Low Impedance Bus Differential System: Grid Solutions
Low Impedance Bus Differential System: Grid Solutions
Low Impedance Bus Differential System: Grid Solutions
Grid Solutions
B90
Low Impedance Bus Differential
System
Instruction Manual
Product version: 7.7x
GE publication code: 1601-0115-AG2 (GEK-131031A)
E83849
S T ER
GI
ED
RE
ISO 9001
LISTED
G
E
IN
M U LT I L
IND.CONT. EQ.
52TL
1601-0115-AG2
Copyright © 2018 GE Multilin Inc. All rights reserved.
B90 Low Impedance Bus Differential System Instruction Manual for version 7.7x.
B90, FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Multilin, and GE Multilin are trademarks or registered trademarks
of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0115-AG2 (May 2018)
B90 Low Impedance Bus Differential System
Table of contents
ABBREVIATIONS
INDEX
Chapter 1: Introduction
Introduction
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Ensure that all connections to the product are correct so as to avoid accidental risk of shock
and/or fire, for example such as can arise from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the alternating current (AC), and voltage input match the ratings
specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
1 Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working
on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
Personal safety can be affected if the product is physically modified by the end user. Modifications to the product
outside of recommended wiring configuration, hardware, or programming boundaries is not recommended end-use
practice. Product disassembly and repairs are not permitted. All service needs to be conducted by the factory.
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
devices are considered safe to the unaided eye. Do not view directly with optical instruments.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
environments. Not to be used near electronic devices rated for Class B levels.
Product description
Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to
connect to a computer for the programming of settings and the monitoring of actual values. The rear RS485 port allows
independent access by operating and engineering staff. It can be connected to system computers with baud rates up to
115.2 kbps. All serial ports use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485
interface. IEC 60870-5-103, DNP, and Modbus cannot be enabled simultaneously on this interface. Also only one of the
DNP, IEC 60870-5-103, and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103
protocol is chosen, the RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The
100Base-FX or 100Base-TX Ethernet interface provides fast, reliable communications in noisy environments. The Ethernet
2 port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access
to the relay via any standard web browser (B90 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet
port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when
purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The B90 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
The available zones of differential protection and their size (maximum number of inputs) are optional and
controlled by the software option portion of the order code. The breaker failure function is also optional. See
the ordering section for information on the maximum number of zones and inputs for a given model. In
addition, different applications can require differing numbers of B90s with different hardware configurations.
Table 2-1: ANSI device numbers and functions supported
Device Function Device Function
number number
27 Undervoltage 51 Time overcurrent
50 Instantaneous overcurrent 50BF Breaker failure
50/74 CT trouble 50EF End fault protection
50/87 Unrestrained bus differential
Isolator position
Breaker position and trip
50 27 50 50 27 50
Zone 1
Zone 2
87B 50/87 50/74
Zone 3
87B 50/87 50/74
Zone 4
87B 50/87 50/74
Function Function
IEC 60870-5-103 communications User-programmable pushbuttons
FlexLogic equations User-programmable self-tests
IEC 61850 communications Virtual inputs (64 per IED)
IEC 62351-9 data and communications security Virtual outputs (96 per IED)
Metering: current, voltage, frequency
2
2.2 Security
The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled
automatically, and the default Password security and EnerVista security are disabled.
Administrator
Engineer
Operator
2 Observer Supervisor
842838A2.CDR
Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security
The B90 is provided with an option of protecting 8, 16, or 24-feeder busbars. When ordered as an eight-feeder
protection system, the B90 is configurable for up to eight-input bus differential, regardless of the number of
physical current inputs available in the B90 IEDs.
The relay is available as a 19-inch rack horizontal mount unit and consists of the following modules: power supply, CPU,
CTs and VTs, contact inputs and outputs, and inter-relay communications. Each of these modules can be supplied in a
number of configurations specified at the time of ordering. The information required to completely specify the relay is
provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. See the web page for the product for the latest options.
The letters in the top row of the table correspond to slots in the UR chassis, for example slot F, H, or U.
The R-GOOSE protocol described in IEC 61850-8-1 is available through the IEC 61850 software option. R-GOOSE
security requires the CyberSentry software option.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are
in English.
2 EB
EC
ED
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IEEE 1588 + PRP + single-zone 24-feeder bus protection + breaker failure
IEEE 1588 + PRP + six-zone 8-feeder bus protection + breaker failure + IEC 61850
IEEE 1588 + PRP + six-zone 16-feeder bus protection + breaker failure + IEC
61850
EE | | | | | | | | | | IEEE 1588 + PRP + six-zone 24-feeder bus protection + breaker failure + IEC
61850
EF | | | | | | | | | | IEEE 1588 + PRP + single-zone 24-feeder bus protection + breaker failure + IEC
61850
F0 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection
F1 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection
F2 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection
F3 | | | | | | | | | | PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection
F4 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + IEC 61850
F5 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection + IEC 61850
F6 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection + IEC 61850
F7 | | | | | | | | | | PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection + IEC 61850
F8 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + breaker failure
F9 | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection + breaker failure
FA | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection + breaker failure
FB | | | | | | | | | | PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection + breaker failure
FC | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + breaker failure + IEC
61850
FD | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection + breaker failure +
IEC 61850
FE | | | | | | | | | | PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection + breaker failure +
IEC 61850
FF | | | | | | | | | | PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection + breaker failure
+ IEC 61850
G0 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection
G1 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection
G2 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection
G3 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection
G4 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + IEC
61850
G5 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection + IEC
61850
G6 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection + IEC
61850
G7 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection + IEC
61850
G8 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + breaker
failure
G9 | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection +
breaker failure
GA | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection +
breaker failure
GB | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection +
breaker failure
GC | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus protection + breaker
failure + IEC 61850
GD | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus protection +
breaker failure + IEC 61850
GE | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus protection +
breaker failure + IEC 61850
GF | | | | | | | | | | IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection +
breaker failure + IEC 61850
J0 | | | | | | | | | | IEC 60870-5-103 + six-zone 8-feeder bus protection
J1 | | | | | | | | | | IEC 60870-5-103 + six-zone 16-feeder bus protection
J2 | | | | | | | | | | IEC 60870-5-103 + six-zone 24-feeder bus protection
J3 | | | | | | | | | | IEC 60870-5-103 + single-zone 24-feeder bus protection
J4 | | | | | | | | | | IEC 60870-5-103 + six-zone 8-feeder bus protection + IEC 61850
J5 | | | | | | | | | | IEC 60870-5-103 + six-zone 16-feeder bus protection + IEC 61850
J6 | | | | | | | | | | IEC 60870-5-103 + six-zone 24-feeder bus protection + IEC 61850
J7 | | | | | | | | | | IEC 60870-5-103 + single-zone 24-feeder bus protection + IEC 61850
J8 | | | | | | | | | | IEC 60870-5-103 + six-zone 8-feeder bus protection + breaker failure
J9 | | | | | | | | | | IEC 60870-5-103 + six-zone 16-feeder bus protection + breaker failure
JA | | | | | | | | | | IEC 60870-5-103 + six-zone 24-feeder bus protection + breaker failure
JB | | | | | | | | | | IEC 60870-5-103 + single-zone 24-feeder bus protection + breaker failure
JC | | | | | | | | | | IEC 60870-5-103 + six-zone 8-feeder bus protection + breaker failure + IEC 61850
JD | | | | | | | | | | IEC 60870-5-103 + six-zone 16-feeder bus protection + breaker failure + IEC
61850
JE | | | | | | | | | | IEC 60870-5-103 + six-zone 24-feeder bus protection + breaker failure + IEC
61850
JF | | | | | | | | | | IEC 60870-5-103 + single-zone 24-feeder bus protection + breaker failure + IEC
61850
K0 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 8-feeder bus protection
K1 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 16-feeder bus protection
K2 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 24-feeder bus protection
K3 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + single-zone 24-feeder bus protection
K4 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 8-feeder bus protection + IEC
61850
K5 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 16-feeder bus protection + IEC
61850
K6 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + six-zone 24-feeder bus protection + IEC
61850
K7 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + single-zone 24-feeder bus protection + IEC
61850
KF | | | | | | | | | |
breaker failure + IEC 61850
IEC 60870-5-103 + IEEE 1588 + PRP + single-zone 24-feeder bus protection +
breaker failure + IEC 61850
2
L0 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus
protection
L1 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus
protection
L2 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus
protection
L3 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder
bus protection
L4 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus
protection + IEC 61850
L5 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus
protection + IEC 61850
L6 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus
protection + IEC 61850
L7 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder
bus protection + IEC 61850
L8 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus
protection + breaker failure
L9 | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus
protection + breaker failure
LA | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus
protection + breaker failure
LB | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder
bus protection + breaker failure
LC | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 8-feeder bus
protection + breaker failure + IEC 61850
LD | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 16-feeder bus
protection + breaker failure + IEC 61850
LE | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + six-zone 24-feeder bus
protection + breaker failure + IEC 61850
LF | | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder
bus protection + breaker failure + IEC 61850
MOUNT/COATING H | | | | | | | | | Horizontal (19” rack)
A | | | | | | | | | Horizontal (19” rack) with harsh-environmental coating
FRONT PANEL + INTERFACE C | | | | | | | | English display
D | | | | | | | | French display
R | | | | | | | | Russian display
A | | | | | | | | Chinese display
P | | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | | Enhanced front panel with English display
M | | | | | | | | Enhanced front panel with French display
Q | | | | | | | | Enhanced front panel with Russian display
U | | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | | Enhanced front panel with German display
J | | | | | | | | Enhanced front panel with German display and user-programmable
pushbuttons
H | | | | | | | | Enhanced front panel with Polish display
O | | | | | | | | Enhanced front panel with Polish display and user-programmable pushbuttons
E | | | | | | | | 7" Graphical front panel display in multiple languages with USB front port and
user-programmable pushbuttons (English, French, Chinese, Russian, Turkish,
German, Polish, Japanese)
POWER SUPPLY H | | | | | | | 125 / 250 V AC/DC
(redundant power supply H | | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
must be same type as main L | | | | | | | 24 to 48 V (DC only)
power supply) L | | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
ENHANCED DIAGNOSTICS CT/VT XX | XX | XX | | None
DSP 8L | 8L | 8L | | Standard 4CT/4VT with enhanced diagnostics
(requires all DSP to be enhanced 8N | 8N | 8N | | Standard 8CT with enhanced diagnostics
diagnostic) 8S | 8S | 8S | | Standard 7CT/1VT with enhanced diagnostics
CONTACT INPUTS/OUTPUTS XX XX XX XX XX XX | No Module
4A 4A 4A 4A 4A 4A | 4 Solid state (no monitoring) MOSFET outputs
4B 4B 4B 4B 4B 4B | 4 Solid state (voltage with optional current) MOSFET outputs
4C 4C 4C 4C 4C 4C | 4 Solid state (current with optional voltage) MOSFET outputs
4D 4D 4D 4D 4D 4D | 16 Contact inputs with auto-burnish
4L 4L 4L 4L 4L 4L | 14 Form-A (no monitoring) latchable outputs
2
6R 6R 6R 6R 6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 6S 6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 6T 6T 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6U 6U 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
67 67 67 67 67 67 | 8 Form-A (no monitoring) outputs
6W 6W 6W 6W 6W 6W | 30 Contact inputs - pin terminals (max 4 modules)
6X 6X 6X 6X 6X 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
INTER-RELAY XX No Module
COMMUNICATIONS 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
(select a maximum of 1 per unit) 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
UR - ** - *
| 3I | Enhanced front panel with German display
| 3J | Enhanced front panel with German display and user-programmable pushbuttons
| 3H | Enhanced front panel with Polish display
| 3O | Enhanced front panel with Polish display and user-programmable pushbuttons
| 3Z | Enhanced front panel with Japanese display
| 3X | Enhanced front panel with Japanese display and user-programmable pushbuttons
| 3E | 7" Graphical front panel display in multiple languages with USB front port and user-programmable pushbuttons
CONTACT INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
2
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
| 6W | 30 Contact inputs - pin terminals (max 4 modules)
| 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multimode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
2
CT/VT Fourier ponents
I Frequency
D
T
RMS
values
Synchro-
Sampling phasors Analog Outputs
DSP module frequency filtering
module
Tracking
HMI frequency Events
Protection
Ethernet selection,
algorithms Control
ports estimation Comtrade, data
I> elements,
Communi-
monitoring logger
Serial cation Z<
Serial
ports protocols U< elements,
FlexLogic, DNP, Modbus,
IEC60870
IRIG-B
Accurate
IEEE Real-Time Time stamping PMU (IEEE C37.118,
Ethernet
1588 clock Synchrophasors Aggregation, IEC 61850-90-5)
SNTP calculations post-filtering IEC 61850 (GOOSE,
CPU module MMS Server)
Contact Inputs
Analog Inputs
Inter-relay
Inter-relay
comms
module
module
module
comms
module
Ddebounce Channel A
filtering monitoring
CRC check D Contact Outputs
module
G.703, RS-422,
Optoisolated C37.94, direct fiber DCmA, RTD
859740A1.vsd
The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is adjusted dynamically to the actual system frequency by an accurate and fast frequency tracking
system.
The analog/digital converter has the following ranges of AC signals:
Voltages:
Eq. 2-1
Currents:
Eq. 2-2
Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.
True RMS value for the current is calculated on a per-phase basis. The true RMS can be used for demand recording or as an
input signal to Time Overcurrent function, if the latter is intended for thermal protection. The true RMS is calculated as per
the widely accepted definition:
Eq. 2-3
RMS values include harmonics, inter-harmonics, DC components, and so on, along with fundamental frequency values.
The true RMS value reflects thermal effects of the current and is used for the thermal related monitoring and protection
2
functions.
Protection and control functions respond to phasors of the fundamental and/or harmonic frequency components
(magnitudes and angles), with an exception for some functions that have an option for RMS or fundamental
measurements, or some function responding to RMS only. This type of response is explained typically in each element's
section in this instruction manual.
Currents are pre-filtered using a Finite Impulse Response (FIR) digital filter. The filter is designed to reject DC components
and low-frequency distortions, without amplifying high-frequency noise. This filter is referred to as a modified MIMIC filter,
which provides excellent filtering and overall balance between speed and accuracy of filtering. The filter is cascaded with
the full-cycle Fourier filter for the current phasor estimation.
Voltages are pre-filtered using a patented FIR digital filter. The filter has been optimized to reject voltage-transformer-
specific distortions, such as Capacitive Voltage Transformer (CVT) noise and high-frequency oscillatory components. The
filter is cascaded with the half-cycle Fourier filter for the voltage phasor estimation.
The URs measure power system frequency using the Clarke transformation by estimating the period of the waveform from
two consecutive zero-crossings in the same direction (negative-to-positive). Voltage or current samples are pre-filtered
using a Finite Impulse Response (FIR) digital filter to remove high frequency noise contained in the signal. The period is
used after several security conditions are met, such as true RMS signal must be above 6% nominal for a certain time. If
these security conditions are not met, the last valid measurement is used for a specific time after which the UR reverts to
nominal system frequency.
Synchrophasors are calculated using a patented convolution integral algorithm. This algorithm allows use of the same
time-stamped samples, which are used for protection and taken at the same sampling frequency. This allows URs to use
one sampling clock for both protection algorithms and synchrophasors.
Synchrophasors on firmware versions 7.23 and up have been tested and certified to meet IEEE C37.118-2011 and
C37.118.1a-2014 standards for both metering and protection classes with outputs available up to 60 synchrophasors per
second for the metering class and 120 synchrophasors per second for the protection class. Synchrophasors measurement
is also available via IEC 61850-90-5 protocol.
The contact inputs threshold is settable in the firmware with 17, 33, 84, and 166 V DC settings available. Inputs are scanned
every 0.5 ms and can be conditioned for the critical applications, using debounce time timer, settable from 0.0 to 16.0 ms.
Contact inputs with auto-burnishing are available as well, when external contacts are exposed to the contamination in a
harsh industrial environment.
All measured values are available in the UR metering section on the front panel and via communications protocols.
Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64
samples per power cycle. Analog values can be captured with the Data Logger, allowing much slower rates extended over
a long period of time.
Other advanced UR order code options are available to support IEC 61850 (including fast GOOSE, ICD/CID/IID files, and so
on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, CyberSentry (advanced cyber security), the Parallel
Redundancy Protocol (PRP), IEC 60870-5-103, and so on.
2.5 Specifications
Specifications are subject to change without notice.
CT TROUBLE
Responding to: Differential current
Pickup level: 0.020 to 2.000 pu in steps of 0.001
Pickup delay: 1.0 to 60.0 sec. in steps of 0.1
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Availability: one per zone of protection
ISOLATOR MONITORING
Responding to: Both normally-open and normally-closed auxiliary contacts
Asserting: Isolator Position, Isolator Alarm, Block Switching
Alarm pickup delay: 0.00 to 120.00 s in steps of 0.05
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
TIME OVERCURRENT
Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy:
0.1 to 2.0 CT 0.5% of reading or 1% of nominal (whichever is greater)
above 2.0 CT 1.5% of reading
Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/Extremely Inverse; I2t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)
TD multiplier: 0.00 to 600.00 in steps of 0.01
Reset type: Instantaneous or Timed (per IEEE)
Curve timing accuracy at 1.03 to 20 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
INSTANTANEOUS OVERCURRENT
Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy:
0.1 to 2.0 CT 0.5% of reading or 1% of nominal (whichever is greater)
above 2.0 CT 1.5% of reading
Pickup delay: 0 to 65.535 s in steps of 0.001
Reset delay: 0 to 65.535 s in steps of 0.001
UNDERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0 to 65.535 s in steps of 0.001
Reset delay:
Timer accuracy:
0 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle (whichever is greater) 2
Operate time: <16 ms at <0.9 x pickup at 60 Hz
BREAKER FAILURE
Mode: 3-pole
Current supervision: phase current
Current supv. pickup: 0.020 to 30.000 pu in steps of 0.001
Current supv. dropout: 97 to 98% of pickup
Current supv. accuracy:
0.1 to 2.0 CT rating: ±0.75% of reading or ±2% of rated (whichever is greater)
above 2 CT rating: ±2.5% of reading
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
FLEXCURVES™
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1
FLEX STATES
Number: up to 256 logical variables grouped under 16 Modbus addresses
Programmability: any logical variable, contact, or virtual input
NON-VOLATILE LATCHES
Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
Output: stored in non-volatile memory
LED TEST
Initiation: from any contact input or user-programmable condition
Number of tests: 3, interruptible at any time
Duration of full test: approximately 3 minutes
Test sequence 1: all LEDs on
Test sequence 2: all LEDs off, one LED at a time on for 1 s
Test sequence 3: all LEDs on, one LED at a time off for 1 s
DIGITAL ELEMENTS
Number of elements: 48
Operating signal: any FlexLogic operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001
Dropout delay: 0.000 to 999999.999 s in steps of 0.001
Timing accuracy: ±3% or ±4 ms, whichever is greater
2.5.3 Monitoring
OSCILLOGRAPHY
Maximum records: 64
Sampling rate: 64 samples per power cycle
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; FlexLogic equation
Data: AC input channels; element state; contact input state; contact output state
Data storage: in non-volatile memory
EVENT RECORDER
Capacity: 1024 events
Time-tag: to 1 microsecond
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
Data storage: in non-volatile memory
2
USER-PROGRAMMABLE FAULT REPORT
Number of elements: 2
Pre-fault trigger: any FlexLogic operand
Fault trigger: any FlexLogic operand
Recorder quantities: 32 (any FlexAnalogTM value)
2.5.4 Metering
CURRENT METERING
Accuracy at
0.1 to 2.0 CT rating: ±0.25% of reading or ±0.1% of rated (whichever is greater)
2.0 CT rating: ±1.0% of reading
VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu: ±0.001 Hz (when voltage signal is used for frequency measurement)
I = 0.1 to 0.25 pu: ±0.005 Hz
I > 0.25 pu: ±0.02 Hz (when current signal is used for frequency measurement)
2.5.5 Inputs
AC CURRENT
CT rated primary: 1 to 50000 A
CT rated secondary: 1 or 5 A by connection
Relay burden: < 0.2 VA at rated secondary
Conversion range: 0.02 to 46 CT rating RMS symmetrical
Current withstand: 20 ms at 250 times rated
1 sec at 100 times rated
continuous 4xInom
URs equipped with 24 CT inputs have a maximum operating temperature of 50°C
Short circuit rating: 150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)
AC VOLTAGE
VT rated secondary: 50.0 to 240.0 V
VT ratio: 1.00 to 24000.00
Relay burden: < 0.25 VA at 120 V
Conversion range: 1 to 275 V
Voltage withstand: continuous at 260 V to neutral
1 min/hr at 420 V to neutral
FREQUENCY
Nominal frequency setting: 25 to 60 Hz
CONTACT INPUTS
Dry contacts: 1000 maximum
Wet contacts: 300 V DC maximum
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Tolerance: ±10%
IRIG-B INPUT
IRIG formats accepted: B000…B007, B120…B127
IRIG control bits: IEEE Std C37.118.1-2011
Amplitude modulation: 1 to 10 V pk-pk
DC shift: TTL–Compatible
Input impedance: 50 k
Isolation: 2 kV
DIRECT INPUTS
Input points: 256
Remote devices: 16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: Yes, No
Data rate: 64, 128, or 213 kbps
CRC: 32-bit
CRC alarm:
Responding to: Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
Unreturned message alarm:
Responding to: Rate of unreturned messages in the ring configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
HIGH RANGE
Nominal DC voltage: 125 to 250 V
Minimum DC voltage: 88 V
Maximum DC voltage: 300 V
Nominal AC voltage: 100 to 240 V at 50/60 Hz
Minimum AC voltage: 88 V at 25 to 100 Hz
Maximum AC voltage:
Voltage loss hold-up:
265 V at 25 to 100 Hz
200 ms duration at maximum load 2
ALL RANGES
Volt withstand: 2 Highest Nominal Voltage for 10 ms
Power consumption: typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code consumption
INTERNAL FUSE
Ratings:
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
Interrupting capacity:
AC: 100 000 A RMS symmetrical
DC: 10 000 A
2.5.7 Outputs
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6A
Break (DC inductive, L/R = 40 ms):
Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6 A as per IEEE C37.90
Break (DC resistive as per IEC61810-1):
Voltage Current
24 V 6A
48 V 1.6 A
125 V 0.4 A
250 V 0.2 A
Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A
Breaking capacity:
Break capability
0.5 seconds off
3.2 A at L/R = 10 ms 10 A at L/R = 40 ms 10 A at L/R = 40 ms
2
(0 to 250 V DC)
1.6 A at L/R = 20 ms
0.8 A
L/R = 40 ms
DIRECT OUTPUTS
Output points: 256
2.5.8 Communications
IEC 61850
IEC 61850: Supports IEC 61850 Editions 1.0 and 2.0. See the UR Family Communications Guide and its con-
formance statements.
RS485
1 rear port: up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance: 1200 m
Isolation: 2 kV, isolated together at 36 Vpk
OTHER
TFTP, SFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD), IEEE C37.118
RS422 distance is based on transmitter power and does not take into consideration the clock source provided by
the user.
Emitter, fiber type Cable type Transmit power Received Power budget Maximum
sensitivity optical input
power
820 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Single 9/125 μm -15 dBm -32 dBm 17 dBm -8 dBm
mode
1300 nm Laser, 9/125 μm 0 dBm -34 dBm 34 dBm -8 dBm
Single mode
1550 nm Laser, 9/125 μm 5 dBm -34 dBm 39 dBm -10 dBm
Single mode
The following specifications apply to filter interface modules implemented before January 2012.
The power budgets are calculated from the manufacturer’s worst-case transmitter power and worst case receiver
sensitivity.
The power budgets for the 1300 nm ELED are calculated from the manufacturer's transmitter power and receiver
sensitivity at ambient temperature. At extreme temperatures these values deviate based on component tolerance.
On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C.
Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one
installation to another, the distance covered by your system can vary.
FIBER LOSSES
820 nm multimode: 3 dB/km
1300 nm multimode: 1 dB/km
1300 nm single mode: 0.35 dB/km
1550 nm single mode: 0.25 dB/km
Splice losses: one splice every 2 km at 0.05 dB loss per splice
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses.
Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms
Pages: 5 single-line diagram pages with controls, status, and metering values
up to 8 annunciator pages with total of 96 annunciator windows
1 phasor metering page for each AC Source
5 tabular metering pages with dynamic metering and status
event records page with dynamic update
product information page
settings, actual values, error messages (targets)
LED INDICATORS
2 Functions: 5 device status indicators
9 event cause indicators
8 user-programmable pushbutton indicators
PUSHBUTTONS
Type: membrane
Functions: 5 bottom Tab pushbuttons and 1 Home pushbutton for page recall
4 directional, 1 ENTER, and 1 ESCAPE pushbutton element selection
10 side pushbuttons for power system element control
RESET pushbutton
8 physical user-programmable pushbuttons, 8 graphical interface pushbuttons
INGRESS PROTECTION
IP code: IP54 front, IP10 back (IP20 back with IP20 cover accessory)
2.5.12 Environmental
AMBIENT TEMPERATURES
Storage temperature: –40 to 85°C
Operating temperature: –40 to 60°C; the LCD contrast can be impaired at temperatures less than –20°C
HUMIDITY
Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days)
OTHER
Altitude: 2000 m (maximum)
Pollution degree: II
Overvoltage category: II
Ingress protection: IP20 front, IP10 back (basic front panel and Rev. 1 enhanced front panel)
IP40 front, IP10 back (Rev. 2 enhanced front panel)
IP54 front with IP54 mounting collar accessory (Rev. 2 enhanced front panel)
Ingress protection with IP20 cover accessory:
IP20 back
Noise: 0 dB
2.5.15 Approvals
APPROVALS
Compliance Applicable council directive According to
CE Low voltage directive EN 60255-5
EMC directive EN 60255-26 / EN 50263
EN 61000-6-5
2.5.16 Maintenance
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required. When dust has accumulated on the front panel display, wipe with a dry cloth.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
Chapter 3: Installation
Installation
This chapter outlines installation of hardware and software. You unpack, mount, wire the unit, turn on power, then install
the software and configure settings.
Model: B90D00HCHF8AH6AM6BP8BX7A
B90
RATINGS:
Mods: NONE
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA See manual
Bus Differential Relay Contact Inputs: 300 VDC Max 10mA
Wiring Diagram:
Inst. Manual: 1601-0115
Contact Outputs: Refer to Instruction Manual Serial Number: MAZB98000029
E83849 Firmware: D
GE Multilin Mfg. Date: NOV 26, 2012
- M A A B 9 7 0 0 0 0 9 9 -
PO Num: 600001234.56
Item Num:
LISTED
®
®
IND.CONT. EQ.
52TL - M A A B 9 7 0 0 0 0 9 9 -
836782A3.CDR
4. Any protective plastic film on the front panel is normally peeled off, but also can be left on.
5. For any issues, contact GE as outlined in the For Further Assistance section in chapter 1.
6. Check that you have the latest copy of the B90 Instruction Manual and the UR Family Communications Guide, for the
applicable firmware version, at http://www.gegridsolutions.com/multilin/manuals/index.htm
The Instruction Manual outlines how to install, configure, and use the unit. The Communications Guide is for advanced use
with communication protocols. The warranty is included at the end of this instruction manual and on the GE Grid Solutions
website.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
3
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm] 842807A1.CDR
9.687”
[24.605 cm] 10.97”
[27.86 cm]
6.995” 6.96”
[17.767 cm] [17.68 cm]
7.13” 4.000”
[181.1 mm] [101,60 mm]
17.750”
[450,85 mm] 842808A2.CDR
BEZEL OUTLINE
8x0.156”
(9.5 mm)
0.375”
(3.962 mm)
(47.6 mm)
10.90”
1.875”
8.97”
(227.8 mm) (276.8 mm)
9.80”
(248.9 mm) 6.960”
(9.5 mm)
0.375”
(176.8 mm)
(121.5 mm)
4.785”
0.375”
17.52” Brackets repositioned (9.5 mm)
(445.0 mm) for switchgear mounting 5.000” 0.375”
(127.0 mm)
9.520” (9.5 mm)
14.520” (241.8 mm)
CUTOUT
7.13” 4.00”
(181.1 mm) (101.6 mm) 7.00”
(177.8 mm)
17.75” 19.00”
(450.8 mm) (482.6 mm)
827704B5.cdr
11.093”
[281,76 mm]
9.687 “
[246,05 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
18.974”
[481,94 mm]
862700A1.cdr
MOUNTING PANEL
8.34”
[21.18 cm]
7.65”
[19.43 cm]
IP54 COLLAR
NOTES
1. INSPECT THE COLLAR BEFORE INSTALLATION, VERIFY GASKET IS ADHERED TO THE METAL ON ALL SIDES
2. MAKE SURE THE RELAY IS POSITIONED CENTER TO THE CUT OUT
3. INSTALL IP-54 COLLAR, CONFIRM THE GASKET PROPERLY MATES WITH THE PANEL ON ALL SIDES
SECURE USING #8-32 HEX NUT AT 6 PLACES. 842497A1.cdr
Ground
Model: B90D00HCHF8AH6AM6BP8BX7A
B90
RATINGS:
Mods: NONE
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA See manual
Bus Differential Relay Contact Inputs: 300 VDC Max 10mA
Wiring Diagram:
Inst. Manual: 1601-0115
Contact Outputs: Refer to Instruction Manual Serial Number: MAZB98000029
E83849 Firmware: D
GE Multilin Mfg. Date: NOV 26, 2012
- M A A B 9 7 0 0 0 0 9 9 -
PO Num: 600001234.56
Item Num:
LISTED
®
®
IND.CONT. EQ.
52TL - M A A B 9 7 0 0 0 0 9 9 -
X W V U T S R P N M L K J H G F D B
c b a c b a c b a c b a c b a c b a
b a
LK1
Tx1 1
1
2
Rx1
ACT1
2
3
LK2
3
Tx1
4
4
5
Tx2 b a
ACT2 5
3
1
1 6
2 LK3
2 6
3
Rx2 3 7
4
4 7
8
Tx2 ACT3 8
IN
Optional Optional Optional Optional Optional Optional CT/VT CPU module Power
direct contact CT/VT or contact CT/VT or contact module (T module shown) supply
input/output input/output contact input/output contact input/output module
module module input/output module input/output module
module module
836790A1.CDR
Do not touch any rear terminals while the relay is energized, else death or serious injury can
result from electrical shock.
Small form-factor pluggable ports (SFPs) are pluggable transceivers. They transmit, receive, and
convert electrical signals to optical signals and vice-versa. Supplied with the device, they are inserted
into the Ethernet ports on the CPU module. A photo in the Maintenance chapter shows this plug-in
device. Do not use non-validated transceivers or install validated transceivers in the wrong Ethernet
slot, else damage can occur.
Terminal number assignments are three characters long and assigned by module slot position, row number, and column
letter. Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module), indicated by
an arrow on the terminal block. The figure shows an example of rear terminal assignments.
J H G F Slot position
c b a c b a Column letter
Torque 9 inch-pounds
842761A2.CDR
The torque used to connect the screws that connect the terminal blocks (top screws a, b, c) and the metal plates over
empty slots to the chassis is 9 inch-pounds. For the screws used to wire the terminal blocks (rows 1 to 8), use 19±1 inch-
pounds.
The CPU module type depends on order code. During manufacturing, the power supply and CPU modules are installed in
slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. Wire
connections to these two modules at 13 inch-pounds.
Figure 3-8: CPU modules and power supply
RS485 Ethernet (3) RS485 Ethernet (3) RS485 Ethernet (3) RS485 Ethernet (3) Power
b a
LK1 LK1 LK1
RJ-45 1
LC copper 1
fiber 2
2
ACT1 ACT1 ACT1 Link, 3
LK2 LK2 LK2 Activity 3
4
4
5
b a
ACT2
b a
ACT2
b a
ACT2
b a 5
1
1
1
1
1
1
1
1 6
2 LK3 2 LK3 2 LK3 2
2 2 2 2 6
3 3 3 3
3 3 3 3 7
4 4 4 4
7
BNC
4 4 4 4
ST 8
for ACT3 ACT3 ACT3 fiber 8
IRIG-B
IN IN IN IN
T CPU module U CPU module V CPU module W CPU module Power supply
module
859758A1.CDR
The following figure shows the optical connectors for CPU modules.
3.3 Wiring
3.3.1 Typical wiring
Figure 3-10: B90 is a multi-IED protection system
A B C
IA5 F1a
IA F1b
IA1 F1c
F1
IB5 F2a IA5 F1a
IB F2b
3
IA F1b
IB1 F2c IA1 F1c
IC5 F3a IB5 F2a
F3b IA5 F1a
IC IB F2b
F3c IA F1b
IC1 IB1 F2c
IA1 F1c
IG5 F4a IC5 F3a
CURRENT INPUTS
IINPUTS
NPUTS
TS
IC1 F3c
8H
IB1 F2c
CURRENT INPU
IA5 F5a IG5 F4a
F5b IC5 F3a
IA
8H
IG
CURRENT
F4b
8
CURRENT INPUTS
F6a IC1 F3c
IB5 IA5 F5a
F6b IG5 F4a
IB IA F5b
8H
F6c IG F4b
IB1 IA1 F5c
F7a IG1 F4c
IC5 IB5 F6a
IED 1 F7b IA5 F5a
IC IB F6b
F7c IA F5b
IC1 IB1 F6c
IA1 F5c
IC5 F7a
IB5 F6a
IED 2 IC F7b
IB F6b
IC1 F7c
IB1 F6c
IC5 F7a
IED 3
IED IC F7b
IC1 F7c
I F1a
6H
F1 F1b
V
F1c
I F2a
F2 F2b
V
F2c
I F3a
F3 F3b
V
F3c
I F4a
F4 F4b
V
F4c
I F5a
F5 F5b
CONTACT INPUTS AND OUTPUTS
V
F5c
I F6a
F6 F6b
V
F6c
CONTACT INPUT F7a F7a
B90 Bus Differential CONTACT INPUT F7c F7c
Protection System CONTACT INPUT F8a F8a
CONTACT INPUT F8c F8c
COMMON F7b F7b
SURGE F8b
IED 4
836780A3.CDR
The wiring diagrams on the next four pages are based on the following order code:
B90-H02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H.
The purpose of these diagrams is to provide examples of how the B90 is typically wired, not
specifically how to wire your own relay. See the sections following the wiring diagrams for examples
on connecting your relay correctly based on your relay configuration and order code.
Figure 3-11: Typical wiring diagram (Phase A; T module shown for CPU)
A
IED2 RX1
IED4 RX2
IED4 TX1
IED2 TX2
NOTE: This diagram is based on the following order code: F1a
Tx1 Rx1 Tx2 Rx2 IA5 F1
B90-T02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H
This diagram provides an example of how the device IA F1b
FIBER FIBER
is wired, not specifically how to wire the device. Please CHANNEL 1 CHANNEL 2 IA1 F1c
refer to the Instruction Manual for additional details on B90 COMMUNICATIONS W7H
wiring based on various configurations. IB5 F2a
F2
IB F2b
IB1 F2c
IC5 F3a
F3
IC F3b
IC1 F3c
CURRENT INPUTS
IED 1 IG1 F4c
8H
(PHASE A PROTECTION) IA5 F5a
F5
IA F5b
IA1 F5c
H1a
3
I
IB5 F6a
F6
6H
H1b H1
V
H1c IB F6b
H2a I
H2 IB1 F6c
H2b
V
H2c F7a
IC5 F7
H3a I
H3b H3 IC F7b
V
H3c
H4a I IC1 F7c
H4b H4
V IG5 F8a
H4c F8
H5a I IG F8b
H5b H5
V
H5c IG1 F8c
H6a I
H6b H6
DIGITAL INPUTS/OUTPUTS
V
H6c IA5 L1a F9
H7a CONTACT INPUT H7a
H7c CONTACT INPUT H7c IA L1b
H8a CONTACT INPUT H8a
IA1 L1c
H8c CONTACT INPUT H8c
H7b COMMON H7b IB5 L2a F10
H8b SURGE
IB L2b
U1a I
L2c
6H
U1b U1 IB1
V
U1c L3a
U2a I
IC5 F11
U2b U2 IC L3b
V
U2c
U3a I IC1 L3c
U3b U3
V IG5 L4a F12
U3c
U4a I
IG L4b
U4 CURRENT INPUTS
U4b V
U4c IG1 L4c
8H
U5a I
U5 IA5 L5a F13
U5b V
U5c IA L5b
U6a I
U6 L5c
DIGITAL INPUTS/OUTPUTS
U6b V
IA1
Wet U6c
IB5 L6a
U7a CONTACT INPUT U7a F14
U7c CONTACT INPUT U7c
IB L6b
U8a CONTACT INPUT U8a
U8c CONTACT INPUT U8c IB1 L6c
U7b COMMON U7b
IC5 L7a
U8b SURGE F15
IC L7b
N1a
6A
I
N1b N1
L7c
V IC1
N1c
N2a I IG5 L8a
N2b N2
F16
V
N2c IG L8b
N3a L8c
IG1
N3b N3
N3c
N4a
N4b N4 IA5 S1a F17
Dry N4c
IA S1b
N5a CONTACT INPUT N5a
N5c CONTACT INPUT N5c IA1 S1c
N6a CONTACT INPUT N6a
N6c CONTACT INPUT N6c IB5 S2a F18
DIGITAL INPUTS/OUTPUTS
Rx1
Rx2
PORT 2
Ground at Rx3
twisted pairs
Remote
D1a
IA5 S5a F21
Device
RS485
D2a COM 2 IA S5b
D3a com
D4b IA1 S5c
Co-axial *
D4a IRIG-B
Input IB5 S6a
F22
CPU
Co-axial BNC
IB S6b
IB1 S6c
Co-axial * - For IRIG-B Input
B1b S7a
only use one CRITICAL IC5 F23
1
Figure 3-12: Typical wiring diagram (Phase B; T module shown for CPU)
B
IED2 RX1
IED4 RX2
IED4 TX1
IED2 TX2
F1
NOTE: This diagram is based on the following order code: IA5 F1a
B90-T02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H Tx1 Rx1 Tx2 Rx2
IB F2b
IB1 F2c
F3
IC5 F3a
IC F3b
IC1 F3c
F4
B90 BUS DIFFERENTIAL RELAY IG5 F4a
IG F4b
CURRENT INPUTS
IED 2 IG1 F4c
F5
8H
(PHASE B PROTECTION) IA5 F5a
IA F5b
IA1 F5c
F6
H1a F6a
3
I
IB5
6H
H1b H1
V
H1c IB F6b
H2a I
H2 IB1 F6c
H2b
V
F7
H2c IC5 F7a
H3a I
H3b H3 IC F7b
V
H3c
H4a I IC1 F7c
H4
F8
H4b F8a
V IG5
H4c
H5a I IG F8b
H5b H5
V
H5c IG1 F8c
H6a I
H6b H6 F9
DIGITAL INPUTS/OUTPUTS
V
H6c IA5 L1a
H7a CONTACT INPUT H7a
H7c CONTACT INPUT H7c IA L1b
H8a CONTACT INPUT H8a
IA1 L1c
H8c CONTACT INPUT H8c F10
H7b COMMON H7b IB5 L2a
H8b SURGE
IB L2b
U1a I
L2c
6H
U1b U1 IB1
V F11
U1c L3a
IC5
U2a I
U2b U2 IC L3b
V
U2c
U3a IC1 L3c
I
F12
U3b U3
V IG5 L4a
U3c
U4a I
IG L4b
CURRENT INPUTS
U4b U4
V
U4c IG1 L4c
F13
8H
U5a I
U5 IA5 L5a
U5b V
U5c IA L5b
U6a I
U6 L5c
DIGITAL INPUTS/OUTPUTS
U6b V
IA1
Wet U6c F14
IB5 L6a
U7a CONTACT INPUT U7a
U7c CONTACT INPUT U7c
IB L6b
U8a CONTACT INPUT U8a
U8c CONTACT INPUT U8c IB1 L6c
U7b COMMON U7b F15
IC5 L7a
U8b SURGE
IC L7b
N1a
6A
I
N1b N1
L7c
V IC1
N1c F16
N2a I IG5 L8a
N2b N2
V
N2c IG L8b
N3a L8c
IG1
N3b N3
N3c
N4a
F17
N4b N4 IA5 S1a
Dry N4c
IA S1b
N5a CONTACT INPUT N5a
N5c CONTACT INPUT N5c IA1 S1c
N6a CONTACT INPUT N6a F18
N6c CONTACT INPUT N6c IB5 S2a
DIGITAL INPUTS/OUTPUTS
Rx1
Rx2
PORT 2
Ground at Rx3
twisted pairs
Remote IA5 S5a
Device D1a
RS485
D2a COM 2 IA S5b
D3a com
D4b IA1 S5c
Co-axial *
D4a IRIG-B F22
Input IB5 S6a
CPU
Co-axial BNC
IB S6b
IB1 S6c
Co-axial * - For IRIG-B Input F23
B1b S7a
only use one CRITICAL IC5
1
Figure 3-13: Typical wiring diagram (Phase C; T module shown for CPU)
C
IED2 RX1
IED4 RX2
IED4 TX1
IED2 TX2
F1
NOTE: This diagram is based on the following order code: IA5 F1a
B90-T02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H Tx1 Rx1 Tx2 Rx2
IB F2b
F3
IB1 F2c
IC5 F3a
IC F3b
F4
IC1 F3c
IG F4b
CURRENT INPUTS
F5
IED 3 IG1 F4c
8H
(PHASE C PROTECTION) IA5 F5a
IA F5b
F6
IA1 F5c
3
H1a I
IB5 F6a
6H
H1b H1
V
H1c IB F6b
H2a I F7
H2 IB1 F6c
H2b
V
H2c IC5 F7a
H3a I
H3b H3 IC F7b
V
H3c F8
H4a I IC1 F7c
H4b H4
V IG5 F8a
H4c
H5a I IG F8b
H5b H5
V
H5c IG1 F8c
H6a I
F9
H6b H6
DIGITAL INPUTS/OUTPUTS
V
H6c IA5 L1a
H7a CONTACT INPUT H7a
H7c CONTACT INPUT H7c IA L1b
H8a CONTACT INPUT H8a
F10
IA1 L1c
H8c CONTACT INPUT H8c
H7b COMMON H7b IB5 L2a
H8b SURGE
IB L2b
U1a I F11
L2c
6H
U1b U1 IB1
V
U1c L3a
IC5
U2a I
U2b U2 IC L3b
V
U2c F12
U3a I IC1 L3c
U3b U3
V IG5 L4a
U3c
U4a I CURRENT INPUTS IG L4b
U4b U4 F13
V
U4c IG1 L4c
8H
U5a I
U5 IA5 L5a
U5b V
U5c IA L5b
U6a I
F14
U6 L5c
DIGITAL INPUTS/OUTPUTS
U6b V
IA1
Wet U6c
IB5 L6a
U7a CONTACT INPUT U7a
U7c CONTACT INPUT U7c
IB L6b
U8a CONTACT INPUT U8a
F15
U8c CONTACT INPUT U8c IB1 L6c
U7b COMMON U7b
IC5 L7a
U8b SURGE
IC L7b
N1a
6A
I
N1b N1 F16
V IC1 L7c
N1c
N2a I IG5 L8a
N2b N2
V
N2c IG L8b
N3a L8c
IG1
N3b N3 F17
N3c
N4a
N4b N4 IA5 S1a
Dry N4c
IA S1b
N5a CONTACT INPUT N5a F18
N5c CONTACT INPUT N5c IA1 S1c
N6a CONTACT INPUT N6a
N6c CONTACT INPUT N6c IB5 S2a
DIGITAL INPUTS/OUTPUTS
Rx1
Rx2
PORT 2 F21
Tx3 100BaseFX IG1 S4c
Shielded PORT 3
8H
Ground at Rx3
twisted pairs
Remote IA5 S5a
Device D1a
RS485
D2a COM 2 IA S5b
D3a com
F22
D4b IA1 S5c
Co-axial *
D4a IRIG-B
Input IB5 S6a
CPU
Co-axial BNC
IB S6b
F23
IB1 S6c
Co-axial * - For IRIG-B Input
B1b S7a
only use one CRITICAL IC5
1
Figure 3-14: Typical wiring diagram (breaker fail and isolator monitoring; T module shown)
IED2 RX1
IED4 RX2
IED4 TX1
IED2 TX2
NOTE: This diagram is based on the following order code: H1a
6H
I
B90-T02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H H1b H1 Tx1 Rx1 Tx2 Rx2
V
This diagram provides an example of how the device H1c
H2a FIBER FIBER
is wired, not specifically how to wire the device. Please I
CHANNEL 1 CHANNEL 2
H2b H2
refer to the Instruction Manual for additional details on V
B90 COMMUNICATIONS W7H
H2c
wiring based on various configurations. H3a I
H3b H3
V
H3c
H4a I
H4b H4
V
H4c
H5a I
H5b H5
V
H5c
3
H8c CONTACT INPUT H8c
H7b COMMON H7b
6H
U1a F1 F1b
6H
I
V
U1b U1 F1c
V
U1c I F2a
U2a I F2 F2b
V
U2b U2 F2c
V
U2c B90 BUS DIFFERENTIAL I F3a
U3a F3 F3b
U3b
I
U3 RELAY V
F3c
V
U3c I F4a
U4a I IED 4 (LOGIC) F4
V
F4b
U4b U4 F4c
V
U4c I F5a
U5a I F5
V
F5b
U5b U5 F5c
6H
6A
I
N1b N1 L1 L1b
V V
N1c L1c
N2a I I L2a
N2b N2 L2 L2b
V V
N2c L2c
N3a I L3a
N3b N3 L3 L3b
V
N3c L3c
N4a I L4a
Dry N4b N4 L4 L4b
V
contact N4c L4c
N5a CONTACT INPUT N5a I L5a
N5c CONTACT INPUT N5c L5
V
L5b
CONTACT INPUTS AND OUTPUTS
Rx1 I S1a
6H
Co-axial BNC V
S4c
I S5a
S5
V
S5b
Co-axial * - For IRIG-B input S5c
CONTACT INPUTS AND OUTPUTS
I S6a
as input B1a FAILURE
B2b S6
V
S6b
B3a 48 V DC
S6c
B3b OUTPUT CONTACT INPUT S7a S7a
DC CONTACT INPUT S7c S7c
POWER SUPPLY
B5b HIGH
CONTROL CONTACT INPUT S8a S8a
B6b LOW
AC or DC POWER CONTACT INPUT S8c S8c
B6a
COMMON S7b S7b
B8a SURGE
B8b FILTER SURGE S8b
#10AWG
minimum 836788A1.CDR
GROUND BUS
MODULE ARRANGEMENT
X W V U T S R P N M L K J H G F D B
MODULES MUST 7 6 8 6 8 6 8 9 1
BE GROUNDED
IF TERMINAL COM Inputs/ CT Inputs/ CT Power
IS PROVIDED
Inputs/ CT CPU
outputs outputs outputs supply
3 3
4
Reserved
Digital contact inputs/
N/A
All
N/A
Chassis
N/A
2000 V AC for 1 minute
outputs
5 Analog inputs/outputs All except 8b Chassis < 50 V DC
6 Digital contact inputs/ All Chassis 2000 V AC for 1 minute
outputs
7 G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute
Filter networks and transient protection clamps are used in the hardware to prevent damage caused
by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90
specified test voltage for longer than the specified minute.
Power supplied to the relay must be connected to the matching power supply range of the relay. If
incorrect voltage is applied or voltage is applied to the wrong terminals, damage can occur.
The B90, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well-
known to deteriorate over time if voltage is not applied periodically. Deterioration can be avoided by
powering up the relay at least once a year.
The power supply module is ordered with one of two possible voltage ranges, and the B90 can be ordered with or without
a redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges
are as follows (see the Specifications section of chapter 2 for details):
• Low (LO) range — 24 to 48 V (DC only) nominal
• High (HI) range — 125 to 250 V nominal
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical Wiring Diagram earlier). The critical failure relay is a form-C device that is energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If ongoing self-test diagnostic checks detect a
critical failure (see the Self-Test Errors section in chapter 7) or control power is lost, the relay de-energizes.
