Instruction Manual: FOR BE1-51/27C Time Overcurrent Relay With Voltage Control
Instruction Manual: FOR BE1-51/27C Time Overcurrent Relay With Voltage Control
Instruction Manual: FOR BE1-51/27C Time Overcurrent Relay With Voltage Control
FOR
BE1-51/27C
Time Overcurrent Relay with Voltage Control
Publication: 9137200998
Revision: E Mar-15
9137200998 Rev E i
Preface
This instruction manual provides information about the installation and operation of the BE1-51/27C Time
Overcurrent Relay with Voltage Control. To accomplish this, the following information is provided:
General information
Controls and indicators
Functional description
Installation
Tests and adjustments
Specifications
Warning!
Caution
Caution boxes call attention to operating conditions that may lead to
equipment or property damage.
Note
Note boxes emphasize important information pertaining to installation
or operation.
BE1-51/27C Preface
ii 9137200998 Rev E
Warning!
READ THIS MANUAL. Read this manual before installing, operating, or maintaining the BE1-51/27C.
Note all warnings, cautions, and notes in this manual as well as on the product. Keep this manual with
the product for reference. Only qualified personnel should install, operate, or service this system.
Failure to follow warning and cautionary labels may result in personal injury or property damage.
Exercise caution at all times.
Basler Electric does not assume any responsibility to compliance or noncompliance with national code, local code,
or any other applicable code. This manual serves as reference material that must be well understood prior to
installation, operation, or maintenance.
For terms of service relating to this product and software, see the Commercial Terms of Products and Services
document available at www.basler.com/terms.
This publication contains confidential information of Basler Electric Company, an Illinois corporation. It is loaned for
confidential use, subject to return on request, and with the mutual understanding that it will not be used in any
manner detrimental to the interests of Basler Electric Company and used strictly for the purpose intended.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide
data for every possible contingency regarding installation or operation. The availability and design of all features
and options are subject to modification without notice. Over time, improvements and revisions may be made to this
publication. Before performing any of the following procedures, contact Basler Electric for the latest revision of this
manual.
The English-language version of this manual serves as the only approved manual version.
Preface BE1-51/27C
9137200998 Rev E iii
Contents
Introduction ................................................................................................................................................. 1
Standard Features ..................................................................................................................................... 1
Time Overcurrent Functions .................................................................................................................. 1
Non-Integrating Timing .......................................................................................................................... 2
Integrating Timing .................................................................................................................................. 3
Built-In Test ............................................................................................................................................ 3
Options ...................................................................................................................................................... 3
Timing .................................................................................................................................................... 3
Sensing Input Type ................................................................................................................................ 3
Sensing Input Range ............................................................................................................................. 3
Power Supply ......................................................................................................................................... 3
Targets ................................................................................................................................................... 4
Outputs .................................................................................................................................................. 4
Instantaneous Outputs ........................................................................................................................... 4
Packaging .............................................................................................................................................. 4
Model and Style Number Description ........................................................................................................ 4
Controls and Indicators .............................................................................................................................. 7
Functional Description ............................................................................................................................. 11
Block Diagram Analysis ........................................................................................................................... 11
Power Supply ....................................................................................................................................... 12
Current Sensing ................................................................................................................................... 12
Tap Select and Tap Cal ....................................................................................................................... 12
Voltage Sensing ................................................................................................................................... 12
Multiplexor ............................................................................................................................................ 12
Analog-To-Digital Converter and Level Detector ................................................................................. 12
Time Trip Comparator and Scaler ....................................................................................................... 12
Microprocessor (Not Shown) ............................................................................................................... 13
Voltage Inhibit ...................................................................................................................................... 13
Instantaneous Overcurrent (Options 1-1 and 1-2) ............................................................................... 13
Timed and Instantaneous Outputs....................................................................................................... 13
Auxiliary Outputs .................................................................................................................................. 13
Push-to-Energize Pushbuttons ............................................................................................................ 13
Power Supply Status Output (Option 3-6) ........................................................................................... 13
Target Indicators .................................................................................................................................. 14
Installation ................................................................................................................................................. 15
Relay Operating Guidelines and Precautions ......................................................................................... 15
Mounting .................................................................................................................................................. 15
Connections ............................................................................................................................................. 28
Maintenance ............................................................................................................................................ 39
Storage .................................................................................................................................................... 39
Tests and Adjustments............................................................................................................................. 41
Required Test Equipment ........................................................................................................................ 41
Operational Test ...................................................................................................................................... 41
Preliminary Instructions ....................................................................................................................... 41
Time Overcurrent Pickup Test ............................................................................................................. 45
Timed Output Test ............................................................................................................................... 47
Instantaneous Overcurrent Pickup Test .............................................................................................. 49
Voltage Control Test ............................................................................................................................ 50
Adjustments of Controls for Relay Operation .......................................................................................... 51
TAP and TAP (NEUTRAL) Selector Setting ........................................................................................ 51
Time Overcurrent Curve Selection (Timing Type Z1, Z2, and Z3 Only) .............................................. 53
Time Delay Selection ........................................................................................................................... 53
Neutral Time Delay Selection .............................................................................................................. 54
BE1-51/27C Contents
iv 9137200998 Rev E
Contents BE1-51/27C
9137200998 Rev E 1
Introduction
BE1-51/27C Time Overcurrent Relays are microprocessor-based devices that monitor the magnitude of
line current to provide accurate time-overcurrent protection with undervoltage control (when the voltage
drops below the set point, the timing circuit is enabled). Instantaneous overcurrent element(s) and the
neutral time overcurrent element, when supplied, operate independently of the undervoltage function.
Each relay is available with one, three, or four time overcurrent elements.
BE1-51/27C relays provide backup protection for generators or transformers. Voltage control provides
discrimination between load and fault conditions by allowing the time overcurrent pickup to be set below
the maximum load (or swing) current. For sustained fault conditions, the synchronous reactance, Xd(unsat), is
typically larger than for normal load, Xd(sat). As a result, if the regulator is not in service, the three-phase
fault current will be less than the normal maximum load current. The relay pickup should be set below
rated maximum load current (e.g., 50 percent of rated) to ensure dependable backup. The BE1-51/27C
relay may also be used to provide primary phase fault protection for small generators or backup
protection for transformers.
When the BE1-51/27C is used to protect for faults on either side of a delta-wye power transformer, phase
overcurrent units should be supplied on all three phases (either three single-phase relays or one three-
phase relay). For this application, each phase time overcurrent element should be controlled by the
phase-to-ground voltage on its phase rather than by the phase-phase voltage.
Because the time overcurrent pickup of the phase element(s) does not vary with voltage level (the
element is either enabled or not depending upon voltage level), conventional time coordination
techniques apply.
A neutral (ground) overcurrent element can be applied and connected residually to a set of three current
transformers on solidly grounded applications or on impedance grounded systems that provide ground
fault current approximating the generator rated current level. The neutral element can also be connected
to a 10:1 ampere, zero-sequence window current transformer to provide protection on systems producing
a minimum of about 20 amperes primary current. Still another alternative would be connecting this device
to a current transformer in the neutral of a generator or power transformer.
