDmA: IDC 16 037 180
RTDmA: IDC 3 037 154 RTDmA: IDC 10 037 168 RTDmA: IDC 17 037 182
RTDmA: IDC 4 037 156 RTDmA: IDC 11 037 170 RTDmA: IDC 18 037 184
RTDmA: IDC 5 037 158 RTDmA: IDC 12 037 172 RTDmA: IDC 19 037 186
RTDmA: IDC 6 037 160 RTDmA: IDC 13 037 174 RTDmA: IDC 20 037 188
RTDmA: IDC 7 037 162 RTDmA: IDC 14 037 176
P63x/UK ST/A54 Settings

(ST) 4-38 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDC, lin 1 =
0.000 IDC, nom
Blocked/
RTDmA: IDC, lin 1 IDC, lin 2 … 19 = 0.200 0.001
0.000
(… 20) Blocked IDC, nom IDC, nom
IDC, nom
IDC, lin 20 =
1.200 IDC, nom
See table below for setting addresses. OP Fig.
100, 101,
102
Setting for the input currents IDC, lin xx that will pair up with the linearized values IDC xx to
form the interpolation points of the characteristic for the linearization of direct current
inputs.
Note: IDC, lin 1 and IDC, lin 20 are the two end points of the characteristic and
can not be blocked.
Setting Address Setting Address Setting Address
RTDmA: IDC, lin 1 037 151 RTDmA: IDC, lin 8 037 165 RTDmA: IDC, lin 15 037 179
ST RTDmA: IDC, lin 2 037 153 RTDmA: IDC, lin 9 037 167 RTDmA: IDC, lin 16 037 181
RTDmA: IDC, lin 3 037 155 RTDmA: IDC, lin 10 037 169 RTDmA: IDC, lin 17 037 183
RTDmA: IDC, lin 4 037 157 RTDmA: IDC, lin 11 037 171 RTDmA: IDC, lin 18 037 185
RTDmA: IDC, lin 5 037 159 RTDmA: IDC, lin 12 037 173 RTDmA: IDC, lin 19 037 187
RTDmA: IDC, lin 6 037 161 RTDmA: IDC, lin 13 037 175 RTDmA: IDC, lin 20 037 189
RTDmA: IDC, lin 7 037 163 RTDmA: IDC, lin 14 037 177

RTDmA:
0 -32768 32767 1
Scaled val. IDC, lin1
037 192 OP Fig.
102, 103
Setting for the scaled value of IDC, lin 1.
RTDmA:
1200 -32768 32767 1
Scaled val. IDC, lin20
037 193 OP Fig.
102, 103
Setting for the scaled value of IDC, lin 20.

1.2.11 Output relay assignment and operating mode configuration (OUTP)


The P63x has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams in the
Installation - IN section.
The P63x identifies the fitted modules during startup. If a given binary I/O module is not
fitted or has fewer output relays than the maximum number possible at that slot, then the
configuration addresses for the missing output relays are automatically hidden in the menu
tree.
The contact data for the all-or-nothing relays permits them to be used either as command
relays or as signal relays. One signal can also be assigned to several output relays
simultaneously for the purpose of contact multiplication.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either follower mode or an inverted mode
and in either a latching or non-latching mode. For output relays operating in latching mode,
the operating mode setting also determines when latching will be cancelled.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-39

Note: For relays with make contacts, the “Follower” mode corresponds to
normally-open operation. The “Inverted” mode means that the polarity
of the driving signal is inverted, such that a logic "0" maintains the
relay normally-closed. For relays with changeover contacts, these
more common descriptions are not applicable.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
Signals from selection table
OUTP: Fct. Assignm.
Disabled dependent upon relay -
K 701 (… 2008)
configuration.
See table below for setting addresses. OP Fig.
105
Assignment of functions to output relays.
Setting Address Setting Address Setting Address
Fct. Assignm. K 701 150 145 Fct. Assignm. K 908 150 214 Fct. Assignm. K 1607 171 026
Fct. Assignm. K 702 150 148 Fct. Assignm. K 1001 150 217 Fct. Assignm. K 1608 171 030 ST
Fct. Assignm. K 703 150 151 Fct. Assignm. K 1002 150 220 Fct. Assignm. K 1801 173 002
Fct. Assignm. K 704 150 154 Fct. Assignm. K 1003 150 223 Fct. Assignm. K 1802 173 006
Fct. Assignm. K 705 150 157 Fct. Assignm. K 1004 150 226 Fct. Assignm. K 1803 173 010
Fct. Assignm. K 706 150 160 Fct. Assignm. K 1005 150 229 Fct. Assignm. K 1804 173 014
Fct. Assignm. K 707 150 163 Fct. Assignm. K 1006 150 232 Fct. Assignm. K 1805 173 018
Fct. Assignm. K 708 150 166 Fct. Assignm. K 1007 150 235 Fct. Assignm. K 1806 173 022
Fct. Assignm. K 801 150 169 Fct. Assignm. K 1008 150 238 Fct. Assignm. K 2001 151 201
Fct. Assignm. K 802 150 172 Fct. Assignm. K 1201 151 009 Fct. Assignm. K 2002 151 204
Fct. Assignm. K 901 150 193 Fct. Assignm. K 1202 151 012 Fct. Assignm. K 2003 151 207
Fct. Assignm. K 902 150 196 Fct. Assignm. K 1601 171 002 Fct. Assignm. K 2004 151 210
Fct. Assignm. K 903 150 199 Fct. Assignm. K 1602 171 006 Fct. Assignm. K 2005 151 213
Fct. Assignm. K 904 150 202 Fct. Assignm. K 1603 171 010 Fct. Assignm. K 2006 151 216
Fct. Assignm. K 905 150 205 Fct. Assignm. K 1604 171 014 Fct. Assignm. K 2007 151 219
Fct. Assignm. K 906 150 208 Fct. Assignm. K 1605 171 018 Fct. Assignm. K 2008 151 222
Fct. Assignm. K 907 150 211 Fct. Assignm. K 1606 171 022

Follower
Follower Latching
OUTP: Oper. Mode Follower Rst on Flt
Follower -
K 701 (… 2008) Follower Rst onStart
Inverted
Inverted Latching
See table below for setting addresses. OP Fig.
105
Selection of operating mode for output relays.
Setting Address Setting Address Setting Address
Oper. Mode K 701 150 146 Oper. Mode K 908 150 215 Oper. Mode K 1607 171 027
Oper. Mode K 702 150 149 Oper. Mode K 1001 150 218 Oper. Mode K 1608 171 031
Oper. Mode K 703 150 152 Oper. Mode K 1002 150 221 Oper. Mode K 1801 173 003
Oper. Mode K 704 150 155 Oper. Mode K 1003 150 224 Oper. Mode K 1802 173 007
Oper. Mode K 705 150 158 Oper. Mode K 1004 150 227 Oper. Mode K 1803 173 011
Oper. Mode K 706 150 161 Oper. Mode K 1005 150 230 Oper. Mode K 1804 173 015
P63x/UK ST/A54 Settings

(ST) 4-40 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Oper. Mode K 707 150 164 Oper. Mode K 1006 150 233 Oper. Mode K 1805 173 019
Oper. Mode K 708 150 167 Oper. Mode K 1007 150 236 Oper. Mode K 1806 173 023
Oper. Mode K 801 150 170 Oper. Mode K 1008 150 239 Oper. Mode K 2001 151 202
Oper. Mode K 802 150 173 Oper. Mode K 1201 151 010 Oper. Mode K 2002 151 205
Oper. Mode K 901 150 194 Oper. Mode K 1202 151 013 Oper. Mode K 2003 151 208
Oper. Mode K 902 150 197 Oper. Mode K 1601 171 003 Oper. Mode K 2004 151 211
Oper. Mode K 903 150 200 Oper. Mode K 1602 171 007 Oper. Mode K 2005 151 214
Oper. Mode K 904 150 203 Oper. Mode K 1603 171 011 Oper. Mode K 2006 151 217
Oper. Mode K 905 150 206 Oper. Mode K 1604 171 015 Oper. Mode K 2007 151 220
Oper. Mode K 906 150 209 Oper. Mode K 1605 171 019 Oper. Mode K 2008 151 223
Oper. Mode K 907 150 212 Oper. Mode K 1606 171 023

1.2.12 Analog output channel configuration (mA_OP)

Setting Range
ST Menu Text Default Setting
Min. Max.
Step Size

Settings\Configuration
mA_OP: Current
Disabled Disabled Enabled -
Loop mA outp
056 020
Enabling the mA_OP function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
mA_OP: General
No No Yes -
Enable USER
031 074 OP Fig.
107
Disabling and enabling the measured data output function.
Signals from selection table
mA_OP:
Disabled dependent upon relay -
Fct. Assignm. BCD
configuration.
053 002 OP Fig.
110
Selection of the measured value to be transmitted in BCD-coded form.
mA_OP: Hold Time Blocked/
0.10 s 10.00 s 0.01 s
Output BCD 0.10 s
010 010 OP Fig.
110
Setting for the time period for transmission of the selected measured value in BCD-coded
form.
mA_OP: Scale BCD 1.00 0.01 100.00 0.01
016 082 OP Fig.
110
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-41

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Scaling factor setting for the measured value to be transmitted in BCD-coded form. The
scaling factor is calculated according to the following formula:
M x,max
scaling factor =
M x,scal
Where:
M x,scal : Scaled measured value
M x,max : Maximum transmitted value for the selected measured value

Signals from selection table


mA_OP:
Disabled dependent upon relay -
Fct. Assignm. A-1
configuration.
053 000 OP Fig.
112
Signals from selection table
mA_OP:
Disabled dependent upon relay -
Fct. Assignm. A-2
configuration. ST
053 001
Selection of the measured value to be transmitted in analog form.
mA_OP: Blocked/
0.1 s 10.00 s 0.01 s
Hold Time Output A-1 0.10 s
010 114 OP Fig.
112
mA_OP: Blocked/
0.1 s 10.00 s 0.01 s
Hold Time Output A-2 0.10 s
010 115
Setting for the time period for output of the selected measured value.
mA_OP:
0.000 0.000 1.000 0.001
Scaled Min. val. A-1
037 104 OP Fig.
112
mA_OP:
0.000 0.000 1.000 0.001
Scaled Min. val. A-2
037 110 OP Fig.
112
Setting for the minimum scaled measured value to be output. The value to be set is
calculated according to the following formula:
M x,min
M x,scal,min =
M x,RL
Where:
Mx,min : Minimum transmitted value of the selected measured value
M x,RL : Range limit of the selected measured value

mA_OP: Blocked/
Blocked 1.000 0.001
Scaled Knee val. A-1 0.000
037 105 OP Fig.
112
P63x/UK ST/A54 Settings

(ST) 4-42 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
mA_OP: Blocked/
Blocked 1.000 0.001
Scaled Knee val. A-2 0.000
037 111 OP Fig.
112
Setting for the scaled measured value for output that defines the knee point of the
characteristic. The value to be set is calculated according to the following formula:
M x,knee
M x,scal,knee =
M x,RL
Where:
M x,knee : Knee point value to be transmitted for selected measured value

M x,RL : Range limit value of selected measured value

mA_OP:
1.000 0.000 1.000 0.001
Scaled Max. val. A-1

ST 037 106 OP Fig.


112
mA_OP:
1.000 0.000 1.000 0.001
Scaled Max. val. A-2
037 112 OP Fig.
112
Setting for the maximum scaled measured value to be output. The value to be set is
calculated according to the following formula:
M x,max
M x,scal,max =
M x,RL

Where:
Mx,max : Maximum value to be transmitted for selected measured value
M x,RL : Range limit value of selected measured value

mA_OP:
0.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Min. val. A-1
037 107 OP Fig.
112
mA_OP:
0.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Min. val. A-2
037 113 OP Fig.
112
Setting for the output current that is output for measured values less than or equal to the
minimum measured value to be transmitted.
mA_OP: AnOut Knee Blocked/
Blocked 20.00 mA 0.01 mA
Point A-1 0.00 mA
037 108 OP Fig.
112
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-43

Setting Range
Menu Text Default Setting Step Size
Min. Max.
mA_OP: AnOut Knee Blocked/
Blocked 20.00 mA 0.01 mA
Point A-2 0.00 mA
037 114 OP Fig.
112
Setting for the output current that is output if the measured value is in the knee point of the
characteristic.
mA_OP:
20.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Max. val. A-1
037 109 OP Fig.
112
mA_OP:
20.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Max. val. A-2
037 115 OP Fig.
112
Setting for the output current that is output for measured values smaller than or equal to
the maximum measured value to be transmitted. ST
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 1
037 120 OP Fig.
110, 112
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 2
037 121 OP Fig.
110, 112
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 3
037 122 OP Fig.
110, 112
Measured values of external devices, which must be scaled to 0 to 100%, can be output.

1.2.13 LED assignment and operating mode configuration (LED)


The P63x has a total of 17 LED indicators for display of binary signals. The following table
provides an overview of the operation of the LEDs.

LED Label Configuration


Not configurable. H 1 signals the operational readiness
H1 HEALTHY
of the device (supply voltage present).
Not configurable. H 17 signals the fact that the user is
H 17 EDIT MODE in the ‘EDIT MODE’. In this mode, parameter values
can be changed.
Permanently assigned to the function MAIN:
H2 OUT OF SERVICE
Blocked/Faulty.
Permanently assigned to the function CHECK: Alarm
H3 ALARM
(LED).
Default assignment to the function MAIN: Gen Trip
H4 TRIP
Signal.
The user has the option of assigning functions to these
H 5 to H 16
LED indicators.

