Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Feeder Protection System: Grid Solutions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 810

GE

Grid Solutions

F60
Feeder Protection System

Instruction Manual
Product version: 8.3x
GE publication code: 1601-0093-AM2

E83849
S T ER
GI
ED
RE

ISO 9001
LISTED
G

E
IN

M U LT I L
IND.CONT. EQ.
52TL

1601-0093-AM2
Copyright © 2022 GE Multilin. All rights reserved.
F60 Feeder Protection System Instruction Manual for version 8.3x.
F60, FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Universal Relay, Multilin, and GE Multilin are trademarks or
registered trademarks of GE Multilin or General Electric Company Corporation.
The contents of this manual are the property of GE Multilin. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
It is the responsibility of the user for verifying and validating the suitability of all GE Grid
Solutions products. This equipment must be used within its design limits. The proper
application including configuration and setting of this product to suit the power system
assets is the responsibility of the user, who is also required to ensure that all local or
regional safety guidelines are adhered to. Incorrect application of this product could risk
damage to property/the environment, personal injuries or fatalities and shall be the sole
responsibility of the person/entity applying and qualifying the product for use.
The content in this document has been developed to provide guidance to properly install,
configure and maintain this product for its intended applications. This guidance is not
intended to cover every possible contingency that may arise during commissioning,
operation, service, or maintenance activities. Should you encounter any circumstance’s
not clearly addressed in this document, contact your local GE service site.
IT IS THE SOLE RESPONSIBILITY OF THE USER TO SECURE THEIR NETWORK AND
ASSOCIATED DEVICES AGAINST CYBER SECURITY INTRUSIONS OR ATTACKS. GE GRID
AUTOMATION AND ITS AFFILIATES ARE NOT LIABLE FOR ANY DAMAGES AND/OR LOSSES
ARISING FROM OR RELATED TO SUCH SECURITY INTRUSION OR ATTACKS.
Part number: 1601-0093-AM2 (October 2022)
F60 Feeder Protection System

Table of contents

1 INTRODUCTION 1.1 Safety symbols and definitions ........................................................................... 1-1


1.1.1 General cautions and warnings .................................................................................... 1-1
1.2 For further assistance........................................................................................... 1-2

2 PRODUCT 2.1 Product description ............................................................................................... 2-1


DESCRIPTION 2.2 Security .................................................................................................................... 2-3
2.2.1 EnerVista security................................................................................................................. 2-3
2.2.2 Password security................................................................................................................ 2-3
2.2.3 CyberSentry security........................................................................................................... 2-4
2.3 Order codes............................................................................................................. 2-7
2.3.1 Order codes with enhanced CT/VT modules........................................................... 2-8
2.3.2 Order codes with process bus modules ..................................................................2-11
2.3.3 Replacement modules .....................................................................................................2-15
2.4 Signal processing ................................................................................................. 2-17
2.4.1 UR signal processing ........................................................................................................2-17
2.5 Specifications........................................................................................................ 2-19
2.5.1 Protection elements ..........................................................................................................2-20
2.5.2 User-programmable elements ....................................................................................2-26
2.5.3 Monitoring..............................................................................................................................2-28
2.5.4 Metering..................................................................................................................................2-29
2.5.5 Inputs .......................................................................................................................................2-30
2.5.6 Power supply ........................................................................................................................2-32
2.5.7 Outputs....................................................................................................................................2-33
2.5.8 Communication protocols..............................................................................................2-35
2.5.9 Inter-relay communications..........................................................................................2-36
2.5.10 CyberSentry security.........................................................................................................2-37
2.5.11 Graphical front panel........................................................................................................2-37
2.5.12 Environmental......................................................................................................................2-38
2.5.13 Type tests ...............................................................................................................................2-39
2.5.14 Production tests ..................................................................................................................2-39
2.5.15 Approvals ...............................................................................................................................2-40
2.5.16 Maintenance.........................................................................................................................2-40

3 INSTALLATION 3.1 Unpack and inspect ............................................................................................... 3-1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL iii


TABLE OF CONTENTS

3.2 Panel cutouts...........................................................................................................3-2


3.2.1 Horizontal units......................................................................................................................3-2
3.2.2 Vertical units............................................................................................................................3-6
3.2.3 Rear terminal layout......................................................................................................... 3-10
3.3 Wiring .....................................................................................................................3-13
3.3.1 Typical wiring ....................................................................................................................... 3-13
3.3.2 Dielectric strength ............................................................................................................. 3-15
3.3.3 Control power ...................................................................................................................... 3-16
3.3.4 CT/VT modules .................................................................................................................... 3-17
3.3.5 Process Bus Module for HardFiber ............................................................................ 3-20
3.3.6 Contact inputs and outputs .......................................................................................... 3-21
3.3.7 Transducer inputs and outputs................................................................................... 3-33
3.3.8 RS232 port............................................................................................................................. 3-35
3.3.9 CPU communication ports ............................................................................................ 3-36
3.3.10 IRIG-B....................................................................................................................................... 3-39
3.4 Direct input and output communications .......................................................3-40
3.4.1 Description ............................................................................................................................ 3-40
3.4.2 Fiber: LED and ELED transmitters............................................................................... 3-43
3.4.3 Fiber laser transmitters................................................................................................... 3-43
3.4.4 G.703 interface.................................................................................................................... 3-44
3.4.5 RS422 interface................................................................................................................... 3-48
3.4.6 RS422 and fiber interface .............................................................................................. 3-50
3.4.7 G.703 and fiber interface................................................................................................ 3-51
3.4.8 IEEE C37.94 interface ....................................................................................................... 3-51
3.4.9 C37.94SM interface........................................................................................................... 3-54
3.5 Activate relay ........................................................................................................3-57
3.6 Install software .....................................................................................................3-58
3.6.1 EnerVista communication overview ......................................................................... 3-58
3.6.2 System requirements....................................................................................................... 3-59
3.6.3 Install software.................................................................................................................... 3-60
3.7 Add device to software........................................................................................3-62
3.7.1 Set IP address in UR.......................................................................................................... 3-62
3.7.2 Configure serial connection.......................................................................................... 3-68
3.7.3 Configure Ethernet connection ................................................................................... 3-69
3.7.4 Configure modem connection.....................................................................................3-70
3.7.5 Automatic discovery of UR devices........................................................................... 3-71
3.8 Connect to the F60 ...............................................................................................3-72
3.8.1 Connect to the F60 in EnerVista.................................................................................. 3-72
3.8.2 Use Quick Connect via front RS232 port................................................................. 3-73
3.8.3 Use Quick Connect via front USB port ..................................................................... 3-74
3.8.4 Use Quick Connect via a rear Ethernet port.......................................................... 3-74
3.9 Set up CyberSentry and change default password........................................3-75
3.10 Import settings .....................................................................................................3-76
3.10.1 import settings from XML file ....................................................................................... 3-76
3.10.2 Import settings from device files ................................................................................ 3-80
3.11 Connect to D400 gateway...................................................................................3-81
3.11.1 Oscillography files.............................................................................................................. 3-81
3.11.2 Event records ....................................................................................................................... 3-81
3.11.3 Log files................................................................................................................................... 3-82
3.11.4 Setting files............................................................................................................................ 3-82

4 INTERFACES 4.1 EnerVista software interface................................................................................4-1


4.1.1 Introduction .............................................................................................................................4-1
4.1.2 Settings files ............................................................................................................................4-1
4.1.3 Event viewing..........................................................................................................................4-2

iv F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


TABLE OF CONTENTS

4.1.4 File support.............................................................................................................................. 4-3


4.1.5 EnerVista main window..................................................................................................... 4-3
4.1.6 Protection summary window ......................................................................................... 4-5
4.1.7 Settings templates............................................................................................................... 4-6
4.1.8 Secure and lock FlexLogic equations........................................................................4-10
4.1.9 Settings file traceability ...................................................................................................4-13
4.2 Front panel interface........................................................................................... 4-16
4.2.1 Front panel ............................................................................................................................4-16
4.2.2 Front panel display ............................................................................................................4-18
4.2.3 Front panel navigation keys..........................................................................................4-39
4.2.4 LED indicators ......................................................................................................................4-40
4.2.5 Front panel labelling .........................................................................................................4-45
4.2.6 Menu navigation.................................................................................................................4-51
4.2.7 Change settings ..................................................................................................................4-53
4.2.8 View actual values.............................................................................................................4-58
4.2.9 Breaker control....................................................................................................................4-59
4.2.10 Change passwords............................................................................................................4-60
4.2.11 Invalid password entry ....................................................................................................4-62
4.3 Logic diagrams ..................................................................................................... 4-63
4.4 FlexLogic design using Engineer ....................................................................... 4-64
4.4.1 Design logic...........................................................................................................................4-66
4.4.2 Send file to and from device .........................................................................................4-76
4.4.3 Monitor logic.........................................................................................................................4-77
4.4.4 View front panel and print labels................................................................................4-78
4.4.5 Generate connectivity report........................................................................................4-78
4.4.6 Preferences ...........................................................................................................................4-79
4.4.7 Toolbars ..................................................................................................................................4-82

5 SETTINGS 5.1 Settings menu......................................................................................................... 5-1


5.2 Overview.................................................................................................................. 5-4
5.2.1 Introduction to elements .................................................................................................. 5-4
5.2.2 Introduction to AC sources .............................................................................................. 5-6
5.3 Product setup.......................................................................................................... 5-8
5.3.1 Security ..................................................................................................................................... 5-8
5.3.2 Display properties ..............................................................................................................5-28
5.3.3 Graphical front panel........................................................................................................5-30
5.3.4 Clear relay records.............................................................................................................5-43
5.3.5 Communications ................................................................................................................5-44
5.3.6 Modbus user map ........................................................................................................... 5-117
5.3.7 Real-time clock.................................................................................................................5-118
5.3.8 Fault reports ......................................................................................................................5-127
5.3.9 Oscillography.....................................................................................................................5-129
5.3.10 Data logger ........................................................................................................................5-132
5.3.11 Demand ...............................................................................................................................5-133
5.3.12 User-programmable LEDs ..........................................................................................5-134
5.3.13 User-programmable self-tests .................................................................................5-139
5.3.14 Control pushbuttons ...................................................................................................... 5-140
5.3.15 User-programmable pushbuttons ..........................................................................5-141
5.3.16 Flex state parameters ...................................................................................................5-147
5.3.17 User-definable displays................................................................................................5-148
5.3.18 Direct inputs and outputs............................................................................................5-150
5.3.19 Teleprotection ...................................................................................................................5-156
5.3.20 Installation ..........................................................................................................................5-157
5.4 Remote resources ..............................................................................................5-158
5.4.1 Remote resources configuration .............................................................................5-158

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL v


TABLE OF CONTENTS

5.5 System setup ...................................................................................................... 5-159


5.5.1 AC inputs ............................................................................................................................. 5-159
5.5.2 Power system ................................................................................................................... 5-160
5.5.3 Signal sources .................................................................................................................. 5-162
5.5.4 Breakers .............................................................................................................................. 5-166
5.5.5 Disconnect switch control .......................................................................................... 5-175
5.5.6 FlexCurves .......................................................................................................................... 5-183
5.5.7 Phasor Measurement Unit.......................................................................................... 5-190
5.6 Process Bus Module .......................................................................................... 5-211
5.6.1 Parallel Redundancy Protocol (PRP) ....................................................................... 5-211
5.6.2 High-availability seamless redundancy (HSR)................................................... 5-212
5.6.3 General ................................................................................................................................ 5-214
5.6.4 SV Stream Config ............................................................................................................ 5-218
5.7 FlexLogic.............................................................................................................. 5-232
5.7.1 FlexLogic operands........................................................................................................ 5-232
5.7.2 FlexLogic rules.................................................................................................................. 5-247
5.7.3 FlexLogic evaluation...................................................................................................... 5-247
5.7.4 FlexLogic example.......................................................................................................... 5-248
5.7.5 FlexLogic equation editor............................................................................................ 5-253
5.7.6 FlexLogic timers............................................................................................................... 5-253
5.7.7 FlexElements ..................................................................................................................... 5-253
5.7.8 Non-volatile latches....................................................................................................... 5-258
5.8 Grouped elements ............................................................................................. 5-260
5.8.1 Overview ............................................................................................................................. 5-260
5.8.2 Setting group 1................................................................................................................. 5-260
5.8.3 Load encroachment ...................................................................................................... 5-260
5.8.4 Phase current ................................................................................................................... 5-262
5.8.5 Neutral current................................................................................................................. 5-275
5.8.6 Wattmetric ground fault.............................................................................................. 5-288
5.8.7 Ground current ................................................................................................................ 5-292
5.8.8 Negative sequence current........................................................................................ 5-302
5.8.9 Breaker failure (ANSI 50BF)......................................................................................... 5-308
5.8.10 Voltage elements ............................................................................................................ 5-317
5.8.11 Sensitive directional power (ANSI 32) .................................................................... 5-327
5.9 Control elements ............................................................................................... 5-330
5.9.1 Overview ............................................................................................................................. 5-330
5.9.2 Trip bus ................................................................................................................................ 5-331
5.9.3 Setting groups .................................................................................................................. 5-333
5.9.4 Selector switch................................................................................................................. 5-335
5.9.5 Underfrequency (ANSI 81U)........................................................................................ 5-342
5.9.6 Overfrequency (ANSI 81O) .......................................................................................... 5-343
5.9.7 Frequency rate of change (ANSI 81R).................................................................... 5-344
5.9.8 Synchrocheck (ANSI 25) ............................................................................................... 5-346
5.9.9 Autoreclose (ANSI 79) .................................................................................................... 5-351
5.9.10 Digital elements............................................................................................................... 5-357
5.9.11 Digital counters................................................................................................................ 5-360
5.10 Monitoring elements......................................................................................... 5-362
5.10.1 Cold load pickup .............................................................................................................. 5-393
5.10.2 Pilot schemes.................................................................................................................... 5-395
5.11 Inputs/outputs ................................................................................................... 5-400
5.11.1 Contact inputs .................................................................................................................. 5-400
5.11.2 Virtual inputs ..................................................................................................................... 5-402
5.11.3 Contact outputs............................................................................................................... 5-403
5.11.4 Virtual outputs.................................................................................................................. 5-407
5.11.5 Resetting ............................................................................................................................. 5-407
5.11.6 Direct inputs and outputs ........................................................................................... 5-408

vi F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


TABLE OF CONTENTS

5.11.7 Teleprotection ...................................................................................................................5-412


5.12 Transducer inputs/outputs ..............................................................................5-414
5.12.1 DCmA inputs ......................................................................................................................5-414
5.12.2 RTD inputs...........................................................................................................................5-415
5.12.3 DCmA outputs...................................................................................................................5-416
5.13 Testing..................................................................................................................5-420
5.13.1 IED mode config...............................................................................................................5-420
5.13.2 Force contact inputs......................................................................................................5-423
5.13.3 Force contact outputs...................................................................................................5-424
5.13.4 Phasor Measurement Unit test values ..................................................................5-424
5.14 Simulation ...........................................................................................................5-426
5.14.1 Subscribe to simulated values ..................................................................................5-426
5.14.2 Publish simulated values .............................................................................................5-428

6 ACTUAL VALUES 6.1 Actual Values menu ............................................................................................... 6-1


6.2 Front panel .............................................................................................................. 6-4
6.2.1 Enhanced and basic front panels................................................................................. 6-4
6.2.2 Graphical front panel.......................................................................................................... 6-4
6.3 Status ....................................................................................................................... 6-5
6.3.1 IED................................................................................................................................................ 6-5
6.3.2 Contact inputs ....................................................................................................................... 6-5
6.3.3 Virtual inputs........................................................................................................................... 6-5
6.3.4 RxGOOSE boolean inputs.................................................................................................. 6-6
6.3.5 RxGOOSE DPS inputs .......................................................................................................... 6-6
6.3.6 Teleprotection inputs.......................................................................................................... 6-6
6.3.7 Contact outputs .................................................................................................................... 6-7
6.3.8 Virtual outputs ....................................................................................................................... 6-7
6.3.9 RxGOOSE status .................................................................................................................... 6-7
6.3.10 RxGOOSE statistics .............................................................................................................. 6-7
6.3.11 Autoreclose ............................................................................................................................. 6-8
6.3.12 Digital counters ..................................................................................................................... 6-8
6.3.13 Breaker status........................................................................................................................ 6-8
6.3.14 Selector switches.................................................................................................................. 6-9
6.3.15 Flex States................................................................................................................................ 6-9
6.3.16 Ethernet .................................................................................................................................... 6-9
6.3.17 Real time clock synchronizing......................................................................................6-10
6.3.18 Hi-Z status .............................................................................................................................6-11
6.3.19 Direct inputs..........................................................................................................................6-11
6.3.20 Direct devices status ........................................................................................................6-11
6.3.21 EGD protocol status ..........................................................................................................6-12
6.3.22 Teleprotection channel tests ........................................................................................6-12
6.3.23 Incipient fault detector ....................................................................................................6-13
6.3.24 Remaining connection status.......................................................................................6-13
6.3.25 Parallel Redundancy Protocol (PRP)...........................................................................6-13
6.3.26 TxGOOSE status ..................................................................................................................6-14
6.3.27 Protocol...................................................................................................................................6-14
6.4 Metering................................................................................................................. 6-15
6.4.1 Metering conventions.......................................................................................................6-15
6.4.2 Sources....................................................................................................................................6-19
6.4.3 Sensitive directional power ...........................................................................................6-25
6.4.4 Synchrocheck.......................................................................................................................6-25
6.4.5 Tracking frequency............................................................................................................6-26
6.4.6 Frequency rate of change..............................................................................................6-26
6.4.7 FlexElements.........................................................................................................................6-26
6.4.8 RxGOOSE analogs ..............................................................................................................6-27

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL vii


TABLE OF CONTENTS

6.4.9 Wattmetric ground fault................................................................................................. 6-27


6.4.10 Phasor Measurement Unit............................................................................................. 6-27
6.4.11 PMU aggregator .................................................................................................................6-28
6.4.12 Restricted ground fault ................................................................................................... 6-28
6.4.13 Transducer inputs and outputs................................................................................... 6-29
6.4.14 Harmonic detection.......................................................................................................... 6-29
6.5 Remote resources.................................................................................................6-29
6.5.1 Field unit................................................................................................................................. 6-29
6.6 Process Bus Module .............................................................................................6-30
6.6.1 General status ..................................................................................................................... 6-30
6.6.2 RxSV status ........................................................................................................................... 6-30
6.6.3 Clock synchronizing .......................................................................................................... 6-31
6.6.4 PRP............................................................................................................................................ 6-32
6.6.5 HSR ........................................................................................................................................... 6-33
6.7 Records...................................................................................................................6-33
6.7.1 Fault reports ......................................................................................................................... 6-33
6.7.2 Event records ....................................................................................................................... 6-34
6.7.3 Oscillography ....................................................................................................................... 6-36
6.7.4 Data logger ........................................................................................................................... 6-36
6.7.5 Phasor Measurement Unit records ........................................................................... 6-37
6.7.6 Breaker maintenance ...................................................................................................... 6-37
6.7.7 Hi-Z records .......................................................................................................................... 6-38
6.8 Product information.............................................................................................6-39
6.8.1 Model information ............................................................................................................. 6-39
6.8.2 Firmware revisions ............................................................................................................ 6-39

7 COMMANDS AND 7.1 Commands menu ...................................................................................................7-1


TARGETS 7.1.1 Virtual inputs ...........................................................................................................................7-2
7.1.2 Clear records...........................................................................................................................7-2
7.1.3 Set date and time..................................................................................................................7-3
7.1.4 Relay maintenance ..............................................................................................................7-3
7.1.5 Phasor Measurement Unit one-shot ...........................................................................7-5
7.1.6 Security ......................................................................................................................................7-6
7.2 Targets menu ..........................................................................................................7-7
7.2.1 Target messages...................................................................................................................7-7
7.2.2 Relay self-tests .......................................................................................................................7-8

8 COMMISSIONING 8.1 Testing ......................................................................................................................8-1


8.1.1 Testing underfrequency and overfrequency elements.......................................8-1

9 THEORY OF 9.1 High-impedance (Hi-Z) fault detection ...............................................................9-1


OPERATION 9.1.1 Description ...............................................................................................................................9-1
9.1.2 Energy algorithm...................................................................................................................9-2
9.1.3 Randomness algorithm......................................................................................................9-2
9.1.4 Expert Arc Detector algorithm........................................................................................9-2
9.1.5 Spectral Analysis algorithm .............................................................................................9-3
9.1.6 Load Event Detector algorithm ......................................................................................9-3
9.1.7 Load Analysis algorithm ....................................................................................................9-3
9.1.8 Load Extraction algorithm ................................................................................................9-3
9.1.9 Arc Burst Pattern Analysis algorithm...........................................................................9-4
9.1.10 Arcing Suspected algorithm ............................................................................................9-4
9.1.11 Overcurrent disturbance monitoring...........................................................................9-4
9.1.12 Hi-Z Even Harmonic Restraint algorithm...................................................................9-4

viii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


TABLE OF CONTENTS

9.1.13 Hi-Z Voltage Supervision algorithm............................................................................. 9-4


9.2 Fault locator............................................................................................................ 9-4
9.2.1 Fault type determination .................................................................................................. 9-4

10 MAINTENANCE 10.1 Monitoring ............................................................................................................. 10-1


10.1.1 Devices with Site Targets................................................................................................10-1
10.1.2 Data with Modbus Analyzer ..........................................................................................10-1
10.2 General maintenance.......................................................................................... 10-3
10.2.1 In-service maintenance ..................................................................................................10-3
10.2.2 Out-of-service maintenance.........................................................................................10-3
10.2.3 Unscheduled maintenance (system interruption)...............................................10-3
10.3 Retrieve files ......................................................................................................... 10-3
10.3.1 CyberSentry security event files ..................................................................................10-4
10.4 Convert device settings ...................................................................................... 10-5
10.5 Copy settings to other device ............................................................................ 10-7
10.6 Export settings...................................................................................................... 10-7
10.7 Compare settings................................................................................................. 10-8
10.7.1 Compare against defaults .............................................................................................10-8
10.7.2 Compare two devices.......................................................................................................10-8
10.8 Back up and restore settings ............................................................................. 10-9
10.8.1 Back up settings..................................................................................................................10-9
10.8.2 Restore settings ...............................................................................................................10-12
10.9 Upgrade software ..............................................................................................10-14
10.10 Upgrade firmware..............................................................................................10-15
10.11 Replace module ..................................................................................................10-17
10.12 Battery .................................................................................................................10-19
10.12.1 Replace battery ................................................................................................................10-19
10.12.2 Dispose of battery...........................................................................................................10-20
10.13 Clear files and data after uninstall .................................................................10-23
10.14 Repairs .................................................................................................................10-24
10.15 Storage.................................................................................................................10-24
10.16 Disposal ...............................................................................................................10-25

A FLEXANALOG A.1 FlexAnalog items .................................................................................................... A-1


OPERANDS

B RADIUS SERVER B.1 RADIUS server configuration ............................................................................... B-1


CONFIGURATION

C COMMAND LINE C.1 Command line interface ....................................................................................... C-1


INTERFACE

D MISCELLANEOUS D.1 Warranty .................................................................................................................D-1


D.2 Revision history ......................................................................................................D-1
D.2.1 Major changes ........................................................................................................................D-3
D.3 Open source licenses ............................................................................................D-3

ABBREVIATIONS

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL ix


TABLE OF CONTENTS

INDEX

x F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 1: Introduction

Introduction

This chapter outlines safety and technical support information.

1.1 Safety symbols and definitions


Before attempting to install or use the device, review all safety indicators in this document to help prevent injury,
equipment damage, or downtime.
The following safety and equipment symbols are used in this document.

Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Indicates a hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

Indicates practices not related to personal injury.

1.1.1 General cautions and warnings


The following general safety precautions and warnings apply.

Ensure that all connections to the product are correct so as to avoid accidental risk of shock
and/or fire, for example such as can arise from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the alternating current (AC), and voltage input match the ratings
specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1-1


FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION

Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
1 Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working
on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
Personal safety can be affected if the product is physically modified by the end user. Modifications to the product
outside of recommended wiring configuration, hardware, or programming boundaries is not recommended end-use
practice. Product disassembly and repairs are not permitted. All service needs to be conducted by the factory.

LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
devices are considered safe to the unaided eye. Do not view directly with optical instruments.

This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
environments. Not to be used near electronic devices rated for Class B levels.

1.2 For further assistance


For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: multilin.tech@ge.com
Europe e-mail: multilin.tech.euro@ge.com
Website: http://www.gegridsolutions.com/multilin
When contacting GE by e-mail, optionally include a device information file, which is generated in the EnerVista software by
clicking the Service Report button. The service report also can be generated in the field, for example with a USB cable
connected between the graphical front panel and a computer, and the Device Setup configured for the USB connection.

1-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 1: INTRODUCTION FOR FURTHER ASSISTANCE

Figure 1-1: Generate service report in EnerVista software

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1-3


FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION

1-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 2: Product description

Product description

This chapter outlines the product, order codes, and specifications.

2.1 Product description


The F60 Feeder Protection System is part of the Universal Relay (UR) family of products. It is a microprocessor-based relay
for feeder protection.
Overvoltage and undervoltage protection, overfrequency and underfrequency protection, breaker failure protection,
directional current supervision, fault diagnostics, remote terminal unit (RTU), and programmable logic functions are
provided. This relay also provides phase, neutral, ground and negative sequence, instantaneous and time overcurrent
protection. The time overcurrent function provides multiple curve shapes or FlexCurves™ for optimum co-ordination.
Automatic reclosing, synchrocheck, and line fault locator features are also provided. When equipped with a type 8Z current
transformer/voltage transformer (CT/VT) module, an element for detecting high impedance faults is provided.
Voltage, current, and power metering are built in as standard features. Current parameters are available as total
waveform root mean square (RMS) magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder that stores 1024 time-tagged events. The internal clock used for time-
tagging can be synchronized with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port,
or using the Precision Time Protocol (PTP). This precise time stamping allows the sequence of events to be determined
throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture
that can be set to record the measured parameters before and after the event for viewing on a computer. These tools
significantly reduce troubleshooting time and simplify report generation in the event of a system fault.
Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to
connect to a computer to program settings and monitor actual values. The rear RS485 port allows independent access by
operating and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports
use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. IEC 60870-5-103, DNP,
and Modbus cannot be enabled simultaneously on this interface. Also only one of the DNP, IEC 60870-5-103, and IEC
60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103 protocol is chosen, the RS485
port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The 100Base-FX or 100Base-TX Ethernet
interface provides fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850, IEC 61850-
90-5, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any
standard web browser (F60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port
also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
GOOSE and secure Routable GOOSE (R-GOOSE) are supported with software options. Process Bus GOOSE is supported with
a hardware module and software options.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-1


PRODUCT DESCRIPTION CHAPTER 2: PRODUCT DESCRIPTION

With a Process Bus Module that supports IEC 61850-9-2LE and IEC 61869, PRP is supported on two Ethernet ports to IEC
62439, and High-availability Seamless Redundancy (HSR) is supported on four Ethernet ports for dual HSR ring
architecture.
Settings and actual values can be accessed from the front panel or EnerVista software.
The F60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
2 device numbers.
Table 2-1: ANSI device numbers and functions supported
Device number Function Device number Function
25 Synchrocheck 51_2 Negative-sequence time overcurrent
27P Phase undervoltage 52 AC circuit breaker
27X Auxiliary undervoltage 59N Neutral overvoltage
32 Sensitive directional power 59P Phase overvoltage
32N Wattmetric zero-sequence directional 59X Auxiliary overvoltage
49 Thermal overload protection 59_2 Negative-sequence overvoltage
50BF/50NBF Breaker failure 67N Neutral directional overcurrent
50DD Disturbance detector 67P Phase directional overcurrent
50G Ground instantaneous overcurrent 67_2 Negative-sequence directional overcurrent
50N Neutral instantaneous overcurrent 79 Automatic recloser
50P Phase instantaneous overcurrent 81O Overfrequency
50_2 Negative-sequence instantaneous overcurrent 81R Rate of change frequency
51G Ground time overcurrent 81U Underfrequency
51N Neutral time overcurrent 87RGF Restricted ground fault
51P Phase time overcurrent

Figure 2-1: Single-line diagram

52

79
CLOSE TRIP 81R
Monitoring

81U

81O
50P 50_2 51_2 50BF 51P/V 67P 67_2 32 49 50N 51N 67N/G 32N 50NBF

27P

Transducer 59P
FlexElementTM Metering + PMU Inputs

59N
87RGF 50G 51G

59_2
27X 59X

25

F60 Feeder Protection System


832784A1.CDR

2-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SECURITY

Table 2-2: Other device functions


Function Function Function
Breaker arcing current (I2t) Ethernet Global Data Pilot schemes
Breaker control Event recorder Setting groups (6)
Breaker flashover Fault detector and fault report Synchrophasor (PMU)
Breaker restrike Fault locator Thermal overload protection
Broken conductor detection FlexElements™ (16) Time synchronization over IRIG-B or IEEE
1588 2
Cold load pickup FlexLogic equations Time synchronization over SNTP
Contact inputs (up to 120) High impedance fault detection (Hi-Z) Transducer inputs and outputs
Contact outputs (up to 72) IEC 60870-5-103 communications User-definable displays
Control pushbuttons IEC 61850 communications User-programmable LEDs
CT failure detector IEC 62351-9 data and communications User-programmable pushbuttons
security
CyberSentry™ security Incipient cable fault detection User-programmable self-tests
Data logger Load encroachment Virtual inputs (128)
Demand Metering: current, voltage, power, PF, Virtual outputs (256)
energy, frequency, harmonics, THD
Digital counters (8) Modbus user map VT fuse failure
Digital elements (96) Non-volatile latches
Direct inputs and outputs (32) Non-volatile selector switch
Disconnect switches Oscillography

2.2 Security
The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled
automatically, and the default Password security and EnerVista security are disabled.
To maximize security, see the UR Family Secure Deployment Guide.

2.2.1 EnerVista security


The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security
management system is disabled by default to allow the administrator direct access to the EnerVista software after
installation. It is recommended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.

2.2.2 Password security


Password security is a basic security feature present by default.
Two levels of password security are provided: command and setting. Use of a password for each level controls whether all
users can enter commands and/or change settings.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-3


SECURITY CHAPTER 2: PRODUCT DESCRIPTION

Two types of connection security are provided: password entry from local or remote connection. Local access is defined as
access to settings or commands via the front panel interface. This includes both keypad entry and the through a front
panel port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. These two settings are on by default and apply to all users.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the F60, the remote password is used. If the
connection is to a front panel port, the local password applies. (These two local and remote password settings are not
shown in the figure.)
2 Password access events are logged in the Event Recorder.
Figure 2-2: Access control by passwords and connection type

2.2.3 CyberSentry security


CyberSentry security is available using software options that provide advanced security. When the option is purchased, the
basic password security is disabled automatically.
CyberSentry provides security through the following features:
• An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that is
managed centrally, enables user attribution, provides accounting of all user activities, and uses secure standards-
based strong cryptography for authentication and credential protection. In other words, this option uses a RADIUS
server for user authentication.
• A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device
operations and configurations based on specific roles and individual user accounts configured on the AAA server.
That is, Administrator, Supervisor, Engineer, Operator, and Observer roles are used.
• Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring
• Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the National
Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems

CyberSentry user roles


CyberSentry user roles (Administrator, Supervisor, Engineer, Operator, Observer) limit the levels of access to various UR
functions. This means that the EnerVista software allows for access to functionality based on the user’s logged in role.
Example: Administrative functions can be segmented from common operator functions, or engineering type access, all of
which are defined by separate roles so that access of UR devices by multiple personnel within a substation is allowed.

2-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SECURITY

One role of one type is allowed to be logged in at a time. For example, one Operator can be logged in but not a second
Operator at the same time. This prevents subsets of settings from being changed at the same time.
Figure 2-3: CyberSentry user roles

Administrator

Engineer

Operator 2
Observer Supervisor

842838A2.CDR

The table lists user roles and permissions.

Table 2-3: Permissions by user role with CyberSentry


Administrator Engineer Operator Supervisor Observer
Summary Complete access Complete access Command Authorizes Default role
except for menu writing
CyberSentry
Security
Device Definition R R R R R
Settings
|---------- Product Setup
|--------------- Security RW R R R R
(CyberSentry)
|--------------- Supervisory See table notes R R See table R
notes
|--------------- Display Properties RW RW R R R
|--------------- Clear Relay Records RW RW R R R
(settings)
|--------------- Communications RW RW R R R
|--------------- Modbus User Map RW RW R R R
|--------------- Real Time Clock RW RW R R R
|--------------- Oscillography RW RW R R R
|--------------- Data Logger RW RW R R R
|--------------- Demand RW RW R R R
|--------------- User-Programmable RW RW R R R
LEDs
|--------------- User-Programmable RW RW R R R
Self Tests
|--------------- Control Pushbuttons RW RW R R R
|--------------- User-Programmable RW RW R R R
Pushbuttons
|--------------- Flex state RW RW R R R
Parameters
|--------------- User-Definable RW RW R R R
Displays
|--------------- Direct I/O RW RW R R R
|--------------- Teleprotection RW RW R R R

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-5


SECURITY CHAPTER 2: PRODUCT DESCRIPTION

Administrator Engineer Operator Supervisor Observer


|--------------- Installation RW RW R R R
|---------- System Setup RW RW R R R
|---------- FlexLogic RW RW R R R
|---------- Grouped Elements RW RW R R R
|---------- Control Elements RW RW R R R
|---------- Inputs / Outputs RW RW R R R
2 |--------------- Contact Inputs RW RW R R R
|--------------- Contact Input RW RW R R R
threshold
|--------------- Virtual Inputs RW RW R R R
|--------------- Contact Outputs RW RW R R R
|--------------- Virtual Outputs RW RW R R R
|--------------- Resetting RW RW R R R
|--------------- Direct Inputs RW RW R R R
|--------------- Direct Outputs RW RW R R R
|--------------- Teleprotection RW RW R R R
|--------------- Direct Analogs RW RW R R R
|--------------- Direct Integers RW RW R R R
|---------- Transducer I/O RW RW R R R
|---------- Testing RW RW R R R
|---------- Front Panel Label Designer NA NA NA NA NA
|---------- Protection Summary NA NA NA NA NA
Commands RW RW RW R R
|---------- Virtual Inputs RW RW RW R R
|---------- Clear Records RW RW RW R R
|---------- Set Date and Time RW RW RW R R
User Displays R R R R R
Targets R R R R R
Actual Values R R R R R
|---------- Front Panel R R R R R
|---------- Status R R R R R
|---------- Metering R R R R R
|---------- Transducer I/O R R R R R
|---------- Records R R R R R
|---------- Product Info R R R R R
Maintenance RW RW R R R
|---------- Modbus Analyzer NA NA NA NA NA
|---------- Change front panel RW RW RW R R
|---------- Update firmware Yes No No No No
|---------- Retrieve file Yes No No No No

Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security

2-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES

2.2.3.1 CyberSentry user authentication


The following types of authentication are supported by CyberSentry to access the UR device:
• Device Authentication (local UR device authenticates)
• Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or the RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the 2
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator, or Administrator and
Supervisor when Device Authentication is disabled) as login names and the associated passwords are stored on the UR
device. As such, when using the local accounts, access is not user-attributable.
In cases where user-attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor is such
information ever transmitted without cryptographic protection.

CyberSentry server authentication


The UR has been designed to direct automatically the authentication requests based on user names. In this respect, local
account names on the UR are considered as reserved and not used on a RADIUS server.
The UR detects automatically whether an authentication request is to be handled remotely or locally. As there are five local
accounts possible on the UR, if the user ID credential does not match one of the five local accounts, the UR forwards
automatically the request to a RADIUS server when one is provided.
If a RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In this
situation, use local UR accounts to gain access to the UR system.

2.3 Order codes


The order code is on the product label and indicates the product options applicable.
The F60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following
modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay
communications. Module options are specified at the time of ordering.
The order codes shown here are subject to change without notice. See the web page for the product for the latest options.
The letters in the top row of the table correspond to slots in the UR chassis, for example slot F, H, or U.

The R-GOOSE protocol described in IEC 61850-8-1 is available through the IEC 61850 software option. R-GOOSE
security requires the CyberSentry software option.
Process Bus GOOSE requires an IEC 61850-9-2LE / IEC 61869 Process Bus Module, as well as IEC 61850, PRP, and
IEEE 1588 software options.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are
in English.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-7


ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION

2.3.1 Order codes with enhanced CT/VT modules


Table 2-4: F60 order codes for horizontal units
F60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT F60 | | | | | | | | | | | Base Unit
CPU T | | | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX
(SFP with RJ45)
V | | | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
W | | | | | | | | | | RS485 with Two 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet,
RJ-45

2 SOFTWARE OPTIONS 00
01
03
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
No software options
Ethernet Global Data (EGD)
IEC 61850
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | Phasor measurement unit (PMU) and IEC 61850
A0 | | | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
A6 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
B0 | | | | | | | | | IEEE 1588
B1 | | | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
B6 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | | | PRP and IEC 61850
C4 | | | | | | | | | PRP, Ethernet Global Data, and IEC 61850
C6 | | | | | | | | | PRP and PMU
C7 | | | | | | | | | PRP, IEC 61850, and PMU
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
D6 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit
(PMU)
E0 | | | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | | | IEEE 1588, PRP, and Ethernet Global Dada
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
E6 | | | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
F0 | | | | | | | | | PRP and CyberSentry Lvl1
F1 | | | | | | | | | PRP, CyberSentry Lvl1, and Ethernet Global Data
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
F6 | | | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G1 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
G6 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
J0 | | | | | | | | | IEC 60870-5-103
J1 | | | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
J6 | | | | | | | | | IEC 60870-5-103 + PMU
J7 | | | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU
K0 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103
K1 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
K6 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + PMU
K7 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU
L0 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
L6 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PMU
L7 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850 + PMU
M0 | | | | | | | | | IEC 61850 + PMU + 61850-90-5
M7 | | | | | | | | | CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MD | | | | | | | | | IEEE 1588 + IEC 61850 + PMU + 61850-90-5
MJ | | | | | | | | | PRP + IEC 61850 + PMU + 61850-90-5
MP | | | | | | | | | IEEE 1588 + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MV | | | | | | | | | IEEE 1588 + PRP + IEC 61850 + PMU + 61850-90-5
N1 | | | | | | | | | PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
N7 | | | | | | | | | IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
ND | | | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NJ | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NP | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU +
61850-90-5

2-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES

F60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount


MOUNT/COATING H | | | | | | | | Horizontal (19” rack) - Standard
A | | | | | | | | Horizontal (19” rack) - With harsh environmental coating
FRONT PANEL + INTERFACE C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons

2
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
H | | | | | | | Enhanced front panel with Polish display
O | | | | | | | Enhanced front panel with Polish display and user-programmable pushbuttons
E | | | | | | | 7" Graphical front panel display in multiple languages with USB front port and
user-programmable pushbuttons (English, French, Chinese, Russian, Turkish,
German, Polish, Japanese)
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
CT/VT DSP | | XX | XX | No DSP module (slots M and U only)
(8L, 8M, 8N, 8R require all DSPs to be 8L | 8L | | | Standard 4CT/4VT with enhanced diagnostics
enhanced diagnostic) 8M | 8M | | | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | | | Standard 8CT with enhanced diagnostics
8R | 8R | | | Sensitive Ground 8CT with enhanced diagnostics
| | 8Z * | | | Hi-Z 4CT (required for high-impedance fault detection element)
CONTACT INPUTS/OUTPUTS XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 4D 4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 4L 4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 6C 6C 8 Form-C outputs
6D 6D 6D 6D 6D 16 Contact inputs
6E 6E 6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 1 Form-A latching output, 8 contact inputs
6W 6W 6W 6W 6W 30 Contact inputs - pin terminals (max 4 modules)
6X 6X 6X 6X 6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
TRANSDUCER INPUTS/OUTPUTS 5A 5A 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
(select a maximum of 3 per unit) 5C 5C 5C 5C 5C 8 RTD inputs
5D 5D 5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
5E 5E 5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 5F 5F 8 DCmA inputs
INTER-RELAY COMMUNICATIONS 2A 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
(select a maximum of 1 per unit) 2B 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
Laser
2J 2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 72 1550 nm, single-mode, Laser, 1 Channel
73 73 1550 nm, single-mode, Laser, 2 Channel
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multimode, LED, 1 Channel
7B 7B 1300 nm, multimode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, Laser, 1 Channel
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multimode, LED, 2 Channels
7I 7I 1300 nm, multimode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, Laser, 2 Channels
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7W 7W RS422, 2 Channels
* When an 8Z module is ordered, slot F must have an 8L module. When 8Z is used alongside a CT/VT module with enhanced diagnostics,
enhanced diagnostics is not enabled because 8Z does not offer enhanced diagnostics.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-9


ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION

Table 2-5: F60 order codes for reduced-size vertical units


F60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT F60 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX
(SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
W | | | | | | | | RS485 with Two 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet,
RJ-45
SOFTWARE OPTIONS 00 | | | | | | | No software options
01 | | | | | | | Ethernet Global Data (EGD)
03 | | | | | | | IEC 61850
04 | | | | | | | Ethernet Global Data (EGD) and IEC 61850

2 06
07
A0
A1
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Phasor measurement unit (PMU)
Phasor measurement unit (PMU) and IEC 61850
CyberSentry Lvl 1
CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
A6 | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
B0 | | | | | | | IEEE 1588
B1 | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
B6 | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | PRP and IEC 61850
C4 | | | | | | | PRP, Ethernet Global Data, and IEC 61850
C6 | | | | | | | PRP and PMU
C7 | | | | | | | PRP, IEC 61850, and PMU
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
D6 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit
(PMU)
E0 | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | IEEE 1588, PRP, and Ethernet Global Dada
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
E6 | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
F0 | | | | | | | PRP and CyberSentry Lvl1
F1 | | | | | | | PRP, CyberSentry Lvl1, and Ethernet Global Data
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
F6 | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G0 | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G1 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
G6 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
J0 | | | | | | | IEC 60870-5-103
J1 | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
J6 | | | | | | | IEC 60870-5-103 + PMU
J7 | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU
K0 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
K6 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + PMU
K7 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
L6 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PMU
L7 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850 + PMU
M0 | | | | | | | IEC 61850 + PMU + 61850-90-5
M7 | | | | | | | CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MD | | | | | | | IEEE 1588 + IEC 61850 + PMU + 61850-90-5
MJ | | | | | | | PRP + IEC 61850 + PMU + 61850-90-5
MP | | | | | | | IEEE 1588 + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MV | | | | | | | IEEE 1588 + PRP + IEC 61850 + PMU + 61850-90-5
N1 | | | | | | | PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
N7 | | | | | | | IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
ND | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NJ | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NP | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU +
61850-90-5
MOUNT/COATING V | | | | | | Vertical (3/4 rack) - Standard
B | | | | | | Vertical (3/4 rack) - With harsh environmental coating
FRONT PANEL + INTERFACE F | | | | | English display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons

2-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES

F60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
CT/VT DSP XX | XX | No DSP module (slots F and M only)
(8L, 8M, 8N, 8R require all DSPs to be 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
enhanced diagnostic) 8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
| | 8Z * | Hi-Z 4CT (required for high-impedance fault detection element)
CONTACT INPUTS/OUTPUTS XX XX XX No module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)

2
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 Contact inputs
6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
6W 6W 6W 30 Contact inputs - pin terminals (max 4 modules)
6W 6X 6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
TRANSDUCER INPUTS/OUTPUTS 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
(select a maximum of 3 per unit) 5C 5C 5C 8 RTD inputs
5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 8 DCmA inputs
INTER-RELAY COMMUNICATIONS 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
(select a maximum of 1 per unit) 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
For the last module, rear slot P is used for digital and 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
transducer input/output modules; rear slot R is used 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
for inter-relay communications modules. Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
* When an 8Z module is ordered, slot F must have an 8L module. When 8Z is used alongside a CT/VT module with enhanced
diagnostics, enhanced diagnostics is not enabled because 8Z does not offer enhanced diagnostics.

2.3.2 Order codes with process bus modules


Table 2-6: F60 order codes for horizontal units with process bus
F60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT F60 | | | | | | | | | | | Base Unit
CPU T | | | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX
(SFP with RJ45)
V | | | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
W | | | | | | | | | | RS485 with Two 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet,
RJ-45

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-11


ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION

F60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount


SOFTWARE OPTIONS 00 | | | | | | | | | No software options
01 | | | | | | | | | Ethernet Global Data (EGD)
03 | | | | | | | | | IEC 61850
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | Phasor measurement unit (PMU) and IEC 61850
A0 | | | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
A6 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
B0 | | | | | | | | | IEEE 1588

2
B1 | | | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
B6 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | | | PRP and IEC 61850
C4 | | | | | | | | | PRP, Ethernet Global Data, and IEC 61850
C6 | | | | | | | | | PRP and PMU
C7 | | | | | | | | | PRP, IEC 61850, and PMU
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
D6 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit
(PMU)
E0 | | | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | | | IEEE 1588, PRP, and Ethernet Global Dada
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
E6 | | | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
F0 | | | | | | | | | PRP and CyberSentry Lvl1
F1 | | | | | | | | | PRP, CyberSentry Lvl1, and Ethernet Global Data
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
F6 | | | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G1 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
G6 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
J0 | | | | | | | | | IEC 60870-5-103
J1 | | | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
J6 | | | | | | | | | IEC 60870-5-103 + PMU
J7 | | | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU
K0 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103
K1 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
K6 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + PMU
K7 | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU
L0 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
L6 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PMU
L7 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850 + PMU
M0 | | | | | | | | | IEC 61850 + PMU + 61850-90-5
M7 | | | | | | | | | CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MD | | | | | | | | | IEEE 1588 + IEC 61850 + PMU + 61850-90-5
MJ | | | | | | | | | PRP + IEC 61850 + PMU + 61850-90-5
MP | | | | | | | | | IEEE 1588 + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MV | | | | | | | | | IEEE 1588 + PRP + IEC 61850 + PMU + 61850-90-5
N1 | | | | | | | | | PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
N7 | | | | | | | | | IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
ND | | | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NJ | | | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NP | | | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU +
61850-90-5
MOUNT/COATING H | | | | | | | | Horizontal (19” rack) - Standard
A | | | | | | | | Horizontal (19” rack) - With harsh environmental coating
FRONT PANEL + INTERFACE C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
H | | | | | | | Enhanced front panel with Polish display
O | | | | | | | Enhanced front panel with Polish display and user-programmable pushbuttons

2-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES

F60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount


E | | | | | | | 7" Graphical front panel display in multiple languages with USB front port and
user-programmable pushbuttons (English, French, Chinese, Russian, Turkish,
German, Polish, Japanese)
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS XX 81 XX | | | IEC 61850 Process Bus Module for HardFiber, 8 x
(non-HardFiber requires IEC 61850, XX 85 XX | | | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 2 x 1000Base-SX, LC
PRP, IEEE 1588 software options) XX 86 XX | | | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 1000Base-SX + 4 x
100Base-FX, LC
XX 87 XX | | | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 100Base-FX, LC
CONTACT INPUTS/OUTPUTS XX XX XX XX XX No module
4A
4B
4C
4D
4A
4B
4C
4D
|
|
|
|
4 Solid-State (no monitoring) MOSFET outputs
4 Solid-State (voltage with optional current) MOSFET outputs
4 Solid-State (current with optional voltage) MOSFET outputs
16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
2
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 Contact inputs
6E 6E | 4 Form-C outputs, 8 contact inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
6W 6W | 30 Contact inputs - pin terminals (max 4 modules)
6X 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
INTER-RELAY COMMUNICATIONS 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
(select a maximum of 1 per unit) 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels

Table 2-7: F60 order codes for reduced-size vertical units with process bus
F60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT F60 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX
(SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
W | | | | | | | | RS485 with Two 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet,
RJ-45
SOFTWARE OPTIONS 00 | | | | | | | No software options
01 | | | | | | | Ethernet Global Data (EGD)
03 | | | | | | | IEC 61850
04 | | | | | | | Ethernet Global Data (EGD) and IEC 61850
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | Phasor measurement unit (PMU) and IEC 61850
A0 | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
A6 | | | | | | | CyberSentry Lvl 1 and phasor measurment unit (PMU)
A7 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
B0 | | | | | | | IEEE 1588
B1 | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
B6 | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
C0 | | | | | | | Parallel Redundancy Protocol (PRP)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-13


ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION

F60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
C1 | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | PRP and IEC 61850
C4 | | | | | | | PRP, Ethernet Global Data, and IEC 61850
C6 | | | | | | | PRP and PMU
C7 | | | | | | | PRP, IEC 61850, and PMU
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
D6 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit
(PMU)
E0 | | | | | | | IEEE 1588 and PRP

2 E1
E3
E4
E6
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IEEE 1588, PRP, and Ethernet Global Dada
IEEE 1588, PRP, and IEC 61850
IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
IEEE 1588, PRP, and PMU
E7 | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
F0 | | | | | | | PRP and CyberSentry Lvl1
F1 | | | | | | | PRP, CyberSentry Lvl1, and Ethernet Global Data
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
F6 | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G0 | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G1 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
G6 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
J0 | | | | | | | IEC 60870-5-103
J1 | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
J6 | | | | | | | IEC 60870-5-103 + PMU
J7 | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU
K0 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
K6 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + PMU
K7 | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
L6 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PMU
L7 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850 + PMU
M0 | | | | | | | IEC 61850 + PMU + 61850-90-5
M7 | | | | | | | CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MD | | | | | | | IEEE 1588 + IEC 61850 + PMU + 61850-90-5
MJ | | | | | | | PRP + IEC 61850 + PMU + 61850-90-5
MP | | | | | | | IEEE 1588 + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
MV | | | | | | | IEEE 1588 + PRP + IEC 61850 + PMU + 61850-90-5
N1 | | | | | | | PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
N7 | | | | | | | IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5
ND | | | | | | | IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NJ | | | | | | | IEEE 1588 + PRP + IEC 60870-5-103 + IEC 61850 + PMU + 61850-90-5
NP | | | | | | | IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU +
61850-90-5
MOUNT/COATING V | | | | | | Vertical (3/4 rack) - Standard
B | | | | | | Vertical (3/4 rack) - With harsh environmental coating
FRONT PANEL + INTERFACE F | | | | | English display
D | | | | | French display
R | | | | | Russian display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
PROCESS BUS XX 81 XX | IEC 61850 Process Bus Module for HardFiber, 8 x
(non-HardFiber requires IEC 61850, XX 85 XX | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 2 x 1000Base-SX, LC
PRP, IEEE 1588 software options) XX 86 XX | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 1000Base-SX + 4 x
100Base-FX, LC
XX 87 XX | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 100Base-FX, LC

2-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES

F60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
CONTACT INPUTS/OUTPUTS XX XX XX No module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 8 Form-C outputs
6D 16 Contact inputs
6E 4 Form-C outputs, 8 contact inputs
6F 8 Fast Form-C outputs

2
6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
6W 30 Contact inputs - pin terminals (max 4 modules)
6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
INTER-RELAY COMMUNICATIONS 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
(select a maximum of 1 per unit) 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
For the last module, rear slot P is used for digital 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
input/output modules; rear slot R is used for 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
inter-relay communications modules. Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels

2.3.3 Replacement modules


Replacement modules can be ordered separately. When ordering a replacement CPU module or front panel, provide the
serial number of your existing unit.
Not all replacement modules apply to the F60 relay. The modules specified in the order codes for the F60 are available as
replacement modules for the F60.
The order codes shown here are subject to change without notice. See the web page for the product for the latest options.
Table 2-8: UR order codes for replacement modules, horizontal units
UR - ** - *
POWER SUPPLY | SH A| 125 / 300 V AC/DC
redundant supply only available in horizontal | SL A| 24 to 48 V (DC only)
units and must be same type as main supply
CPU | T | RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
| U | RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet, multimode, SFP with LC
| V | RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
| W | RS485 with 2 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet, RJ-45
FRONT PANEL + INTERFACE | 3C | Horizontal front panel with keypad and English display
| 3D | Horizontal front panel with keypad and French display
| 3R | Horizontal front panel with keypad and Russian display
| 3A | Horizontal front panel with keypad and Chinese display
| 3P | Horizontal front panel with keypad, user-programmable pushbuttons, and English display
| 3G | Horizontal front panel with keypad, user-programmable pushbuttons, and French display
| 3S | Horizontal front panel with keypad, user-programmable pushbuttons, and Russian display
| 3B | Horizontal front panel with keypad, user-programmable pushbuttons, and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
| 3I | Enhanced front panel with German display
| 3J | Enhanced front panel with German display and user-programmable pushbuttons

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-15


ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION

UR - ** - *
| 3H | Enhanced front panel with Polish display
| 3O | Enhanced front panel with Polish display and user-programmable pushbuttons
| 3Z | Enhanced front panel with Japanese display
| 3X | Enhanced front panel with Japanese display and user-programmable pushbuttons
| 3E | 7" Graphical front panel display in multiple languages with USB front port and user-programmable pushbuttons
CONTACT INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs

2
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
| 6W | 30 Contact inputs - pin terminals (max 4 modules)
| 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
| 8Z * | Hi-Z 4CT
PROCESS BUS MODULES | 81 | IEC 61850 Process Bus Module for HardFiber, 8 x
| 85 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 2 x 1000Base-SX, LC
| 86 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 1000Base-SX + 4 x 100Base-FX, LC
| 87 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 100Base-FX, LC
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
* When an 8Z module is ordered, slot F must have an 8L module. When 8Z is used alongside a CT/VT module with enhanced diagnostics, enhanced diagnostics is not enabled
because 8Z does not offer enhanced diagnostics.