Instantaneous elements can be used for transformer back-up applications when connected on the source
side of the power transformer. Because the pickup of these elements can be set above the relay current
flowing in the low-side fault, coordination can be achieved. Instantaneous overcurrent elements would not
ordinarily be used for a generator back-up function because they would not operate correctly for faults
external to the generator zone.
Under normal operating conditions, the phase time overcurrent pickup will be less than the maximum load
or non-fault current. As long as the rated voltage is applied to the relay, no operation will occur. However,
if a fuse opens on the voltage transformer and interrupts the signal, the relay will see this as a fault
condition (i.e., current level above pickup and voltage level below minimum set point) and operate
accordingly. The Basler Electric BE1-60 Voltage Balance Relay can prevent such a misoperation where
two sources of signal voltage are available. This relay compares the output of two signal sources, to
detect an anomaly in one of these sources and block the operation of those devices connected to that
signal source. Therefore, for generator applications, the Basler BE1-60 Voltage Balance relay should be
used in conjunction with the BE1-51/27C to prevent misoperations due to loss of the voltage source.
Standard Features
Time Overcurrent Functions
Time overcurrent elements pick up over a range of 0.1 to 0.8 amperes, 0.3 to 2.4 amperes, 0.5 to 4.0
amperes, 1.5 to 12.0 amperes, 0.1 to 2.4 amperes, or 0.5 to 12.0 amperes and provide an adjustable time
delay that is proportional to the overcurrent. Time delay is initiated when the sensed current exceeds the
pickup point. When the current drops below the pickup point, the timing circuit is reset immediately. At
reset, the output contacts, if operated, are restored to normal.
BE1-51/27C Introduction
2 9137200998 Rev E
Adjustment of the overcurrent pickup point is provided by controls on the relay front panel. Time delay is a
function of the characteristic curve that has been selected. Time delay is settable from 00 to 99 on the
TIME DIAL thumbwheel switch located on the front panel. Curve type is selected either as an option or, in
some models, is switch selectable.
Sixty-nine characteristic curves and three timing options are available:
Characteristic curves:
Seven inverse time
Nine I t
2
Timing option Z1 with option 2-D or 2-E (switch-selectable, 16-position) B and C curves:
Seven inverse time with extended timing range
Nine I t with extended timing range
2
Timing option Z3 with option 2-D or 2-E (switch-selectable, 16-position) integrating extended B and C
curves:
Seven integrating inverse time with extended timing range
Nine integrating I t with extended timing range
2
Characteristic curves are shown by the graphs in the Time Overcurrent Characteristic Curves chapter.
Note that each graph (i.e. function) consists of a set of representative curves. Each curve (as well as any
between-curve interpolation) is selectable by the front panel TIME DIAL using a two-digit destination from
00 to 99. Because of space limitations, each graph shows only 14 of the 100 possible selections.
Non-Integrating Timing
Timing options Z1 and Z2 and the characteristic curves available with those options use non-integrating
timing. Non-integrating timing is accomplished by timing at a gate that is not solely dependent on the
magnitude of the applied multiple of pickup current. The time-out value is calculated based on the type of
time curve characteristic selected, time dial setting, and the magnitude of the applied multiple of pickup
current. The time-out value is continuously updated during the timing cycle. When pickup is exceeded, a
timer is initiated. When the timer elapsed time exceeds the calculated time-out value, a time trip output
signal is generated.
Introduction BE1-51/27C
9137200998 Rev E 3
This type of non-integrating time delay characteristic exhibits a dynamic characteristic that is immediately
responsive to changes of the applied multiple of pickup current.
Integrating Timing
Timing option Z3 and the characteristic curves available for that option uses integrating timing. Integrating
timing is accomplished by summing time increments that are based on the magnitude of the applied
multiple of pickup current, the time curve characteristic selected, and the time dial value. These time
increments are summed until a predetermined value is exceeded, then a time trip output signal is
generated.
This type of integrating time delay characteristic simulates the operating characteristics of an
electromechanical overcurrent relay.
Built-In Test
A built-in test (BIT) switch mounted on the Logic Board provides diagnostic troubleshooting and
calibration.
Options
Timing
An extended timing option multiplies by approximately 5.7, the standard time delays. The resulting curves
are shown following the standard curves in the Time Overcurrent Characteristic Curves chapter.
When timing option Z1, Z2, or Z3 is specified, a printed circuit board mounted selector switch allows a
choice of up to sixteen different time overcurrent functions. Timing option Z1 or Z3 may be further
specified as standard or extended time, depending upon option 2 selection.
Power Supply
Five power supply options are available:
BE1-51/27C Introduction
4 9137200998 Rev E
24 Vdc
48 Vdc
125 Vdc and 100/125 Vac
48 Vdc or 125 Vdc and 100/125 Vac
250 Vdc and 240 Vac
Targets
Single-phase relays have two function targets that indicate when the time delay or instantaneous
element(s) have operated. On multiple phase relays, additional targets indicate which phase or neutral
element(s) operated.
Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.
Outputs
Optional normally opened, normally closed, or SPDT auxiliary output contacts may be selected. Contacts
actuate when the output relay is energized. Internally operated front panel mounted targets, and front
panel targets operated by the dc current in the output circuit are available for the time overcurrent and
instantaneous overcurrent functions. Optional front panel mounted PUSH-TO-ENERGIZE-OUTPUT
pushbuttons allow direct actuation of each output relay for external circuit testing.
Instantaneous Outputs
One or two instantaneous overcurrent outputs are optionally available. Each is adjustable up to 40 times
the time overcurrent pickup point. When the sensed current exceeds the instantaneous overcurrent
pickup point, an output relay is energized. An independent front panel control (INST 1 or INST 2) adjusts
the pickup point for each optional output. If more than one phase is applied to the relay, the instantaneous
pickup point will be the same for all phases. If neutral current is sensed, a front panel INST 1 (NEUTRAL)
provides adjustment of the neutral pickup point. Instantaneous overcurrent elements are not voltage
controlled.
Packaging
Each relay is mounted in a drawout cradle and enclosed in a standard utility style case with either semi-
flush or projection mounting (depending upon case style selected). An available test plug (Basler Electric
part number 10095) allows the relay to be tested in place without disturbing external control circuit wiring.
Introduction BE1-51/27C
9137200998 Rev E 5
BE1-51/27C Introduction
6 9137200998 Rev E
Introduction BE1-51/27C
9137200998 Rev E 7
A Phase Tap Calibration Control. This single-turn potentiometer adjusts the phase overcurrent pickup
threshold between the selected phase tap setting and the next lower tap setting.
B Phase Tap Selector. Selects the phase overcurrent pickup point in conjunction with the front panel
Phase Tap Calibration Control (locator A).
