Digital Energy
F35
Multiple Feeder Protection
System
Instruction Manual
Product version: 7.3x
GE publication code: 1601-0106-AB1 (GEK-119617)
E83849
S T ER
GI
ED
RE
ISO 9001
LISTED
G
E
IN
M U LT I L
IND.CONT. EQ.
52TL
1601-0106-AB1
Copyright © 2014 GE Multilin Inc. All rights reserved.
F35 Multiple Feeder Protection System Instruction Manual for version 7.3x.
F35, FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks or
registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0106-AB1 (November 2014)
F35 Multiple Feeder Protection System
Table of contents
ABBREVIATIONS
INDEX
Chapter 1: Introduction
Introduction
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
DANGER
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION
Indicates practices not related to personal injury.
NOTICE
Ensure that all connections to the product are correct so as to avoid accidental risk of shock
DANGER and/or fire, for example such as can arise from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on
the relay nameplate. Do not apply current or voltage in excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
1 Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are
working on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
CAUTION devices are considered safe to the unaided eye. Do not view directly with optical instruments.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
NOTICE environments. Not to be used near electronic devices rated for Class B levels.
Product description
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device number Function Device number Function
27P Phase undervoltage 51N (up to 6) Neutral time overcurrent
27X Auxiliary undervoltage 51P (up to 6) Phase time overcurrent
2 50DD
50G (up to 12)
Disturbance detector
Ground instantaneous overcurrent
51_2 (2)
52
Negative-sequence time overcurrent
AC circuit breaker
50N (up to 12) Neutral instantaneous overcurrent 59N Neutral overvoltage
50P (up to 12) Phase instantaneous overcurrent 59X Auxiliary overvoltage
50_2 (2) Negative-sequence instantaneous overcurrent 79 (up to 6) Autoreclose
51G (up to 6) Ground time overcurrent 81 (up to 6) Underfrequency
52 2 3 4 5
79
Same functions as breaker 1
CLOSE TRIP
Monitoring
Transducer
FlexElementsTM inputs
2.2 Security
The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
2
2.2.0.1 EnerVista security
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security
management system is disabled by default to allow the administrator direct access to the EnerVista software after
installation. It is recommended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
Administrator
Engineer
Operator
2 Observer Supervisor
842838A2.CDR
The following types of authentication are supported by CyberSentry to access the UR device:
• Device Authentication (local UR device authenticates)
• Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or the RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attributable.
In cases where user-attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor is such
information ever transmitted without cryptographic protection.
Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security
2
A0 | | | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
AW | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and PID controller
B0 | | | | | | | | | IEEE 1588
B1 | | | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
BW | | | | | | | | | IEEE 1588 and IEC 61850 and PID controller
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | | | PRP and IEC 61850
C4 | | | | | | | | | PRP, Ethernet Global Data, and IEC 61850
CW | | | | | | | | | PRP, PID controller, and IEC 61850
D1 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | | | IEC 60870-5-103
J1 | | | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
2 6A
6B
6C
6D
6A
6B
6C
6D
6A
6B
6C
6D
6A
6B
6C
6D
6A
6B
6C
6D
2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
8 Form-C outputs
16 Contact inputs
6E 6E 6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
TRANSDUCER 5A 5A 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 5C 5C 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed)
5E 5E 5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 5F 5F 8 DCmA inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
2
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
ENHANCED DIAGNOSTICS CT/VT DSP XX | XX | No DSP module (slots M and U only)
(requires all DSP to be enhanced 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
diagnostic) 8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
CONTACT INPUTS/OUTPUTS XX XX XX No Module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 Contact inputs
6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
TRANSDUCER 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 8 DCmA inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
2
A0 | | | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
AW | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and PID controller
B0 | | | | | | | | | IEEE 1588
B1 | | | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
BW | | | | | | | | | IEEE 1588 and IEC 61850 and PID controller
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | | | PRP and IEC 61850
C4 | | | | | | | | | PRP, Ethernet Global Data, and IEC 61850
CW | | | | | | | | | PRP, PID controller, and IEC 61850
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | | | IEC 60870-5-103
J1 | | | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | Eight-port digital process bus module
CONTACT INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 Contact inputs
6E 6E | 4 Form-C outputs, 8 contact inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Table 2-7: F35 order codes for reduced-size vertical units with process bus
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT F35 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX (SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
SOFTWARE 00 | | | | | | | No Software Options
01 | | | | | | | Ethernet Global Data (EGD)
03 | | | | | | | IEC 61850
04 | | | | | | | Ethernet Global Data (EGD) and IEC 61850
A0 | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
AW | | | | | | | CyberSentry Lvl 1 and IEC 61850 and PID controller
B0 | | | | | | | IEEE 1588
B1 | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
BW | | | | | | | IEEE 1588 and IEC 61850 and PID controller
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | PRP and IEC 61850
C4 | | | | | | | PRP, Ethernet Global Data, and IEC 61850
CW | | | | | | | PRP, PID controller, and IEC 61850
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | IEC 60870-5-103
J1 | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
CT/VT MODULES | 81 | | Eight-port digital process bus module
CONTACT INPUTS/OUTPUTS XX XX XX No Module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 8 Form-C outputs
6D 16 Contact inputs
6E 4 Form-C outputs, 8 contact inputs
6F 8 Fast Form-C outputs
2 6G
6H
6K
6L
4 Form-A (voltage with optional current) outputs, 8 contact inputs
6 Form-A (voltage with optional current) outputs, 4 contact inputs
4 Form-C and 4 Fast Form-C outputs
2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
UR - ** - *
CONTACT INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
2
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multimode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
UR - ** - *
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
2 |
|
|
|
7E
7F
7G
7H
|
|
|
|
Channel 1 - G.703; Channel 2 - 820 nm, multimode
Channel 1 - G.703; Channel 2 - 1300 nm, multimode
Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
2.4 Specifications
Specifications are subject to change without notice.
PHASE/NEUTRAL/GROUND TOC
Current: Phasor or RMS
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97% to 98% of pickup
Level accuracy:
for 0.1 to 2.0 CT: ±0.5% of reading or ±0.4% of rated (whichever is greater)
for > 2.0 CT: ±1.5% of reading > 2.0 CT rating
Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/ Extremely Inverse; I2t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)
Curve multiplier: Time Dial = 0.00 to 600.00 in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE)
Curve timing accuracy at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate
Voltage restraint: Modifies pickup current for voltage in the range of 0.1 < V < 0.9 VT Nominal in a fixed linear rela-
tionship
PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy:
0.1 to 2.0 CT rating: ±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0 CT rating: ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
PHASE UNDERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Curve shapes: GE IAV Inverse;
Definite Time (0.1s base curve)
Curve multiplier: Time dial = 0.00 to 600.00 in steps of 0.01
Curve timing accuracy at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
AUXILIARY UNDERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Curve shapes: GE IAV Inverse, Definite Time
Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01
NEUTRAL OVERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 s in steps of 0.01 (definite time) or user-defined curve
2 Reset delay:
Curve timing accuracy at >1.1 x pickup:
0.00 to 600.00 s in steps of 0.01
±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time: 30 ms at 1.10 pickup at 60 Hz
AUXILIARY OVERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0 to 600.00 s in steps of 0.01
Reset delay: 0 to 600.00 s in steps of 0.01
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: 30 ms at 1.10 pickup at 60 Hz
UNDERFREQUENCY
Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Dropout level: pickup + 0.03 Hz
Level accuracy: ±0.001 Hz
Time delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.
BREAKER RESTRIKE
Principle: detection of high-frequency overcurrent condition ¼ cycle after breaker opens
Availability: one per CT/VT module (not including 8Z modules)
Pickup level: 0.1 to 2.00 pu in steps of 0.01
Reset delay: 0.000 to 65.535 s in steps of 0.001
AUTORECLOSURE
Single breaker applications, 3-pole tripping schemes
Up to four reclose attempts before lockout
FLEXCURVES™
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1
FLEX STATES
Number: up to 256 logical variables grouped under 16 Modbus addresses
Programmability: any logical variable, contact, or virtual input
FLEXELEMENTS™
Number of elements: 16
Operating signal: any analog actual value, or two values in differential mode
Operating signal mode: signed or absolute value
Operating mode: level, delta
Comparator direction: over, under
Pickup Level: –90.000 to 90.000 pu in steps of 0.001
Hysteresis: 0.1 to 50.0% in steps of 0.1
Delta dt: 20 ms to 60 days
Pickup and dropout delay: 0.000 to 65.535 s in steps of 0.001
NON-VOLATILE LATCHES
Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
Output: stored in non-volatile memory
USER-PROGRAMMABLE LEDs
Number: 48 plus trip and alarm
Programmability: from any logical variable, contact, or virtual input
Reset mode: self-reset or latched
LED TEST
2 Initiation:
Number of tests:
from any contact input or user-programmable condition
3, interruptible at any time
Duration of full test: approximately 3 minutes
Test sequence 1: all LEDs on
Test sequence 2: all LEDs off, one LED at a time on for 1 s
Test sequence 3: all LEDs on, one LED at a time off for 1 s
USER-DEFINABLE DISPLAYS
Number of displays: 16
Lines of display: 2 20 alphanumeric characters
Parameters: up to 5, any Modbus register addresses
Invoking and scrolling: keypad, or any user-programmable condition, including pushbuttons
CONTROL PUSHBUTTONS
Number of pushbuttons: 7
Operation: drive FlexLogic operands
SELECTOR SWITCH
Number of elements: 2
Upper position limit: 1 to 7 in steps of 1
Selecting mode: time-out or acknowledge
Time-out timer: 3.0 to 60.0 s in steps of 0.1
Control inputs: step-up and 3-bit
Power-up mode: restore from non-volatile memory or synchronize to a 3-bit control input or synch/restore mode
8-BIT SWITCH
Number of elements: 6
Input signals: two 8-bit integers via FlexLogic operands
Control signal: any FlexLogic operand
Response time: < 8 ms at 60 Hz, < 10 ms at 50 Hz
DIGITAL ELEMENTS
Number of elements: 48
Operating signal: any FlexLogic operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001
Dropout delay: 0.000 to 999999.999 s in steps of 0.001
Timing accuracy: ±3% or ±4 ms, whichever is greater
2.4.3 Monitoring
OSCILLOGRAPHY
Maximum records: 64
Sampling rate: 64 samples per power cycle
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; FlexLogic equation
Data: AC input channels; element state; contact input state; contact output state
Data storage: in non-volatile memory 2
EVENT RECORDER
Capacity: 1024 events
Time-tag: to 1 microsecond
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
Data storage: in non-volatile memory
DATA LOGGER
Number of channels: 1 to 16
Parameters: any available analog actual value
Sampling rate: 15 to 3600000 ms in steps of 1
Trigger: any FlexLogic operand
Mode: continuous or triggered
Storage capacity: (NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
FAULT LOCATOR
Number of independent fault locators: 1 per CT bank (to a maximum of 5)
Method: single-ended
Voltage source: wye-connected VTs, delta-connected VTs and neutral voltage, delta-connected VTs and zero-
sequence current (approximation)
Maximum accuracy if: fault resistance is zero or fault currents from all line terminals are in phase
Relay accuracy: ±1.5% (V > 10 V, I > 0.1 pu)
Worst-case accuracy:
VT%error + user data
CT%error + user data
ZLine%error + user data
RELAY ACCURACY%error + (1.5%)
2.4.4 Metering
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 CT rating: ±0.25% of reading or ±0.1% of rated (whichever is greater)
2.0 CT rating: ±1.0% of reading
RMS VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V
2 ±1.0% of reading
VOLTAGE HARMONICS
Harmonics: 2nd to 25th harmonic: per phase, displayed as a % of f1 (fundamental frequency phasor)
THD: per phase, displayed as a % of f1
Accuracy:
HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) of reading or 0.15% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) of reading or 0.20% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu: ±0.01 Hz (when voltage signal is used for frequency measurement)
I = 0.1 to 0.25 pu: ±0.05 Hz
I > 0.25 pu: ±0.02 Hz (when current signal is used for frequency measurement)
DEMAND
Measurements: Phases A, B, and C present and maximum measured currents
3-Phase Power (P, Q, and S) present and maximum measured currents
Accuracy: ±2.0%
2.4.5 Inputs
AC CURRENT
CT rated primary: 1 to 50000 A
CT rated secondary: 1 A or 5 A by connection
Relay burden: < 0.2 VA at rated secondary
Conversion range:
Standard CT: 0.02 to 46 CT rating RMS symmetrical
Sensitive Ground CT module: 0.002 to 4.6 CT rating RMS symmetrical
Current withstand: 20 ms at 250 times rated
1 sec at 100 times rated
continuous 4xInom
Short circuit rating: 150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)
AC VOLTAGE
VT rated secondary: 50.0 to 240.0 V
FREQUENCY
Nominal frequency setting: 25 to 60 Hz
Sampling frequency:
Tracking frequency range:
64 samples per power cycle
20 to 70 Hz 2
CONTACT INPUTS
Dry contacts: 1000 maximum
Wet contacts: 300 V DC maximum
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Tolerance: ±10%
Contacts per common return: 4
Recognition time: < 1 ms
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Continuous current draw: 4 mA (when energized)
DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable)
Input impedance: 379 ±10%
Conversion range: –1 to + 20 mA DC
Accuracy: ±0.2% of full scale
Type: Passive
RTD INPUTS
Types (3-wire): 100 Platinum, 100 and 120 Nickel, 10 Copper
Sensing current: 5 mA
Range: –50 to +250°C
Accuracy: ±2°C
Isolation: 36 V pk-pk
IRIG-B INPUT
Amplitude modulation: 1 to 10 V pk-pk
DC shift: TTL–Compatible
Input impedance: 50 k
Isolation: 2 kV
DIRECT INPUTS
Input points: 32
Remote devices: 16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: Yes, No
TELEPROTECTION
Input points: 16
Remote devices: 3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: No
Data rate: 64 or 128 kbps
CRC: 32-bit
HIGH RANGE
Nominal DC voltage: 125 to 250 V
Minimum DC voltage: 88 V
Maximum DC voltage: 300 V
Nominal AC voltage: 100 to 240 V at 50/60 Hz
Minimum AC voltage: 88 V at 25 to 100 Hz
Maximum AC voltage: 265 V at 25 to 100 Hz
Voltage loss hold-up: 200 ms duration at maximum load
ALL RANGES
Volt withstand: 2 Highest Nominal Voltage for 10 ms
Power consumption: typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code consumption
INTERNAL FUSE
Ratings:
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
Interrupting capacity:
AC: 100 000 A RMS symmetrical
DC: 10 000 A
2.4.7 Outputs
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6A
Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A
Operate time:
Contact material:
< 4 ms
silver alloy
2
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6 A as per IEEE C37.90
Break (DC resistive as per IEC61810-1):
Voltage Current
24 V 6A
48 V 1.6 A
125 V 0.4 A
250 V 0.2 A
Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A
DIRECT OUTPUTS
Output points: 32
DCMA OUTPUTS
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance: 12 k for –1 to 1 mA range
12 k for 0 to 1 mA range
600 for 4 to 20 mA range
Accuracy: ±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation: 1.5 kV
Driving signal: any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001
2.4.8 Communications
IEC 61850
IEC 61850: Supports IEC 61850 Edition 2.0. See the UR Series Communications Guide and its conformance
statements.
RS232
Front port: 19.2 or 115.2 kbps, Modbus RTU
RS485 2
1 rear port: up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance: 1200 m
Isolation: 2 kV, isolated together at 36 Vpk
ETHERNET (FIBER)
Parameter Fiber type
100 Mb multimode
Wavelength 1310 nm
Connector LC
Transmit power –20 dBm
Receiver sensitivity –30 dBm
Power budget 10 dB
Maximum input power –14 dBm
Typical distance 2 km
Duplex full/half
Redundancy yes
OTHER
TFTP, SFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD), IEEE C37.118
2
RS422 distance is based on transmitter power and does not take into consideration the clock source provided
by the user.
NOTE
These power budgets are calculated from the manufacturer’s worst-case transmitter power and worst case
receiver sensitivity.
NOTE
The power budgets for the 1300 nm ELED are calculated from the manufacturer's transmitter power and
receiver sensitivity at ambient temperature. At extreme temperatures these values deviate based on
component tolerance. On average, the output power decreases as the temperature is increased by a factor
1 dB / 5 °C.
Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one
installation to another, the distance covered by your system can vary.
NOTE
FIBER LOSSES
820 nm multimode: 3 dB/km
1300 nm multimode: 1 dB/km
1300 nm single mode: 0.35 dB/km
1550 nm single mode: 0.25 dB/km
Splice losses: one splice every 2 km at 0.05 dB loss per splice
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses.
Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms
2.4.10 Environmental
AMBIENT TEMPERATURES
Storage temperature: –40 to 85°C
Operating temperature: –40 to 60°C; the LCD contrast can be impaired at temperatures less than –20°C
HUMIDITY
Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days)
OTHER
Altitude: 2000 m (maximum)
Pollution degree: II
Overvoltage category: II
Ingress protection: IP20 front, IP10 back
2 Damped oscillatory
Electrostatic discharge
IEC 61000-4-18 / IEC 60255-22-1
EN 61000-4-2 / IEC 60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN 61000-4-3 / IEC 60255-22-3 Level 3
Fast transient disturbance EN 61000-4-4 / IEC 60255-22-4 Class A and B
Surge immunity EN 61000-4-5 / IEC 60255-22-5 Level 3 and 4
Conducted RF immunity EN 61000-4-6 / IEC 60255-22-6 Level 3
Power frequency immunity EN 61000-4-7 / IEC 60255-22-7 Class A and B
Voltage interruption and ripple DC IEC 60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC 60255-25 Class A
Sinusoidal vibration IEC 60255-21-1 Class 1
Shock and bump IEC 60255-21-2 Class 1
Seismic IEC 60255-21-3 Class 1
Power magnetic immunity IEC 61000-4-8 Level 5
Pulse magnetic immunity IEC 61000-4-9 Level 4
Damped magnetic immunity IEC 61000-4-10 Level 4
Voltage dip and interruption IEC 61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC 61000-4-12 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC 61000-4-16 Level 4
Voltage ripple IEC 61000-4-17 15% ripple
Ingress protection IEC 60529 IP40 front, IP10 back
Cold IEC 60068-2-1 –40°C for 16 hours
Hot IEC 60068-2-2 85°C for 16 hours
Humidity IEC 60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL 508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
Safety UL 1053 e83849 NKCR
Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over
voltage cat II
2.4.13 Approvals
APPROVALS
Compliance Applicable council According to
directive
CE Low voltage directive EN 60255-5
EMC directive EN 60255-26 / EN 50263
EN 61000-6-5 2
C-UL-US --- UL 508
UL 1053
C22.2 No. 14
2.4.14 Maintenance
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required. When dust has accumulated on the faceplate display, wipe with a dry cloth.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
NOTICE state once per year, for one hour continuously.
Chapter 3: Installation
Installation
This chapter outlines installation of hardware and software. You unpack, check, mount, and wire the unit, then install the
software and configure settings.
Model: F35D00HCHF8AH6AM6BP8BX7A
RATINGS:
F35
Mods: NONE
Wiring Diagram: See manual
Multiple Feeder Management Relay Control Power: 125-250 V — 0.7A/100-240, 50/60Hz, 0.7A
Contact Inputs: 300 V ---- Max 10mA Inst. Manual: 1601-0106
Serial Number: AAIC07000515
Contact Outputs: Refer to Instruction Manual Firmware: A09MA521.000
GE Multilin E83849 Mfg. Date: NOV 12, 2012
PO Num: 600001234.56
Item Num:
® LISTED
® IND.CONT. EQ.
52TL
832772A2.CDR
4. For any issues, contact GE Digital Energy as outlined in the For Further Assistance section in chapter 1.
5. Check that you have the latest copy of the F35 Instruction Manual and the UR Series Communications Guide, for the
applicable firmware version, at http://gedigitalenergy.com/multilin/manuals/index.htm
The Instruction Manual outlines how to install, configure, and use the unit. The Communications Guide is for advanced use
with communication protocols. The warranty is included at the end of this instruction manual and on the GE Digital Energy
website.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm]
842807A1.CDR
0.280”
[7,11 mm]
Typ. x 4
CUT-OUT
4.000”
[101,60 mm]
17.750”
[450,85 mm] 842808A1.CDR 3
Figure 3-3: Horizontal mounting and dimensions (standard panel)
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
Figure 3-4: Vertical dimensions (enhanced panel)
Mounting Bracket Front of Panel
7.48”
(190.0 mm)
Front
Bezel
3
13.56”
15.00” (344.4 mm)
(381.0 mm)
14.03”
9.58” (356.2 mm) CUTOUT
(243.4 mm)
Front of Panel
Reference only 13.66”
(347.0 mm)
1.38”
(35.2 mm)
Mounting Bracket
Vertical Enhanced Top View
Front
bezel
13.72" 13.50"
(348.5 mm) (342.9 mm)
7.13”
(181.1 mm)
1.85" 4.00
(47.0 mm) (101.6)
1.57” 0.46”
(39.9 mm) (11.7 mm)
9.00"
(228.6 mm) Mounting bracket
(365.8 mm)
(346.7 mm)
14.40”
13.65”
Terminal blocks
7.00"
(177.8 mm)
For details on side-mounting F35 devices with the enhanced front panel, see the following documents available on the UR
DVD and the GE Digital Energy website.
• GEK-113180 — UR-series UR-V side-mounting front panel assembly instructions
• GEK-113181 — Connecting the side-mounted UR-V enhanced front panel to a vertical UR-series device
• GEK-113182 — Connecting the side-mounted UR-V enhanced front panel to a vertically-mounted horizontal UR-series
device
For details on side-mounting F35 devices with the standard front panel, see the following figures.
Figure 3-6: Vertical side-mounting installation (standard panel)
F35
Mods: NONE
Wiring Diagram: See manual
Multiple Feeder Management Relay Control Power: 125-250 V — 0.7A/100-240, 50/60Hz, 0.7A
Contact Inputs: 300 V ---- Max 10mA Inst. Manual: 1601-0106
Serial Number: AAIC07000515
Contact Outputs: Refer to Instruction Manual Firmware: A09MA521.000
GE Multilin E83849 Mfg. Date: NOV 12, 2012
PO Num: 600001234.56
Item Num:
® LISTED
® IND.CONT. EQ.
52TL
X W V U T S R P N M L K J H G F D B
c b a c b a c b a c b a
b a
LK1
Tx1 1
1
2
Rx1 2
ACT1
3
LK2
3
Tx1
4
4
5
Tx2 b a
ACT2 5
1
1 6
2 LK3
2 6
3
Rx2 3 7
4
4 7
8
Tx2 8
ACT3
IN
The small form-factor pluggable ports (SFPs) are pluggable transceivers. Do not use non-validated
NOTICE transceivers or install validated transceivers in the wrong Ethernet slot, else damage can occur.
The relay follows a convention with respect to terminal number assignments, which are three characters long and
assigned by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from
the first slot position (nearest to CPU module), indicated by an arrow marker on the terminal block. The figure shows an
example of rear terminal assignments.
Figure 3-8: Example of modules in F and H slots
3.3 Wiring
3.3.1 Typical wiring
Figure 3-9: Typical wiring diagram (T module shown for CPU)
Typical configuration.
The AC signal path is configurable. Positive watts
6H
I
Voltage and A B C
H1b H1 IA F1b
current supervision V
TC1 H1c
IA1 F1c
H2a I
H2b H2 IB5 F2a
V
Voltage supervision H2c F35 IB F2b
TC2 H3a I Multiple Feeder IB1 F2c
Protection System 1
H3b H3
V IC5 F3a
H3c
3
H4a I IC F3b
H4b H4 IC1 F3c
Current inputs
IG
I
F4b
H5b H5
V IG1 F4c
I
P1b P1 IG5 F8a
V
P1c IG F8b
P2a I IG1 F8c
P2b P2 IA5 M1a
V
P2c
IA M1b
P3a
P3b P3 IA1 M1c
( DC only )
IG M4b
P7a Contact input P7a
IG1 M4c
P7c Contact input P7c
P8a Contact input P8a IA5 M5a
P8c Contact input P8c IA M5b
P7b Common P7b IA1 M5c
P8b Surge IB5 M6a
IB M6b
B1b IB1 M6c
B1a Critical failure 4
B2b IC5 M7a
DC B3a IC M7b
48 V DC output
B3b IC1 M7c
B5b HI
Power supply
IG5 M8a
AC or DC B6b LO Control power
IG M8b
B6a
B8a Surge IG1 M8c
B8b Filter IA5 U1a
Fibre IA U1b
Tx1100BaseFX
optic Port 1 IA1 U1c
T
Rx1
IB U2b
Shielded Tx3100BaseFX
Ground at Port 3 IB1 U2c 5
twisted pairs Rx3
remote IC5 U3a
D1a
Type 8F/8G CT/VT module
device
D2a RS485 COM 2 IC U3b
D3a COM IC1 U3c
D4b
IG5 U4a
D4a
IRIG-B input IG U4b
CPU
VB U6a
VB U6c
VC U7a
Contacts shown
No. 10AWG with no VC U7c
Modules must be
minimum control power VX U8a Connection
grounded if terminal
is provided VX U8c as required
Ground bus
832778A2.CDR
Filter networks and transient protection clamps are used in the hardware to prevent damage caused
NOTICE by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90
specified test voltage for a period longer than the specified one minute.
NOTE:
AC or DC 14 gauge stranded
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
3
or braided wire
827247A1.CDR
Ground
outside CT
3
To ground;
LOAD must be on
load side
LOAD 996630A6.CDR
The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features, which are optional features available for some UR models.
Substitute the tilde “~” symbol with the slot position of the module in the following figure.
NOTE
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 6a
~ 7a
~ 8a
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
VC
VB
VA
VX
IG
IG1
IA
IC
IA1
IC1
IB
IB1
IG5
VC
VB
VA
VX
IA5
IC5
IB5
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 5b
~ 6a
~ 6b
~ 7a
~ 7b
~ 8a
~ 8b
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
IG
IG
IG1
IG1
IA
IC
IA
IC
IA1
IC1
IA1
IC1
IB
IB
IB1
IB1
IG5
IG5
IA5
IC5
IA5
IC5
IB5
IB5
Current inputs
8H, 8J, 8N, and 8R modules (8 CTs)
842766A3.CDR
• Integrates seamlessly with existing UR applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules
• Communicates using open standard IEC 61850 messaging
For details on the HardFiber system, see its Instruction Manual.
Figure 3-13: Form-A and solid-state contact outputs with voltage and current monitoring
~#a ~#a
I I
~#b ~#b Load
V Load V
~#c + ~#c +
a) Voltage with optional
Voltage monitoring only Both voltage and current monitoring
current monitoring
~#a ~#a
V V
~#a
~#b
Load
~#c +
c) No monitoring 827862A4.CDR
The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON, CONT OP
# VOFF, and CONT OP # ION) that can be used in protection, control, and alarm logic. The typical application of the voltage
monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the control
command.
See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied
for breaker trip circuit integrity monitoring.
Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears,
substitute the contact number.
NOTE
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
NOTICE FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
Table 3-3: Contact input and output module assignments
~6A module ~6B module ~6C module ~6D module
Terminal Output or Terminal Output or Terminal Output Terminal Output
assignment input assignment input assignment assignment
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4
~5a, ~5c
Form-C
2 Inputs
~4
~5
Form-C
Form-C
~4
~5
Form-C
Form-C
~4a, ~4c
~5a, ~5c
2 Inputs
2 Inputs
3
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
842762A3.CDR
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
~ 8c
3
~ 5a CONTACT IN ~ 5a DIGITAL I/O 6N V ~ 1a ~ 7a CONTACT IN ~ 7a DIGITAL I/O 6P V ~ 1a
I I
~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
V ~ 3a V ~ 3a
~ 7c CONTACT IN ~ 7c I I
~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
V ~ 4a V ~ 4a
~ 7b COMMON ~ 7b I I
~4 ~ 4b ~4 ~ 4b
~ 8b SURGE ~ 4c ~ 4c
V ~ 5a
I
~5 ~ 5b
~ 5c
V ~ 6a
I
~6 ~ 6b
~ 5a CONTACT IN ~ 5a DIGITAL I/O 6R ~ 1a
~ 6c
~ 5c CONTACT IN ~ 5c ~1 ~ 1b
~ 6a CONTACT IN ~ 6a ~ 1c
~ 6c CONTACT IN ~ 6c ~ 2a
~ 5b COMMON ~ 5b ~2 ~ 2b
~ 2c ~ 7a CONTACT IN ~ 7a DIGITAL I/O 6S ~ 1a
~ 7a CONTACT IN ~ 7a
~ 3a ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 7c CONTACT IN ~ 7c
~3 ~ 3b ~ 8a CONTACT IN ~ 8a ~ 1c
~ 8a CONTACT IN ~ 8a
~ 3c ~ 8c CONTACT IN ~ 8c ~ 2a
~ 8c CONTACT IN ~ 8c
~ 4a ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 7b COMMON ~ 7b
~4 ~ 4b ~ 2c
~ 8b SURGE ~ 4c ~ 8b SURGE
~ 3a
~3 ~ 3b
~ 3c
~ 4a
~4 ~ 4b
~ 5a CONTACT IN ~ 5a DIGITAL I/O 6T ~ 1a ~ 4c
~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 5a
~ 6a CONTACT IN ~ 6a ~ 1c ~5 ~ 5b
~ 6c CONTACT IN ~ 6c ~ 2a ~ 5c
~ 5b COMMON ~ 5b ~2 ~ 2b ~ 6a
~ 2c ~6 ~ 6b
~ 7a CONTACT IN ~ 7a ~ 6c
~ 3a
~ 7c CONTACT IN ~ 7c
~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a
~ 7b COMMON ~ 7b
~4 ~ 4b
~ 7a CONTACT IN ~ 7a DIGITAL I/O 6U ~ 1a
~ 8b SURGE ~ 4c
~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 8a CONTACT IN ~ 8a ~ 1c
~ 8c CONTACT IN ~ 8c ~ 2a
~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c
~ 8b SURGE
~ 3a
~3 ~ 3b
~ 3c
~ 4a
~4 ~ 4b
~ 4c
~ 5a
~5 ~ 5b
~ 5c
~ 6a
~6 ~ 6b
~ 6c
842763A2.CDR
For proper functionality, observe the polarity shown in the figures for all contact input and output
NOTICE connections.
(Dry)
Terminals from type 6B
contact input/output module (Wet)
Terminals from type 6B
contact input/output module
3
~7a Contact input 1 ~7a Contact input 1
~7c Contact input 2 ~7c Contact input 2
~8a Contact input 3 24 to 250 V ~8a Contact input 3
~8c Contact input 4 ~8c Contact input 4
~7b Common ~7b Common
~8b Surge ~8b Surge
B1b
B1a Critical failure
B2b
Power supply module
B3a
48 V DC output
B3b
B5b HI+
B6b LO+ Control power
B6a
B8a Surge
B8b Filter
827741A5.CDR
Where a tilde “~” symbol appears, substitute the slot position of the module.
NOTE
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend
using an external DC supply.
50 to 70 mA
3 mA
time
25 to 50 ms 842749A1.CDR
3 Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with
auto-burnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed. Then, within
25 to 50 ms, this current is slowly reduced to 3 mA as indicated. The 50 to 70 mA peak current burns any film on the
contacts, allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing
starts when external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two
contact inputs have common ground, as opposed to four contact inputs sharing one common ground (see the Contact
Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources.
Consequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.
Figure 3-18: Auto-burnish DIP switches
842751A1.CDR
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-burnish
functionality using an oscilloscope.
Transducer output modules provide DC current outputs in several standard DCmA ranges. Software is provided to
configure virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three
terminals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column
"a" having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single
input/output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The following figure illustrates the
transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.
Where a tilde “~” symbol appears, substitute the slot position of the module.
3
NOTE
842764A1.CDR
Hot ~1a
RTD ~1
Comp ~1c
For RTD ~1 & ~2 Return ~1b RTD terminals
3 RTD ~2
Hot ~2a
Comp ~2c
RTD
3.3.9.1 Overview
In addition to the faceplate RS232 port, there is a rear RS485 communication port.
T
optic cable Tx1 Rx1 100Base-FX
Tx2 Rx2 100Base-FX Port 2
Shielded Tx3 Rx3 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
U
100Base-TX Port 1
Tx1 Rx1 100Base-FX Port 2
Shielded Tx1 Rx1 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
Port 1
V
100Base-TX
100Base-TX Port 2
Shielded 100Base-TX
twisted-pairs Port 3
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
842722A4.CDR
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are provided internally at both communication ports. An
isolated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum
reliability, ensure that all equipment has similar transient protection devices installed.
Terminate both ends of the RS485 circuit with an impedance as shown in the figure.
Figure 3-23: RS485 serial connection
COM
3 COMP 485COM
COMP 485COM
Up to 32 devices,
maximum 4000 feet
(1200 m)
Relay
ZT (*)
RS485 +
RS485 –
3.3.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The
IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the F35 operates an internal oscillator with 1 µs
resolution and accuracy. The IRIG time code formats are serial, width-modulated codes that can be either DC level shifted
or amplitude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a
global positioning system (GPS) satellite system to obtain the time reference so that devices at different geographic
locations can be synchronized.
UR-series device
4B IRIG-B (+)
IRIG-B
4A IRIG-B (–)
time code generator
RG58/59 coaxial cable Receiver
(DC-shift or + BNC (in)
amplitude modulated
signal can be used)
IRIG-B
time code generator
UR-series device
Twisted-pair cable
(DC-shift or +
4B IRIG-B (+)
amplitude modulated
4A IRIG-B (–)
signal can be used)
Receiver
BNC (in)
827756A8.CDR
Tx
UR 1
Rx
Tx
UR 2
Rx
Tx
UR 3
Rx
Tx
UR 4
3
Rx
842006A2.CDR
The interconnection for dual-channel type 7 communications modules is shown as follows. Two-channel modules allow for
a redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The
required connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the
first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring.
Figure 3-26: Direct input and output dual-channel connection
Tx1
Rx1
UR 1
Tx2
Rx2
Tx1
Rx1
UR 2
Tx2
Rx2
Tx1
Rx1
UR 3
Tx2
Rx2
Tx1
Rx1
UR 4
Tx2
Rx2
842007A3.CDR
The following diagram shows the connection for three UR-series relays using two independent communication channels.
UR1 and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication
channels can be of different types, depending on the type 7 modules used. To allow the direct input and output data to
cross-over from channel 1 to channel 2 on UR2, set the DIRECT I/O CHANNEL CROSSOVER setting to “Enabled” on UR2. This
forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.
Figure 3-27: Direct input and output single/dual channel combination connection
Tx
UR 1
Rx
Channel 1
Tx1
Rx1
UR 2
Tx2
Rx2
3
Channel 2
Tx
UR 3
Rx
842013A2.CDR
The inter-relay communications modules are available with several interfaces and some are outlined here in more detail.
Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the
Order Code tables in Chapter 2. All of the fiber modules use ST type connectors.
Rx1 Rx1
Tx1 Tx1
Rx2
Tx2
1 channel 2 channels
831719A3.CDR
Tx1 Tx1
Rx1 Rx1
Tx2
Rx2
3
1 channel 2 channels
831720A5.CDR
The following figure shows configuration for the 2I and 2J fiber-laser modules.
Figure 3-30: 2I and 2J laser fiber modules
2I and 2J
modules
Rx1
Tx1
Rx2
Tx2
2 channels
831827A1.CDR
3.4.4.1 Description
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The SETTINGS PRODUCT SETUP DIRECT I/O DIRECT I/O DATA RATE setting is not
applicable to this module.
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end.
Connecting the shield to pin X1a or X6a grounds the shield since these pins are connected internally to ground. Thus, if
pin X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is
protected by surge suppression devices.
Figure 3-31: G.703 interface configuration
Shield ~1a
7S
Tx – ~1b
G.703 Rx – ~2a
channel 1
Tx + ~2b
Rx + ~3a
G.703 communications
Surge ~3b
Shield ~6a
Tx – ~6b
G.703
3
channel 2 Rx – ~7a
Tx + ~7b
Rx + ~8a
Surge ~8b
842773A3.CDR
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical
arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3-32: Typical PIN interconnection between two G.703 interfaces
Shield X1a X1a Shield
7S
7S
Tx – X1b X1b Tx –
G.703 Rx – X2a X2a Rx – G.703
channel 1 channel 1
Tx + X2b X2b Tx +
Rx + X3a X3a Rx +
G.703 communications
G.703 communications
Surge X3b X3b Surge
Shield X6a X6a Shield
Tx – X6b X6b Tx –
G.703 Rx – X7a X7a Rx – G.703
channel 2 channel 2
Tx + X7b X7b Tx +
Rx + X8a X8a Rx +
Surge X8b X8b Surge
831727A5.CDR
Pin nomenclature differs from one manufacturer to another. It is not uncommon to see pinouts numbered TxA,
TxB, RxA, and RxB. In such cases, assume that “A” is equivalent to “+” and “B” is equivalent to “–.”
NOTE
Ejector/inserter clip
FRONT
Channel 1
Timing selection
switches
Top cover
3
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
842752A2.CDR
DMX G7R
842774A1.CDR
In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing.
One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the
interface.
Figure 3-36: G.703 dual loopback mode
DMX G7R
842775A1.CDR
3.4.5.1 Description
There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel
RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 20-24 twisted shielded pair cable
is recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are connected internally to the ground pin (8a). Proper shield termination is as follows:
• Site 1 — Terminate shield to pins 6a or 7b or both
• Site 2 — Terminate shield to COM pin 2b
Match the clock terminating impedance with the impedance of the line.
Figure 3-37: RS422 interface connections
3 Single-channel RS422 module Dual-channel RS422 module
~ 3b ~ 3b
7W
Tx – Tx –
7T
~ 3a Rx – ~ 3a Rx –
RS422
~ 2a Tx + RS422 ~ 2a Tx +
channel 1
~ 4b Rx + Inter-relay comms. ~ 4b Rx +
~ 6a Shield ~ 6a Shield
Inter-relay communications
~ 7a ~ 5b Tx –
Clock
~ 8b ~ 5a Rx –
RS422
~ 2b COM ~ 4a Tx +
channel 2
~ 8a Surge ~ 6b Rx +
~ 7b Shield
~ 7a
Clock
~ 8b
~ 2b COM
The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
Figure 3-38: Typical PIN interconnect between two RS422 interfaces
Tx – W3b W3b Tx –
RS422 communications 7T
RS422 communications 7T
Rx – W3a W3a Rx –
RS422 Tx + W2a W2a Tx + RS422
channel 1 channel 1
Rx + W4b W4b Rx +
Shield W6a W6a Shield
+ W7a W7a +
Clock Clock
– W8b W8b –
Common COM W2b W2b COM Common
Surge W8a W8a Surge
+ –
source. As a result, data sampling for both of the UR RS422 channels is synchronized via the send timing leads on data
module 1, shown as follows. If the terminal timing feature is not available or this type of connection is not wanted, the
G.703 interface is a viable option that does not impose timing restrictions.