Table 2-9: UR order codes for replacement modules, vertical units


UR - ** - *
POWER SUPPLY | SH B| 125 / 300 V AC/DC
| SL B| 24 to 48 V (DC only)
CPU | T | RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
| U | RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet, multimode, SFP with LC
| V | RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
| W | RS485 with 2 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet, RJ-45
FRONT PANEL + INTERFACE | 3F | Vertical front panel with keypad and English display
| 3D | Vertical front panel with keypad and French display
| 3R | Vertical front panel with keypad and Russian display
| 3A | Vertical front panel with keypad and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
| 3I | Enhanced front panel with German display
| 3J | Enhanced front panel with German display and user-programmable pushbuttons

2-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SIGNAL PROCESSING

UR - ** - *
CONTACT INPUTS/OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs

2
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
| 6W | 30 Contact inputs - pin terminals (max 4 modules)
| 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
| 8Z * | HI-Z 4CT
PROCESS BUS | 81 | IEC 61850 Process Bus Module for HardFiber, 8 x
| 85 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 2 x 1000Base-SX, LC
| 86 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 1000Base-SX + 4 x 100BaseFx, LC
| 87 | IEC 61850-9-2LE and IEC 61869 Process Bus Module, 4 x 100Base-FX, LC
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
* When an 8Z module is ordered, slot F must have an 8L module. When 8Z is used alongside a CT/VT module with enhanced diagnostics, enhanced diagnostics is not enabled
because 8Z does not offer enhanced diagnostics.

2.4 Signal processing


2.4.1 UR signal processing
The URs are microprocessor-based protective relays that are designed to measure power system conditions directly via CT
and VT inputs and via other sources of information, such as analog inputs, communications inputs, and contact inputs. The
following figure shows the overall signal processing in URs.
An analog low pass anti-aliasing filter with a 3 dB corner frequency is set at 2.4 kHz and is used for current and voltage
analog filtering as well as signal conditioning. The same filtering is applied for phase, ground currents, phase-to-phase
(when applicable), and auxiliary voltages. The 2.4 kHz cut-off frequency applies to both 50 and 60 Hz applications and fixed
in the hardware, and thus is not dependent on the system nominal frequency setting.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-17


SIGNAL PROCESSING CHAPTER 2: PRODUCT DESCRIPTION

Figure 2-4: UR signal processing

Analog Analog low- Analog-to- Digital band- Phasor


Inputs pass filter Digital pass filter estimation
Converter
½ cycle Fundament
U A Fourier al freq.
Phasors,
From 1 cycle Seq. com-

2 CT/VT Fourier ponents

I Frequency
D
T
RMS
values

Synchro-
Sampling phasors Analog Outputs
frequency filtering
DSP module module

Tracking
HMI frequency Events
selection,
Protection
Ethernet algorithms
ports
estimation Control Comtrade, data
I> elements,
Commun logger
Serial i-cation Z< monitoring

Serial
ports protocols U< elements,
FlexLogic, DNP, Modbus,
IEC60870
IRIG-B Accurate
Real- Time PMU (IEEE C37.118,
IEEE stamping

Ethernet
1588 Time Synchrophasors IEC 61850-90-5)
clock Aggregation,
SNTP calculations post-filtering IEC 61850 (GOOSE,
CPU module MMS Server)
comms module
Contact Inputs

Analog Inputs
Inter-relay

Inter-relay
module

module

Channel comms module


Ddebounce monitorin A
filtering g CRC
check D Contact Outputs
module

G.703, RS-422,
Optoisolated C37.94, direct fiber DCmA, RTD
859740A1.vsd

The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is adjusted dynamically to the actual system frequency by an accurate and fast frequency tracking
system.
The analog/digital converter has the following ranges of AC signals:
Voltages:

r 2 ˜ 260 V Eq. 2-1

Currents:

r 2 ˜ 46rated A Eq. 2-2

Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.

2-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

True RMS value for the current is calculated on a per-phase basis. The true RMS can be used for demand recording or as an
input signal to Time Overcurrent function, if the latter is intended for thermal protection. The true RMS is calculated as per
the widely accepted definition:

t
1 2
I RMS t = -- ³ i t dt
T
t – T Eq. 2-3

RMS values include harmonics, inter-harmonics, DC components, and so on, along with fundamental frequency values.
The true RMS value reflects thermal effects of the current and is used for the thermal related monitoring and protection
2
functions.
Protection and control functions respond to phasors of the fundamental and/or harmonic frequency components
(magnitudes and angles), with an exception for some functions that have an option for RMS or fundamental
measurements, or some function responding to RMS only. This type of response is explained typically in each element's
section in this instruction manual.
Currents are pre-filtered using a Finite Impulse Response (FIR) digital filter. The filter is designed to reject DC components
and low-frequency distortions, without amplifying high-frequency noise. This filter is referred to as a modified MIMIC filter,
which provides excellent filtering and overall balance between speed and accuracy of filtering. The filter is cascaded with
the full-cycle Fourier filter for the current phasor estimation.
Voltages are pre-filtered using a patented FIR digital filter. The filter has been optimized to reject voltage-transformer-
specific distortions, such as Capacitive Voltage Transformer (CVT) noise and high-frequency oscillatory components. The
filter is cascaded with the half-cycle Fourier filter for the voltage phasor estimation.
The URs measure power system frequency using the Clarke transformation by estimating the period of the waveform from
two consecutive zero-crossings in the same direction (negative-to-positive). Voltage or current samples are pre-filtered
using a Finite Impulse Response (FIR) digital filter to remove high frequency noise contained in the signal. The period is
used after several security conditions are met, such as true RMS signal must be above 6% nominal for a certain time. If
these security conditions are not met, the last valid measurement is used for a specific time after which the UR reverts to
nominal system frequency.
Synchrophasors are calculated using a patented convolution integral algorithm. This algorithm allows use of the same
time-stamped samples, which are used for protection and taken at the same sampling frequency. This allows URs to use
one sampling clock for both protection algorithms and synchrophasors.
Synchrophasors on firmware versions 7.23 and up have been tested and certified to meet IEEE C37.118-2011 and
C37.118.1a-2014 standards for both metering and protection classes with outputs available up to 60 synchrophasors per
second for the metering class and 120 synchrophasors per second for the protection class. Synchrophasors measurement
is also available via IEC 61850-90-5 protocol.
The contact inputs threshold is settable in the firmware with 17, 33, 84, and 166 V DC settings available. Inputs are scanned
every 0.5 ms and can be conditioned for the critical applications, using debounce time timer, settable from 0.0 to 16.0 ms.
Contact inputs with auto-burnishing are available as well, when external contacts are exposed to the contamination in a
harsh industrial environment.
All measured values are available in the UR metering section on the front panel and via communications protocols.
Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64
samples per power cycle. Analog values can be captured with the Data Logger, allowing much slower rates extended over
a long period of time.
Other advanced UR order code options are available to support IEC 61850 (including fast GOOSE, ICD/CID/IID files, and so
on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, CyberSentry (advanced cyber security), the Parallel
Redundancy Protocol (PRP), IEC 60870-5-103, and so on.

2.5 Specifications
Specifications are subject to change without notice.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-19


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

2.5.1 Protection elements


The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated. FlexLogic
operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect with other
protection or control elements of the relay, building FlexLogic equations, or interfacing with other intelligent electronic
devices (IEDs) or power system devices via communications or different output contacts. If not specified, the operate times
given here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
Timer Accuracy is specified as a percentage of the total operating time that is the sum of the Operate Time and settable
2 Pickup Delay.
NOTE 1 — Protection and control elements with NOTE 1 have additional operating time delay of up to 3 ms if the F60 is
ordered with an IEC 61850-9-2LE / IEC 61869 Process Bus Module (order code 85, 86, 87).

RESTRICTED GROUND FAULT


Pickup: 0.005 to 30.000 pu in steps of 0.001
Dropout: 97 to 98% of pickup
Slope: 0 to 100% in steps of 1%
Level accuracy:
0.1 to 2.0 x CT rating: ±0.5% of reading or ±1% of rated (whichever is greater)
>2.0 x CT rating: ±1.5% of reading
Pickup delay: 0 to 600.00 s in steps of 0.01
Dropout delay: 0 to 600.00 s in steps of 0.01
Operate time: <2 power system cycles (see NOTE 1)

PHASE/NEUTRAL/GROUND TOC
Current: Phasor or RMS
Pickup level: 0.020 to 30.000 pu in steps of 0.001 (standard CT for ground)
0.002 to 3.000 pu in steps of 0.001 (sensitive ground CT)
0.005 to 30.000 pu in steps of 0.001 (Process Bus Module, ground)
Dropout level: 97% of pickup
Level accuracy:
0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0 × CT: ±1.5% of reading > 2.0 × CT rating
Timing characteristics: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/ Extremely Inverse; I2t; FlexCurves™ (programmable); (Curve multiplier 0.00 to 600.00
in steps of 0.01 s)
Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s)
Reset type: Instantaneous/Timed (per IEEE)
Curve timing accuracy at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate (see NOTE 1)
Voltage restraint: Modifies pickup current for voltage in the range of 0.1 < V < 0.9 VT Nominal in a fixed linear rela-
tionship

PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.020 to 30.000 pu in steps of 0.001 (standard CT for ground)
0.002 to 3.000 pu in steps of 0.001 (sensitive ground CT)
0.005 to 30.000 pu in steps of 0.001 (Process Bus Module, ground)
Dropout level: 97% of pickup
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0 × CT rating: ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operate time: <16 ms at 3 × pickup at 60 Hz (Phase IOC) (see NOTE 1)
<20 ms at 3 × pickup at 60 Hz (Neutral IOC) (see NOTE 1)

2-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

<25 ms at 3 x pickup at 60 Hz (Ground IOC) (see NOTE 1)


Timer accuracy: ±3.5% of operate time or ±1/4 cycle (whichever is greater)

NEGATIVE SEQUENCE TOC


Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97% of pickup
Level accuracy: ±0.5% of reading or ±0.4% of rated (whichever is greater)
from 0.1 to 2.0 x CT rating

Timing characteristics:
±1.5% of reading > 2.0 x CT rating
IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse, 2
Short/Very/ Extremely Inverse; I2t; FlexCurves™ (programmable) (Curve multiplier = 0.00 to
600.00 in steps of 0.01 s); Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s)
Reset type: Instantaneous/Timed (per IEEE) and Linear
Curve timing accuracy
at 1.03 to 20 x pickup: ±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate (see NOTE 1)

NEGATIVE SEQUENCE IOC


Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97% of pickup
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated (whichever is greater);
>2.0 × CT rating: ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operate time: <20 ms at 3 × pickup at 60 Hz (see NOTE 1)
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)

PHASE DIRECTIONAL OVERCURRENT


Relay connection: 90° (quadrature)
Quadrature voltage: ABC phase seq.: phase A (VBC), phase B (VCA), phase C (VAB); ACB phase seq.: phase A (VCB), phase
B (VAC), phase C (VBA)
Polarizing voltage threshold: 0.004 to 3.000 pu in steps of 0.001
Current sensitivity threshold: 0.05 pu
Characteristic angle: 0 to 359° in steps of 1
Angle accuracy: ±2°
Operation time (FlexLogic operands):
Tripping (reverse load, forward fault): <12 ms, typically (see NOTE 1)
Blocking (forward load, reverse fault): <8 ms, typically (see NOTE 1)

NEUTRAL DIRECTIONAL OVERCURRENT


Directionality: Co-existing forward and reverse
Polarizing: Voltage, Current, Dual, Dual-V, Dual-I
Polarizing voltage: V_0 or VX
Polarizing current: IG
Operating current: I_0
Level sensing: 3 × (|I_0| – K × |I_1|), IG
Independent for forward and reverse
Restraint, K: 0.000 to 0.500 in steps of 0.001
Characteristic angle: –90 to 90° in steps of 1
Limit angle: 40 to 90° in steps of 1, independent for forward and reverse
Angle accuracy: ±2°
Offset impedance: 0.00 to 250.00 Ω in steps of 0.01
Pickup level: 0.002 to 30.000 pu in steps of 0.01
Dropout level: 97 to 98%
Operation time: <16 ms at 3 × pickup at 60 Hz (see NOTE 1)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-21


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

NEGATIVE SEQUENCE DIRECTIONAL OC


Directionality: Co-existing forward and reverse
Polarizing: Voltage
Polarizing voltage: V_2
Operating current: I_2
Level sensing:
Zero-sequence: |I_0| – K × |I_1|
Negative-sequence: |I_2| – K × |I_1|
2 Restraint, K:
Characteristic angle:
0.000 to 0.500 in steps of 0.001
0 to 90° in steps of 1
Limit angle: 40 to 90° in steps of 1, independent for forward and reverse
Angle accuracy: ±2°
Offset impedance: 0.00 to 250.00 Ω in steps of 0.01
Pickup level: 0.015 to 30.000 pu in steps of 0.01
Dropout level: 97%
Operation time: <16 ms at 3 × pickup at 60 Hz (see NOTE 1)

WATTMETRIC ZERO-SEQUENCE DIRECTIONAL


Measured power: zero-sequence
Number of elements: 2
Characteristic angle: 0 to 360° in steps of 1
Minimum power: 0.001 to 1.200 pu in steps of 0.001
Pickup level accuracy: ±1% or ±0.0025 pu, whichever is greater
Hysteresis: 3% or 0.001 pu, whichever is greater
Timing characteristics: Inverse time, or FlexCurve (Curve multiplier= 0.01 to 2.00 in steps of 0.01 s);
Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s)
Curve timing accuracy: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 60 Hz

SENSITIVE DIRECTIONAL POWER


Measured power: 3-phase, true RMS
Number of stages: 2
Characteristic angle: 0 to 359° in steps of 1
Calibration angle: 0.00 to 0.95° in steps of 0.05
Minimum power: –3.300 to 3.300 pu in steps of 0.001
Pickup level accuracy: ±1% or ±0.001 pu, whichever is greater
Hysteresis: 2% or 0.001 pu, whichever is greater
Pickup delay: 0 to 600.00 s in steps of 0.01
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: <50 ms (plus up to 5 ms with Process Bus Module with order code 85, 86, 87)

PHASE UNDERVOLTAGE
Voltage: Phasor only
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 102% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Timing characteristics: GE IAV Inverse (Curve multiplier 0.00 to 600.00 in steps of 0.01 s)
Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s)
FlexCurves (programmable, Curve multiplier = 0.00 to 600.00 in steps of 0.01 s)
Reset delay: 0 to 600.00 s in steps of 0.01 s
Curve timing accuracy at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 0.9 pickup at 60 Hz for Definite Time mode

AUXILIARY UNDERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 103% of pickup

2-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

Level accuracy: ±0.5% of reading from 10 to 208 V


Timing characteristics: GE IAV Inverse (Curve multiplier = 0.00 to 600.00 in steps of 0.01 s);
Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s)
FlexCurves (programmable, Curve multiplier = 0.00 to 600.00 in steps of 0.01 s)
Reset delay: 0 to 600.00 s in steps of 0.01 s
Curve timing accuracy at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 0.9 pickup at 60 Hz for Definite Time mode

PHASE OVERVOLTAGE 2
Voltage: Phasor only
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Timing characteristics: GE IAV Inverse (Curve multiplier 0.00 to 600.00 in steps of 0.01 s);
Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s);
FlexCurves (programmable, Curve multiplier = 0.00 to 600.00 in steps of 0.01 s)
Reset delay: 0 to 600.00 s in steps of 0.01 s
Curve timing accuracy at >1.10 × pickup:±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 1.10 × pickup at 60 Hz for Definite Time mode

NEUTRAL OVERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 97% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 s in steps of 0.01 (definite time) or user-defined curve
Reset delay: 0.00 to 600.00 s in steps of 0.01
Curve timing accuracy at >1.1 × pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 1.10 × pickup at 60 Hz

AUXILIARY OVERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 97% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Timing characteristics: Definite Time (Time delay = 0.00 to 600.00 in steps of 0.01 s);
GE IAV Inverse (Curve multiplier= 0.00 to 600.00 in steps of 0.01 s);
FlexCurves (programmable, Curve multiplier= 0.00 to 600.00 in steps of 0.01 s)
Reset delay: 0 to 600.00 s in steps of 0.01
Curve timing accuracy at >1.10 x pickup:±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 1.10 × pickup at 60 Hz for Definite Time mode

NEGATIVE SEQUENCE OVERVOLTAGE


Pickup level: 0.004 to 1.250 pu in steps of 0.001
Dropout level: 97% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0 to 600.00 s in steps of 0.01
Reset delay: 0 to 600.00 s in steps of 0.01
Timer accuracy: ±3% of operate time or ±20 ms, whichever is greater
Operate time: <30 ms at 1.10 × pickup at 60 Hz

UNDERFREQUENCY
Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Dropout level: pickup + 0.03 Hz
Level accuracy: ±0.001 Hz
Time delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-23


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Operate time: typically 4 cycles at 0.1 Hz/s change


typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables, such as frequency change instance, and test method, and can vary by ±0.5
cycles.

OVERFREQUENCY
Pickup level: 20.00 to 65.00 Hz in steps of 0.01

2 Dropout level:
Level accuracy:
pickup – 0.03 Hz
±0.001 Hz
Time delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.

RATE OF CHANGE OF FREQUENCY


df/dt trend: increasing, decreasing, bi-directional
df/dt pickup level: 0.10 to 15.00 Hz/s in steps of 0.01
df/dt dropout level: 96% of pickup
df/dt level accuracy: 80 mHz/s or 3.5%, whichever is greater (up to df/dt trend of 10 Hz/s)
Overvoltage supv.: 0.100 to 3.000 pu in steps of 0.001
Overcurrent supv.: 0.020 to 30.000 pu in steps of 0.001
Pickup delay: 0 to 65.535 s in steps of 0.001
Reset delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: typically 9.5 cycles at 2 × pickup
typically 8.5 cycles at 3 × pickup
typically 6.5 cycles at 5 × pickup
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.

BREAKER FAILURE
Mode: 1-pole, 3-pole
Current supervision: phase, neutral current
Current supv. pickup: 0.020 to 30.000 pu in steps of 0.001
Current supv. dropout: 97% of pickup
Current supv. accuracy:
0.1 to 2.0 × CT rating: ±0.75% of reading or ±2% of rated (whichever is greater)
above 2 × CT rating: ±2.5% of reading

BREAKER ARCING CURRENT


Principle: accumulates breaker duty (I2t) and measures fault duration
Initiation: programmable per phase from any FlexLogic operand
Compensation for auxiliary relays: 0 to 65.535 s in steps of 0.001
Alarm threshold: 0 to 50000 kA2-cycle in steps of 1
Fault duration accuracy: 0.25 of a power cycle
Availability: 1 per CT bank with a minimum of 2

BREAKER FLASHOVER
Operating quantity: phase current, voltage, and voltage difference
Pickup level voltage: 0.004 to 1.500 pu in steps of 0.001
Dropout level voltage: 97% of pickup
Pickup level current: 0.020 to 1.500 pu in steps of 0.001
Dropout level current: 97% of pickup

2-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

Level accuracy: ±0.5% or ±0.1% of rated, whichever is greater


Pickup delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±42 ms, whichever is greater
Operate time: <42 ms at 1.10 × pickup at 60 Hz (see NOTE 1)

BREAKER RESTRIKE
Principle: detection of high-frequency overcurrent condition ¼ cycle after breaker opens
Availability: one per digital signal processor (DSP)
Pickup level:
Reset delay:
0.1 to 2.00 pu in steps of 0.01
0.000 to 65.535 s in steps of 0.001 2
INCIPIENT CABLE FAULT DETECTION
Principle: detection of ½ cycle or less overcurrent condition during normal load
Availability: two per CT/VT module (not including 8Z modules)
Pickup level: 0.1 to 10.00 pu in steps of 0.01
Reset delay: 0.000 to 65.535 s in steps of 0.001
Operating mode: number of counts, counts per time window

SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference: 0 to 100° in steps of 1
Max freq. difference: 0.005 to 2.000 Hz in steps of 0.001
Hysteresis for max. freq. diff.: 0.000 to 0.100 Hz in steps of 0.001
Dead source function: None, LV1 & DV2, DV1 & LV2, DV1 or DV2, DV1 xor DV2, DV1 & DV2 (L = Live, D = Dead)
S-CLS MAX dF: 0.100 to 10.000 Hz in steps of 0.001
S-CLS MIN dF: 0.005 to 1.000 Hz in steps of 0.001
V2 MAG CORR FACTOR: 0.10 to 10.00 in steps of 0.01
V2 ANGLE SHIFT: -180° to +180° in steps of 1°
PHASE SELECT: Auto, Vag, Vbg, Vcg, Vab, Vbc, Vca

AUTORECLOSURE
Single breaker applications, 3-pole tripping schemes
Up to four reclose attempts before lockout
Independent dead time setting before each shot
Possibility of changing protection settings after each shot with FlexLogic

PILOT-AIDED SCHEMES
Permissive Overreaching Transfer Trip (POTT)
Directional Comparison Blocking Scheme

LOAD ENCROACHMENT
Responds to: Positive-sequence quantities
Minimum voltage: 0.004 to 3.000 pu in steps of 0.001
Reach (sec. Ω): 0.02 to 250.00 Ω in steps of 0.01
Impedance accuracy: ±5%
Angle: 5 to 50° in steps of 1
Angle accuracy: ±2°
Pickup delay: 0 to 65.535 s in steps of 0.001
Reset delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: <30 ms at 60 Hz (see NOTE 1)

THERMAL OVERLOAD PROTECTION


Thermal overload curves: IEC 255-8 curve
Base current: 0.20 to 3.00 pu in steps of 0.01
Overload (k) factor: 0.2 to 4 pu in steps of 0.05
Alarm level: 0.2 to 1.0 pu in steps of 0.1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-25


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Trip time constant: 0 to 999 min. in steps of 0.1


Reset time constant: 0 to 999 min. in steps of 0.1
Minimum reset time: 0 to 999 min. in steps of 0.1
Timer accuracy (cold curve): ±100 ms or 2%, whichever is greater
Timer accuracy (hot curve): ±500 ms or 2%, whichever is greater for Ip < 0.9 × k × Ib and I / (k × Ib) > 1.1

TRIP BUS (TRIP WITHOUT FLEXLOGIC)

2 Number of elements:
Number of inputs:
6
16
Operate time: <2 ms at 60 Hz
Timer accuracy: ±3% or 10 ms, whichever is greater

HARMONIC DETECTION
Number of elements: 6
Pickup threshold: 2.0 to 100.0% of I(f1) (current fundamental frequency phasor) in steps of 0.1%
Pickup level accuracy:
Harmonics: With I(f1) from 0.4 to 2.0 × CT rating: ±2% of reading or ±1% of 100%, whichever is greater
THD: With I(f1) from 0.4 to 2.0 × CT rating: ±2% of reading or ±1% of 100% per each harmonic, which-
ever is greater
Pickup delay: 0 to 600.00s in steps of 0.01
Timer accuracy: ±3% of delay setting or ±1/4 cycle (whichever is greater) from pickup to operate
Operating time: <10 ms at 2 × pickup at 60 Hz
Note: Accuracy of the DC measurement depends on the duration and content of the DC component, compared to the fundamental fre-
quency current. It also depends on the source of the signal. DSP or HardFiber transducers can saturate and cause higher error than
stated here, while with an MU-320 merging unit as a source, it meets the accuracy stated here due to immunity of the MU-320 to satura-
tion.

TRANSIENT GROUND FAULT DETECTION


Voltage pickup level: 0.00 to 1.50 pu in steps of 0.01
Voltage dropout level: 98% of pickup
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operating time: <40 ms for 60Hz
<50 ms for 50Hz

2.5.2 User-programmable elements


FLEXLOGIC
Programming language: Reverse Polish Notation with graphical visualization (keypad programmable)
Lines of code: 1024
Internal variables: 64
Supported operations: NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to 16 inputs), NAND (2 to 16 inputs),
latch (reset-dominant), edge detectors, timers
Inputs: any logical variable, contact, or virtual input
Number of timers: 64
Pickup delay: 0 to 60000 (ms, sec., min.) in steps of 1
Dropout delay: 0 to 60000 (ms, sec., min.) in steps of 1
Timer accuracy: ±0.1% of operate time or ±1/8 cycle, whichever is greater

FLEXCURVES™
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1

2-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

FLEX STATES
Number: up to 256 logical variables grouped under 16 Modbus addresses
Programmability: any logical variable, contact, or virtual input

FLEXELEMENTS™
Number of elements: 16
Operating signal: any analog actual value, or two values in differential mode
Operating signal mode: signed or absolute value
Operating mode:
Comparator direction:
level, delta
over, under 2
Pickup level: –90.000 to 90.000 pu in steps of 0.001
Hysteresis: 0.1 to 50.0% in steps of 0.1
Delta dt: 20 ms to 60 days
Pickup and dropout delay: 0.000 to 65.535 s in steps of 0.001

NON-VOLATILE LATCHES
Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
Output: stored in non-volatile memory
Execution sequence: as input prior to protection, control, and FlexLogic

USER-PROGRAMMABLE LEDs (Enhanced and basic front panels)


Number: 48 plus trip and alarm
Programmability: from any logical variable, contact, or virtual input
Reset mode: self-reset or latched

LED TEST
Initiation: from any contact input or user-programmable condition
Number of tests: 3, interruptible at any time
Duration of full test: approximately 3 minutes
Test sequence 1: all LEDs on
Test sequence 2: all LEDs off, one LED at a time on for 1 s
Test sequence 3: all LEDs on, one LED at a time off for 1 s

USER-DEFINABLE DISPLAYS (Enhanced and basic front panels)


Number of displays: 16
Lines of display: 2 × 20 alphanumeric characters
Parameters: up to 5, any Modbus register addresses
Invoking and scrolling: keypad, or any user-programmable condition, including pushbuttons

CONTROL PUSHBUTTONS (Enhanced and basic front panels)


Number of pushbuttons: 7
Operation: drive FlexLogic operands

USER-PROGRAMMABLE PUSHBUTTONS
Number of pushbuttons: 12 on basic front panel
16 on enhanced horizontal front panel
6 on enhanced vertical front panel
48 on graphical front panel (8 physical pushbuttons, 40 graphical interface pushbuttons)
Mode: self-reset, latched
Display message: 2 lines of 20 characters each
Drop-out timer: 0.00 to 60.00 s in steps of 0.05
Autoreset timer: 0.2 to 600.0 s in steps of 0.1
Hold timer: 0.0 to 10.0 s in steps of 0.1

SELECTOR SWITCH
Number of elements: 2
Upper position limit: 1 to 7 in steps of 1
Selecting mode: time-out or acknowledge

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-27


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Time-out timer: 3.0 to 60.0 s in steps of 0.1


Control inputs: step-up and 3-bit
Power-up mode: restore from non-volatile memory or synchronize to a 3-bit control input or synch/restore mode

DIGITAL ELEMENTS
Number of elements: 96
Operating signal: any FlexLogic operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001

2 Dropout delay:
Timing accuracy:
0.000 to 999999.999 s in steps of 0.001
±3% or ±4 ms, whichever is greater

2.5.3 Monitoring
OSCILLOGRAPHY
Number of records: 3 to 64, configurable
Sampling rate: 8, 16, 32, or 64 samples per power cycle, configurable
Triggers: any FlexLogic operand, configurable
Trigger position: 0 to 100%, configurable
Recorded data: raw AC input channels
up to 127 configured digital channels (+ 1 trigger operand), representing any FlexLogic operand
up to 32 configured analog channels, representing any measured analog value
Data storage: in non-volatile memory
Format: COMTRADE IEEE C37.111 (1999 or 2013)

EVENT RECORDER
Capacity: 1024 events
Time-tag: to 1 microsecond
Triggers: any FlexLogic operand, configurable
Data storage: in non-volatile memory

DATA LOGGER
Number of channels: 1 to 16
Parameters: any available analog actual value
Sampling rate: 15 to 3600000 ms in steps of 1
Trigger: any FlexLogic operand
Mode: continuous or triggered
Storage capacity: (NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days

60-minute rate:
01 channel for NN days
16 channels for NN days

FAULT LOCATOR
Number of independent fault locators: 1 per CT bank to a maximum of 5
Method: single-ended
Voltage source: wye-connected VTs, delta-connected VTs and neutral voltage, delta-connected VTs and zero-
sequence current (approximation)
Maximum accuracy if: fault resistance is zero and fault currents from all line terminals are approximately in phase (sin-
gle-ended method)
Relay accuracy: ±1.5% (V > 10 V, I > 0.2 pu), single-ended method
Worst-case accuracy:
VT%error + user data
CT%error + user data
ZLine%error + user data

2-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

METHODerror + 1.5% single-ended method


See Theory of Operation chapter, Fault Locator section

HI-Z
Detections: Arc Suspected, Arc Detected, Downed Conductor, Phase Identification

PHASOR MEASUREMENT UNIT


Output format: per IEEE C37.118-2011, C37.118.1a-2014, or IEC 61850-90-5 standard
Number of channels: 14 synchrophasors, 16 analogs, 16 digitals
TVE (total vector error): <1% 2
Triggering: frequency, voltage, current, power, rate of change of frequency, user-defined
Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times per second for P and M class, and 100 or 120 times
per second for P class only
Number of clients: one over TCP/IP port and one over UDP/IP per aggregator
AC ranges: as indicated in appropriate specification sections
Network reporting format: 16-bit integer (for IEEE C37.118) or 32-bit IEEE floating point numbers
Network reporting style: rectangular (real and imaginary for IEEE C37.188) or polar (magnitude and angle) coordinates
Post-filtering: none, 3-point, 5-point, 7-point
Calibration: ±5° (angle) and ±5% (magnitude)

2.5.4 Metering
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated (whichever is greater)
> 2.0 × CT rating: ±1.0% of reading

RMS VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V

REAL POWER (WATTS)


Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
±1.0% of reading at –1.0 ≤ PF < –0.8 and 0.8 < PF ≤ 1.0

REACTIVE POWER (VARS)


Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
±1.0% of reading at –0.2 ≤ PF ≤ 0.2

APPARENT POWER (VA)


Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
±1.0% of reading

WATT-HOURS (POSITIVE AND NEGATIVE)


Accuracy: ±2.0% of reading
Range: ±0 to 1 × 106 MWh
Parameters: three-phase only
Update rate: 50 ms

VAR-HOURS (POSITIVE AND NEGATIVE)


Accuracy: ±2.0% of reading
Range: ±0 to 1 × 106 Mvarh
Parameters: three-phase only
Update rate: 50 ms

CURRENT HARMONICS
Harmonics: 2nd to 25th harmonic: per phase, displayed as a % of I(f1) (current fundamental frequency pha-
sor)
THD: per phase, displayed as a % of I(f1)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-29


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Accuracy:
Harmonics: with I(f1) 0.4 to 2.0 × CT rating: ±2% of reading or ±1% of 100%, whichever is greater
THD: with I(f1) from 0.4 to 2.0 × CT rating: ±2% of reading or ±1% of 100% per each harmonic, which-
ever is greater
Accuracy applies to: 2nd to 17th harmonic including THD with a regular CT/VT module
2nd to 13th harmonic including THD with a Process Bus Module (order code 85, 86, 87) when
anti-aliasing filter is enabled
2nd to 16th harmonic including THD with a Process Bus Module (order code 85, 86, 87) when

2 anti-aliasing filter is disabled


2nd to 15th harmonic including THD with a HardFiber Process Bus Module (order code 81)

VOLTAGE HARMONICS
Harmonics: 2nd to 25th harmonic: per phase, displayed as a % of V(f1) (voltage fundamental frequency pha-
sor)
THD: per phase, displayed as a % of V(f1)
Accuracy:
Harmonics: with V(f1) 25 to 208 V: ±2% of reading or ±1% of 100%, whichever is greater
THD: with V(f1) 25 to 208 V: ±2% of reading or ±1% of 100% per each harmonic, whichever is greater
Accuracy applies to: 2nd to 25th harmonic including THD with a regular CT/VT module
2nd to 10th harmonic including THD with a Process Bus Module (order code 85, 86, 87) when
anti-aliasing filter is enabled
2nd to 16th harmonic including THD with a Process Bus Module (order code 85, 86, 87) when
anti-aliasing filter is disabled
2nd to 15th harmonic including THD with a HardFiber Process Bus Module (order code 81)

FREQUENCY
Accuracy for 20 to 65 Hz input at
V = 0.8 to 1.2 pu: ±0.001 Hz (when voltage signal is used for frequency measurement)
I = 0.1 to 0.25 pu: ±0.02 Hz (when current signal is used for frequency measurement)
I > 0.25 pu: ±0.005 Hz (when current signal is used for frequency measurement)

DEMAND
Measurements: Phases A, B, and C present and maximum measured currents
3-Phase Power (P, Q, and S) present and maximum measured currents
Accuracy: ±2.0%

2.5.5 Inputs
AC CURRENT
CT rated primary: 1 to 50000 A
CT rated secondary: 1 or 5 A by connection
Relay burden: < 0.2 VA at rated secondary
Conversion range:
Standard CT: 0.02 to 46 × CT rating RMS symmetrical
Sensitive Ground CT module: 0.002 to 4.6 × CT rating RMS symmetrical
HI-Z CT module: 0.002 to 4.6 × CT rating RMS symmetrical
Current withstand: 20 ms at 250 times rated
1 sec at 100 times rated
continuous 4x Inom
Short circuit rating: 150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)

AC VOLTAGE
VT rated secondary: 25.0 to 240.0 V
VT ratio: 1.00 to 24000.00
Relay burden: < 0.25 VA at 120 V
Conversion range: 1 to 275 V

2-30 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

Voltage withstand: continuous at 260 V to neutral


1 min/hr at 420 V to neutral

FREQUENCY
Nominal frequency setting: 25 to 60 Hz
Sampling frequency: 64 samples per power cycle
Tracking frequency range with DSP: 20 to 70 Hz
with Process Bus Module 81, 85, 86, 87: 20 to 65 Hz

CONTACT INPUTS 2
Dry contacts: 1000 Ω maximum
Wet contacts: 300 V DC maximum
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Tolerance: ±10%
Contacts per common return: 4
Recognition time: < 1 ms
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Continuous current draw: 4 mA (when energized)

CONTACT INPUTS WITH AUTO-BURNISHING


Dry contacts: 1000 Ω maximum
Wet contacts: 300 V DC maximum
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Tolerance: ±10%
Contacts per common return: 2
Recognition time: < 1 ms
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Continuous current draw: 4 mA (when energized)
Auto-burnish impulse current: 50 to 70 mA
Duration of auto-burnish impulse: 25 to 50 ms

DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable)
Input impedance: 379 Ω ±10%
Conversion range: –1 to + 20 mA DC
Accuracy: ±0.2% of full scale
Type: Passive

RTD INPUTS
Types (3-wire): 100 Ω Platinum, 100 and 120 Ω Nickel, 10 Ω Copper
Sensing current: 5 mA
Range: –50 to +250°C
Accuracy: ±2°C
Isolation: 36 V pk-pk

IRIG-B INPUT
IRIG formats accepted: B000…B007, B120…B127
IRIG control bits: IEEE Std C37.118.1-2011
Amplitude modulation: 1 to 10 V pk-pk
DC shift:
Operating range: 0 to 10 V DC
TTL logic low: 0.0 to 0.8 V DC
TTL logic high: 2.0 to 5.0 V DC
Input impedance: 50 kΩ
Isolation: 2 kV

DIRECT INPUTS
Input points: 32

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-31


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Remote devices: 16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: Yes, No
Data rate: 64 or 128 kbps
CRC: 32-bit
CRC alarm:
Responding to: Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
2 Alarm threshold:
Unreturned message alarm:
1 to 1000 in steps of 1

Responding to: Rate of unreturned messages in the ring configuration


Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1

TELEPROTECTION
Input points: 16
Remote devices: 3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: No
Data rate: 64 or 128 kbps
CRC: 32-bit

2.5.6 Power supply


LOW RANGE
Nominal DC voltage: 24 to 48 V
Minimum DC voltage: 20 V
Maximum DC voltage: 75 V for SL power supply module
Voltage loss hold-up: 200 ms duration at maximum load
NOTE: Low range is DC only.

HIGH RANGE
Nominal DC voltage: 125 to 250 V
Minimum DC voltage: 88 V
Maximum DC voltage: 300 V
Nominal AC voltage: 100 to 240 V at 50/60 Hz
Minimum AC voltage: 88 V at 25 to 100 Hz
Maximum AC voltage: 265 V at 25 to 100 Hz
Voltage loss hold-up: 200 ms duration at maximum load

ALL RANGES
Volt withstand: 2 × Highest Nominal Voltage for 10 ms
Power consumption: typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code consumption

INTERNAL FUSE
Ratings:
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
Interrupting capacity:
AC: 100 000 A RMS symmetrical
DC: 10 000 A

2-32 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

2.5.7 Outputs
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6A
Break (DC inductive, L/R = 40 ms):

Voltage Current
24 V
48 V
1A
0.5 A
2
125 V 0.3 A
250 V 0.2 A

Operate time: < 4 ms


Contact material: silver alloy

LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6 A as per IEEE C37.90
Break (DC resistive as per IEC 61810-1):

Voltage Current
24 V 6A
48 V 1.6 A
125 V 0.4 A
250 V 0.2 A

Operate time: < 4 ms


Contact material: silver alloy
Control: separate operate and reset inputs
Control mode: operate-dominant or reset-dominant

FORM-A VOLTAGE MONITOR


Applicable voltage: approx. 15 to 250 V DC
Trickle current: approx. 1 to 2.5 mA

FORM-A CURRENT MONITOR


Threshold current: approx. 80 to 100 mA

FORM-C AND CRITICAL FAILURE RELAY


Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 8A
Break (DC inductive, L/R = 40 ms):

Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A

Operate time: < 8 ms


Contact material: silver alloy

FAST FORM-C RELAY


Make and carry: 0.1 A max. (resistive load)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-33


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Minimum load impedance:

Input voltage Impedance


2 W Resistor 1 W Resistor
250 V DC 20 KΩ 50 KΩ
120 V DC 5 KΩ 2 KΩ
48 V DC 2 KΩ 2 KΩ
24 V DC 2 KΩ 2 KΩ
2 Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load
impedance.

Operate time: < 0.6 ms


Internal Limiting Resistor: 100 Ω, 2 W

SOLID-STATE OUTPUT RELAY


Operate and release time: <100 µs
Maximum voltage: 265 V DC
Maximum leakage current in off state
(excluding voltage monitor circuit current): 100 µA
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
Make and carry:
for 0.2 s: 30 A as per ANSI C37.90
for 0.03 s: 300 A
Breaking capacity:

Specification UL 508 Utility application Industrial application


(autoreclose scheme)
Operations per 5000 operations, 5 operations, 10000 operations,
interval 1 second on, 0.2 seconds on, 0.2 seconds on,
9 seconds off 0.2 seconds off, 30 seconds off
within 1 minute
1000 operations,
0.5 seconds on,
0.5 seconds off
Break capability 3.2 A at L/R = 10 ms 10 A at L/R = 40 ms 10 A at L/R = 40 ms
(0 to 250 V DC)
1.6 A at L/R = 20 ms
0.8 A
L/R = 40 ms

CONTROL POWER EXTERNAL OUTPUT (For dry contact input)


Capacity: 100 mA DC at 48 V DC
Isolation: ±300 Vpk

DIRECT OUTPUTS
Output points: 32

DCMA OUTPUTS
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance: 12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
Accuracy: ±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation: 1.5 kV
Driving signal: any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001

2-34 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

2.5.8 Communication protocols


IEC 61850
IEC 61850: Supports IEC 61850 Editions 1.0 and 2.0. See the UR Family Communications Guide and its con-
formance statements.

RS232 (Enhanced and basic front panels)


Front port: 19.2 kbps, Modbus RTU

USB (Graphical front panel) 2


Front port: USB 2.0 type B

RS485
1 rear port: up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance: 1200 m
Isolation: 2 kV, isolated together at 36 Vpk

FIBER ETHERNET PORT


Operates with 50/125 μm and 62.5/125 μm multimode fiber

Parameter Fiber type


100 Mb multimode
Wavelength 1310 nm
Connector LC
Transmit power –20 dBm
Receiver sensitivity –30 dBm
Power budget 10 dB
Maximum input power –14 dBm
Typical distance 2 km
Full duplex yes
Redundancy yes

ETHERNET (10/100 MB TWISTED PAIR)


Modes: 10 Mb, 10/100 Mb (auto-detect)
Connector: RJ45

SIMPLE NETWORK TIME PROTOCOL (SNTP)


Clock synchronization error: <10 ms (typical)

PRECISION TIME PROTOCOL (PTP)


PTP IEEE Std 1588-2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238-2017
Clock: Slave-only ordinary clock when using station bus Ethernet interface
Boundary clock when using process bus Ethernet interface
Peer delay measurement mechanism

PARALLEL REDUNDANCY PROTOCOL (PRP)


(IEC 62439-3 CLAUSE 4, 2012)
Ethernet ports used: 2 and 3
Networks supported: 10/100 Mb Ethernet

PROCESS BUS MODULE (NON-HARDFIBER)


Ethernet ports: 2 x 1000Base-SX, 1 Gbps LC connectors,
4 x 1000Base-SX (1 Gbps) + 4 x 100Base-FX (100 Mbps) LC connectors, or
4 x 100Base-FX, LC connectors
Number of sampled value (SV) streams: Up to 8
SV subscription profiles: IEC 61850-9-2LE (1 ASDU only) or IEC 61869-9 (1 or 2 ASDUs)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-35


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Sampling Rate:
IEC 61850-9-2: 4800 Hz (80 samples/cycle) fixed for 60 Hz - Protection class
4000 Hz (80 samples/cycle) fixed for 50 Hz - Protection class
IEC 61869-9: 4800 Hz for 60/50 Hz - Protection class
GOOSE support: P1 class 1 TxGOOSE, and 8 RxGOOSE
Network Config modes: IEC 62439-3:2012 PRP (ports 1 and2); IEC 62439-3:2012 HSR (ports 1 and 2); IEC 62439-3:2012
Dual HSR (ports 1 and 2, 5 and 6); or Point-to-Point (ports 1 to 8)
Time synchronization: IEC 61850-9-3 PTPv2 Utility profile; PTPv2/PP (IEEE C37.238-2017 over Process Bus Module;
2 Time synchronization mode:
PTPv2/PP (IEEE C37.238-2017; or IRIG-B over CPU for PTP master
Slave-only, master-slave on Process Bus Module, and slave-only on CPU
Simulation mode: Supported for both GOOSE and SV
Test mode (test, test/block): Supported for both GOOSE and SV

OTHER
TFTP, SFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD), IEEE C37.118

2.5.9 Inter-relay communications


SHIELDED TWISTED-PAIR INTERFACE OPTIONS
Interface type Typical distance
RS422 1200 m
G.703 100 m

RS422 distance is based on transmitter power and does not take into consideration the clock source provided by
the user.

LINK POWER BUDGET AND MAXIMUM OPTICAL INPUT POWER


The following specifications apply to filter interface modules manufactured from January 2012.

Emitter, fiber type Cable type Transmit power Received Power budget Maximum
sensitivity optical input
power
820 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Single 9/125 μm -15 dBm -32 dBm 17 dBm -8 dBm
mode
1300 nm Laser, 9/125 μm 0 dBm -34 dBm 34 dBm -8 dBm
Single mode
1550 nm Laser, 9/125 μm 5 dBm -34 dBm 39 dBm -10 dBm
Single mode

The following specifications apply to filter interface modules implemented before January 2012.

Emitter, fiber type Transmit Received Power budget Maximum optical


power sensitivity input power
820 nm LED, Multimode –20 dBm –30 dBm 10 dB –7.6 dBm
1300 nm LED, Multimode –21 dBm –30 dBm 9 dB –11 dBm
1300 nm ELED, Single mode –23 dBm –32 dBm 9 dB –14 dBm
1300 nm Laser, Single mode –1 dBm –30 dBm 29 dB –14 dBm
1550 nm Laser, Single mode +5 dBm –30 dBm 35 dB –14 dBm

2-36 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

The power budgets are calculated from the manufacturer’s worst-case transmitter power and worst case receiver
sensitivity.
The power budgets for the 1300 nm ELED are calculated from the manufacturer's transmitter power and receiver
sensitivity at ambient temperature. At extreme temperatures these values deviate based on component tolerance.
On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C.

TYPICAL LINK DISTANCE


Emitter, fiber type Cable type Connector Typical distance 2
type
Before From
January January
2012 2012
820 nm LED, 62.5/125 μm ST 1.65 km 2 km
multimode
50/125 μm ST 1.65 km 2 km
1300 nm LED, 62.5/125 μm ST 4 km 5 km
multimode
50/125 μm ST 4 km 5 km
1300 nm ELED, 9/125 μm ST 11.4 km 20 km
single mode
1300 nm Laser, 9/125 μm ST 64 km 65 km
single mode
1550 nm Laser, 9/125 μm ST 105 km 125 km
single mode

Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one
installation to another, the distance covered by your system can vary.

CONNECTOR LOSSES (Total of both ends)


ST connector: 0.7 dB (each)

FIBER LOSSES
820 nm multimode: 3 dB/km
1300 nm multimode: 1 dB/km
1300 nm single mode: 0.35 dB/km
1550 nm single mode: 0.25 dB/km
Splice losses: one splice every 2 km at 0.05 dB loss per splice

SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses.

Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms

2.5.10 CyberSentry security


OPTIONS
Software options: Level 1

2.5.11 Graphical front panel


DISPLAY
Type: color graphical back-lit LCD display
Size: 7 inches (17.8 cm)
Resolution: 800 by 480 pixels

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-37


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

Pages: 5 single-line diagram pages with controls, status, and metering values
up to 8 annunciator pages with total of 96 annunciator windows
1 phasor metering page for each AC Source
5 tabular metering pages with dynamic metering and status
event records page with dynamic update
product information page
settings, actual values, error messages (targets)

LED INDICATORS
2 Functions: 5 device status indicators
9 event cause indicators
8 user-programmable pushbutton indicators

PUSHBUTTONS
Type: membrane
Functions: 5 bottom Tab pushbuttons and 1 Home pushbutton for page recall
4 directional, 1 ENTER, and 1 ESCAPE pushbutton element selection
10 side pushbuttons for power system element control
RESET pushbutton

INGRESS PROTECTION
IP code: IP40 front (IP54 front with IP54 mounting collar accessory)
IP10 back (IP20 back with IP20 cover accessory)

2.5.12 Environmental
AMBIENT TEMPERATURES
Maximum operating range: –40 to 85°C
Continuous operating range: –40 to 60°C1
1 Based on IEC 60068-2-1 and IEC 60068-2-2, Variant Bd and Ad for 16 hrs. The UR can operate up to a surrounding ambient of 85°C,
however operating outside the recommended continuous temperature range for extended periods can result in MTBF degradation and
decrease the response time of the LCD.
Ideal Storage Temperature Range: 15ºC to 27ºC

HUMIDITY
Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC 60068-2-30 variant 1, 6 days)
Ideal Storage Humidity Range: 30% to 60%
Relative Humidity (RH) Air Quality: Proper ventilation is recommended

OTHER
Altitude: 2000 m (maximum)
Pollution degree: II
Overvoltage category: II
Ingress protection: IP20 front, IP10 back (basic front panel and Rev. 1 enhanced front panel)
IP40 front, IP10 back (Rev. 2 enhanced front panel)
IP54 front with IP54 mounting collar accessory (Rev. 2 enhanced front panel)
Ingress protection with IP20 cover accessory:
IP20 back
Noise: 0 dB

2-38 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 2: PRODUCT DESCRIPTION SPECIFICATIONS

2.5.13 Type tests


F60 TYPE TESTS
Test Reference standard Test level
1
Dielectric voltage withstand EN 60255-5 2.2 kV
Impulse voltage withstand EN 60255-51 5 kV
Damped oscillatory IEC 61000-4-18 / IEC 60255-22-1 2.5 kV CM, 1 kV DM
Electrostatic discharge EN 61000-4-2 / IEC 60255-22-2 Level 3 2
RF immunity EN 61000-4-3 / IEC 60255-22-3 Level 3
Fast transient disturbance EN 61000-4-4 / IEC 60255-22-4 Class A and B
Surge immunity EN 61000-4-5 / IEC 60255-22-5 Level 3 and 4
Conducted RF immunity EN 61000-4-6 / IEC 60255-22-6 Level 3
1
Power frequency immunity EN 61000-4-7 / IEC 60255-22-7 Class A and B
Voltage interruption and ripple DC IEC 60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC 60255-25 Class A
Sinusoidal vibration IEC 60255-21-1 Class 1
Shock and bump IEC 60255-21-2 Class 1
Seismic IEC 60255-21-3 Class 1
Power magnetic immunity IEC 61000-4-8 Level 5
Pulse magnetic immunity IEC 61000-4-9 Level 4
Damped magnetic immunity IEC 61000-4-10 Level 4
Voltage dip and interruption IEC 61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC 61000-4-121 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC 61000-4-16 Level 4
Voltage ripple IEC 61000-4-17 15% ripple
1
Ingress protection IEC 60529 IP20 front, IP10 back
Cold IEC 60068-2-1 –40°C for 16 hours
Hot IEC 60068-2-2 85°C for 16 hours
Humidity IEC 60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL 508 e83849 NKCR
Section 43 - Temperature test
Energization of Contact Inputs and/or Contact
Outputs for continuous duty is not to exceed a
total of 31 W of power
Safety UL C22.2-14 e83849 NKCR7
Safety UL 1053 e83849 NKCR
Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over
voltage cat II

1 Not tested by third party.

2.5.14 Production tests


THERMAL
Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-39


SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION

2.5.15 Approvals
APPROVALS
Compliance Applicable council directive According to
CE Low voltage directive EN 60255-5
EMC directive EN 60255-26 / EN 50263
EN 61000-6-5

2 C-UL-US --- UL 508


UL 1053
C22.2 No. 14

2.5.16 Maintenance
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.

CLEANING
Normally, cleaning is not required. When dust has accumulated on the front panel display, wipe with a dry cloth.

To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.

2-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 3: Installation

Installation

This chapter outlines installation of hardware and software. You unpack, mount, wire the unit, turn on power, then install
the software and configure settings.

3.1 Unpack and inspect


1. Open the relay package and check that the following items have been delivered:
– F60
– Mounting screws
– GE EnerVista™ DVD (software and documentation)
– F60 Instruction Manual (soft copy on DVD; printed copy if ordered)
– UR Family Communications Guide (soft copy on DVD; printed copy if Instruction Manual ordered)
– Certificate of Calibration
– Test Report
– EC Declaration of Conformity
– Front panel label package
2. Inspect the unit for physical damage.
3. View the rear nameplate and verify that the correct model has been delivered. The model number is at the top right.

Model: F60H00HCHF8FH6AM6BP8BX7A

F60
RATINGS:
® Mods: 000
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA
Feeder Management Relay Contact Inputs: 300V DC Max 10mA
Wiring Diagram:
Inst. Manual:
See manual
1601-0093
Contact Outputs: Refer to Instruction Manual Serial Number: MAZB98000029
E83849 Firmware: D
GE Multilin Mfg. Date: NOV 26, 2012
- M A A B 9 7 0 0 0 0 9 9 -
PO Num: 600001234.56
Item Num:
LISTED
IND.CONT. EQ.
52TL - M A A B 9 7 0 0 0 0 9 9 -

832773A3.CDR

4. Any protective plastic film on the front panel is normally peeled off, but also can be left on.
5. For any issues, contact GE as outlined in the For Further Assistance section in chapter 1.
6. Check that you have the latest copy of the F60 Instruction Manual and the UR Family Communications Guide, for the
applicable firmware version, at http://www.gegridsolutions.com/multilin/manuals/index.htm

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-1


PANEL CUTOUTS CHAPTER 3: INSTALLATION

The Instruction Manual outlines how to install, configure, and use the unit. The Communications Guide is for advanced use
with communication protocols. The warranty is included at the end of this instruction manual and on the GE Grid Solutions
website.

3.2 Panel cutouts


This section does not apply to the HardFiber Brick; see its instruction manual.
Install the relay in an indoor environment within the environmental specifications. The relay complies with Pollution
Category II, which means installation in an office, laboratory, or testing environment.