The arrangement of the LED indicators on the HMI panel is illustrated in the dimensional
drawings of the Installation - IN section.
P63x/UK ST/A54 Settings

(ST) 4-44 MiCOM P631, P632, P633, P634

An operating mode can be defined for each LED indicator. Depending on the selected
operating mode, the LED will operate in either “Follower” mode or “Inverted” mode as either
latching or non-latching indicators. For LED indicators operating in latching mode, the
operating mode setting also determines when latching will be cancelled.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LED: MAIN
MAIN Blocked/Faulty -
Fct. Assignm. H 2 Blocked/Faulty
085 001 Read only OP Fig.
113
Display of the function assigned to LED indicator H 2 (‘OUT OF SERVICE’).
The MAIN: Blocked/Faulty function is permanently assigned to this LED.
LED: CHECK Alarm
CHECK Alarm (LED) -
Fct. Assignm. H 3 (LED)
085 004 Read only OP Fig.
113
ST Display of the function assigned to LED indicator H 3 (‘ALARM’). The CHECK: Alarm
(LED) function is permanently assigned to this LED.
Signals from selection table
LED: MAIN Gen Trip
dependent upon relay -
Fct. Assignm. H 4 Signal
configuration.
085 007 OP Fig.
113
Default assignment to the function MAIN: Gen Trip Signal.
Signals from selection table
LED: Fct. Assignm. Disabled dependent upon relay -
H 5 (… 16) configuration.
See table below for setting addresses. OP Fig.
113
Assignment of functions to LED indicators.
Setting Address Setting Address Setting Address
Fct. Assignm. H 5 085 010 Fct. Assignm. H 9 085 022 Fct. Assignm. H 13 085 034
Fct. Assignm. H 6 085 013 Fct. Assignm. H 10 085 025 Fct. Assignm. H 14 085 037
Fct. Assignm. H 7 085 016 Fct. Assignm. H 11 085 028 Fct. Assignm. H 15 085 040
Fct. Assignm. H 8 085 019 Fct. Assignm. H 12 085 031 Fct. Assignm. H 16 085 043

LED:
Follower Follower -
Operating Mode H 2
085 002 Read only OP Fig.
113
LED:
Follower Follower -
Operating Mode H 3
085 005 Read only OP Fig.
113
Follower
Follower Latching
LED: Follower Rst on Flt
Follower Rst on Flt -
Operating Mode H 4 Follower Rst onStart
Inverted
Inverted Latching
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-45

Setting Range
Menu Text Default Setting Step Size
Min. Max.
085 008
The TRIP LED may be set as a “Follower” or “Inverted” mode of operation. It can also be
set for latching. Reset of latching may be performed either via a user command,
automatically at the onset of the next fault or at the start of a system disturbance (any
protection element start).
LED: Operating Mode As per ‘LED: Operating
Follower -
H 5 (… 16) Mode H 4’
See table below for setting addresses. OP Fig.
113
Selection of operating mode for LED indicators.
Setting Address Setting Address Setting Address
Operating Mode H 5 085 011 Operating Mode H 9 085 023 Operating Mode H 13 085 035
Operating Mode H 6 085 014 Operating Mode H 10 085 026 Operating Mode H 14 085 038
Operating Mode H 7 085 017 Operating Mode H 11 085 029 Operating Mode H 15 085 041
Operating Mode H 8 085 020 Operating Mode H 12 085 032 Operating Mode H 16 085 044 ST
1.2.14 Communication and time synchronization channel assignment (MAIN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
MAIN: Chann Assign. COMM1->Chann.1, COMM1->Chann.1, (2-2)
-
Comm1/2 (2-2) COMM1->Chann.2, (2-1)
OP Fig.
003 169
137
Assignment of “logical” communications function groups COMM1 and COMM2 to physical
rear communications ports. This setting allows the main rear SCADA port (COMM1) to be
selected as either fiber or EIA(RS)485, with COMM2 assigned to the other physical port
where the two rear port -922 or -924 order options are present.
COMM1
MAIN: Prim.Source COMM2/PC
COMM1 -
TimeSync IRIG-B
Minute-pulse input
103 210
Selection of the primary time synchronization source. The source is monitored for valid
time synchronization commands and will be used whenever available.
MAIN: BackupSource As per ‘MAIN: Prim.Source
COMM2/PC -
TimeSync TimeSync’
103 211
Selection of a backup time synchronization source. This source will be used when the
primary source above is not available.
MAIN: Blocked /
Blocked 60 min 1 min
Time Sync. Time-Out 1 min
103 212
Time out setting for valid time synchronization commands. If set to “Blocked”, primary
source only will be used.
P63x/UK ST/A54 Settings

(ST) 4-46 MiCOM P631, P632, P633, P634

1.2.15 Disturbance recorder channel configuration (OSCIL)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
OSCIL:
Current IA, end a Current IA, end a -
Dist Rec Analog Ch1
035 160 Read only OP Fig.
157
OSCIL:
Current IB, end a Current IB, end a -
Dist Rec Analog Ch2
035 161 Read only OP Fig.
157
OSCIL:
Current IC, end a Current IC, end a -
Dist Rec Analog Ch3
035 162 Read only OP Fig.
157
ST OSCIL: Current IN, end a
Current IY, end a -
Dist Rec Analog Ch4 Current IY, end a
035 163 OP Fig.
157
OSCIL:
Current IA, end b Current IA, end b -
Dist Rec Analog Ch5
035 164 Read only OP Fig.
157
OSCIL:
Current IB, end b Current IB, end b -
Dist Rec Analog Ch6
035 165 Read only OP Fig.
157
OSCIL:
Current IC, end b Current IC, end b -
Dist Rec Analog Ch7
035 166 Read only OP Fig.
157
OSCIL: Current IN, end b
Current IY, end b -
Dist Rec Analog Ch8 Current IY, end b
035 167 OP Fig.
157
OSCIL:
Voltage V Voltage V -
Dist Rec Analog Ch9
035 168 Read only OP Fig.
157
OSCIL: Dist Rec
Current IA, end c Current IA, end c -
Analog Ch10
035 169 Read only OP Fig.
157
OSCIL: Dist Rec
Current IB, end c Current IB, end c -
Analog Ch11
035 170 Read only OP Fig.
157
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-47

Setting Range
Menu Text Default Setting Step Size
Min. Max.
OSCIL: Dist Rec
Current IC, end c Current IC, end c -
Analog Ch12
035 171 Read only OP Fig.
157
OSCIL: Dist Rec Current IN, end c
Current IY, end c -
Analog Ch13 Current IY, end c
035 172 OP Fig.
157
OSCIL: Dist Rec
Current IA, end d Current IA, end d -
Analog Ch14
035 173 Read only OP Fig.
157
OSCIL: Dist Rec
Current IB, end d Current IB, end d -
Analog Ch15
035 174 Read only OP Fig.
157 ST
OSCIL: Dist Rec
Current IC, end d Current IC, end d -
Analog Ch16
035 175 Read only OP Fig.
157
The user specifies the channel on which each physical variable is recorded.

1.2.16 Cancelling a protection function


The user can adapt the device to the requirements of a particular high-voltage system by
including the relevant protection functions in the device configuration and canceling all others
(removing them from the device configuration).
The following conditions must be met before canceling a protection function:

• The protection function in question must be disabled

• None of the functions of the protection function to be cancelled may be assigned to a


binary input

• None of the signals of the protection function may be assigned to a binary output or an
LED indicator

• None of the signals of the protection function may be linked to other signals by way of an
‘m out of n’ parameter
The protection function to which a setting, a signal, or a measured value belongs is defined
by the function group designation (example: ‘LIMIT’).

1.2.17 Enabling differential protection (DIFF)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
DIFF:
Disabled Disabled Enabled -
Differential PR (87)
056 027 OP Fig. 1
Enabling the DIFF function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
P63x/UK ST/A54 Settings

(ST) 4-48 MiCOM P631, P632, P633, P634

1.2.18 Enabling restricted earth fault protection (REF_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
REF_1:
Disabled Disabled Enabled -
Restricted EF_1 (64)
056 037 OP Fig. 14
REF_2:
Disabled Disabled Enabled -
Restricted EF_2 (64)
056 038 OP Fig. 14
REF_3:
Disabled Disabled Enabled -
Restricted EF_3 (64)
056 039 OP Fig. 14
Enabling the REF_1 to REF_3 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
ST Note: Restricted earth fault protection is not available in the P631. Function
group REF_3 is available with the P633 and the P634 only.

1.2.19 Enabling definite time overcurrent protection (DTOC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
DTOC1:
Disabled Disabled Enabled -
I> Winding 1 (50/51)
056 031 OP Fig. 22
DTOC2:
Disabled Disabled Enabled -
I> Winding 2 (50/51)
056 032 OP Fig. 22
DTOC3:
Disabled Disabled Enabled -
I> Winding 3 (50/51)
056 053 OP Fig. 22
Enabling the DTOC1 to DTOC3 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
Note: Function group DTOC3 is available with the P633 and the P634 only.

1.2.20 Enabling inverse time overcurrent protection (IDMT)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IDMT1:
Disabled Disabled Enabled -
IDMT Winding 1 (51)
056 051 OP Fig. 29
IDMT2:
Disabled Disabled Enabled -
IDMT Winding 2 (51)
056 061 OP Fig. 29
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-49

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3:
Disabled Disabled Enabled -
IDMT Winding 3 (51)
056 071 OP Fig. 29
Enabling the IDMT1 to IDMT3 functions or disabling them in the configuration. If a function
group is disabled, then all associated settings and signals are hidden, with the exception of
this setting.
Note: Function group IDMT3 is available with the P633 and the P634 only.

1.2.21 Enabling thermal overload protection (THRM)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
THRM1:
Disabled Disabled Enabled -
Thermal Oload 1 (49)
056 054 OP Fig. 41
ST
THRM2:
Disabled Disabled Enabled -
Thermal Oload 2 (49)
056 055 OP Fig. 41
Enabling the THRM1 to THRM2 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
Note: Function group THRM2 is available with the P633 and the P634 only.

1.2.22 Enabling under/overvoltage protection (V<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
V<>: Under Over
Disabled Disabled Enabled -
Volts V<>
056 010 OP Fig. 47
Enabling the V<> function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
Note: Time-voltage protection is not available in the P631.

1.2.23 Enabling frequency protection (f<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
f<>:
Disabled Disabled Enabled -
Frequency Prot. (81)
056 033 OP Fig. 50
Enabling the f<> function or disabling it in the configuration. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
Note: Over/underfrequency is not available in the P631.
P63x/UK ST/A54 Settings

(ST) 4-50 MiCOM P631, P632, P633, P634

1.2.24 Enabling overfluxing protection (V/f)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
V/f:
Disabled Disabled Enabled -
Overfluxing V/f (24)
056 056 OP Fig. 54
Enabling the V/f function or disabling it in the configuration. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
Note: Overfluxing protection is not available in the P631.

1.2.25 Enabling current transformer supervision (CTS)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
ST CTS: CT Supervision Disabled Disabled Enabled -
056 077 OP Fig. 64
Enabling the CTS function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
Note: CTS is only available if the DSP coprocessor is selected as an order option.

1.2.26 Enabling broken conductor detection (BC_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
BC_1:
Disabled Disabled Enabled -
Broken Conductor 1
056 073 OP Fig. 62
BC_2:
Disabled Disabled Enabled -
Broken Conductor 2
056 074 OP Fig. 62
BC_3:
Disabled Disabled Enabled -
Broken Conductor 3
056 075 OP Fig. 62
BC_4:
Disabled Disabled Enabled -
Broken Conductor 4
056 076 OP Fig. 62
Enabling the broken conductor detection function or disabling it in the configuration. If the
function is disabled, then all associated settings and signals are hidden, with the exception
of this setting.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-51

1.2.27 Enabling temperature & DC monitoring (LIMIT)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LIMIT:
Disabled Disabled Enabled -
Limit Thresholds I<>
056 025
Enabling the LIMIT function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.

1.2.28 Enabling phase current monitoring (LIM_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LIM_1:
Limits I<> Winding 1
Disabled Disabled Enabled - ST
056 042
LIM_2:
Disabled Disabled Enabled -
Limits I<> Winding 2
056 043
LIM_3:
Disabled Disabled Enabled -
Limits I<> Winding 3
056 050
Enabling the LIM_1 to LIM_3 functions or disabling them in the configuration. If a function
group is disabled, then all associated settings and signals are hidden, with the exception of
this setting.
Note: Function group LIM_3 is available with the P633 and the P634 only.

1.2.29 Enabling programmable logic (LOGIC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LOGIC:
Programmable Disabled Disabled Enabled -
LOGIC
056 017
Enabling the LOGIC function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
P63x/UK ST/A54 Settings

(ST) 4-52 MiCOM P631, P632, P633, P634

1.3 Function settings

1.3.1 Global

1.3.1.1 Front port communication blocking (PC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
PC:
No No Yes -
Command Blocking
003 182 OP Fig. 86
When command blocking is activated, commands are rejected at the PC interface.
PC:
No No Yes -
Sig/meas. val. Block
003 086 OP Fig. 86

ST When signal and measured value blocking is activated, no signals or measured data are
transmitted through the PC interface.

1.3.1.2 Rear port communication blocking (COMM1)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
COMM1: USER
Yes No Yes -
Command Block
003 172 OP Fig. 87
When command blocking is activated, commands are rejected at the communication
interface.
COMM1: USER
No No Yes -
Sig/meas Block
003 076 OP Fig. 88,
89, 90
When signal and measured value blocking is activated, no signals or measured data are
transmitted through the communication interface.

1.3.1.3 Rear port communication blocking (COMM2)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
COMM2: USER
Yes No Yes -
Command Block
103 172
When command blocking is activated, commands are rejected at the communication
interface.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-53

Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: USER
No No Yes -
Sig/meas Block
103 076
When signal and measured value blocking is activated, no signals or measured data are
transmitted through the communication interface.

1.3.1.4 Output relay blocking (OUTP)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
OUTP:
USER Outp Rel No No Yes -
Block
021 014 OP Fig.
105 ST
When this blocking is activated, all output relays are blocked.

1.3.1.5 Main global settings (MAIN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
MAIN: No Yes
No (Disabled) -
Protection Enabled (Disabled) (Enabled)
003 030 OP Fig.
129
Switching the device off-line or on-line. Parameters marked ‘off’ in the Address List can
only be changed when the device is off-line.
MAIN:
No No Yes -
USER Test Mode
003 012 OP Fig.
141
When the test mode is activated, signals or measured data for PC and communication
interfaces are labeled ‘test mode’.
50 Hz
MAIN: Frequency fn 50 Hz -
60 Hz
010 030 OP Fig. 53
Setting for the nominal frequency of the protected system.
MAIN: A–B–C
A–B–C -
Phase Rotation A–C–B
010 049 OP Fig. 5
Setting for the phase rotation of the protection system, either A-B-C (standard) or A-C-B
(reverse).
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end a
019 020 OP Fig.
119
P63x/UK ST/A54 Settings

(ST) 4-54 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end b
019 021 OP Fig.
119
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end c
019 022 OP Fig.
119
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end d
019 026 OP Fig.
119
Setting for the primary nominal current of the main current transformer (phase currents) of
end a, b, c or d.
MAIN:
ST In CT.Y prim, end a
200 A 1A 50000 A 1A

019 027 OP Fig.


