Cable Gland Types E1FW, E2FW, E1FX, E2Fx, E1Fu & E2Fu

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SCAN FOR INSTALLATION VIDEOS

TECHNICAL DATA

INSTALLATION INSTRUCTIONS FOR


CABLE GLAND TYPE : E** Family of Glands
INGRESS PROTECTION : IP66, (IP67, IP68 available upon request)
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO / IEC 80079-34:2001
EXPLOSIVE ATMOSPHERES CLASSIFICATION
ATEX CERTIFICATION No
ATEX CERTIFICATION CODE
IECEx CERTIFICATION No
IECEx CERTIFICATION CODE
c-CSA-us CERTIFICATION No
: SIRA 13ATEX1071X, SIRA13ATEX4077X
: II 2/3G 1D Ex d IIC Gb / Ex e IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
: IECEx SIR 13.0026X
: Ex d IIC Gb / Ex e IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
: 02.1310517
CMP CABLE GLAND TYPE “E”
c-CSA-us CERTIFICATION CODE : Ex d IIC / Ex e II / Ex nR II; Class I Zone 1, AEx e II / AEx nR II

INSTALLATION INSTRUCTIONS FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
ARMOUR & SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON “E2”
SPECIAL CONDITIONS FOR SAFE USE
For ATEX & IECEx certification:
1. E type glands used for terminating braided cables are only suitable for fixed installations. Cables must be clamped to prevent pulling or twisting.
VARIANT). FOR USE IN HAZARDOUS LOCATIONS.
FOR cCSAus Certification:
1. These glands are not suitable for use with flameproof enclosures installed in Group IIC atmospheres which have a volume greater than 2000 cc (2 Litre).
2. These glands are for use with Certified Marine Shipboard metal braided cables constructed in according to cCSAus Std. 245 and
IEEE45/IEC600092-353 Standards, or Certified equivalent), for use on Shipboards and Offshore Rigs/Platforms only INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 2014/34/EU
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

CABLE GLAND TYPES


Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud
Outer Seal Tightening Guide
Number of turns GLAND SIZE
to tighten 20S16 20S 20 25S 25 32 40 50S 50 63S 63 75S 75
CABLE DIAMETER

E1FW, E2FW, E1FX,


0.5 13.2 15.9 20.9 22.0 26.2 33.9
1 12.5 15.3 20.0 21.2 25.4 32.9 40.4 46.7 52.8 59.2 65.9 72.1 78.5
1.5 11.9 14.7 19.0 20.4 24.6 31.9 39.0 45.4 51.4 57.7 64.6 70.6 77.2
2 11.2 14.2 18.1 19.6 23.8 30.8 37.6 44.1 50.0 56.2 63.4 69.2 75.9
2.5 10.5 13.6 17.2 18.8 23.0 29.8 36.2 42.9 48.7 54.7 62.1 67.7 74.6

E2FX, E1FU & E2FU


3 9.8 13.0 16.2 18.0 22.2 28.8 34.8 41.6 47.3 53.2 60.9 66.3 73.3
3.5 9.2 12.4 15.3 17.2 21.4 27.8 33.5 40.3 45.9 51.6 59.6 64.8 71.9
4 8.5 11.8 14.4 16.4 20.6 26.8 32.1 39.0 44.5 50.1 58.4 63.4 70.6
4.5 7.8 11.2 13.4 15.6 19.8 25.7 30.7 37.8 43.2 48.6 57.1 61.9 69.3
5 7.1 10.7 12.5 14.8 19.0 24.7 29.3 36.5 41.8 47.1 55.9 60.5 68.0
5.5 6.5 10.1 12.0 14.0 18.2 23.7 27.9 35.2 40.4 45.6 54.6 59.0 66.7
6 5.8 9.5

Cable Available Entry Threads Thread Cable Bedding Overall Cable Armour Wire Diameter Across Across Ordering PVC
Diameter Diameter Flats Corners Protrusion
Gland Standard Option Length Grooved Cone Stepped Cone Reference Shroud
Length
Size Metric NPT NPT Metric Min Max Min Max Min Max Min Max Max Max (Brass Metric) Ref
20S/16 M20 1/2” 3/4” 15.0 3.1 8.6 6.1 13.2 0.15 0.5 0.8 1.25 24.0 26.4 58.5 20S16E1FU1RA PVC04
20S M20 1/2” 3/4” 15.0 6.1 11.6 9.5 15.9 0.15 0.5 0.8 1.25 24.0 26.4 58.5 20SE1FU1RA PVC04