3.2.1 Horizontal units


3 The F60 is available as a 19-inch rack horizontal mount unit with a removable front panel. The front panel is specified as
enhanced, basic, or graphical at the time of ordering. The enhanced and graphical front panels have additional user-
programmable pushbuttons and LED indicators, while the basic front panel has additional user-programmable
pushbuttons.
The modular design allows the relay to be upgraded and repaired by qualified service personnel. The front panel is hinged
to allow access to the modules. The front panel is itself removable to allow mounting on doors with limited rear depth and
for upgrading.
In November 2017, GE began transitioning to a new enhanced horizontal front panel, referred to as the IP54 Front Panel or
Enhanced Front Panel Rev. 2. This panel can be identified by the use of a screw instead of a knob to close the panel. It can
conform to an IP54 rating with the IP54 mounting collar purchased separately. The IP54 mounting collar can be used in
panel-mount installations, not 19-inch rack-mount installations. The IP54 mounting collar cannot be used with Rev. 1
enhanced front panels.
The case dimensions are shown in the following figures, along with panel cutout details for panel mounting. When
planning the location of your panel cutout, ensure that provision is made for the front panel to swing open without
interference to or from adjacent equipment.
Mount the relay such that the front panel sits semi-flush with the panel or switchgear door, allowing the operator access to
the keypad and the front communications port.

3-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION PANEL CUTOUTS

Figure 3-1: Horizontal dimensions (Rev. 1 enhanced front panel)

11.016”
[279,81 mm]
9.687”
[246,05 mm]

17.56”
[446,02 mm]
3

7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]

19.040”
[483,62 mm] 842807A1.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-3


PANEL CUTOUTS CHAPTER 3: INSTALLATION

Figure 3-2: Horizontal dimensions (Rev. 2 enhanced front panel)

9.687”
[24.605 cm] 10.97”
[27.86 cm]

3 17.59” [44.68 cm]

6.995” 6.96”
[17.767 cm] [17.68 cm]

18.974” [48.194 cm]


842496A1.cdr

Figure 3-3: Horizontal mounting (enhanced and graphical front panels)


18.370”
[466,60 mm]
0.280”
[7,11 mm]
Typ. x 4
CUT-OUT

7.13” 4.000”
[181.1 mm] [101,60 mm]

17.750”
[450,85 mm] 842808A2.CDR

3-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION PANEL CUTOUTS

Figure 3-4: Horizontal dimensions and mounting (basic front panel)


HORIZONTAL TOP VIEW (19” 4RU) REMOTE MOUNTING
VIEW FROM REAR OF PANEL

BEZEL OUTLINE
8x0.156”

(9.5 mm)
0.375”
(3.962 mm)

(47.6 mm)
10.90”

1.875”
8.97”
(227.8 mm) (276.8 mm)

9.80”
(248.9 mm) 6.960”

(9.5 mm)
0.375”
(176.8 mm)

(121.5 mm)
4.785”
0.375”
17.52” Brackets repositioned (9.5 mm)
(445.0 mm) for switchgear mounting 5.000” 0.375”
(127.0 mm)
9.520” (9.5 mm)
14.520” (241.8 mm)

HORIZONTAL PANEL MOUNTING


4x0.28”
(368.8 mm)
17.720”
(450.1 mm)
3
18.37” (7.1 mm
(466.6 mm) diameter)
HORIZONTAL FRONT VIEW

CUTOUT
7.13” 4.00”
(181.1 mm) (101.6 mm) 7.00”
(177.8 mm)

17.75” 19.00”
(450.8 mm) (482.6 mm)
827704B5.cdr

Figure 3-5: Horizontal dimensions (graphical front panel)

µ
>PP@

´
>PP@

µ µ
>PP@ >PP@

µ
>PP@
$FGU

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-5


PANEL CUTOUTS CHAPTER 3: INSTALLATION

Figure 3-6: Horizontal dimensions (IP54 mounting collar)

MOUNTING PANEL

1.3” [3.3 cm]

3 16.00” [40.64 cm]


Ø 0.200
6 PLACES

8.34”
[21.18 cm]

7.65”
[19.43 cm]

20.19” [51.28 cm]

IP54 COLLAR

NOTES
1. INSPECT THE COLLAR BEFORE INSTALLATION, VERIFY GASKET IS ADHERED TO THE METAL ON ALL SIDES
2. MAKE SURE THE RELAY IS POSITIONED CENTER TO THE CUT OUT
3. INSTALL IP-54 COLLAR, CONFIRM THE GASKET PROPERLY MATES WITH THE PANEL ON ALL SIDES
SECURE USING #8-32 HEX NUT AT 6 PLACES. 842497A1.cdr

3.2.2 Vertical units


The F60 is available as a reduced size (¾) vertical mount unit, with a removable front panel. The front panel is specified as
enhanced or basic at the time of ordering. The enhanced front panel contains additional user-programmable pushbuttons
and LED indicators, while the basic front panel has additional user-programmable pushbuttons.
The modular design allows the relay to be upgraded and repaired by qualified service personnel. The front panel is hinged
to allow easy access to the modules. The front panel is itself removable to allow mounting on doors with limited rear depth
and for upgrading.
The case dimensions are shown in the following figures, along with panel cutout details for panel mounting. When
planning the location of your panel cutout, ensure that provision is made for the front panel to swing open without
interference to or from adjacent equipment.
Mount the relay such that the front panel sits semi-flush with the panel or switchgear door, allowing the operator access to
the keypad and the RS232 communications port.

3-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION PANEL CUTOUTS

Figure 3-7: Vertical dimensions and mounting (enhanced front panel)


0RXQWLQJ%UDFNHW )URQWRI3DQHO
µ
PP

)URQW
%H]HO

µ
µ PP
PP
3

9HUWLFDO(QKDQFHG6LGH9LHZ
)URQWRI3DQHO
9HUWLFDO(QKDQFHG)URQW9LHZ µ
PP
µ µ
PP PP µ
µ PP
PP
7HUPLQDO%ORFNV

µ
µ PP &87287
PP
)URQWRI3DQHO
5HIHUHQFHRQO\ µ
PP

µ
PP
0RXQWLQJ%UDFNHW
9HUWLFDO(QKDQFHG7RS9LHZ

µ PP
3ODFHV 9HUWLFDO(QKDQFHG0RXQWLQJ3DQHO
$FGU

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-7


PANEL CUTOUTS CHAPTER 3: INSTALLATION

Figure 3-8: Vertical dimensions and mounting (basic front panel)



)URQWRI PP
SDQHO 3DQHO
0RXQWLQJEUDFNHW

)URQW
EH]HO

 
PP PP

9HUWLFDOVLGHYLHZ
9HUWLFDOIURQWYLHZ

µ
PP
 
PP 
µ µ
PP PP

3DQHOVKRZQIRU
UHIHUHQFHRQO\


PP 0RXQWLQJEUDFNHW
PP

PP
µ

µ

7HUPLQDOEORFNV

PP

9HUWLFDOERWWRPYLHZ

 PP 
SODFHV

$&'5 9HUWLFDOSDQHOPRXQWLQJ

For side-mounting F60 devices with the enhanced front panel, see the following documents available on the UR DVD and
the GE Grid Solutions website:
• GEK-113180 — UR-Series UR-V Side-Mounting Front Panel Assembly Instructions
• GEK-113181 — Connecting a Remote UR-V Enhanced Front Panel to a Vertical UR Device Instruction Sheet
• GEK-113182 — Connecting a Remote UR-V Enhanced Front Panel to a Vertically-Mounted Horizontal UR Device
Instruction Sheet

3-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


STEP 1 - CREATE THE HOLES AND CUT-OUT INTO THE PANEL
AS PER DRAWING 843753. PLUG THE DISPLAY CABLE INTO
THE FRONT BEZEL
#8-3/8" PAN PHILIPS HEAD
BEFORE MOUNTING THE
CHAPTER 3: INSTALLATION

BLACK OXIDE SCREW


UNIT ON THE PANEL
P/N: 1408-0306
#8-3/8" 8 PLACES TO MOUNT THE UNIT
PAN PHILIPS HEAD
BLACK OXIDE
#8 LOCKWASHER
SCREW
EXTERNAL TOOTH
UR 19" P/N: 1435-0002
MOUNTING #6x1/2" PAN PHILIPS 8 PLACES TO MOUNT
BRACKET HEAD
BLACK OXIDE
PLASTITE SCREW

DISPLAY CABLE

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


GROUND CABLE
ATTACH CABLE TO
FRONT BEZEL
BEFORE MOUNTING
FRONT BEZEL ON
THE
PANEL

#10-32 NYLOCK
NUT
For side-mounting F60 devices with the basic front panel, use the following figures.

P/N: 1422-1032
4 PLACES SIDE MOUNT COVER
#10-3/8" PAN PHILIPS HEAD P/N: 1004-0018
ZINC
P/N: 1410-0006 UR-V FRONT BEZEL
4 PLACES TO MOUNT THE ASSEMBLY UR-V UNIT
BRACKETS PANEL
Figure 3-9: Vertical side-mounting installation (basic front panel)

STEP 2 STEP 3 STEP 4


MOUNT BRACKETS TO MOUNT FRONT BEZEL TO ASSEMBLE UR-V UNIT
PANEL PANEL TO MOUNTING BRACKETS
843757A2.cdr

3-9
PANEL CUTOUTS

3
PANEL CUTOUTS CHAPTER 3: INSTALLATION

Figure 3-10: Vertical side-mounting rear dimensions (basic front panel)

6.66"
(169.2)
5.33"
(135.4)

INCHES
(MILLIMETERS) 2.83"
1.00"
(71.9)
(25.4)
PANEL SHOWN FOR
0.68" 0.04" 1.33" REFERENCE ONLY
(17.3) (1.0) (33.9) (VIEWED FROM FRONT)

3 'X' 'X'
1.00"
(25.4)

OUT
T-
CU
5.27"
(133.8)

0.159" DIA. (6 PLACES)


(4.0)
10.05"
(255.3)

12.20"
(309.9)

'X' 'X'

0.213" DIA. (5.4) 843753A3.cdr


(4 PLACES)
SEE HOLES MARKED 'X'

3.2.3 Rear terminal layout


The rear terminals depend on order code. An example is shown.

3-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION PANEL CUTOUTS

Ground
Model: F60H00HCHF8FH6AM6BP8BX7A

F60
RATINGS:
® Mods: 000
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA
Feeder Management Relay Contact Inputs: 300V DC Max 10mA
Wiring Diagram:
Inst. Manual:
See manual
1601-0093
Contact Outputs: Refer to Instruction Manual Serial Number: MAZB98000029
E83849 Firmware: D
GE Multilin Mfg. Date: NOV 26, 2012
- M A A B 9 7 0 0 0 0 9 9 -
PO Num: 600001234.56
Item Num:
LISTED
IND.CONT. EQ.
52TL - M A A B 9 7 0 0 0 0 9 9 -

X W V U T S R P N M L K J H G F D B

c b a c b a c b a

b a
LK1
Tx1 1
1
2
Rx1
ACT1
2
3
LK2
3
Tx1
4
4
5
Tx2 b a
ACT2 5
1 6

3
1
2 LK3
2 6
3
Rx2 3 7
4
4 7
8
Tx2 ACT3 8

IN

Optional Optional Optional CT/VT CPU module Power


direct HI-Z CT or contact module (T module shown) supply
input/output contact input/output module
module input/output module
module
832782A3.CDR

Do not touch any rear terminals while the relay is energized, else death or serious injury can
result from electrical shock.

Small form-factor pluggable ports (SFPs) are pluggable transceivers. They transmit, receive, and
convert electrical signals to optical signals and vice-versa. Supplied with the device, they are inserted
into the Ethernet ports on the CPU and/or Process Bus modules. A photo in the Maintenance chapter
shows this plug-in device. Do not use non-validated transceivers or install validated transceivers in
the wrong Ethernet slot, else damage can occur.
When using a copper SFP with a Process Bus Module, GE recommends limiting the length of the
copper Ethernet cable to three meters (9.8 feet) and confining it within one bay/cubicle.
When using a Process Bus Module, to view if the SFP is 100 Mbps or 1 Gbps, enter the IP address of
the F60 in a web browser and access Process Card Menu > Process Card SFP Information.
Terminal number assignments are three characters long and assigned by module slot position, row number, and column
letter. Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module), indicated by
an arrow on the terminal block. The figure shows an example of rear terminal assignments.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-11


PANEL CUTOUTS CHAPTER 3: INSTALLATION

Figure 3-11: Example of modules in F and H slots

J H G F Slot position

c b a c b a Column letter
Torque 9 inch-pounds

1 H1c H1b H1a F1c F1b F1a 1 Row number


Torque 19 ±1 inch-pounds
2 H2c H2b H2a F2c F2b F2a 2

3 H3c H3b H3a F3c F3b F3a 3

4 H4c H4b H4a F4c F4b F4a 4

5 H5c H5b H5a F5c F5b F5a 5

3 6 H6c H6b H6a F6c F6b F6a 6

7 H7c H7b H7a F7c F7b F7a 7

8 H8c H8b H8a F8c F8b F8a 8

842761A2.CDR

The torque used to connect the screws that connect the terminal blocks (top screws a, b, c) and the metal plates over
empty slots to the chassis is 9 inch-pounds. For the screws used to wire the terminal blocks (rows 1 to 8), use 19±1 inch-
pounds.
The CPU module type depends on order code. During manufacturing, the power supply and CPU modules are installed in
slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. Wire
connections to these two modules at 13 inch-pounds.
Figure 3-12: CPU modules and power supply

56 (WKHUQHW  56 (WKHUQHW  56 (WKHUQHW  56 (WKHUQHW  3RZHU

E D
/. /. /.
5- 
/& FRSSHU 
ILEHU 

$&7 $&7 $&7 /LQN 
/. /. /. $FWLYLW\ 



E D
$&7
E D
$&7
E D
$&7
E D 







 
 /.  /.  /. 
    
   
    
   

%1&
   
67 
IRU $&7 $&7 $&7 ILEHU 

,5,*%
,1 ,1 ,1 ,1

7&38PRGXOH 8&38PRGXOH 9&38PRGXOH :&38PRGXOH 3RZHUVXSSO\


PRGXOH
$&'5

The following figure shows the optical connectors for CPU modules.

3-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-13: LC fiber connector (left) and ST fiber connector (right)

Speeds for the LC connections on non-HardFiber Process Bus Modules are as follows:
• Order code 85 — 1000Base-SX ports 1a and 1b, or ports 3a and 3b
• Order code 86 — 1000Base-SX ports 1a, 1b, 3a, 3b; 100Base-FX ports 2a, 2b, 4a, 4b
• Order code 87 — 100Base-FX ports 1a, 1b, 2a, 2b 3

3.3 Wiring
3.3.1 Typical wiring
For Sampled Value (SV) applications using a Process Bus Module with order code 85, 86, or 87 with IRIG-B for
synchronization, follow the recommended cables and grounding connections outlined here and later.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-13


WIRING CHAPTER 3: INSTALLATION

Figure 3-14: Typical wiring diagram (T module shown for CPU)

7<3,&$/&21),*85$7,21
7+($&6,*1$/3$7+,6&21),*85$%/(

7KLVGLDJUDPLVEDVHGRQWKHIROORZLQJRUGHUFRGH $ % & 326,7,9(:$776 $PS&7


)7+&+))+%0.3&8':$
7KLVGLDJUDPSURYLGHVDQH[DPSOHRIKRZWKHGHYLFH
LVZLUHGQRWVSHFLILFDOO\KRZWRZLUHWKHGHYLFH3OHDVH

UHIHUWRWKH,QVWUXFWLRQ0DQXDOIRUDGGLWLRQDOGHWDLOVRQ
ZLULQJEDVHGRQYDULRXVFRQILJXUDWLRQV
&211(&7,21
23(1'(/7$ $65(48,5('
97&211(&7,21 $%&

)XVH *URXQG
LVRODWLRQ
OLQN

)D

)D

)D

)D

)D

)D

)D

)D

)E

)D

)E

)D

)E

)D

)E
)F

)F

)F

)F

)F

)F

)F

)F

)F

)F

)F
3

9;
9%

9&

9%

9&
9$

9$

9;

,*

,*
9%

9&

9%

9&

,*
9$

9$

,$

,$

,%

,&
,$

,&

,&
,%

,%

&855(17683(59,6,21
92/7$*($1'
92/7$*(,13876 92/7$*(,13876 &855(17,13876
)*
+D &217$&7,1387+D ',*,7$/,138762873876 % , +D 7& 
+F &217$&7,1387+F + +E
9
+D &217$&7,1387+D +F
+F &217$&7,1387+F , +D
+E &20021+E + +E

92/7$*(683(59,6,21
9
+F
+E 685*(
+D
+ +E 7& 
+F
+D
+ +E
+F
+D
+ +E
) )(('(50$1$*(0(175(/$< +F
+D
+ +E
+F
:D &217$&7,1387:D ',*,7$/,138762873876 $ , :D
:F &217$&7,1387:F : :E
9
:D &217$&7,1387:D :F
:F &217$&7,1387:F , :D
:E &20021:E : :E
9
:F
:D &217$&7,1387:D
:D
:F &217$&7,1387:F
: :E
:D &217$&7,1387:D
:F
:F &217$&7,1387:F
:D
:E &20021:E
: :E
:E 685*( :F
'&21/<

3D
&

3 3E
8D &217$&7,13878D
'

8F &217$&7,13878F 3F


8D &217$&7,13878D
3D
3 3E
8F &217$&7,13878F
8E &200218E 3F
3D
8D &217$&7,13878D 3 3E
8F &217$&7,13878F 3F 85 &20387(5
8D &217$&7,13878D 3D
8F &217$&7,13878F   
3 3E
8E &200218E 7;'    5;'
3F
5;'    7;'
8D &217$&7,13878D 3D
  
8F &217$&7,13878F 3 3E
6*1'    6*1'
8D &217$&7,13878D 3F
  
',*,7$/,138762873876

8F &217$&7,13878F 3D


  
',*,7$/,138762873876

8E &200218E 3 3E


  
8D &217$&7,13878D 3F
  
8F &217$&7,13878F 3D
3 3E
8D &217$&7,13878D 3,1
3F 3,1
8F &217$&7,13878F &211(&725 &211(&725
8E &200218E 3D
3 3E
8E 685*( 56
3F
'%
%E 0D
&5,7,&$/


.

%D IURQW
)$,/85( 0 0E
%E 0F
'& %D 9'& &217$&766+2:1 0D
%E 287387 :,7+12 0 0E
32:(56833/<

%E +, &21752/32:(5 0F


&21752/
$&RU'& %E /2 0D
32:(5
%D 0 0E
%D 685*( 0F
%E ),/7(5 0D
0 0E
0F
0D
)LEUH 7[ %DVH); 0 0E
7

2SWLF 5[ 3257


0F
7[ %DVH);
5[
3257 0D
',*,7$/,138762873876

0 0E
6KLHOGHG 7[ %DVH);
*URXQGDW 5[
3257 0F
WZLVWHGSDLUV
85 0D
'HYLFH 'D 0
56 0E
'D &20 0F
'D FRP
0D
'E 0 0E
'D ,5,*%
,QSXW 0F
&38

&RD[LDO %1&

1R$:*
02'8/($55$1*(0(17 $&'5
0LQLPXP
*5281'%86 ; : 9 8 7 6 5 3 1 0 / . - + * ) ' %
       
,QSXWV ,QSXWV ,QSXWV ,QSXWV
RXWSXWV RXWSXWV RXWSXWV RXWSXWV ,QSXWV &797 &38 3RZHU
02'8/(60867%(
*5281'(',) RXWSXWV 6XSSO\
7(50,1$/,6 5HDUYLHZ
3529,'(' 2SWLRQDO

3-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-15: Typical wiring diagram with high-impedance detection (T module shown for CPU)

7<3,&$/&21),*85$7,21
7+($&6,*1$/3$7+,6&21),*85$%/(

7KLVGLDJUDPLVEDVHGRQWKHIROORZLQJRUGHUFRGH
)7+&+))+%0=3&8;;:;; 3D

&
7KLVGLDJUDPSURYLGHVDQH[DPSOHRIKRZWKHGHYLFH 3 3E
LVZLUHGQRWVSHFLILFDOO\KRZWRZLUHWKHGHYLFH3OHDVH 3F
UHIHUWRWKH,QVWUXFWLRQ0DQXDOIRUDGGLWLRQDOGHWDLOVRQ 3D
3 3E
ZLULQJEDVHGRQYDULRXVFRQILJXUDWLRQV
3F
3D
0F 3 3E
3F
0E 3D
3
0D ) )(('(50$1$*(0(175(/$< 3E
3F
0F 3D
3 3E ) &20387(5
0E 3F   

12786('
3D 7;'    5;'
0D

',*,7$/,138762873876
3 3E
5;'    7;'
0F 3F   
3D  
6*1'  6*1'
0E 3 3E
  

3
3F
0D   
3D
3   
0F 3E
  
3F
0E
3,1 3,1
0D &211(&725 &211(&725
=

0F ,* 56

0E ,* '%
, +D

%
IURQW
0D ,* + +E
9
,& +F
0F
, +D
0E ,& + +E
&855(17,13876

9
+F
0D ,& +D
+ +E
0F ,%
+F
0E ,% +D
+ +E
0D ,% +F
&211(&7,21
$65(48,5('

+D
0F ,$ + +E
0E ,$ +F
+D
0D ,$ + +E

',*,7$/,138762873876
+F
&217$&7,1387+D +D
&217$&7,1387+F +F
)F ,*
&217$&7,1387+D +D

'&21/<
)E ,* &217$&7,1387+F +F
&20021+E +E
)D ,*
685*( +E
)F ,&
%E


)E ,& &5,7,&$/


&855(17,13876

)$,/85( %D
%E
)D ,& '&
9'& %D
$PS&7

)F ,% 287387 %E


32:(56833/<

+, %E
)E ,% &21752/
/2 %E $&RU'&
32:(5
%D
)D ,%
)/*0

685*( %D
)F ,$ ),/7(5 %E

)E ,$

)D ,$
1250$/
7[ %DVH); 2SWLF
)LEUH
&387

5[
)F 9; &20 7[ %DVH);
$/7(51$7(
 5[


)D 9;
7[ %DVH); 6KLHOGHG
5[ *URXQGDW
)F 9& WZLVWHGSDLUV
92/7$*(,13876

85
'D 'HYLFH
56
)D 9& 'D
&20
FRP 'D
)F 9%
'E
326,7,9(:$776

&RD[LDO
)D 9% &217$&766+2:1
,5,*% 'D
,QSXW
:,7+12 %1& &RD[LDO
)F 9$ &21752/32:(5

)D 9$
&RD[LDO )RU,5,*%,QSXW
$&'5 RQO\XVHRQH
)F 9& WHUPLQDODVLQSXW
02'8/($55$1*(0(17 1R$:*
)D 9& PLQLPXP
92/7$*(,13876

*5281'%86
)XVH ; : 9 8 7 6 5 3 1 0 / . - + * ) ' %
97&211(&7,21 $%&

)F 9%        
'LJLWDO 'LJLWDO 'LJLWDO 'LJLWDO 02'8/(60867%(
)D 9% LQSXWV LQSXWV LQSXWV LQSXWV 3RZHU *5281'(',)
*URXQG RXWSXWV RXWSXWV RXWSXWV &7 RXWSXWV &797 &38 6XSSO\
23(1'(/7$

7(50,1$/,6
LVRODWLRQ )F 9$ 3529,'('
OLQN 5HDUYLHZ
)D 9$ 2SWLRQDO
$ % &

3.3.2 Dielectric strength


Dielectric strength is the maximum electric strength that can be sustained without breakdown. It is measured in volts.
The table shows the dielectric strength of the UR-series module hardware.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-15


WIRING CHAPTER 3: INSTALLATION

Table 3-1: Dielectric strength of UR modules


Module type Module function Terminals Dielectric strength
From To
1 Power supply High (+); Low (+); (–) Chassis 2000 V AC for 1 minute
1 Power supply 48 V DC (+) and (–) Chassis 2000 V AC for 1 minute
1 Power supply Relay terminals except Chassis 2000 V AC for 1 minute
terminals 8a and 8b
2 Reserved N/A N/A N/A
3 Reserved N/A N/A N/A
4 Digital contact inputs/ All Chassis 2000 V AC for 1 minute
outputs
5 Analog inputs/outputs All except 8b Chassis < 50 V DC

3 6 Digital contact inputs/


outputs
All Chassis 2000 V AC for 1 minute

7 G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute

Filter networks and transient protection clamps are used in the hardware to prevent damage caused
by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90
specified test voltage for longer than the specified minute.

3.3.3 Control power

Power supplied to the relay must be connected to the matching power supply range of the relay. If
incorrect voltage is applied or voltage is applied to the wrong terminals, damage can occur.
The F60, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well-
known to deteriorate over time if voltage is not applied periodically. Deterioration can be avoided by
powering up the relay at least once a year.
The power supply module is ordered with one of two possible voltage ranges, and the F60 can be ordered with or without a
redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges
are as follows (see the Specifications section of chapter 2 for details):
• Low (LO) range — 24 to 48 V (DC only) nominal
• High (HI) range — 125 to 250 V nominal
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical Wiring Diagram earlier). The critical failure relay is a form-C device that is energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If ongoing self-test diagnostic checks detect a
critical failure (see the Self-Test Errors section in chapter 7) or control power is lost, the relay de-energizes.

Connect all wires at the back of a UR before connecting to power, else death or serious injury can
result from electrical shock.
To connect power to the relay:
1. On the power supply module in the first slot, slot B, on the back of the device, connect the three wires to the terminals,
or connect two to the terminals and the third to the ground screw. 14 gauge stranded wire with disconnect devices is
recommended. Use 13 inch-pounds torque. Connect all wires to the relay before turning on power.

3-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

For high-reliability systems, the F60 has a redundant option in which two F60 power supplies are placed in parallel on the
bus. If one of the power supplies becomes faulted, the second power supply assumes the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate that it is functional. The critical fail
relay of the module also indicates a faulted power supply.
An LED on the front of the control power module shows the status of the power supply, as outlined in the table.
Table 3-2: Power supply LED on module
LED indication Power supply
Continuous on OK
On/off cycling Failure
Off Failure or no power

Figure 3-16: Control power connection

127(
3
$&RU'& JDXJHVWUDQGHG
ZLUHZLWKVXLWDEOH
GLVFRQQHFWGHYLFHV
LVUHFRPPHQGHG
+HDY\FRSSHUFRQGXFWRU )XVHV
RUEUDLGHGZLUH

%E %D %D %E %E


 
¯ /2: +,*+
),/7(5 685*(
&21752/
32:(5
6ZLWFKJHDU 85
JURXQGEXV SURWHFWLRQV\VWHP

$&'5

3.3.3.1 Non-volatile data storage


Non-volatile data is temporary data required after a power cycle for relay state, such as latch status before reboot. The
relay saves this data in non-volatile storage every two minutes or when a state change occurs.
If a state change occurs just before a power down (less than two minutes) and the relay power is cycled, some temporary
data can be saved and the prior state is retained at power up. Otherwise, a two-minute powered on period after a state
change ensures that all temporary state changes required after reboot have been saved. A command also is available to
initiate saving of data in the compact flash memory using Commands > Relay Maintenance > Save Volatile Data.

3.3.4 CT/VT modules


The CT and VT inputs are analog current transformer and voltage transformer signals used to monitor AC power lines. The
UR-series relays support 1 A and 5 A CTs.
A CT/VT module can have current or voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive.
Channels 1 and 5 are intended for connection to phase A, and are labelled as such in the relay. Likewise, channels 2 and 6
are intended for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channels are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-17


WIRING CHAPTER 3: INSTALLATION

Verify that the connection made to the relay terminals for nominal current of 1 A or 5 A matches the
secondary rating of the connected CTs. Unmatched CTs can result in equipment damage or
inadequate protection.
To connect to the module, size 12 American Wire Gauge (AWG) is used commonly; the maximum size is 10 AWG.
CT/VT modules can be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1
to 50000 A primaries and 1 A or 5 A secondaries can be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is 10
times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase VT
inputs are the same as those of regular CT/VT modules.

3 These modules have enhanced diagnostics that can detect automatically CT/VT hardware failure and take the relay out of
service.
CT connections for both ABC and ACB phase rotations are identical, as shown in the Typical Wiring Diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair
cabling on the zero-sequence CT is recommended.
Figure 3-17: Zero-sequence core balance CT installation
UNSHIELDED CABLE SHIELDED CABLE
Ground connection to neutral
Stress cone
Source must be on the source side Source shields
A B C N G A B C

Ground
outside CT

To ground;
LOAD must be on
load side

LOAD 996630A6.CDR

The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features, which are optional features for some UR models.

Substitute the tilde “~” symbol with the slot position of the module in the following figure.

3-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-18: CT/VT module wiring

IA5 ~ 1a IA5 ~ 1a

IA ~ 1b IA ~ 1b

IA1 ~ 1c IA1 ~ 1c

IB5 ~ 2a IB5 ~ 2a

IA5 ~1a IB ~ 2b IB ~ 2b

Current inputs
IA ~1b IB1 ~ 2c IB1 ~ 2c

IA1 ~1c IC5 ~ 3a IC5 ~ 3a

8Z module (used for high-impedance fault detection)


IB5 ~2a IC ~ 3b IC ~ 3b

IB ~2b IC1 ~ 3c IC1 ~ 3c


3
Current inputs

8H, 8J, 8N, and 8R modules (8 CTs)


IB1 ~2c IG5 ~ 4a IG5 ~ 4a
8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs)

IC5 ~3a IG ~ 4b IG ~ 4b

IC ~3b Current inputs IG1 IG1


~ 4c ~ 4c

IC1 ~3c IA5 ~ 5a

IG5 ~4a IA ~ 5b

IG ~4b IA1 ~ 5c

IG1 ~4c IB5 ~ 6a

VA ~5a IB ~ 6b

Not used
VA ~5c IB1 ~ 6c

VB ~6a IC5 ~ 7a
Voltage inputs

VB ~6c IC ~ 7b

VC ~7a IC1 ~ 7c

VC ~7c IG5 ~ 8a

VX ~8a IG ~ 8b

VX ~8c IG1 ~ 8c

842769A2.CDR

A relay configured for high impedance fault detection element includes two CT/VT modules: one type 8F, 8G, 8H, 8J, 8L, or
8N module and one type 8Z module. When 8Z is used alongside a CT/VT module with enhanced diagnostics, enhanced
diagnostics is not enabled because 8Z does not offer enhanced diagnostics. For correct operation of the high impedance
fault detection element, the ground current terminals of the two CT modules must be connected to a ground current
source, either a zero-sequence CT (see the Typical Wiring Diagram with High Impedance Fault Detection earlier in this
chapter) or, if a zero-sequence CT is not available, to the neutral conductor of the phase CTs (see diagram below).

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-19


WIRING CHAPTER 3: INSTALLATION

Figure 3-19: Typical 8Z module wiring with phase CTs

3RVLWLYHZDWWV
DPS&7

$
% 

&

0F ,*

=PRGXOH XVHGIRUKLJKLPSHGDQFHIDXOWGHWHFWLRQ
0E ,*

0D ,*

0F ,&

3 0E ,&

&XUUHQWLQSXWV
0D ,&

0F ,%

*URXQG 0E ,%
)XVH
LVRODWLRQ
OLQN 0D ,%

0F ,$

0E ,$

0D ,$
)D

)D

)D

)D

)D

)D

)D
)D

)E

)E

)E

)E
)F

)F

)F

)F

)F

)F

)F

)F
9&
9%

9;
9$

,*

,*
,&
,$

,%
9&

,&
,$

,%
9%

,*
9;
9$

,&
,$

,%

9ROWDJHLQSXWV &XUUHQWLQSXWV
)*/DQG0PRGXOHV &7VDQG97V $&'5

3.3.5 Process Bus Module for HardFiber


The F60 can be ordered with a process bus interface module to interface with the HardFiber Process Bus System, or
HardFiber Brick, allowing bidirectional IEC 61850 fiber-optic communications with up to eight HardFiber Bricks. The
HardFiber system integrates seamlessly with the existing UR-series applications, including protection functions, FlexLogic,
metering, and communications.
This process bus system offers the following benefits:
• Reduces labor associated with design, installation, and testing of protection and control applications using the UR by
reducing the number of individual copper terminations
• Integrates seamlessly with existing UR applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules
• Communicates using open standard IEC 61850 messaging
For details on the HardFiber system, see its Instruction Manual.

3-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

3.3.6 Contact inputs and outputs


Nearly all contact input/output modules have 24 terminal connections. The connections are arranged typically as three
terminals per row, with eight rows in total. A given row of three terminals can be used for the outputs of one relay. For
example, for form-C relay outputs, the terminals connect to the normally open (NO), normally closed (NC), and common
contacts of the relay. For a form-A output, there are options of using current or voltage detection for feature supervision,
depending on the module ordered. The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The input/output modules have three versions of grouping: four
inputs per common return, five inputs per common return on a high-density module, and two inputs per common return.
When a contact input/output module is ordered, four inputs per common is used. If the inputs must be isolated per row,
then two inputs per common return are selected (4D module). If the space limitation in the relay requires use of a high-
density input module (6W), five inputs share one common return and the module has six banks of inputs.
The tables and diagrams that follow illustrate the module types (6A and so on) and contact arrangements that can be
ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
3
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is
open, and the DC current through the output contact when it is closed. Each of the monitors contains a level detector
whose output is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is
set to “On = 1” when there is a voltage across open contact (the detector allows a current of about 1 to 2.5 mA), and the
current monitor is set to “On = 1” when the current flowing through the closed contact exceeds about 80 to 100 mA. The
voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be used to seal-in
the output contact until an external contact has interrupted current flow. If enabled, the current monitoring can be used as
a seal-in signal to ensure that the form-A contact does not attempt to break the energized inductive coil circuit and weld
the output contacts.
Block diagrams are shown as follows for form-A and solid-state relay outputs with optional voltage monitor, optional
current monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact
outputs. Form-A contact output with or without a current or voltage monitoring option is not polarity sensitive. The polarity
shown in the figure is required for solid-state contact output connection.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-21


WIRING CHAPTER 3: INSTALLATION

Figure 3-20: Form-A and solid-state contact outputs with voltage and current monitoring

~#a ~#a
I I
~#b ~#b Load
V Load V
~#c + ~#c +
a) Voltage with optional
Voltage monitoring only Both voltage and current monitoring
current monitoring

~#a ~#a
V V

3 I ~#b

Load
I ~#b Load

~#c + ~#c +
b) Current with optional
Current monitoring only Both voltage and current monitoring
voltage monitoring
(external jumper a-b is required)

~#a

~#b

Load
~#c +
c) No monitoring
827862A5.CDR

The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON,
CONT OP # VOFF, and CONT OP # ION) that can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied
for breaker trip circuit integrity monitoring.

Consider relay contacts unsafe to touch when the unit is energized. Death or serious injury can
result from touching live relay contacts.

USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH-IMPEDANCE CIRCUITS


For form-A and solid-state relay output contacts internally equipped with a voltage measuring circuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high-input
impedance monitoring equipment, such as modern relay test set trigger circuits. These monitoring circuits can
continue to read the form-A contact as being closed after it has closed and subsequently opened, when measured
as an impedance.
The solution is to use the voltage measuring trigger input of the relay test set, and connect the form-A contact
through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is used as a
source, a 500 Ω, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A contact or
the resistor can be used to monitor the state of the output.

Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears,
substitute the contact number.

3-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
For high-density input/output modules 6W and 6X, use the following guidelines to connect. The new I/O modules use pin
type terminal blocks instead of the current ring type. The new terminals are required to achieve higher I/O count per
module.
• 12 to 24 AWG (3.3 mm2 to 0.2 mm2), single wire termination
• 16 to 24 AWG (1.31 mm2 to 0.2 mm2), multiple wire termination with matching wire sizes and stranding. Two wires
maximum per circuit
• Suggested wiring screw tightening torque is a minimum 4.43 in-lb (0.5 Nm) and maximum 5.31 in-lb (0.6 Nm)


Minimum suggested temperature rating for the conductors is 75°C
Wire type: copper
3
For module types 67, 6A, 6B, 6C, 6D, 6E, 6F, 6G, 6H, 6K, 6L, 6M, 6N, 6P, 6R, 6S, 6T, 6U, 6V, 4A, 4B, 4C, 4D, and 4L, use the
following guidelines to connect:
• 12 to 24 AWG (3.3 mm2 to 0.2 mm2)
• Wiring screw tightening torque is 19 inch-pounds, (2.15 Nm)
• Minimum suggested temperature rating for the conductors is 75°C
• Wire type: copper
Table 3-3: Contact input and output module assignments
~6A module ~6B module ~6C module ~6D module
Terminal Output or Terminal Output or Terminal Output Terminal Output
assignment input assignment input assignment assignment
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4 Form-C ~4 Form-C ~4 Form-C ~4a, ~4c 2 Inputs
~5a, ~5c 2 Inputs ~5 Form-C ~5 Form-C ~5a, ~5c 2 Inputs
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs

~6E module ~6F module ~6G module ~6H module


Terminal Output or Terminal Output Terminal Output or Terminal Output or
assignment input assignment assignment input assignment input
~1 Form-C ~1 Fast Form-C ~1 Form-A ~1 Form-A
~2 Form-C ~2 Fast Form-C ~2 Form-A ~2 Form-A
~3 Form-C ~3 Fast Form-C ~3 Form-A ~3 Form-A
~4 Form-C ~4 Fast Form-C ~4 Form-A ~4 Form-A
~5a, ~5c 2 Inputs ~5 Fast Form-C ~5a, ~5c 2 Inputs ~5 Form-A
~6a, ~6c 2 Inputs ~6 Fast Form-C ~6a, ~6c 2 Inputs ~6 Form-A
~7a, ~7c 2 Inputs ~7 Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8 Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-23


WIRING CHAPTER 3: INSTALLATION

~6K module ~6L module ~6M module ~6N module


Terminal Output Terminal Output or Terminal Output or Terminal Output or
assignment assignment input assignment input assignment input
~1 Form-C ~1 Form-A ~1 Form-A ~1 Form-A
~2 Form-C ~2 Form-A ~2 Form-A ~2 Form-A
~3 Form-C ~3 Form-C ~3 Form-C ~3 Form-A
~4 Form-C ~4 Form-C ~4 Form-C ~4 Form-A
~5 Fast Form-C ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Fast Form-C ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7 Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8 Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs
3
~6P module ~6R module ~6S module ~6T module
Terminal Output or Terminal Output or Terminal Output or Terminal Output or
assignment input assignment input assignment input assignment input
~1 Form-A ~1 Form-A ~1 Form-A ~1 Form-A
~2 Form-A ~2 Form-A ~2 Form-A ~2 Form-A
~3 Form-A ~3 Form-C ~3 Form-C ~3 Form-A
~4 Form-A ~4 Form-C ~4 Form-C ~4 Form-A
~5 Form-A ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Form-A ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs

~6U module ~6V module ~6W module 6X module


Terminal Output or Terminal Output or Terminal Output or Terminal Output or
assignment input assignment input assignment input assignment input
~1 Form-A ~1 Form-A ~1a Input ~1a, ~2a Form-A
~2 Form-A ~2 Form-A ~2a Input ~3a, ~4a Form-A
~3 Form-A ~3 Form-C ~3a Input ~5a, ~6a Form-A
~4 Form-A ~4 2 Outputs ~4a Input ~7a, ~8a Form-A
~5 Form-A ~5a, ~5c 2 Inputs ~5a Input ~9a, ~10a Form-A
~6 Form-A ~6a, ~6c 2 Inputs ~7a Input ~11a, ~12a Form-A
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a Input ~13a, ~14a Form-A
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~9a Input ~15a, ~16a Form-A
--- --- --- --- ~10a Input ~17a, ~18a Form-A
--- --- --- --- ~11a Input ~1b, ~2b Form-A
--- --- --- --- ~13a Input ~3b, ~4b Form-A
--- --- --- --- ~14a Input ~5b, ~6b Form-A
--- --- --- --- ~15a Input ~7b, ~8b Form-A
--- --- --- --- ~16a Input ~9b, ~10b Form-A
--- --- --- --- ~17a Input ~11b, ~12b Form-A
--- --- --- --- ~1b Input ~13b, ~14b Form-A
--- --- --- --- ~2b Input ~15b, ~16b Form-A
--- --- --- --- ~3b Input ~17b, ~18b Form-A

3-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

~6U module ~6V module ~6W module 6X module


Terminal Output or Terminal Output or Terminal Output or Terminal Output or
assignment input assignment input assignment input assignment input
--- --- --- --- ~4b Input --- ---
--- --- --- --- ~5b Input --- ---
--- --- --- --- ~7b Input --- ---
--- --- --- --- ~8b Input --- ---
--- --- --- --- ~9b Input --- ---
--- --- --- --- ~10b Input --- ---
--- --- --- --- ~11b Input --- ---
--- --- --- --- ~13b Input --- ---
--- --- --- --- ~14b Input --- ---
--- --- --- --- ~15b Input --- --- 3
--- --- --- --- ~16b Input --- ---
--- --- --- --- ~17b Input --- ---

~67 module ~4A module ~4B module ~4C module


Terminal Output Terminal Output Terminal Output Terminal Output
assignment assignment assignment assignment
~1 Form-A ~1 Not Used ~1 Not Used ~1 Not Used
~2 Form-A ~2 Solid-State ~2 Solid-State ~2 Solid-State
~3 Form-A ~3 Not Used ~3 Not Used ~3 Not Used
~4 Form-A ~4 Solid-State ~4 Solid-State ~4 Solid-State
~5 Form-A ~5 Not Used ~5 Not Used ~5 Not Used
~6 Form-A ~6 Solid-State ~6 Solid-State ~6 Solid-State
~7 Form-A ~7 Not Used ~7 Not Used ~7 Not Used
~8 Form-A ~8 Solid-State ~8 Solid-State ~8 Solid-State

~4D module ~4L module


Terminal Output Terminal Output
assignment assignment
~1a, ~1c 2 Inputs ~1 2 Outputs
~2a, ~2c 2 Inputs ~2 2 Outputs
~3a, ~3c 2 Inputs ~3 2 Outputs
~4a, ~4c 2 Inputs ~4 2 Outputs
~5a, ~5c 2 Inputs ~5 2 Outputs
~6a, ~6c 2 Inputs ~6 2 Outputs
~7a, ~7c 2 Inputs ~7 2 Outputs
~8a, ~8c 2 Inputs ~8 Not Used

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-25


WIRING CHAPTER 3: INSTALLATION

Figure 3-21: Contact input and output module wiring (Sheet 1 of 3)

842762A4.CDR

3-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-22: Contact input and output module wiring (Sheet 2 of 3)


a D a D a
&217$&7,1D ',*,7$/,2 / 9 a D a D a
&217$&7,1D ',*,7$/,2 0 9 a D

.
, ,
a E a a F a
&217$&7,1F a a E a F a
&217$&7,1F a a E
a F a D a
&217$&7,1D a F a D a
&217$&7,1D a F
a D a F a
&217$&7,1F 9 a D a F a
&217$&7,1F 9 a D
, ,
a E a a E a
&20021E a a E a E a
&20021E a a E
a F a F a F
a D a
&217$&7,1D a E 685*(
a D a D a D
a F a
&217$&7,1F
a E a a a E a a E
a D a
&217$&7,1D
a F a F a F
a F a
&217$&7,1F
a D a D a D
a E a
&20021E
a E a a a E a a E
a F a E 685*( a F a F
a D a D
a E a a a E
a F a F
a D a D
a E a a a E
a F a F
a D
',*,7$/,2

a E a
a F
a D
a E a
a F
3
a D a
&217$&7,1D ',*,7$/,2 1 9 a D a D a
&217$&7,1D ',*,7$/,2 3 9 a D
, ,
a F a
&217$&7,1F a a E a F a
&217$&7,1F a a E
a D a
&217$&7,1D a F a D a
&217$&7,1D a F
a F a
&217$&7,1F 9 a D a F a
&217$&7,1F 9 a D
, ,
a E a
&20021E a a E a E a
&20021E a a E
a F a F
a D a
&217$&7,1D a E 685*(
9 a D 9 a D
a F a
&217$&7,1F , ,
a a E a a E
a D a
&217$&7,1D
a F a F
a F a
&217$&7,1F
9 a D 9 a D
a E a
&20021E , ,
a a E a a E
a E 685*( a F a F
9 a D
,
a a E
a F
a D a
&217$&7,1D ',*,7$/,2 5 a D 9 a D
,
a F a
&217$&7,1F a a E a a E
a D a
&217$&7,1D a F a F
a F a
&217$&7,1F a D
a E a
&20021E a a E
a F
a D a
&217$&7,1D
a D a D a
&217$&7,1D ',*,7$/,2 6 a D
a F a
&217$&7,1F
a a E a F a
&217$&7,1F a a E
a D a
&217$&7,1D
a F a D a
&217$&7,1D a F
a F a
&217$&7,1F
a D a F a
&217$&7,1F a D
a E a
&20021E
a a E a E a
&20021E a a E
a E 685*( a F a F
a E 685*(
a D
a a E
a F
a D a
&217$&7,1D ',*,7$/,2 7 a D a D
a F a
&217$&7,1F a a E a a E
a D a
&217$&7,1D a F a F
a F a
&217$&7,1F a D a D
a E a
&20021E a a E a a E
a F a F
a D a
&217$&7,1D
a D a D
a F a
&217$&7,1F
a a E a a E
a D a
&217$&7,1D
a F a F
a F a
&217$&7,1F
a D
a E a
&20021E
a a E
a E 685*( a F
a D a
&217$&7,1D ',*,7$/,2 8 a D
a F a
&217$&7,1F a a E
a D a
&217$&7,1D a F
a D a
&217$&7,1D ',*,7$/,2 9 9 a D
, a F a
&217$&7,1F a D
a F a
&217$&7,1F a a E
a E a
&20021E a a E
a D a
&217$&7,1D a F
a F
a F a
&217$&7,1F 9 a D a E 685*(
, a D
a E a
&20021E a a E
a a E
a F
a D a
&217$&7,1D a F
a D
a F a
&217$&7,1F a D
a a E
a D a
&217$&7,1D a a E
a F
a F a
&217$&7,1F a F
a D
a E a
&20021E a D a D
a E
a F a a E
a E 685*( a F
a F
a D
a a E
a F

$&'5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-27


WIRING CHAPTER 3: INSTALLATION

Figure 3-23: Contact input and output module wiring (Sheet 3 of 3)


',*,7$/,2 : ',*,7$/,2 ;
a E a
&217$&7,1E a
&217$&7,1D a D a E a D
a  a 
a E a
&217$&7,1E a
&217$&7,1D a D a E a D
a E a
&217$&7,1E a
&217$&7,1D a D a E a D
a  a 
a E a
&217$&7,1E a
&217$&7,1D a D a E a D
a E a
&217$&7,1E a
&217$&7,1D a D a E a D
a  a 
a E  &20021aE &20021aD  a D a E a D
a E a D
a E a
&217$&7,1E a
&217$&7,1D a D a  a 
a E a D
a E a
&217$&7,1E a
&217$&7,1D a D
a E a D
a E a
&217$&7,1E a
&217$&7,1D a D a  a 
aE a D
aE a
&217$&7,1E a
&217$&7,1 aD aE a D
aE a
&217$&7,1E a
&217$&7,1D aD a  a 
aE a D
aE  &20021aE &20021aD  aD aE a D
a  a 
a E a
&217$&7,1E &217$&7,1D
a a D aE a D
a E a
&217$&7,1E a
&217$&7,1D a D aE a D
a  a 
a E a
&217$&7,1E &217$&7,1D
a a D aE a D
aE a
&217$&7,1E a
&217$&7,1D aD aE a D
a  a 
aE a
&217$&7,1E a
&217$&7,1D aD aE a D
aE  &20021aE &20021aD  aD
$&'5

3 For proper functionality, observe the polarity shown in the figures for all contact input and output
connections.

3.3.6.1 Contact inputs


A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power supply
module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal that must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA flows through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this
contact is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external
source must be connected to the relay common (negative) terminal of each contact group. The maximum external source
voltage for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs detects a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
Figure 3-24: Dry and wet contact input connections
Terminals from type 6B Terminals from type 6B
(Dry) contact input/output module (Wet) contact input/output module
~7a Contact input 1 ~7a Contact input 1
~7c Contact input 2 ~7c Contact input 2
~8a Contact input 3 24 to 250 V ~8a Contact input 3
~8c Contact input 4 ~8c Contact input 4
~7b Common ~7b Common
~8b Surge ~8b Surge

B1b
B1a Critical failure
B2b
Power supply module

B3a
48 V DC output
B3b
B5b HI+
B6b LO+ Control power
B6a
B8a Surge
B8b Filter

827741A5.CDR

Where a tilde “~” symbol appears, substitute the slot position of the module.

3-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend
using an external DC supply.

3.3.6.2 General application considerations


Contacts outputs of protective relays, auxiliary contacts from breakers, disconnectors and other devices are connected
generally to contacts inputs of protective relays. In some situations, the contact outputs of some protective relays can
have high impedance connected across it. When such a contact output is connected across a F60 contact input, it can
spuriously operate the F60 input even when the output is open, if there is a substantial distributed capacitance
(represented by C1) present in the wiring between the output and the F60 input, and the debounce time setting in the F60
relay is low enough. This false assertion of the contact input, when there is inadvertent ground present at the DC positive
terminal, can be prevented by inserting a resistor across the F60 input.
The following figure shows a typical DC circuit, with battery ground detection, of contact input. The contact output has
parallel impedance across it (represented by R1).
Figure 3-25: Typical contact input DC circuit 3

$POUBDU*OQVU

$FGU

The presence of the impedance path (R1) across the contact output allows the stray (distributed) capacitance C1 to charge
as shown, thus developing a voltage across the contact input enough to momentarily operate the input while the
capacitance discharges in the presence of DC ground on the positive terminal of the battery.
The duration of the discharge depends on the value of the distributed capacitance, the initial voltage of the distributed
capacitance, and the input impedance of the contact input. If the duration is greater than the debounce time setting, then
the contact input operates.
The application example that follows describes how to mitigate this issue by connecting a resistor across the contact
input, as shown in the next figure, or by adjusting the debounce time setting to a value greater than the discharge time to
prevent spurious operation of the contact input only if the voltage (with output open) across the contact input due to trickle
current is less than the threshold voltage. This operation of contact inputs also can be prevented by using the Auto-Burnish
contact inputs or contact inputs with active impedance.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-29


WIRING CHAPTER 3: INSTALLATION

Figure 3-26: Contact input connected to a contact output with resistor (R2) across the input

$POUBDU*OQVU

3
$FGU

Application example
This example is for illustrative purposes only and the calculations present the worst-case scenario. In practice, the value of
debounce time can be lower.
Contact input ON state impedance used in the calculation of the discharge period is based on the following table.
Table 3-4: Discharge period
Battery voltage (V) Input impedance (kΩ)
130 50
250 97

Debounce time setting = 2 ms


Assume a stray capacitance of 0.1 μF.
Assume an initial voltage across the stray capacitance "Vinitial" = 19 V (Vthreshold - 65 V), where Vthreshold = 84 V. The
initial voltage Vinitial depends on values of impedance of R1 and contact inputs when the contact input is OFF (non-
activated state).
Therefore, discharge time constant (τ) =50 kΩ *0.1 μF = 5 ms.
Discharge period t is calculated from the following equation:
Vthreshold = (Vbatt - VInitial) *e^ (-t/τ)
84 = -149 *e^ (t/0.005) Eq. 3-1
T = -0.005 * ln (84/149) = 0.0029 s
Therefore, in this example the contact inputs operate.
To prevent this operation, the debounce time must be increased to 4 ms (set debounce time as per the following table) or
insert a resistor less than or equal to "R" as calculated later.
Table 3-5: Typical debounce time setting
Stray capacitance (μF) Battery voltage (V) Debounce time (ms)
0.05 130 2
0.1 130 4
0.2 130 6
0.05 250 3
0.1 250 6*

3-30 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Stray capacitance (μF) Battery voltage (V) Debounce time (ms)


0.2 250 11

* Default debounce time on contact inputs is 6 ms.


The value of this resistor "R" is calculated as follows:
1. Determine the minimum voltage (V threshold) required to turn on the input. This is determined by direct measurement
or referenced in the input specifications.
2. Calculate the resistance necessary to limit the voltage to 1/3 V threshold (when the contact is OFF, the non-activated
state) as follows:
R = (Vthreshold / 3) / (2 mA) Eq. 3-2
The 2 mA current is used in case the contact input is connected across the GE Form A contact output with voltage
monitoring. Otherwise use the amperage of the active circuit connected to the contact input when its contact output

3.
is open and the voltage across the contact input is third trigger threshold to calculate the resistor value.
When the contact is ON (operate state), the battery voltage appears across the resistor. The wattage rating of the
3
resistor is then:
PR = 1.3 * (Vbatt) ^2 / R Watts Eq. 3-3
4. Applying the following equation to our example:
R = 84 V / 3 * (1 / 2 mA) = 14 kΩ
PR = 1.57 Watts Eq. 3-4
5. Calculating the voltage across the contact input with the Burden Resistor, Voltage across the contact Input:
Vresistor = 2 mA * 14 Kohm = 28 V
Vresistor < contact input threshold (84 V) Eq. 3-5
In conclusion, in this example, the contact input does NOT operate falsely with the Burden Resistor across its input AND
when a battery ground is present.

