SG30KTL-M User Manual PDF
SG30KTL-M User Manual PDF
SG30KTL-M User Manual PDF
SG30KTL-M
PV Grid-Connected Inverter
Aim
The manual contains information about the inverter, providing you guidelines to
connect the inverter into the PV power system and operate the inverter.
Related Documents
The manual cannot include complete information about the PV system. You will get
the additional information about other devices at www.sungrowpower.com or via
webpage of device manufacturer.
Target Group
The manual is targeted to technical personnel who is responsible for inverter
installation and commissioning in the PV power system and inverter owner who will
perform daily LCD operation.
I
Symbols Explanation
Important instructions contained in this manual should be followed during
installation, operation and maintenance of the inverter. And they will be highlighted
by the following symbols.
DANGER indicates a hazard with a high level of risk which, if not avoided,
will result in death or serious injury.
CAUTION indicates a hazard with a low level of risk which, if not avoided,
could result in minor or moderate injury.
II
Symbols on the Inverter Body
This symbol indicates that you should wait at least 10 minutes
after disconnecting the inverter from the utility grid and from
the PV input before touching any inner live parts.
Hot surface! In order to reduce the risk of burns, do not touch
the hot surface when the device is running.
Look over the user manual before any operation on the
inverter!
The installation and service of the inverter unit can only be
performed by qualified personnel.
Do not disconnect DC connectors from the unit under load!
III
Contents
IV
6.2 Connecting Inverter to AC Grid ..................................................................... 29
6.2.1 AC Side Requirements .......................................................................................... 29
6.2.2 Grid Connection ..................................................................................................... 30
6.3 Connecting Inverter to PV Arrays.................................................................. 33
6.3.1 PV Inputs Configuration ...................................................................................... 34
6.3.2 PV Connection Procedures ................................................................................. 36
6.4 Grounding the Inverter ..................................................................................... 40
6.4.1 Grounding System Overview............................................................................. 40
6.4.2 Second Protective Earth Terminal .................................................................... 41
6.5 Communication Connection .......................................................................... 42
6.5.1 Communication Overview.................................................................................. 42
6.5.2 Communication System ...................................................................................... 43
6.5.3 RS485 Communication Connection................................................................ 45
7 Commissioning ...................................................................... 48
7.1 Inspection before Commissioning ............................................................... 48
7.2 Commissioning Procedure .............................................................................. 48
8 Disconnecting, Dismantling and Disposing the Inverter .... 53
8.1 Disconnecting the Inverter ............................................................................. 53
8.2 Dismantling the Inverter .................................................................................. 54
8.3 Disposing the Inverter ...................................................................................... 54
9 Troubleshooting and Maintenance ...................................... 55
9.1 Troubleshooting .................................................................................................. 55
9.1.1 Troubleshooting of LED Indicator .................................................................... 55
9.1.2 Troubleshooting of Faults in LCD Screen ...................................................... 55
9.2 Maintenance ......................................................................................................... 61
9.2.1 Routine Maintenance ........................................................................................... 61
9.2.2 Maintenance Instruction ..................................................................................... 61
9.3 Contact Sungrow Service................................................................................. 64
10 Operation of LCD Display ...................................................... 65
10.1 Description of Button Function ..................................................................... 65
10.2 Inverter Menu Structure ................................................................................... 66
V
10.3 Main Screen .......................................................................................................... 67
10.4 Adjust Contrast .................................................................................................... 68
10.5 Detailed Running Information....................................................................... 69
10.6 History Records ................................................................................................... 70
10.6.1 Running Information Records ......................................................................... 70
10.6.2 Fault Records ......................................................................................................... 70
10.7 Start and Stop Inverter ..................................................................................... 71
10.8 Input Parameter Settings Password............................................................. 71
10.9 System Parameters Setting ............................................................................. 72
10.9.1 Time Setting ........................................................................................................... 72
10.9.2 Energy Deviation Adjustment......................................................................... 72
10.9.3 Load Default .......................................................................................................... 73
10.9.4 Firmware Version.................................................................................................. 73
10.10 Running Parameters Setting .......................................................................... 74
10.10.1 Main Menu of Run-param .............................................................................. 74
10.10.2 Reactive Power Regulation ............................................................................ 75
10.10.3 Save P/Q-set ........................................................................................................ 80
10.11 Protective Parameters Setting ....................................................................... 80
10.11.1 Country Setting .................................................................................................. 80
10.11.2 Pro-param Setting ............................................................................................. 82
10.11.3 Single-stage Protection Parameter Setting ............................................. 82
10.11.4 Multi-stage Protective Parameter(when the country selection is not
“IT”) ......................................................................................................................................... 83
10.11.5 Multi-stage Protective Parameter(when the country selection is “IT”)
.................................................................................................................................................. 84
10.11.6 Protection Parameter Confirmation ........................................................... 85
10.12 Communication Parameters Setting ........................................................... 85
10.13 Advanced Parameters Setting ....................................................................... 85
10.13.1 PVS Detect Settings .......................................................................................... 86
10.13.2 Fre Derating ......................................................................................................... 86
10.13.3 P-Control ............................................................................................................... 87
10.13.4 Grid-pro ................................................................................................................. 88
VI
10.13.5 Island ...................................................................................................................... 88
11 Appendix ................................................................................ 89
11.1 Technical Data ...................................................................................................... 89
11.2 Terminals and Cables ......................................................................................... 90
11.3 Exclusion of Liability .......................................................................................... 91
11.4 About Us ................................................................................................................ 92
VII
VIII
1 Safety Instructions
IMPORTANT SAFETY INSTRUCTIONS
The SG30KTL-M has been designed and tested strictly according to the international
safety regulations. As electrical and electronic equipment, safety instructions related
to them must be complied with during installation, commissioning, operation and
maintenance. Incorrect operation or work may result in damage to:
y The life and well-being of the operator or a third party
y The inverter and other properties that belong to the operator or a third party
Therefore, the following safety instructions must be read and always kept in mind
prior to any work. All detailed work-related safety warnings and notes will be
specified at the critical points in corresponding chapter.