Figure 3-39: Timing configuration for RS422 two-channel, three-terminal application
Data module 1
Signal name
Tx1(+) W 2a SD(A) - Send data
7W
Tx1(-) W 3b SD(B) - Send data
RS422
CHANNEL 1
Rx1(+) W 4b RD(A) - Received data
Rx1(-) W 3a RD(B) - Received data
Shld. W 6a RS(A) - Request to send (RTS)
INTER-RELAY COMMUNICATIONS
+ W 7a RS(B) - Request to send (RTS)
CLOCK
– W 8b RT(A) - Receive timing
Tx2(+) W 4a RT(B) - Receive timing
Tx2(-) W 5b CS(A) - Clear To send
RS422
CHANNEL 2
Rx2(+) W 6b CS(B) - Clear To send
3
Rx2(-) W 5a Local loopback
Shld. W 7b Remote loopback
com W 2b Signal ground
SURGE W 8a ST(A) - Send timing
ST(B) - Send timing
Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
Data module 1 provides timing to the F35 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure because they vary by manufacturer.
Tx Clock
Tx Data
831733A1.CDR
3 AWG 20-24 twisted shielded pair is recommended for external RS422 connections and ground the shield only at one end.
For the direct fiber channel, address power budget issues properly.
When using a laser interface, attenuators can be necessary to ensure that you do not exceed
NOTICE maximum optical input power to the receiver.
Figure 3-41: RS422 and fiber interface connection
+ ~7a
7L, 7M, 7N,
7P, and 74
Clock
channel 1 – ~8b
Common COM ~2b
Tx – ~3b
Rx – ~3a
RS422 Tx + ~2a
channel 1
communications
Rx + ~4b
Shield ~6a
Fiber Tx2 Rx2
RS422
channel 2
Surge ~8a
842777A2.CDR
The connections shown in the figure are for multiplexers configured as data communications equipment (DCE) units.
When using a laser interface, attenuators can be necessary to ensure that you do not exceed the
NOTICE maximum optical input power to the receiver.
Shield ~1a
communications
Rx + ~3a
Surge ~3b
Fiber Tx2
G.703
channel 2 Rx2
842778A2.CDR
Digital
UR-series multiplexer,
device IEEE C37.94
compliant
up to 2 km
842755A2.CDR
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a non-
compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard. The
following figure shows the concept.
842756A2.CDR
The UR-series C37.94 communication module has six switches to set the clock configuration. The following figure shows
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. With power to the relay off, remove the IEEE C37.94 module (type 2G, 2H, 2I, 2J, 76, or 77 module) as follows. Record
the original location of the module to help ensure that the same or replacement module is inserted into the correct
slot.
2. Simultaneously pull the ejector/inserter clips located at the top and bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
6. Replace the top cover and the cover screw.
7. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Ejector/inserter clip
FRONT
Channel 1
Timing selection
switches
Top cover
3
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Figure 3-45: Status LEDs
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
Tel: (905)294-6222
Fax: (905)201-2098
Rx2
(NORTH AMERICA)
1 800 547-8629
GE Multilin
Digital
UR-series
multiplexer
device
C97.94SM
up to 10 km
842757A2.CDR
It also can be connected directly to any other UR-series relay with a C37.94SM module, as shown.
C37.94SM
fiber interface
UR-series UR-series
device with device with
C37.94SM C37.94SM
module module
up to 10 km
842758A2.CDR
The UR-series C37.94SM communication module has six switches that are used to set the clock configuration. The
following figure shows the functions of these control switches.
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher-order systems.
3
The C37.94SM communications module cover removal procedure is as follows:
1. With power to the relay off, remove the C37.94SM module (module 2A or 2B) as follows. Record the original location of
the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release
the module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
6. Replace the top cover and the cover screw.
7. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Ejector/inserter clip
FRONT
Channel 1
Timing selection
switches
Top cover
3
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Figure 3-48: Status LEDs
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
Tel: (905)294-6222
Fax: (905)201-2098
Rx2
(NORTH AMERICA)
1 800 547-8629
GE Multilin
The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message displays.
2. Press the MESSAGE right arrow until the SECURITY message displays.
3. Press the MESSAGE down arrow until the INSTALLATION message displays.
4. Press the MESSAGE right arrow until the RELAY SETTINGS: Not Programmed message displays.
SETTINGS
SETTINGS SECURITY
PRODUCT SETUP
DISPLAY
PROPERTIES
INSTALLATION RELAY SETTINGS:
Not Programmed
5. After the RELAY SETTINGS: Not Programmed message displays, press a VALUE key to change the selection to
"Programmed."
6. Press the ENTER key to save the change.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
3 To communicate via the faceplate RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to
the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports
section earlier in this chapter.
Figure 3-49: Relay communication options
Regional
control
center
Ethernet Remote
10/100 Mbps communications link
Local
control
UR-series IED
EnerVista Engineer
Modem
GE Multilin F485
communications converter
RS232
EnerVista
Reports
EnerVista
Troubleshooting
Commissioning
Setting changes
842759A2.CDR
To communicate through the F35 rear RS485 port from a computer RS232 port, the GE Digital Energy RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the F35 rear communications port. The
converter terminals (+, –, GND) are connected to the F35 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as
described in this chapter.
5. In the EnerVista Launch Pad window, click the Add Product button and select the appropriate product as follows.
Select the Web option to ensure the most recent software release, or select CD if you do not have an Internet
connection, then click the Add Now button to list software items for the product. EnerVista Launchpad obtains the
software from the Internet or DVD and automatically starts the installation program.
6. Select the complete path, including the new directory name, where the EnerVista UR Setup software is to be installed.
7. Click the Next button to begin the installation. The files are installed in the directory indicated, and the installation
program automatically creates icons and adds an entry to the Windows start menu.
8. Click Finish to complete the installation. The UR device is added to the list of installed intelligent electronic devices
(IEDs) in the EnerVista Launchpad window, as shown.
Figure 3-52: UR device added to Launchpad window
9. Enter the COM port used by the computer, the baud rate, and parity settings from the front panel SETTINGS PRODUCT
SETUP COMMUNICATIONS SERIAL PORTS menu, and the relay slave address setting from the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL MODBUS SLAVE ADDRESS menu in their respective
fields.
10. Click the Read Order Code button to connect to the F35 and upload the order code to the software. If a
communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the
previous step correspond to the relay setting values.
11. Click the OK button when the relay order code has been received. The new device is added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The device has now been configured for RS232 communications. Proceed to the Connect to the F35 section to begin
communication.
3 5.
6.
Click the Add Device button to define the new device.
Enter the desired name in the “Device Name” field and a description (optional) of the site.
7. Select “Ethernet” from the Interface drop-down list. This displays a number of interface parameters that must be
entered for proper Ethernet functionality.
Figure 3-54: Configuring Ethernet communication
8. Enter the relay IP address specified in the front panel SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK
IP ADDRESS in the IP Address field.
9. Enter the relay slave address and Modbus port address values from the respective settings in the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.
10. Click the Read Order Code button to connect to the UR device and upload the order code. If an communications error
occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting
values.
11. Click OK when the relay order code has been received. The new device is added to the Site List window (or Online
window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the F35 section to
begin communications.
3
Expand the site list by double-clicking
or selecting the +/– box.
842743A3.CDR
2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly set up for communications (steps A and B earlier).
3. If a relay icon appears in place of the status indicator, then a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be edited, printed, or changed.
3.8.2 Use Quick Connect via the front panel RS232 port
To connect to the UR from a computer using a serial cable:
1. Connect a nine-pin to nine-pin RS232 serial cable to the computer and the front panel RS232 port.
2. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista DVD or
online from http://www.gedigitalenergy.com/multilin). See the software installation section if not already installed.
3. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.
4. Click the Quick Connect button to open the window.
5. Select the Serial interface and the correct COM Port, then click Connect.
6. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and displays them on the left side of the screen. Expand the sections to view data directly from the
F35 device. Use the Device Setup button to change the site names.
3
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model
number.
Now, assign the computer an IP address compatible with the relay’s IP address.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window.
3
2. Right-click the Local Area Connection icon and select Properties.
3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
Before using the Quick Connect feature through the Ethernet port, disable any configured proxy settings in Internet
Explorer.
1. Start the Internet Explorer software.
2. Select the Tools > Internet Options menu item and click the Connections tab.
3. Click on the LAN Settings button to open the following window.
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F35 relay.
1. Start the Internet Explorer software.
2. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.
4. Select the Ethernet interface and enter the IP address assigned to the F35, then click the Connect button. The
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them on the left side of the screen.
5. Expand the sections to view data directly from the F35 device. 3
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model
number.
When direct communications with the F35 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown.
If the computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F35 relay.
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under Settings > Product Setup > Security > Supervisory. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista.
If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for
example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the
passwords for the other three roles is optional.
Chapter 4: Interfaces
Interfaces
This chapter explains the EnerVista software interface, the front panel interface, and logic diagrams.
• Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the F35 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address
IP Subnet Mask
IP Routing
When a settings file is loaded to a F35 that is in-service, the following sequence occurs:
1. The F35 takes itself out of service.
4 2. The F35 issues a UNIT NOT PROGRAMMED major self-test error.
3. The F35 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.
2 1 6 7
10
4
4
9 8 842786A2.CDR
Alternatively, the settings template can also be applied to online settings, as follows.
1. Select an installed device in the online window of the EnerVista UR Setup window.
2. Right-click the selected device and select the Template Mode > Create Template option.
The software prompts for a template password. This password is required to use the template feature and must be at
least four characters in length.
3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
The software prompts for a template password. This password must be at least four characters in length.
When templates are created for online settings, the password is added during the initial template creation
step. It does not need to be added after the template is created.
NOTE
Viewing the settings in template mode also modifies the settings menu, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings menu is shown as follows.
Figure 4-5: Applying templates using the View in Template Mode settings command
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Use the following procedure to display settings available for editing and settings locked by the template.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2.
3.
Apply the template by selecting the Template Mode > View All Settings option.
Enter the template password then click OK to apply the template.
4
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown as follows.
Figure 4-6: Applying templates using the View All Settings command
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
The EnerVista software removes all template information and all settings are available.
5. Click the Save button to save and apply changes to the settings template.
6. Select the Template Mode > View In Template Mode option to view the template.
7. Apply a password to the template then click OK to secure the FlexLogic equation.
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries is shown here.
Figure 4-8: Locking FlexLogic entries through settings templates
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
4
The FlexLogic entries are also shown as locked in the graphical view and on the front panel display.
Figure 4-9: Secured FlexLogic in graphical view
2. Enter the serial number of the F35 device to lock to the settings file in the Serial # Lock field.
3. Click the OK button to apply the change.
4 The settings file and corresponding secure FlexLogic equations are now locked to the F35 device specified by the serial
number.
The serial number of the UR-series device and the file transfer
date are added to the setting file when setting files
are transferred to the device.
842863A1.CDR
This information is also available in printed settings file reports as shown in the example.
Figure 4-13: Settings file report showing traceability data
Traceability data
in settings report
842862A1.CDR
842865A1.CDR
This information is also available from the front panel display through the following actual values:
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION SERIAL NUMBER
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE
SETTINGS
PRODUCT SETUP
HELP 4 5 6
3. Press to scroll third level fields MESSAGE
2. Press to scroll second level:
ESCAPE 1 2 3 PRODUCT SETUP.
4. Press to scroll through values
ENTER VALUE 0 . +/-
5. Press to save change
842231A1.cdr
4.2.4.1 Example
ACTUAL VALUES Press the MENU key until the header for the first Actual Values page appears. This page contains
STATUS system and relay status information. Repeatedly press the MESSAGE keys to display the other
actual value headers.
SETTINGS Press the MENU key until the header for the first page of Settings appears. This page contains
PRODUCT SETUP settings to configure the relay.
SETTINGS Press the MESSAGE down arrow to move to the next Settings page. This page contains settings
SYSTEM SETUP for System Setup. Repeatedly press the MESSAGE up and down arrows to display the other
setting headers and then back to the first Settings page header.
SECURITY From the Settings page one header (Product Setup), press the MESSAGE right arrow once to
display the first sub-header (Security).
4 ACCESS LEVEL:
Restricted
Press the MESSAGE right arrow once more and this displays the first setting for Security.
Pressing the MESSAGE down arrow repeatedly displays the remaining setting messages for the
Security sub-header.
SECURITY Press the MESSAGE left arrow once to move back to the first sub-header message.
DISPLAY Pressing the MESSAGE down arrow displays the second setting sub-header associated with the
PROPERTIES Product Setup header.
FLASH MESSAGE Press the MESSAGE right arrow once more to display the first setting for Display Properties.
TIME: 10.0 s
FLASH MESSAGE For example, select the SETTINGS PRODUCT SETUP DISPLAY PROPERTIES FLASH
TIME: 10.0 s MESSAGE TIME setting.
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the key again to view the
MAXIMUM: 10.0 next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point — The relay numeric keypad works the same as a calculator. A number is entered one digit at
a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MESSAGE left arrow or
pressing the ESCAPE key, returns the original value to the display.
• VALUE keys — The VALUE up arrow increments the displayed value by the step value, up to the maximum value
allowed. While at the maximum value, pressing the VALUE up arrow again allows the setting selection to continue
upward from the minimum value. The VALUE down arrow decrements the displayed value by the step value, down to
the minimum value. While at the minimum value, pressing the VALUE down arrow again allows the setting selection to
continue downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate numeric
TIME: 2.5 s keys in the sequence “2 . 5". The display message changes as the digits are being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Press ENTER to store the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation of the storing
process. Numerical values that contain decimal places are rounded-off if more decimal place digits
are entered than specified by the step value.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted," "Command," "Setting," and
Restricted "Factory Service."
4
Enumeration type values are changed using the VALUE keys. The VALUE up arrow displays the next selection while the
VALUE down arrow displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting," press the VALUE keys until the proper selection displays.
Setting Press HELP at any time for the context sensitive help messages.
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing ENTER stores the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation.
4.2.6 Faceplate
4.2.6.1 Enhanced faceplate
The front panel consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow access to the removable modules.
Display
Keypad
Front panel
RS232 port
Display
Front panel
RS232 port
The following figure shows the vertical arrangement of the faceplate panel for relays ordered with the vertical option.
GE Multilin
Display
MENU 7 8 9
HELP MESSAGE 4 5 6
ESCAPE 1 2 3 Keypad
ENTER VALUE 0 . +/-
1 3 5
User-programmable
USER LABEL USER LABEL USER LABEL
2
USER LABEL
4
USER LABEL
6
USER LABEL
pushbuttons 1-6
LED panel 2
4
STATUS EVENT CAUSE
IN SERVICE VOLTAGE
TROUBLE CURRENT RESET
TEST MODE FREQUENCY
TRIP
ALARM
PICKUP
OTHER
PHASE A
PHASE B
USER 1
USER 2
LED panel 1
PHASE C
NEUTRAL/GROUND USER 3
827830A3.CDR
842811A1.CDR
• IN SERVICE — This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are
OK, and that the device has been programmed
• TROUBLE — This LED indicates that the relay has detected an internal problem
• TEST MODE — This LED indicates that the relay is in test mode. For more information, see the Test Mode section in the
Settings chapter.
• TRIP — This LED indicates that the FlexLogic operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to reset.
• ALARM — This LED indicates that the FlexLogic operand serving as an alarm switch has operated. This indicator is
never latched.
• PICKUP — This LED indicates that an element is picked up. This indicator is never latched.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event-cause LEDs
remain on as long as the operate operand associated with the element remains asserted. If a protection element target
setting is “Latched,” then the corresponding event-cause LEDs turn on when the operate operand associated with the
element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
4 includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — This LED indicates voltage was involved
• CURRENT — This LED indicates current was involved
• FREQUENCY — This LED indicates frequency was involved
• OTHER — This LED indicates a composite function was involved
• PHASE A — This LED indicates phase A was involved
• PHASE B — This LED indicates phase B was involved
• PHASE C — This LED indicates phase C was involved
• NEUTRAL/GROUND — This LED indicates that neutral or ground was involved
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label
package of every F35, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-Programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
842781A1.CDR
Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay has been programmed
• TROUBLE — Indicates that the relay has detected an internal problem
• TEST MODE — Indicates that the relay is in test mode. For more information, see the Test Mode section in the Settings
chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a Trip switch has operated. This indicator always
4
latches; the reset command must be initiated to allow the latch to be reset.
• ALARM — Indicates that the selected FlexLogic operand serving as an Alarm switch has operated. This indicator is
never latched.
• PICKUP — Indicates that an element is picked up. This indicator is never latched.
Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event cause LEDs
remain on as long as operate the operand associated with the element remains asserted. If a protection element target
setting is “Latched,” then the corresponding event cause LEDs turn on when the operate operand associated with the
element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — Indicates voltage was involved
• CURRENT — Indicates current was involved
• FREQUENCY — Indicates frequency was involved
• OTHER — Indicates a composite function was involved
• PHASE A — Indicates phase A was involved
• PHASE B — Indicates phase B was involved
• PHASE C — Indicates phase C was involved
• NEUTRAL/GROUND — Indicates that neutral or ground was involved
User-programmable indicators
The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Support for
applying a customized label beside every LED is provided.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
842782A1.CDR
4 •
•
RECLOSE IN PROGRESS — A reclose operation is in progress
RECLOSE LOCKED OUT — The recloser is not operational and requires a reset
Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six
setting groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting
NOTE
groups. Even though the LEDs have default labels, they are fully user-programmable.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in
the next section.
Figure 4-22: LED panel 2 (default labels)
842784A1.CDR
To create custom LED labels for the enhanced front panel display:
1. Start the EnerVista UR Setup software.
2. Select the Front Panel Report item at the bottom of the navigation menu for the settings file. The front panel report
window displays.
Figure 4-23: Front panel report window
3. Enter the text to appear next to each LED and above each user-programmable pushbutton in the fields provided.
4. Feed the UR front panel label cutout sheet into a printer and press the Print button in the front panel report window.
5. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
6. Remove the UR label insert tool from the package and bend the tabs as described in the following procedures. These
tabs are used for removal of the default and custom LED labels.
Use the tool EXACTLY as outlined as follows, with the printed side containing the GE part number facing the
user.
NOTE
The label package shipped with every F35 contains the three default labels, the custom label template sheet, and the label
removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, use the following procedures to remove the original labels and insert the new ones.
To remove the LED labels from the F35 enhanced front panel and insert the custom labels:
1. Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from
the relay.
2. Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown.
To remove the user-programmable pushbutton labels from the F35 enhanced front panel and insert the custom labels:
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown. This attaches the
label tool to the user-programmable pushbutton label.
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the
buttons.
4
4.2.8.2 Standard faceplate
Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL:
http://www.gedigitalenergy.com/products/support/ur/GET-8494A.doc
This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures
are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x)
edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling.
1. Remove the clear Lexan Front Cover (GE part number: 1501-0014).
Push in
and gently lift
up the cover.
842771A1.CDR
2. Pop out the LED module and/or the blank module with a screwdriver as shown. Be careful not to damage the plastic
covers.
F60
R
842722A1.CDR
3. Place the left side of the customized module back to the front panel frame, then snap back the right side.
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a COMMAND
PASSWORD PASSWORD is required, that is, if COMMAND PASSWORD is enabled and no commands have been
issued within the last 30 minutes.
Press USER 1 This message appears if the correct password is entered or if none is required. This message
To Select Breaker displays for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED This message displays after the USER 1 key is pressed for the second time. Three possible actions
USER 2=CLS/USER 3=OP can be performed from this state within 30 seconds as per the following items (1), (2) and (3).
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is pressed
To Close BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is pressed
To Open BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
(3)
open breaker 1.
4
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different breaker is
USER 2=CLS/USER 3=OP selected. Three possible actions can be performed from this state as per (1), (2) and (3). Repeatedly
pressing the USER 1 key alternates between available breakers. Pressing keys other than USER 1, 2,
or 3 at any time cancels the breaker control function.
4 CHANGE SETTING
PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ---------
ENCRYPTED SETTING
PASSWORD: ---------
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change the
selection to “Yes.”
6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.
7. Type in a numerical password (up to 10 characters) and press the ENTER key.
8. When VERIFY NEW PASSWORD displays, re-type the password and press ENTER .
CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) password is active.
•
from the TRIP BUS 1 RESET FlexLogic operand must be 1, or output from the RESET OP FlexLogic operand must be 1.
For the settings, one of 16 input conditions at the top left must be met for the OR, the TRIP BUS 1 FUNCTION must be
4
Enabled, and the TRIP BUS 1 BLOCK output must output as 0, which is then negated/reversed by NOT to become 1.
Table 4-1: Logic diagram symbols
Symbol Description
= Off Output from FlexLogic operand, so user-defined
= Enabled 1 = Enabled and 0 = Disabled
OR Any function input on the left side satisfies the condition
AND All functions input on the left side are required to satisfy the condition
Not. Negates/reverses the output, for example 0 becomes 1.
Connection
S, R Set, Reset
TPKP Timer pickup. Triggered by the settings latch in the diagram.
TRST Timer reset. Triggered by the reset latch in the diagram.
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
Chapter 5: Settings
Settings
5 BREAKERS
See page 5-120
SETTING GROUP 2
SETTING GROUP 3
SETTING GROUP 4
SETTING GROUP 5
SETTING GROUP 6
VIRTUAL INPUTS
See page 5-220 5
CONTACT OUTPUTS See page 5-221
5.2 Overview
5.2.1 Introduction to elements
For URs, the term element is used to describe a feature that is based around a comparator. The comparator is provided
with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to determine if the input is
within the defined range that sets the output to logic 1, also referred to as setting the flag. A single comparator can make
multiple tests and provide multiple outputs. For example, the time overcurrent comparator sets a pickup flag when the
current input is above the setting and sets an operate flag when the input current has been at a level above the pickup
setting for the time specified by the time-current curve settings. All comparators use analog actual values as the input.
The exceptions to this rule are digital elements, which use logic states as inputs.
NOTE
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on a logic diagram. This includes the inputs, settings, fixed logic, and the
5 output operands generated. The previous chapter explains how to read a logic diagram, and the abbreviations used in a
diagram are defined in the Abbreviations chapter.
Some settings are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
Where the current source is from a single current transformer (CT), the base quantity is the nominal secondary or primary
current of the CT. Use the secondary current base to convert per-unit settings to/from a secondary current value, and use
the primary current base to convert to/from a primary current value.
Where the current source is the sum of two or more CTs with different nominal primary current, the primary base quantity
is the largest nominal primary current. For example, if CT1 = 300 / 5 A and CT2 = 100 / 1 A, then in order to sum these, CT2
is scaled to the CT1 ratio. In this case, the base quantity is 300 A primary, 5 A secondary for CT1, and 300/(100/1) = 3 A
secondary for CT2.
For voltage elements, the primary base quantity is the nominal phase-to-phase primary voltage of the protected system
provided that the VT ratio setting is set to the nominal ratio of the VTs and the secondary voltage setting is set to the
phase-to-phase voltage seen by the relay when the voltage of the protected system in nominal. The UR uses the
convention that nominal voltages in a three-phase system are phase-to-phase voltages.
For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta-
connected VTs, the secondary base quantity and secondary voltage setting is:
13800
-------------- 120 = 115 V Eq. 5-1
14400
For wye-connected VTs, the primary and secondary base quantities are as before, but the secondary voltage setting (here
a phase-to-ground value) is:
13800 120
-------------- -------- = 66.4 V Eq. 5-2
14400 3
Many settings are common to most elements, outlined as follows:
• FUNCTION setting — This setting programs the element to operate when selected as “Enabled.” The factory default is
“Disabled.” Once “Enabled,” any element associated with the function becomes active and all options become
available.
• NAME setting — This setting is used to uniquely identify the element.
• SOURCE setting — This setting is used to select the AC source to be monitored. See the Introduction to AC Sources
section later.
• PICKUP setting — For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings can be provided to define the
range of the measured parameters that cause the element to pick up.
• PICKUP DELAY setting — This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting — This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting — The default output operand state of all comparators is a logic 0 or “flag not set.” The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting — This setting is used to define the operation of an element target message. When set to "Disabled,"
no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to
“Self-Reset,” the target message and LED indication follow the operate state of the element and self-resets once the
operate element condition clears. When set to “Latched,” the target message and LED indication remains visible after
the element output returns to logic 0 until a RESET command is received by the relay.
• EVENTS setting — This setting is used to control whether the pickup, dropout, or operate states are recorded by the
event recorder. When set to “Disabled,” element pickup, dropout, or operate are not recorded as events. When set to
“Enabled,” events are created for:
5
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This can happen when the element is in the operate state if the reset delay time is not 0.
5.2.2.1 Background
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources, in
the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains all
the signals required to measure the load or fault in a particular power apparatus. A given source can contain all or some of
the following signals: three-phase currents, single-phase ground current, three-phase voltages, and an auxiliary voltage
from a single VT for checking for synchronism.
The basic idea of an AC source is to select a point on the power system where the voltages and currents are of interest. To
illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme that follows. In
this application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other
location or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor
sum (or difference) of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of
the CT connections). The same considerations apply to transformer winding 2. The protection elements require access to
the net current for transformer protection, but some elements can need access to the individual currents from CT1 and
CT2.
Winding 1
current
Winding 1
UR-series
relay Power
transformer
Winding 2
CT3 CT4
827791A3.CDR
In conventional analog or electronic relays, the sum of the currents is obtained from an appropriate external connection of
all CTs through which any portion of the current for the element being protected can flow. Auxiliary CTs are required to
perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the UR series of relays, provisions
have been included for all the current signals to be brought to the UR device where grouping, ratio correction, and
summation are applied internally via configuration settings.
A major advantage of using internal summation is that the individual currents are available to the protection device, for
5 example as additional information to calculate a restraint current, or to allow the provision of additional protection
features that operate on the individual currents, such as breaker failure.
Given the flexibility of this approach, it becomes necessary to add configuration settings to the platform to allow the user
to select which sets of CT inputs are to be added to form the net current into the protected device.
The internal grouping of current and voltage signals forms an AC source. This source can be given a specific name through
the settings and becomes available to protection and metering elements in the UR platform. Individual names can be
given to each source to help identify them for later use. For example, in the scheme shown in the preceding figure, the user
configures one source to be the sum of CT1 and CT2 and can name this source as “Wdg1 I.”
Once the sources have been configured, the user has them available as selections for the choice of input signal for the
protection elements and as metered quantities.
The UR platform allows for a maximum of six sets of three-phase voltages and six sets of three-phase currents. The result
of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is as follows.
Item Maximum number
CT/VT Module 3
CT Bank (3 phase channels, 1 ground channel) 6
VT Bank (3 phase channels, 1 auxiliary channel) 3
Lost password
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1. Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2. Enter the reset code on the front panel, under COMMANDS RELAY MAINTENANCE SERVICE COMMAND.
3. Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
• Password is case-sensitive
• Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
• Password must be 6 to 20 characters in length
• Password must contain characters from three of the following four categories:
– English uppercase characters (A through Z)
– English lowercase characters (a through z)
– Base 10 digits (0 through 9)
– Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
5 PASSWORD ACCESS:
EVENTS: Disabled
Range: Disabled, Enabled
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the F35, the remote password must be used. If the
connection is to the RS232 port of the faceplate, the local password must be used.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
• ACCESS LOC SETG OFF — Asserted when local setting access is disabled
• ACCESS LOC SETG ON — Asserted when local setting access is enabled
• ACCESS LOC CMND OFF — Asserted when local command access is disabled
• ACCESS LOC CMND ON — Asserted when local command access is enabled
• ACCESS REM SETG OFF — Asserted when remote setting access is disabled
• ACCESS REM SETG ON — Asserted when remote setting access is enabled
• ACCESS REM CMND OFF — Asserted when remote command access is disabled
• ACCESS REM CMND ON — Asserted when remote command access is enabled
A command or setting write operation is required to update the state of the remote and local security
operands listed.
NOTE
PASSWORD ACCESS EVENTS — This setting allows recording of password access events in the event recorder.
As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a CHANGE COMMAND PASSWORD or CHANGE
SETTING PASSWORD setting is programmed to “Yes” via the front panel interface, the following message sequence is
invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the “Restricted” level according to the
access level timeout setting values and when power is cycled.
If the setting and command passwords are identical, then this one password allows access to both commands
and settings.
NOTE
If a remote connection is established, local passcodes are not visible.
If you establish a local (serial) connection to the relay, you cannot view remote passcodes.
NOTE
Access supervision
SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION
ACCESS ACCESS LEVEL See below
SUPERVISION TIMEOUTS
The F35 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a
password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is asserted.
The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be used to
protect against both unauthorized and accidental access attempts.
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS CLEAR RECORDS RESET UNAUTHORIZED ALARMS
command. Therefore, to apply this feature with security, password-protect the Command level. The operand does not
generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed with
event logs or targets enabled.
The following table outlines access level timeout settings.
SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS
ACCESS LEVEL COMMAND LEVEL ACCESS Range: 5 to 480 minutes in steps of 1
TIMEOUTS TIMEOUT: 5 min
These settings allow the user to specify the length of inactivity required before returning to the Restricted access level.
Note that the access level is set to Restricted when control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to
return to Restricted access from the Command password level.
SETTING LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to return
to Restricted access from the Command password level.
This feature provides a mechanism to prevent unauthorized or unintended upload of settings to a relay through the local
or remote interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH — This setting is used for local (front panel or RS232 interface) setting access supervision. Valid
values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On,“ then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (on) prior to providing the local
setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message displays on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• REMOTE SETTING AUTH — This setting is used for remote (Ethernet or RS485 interface) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required. If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to
providing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• ACCESS AUTH TIMEOUT — This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On.” The state of the FlexLogic operand
is monitored continuously for an off-to-on transition. When this occurs, local access is permitted and the timer
programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the
timeout is restarted. The status of this timer updates every five seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
5
The Remote Settings Authorized setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required).
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
The Access Authorized Timeout setting represents the timeout delay remote setting access. It applies when the Remote
Settings Authorized setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the Access Authorized Timeout setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
2. Check the Enable Security check box in the lower-left corner to enable the security management system.
If you force password entry by using this feature, ensure that you know the Administrator password. If you do
NOTE
not know the password and are locked out of the software, contact GE Digital Energy for the default password
or a UR device. When using CyberSentry, the default password is "ChangeMe1#".
5
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.
3. Select the user access rights by enabling the check box of one or more fields.
3. Modify the user access rights by enabling or disabling one or more of the check boxes.
When the "Server" Authentication Type is selected, the F35 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the F35 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer), as login
accounts and the associated passwords are stored on the F35 device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server
authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.
Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features
5 NOTE
are open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found
open.
5
For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
5
For the Security panel, the following settings are available.
Table 5-3: RADIUS server settings
Setting name Description Minimum Maximum Default Units Minimum
permission
Primary RADIUS IP IP address of the main RADIUS server. 0.0.0.0 223.255.255.254 0.0.0.0 - Administrator
Address Default value indicates no Primary
RADIUS server is configured, and hence
RADIUS is disabled.
Primary RADIUS authentication port 1 65535 1812 - Administrator
Authentication Port
Primary Accounting RADIUS accounting port 1 65535 1813 - Administrator
Port
Vendor ID An identifier that specifies RADIUS Value that Administrator
vendor-specific attributes used with the represents
protocol General
Electric
RADIUS Shared secret used in authentication. It See the See the following N/A - Administrator
Authentication displays as asterisks. This setting must Password password section
(Shared) Secret meet the CyberSentry password Requirements for requirements
requirements. section earlier
in this chapter
RADIUS Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS - Administrator
Authentication server. Currently fixed to EAP-TTLS.
Method
Timeout Timeout in seconds between re- 0 9999 10 sec Administrator
transmission requests
Retries Number of retries before giving up 0 9999 3 - Administrator
LOGIN — This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
outlined here. For the Supervisor role, enable the “Supervisor Role” setting.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password.
The roles are defined as follows:
• Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
• Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
• Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
exist offline.
• Supervisor — This is only an approving role. This role’s authentication commits setting changes submitted by
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
• Observer — This role has read-only access to all F35 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available. It is for factory use only.
NOTE
The Change Local Passwords menu is shown on the front panel and in EnerVista upon successful login of the Administrator
role.
The LOGIN setting in this menu is similar to that described in SETTINGS > PRODUCT SETUP > SECURITY except for the factory
role.
Passwords are stored in text format. No encryption is applied.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
5
authentication mode the Observer role requires a password.
NOTE
If you are locked out of the software, contact GE Digital Energy for the default password. When using
CyberSentry, the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated
password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
SESSION SESSION LOCKOUT: Range: 0 to 99
SETTINGS 3
SESSION LOCKOUT — This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD — This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS
RESTORE DEFAULTS LOAD FACTORY Range: Yes, No
DEFAULTS: No
LOAD FACTORY DEFAULTS — This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
SUPERVISORY DEVICE Range: Yes, No
AUTHENTICATION: Yes
The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
5 DEVICE AUTHENTICATION — This setting is enabled by default, meaning "Yes" is selected. When enabled, Device
authentication with roles is enabled. When this setting is disabled, the UR only authenticates to the AAA server (RADIUS).
However, the Administrator and Supervisor (when enabled) remain active even after device authentication is disabled and
their only permission is to re-enable Device authentication. To re-enable Device authentication, the Supervisor unlocks the
device for settings changes, then the Administrator re-enables device authentication.
BYPASS ACCESS — The bypass security feature provides an easier access, with no authentication and encryption for those
special situations when this is considered safe. Only the Supervisor, or the Administrator when the Supervisor role is
disabled, can enable this feature.
Mode Front panel or serial (RS232, RS485) Ethernet
Normal mode Authentication — Role Based Access Control (RBAC) Authentication — RBAC and passwords encrypted
and passwords in clear SSH tunneling
Bypass access mode No passwords for allowed RBAC levels No passwords for allowed RBAC levels
No SSH tunneling
FACTORY SERVICE MODE — When Enabled, the device can go into factory service mode. For this setting to become enabled a
Supervisor authentication is necessary. The default value is Disabled.
SUPERVISOR ROLE — When Enabled, the Supervisor role is active. To Disable this setting a Supervisor authentication is
necessary. If disabled, the Supervisor role is not allowed to log in. In this case, the Administrator can change the settings
under the Supervisory menu.
If enabled, Supervisor authentication is required to change the settings in the Supervisory menu. If the Supervisor disables
their role after authentication, the Supervisor session remains valid until they switch to another role using MMI or until they
end the current Supervisor session if using communications.
This role is disabled by default.
SERIAL INACTIVITY TIMEOUT — The role logged via a serial port is auto logged off after the Serial Inactivity timer times out. A
separate timer is maintained for RS232 and RS485 connections. The default value is 1 minute.
Self-tests
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS
SELF TESTS FAILED See below
AUTHENTICATE
FAILED AUTHENTICATE — If this setting is Enabled then the number of failed authentications is compared with the Session
Lockout threshold. When the Session Lockout threshold is exceeded, this minor alarm indication comes up.
FIRMWARE LOCK — If this setting is Enabled, then any firmware upgrade operation attempt when the Lock Relay setting is
5
enabled brings up this self test alarm.
SETTINGS LOCK — If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS FAILED AUTHENTICATE
FAILED FAILED AUTHENTICATE: Range: Enabled, Disabled
AUTHENTICATE Enabled
CyberSentry setup
When first using CyberSentry security, use the following procedure for setup.
1. Log in to the relay as Administrator by using the VALUE keys on the front panel to enter the default password
"ChangeMe1#". Note that the Lock Relay setting needs to be disabled in the Security > Supervisory menu. When this
setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None.
5. Next, Device or Server authentication can be chosen on the login screen, but the choice is available only in EnerVista.
Use Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only Device authentication is supported. When Server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the
EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server at the end of
this instruction manual gives an example of how to set up a simple RADIUS server. Once both the RADIUS server and
the parameters for connecting the UR to the server have been configured, you can choose Server authentication on
the login screen of EnerVista.
The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
NOTICE supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at a time, for both login by front
panel and software.
To configure Server authentication:
1. In the EnerVista software, choose Device authentication and log in as Administrator.
2. Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3. On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4. In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
5. After making any required changes, log out.
When changing settings offline, ensure that only settings permitted by the role that performs the
NOTICE settings download are changed because only those changes are applied.
5 Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the RESET button, which resets targets, where targets are errors
displayed on the front panel or the Targets panel of the EnerVista software. The RESET button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1. Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Syslog format
System logs are produced with the CyberSentry option. The format is as follows.
Security log Event Number Date & Username IP address Role Activity Value
Timestamp
Enumeration Role
0 None
1 Administrator
2 Supervisor
3 Engineer
4 Operator
5 Factory
Enumeration Description
1 Authentication Failed
2 User Lockout
3 FW Upgrade
4 FW Lock
5 Settings Lock
6 Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7 Clear Oscillography command
8 Clear Data Logger command (not applicable to all UR products)
9 Clear Demand Records command (not applicable to all UR products)
10 Clear Energy command (not applicable to all UR products)
11 Clear Unauthorized Access command
12 Clear Teleprotection Counters command (not applicable to all UR products)
13 Clear All Relay Records command
14 Role Log in
15 Role Log off
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE — This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
FLASH MESSAGE TIME — Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT — If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
during programming or reading of actual values.
DEFAULT MESSAGE INTENSITY — To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME — These settings are only visible if the F35 has a liquid crystal display
(LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on.
CURRENT CUT-OFF LEVEL — This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The F35 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the CURRENT CUT-OFF LEVEL setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL — This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The F35
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated using the following equations. For Delta connections:
Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as
valid measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for
NOTE
CURRENT CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
CLEAR ENERGY:
Off
Range: FlexLogic operand 5
RESET UNAUTH ACCESS: Range: FlexLogic operand
Off
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-
programmable pushbuttons to clear specific records is a typical application for these commands. Since the F35 responds
to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-
programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-
programmable pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, apply the following settings.
1. Assign the clear demand function to pushbutton 1 by making the following change in the SETTINGS PRODUCT SETUP
CLEAR RELAY RECORDS menu:
CLEAR DEMAND: “PUSHBUTTON 1 ON”
2. Set the properties for user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCT
SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”
5.3.4 Communications
5.3.4.1 Menu
SETTINGS PRODUCT SETUP COMMUNICATIONS
COMMUNICATIONS SERIAL PORTS See below
RS485 COM2 BAUD RATE: Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
19200 28800, 33600, 38400, 57600, 115200 bit/s
RS232 BAUD RATE, RS485 COM2 BAUD RATE, and PARITY — The F35 is equipped with two independent serial communication
ports. The faceplate RS232 port is intended for local use and has two options for baud rate. The rear COM2 port is RS485
and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software. This software can download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME — This setting specifies the minimum time before the rear RS485 port transmits after
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
5
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Public Network
SCADA
EnerVista Software
LAN1
ML3000
P1
IP1/ P2 P3
MAC1
UR
859708A2.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN2
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP2/
MAC1 MAC2 MAC2
Redundancy mode
UR
859709A4.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN3
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP3/
MAC1 MAC2 MAC3
UR
5
859710A2.vsd
5.3.4.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3)
NETWORK PORT 1 PRT1 IP ADDRESS: Range: standard IPV4 address format
127.0.0.1
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
PRT1 (2 or 3) IP ADDRESS — This setting sets the port’s IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) SUBNET MASK — This setting sets the port’s IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2 REDUNDANCY is set to None.