Connect all wires at be back of a UR before connecting to power, else death or serious injury can
result from electrical shock.
NOTE:
AC or DC 14 gauge stranded
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
827247A1.CDR
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary
rating of the connected CTs. Unmatched CTs may result in equipment damage or inadequate
protection.
Each AC current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the
module is withdrawn from the chassis. There are no internal ground connections on the current inputs. Current
transformers with 1 to 50000 A primaries and 1 A or 5 A secondaries may be used.
Each B90 voltage input is intended for monitoring a single-phase voltage. The may include phase voltages or neutral
voltage from the open-delta VT.
All CT and VT modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
Substitute the tilde “~” symbol with the slot position of the module in the following figure.
3
~1a
~2a
~3a
~4a
~5a
~6a
~7a
~8a
~1b
~2b
~3b
~4b
~1c
~2c
~3c
~4c
~5c
~6c
~7c
~8c
VC
VB
VX
VA
IG
IG1
IC
IA
IB
VC
IC1
IA1
IB1
VB
IG5
VX
VA
IC5
IA5
IB5
~2a
~3a
~4a
~5a
~6a
~7a
~8a
~1b
~2b
~3b
~4b
~5b
~6b
~7b
~8b
~1c
~2c
~3c
~4c
~5c
~6c
~7c
~8c
IG
IG
IG1
IG1
IC
IC
IA
IB
IA
IB
IC1
IC1
IA1
IB1
IA1
IB1
IG5
IG5
IC5
IC5
IA5
IB5
IA5
IB5
Current inputs
8H, 8J, 8N, and 8R modules (8 CTs)
~1a
~2a
~3a
~4a
~5a
~6a
~7a
~8a
~1b
~2b
~3b
~4b
~5b
~6b
~7b
~1c
~2c
~3c
~4c
~5c
~6c
~7c
~8c
IG
IG1
IC
IA
IC
IB
IA
IB
IC1
IA1
IC1
IB1
IA1
IB1
IG5
IC5
IA5
IC5
IB5
IA5
IB5
V
V
The contact inputs are grouped with a common return. The input/output modules have three versions of grouping: four
inputs per common return, five inputs per common return on a high-density module, and two inputs per common return.
When a contact input/output module is ordered, four inputs per common is used. If the inputs must be isolated per row,
then two inputs per common return are selected (4D module). If the space limitation in the relay requires use of a high-
density input module (6W), five inputs share one common return and the module has six banks of inputs.
The tables and diagrams that follow illustrate the module types (6A and so on) and contact arrangements that can be
ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is
open, and the DC current through the output contact when it is closed. Each of the monitors contains a level detector
whose output is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is
set to “On = 1” when there is a voltage across open contact (the detector allows a current of about 1 to 2.5 mA), and the
current monitor is set to “On = 1” when the current flowing through the closed contact exceeds about 80 to 100 mA. The
voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be used to seal-in
3
the output contact until an external contact has interrupted current flow. If enabled, the current monitoring can be used as
a seal-in signal to ensure that the form-A contact does not attempt to break the energized inductive coil circuit and weld
the output contacts.
Block diagrams are shown as follows for form-A and solid-state relay outputs with optional voltage monitor, optional
current monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact
outputs. Form-A contact output with or without a current or voltage monitoring option is not polarity sensitive. The polarity
shown in the figure is required for solid-state contact output connection.
Figure 3-17: Form-A and solid-state contact outputs with voltage and current monitoring
~#a ~#a
I I
~#b ~#b Load
V Load V
~#c + ~#c +
a) Voltage with optional
Voltage monitoring only Both voltage and current monitoring
current monitoring
~#a ~#a
V V
~#a
~#b
Load
~#c +
c) No monitoring
827862A5.CDR
The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON, CONT
OP # VOFF, and CONT OP # ION) that can be used in protection, control, and alarm logic. The typical application of the voltage
monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the control
command.
See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied
for breaker trip circuit integrity monitoring.
Consider relay contacts unsafe to touch when the unit is energized. Death or serious injury can
result from touching live relay contacts.
Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears,
substitute the contact number.
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
For high-density input/output modules 6W and 6X, use the following guidelines to connect. The new I/O modules use pin
type terminal blocks instead of the current ring type. The new terminals are required to achieve higher I/O count per
module.
• 12 to 24 AWG (3.3 mm2 to 0.2 mm2), single wire termination
• 16 to 24 AWG (1.31 mm2 to 0.2 mm2), multiple wire termination with matching wire sizes and stranding. Two wires
maximum per circuit.
• Suggested wiring screw tightening torque is a minimum 4.43 in-lb (0.5 Nm) and maximum 5.31 in-lb (0.6 Nm)
• Minimum suggested temperature rating for the conductors is 75°C
• Wire type: copper
Table 3-3: Contact input and output module assignments
~6A module ~6B module ~6C module ~6D module
Terminal Output or Terminal Output or Terminal Output Terminal Output
assignment input assignment input assignment assignment
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4 Form-C ~4 Form-C ~4 Form-C ~4a, ~4c 2 Inputs
~5a, ~5c 2 Inputs ~5 Form-C ~5 Form-C ~5a, ~5c 2 Inputs
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
842762A4.CDR
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
3
~ 8c
842763A2.CDR
For proper functionality, observe the polarity shown in the figures for all contact input and output 3
connections.
B1b
B1a Critical failure
B2b
Power supply module
B3a
48 V DC output
B3b
B5b HI+
B6b LO+ Control power
B6a
B8a Surge
B8b Filter
827741A5.CDR
Where a tilde “~” symbol appears, substitute the slot position of the module.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend
using an external DC supply.
Contact Input
859755A1.cdr
The presence of the impedance path (R1) across the contact output allows the stray (distributed) capacitance C1 to charge
as shown, thus developing a voltage across the contact input enough to momentarily operate the input while the
capacitance discharges in the presence of DC ground on the positive terminal of the battery.
The duration of the discharge depends on the value of the distributed capacitance, the initial voltage of the distributed
capacitance, and the input impedance of the contact input. If the duration is greater than the debounce time setting, then
the contact input operates.
The application example that follows describes how to mitigate this issue by connecting a resistor across the contact
input, as shown in the next figure, or by adjusting the debounce time setting to a value greater than the discharge time to
prevent spurious operation of the contact input only if the voltage (with output open) across the contact input due to trickle
current is less than the threshold voltage. This operation of contact inputs also can be prevented by using the Auto-Burnish
contact inputs or contact inputs with active impedance.
Figure 3-23: Contact input connected to a contact output with resistor (R2) across the input
Contact Input
3
859756A1.cdr
Application example
This example is for illustrative purposes only and the calculations present the worst-case scenario. In practice, the value of
debounce time can be lower.
Contact input ON state impedance used in the calculation of the discharge period is based on the following table.
Table 3-4: Discharge period
Battery voltage (V) Input impedance (kΩ)
130 50
250 97
50 to 70 mA
3 mA
Time
25 to 50 ms
842749A1.CDR
Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with
auto-burnishing allow currents up to 50 to 70 mA at the first instance when the change of state is sensed. Then, within 25
to 50 ms, this current is slowly reduced to 3 mA as indicated. The 50 to 70 mA peak current burns any film on the contacts,
allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts when
external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two
contact inputs have common ground, as opposed to four contact inputs sharing one common ground (see the Contact
Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources.
Consequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.
Figure 3-25: Auto-burnish DIP switches
842751A1.CDR
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-burnish
functionality using an oscilloscope.
30
84 V threshold
166 V threshold
17 V threshold
33 V threshold
e
at
st
e
25
nc
da
pe
im
w
Lo
20
3
Current (millamperes)
15
s
m
oh
K
10
10
166 V threshold
84 V threshold
33 V threshold
5
17 V threshold
dance state
100 K ohms HIgh impe
0
0 50 100 150 200 250 300
Voltage (Volts) 859757A2.vsd
1: N/A
2: (TXD)
3: (RXD)
RELAY
PERSONAL 4: N/A
COMPUTER 5: (SGND) Signal Ground
FRONT PANEL
6: N/A
PROGRAM PORT 7: N/A
8: N/A
9: N/A
9 PIN
RS232 RS232
3
D CONNECTOR D CONNECTOR
9 PIN 25 PIN
CONNECTOR CONNECTOR
3.3.7.1 Overview
There is a rear RS485 communication port on the CPU module. The CPU module does not require a surge ground
connection.
T
optic cable Tx1 Rx1 100Base-FX
Tx2 Rx2 100Base-FX Port 2
Shielded
twisted-pairs
Tx3 Rx3 100Base-FX Port 3
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
U
100Base-TX Port 1
MM fiber-
optic cable Tx1 Rx1 100Base-FX Port 2
Shielded Tx2 Rx2 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
Port 1
V
100Base-TX
100Base-TX Port 2
Shielded 100Base-TX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
W
10/100Base-TX Port 1
MM fiber-
optic cable
Tx1 Rx1 100Base-FX Port 2
Shielded Tx2 Rx2 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
859774A1.CDR
or common voltage. This common voltage is implied to be a power supply common. Some systems allow the shield (drain
wire) to be used as common wire and to connect directly to the B90 COM terminal (#3); others function correctly only if the
common wire is connected to the B90 COM terminal, but insulated from the shield.
To avoid loop currents, ground the shield at only one point. If other system considerations require the shield to be
grounded at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding
point. Each relay needs to be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this
manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also
possible to use commercially available repeaters to have more than 32 relays on a single channel. Avoid star or stub
connections entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are provided internally at both communication ports. An
isolated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum
reliability, ensure that all equipment has similar transient protection devices installed.
Terminate both ends of the RS485 circuit with an impedance as shown in the figure. 3
Figure 3-29: RS485 serial connection
COM
COMP 485COM
COMP 485COM
Up to 32 devices,
maximum 4000 feet
(1200 m)
Relay
ZT (*)
RS485 +
RS485 –
3.3.8 IRIG-B
There is a round IRIG-B connector at the back of the CPU module, marked "IN". Use is optional.
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The
IRIG-B code allows time accuracies of up to 100 ns. The GE MultiSync 100 1588 GPS Clock as well as third-party equipment
are available for generating the IRIG-B signal. This equipment can use a global positioning system (GPS) satellite system to
obtain the time reference so that devices at different geographic locations can be synchronized. The IRIG time code
formats are serial, pulse width-modulated codes that can be either DC level shifted or amplitude modulated (AM). Using
IRIG-B input, the B90 operates an internal oscillator with 1 µs resolution and accuracy.
Figure 3-30: Options for IRIG-B connection
UR-series device
3 IRIG-B
4B IRIG-B (+)
4A IRIG-B (–)
time code generator
RG58/59 coaxial cable Receiver
(DC-shift or + BNC (in)
amplitude modulated
signal can be used)
IRIG-B
time code generator
UR-series device
Twisted-pair cable
(DC-shift or +
4B IRIG-B (+)
amplitude modulated
4A IRIG-B (–)
signal can be used)
Receiver
BNC (in)
827756A8.CDR
The communications channels are normally connected in a ring configuration, as shown in the following figure. The
transmitter of one module is connected to the receiver of the next module. The transmitter of this second module is then
connected to the receiver of the next module in the ring. This is continued to form a communications ring. The figure
illustrates a ring of four UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to
UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of 16 URs can be connected in a single ring.
Figure 3-31: Direct input and output single-channel connection
Tx
UR 1
Rx
Tx
UR 2
Rx
UR 3
Tx 3
Rx
Tx
UR 4
Rx
842006A2.CDR
Inter-relay communication (IRC) modules with protocol C37.94 and G.703 are designed for back-to-back communication
connections, so the ring configuration shown in the previous figure does not apply. To establish inter-relay communication
in more than two URs, you need to have a two-channel IRC module and enable the DIRECT I/O CHANNEL CROSSOVER setting
in all relays, as shown in the next figure. This configuration can be expanded to 16 URs, and this configuration does not
provide a redundancy ring since both channels are made into a single ring by the channel crossover function. As per the
figure entitled Typical Pin Interconnection between Two G.703 Interfaces later in this chapter, the clock is supplied typically
by multiplexer (MUX) and all URs are in Loop Timing Mode. If there is no MUX, then UR1 and UR3 can be in Internal Timing
Mode and UR2 and UR4 can be in Loop Timing Mode. That is, connected channels must have opposite timing modes.
Figure 3-32: Ring configuration for C37.94 module (concept also applies to G.703)
842236A1.CDR
The interconnection for dual-channel type 7 communications modules is shown as follows. Two-channel modules allow for
a redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The
required connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the
first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring.
Tx1
Rx1
UR 1
Tx2
Rx2
Tx1
Rx1
UR 2
Tx2
Rx2
3 Tx1
Rx1
UR 3
Tx2
Rx2
Tx1
Rx1
UR 4
Tx2
Rx2
842007A3.CDR
The following figure shows the connection for three UR-series relays using two independent communication channels. UR1
and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication channels
can be of different types, depending on the type 7 modules used. To allow the direct input and output data to cross-over
from channel 1 to channel 2 on UR2, set the DIRECT I/O CHANNEL CROSSOVER setting to “Enabled” on UR2. This forces UR2 to
forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.
Figure 3-34: Direct input and output single/dual channel combination connection
Tx
UR 1
Rx
Channel 1
Tx1
Rx1
UR 2
Tx2
Rx2
Channel 2
Tx
UR 3
Rx
842013A2.CDR
The inter-relay communications modules are available with several interfaces and some are outlined here in more detail.
Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the
Order Code tables in Chapter 2. All of the fiber modules use ST type connectors.
Rx1 Rx1
Tx1 Tx1
3
Rx2
Tx2
1 channel 2 channels
831719A3.CDR
Tx1 Tx1
Rx1 Rx1
Tx2
Rx2
1 channel 2 channels
831720A5.CDR
The following figure shows configuration for the 2I and 2J fiber-laser modules.
Rx1
Tx1
Rx2
3 Tx2
2 channels
831827A1.CDR
When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
3.4.4.1 Description
G.703 is an International Telecommunications Union (ITU) standard for the transmission of data and voice signals. Modules
7R (one channel) and 7S (two channels) apply.
The following figure shows the 64K ITU G.703 co-directional interface configuration. This is module 7S.
The G.703 module is fixed at 64 kbps. The SETTINGS PRODUCT SETUP DIRECT I/O DIRECT I/O DATA RATE setting is not
applicable to this module.
AWG 24 twisted shielded pair wiring is recommended for external connections, with the shield grounded only at one end.
Connecting the shield to pin X1a or X6a grounds the shield since these pins are connected internally to ground. Thus, if
pin X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is
protected by surge suppression devices.
Figure 3-38: G.703 interface configuration
Shield ~1a
7S
Tx – ~1b
G.703 Rx – ~2a
channel 1
Tx + ~2b
Rx + ~3a
G.703 communications
Surge ~3b
Shield ~6a
Tx – ~6b
G.703 Rx – ~7a
channel 2
Tx + ~7b
Rx + ~8a
Surge ~8b
842773A3.CDR
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical
arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3-39: Typical pin interconnection between two G.703 interfaces
7S
7S
Tx – X1b X1b Tx –
G.703 Rx – X2a X2a Rx – G.703
channel 1 channel 1
Tx + X2b X2b Tx +
Rx + X3a X3a Rx +
G.703 communications
G.703 communications
Surge X3b X3b Surge
Shield X6a X6a Shield
Tx – X6b X6b Tx –
G.703 Rx – X7a X7a Rx – G.703
channel 2 channel 2
3
Tx + X7b X7b Tx +
Rx + X8a X8a Rx +
Surge X8b X8b Surge
831727A5.CDR
Pin nomenclature differs from one manufacturer to another. It is not uncommon to see pinouts numbered TxA, TxB,
RxA, and RxB. In such cases, assume that “A” is equivalent to “+” and “B” is equivalent to “–.”
Ejector/inserter clip
FRONT
Channel 1
Timing selection
switches
Top cover
3
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
842752A2.CDR
DMX G7R
842774A1.CDR
In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing.
One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the
interface.
Figure 3-43: G.703 dual loopback mode
DMX G7R
842775A1.CDR
3.4.5.1 Description
There are two RS422 inter-relay communications modules available: single-channel (module 7T) and dual-channel (module
7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 20 to 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are connected internally to the ground pin (8a). Proper shield termination is as follows:
• Site 1 — Terminate shield to pins 6a or 7b or both
• Site 2 — Terminate shield to COM pin 2b
Match the clock terminating impedance with the impedance of the line.
Figure 3-44: RS422 interface connections
3 Single-channel RS422 module Dual-channel RS422 module
7W
Tx – ~3b Tx – ~3b
7T
Rx – ~3a Rx – ~3a
RS422 communications
The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
Figure 3-45: Typical pin interconnect between two RS422 interfaces
Tx – W3b W3b Tx –
7T
7T
Rx – W3a W3a Rx –
RS422 communications
RS422 communications
outputs from the multiplexer (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In
addition, the send timing outputs of data module 1 are also paralleled to the terminal timing inputs of data module 2. By
using this configuration, the timing for both data modules and both UR RS422 channels is derived from a single clock
source. As a result, data sampling for both of the UR RS422 channels is synchronized via the send timing leads on data
module 1, shown as follows. If the terminal timing feature is not available or this type of connection is not wanted, the
G.703 interface is a viable option that does not impose timing restrictions.
Figure 3-46: Timing configuration for RS422 two-channel, three-terminal application
Data module 1
Signal name
Tx1(+) W2a SD(A) - Send data
7W
Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
Data module 1 provides timing to the B90 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure because they vary by manufacturer.
Tx Clock
Tx Data
831733A1.CDR
When using a laser interface, attenuators can be necessary to ensure that you do not exceed
maximum optical input power to the receiver.
Figure 3-48: RS422 and fiber interface connection
+ ~1a
7L, 7M, 7N,
7P, and 74
Clock
channel 1 – ~1b
Common COM ~2b
Tx – ~3b
Rx – ~3a
RS422 Tx + ~2a
channel 1
communications
Rx + ~4b
Shield ~6a
Fiber Tx2 Rx2
RS422
channel 2
Surge ~8a
842777A3.CDR
The connections shown in the figure are for multiplexers configured as data communications equipment (DCE) units.
When using a laser interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
Figure 3-49: G.703 and fiber interface connection
Shield ~1a
communications
Rx + ~3a
Surge ~3b
Fiber Tx2
G.703
channel 2 Rx2
842778A2.CDR
Digital
UR-series multiplexer,
device IEEE C37.94
compliant
up to 2 km
842755A2.CDR
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a non-
compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard. The
following figure shows the concept.
842756A2.CDR
In 2008, GE Grid Solutions released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of B90 communication for
two and three terminal applications. Failure to use it at all ends results in intermittent communication alarms. For
customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94 communication module has six switches to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-52: Switches
Loop timing mode
Internal timing mode (factory default)
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. With power to the relay off, remove the IEEE C37.94 module (type 2G, 2H, 2I, 2J, 76, or 77 module) as follows. Record
the original location of the module to help ensure that the same or replacement module is inserted into the correct
slot.
2. Simultaneously pull the ejector/inserter clips located at the top and bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
6. Replace the top cover and the cover screw.
7. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Figure 3-53: IEEE C37.94 timing selection switch setting
Bottom cover
Ejector/inserter clip
FRONT 3
Channel 1
Timing selection
switches
Top cover
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
3
Tel: (905)294-6222
Fax: (905)201-2098
Rx2
(NORTH AMERICA)
1 800 547-8629
GE Multilin
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that
supports C37.94SM, as shown.
C37.94SM
fiber interface
Digital
UR-series
multiplexer
device
C97.94SM
up to 10 km
842757A2.CDR
It also can be connected directly to any other UR-series relay with a C37.94SM module, as shown.
C37.94SM
fiber interface 3
UR-series UR-series
device with device with
C37.94SM C37.94SM
module module
up to 10 km
842758A2.CDR
In 2008, GE Grid Solutions released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of B90 communication for
two and three terminal applications. Failure to use it at all ends results in intermittent communication alarms. For
customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94SM module has six switches that are used to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-55: Switches
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher-order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. With power to the relay off, remove the C37.94SM module (module 2A or 2B) as follows. Record the original location of
the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release
the module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
Ejector/inserter clip
FRONT
3 Channel 1
Timing selection
switches
Top cover
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
Tel: (905)294-6222
Fax: (905)201-2098
(NORTH AMERICA)
1 800 547-8629
Rx2
3
GE Multilin
RELAY SETTINGS: When the relay is powered up, the "Trouble LED" is on, the "In Service" LED is off, and this message
Not Programmed displays, indicating that the relay is in the "Not Programmed" state and is safeguarding (output
relays blocked) against the installation of a relay whose settings have not been entered. This
message remains until the relay is explicitly put into "Programmed" state.
The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message displays.
2. Press the MESSAGE right arrow until the SECURITY message displays.
3. Press the MESSAGE down arrow until the INSTALLATION message displays.
4. Press the MESSAGE right arrow until the RELAY SETTINGS: Not Programmed message displays.
SETTINGS
SETTINGS SECURITY
PRODUCT SETUP
DISPLAY
PROPERTIES
INSTALLATION RELAY SETTINGS:
Not Programmed
3 5. After the RELAY SETTINGS: Not Programmed message displays, press a VALUE key to change the selection to
"Programmed."
6. Press the ENTER key to save the change.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
To activate the relay using EnerVista software:
1. Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2. Save the change.
Regional
control
center
Ethernet Remote
10/100 Mbps communications link
Local
control
UR-series IED
EnerVista Engineer
GE Multilin F485
communications converter
Modem
3
RS485 115 kbps
RS232
EnerVista
Reports
EnerVista
Troubleshooting
Commissioning
Setting changes
842759A2.CDR
To communicate through the B90 rear RS485 port from a computer RS232 port, the GE Grid Solutions RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair wire (20, 22, or 24 AWG) connects the F485 converter to the B90 rear communications port.
The converter terminals (+, –, GND) are connected to the B90 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as
described in this chapter.
The front panel can be switched in the EnerVista software between enhanced and basic panels under
Maintenance > Change Front Panel.
3 To install the software from the DVD and using EnerVista Launchpad:
1. Insert the DVD into the DVD drive of your computer.
2. Click the Install Now button and follow the instructions.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
Figure 3-59: Adding a UR device in Launchpad window
5. In the EnerVista Launch Pad window, click the Add Product button and select the appropriate product as follows.
Select the Web option to ensure the most recent software release, or select CD if you do not have an Internet
connection, then click the Add Now button to list software items for the product. EnerVista Launchpad obtains the
software from the Internet or DVD and automatically starts the installation program after prompting about updates.
From the web, the software is downloaded. A wizard opens.
6. In the wizard, click the Next button and complete the process. The files are installed in the directory indicated, and the
installation program automatically creates icons and adds an entry to the Windows start menu.
The UR device is added to the EnerVista Launchpad window, as shown.
Figure 3-61: UR device added to Launchpad window
7. For other than English, configure the language for the front panel in the EnerVista software under Settings > Product
Setup > Display Properties. User-entered strings are not translated, for example relay names, so setting the language
now ensures that the names are entered/displayed in the required language. For the EnerVista software language,
access the View > Language menu item.
• Connect locally with a computer through either the front RS232 or USB port or rear Ethernet port; see the Connect to
the B90 section
• Discover automatically UR devices within a network; see the Automatic Discovery of UR Devices section
Devices in the Device Setup window are listed in the order entered.
Devices in the main software window are listed alphabetically. Use the Device Name to order them as required, for
example B30 Odessa, B30 Truro, B90, T35.
You cannot import a file to add a device to the software. You can import settings as outlined at the end of the chapter.
The Quick Connect button also can be used to add devices. The device is added to a Quick Connect menu item in the
Online Window area, cannot be moved from it to another grouping, and needs to be renamed in the Device Setup window.
GE instead recommends using the Device Setup window to add devices, as outlined here.
Both network and subnet addresses are contained within a range. The number of hosts determines the class and
addresses as follows:
• Class A 255.0.0.0 — The first octet (255) specifies the network, the second to fourth octets (0) specify the subnet and
host. Use this class when you have more than 65,535 hosts (UR devices).
• Class B 255.255.0.0 — The first two octets (255) specify the network, the third octet (0) specifies the subnet, and the
fourth octet (0) specifies the host. Use this class when you have 255 to 65,534 hosts (UR devices).
• Class C 255.255.255.0 — The first three octets (255) specify the network and the last octet (0) specifies the subnet and
host. Use this class when you have up to 254 hosts (UR devices).
An example of implementation is one computer and one UR device. Because there is one UR device, class C addressing is
required. So we use UR 192.167.2.x with subnet mask 255.255.255.0 and computer 192.167.3.x with subnet mask
255.255.255.0.
For older, non-CIDR routing protocols, such as RIP version 1, follow these restrictions:
• Identical subnet masks — Use a single mask for all subnets within a network
• Contiguous subnets — The subnets must be contiguous and not split among networks. The subnets cannot pass
traffic through other networks.
The IP and subnet addresses need to be added to the UR for Ethernet communication.
For serial communication, for example using any front RS232 port and the Quick Connect feature, the addresses are not
required, but typically they are entered to add/configure devices for regular use.
To add the IP addresses:
1. On the front of the UR, press the MENU key until the SETTINGS menu displays.
2. Navigate to SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK PRT IP ADDRESS SETTING.
3. Enter an IP address, for example 10.11.33.1, and press the ENTER key to save the value. For example, press the period
key to clear any existing address, then press the number keys to add anew address.
4. In the same menu, select the PRT SUBNET IP MASK setting. Enter a subnet IP address, for example 255.0.0.0.
5. Press the ENTER key to save the value.
The gateway address also needs to be configured when connecting through an Ethernet network. Access SETTINGS
PRODUCT SETUP COMMUNICATIONS IPv4 ROUTE TABLE DEFAULT IPv4 ROUTE GATEWAY ADDRESS.
If using a blue or grey Ethernet cable, skip the rest of the this section. If using an orange cross-over Ethernet cable, the
computer needs to be set up as follows.
1. Use an orange Ethernet cross-over cable to connect the computer to the rear Ethernet port. In case you need it, the
following figure shows the pinout for an Ethernet cross-over cable.
Figure 3-62: Ethernet cross-over cable PIN layout
3 4 5 6
END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8
3
1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR
Next, assign the computer an IP address compatible with the relay’s IP address.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel.
3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
Before using the Quick Connect feature through the Ethernet port, disable any configured proxy settings in Internet
Explorer.
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the B90 relay.
1. Start the Internet Explorer software.
2. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.
4. Select the Ethernet interface and enter the IP address assigned to the B90, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them on the left side of the screen.
5. Expand the sections to view data directly from the B90 device.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the B90. This ensures that configuration of the EnerVista UR Setup software matches the B90 model
number.
When direct communications with the B90 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown.
If the computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the B90 relay.
3 3.
4.
Click the Device Setup button. The window opens.
Click the Add Site button. A new category is added. Enter a site name in the Site Name field. Optionally add a short
Description of the site. This example uses “Location 1” as the site name.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 15 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Serial” from the Interface drop-down list. Interface parameters display that must be entered for serial
communications. Try to load automatically the fields by clicking the Read Order Code button.
Figure 3-63: Configuring serial communication
8. Enter the COM port used by the computer, the baud rate, and parity settings from the front panel SETTINGS PRODUCT
SETUP COMMUNICATIONS SERIAL PORTS menu, and the relay slave address setting from the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL MODBUS SLAVE ADDRESS menu in their respective
fields.
Baud Rate — Typically 19200 bits per second (bps) for RS232, and higher for RS485. Both modems need to use the
same rate, meaning at the computer and the B90 ends.
Parity — Set to None if unsure
Bits — Set to 8 if unsure
Stop Bits — Set to 1 if unsure
Post Terminal Window — Enable this option if you have a Schweitzer Engineering (SEL) SEL-203x Communications
Processor, such as an SEL-2030 or SEL-2032. This option enables display of a terminal window to allow interaction
with the other device.
9. Click the Read Order Code button to connect to the B90 and upload the order code to the EnerVista software. If a
communications error occurs, ensure that the EnerVista software serial communications values entered in the
previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to
multiple B90 ports.
10. Click the OK button when the relay order code has been received. The new site and device are added to the Online
3
Window.
The device has been configured for serial communications. Proceed to the Connect to the B90 section to begin
communication.
8. Enter the relay IP Address, which can be viewed on the device front panel under SETTINGS PRODUCT SETUP
COMMUNICATIONS NETWORK IP ADDRESS. Once the IP address is entered, try to load automatically the fields by
clicking the Read Order Code button.
9. Enter the relay Slave address and Modbus Port address values from the settings in the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.
10. If using a gateway to connect to the device, select Yes from the drop-down list.
11. Click the Read Order Code button to connect to the B90 device and upload the order code. If the device was entered
already, a message displays "Device ’x’ is also using IP address...." If a communications error occurs, ensure that the
values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address
is not assigned to multiple B90 ports.
12. Click the OK button when the relay order code has been received. The new site and device are added to the Online
Window.
The device has been configured for Ethernet communications. Proceed to the Connect to the B90 section to begin
communications.
2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Device Setup button. The window opens.
4. Click the Add Site button. A new category is added. Enter a site name in the Site Name field, such as London East.
Optionally add a short Description of the site, such as the address or intersection.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 15 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Modem” from the Interface drop-down list. This displays a number of interface parameters that must be
entered.
8. Select "Generic Modem" from the Modem Name drop-down list, then enter the Phone Number to dial to establish
communication with the remote modem.
Post Terminal Window — Enable this option if you have a SEL-203x Communications Processor, such as an SEL-2030
or SEL-2032. It enables display of a terminal window to allow interaction with the other device. 3
9. Once the phone number is entered, try to load automatically the device information by clicking the Read Order Code
button.
10. Click the OK button when the relay order code has been received. The new device is added to the Online window.
The UR device has been added to the software.
When multiple computers are connected to a B90 device, EnerVista settings windows are not updated
automatically. They are refreshed when re-opened. If a user changes a setting on one computer, the other users
need to refresh the display by closing and opening the settings window to see the change. To ensure that current
settings are always viewed, close settings windows when not in use so that they are up-to-date when next
accessed.
3
Expand the site list by double-clicking
or selecting the +/– box.
842743A3.CDR
2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly set up for communication.
3. If a relay icon appears in place of the status indicator, then a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be viewed, edited, or printed.
3 4. Select the serial Interface and the communications port (COM Port) from the drop-down lists, then click Connect. The
COM Port is that of the computer.
5. The EnerVista software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them in the Online Window. Expand the sections to view data directly from the UR device. Use
the Device Setup button to change the site name.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the B90. This ensures that configuration of the EnerVista UR Setup software matches the B90 model
number.
2. Select the Ethernet interface and enter the IP address assigned to the B90, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3. Expand the sections to view data directly from the B90 device. Use the Device Setup button to change the site name.
Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to
the B90. This ensures that configuration of the EnerVista UR Setup software matches the B90 model number.
3
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under Settings > Product Setup > Security > Supervisory. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista. If using EnerVista, navigate to
Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended
that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is
optional.
When EIC 61850 and version is 7.30 or later, the file is added and time stamp is unchanged. When clicking in the
software on the tree element, a device folder is created, the original file moves into it, SCL files are generated there,
and the "Last modified" time stamp on the URS file changes.
Chapter 4: Interfaces
Interfaces
This chapter explains the EnerVista software interface, the front panel interface, logic diagrams, and Engineer interface for
logic design and monitoring.
• Remote resources
• Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the B90 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address (see end of previous chapter for information)
IP Subnet Mask
IP Routing
When a settings file is loaded to a B90 that is in-service, the following sequence occurs:
4 1. The B90 takes itself out of service.
2. The B90 issues a UNIT NOT PROGRAMMED major self-test error.
3. The B90 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.
2 1 6 7
10
4
4 5
9 8 842786A2.CDR
When templates are created for online settings, the password is added during the initial template creation step. It
does not need to be added after the template is created.
4
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR
Viewing the settings in template mode also modifies the settings menu, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings menu is shown as follows.
Figure 4-7: Applying templates using the View in Template Mode settings command
Use the following procedure to display settings available for editing and settings locked by the template.
1. Right-click the device in the Online or Offline Window area and apply the template by selecting the Template Mode >
View All Settings option.
2. Enter the template password then click OK to apply the template.
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown as follows.
Figure 4-8: Applying templates using the View All Settings command
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
4
842859A1.CDR
4 5. Click the Save button to save and apply changes to the settings template.
6. Select the Template Mode > View In Template Mode option to view the template.
7. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode >
Password Protect Template option.
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries is shown here.
Figure 4-10: Locking FlexLogic entries through settings templates
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
The FlexLogic entries are also shown as locked in the graphical view and on the front panel display.
2. Enter the serial number of the B90 device to lock to the settings file in the Serial # Lock field.
3. Click the OK button to apply the change. The serial number is not validated.
The settings file and corresponding secure FlexLogic equations are now locked to the B90 device specified by the serial
number.
The serial number of the UR-series device and the file transfer
date are added to the setting file when setting files
are transferred to the device.
842863A1.CDR
This information is also available in printed settings file reports as shown in the example. A report is generated by right-
clicking and selecting the Print Settings option.
Traceability data
in settings report
4
842862A1.CDR
This information is also available from the front panel display through the following actual values:
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION SERIAL NUMBER
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE
Display
4
Keypad
Control
pushbuttons (3)
Front panel
RS232 port
Display
Front panel
RS232 port
Small user-programmable
User-programmable Keypad
(control) pushbuttons 1 to 7
pushbuttons 1 to 12
827801A9.CDR
1 5
IN SERVICE
TROUBLE
TEST MODE
TRIP
ALARM 2 6
PICKUP
VOLTAGE
CURRENT 3 7
USB port FREQUENCY
OTHER
PHASE A 4 8
PHASE B
Not used
PHASE C
NEUTRAL / GND
RESET ESC
ENTER
4
The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the
front panel or the LEDs.
To view the front panel in EnerVista software:
1. Click Actual Values > Front Panel, then any option.
Figure 4-21: Front panel use in the software (C60 shown)
Header content varies by page. The home page displays any active icons, such as security status, active setting group, and
active target messages. It shows the date and time of the relay. If the relay synchronizes to an external time source via PTP,
IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow. On pages other than the home page, the
header displays the name of the page.
The footer dynamically labels the Tab, or control, pushbuttons immediately below.
Page content displays between the header and footer.
Figure 4-22: Home page example with default content (product information)
Setting Group
Alarm Target Relay Date and Time
859850A1.cdr
There are multiple ways to navigate pages, by using the pushbuttons and the menu hierarchy. The menu hierarchy is
similar to the other front panels whereby you select a submenu using Up and Down arrow pushbuttons, and press the
ENTER or Right pushbutton. On setting pages, opening a setting for editing is done by highlighting the setting using Up and
Down pushbuttons, and pressing the ENTER or Right pushbutton.
Home page
Press the Home pushbutton to display the root page no matter the state. Any edit, control, or password entry sessions are
cancelled. The header shows several relay/system status icons. The default content of the home page is the product
information page and can be user-configured to show the content of any single-line diagram page, annunciator page,
metering page, or event records page for example. The Tab pushbuttons on the bottom row each navigate to their page.
The home page displays for a user-configured time period, then scrolls through user-configured pages, a feature referred
to as rolling.
Holding the Home pushbutton for one second displays the product information page. The Home page also can display
when settings are saved.
Security indicator, showing how many people are logged in, including local and remote users. The lock is red when
one or more users are logged in and other otherwise green.
When no users are logged in because login is not required, an icon does not display.
Identifies the active setting group number (not shown)
Displays when an abnormal annunciator alarm is present. Navigate to the Annunciator for details. When there
are no such alarms, the icon does not display.
Even when you acknowledge/reset an alarm, the icon displays as long as the condition remains. For example, a
breaker trouble alarm displays, you acknowledge it, but the icon remains because the breaker trouble remains.
Active targets symbol, where targets are error messages.
View error messages by pressing the Menu Tab pushbutton, then accessing the TARGETS menu. Pressing the
RESET button clears those messages that can be.
Configure the home page in the software under Settings > Product Setup > Graphical Panel > Home Page. The menu
does not display when there is no graphical front panel.
Rolling mode
After a user-defined period of inactivity, the graphical front display rolls among up to 10 user-selected pages. The roll-to-
pages are selected in the EnerVista software, with the defaults being the product information page. Each page displays for
less than five seconds. Also, the display backlight intensity is lowered after a configurable period to a user-defined level (0,
10, 20, or 30%); lower intensity extends the life of the display.
Configure rolling mode in the software under Settings > Product Setup > Graphical Panel > Rolling Mode.
Operation works as follows:
• Press the Home pushbutton or ESCAPE pushbutton twice to cancel rolling, restore full backlight intensity, and return
to the Home page 4
• Press the ENTER, ESCAPE, or a pushbutton to pause rolling once and restore full backlight intensity
Rolling is disabled by setting the delay to 0.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all rolling mode settings to their factory default values
• Reset — Displays factory default values. Previous changes are not lost unless you save the reset window.
Single-line diagrams
A single-line diagram, or mimic diagram, is a line drawing of elements in an electrical system. The graphical front panel
displays up to five single-line diagrams. Each can be configured to show the arrangement of a portion of the power
system, the status of circuit breakers and of ground and disconnect switches, user-programmable pushbuttons, and
metering and status values. Each also enables control of the displayed power system devices.
Configure the diagrams under Settings > Product Setup > Graphical Panel > Single Line Diagram Editor.
Each single-line diagram page has a user-configurable name that appears in the header and in the footer Tab pushbutton
label. Factory default names are SLD 1 to SLD 5. Pages that have no configured content have a blank Tab pushbutton
label, and the Tab pushbutton does nothing. The label for the current page has a blue background.
The letters T, S, B, R, and X next to a controllable element have the following meaning. An example (TSB) is shown in the
next figure.
• T — The element is "tagged." Local and remote control of the device are inhibited, both open and close. Tripping is
unaffected unless additional logic has been configured.
• S — The position indication of the device is substituted with a manually entered value
• B — Blocking open/close command is bypassed
• R — Autoreclose is enabled and not blocked
• X — The device is out-of-service and control is not available
Under Settings > System Setup > Switches and Breakers, enable and name the six switches and two breakers. Switch 6,
M568G, has the A/3 Pole Opened setting on.
Figure 4-25: Configure Breaker and Switch settings
In the EnerVista software, open the single-line diagram editor under Settings > Product Setup > Graphical Panel > Single
Line Diagram Editor.
Add the four switches for the top line by clicking the GE switch symbol in the toolbar, then clicking in the window. (If the UR
device is not online, the software attempts to connect.) Right-click to edit properties. Rotate switches SW569 and SW5682
to 270 degrees. Rotate switches 5681 and SW523 to 90 degrees. Ignore the TSB text.
Next is to close circuit breaker CB523. This circuit breaker is shown at the top right of the figure. A vertical line means that
it is open, and the color can be set as red or green.
On the graphical front panel, press the Home pushbutton, then press the SLDs pushbutton to activate the first single-line
4 diagram page.
Figure 4-26: Single-line diagram on graphical front panel
Press the Enable Control pushbutton. The side pushbutton labels display.
Press the pushbutton to close the breaker, confirming the action at the prompt.
In this diagram, the two circuit breakers have hard-coded actions available to them. No action is possible on the switches.
Note the USER PB 9 and 10 entries in the earlier figure. As outlined later, these are activated by clicking the PB icon on the
software toolbar. These two pushbuttons can be configured under Settings > Product Setup > User-Programmable
Pushbuttons.
• Store — Saves all five single-line diagrams as a .mif file. Because single-line diagrams are not retained when using the
Convert Device Settings function, for example when converting in the Offline Window area from version 7.6 to 7.7, GE
recommends making backup files using this function.
On the right side of the window is a toolbox containing the components that can be added to the window. These include
line, breaker, disconnect, metering value, status value, text, and miscellaneous power system elements. To create the
single-line diagram, click the symbol, then click in the window. Once in the window, the component can be positioned and
its properties modified. When using the pointing device to position a component, the component can snap to the nearest
snap point. Snap points are in a 4 x 4 rectangular grid. The keyboard arrow keys move the selected component(s) in one
pixel increments when snap locations are inadequate. Multiple components can be selected and moved or deleted as a
group, or copied and pasted to another location. Right- or double-clicking a component opens the properties window.
Ctrl+A selects all objects in a diagram.
Lines
Line components represent power system buses or electrical connections between power system elements. They can also
be used as visual dividers and underline.
To add a line component, click it in the toolbox, then click in the window. Double-click a line to open its properties window
to set orientation.
Figure 4-29: Line and bus crossover symbols
4
Static symbols
Static symbols depicting power system elements are available. For information, see the ANSI/IEEE 315A and IEC 60617
standards.
Up to 32 static symbols can be used per single-line diagram.
To add a symbol, click it in the toolbox, then click in the window. Double-click the symbol to open its properties window to
set orientation.
To add a breaker or disconnect component, click it in the toolbox, then click in the window. Up to 10 dynamic components
can be added to each single-line diagram.
Breaker and disconnect components have three different parts: label, symbol, and flags. Drag each of its parts to their final
locations. Double or right-click any of these parts to open the properties window. Properties that can be edited are label
text, breaker control element or disconnect switch element number, symbol orientation (horizontal or vertical), color
scheme (red - closed, or red - open), and assigned side button (if any). If the selected breaker or disconnect element does
not exist in the target relay or has not been enabled, then the component is displayed in the graphical front panel and in
the drawing edit window in grey. The color scheme selection has no effect when an IEC style symbol is used because IEC
style symbols do not use color.
Symbol orientation
The figure shows the orientation available for the breaker and disconnect switch (taking Open status as examples). The
default position is 0 degrees.
Figure 4-32: Single-line diagram symbol orientation
A question mark displays in a symbol on the graphical front panel when status is bad. The question mark does not rotate
with orientation.
Figure 4-33: Symbols when status is bad
The following figures show the orientation available for the static components. The default position is 0 degrees.
User-programmable pushbuttons
User-programmable pushbuttons 1 to 8 are physical pushbuttons on the right side of the graphical front panel, numbering
down the two columns.
User-programmable pushbuttons 9 to 16 can be programmed among the 10 pushbuttons on the left and right sides of the
screen display. They show dynamically and provide a means to perform the same control as the other pushbuttons.
4 As an example, if you set up a single-line diagram with two breakers and six switches, then eight of the side pushbuttons
are used automatically for control of the breakers and switches. Side pushbuttons 9 and 10 are available. In the single-line
diagram, let us set side pushbutton 9 to clear event records as follows:
• Show side pushbutton 9 on the graphical front panel — Click the PB symbol in the toolbar, then set Side button 9 to
pushbutton 9 in the drop-down list. This pushbutton then displays when appropriate on the right side of the screen
display.
• Program event record clearing — Set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 9 ON
• Program pushbutton 9 — Set Settings > Product Setup > User-Programmable Pushbuttons > Pushbutton 9
Function to "Self-reset." When pressed, pushbutton 9 clears the event records.
To instead set the second user pushbutton (not a side pushbutton) to clear events, follow the second and third bullet
points, selecting settings of PUSHBUTTON 2 ON and Pushbutton 2.
Metering components
Metering components show dynamically the value of a FlexAnalog operand or actual value. Up to 16 metering
components can be added to each single-line diagram.
To add a metering component, click the M symbol in the toolbox, then click in the window. Drag it to its final location.
Double-click it to open the properties window. The figure shows the properties that can be edited.
Status components
Status components show dynamically the value of a FlexLogic operand. Up to 16 can be used in a diagram and 30 in all
single-line diagrams.
An example is to show the Off or On state of the ANY MAJOR ERROR FlexLogic operand. The name of the operand displays in
the single-line diagram editor, then as Off or On on the graphical front panel.
To add a status component, click the S symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited include parameter (any FlexLogic operand), text color
background color, and on and off text.
Optionally add a text label to display beside the status.
Text
Text components show a single line of user-configured text.
Up to 16 text components can be used per single-line diagram.
To add a text component, click the T symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited are text, color, and size.
Annunciator
An annunciator is a grid of small windows for alarms, actual values, self-test messages, and product information.
The graphical front panel emulates a conventional annunciator panel. The annunciator has 96 windows, each with a
description of the alarm condition that lights the window. The windows are arranged in rows and columns of 3 x 4, 4 x 6, or
6 x 8 over several pages. Each window can have up to three lines of configurable text, and one line can instead be a
metered value. Normally the window background is dark, and when the configured FlexLogic operand becomes On, the
window lights up.
The figure shows that two alarms are active. One alarm is configured red and the other alarm is configured blue. The red
alarm type is Self Reset, so the alarm displays in a solid color. The blue alarm type is Acknowledgeable, so the alarm flashes
until it is acknowledged, for example by navigating with the arrow keys and pressing the ENTER button. The alarm then
remains blue until the trigger condition is eliminated.
To display the annunciator, press the Home pushbutton, then the Annunciator Tab pushbutton. If there is one or more
4 window in alarm or requiring reset, the annunciator page showing the first of these opens. Otherwise the first annunciator
page opens.
Alarms do not display automatically. Set the Home page and/or rolling pages to display annunciator pages.
The Tab pushbutton labels populate with the annunciator pages. The label text for each annunciator page is configurable
and displays in the header and Tab label. The current page has a blue Tab label. Tab labels for annunciator pages that
have an active window (that is, on, latched, or unacknowledged) are red. Pages where alarms are not triggered have a grey
Tab label. Pages that have no configured windows do not have Tab pushbuttons and do not display.
The Up, Down, Left, and Right pushbuttons cause the selection to move one window in the indicated direction. Pressing the
Right pushbutton past the last window in a row scrolls the display to any next annunciator page, not the next row. The
behavior is similar for the other pushbuttons, for example pressing the Up pushbutton while in the top row goes to any
previous page. If no previous page exists, no action occurs.
Annunciator windows are positioned statically, so that all windows are visible no matter their state.
Alarm types of each window can be configured as Self Reset, Latched, or Acknowledgeable. In Self Reset mode, the
window lighting follows the state of the configured FlexLogic operand. The self-reset mode alarm sequence conforms to
ISA-18.1-1979 (R2004) standard type A 4 5 6.
Figure 4-39: Annunciator alarm sequence in Self Reset mode
Process: Normal
Sequence: Normal
Visual: Off
Return to Normal
To Abnormal
Process: Abnormal
Sequence: Acknowledged
Visual: On
859856A1.vsd
Latched mode is intended for transient signals such as trip, and it conforms to ISA-18.1-1979 (R2004) standard type M 6.
Figure 4-40: Annunciator alarm sequence in Latched mode
Process: Normal
Sequence: Normal To Abnormal
Visual: Off
Process: Abnormal
Reset while
Sequence: Acknowledged
Abnormal
Visual: On
859857A1.vsd
4
In Acknowledgeable mode, both Off to On and On to Off state changes in the configured operand cause the background to
flash; the window must be acknowledged/reset to cancel flashing. This mode conforms to ISA-18.1-1979 (R2004) standard
type R-6.
Figure 4-41: Annunciator alarm sequence in Acknowledgeable mode
Process: Normal
Reset Sequence: Normal To Abnormal
Visual: Off
Process: Abnormal
Reset while
Return to Normal Sequence: Acknowledged
Abnormal
Visual: On
859858A1.vsd
An alarm remains in an alarm state (for example, displays red) when the condition remains. That is, if you acknowledged a
flashing alarm but the alarm condition remains, the background color remains red.
The SETTINGS > INPUTS/OUTPUTS > RESETTING > RESET ANNUNCIATOR setting can be used to select a FlexLogic
operand that when activated acknowledges/resets all annunciator windows.
Annunciator editor
The annunciator editor is used to configure alarms and actual value displays for the graphical front panel.
The path in the EnerVista software is Settings > Product Setup > Graphical Panel > Annunciator Editor.
The figure shows the annunciator editor and its preview window. The page name is entered as General at the top right.