C Phase Instantaneous 1 Control. This four-turn potentiometer adjusts the phase instantaneous 1
element trip setting over the range of 1 to 40 times the selected Phase Tap Selector (locator B)
setting value. Your relay may be equipped with a Phase Instantaneous 2 Control which provides
similar adjustment of the phase instantaneous 2 element trip setting.
D Phase Time Dial Selector. These two knobs set the time delay between sensing of a phase
overcurrent condition and closing of the output contacts. See the Time Overcurrent Characteristic
Curves chapter for curve selection information.
E Target Indicators. LED indicators latch on when the corresponding output relay is energized by an
overcurrent condition. Target indicators are reset by the Target Reset Switch (locator H).
F Push-to-Energize Output Pushbuttons. These recessed pushbuttons are depressed to energize the
external trip circuits for testing purposes. A thin, non-conducting rod should be used to depress the
buttons. Do not use a screwdriver.
G Tap Selector Table. This front-panel reference lists the high and low setting limits for a particular tap
selection.
H Target Reset Switch. Operating this switch resets all active targets (locator E).
I Power Indicator. This LED indicator lights when control power is applied and the relay power supply is
functioning.
J Timing Indicators. A Timing LED lights when the corresponding overcurrent pickup point is reached
and exceeded.
K Neutral Time Dial Selector. These two knobs set the time delay between sensing of a neutral
overcurrent condition and closing of the output contacts. See the Time Overcurrent Characteristic
Curves chapter for curve selection information.
L Neutral Tap Calibration Control. This single-turn potentiometer adjusts the phase overcurrent pickup
threshold between the selected neutral tap setting and the next lower tap setting.
M Neutral Tap Selector. Selects the neutral overcurrent pickup point in conjunction with the front panel
Neutral Tap Calibration Control (locator L).
N Neutral Instantaneous 1 Control. This four-turn potentiometer adjusts the neutral instantaneous 1
element trip setting over the range of 1 to 40 times the selected Neutral Tap Selector (locator M)
setting value.
O Voltage Inhibit Indicators. A Voltage Inhibit indicator lights when the sensed input voltage level
exceeds the Voltage Inhibit control setting (locator P).
P Voltage Inhibit Control. This four-turn potentiometer adjusts the voltage inhibit level over the range of
40 to 120 Vac.
The time overcurrent characteristic curve selector (not shown) is located on the left-side interior. This
circuit board mounted switch selects the characteristic curve to be used.
Prior to August 2010, this switch was located behind the front panel.
The normal/test slide switch (not shown) is located on the left-side interior. This switch is only used for
factory testing and must be in the normal position (towards front of relay) for proper operation.
Prior to August 2010, this switch was located on the right-side interior.
The tap range plate (not shown) indicates the terminal connections (high or low) used to select the current
sensing input range. The sensing input ranges are listed in Table 2.
* For relays with sensing input ranges 1 or 9, connect the system wiring to the current sensing terminals
for the desired range (HIGH or LOW).
X X X X
X X X X
P
X X X X X X
X X X X X
T
X X X X X X X
X X X X
A
X X X X X X
X X X X X
D
X X X X X X X
X X X X
J
X X X X X X
Functional Description
BE1-51/27C Time Overcurrent Relays are microprocessor-based devices that provide protection for the
phase or phase and neutral time and instantaneous overcurrent functions.
Power Supply
Operating power for the relay circuitry is supplied by a wide range, electrically isolated, low-burden power
supply. Power supply operating power is not polarity sensitive. The front panel power LED and power
supply status output indicate when the power supply is operating. Power supply specifications are listed in
the Specifications chapter.
Current Sensing
All relay models (except three-phase-and-neutral units) have two sensing ranges for each phase. Each
high/low sensing range has its own set of input terminal connections.
Five ampere CTs have: LOW (0.5 A to 4.0 A) and HIGH (1.5 A to 12.0 A).
One ampere CTs have: LOW (0.1 A to 0.8 A) and HIGH (0.3 A to 2.4 A).
Three-phase-and-neutral sensing units, however, have one of four possible combinations of input sensing
ranges with one range for neutral and one range for the phases.
Five ampere CTs have: 0.5 A to 4.0 A and 1.5 A to 12.0 A.
One ampere CTs have: 0.1 A to 0.8 A and 0.3 A to 2.4 A.
Voltage Sensing
Input voltage for each phase to be monitored is applied to the voltage sensing circuits. Each voltage
sensing circuit consists of an input transformer, rectifier, and filter Analog voltages from the voltage
sensing circuits are applied to the multiplexor. Note that neutral is not monitored for voltage.
Multiplexor
The multiplexor sequentially switches a voltage representing each of the sensed input currents to the
analog-to-digital converter and level detector.
Voltage Inhibit
The output of the multiplexor is applied to the voltage inhibit circuit for comparison with a voltage limit set
by the front panel VOLTAGE INHIBIT ADJ control. If the (phase) input voltage exceeds this level, the
appropriate front panel VOLTAGE INHIBIT indicator will be illuminated and a voltage inhibit signal will
prevent the timed output relay and (if present) the auxiliary output relay from energizing. Instantaneous
overcurrent operation, if present, will not be affected.
Auxiliary Outputs
In addition to the output relays, an auxiliary relay, having the same or a different contact configuration,
may be specified. Both the output and the auxiliary relays will remain energized for the duration of the
overcurrent condition.
Push-to-Energize Pushbuttons
If either option 2-C or 2-E is present, each individual output relay can be directly energized for test
purposes by the actuation of a front panel PUSH-TO-ENERGIZE OUTPUT pushbutton. The pushbutton is
actuated by the insertion of a thin, non-conducting rod through an access hole in the front panel.
output relay is de-energized and the output contacts close. Shorting bars across the output contacts are
held open by the installed connection plug. When the relay is removed from service by removing the
connection plug, the shorting bars are closed.
Target Indicators
Target indicators are optional components selected when a relay is ordered. The electronically latched
and reset targets consist of red LED indicators located on the relay front panel. A latched target is reset
by operating the target reset switch on the front panel. If relay operating power is lost, any illuminated
(latched) targets are extinguished. When relay operating power is restored, the previously latched targets
are restored to their latched state.
A relay can be equipped with either internally operated targets or current operated targets.
Internally Operated Targets
The relay trip outputs are directly applied to drive the appropriate target indicator. Each indicator is
illuminated regardless of the current level in the trip circuit.
Current Operated Targets
A current operated target is triggered by closure of the corresponding output contact and the presence of
at least 200 milliamperes of current flowing in the trip circuit.
Note that the front panel function targets (TIMED, INST 1, etc.) may be either internally or current
operated. Phase and neutral indicators are current operated only if the instantaneous options are not
included and if current operated targets are specified.
Note
Prior to August 2007, BE1-51/27C target indicators consisted of
magnetically latched, disc indicators. These mechanically latched
target indicators have been replaced by the electronically latched LED
targets in use today.
Installation
BE1-51/27C relays are shipped in sturdy cartons to prevent damage during transit. Upon receipt of a
relay, check the model and style number against the requisition and packing list to see that they agree.
