Cooling Water Towers
Cooling Water Towers
Cooling Water Towers
1. References
2. Scope
3. Pressure Relief Valve Installations
4. Thermal Relief Valve Installations
5. Rupture Disk Installation
6. Venting Atmospheric and Low Pressure Storage Tanks
1. References
The design of a relief system is governed by the following:
- API.RP520 “design and installation of pressure - relieving systems in refineries”
- British Factory Acts, in relation to steam raising plants, if applicable
- Local authorities and Clients requirements
- Good engineering practice
The design of atmospheric and low pressure venting systems are governed by the following :
- API.RP2000 “Venting atmospheric and low pressure storage tanks”
- Local authorities and Clients requirements
- Good engineering practice
2. Scope
This guide is intended to cover methods of installation for pressure relief valves and their associated
pipe work and fittings.
The installation of rupture disks.
Venting storage tanks.
The flow diagram will determine if the discharge is to atmosphere, or to a closed discharge header,
see below figures for details.
It is poor practice to mount the relief valve at the end of a long, horizontal inlet pipe through which
there is normally no flow
Foreign matter may accumulate or liquid may be trapped and may interfere with the operation of the
valve or be the cause of more frequent valve maintenance.
Process laterals generally should not be connected to relief valve inlet piping, see below figure 4.
Proximity of other valves and equipment, the recommendations laid down in below figures 4, 6 and 7
should be followed if possible for the minimum number of straight pipe diameters between the device
causing turbulence and the relief valve. The above does not apply to relief valves fitted with stop
valves, see below figures.
Relief valves discharging into a relief header must be located at an elevation above the relief header
so that the discharge line is free draining. Under no circumstances may the discharge line or the relief
header be pocketed.
Figures 1 - 8 Incl.
RECOMMENDED TYPICAL RELIEF VALVE INSTALLATION (BASED ON API RP 520)
RECOMMENDED TYPICAL RELIEF VALVE INSTALLATIONS (EXTRACTED FROM API RP 520)
RECOMMENDED TYPICAL RELIEF VALVE INSTALLATIONS (EXTRACTED FROM API RP 520)
RECOMMENDED TYPICAL RELIEF VALVE INSTALLATION
RECOMMENDED TYPICAL RELIEF VALVE INSTALLATION
RECOMMENDED TYPICAL RUPTURE DISK INSTALLATION
TYPICAL PRESSURE & VACUUM BREATHING VALVE