Acknowledgeable and self-resetting alarms are set for basic functions, such as online/offline, Ethernet ports, unauthorized
access/failed logins, and battery failure. The text to display in the annunciator window is entered. The IN SERVICE LED is set
to be green because when the device is on, this LED is green. The preview shows what the annunciator looks like with all
alarms triggered. The last window is not configured and displays blank/grey. In order for the Ethernet and battery alarms
to work, the corresponding self-test alarms have been enabled under Settings > Product Setup > User-Programmable
Self Tests (not shown). The LEDs can be viewed on the front panel, so adding them to the annunciator is for illustrative
purposes only.
The three page layouts (3 × 4, 4 × 6, and 6 × 8) select the number of rows x columns of windows that appear in a page.
Annunciator window size and text size shrink as the number of annunciator windows in a page increases.
Properties that can be edited include alarm type (acknowledgeable, latched, self-reset), alarm input (any FlexLogic
operand), text color, and alarm background color.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all annunciator settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.
Metering editor
The metering editor is an actual values display tool. It creates pages of actual values for the graphical front panel. There
are two types: tables and phasor diagrams. Tabular actual values pages have settings to configure, while phasor actual
values pages have no settings. Five tabular metering pages can be configured, while there can be a phasor page for each
configured AC source. They display on the graphical front panel using the Metering Tab pushbutton.
The path to the editor is Settings > Product Setup > Graphical Panel > Metering Editor.
Figure 4-43: Metering editor with preview window
4
The inputs are selected at the top. Select from the drop-down list or start typing in the field.
The page, page name, and grid layout are set below the inputs.
Content to display is configured with the cell lines. The content can be actual values, a status indicator, or text.
• Actual value — Select from the FlexAnalogs applicable to the B90, where a FlexAnalog is an analog parameter
• Status — Select from the FlexLogic operands identified in the Status Inputs at the top of the window. An example is to
display text to indicate whether the BATTERY FAIL operand is on or off.
• Text — Enter text to display in the table, for example name of table or column heading
If the metering input is other than OFF, the value of the selected metering input displays, formatted according to the size,
text color, units, multiplier, and decimal configuration. Otherwise either the Text or the Off Text displays depending on the
value of the operand selected by setting Status Input/Index.
A maximum of eight Status Inputs/Indexes can be used per metering page and 16 in all metering pages.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all actual value settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.
The path is Settings > Product Setup > Graphical Panel > Configurable Navigation.
The settings consist of 64 field pairs, each with a condition and an activation page. The condition selects any FlexLogic
operand. The activation page selection is the standard set, such as product information, event records, annunciator pages,
and single-line diagrams.
To use the feature, select a CONDITION, select its ACTIVATE PAGE option, then save. When selecting the condition
operand, open the drop-down list and start typing in the field to auto-fill. For example, typing F displays FIRST ETHERNET
FAIL.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
SETTINGS
PRODUCT SETUP
HELP 4 5 6
3. Press to scroll third level fields MESSAGE
2. Press to scroll second level:
ESCAPE 1 2 3 PRODUCT SETUP.
4. Press to scroll through values
ENTER VALUE 0 . +/-
5. Press to save change
842231A1.cdr
Up/Down/Left/Right — These pushbuttons move the selector among the options on a page. The selection is
indicated by a yellow background or a yellow border. On menu pages, the Right pushbutton activates the selected
submenu drilling down the menu hierarchy, and the Left pushbutton backs up the menu hierarchy. These
pushbuttons have a typematic feature on some pages: after a short pause, the pushbutton repeats as long as it is
pressed.
ENTER — Activates the selection on the display, for example a submenu, a control, a keypad key, or a setting. Also
stores updated settings.
ESCAPE — If a setting is open for edit, this pushbutton closes the setting without saving. If a popup menu is open,
this pushbutton closes it. If an item is selected, this pushbutton deselects it. Otherwise this pushbutton activates
the previous page in the page hierarchy.
RESET — Clears all latched LED indications and target messages. When a page with acknowledgeable/resettable
items is displayed, it instead resets/acknowledges all items on that page, or if an item on that page is selected, it
resets/acknowledges that item.
If you reset/acknowledge alarms, they stop flashing but remain in the alarm state as long as that state remains. In
other words, a red alarm does not switch off just because you acknowledged the alarm.
Home — Activates the home page, which is the root page. The page displays product information by default and
is configurable.
Side pushbutton — Five pushbuttons on the left side of the display and five pushbuttons on the right side of the
display. They perform various functions depending on the displayed page, such as switchgear controls. The
display dynamically shows its label next to each side pushbutton when the pushbutton has an assigned function.
These pushbuttons can also be programmed to function as user-programmable pushbuttons 9 to 16.
Tab pushbutton — Five pushbuttons under the display. They navigate through the page hierarchy, and on some
pages activate other actions. The display footer dynamically labels the page or action that is activated by the Tab
pushbutton.
User-programmable pushbutton — Eight physical pushbuttons are associated with the first eight user-
programmable pushbutton elements. Numbering is down, that is, 1 to 4 down the left column and 5 to 8 down the
right column.
These elements control a set of FlexLogic operands that can be used to initiate outputs or select modes. Each
physical pushbutton has an integrated LED indicator that can be user-configured to display the appropriate
status.
4 These pushbuttons have clear covers behind which custom labels can be mounted. A utility is available to print
the labels, under File > Front Panel Report in the software.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the FlexLogic operand serving as an alarm switch has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator never latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as either “Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the
corresponding event-cause LEDs remain on as long as the operand associated with the element remains asserted. If a
protection element target setting is “Latched,” then the corresponding event-cause LEDs turn on when the operate
operand associated with the element is asserted and remains on until the RESET button on the front panel is pressed after
the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — Indicates voltage was involved 4
• CURRENT — Indicates current was involved
• FREQUENCY — Not used
• <blank> — Always off by default
• ZONE 1 — Indicates bus differential zone 1 was involved
• ZONE 2 — Indicates bus differential zone 2 was involved
• ZONE 3 — Indicates bus differential zone 3 was involved
• ZONE 4 — Indicates bus differential zone 4 was involved
• OTHER — Indicates a composite function was involved, BUS 5 OP was asserted, or BUS 6 OP was asserted. For the
B90, a composite function means either any Digital Element OP or any TRIP BUS OP.
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label
package of every B90, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-Programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and
the relay is in (online) Programmed mode (under Settings > Product Setup > Installation)
4 • TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip switch has operated. This indicator always
latches; initiate the reset command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm switch has operated. This indicator never
latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.
Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event cause LEDs
remain on as long as the operand associated with the element remains asserted. If a protection element target setting is
“Latched,” then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remains on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — Indicates voltage was involved
• CURRENT — Indicates current was involved
• FREQUENCY — Not used
• <blank> — Always off by default
• ZONE 1 — Indicates bus differential zone 1 was involved
• ZONE 2 — Indicates bus differential zone 2 was involved
• ZONE 3 — Indicates bus differential zone 3 was involved
• ZONE 4 — Indicates bus differential zone 4 was involved
• OTHER — Indicates a composite function was involved, BUS 5 OP was asserted, or BUS 6 OP was asserted. For the
B90, a composite function means either any Digital Element OP or any TRIP BUS OP.
User-programmable indicators
The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Custom labelling
can be done.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
Figure 4-48: LED panels 2 and 3 (index template)
Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay’s test mode is disabled, and the relay is in (online) Programmed mode (under Settings > Product Setup >
Installation)
• TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in Isolated (solid) or Forcible (flashing) test mode. For information, see the Test
Mode section in the Settings chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm input has operated. Set the operand
under Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs.
Figure 4-50: Example of LEDs on graphical front panel
• Small-bladed knife
To create custom LED and pushbuttons labels for the enhanced front panel:
1. Start the EnerVista UR Setup software.
2. If not already copied to the Offline Window area, right-click the online device and select the Add Device to Offline
Window option. Click the Receive button in the window that opens to save the settings file to the Offline Window area.
3. Type labels as follows. Select the File > Front Panel Report. The window opens.
Figure 4-51: Enhanced front panel label designer
4. Enter the text to appear next to each LED and above each user-programmable pushbutton in the fields provided. The
LED Offsets and Button Offsets buttons move all labels left/right and up/down on the page (they both do the same
action, so use either button). The Button Offsets button does not display when there are no pushbuttons to customize.
5. Feed the UR front panel label cutout sheet into a printer and press the Print button in the front panel report window.
6. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
7. Remove the UR label insert tool from the package and bend the tabs as described in the following procedures. These
tabs are used for removal of the default and custom LED labels.
Use the tool with the printed side containing the GE part number facing the user.
The label package shipped with every B90 contains the three default labels, the custom label template sheet, and the label
removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, use the following procedures to remove the original labels and insert the new ones.
To remove the LED labels from the B90 front panel and insert the custom labels:
1. Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from
the relay.
2. Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown.
To remove the user-programmable pushbutton labels from the B90 front panel and insert the custom labels:
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown. This attaches the
label tool to the user-programmable pushbutton label.
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the
buttons.
4
4.2.5.2 Basic front panel
After programming LEDs and pushbuttons under Settings > Product Setup > User-Programmable Leds and User-
Programmable Pushbuttons, labels can be created for the front panel.
To create LED and pushbutton labels for a basic front panel:
1. In the EnerVista software, if the B90 is not already listed in the Offline Window area, add it by right-clicking it and
selecting the Add Device to Offline Window option.
2. Click the File > Front Panel Report menu item and select the device.
3. In the Front Panel Report window, double-click an LED or pushbutton slot and type a label. If you need to see the
existing front panel remotely, access Actual Values > Front Panel for the online device. If you need to see the In the
figure, note that labelling is being done for the third set of LEDs because the second panel of LEDs was factory-
labelled.
4
4. Optionally save the changes by clicking the Save icon on the toolbar.
5. Click the Print icon on the toolbar. Consider printing to PDF format and adjusting the zoom for appropriate label size,
then print on a physical printer.
6. Cut labels as a block or individually, for example with scissors or an Exacto knife.
7. If there is a plastic cover over the front panel, remove it by gently pushing in on the right side and lifting off the cover.
8. Remove the plastic cover over the LEDs or pushbutton(s) using a screw driver.
9. Insert the labels.
10. Re-attach the plastic covers.
Figure 4-53: Front panel label designer for graphical front panel
5. Click the Print button in the window and select the printer.
6. Once printed, peel the labels off the template and stick them on the front panel. For the enhanced and graphical front
panels, they go over the clear plastic inserts, not under. For the basic front panel, they go under or over the plastic
covers.
Any changes are not saved. Each time that the label designer window opens, the original template displays. Any labels
deleted are not lost.
values. Continually pressing the MESSAGE right arrow from a header display displays specific information for the category.
Conversely, continually pressing the MESSAGE left arrow from a setting value or actual value display returns to the header
display.
Default values are indicated in this instruction manual in mixed case. In the example shown here, the default access level is
Restricted.
Highest level Lowest level (setting value)
Example
ACTUAL VALUES Press the MENU key until the Actual Values header page appears. This page contains system
STATUS and relay status information.
4 SETTINGS
Press the MENU key until the Settings header page appears. This category contains settings to
PRODUCT SETUP configure the relay.
SECURITY Press the MESSAGE right arrow once to display the first sub-header (Security).
ACCESS LEVEL: Press the MESSAGE right arrow once to display the first setting for Security.
Restricted
SECURITY Press the MESSAGE left arrow to return to the Security heading.
DISPLAY Press the MESSAGE down arrow to display the second setting sub-header associated with the
PROPERTIES Product Setup header.
LANGUAGE: Press the MESSAGE right arrow once to display the first setting for Display Properties.
English
SETTINGS Press the MESSAGE left arrow to return to the Display Properties page, then again to return to
SYSTEM SETUP the Product Setup Page. Press the MESSAGE down arrow to move to the next Settings page. This
page contains settings for System Setup.
Numerical data
Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define
what values are acceptable for a setting.
FLASH MESSAGE For example, select the SETTINGS PRODUCT SETUP DISPLAY PROPERTIES FLASH
TIME: 10.0 s MESSAGE TIME setting.
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the key again to view the
MAXIMUM: 10.0 next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point — The relay numeric keypad works the same as a calculator. A number is entered one digit at
a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MESSAGE left arrow or
pressing the ESCAPE key, returns the original value to the display.
• VALUE keys — The VALUE up arrow increments the displayed value by the step value, up to the maximum value
allowed. While at the maximum value, pressing the VALUE up arrow again allows the setting selection to continue
upward from the minimum value. The VALUE down arrow decrements the displayed value by the step value, down to
the minimum value. While at the minimum value, pressing the VALUE down arrow again allows the setting selection to
continue downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate numeric
TIME: 2.5 s keys in the sequence “2 . 5". The display message changes as the digits are being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Press ENTER to store the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation of the storing
process. Numerical values that contain decimal places are rounded-off if more decimal place digits
are entered than specified by the step value.
Enumeration data
Enumeration settings have data values that are part of a set, whose members are explicitly defined by a name. A set has
two or more members.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted," "Command," "Setting," and
Restricted "Factory Service."
Enumeration type values are changed using the VALUE keys. The VALUE up arrow displays the next selection while the
VALUE down arrow displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting," press the VALUE keys until the proper selection displays.
Setting Press HELP at any time for the context sensitive help messages.
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing ENTER stores the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation.
4 Alphanumeric text
Text settings have data values that are fixed in length, but user-defined in characters. They can be upper-case letters,
lower-case letters, numerals, and a selection of special characters.
There are several places where text messages can be programmed to allow the relay to be customized for specific
applications. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example, enter the text “Breaker #1”.
1. Press the decimal point to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for several
seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
Numerical data
This example outlines how to change the FLASH MESSAGE TIME setting. Flash messages are status, warning, error, and
information messages displayed in response to certain key presses during settings programming. An example is a
confirmation message upon saving settings. This setting specifies how long to display the message.
Press the Menu pushbutton to display the main menu.
Use the Up or Down pushbutton to select SETTINGS, then press the Right or ENTER pushbutton.
Figure 4-56: Settings menu 4
Use the Up or Down pushbutton to select DISPLAY PROPERTIES, then press the Right or ENTER pushbutton.
4 Figure 4-58: Display Properties menu
Use the Up or Down pushbutton to select FLASH MESSAGE TIME, then press the Right or ENTER pushbutton. If the relay is
configured to require login to edit settings, and the user is not already logged in, the login page displays. When the user
has successfully logged in, the setting is opened for edit. As the FLASH MESSAGE TIME setting accepts a numerical value, a
keypad displays. The time is to be changed to 4.0 seconds.
The current setting displays. A flashing cursor line marks the insertion point, initially positioned after the last character of
the setting. The setting range displays under the text.
Press the <-- Move Cursor and Move Cursor --> Tab pushbuttons to move the insertion point. Place it after the 2.
Press the Backspace Tab pushbutton to remove the character to the left of the cursor, in this case the 2.
Using the arrow keys, enter another time, for example 4 for four seconds. These Up, Down, Left, and Right pushbuttons
move the keypad key selector. Pressing the ENTER pushbutton with the - key selected inverts the sign. Pressing the ENTER
pushbutton with the decimal point selected enters that character at the insertion point. Push ENTER now to accept the 4.
Press the Save Tab pushbutton, which does a range check on the value, saves the setting when valid, closes the page, and
displays the previous page. 4
When a setting is not saved due to an invalid value, a message flashes, for example being out of range. In cases where the
relay needs to be restarted for settings to take effect, the flash message advises.
Setting entry can be cancelled without impact on the original value by pressing the ESCAPE or Home pushbutton.
Alphanumeric text
Settings that accept alphanumeric values display a keyboard. An example is a pushbutton name.
The &123 key toggles between text and numbers.
The shift key (up arrow on keyboard) is green upon activation, while the keyboard letters switch to upper case. Double-click
the shift key to lock capital lettering, or full capitals.
The globe key (shown greyed-out) toggles the keyboard language between English and another display language selected,
for example between English and French. (The second language needs to be activated under Settings > Product Setup >
Display Properties.)
For Japanese and Chinese, up to 10 characters can be input in a field, not 20.
To add accents, highlight a key and hold the ENTER pushbutton on the graphical front panel. Any special characters
associated with the key display.
Figure 4-60: Settings page with keyboard and accents
The configurable name displays in the header and Tab pushbutton label. Factory default names are Page 1, Page 2, and so
on.
The phasor sources are configured under Settings > System Setup > Signal Sources. The tables to display the actual
values are configured in the software under Settings > Product Setup > Graphical Panel > Metering Editor.
4
display.
2. Press the MESSAGE right arrow until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE down arrow until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE right arrow until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
SECURITY ACCESS LEVEL:
Restricted
CHANGE SETTING
PASSWORD: No
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change the
selection to “Yes.”
6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.
7. Type in a password and press the ENTER key.
8. When VERIFY NEW PASSWORD displays, re-type the password and press ENTER.
4 CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) password is active.
Reading from right to left in the following diagram, the TRIP BUS 1 OP and TRIP BUS 1 PKP FlexLogic operands on the right side
are triggered when either the settings or reset latch in the middle of the diagram is triggered. When this applies, the TRIP
BUS 1 OP operand is triggered after the delay set by the TRIP BUS 1 PICKUP DELAY or TRIP BUS 1 RESET DELAY setting, while the
TRIP BUS 1 PKP operand initiates immediately. The settings or reset latch in the middle of the diagram is triggered as follows.
• For the reset, one of three conditions are required to meet the OR requirement shown at the bottom left. That is, the
TRIP BUS 1 LATCHING setting must be 0=Disabled (which is negated by the NOT function to become 1=Enabled), output
from the TRIP BUS 1 RESET FlexLogic operand must be 1, or output from the RESET OP FlexLogic operand must be 1.
• For the settings, one of 16 input conditions at the top left must be met for the OR, the TRIP BUS 1 FUNCTION must be
Enabled, and the TRIP BUS 1 BLOCK output must output as 0, which is then negated/reversed by NOT to become 1.
Table 4-2: Logic diagram symbols
Symbol Description
= Off Output from FlexLogic operand, so user-defined
= Enabled 1 = Enabled and 0 = Disabled
OR Any function input on the left side satisfies the condition
AND All functions input on the left side are required to satisfy the condition
Not. Negates/reverses the output, for example 0 becomes 1.
Connection
S, R Set, Reset 4
TPKP Timer pickup. Triggered by the settings latch in the diagram.
TRST Timer reset. Triggered by the reset latch in the diagram.
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
4.4.1.1 Examples
The symbols are displayed in the UR format.
Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, the first and second virtual outputs are named
OscTrigger
Top logic — Three-minute timer trigger
Bottom logic — Turn on LED 1 for 10 seconds when the trigger starts
Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger
Top logic — Seven-minute timer trigger
Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts
Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual output 5 is named EVStart, 6 is named
EVTriggered, and 7 is named EVMakeEvent
Top logic — One-minute timer trigger
Middle logic — Turn on LED 17 for 10 seconds when trigger starts
Bottom logic — Create events at 100 ms intervals for the same 10 second period
The FlexLogic Equation Editor window is in view-only mode when the Logic Designer is open. To instead work in the
FlexLogic Equation Editor, close the Logic Designer window, then re-open the FlexLogic Equation Editor.
option.
Upon saving the modified FlexLogic, a yellow icon appears for the device in the Offline Window area to indicate that
the logic differs from the Online device.
2. In the Offline Window area, access Engineer for the device, then Logic Designer. The logic opens.
3. Click the Edit > Auto Populate Workbook menu item. If the software prompts if you want to keep or discard existing
sheets, either is acceptable, with the older excluded sheeted being denoted by brackets, such as < Sheet 1 >. The logic
displays in the various tabs. The FlexLogic created in the equation editor appears in Sheet 1, for example.
A default block diagram opens that shows 48 inputs (boxes) and 48 user-programmable LEDs (circles).
For the graphical front panel, no LEDs can be added to the window and the LEDs are removed when opening any
existing files. For these existing files with the LEDs removed, save the file without them.
2. Optionally delete the default logic diagram by right-clicking its tab at the bottom of the window and selecting Delete.
3. To add a blank sheet, click Edit > Add Sheet. A new tab displays. Or use the last tab displayed, which is a blank sheet.
4. Optionally right-click the new tab and Rename it.
5. Add the input blocks to the logic diagram. For example, click the I/O Tokens tab on the right, click the Input element,
then click in the logic sheet to add it. Or drag-and-drop it.
6. Double-click the block on the sheet to configure it, selecting from the two drop-down lists. The figure shows that
virtual input 61 is being added. The View Associated Screen button opens its settings window.
Figure 4-70: Configuring an input block
7. Add the output blocks to the logic diagram. For example, click the I/O Tokens tab, click the Virtual Output element,
then click in the logic sheet to add it. Double-click the block on the sheet to configure it. For the name, make it unique.
The figure shows virtual output 61 is being added, with a suffix of "io" added to the name to make it unique. Note that
the outline color of a block is red until it is configured, and that this properties window varies by block and the
selectable options by order code.
Figure 4-71: Configuring an output block
4
8. Connect the input blocks to the output blocks by drawing a line as follows. Click at the end of one block and drag the
line to the next block. Or click the Drawing Tools tab, then select the Line option. The cursor needs to be at the
connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks.
Figure 4-72: Completed inputs and outputs
9. Add any remaining blocks or information. Right-click a block to copy and paste it. Notes are as follows.
Add a text box — Drawing Tools > Text
Add a FlexElement — Elements > FlexElement. An analog input is expected where a small arrow head shows in the
box.
Figure 4-73: FlexElement accepts analog inputs on left side where arrow heads display
Add an Element — Elements tab. Available elements reflect the product, for example the Control Elements category.
10. Check for any blocks that have a red outline. These are invalid. Fix them before continuing, for example by configuring
them.
11. Compile the logic diagram to check for errors by clicking the Compile button at the bottom left or by pressing the F7
key.
4 If prompted about a message about sorting, click Yes to apply the default (for this example), which can be automatic
sorting based on an algorithm that applies fastest execution time.
With successful compiling, the file is saved and the FlexLogic equations populate automatically. Scroll up through the
compile messages, with the red errors being the only messages that require fixing before proceeding.
The figure shows that we forgot to add the "Io" suffix to the names of virtual outputs 62 and 63, as indicated by
"Warning: Virtual output xx using default name." This warning is a minor warning.
The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the
View Associated Screen button, enable the setting, save, and recompile.
The output and messages are explained in the next section.
Some information displayed in the compile messages updates automatically, for example messages after a device is
unplugged.
Figure 4-75: Compile and check the logic
12. View the FlexLogic equations by navigating in the Offline Window area to FlexLogic > FlexLogic Equation Editor. The
window opens with the entries displayed in the next tab.
When the Update SCL files option is selected, the CID and IID files in the device folder are updated by the user
configuration in the IEC 61850 panel and thereby become synchronized. The CID file and the IID file (depending on the
preference 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated.
The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.
Any FlexLogic equations entered in the Offline Window area are erased. The logic drawn in the Logic Designer window in
Engineer in the Offline Window area remain. The warning icon disappears after updating.
The following information is contained in the compile window.
Number of Lines Saved — The number of compiled logic lines eliminated by using the optimization algorithm, as set in the
Optimize Compiled Output option of the Preferences. In the example shown, no lines were saved because the optimizer is
disabled.
FlexLogic Lines — The number of lines that the compiled logic uses, for example seven of 512 available.
Virtual Output equations — The number of FlexLogic equations used in the Logic Designer window.
Timers used — The number of timers used in the Logic Designer window.
Memory Used — The percent of memory used in the Logic Designer window.
Errors
Table 4-3: Errors from compiling
Category Block or gate Message Description
affected
Error All Number of lines (nnn) exceeds The compiled result exceeds the limit of 512. Reduce the number of
maximum limit of 512 equations to 512 or less.
Error Tag-In Tag-in not configured (TAG_ID, A Tag-In is connected to a circuit but the Tag-In is not referencing an
SheetReference) existing Tag-Out
Error 1 Shots One Shot is over limit The number of One-Shots contained within all of the VO blocks has
(SYMBOL_ID, SheetReference) exceeded the maximum allowed for the firmware revision. This value can
either be 0 or 32.
Error =VO VO has no inputs (VO_ID, A Virtual Output block is located within the FlexLogic diagram and there
SheetReference) is no block connected as input to it. Connect and identify the inputs.
Error Timer Timer used more than once The same timer is used in more than one place in the editor. This means
(TIMER_ID, SheetReference) either the circuit that the Timer belongs to has been branched, or the
Timer has been duplicated.
Warnings
When using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that the
Reset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the front
panel of the relay or by sending a Reset command through communications.
Table 4-4: Warning messages from compiling
Category Block or Message Description
gate
affected
Minor warning Input Input set to unused VO An Input symbol is using an unassigned Virtual Output
(SYMBOL_ID,Name,Sheet)
Major warning Tag-Out Tag-out not connected A Tag-Out symbol has no input
(TAG_ID,Sheet)
Major warning All Symbol not connected
(SYMBOL_ID,Name,Sheet)
A symbol’s input and/or output is not connected and is not part of a
VO block. Draw the input and/or output to the block.
4
Minor warning =VO Virtual Output n using default The Assigned Virtual Output is using the default name. Change the
name (VO_ID,Sheet) name.
Minor warning Input Input using default name An Input symbol is using a Contact Input, Contact Output, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, or Digital Counter set to the default name.
Change the name so that it is unique.
Setting warning Input Input using disabled feature An Input symbol is using a disabled Virtual Input, Contact Input, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, Digital Counter, Control Pushbutton,
Programmable Pushbutton, Contact Output, or Protection/Monitoring
Element. Enable it and try again.
Major warning Input Input set to OFF An Input symbol is set to OFF
(SYMBOL_ID,Sheet)
Major warning Input Input set to ON An Input symbol is set to ON
(SYMBOL_ID,Sheet)
Setting warning Input Contact Output Operate is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)
Setting warning Input Contact Output Seal-In is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)
4. In the second sheet, click and drag the Tag In element to the sheet where the first sheet is to connect.
5. Double-click the element and in the window that opens, select the first sheet from the drop-down list to connect the
two sheets.
6. Save the work.
You can also select an element from the drop-down list on the toolbar. It is then highlighted in the logic diagram.
Figure 4-85: Monitoring a device, with minor error caused by weak battery
To print labels:
1. In the Front Panel Report window, double-click an LED or pushbutton and enter text.
2. To print the labels, click the Print icon on the toolbar.
3. To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format.
4. Use the instructions in the second tab of the window to add the labels to the physical device.
4.4.6 Preferences
Preferences determine functionality. As such, you are encouraged to review them. This section outlines some options
available in the menus and preference panels.
Access them in the Logic Designer panel under the View menu and under File > Preferences. The Logic Designer and
Logic Monitor preferences are outlined here, not all preferences for a device.
Workbook Setup
4 WorkBook
Print Scale — The scale for logic diagram when printing. Scaling a large diagram to 200 percent, for example, results in the
diagram being cut off.
Orphan Protection — When enabled, the printing output prevents Virtual Output circuits from spanning more than a single
page. The largest Virtual Output circuit is scaled to fit on a single page and all remaining Virtual Output circuits are scaled
so that all circuits are printed using the same scale.
Show Title Block — When enabled, places an information box at the bottom right of the diagram when printing. Enter the
information in the File Information panel.
Show Sheet Name — When enabled, shows Sheet 1, Sheet 2, or any other name at the top of the logic diagram when
printing.
Start Sheet On New Page — Places the sheet on the next page when printing.
Show Notes Selection — When other than None, prints the text from any information notes added to the document (under
Drawing Tools tab > Note). The text is printed after the logic diagram.
File Information
The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is
enabled. Note the option to change the logo from the GE logo to your company logo.
Display
The panel sets how the element boxes display. The figure shows how an AND gate displays when the UR default, IEC, or
ISO symbol type is selected.
Figure 4-89: AND gate varies by standard selected
Symbol Style — IEC, ISO, UR Setup — Sets how the gates display in the logic diagram.
Symbol Color — When set to Black & White, only logic blocks with issues continue to display red.
Zoom Operation — Determines what happens when the View > Zoom functions are used. When set to Sheet Only and the
zoom is changed, the single tab changes. When set to Workbook, all tabs change.
Editor
Repeat Symbol — Enable this feature to add element blocks rapidly in sequence, for example when you have inputs 1 to
10, without having to select the element each time. Select the element block from the toolbox, click the diagram, then
continue to click to add additional blocks.
Use first available VO / Timer — When enabled and you copy and paste a virtual output or timer element, the numbering
continues in sequence. For example, you copy timer 5 and paste it as timer 6. When disabled and you copy and paste a
virtual output or timer element, the same number is used. For example, you copy timer 5 and paste it as timer 5.
Auto-Save Logic Designer every x minutes — Logic diagrams with changes are saved automatically according to this
interval. The range is 5 minutes (default) to 30 minutes. With auto-save, the file extension of the saved file is .auto. This file
remains until you save the file manually.
Auto Populate
These options work in the Edit > Auto Populate Workbook function.
VOs per Worksheet — When an existing settings file is opened in the Logic Designer, the Logic Designer populates the
canvas and attempts to evenly distribute the Virtual Output circuits across multiple sheets. A value of 100 in this setting
places all FlexLogic equations on a single sheet until there are 100, then the next ones are placed on another sheet. A value
of 1 places each Virtual Output circuit on a separate sheet.
Show / FlexLogic Merge / Show Unused — If Show Contact Outputs and Show LEDs are selected, for example, the function
places Contact Output and User-programmable LED symbols for settings that are configured. If you disable the LED check
4
boxes, then the LED tab/sheet does not display when you next open the Logic Designer window. The settings apply to all
products, not just the active window when it is next opened. Close then reopen the Logic Designer window for the setting
to take effect.
Compiler
Show Warnings — Options to filter the messages that display when logic compiles.
Minor — Enable to display minor errors. An example is using the default values of an element added to the diagram, such
as the name of the element. An example is "Warning: Virtual output xx using default name," for which you simply click into
the element to rename it.
Major — Enable to display major errors. Examples are an input that does not have a corresponding output, using disabled
features, and failing to connect a symbol. Fix these errors.
Setting — Enable to display error message related to settings, such as an improperly configured setting, such as using ON
or OFF.
Automatically Sort VOs — When enabled, the logic is compiled with an algorithm to give best results and quickest
performance, for example the fastest logic first. The fastest logic displays in the FlexLogic Equation Editor output as the
first entries in the table. Use sorting when virtual outputs have dependencies on other virtual outputs. This setting takes
precedence over order set manually in the VO Order tab in the compiler.
When disabled, the sequence in which the blocks were drawn is followed.
Optimize Compiled Output — With this option enabled, the software automatically optimizes a logic diagram to reduce
space and free up FlexLogic entries. Run the compiler again, for example by clicking the Compile button at the bottom left
of the software. The number of saved lines displays in the Optimization Summary. Changes also display when the FlexLogic
Equation Editor is accessed. The logic diagram does not change.
Display
The software displays the color specified when an element is on. There is no color when the element is off.
The software displays another color when the status cannot be determined and is unknown.
Timing
Timing Information can be displayed in the monitoring window. This timing information is only an approximate
representation of how Engineer sees transitions. Use the device's Event Record to view accurate timing information.
The timing information can also be streamed to a comma-separated values (CSV) spreadsheet.
The timing information displayed and recorded can be filtered based on six categories. If a category is not selected, any
timing information related to that category does not display and is not recorded to the CSV file.
Show Timing Information in Output Window — Enable to display times in the monitoring window.
Because of the update rate of the Logic Monitoring, the timing information cannot be used as an accurate representation
of the events that occur within the relay. Use instead the device's event record. Timing information can be delayed by 30
seconds.
Save Timing Information to CSV File — Enable to write timing information in a spreadsheet. The timing information is
recorded in a text file that uses commas to separate each of the fields. This file uses the extension CSV that is supported by
any spreadsheet application.
Every change written to the CSV file requires a timestamp.
The format for the timing information in the output window is as follows:
yyyy/mm/dd hh:dd:ss
4 devicename offline
yyyy/mm/dd hh:dd:ss
devicename ONLINE
yyyy/mm/dd hh:dd:ss
VO1: Virt Out 1- 0
VI4: Virt In 4- 1
DI3: Direct In 3- 0
RI2: Remote In 2- 1
H5a: Contact In 1- 1
H1: Contact Output 1- 0
Data is only appended to the CSV file. The format for the data is as follows:
yyyy/mm/dd hh:dd:ss, devicename, offline
yyyy/mm/dd hh:dd:ss, devicename, ONLINE
yyyy/mm/dd hh:dd:ss, VO1: Virt Out 1, 0
yyyy/mm/dd hh:dd:ss, VI4: Virt In 4, 1
yyyy/mm/dd hh:dd:ss, DI3: Direct In 3, 0
yyyy/mm/dd hh:dd:ss, RI2: Remote In 2, 1
yyyy/mm/dd hh:dd:ss, H5a: Contact In 1, 1
yyyy/mm/dd hh:dd:ss, H1: Contact Output 1, 0
Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status.
4.4.7 Toolbars
These are toggled in the View > Toolbar menu.
The UR symbols are displayed for the toolbox icons. They change when the default setting is changed to IEC or ISO
symbols. The symbols displayed in the toolbox also vary by firmware version, reflecting what is supported for each release.
Open File Open an existing settings file in the URS, CID, or IID format
PDF Report Create a PDF document from Logic Designer diagram(s). Settings can be
changed under File > Preferences > Workbook Setup.
Toggle Compile Window Display or hide the compile window area
4
Sort Order Select to change the sort order of the Virtual Output list to the right of the
icon. Virtual Outputs can be sorted numerically in ascending and
descending order based on numbers and names.
Select VO to View (x - x) Select a Virtual Output to locate and select it in the workbook. Each Virtual
Output listed also contains the name of the sheet where the Virtual Output
is located.
Edit Mode Switch to Logic Designer mode
Logic Designer
Monitor Mode Switch to Logic Monitor mode
Logic Monitor
Turn On ALL Communications Turn on all communications to all Logic Designer diagrams that are in the
monitoring mode. Default upon each launch of Engineer.
Turn Off All Communications Turn off all communications to all Logic Designer diagrams that are in the
monitoring mode. This is a legacy function for serial communication to turn
off communication to devices. Turning off communication applies to the
current session only. When you re-launch the EnerVista software,
communication is on by default.
Drawing Tools
Draw multiple joined lines. Click and drag for each line. Double-click to finish.
Draw multiple, closed curves. Click for each line. Double-click to finish.
Add text box with rectangle around it. Click to add. Double-click it to change text.
4
Add figure. Select file in the window that opens, then click on diagram canvas to add figure.
Add note icon and text. Click to add. Double-click to edit the title and text.
I/O Tokens
These are parts used in FlexLogic equations. They are the inputs and outputs of the Virtual Output equations. The display
can vary from that shown here.
Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and
cannot be used simultaneously.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously.
FlexAnalog symbol that can be used as the input to a FlexElement or use the FlexAnalog symbol to monitor an actual
value when in logic Monitoring mode
Contact Input Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Input
Contact Output Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Output.
The Operate and Seal-In settings can be configured graphically.
The Non-Volatile Latch is similar to the Input symbol but is restricted to the operands associated with a Non-Volatile
Latch. The Set and Reset settings can be configured graphically.
The final output of an equation is a numbered register called a virtual output. Virtual outputs can be used as an input
operand in any equation, including the equation that generates the output, as a seal-in or other type of feedback.
4
Place and configure a Remote Output. The UR's order code and firmware version then determine the availability of the
Remote Output.
Place and configure a Direct Output. The UR's order code and firmware version then determine the availability of the
Direct Output to another UR device.
Place and configure a Teleprotection Output. The UR's order code and firmware version then determine the availability
of the Teleprotection Output.
Place a User Programmable LED in the Logic Designer diagram. Not applicable when using a graphical front panel.
A Tag Out can be used in 1 of 2 ways. The first use of the Tag Out is to break up logic that needs to span several sheets.
The second use of the Tag Out is to associate a frequently used block of code with the Tag Out and then repeatedly use
the same block of code using a Tag In. When a Tag Out is referenced more than once, the Tag Out is replaced with a
Virtual Output during the compile phase.
Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram.
Boolean Tokens
These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations.
The display can vary from that shown here.
Place an OR gate in the Logic Designer diagram. Only one action needs to occur. Any function input on the left side
satisfies the condition.
The number of inputs is configurable from two to 16.
Place an AND gate in the Logic Designer diagram. Multiple actions need to occur. All functions input on the left side are
required to satisfy the condition.
The number of inputs is configurable from two to 16.
Place a NOR gate in the Logic Designer diagram. Gives the value of one when all input operands have a value of zero
and otherwise gives a value of zero. It gives an output signal when there are no input signals. An inverter that reverses
the logic state.
The number of inputs is configurable from two to 16.
Place a NAND gate in the Logic Designer diagram. Gives the value of zero when all input operands have a value of one
and otherwise gives a value of one. It gives an output signal until all signals are present on its inputs. An inverter that
reverses the logic state.
The number of inputs is configurable from two to 16.
Place a XOR gate in the Logic Designer diagram, which is two exclusive OR gates. Only one action needs to occur. If
there are two inputs or there is no input, there is no output.
Place a NOT gate in the Logic Designer diagram. Gives the value of one when the input operand has a value of zero and
4 otherwise gives a value of zero. It gives an output signal when there is no input signal. An inverter that reverses the
logic state.
Place a latch in the Logic Designer diagram. A latch has two inputs and one output. One input is the Set input, and
other input is the Reset input.
Place a positive one shot symbol that responds to a positive going edge in the Logic Designer diagram. A "one shot" is a
single input gate that generates a pulse ins response to an edge on the input.
Place a negative one shot symbol that responds to a negative going edge in the Logic Designer diagram
Place a positive one shot and a negative one shot symbol in the Logic Designer diagram
Elements
These blocks configure properties of the element or use element operands as input to FlexLogic equations.
Place and configure a FlexElement. A FlexElement is a universal comparator used to monitor any analog actual value
calculated by the relay or a net difference of any two analog actual values of the same type.
Place and configure a Selector Switch element. Firmware version determines feature availability. The Selector Switch
element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic. The element provides for two control inputs.
Place and configure a Digital Element. A Digital Element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state.
Place and configure a Digital Counter element. A Digital Counter counts the number of state transitions
from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element.
4
Select Select components. Click one component and hold down the CTRL key to select others.
Or click and drag an area that contains multiple components to select.
Edit Vertices Shows vertices points for the component selected (if the component support vertices
manipulation)
Properties Shows the properties of the selected component
Zoom Normal Zoom in and center the screen to the spot selected
Zoom to Fit Zoom in to a magnitude that fits your entire schema layout on your entire screen
Pan Move the viewable area of your screen around the schema. To activate, select this tool
and then place the hand icon over and part of your schema. Click and drag the hand in
a direction to move around the schema.
Align Top, Middle, Bottom Align the selected components to the top, middle, or bottom of the reference
component
Align Left, Center, Right Align the selected components to the left, middle, or right of the reference component
Space Across Evenly space the selected components across a horizontal axis, starting from the far
left component and ending at the far right component
Space Down Evenly space the selected components across a vertical axis, starting from the top
component and ending at the bottom component
Same Width Set the width of the selected components to the same width as the reference
component
Same Height Set the height of the selected components to the same height as the reference
component
Same Size Set the width and height of the selected components to the same width and height of
the reference component
Only basic objects (lines, rectangles, ellipses) can be rotated and flipped.
Only objects from the Drawing Toolbar can be structured (grouped, ungrouped, forward, backward).
Nudge Up, Down, Left, Right Moves selected component one pixel upward, downward, left, right
Rotate Rotates selected component freely. Once selected, put your mouse cursor over the
component and move the component clockwise or counter-clockwise depending on
what you need.
Rotate Left, Right Rotates selected component 90 degrees counter-clockwise or clockwise
Group, Ungroup Combines all selected components into one combined entity. Ungroups them into
separate components.
Front, Back Moves current components to the absolute front or back of all viewable layers
Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy
Chapter 5: Settings
Settings
This chapter outlines front panel and/or software settings. The relay is not taken out of service when saving settings; the
relay is taken out of service when a settings file is written to it.
Settings can be viewed remotely in a web browser by entering the IP address of the relay, accessing the Device
Information Menu option, then the Front-Panel Display Report option.
When indicated that a restart is required for a setting change to take effect, use the Maintenance > Reboot Relay
Command in the software.
Settings file conversion from previous firmware versions is supported. See the Maintenance chapter.
5 FLEXCURVES
See page 5-132
SETTING GROUP 2
SETTING GROUP 3
SETTING GROUP 4
SETTING GROUP 5
SETTING GROUP 6
FORCE CONTACT
INPUTS
See page 5-205 5
FORCE CONTACT See page 5-206
OUTPUTS
5.2 Overview
5.2.1 Introduction to elements
For URs, the term element is used to describe a feature that is based around a comparator. The comparator is provided
with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to determine if the input is
within the defined range that sets the output to logic 1, also referred to as setting the flag. A single comparator can make
multiple tests and provide multiple outputs. For example, the time overcurrent comparator sets a pickup flag when the
current input is above the setting and sets an operate flag when the input current has been at a level above the pickup
setting for the time specified by the time-current curve settings. All comparators use analog actual values as the input.
An exception to this rule is digital elements, which use logic states as inputs.
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on a logic diagram. This includes the inputs, settings, fixed logic, and the
output operands generated. The previous chapter explains how to read a logic diagram, and the abbreviations used in a
diagram are defined in the Abbreviations chapter.
Some settings are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
Where the current source is from a single current transformer (CT), the base quantity is the nominal secondary or primary
current of the CT. Use the secondary current base to convert per-unit settings to/from a secondary current value, and use
the primary current base to convert to/from a primary current value.
For voltage elements, the primary base quantity is the nominal phase-to-phase primary voltage of the protected system
provided that the VT ratio setting is set to the nominal ratio of the VTs and the secondary voltage setting is set to the
phase-to-phase voltage seen by the relay when the voltage of the protected system in nominal. The UR uses the
convention that nominal voltages in a three-phase system are phase-to-phase voltages.
For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta-
connected VTs, the secondary base quantity and secondary voltage setting is:
Eq. 5-1
For wye-connected VTs, the primary and secondary base quantities are as before, but the secondary voltage setting (here
a phase-to-ground value) is:
Eq. 5-2
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This can happen when the element is in the operate state if the reset delay time is not zero.
Not every operand of a given element in a UR relay generates events, only the major output operands. Elements,
asserting output per phase, log operating phase output only, without asserting the common three-phase operand
event.
The setting acts as a B90 master switch enabling certain relay elements. The features displayed vary with the selection of
"Protection" or "Logic." All features dependent on AC inputs (such as system setup, bus differential, instantaneous
overcurrent, time overcurrent, end fault protection, CT Trouble, AC metering, and undervoltage) become available if the
B90 FUNCTION is set to “Protection.” Features that are not dependent on AC signals (such as logic part of the Breaker Failure
protection or Isolator Monitoring) become available if the B90 FUNCTION is set to “Logic.”
Typically, three IEDs in the B90 system have hardware configured to support AC inputs (set B90 FUNCTION to “Protection”),
while the fourth IED is configured to support all required input contacts and is intended for isolator monitoring and other
logic functions (set B90 FUNCTION to “Logic”).
The B90 FUNCTION setting allows the user to work with a single setting file, program all required functions (both protection
and logic), download the same file to all the B90 IEDs, and modify the settings accordingly to finalize the application. This
5
means that some modules, for example CT/VT module when set to "Logic," can become unusable. Communications and
B90 FUNCTION settings are typically modified when downloading the common B90 setting file.
If hardware modules do not match the B90 order code, the minor self-test error "Discrepancy between order code and
h/w" displays. The B90 remains in service, and features are available as per detected hardware. If, for example, the B90
order code assumes 24 feeder configuration, but there are two DSP modules with 16 CT inputs, the B90 configuration
allows 16 current terminals in the SETTINGS SYSTEM SETUP AC INPUTS CURRENT TERMINAL F1(S8) menu.
5.3.2 Security
Lost password
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1. Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2. Enter the reset code on the front panel, under COMMANDS RELAY MAINTENANCE SERVICE COMMAND.
3. Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
• Password is case-sensitive
• Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
• Password must be 8 to 20 characters in length
• Password must contain characters from all of the following categories:
– English uppercase characters (A through Z)
– English lowercase characters (a through z)
– Base 10 digits (0 through 9)
– Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
5 CHANGE REMOTE
PASSWORDS
See page 5-8
A command or setting write operation is required to update the state of the remote and local security operands
listed.
When a setting password or command password is set or updated, user access with a graphical front panel is
5
removed. Simply log in again on the graphical front panel.
When the setting password is set or updated, the graphical front panel Access Level displays as Command. This is
because the graphical front panel is a Modbus client and it does not have automatic access to the password
change.
PASSWORD ACCESS EVENTS — This setting allows recording of password access events in the event recorder.
As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a CHANGE COMMAND PASSWORD or CHANGE
SETTING PASSWORD setting is programmed to “Yes” via the front panel interface, the following message sequence is
invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the “Restricted” level according to the
access level timeout setting values and when power is cycled.
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
If a remote connection is established, local passcodes are not visible.
5 5. Click the OK button. The password is checked to ensure that it meets requirements.
If you establish a local (serial) connection to the relay, you cannot view remote passcodes.
Access supervision
SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION
ACCESS ACCESS LEVEL See below
SUPERVISION TIMEOUTS
INVALID ATTEMPTS BEFORE LOCKOUT — This setting specifies the number of times that an incorrect password can be entered
within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or REMOTE ACCESS
DENIED FlexLogic operands are set to “On.” These operands are returned to the “Off” state upon expiration of the lockout.
PASSWORD LOCKOUT DURATION — This setting specifies the time that the B90 locks out password access after the number
of invalid password entries specified by the INVALID ATTEMPTS BEFORE LOCKOUT setting has occurred.
The B90 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a
password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS CLEAR RECORDS RESET UNAUTHORIZED ALARMS
command. Therefore, to apply this feature with security, password-protect the Command level. The operand does not
generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed with
event logs or targets enabled.
The following table outlines access level timeout settings.
SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS
ACCESS LEVEL COMMAND LEVEL ACCESS Range: 5 to 480 minutes in steps of 1
TIMEOUTS TIMEOUT: 5 min
These settings allow the user to specify the length of inactivity required before returning to the Restricted access level.
Note that the access level is set to Restricted when control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to 5
return to Restricted access from the Command password level.
SETTING LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to return
to Restricted access from the Command password level.
This feature provides a mechanism to prevent unauthorized or unintended upload of settings to a relay through the local
or remote interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH — This setting is used for local (front panel or RS232 interface) setting access supervision. Valid
values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On,“ then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (on) prior to providing the local
setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message displays on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• REMOTE SETTING AUTH — This setting is used for remote (Ethernet or RS485 interface) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required. If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to
providing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• ACCESS AUTH TIMEOUT — This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On.” The state of the FlexLogic operand
is monitored continuously for an off-to-on transition. When this occurs, local access is permitted and the timer
programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the
timeout is restarted. The status of this timer updates every five seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorized setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required.
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
The Access Authorized Timeout setting represents the timeout delay remote setting access. It applies when the Remote
Settings Authorized setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the Access Authorized Timeout setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
2. Enable the Enable Security check box in the lower-left corner to enable the security management system.
3. Click the Ok button.
If you force password entry by using this feature, ensure that you know the Administrator password. If you do not
know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR
5
device. When using CyberSentry, the default password is "ChangeMe1#".
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.
3. Select the user access rights by enabling the check box of one or more fields.
3. Modify the user access rights by enabling or disabling one or more of the check boxes.
This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details.
The EnerVista software provides the means to configure and authenticate the B90 access using either a server or the
device. Access to functions depends on user role.
The login screen of EnerVista has two options for access to the B90, these being Server and Device authentication.
When the "Server" Authentication Type is selected, the B90 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the B90 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or
Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords
are stored on the B90 device. In this case, access is not user-attributable. In cases where user-attributable access is
required, especially for auditable processes for compliance reasons, use server authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.
Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features are
5 open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found open.
When CyberSentry is enabled, Modbus communications over Ethernet is encrypted, which is not always tolerated by
SCADA systems. The UR has a bypass access feature for such situations, which allows unencrypted Modbus over Ethernet.
The Bypass Access setting is available on the SETTINGS PRODUCT SETUP SECURITY SUPERVISORY screen. Note that
other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA
systems when CyberSentry is enabled.