PRT2 REDUNDANCY — Determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was
purchased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the options are None and
Failover. In non-redundant mode (REDUNDANCY set to None), ports 2 and 3 operate independently with their own MAC, IP,
and mask addresses. If REDUNDANCY is set to Failover, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are hidden
• Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the
Multilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect,
acting as a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the
switch is good and that communication is healthy for five minutes, then switching back to port 2 is performed. The
delay in switching back ensures that rebooted switching devices connected to the F35, which signal their ports as
active prior to being completely functional, have time to completely initialize themselves and become active. Once
port 2 is active again, port 3 returns to standby mode.
If REDUNDANCY is set to PRP, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
5 • Port 2 MCST ADDRESS field is visible
• The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still
synchronizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case
for PRP networks, the port with the better connectivity is used.
The two ports must be connected to completely independent LANs with no single point of failure, such as
common power supplies that feed switches on both LANs.
NOTE
For any changes to this setting to take effect, restart the unit.
PRT2 PRP MCST ADDR — This setting allows the user to change the multicast address used by the PRP supervision frames.
This setting is available if REDUNDANCY is set to PRP. All devices in the same PRP network need to have the same multicast
address. Choose an address that does not conflict with another multicast protocol.
It is strongly recommended to have switches used for substation automation that support the Far-End Fault feature,
especially when UR 7 redundancy Failover is selected for redundancy.
5
PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the duplicated frames. DANP devices have
an additional module, called a Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions on received frames as to which
one is sent up the OSI stack to the application layer and which one is discarded. LRE is responsible for making PRP
transparent to the higher layers of the stack.
In addition, there is a second type of specialized device used in PRP networks, called RedBox, with the role of connecting
Single Attached Nodes (SANs) to a redundant network.
UR relays implement the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy (HSR)
protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 version. The
revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0. The UR relays
support PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Ports 2 and 3 of the CPU module. Use the previous
section (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Ports 2 and 3) operate in redundant mode.
In this mode, Port 3 uses the MAC, IP address, and mask of Port 2.
5.3.4.7 Routing
SETTINGS PRODUCT SETUP COMMUNICATIONS IPv4 ROUTE TABLE 1(6)
IPv4 ROUTE TABLE DEFAULT IPv4 ROUTE
IPv4 NETWORK
ROUTE 1
IPv4 NETWORK
ROUTE 6
Configure the network IP and subnet settings before configuring the routing settings.
The following rules must be observed when you configure static routes:
• The route destination must not be a connected network
• The route gateway must be on a connected network. This rule applies to the gateway address of the default route as
well. This can be verified by checking that:
(RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP
& Prt3Mask)
where
& is the bitwise-AND operator
== is the equality operator
|| is the logical OR operator
Router1
Public network 5
.1
Router2
10.1.2.0/24 10.1.3.0/24
10.1.1.0/24
ML3000 ML3000 .1
EnerVista Software
P1 P2 P3
IP1/ IP2/ IP3/
.2 .2 MAC2 MAC3
MAC1
UR
859714A1.vsd
In the figure, the UR connects through the following two Ethernet ports:
• Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
• Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router2. Router2
has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
The behavior before release 7.10 was as follows. When sending packets to EnerVista, the UR noticed that the destination
was not on a connected network and it tried to find a route to destination. Since the default route was the only route it
knew, it used it. Yet EnerVista was on a private network, which was not reachable through Router1. Hence a destination
unreachable message was received from the router.
The configuration starting with release 7.10 is as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY =
10.1.2.1
The behavior since release 7.10 is as follows. There is one added static network route to the destination 10.1.3.0/24, where
a computer running EnerVista is located. This static route uses a different gateway (10.1.2.1) than the default route. This
gateway is the address of Router2, which has knowledge about 10.1.3.0 and is able to route packets coming from the UR
and destined to EnerVista.
The serial communication ports utilize the Modbus protocol, unless the port is configured for DNP or IEC 60870-5-103
operation. This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave
devices only.
For more information on the protocol, including the memory map table, see the UR Series Communications Guide.
MODBUS SLAVE ADDRESS — When using the Modbus protocol on the RS232 port, the F35 responds regardless of the
MODBUS SLAVE ADDRESS programmed. For the RS485 port, each device on the serial bus must have a unique slave address
from 1 to 254. Address 0 and addresses from 248 and up are reserved by the Modbus protocol specification, and so their
use here is not recommended. Address 0 is the broadcast address that all Modbus slave devices listen to. When MODBUS
SLAVE ADDRESS is set to 0, the F35 accepts broadcast messages, but in compliance with protocol specifications for
broadcast messages, never replies. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors occur. Generally, each device added to the link gets set to use the next higher
address starting at 1. When using Modbus TCP/IP, the client must use the programmed MODBUS SLAVE ADDRESS value in the
Unit Identifier field.
MODBUS TCP PORT NUMBER — Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502
is reserved for Modbus communications, and only in exceptional cases when MODBUS TCP PORT NUMBER is set to any other
port. The MODBUS TCP PORT NUMBER setting sets the TCP port used by Modbus on Ethernet. A MODBUS TCP PORT NUMBER of
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the F35 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000
DNP VOLTAGE SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000
DNP POWER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000
DNP ENERGY SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000
DNP PF SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000
DNP CHANNEL 2 PORT: Range: NONE, COM2 - RS485, FRONT PANEL - RS232,
NONE NETWORK - TCP
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the DNP CHANNEL 1(2) PORT setting is set to “Network - TCP,” the channel 1(2) DNP
protocol can be used over TCP/IP on the Ethernet ports. When this value is set to “Network - UDP,” the DNP protocol can be
used over UDP/IP on channel 1 only.
Changes to these port settings take effect when power has been cycled to the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
The DNP ADDRESS setting is the DNP slave address. This number identifies the F35 on a DNP communications link. Assign a
unique address to each DNP slave.
The F35 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the F35 can connect. The settings follow.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP NETWORK CLIENT ADDRESSES
DNP NETWORK CLIENT ADDRESS 1: Range: standard IP address
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IP address
0.0.0.0
The DNP TCP/UDP PORT NUMBER setting is for normal DNP operation. To close the port, set the port number to 0. The change
takes effect when the F35 is restarted.
The DNP UNSOL RESPONSE FUNCTION is set to “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the F35 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the F35 retransmits an
unsolicited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP
UNSOL RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which
solicited responses are sent is determined by the F35 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the F35 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000,”
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the F35 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
5 ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10 times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the F35 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger
unsolicited responses from the F35 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
is set to “15.” Note that these settings are the deadband default values. DNP object 34 points can be used to change
deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and re-
applied to the F35, the default deadbands are in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the F35.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to
be necessary, which provides more robust data transfer over noisy communication channels.
Check the “DNP Points Lists” F35 web page to view the analog inputs and/or binary inputs points lists. This
page can be viewed with a web browser by entering the IP address of the F35 Ethernet port employed to
NOTE
access the F35 Main Menu, then by clicking the Device Information Menu item, then the DNP Points Lists
item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings select the DNP default variation
number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation
0 is requested and/or in class 0, 1, 2, or 3 scans. See the DNP Implementation section in the UR Series Communications
Guide.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the F35 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The F35 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED
CONTROL POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired
operate on a one-to-one basis.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection is
aborted by the F35. This frees up the connection to be re-used by a client. Any change takes effect after cycling power to
the relay.
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP SECURITY COMMUNICATIONS DNP / IEC104 POINT LISTS BINARY INPUT /
MSP POINTS
BINARY INPUT / MSP Point: 0 Range: FlexLogic operand
POINTS Off
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F35 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP SECURITY COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT
/ MME POINTS
ANALOG INPUT / MME Point: 0 Range: any FlexAnalog parameter
POINTS Off
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F35 is restarted.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are
NOTE
ignored.
The F35 is provided with optional IEC 61850 communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850. The settings are not accessible from the front panel
of the device.
IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same
criticality as protection element settings. To ensure reliable performance of protection schemes utilizing IEC
NOTE
61850 messaging, route IEC 61850 traffic on a separate port from SCADA communications, or use redundant,
independent ports, and a high speed network recovery method, such as PRP.
Overview
IEC 61850 is a series of international standards and technical reports applicable to power utility automation systems. It
5 includes semantics, abstract communication services, specific communication services, performance specifications,
network engineering guidelines, configuration description methodologies, and engineering processes. The standard
enables interoperability among intelligent electronic devices (IEDs) from different suppliers and interoperability among
software configuration tools from different suppliers. Interoperability in this case is the ability for IEDs to operate on the
same network or communication path sharing information and commands, and for configuration tools to understand
each other's configuration files.
The UR series supports a large subset of IEC 61850 features. These are detailed in the UR Series Communications Guide
and include the information model, GOOSE publish, GOOSE subscribe, buffered report server, unbuffered report server, and
Manufacturing Message Specification (MMS) query, read, write, and control services. In addition, the UR and EnerVista UR
Setup software support IEC 61850 Substation Configuration Language (SCL) file import/export.
Whereas prior UR releases used edition 1.0 of IEC 61850, this release uses edition 2.0, with certain modifications according
to IEC/TR 61850-90-5. Only edition 2.0 61850 configuration tools can interoperate with edition 2.0 devices such as the UR
7.3x release. The UR release uses edition 2.0 SCL, which differs from edition 1.0 SCL. GSSE, fixed GOOSE, and fixed report
services of previous releases are no longer supported, and thus UR devices of previous releases using these features have
to be converted to configurable GOOSE to communicate with a 7.3x device.
Many settings of UR protection, control, and monitoring elements, that is to say elements that are not concerned with the
IEC 61850 protocol, can nevertheless be accessed via IEC 61850. These settings are documented elsewhere in this Settings
chapter. This section of the Settings chapter deals solely with the settings that configure the IEC 61850 protocol itself.
Communications Guide for MMS and SCL access. Note that if you update the IEC 61850 settings in the EnerVista software
by writing to them by MMS while the corresponding IEC 61850 panel is open in EnerVista, you need to close then open the
panel in EnerVista for the correct readings to display.
All IEC 61850 protocol configuration settings are accessed through software panels that are selected either in the Online
Window area (see figure) or the Offline Window area in the EnerVista software.
Figure 5-10: IEC 61850 protocol panel in EnerVista software
The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
5
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
setting entry panel contains in the SETTING column the names of the settings, and the settings entry boxes are in the
PARAMETER column. Hovering the mouse over a setting name displays a tool-tip showing the 61850 information model
name of the setting or its location in SCL files.
Figure 5-11: Main IEC 61850 panel
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the
connected F35. This SCD file contains all the settings in the UR at the time of the file request, both those that are mapped
into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model (that is, the "private"
section). The UR Setup software imports all of these settings into the current session, not just those in the IEC 61850
window. To avoid loss of any unsaved setting changes made in other panels during the current session, all other panels for
the F35 must be closed before the IEC 61850 panel can be opened; the software prompts for this when applicable. Panels
for other devices can be open concurrently to facilitate parameter coordination.
The Restore button restores all settings in the IEC 61850 window to their last saved values. The Default button causes all
settings in the IEC 61850 window to revert to factory default values. Both buttons affect the current panel being displayed.
Neither button affects settings in other than the IEC 61860 window.
Server configuration
5 The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting.
IED NAME
Range: 1 to 64 VisibleString characters
Default: TEMPLATE
The value entered sets the IED name used by IEC 61850 for the F35. An IED name unique within the network must be
entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
The first character must be a letter.
Master functional ldName
Range: 0 to 64 VisibileString characters
Default:
The Master logical device contains the UR logical nodes modelling communications and setting group control. Valid
characters are upper and lowercase letters, digits, and the underscore (_) character. If the number of characters entered
is greater than zero, this setting sets the name used in communications for the Master logical device. If an ldName is
entered, a name unique within the network must be entered for proper operation. The standard recommends choosing
this name according to IEC 81346-1. If the number of characters entered is zero, the name used in communications for
the Master logical device is "<iedName>Master", where <iedName> is the value of setting IED NAME described earlier.
Throughout the remainder of this section, <LDName> is a syntactic variable representing the present name of
the master logical device. Depending on its context, <LDName> can be a product-related name or a function-
NOTE
related name. In SCL files, <LDName> is always the product-related name. In IEC 61850 messages, <LDName>
is the function-related name if one is set by the Master functional ldName setting, otherwise <LDName> is
again the product-related name. The product-related name of the Master logical device is
"<iedName>Master". The function related name of the Master logical device is the value of the Master
functional ldName setting.
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to allow the user to declare the geographical position of the device in WGS84 coordinates - altitude.
Prefix for GGIO1
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of the logical node GGIO1 that is described in the GGIO1 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Prefix for GGIO2
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of logical node GGIO2 that is described in the GGIO2 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Prefix for GGIO4
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of logical node GGIO4 that is described in the GGIO4 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Master configRev
Range: 0 to 255 ASCII characters
5 Default:
This data attribute is provided by the protocol to allow the user to declare changes to the semantic of the data model of
the UR. The intent is that the user changes Master configRev each time that the semantic or data model changes, so
that clients can readily detect the change. A semantic change is a logical node getting a new semantic use; for example,
an instance of logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now
used for another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes,
or instance names.
The scope of Maser configRev is the entire relay configuration as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.
paramRev
Range: -2,147,483,648 to 2,147,483,647 in steps of 1
Default: 0
This data attribute is provided by the protocol to make changes to the settings of the F35 apparent to clients. The
Substation Configuration Tool and UR Setup software advance the value of paramRev each time any setting changes.
The F35 increments the value of parmRev when a setting change is made other than through CID file download.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the F35. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
IEC/MMS TCP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 102
This setting allows the user to change the TCP port number for Manufacturing Message Specification (MMS) connections.
It is recommended that this setting be left at the default value.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting specifies the method used to describe GOOSE subscription configuration in SCL. See the UR Series
Communications Guide for details. Basically, in the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode.
GOOSE
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.
Figure 5-12: IEC 61850 TxGOOSE Access Points panel
TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of a set of generic substation event
information in a publishing physical device to more than one subscribing physical device. A TxGOOSE is a UR element
implementing a single IEC 61850 GOOSE message publishing service. The subscribing function in URs is performed by
RxGOOSE elements, as described in the next section. Each UR with IEC 61850 order code options has eight TxGOOSE
elements. Each TxGOOSE element can publish the values of up to 64 FlexLogic or FlexAnalog operands in the UR.
Published TxGOOSE messages configured in the EnerVista UR Setup software can be subscribed by and the published
operand values understood by other UR devices. In fact, they can be subscribed to and understood by any device of any
manufacturer that implements the IEC 61850 edition 1.0 or 2.0 GOOSE subscription mechanism. The messages are
published with a multicast address so that the network sends the messages to all devices; any number of devices that
want to subscribe can.
The entities whose values are published in GOOSE messages are known as members. The members are itemized in an
ordered list known as a data set. Each TxGOOSE can use any one of the data sets provided. See the DataSets section later
for details.
Each enabled TxGOOSE transmits its message whenever a value change is detected in one or more of its members. To
guard against the possibility that such a message is lost in the network before it reaches all subscribers, the message is
quickly retransmitted several times. To allow subscribers to verify that their link to the publisher and the publisher itself are
healthy, each message is also periodically retransmitted even while the values are unchanging. These latter messages are
known as heartbeat messages, while the former are known as event messages. Heartbeat messages also provide means
for a subscriber newly online to receive the published values in the absence of an event.
TxGOOSE1 and TxGOOSE2 scan for value changes in its FlexLogic operand members as frequently as such a change can
occur. TxGOOSE1 and TxGOOSE2 are therefore suitable for highly time critical signals, such as tripping and dynamic
blocking. FlexAnalog members are scanned for value changes only every 250 ms. See the Deadband Settings section later
for a description of what is considered a value change in an analog member.
The remaining TxGOOSE, meaning TxGOOSE3 and up, scan both their FlexLogic and FlexAnalog members for value
changes every 250 ms. They are suited for control applications, such as voltage control or power factor regulation.
The details of TxGOOSE message construction are contained in the UR Series Communications Guide. Knowledge of these
details is not required to configure GOOSE.
The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause
A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850-8-1:2004
and as optional in IEC 61850-8-1:2011 clause A.3. So do not try to configure the UR for fixed-offset TxGOOSE.
TxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > Access Points to access
the settings that are common to all GOOSE messages published.
The following settings are available.
PORT1 GOOSE ENABLE
5 Range: Enabled, Disabled
Default: Enabled
When set to Disabled, no GOOSE messages are published on F35 Ethernet port 1, and any GOOSE messages received on
port 1 are ignored. When set to Enabled, all enabled GOOSE messages are published on F35 Ethernet port 1, and any
GOOSE messages received on port 1 are listened to.
F35 Ethernet ports 2 and 3 each have a similar setting.
TxGOOSE UPDATE TIME
Range: 1 to 60 s in steps of 1 s
Default: 60 s
This setting specifies the time interval between heartbeat messages, which are messages that are sent periodically
while no events are detected. The standard suggests that the heartbeat time be less than (actually half) of the
timeAllowedtoLive parameter, which is set by the TxGOOSE TIME TO LIVE settings described later.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the
settings for the first TxGOOSE. The settings and functionality for the others are similar.
TxGOOSE1 FUNCTION
Range: Enabled, Disabled
Default: Enabled
When set to Disabled, TxGOOSE1 messages are not published. When set to Enabled, TxGOOSE1 messages are published.
When TxGOOSE1 to 8 are set to Disabled in EnerVista and subsequently Enabled by writing via MMS, the panel continues
to read Disabled until relaunched. There is no polling capability to update automatically the IEC 61860 readings, so the
panel needs to be closed then opened for the correct status to display.
TxGOOSE1 GoID 5
Range: 0 to 129 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate
the TxGOOSE1 messages from other GOOSE messages.
TxGOOSE1 DatSet
Range: None, DataSet01, DataSet02,...
Default: None
This setting selects the published data set using the UR Setup software designator for the data set. The IEC 61850 name
of the data sets are configured in the Datasets panel, as described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0." and the data
set name, is published in the datSet field of TxGOOSE1 messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages.
TxGOOSE1 DST MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
The value entered sets the Ethernet destination Media Access Control (MAC) address in published TxGOOSE1 messages.
As the standard requires that the address have the multicast bit set TRUE, that is to say the second digit is set to an odd
number, messages transmitted have the multicast bit set TRUE no matter its value in this setting.
The destination MAC address can be used by the network to restrict message delivery to selected devices that need to
receive them, reducing network loading. This address also can be used by hardware in receiving devices to filter out
messages that are of no interest to them, reducing processor burden. Different filtering algorithms are implemented by
different devices. The standard recommends that the algorithm used by hardware of the receiving device be considered
when assigning destination multicast addresses.
Subscribers can use this address to discriminate TxGOOSE1 messages from other GOOSE messages.
Base this setting on the TxGOOSE UPDATE TIME and the tolerable number of contiguous message delivery misses. For
example, if the heartbeat time is 10 s, and missing up to three successive messages is tolerable, make the setting 10*3 +
1 = 31 s. The extra second is to ensure that arrival of the third heartbeat transmission beats the timeAllowedtoLive timer.
The standard suggests that the heartbeat time be less than (actually half) of the timeAllowedtoLive parameter.
RxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages.
IEC 61850, GOOSE is an efficient method for simultaneous high-speed delivery of the same generic substation event
information in a publishing physical device to more than one subscribing physical device. An RxGOOSE is a UR element
implementing a single IEC 61850 GOOSE message subscribing service. The publishing function in URs is performed by
TxGOOSE elements, as described in the previous section. Each F35 has 16 RxGOOSE elements. Each RxGOOSE element can
subscribe to GOOSE messages from a specified publisher. Subscribed messages can contain up to 64 of any set of data
attributes with basic types BOOLEAN, FLOAT32, INT32, Dbpos, TimeStamp, or Quality. Messages containing data objects,
that is to say structured data, are not accepted.
With these conditions, GOOSE messages from any device of any manufacturer that implements the IEC 61850 edition 1.0
or 2.0 GOOSE publish service can be subscribed to. The UR accepts both the variable-length encoded GOOSE messages
specified in IEC 61850-8-1:2004 and the Fixed-Length encoded GOOSE messages as specified in IEC 61850-8-1:2011
clause A.3.
Each enabled RxGOOSE monitors for interruption of the GOOSE messages that it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example, RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. RxGOOSE connectivity of an RxGOOSE with non-zero MAC address is also considered
lost after the F35 finishes restart until a message is received. When RxGOOSE connectivity is lost, a common RxGOOSE Fail
self-test activates. 5
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. Messages that
contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the simulation field
(test field in edition 1.0 messages) are accepted only when the UR test mode is Forcible; see the Testing section at the end
of this chapter for details. The settings and functionality for the other RxGOOSE are similar.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1. The following settings are available.
Figure 5-14: IEC 61850 RxGOOSE Messages panel
RxGOOSE1 ID
Range: 0 to 129 VisibleString characters
Default:
If the value entered has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 00-00-00-00-00-00
Set this setting to the MAC address of the publisher. Only received GOOSE messages having a Media Access Control
(MAC) address equal to this value are accepted as valid RxGOOSE1 messages. An entered address of zero disables
RxGOOSE1.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE Dst MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPID
setting.
5 RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
Default:
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if any of the logical device containing the publishing control block,
otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing control
block.
The F35 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x series device, <LDName> is the value of the publisher's Master functional ldName setting if
that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the publisher is a
UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for example
"GoCB01".
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default:
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, Dbpos, FLOAT32, INT32, Quality, TimeStamp
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the members that the UR is able to
subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the last
member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x series device, set these settings to match the basic type of the members of the publisher's
data set selected by the publisher's TxGOOSE datSet setting.
RxGOOSE inputs
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean member received by a specified RxGOOSE to a
FlexLogic operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) member to four
FlexLogic operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a
specified FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the
RxGOOSE connectivity is lost. INT32, Quality, and TimeStamp members cannot be converted to operands, and thus
5
although they can be accepted in GOOSE messages, they have no effect on the UR.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible via UR Setup software. See the UR Communications Guide for more information on
GGIO3.
RxGOOSE Boolean1 ID
Range: 0 to 12 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". This descriptive text also appears in the SCL files
associated with the UR.
5 RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member that is not a BOOLEAN results in the RxGOOSE
Boolean1 FlexLogic operand assuming its default state.
RxGOOSE Boolean1 DEFAULT STATE
Range: On, Off, Latest/On, Latest/Off
Default: On
This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and
the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the
publisher. The following choices are available:
– "On" value defaults the input to logic 1
– "Off" value defaults the input to logic 0
– "Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
– "Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
RxGOOSE DPS1 ID
Range: 0 to 12 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Intermediate," "On," "Off," or "Bad." This descriptive text
also appears in the SCL files associated with the F35.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None,
the RxGOOSE DPS1 FlexLogic operand assumes its default state.
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state.
RxGOOSE Analog1 ID
Range: 0 to 12 characters
Default: RxG Analog1
This setting allows the user to assign descriptive text to RxGOOSE Analog1. This descriptive text also appears in the SCL
files associated with the F35. Unlike RxGOOSE Booleans and RxGOOSE DPS, the RxGOOSE Analog operands have fixed
names, for example RxGOOSE Analog1.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and a
PU base of 0.001 is 1.
When using RxGOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexElement
actual values is 2,140,000.000.
Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.
Figure 5-18: IEC 61850 buffered report panel
5 An IEC 61850 Report server is an efficient method for delivery of generic substation event information in a single server to
a single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-9: Number of report elements
Number
Buffered reports 20
Unbuffered reports 14
Configurable Reports interoperate with any client device of any manufacturer that conforms to the IEC 61850 edition 1.0
or 2.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided that no more than
four data sets are used for reports. This restriction is to limit the amount of processing power that can be allocated to
reporting.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
read and acknowledged by the client to be retransmitted.
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the F35 a CID file. See the UR Series Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
5 RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/LLN0$RP$"URCB01".
Unbuffered Report1 DatSet
Range: None, DataSet01, DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Unbuffered
Report1 messages from other messages.
Unbuffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the confRev value in Unbuffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRef be incremented each time the members or the order of the members is changed, and each time the data
set name is changed.
Unbuffered Report1 OptFlds
Range: The check box for an individual bit can be enabled or not
Default: All bits true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The options are
as follows:
– sequence-number
– report-time-stamp
– reason-for-inclusion
– data-set-name
– data-reference
– conf-revision
Notice that OptFlds bits buffer-overflow and entryID are not applicable to unbuffered reports even though the bits exist
in the protocol. They are therefore labelled N/A (not applicable) on the display.
Unbuffered Report1 BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the time interval in milliseconds for the buffering of events for inclusion into a single report.
Unbuffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows:
– data-change
– quality-change
– integrity
– general interrogation
Unbuffered Report1 IntgPd
Range: 0 to 4294967295 in steps of 1.
Default: 0
The entered value sets the period in milliseconds for generating Unbuffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.
DataSets 5
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As mentioned in the preceding GOOSE and Reports sections, the members whose values are communicated by these
services are itemized in an ordered list known as a data set. Each UR with the IEC 61850 option has 12 data sets. Each data
set can contain as many as 64 members. Any data set can be used simultaneously by any number of TxGOOSE elements
and/or by any number of Configurable Report elements. UR Setup software can configure any FlexLogic operands and any
FlexAnalog operands as members.
Figure 5-20: IEC 61850 DataSets
UR Setup requires data set members to be IEC 61850 data attributes. Certain FlexLogic and FlexAnalog operands have
factory assigned data attributes as tabulated in the UR Series Communications Guide. All FlexLogic and FlexAnalog
operands can be user-assigned to GGIO1 or GGIO4 data attributes, so that operands without factory assigned data
attributes can still have their values published. See the GGIO1 and GGIO4 sections later for details.
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets > DataSet01 to access the settings for
the first data set. The settings and functionality for the others are similar.
DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. An
ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the DataSet01
name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages, and it can
be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An ObjectReference
to the data set is optionally published in the DatSet field of Report messages. Valid characters are upper and lowercase
letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Deadband settings
The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: System Setup > Signal
Sources, FlexLogic, Grouped Elements, Control Elements, and GGIO4. Each panel is not outlined here.
Deadband setting names all end either with "DEADBAND" or .db. As they all work the same way, but each on a different
analog value, a single description applicable to all deadband settings is given here. The analog value that each deadband
setting applies to is usually obvious from the name of the setting. However, a tabulation of the analog values and their
5 associated deadband setting can be found in the UR Series Communications Guide.
Figure 5-21: Deadband settings with .db suffix
GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Deadband settings are entered in UR Setup in units of percent of the difference between the "max." and "min." of the
associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings is
0.000 to 100.000% in steps of 0.001. The default value is 10.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
• Phase current — 46 x phase CT primary setting
• Neutral current — 46 x ground CT primary setting
• Phase and phase-to-phase voltage — 275 x VT ratio setting
• Power (real, reactive, apparent, 3-phase, and 1-phase) — 46 x phase CT primary setting x 275 x VT ratio setting
• Energy (real or imaginary) — 46 x phase CT primary setting x 275 x VT ratio setting x 1 hour
• Frequency — 90 Hz 5
• Frequency rate of change — 90 Hz/s
• Power factor — 2
• Angle — 360 degrees
Select the deadband settings from knowledge of the characteristics of the power system quantity measured and
knowledge of the demands of the applications receiving the measurement via GOOSE or report such that changes of
significance to the application are promptly reported, yet the network is not overly burdened with event messages.
Breaker 1
The UR breaker control and status monitoring elements have certain settings that configure how the IEC 61850 protocol
interacts with these elements. These settings are described in this section. See the Breakers section in the System Setup
section of this chapter for details on the operation of breaker control elements.
Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that
configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and
functionality for the others are similar.
Switch 1
The UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850
protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >
Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.
Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to access
the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring
element. The settings and functionality for the others are similar.
Figure 5-24: Switches panel
Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.
Figure 5-25: Setting Groups panel
Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Commands to access the settings that configure
the IEC 61850 protocol interface for record clear commands.
Figure 5-26: Commands panel
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the F35 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.
DatLogRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.
EnrMtrMMTR.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ENERGY.
GGIO1
GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information model
data attributes.
For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
GGIO1 also provides a chatter suppression service. Oscillation in a value, also known as chatter, can be caused by errors in
logic programming, inadequate hysteresis (deadband) on a threshold, or a failed station component. Chatter can flood a
5 communications network with GOOSE messages, degrading response time for all users. If chatter is detected in a GGIO1
data attribute, TxGOOSE suspends GOOSE event message triggering from that data attribute for as long as the condition
exists, and for a minimum period of one second. While sending is suspended, a self-test message identifying the specific
data item detected as oscillating is activated.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1.
Figure 5-27: IEC 61850 GGIO1 panel
GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.
GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
Figure 5-28: GGIO2 panel
GGIO4
GGIO4 is a UR feature that allows any of up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information
model data attribute.
For the value of a FlexAnalog operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO4 allows those FlexAnalog operands that have not
yet been factory assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the
settings for the first GGIO4 value. The settings and functionality for the others are similar.
Figure 5-29: GGIO4 panel
ANALOG IN 1 VALUE
Range: any FlexAnalog operand
Default: OFF
This setting selects the FlexAnalog operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO4.AnIn01.instMag.f. The value of the FlexAnalog operand is converted automatically to the format and
scaling required by the standard, that is to say primary amperes, primary volts, and so on. See Appendix A for a list of
FlexAnalog operands.
ANALOG IN 1 DB
Range: 0.000 to 100.000% in steps of 0.001
Default: 10.000%
This setting specifies the deadband for the ANALOG IN 1 VALUE. The deadband is used to determine when to update the
deadbanded magnitude from the instantaneous magnitude. The deadband is a percentage of the difference between
the "max." and "min." values. Here, the "max." and "min." are as specified by the settings ANALOG IN 1 MAX and ANALOG IN
1 MIN.
See the Deadband Settings section earlier for a description of deadbanded values.
ANALOG IN 1 MIN
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 1000.000
This setting specifies the "min." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
ANALOG IN 1 MAX
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
This setting specifies the "max." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
The F35 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the F35 “Main Menu.” Web pages are available showing DNP and IEC
60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the F35 and a computer to
an Ethernet network, then enter the IP address of the F35 Ethernet port in a web browser.
To close the port, set the port number to 0. The change takes effect when the F35 is restarted.
Figure 5-30: Example of UR web page showing event records
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F35 over a network. The F35 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained
from the F35 contains a list and description of all available files (event records, oscillography, and so on).
While TFTP is supported, the put function is not for security reasons. For example, you can enter a "get" command but not
a "put" command.
TFTP MAIN UDP PORT NUMBER — To close the port, set the port number to 0. The change takes effect when the F35 is
restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
IEC 60870-5-104 is a transmission protocol for network access, specifically for communication between a control station
and substation over a TCP/IP network.
The F35 supports the IEC 60870-5-104 protocol. This protocol is enabled when the SETTINGS PRODUCT SETUP
COMMUNICATIONS PROTOCOL setting is set to IEC 60870-5-104. The F35 can be used as an IEC 60870-5-104 slave device
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F35 maintains two
sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the F35 at one
time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the F35 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the F35 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD
setting is set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured
value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the F35, the default thresholds are in effect.
The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
IEC TCP PORT NUMBER — To close the port, set the port number to 0. The change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL IEC NETWORK CLIENT
ADDRESSES
IEC NETWORK CLIENT ADDRESS 1: Range: standard IPV4 address format
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IPV4 address format
0.0.0.0
The F35 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the F35 can connect. A maximum of two simultaneous connections are supported at any given time.
The F35 is provided with optional Ethernet Global Data (EGD) communications capability. This feature is
specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for
details.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD data
exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
The relay supports one fast EGD exchange and two slow EGD exchanges. There are 20 data items in the fast-produced
EGD exchange and 50 data items in each slow-produced exchange.
EGD cannot be used to transfer data between UR series relays. The relay supports EGD production only. An EGD exchange
is not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid
Modbus register address. The default setting value of “0” is considered invalid.
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The F35 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the fast EGD exchange follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL FAST PROD EXCH 1 CONFIGURATION
FAST PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable
CONFIGURATION Disable
Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are as follows.
EXCH 1 DESTINATION — This setting specifies the destination IP address of the produced EGD exchange. This is usually
unicast or broadcast.
EXCH 1 DATA RATE — This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms, the
exchange data is updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data is updated and sent
once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a setting range of 500 to
1000 ms.
EXCH 1 DATA ITEM 1 to 20/50 — These settings specify the data items that are part of this EGD exchange. Almost any data
from the F35 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus
register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications
Guide for details. The Modbus memory map display shows addresses in hexadecimal format. Convert these hex values to
decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values), only the
first Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus addresses
and the fourth is 0, the produced EGD exchange contains three data items.
The F35 is provided with optional IEC 60870-5-103 communications capability. This feature is specified as
a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
IEC 60870-5-103 is a companion standard to the IEC 60870-5 suite of standards for transmission protocols. It defines
messages and procedures for interoperability between protection equipment and devices of a control system in a
substation for communicating on a serial line.
The IEC 60870-5-103 protocol is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL setting
is set to IEC 60870-5-103.
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication, exchanging
5
information with a control system. In the context of this protocol, the protection equipment is the slave and the control
system is the master. The communication is based on a point-to-point principle. The master must be able to interpret the
IEC 60870-5-103 communication messages.
The UR implementation of IEC 60870-5-103 consists of the following functions:
• Report binary inputs
• Report analog values (measurands)
• Commands
• Time synchronization
The RS485 port supports IEC 60870-5-103.
The UR Series Communications Guide contains more information on the protocol.
IEC103 COMMON ADDRESS OF ASDU — This setting uniquely defines this F35 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is
recommended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range
of 254 addresses is never exhausted.
IEC103 SYNC TIMEOUT — This setting defines the time that the F35 waits for a synchronization message. The F35
synchronizes its clock using all available sources, with the source synching more frequently overwriting the time of the
other sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B,
PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs
and none of IRIG-B, PTP, or SNTP is active, the F35 sets the invalid bit in the time stamp of a time-tagged message.
The settings for the remaining menus are outlined as follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-103 IEC103 INPUTS BINARY
IEC103 INPUTS POINT 0 See below
BINARY
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
5 inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the F35 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
ASDU 4 ANALOG 1
Off
Range: FlexAnalog parameter 5
ASDU 4 ANALOG 1 Range: 0.000 to 65.535 in steps of 0.001
FACTOR: 1.000
ANALOG # — This field contains the actual measurand to be sent in the response to the master. The measurands can be
mapped using elements from a list of FlexAnalog operands. The measurands sent are voltage, current, power, power
factor, and frequency. If any other FlexAnalog is chosen, the F35 sends 0 instead of its value. Note that the power is
transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I,
respectively measurands II).
Each IEC 60870-5-103 measurands list ends at the first unconfigured ("Off") value. Any measurand assigned after the first
"Off" value is ignored.
At least one measurand per ASDU must be configured in order to configure the following ASDU. For example, the user can
configure only one measurand for each ASDU, but the user is not allowed to skip ASDU 2 and configure measurands in
ASDU 3.
ANALOG # FACTOR and OFFSET — For each measurand included in the ASDU, a factor and offset also can be configured. The
factor and offset allow for scaling to be performed on measurands. The final measurement sent to the IEC 60870-103
master is then "a*x + b," where x is the measurand, a is the multiplying factor and b is the offset. The master has to perform
the reversed operation in order to retrieve the actual value if such scaling is done. By default a = 1 and b = 0, so no scaling
is done if these values are left at their defaults. Examples of when scaling is appropriate are as follows:
• If the measured value contains decimals and it is important to preserve the resolution. Since the format for
transmitting the measurand does not permit decimals, a factor a>1 can be applied before transmission. For example,
a frequency F=59.9Hz can be transmitted as Ft = 10 * F = 10 * 59.9 = 599. In this case a = 10, b = 0. The master receives
599 and has to divide by 10 to retrieve the real value 59.9.
• If the measured value is larger than what fits in the format defined in IEC 103. The format defined in the standard
allows for signed integers up to 4095. By offsetting, unsigned integers up to 4096 + 4095 = 8191 are supported.
Scaling using factors <1 can be required in such cases. The calculation is outlined in the IEC 60870-5-103 chapter of
the UR Series Communications Guide. Two examples follow, where you decide factors a and b.
COMMAND 1
COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the F35. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-10: Commands mapping table
Description Value
Off 0
Virtual Input 1 1
Virtual Input 2 2
... ...
Virtual Input 64 64
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the ADDRESS line (converted from hex to decimal format). The corresponding value displays in the VALUE line. A value of
“0” in subsequent register ADDRESS lines automatically returns values for the previous ADDRESS lines incremented by “1.”
An address value of “0” in the initial register means “none” and values of “0” display for all registers. Different ADDRESS
values can be entered as required in any of the register positions.
The UR Series Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser; enter
the IP address of the F35 in the web browser and click the option.
5.3.6.1 Menu
SETTINGS PRODUCT SETUP REAL TIME CLOCK
REAL TIME SYNCRONIZING SOURCE: Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
CLOCK None SNTP, PP/PTP/IRIG-B/SNTP
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
time delivered to the relay.
The SYNCHRONIZING SOURCE setting configures the priority sequence of the time synchronization source, to determine
which of the available external time sources to use for time synchronization. A setting of None causes the RTC and the
synchrophasor clock to free-run. A setting of PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/SNTP, or PP/PTP/IRIG-B/SNTP causes the
relay to track the first source named that is enabled and operational, or free-run if none of these are available. Here, PP
means a time source that is strictly compliant with PP, and PTP means a time source that is not strictly compliant with PP.
When a time source fails or recovers, the relay automatically transfers synchronization as required by this setting.
Setup for IRIG-B is illustrated in the Installation chapter.
The clock is updated by all sources active in the device. This means that whenever a time synchronization message is
received through any of the active protocols, the F35 clock updates. However, given that IEC 60870-5-103, IEC 60870-5-
104, Modbus, and DNP are low-accuracy time synchronization methods, avoid their use for synchronization when better
accuracy time protocols, such as IRIG-B, PTP, and SNTP, are active in the system.
See the COMMANDS SET DATE AND TIME menu section of this manual to manually set the RTC.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment.
To enable IRIG-B synchronization, the input IRIG-B SIGNAL TYPE must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use the
following sections.
SETTINGS PRODUCT SETUP REAL TIME CLOCK PRECISION TIME PROTOCOL (1588) PTP PORT 1(3)
PTP PORT 1 PORT 1 PTP FUNCTION: Range: Enabled, Disabled
Disabled
The F35 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in
IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network
that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include 1) missing declaration of PP compliance in the
messages, 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially
greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates.
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes referred to as
version 2 PTP. It does not support the previous version of the standard (version 1).
PTP is a protocol that allows multiple clocks in a network to synchronize with one another. It permits synchronization
accuracies better than 1 ns, but this requires that each and every component in the network achieve very high levels of
accuracy and a very high baud rate, faster than normally used for relay communications. When operating over a generic
Ethernet network, time error can amount to 1 ms or more. PP is a profile of PTP which specifies a limited subset of PTP
suitable for use in power system protection, control, automation, and data communication applications, and thereby
facilitates interoperability between different vendor’s clocks and switches. PP specifies a worst-case delivered time error of
less than 1 µs over a 16-hop network.