Inspect the relay for shipping damage. If there is evidence of damage, file a claim with the carrier, and
notify your sales representative or Basler Electric.
If the relay will not be installed immediately, store it in its original shipping carton in a moisture- and dust-
free environment. Before placing the relay in service, it is recommended that the test procedures of the
Tests and Adjustments chapter be performed.
Caution
When the connection plugs are removed, the relay is disconnected
from the operating circuit and will not provide system protection.
Always be sure that external operating (monitored) conditions are
stable before removing a relay for inspection, test, or service.
Note
Be sure that the BE1-51/27C is hard-wired to earth ground with no
smaller than 12 AWG copper wire attached to the ground terminal on
the rear of the case. When the BE1-51/27C is configured in a system
with other devices, it is recommended to use a separate lead to the
ground bus from each device.
Mounting
Because the relay is of solid-state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen. Refer to the following figures for relay outline dimensions and panel
drilling diagrams.
BE1-51/27C Installation
16 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 17
BE1-51/27C Installation
18 9137200998 Rev E
10-32 SCREWS
.31
(7.9)
4.03
(102.4)
4.03
(102.4)
10-32 SCREWS
.31
(7.9)
Installation BE1-51/27C
9137200998 Rev E 19
BE1-51/27C Installation
20 9137200998 Rev E
8.06
(204.72)
10-32 SCREWS
.31
(7.9)
Installation BE1-51/27C
9137200998 Rev E 21
BE1-51/27C Installation
22 9137200998 Rev E
Figure 10. S1 Case Dimensions, Rear View, Double Ended, Projection Mount
Installation BE1-51/27C
9137200998 Rev E 23
10-32 SCREWS
.31
(7.9)
MOUNTING PANEL
.25
(6.4)
4.03
(102.4)
10-32 SCREWS
.31
(7.9)
Figure 11. S1 Case Dimensions, Side View, Double Ended, Projection Mount
BE1-51/27C Installation
24 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 25
Figure 13. S1 Case Dimensions, Rear View, Single Ended, Projection Mount
BE1-51/27C Installation
26 9137200998 Rev E
1.95 6.19
(49.53) (157.2)
MOUNTING PANEL
5/16-18 STUD
2 PLACES
.25
(6.4)
8.06
(204.72) .75
(19.1)
10-32 SCREWS
.31
(7.9)
Figure 14. S1 Case Dimensions, Side View, Single Ended, Projection Mount
Installation BE1-51/27C
9137200998 Rev E 27
P0066-68
BE1-51/27C Installation
28 9137200998 Rev E
Connections
Be sure to check the model and style number of a relay before connecting and energizing the relay.
Incorrect wiring may result in damage to the relay. Except where noted, connections should be made with
wire no smaller than 14 AWG.
Typical external and internal connections are shown in the following figures.
To prevent an inductive overload of the relay contacts, it is necessary to break the trip circuit externally
through the 52a contacts.
Relay circuitry is connected to the case terminals by removable connection plugs (1 plug for 10-terminal
cases and 2 plugs for 20-terminal cases). Removal of the connection plug(s) opens the normally open trip
contact circuits and shorts the normally closed trip circuits before opening the power and sensing circuits.
P0050-03
Installation BE1-51/27C
9137200998 Rev E 29
P0050-04
BE1-51/27C Installation
30 9137200998 Rev E
P0050-06
Installation BE1-51/27C
9137200998 Rev E 31
P0050-08
BE1-51/27C Installation
32 9137200998 Rev E
P0050-10
Figure 23. Typical Sensing External Connections, Sensing Input Type P, Unit-Connected
Installation BE1-51/27C
9137200998 Rev E 33
BE1-51/27C Installation
34 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 35
BE1-51/27C Installation
36 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 37
BE1-51/27C Installation
38 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 39
Maintenance
BE1-51/27C relays require no preventative maintenance other than a periodic operational check. If the
relay fails to function properly, contact Technical Sales Support at Basler Electric to coordinate repairs.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.
BE1-51/27C Installation
40 9137200998 Rev E
Installation BE1-51/27C
9137200998 Rev E 41
Operational Test
Preliminary Instructions
Perform the following steps before going on to any testing.
Step 1. Connect the relay test setup in accordance with Figures 30 through 35, depending upon the
sensing input type for your relay (see the style chart in the General Information chapter).
(a) Sensing Input Type L (Single-Phase Sensing). Refer to Figure 30.
Note
For relays having the above sensing, only the from panel LOW range
current sense terminal(s) should be connected for a complete check of
the relay.
Note
For relays having the above sensing, only the from panel LOW range
current sense terminal(s) should be connected for a complete check of
the relay.
For all three-phase relays, the test signals must connect to both the
current and voltage terminals for the same phase.
(c) Sensing Input Type T (Three-Phase with Neutral Sensing). Refer to Figure 32.
Ensure that the timed output terminals 1 and 10 are connected. Also, verify that either A,
B, or C current sense terminals are connected initially (N terminals will be connected later
in the test).
(d) Sensing Input Type A (Three-Phase Sensing). Refer to Figure 33.
Ensure that the timed output terminals 1 and 10 are connected. Also, verify that either A,
B, or C current sense terminals are connected initially (N terminals will be connected later
in the test). Ensure that the voltage sense terminals and the current sense terminals are
connected to the same phase.
(e) Sensing Input Type D (Three-Phase with Neutral Sensing). Refer to Figure 34.
Ensure that the timed output terminals 1 and 10 are connected. Also, verify that either A,
B, or C current sense terminals are connected initially (N terminals will be connected later
in the test).
(f) Sensing Input Type J (Two-Phase with Neutral Sensing). Refer to Figure 35.
Ensure that the timed output terminals 1 and 10 are connected. Also, verify that either A,
B, or C current sense terminals are connected initially (N terminals will be connected later
in the test).
Step 2. Remove the relay front cover.
Step 3. Set the front panel TIME DIAL selector and, if present, the front panel TIME DIAL (NEUTRAL)
selector to 99.
Step 4. Adjust the front panel INST 1 and INST 2 controls, if present, fully clockwise (CW).
Step 5. Adjust the front panel TAP CAL control, and if present, the front panel TAP (NEUTRAL) control
fully CW.
Step 6. Ensure that the relay front panel TARGETS, if present, are reset.
Step 7. Apply 100% of nominal voltage based on the sensing input type for your relay.
Figure 30. Test Setup for Sensing Input Type L (Single-Phase Sensing)
Figure 31. Test Setup for Sensing Input Type P (Three-Phase Sensing)
Figure 32. Test Setup for Sensing Input Type T (Three-Phase with Neutral Sensing)
Figure 33. Test Setup for Sensing Input Type A (Three-Phase, Delta Configuration)
Figure 34. Test Setup for Sensing Input Type D (Three-Phase with Neutral Sensing)
Figure 35. Test Setup for Sensing Input Type J (Two-Phase with Neutral Sensing)
Note
During this test, disregard any indication on the test setup timer.
Note
Ensure that the voltage sense terminals and current sense terminals
are connected to the same phase.