When using the rear RS485 port and CyberSentry, registers can be read with a maximum buffer of 64 bytes. Settings may
not be written, so use another port or configure the SERIAL INACTIVITY TIMEOUT setting to a high value, such as eight
minutes, to give the relay enough time to finish the task.
For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
Figure 5-3: Supervisory panel
5
LOGIN — This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
outlined here. For the Supervisor role, enable the “Supervisor Role” setting. Log out by right-clicking the device in EnerVista
and selecting the Disconnect option.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password. There are no time-outs for the
Administrator, Engineer, Operator, and Supervisor when logged in using the front panel; log out manually or use the
Command > Security commands in the software.
The roles are defined as follows:
• Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
• Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
• Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
5 •
exist offline.
Supervisor — This is only an approving role. This role’s authentication commits setting changes submitted by
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
• Observer — This role has read-only access to all B90 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel. When local authentication is used, no password is required for
this role. When RADIUS server authentication is used, a password is required.
The Factory service role is not available. It is for factory use only.
The Local Access Denied message on the front panel can mean that you need to log in to the UR in order to
complete the action.
The menu is shown on the front panel upon successful login of the Administrator role.
The LOGIN setting in this menu is similar to that described in SETTINGS > PRODUCT SETUP > SECURITY except for the factory
role.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
SESSION SESSION LOCKOUT: Range: 0 to 99
SETTINGS 3
SESSION LOCKOUT — This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD — This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS
5
RESTORE DEFAULTS LOAD FACTORY Range: Yes, No
DEFAULTS: No
LOAD FACTORY DEFAULTS — This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
SUPERVISORY DEVICE Range: Yes, No
AUTHENTICATION: Yes
The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
DEVICE AUTHENTICATION — This setting is enabled by default, meaning "Yes" is selected. When enabled, Device
authentication with roles is enabled. When this setting is disabled, the UR only authenticates to the AAA server (RADIUS).
However, the Administrator and Supervisor (when enabled) remain active even after device authentication is disabled and
their only permission is to re-enable Device authentication. To re-enable Device authentication, the Supervisor unlocks the
device for settings changes, then the Administrator re-enables device authentication.
BYPASS ACCESS — The bypass security feature provides an easier access, with no authentication and encryption for those
special situations when this is considered safe. Only the Supervisor, or the Administrator when the Supervisor role is
disabled, can enable this feature.
Mode Front panel or serial (RS232, RS485) Ethernet
Normal mode Authentication — Role Based Access Control (RBAC) Authentication — RBAC and passwords encrypted
and passwords in clear SSH tunneling
Bypass access mode No passwords for allowed RBAC levels No passwords for allowed RBAC levels
No SSH tunneling
Self-tests
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS
SELF TESTS FAILED See below
AUTHENTICATE
FAILED AUTHENTICATE — If this setting is Enabled then the number of failed authentications is compared with the Session
Lockout threshold. When the Session Lockout threshold is exceeded, this minor alarm indication comes up.
FIRMWARE LOCK — If this setting is Enabled, then any firmware upgrade operation attempt when the Lock Relay setting is
enabled brings up this self test alarm.
SETTINGS LOCK — If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS FAILED AUTHENTICATE
FAILED FAILED AUTHENTICATE: Range: Enabled, Disabled
AUTHENTICATE Enabled
CyberSentry setup
When first using CyberSentry security, use the following procedure for setup.
1. Log in to the relay as Administrator by using the VALUE keys on the front panel to enter the default password
"ChangeMe1#". Note that the Lock Relay setting needs to be disabled in the Security > Supervisory menu. When this
setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None. 5
5. Next, Device or Server authentication can be chosen on the login screen, but the choice is available only in EnerVista.
Use Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only Device authentication is supported. When Server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the
EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server at the end of
this instruction manual gives an example of how to set up a simple RADIUS server. Once both the RADIUS server and
the parameters for connecting the UR to the server have been configured, you can choose Server authentication on
the login screen of EnerVista.
The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at a time, for both login by front
panel and software.
To configure Server authentication:
1. In the EnerVista software, choose Device authentication and log in as Administrator.
2. Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3. On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4. In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
When changing settings offline, ensure that only settings permitted by the role that performs the
settings download are changed because only those changes are applied.
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the RESET button, which resets targets, where targets are errors
displayed on the front panel or the Targets panel of the EnerVista software. The RESET button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1. Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Security log Event Number Date & Username IP address Role Activity Value
Timestamp
Enumeration Role
0 None
1 Administrator
2 Supervisor
3 Engineer
4 Operator
5 Factory
Enumeration Description
1 Authentication Failed
2 User Lockout
3 FW Upgrade
4 FW Lock
5 Settings Lock
6 Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7 Clear Oscillography command
8 Clear Data Logger command (not applicable to all UR products)
9 Clear Demand Records command (not applicable to all UR products)
10 Clear Energy command (not applicable to all UR products)
11 Clear Unauthorized Access command
12 Clear Teleprotection Counters command (not applicable to all UR products)
13 Clear All Relay Records command
14 Role Log in
Enumeration Description
15 Role Log off
In addition to supporting syslog, a B90 with CyberSentry also saves the security events in two local security files, these
being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in
the EnerVista software under Maintenance > Retrieve File. Depending on the level of criticality/severity, a syslog server or
a reporting tool gathering information from a syslog server can produce reports, charts, and so on. All severity levels are
per RFC 5424.
Table 5-6: CyberSentry system events recorded
Event Severity Description
FAILED_AUTH, ORIGIN, TIMESTAMP Notice (5) A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN, TIMESTAMP Warning (4) An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN, Information (6) Indicates that a change of firmware has occurred
TIMESTAMP
FIRMWARE_LOCK, ORIGIN, Warning (4) An attempt was made to change firmware while the firmware lock was
TIMESTAMP enabled
SETTING_CHG, ORIGIN, TIMESTAMP Notice (5) Indicates setting change(s)
SETTING_LOCK, ORIGIN, TIMESTAMP Warning (4) An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY Notice (5) Clear oscillography command was issued
CLEAR_DATA_LOGGER
CLEAR_DEMAND_RECS
Notice (5)
Notice (5)
Clear data logger command was issued
Clear demand records command was issued
5
CLEAR_ENERGY Notice (5) Clear energy command was issued
RESET_UNAUTH_ACCESS Notice (5) Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT Notice (5) Clear teleprotection counters command was issued
CLEAR_ALL_RECS Notice (5) Clear all records command was issued
WRITE_SETTING_FILE Notice (5) Write settings file to the relay
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE — This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are in
English.
For Japanese and Chinese, up to 10 characters can be input in a field on the graphical front panel, not 20.
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always
second, and Language is always first.
If the language is changed after entering user-configured names, such as relay names, the strings are not translated. For
example, a relay name is entered in English, the language is changed to Japanese, and the relay name remains in English.
Set the language before changing settings.
The language can be selected also for the front panel in EnerVista under Maintenance > Change Front Panel.
The language of the EnerVista software can be changed under View > Language. Languages supported by the operating
system display; that is for Polish or Japanese to display, the software needs to be installed on a Polish or Japanese
operating system.
FLASH MESSAGE TIME — Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT — If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
5 during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY — To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME — These settings are only visible if the B90 has a liquid crystal display
(LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL — This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The B90 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the CURRENT CUT-OFF LEVEL setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL — This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The B90
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as valid
measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for CURRENT
CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
The graphical front panel is a hardware option. See the Order Codes section in chapter 2 for details.
Use the EnerVista software to configure the graphical front panel. The settings are not accessible from the graphical front
panel.
The following screens are available:
• Home page
• Rolling mode
• Metering editor
• Single-line diagram editor
• Annunciator editor
• Configurable navigation
The settings menu itself and the event record pages are not configurable.
Multiple screens can be opened in the EnerVista software, but the first remains active and the others can be read-only. For
example, the Annunciator Editor and Single Line Diagram Editor can be open and active, then subsequently opened Rolling
Mode and Home Page screens are read-only. Close the windows, then re-open the one required.
859850A1.cdr
Time Format
Range: hh:mm:ss, h:mm:ss tt
Default: hh:mm:ss
This setting specifies the format for time on the graphical front panel. It applies to the page header and everywhere else
a time displays on the panel. When the Date Format and the Time Format use the defaults, the date and time are
separated by the character "T" per the ISO convention, such as "2017-09-24T10:58:31". Otherwise the date and time are
separated by a space. If the relay is synchronized to an external time source via PTP, IRIG-B, SNTP, and so on, the date/
time is shown in white, and otherwise in yellow.
hh — two-digit hour, for example 02 for two o’clock
h — one or two-digit hour, for example 2 for two o’clock
mm — two-digit minute, for example 51 minutes
ss — two-digit second (can have a decimal and further digits appended), for example 16 seconds
tt — AM or PM based on 12 hour clock
If microseconds have to be displayed, for example, in the event records, the 24-hour clock is adopted. The representation
of an accumulated period (for example hh:mm) is not affected by the selected time format.
To set the date and time, access Synchronize Devices in the software or synchronize to a time source using Settings >
Product Setup > Real Time Clock.
For a phasor diagram, configure the source under Settings > System Setup > Signal Sources. The diagram is then
viewable by pushing the Metering Tab pushbutton on the graphical front panel. The Metering Editor is not used for these
phasor diagrams.
The figures show setup and table preview.
The Cells configured are not retained when using the Convert Device Settings function, for example when converting a
file in the Offline Window from version 7.6 to 7.7.
Figure 5-7: Metering Editor window
STATUS INPUTS 1 to 16
Range: OFF, ON, any FlexLogic operand
Default: OFF
This setting identifies the potential inputs for use in the STATUS INDEX fields, for display of the status of FlexLogic
operands.
A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
Select the metering input from the drop-down list. The options reflect the FlexLogic operands applicable to the B90. They
are inputs for all five metering pages, not just the current page.
CURRENT PAGE
Range: Page 1...Page 5
Default: Page 1
Select the metering page to configure from the drop-down list. There are five pages possible, viewable with the Tab
pushbuttons on the graphical front panel.
PAGE NAME
Range: Page 1...Page 5
Default: Page 1
Up to 20 characters can be input here as the name of each metering page. The name displays for the Tab pushbutton on
the graphical front panel.
LAYOUT
Range: 3x4, 4x6, 6x8, 6x4, 8x6, 12x8, 12x4, 16x6, 18x8
Default: 6x4
This setting determines how many rows and columns display on the graphical front panel with the metering information.
5 The configurable rows in the settings window change dynamically based on this setting.
CONTENT
Range: Actual, Status, Text
Default: Text
Select the type of content to display.
– Actual — an actual value/data. The Configure button becomes active for the actual value to be selected.
– Status — one of the operands selected from the STATUS INPUTS fields. Select it in the STATUS INDEX field.
– Text — indicates that text is to display instead of a metered value
STATUS INDEX
Range: 1...16
Default:
This field becomes active when the CONTENT field is set to Status. It selects the input from the STATUS INPUTS to display
the on/off status of the selected operand.
A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel. This field is active when the CONTENT field is set to Text or Status.
When Status is selected, the text displays when the status input is in the "on" state.
OFF TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel when the element being monitored is in an off/closed state. This
field is active when the CONTENT field is set to Status. The text displays when the status input is in the "off" state.
FONT
Range: 16, 18, 20
Default: 16
Set the font size to display on the graphical front panel.
TEXT COLOR
Range: 24-bit color selector
Default: Black
Set the text color to display in the specified cell.
BACK COLOR
Range: 24-bit color selector
Default: Grey
Set the background color to display in the specified cell.
ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual." The window specifies the metering
data to display.
Figure 5-9: Metering value properties window
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the metering window. A
FlexAnalog is an analog parameter.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
Reset
Range: ON, OFF, any FlexLogic operand
Default: OFF
This setting selects a FlexLogic operand that when activated acknowledges/resets all annunciator windows in the
graphical front panel. For example, to have the first user pushbutton resets all alarms, set this to PUSHBUTTON 1 ON and
turn on the pushbutton under Settings > Product Setup > User-Programmable Pushbuttons. This setting is the same
as the one defined in Settings > Inputs/Outputs > Resetting > Reset Annunciator. See the Resetting section later in this
chapter.
LAYOUT
Range: 3x4, 4x6, 6x8
Default: 3x4
Selects the number of rows and columns to display on the annunciator pages. For example, 3x4 means 12 windows
display per page over eight pages. Up to 96 entries are possible.
To view the layout, click the Preview button.
PAGE NAMES
Range: up to 20 alphanumeric characters
Default: Page 1...Page 8
Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout.
The name displays for the Tab pushbutton on the graphical front panel.
PARAMETER
Range: Indicator 1...Indicator 96
Default: Indicator 1...Indicator 96
Read-only field. Up to 96 windows are possible.
CONTENT
Range: Actual, Alarm, Mixed
Default: Alarm
Select if the cell is to be an alarm, an actual value, or a combination thereof, for example consists of a single metered
value (set to “Actual”), contains a single alarm indication (set to “Alarm”), or contains both a metered value and an alarm
indication (set to “Mixed”).
ALARM INPUT
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select a trigger for the alarm, or the input signal connected to the alarm. For example, when set to "FIRST ETHERNET
FAIL" and the Ethernet cable connected to port 1 is removed, the alarm is triggered. (Note that when the Ethernet cable
is inserted into an SFP connector and the SFP connector is removed, the alarm is not triggered.) The field is read-only for
an actual value.
The selectable options are the FlexLogic operands specific to the product.
ALARM TYPE
Range: Acknowledgeable, Self Reset, Latched
Default: Acknowledgeable
Set the alarm type. The field is read-only for an actual value.
5 Acknowledgeable — Follow the state transitions, as outlined in the Annunciator section of the Interfaces chapter. The
alarm blinks until acknowledged, then remains on until the condition clears.
Self Reset — Track the state of the input operand. The alarm turns on when the trigger activates and off when the trigger
clears.
Latched — Alarm is on until acknowledged/reset individually or until the RESET button is pressed.
To acknowledge/reset/unlatch an alarm, use the arrow buttons on the graphical front panel and press the ENTER
button.
TEXT (LINE 1 to 3)
Range: up to 10 alphanumeric characters
Default:
The text that displays in the annunciator cell. Three lines can be displayed. Note that a specified metering value replaces
the text for the selected line. This means that a line can display text or be set to show an actual metered value. If the text
does not display it is because an actual metered value is over-riding it; change the line for the text or for the actual value.
TEXT COLOR
Range: 24-bit color selector
Default: White
The color to display for the three text or actual value lines specified.
BACK COLOR
Range: 24-bit color selector
Default: Red
The background color to display for any triggered cell, for example when an alarm is triggered.
ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual" or "Mixed." The window specifies the
metering data to display.
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the annunciator alarm.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed analog value. It can be used to provide for leading 5
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed analog value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
Display in Line
Range: 1, 2, 3
Default: 1
This setting specifies the line in the annunciator alarm window to display the metered value. The actual value replaces
the text for the selected line. For example, 2 means the value displays in line 2 of the text; any text configured to display
in that line does not display.
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure operation to work, these functions also
have been enabled under Settings > Product Setup > User-Programmable Self Tests.
Figure 5-11: Configurable navigation editor
To use the feature, select a CONDITION, select an ACTIVATE PAGE, then save.
CONDITION
5.3.6.1 Menu
SETTINGS PRODUCT SETUP COMMUNICATIONS
COMMUNICATIONS SERIAL PORTS See page 5-38
RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
RATE: 19200 28800, 33600, 38400, 57600, 115200 bit/s
The front RS232 port applies to enhanced and basic front panels.
RS232 BAUD RATE, RS485 COM2 BAUD RATE, and PARITY — The B90 is equipped with two independent serial communication
5 ports. The front panel RS232 port (USB port with graphical front panel) is intended for local use. The rear COM2 port is
RS485 and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software, for example to download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME — This setting specifies the minimum time before the rear RS485 port transmits after
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Public Network
SCADA
EnerVista Software
LAN1 5
ML3000
P1
IP1/ P2 P3
MAC1
UR
859708A2.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN2
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP2/
MAC1 MAC2 MAC2
Redundancy mode
UR
859709A4.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN3
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP3/
MAC1 MAC2 MAC3
UR
859710A2.vsd
5.3.6.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
Follow the IP and subnet mask rules outlined in the Set IP Address in UR section of the Installation chapter.
To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating
information, such as the serial number and order code of your device.
SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3)
NETWORK PORT 1 PRT1 IP ADDRESS: Range: standard IPV4 address format
127.0.0.1
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
Use the front panel to change these settings. When online, the EnerVista software can be used to enable/disable each port
only. In the Offline Window area, all settings can be changed except port 2 redundancy (depending on firmware version).
When using GOOSE, in failover or PRP mode, port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP
elements has no meaning, as ports 2 and 3 use the port 2 MAC address, IP address, and mask.
PRT1 (2 or 3) IP ADDRESS — This setting sets the port’s IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) SUBNET MASK — This setting sets the port’s IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) FUNCTION — This setting enable/disables network communication on the respective port. When the port
function is Disabled, the network traffic on this port is disabled. The PRT2 redundancy setting has no effect on this
functionality. The change takes effect upon relay restart.
If you disable a port here that is used to communicate between the relay and the software, this can take down all
communication between the two. For example, an Ethernet connection set to the IP address of the relay can be disabled
and cannot be reached, even when pinging. The port needs to be re-enabled, IP and any gateway addresses need to be
checked, and the relay needs to be set to Programmed.
PRT2 REDUNDANCY — Determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was
purchased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the options are None and
Failover. In non-redundant mode (REDUNDANCY set to None), ports 2 and 3 operate independently with their own MAC, IP,
and mask addresses. If REDUNDANCY is set to Failover, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are hidden
• Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the
Multilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect,
acting as a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the
switch is good and that communication is healthy for five minutes, then switching back to port 2 is performed. The
delay in switching back ensures that rebooted switching devices connected to the B90, which signal their ports as
active prior to being completely functional, have time to completely initialize themselves and become active. Once
port 2 is active again, port 3 returns to standby mode.
If REDUNDANCY is set to PRP, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
• Port 2 MCST ADDRESS field is visible
• The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still
5 synchronizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case
for PRP networks, the port with the better connectivity is used.
Behavior for GOOSE messages is as follows:
• If REDUNDANCY is set to Failover or PRP, In order to transmit a GOOSE message on port 2, the CID file must be
configured to have the corresponding GSE element in both ConnectedAPs S2 and S3. In the EnerVista software, the
TxGOOSE PORT ASSIGNMENT needs to be "Ports-1,2,3" to transmit GOOSE on both ports 1 and 2, or "Ports-2,3" to have
GOOSE only on port 2, with failover/ PRP.
• If REDUNDANCY is set to PRP, the port 2 configured GOOSE message is simultaneously transmitted on ports 2 and 3
• If REDUNDANCY is set to failover and the port 2 link fails, then only the port 2 configured GOOSE message is transmitted
on port 3
The two ports must be connected to completely independent LANs with no single point of failure, such as common
power supplies that feed switches on both LANs.
For any changes to this setting to take effect, restart the unit.
PRT2 PRP MCST ADDR — This setting allows the user to change the multicast address used by the PRP supervision frames.
This setting is available if REDUNDANCY is set to PRP. All devices in the same PRP network need to have the same multicast
address. Choose an address that does not conflict with another multicast protocol.
When the local receiver again detects a signal, the local transmitter automatically returns to normal operation.
If a Far-End Fault pattern is received by a fiber interface that supports the Far-End Fault feature and it is enabled, it reacts
by dropping the link as if there were no signal at all.
If the receiving interface does not support the Far-End Fault feature or has it disabled, an incoming Far-End Fault pattern is
ignored.
It is strongly recommended to have switches used for substation automation that support the Far-End Fault feature,
especially when UR 7 redundancy Failover is selected for redundancy.
The B90 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks. It applies to networks based on Ethernet technology (ISO/IEC 8802-3) and is based on the second edition (July
2012) of IEC 62439-3, clause 4.
PRP is designed to provide seamless recovery in case of a single failure in the network, by using a combination of LAN
duplication and frame duplication. Identical frames are sent on two completely independent networks that connect source
and destination. Under normal circumstances both frames reach the destination and one of them is sent up the OSI stack
to the destination application, while the second one is discarded. If an error occurs in one of the networks and traffic is
prevented from flowing on that path, connectivity is provided through the other network to ensure continuous
communication. Take care when designing the two LANs, so that no single point of failure (such as a common power
supply) is encountered, as such scenarios can bring down both LANs simultaneously.
Figure 5-15: Example of parallel redundant network 5
PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the duplicated frames. DANP devices have
an additional module, called a Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions on received frames as to which
one is sent up the OSI stack to the application layer and which one is discarded. LRE is responsible for making PRP
transparent to the higher layers of the stack.
In addition, there is a second type of specialized device used in PRP networks, called RedBox, with the role of connecting
Single Attached Nodes (SANs) to a redundant network.
UR relays implement the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy (HSR)
protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 version. The
revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0. The UR relays
support PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Ports 2 and 3 of the CPU module. Use the previous
section (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Ports 2 and 3) operate in redundant mode.
In this mode, Port 3 uses the MAC, IP address, and mask of Port 2.
IPv4 NETWORK
ROUTE 1
IPv4 NETWORK
ROUTE 6
5 IPv4 NETWORK
ROUTE 1 RT1 DESTINATION:
127.0.0.1
Range: standard IPV4 address format
Configure the network IP and subnet settings before configuring the routing settings.
2. Delete the default route by replacing the default gateway with the default value of 127.0.0.1.
Router1
Public network
.1
Router2
10.1.2.0/24 10.1.3.0/24
10.1.1.0/24
ML3000 ML3000 .1
EnerVista Software
P1 P2 P3
IP1/ IP2/ IP3/
.2 .2 MAC2 MAC3
MAC1
UR
859714A1.vsd
In the figure, the UR connects through the following two Ethernet ports:
• Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
• Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router2. Router2
has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
The behavior before release 7.10 was as follows. When sending packets to EnerVista, the UR noticed that the destination
was not on a connected network and it tried to find a route to destination. Since the default route was the only route it
knew, it used it. Yet EnerVista was on a private network, which was not reachable through Router1. Hence a destination
unreachable message was received from the router.
The configuration starting with release 7.10 is as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY =
10.1.2.1
The behavior since release 7.10 is as follows. There is one added static network route to the destination 10.1.3.0/24, where
a computer running EnerVista is located. This static route uses a different gateway (10.1.2.1) than the default route. This
gateway is the address of Router2, which has knowledge about 10.1.3.0 and is able to route packets coming from the UR
The serial communication ports utilize the Modbus protocol, unless the port is configured for DNP or IEC 60870-5-103
operation. This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave
devices only.
For more information on the protocol, including the memory map table, see the UR Family Communications Guide.
MODBUS SLAVE ADDRESS — When using the Modbus protocol on the RS232 port, the B90 responds regardless of the
MODBUS SLAVE ADDRESS programmed. For the RS485 port, each device on the serial bus must have a unique slave address
from 1 to 254. Address 0 and addresses from 248 and up are reserved by the Modbus protocol specification, and so their
use here is not recommended. Address 0 is the broadcast address to which all Modbus slave devices listen. Addresses do
not have to be sequential, but no two devices can have the same address or conflicts resulting in errors occur. Generally,
starting at 1, set each device added to the link to use the next higher address. When using Modbus TCP/IP, the client must
use the programmed MODBUS SLAVE ADDRESS value in the Unit Identifier field.
MODBUS TCP PORT NUMBER — Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502
is reserved for Modbus communications, and only in exceptional cases when MODBUS TCP PORT NUMBER is set to any other
port. The MODBUS TCP PORT NUMBER setting sets the TCP port used by Modbus on Ethernet. A MODBUS TCP PORT NUMBER of
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the B90 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
5
those protocols.
The PROTOCOL menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
SCADA PROTOCOL — This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
the unit.
MMS CONNECTION TIMEOUT — This setting specifies a time delay for the detection of network TCP connection lost. If there is
no data traffic on the TCP connection for greater than the time specified by this setting, the connection is terminated. This
frees up the connection to be re-used by a client. A setting of 10 seconds disables this timer. The TCP connection then is
managed by a standard TCP KeepAlive message sequence. These messages are transmitted every 20 seconds when there
is no MMS communication between the relay and the client. If there are no responses to the TCP KeepAlive messages, the
connection is closed. For any change to this setting to take effect, restart the unit. The change takes effect for a new
connection. For any existing open connection when the change is made, close and re-open the connection. Cycling power
to the relay also applies the new setting.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the PROTOCOL and DNP CHANNEL 1(2) PORT settings.
5 Channel 1: RS232
Channel 2: RS485
DNP DNP Modbus, IEC 61850
IEC61850 EDITION — Switches between Editions 1 and 2 of the IEC 61850 protocol. Settings default with the change, except
GGIO1, GGIO2, GGIO4, and those for the graphical front panel. A message displays that a reboot is required, which can be
done using Maintenance > Reboot Relay Command.
DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP VOLTAGE SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP POWER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP ENERGY SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP PF SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP OTHER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1 5
DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1
DEADBAND: 30000
The Distributed Network Protocol (DNP) allows for the optimization of control and data acquisition between the equipment
in the substation and the central control center. The protocol is scalable; that is, it is designed to be compatible with the
latest high speed LAN technology yet still be implemented over slower speed serial links.
The DNP improves upon many master-slave protocols by improving overall communication performance requirements
and provides time-stamping with millisecond accuracy.
The B90 supports DNP version 3.0.
DNP is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL setting is set to DNP 3.0. The B90
can be used as a DNP slave device connected to multiple DNP masters (usually an RTU or a SCADA master station). Since
the B90 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively
communicate with the B90 at one time.
DNP is not available using the USB port on the graphical front panel.
See the UR Family Communications Guide for more information on DNP.
The DNP Channels sub-menu is shown.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP CHANNELS
DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
NONE PANEL - RS232, NETWORK - TCP, NETWORK - UDP
DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
5 NONE PANEL - RS232, NETWORK - TCP
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the DNP CHANNEL 1(2) PORT setting is set to “Network - TCP,” the channel 1(2) DNP
protocol can be used over TCP/IP on the Ethernet ports. When this value is set to “Network - UDP,” the DNP protocol can be
used over UDP/IP on channel 1 only. The "Front Panel - RS232" setting does not apply to the graphical front panel; when
selected the DNP client cannot establish a connection on a USB port.
For any change to take effect, restart the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The DNP ADDRESS setting is the DNP slave address. This number identifies the B90 on a DNP communications link. Assign a
unique address to each DNP slave.
The B90 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the B90 can connect. The settings follow.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP NETWORK CLIENT ADDRESSES
DNP NETWORK CLIENT ADDRESS 1: Range: standard IP address
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IP address
0.0.0.0
The DNP TCP/UDP PORT NUMBER setting is for normal DNP operation. To close the port, set the port number to 0. The change
takes effect when the B90 is restarted.
The DNP UNSOL RESPONSE FUNCTION is set to “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the B90 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the B90 retransmits an
unsolicited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP
UNSOL RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which
solicited responses are sent is determined by the B90 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the B90 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000,”
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the B90 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10 times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the B90 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger
unsolicited responses from the B90 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
is set to “15.” Note that these settings are the deadband default values. DNP object 34 points can be used to change
deadband values, from the default, for each individual DNP analog input point. For any change to take effect, restart the
relay. Whenever power is removed and re-applied to the B90, the default deadbands are in effect.
The B90 relay does not support power metering. As such, the DNP POWER SCALE FACTOR and DNP POWER DEFAULT
DEADBAND settings are not applicable.
The B90 relay does not support energy metering. As such, the DNP ENERGY SCALE FACTOR and DNP ENERGY DEFAULT
DEADBAND settings are not applicable.
5
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the B90.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to
be necessary, which provides more robust data transfer over noisy communication channels.
Check the “DNP Points Lists” B90 web page to view the analog inputs and/or binary inputs points lists. This page
can be viewed with a web browser by entering the IP address of the B90 Ethernet port employed to access the B90
Main Menu, then by clicking the Device Information Menu item, then the DNP Points Lists item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings select the DNP default variation
number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation
0 is requested and/or in class 0, 1, 2, or 3 scans. See the DNP Implementation section in the UR Family Communications
Guide.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the B90 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The B90 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED
CONTROL POINTS setting allows configuration of 0 to 32 binary output paired controls. Points not configured as paired
operate on a one-to-one basis.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection is
aborted by the B90. This frees up the connection to be re-used by a client. For any change to take effect, restart the relay.
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS BINARY INPUT / MSP POINTS
BINARY INPUT / MSP Point: 0 Range: FlexLogic operand
POINTS Off
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
5 Changes to the DNP / IEC 60870-5-104 point lists take effect when the B90 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT / MME
POINTS
ANALOG INPUT / MME Point: 0 Range: any FlexAnalog parameter
POINTS Off
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the B90 is restarted.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
The B90 is provided with optional IEC 61850 communications. This feature is specified as a software option at
the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850 or Settings > IEC 61850. The settings are not
accessible from the front panel of the device.
IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing IEC 61850 messaging,
route IEC 61850 traffic on a separate port from SCADA communications, or use redundant, independent ports, and
a high-speed network recovery method, such as PRP.
Overview
IEC 61850 is a series of international standards and technical reports applicable to power utility automation systems. It
includes semantics, abstract communication services, specific communication services, performance specifications,
network engineering guidelines, configuration description methodologies, and engineering processes. The standard
enables interoperability among intelligent electronic devices (IEDs) from different suppliers and interoperability among
software configuration tools from different suppliers. Interoperability in this case is the ability for IEDs to operate on the
same network or communication path sharing information and commands, and for configuration tools to understand
each other's configuration files.
The UR family supports a large subset of IEC 61850 features. These are detailed in the UR Family Communications Guide
and include the information model, GOOSE publish, GOOSE subscribe, buffered report server, unbuffered report server, and
Manufacturing Message Specification (MMS) query, read, write, and control services. In addition, the URs and their
EnerVista UR Setup software support IEC 61850 Substation Configuration Language (SCL) file import/export and merging.
Many settings of UR protection, control, and monitoring elements, that is to say elements that are not concerned with the
IEC 61850 protocol, can nevertheless be accessed via IEC 61850. These settings are documented elsewhere in this Settings
chapter. This section of the Settings chapter deals solely with the settings that configure the IEC 61850 protocol itself.
The maximum number of simultaneous clients supported by the UR family is five. 5
IEC 61850 Editions 1 and 2
This release supports IEC 61850 Edition 1 and Edition 2. The default is Edition 2.
Select IEC 61850 Edition 1 or Edition 2 under Settings > Product Setup > Communications > Protocol. Switching defaults
the IEC 61850 settings, except GGIO1, GGIO2, GGIO4, and those for the graphical front panel. A message displays that a
reboot is required, which can be done using Maintenance > Reboot Relay Command.
Edition 2.0 is used with certain modifications according to IEC/TR 61850-90-5. Only edition 2.0 61850 configuration tools
can interoperate with edition 2.0 devices, such as the UR 7.3x, 7.4x, or 7.6x release. When using Edition 2, the UR release
uses edition 2.0 SCL, which differs from edition 1.0 SCL. GSSE, fixed GOOSE, and fixed report services of Edition 1 are not
supported in Edition 2, and thus UR devices using these features have to be converted to configurable GOOSE to
communicate with a 7.3x, 7.4x, or 7.6x device.
When set to Edition 1
• The Test Flag in the Tx GOOSE message header is set to TRUE when the TEST MODE FUNCTION is set to Forcible or
Isolated
• The test flag in the received GOOSE message header is not validated
• Routable GOOSE is not supported
• The FlexLogic category does not display in the IEC 61850 panels in the EnerVista UR Setup software
• With SCL file import, for Edition 1 the IP address in the ConnectedAP element must match one IP address of the device,
while for Edition 2 one of the three IP addresses in the ConnectedAP element must match
The fields that display in the software depend on the Edition selected and the B90. Differences are noted in the sections
that follow. If required, consult the Model Implementation Conformance Statement (MICS) section of the UR Family
Communications Guide to understand what applies to your setup.
The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the B90.
This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those
that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model
(that is, the "private" section). The UR EnerVista Setup software imports all of these settings into the current session, not just
those in the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the current
session, all other panels for the B90 must be closed before the IEC 61850 panel can be opened, and the software prompts 5
for this when applicable. Panels for other devices can be open concurrently to facilitate parameter coordination.
When CyberSentry security is enabled, editable settings depend on the user role logged in. For example, an Administrator
and Engineer can change settings. If prompted for a "Settings password," it means the Administrator or Engineer
password.
The Restore button restores settings in the window to their last saved values. The Default button reverts settings in the
window to factory default values or Oscillography, Data Logger, or FlexLogic Equation Editor pre-configured values. The
Reset button reverts all IEC 61850 settings to the factory default values, not just the current window. (In other settings
windows, the button reverts settings in the window to factory default values.)
When a setting is enabled, its panel continues to read Disabled until relaunched. There is no polling capability to update
automatically the IEC 61850 readings, so the panel needs to be closed then opened for the correct status to display. Good
practice is to close any panel not in use because changes being made by other users too are reflected only upon relaunch
of the panel.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and for example results in differences shown on a settings
comparison report.
Server configuration
The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting.
IED NAME
Range: 1 to 58 VisibleString characters
Default: TEMPLATE
The value entered sets the IED name used by IEC 61850 for the B90. An IED name unique within the network must be
entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
The first character must be a letter.
The IED NAME and the Product LD inst name comprise the <LDName> for a product. The longest LD inst are "Master"
and "System" at six characters, with Master being fixed and the others configurable with the configurable Logical device
feature. So the IED NAME needs to be restricted to 58 characters to meet a 64 character limit.
Access Point
Range: S1, S2, S3
Default: S1
This setting applies to IEC 61850 Edition 1. It is the subnetwork.
Location
Range: 0 to 255 ASCII characters
Default: Location
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.location. This data attribute is
provided by the protocol to allow the user to declare where the equipment is installed.
Latitude
Range: -90.000 to 90.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.latitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates -latitude. Negative values
indicate a southern latitude. WGS refers to the world geodetic system, which is used in global positioning systems (GPS),
and 84 is the current version of the standard.
Longitude
Range: -180.000 to 180.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.longitude. This data attribute is
provided by the protocol to declare the geographical position of the device in WGS84 coordinates -longitude. Negative
values indicate a western longitude.
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates - altitude.
Prefix for GGIO1
5
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexLogic operand interface logical node GGIO1 that is described in the GGIO1
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO1 prefix
that is used by the product, such as ConIn and ConOut.
Prefix for GGIO2
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the Virtual Inputs Interface logical node GGIO2 that is described in the GGIO2 section
later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must
be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO2 prefix that is used by the
product.
Prefix for GGIO4
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexAnalog operand interface logical node GGIO4 that is described in the GGIO4
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO4 prefix
that is used by the product.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the B90. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting is read only. It specifies the method used to describe GOOSE subscription configuration in SCL. See the UR
Family Communications Guide for details. In the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode. The set value is for the entire EnerVista installation and is
preserved between sessions. To change this global field, click File > Preferences and access the IEC 61850 panel; you do
not need to be connected to the device.
Logical devices
The Logical Devices panel contains IEC 61850 settings relevant to the configurable logical devices feature, wherein logical
device naming can be reconfigured and logical nodes re-assigned.
The path is Settings > Product Setup > Communications > IEC 61850 > Logical Devices.
Figure 5-20: Default IEC 61850 Logical Devices panel with devices middle and nodes right (Edition 2)
• Gen — FlexLogic, Virtual Outputs, non-volatile latches, FlexElements, recording (for example oscillography), security,
front panel, clock
For the Master logical device, the following logical nodes have fixed assignment:
• The LLN0 in the Master logical device, which includes setting group, GOOSE and report control blocks, and datasets
• LPHD1 — Models common issues for physical devices
• GGIO1 — For unmapped FlexLogic operands
• GGIO2 — For Virtual Input control
• GGIO3 — For RxGOOSE Inputs
• GGIO4 — For unmapped FlexAnalog operands
• LGOS logical nodes — For GOOSE subscription
The Logical Devices panel has middle and right panes. The middle pane has a list of the instantiated logical devices in the
sequence that they appear in SCL, with one device selected. The right pane has a list of the logical nodes presently
assigned to the selected logical device in lexicographic order by logical node name.
In the middle pane logical devices are shown with their product-related name, followed in brackets by their function-
related ldName, and followed by the value of their confRev. In the following example, by right-clicking and editing, the
Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the
configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The
next paragraphs explain how to do this setup.
Figure 5-21: Protection logical node selected
Right-clicking a logical device displays the menu that allows insertion of a new logical device immediately below the
selected one, deletion of the selected logical device, or editing the selected logical device's parameters. The insert option is
disabled and greyed-out if there are already 16 logical devices instantiated. The delete option is disabled and greyed-out if
the selected logical device is Master or it contains any logical nodes other than LLN0.
If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device
parameters edit dialog opens.
Figure 5-23: Insert new logical node (Edition 2)
If the edit option is selected for the Master logical device, the Product LD inst name setting is not editable.
When the Ok button is clicked, the entered values for Product LD inst name and Functional ldName are checked for
uniqueness within the UR, and they are updated in the pane.
The settings are explained as follows, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting. When adding or editing a logical device entry, these are the fields that need to be completed.
Functional ldName
Range: 0 to 64 VisibleString characters
Default: empty string
Each logical device has this setting. The value is configurable in all logical devices. Valid characters are upper and
lowercase letters, digits, and the underscore (_) character. If the number of characters entered is greater than zero, the
setting sets the value of the function-related name used in communications. If an ldName is entered, it must form an
LDName that is unique within the network for proper operation. The standard recommends choosing this name
according to IEC 81346-1. If the number of characters entered is zero, no function-related name is defined.
Throughout the remainder of this IEC 61850 section, <LDName> is a syntactic variable representing the present
LDName of the master logical device. In other contexts LDName can refer to some other logical device. Depending
on its context, <LDName> can be a product-related name or a function-related name.
configRev
Range: 0 to 255 ASCII characters
Default:
This data attribute is provided by the protocol to declare changes to the semantic of the data model of the UR. The intent
is that the user changes Master configRev each time that the semantic or data model changes, so that clients can
readily detect the change. A semantic change is a logical node getting a new semantic use; for example, an instance of
logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now used for
another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes, or
instance names.
The scope of Maser configRev is the entire relay configuration, as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
Each logical device has a name: LDName. (Note the upper case LD.) LDName has both a product-related form and
a function-related form as per IEC 61850 6:2009 8.5.3.
SCL files invariably use the product-related form of LDName. The product-related form is the concatenation of the
IED name of the device and the individual logical device's inst name. The IED name is the value of the "IED NAME"
setting on the Server Configuration panel, and the logical device inst names are each the value of the
corresponding "Product LD inst name" setting here. The "Product LD inst name" of the first logical device is fixed at
"Master".
Communications use the function-related form of LDName if a function-related name is defined, otherwise
communications use the product-related name. The function-related name is the value of the corresponding
"Functional ldName" setting if this setting is not empty, if empty the function-related name is not defined.
In SCL, the function-related name is specified by the LDevice element attribute ldName (note the lower case ld).
Absence of this attribute indicates the function-related name is not defined. In SCL the product-related name is
specified by the name attribute of the IED element and the inst attribute of the LDevice element.
In the right pane, logical nodes assigned permanently to the Master logical device and LLN0 in all logical devices are
greyed-out as shown earlier. These are not movable. Any other logical node can be dragged to any of the logical devices in
the middle pane, which causes that logical device to be re-assigned to that logical device. Right-clicking a logical node
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
Figure 5-25: Move logical node (Edition2)
GOOSE
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.
R-GOOSE is available through the IEC 61850 software option. If R-GOOSE security is required, the CyberSentry
software option also must be purchased.
TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. A TxGOOSE is a UR element implementing a single IEC 61850
GOOSE message publishing service. The subscribing function in URs is performed by RxGOOSE elements, as described in
the next section. Each UR with IEC 61850 order code options has 16 TxGOOSE elements. Each TxGOOSE can either use the
original format specified in IEC 61850 8 1:2011 or the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in
IEC TR 61850-90-5:2012. Each TxGOOSE element can publish the values of up to 64 attributes of the IEC 61850 nodes in the
UR.
Published TxGOOSE messages configured in the EnerVista UR Setup software can be subscribed by and the published
operand values understood by other UR devices. Furthermore, they can be subscribed to and understood by any device of
any manufacturer that implements the IEC 61850 edition 1.0 or 2.0 GOOSE subscription mechanism. The messages are
published with a multicast address so that the network sends the messages to all devices; any number of devices that
want to subscribe can.
For wide area protection, control, and monitoring schemes, R-GOOSE wraps the proven original format GOOSE in IP/UDP to
multicast (or unicast) the data over a Wide Area Network (WAN). Sample applications are Wide area Remedial Action
Scheme (RAS) and Under Voltage/ Frequency Load Shedding Schemes (UVLS/UFLS). R GOOSE uses IGMPv3 (Internet Group
Management Protocol version-3, RFC 3376) for multicasting.
The entities whose values are published in GOOSE messages are known as members. The members are itemized in an
ordered list known as a data set. Each TxGOOSE can use any one of the configured data sets. (See the DataSets section
later for details.) The performance of a TxGOOSE is determined by its dataset. Booleans in fast GOOSE datasets are
designed for the TT6 transfer time class (3 ms), while Booleans in the Normal datasets are designed for the TT3 class (100
ms). Due to the significant amount of CPU time required to compose a TT6 TxGOOSE message and the limited amount of
time allowed by the TT6 class, at most four of these can be configured in a given UR. So only four fast GOOSE are allowed
to be configured, and the UR software has a check to disallow the use of more than four fast datasets in GOOSE. If six fast
datasets are configured outside of UR software and the file sent directly to the relay, the relay rejects the file. The design
does allow six fast datasets to be used in report control blocks, which allows fast scanned data in reports.
Each enabled TxGOOSE transmits its message whenever a value change is detected in one or more of its members. If the
changed value is a Boolean in a fast dataset, then the change detect occurs in the TT6 detection time of 3 ms or less. If the
member is an analog value in a fast dataset, the change detect occurs in theTT3 time of 100 ms. In Normal GOOSE
Datasets, change detection for all dataset members occurs in the TT3 time of 100 ms. To guard against the possibility that
such a message is lost in the network before it reaches all subscribers, the message is quickly retransmitted several times.
To allow subscribers to verify that their link to the publisher and the publisher itself are healthy, each message is also
5 retransmitted periodically even while the values are unchanging. These latter messages are known as heartbeat
messages, while the former are known as event messages. Heartbeat messages also provide means for a subscriber
newly online to receive the published values in the absence of an event.
The details of TxGOOSE message construction are contained in the UR Family Communications Guide. Knowledge of these
details is not required to configure GOOSE.
The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause
A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850 edition 1.0
and as optional in IEC 61850 edition 2.0.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the
settings for the first TxGOOSE. The settings and functionality for the others are similar.
5
A data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.
When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottom
right of the window.
TxGOOSE1 MODE
Range for Edition 2: Disabled, GOOSE, R-GOOSE
Range for Edition 1: Disabled, GOOSE
Default: Disabled
When set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are published
in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSE
format according to IEC 61850 90-5, and the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed.
TxGOOSE1 GoCB name
Range: 0 up to 32 VisibleString characters
Default: GoCB01
The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.
An ObjectReference to the control block, which consists of the concatenation of the string "<LDName>/LLN0." and the
control block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
TxGOOSE1 GoID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate
the TxGOOSE1 messages from other GOOSE messages. Special characters are not allowed, such as <, >, &, ’, and ".
TxGOOSE1 DatSet
Range: None, TT6DataSet1,TT6 DataSet2, … TT3DataSet01,TT3 DataSet02, …
Default: None
This setting selects the published data set using the UR Setup software designator for the data set. If None is selected,
no TxGOOSE1 messages are sent.
The IEC 61850 name of the data sets are configured in the Datasets panel, as described later.
Some datasets are designed for the TT6 transfer time class (3 ms), while others are designed for the TT3 class (100 ms).
The performance of a TxGOOSE is determined by its dataset. Use TT6 datasets for trips and blocking applications, TT3
datasets for slow automatic interactions. The 61850 name of the datasets are configured in the Datasets panel.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0." and the data
set name, is published in the datSet field of TxGOOSE1 messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
To configure a DataSet, select it at the top of the window from the drop-down list. In the lower part of the window, drag
and drop configuration items to the right side. Dataset members configured here affect other Report or TxGOOSE
control blocks that use the same DataSet.
5 The performance of the TxGOOSE is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
TxGOOSE1 DST MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the TxGOOSE1 MODE setting is R-GOOSE, the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed. Otherwise, the value entered here sets the Ethernet destination Media Access Control (MAC) address in
published TxGOOSE1 messages. As the standard requires that the address have the multicast bit set TRUE, that is to say
the second digit is set to an odd number, messages transmitted have the multicast bit set TRUE no matter its value in
this setting.
The destination MAC address can be used by the network to restrict message delivery to selected devices that need to
receive them, reducing network load. This address also can be used by hardware in receiving devices to filter out
messages that are of no interest to them, reducing processor burden. Different filtering algorithms are implemented by
different devices. The standard recommends that the algorithm used by hardware of the receiving device be considered
when assigning destination multicast addresses.
Subscribers can use this address to discriminate TxGOOSE1 messages from other GOOSE messages.
TxGOOSE1 VLAN PRIORITY
Range: 0, 1, 2, 3, 4, 5, 6, 7, 5-4, 6-4, 6-5, 7-4, 7-5, 7-6
Default: 4
When the value entered is 0, 1, 2, 3, 4, 5, 6, or 7, the User Priority value in the IEEE 802.1Q VLAN tag included in published
TxGOOSE1 messages is set to that value. When one of the two-digit values is entered, the dynamic priority feature is
selected: the first event message has the User Priority value of the first digit, and User Priority is decremented in each
following message until reaching the value of the second digit. For instance, if the selected value is 7-5, then the User
Priority values in successive messages beginning with the message triggered by an event is 7, 6, 5, 5, 5, 5, 5, and so on.
Do not make a dynamic priority selection when standard behavior is required.
Network devices can forward a message with a higher priority value before a message with a lower priority value, which
speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority
messages, such as GOOSE, have priority values in the range of 4 to 7.
TxGOOSE1 VLAN ID
Range: 0 to 4095 in steps of 1
Default: 0
The value entered sets the VID value in the IEEE 802.1Q VLAN tag included in published TxGOOSE1 messages. VID can be
used by network devices to direct messages to only selected devices, reducing network burden. VID values of 0 and 1
are assigned by IEEE 802.1Q to other functions and are not to be used for GOOSE.
TxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
The value entered sets the APPID value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages.
The standard reserves the value range 0 to 16383 for GOOSE Type 1 (Fast messages), and reserves the value range
32768 to 41151 for GOOSE Type 1A (Trip messages). Some subscribers can process messages in the Type 1A range
faster than messages in the Type 1 range. The standard reserves the default value (0) to indicate lack of configuration.
The standard strongly recommends unique, source-orientated APPIDs within a given system.
TxGOOSE1 CONFREV
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE messages of the expected configuration revision from messages of a different revision. The standard requires
that CONFREV be incremented each time the members or the order of the members published is changed. The standard
states that the value of 0 is reserved.
TxGOOSE1 RETRANS TIME
Range: 0 to 100 ms in steps of 1 ms 5
Default: 4 ms
If the entered time is non-zero, when a member value change is detected, four event transmissions are sent, then
heartbeat transmissions resume. The interval between the first and second event transmissions, and between the
second and third, is the time set here. The interval between the third and the fourth event transmission is double the set
time. If the entered time is zero, only a single event transmission occurs, then heartbeat transmissions resume.
TxGOOSE1 TIME TO LIVE
Range: 1 to 60 s in steps of 1 s
Default: 60 s
The value entered sets the timeAllowedtoLive value in published TxGOOSE1 messages. The standard requires
subscribers to assume a failure has occurred when another TxGOOSE1 message is not received within the published
timeAllowedtoLive time.