In a PTP system and in a PP system, the clocks automatically organize themselves into a master-slave synchronization
hierarchy with the “best” clock available making itself the "grandmaster" at the top of the hierarchy; all others make
themselves “slaves” and track the grandmaster. Typically the grandmaster clock receives its time from GPS satellites or
some other link to the international time standard. If the grandmaster fails, the next “best” clock available in the domain
assumes the grandmaster role. When a clock on start-up discovers that it is “better” than the present grandmaster, it
assumes the grandmaster role and the previous grandmaster reverts to slave.
Time messages issued by the grandmaster are delayed as they pass through the network both due to the finite speed of
the signal in the interconnecting fiber or wire, and due to processing delays in the Ethernet switches. Each clock and switch
implementing PP measures the propagation delay to each of its PP neighbors, and compensates for these delays in the
time received. Each network device implementing PP measures the processing delay it introduces in each time message
and compensates for this delay in the time it transmits. As a result, the time delivered to end-devices such as the UR are
virtually identical to the grandmaster time. If one of the network devices in the hierarchy does not fully implement PP, the
associated propagation delay and/or latency may not be compensated for, and the time received at the end-device can be
in error by more than 100 µs.
See the preceding Real Time Clock section for a description of when time values received via PTP are used to update the
relay’s real time clock.
The following settings are available for configuring the relay for PTP. The PTP menu displays only when the option was
purchased.
STRICT POWER PROFILE — Power profile (IEEE Std C37.238 2011) requires that the relay only select a power profile compliant
clock as a grandmaster, that the delivered time have worst-case error of ±1 µs, and that the peer delay mechanism be
implemented. With the strict power profile setting enabled, the relay only selects as master the clocks displaying the
IEEE_C37_238 identification codes. It uses a port only when the peer delay mechanism is operational. With the strict power
profile setting disabled, the relay uses clocks without the power profile identification when no power profile clocks are
present, and uses ports even if the peer delay mechanism is non-operational. This setting applies to all of the relay’s PTP
capable ports.
PTP DOMAIN NUMBER — Set this setting to the domain number of the grandmaster-capable clock(s) to be synchronized to. A
network can support multiple time distribution domains, each distinguished with a unique domain number. More
commonly, there is a single domain using the default domain number zero.
This setting applies to all of the relay’s PTP capable ports.
5 PTP VLAN PRIORITY — This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued
by the relay’s peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that it be
set to 7 in accordance with PTP. Depending on the characteristics of the device to which the relay is linked directly, VLAN
Priority can have no effect.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN ID — This setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. It is provided in compliance with PP. As these messages have a destination address that indicates
they are not to be bridged, their VLAN ID serves no function, and so can be left at its default value. Depending on the
characteristics of the device to which the relay is linked directly, VLAN ID can have no effect. This setting applies to all of
the relay’s PTP capable ports.
PORT 1 ... 3 FUNCTION — While this port setting is selected to disabled, PTP is disabled on this port. The relay does not
generate or listen to PTP messages on this port.
PORT 1 ... 3 PATH DELAY ADDER — The time delivered by PTP is advanced by the time value in this setting prior to the time
being used to synchronize the relay’s real time clock. This is to compensate to the extent practical for time delivery delays
not compensated for in the network. In a fully compliant PP network, the peer delay and the processing delay mechanisms
compensate for all the delays between the grandmaster and the relay. In such networks, make this setting zero.
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay is later than the time indicated in the message. This
setting can be used to approximately compensate for this delay. However, as the relay is not aware of network switching
that dynamically changes the amount of uncompensated delay, there is no setting that always and completely corrects
for uncompensated delay. A setting can be chosen that reduces the worst-case error to half of the range between
minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASSYMMETRY — This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two directions of a link. Except in
unusual cases, the two fibers are of essentially identical length and composition, so make this setting zero.
In unusual cases where the length of the link is different in different directions, set this setting to the number of
nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and from
the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the fibers that
the delay from the relay to the Ethernet switch it is connected to is 9000 ns and that the delay from the switch to the relay
is 11000 ns, then the mean delay is 10000 ns, and the path delay asymmetry is 11000 - 10000 = +1000 ns.
The F35 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the F35 can obtain clock time over
an Ethernet network. The F35 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated
product using a GPS receiver. Unicast SNTP is supported. The UR series relays do not support the broadcast, multicast, or
anycast SNTP functionality.
The SNTP FUNCTION setting enables or disables the SNTP feature on the F35.
To use SNTP, set SNTP SERVER IP ADDR to the SNTP/NTP server IP address. Once this address is set and SNTP FUNCTION is
“Enabled,” the F35 attempts to obtain time values from the SNTP/NTP server. Since many time values are obtained and
averaged, it generally takes three to four minutes until the F35 clock is closely synchronized with the SNTP/NTP server. It
takes up to two minutes for the F35 to signal an SNTP self-test error if the server is offline.
The SNTP UDP PORT NUMBER is 123 for normal SNTP operation. If SNTP is not required, close the port by setting the port
5
number to 0, after which the change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
DST START DAY: Range: Sunday to Saturday (all days of the week)
Sunday
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
Sunday
The F35 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and timestamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
LOCAL TIME OFFSET FROM UTC — Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time. When a communications protocol other
than PTP provides UTC to local time offset (meaning IRIG-B), that offset is used instead of the local time and daylight time
settings.
DAYLIGHT SAVINGS TIME and DST — Can be used to allow the relay to follow the DST rules of the local time zone. Note that
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.
The F35 relay supports one fault report and an associated fault locator per CT bank to a maximum of 5. The signal source
and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
• Fault report number
• Name of the relay, programmed by the user
• Firmware revision of the relay
• Date and time of trigger
• Name of trigger (specific operand)
• Line or feeder ID via the name of a configured signal source
• Active setting group at the time of trigger
• Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report
source or the trigger operate). Once a disturbance is detected, pre-fault phasors hold for three seconds waiting for the
fault report trigger. If trigger does not occur within this time, the values are cleared to prepare for the next disturbance.
• Fault current and voltage phasors (one cycle after the trigger)
• Elements operated at the time of triggering
• Events — Nine before trigger and seven after trigger (only available via the relay web page)
• Fault duration times for each breaker (created by the breaker arcing current feature)
The captured data also includes the fault type and the distance to the fault location, as well as the reclose shot number
(when applicable). To include fault duration times in the fault report, enable and configure the breaker arcing current
feature for each of the breakers. Fault duration is reported on a per-phase basis.
The relay allows locating faults, including ground faults, from delta-connected VTs. In this case, the missing zero-sequence
voltage is substituted either by the externally provided neutral voltage (broken delta VT) connected to the auxiliary voltage
channel of a VT bank, or by the zero-sequence voltage approximated as a voltage drop developed by the zero-sequence
current, and user-provided zero-sequence equivalent impedance of the system behind the relay. 5
The trigger can be any FlexLogic operand, but in most applications it is expected to be the same operand, usually a virtual
output, that is used to drive an output relay to trip a breaker. To prevent the overwriting of fault events, do not use the
disturbance detector to trigger a fault report. A FAULT RPT TRIG event is automatically created when the report is triggered.
If a number of protection elements are ORed to create a fault report trigger, the first operation of any element causing the
OR gate output to become high triggers a fault report. However, If other elements operate during the fault and the first
operated element has not been reset (the OR gate output is still high), the fault report is not triggered again. Considering
the reset time of protection elements, there is very little chance that a fault report can be triggered twice in this manner. As
the fault report must capture a usable amount of pre and post-fault data, it cannot be triggered faster than every 20 ms.
Each fault report is stored as a file; the relay capacity is 15 files. A 16th trigger overwrites the oldest file.
Individual fault report features store their files in the same memory space. The sixteenth report overwrites the first one
regardless of which fault report feature produced the sixteenth and the first records.
The EnerVista software is required to view all captured data. The relay faceplate display can be used to view the date and
time of trigger, the fault type, the distance location of the fault, and the reclose shot number.
The FAULT REPORT 1 SOURCE setting selects the source for input currents and voltages and disturbance detection.
The FAULT 1 REPORT TRIG setting assigns the FlexLogic operand representing the protection element/elements requiring
operational fault location calculations. The distance to fault calculations are initiated by this signal. The FAULT REPORT 1 Z1
MAG and FAULT REPORT 1 Z0 MAG impedances are entered in secondary ohms.
The FAULT REPORT 1 VT SUBSTITUTION setting is set to “None” if the relay is fed from wye-connected VTs. If delta-connected
VTs are used, and the relay is supplied with the neutral (3V0) voltage, this setting is set to “V0”. The method is still exact, as
the fault locator combines the line-to-line voltage measurements with the neutral voltage measurement to re-create the
line-to-ground voltages. See the ACTUAL VALUES RECORDS FAULT REPORTS menu for details. It is required to configure
the delta and neutral voltages under the source indicated as input for the fault report. Also, the relay checks if the auxiliary
signal configured is marked as “Vn” by the user (under VT setup) and inhibits the fault location if the auxiliary signal is
labeled differently.
If the broken-delta neutral voltage is not available to the relay, an approximation is possible by assuming the missing zero-
sequence voltage to be an inverted voltage drop produced by the zero-sequence current and the user-specified
equivalent zero-sequence system impedance behind the relay: V0 = –Z0 I0. In order to enable this mode of operation, the
FAULT REPORT 1 VT SUBSTITUTION setting is set to “I0”.
The FAULT REP 1 SYSTEM Z0 MAG and FAULT REP 1 SYSTEM Z0 ANGLE settings are used only when the VT SUBSTITUTION setting
value is “I0”. The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent behind
the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault.
If the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-
ground faults is trusted accordingly. Keep in mind that grounding points in the vicinity of the installation impact the system
zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, and so on).
5.3.8 Oscillography
5.3.8.1 Menu
SETTINGS PRODUCT SETUP OSCILLOGRAPHY
OSCILLOGRAPHY NUMBER OF RECORDS: Range: 1 to 64 in steps of 1
5
5 TRIGGER SOURCE:
Off
Range: FlexLogic operand
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records can be captured
simultaneously.
When EnerVista UR Setup creates a new settings file, a Smart defaults feature automatically enters a basic oscillography
configuration. The basic configuration changes the factory default values to make the number of samples per cycle 32,
adds a selection of digital and analog channels that are often of interest, and adds a FlexLogic equation to trigger
oscillography. Review and update this basic configuration as required for the application at hand.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors, such as sample rate and the number of operational modules. There is a fixed amount of data storage for
oscillography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES
RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sample
configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
TRIGGER MODE — A new record automatically overwrites an older record when TRIGGER MODE is set to “Automatic
Overwrite.”
TRIGGER POSITION — Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
position of 25% consists of 25% pre- and 75% post-trigger data.
TRIGGER SOURCE — Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS — Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
5
When changes are made to the oscillography settings, all existing oscillography records are cleared.
NOTE
DIGITAL 1(63) CHANNEL — This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay depend on
• the type of relay,
DATA LOGGER CONFIG: Range: Not applicable - shows computed data only
0 CHNL x 0.0 DAYS
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data can
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, so the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. The
following table outlines examples of storage capacities for a system frequency of 60 Hz.
Changing any setting affecting data logger operation clears data in the log.
NOTE
DATA LOGGER MODE — This setting configures the mode in which the data logger operates. When set to “Continuous,” the 5
data logger actively records any configured channels at the rate as defined by the DATA LOGGER RATE. The data logger is
idle in this mode when no channels are configured. When set to “Trigger,” the data logger records any configured channels
at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic operand. The data logger ignores all
subsequent triggers and continues to record data until the active record is full. Once the data logger is full, a CLEAR DATA
LOGGER command is required to clear the data logger record before a new record can be started. Performing the CLEAR
DATA LOGGER command also stops the current record and resets the data logger to be ready for the next trigger.
DATA LOGGER TRIGGER — This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic
operand can be used as the trigger source. This setting only applies when the mode is set to “Trigger.”
DATA LOGGER RATE — This setting selects the time interval at which the actual value data is recorded.
DATA LOGGER CHNL 1(16) — This setting selects the metering actual value that is to be recorded in Channel 1(16) of the data
log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/VT hardware
modules installed, and the type and number of Analog Input hardware modules installed. Upon startup, the relay
automatically prepares the parameter list. A list of all possible analog metering actual value parameters is shown in
Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to expedite the
selection of the parameter on the relay display. It can be time-consuming to scan through the list of parameters via the
relay keypad/display—entering this number via the relay keypad causes the corresponding parameter to display.
DATA LOGGER CONFIG — This display presents the total amount of time that the Data Logger can record the channels not
selected to “Off” without overwriting old data.
5.3.10 Demand
SETTINGS PRODUCT SETUTP DEMAND
DEMAND CRNT DEMAND METHOD: Range: Thermal Exponential, Block Interval, Rolling
Thermal Exponential Demand
The relay measures current demand on each phase, and three-phase demand for real, reactive, and apparent power.
Current and Power methods can be chosen separately for the convenience of the user. Settings are provided to allow the
user to emulate common electrical utility demand measuring techniques, for statistical or control purposes. If the CRNT
DEMAND METHOD is set to "Block Interval" and the DEMAND TRIGGER is set to “Off,” Method 2 is used as follows. If DEMAND
TRIGGER is assigned to any other FlexLogic operand, Method 2a is used as follows.
The relay can be set to calculate demand by any of the following three methods.
5 The figure shows the 90% thermal response time characteristic of 15 minutes. A setpoint establishes the time to reach
90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the
response time indicates 99% of the value.
Figure 5-31: Thermal demand characteristic
Demand (%)
5.3.10.3 Calculation method 2a: Block interval (with start demand interval logic trigger)
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the interval between successive Start Demand Interval logic input pulses. Each new value of demand becomes available at
the end of each pulse. Assign a FlexLogic operand to the DEMAND TRIGGER setting to program the input for the new
demand interval pulses.
If no trigger is assigned in the DEMAND TRIGGER setting and the CRNT DEMAND METHOD is "Block Interval," use
calculation method 2. If a trigger is assigned, the maximum allowed time between two trigger signals is 60
NOTE
minutes. If no trigger signal appears within 60 minutes, demand calculations are performed and available, and
the algorithm resets and starts the new cycle of calculations. The minimum required time for trigger contact
closure is 20 ms.
5.3.11.1 Menu
SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS
USER-PROGRAMMABLE LED TEST See below
LEDS
The 48 amber LEDs on relay panels 2 and 3 can be customized to illuminate when a selected FlexLogic operand is in the
logic 1 state. The trip and alarm LEDs on panel 1 can also be customized in a similar manner. To ensure correct
functionality of all LEDs, an LED test feature is also provided.
When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user-
programmable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all
LEDs, including the LEDs of the optional user-programmable pushbuttons.
The test consists of the following three stages:
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned.” This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and
monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay
and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting
from relay response during testing. The reset pushbutton does not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is initiated,
the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL
setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is
executed.
Figure 5-32: LED test sequence
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
5 STAGE 1
(all LEDs on)
time-out
(1 minute)
rising edge
STAGE 3
of the control
(one LED off at a time) input
842011A1.CDR
Application example 1
Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER-
PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu. (The option does not display when not purchased.)
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.10 s”
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS
PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST menu:
LED TEST FUNCTION: “Enabled”
LED TEST CONTROL: “PUSHBUTTON 1 ON”
The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.
Application example 2
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic operand is in the logic 1 state.
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illuminate
when the selected FlexLogic operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows:
• LED Panel 2 — User-programmable LEDs 1 through 24
• LED Panel 3 — User programmable LEDs 25 through 48
For the enhanced faceplate, the LEDs are located as follows:
• LED column 2 — User-programmable LEDs 1 through 12
• LED column 3 — User-programmable LEDs 13 through 24
• LED column 4 — User-programmable LEDs 25 through 36
• LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is “Self-
Reset” (the default setting), the LED illumination tracks the state of the selected LED operand. If the LED 1 TYPE setting is
“Latched,” the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.
DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped
FUNCTION: Enabled with Direct Input/Output module.
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
Most of the minor alarms can be disabled if so wanted.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
The location of the control pushbuttons are shown in the following figures.
Figure 5-33: Control pushbuttons (enhanced faceplate)
5
Control pushbuttons
842813A1.CDR
An additional four control pushbuttons are included on the standard faceplate when the F35 is ordered with the 12 user-
programmable pushbutton option.
Figure 5-34: Control pushbuttons (standard faceplate)
USER 4
842733A2.CDR
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to perform
the required function. Each operand remains asserted as long as the pushbutton is pressed and resets when the
pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognized
by various features that can use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously—a given key
must be released before the next one can be pressed.
Figure 5-35: Control pushbutton logic
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
The F35 is provided with this optional feature, specified as an option at the time of ordering. Using the
order code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number of available pushbuttons is dependent on the faceplate module ordered with the relay.
• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons
• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic
operands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker
control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control
level of password protection.
The figure shows user-configurable pushbuttons for the enhanced faceplate.
Figure 5-36: User-programmable pushbuttons (enhanced faceplate)
USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16
842814A1.CDR
5
The following figure shows user-configurable pushbuttons for the standard faceplate.
Figure 5-37: User-programmable pushbuttons (standard faceplate)
1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.CDR
Both the standard and enhanced faceplate pushbuttons can be custom labeled with a factory-provided template,
available online at http://www.gedigitalenergy.com/multilin. The EnerVista software can also be used to create labels for
the enhanced faceplate.
Each pushbutton asserts its own “On” and “Off” FlexLogic operands (for example, PUSHBUTTON 1 ON and PUSHBUTTON 1 OFF).
These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is active,
the ANY PB ON operand is asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the
corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the
PUSHBTN 1 LED CTL setting.
The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched
and self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when
the PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
• Latched mode — In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSHBTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set
state until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is
stored in non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET
setting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY
settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if
control is not executed within a specified time period.
• Self-reset mode — In self-reset mode, a pushbutton remains active for the time it is pressed (the pulse duration) plus
the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic, the
pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the
PUSHBTN 1 SET setting has no effect on the pulse duration.
The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT
TIME setting expires.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the
pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events
NOTE
and various system disturbances that can cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL
and PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton ignores set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton ignores set and reset
commands executed through FlexLogic operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
5 The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
PUSHBUTTON 1 FUNCTION — This setting selects the characteristic of the pushbutton. If set to “Disabled,” the pushbutton is
not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If set to “Self-Reset,” the
control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically pressed or
virtually pressed via a FlexLogic operand assigned to the PUSHBTN 1 SET setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding FlexLogic
operand as long as the pushbutton is being physically pressed, and after being released the deactivation of the operand is
delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deactivated. If the
pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” FlexLogic operand
only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting.
If set to “Latched,” the control logic alternates the state of the corresponding FlexLogic operand between “On” and “Off” on
each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the “Latched”
mode, the states of the FlexLogic operands are stored in a non-volatile memory. If power supply is lost, the correct state of
the pushbutton is retained upon subsequent power up of the relay.
PUSHBTN 1 ID TEXT — This setting specifies the top 20-character line of the user-programmable message and is intended to
provide ID information of the pushbutton. See the User-definable Displays section for instructions on how to enter
alphanumeric characters from the keypad.
PUSHBTN 1 ON TEXT — This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. See the User-definable Displays section for instructions on entering
alphanumeric characters from the keypad.
PUSHBTN 1 OFF TEXT — This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is “Latched.”
This message is not displayed when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand status is
implied to be “Off” upon its release. The length of the “Off” message is configured with the PRODUCT SETUP DISPLAY
PROPERTIES FLASH MESSAGE TIME setting.
PUSHBTN 1 HOLD — This setting specifies the time required for a pushbutton to be pressed before it is deemed active. This
timer is reset upon release of the pushbutton. Note that any pushbutton operation requires the pushbutton to be pressed a
minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
PUSHBTN 1 SET — This setting assigns the FlexLogic operand serving to operate the pushbutton element and to assert
PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms.
PUSHBTN 1 RESET — This setting assigns the FlexLogic operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the incoming
reset signal must be at least 50 ms.
PUSHBTN 1 AUTORST — This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in the “Latched” mode.
PUSHBTN 1 AUTORST DELAY — This setting specifies the time delay for automatic reset of the pushbutton when in the
latched mode.
PUSHBTN 1 REMOTE — This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the operand
assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
PUSHBTN 1 LOCAL — This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel
pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME — This setting applies only to “Self-Reset” mode and specifies the duration of the pushbutton
active status after the pushbutton has been released. When activated remotely, this setting specifies the entire activation
time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration. This setting
is required to set the duration of the pushbutton operating pulse.
PUSHBTN 1 LED CTL — This setting assigns the FlexLogic operand serving to drive pushbutton LED. If this setting is “Off,” then
LED operation is directly linked to the PUSHBUTTON 1 ON operand.
PUSHBTN 1 MESSAGE — If pushbutton message is set to “High Priority,” the message programmed in the PUSHBTN 1 ID and
PUSHBTN 1 ON TEXT settings are displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted. The high priority
5
option is not applicable to the PUSHBTN 1 OFF TEXT setting.
This message can be temporary removed if any front panel keypad button is pressed. However, 10 seconds of keypad
inactivity restores the message if the PUSHBUTTON 1 ON operand is still active.
If the PUSHBTN 1 MESSAGE is set to “Normal,” the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings
are displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified by FLASH MESSAGE
TIME setting. After the flash time is expired, the default message or other active target message is displayed. The
instantaneous reset of the flash message is executed if any relay front panel button is pressed or any new target or
message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and displays in conjunction with PUSHBTN 1 ID only if
pushbutton element is in the “Latched” mode. The PUSHBTN 1 OFF TEXT message displays as “Normal” if the PUSHBTN 1
MESSAGE setting is “High Priority” or “Normal.”
PUSHBUTTON 1 EVENTS — If this setting is enabled, each pushbutton state change is logged as an event into the event
recorder.
The figures show the user-programmable pushbutton logic.
SETTING
Function
LATCHED To user-programmable
= Enabled
pushbuttons logic
= Latched sheet 2, 842024A2
OR LATCHED/SELF-RESET
= Self-Reset
SETTING
Local Lock
Off = 0 Non-volatile latch
AND
S
TIMER
SETTING Latch
50 ms
Remote Lock R
Off = 0 AND
0
SETTING OR
TIMER
Hold 50 ms
TPKP
0
0
OR
SETTING
Set AND
Off = 0
To user-programmable
OR PUSHBUTTON ON pushbuttons logic
OR
sheet 2, 842024A2
SETTING
Reset AND
Off = 0
5 SETTING
AND
SETTING
Autoreset Delay
Autoreset Function
TPKP
= Enabled
AND
= Disabled
0
AND
SETTING
Drop-Out Timer
TIMER 0
FLEXLOGIC OPERAND 200 ms OR
TRST
PUSHBUTTON 1 ON
0
842021A3.CDR
AND
LCD MESSAGE
ENGAGE MESSAGE
SETTING
LATCHED Flash Message Time
SETTINGS
0 Top Text
AND
OR TRST = XXXXXXXXXX
On Text
= XXXXXXXXXX
Instantaneous
From user-programmable reset *
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
Instantaneous
Instantaneous reset will be executed if any
5
reset *
front panel button is pressed or any new
target or message becomes active.
PUSHBUTTON 1 LED LOGIC
1. If pushbutton 1 LED control is set to off.
Pushbutton 1
FLEXLOGIC OPERAND LED
FLEXLOGIC OPERAND PUSHBUTTON 1 ON
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON 2. If pushbutton 1 LED control is not set to off.
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON SETTING Pushbutton 1
OR ANY PB ON
PUSHBTN 1 LED CTL LED
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256
state bits.
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient
viewing sequence in the USER DISPLAY menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus
facilitate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
• Keypad — Use the MENU key to select the USER DISPLAY menu item to access the first user-definable display (note that
only the programmed screens are displayed). The screens can be scrolled using the up and down arrow keys. The
5 display disappears after the default message time-out period specified by the PRODUCT SETUP DISPLAY PROPERTIES
DEFAULT MESSAGE TIMEOUT setting.
• User-programmable control input — The user-definable displays also respond to the INVOKE AND SCROLL setting. Any
FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the
programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the
first one. The INVOKE AND SCROLL input and the down arrow key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay starts to cycle through the user
displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user display, not
at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display then prompts with ADD TO USER DISPLAY LIST? After selecting “Yes,” a message
indicates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus
are automatically configured with the proper content—this content can be edited subsequently.
This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user
display. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the
start of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered
in a user display – the nth tilde (~) refers to the nth item.
A user display can be entered from the faceplate keypad or the EnerVista interface (preferred for convenience). The
following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key can be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected
system display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the
Modbus address, then manually convert it to decimal form before entering it (EnerVista usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option
5
to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
An example of user display setup and result is shown as follows.
USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first tilde marker
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker
Current Y ~ A
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom
line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different.
5.3.17.1 Menu
SETTINGS PRODUCT SETUP DIRECT I/O
DIRECT I/O DIRECT OUTPUT Range: 1 to 16 in steps of 1
DEVICE ID: 1
UNRETURNED
5 MESSAGES ALARM CH2
This option is available when an Inter-Relay Communications card is specified at the time of ordering (see
the Order Code tables). With the option, direct inputs/outputs display by default. When you enable the
teleprotection feature, direct I/O is not visible.
Direct inputs and outputs exchange status information (inputs and outputs) between UR-series relays connected directly
via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GOOSE, except that communications
takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that support two channels,
direct output messages are sent from both channels simultaneously. This effectively sends direct output messages both
ways around a ring configuration. On type 7 cards that support one channel, direct output messages are sent only in one
direction. Messages are resent (forwarded) when it is determined that the message did not originate at the receiver.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked,
NOTE
and vice versa.
Direct output message timing is similar to GOOSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic operands:
• DIRECT RING BREAK (direct input/output ring break). This FlexLogic operand indicates that direct output messages sent
from a UR-series relay are not being received back by the relay.
• DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic operands indicate that direct output
messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID setting, which identifies the relay in all direct output
messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of
the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages are received back. If not, the direct input/output ring break
self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel
communications cards apply the same data rate to both channels. Delivery time for direct input and output messages is
approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each "bridge."
Table 5-14: Direct input and output data rates
Module Channel Supported data rates
74 Channel 1 64 kbps
Channel 2 64 kbps
7L Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7M Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7P Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7T Channel 1 64 kbps, 128 kbps
7W Channel 1 64 kbps, 128 kbps 5
Channel 2 64 kbps, 128 kbps
7V Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
2A Channel 1 64 kbps
2B Channel 1 64 kbps
Channel 2 64 kbps
2G Channel 1 128 kbps
2H Channel 1 128 kbps
2I Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
2J Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
NOTE
5 The DIRECT I/O CHANNEL CROSSOVER setting applies to F35s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputs
and Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
UR IED 1 BLOCK
842712A1.CDR
For increased reliability, a dual-ring configuration (shown as follows) is recommended for this application.
Figure 5-42: Interlocking bus protection scheme via direct inputs/outputs 5
TX1 RX1
UR IED 1
RX2 TX2
TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR
Message delivery time is approximately 0.2 of power system cycle (at 128 kbps) times number of ‘bridges’ between the
origin and destination. Dual-ring configuration effectively reduces the maximum ‘communications distance’ by a factor of
two.
In this configuration the following delivery times are expected (at 128 kbps) if both rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.2 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
If one ring is broken (say TX2-RX2) the delivery times are as follows:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.6 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
A coordinating timer for this bus protection scheme could be selected to cover the worst case scenario (0.4 of a power
system cycle). Upon detecting a broken ring, the coordination time is adaptively increased to 0.6 of a power system cycle.
The complete application requires addressing a number of issues, such as failure of both the communications rings, failure
or out-of-service conditions of one of the relays, and so on. Self-monitoring flags of the direct inputs and outputs feature
primarily are used to address these concerns.
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2
constitute a first ring, while IEDs 2 and 3 constitute a second ring).
Figure 5-44: Single-channel open loop configuration
RX1
UR IED 3
TX1
842714A1.CDR
TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR
The F35 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter
adds up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the
CRC ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC ALARM
FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT
setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions—if required—are programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES STATUS DIRECT INPUTS CRC FAIL COUNT CH1 actual value.
5 • Message count and length of the monitoring window — To monitor communications integrity, the relay sends 1
message per second (at 64 kbps) or 2 messages per second (128 kbps) even if there is no change in the direct outputs.
For example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000,” corresponds a time window of about 160 minutes
at 64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity, the
monitoring time interval shortens. Take this into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT is set to 10 60 1 = 600.
• Correlation of failed CRC and bit error rate (BER) — The CRC check can fail if one or more bits in a packet are
corrupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain
assumptions an approximation can be made as follows. A direct input and output packet containing 20 bytes results
in 160 bits of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4
implies 1 bit error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet,
having 1 failed packet for every 63 received is about equal to a BER of 10–4.
The F35 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of
unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have
failed to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS
ALARM CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1
UNRET ALM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions, if required, are programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES STATUS DIRECT INPUTS
UNRETURNED MSG COUNT CH1 actual value.
5.3.18 Teleprotection
SETTINGS PRODUCT SETUP TELEPROTECTION
TELEPROTECTION TELEPROTECTION Range: Disabled, Enabled
FUNCTION: Disabled
This option is available when an Inter-Relay Communications card is specified at the time of ordering (see
the Order Code tables). With the option, direct inputs/outputs display by default. When you enable the
teleprotection feature, direct I/O is not visible.
Digital teleprotection transfers protection commands between two or three relays in a secure, fast, dependable, and
deterministic way. Possible applications are permissive or blocking pilot schemes and direct transfer trip (DTT).
Teleprotection can be applied over any analog or digital channels and any communications media, such as direct fiber,
copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted
continuously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel
data is achieved by using CRC-32 on the data packet.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked,
NOTE
and vice versa.
NUMBER OF TERMINALS — Specifies whether the teleprotection system operates between two peers or three peers.
NUMBER OF CHANNELS — Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal system),
set the NUMBER OF CHANNELS to “2.” For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or “2” (redundant
channels).
LOCAL RELAY ID NUMBER , TERMINAL 1 RELAY ID NUMBER , and TERMINAL 2 RELAY ID NUMBER — In installations that use
multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line is from the correct
relays. The teleprotection function performs this check by reading the message ID sent by transmitting relays and
comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inadvertently set to
loopback mode or data is being received from a wrong relay by checking the ID on a received channel. If an incorrect ID is
found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL FlexLogic operand is set, driving the
event with the same name and blocking the teleprotection inputs. For commissioning purposes, the result of channel
identification is also shown in the STATUS CHANNEL TESTS VALIDITY OF CHANNEL CONFIGURATION actual value. The
default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID is not to be checked. On two- terminals two-
channel systems, the same LOCAL RELAY ID NUMBER is transmitted over both channels; as such, only the TERMINAL 1 ID
NUMBER has to be programmed on the receiving end.
5.3.19 Installation
SETTINGS PRODUCT SETUP INSTALLATION
INSTALLATION RELAY SETTINGS: Range: Not Programmed, Programmed
Not Programmed
To safeguard against the installation of a relay without any entered settings, the unit does not allow signaling of any
output relay until RELAY SETTINGS is set to "Programmed." This setting is "Not Programmed" by default. The UNIT NOT
PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
The RELAY NAME setting allows the user to uniquely identify a relay. This name appears on generated reports.
5
5.4 Remote resources
5.4.1 Remote resources configuration
When the F35 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources
menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
Figure 5-46: Remote Resources configuration menu
The remote resources settings configure a F35 with a process bus module to work with HardFiber Bricks. Remote
resources configuration is only available through the EnerVista software, and is not available through the F35 front panel.
A Brick provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to be the
remote interface to field equipment such as circuit breakers and transformers. The F35 with a process bus module has
access to all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection
between specific fiber optic ports on the F35 process card and specific Brick. The relay is then configured to measure
specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
The configuration process for remote resources is straightforward and consists of the following steps.
• Configure the field units. This establishes the point-to-point connection between a specific port on the relay process
bus module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus
relay.
• Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages. AC
bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful
reliability improvement possible with process bus.
• Configure signal sources. This functionality of the F35 has not changed other than the requirement to use currents
and voltages established by AC bank configuration under the remote resources menu.
• Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's
functionality. These inputs and outputs are the physical interface to circuit breakers, transformers, and other
equipment. They replace the traditional contact inputs and outputs located at the relay to virtually eliminate copper
wiring.
• Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are
distinct binary channels that provide high-speed protection quality signaling between relays through a Brick.
For additional information on how to configure a relay with a process bus module, see the HardFiber Process Bus System
Instruction Manual.
5
5.5 System setup
5.5.1 AC inputs
PHASE CT F1 Range: 1 A, 5 A
SECONDARY: 1 A
GROUND CT F1 Range: 1 A, 5 A
SECONDARY: 1 A
Because energy parameters are accumulated, record these values and then reset immediately prior to changing CT
characteristics.
Six banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M, U} and a = {1, 5}
See the Introduction to AC Sources section at the beginning of this chapter for details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the input
for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor can also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input can be used. In this
case, the sensitive ground CT primary rating must be entered. See chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct operation,
the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given the
following current banks:
• F1: CT bank with 500:1 ratio
• F5: CT bank with 1000:1 ratio
• M1: CT bank with 800:1 ratio
The following rule applies:
SRC 1 = F1 + F5 + M1 Eq. 5-7
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 ratio CT is
adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then
a pickup level of 1 pu operates on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).
Because energy parameters are accumulated, these values should be recorded and then reset immediately prior to
changing VT characteristics.
Three banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M, U} and a = {5}
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5
CONNECTION made to the system as “Wye” or “Delta.” An open-delta source VT connection is entered as “Delta.”
The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when
nominal voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta
connection, the secondary voltage is 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage
value entered must be the phase to neutral voltage, which is 115 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the
voltage value entered is 120; that is, 14400 / 120.
If the PHASE VT F5 CONNECTION is set to “Delta”, the relay does not calculate voltage harmonics.
NOTE
FREQUENCY AND PHASE Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
REFERENCE: SRC 1
FREQUENCYTRACKING:
Enabled
Range: Disabled, Enabled 5
The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This can happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a
safe period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence. Note that this setting informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be connected
to system phases A, B, and C for correct operation.
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs that are configured for the signal source:
phase voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing ( V ANGLE REF = V A ), while Clarke transformation of the
phase signals is used for frequency metering and tracking ( V FREQUENCY = 2V A – V B – V C 3 ) for better performance during
fault, open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the Source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal always displays zero degrees and all other phase angles are relative to this signal. If the
pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of phase angle indications between different UR-
series relays.
FREQUENCY TRACKING is set to “Disabled” only in unusual circumstances; consult the factory for special variable-frequency
applications.
The frequency tracking feature functions only when the F35 is in the “Programmed” mode. If the F35 is “Not
Programmed,” then metering values are available but can exhibit significant errors.
NOTE
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter
represents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called
5 “5” in a particular CT/VT module. See the Introduction to AC Sources section at the beginning of this chapter for details.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others are referred.
For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5,” scaled to whichever CT
has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio
and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs are summed together.
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR
5
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(PRODUCT SETUP DISPLAY PROPERTIES CURRENT CUT-OFF LEVEL) controls the sensitivity of the disturbance detector
accordingly.
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
F5
Source 1 Source 2
Amps Amps
Source 3
51BF-1 51BF-2
U1 Volts Amps
A W Var 87T
A W Var 51P
Volts Amps
M1
M1 Source 4
UR Relay
M5
827794A1.CDR
Y LV D HV AUX
5 Phase CT
SRC 1
M1
SRC 2
F1+F5
SRC 3
None
Ground CT M1 None None
Phase VT M5 None None
Aux VT None None U1
5.5.4 Breakers
SETTINGS SYSTEM SETUP BREAKERS BREAKER 1(6)
BREAKER 1 BREAKER 1 Range: Disabled, Enabled
FUNCTION: Disabled
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled 5
A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Information to
program the settings is covered here. These features are provided for two or more breakers; a user can use only those
portions of the design relevant to a single breaker, which must be breaker 1.
The number of breaker control elements depends on the number of CT/VT modules specified with the F35. The following
settings are available for each breaker control element.
BREAKER 1 FUNCTION — This setting enables and disables the operation of the breaker control feature.
BREAKER1 PUSH BUTTON CONTROL — Set to “Enable” to allow faceplate pushbutton operations.
BREAKER 1 NAME — Assign a user-defined name (up to six characters) to the breaker. This name is used in flash messages
related to breaker 1.
BREAKER 1 MODE — Selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-Pole” mode where all
breaker poles are operated either independently or simultaneously.
BREAKER 1 OPEN — Selects an operand that creates a programmable signal to operate an output relay to open breaker 1.
BREAKER 1 BLK OPEN — Selects an operand that prevents opening of the breaker. This setting can be used for select-before-
operate functionality or to block operation from a panel switch or from SCADA.
BREAKER 1 CLOSE — Selects an operand that creates a programmable signal to operate an output relay to close breaker 1.
BREAKER 1 BLK CLOSE — Selects an operand that prevents closing of the breaker. This setting can be used for select-before-
operate functionality or to block operation from a panel switch or from SCADA.
BREAKER 1 A/3P CLOSED — Selects an operand, usually a contact input connected to a breaker auxiliary position tracking
mechanism. This input is a normally-open 52/a status input to create a logic 1 when the breaker is closed. If the BREAKER 1
MODE setting is selected as “3-Pole,” this setting selects a single input as the operand used to track the breaker open or
closed position. If the mode is selected as “1-Pole,” the input mentioned is used to track phase A and the BREAKER 1 B and
BREAKER 1 C settings select operands to track phases B and C, respectively.
BREAKER 1 A/3P OPND — Selects an operand, usually a contact input, that is a normally-closed 52/b status input to create
a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted BREAKER 1 CLOSED status
signal can be used.
BREAKER 1 B CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1 B OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1 C CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1 C OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 Toperate — This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes.
BREAKER 1 EXT ALARM — This setting selects an operand, usually an external contact input, connected to a breaker alarm
reporting contact.
BREAKER 1 ALARM DELAY — This setting specifies the delay interval during which a disagreement of status among the three-
pole position tracking operands does not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
MANUAL CLOSE RECAL1 TIME — This setting specifies the interval required to maintain setting changes in effect after an
operator has initiated a manual close command to operate a circuit breaker.
BREAKER 1 OUT OF SV — Selects an operand indicating that breaker 1 is out-of-service.