1
1 Safety Instructions User Manual
Before Installation
During Installation
Prior to installing the inverter onto the wall, it is crucial to make certain that the
inverter is not electrically connected.
Prior to installing the inverter onto the wall, it is crucial to make certain that
the inverter is not electrically connected.
2
User Manual 1 Safety Instructions
3
1 Safety Instructions User Manual
y Any fault that may impair the inverter safety functions must be repaired
immediately before the inverter is restarted.
y Inverter contains no owner serviceable parts inside. Please contact local
authorized personnel if any service work is required.
Others
4
User Manual 1 Safety Instructions
All safety instructions, warning labels and nameplate on the inverter body:
y Must be clearly visible;
y Must not be removed, covered and pasted.
5
2 Product Introduction
2.1 Intended Usage
SG30KTL-M (It will be referred to as inverter hereinafter unless otherwise specified)
which is a 3-phase string inverter without transformer, is a crucial unit between the
PV strings and utility grid in the PV power system.
Inverter is dedicated to converting direct current power generated by the PV
modules into alternating current, which conforms to parameters of local utility grid,
and feeds it into the utility grid. The intended usage of the inverter is illustrated in
Fig. 2-1.
6
User Manual 2 Product Introduction
If the PV system exceeds the capacity of one inverter, it is possible to connect several
inverters into the PV system, with each one connected to an appropriate section of
PV inputs and on the AC side they connected in parallel to the grid.
Any other or additional usage is not permitted except the intended usage.
Inverter may only accept PV modules with Protection Class II as its input.
Inverter may only be connected to utility grid via distribution board. Local
loads (home appliance, lights, motor loads, etc.) cannot be connected
between inverter and AC circuit breaker on the distribution board.
Additionally, the unit is intended for fixed installation. Located on a part
that is not removable without impairing the operation of the unit.
7
2 Product Introduction User Manual
*Image shown here is for reference only. Actual product you receive may differ.
Item Name Description
LCD display Inverter operation data viewing and parameters
1
panel configuration can be performed via the LCD display panel.
Connection They are DC input terminals, AC output terminal and RS485
2
terminals communication terminal.
The handles are designed for holding the unit when
3 Handles
transporting, installing or servicing.
Second PE
4 Second protective earth terminals as specified in EN 50178.
Terminals
5 Air outlet Exit of hot air during the inverter operation.
6 Mounting ear It is used for hanging inverter onto the backplate.
7 Fans There are four fans to perform controlled forced-air cooling.
During normal operation it is in “ON” state. It can shut down
8 DC switch
the inverter immediately in “OFF” position.
9 Air inlet Entrance of cool air.
8
User Manual 2 Product Introduction
9
2 Product Introduction User Manual
2.2.4 DC Switch
DC switch is designed for safely disconnecting the DC input current if required.
The inverter works automatically when input and output meet the requirements.
Rotating DC switch to the “OFF” position will immediately cut off the flow of DC
current.
Rotate the DC switch to the “ON” position, before restarting the inverter.
10
User Manual 2 Product Introduction
The Version 2 inverter is equipped with Fuses for both positive and negative DC
inputs, and can detects positive fuse current.
11
2 Product Introduction User Manual
Standard RS485 interface for connecting other monitoring devices into the PV
system is included.
y Protection functions
− Short circuit protection
− Insulation resistance to ground surveillance
− Inverter output voltage surveillance
− Inverter output frequency surveillance
− Residual current protection
− DC component of AC output current surveillance
− Anti-islanding phenomena protection
− Ambient temperature surveillance
− DC over-voltage protection
− Over current protection
− Power module over-temperature protection
2.3.3 Derating
Derating the output power is a way to protect the inverter from overload and
potential faults. Inverter’s derating function can be activated in the following
scenarios:
y Grid voltage too low
y Temperature too high (Inner temperature and power modules temperature)
y Power limit setting on the inverter LCD display or remote dispatch
y Grid frequency too high (when the Country selection is “DE” or “IT”)
Over-temperature Derating
Power modules over-temperature may result from high ambient temperature, poor
ventilation or fault of fans. Over-temperature derating may protect the inverter as
well as the power modules against damage.
y When the modules temperature exceeds an upper limit, the inverter start to
gradually derating until the temperature decreases to normal range.
12
User Manual 2 Product Introduction
y When the inner temperature exceeds an upper limit, the inverter start to
gradually derating until the temperature decreases to normal range.
13
3 Installation Flow
Fig. 3-1 shows the installation flow of inverter. Please follow these procedures when
installing the inverter.
14
User Manual 3 Installation Flow
15
4 Unpacking and Storage
4.1 Unpacking and Inspection
The unit is thoroughly tested and strictly inspected before delivery. Damage may
still occur during shipping.
y Check the packing for any visible damage upon receiving.
y Check the inner contents for damage after unpacking.
y Check the completeness of delivery contents according to the inner packing list.
If there is visible damage to the packaging or the inner contents, or if there is
something missing, contact the unit dealer.
Do not dispose of the original packaging. It will be the best choice to store the
inverter by re-using the original packaging. m
0m
76
1020mm
Fig. 4-1 Paper Packaging of Inverter
16
User Manual 4 Unpacking and Storage
*Image shown here is for reference only. Actual product you receive may differ.
Item Description
1 SUNGROW logo and product type
2 Technical data of inverter
3 Marks of certification institutions of inverter
4 Company name, website and origin
17
4 Unpacking and Storage User Manual
*Images shown here is for reference only! Actual product you receive may differ.