Base this setting on the TxGOOSE UPDATE TIME and the tolerable number of contiguous message delivery misses. For
example, if the heartbeat time is 10 s, and missing up to three successive messages is tolerable, make the setting
10 * 3 + 1 = 31 s. The extra second is to ensure that arrival of the third heartbeat transmission beats the
timeAllowedtoLive timer.
In the imported CID file, if the TxGOOSE1 TIME TO LIVE is greater than 60 seconds, clamp the setting value to 60 seconds
and an information log is provided in SCL log.
TxGOOSE1 UPDATE TIME
Range: 1 to 59 s in steps of 1 s
Default: 30 s
This setting specifies the time interval between heartbeat messages, meaning messages that are sent periodically while
no events are detected.
TxGOOSE1 PORT ASSIGNMENT
Range: Disabled, Port-1; Port-2; Port-3; Ports-1,2; Ports-2,3; Ports-1,3; Ports-1,2,3
Default: Ports-1, 2, 3
This setting applies to IEC 61850 Edition 2.
This setting specifies the Ethernet ports for transmission of TxGOOSE1. When set to disabled, TxGOOSE1 messages are
not transmitted on any port no matter the state of GoEna. When set to Port-1, TxGOOSE1 is published over Ethernet
Port-1 only; while selecting Ports-1, 3 option, the same TxGOOSE1 is published to both Ports 1 and 3; and similarly if set
to Ports-1, 2, 3, all ports publish TxGOOSE1.
When setting PRT2 REDUNDANCY to Failover or to PRP, the TxGOOSE 1 port assignment needs to be set to ports 2
and 3 (Ports-2,3).
Also, Port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP elements has no meaning, as ports 2
and 3 use the port 2 MAC address, IP address, and mask.
R-TxGOOSE1 IP CLASS
Range: 0 to 256 in steps of 1
Default: 46
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
selects the IPv4 Differentiated Services Code Point-DSCP (formerly called TypeOfService-TOS) value. This value provides
priority routing, when supported in the routers. The default value is for Expedited Forwarding (101110B, 46 or 2EH).
R-TxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
specifies destination IP address for the R-TXGOOSE1 that is entered in Standard IPV4 address format. The destination IP
5 address needs to be a valid multicast or unicast IP address. The value specified in this setting is mapped to IPv4 header
32 bit field for Destination IP Address while publishing R-GOOSE1.
The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
The source IP address is that of the UR port from which the R-GOOSE messages are transmitted.
R-TxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies level of security (authentication/encryption) used for TxGOOSE1. None specifies no security
mechanisms are to be used. Signature specifies only signature (no encryption) is to be used. SignatureAndEncryption
specifies that both signature and encryption are to be used.
RxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages.
IEC 61850, GOOSE is an efficient method for simultaneous high-speed delivery of the same generic substation event
information by a publishing device to more than one subscribing device. An RxGOOSE is a UR element implementing a
single IEC 61850 GOOSE message subscribing service. The publishing function in URs is performed by TxGOOSE elements,
as described in the previous section.
Each UR with the IEC 61850 order code option has 64 RxGOOSE elements. Each RxGOOSE element can subscribe to GOOSE
messages from a specified publisher. Each RxGOOSE can either use the original format specified in IEC 61850 8 1:2011 or
the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in IEC TR 61850-90-5:2012. Subscribed message
members can be DataObjects, SubDataObjects, DataAttributes or SubAttributes. In E2-2.0 mode members are restricted to
basic types BOOLEAN, FLOAT32, INT32, Dbpos, TimeStamp or Quality. Each subscribed message can contain up to 64
values. A member can be a structure containing several values; note that it is the number of values rather than the number
of members that are limited to 64.
GOOSE messages from any device of any manufacturer that implements the IEC 61850 Edition 1.0 or 2.0 GOOSE publish
service or the 61850-90-5 R-GOOSE service (IEC 61850 Edition 2) can be subscribed to. The UR accepts both the variable
length encoded GOOSE messages specified IEC 61850 8 1:2004 and the Fixed-Length encoded GOOSE messages as
specified in IEC 61850 8 1:2011 clause A.3.
Each enabled RxGOOSE monitors for interruption of the GOOSE messages it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. An RxGOOSE connection is also considered lost after the UR finishes restart until a
message is received. While any RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test is activated.
Messages that contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the
simulation field (test field in edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to
Forcible or Isolated.
RxGOOSE messages can be received through any UR Ethernet port.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages it is to accept. Most of these settings are automatically configured by UR Setup software
when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made as
described in the sections following this. For IEC 61850 Edition 2, settings R-RxGOOSE1 RECEPTION MODE, R-RxGOOSE1
SECURITY, and R-RxGOOSE SRC IP need to be manually completed as the information is not contained in publisher SCL.
Figure 5-27: IEC 61850 RxGOOSE Messages panel (Edition 2)
RxGOOSE1 MODE
Range for Edition 2: GOOSE, R-GOOSE
Range for Edition 1: GOOSE
Default: GOOSE
When set to GOOSE, TxGOOSE1 messages are published in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE,
TxGOOSE1 messages are published in Routable GOOSE format according to IEC 61850 90-5. When set to R-GOOSE, the
R-RxGOOSE DST IP needs to be a valid multicast or unicast IP address.
RxGOOSE1 goID
Range: 0 to 129 VisibleString characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field. Special characters are not allowed, such as <, >, &, ’, and ".
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the RxGOOSE1 MODE setting is R-GOOSE, the value of this setting is not used, the destination Media Access
Control (MAC) address for RxGOOSE1 messages is calculated based on the RxGOOSE DST IP address. Otherwise, set this
setting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this value
are accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
5 If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPID
setting.
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if the logical device containing the publishing control block has "ldName"
configured, otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing
control block.
The B90 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName
setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the
publisher is a UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for
example "GoCB01". If the publisher is a UR 7.40 series device, <GoCBName> is as specified earlier in the TxGOOSE
section of this chapter.
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default: empty string
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting. If the publisher is a UR 7.40
series device, datSet is as specified in the DataSets section of this chapter.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.
R-RxGOOSE1 RECEPTION MODE
Range: SSM, ASM, Unicast
Default: SSM
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE the value of this setting is not used. Otherwise it selects the
R-GOOSE reception mode.
R-RxGOOSE RECEPTION MODE specifies the R-RxGOOSE DST IP range. When set to SSM, R-RxGOOSE DST IP must be in
the range of 232.0.0.1 to 232.255.255.255. When set to ASM, R-RxGOOSE DST IP must be in the range of 224.0.0.1 to
239.255.255.255, excluding the SSM range. Note that the SSM range is inside the ASM range and therefore the ASM use
excludes the SSM range. The default destination IP address 224.0.0.0 is reserved, and hence not a valid multicast IP
address.
The reception modes are related to Layer-3 R-GOOSE reception from routers/WAN. The subscription to multicasting of R-
GOOSE is supported using IGMP Protocol Independent Multicast (PIM). It is made available in either Source Specific
Multicast (SSM) mode or Any Source Multicast (ASM) mode. Unicast (over UDP) mode can also be used. In case of
multicasting (IGMPv3 based SSM or ASM), the R-GOOSE subscriber device requests the Last Hop Router (LHR) to
subscribe to a specific multicasting group.
If the publisher is using a unicast destination IP address for this R-GOOSE, then set R-RxGOOSE1 RECEPTION MODE to 5
Unicast. Otherwise set R-RxGOOSE1 RECEPTION MODE to the SSM or ASM mode used by the local routers/firewalls.
R-RxGOOSE1 SRC IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 127.0.0.1
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. When the RxGOOSE1
MODE setting is R-GOOSE and the R-RxGOOSE RECEPTION MODE setting is ASM, the value of this setting is not used.
Otherwise the Source IP Address field of incoming R-GOOSE messages must exactly match this value for the message to
be accepted as a valid RxGOOSE1 message. Set this setting to the value of the source IP address used by the publisher.
For UR publishers, this value is in setting PRT# IP ADDRESS.
The UR does not validate the address entered. The default IP address 127.0.0.1 is a reserved, not a valid IP address. Enter
a valid IP source address.
R-RxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise the
Destination IP Address field of incoming R GOOSE messages must exactly match this value for the message to be
accepted as a valid RxGOOSE1 message. Set this setting to the same value as the R-GOOSE publisher's Destination IP
Address. For UR publishers, this value is in setting R-TxGOOSE# DST IP.
The destination IP address needs to be a valid multicast or unicast IP address. The UR does not validate the address
entered. The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
R-RxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies the level of security (authentication/encryption) used for RxGOOSE1. None indicates no security
mechanisms are in use. Signature indicates only signature (no encryption) is in use. SignatureAndEncryption indicates
that both signature and encryption are in use. Normally this setting is set to match the GOOSE publisher's security
method.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, FLOAT32, INT32, Dbpos (DPS), Quality, TimeStamp, Struct
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the up to 64 members that the UR is able
to subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the
last member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the
publisher's data set selected by the publisher's TxGOOSE datSet setting.
If the publisher dataset includes members with structured data, that is, data attributes, sub-data objects, and/or data
attributes with sub-data attributes, configuration must use one of the new 7.40 UR Setup RxGOOSE Inputs pages. In this
case the Member setting displays as the product-related name used by the publishing IED of the data object or data
attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal).
Note that a dataset can hold at most 64 basic data attribute values, and that a single structured data object or attribute
can contain multiple basic data attribute values. UR Setup software does not allow more that 64 basic data attribute
values to be entered, in which case the last several members settings cannot be changed from End of List.
Note that the publisher's name alone does not contain all the information required for subscription, additional publisher
information model information is stored elsewhere. For this reason, manual entry of the name is not supported.
5 RxGOOSE inputs
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean value received by a specified RxGOOSE to a FlexLogic
operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) value to four FlexLogic
operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a specified
FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the RxGOOSE
connectivity is lost. Other types of values can be present in subscribed GOOSE messages, but cannot be converted to
operands.
When an RxGOOSE Input is mapped to a value in the GOOSE message, the associated q value is validated, if the q value is
included in that GOOSE message as part of the data object.
The RxGOOSE Input value is reverted to its default value, if the associated:
• q.validity is invalid
• or q.test bit is set and the relay test mode is disabled
When the test mode function is Forcible or Isolated, the q.test bit is not validated. That means, when the relay is in Test or
Test/blocked mode, the q.test = False is treated same as q.test = True.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible in the UR Setup software. See the UR Family Communications Guide for more
information on GGIO3.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). With SCL file import, for Edition 1 the IP address in the ConnectedAP element must
match one IP address of the device, while for Edition 2 one of the three IP addresses in the ConnectedAP element must
match. When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The
figure shows a selection being made by importing a CID file using the Add IED function.
Figure 5-28: RxGOOSE Boolean panel (Edition 2)
Most of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must be
individually entered when the factory default values are not acceptable.
RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". The basic and enhanced front panels display the first 17
characters of this setting plus " On" to fit the 20 character display.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member which does not contain a BOOLEAN results in the
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular
Boolean subscribed to even if the member is a structure containing more than one Boolean.
RxGOOSE DPS1 ID
Range: 0 to 20 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Interm," "On," "Off," or "Bad." The basic and enhanced front
panels display the first 13 characters of this setting plus the state suffix to fit the 20 character display.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to
None, the RxGOOSE DPS1 FlexLogic operand assumes its default state.
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state. In the case that the member is a structure containing more than one Dbpos, the Subscribed
to column identifies the particular Dbpos subscribed to.
RxGOOSE DSP1 DEFAULT STATE
Range: Intermediate-state, Off, On, Bad-state, Latest
Default: Latest
This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal and the DPS FlexLogic operands
when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and when the 5
RxGOOSE has lost its connection with the publisher. When this setting is selected to Latest, the value of @Master/
GGIO3.IndPosψψ.stVal is Intermediate-state when the UR has just completed start-up and the selected RxGOOSE has
not yet received a message, and the latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
5 This setting allows the user to assign descriptive text to RxGOOSE Analog1. Unlike RxGOOSE Booleans and RxGOOSE
DPS, the RxGOOSE Analog operands have fixed names, for example RxGOOSE Analog1.
RxGOOSE Analog1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message that drives the RxGOOSE Analog1 FlexAnalog operand. If set to None, the
RxGOOSE Analog1 FlexAnalog operand assumes its default state.
RxGOOSE Analog1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Analog1 FlexAnalog operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member that does not contain a FLOAT32 results in the
RxGOOSE Analog1 FlexAnalog operand assuming its default state. The Subscribed to column identifies the particular
FLOAT32 subscribed to even if the member is a structure containing more than one FLOAT32.
RxGOOSE Analog1 DEFAULT
Range: -1000000.000 to 1000000.000 in steps of 0.001
Default: 1000.000
This setting specifies the value of the GOOSE analog input when the selected RxGOOSE has lost its connectivity with the
publisher and the RxGOOSE Analog1 DEFAULT MODE is set to "Default Value." Otherwise this setting has no effect. This
setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all
possible values can be stored. Some values can be rounded to the closest possible floating point number.
Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.
Report settings
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
An IEC 61850 Report server is an efficient method to deliver generic substation event information from a single server to a
single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-11: Number of report elements
Number
Buffered reports 30
Unbuffered reports 18
When using IEC 61850 Edition 2, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 or 2.0 report client requirements.
When using IEC 61850 Edition 1, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided that no more than
four data sets are used for reports. This restriction is to limit the amount of processing power that can be allocated to
reporting.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
read and acknowledged by the client to be retransmitted. 5
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the B90 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
Buffered Report1 RptID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the
client to discriminate Buffered Report1 messages from other messages. If the number of characters entered is zero, the
value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$BR$"BRCB01".
Buffered Report1 Name
Range: 0 to 32 VisibleString characters
Default: BRCB01
The entered value sets the report control block name value for Buffered Report1.
Buffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
To configure a DataSet, select it at the top of the window from the drop-down list, for example DataSet02 shown in the
previous figure. In the lower part of the window, drag and drop configuration items to the right side. For example select
the ST Ind001 stVal item and drag it to DataSet Member 1. Dataset members configured here affect other Report or
TxGOOSE control blocks that use the same DataSet.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Buffered Report1 OptFlds
Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits enabled/ true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits. To reduce message size, uncheck any fields that are not needed.
Figure 5-32: Options for buffered report messages (Edition 2)
DataSets
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As mentioned in the preceding GOOSE and Reports sections, the members whose values are communicated by these
services are itemized in an ordered list known as a data set. Each UR with the IEC 61850 option has 18 data sets (six fast
and 12 slow). Each data set can contain as many as 64 members. Any data set can be used simultaneously by any number
of TxGOOSE elements and/or by any number of Configurable Report elements. UR Setup software can configure any
FlexLogic operands and any FlexAnalog operands as members.
5 Figure 5-33: IEC 61850 DataSets (Edition 2)
UR Setup software requires data set members to be IEC 61850 data objects or data attributes with Functional Constraint
ST or MX. Certain FlexLogic and FlexAnalog operands have factory-assigned data attributes as tabulated in the UR Family
Communications Guide. All FlexLogic and FlexAnalog operands can be user-assigned to GGIO1 or GGIO4 data attributes,
so that operands without factory-assigned data attributes can still have their values published. See the GGIO1 and GGIO4
sections later for details.
Datasets used by TxGOOSE1, TxGOOSE2, and/or by reports also provide a chatter suppression service for their Boolean
members. Oscillation in a value, also known as chatter, can be caused by errors in logic programming, inadequate
hysteresis (deadband) on a threshold, or a failed station component. Chatter can flood a communications network with
GOOSE messages, degrading response time for all users. If chatter is detected in a Boolean member, TxGOOSE suspends
GOOSE event message triggering and report message triggering from that member for as long as the condition exists, and
for a minimum period of one second. While sending is suspended, a self-test message identifying the specific data item
detected as oscillating is activated.
For a summary of the panels in which the data sets are used, the path is Settings > Product Setup > Communications >
IEC 61850 > DataSets > Summary.
For the settings, navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets > TT6DataSet1 for the
first data set.
Copy and paste functions are available when right-clicking a DataSet. They allow the target dataset to be configured
based on its order code. If some dataset items are not supported, they are not pasted, and a warning message shows a list
of dataset items that were not supported and not pasted. The DataSet name is not copied or pasted. In short, use this
feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples.
Figure 5-34: Member right-click
DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. The
value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fast
datasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSE
datasets are allowed.
An ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the
DataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,
and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An
ObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 shared by
Range: 0 to 32 VisibleString characters
Default:
Names of all control blocks that use this DataSet. Read-only field.
DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.
Product setup
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup.
Security
This setting applies to IEC 61850 Edition 2.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Security.
5 Figure 5-35: IEC 61850 Security
SecGSAL1.SecDataClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to
SecGSAL1.SecDataClr. "sbo" here is select-before-operate.
SecGSAL1.OpCntRs ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to SecGSAL1.OpCntRs.
"sbo" here is select-before-operate.
Demand
Deadband parameters of measured values related to the Demand metering are configured here.
Energy
Deadband parameters of measured values related to the Energy metering are configured here.
TmClkLTMS1.TmnsDelta.db
Range: 0.000 to 100.000 %
Default: 0.000 %
This setting is a deadband setting and is used by the relay to determine when to update the "mag" and "cVal" values
from the associated "instMag" and "instCVal" values. The value shall represent the percentage of difference between
maximum and minimum in units of 0.001%. The minimum and maximum values for TmnsDelta data object are
-500000000 ns and 500000000 ns respectively and for example, a setting value of 0.002% results in the dead banded
value of (500000000 - (-500000000)) * 0.002 / 100 = 20000 ns. The default setting value of 0.000% does not update the
"mag" and "cVal" values.
Deadband settings
A deadband is a range in which no action occurs, usually expressed as a percentage.
The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: Product Setup > Real Time
Clock, FlexLogic, Control Elements, and GGIO4. Each panel is not outlined here. The FlexLogic category applies to IEC 61850
Edition 2.
Deadband setting names all end either with "DB" or .db. As they all work the same way, but each on a different analog
value, a single description applicable to all deadband settings is given here. The analog value that each deadband setting
applies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associated
deadband setting can be found in the UR Family Communications Guide.
Figure 5-37: Deadband settings with .db suffix (Edition 2)
GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
5 change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Figure 5-38: Deadband settings
Deadband settings are entered in UR Setup software in units of percent of the difference between the "max." and "min." of
the associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings
is 0.000 to 100.000% in steps of 0.001. The default value is 0.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
• Phase current — 46 x phase CT primary setting
• Neutral current — 46 x ground CT primary setting
• Ground current (sensitive ground CT) — 4.6 x sensitive ground CT primary setting
• Phase, phase-to-phase, and sequence voltage — 275 x phase VT ratio setting
After making changes to settings that affect the per unit bases, such as CT PRIMARY, CT SECONDARY, VT
SECONDARY, VT RATIO, and VT CONNECTION settings, cycle power to the relay to force recalculation of the IEC
61850 deadband interval in primary units. Until the relay restarts, for some quantities, the deadband interval in
primary units calculated for the previous settings remains in effect.
Signal sources
Deadband parameters of measured values related to the signal sources are configured here.
Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
5
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.
Figure 5-39: Setting Groups panel (Edition 2)
This setting is not mapped into the IEC 61850 information model, but sets the value of SettingControl element attribute
actSG in SCL files.
Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings
that configure the IEC 61850 protocol interface for record clear commands.
Figure 5-40: Commands panel (Edition 2)
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the B90 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.
DatLogRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.
CBArc0SCBR1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
DmdMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
EnrMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
GGIO1
GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information model
data attributes.
For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications. 5
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1.
Figure 5-41: IEC 61850 GGIO1 panel (Edition 2)
GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.
GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
Figure 5-42: GGIO2 panel (Edition 2)
GGIO4
GGIO4 is a UR feature that allows up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information model
data attribute.
For the value of a FlexAnalog operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO4 allows those FlexAnalog operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the
settings for the first GGIO4 value. The settings and functionality for the others are similar.
ANALOG IN 1 VALUE
Range: any FlexAnalog operand
Default: OFF
This setting selects the FlexAnalog operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO4.AnIn01.instMag.f. The value of the FlexAnalog operand is converted automatically to the format and
scaling required by the standard, that is to say primary amperes, primary volts, and so on. See Appendix A for a list of
FlexAnalog operands. 5
ANALOG IN 1 DB
Range: 0.000 to 100.000% in steps of 0.001
Default: 0.000%
This setting specifies the deadband for the ANALOG IN 1 VALUE. The deadband is used to determine when to update the
deadbanded magnitude from the instantaneous magnitude. The deadband is a percentage of the difference between
the "max." and "min." values. Here, the "max." and "min." are as specified by the settings ANALOG IN 1 MAX and ANALOG IN
1 MIN.
See the Deadband Settings section earlier for a description of deadbanded values.
ANALOG IN 1 MIN
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
This setting specifies the "min." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
ANALOG IN 1 MAX
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 1000000.000
This setting specifies the "max." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
The B90 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the B90 “Main Menu.” Web pages are read-only and are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the
B90 and a computer to an Ethernet network, then enter the IP address of the B90 Ethernet port in a web browser.
To close the port, set the port number to 0.
Any change takes effect when the B90 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the B90 over a network. The B90 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained
from the B90 contains a list and description of all available files, for example event records and oscillography.
The "put" function is not for security reasons. You can enter a "get" command but not a "put" command.
TFTP MAIN UDP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the B90 is
restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
IEC 60870-5-104 is a transmission protocol for network access, specifically for communication between a control station
and substation over a TCP/IP network.
The B90 supports the IEC 60870-5-104 protocol. This protocol is enabled when the SETTINGS PRODUCT SETUP
COMMUNICATIONS PROTOCOL setting is set to IEC 60870-5-104. The B90 can be used as an IEC 60870-5-104 slave device
5 connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the B90 maintains two
sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the B90 at one
time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the B90 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the B90 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD
setting is set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured
value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the B90, the default thresholds are in effect.
The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
IEC TCP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the B90 is restarted.
IEC COMMON ADDRESS OF ASDU — The change takes effect when the B90 is restarted.
IEC CYCLIC DATA PERIOD — The change takes effect when the B90 is restarted.
The B90 relay does not support power metering. As such, the IEC POWER DEFAULT THRESHOLD setting is not
applicable.
The B90 relay does not support energy metering. As such, the IEC ENERGY DEFAULT THRESHOLD setting is not
applicable.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL IEC NETWORK CLIENT
ADDRESSES
IEC NETWORK CLIENT ADDRESS 1: Range: standard IPV4 address format
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IPV4 address format
0.0.0.0
The B90 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the B90 can connect. A maximum of two simultaneous connections are supported at any given time.
IEC 60870-5-103 is a companion standard to the IEC 60870-5 suite of standards for transmission protocols. It defines
messages and procedures for interoperability between protection equipment and devices of a control system in a
substation for communicating on a serial line.
The IEC 60870-5-103 protocol is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL setting
is set to IEC 60870-5-103.
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication, exchanging
information with a control system. In the context of this protocol, the protection equipment is the slave and the control
system is the master. The communication is based on a point-to-point principle. The master must be able to interpret the
IEC 60870-5-103 communication messages.
The UR implementation of IEC 60870-5-103 consists of the following functions:
• Report binary inputs
• Report analog values (measurands)
• Commands
• Time synchronization
The RS485 port supports IEC 60870-5-103.
The UR Family Communications Guide contains more information on the protocol.
IEC103 COMMON ADDRESS OF ASDU — This setting uniquely defines this B90 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is
recommended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range
of 254 addresses is never exhausted.
IEC103 SYNC TIMEOUT — This setting defines the time that the B90 waits for a synchronization message. The B90
synchronizes its clock using all available sources, with the source synching more frequently overwriting the time of the
other sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B,
PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs
and none of IRIG-B, PTP, or SNTP is active, the B90 sets the invalid bit in the time stamp of a time-tagged message.
The settings for the remaining menus are outlined as follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-103 IEC103 INPUTS BINARY
IEC103 INPUTS POINT 0 See below
BINARY
5
POINT 95 POINT 95 FUN Range: 0 to 255 in steps of 1
0
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the B90 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
For any change to take effect, restart the relay.
TYPE IDENTIFICATION (TYP) — The configuration field TYP indicates how many measurands are present in the corresponding
ASDU. Each ASDU can take either 4 or 9 measurands maximum, depending on the type identification (3 respectively 9). For
any change to take effect, restart the relay.
FUNCTION TYPE (FUN) and INFORMATION NUMBER (INF) — These two fields form the Information Object Identifier of the ASDU
as defined in IEC 60870-103. For any change to take effect, restart the relay.
SCAN TIMEOUT (SCAN TOUT) — This is the cyclic period used by the B90 to decide when a measurand ASDU is included in a
response. The measurand is sent as response to a Class 2 request when the corresponding timeout expires. The default
value 0 means 500 ms.
ANALOG # — This field contains the actual measurand to be sent in the response to the master. The measurands can be
mapped using elements from a list of FlexAnalog operands. The measurands sent are voltage, current, power, power
factor, and frequency. If any other FlexAnalog is chosen, the B90 sends 0 instead of its value. Note that the power is
transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I,
respectively measurands II).
Each IEC 60870-5-103 measurands list ends at the first unconfigured ("Off") value. Any measurand assigned after the first
"Off" value is ignored.
At least one measurand per ASDU must be configured in order to configure the following ASDU. For example, the user can
configure only one measurand for each ASDU, but the user is not allowed to skip ASDU 2 and configure measurands in
ASDU 3.
For any change to take effect, restart the relay.
ANALOG # FACTOR and OFFSET — For each measurand included in the ASDU, a factor and offset also can be configured. The
factor and offset allow for scaling to be performed on measurands. The final measurement sent to the IEC 60870-103
master is then "a*x + b," where x is the measurand, a is the multiplying factor and b is the offset. The master has to perform
the reversed operation in order to retrieve the actual value if such scaling is done. By default a = 1 and b = 0, so no scaling
5 is done if these values are left at their defaults. Examples of when scaling is appropriate are as follows:
• If the measured value contains decimals and it is important to preserve the resolution. Since the format for
transmitting the measurand does not permit decimals, a factor a>1 can be applied before transmission. For example,
a frequency F=59.9Hz can be transmitted as Ft = 10 * F = 10 * 59.9 = 599. In this case a = 10, b = 0. The master receives
599 and has to divide by 10 to retrieve the real value 59.9.
• If the measured value is larger than what fits in the format defined in IEC 103. The format defined in the standard
allows for signed integers up to 4095. By offsetting, unsigned integers up to 4096 + 4095 = 8191 are supported.
Scaling using factors <1 can be required in such cases. The calculation is outlined in the IEC 60870-5-103 chapter of
the UR Family Communications Guide. Two examples follow, where you decide factors a and b.
Example 1: Nominal power Pn = 100 MW = 100000 KW (power is transmitted in KW)
Since P can be both positive and negative:
Transmitted power Pt = (4095/(Pn*2.4)) * P = (4095/(100000 * 2.4) ) * P
= 0.017 * P
a = 0.017
b=0
Pt = 0.017 * P
For a max power 100000 KW * 2.4 = 240000 KW, we transmit
Pt = 0.017 * 240000 = 4080
A value above 240 MW is indicated by overflow.
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000 V * 2.4 = 1200000 V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104
COMMAND 1
COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the B90. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
Description Value
Off 0
Virtual Input 1 1
Virtual Input 2 2
... ...
Virtual Input 64 64
This setting applies to the USB port on the graphical front panel.
This setting enables/disables the USB port on the graphical front panel. When the port function is "Enabled," a standard
USB serial cable allows a computer running the EnerVista UR Setup software to retrieve, display, and write settings either
individually or collectively, to display status and actual values, to initiate controls, and to retrieve and display event records,
oscillography records, data logger records, and disturbance records. Installation of the EnerVista software automatically
installs the drivers required to use this USB port.
DNP is not available using the USB port on the graphical front panel.
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the ADDRESS line (converted from hex to decimal format). The corresponding value (if programmed) displays in the VALUE
line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previous ADDRESS lines
incremented by 1. An address value of “0” in the initial register means “none” and values of “0” display for all registers.
Different ADDRESS values can be entered as required in any of the register positions.
The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser;
enter the IP address of the B90 in a web browser and click the option.
5.3.8.1 Menu
SETTINGS PRODUCT SETUP REAL TIME CLOCK
REAL TIME SYNCRONIZING SOURCE: Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
CLOCK None Other, PP/PTP/IRIG-B/Other
The relay contains a real time clock (RTC) to create time stamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
time delivered to the relay. While the RTC is not synchronized via PTP or IRIG-B, or the relay determines that it has an offset
possibly greater than 10 µs from the international time standard, the CLOCK UNSYNCHRONIZED FlexLogic operand is
activated.
The SYNCHRONIZING SOURCE setting displays in the software when the relay includes the IEEE 1588 software option. The
setting configures the priority sequence of the time synchronization source, to determine which of the available external
time sources to use for time synchronization. A setting of None causes the RTC and the synchrophasor clock to free-run,
and the clock can be changed from the front panel or from communications protocols. A setting of PP/IRIG-B/PTP/Other,
IRIG-B/PP/PTP/Other, or PP/PTP/IRIG-B/Other causes the relay to track the first source named that is enabled and
operational, or free-run if none of these are available. Here, PP means a time source that is strictly compliant with PP, PTP
means a time source that is not strictly compliant with PP, and Other means any less precise source (SNTP, IEC 103, IEC 104,
Modbus, or DNP). When a time source fails or recovers, the relay automatically transfers synchronization as required by
this setting.
When the relay does not have the IEEE 1588 software option and this setting does not display, it uses IRIG-B when enabled
and operational, then failing that SNTP when configured and operational, and otherwise it free-runs unless the clock is
changed from the front panel or from communications protocols.
Setup for IRIG-B is illustrated in the Installation chapter.
For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the B90
clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time
synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP,
5
are active in the system. If IRIG-B or PTP is used to update the relay clock, the other protocols (such as SNTP) are not
allowed to update, even if active.
See the COMMANDS SET DATE AND TIME menu section of this manual to manually set the RTC.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment. A Date/Time Changed event is generated when:
• The real time clock changed from SNTP/PTP/IRIG-B and the time difference is more than one second
• The real time clock changed from the front panel or via Modbus register. The relay always generates this event
regardless of the time difference.
• The Daylight Saving Time (DST) setting gets enabled and the current relay time is already in the DST zone
• The real time clock enters or leaves DST
To enable IRIG-B synchronization, the input IRIG-B SIGNAL TYPE must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
Clocks can be synchronized locally among several relays using the computer time. When using a time source, such as IRIG-
B, the time is overwritten eventually by the time source. To synchronize clocks among UR devices:
1. In the EnerVista software, expand the main menu in the Online Window area and select the Synchronize Devices
entry. The window opens. The software prompts to acknowledge any offline devices.
2. Click the Synchronize Devices button at the top of the window, and confirm the action at the prompt. The devices
assume the time of the computer being used.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use the
following sections.
SETTINGS PRODUCT SETUP REAL TIME CLOCK PRECISION TIME PROTOCOL (1588) PTP PORT 1(3)
PTP PORT 1 PORT 1 PTP FUNCTION: Range: Enabled, Disabled
Disabled
The B90 is provided with optional Precision Time Protocol capability. This feature is specified as the IEEE 1588
5 software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The B90 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in
IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network
that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include 1) missing declaration of PP compliance in the
messages, 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially
greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates.
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes referred to as
version 2 PTP. It does not support the previous version of the standard (version 1).
PTP is a protocol that allows multiple clocks in a network to synchronize with one another. It permits synchronization
accuracies better than 1 ns, but this requires that each and every component in the network achieve very high levels of
accuracy and a very high baud rate, faster than normally used for relay communications. When operating over a generic
Ethernet network, time error can amount to 1 ms or more. PP is a profile of PTP which specifies a limited subset of PTP
suitable for use in power system protection, control, automation, and data communication applications, and thereby
facilitates interoperability between different vendor’s clocks and switches. PP specifies a worst-case delivered time error of
less than 1 µs over a 16-hop network.
In a PTP system and in a PP system, the clocks automatically organize themselves into a master-slave synchronization
hierarchy with the “best” clock available making itself the "grandmaster" at the top of the hierarchy; all others make
themselves “slaves” and track the grandmaster. Typically the grandmaster clock receives its time from GPS satellites or
some other link to the international time standard. If the grandmaster fails, the next “best” clock available in the domain
assumes the grandmaster role. When a clock on start-up discovers that it is “better” than the present grandmaster, it
assumes the grandmaster role and the previous grandmaster reverts to slave. The B90 qualification mechanism accepts a
potential master clock as a new grandmaster, when in a four-second interval it has received three announce messages
from it, all better than the present grandmaster clock and better than any other announce in this interval.
Time messages issued by the grandmaster are delayed as they pass through the network both due to the finite speed of
the signal in the interconnecting fiber or wire, and due to processing delays in the Ethernet switches. Each clock and switch
implementing PP measures the propagation delay to each of its PP neighbors, and compensates for these delays in the
time received. Each network device implementing PP measures the processing delay it introduces in each time message
and compensates for this delay in the time it transmits. As a result, the time delivered to end-devices such as the UR are
virtually identical to the grandmaster time. If one of the network devices in the hierarchy does not fully implement PP, the
associated propagation delay and/or latency may not be compensated for, and the time received at the end-device can be
in error by more than 100 µs.
See the preceding Real Time Clock section for a description of when time values received via PTP are used to update the
relay’s real time clock.
The following settings are available for configuring the relay for PTP. The PTP menu displays only when the option was
purchased.
STRICT POWER PROFILE — Power profile (IEEE Std C37.238 2011) requires that the relay only select a power profile compliant
clock as a grandmaster, that the delivered time have worst-case error of ±1 µs, and that the peer delay mechanism be
implemented. With the strict power profile setting enabled, the relay only selects as master the clocks displaying the
IEEE_C37_238 identification codes. It uses a port only when the peer delay mechanism is operational. With the strict power
profile setting disabled, the relay uses clocks without the power profile identification when no power profile clocks are
present, and uses ports even if the peer delay mechanism is non-operational. This setting applies to all of the relay’s PTP
capable ports.
PTP DOMAIN NUMBER — Set this setting to the domain number of the grandmaster-capable clock(s) to be synchronized to. A
network can support multiple time distribution domains, each distinguished with a unique domain number. More
commonly, there is a single domain using the default domain number zero.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN PRIORITY — This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued
by the relay’s peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that it be
5
set to 7 in accordance with PTP. Depending on the characteristics of the device to which the relay is linked directly, VLAN
Priority can have no effect.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN ID — This setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. It is provided in compliance with PP. As these messages have a destination address that indicates
they are not to be bridged, their VLAN ID serves no function, and so can be left at its default value. Depending on the
characteristics of the device to which the relay is linked directly, VLAN ID can have no effect. This setting applies to all of
the relay’s PTP capable ports.
PORT 1 ... 3 FUNCTION — While this port setting is selected to disabled, PTP is disabled on this port. The relay does not
generate or listen to PTP messages on this port.
PORT 1 ... 3 PATH DELAY ADDER — The time delivered by PTP is advanced by the time value in this setting prior to the time
being used to synchronize the relay’s real time clock. This is to compensate to the extent practical for time delivery delays
not compensated for in the network. In a fully compliant PP network, the peer delay and the processing delay mechanisms
compensate for all the delays between the grandmaster and the relay. In such networks, make this setting zero.
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay is later than the time indicated in the message. This
setting can be used to approximately compensate for this delay. However, as the relay is not aware of network switching
that dynamically changes the amount of uncompensated delay, there is no setting that always and completely corrects
for uncompensated delay. A setting can be chosen that reduces the worst-case error to half of the range between
minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASSYMMETRY — This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two directions of a link. Except in
unusual cases, the two fibers are of essentially identical length and composition, so make this setting zero.
In unusual cases where the length of the link is different in different directions, set this setting to the number of
nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and from
the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the fibers that
the delay from the relay to the Ethernet switch it is connected to is 9000 ns and that the delay from the switch to the relay
is 11000 ns, then the mean delay is 10000 ns, and the path delay asymmetry is 11000 - 10000 = +1000 ns.
The B90 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the B90 can obtain clock time over
an Ethernet network. The B90 acts as an SNTP client to receive time values from redundant SNTP/NTP servers, usually a
dedicated product using a GPS receiver to provide an accurate time. One or two SNTP servers can be used; use of both
servers for redundancy is recommended but not required.
5 To use SNTP, enable the function and set SNTP SERVER1 IP ADDR and/or SNTP SERVER2 IP ADDR to the SNTP/NTP server IP
addresses. The B90 attempts to obtain time values from the SNTP SERVER1 SNTP/NTP server. If SERVER1 is not available/
reachable, the B90 switches to the SNTP SERVER2 to get the time value and vice versa.
Since many time values are obtained and averaged, it generally takes three to four minutes until the B90 clock is closely
synchronized with the SNTP/NTP server. It can take up to 20 minutes for the B90 to signal an SNTP self-test error if the
server is offline, depending on the number and SNTP server modes. Broadcast mode timeout is 10 minutes and unicast
timeout is 80 seconds (corresponds to three unicast request retries).
SNTP FUNCTION — Enables or disables the SNTP feature on the B90.
SNTP SERVER1 IP ADDR — The B90 uses the SERVER1 address to contact an SNTP/NTP server to obtain time values. When
the SNTP FUNCTION setting is set to enabled or on startup if the setting is enabled, the B90 SNTP client requests SERVER1 for
the time value. If the SERVER1 channel fails or is not reachable, the B90 switches to SERVER2 SNTP/NTP server.
If SERVER1 SNTP server is set to 127.0.0.1, the B90 considers the SERVER1 SNTP server to be unconfigured.
To use SERVER1 SNTP in broadcast mode, set the SNTP SERVER1 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The B90 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The B90 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER2 IP ADDR — The B90 uses this address to contact an SNTP/NTP server if SERVER1 channel fails or is not
reachable. If SERVER2 SNTP server is set to 127.0.0.1, the B90 considers the SERVER2 SNTP server to be unconfigured.
To use SERVER2 SNTP in broadcast mode, set the SNTP SERVER2 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The B90 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The B90 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER1 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER1 SNTP is not required, close the port by
changing this setting to zero.
SNTP SERVER2 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER2 SNTP is not required, close the port by
changing this setting to zero.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
If SERVER1 IP ADDR and UDP PORT settings match the SERVER2 IP ADDR and UDP PORT settings, the B90 considers only
the SERVER1 SNTP server as being configured and an SNTP Failure error message generates. The failure message
also displays when both servers are unavailable.
DST START DAY: Range: Sunday to Saturday (all days of the week)
Sunday
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
5
Sunday
The B90 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.
LOCAL TIME OFFSET FROM UTC — Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME and DST — Can be used to allow the relay to follow the DST rules of the local time zone. Note that
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective
creation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the
pre-fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the
complete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the
element resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (x.xx, for example) and relay model (B90), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the
5 active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger),
and fault values of all programmed analog channels (at the fault trigger).
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista software is required to view all captured data. A FAULT RPT TRIG event is automatically created when the report
is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from
thermal protection with the report configured to include temperatures, and short-circuit trip with the report configured to
include voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
PRE-FAULT 1 TRIGGER — Specifies the FlexLogic operand to capture the pre-fault data. The rising edge of this operand stores
one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a record as long as
the operand selected as PRE-FAULT 1 TRIGGER is “On.” If the operand remains “Off” for 1 second, the element resets and no
record is created.
FAULT 1 TRIGGER — Specifies the FlexLogic operand to capture the fault data. The rising edge of this operand stores the
data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time of the
report.
FAULT REPORT 1 #1 to FAULT REPORT 1 #32 — These settings specify an actual value such as voltage or current magnitude,
true RMS, phase angle, frequency, temperature, and so on, to be stored when the report is created. Up to 32 channels can
be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.
5.3.10 Oscillography
5.3.10.1 Menu
SETTINGS PRODUCT SETUP OSCILLOGRAPHY
OSCILLOGRAPHY NUMBER OF RECORDS: Range: 1 to 64 in steps of 1
15
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records can be captured
simultaneously.
To retrieve an Oscillography record from a relay:
1. If not yet set up for oscillography, configure settings under Settings > Product Setup > Oscillography in the EnerVista
software.
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display. 5
5. In the waveform window that opens, you can save the file, for example with the CFG extension.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors, such as sample rate and the number of operational modules. There is a fixed amount of data storage for
oscillography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES
RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sample
configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
Table 5-13: Oscillography cycles/record example
Records CT/VTs Sample rate Digital Analog Cycles per
channels channels record
3 1 32 32 16 2399
3 1 64 32 16 1450
16 1 32 32 16 666
16 1 64 32 16 402
32 1 32 32 16 352
32 1 64 32 16 213
3 2 32 32 16 1516
3 2 64 32 16 851
16 2 32 32 16 421
TRIGGER MODE — A new record automatically overwrites an older record when TRIGGER MODE is set to “Automatic
Overwrite.”
TRIGGER POSITION — Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
position of 25% consists of 25% pre- and 75% post-trigger data.
TRIGGER SOURCE — Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS — Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records are cleared.
DIGITAL 1(63) CHANNEL — This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
To populate quickly the rows in the Offline Window, use Ctrl C/V to copy/paste, or click then double-click a row to display a
quick selection window.
Figure 5-46: Quick selection window
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay depend on
• the type of relay,
• the type and number of CT/VT hardware modules installed, and
• the type and number of analog input hardware modules installed
A list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog Parameters. The
parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display.
It can be time-consuming to scan through the list of parameters via the relay keypad and display — entering this number
via the relay keypad causes the corresponding parameter to display.
If there are no CT/VT modules and analog input modules, no analog traces appear in the file; only the digital traces appear.
The LEDs can be customized to illuminate when a selected FlexLogic operand is in the logic 1 state. The trip and alarm
LEDs can also be customized in a similar manner. To ensure correct functionality of all LEDs, an LED test feature is also
provided.
When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user-
programmable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all
LEDs, including the LEDs of the optional user-programmable pushbuttons.
For the enhanced and basic front panels, the test consists of the following three stages:
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned.” This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on for one second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for one second, then back on. The test routine starts at the top
left panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to
more than one LED being turned off from a single logic point. This stage can be interrupted at any time.
For the graphical front panel, the test consists of the following stages:
1. All 22 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is "burned." This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on with the orange color for one second, then back off.
The test routine starts at the top left panel, moving from the top to bottom for all 14 LEDs. Then the eight pushbutton
LEDs are tested in the same manner. This test checks for hardware failures that lead to more than one LED being
turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on with the orange color. One LED at a time turns off for one second, then back on. The test
routine starts at the top left panel moving from top to bottom for all 14 LEDs. Then the eight pushbutton LEDs are
tested in the same manner. This test checks for hardware failures that lead to more than one LED being turned off
from a single logic point. This stage can be interrupted at any time.
4. Additionally, stages 2 and 3 are repeated twice for the five device status LEDs and nine event cause LEDs, one time
with green color on and the other with red color on.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and
monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay
and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting
from relay response during testing. The reset pushbutton does not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is initiated,
the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL
setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is
executed.
5
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
STAGE 1 time-out
(all LEDs on) (1 minute)
5
Wait 1 second
control input
rising edge
STAGE 3
of the control
(one LED off at a time) input
842011A1.CDR
Application example 1
Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER-
PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu. (The option does not display when not purchased.)
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.10 s”
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS
PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST menu:
LED TEST FUNCTION: “Enabled”
LED TEST CONTROL: “PUSHBUTTON 1 ON”
The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.
Application example 2
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.
The trip and alarm LEDs are in the first LED column (enhanced and graphical front panels) and on LED panel 1 (basic front
panel). Each LED can be programmed to turn on when the selected FlexLogic operand is in the logic 1 state.
For the enhanced and basic front panels, there are 48 amber LEDs across the relay LED panels. Each of these indicators
can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state.
For the basic front panel, the LEDs are located as follows:
• LED Panel 2 — User-programmable LEDs 1 through 24
• LED Panel 3 — User programmable LEDs 25 through 48
5 For the enhanced front panel, the LEDs are located as follows:
• LED column 2 — User-programmable LEDs 1 through 12
• LED column 3 — User-programmable LEDs 13 through 24
• LED column 4 — User-programmable LEDs 25 through 36
• LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is “Self-
Reset” (the default setting), the LED illumination tracks the state of the selected LED operand. If the LED 1 TYPE setting is
“Latched,” the LED, once lit, remains so until reset by the front panel RESET button, from a remote device via a
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5-14: Recommended settings for user-programmable LEDs
Setting Parameter Setting Parameter
LED 1 operand SETTING GROUP ACT 1 LED 13 operand Off
LED 2 operand SETTING GROUP ACT 2 LED 14 operand Off
LED 3 operand SETTING GROUP ACT 3 LED 15 operand Off
LED 4 operand SETTING GROUP ACT 4 LED 16 operand Off
LED 5 operand SETTING GROUP ACT 5 LED 17 operand Off
LED 6 operand SETTING GROUP ACT 6 LED 18 operand Off
LED 7 operand Off LED 19 operand Off
LED 8 operand Off LED 20 operand Off
LED 9 operand Off LED 21 operand Off
LED 10 operand Off LED 22 operand Off
LED 11 operand Off LED 23 operand Off
LED 12 operand Off LED 24 operand Off
For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
LED 1 TYPE — If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel RESET button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-15: Default input and output operand for event cause LEDs
LED Default input operand Output operand Default color
Event Cause LED 1 LED PICKUP EVENT CAUSE LED 1 Green
Event Cause LED 2 LED VOLTAGE EVENT CAUSE LED 2 Orange
Event Cause LED 3 LED CURRENT EVENT CAUSE LED 3 Orange
Event Cause LED 4 LED FREQUENCY EVENT CAUSE LED 4 Orange
Event Cause LED 5 LED OTHER EVENT CAUSE LED 5 Orange
Event Cause LED 6
Event Cause LED 7
LED PHASE A
LED PHASE B
EVENT CAUSE LED 6
EVENT CAUSE LED 7
Orange
Orange
5
Event Cause LED 8 LED PHASE C EVENT CAUSE LED 8 Orange
Event Cause LED 9 LED NEUTRAL/GROUND EVENT CAUSE LED 9 Orange
DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped
FUNCTION: Enabled with Direct Input/Output module.
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
This settings menu allows enabling and disabling of most minor self-test alarms.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
When using the graphical front panel and setting annunciator alarms, the function needs to be enabled here too, else the
alarm is not triggered.
Control pushbuttons
842813A1.CDR
An additional four control pushbuttons are included on the basic front panel when the B90 is ordered with the 12 user-
programmable pushbutton option.
USER 4
842733A2.CDR
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to perform
the required function. Each operand remains asserted as long as the pushbutton is pressed and resets when the
pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognized
by various features that can use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The front panel keys (including control keys) cannot be operated simultaneously—a given key
must be released before the next one can be pressed. 5
Figure 5-50: Control pushbutton logic
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
5
The B90 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
• Enhanced horizontal front panel — 16 user-programmable pushbuttons
• Enhanced vertical front panel — 6 user-programmable pushbuttons
• Basic horizontal front panel — 12 user-programmable pushbuttons
• Graphical front panel — 16 user-programmable pushbuttons (eight physical pushbuttons, eight graphical interface
pushbuttons)
User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under Maintenance > Change Front Panel.
The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.
Example
To clear event records using pushbutton 1, set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 1 ON. Then program the pushbutton by setting Settings > Product Setup > User-
Programmable Pushbuttons > Pushbutton 1 Function to "Self-reset." For a graphical front panel, to use a side
pushbutton 9 to 16 to clear the event records, it also needs to be programmed in a single-line diagram.
The figures show user-configurable pushbuttons for the front panels.
842814A1.CDR
1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.cdr
5
1 5
2 6
3 7
4 8
RESET ESC
ENTER
859761A1.CDR
Front panel pushbuttons and LEDs can be custom labelled as outlined in the Front Panel Labelling section in the previous
chapter.
Each pushbutton asserts its own “On” and “Off” FlexLogic operands (for example, PUSHBUTTON 1 ON and PUSHBUTTON 1 OFF).
These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is active,
the ANY PB ON operand is asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the
corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the
PUSHBTN 1 LED CTL setting.