5
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE
61850 model 61850 model
BrkCSWI1.PosOpn.ctVal Brk0XCBR1.BlkOpn.stVal
OR AND
Brk0XCBR1.PosOpn.ctVal
SETTING
OR
BREAKER 1 OPEN
Off = 0
USER 3 OFF/ON
To open BRK1-(Name)
SETTING
AND
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled
OR 0
5
USER 2 OFF/ON AND
AND 20 ms
To open BRK1-(Name)
61850 model
BrkCSWI1.PosCls.ctVal
OR
Brk0XCBR1.PosCls.ctVal
AND
61850 XCBR config setting AND
SETTING OR
XCBR1 ST.LOC OPERAND: OR
FLEXLOGIC OPERAND
Off = 0
AND BREAKER 1 MNL CLS
SETTING SETTING
MANUAL CLOSE RECAL1 TIME AND
BREAKER 1 CLOSE
Off = 0
C60, D60, L60, and L90 relays from recloser
0
FLEXLOGIC OPERAND
AR CLOSE BKR 1
61850 model OR
FLEXLOGIC OPERAND
AND
Brk0XCBR1.BlkCls.ctVal AND BREAKER 1 ON CMD
SETTING OR
BREAKER 1 BLOCK CLOSE
Off = 0 OR 61850 model
Brk0XCBR1.BlkCls.stVal
IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in local control mode.
NOTE
FLEXLOGIC OPERAND
SETTING SETTING
AND OR BREAKER 1 BAD STATUS
BREAKER 1 ΦA/3P CLSD BREAKER 1 Toperate
= Off OR
FLEXLOGIC OPERANDS
AND AND
BREAKER 1 ΦA BAD ST
0
BREAKER 1 ΦA CLSD
SETTING BKR1 A CLOSED AND BREAKER 1 ΦA OPEN
BREAKER 1 ΦA/3P OPND
AND BREAKER 1 ΦA INTERM
= Off
BKR1 A OPENED AND
AND
AND
SETTING SETTING
AND
BREAKER 1 Toperate
5
BREAKER 1 ΦB CLSD
FLEXLOGIC OPERANDS
= Off OR AND
AND BREAKER 1 ΦB BAD ST
0 BREAKER 1 ΦB CLSD
SETTING BREAKER 1 ΦB OPEN
BKR1 B CLOSED AND
BREAKER 1 ΦB OPENED BREAKER 1 ΦB INTERM
AND
= Off
BKR1 B OPENED AND
AND
AND
SETTING SETTING
AND
BREAKER 1 ΦC CLSD BREAKER 1 Toperate
OR FLEXLOGIC OPERANDS
= Off AND
AND BREAKER 1 ΦC BAD ST
0 BREAKER 1 ΦC CLSD
SETTING BREAKER 1 ΦC OPEN
BKR1 C CLOSED AND
BREAKER 1 ΦC OPENED BREAKER 1 ΦC INTERM
AND
= Off
BKR1 C OPENED AND
AND
AND
BKR1 A CLOSED
BKR1 B CLOSED AND FLEXLOGIC OPERANDS
BKR1 C CLOSED AND BREAKER 1 ANY P OPEN
BREAKER 1 1P OPEN
BREAKER 1 OOS
XOR AND
SETTING
BREAKER 1 OUT OF SV AND
= Off 859712A1.cdr
The breaker element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each breaker, using either CSWI or XCBR IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking of open/close commands are provided. Note
that the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/
open command for a certain time, do so on the contact outputs using the "Seal-in" setting, in the Trip Output element, or in
FlexLogic.
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to
create interlocking functionality. For greater security in determination of the switch pole position, both the 89/a and 89/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the F35.
SWITCH 1 FUNCTION — This setting enables and disables operation of the disconnect switch element.
SWITCH 1 NAME — Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
messages related to disconnect switch 1.
SWITCH 1 MODE — This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
SWITCH 1 OPEN — This setting selects an operand that creates a programmable signal to operate a contact output to open
disconnect switch 1.
SWITCH 1 BLK OPEN — This setting selects an operand that prevents opening of the disconnect switch. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWITCH 1 CLOSE — This setting selects an operand that creates a programmable signal to operate a contact output to close
disconnect switch 1.
SWITCH 1 BLK CLOSE — This setting selects an operand that prevents closing of the disconnect switch. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWTCH 1A/3P CLSD — This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
position tracking mechanism. This input is a normally-open 89/a status input to create a logic 1 when the disconnect
switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole,” this setting selects a single input as the operand used
to track the disconnect switch open or closed position. If the mode is selected as “1-Pole,” the input mentioned is used to
track phase A and the SWITCH 1 B and SWITCH 1 C settings select operands to track phases B and C, respectively.
SWTCH 1 A/3P OPND — This setting selects an operand, usually a contact input, that is a normally-closed 89/b status input
to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an inverted
89/a status signal can be used.
SWITCH 1 B CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1 B OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
SWITCH 1 C CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1 C OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 Toperate — This setting specifies the required interval to overcome transient disagreement between the 89/a and
89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has expired,
the SWITCH 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes.
5 SWITCH 1 ALARM DELAY — This setting specifies the delay interval during which a disagreement of status among the three-
pole position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in local control mode.
NOTE
SETTING
SWITCH 1 CLOSE
= Off
61850 model
Disc0CSWI1.PosCls.ctVal FLEXLOGIC OPERAND
OR
Disc0XSWI1.PosCls.ctVal AND SWITCH 1 ON CMD
OR
61850 XSWI configuration setting AND
SETTING
XSWI1 ST.LOC OPERAND:
61850 model
Off = 0 Disc0XSWI1.BlkCls.stVal
61850 model AND
Disc0XSWI1.BlkCls.ctlVal OR
FLEXLOGIC OPERAND
SETTING AND SWITCH 1 OPEN
SWITCH 1 MODE AND OR
= 3-Pole
FLEXLOGIC OPERAND
= 1-Pole SETTING AND SWITCH 1 DISCREP
5
SWITCH 1 ALARM DELAY
SW1 A CLOSED
SW1 B CLOSED AND
AND 0
SW1 C CLOSED
FLEXLOGIC OPERAND
OR AND SWITCH 1 TROUBLE
SW1 A OPENED
AND
SW1 B OPENED
SW1 C OPENED
FLEXLOGIC OPERAND
SETTING OR SWITCH 1 BAD STATUS
SETTING
SWITCH 1 Toperate
SWTCH1 ΦA/3P CLSD AND
FLEXLOGIC OPERANDS
= Off
AND SWITCH 1 ΦA BAD ST
OR
AND 0 SWITCH 1 ΦA CLSD
SETTING SW1 A CLOSED
AND SWITCH 1 ΦA OPEN
SWTCH 1 ΦA/3P OPND
AND SWITCH 1 ΦA INTERM
= Off
SW1 A OPENED AND
AND
AND
SETTING
SETTING
SWITCH 1 Toperate
SWITCH 1 ΦB CLOSED AND
FLEXLOGIC OPERANDS
= Off AND SWITCH 1 ΦB BAD ST
OR
AND 0 SWITCH 1 ΦB CLSD
SETTING SW1 B CLOSED
AND SWITCH 1 ΦB OPEN
SWITCH 1 ΦB OPENED
AND SWITCH 1 ΦB INTERM
= Off
SW1 B OPENED
AND
AND
SETTING AND
SETTING
SWITCH 1 Toperate
SWITCH 1 ΦC CLOSED AND
= Off FLEXLOGIC OPERANDS
AND SWITCH 1 ΦC BAD ST
OR
AND 0 SWITCH 1 ΦC CLSD
SETTING SW1 C CLOSED
AND SWITCH 1 ΦC OPEN
SWITCH 1 ΦC OPENED
AND SWITCH 1 ΦC INTERM
= Off
SW1 C OPENED
AND
SETTING AND
SWITCH 1 FUNCTION
= Disabled AND
= Enabled
859720A1.CDR
The switch element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking open/close commands are provided. Note that
the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain close/open
command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in FlexLogic.
5.5.6 FlexCurves
5.5.6.1 Settings
SETTINGS SYSTEM SETUP FLEXCURVES FLEXCURE A(D)
FLEXCURVE A FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1
0.00 xPKP: 0 ms
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter
a custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE up/down keys) for the required protection curve (A, B, C, or D).
5 0.10
0.15
0.72
0.74
1.1
1.2
3.1
3.2
5.1
5.2
11.5
12.0
0.20 0.76 1.3 3.3 5.3 12.5
0.25 0.78 1.4 3.4 5.4 13.0
0.30 0.80 1.5 3.5 5.5 13.5
0.35 0.82 1.6 3.6 5.6 14.0
0.40 0.84 1.7 3.7 5.7 14.5
0.45 0.86 1.8 3.8 5.8 15.0
0.48 0.88 1.9 3.9 5.9 15.5
0.50 0.90 2.0 4.0 6.0 16.0
0.52 0.91 2.1 4.1 6.5 16.5
0.54 0.92 2.2 4.2 7.0 17.0
0.56 0.93 2.3 4.3 7.5 17.5
0.58 0.94 2.4 4.4 8.0 18.0
0.60 0.95 2.5 4.5 8.5 18.5
0.62 0.96 2.6 4.6 9.0 19.0
0.64 0.97 2.7 4.7 9.5 19.5
0.66 0.98 2.8 4.8 10.0 20.0
The relay using a given FlexCurve applies linear approximation for times between the user-entered points. Take
care when setting the two points that are close to the multiple of pickup of 1; that is, 0.98 pu and 1.03 pu. It is
NOTE
recommended to set the two times to a similar value, otherwise the linear approximation can result in
undesired behavior for the operating quantity that is close to 1.00 pu.
Addr: Adds the time specified in this field (in ms) to each
curve operating time value.
5
Minimum Response Time (MRT): If enabled, the MRT setting
defines the shortest operating time even if the curve suggests
a shorter time at higher current multiples. A composite operating
characteristic is effectively defined. For current multiples lower
than the intersection point, the curve dictates the operating time;
otherwise, the MRT does. An information message appears
when attempting to apply an MRT shorter than the minimum
curve time.
The Multiplier and Adder settings only affect the curve portion of the characteristic and not the MRT and HCT
settings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
NOTE
5.5.6.4 Example
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight times pickup with an operating time of 30 ms. At approximately four times pickup, the curve operating
time is equal to the MRT and from then onwards the operating time remains at 200 ms.
842719A1.CDR
With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup.
Figure 5-54: Composite recloser curve with HCT enabled
842720A1.CDR
Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed.
If this is attempted, the EnerVista software generates an error message and discards the proposed changes.
NOTE
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup)
5
842723A1.CDR
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
Figure 5-57: Recloser curves GE134, GE137, GE140, GE151, and GE201
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
5
Figure 5-58: Recloser curves GE131, GE141, GE152, and GE200
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
Figure 5-59: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5-60: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139
5
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
Figure 5-61: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR
5
Figure 5-62: Recloser curves GE119, GE135, and GE202
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
5.6 FlexLogic
5.6.1 FlexLogic operands
For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.
Figure 5-63: UR architecture overview
CTs DSP
VTs (A/D) FlexLogic™ Virtual
equations outputs
Calculate
DCmA parameters Measuring
Analog and
or
input decision Digital Flags
RTD
(A/D) elements elements
inputs
V I
Contact Form-A and
inputs FlexLogic™ SCR only
Block counters
operation Contact
(each outputs
Keypad
element)
5
Virtual Remote
inputs (FlexLogic operands) outputs
OR
Remote Display
inputs Control and LEDs
(GOOSE) and Display
monitoring
features
fiber Analog
Direct output (D/A)
G.703 inputs
RS422 (dcmA)
(Status) Fiber
Direct
G.703
outputs
RS422
(Actual values) (Status)
827022A7.cdr
The states of all digital signals used in the F35 are represented by flags (or FlexLogic operands, which are described later in
this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an
element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output. The state
of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple
scheme where a contact input is used to block an element is wanted, this selection is made when programming the
element. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes,
and human operators.
If more complex logic than shown in the figure is required, it is implemented via FlexLogic. For example, to have the closed
state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase
time overcurrent element, the two control input states are programmed in a FlexLogic equation. This equation ANDs the
two control inputs to produce a virtual output that is then selected when programming the phase time overcurrent to be
used as a blocking input. Virtual outputs can only be created by FlexLogic equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or
supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the requirement for
auxiliary components and wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes, and outputs is field-programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is
available internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes, and outputs. The operators are logic gates, timers, and latches (with
set and reset inputs). A system of sequential operations allows any combination of operands to be assigned as inputs to
specified operators to create an output. The final output of an equation is a numbered register called a virtual output.
Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of
parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, or flag set) or 0
(=OFF, or flag not set). Each equation is evaluated at least four times every power system cycle.
Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the faceplate display. The table lists characteristics
of the different types of operands.
Table 5-16: F35 FlexLogic operand types
Operand type State Example of format Characteristics
[Input Is ‘1’ (= ON) if...]
Contact Input On Cont Ip On Voltage is applied presently to the input (external contact
5 Off Cont Ip Off
closed)
Voltage is not applied presently to the input (external
contact open)
Contact Output Current On Cont Op 1 Ion Current is flowing through the contact
(type Form-A contact
Voltage On Cont Op 1 VOn Voltage exists across the contact
only)
Voltage Off Cont Op 1 VOff Voltage does not exist across the contact
Direct Input On DIRECT INPUT 1 On The direct input is presently in the ON state
Element Pickup PHASE TOC1 PKP The tested parameter is presently above the pickup setting
(Analog) of an element that responds to rising values or below the
pickup setting of an element that responds to falling values
Dropout PHASE TOC1 DPO This operand is the logical inverse of the above PKP
operand
Operate PHASE TOC1 OP The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing
Block PHASE TOC1 BLK The output of the comparator is set to the block function
Element Pickup Dig Element 1 PKP The input operand is at logic 1
(Digital)
Dropout Dig Element 1 DPO This operand is the logical inverse of the above PKP
operand
Operate Dig Element 1 OP The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing
Element Higher than Counter 1 HI The number of pulses counted is above the set number
(Digital Counter)
Equal to Counter 1 EQL The number of pulses counted is equal to the set number
Lower than Counter 1 LO The number of pulses counted is below the set number
Fixed On On Logic 1
Off Off Logic 0
The following table lists alphabetically the operands available for the relay.
Table 5-17: F35 FlexLogic operands
Operand type Operand syntax Operand description
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
DIRECT DEVICES DIRECT DEVICE 1On Flag is set, logic=1
DIRECT DEVICE 16On Flag is set, logic=1
DIRECT DEVICE 1Off Flag is set, logic=1
DIRECT DEVICE 16Off Flag is set, logic=1
DIRECT INPUT/ DIR IO CH1 CRC ALARM The rate of direct input messages received on channel 1 and failing the CRC
OUTPUT CHANNEL exceeded the user-specified level.
MONITORING DIR IO CH2 CRC ALARM The rate of direct input messages received on channel 2 and failing the CRC
5 SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
SELECTOR 1 BIT ALARM Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
SELECTOR 1 ALARM Position of selector 1 has been pre-selected but not acknowledged
SELECTOR 1 PWR ALARM Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
SELECTOR 2 Same set of operands as shown for SELECTOR 1
ELEMENT: SETTING GROUP ACT 1 Setting group 1 is active
Setting group SETTING GROUP ACT 2 Setting group 2 is active
SETTING GROUP ACT 3 Setting group 3 is active
SETTING GROUP ACT 4 Setting group 4 is active
SETTING GROUP ACT 5 Setting group 5 is active
SETTING GROUP ACT 6 Setting group 6 is active
ELEMENT: SH STAT GND STG1 PKP Stage 1 of the sub-harmonic stator ground protection has picked up
Sub-harmonic stator SH STAT GND STG1 DPO Stage 1 of the sub-harmonic stator ground protection has dropped out
ground fault detector SH STAT GND STG1 OP Stage 1 of the sub-harmonic stator ground protection has operated
SH STAT GND STG2 PKP Stage 2 of the sub-harmonic stator ground protection has picked up
SH STAT GND STG2 DPO Stage 2 of the sub-harmonic stator ground protection has dropped out
SH STAT GND STG2 OP Stage 2 of the sub-harmonic stator ground protection has operated
SH STAT GND OC PKP Ground over current element of the sub-harmonic stator ground protection
has picked up
SH STAT GND OC DPO Ground over current element of the sub-harmonic stator ground protection
has dropped out
SH STAT GND OC OP Ground over current element of the sub-harmonic stator ground protection
has operated
SH STAT GND TRB PKP Sub-harmonic stator ground module trouble has picked up
SH STAT GND TRB DPO Sub-harmonic stator ground module trouble has dropped out
SH STAT GND TRB OP Sub-harmonic stator ground module trouble has operated
ELEMENT: SRC1 50DD OP Source 1 disturbance detector has operated
Disturbance detector SRC2 50DD OP Source 2 disturbance detector has operated
SRC3 50DD OP Source 3 disturbance detector has operated
SRC4 50DD OP Source 4 disturbance detector has operated
SRC5 50DD OP Source 5 disturbance detector has operated
SRC6 50DD OP Source 6 disturbance detector has operated
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or ID of any of
these operands, the assigned name appears in the relay list of operands. The default names are shown in the FlexLogic
operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-18: FlexLogic gate characteristics
Gates Number of inputs Output is ‘1’ (= ON) if...
NOT 1 input is ‘0’
OR 2 to 16 any input is ‘1’
AND 2 to 16 all inputs are ‘1’
NOR 2 to 16 all inputs are ‘0’
NAND 2 to 16 any input is ‘0’
XOR 2 only one input is ‘1’
FlexLogic provides latches that by definition have a memory action, remaining in the set state after the set
input has been asserted. However, they are volatile; that is, they reset on the re-application of control power.
NOTE
When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value is
entered, so that all latches are reset automatically. If it is necessary to re-initialize FlexLogic during testing, for
example, power down the unit and then back up.
Virtual output 2
Set
state = On
Latch
Virtual input 1 OR #1 Reset
state = On
5
XOR
Digital element 1 Timer 2
state = Pickup Time Delay Operate output
OR #2
on dropout relay H1
Digital element 2 Timer 1
(200 ms)
state = Operated Time delay
AND on pickup
(800 ms)
Contact input H1c
state = Closed 827025A2.CDR
1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic
operators. If this is not possible, the logic must be altered until this condition is satisfied. Once done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If
the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25
inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs
from these two gates to AND(2).
Inspect each operator between the initial operands and final virtual outputs to determine if the output from the
operator is used as an input to more than one following operator. If so, the operator output must be assigned as a
virtual output.
For the example shown, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must therefore
be made a virtual output and assigned the next available number (that is, Virtual Output 3). The final output must also
be assigned to a virtual output as virtual output 4, which is programmed in the contact output section to operate relay
H1 (that is, contact output H1).
Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and
virtual output 4, shown as follows.
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
Digital element 1 OR #2 Virtual output 4
on dropout
state = Pickup
(200 ms)
827026A2.CDR
2. Prepare a logic diagram for the equation to produce virtual output 3, as this output is used as an operand in the virtual
output 4 equation (create the equation for every output that is used as an operand first, so that when these operands
are required they already have been evaluated and assigned to a specific virtual output). The logic for virtual output 3
is shown as follows with the final output assigned.
Figure 5-66: Logic for virtual output 3
5 Digital element 2
state= Operated
3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as
virtual output 3, shown as follows.
Figure 5-67: Logic for virtual output 4
Virtual output 1
state = On
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
OR #2 Virtual output 4
Digital element 1 on dropout
state = Pickup
(200 ms)
Timer 1
Virtual output 3 Time delay
state = On on pickup
(800 ms)
Contact input H1c
state = Closed
827028A2.CDR
4. Program the FlexLogic equation for virtual output 3 by translating the logic into available FlexLogic parameters. The
equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the
output end of the equation and work back towards the input, as shown in the following steps. It is also recommended
to list operator inputs from bottom to top. For demonstration, the final outputs are arbitrarily identified as parameter
99, and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic, it is suggested
that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared shown as follows.
Figure 5-68: FlexLogic worksheet
01
02
03
04
05
.....
97
98
99
827029A1.VSD
6. Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4.
– 99: The final output of the equation is virtual output 4, which is parameter “= Virt Op 4".
– 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for
the timer are established in the timer programming section.
– 97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
– 96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
– 95: The center input to OR #2 is operand “TIMER 1".
– 94: The input to timer 1 is operand “Virt Op 3 On".
– 93: The upper input to OR #2 is operand “LATCH (S,R)”.
– 92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR,
which is parameter “OR(4)”.
– 91: The lowest input to OR #1 is operand “Virt Op 3 On".
5 – 90: The input just above the lowest input to OR #1 is operand “XOR(2)”.
– 89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
– 88: The upper input to the XOR is operand “Virt Ip 1 On".
– 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
– 86: The upper input to OR #1 is operand “Virt Op 1 On".
– 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
Now check that the selection of parameters produce the required logic by converting the set of parameters into a
logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check.
FlexLogic entry:
85 Virt Op 4 On (VO4)
FlexLogic entry:
86 Virt Op 1 On (VO1)
FlexLogic entry:
87 Virt Op 2 On (VO2)
FlexLogic entry: Set
88 Latch
Virt Ip 1 On (VI1)
XOR OR Reset
FlexLogic entry:
89 Dig Element 1 (DE1) PKP
FlexLogic entry:
90 XOR (2 Input)
FlexLogic entry:
91 Virt Op 3 On (VO3)
OR T2 Virtual output 4
FlexLogic entry:
92 OR (4 Input)
FlexLogic entry:
93 Latch (Set, Reset)
FlexLogic entry:
94 Virt Op 3 On (VO3) T1
FlexLogic entry:
95 Timer 1
FlexLogic entry:
96 Cont Ip 2 On (H1c)
FlexLogic entry:
97 OR (3 Input)
FlexLogic entry:
98 Timer 2
FlexLogic entry:
99 =Virt Op 4 (VO4) 827031A2.CDR
7. Now write the complete FlexLogic expression required to implement the logic, making an effort to assemble the
5
equation in an order where Virtual Outputs that are used as inputs to operators are created before needed. In cases
where a lot of processing is required to perform logic, this can be difficult to achieve, but in most cases does not cause
problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by
sequential processing emphasizes the necessity to test the performance of FlexLogic before it is placed in service.
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the following
order:
DIG ELEM 2 OP
Cont Ip H1c On
NOT
AND(2)
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In this expression, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of
feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
There are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" element
is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the +/– key when editing FlexLogic
equations to quickly scan through the major parameter types.
5 TIMER 1 PICKUP
DELAY: 0
Range: 0 to 60000 in steps of 1
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE — Selects the time measurement unit.
TIMER 1 PICKUP DELAY — Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY — Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
5.6.7 FlexElements
SETTINGS FLEXLOGIC FLEXELEMENTS FLEXELEMENT 1(16)
FLEXELEMENT 1 FLEXELEMENT 1 Range: Disabled, Enabled
FUNCTION: Disabled
A FlexElement is a universal comparator used to monitor any analog actual value calculated by the relay or a net
difference of any two analog actual values of the same type. The effective operating signal can be treated as a signed
number or its absolute value can be used.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold, as
per your choice.
5
Figure 5-71: FlexElement logic
SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT MODE:
Enabled = 1
FLEXELEMENT 1 COMP MODE:
FLEXELEMENT 1 DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS
FxE 1 PKP
ACTUAL VALUE
FlexElement 1 OpSig
842004A4.CDR
FLEXELEMENT 1 +IN — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if
this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element
does not assert its output operands.
FLEXELEMENT 1 –IN — Specifies the second (inverted) input to the FlexElement. Zero is assumed as the input if this setting is
set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not
assert its output operands. This input is used to invert the signal if needed for convenience, or to make the element
respond to a differential signal, such as for a top-bottom oil temperature differential alarm. The element does not operate
if the two input signals are of different types, for example if one tries to use active power and phase angle to build the
effective operating signal.
The element responds directly to the differential signal if the FLEXELEMENT 1 INPUT MODE setting is set to “Signed” The
element responds to the absolute value of the differential signal if this setting is set to “Absolute.” Sample applications for
the “Absolute” setting include monitoring the angular difference between two phasors with a symmetrical limit angle in
both directions; monitoring power regardless of its direction, or monitoring a trend regardless of whether the signal
increases of decreases.
The element responds directly to its operating signal—as defined by the FLEXELEMENT 1 +IN, FLEXELEMENT 1 –IN and
FLEXELEMENT 1 INPUT MODE settings—if the FLEXELEMENT 1 COMP MODE setting is set to “Level.” The element responds to the
rate of change of its operating signal if the FLEXELEMENT 1 COMP MODE setting is set to “Delta.” In this case, the
FLEXELEMENT 1 dt UNIT and FLEXELEMENT 1 dt settings specify how the rate of change is derived.
FLEXELEMENT 1 DIRECTION — Enables the relay to respond to either high or low values of the operating signal. The following
figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP, and FLEXELEMENT 1 HYSTERESIS
settings.
Figure 5-72: FlexElement direction, pickup, and hysteresis
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
5 HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
842705A1.CDR
In conjunction with the FLEXELEMENT 1 INPUT MODE setting, the element can be programmed to provide two extra
characteristics, as shown in the following figure.
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig 5
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
842706A2.CDR
FLEXELEMENT 1 PICKUP — This setting specifies the operating threshold for the effective operating signal of the element. If
set to “Over,” the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under,” the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
FLEXELEMENT 1 HYSTERESIS — This setting controls the element dropout. Notice that both the operating signal and the
pickup threshold can be negative, facilitating applications such as reverse power alarm protection. The FlexElement can be
programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP setting is entered in
per-unit values using the following definitions of the base units.
Table 5-20: FlexElement base units
Unit Description
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs
DELTA TIME BASE = 1 µs
FREQUENCY fBASE = 1 Hz
PHASE ANGLE BASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
Unit Description
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE IBASE for the +IN and –IN inputs
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
FLEXELEMENT 1 HYSTERESIS — This setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement Direction, Pickup, and Hysteresis diagram.
FLEXELEMENT 1 dt UNIT — Specifies the time unit for the setting FLEXELEMENT 1 dt . This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 dt — Specifies duration of the time interval for the rate of change mode of operation. This setting is
applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 PKP DELAY — Specifies the pickup delay of the element.
FLEXELEMENT 1 RST DELAY — Specifies the reset delay of the element.
5 LATCH 1 TYPE:
Reset Dominant
Range: Reset Dominant, Set Dominant
The non-volatile latches provide a permanent logical flag that is stored safely and do not reset upon restart after the relay
is powered down. Typical applications include sustaining operator commands or permanently blocking relay functions,
such as Autorecloser, until a deliberate interface action resets the latch.
LATCH 1 TYPE — This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET — If asserted, the specified FlexLogic operands 'sets' Latch 1.
LATCH 1 RESET — If asserted, the specified FlexLogic operand 'resets' Latch 1.
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
5.7.3.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT
PHASE CURRENT PHASE TOC1 See page 5-161
PHASE TOC6
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed.” The
“Instantaneous” selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the
relay must coordinate with electromechanical relays.
IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
A tr
------------------------------- + B -------------------------------
-
I p
T = TDM ------------- , T RESET = TDM I 2 Eq. 5-8
I pickup
- –1 1 – --------------
I pickup
where
IEC curves
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
K tr
----------------------------------- ----------------------------------
-
T = TDM I Ipickup E – 1 , T RESET = TDM 1 – I I 2 Eq. 5-9
pickup
where
IAC curves
The curves for the General Electric type IAC relay family are derived from the formulae:
B D E
T = TDM A + --------------------------- + ---------------------------------2 + ---------------------------------3 tr
, T RESET = TDM ---------------------------- Eq. 5-10
I I pkp – C I I pkp – C I I pkp – C -
2
1 – I I pkp
where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input current
Ipkp = Pickup Current setting
A to E = constants
tr = characteristic constant
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-26: GE type IAC inverse time curve constants
IAC Curve Shape A B C D E tr
IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse 0.0900 0.7955 0.1000 –1.2885 7.9586 4.678
IAC Inverse 0.2078 0.8630 0.8000 –0.4180 0.1947 0.990 5
IAC Short Inverse 0.0428 0.0609 0.6200 –0.0010 0.0221 0.222
I2t curves
The curves for the I2t are derived from the formulae:
100 100
----------------------- -------------------------
T = TDM -------------
I 2 , T RESET = TDM I –2
- Eq. 5-11
I pickup --------------
I pickup
5 where
T = Operate Time (in seconds)
TDM = Multiplier Setting
I = Input Current
Ipickup = Pickup Current Setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
FlexCurves
The custom FlexCurves are described in detail in the FlexCurves section of this chapter. The curve shapes for the
FlexCurves are derived from the formulae:
I I
T = TDM FlexCurve Time at -------------- when -------------- 1.00 Eq. 5-12
I pickup I pickup
I I
T RESET = TDM FlexCurve Time at -------------- when -------------- 0.98 Eq. 5-13
I pickup I pickup
where
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
Recloser curves
The F35 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurve section in this
chapter for details.
5
5.7.3.3 Phase time overcurrent (ANSI 51P, IEC PTOC)
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT PHASE TOC1(6)
PHASE TOC 1 PHASE TOC1 Range: Disabled, Enabled
FUNCTION: Disabled
PHASE TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental
phasor magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times, and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator is cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint feature (when enabled). This is
accomplished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic
curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the voltage
restraint feature is disabled, the pickup level always remains at the setting value.
Figure 5-75: Phase time overcurrent voltage restraint characteristic
Multiplier for Pickup Current
1.0
0.9
0.8
0.7
0.6
0.5
5
0.4
0.3
0.2
0.1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR
SETTING
PHASE TOC1
BLOCK-A :
Off=0
SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
5
RESTRAINT: OR PHASE TOC1 OP
Enabled
827072A5.CDR
PHASE IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication
Instantaneous Overcurrent (IOC) Element Response to Saturated Waveforms in UR Series Relays (GET-8400A).
Figure 5-77: Phase instantaneous overcurrent 1 logic
SETTINGS FLEXLOGIC OPERANDS
SETTING
SETTING Pickup Delay PHASE IOC1 A PKP
Function
Pickup Reset Delay PHASE IOC1 A DPO
AND RUN TPKP PHASE IOC1 B PKP
1 = Enabled
IA > Pickup PHASE IOC1 B DPO
TRST PHASE IOC1 C PKP
AND RUN TPKP PHASE IOC1 C DPO
SETTING
Source IB > Pickup
TRST
= IA FLEXLOGIC OPERANDS
AND RUN TPKP
= IB PHASE IOC1 A OP
IC > Pickup PHASE IOC1 B OP
= IC TRST
PHASE IOC1 C OP
5 5.7.4.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEUTRAL CURRENT
NEUTRAL CURRENT NEUTRAL TOC1 See below
NEUTRAL IOC6
NEUTRAL TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and can be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section for details on curve setup, trip times, and reset operation). When the element is blocked, the time accumulator
resets according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator is cleared immediately.
Figure 5-78: Neutral time overcurrent 1 logic
SETTINGS
NEUTRAL TOC1
INPUT:
SETTING NEUTRAL TOC1
NEUTRAL TOC1
FUNCTION:
PICKUP:
NEUTRAL TOC1
CURVE:
5
Enabled = 1
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN PICKUP NEUTRAL TOC1 DPO
SOURCE:
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0 827034A4.VSD
NEUTRAL IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The neutral instantaneous overcurrent element can be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency
phasor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when
forming the operating quantity of the element as follows:
I op = 3 I_0 – K I_1 where K = 1 16 Eq. 5-16
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults
• Switch-off transients during double-line and three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection:
I op = 0.9375 I injected ; three-phase pure zero-sequence injection: I op = 3 I injected ).
Figure 5-79: Neutral IOC1 logic
SETTING
SETTINGS
Enabled=1
SETTING
NEUTRAL IOC1
PICKUP DELAY :
FLEXLOGIC OPERANDS
NEUTRAL IOC1
NEUTRAL IOC1 PICKUP: NEUTRAL IOC1 PKP
RESET DELAY :
SETTING NEUTRAL IOC1 DPO
AND RUN tPKP
tRST NEUTRAL IOC1 OP
NEUTRAL IOC1 BLOCK: 3( I_0 - K I_1 ) PICKUP
Off=0
SETTING
I_0
827035A5.CDR
WATTMETRIC GND FLT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The wattmetric zero-sequence directional element responds to power derived from zero-sequence voltage and current in
5
a direction specified by the element characteristic angle. The angle can be set within all four quadrants, and the power can
be active or reactive. Therefore, the element can be used to sense either forward or reverse ground faults in either
inductive, capacitive, or resistive networks. The inverse time characteristic allows time coordination of elements across the
network.
Typical applications include ground fault protection in solidly grounded transmission networks, grounded/ungrounded/
resistor-grounded/resonant-grounded distribution networks, or for directionalizing other non-directional ground elements.
WATTMETRIC GND FLT 1 VOLT — The element uses neutral voltage (that is, three times the zero-sequence voltage). This
setting allows selecting between the internally calculated neutral voltage or the externally supplied voltage (broken delta
VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel must be
identified by the user as a neutral voltage under the VT bank settings. This element operates when the auxiliary voltage is
configured as neutral.
WATTMETRIC GND FLT 1 OV PKP — This setting specifies the minimum zero sequence voltage supervising the directional
power measurement. Set this threshold higher than possible unbalance during normal operation of the system. Typically,
this setting is at 0.1 to 0.2 pu for the ungrounded or resonant grounded systems and at 0.05 to 0.1 pu for solidly or resistor-
grounded systems. When using externally supplied voltage via the auxiliary voltage channel, 1 pu is the nominal voltage of
this channel as per VT bank settings. When using internally calculated neutral voltage, 1 pu is the nominal phase to ground
voltage as per the VT bank settings.
WATTMETRIC GND FLT 1 CURR — The element responds to the neutral current (that is, three times zero-sequence current),
either calculated internally from the phase currents or supplied externally via the ground CT input from more accurate
sources such as the core balanced CT. This setting allows selecting the source of the operating current.
WATTMETRIC GND FLT 1 OC PKP — This setting specifies the current supervision level for the measurement of the zero-
sequence power.
WATTMETRIC GND FLT 1 OC PKP DEL — This setting specifies delay for the overcurrent portion of this element. The delay
applies to the WATTMETRIC 1 PKP operand driven from the overcurrent condition.
WATTMETRIC GND FLT 1 PWR PKP — This setting specifies the operating point of the element. A value of 1 pu is a product of
the 1 pu voltage as specified for the overvoltage condition of this element, and 1 pu current as specified for the
overcurrent condition of this element.
WATTMETRIC GND FLT 1 REF PWR — This setting is used to calculate the inverse time characteristic delay (defined by Sref in
the following equations). A value of 1 pu represents the product of a 1 pu voltage (as specified in the overvoltage condition
for this element) and a 1 pu current (as specified in the overcurrent condition for this element.
WATTMETRIC GND FLT 1 ECA — This setting adjusts the maximum torque angle of the element. The operating power is
calculated as:
S_op = Re V n I n 1 ECA Eq. 5-17
where
* indicates complex conjugate
By varying the element characteristic angle (ECA), the element can be made to respond to forward or reverse direction in
inductive, resistive, or capacitive networks as shown in the Wattmetric Characteristic Angle Response diagram.
WATTMETRIC GND FLT 1 PWR PKP DEL — This setting defines a definite time delay before the inverse time characteristic is
activated. If the curve selection is set as “Definite Time”, the element operates after this security time delay. If the curve
selection is “Inverse” or one of the FlexCurves, the element uses both the definite and inverse time timers simultaneously.
The definite time timer, specified by this setting, is used and when expires it releases the inverse time timer for operation
(torque control).
WATTMETRIC GND FLT 1 CURVE — Choose one of three methods to delay the operate signal once all conditions are met to
discriminate fault direction.
The “Definite Time” selection allows for a fixed time delay defined by the WATTMETRIC GND FLT 1 PWR PKP DEL setting.
5 The “Inverse” selection allows for inverse time characteristics delay defined by the following formula:
S ref
t = m -------- Eq. 5-18
S op
where
m is a multiplier defined by the multiplier setting
Sref is the multiplier setting
Sop is the operating power at the time
This timer starts after the definite time timer expires.
The four FlexCurves allow for custom user-programmable time characteristics. When working with FlexCurves, the
element uses the operate to pickup ratio, and the multiplier setting is not applied:
S op
t = FlexCurve -------- Eq. 5-19
S ref
Again, the FlexCurve timer starts after the definite time timer expires.
INDUCTIVE NETWORK
Vn Vn
In In
RESISTIVE NETWORK
Vn Vn
In In
In In
CAPACITIIVE NETWORK
Vn Vn
5
837804A1.CDR
WATTMETRIC GND FLT 1 MULTIPLIER — This setting is applicable if the WATTMETRIC GND FLT 1 CURVE is set to Inverse and
defines the multiplier factor for the inverse time delay.
5-170
5.7.6.1 Menu
GROUPED ELEMENTS
GROUND CURRENT
5.7.6 Ground current
SETTINGS SETTINGS
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
SOURCE: PWR PICKUP:
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
CURRENT: SETTING SETTINGS
OC PICKUP:
Calculated: Measured: WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
WATTMETRIC GND FLT 1
Neutral, In Ground, Ig ECA: OV PICKUP: CURVE:
SETTING
GROUND TOC1
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
VOLTAGE: S = V*conj (I*exp(-j*ECA)) SOP > PWR PICKUP WATTMETRIC GND FLT 1 REF PWR:
Calculated: Measured: 1 PWR PKP DEL:
WATTMETRIC GND FLT 1
Neutral, Vn Auxiliary, Vx MULTIPLIER:
VMAG > OV PICKUP
AND tPKP RUN
IMAG > OC PICKUP 0 FLEXLOGIC OPERAND
SREF
SETTINGS t = m× WATTMETRIC 1 OP
SOP
WATTMETRIC GND FLT SETTING
AND
1 FUNCTION:
WATTMETRIC GND FLT 1
Enabled = 1
OC PKP DEL:
WATT GND FLT 1 BLK:
AND
FLEXLOGIC OPERAND
Off = 0
tPKP WATTMETRIC 1 PKP
See below
0
837033A4.CDR
GROUND TOC6
GROUND TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
GROUND TOC1
RESET: Instantaneous
Range: Instantaneous, Timed 5
GROUND TOC1 BLOCK: Range: FlexLogic operand
Off
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the
fundamental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous”
(see the Inverse TOC Curve Characteristics section for details). When the element is blocked, the time accumulator resets
according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and the
element is blocked, the time accumulator is cleared immediately.
These elements measure the current that is connected to the ground channel of a CT/VT module. The
conversion range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel can be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE
GROUND IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The ground instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The
conversion range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel can be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
FLEXLOGIC OPERANDS
GROUND IOC1 PKP
SETTING GROUND IOIC DPO
GROUND IOC1
SETTINGS GROUND IOC1 OP
FUNCTION:
Enabled = 1 GROUND IOC1 PICKUP
SETTING DELAY:
GROUND IOC1 GROUND IOC1 RESET
SETTING
PICKUP: DELAY:
GROUND IOC1
AND RUN tPKP
SOURCE:
IG
IG PICKUP tRST
SETTING
GROUND IOC1
BLOCK:
827037A5.VSD
Off = 0
5.7.7.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEGATIVE SEQUENCE CURRENT
NEGATIVE SEQUENCE NEG SEQ TOC1 See below
CURRENT
The F35 provides two negative-sequence time overcurrent elements and two negative-sequence instantaneous
overcurrent elements. For information on the negative sequence time overcurrent curves, see the Inverse Time
Overcurrent Curves section earlier.