121
MAIN:
200 A 1A 50000 A 1A
In CT.Y prim, end b
019 028 OP Fig.
121
MAIN:
200 A 1A 50000 A 1A
In CT.Y prim, end c
019 029 OP Fig.
121
Setting for the primary nominal current of the main current transformer at the
neutral-point-to-earth connection.
MAIN: Vn V.T. prim. 100.0 kV 0.1 kV 1500.0 kV 0.1 kV
010 002 OP Fig.
124
Setting for the primary nominal voltage of the system transformer.
MAIN:
1A 1A 5A 4A
In Device, end a
010 024 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
In Device, end b
010 025 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
In Device, end c
010 029 OP Fig.
115, 116
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-55

Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
1A 1A 5A 4A
In Device, end d
010 047 OP Fig.
115, 116
Setting for the secondary nominal current of the system transformer for measurement of
the phase currents of ends a, b, c and d. This current corresponds to the nominal current
of the device.
MAIN:
1A 1A 5A 4A
IY, nom device, end a
010 142 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
IY, nom device, end b
010 143 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
ST
IY, nom device, end c
010 144 OP Fig.
115, 116
Setting for the secondary nominal current of the system transformer for measurement of
the neutral-point-to-earth connection current of ends a, b, and c.
MAIN: Vn VT. Sec. 100 V 50 V 130 V 1V
010 009 OP Fig.
124
Setting for the secondary nominal voltage of the system transformer for voltage
measurement.
MAIN: Standard
Standard -
CT Orientation Iph, a Reversed
010 140 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, b Reversed
010 150 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, c Reversed
010 160 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, d Reversed
010 170 OP Fig.
115, 116
Instead of accounting for connection reversal applied to one end in the settings for DIFF:
Vector Grp. ends z1-z2 (where z1-z2 stands for b-a, c-a or d-a), it is possible to account for
it in the settings for connection of the measuring circuits. The connection of the
neutral/point current circuits, ends a to d, is set here as Standard if in accordance with the
connection scheme shown in the Installation - IN section, else as Reversed.
P63x/UK ST/A54 Settings

(ST) 4-56 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN: Standard
Standard -
CT Orientation IY, a Reversed
010 141 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation IY, b Reversed
010 151 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation IY, c Reversed
010 161 OP Fig.
115, 116
Connection reversal applied to one end is accounted for it in the settings for connection of
the measuring circuits. The connection of the wye/neutral current circuits, ends a to c, is
set here as Standard if in accordance with the connection scheme shown in the Installation
ST - IN section, else as Reversed.
MAIN: Minimum Iph
0.00 In 0.00 In 0.20 In 0.01 In
Meas’mt
011 030 OP Fig.
119, 123
Setting for the minimum current that must be exceeded in order for the measured operating
values of the phase currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum I2 Meas’mt
011 048
Setting for the minimum current that must be exceeded in order for the calculated values of
the negative sequence currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum I1 Meas’mt
011 058
Setting for the minimum current that must be exceeded in order for the calculated values of
the positive sequence currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum IN Meas’mt
011 031 OP Fig.
121, 122,
123
Setting for the minimum current that must be exceeded in order for the measured operating
value of the residual current to be displayed.
MAIN: 0.000 0.200 0.001
0.000 IN, nom
Minimum IY Meas’mt IN, nom IN, nom IN, nom
011 036 OP Fig.
121
Setting for the minimum current that must be exceeded in order for the measured operating
values of the currents in the neutral-point-to-earth connection to be displayed.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-57

Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
0.00 Vn 0.00 Vn 0.20 Vn 0.01 Vn
Minimum V Meas’mt
011 032 OP Fig.
124
Setting for the minimum voltage that must be exceeded in order for the measured
operating values of the voltage to be displayed.
MAIN:
15.0 min 0.1 min 60.0 min 0.1 min
Time Const Iph Dem.
010 113 OP Fig.
119, 120
Setting for the time after which the delayed maximum current display shall reach 95% of
the maximum current IP, max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 1
configuration.
021 021 OP Fig. ST
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 2
configuration.
021 022 OP Fig.
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 3
configuration.
021 048 OP Fig.
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 4
configuration.
021 049 OP Fig.
131
Assignment of functions that will be blocked together when blocking input 1, 2, 3 or 4 is
activated e.g. for blocking input 1 (MAIN: Blocking 1 EXT).
MAIN: Trip Cmd.
No No Yes -
Block USER
021 012 OP Fig.
135
Blocking of the trip commands from the local control panel.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.1
configuration.
021 001 OP Fig.
135
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.2
configuration.
021 002 OP Fig.
135
P63x/UK ST/A54 Settings

(ST) 4-58 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.3
configuration.
021 046 OP Fig.
135
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.4
configuration.
021 047 OP Fig.
135
Assignment of the signals that trigger Trip Command 1, 2, 3 or 4.
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 1
021 003 OP Fig.
135
ST MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 2
021 004 OP Fig.
135
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 3
021 032 OP Fig.
135
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 4
021 033 OP Fig.
135
Setting for the minimum duration of Trip Command 1, 2, 3 or 4.
MAIN:
No No Yes -
Latching trip cmd. 1
021 023 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 2
021 024 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 3
021 025 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 4
021 026 OP Fig.
135
Specification as to whether Trip Command 1, 2, 3 or 4 should latch.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-59

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct Assign Fault
configuration.
021 031 OP Fig.
132
Selection of the signals whose appearance shall result in a ‘Blocked/Faulty’ indication.
Signals that lead to blocking of the device are not configurable and always result in a
‘Blocked/Faulty’ indication.

1.3.1.6 Setting group selection (GROUP)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
GROUP:
No No Yes -
Control via USER
ST
003 100 OP Fig.
142
If setting group selection is to be handled from the integrated local control panel rather
than via the binary signal inputs, choose the ‘Yes’ setting.
Setting Group SG1
GROUP: Setting Grp Setting Group SG2
Setting Group SG1 -
Sel USER Setting Group SG3
Setting Group SG4
003 060 OP Fig.
142
Selection of the setting group from the local control panel.
Blocked /
GROUP: Hold Timer Blocked 65.000 s 0.001 s
0.000 s
003 063 OP Fig.
142
The setting of this timer stage is relevant only if setting group selection is carried out via
the binary signal inputs. Any voltage-free pause that may occur during selection is
bridged. If, after this time period has elapsed, no binary signal input has yet been set, then
the setting group selected from the local control panel shall apply.

1.3.1.7 Self testing & diagnostics (CHECK)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
Signals from selection table
CHECK:
Disabled dependent upon relay -
Fct Assign. Alarm
configuration.
021 030 OP Fig.
143
This setting defines the monitoring signals that will be entered in the monitoring signal
memory. Signals resulting from internal device faults are not configurable and always
result in a warning.
P63x/UK ST/A54 Settings

(ST) 4-60 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
CHECK: Blocked /
Blocked 240 hrs 1 hrs
Mon.Sig. Retention 0 hrs
021 018
Retention time of monitoring signals in the memory. After this time has elapsed any
recurrence of the signal will be processed in the same way as if it were a first occurrence.

1.3.1.8 Disturbance recorder settings (OSCIL)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
Signals from selection table
OSCIL:
Disabled dependent upon relay -
Fct Assig. Trigger
configuration.
003 085 OP Fig.
ST 155
This setting defines the signals that will trigger fault recording.
Blocked/
OSCIL: Id> Blocked 30.00 Iref 0.01 Iref
0.01 Iref
016 018 OP Fig.
155
This setting defines the threshold value of the differential current that will trigger fault
recording.
Blocked/
OSCIL: IR> Blocked 30.00 Iref 0.01 Iref
0.01 Iref
016 019 OP Fig.
155
This setting defines the threshold value of the restraining current that will trigger fault
recording.
OSCIL:
5 Cycles 1 Cycles 50 Cycles 1 Cycles
Pre-Fault Time
003 078 OP Fig.
157
Setting for the time during which data will be recorded before the onset of a fault (pre-fault
recording time).
OSCIL:
2 Cycles 1 Cycles 50 Cycles 1 Cycles
Post-Fault Time
003 079 OP Fig.
157
Setting for the time during which data will be recorded after the end of a fault (post-fault
recording time).
OSCIL:
50 Cycles 5 Cycles 300 Cycles 1 Cycles
Max Record Time
003 075 OP Fig.
157
Setting for the maximum recording time per fault. This includes pre-fault and post-fault
recording times.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-61

1.3.2 Common settings

1.3.2.1 Main common settings (MAIN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end a
019 017 OP Fig. 2,
15
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end b
019 018 OP Fig. 2
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end c
019 019 OP Fig. 2
ST
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end d
019 037 OP Fig. 2
Setting for the primary nominal voltage (phase to phase = line) for each end of the
protected transformer.
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end a Measured
016 096 OP Fig.
117
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end b Measured
016 097 OP Fig.
117
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end c Measured
016 098 OP Fig.
117
This setting specifies which current will be used by the P63x as the residual current: either
the calculated residual current based on the sum of the phase currents or the residual
current measured at the neutral transformer input.
P63x/UK ST/A54 Settings

(ST) 4-62 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Without
End(a) +end(b)
End(a) +end(c)
End(a) +end(d)
End(b) +end(c)
End(b) +end(d)
End(c) +end(d)
End(a) +end(b) +end(c)
MAIN:
Without End(a) +end(b) +end(d) -
Current Summation
End(a) +end(c) +end(d)
End(b) +end(c) +end(d)
End(a) -end(b)
End(a) -end(c)
End(a) -end(d)
End(b) -end(c)
End(b) -end(d)
End(c) -end(d)
019 099 OP Fig.
ST 118
Where a transformer winding is energized from two or three infeeds, such as is the case in
mesh, ring-bus, or breaker and a half feeding, the relay can summate currents to obtain the
total current for that winding. The currents for each phase and the residual currents can be
combined. This setting specifies the CT ends to be involved.
Note: This setting is available for the P633 and P634 only.
MAIN: Blocked/
Blocked 100.00 s 0.01 s
Hold Time Dyn.Settg 0.00 s
018 009 OP Fig.
130
Setting for the hold time of the “dynamic settings”. During this period, the “dynamic”
thresholds are active in place of the “normal” thresholds.

1.3.2.2 Differential protection common settings (DIFF)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
DIFF: General
No No Yes -
Enable USER
019 080 OP Fig. 1
Disabling and enabling the differential protection function.
DIFF: Rated Ref
38.1 MVA 0.1 MVA 5000.0 MVA 0.1 MVA
Power Sref
019 016 OP Fig. 2
Setting for the reference power, usually the nominal transformer power.
DIFF: Ref. Curr. Iref,a Not Measured 0.000 kA 50.000 kA 0.001 kA
019 023 Read only OP Fig. 2
DIFF: Ref. Curr. Iref,b Not Measured 0.000 kA 50.000 kA 0.001 kA
019 024 Read only OP Fig. 2
DIFF: Ref. Curr. Iref,c Not Measured 0.000 kA 50.000 kA 0.001 kA
019 025 Read only OP Fig. 2
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-63

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: Ref. Curr. Iref,d Not Measured 0.000 kA 50.000 kA 0.001 kA
019 038 Read only OP Fig. 2
Display of the reference current calculated by the P63x for each end.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, a
004 105 Read only OP Fig. 2
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, b
004 106 Read only OP Fig. 2
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, c
004 127 Read only OP Fig. 2
ST
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, d
004 168 Read only OP Fig. 2
Display of the matching factor calculated by the P63x for each end.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
DIFF:
0.000 Iref 0.000 Iref 0.200 Iref 0.001 Iref
Minimum Id Meas’mt
011 037 OP Fig. 13
Setting for the minimum differential current that must be exceeded in order for the P63x to
display the differential currents as measured operating data.
DIFF:
0.000 Iref 0.000 Iref 0.200 Iref 0.001 Iref
Minimum IR Meas’mt
011 038 OP Fig. 13
Setting for the minimum restraining current that must be exceeded in order for the P63x to
display the restraining currents as measured operating data.

1.3.2.3 Restricted earth fault protection common settings (REF_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
REF_1: General
No No Yes -
Enable USER
019 050 OP Fig. 14
REF_2: General
No No Yes -
Enable USER
019 150 OP Fig. 14
P63x/UK ST/A54 Settings

(ST) 4-64 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3: General
No No Yes -
Enable USER
019 250 OP Fig. 14
Disabling and enabling the ground differential protection function.
Note: Function group REF_3 is available with the P633 and the P634 only.
REF_1:
End a End a -
Select CT Input
019 100 Read only
REF_2:
End b End b -
Select CT Input
019 101 Read only
REF_3:
End c End c -
Select CT Input

ST 019 102 Read only


Display of the measuring input that provides the measured variables evaluated by the
ground differential protection function.
REF_1: Rated Ref
38.1 MVA 0.1 MVA 5000.0 MVA 0.1 MVA
Power Sref
019 031 OP Fig. 15
REF_2: Rated Ref
38.1 MVA 0.1 MVA 5000.0 MVA 0.1 MVA
Power Sref
019 032 OP Fig. 15
REF_3: Rated Ref
38.1 MVA 0.1 MVA 5000.0 MVA 0.1 MVA
Power Sref
019 033 OP Fig. 15
Setting for the reference power, usually the nominal transformer power for the relevant
transformer end.
Not
REF_1: 50.000 kA/
Not Measured Measured/ 0.001 kA
Ref. Curr. Iref Overflow
0.000 kA
019 034 Read only OP Fig. 15
Not
REF_2: 50.000 kA/
Not Measured Measured/ 0.001 kA
Ref. Curr. Iref Overflow
0.000 kA
019 035 Read only OP Fig. 15
Not
REF_3: 50.000 kA/
Not Measured Measured/ 0.001 kA
Ref. Curr. Iref Overflow
0.000 kA
019 036 Read only OP Fig. 15
Display of the reference current calculated by the P63x.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
Not
REF_1: Matching 50.000/
Not Measured Measured/ 0.001
Fact. kam, N Overflow
0.000
004 160 Read only OP Fig. 15
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-65

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Not
REF_2: Matching 50.000/
Not Measured Measured/ 0.001
Fact. kam, N Overflow
0.000
004 161 Read only OP Fig. 15
Not
REF_3: Matching 50.000/
Not Measured Measured/ 0.001
Fact. kam, N Overflow
0.000
004 162 Read only OP Fig. 15
Display of the matching factor calculated by the P63x for the vector sum of the phase
currents.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
Not
REF_1: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 163 Read only OP Fig. 15
ST
Not
REF_2: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 164 Read only OP Fig. 15
Not
REF_3: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 165 Read only OP Fig. 15
Display of the matching factor calculated by the P63x for the neutral-point current.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
REF_1:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 039 OP Fig. 20
REF_2:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 044 OP Fig. 20
REF_3:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 045 OP Fig. 20
Setting for the minimum differential current that must be exceeded in order for the P63x to
display the differential currents as measured operating data.
REF_1:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 040 OP Fig. 20
REF_2:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 046 OP Fig. 20
P63x/UK ST/A54 Settings

(ST) 4-66 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 047 OP Fig. 20
Setting for the minimum restraining current that must be exceeded in order for the P63x to
display the restraining currents as measured operating data.

1.3.2.4 Definite time overcurrent protection common settings (DTOC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
DTOC1: General
No No Yes -
Enable USER
031 135 OP Fig. 22
DTOC2: General
ST Enable USER
No No Yes -

031 136 OP Fig. 22


DTOC3: General
No No Yes -
Enable USER
031 139 OP Fig. 22
Disabling and enabling the definite-time overcurrent protection function.
Note: Function group DTOC3 is available with the P633 and the P634 only.
End a
End b
DTOC1:
End a End c -
Select CT Input
End d
Current Summation
019 103 OP Fig. 21
DTOC2: As per ‘DTOC1: Select
End b -
Select CT Input CT Input’
019 104 OP Fig. 21
DTOC3: As per ‘DTOC1: Select
End c -
Select CT Input CT Input’
019 105 OP Fig. 21
Selection of the measuring input that provides the measured variables monitored by the
definite-time overcurrent protection function.