The activation and deactivation of user-programmable pushbuttons depends on whether latched or self-reset mode is
programmed.
• Latched mode — In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSHBTN 1 SET setting, by directly pressing the associated front panel pushbutton, or with the graphical front panel
interface. The state of each pushbutton is stored in non-volatile memory and maintained through a loss of control
power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET
setting, by directly pressing the active front panel pushbutton, or with the graphical front panel interface.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY
settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if
control is not executed within a specified time period.
• Self-reset mode — In self-reset mode, a user-programmable pushbutton can be set (activated) by asserting the
operand assigned to the PUSHBTN 1 SET setting, by pressing the front panel pushbutton, or by the graphical front panel
interface. A pushbutton remains active for the time it is pressed physically or pressed in the graphical front panel
interface, plus the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via
FlexLogic, the pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand assigned to the
PUSHBTN 1 SET setting remains On has no effect on the pulse duration.
The pulse duration of the remote set or local front panel pushbutton must be at least 50 ms to operate the
pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events and
various system disturbances that can cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL
and PUSHBTN 1 REMOTE settings. If local inhibit is applied, the pushbutton ignores set and reset commands executed
through the front panel pushbuttons. If remote inhibit is applied, the pushbutton ignores set and reset commands
executed through FlexLogic operands.
5 The inhibit functions are not applied to the autoreset feature. The inhibit function can be used in SBO control operations to
prevent user-programmable pushbutton activation and ensuring “one-at-a-time” select operation.
The inhibit functions can also be used to prevent pushbutton activation from the accidental pressing of the front panel
pushbuttons. The separate inhibit of the local and remote operation simplifies the implementation of local/remote control
supervision.
Pushbutton states can be logged by the event recorder. User-defined messages can also be associated with each
pushbutton and displayed on basic and enhanced front panels when the user-programmable pushbutton is activated, and
when in the latched mode when the user-programmable pushbutton is deactivated. With the graphical front panel
interface, instead of messages, the status of user-programmable pushbuttons can display on a single-line diagram and
can also display in annunciator page windows and in actual values page cells.
For the graphical front panel, the pushbuttons 1 to 8 are linked to the eight physical pushbuttons, and pushbuttons 9 to 16
are mapped to the graphical interface pushbuttons. To set the buttons for pushbuttons 9 to 16, access Settings > Product
Setup > Graphical Panel > Single Line Diagram Editor, click the PB symbol in the toolbox, then configure pushbuttons 9 to
16.
PUSHBUTTON 1 FUNCTION — This setting selects the mode of the pushbutton (Self-Reset, Latched, Disabled). If set to
“Disabled,” the pushbutton is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If
set to "Latched," the pushbutton remains on until reset.
PUSHBTN 1 ID TEXT — This setting specifies the top 20-character line of the user-programmable pushbutton message and is
intended to provide ID information of the pushbutton. For example, the text displays in the Event Record. See the User-
definable Displays section in this chapter for instructions on how to enter alphanumeric characters from the keypad. On a
graphical front panel, this setting instead controls the label of the user-programmable pushbutton component on single-
line diagrams.
PUSHBTN 1 ON TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and is displayed when the pushbutton is in the “on” position. See the User-definable Displays section for instructions on
entering alphanumeric characters from the keypad. On a graphical front panel, this setting instead controls the on status
text of the user-programmable pushbutton component on single-line diagrams. This setting is not applied to the physical
pushbuttons on the graphical front panel.
PUSHBTN 1 OFF TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and displays when the pushbutton is deactivated and the PUSHBUTTON 1 FUNCTION is “Latched.” A message does not
display when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand status is implied to be “Off” upon its
release. The length of the “Off” message is configured with the PRODUCT SETUP DISPLAY PROPERTIES FLASH MESSAGE
TIME setting. On a graphical front panel, this setting instead controls the off status text of the user-programmable
pushbutton component on single-line diagrams. This setting is not applied to the physical pushbuttons on the graphical
front panel.
PUSHBTN 1 HOLD — This setting specifies the time required for a front panel pushbutton to be pressed before it is deemed
active. This timer is reset upon release of the pushbutton. Note that user-programmable pushbutton operation requires the
front panel pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the user-
programmable pushbutton hold timer.
PUSHBTN 1 SET — This setting assigns the FlexLogic operand serving to activate the user-programmable pushbutton
element. The duration of the incoming set signal must be at least 50 ms.
PUSHBTN 1 RESET — This setting assigns the FlexLogic operand serving to deactivate the user-programmable pushbutton
element. This setting is applicable only if the user-programmable pushbutton is in "Latched" mode.
PUSHBTN 1 AUTORST — This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in “Latched” mode.
PUSHBTN 1 AUTORST DELAY — This setting specifies the time delay for automatic reset of the pushbutton when in "Latched"
mode.
PUSHBTN 1 REMOTE — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
PUSHBTN 1 LOCAL — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME — This setting applies only to “Self-Reset” mode and specifies the duration of the user- 5
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by PUSHBTN 1 SET remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL — This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the PUSHBUTTON 1 ON operand. This setting is not applied to
Pushbuttons 9 to 16 on the graphical front panel, where the label background shows the orange glow color for the "on"
state.
PUSHBTN 1 MESSAGE — This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the PUSHBTN 1 ID and PUSHBTN 1 OFF TEXT settings. This settings has no effect on the
graphical front panel.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays when
the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the FLASH MESSAGE TIME setting.
When set to "High Priority", the duration of the off message is as specified by the FLASH MESSAGE TIME setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS — If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
The figures show the user-programmable pushbutton logic.
SETTING 0 OR
PUSHBTN 1 SET
Off = 0 TIMER
50 ms Non-volatile latch
SETTING AND S
AND
0
PUSHBTN 1 REMOTE Latch
Off = 0 R
TIMER
SETTING 200 ms
PUSHBUTTON 1 OFF
0
SETTING
PUSHBTN 1 RESET AND
Off = 0
OR To user-programmable
SETTING OR PUSHBUTTON ON pushbuttons logic
SETTING sheet 2
PUSHBTN 1 AUTORST DELAY
PUSHBTN 1 AUTORST
TPKP
= Enabled
AND AND
= Disabled
5
0
TIMER
FLEXLOGIC OPERAND 200 ms OR
PUSHBUTTON 1 ON
0
SETTING
AND PUSHBTN 1 DROP-OUT TIME
0
OR
TRST
AND
842237A1.CDR
OFF MESSAGE
ENGAGE MESSAGE
SETTING
LATCHED FLASH MESSAGE TIME
SETTINGS
0 PUSHBTN ID TEXT
AND
OR TRST = XXXXXXXXXX
PUSHBTN OFF TEXT
= XXXXXXXXXX
Instantaneous
From user-programmable reset * Enhanced and standard front panels
pushbuttons logic sheet 1
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
ON MESSAGE
SETTING ENGAGE MESSAGE
PUSHBTN 1 MESSAGE
AND
= Disabled
= High Priority SETTINGS
= Normal PUSHBTN ID TEXT
= XXXXXXXXXX
OR
PUSHBTN ON TEXT
SETTING
= XXXXXXXXXX
FLASH MESSAGE TIME
0 Enhanced and standard front panels
AND
TRST The message is temporarily removed if
5
any keypad button is pressed. Ten
seconds of keypad inactivity restores
Instantaneous
Instantaneous reset is executed if any reset * the message.
front panel button is pressed or any new
target or message becomes active.
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256
state bits.
5.3.16.1 Menu
SETTINGS PRODUCT SETUP USER-DEFINABLE DISPLAYS
USER-DEFINABLE INVOKE AND SCROLL: Range: FlexLogic operand
DISPLAYS Off
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display then prompts with ADD TO USER DISPLAY LIST? After selecting “Yes,” a message
indicates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus
are automatically configured with the proper content—this content can be edited subsequently.
This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user
display. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the
start of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered
in a user display – the nth tilde (~) refers to the nth item.
A user display can be entered from the front panel keypad or the EnerVista interface (preferred for convenience). The
following procedure shows how to enter text characters in the top and bottom lines from the front panel keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key can be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the front panel
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected
system display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the
Modbus address, then manually convert it to decimal form before entering it (EnerVista usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option
to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
An example of user display setup and result is shown as follows.
USER DISPLAY 1
DISP 1 TOP LINE: Shows user-defined text with first tilde marker 5
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker
Current Y ~ A
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom
line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different.
5.3.17.1 Menu
SETTINGS PRODUCT SETUP DIRECT I/O
DIRECT I/O DIRECT OUTPUTS Range: 1 to 16 in steps of 1
DEVICE ID: 1
UNRETURNED
5 MESSAGES ALARM CH2
This option is available when an Inter-Relay Communications card is specified at the time of ordering (see the
Order Code tables). With the option, direct inputs/outputs display by default. When you enable the
teleprotection feature, direct I/O is not visible.
Direct inputs and outputs exchange status information (inputs and outputs) between UR-series relays connected directly
via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GOOSE, except that communications
takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that support two channels,
direct output messages are sent from both channels simultaneously. This effectively sends direct output messages both
ways around a ring configuration. On type 7 cards that support one channel, direct output messages are sent only in one
direction. Messages are resent (forwarded) when it is determined that the message did not originate at the receiver.
Direct Inputs and Outputs are initiated automatically and start running once at least one Direct Output in the given UR is
set to anything but Off.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are disabled, and
vice versa.
B90 supports 96 Direct I/Os at 64 or 128 kbps rate and 256 Direct I/Os at 213 kbps rate. With 64 or 128 kbps rate, the B90
can exchange Direct I/Os with other URs, while at 213 kbps B90s can exchange between each other's only. Functionality at
213 kbps is possible only with firmware 7.4 or higher and with CPU FPGA revision 2.02 or higher. The CPU FPGA version can
be confirmed in the ACTUAL VALUES > PRODUCT INFO > FIRMWARE REVISIONS > FPGA PROGRAM REVISION menu. CPU FPGA can
be upgraded in the field; see the upgrade procedures on the B90 Support Documents page of the GE Multilin web site. In
version 7.42 and later, when connected by serial cable, use Maintenance > Update FPGA Firmware.
Direct output message timing is similar to GOOSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic operands:
• DIRECT RING BREAK (direct input/output ring break). This FlexLogic operand indicates that direct output messages sent
from a UR-series relay are not being received back by the relay.
• DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic operands indicate that direct output
messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID setting, which identifies the relay in all direct output
messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of
the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages are received back. If not, the direct input/output ring break
self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel
communications cards apply the same data rate to both channels. Delivery time for direct input and output messages is
approximately 0.2 of a power system cycle at 128 or 213 kbps and 0.4 of a power system cycle at 64 kbps, per each
"bridge."
For B90 applications, the DIRECT I/O DATA RATE should be set to 128 or 213 kbps.
Table 5-16: Direct input and output data rates
Module Supported data rates
2A, 2B 64 kbps
2E, 2F 64 kbps
2G, 2H 128 kbps
2I, 2J 64 kbps, 128 kbps 5
72, 73 64 kbps, 128 kbps, 213 kbps
74, 75 64 kbps
76, 77 64 kbps
7A, 7B, 7C, 7D 64 kbps, 128 kbps, 213 kbps
7E, 7F, 7G 64 kbps
7H, 7I, 7J, 7K 64 kbps, 128 kbps, 213 kbps
7L, 7M, 7N, 7P, 7Q 64 kbps
7R, 7S 64 kbps
7T, 7W 64 kbps
The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
The DIRECT I/O CHANNEL CROSSOVER setting applies to a B90 with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputs
and Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
Figure 5-56: Input and output extension via direct inputs and outputs
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
UR IED 1 BLOCK
842712A1.CDR
For increased reliability, a dual-ring configuration (shown as follows) is recommended for this application.
Figure 5-58: Interlocking bus protection scheme via direct inputs/outputs
TX1 RX1
UR IED 1
RX2 TX2
TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR
UR IED 1 UR IED 2
UR IED 3 842713A1.CDR
A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2
constitute a first ring, while IEDs 2 and 3 constitute a second ring).
Figure 5-60: Single-channel open loop configuration
5 UR IED 3
RX1
TX1
842714A1.CDR
TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR
The B90 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter
adds up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the
CRC ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC
ALARM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT
setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions—if required—are programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES STATUS DIRECT INPUTS CRC FAIL COUNT CH1 actual value.
• Message count and length of the monitoring window — To monitor communications integrity, the relay sends 1
message per second (at 64 kbps) or 2 messages per second (at 128 kbps) or 3 messages per second (at 213 kbps) even
if there is no change in the direct outputs. For example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000,”
corresponds a time window of about 160 minutes at 64 kbps and 80 minutes at 128 kbps. If the messages are sent
faster as a result of direct outputs activity, the monitoring time interval shortens. Take this into account when
determining the CRC ALARM CH1 MESSAGE COUNT setting. For example, if the requirement is a maximum monitoring
time interval of 10 minutes at 64 kbps, then the CRC ALARM CH1 MESSAGE COUNT is set to 10 60 1 = 600.
• Correlation of failed CRC and bit error rate (BER) — The CRC check can fail if one or more bits in a packet are
corrupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain
assumptions an approximation can be made as follows. A direct input and output packet containing 20 bytes results
in 160 bits of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4
implies 1 bit error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet,
having 1 failed packet for every 63 received is about equal to a BER of 10–4.
The B90 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of
unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have
failed to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS
ALARM CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1
UNRET ALM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions, if required, are programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES STATUS DIRECT INPUTS
UNRETURNED MSG COUNT CH1 actual value.
5.3.18 Installation
SETTINGS PRODUCT SETUP INSTALLATION
INSTALLATION RELAY SETTINGS: Range: Not Programmed, Programmed
Not Programmed
RELAY SETTINGS — To safeguard against the installation of a relay without any entered settings, the unit does not allow
signaling of any output relay until RELAY SETTINGS is set to "Programmed." This setting is "Not Programmed" by default. The
UNIT NOT PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
RELAY NAME — This setting allows the user to uniquely identify a relay. This name appears on generated reports.
CT F1 SECONDARY: Range: 1 A, 5 A
1A
This menu configures the AC current inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis
and populates the above menu accordingly.
The current terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (1, 2,..., 8}. X represents the chassis
slot containing the AC input module and a represents the AC channel of each module. For example, a B90 unit containing
the F8H and L8K modules displays the following current inputs for configuration: F1, F2, F3, F4, F5, F6, F7, F8, L1, L2, L3, L4,
L5, L6, and L7. 5
5.4.1.2 Voltage terminals
SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE TERMINAL F1(S8)
VOLTAGE VT F1 SECONDARY: Range: 50.0 to 240.0 V in steps of 0.1
TERMINAL F1 66.4 V
This menu configures the AC voltage inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis
and populates the above menu accordingly.
The voltage terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (5, 6, 7, 8}. X represents the chassis
slot containing the AC input module and a represents the AC channel of each module. For example, a B90 unit containing
the F8F and L8K modules displays the following voltage inputs: F5, F6, F7, F8, and L8.
The nominal VT F1 SECONDARY setting is the voltage across the relay input terminals when nominal voltage is
applied to the VT primary.
NOMINAL FREQUENCY — Used as a default to set the digital sampling rate if the system frequency cannot be measured from
available signals. This can happen if the signals are not present or are heavily distorted. Before reverting to the nominal
frequency, the frequency tracking algorithm holds the last valid frequency measurement for a safe period of time while
waiting for the signals to reappear or for the distortions to decay.
FREQUENCY AND PHASE REFERENCE — Determines which AC signal is used for phase angle reference.
The phase reference and frequency tracking AC signals are selected based upon the configuration, regardless of whether
or not a particular signal is actually applied to the relay.
Phase angle of the reference signal always displays zero degrees and all other phase angles are relative to this signal. If the
pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of time tagging in the event recorder between
different UR-series relays, provided that the relays have an IRIG-B connection.
FREQUENCY TRACKING — Set to Disabled only in very unusual circumstances; consult the factory for special variable-
frequency applications.
5.4.3 FlexCurves
5.4.3.1 Settings
SETTINGS SYSTEM SETUP FLEXCURVES FLEXCURE A(D)
5 FLEXCURVE A
FLEXCURVE A TIME AT
0.00 xPKP: 0 ms
Range: 0 to 65535 ms in steps of 1
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter
a custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE up/down keys) for the required protection curve (A, B, C, or D).
Addr: Adds the time specified in this field (in ms) to each
curve operating time value.
The Multiplier and Adder settings only affect the curve portion of the characteristic and not the MRT and HCT
settings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
5.4.3.4 Example
5 A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight times pickup with an operating time of 30 ms. At approximately four times pickup, the curve operating
time is equal to the MRT and from then onwards the operating time remains at 200 ms.
Figure 5-63: Composite recloser curve with HCT disabled
842719A1.CDR
With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup.
842720A1.CDR
Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If
this is attempted, the EnerVista software generates an error message and discards the proposed changes.
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
50
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
5
Figure 5-67: Recloser curves GE134, GE137, GE140, GE151, and GE201
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
5
Figure 5-69: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5-70: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
5
Figure 5-71: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
5
5.4.4 Bus
SETTINGS SYSTEM SETUP BUS BUS ZONE 1(6) BUS ZONE 1(6) INPUT A(X)
BUS ZONE 1 INPUT A BUS 1A CT: Range: available CT channels
F1
The number of available zones and their size (maximum number of inputs) are optional and controlled by the
software option portion of the order code. See the Order Codes section in chapter 2 for information on the
maximum number of zones and inputs for a given B90 model.
Six bus differential zones are available. Each zone is associated with its own bus differential protection and CT trouble
monitoring elements. A differential zone is defined by up to 24 pairs (inputs A to X) of current input–bus connection status
values.
BUS 1A CT — This setting defines a current input to the zone. Selections include all the CT channels available in the relay as
per configured hardware. The protected bus zone is uniquely identified as the portion of the bus between the selected
current sources (CTs).
BUS 1A DIRECTION — This setting configures the CT orientation with respect to the protected zone. Bus differential and CT
trouble decisions are based on current summation and thus correct orientation selection is important. The following figure
shows a tie-breaker dividing a single bus into two sections, defined as zone 1 and zone 2. The tie-breaker CT (F5) is
common to both zones and therefore the respective direction settings are opposite. The CT polarity dots are in relation to
the protected zone and are terminated to the “common” of the tapped (1 A / 5 A) inputs. The polarity dots for the zone 2 CTs
face outward with respect to the bus; as such, the F5 to F8 direction settings are “IN”. Similarly, the F1 to F4 CTs for zone 1
are selected as “IN.” However, the polarity dot orientation for the F5 CT faces inward with respect to zone 1 and therefore
the BUS 1E DIRECTION setting is “OUT.”
BUS 1A STATUS — This setting dynamically defines a connection status of a given feeder with respect to the differential zone
(dynamic bus replica). If a given feeder is connected to the zone and its current included into differential calculations, the
FlexLogic operand used for this setting is “On.” If the current is excluded, the FlexLogic operand is “Off.” Typically, this
setting is an appropriately filtered position of an isolator, a breaker, or a tie-breaker.
In the case of an isolator connecting a feeder to a given section of a bus, the isolator monitoring feature produces a
reliable isolator position operand (ISOLATOR 1 POSITION). Typically, the isolator monitoring feature is enabled in the fourth
B90 IED and the ISOLATOR 1 POSITION status operand must be sent over direct input/output communications before it can
be configured as a BUS ZONE 1A(X) STATUS setting.
Figure 5-73: Bus zone direction setting
ZONE 1 F5 ZONE 2
F1 F2 F3 F4 F6 F7 F8
ZONE 1: ZONE 2:
BUS 1A CT = F1 BUS 2A CT = F5
BUS 1A DIRECTION = IN BUS 2A DIRECTION = IN
BUS 1B CT = F2 BUS 2B CT = F6
BUS 1B DIRECTION = IN BUS 2B DIRECTION = IN
BUS 1C CT = F3 BUS 2C CT = F7
BUS 1C DIRECTION = IN BUS 2C DIRECTION = IN
BUS 1D CT = F4 BUS 2D CT = F8
BUS 1D DIRECTION = IN BUS 2D DIRECTION = IN
5
BUS 1E CT = F5
BUS 1E DIRECTION = OUT
836757A2.CDR
For example, assume that B90 IED 4 is used for isolator monitoring while IEDs 1, 2, and 3 are used for protection.
Consequently, the B90 FUNCTION setting of IED 4 must be set to “Logic” while B90 FUNCTION on the IEDs 1, 2 and 3 must be
set to “Protection.” Normally open and closed auxiliary switches of a given isolator must be wired to the IED 4, and the
Isolator feature must be enabled and configured appropriately.
Assume that the isolator shown as follows is monitored by the Isolator 1 feature. The ISOLATOR 1 POSITION is the FlexLogic
operand asserted by the isolator 1 monitoring element. This operand must be configured to drive a direct output in order
to send the connection status to IEDs 1, 2, and 3 where the bus replica is being utilized by differential protection. Assume
bit 12 of the message originating at IED 4 is used for this purpose. This is achieved by applying the following settings:
For IED 4:
DIRECT OUTPUT DEVICE ID: “4” (this is the originating device)
DIRECT OUT 12 OPERAND: “ISOLATOR 1 POSITION” (this operand drives output number 12)
The above information is to be received by IEDs 1, 2, and 3. Assume direct input 68 is to reflect the isolator position.
For IEDs 1, 2, and 3:
DIRECT INPUT 68 DEVICE: “4” (message received from IED 4)
DIRECT INPUT 68 BIT NUMBER: “12” (using bit number 12)
Once received, the isolator 1 status (known on IEDs 1, 2, and 3 as DIRECT INPUT 68 On) is used for bus configuration.
For IEDs 1, 2, and 3:
BUS 1E CT: “F7” (the current wired to the F7 terminal)
BUS 1E STATUS: “DIRECT INPUT 68 On”
Figure 5-74: Direct input and output sample configuration for dynamic bus replica
ZONE 2
ZONE 1
IED 3
phase C current, wired to F7
Received as DIRECT
INPUT 68 On
BUS 1E CT = F7
BUS 1E STATUS = DIRECT INPUT 68 On
836758A2.CDR
In the case of a breaker (or a tie-breaker), a breaker closed position with a dropout time of 40 to 60 ms is typically used as
a connection status to avoid over-tripping or dead zones, depending on the relative position of the breaker and CT. See the
Application of Settings chapter for details on configuring bus differential zones. 5
5.5 FlexLogic
5.5.1 FlexLogic operands
For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.
CTs DSP
VTs (A/D) FlexLogic™ Virtual
equations outputs
Calculate
DCmA parameters Measuring
Analog and
or
input decision Digital Flags
RTD
(A/D) elements elements
inputs
V I
Contact Form-A and
inputs FlexLogic™ SCR only
Block counters
operation Contact
(each outputs
element)
Keypad
Virtual Remote
inputs (FlexLogic operands) outputs
OR
Remote Display
inputs Control and LEDs
(GOOSE) and Display
monitoring
features
fiber Analog
Direct output (D/A)
G.703 inputs
RS422 (dcmA)
5 (Status) Direct
outputs
Fiber
G.703
RS422
(Actual values) (Status)
827022A7.cdr
The states of all digital signals used in the B90 are represented by flags (or FlexLogic operands, which are described later in
this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an
element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output. The state
of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple
scheme where a contact input is used to block an element is wanted, this selection is made when programming the
element. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes,
and human operators.
If more complex logic than shown in the figure is required, it is implemented via FlexLogic. For example, to have the closed
state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase
time overcurrent element, the two control input states are programmed in a FlexLogic equation. This equation ANDs the
two control inputs to produce a virtual output that is then selected when programming the phase time overcurrent to be
used as a blocking input. Virtual outputs can only be created by FlexLogic equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or
supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the requirement for
auxiliary components and wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes, and outputs is field-programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is
available internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes, and outputs. The operators are logic gates, timers, and latches (with
set and reset inputs). A system of sequential operations allows any combination of operands to be assigned as inputs to
specified operators to create an output. The final output of an equation is a numbered register called a virtual output.
Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of
parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, or flag set) or 0
(=OFF, or flag not set). Each equation is evaluated at least four times every power system cycle.
Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the front panel display. The table lists characteristics
of the different types of operands.
Table 5-18: B90 FlexLogic operand types
Operand type State Example of format Characteristics
[Input Is ‘1’ (= ON) if...]
Contact Input On Cont Ip On Voltage is applied presently to the input (external contact
closed)
Off Cont Ip Off Voltage is not applied presently to the input (external
contact open)
Contact Output Contact Closed Cont Op 1 Closed Contact output is closed
(type Form-A contact
Current On Cont Op 1 Ion Current is flowing through the contact
only)
Voltage On Cont Op 1 VOn Voltage exists across the contact
Voltage Off Cont Op 1 VOff Voltage does not exist across the contact
Direct Input On DIRECT INPUT 1 On The direct input is presently in the ON state
Element Pickup PHASE TOC1 PKP The tested parameter is presently above the pickup setting
(Analog) of an element that responds to rising values or below the
pickup setting of an element that responds to falling values
5
Dropout PHASE TOC1 DPO This operand is the logical inverse of the above PKP
operand
Operate PHASE TOC1 OP The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing
Block PHASE TOC1 BLK The output of the comparator is set to the block function
Element Pickup Dig Element 1 PKP The input operand is at logic 1
(Digital)
Dropout Dig Element 1 DPO This operand is the logical inverse of the above PKP
operand
Operate Dig Element 1 OP The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing
Fixed On On Logic 1
Off Off Logic 0
RxGOOSE Boolean On RxGOOSE Boolean 1 On The RxGOOSE Boolean is presently in the ON state
Virtual Input On Virt Ip 1 On The virtual input is presently in the ON state
Virtual Output On Virt Op 1 On The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
Table 5-19: B90 FlexLogic operands
Operand type Operand syntax Operand description
ANNUNCIATOR ANY ANCTR ABNORMAL On for one second when any annunciator window state changes from
Graphical front panel normal to abnormal
ANY ANCTR ALARMED On while any annunciator window state is abnormal
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-20: FlexLogic gate characteristics
Gates Number of inputs Output is ‘1’ (= ON) if...
NOT 1 input is ‘0’
OR 2 to 16 any input is ‘1’
AND 2 to 16 all inputs are ‘1’
NOR 2 to 16 all inputs are ‘0’
5 NAND
XOR
2 to 16
2
any input is ‘0’
only one input is ‘1’
FlexLogic provides built-in latches that by definition have a memory action, remaining in the set state after the set
input has been asserted. These built-in latches are reset dominant, meaning that if logical "1" is applied to both set
and reset entries simultaneously, then the output of the latch is logical "0." However, they are volatile, meaning that
they reset upon removal of control power.
When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any
new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically.
To implement FlexLogic using a graphical user interface, see the FlexLogic Design and Monitoring using Engineer
section in the previous chapter.
5 Virtual output 2
state = On
Set
Latch
Virtual input 1 OR #1 Reset
state = On
XOR
Digital element 1 Timer 2
state = Pickup Time Delay Operate output
OR #2
on dropout relay H1
Digital element 2 Timer 1
(200 ms)
state = Operated Time delay
AND on pickup
(800 ms)
Contact input H1c
state = Closed 827025A2.CDR
1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic
operators. If this is not possible, the logic must be altered until this condition is satisfied. Once done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If
the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25
inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs
from these two gates to AND(2).
Inspect each operator between the initial operands and final virtual outputs to determine if the output from the
operator is used as an input to more than one following operator. If so, the operator output must be assigned as a
virtual output.
For the example shown, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must therefore
be made a virtual output and assigned the next available number (that is, Virtual Output 3). The final output must also
be assigned to a virtual output as virtual output 4, which is programmed in the contact output section to operate relay
H1 (that is, contact output H1).
Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and
virtual output 4, shown as follows.
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
Digital element 1 OR #2 Virtual output 4
on dropout
state = Pickup
(200 ms)
827026A2.CDR
2. Prepare a logic diagram for the equation to produce virtual output 3, as this output is used as an operand in the virtual
output 4 equation (create the equation for every output that is used as an operand first, so that when these operands
are required they already have been evaluated and assigned to a specific virtual output). The logic for virtual output 3
is shown as follows with the final output assigned.
Figure 5-78: Logic for virtual output 3
Digital element 2 5
state= Operated
3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as
virtual output 3, shown as follows.
Figure 5-79: Logic for virtual output 4
Virtual output 1
state = On
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
OR #2 Virtual output 4
Digital element 1 on dropout
state = Pickup
(200 ms)
Timer 1
Virtual output 3 Time delay
state = On on pickup
(800 ms)
Contact input H1c
state = Closed
827028A2.CDR
4. Program the FlexLogic equation for virtual output 3 by translating the logic into available FlexLogic parameters. The
equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the
output end of the equation and work back towards the input, as shown in the following steps. It is also recommended
to list operator inputs from bottom to top. For demonstration, the final outputs are arbitrarily identified as parameter
99, and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic, it is suggested
that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared shown as follows.
Figure 5-80: FlexLogic worksheet
01
02
03
04
05
.....
97
98
99
827029A1.VSD
5 – 98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a
2-input AND so the parameter is “AND(2)”. Note that FlexLogic rules require that the number of inputs to most
types of operators must be specified to identify the operands for the gate. As the 2-input AND operates on the
two operands preceding it, these inputs must be specified, starting with the lower.
– 97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next
parameter is “NOT”. The NOT operator acts upon the operand immediately preceding it, so specify the inverter
input next.
– 96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to
be set when the contact is either open or closed. Assume for this example that the state is to be ON for a closed
contact. The operand is therefore “Cont Ip H1c On”.
– 95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital
element 2. This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order forms the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters produces the required logic by converting the set of
parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for
virtual output 3 diagram as a check.
6. Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4.
– 99: The final output of the equation is virtual output 4, which is parameter “= Virt Op 4".
– 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for
the timer are established in the timer programming section.
– 97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
– 96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
– 95: The center input to OR #2 is operand “TIMER 1".
– 94: The input to timer 1 is operand “Virt Op 3 On".
– 93: The upper input to OR #2 is operand “LATCH (S,R)”.
– 92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR,
which is parameter “OR(4)”.
– 91: The lowest input to OR #1 is operand “Virt Op 3 On".
– 90: The input just above the lowest input to OR #1 is operand “XOR(2)”. 5
– 89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
– 88: The upper input to the XOR is operand “Virt Ip 1 On".
– 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
– 86: The upper input to OR #1 is operand “Virt Op 1 On".
– 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
Now check that the selection of parameters produce the required logic by converting the set of parameters into a
logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check.
5 7. Now write the complete FlexLogic expression required to implement the logic, making an effort to assemble the
equation in an order where Virtual Outputs that are used as inputs to operators are created before needed. In cases
where a lot of processing is required to perform logic, this can be difficult to achieve, but in most cases does not cause
problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by
sequential processing emphasizes the necessity to test the performance of FlexLogic before it is placed in service.
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the following
order:
DIG ELEM 2 OP
Cont Ip H1c On
NOT
AND(2)
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In this expression, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of
feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE — Selects the time measurement unit.
TIMER 1 PICKUP DELAY — Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY — Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
The non-volatile latches provide a permanent logical flag that is stored safely and do not reset upon restart after the relay
is powered down. Typical applications include sustaining operator commands or permanently blocking relay functions,
such as Autorecloser, until a deliberate interface action resets the latch.
LATCH 1 TYPE — This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET — If asserted, the specified FlexLogic operands 'sets' Latch 1.
LATCH 1 RESET — If asserted, the specified FlexLogic operand 'resets' Latch 1.
Enabled=1 RUN
SETTING
LATCH 1 SET:
FLEXLOGIC OPERANDS
Off=0 SET LATCH 1 ON
LATCH 1 OFF
SETTING
LATCH 1 RESET:
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
Up to six zones of bus differential protection are provided, depending on the software options. The operation of these
elements is completely dependent on the dynamic bus replica, which must be defined first. Both restrained (biased) and
unrestrained (unbiased, instantaneous) bus differential protection functions are provided for each bus differential zone.
The biased bus differential function has a dual-slope operating characteristic (see figure below) operating in conjunction
with saturation detection and a directional comparison principle (see the logic diagram in this section).
|Id|
differential
OPERATE
HIGH
SLOPE
BLOCK
LOW SLOPE Ir
PICKUP
HIGH BPNT
LOW BPNT
restraining
836720A1.cdr
The protected zone input current with the highest magnitude is used as the restraining signal. Stability during heavy
external faults is achieved by dynamic CT saturation detection and current flow direction supervision without affecting
sensitivity and speed of operation for internal faults.
The differential operating characteristic is divided into two regions. In the region of low differential currents and lower
5 slope, the element operates on a 2-out-of-2 basis, applying both the differential and current directional tests. In the region
of high differential currents, the element operates on a dynamic 1-out-of-2 / 2-out-of-2 basis. If the differential current is in
this region and CT saturation is detected, both the differential and current directional tests are applied. If CT saturation is
ruled out by the saturation detector, the differential protection principle alone is capable of causing the element to
operate.
The saturation detector is an integral part of the bus differential element. It has no settings but uses some of the
differential characteristic parameters. The flags indicating CT saturation are available on a per phase basis as FlexLogic
operands.
The directional principle is an integral part of the biased bus differential element and has no associated settings. The
directional element dynamically identifies what appears to be the faulted circuit and compares its current angle with that
of the sum of the remaining currents of the protected zone. The element declares a bus fault if the angle is less than 90°.
Directional indicating flags signal operation on a per-phase basis and are available as FlexLogic operands.
The unbiased bus differential function checks the magnitude of the differential current against an adjustable threshold.
Neither the bias nor the directional principles apply. The operation of the unbiased differential function is associated with
separate output operands.
The bus differential protection feature is available only when PRODUCT SETUP B90 FUNCTION B90 FUNCTION is set to
“Protection”.
Operation of this element is completely dependent on the dynamic bus replica which must be first defined under bus zone
1. The bus differential element 1 protects the differential zone defined as bus zone 1.
BUS ZONE 1 DIF PICKUP — This setting defines the minimum differential current required for operation of the biased bus
differential protection element. This setting is chosen based on the maximum magnitude of the differential current that
might be seen under no-load conditions. This setting prevents relay maloperation in the situation when the bus carries
little power and the restraining signal is too low to provide enough bias in the first slope region of the differential
characteristic.
This setting can also be set above the maximum load level to ensure security during CT trouble conditions. However,
voltage supervision or a check-zone are better alternatives.
BUS ZONE 1 DIF LOW SLOPE — This setting defines the percentage bias for the restraining currents, from zero to the lower
breakpoint (LOW BPNT). This setting determines the sensitivity of the relay for low current internal faults. The value chosen
needs to be high enough to accommodate the spurious differential current resulting from inaccuracy of the CTs operating
in their linear mode, i.e. in load conditions and during distant external faults. When adjusting this setting, it must be kept in
mind that the restraining signal used by the biased bus differential protection element is created as the maximum of all the
input currents.
BUS ZONE 1 DIF LOW BPNT — This setting defines the lower breakpoint of the dual-slope operating characteristic. The
percentage bias applied for the restraining current from zero to the value specified as LOW BPNT is given by the LOW SLOPE
setting. This setting needs to be set above the maximum load current. The LOW BPNT can be moved to the AC current
under which all the CTs are guaranteed to transform without saturation. This includes the effect of residual magnetism.
When adjusting this setting, keep in mind that the restraining signal is created as the maximum of all the input currents.
BUS ZONE 1 DIF HIGH SLOPE — This setting defines the percentage bias for the restraining currents above the higher
breakpoint (HIGH BPNT). This setting affects stability of the relay for heavy external faults. Traditionally, the value chosen for
this setting needs to be high enough to accommodate the spurious differential current resulting from saturation of the CTs
during heavy external faults. This requirement can be considerably relaxed in favor of sensitivity and speed of operation as
the relay detects CT saturation and upon detection applies the directional principle to prevent maloperation. When
adjusting this setting, keep in mind that the restraining signal is created as the maximum of all the input currents.
BUS ZONE 1 DIF HIGH BPNT — This setting defines the higher breakpoint of the dual-slope operating characteristic. The
percentage bias applied for the restraining current above the value specified as HIGH BPNT is given by the HIGH SLOPE
setting. The HIGH BPNT setting needs to be set below the minimum AC current that is likely to saturate the weakest CT
feeding the relay. When adjusting this setting, it must be kept in that mind the restraining signal is created as the
maximum of all the input currents.
The dual-slope operating characteristic of the biased bus differential protection element is shaped to ensure true
percentage bias for high restraining currents (see the following figure). This means that the straight line defining the upper
slope intersects the origin of the differential-restraining plane and a discontinuity appears between the low and high slope
regions (between the LOW BPNT and HIGH BPNT settings). This discontinuity is handled by approximating the operate/no-
5
operate boundary of the characteristic using a certain “gluing” function. This ensures smooth transition of the slope from
LOW SLOPE (lower value) to HIGH SLOPE (higher value).
The following parameters of the biased operating characteristic are used by the saturation detector: LOW SLOPE, HIGH
SLOPE, and HIGH BPNT. The saturation detector uses these settings to detect specific relations between the differential and
restraining currents. The values of these settings are selected based on the aforementioned criteria related to the art of
bus differential protection.
BUS ZONE 1 DIF HIGH SET — This setting defines the minimum differential current required for operation of the unbiased bus
differential protection function. This setting is based on the maximum magnitude of the differential current that might be
seen during heavy external faults causing deep CT saturation. When selecting this setting, keep in mind that the unbiased
bus differential protection function uses the full-cycle Fourier measuring algorithm and applies it to pre-filtered samples of
the input currents. As a result, the transient measuring errors including the effect of the DC component are below 2%.
During heavy CT saturation when the currents are significantly distorted, the magnitude of the differential current as
measured by the relay and used by the unbiased bus differential function is significantly lower than both the peak values
of the waveform and the true RMS value. The measured magnitude practically reflects the power system frequency
component alone. This allows for lower values of the HIGH SET setting.
The unbiased (high set) differential function can be virtually disabled by setting its operating threshold, HIGH SET, very high.
BUS ZONE 1 DIF SEAL-IN — This setting defines the drop-out time of the seal-in timer applied to the BUS 1 OP FlexLogic
operand.
BUS ZONE 1 DIFF SUPV — This setting specifies a FlexLogic operand that supervises operation of the element. Typical
applications include undervoltage condition and overall (check) zone. In a sense the setting is similar to the blocking input,
but does not stop the element from running. This is important for saturation detector, as the latter requires some historical
data. The Bus Differential element shall not be supervised from the blocking input. The blocking input (BUS ZONE 1 DIF BLK
setting) is meant to block the element permanently, not dynamically from a fault depended condition such as
undervoltage.
BUS ZONE 1 DIF TRIP — This setting specifies a FlexLogic operand that forces operation of the zone. Typical applications
include forced trip of the healthy phase from the faulted phase, or a trip command from the BF function to isolate the
entire zone of busbar protection.
More information on the bus zone differential settings can be found in the Application of Settings chapter.
AND
SETTING
SETTING BUS ZONE 1 DIF SUPV:
SETTINGS
BUS ZONE 1 DIF SETTING
BUS ZONE 1 DIF On = 1
BLOCK: BUS ZONE 1 DIF SEAL-IN:
PICKUP:
FLEXLOGIC OPERAND
Off = 0
BUS ZONE 1 DIF SETTING 0 BUS 1 OP
AND
LOW SLOPE: tRST
SETTING BUS ZONE 1 DIF TRIP:
BUS ZONE 1 DIF
BUS 1A CT: LOW BPNT: Off = 0
OR
Current Phasor BUS ZONE 1 DIF
HIGH SLOPE:
Current Samples
BUS ZONE 1 DIF
HIGH BPNT:
SETTING
RUN
BUS 1A STATUS:
Off = 0
ID1
differential
... FLEXLOGIC OPERAND
restraining
BUS 1 BIASED OP
OR
SETTING
BUS 1X CT:
OR
AND
Current Phasor
Current Samples
differential
IR1
FLEXLOGIC OPERANDS
Figure 5-85: Bus zone 1 differential logic
FLEXLOGIC OPERANDS
SATURATION
BUS 1 SAT
DETECTOR
836001A3.vsd
5-161
GROUPED ELEMENTS
5
GROUPED ELEMENTS CHAPTER 5: SETTINGS
BREAKER FAILURE
CURRENT SUPV 1
BREAKER FAILURE 1
BF1 TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled 5
BF1 EVENTS: Range: Enabled, Disabled
Disabled
BREAKER FAILURE
CURRENT SUPV 2
BREAKER FAILURE 2
BREAKER FAILURE
CURRENT SUPV 24
BREAKER FAILURE 24
The breaker failure feature has two parts: breaker failure current supervision and breaker failure logic. Breaker failure
current supervision acts upon current levels and is available if the PRODUCT SETUP B90 FUNCTION B90 FUNCTION setting
is “Protection.” Breaker failure logic is based on status information and is available if the PRODUCT SETUP B90 FUNCTION
B90 FUNCTION setting is “Logic.” The Breaker failure element requires B90 fiber optic interconnection and proper
configuration of the breaker failure and direct input/output settings. See the Application of Settings chapter for details.
The Breaker Failure can be used with single-pole tripping schemes if the HISET and LOSET current elements are set
below the lowest expected fault current and above the highest expected load current.
BF1 AMP LOSET PICKUP — This setting is used to set the phase current fault detection level. Generally this setting detects the
lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted approximately 90% of
resistor current).
Figure 5-86: Breaker failure current supervision logic
SETTING
B90 FUNCTION:
Protection = 1
Logic = 0
SETTING
BF 1 AMP SUPV
SETTING PICKUP:
FLEXLOGIC OPERAND
AND RUN
BF 1 CURRENT SUPV
FUNCTION: I ³ PKP BKRSUPV 1 SUP OP
Disabled = 0
Enabled = 1 SETTING
BF 1 AMP HISET
PICKUP:
FLEXLOGIC OPERAND
RUN
I ³ PKP BKRSUPV 1 HISET OP
SETTING
SETTING
5
BF 1 AMP LOSET
PICKUP: FLEXLOGIC OPERAND
BF 1 CT:
RUN
I ³ PKP BKRSUPV 2 LOSET OP
F1
836740A4.cdr
B90 FUNCTION:
Protection = 1
Logic = 0
SETTING
BF 1
FUNCTION:
Disabled = 0
Enabled = 1 AND
SETTING
BF 1 BLOCK:
Off = 0
SETTING
BF 1 INITIATE: SETTING
BF 1 RETRIP FLEXLOGIC OPERAND
Off = 0 TIME DELAY:
AND 0 BKRFAIL 1 RETRIP
SETTING
OR
BF 1 USE SEAL-IN:
YES = 1 / NO = 0
AND
YES = 1 / NO = 0
SETTING
BF 1 AMP SUPV OP A: OR
Off = 0
BF 1 AMP SUPV OP B:
Off = 0 OR
BF 1 AMP SUPV OP C:
Off = 0
5
SETTING
BF 1 USE TIMER 1:
SETTING FLEXLOGIC OPERAND
YES = 1 / NO = 0 BF 1 TIMER1 PICKUP
DELAY: BKRFAIL 1 T1 OP
SETTING AND 0
BF 1 BKR POS1:
Off = 0
OR
SETTING
SETTING BF 1 TIMER2 PICKUP
BF 1 USE TIMER 2: DELAY:
FLEXLOGIC OPERAND
AND 0
YES = 1 / NO = 0 BKRFAIL 1 T2 OP
SETTING
BF 1 AMP HISET OP A:
Off = 0
BF 1 AMP HISET OP B: AND
Off = 0 OR
BF 1 AMP HISET OP C:
Off = 0
SETTING
BF 1 LOSET TIME
SETTING DELAY:
BF 1 AMP LOSET OP A:
0
Off = 0
BF 1 AMP LOSET OP B: AND
Off = 0 OR
SETTING
BF 1 AMP LOSET OP C:
BF 1 TRIP DROPOUT
Off = 0 FLEXLOGIC OPERAND
TIME DELAY:
OR 0 BKRFAIL 1 TRIP OP
SETTING
BF 1 USE TIMER 3:
YES = 1 / NO = 0
SETTING SETTING
BF 1 TIMER 3 PICKUP
BF 1 BKR POS2: DELAY:
AND 0 FLEXLOGIC OPERAND
Off = 0
BKRFAIL 1 T3 OP
SETTING
BF 1 BKR TEST ON:
Off = 0
836739A4.cdr
Received as DIRECT
INPUTs 1 through 9
breaker auxiliary switches
(if used for BF) IED 4
IED 3
phase C current, wired to F7
BKR FAIL SUPV OP
BKR FAIL HISET OP
BF CT = F7 BKR FAIL LOSET OP
836759A3.CDR
The Protection IEDs 1, 2, and 3 (B90 FUNCTION set to "Protection") send the Breaker Fail current supervision flags over the
Direct I/O communications. Assume bits 13, 14, and 15 are used for this purpose as follows:
5 For IED 1:
DIRECT OUTPUT DEVICE ID: "1" (this is an originating device)
DIRECT OUT 13 OPERAND: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
For IED 2:
DIRECT OUTPUT DEVICE ID: "2" (this is an originating device)
DIRECT OUT 13 OPERAND: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
For IED 3:
DIRECT OUTPUT DEVICE ID: "3" (this is an originating device)
DIRECT OUT 13 OPERAND: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
The above nine flags must be received at the IED 4. Assume Direct Inputs 1 through 9 are to be used for this purpose. This
is accomplished with the following settings.
For IED 4:
DIRECT INPUT 1 DEVICE: "1" (message received from IED 1)
DIRECT INPUT 1 BIT NUMBER: "13" (this is BKRSUPV 3 SUPV OP for Phase A)
DIRECT INPUT 2 DEVICE: "1" (message received from IED 1)
DIRECT INPUT 2 BIT NUMBER: "14" (this is BKRSUPV 3 HISET OP for Phase A)
DIRECT INPUT 3 DEVICE: "1" (message received from IED 1)
DIRECT INPUT 3 BIT NUMBER: "15" (this is BKRSUPV 3 LOSET OP for Phase A)
DIRECT INPUT 4 DEVICE: "2" (message received from IED 2)
DIRECT INPUT 4 BIT NUMBER: "13" (this is BKRSUPV 3 SUPV OP for Phase B)
DIRECT INPUT 5 DEVICE: "2" (message received from IED 2)
DIRECT INPUT 5 BIT NUMBER: "14" (this is BKRSUPV 3 HISET OP for Phase B)
0.8
Margin
Maximum
5
Breaker failure reset time (cycles)
Average
0.6
0.4
0.2
0
0 20 40 60 80 100 120 140
MulWLple of pickup fault current
threshold setting 836769A4.CDR
As the overcurrent supervising flags must be sent via Direct I/Os to the B90 IEDs that perform the BF functionality, an extra
delay is introduced. Consequently, the following is recommended for coordinating the BF time:
Total BF Reset Time = 0.7 of a power cycle + 0.2 of a power cycle x Direct I/O bridge count Eq. 5-3
where
0.7 of a power cycle = the reset of the BF overcurrent elements
Direct I/O bridge count = the number of "bridges" between the source and destination of the Direct I/O messages
(Direct I/O delay)
For example, in the four-IED application example shown earlier, IED 2 is two "bridges" away from IED 4; therefore, the Total
BF Reset Time is 0.7 + 2 x 0.2 = 1.1 of a power system cycle.
Total BF Reset Time = 0.7 of a power cycle + 0.2 of a power cycle x Direct I/O bridge count
= 0.7 + 2 x 0.2 = 1.1 of a power cycle Eq. 5-4
Note that a message delivery time of 0.2 of a cycle per "bridge" applies when the DIRECT I/O DATA RATE is set to 128 kbps.
The relay uses sophisticated algorithms to speed up the reset time of the breaker failure overcurrent supervision.
Caution must be paid when testing the B90 for BF reset times. In particular, the current must be interrupted in a
way resembling the actual breaker operation (zero-crossing).
5.6.5.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTS
VOLTAGE ELEMENTS UNDERVOLTAGE 1 See below
UNDERVOLTAGE 12
The undervoltage element supervises (low-voltage check) current based main protection (that is, differential, breaker
failure, end fault, and time overcurrent backup protection). The B90 accepts phase-to-ground or phase-to-phase voltage
input configurations. If the intention is to operate all three phases for any one phase voltage collapse, appropriate
FlexLogic operand exchanges must occur between the B90s using fiber optic communications (direct inputs and outputs).