NEG SEQ TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The negative-sequence time overcurrent element can be used to determine and clear unbalance in the system. The input
for calculating negative-sequence current is the fundamental phasor value.
Two methods of resetting operation are available; “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator clears immediately.
Figure 5-84: Negative sequence TOC1 logic
SETTING
Off=0
t
5 SETTING
NEG SEQ IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The negative-sequence instantaneous overcurrent element is used as an instantaneous function with no intentional delay
or as a definite time function. The element responds to the negative-sequence current fundamental frequency phasor
magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance: a small
portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current magnitude
when forming the operating quantity:
I op = I_2 – K I_1 where K = 1 8 Eq. 5-20
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence
currents resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during three-phase faults
• Fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
I op = 0.2917 I injected ; three-phase injection, opposite rotation: I op = I injected ).
Figure 5-85: Negative sequence IOC1 logic
SETTING
SETTING
NEG SEQ IOC1 FUNCTION: NEG SEQ IOC1
SETTING PICKUP DELAY:
Enabled=1 FLEXLOGIC OPERANDS
NEG SEQ IOC1
NEG SEQ IOC1 PICKUP: NEG SEQ IOC1 PKP
RESET DELAY:
SETTING NEG SEQ IOC1 DPO
AND RUN tPKP
tRST NEG SEQ IOC1 OP
NEG SEQ IOC1 BLOCK: I_2 - K I_1 PICKUP
Off=0 5
SETTING
I_2 827058A6.CDR
5.7.8.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTS
VOLTAGE ELEMENTS PHASE See below
UNDERVOLTAGE1
PHASE
UNDERVOLTAGE3
where
T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
Vpickup = pickup level
Figure 5-86: Inverse time undervoltage curves
Time (seconds)
% of voltage pickup
842788A1.CDR
At 0% of pickup, the operating time equals the PHASE UNDERVOLTAGE DELAY setting.
PHASE UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
This element is used to give a time-delay operating characteristic versus the applied fundamental voltage (phase-to-
5
ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite time
element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting selects
the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage below
which the element is blocked (a setting of “0” allows a dead source to be considered a fault condition).
Figure 5-87: Phase undervoltage1 logic
SETTING
SETTING PHASE UV1
PHASE UV1 PICKUP:
FUNCTION: PHASE UV1
Enabled = 1 CURVE:
PHASE UV1
SETTING DELAY: FLEXLOGIC OPERANDS
AND
PHASE UV1 AND RUN VAG or VAB < PICKUP PHASE UV1 A PKP
BLOCK: t PHASE UV1 A DPO
Off = 0 PHASE UV1 A OP
V
SETTING
SETTING AND RUN VBG or VBC< PICKUP PHASE UV1 B PKP
PHASE UV1
t PHASE UV1 B DPO
PHASE UV1 SOURCE: MINIMUM VOLTAGE:
PHASE UV1 B OP
VAG or VAB < Minimum
Source VT = Delta V
}
VBG or VBC < Minimum
VAB AND RUN VCG or VCA< PICKUP PHASE UV1 C PKP
VCG or VCA < Minimum
VBC t PHASE UV1 C DPO
VCA PHASE UV1 C OP
Source VT = Wye V
FLEXLOGIC OPERAND
SETTING OR PHASE UV1 PKP
827039AC.CDR
NEUTRAL OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect
5 asymmetrical system voltage condition due to a ground fault or to the loss of one or two phases of the source. The
element responds to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary
voltage of the phase voltage channels entered under SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK PHASE
VT SECONDARY is the p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The NEUTRAL OV1 PICKUP DELAY setting applies only if the
NEUTRAL OV1 CURVE setting is “Definite time.” The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5-88: Neutral overvoltage1 logic
SETTING
NEUTRAL OV1
FUNCTION:
SETTING SETTING
Enabled=1
NEUTRAL OV1 PICKUP
NEUTRAL OV1 PICKUP: DELAY :
SETTING
AND RUN NEUTRAL OV1 RESET
DELAY :
NEUTRAL OV1 BLOCK:
NEUTRAL OV1 CURVE :
Off=0
FLEXLOGIC OPERANDS
3V_0< Pickup tPKP
t NEUTRAL OV1 OP
SETTING tRST
NEUTRAL OV1 DPO
NEUTRAL OV1 SIGNAL
SOURCE: NEUTRAL OV1 PKP
ZERO SEQ VOLT (V_0)
827848A3.CDR
AUX UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The F35 contains one auxiliary undervoltage element for each VT bank. This element monitors undervoltage conditions of
the auxiliary voltage.
The AUX UV1 PICKUP selects the voltage level at which the time undervoltage element starts timing. The nominal secondary
voltage of the auxiliary voltage channel entered under SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY is the per-unit base used when setting the pickup level.
The AUX UV1 DELAY setting selects the minimum operating time of the auxiliary undervoltage element.
Both AUX UV1 PICKUP and AUX UV1 DELAY settings establish the operating curve of the undervoltage element. The auxiliary 5
undervoltage element can be programmed to use either definite time delay or inverse time delay characteristics. The
operating characteristics and equations for both definite and inverse time delay are as for the phase undervoltage
element.
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element
is blocked.
Figure 5-89: Auxiliary undervoltage logic
SETTING
AUX UV1 SETTING
FUNCTION:
AUX UV1 PICKUP:
Enabled=1
827849A3.CDR
AUX OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The F35 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
SETUP AC INPUTS VOLTAGE BANK X5 AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the
pickup level.
Figure 5-90: Auxiliary overvoltage logic
SETTING
AUX OV1
FUNCTION:
SETTING
Enabled=1
AUX OV1 PICKUP: SETTING
5
SETTING
AND RUN AUX OV1 PICKUP
DELAY :
AUX OV1 BLOCK:
AUX OV1 RESET
Off=0 DELAY :
FLEXLOGIC OPERANDS
Vx < Pickup tPKP
SETTING tRST AUX OV1 OP
AUX OV1 DPO
AUX OV1 SIGNAL
SOURCE: AUX OV1 PKP
AUXILIARY VOLT (Vx)
827836A3.CDR
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista software A protection summary is
displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it can be assigned directly from the trip bus menu.
Figure 5-91: Trip bus fields in the protection summary 5
TRIP BUS 1 LATCHING — This setting enables or disables latching of the trip bus output. This is typically used when lockout is
required or user acknowledgement of the relay response is required.
TRIP BUS 1 RESET — The trip bus output is reset when the operand assigned to this setting is asserted. Note that the RESET OP
operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via
communications resets the trip bus output.
Figure 5-92: Trip bus logic
SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
5
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.
SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled.
SETTING GROUPS BLK — Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON — Selects a FlexLogic operand which, when set, makes the particular setting
group active for use by any grouped element. A priority scheme ensures that only one group is active at a given time — the
highest-numbered group that is activated by its ACTIVATE ON parameter takes priority over the lower-numbered groups.
There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes active if no
other group is active.
SETTING GROUP 1 NAME to SETTING GROUP 6 NAME — Allows the user to assign a name to each of the six settings groups.
Once programmed, this name appears on the second line of the GROUPED ELEMENTS SETTING GROUP 1(6) menu display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic equation (see the following figure) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a particular
settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings group.
Figure 5-93: Example of FlexLogic control of a setting group
1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)
3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4
5
PHASE TOC1 PKP
NOT
5
6 PHASE TOC2 PKP
7 NOT
8 AND (3)
9 = VIRT OP 1 (VO1)
10 END
842789A1.CDR
A setting group selection can also be made by the IEC 61850 MMS service SelectActiveSG to the control block @Master/
LLN0.SGCB. The priority scheme mentioned makes active the highest numbered group selected by SelectActiveSG or the
GROUP ACTIVATE ON settings. The SelectActiveSG selection has a default value of 1, so until a higher SelectActiveSG
selection is received, the GROUP ACTIVATE ON settings control the active group.
The most recent SelectActiveSG selection is preserved while the UR is powered down or reset.
If it becomes necessary to cancel the SelectActiveSG selection without using a SelectActiveSG service request, change the
SETTING GROUPS FUNCTION setting to Disabled. This resets the SelectActiveSG selection to 1.
5 SELECTOR 1 EVENTS:
Disabled
Range: Disabled, Enabled
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows
setting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after
time-out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile
memory. Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word
(user setting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input
being out of range.
SELECTOR 1 FULL RANGE — This setting defines the upper position of the selector. When stepping up through available
positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-bit control
word for programming the selector to a desired position, the change would take place only if the control word is within the
range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established by setting the
SELECTOR ALARM FlexLogic operand for three seconds.
SELECTOR 1 TIME-OUT — This setting defines the time-out period for the selector. This value is used by the relay in the
following two ways. When the SELECTOR STEP-UP MODE is “Time-out,” the setting specifies the required period of inactivity
of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-UP MODE is
“Acknowledge,” the setting specifies the period of time for the acknowledging input to appear. The timer is re-started by
any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT timer expires;
otherwise, the change does not take place and an alarm is set.
SELECTOR 1 STEP-UP — This setting specifies a control input for the selector switch. The switch is shifted to a new position at
each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1 FULL RANGE) to
the first (position 1). Consecutive pulses of this control operand must not occur faster than every 50 ms. After each rising
edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1: POS Z CHNG INITIATED target
message is displayed, where Z the pre-selected position. The message is displayed for the time specified by the FLASH
MESSAGE TIME setting. The pre-selected position is applied after the selector times out (“Time-out” mode), or when the
acknowledging signal appears before the element times out (“Acknowledge” mode). When the new position is applied, the
relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is
configured as the stepping up control input.
SELECTOR 1 STEP-UP MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge,” the selector
changes its position only after the intent is confirmed through a separate acknowledging signal. If the acknowledging
signal does not appear within a pre-defined period of time, the selector does not accept the change and an alarm is
established by setting the SELECTOR STP ALARM output FlexLogic operand for three seconds.
SELECTOR 1 ACK — This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the last
activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
SELECTOR 1 3BIT A0, A1, and A2 — These settings specify a three-bit control input of the selector. The three-bit control word
pre-selects the position using the following encoding convention:
A2 A1 A0 Position
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6 5
1 1 1 7
The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the three-
bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out,” the pre-selected position is applied in
SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is “Acknowledge,”
the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2) lock-out
mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit control
sequence is initiated, the stepping up input is inactive.
SELECTOR 1 3BIT MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector changes
its position after a pre-defined period of inactivity at the control input. The change is automatic and does not require
explicit confirmation to change the selector position. When set to “Acknowledge,” the selector changes its position only
after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a pre-defined
period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT ALARM FlexLogic operand
for three seconds.
SELECTOR 1 3BIT ACK — This setting specifies an acknowledging input for the three-bit control input. The pre-selected
position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the
“Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR TIME-
OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and three-bit
control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK , accordingly).
SELECTOR 1 POWER-UP MODE — This setting specifies the element behavior on power up of the relay.
When set to “Restore,” the last position of the selector (stored in the non-volatile memory) is restored after powering up the
relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and an alarm
is set (SELECTOR 1 PWR ALARM).
When set to “Synchronize,” the selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range), then the selector
switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR ALARM).
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch attempts to restore the position stored in the relay memory. The “Synch/
Restore” mode is useful for applications where the selector switch is employed to change the setting group in redundant
(two relay) protection schemes.
SELECTOR 1 EVENTS — If enabled, the following events are logged:
The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.
STEP-UP
T T
3BIT A0
3BIT A1
3BIT A2
T T
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
5
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842737A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
5 POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842736A1.CDR
Application example
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group is to be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity
of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu:
SETTING GROUPS FUNCTION: “Enabled”
SETTING GROUPS BLK : “Off”
GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2"
GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"
5.8.5 Underfrequency
SETTINGS CONTROL ELEMENTS UNDERFREQUENCY UNDERFREQUENCY 1(6)
UNDERFREQUENCY 1 UNDFREQ 1 FUNCTION: Range: Disabled, Enabled
Disabled
UNDERFREQ 1 FUNCTION:
Enabled=1
5.8.6 Autoreclose
SETTINGS CONTROL ELEMENTS AUTORECLOSE AUTORECLOSE 1(6)
AUTORECLOSE 1 AR1 FUNCTION: Range: Disabled, Enabled
Disabled
The maximum number of autoreclosure elements available is equal to the number of installed CT banks.
The autoreclosure feature is intended for use with transmission and distribution lines, in three-pole tripping schemes for
single breaker applications. Up to four selectable reclosures "shots" are possible prior to locking out. Each shot has an
independently settable dead time. The protection settings can be changed between shots if required, using FlexLogic.
Logic inputs are available for disabling or blocking the scheme.
Faceplate panel LEDs indicate the state of the autoreclose scheme as follows:
• Reclose Enabled — The scheme is enabled and can reclose if initiated
• Reclose Disabled — The scheme is disabled
• Reclose In Progress — An autoreclosure has been initiated but the breaker has not yet been signaled to close
• Reclose Locked Out — The scheme has generated the maximum number of breaker closures allowed and, as the fault
persists, does not close the breaker again; known as "Lockout." The scheme can also be sent in "Lockout" when the
incomplete sequence timer times out or when a block signal occurs while in "reclose in progress." The scheme must be
reset from Lockout in order to perform reclose for further faults.
The reclosure scheme is considered enabled when all of the following conditions are true:
• The AR1 FUNCTION is set to “Enabled”
5 •
•
The scheme is not in the "Lockout" state
The "Block" input is not asserted
• The AR1 BLK TIME UPON MNL CLS timer is not active
The autoreclose scheme is initiated by a trip signal from any selected protection feature operand. The scheme is initiated
provided the circuit breaker is in the closed state before protection operation.
The reclose-in-progress (RIP) is set when a reclosing cycle begins following a reclose initiate signal. Once the cycle is
successfully initiated, the RIP signal seals-in and the scheme continues through its sequence until one of the following
conditions is satisfied:
• The close signal is issued when the dead timer times out, or
• The scheme goes to lockout
While RIP is active, the scheme checks that the breaker is open and the shot number is below the limit, and then begins
measuring the dead time.
Each of the four possible shots has an independently settable dead time. Two additional timers can be used to increase the
initial set dead times 1 to 4 by a delay equal to AR1 DELAY 1 or AR1 DELAY 2 or the sum of these two delays depending on the
selected settings. This offers enhanced setting flexibility using FlexLogic operands to turn the two additional timers “on”
and “off.” These operands can possibly include AR1 SHOT CNT =n, SETTING GROUP ACT 1, and so on. The autoreclose provides
up to maximum 4 selectable shots. Maximum number of shots can be dynamically modified through the settings AR1
REDUCE MAX TO 1 (2, 3), using the appropriate FlexLogic operand.
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs:
• The maximum shot number was reached
• A "Block" input is in effect (for instance, Breaker Failure or bus differential protection operated)
• The "Incomplete Sequence" timer times out
The recloser is latched in the Lockout state until a "reset from lockout" signal is asserted, either from a manual close of the
breaker or from a manual reset command (local or remote). The reset from lockout can be accomplished by operator
command, by manually closing the breaker, or whenever the breaker has been closed and stays closed for a preset time.
After the dead time elapses, the scheme issues the close signal. The close signal is latched until the breaker closes or the
scheme goes to Lockout.
A reset timer output resets the recloser following a successful reclosure sequence. The reset time is based on the breaker
"reclaim time," which is the minimum time required between successive reclose sequences.
5.8.6.1 Settings
AR1 INITIATE — Selects the FlexLogic operand that initiates the scheme, typically the trip signal from protection.
AR1 BLOCK — Selects the FlexLogic operand that blocks the autoreclosure initiate (it can be from the breaker failure, bus
differential protection, and so on).
AR1 MAX NUMBER OF SHOTS — Specifies the number of reclosures that can be attempted before reclosure goes to “Lockout”
because the fault is permanent.
AR1 REDUCE MAX TO 1(3) — Selects the FlexLogic operand that changes the maximum number of shots from the initial
setting to 1, 2, or 3, respectively.
AR1 MANUAL CLOSE — Selects the logic input set when the breaker is manually closed.
AR1 MNL RST FRM LO — Selects the FlexLogic operand that resets the autoreclosure from Lockout condition. Typically this is
a manual reset from lockout, local or remote.
AR1 RESET LOCKOUT IF BREAKER CLOSED — This setting allows the autoreclose scheme to reset from Lockout if the breaker
has been manually closed and stays closed for a preset time. In order for this setting to be effective, disable the next
setting (AR1 RESET LOCKOUT ON MANUAL CLOSE).
AR1 RESET LOCKOUT ON MANUAL CLOSE — This setting allows the autoreclose scheme to reset from Lockout when the
breaker is manually closed regardless if the breaker remains closed or not. This setting overrides the previous setting (AR1
RESET LOCKOUT IF BREAKER CLOSED).
AR1 BLK TIME UPON MNL CLS — The autoreclose scheme can be disabled for a programmable time delay after the
associated circuit breaker is manually closed. This prevents reclosing onto a fault after a manual close. This delay must be
longer than the slowest expected trip from any protection not blocked after manual closing. If no overcurrent trips occur
after a manual close and this time expires, the autoreclose scheme is enabled.
5
AR1 DEAD TIME 1 to AR1 DEAD TIME 4 — These are the intentional delays before first, second, third, and fourth breaker
automatic reclosures (1st, 2nd, and 3rd shots), respectively. Set them longer than the estimated deionizing time following a
three pole trip.
AR1 ADD DELAY 1 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 1) to the initial set
Dead Time (1 to 4). When this setting is “Off,” Delay 1 is by-passed.
AR1 DELAY 1 — This setting establishes the extent of the additional dead time Delay 1.
AR1 ADD DELAY 2 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 2) to the initial set
Dead Time (1 to 4). When this setting is “Off”, Delay 2 is by-passed.
AR1 DELAY 2 — This setting establishes the extent of the additional dead time Delay 2.
AR1 RESET LOCKOUT DELAY — This setting establishes how long the breaker stays closed after a manual close command, in
order for the autorecloser to reset from Lockout.
AR1 RESET TIME — A reset timer output resets the recloser following a successful reclosure sequence. The setting is based
on the breaker "reclaim time," which is the minimum time required between successive reclose sequences.
AR1 INCOMPLETE SEQ TIME — This timer defines the maximum time interval allowed for a single reclose shot. It is started
whenever a reclosure is initiated and is active when the scheme is in the "reclose-in-progress" state. If all conditions
allowing a breaker closure are not satisfied when this time expires, the scheme goes to Lockout.
This timer must be set to a delay less than the reset timer.
NOTE
5-194
FLEXLOGIC OPERAND
AR1 BLK FROM MAN CLS
CONTROL ELEMENTS
FLEXLOGIC OPERAND
Enabled
AR1 ENABLED (Default)
SETTING
Off = 0
AR Initiate
Bkr Is Closed
Shot cnt = Max
SETTING (Default)
To sheet 2
SETTING
AR1 INCOMPLETE SEQ
SETTING AR1 RESET LOCKOUT TIME:
AR1 RESET LOCKOUT IF DELAY:
OR LO
BREAKER CLOSED: OR
AND LO
O
On=1 0 AND
SETTING
AR1 RESET LOCKOUT ON
MANUAL CLOSE:
AND OR
On=1 AND
SETTING
Reset From LO
AR1 MNL RST FROM LO:
827081AE.CDR
Off = 0
S
FLEXLOGIC OPERAND
Latch AR1 CLOSE
SHOT COUNTER
FLEXLOGIC OPERANDS
OR R
Shot cnt = 4 AR1 SHOT CNT = 4
Increment
Close Shot cnt = 3 AR1 SHOT CNT = 3
shot
Bkr is Closed counter Shot cnt = 2 AR1 SHOT CNT = 2
Shot cnt = 1 AR1 SHOT CNT = 1
To 100 ms Reset shot
AR Initiate SETTING OR counter Shot cnt = 0 FLEXLOGIC OPERAND
Sheet 1
AND OR AR1 SHOT CNT = 0
LO AR1 RESET TIME:
Reset from LO OR
AND O
MAX = 1 AND
OR AND
MAX = 4
Figure 5-99: Autorecloser logic (Sheet 2 of 2)
AND
AND
SETTING
Off = 0
SETTING
Off = 0
SETTING 827082A7.CDR
AR1 REDUCE MAX TO 3:
Off = 0
5-195
CONTROL ELEMENTS
5
5
5-196
CONTROL ELEMENTS
BREAKER
STATUS
PROT TIME OPENING TIME CLOSING TIME PROT TIME OPENING TIME
BKR CLOSED
BKR OPEN
AUTO RECLOSE
DEAD TIME
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name to be referenced in any target message, a blocking input from any selected FlexLogic operand,
5
and a timer for pickup and reset delays for the output operand.
DIGITAL ELEMENT 1 INPUT — Selects a FlexLogic operand to be monitored by the digital element.
DIGITAL ELEMENT 1 PICKUP DELAY — Sets the required time delay from element pickup to element operation. If a pickup delay
is not required, set to "0," To avoid nuisance alarms, set the delay greater than the operating time of the breaker.
DIGITAL ELEMENT 1 RESET DELAY — Sets the time delay to reset. If a reset delay is not required, set to “0.”
DIGITAL ELEMENT 1 PICKUP LED — This setting enables or disabled the digital element pickup LED. When set to “Disabled,” the
operation of the pickup LED is blocked.
Figure 5-101: Digital element logic
SETTING
DIGITAL ELEMENT 01
FUNCTION: SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0 827042A2.VSD
As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the Cont
Op 1 VOn FlexLogic operand is set (for contact input 1—corresponding operands exist for each contact output). If the output
circuit has a high resistance or the DC current is interrupted, the trickle current drops below the threshold and the Cont Op 1
VOff FlexLogic operand is set. Consequently, the state of these operands can be used as indicators of the integrity of the
circuits in which form-A contacts are inserted.
H1a
I
H1b DC–
5 V
H1c 52a Trip coil
DC+
I = current monitor
V = voltage monitor 827073A2.CDR
Assume the output contact H1 is a trip contact. Using the contact output settings, this output is given an ID name; for
example, “Cont Op 1." Assume a 52a breaker auxiliary contact is connected to contact input H7a to monitor breaker status.
Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is
closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown).
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring
and solid-state contact with voltage monitoring.
NOTE
There are eight identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions
from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of
an external contact (for example, breaker auxiliary switch), or pulses from a watt-hour meter.
COUNTER 1 UNITS — Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted. The
units label appears in the corresponding actual values status.
COUNTER 1 PRESET — Sets the count to a required preset value before counting operations begin, as in the case where a
5 substitute relay is to be installed in place of an in-service relay, or while the counter is running.
COUNTER 1 COMPARE — Sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set value.
COUNTER 1 UP — Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when the
accumulated value is at the limit of +2,147,483,647 counts, the counter rolls over to –2,147,483,648.
COUNTER 1 DOWN — Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is received
when the accumulated value is at the limit of –2,147,483,648 counts, the counter rolls over to +2,147,483,647.
COUNTER 1 BLOCK — Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked.
CNT1 SET TO PRESET — Selects the FlexLogic operand used to set the count to the preset value. The counter sets to the
preset value in the following situations:
• When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled and
CNT1 SET TO PRESET operand is 0, the counter sets to 0)
• When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO PRESET
changing from 1 to 0 while the counter is running has no effect on the count)
• When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 1
(when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 0, the
counter sets to 0)
COUNTER 1 RESET — Selects the FlexLogic operand for setting the count to either “0” or the preset value depending on the
state of the CNT1 SET TO PRESET operand.
COUNTER 1 FREEZE/RESET — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a
separate register with the date and time of the operation, and resetting the count to “0.”
COUNTER 1 FREEZE/COUNT — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a
separate register with the date and time of the operation, and continuing counting. The present accumulated value and
captured frozen value with the associated date/time stamp are available as actual values. If control power is interrupted,
the accumulated and frozen values are saved into non-volatile memory during the power-down operation.
SETTING
COUNTER 1 FUNCTION:
SETTINGS
Enabled = 1
COUNTER 1 NAME:
SETTING AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
COUNTER 1 UP:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO
SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE
This feature allows switching between two input arguments defined by 8 bits each. The bits are specified by FlexLogic
operands. The feature could be viewed as an integrated two-position switch for 8 logic signals.
Typically this element is applied in conjunction with the Digitizer and 8-bit Comparator features.
8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7 — These settings specify FlexLogic operands that constitute the first (A) input of the
switch. These operands are routed to the output operands if the control input is in the "Off" position.
BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7 — These settings specify FlexLogic operands that constitute the second (B) input of the
switch. These operands are routed to the output operands if the control input is in the "On" position.
8BIT SW 1 CONTROL — This setting specifies FlexLogic operands to control the routing between the A and B inputs of the
switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand is in the
"On" state, the second (B) input is switched to the output. The switching takes place instantaneously.
Figure 5-105: 8-bit switch logic
SETTING
8BIT SWITCH 1
FUNCTION:
Enabled = 1 RUN
SETTINGS
8BIT SW 1 ARG A0:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B0: 8BIT SWITCH 1 BIT 0
Off = 0
8BIT SW 1 ARG A1:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B1: 8BIT SWITCH 1 BIT 1
Off = 0
8BIT SW 1 ARG A2:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B2: 8BIT SWITCH 1 BIT 2
Off = 0
8BIT SW 1 ARG A3:
SETTING
8BIT SW 1 CONTROL:
Off = 0
842017A1.CDR
BREAKER 6
ARCING CURRENT
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element
calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared
passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase
and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an
output operand to “1.” The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays, and the breaker mechanism. For maximum measurement accuracy, measure the interval between change-of-state
of the operand (from 0 to 1) and contact separation for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function.
Correction is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES RECORDS MAINTENANCE
BREAKER 1(6) menus.
BKR 1 ARC AMP INT-A(C) — Select the same output operands that are configured to operate the output relays used to trip the
breaker. In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A,
B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations
for the poles that are actually tripped.
BKR 1 ARC AMP DELAY — This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
BKR 1 ARC AMP LIMIT — Selects the threshold value above which the output operand is set.
Total Area =
Breaker
Arcing
5
Current
(kA·cycle)
Programmable
Start Delay 100 ms
Start Stop
Integration Integration
SETTING
AND
BREAKER 1 ARCING
SETTING
AMP FUNCTION:
Enabled=1 BREAKER 1 ARCING
AMP DELAY: 100 ms
SETTING OR 0 0
BREAKER 1 ARCING
AMP BLOCK:
Off=0
AND
SETTINGS
BREAKER 1 ARCING
AMP INIT-A:
Off=0
BREAKER 1 ARCING
AMP INIT-B:
Off=0 OR
BREAKER 1 ARCING
AND RUN
SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE: AND RUN Accumulator BREAKER 1 ARCING
IA IA 2-Cycle AMP LIMIT: FLEXLOGIC OPERANDS
Select
2
IB Integrate IB 2-Cycle Highest KA * Cycle Limit BKR1 ARC OP
Figure 5-107: Breaker arcing current logic
2 Value
IC IC -Cycle BKR1 ARC DPO
AND RUN
COMMAND
5-205
CONTROL ELEMENTS
5
CONTROL ELEMENTS CHAPTER 5: SETTINGS
10
8
6
4
current (amps)
2
0.01 0.03
0 time (ms)
0.02 0.05
–2
–4
–6
–8
OPERATE
–10
834764A1.CDR
The breaker restrike algorithm responds to a successful interruption of the phase current following a declaration of
capacitor bank offline as per the breaker pole indication. If a high-frequency current with a magnitude greater than the
threshold is resumed at least ¼ of a cycle later than the phase current interruption, then a breaker restrike condition is
declared in the corresponding phase and the BRK RESTRIKE 1 OP operand asserts for a short period of time. The user can add
counters and other logic to facilitate the decision making process as to the appropriate actions upon detecting a single
restrike or a series of consecutive restrikes.
A restrike event (FlexLogic operand) is declared if all of the following hold:
• The current is initially interrupted
• The breaker status is open
• An elevated high frequency current condition occurs and the current subsequently drops out again
The algorithm is illustrated in the following state machine diagram.
Figure 5-109: Algorithm illustration of state machine to detect restrike
Breaker open
command or breaker
open state
Capacitor bank
offline
Breaker
close
Current
Capacitor bank
interruption
Breaker online
(overcurrent)
close
High-frequency
elevated current Breaker close
Current
interruption
(overcurrent)
5
Restrike detected:
OP state asserted
834768A1.CDR
In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes is picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
BREAKER RESTRIKE 1 FUNCTION — Enables and disables operation of the breaker restrike detection element.
BRK RSTR 1 BLOCK — Blocks operation of the breaker restrike detection element.
BREAKER RESTRIKE 1 SOURCE — Selects the source of the current for this element. This source must have a valid CT bank
assigned.
BREAKER RESTRIKE 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of CT nominal
current.
BREAKER RESTRIKE 1 RESET DELAY — Specifies the reset delay for this element. When set to “0 ms,” then FlexLogic operand is
picked up for only 1/8th of the power cycle.
BRK RSTR 1 BRK OPEN — Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic “1” when
the breaker is open.
BRK RSTR 1 OPEN CMD — Assigns a FlexLogic operand indicating a breaker open command. It must be logic “1” when the
breaker is opened, either manually or from protection logic.
BRK RSTR 1 CLS CMD — Assigns a FlexLogic operand indicating a breaker close command. It must be logic “1” when the
breaker is closed.
SETTING AND
BKR RSTR 1 BLK
= Off SETTING SETTING
BREAKER RESTRIKE 1 PICKUP BREAKER RESTRIKE 1
RUN RESET DELAY
SETTING 0
BREAKER RESTRIKE 1 RUN Restrike detection logic
SOURCE ARMED TRST
Current interruption
= IA detection logic 0
FLEXLOGIC OPERANDS
= IB
Imag < 0.05 pu TRST BKR RESTRIKE 1 OP A
= IC
for t > ¼ cycle 0 BKR RESTRIKE 1 OP B
BKR RESTRIKE 1 OP C
SETTING RESET TRST
BKR RSTR 1 BKR OPEN
= Off
FLEXLOGIC OPERAND
OR BKR RESTRIKE 1 OP
SETTING OR
BKR RSTR 1 OPEN CMD
= Off
AND
SETTING
BKR RSTR 1 CLS CMD
= Off 834012A1.CDR
There are two incipient cable fault detection elements for each CT/VT module in the relay.
Before a permanent cable fault occurs, there are usually signs of degrading insulation manifesting itself as a short, mostly
half-cycle spikes asserting at the phase voltage peak. Due to shortness of such spikes, they are not usually detected by the
instantaneous protection of the feeder, which operates on the RMS or fundamental component of the phase current with a
relatively high pickup.
The number of detected incipient faults in each phase is counted and available in the ACTUAL VALUES STATUS
INCIPIENT FAULT menus. The counters can be reset with the COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT
COUNTERS command.
Changes to any of the incipient cable fault detector settings resets of the number of the incipient faults
detected to zero.
NOTE
To provide a clear timing indication when the incipient fault occurred, the incipient fault event is time-stamped
with the time the fault actually occurred. However, the FlexLogic operand is asserted four cycles later, when the
incipient fault pattern is confirmed and therefore detected.
The figure illustrates a recorded field case of an incipient phase B fault. The top portion of the figure shows the raw A, B,
and C currents. The bottom portion shows the neutral current (blue) and reveals the fault period from under the load and
the superimposed phase B current (red). The superimposed current shows two fault current blips as the data slides through
the two-cycle memory window. During the actual fault, the neutral current and the superimposed phase B currents closely
correspond, confirming the incipient fault hypothesis and identifying the affected phase.
Figure 5-111: Illustration of the incipient fault detector algorithm
1.0
Phase C
0
–0.5
Phase A
Phase B 5
0.62 0.64 0.66 0.68 0.70 0.72 0.74
1.0
–1.0
IFB
–2.0
0.62 0.64 0.66 0.68 0.7 0.72 0.74
832774A1.CDR
The following settings are available for each incipient cable fault detector.
INCIPIENT FAULT 1 FUNCTION — This setting enables and disables operation of the incipient fault detection element.
INCIPNT FLT 1 BLOCK — Blocks operation of the incipient cable fault detector element. Assertion of the FlexLogic operand
assigned to this setting blocks operation.
INCIPIENT FAULT 1 SOURCE — Selects a current source for the incipient cable fault detector element. This source must be
assigned a valid CT bank.
INCIPIENT FAULT 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of the CT nominal
current.
INCIPNT FLT 1 MODE — There are two modes of operation available for the incipient cable fault detector element. In the
“Number of counts” mode, a trip is initiated only after the selected number of faults is detected. In the “Counts per window”
mode, a trip is initiated only after the selected number of faults is detected within the time specified by the INCIPNT FLT 1
DETECT WINDOW setting.
INCIPIENT FLT 1 TRIP COUNTS NUMBER — Selects the number of faults required to initiate a trip.
INCIPNT FLT 1 DETECT WINDOW — Specifies a time window for “Counts per window” mode of operation.
INCIPIENT FAULT 1 RESET DELAY — Specifies a reset time for the output after the trip is initiated.
ACTUAL VALUES
INCIPIENT FAULT 1 PH A
FAULTS
INCIPIENT FAULT 1 PH B
FAULTS
COMMAND INCIPIENT FAULT 1 PH C
CLEAR INCIPIENT FAULT FAULTS
COUNTERS
RESET
= Yes
832028A1.CDR
To distinguish between single-phase disappearance and system disturbance in all three phases (such as load change and
switching), the broken conductor element monitors the change in all three phase currents at the present instance and at
four cycles previous. It also monitors changes in the I_2 / I_1 ratio, I_1 minimum, and I_1 maximum.
Do not use the broken conductor function to respond to fault transients and single-pole tripping/reclosing conditions.
Therefore, program the time delay to a sufficient length to ensure coordination with the breaker dead time of the recloser
function.
BROKEN CONDUCTOR 1 FUNCTION — This setting enables and disables the broken conductor function.
BROKEN CONDUCTOR 1 SOURCE — Selects a signal source used to provide three-phase current inputs to this function.
BROKEN CONDUCTOR 1 I2/I1 RATIO — This setting specifies the ratio of negative-sequence current to positive-sequence
current. When one phase conductor is broken, the I_2 / I_1 ratio with a balanced remaining two phases is 50%. So
normally you this setting below 50% (for example, to 30%).
BROKEN CONDUCTOR 1 I1 MIN — This setting specifies the minimum positive-sequence current supervision level. Ensure this
setting is programmed to a sufficient level to prevent I_2 / I_1 from erratic pickup due to a low I_1 signal. However, do not
set this setting too high, since the broken conductor condition cannot be detected under light load conditions when I_1 is
less than the value specified by this setting.
BROKEN CONDUCTOR 1 I1 MAX — This setting specifies the maximum I_1 level allowed for the broken conductor function to
operate. When I_1 exceeds this setting, this it is considered a fault. In order for this function to not respond to any fault
conditions, set this setting to less than the maximum load current.
BROKEN CONDUCTOR 1 PKP DELAY — This setting specifies the pickup time delay for this function to operate after assertion
of the broken conductor pickup FlexLogic operand.
5-212
CONTROL ELEMENTS
SETTINGS
BROKEN CONDUCTOR 1
FUNCTION:
Enabled = 1
BROKEN CONDCT 1 BLK: AND
SETTINGS
Off = 0
BROKEN CONDUCTOR 1
I1 MAX:
BROKEN CONDUCTOR 1
SETTING I2/I1 RATIO:
SETTINGS
BROKEN CONDUCTOR 1 Run
BROKEN CONDUCTOR 1
SOURCE: I1 MIN:
|I1 | < I1 MAX SETTING
I2 Run |I2| / |I1| > RATIO
BROKEN CONDUCTOR 1
I1 |I1 > I1 MIN I1 MAX:
Ia |Ia| < I1 MIN FLEXLOGIC OPERAND
tPKP
|Ib| < I1 MIN AND BROKEN CONDUCT 1 OP
Ib AND
0
Ic |Ic| < I1 MIN
|Ia’| - |Ia| > 0.05 pu
Ic
|Ib’| - |Ib| > 0.05 pu 2 cyc
AND OR
|Ic’| - |Ic| > 0.05 pu
0 OR
Where I’ is four cycles old
FLEXLOGIC OPERAND
BROKEN CONDUCT 1 PKP
AND
Figure 5-113: Broken conductor detection logic
The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect
different elements of the power system. The cold curve characteristic is applied when the previous averaged load current
over the last 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base
current, then the hot curve characteristic is applied.
The IEC255-8 cold curve is defined as follows:
2
I
t op = op ln ----------------------
2
-
2
Eq. 5-22
I – kI B
where
top = time to operate
τop = thermal protection trip time constant
I = measured overload RMS current
Ip = measured load RMS current before overload occurs
k = IEC 255-8 k-factor applied to IB, defining maximum permissible current above nominal current
IB = protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x IB) is limited to 8, even when
realistically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
2
kI B
t rst = rst ln ------------------------
2 2
- + T min Eq. 5-24
I – kI B
where
τrst = thermal protection trip time constant
Tmin = a minimum reset time setting
Figure 5-114: IEC 255-8 sample operate and reset curves
100
Tmin = 10
10
τrst = 30
τop = 30
5
t (min)
0.1
0.01
0.1 1 10 100
I / Ipkp
827724A1.CDR
The thermal overload protection element estimates accumulated thermal energy E using the following equations
calculated each power cycle. When current is greater than the pickup level, In > k × IB, element starts increasing the
thermal energy:
t Eq. 5-25
E n = E n – 1 + --------------
t op In
When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:
t
E n = E n – 1 – -------------- Eq. 5-26
t rst In
where
∆t is the power cycle duration
n is the power cycle index
top(In) is the trip time calculated at index n as per the IEC255-8 cold curve or hot curve equations
trst(In) is the reset time calculated at index n as per the reset time equation
In is the measured overload RMS current at index n
En is the accumulated energy at index n
En – 1 is the accumulated energy at index n – 1
The thermal overload protection element removes the THERMAL PROT 1 OP output operand when E < 0.05. In case of
emergency, the thermal memory and THERMAL PROT 1 OP output operand can be reset using THERM PROT 1 RESET setting.
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-29: Typical time constants
Protected equipment Time constant Minimum reset time
Capacitor bank 10 minutes 30 minutes
Overhead line 10 minutes 20 minutes
Air-core reactor 40 minutes 30 minutes
Busbar 60 minutes 20 minutes
Underground cable 20 to 60 minutes 60 minutes
5
The figure shows the logic for the thermal overload protection element.