Item Name Description
A Inverter unit ---
B Backplate It is used for mounting inverter onto the wall.
C Inverter cap It is for inverter’s better weather-proof function.
Documents include quality certificate, packing list, product
D Documents
test report, CD and quick user manual.
Expansion Six units. It is used for fastening backplate onto concrete
E
bolts wall.
F Fastener set Six units. It is used for fastening backplate onto metal frame.
G Fix screws 2 M4×16 screws for fix the inverter to the backplate.
DC Eight pairs. PV input cables must be equipped with the
H
connectors connector.
Waterproof Four pairs. Seal the unused DC terminals with the
I
plugs waterproof plugs.
Jumper Configure PV configuration in parallel mode via jumper
J
cables cables.
18
User Manual 4 Unpacking and Storage
19
5 Installing Inverter onto Wall
5.1 Selecting Installation Location
Selecting an optimal installation location for the inverter is decisive for its operating
safety as well as its expected efficiency and service life.
y Take the load capacity of the wall into account. The wall (such as concrete wall
and metal structure) should be strong enough to hold the weight of the inverter
over a long period of time.
y Install the unit where is accessible to install, electrical connect or service.
y Do not install the unit on the wall of flammable
materials.
20
User Manual 5 Installing Inverter onto Wall
y Never install the inverter horizontally, nor with a forward tilt, nor with a backward
tilt nor even with upside down.
21
5 Installing Inverter onto Wall User Manual
y Avoid exposing inverter to direct sunlight or rain or snow to extend its service life
despite the IP65 protection degree. Exposure to the sun may cause additional
internal heating which will cause power reducing. Shaded site of the building is
preferred.
y Take enough space for convection into consideration during installing multiple
inverters. It is suggested that position the multiple inverters in a staggered way if
necessary.
22
User Manual 5 Installing Inverter onto Wall
23
5 Installing Inverter onto Wall User Manual
There are two sets of stainless fasteners supplied for attaching the backplate to
concrete wall and metal frame.
Fig. 5-2 Dimensions of Expansion Bolt Set for Concrete Wall (unit: mm)
Step 5 Attach the backplate to the wall firmly with the supplied expansion bolt set.
The torque for fastening the nut is 35 Nm.
24
User Manual 5 Installing Inverter onto Wall
Step 6 Assemble the cap onto the inverter for better weatherproof function.
Step 7 Lift up inverter above the backplate and then slide down to make sure that
the recesses on the back of the inverter fit perfectly together with the
backplate.
Step 8 After fit the inverter to the backplate, fasten the inverter to the backplate
with two M4×16 screws.
25
5 Installing Inverter onto Wall User Manual
Step 5 Fasten the backplate against the metal frame with bolts and nuts. The
dimensions of fasteners used in the following diagram are recommended.
The torque for fastening the nut is 35 Nm.
Install backplate E F
Item Description Remark
C A Hexagonal socket nut M10
B B Spring washer -
A D
C Washer -
D Hexagonal bolt M10*45
E Metallic wall -
F Backplate -
Step 6 Assemble the cap onto the inverter for better weatherproof function.
Step 7 Lift up the inverter above the backplate and then slide down to make sure
that the recesses on the back of the inverter fit perfectly together with the
backplate.
Step 8 After fit the inverter to the backplate, fasten the inverter to the backplate
with two M4×16 screws.
26
User Manual 5 Installing Inverter onto Wall
27
6 Electrical Connection
Once the inverter is firmly attached to the appropriate location, it can be connected
to the PV power system.
Installation shall comply with local regulations and technical rules. Installation shall
comply with the relevant instructions of AS 4777.1. All electrical connection should
follow the National Wiring Rules of Standard AS/NZS 3000.
Improper operation during the wiring process can cause fatal injury to the
operator or unrecoverable damage to the inverter.
Only qualified personnel can perform the wiring work.
Prior to any electrical connection, keep in mind that inverter has dual power
supplies. It is mandatory for technical personnel to wear personal protective
equipment: helmet, footwear and gloves during the electrical work.
28
User Manual 6 Electrical Connection
*Image shown here is for reference only. Actual product you receive may differ.
No. Description No. Description
1 DC switch 6 AC connection terminal block
Plinth of DC SPDs (Surge Protection
2 7 Second PE terminal
Devices)
3 Configuration circuit board 8 PV input terminals
4 Cooling Fan 9 Communication cable glands
5 AC connection circuit board 10 AC cable gland
Only after receiving prior approval from the local grid company as
required, should you connect the inverter to the grid.
Prior to connecting to the utility grid, verify whether the grid voltage and frequency
are within the range of inverter output parameters, referred to “Appendix”.
Otherwise consult local grid company for solution.
y It is not allowed for several inverters to use the same circuit breaker.
y It is not allowed to connect loads between inverter and circuit breaker.
29
6 Electrical Connection User Manual
Scenario 1:
Several inverters are operated
in parallel connection to the
three-phase Low Voltage grid.
Requirements:
Max. grid-connected power is 1.6MVA. Please contact Sungrow for technical
evaluation if the grid-connected power exceeds 1.6MVA.
Scenario 2:
Several inverters are operated in parallel connection to low-voltage side of MV
transformer. The high-voltage side of MV transformer is connected to the Middle
Voltage Grid.
Requirements:
y Max. grid-connected power is 1.6MVA. Please contact Sungrow for technical
evaluation if the grid-connected power exceeds 1.6MVA.
y The rate voltage on the low-voltage side of transformer must meet the inverter
output electrical specification. A neutral point is necessary and must lead
outwards as neutral conductor.