3.3.6.3 Use of contact inputs with auto-burnishing


The contact inputs sense a change of state of the external device contact based on the measured current. When external
devices are located in a harsh industrial environment (either outdoor or indoor), their contacts can be exposed to various
types of contamination. Normally, there is a thin film of insulating sulfidation, oxidation, or contaminates on the surface of
the contacts, sometimes making it difficult or impossible to detect a change of state. This film must be removed to
establish circuit continuity — an impulse of higher than normal current can accomplish this.
The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation
layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The
impulse has a five-second delay after a contact input changes state.
Figure 3-27: Current through contact inputs with auto-burnishing
Current

50 to 70 mA

3 mA
Time

25 to 50 ms
842749A1.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-31


WIRING CHAPTER 3: INSTALLATION

Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with
auto-burnishing allow currents up to 50 to 70 mA at the first instance when the change of state is sensed. Then, within 25
to 50 ms, this current is slowly reduced to 3 mA as indicated. The 50 to 70 mA peak current burns any film on the contacts,
allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts when
external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two
contact inputs have common ground, as opposed to four contact inputs sharing one common ground (see the Contact
Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources.
Consequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.
Figure 3-28: Auto-burnish DIP switches

3 &RQWDFWLQSXWDXWREXUQLVK 2II
&RQWDFWLQSXWDXWREXUQLVK 2II

&RQWDFWLQSXWDXWREXUQLVK 2Q
&RQWDFWLQSXWDXWREXUQLVK 2II

&RQWDFWLQSXWDXWREXUQLVK 2II
&RQWDFWLQSXWDXWREXUQLVK 2Q

&RQWDFWLQSXWDXWREXUQLVK 2Q
&RQWDFWLQSXWDXWREXUQLVK 2Q

$&'5

The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-burnish
functionality using an oscilloscope.

3.3.6.4 Use of contact inputs with active impedance


Contact inputs can be susceptible to parasitic capacitance, caused by long cable runs affected by switching surges from
external circuits. This can result in inadvertent activation of contact inputs with the external contact open. In this case, GE
recommends using the contact I/O module with active impedance circuit.
Active impedance contact input can tolerate external cable capacitance of up to 0.2 µF, without entering the ON state for
more than 2 ms. The contact input debounce time can still be set above 2 ms for added security to prevent contact input
activations caused by external transient ON states.
An active impedance contact input is normally in Low impedance mode during OFF contact state (non-activated
condition). During Low impedance state, contact input impedance is maintained at 10 K Ohms impedance to allow fast
discharge of the stray capacitance of the long cables.
When the contact input voltage exceeds the set threshold, active impedance maintains 10 K Ohms impedance. If voltage
starts rapidly decreasing, this indicates that stray capacitance is being discharged through the contact input. If, however,
voltage stabilizes above the set threshold, the input impedance is switched to High impedance mode of 100 K Ohms. This
value reduces the input current to <3 mA, and contact input switches to the ON state (operated state).
The figure shows the active impedance contact input V-I characteristic. Different thresholds with their corresponding
characteristics are shown by color. The contact input is in the ON (operated) state if the input voltage is to the right of the
colored threshold band (+/-10% tolerance), and the contact input is in the OFF (non-activated) state when input voltage is
to the left of the band. A contact input is in LOW state during non-operated system condition, and actively switches to
HIGH state upon detection of input voltage above the settable threshold.

3-32 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-29: Active impedance contact input V-I characteristic

30

84 V threshold

166 V threshold
17 V threshold

33 V threshold

e
at
st
e
25

nc
da
pe
im
w
Lo
20

3
Current (millamperes)

15
s
m
oh
K
10

10

166 V threshold
84 V threshold
33 V threshold
5 17 V threshold

100 K ohms dance state


HIgh impe
0 5
0 100 150 200 250 300
0
Voltage (Volts) 859757A2.vsd

3.3.7 Transducer inputs and outputs


Transducer input modules receive input signals from external DCmA output transducers (DCmA In) or resistance
temperature detectors (RTDs). Hardware and software are provided to receive signals from these external transducers and
convert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard DCmA ranges. Software is provided to
configure virtually any analog quantity used in the relay to drive the analog outputs.
Each transducer input/output module has 24 terminal connections. These connections are arranged as three terminals
per row over eight rows. A given row can be used for either inputs or outputs, with terminals in column "a" having positive
polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/output channel,
the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The following figure illustrates the
transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-33


WIRING CHAPTER 3: INSTALLATION

Where a tilde “~” symbol appears, substitute the slot position of the module.

Figure 3-30: Transducer input/output module wiring

$&'5

The following figure show how to connect RTDs.

3-34 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-31: RTD connections


7KUHHZLUHVKLHOGHGFDEOH
5RXWHFDEOHLQVHSDUDWHFRQGXLWIURP
FXUUHQWFDUU\LQJFRQGXFWRUV
57'WHUPLQDOV

685*( aE 57'

+RW aD
57' a
&RPS aF
)RU57' a a 5HWXUQ aE 57'WHUPLQDOV
+RW aD
57' a
&RPS aF
57'
3
0D[LPXPWRWDOOHDGUHVLVWDQFH
RKPVIRU3ODWLQXP57'V
$&'5

3.3.8 RS232 port


On the enhanced and basic front panels is a nine-pin RS232C serial port for programming with a computer. All that is
required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for
the RS232 port is shown in the following figure for the nine-pin connector on the UR and nine or 25-pin connector on a
computer.
The baud rate for this port can be set, with a default of 115200 bps.
Figure 3-32: RS232 front panel port connection
Front panel 9 pin RS232 Program port

1: N/A
2: (TXD)
3: (RXD)
RELAY
PERSONAL 4: N/A
COMPUTER 5: (SGND) Signal Ground
FRONT PANEL
6: N/A
PROGRAM PORT 7: N/A
8: N/A
9: N/A

9 PIN
RS232 RS232
D CONNECTOR D CONNECTOR

URS232 INTERFACE COM1 OR COM2


SERIAL PORT
RELAY COMPUTER
1 1 8 827758A3.cdr
TXD 2 2 3 RXD
RXD 3 3 2 TXD
4 4 20
SGND 5 5 7 SGND
6 6 6
7 7 4
8 8 5
9 9 22

9 PIN 25 PIN
CONNECTOR CONNECTOR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-35


WIRING CHAPTER 3: INSTALLATION

3.3.9 CPU communication ports

3.3.9.1 Overview
There is a rear RS485 communication port on the CPU module.
The CPU module does not require a surge ground connection.
For Sampled Value (SV) applications using a Process Bus Module with order code 85, 86, or 87 with IRIG-B for
synchronization, follow the recommended cables and grounding connections. If using a Process Bus Module and IRIG-B as
the synchronizing source, GE recommends moving the grounding from the IRIG-B generator to UR terminal D4a in order to
better protect the IRIG-B input from long bursts of transient noise.

3-36 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Figure 3-33: CPU module wiring when using a Process Bus Module

00ILEHU
3RUW

7
RSWLFFDEOH 7[ 5[ %DVH);
7[ 5[ %DVH); 3RUW

6KLHOGHGWZLVWHGSDLUFDEOH
7[ 5[ %DVH); 3RUW
'D 
56
'D ³
&20
*URXQGDW 'D &20021
85 'E 
GHYLFH
'D ³ ,5,*%
LQSXW

&38
%1&
&RD[LDOFDEOH
*URXQGFRD[LDOFDEOHXVLQJWHUPLQDO'D

6KLHOGHG(WKHUQHWFDEOH 3

8
%DVH7; 3RUW
00ILEHU
RSWLFFDEOH 7[ 5[ %DVH); 3RUW
7[ 5[ %DVH); 3RUW
6KLHOGHGWZLVWHGSDLUFDEOH
'D 
56
'D ³
&20
*URXQGDW 'D &20021
85 'E 
GHYLFH
'D ³ ,5,*%
LQSXW

&38
%1&
&RD[LDOFDEOH
*URXQGFRD[LDOFDEOHXVLQJWHUPLQDO'D

3RUW

9
%DVH7;
6KLHOGHG(WKHUQHWFDEOH
%DVH7; 3RUW
%DVH7; 3RUW
6KLHOGHGWZLVWHGSDLUFDEOH
'D 
56
'D ³
&20
*URXQGDW 'D &20021
85 'E 
GHYLFH
'D ³ ,5,*%
LQSXW
&38
%1&
&RD[LDOFDEOH
*URXQGFRD[LDOFDEOHXVLQJWHUPLQDO'D

6KLHOGHG(WKHUQHWFDEOH
:

%DVH7; 3RUW
00ILEHU
RSWLFFDEOH
7[ 5[ %DVH); 3RUW
7[ 5[ %DVH); 3RUW
6KLHOGHGWZLVWHGSDLUFDEOH
'D 
56
'D ³
&20
*URXQGDW 'D &20021
85 'E 
GHYLFH
'D ³ ,5,*%
LQSXW
&38

%1&
&RD[LDOFDEOH
*URXQGFRD[LDOFDEOHXVLQJWHUPLQDO'D $&'5

If not using a Process Bus Module (order code 85, 86, 87), the following IRIG-B cable and ground connection is appropriate.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-37


WIRING CHAPTER 3: INSTALLATION

Figure 3-34: CPU module wiring for IRIG-B without Process Bus Module
00ILEHU
3RUW

7
RSWLFFDEOH 7[ 5[ %DVH);
7[ 5[ %DVH); 3RUW
6KLHOGHG 7[ 5[ %DVH); 3RUW
WZLVWHGSDLUV
'D 
56
'D ³
&20
*URXQGDW 'D &20021
UHPRWH 'E 
GHYLFH
'D ³ ,5,*%
LQSXW

&38
%1&
&RD[LDOFDEOH

8
%DVH7; 3RUW
7[ 5[ %DVH); 3RUW
6KLHOGHG 7[ 5[ %DVH); 3RUW
WZLVWHGSDLUV
'D 
56
'D ³
&20
*URXQGDW 'D &20021
UHPRWH 'E 
GHYLFH
'D ³ ,5,*%
LQSXW

&38
%1&
&RD[LDOFDEOH

3RUW

9
%DVH7;

%DVH7; 3RUW
6KLHOGHG %DVH7;
WZLVWHGSDLUV 3RUW
'D 
56
'D ³
&20
*URXQGDW 'D &20021
UHPRWH 'E 
GHYLFH
'D ³ ,5,*%
LQSXW
&38

%1&
&RD[LDOFDEOH
$&'5

3.3.9.2 RS485 port


RS485 data transmission and reception are accomplished over a single twisted-pair wire with transmit and receive data
alternating over the same two wires. Through the use of the port, continuous monitoring and control from a remote
computer, SCADA system, or Power Line Carrier (PLC) is possible.
To minimize errors from noise, the use of shielded twisted-pair wire is recommended. Correct polarity must be observed.
For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–” terminals
connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared reference,
or common voltage. This common voltage is implied to be a power supply common. Some systems allow the shield (drain
wire) to be used as common wire and to connect directly to the F60 COM terminal (#3); others function correctly only if the
common wire is connected to the F60 COM terminal, but insulated from the shield.
To avoid loop currents, ground the shield at only one point. If other system considerations require the shield to be
grounded at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding
point. Each relay needs to be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this
manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also
possible to use commercially available repeaters to have more than 32 relays on a single channel. Avoid star or stub
connections entirely.

3-38 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION WIRING

Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are provided internally at both communication ports. An
isolated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum
reliability, ensure that all equipment has similar transient protection devices installed.
Terminate both ends of the RS485 circuit with an impedance as shown in the figure.
Figure 3-35: RS485 serial connection

SCADA / PLC / computer UR-series device


Shield Twisted pair
ZT (*) RS485 +
Data Optocoupler Optocoupler Data
RS485 –

COM

COMP 485COM 3
Ground shield at SCADA / PLC /
computer only or at
UR-series device only Relay
RS485 +
ZT (*) Terminating impedance at
RS485 –
each end (typically 120 Ω and 1 nF)

COMP 485COM

Up to 32 devices,
maximum 4000 feet
(1200 m)
Relay
ZT (*)
RS485 +
RS485 –

COMP 485COM Last device


827757AA.CDR

3.3.9.3 100Base-FX fiber optic ports


The fiber-optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical
fiber can be connected to the relay supporting a wavelength of 1310 nm in multimode.
Ensure that the dust covers are installed when the fiber is not in use. Dirty or scratched connectors can lead to high losses
on a fiber link.

3.3.10 IRIG-B
There is a round IRIG-B connector at the back of the CPU module, marked "IN." Use is optional.
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The
IRIG-B code allows time accuracies of up to 100 ns. The GE MultiSync 100 1588 GPS Clock as well as third-party equipment
are available for generating the IRIG-B signal. This equipment can use a global positioning system (GPS) satellite system to
obtain the time reference so that devices at different geographic locations can be synchronized. The IRIG time code
formats are serial, pulse width-modulated codes that can be either DC level shifted or amplitude modulated (AM). Using
IRIG-B input, the F60 operates an internal oscillator with 1 µs resolution and accuracy.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-39


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-36: Options for IRIG-B connection

*36FRQQHFWLRQ *36VDWHOOLWHV\VWHP

85
,5,*% % ,5,*% 
WLPHFRGHJHQHUDWRU $ ,5,*% ²
5*FRD[LDOFDEOH 5HFHLYHU
'&VKLIWRU 
%1& LQ
DPSOLWXGHPRGXODWHG
VLJQDOFDQEHXVHG

*36FRQQHFWLRQ *36VDWHOOLWHV\VWHP

,5,*%
WLPHFRGHJHQHUDWRU 85
6KLHOGHGWZLVWHGSDLUFDEOH
 % ,5,*% 
'&VKLIWRU
$ ,5,*% ²
DPSOLWXGHPRGXODWHG
VLJQDOFDQEHXVHG 5HFHLYHU
%1& LQ

$&'5

Using an amplitude-modulated receiver causes errors up to 1 ms in event time stamping.

3.4 Direct input and output communications


3.4.1 Description
The direct inputs and outputs feature makes use of the type 7 series of communications modules and allows direct
messaging between UR devices. The communications modules are outlined in the table later in this section.
The communications channels are normally connected in a ring configuration, as shown in the following figure. The
transmitter of one module is connected to the receiver of the next module. The transmitter of this second module is then
connected to the receiver of the next module in the ring. This is continued to form a communications ring. The figure
illustrates a ring of four UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to
UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of 16 URs can be connected in a single ring.

3-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

Figure 3-37: Direct input and output single-channel connection

Tx
UR 1
Rx

Tx
UR 2
Rx

Tx
UR 3
Rx

Tx
UR 4

3
Rx
842006A2.CDR

Inter-relay communication (IRC) modules with protocol C37.94 and G.703 are designed for back-to-back communication
connections, so the ring configuration shown in the previous figure does not apply. To establish inter-relay communication
in more than two URs, you need to have a two-channel IRC module and enable the DIRECT I/O CHANNEL CROSSOVER setting
in all relays, as shown in the next figure. This configuration can be expanded to 16 URs, and this configuration does not
provide a redundancy ring since both channels are made into a single ring by the channel crossover function. As per the
figure entitled Typical Pin Interconnection between Two G.703 Interfaces later in this chapter, the clock is supplied typically
by multiplexer (MUX) and all URs are in Loop Timing Mode. If there is no MUX, then UR1 and UR3 can be in Internal Timing
Mode and UR2 and UR4 can be in Loop Timing Mode. That is, connected channels must have opposite timing modes.
Figure 3-38: Ring configuration for C37.94 module (concept also applies to G.703)

7[ 7[ 7[ 7[


08; 85 08; 08; 85 08;
5[ 5[ 5[ 5[

7[ 7[ 7[ 7[


08; 85 08; 08; 85 08;
5[ 5[ 5[ 5[

$&'5

The interconnection for dual-channel type 7 communications modules is shown as follows. Two-channel modules allow for
a redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The
required connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the
first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-41


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-39: Direct input and output dual-channel connection

Tx1

Rx1
UR 1
Tx2

Rx2

Tx1

Rx1
UR 2
Tx2

Rx2

3 Tx1

Rx1
UR 3
Tx2

Rx2

Tx1

Rx1
UR 4
Tx2

Rx2
842007A3.CDR

The following figure shows the connection for three UR-series relays using two independent communication channels. UR1
and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication channels
can be of different types, depending on the type 7 modules used. To allow the direct input and output data to cross-over
from channel 1 to channel 2 on UR2, set the DIRECT I/O CHANNEL CROSSOVER setting to “Enabled” on UR2. This forces UR2 to
forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.
Figure 3-40: Direct input and output single/dual channel combination connection

Tx
UR 1
Rx

Channel 1

Tx1

Rx1
UR 2
Tx2

Rx2

Channel 2

Tx
UR 3
Rx
842013A2.CDR

The inter-relay communications modules are available with several interfaces and some are outlined here in more detail.
Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the
Order Code tables in Chapter 2. All of the fiber modules use ST type connectors.

3-42 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

3.4.2 Fiber: LED and ELED transmitters


The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
Figure 3-41: LED and ELED fiber modules
7A, 7B, and 7H, 7I, and
7C modules 7J modules

Rx1 Rx1

Tx1 Tx1

3
Rx2

Tx2

1 channel 2 channels
831719A3.CDR

3.4.3 Fiber laser transmitters


The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules.
Figure 3-42: 7x Laser fiber modules
72 and 7D 73 and 7K
modules modules

Tx1 Tx1

Rx1 Rx1

Tx2

Rx2

1 channel 2 channels
831720A5.CDR

The following figure shows configuration for the 2I and 2J fiber-laser modules.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-43


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-43: 2I and 2J laser fiber modules


2I and 2J
modules

Rx1

Tx1

Rx2

3 Tx2

2 channels
831827A1.CDR

Observing any fiber transmitter output can injure the eye.

When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.

3.4.4 G.703 interface

3.4.4.1 Description
G.703 is an International Telecommunications Union (ITU) standard for the transmission of data and voice signals. Modules
7R (one channel) and 7S (two channels) apply.
The following figure shows the 64K ITU G.703 co-directional interface configuration. This is module 7S.
The G.703 module is fixed at 64 kbps. The SETTINGS  PRODUCT SETUP  DIRECT I/O  DIRECT I/O DATA RATE setting is not
applicable to this module.
AWG 24 twisted shielded pair wiring is recommended for external connections, with the shield grounded only at one end.
Connecting the shield to pin X1a or X6a grounds the shield since these pins are connected internally to ground. Thus, if
pin X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is
protected by surge suppression devices.
Figure 3-44: G.703 interface configuration
Shield ~1a
7S

Tx – ~1b
G.703 Rx – ~2a
channel 1
Tx + ~2b
Rx + ~3a
G.703 communications

Surge ~3b
Shield ~6a
Tx – ~6b
G.703 Rx – ~7a
channel 2
Tx + ~7b
Rx + ~8a
Surge ~8b
842773A3.CDR

3-44 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical
arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3-45: Typical pin interconnection between two G.703 interfaces

Shield X1a X1a Shield

7S

7S
Tx – X1b X1b Tx –
G.703 Rx – X2a X2a Rx – G.703
channel 1 channel 1
Tx + X2b X2b Tx +
Rx + X3a X3a Rx +
G.703 communications

G.703 communications
Surge X3b X3b Surge
Shield X6a X6a Shield
Tx – X6b X6b Tx –
G.703 Rx – X7a X7a Rx – G.703
channel 2 channel 2

3
Tx + X7b X7b Tx +
Rx + X8a X8a Rx +
Surge X8b X8b Surge
831727A5.CDR

Pin nomenclature differs from one manufacturer to another. It is not uncommon to see pinouts numbered TxA, TxB,
RxA, and RxB. In such cases, assume that “A” is equivalent to “+” and “B” is equivalent to “–.”

3.4.4.2 G.703 selection switch procedures


1. With the power to the relay off, remove the G.703 module (7R or 7S) as follows. Record the original location of the
module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release
the module for removal. (For more information on accessing modules, see the Maintenance chapter.)
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes.
6. Replace the top cover and the cover screw.
7. Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and bottom of each module must be in the disengaged position as the
module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips
simultaneously. When the clips have locked into position, the module is inserted fully.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-45


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-46: G.703 timing selection switch setting


Bottom cover

Ejector/inserter clip

FRONT

Channel 1

Timing selection
switches

Top cover

3
Channel 2

Cover screw
Ejector/inserter clip

REAR
831774A3.CDR

Table 3-6: G.703 timing selections


Switches Function
S1 OFF → octet timing disabled
ON → octet timing 8 kHz
S5 and S6 S5 = OFF and S6 = OFF → loop timing mode
S5 = ON and S6 = OFF → internal timing mode
S5 = OFF and S6 = ON → minimum remote loopback mode
S5 = ON and S6 = ON → dual loopback mode

3.4.4.3 G.703 octet timing


If octet timing is enabled (ON), this 8 kHz signal is asserted during the violation of bit 8 (LSB) necessary for connecting to
higher order systems. When F60s are connected back-to-back, octet timing is disabled (OFF).

3.4.4.4 G.703 timing modes


There are two timing modes for the G.703 module: internal timing mode and loop timing mode (default).
• Internal Timing Mode — The system clock is generated internally. Therefore, set the G.703 timing selection to internal
timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set octet timing (S1 = OFF) and
timing mode to internal timing (S5 = ON and S6 = OFF).
• Loop Timing Mode — The system clock is derived from the received line signal. Therefore, set the G.703 timing
selection to loop timing mode for connections to higher order systems. For connection to a higher order system (UR-
to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 =
OFF).
The switch settings for the internal and loop timing modes are shown.

3-46 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

Figure 3-47: Switches


Loop timing mode
Internal timing mode (factory default)

842752A2.CDR

3.4.4.5 G.703 test modes


In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any
processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs,
passes through the data stabilization latch that also restores the proper signal polarity, passes through the multiplexer,
and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module
3
after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and
passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is
expected to be from the G.703 line side of the interface.
Figure 3-48: G.703 minimum remote loopback mode

'05 'LIIHUHQWLDO0DQFKHVWHUUHFHLYHU
'05 *; '0; 'LIIHUHQWLDO0DQFKHVWHUWUDQVPLWWHU
*; *WUDQVPLWWHU
*5 *UHFHLYHU

'0; *5

$&'5

In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing.
One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the
interface.
Figure 3-49: G.703 dual loopback mode

'05 'LIIHUHQWLDO0DQFKHVWHUUHFHLYHU
'05 *; '0; 'LIIHUHQWLDO0DQFKHVWHUWUDQVPLWWHU
*; *WUDQVPLWWHU
*5 *UHFHLYHU

'0; *5

$&'5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-47


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

3.4.5 RS422 interface

3.4.5.1 Description
There are two RS422 inter-relay communications modules available: single-channel (module 7T) and dual-channel (module
7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 20 to 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are connected internally to the ground pin (8a). Proper shield termination is as follows:
• Site 1 — Terminate shield to pins 6a or 7b or both
• Site 2 — Terminate shield to COM pin 2b
Match the clock terminating impedance with the impedance of the line.
Figure 3-50: RS422 interface connections
3 Single-channel RS422 module Dual-channel RS422 module

7W
Tx – ~3b Tx – ~3b
7T

Rx – ~3a Rx – ~3a
RS422 communications

RS422 Tx + ~2a RS422 Tx + ~2a


channel 1 channel 1
Rx + ~4b Rx + ~4b
Shield ~6a Shield ~6a
+ ~7a Tx – ~5b
Clock
– ~8b Rx – ~5a
RS422 communications
Common COM ~2b RS422 Tx + ~4a
channel 2
Surge ~8a Rx + ~6b
Shield ~7b
Tx – ~7a
Clock
Rx – ~8b
Common COM ~2b
~ indicates the slot position Surge ~8a
842776A3.CDR

The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
Figure 3-51: Typical pin interconnect between two RS422 interfaces

7[² :E :E 7[²


7

7

5[² :D :D 5[²


56FRPPXQLFDWLRQV

56FRPPXQLFDWLRQV

56 7[ :D :D 7[ 56


FKDQQHO FKDQQHO
5[ :E :E 5[
6KLHOG :D :D 6KLHOG
 :D :D 
&ORFN &ORFN
² :E :E ²
&RPPRQ &20 :E :E &20 &RPPRQ
6XUJH :D :D 6XUJH
 ²

RUNESV
$&'5

3.4.5.2 Two-channel application via multiplexers


The RS422 interface can be used for single-channel or two-channel applications over SONET/SDH or multiplexed systems.
When used in single-channel applications, the RS422 interface links to higher-order systems in a typical way, observing
transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications, certain
criteria must be followed since there is one clock input for the two RS422 channels. The system functions correctly when
the following connections are observed and your data module has a terminal timing feature. Terminal timing is a common
feature in most synchronous data units that allows the module to accept timing from an external source. Using the
terminal timing feature, two-channel applications can be achieved if these connections are followed: the send timing

3-48 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

outputs from the multiplexer (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In
addition, the send timing outputs of data module 1 are also paralleled to the terminal timing inputs of data module 2. By
using this configuration, the timing for both data modules and both UR RS422 channels is derived from a single clock
source. As a result, data sampling for both of the UR RS422 channels is synchronized via the send timing leads on data
module 1, shown as follows. If the terminal timing feature is not available or this type of connection is not wanted, the
G.703 interface is a viable option that does not impose timing restrictions.
Figure 3-52: Timing configuration for RS422 two-channel, three-terminal application
'DWDPRGXOH
6LJQDOQDPH
7[  :D 6' $ 6HQGGDWD
:

7[ ² :E 6' % 6HQGGDWD


56
5[  :E 5' $ 5HFHLYHGGDWD
&+$11(/
5[ ² :D 5' % 5HFHLYHGGDWD
6KLHOG

:D
:D
56 $ 5HTXHVWWRVHQG 576
56 % 5HTXHVWWRVHQG 576
3
&/2&.
² :E 57 $ 5HFHLYHWLPLQJ
56&20081,&$7,216

7[  :D 57 % 5HFHLYHWLPLQJ


7[ ² :E &6 $ &OHDU7RVHQG
56
5[  :E &6 % &OHDU7RVHQG
&+$11(/
5[ ² :D /RFDOORRSEDFN
6KLHOG :E 5HPRWHORRSEDFN
&20021 &20 :E 6LJQDOJURXQG
685*( :D 67 $ 6HQGWLPLQJ
67 % 6HQGWLPLQJ

'DWDPRGXOH
6LJQDOQDPH
77 $ 7HUPLQDOWLPLQJ
77 % 7HUPLQDOWLPLQJ
6' $ 6HQGGDWD
6' % 6HQGGDWD
5' $ 5HFHLYHGGDWD
5' % 5HFHLYHGGDWD
56 $ 5HTXHVWWRVHQG 576
56 % 5HTXHVWWRVHQG 576
&6 $ &OHDU7RVHQG
&6 % &OHDU7RVHQG
/RFDOORRSEDFN
5HPRWHORRSEDFN
6LJQDOJURXQG
67 $ 6HQGWLPLQJ
67 % 6HQGWLPLQJ
$&'5

Data module 1 provides timing to the F60 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure because they vary by manufacturer.

3.4.5.3 Transmit timing


The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is
important to confirm clock and data transitions to ensure proper system operation. For example, the following figure
shows the positive edge of the Tx clock in the center of the Tx data bit.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-49


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-53: Clock and data transitions

7[FORFN

7[GDWD

$&'5

3.4.5.4 Receive timing


The RS422 interface utilizes NRZI-MARK modulation code and therefore does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
To recover the Rx clock from the data-stream, an integrated digital phase lock loop (DPLL) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the serial communication controller (SCC) receive clock.

3.4.6 RS422 and fiber interface


The following figure shows the combined RS422 plus fiberoptic interface configuration at 64 K baud. The 7L, 7M, 7N, 7P,
and 74 modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is
employed via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 20 to 24 twisted shielded pair wiring is recommended for external RS422 connections. Ground the shield only at one
end. For the direct fiber channel, address power budget issues properly.

When using a laser interface, attenuators can be necessary to ensure that you do not exceed
maximum optical input power to the receiver.
Figure 3-54: RS422 and fiber interface connection

+ ~1a
7L, 7M, 7N,
7P, and 74

Clock
channel 1 – ~1b
Common COM ~2b
Tx – ~3b
Rx – ~3a
RS422 Tx + ~2a
channel 1
communications

Rx + ~4b
Shield ~6a
Fiber Tx2 Rx2
RS422

channel 2
Surge ~8a
842777A3.CDR

The connections shown in the figure are for multiplexers configured as data communications equipment (DCE) units.

3-50 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

3.4.7 G.703 and fiber interface


The following figure shows the combined G.703 plus fiber-optic interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and
75 modules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer)
and channel 2 via direct fiber. AWG 24 twisted shielded pair wiring is recommended for external G.703 connections
connecting the shield to pin 1a at one end only. For the direct fiber channel, address power budget issues properly. See
previous sections for details on the G.703 and fiber interfaces.

When using a laser interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
Figure 3-55: G.703 and fiber interface connection
Shield ~1a

75, 7E, 7F, 7G,


and 7Q
3
Tx – ~1b
G.703 Rx – ~2a
channel 1
Tx + ~2b

communications
Rx + ~3a
Surge ~3b

Fiber Tx2
G.703

channel 2 Rx2

842778A2.CDR

3.4.8 IEEE C37.94 interface


IEEE C37.94 is a standard interface between teleprotection equipment and digital multiplexers.
The UR-series IEEE C37.94 modules (module types 2G, 2H, 2I, 2J, 76, and 77) are designed to interface with IEEE C37.94
compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and output
applications. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a multiplexer
and a teleprotection device. Data speed is typically 64 kbps, but the standard provides for speeds up to 64n kbps, where n
= 1, 2,…, 12. The UR-series C37.94 communication modules are either 64 kbps (with n fixed at 1) or 128 kbps (with n fixed at
2). The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from the standpoint
of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048
kbps.
The specifications for the module are as follows:
• IEEE standard — C37.94 for 1 × 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 × 64 kbps
optical fiber interface (for 76 and 77 modules)
• Fiber-optic cable type — 50 nm or 62.5 μm core diameter optical fiber
• Fiber-optic mode — multimode
• Fiber-optic cable length — up to 2 km
• Fiber-optic connector — type ST
• Wavelength — 820 ±40 nm
• Connection — as per all fiber-optic connections, a Tx-to-Rx connection is required
The UR-series C37.94 module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94
standard. The figure shows the concept.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-51


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-56: IEEE C37.94 connection to compliant digital multiplexer


IEEE C37.94
fiber interface

Digital
UR-series multiplexer,
device IEEE C37.94
compliant

up to 2 km

842755A2.CDR

The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a non-
compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard. The
following figure shows the concept.

3 Figure 3-57: IEEE C37.94 connection to non-compliant digital multiplexer

IEEE C37.94 RS422


fiber interface interface
Digital
UR-series IEEE C37.94 multiplexer
device converter with EIA-422
interface
up to 2 km

842756A2.CDR

In 2008, GE Grid Solutions released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" or "Rev E" printed on it and is to be used on all ends of F60
communication for two and three terminal applications. Failure to use it at all ends results in intermittent communication
alarms. For customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94 communication module has six switches to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-58: Switches
Loop timing mode
Internal timing mode (factory default)

842753A2.CDR

For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher order systems.
To remove the IEEE C37.94 communications module cover and set the switches:
1. With power to the relay off, remove the IEEE C37.94 module (type 2G, 2H, 2I, 2J, 76, or 77 module) as follows. Record
the original location of the module to help ensure that the same or replacement module is inserted into the correct
slot.
2. Simultaneously pull the ejector/inserter clips located at the top and bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.

3-52 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
6. Replace the top cover and the cover screw.
7. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Figure 3-59: IEEE C37.94 timing selection switch setting
Bottom cover

Ejector/inserter clip

FRONT 3
Channel 1

Timing selection
switches

Top cover

Channel 2

Cover screw
Ejector/inserter clip

REAR
831774A3.CDR

Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-53


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

Figure 3-60: Status LEDs

^|:
&+/LQN$FWLYLW\/('
&2006
\|:
%
M<@B=]W
:<88rqwmrkpiqshi
OVON
;glerrip
^|:

^|;
\O`N &+/LQN$FWLYLW\/('
^iglrmgepwyttsvx

3
^ip0B8>1;B=?;;;
Pe|0B8>1;8:;8BA \|;
0XY\^RKWO\SMK1
:A88>=@A?;B

QOWypxmpmr

WehimrMerehe ^|;

&+&ORFN&RQILJXUDWLRQ/('
&+&ORFN&RQILJXUDWLRQ/('

)52179,(: 5($59,(: $FGU

The clock configuration LED status is as follows:


• Flashing green — loop timing mode while receiving a valid data packet
• Flashing yellow — internal mode while receiving a valid data packet
• Solid red — (switch to) internal timing mode while not receiving a valid data packet
The link/activity LED status is as follows:
• Flashing green — FPGA is receiving a valid data packet
• Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit"
• Solid red — FPGA is not receiving a valid packet or the packet received is invalid

3.4.9 C37.94SM interface


The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94
compliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-
mode fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link
for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard
provides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid ITU-recommended G.704 pattern from the standpoint of framing and data rate. The
frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps.
The specifications for the module are as follows:
• Emulated IEEE standard — Emulates C37.94 for 1 × 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps)
• Fiber-optic cable type — 9/125 μm core diameter optical fiber
• Fiber-optic mode — Single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver
• Fiber-optic cable length — Up to 11.4 km
• Fiber-optic connector — Type ST
• Wavelength — 1300 ±40 nm
• Connection — As per all fiber-optic connections, a Tx-to-Rx connection is required

3-54 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION DIRECT INPUT AND OUTPUT COMMUNICATIONS

The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that
supports C37.94SM, as shown.

C37.94SM
fiber interface

Digital
UR-series
multiplexer
device
C97.94SM

up to 10 km

842757A2.CDR

It also can be connected directly to any other UR-series relay with a C37.94SM module, as shown.

C37.94SM
fiber interface 3
UR-series UR-series
device with device with
C37.94SM C37.94SM
module module
up to 10 km

842758A2.CDR

In 2008, GE Grid Solutions released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of F60 communication for
two and three terminal applications. Failure to use it at all ends results in intermittent communication alarms. For
customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94SM module has six switches that are used to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-61: Switches

Loop timing mode


Internal timing mode (factory default)

842753A2.CDR

For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher-order systems.
To remove the C37.94SM communications module cover and set the switches:
1. With power to the relay off, remove the C37.94SM module (module 2A or 2B) as follows. Record the original location of
the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release
the module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-55


DIRECT INPUT AND OUTPUT COMMUNICATIONS CHAPTER 3: INSTALLATION

6. Replace the top cover and the cover screw.


7. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Figure 3-62: C37.94SM timing selection switch setting
Bottom cover

Ejector/inserter clip

FRONT

3 Channel 1

Timing selection
switches

Top cover

Channel 2

Cover screw
Ejector/inserter clip

REAR
831774A3.CDR

Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.

3-56 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ACTIVATE RELAY

Figure 3-63: Status LEDs

^|:
&+/LQN$FWLYLW\/('
&2006
\|:
%
M<@B=]W
:<88rqwmrkpiqshi
OVON
;glerrip
^|:

^|;
\O`N &+/LQN$FWLYLW\/('
^iglrmgepwyttsvx
^ip0B8>1;B=?;;;
Pe|0B8>1;8:;8BA
0XY\^RKWO\SMK1
:A88>=@A?;B
\|;
3
QOWypxmpmr

WehimrMerehe ^|;

&+&ORFN&RQILJXUDWLRQ/('
&+&ORFN&RQILJXUDWLRQ/('

)52179,(: 5($59,(: $FGU

The clock configuration LED status is as follows:


• Flashing green — loop timing mode while receiving a valid data packet
• Flashing yellow — internal mode while receiving a valid data packet
• Solid red — (switch to) internal timing mode while not receiving a valid data packet
The link/activity LED status is as follows:
• Flashing green — FPGA is receiving a valid data packet
• Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit"
• Solid red — FPGA is not receiving a valid packet or the packet received is invalid

3.5 Activate relay


The relay is in the default “Not Programmed” state when it leaves the factory. When powered up successfully, looking at
the front panel, the "Trouble" LED is on and the "In Service" LED is off. The relay in the “Not Programmed” state blocks
signaling of any output relay. These conditions remain until the relay is explicitly put into “Programmed” state.

RELAY SETTINGS: When the relay is powered up, the "Trouble LED" is on, the "In Service" LED is off, and this message
Not Programmed displays, indicating that the relay is in the "Not Programmed" state and is safeguarding (output
relays blocked) against the installation of a relay whose settings have not been entered. This
message remains until the relay is explicitly put into "Programmed" state.

The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message displays.
2. Press the MESSAGE right arrow until the SECURITY message displays.
3. Press the MESSAGE down arrow until the INSTALLATION message displays.
4. Press the MESSAGE right arrow until the RELAY SETTINGS: Not Programmed message displays.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-57


INSTALL SOFTWARE CHAPTER 3: INSTALLATION

SETTINGS


 SETTINGS  SECURITY
 PRODUCT SETUP  

 DISPLAY
  PROPERTIES


 INSTALLATION RELAY SETTINGS:
   Not Programmed

3 5. After the RELAY SETTINGS: Not Programmed message displays, press a VALUE key to change the selection to
"Programmed."
6. Press the ENTER key to save the change.

RELAY SETTINGS: RELAY SETTINGS: NEW SETTING


Not Programmed Programmed HAS BEEN STORED

7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
To activate the relay using EnerVista software:
1. Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2. Save the change.

3.6 Install software


3.6.1 EnerVista communication overview
The EnerVista UR Setup software communicates to the relay via the front panel RS232 or USB port or the rear RS485 /
Ethernet ports.
To communicate via the RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to the relay
and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports section
earlier in this chapter.

3-58 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION INSTALL SOFTWARE

Figure 3-64: Relay communication options

Regional
control
center

Ethernet Remote
10/100 Mbps communications link
Local
control

UR-series IED
EnerVista Engineer

GE Multilin F485
communications converter
Modem
3
RS485 115 kbps

RS232

EnerVista
Reports

EnerVista

Troubleshooting
Commissioning
Setting changes

842759A2.CDR

To communicate through the F60 rear RS485 port from a computer RS232 port, the GE Grid Solutions RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair wire (20, 22, or 24 AWG) connects the F485 converter to the F60 rear communications port.
The converter terminals (+, –, GND) are connected to the F60 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 Ω, 1 nF) as
described in this chapter.

3.6.2 System requirements


The relay front panel or the EnerVista UR Setup software can be used to communicate with the relay. The software
interface is the preferred method to edit settings and view actual values because the computer monitor can display more
information.
The system requirements for the EnerVista software are as follows:
• Intel Pentium processor (dual core) or (recommended) Core Duo
• One of the following operating systems in the required EnerVista language, such as English or French:
– Windows 7 with Service Pack 1 (32-bit or 64-bit)
– Windows 10
– Windows Server 2008 Release 2 with Service Pack 1 (64-bit)
– Windows Server 2012 Release 2 (64-bit)
– Windows Server 2016
• 1 GB free hard drive space

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-59


INSTALL SOFTWARE CHAPTER 3: INSTALLATION

• 2 GB RAM
• 1280 x 800 display screen

3.6.3 Install software


After ensuring that the requirements for using EnerVista UR Setup software are met, there are three ways to install the
software:
• From the DVD
• Download EnerVista Launchpad software from http://www.gegridsolutions.com/multilin and install it
• Download the EnerVista UR Setup software from http://www.gegridsolutions.com/multilin and install it
Install on a computer that has an operating system in the required language, for example a German operating system for
use with EnerVista software in German.
3 Unless specifically granted, the software can be installed on one computer and used by one user.

The front panel can be switched in the EnerVista software between enhanced and basic panels under
Maintenance > Change Front Panel.

When installing on a computer with Windows Server 2012, its Release 2 needs the KB2919355 update first. Follow the
instructions described in the link, which works in Internet Explorer, not Chrome.
https://www.microsoft.com/en-US/download/details.aspx?id=42334

To install the software from the DVD and using EnerVista Launchpad:
1. Insert the DVD into the DVD drive of your computer.
2. Click the Install Now button and follow the instructions.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
Figure 3-65: Adding a UR device in Launchpad window

5. In the EnerVista Launch Pad window, click the Add Product button and select the appropriate product as follows.
Select the Web option to ensure the most recent software release, or select CD if you do not have an Internet
connection, then click the Add Now button to list software items for the product. EnerVista Launchpad obtains the
software from the Internet or DVD and automatically starts the installation program after prompting about updates.
From the web, the software is downloaded. A wizard opens.

3-60 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION INSTALL SOFTWARE

Figure 3-66: Identifying the UR device type

6. In the wizard, click the Next button and complete the process. The files are installed in the directory indicated, and the
installation program automatically creates icons and adds an entry to the Windows start menu.
The UR device is added to the EnerVista Launchpad window, as shown.
Figure 3-67: UR device added to Launchpad window

7. For other than English, configure the language for the front panel in the EnerVista software under Settings > Product
Setup > Display Properties. User-entered strings are not translated, for example relay names, so setting the language
now ensures that the names are entered/displayed in the required language. For the EnerVista software language,
access the View > Language menu item.

3.6.3.1 Install EGD software


Install Ethernet Global Data (EGD) software separately if required. Microsoft .NET Framework 4.5 or later is required.
1. Access the folder in which the UR software is installed, such as C:\Program Files (x86)\GE Power Management\URPC
2. Access the EGD Client Installer folder, double-click the .exe file, such as the EgdClient6101.exe file, and complete the
wizard.
The software installs. When Microsoft .NET Framework 4.5 or higher is not installed, it installs automatically version 4.5.
When an EGD device/client is connected to a UR, an Ethernet Global Data item displays in the UR EnerVista Setup
software.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-61


ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION

3.7 Add device to software


You connect remotely to the F60 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup
software. The F60 also can be accessed locally with a computer through the front panel RS232 or USB port or the rear
Ethernet port using the Quick Connect feature.
The following procedures are outlined:
• Add device for serial access; see the Configure Serial Connection section
• Add device for the rear Ethernet port; see the Configure Ethernet Connection section
• Add device for access using a modem; see the Configure Modem Connection section
• Connect locally with a computer through either the front RS232 or USB port or rear Ethernet port; see the Connect to
the F60 section
3 • Discover automatically UR devices within a network; see the Automatic Discovery of UR Devices section
Devices in the Device Setup window are listed in the order entered.
Devices in the main software window are listed alphabetically. Use the Device Name to order them as required, for
example B30 Odessa, B30 Truro, B90, T35.
You cannot import a file to add a device to the software. You can import settings as outlined at the end of the chapter.
The Quick Connect button also can be used to add devices. The device is added to a Quick Connect menu item in the
Online Window area, cannot be moved from it to another grouping, and needs to be renamed in the Device Setup window.
GE instead recommends using the Device Setup window to add devices, as outlined here.

3.7.1 Set IP address in UR


Implement IP addresses for the computer and a F60 device as follows.
The UR family supports the use of subnetworks as documented in RFC 950, which divides class-based networks into
subnetworks (non-CIDR). The classes and IP address ranges are defined as follows.
Table 3-7: IP address classes
Classes IP address range Default subnet mask address UR devices
A 1.0.0.0 to 127.255.255.255 255.0.0.0 65,535 or more
B 128.0.0.0 to 191.255.255.255 255.255.0.0 255 to 65,534
C 192.0.0.0 to 223.255.255.255 255.255.255.0 0 to 254
D 224.0.0.0 to 239.255.255.255 (Reserved for multicasting)
E 240.0.0.0 to 255.255.255.255 (Reserved)

Both network and subnet addresses are contained within a range. The number of hosts determines the class and
addresses as follows:
• Class A 255.0.0.0 — The first octet (255) specifies the network, the second to fourth octets (0) specify the subnet and
host. Use this class when you have more than 65,535 hosts (UR devices).
• Class B 255.255.0.0 — The first two octets (255) specify the network, the third octet (0) specifies the subnet, and the
fourth octet (0) specifies the host. Use this class when you have 255 to 65,534 hosts (UR devices).
• Class C 255.255.255.0 — The first three octets (255) specify the network and the last octet (0) specifies the subnet and
host. Use this class when you have up to 254 hosts (UR devices).
An example of implementation is one computer and one UR device. Because there is one UR device, class C addressing is
required. So we use UR 192.167.2.x with subnet mask 255.255.255.0 and computer 192.167.3.x with subnet mask
255.255.255.0.
For older, non-CIDR routing protocols, such as RIP version 1, follow these restrictions:
• Identical subnet masks — Use a single mask for all subnets within a network

3-62 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE

• Contiguous subnets — The subnets must be contiguous and not split among networks. The subnets cannot pass
traffic through other networks.

The IP and subnet addresses need to be added to the UR for Ethernet communication.
For serial communication, for example using any front RS232 port and the Quick Connect feature, the addresses are not
required, but typically they are entered to add/configure devices for regular use.
To add the IP addresses:
1. On the front of the UR, press the MENU key until the SETTINGS menu displays.
2. Navigate to one of the ports under SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK  NETWORK PORT
 PRT IP ADDRESS.
3. Enter an IP address, for example 10.11.33.01, and press the ENTER key to save the value. For example, press the period

4.
key to clear any existing address, then press the number keys to add a new address.
In the same menu, select the PRT SUBNET IP MASK setting. Enter a subnet IP address, for example 255.000.000.000 for
3
255.0.0.0. Press the ENTER key to save the value.
5. When connecting through an Ethernet network, also configure the gateway address under SETTINGS  PRODUCT
SETUP  COMMUNICATIONS  IPv4 ROUTE TABLE  DEFAULT IPv4 ROUTE  GATEWAY ADDRESS. Press the ENTER key to
save the value.
If using a blue or grey Ethernet cable, skip the rest of the this section. If using an orange cross-over Ethernet cable, the
computer needs to be set up as follows.
1. Use an orange Ethernet cross-over cable to connect the computer to the rear Ethernet port. In case you need it, the
following figure shows the pinout for an Ethernet cross-over cable.
Figure 3-68: Ethernet cross-over cable PIN layout

3 4 5 6
END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8 1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR

Next, assign the computer an IP address compatible with the relay’s IP address.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-63


ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION

2. Right-click the Local Area Connection icon and select Properties.

3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.

4. Click the “Use the following IP address” box.


5. Enter an IP address with the first three numbers the same as the IP address of the F60 relay and the last number
different (in this example, 1.1.1.2).
6. Enter a subnet mask equal to the one set in the F60 (in this example, 255.0.0.0).
7. Click the OK button to save the values.

3-64 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE

Before continuing, test the Ethernet connection.


1. Open a Windows console window, for example by selecting Start > Run from the Windows Start menu and typing
“cmd” or clicking the Start button and entering "cmd".
2. Type the following command, substituting the IP address of 1.1.1.1 with yours:
C:\WINNT>ping 1.1.1.1
3. If the connection is successful, the system returns four replies similar to the following:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms 3
Note that the values for time and TTL vary depending on local network configuration.
4. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the F60 and the computer, and double-check the programmed IP address in
the PRODUCT SETUP  COMMUNICATIONS  NETWORK  IP ADDRESS setting, then repeat step 2.
5. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the F60 and the computer, and double-check the programmed IP address in
the PRODUCT SETUP  COMMUNICATIONS  NETWORK  IP ADDRESS setting, then repeat step 2.
6. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Destination host unreachable.
Destination host unreachable.
Destination host unreachable.
Destination host unreachable.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the IP address is programmed in the local computer by entering the ipconfig command in the command
window.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-65


ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION

C:\WINNT>ipconfig
Windows IP Configuration
Ethernet adapter <F4FE223E-5EB6-4BFB-9E34-1BD7BE7F59FF>:
Connection-specific DNS suffix. . :
IP Address. . . . . . . . . . . . : 0.0.0.0
Subnet Mask . . . . . . . . . . . : 0.0.0.0
Default Gateway . . . . . . . . . :
Ethernet adapter Local Area Connection:
Connection-specific DNS suffix . :
IP Address. . . . . . . . . . . . : 1.1.1.2
Subnet Mask . . . . . . . . . . . : 255.0.0.0
Default Gateway . . . . . . . . . :
C:\WINNT>

Before using the Quick Connect feature through the Ethernet port, disable any configured proxy settings in Internet
3 Explorer.
1. Start the Internet Explorer software.
2. Select the Tools > Internet Options menu item and click the Connections tab.
3. Click on the LAN Settings button to open the following window.

4. Ensure that the “Use a proxy server for your LAN” box is not checked.

If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F60 relay.
1. Start the Internet Explorer software.
2. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.

3-66 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE

3. Click the Quick Connect button to open the window.

4. Select the Ethernet interface and enter the IP address assigned to the F60, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them on the left side of the screen.
5. Expand the sections to view data directly from the F60 device.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model
number.

When direct communications with the F60 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-67


ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION

If the computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F60 relay.

3.7.2 Configure serial connection


Two options are possible: local connection between computer and front RS232 port, and remote connection using the rear
RS485 terminals.
If using Windows 10 and a GE USB-to-Serial Cable Converter (part number 0100-0001) connected between a USB port on
the computer and the front serial port on the UR, use the Prolific driver version 3.2.0.0 from the Internet.
To use the RS485 terminals at the back of the relay, a GE Grid Solutions F485 converter (or compatible RS232-to-RS485
converter) is required. See the F485 instruction manual for details.
1. Connect the computer to the F485 and the F485 to the RS485 terminal on the back of the UR device. Or connect the
3 2.
computer to the RS232 port on the front of the relay.
Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Device Setup button. The window opens.
4. Click the Add Site button. A new category is added. Enter a site name in the Site Name field. Optionally add a short
Description of the site. This example uses “Location 1” as the site name.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 16 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Serial” from the Interface drop-down list. Interface parameters display that must be entered for serial
communications. Try to load automatically the fields by clicking the Read Order Code button.
Figure 3-69: Configuring serial communication

3-68 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE

8. Enter the COM port used by the computer, the baud rate, and parity settings from the front panel SETTINGS  PRODUCT
SETUP  COMMUNICATIONS  SERIAL PORTS menu, and the relay slave address setting from the front panel SETTINGS
 PRODUCT SETUP  COMMUNICATIONS  MODBUS PROTOCOL  MODBUS SLAVE ADDRESS menu in their respective
fields.
Baud Rate — Typically 19200 bits per second (bps) for RS232, and higher for RS485. Both modems need to use the
same rate, meaning at the computer and the F60 ends.
Parity — Set to None if unsure
Bits — Set to 8 if unsure
Stop Bits — Set to 1 if unsure
Post Terminal Window — Enable this option if you have a Schweitzer Engineering (SEL) SEL-203x Communications
Processor, such as an SEL-2030 or SEL-2032. This option enables display of a terminal window to allow interaction
with the other device.
9. Click the Read Order Code button to connect to the F60 and upload the order code to the EnerVista software. If a
communications error occurs, ensure that the EnerVista software serial communications values entered in the
3
previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to
multiple F60 ports.
10. Click the OK button when the relay order code has been received. The new site and device are added to the Online
Window.
The device has been configured for serial communications. Proceed to the Connect to the F60 section to begin
communication.

3.7.3 Configure Ethernet connection


You connect the Ethernet cable, define a site in the software, then add the relay as a device for the site.
The Ethernet cable can be connected from the relay to an Ethernet network or directly to the computer. The computer and
UR device must be on the same subnet.
1. Connect the Ethernet network cable and any SFP supplied with the F60 to the Ethernet port on the CPU module at the
back of the device.
2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Device Setup button. The window opens.
4. Click the Add Site button. A new category is added. Enter a site name in the Site Name field. Optionally add a short
Description of the site. This example uses “Location 1” as the site name.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 16 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Ethernet” from the Interface drop-down list. This displays a number of interface parameters that must be
entered for Ethernet functionality.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-69


ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION

Figure 3-70: Configuring Ethernet communication

8. Enter the relay IP Address, which can be viewed on the device front panel under SETTINGS  PRODUCT SETUP 
COMMUNICATIONS  NETWORK  NETWORK PORT  PRT IP ADDRESS. Once the IP address is entered, try to load
automatically the fields by clicking the Read Order Code button.
9. Enter the relay Slave address and Modbus Port address values from the settings in the front panel SETTINGS 
PRODUCT SETUP  COMMUNICATIONS MODBUS PROTOCOL menu.
10. If using a gateway to connect to the device, select Yes from the drop-down list.
11. Click the Read Order Code button to connect to the F60 device and upload the order code. If the device was entered
already, a message displays "Device ’x’ is also using IP address...." If a communications error occurs, ensure that the
values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address
is not assigned to multiple F60 ports.
12. Click the OK button when the relay order code has been received. The new site and device are added to the Online
Window.
The device has been configured for Ethernet communications. Proceed to the Connect to the F60 section to begin
communications.

3.7.4 Configure modem connection


A modem connection allows a computer to communicate with a UR device over phone lines.
Two modems are required. One modem is connected to the UR device, either by connecting the serial cable to the front
panel port or through a RS485 box to the rear terminals of the UR device. The second modem is connected to the
computer that initiates the connection.
To add a UR device for modem connections:
1. Connect the modems to the computer and UR.