(a) Sensing Input Type L (Single-Phase Sensing). This concludes the time overcurrent test.
Proceed to the timed output test.
(b) Sensing Input Type J (Two-Phase and Neutral Sensing). Remove the power and
reconnect the input sensing to the remaining phases as shown in Figure 35, each time
repeating Steps 1 through 10. For neutral testing, continue with Step 12.
(c) Sensing Input Type A and P (Three-Phase Sensing). Remove the power and reconnect
the input sensing to each of the remaining phases as shown in Figures 33 and 35, each
time repeating Steps 1 through 10.
(d) Sensing Input Type D and U (Three-Phase with Neutral Sensing). Remove the power
and reconnect the input sensing to each of the remaining phases as shown in Figures 32
and 34, each time repeating Steps 1 through 10. For neutral testing, continue with Step
12.
Step 12. Perform the preliminary instructions.
For the neutral sensing (terminals 17 and 18), connect the relay as shown in Figures 32 and 34,
then perform the following steps (Steps 13 through 21).
Step 13. Set the front panel TAP (NEUTRAL) selector to A.
Step 14. Adjust the test set for an overcurrent threshold having one of the following values:
(a) 0.5 A for relays with Sensing Input Range 2 or 3.
(b) 1.5 A for relays with Sensing Input Range 4 or 5.
Step 15. Slowly adjust the front panel CAL (NEUTRAL) control CCW until the front panel TIMING
indicator illuminates.
RESULT: For the neutral minimum overcurrent pickup point of 0.5 A (Step 16a, above) or 1.5 A
(Step 16b, above) the front panel CAL (NEUTRAL) control should be near its maximum CCW
limit.
Step 16. Adjust the front panel CAL (NEUTRAL) control fully CW to allow measurement of the actual
overcurrent pickup point at the A setting of the front panel TAP (NEUTRAL) selector. Note that
the front panel TIMING (NEUTRAL) indicator will extinguish. Do not disturb this setting.
Step 17. Slowly increase the current toward the value of the front panel TAP (NEUTRAL) selector A
setting until the front panel TIMING (NEUTRAL) indicator illuminates. Do not disturb this
setting.
Step 18. Record the current reading and remove input current.
RESULT: The recorded value should be within 5% of the front panel TAP (NEUTRAL)
selector A setting for the neutral minimum overcurrent pickup point for the time overcurrent.
Step 19. Set the front panel TAP (NEUTRAL) selector to J.
Step 20. Slowly adjust the test set, increasing the overcurrent threshold toward the value of the front
panel TAP (NEUTRAL) selector J setting until the front panel TIMING (NEUTRAL) indicator
just illuminates. Do not disturb this setting.
Step 21. Record the current reading and remove input current.
RESULT: The recorded value should be within 5% of the front panel TAP (NEUTRAL)
selector J setting for the neutral maximum overcurrent pickup point for the time overcurrent
element.
Note
For relays having three-phase sensing (Sensing Input Type A or P)
only a single input phase needs to be connected, since this is
sufficient for a complete test of the Time Delay. For relays that include
neutral sensing (Sensing Input Type D, T, or J), this test includes
reconnecting the Test Output to the Neutral Sensing terminals for
testing the Timed Output during neutral sensing.
Note
Due to delays inherent in the test equipment, the time delay for the
following test may appear to exceed these limits.
Step 9. On the appropriate time overcurrent curve chart (in the Time Overcurrent Characteristic Curves
chapter), locate the line representing 5 times the tap value (from Step 5) where it intersects the
particular curve representing the front panel TIME DIAL setting of 20 (from Step 4). The
resulting time delay value in seconds should be within 5% of the timer reading [from Step
7(2)].
Step 10. Adjust the front panel TIME DIAL to 40, 60, and 99, each time repeating Steps 6 through 9.
Note
For relays having two-phase-and-neutral, three-phase, or three-phase-
and-neutral sensing (Sensing Input Types A, D, P, T, or J) it is not
necessary to repeat this test for the remaining phases.
For relays having two-phase-and-neutral, or three-phase-and-neutral
sensing (Sensing Input Types D, T, or J) perform Steps 11 through 20.
For relays having single-phase or three-phase sensing (Sensing Input
Types A or P) with instantaneous overcurrent option 1-1 or 1-2,
proceed to the instantaneous overcurrent test.
Step 11. Remove the power and reconnect the test output to the neutral current sensing input of the
relay as shown in Figures 32 and 34 (terminals 17 and 18).
Step 12. Set the front panel TAP (NEUTRAL) selector to B.
Step 13. Rotate the front panel CAL (NEUTRAL) control fully CW.
Step 14. Rotate the front panel TIME DIAL (NEUTRAL) to 20.
Step 15. Ensure that all relay targets have been reset.
Step 16. Adjust the test set for an overcurrent threshold of precisely 5 times the front panel TAP
(NEUTRAL) selector B setting as measured by the ammeter.
Step 17. Apply input current to the relay and initiate the test setup timer.
RESULTS: Observe that the appropriate front panel TIMING (NEUTRAL) indicator illuminates.
Step 18. When the time delay ends, the timed output relay is energized.
RESULTS: (1) The front panel TIMING (NEUTRAL) indicator extinguishes.
(2) The test setup timer stops. (Record count for use in Step 20.)
(3) If target Type A or B is present:
(a) Front panel FUNCTION-TIME target (if present) trips.
(b) Appropriate front panel ELEMENT target A, B, or C (if present) trips.
Step 19. Remove input current and (if present) reset the relay front panel targets.
Step 20. On the appropriate time overcurrent curve chart (in the Time Overcurrent Characteristic Curves
chapter), locate the line representing 5 times the tap value (from Step 5) where it intersects the
particular curve representing the front panel TIME DIAL (NEUTRAL) setting of 20 (from Step
14). The resulting time delay value in seconds should be within 5% of the timer reading [from
step 18(2)].
Note
Due to delays inherent in the test equipment, the time delay may
appear to exceed these limits. This concludes the timed output test.
Relays having instantaneous overcurrent option 1-1 or 1-2 only
proceed to the Instantaneous Overcurrent Pickup Test.
Note
For relays having three-phase sensing (Sensing Input Types A or P),
only a single input phase is connected since this is sufficient for a
complete test of the instantaneous overcurrent sensing and output.
For relays that include neutral sensing (Sensing Input Types D, T, or
J), this test includes reconnecting the test output to the neutral sensing
terminals for testing the instantaneous 1 output during neutral sensing.
Step 11. Record the current reading. Remove input current (the front panel TIMING indicator should
extinguish).
RESULT: The recorded value should be greater than 40 times the front panel TAP selector A
setting for the maximum overcurrent pickup point for the instantaneous 1 overcurrent element.
Note
For relays having neutral sensing (Sensing Input Types D, T, or J)
perform Step 12. Otherwise, proceed to Step 13.
Step 12. For the neutral sensing, connect the relay as shown in Figures 32 and 34, then repeat Steps 2
through 11, substituting the following:
(a) The front panel TAP (NEUTRAL) selector instead of the front panel TAP selector (Step 3).