30
User Manual 6 Electrical Connection
AC Cable Requirements
Consider the following facts when select AC cables specifications and types:
y The grid impedance of the AC cable must correspond to the specification to
avoid unintended disconnection from the grid or derating of the output power.
y Voltage drop and other consideration may use the larger size cables. Avoid
power loss in cables of more than 1% of nominal inverter rating.
y Withstand ambient temperature;
y Layout type (inside wall, underground, free air etc.);
y UV resistance and so on.
Danger to human life due to high voltage existing inside the inverter!
Make sure that all the DC and AC cables to the inverter are not live before
you start the electrical work.
Do not turn on the AC side circuit breaker until all inverter electrical
connections have completed.
Connect the inverter to AC Grid as the following procedures:
31
6 Electrical Connection User Manual
For flexible cables (stranded wires), use cold pressing terminal lugs
(plastic sleeves).
32
User Manual 6 Electrical Connection
y Observe the AC terminal layout. Device will not work normally if the phase
cable is connected to the PE terminal.
y Do not squeeze or press the cable insulation layer. Improper connection
may affect the normal operation of the inverter.
*Images shown here is for reference only! Actual product you receive may differ.
Make sure that the maximum input-ground capacity of the inverter is less
than (0.12uf/kW) * 30kW, otherwise the inverter will not function properly.
Before connecting the PV arrays to the inverter, make sure that the
impedance between the positive terminal of the PV string and Earth and the
impedances between the negative terminal of the PV string and Earth are
33
6 Electrical Connection User Manual
34
User Manual 6 Electrical Connection
Supposed that the lowest temperature is -25°C, the open-circuit voltage of PV cells is
23×37.6V×[1+β×(min. ambient temperature- STC temperature)] =
23×37.6V×[1+(-0.32%/°C) ×(-25°C-25°C)]=990V<1000V (meet the operation
requirement).
Therefore, PV string should be designed to meet the open-circuit voltage
requirement even under the lowest ambient temperature condition.
As shown in the following diagram, the inverter may choose parallel mode due to
no difference between the two PV inputs.
35
6 Electrical Connection User Manual
36
User Manual 6 Electrical Connection
Sungrow provides corresponding plug connectors in the scope of delivery for quick
connection of PV inputs. Pairs of MC4 DC connectors are supplied in the scope of
delivery. (Plug-in Connection Version)
DC Cable Requirements
Tab. 6-1 DC Cable Requirements
Cross-section Outer cable Max. Withstand Max. input current
Area Range diameters Voltage for each PV string
4...6mm2
6…9mm 1000V 12A
12AWG…10AWG
The input current of each input channel should be less than 12A, otherwise
the fuse may blow out.
DC Cable Connection
Make sure that all the DC and AC cables to the inverter are not live before
you start the electrical work.
37
6 Electrical Connection User Manual
The inverter will not function properly if the DC polarities are reversed.
Step 7 Disconnect the DC switch.
38
User Manual 6 Electrical Connection
880.0
+
39
6 Electrical Connection User Manual
40
User Manual 6 Electrical Connection
Where there are multiple inverters in the PV power system, connect “PE” cables of all
inverters and mounting frame of PV arrays to the same copper bus bar. In this way, it
will establish equipotential connection.
Second PE Terminals
There is a second PE terminal on one side of the inverter. Users may choose to
connect PE connection.
41
6 Electrical Connection User Manual
Second PE Connection
42
User Manual 6 Electrical Connection
43
6 Electrical Connection User Manual
Communication Connection
(RS 485 A/B bus or RJ 45) Terminating
Inverter
Resistor
RS 485 A/B bus RJ 45
Only out. Only out.
No
Single one
44
User Manual 6 Electrical Connection
Communication Connection
(RS 485 A/B bus or RJ 45) Terminating
Inverter
Resistor
RS 485 A/B bus RJ 45
Only out Only out
Yes
Inverter 1
Inverter
2…n-1
Inverter n
Step 3 According to the position of the inverter (refer to the prior section), repeat
step 1…2 to connect the other RS485 cables.
Step 4 Pull cables outwards to confirm whether they are fastened firmly.
Step 5 According to the position of the inverter (refer to the prior section) switch ON
45
6 Electrical Connection User Manual
SolarInfo logger and RS485-232 converter are optional parts and can be
ordered from Sungrow.
RJ45 Connection
Step 1 Lead Network cable through communication cable gland to the
configuration circuit board.
Step 2 Use the Ethernet crimper to crimp the cables and connect cables to RJ45
plug according to TIA/EIA 568B.
Step 3 Connect the RJ45 plug into the RS485 in/RS485 out terminal on the
configuration circuit board.
46
User Manual 6 Electrical Connection
Step 4 According to the position of the inverter (refer to the prior section), repeat
step1…3 to connect the other Network cables to the RS485 out/RS485 in
terminal on the configuration circuit board.
Step 5 Pull cables outwards to confirm whether they are fastened firmly.
Step 6 Tighten the tread-lock sealing lock. Block off the vacant terminals to protect
the inverter’s internal from dust and moisture.
Step 7 According to the position of the inverter (refer to the prior section) switch ON
or OFF the terminating resistor.
Step 8 If there is no other connection procedure, recover and fix the front cover of
the connection cabinet.
Step 9 As for the wires which connect to the logging devices, use the Ethernet wire
stripper to strip the insulation layer and connect the RS485 A and B cables (3
and 6) to data logging device or RS485-232 converter. Communication
terminal definition is referred to the device manual.
Step 10 Verify the communication connection and configure the
communication parameters.
SolarInfo logger and RS485-232 converter are optional parts and can be
ordered from Sungrow.
47
7 Commissioning
Commissioning is a critical part for a well-installed PV system, which can protect
against fires, injury and electrical shock.