Figure 5-115: Thermal overload protection logic
SETTINGS
Function
Enabled = 1
Block AND
Off = 0
SETTINGS
Reset Time Constant
Minimum Reset Time
RUN
E < 0.1
SETTING
Reset
Off = 0 Reset E to 0 827013A1.CDR
+ p
b K
+
+
sKTd d +
y -1 u
1+sTd/N
+
-
+ e K + 1 i
r
Ti s
+
1
Tt
+ -
w
832031A1.cdr
where
y is the process signal
r is the setpoint signal
w is the tracking signal
5
u is the regulator output
K is the proportional gain
b is the setpoint weighting
Td is the derivative time constant
N is the derivative limit
T i is the integral time constant
Tt is the anti-windup time constant
s is the domain
In discrete form, the equations for the regulator are
ek = rk – yk
p k = K br k – y k
Td kT d N
d k = ------------------- d k – 1 – ------------------- y k – y k – 1
T d + NT S T d + NT S Eq. 5-27
u k = pk + ik + d k
KT S e k T S
i k + 1 = i k + ------------------ + ---- w k – u k AW
Ti Tt
where
TS is the sampling time
AW is a flag which enables anti-windup
The incremental form of this equation is:
Du k = u k – u k – 1
Eq. 5-28
= Dp k + Di k + Dd k
where
Dp k = p k – p k – 1
= K br k – y k – br k – 1 + y k – 1
Di k = i k – p k – 1
KT T
= e k – 1 -------S- + AW w k – 1 – v k – 1 ----S Eq. 5-29
Ti Tt
Dd k = d k – d k – 1
Td T d KN
- + y k – 2y k – 1 + y k – 2 ------------------
= Dd k – 1 ------------------ -
T d + NT S T d + NT S
SETTING SETTING
u>0 FLEXLOGIC OPERAND
FUNCTION: DEAD TIME:
AND PID 1 LOWER
Enabled = 1 Tdead
u > Tmin AND
|u| ms
SETTING AND FLEXLOGIC OPERAND
BLOCKED: AND PID 1 RAISE
Off = 0 SETTING u<0
Ts, K, b,
SETTING Ti, Tt, Td, N
Run FLEXLOGIC OPERAND
ANTIWINDUP: u
PID 1 DELTA OUT
Enabled = 1 AW
5 SETTING
PID
ACTUAL VALUE
SETPOINT
832029A1.cdr
5.9 Inputs/outputs
5.9.1 Contact inputs
SETTINGS INPUTS/OUTPUTS CONTACT INPUTS
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each
group of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules)
which contact inputs are available and then display settings for only those inputs.
An alphanumeric ID can be assigned to a contact input for diagnostic, setting, and event recording purposes. The CONTACT IP
X On (Logic 1) FlexLogic operand corresponds to contact input “X” being closed, while CONTACT IP X Off corresponds to contact
input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to overcome ‘contact
bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maximum contact
debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT INPUT EVENTS is
set to “Enabled,” every change in the contact input state triggers an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the following
figure. The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a
user-settable debounce time in order for the F35 to validate the new contact state. In the following figure, the debounce
time is set at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated
(de-bounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the
contact input into the Event Recorder (mark no. 2 in the figure).
5
Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the
figure below). The update is performed at the beginning of the protection pass so all protection and control functions, as
well as FlexLogic equations, are fed with the updated states of the contact inputs.
The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration
of the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically
a delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1 ms.
For example, eight protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a
contact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 s accuracy using the
time of the first scan corresponding to the new state (mark no. 2 shown). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the
debounce timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the
change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure) and HIGH-LOW (marks no. 5, 6, 7, and 8) transitions.
Figure 5-118: Input contact debouncing mechanism and time-stamping sample timing
VOLTAGE
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
Time stamp of the first At this time, the The FlexLogicTM scan corresponding to the
At this time, the new
scan corresponding to new (HIGH) operand is going to new validated state is
(LOW) contact state is
the new validated state is contact state is be asserted at this logged in the SOE record
validated
logged in the SOE record validated protection pass
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
5
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value is selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V sources
and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it
in the Event Records menu, make the following settings changes:
CONTACT INPUT H5a ID: "Breaker Closed (52b)"
CONTACT INPUT H5a EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
COMMANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the
appropriate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled,” the input is forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled,” the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x type is “Self-Reset,” when the input signal
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched,” the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
Figure 5-119: Virtual inputs logic
SETTING
VIRTUAL INPUT 1
FUNCTION:
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset
5
827080A3.CDR
Upon startup of the relay, the main processor determines from an assessment of the modules installed in the chassis
which contact outputs are available and then present the settings for only these outputs.
An ID can be assigned to each contact output. The signal that can OPERATE a contact output can be any FlexLogic operand
(virtual output, element state, contact input, or virtual input). An additional FlexLogic operand can be used to SEAL-IN the
relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A
contacts (see the trip circuit example in the Digital Elements section). The monitor sets a flag (see the specifications for
Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, Cont OP 1 IOn.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect
operation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in
the trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the
tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the F35 using the Cont OP 1 IOn FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
The F35 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
5 they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and
populates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic).
The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all
latching contacts opened. It is highly recommended to double-check the programming and positions of the latching
contacts when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring
capabilities for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test
error is declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message.
OUTPUT H1a OPERATE — This setting specifies a FlexLogic operand to operate the ‘close coil’ of the contact. The relay seals-
in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off), any activity of the
OPERATE input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active
(logic 1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a RESET — This setting specifies a FlexLogic operand to operate the ‘trip coil’ of the contact. The relay seals-in
this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any activity of the
RESET input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active (logic
1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a TYPE — This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact closes if set to
“Operate-dominant” and opens if set to “Reset-dominant.”
Application example 1
A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings are applied.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “PUSHBUTTON 1 ON”
OUTPUT H1a RESET: “PUSHBUTTON 2 ON”
Program the pushbuttons by making the following changes in the PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.00 s”
PUSHBUTTON 2 FUNCTION: “Self-reset”
PUSHBTN 2 DROP-OUT TIME: “0.00 s”
Application example 2
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
OUTPUT H1c OPERATE: “VO2”
OUTPUT H1c RESET: “VO1”
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they do not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time can occur.
Therefore, a pair of contacts programmed to be a multi-contact relay do not guarantee any specific sequence of operation
(such as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the
control inputs as shown in the next application example.
Application example 3
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
5
this functionality.
Write the following FlexLogic equation (EnerVista example shown).
Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
5.9.5 Resetting
SETTINGS INPUTS/OUTPUTS RESETTING
RESETTING RESET OPERAND: Range: FlexLogic operand
Off
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate RESET button, a remote device via a communications channel, or any
programmed operand.
When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are stored
as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each create the
RESET OP FlexLogic operand. Each individual source of a RESET command also creates its individual operand RESET OP
(PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The RESET OPERAND setting here
selects the operand that creates the RESET OP (OPERAND) operand.
DIRECT OUT 1 NAME — This setting allows the user to assign a descriptive name to the direct output.
DIR OUT 1 OPERAND — This sets the FlexLogic operand that determines the state of this direct output.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
Assume that contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings are applied (Direct Input 5 and
bit number 12 are used, as an example).
UR IED 1:
DIRECT INPUT 5 DEVICE ID = “2”
DIRECT INPUT 5 BIT NUMBER = “12”
UR IED 2:
DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
5 The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.
UR IED 1 BLOCK
842712A1.CDR
Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
trips the bus upon detecting a fault and applying a short coordination time delay.
The following settings are applied (assume Bit 3 is used by all 3 devices to send the blocking signal and Direct Inputs 7, 8,
and 9 are used by the receiving device to monitor the three blocking signals).
UR IED 2:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 3:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 4:
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown as
follows. The scheme output operand HYB POTT TX1 is used to key the permission.
Figure 5-123: Single-channel open-loop configuration
RX1
UR IED 3
TX1
842714A1.CDR
In this architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a ‘bridge’. The following
settings are applied:
UR IEC 1:
UR IED 1 UR IED 2
842717A1.CDR
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1
setting).
5.9.7 Teleprotection
5.9.7.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
distributed protection and control schemes via dedicated communications channels. Some examples are directional
comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect
teleprotection functionality. The teleprotection function must be enabled to utilize the inputs.
Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/
On” and logic 0 for “Latest/Off.”
As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of
communication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each
channel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand
on both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end).
On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of
channel failure between any pair of relays.
UR-1 UR-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: TELEPROT INPUT 1-1
DEFAULT:
SETTING (same for 1-2...1-16)
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off (Flexlogic Operand) Off TELEPRO INPUT 1-1 On
OK OR
(same for 1-2...1-16)
UR-2 or UR-3
ACTUAL VALUES SETTING
CHANNEL 2 STATUS: TELEPROT INPUT 2-1
DEFAULT:
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off TELEPRO INPUT 2-1 On
Off (Flexlogic Operand) OK OR
(same for 2-2...2-16)
842750A2.CDR
5
5.10 Transducer inputs/outputs
5.10.1 DCmA inputs
SETTINGS TRANSDUCER I/O DCMA INPUTS DCMA INPUT H1(W8)
DCMA INPUT H1 DCMA INPUT H1 Range: Disabled, Enabled
FUNCTION: Disabled
Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
Before the DCmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
DCmA input channels are arranged in a manner similar to CT and VT channels. Configure the individual channels with the
settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are generated automatically for every channel available in the specific relay as shown above for the first channel
of a type 5F transducer module installed in slot H.
The function of the channel can be “Enabled” or “Disabled.” If “Disabled,” no actual values are created for the channel. An
alphanumeric “ID” is assigned to each channel; this ID is included in the channel actual value, along with the programmed
units associated with the parameter measured by the transducer, such as volts, °C, megawatts, and so on. This ID is also
used to reference the channel as the input parameter to features designed to measure this type of parameter. The DCMA
INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250 °C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250.” Another example is a watts transducer with a span
from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value is “–20” and the DCMA INPUT H1 MAX VALUE value is
“180.” Intermediate values between the minimum and maximum values are scaled linearly.
RTD INPUT H1 TYPE: Range: 100Ω Nickel, 10Ω Copper, 100Ω Platinum,
100Ω Nickel 120Ω Nickel
Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either “Enabled” or “Disabled.” If “Disabled,” there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
Hardware and software is provided to generate DCmA signals that allow interfacing with external equipment. Hardware
details are contained in chapter 3. The DCmA output channels are arranged in a manner similar to transducer input or CT
and VT channels. The user configures individual channels with the settings as follows.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an
example for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The
following equation is applied:
where
x is a driving signal specified by the SOURCE setting
Imin and Imax are defined by the RANGE setting
k is a scaling constant calculated as:
I max – I min
k = -------------------------------------------
- Eq. 5-31
MAX VAL – MIN VAL
The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, for example when MAX VAL 5
– MIN VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure.
Figure 5-126: DCmA output characteristic
Imax
OUTPUT CURRENT
Imin
DRIVING SIGNAL
MIN VAL MAX VAL 842739A1.CDR
Settings
DCMA OUTPUT H1 SOURCE — This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving DCmA outputs. See Appendix A for a list of FlexAnalog parameters.
DCMA OUTPUT H1 RANGE — This setting allows selection of the output range. Each DCmA channel can be set independently
to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT H1 MIN VAL — This setting allows setting the minimum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.
DCMA OUTPUT H1 MAX VAL — This setting allows setting the maximum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.
The DCMA OUTPUT H1 MIN VAL and DCMA OUTPUT H1 MAX VAL settings are ignored for power factor base units
(i.e. if the DCMA OUTPUT H1 SOURCE is set to FlexAnalog value based on power factor measurement).
NOTE
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
P BASE = 115 V 120 1.2 kA = 16.56 MW Eq. 5-34
5 The minimum and maximum power values to be monitored (in pu) are:
– 20.65 MW 20.65 MW
minimum power = -------------------------- = – 1.247 pu, maximum power = ----------------------- = 1.247 pu Eq. 5-35
16.56 MW 16.56 MW
The following settings are entered:
DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAl: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or 0.005 1 – – 1 20.65 MW = 0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 20 MW + 0.207 MW = 0.407 MW.
The base unit for current (see the FlexElements section in this chapter for additional details) is:
I BASE = 5 kA Eq. 5-37
The minimum and maximum power values to be monitored (in pu) are:
0 kA 6.3 kA
minimum current = ---------- = 0 pu, maximum current = -------------- = 1.26 pu Eq. 5-38
5 kA 5 kA
The minimum and maximum voltage values to be monitored (in pu) are:
161.66 kV
minimum voltage = ----------------------- = 0.404 pu,
400 kV
254.03 kV
maximum voltage = ----------------------- = 0.635 pu
400 kV
Eq. 5-41 5
The following settings are entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”
The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (see the Metering Conventions section in
chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in this
example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or 0.005 1 – 0 254.03 kV = 1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 230.94 kV + 1.27 kV = 2.42 kV.
5.11 Testing
5.11.1 Test mode function
SETTINGS TESTING TEST MODE FUNCTION
TESTING TEST MODE Range: Disabled, Isolated, Forcible
FUNCTION: Disabled
The F35 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels
and the phasor measurement unit (where applicable), using simulated conditions.
The test mode can be in any of three states: Disabled, Isolated, or Forcible.
The Disabled mode is intended for normal in service operation; relay protection, control and communication function is
normal. Test features are disabled, except channel tests and phasor measurement unit tests remain usable when
provided.
The Isolated mode is intended to allow the relay to be quickly placed in a state where the relay cannot negatively impact
the power system or other parts of the substation automation system. This is to allow changing settings, loading new
firmware, changing hardware modules, and changing communication connections. As far as practical all relay output
signals are blocked. Contact outputs are de-energized, latching outputs are frozen. Commands to bricks are blocked.
GOOSE transmissions have their "simulation" flag (also known as "test" flag) set, which results in the messages not being
accepted by compliant receiving devices that do not have a "Sim" data attribute set. The quality attribute of values that
can be output via 61850 MMS services are set to "invalid," which results in the values not being used for operational
purposes by compliant receiving devices.
The Forcible mode is intended for testing involving forcing relay operation by test signal injection and verifying correct
relay output. This mode is also for tests to verify the relay outputs (both contact and communications) have the intended
impact on specific power system devices or on specific other substation automation devices. Contact outputs can be
selectively enabled or forced as described in the following two sections. Shared outputs to bricks have their test mode flag
raised, which results in their value only being accepted by relays also in forcible mode. GOOSE transmissions have the
"simulation" flag set, which results in these only being accepted by other devices that have their "Sim" data attribute set.
The "Sim" data attribute in the relay is set, so that if GOOSE messages are received with the "simulation" flag set, these are
used in place of the normal messages. The quality attribute of values that are output via 61850 MMS services are set to
"valid" + "test," which signals that the values should not be used for operational purposes.
Otherwise, the UR remains fully operational while in the Forcible test mode, allowing for various testing procedures. In
5 particular, the protection and control elements, and FlexLogic function normally. Other than the IEC 61850 protocol,
communications based inputs and outputs remain fully operational. The test procedure must take this into account.
The test mode can be selected either through the front panel, through EnerVista UR Setup, or through IEC 61850 control to
LLN0.Mod. LLN0.Mod.ctlVal "on" selects Disabled, "test/blocked" selects Isolated, and "test" selects Forcible. The TEST MODE
FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings upload, or
firmware upgrade, the test mode remains at the last programmed value. This allows a UR that has been placed in isolated
mode to remain isolated during testing and maintenance activities.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
Table 5-31: Test mode operation
Test mode In-service Test mode Critical fail Test mode forcing Contact input and output behavior
function LED LED relay
Disabled Unaffected Off Normal No effect Normal
Isolated Off On De-energized No effect Contact outputs disabled
Forcible Off Flashing De-energized Off Normal
On Controlled by forcing features
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert
to their default states.
NOTE
The force contact inputs feature provides a method of performing checks on the function of all contact inputs.
While in Forcible test mode, the relay contact inputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. Select this value if a given input must be operational during the test. This
includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open,” the input is forced to report as opened (Logic 0) while the operand selected by TEST MODE FORCING
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
• If set to “Closed,” the input is forced to report as closed (Logic 1) while the operand selected by TEST MODE FORCING
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert 5
to their default states.
NOTE
The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
While in Forcible test mode, the relay contact outputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the contact output remains fully operational. It operates when its control operand is logic 1 and
resets when its control operand is logic 0.
• If set to “Energized,” the output closes and remains closed while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “De-energized,” the output opens and remains opened while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “Freeze,” the output retains its position at the instant before the TEST MODE FUNCTION was Forcible and the
operand selected by the TEST MODE FORCING setting was On, regardless of later changes in the status of the operand
configured to control the output contact. While the selected operand is Off, the output behaves as it does when in
service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert
to their default states.
NOTE
Actual values
This chapter outlines viewing of data on the front panel and in the software.
SOURCE SRC 2
SOURCE SRC 3
SOURCE SRC 4
6
SOURCE SRC 5
SOURCE SRC 6
WATTMETRIC
GROUND FAULT 2
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed is
that of corresponding remote output unless the channel is declared failed.
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.1.8 Autoreclose
ACTUAL VALUES STATUS AUTORECLOSE AUTORECLOSE 1(6)
AUTORECLOSE 1 AUTORECLOSE 1 Range: 0, 1, 2, 3, 4
SHOT COUNT: 0
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
The All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.
RxGOOSE 1
sqNum: 0
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
Counter 1 FROZEN:
0
Counter 1 FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
0
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.1.13 FlexStates
ACTUAL VALUES STATUS FLEX STATES
FLEX STATES PARAM 1: Off Range: On, Off
Off
PARAM 256: Off Range: On, Off
Off
There are 256 FlexStateTM bits available. The second line value indicates the state of the given FlexState bit.
6.1.14 Ethernet
ACTUAL VALUES STATUS ETHERNET
ETHERNET ETHERNET PRI LINK Range: Fail, OK
STATUS: Fail
These values indicate the status of the first, second, and third Ethernet links.
UNRETURNED MSG
COUNT CH1: 0
UNRETURNED MSG
COUNT CH2: 0
DIRECT INPUT 1:
On
DIRECT INPUT 32:
On
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts can indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
6 COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.
These actual values represent the state of direct devices 1 through 16.
FAST EXCHANGE 1
DATA LENGTH: 0
These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet size
for the fast EGD exchange display.
SLOW EXCHANGE 1
DATA LENGTH: 0
These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD
exchanges display.
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT COUNTERS command.
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device, for example the PMU entry does not display when not applicable. Each time a
connection is used, the remaining number of connections decrements. When released, the remaining number of
connections increments. If no connection is made over the specific protocol, the number equals the maximum number
available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
MMS TCP — The number of IEC 61850 connections remaining.
PMU TCP — The maximum number of PMU TCP connections matches the number of aggregators. The maximum number of
aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with a
6 PMU. The remaining number of aggregators displays here.
The F35 is provided with optional PRP capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section in chapter 2 for details
Total Received Port A is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
6.2 Metering
6.2.1 Metering conventions
Figure 6-1: Flow direction of signed values for watts and VARs
Voltage +Q
VCG
WATTS = Positive IC
PF = Lead PF = Lag
VARS = Positive
PF = Lag IA
VAG -P +P
Current
IB IA
PF = Lag PF = Lead
UR RELAY
VBG -Q
M LOAD
- 1
Inductive Resistive S=VI
Generator
VCG
+Q
Voltage
PF = Lead PF = Lag
WATTS = Positive
IA
VARS = Negative IC
PF = Lead VAG -P +P
IA
Current
PF = Lag PF = Lead
IB
UR RELAY
VBG -Q
LOAD S=VI
- 2
Resistive
Inductive Resistive
M LOAD
VCG +Q
6 Voltage
WATTS = Negative
IA
IB
PF = Lead PF = Lag
VAG
VARS = Negative -P +P
PF = Lag
IA
IC PF = Lag PF = Lead
Current
VBG
-Q
UR RELAY
G S=VI
- 3
Generator
Resistive
LOAD
VCG
+Q
Voltage IB
PF = Lead PF = Lag
WATTS = Negative IA
VARS = Positive VAG -P +P
PF = Lead
IC
IA
Current
PF = Lag PF = Lead
VBG -Q
UR RELAY
G 827239AC.CDR
- 4
S=VI
Generator
For display and oscillography purposes, all phasor angles in a given relay are referred to an AC input channel pre-selected
by the SETTINGS SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE setting. This setting defines a
particular AC signal source to be used as the reference.
The relay first determines if any “Phase VT” bank is indicated in the source. If it is, voltage channel VA of that bank is used
as the angle reference. Otherwise, the relay determines if any “Aux VT” bank is indicated; if it is, the auxiliary voltage
channel of that bank is used as the angle reference. If neither of the two conditions is satisfied, then two more steps of this
hierarchical procedure to determine the reference signal include “Phase CT” bank and “Ground CT” bank.
If the AC signal pre-selected by the relay upon configuration is not measurable, the phase angles are not referenced. The
phase angles are assigned as positive in the leading direction, and are presented as negative in the lagging direction, to
more closely align with power system metering conventions. The figure illustrates this.
Figure 6-2: UR phase angle measurement convention
-270o
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
-90o 827845A1.CDR
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6-1: Symmetrical components calculation example
SYSTEM VOLTAGES, sec. V * VT conn. relay INPUTS, sec. V SYMM. COMP, sec. V
VAG VBG VCG VAB VBC VCA F5ac F6ac F7ac V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
0° –125° –250° –313° –97° –241° 0° –125° –250° –192° –7° –187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) 0° –144° –288° 0° –144° –288° –54° –234°
* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the UR displays are always referenced as specified under SETTINGS
SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
Figure 6-3: Measurement convention for symmetrical components
SYSTEM VOLTAGES SYMMETRICAL
COMPONENTS
6
UR phase angle
reference
1
UR phase angle
A
reference
WYE VTs
C
B
0
2
U
re R ph
fe a
re se
nc a
e ng
le
A U
1
re R ph
fe a
re se
nc a
e ng
DELTA VTs le
C
B
2
827844A1.CDR
6.2.2 Sources
6.2.2.1 Menu
ACTUAL VALUES METERING SOURCE SRC 1
SOURCE SRC 1 PHASE CURRENT See below
SRC 1
This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power
values are unavailable.
6
6.2.2.2 Phase current metering
ACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT
PHASE CURRENT SRC 1 RMS Ia: 0.000
SRC 1 b: 0.000 c: 0.000 A
The metered phase current values are displayed in this menu. The "SRC 1" text gets replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered ground current values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered phase voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
This menu displays metered values for real, reactive, and apparent power, as well as power factor. The "SRC 1" text is
replaced by the name programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL
SOURCES).
This menu displays metered values for real and reactive energy. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES). Because energy values are
accumulated, record them and then reset them immediately prior to changing CT or VT characteristics.
SRC 1 DMD W:
0.000 W
This menu displays metered values for current and power demand. The "SRC 1" text is replaced by the name programmed
by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the SETTINGS PRODUCT SETUP
DEMAND menu. For each quantity, the relay displays the demand over the most recent demand time interval, the
maximum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value.
Maximum demand quantities can be reset to zero with the CLEAR RECORDS CLEAR DEMAND RECORDS command.
This menu displays metered current harmonics values. The “SRC 1” text is replaced by the programmed name for the
associated source (see the SETTINGS SYSTEM SETUP SIGNAL SOURCES menu).
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
0 = 2f is the angular frequency based on the system frequency (50 or 60 Hz)
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:
2
F real m, h = --- f m – k cos h 0 t k
N
k
2 Eq. 6-1
F imag m, h = --- f m – k sin h 0 t k
N
k
2 2
F ampl m, h = F real m, h + F imag m, h
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental
amplitude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the
fundamental:
2 2 2
THD = F 2 + F 3 + + F 25 Eq. 6-2
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure that the SYSTEM SETUP AC
INPUTS VOLTAGE BANK F5 PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics
NOTE
metering.
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM SETUP POWER SYSTEM menu. See the Power
System section of chapter 5 for details.
6.2.4 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(16)
FLEXELEMENT 1 FLEXELEMENT 1
OpSig: 0.000 pu
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit Description
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FREQUENCY fBASE = 1 Hz
PHASE ANGLE BASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
The F35 is provided with optional GOOSE communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
This menu displays the wattmetric zero-sequence directional element operating power values.
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx
RTD INPUT xx RTD INPUT xx
-50 °C
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6.3 Records
6.3.1 Fault reports
ACTUAL VALUES RECORDS FAULT REPORTS FAULT REPORT 1(15)
NO FAULTS TO REPORT
or
FAULT REPORT 1 FAULT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
LINE ID: SRC 1
FAULT 1 TYPE: Range: not available if the source VTs are in the
ABG “Delta” configuration
FAULT 1 LOCATION Range: not available if the source VTs are in the
00.0 km “Delta” configuration
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS PRODUCT
SETUP FAULT REPORTS menu for assigning the source and trigger for fault calculations. See the COMMANDS CLEAR
RECORDS menu for manual clearing of the fault reports and to the SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS
menu for automated clearing of the fault reports.
EVENT: 3 EVENT 3
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
POWER OFF TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the COMMANDS CLEAR RECORDS menu for clearing event records.
6.3.3 Oscillography
ACTUAL VALUES RECORDS OSCILLOGRAPHY
OSCILLOGRAPHY FORCE TRIGGER? Range: No, Yes
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The cycles
per record value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography
section of chapter 5 for details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. See the COMMANDS CLEAR
RECORDS menu for information on clearing the oscillography records.
The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It is static until the log gets
full, at which time it starts counting at the defined sampling rate.
The NEWEST SAMPLE TIME represents the time the most recent samples were taken. It counts up at the defined sampling
rate. If the data logger channels are defined, then both values are static.
See the COMMANDS CLEAR RECORDS menu for clearing data logger records.
6
6.3.5 Breaker maintenance
ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1(6)
BREAKER 1 BKR 1 ARCING AMP A:
0.00 kA2-cyc
BKR 1 OPERATING
TIME: 0 ms
The BREAKER OPERATING TIME is defined as the slowest operating time of breaker poles that were initiated to open.
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information.
6
6.4.2 Firmware revisions
ACTUAL VALUES PRODUCT INFO FIRMWARE REVISIONS
FIRMWARE REVISIONS F35 Relay Range: 0.00 to 655.35
REVISION: 7.3x Revision number of the application firmware.
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
This chapter outlines the Commands and Targets menus and self-tests/error messages. Commands related to the IEC
61850 protocol are outlined in the IEC 61850 section of the Settings chapter. Log/error messages for IEC 61850 are
outlined in the UR Series Communications Guide.
COMMANDS
COMMANDS
VIRTUAL INPUTS
COMMANDS
CLEAR RECORDS
COMMANDS
SET DATE AND TIME
COMMANDS
RELAY MAINTENANCE
COMMANDS
SECURITY
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash
message appears after successfully command entry.
COMMAND
EXECUTED
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to
“No.”
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over-
written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the ENTER key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the ENTER key.
PERFORM LAMPTEST — Turns on all faceplate LEDs and display pixels for a short duration.
UPDATE ORDER CODE — This command causes the relay to scan the backplane for the hardware modules and update the
order code to match. If an update occurs, the following message displays.
UPDATING... 7
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
REBOOT RELAY — Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator or Operator role can initiate the Reboot Relay command.
NOTE
SERVICE COMMAND — Performs specific F35 service actions. Presently, there are two service actions available. Code "20511"
returns all settings to their factory default value. Code “101” is used to clear factory diagnostic information stored in the
non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken. Various
self-checking diagnostics are performed in the background while the F35 is running, and diagnostic information is stored
on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is
cleared before the F35 is shipped from the factory, the user can want to clear the diagnostic information for themselves
under certain circumstances. For example, you clear diagnostic information after replacement of hardware. Once the
diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from
scratch.
SAVE VOLATILE DATA — Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS SECURITY
SECURITY ADMINISTRATOR Range: Yes, No
LOGOFF: No
With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.
ENGINEER LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.
OPERATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.
CLEAR SECURITY DATA — Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.
7.2 Targets
TARGETS
7 DIGITAL ELEMENT 1:
LATCHED
Displayed only if targets for this element are active.
Example shown.
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
LATCHED Example shown.
The status of any active targets displays in the targets menu. If no targets are active, the display reads NO ACTIVE TARGETS.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
MODULE FAILURE___:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: Module hardware failure detected.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed
module (for example, F8L). 7
INCOMPATIBLE H/W:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: One or more installed hardware modules is not compatible with the F35 order code.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed
module (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
• Latched target message: No.
• Description of problem: The configuration of modules does not match the order code stored in the F35.
• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
• Latched target message: No.
• Description of problem: A FlexLogic equation is incorrect.
• How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified.
• What to do: Finish all equation editing and use self tests to debug any errors.
MAINTENANCE ALERT:
Replace Battery
• Latched target message: Yes.
• Description of problem: The battery is not functioning.
• How often the test is performed: The battery is monitored every five seconds. The error message displays after 60
seconds if the problem persists.
• What to do: Replace the battery as outlined in the Maintenance chapter.
MAINTENANCE ALERT:
7 Direct I/O Ring Break
• Latched target message: No.
• Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
• How often the test is performed: Every second.
• What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
ENET PORT # OFFLINE
• Latched target message: No.
• Description of problem: The Ethernet connection has failed for the specified port.
• How often the test is performed: Every five seconds.
• What to do: Check the Ethernet port connection on the switch.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
• Latched target message: No.
MAINTENANCE ALERT:
**Bad PTP Signal**
• Latched target message: No.
• Description of problem: No PTP enabled port has good PTP signal input.
• How often the test is performed: Activated when no acceptable signal is being received.
• What to do: Ensure the following:
– The Ethernet cable(s) are properly connected.
– At least one PTP grandmaster-capable clock is functioning.
– If strict PP is enabled, that entire network is PP compliant.
– The network is delivering PTP messages to the relay.
MAINTENANCE ALERT:
Port ## Failure
• Latched target message: No.
• Description of problem: An Ethernet connection has failed.
• How often the test is performed: Monitored every five seconds.
• What to do: Check Ethernet connections. Port 1 is the primary port and port 2 is the secondary port.
MAINTENANCE ALERT:
SNTP Failure
• Latched target message: No.
• Description of problem: The SNTP server is not responding.
• How often the test is performed: Every 10 to 60 seconds.
7
• What to do: Check that Ethernet cable(s) are properly connected. Check that configuration for the SNTP server
corresponds to the actual server settings. Check connectivity to the server (ping the server IP address.
MAINTENANCE ALERT:
4L Discrepancy
• Latched target message: No.
• Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact
output of an installed type “4L” module.
• How often the test is performed: Upon initiation of a contact output state change.
• What to do: Verify the state of the output contact and contact the factory if the problem persists.
MAINTENANCE ALERT:
GGIO Ind xxx oscill
• Latched target message: No.
• Description of problem: A data item in a configurable GOOSE data set is oscillating.
• How often the test is performed: Upon scanning of each configurable GOOSE data set.
• What to do: The “xxx” text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.
RxGOOSE FAIL:
Missing messages
• Latched target message: No.
• Description of problem: One or more RxGOOSE messages are not being received.
• How often the test is performed: The self-test is activated when no message is received within the expected time
interval, which is the time-to-live time in the previous message. This time can be from milliseconds to minutes.
• What to do: Check GOOSE setup.
TEMP MONITOR:
OVER TEMPERATURE
• Latched target message: Yes.
• Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
• How often the test is performed: Every hour.
• What to do: Remove the F35 from service and install in a location that meets operating temperature standards.
UNEXPECTED RESTART:
Press “RESET” key
• Latched target message: Yes.
• Description of problem: Abnormal restart from modules being removed or inserted while the F35 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
7 •
•
How often the test is performed: Event driven.
What to do: Contact the factory.
WRONG TRANSCEIVER
If the problem persists with the foregoing all clear, the cause must be an AC input discrepancy, which is typically the
result of problems in the input signals to the Bricks, or faults in the Brick input conditioning hardware. If the error was
annunciated the first time significant signal was encountered, suspect the former cause and check the copper
connections external to the Brick. Where multiple UR-series devices have self-test errors, look for common causes.
To further isolate AC input discrepancy errors, put the relay in test-isolated mode, then one by one, temporally change
an AC bank crosschecking setting to none, until the Process Bus Failure clears. Once the problem AC bank has been
identified, the values from each of the two Bricks can be examined individually by temporarily mapping each to an AC
bank with a single origin.
Chapter 8: Commissioning
Commissioning
8.1 Testing
8.1.1 Testing underfrequency elements
Underfrequency and overfrequency protection requires techniques with subtle testing implications. Whereas most
protection is designed to detect changes from normal to fault conditions that occur virtually instantaneously, power
system inertia requires frequency protection to pick up while the frequency is changing slowly. Frequency measurement is
inherently sensitive to noise, making high precision in combination with high speed challenging for both relays and test
equipment.
Injection to a particular F35 frequency element must be to its configured source and to the channels that the source uses
for frequency measurement. For frequency measurement, a source uses the first quantity configured in the following
order:
1. Phase voltages
2. Auxiliary voltage
3. Phase currents
4. Ground current
For example, if auxiliary voltage and phase currents are configured, the source uses the auxiliary voltage, not the phase
voltages or any of the currents.
When phase voltages or phase currents are used, the source applies a filter that rejects the zero-sequence component. As
such, the same signal must not be injected to all three phases, or the injected signal is completely filtered out. For an
underfrequency element using phase quantities, the phase A signal must be above the MIN VOLT/AMP setting value.
Therefore, either inject into phase A only, or inject a balanced three-phase signal.
Frequency
Injection frequency
Source frequency
Tracking frequency
Pickup
frequency
Time
Underfrequency element detection time
The static accuracy of the frequency threshold is determined by slowly adjusting the frequency of the injected signal about
the set pickup. If the F35 frequency metering feature is used to determine the injected frequency, verify the metering
accuracy by checking it against a known standard (for example, the power system).
To accurately measure the time delay of a frequency element, a test emulating realistic power system dynamics is
required. Let the injected frequency ramp smoothly through the set threshold, with the ramp starting frequency sufficiently
outside the threshold so that the relay becomes conditioned to the trend before operation. For typical interconnected
power systems, the recommended testing ramp rate is 0.20 Hz/s.
The required delay time is the interval from the point the frequency crosses the set threshold to the point that the element
operates. Some test sets can measure only the time from the ramp start to element operation, necessitating the
subtraction of the pre-threshold ramp time from the reading. For example, with a ramp rate of 0.20 Hz/s, start the ramp
0.20 Hz before the threshold and subtract 1 second from the test set time reading of ramp start to relay operation.
Note that the F35 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time
taken by the frequency responding component to pickup.
F35 oscillography can be used to measure the time between the calculated source frequency crossing the threshold and
element operation; however, this method omits the delay in the calculated source frequency. The security features of the
source frequency measurement algorithm result in the calculated frequency being delayed by two to four cycles (or longer
with noise on the input). In addition, oscillography resolution is 0.004 Hz, which at 0.20 Hz/s corresponds to a delay of 20
8 ms. Do not use the tracking frequency in timing measurements, as its algorithm involves phase locking, which purposely
sets its frequency high or low to allow the F35 sample clock to catch-up or wait as necessary to reach synchronism with
the power system.
Theory of operation
distance to fault
Remote
Local bus bus
ZA IA mZ (1-m)Z IB ZB
EA VF RF EB
VA VB
842780A1.CDR
where
Inserting the IA and IB equations into the VA equation and solving for the fault resistance yields:
VA – m Z IA
R F = ------------------------------
- Eq. 9-4
I BF
I AF 1 + ----- -
I AF
Assuming the fault components of the currents, IAF and IBF are in phase, and observing that the fault resistance, as
impedance, does not have any imaginary part gives:
VA – m Z IA
Im ------------------------------- = 0 Eq. 9-5
I AF
where Im() represents the imaginary part of a complex number. Solving this equation for the unknown m creates the
following fault location algorithm:
Im V A I AF
m = ----------------------------------
- Eq. 9-6
Im Z I A I AF
For BG faults:
B B
VA = VA , I A = I A + K 0 I 0A Eq. 9-8
For CG faults:
C BC
VA = VA , I A = I A + K 0 I 0A Eq. 9-9
9 where K0 is the zero sequence compensation factor (for the first six equations).
For ABC faults, all three AB, BC, and CA loops are analyzed and the final result is selected based upon consistency of the
results.
The element calculates the distance to the fault (with m in miles or kilometers) and the phases involved in the fault.
The relay allows locating faults from delta-connected VTs. If the FAULT REPORT 1 VT SUBSTITUTION setting is set to “None,”
and the VTs are connected in wye, the fault location is performed based on the actual phase to ground voltages. If the VTs
are connected in delta, fault location is suspended.
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “V0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and externally supplied neutral voltage:
1
V A = -- V N + V AB – V CA
3
1
V B = -- V N + V BC – V AB Eq. 9-13
3
1
V B = -- V N + V CA – V BC
3
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “I0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and zero-sequence voltage approximated based on the zero-sequence
current:
1
V A = -- V AB – V CA – Z SYS0 I 0
3
1
V B = -- V BC – V AB – Z SYS0 I 0 Eq. 9-14
3
1
V B = -- V CA – V BC – Z SYS0 I 0
3
where ZSYS0 is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu.
SETTINGS
FAULT REPORT 1 Z1
MAG:
FAULT REPORT 1 Z1
ANGLE:
FAULT REPORT 1 Z0
MAG:
FAULT REPORT 1 Z0
ANGLE:
FAULT REPORT 1
LENGTH UNITS:
FAULT REPORT 1
LENGTH:
SHOT # FROM
AUTO RECLOSURE 827094A5.CDR
Maintenance
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
NOTICE state once per year, for one hour continuously.
4. Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URS
file. The URS file is added to the Offline Window area.
5. Drag the imported file in the Offline Window to the device in the Online Window.
6. Manually copy the remaining settings, outlined as follows.
3.
TFTP cannot be used here.
Use the device's IP address as the host name.
10
4. If the device has the CyberSentry option, use the User Name of "Administrator" or "Engineer", and the password
programmed for the selected role. The default password is "ChangeMe1#" (without quotation marks).
5. If the device does not have the CyberSentry option, use the User Name of "Setting", and the password programmed for
the Setting role. The default password is "ChangeMe1#" (without quotation marks).
6. Upload the backup file copy with the CID extension. WinSCP uses drag-and-drop or copy-and-paste for this.
7. Manually copy the remaining settings, outlined as follows.
5. Set the device to "programmed" under Settings > Produce Setup > Installation.
6. If you changed the Remote Setting Authorized, the Local Setting Authorized settings, or relay lock settings, return
them to their previous settings.
7. To apply any previously saved settings, right-click the saved settings file in the Offline Window area and select Write
to Device.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is,
default values, minimum/maximum values, data type, and item size) can change slightly from version to
NOTE
version of firmware. The addresses are rearranged when new features are added or existing features are
enhanced or modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the
firmware is a resettable, self-test message intended to inform users that the Modbus addresses have changed
with the upgraded firmware. This message does not signal any problems when appearing after firmware
upgrades.
Withdraw or insert a module only when control power has been removed from the unit, and be
WARNING sure to insert only the correct module type into a slot, else personal injury, damage to the unit
or connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
NOTICE static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
To replace a module:
1. Open the enhanced faceplate to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the F35.
Figure 10-4: Modules inside relay with front cover open (enhanced faceplate)
842812A1.CDR
The standard faceplate can be opened to the left once the black plastic sliding latch on the right side has been pushed
up, as shown below.
10
2. With power to the unit off, disconnect individually the connections from the module before removing the module from
the chassis.
3. To properly remove a module, pull simultaneously the ejector/inserter clips, located at the top and bottom of the
module. Record the original location of the module to ensure that the same or replacement module is inserted into the
correct slot. Modules with current input provide automatic shorting of external CT circuits.