(b) The front panel INST 1 (NEUTRAL) control instead of the front panel INST 1 control
(Step 4)
Note
For relays with Option 1-2 (Inst. 2 elements), perform Step 13.
Otherwise, the test ends here.
Step 13. Reconnect the test setup to the INST 2 output terminals (11 and 12) as shown in Figure 30,
then repeat Steps 4 through 11, substituting the following:
(a) Front panel INST 2 control instead of the front panel INST 1 control (Step 3).
(b) Front panel FUNCTION-INST 2 target instead of the front panel INST 1 target (Step 4).
(c) Instantaneous 2 output relay instead of the instantaneous 1 output relay (Step 2).
Step 10. Adjust the test voltage for a 110 Vac output, and then slowly increase its output voltage until the
appropriate front panel VOLTS INHIBIT or VOLTAGE INHIBIT indicator just illuminates.
RESULT: The voltage should be >120 Vac.
Note
For relays having two-phase-and-neutral sensing, three-phase
sensing, or three-phase-and-neutral sensing (sensing input types A,
D, P, T, or J) remove power and reconnect the input sensing to each
of the remaining phases (see Figures 31 through 35), each time
repeating Steps 1 through 10. Ensure that the voltage sense terminals
and the current sense terminals are connected to the same phase.
When all phases have been tested, the voltage control test is
concluded. If the instantaneous overcurrent Option 1-1 or 1-2 is
present, proceed to instantaneous overcurrent pickup.
Note
Selection of one of the specific overcurrent pickup points provided by
the front panel TAP selector (and with the front panel TAP CAL
control fully CW) will permit a pickup point within 5% of the selector
value without having to connect the relay to a test setup to verify the
setting. If present, the front panel TAP (NEUTRAL) selector and the
front panel CAL (NEUTRAL) control provide this function for the
neutral overcurrent pickup point.
However, if the desired pickup point falls between these front panel
TAP selector settings, or if the instantaneous overcurrent option 1-1 or
1-2 is present, the relay should be connected to a test setup for a
precise setting, then the following steps should be performed.
Step 1. Connect the test setup to the relay according to the sensing input type present in the relay as
follows:
(a) Sensing Input Type L: Refer to Figure 30. Because the relay front panel TIMING indicator
provides the needed pickup indication, do not connect the test setup to the output
terminals. The current sense terminals for the desired range (HIGH or LOW), however,
should be connected to the relay.
(b) Sensing Input Type J: Refer to Figure 35. Because the relay front panel TIMING indicator
provides the needed pickup indication, do not connect the test setup to the output
terminals. The front panel TAP selector is ganged and the adjustment of one input phase
automatically aligns the other, thus, only one set of current sense terminals need be
connected. For adjustment of the front panel TAP (NEUTRAL) selector, the relay is
reconnected for neutral sensing by this procedure.
(c) Sensing Input Types A or P: Refer to Figures 31 and 33. Because the relay front panel
TIMING indicator provides the needed pickup indication, do not connect the test setup to
the output terminals. The desired range terminals (HIGH or LOW), however, should be
connected to the relay. The front panel TAP selector is ganged and the adjustment of one
input phase automatically aligns the others, thus, only one set of current sense terminals
need be connected.
(d) Sensing Input Types D or T: Refer to Figures 32 and 34. Because the relay front panel
TIMING indicator provides the needed pickup indication, do not connect the test setup to
the output terminals. The front panel TAP selector is ganged and the adjustment of one
input phase automatically aligns the others, thus, only one set of current sense terminals
need be connected. For adjustment of the front panel TAP (NEUTRAL) selector, the relay
is reconnected for neutral sensing by this procedure.
Note
For three-phase relays, ensure that the test signals are connected to
both the current and voltage terminals for the same phase.
Note
For relays with two-phase-and-neutral or three-phase-and-neutral
sensing (Sensing Input Types D, T, or J), perform Steps 10 through
15. Otherwise, the time overcurrent pickup point calibration ends here
(unless instantaneous 1 or 2 overcurrent calibration is to be performed
later in these procedures).
Step 10. Reconnect the test set output to the neutral sense terminals. See Figures 32, 34, or 35.
Step 11. Adjust the current to the desired time overcurrent pickup point for the relay.
Step 12. Set the front panel TAP (NEUTRAL) selector to the closest setting above the desired pickup
point.
Step 13. Rotate the front panel CAL (NEUTRAL) control fully CW.
Step 14. Slowly adjust the front panel CAL (NEUTRAL) control CCW until the front panel TIMING
(NEUTRAL) indicator just illuminates to establish the desired time overcurrent pickup point for
neutral sensing.
Note
Pickup point calibration ends here.
Time Overcurrent Curve Selection (Timing Type Z1, Z2, and Z3 Only)
Step 1. Remove the relay cradle front cover to gain access to the logic board time overcurrent
characteristic curve selector.
Step 2. Remove the Phillips screws from both sides of the unit and remove the front panel. See the
Controls and Indicators chapter for the location of the logic board and curve selector.
Step 3. Select the desired curve. See the Time Overcurrent Characteristic Curves chapter for the
desired curve and selector position.
Step 4. Re-install the front panel and the front cover.
Note
If Timing Type Z1, Z2, or Z3 is installed, refer to time overcurrent
curve selection to obtain the desired set of time overcurrent curves
(see the Time Overcurrent Characteristic Curves chapter). Then
proceed to Step 1, following.
If Timing Type Z1, Z2, or Z3 is not installed, determine the timing type
from the model and style number for a specific relay. Then select the
appropriate timing curve (see the Time Overcurrent Characteristic
Curves chapter). Proceed to the following, Step 1.
Step 1. Referring to the appropriate time overcurrent characteristic curve, select the desired time delay
on the front panel TIME DIAL for the anticipated input overcurrent difference (multiples-of-
pickup current) from the selected time overcurrent pickup point as follows:
(Selected Pickup Point) - (Anticipated Input Overcurrent) = Overcurrent Difference from Pickup
Step 2. Set the front panel TIME DIAL as follows:
(a) On the appropriate curve, plot upward from the multiples-of-pickup-current value until the
horizontal line opposite the desired time delay (time-in-seconds) is reached. The setting
curve nearest the plot point should then be entered on the front panel TIME DIAL.
(b) Using the timing type B3, Definite Time Curve in the Time Overcurrent Characteristic
Curves chapter as an example, if the overcurrent is expected to be 4 times the pickup point
value and time delay of 4 seconds is desired, plot upward from the point 4 on the
multiples-of-pickup-current axis until the point 4 from the time-in-seconds axis is
crossed. The curve for a setting of 52 crosses the plot point and should be entered on the
front panel TIME DIAL.
(c) For a lesser overcurrent difference from the pickup point, the time delay will be greater, so
that for a multiple of 3 times the pickup current, the time delay for the previous front panel
setting of 52 will be 5.8 seconds.