48
User Manual 7 Commissioning
Refer to “10.11 Protective Parameters Setting” for country code explanation. If the
inverter is installed where the country code is not included, please choose item
“Other” and manually set the protective parameters.
If the country code is not set correctly during commissioning, reset the
protective parameters as dictated in “10.11 Protective Parameters Setting”.
There may be faults if otherwise.
Step 5 If the country code set as TH, a Grid codes
page special for Thailand will appear. Press j
to select grid code. Confirm the selection by
Pressing ENTER.
If the country code set as Other, a Grid Fre and LVRT Param page as shown below will
appear. Press j to select. Confirm the selection by Pressing ENTER.
49
7 Commissioning User Manual
If the Country selected does not have the “Grid codes” directives, this
configuration will not affect the following procedures.
However, you may select the MV to enable/disable the LVRT function
regardless of the country selected.
Step 6 After completing the operation confirmed
that the interface above, if the country code
set as IT, AT or Other. The Pro-Stage interface
will appear. Press j to select. Press ENTER to
confirm the selection.
50
User Manual 7 Commissioning
51
7 Commissioning User Manual
If inverter’s commissioning fails, the “FAULT” indicator will be lit and “fault” will occur
on the display. Press j to view “current fault” information. Remove the existing fault
and then repeat starting up inverter as the above procedures.
52
8 Disconnecting, Dismantling and
Disposing the Inverter
8.1 Disconnecting the Inverter
For maintenance work or any service work, inverter must be switched off. In normal
operation, switching off is not necessary.
In order to disconnect the inverter from the AC and DC power sources, you should
proceed as follows. Otherwise you will be exposed to lethal voltages or the inverter
will be damaged.
Step 1 Disconnect the external AC circuit breaker and prevent it from reconnecting.
Step 2 Rotate DC switch to the “OFF” position and then turn off the upstream DC
circuit break or pull off the MC4 terminal.
Please strictly follow the above sequence. Inverter will not work normally if
otherwise.
Step 3 Wait about ten minutes until the capacitors inside the inverter have
discharged.
Step 4 Loose the six screws on the lower connection cabinet and then remove the
lid.
53
8 Disconnecting, Dismantling and Disposing the Inverter User Manual
If the inverter will be reinstalled in the future, please refer to 4.4 Storage of
Inverter for a proper conservation.
Some parts and devices in the inverter, such as the LCD display, batteries,
capacitors, may cause environment pollution. Users must comply with the
related local regulations to avoid pollution.
54
9 Troubleshooting and
Maintenance
9.1 Troubleshooting
55
9 Troubleshooting and Maintenance User Manual
Fault
Description Troubleshooting
Code
1. Check the voltage of the grid.
2. If the grid voltage exceeds the permissible
The grid voltage
range of inverter protection parameters, ask
002 exceeds inverter
utility grid company for solution.
allowable upper limit.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept..
1. This is a short-term fault due to grid
Grid transient voltage condition. Wait a moment for inverter
003 exceeds the permissible recovery.
range 2. If the fault still exists, please contact
Sungrow Service Dept..
1. Check the grid voltage.
2. If the grid voltage exceeds the permissible
The grid voltage is
range of inverter protection parameters, ask
004 below inverter’s
utility grid company for solution.
allowable lower limit.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept..
1. This is a short-term fault due to grid
condition. Wait a moment for inverter
The grid voltage is too
005 recovery.
low.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. The inverter will resume if the output
The AC output current
current falls below the protection value.
006 exceeds inverter
2. If the fault still exists, please contact
protection limit.
Sungrow Service Dept..
Transient AC The inverter will self-recover after several
007
overcurrent seconds.
The grid frequency 1. Check the grid frequency.
008 exceeds inverter 2. If the grid frequency exceeds the
allowable upper limit. permissible range of inverter protection
parameters, ask utility grid company for
The grid frequency is solution.
009 below the inverter 3. If the grid frequency is within the
allowable lower limit. permissible range, contact Sungrow Service
Dept..
1. Check whether AC circuit breaker is
triggered.
2. Check whether AC cables are all firmly
connected.
010 Islanding
3. Check whether grid is not in service.
4. If all conditions are OK and this fault still
occurs in the LCD screen, contact Sungrow
Service Dept..
56
User Manual 9 Troubleshooting and Maintenance
Fault
Description Troubleshooting
Code
The DC component of 1. Wait a moment for inverter recovery.
011 AC current exceeds 2. If the fault occurs repeatedly, contact
inverter limit. Sungrow Service Dept..
1. Check the PV strings for ground fault.
A failure current is
012 2. If the fault occurs repeatedly, contact
detected.
Sungrow Service Dept..
1. Wait a moment for grid recovery.
2. If the grid parameters exceed the
permissible range, ask utility grid company for
Grid abnormal is
013 solution.
detected
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept..
The average grid voltage
1. Wait a moment for inverter recovery.
exceeds the permissible
014 2. If the fault occurs repeatedly, contact
range for over 10
Sungrow Service Dept..
minutes.
1. Check the model of the AC cables.
Grid impedance exceeds 2. Wait a moment for inverter recovery.
015
inverter’s limit 3. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
The AC output
016 2. If the fault occurs repeatedly, contact
overloads.
Sungrow Service Dept..
Unbalance between the 1. Wait a moment for inverter recovery.
017 three phase voltages is 2. If the fault occurs repeatedly, contact
detected Sungrow Service Dept..
1. Wait a moment for inverter recovery.
The transient bus
019 2. If the fault occurs repeatedly, contact
voltage is high.
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
020 The bus voltage is high. 2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
PV1 input overcurrent is
021 Check the layout and the wiring of PV1 input.
detected
PV2 input overcurrent is
022 Check the layout and the wiring of PV2 input.
detected
PV configuration mode
Check the PV input configuration mode and
023 has changed during
restart the inverter when necessary.
inverter running.
