Quick Start Guide: FOR BE1-11 Protection Systems
Quick Start Guide: FOR BE1-11 Protection Systems
Quick Start Guide: FOR BE1-11 Protection Systems
FOR
BE1-11
Protection Systems
Publication: 9424200772
Revision: E Feb-19
BE1-11d, IT-D, and RTD Module
WARNING: California's Proposition 65 requires special warnings for products that
may contain chemicals known to the state of California to cause cancer, birth defects, or
other reproductive harm. Please note that by posting this Proposition 65 warning, we are
notifying you that one or more of the Proposition 65 listed chemicals may be present in
products we sell to you. For more information about the specific chemicals found in this
product, please visit https://www.basler.com/Prop65.
9424200772 Rev E i
Preface
This instruction manual provides basic installation and setup information for BE1-11 Protection Systems.
To accomplish this, the following information is provided:
• BESTCOMSPlus® software installation and operation
• Power supply connections
• Settings configuration
• Programming BESTlogic™Plus programmable logic
For complete information on a specific BE1-11 Protection System, refer to one of the following instruction
manuals:
• BE1-11d, DC Power Protection System, Publication 9424200761
• BE1-11f, Feeder Protection System, Publication 9424200990
• BE1-11g, Generator Protection System, Publication 9424200994
• BE1-11i, Intertie Protection System, Publication 9424200993
• BE1-11m, Motor Protection System, Publication 9424200996
• BE1-11t, Transformer Protection System, Publication 9424200995
Warning!
Caution
Caution boxes call attention to operating conditions that may lead to
equipment or property damage.
Note
Note boxes emphasize important information pertaining to installation
or operation.
BE1-11 Preface
ii 9424200772 Rev E
Warning!
READ THIS MANUAL. Read this manual before installing, operating, or maintaining the BE1-11. Note
all warnings, cautions, and notes in this manual as well as on the product. Keep this manual with the
product for reference. Only qualified personnel should install, operate, or service this system. Failure to
follow warning and cautionary labels may result in personal injury or property damage. Exercise
caution at all times.
Basler Electric does not assume any responsibility to compliance or noncompliance with national code, local code,
or any other applicable code. This manual serves as reference material that must be well understood prior to
installation, operation, or maintenance.
For terms of service relating to this product and software, see the Commercial Terms of Products and Services
document available at www.basler.com/terms.
This publication contains confidential information of Basler Electric Company, an Illinois corporation. It is loaned for
confidential use, subject to return on request, and with the mutual understanding that it will not be used in any
manner detrimental to the interests of Basler Electric Company and used strictly for the purpose intended.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide
data for every possible contingency regarding installation or operation. The availability and design of all features
and options are subject to modification without notice. Over time, improvements and revisions may be made to this
publication. Before performing any of the following procedures, contact Basler Electric for the latest revision of this
manual.
The English-language version of this manual serves as the only approved manual version.
Preface BE1-11
9424200772 Rev E iii
Contents
Quick Start Guide ........................................................................................................................................ 1
Maintenance .............................................................................................................................................. 1
Storage ...................................................................................................................................................... 1
Install BESTCOMSPlus® Software ............................................................................................................ 1
Power Up and Activate the BE1-11 Plug-In .............................................................................................. 2
USB Connection .................................................................................................................................... 2
Apply Operating Power .......................................................................................................................... 2
Start BESTCOMSPlus® and Activate BE1-11 Plugin ............................................................................ 4
Programming the BE1-11 .......................................................................................................................... 6
Introduction to BESTCOMSPlus® .......................................................................................................... 6
Summary Screens ................................................................................................................................. 7
Programming Example .......................................................................................................................... 8
Revision History ........................................................................................................................................ 15
BE1-11 Contents
iv 9424200772 Rev E
Contents BE1-11
9424200772 Rev E 1
Note
Do not connect a USB cable between the PC and the BE1-11 until
BESTCOMSPlus is installed. Connecting a USB cable before setup is
complete may result in errors.
Maintenance
Preventive maintenance consists of periodic replacement of the backup battery and periodically checking
that the connections between the BE1-11 and the system are clean and tight. The front cover should be
removed only when replacing the backup battery for the real-time clock. Ensure that the BE1-11 is
powered off and taken out of service before removing the front cover. BE1-11 units are manufactured
using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair
procedures be attempted by anyone other than Basler Electric personnel.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.
USB Connection
The USB driver was copied to your PC during BESTCOMSPlus installation and is
installed automatically after powering the BE1-11. USB driver installation progress is
shown in the Windows Taskbar area. Windows will notify you when installation is
complete.
Connect a USB cable between the PC and your BE1-11. A typical USB cable with a
B-type connector is shown to the right.
NOTE
In some instances, the Found New Hardware Wizard will prompt you for the
USB driver. If this happens, direct the wizard to the following folder:
C:\Program Files\Basler Electric\USB Device Drivers\
If the USB driver does not install properly, refer to the Troubleshooting chapter.