The undervoltage element also accepts the neutral voltage (3V0) from an open-corner delta VT arrangement. In this case,
the FlexLogic output is inverted to accomplish the 3V0 overvoltage functionality.
Application of the Undervoltage element is beneficial during CT trouble conditions. A low-voltage check prevents
maloperation of the main protection until the CT trouble element (differential current alarm) operates. The CT Trouble
element is user-configurable to block selected protection functions indefinitely. Voltage supervision alone does not
guarantee security because a CT trouble may be followed by an external fault causing a low-voltage condition.
Voltage pickup is set in per-unit values. The nominal voltage as entered in the SYSTEM SETUP AC INPUTS VOLTAGE BANK
## VT ## SECONDARY setting corresponds to 1 pu. The minimum voltage setting (UNDERVOLTAGE 1 MIN VOLTAGE)
specifies the minimum voltage required for element operation. This setting discriminates between undervoltage conditions
for energized and de-energized circuits. If the element is used for low-voltage supervision, set this value to 0.004.
The Undervoltage element is enabled only when PRODUCT SETUP B90 FUNCTION B90 FUNCTION is set to “Protection”.
One element is available per each voltage input of the relay.
Figure 5-90: Undervoltage logic
SETTING
B90 FUNCTION:
Logic = 0
Protection = 1
SETTING
UNDERVOLTAGE 1
FUNCTION:
Disabled = 0
AND
Enabled = 1
UNDERVOLTAGE 1 PKP
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed.” The
“Instantaneous” selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the
relay must coordinate with electromechanical relays.
IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse curves. The IEEE curves are derived from the operate and reset time equations.
Eq. 5-5
where
T = operate time (in seconds)
TDM = Multiplier setting
5 I = input current
Ipickup = Pickup Current setting
A, B, p = constants defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
tr = characteristic constant defined in the table
Table 5-23: IEEE inverse time curve constants
IEEE curve shape A B p tr
IEEE Extremely Inverse 28.2 0.1217 2.0000 29.1
IEEE Very Inverse 19.61 0.491 2.0000 21.6
IEEE Moderately Inverse 0.0515 0.1140 0.02000 4.85
IEC curves
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The IEC curves are derived by the operate and reset time
equations.
Eq. 5-6
5
where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
Ipickup = Pickup Current setting
K, E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-25: IEC (BS) inverse time curve constants
IEC (BS) curve shape K E tr
IEC Curve A (BS142) 0.140 0.020 9.7
IEC Curve B (BS142) 13.500 1.000 43.2
IEC Curve C (BS142) 80.000 2.000 58.2
IEC Short Inverse 0.050 0.040 0.500
5 0.10
0.20
0.306
0.612
0.178
0.356
0.111
0.223
0.088
0.175
0.075
0.150
0.067
0.135
0.062
0.124
0.058
0.115
0.054
0.109
0.052
0.104
0.40 1.223 0.711 0.445 0.351 0.301 0.269 0.247 0.231 0.218 0.207
0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311
0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415
1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518
IAC curves
The curves for the General Electric type IAC relay family are derived from the formulae:
Eq. 5-7
where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input current
Ipkp = Pickup Current setting
A to E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-27: GE type IAC inverse time curve constants
IAC curve shape A B C D E tr
IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse 0.0900 0.7955 0.1000 –1.2885 7.9586 4.678
IAC Inverse 0.2078 0.8630 0.8000 –0.4180 0.1947 0.990
I2t curves
The I2t curves are derived as follows:
Eq. 5-8
where
Eq. 5-9
5 Eq. 5-10
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
The instantaneous overcurrent element is used primarily for supervising main protection trip commands on a per-breaker
basis (that is, differential, breaker failure, and end fault protection). It responds to a single-phase current. If the intention is
to allow three-phase tripping if any phase current is above the threshold, the appropriate FlexLogic operands are passed
between the IEDs using the B90 fiber optic communications (Direct I/Os).
Instantaneous Overcurrent supervision can also be used to prevent tripping feeders with low currents or for definite time
backup protection.
The pickup setting is specified in per unit values. The nominal current as entered under SYSTEM SETUP AC INPUTS
CURRENT BANK XY CT XY SECONDARY is 1 p.u. The element can be effectively enabled only when B90 FUNCTION is set to
"Protection". One instantaneous overcurrent element is available per each CT input of the relay.
Figure 5-91: Instantaneous overcurrent logic
SETTING
B90 FUNCTION:
Logic = 0
Protection = 1
SETTING
IOC 1 FUNCTION:
Disabled = 0
AND
Enabled = 1
SETTING SETTINGS
IOC 1 BLOCK: IOC 1 PICKUP DELAY:
SETTING
Off = 0
IOC 1 PICKUP: IOC 1 RESET DELAY:
IOC 1 CT:
SETTING
RUN tPKP FLEXLOGIC OPERANDS
IOC 1 OP
5
Current Magnitude, |I| | I | > PICKUP tRST IOC 1 DPO
IOC 1 PKP
The Time Overcurrent (TOC) element is provided for backup protection with a choice of inverse time curves. The element is
enabled only when PRODUCT SETUP B90 FUNCTION B90 FUNCTION is set to "Protection". One TOC element is available per
each CT input.
Figure 5-92: Time overcurrent logic
SETTING
B90 FUNCTION:
Logic = 0
Protection = 1
SETTING
TOC 1 FUNCTION:
SETTINGS
Disabled = 0
AND
TOC 1 PICKUP:
Enabled = 1
TOC 1 CURVE:
SETTING
TOC 1 BLOCK: TOC 1 TD MULTIPLIER:
Off = 0
TOC 1 RESET: FLEXLOGIC OPERANDS
RUN |I| > PICKUP TOC 1 PKP
SETTING
TOC 1 CT: TOC 1 DPO
Current Magnitude, |I| TOC 1 OP
836006A1.vsd
5 END FAULT
PROTECTION 1 EFP1 FUNCTION:
Disabled
Range: Disabled, Enabled
The End Fault Protection (EFP) element operates for dead-zone faults; i.e., faults between the CT and an open feeder
breaker. Since a bus protection zone terminates on the CTs, faults between the CT and breaker require special
consideration.
With a bus-side CT (Part A of the figure below), a fault between the open CB and CT is outside the bus zone but can only
cleared by tripping the bus zone protection. In this case EFP trips the bus zone protection once the current exceeds a user-
programmable threshold, effectively clearing the fault.
With a line-side CT (Part B of the figure below), the zone is reduced once the breaker opens. Otherwise, the bus protection
may issue an unnecessary widespread trip in the case of a fault between the open CB and CT. The zone is shortened using
the breaker position with a short drop-out delay as a connection status for the associated current. Once the bus zone
moves and terminates on the CB, a dead-zone is created between the CB and CT. In this case, the EFP is used; upon
operation, the EFP will trip the remote breaker.
The EFP element arms when the feeder breaker opens and resets when a manual breaker CLOSE command is issued. To
avoid race conditions, a user-programmable time delay for the breaker OPEN signal is provided. Once armed, the element
operates when the current exceeds a user-programmable threshold. The output must be configured to either send an
inter-trip or trip the bus zone protection depending on the CT orientation with respect to the breaker.
Figure 5-93: Application of end fault protection element
(a) (b)
"dead-zone" "dead-zone"
(requires tripping (requires inter-
the bus) tripping)
836745A1.vsd
5
EFP1 PICKUP — Specifies the current level recognized by an armed EFP scheme as fault current in the protected dead-zone.
Although it can be set very low (above the noise level), set above the maximum load current for extra security.
EFP1 BREAKER OPEN — This setting is a FlexLogic operand indicating an open breaker. The operand shall be "On" when the
breaker is open. Typically, this setting is a position of an appropriately wired input contact of the B90.
EFP1 BKR DELAY — This setting specifies a timed delay between the breaker position being declared as open by the EFP1
BREAKER OPEN setting and the moment the EFP scheme is armed. Set this delay long enough to avoid spurious operation
due to a delay between the breaker position and decaying of the breaker current. The current ramp down period of the
B90 for the purpose of setting the EFP is 1.3 of a power system cycle.
EFP1 MANUAL CLOSE — This setting is a FlexLogic operand indicating a close command for the breaker. This operand shall
be "On" when the breaker is ordered to close. Typically this setting is a position of an appropriately wired input contact of
the B90.
EFP1 PICKUP DELAY — This setting allows extra security when tripping the bus from the EFP element. This timer shall be set
longer than the maximum delay between the breaker closing and picking up some current and the EFP MANUAL CLOSE
signal. If the manual close signal, EFP MANUAL CLOSE, arrives before the timer expires, the element resets and misoperation
due to signal transit times is avoided.
EFP1 BLOCK — This setting dynamically block/unblocks the element. A typical application is a by-pass isolator as shown
below. When the isolator is closed, the current does not necessarily indicate on a fault between the CB and CT and the
element shall be blocked. Therefore, the close status of the isolator shall be used as the block setting.
TRANSFER BUS
CB ISO
selective
"dead-zone"
only if the isolator is
open
836746A1.vsd
SETTING
5 EFP 1 FUNCTION:
Disabled = 0
AND
Enabled = 1
SETTING
EFP 1 BLOCK:
SETTING
Off = 0
EFP 1 PICKUP:
RUN
SETTING
EFP 1 CT:
Current Magnitude, |I| | I | > PICKUP
SETTING
SETTING EFP 1 PICKUP DELAY:
EFP 1 MANUAL CLOSE: FLEXLOGIC OPERANDS
tPKP
AND
Off = 0 EFP 1 OP
0
SETTINGS EFP 1 DPO
SETTING EFP 1 BRK DELAY: EFP PKP
EFP 1 BREAKER OPEN:
tPKP
Off = 0
0
836004A1.vsd
TRIP BUS 1
EVENTS: Disabled
Range: Enabled, Disabled
5
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista software under Settings > Protection
Summary. Navigate to a specific protection or control protection element and check the bus box by hovering over the
blank check box and selecting an option that displays. Once the required element is selected for a specific bus, a list of
element operate-type operands are displayed and can be assigned to a trip bus. If more than one operate-type operand is
required, it can be assigned directly from the trip bus menu.
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.
SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled.
SETTING GROUPS BLK — Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON — Selects a FlexLogic operand which, when set, makes the particular setting
group active for use by any grouped element. A priority scheme ensures that only one group is active at a given time — the
highest-numbered group that is activated by its ACTIVATE ON parameter takes priority over the lower-numbered groups.
There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes active if no
other group is active.
SETTING GROUP 1 NAME to SETTING GROUP 6 NAME — Allows the user to assign a name to each of the six settings groups.
Once programmed, this name appears on the second line of the GROUPED ELEMENTS SETTING GROUP 1(6) menu display.
A setting group selection can also be made by the IEC 61850 MMS service SelectActiveSG to the control block @Master/
LLN0.SGCB. The priority scheme mentioned makes active the highest numbered group selected by SelectActiveSG or the
GROUP ACTIVATE ON settings. The SelectActiveSG selection has a default value of 1, so until a higher SelectActiveSG
selection is received, the GROUP ACTIVATE ON settings control the active group.
The most recent SelectActiveSG selection is preserved while the UR is powered down or reset.
If it becomes necessary to cancel the SelectActiveSG selection without using a SelectActiveSG service request, change the
SETTING GROUPS FUNCTION setting to Disabled. This resets the SelectActiveSG selection to 1.
DIGITAL ELEMENT 1 PICKUP DELAY — Sets the required time delay from element pickup to element operation. If a pickup delay
is not required, set to "0," To avoid nuisance alarms, set the delay greater than the operating time of the breaker.
DIGITAL ELEMENT 1 RESET DELAY — Sets the time delay to reset. If a reset delay is not required, set to “0.”
DIGITAL ELEMENT 1 PICKUP LED — This setting enables or disabled the digital element pickup LED. When set to “Disabled,” the
operation of the pickup LED is blocked.
Figure 5-98: Digital element logic
SETTING
DIGITAL ELEMENT 01
FUNCTION: SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0 827042A2.VSD
H1a
I
H1b DC–
V DC+
H1c 52a Trip coil
I = current monitor
V = voltage monitor 827073A2.CDR
Assume the output contact H1 is a trip contact. Using the contact output settings, this output is given an ID name; for
example, “Cont Op 1." Assume a 52a breaker auxiliary contact is connected to contact input H7a to monitor breaker status.
Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is
closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown).
5
with form-A contacts
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
5.7.5.1 Menu
SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS
MONITORING CT TROUBLE ZONE 1 See below
ELEMENTS
CT TROUBLE ZONE 6
The CT Trouble feature is available only when PRODUCT SETUP B90 FUNCTION B90 FUNCTION is set to "Protection".
This element uses the differential current calculated in accordance with the bus configuration programmed under Bus
Zone 1. Operation of this element is therefore completely dependent on the dynamic bus replica, which must be defined
first. The bus differential zones are defined using the path SETTINGS SYSTEM SETUP BUS. The CT Trouble element 1
detects CT problems in any of the circuits actually connected to the differential zone defined as Bus Zone 1.
The CT TROUBLE ZONE 1 PICKUP setting specifies the differential current level that defines an abnormal bus state. If the
differential current in a given phase remains above this level for the time interval defined by the CT TROUBLE ZONE 1 DELAY
5 setting, CT Trouble is declared for the given phase by setting the appropriate FlexLogic output operand. The operand may
be configured to raise an alarm and block the bus differential function for the corresponding zone of protection.
B90 FUNCTION:
Logic = 0
Protection = 1
SETTING
CT TROUBLE ZONE 1 AND
FUNCTION:
Enabled = 1
SETTING
BUS 1A CT:
Current Phasor
SETTINGS
BUS 1A STATUS:
Off = 0
BUS 1A DIRECTION:
ZONE 1 DIFFERENTIAL CURRENT
SETTINGS SETTINGS
CT TROUBLE ZONE 1 CT TROUBLE ZONE 1
... PICKUP:
RUN
Id1 > PICKUP
DELAY:
tPKP
FLEXLOGIC OPERAND
CT TROUBLE1 OP
ID1
SETTING
BUS 1X CT: 5
Current Phasor
SETTINGS
BUS 1X STATUS:
Off = 0
BUS 1X DIRECTION:
836759A4.CDR
Bus protection zone discrimination depends heavily on reliable isolator position feedback. Therefore, two isolator auxiliary
contacts – normally open and normally closed – must confirm the status of the isolator via the B90 contact inputs.
This element responds to both normally open and normally closed auxiliary contacts of an isolator or a tie-breaker in order
to assert the actual position of the isolator for the dynamic bus image. The element asserts two extra output operands
indicating "isolator alarm" (auxiliary contact discrepancy), and "block switching operations in the substation." The
operation of the element is summarized in the following table.
Table 5-30: Isolator monitoring logic
Isolator open Isolator closed Isolator position Alarm Block switching
auxiliary contact auxiliary contact
Off On CLOSED No No
Off Off LAST VALID After time delay Until Isolator
until acknowledged Position is valid
On On CLOSED
On Off OPEN No No
The position of an isolator is indicated by the ISOLATOR N POSITION FlexLogic operand (On = Closed, Off = Open). This operand
is used as a circuit connection status for the bus configuration. When "On", the related current is associated with a given
differential zone; when "Off", the current is excluded from differential calculations.
An isolator alarm FlexLogic operand, ISOLATOR 1 ALARM, is asserted after a settable time delay if the auxiliary contacts of the
isolator do not match (open-open, closed-closed instead of open-closed or closed-open), yielding an undefined isolator
position. The operand may be used to block user-selected protection functions and may be reset manually or remotely via
the resetting input operand.
The ISOLATOR 1 BLOCK operand is asserted as long as the isolator position is invalid. This operand may be used to block
switching operations in the substation. Typically, breakers and isolators that control currents flowing through a given
5 isolator shall be blocked from operation as long as isolator position is not resolved.
The element is effectively enabled only when PRODUCT SETUP B90 FUNCTION B90 FUNCTION is set to “Logic.” See the
Application of Settings chapter for details on the usage of the Bus Replica element.
ISOLATOR 1 OPEN — This setting specifies a FlexLogic operand that represents an auxiliary contact of the monitored isolator.
Typically this setting is a status of an appropriately wired input contact (“On” = isolator open).
ISOLATOR 1 CLOSED — This setting indicates a FlexLogic operand that represents an auxiliary contact of the monitored
isolator. Typically this setting is a status of an appropriately wired input contact (“On” = isolator closed).
Figure 5-102: Typical isolator open/closed settings
+
ISOLATOR 1
836743A1.vsd
ISOLATOR 1 ALARM DELAY — This setting specifies a time delay after which an isolator alarm is issued by asserting the
operand assigned to ISOLATOR 1 ALARM. Set the delay longer than the slowest operation (transition) time of the isolator.
ISOLATOR 1 RESET — This setting indicates a FlexLogic operand that acknowledges the isolator alarm. Once the alarm is
acknowledged, the ISOLATOR 1 ALARM is reset. If the latter operand was configured to block protection, the blocking is
removed once the alarm is acknowledged. The acknowledge pulse must last at least 50 ms to take effect.
Figure 5-103: Isolator monitoring logic
SETTING
B90 FUNCTION:
Logic = 0
Protection = 1
SETTING
ISOLATOR 1
FUNCTION:
Disabled = 0 AND
Enabled = 1
SETTINGS
RUN
ISOLATOR 1 OPEN:
Off = 0 FLEXLOGIC OPERAND
Isolator
ISOLATOR 1 CLOSED: Position ISOLATOR 1 POSITION
Logic
Off = 0
SETTING
ISOLATOR 1 ALARM
DELAY:
FLEXLOGIC OPERAND
5
XOR
AND
tPKP
ISOLATOR 1 BLOCK
0
Positive
Edge S
Detector FLEXLOGIC OPERAND
ISOLATOR 1 ALARM
SETTING
OR
ISOLATOR 1 RESET: R
Off = 0
836002A1.vsd
ISOLATOR 1 OPEN
ISOLATOR 1 CLOSED
ISOLATOR 1 POSITION
alarm
ISOLATOR 1 ALARM acknowledged
alarm acknowledging
ISOLATOR 1 RESET signal
836744A1.vsd
5 5.8 Inputs/outputs
5.8.1 Contact inputs
SETTINGS INPUTS/OUTPUTS CONTACT INPUTS
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each
group of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules)
which contact inputs are available and then display settings for only those inputs.
An alphanumeric ID can be assigned to a contact input for diagnostic, setting, and event recording purposes. The CONTACT
IP X On (Logic 1) FlexLogic operand corresponds to contact input “X” being closed, while CONTACT IP X Off corresponds to
contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to overcome
‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maximum
contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT INPUT
EVENTS is set to “Enabled,” every change in the contact input state triggers an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the following
figure. The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a
user-settable debounce time in order for the B90 to validate the new contact state. In the following figure, the debounce
time is set at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated
(de-bounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the
contact input into the Event Recorder (mark no. 2 in the figure).
Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the
figure that follows). The update is performed at the beginning of the protection pass so all protection and control functions,
as well as FlexLogic equations, are fed with the updated states of the contact inputs.
The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
5
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration
of the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically
a delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1 ms.
For example, eight protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a
contact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 s accuracy using the
time of the first scan corresponding to the new state (mark no. 2 shown). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the
debounce timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the
change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure) and HIGH-LOW (marks no. 5, 6, 7, and 8) transitions.
VOLTAGE
Figure 5-105: Input contact debouncing mechanism and time stamp sample timing
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
TM
Time stamp of the first At this time, the The FlexLogic scan corresponding to the
At this time, the new
scan corresponding to new (HIGH) operand is going to new validated state is
(LOW) contact state is
the new validated state is contact state is be asserted at this logged in the SOE record
validated
logged in the SOE record validated protection pass
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
5 Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value is selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V sources
and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it
in the Event Records menu, make the following settings changes:
CONTACT INPUT H5a ID: "Breaker Closed (52b)"
CONTACT INPUT H5a EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
COMMANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the
appropriate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled,” the input is forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled,” the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x type is “Self-Reset,” when the input signal
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched,” the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
Figure 5-106: Virtual inputs logic
SETTING
VIRTUAL INPUT 1
FUNCTION:
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
5
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A3.CDR
A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
Upon startup of the relay, the main processor determines from an assessment of the modules installed in the chassis
which contact outputs are available and then presents the settings for only these outputs. Where the contact input is non-
latching, the settings are as shown.
An ID can be assigned to each contact output. The signal that can OPERATE a contact output can be any FlexLogic
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic operand can be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A
contacts (see the trip circuit example in the Digital Elements section). The monitor sets a flag (see the specifications for
Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, Cont OP 1 IOn.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect
operation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in
the trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the
tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized using the Cont OP 1 IOn FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
H1b
5 H1c
859743A1.vsd
The latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and
populates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic).
The latching output modules, either as part of the relay or as individual modules, are shipped from the factory with all
latching contacts open. It is highly recommended to double-check the programming and positions of the latching contacts
when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring
capabilities for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test
error is declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message.
OUTPUT H1a OPERATE — This setting specifies a FlexLogic operand to operate the ‘close coil’ of the contact. The relay seals-
in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off), any activity of the
OPERATE input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active
(logic 1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a RESET — This setting specifies a FlexLogic operand to operate the ‘trip coil’ of the contact. The relay seals-in
this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any activity of the
RESET input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active (logic
1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a TYPE — This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact closes if set to
“Operate-dominant” and opens if set to “Reset-dominant.”
Figure 5-108: Contact input/output module type 4L contact 1 logic
SETTING
CONTACT OUTPUT H1a Non-volatile,
OPERATE = On Set-dominant
AND S
SETTING OR Latch On
CONTACT OUTPUT H1a TYPE Close
= Operate-dominant R
H1b
= Reset-dominant
Non-volatile,
SETTING OR Set-dominant
H1a
CONTACT OUTPUT H1a RESET AND S
= On Open
Latch
R
FLEXLOGIC OPERAND
Cont Op 1 Closed
859744A1.vsd
5
Application example 1
A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings are applied.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “PUSHBUTTON 1 ON”
OUTPUT H1a RESET: “PUSHBUTTON 2 ON”
Program the pushbuttons by making the following changes in the PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.00 s”
PUSHBUTTON 2 FUNCTION: “Self-reset”
PUSHBTN 2 DROP-OUT TIME: “0.00 s”
Application example 2
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
OUTPUT H1c OPERATE: “VO2”
OUTPUT H1c RESET: “VO1”
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they do not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time can occur.
Therefore, a pair of contacts programmed to be a multi-contact relay do not guarantee any specific sequence of operation
(such as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the
control inputs as shown in the next application example.
Application example 3
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality.
Write the following FlexLogic equation (EnerVista example shown).
Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista example shown).
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to ‘OFF’ (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID: "Trip"
VIRTUAL OUTPUT 1 EVENTS: "Disabled"
5.8.5 Resetting
Some events can be programmed to latch the front panel LED event indicators, target messages, and/or graphical front
panel annunciator windows. Once set, the latching mechanism holds the latched indicators, messages, or windows in the
set state after the initiating condition has cleared until a RESET command is received to return these latches (not including
FlexLogic latches) to the reset state where the initiating condition has cleared. The RESET command can be sent from the
front panel RESET button, a remote device via a communications channel, or any selected operand. The Modbus execute
function 05h with operation code 1 command is also available to perform the same function as the front panel RESET key.
RESET OPERAND — The three sources of RESET commands each activates the RESET OP FlexLogic operand. Each individual
source of a RESET command also activates its individual operand RESET OP (PUSHBUTTON), RESET OP (COMMS), or RESET OP
(OPERAND) to identify the source of the command. Each of these three operands generates an event in the event record
when activated. The RESET OPERAND setting here selects the operand that activates the RESET OP (OPERAND) operand.
RESET ANNUNCIATOR — Used to select a FlexLogic operand that when activated acknowledges/resets all annunciator
windows on the graphical front panel. The other methods to acknowledge/reset annunciator windows include:
• On the displayed page, press the RESET pushbutton with none of the annunciator windows selected to acknowledge/
reset all annunciator windows on that page
• To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the RESET or ENTER pushbutton
• All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the RESET ANNUNCIATOR setting. Then the Modbus execute function 05h with operation code 1000h command
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the RESET ANNUNCIATOR setting, the RESET ANCTR OP FlexLogic operand is activated by the two sources of RESET
command, operand source and manual source. Each individual source of a RESET ANNUNCIATOR command also activates
its individual operand RESET OP (OPRD) or RESET ANCTR OP (MNUL) to identify the source of the command. Each of these two
operands generates an event in the event record when activated. The setting here selects the operand that activates the
RESET ANCTR OP (OPRD) operand. The RESET pushbutton on the front panel or the reset command from the software
activates the RESET ANCTR OP (MNUL) operand.
DIRECT OUT 1 NAME — This setting allows the user to assign a descriptive name to the direct output.
DIR OUT 1 OPERAND — This sets the FlexLogic operand that determines the state of this direct output.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR 5
Assume that contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings are applied (Direct Input 5 and
bit number 12 are used, as an example).
UR IED 1:
DIRECT INPUT 5 DEVICE ID = “2”
DIRECT INPUT 5 BIT NUMBER = “12”
UR IED 2:
DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.
UR IED 1 BLOCK
842712A1.CDR
Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
trips the bus upon detecting a fault and applying a short coordination time delay.
The following settings are applied (assume Bit 3 is used by all 3 devices to send the blocking signal and Direct Inputs 7, 8,
and 9 are used by the receiving device to monitor the three blocking signals).
UR IED 2:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 3:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 4:
5 DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 1:
DIRECT INPUT 7 DEVICE ID: "2"
DIRECT INPUT 7 BIT NUMBER: "3"
DIRECT INPUT 7 DEFAULT STATE: select "On" for security, select "Off" for dependability
UR IED 1 UR IED 2
UR IED 3 842713A1.CDR
Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown as
follows. The scheme output operand HYB POTT TX1 is used to key the permission.
Figure 5-112: Single-channel open-loop configuration
UR IED 3
RX1 5
TX1
842714A1.CDR
In this architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a ‘bridge’. The following
settings are applied:
UR IEC 1:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "4" (effectively, this is a message from IED 3)
UR IED 3:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "3" (effectively, this is a message from IED 1)
UR IED 2:
DIRECT INPUT 5 DEVICE ID: "1"
DIRECT INPUT 5 BIT NUMBER: "2"
DIRECT INPUT 6 DEVICE ID: "3"
DIRECT INPUT 6 BIT NUMBER: "2"
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT OUT 3 OPERAND: "DIRECT INPUT 5" (forward a message from 1 to 3)
DIRECT OUT 4 OPERAND: "DIRECT INPUT 6" (forward a message from 3 to 1)
The figure shows the signal flow among the three IEDs.
UR IED 1 UR IED 2
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6 DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1
setting).
5.9 Testing
5
5.9.1 Test mode function
SETTINGS TESTING TEST MODE FUNCTION
TESTING TEST MODE Range: Disabled, Isolated, Forcible
FUNCTION: Disabled
The B90 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions
and the Phasor Measurement Unit (PMU, where applicable), using simulated conditions. It is accessible in the software and
graphical front panel.
The TEST MODE FUNCTION can be in one of three states: Disabled, Isolated, or Forcible. In UR 7.7 and later, as outlined in the
Simulation section that follows, the UR test mode and GOOSE simulation mode are Isolated, and they no longer depend on
the UR TEST MODE FUNCTION.
The Disabled mode is intended for normal in service operation; the relay protection, control, and communication function
is normal. Test features are disabled, except channel tests and Phasor Measurement Unit tests remain usable when
provided.
The Isolated mode is intended to allow the relay to be quickly placed in a state where the relay cannot negatively impact
the power system or other parts of the substation automation system. This is to allow changing settings, loading new
firmware, changing hardware modules, and changing communication connections. As far as practical all relay output
signals are blocked. Contact outputs are de-energized, latching outputs are frozen. Commands to HardFiber Bricks are
blocked. GOOSE transmissions have their "simulation" flag (also known as "test" flag) set, which results in the messages not
being accepted by compliant receiving devices that do not have a "Sim" data attribute set. The quality attribute of values
that can be output via IEC 61850 MMS services are set to "invalid," which results in the values not being used for
operational purposes by compliant receiving devices. Direct I/O channel tests and PMU tests are usable on applicable
models.
The Forcible mode is intended for testing involving forcing relay operation by test signal injection and verifying correct
relay output. This mode is also for tests to verify the relay outputs (both contact and communications) have the intended
impact on specific power system devices or on specific other substation automation devices. Contact outputs can be
selectively enabled or forced as described in the following two sections. Shared outputs to Bricks have their test mode flag
raised, which results in their value only being accepted by relays also in forcible mode. GOOSE transmissions have the
"simulation" flag set, which results in these only being accepted by other devices that have their "Sim" data attribute set.
The "Sim" data attribute in the relay is set, so that if GOOSE messages are received with the "simulation" flag set, these are
used in place of the normal messages. The quality attribute of values that are output via IEC 61850 MMS services are set to
"valid" + "test," which signals that the values are not to be used for operational purposes.
Otherwise, the UR remains fully operational while in the Forcible test mode, allowing for various testing procedures. In
particular, the protection and control elements, and FlexLogic function normally. Other than the IEC 61850 protocol,
communications based inputs and outputs remain fully operational. The test procedure must take this into account. Direct
I/O channel tests and PMU tests are usable on applicable models.
The test mode can be selected through the front panel, EnerVista UR Setup software, or IEC 61850 control to LLN0.Mod.
LLN0.Mod.ctlVal "on" selects Disabled, "test/blocked" selects Isolated, and "test" selects Forcible. The TEST MODE FUNCTION
setting can only be changed by a direct user command. Following a restart, power up, settings upload, or firmware
upgrade, the test mode remains at the last programmed value. This allows a UR that has been placed in isolated mode to
remain isolated during testing and maintenance activities.
When in Forcible mode, the operand selected by the TEST MODE FORCING setting dictates further response of the B90 to
testing conditions, as described in the following two sections.
The test mode state is indicated on the relay front panel by a combination of the Test Mode LED indicator, the In-Service
LED indicator, and by the critical fail relay, as shown in the following table. 5
Table 5-31: Test mode operation
TEST MODE In-service Test mode Critical fail TEST MODE Contact input and output behavior
FUNCTION LED LED relay FORCING
Disabled Unaffected Off Normal No effect Normal
Isolated Off On De-energized No effect Contact outputs disabled
Forcible Off Flashing De-energized Off Normal
On Controlled by forcing features
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs.
While in Forcible test mode, the relay contact inputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. Select this value if a given input must be operational during the test. This
includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open,” the input is forced to report as opened (Logic 0) while the operand selected by TEST MODE FORCING
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
• If set to “Closed,” the input is forced to report as closed (Logic 1) while the operand selected by TEST MODE FORCING
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
While in Forcible test mode, the relay contact outputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the contact output remains fully operational. It operates when its control operand is logic 1 and
resets when its control operand is logic 0.
• If set to “Energized,” the output closes and remains closed while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “De-energized,” the output opens and remains opened while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “Freeze,” the output retains its position at the instant before the TEST MODE FUNCTION was Forcible and the
operand selected by the TEST MODE FORCING setting was On, regardless of later changes in the status of the operand
configured to control the output contact. While the selected operand is Off, the output behaves as it does when in
service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
5.10 Simulation
5.10.1 GOOSE
SETTINGS SIMULATION GOOSE
GOOSE Tx GOOSE SIM MODE: Range: Enabled, Disabled
Disabled
Prior to UR 7.7, when the UR TEST MODE FUNCTION is set to "Isolated" or "Forcible," the sim bit in the header of all
transmitted GOOSE messages is set to "TRUE," so that the UR plays the simulator role during the testing and
commissioning phases. The "Sim" data attribute in the relay is set (<MasterLD>/LPHD1.Sim.stVal = TRUE), so that if GOOSE
messages are received with the "simulation" flag set, these are used in place of the normal messages. The quality attribute
values that are transmitted via GOOSE services are set to "valid" + "test."
In UR 7.7 and later, the UR test mode and GOOSE simulation mode are isolated. The sim bit in the transmitted GOOSE
messages and the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.stVal) are controlled via new Modbus settings and MMS
control requests. They no longer depend on the UR TEST MODE FUNCTION.
When the B90 is set to IEC 61850 Edition 2, the settings display in the software and front panel. When using IEC 61850
Edition 1, the settings display in the software and are read-only.
5
Tx GOOSE SIM MODE — When set to Disabled, the sim bit in all transmitted GOOSE messages are set to FALSE. When set to
Enabled, the sim bit in all transmitted GOOSE messages are set to TRUE. This setting also is accessible from IEC 61850
client control to <MasterLD>/LPHD1.TxGoSim.
SIM q.VALIDITY — This setting simulates the validity bits of the quality attribute values included in all transmitted GOOSE
messages. This setting is used when Tx GOOSE SIM MODE is set to Enabled. When this setting is set to None, the q.Validity
bits are set based on the logical node behavior value. When set to any other value, the q.Validity bits of quality attributes
included in all transmitted GOOSE messages are set to the selected value.
SIM q.TEST — This setting simulates the Test bit of the quality attribute values included in all transmitted GOOSE messages.
This setting is used when Tx GOOSE SIM MODE is set to Enabled. When this setting is set to None, the q.Test bit is set based
on the relay TEST MODE FUNCTION. When set to any other value, the q.Test bit of quality attributes included in all
transmitted GOOSE messages is set to the selected value.
ACCEPT SIM GOOSE & SV — When set to Disabled, the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.stVal) is set to False and
the GOOSE messages received with simulation flag set are ignored. When set to Enabled, the relay "Sim" attribute
(<MasterLD>/LPHD1.Sim.stVal) is set to True, so that if GOOSE messages are received with the "simulation" flag set, these
are used in place of the normal messages. This setting also is accessible from IEC 61850 client control to <MasterLD>/
LPHD1.Sim.
Actual values
This chapter outlines viewing of data on the front panel and in the software.
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
Annunciator alarms can be acknowledged and reset, and LEDs and pushbuttons can be viewed. 6
To view alarms for the graphical front panel in EnerVista:
1. Access Actual Values > Graphical Panel > Annunciator Panel. Alarms are listed, allowing remote acknowledgement/
reset.
2. Click the Acknowledge or Reset button for an alarm.
Figure 6-2: Annunciator alarms displayed in the software)
6.3 Status
6.3.1 Contact inputs
ACTUAL VALUES STATUS CONTACT INPUTS
CONTACT INPUTS Cont Ip 1 Range: On, Off
Off
Cont Ip xx Range: On, Off
Off
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
6
6.3.3 RxGOOSE boolean inputs
ACTUAL VALUES STATUS RxGOOSE BOOLEANS
RxGOOSE BOOLEANS RxGOOSE BOOLEAN 1 Range: On, Off
STATUS: Off
RxGOOSE BOOLEAN 256 Range: On, Off
STATUS: Off
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
6
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
IGMP — Multicast (SSM and ASM) modes of R-GOOSE reception require that the B90 device subscribe to a multicast group
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.
There are 256 FlexStateTM bits available. The second line value indicates the state of the given FlexState bit.
6.3.10 Ethernet
ACTUAL VALUES STATUS ETHERNET
ETHERNET ETHERNET PRI LINK Range: Fail, OK
STATUS: Fail
These values indicate the status of the first, second, and third Ethernet links.
This item displays in the software when the product includes an IEEE 1588 software option.
RTC SYNC SOURCE actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, SNTP1, SNTP2, and None. An actual value displays when the relay
includes the IEEE 1588 software option.
The GRANDMASTER ID is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
ACCURACY is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
6
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE is the present state of the port’s PTP clock. The PTP clock state is:
• Disabled is the port’s function setting is Disabled
• No Signal if enabled but no signal from an active master has been found and selected
• Calibrating if an active master has been selected but lock is not at present established
• Synch’d (No Pdelay) if the port is synchronized, but the peer delay mechanism is non-operational
• Synchronized if synchronized
PTP - IRIG-B DELTA is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-
B time.
UNRETURNED MSG
COUNT CH1: 0
UNRETURNED MSG
COUNT CH2: 0
DIRECT INPUT 1:
On
DIRECT INPUT 256:
On
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts can indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (256) values represent the state of each direct input.
These actual values represent the state of direct devices 1 through 16.
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
MMS TCP — The number of IEC 61850 connections remaining.
The B90 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
6
Total Received Port A is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
ARP — The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.
6.3.17 Protocol
ACTUAL VALUES STATUS PROTOCOL
PROTOCOL IEC61850 EDITION: Range: Edition1, Edition2
Edition2
The B90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
Displays the IEC 61850 edition currently being used, as set under Settings > Product Setup > Communications > Protocol
> IEC61850 SCL Edition. This value displays only on the front panel.
6 6.4 Metering
6.4.1 Metering conventions
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
-90o
827845A1.CDR
These values display the differential and restraint currents phasors for each bus zone. The magnitudes are displayed in
primary amperes. 6
There is no cutoff level applied to the differential and restraint currents computed by the B90. Therefore, a small
differential current reflecting CT inaccuracies and bus leakage current can be present during balanced conditions.
This is done to achieve a more accurate differential balance and to provide a direct indication of the real differential
current, as excluding small currents or not accounting for CT errors can impose significant unaccounted
differential current. It is advisable to set the minimum pickup for 87B protection greater than the maximum
differential current during normal load conditions.
6.4.3 Currents
ACTUAL VALUES METERING CURRENTS
CURRENTS F1 CURRENT:
0.000 A 0.0°
F2 CURRENT:
0.000 A 0.0°
S8 CURRENT:
0.000 A 0.0°
The metered current values for each terminal are displayed in this menu.
6.4.4 Voltages
ACTUAL VALUES METERING VOLTAGES
VOLTAGES F5 VOLTAGE:
0.000 V 0.0°
F6 VOLTAGE:
0.000 V 0.0°
S8 VOLTAGE:
0.000 V 0.0°
This menu displays the metered voltage values for each terminal.
6.4.5 Frequency
ACTUAL VALUES METERING FREQUENCY
FREQUENCY FREQUENCY:
0.00 Hz
TRACKING FREQUENCY:
60.00 Hz
This menu displays the metered frequency value and the tracking frequency. The frequency is tracked based on the
selection of the reference source with the FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM SETUP
POWER SYSTEM menu. See the Power System section of chapter 5 for details.
6 RxGOOSE
Analogs RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
The B90 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
6.5 Records
6.5.1 User-programmable fault reports
ACTUAL VALUES RECORDS USER-PROGRAMMABLE FAULT REPORTS
USER-PROGRAMMABLE NEWEST RECORD
FAULT REPORTS NUMBER: 0
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for information on this feature.
EVENT: 3 EVENT 3
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
POWER OFF TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the COMMANDS CLEAR RECORDS menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
See also the system log (syslog) information in the previous chapter.
The event records are viewable in the software and in a web browser. The figure shows the event records in the software.
Figure 6-4: Event records viewed in EnerVista software
6
6.5.3 Oscillography
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The cycles
per record value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography
section of chapter 5 for details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. See the COMMANDS CLEAR
RECORDS menu for information on clearing the oscillography records.
To view a waveform:
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display.
5. In the waveform window that opens, you can save the file, for example with the CFG extension.
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information. The information is read-only in the software and modifiable on
the front panel. For example, the order code can be corrected using the front panel.
ETHERNET MAC ADDRESS — UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
6 FIRMWARE REVISIONS
B90 Relay
REVISION: 7.6x
Range: 0.00 to 655.35
Revision number of the application firmware.
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed. The date format reflects the format specified for the clock and can vary from that shown here.
This chapter outlines the Commands and Targets menus and self-tests/error messages. Commands related to the IEC
61850 protocol are outlined in the IEC 61850 section of the Settings chapter. Log/error messages for IEC 61850 are
outlined in the UR Family Communications Guide.
COMMANDS
COMMANDS
VIRTUAL INPUTS
COMMANDS
CLEAR RECORDS
COMMANDS
SET DATE AND TIME
COMMANDS
RELAY MAINTENANCE
COMMANDS
SECURITY
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash
message appears after successfully command entry.
COMMAND
EXECUTED
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to
“No.”
7
7.1.3 Set date and time
COMMANDS SET DATE AND TIME
COMMANDS SET DATE AND TIME: Range: YYYY/MM/DD HH:MM:SS
SET DATE AND TIME 2000/01/14 13:47:03
The date and time can be entered on the front panel keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
The clock also can be synchronized to the local computer time among several UR devices. Use the Synchronize Devices
entry in the Online Window area of the EnerVista software. (Click the button at the top of the window that opens.)
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time or the
manually synchronized time is over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
PERFORM LCD TEST? Range: Off, Red, Green, Blue, White & Text Pattern,
Off Black & Text Pattern, TV Test Pattern
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the ENTER key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the ENTER key.
Not all commands display in the software; use the front panel when required.
PERFORM LAMP TEST — Turns on all front panel LEDs and display pixels for a short duration.
PERFORM LCD TEST — This command detects either stuck-ON or stuck-OFF pixels (dead pixels) in the display screen on the
graphical front panel. RED/GREEN/BLUE is to display the solid background color in the whole screen. WHITE & TEXT
PATTERN shows the white background and black texts. BLACK & TEXT PATTERN shows the black background and white
texts. TV TEST PATTERN displays a standard television test pattern (SMPTE color bars). The test screen can be canceled by
pressing any pushbutton or after 30 seconds of inactivity.
PERFORM PUSHBUTTON TEST — This command tests the pushbuttons on the graphical front panel. During testing, press the
corresponding pushbutton according to the prompt text. A failure message is given if the expected action is not detected
in one minute. Holding the ESCAPE button for five seconds to interrupt the test sequence. The designated function of a
specific pushbutton is bypassed in the test.
UPDATE ORDER CODE — Use this command to read and update the order code, for example when hardware modules have
been changed inside the relay. It causes the relay to scan the backplane for the modules and update the order code to
match. All settings are defaulted with an update. When an update occurs, the following message displays and the relay
7
restarts.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
REBOOT RELAY — Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SERVICE COMMAND — Performs specific B90 service actions. Presently, there are two service actions available. Code
"20511" returns all settings to their factory default value and restarts the relay (then you re-enter IP address, restart, set
unit to "Programmed"). Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a
code other than these two is entered, the command is ignored and no action is taken. Various self-checking diagnostics
are performed in the background while the B90 is running, and diagnostic information is stored on the non-volatile
memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the B90
is shipped from the factory, the user can want to clear the diagnostic information for themselves under certain
circumstances. For example, you clear diagnostic information after replacement of hardware. Once the diagnostic
information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from scratch.
SAVE VOLATILE DATA — Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS SECURITY
SECURITY ADMINISTRATOR Range: Yes, No
LOGOFF: No
With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.
ENGINEER LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.
OPERATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.
CLEAR SECURITY DATA — Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.
TARGETS
7
PHASE TOC4 Displayed only if targets for this element are active.
OP: A B - Example shown.
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
LATCHED Example shown.
A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target
messages of all the devices inserted into that site.
Each B90 element with a TARGET setting has a target message that when activated by its element is displayed in sequence
with any other currently active target messages in the TARGETS menu. In the example shown, the Phase TOC4 and Digital
Element 48 target settings are active and so have their targets displayed. The down arrow below the two elements
indicates that there can be other active elements beyond these two.
For more information, see the description of target messages in the next section, and the Introduction to Elements section
in the Settings chapter for instructions on TARGET setting.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7.2.2.1 Description
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major
and minor) are listed in the following tables. When either type of error occurs, the Trouble LED Indicator turns on and a
target message displays. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module de-energizes
• All other output relays de-energize and are prevented from further operation
• The front panel In Service LED indicator turns off
• A RELAY OUT OF SERVICE event is recorded
To view error messages in EnerVista software:
1. Access Actual Values > Records > Event Records.
7
Messages display on the front panel with one or two lines of text. An example is as follows. In the tables that follow,
messages are grouped using the first line of text. For example, MAINTENANCE ALERT, then a row for 4L Discrepancy, then a
row for Bad IRIG-B Signal.
MAINTENANCE ALERT:
4L Discrepancy
MAINTENANCE ALERT:
Bad IRIG-B Signal
The consequence of an
incorrect SFP can range from
damage to the B90 to no
power information for the B90
on its web page (enter IP
address in a web browser,
then click the SFP
Transceiver Information —
only the type of SFP displays
and not power data).
Application of settings
8.1 Overview
8.1.1 Introduction
This chapter provides an example of setting calculations for a sample bus. The selected example includes various bus
configurations to clarify a number of typical situations. Both the bus configuration and numerical data used are not meant
to reflect any specific utility practice or design standards.
It is also assumed that the CTs have been selected without considering a B90 application, but the UR settings are to be
calculated for proper relay application. The CT data used in this example are kept to a minimum and in a generic form. The
CT data does not reflect any particular notation or national standards.
The analysis provided in this chapter has been performed with the following goals:
• The limits of linear operation of the CTs considering zero remanent flux have been determined in order to select the
high breakpoint settings of the biased differential characteristic
• The limits of linear operation of the CTs considering a remanent flux of 80% have been determined in order to select
the low breakpoint settings of the biased differential characteristic
• Saturation of the CTs has been analyzed in order to select the higher slope of the biased differential characteristic and
the high set differential overcurrent setting
The analysis tools and safety margins applied are examples only and do not reflect any particular protection philosophy.
Typically, for the CT saturation related calculations, it is sufficient to consider the weakest (most prone to saturation) CT
connected to the bus and the total bus fault current combined with the longest time constant among all the circuits
connected to the bus. This chapter provides more detailed analysis (see the Slopes and High Set Threshold section) in order
to illustrate the idea of using setting groups to enhance the B90 performance when the bus configuration changes (see
the Enhancing Relay Performance section).
C-3 C-5
NORTH BUS
CT-1 CT-7
CT-2 B-2 CT-3 B-3 CT-4 B-4 CT-5
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
836731A2.CDR
The table shows the assumed short circuit contributions of the connected circuits and their DC time constants.
Table 8-1: Basic fault data of the connected circuit
Circuit IFAULT (kA) TDC (ms)
C-1 0.00 N/A
C-2 0.00 N/A
C-3 6.00 5
C-4 5.00 30
C-5 3.00 40
The basic CT data is presented in the following table. The magnetizing characteristics of the three different types of CTs
used in this example are shown in the following figure.
Table 8-2: Basic CT data
CT Ratio Vsat (V) RCTsec () Leads (m)
CT-1 600:5 144 0.34 210
CT-2 600:5 144 0.34 205
8 CT-3 1200:5 288 0.64 200
CT-4 1000:5 240 0.54 200
CT-5, CT-6 1000:5 240 0.54 180
CT-7, CT-8 1200:5 288 0.64 200
836732A4.CDR
C-3 C-5
NORTH BUS
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
C-3 C-5
NORTH BUS
8
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
Eq. 8-1
where
Imax is the maximum secondary current transformed without saturation (AC component only, no residual magnetism),
Rs is the total burden resistance
Vsat is the saturation voltage of the CT
The total burden resistance depends on both the fault type and connection of the CTs. For single-line-to-ground faults and
CTs connected in Wye, the burden resistance is calculated as:
Eq. 8-2
where
Rlead is the lead resistance (one way, hence the factor of 2)
RCTsec is the secondary CT resistance
Rrelay is the relay input resistance
Assuming 0.003 /m lead resistance and approximating the B90 input resistance for the 5A input CTs as 0.2 VA / (5 A)2 or
0.008 , the limits of the linear operation of the CTs have been calculated and presented in the Limits of Linear Operations
of the CTs table.
The third and fourth columns of the table have the following significance.
If an external fault occurs on circuit C-1, then CT-1 carries the fault current. As the fault current is higher than any of the
other currents, the current supplied by CT-1 is used as the restraint signal. CT-1 is guaranteed to saturate if the current
exceeds 89.55 A secondary, or 17.9 times its rated current, or 8.96 pu of the bus differential zone. Consequently,
considering CT-1, the value of 8.96 pu is used as the higher breakpoint of the characteristic.