1. Inverter will recover if the deviation value
Deviation from neutral
falls below the protection limit.
024 point voltage is
2. If the fault occurs repeatedly, contact
detected.
Sungrow Service Dept..
57
9 Troubleshooting and Maintenance User Manual
Fault
Description Troubleshooting
Code
1. Inverter will recover if the deviation value
Transient unbalance of
falls below the protection limit.
025 neutral point voltage is
2. If the fault occurs repeatedly, contact
detected
Sungrow Service Dept..
1. This is a short-term fault. Wait a moment for
Bus fluctuation voltage inverter recovery.
026
is high. 2. If the fault still exists, please contact
Sungrow Service Dept..
The DC current is not
balanced between the 1. Wait a moment for inverter recovery.
027 two PV inputs for 2. If the fault occurs repeatedly, contact
parallel PV configuration Sungrow Service Dept..
mode.
The temperature of 1. Check whether AC output power exceeds
036
module is too high the nominal power.
2. Check the functionality of the fans and
whether there are some abnormal fans. Please
The ambient replace broken fan if necessary.
037
temperature is too high 3. Clean air outlet grills.
4. If the fault still exists, please contact
Sungrow.
1. Wait a moment for inverter recovery.
038 Relay fault is detected 2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
The insulation resistance
039 2. If the fault occurs repeatedly, contact
is low. (ISO-flt)
Sungrow Service Dept..
AC or DC overcurrent 1. Wait a moment for inverter recovery.
040 fault, or DC overvoltage 2. If the fault occurs repeatedly, contact
fault. Sungrow Service Dept..
1. Wait a moment for inverter recovery.
041 Sampling channel failure 2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
If the fault occurs repeatedly, contact Sungrow
042 Current imbalance.
Service Dept..
The ambient Disconnect and stop the inverter. Wait for
043 temperature falls below ambient temperature to rise above -25 ℃
-25oC and then restart inverter.
1. Wait a moment for inverter recovery.
There is a fault with
044 2. If the fault occurs repeatedly, contact
DC/AC inversion circuit
Sungrow Service Dept..
There is a fault with PV1
045 1. Wait a moment for inverter recovery.
boost circuit.
2. If the fault occurs repeatedly, contact
There is a fault with PV2
046 Sungrow Service Dept..
boost circuit.
58
User Manual 9 Troubleshooting and Maintenance
Fault
Description Troubleshooting
Code
The PV configuration 1. Disconnect the inverter.
mode set on the display 2. Re-select PV configuration mode and
047 is not in accordance re-connect PV strings. For more detailed
with the configuration in information please refer to “6.3 Connecting
the connection cabinet. Inverter to PV Arrays”.
Phase-R current
048
sampling channel fault.
1. Wait a moment for inverter recovery.
Phase-S current
049 2. If the fault occurs repeatedly, contact
sampling channel fault.
Sungrow Service Dept..
Phase-T current
050
sampling channel fault.
1. Wait a moment for inverter recovery.
Hardware Overvoltage/
051 2. If the fault occurs repeatedly, contact
Overcurrent protection
Sungrow Service Dept..
Disconnect inverter and remove the broken
070 Fans are defective.
fan.
It is necessary to replace the DC SPD. Contact
072 Fault with DC SPD
Sungrow Service Dept..
Disconnect the inverter and replace the fuses.
073 Fuse has blown out
Contact Sungrow Service Dept..
A fault has occurred in the internal
Communication fault of communication of the inverter. However, the
074
LCD inverter continues feeding into the grid.
Contact Sungrow Service Dept..
1. Wait for higher irradiation.
Solar irradiation is not
2. If this recurs at medium irradiation, check
075 sufficient for inverter
the PV system design and correct the
operation.
connection of PV inputs.
Check the PV system design and correct the
076 PV1 overload
connection of PV1 inputs.
Check the PV system design and correct the
077 PV2 overload
connection of PV2 inputs.
1. Check whether the PV1 input not connected
or loose.
PV1 power abnormal
078 2. If all PV1 input cables are firmly attached
warning
and the warning fault still exists, please
contact Sungrow Service Dept..
1. Check whether the PV2 input not connected
or loose.
PV2 power abnormal
079 2. If all PV2 input cables are firmly attached
warning
and the warning fault still exists, please
contact Sungrow Service Dept..
59
9 Troubleshooting and Maintenance User Manual
Fault
Description Troubleshooting
Code
PVS(X) reverse polarity
warning of PV1 ( X 1. Check the polarity of the PV1 inputs, if the
represents the alarm polarity is reverse, please reconnect PV strings.
532-535
code corresponding 2. If the fault still exists, please contact with
DC1-(X) ones, followed SUNGROW.
by 1,2,3,4)
PVS(X) reverse polarity
warning of PV2 ( X 1. Check the polarity of the PV2 inputs, if the
represents the alarm polarity is reverse, please reconnect PV strings.
536-539
code corresponding 2. If the fault still exists, please contact with
DC2-(X) ones, followed SUNGROW.
by 1,2,3,4)
1. Check whether the PV array is shielded. If
PVS(X) output current the PV array is clear and is not shielded,
abnormal warning of check whether the PV modules are faulty.
PV1(X represents the 2. Check the DC1 input cable for
548-551 alarm code disconnection. If so, reconnect the cable
corresponding DC1-(X) and reset the PVS function.
ones, followed by
1,2,3,4) 3. If the fault still exists, please contact with
SUNGROW.
1. Check whether the PV array is shielded. If
PVS(X) output current the PV array is clear and is not shielded,
abnormal warning of check whether the PV modules are faulty.