4. To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module
is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips
simultaneously. When the clips have locked into position, the module is fully inserted.
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with
old CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function
NOTE
and a DSP ERROR or HARDWARE MISMATCH error displays.
10.6 Battery
A battery powers the real time clock on startup of the device.
When required, the battery can be replaced. Because the power supply module contains the battery and there are two
power supply options, two procedures are possible. To determine which procedure to use, check the power supply module
or use the photographs here.
To avoid injury, ensure that the unit has been powered off for a minimum of three minutes
CAUTION before replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
To replace the battery:
1. Turn off the power to the unit. 10
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the plastic latch on the right side of the front panel
(standard front panel) or unscrewing the panel (enhanced front panel).
4. For the standard front panel, it needs to be removed in order to access the power supply module, which is typically in
the first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew its bracket
on the front left side of the unit.
5. Simultaneously pull the ejector clips at the top and bottom of the power supply module and remove the module.
6. Unscrew the screw that attaches the metal cover to the module.
7. Slide the metal cover away from the clips about 1 cm (1/4 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides. Use a flat-head screwdriver if you cannot unclip the plastic with your fingers.
9. Observe the + and - polarity of the battery and replace it with the same polarity as marked on the battery holder.
Replace the battery with the identical make and model. For example, do not use a rechargeable battery.
Figure 10-6: Battery location on RH/RL power supply module
10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.
To avoid injury, ensure that the unit has been powered off for a minimum of three minutes
CAUTION before replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
To replace the battery:
1. Turn off the power to the unit.
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the plastic latch on the right side of the front panel
(standard front panel) or unscrewing the panel (enhanced front panel).
4. For the standard front panel, it needs to be removed in order to access the power supply module, which is typically in
the first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew the bracket
10 5.
on the front left side of the unit.
Simultaneously pull the ejector clips at the top and bottom of the power supply module and remove the module.
6. Unscrew all four screws (not three) that attach the metal cover to the module.
7. Slide the metal cover away from the clips about 1 cm (1/4 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides. Use a flat-head screwdriver if you cannot unclip the plastic with your fingers.
9. Observe the + and - polarity of the battery and replace it with the same polarity as marked on the battery holder.
Replace the battery with the identical make and model. For example, do not use a rechargeable battery.
Figure 10-7: Battery location on SH/SL power supply module
10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.
10
10
Appendices
FlexAnalog operands
A
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Degrees Source 3 ground current magnitude
6296 SRC 3 Ig Angle Amps Source 3 ground current angle
6297 SRC 3 I_0 Mag Degrees Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Amps Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Degrees Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Amps Source 3 positive-sequence current angle
6303 SRC 3 I_2 Mag Degrees Source 3 negative-sequence current magnitude
6305 SRC 3 I_2 Angle Amps Source 3 negative-sequence current angle
6306 SRC 3 Igd Mag Degrees Source 3 differential ground current magnitude
6308 SRC 3 Igd Angle Amps Source 3 differential ground current angle
6336 SRC 4 Ia RMS Amps Source 4 phase A current RMS
6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS
6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS
6342 SRC 4 In RMS Amps Source 4 neutral current RMS
6344 SRC 4 Ia Mag Amps Source 4 phase A current magnitude
6346 SRC 4 Ia Angle Degrees Source 4 phase A current angle
6347 SRC 4 Ib Mag Amps Source 4 phase B current magnitude
6349 SRC 4 Ib Angle Degrees Source 4 phase B current angle
6350 SRC 4 Ic Mag Amps Source 4 phase C current magnitude
6352 SRC 4 Ic Angle Degrees Source 4 phase C current angle
6353 SRC 4 In Mag Amps Source 4 neutral current magnitude
6355 SRC 4 In Angle Degrees Source 4 neutral current angle
6356 SRC 4 Ig RMS Amps Source 4 ground current RMS
6358 SRC 4 Ig Mag Degrees Source 4 ground current magnitude
6360 SRC 4 Ig Angle Amps Source 4 ground current angle
6361 SRC 4 I_0 Mag Degrees Source 4 zero-sequence current magnitude
6363 SRC 4 I_0 Angle Amps Source 4 zero-sequence current angle
6364 SRC 4 I_1 Mag Degrees Source 4 positive-sequence current magnitude
6366 SRC 4 I_1 Angle Amps Source 4 positive-sequence current angle
6367 SRC 4 I_2 Mag Degrees Source 4 negative-sequence current magnitude
6369 SRC 4 I_2 Angle Amps Source 4 negative-sequence current angle
6370 SRC 4 Igd Mag Degrees Source 4 differential ground current magnitude
6372 SRC 4 Igd Angle Amps Source 4 differential ground current angle
6400 SRC 5 Ia RMS Amps Source 5 phase A current RMS
6402 SRC 5 Ib RMS Amps Source 5 phase B current RMS
6404 SRC 5 Ic RMS Amps Source 5 phase C current RMS
6406 SRC 5 In RMS Amps Source 5 neutral current RMS
6408 SRC 5 Ia Mag Amps Source 5 phase A current magnitude
6410 SRC 5 Ia Angle Degrees Source 5 phase A current angle
6411 SRC 5 Ib Mag Amps Source 5 phase B current magnitude
6413 SRC 5 Ib Angle Degrees Source 5 phase B current angle
A
6671 SRC 1 Vab RMS Volts Source 1 phase AB voltage RMS
6673 SRC 1 Vbc RMS Volts Source 1 phase BC voltage RMS
6675 SRC 1 Vca RMS Volts Source 1 phase CA voltage RMS
6677 SRC 1 Vab Mag Volts Source 1 phase AB voltage magnitude
6679 SRC 1 Vab Angle Degrees Source 1 phase AB voltage angle
6680 SRC 1 Vbc Mag Volts Source 1 phase BC voltage magnitude
6682 SRC 1 Vbc Angle Degrees Source 1 phase BC voltage angle
6683 SRC 1 Vca Mag Volts Source 1 phase CA voltage magnitude
6685 SRC 1 Vca Angle Degrees Source 1 phase CA voltage angle
6686 SRC 1 Vx RMS Volts Source 1 auxiliary voltage RMS
6688 SRC 1 Vx Mag Volts Source 1 auxiliary voltage magnitude
6690 SRC 1 Vx Angle Degrees Source 1 auxiliary voltage angle
6691 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude
6693 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle
6694 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude
6696 SRC 1 V_1 Angle Degrees Source 1 positive-sequence voltage angle
6697 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude
6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle
6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS
6722 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
6724 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
6729 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
6731 SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
6732 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle
6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
6737 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
6743 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
6744 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
6749 SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
6786 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
A
6885 SRC 4 V_0 Angle Degrees Source 4 zero-sequence voltage angle
6886 SRC 4 V_1 Mag Volts Source 4 positive-sequence voltage magnitude
6888 SRC 4 V_1 Angle Degrees Source 4 positive-sequence voltage angle
6889 SRC 4 V_2 Mag Volts Source 4 negative-sequence voltage magnitude
6891 SRC 4 V_2 Angle Degrees Source 4 negative-sequence voltage angle
6912 SRC 5 Vag RMS Volts Source 5 phase AG voltage RMS
6914 SRC 5 Vbg RMS Volts Source 5 phase BG voltage RMS
6916 SRC 5 Vcg RMS Volts Source 5 phase CG voltage RMS
6918 SRC 5 Vag Mag Volts Source 5 phase AG voltage magnitude
6920 SRC 5 Vag Angle Degrees Source 5 phase AG voltage angle
6921 SRC 5 Vbg Mag Volts Source 5 phase BG voltage magnitude
6923 SRC 5 Vbg Angle Degrees Source 5 phase BG voltage angle
6924 SRC 5 Vcg Mag Volts Source 5 phase CG voltage magnitude
6926 SRC 5 Vcg Angle Degrees Source 5 phase CG voltage angle
6927 SRC 5 Vab RMS Volts Source 5 phase AB voltage RMS
6929 SRC 5 Vbc RMS Volts Source 5 phase BC voltage RMS
6931 SRC 5 Vca RMS Volts Source 5 phase CA voltage RMS
6933 SRC 5 Vab Mag Volts Source 5 phase AB voltage magnitude
6935 SRC 5 Vab Angle Degrees Source 5 phase AB voltage angle
6936 SRC 5 Vbc Mag Volts Source 5 phase BC voltage magnitude
6938 SRC 5 Vbc Angle Degrees Source 5 phase BC voltage angle
6939 SRC 5 Vca Mag Volts Source 5 phase CA voltage magnitude
6941 SRC 5 Vca Angle Degrees Source 5 phase CA voltage angle
6942 SRC 5 Vx RMS Volts Source 5 auxiliary voltage RMS
6944 SRC 5 Vx Mag Volts Source 5 auxiliary voltage magnitude
6946 SRC 5 Vx Angle Degrees Source 5 auxiliary voltage angle
6947 SRC 5 V_0 Mag Volts Source 5 zero-sequence voltage magnitude
6949 SRC 5 V_0 Angle Degrees Source 5 zero-sequence voltage angle
6950 SRC 5 V_1 Mag Volts Source 5 positive-sequence voltage magnitude
6952 SRC 5 V_1 Angle Degrees Source 5 positive-sequence voltage angle
6953 SRC 5 V_2 Mag Volts Source 5 negative-sequence voltage magnitude
6955 SRC 5 V_2 Angle Degrees Source 5 negative-sequence voltage angle
6976 SRC 6 Vag RMS Volts Source 6 phase AG voltage RMS
6978 SRC 6 Vbg RMS Volts Source 6 phase BG voltage RMS
6980 SRC 6 Vcg RMS Volts Source 6 phase CG voltage RMS
6982 SRC 6 Vag Mag Volts Source 6 phase AG voltage magnitude
6984 SRC 6 Vag Angle Degrees Source 6 phase AG voltage angle
6985 SRC 6 Vbg Mag Volts Source 6 phase BG voltage magnitude
6987 SRC 6 Vbg Angle Degrees Source 6 phase BG voltage angle
6988 SRC 6 Vcg Mag Volts Source 6 phase CG voltage magnitude
6990 SRC 6 Vcg Angle Degrees Source 6 phase CG voltage angle
6991 SRC 6 Vab RMS Volts Source 6 phase AB voltage RMS
6993 SRC 6 Vbc RMS Volts Source 6 phase BC voltage RMS
6995 SRC 6 Vca RMS Volts Source 6 phase CA voltage RMS
6997 SRC 6 Vab Mag Volts Source 6 phase AB voltage magnitude
6999 SRC 6 Vab Angle Degrees Source 6 phase AB voltage angle
7000 SRC 6 Vbc Mag Volts Source 6 phase BC voltage magnitude
A
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power
7274 SRC 4 Qa Vars Source 4 phase A reactive power
7276 SRC 4 Qb Vars Source 4 phase B reactive power
7278 SRC 4 Qc Vars Source 4 phase C reactive power
7280 SRC 4 S VA Source 4 three-phase apparent power
7282 SRC 4 Sa VA Source 4 phase A apparent power
7284 SRC 4 Sb VA Source 4 phase B apparent power
7286 SRC 4 Sc VA Source 4 phase C apparent power
7288 SRC 4 PF --- Source 4 three-phase power factor
7289 SRC 4 Phase A PF --- Source 4 phase A power factor
7290 SRC 4 Phase B PF --- Source 4 phase B power factor
7291 SRC 4 Phase C PF --- Source 4 phase C power factor
7296 SRC 5 P Watts Source 5 three-phase real power
7298 SRC 5 Pa Watts Source 5 phase A real power
7300 SRC 5 Pb Watts Source 5 phase B real power
7302 SRC 5 Pc Watts Source 5 phase C real power
7304 SRC 5 Q Vars Source 5 three-phase reactive power
7306 SRC 5 Qa Vars Source 5 phase A reactive power
7308 SRC 5 Qb Vars Source 5 phase B reactive power
7310 SRC 5 Qc Vars Source 5 phase C reactive power
7312 SRC 5 S VA Source 5 three-phase apparent power
7314 SRC 5 Sa VA Source 5 phase A apparent power
7316 SRC 5 Sb VA Source 5 phase B apparent power
7318 SRC 5 Sc VA Source 5 phase C apparent power
7320 SRC 5 PF --- Source 5 three-phase power factor
7321 SRC 5 Phase A PF --- Source 5 phase A power factor
7322 SRC 5 Phase B PF --- Source 5 phase B power factor
7323 SRC 5 Phase C PF --- Source 5 phase C power factor
7328 SRC 6 P Watts Source 6 three-phase real power
7330 SRC 6 Pa Watts Source 6 phase A real power
A
7750 SRC 5 Demand Watt Watts Source 5 real power demand
7752 SRC 5 Demand var Vars Source 5 reactive power demand
7754 SRC 5 Demand Va VA Source 5 apparent power demand
7760 SRC 6 Demand Ia Amps Source 6 phase A current demand
7762 SRC 6 Demand Ib Amps Source 6 phase B current demand
7764 SRC 6 Demand Ic Amps Source 6 phase C current demand
7766 SRC 6 Demand Watt Watts Source 6 real power demand
7768 SRC 6 Demand var Vars Source 6 reactive power demand
7770 SRC 6 Demand Va VA Source 6 apparent power demand
9024 Prefault Ia Mag [0] Amps Fault 1 pre-fault phase A current magnitude
9026 Prefault Ia Ang [0] Degrees Fault 1 pre-fault phase A current angle
9027 Prefault Ib Mag [0] Amps Fault 1 pre-fault phase B current magnitude
9029 Prefault Ib Ang [0] Degrees Fault 1 pre-fault phase B current angle
9030 Prefault Ic Mag [0] Amps Fault 1 pre-fault phase C current magnitude
9032 Prefault Ic Ang [0] Degrees Fault 1 pre-fault phase C current angle
9033 Prefault Va Mag [0] Volts Fault 1 pre-fault phase A voltage magnitude
9035 Prefault Va Ang [0] Degrees Fault 1 pre-fault phase A voltage angle
9036 Prefault Vb Mag [0] Volts Fault 1 pre-fault phase B voltage magnitude
9038 Prefault Vb Ang [0] Degrees Fault 1 pre-fault phase B voltage angle
9039 Prefault Vc Mag [0] Volts Fault 1 pre-fault phase C voltage magnitude
9041 Prefault Vc Ang [0] Degrees Fault 1 pre-fault phase C voltage angle
9042 Postfault Ia Mag [0] Amps Fault 1 post-fault phase A current magnitude
9044 Postfault Ia Ang [0] Degrees Fault 1 post-fault phase A current angle
9045 Postfault Ib Mag [0] Amps Fault 1 post-fault phase B current magnitude
9047 Postfault Ib Ang [0] Degrees Fault 1 post-fault phase B current angle
9048 Postfault Ic Mag [0] Amps Fault 1 post-fault phase C current magnitude
9050 Postfault Ic Ang [0] Degrees Fault 1 post-fault phase C current angle
9051 Postfault Va Mag [0] Volts Fault 1 post-fault phase A voltage magnitude
9053 Postfault Va Ang [0] Degrees Fault 1 post-fault phase A voltage angle
9054 Postfault Vb Mag [0] Volts Fault 1 post-fault phase B voltage magnitude
9056 Postfault Vb Ang [0] Degrees Fault 1 post-fault phase B voltage angle
9057 Postfault Vc Mag [0] Volts Fault 1 post-fault phase C voltage magnitude
9059 Postfault Vc Ang [0] Degrees Fault 1 post-fault phase C voltage angle
9060 Fault Type [0] --- Fault 1 type
9061 Fault Location [0] --- Fault 1 location
9062 Prefault Ia Mag [1] Amps Fault 2 pre-fault phase A current magnitude
9064 Prefault Ia Ang [1] Degrees Fault 2 pre-fault phase A current angle
9065 Prefault Ib Mag [1] Amps Fault 2 pre-fault phase B current magnitude
9067 Prefault Ib Ang [1] Degrees Fault 2 pre-fault phase B current angle
9068 Prefault Ic Mag [1] Amps Fault 2 pre-fault phase C current magnitude
9070 Prefault Ic Ang [1] Degrees Fault 2 pre-fault phase C current angle
9071 Prefault Va Mag [1] Volts Fault 2 pre-fault phase A voltage magnitude
9073 Prefault Va Ang [1] Degrees Fault 2 pre-fault phase A voltage angle
9074 Prefault Vb Mag [1] Volts Fault 2 pre-fault phase B voltage magnitude
9076 Prefault Vb Ang [1] Degrees Fault 2 pre-fault phase B voltage angle
9077 Prefault Vc Mag [1] Volts Fault 2 pre-fault phase C voltage magnitude
9079 Prefault Vc Ang [1] Degrees Fault 2 pre-fault phase C voltage angle
A
9149 Prefault Va Ang [3] Degrees Fault 4 pre-fault phase A voltage angle
9150 Prefault Vb Mag [3] Volts Fault 4 pre-fault phase B voltage magnitude
9152 Prefault Vb Ang [3] Degrees Fault 4 pre-fault phase B voltage angle
9153 Prefault Vc Mag [3] Volts Fault 4 pre-fault phase C voltage magnitude
9155 Prefault Vc Ang [3] Degrees Fault 4 pre-fault phase C voltage angle
9156 Postfault Ia Mag [3] Amps Fault 4 post-fault phase A current magnitude
9158 Postfault Ia Ang [3] Degrees Fault 4 post-fault phase A current angle
9159 Postfault Ib Mag [3] Amps Fault 4 post-fault phase B current magnitude
9161 Postfault Ib Ang [3] Degrees Fault 4 post-fault phase B current angle
9162 Postfault Ic Mag [3] Amps Fault 4 post-fault phase C current magnitude
9164 Postfault Ic Ang [3] Degrees Fault 4 post-fault phase C current angle
9165 Postfault Va Mag [3] Volts Fault 4 post-fault phase A voltage magnitude
9167 Postfault Va Ang [3] Degrees Fault 4 post-fault phase A voltage angle
9168 Postfault Vb Mag [3] Volts Fault 4 post-fault phase B voltage magnitude
9170 Postfault Vb Ang [3] Degrees Fault 4 post-fault phase B voltage angle
9171 Postfault Vc Mag [3] Volts Fault 4 post-fault phase C voltage magnitude
9173 Postfault Vc Ang [3] Degrees Fault 4 post-fault phase C voltage angle
9174 Fault Type [3] --- Fault 4 type
9175 Fault Location [3] --- Fault 4 location
9176 Prefault Ia Mag [4] Amps Fault 5 pre-fault phase A current magnitude
9178 Prefault Ia Ang [4] Degrees Fault 5 pre-fault phase A current angle
9179 Prefault Ib Mag [4] Amps Fault 5 pre-fault phase B current magnitude
9181 Prefault Ib Ang [4] Degrees Fault 5 pre-fault phase B current angle
9182 Prefault Ic Mag [4] Amps Fault 5 pre-fault phase C current magnitude
9184 Prefault Ic Ang [4] Degrees Fault 5 pre-fault phase C current angle
9185 Prefault Va Mag [4] Volts Fault 5 pre-fault phase A voltage magnitude
9187 Prefault Va Ang [4] Degrees Fault 5 pre-fault phase A voltage angle
9188 Prefault Vb Mag [4] Volts Fault 5 pre-fault phase B voltage magnitude
9190 Prefault Vb Ang [4] Degrees Fault 5 pre-fault phase B voltage angle
9191 Prefault Vc Mag [4] Volts Fault 5 pre-fault phase C voltage magnitude
9193 Prefault Vc Ang [4] Degrees Fault 5 pre-fault phase C voltage angle
9194 Postfault Ia Mag [4] Amps Fault 5 post-fault phase A current magnitude
9196 Postfault Ia Ang [4] Degrees Fault 5 post-fault phase A current angle
9197 Postfault Ib Mag [4] Amps Fault 5 post-fault phase B current magnitude
9199 Postfault Ib Ang [4] Degrees Fault 5 post-fault phase B current angle
9200 Postfault Ic Mag [4] Amps Fault 5 post-fault phase C current magnitude
9202 Postfault Ic Ang [4] Degrees Fault 5 post-fault phase C current angle
9203 Postfault Va Mag [4] Volts Fault 5 post-fault phase A voltage magnitude
9205 Postfault Va Ang [4] Degrees Fault 5 post-fault phase A voltage angle
9206 Postfault Vb Mag [4] Volts Fault 5 post-fault phase B voltage magnitude
9208 Postfault Vb Ang [4] Degrees Fault 5 post-fault phase B voltage angle
9209 Postfault Vc Mag [4] Volts Fault 5 post-fault phase C voltage magnitude
9211 Postfault Vc Ang [4] Degrees Fault 5 post-fault phase C voltage angle
9212 Fault Type [4] --- Fault 5 type
9213 Fault Location [4] --- Fault 5 location
12306 Oscill Num Triggers --- Oscillography number of triggers
13504 DCmA Inputs 1 Value mA DCmA input 1 actual value
A
13576 RTD Inputs 25 Value --- RTD input 25 actual value
13577 RTD Inputs 26 Value --- RTD input 26 actual value
13578 RTD Inputs 27 Value --- RTD input 27 actual value
13579 RTD Inputs 28 Value --- RTD input 28 actual value
13580 RTD Inputs 29 Value --- RTD input 29 actual value
13581 RTD Inputs 30 Value --- RTD input 30 actual value
13582 RTD Inputs 31 Value --- RTD input 31 actual value
13583 RTD Inputs 32 Value --- RTD input 32 actual value
13584 RTD Inputs 33 Value --- RTD input 33 actual value
13585 RTD Inputs 34 Value --- RTD input 34 actual value
13586 RTD Inputs 35 Value --- RTD input 35 actual value
13587 RTD Inputs 36 Value --- RTD input 36 actual value
13588 RTD Inputs 37 Value --- RTD input 37 actual value
13589 RTD Inputs 38 Value --- RTD input 38 actual value
13590 RTD Inputs 39 Value --- RTD input 39 actual value
13591 RTD Inputs 40 Value --- RTD input 40 actual value
13592 RTD Inputs 41 Value --- RTD input 41 actual value
13593 RTD Inputs 42 Value --- RTD input 42 actual value
13594 RTD Inputs 43 Value --- RTD input 43 actual value
13595 RTD Inputs 44 Value --- RTD input 44 actual value
13596 RTD Inputs 45 Value --- RTD input 45 actual value
13597 RTD Inputs 46 Value --- RTD input 46 actual value
13598 RTD Inputs 47 Value --- RTD input 47 actual value
13599 RTD Inputs 48 Value --- RTD input 48 actual value
13600 Ohm Inputs 1 Value Ohms Ohm inputs 1 value
13601 Ohm Inputs 2 Value Ohms Ohm inputs 2 value
14189 PTP–IRIG-B Delta ns PTP time minus IRIG-B time
24447 Active Setting Group --- Current setting group
32768 Tracking Frequency Hz Tracking frequency
39168 FlexElement 1 Value --- FlexElement 1 actual value
39170 FlexElement 2 Value --- FlexElement 2 actual value
39172 FlexElement 3 Value --- FlexElement 3 actual value
39174 FlexElement 4 Value --- FlexElement 4 actual value
39176 FlexElement 5 Value --- FlexElement 5 actual value
39178 FlexElement 6 Value --- FlexElement 6 actual value
39180 FlexElement 7 Value --- FlexElement 7 actual value
39182 FlexElement 8 Value --- FlexElement 8 actual value
39184 FlexElement 9 Value --- FlexElement 9 actual value
39186 FlexElement 10 Value --- FlexElement 10 actual value
39188 FlexElement 11 Value --- FlexElemen 11 actual value
39190 FlexElement 12 Value --- FlexElement 12 actual value
39192 FlexElement 13 Value --- FlexElement 13 actual value
39194 FlexElement 14 Value --- FlexElement 14 actual value
39196 FlexElement 15 Value --- FlexElement 15 actual value
39198 FlexElement 16 Value --- FlexElement 16 actual value
42336 PID 1 Out --- PID 1 out
42338 PID 1 Delta Out --- PID 1 delta out
VENDOR GE 2910
# Management authorization
BEGIN-VENDOR GE
# Role ID
ATTRIBUTE GE-UR-Role 1 integer
# GE-UR-ROLE values
VALUE GE-UR-Role Administrator 1
VALUE GE-UR-Role Supervisor 2
VALUE GE-UR-Role Engineer 3
VALUE GE-UR-Role Operator 4
VALUE GE-UR-Role Observer 5
B END-VENDOR GE
#############################################################
6. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
For example, the file can look like the following:
$INCLUDE ../shareéfreeradius/dictionary
$INCLUDE dictionary.ge
7. For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors.
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS parameters on the UR as follows.
8.1. If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default
password is "ChangeMe1#".
8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave
the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf
file.
9. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "testpw"). Check that the RADIUS server log
file shows the access with an "Access-Accept" entry.
Recall that If you tried another third-party tool and it did not work, you can use the FreeRADIUS software from
freeradius.net.
Appendix C: Miscellaneous
Miscellaneous
C.1 Warranty
For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years.
For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at
https://www.gedigitalenergy.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.
Table C-2: Major changes for F35 manual version AB1 (English)
Page Description
--- Updated document throughout and put into new template. Major revision.
--- Updated references to digital inputs/outputs to contact inputs/outputs for consistency
--- Added content for advanced IEC 61850, for example in the Settings and Actual Values chapters
Page Description
2- Updated Order Codes and Specifications
5-28 Added RS232 Baud Rate setting to Serial Ports section. Baud rate is now configurable, with two options.
5-32 Added Far-End Fault Indication (FEFI) section
9-2 Added Software Upgrade section to the Maintenance chapter
--- Moved communications appendices B through F to new UR Series Communications Guide for UR 7.3x AB1
C-1 Updated product warranty from 24 months to 10 years
Table C-3: Major changes for F35 manual version AA1 (English)
Page Page Change Description
(Z1) (AA1)
--- --- Add Added content for IEC 60870-5-103 throughout document
--- 10- Add Added Maintenance chapter, moving content from other chapters and adding new instructions to
replace the battery
Abbreviations
T Time, transformer
TC Thermal Capacity
TCP Transmission Control Protocol
TCU Thermal Capacity Used
TD MULT Time Dial Multiplier
TEMP Temperature
TFTP Trivial File Transfer Protocol
THD Total Harmonic Distortion
TMR Timer
TOC Time Overcurrent
TOV Time Overvoltage
TRANS Transient
TRANSF Transfer
TSEL Transport Selector
TUC Time Undercurrent
TUV Time Undervoltage
TX (Tx) Transmit, Transmitter
U Under
UC Undercurrent
UCA Utility Communications Architecture
UDP User Datagram Protocol
UL Underwriters Laboratories
UNBAL Unbalance
UR Universal Relay
URC Universal Recloser Control
.URS Filename extension for settings files
UV Undervoltage
Index
Autoreclose
Numerics actual values .........................................................................................6-5
10BASE-F settings ...............................................................................5-31 FlexLogic operands .......................................................................5-137
8-bit switch logic diagram ...................................................................................5-194
FlexLogic operands .......................................................................5-137 settings ...............................................................................................5-191
settings ...............................................................................................5-201 single shot sequence ....................................................................5-196
specifications ......................................................................................2-18 Auxiliary overvoltage
FlexLogic operands .......................................................................5-137
logic ......................................................................................................5-180
settings ...............................................................................................5-179
A specifications ..................................................................................... 2-16
AC current input specifications ...................................................2-20 Auxiliary undervoltage
AC current inputs ..............................................................................5-115 FlexLogic operands .......................................................................5-137
AC inputs ...................................................................................................3-11 logic diagram ...................................................................................5-179
AC voltage input specifications ...................................................2-20 settings ...............................................................................................5-178
Active setting group ........................................................................5-155 specifications ..................................................................................... 2-15
Actual values ............................................................................................ 6-1 Auxiliary voltage channel ............................................................... 3-12
Administrator Auxiliary voltage metering ............................................................. 6-17
add user account ..............................................................................5-13 AWG wire size .................................................... 3-11, 3-29, 3-32, 3-34
command to force logoff ................................................................ 7-4
role for CyberSentry .......................................................................... 2-4
Alarm LEDs ..............................................................................................5-95
ANSI device numbers .......................................................................... 2-2
B
Apparent power ....................................................................................6-17 Back up settings ...................................................................... 5-44, 10-2
Apparent power specifications ....................................................2-20 Banks ................................................................................5-6, 5-115, 5-116
Application examples Battery
disposal ................................................................................................. 10-9
breaker trip circuit integrity ......................................................5-199
failure message ...................................................................................7-6
contact inputs .................................................................................5-220
replace .................................................................................................. 10-7
direct inputs and outputs ..........................................................5-225
latching outputs .............................................................................5-222 Baud rate ................................................................................................. 5-28
Approvals .................................................................................................2-29 BLOCK setting ..........................................................................................5-5
Architecture, relay ............................................................................5-135 Breaker arcing current
Arcing current .....................................................................................5-203 actual values ...................................................................................... 6-23
clearing ........................................................................................5-27, 7-2
Authentication by device or server ...........................................5-15
FlexLogic operands .......................................................................5-138
Automatic discovery of UR devices ...........................................3-47
logic diagram ...................................................................................5-205
measurement ..................................................................................5-204
settings ...............................................................................................5-203
specifications ..................................................................................... 2-16
Outputs
N contact outputs ..............................................................................5-221
Nameplate, rear ..................................................................................... 3-1 control power specifications ...................................................... 2-24
Negative sequence IOC critical failure relay specifications ............................................ 2-23
FlexLogic operands .......................................................................5-139 Fast form-C relay specifications ............................................... 2-23
logic diagram ...................................................................................5-175 Form-A relay ........................................................................... 2-22, 3-13
settings ...............................................................................................5-174 Form-C relay ....................................................................................... 3-13
specifications ......................................................................................2-15 Form-C relay specifications ........................................................ 2-23
Negative sequence TOC latching output specifications ................................................... 2-23
FlexLogic operands .......................................................................5-139 latching outputs ..............................................................................5-222
logic diagram ...................................................................................5-174 virtual outputs .................................................................................5-224
settings ...............................................................................................5-173 Overcurrent curve types ...............................................................5-156
specifications ......................................................................................2-15 Overcurrent curves
Neutral IOC FlexCurves .........................................................................................5-160
FlexLogic operands .......................................................................5-139 I²t ...........................................................................................................5-160
logic diagram ...................................................................................5-166 IAC .........................................................................................................5-159
settings ...............................................................................................5-165 IEC .........................................................................................................5-157
specifications ......................................................................................2-14 Overfrequency
Neutral overvoltage testing .......................................................................................................8-1
FlexLogic operands .......................................................................5-139 Overvoltage
logic diagram ...................................................................................5-178 auxiliary ..................................................................................2-16, 5-179
settings ...............................................................................................5-178 neutral .....................................................................................2-16, 5-178
specifications ......................................................................................2-16
Neutral TOC
FlexLogic operands .......................................................................5-139 P
logic diagram ...................................................................................5-165 Panel cutout .....................................................................................3-2, 3-3
settings ...............................................................................................5-164 Parallel Redundancy Protocol
specifications ......................................................................................2-14 actual values ...................................................................................... 6-10
Non-volatile latches explained .............................................................................................. 5-33
FlexLogic operands .......................................................................5-139 settings ................................................................................................. 5-31
settings ...............................................................................................5-154 specifications ..................................................................................... 2-25
specifications ......................................................................................2-17 Parity .......................................................................................................... 5-28
Part numbering .......................................................................................2-6
Passwords
O authentication by device or server .......................................... 5-15
One-shot bypass authentication ................................................................... 5-22
FlexLogic operators ......................................................................5-144 change .................................................................................................. 4-27
Operating temperature ....................................................................2-27 change after installation .............................................................. 3-54
Operating times ....................................................................................2-14 command ...................................................................................4-27, 5-9
Operator command to force logoff ............................................. 7-4 default ................................................................................................... 5-13
Order codes .............................................................................................. 2-6 explained .................................................................................................2-3
actual values .......................................................................................6-24 FlexLogic operands .......................................................................5-142
update ...................................................................................................... 7-3 lockout ....................................................................................... 4-28, 5-13
Oscillatory transient testing specifications ..........................2-28 lost password ........................................................................................5-7
Oscillography requirements .........................................................................................5-7
actual values .......................................................................................6-22 reset to factory defaults ..................................................................5-7
clearing ........................................................................................ 5-27, 7-2 rules ...........................................................................................................5-7
settings ..................................................................................................5-88 settings ........................................................................................4-27, 5-9
specifications ......................................................................................2-19 settings templates ..............................................................................4-5
via EnerVista software ..................................................................... 4-2 wrong entry ........................................................................................ 4-28
Permissive functions .......................................................................5-176
Per-unit quantity ....................................................................................5-4
Phase angle metering ...................................................................... 6-12
Phase current metering .................................................................. 6-15
Resetting Self-tests
FlexLogic operands .......................................................................5-143 description ..............................................................................................7-5
setting to clear LEDs and messages ....................................5-224 error messages ....................................................................................7-6
to factory defaults .............................................................................. 5-7 FlexLogic operands .......................................................................5-143
Restart relay user-programmable ....................................................................... 5-96
using EnerVista ..................................................................................5-44 Serial number ......................................................................3-1, 4-9, 6-24
using relay .............................................................................................. 7-3 Serial ports
Restore settings ....................................................................................10-2 settings ................................................................................................. 5-28
Revision history ....................................................................................... C-1 specifications ..................................................................................... 2-25
RF immunity specifications ............................................................2-28 Server authentication ....................................................................... 5-15
RFI, conducted specifications .......................................................2-28 Setting groups ......................................................................5-155, 5-182
RMS voltage specifications ............................................................2-19 active setting group ......................................................................5-155
Rolling demand .....................................................................................5-93 FlexLogic operands .......................................................................5-140
RS232 Settings ........................................................................................................5-1
baud rate ..............................................................................................5-28 back up ..................................................................................... 5-44, 10-2
configuration ......................................................................................3-48 change .................................................................................................. 4-14
specifications ......................................................................................2-25 control user accounts .................................................................... 5-13
wiring ......................................................................................................3-22 edit .......................................................................................................... 4-14
RS422 export .................................................................................................... 10-2
configuration ......................................................................................3-32 restore ................................................................................................... 10-2
timing .....................................................................................................3-33 Settings file ............................................................................................. 5-44
two-channel application ...............................................................3-32 Settings files ..................................................................................4-1, 4-10
with fiber interface ...........................................................................3-34 Settings password .....................................................................4-27, 5-9
RS485 Settings templates
description ...........................................................................................3-23 description ..............................................................................................4-3
settings ..................................................................................................5-28 edit .............................................................................................................4-4
specifications ......................................................................................2-25 enable .......................................................................................................4-4
RTD inputs password protection .........................................................................4-5
actual values .......................................................................................6-21 remove .....................................................................................................4-7
settings ...............................................................................................5-231 view ...........................................................................................................4-6
specifications ......................................................................................2-21 SFP module fail message ..................................................................7-9
Rules for passwords ............................................................................. 5-7 Signal loss detection for fiber ...................................................... 5-32
RxGOOSE Signal sources
actual values .......................................................................................6-21 description ..............................................................................................5-5
error messages .................................................................................... 7-8 metering ............................................................................................... 6-15
settings ..................................................................................................5-51 settings ...............................................................................................5-118
Single-line diagram ...............................................................................2-2
Smart defaults ...................................................................................... 5-88
S SNTP protocol
Save settings ............................................................................................ 4-1 accuracy specifications ................................................................ 2-25
error messages ....................................................................................7-7
Security
port, close ............................................................................................ 5-85
commands ............................................................................................. 7-4
settings ................................................................................................. 5-85
delete files and records ..............................................................10-12
lock FlexLogic equations ................................................................. 4-8
Software
installation ........................................................................................... 3-43
password for settings template ................................................... 4-5
interface explained ............................................................................4-1
passwords for settings and commands ...................... 4-27, 5-9
system requirements ..................................................................... 3-43
settings ..................................................................................................5-20
updates ................................................................................................. 10-5
Selector switch
actual values ......................................................................................... 6-6
Source frequency ................................................................................ 6-19
application example .....................................................................5-188 Source transfer schemes .............................................................5-176
FlexLogic operands .......................................................................5-140 Sources
logic diagram ...................................................................................5-189 description ..............................................................................................5-5
settings ...............................................................................................5-183 example of use ................................................................................5-119
specifications ......................................................................................2-18 metering ............................................................................................... 6-15
timing ..................................................................................................5-187 settings ...............................................................................................5-118
Specifications ........................................................................................ 2-14
Standards, certification ................................................................... 2-29
Status LEDs ............................................................................................. 4-19
Updates
firmware ................................................................................................10-4 W
firmware version error ...................................................................10-5 Warranty .....................................................................................................C-1
instruction manual ............................................................................. 3-1 Watt-hour specifications ................................................................ 2-20
order code .............................................................................................. 7-3 Watt-hours .............................................................................................. 6-18
software ................................................................................................10-5 Wattmetric zero-sequence directional
URS settings file ........................................................................5-44, 10-2 actual values ...................................................................................... 6-21
User accounts FlexLogic operands .......................................................................5-141
add ...........................................................................................................5-13 logic diagram ...................................................................................5-170
authentication by device or server ..........................................5-15 settings ...............................................................................................5-166
passwords for settings and commands ...................... 4-27, 5-9 specifications ..................................................................................... 2-15
User-definable displays Web server protocol .......................................................................... 5-73
example ..............................................................................................5-105 Wire size
invoking and scrolling ..................................................................5-104 CT/VT ...................................................................................................... 3-11
settings ...............................................................................................5-104 G.703 and fiber interface .............................................................. 3-34
specifications ......................................................................................2-18 G.703 interface .................................................................................. 3-29
User-programmable LEDs RS422 and fiber interface ............................................................ 3-34
custom labels .....................................................................................4-20 RS422 interface ................................................................................. 3-32
defaults ..................................................................................................4-20 Wiring diagram .......................................................................................3-9
settings ..................................................................................................5-95 Wrong transceiver message ...........................................................7-9
specifications ......................................................................................2-18
User-programmable pushbuttons
FlexLogic operands .......................................................................5-143
logic diagrams ................................................................................5-102 Z
settings ..................................................................................................5-98 Zero-sequence core balance ....................................................... 3-12
specifications ......................................................................................2-18
User-programmable self-tests
settings ..................................................................................................5-96
V
VAR hour
actual values .......................................................................................6-18
specifications ......................................................................................2-20
Vibration testing specifications ...................................................2-28
Virtual inputs
actual values ......................................................................................... 6-3
commands ............................................................................................. 7-2
FlexLogic operands .......................................................................5-142
logic diagram ...................................................................................5-221
settings ...............................................................................................5-220
Virtual outputs
actual values ......................................................................................... 6-5
FlexLogic operands .......................................................................5-142
settings ...............................................................................................5-224
Voltage banks .....................................................................................5-116
Voltage deviation specifications .................................................2-28
Voltage elements ..............................................................................5-176
Voltage metering
actual values .......................................................................................6-16
specifications ......................................................................................2-19
Voltage restraint characteristic ................................................5-162
VT inputs ...........................................................................3-11, 5-6, 5-116
VT wiring ...................................................................................................3-12