1.3.2.5 Inverse time overcurrent protection common settings (IDMT)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
IDMT1: General
No No Yes -
Enable USER
031 141 OP Fig. 29
IDMT2: General
No No Yes -
Enable USER
031 142 OP Fig. 29
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-67

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: General
No No Yes -
Enable USER
031 143 OP Fig. 29
Disabling and enabling the inverse-time overcurrent protection function.
Note: Function group IDMT3 is available with the P633 and the P634 only.
End a
End b
IDMT1:
End a End c -
Select CT Input
End d
Current Summation
019 106 OP Fig. 28
IDMT2: As per ‘IDMT1: Select
End b -
Select CT Input CT Input’
019 116 OP Fig. 28
IDMT3:
End c
As per ‘IDMT1: Select
-
ST
Select CT Input CT Input’
019 126 OP Fig. 28
Selection of the measuring input that provides the measured variables monitored by the
inverse-time overcurrent protection function.

1.3.2.6 Thermal overload protection common settings (THRM)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
THRM1: General
No No Yes -
Enable USER
031 144 OP Fig. 41
THRM2: General
No No Yes -
Enable USER
031 145 OP Fig. 41
Disabling and enabling the thermal overload protection function.
Note: Function group THRM2 is available with the P633 and the P634 only.
End a
End b
THRM1:
End b End c -
Select CT Input
End d
Current Summation
019 109 OP Fig. 40
THRM2: As per ‘THRM1: Select
End c -
Select CT Input CT Input’
019 110 OP Fig. 40
Selection of the current relevant for thermal overload protection. Select from the currents
measured at the measuring input for end a, b, c, d. For the P633 and the P634, there is an
additional option, namely the selection of the value obtained according to the setting at
MAIN: Current summation.
P63x/UK ST/A54 Settings

(ST) 4-68 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1: Absolute Replica
Relative Replica -
Operating Mode Relative Replica
039 121 OP Fig. 45
THRM2: Absolute Replica
Relative Replica -
Operating Mode Relative Replica
039 181 OP Fig. 45
Setting for the operating mode of thermal overload protection. Select between Absolute
replica and Relative replica.
Not
THRM1: 300 °C/
Not Measured Measured/ 1 °C
O/T f Iref Persist 1 Overflow
-40 °C
004 152 Read only
Not
THRM2: 300 °C/
Not Measured Measured/ 1 °C
O/T f Iref Persist 2 Overflow
ST -40 °C
004 172 Read only
Display of the difference between the settings for the maximum permissible temperatures
of the protected object and the coolant.

1.3.2.7 Under/overvoltage protection common settings (V<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
V<>: General Enable
No No Yes -
USER
023 030 OP Fig. 47
Disabling and enabling the time-voltage protection function.
Note: Time-voltage protection is not available with the P631.

1.3.2.8 Frequency protection common settings (f<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
f<>: General Enable
No No Yes -
USER
023 031 OP Fig. 50
Disabling and enabling the over/underfrequency protection function.
Note: Over/underfrequency protection is not available with the P631.
f<>: Evaluation Time 4 Cycles 3 Cycles 6 Cycles 1 Cycles
018 201 OP Fig. 51
Setting for the evaluation time. The operate conditions must be met for this length of time
for a signal to be issued.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-69

Setting Range
Menu Text Default Setting Step Size
Min. Max.
f<>:
0.90 Vn 0.20 Vn 1.00 Vn 0.01 Vn
Undervolt. Block. V<
018 200 OP Fig. 51
Setting for the threshold of the undervoltage blocking. If the voltage falls below this
threshold, the over/underfrequency protection function will be blocked.

1.3.2.9 Overfluxing protection common settings (V/f)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
V/f: General Enable
No No Yes -
USER
019 097 OP Fig. 54
Disabling and enabling the overfluxing protection function.
ST
Note: Overfluxing protection is not available with the P631.

1.3.2.10 Current transformer supervision common settings (CTS)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
CTS: General Enable
No No Yes -
USER
031 085 OP Fig. 64
Disabling and enabling the CT supervision function.
Note: CT Supervision is only available with DSP coprocessor order option.

1.3.2.11 Broken conductor detection common settings (BC_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
BC_1: General
No No Yes -
Enable USER
031 146 OP Fig. 62
BC_2: General
No No Yes -
Enable USER
031 147 OP Fig. 62
BC_3: General
No No Yes -
Enable USER
031 148 OP Fig. 62
BC_4: General
No No Yes -
Enable USER
031 149 OP Fig. 62
Disabling and enabling the broken conductor detection function.
P63x/UK ST/A54 Settings

(ST) 4-70 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
BC_1:
End a End a -
Select CT Input
031 150 Read only
BC_2:
End b End b -
Select CT Input
031 151 Read only
BC_3:
End c End c -
Select CT Input
031 152 Read only
BC_4:
End d End d -
Select CT Input
031 153 Read only
Indication of the CT set monitored by the broken conductor detection function.

ST 1.3.2.12 Temperature & DC monitoring settings (LIMIT)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LIMIT: General
No No Yes -
Enable USER
014 010 OP Fig. 71
Enabling or disabling limit value monitoring.
Blocked/
1.100 0.001
LIMIT: IDC, lin> Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 110 OP Fig. 71
Setting for operate value IDClin> for monitoring the linearized direct current.
Blocked/
1.100 0.001
LIMIT: IDC, lin>> Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 111 OP Fig. 71
Setting for operate value IDClin>> for monitoring the linearized direct current.
Blocked/
LIMIT: tIDC, lin> Blocked 20.00 s 0.01 s
0.00 s
014 112 OP Fig. 71
Setting for the operate delay of overcurrent stage IDClin>.
Blocked/
LIMIT: tIDC, lin>> Blocked 20.00 s 0.01 s
0.00 s
014 113 OP Fig. 71
Setting for the operate delay of overcurrent stage IDClin>>.
Blocked/
1.100 0.001
LIMIT: IDC, lin< Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 114 OP Fig. 71
Setting for operate value IDClin< for monitoring the linearized direct current.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-71

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
1.100 0.001
LIMIT: IDC, lin<< Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 115 OP Fig. 71
Setting for operate value IDClin<< for monitoring the linearized direct current.
Blocked/
LIMIT: tIDC, lin< Blocked 20.00 s 0.01 s
0.00 s
014 116 OP Fig. 71
Setting for the operate delay of undercurrent stage IDClin<.
Blocked/
LIMIT: tIDC, lin<< Blocked 20.00 s 0.01 s
0.00 s
014 117 OP Fig. 71
Setting for the operate delay of the undercurrent stage IDClin<<.
LIMIT: T> 200 °C -20 °C 200 °C 1 °C ST
014 100 OP Fig. 72
Setting for the operate value of temperature monitoring T>.
LIMIT: T>> 200 °C -20 °C 200 °C 1 °C
014 101 OP Fig. 72
Setting for the operate value of temperature monitoring T>>.
Blocked/
LIMIT: tT> Blocked 1000 s 1s
0s
014 103 OP Fig. 72
Setting for the operate delay of temperature monitoring T>.
Blocked/
LIMIT: tT>> Blocked 1000 s 1s
0s
014 104 OP Fig. 72
Setting for the operate delay of temperature monitoring T>>.
LIMIT: T< -20 °C -20 °C 200 °C 1 °C
014 105 OP Fig. 72
Setting for the operate value of temperature monitoring T<.
LIMIT: T<< -20 °C -20 °C 200 °C 1 °C
014 106 OP Fig. 72
Setting for the operate value of temperature monitoring T<<.
Blocked/
LIMIT: tT< Blocked 1000 s 1s
0s
014 107 OP Fig. 72
Setting for the operate delay of temperature monitoring T<.
Blocked/
LIMIT: tT<< Blocked 1000 s 1s
0s
014 108 OP Fig. 72
Setting for the operate delay of temperature monitoring T<<.
P63x/UK ST/A54 Settings

(ST) 4-72 MiCOM P631, P632, P633, P634

1.3.2.13 Phase current monitoring settings (LIM_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LIM_1: General
No No Yes -
Enable USER
014 014 OP Fig. 74
LIM_2: General
No No Yes -
Enable USER
014 015 OP Fig. 74
LIM_3: General
No No Yes -
Enable USER
014 017 OP Fig. 74
Disabling and enabling the limit value monitoring function.
Note: Function group LIM_3 is available with the P633 and the P634 only.
ST
End a
End b
LIM_1:
End a End c -
Select CT Input
End d
Current Summation
019 111 OP Fig. 73
LIM_2: As per ‘LIM_1: Select
End b -
Select CT Input CT Input’
019 112 OP Fig. 73
LIM_3: As per ‘LIM_1: Select
End c -
Select CT Input CT Input’
019 113 OP Fig. 73
Selection of the measuring input that provides the measured variables monitored by limit
value monitoring function 1, 2 or 3, respectively.
Blocked/
LIM_1: I> 1.20 In 4.00 In 0.01 In
0.20 In
015 116 OP Fig. 74
Blocked/
LIM_2: I> 1.20 In 4.00 In 0.01 In
0.20 In
016 116 OP Fig. 74
Blocked/
LIM_3: I> 1.20 In 4.00 In 0.01 In
0.20 In
017 114 OP Fig. 74
Setting for the operate value of I>.
Blocked/
LIM_1: I>> Blocked 4.00 In 0.01 In
0.20 In
015 117 OP Fig. 74
Blocked/
LIM_2: I>> Blocked 4.00 In 0.01 In
0.20 In
016 117 OP Fig. 74
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-73

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
LIM_3: I>> Blocked 4.00 In 0.01 In
0.20 In
017 117 OP Fig. 74
Setting for the operate value of I>>.
Blocked/
LIM_1: tI> 5s 100 s 1s
0s
015 120 OP Fig. 74
Blocked/
LIM_2: tI> 5s 100 s 1s
0s
016 120 OP Fig. 74
Blocked/
LIM_3: tI> 5s 100 s 1s
0s
017 120 OP Fig. 74
Setting for the operate delay of I>.
ST
Blocked/
LIM_1: tI>> Blocked 100 s 1s
0s
015 121 OP Fig. 74
Blocked/
LIM_2: tI>> Blocked 100 s 1s
0s
016 121 OP Fig. 74
Blocked/
LIM_3: tI>> Blocked 100 s 1s
0s
017 121 OP Fig. 74
Setting for the operate delay of I>>.
Blocked/
LIM_1: I< 0.10 In 4.00 In 0.01 In
0.00 In
015 118 OP Fig. 74
Blocked/
LIM_2: I< 0.10 In 4.00 In 0.01 In
0.00 In
016 118 OP Fig. 74
Blocked/
LIM_3: I< 0.10 In 4.00 In 0.01 In
0.00 In
017 118 OP Fig. 74
Setting for the operate value of I<.
Blocked/
LIM_1: I<< Blocked 4.00 In 0.01 In
0.00 In
015 119 OP Fig. 74
Blocked/
LIM_2: I<< Blocked 4.00 In 0.01 In
0.00 In
016 119 OP Fig. 74
Blocked/
LIM_3: I<< Blocked 4.00 In 0.01 In
0.00 In
017 119 OP Fig. 74
Setting for the operate value of I<<.
P63x/UK ST/A54 Settings

(ST) 4-74 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
LIM_1: tI< 5s 100 s 1s
0s
015 122 OP Fig. 74
Blocked/
LIM_2: tI< 5s 100 s 1s
0s
016 122 OP Fig. 74
Blocked/
LIM_3: tI< 5s 100 s 1s
0s
017 122 OP Fig. 74
Setting for the operate delay of I<.
Blocked/
LIM_1: tI<< Blocked 100 s 1s
0s
015 123 OP Fig. 74

ST LIM_2: tI<< Blocked


Blocked/
0s
100 s 1s

016 123 OP Fig. 74


Blocked/
LIM_3: tI<< Blocked 100 s 1s
0s
017 123 OP Fig. 74
Setting for the operate delay of I<<.

1.3.2.14 Programmable logic settings (LOGIC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LOGIC: General
No No Yes -
Enable USER
031 099 OP Fig. 76
Disabling or enabling the logic function.
LOGIC: Set 1 (… 8)
No No Yes -
USER
See table below for setting addresses. OP Fig. 75,
76
These settings define the static input conditions for the logic function.
Setting Address Setting Address Setting Address
Set 1 USER 034 030 Set 4 USER 034 033 Set 7 USER 034 036
Set 2 USER 034 031 Set 5 USER 034 034 Set 8 USER 034 037
Set 3 USER 034 032 Set 6 USER 034 035
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-75

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
LOGIC: Fct.Assignm.
Disabled dependent upon relay -
Outp. 1 (… 32)
configuration.
See table below for setting addresses. OP Fig. 76
These settings assign functions to the outputs.
Setting Address Setting Address Setting Address
Fct.Assignm. Outp. 1 030 000 Fct.Assignm. Outp. 12 030 044 Fct.Assignm. Outp. 23 030 088
Fct.Assignm. Outp. 2 030 004 Fct.Assignm. Outp. 13 030 048 Fct.Assignm. Outp. 24 030 092
Fct.Assignm. Outp. 3 030 008 Fct.Assignm. Outp. 14 030 052 Fct.Assignm. Outp. 25 030 096
Fct.Assignm. Outp. 4 030 012 Fct.Assignm. Outp. 15 030 056 Fct.Assignm. Outp. 26 031 000
Fct.Assignm. Outp. 5 030 016 Fct.Assignm. Outp. 16 030 060 Fct.Assignm. Outp. 27 031 004
Fct.Assignm. Outp. 6 030 020 Fct.Assignm. Outp. 17 030 064 Fct.Assignm. Outp. 28 031 008
Fct.Assignm. Outp. 7 030 024 Fct.Assignm. Outp. 18 030 068 Fct.Assignm. Outp. 29 031 012
Fct.Assignm. Outp. 8 030 028 Fct.Assignm. Outp. 19 030 072 Fct.Assignm. Outp. 30 031 016
Fct.Assignm. Outp. 9 030 032 Fct.Assignm. Outp. 20 030 076 Fct.Assignm. Outp. 31 031 020
ST
Fct.Assignm. Outp. 10 030 036 Fct.Assignm. Outp. 21 030 080 Fct.Assignm. Outp. 32 031 024
Fct.Assignm. Outp. 11 030 040 Fct.Assignm. Outp. 22 030 084