Note
Because the lower limit for this pickup is determined by the front panel
TAP selector setting and the front panel TAP (CAL) control position,
ensure that these adjustments have been performed as in the
paragraph TAP and TAP (NEUTRAL) Selector Setting.
Caution
Steps 3 through 8 provide the application of overcurrent for short
periods to allow adjustment while avoiding overheating of the input
sensing transformers. To avoid damaging the relay, do not attempt to
apply a constant high level of input current for adjustment of the front
panel INST 1, INST 1 (NEUTRAL), or INST 2 controls.
Step 3. Set the front panel INST 1 control to a position approximating the desired instantaneous 1
overcurrent pickup point for the relay.
Step 4. Apply current to the relay.
Step 5. Rapidly increase the overcurrent input to the relay until the instantaneous output relay just
energizes. Note the overcurrent threshold reading on the ammeter.
Step 6. Remove input current.
Step 7. Reset the INST TARGET (if present).
Step 8. If the overcurrent threshold reading from Step 5 was too high or low, adjust the front panel INST
1 control CCW to lower (or CW to raise) the instantaneous 1 overcurrent pickup point. Repeat
Steps 4 through 8. If the overcurrent threshold reading from Step 5 was NOT too high or low,
proceed to Step 9.
Note
For relays with two-phase-and-neutral or three-phase-and-neutral
sensing (Sensing Input Types D, T, or J), perform Steps 9 through 14.
Step 9. Reconnect the output to the neutral current sense terminals. See Figures 32, 34, or 35.
Step 10. Set the front panel INST 1 (NEUTRAL) control to a position approximating the desired neutral
instantaneous 1 overcurrent pickup point for the relay.
Step 11. Apply current to the relay.
Step 12. Rapidly increase the overcurrent input to the relay until the instantaneous output relay just
energizes. Note the test set overcurrent threshold reading on the ammeter.
Step 13. Remove the input current.
Step 14. Reset the INST TARGET (if present).
Step 15. If the overcurrent threshold reading from Step 13 was too high or low, adjust the front panel
INST 1 (NEUTRAL) control CCW to lower (or CW to raise) the Neutral Instantaneous 1
Overcurrent Pickup Point. Repeat Steps 9 through 14. If NOT, proceed to the next test.
lower accuracy-class voltages. A neutral element pickup of 10 percent of the circuit rating is normally
enough to be above any non-fault unbalance for a solidly grounded system. Lower settings are
appropriate and safe for impedance-grounded systems or for ungrounded, protected-equipment
connections.
Undervoltage settings should be as high as possible without allowing operation under the worse no-fault
conditions. An 85 percent of rated voltage setting meets these requirements. If motor starting or motor
accelerating following a fault can severely depress the relay voltage, a setting of 75 percent or 80 percent
may be advisable.
Setting Example
Figure 36 illustrates generator relay elements that are to be set in this example. Plant 11 kV feeders are
supplied by a 115 kV system that is supplemented by two local 3,700 kVA generators. Line 1 is illustrated
completely; line 2 is the same as line 1 and only shows major components. Settings are provided for the
BE1-51/27C Time Overcurrent Relay with voltage control, BE1-51 Time Overcurrent Relay, and BE1-67
Phase Directional Overcurrent Relay.
Generator Backup (Breaker A)
BE1-51/27C (51/27), relay style number: T3E B6S B2C0F
Three-phase-and-neutral overcurrent
1.5 to 12 A phase (instantaneous trip is out of service)
0.5 to 4 A neutral (instantaneous is in service)
Very inverse timing (B6)
300/5 CTs
Feeder (Breaker F)
BE1-51 (51)
0.5 to 12 A
Very inverse timing (B6)
800/5 CTs
No instantaneous
Pickup set to 6 A
Time Dial set to 08
Phase Directional (Breaker L)
BE1-67 (67)
0.5 to 12 A
Definite timing (B3)
3,000/5 CTs
Pickup set to 0.5 A
Time Dial set to 02
Generator Reactance (Per Unit)
Sub transient........... 0.18
Transient ................. 0.25
Steady State ........... 1.5
(2) Relay 51 time at 7.6 multiples (from B6 curves) @ 08 time dial: 0.31 s.
(3) Set 51/27 pickup:
0.5 (3700 ) 97
= 97 A Primary = 1.6 A
11 (1.73 ) (300/5 )
(4) Set the 51/27 time to provide 0.3 s coordinating interval:
0.31 + 0.3 = 0.61 s @ 776 A
(7) For a failure of Breaker L to open, the 51 relays on transformer T2 will operate as well as the
generator relays to clear fault 2. For a failure of the T1 differential relays (87T), the T2 51 relays
should coordinate with the 67 relays so T2 and the generators will remain in service.
Figure 37. Relay 51/27 Coordination with Relay 67 for Fault 3 Example
(7) Assuming that the 67 relays will not operate for fault 3, the generators will be unnecessarily tripped
if the line relaying fails to operate or if breaker R fails to interrupt the fault. Redundant line relaying
will minimize the need for generator tripping. Use of a breaker-failure timer set to about 0.25
seconds would avoid generator tripping for a failure of breaker R to interrupt.
Specifications
BE1-51/27C Time Overcurrent Relays electrical and physical specifications are described below.
Operational Specifications
Time Overcurrent Pickup Selection Range
Continuously adjustable over the current sensing input ranges specified in the style chart.
Instantaneous Response
Figure 38 shows the typical response for the instantaneous pickup element.
BE1-51/27C Specifications
62 9137200998 Rev E
General Specifications
Voltage Sensing Inputs
Rated for 160 Vac continuous at 40 to 70 Hz (nominal frequency 50 or 60 Hz) with a maximum burden of
1 VA.
Output Circuits
Resistive Ratings
120 Vac ............ Make, break, and carry 7 Aac continuously
250 Vdc ............ Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 Adc
500 Vdc ............ Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc........ Break 0.3 A (L/R = 0.04)
Target Indicators
Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.
Power Supply
Power for the internal circuitry may be derived from a variety of ac or dc external power sources as
indicated in Table 5.
Specifications BE1-51/27C
9137200998 Rev E 63
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one-minute dielectric (high potential) tests as
follows:
All circuits to ground ........................ 2,121 Vdc
Input to output circuits ..................... 1,500 Vac or 2,121 Vdc
UL Recognized
UL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts and input power supply voltages greater than 150 volts.
GOST-R
GOST-R certified per the relevant standards of Gosstandart of Russia.
Operating Temperature
The operating temperature range is from 40C (40F) to +70C (+158F).
Storage Temperature
The storage temperature range is from 65C (85F) to +100C (+212F).
Shock
In standard tests, the relay has withstood 15 g in each of three mutually perpendicular planes without
structural damage or degradation of performance.
BE1-51/27C Specifications
64 9137200998 Rev E
Vibration
In standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes, swept over
the range of 10 to 500 Hz for six sweeps, 15 minutes each sweep without structural damage or
degradation of performance.
