Technical Data: 1. Description
Technical Data: 1. Description
Technical Data: 1. Description
3. technical data
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating “250” stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric†)
Glass-bulb fluid temperature rated to -65°F (-55°C)
Patents Pending
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The m�����������������������������������
inimum operating pressure for LPCB and
�������
CE
Approvals ONLY is 5 psi (0.35 bar).
†Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C19500 for Sprinkler VK462 Viking Technical Data may be found on
Phosphor Bronze UNS-C51000 for Sprinkler VK463 The Viking Corporation’s Web site at
Deflector Pins: Stainless Steel Alloy http://www.vikinggroupinc.com.
Bulb: Glass, nominal 3 mm diameter The Web site may include a more recent
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel edition of this Technical Data Page.
UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-C51000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
4. Installation
Refer to appropriate NFPA Installation Standards.
5. Operation
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
7. availability
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. Guarantee
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
January 27, 2012 Sprinkler 54c
Footnotes
1
The sprinkler temperature rating is stamped on the sprinkler deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 on page 54c.)
cULus Listing Requirements:
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
• For hazard occupancies up to and including Ordinary Hazard, Group II.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
N�����������������������������������������������������������������������������������������
OTE: Concealed sprinklers m��������������������������������������������������������������
ust be installed in neutral or negative pressure plenums only.
VdS Approval Requirements:
a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials.
b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-
cies, except in OH4.
NOTES: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
1. Prepare the sprinkler key.
2. Remove the plastic cover.
3. Hold the sprinkler with the wrench and fasten it.
4. Replace the plastic cover and do not remove until the cover is installed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1-3 or QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards, whenever applicable.
Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394
January 27, 2012 Sprinkler 54e
Maximum
Sprinkler Base NPT Thread Size Nominal K-Factor FM Approvals3
SIN Water Working
Part No.1 (Refer also to Design Criteria below.)
Inch mm U.S. metric2 Pressure
13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AW1, BX1
Cover Plate Assembly Temperature Ratings 4 Cover Plate Assembly Finishes5
Sprinkler Temperature Ratings W - ��������������������������
139 °F (59 °C) cover 135041, 136421 (large diameter), 1 - Polished Chrome, Brushed Chrome, Bright
A - 155 °F (68 °C) or 153941 (square cover plate) Brass, Antique Brass, Brushed Brass,
B - 175 °F (79 °C) and 200 °F (93 °C) X - ��������������������������
165 °F (74 °C) cover 135041, 136421 (large diameter), or Brushed Copper, Painted White, Painted
153941 (square cover plate) Ivory, or Painted Black
Footnotes
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
approvals.
4
The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
5
Painted finish consists of Polyester Baked Enamel. Other
�������������������������������������������������������������������������������������������������
paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.��
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Sprinkler 54f January 27, 2012