Without Timer Stage


PickUp & Reset Delay
LOGIC: Op. Mode t Pulse Delayed PickUp
Without Timer Stage -
Output 1 (… 32) PickUp & Rst.Retrig
Delayed Pulse Retrig
Minimum Dwell
See table below for setting addresses. OP Fig. 76,
77, 78, 79,
80, 81
These settings define the operating modes for the output timer stages.
Setting Address Setting Address Setting Address
Op. Mode t Output 1 030 001 Op. Mode t Output 12 030 045 Op. Mode t Output 23 030 089
Op. Mode t Output 2 030 005 Op. Mode t Output 13 030 049 Op. Mode t Output 24 030 093
Op. Mode t Output 3 030 009 Op. Mode t Output 14 030 053 Op. Mode t Output 25 030 097
Op. Mode t Output 4 030 013 Op. Mode t Output 15 030 057 Op. Mode t Output 26 031 001
Op. Mode t Output 5 030 017 Op. Mode t Output 16 030 061 Op. Mode t Output 27 031 005
Op. Mode t Output 6 030 021 Op. Mode t Output 17 030 065 Op. Mode t Output 28 031 009
Op. Mode t Output 7 030 025 Op. Mode t Output 18 030 069 Op. Mode t Output 29 031 013
Op. Mode t Output 8 030 029 Op. Mode t Output 19 030 073 Op. Mode t Output 30 031 017
Op. Mode t Output 9 030 033 Op. Mode t Output 20 030 077 Op. Mode t Output 31 031 021
Op. Mode t Output 10 030 037 Op. Mode t Output 21 030 081 Op. Mode t Output 32 031 025
Op. Mode t Output 11 030 041 Op. Mode t Output 22 030 085
P63x/UK ST/A54 Settings

(ST) 4-76 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
LOGIC: Time t1
0.00 s 0.00 s 600.00 s 0.01 s
Output 1 (… 32)
See table below for setting addresses. OP Fig. 76,
77, 78, 79,
80, 81
Settings for timer stage t1 of the respective outputs.
Setting Address Setting Address Setting Address
Time t1 Output 1 030 002 Time t1 Output 12 030 046 Time t1 Output 23 030 090
Time t1 Output 2 030 006 Time t1 Output 13 030 050 Time t1 Output 24 030 094
Time t1 Output 3 030 010 Time t1 Output 14 030 054 Time t1 Output 25 030 098
Time t1 Output 4 030 014 Time t1 Output 15 030 058 Time t1 Output 26 031 002
Time t1 Output 5 030 018 Time t1 Output 16 030 062 Time t1 Output 27 031 006
Time t1 Output 6 030 022 Time t1 Output 17 030 066 Time t1 Output 28 031 010
Time t1 Output 7 030 026 Time t1 Output 18 030 070 Time t1 Output 29 031 014
ST Time t1 Output 8 030 030 Time t1 Output 19 030 074 Time t1 Output 30 031 018
Time t1 Output 9 030 034 Time t1 Output 20 030 078 Time t1 Output 31 031 022
Time t1 Output 10 030 038 Time t1 Output 21 030 082 Time t1 Output 32 031 026
Time t1 Output 11 030 042 Time t1 Output 22 030 086

LOGIC: Time t2
0.00 s 0.00 s 600.00 s 0.01 s
Output 1 (… 32)
See table below for setting addresses. OP Fig. 76,
77, 78, 79,
80, 81
Settings for timer stage t2 of the respective outputs.
Note: This setting has no effect in the ‘Minimum Dwell’ operating mode.
Setting Address Setting Address Setting Address
Time t2 Output 1 030 003 Time t2 Output 12 030 047 Time t2 Output 23 030 091
Time t2 Output 2 030 007 Time t2 Output 13 030 051 Time t2 Output 24 030 095
Time t2 Output 3 030 011 Time t2 Output 14 030 055 Time t2 Output 25 030 099
Time t2 Output 4 030 015 Time t2 Output 15 030 059 Time t2 Output 26 031 003
Time t2 Output 5 030 019 Time t2 Output 16 030 063 Time t2 Output 27 031 007
Time t2 Output 6 030 023 Time t2 Output 17 030 067 Time t2 Output 28 031 011
Time t2 Output 7 030 027 Time t2 Output 18 030 071 Time t2 Output 29 031 015
Time t2 Output 8 030 031 Time t2 Output 19 030 075 Time t2 Output 30 031 019
Time t2 Output 9 030 035 Time t2 Output 20 030 079 Time t2 Output 31 031 023
Time t2 Output 10 030 039 Time t2 Output 21 030 083 Time t2 Output 32 031 027
Time t2 Output 11 030 043 Time t2 Output 22 030 087
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-77

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
LOGIC: Sig. Assig
Disabled dependent upon relay -
Outp. 1 (… 32)
configuration.
See table below for setting addresses. OP Fig. 82
These settings assign the function of a binary input signal to the output of the logic
equation.
Setting Address Setting Address Setting Address
Sig. Assig Outp. 1 044 000 Sig. Assig Outp. 12 044 022 Sig. Assig Outp. 23 044 044
Sig. Assig Outp. 2 044 002 Sig. Assig Outp. 13 044 024 Sig. Assig Outp. 24 044 046
Sig. Assig Outp. 3 044 004 Sig. Assig Outp. 14 044 026 Sig. Assig Outp. 25 044 048
Sig. Assig Outp. 4 044 006 Sig. Assig Outp. 15 044 028 Sig. Assig Outp. 26 044 050
Sig. Assig Outp. 5 044 008 Sig. Assig Outp. 16 044 030 Sig. Assig Outp. 27 044 052
Sig. Assig Outp. 6 044 010 Sig. Assig Outp. 17 044 032 Sig. Assig Outp. 28 044 054
Sig. Assig Outp. 7 044 012 Sig. Assig Outp. 18 044 034 Sig. Assig Outp. 29 044 056
Sig. Assig Outp. 8 044 014 Sig. Assig Outp. 19 044 036 Sig. Assig Outp. 30 044 058 ST
Sig. Assig Outp. 9 044 016 Sig. Assig Outp. 20 044 038 Sig. Assig Outp. 31 044 060
Sig. Assig Outp. 10 044 018 Sig. Assig Outp. 21 044 040 Sig. Assig Outp. 32 044 062
Sig. Assig Outp. 11 044 020 Sig. Assig Outp. 22 044 042

Signals from selection table


LOGIC: Sig. Assig
Disabled dependent upon relay -
Outp. 1 (… 32) (t)
configuration.
See table below for setting addresses. OP Fig. 82
These settings assign the function of a binary input signal to the output of the logic
equation.
Setting Address Setting Address Setting Address
Sig. Assig Outp. 1 (t) 044 001 Sig. Assig Outp. 12 (t) 044 023 Sig. Assig Outp. 23 (t) 044 045
Sig. Assig Outp. 2 (t) 044 003 Sig. Assig Outp. 13 (t) 044 025 Sig. Assig Outp. 24 (t) 044 047
Sig. Assig Outp. 3 (t) 044 005 Sig. Assig Outp. 14 (t) 044 027 Sig. Assig Outp. 25 (t) 044 049
Sig. Assig Outp. 4 (t) 044 007 Sig. Assig Outp. 15 (t) 044 029 Sig. Assig Outp. 26 (t) 044 051
Sig. Assig Outp. 5 (t) 044 009 Sig. Assig Outp. 16 (t) 044 031 Sig. Assig Outp. 27 (t) 044 053
Sig. Assig Outp. 6 (t) 044 011 Sig. Assig Outp. 17 (t) 044 033 Sig. Assig Outp. 28 (t) 044 055
Sig. Assig Outp. 7 (t) 044 013 Sig. Assig Outp. 18 (t) 044 035 Sig. Assig Outp. 29 (t) 044 057
Sig. Assig Outp. 8 (t) 044 015 Sig. Assig Outp. 19 (t) 044 037 Sig. Assig Outp. 30 (t) 044 059
Sig. Assig Outp. 9 (t) 044 017 Sig. Assig Outp. 20 (t) 044 039 Sig. Assig Outp. 31 (t) 044 061
Sig. Assig Outp. 10 (t) 044 019 Sig. Assig Outp. 21 (t) 044 041 Sig. Assig Outp. 32 (t) 044 063
Sig. Assig Outp. 11 (t) 044 021 Sig. Assig Outp. 22 (t) 044 043

1.3.3 Setting group SGx (x = 1 to 4)


The device provides four setting groups containing identical settings that may be enabled
and configured independently.
The setting address for each setting differs between the groups and is displayed in the line
below the setting in the order SG1, SG2, SG3, SG4. As an example, for the DIFF: Enable
SGx setting immediately below the addresses are read as:
Address: 072 152 DIFF: Enable SG1
Address: 073 152 DIFF: Enable SG2
Address: 074 152 DIFF: Enable SG3
P63x/UK ST/A54 Settings

(ST) 4-78 MiCOM P631, P632, P633, P634

Address: 075 152 DIFF: Enable SG4

1.3.3.1 Phase reversal logic (MAIN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end a SGx B-C Swapped
C-A Swapped
010 200 010 201 010 202 010 203
Setting to determine if CT input phase-swapping shall apply in pumped storage
applications, when in motoring (pump) mode. Setting available for each CT set, in this
case for end a.
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end b SGx B-C Swapped
ST C-A Swapped
010 204 010 205 010 206 010 207
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end c SGx B-C Swapped
C-A Swapped
010 208 010 209 010 210 010 211
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end d SGx B-C Swapped
C-A Swapped
010 212 010 213 010 214 010 215

1.3.3.2 Differential protection (DIFF)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
DIFF: Enable SGx No No Yes -
072 152 073 152 074 152 075 152 OP Fig. 1
This setting specifies the setting group to be enabled for differential protection.
DIFF: Vec. Gr. ends
0 0 11 1
b-a SGx
019 010 019 040 019 041 019 042 OP Fig. 5
DIFF: Vec. Gr. ends
0 0 11 1
c-a SGx
019 011 019 043 019 044 019 045 OP Fig. 5
DIFF: Vec. Gr. ends
0 0 11 1
d-a SGx
019 014 019 046 019 047 019 048 OP Fig. 6
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-79

Setting Range
Menu Text Default Setting Step Size
Min. Max.
The vector group is read from the transformer rating plate, taking end "a" as the HV
reference. In the case of a Yd1 transformer, with end "b" as the delta winding the clock
notation setting required will be 1 for end b-a.
If the phase currents of the low and high voltage sides are exchanged or if the connection
of the measuring circuits is not accounted for by the settings at MAIN: CT Orientation
IPh, z (where z is end a, b, c or d) then the algorithm is:
Setting = 12 - ID
If a reverse phase rotation is present (phase sequence A-C-B) then this should be entered
as a setting at the P63x. In this case, the P63x will automatically form the complementary
value of the set vector group ID to the number 12
(vector group ID = 12 - set ID).
For application of the P63x as machine protection, the setting must be 0 or 6 depending on
the current transformer connection.
DIFF: Idiff> SGx 0.20 Iref 0.10 Iref 2.50 Iref 0.01 Iref
072 142 073 142 074 142 075 142 OP Fig. 9
Minimum pickup value of the differential protection function as referred to the reference
ST
current of the relevant transformer end.
DIFF: Idiff>> SGx 15.0 Iref 2.5 Iref 30.0 Iref 0.1 Iref
072 143 073 143 074 143 075 143 OP Fig. 9
Threshold value of the differential current for deactivation of the inrush stabilization
function (harmonic restraint) and of the overfluxing restraint.
Note: If the threshold is set too high, it is possible for the P63x not to trip in the
presence of internal faults with transformer saturation.
Blocked/
DIFF: Idiff>>> SGx 30.0 Iref 30.0 Iref 0.1 Iref
2.5 Iref
072 144 073 144 074 144 075 144 OP Fig. 9
Threshold value of the differential current for tripping by the differential protection function
independent of restraining variable, harmonic restraint, overfluxing restraint and saturation
detector.
Note: If the threshold is set too low, the P63x can trip in the presence of external
faults with transformer saturation.
DIFF:
0.20 Iref 0.10 Iref 30.00 Iref 0.01 Iref
Idiff> (CTS) SGx
080 000 081 000 082 000 083 000 OP Fig. 68
Low set threshold of differential protection when a CTS condition is detected.
DIFF: m1 SGx 0.30 0.10 1.50 0.01
072 145 073 145 074 145 075 145 OP Fig. 9
Gradient of the tripping characteristic of differential protection in the range:
0.5 ⋅ Idiff >< IR ≤ IR,m2

DIFF: m2 SGx 0.70 0.10 1.50 0.01


072 146 073 146 074 146 075 146 OP Fig. 9
Gradient of the tripping characteristic of differential protection in the range:
IR > IR,m2
P63x/UK ST/A54 Settings

(ST) 4-80 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: IR, m2 SGx 4.0 Iref 1.5 Iref 10.0 Iref 0.1 Iref
072 147 073 147 074 147 075 147 OP Fig. 9
This setting defines the second knee of the tripping characteristic. Above this knee, the
gradient is m2.
Disabled
DIFF:
Not Phase-Selective Not Phase-Selective -
Op. Mode Inrush SGx
Phase-Selective
072 148 073 148 074 148 075 148 OP Fig. 9
Setting for the operating mode of the inrush stabilization function (harmonic blocking or
harmonic restraint).
For application of the P63x as machine protection, the harmonic restraint can be
deactivated by way of this setting.
For application of the P63x as transformer protection, the user can select whether the
harmonic restraint should operate in cross-blocking mode or selectively for one measuring
system.
ST
DIFF: Inrush 2nd
20 % 10 % 50 % 1%
Harmon SGx
072 159 073 159 074 159 075 159 OP Fig. 10
Operate value of the inrush stabilization function (harmonic restraint) of differential
protection, as ratio of the second harmonic component to the fundamental for the
differential current, in percent.
DIFF:
Yes No Yes -
I0 filt a Enab SGx
072 155 073 155 074 155 075 155 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt b Enab SGx
072 156 073 156 074 156 075 156 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt c Enab SGx
072 157 073 157 074 157 075 157 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt d Enab SGx
072 154 073 154 074 154 075 154 OP Fig. 6
Enabling or disabling the zero-sequence filtering of winding a, b, c or d.
DIFF:
No No Yes -
O/Flux Blk Enab SGx
072 158 073 158 074 158 075 158 OP Fig. 12
Enabling or disabling the overfluxing restraint.
DIFF: O/Flux 5th
20 % 10 % 80 % 1%
Harmon SGx
072 160 073 160 074 160 075 160 OP Fig. 12
Operate value of the overfluxing restraint of differential protection as ratio of the fifth
harmonic component to the fundamental for the differential current, in percent.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-81

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: Op.del., trip
0.00 s 0.00 s 100.00 s 0.01 s
sig. SGx
010 162 010 163 010 164 010 165
Tripping of the restraint differential protection may be delayed via a settable timer stage.
DIFF: Hyst. Effective
Yes No Yes -
SGx
072 006 073 006 074 006 075 006
Hysteresis of the tripping characteristic at the rate of 10% be disabled.