3-70 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE

2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Device Setup button. The window opens.
4. Click the Add Site button. A new category is added. Enter a site name in the Site Name field, such as London East.
Optionally add a short Description of the site, such as the address or intersection.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 16 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Modem” from the Interface drop-down list. This displays a number of interface parameters that must be
entered.
8. Select "Generic Modem" from the Modem Name drop-down list, then enter the Phone Number to dial to establish
communication with the remote modem.
Post Terminal Window — Enable this option if you have a Schweitzer Engineering (SEL) SEL-203x Communications
Processor, such as an SEL-2030 or SEL-2032. It enables display of a terminal window to allow interaction with the
other device.
3
9. Once the phone number is entered, try to load automatically the device information by clicking the Read Order Code
button.
10. Click the OK button when the relay order code has been received. The new device is added to the Online window.
The UR device has been added to the software.

3.7.5 Automatic discovery of UR devices


The EnerVista UR Setup software can find and communicate to all UR-family devices located on an Ethernet network.
Using the Discover button in the Device Setup window, a single click of the mouse triggers the software to detect any URs
located on the network. This is done by searching a range of IP addresses based on the subnet mask of the computer.
When a UR device is detected, the EnerVista UR Setup software proceeds to configure all settings and order code options
in the window. This feature allows the user to identify and interrogate all UR devices at a location.
Examples of address ranges are as follows:
• If the host has an IP address of 3.94.247.10 and its subnet mask is 255.255.252.0, then the host’s subnet is 3.94.244.0,
and the possible IP addresses in this subnet are
3.94.244.1 to 254
3.94.245.1 to 254
3.94.246.1 to 254
3.94.247.1 to 254
The discover function scans all those possible IP addresses to detect UR relays.
• If the host has an IP address of 3.94.247.145 and its subnet mask is 255.255.255.128, then the host’s subnet is
3.94.247.128, and the discover function scans IP addresses of 3.94.247.128 to 3.94.248.254 for UR relays
To automatically add UR devices:
1. In the EnerVista software, click the Device Setup button. The window opens.
2. Click the Discover button. The software searches for UR devices on the computer subnet and adds any found to the
Online Window area. If a required device is not found, add it manually as outlined earlier.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-71


CONNECT TO THE F60 CHAPTER 3: INSTALLATION

Figure 3-71: Discover button to detect UR devices in network

3 3.8 Connect to the F60


There are four ways to the connect to the device, as follows:
• RS232 or USB port (outlined here)
• RS485 port
• Ethernet port (outlined here)
• LAN
When unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for the
device.
When unable to connect, ensure that the same IP address is not assigned to multiple F60 ports, for example under
Settings > Product Setup > Communications > Network.
If still unable to connect, try unplugging and replugging the Ethernet connection. If that does not work, try to ping the
device from the computer, and if unsuccessful, restart the computer.

When multiple computers are connected to a F60 device, EnerVista settings windows are not updated
automatically. They are refreshed when re-opened. If a user changes a setting on one computer, the other users
need to refresh the display by closing and opening the settings window to see the change. To ensure that current
settings are always viewed, close settings windows when not in use so that they are up-to-date when next
accessed.

3.8.1 Connect to the F60 in EnerVista


For information on using the EnerVista software, see the Interfaces chapter.
To access the relay in EnerVista:
1. Open the Settings > Product Setup > Display Properties window as shown. The window opens with a status indicator
on the lower left of the EnerVista UR Setup window.

3-72 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION CONNECT TO THE F60

Figure 3-72: EnerVista window

Quick action hot links

3
Expand the site list by double-clicking
or selecting the +/– box.

Communications status indicators:


Green = OK
Red = No communications
UR icon = report is open

842743A3.CDR

2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly set up for communication.
3. If a relay icon appears in place of the status indicator, then a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be viewed, edited, or printed.

3.8.1.1 Quick action hot links


The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are
performed often when using URs. From the online window, users can select the relay to interrogate from a pull-down
window, then click the button for the action to perform. The following quick action functions are available:
• View the event record
• View the last recorded oscillography record
• View the F60 protection summary
• View all of the F60 metering values
• View the status of all F60 inputs and outputs
• Generate a service report

3.8.2 Use Quick Connect via front RS232 port


This feature applies to the enhanced and basic front panels.
To connect to the UR from a computer using a serial cable:
1. Connect an RS232 serial cable to the computer and the front panel RS232 port. For example, use a USB-to-serial
RS232 DB9M converter cable when connecting to the USB port on the computer. If using Windows 10 and a GE USB-
to-Serial Cable Converter (part number 0100-0001) connected between a USB port on the computer and the front
serial port on the UR, use the Prolific driver version 3.2.0.0 from the Internet.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-73


CONNECT TO THE F60 CHAPTER 3: INSTALLATION

2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Quick Connect button. The window opens.
Figure 3-73: Quick Connect window to access a device

3
4. Select the serial Interface and the communications port (COM Port) from the drop-down lists, then click Connect. The
COM Port is that of the computer.
5. The EnerVista software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them in the Online Window. Expand the sections to view data directly from the UR device. Use
the Device Setup button to change the site name.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model
number.

3.8.3 Use Quick Connect via front USB port


This feature applies to the graphical front panel.
To connect to the UR from a computer using a USB cable:
1. Connect the cable to the computer and the front panel USB port (square connector).
2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Quick Connect button to open the window.
4. Select the USB Interface and the "GE Virtual Serial Port" driver from the drop-down list, then click Connect. If the GE
driver does not display, it means that the USB cable was connected on Windows 10 when upgrading the UR software.
You need to re-install the EnerVista software with the USB cable disconnected.
5. The EnerVista software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them in the Online Window. Expand the sections to view data directly from the UR device. Use
the Device Setup button to change the site name.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model
number.

3.8.4 Use Quick Connect via a rear Ethernet port


To connect to a UR using an Ethernet cable:
1. In the EnerVista software, click the Quick Connect button. The window opens.

3-74 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD

Figure 3-74: Quick Connect window for Ethernet connection

2. Select the Ethernet interface and enter the IP address assigned to the F60, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3. Expand the sections to view data directly from the F60 device. Use the Device Setup button to change the site name.
Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to
the F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model number.

3.9 Set up CyberSentry and change default password


If and when first using CyberSentry security, use the following procedure for set up.
1. Log in to the relay as Administrator by using the VALUE keys on the front panel or through EnerVista connected serially
(so that no IP address is required). If logging in through EnerVista choose Device authentication (see figure). Enter the
default password "ChangeMe1#". Note that the LOCK SETTINGS setting needs to be disabled (default) in the SETTINGS 
PRODUCT SETUP  SECURITY  SUPERVISORY menu.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator, Observer,
or Administrator and Supervisor when Device authentication is disabled). When using a serial connection, only Device
authentication is supported. When Server authentication is required, characteristics for communication with a RADIUS
server must be configured on the UR. This is possible only through the EnerVista software. The RADIUS server itself also
must be configured. At the end of this instruction manual, the appendix called RADIUS Server Configuration gives an
example of how to set up a simple RADIUS server. Once both the RADIUS server and the parameters for connecting the UR
to the server have been configured, you can choose Server authentication on the login screen of EnerVista.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-75


IMPORT SETTINGS CHAPTER 3: INSTALLATION

Figure 3-75: Login screen for CyberSentry

3
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under Settings > Product Setup > Security > Supervisory. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista. If using EnerVista, navigate to
Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended
that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is
optional.

3.10 Import settings


Options are:
• Import settings from XML or CID file — Import all settings or a group of settings from an XML or CID file to a device in
the Offline Window area. Examples are Control elements, FlexLogic operands, and System Setup settings. This feature
uses a built-in import/export tool.
• Import settings from device files — Import a URS, IID, or CID file to a device in the Offline Window area.

3.10.1 import settings from XML file


All settings, groups of settings, and/or individual settings can be imported, such as System Setup, FlexLogic operands,
inputs/outputs, protection, and Control elements. A built-in import/export tool is used.
Note the following behavior:
• Available in English only
• Works in the Offline Window area
• Supports older firmware versions too, such as 6.x
• Import must be to same version, such as 8.03 to 8.03
• Except for B90, import can be to a different product, such as L90 to D60; order codes do not need to match
• Setting must exist in target device
• Complete single-line diagram can be imported, not parts of it
• Engineer function/menu item is not included
• Order codes must match when applying settings from the Offline Window area to a live device in the Online Window
area. For example, settings from a C30 in the Offline Window area cannot be applied directly to a live C60 device.

A B90 device can import settings only from a B90 device.

3-76 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION IMPORT SETTINGS

For information on exporting, see the Maintenance chapter.


Features in the tool include
• Ability to perform global import (Import All button), by current window (Import button), or individual setting (right-
click)
• Can import from a different dataset, such as from Dataset 3 to Dataset 2
• When a setting is not present in the target device, it cannot be selected/activated for the import device and the
Import button is inactive
• Use the search box at the top-left to locate setting names and values, highlighted in blue
• Use the Compare by Lines and Compare VOs drop-down lists to sort display of FlexLogic equations
• Use the Left Entry From / Left Entry To boxes to display select rows
• Enable the Synchronous Scrolling check box to lock scrolling for target and import devices


Add rows by right-clicking; validation is done later by the software
Use the Comparison Report button to view quickly all differences, whether saved or not
3
• Use the Target Device Report to view quickly the imported settings, whether saved or not
• Click the Save button to save imports, otherwise none are
The following procedures outline how to import settings, apply to a live device, compare settings, and view imported
settings.
To import settings:
1. In EnerVista, right-click the device in the Offline Window area and select the Import Settings option. A window opens.
If the device is not listed in the Offline Window area, right-click it in the Online Window area and select the Add Device
to Offline Window option.
2. Select the XML file to import, and click the Open button.
When the firmware versions differ, a message displays and the file cannot be imported.
When the firmware versions match, a window opens that compares existing and import settings. Existing settings are
on the left, and settings to be imported are on the right. The window for FlexLogic operands differs, allowing more
granularity.
When the order codes of the existing and imported setting files do not match, but both devices share the same
function(s), then the comparison list shows the common settings instead of all the settings. For example, the distance
protection function exists both in L90 and D60. The software allows importing L90 distance protection to D60
distance, and vice versa.
With successful launch, the device with the settings to be imported displays on the right, and the targeted device to
receive these settings is on the left. The differences are highlighted in orange. When check boxes are deselected on
the right side, it means that there are no differences or that settings are not present in the target device. (For a
summary, click the Comparison Report button at the top-right, as outlined in the next procedure.)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-77


IMPORT SETTINGS CHAPTER 3: INSTALLATION

Figure 3-76: Import settings window before clicking Import button

3. Review the settings, either in the main window or using the Comparison Report.
If required, deselect any settings on the right side that are no longer wanted for import.
If required, copy any setting in the import device by right-clicking the value, selecting the Copy option, and Pasting it
in the target setting field. Or select the Import option.
4. To filter FlexLogic operands, click the Compare by Lines / Compare VOs button to toggle.
Compare by Lines — Displays FlexLogic operands 1 to 1024.
Compare VOs — For virtual outputs, enable the check boxes of those wanted, for both the import and target devices.
5. To import the settings for the window currently active, click the Import button. Or to import all settings, click the
Import All button. The settings are imported, as shown in green.

3-78 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION IMPORT SETTINGS

Figure 3-77: Import settings window after clicking Import button

6. If required, to undo an import, click the Undo Import button. Or, to undo an import and to refresh all entries to their
original state, click the Restore button.
7. To save the changes, click the Save button and confirm at the prompt. Or to cancel all changes, click the Cancel
button. The window closes.

To apply the settings to a live device:


1. Drag-and-drop the device entry from the Offline Window area to an entry in the Online Window area. Individual
settings also can be dragged and dropped. The order codes must match.

To compare settings:
1. Click the Comparison Report button at the top-right of the window. This displays a summary of activity and includes
following settings: different, missing, imported, and invalid.
Number of Differences — The number of settings in the target device having setting values different from the import
device
Number of Missing Settings — The number of settings that are not found in the target device settings
Number of Settings Imported — The number of settings imported in the target device
Number of Invalid Settings — The number of settings that are same in both devices but the import device setting
value is not within range (out-of-range) of the target device setpoint range. For example, a 'FuncName Block' setting is
available in both import and target devices. The import device 'FuncName Block' setting is configured as '87L TRIP
OPIOC 1 OP,' however operand '87L TRIP OPIOC 1 OP' is not within the range of the target device.
2. To save the display as an HTML file, click the Save to File button.

To view imported settings on the target device:


1. Click the Target Device Report button at the top-right of the window.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-79


IMPORT SETTINGS CHAPTER 3: INSTALLATION

When no settings have been imported yet, the window shows basic information about the receiving device, such as
order code.
When settings have been imported, whether saved or not, a report displays. It is a comparison of the target device
before and after import.
For invalid settings for the target device, a message displays, they are highlighted in red in the main window, and they
are listed in red at the bottom of the window. This means that the target device does not have the feature and cannot
accept the settings. In the example shown, the device does not have bus functions, so the settings are invalid. Scroll
through the list to review the invalid settings. Note that the sets of invalid setting groups are highlighted in red on the
left side of the window (not shown).
Figure 3-78: Invalid settings on the target device in red

2. To save the display as an HTML file, click the Save to File button.

3.10.2 Import settings from device files


The following file types can be imported:
• URS — UR settings file (firmware version 7.3x or earlier)
• IID — Instantiated IED capability description file — Actual settings on UR
• CID — Configured IED description file — Settings sent to the UR (may or may not be actual settings). When using IEC
61850, network settings can also be configured by accepting a CID file that includes them, as long as the IP address of
at least one port is manually configured in the relay before the CID file is sent and the IP address matches that in the
file.
The import is done in the Offline Window area.
To import a settings file:
1. In the Offline Window area, right-click the device and select the Add Device from File option. The device is that from
which you want to import settings.
2. If required, change the Files of type drop-down list.
3. Select the file to import.

3-80 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 3: INSTALLATION CONNECT TO D400 GATEWAY

To apply the settings to a live device:


1. Drag-and-drop the device entry from the Offline Window area to its entry in the Online Window area. Individual
settings also can be dragged and dropped. The order codes must match.

This is what happens:


• CID — For version 7.30 or later, a new URS file generates and moves into a new device folder, generating SCL files from
the new URS file. Files in the folder have new time stamps. The CID file retains its time stamp.
• URS — When not IEC 61850 and version is lower than 7.30, the file is added and time stamp is unchanged. When
clicking in the software on the tree element, a device folder is created, the original file moves into it, and time stamp is
on the URS file is retained.
When EIC 61850 and version is 7.30 or later, the file is added and time stamp is unchanged. When clicking in the
software on the tree element, a device folder is created, the original file moves into it, SCL files are generated there,
and the "Last modified" time stamp on the URS file changes. 3

3.11 Connect to D400 gateway


A GE Multilin D400 Substation Gateway can be used to collect data from UR devices in a local area network (LAN). It collects
metering, status, event, and fault report data from serial or LAN-based intelligent substation devices, and it pre-processes
the data. The D400 supports up to 16 serial and eight network connections, with multiple devices possible on each serial
connection. Up to 10 concurrent file transfer sessions are possible, meaning data for up to 10 URs can be transferred at
the same time and any additional IEDs are queued on a first-come-first-served basis. The D400 can then upload files to a
demilitarized zone (DMZ) server at the enterprise level.
Setup is as follows. For UR devices with the CyberSentry software option, when there is a need to retrieve periodically the
logs from the UR securely without a human interface, the following approach can be used. See the D400 manual for
configuration details to achieve it.
A UR in the substation can authenticate a user either connecting to a RADIUS server or on the device itself. This depends
on the user name used for authentication on a connection. The D400 connects to the UR device using an Ethernet, USB, or
serial port on the UR. At the other end, the cable attaches to the rear of D400. Use the D400 software to configure a serial
or network communication/connection for the UR, then to configure the IED device blocks/clients for the UR, and then to
configure record retrieval. Once configured, the UR and D400 use a keyfile authentication mechanism to establish
communication.
For UR devices with the IEC 61850 software option, also use the D400 IEC 61850 Loader software.
When a D400 detects new files available for download from a UR, it connects to the UR and reads the files via Secure File
Transfer Protocol (SFTP) protocol. The following files can be transferred:
• Oscillography files
• Event records
• Log files
• Configuration (setting) files
The D400 information is viewable in its software and in a web browser.

3.11.1 Oscillography files


These are stored in COMTRADE format in the D400 folder system using the UR site and device name.

3.11.2 Event records


These are stored as the EVT.TXT file in the D400 folder system using the UR site and device name.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-81


CONNECT TO D400 GATEWAY CHAPTER 3: INSTALLATION

3.11.3 Log files


Log files can be retrieved for UR 7.0 and later. The following file types are possible, stored in the D400 folder system using
the UR site and device name:
• factory_event.txt — Information about change methods and origins. Saved with a "_YYMMDDhhmmss" retrieval time
stamp, for example FACTORY_EVENT_170525183124.TXT.
• setting_changes.log — Information on what settings have been changed. Saved with a "_YYMMDDhhmmss" retrieval
time stamp, for example SETTING_CHANGES_170525183124.TXT.

3.11.4 Setting files


These are the configuration/settings files in the IEC 61850 SCL/IID format. The ur.iid file is saved with a
"_YYMMDDhhmmss" retrieval time stamp, for example ur_170525183124.iid. It is stored in the D400 folder system using
3 the UR site and device name.

3-82 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 4: Interfaces

Interfaces

This chapter explains the EnerVista software interface, the front panel interface, logic diagrams, and Engineer interface for
logic design and monitoring.

4.1 EnerVista software interface


4.1.1 Introduction
The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and troubleshoot relays
connected over local or wide-area networks. It can be used while disconnected (offline) or connected (online) to a UR
device. In offline mode, settings files can be created for eventual downloading to the device. In online mode,
communication with the device is real-time.
The EnerVista UR Setup software is provided with every F60. This chapter outlines the EnerVista software interface. The
EnerVista UR Setup help file in the software also provides details for getting started and using the software interface.

4.1.2 Settings files


The EnerVista software supports the following three ways of handling changes to relay settings:
• In offline mode (relay disconnected) to create or edit relay settings files for later transfer to relays
• While connected to a relay to modify relay settings, and then save the settings to the relay
• Create/edit settings files and then write them to the relay while connected to the relay
See the back up section in the Maintenance chapter for instructions on how to create a settings file either offline or online.
Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the
following types of relay settings:
• Device definition
• Product setup
• System setup
• FlexLogic
• Grouped elements
• Control elements
• Inputs/outputs

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-1


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

• Remote resources
• Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the F60 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address (see end of previous chapter for information)
IP Subnet Mask
IP Routing
When a settings file is loaded to a F60 that is in-service, the following sequence occurs:
4 1. The F60 takes itself out of service.
2. The F60 issues a UNIT NOT PROGRAMMED major self-test error.
3. The F60 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.

4.1.3 Event viewing


In online or offline mode, you can view and analyze data generated by triggered parameters as follows:
• Event recorder — The event recorder captures contextual data associated with the last 1024 events, listed
chronologically from most recent to oldest
• Oscillography — The oscillography waveform traces and digital states are used to provide a visual display of power
system and relay operation data captured during specific triggered events
Event records are viewable at software and device-specific levels. Access the former under Admin > Event Log > View.
Access the latter under Actual Values > Records > Event Record.
Event record entries for CyberSentry are explained in the next chapter. The following table outlines some software-level
entries.
Table 4-1: Event record descriptions
Event Description
EnerVista UR Setup SESSION STARTED The EnerVista software was launched
Language was changed. The user changed the software language using the View > Language menu item
DEFAULT USERS CREATED The user management window was launched using the Admin > User Management menu
item
: Successful upload of firmware The firmware on a device was upgraded
END
Firmware verified
Firmware uploaded
Firmware erased
START: Upload new firmware
EnerVista UR Setup EVENT LOG CLEARED The event record was cleared. All event records were deleted using the Admin > Event Log >
Clear menu item.

4-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

4.1.4 File support


The following support applies, where the Settings List is at the bottom left and the Site List is at the top left of the EnerVista
window:
• Execution — Any EnerVista UR Setup file that is opened launches the application or provides focus to the already
opened application. If the file was a settings file (has a .urs extension) that had been removed from the Settings List
navigation menu, it is added back to the menu.
• Drag and Drop — The device settings and individual settings can be dragged and dropped between the Online and
Offline Window areas. Also, any Windows Explorer directory folder is a file drag source and drop target.
New files that are dropped into the Offline Window are added to the tree, which is automatically sorted alphabetically
with respect to settings file names. In the Online Window, files or individual menu items that are dropped in the
selected device menu are sent automatically to the online device.

4.1.5 EnerVista main window


The EnerVista UR Setup software window has the following components:
1. Title bar that shows the pathname of the active data view or the name of the software
2. Main window menu bar
3. Main window toolbar 4
4. Site list / online window area
5. Settings list / offline window area
6. Software windows, with common toolbar
7. Settings file data view windows, with common toolbar
8. Workspace area with data view tabs
9. Status bar
10. Quick action hot links

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-3


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-1: EnerVista UR Setup software window

2 1 6 7

10
4

4 5

9 8 842786A2.CDR

When the Offline Window has devices saved to it, it includes a Reserved entry with spare settings when customer-specific
functions are provided on a UR.

4-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

Figure 4-2: Reserved settings

4.1.6 Protection summary window


The Protection Summary is a graphical user interface to manage elements, such as enabling and disabling them. Access it
under Settings > Protection Summary. See the Settings chapter for information on use.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-5


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-3: Protection Summary interface (B30 example shown)

4.1.7 Settings templates


Settings file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An
example is a substation that has 10 similar feeders protected by 10 UR F60 relays.
In these situations, typically 90% or greater of the settings are identical among devices. The templates allow engineers to
configure and test these common settings, then lock them so that they are not available to users. For example, locked
settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate on specific settings.
The remaining settings (typically 10% or less) can be specified as editable and made available to field engineers installing
the devices. These are settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings are visible in the software. Settings templates can be
applied to both settings files (settings file templates) and online devices (online settings templates). The functionality is
identical for both purposes.

Template mode is available in the English software only.

Settings file conversion from previous firmware versions is supported.

4.1.7.1 Enable the settings template


The settings file template feature is disabled by default. It can be enabled in offline or online mode.
To enable in offline mode the settings template for UR settings files:
1. Locate the settings file in the Offline Window area of the EnerVista UR Setup software. If not there, a file can be added
from an online device by right-clicking it and selecting the Add Device to Offline Window option.
2. In the Offline Window area, right-click the selected device or settings file and select the Template Mode > Create
Template option.
The settings file template is now enabled and the file menus display in light blue. The settings file is now in template
editing mode. To undo the action, select Template Mode > Remove Template.

4-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

Alternatively, to apply the settings template to online settings:


1. Locate the device in the Online Window area of the EnerVista UR Setup software.
2. Right-click the device and select the Template Mode > Create Template option. The software prompts for a template
password. This password is required to use the template feature and must be at least four characters in length.
Figure 4-4: Entering a settings file password

3. Enter and re-enter the new password, then click OK to continue.


The online settings template is now enabled. The device is now in template editing mode.

4.1.7.2 Edit the settings template 4


The settings template editing feature allows the user to specify which settings are available for viewing and modification in
EnerVista UR Setup. By default, all settings except the FlexLogic equation editor settings are locked.
1. With the template already enabled, locate the device or settings file in the Online or Offline Window area in the
software.
2. Right-click the device or file and select the Template Mode > Edit Template option to verify or place the device in
template editing mode (check mark beside option). If prompted, enter the template password then click OK.
3. Open the relevant settings window that contains settings to be specified as viewable.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window indicates that the EnerVista software is in EDIT mode. The following example shows the phase
time overcurrent settings window in edit mode.
Figure 4-5: Settings template with all settings specified as locked

4. Specify the settings to make viewable by clicking them.


A setting available to view displays with a yellow background.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-7


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-6: Settings template with two settings specified as editable

5. Click the Save button to save changes to the settings template.


6. Continue through any other settings window to specify all viewable settings.
4 The next time that the device/settings are accessed, only those specified as viewable/editable display in the menu
hierarchy.

4.1.7.3 Add password protection to a template


GE recommends that templates be saved with password protection to maximize security.

When templates are created for online settings, the password is added during the initial template creation step. It
does not need to be added after the template is created.

To add password protection to a settings file template:


1. In the Offline Window area, right-click the device and select the Template Mode > Password Protect Template
option.
The software prompts for a template password. This password must be at least four characters in length.

2. Enter and re-enter the new password, then click OK to continue.


The settings file template is now secured with password protection.

4.1.7.4 View the settings template


Once all necessary settings are specified for viewing, users are able to view the settings template on the online device or
settings file. There are two ways to specify the settings view with the settings template feature:
• Display only those settings available for editing
• Display all settings, with settings not available for editing greyed-out
To display settings available for editing:
1. Right-click the device in the Online or Offline Window area and apply the template by selecting the Template Mode >

4-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

View In Template Mode option.


2. Enter the template password if prompted, then click OK to apply the template.
Once the template has been applied, users are limited to view and edit the settings specified by the template. The effect of
applying the template to the phase time overcurrent settings is shown.
Figure 4-7: Applying templates using the View in Template Mode command

4
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR

Viewing the settings in template mode also modifies the settings menu, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings menu is shown as follows.
Figure 4-8: Applying templates using the View in Template Mode settings command

To display settings available for editing and settings locked by the template:
1. Right-click the device in the Online or Offline Window area and apply the template by selecting the Template Mode >
View All Settings option.
2. Enter the template password then click OK to apply the template.
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown as follows.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-9


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-9: Applying templates using the View All Settings command

Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via

4
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR

4.1.7.5 Remove the settings template


Once a settings template is removed, it cannot be reapplied and a new settings template needs to be defined before use.
1. Right-click the device in the Online or Offline Window area and select the Template Mode > Remove Template option.
2. Enter the template password if prompted and click OK to continue.
3. Confirm that you want to remove the template by clicking Yes.
The EnerVista software removes all template information and all settings are available.

4.1.8 Secure and lock FlexLogic equations


The UR allows users to secure some or all FlexLogic equations, preventing unauthorized viewing or modification of critical
FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within FlexLogic
equations.
Secured FlexLogic equations remain secure when files are sent to and retrieved from any UR-series device.
Locking can be tied to the serial number too.

4.1.8.1 Lock FlexLogic equations


To lock individual entries of a FlexLogic equation:
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the
settings template feature.
2. If prompted, enter the template password.
3. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic entries are specified as viewable and display against a yellow background. The icon on the
upper right of the window also indicates that EnerVista UR Setup is in EDIT mode.
4. Specify the entries to lock by clicking them.
The locked entries display a grey background as shown in the example.

4-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

Figure 4-10: Locking FlexLogic equation entries in Edit Mode

5.
6.
Click the Save button to save and apply changes to the settings template.
Select the Template Mode > View In Template Mode option to view the template.
4
7. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode >
Password Protect Template option.
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries is shown here.
Figure 4-11: Locking FlexLogic entries through settings templates

Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR

The FlexLogic entries are also shown as locked in the graphical view and on the front panel display.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-11


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-12: Secured FlexLogic in graphical view

4.1.8.2 Lock FlexLogic equations to the serial number


A settings file and associated FlexLogic equations also can be locked to a UR serial number. Once FlexLogic entries in a
settings file have been secured, use the following procedure to lock the settings file to a serial number. A serial number is
viewable under Actual Values > Product Info > Model Information, the inside front panel, and the rear of the device.
1. Right-click the setting file in the Offline Window area and select the Edit Device Properties item. The window opens.

4-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

Figure 4-13: Settings file properties window

2. Enter the serial number of the F60 device to lock to the settings file in the Serial # Lock field.
3. Click the OK button to apply the change. The serial number is not validated.
The settings file and corresponding secure FlexLogic equations are now locked to the F60 device specified by the serial
number.

4.1.9 Settings file traceability


A traceability feature for settings files allows the user to quickly determine if the settings in a F60 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a F60 device, the date, time,
and serial number of the F60 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This
information can be compared with the F60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the F60
device or obtained from the F60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-13


ENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES

Figure 4-14: Settings file traceability

1 SETTING FILE TRANSFERRED


TO UR-SERIES DEVICE

The serial number and last setting change date


are stored in the UR-series device.

The serial number of the UR-series device and the file transfer
date are added to the setting file when setting files
are transferred to the device.

4 Compare transfer dates in the setting file and the


UR-series device to determine if security SERIAL NUMBER AND TRANSFER DATE
has been compromised. 2 SENT BACK TO ENERVISTA AND
ADDED TO SETTING FILE. 842864A2.CDR

With respect to the figure, the traceability feature is used as follows.


• The transfer date of a settings file written to a F60 is logged in the relay and can be viewed in the EnerVista software
or the front panel display. Likewise, the transfer date of a settings file saved to a local computer is logged in the
EnerVista software.
• Comparing the dates stored in the relay and on the settings file at any time in the future indicates if any changes have
been made to the relay configuration since the settings file was saved.

4.1.9.1 Settings file traceability information


The serial number and file transfer date are saved in the settings files when they are sent to a F60 device.
The F60 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup
offline window as shown in the example.
Figure 4-15: Device definition showing traceability data

Traceability data in settings


file device definition

842863A1.CDR

This information is also available in printed settings file reports as shown in the example. A report is generated by right-
clicking and selecting the Print Settings option.

4-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE

Figure 4-16: Settings file report showing traceability data

Traceability data
in settings report

4
842862A1.CDR

4.1.9.2 Online device traceability information


The F60 serial number and file transfer date are available for an online device through the actual values. Select the Actual
Values > Product Info > Model Information menu item within the EnerVista online window as shown in the example.
Figure 4-17: Traceability data in Actual Values window

7UDFHDELOLW\GDWDLQRQOLQH
GHYLFHDFWXDOYDOXHVSDJH

$&'5

This information is also available from the front panel display through the following actual values:
ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION  SERIAL NUMBER
ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION  LAST SETTING CHANGE

4.1.9.3 Additional traceability rules


The following additional rules apply for the traceability feature:
• If the user changes any settings within the settings file in the offline window, then the traceability information is
removed from the settings file
• If the user creates a new settings file, then no traceability information is included in the settings file
• If the user converts an existing settings file to another revision, then any existing traceability information is removed
from the settings file
• If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings
file

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-15


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

4.2 Front panel interface


This section explains use of the enhanced, basic, and graphical front panels.

4.2.1 Front panel

4.2.1.1 Enhanced front panel


The enhanced front panel consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional
user-programmable pushbuttons.
The front panel is hinged to allow access to removable modules inside the chassis. The F60 enhanced front panel can be
horizontal or vertical. The following figure shows the horizontal front panel.
Figure 4-18: Enhanced horizontal front panel
Five column LED indicator panel

4 Display

Keypad

Control
pushbuttons (3)
Front panel
RS232 port

User-programmable pushbuttons 1 to 16 842810A2.CDR

4.2.1.2 Basic front panel


The basic front panel consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The front panel is hinged to allow easy access to removable modules inside the chassis. There is also a removable dust
cover that is to be removed when accessing the keypad. The F60 basic front panel can be horizontal or vertical. The
following figure shows the horizontal front panel.

4-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-19: Basic horizontal front panel


LED panel 1 LED panel 2 LED panel 3

Display
Front panel
RS232 port

Small user-programmable
User-programmable Keypad
(control) pushbuttons 1 to 7
pushbuttons 1 to 12
827801A9.CDR

The following figure shows the vertical front panel for relays ordered with the vertical option.
Figure 4-20: Basic vertical front panel
4

GE Multilin
Display

MENU 7 8 9

HELP MESSAGE 4 5 6

ESCAPE 1 2 3
Keypad
ENTER VALUE 0 . +/-

1 3 5
USER LABEL USER LABEL USER LABEL
User-programmable
2 4 6
pushbuttons 1 to 6
USER LABEL USER LABEL USER LABEL

LED panel 2

STATUS EVENT CAUSE


IN SERVICE VOLTAGE
TROUBLE CURRENT RESET
TEST MODE FREQUENCY
TRIP OTHER USER 1
ALARM
PICKUP
PHASE A
PHASE B USER 2 LED panel 1
Front panel PHASE C
NEUTRAL/GROUND USER 3

RS232 port
827830A3.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-17


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

4.2.1.3 Graphical front panel


The graphical front panel consists of a USB port, LED panel, color screen display, user-programmable pushbuttons, and
navigation keys. The screen is used to read data, such as metering actual values, alarms, self-test messages, and event
records, and for viewing single-line diagrams. Settings can be changed on the front panel, except for the graphical front
panel itself and for IEC 61850. The USB port connects to a computer with the EnerVista software and can be used to
upgrade the relay and to transfer files and settings. The USB port is the square type B.
User-programmable pushbuttons 9 to 40 can be programmed among the 10 pushbuttons on the left and right sides of the
display.
Figure 4-21: Graphical front panel
Side pushbuttons
LEDs Display User-programmable pushbuttons

1 5
IN SERVICE

TROUBLE

TEST MODE

TRIP

ALARM 2 6

4
PICKUP

VOLTAGE

CURRENT 3 7
USB port FREQUENCY

OTHER

PHASE A 4 8
PHASE B

Not used
PHASE C

NEUTRAL / GND

RESET ESC
ENTER

Reset Tab pushbuttons Home Escape Navigation keys


859760A1.CDR

4.2.2 Front panel display

4.2.2.1 Enhanced and basic front panels


Messages display on a backlit liquid crystal display (LCD) to make them visible under poor lighting conditions. When the
keypad and display are not actively being used, the display defaults to user-defined messages. Any high-priority event-
driven message overrides the default messages.
Up to 20 characters can be used to configure some setting names in the software, while up to 12 characters display on the
front panel. A tilde ~ symbol is used for the twelfth character on the front panel when a name extends beyond the 12
character limit. An example is shown for a Virtual Input.
Figure 4-22: Tilde symbols displays with names 12 or more characters long

The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the
front panel or the LEDs.
To view the front panel in EnerVista software:
1. Click Actual Values > Front Panel, then any option.

4-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-23: Front panel use in the software (C60 shown)

4.2.2.2 Graphical front panel


The graphical front panel has a seven-inch (17.8 cm) color liquid crystal display (LCD). The display provides convenient
access to operational data generated by the relay, enables local control of power system devices, and allows display/
editing of settings.
Header content varies by page. The home page displays any active icons, such as security status, active setting group, and
active target messages. It shows the date and time of the relay. If the relay synchronizes to an external time source via PTP,
IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow. On pages other than the home page, the
header displays the name of the page.
The footer dynamically labels the Tab, or control, pushbuttons immediately below.
Page content displays between the header and footer.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-19


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-24: Home page example with default content (product information)
Setting Group
Alarm Target Relay Date and Time

4
859850A1.cdr

There are multiple ways to navigate pages, by using the pushbuttons and the menu hierarchy. The menu hierarchy is
similar to the other front panels whereby you select a submenu using Up and Down arrow pushbuttons, and press the
ENTER or Right pushbutton. On setting pages, opening a setting for editing is done by highlighting the setting using Up and
Down pushbuttons, and pressing the ENTER or Right pushbutton.

Home page
Press the Home pushbutton to display the root page no matter the state. Any edit, control, or password entry sessions are
canceled. The header shows several relay/system status icons. The default content of the home page is the product
information page and can be user-configured to show the content of any single-line diagram page, annunciator page,
metering page, or event records page for example. The Tab pushbuttons on the bottom row each navigate to their page.
The home page displays for a user-configured time period, then scrolls through user-configured pages, a feature referred
to as rolling.
Holding the Home pushbutton for one second displays the product information page. The Home page also can display
when settings are saved.

Security indicator, showing how many people are logged in, including local and remote users. The lock is red when
one or more users are logged in and other otherwise green.
When no users are logged in because login is not required, an icon does not display.
Identifies the active setting group number (not shown)

Displays when an abnormal annunciator alarm is present. Navigate to the Annunciator for details. When there
are no such alarms, the icon does not display.
Even when you acknowledge/reset an alarm, the icon displays as long as the condition remains. For example, a
breaker trouble alarm displays, you acknowledge it, but the icon remains because the breaker trouble remains.
Active targets symbol, where targets are error messages.
View error messages by pressing the Menu Tab pushbutton, then accessing the TARGETS menu. Pressing the
RESET button clears those messages that can be.

Configure the home page in the software under Settings > Product Setup > Graphical Panel > Home Page. The menu
does not display when there is no graphical front panel.

4-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Rolling mode
After a user-defined period of inactivity, the graphical front display rolls among up to 10 user-selected pages. The roll-to-
pages are selected in the EnerVista software, with the defaults being the product information page. Each page displays for
less than five seconds. Also, the display backlight intensity is lowered after a configurable period to a user-defined level (0,
10, 20, or 30%); lower intensity extends the life of the display.
Configure rolling mode in the software under Settings > Product Setup > Graphical Panel > Rolling Mode.
Operation works as follows:
• Press the Home pushbutton or ESCAPE pushbutton twice to cancel rolling, restore full backlight intensity, and return
to the Home page
• Press the ENTER, ESCAPE, or a pushbutton to pause rolling once and restore full backlight intensity
Rolling is disabled by setting the delay to 0.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all rolling mode settings to their factory default values
• Reset — Displays factory default values. Previous changes are not lost unless you save the reset window.

Single-line diagrams
4
A single-line diagram, or mimic diagram, is a line drawing of elements in an electrical system. The graphical front panel
displays up to five single-line diagrams. Each can be configured to show the arrangement of a portion of the power
system, the status of circuit breakers and of ground and disconnect switches, user-programmable pushbuttons, and
metering and status values. Each also enables control of the displayed breakers and switches when operand status
assigned to the Enable Controls from GFP setting is ON.
One diagram is provided by default, single_bus_line_dsc.mif, which can be modified.
Configure the diagrams under Settings > Product Setup > Graphical Panel > Single Line Diagram Editor.
Each single-line diagram page has a user-configurable name that appears in the header and in the footer Tab pushbutton
label. Factory default names are SLD 1 to SLD 5. Pages that have no configured content have a blank Tab pushbutton
label, and the Tab pushbutton does nothing. The label for the current page has a blue background.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-21


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-25: Toolbar options for single-line diagram

Select Breaker IEEE Transformer 3W IEEE


Line Breaker IEC Transformer 2W IEEE

Line Crossover Breaker GE Transformer 3W IEC

Bus Crossover Switch IEEE Transformer 2W IEC


Bus Switch IEC Reactor IEEE
Feeder Switch GE Reactor IEC
Ground
Metering Capacitor General IEC
Generator Status Capacitor Polarity IEEE
Motor Text Current Transformer IEEE
AC Source
Pushbutton Current Transformer IEC

Voltage Transformer IEEE


4 Voltage Transformer IEC
859875A1.cdr

The letters T, S, B, R, and X next to a controllable element have the following meaning. An example (TSB) is shown in the
next figure.
• T — The element is “tagged” (irrespective of whether it is tagged from graphical front panel or via IEC 61850). Local and
remote control of the device are inhibited, both open and close. Tripping is unaffected unless additional logic has been
configured.
• S — The position indication of the device is substituted with a manually entered value
• B — Blocking open/close command is bypassed
• R — Autoreclose is enabled and not blocked
• X — The device is out-of-service and control is not available

Single-line diagram example


The following example outlines how to create a circuit breaker diagram, then how to close the second circuit breaker. The
figure shows six switches (SW, M), two breakers (CB), feeder (arrow), and ground (lined arrow).

4-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-26: Single-line diagram of open circuit breakers

Under Settings > System Setup > Switches and Breakers, enable and name the six switches and two breakers. Switch 6,
M568G, has the A/3 Pole Opened setting on.
Figure 4-27: Configure Breaker and Switch settings

In the EnerVista software, open the single-line diagram editor under Settings > Product Setup > Graphical Panel > Single
Line Diagram Editor.
Add the four switches for the top line by clicking the GE switch symbol in the toolbar, then clicking in the window. (If the UR
device is not online, the software attempts to connect.) Right-click to edit properties. Rotate switches SW569 and SW5682
to 270 degrees. Rotate switches 5681 and SW523 to 90 degrees. Ignore the TSB text.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-23


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Add the two lower switches. Leave rotation at 0 degrees.


Add the two breakers by clicking the GE breaker symbol in the toolbar, then click in the window. Right-click to edit
properties, rotating 90 degrees and setting the color to red (open).
Draw lines to fill in the gaps between the switches and breakers by clicking the line symbol in the toolbar, then clicking and
dragging on the canvas to draw a line. Do not draw a single line for the top line, but instead draw several small lines.
Add the feeder arrow head by clicking the symbol in the toolbar, then clicking the end of the line.
Add the ground symbol by clicking the symbol in the toolbar, then clicking the end of the line.
Add three metered values by clicking the M symbol in the toolbar, then clicking near the feeder arrow. Double-click to edit.
The three metered values are SRC1 Vag Mag, SRC 1 P, and SRC 1 Q.
Name the page by right-clicking the bottom tab. Here, page 1 is renamed "Milton line M568M."
Note that active symbols in the toolbar display and those that are inactive are greyed-out.
The diagram has been created. Save it by clicking the Save button.

Next is to close circuit breaker CB523. This circuit breaker is shown at the top right of the figure. A vertical line means that
it is open, and the color can be set as red or green.
On the graphical front panel, press the Home pushbutton, then press the SLDs pushbutton to activate the first single-line
4 diagram page.
Figure 4-28: Single-line diagram on graphical front panel

Press the Enable Control pushbutton, which displays when the Settings > Product Setup > Graphical Panel > Home Page
> Enable Controls From GFP setting is configured and its FlexLogic operand is ON. The side pushbutton labels display.

4-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-29: Side pushbutton display on graphical front panel

Press the CB523 breaker pushbutton. Its menu displays.


Figure 4-30: Pushbuttons to control the breaker 4

Press the pushbutton to close the breaker, confirming the action at the prompt.

If at the prompt the control action is prevented this is because status of the operand assigned to the Enable
Controls From GFP setting has changed back to OFF before confirming the prompt action. As a result, the
command is not issued, and the screen goes to the top SLD page.
In this diagram, the two circuit breakers have hard-coded actions available to them. No action is possible on the switches.
Note the USER PB 9 and 10 entries in the earlier figure. As outlined later, these are activated by clicking the PB icon on the
software toolbar. These two pushbuttons can be configured under Settings > Product Setup > User-Programmable
Pushbuttons.
When a breaker is tagged, the letter T displays under the breaker in the diagram. The Tag pushbutton shown toggles to
Remove Tag.

Single-line diagram editor use


Start the application in the EnerVista software under Settings > Product Setup > Graphical Panel > Single Line Diagram
Editor.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-25


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

The following buttons display at the top of the window:


• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Load — Opens single-line diagram files, which replaces one or all windows with that in the file selected
• Store — Saves all single-line diagrams as a .mif file. Because single-line diagrams are not retained when using the
Convert Device Settings function, for example when converting in the Offline Window area from version 7.6 to 7.7, GE
recommends making backup files using this function.
On the right side of the window is a toolbox containing the components that can be added to the window. These include
line, breaker, disconnect, metering value, status value, text, and miscellaneous power system elements. To create the
single-line diagram, click the symbol, then click in the window. Once in the window, the component can be positioned and
its properties modified. When using the pointing device to position a component, the component can snap to the nearest
snap point. Snap points are in a 4 x 4 rectangular grid. The keyboard arrow keys move the selected component(s) in one
pixel increments when snap locations are inadequate. Multiple components can be selected and moved or deleted as a
group, or copied and pasted to another location. Right- or double-clicking a component opens the properties window.
Ctrl+A selects all objects in a diagram.

Lines

4 Line components represent power system buses or electrical connections between power system elements. They can also
be used as visual dividers and underline.
To add a line component, click it in the toolbox, then click in the window. Double-click a line to open its properties window
to set orientation.
Figure 4-31: Line and bus crossover symbols

Static symbols
Static symbols depicting power system elements are available. For information, see the ANSI/IEEE 315A and IEC 60617
standards.
Up to 32 static symbols can be used per single-line diagram.
To add a symbol, click it in the toolbox, then click in the window. Double-click the symbol to open its properties window to
set orientation.

4-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-32: IEEE and IEC static symbols

Breaker and disconnect components


Breaker components and disconnect components are interfaces to the UR breaker control elements and disconnect
switch elements. On a UR device they show dynamically the breaker or disconnect status as calculated by the element,
and provide means to open, close, tag, bypass interlock, and substitute (force status of) the element. Breaker components
in addition provide means to enable/disable breaker autoreclose.
Each breaker and disconnect component can be configured to use UR-style symbols, IEC symbols, or simple square/slash
symbols as shown in the following figure. The symbols assume horizontal symbol orientation, red - closed color, and green
- open scheme. With vertical orientation, they are rotated 90 degrees.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-27


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-33: Single-line diagram symbols

To add a breaker or disconnect component, click it in the toolbox, then click in the window. Up to 10 dynamic components
can be added to each single-line diagram.
Breaker and disconnect components have three different parts: label, symbol, and flags. Drag each of its parts to their final
locations. Double or right-click any of these parts to open the properties window. Properties that can be edited are label
text, breaker control element or disconnect switch element number, symbol orientation (horizontal or vertical), color
scheme (red - closed, or red - open), and assigned side button (if any). If the selected breaker or disconnect element does
not exist in the target relay or has not been enabled, then the component is displayed in the graphical front panel and in
the drawing edit window in grey. The color scheme selection has no effect when an IEC style symbol is used because IEC
style symbols do not use color.

4-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Symbol orientation
The figure shows the orientation available for the breaker and disconnect switch (taking Open status as examples). The
default position is 0 degrees.
Figure 4-34: Single-line diagram symbol orientation

A question mark displays in a symbol on the graphical front panel when status is bad. The question mark does not rotate
with orientation.
Figure 4-35: Symbols when status is bad

The following figures show the orientation available for the static components. The default position is 0 degrees.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-29


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-36: Single-line diagram static symbol orientation (sheet 1 of 2)

4-30 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-37: Single-line diagram static symbol orientation (sheet 2 of 2)

User-programmable pushbuttons
User-programmable pushbuttons 1 to 8 are physical pushbuttons on the right side of the graphical front panel, numbering
down the two columns.
Any remaining user-programmable pushbuttons are programmed among the 10 pushbuttons on the left and right sides of
the screen display. They show dynamically and provide a means to perform the same control as the other pushbuttons.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-31


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-38: Assigning pushbuttons to the display

4 As an example, if you set up a single-line diagram with two breakers and six switches, then eight of the side pushbuttons
are used automatically for control of the breakers and switches. Side pushbuttons 9 and 10 are available. In the single-line
diagram, let us set side pushbutton 9 to clear event records as follows:
• Show side pushbutton 9 on the graphical front panel — Click the PB symbol in the toolbar, then set Side button 9 to
pushbutton 9 in the drop-down list. This pushbutton then displays when appropriate on the right side of the screen
display.
• Program event record clearing — Set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 9 ON
• Program pushbutton 9 — Set Settings > Product Setup > User-Programmable Pushbuttons > Pushbutton 9
Function to "Self-reset." When pressed, pushbutton 9 clears the event records.
To instead set the second user pushbutton (not a side pushbutton) to clear events, follow the second and third bullet
points, selecting settings of PUSHBUTTON 2 ON and Pushbutton 2.

Metering components
Metering components show dynamically the value of a FlexAnalog operand or actual value. Up to 16 metering
components can be added to each single-line diagram.
To add a metering component, click the M symbol in the toolbox, then click in the window. Drag it to its final location.
Double-click it to open the properties window. The figure shows the properties that can be edited.

4-32 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-39: Metering properties

Status components
Status components show dynamically the value of a FlexLogic operand. Up to 16 can be used in a diagram and 30 in all
single-line diagrams.
An example is to show the Off or On state of the ANY MAJOR ERROR FlexLogic operand. The name of the operand
displays in the single-line diagram editor, then as Off or On on the graphical front panel.
To add a status component, click the S symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited include parameter (any FlexLogic operand), text color
background color, and on and off text.
Optionally add a text label to display beside the status.

Text
Text components show a single line of user-configured text.
Up to 16 text components can be used per single-line diagram.
To add a text component, click the T symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited are text, color, and size.

Annunciator
An annunciator is a grid of small windows for alarms, actual values, self-test messages, and product information.
The graphical front panel emulates a conventional annunciator panel. The annunciator has 96 windows, each with a
description of the alarm condition that lights the window. The windows are arranged in rows and columns of 3 x 4, 4 x 6, or
6 x 8 over several pages. Each window can have up to three lines of configurable text, and one line can instead be a
metered value. Normally the window background is dark, and when the configured FlexLogic operand becomes On, the
window lights up.
The figure shows that two alarms are active. One alarm is configured red and the other alarm is configured blue. The red
alarm type is Self Reset, so the alarm displays in a solid color. The blue alarm type is Acknowledgeable, so the alarm flashes
until it is acknowledged, for example by navigating with the arrow keys and pressing the ENTER button. The alarm then
remains blue until the trigger condition is eliminated.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-33


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-40: 3x4 annunciator page with two active windows

To display the annunciator, press the Home pushbutton, then the Annunciator Tab pushbutton. If there is one or more
4 window in alarm or requiring reset, the annunciator page showing the first of these opens. Otherwise the first annunciator
page opens.
Alarms do not display automatically. Set the Home page and/or rolling pages to display annunciator pages.
The Tab pushbutton labels populate with the annunciator pages. The label text for each annunciator page is configurable
and displays in the header and Tab label. The current page has a blue Tab label. Tab labels for annunciator pages that
have an active window (that is, on, latched, or unacknowledged) are red. Pages where alarms are not triggered have a grey
Tab label. Pages that have no configured windows do not have Tab pushbuttons and do not display.
The Up, Down, Left, and Right pushbuttons cause the selection to move one window in the indicated direction. Pressing the
Right pushbutton past the last window in a row scrolls the display to any next annunciator page, not the next row. The
behavior is similar for the other pushbuttons, for example pressing the Up pushbutton while in the top row goes to any
previous page. If no previous page exists, no action occurs.
Annunciator windows are positioned statically, so that all windows are visible no matter their state.
Alarm types of each window can be configured as Self Reset, Latched, or Acknowledgeable. In Self Reset mode, the
window lighting follows the state of the configured FlexLogic operand. The self-reset mode alarm sequence conforms to
ISA-18.1-1979 (R2004) standard type A 4 5 6.
Figure 4-41: Annunciator alarm sequence in Self Reset mode

Process: Normal
Sequence: Normal
Visual: Off
Return to Normal

To Abnormal

Process: Abnormal
Sequence: Acknowledged
Visual: On
859856A1.vsd

4-34 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Latched mode is intended for transient signals such as trip, and it conforms to ISA-18.1-1979 (R2004) standard type M 6.
Figure 4-42: Annunciator alarm sequence in Latched mode

Process: Normal
Sequence: Normal To Abnormal
Visual: Off

Return to Normal Reset while


Process: Abnormal or Normal
Sequence: Alarm
Normal
Visual: Fast Flash

Process: Abnormal
Reset while
Sequence: Acknowledged
Abnormal
Visual: On
859857A1.vsd

4
In Acknowledgeable mode, both Off to On and On to Off state changes in the configured operand cause the background to
flash; the window must be acknowledged/reset to cancel flashing. This mode conforms to ISA-18.1-1979 (R2004) standard
type R-6.
Figure 4-43: Annunciator alarm sequence in Acknowledgeable mode

Process: Normal
Reset Sequence: Normal To Abnormal
Visual: Off

Process: Normal Reset while Normal Process: Abnormal or Normal


Sequence: Ringback Sequence: Alarm
Visual: Slow Flash Return to Abnormal Visual: Fast Flash

Process: Abnormal
Reset while
Return to Normal Sequence: Acknowledged
Abnormal
Visual: On
859858A1.vsd

To reset all annunciator windows:


1. In the software, access Actual Values > Graphical Panel > Annunciator Panel.

To acknowledge/reset all annunciator windows on a page:


1. On the graphical front panel with none of the annunciator windows selected, press the RESET pushbutton once for
acknowledgement and twice for reset. The flashing stops.

To acknowledge an annunciator window:


1. On the graphical front panel, press the Up, Down, Left, and Right pushbuttons to select the window, so that is has a
yellow outline. Press the RESET or ENTER pushbutton. While a window is selected, if that window has activated since
the last restart, the date/time of the last activation of that window displays in the header.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-35


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

An alarm remains in an alarm state (for example, displays red) when the condition remains. That is, if you acknowledged a
flashing alarm but the alarm condition remains, the background color remains red.
The SETTINGS > INPUTS/OUTPUTS > RESETTING > RESET ANNUNCIATOR setting can be used to select a FlexLogic
operand that when activated acknowledges/resets all annunciator windows.

Annunciator editor
The annunciator editor is used to configure alarms and actual value displays for the graphical front panel.
The path in the EnerVista software is Settings > Product Setup > Graphical Panel > Annunciator Editor.
The figure shows the annunciator editor and its preview window. The page name is entered as General at the top right.
Acknowledgeable and self-resetting alarms are set for basic functions, such as online/offline, Ethernet ports, unauthorized
access/failed logins, and battery failure. The text to display in the annunciator window is entered. The IN SERVICE LED is set
to be green because when the device is on, this LED is green. The preview shows what the annunciator looks like with all
alarms triggered. The last window is not configured and displays blank/grey. In order for the Ethernet and battery alarms
to work, the corresponding self-test alarms have been enabled under Settings > Product Setup > User-Programmable
Self Tests (not shown). The LEDs can be viewed on the front panel, so adding them to the annunciator is for illustrative
purposes only.