Considering CTs that can be connected (depending on the positions of the switches) to the North bus, the HIGH BPNT for the
North bus zone is selected as the minimum of (8.96, 9.13, 31.17, 22.88, 24.57, 31.17), or 8.96 pu.
Considering CTs that can be connected (depending on the positions of the switches) to the South bus, the HIGH BPNT for the
South bus zone is selected as the minimum of (9.13, 31.17, 22.88, 24.57, 31.17), or 9.13 pu.
Eq. 8-4
For Is = 116.67 A, Rs = 1.61 Ω and the characteristic shown earlier in the Approximate CT Magnetizing Characteristics
figure, the solution is Imagnetizing = 29.73 A, Irelay = 112.8 A.
The magnetizing current of the saturated CT-1 appears to the differential element protecting the North bus as a
differential signal of 29.73 A, while the restraint signal is the maximum of the bus currents (112.8 A in this case).
Consequently, the higher slope of the characteristic should not be lower than 29.73 A / 112.8 A, or 26%, and the pickup of
the high set differential elements should not be lower than 29.73 A, or 2.97 pu.
The CTs identified as operating in the linear mode as far as the AC components are considered can, however, saturate due
to the DC components. Saturation does not occur if Vsat > Is x Rs x (1 + x Tdc), where is radian system frequency (2f).
If the above condition is violated, CT time-to-saturate for a full DC saturation can be estimated as follows. The CT
saturation factor Ks capability curve is defined as
Eq. 8-5
where
T1 is a primary system time constant
T2 is the secondary CT time constant, which can be estimated by the following equation:
Eq. 8-6
where
N is the CT ratio
Vs is the CT voltage at 10 A exciting current obtained from the CT excitation curve 8
CT limiting factor KS_LIM is defined by the following equation:
Eq. 8-7
where
Ip is the maximum CT primary fault current
The figure illustrates the Ks CT saturation capability curve and KS_LIM limiting factor.
CT time-to-saturate (tSAT) is determined as a projection of the intersection of the Ks CT saturation capability curve and
KS_LIM CT limiting factor, as shown in the figure.
Practically, CT time-to-saturate can be obtained by either of the following methods:
• Method 1 — Download the "CT Time-to-Saturate Estimator.xlsm" spreadsheet from the GE Multilin web site, located
under Support > Support Documents > B90 Low Impedance Bus Differential System. Enter the required system and CT
parameters to obtain the CT time-to-saturate.
• Method 2
– Define several time instances t1, t2...tn
– Use equation 8-5 to calculate the corresponding KS1, KS2…KSn
– Calculate KS_LIM using equation 8-7
– Compare each KS value with KS_LIM. If KS at the given time instance ti is less than KS_LIM, it means that true tSAT is
greater than ti, otherwise it is less than ti
Columns 6 and 7 of the table below summarize the DC saturation threat for the fault on C-1. CT-4, CT-6, CT-7, and CT-8 can
saturate due to the DC components and can generate spurious differential signal for both the North and South bus relays
depending on the bus configuration. The saturation does not occur before 5.02 ms and is detected by the Saturation
Detector.
The transient saturation of the CTs due to the DC component can be neglected when setting the slopes of the
characteristic as the saturation is detected and the relay uses the current directional principle. It must, however, be taken
into account when setting the high set (unbiased) differential element.
The lower breakpoint (LOW BPNT) could be increased to 4.58 pu (fifth column of the Limits of Linear Operations of the CTs
table). The higher slope (HIGH SLOPE) could be decreased as no AC saturation is possible for the South bus CTs (see the
external fault calculation tables for each circuit).
The concept could be implemented by using:
• FlexLogic to process the status signals in order to identify the weakest CT
• Setting Groups to switch dynamically from one setting group to another (adaptive settings)
This approach can be extended for buses that do not require the dynamic bus replica mechanism. This can include
approximation of the total bus fault current using positions of all switches and breakers and optimizing the settings
depending on the amount of stress imposed on the CTs in any particular bus configuration.
Theory of operation
9.1 Introduction
9.1.1 Bus differential protection
The figure shows that input currents defining (through the dynamic bus replica) the bus differential zone are received by
the B90 from current transformers (CTs) associated with the power system.
Differential
Unbiased
DIFUNB
4
i2 I2
ID
Ratio Matching and Scaling Differential 6
Current
Phasor Estimation
i3 I3
Pre-Filtering
input currents
DIFL
DIF1
5 7
IR
Restraining
DIFH
DIF2
Current
8 L
iN IN O DIFBIASED
G
I
C
Directional
DIR
Element
10
Saturation SAT
Detector
11
9 Biased Differential
Unit
836723A1.CDR
The currents are digitally pre-filtered (Block 1) in order to remove the decaying DC components and other signal
distortions.
The filtered input signals are brought to a common scale taking into account the transformation ratios of the connected
CTs (Block 2). See the Dynamic Bus Replica section in this chapter.
Phasors of the differential zone currents are estimated digitally (Block 3), and the differential (Block 4) and restraining (Block
5) signals are calculated. See the Differential Principle section.
The magnitude of the differential signal is compared with a threshold, and an appropriate flag indicating operation of the
unbiased bus differential protection is produced (Block 6).
The magnitudes of the differential and restraining currents are compared and two auxiliary flags that correspond to two
specifically shaped portions of the differential operating characteristic (DIF1 and DIF2) are produced (blocks 7 and 8). The
characteristic is split in order to enhance performance of the relay by applying diverse security measures for each of the
regions. See the Differential Principle section.
The directional element (Block 10) supervises the biased differential characteristic when necessary. The current directional
comparison principle is used that processes phasors of all the input currents as well as the differential and restraining
currents. See the Directional Principle section.
The saturation detector (Block 9) analyzes the differential and restraining currents as well as the samples of the input
9 currents. This block sets its output flag upon detecting CT saturation. See the Saturation Detector section.
The output logic (Block 11) combines the differential, directional, and saturation flags into the biased differential operation
flag. The applied logic enhances performance of the relay while keeping an excellent balance between dependability/
speed and security. See the Output Logic and Examples section.
9.2.2.1 Example 1
Assume that the CTs installed in the circuit defining the BUS ZONE 1 have the following ratings:
• 1A CT: 600:5
• 1B CT: 500:1
• 1C CT: 600:5
• 1D CT: 1000:5
• 1E CT: 500:1
• 1F CT: 600:5
The maximum of 600, 500, 600, 1000, 500, and 600 is 1000 A, which is selected as the base upon configuration of the BUS
ZONE 1. 1 per unit (pu) represents 1000 A primary.
|Id|
differential OPERATE
HIGH
SLOPE
BLOCK
LOW SLOPE Ir
PICKUP
HIGH BPNT
LOW BPNT restraining
836720A1.cdr
The higher slope used by the B90 acts as an actual percentage bias regardless of the value of the restraining signal. This is
so because the boundary of the operating characteristic in the higher slope region is a straight line intersecting the origin
of the ‘differential - restraining’ plane. The advantage of having a constant bias specified by the HIGH SLOPE setting creates
an obstacle of a discontinuity between the first and second slopes. This is overcome by using a smooth approximation
(cubic spline) of the characteristic between the lower and higher breakpoints. Consequently, the characteristic ensures
• A constant percentage bias of LOW SLOPE for restraining currents below the lower breakpoint of LOW BPNT,
• A constant percentage bias of HIGH SLOPE for restraining currents above the higher breakpoint of HIGH BPNT, and
• A smooth transition from the bias of LOW SLOPE to HIGH SLOPE between the breakpoints
9 operating characteristic.
The following example is provided with respect to the breakpoint settings.
9.3.2.1 Example 2
Proceed with the previous example and assume that taking into account the relevant factors such as properties of the CTs
themselves, resistance of the leads, and burden of the CTs, the following primary currents are guaranteed to be
transformed without significant saturation:
• 1A CT: 6.0 kA
• 1B CT: 7.5 kA
• 1C CT: 5.0 kA
• 1D CT: 13.0 kA
• 1E CT: 8.0 kA
• 1F CT: 9.0 kA
As having the lowest primary current guaranteeing operation without saturation, the CT associated with the 1C input is
most exposed to saturation. During an external fault on the 1C circuit, the 1C CT carries the fault current contributed by
potentially all the remaining circuits. The fault current is higher than any contributing current, and therefore, the current of
the 1C CT becomes the restraining signal for the biased differential characteristic for external faults on the 1C circuit.
Consequently, the higher breakpoint of the differential characteristic (HIGH BPNT) needs to be set no higher than 5000 A,
where 1000 A = 5 pu (1000 A is the base unit as outlined in the previous the example).
The same approach applies to the setting of the lower breakpoint, LOW BPNT.
Region 2
(high differential
differential
currents)
Region 1
(low differential
currents)
restraining
836725A1.CDR
The second region includes the remaining portion of the differential characteristic and applies to comparatively high
differential currents. If, during an external fault, the spurious differential current is high enough so that the differential-
restraining current trajectory enters the second region, then saturation is guaranteed to be detected by the saturation
detector.
9
The B90 operates in the 2-out-of-2 mode in the first region of the differential characteristic. Both differential and
directional principles (Differential Principle and Directional Principle) must confirm an internal fault in order for the biased
differential element to operate.
The relay operates in the dynamic 1-out-of-2 / 2-out-of-2 mode in the second region of the differential characteristic. If the
saturation detector (see the Saturation Detector section) does not detect CT saturation, the differential protection principle
alone is capable of operating the biased differential element. If CT saturation is detected, both differential and directional
principles must confirm an internal fault in order for the biased differential element to operate.
Because of diverse operating modes in the first and second regions of the differential characteristic, the user gains double
control over the dependability and security issues. The first level includes slopes and breakpoints of the characteristic with
regard to the amount of the bias. The second level includes control over the split between the first and second regions of
the characteristic.
⎛ Ip ⎞
imag ⎜ ⎟
⎜ ID − I p ⎟ OPERATE
⎝ ⎠
BLOCK
⎛ Ip ⎞
ID - Ip real ⎜ ⎟
Ip ⎜ ID − I p ⎟
⎝ ⎠
BLOCK
OPERATE
836726A2.CDR
⎛ Ip ⎞
imag ⎜ ⎟
⎜ ID − I p ⎟ OPERATE
⎝ ⎠
BLOCK
⎛ Ip ⎞
ID - Ip real ⎜ ⎟
⎜ ID − I p ⎟
⎝ ⎠
Ip
BLOCK
OPERATE
836727A2.CDR
The B90 implementation calculates the maximum angle for the considered currents and compares it against a fixed
threshold of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic
operand BUS 1(4) DIR A/B/C.
N
differential
TTER
N
TER
LT PA
PAT
OPERATE
L FAU
T
AUL
BLOCK
AL F
RNA
ERN
INTE
E XT
TERN
EXTERNAL FAULT PAT
restraining
836728A1.CDR
The CT saturation condition is declared by the saturation detector when the magnitude of the restraining signal becomes
larger than the higher breakpoint (HIGH BPNT) and at the same time the differential current is below the first slope (LOW
SLOPE). The said condition is of a transient nature and requires a seal-in. A special logic in the form of a “state machine” is
used for this purpose as depicted in the following figure on saturation detector state machine.
As the phasor estimator introduces a delay into the measurement process, the aforementioned saturation test fails to
detect CT saturation occurring very fast. In order to cope with very fast CT saturation, another condition is checked that
uses relations between the signals at the waveform level. The basic principle is similar to that described. Additionally, the
sample-based stage of the saturation detector uses the time derivative of the restraining signal (di/dt) to better trace the
saturation pattern shown in the following figure.
The saturation detector is capable of detecting saturation occurring in approximately 3 ms from fault inception. The
saturation detector, although having no dedicated settings, uses the main differential characteristic for proper operation.
This must be kept in mind when setting the characteristic as its parameters must retain their original meaning.
The operation of the saturation detector is available as the FlexLogic operand BUS 1(4) SAT A/B/C.
NORMAL
SAT := 0
The differential
current below the saturation
first slope for a condition
certain period of
time
EXTERNAL
FAULT
SAT := 1
The differential-
The differential restraining trajectory
characteristic out of the differential
entered characteristic for a
certain period of time
EXTERNAL
FAULT and CT
SATURATION
SAT := 1
836729A1.CDR
DIFL
AND
SAT
AND
DIFH
836730A1.CDR
Maintenance
This chapter outlines monitoring, maintenance, repair, storage, and disposal of the hardware and software.
10.1 Monitoring
Devices and data can be monitored.
The first row in the figure shows that Contact Output 1 operation is being monitored. Its Modbus address is CAFA. The
actual value read from the device is 0, which means that it is off.
The second row in the figure shows the Contact Output 1 Name. It has a Modbus address of CAF0 and a default value of
"Cont Op 1." None of Selection column settings render this value because they present the information based on
numbering systems.
Figure 10-2: Modbus Analyzer used to monitor actual values on a UR
Address (HEX) — Modbus address in hexadecimal. See the Modbus memory map in the UR Family Communications Guide
or in the web interface (enter IP address of UR device in a web browser).
Modbus Type
Actual Value — To read the data in the UR device
Setting — To read a setting in the UR device
Coil — To read a command in the UR device
# of — Element, input, or output to read. An example is 1 for Contact Output 1.
Selection (examples demonstrate various ways to represent 0)
Hex — A decimal numbering system based on 16 possible values, from 0 to 9 and A to F. An example is 0x0000.
Char — A single unicode character, such as C. An example is 0.
Int — A 32-bit number, either positive or negative. An example is 0.
UInt — Unsigned 32-bit integer, which means that it cannot be negative but can be twice as large as a signed integer. An
example is 0.
Long — A 64-bit number, either positive or negative. An example is 0.
ULong — Unsigned 64-bit number, which means that it cannot be negative but can be twice as large as a signed 64-bit
number. An example is 0.
Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000.
Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000.
10
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
5. Click the Read File button. The file is saved to the destination folder. The EnerVista window remains open to download
additional files.
Do not unplug the USB drive while copying is in progress, else the USB drive can be compromised.
4. When done, to exit unplug the USB drive or press the ESCAPE pushbutton.
0 = None
1 = Keypad
2 = Front port
3 = COM1 (not used)
4 = COM2 (RS485)
5 = Ethernet
GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to
7.0 then 7.4 in order to follow embedded conversion rules and keep settings.
The settings convert and a report generates.
Figure 10-5: Upgrade settings
4. Review the conversion report. The values of all settings that have been defaulted during conversion are not listed in
the conversion report; to find the value of a setting before conversion, inspect the device backup file made before
conversion.
In the example shown here, settings have been reset to factory defaults and several settings are new in firmware
version 7.6 under Settings > System Setup > Switches and Breakers.
Figure 10-6: Conversion report
5. Change settings in the new file, for example by looking at the original file.
6. Write the converted file to the device, for example by dragging and dropping from the Offline Window to the Online
Window.
7. Check settings and operation.
10
10
There are two ways to compare devices: devices in the Offline area or between Online and Offline devices.
To compare settings of two devices in the Offline Window area:
1. Right-click a first device in the Offline Window area and select Compare Two Devices.
2. In the window that opens, select a second device and click the Receive button. The file generates and the number of
differences displays.
3. To save the report, click File > Save As, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
10 UR device settings can be saved in a backup URS file using the EnerVista UR Setup software. The URS file is the standard
UR settings file. For an introduction to settings files in the URS format, see the beginning of the Interfaces chapter.
When the IEC 61850 option is present, the settings can be saved alternatively in a backup IID file either using the EnerVista
UR Setup software in online mode or by using any of the supported file transfer protocols. The IID file is one of several IEC
61850 Substation Configuration Language (SCL) file types; see the IEC 61850 chapter in the UR Series Communications
Guide for an introduction to SCL.
"TBD" displays when a setting in a modeled element is configured with a non-modeled operand. For example, Phase IOC is
modeled in a firmware release, while the LED operands are not modeled. If the block setting of the Phase IOC is configured
with LED operands, its displays as TBD in IID and CID files, the web interface, or in an MMS client.
The options that display in the EnerVista software when right-clicking depend on device options.
Preferences are set in the File > Preferences > IEC 61850 menu. There are two options as follows:
• Preserve custom attributes when importing SCD/CID files — Applies to the Add Device to Offline Window option.
When enabled, the IID file also is to be copied to the computer. The IID file that is retrieved from the relay is therefore
assumed to be in synchronization with the resulting .urs file, and in fact in this situation the IID file on the computer is
a copy of the IID file that was read from the online device. When disabled, the IID file on the computer is to be left
unchanged. The location of the IID file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
• Do not update IID file when updating SCL files — When enabled (default), an IID file is not to be created on the
computer and if one is already present there, it is neither removed nor updated. Have this option enabled when you
want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE
Power Management\urpc\Offline, for example.
An Environment backup stores a list of sites and devices in the Online and Offline Window areas. Settings files are not
contained within the environment file. If a settings file is moved, renamed, or deleted after the backup, it is removed from
the Offline Window during the restore.
To create a new settings file in the URS format in EnerVista Offline Window:
1. In EnerVista, right-click in the Offline Window area and select New Device. A window opens.
2. Change the file name at the end of the Path field, keeping the .urs extension.
3. From the Associate File with Device drop-down list, select the UR device. Other fields complete automatically.
Otherwise, when you do not select a device from the drop-down list, all fields need to be completed manually and
only devices that match the entered order code and version display in the list.
4. The Serial # Lock field is the serial number of the intended device. It ensures that the settings file is sent only to the
specific relay that matches the serial number.
5. Click the OK button to create the .urs file in the Offline Window area.
No file is generated. The IID file on the computer is copied to the location specified.
3. If the Do not update IID file when updating SCL files preference is enabled under File > Preferences > IEC 61850,
then a message displays to that effect. This means that there is no IID file available on the computer to be copied, so
a new one is generated.
10
3. Two prompts are possible, first that the URS file does not include the complete IEC 61850 configuration and that it
needs to be recreated if you continue. This means that the URS file is from UR version 7.30 or higher, has the IEC 61850
software option in the order code, but any IEC 61850 content will be compromised and will need to be configured.
Second, a message can display that the URS file is part of a device folder and to use the device’s CID file. This means
that the URS file is from UR version 7.3 or higher, has the IEC 61850 software option in the order code, and is part of the
device folder. The user is trying to add a URS file from inside a device’s folder. Instead, the user needs to use the CID file
from the device folder.
These messages display because the roles of the protection engineer and network engineer can be separate. The
former can require a URS file, while the latter can require stored Modbus settings and protection schemes. 10
4. Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URS
file. The URS file is added to the Offline Window area.
5. Drag the imported file in the Offline Window to the device in the Online Window. Note that the RELAY SETTINGS value
also is written to a device, and the accepting relay is put into "Programmed" or "Not Programmed" mode as
configured in the offline file.
6. Manually copy the remaining settings, outlined as follows.
The field-programmable gate array (FPGA) can be upgraded under Maintenance > Update FPGA when the device
is connected via serial cable and the firmware revision is 7.0 or higher.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of
firmware. The addresses are rearranged when new features are added or existing features are enhanced or
modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable,
self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware.
This message does not signal any problems when appearing after firmware upgrades.
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The following procedure can be used for the Rev. 1 and Rev. 2 enhanced front panels, with Rev. 1 is documented here. The
Rev. 2 enhanced horizontal front panel introduced starting November 2017 uses a screw to close it and internal hinge
screws as per the graphical front panel.
To remove an enhanced or basic front panel:
1. In the EnerVista software or on the front panel, access Settings > Product Setup > Communications > Network and
record the IP address and subnet mask of the port(s) being used. Record the gateway address under Default IPv4
Route.
2.
3.
Turn off power to the unit. Hot-swapping of the front panel is not supported.
For an enhanced front panel, loosen the thumb screw and open slightly the front panel.
10
For a basic front panel, lift up the black plastic latch on the right side of the front panel and open slightly the front
panel.
Figure 10-12: Loosen thumb screw on enhanced front panel to open
4. With a Phillips screwdriver, unscrew and remove the mounting bracket on the right side of the unit. The bracket for the
enhanced front panel looks similar to that for the graphical front panel, but they are not the same.
10
Figure 10-14: Remove enhanced front panel mounting bracket on right side
Figure 10-15: Remove basic front panel mounting bracket on right side
5. Open the front panel. Unplug or unscrew the grey ground cable from the front panel. Unplug the RJ45 connector from
the CPU module in the second slot on the left.
10
6. Unscrew and remove the mounting bracket with the front panel from the left side.
Figure 10-17: Unscrew enhanced front panel mounting bracket on left side
Figure 10-18: Unscrew basic front panel mounting bracket on left side
10
(note riveted hinges with red arrows - cannot replace this front panel)
2. Screw the right mounting bracket to the right side of the relay. 10
3. Attach the graphical front panel hinge to the left mounting bracket using the nuts provided.
Figure 10-21: Attach to left mounting bracket inside relay
4. Close the front panel without tightening the screw to the mounting bracket.
5. Optionally remove the protective plastic film on the graphical front panel. It is normally peeled off, but also can be left
on.
The graphical front panel has been installed but not connected.
10
2. At the front of the relay, insert the new CPU module in the second slot. The new CPU has two connection slots on the
front. Ensure that the RS485 connector and the black cover plate are not on the back of the CPU module before sliding
the module into the front of the relay.
Figure 10-23: Rear of a CPU module before insertion without RS485 connector or cover plate
10
3. Once the module is in place, connect the graphical front panel to the CPU module (ground and upper connector) and
close the front panel. There are two connections possible on the front of the CPU module: upper for the graphical front
panel and lower for the enhanced and basic front panels. The upper connection is black with holes, similar to the
cover, so it is difficult to see.
Figure 10-24: Connect graphical front panel to top connection on CPU module
4. Tighten the embedded screw on the right side of the graphical front panel to the mounting bracket.
Figure 10-25: Screw to attach graphical front panel to mounting bracket
5. At the back of the CPU module, attach the new black cover plate to the back of the relay, then connect the new RS485
connector.
10 6.
Insert the silver SFP connector(s) at the back of the CPU module, then connect any Ethernet connection(s).
Power up the relay. If the graphical front panel does not power up immediately, disconnect power, open the front
panel, then check that the graphical front panel is plugged into the upper connection, not the lower silver connection
on the CPU module.
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
Two procedures follow: replace a module with the same module, and upgrade a module.
To replace a module with the same module:
1. Open the enhanced front panel to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the B90.
10
Figure 10-26: Modules inside relay with front cover open (enhanced front panel)
The basic front panel can be opened to the left once the black plastic sliding latch on the right side has been pushed
up, as shown below.
Figure 10-27: Removing module (basic front panel)
2. With power to the unit off, disconnect individually the connections at the front and back of the module before
removing the module from the chassis.
For any Process Card/process bus module in slot H for use with a HardFiber Brick, also remove the two screws at the
back that attach the module to the chassis.
3. To properly remove a module, pull simultaneously the ejector/inserter clips, located at the top and bottom of the
module. Record the original location of the module to ensure that the same or replacement module is inserted into the
correct slot. While modules with current input provide automatic shorting of external CT circuits, for CT/VT modules it
is recommended to short/isolate external circuits accordingly for maximum safety.
4. To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module
is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips
simultaneously. When the clips have locked into position, the module is fully inserted.
When adding a module (versus replacing a module), check that settings have not changed. Depending on the
module, settings can reset to default values.
10
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and a
DSP ERROR or HARDWARE MISMATCH error displays.
An upgrade example is replacing the CPU module with a more recent one, such as swapping 9G/9H/9N with 9T/9U/9V/9W.
A power supply module upgrade does not affect an order code.
To upgrade a module:
1. Back up settings by sending the device to the Offline Window area. Convert the settings to the new order code by
right-clicking in the Offline Window area. Replace the module as outlined in the previous procedure. In the Online
Window area, reset all settings to factory defaults and read the new order code from the device using Commands >
Relay Maintenance > Update Order Code. Send the saved settings from the Offline Window area to the online device.
Refresh the order code in the Device Setup window and set the device to "Programmed" under Settings > Product
Setup > Installation.
10.12 Battery
A battery powers the real time clock on startup of the device.
When required, the battery can be replaced. The battery type is 3 V cylindrical.
The power supply module contains the battery. The power supply modules were upgraded in 2014 to SH/SL from RH/RL,
but the order code when purchasing a UR with redundant power supply remained as RH/RL so that customers can
continue to use the same order codes. The order code can read RH or RL, while the module inside the unit reads SH or SL.
The order code for replacement redundant power supply modules was changed to SH/SL.
To avoid injury, ensure that the unit has been powered off for a minimum of three minutes before
replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
To replace the battery:
1. Turn off the power to the unit.
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the plastic latch on the right side of the front panel
(basic front panel) or unscrewing the panel (enhanced front panel).
4. For the basic front panel, it needs to be removed in order to access the power supply module, which is typically in the
first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew the bracket on
the left side of the unit.
5. Remove the power supply module by simultaneously pulling the ejector clips at the top and bottom of the module and
sliding it out.
6. Unscrew all four screws (not three) that attach the metal cover to the module. The fourth screw is at the back end of
the module, on the opposite side from the clips, beside the white electronics part (see figure).
7. Slide the metal cover away from the clips about 0.5 cm (1/8 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides—pull the plastic away from the battery. Use a flat-head screwdriver if you cannot unclip the plastic with your
fingers.
9. Replace the battery with the identical make and model. For example, do not use a rechargeable battery. Observe the
+ and - polarity of the battery and replace it with the same polarity as marked on the battery holder. 10
10. Reinstall the battery holder and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.
10
10
10
10.14 Repairs
The battery and modules inside the case can be replaced without return of the device to the factory. The firmware and
software can be upgraded without return of the device to the factory.
Fuses in the power supply module are not field-replaceable.
Files can be requested for use by technical support staff, for example the Service Report (click the icon in the software or
connect a USB drive to the graphical front panel) or under Maintenance > Retrieve File, as outlined elsewhere in this
document.
For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows:
• Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter.
• Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
• Verify that the RMA and Commercial Invoice received have the correct information.
• Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to cushion
the item(s). You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of
cushioning material.
• Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory.
GE GRID SOLUTIONS
650 MARKLAND STREET
MARKHAM, ONTARIO
CANADA L6C 0M1
ATTN: SERVICE DEPT.
RMA# : ______________
Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty.
• Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098.
Use the detailed return procedure outlined at
https://www.gegridsolutions.com/multilin/support/ret_proc.htm
The current warranty and return information are outlined at
https://www.gegridsolutions.com/multilin/warranty.htm
10.15 Storage
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range
outlined in the Specifications.
10
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
10.16 Disposal
Other than the battery, there are no special requirements for disposal of the unit at the end its service life. For customers
located in the European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove
the modules, dismantle the unit, and recycle the metal when possible.
10
10
Appendices
FlexAnalog operands
The following addresses are given for the maximum number of physical channels. For example, if there are 7 CT
channels in the CT/VT module, that address 28437 corresponds to the "L1 Current Mag" value.
A
28460 L7 Curr Ang Degrees Terminal 15 current angle
28461 L8 Curr Mag Amps Terminal 16 current magnitude
28463 L8 Curr Ang Degrees Terminal 16 current angle
28464 S1 Curr Mag Amps Terminal 17 current magnitude
28466 S1 Curr Ang Degrees Terminal 17 current angle
28467 S2 Curr Mag Amps Terminal 18 current magnitude
28469 S2 Curr Ang Degrees Terminal 18 current angle
28470 S3 Curr Mag Amps Terminal 19 current magnitude
28472 S3 Curr Ang Degrees Terminal 19 current angle
28473 S4 Curr Mag Amps Terminal 20 current magnitude
28475 S4 Curr Ang Degrees Terminal 20 current angle
28476 S5 Curr Mag Amps Terminal 21 current magnitude
28478 S5 Curr Ang Degrees Terminal 21 current angle
28479 S6 Curr Mag Amps Terminal 22 current magnitude
28481 S6 Curr Ang Degrees Terminal 22 current angle
28482 S7 Curr Mag Amps Terminal 23 current magnitude
28484 S7 Curr Ang Degrees Terminal 23 current angle
28485 S8 Curr Mag Amps Terminal 24 current magnitude
28487 S8 Curr Ang Degrees Terminal 24 current angle
28488 F5 Volt Mag Volts Terminal 1 voltage magnitude
28490 F5 Volt Ang Degrees Terminal 1 voltage angle
28491 F6 Volt Mag Volts Terminal 2 voltage magnitude
28493 F6 Volt Ang Degrees Terminal 2 voltage angle
28494 F7 Volt Mag Volts Terminal 3 voltage magnitude
28496 F7 Volt Ang Degrees Terminal 3 voltage angle
28497 F8 Volt Mag Volts Terminal 4 voltage magnitude
28499 F8 Volt Ang Degrees Terminal 4 voltage angle
28500 M5 Volt Mag Volts Terminal 5 voltage magnitude
28502 M5 Volt Ang Degrees Terminal 5 voltage angle
28503 M6 Volt Mag Volts Terminal 6 voltage magnitude
28505 M6 Volt Ang Degrees Terminal 6 voltage angle
28506 M7 Volt Mag Volts Terminal 7 voltage magnitude
28508 M7 Volt Ang Degrees Terminal 7 voltage angle
28509 M8 Volt Mag Volts Terminal 8 voltage magnitude
28511 M8 Volt Ang Degrees Terminal 8 voltage angle
28512 S1 Volt Mag Volts Terminal 9 voltage magnitude
28514 S1 Volt Ang Degrees Terminal 9 voltage angle
28515 S2 Volt Mag Volts Terminal 10 voltage magnitude
28517 S2 Volt Ang Degrees Terminal 10 voltage angle
28518 S3 Volt Mag Volts Terminal 11 voltage magnitude
28520 S3 Volt Ang Degrees Terminal 11 voltage angle
28521 S4 Volt Mag Volts Terminal 12 voltage magnitude
28523 S4 Volt Ang Degrees Terminal 12 voltage angle
28624 System Frequency Hz Terminal frequency
32768 Tracking Frequency Hz Terminal tracking frequency
45584 RxGOOSE Analog 1 --- RxGOOSE analog input 1
45586 RxGOOSE Analog 2 --- RxGOOSE analog input 2
This appendix outlines how to set up a RADIUS server for user authentication.
VENDOR GE 2910
# Management authorization
BEGIN-VENDOR GE
# Role ID
ATTRIBUTE GE-UR-Role 1 integer
# GE-UR-ROLE values
VALUE GE-UR-Role Administrator 1
VALUE GE-UR-Role Supervisor 2
VALUE GE-UR-Role Engineer 3
B VALUE GE-UR-Role
VALUE GE-UR-Role
Operator
Observer
4
5
END-VENDOR GE
#############################################################
6. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
For example, the file can look like the following:
$INCLUDE ../shareéfreeradius/dictionary
$INCLUDE dictionary.ge
7. For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors.
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS parameters on the UR as follows.
8.1. If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default
password is "ChangeMe1#".
8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave
the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf
file. Restart the relay for the IP address and port changes to take effect.
9. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "testpw"). Check that the RADIUS server log
file shows the access with an "Access-Accept" entry.
Recall that if you tried another third-party tool and it did not work, you can use the FreeRADIUS software from
freeradius.net.
SetupCLI -h
Display help.
It displays the content outline here.
SetupCLI <Application> login -d <device> [-A <authentication type>] [-a <account>] -w <password> [-s]
Authenticate with device <device> using password <password>.
For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to
"traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is
used.
Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1
Example of a batch file that checks for an error (this batch file uses standard batch file operations to check the return
code (ERRORLEVEL) and jump to an error handler):
SetupCLI URPC start
SetupCLI URPC login -d demoDevice -a SETTINGS -w WrongPassword -A traditional
IF NOT ERRORLEVEL 0 GOTO FAILED
SetupCLI URPC putsettings -d demoDevice -f "example file.urs"
SetupCLI URPC inservice -d demoDevice
SetupCLI URPC reboot -d demoDevice
SetupCLI URPC exit
exit
:FAILED
echo Please try again C
exit
For CyberSentry devices with local authentication — Set <authentication type> to "local" . Set <account> to
"Supervisor", "Administrator", "Engineer", "Operator", or "Observer".
For CyberSentry devices with RADIUS authentication — Set <authentication type> to "radius". Set <account> to the
user's account on the RADIUS server.
The device is named as DEV@SETUP_CLI, which is used as the device name required by the <device> parameter of other
SetupCLI commands.
The device name DEV@SETUP_CLI is always assigned to the device that is connected most recently by performing
'adddevice' command. It means that the Application only keeps up to one device named as DEV@SETUP_CLI, the
'adddevice' command disconnects/deletes the device DEV@SETUP _CLI that was connected previously by performing
'adddevice' command.
The device name DEV@SETUP_CLI is never used to configure/connect to a device through the graphical user interface.
Example of a batch file using a device IP address to retrieve its settings file:
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f C:\example.urs
SetupCLI URPC exit
After connecting the device using IP address, the device name DEV@SETUP_CLI is used to identify this device in
'getsettings' command.
Example of a batch file using a device IP address to retrieve a settings file when RADIUS authentication is required: C
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC login -d DEV@SETUP_CLI -a %1 -w %2 -A radius
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs"
SetupCLI URPC logout -d DEV@SETUP_CLI
SetupCLI URPC exit
DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command.
Appendix D: Miscellaneous
Miscellaneous
D.1 Warranty
For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years.
For warranty details including any limitations and disclaimers, see the Terms and Conditions at
http://www.gegridsolutions.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.
D 1601-0115-AC1
1601-0115-AE1
7.40x
7.41x
8 December 2016
31 January 2017
16-3319
17-3427
1601-0115-AE3 7.4x 28 April 2017 17-3561
1601-0115-AF1 7.6x 30 June 2017 17-3779
1601-0115-AF2 7.6x 31 October 2017 17-3935
1601-0115-AG1 7.7x 31 March 2018 18-4430
1601-0115-AG2 7.7x 4 May 2018 18-4517
Table D-2: Major changes for B90 manual version AG2 (English)
Page Description
--- General revision. Improved figure quality by using conditional text to switch between PDF and PNG figures.
Table D-3: Major changes for B90 manual version AG1 (English)
Page Description
--- General revision
2-9 Updated order codes from SH / SL to RH / RL for the redundant power supply for UR purchase. The power supply modules
were upgraded in 2014 to SH and SL, but the order codes when purchasing a UR remain as RH and RL so that customers do
not need to change order codes. The order codes for the power supply replacement modules are correct as SH and SL.
3-56 Added IP and subnet mask address rules to the Set IP Address in UR section
5-53 Added IEC 61850 Editions 1 and 2 section
5-103 Added support for a redundant SNTP server as a time source
5-149 Added GOOSE simulation operands to FlexLogic operands table
5-204 Added Settings > Simulation > GOOSE section
6-3 Added Actual Values > Graphical Panel > LEDs and Pushbuttons information
6-10 Added Actual Values > Status > Protocol section
Table D-4: Major changes for B90 manual version AF2 (English)
Page Description
--- General revision
--- Added type W CPU module to order codes in chapter 2, installation chapter 3, Replace Front Panel section in chapter 10
Page Description
--- Added Japanese and Polish languages and modules 6W and 6X to order codes in chapter 2. Module 6W allows 30 contact
inputs, and Module 6X allows 18 outputs.
3-16 Added contact input and contact output modules 6W and 6X to Table 3-3 Contact Input and Output Module Assignments and
to Figure 3-16 Contact Input and Output Module Wiring (Sheet 3 of 3)
Table D-5: Major changes for B90 manual version AF1 (English)
Page Description
--- General revision
--- Updated "faceplate" to "front panel" for consistency and to reflect web site
--- Added graphical front panel option to order codes and specifications in chapter 2, Interfaces chapter 4, Settings chapter 5,
Actual Values chapter 6
--- Added PEAP-GTC and PAP protocols for authenticating user logins when using a RADIUS server. Added to Settings > Product
Setup > Security > RADIUS Authentication Method and to Modbus memory map and F codes.
--- Updated Contact Inputs from 96 to 120 and Contact Outputs from 64 to 72 in Product Description in chapter 2 and FlexLogic
operands table in chapter 5
3-36 Updated RS422 and Fiber Interface Connection figure for the clock channels (from 7a and 7b to 1a and 1b)
3-67 Added Connect to a D400 Gateway section
4-42
4-50
Updated LED Labelling instructions for the new Front Panel Label Designer
Added Standard Front Panel section for labelling LEDs and pushbuttons
D
5-98 Added USB Port section to enable/disable the USB port on the graphical front panel
5-110 Updated User-programmable Pushbuttons section as per specifications
10-5 Added Convert Device Settings section
10-7 Added Copy Settings to Other Device section
10-15 Added Replace Front Panel section for retrofit with the new graphical front panel
Table D-6: Major changes for B90 manual version AE3 (English)
Page Description
--- General revision
2- Updated order codes
10-5 Added Copy Settings to Other Device section
Table D-7: Major changes for B90 manual version AE1 (English)
Page Description
--- General revision
--- Added routable GOOSE content in chapters 2 and 5
3-34 Updated RS422 and Fiber Interface Connection figure for the clock channels (from 7a and 7b to 1a and 1b)
4- Added Engineer content
5- Updated IEC 61850 content
A- Updated FlexAnalog table for most UR products
Table D-8: Major changes for B90 manual version AC1 (English)
Page Description
--- General revision. Added online help and updated generic online help.
--- Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not
translated into Russian
--- Updated number of Direct Inputs / Direct Outputs, increasing them from 96 to 256, in specifications, FlexLogic operands table,
settings, actual values, Modbus memory map
2- Updated several specifications, such as TOC, IOC, number of FlexLogic lines
4-28 Added FlexLogic Design and Monitoring using Engineer section to end of Interfaces chapter
Page Description
5-38 Added PRT FUNCTION settings in Network section to enable/disable each Ethernet port
5-47 Updated IEC 61850 section
5-58 Added Support for Routable GOOSE section
5-143 Updated number of FlexLogic lines from 512 to 1024 in FlexLogic Equation Editor settings section
10-1 Added Monitoring section
10-2 Added Retrieve Files section
C- Added Command Line Interface appendix
Abbreviations
A Ampere
AC Alternating Current CRC Cyclic Redundancy Code/Check
A/D Analog to Digital CRL Certificate Revocation List
AE Accidental Energization, Application Entity CRT, CRNT Current
AMP Ampere CSA Canadian Standards Association
ANG Angle CT Current Transformer
ANSI American National Standards Institute CVT Capacitive Voltage Transformer
AR Automatic Reclosure
ARP Address Resolution Protocol D/A Digital to Analog
ASDU Application-layer Service Data Unit DC (dc) Direct Current
ASYM Asymmetry DCE Data Communications Equipment
AUTO Automatic DCS Distributed Control System
AUX Auxiliary DD Disturbance Detector
AVG Average DFLT Default
AWG American Wire Gauge DGNST Diagnostics
DIFF Differential
BCS Best Clock Selector DIR Directional
BER Bit Error Rate DISCREP Discrepancy
BF Breaker Fail DIST Distance
BFI Breaker Failure Initiate DMD Demand
BKR Breaker DNP Distributed Network Protocol
BLK Block DPO Dropout
BLKG Blocking DPS Double-Point Status
BNC Bayonet Neill-Concelman DSP Digital Signal Processor
BPNT Breakpoint of a characteristic DST Daylight Savings Time
BRKR Breaker dt Rate of Change
DTT Direct Transfer Trip
CA Certificate Authority DUTT Direct Under-reaching Transfer Trip
CAP Capacitor
CC Coupling Capacitor EGD Ethernet Global Data
CCVT Coupling Capacitor Voltage Transformer ENCRMNT Encroachment
CFG Configure / Configurable EPRI Electric Power Research Institute
.CFG Filename extension for oscillography files .EVT Filename extension for event recorder files
CHK Check EXT Extension, External
CHNL Channel
CID Configured IED Description F Field
CLS Close FAIL Failure
CLSD Closed FD Fault Detector
CMND Command FDH Fault Detector high-set
CMPRSN Comparison FDL Fault Detector low-set
CO Contact Output FIR Finite Impulse Response
COM Communication FLA Full Load Current
COMM Communications FO Fiber Optic
COMP Compensated, Comparison FPGA Field-programmable Gate Array
CONN Connection FREQ Frequency
CONT Continuous, Contact FSK Frequency-Shift Keying
CO-ORD Coordination FTP File Transfer Protocol
FxE FlexElement™
T Time, transformer
TC Thermal Capacity
TCP Transmission Control Protocol
TCU Thermal Capacity Used
TD MULT Time Dial Multiplier
TEMP Temperature
TFTP Trivial File Transfer Protocol
THD Total Harmonic Distortion
TMR Timer
TOC Time Overcurrent
TOV Time Overvoltage
TRANS Transient
Index
Index
Alarms
Numerics acknowledge ....................................................................4-33, 6-2, 6-3
10BASE-F settings ...............................................................................5-41 add .............................................................................................. 4-34, 5-32
4L Discrepancy message .................................................................. 7-7 messages ................................................................................................7-5
7R module ................................................................................................3-39 overview ............................................................................................... 4-31
7S module ................................................................................................3-38 reset ...............................................................................................4-33, 6-3
AND gate explained ........................................................................... 4-81
Annunciator editor ............................................................................. 4-34
ANSI device numbers ...........................................................................2-2
A Application examples
AC current inputs .................................................................................3-18 breaker trip circuit integrity .......................................................5-187
specifications ......................................................................................2-19 contact inputs ..................................................................................5-194
AC voltage input specifications ...................................................2-19 direct inputs and outputs ...........................................................5-201
Accents ......................................................................................................4-55 latching outputs ..............................................................................5-197
Access Violation message ..............................................................3-66 Apply settings to other device ..................................................... 10-7
Acknowledge alarm ............................................................................. 6-3 Approvals ................................................................................................. 2-28
Activate relay .........................................................................................3-51 Architecture, relay ............................................................................5-141
Active setting group ........................................................................5-156 Audit list of port numbers ............................................................... 5-41
Actual values ............................................................................................ 6-1 Authentication by device or server ........................................... 5-13
alarms for graphical front panel ................................................. 6-2 Automatic discovery of UR devices .......................................... 3-65
display on graphical front panel ...................................4-34, 4-35 AWG wire size ........................................................................................ 3-45
monitor with Modbus Analyzer ..................................................10-1 F485 converter .................................................................................. 3-53
not activated graphical front panel .........................................4-52 G.703 interface .................................................................................. 3-38
Add Device from File option module 7S ............................................................................................ 3-38
restore settings to online device ............................................10-11 modules 6X, 6W ................................................................................ 3-20
save to Offline Window ..................................................................3-70 modules 7E, 7F, 7G, 7Q, 75 .......................................................... 3-45
Add Device to Offline Window preferences .........................10-9 modules 7L, 7M, 7N, 7P, 74 .......................................................... 3-44
Add module, check settings not defaulted ........................10-24 modules 7T, 7W ................................................................................ 3-42
Add relay ...................................................................................................3-55 RS422 and fiber interface ............................................................ 3-44
Administrator
add user account ..............................................................................5-11
command to force logoff ................................................................ 7-4
no automatic logout from front panel ....................................5-18
B
role for CyberSentry .......................................................................... 2-5 B90 function ..............................................................................................5-5
Alarm LEDs ...........................................................................................5-112 Back up settings ...................................................................... 5-55, 10-8
Bad IRIG-B Signal message ..............................................................7-7
Bad PTP Signal message ...................................................................7-8
I
IAC curves ............................................................................................. 5-174
ICD file ................................................................................ 5-73, 5-74, 5-75
IEC 60870-5-103 protocol
explained .............................................................................................. 5-95
select protocol ................................................................................... 5-47
settings .................................................................................................. 5-95
IEC 60870-5-104 protocol
connections remaining .....................................................................6-8
port, close ............................................................................................ 5-94
select protocol ................................................................................... 5-47
settings .................................................................................................. 5-93
User-programmable LEDs
U custom labels ..................................................................................... 4-42
UDP for TFTP ...........................................................................................5-93 defaults ................................................................................................. 4-41
UL certification ......................................................................................2-28 settings ...............................................................................................5-112
Unable to connect to relay .................................................3-66, 5-41 specifications ..................................................................................... 2-18
Unable to put relay in flash mode ...........................................10-14 User-programmable pushbuttons
Unauthorized access FlexLogic operands .......................................................................5-148
commands ...........................................................................................5-37 graphical front panel buttons 9 to 16 .................................... 4-29
resetting .................................................................................................. 7-2 logic diagrams .................................................................................5-120
Undervoltage settings ...............................................................................................5-115
FlexLogic operands .......................................................................5-145 specifications ..................................................................................... 2-18
settings ...............................................................................................5-170 testing .......................................................................................................7-3
specifications ......................................................................................2-17 User-programmable self-test settings .................................5-113
Uninstall .................................................................................................10-29
Unit Not Calibrated message .......................................................7-10
Unit not programmed ...........................................................5-130, 7-6 V
Unpacking the relay ............................................................................. 3-1 Vibration testing specifications .................................................. 2-27
Unreturned messages alarm .....................................................5-130 Virtual inputs
Update SCL files prompt ..................................................................4-67 actual values .........................................................................................6-4
Update settings with Convert Device Settings ...................10-5 commands .............................................................................................7-2
Updates explained ............................................................................................5-194
device not recognized .................................................................10-13 FlexLogic operands .......................................................................5-146
firmware .............................................................................................10-14 logic diagram ...................................................................................5-195
FPGA .....................................................................................................10-15 settings ...............................................................................................5-194
instruction manual ............................................................................. 3-1 Virtual outputs
order code .............................................................................................. 7-3 actual values .........................................................................................6-5
single-line diagrams not retained .............................................4-24 explained ............................................................................................5-199
software .............................................................................................10-13 FlexLogic operands .......................................................................5-146
Upgrade device settings ..................................................................10-5 settings ...............................................................................................5-199
Upgrade over Internet message ..............................................10-14 Voltage deviation specifications ................................................ 2-27
Upload settings to relay ...................................................................10-7 Voltage metering ................................................................................. 6-12
URS file does not include IEC 61850 configuration .......10-11 Voltage Monitor message .............................................................. 7-10
URS file is part of a device folder .............................................10-11 VT wiring ................................................................................................... 3-18
URS settings file ............................................................3-70, 5-55, 10-8
USB port
graphical front panel .......................................................4-16, 5-100 W
Quick Connect ....................................................................................3-68 Warning messages in Engineer .................................................. 4-69
specifications ......................................................................................2-23 Warning symbol in Offline Window .......................................... 4-67
User accounts Warning, firmware upload not supported ..........................10-14
add ...........................................................................................................5-11 Warranty .................................................................................................... D-1
authentication by device or server ..........................................5-13 Waveform
multiple login limitation CyberSentry ........................................ 2-5 view in actual values window .................................................... 6-14
passwords for settings and commands .............4-57, 5-7, 5-8 view in event record ....................................................................... 6-13
permissions by role ............................................................................ 2-5
Waveform files, view ......................................................................... 4-78
permissions, set .................................................................................5-11
Web access port .................................................................................. 5-92
User-definable displays
Web server protocol .......................................................................... 5-92
example ..............................................................................................5-123
Windows requirement ..................................................................... 3-53
invoking and scrolling ..................................................................5-122
settings ...............................................................................................5-122
specifications ......................................................................................2-18
User-programmable fault report
actual values .......................................................................................6-12
clearing ........................................................................................ 5-36, 7-2
settings ...............................................................................................5-106
Wire size
F485 converter .................................................................................. 3-53
G.703 and fiber interface ............................................................. 3-45
G.703 interface .................................................................................. 3-38
module 7S ........................................................................................... 3-38
modules 6X, 6W ................................................................................ 3-20
modules 7E, 7F, 7G, 7Q, 75 .......................................................... 3-45
modules 7L, 7M, 7N, 7P, 74 ......................................................... 3-44
modules 7T, 7W ................................................................................ 3-42
power supply module .................................................................... 3-17
RS422 and fiber interface ............................................................ 3-44
RS422 interface ................................................................................ 3-42
Wiring diagrams .................................................................................. 3-10
Withdraw UR from operation ....................................................10-29
Wrong Transceiver message ....................................................... 7-10
X
XOR gate explained ........................................................................... 4-81
Y
Yellow caution icon in Offline Window ................................... 4-67