1.3.3.3 Restricted earth fault protection (REF_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
REF_1: Enable SGx No No Yes - ST
072 141 073 141 074 141 075 141 OP Fig. 14
REF_2: Enable SGx No No Yes -
072 161 073 161 074 161 075 161 OP Fig. 14
REF_3: Enable SGx No No Yes -
072 031 073 031 074 031 075 031 OP Fig. 14
This setting allows restricted earth fault protection to be enabled or disabled on the
associated winding for each setting group.
Low-Z Iph Sum Bias
REF_1:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 149 073 149 074 149 075 149 OP Fig. 16,
18, 19
Low-Z Iph Sum Bias
REF_2:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 169 073 169 074 169 075 169 OP Fig. 16,
18, 19
Low-Z Iph Sum Bias
REF_3:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 049 073 049 074 049 075 049 OP Fig. 16,
18, 19
This setting specifies the mode of operation for the restricted earth fault protection. The
protection may be biased by residual current or the maximum phase current. Alternatively,
operation as a high impedance element may be selected.
REF_1:
No No Yes -
CTS Effective SGx
080 003 081 003 082 003 083 003
REF_2:
No No Yes -
CTS Effective SGx
080 004 081 004 082 004 083 004
P63x/UK ST/A54 Settings

(ST) 4-82 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3:
No No Yes -
CTS Effective SGx
080 005 081 005 082 005 083 005
Blocking of REF protection when a CTS condition is detected.
REF_1: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 150 073 150 074 150 075 150 OP Fig. 17
REF_2: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 170 073 170 074 170 075 170 OP Fig. 17
REF_3: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 040 073 040 074 040 075 040 OP Fig. 17
Pickup value of the restricted earth fault protection as referred to the reference current of
the relevant transformer end.
Blocked/
ST REF_1: Idiff>>> SGx 10.0 Iref
2.5 Iref
30.0 Iref 0.1 Iref

072 151 073 151 074 151 075 151 OP Fig. 17


Blocked/
REF_2: Idiff>>> SGx 10.0 Iref 30.0 Iref 0.1 Iref
2.5 Iref
072 171 073 171 074 171 075 171 OP Fig. 17
Blocked/
REF_3: Idiff>>> SGx 10.0 Iref 30.0 Iref 0.1 Iref
2.5 Iref
072 041 073 041 074 041 075 041 OP Fig. 17
Threshold value of the differential current for tripping by the restricted earth fault protection
independent of restraint current.
REF_1: m1 SGx 0.20 0.00 1.00 0.01
072 162 073 162 074 162 075 162 OP Fig. 18
REF_2: m1 SGx 0.20 0.00 1.00 0.01
072 172 073 172 074 172 075 172 OP Fig. 18
REF_3: m1 SGx 0.20 0.00 1.00 0.01
072 192 073 192 074 192 075 192 OP Fig. 18
Lower slope gradient of tripping characteristic for restricted earth fault protection when
operating in a low impedance biased mode.
REF_1: m2 SGx 1.50 0.15 1.50 0.01
072 163 073 163 074 163 075 163 OP Fig. 18
REF_2: m2 SGx 1.50 0.15 1.50 0.01
072 165 073 165 074 165 075 165 OP Fig. 18
REF_3: m2 SGx 1.50 0.15 1.50 0.01
072 193 073 193 074 193 075 193 OP Fig. 18
Upper slope gradient of tripping characteristic for restricted earth fault protection when
operating in a low impedance biased mode.
REF_1: IR, m2 SGx 1.00 Iref 0.10 Iref 1.50 Iref 0.01 Iref
072 164 073 164 074 164 075 164 OP Fig. 18
REF_2: IR, m2 SGx 1.00 Iref 0.10 Iref 1.50 Iref 0.01 Iref
072 166 073 166 074 166 075 166 OP Fig. 18
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-83

Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3: IR, m2 SGx 1.00 Iref 0.10 Iref 1.50 Iref 0.01 Iref
072 194 073 194 074 194 075 194 OP Fig. 18
Bias current threshold setting above which the gradient of the tripping characteristic is m2
for restricted earth fault protection when operating in a low impedance biased mode.

1.3.3.4 Definite time overcurrent protection (DTOC)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
DTOC1: Enable SGx No No Yes -
076 050 077 050 078 050 079 050
DTOC2: Enable SGx No No Yes -
076 070 077 070 078 070 079 070
DTOC3: Enable SGx No No Yes -
ST
076 180 077 180 078 180 079 180
This setting specifies the setting group to be enabled for definite-time overcurrent
protection.
Disabled
DTOC1:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 067 077 067 078 067 079 067 OP Fig. 25
Disabled
DTOC2:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 087 077 087 078 087 079 087 OP Fig. 25
Disabled
DTOC3:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 108 077 108 078 108 079 108 OP Fig. 25
This setting defines whether blocking of the residual current stages will take place for
single-pole or multi-pole phase current starting.
DTOC1: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 066 077 066 078 066 079 066 OP Fig. 26
DTOC2: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 086 077 086 078 086 079 086 OP Fig. 26
DTOC3: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 106 077 106 078 106 079 106 OP Fig. 26
This setting defines whether starting of the negative-sequence and residual current stages
will be included in the general starting signal of DTOC protection.
Blocked/
DTOC1: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 065 077 065 078 065 079 065 OP Fig. 26
P63x/UK ST/A54 Settings

(ST) 4-84 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC2: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 085 077 085 078 085 079 085 OP Fig. 26
Blocked/
DTOC3: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 107 077 107 078 107 079 107 OP Fig. 26
Setting for the operate delay of the general starting signal of DTOC protection.
DTOC1: Inrush Restr
No No Yes -
Enab SGx
076 063 077 063 078 063 079 063 OP Fig. 24
DTOC2: Inrush Restr
No No Yes -
Enab SGx
076 083 077 083 078 083 079 083 OP Fig. 24

ST DTOC3: Inrush Restr


Enab SGx
No No Yes -

076 193 077 193 078 193 079 193 OP Fig. 24


Setting as to whether the inrush stabilization function (harmonic restraint) of differential
protection shall be able to block the definite-time overcurrent protection function.
Blocked/
DTOC1: I> SGx 1.00 In 30.00 In 0.01 In
0.10 In
076 051 077 051 078 051 079 051 OP Fig. 23
Blocked/
DTOC2: I> SGx 1.00 In 30.00 In 0.01 In
0.10 In
076 071 077 071 078 071 079 071 OP Fig. 23
Blocked/
DTOC3: I> SGx 1.00 In 30.00 In 0.01 In
0.10 In
076 081 077 081 078 081 079 081 OP Fig. 23
Setting for the operate value I>.
Blocked/
DTOC1: I>> SGx 4.00 In 30.00 In 0.01 In
0.10 In
076 052 077 052 078 052 079 052 OP Fig. 23
Blocked/
DTOC2: I>> SGx 4.00 In 30.00 In 0.01 In
0.10 In
076 072 077 072 078 072 079 072 OP Fig. 23
Blocked/
DTOC3: I>> SGx 4.00 In 30.00 In 0.01 In
0.10 In
076 082 077 082 078 082 079 082 OP Fig. 23
Setting for the operate value I>>.
Blocked/
DTOC1: I>>> SGx Blocked 30.00 In 0.01 In
0.10 In
076 053 077 053 078 053 079 053 OP Fig. 23
Blocked/
DTOC2: I>>> SGx Blocked 30.00 In 0.01 In
0.10 In
076 163 077 163 078 163 079 163 OP Fig. 23
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-85

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC3: I>>> SGx Blocked 30.00 In 0.01 In
0.10 In
076 183 077 183 078 183 079 183 OP Fig. 23
Setting for the operate value I>>>.
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 151 077 151 078 151 079 151 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 161 077 161 078 161 079 161 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 181 077 181 078 181 079 181 OP Fig. 23
Setting for the operate value I> in dynamic mode. This operate value is only effective while
the hold time for dynamic settings is elapsing.
ST
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 152 077 152 078 152 079 152 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 162 077 162 078 162 079 162 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 182 077 182 078 182 079 182 OP Fig. 23
Setting for the operate value I>> in dynamic mode. This operate value is only effective
while the hold time for dynamic settings is elapsing.
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 153 077 153 078 153 079 153 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 173 077 173 078 173 079 173 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 109 077 109 078 109 079 109 OP Fig. 23
Setting for the operate value I>>> in dynamic mode. This operate value is only effective
while the hold time for dynamic settings is elapsing.
Blocked/
DTOC1: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 057 077 057 078 057 079 057 OP Fig. 23
Blocked/
DTOC2: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 077 077 077 078 077 079 077 OP Fig. 23
P63x/UK ST/A54 Settings

(ST) 4-86 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC3: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 187 077 187 078 187 079 187 OP Fig. 23
Setting for the operate delay of the I> stage.
Blocked/
DTOC1: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 058 077 058 078 058 079 058 OP Fig. 23
Blocked/
DTOC2: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 078 077 078 078 078 079 078 OP Fig. 23
Blocked/
DTOC3: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 188 077 188 078 188 079 188 OP Fig. 23

ST Setting for the operate delay of the I>> stage.


Blocked/
DTOC1: tI>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 059 077 059 078 059 079 059 OP Fig. 23
Blocked/
DTOC2: tI>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 169 077 169 078 169 079 169 OP Fig. 23
Blocked/
DTOC3: tI>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 189 077 189 078 189 079 189 OP Fig. 23
Setting for the operate delay of the I>>> stage.
Blocked/
DTOC1: I2> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 197 077 197 078 197 079 197 OP Fig. 24
Blocked/
DTOC2: I2> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 207 077 207 078 207 079 207 OP Fig. 24
Blocked/
DTOC3: I2> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 217 077 217 078 217 079 217 OP Fig. 24
Setting for the operate value of the I2> stage for negative sequence current.
Blocked/
DTOC1: I2>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 198 077 198 078 198 079 198 OP Fig. 24
Blocked/
DTOC2: I2>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 208 077 208 078 208 079 208 OP Fig. 24
Blocked/
DTOC3: I2>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 218 077 218 078 218 079 218 OP Fig. 24
Setting for the operate value of the I2>> stage for negative sequence current.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-87

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC1: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 199 077 199 078 199 079 199 OP Fig. 24
Blocked/
DTOC2: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 209 077 209 078 209 079 209 OP Fig. 24
Blocked/
DTOC3: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 219 077 219 078 219 079 219 OP Fig. 24
Setting for the operate value of the I2>>> stage for negative sequence current.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2> dynamic SGx 0.10 In
076 200 077 200 078 200 079 200 OP Fig. 24
DTOC2:
I2> dynamic SGx
1.00 In
Blocked/
0.10 In
8.00 In 0.01 In ST
076 210 077 210 078 210 079 210 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2> dynamic SGx 0.10 In
076 220 077 220 078 220 079 220 OP Fig. 24
Setting for the operate value of the I2> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 201 077 201 078 201 079 201 OP Fig. 24
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 211 077 211 078 211 079 211 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 221 077 221 078 221 079 221 OP Fig. 24
Setting for the operate value of the I2>> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 202 077 202 078 202 079 202 OP Fig. 24
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 212 077 212 078 212 079 212 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 222 077 222 078 222 079 222 OP Fig. 24
Setting for the operate value of the I2>>> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
P63x/UK ST/A54 Settings

(ST) 4-88 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC1: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 203 077 203 078 203 079 203 OP Fig. 24
Blocked/
DTOC2: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 213 077 213 078 213 079 213 OP Fig. 24
Blocked/
DTOC3: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 223 077 223 078 223 079 223 OP Fig. 24
Setting for the operate delay of the I2> stage for negative sequence current.
Blocked/
DTOC1: tI2>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 204 077 204 078 204 079 204 OP Fig. 24

ST DTOC2: tI2>> SGx 0.50 s


Blocked/
0.00 s
100.00 s 0.01 s

076 214 077 214 078 214 079 214 OP Fig. 24


Blocked/
DTOC3: tI2>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 224 077 224 078 224 079 224 OP Fig. 24
Setting for the operate delay of the I2>> stage for negative sequence current.
Blocked/
DTOC1: tI2>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 205 077 205 078 205 079 205 OP Fig. 24
Blocked/
DTOC2: tI2>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 215 077 215 078 215 079 215 OP Fig. 24
Blocked/
DTOC3: tI2>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 225 077 225 078 225 079 225 OP Fig. 24
Setting for the operate delay of the I2>>> stage for negative sequence current.
Blocked/
DTOC1: IN> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 054 077 054 078 054 079 054 OP Fig. 25
Blocked/
DTOC2: IN> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 164 077 164 078 164 079 164 OP Fig. 25
Blocked/
DTOC3: IN> SGx 0.25 In 8.00 In 0.01 In
0.10 In
076 184 077 184 078 184 079 184 OP Fig. 25
Setting for the operate value IN> for residual current.
Blocked/
DTOC1: IN>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 055 077 055 078 055 079 055 OP Fig. 25
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-89

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC2: IN>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 165 077 165 078 165 079 165 OP Fig. 25
Blocked/
DTOC3: IN>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 185 077 185 078 185 079 185 OP Fig. 25
Setting for the operate value IN>> for residual current.
Blocked/
DTOC1: IN>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 056 077 056 078 056 079 056 OP Fig. 25
Blocked/
DTOC2: IN>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 166 077 166 078 166 079 166 OP Fig. 25

DTOC3: IN>>> SGx Blocked


Blocked/
0.10 In
8.00 In 0.01 In ST
076 186 077 186 078 186 079 186 OP Fig. 25
Setting for the operate value IN>>> for residual current.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
IN> dynamic SGx 0.10 In
076 154 077 154 078 154 079 154 OP Fig. 25
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
IN> dynamic SGx 0.10 In
076 174 077 174 078 174 079 174 OP Fig. 25
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
IN> dynamic SGx 0.10 In
076 194 077 194 078 194 079 194 OP Fig. 25
Setting for the operate value IN> for residual current in dynamic mode. This operate value
is only effective while the hold time for dynamic settings is elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
IN>> dynamic SGx 0.10 In
076 155 077 155 078 155 079 155 OP Fig. 25
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
IN>> dynamic SGx 0.10 In
076 175 077 175 078 175 079 175 OP Fig. 25
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
IN>> dynamic SGx 0.10 In
076 195 077 195 078 195 079 195 OP Fig. 25
Setting for the operate value IN>> for residual current in dynamic mode. This operate
value is only effective while the hold time for dynamic settings is elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
IN>>> dynamic SGx 0.10 In
076 156 077 156 078 156 079 156 OP Fig. 25
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
IN>>> dynamic SGx 0.10 In
076 176 077 176 078 176 079 176 OP Fig. 25
P63x/UK ST/A54 Settings

(ST) 4-90 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
IN>>> dynamic SGx 0.10 In
076 196 077 196 078 196 079 196 OP Fig. 25
Setting for the operate value IN>>> for residual current in dynamic mode. This operate
value is only effective while the hold time for dynamic settings is elapsing.
Blocked/
DTOC1: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 060 077 060 078 060 079 060 OP Fig. 25
Blocked/
DTOC2: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 170 077 170 078 170 079 170 OP Fig. 25
Blocked/
DTOC3: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 190 077 190 078 190 079 190 OP Fig. 25
ST Setting for the operate delay of the IN> for residual current stage.
Blocked/
DTOC1: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 061 077 061 078 061 079 061 OP Fig. 25
Blocked/
DTOC2: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 171 077 171 078 171 079 171 OP Fig. 25
Blocked/
DTOC3: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 191 077 191 078 191 079 191 OP Fig. 25
Setting for the operate delay of the IN>> for residual current stage.
Blocked/
DTOC1: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 062 077 062 078 062 079 062 OP Fig. 25
Blocked/
DTOC2: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 172 077 172 078 172 079 172 OP Fig. 25
Blocked/
DTOC3: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 192 077 192 078 192 079 192 OP Fig. 25
Setting for the operate delay of the IN>>> for residual current stage.