4 Figure 4-44: Annunciator editor and preview window

4-36 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

The three page layouts (3 × 4, 4 × 6, and 6 × 8) select the number of rows x columns of windows that appear in a page.
Annunciator window size and text size shrink as the number of annunciator windows in a page increases.
Properties that can be edited include alarm type (acknowledgeable, latched, self-reset), alarm input (any FlexLogic
operand), text color, and alarm background color.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all annunciator settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.

Metering editor
The metering editor is an actual values display tool. It creates pages of actual values for the graphical front panel. There
are two types: tables and phasor diagrams. Tabular actual values pages have settings to configure, while phasor actual
values pages have no settings. Five tabular metering pages can be configured, while there can be a phasor page for each
configured AC source. They display on the graphical front panel using the Metering Tab pushbutton.
The path to the editor is Settings > Product Setup > Graphical Panel > Metering Editor.
Figure 4-45: Metering editor with preview window
4

The inputs are selected at the top. Select from the drop-down list or start typing in the field.
The page, page name, and grid layout are set below the inputs.
Content to display is configured with the cell lines. The content can be actual values, a status indicator, or text.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-37


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

• Actual value — Select from the FlexAnalogs applicable to the F60, where a FlexAnalog is an analog parameter
• Status — Select from the FlexLogic operands identified in the Status Inputs at the top of the window. An example is to
display text to indicate whether the BATTERY FAIL operand is on or off.
• Text — Enter text to display in the table, for example name of table or column heading
If the metering input is other than OFF, the value of the selected metering input displays, formatted according to the size,
text color, units, multiplier, and decimal configuration. Otherwise either the Text or the Off Text displays depending on the
value of the operand selected by setting Status Input/Index.
A maximum of eight Status Inputs/Indexes can be used per metering page and 16 in all metering pages.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all actual value settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.

Configurable navigation editor


Configurable Navigation is a feature that opens specified pages when specific FlexLogic operands are activated. This
4 feature is useful to open the annunciator page containing an annunciator window that has entered its abnormal state.
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure pages to work, these functions also have
been enabled under Settings > Product Setup > User-Programmable Self Tests. For the breaker trouble, the single-line
diagram has been configured.
Figure 4-46: Navigation editor

The path is Settings > Product Setup > Graphical Panel > Configurable Navigation.
The settings consist of 64 field pairs, each with a condition and an activation page. The condition selects any FlexLogic
operand. The activation page selection is the standard set, such as product information, event records, annunciator pages,
and single-line diagrams.
To use the feature, select a CONDITION, select its ACTIVATE PAGE option, then save. When selecting the condition
operand, open the drop-down list and start typing in the field to auto-fill. For example, typing F displays FIRST ETHERNET
FAIL.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved

4-38 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

• Default — Changes all settings in the window to factory default values


• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.

4.2.3 Front panel navigation keys

4.2.3.1 Enhanced and basic front panels


Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is divided further into further submenus.
The MESSAGE keys navigate through the submenus. The VALUE keys increment or decrement numerical setting values when
in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, values can
be entered with the numeric keypad.
The decimal key initiates and advances to the next character in text edit mode or enters a decimal point.
The HELP key can be pressed at any time for context-sensitive help messages.
The ENTER key stores setting values.
When entering an IP address on the front panel, key in the first sequence of the number, then press the • key for the
decimal place. For example, for 127.0.0.1, press 127, then •, then 0, then •, then 0, then •, then 1. To save the address, press
the ENTER key. 4
When entering or changing an order code with two lines, press the down arrow to access the second line. On a basic front
panel, do this under ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION.
The figure shows the sequence to use to enter a setting. Subsequent sections provide more detail.
Figure 4-47: Front panel keypad use (basic front panel shown)

SETTINGS
PRODUCT SETUP

1. Press to scroll top level:


SETTINGS
MENU 7 8 9

HELP 4 5 6
3. Press to scroll third level fields MESSAGE
2. Press to scroll second level:
ESCAPE 1 2 3 PRODUCT SETUP.
4. Press to scroll through values
ENTER VALUE 0 . +/-
5. Press to save change

842231A1.cdr

4.2.3.2 Graphical front panel


These keys and pushbuttons navigate and select items.

Up/Down/Left/Right — These pushbuttons move the selector among the options on a page. The selection is
indicated by a yellow background or a yellow border. On menu pages, the Right pushbutton activates the selected
submenu drilling down the menu hierarchy, and the Left pushbutton backs up the menu hierarchy. These
pushbuttons have a typematic feature on some pages: after a short pause, the pushbutton repeats as long as it is
pressed.

ENTER — Activates the selection on the display, for example a submenu, a control, a keypad key, or a setting. Also
stores updated settings.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-39


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

ESCAPE — If a setting is open for edit, this pushbutton closes the setting without saving. If an item is selected, this
pushbutton deselects it. Otherwise this pushbutton activates the previous page in the page hierarchy.

RESET — Clears all latched LED indications and target messages. When a page with acknowledgeable/resettable
items is displayed, it instead resets/acknowledges all items on that page, or if an item on that page is selected, it
resets/acknowledges that item.
If you reset/acknowledge alarms, they stop flashing but remain in the alarm state as long as that state remains. In
other words, a red alarm does not switch off just because you acknowledged the alarm.
Home — Activates the home page, which is the root page. The page displays product information by default and
is configurable.

Side pushbutton — Five pushbuttons on the left side of the display and five pushbuttons on the right side of the
display. They perform various functions depending on the displayed page, such as switchgear controls. The
display dynamically shows its label next to each side pushbutton when the pushbutton has an assigned function.
These pushbuttons can also be programmed to function as user-programmable pushbuttons 9 and above.
Tab pushbutton — Five pushbuttons under the display. They navigate through the page hierarchy, and on some
pages activate other actions. The display footer dynamically labels the page or action that is activated by the Tab
pushbutton.

User-programmable pushbutton — Eight physical pushbuttons are associated with the first eight user-

4 programmable pushbutton elements. Numbering is down, that is, 1 to 4 down the left column and 5 to 8 down the
right column.
These elements control a set of FlexLogic operands that can be used to initiate outputs or select modes. Each
physical pushbutton has an integrated LED indicator that can be user-configured to display the appropriate
status.
These pushbuttons have clear covers behind which custom labels can be mounted. A utility is available to print
the labels, under File > Front Panel Report in the software.

4.2.4 LED indicators

4.2.4.1 Enhanced front panel


The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event-
cause LEDs. The next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the SETTINGS  INPUT/OUTPUTS  RESETTING menu).
The USER keys are used by the breaker control feature.

Figure 4-48: Typical LED panel for enhanced front panel

842811A1.CDR

The status indicators in the first column are as follows:

4-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and
the relay is in (online) Programmed mode (under Settings > Product Setup > Installation)
• TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Testing section in the Settings chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the FlexLogic operand serving as an alarm switch has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator never latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as either “Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the
corresponding event-cause LEDs remain on as long as the operand associated with the element remains asserted. If a
protection element target setting is “Latched,” then the corresponding event-cause LEDs turn on when the operate
operand associated with the element is asserted and remains on until the RESET button on the front panel is pressed after
the operand is reset. 4
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — This LED indicates voltage was involved
• CURRENT — This LED indicates current was involved
• FREQUENCY — This LED indicates frequency was involved
• OTHER — This LED indicates a composite function that is not solely current, voltage, or frequency based (distance or
power for example) or a control function (digital element or trip bus for example)
• PHASE A — This LED indicates phase A was involved
• PHASE B — This LED indicates phase B was involved
• PHASE C — This LED indicates phase C was involved
• NEUTRAL/GROUND — This LED indicates that neutral or ground was involved

The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label
package of every F60, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-Programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.

4.2.4.2 Basic front panel


The basic front panel consists of three panels with LED indicators, keys, and a communications port. The RESET key is used
to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions can
also be reset via the SETTINGS  INPUT/OUTPUTS  RESETTING menu). The RS232 port is for connection to a computer.
The USER keys are used by the breaker control feature.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-41


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-49: LED panel 1

Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and
the relay is in (online) Programmed mode (under Settings > Product Setup > Installation)

4 • TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Testing section in the Settings chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip switch has operated. This indicator always
latches; initiate the reset command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm switch has operated. This indicator never
latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.

Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event cause LEDs
remain on as long as the operand associated with the element remains asserted. If a protection element target setting is
“Latched,” then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remains on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — Indicates voltage was involved
• CURRENT — Indicates current was involved
• FREQUENCY — Indicates frequency was involved
• OTHER — Indicates a composite function that is not solely current, voltage, or frequency based (distance or power for
example) or a control function (digital element or trip bus for example)
• PHASE A — Indicates phase A was involved
• PHASE B — Indicates phase B was involved
• PHASE C — Indicates phase C was involved
• NEUTRAL/GROUND — Indicates that neutral or ground was involved

User-programmable indicators
The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Custom labeling
can be done.

4-42 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
Figure 4-50: LED panels 2 and 3 (index template)

Default labels for LED panel 2


The default labels are intended to represent the following:


GROUP 1...6 — The illuminated GROUP is the active settings group
BREAKER 1(2) OPEN — The breaker is open
4
• BREAKER 1(2) CLOSED — The breaker is closed
• BREAKER 1(2) TROUBLE — A problem related to the breaker has been detected
• SYNCHROCHECK NO1(4) IN-SYNCH — Voltages have satisfied the synchrocheck element
• RECLOSE ENABLED — The recloser is operational
• RECLOSE DISABLED — The recloser is not operational
• RECLOSE IN PROGRESS — A reclose operation is in progress
• RECLOSE LOCKED OUT — The recloser is not operational and requires a reset

Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six setting
groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups. Even
though the LEDs have default labels, they are fully user-programmable.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in
the next section.
Figure 4-51: LED panel 2 (default labels)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-43


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

4.2.4.3 Graphical front panel


The graphical front panel has 14 LEDs. LEDs 1 to 5 are fixed status LEDs, and LEDs 6 to 14 are programmable.

Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay’s test mode is disabled, and the relay is in (online) Programmed mode (under Settings > Product Setup >
Installation)
• TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in Test Blocked (solid) or Test (flashing) mode. For information, see the Testing
section in the Settings chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm input has operated. Set the operand
under Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs.

4 Figure 4-52: Example of LEDs on graphical front panel

User-programmable event-cause indicators


Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as “Self-Reset” or “Latched.” If set to “Self-Reset,” then the corresponding event cause LED remains
on as long as the operand associated with the element remains asserted. If set to “Latched” and asserted, then it remains
on until the operand is reset and then a reset command initiated.
All elements that are able to discriminate faulted phases can independently turn on or off the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
The LEDs have defaults and can be configured to show instead the status of any FlexLogic operand.
The labeling area has a clear cover for custom labels. A utility is available to print stick-on labels, as outlined later in this
chapter.
These LEDs are programmed by default as follows:
• PICKUP — LED 6 — Indicates that an element is picked up, and hence a trip can be imminent
• VOLTAGE — LED 7 — Indicates voltage was involved
• CURRENT — LED 8 — Indicates current was involved
• FREQUENCY — LED 9 — Indicates frequency was involved

4-44 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

• OTHER — LED 10 — Indicates a composite function that is not solely current, voltage, or frequency based (distance or
power for example) or a control function (digital element or trip bus for example)
• PHASE A — LED 11 — Indicates phase A was involved
• PHASE B — LED 12 — Indicates phase B was involved
• PHASE C — LED 13 — Indicates phase C was involved
• NEUTRAL/GROUND — LED 14 — Indicates that neutral or ground was involved

4.2.5 Front panel labelling


4.2.5.1 Enhanced front panel
The following procedure requires these pre-requisites:
• The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded from
http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed
• Small-bladed knife
To create custom LED and pushbuttons labels for the enhanced front panel:
1. Start the EnerVista UR Setup software.
2. If not already copied to the Offline Window area, right-click the online device and select the Add Device to Offline 4
Window option. Click the Receive button in the window that opens to save the settings file to the Offline Window area.
3. Type labels as follows. Select the File > Front Panel Report. The window opens.
Figure 4-53: Enhanced front panel label designer

4. Enter the text to appear next to each LED and above each user-programmable pushbutton in the fields provided. The
LED Offsets and Button Offsets buttons move all labels left/right and up/down on the page (they both do the same
action, so use either button). The Button Offsets button does not display when there are no pushbuttons to customize.
5. Feed the UR front panel label cutout sheet into a printer and press the Print button in the front panel report window.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-45


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

6. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
7. Remove the UR label insert tool from the package and bend the tabs as described in the following procedures. These
tabs are used for removal of the default and custom LED labels.

Use the tool with the printed side containing the GE part number facing the user.

The label package shipped with every F60 contains the three default labels, the custom label template sheet, and the label
removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, use the following procedures to remove the original labels and insert the new ones.
To set up and use the label removal tool:
1. Bend the tabs at the left end of the tool upwards as shown.

Bend the tab at the center of the tool tail as shown.

To remove the LED labels from the F60 front panel and insert the custom labels:
1. Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from

4-46 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

the relay.

2. Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label.

3. Remove the tool and attached LED label as shown.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-47


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown.

To remove the user-programmable pushbutton labels from the F60 front panel and insert the custom labels:
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent
4 tab points away from the relay.

2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown. This attaches the
label tool to the user-programmable pushbutton label.

4-48 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

3. Remove the tool and attached user-programmable pushbutton label.

4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the
buttons.
4

4.2.5.2 Basic front panel


After programming LEDs and pushbuttons under Settings > Product Setup > User-Programmable Leds and User-
Programmable Pushbuttons, labels can be created for the front panel.
To create LED and pushbutton labels for a basic front panel:
1. In the EnerVista software, if the F60 is not already listed in the Offline Window area, add it by right-clicking it and
selecting the Add Device to Offline Window option.
2. Click the File > Front Panel Report menu item and select the device.
3. In the Front Panel Report window, double-click an LED or pushbutton slot and type a label. If you need to see the
existing front panel remotely, access Actual Values > Front Panel for the online device. If you need to see the In the
figure, note that labeling is being done for the third set of LEDs because the second panel of LEDs was factory-labeled.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-49


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-54: Basic front panel label designer (LEDs shown)

4
4. Optionally save the changes by clicking the Save icon on the toolbar.
5. Click the Print icon on the toolbar. Consider printing to PDF format and adjusting the zoom for appropriate label size,
then print on a physical printer.
6. Cut labels as a block or individually, for example with scissors or an Exacto knife.
7. If there is a plastic cover over the front panel, remove it by gently pushing in on the right side and lifting off the cover.
8. Remove the plastic cover over the LEDs or pushbutton(s) using a screw driver.
9. Insert the labels.
10. Re-attach the plastic covers.

4.2.5.3 Graphical front panel


The F60 includes software for labeling the LEDs and pushbuttons on the graphical front panel and a sticker sheet with pre-
printed and blank labels. The pre-printed labels are on the top-left of the template sheet, and the blank labels are on the
bottom-right. Use the pre-printed labels, or use the designer provided in the software and print labels onto the template.
One sheet is provided.
The example shows LED labeling, with pushbutton labeling below it (cut off).
To create LED and pushbutton labels for the front panel:
1. In the EnerVista software, in the Online or Offline Window area, access Settings > Front Panel Label Designer or
Front Panel Label Designer (at the product root level). The designer window opens with pre-configured labels.
2. Under File > Print Setup, change the page orientation to Landscape.
3. In the label designer window, delete all labels not wanted for printing. This can be done by clicking the Reset button to
clear all labels, or by selecting each unwanted label and deleting it. Otherwise, all labels displayed print on the
template and use up the template. If you make a mistake, exit the window and open it again to view the default labels.
4. Based on the location on the template on which to print, create the labels by typing in the appropriate slots.

4-50 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-55: Front panel label designer for graphical front panel

5. Click the Print button in the window and select the printer.
6. Once printed, peel the labels off the template and stick them on the front panel. For the enhanced and graphical front
panels, they go over the clear plastic inserts, not under. For the basic front panel, they go under or over the plastic
covers.
Any changes are not saved. Each time that the label designer window opens, the original template displays. Any labels
deleted are not lost.

4.2.6 Menu navigation


Press the MENU key to display selections or home page. Each press of the key advances through the following main
headings:
• Actual Values
• Settings
• Commands
• Targets
• Factory Service
• User displays (when enabled)

4.2.6.1 Enhanced and basic front panels


The setting and actual value pages are arranged hierarchically. Header display pages are indicated by double scroll bars
(), while sub-header pages are indicated by a single scroll bar (). The header display pages represent the highest level
of the hierarchy and the sub-header display pages fall below this level. Use the down, right, left, and up arrows to navigate
the menu. The MESSAGE up and down arrow keys move within a group of headers, sub-headers, setting values, or actual

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-51


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

values. Continually pressing the MESSAGE right arrow from a header display displays specific information for the category.
Conversely, continually pressing the MESSAGE left arrow from a setting value or actual value display returns to the header
display.
Default values are indicated in this instruction manual in mixed case. In the example shown here, the default access level is
Restricted.
Highest level Lowest level (setting value)

 SETTINGS  SECURITY ACCESS LEVEL:


 PRODUCT SETUP    Restricted

 SETTINGS
 SYSTEM SETUP

Example

 ACTUAL VALUES Press the MENU key until the Actual Values header page appears. This page contains system
 STATUS and relay status information.

4  SETTINGS

Press the MENU key until the Settings header page appears. This category contains settings to
 PRODUCT SETUP configure the relay.

 SECURITY Press the MESSAGE right arrow once to display the first sub-header (Security).


ACCESS LEVEL: Press the MESSAGE right arrow once to display the first setting for Security.
Restricted

 SECURITY Press the MESSAGE left arrow to return to the Security heading.


 DISPLAY Press the MESSAGE down arrow to display the second setting sub-header associated with the
 PROPERTIES Product Setup header.

LANGUAGE: Press the MESSAGE right arrow once to display the first setting for Display Properties.
English

 SETTINGS Press the MESSAGE left arrow to return to the Display Properties page, then again to return to
 SYSTEM SETUP the Product Setup Page. Press the MESSAGE down arrow to move to the next Settings page. This
page contains settings for System Setup.

4.2.6.2 Graphical front panel


Access the main menu by pressing the Home pushbutton, then the Menu Tab pushbutton.
Use the Up and Down arrow pushbuttons to select a submenu, then press the Right or ENTER pushbutton to drill into that
submenu. The Left and ESCAPE pushbuttons back up the menu hierarchy.
The Page Up and Page Down Tab pushbuttons also navigate through the list. When there is only a single page of options,
they jump to the first and last entries.
The options displayed depend on order code.

4-52 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-56: Main menu on graphical front panel

4.2.7 Change settings


4
4.2.7.1 Enhanced and basic front panels

Numerical data
Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define
what values are acceptable for a setting.

FLASH MESSAGE For example, select the SETTINGS  PRODUCT SETUP  DISPLAY PROPERTIES  FLASH
TIME: 10.0 s MESSAGE TIME setting.

MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the key again to view the
MAXIMUM: 10.0 next context sensitive help message.

Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point — The relay numeric keypad works the same as a calculator. A number is entered one digit at
a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MESSAGE left arrow or
pressing the ESCAPE key, returns the original value to the display.
• VALUE keys — The VALUE up arrow increments the displayed value by the step value, up to the maximum value
allowed. While at the maximum value, pressing the VALUE up arrow again allows the setting selection to continue
upward from the minimum value. The VALUE down arrow decrements the displayed value by the step value, down to
the minimum value. While at the minimum value, pressing the VALUE down arrow again allows the setting selection to
continue downward from the maximum value.

FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate numeric
TIME: 2.5 s keys in the sequence “2 . 5". The display message changes as the digits are being entered.

NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Press ENTER to store the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation of the storing
process. Numerical values that contain decimal places are rounded-off if more decimal place digits
are entered than specified by the step value.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-53


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Enumeration data
Enumeration settings have data values that are part of a set, whose members are explicitly defined by a name. A set has
two or more members.

ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted," "Command," "Setting," and
Restricted "Factory Service."

Enumeration type values are changed using the VALUE keys. The VALUE up arrow displays the next selection while the
VALUE down arrow displays the previous selection.

ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting," press the VALUE keys until the proper selection displays.
Setting Press HELP at any time for the context sensitive help messages.

NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing ENTER stores the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation.

4 Alphanumeric text
Text settings have data values that are fixed in length, but user-defined in characters. They can be upper-case letters,
lower-case letters, numerals, and a selection of special characters.
There are several places where text messages can be programmed to allow the relay to be customized for specific
applications. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example, enter the text “Breaker #1”.
1. Press the decimal point to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for several
seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.

4.2.7.2 Graphical front panel


When enabling an element in the EnerVista software that outputs to an actual value, the actual values menu is not
updated on the graphical front panel via Ethernet connection when that menu is active on the graphical front panel.
Navigate out and back into the menu for activation.

Numerical data
This example outlines how to change the FLASH MESSAGE TIME setting. Flash messages are status, warning, error, and
information messages displayed in response to certain key presses during settings programming. An example is a
confirmation message upon saving settings. This setting specifies how long to display the message.
Press the Menu pushbutton to display the main menu.

4-54 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-57: Main menu

Use the Up or Down pushbutton to select SETTINGS, then press the Right or ENTER pushbutton.
Figure 4-58: Settings menu 4

With PRODUCT SETUP selected, press the Right or ENTER pushbutton.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-55


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-59: Product Setup menu

Use the Up or Down pushbutton to select DISPLAY PROPERTIES, then press the Right or ENTER pushbutton.
4 Figure 4-60: Display Properties menu

Use the Up or Down pushbutton to select FLASH MESSAGE TIME, then press the Right or ENTER pushbutton. If the relay is
configured to require login to edit settings, and the user is not already logged in, the login page displays. When the user
has successfully logged in, the setting is opened for edit. As the FLASH MESSAGE TIME setting accepts a numerical value, a
keypad displays. The time is to be changed to 4.0 seconds.
The current setting displays. A flashing cursor line marks the insertion point, initially positioned after the last character of
the setting. The setting range displays under the text.
Press the <-- Move Cursor and Move Cursor --> Tab pushbuttons to move the insertion point. Place it after the 2.
Press the Backspace Tab pushbutton to remove the character to the left of the cursor, in this case the 2.
Using the arrow keys, enter another time, for example 4 for four seconds. These Up, Down, Left, and Right pushbuttons
move the keypad key selector. Pressing the ENTER pushbutton with the - key selected inverts the sign. Pressing the ENTER
pushbutton with the decimal point selected enters that character at the insertion point. Push ENTER now to accept the 4.

4-56 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-61: Settings page with numeric keypad

Press the Save Tab pushbutton, which does a range check on the value, saves the setting when valid, closes the page, and
displays the previous page. 4
When a setting is not saved due to an invalid value, a message flashes, for example being out of range. In cases where the
relay needs to be restarted for settings to take effect, the flash message advises.
Setting entry can be canceled without impact on the original value by pressing the ESCAPE or Home pushbutton.

Alphanumeric text
Settings that accept alphanumeric values display a keyboard. An example is a pushbutton name.
The &123 key toggles between text and numbers.
The shift key (up arrow on keyboard) is green upon activation, while the keyboard letters switch to upper case. Double-click
the shift key to lock capital lettering, or full capitals.
The globe key (shown greyed-out) toggles the keyboard language between English and another display language selected,
for example between English and French. (The second language needs to be activated under Settings > Product Setup >
Display Properties.)
For Japanese and Chinese, up to 10 characters can be input in a field, not 20.
To add accents, highlight a key and hold the ENTER pushbutton on the graphical front panel. Any special characters
associated with the key display.
To avoid conflict with XML programming, do not enter the following characters on the Annunciator and Metering editor
panels: " (quotation mark), ' (apostrophe), < (less than), > (greater than), & (ampersand). When used, the text following the
character does not display or the Annunciator and Metering panels do not display on the graphical front panel.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-57


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

Figure 4-62: Settings page with keyboard and accents

4.2.8 View actual values


4
4.2.8.1 Graphical front panel
In addition to data viewable in the Actual Values menu on the front panel, phasor diagrams and metered data can be
displayed. The metered data can be arranged as a table.
The update rate of metered values is 500 ms.
A phasor page for each configured AC Source and up to five user-configurable metering pages can be displayed. The
phasor pages are not configurable. Each phasor page shows a phasor plot and numerical values of all currents, voltages,
and symmetrical components of a single AC source.
The Annunciator and Metering pages can be configured to display data. Each has a user-configured number of rows and
columns. Each cell can include either configurable static text or the value of a selected FlexLogic operand, FlexAnalog
operand, or actual value.
To display a metering page, press the Home pushbutton, then the Metering Tab pushbutton. The first metering page
opens, with phasor pages listed before tabular pages. The Tab pushbuttons display any other metering page, as do the Up,
Down, Left and Right pushbuttons. The current page is highlighted with a blue Tab pushbutton.
Each phasor page has a name, which consists of the value of the SOURCE NAME # setting appended with " Phasors."
Phasor pages that have no configured CTs or VTs do not have a Tab pushbutton, and phasor pages that have no
configured cells cannot be displayed.

4-58 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

Figure 4-63: Phasor display

The configurable name displays in the header and Tab pushbutton label. Factory default names are Page 1, Page 2, and so 4
on.
Figure 4-64: Metered actual values

The phasor sources are configured under Settings > System Setup > Signal Sources. The tables to display the actual
values are configured in the software under Settings > Product Setup > Graphical Panel > Metering Editor.

4.2.9 Breaker control


The F60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker,
that can be presented on front panel LEDs, along with a breaker trouble indication. Breaker operations can be manually
initiated from the front panel keypad or automatically initiated from a FlexLogic operand. A setting is provided to assign
names to each breaker; this user-assigned name is for the display of related flash messages. These features are provided
for two breakers; the user can use only those portions of the design relevant to a single breaker, which must be breaker 1.
It is assumed in the following discussion that the SETTINGS  SYSTEM SETUP  BREAKERS  BREAKER 1(2)  BREAKER
FUNCTION setting is "Enabled" for each breaker.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-59


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

4.2.9.1 Control mode selection and monitoring


Installations can require that a breaker be operated in the three-pole only mode (3-pole), or in the one and three-pole (1-
pole) mode, selected by setting. If the mode is selected as three-pole, a single input tracks the breaker open or closed
position. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be
in agreement to indicate the position of the breaker.
For the following discussion it is assumed that the SETTINGS  SYSTEM SETUP  BREAKERS  BREAKER 1(2)  BREAKER
1(2) PUSH BUTTON CONTROL setting is “Enabled” for each breaker.

4.2.9.2 Front panel (user key) control


After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.

4.2.9.3 Control of two breakers


For the following setup example, the (Name) field represents the user-programmed variable name.
For this example, the relay is connected and programmed for both breaker 1 and breaker 2. The USER 1 key performs the
selection of which breaker is to be operated by the USER 2 and USER 3 keys. The USER 2 key manually closes the breaker, and
the USER 3 key manually opens the breaker.
4
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a COMMAND
PASSWORD PASSWORD is required, that is, if COMMAND PASSWORD is enabled and no commands have been
issued within the last 30 minutes.

Press USER 1 This message appears if the correct password is entered or if none is required. This message
To Select Breaker displays for 30 seconds or until the USER 1 key is pressed again.

BKR1-(Name) SELECTED This message displays after the USER 1 key is pressed for the second time. Three possible actions
USER 2=CLS/USER 3=OP can be performed from this state within 30 seconds as per the following items (1), (2) and (3).

(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is pressed
To Close BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
close breaker 1.

(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is pressed
To Open BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
open breaker 1.

(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different breaker is
USER 2=CLS/USER 3=OP selected. Three possible actions can be performed from this state as per (1), (2) and (3). Repeatedly
pressing the USER 1 key alternates between available breakers. Pressing keys other than USER 1, 2,
or 3 at any time cancels the breaker control function.

4.2.9.4 Control of one breaker


For this application, the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described in the previous section for two breakers.

4.2.10 Change passwords


The information in this section refers to password security. For information on how to set the password for the first time or
change CyberSentry passwords, see the previous chapter or the Settings > Product Setup > Security > CyberSentry section
in the next chapter.

4-60 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FRONT PANEL INTERFACE

The F60 supports password entry from a local or remote connection.


Local access is defined as access to settings or commands via the front panel. This includes both keypad entry and the
RS232 port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. Any change to the local or remote password enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the F60, the remote password must be used. If the
connection is to the RS232 port of the front panel, the local password must be used.
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
• Setting — Allows the user to make any changes to any of the setting values:
– Changing any setting
– Test mode operation
• Command — Restricts the user from making any settings changes, but allows the user to perform the following
operations:
– Operating the breakers via front panel keypad
– Changing the state of virtual inputs
– Clearing the event records 4
– Clearing the oscillography records
– Clearing fault reports
– Changing the date and time
– Clearing the breaker arcing current
– Clearing energy records
– Clearing the data logger
– Clearing the user-programmable pushbutton states
To enter the initial setting or command password:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE right arrow until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE down arrow until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE right arrow until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
 SECURITY ACCESS LEVEL:
  Restricted

 CHANGE LOCAL CHANGE COMMAND


  PASSWORDS  PASSWORD: No

CHANGE SETTING
 PASSWORD: No

5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change the
selection to “Yes.”
6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.
7. Type in a password and press the ENTER key.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-61


FRONT PANEL INTERFACE CHAPTER 4: INTERFACES

8. When VERIFY NEW PASSWORD displays, re-type the password and press ENTER.
CHANGE SETTING
PASSWORD: No

CHANGE SETTING ENTER NEW VERIFY NEW


PASSWORD: Yes PASSWORD: ########## PASSWORD: ##########

NEW PASSWORD
HAS BEEN STORED

9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) password is active.

4.2.10.1 Resetting the password in a device without CyberSentry

EnerVista UR Setup
1. In Settings > Product Setup, click the CHANGE button for the Command Password or Setting Password.
2. The pop-up states “Password Status: Set”, confirming that the user has previously set a password. Type
“ChangeMe1#” in both the New Password and Confirm Password fields, and press OK.
4 3. If the device has not been logged into using the previously set password, a prompt will request that the previous
password should be entered. Do this and press OK.
4. A message will appear confirming that this was a valid password - click OK.
5. A pop-up will now appear confirming “Password Status: Default” (i.e. the password is reset to the default
“ChangeMe1#”) and prompting for the new password. Type the new password, confirm it in the next field, then click
OK.

Front panel
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE right arrow until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE down arrow until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE right arrow until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change the
selection to “Yes”.
6. Type “ChangeMe1#” and press the ENTER key. This will clear the current password and make “ChangeMe1#” the
password.
7. The display will prompt you to ENTER CURRENT PASSWORD. Type in a new password and press the ENTER key.

4.2.11 Invalid password entry


By default, when an incorrect Command or Setting password has been entered via the front panel three times within five
minutes, the LOCAL ACCESS DENIED FlexLogic operand is set to “On” and the F60 does not allow settings or command
level access via the front panel for five minutes.
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within five minutes, the REMOTE ACCESS DENIED FlexLogic operand is set to “On” and the F60 does not
allow settings or command access via the any external communications interface for five minutes. The REMOTE
ACCESS DENIED FlexLogic operand is set to “Off” after five minutes for a Command password or 30 minutes for a
Settings password.
These default settings can be changed in EnerVista under Settings > Product Setup > Security.

4-62 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES LOGIC DIAGRAMS

4.3 Logic diagrams


Logic diagrams in this instruction manual provide an overview of function and settings. A logic diagram is based on
• Inputs-on the left side, which are setting and operands
• Logical gates, which is Boolean algebra to combine logical lines using AND, OR, NOT, and other gates to get a new
logical state
• Logical operators, which are timers, one-shot operations, latches, and so on
• Outputs-on the right side, which are products of the manipulations with inputs, logical gates, and logical operators to
produce new operands and define the output state of the element
True and false values are denoted by 1 and 0 respectively. A function usually is high/on/enabled when 1.
Reading from right to left in the following diagram, the TRIP BUS 1 OP and TRIP BUS 1 PKP FlexLogic operands on the
right side are triggered when either the settings or reset latch in the middle of the diagram is triggered. When this applies,
the TRIP BUS 1 OP operand is triggered after the delay set by the TRIP BUS 1 PICKUP DELAY or TRIP BUS 1 RESET DELAY
setting, while the TRIP BUS 1 PKP operand initiates immediately. The settings or reset latch in the middle of the diagram
is triggered as follows.
• For the reset, one of three conditions are required to meet the OR requirement shown at the bottom left. That is, the
TRIP BUS 1 LATCHING setting must be 0=Disabled (which is negated by the NOT function to become 1=Enabled), output
from the TRIP BUS 1 RESET FlexLogic operand must be 1, or output from the RESET OP FlexLogic operand must be 4
1.
• For the settings, one of 16 input conditions at the top left must be met for the OR, the TRIP BUS 1 FUNCTION must be
Enabled, and the TRIP BUS 1 BLOCK output must output as 0, which is then negated/reversed by NOT to become 1.
Table 4-2: Logic diagram symbols
Symbol Description
= Off Output from FlexLogic operand, so user-defined
= Enabled 1 = Enabled and 0 = Disabled
OR Any function input on the left side satisfies the condition
AND All functions input on the left side are required to satisfy the condition
 Not. Negates/reverses the output, for example 0 becomes 1.
 Connection
S, R Set, Reset
TPKP Timer pickup. Triggered by the settings latch in the diagram.
TRST Timer reset. Triggered by the reset latch in the diagram.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-63


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Figure 4-65: Logic diagram


SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***

DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R

SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off

SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET

4 = Off
OR

FLEXLOGIC OPERAND
RESET OP 842023A1.CDR

4.4 FlexLogic design using Engineer


The IED internally uses the FlexLogic equations. EnerVista Engineer provides a graphical way to design the logic. When the
user presses “compile” in Logic Designer, the software converts the graphical logic into equations and updates the
FlexLogic Equations.
There are two ways to create, edit and maintain the FlexLogic equations:
1. Using the FlexLogic Equation Editor available at FlexLogic > FlexLogic Equation Editor
2. Using the Logic Designer available at Engineer > Logic Designer

EnerVista Engineer is only available through the offline window of the EnerVista UR Setup.
FlexLogic Equation Editor and Logic Designer are designed to be mutually exclusive as using them interchangeably
to create, edit and maintain the FlexLogic equations may cause inconsistencies in the resulting equations. The user
is recommended to use only one of the two methods throughout the process.
Parts of EnerVista Viewpoint Engineer software are integrated in the EnerVista UR Setup software. Engineer can be used to
create and modify FlexLogic that is used by a device, such as to monitor output, monitor triggers, and create self-tests.
Features include
• Automatically displays existing FlexLogic
• Drag-and-drop interface
• Open multiple tabs and edit simultaneously
• Display symbols in IEC, ISO, or UR formats
• Export a diagram as BMP file or copy it to the clipboard for import into other applications
• Scale and print files in various paper sizes
• Works with all UR firmware versions
The figure shows an example where several inputs are used to trigger an output. With the OR function, any one of the
inputs can trigger the output.

4-64 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Figure 4-66: Inputs triggering output in Engineer

The process is as follows:


• Modify or create a logic diagram in the Offline Window area of the EnerVista UR Setup software
• Compile it and troubleshoot any errors
• The logic populates automatically into the FlexLogic Equation Editor
• Upload the file to the live device
• Monitor the output
This section explains how to use Engineer. It outlines the following topics:
• Design logic
• Send file to and from device
• Monitor logic
• View front panel
• Generate connectivity report
• Preferences

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-65


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

• Toolbars

4.4.1 Design logic


FlexLogic can be created with a block diagram. Note that although work is completed in the Offline Window area of the
software, communication occurs with the online device, for example when switching to monitoring mode.
The following procedures are outlined:
• Examples
• Add existing FlexLogic equations
• Create a logic diagram/sheet
• Rapidly add logic blocks in sequence
• Connect two logic diagrams/sheets
• Optimize the logic
• Change logic order
• Search logic
• Exclude sheet from compile

4 4.4.1.1 Examples
The symbols are displayed in the UR format.

Create oscillography trigger every three minutes


Figure 4-67: Three-minute timer turns on LED for 10 seconds

Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, the first and second virtual outputs are named
OscTrigger
Top logic — Three-minute timer trigger
Bottom logic — Turn on LED 1 for 10 seconds when the trigger starts

Create data logger trigger every seven minutes


Figure 4-68: Seven-minute timer turns on LED for 10 seconds

Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger
Top logic — Seven-minute timer trigger
Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts

4-66 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Create events every minute, then every 100 ms


Figure 4-69: One-minute timer turns on LED and creates events every 100 ms

Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual output 5 is named EVStart, 6 is named
EVTriggered, and 7 is named EVMakeEvent 4
Top logic — One-minute timer trigger
Middle logic — Turn on LED 17 for 10 seconds when trigger starts
Bottom logic — Create events at 100 ms intervals for the same 10 second period

4.4.1.2 Add existing FlexLogic equations


A logic diagram can be created using existing FlexLogic equations (this section) or by creating new ones (next section).

FlexLogic Equation Editor and Logic Designer are designed to be mutually exclusive as using them interchangeably
to create, edit and maintain the FlexLogic equations may cause inconsistencies in the resulting equations. The user
is recommended to use only one of the two methods throughout the process.
To create a logic diagram using existing FlexLogic equations:
1. In the Offline Window area, modify the FlexLogic for the device under FlexLogic > FlexLogic Equation Editor. If the
device is not listed, right-click the device in the Online Window area and select the Add Device to Offline Window
option.
Upon saving the modified FlexLogic, a yellow icon appears for the device in the Offline Window area to indicate that
the logic differs from the Online device.
2. In the Offline Window area, access Engineer for the device, then Logic Designer. The logic opens.
3. Click the Edit > Auto Populate Workbook menu item. If the software prompts if you want to keep or discard existing
sheets, either is acceptable, with the older excluded sheeted being denoted by brackets, such as < Sheet 1 >. The logic
displays in the various tabs. The FlexLogic created in the equation editor appears in Sheet 1, for example.

4.4.1.3 Create logic diagram


Upon access of the Logic Designer, the FlexLogic equations of the device display. You can create new logic in new sheets or
modify the ones that display.
This procedure uses input / output logic as an example.
1. In the Offline Window area, access Engineer for the device, then Logic Designer. If the device is not listed, right-click
the device in the Online Window area and select the Add Device to Offline Window option.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-67


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Figure 4-70: Access Engineer in the Offline Window area

4 A default block diagram opens that shows 48 inputs (boxes) and 48 user-programmable LEDs (circles).
For the graphical front panel, no LEDs can be added to the window and the LEDs are removed when opening any
existing files. For these existing files with the LEDs removed, save the file without them.
Figure 4-71: Default view of FlexLogic designer

2. Optionally delete the default logic diagram by right-clicking its tab at the bottom of the window and selecting Delete.
3. To add a blank sheet, click Edit > Add Sheet. A new tab displays. Or use the last tab displayed, which is a blank sheet.
4. Optionally right-click the new tab and Rename it.
5. Add the input blocks to the logic diagram. For example, click the I/O Tokens tab on the right, click the Input element,

4-68 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

then click in the logic sheet to add it. Or drag-and-drop it.


6. Double-click the block on the sheet to configure it, selecting from the two drop-down lists. The figure shows that
virtual input 61 is being added. The View Associated Screen button opens its settings window.
Figure 4-72: Configuring an input block

7. Add the output blocks to the logic diagram. For example, click the I/O Tokens tab, click the Virtual Output element, 4
then click in the logic sheet to add it. Double-click the block on the sheet to configure it. For the name, make it unique.
The figure shows virtual output 61 is being added, with a suffix of "io" added to the name to make it unique. Note that
the outline color of a block is red until it is configured, and that this properties window varies by block and the
selectable options by order code.
Figure 4-73: Configuring an output block

8. Connect the input blocks to the output blocks by drawing a line as follows. Click at the end of one block and drag the
line to the next block. Or click the Drawing Tools tab, then select the Line option. The cursor needs to be at the
connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-69


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Figure 4-74: Completed inputs and outputs

9. Add any remaining blocks or information. Right-click a block to copy and paste it. Notes are as follows.
Add a text box — Drawing Tools > Text
Add a FlexElement — Elements > FlexElement. An analog input is expected where a small arrow head shows in the
box.
Figure 4-75: FlexElement accepts analog inputs on left side where arrow heads display

Add an Element — Elements tab. Available elements reflect the product, for example the Control Elements category.
Figure 4-76: Elements reflect Control Elements

10. Check for any blocks that have a red outline. These are invalid. Fix them before continuing, for example by configuring
them.
11. Compile the logic diagram to check for errors by clicking the Compile button at the bottom left or by pressing the F7
key.
If prompted about a message about sorting, click Yes to apply the default (for this example), which can be automatic
sorting based on an algorithm that applies fastest execution time.
With successful compiling, the file is saved and the FlexLogic equations populate automatically. Scroll up through the
compile messages, with the red errors being the only messages that require fixing before proceeding.
The figure shows that we forgot to add the "Io" suffix to the names of virtual outputs 62 and 63, as indicated by
"Warning: Virtual output xx using default name." This warning is a minor warning.
The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the
View Associated Screen button, enable the setting, save, and recompile.
The output and messages are explained in the next section.

4-70 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Some information displayed in the compile messages updates automatically, for example messages after a device is
unplugged.
Figure 4-77: Compile and check the logic

12. View the FlexLogic equations by navigating in the Offline Window area to FlexLogic > FlexLogic Equation Editor. The
window opens with the entries displayed in the next tab.
Figure 4-78: Logic displayed in FlexLogic Equation Editor
4

13. Save the work.


The logic diagram has been created and the FlexLogic equations populated. The next steps are to upload the file to the
device and to monitor the device.

4.4.1.4 Compiled results and warning messages


When a yellow caution symbol displays in the Offline Window area, it means that the settings file is not synchronized with
the online device. Right-click the device in the Offline Window area, and select the Update SCL files option. SCL refers to
the Substation Configuration Language. An Instantiated IED capability description (IID) file is an example of an SCL file and
contains the actual settings on a UR device.
Figure 4-79: Settings files not synchronized between offline and online files

When the Update SCL files option is selected, the CID and IID files in the device folder are updated by the user
configuration in the IEC 61850 panel and thereby become synchronized. The CID file and the IID file (depending on the
preference 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-71


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.
Any FlexLogic equations entered in the Offline Window area are erased. The logic drawn in the Logic Designer window in
Engineer in the Offline Window area remain. The warning icon disappears after updating.
The following information is contained in the compile window.
Figure 4-80: Compiled results

Number of Lines Saved — The number of compiled logic lines eliminated by using the optimization algorithm, as set in the
Optimize Compiled Output option of the Preferences. In the example shown, no lines were saved because the optimizer is
disabled.
FlexLogic Lines — The number of lines that the compiled logic uses, for example seven of 512 available.
Virtual Output equations — The number of FlexLogic equations used in the Logic Designer window.
Timers used — The number of timers used in the Logic Designer window.
Memory Used — The percent of memory used in the Logic Designer window.

Errors
Table 4-3: Errors from compiling
Category Block or gate Message Description
affected
Error All Number of lines (nnn) exceeds The compiled result exceeds the limit of 512. Reduce the number of
maximum limit of 512 equations to 512 or less.
Error Tag-In Tag-in not configured (TAG_ID, A Tag-In is connected to a circuit but the Tag-In is not referencing an
SheetReference) existing Tag-Out
Error 1 Shots One Shot is over limit The number of One-Shots contained within all of the VO blocks has
(SYMBOL_ID, SheetReference) exceeded the maximum allowed for the firmware revision. This value can
either be 0 or 32.
Error =VO VO has no inputs (VO_ID, A Virtual Output block is located within the FlexLogic diagram and there
SheetReference) is no block connected as input to it. Connect and identify the inputs.

4-72 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Category Block or gate Message Description


affected
Error Timer Timer used more than once The same timer is used in more than one place in the editor. This means
(TIMER_ID, SheetReference) either the circuit that the Timer belongs to has been branched, or the
Timer has been duplicated.
Error Input Unrecognized Parameter An Input symbol is configured to an item that is not recognized by the
(SYMBOL_ID,Name,SheetRefere current order code and version. Possible cause: The order code and/or
nce) version of the settings file was converted causing the input parameter to
become unavailable.

Warnings
When using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that the
Reset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the front
panel of the relay or by sending a Reset command through communications.
Table 4-4: Warning messages from compiling
Category Block or Message Description
gate
affected
Minor warning Input Input set to unused VO An Input symbol is using an unassigned Virtual Output

Major warning Tag-Out


(SYMBOL_ID,Name,Sheet)
Tag-out not connected A Tag-Out symbol has no input
4
(TAG_ID,Sheet)
Major warning All Symbol not connected A symbol’s input and/or output is not connected and is not part of a
(SYMBOL_ID,Name,Sheet) VO block. Draw the input and/or output to the block.
Minor warning =VO Virtual Output n using default The Assigned Virtual Output is using the default name. Change the
name (VO_ID,Sheet) name.
Minor warning Input Input using default name An Input symbol is using a Contact Input, Contact Output, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, or Digital Counter set to the default name.
Change the name so that it is unique.
Setting warning Input Input using disabled feature An Input symbol is using a disabled Virtual Input, Contact Input, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, Digital Counter, Control Pushbutton,
Programmable Pushbutton, Contact Output, or Protection/Monitoring
Element. Enable it and try again.
Major warning Input Input set to OFF An Input symbol is set to OFF
(SYMBOL_ID,Sheet)
Major warning Input Input set to ON An Input symbol is set to ON
(SYMBOL_ID,Sheet)
Setting warning Input Contact Output Operate is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)
Setting warning Input Contact Output Seal-In is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)

4.4.1.5 Rapidly add logic blocks in sequence


Blocks are added by clicking an element then clicking in the drawing area, or by dragging and dropping the element onto
the canvas. Blocks can be added rapidly in sequence, for example when you have inputs 1 to 10, without having to select
the element each time.
1. In Engineer, click File > Preferences. The window opens.
2. Click the Editor entry.
3. Enable the Repeat Symbol check box.
4. Click the Ok button to save and exit from the window.
5. In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and
so on.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-73


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

4.4.1.6 Connect two logic diagrams


When the logic is complex and requires two sheets, for example, these two sheets can be connected. By connecting them,
the logic is continuous from one sheet to the next.
1. In the first sheet, click the I/O Tokens tab.
2. Scroll to the bottom, and click and drag the Tag Out element to the sheet where the next sheet is to connect.
3. Double-click the element and in the window that opens, give it a name, such as "To Sheet 2" or "To IO Sheet 2."
Figure 4-81: Connecting sheet 1 to sheet 2

4. In the second sheet, click and drag the Tag In element to the sheet where the first sheet is to connect.
5. Double-click the element and in the window that opens, select the first sheet from the drop-down list to connect the
two sheets.
6. Save the work.

4.4.1.7 Optimize the logic


The number of available FlexLogic entries depends on firmware, for example 515 or 1024 lines. The software can
automatically optimize a logic diagram to reduce space and free up entries.
1. In Engineer, enable the optimization check box in the Compile tab. With this option enabled, the software
automatically optimizes a logic diagram to reduce space and free up FlexLogic entries.
2. Run the compiler by clicking the Compile button. The number of saved lines displays in the Optimization Summary.
Changes also display when the FlexLogic Equation Editor is accessed. The logic diagram does not change. In the
example shown, no lines were saved to free up space.
Figure 4-82: Code optimization results

4.4.1.8 Change logic order


The order in which the FlexLogic is populated in the FlexLogic Equation Editor window depends on settings.

4-74 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

First, when automatic sorting is not enabled, the sequence in which the blocks were drawn is followed.
Second, the order in which equations are executed can be manually changed, as outlined here.
Third, automatic sorting can be set in preferences, as outlined here. It is enabled by default and means that an algorithm is
implemented to give best results and quickest performance, For example, the block with the fastest execution time is
entered first in the FlexLogic. When two block functions have the same execution time the block drawn first displays first in
the FlexLogic. For example, drawing input 61 to output 61, then input 62 to output 62 causes the input/output 61 to be
entered into the FlexLogic first. Automatic sorting takes precedence over manual sort; if you enable this option, manual
sorting is not implemented.
To manually change logic order:
1. In the compile area, click the VO Order tab.
2. If the window is blank, click the Refresh button.
3. Select an entry and click the up or down arrow. To cancel any manual changes, click the Sort or Refresh button.
4. Recompile. The change is not executed or saved if automatic sorting is enabled.
Figure 4-83: Ordering FlexLogic entries

To set automatic sorting:


1. In Engineer, under File > Preferences, select the Compiler option. The Automatically Sort VOs option means that the
block with the fastest execution time is entered first in the FlexLogic. When two block functions have the same
execution time the block drawn first displays first in the FlexLogic. For example, drawing input 61 to output 61, then
input 62 to output 62 causes the input/output 61 to be entered into the FlexLogic first.

4.4.1.9 Search logic


Items that can be searched in a logic diagram include gates, Input, Contact Input, Contact Output, Timer, Virtual Output,
Tag In, Tag Out, and User-programmable LED. A search can be performed while designing or monitoring.
1. In the compiler area of Engineer, click the Search tab.
2. Use one of the following methods to set search criteria:
– Select an element from the first drop-down list. Results display automatically.
– Type in the second text string box, or select any of the 32 previous searches from the drop-down list. Click the
Search button. Any results display.
The search applies to all tabs, not just the active tab.
3. Double-click a search result to view the item.
Figure 4-84: Search function

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-75


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

You can also select an element from the drop-down list on the toolbar. It is then highlighted in the logic diagram.

4.4.1.10 Exclude sheet from compile


While designing the FlexLogic equations, entire sheets can be removed from the compile logic. This allows the user to test
various schemes by placing schemes on separate sheets and including either sheet at compile time.
1. In the Logic Designer window, right-click the tab and select the Exclude from Compile option so that the check mark
displays. When sheets are excluded, a message displays with each compile that "excluded sheets will not be reflected
in the RPN." An excluded sheet is denoted with end brackets, similar to < Sheet 1 >.
Figure 4-85: Excluding a tab from compiling

Figure 4-86: Tab excluded from compiling

4.4.2 Send file to and from device


With the logic diagram created, compiled, and errors eliminated, the FlexLogic can be sent to a live device. And,
conversely, a file from a live device can be added to the Offline Window area for additional work.
To send a file to a device:
1. In the Offline Window area of the software, right-click the device name and select the Write Settings to Device option.
A prompt can appear that the URS file has been repaired; acknowledge the message.
2. When a window opens, select the device to which you want to send the file, then click the Send button and confirm.
The order codes and IEC 61850 edition must match. The file is sent to the live device. Any errors can be viewed in the
log file at the prompt.

To import a file from a device:


1. Close all open files in Engineer that relate to the device, else a message displays to that effect, for example to close
the FlexLogic view associated with the file. When the file is not associated with a live device, a message displays to
that effect; you need to identify the device to which you want to send the file. The order codes must match.
2. Right-click the device in the Online Window area and select the Add Device to Offline Window option. After you enter
a name for the file, it is written to the Offline Window area.

4-76 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

4.4.3 Monitor logic


After creating the logic diagram, validating it, and uploading the FlexLogic to a device, the results from the device can be
viewed.
The following checks are performed automatically when switching from design to monitoring, and prompts display when
necessary:
• Verify that the order code of the linked relay matches the settings file
• Verify that the version of the linked relay matches the settings file
• Verify that the FlexLogic Equation Editor of the linked relay matches the settings file. Solution: Compile the FlexLogic
logic diagram and send the settings file to the relay.
• Verify that the FlexLogic Timers of the linked relay match the settings file. Solution: Compile the FlexLogic logic
diagram and send the settings file to the relay.
• If the settings file contains a serial number lock, then verify that the serial number of the linked relay matches the
settings file
To view results:
1. In the Offline Window area of the software, expand the Engineer entry for the device.
2. Double-click the Logic Designer entry and Compile the logic.
3. Double-click the Logic Monitor entry, or click the M button in the toolbar at the top of the window. With successful 4
launch, the logic displays and a green indicator displays at the bottom of the tab.
When the file is not associated with a live device, a message displays to that effect; you need to identify the device to
which you want to send the file. The order codes must match between the Offline Window and the Online Window.
When the device is offline, a message indicates problems communicating with the device.
When the devices are not synchronized, a message indicates the FlexLogic does not match the settings file. To send
the offline file to the device, right-click the device name and select the Write Settings to Device option.
When the state of a symbol is OFF, the symbol is shown in the default color or no color.
When a symbol's state changes to ON, the symbol and connection line turns green.
The state of some symbols can either be unknown or the state transitions faster than the update interval. For these
two cases, the state of the symbol is considered 'UNKNOWN' and the symbol is outlined in red.
The colors for the ON and Unknown state can be customized in the Preferences.
The figure shows that the software is communicating with devices (square green indicator) and that a minor error is
present (green box outline). In this case, the battery is weak and needs to be replaced. This can be viewed as the
Replace Battery message on the front panel of the device and in the EnerVista software under Actual Values > Front
Panel > Front Panel or Display/Keypad.
Figure 4-87: Monitoring a device, with minor error caused by weak battery

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-77


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

4.4.4 View front panel and print labels


This window displays the LEDs that are on the front panel. You can create labels and print them for the device. You do not
use the window to add text labels and upload them to the device. Custom labelling is also outlined earlier in this chapter;
see the Front Panel Labelling section.
To view the front panel:
1. In the Offline Window area of the software, expand the Engineer entry for the device.
2. Double-click the Front Panel Report entry. The report displays. The Device Summary is read from the settings file and
cannot be changed. The LEDs and pushbuttons display below the summary.
3. To save the report, click File > Save As, enter a file name, and select the front panel report (FPR), JPG, or PDF format.
Figure 4-88: Front panel display in Engineer

To print labels:
1. In the Front Panel Report window, double-click an LED or pushbutton and enter text.
2. To print the labels, click the Print icon on the toolbar.
3. To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format.
4. Use the instructions in the second tab of the window to add the labels to the physical device.