B1 B2 B3 B4 B5 B6 B7 B8
GND
IRIG COM2 RS-485 PWR D2 D4 D6 D8
A B C IA1 I B1 IC1 IG1
F2 F4 F6 F8
E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 E12 IA2 I B2 IC2 IG2
P0061-43
Figure 2. PWR Rear Terminals (J Type Case with Standard I/O Option)
Basler Electric
Highland, Illinois USA (618) 654-2341
P0069-28
Figure 3. PWR Rear Terminals (H or P Type Case) (BE1-11f, BE1-11i, and BE1-11g only)
Introduction to BESTCOMSPlus®
BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user
interface (GUI) for use with Basler Electric communicating products. The name BESTCOMSPlus is an
acronym that stands for Basler Electric Software Tool for Communications, Operations, Maintenance, and
Settings.
BESTCOMSPlus provides the user with a point-and-click means to set and monitor the BE1-11. The
capabilities of BESTCOMSPlus make the configuration of one or several BE1-11 Protection Systems fast
and efficient. A primary advantage of BESTCOMSPlus is that a settings scheme can be created, saved
as a file, and then uploaded to the BE1-11 at the user’s convenience.
The BE1-11 plugin opens inside the BESTCOMSPlus main shell. The same default logic scheme that is
shipped with the BE1-11 is brought into BESTCOMSPlus by downloading settings and logic from the
BE1-11 or by selecting application type (D, F, I, G, T, or M) on the Style Number screen. This gives the
user the option of developing a custom setting file by modifying the default logic scheme or by building a
unique scheme from scratch.
BESTlogic™Plus Programmable Logic is used to program BE1-11 logic for protection elements, inputs,
outputs, alarms, etc. This is accomplished by the drag-and-drop method. The user can drag elements,
components, inputs, and outputs onto the program grid and make connections between them to create
the desired logic scheme.
BESTCOMSPlus also allows for downloading industry-standard COMTRADE files for analysis of stored
oscillography data. Detailed analysis of the oscillography files can be accomplished using BESTwave
software.
Figure 8 illustrates the typical user interface components of the BE1-11 plugin with BESTCOMSPlus.
Summary Screens
Summary screens provide an overview of the system setup. The legend, located in the lower right-hand
corner, provides interpretation for the various indicated colors. The current state of a protection and
control function or element is indicated by the color of the adjacent indicator. If the function is enabled, the
color is green. If the function is disabled only by a setting (such as zero), the color is yellow. If the function
is disabled only by a mode, the color is blue. If the function is disabled by both a setting and mode, the
color is gray. The System Summary screen is available by clicking BE1-11 in the Settings Explorer as
shown in Figure 10. Summary screens are also available for General Settings, Alarm Configuration,
Protection, and Control.
Programming Example
Changing default logic is sometimes required to match the protection requirements of the system.
Additionally, elements must be enabled and operating settings set. This example demonstrates how to
configure typical nominal settings and program the 50-3 instantaneous overcurrent element. System
nominal quantities are set to 69.3 volts and 3.6 amps. The 50-3 element is set for a 5.62 amp pickup and
a 30 second time delay. Additionally, the element pickup output is logically wired to output 4 and a user
alarm.
Step 1: Start BESTCOMSPlus and select New Connection, BE1-11 from the Communication pull-down
menu to connect to the BE1-11. See Figure 6.
Step 2: The BE1-11 Connection screen appears. See Figure 7. Select USB Connection and click
Connect.
Step 3: Select Download Settings and Logic from Device from the Communication pull-down menu. This
copies all settings and logic from the BE1-11 to BESTCOMSPlus.
Step 4: Click on the View drop-down button and de-select Show Metering Panel and Show Setting
Information. See Figure 9. This maximizes the settings workspace.
Step 5: In the Settings Explorer, click the “+” next to BE1-11. This expands the sub menus in the tree.
Now expand System Parameters and select the Power System screen. See Figure 11.
Step 6: Under Nominal Settings, enter settings for (secondary) Phase Voltage (69.3 V) and (secondary)
Phase Current (3.6 A).
Step 7: In the Settings Explorer, expand Protection, Current and select the Instantaneous Overcurrent
(50-3) screen. See Figure 12.
Step 8: Select the Mode (3 Phase) and enter settings for Pickup (5.62 A) and Time Delay (30,000 ms).
Revision History
Table 2 provides a historical summary of the changes made to this quick start guide. Revisions are listed
in chronological order.
Table 2. Quick Start Guide Revision History
Quick Start Guide
Change
Revision and Date
A, Apr-14 • Initial release (consolidated 9424200893, 9424200894,
9424200895, 9424200896, and 9424200998)
B, Dec-15 • Updated Figure 12 to show Primary A pickup setting
C, Jul-16 • Added Windows 10 compatibility for BESTCOMSPlus
software
• Replaced Figures 4 and 6 to keep consistent with
BESTCOMSPlus version 3.14.00
• Added a note about standard I/O option in the paragraph
above Figure 2
D, May-17 • Minor text edits throughout manual
D1, Nov-18 • Added Prop 65 warning on back of cover page
E, Feb-19 • Added information for BE1-11d
• Minor edits throughout manual