1.3.3.5 Inverse time overcurrent protection (IDMT)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
IDMT1: Enable SGx No No Yes -
081 050 082 050 083 050 084 050 OP Fig. 29
IDMT2: Enable SGx No No Yes -
081 170 082 170 083 170 084 170 OP Fig. 29
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-91

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: Enable SGx No No Yes -
081 190 082 190 083 190 084 190 OP Fig. 29
This setting specifies the setting group to be enabled for inverse-time overcurrent
protection.
Disabled
IDMT1:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
081 068 082 068 083 068 084 068 OP Fig. 36
Disabled
IDMT2:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
081 188 082 188 083 188 084 188 OP Fig. 36
Disabled
IDMT3:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
ST
081 208 082 208 083 208 084 208 OP Fig. 36
This setting defines whether blocking of the residual current stages will take place for
single-pole or multi-pole phase current starting.
IDMT1: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 059 082 059 083 059 084 059 OP Fig. 35,
36, 38
IDMT2: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 179 082 179 083 179 084 179 OP Fig. 35,
36, 38
IDMT3: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 199 082 199 083 199 084 199 OP Fig. 35,
36, 38
This setting defines whether starting of the negative-sequence and residual current stages
will be included in the general starting signal of IDMT protection.
Blocked/
IDMT1: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 058 082 058 083 058 084 058 OP Fig. 38
Blocked/
IDMT2: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 178 082 178 083 178 084 178 OP Fig. 38
Blocked/
IDMT3: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 198 082 198 083 198 084 198 OP Fig. 38
Setting for the operate delay of the general starting signal of IDMT protection.
IDMT1: Inrush Restr
No No Yes -
Enab SGx
081 060 082 060 083 060 084 060 OP Fig. 34,
35
P63x/UK ST/A54 Settings

(ST) 4-92 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT2: Inrush Restr
No No Yes -
Enab SGx
081 180 082 180 083 180 084 180 OP Fig. 34,
35
IDMT3: Inrush Restr
No No Yes -
Enab SGx
081 200 082 200 083 200 084 200 OP Fig. 34,
35
Setting as to whether the inrush restraint of differential protection shall be able to block the
inverse-time overcurrent protection function.
Blocked/
IDMT1: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
081 051 082 051 083 051 084 051 OP Fig. 34
Blocked/
IDMT2: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
ST
081 171 082 171 083 171 084 171 OP Fig. 34
Blocked/
IDMT3: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
081 191 082 191 083 191 084 191 OP Fig. 34
Setting for the reference current (phase overcurrent pickup).
IDMT1: Blocked/
1.00 In 4.00 In 0.01 In
Iref, Ph dynamic SGx 0.10 In

081 052 082 052 083 052 084 052 OP Fig. 34


IDMT2: Blocked/
1.00 In 4.00 In 0.01 In
Iref, Ph dynamic SGx 0.10 In
081 172 082 172 083 172 084 172 OP Fig. 34
IDMT3: Blocked/
1.00 In 4.00 In 0.01 In
Iref, Ph dynamic SGx 0.10 In
081 192 082 192 083 192 084 192 OP Fig. 34
Setting for the reference current (phase overcurrent pickup) in dynamic mode. This
threshold value is only effective while the hold time for dynamic settings is elapsing.
Definite Time
IEC Standard Inverse
IEC Very Inverse
IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IDMT1:
Definite Time IEEE Very Inverse -
Phase Charac SGx
IEEE Extr. Inverse
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
081 053 082 053 083 053 084 053 OP Fig. 34
IDMT2: As per ‘IDMT1: Phase
Definite Time -
Phase Charac SGx Charac SGx’
081 173 082 173 083 173 084 173 OP Fig. 34
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-93

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: As per ‘IDMT1: Phase
Definite Time -
Phase Charac SGx Charac SGx’
081 193 082 193 083 193 084 193 OP Fig. 34
Setting for the tripping characteristic (phase current system).
IDMT1: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 054 082 054 083 054 084 054 OP Fig. 34
IDMT2: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 174 082 174 083 174 084 174 OP Fig. 34
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 194 082 194 083 194 084 194 OP Fig. 34
TMS or time dial setting of the starting characteristic (phase current system).
ST
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 057 082 057 083 057 084 057 OP Fig. 34
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 177 082 177 083 177 084 177 OP Fig. 34
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 197 082 197 083 197 084 197 OP Fig. 34
Setting for the minimum trip time (phase current system).
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 055 082 055 083 055 084 055 OP Fig. 34
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 175 082 175 083 175 084 175 OP Fig. 34
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 195 082 195 083 195 084 195 OP Fig. 34
Setting for the hold time for storing the starting time once the starting has dropped out
(phase current system).
IDMT1: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 056 082 056 083 056 084 056 OP Fig. 34
IDMT2: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 176 082 176 083 176 084 176 OP Fig. 34
IDMT3: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 196 082 196 083 196 084 196 OP Fig. 34
Setting for the release characteristic (phase current system).
P63x/UK ST/A54 Settings

(ST) 4-94 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
IDMT1: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 111 082 111 083 111 084 111 OP Fig. 35
Blocked/
IDMT2: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 121 082 121 083 121 084 121 OP Fig. 35
Blocked/
IDMT3: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 131 082 131 083 131 084 131 OP Fig. 35
Setting for the pickup current (negative-sequence current system).
IDMT1: Blocked/
Blocked 0.80 In 0.01 In
Iref, I2 dynamic SGx 0.01 In
081 112 082 112 083 112 084 112 OP Fig. 35

ST IDMT2:
Iref, I2 dynamic SGx
Blocked
Blocked/
0.01 In
0.80 In 0.01 In

081 122 082 122 083 122 084 122 OP Fig. 35


IDMT3: Blocked/
Blocked 0.80 In 0.01 In
Iref, I2 dynamic SGx 0.01 In
081 132 082 132 083 132 084 132 OP Fig. 35
Setting for the pickup current (negative-sequence current system). This value is only
effective while the hold time for dynamic settings is elapsing.
Definite Time
IEC Standard Inverse
IEC Very Inverse
IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IDMT1:
Definite Time IEEE Very Inverse -
I2 Charac SGx
IEEE Extr. Inverse
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
081 113 082 113 083 113 084 113 OP Fig. 35
IDMT2: As per ‘IDMT1:
Definite Time -
I2 Charac SGx I2 Charac SGx’
081 123 082 123 083 123 084 123 OP Fig. 35
IDMT3: As per ‘IDMT1:
Definite Time -
I2 Charac SGx I2 Charac SGx’
081 133 082 133 083 133 084 133 OP Fig. 35
Setting for the tripping characteristic (negative-sequence current system).
IDMT1: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 114 082 114 083 114 084 114 OP Fig. 35
IDMT2: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 124 082 124 083 124 084 124 OP Fig. 35
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-95

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 134 082 134 083 134 084 134 OP Fig. 35
TMS or time dial setting of the starting characteristic (negative-sequence current system).
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 117 082 117 083 117 084 117 OP Fig. 35
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 127 082 127 083 127 084 127 OP Fig. 35
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 137 082 137 083 137 084 137 OP Fig. 35
Setting for the minimum trip time characteristic (negative-sequence current system).
ST
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 115 082 115 083 115 084 115 OP Fig. 35
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 125 082 125 083 125 084 125 OP Fig. 35
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 135 082 135 083 135 084 135 OP Fig. 35
Setting for the hold time for storing the starting time once the starting has dropped out
characteristic (negative-sequence current system).
IDMT1: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 116 082 116 083 116 084 116 OP Fig. 35
IDMT2: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 126 082 126 083 126 084 126 OP Fig. 35
IDMT3: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 136 082 136 083 136 084 136 OP Fig. 35
Setting for the release characteristic (negative-sequence current system).
Blocked/
IDMT1: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 061 082 061 083 061 084 061 OP Fig. 36
Blocked/
IDMT2: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 181 082 181 083 181 084 181 OP Fig. 36
Blocked/
IDMT3: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 201 082 201 083 201 084 201 OP Fig. 36
Setting for the pickup current (residual current system).
P63x/UK ST/A54 Settings

(ST) 4-96 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT1: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 062 082 062 083 062 084 062 OP Fig. 36
IDMT2: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 182 082 182 083 182 084 182 OP Fig. 36
IDMT3: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 202 082 202 083 202 084 202 OP Fig. 36
Setting for the pickup current (residual current system) in dynamic mode. This operate
value is only effective while the hold time for dynamic settings is elapsing.
Definite Time
IEC Standard Inverse
IEC Very Inverse
ST IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IDMT1: IEC Standard
IEEE Very Inverse -
N Charac SGx Inverse
IEEE Extr. Inverse
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
081 063 082 063 083 063 084 063 OP Fig. 36
IDMT2: IEC Standard As per ‘IDMT1:
-
N Charac SGx Inverse N Charac SGx’
081 183 082 183 083 183 084 183 OP Fig. 36
IDMT3: IEC Standard As per ‘IDMT1:
-
N Charac SGx Inverse N Charac SGx’
081 203 082 203 083 203 084 203 OP Fig. 36
Setting for the tripping characteristic (residual current system).
IDMT1: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 064 082 064 083 064 084 064 OP Fig. 36
IDMT2: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 184 082 184 083 184 084 184 OP Fig. 36
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 204 082 204 083 204 084 204 OP Fig. 36
TMS or time dial setting of the starting characteristic (residual current system).
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 067 082 067 083 067 084 067 OP Fig. 36
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 187 082 187 083 187 084 187 OP Fig. 36
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-97

Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 207 082 207 083 207 084 207 OP Fig. 36
Setting for the minimum trip time (residual current system).
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 065 082 065 083 065 084 065 OP Fig. 36
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 185 082 185 083 185 084 185 OP Fig. 36
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 205 082 205 083 205 084 205 OP Fig. 36
Setting for the hold time for storing the starting time once the starting has dropped out
(residual current system).
ST
IDMT1: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 066 082 066 083 066 084 066 OP Fig. 36
IDMT2: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 186 082 186 083 186 084 186 OP Fig. 36
IDMT3: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 206 082 206 083 206 084 206 OP Fig. 36
Setting for the release characteristic (residual current system).

1.3.3.6 Thermal overload protection (THRM)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
THRM1:
No No Yes -
Enable SGx
081 070 082 070 083 070 084 070 OP Fig. 41
THRM2:
No No Yes -
Enable SGx
081 090 082 090 083 090 084 090 OP Fig. 41
This setting specifies the setting group to be enabled for thermal overload protection.
THRM1:
1.00 In 0.10 In 4.00 In 0.01 In
Iref Rating SGx
081 074 082 074 083 074 084 074 OP Fig. 45
THRM2:
1.00 In 0.10 In 4.00 In 0.01 In
Iref Rating SGx
081 094 082 094 083 094 084 094 OP Fig. 45
Setting for the reference current.
P63x/UK ST/A54 Settings

(ST) 4-98 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1: Start
1.15 1.05 1.50 0.01
Fact.OL_RC SGx
081 075 082 075 083 075 084 075 OP Fig. 45
THRM2: Start
1.15 1.05 1.50 0.01
Fact.OL_RC SGx
081 095 082 095 083 095 084 095 OP Fig. 45
The starting factor k must be set in accordance with the maximum permissible continuous
thermal current of the protected object:
I therm,prot.object
k=
Inom,prot.object

THRM1: Tim.const
30.0 min 1.0 min 1000.0 min 0.1 min
1(heat) SGx
081 082 082 082 083 082 084 082 OP Fig. 45
THRM2: Tim.const
ST 1(heat) SGx
30.0 min 1.0 min 1000.0 min 0.1 min

081 102 082 102 083 102 084 102 OP Fig. 45


Setting for the thermal time constants of the protected object with current flow (heating).
THRM1: Tim.const
30.0 min 1.0 min 1000.0 min 0.1 min
2(cool) SGx
081 083 082 083 083 083 084 083 OP Fig. 45
THRM2: Tim.const
30.0 min 1.0 min 1000.0 min 0.1 min
2(cool) SGx
081 103 082 103 083 103 084 103 OP Fig. 45
Setting for the thermal time constants of the protected object without current flow. This
setting option is only relevant when machines are running. In all other cases time constant
2 must be set equal to time constant 1.
THRM1: Max perm
120 °C 0 °C 300 °C 1 °C
obj tmp. SGx
081 077 082 077 083 077 084 077 OP Fig. 45
THRM2: Max perm
120 °C 0 °C 300 °C 1 °C
obj tmp. SGx
081 097 082 097 083 097 084 097 OP Fig. 45
Setting for the maximum permissible temperature of the protected object.
THRM1: Max perm
40 °C 0 °C 70 °C 1 °C
cool tmp. SGx
081 080 082 080 083 080 084 080 OP Fig. 45
THRM2: Max perm
40 °C 0 °C 70 °C 1 °C
cool tmp. SGx
081 100 082 100 083 100 084 100 OP Fig. 45
Setting for the maximum permissible temperature of the coolant.
Note: This setting is only effective if the coolant temperature is measured via the
PT100 or the 20mA input.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-99

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Default Temp. Value
THRM1: Select CT
Default Temp. Value From PT100 -
Ambient SGx
From 20 mA Input
081 072 082 072 083 072 084 072 OP Fig. 44
Default Temp. Value
THRM2: Select CT
Default Temp. Value From PT100 -
Ambient SGx
From 20 mA Input
081 092 082 092 083 092 084 092 OP Fig. 44
Select the mode of the coolant temperature acquisition. Select from:
• No data acquisition. A default temperature value is used instead
• Data acquisition via the PT 100 input
• Data acquisition via the 20 mA input

THRM1:
40 °C -40 °C 70 °C 1 °C
Default CT Amb SGx
081 081 082 081 083 081 084 081 OP Fig. 45 ST
THRM2:
40 °C -40 °C 70 °C 1 °C
Default CT Amb SGx
081 101 082 101 083 101 084 101 OP Fig. 45
Setting for the coolant temperature to be used for calculation of the trip time if there is no
data acquisition for the coolant temperature.
THRM1:
Yes No Yes -
Blk for CTA Fail SGx
081 073 082 073 083 073 084 073 OP Fig. 44
THRM2:
Yes No Yes -
Blk for CTA Fail SGx
081 093 082 093 083 093 084 093 OP Fig. 44
This setting specifies whether the thermal overload protection function will be blocked in
the event of faulty coolant temperature acquisition.
THRM1: T> Alarm
95 % 50 % 200 % 1%
Reset,% SGx
081 079 082 079 083 079 084 079 OP Fig. 45
THRM2: T> Alarm
95 % 50 % 200 % 1%
Reset,% SGx
081 099 082 099 083 099 084 099 OP Fig. 45
Setting for the operate value of the warning stage.
THRM1: T> Trip
100 % 50 % 200 % 1%
Reset,% SGx
081 076 082 076 083 076 084 076 OP Fig. 45
THRM2: T> Trip
100 % 50 % 200 % 1%
Reset,% SGx
081 096 082 096 083 096 084 096 OP Fig. 45
Setting for the operate value of the trip stage.
Note: If the operating mode has been set to Absolute Replica, the setting here will
be automatically set to 100% and this parameter is hidden as far as the
local control panel is concerned.
P63x/UK ST/A54 Settings

(ST) 4-100 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1:
2% 2% 30 % 1%
Trip Hysteresis SGx
081 078 082 078 083 078 084 078 OP Fig. 45
THRM2:
2% 2% 30 % 1%
Trip Hysteresis SGx
081 098 082 098 083 098 084 098 OP Fig. 45
Setting for the hysteresis of the trip stage.
THRM1: Blocked/
30.0 min 1000.0 min 0.1 min
Pre-Trip Alarm SGx 0.0 min
081 085 082 085 083 085 084 085 OP Fig. 45
THRM2: Blocked/
30.0 min 1000.0 min 0.1 min
Pre-Trip Alarm SGx 0.0 min
081 105 082 105 083 105 084 105 OP Fig. 45

ST A warning will be given in advance of the trip. The time difference between the warning
time and the trip time is set here.