4.4.5 Generate connectivity report


This report displays basic information about a device, such as order code, port numbers, inputs and outputs. You can use it
to create a PDF file of basic information. The report is based on CID and/or IID files, and not the system or full SCD. All
device details including Remote Inputs, Remote Outputs, and Analog Inputs/Outputs are indicated, including quantities
used and available.
To display a device report:
1. In the Offline Window area of the software, expand the Engineer entry for the device.
2. Double-click the Device Connectivity Report entry. The report displays.
3. To save as a PDF file, click File > Save As.

4-78 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Figure 4-89: Device Connectivity Report

4.4.6 Preferences
Preferences determine functionality. As such, you are encouraged to review them. This section outlines some options
available in the menus and preference panels.
Access them in the Logic Designer panel under the View menu and under File > Preferences. The Logic Designer and
Logic Monitor preferences are outlined here, not all preferences for a device.

4.4.6.1 View menu


View > Toolbar > Advanced Actions — Active when in Logic Designer. Toggles a toolbar to nudge, rotate, flip, or change
the order of an element.
View > Show Unused Pins — Enable to display unconnected pins. Disable to eliminate unconnected pins from the view, for
example when printing.
Figure 4-90: Unused pins on and off

4.4.6.2 Logic designer


The path is File > Preferences > Logic Designer.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-79


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Workbook Setup

Size and Units


Size and Units — Changes the size of diagram area displayed in Engineer. If you set the size to be smaller than an existing
logic diagram, the content is cut off.

WorkBook
Print Scale — The scale for logic diagram when printing. Scaling a large diagram to 200 percent, for example, results in the
diagram being cut off.
Orphan Protection — When enabled, the printing output prevents Virtual Output circuits from spanning more than a single
page. The largest Virtual Output circuit is scaled to fit on a single page and all remaining Virtual Output circuits are scaled
so that all circuits are printed using the same scale.
Show Title Block — When enabled, places an information box at the bottom right of the diagram when printing. Enter the
information in the File Information panel.
Show Sheet Name — When enabled, shows Sheet 1, Sheet 2, or any other name at the top of the logic diagram when
printing.
Start Sheet On New Page — Places the sheet on the next page when printing.
4 Show Notes Selection — When other than None, prints the text from any information notes added to the document (under
Drawing Tools tab > Note). The text is printed after the logic diagram.

File Information
The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is
enabled. Note the option to change the logo from the GE logo to your company logo.

Display
The panel sets how the element boxes display. The figure shows how an AND gate displays when the UR default, IEC, or
ISO symbol type is selected.
Figure 4-91: AND gate varies by standard selected

Symbol Style — IEC, ISO, UR Setup — Sets how the gates display in the logic diagram.
Symbol Color — When set to Black & White, only logic blocks with issues continue to display red.
Zoom Operation — Determines what happens when the View > Zoom functions are used. When set to Sheet Only and the
zoom is changed, the single tab changes. When set to Workbook, all tabs change.

Editor
Repeat Symbol — Enable this feature to add element blocks rapidly in sequence, for example when you have inputs 1 to
10, without having to select the element each time. Select the element block from the toolbox, click the diagram, then
continue to click to add additional blocks.
Use first available VO / Timer — When enabled and you copy and paste a virtual output or timer element, the numbering
continues in sequence. For example, you copy timer 5 and paste it as timer 6. When disabled and you copy and paste a
virtual output or timer element, the same number is used. For example, you copy timer 5 and paste it as timer 5.
Auto-Save Logic Designer every x minutes — Logic diagrams with changes are saved automatically according to this
interval. The range is 5 minutes (default) to 30 minutes. With auto-save, the file extension of the saved file is .auto. This file
remains until you save the file manually.

4-80 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Auto Populate
These options work in the Edit > Auto Populate Workbook function.
VOs per Worksheet — When an existing settings file is opened in the Logic Designer, the Logic Designer populates the
canvas and attempts to evenly distribute the Virtual Output circuits across multiple sheets. A value of 100 in this setting
places all FlexLogic equations on a single sheet until there are 100, then the next ones are placed on another sheet. A value
of 1 places each Virtual Output circuit on a separate sheet.
Show / FlexLogic Merge / Show Unused — If Show Contact Outputs and Show LEDs are selected, for example, the function
places Contact Output and User-programmable LED symbols for settings that are configured. If you disable the LED check
boxes, then the LED tab/sheet does not display when you next open the Logic Designer window. The settings apply to all
products, not just the active window when it is next opened. Close then reopen the Logic Designer window for the setting
to take effect.

Compiler
Show Warnings — Options to filter the messages that display when logic compiles.
Minor — Enable to display minor errors. An example is using the default values of an element added to the diagram, such
as the name of the element. An example is "Warning: Virtual output xx using default name," for which you simply click into
the element to rename it.
Major — Enable to display major errors. Examples are an input that does not have a corresponding output, using disabled
features, and failing to connect a symbol. Fix these errors.
4
Setting — Enable to display error message related to settings, such as an improperly configured setting, such as using ON
or OFF.
Automatically Sort VOs — When enabled, the logic is compiled with an algorithm to give best results and quickest
performance, for example the fastest logic first. The fastest logic displays in the FlexLogic Equation Editor output as the
first entries in the table. Use sorting when virtual outputs have dependencies on other virtual outputs. This setting takes
precedence over order set manually in the VO Order tab in the compiler.
When disabled, the sequence in which the blocks were drawn is followed.
Optimize Compiled Output — Not applicable. Use the check box outlined earlier in the Optimize the Logic section.

4.4.6.3 Logic monitor

Display
The software displays the color specified when an element is on. There is no color when the element is off.
The software displays another color when the status cannot be determined and is unknown.

Timing
Timing Information can be displayed in the monitoring window. This timing information is only an approximate
representation of how Engineer sees transitions. Use the device's Event Record to view accurate timing information.
The timing information can also be streamed to a comma-separated values (CSV) spreadsheet.
The timing information displayed and recorded can be filtered based on six categories. If a category is not selected, any
timing information related to that category does not display and is not recorded to the CSV file.
Show Timing Information in Output Window — Enable to display times in the monitoring window.
Because of the update rate of the Logic Monitoring, the timing information cannot be used as an accurate representation
of the events that occur within the relay. Use instead the device's event record. Timing information can be delayed by 30
seconds.
Save Timing Information to CSV File — Enable to write timing information in a spreadsheet. The timing information is
recorded in a text file that uses commas to separate each of the fields. This file uses the extension CSV that is supported by
any spreadsheet application.
Every change written to the CSV file requires a timestamp.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-81


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

The format for the timing information in the output window is as follows:
yyyy/mm/dd hh:dd:ss
devicename offline
yyyy/mm/dd hh:dd:ss
devicename ONLINE
yyyy/mm/dd hh:dd:ss
VO1: Virt Out 1- 0
VI4: Virt In 4- 1
DI3: Direct In 3- 0
RI2: Remote In 2- 1
H5a: Contact In 1- 1
H1: Contact Output 1- 0

Data is only appended to the CSV file. The format for the data is as follows:
yyyy/mm/dd hh:dd:ss, devicename, offline
4 yyyy/mm/dd hh:dd:ss, devicename, ONLINE
yyyy/mm/dd hh:dd:ss, VO1: Virt Out 1, 0
yyyy/mm/dd hh:dd:ss, VI4: Virt In 4, 1
yyyy/mm/dd hh:dd:ss, DI3: Direct In 3, 0
yyyy/mm/dd hh:dd:ss, RI2: Remote In 2, 1
yyyy/mm/dd hh:dd:ss, H5a: Contact In 1, 1
yyyy/mm/dd hh:dd:ss, H1: Contact Output 1, 0

Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status.

4.4.6.4 COMTRADE waveforms


Waveform files are viewable in the EnerVista software. The preferences are unrelated to Engineer and are outlined in the
UR Family Communications Guide.

4.4.7 Toolbars
These are toggled in the View > Toolbar menu.
The UR symbols are displayed for the toolbox icons. They change when the default setting is changed to IEC or ISO
symbols. The symbols displayed in the toolbox also vary by firmware version, reflecting what is supported for each release.

4.4.7.1 FlexLogic Editor toolbar

New Device Create a new settings file

Open File Open an existing settings file in the URS, CID, or IID format

Save FlexLogic Save the Logic Designer diagram

4-82 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

PDF Report Create a PDF document from Logic Designer diagram(s). Settings can be
changed under File > Preferences > Workbook Setup.
Toggle Compile Window Display or hide the compile window area

Sort Order Select to change the sort order of the Virtual Output list to the right of the
icon. Virtual Outputs can be sorted numerically in ascending and
descending order based on numbers and names.
Select VO to View (x - x) Select a Virtual Output to locate and select it in the workbook. Each Virtual
Output listed also contains the name of the sheet where the Virtual Output
is located.
Edit Mode Switch to Logic Designer mode
Logic Designer
Monitor Mode Switch to Logic Monitor mode
Logic Monitor
Turn On ALL Communications Turn on all communications to all Logic Designer diagrams that are in the
monitoring mode. Default upon each launch of Engineer.
Turn Off All Communications Turn off all communications to all Logic Designer diagrams that are in the
monitoring mode. This is a legacy function for serial communication to turn
off communication to devices. Turning off communication applies to the
current session only. When you re-launch the EnerVista software,
communication is on by default.
4
4.4.7.2 Token Toolbox

Drawing Tools

Draw a line. Click and drag to draw.

Draw multiple joined lines. Click and drag for each line. Double-click to finish.

Draw multi-sided object. Click for each line. Double-click to finish.

Draw four-sided object. Click and drag to draw.

Draw multiple curves. Click for each line. Double-click to finish.

Draw multiple, closed curves. Click for each line. Double-click to finish.

Draw oval or circle. Click and drag to draw.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-83


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Add text box with rectangle around it. Click to add. Double-click it to change text.

Add figure. Select file in the window that opens, then click on diagram canvas to add figure.

Add note icon and text. Click to add. Double-click to edit the title and text.

I/O Tokens
These are parts used in FlexLogic equations. They are the inputs and outputs of the Virtual Output equations. The display
can vary from that shown here.

Input symbol that can be configured to any FlexLogic operand value

Remote inputs from other devices

Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and
cannot be used simultaneously.

Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously.

FlexAnalog symbol that can be used as the input to a FlexElement or use the FlexAnalog symbol to monitor an actual
value when in logic Monitoring mode

Contact Input Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Input

Contact Output Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Output.
The Operate and Seal-In settings can be configured graphically.

The Non-Volatile Latch is similar to the Input symbol but is restricted to the operands associated with a Non-Volatile
Latch. The Set and Reset settings can be configured graphically.

4-84 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

The final output of an equation is a numbered register called a virtual output. Virtual outputs can be used as an input
operand in any equation, including the equation that generates the output, as a seal-in or other type of feedback.

Place and configure a Remote Output. The UR's order code and firmware version then determine the availability of the
Remote Output.

Place and configure a Direct Output. The UR's order code and firmware version then determine the availability of the
Direct Output to another UR device.

Place and configure a Teleprotection Output. The UR's order code and firmware version then determine the availability
of the Teleprotection Output.

Place a User Programmable LED in the Logic Designer diagram. Not applicable when using a graphical front panel.

A Tag Out can be used in 1 of 2 ways. The first use of the Tag Out is to break up logic that needs to span several sheets.
The second use of the Tag Out is to associate a frequently used block of code with the Tag Out and then repeatedly use 4
the same block of code using a Tag In. When a Tag Out is referenced more than once, the Tag Out is replaced with a
Virtual Output during the compile phase.
Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram.

Boolean Tokens
These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations.
The display can vary from that shown here.

Place an OR gate in the Logic Designer diagram. Only one action needs to occur. Any function input on the left side
satisfies the condition.
The number of inputs is configurable from two to 16.

Place an AND gate in the Logic Designer diagram. Multiple actions need to occur. All functions input on the left side are
required to satisfy the condition.
The number of inputs is configurable from two to 16.

Place a NOR gate in the Logic Designer diagram. Gives the value of one when all input operands have a value of zero
and otherwise gives a value of zero. It gives an output signal when there are no input signals. An inverter that reverses
the logic state.
The number of inputs is configurable from two to 16.
Place a NAND gate in the Logic Designer diagram. Gives the value of zero when all input operands have a value of one
and otherwise gives a value of one. It gives an output signal until all signals are present on its inputs. An inverter that
reverses the logic state.
The number of inputs is configurable from two to 16.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-85


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Place a XOR gate in the Logic Designer diagram, which is two exclusive OR gates. Only one action needs to occur. If
there are two inputs or there is no input, there is no output.

Place a NOT gate in the Logic Designer diagram. Gives the value of one when the input operand has a value of zero and
otherwise gives a value of zero. It gives an output signal when there is no input signal. An inverter that reverses the
logic state.

Place a latch in the Logic Designer diagram. A latch has two inputs and one output. One input is the Set input, and
other input is the Reset input.

Place a positive one shot symbol that responds to a positive going edge in the Logic Designer diagram. A "one shot" is a
single input gate that generates a pulse ins response to an edge on the input.

Place a negative one shot symbol that responds to a negative going edge in the Logic Designer diagram

Place a positive one shot and a negative one shot symbol in the Logic Designer diagram

4
Place a timer in the Logic Designer diagram

Elements
These blocks configure properties of the element or use element operands as input to FlexLogic equations.

Place and configure a FlexElement. A FlexElement is a universal comparator used to monitor any analog actual value
calculated by the relay or a net difference of any two analog actual values of the same type.

Place and configure the Settings Group settings

Place and configure a Selector Switch element. Firmware version determines feature availability. The Selector Switch
element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic. The element provides for two control inputs.

Place and configure a Digital Element. A Digital Element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state.

4-86 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 4: INTERFACES FLEXLOGIC DESIGN USING ENGINEER

Place and configure a Digital Counter element. A Digital Counter counts the number of state transitions
from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element.

4.4.7.3 Basic Actions toolbar

Select Select components. Click one component and hold down the CTRL key to select others.
Or click and drag an area that contains multiple components to select.
Edit Vertices Shows vertices points for the component selected (if the component support vertices
manipulation)
Properties Shows the properties of the selected component

Zoom Normal Zoom in and center the screen to the spot selected

Zoom to Fit Zoom in to a magnitude that fits your entire schema layout on your entire screen 4
Zoom Custom Zoom in on the components that you have selected

Pan Move the viewable area of your screen around the schema. To activate, select this tool
and then place the hand icon over and part of your schema. Click and drag the hand in
a direction to move around the schema.
Align Top, Middle, Bottom Align the selected components to the top, middle, or bottom of the reference
component
Align Left, Center, Right Align the selected components to the left, middle, or right of the reference component

Space Across Evenly space the selected components across a horizontal axis, starting from the far
left component and ending at the far right component
Space Down Evenly space the selected components across a vertical axis, starting from the top
component and ending at the bottom component
Same Width Set the width of the selected components to the same width as the reference
component
Same Height Set the height of the selected components to the same height as the reference
component
Same Size Set the width and height of the selected components to the same width and height of
the reference component

4.4.7.4 Advanced Actions toolbar

Only basic objects (lines, rectangles, ellipses) can be rotated and flipped.
Only objects from the Drawing Toolbar can be structured (grouped, ungrouped, forward, backward).
Nudge Up, Down, Left, Right Moves selected component one pixel upward, downward, left, right

Rotate Rotates selected component freely. Once selected, put your mouse cursor over the
component and move the component clockwise or counter-clockwise depending on
what you need.
Rotate Left, Right Rotates selected component 90 degrees counter-clockwise or clockwise

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-87


FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES

Flip Vertical Flips the selected component on the vertical axis

Flip Horizontal Flips the selected component on the horizontal axis

Group, Ungroup Combines all selected components into one combined entity. Ungroups them into
separate components.
Front, Back Moves current components to the absolute front or back of all viewable layers

Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy

4-88 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 5: Settings

Settings

This chapter outlines front panel and/or software settings. The relay is not taken out of service when saving settings; the
relay is taken out of service when a settings file is written to it.
Settings can be viewed remotely in a web browser by entering the IP address of the relay, accessing the Device
Information Menu option, then the Front-Panel Display Report option.
When indicated that a restart is required for a setting change to take effect, use the Maintenance > Reboot Relay
Command in the software.
Settings file conversion from previous firmware versions is supported. See the Maintenance chapter.

5.1 Settings menu

 SETTINGS  SECURITY See page 5-8


 PRODUCT SETUP  

 DISPLAY See page 5-28


   PROPERTIES

 GRAPHICAL FRONT PANEL Access in EnerVista


  See page 5-30

 CLEAR RELAY See page 5-43


  RECORDS

 COMMUNICATIONS See page 5-44


 

 MODBUS USER MAP See page 5-117


 

 REAL TIME See page 5-118


  CLOCK

 FAULT REPORTS See page 5-127


 

 OSCILLOGRAPHY See page 5-129


 

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-1


SETTINGS MENU CHAPTER 5: SETTINGS

 DATA LOGGER See page 5-132


 

 DEMAND See page 5-133


 

 USER-PROGRAMMABLE See page 5-134


  LEDS

 USER-PROGRAMMABLE See page 5-139


  SELF TESTS

 CONTROL See page 5-140


  PUSHBUTTONS

 USER-PROGRAMMABLE See page 5-141


  PUSHBUTTONS

 FLEX STATE See page 5-147


  PARAMETERS

 USER-DEFINABLE See page 5-148


  DISPLAYS

 DIRECT I/O See page 5-150


 

 TELEPROTECTION See page 5-156


 

 INSTALLATION See page 5-157


  

5  REMOTE RESOURCES
  

Access in EnerVista
See page 5-158

 SETTINGS  AC INPUTS See page 5-159


 SYSTEM SETUP  

 POWER SYSTEM See page 5-160


  

 SIGNAL SOURCES See page 5-162


 

 BREAKERS See page 5-166


 

 SWITCHES See page 5-175


 

 FLEXCURVES See page 5-183


 

 PHASOR MEASUREMENT See page 5-190


   UNIT

 PROCESS BUS  GENERAL See page 5-211


 MODULE  

 SV STREAM CONFIG Access in EnerVista


   See page 5-218

 SETTINGS  FLEXLOGIC See page 5-253


 FLEXLOGIC   EQUATION EDITOR

 FLEXLOGIC See page 5-253


   TIMERS

 FLEXELEMENTS See page 5-253


 

5-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SETTINGS MENU

 NON-VOLATILE See page 5-258


   LATCHES

 SETTINGS  SETTING GROUP 1 See page 5-260


 GROUPED ELEMENTS  

 SETTING GROUP 2
  

 SETTING GROUP 3
 

 SETTING GROUP 4
 

 SETTING GROUP 5
 

 SETTING GROUP 6
  

 SETTINGS  TRIP BUS See page 5-331


 CONTROL ELEMENTS  

 SETTING GROUPS See page 5-333


  

 SELECTOR SWITCH See page 5-335


 

 UNDERFREQUENCY See page 5-342


 

  OVERFREQUENCY

See page 5-343 5
 FREQUENCY RATE See page 5-344
  OF CHANGE

 SYNCHROCHECK See page 5-346


 

 AUTORECLOSE See page 5-351


 

 DIGITAL ELEMENTS See page 5-357


 

 DIGITAL COUNTERS See page 5-360


 

 MONITORING See page 5-362


  ELEMENTS

 COLD LOAD PICKUP See page 5-393


 

 PILOT SCHEMES See page 5-395


  

 SETTINGS  CONTACT INPUTS See page 5-400


 INPUTS / OUTPUTS  

 VIRTUAL INPUTS See page 5-402


  

 CONTACT OUTPUTS See page 5-403


 

 VIRTUAL OUTPUTS See page 5-407


 

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-3


OVERVIEW CHAPTER 5: SETTINGS

 RESETTING See page 5-407


 

 DIRECT INPUTS See page 5-408


 

 DIRECT OUTPUTS See page 5-408


 

 TELEPROTECTION See page 5-412


  

 SETTINGS  DCMA INPUTS See page 5-414


 TRANSDUCER I/O  

 RTD INPUTS See page 5-415


  

 DCMA OUTPUTS See page 5-416


  

 SETTINGS  IED MODE CONFIG See page 5-420


 TESTING  

 FORCE CONTACT See page 5-423


   INPUTS

 FORCE CONTACT See page 5-424


  OUTPUTS

 PMU See page 5-424


   TEST VALUES

5  SETTINGS
 SIMULATION   SUBSCRIBE TO
 SIMULATED VALUES
See page 5-426

 PUBLISH See page 5-428


  SIMULATED VALUES

5.2 Overview
5.2.1 Introduction to elements
For URs, the term element is used to describe a feature that is based around a comparator. The comparator is provided
with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to determine if the input is
within the defined range that sets the output to logic 1, also referred to as setting the flag. A single comparator can make
multiple tests and provide multiple outputs. For example, the time overcurrent comparator sets a pickup flag when the
current input is above the setting and sets an operate flag when the input current has been at a level above the pickup
setting for the time specified by the time-current curve settings. All comparators use analog actual values as the input.

An exception to this rule is digital elements, which use logic states as inputs.

Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on a logic diagram. This includes the inputs, settings, fixed logic, and the
output operands generated. The previous chapter explains how to read a logic diagram, and the abbreviations used in a
diagram are defined in the Abbreviations chapter.
Some settings are specified in per-unit (pu) calculated quantities:

5-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS OVERVIEW

pu quantity = (actual quantity) / (base quantity)


Where the current source is from a single current transformer (CT), the base quantity is the nominal secondary or primary
current of the CT. Use the secondary current base to convert per-unit settings to/from a secondary current value, and use
the primary current base to convert to/from a primary current value.
Where the current source is the sum of two or more CTs with different nominal primary current, the primary base quantity
is the largest nominal primary current. For example, if CT1 = 300 / 5 A and CT2 = 100 / 1 A, then in order to sum these, CT2
is scaled to the CT1 ratio. In this case, the base quantity is 300 A primary, 5 A secondary for CT1, and 300/(100/1) = 3 A
secondary for CT2.
For voltage elements, the primary base quantity is the nominal phase-to-phase primary voltage of the protected system
provided that the VT ratio setting is set to the nominal ratio of the VTs and the secondary voltage setting is set to the
phase-to-phase voltage seen by the relay when the voltage of the protected system in nominal. The UR uses the
convention that nominal voltages in a three-phase system are phase-to-phase voltages.
For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta-
connected VTs, the secondary base quantity and secondary voltage setting is:

13800
-------------- u 120 = 115 V Eq. 5-1
14400

For wye-connected VTs, the primary and secondary base quantities are as before, but the secondary voltage setting (here
a phase-to-ground value) is:

13800 120
-------------- u -------- = 66.4 V
14400 3 Eq. 5-2

Some settings are common to many elements, outlined as follows:


• FUNCTION setting — This setting programs the element to operate when selected as “Enabled.” The factory default is
5
“Disabled.” Once “Enabled,” any element associated with the function becomes active and all options become
available.
• NAME setting — This setting is used to uniquely identify the element.
• SOURCE setting — This setting is used to select the AC source to be monitored. See the Introduction to AC Sources
section later.
• PICKUP setting — For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings can be provided to define the
range of the measured parameters that cause the element to pick up.
• PICKUP DELAY setting — This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting — This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting — The default output operand state of all comparators is a logic 0 or “flag not set.” The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting — This setting is used to define the operation of an element target message. When set to "Disabled,"
no target message or illumination of a front panel LED indicator is issued upon operation of the element. When set to
“Self-Reset,” the target message and LED indication follow the operate state of the element and self-resets once the
operate element condition clears. When set to “Latched,” the target message and LED indication remains visible after
the element output returns to logic 0 until a RESET command is received by the relay.
• EVENTS setting — This setting is used to control whether the pickup, dropout, or operate states are recorded by the
event recorder. When set to “Disabled,” element pickup, dropout, or operate are not recorded as events. When set to
“Enabled,” events are created for

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-5


OVERVIEW CHAPTER 5: SETTINGS

<Element> PKP (pickup)


<Element> DPO (dropout)
<Element> OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This can happen when the element is in the operate state if the reset delay time is not zero.
Not every operand of a given element in a UR relay generates events, only the major output operands. Elements,
asserting output per phase, log operating phase output only, without asserting the common three-phase operand
event.

5.2.2 Introduction to AC sources

5.2.2.1 Background
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources, in
the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains all
the signals required to measure the load or fault in a particular power apparatus. A given source can contain all or some of
the following signals: three-phase currents, single-phase ground current, three-phase voltages, and an auxiliary voltage
from a single VT for checking for synchronism.
The basic idea of an AC source is to select a point on the power system where the voltages and currents are of interest. To
illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme that follows.
(The breaker-and-a-half scheme is used for illustrative purposes and is available on select UR products.) In this application,
the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location or power
equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or difference)
of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
5 connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements can need access to the individual currents from CT1 and CT2.
Figure 5-1: Breaker-and-a-half scheme
&7 WKURXJKFXUUHQW &7

:LQGLQJ
FXUUHQW
:LQGLQJ
85 3RZHU
WUDQVIRUPHU

:LQGLQJ

&7 &7
$&'5

In conventional analog or electronic relays, the sum of the currents is obtained from an appropriate external connection of
all CTs through which any portion of the current for the element being protected can flow. Auxiliary CTs are required to
perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the UR series of relays, provisions
have been included for all the current signals to be brought to the UR device where grouping, ratio correction, and
summation are applied internally via configuration settings.

5-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS OVERVIEW

A major advantage of using internal summation is that the individual currents are available to the protection device, for
example as additional information to calculate a restraint current, or to allow the provision of additional protection
features that operate on the individual currents, such as breaker failure.
Given the flexibility of this approach, it becomes necessary to add configuration settings to the platform to allow the user
to select which sets of CT inputs are to be added to form the net current into the protected device.
The internal grouping of current and voltage signals forms an AC source. This source can be given a specific name through
the settings and becomes available to protection and metering elements in the UR platform. Individual names can be
given to each source to help identify them for later use. For example, in the scheme shown in the preceding figure, the user
configures one source to be the sum of CT1 and CT2 and can name this source as “Wdg1 I.”
Once the sources have been configured, the user has them available as selections for the choice of input signal for the
protection elements and as metered quantities.

5.2.2.2 CT/VT module configuration


CT and voltage transformer (VT) input channels are contained in CT/VT modules. The type of input channel can be phase/
neutral/other voltage, phase/ground current, or sensitive ground current. The CT/VT modules calculate total waveform
RMS levels, fundamental frequency phasors, symmetrical components, and harmonics for voltage or current, as allowed
by the hardware in each channel. These modules can calculate other parameters as directed by the CPU module.
A CT/VT module contains up to eight input channels, numbered 1 through 8. The channel numbering corresponds to the
module terminal numbering 1 through 8 and is arranged as follows. Channels 1, 2, 3, and 4 are always provided as a group,
hereafter called a “bank,” and all four are either current or voltage, as are channels 5, 6, 7, and 8. Channels 1, 2, 3 and 5, 6,
7 are arranged as phase A, B, and C respectively. Channels 4 and 8 are either another current or voltage.
Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels,
and from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows.
Increasing slot position letter --> 5
CT/VT module 1 CT/VT module 2 CT/VT module 3
< bank 1 > < bank 3 > < bank 5 >
< bank 2 > < bank 4 > < bank 6 >

The UR platform allows for a maximum of six sets of three-phase voltages and six sets of three-phase currents. The result
of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is as follows.
Item Maximum number
CT/VT Module 2
CT Bank (3 phase channels, 1 ground channel) 4
VT Bank (3 phase channels, 1 auxiliary channel) 2

5.2.2.3 CT/VT input channel configuration


Upon relay startup, configuration settings for every bank of current or voltage input channels in the relay are generated
automatically from the order code. Within each bank, a channel identification label is assigned automatically to each bank
of channels in a given product. The bank naming convention is based on the physical location of the channels, required by
the user to know how to connect the relay to external circuits. Bank identification consists of the letter designation of the
slot in which the CT/VT module is mounted as the first character, followed by numbers indicating the channel, either 1 or 5.
See the HardFiber instruction manual for designations of HardFiber voltage and current banks.
For three-phase channel sets, the number of the lowest numbered channel identifies the set. For example, F1 represents
the three-phase channel set of F1/F2/F3, where F is the slot letter and 1 is the first channel of the three channels.
Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and it displays them
in the appropriate section in the sequence of the banks (as described earlier) as follows for a maximum configuration: F1,
F5, M1, M5, U1, and U5.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-7


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3 Product setup


5.3.1 Security

Cyber Security
The UR family of products are digital devices designed to be installed and operated in utility substations & industrial
plant environments and connected to secure private networks. UR Family IED should not be connected to the public
internet.
GE strongly recommends that users protect their digital devices using a defense-in-depth strategy which will protect
their products, their network, their systems and interfaces against cyber security threats. This includes, but is not
limited to, placing digital devices inside the control system network security perimeter, deploying and maintaining
access controls, monitoring and Intrusion Detection, security awareness training, security policies, network
segmentation and firewalls installation, strong and active password management, data encryption, antivirus and
other mitigating applicable technologies.
UR Family IEDs are available with an optional software option, which provides additional cyber security mechanisms
to help users protect against cyber security intrusion. GE strongly recommends use this "CyberSentry" option.
For additional details and recommendations on how to protect the UR Family IED, please see Hardening Setup section
below. GE Grid Solution may also provide additional instructions and recommendations to users from time to time
relating to UR Family IED and cyber security threats or vulnerabilities.
It is the users' sole responsibility to make sure that UR Family IEDs are installed and operated considering its cyber

5 security capabilities, security context, and the instructions and recommendations provided to the user relating to UR
Family IED. Users assume all risks and liability associated with damages or losses incurred in connection with any and
all cyber security incidences.

5.3.1.1 Security overview


The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled
automatically, and the default Password security and EnerVista security are disabled.
To maximize security, see the UR Family Secure Deployment Guide.

Lost password
If all passwords are lost, reset the unit to default values. Follow the instructions outlined later for COMMANDS  RELAY
MAINTENANCE  SERVICE COMMAND. Note that the relay is reset to default values, not just the passwords.
Then for CyberSentry, change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change
Default Password section at the end of the Installation chapter.

Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
• Password is case-sensitive
• Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
• Password must be 8 to 20 characters in length
• Password must contain characters from all of the following categories:

5-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

– English uppercase characters (A through Z)


– English lowercase characters (a through z)
– Base 10 digits (0 through 9)
– Non-alphabetic characters (for example, ~, !, @, #, $,%, &)

5.3.1.2 Password security


SETTINGS  PRODUCT SETUP  SECURITY
 SECURITY ACCESS LEVEL: Range: Restricted, Command, Setting,
  Restricted Factory Service (for factory use only)

 CHANGE LOCAL See page 5-10


  PASSWORDS

 CHANGE REMOTE See page 5-11


  PASSWORDS

 AC CESS See page 5-11


  SUPERVISION

 DUAL PERMISSION See page 5-13


  SECURITY ACCESS

PASSWORD ACCESS Range: Disabled, Enabled


 EVENTS: Disabled

The F60 supports password entry from a local or remote connection.


Local access is defined as access to settings or commands via the front panel. This includes both keypad entry and the
RS232 port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. Any change to the local or remote password enables this functionality.
5
For a relay without a CyberSentry software option, any user can activate the RESET button or Reset/Acknowledge
an alarm in the Graphical Front Panel Annunciator without password entry.

ACCESS LEVEL — This setting is viewable on the front panel. The Setting and Command passwords can be changed in the
EnerVista interface.
The "Restricted" option means that settings and commands can be accessed, but there is no access to factory
configuration. Access automatically reverts to the Restricted level according to the ACCESS LEVEL TIMEOUTS values. The
access level is set to Restricted when control power is cycled.
The "Factory Service" level is for factory functions.
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
• Setting — Allows the user to make any changes to any of the setting values:
– Change any setting
– Test mode operation
• Command — Restricts the user from making any settings changes, but allows the user to perform the following
operations:
– Operate the breakers via front panel keypad
– Change the state of virtual inputs
– Clear the event records
– Clear the oscillography records
– Clear fault reports
– Change the date and time

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-9


PRODUCT SETUP CHAPTER 5: SETTINGS

– Clear the breaker arcing current


– Clear energy records
– Clear the data logger
– Clear the user-programmable pushbutton states
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the F60, use the remote password. If the
connection is to the RS232 port of the front panel, use the local password.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
• ACCESS LOC SETG OFF — Asserted when local setting access is disabled
• ACCESS LOC SETG ON — Asserted when local setting access is enabled
• ACCESS LOC CMND OFF — Asserted when local command access is disabled
• ACCESS LOC CMND ON — Asserted when local command access is enabled
• ACCESS REM SETG OFF — Asserted when remote setting access is disabled
• ACCESS REM SETG ON — Asserted when remote setting access is enabled
• ACCESS REM CMND OFF — Asserted when remote command access is disabled
• ACCESS REM CMND ON — Asserted when remote command access is enabled

A command or setting write operation is required to update the state of the remote and local security operands
5 listed.
When a setting password or command password is set or updated, user access with a graphical front panel is
removed. Simply log in again on the graphical front panel.
When the setting password is set or updated, the graphical front panel Access Level displays as Command. This is
because the graphical front panel is a Modbus client and it does not have automatic access to the password
change.
PASSWORD ACCESS EVENTS — This setting allows recording of password access events in the event recorder.

Change local passwords


SETTINGS  PRODUCT SETUP  SECURITY  CHANGE LOCAL PASSWORDS
 CHANGE LOCAL CHANGE SETTING Range: No, Yes
 PASSWORDS  PASSWORD: No

CHANGE COMMAND Range: No, Yes


 PASSWORD: No

As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a CHANGE COMMAND PASSWORD or CHANGE
SETTING PASSWORD setting is programmed to “Yes” via the front panel interface, the following message sequence is
invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the “Restricted” level according to the
access level timeout setting values and when power is cycled.

5-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
If a remote connection is established, local passcodes are not visible.

Change remote passwords


Proper passwords are required to enable each command or setting level access, which are explained in the previous
section.
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE REMOTE PASSWORDS
 CHANGE REMOTE CHANGE SETTING Range: No, Yes
 PASSWORDS  PASSWORD: No

CHANGE COMMAND Range: No, Yes


 PASSWORD: No

To set the command or setting password in EnerVista:


1. In the EnerVista software or from the front panel, navigate to Settings > Product Setup > Security menu item to open
the remote password settings window.
2. Click the command or setting password Change button.
3. Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
earlier in this chapter. When an original password has already been used, enter it in the Enter Password field and click
the Send Password to Device button.
4. Re-enter the password in the Confirm Password field.
5. Click the OK button. The password is checked to ensure that it meets requirements.
5

If you establish a local (serial) connection to the relay, you cannot view remote passcodes.

Access supervision
SETTINGS  PRODUCT SETUP  SECURITY  ACCESS SUPERVISION
 ACCESS  ACCESS LEVEL See below
 SUPERVISION   TIMEOUTS

INVALID ATTEMPTS Range: 2 to 5 in steps of 1


 BEFORE LOCKOUT: 3

PASSWORD LOCKOUT Range: 5 to 60 minutes in steps of 1


 DURATION: 5 min

FACTORY SERVICE MODE: Range: Enabled, Disabled


 Disabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-11


PRODUCT SETUP CHAPTER 5: SETTINGS

LOCK FIRMWARE: Enabled Range: Enabled, Disabled


This menu displays when the ACCESS LEVEL setting is other than Restricted or Command.
The following access supervision settings are available.
INVALID ATTEMPTS BEFORE LOCKOUT — This setting specifies the number of times that an incorrect password can be entered
within three minutes before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or REMOTE ACCESS
DENIED FlexLogic operands are set to “On.” These operands return to the “Off” state upon expiration of the lockout.
PASSWORD LOCKOUT DURATION — This setting specifies the time that the F60 locks out password access after the number
of invalid password entries specified by the INVALID ATTEMPTS BEFORE LOCKOUT setting.
The F60 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a
password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS  CLEAR RECORDS  RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, password-protect the Command level. The operand does
not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element
programmed with event logs or targets enabled.
FACTORY SERVICE MODE — A factory service user is supported to perform additional operations intended only for them. This
setting allows access by GE support staff to be turned on and off. A factory service user can log in only when this setting is
configured as Enabled. It is disabled by default. When Enabled, the relay logs events and activates the TROUBLE LED.
GE recommends that Factory Service Mode be disabled when factory operations are not intended to be performed. The
5 TROUBLE LED de-activates when a user disables Factory Service Mode.
Login is required for this user, and the password is unique for each relay.
A factory service user is logged out with any of the following circumstances:
• UR restarts
• FACTORY SERVICE MODE setting is disabled by Administrator or factory service user
• ACCESS LEVEL setting is changed from "Factory Service" via front panel or serial connection
LOCK FIRMWARE — This setting determines whether the device accepts or blocks a firmware upgrade. When Disabled,
firmware can be updated. When Enabled, the firmware cannot be updated. When Enabled/locked and a firmware
upgrade is attempted using the software, the UNAUTH FW ATTEMPT FlexLogic operand does not assert. When locked
and a firmware upgrade is attempted without using the software, the operand asserts. A user with an Access Level of
"Settings" can modify this setting.

The following table outlines access level timeout settings.


SETTINGS  PRODUCT SETUP  SECURITY  ACCESS SUPERVISION  ACCESS LEVEL TIMEOUTS
 ACCESS LEVEL COMMAND LEVEL ACCESS Range: 5 to 480 minutes in steps of 1
 TIMEOUTS  TIMEOUT: 5 min

SETTING LEVEL ACCESS Range: 5 to 480 minutes in steps of 1


 TIMEOUT: 30 min

These settings allow the user to specify the length of inactivity required before returning to the Restricted access level.
Note that the access level is set to Restricted when control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to
return to Restricted access from the Command password level.
SETTING LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to return
to Restricted access from the Settings password level.

5-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Dual-permission security access


SETTINGS  PRODUCT SETUP  SECURITY  DUAL PERMISSION SECURITY ACCESS
 DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic operands (see below)
 SECURITY ACCESS  On

REMOTE SETTING AUTH: Range: FlexLogic operand


 On

ACCESS AUTH Range: 5 to 480 minutes in steps of 1


 TIMEOUT: 30 min

This menu displays when the ACCESS LEVEL setting is other than Restricted or Command.
This feature provides a mechanism to prevent unauthorized or unintended upload of settings to a relay through the local
or remote interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH — This setting is used for local (front panel or RS232 interface) setting access supervision. Valid
values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On,“ then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (on) prior to providing the local
setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message displays on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• REMOTE SETTING AUTH — This setting is used for remote (Ethernet or RS485 interface) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is 5
required. If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to
providing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• ACCESS AUTH TIMEOUT — This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On.” The state of the FlexLogic operand
is monitored continuously for an off-to-on transition. When this occurs, local access is permitted and the timer
programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the
timeout is restarted. The status of this timer updates every five seconds.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-13


PRODUCT SETUP CHAPTER 5: SETTINGS

The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.

The Remote Settings Authorized setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required.
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
5 The Access Authorized Timeout setting represents the timeout delay remote setting access. It applies when the Remote
Settings Authorized setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the Access Authorized Timeout setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.

5.3.1.3 EnerVista security

Enable the security management system


Access to files is controlled by the operating system and EnerVista software as follows:
• Access privileges to files are defined by the Windows operating system. A standard user does not have access to a file
created by an administrator or another user.
• When the EnerVista UR Setup software security system is disabled (passwords are not required), all users have
administrator access
The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista. It is
disabled by default to allow access to the device immediately after installation. When security is disabled, all users have
administrator access. GE recommends enabling the EnerVista security before placing the device in service.

5-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

To enable the security system and require password use:


1. Select the Security > User Management menu to open the user management window.

2. Enable the Enable Security check box in the lower-left corner to enable the security management system.
3. Click the Ok button.

If you force password entry using this feature, ensure that you know the Administrator password. If you do not
know the password and are locked out of the software, reset the device to factory defaults as outlined later for
5
COMMANDS  RELAY MAINTENANCE  SERVICE COMMAND. When using CyberSentry, the default password is
"ChangeMe1#".
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.

Add a new user


The following pre-requisites are required to add user accounts to the EnerVista security management system:
• The user adding the account must have administrator rights
• The EnerVista security management system must be enabled (previous section)
To add a user account:
1. Select the Security > User Management item from the top menu to open the user management window.
2. Enter a username in the User field. The username must be four to 20 characters in length.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-15


PRODUCT SETUP CHAPTER 5: SETTINGS

3. Select the user access rights by enabling the check box of one or more fields.

The table outlines access rights.


Table 5-1: Access rights summary
Field Description
Delete Entry Deletes the user account when exiting the user management window
5 Actual Values Allows the user to read Actual Values
Settings Allows the user to read Settings values
Commands Allows the user to execute Commands
Event Recorder Allows the user to use the Event Recorder
FlexLogic Allows the user to read FlexLogic values
Update Info Allows the user to write to any function to which they have read privileges. When any of the Settings, Event
Recorder, and FlexLogic check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the Update Info box, they are granted read and write access.
The user is not granted write access to functions that are not enabled, even if the Update Info field is
enabled.
Admin When the check box is enabled, the user becomes an EnerVista UR Setup administrator and has all
administrative rights. Exercise caution when granting administrator rights.

4. Click OK to add the user account to the system.

Modify user privileges


The following pre-requisites are required to modify user privileges in the EnerVista security management system:
• The user modifying the privileges must have administrator rights
• The EnerVista security management system must be enabled (the Enable Security check box enabled)
To modify user privileges:
1. Select the Security > User Management item from the top menu to open the user management window.
2. Locate the username in the User field.

5-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

3. Modify the user access rights by enabling or disabling one or more of the check boxes.

The table outlines access rights.


Table 5-2: Access rights summary
Field Description
Delete Entry Deletes the user account when exiting the user management window
Actual Values Allows the user to read actual values 5
Settings Allows the user to read setting values
Commands Allows the user to execute commands
Event Recorder Allows the user to use the digital fault recorder
FlexLogic Allows the user to read FlexLogic values
Update Info Allows the user to write to any function to which they have read privileges. When any of the Settings, Event
Recorder, and FlexLogic check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the Update Info box, they are granted read and write access.
The user is not granted write access to functions that are not enabled, even if the Update Info field is
enabled.
Admin When this check box is enabled, the user becomes an EnerVista UR Setup administrator and has all
administrative rights. Exercise caution when granting administrator rights.

4. Click OK to save the changes.

5.3.1.4 CyberSentry security

This feature requires a CyberSentry software option, specified at the time of ordering.

The EnerVista software provides the means to configure and authenticate the F60 access using either a server or the
device. Access to functions depends on user role.
The login screen of EnerVista has two options for access to the F60, these being Server and Device authentication.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-17


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-2: Login screen for CyberSentry

When the “Server” Authentication Type is selected, the F60 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the “Device” button is selected, the F60 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or
Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords
are stored on the F60 device. In this case, access is not user-attributable. In cases where user-attributable access is
required, especially for auditable processes for compliance reasons, use server authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.

Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features are

5 open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found open.
When CyberSentry is enabled, Modbus communications over Ethernet is encrypted for all roles but for the Observer. The
built-in Observer role has read-only access to data over Modbus over Ethernet without authentication. Encrypted Modbus
communication over Ethernet is not always tolerated by SCADA systems. The UR has a bypass access feature for such
situations, which allows unencrypted Modbus over Ethernet. The Bypass Access setting is available on the SETTINGS 
PRODUCT SETUP  SECURITY  SUPERVISORY screen. Note that other protocols (DNP, 101, 103, 104, EGD) are not encrypted,
and they are good communications options for SCADA systems when CyberSentry is enabled.
When using the rear RS485 port and CyberSentry, registers can be read with a maximum buffer of 64 bytes. Settings may
not be written, so use another port or configure the SERIAL INACTIVITY TIMEOUT setting to a high value, such as eight
minutes, to give the relay enough time to finish the task.

CyberSentry settings through EnerVista


CyberSentry security settings are configured under Settings > Product Setup > Security.

5-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-3: Security panel when CyberSentry installed

For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
Figure 5-4: Supervisory panel
5

For the Security panel, the following settings are available.


Table 5-3: RADIUS server settings
Setting name Description Minimum Maximum Default Units Minimum
permission
Primary RADIUS IP IP address of the main RADIUS server. 0.0.0.0 223.255.255.254 0.0.0.0 - Administrator
Address Default value indicates no Primary
RADIUS server is configured, and hence
RADIUS is disabled.
Restart the relay for any change to take
effect.
Primary RADIUS authentication port 1 65535 1812 - Administrator
Authentication Port

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-19


PRODUCT SETUP CHAPTER 5: SETTINGS

Setting name Description Minimum Maximum Default Units Minimum


permission
Primary Accounting RADIUS accounting port 1 65535 1813 - Administrator
Port
Vendor ID An identifier that specifies RADIUS Value that Administrator
vendor-specific attributes used with the represents
protocol General
Electric
RADIUS Authentication method used by RADIUS EAP-TTLS PAP EAP-TTLS - Administrator
Authentication server
Method
RADIUS Shared secret used in authentication. It See the See the following N/A - Administrator
Authentication displays as asterisks. This setting must Password password section
(Shared) Secret meet the CyberSentry password Requirements for requirements
requirements. section earlier
in this chapter
Confirm RADIUS Confirmation of the shared secret. The See the 245 characters N/A - Administrator
Authentication entry displays as asterisks. Password
(Shared) Secret Requirements
section

Table 5-4: General security settings


Setting name Description Minimum Maximum Default Units Minimum
permission
Session Lockout Number of failed authentications before the 0 (lockout 99 3 - Administrator

5 device blocks subsequent authentication


attempts for the lockout period
disabled)

Session Lockout The period in minutes that a user is prevented 0 (no period) 9999 3 min Administrator
Period from logging in after being locked out
Syslog Server IP The IP address of the target Syslog server to 0.0.0.0 223.255. 0.0.0.0 - Administrator
Address which all security events are transmitted 255.254
Syslog Server Port The UDP port number of the target syslog 1 65535 514 - Administrator
Number server to which all security events are
transmitted
Device When enabled, local Device authentication Disabled Enabled Enabled - Administrator
Authentication with roles is allowed. When disabled, the UR
only authenticates to the AAA server (RADIUS).
NOTE: Administrator and Supervisor (if still
enabled) remain active even after Device
authentication is disabled. The only permission
for local Administrator is to re-enable Device
authentication when Device authentication is
disabled. To re-enable Device authentication,
the Supervisor unlocks the device for setting
changes, and then the Administrator can re-
enable Device authentication.
Factory Service When enabled, the device can go into factory Disabled Enabled Disabled - Supervisor
Mode service mode. To enable, Supervisor (Administrator
authentication is necessary. when Supervisor
is disabled)
Lock Settings When disabled, the device allows modification Disabled Enabled Disabled - Supervisor
of settings. To enable, Supervisor (Administrator
authentication is necessary. when Supervisor
is disabled)
Lock Firmware When enabled, the device denies firmware Disabled Enabled Disabled - Supervisor
upload. To change setting, Supervisor (Administrator
authentication is necessary. when Supervisor
is disabled)
Restore to Defaults Sets the device to factory defaults No Yes No - Administrator

5-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Setting name Description Minimum Maximum Default Units Minimum


permission
Supervisor Role When enabled, the Supervisor role is active. To Disabled Enabled Enabled - Administrator to
enable, Administrator authentication is enable and
necessary. When disabled, the Supervisor role Supervisor to
is inactive. To disable, Supervisor disable
authentication is necessary.
RADIUS user names Ensures that RADIUS user names are not the See RADIUS See - Administrator
same as local/device role names server RADIUS
documents server
document
s
Password Local/device roles except for Observer are See the See the Change Text The specified
password-protected. All RADIUS users are Password following Me1# role and
password-protected. Requirements password Administrator,
section earlier section for except for
in this chapter requireme Supervisor,
nts where it is only
itself

Table 5-5: Security alarm settings


Setting name Description / Details Min Max Default Units Minimum
permissions
Failed A threshold number indicating when an alarm Disabled Enabled Enabled - Administrator
Authentications is set off to indicate too many failed
authentication attempts
Firmware Lock A value indicating if the device can receive a
firmware upgrade. If Enabled and a firmware
Disabled Enabled Enabled - Administrator
5
upgrade attempt is made, the device alarm
activates. If Disabled, the device alarm does
not activate. On each firmware upgrade this
setting goes back to the default.
Settings Lock A value indicating if the device can accept any Disabled Enabled Enabled - Supervisor
settings changes. If Enabled and a settings (Administrator if
change attempt is made, the device alarm Supervisor has
activates. If Disabled, the device alarm does been disabled)
not activate.

CyberSentry settings through the front panel


SETTINGS  PRODUCT SETUP  SECURITY
 SECURITY LOGIN: Range: Administrator, Engineer, Supervisor,
  None Operator, Factory (for factory use only), None

 CHANGE DEVICE See page 5-22


  PASSWORD

 SESSION See page 5-23


  SETTINGS

 RESTORE DEFAULTS See page 5-23


 

 SUPERVISORY See page 5-23


 

SYSLOG IP ADDRESS: Range: 0.0.0.0, 255.255.255.255


 0.0.0.0

SYSLOG PORT NUMBER: Range: 1 to 65535


 514

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-21


PRODUCT SETUP CHAPTER 5: SETTINGS

LOGIN — This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
outlined here. For the Supervisor role, enable the “Supervisor Role” setting. Log out by right-clicking the device in EnerVista
and selecting the Disconnect option.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password. There are no time-outs for the
Administrator, Engineer, Operator, and Supervisor when logged in using the front panel; log out manually or use the
Command > Security commands in the software.
The roles are defined as follows:
• Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
• Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
• Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
exist offline.
• Supervisor — This is only an approving role. This role’s authentication commits setting changes submitted by
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
• Observer — This role has read-only access to all F60 settings. This role allows concurrent Observer access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
5 device. This role displays as "None" on the front panel. When local authentication is used, no password is required for
this role. When RADIUS server authentication is used, a password is required.

The Factory service role is not available. It is for factory use only. The FACTORY SERVICE MODE setting must be
enabled for access.
The Local Access Denied message on the front panel can mean that you need to log in to the UR in order to
complete the action.

Change device password


SETTINGS  PRODUCT SETUP  SECURITY  CHANGE DEVICE PASSWORD
 CHANGE DEVICE NEW PASSWORD: Range: 20 alphanumeric characters
 PASSWORD 
CONFIRM PASSWORD: Range: 20 alphanumeric characters

The menu displays on the front panel upon successful login of the Administrator role.
Passwords are stored in text format. No encryption is applied.

In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, reset the device to factory defaults as outlined later for COMMANDS  RELAY
MAINTENANCE  SERVICE COMMAND. When using CyberSentry, the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.

5-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Session settings
SETTINGS  PRODUCT SETUP  SECURITY  SESSION SETTINGS
 SESSION SESSION LOCKOUT: Range: 0 to 99
 SETTINGS  3

SESSION LOCKOUT Range: 0 to 9999 minutes


 PERIOD: 3 min

SESSION LOCKOUT — This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD — This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.

Restore defaults
SETTINGS  PRODUCT SETUP  SECURITY  RESTORE DEFAULTS
 RESTORE DEFAULTS LOAD FACTORY Range: Yes, No
  DEFAULTS: No

LOAD FACTORY DEFAULTS — This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.