PV2(X represents the
2. Check the DC2 input cable for
552-555 alarm code
corresponding DC2-(X) disconnection. If so, reconnect the cable
ones, followed by and reset the PVS function.
1,2,3,4) 3. If the fault still exists, please contact with
SUNGROW.
60
User Manual 9 Troubleshooting and Maintenance
9.2 Maintenance
Fans’ Maintenance
There are four fans at the side of the inverter for active cooling during running
operation. If the fans are dirty or out of work, the inverter may not be well cooled
down and its efficiency may accordingly decrease. Therefore it is necessary to clean
the dirty fans or replace the broken fans.
y Disconnect the inverter from the grid first and then PV arrays before any
61
9 Troubleshooting and Maintenance User Manual
maintenance work.
y Lethal voltage still exists in the inverter. Please wait for at least ten
minutes and then perform maintenance work.
y Fans’ maintenance work may only be performed by qualified electricians.
Step 1 Disconnect the AC circuit breaker.
Step 2 Rotate DC switch to the “OFF” position and then turn off the upstream DC
circuit break or pull off the MC4 terminal.
Step 3 Wait for at least ten minutes.
Step 4 Disconnect all electrical connection in the reverse procedures in the “6
Electrical Connection”.
Step 5 Lift up the inverter over the backplate with the help of others and then
remove it from the wall.
Step 6 Place the inverter onto the platform.
Step 7 Loosen the screws as shown in the right
diagram.
62
User Manual 9 Troubleshooting and Maintenance
Step 11 You can clean the dirty fans with soft brush or vacuum cleaner. Or
replace the broken fans.
Step 12 Re-assemble the fans onto the inverter.
Step 13 Connect the four connectors and fasten them with cable ties.
Step 14 Assemble the plate by fastening the four screws.
Step 15 Perform the electrical and mechanical connection and then restart the
inverter.
63
9 Troubleshooting and Maintenance User Manual
64
10 Operation of LCD Display
10.1 Description of Button Function
Inverter offers two buttons for user to look up the running information and
configure parameters. The two buttons have multiple functions. Please refer to
0before any operation onto inverter.
Tab. 10-1 Button Function
Button Operation Description
Press less than Move upwards or downwards, or increase the set
two seconds value. Hereinafter, it is referred to as “Press j”.
Return to the previous menu or cancel the
Press more than
command. Hereinafter, it is referred to as “Press
two seconds
ESC”.
Press less than Move left or right, or turn pages. Hereinafter, it is
two seconds referred to as “Press h”.
Enter into the sub-screen or confirm the
Press more than
command. Hereinafter, it is referred to as “Press
two seconds
ENTER”.
The background light of the LCD screen will go out to save power if
there is no button operation for one minute. You can activate it by
pressing any button.
65
10 Operation of LCD Display User Manual
66
User Manual 10 Operation of LCD Display
No. Description
1 Power curve. x-axis: time in hours; y-axis: output power yield P in %.
2 Icons (refer to the Tab. 10-3) and the Inverter active power limits (P-W limits).
3 Current output power.
4 Energy generation during this day until now.
5 Total energy generation since initial commissioning.
6 Inverter state.
7 Date (year/month/date) and time.
67
10 Operation of LCD Display User Manual
68
User Manual 10 Operation of LCD Display
69
10 Operation of LCD Display User Manual
70
User Manual 10 Operation of LCD Display
71
10 Operation of LCD Display User Manual
72
User Manual 10 Operation of LCD Display
All history information will be unrecoverable cleared and all parameters will
return to the default value except the protection parameters and time once
the “load default” operation is performed.
73
10 Operation of LCD Display User Manual
74
User Manual 10 Operation of LCD Display
“Pf” Mode
The reactive power can be regulated by the parameter PF on the Run-param screen.
“Qt” Mode
The reactive power can be regulated by the parameter Q-Var limits (in %) on the
Run-param screen.
“Off” Mode
The PF is limited to +1.000, and the Q-Var limit is limited to 0.0%.
75
10 Operation of LCD Display User Manual
76
User Manual 10 Operation of LCD Display
77
10 Operation of LCD Display User Manual
In the Q(U) mode, the Sn value is 1.118 times of Pn value. If you need set
the Qmax that is equal to x% Sn, you can set Qmax to be 1.118 * x% Pn.
That means to set "Lower Q/Pn Ind" to be 1.118 * x%, and set "Upper
Q/Pn Cap" to be 1.118 * x%.
78
User Manual 10 Operation of LCD Display
79
10 Operation of LCD Display User Manual
80
User Manual 10 Operation of LCD Display
DK Denmark English
GR_L Greece Land English
GR_IS Greece Island English
NL Netherlands English
PT Portugal English
CHN China Chinese
SE Sweden English
RO Romania English
TH Thailand English
TK Turkey English
Other Country not included above English
If the country code set as TH, a Grid codes page as shown in
the right will appear. Press j to select grid code. Confirm
the selection by Pressing ENTER.
If the country code you set is not more than a few, a Grid
codes page as shown in the right will appear. Press j to
select. Confirm the selection by Pressing ENTER.
81
10 Operation of LCD Display User Manual
82
User Manual 10 Operation of LCD Display
83
10 Operation of LCD Display User Manual
84
User Manual 10 Operation of LCD Display
When the Country or the Grid code or LVRT switch mode is changed,
the protective settings will be unavailable unless the inverter is
re-energized.
85
10 Operation of LCD Display User Manual
When the PV inputs are changed, the corresponding “fault” state will
be shown on the main screen. You can perform the PVS Detect Reset
function to re-detect the PV input strings number.
PVS Detect is only valid in the machine that is equipped with this
feature.