1.3.3.7 Under/overvoltage protection (V<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
V<>: Enable SGx No No Yes -
076 000 077 000 078 000 079 000 OP Fig. 47
The time-voltage protection will be enabled in the setting group selected with this setting.
Blocked/
V<>: V> SGx 1.10 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 003 077 003 078 003 079 003 OP Fig. 48
Setting for the operate value V>.
Blocked/
V<>: V>> SGx 1.10 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 004 077 004 078 004 079 004 OP Fig. 48
Setting for the operate value V>>.
Blocked/
V<>: tV> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 005 077 005 078 005 079 005 OP Fig. 48
Setting for the operate delay of time-overvoltage stage V>.
Blocked/
V<>: tV>> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 006 077 006 078 006 079 006 OP Fig. 48
Setting for the operate delay of time-overvoltage stage V>>.
Blocked/
V<>: V< SGx 0.80 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 007 077 007 078 007 079 007 OP Fig. 49
Setting for the operate value V<.
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-101

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
V<>: V<< SGx 0.80 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 008 077 008 078 008 079 008 OP Fig. 49
Setting for the operate value V<<.
Blocked/
V<>: Vmin> SGx 0.25 Vn 0.60 Vn 0.01 Vn
0.00 Vn
076 046 077 046 078 046 079 046 OP Fig. 49
Setting for Vmin>. Can be used to prevent undervoltage stages operating when the VT is
dead, restricting operation to low voltage conditions only.
Blocked/
V<>: tV< SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 009 077 009 078 009 079 009 OP Fig. 49
Setting for the operate delay of time-undervoltage stage V<.

V<>: tV<< SGx 1.00 s


Blocked/
0.00 s
100.00 s 0.01 s ST
076 010 077 010 078 010 079 010 OP Fig. 49
Setting for the operate delay of time-undervoltage stage V<<.
Blocked/
V<>: tTransient SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 029 077 029 078 029 079 029 OP Fig. 49
Setting for the time limit of the signals generated by the time-undervoltage stages.
V<>:
3% 1% 10 % 1%
Hyst. V<> Meas. SGx
076 048 077 048 078 048 079 048 OP Fig. 49
Setting for the hysteresis of the trigger stages for measured-voltage monitoring.

1.3.3.8 Frequency protection (f<>)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
f<>: Enable SGx No No Yes -
018 196 018 197 018 198 018 199 OP Fig. 50
This setting specifies the setting group to be enabled for over/underfrequency protection.
f
f<>:
f f with df/dt -
Oper. Mode f1 SGx
f + Delta f/Delta t
018 120 018 121 018 122 018 123 OP Fig. 53
f
f<>:
f f with df/dt -
Oper. Mode f2 SGx
f + Delta f/Delta t
018 144 018 145 018 146 018 147 OP Fig. 53
f
f<>:
f f with df/dt -
Oper. Mode f3 SGx
f + Delta f/Delta t
018 168 018 169 018 170 018 171 OP Fig. 53
P63x/UK ST/A54 Settings

(ST) 4-102 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
f
f<>:
f f with df/dt -
Oper. Mode f4 SGx
f + Delta f/Delta t
018 192 018 193 018 194 018 195 OP Fig. 53
Setting for the operating mode of the timer stages of over/underfrequency protection, and
whether instantaneous rate of change of frequency, or average frequency gradient shall
supervize.
Blocked/
f<>: f1 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 100 018 101 018 102 018 103 OP Fig. 53
Blocked/
f<>: f2 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 124 018 125 018 126 018 127 OP Fig. 53
Blocked/
f<>: f3 SGx 49.80 Hz 70.00 Hz 0.01 Hz
ST 40.00 Hz
018 148 018 149 018 150 018 151 OP Fig. 53
Blocked/
f<>: f4 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 172 018 173 018 174 018 175 OP Fig. 53
Setting for the frequency threshold. The over/underfrequency protection function operates
if one of the following two conditions applies:
• The threshold is higher than the set nominal frequency and the frequency
exceeds this threshold
• The threshold is lower than the set nominal frequency and the frequency falls
below this threshold
Depending on the selected operating mode, a signal will be issued without further
monitoring or, alternatively, further monitoring mechanisms will be triggered.
Blocked/
f<>: tf1 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 104 018 105 018 106 018 107 OP Fig. 53
Blocked/
f<>: tf2 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 128 018 129 018 130 018 131 OP Fig. 53
Blocked/
f<>: tf3 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 152 018 153 018 154 018 155 OP Fig. 53
Blocked/
f<>: tf4 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 176 018 177 018 178 018 179 OP Fig. 53
Setting for the operate delay of over/underfrequency protection.
Blocked/
f<>: df1/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 108 018 109 018 110 018 111 OP Fig. 53
Blocked/
f<>: df2/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 132 018 133 018 134 018 135 OP Fig. 53
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-103

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
f<>: df3/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 156 018 157 018 158 018 159 OP Fig. 53
Blocked/
f<>: df4/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 180 018 181 018 182 018 183 OP Fig. 53
Setting for the frequency gradient to be monitored.
Note: This setting is ineffective unless the operating mode f with df/dt has been
selected.
Blocked/
f<>: Delta f1 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 112 018 113 018 114 018 115 OP Fig. 53
Blocked/
f<>: Delta f2 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 136 018 137 018 138 018 139 OP Fig. 53
ST
Blocked/
f<>: Delta f3 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 160 018 161 018 162 018 163 OP Fig. 53
Blocked/
f<>: Delta f4 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 184 018 185 018 186 018 187 OP Fig. 53
Setting for delta f.
Note: This setting is ineffective unless the operating mode f with Delta f/Delta t
has been selected.
f<>: Delta t1 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 116 018 117 018 118 018 119 OP Fig. 53
f<>: Delta t2 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 140 018 141 018 142 018 143 OP Fig. 53
f<>: Delta t3 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 164 018 165 018 166 018 167 OP Fig. 53
f<>: Delta t4 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 188 018 189 018 190 018 191 OP Fig. 53
Setting for delta t.
Note: This setting is ineffective unless the operating mode f with Delta f/Delta t
has been selected.

1.3.3.9 Overfluxing protection (V/f)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
V/f: Enable SGx No No Yes -
018 210 082 210 083 210 084 210 OP Fig. 54
This setting specifies the setting group to be enabled for overfluxing protection.
P63x/UK ST/A54 Settings

(ST) 4-104 MiCOM P631, P632, P633, P634

Setting Range
Menu Text Default Setting Step Size
Min. Max.
V/f: Blocked/
1.05 Vn/fn 1.20 Vn/fn 0.01 Vn/fn
V/f> (Alarm) SGx 1.00 Vn/fn

018 211 082 211 083 211 084 211 OP Fig. 56


Pickup value of definite time warning stage of overfluxing protection.
Blocked/
V/f: V/f(t)> SGx 1.10 Vn/fn 1.50 Vn/fn 0.01 Vn/fn
1.05 Vn/fn
018 212 082 212 083 212 084 212 OP Fig. 60
Pickup value of the variable time characteristic for overfluxing protection.
Blocked/
V/f: V/f>> SGx Blocked 1.60 Vn/fn 0.01 Vn/fn
1.05 Vn/fn
018 213 082 213 083 213 084 213 OP Fig. 57
Pickup value of definite time tripping stage of overfluxing protection.
V/f: tV/f> SGx 1s Blocked/1 s 10000 s 1s
ST 018 214 082 214 083 214 084 214 OP Fig. 56
Time delay for definite time warning stage of overfluxing protection.
V/f: t at V/f=1.05 SGx 72.8 s 1.0 s 1000.0 s 0.1 s
018 217 082 217 083 217 084 217 OP Fig. 58,
60
V/f: t at V/f=1.10 SGx 18.8 s 1.0 s 1000.0 s 0.1 s
018 218 082 218 083 218 084 218 OP Fig. 58,
60
V/f: t at V/f=1.15 SGx 8.8 s 1.0 s 1000.0 s 0.1 s
018 219 082 219 083 219 084 219 OP Fig. 58,
60
V/f: t at V/f=1.20 SGx 5.3 s 1.0 s 1000.0 s 0.1 s
018 220 082 220 083 220 084 220 OP Fig. 58,
60
V/f: t at V/f=1.25 SGx 3.7 s 1.0 s 1000.0 s 0.1 s
018 221 082 221 083 221 084 221 OP Fig. 58,
60
V/f: t at V/f=1.30 SGx 2.8 s 1.0 s 1000.0 s 0.1 s
018 222 082 222 083 222 084 222 OP Fig. 58,
60
V/f: t at V/f=1.35 SGx 2.3 s 1.0 s 1000.0 s 0.1 s
018 223 082 223 083 223 084 223 OP Fig. 58,
60
V/f: t at V/f=1.40 SGx 1.9 s 1.0 s 1000.0 s 0.1 s
018 224 082 224 083 224 084 224 OP Fig. 58,
60
V/f: t at V/f=1.45 SGx 1.7 s 1.0 s 1000.0 s 0.1 s
018 225 082 225 083 225 084 225 OP Fig. 58,
60
V/f: t at V/f=1.50 SGx 1.5 s 1.0 s 1000.0 s 0.1 s
018 226 082 226 083 226 084 226 OP Fig. 58,
60
Settings P63x/UK ST/A54

MiCOM P631, P632, P633, P634 (ST) 4-105

Setting Range
Menu Text Default Setting Step Size
Min. Max.
V/f: t at V/f=1.55 SGx 1.4 s 1.0 s 1000.0 s 0.1 s
018 227 082 227 083 227 084 227 OP Fig. 58,
60
V/f: t at V/f=1.60 SGx 1.3 s 1.0 s 1000.0 s 0.1 s
018 228 082 228 083 228 084 228 OP Fig. 58,
60
Time delay settings to configure the overfluxing protection characteristic for V/f values from
1.05 to 1.60 in 0.05 V/Hz steps.
V/f: Reset Time SGx 0s 0s 10000 s 1s
018 230 082 230 083 230 084 230 OP Fig. 60
Reset delay for the variable time tripping characteristic of overfluxing protection.
V/f: tV/f>> SGx Blocked Blocked/0 s 10000 s 1s
018 229 082 229 083 229 084 229
Time delay for definite time tripping stage of overfluxing protection. ST
1.3.3.10 Current transformer supervision (CTS)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
CTS: Enable SGx No No Yes -
001 118 001 119 001 120 001 121 OP Fig. 64
This setting specifies the setting group to be enabled for CT supervision.
CTS: I1> SGx 0.10 Iref 0.05 Iref 4.00 Iref 0.01 Iref
001 111 001 115 001 116 001 117 OP Fig. 66
Positive sequence current threshold to be exceeded in order to determine CTS condition.
CTS: I2/I1> SGx 0.05 0.05 1.00 0.01
001 102 001 103 001 104 001 105 OP Fig. 66
Low set negative to positive sequence current ratio that is not to be exceeded in order to
determine CTS condition.
CTS: I2/I1>> SGx 0.40 0.05 1.00 0.01
001 122 001 123 001 124 001 125 OP Fig. 66
High set negative to positive sequence current ratio to be exceeded at exactly one end in
order to determine CTS condition.
CTS: t(Alarm) SGx 1.00 s 0.00 s 10.00 s 0.01 s
001 126 001 127 001 128 001 129 OP Fig. 69
Alarming delay timer for CTS indication.
Blocked/
CTS: t(Latch) SGx 1.00 s 10.00 s 0.01 s
0.00 s
001 130 001 131 001 132 001 133 OP Fig. 69
Latching alarm delay timer for CTS indication.
P63x/UK ST/A54 Settings

(ST) 4-106 MiCOM P631, P632, P633, P634

1.3.3.11 Broken conductor detection (BC_)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
BC_1: Enable SGx No No Yes -
081 038 082 038 083 038 084 038 OP Fig. 62
BC_2: Enable SGx No No Yes -
081 039 082 039 083 039 084 039 OP Fig. 62
BC_3: Enable SGx No No Yes -
081 040 082 040 083 040 084 040 OP Fig. 62
BC_4: Enable SGx No No Yes -
081 041 082 041 083 041 084 041 OP Fig. 62
This setting specifies the end to be enabled for broken conductor detection for each setting
group.
ST BC_1: I2/I1> SGx 0.30 0.20 1.00 0.01
081 042 082 042 083 042 084 042 OP Fig. 63
BC_2: I2/I1> SGx 0.30 0.20 1.00 0.01
081 043 082 043 083 043 084 043 OP Fig. 63
BC_3: I2/I1> SGx 0.30 0.20 1.00 0.01
081 044 082 044 083 044 084 044 OP Fig. 63
BC_4: I2/I1> SGx 0.30 0.20 1.00 0.01
081 045 082 045 083 045 084 045 OP Fig. 63
Pickup level of broken conductor detection based on ratio of negative to positive sequence
current.
BC_1:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 046 082 046 083 046 084 046 OP Fig. 63
BC_2:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 047 082 047 083 047 084 047 OP Fig. 63
BC_3:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 048 082 048 083 048 084 048 OP Fig. 63
BC_4:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 049 082 049 083 049 084 049 OP Fig. 63
Operate delay for broken conductor detection.

You might also like