Weight
Single-Phase ................................... 13.0 lbs. (5.90 kg)
Two-Phase and Neutral .................. 14.0 lbs. (6.35 kg)
Three-Phase ................................... 14.0 lbs. (6.35 kg)
Three-Phase and Neutral ................ 14.4 lbs. (6.53 kg)
Case Size
S1 (Refer to the Installation chapter for case dimensions.)
Specifications BE1-51/27C
9137200998 Rev E 65
P0049-03
P0049-02
1.5
1.5
Figure 39. Timing Type B1, Short Inverse Figure 40. Timing Type B1, Short Inverse with
Extended Timing Range
P0049-04
P0049-05
Figure 41. Timing Type B2, Long Inverse Figure 42. Timing Type B2, Long Inverse
with Extended Timing Range
P0049-07
P0049-06
Figure 43. Timing Type B3, Definite Time Figure 44. Timing Type B3, Definite Time with
Extended Timing Range
P0049-08
P0049-09
Figure 45. Timing Type B4, Moderately Inverse Figure 46. Timing Type B4, Moderately Inverse
with Extended Timing Range
P0049-10
P0049-10
Figure 47. Timing Type B5, Inverse Figure 48. Timing Type B5, Inverse
with Extended Timing Range
P0049-13
P0049-12
Figure 49. Timing Type B6, Very Inverse Figure 50. Timing Type B6, Very Inverse with
Extended Timing Range
P0049-15
P0049-14
Figure 51. Timing Type B7, Extremely Inverse Figure 52. Timing Type B7, Extremely Inverse with
Extended Timing Range
P0049-17
P0049-16
2
Figure 53. Timing Type B8, I t 2
Figure 54. Timing Type B8, I t
with Extended Timing Range
P0049-19
P0049-18
2 2
Figure 55. Timing Type C1, I t with Limit #1 Figure 56. Timing Type C1, I t with Limit #1 and
Extended Timing Range
P0049-21
P0049-20
2
2
Figure 57. Timing Type C2, I t with Limit #2 Figure 58. Timing Type C2, I t with Limit #2 and
Extended Timing Range
P0049-22
P0049-23
2
2
Figure 59. Timing Type C3, I t with Limit #3 Figure 60. Timing Type C3, I t with Limit #3 and
Extended Timing Range
P0049-24
P0049-25
2
2
Figure 61. Timing Type C4, I t with Limit #4 Figure 62. Timing Type C4, I t with Limit #4 and
Extended Timing Range
P0049-27
P0049-26
2
2
Figure 63. Timing Type C5, I t with Limit #5 Figure 64. Timing Type C5, I t with Limit #5 and
Extended Timing Range
P0049-29
P0049-28
2 2
Figure 65. Timing Type C6, I t with Limit #6 Figure 66. Timing Type C6, I t with Limit #6 and
Extended Timing Range
P0049-31
P0049-30
2
Figure 67. Timing Type C7, I t with Limit #7 2
Figure 68. Timing Type C7, I t with Limit #7 and
Extended Timing Range
P0049-32
P0049-33
2 2
Figure 69. Timing Type C8, I t with Limit #8 Figure 70. Timing Type C8, I t with Limit #8 and
Extended Timing Range
P0049-34
P0049-35
Figure 71. Timing Type E2, Figure 72. Timing Type E4,
BS 142 Long Inverse BS 142 Inverse
P0049-37
P0049-36
Figure 73. Timing Type E5, Figure 74. Timing Type E6,
BS 142 Inverse BS 142 Very Inverse
P0049-39
P0049-38
P0049-41
P0049-40
Figure 77. Timing Type B1, Short Inverse with Figure 78. Timing Type B2, Long Inverse
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-43
P0049-42
Figure 79. Timing Type B2, Long Inverse with Figure 80. Timing Type B3, Definite Time
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-44
P0049-45
Figure 81. Timing Type B3, Definite Time with Figure 82. Timing Type B4, Moderately Inverse
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-46
P0049-47
Figure 83. Timing Type B4, Moderately Inverse Figure 84. Timing Type B5, Inverse with Integrated
with Integrated Algorithm Algorithm
and Extended Timing
P0049-48
P0049-49
Figure 85. Timing Type B5, Inverse with Integrated Figure 86. Timing Type B6, Very Inverse
Algorithm and Extended Timing with Integrated Algorithm
P0049-51
P0049-50
Figure 87. Timing Type B6, Very Inverse with Figure 88. Timing Type B7, Extremely Inverse with
Integrated Algorithm and Extended Timing Integrated Algorithm
P0049-53
P0049-52
2
Figure 89. Timing Type B7, Extremely Inverse with Figure 90. Timing Type B8, I t
Integrated Algorithm with Integrated Algorithm
and Extended Timing
P0049-55
P0049-54
2 2
Figure 91. Timing Type B8, I t with Integrated Figure 92. Timing Type C1, I t Limit #1
Algorithm and Extended Timing with Integrated Algorithm
P0049-56
P0049-57
2
Figure 93. Timing Type C1, I t Limit #1 2
Figure 94. Timing Type C2, I t Limit #2
with Integrated Algorithm with Integrated Algorithm
P0049-59
P0049-58
2
Figure 95. Timing Type C2, I t Limit #2 with 2
Figure 96. Timing Type C3, I t Limit #3
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-61
P0049-60
2 2
Figure 97. Timing Type C3, I t Limit #3 with Figure 98. Timing Type C4, I t Limit #4
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-62
P0049-63
2 2
Figure 99. Timing Type C4, I t Limit #4 with Figure 100. Timing Type C5, I t Limit #5
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-65
P0049-64
2 2
Figure 101. Timing Type C5, I t Limit #5 with Figure 102. Timing Type C6, I t Limit #6
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-67
P0049-66
2 2
Figure 103. Timing Type C6, I t Limit #6 with Figure 104. Timing Type C7, I t Limit #7
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-68
P0049-69
2
Figure 105. Timing Type C7, I t Limit #7 with 2
Figure 106. Timing Type C8, I t Limit #8
Integrated Algorithm and Extended Timing with Integrated Algorithm
P0049-70
2
Figure 107. Timing Type C8, I t Limit #8 with Integrated Algorithm and Extended Timing
Revision History
Table 8 provides a historical summary of the changes made to this instruction manual. Revisions are
listed in chronological order.
Table 8. Manual Revision History
Manual
Change
Revision and Date
, Sep-93 Initial release
A, Jul-03 Moved Time Curves into new Appendix A
B, Aug-07 Moved content of Section 6, Maintenance to Section 4
Updated front panel illustrations to show laser graphics
Added manual part number and revision to all footers
Updated manual to current style used
Updated power supply burden data in Section 1
Updated Target Indicator description in Section 3
C, Jul-10 Replaced cover drawing and Figures 2-1. (New front panel
switches and graphics.)
D, May-12 Updated locations of Curve Selector and Normal/Test switches
Minor text edits
Replaced Figures 4-1 through 4-5 and added Figures 4-6 through
4-12. (For consistency between manuals of this product line.)
E, Mar-15 Updated manual to latest style
Minor text edits throughout manual