86
User Manual 10 Operation of LCD Display
If the country code set as RO, a Derating page as shown below will appear. Press j
to select. Confirm the selection by Pressing ENTER.
The following graph shows the automatic reduction in output power when the
frequency exceeds the threshold value.
10.13.3 P-Control
Main Screen(Press ENTER )→Menu screen(Press j×4)→Advanced settings(Press
ENTER)→Enter password(Press ENTER)→Advanced settings(Press ENTER, Press j×2)
→P-Control
P-Control can control the active power raise and decline rate. And when Flt slowup
is ON, you can also set the power rise rate when a fault is removed.
87
10 Operation of LCD Display User Manual
10.13.4 Grid-pro
Main Screen(Press ENTER )→Menu screen(Press j×4)→Advanced settings(Press
ENTER)→Enter password(Press ENTER)→Advanced settings(Press ENTER, Press j×3)
→Grid-pro
Grid-pro can set the over-voltage protection point in 10min and the Grid voltage
unbalance protection point.
10.13.5 Island
Main Screen(Press ENTER )→Menu screen(Press j×4)→Advanced settings(Press
ENTER)→Enter password(Press ENTER)→Advanced settings(Press ENTER, Press j×4)
→Island
Island can set the threshold value of grid frequency change rate and phase change
rate to trigger the Islanding protection fuction.
88
11 Appendix
11.1 Technical Data
Parameters SG30KTL-M
Input Side Data
Max. PV input power 30800W
Max. PV input voltage 1000V
Startup voltage 300V
Nominal input voltage 620V
MPP voltage range 280…950V
MPP voltage range for nominal power 480...800V
No. of MPPT(s) 2
Max. number of PV strings per MPPT 4
Max. PV input current(DC1/DC2) 66A(33A/33A)
Max. input current for input connector 12A
Short-circuit current of PV input
80A(40A/40A)
(DC1/DC2)
Output Side Data
Nominal AC output power 30000W
Max. AC output apparent power 33120VA
Max. AC output current 48A
Nominal AC voltage 3/N/PE, 230/400Vac
310...480Vac
AC voltage range (May vary as per corresponding country’s
grid standard.)
Nominal grid frequency 50Hz/60Hz
45...55Hz/55...65Hz
Grid frequency range (May vary as per corresponding country’s
grid standard.)
THD < 3 % (at nominal power)
DC current injection <0.5%In
Power factor >0.99 default value at nominal power
(adj. 0.8 overexcited...0.8 underexcited)
Protection
Anti-islanding protection Yes
LVRT Yes
AC short circuit protection Yes
89
Parameters SG30KTL-M
Leakage current protection Yes
DC switch Integrated
DC fuse Integrated
Overvoltage protection Type II DC SPD
System data
Max. efficiency 98.3%
Max. European efficiency 98.0%
Isolation method Transformerless
Ingress protection rating IP65
Night power consumption <1W
Operating ambient temperature range -25...+60℃ (>45℃ derating)
Allowable relative humidity range 0...100%
Cooling method Smart forced air cooling
Max. operating altitude 4000m (>3000m derating)
Display Graphic LCD
Communication RS485 (RJ45 connector)
DC connection type MC4
AC connection type Screw connection
VDE0126-1-1,EN62109-1,EN62109-2,G59/3,CEI0-21,CEI
0-16,AS4777.2,AS4777.3,VDE-AR-N-4105,BDEW ,CGC , NRS
Certification 097-2-1,UTE C15-712-1,IEC 61683, IEC 60068-2,IEC 61727,IEC
62116,IEC62109-1,IEC62109-2,EN50178,IEC62103,EN61000-6
-1,EN61000-6-2,EN61000-6-3,EN61000-6-4,AS/NZS 3100
Mechanical Data
Dimensions (W×H×D) 634×820×257mm
Mounting method Wall bracket
Weight 65kg
90
Recommended
Terminal Type Conductor size
conductor size
Twist-pair type cable 、 Twist-pair type
shielding Ethernet cable
RS485Comm.
MG25A-H2-06-ST ( The diameter of the cable outside
terminals
diameter should be in the range of 5.1 ~
6.5mm.)
10AWG…8AWG 9AWG
Second PE terminal -
6mm2 6mm2
91
y Sungrow Power Supply Co., Ltd. rejects any liability for direct or indirect damages
arising from the use of the SolarInfo software. This also applies to the provision or
non-provision of support activities.
y Using the SolarInfo software for commercial purposes is prohibited.
y Decompiling, decoding or destroying the original program, including SolarInfo
software and the embedded software, is prohibited.
11.4 About Us
Sungrow power supply is a China-leading manufacturer of various power electronics
products for renewable energy generation systems. Our products include converters,
inverters, battery chargers and other power supplies for distributable generation
system in both grid-connected and stand-alone applications. The power rating of
Sungrow products covers from hundred watt to mega-watt systems.
The vision of Sungrow is to help our customers acquire stable and clean power with
minimum cost, maximum reliability and enhanced safety.
Contact Information
Should you have any question about this product, please contact us.
Company: Sungrow Power Supply Co., Ltd.
Website: www.sungrowpower.com
Email: info@sungrow.cn, service@sungrow.cn
No.1699 Xiyou Rd., New & High Technology Industrial Development
Address:
Zone, Hefei, P. R. China.
Zip: 230088
Telephone: +86 551 6532 7834, +86 551 6532 7845
Fax: +86 551 6532 7856
92
Sungrow Power Supply Co., Ltd.
Add: No.1699 Xiyou Rd.,New & High Technology Industrial Development Zone, 230088,Hefei, P. R. China.
Post Zip: 230088
Web: www.sungrowpower.com Tel: +86 551 6532 7834/6532 7845
E-mail: info@sungrow.cn Fax: +86 551 6532 7856