DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or
operate the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single asynchronous motor with a motor cable length less than 50 meters (164ft).
In any other case, consult the drive installation manuals (1760643 or 1760655) and programming manual (1760649) on www.schneider-electric.com.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
ATV61HU15N4
1.5KW - 2HP - 380/480V
uh3
ATV61H h1 h2
D55M3X, D75M3X, mm (in.) mm (in.) ATV61H h3 h4
100 (3.9) 100 (3.9) mm (in.) mm (in.)
D90M3X, D90N4, C11N4 D18M3X to D45M3X,
C13N4, C16N4, C22N4, 150 (5.9) u h4 u h4 D22N4 to D75N4
C11Y, C13Y, C16Y, C20Y 150 (5.9) U30Y to D90Y 100 (3.9) 50 (1.9)
C25N4, C31N4, C25Y, 200 (7.8) 150 (5.9) 075M3 to D15M3X,
C31Y, C40Y 075N4 to D18N4,
U22S6X to U75S6X
h3
C80Y
h2u
For a surrounding air temperature up to 50 °C (122°F), see installation manual ( 1760643 or 1760655)
on www.schneider-electric.com for other thermal conditions.
COM
AI1+
+10 v
AI1-
3 200...690 Vac
or
• Wire the command:
Source
Control command 2-wire:
Parameter tCC = 2C SW1 Ext
Sink
Int
LI1: forward
LI2: reverse
... N.m
... lb.in
ATVpppppp
+24
LI1
LI2
See installation manual
(1760643 or 1760655) on
www.schneider-electric.com
or on the drive nameplate for
tightening torque.
DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK
• To avoid overheating or loss of contact, connections must be carried out according to the cable sizes and tightening torques visible on the
label stuck on the ATVpp.
• The use of multi-wire cable without a lug is forbidden for the mains connection.
• Carry-out a pull out test to check that terminal screws are correctly tighten.
Failure to follow these instructions will result in death or serious injury.
Français Standard
ATV61HU15N4
3 seconds Deutsch Advanced
1.5kW/2HP 380/480Vac
Config. n°1 Español Expert
Italiano
<< >> Quick << >> Quick
DANGER WARNING
HAZARD OF ELECTRIC SHOCK OR ARC FLASH DAMAGED DRIVE EQUIPMENT
• During auto-tuning, the motor operates at rated • Asynchronous motor: It is essential that the following parameters
current. UnS, FrS, nCr, nSP and nPr are correctly configured before starting
• Do not service the motor during auto-tuning. autotuning.
Failure to follow these instructions will result in • Synchronous motor: It is essential that the following parameters
death or serious injury. nCrS, nSPS, PPnS, PHS, LdS and LqS are correctly configured
before starting autotuning.
• When one or more of these parameters have been changed after
auto-tuning has been performed, YES will return to dOnE and the
procedure will have to be repeated.
LI1
+ 38.0 Hz
Code Quick
AdU[Advanced]
drC-
EPr[Expert]
bAS[Basic]
(factorysetting)
[1.4 MOTOR CONTROL]
Std[Standard]
[1.5 INPUTS / OUTPUTS CFG] I-O-
[1.6 COMMAND] CtL-
[1.7 APPLICATION FUNCT.] FUn-
[1.8 FAULT MANAGEMENT] FLt-
[1.9 COMMUNICATION] COM-
[1.10 DIAGNOSTICS] -
[1.14 PROGRAMMABLE CARD] (1) PLC-
[6 MONITORING CONFIG.] -
A single function can be assigned to each input.
[7 DISPLAY CONFIG.] -
Several functions can be assigned to each input
Expert parameters EPr-
Several functions can be assigned to each input.
Power-up
XXX Displays the state of the drive
ENT
ESC ENT
ESC
Refer to the programming manual
(1760649) for comprehensive menu
description.
Certificate CE/ATEX e
ATV61H CE Certificate
See on www.schneider-electric.com
ATV61W CE Certificate 07ATEX0004X
ATV61E5 CE Certificate