CMP Document No. FI407 CSA Issue 11 09/14, IEC Issue 11 09/14
20 M20 1/2” 3/4” 15.0 6.5 13.9 12.5 20.9 0.2 0.5 0.8 1.25 30.5 33.6 60.5 20E1FU1RA PVC06
25S M25 3/4” 1” 15.0 11.1 19.9 14.0 22.0 0.2 0.6 1.25 1.6 37.5 41.3 67.5 25SE1FU1RA PVC09
25 M25 3/4” 1” 15.0 11.1 19.9 18.2 26.2 0.2 0.6 1.25 1.6 37.5 41.3 67.5 25E1FU1RA PVC09
32 M32 1” 1-1/4” 15.0 17.0 26.2 23.7 33.9 0.2 0.6 1.6 2.0 46.0 50.6 69.5 32E1FU1RA PVC11
40 M40 1-1/4” 1-1/2” 15.0 22.0 32.1 27.9 40.4 0.2 0.8 1.6 2.0 55.0 60.5 78.0 40E1FU1RA PVC15
50S M50 1-1/2” 2” 15.0 29.5 38.1 35.2 46.7 0.2 0.8 2.0 2.5 60.0 66.0 75.5 50SE1FU1RA PVC18
50 M50 2” 2-1/2” 15.0 35.6 44.0 40.4 53.1 0.3 0.8 2.0 2.5 70.0 77.0 80.5 50E1FU1RA PVC21
63S M63 2” 2-1/2” 15.0 40.1 49.9 45.6 59.4 0.3 0.8 2.0 2.5 75.0 82.5 91.5 63SE1FU1RA PVC23
63 M63 2-1/2” 3” 15.0 47.2 55.9 54.6 65.9 0.3 0.8 2.0 2.5 80.0 88.0 92.0 63E1FU1RA PVC25
75S M75 2-1/2” 3” 15.0 52.8 61.9 59.0 72.1 0.3 0.8 2.0 2.5 89.0 97.9 99.0 75SE1FU1RA PVC28
75 M75 3” 3-1/2” 15.0 59.1 67.9 66.7 78.5 0.3 0.8 2.5 3.0 99.0 108.9 102.0 75E1FU1RA PVC30
90 M90 3” 4” 24.0 66.6 79.9 76.2 90.4 0.4 0.8 3.0 3.5 114.0 125.4 120.0 90E1FU1RA PVC32
E1FW - SWA Armour
100 M100 4” 5” 24.0 76.0 90.9 86.1 101.5 0.4 0.8 3.15 4.0 123.0 135.3 148.0 100E1FU1RA LSF33 E2FW - SWA Armour for lead
115 M115 4” 5” 24.0 86.0 97.9 101.5 110.3 0.4 0.8 3.15 4.0 133.4 146.7 169.0 115E1FU1RA LSF34 sheathed cable
130 M130 5” 6” 24.0 97.0 114.9 114.2 123.3 0.4 0.8 3.15 4.0 146.0 160.7 183.0 130E1FU1RA LSF35
E1FX - Braid, Tape, etc Armour
Dimensions are displayed in millimetres unless otherwise stated
Order codes shown are for E1FU glands - For e.g. E1FWD glands substitute E1FWD for E1FU - e.g. 20E1FWD1RA
E2FX - Braid, Tape, etc Armour for
* Please note that the overall maximum cable bedding diameter for “E2” variants should be reduced by 1mm to allow for the inner lead sheath lead sheathed cable
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards:- E1FU - Universal Gland for all
EN 60079-0:2012, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2010, EN 60079-31:2009, BS 6121:1989, EN 62444:2013
Armour Types
E2FU - Universal Gland for all
David Willcock - Certification Engineer (Authorised Person) Armour Types with lead
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS sheathed cable
0518
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
E-Mail: customerservices@cmp-products.co.uk • Web: www.cmp-products.com

www.cmp-products.com Logo’s shown for illustration purposes only. Please check certification for details
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES “E” 4. Locate the Armour Cone (3) into its recess in the Main Item (2). (N.B. For E1FU and E2FUvariants, make sure the correct side of
the cone is outermost - grooved for braid/tape armour and stepped for SWA). Pass the cable through sub-assembly “A” until the
CABLE GLAND COMPONENTS - It is not necessary to dismantled the cable gland any further than illustrated below armour engaged with the cone. Spread the armour evenly around the cone.
Universal Cone
1. Entry Component (E1FU, E2FU) use
stepped side for SWA
SUB ASSEMBLY A and grooved side for SUB ASSEMBLY B
2. Main Item all other armours

3. Detachable Armour Cone


4. AnyWay Clamping Ring
5. Body
6. Outer Seal Nut 1. 2. 3. 4. 5. 6.

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION 5. While continuing to push the cable forward to maintain contact between the armour and the cone, tighten the Main Item (2)
until the inner seal makes contact with the cable inner sheath (heavier resistance is felt at this point). Tighten a further full turn.
1. If required fit shroud over the cable outer sheath; NOTE: The earthing device on E2* type glands will automatically engage the lead sheath.

Prepare the cable by stripping back the cable outer sheath and armour to suit the equipment geometry.
Expose the armour by stripping back the outer sheath further using the table below as a guide.
If applicable remove any tapes or wrappings to expose cable inner sheath.

Cable Strip Tape armour should be further


Length “L”
prepared by cutting the tape into
strips as shown below:

6. Hold the Main Item (2) with a spanner and tighten sub-assembly “B” onto sub-assembly “A” using a spanner until all available
threads are used.

CABLE GLAND SIZE 20S/16, 20S, 20 25S, 25, 32, 40 50S, 50, 63S, 63 75S, 75, 90, 100, 115, 130

CABLE STRIP LENGTH “L” 12mm 15mm 18mm 20mm

2. Separate the gland into two sub-assemblies “A & B”. Ensuring that the Outer Seal Nut (6) is relaxed, pass sub-assembly “B” over
the cable outer sheath and armour followed by the “AnyWay” clamping ring (4).

Note: On maximum size cables the clamping ring may 7. Only using finger pressure, tighten the outer seal nut assembly (6) until light resist-
only pass over the armour. ance to tightening is met.

Then either use the outer seal tightening guide tape or table on the rear of the page to
determine how much further to tighten the seal using a spanner (using the outer seal
tightening guide is recomended).
3. Ensure that the inner seal is relaxed by slackening the Main Item (2). Secure sub-assembly “A” into the equipment either by
screwing the Entry Item (1) into a threaded hole or by securing it in a clearance hole using a locknut as applicable. Wrap the outer seal tightening guide tape around the cable to show the amount of
spanner turns needed (as shown here). Make sure the correct side of the outer seal
tightening guide tape is used depending on the cable gland size.

www.cmp-products.com www.cmp-products.com