Supervisory
SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY
 SUPERVISORY
  DEVICE
AUTHENTICATION: Yes
Range: Yes, No 5
BYPASS ACCESS: Range: Local, Remote, Local and Remote, Disabled,
 Disabled Pushbuttons

RESET KEY ACCESS: Range: Enabled, Disabled


 Disabled

FACTORY SERVICE Range: Enabled, Disabled


 MODE: Disabled

 SELF TESTS See below


 

SUPERVISOR ROLE: Range: Enabled, Disabled


 Disabled

SERIAL INACTIVITY Range: 1 to 9999 minutes


 TIMEOUT: 1 min

LOCK SETTINGS: Range: Enabled, Disabled


 Disabled

LOCK FIRMWARE: Range: Enabled, Disabled


 Enabled

The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
DEVICE AUTHENTICATION — This setting is enabled by default, meaning "Yes" is selected. When enabled, Device
authentication with roles is enabled. When this setting is disabled, the UR only authenticates to the AAA server (RADIUS).
However, the Administrator and Supervisor (when enabled) remain active even after device authentication is disabled and
their only permission is to re-enable Device authentication. To re-enable Device authentication, the Supervisor unlocks the
device for settings changes, then the Administrator re-enables device authentication.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-23


PRODUCT SETUP CHAPTER 5: SETTINGS

BYPASS ACCESS — The bypass security feature provides an easier access, with no authentication and encryption for those
special situations when this is considered safe. Only the Supervisor, or the Administrator when the Supervisor role is
disabled, can enable this feature.
Mode Front panel or serial (RS232, RS485) Ethernet
Normal mode Authentication — Role Based Access Control (RBAC) Authentication — RBAC and passwords encrypted
and passwords in clear SSH tunneling
Bypass access mode No passwords for allowed RBAC levels No passwords for allowed RBAC levels
No SSH tunneling

The bypass options are as follows:


• Local — Bypasses authentication for push buttons, keypad, and RS232
• Remote — Bypasses authentication for RS485 and Ethernet
• Local and Remote — Bypasses authentication for push buttons, keypad, RS232, RS485, and Ethernet
• Pushbuttons — Bypasses authentication for front panel push buttons, including in the software. On the graphical front
panel, the authentication for side pushbuttons to control breakers and disconnects also is bypassed.
With BYPASS ACCESS set to other than "Disabled," the software displays a message that LOCK SETTINGS is ignored.
RESET KEY ACCESS — Indicates whether user authentication is required for executing the RESET button on the front panel or
the front panel in the software. When Disabled, user authentication is required at the Administrator or Engineer level. When
Enabled, any user can execute the RESET command without authentication. A Supervisor, or the Administrator if the
Supervisor role is disabled, can enable this feature.
FACTORY SERVICE MODE — This setting allows access by GE support staff to be turned on and off. When Enabled, the device
can go into factory service mode. A Supervisor role is necessary to enable the setting, and otherwise an Administrator role
when the Supervisor role is disabled. The default value is Disabled.
5 An event is generated when disabling and enabling, and the TROUBLE LED activates when enabled. The factory service
user enters a password that is unique for each device.
When a factory service user is logged in on the front panel, a remote user cannot access the device at the same time.
A factory service user is logged out with any of the following circumstances:
• UR restarts
• Factory Service Mode setting is disabled by Administrator or factory service user
• When a non-factory service user logs in via front panel or serial connection
SUPERVISOR ROLE — When Enabled, the Supervisor role is active. To Disable this setting a Supervisor authentication is
necessary. If disabled, the Supervisor role is not allowed to log in. In this case, the Administrator can change the settings
under the Supervisory menu.
If enabled, Supervisor authentication is required to change the settings in the Supervisory menu. If the Supervisor disables
their role after authentication, the Supervisor session remains valid until they switch to another role using MMI or until they
end the current Supervisor session if using communications.
This role is disabled by default.
SERIAL INACTIVITY TIMEOUT — The role logged via a serial port is auto logged off after the Serial Inactivity timer times out. A
separate timer is maintained for RS232 and RS485 connections. Set this value to a high number, such as eight minutes,
when using the rear RS485 terminals for settings write.
GE recommends setting this value to at least 3 minutes for the following scenario: while connected to a CyberSentry
device, with serial or USB cable connected to the front panel, and performing "Add Device to Offline Window" or an online/
offline comparison. With less than the recommended 3 minutes, the serial activity timeout interrupts the connection and
the security role login window appears. Upon login, the process resumes.
LOCK SETTINGS — Specifies whether the device accepts settings changes, with a default of Disabled to allow changes. The
Supervisor role Disables this setting for the relay to start accepting setting changes or command changes. After all the
setting changes are applied or commands executed, the Supervisor then Enables the setting to lock setting changes.
When set to "Enabled," all other settings in the Supervisory window cannot be edited. Any setting changes on other
Modbus screens and IEC 61850 screens cannot be saved to the relay.

5-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

When the BYPASS ACCESS setting is set to a local or remote option, it overrides LOCK SETTINGS and allows changes.
LOCK FIRMWARE — Specifies whether the device accepts a firmware upgrade, with a default of Enabled to deny upgrade.
The Supervisor role Disables this setting to allow upgrades. After the upgrade, the Supervisor then Enables the setting to
prevent upgrades.
When the BYPASS ACCESS setting is set to a local or remote option, it overrides LOCK FIRMWARE and allows changes.

Self-tests
SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY  SELF TESTS
 SELF TESTS  FAILED See below
   AUTHENTICATE

FIRMWARE LOCK: Range: Enabled, Disabled


 Enabled

SETTINGS LOCK: Range: Enabled, Disabled


 Enabled

FAILED AUTHENTICATE — If this setting is Enabled then the number of failed authentications is compared with the Session
Lockout threshold. When the Session Lockout threshold is exceeded, this minor alarm indication comes up.
FIRMWARE LOCK — If this setting is Enabled, then any firmware upgrade operation attempt when the LOCK FIRMWARE
setting is enabled brings up this self test alarm.
SETTINGS LOCK — If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY  SELF TESTS  FAILED AUTHENTICATE
 FAILED
 AUTHENTICATE  FAILED AUTHENTICATE:
Enabled
Range: Enabled, Disabled 5
CyberSentry setup
When first using CyberSentry security, use the following procedure for setup.
1. Log in to the relay as Administrator by using the VALUE keys on the front panel to enter the default password
"ChangeMe1#". Note that the LOCK SETTINGS setting needs to be disabled (default) in the SETTINGS  PRODUCT SETUP
 SECURITY  SUPERVISORY menu.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None.
5. Next, Device or Server authentication can be chosen on the login screen, but the choice is available only in EnerVista.
Use Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only Device authentication is supported. When Server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the
EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server at the end of
this instruction manual gives an example of how to set up a simple RADIUS server. Once both the RADIUS server and
the parameters for connecting the UR to the server have been configured, you can choose Server authentication on
the login screen of EnerVista.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-25


PRODUCT SETUP CHAPTER 5: SETTINGS

The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at a time, for both login by front
panel and software.
To configure Server authentication:
1. In the EnerVista software, choose Device authentication and log in as Administrator.
2. Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3. On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4. In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
5. After making any required changes, log out.

When changing settings offline, ensure that only settings permitted by the role that performs the
settings download are changed because only those changes are applied.
5 Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the RESET button, which resets targets, where targets are errors
displayed on the front panel or the Targets panel of the EnerVista software. The RESET button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1. Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.

Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Security log Event Number Date & Username IP address Role Activity Value
Timestamp

Event Number — Event identification number (index)


Date & Timestamp — UTC date and time
Username — 255 chars maximum, but in the security log it is truncated to 20 characters
IP address — Device IP address
Role — 16 bit unsigned, of type format F617

Enumeration Role
0 None
1 Administrator
2 Supervisor
3 Engineer
4 Operator

5-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Enumeration Role
5 Factory

Activity Value — 16 bit unsigned

Enumeration Description
1 Authentication Failed
2 User Lockout
3 FW Upgrade
4 FW Lock
5 Settings Lock
6 Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7 Clear Oscillography command
8 Clear Data Logger command (not applicable to all UR products)
9 Clear Demand Records command (not applicable to all UR products)
10 Clear Energy command (not applicable to all UR products)
11 Clear Unauthorized Access command
12 Clear Teleprotection Counters command (not applicable to all UR products)
13 Clear All Relay Records command
14 Role Log in
15 Role Log out
16 WRITE_SETTING_FILE
17 Factory Mode enabled 5
18 Factory Mode disabled

In addition to supporting syslog, a F60 with CyberSentry also saves the security events in two local security files, these
being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in
the EnerVista software under Maintenance > Retrieve File. Depending on the level of criticality/severity, a syslog server or
a reporting tool gathering information from a syslog server can produce reports, charts, and so on. All severity levels are
per RFC 5424.
Table 5-6: CyberSentry system events recorded
Event Severity Description
FAILED_AUTH, ORIGIN, TIMESTAMP Notice (5) A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN, TIMESTAMP Warning (4) An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN, Information (6) Indicates that a change of firmware has occurred
TIMESTAMP
FIRMWARE_LOCK, ORIGIN, Warning (4) An attempt was made to change firmware while the firmware lock was
TIMESTAMP enabled
SETTING_CHG, ORIGIN, TIMESTAMP Notice (5) Indicates setting change(s)
SETTING_LOCK, ORIGIN, TIMESTAMP Warning (4) An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY Notice (5) Clear oscillography command was issued
CLEAR_DATA_LOGGER Notice (5) Clear data logger command was issued
CLEAR_DEMAND_RECS Notice (5) Clear demand records command was issued
CLEAR_ENERGY Notice (5) Clear energy command was issued
RESET_UNAUTH_ACCESS Notice (5) Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT Notice (5) Clear teleprotection counters command was issued

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-27


PRODUCT SETUP CHAPTER 5: SETTINGS

Event Severity Description


CLEAR_ALL_RECS Notice (5) Clear all records command was issued
WRITE_SETTING_FILE Notice (5) Write settings file to the relay
FACTORY_MODE_ENABLED Warning (4) Factory Service Mode activated
FACTORY_MODE_DISABLED Warning (4) Factory Service Mode deactivated

5.3.2 Display properties


SETTINGS  PRODUCT SETUP  DISPLAY PROPERTIES
 DISPLAY LANGUAGE: Range: English; English, French; English, Russian; English,
 PROPERTIES  English Chinese; English, German (examples; depends on order code)
Visible when language other than English purchased

FLASH MESSAGE Range: 0.5 to 10.0 s in steps of 0.1


 TIME: 1.0 s

DEFAULT MESSAGE Range: 10 to 900 s in steps of 1


 TIMEOUT: 300 s

DEFAULT MESSAGE Range: 25%, 50%, 75%, 100%


 INTENSITY: 25 % Visible when a VFD is installed

SCREEN SAVER Range: Disabled, Enabled


 FEATURE: Disabled Visible when an LCD is installed

SCREEN SAVER WAIT Range: 1 to 65535 min. in steps of 1


 TIME: 30 min Visible when an LCD is installed

5  CURRENT CUT-OFF
LEVEL: 0.020 pu
Range: 0.002 to 0.020 pu in steps of 0.001

VOLTAGE CUT-OFF Range: 0.1 to 2.0 V secondary in steps of 0.1


 LEVEL: 1.0 V

Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE — This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are in
English.
For Japanese and Chinese, up to 10 characters can be input in a field on the graphical front panel, not 20.
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always
second, and Language is always first.
If the language is changed after entering user-configured names, such as relay names, the strings are not translated. For
example, a relay name is entered in English, the language is changed to Japanese, and the relay name remains in English.
Set the language before changing settings.

Restart the relay after changing the LANGUAGE setting.

The language can be selected also for the front panel in EnerVista under Maintenance > Change Front Panel.
The language of the EnerVista software can be changed under View > Language. Languages supported by the operating
system display; that is for Polish or Japanese to display, the software needs to be installed on a Polish or Japanese
operating system.

5-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

FLASH MESSAGE TIME — Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT — If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY — To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME — These settings are only visible if the F60 has a liquid crystal display
(LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL — This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The F60 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the CURRENT CUT-OFF LEVEL setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL — This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The F60 5
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated using the following equations. For Delta connections:

3 u CURRENT CUT-OFF LEVEL u VOLTAGE CUT-OFF LEVEL u VT primary u CT primary


3-phase power cut-off = -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- Eq. 5-3
VT secondary

For Wye connections:

3 u CURRENT CUT-OFF LEVEL u VOLTAGE CUT-OFF LEVEL u VT primary u CT primary


3-phase power cut-off = ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
VT secondary Eq. 5-4

CURRENT CUT-OFF LEVEL u VOLTAGE CUT-OFF LEVEL u VT primary u CT primary


per-phase power cut-off = --------------------------------------------------------------------------------------------------------------------------------------------------------------------------
VT secondary Eq. 5-5

where VT primary = VT secondary × VT ratio and CT primary = CT secondary × CT ratio.


For example, given the following settings:
CURRENT CUT-OFF LEVEL: “0.02 pu”
VOLTAGE CUT-OFF LEVEL: “1.0 V”
PHASE CT PRIMARY: “100 A”
PHASE VT SECONDARY: “66.4 V”
PHASE VT RATIO: “208.00 : 1"
PHASE VT CONNECTION: “Delta”
We have:
CT primary = “100 A”, and
VT primary = PHASE VT SECONDARY x PHASE VT RATIO = 66.4 V x 208 = 13811.2 V

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-29


PRODUCT SETUP CHAPTER 5: SETTINGS

The power cut-off is therefore:


power cut-off= (CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × CT primary × VT primary)/VT secondary
=( × 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off does not display. As well, the three-phase energy data do not accumulate if
the total power from all three phases does not exceed the power cut-off.

Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as valid
measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for CURRENT
CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.

5.3.3 Graphical front panel

The graphical front panel is a hardware option.

Use the EnerVista software to configure the graphical front panel. The settings are not accessible from the graphical front
panel.
The following screens are available:
• Home page

5 •

Rolling mode
Metering editor
• Single-line diagram editor
• Annunciator editor
• Configurable navigation
The settings menu itself and the event record pages are not configurable.
Multiple screens can be opened in the EnerVista software, but the first remains active and the others can be read-only. For
example, the Annunciator Editor and Single Line Diagram Editor can be open and active, then subsequently opened Rolling
Mode and Home Page screens are read-only. Close the windows, then re-open the one required.

5.3.3.1 Home page


This window sets the home page displayed on the graphical front panel and the date and time formats for all pages. Home
page options include display of product information, alarms, actual values, and event records. In addition, the window
allows selection of a FlexLogic operand that enables/disables local control of breakers and switches from the graphical
front panel.
The path is Settings > Product Setup > Graphical Panel > Home Page. The menu does not display when there is no
graphical front panel.

5-30 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-5: Home page with product information


Setting Group
Alarm Target Relay Date and Time

859850A1.cdr

Figure 5-6: Home page settings

Home Page Content


Range: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Phasors 1…6, Tabular 1…5, Event Records, Targets
Default: Product Information
This setting specifies the page to display between the home page header and footer. Pressing the Home button returns
the display to this page. The home page displays for the rolling mode delay specified, then changes to the rolling mode
pages.
The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:
– The first annunciator page that contains an annunciator window that is in alarm (fast flash)
– The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
– The first annunciator page that contains an annunciator window that is in abnormal state
– Annunciator page 1
Whenever an annunciator window changes state this list is re-evaluated, which can result in the home page displaying
a different annunciator page.
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages, such as wrong transceiver, similar to event record entries.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-31


PRODUCT SETUP CHAPTER 5: SETTINGS

Date Format
Range: yyyy-mm-dd, dd-mmm-yy, yyyy/mm/dd, m/d/yyyy, m/d/yy, mm/dd/yy, mm/dd/yyyy, yy/mm/dd
Default: yyyy-mm-dd
This setting specifies the format for dates on the graphical front panel. It applies to the page header, the events records,
the annunciator, and everywhere else a date displays on the panel. If the relay is synchronized to an external time
source via PTP, IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow.
yyyy — four-digit year, for example 2017
yy — two-digit year, for example 17 for 2017
mmm — abbreviation of month name, for example Jan for January
mm — two-digit month, for example 01 for January
m — one or two-digit month, for example 1 for January and 10 for October
dd — two-digit day, for example 08
d — one or two-digit day, for example 8 and 28
To set the date and time, access Synchronize Devices in the software, synchronize to a time source using Settings >
Product Setup > Real Time Clock, or synchronize to the computer using Commands > Set Date and Time.
Time Format
Range: hh:mm:ss, h:mm:ss tt
Default: hh:mm:ss
This setting specifies the format for time on the graphical front panel. It applies to the page header and everywhere else
a time displays on the panel. When the Date Format and the Time Format use the defaults, the date and time are
separated by the character "T" per the ISO convention, such as "2017-09-24T10:58:31". Otherwise the date and time are
separated by a space. If the relay is synchronized to an external time source via PTP, IRIG-B, SNTP, and so on, the date/
5 time is shown in white, and otherwise in yellow.
hh — two-digit hour, for example 02 for two o’clock
h — one or two-digit hour, for example 2 for two o’clock
mm — two-digit minute, for example 51 minutes
ss — two-digit second (can have a decimal and further digits appended), for example 16 seconds
tt — AM or PM based on 12 hour clock
If microseconds have to be displayed, for example, in the event records, the 24-hour clock is adopted. The representation
of an accumulated period (for example hh:mm) is not affected by the selected time format.
To set the date and time, access Synchronize Devices in the software or synchronize to a time source using Settings >
Product Setup > Real Time Clock.
Enable Controls From GFP
Range: FlexLogic operand
Default: ON
This setting enables/disables local control of breakers and switches from the graphical front panel.
The FlexLogic operand assigned to this setting applies to controls of all the single-line diagram pages. The assigned
operand status is reflected in the ENABLE CTRL FROM GFP FlexLogic operand.
When the operand assigned to this setting is ON, controls are enabled, as indicated on a single-line diagram with an
Enable Control label. Pressing the side pushbutton next to the label populates the front panel display with control soft
keys.
When the operand assigned to this setting is OFF, controls are disabled, and the Enable Control label does not display.
If already in control mode and the operand status assigned to this setting changes to OFF, at the confirmation prompt
the control command is not issued and the SLD screen goes to the top SLD page instead.

5-32 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

5.3.3.2 Rolling mode


After a user-defined period of inactivity, the graphical front panel changes, or rolls, to user-selected pages. Up to 10 pages
can be specified. Similarly, the display backlight intensity is lowered to a specified level; lower intensity extends the life of
the display.
Each rolling page displays for a few seconds; duration cannot be set.
The path is Settings > Product Setup > Graphical Panel > Rolling Mode.
Figure 5-7: Rolling mode settings

5
Rolling Mode Delay
Range: 0 to 900 s in steps of 1
Default: 300 s
Set this delay to 0 to disable the rolling mode feature.
Otherwise, after no pushbutton has been pressed for the amount of time specified by this setting, the display
automatically enters rolling mode. While in the rolling mode, the Rolling Mode Pages display. Rolling mode can be
interrupted when a setting changes, such as changing the home page, then resumes rolling.
Automatic Annunciator Recall
Range: Enabled, Disabled
Default: Enabled
When Enabled, an annunciator window changes state, and the display is in rolling mode, this setting terminates rolling
mode and displays the annunciator page containing the changed state.
The Configurable Navigation feature takes precedence over this setting when the Automatic Annunciator Recall and
Configurable Navigation are activated by the same input.
Screen Saver Delay
Range: 0 to 900 s in steps of 1
Default: 300 s
The screen saver mode extends the life of the display. After the amount of time set here, the screen saver activates and
the display intensity is reduced to the level set by the Screen Saver Intensity setting. When in rolling mode, rolling
continues while the screen saver is active. The screen saver terminates when rolling mode terminates. To disable the
screen saver, set the delay to 0.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-33


PRODUCT SETUP CHAPTER 5: SETTINGS

Screen Saver Intensity


Range: 0, 10, 20, or 30 %
Default: 30 %
This setting sets the brightness of the display while the screen saver is active. For example, 0% means that the screen is
dark and nothing displays. Pressing a pushbutton or changing a setting in the software, for example, re-activates the
display.
Number of Rolling Mode Pages
Range: 1 to 10 in steps of 1
Default: 1
This setting specifies the number of rolling pages. During rolling mode, the graphical front panel displays pages from 1
to the selected number.
Rolling Mode Page 1 to 10
Range: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Phasors 1…6, Tabular 1…5, Event Records, Targets
Default: Product Information
These settings specify the pages to display on the graphical front panel while in rolling mode.
The "Annunciator" selection without a page number specifies the first annunciator page in the following sequence:
– The first annunciator page that contains an annunciator window that is in alarm (fast flash)
– The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
– The first annunciator page that contains an annunciator window that is in abnormal state
– Annunciator page 1
5 Whenever an annunciator window changes state the list is re-evaluated, which can result in the display of a different
annunciator page in the rolling sequence.
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages, such as wrong transceiver, similar to event record entries.

5.3.3.3 Metering editor


This feature creates tables of actual/metered values for the graphical front panel. It configures the content that displays in
the Metering Tab pushbutton. An actual value, status, or text can be displayed. Five tabular metering pages can be
configured. There also can be a phasor page for each configured AC source, and these pages are not configurable.
The path is Settings > Product Setup > Graphical Panel > Metering Editor.
Set the Current Page, Page Name, Layout, configure the top inputs, then the cells. The 16 inputs at the top of the page are
used as inputs for the Status Index fields. Click the Preview button to view the page.
For a phasor diagram, configure the source under Settings > System Setup > Signal Sources. The diagram is then
viewable by pushing the Metering Tab pushbutton on the graphical front panel. The Metering Editor is not used for these
phasor diagrams.
The figures show setup and table preview.
The Cells configured are not retained when using the Convert Device Settings function, for example when converting a
file in the Offline Window from version 7.6 to 7.7.

5-34 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-8: Metering Editor window

5
Figure 5-9: Preview for graphical front panel

To avoid conflict with XML programming, do not enter the following characters on the Annunciator and Metering editor
panels: " (quotation mark), ' (apostrophe), < (less than), > (greater than), & (ampersand). When used, the text following the
character does not display or the Annunciator and Metering panels do not display on the graphical front panel.
STATUS INPUTS 1 to 16
Range: OFF, ON, any FlexLogic operand
Default: OFF
This setting identifies the potential inputs for use in the STATUS INDEX fields, for display of the status of FlexLogic
operands.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-35


PRODUCT SETUP CHAPTER 5: SETTINGS

A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
Select the metering input from the drop-down list. The options reflect the FlexLogic operands applicable to the F60. They
are inputs for all five metering pages, not just the current page.
CURRENT PAGE
Range: Page 1...Page 5
Default: Page 1
Select the metering page to configure from the drop-down list. There are five pages possible, viewable with the Tab
pushbuttons on the graphical front panel.
PAGE NAME
Range: Page 1...Page 5
Default: Page 1
Up to 20 characters can be input here as the name of each metering page. The name displays for the Tab pushbutton on
the graphical front panel.
LAYOUT
Range: 3x4, 4x6, 6x8, 6x4, 8x6, 12x8, 12x4, 16x6, 18x8
Default: 6x4
This setting determines how many rows and columns display on the graphical front panel with the metering information.
The configurable rows in the settings window change dynamically based on this setting.
CONTENT
Range: Actual, Status, Text
Default: Text
Select the type of content to display.
5 – Actual — an actual value/data. The Configure button becomes active for the actual value to be selected.
– Status — one of the operands selected from the STATUS INPUTS fields. Select it in the STATUS INDEX field.
– Text — indicates that text is to display instead of a metered value
STATUS INDEX
Range: 1...16
Default:
This field becomes active when the CONTENT field is set to Status. It selects the input from the STATUS INPUTS to display
the on/off status of the selected operand.
A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel. This field is active when the CONTENT field is set to Text or Status.
When Status is selected, the text displays when the status input is in the "on" state.
OFF TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel when the element being monitored is in an off/closed state. This
field is active when the CONTENT field is set to Status. The text displays when the status input is in the "off" state.
FONT
Range: 16, 18, 20
Default: 16
Set the font size to display on the graphical front panel.

5-36 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

TEXT COLOR
Range: 24-bit color selector
Default: Black
Set the text color to display in the specified cell.
BACK COLOR
Range: 24-bit color selector
Default: Grey
Set the background color to display in the specified cell.
ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual." The window specifies the metering
data to display.
Figure 5-10: Metering value properties window

Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the metering window. A
FlexAnalog is an analog parameter.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-37


PRODUCT SETUP CHAPTER 5: SETTINGS

Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.

5.3.3.4 Single-line diagram editor


The path is Settings > Product Setup > Graphical Panel > Single Line Diagram Editor. Use is explained in the Interfaces
chapter.

5.3.3.5 Annunciator editor


The annunciator editor is used to create annunciator content for the graphical front panel, including alarms and actual
values. Use is explained in the Interfaces chapter.
The path is Settings > Product Setup > Graphical Panel > Annunciator Editor.
To add an alarm, access the Annunciator Editor, configure the Layout and Page Name, configure the alarm or actual value,
set the text and color, then save. On the graphical front panel, view the content by pressing the Annunciator Tab
5 pushbutton at the bottom of the Home page. (Alarms do not display automatically.) Acknowledge the alarm by navigating
to it with the arrow pushbuttons, then pressing the ENTER or RESET pushbutton.
The figure shows alarms for basic functions. The last annunciator page is named Device Alarms. Alarms are set for the
device being offline, Ethernet cable issues, unauthorized access, battery failure, and high ambient temperature. They can
reset themselves when conditions return to normal, except for unauthorized access and temperature monitoring, which
require the alarms to be acknowledged. The self-test error functions, here for Ethernet and battery failures, also have been
enabled under Settings > Product Setup > User-Programmable Self Tests (not shown). When the alarms are triggered,
they display with a red background. An alarm is acknowledged by using the arrow keys on the graphical front panel then
pressing the ENTER button.

5-38 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-11: Annunciator editor with preview shown

To avoid conflict with XML programming, do not enter the following characters on the Annunciator and Metering editor
panels: " (quotation mark), ' (apostrophe), < (less than), > (greater than), & (ampersand). When used, the text following the
character does not display or the Annunciator and Metering panels do not display on the graphical front panel.
Reset
Range: ON, OFF, any FlexLogic operand
Default: OFF
This setting selects a FlexLogic operand that when activated acknowledges/resets all annunciator windows in the
graphical front panel. For example, to have the first user pushbutton resets all alarms, set this to PUSHBUTTON 1 ON
and turn on the pushbutton under Settings > Product Setup > User-Programmable Pushbuttons. This setting is the
same as the one defined in Settings > Inputs/Outputs > Resetting > Reset Annunciator. See the Resetting section later
in this chapter.
LAYOUT
Range: 3x4, 4x6, 6x8
Default: 3x4
Selects the number of rows and columns to display on the annunciator pages. For example, 3x4 means 12 windows
display per page over eight pages. Up to 96 entries are possible.
To view the layout, click the Preview button.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-39


PRODUCT SETUP CHAPTER 5: SETTINGS

PAGE NAMES
Range: up to 20 alphanumeric characters
Default: Page 1...Page 8
Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout.
The name displays for the Tab pushbutton on the graphical front panel.
PARAMETER
Range: Indicator 1...Indicator 96
Default: Indicator 1...Indicator 96
Read-only field. Up to 96 windows are possible.
CONTENT
Range: Actual, Alarm, Mixed
Default: Alarm
Select if the cell is to be an alarm, an actual value, or a combination thereof, for example consists of a single metered
value (set to “Actual”), contains a single alarm indication (set to “Alarm”), or contains both a metered value and an alarm
indication (set to “Mixed”).
ALARM INPUT
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select a trigger for the alarm, or the input signal connected to the alarm. For example, when set to "FIRST ETHERNET
FAIL" and the Ethernet cable connected to port 1 is removed, the alarm is triggered. (Note that when the Ethernet cable
is inserted into an SFP connector and the SFP connector is removed, the alarm is not triggered.) The field is read-only for
an actual value.
5 The selectable options are the FlexLogic operands specific to the product.
ALARM TYPE
Range: Acknowledgeable, Self Reset, Latched
Default: Acknowledgeable
Set the alarm type. The field is read-only for an actual value.
Acknowledgeable — Follow the state transitions, as outlined in the Annunciator section of the Interfaces chapter. The
alarm blinks until acknowledged, then remains on until the condition clears.
Self Reset — Track the state of the input operand. The alarm turns on when the trigger activates and off when the trigger
clears.
Latched — Alarm is on until acknowledged/reset individually or until the RESET button is pressed.
To acknowledge/reset/unlatch an alarm, use the arrow buttons on the graphical front panel and press the ENTER
button.
TEXT (LINE 1 to 3)
Range: up to 10 alphanumeric characters
Default:
The text that displays in the annunciator cell. Three lines can be displayed. Note that a specified metering value replaces
the text for the selected line. This means that a line can display text or be set to show an actual metered value. If the text
does not display it is because an actual metered value is over-riding it; change the line for the text or for the actual value.
TEXT COLOR
Range: 24-bit color selector
Default: White
The color to display for the three text or actual value lines specified.
BACK COLOR
Range: 24-bit color selector
Default: Red
The background color to display for any triggered cell, for example when an alarm is triggered.

5-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual" or "Mixed." The window specifies the
metering data to display.
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the annunciator alarm.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE 5
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed analog value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed analog value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
Display in Line
Range: 1, 2, 3
Default: 1
This setting specifies the line in the annunciator alarm window to display the metered value. The actual value replaces
the text for the selected line. For example, 2 means the value displays in line 2 of the text; any text configured to display
in that line does not display.

5.3.3.6 Configurable navigation


The path is Settings > Product Setup > Graphical Panel > Configurable Navigation.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-41


PRODUCT SETUP CHAPTER 5: SETTINGS

This feature allows FlexLogic operands to trigger page display on the graphical front panel. It consists of 64 setting pairs,
each with a condition and an activation page. The condition selects any FlexLogic operand. The activation page selects
any page available for the graphical front panel. The page opens whenever the selected operand transitions from Off to
On. The page remains open until rolling mode initiates, another trigger initiates from Configurable Navigation, or the Home
button is pressed.
Avoid selecting condition operands that are likely to operate simultaneously but activate different pages, as only one page
can be opened at a time. For example, do not select a single-line diagram page for breaker status open and select an
annunciator page for a trip alarm.
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure operation to work, these functions also
have been enabled under Settings > Product Setup > User-Programmable Self Tests.
Figure 5-12: Configurable navigation editor

To use the feature, select a CONDITION, select an ACTIVATE PAGE, then save.
CONDITION
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select the FlexLogic operand for the trigger. When it transitions from Off to On, it opens the page specified by the
ACTIVATE PAGE setting. The FlexLogic operands selectable depend on product. Select it from the drop-down list. Or click
or select the field and start typing to auto-fill. For example, typing F displays FIRST ETHERNET FAIL, while typing BR
displays the first breaker option.
ACTIVATE PAGE
Range: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Actual Values Phasors 1…6, Tabular 1…5, Event
Records, Targets
Default: Product Information
This setting specifies the page to display on the graphical front panel when the FlexLogic operand selected by its
CONDITON setting transitions from Off to On.
The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:
– The first annunciator page that contains an annunciator window that is in alarm (fast flash)
– The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
– The first annunciator page that contains an annunciator window that is in abnormal state
– Annunciator page 1
The Tabular option displays a configured actual values/metering page.

5-42 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The Targets option displays error messages, such as wrong transceiver, similar to event record entries.

5.3.4 Clear relay records


SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
 CLEAR RELAY CLEAR FAULT REPORTS: Range: FlexLogic operand
 RECORDS  Off

CLEAR EVENT RECORDS: Range: FlexLogic operand


 Off

CLEAR OSCILLOGRAPHY: Range: FlexLogic operand


 Off

CLEAR DATA LOGGER: Range: FlexLogic operand


 Off

CLEAR ARC AMPS 1: Range: FlexLogic operand


 Off

CLEAR ARC AMPS 2: Range: FlexLogic operand


 Off

CLEAR DEMAND: Range: FlexLogic operand


 Off

CLEAR ENERGY: Range: FlexLogic operand


 Off

CLEAR HIZ RECORDS: Range: FlexLogic operand


 Off

RESET UNAUTH ACCESS: Range: FlexLogic operand


5
 Off

CLEAR DIR I/O STATS: Range: FlexLogic operand


 Off Visible only for units with Direct I/O module

RESET UNAUTH ACCESS — Resets the access restriction counter.


Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-
programmable pushbuttons to clear specific records is a typical application for these commands. Since the F60 responds
to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-
programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-
programmable pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, apply the following settings.
1. Assign the clear demand function to pushbutton 1 by making the following change in the SETTINGS  PRODUCT SETUP
 CLEAR RELAY RECORDS menu:
CLEAR DEMAND: “PUSHBUTTON 1 ON”
2. Set the properties for user-programmable pushbutton 1 by making the following changes in the SETTINGS  PRODUCT
SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-43


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.5 Communications

5.3.5.1 Menu
SETTINGS  PRODUCT SETUP  COMMUNICATIONS
 COMMUNICATIONS  SERIAL PORTS See below
  

 NETWORK See page 5-45


 

 IPv4 ROUTE TABLE See page 5-50


 

 MODBUS PROTOCOL See page 5-53


 

 PROTOCOL See page 5-54


 

 DNP PROTOCOL See page 5-56


 

 DNP / IEC104 See page 5-59


  POINT LISTS

 IEC 61850 PROTOCOL Access in EnerVista


  See page 5-60

 WEB SERVER See page 5-108



5  HTTP PROTOCOL

 TFTP PROTOCOL See page 5-109


 

 IEC 60870-5-104 See page 5-109


  PROTOCOL

 EGD PROTOCOL See page 5-111


 

 IEC103 See page 5-112


  PROTOCOL

 USB 2.0 PORT See page 5-117


 

5.3.5.2 Serial ports


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  SERIAL PORTS
 SERIAL PORTS RS232 BAUD Range: 19200, 115200
  RATE: 115200

RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
 RATE: 19200 28800, 33600, 38400, 57600, 115200 bit/s

RS485 COM2 PARITY: Range: None, Odd, Even


 Even

RS485 COM2 RESPONSE Range: 0 to 1000 ms in steps of 10


 MIN TIME: 0 ms

The front RS232 port applies to enhanced and basic front panels.
RS232 BAUD RATE, RS485 COM2 BAUD RATE, and PARITY — The F60 is equipped with two independent serial communication
ports. The front panel RS232 port (USB port with graphical front panel) is intended for local use. The rear COM2 port is
RS485 and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the

5-44 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software, for example to download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME — This setting specifies the minimum time before the rear RS485 port transmits after
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.

5.3.5.3 Ethernet network topology


The F60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP
address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND
operation performed between their respective IP address and mask produces a different result. Communication becomes
unpredictable when more than one port is configured to the same subnet.

Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)

Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
5
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)

Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.

Single LAN, no redundancy


The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-45


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-13: Network configuration for single LAN

Public Network

SCADA

EnerVista Software

LAN1

ML3000

P1
IP1/ P2 P3
MAC1
UR
859708A2.vsd

Multiple LANS, with redundancy


5 The following topology provides local configuration/monitoring through EnerVista software and access to the public
network shared on LAN1, to which port 1 (P1) is connected. There is no redundancy provided on LAN1. Communications to
SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is the
redundant channel. In this configuration, P3 uses the IP and MAC addresses of P2.
Figure 5-14: Multiple LANs, with redundancy

Public Network

SCADA
EnerVista Software

LAN1 LAN2
LAN2

ML3000
ML3000 ML3000

P1 P2 P3
IP1/ IP2/ IP2/
MAC1 MAC2 MAC2
Redundancy mode
UR
859709A4.vsd

5-46 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Multiple LANS, no redundancy


The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected, and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
Figure 5-15: Multiple LANS, no redundancy

Public Network

SCADA
EnerVista Software

LAN1 LAN2
LAN3

ML3000
ML3000 ML3000

P1 P2 P3
IP1/ IP2/ IP3/
MAC1 MAC2 MAC3

UR
859710A2.vsd
5
5.3.5.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
Follow the IP and subnet mask rules outlined in the Set IP Address in UR section of the Installation chapter.
To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating
information, such as the serial number and order code of your device.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK  NETWORK PORT 1(3)
 NETWORK PORT 1 PRT1 IP ADDRESS: Range: standard IPV4 address format
  127.0.0.1

PRT1 SUBNET IP MASK: Range: standard IPV4 address format


 255.0.0.0

PRT1 FUNCTION: Range: Enabled, Disabled


 Enabled

 NETWORK PORT 2 PRT2 IP ADDRESS: Range: standard IPV4 address format


  127.0.0.1

PRT2 SUBNET IP MASK: Range: standard IPV4 address format


 255.0.0.0

PRT2 REDUNDANCY: Range: None, Failover, PRP


 None Range if no PRP license: None, Failover

PRP MCST ADDR: Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF


 01154E000100

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-47


PRODUCT SETUP CHAPTER 5: SETTINGS

PRT2 FUNCTION: Range: Enabled, Disabled


 Enabled

 NETWORK PORT 3 PRT3 IP ADDRESS: Range: standard IPV4 address format


  127.0.0.1

PRT3 SUBNET IP MASK: Range: standard IPV4 address format


 255.0.0.0

PRT3 FUNCTION: Range: Enabled, Disabled


 Enabled

The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
Use the front panel to change these settings. When online, the EnerVista software can be used to enable/disable each port
only. In the Offline Window area, all settings can be changed except port 2 redundancy (depending on firmware version).
When using GOOSE, in failover or PRP mode, port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP
elements has no meaning, as ports 2 and 3 use the port 2 MAC address, IP address, and mask.
PRT1 (2 or 3) IP ADDRESS — This setting sets the port’s IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) SUBNET MASK — This setting sets the port’s IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) FUNCTION — This setting enable/disables network communication on the respective port. When the port
function is Disabled, the network traffic on this port is disabled. The PRT2 redundancy setting has no effect on this
5 functionality. The change takes effect upon relay restart.
If you disable a port here that is used to communicate between the relay and the software, this can take down all
communication between the two. For example, an Ethernet connection set to the IP address of the relay can be disabled
and cannot be reached, even when pinging. The port needs to be re-enabled, IP and any gateway addresses need to be
checked, and the relay needs to be set to Programmed.
PRT2 REDUNDANCY — Determines if ports 2 and 3 operate in redundant or independent mode. If the software options in the
order code include PRP, the available options are None, Failover, and PRP. If the software options in the order code do not
include PRP, the available options are None and Failover. In non-redundant mode (REDUNDANCY set to None), ports 2 and 3
operate independently with their own MAC, IP, and mask addresses. If REDUNDANCY is set to Failover, the operation of ports
2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are hidden
• Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the
Multilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect,
acting as a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the
switch is good and that communication is healthy for five minutes, then switching back to port 2 is performed. The
delay in switching back ensures that rebooted switching devices connected to the F60, which signal their ports as
active prior to being completely functional, have time to completely initialize themselves and become active. Once
port 2 is active again, port 3 returns to standby mode.
If REDUNDANCY is set to PRP, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
• Port 2 MCST ADDRESS field is visible
• The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still
synchronizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case
for PRP networks, the port with the better connectivity is used.

5-48 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Behavior for GOOSE messages is as follows:


• If REDUNDANCY is set to Failover or PRP, In order to transmit a GOOSE message on port 2, the CID file must be
configured to have the corresponding GSE element in both ConnectedAPs S2 and S3. In the EnerVista software, the
TxGOOSE CPU PORT ASSIGNMENT needs to be "Ports-1,2,3" to transmit GOOSE on both ports 1 and 2, or "Ports-2,3" to
have GOOSE only on port 2, with failover/ PRP.
• If REDUNDANCY is set to PRP, the port 2 configured GOOSE message is simultaneously transmitted on ports 2 and 3
• If REDUNDANCY is set to failover and the port 2 link fails, then only the port 2 configured GOOSE message is transmitted
on port 3

The two ports must be connected to completely independent LANs with no single point of failure, such as common
power supplies that feed switches on both LANs.
When REDUNDANCY is set to PRP or failover and the network path with resolved default gateway is broken, then the
ARP table needs approximately five seconds to rebuild. The layer 2 protocols (GOOSE and PTP) are not affected.
However, the TCP/IP or UDP protocols (MMS connections, DNP3.0, and so on) can require reconnection if their active
connection does not ride through re-transmission frames.
For any changes to this setting to take effect, restart the unit.
PRT2 PRP MCST ADDR — This setting allows the user to change the multicast address used by the PRP supervision frames.
This setting is available if REDUNDANCY is set to PRP. All devices in the same PRP network need to have the same multicast
address. Choose an address that does not conflict with another multicast protocol.

5.3.5.5 Far-End Fault Indication (FEFI)


Since 100BASE-FX does not support Auto-Negotiation, a Far-End Fault Indication (FEFI) feature is included since UR 7 that
allows for detection of link failures.
The purpose of the Far-End Fault feature is to allow the stations on both ends of a pair of fibers to be informed when there 5
is a problem with one of the fibers. Without the Far-End Fault feature, it is impossible for a fiber interface to detect a
problem that affects only its transmit fiber.
When the Far-End Fault feature is supported, a loss of receive signal (link) causes the transmitter to generate a Far-End
Fault pattern in order to inform the device at the far end of the fiber pair that a fault has occurred.
When the local receiver again detects a signal, the local transmitter automatically returns to normal operation.
If a Far-End Fault pattern is received by a fiber interface that supports the Far-End Fault feature and it is enabled, it reacts
by dropping the link as if there were no signal at all.
If the receiving interface does not support the Far-End Fault feature or has it disabled, an incoming Far-End Fault pattern is
ignored.
It is strongly recommended to have switches used for substation automation that support the Far-End Fault feature,
especially when UR 7 redundancy Failover is selected for redundancy.

5.3.5.6 Parallel Redundancy Protocol (PRP)

The F60 is provided with optional PRP capability, specified as a software option at the time of ordering.

The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks. It applies to networks based on Ethernet technology (ISO/IEC 8802-3) and is based on the second edition (July
2012) of IEC 62439-3, clause 4.
PRP is designed to provide seamless recovery in case of a single failure in the network, by using a combination of LAN
duplication and frame duplication. Identical frames are sent on two completely independent networks that connect source
and destination. Under normal circumstances both frames reach the destination and one of them is sent up the OSI stack
to the destination application, while the second one is discarded. If an error occurs in one of the networks and traffic is

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-49


PRODUCT SETUP CHAPTER 5: SETTINGS

prevented from flowing on that path, connectivity is provided through the other network to ensure continuous
communication. Take care when designing the two LANs, so that no single point of failure (such as a common power
supply) is encountered, as such scenarios can bring down both LANs simultaneously.
Figure 5-16: Example of parallel redundant network

PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the duplicated frames. DANP devices have
an additional module, called a Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions on received frames as to which
one is sent up the OSI stack to the application layer and which one is discarded. LRE is responsible for making PRP
transparent to the higher layers of the stack.
In addition, there is a second type of specialized device used in PRP networks, called RedBox, with the role of connecting
Single Attached Nodes (SANs) to a redundant network.
UR relays implement the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy (HSR)
5 protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 version. The
revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0. The UR relays
support PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Ports 2 and 3 of the CPU module. Use the previous
section (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Ports 2 and 3) operate in redundant mode.
In this mode, Port 3 uses the MAC, IP address, and mask of Port 2.

5.3.5.7 IPv4 route table


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IPv4 ROUTE TABLE 1(6)
 IPv4 ROUTE TABLE  DEFAULT IPv4 ROUTE
  

 IPv4 NETWORK
  ROUTE 1

 IPv4 NETWORK
  ROUTE 6

A default route and up to six static routes can be configured.


The default route is used as the last choice when no other route towards a given destination is found.
 DEFAULT IPv4 ROUTE GATEWAY ADDRESS: Range: standard IPV4 unicast address format
  127.0.0.1

5-50 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

 IPv4 NETWORK RT1 DESTINATION: Range: standard IPV4 address format


 ROUTE 1  127.0.0.1

RT1 NET MASK: Range: standard IPV4 subnet mask format


 255.0.0.0

RT1 GATEWAY: Range: standard IPV4 unicast address format


 127.0.0.1

Configure the network IP and subnet settings before configuring the routing settings.

Add and delete static routes


Host routes are not supported at present.
The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of
connectivity when remotely configuring the F60.
By default, the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the
static routes are not configured. When the destination address is 127.0.0.1, the mask and gateway also must be kept on
default values.
By default, the value of the route gateway address is 127.0.0.1. This means that the default route is not configured.
To add a route:
1. Use any of the static network route entries numbered 1 to 6 to configure a static network route. Once a route
destination is configured for any of the entries 1 to 6, that entry becomes a static route and it must meet all the rules
listed in the next section, General Conditions to be Satisfied by Static Routes.
2. To configure the default route, enter a default gateway address. Once a default gateway address is configured, it 5
must be validated against condition 2 of the General Conditions to be Satisfied by Static Routes, where the route
gateway must be on a connected network.
To delete a route:
1. Replace the route destination with the default loopback address of 127.0.0.1. When deleting a route, the mask and
gateway also must be brought back to default values.
2. Delete the default route by replacing the default gateway with the default value of 127.0.0.1.

General conditions to be satisfied by static routes


The following rules are validated internally:
• The route mask has IP mask format. In binary this needs to be a set of contiguous bits of 1 from left to right, followed
by one or more contiguous bits of 0.
• The route destination and mask must match. This can be verified by checking that
RtDestination and RtMask = RtDestination
Example of good configuration: RtDestination = 10.1.1.0; Rt Mask = 255.255.255.0
Example of bad configuration: RtDestination = 10.1.1.1; Rt Mask = 255.255.255.0
The following rules must be observed when you configure static routes:
• The route destination must not be a connected network
• The route gateway must be on a connected network. This rule applies to the gateway address of the default route as
well. This can be verified by checking that:
(RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP
& Prt3Mask)
where
& is the bitwise-AND operator
== is the equality operator
|| is the logical OR operator

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-51


PRODUCT SETUP CHAPTER 5: SETTINGS

Routing behavior compared to previous releases


Prior to release 7.10, UR devices did not have an explicit manner of configuring routes. The only available route was the
default route configured as part of the network settings (port gateway IP address). This limited the ability to route to
specific destinations, particularly if these destinations were reachable through a different interface than the one on which
the default gateway was.
Starting with UR 7.10, up to six static network routes can be configured in addition to a default route. The default route
configuration was also moved from the network settings into the routing section.
The figure shows an example of topology that benefits from the addition of static routes.
Figure 5-17: Using static routes

Router1
Public network
.1

Router2
10.1.2.0/24 10.1.3.0/24
10.1.1.0/24
ML3000 ML3000 .1
EnerVista Software
P1 P2 P3
IP1/ IP2/ IP3/
.2 .2 MAC2 MAC3
MAC1

UR
5 859714A1.vsd

In the figure, the UR connects through the following two Ethernet ports:
• Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
• Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router2. Router2
has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
The behavior before release 7.10 was as follows. When sending packets to EnerVista, the UR noticed that the destination
was not on a connected network and it tried to find a route to destination. Since the default route was the only route it
knew, it used it. Yet EnerVista was on a private network, which was not reachable through Router1. Hence a destination
unreachable message was received from the router.
The configuration starting with release 7.10 is as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY =
10.1.2.1

5-52 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The behavior since release 7.10 is as follows. There is one added static network route to the destination 10.1.3.0/24, where
a computer running EnerVista is located. This static route uses a different gateway (10.1.2.1) than the default route. This
gateway is the address of Router2, which has knowledge about 10.1.3.0 and is able to route packets coming from the UR
and destined to EnerVista.

Show routes and ARP tables


This feature is available on the web page interface when using basic security and by SFTP to an Administrator when using
CyberSentry. The main menu contains an additional Communications menu and two submenus:
• Routing Table
• ARP Table
The tables outline the information displayed when the two submenus are selected.
Table 5-7: Routing table information
Field Description
Destination The IP address of the remote network to which this route points
Mask The network mask for the destination
Gateway The IP address of the next router to the remote network
Interface Interface through which the specified network can be reached

Table 5-8: IP ARP information


Field Description
IP Address The network address that corresponds to Hardware Address
Age (min)
Hardware Address
Age, in minutes, of the cache entry. A hyphen (-) means the address is local.
LAN hardware address, a MAC address that corresponds to network address
5
Type Dynamic or Static
Interface Interface to which this address mapping has been assigned

5.3.5.8 Modbus protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  MODBUS PROTOCOL
 MODBUS PROTOCOL MODBUS SLAVE Range: 1 to 254 in steps of 1
  ADDRESS: 254

MODBUS TCP PORT Range: 0 to 65535 in steps of 1


 NUMBER(502): 502

The serial communication ports utilize the Modbus protocol, unless the port is configured for DNP or IEC 60870-5-103
operation. This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave
devices only.
For more information on the protocol, including the memory map table, see the UR Family Communications Guide.
MODBUS SLAVE ADDRESS — When using the Modbus protocol on the RS232 port, the F60 responds regardless of the
MODBUS SLAVE ADDRESS programmed. For the RS485 port, each device on the serial bus must have a unique slave address
from 1 to 254. Address 0 and addresses from 248 and up are reserved by the Modbus protocol specification, and so their
use here is not recommended. Address 0 is the broadcast address to which all Modbus slave devices listen. Addresses do
not have to be sequential, but no two devices can have the same address or conflicts resulting in errors occur. Generally,
starting at 1, set each device added to the link to use the next higher address. When using Modbus TCP/IP, the client must
use the programmed MODBUS SLAVE ADDRESS value in the Unit Identifier field.
MODBUS TCP PORT NUMBER — Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502
is reserved for Modbus communications, and only in exceptional cases when MODBUS TCP PORT NUMBER is set to any other
port. The MODBUS TCP PORT NUMBER setting sets the TCP port used by Modbus on Ethernet. A MODBUS TCP PORT NUMBER of
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the F60 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-53


PRODUCT SETUP CHAPTER 5: SETTINGS

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.

5.3.5.9 Protocol selection


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  PROTOCOL& AUTHORITY
 PROTOCOL & AUTHORITY SCADA PROTOCOL: Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
  DNP 3.0

IEC61850 EDITION: Range: Edition1, Edition2


 Edition2

SFTP PROTOCOL: Range: Disabled, Enabled


 Enabled

Multi-Level Control: Range: Disabled, Enabled


 Enabled

IED Local Status: Range: Flex-Logic operand


 Off

CID FILE WRITE VIA MMS: Range: Disabled, Enabled


 Enabled

The PROTOCOL menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
SCADA PROTOCOL — This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
5 the unit.
The table shows the protocols that are operational on the RS232, RS485, and Ethernet ports. It shows all possible
combinations of the PROTOCOL and DNP CHANNEL 1(2) PORT settings.

5-54 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Table 5-9: Port and protocol combinations


PROTOCOL DNP CHANNEL 1(2) PORT RS232 RS485 Ethernet
setting settings
DNP Channel 1: Eth TCP Modbus Modbus DNP, Modbus, IEC 61850
Channel 2: Eth TCP
Channel 1: Eth TCP Modbus Modbus DNP, Modbus, IEC 61850
Channel 2: none
Channel 1: none Modbus Modbus DNP, Modbus, IEC 61850
Channel 2: Eth TCP
Channel 1: Eth UDP Modbus Modbus DNP, Modbus, IEC 61850
Channel 2: none
Channel 1: Eth TCP Modbus DNP DNP, Modbus, IEC 61850
Channel 2: RS485
Channel 1: Eth TCP DNP Modbus DNP, Modbus, IEC 61850
Channel 2: RS232
Channel 1: Eth UDP Modbus DNP DNP, Modbus, IEC 61850
Channel 2: RS485
Channel 1: Eth UDP DNP Modbus DNP, Modbus, IEC 61850
Channel 2: RS232
Channel 1: RS485 Modbus DNP DNP, Modbus, IEC 61850
Channel 2: Eth TCP
Channel 1: RS232 DNP Modbus DNP, Modbus, IEC 61850
Channel 2: Eth TCP
Channel 1: RS485 DNP DNP Modbus, IEC 61850
Channel 2: RS232
Channel 1: RS232
Channel 2: RS485
DNP DNP Modbus, IEC 61850
5
Channel 1: RS485 Modbus DNP Modbus, IEC 61850
Channel 2: none
IEC 104 Modbus Modbus IEC 104, Modbus, IEC 61850
IEC 103 Modbus IEC 103 Modbus, IEC 61850

IEC61850 EDITION — Switches between Editions 1 and 2 of the IEC 61850 protocol. For Process Bus GOOSE, the setting is
fixed at Edition 2. When switching, settings default with the change, except GGIO1, GGIO2, GGIO4, and those for the
graphical front panel. A message displays that a reboot is required, which can be done using Maintenance > Reboot Relay
Command.
SFTP PROTOCOL — Enables and disables file transfer to/from the relay by Secure Shell (SSH) and Secure File Transfer
Protocol (SFTP). This setting displays when using IEC 61850 without CyberSentry.
SETTINGS   PRODUCT SETUP  COMMUNICATIONS  PROTOCOL & AUTHORITY
 PROTOCOL & AUTHORITY MULTI-LEVEL CONTROL: Range: Disabled, Enabled
  Enabled

IED LOCAL STATUS: Range: FlexLogic operand


 Off

Multi-Level Control - When set to Enabled, control authority from multiple levels (Bay, Station and Remote) are allowed
simultaneously based on Local/Remote status and status authority status. Otherwise only one level has the authority to
control, based on Local/Remote status and status authority status.
IED Local Status - Selects an operand, that indicates the IED is in Local or Remote mode. When the operand value is set,
the IED is in Local mode and any commands from remote protocols (IEC61850) are rejected.
CID FILE Write via MMS - When set to Enabled, CID file write from MMS client is enabled, otherwise CID file write from MMS
client is not allowed.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-55


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.5.10 DNP protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL
 DNP PROTOCOL  DNP CHANNELS See below
  

DNP ADDRESS: Range: 0 to 65535 in steps of 1


 1

 DNP NETWORK See below


  CLIENT ADDRESSES

DNP TCP/UDP PORT Range: 0 to 65535 in steps of 1


 NUMBER(20000): 20000

DNP UNSOL RESPONSE Range: Enabled, Disabled


 FUNCTION: Disabled

DNP UNSOL RESPONSE Range: 0 to 60 s in steps of 1


 TIMEOUT: 5 s

DNP UNSOL RESPONSE Range: 1 to 255 in steps of 1


 MAX RETRIES: 10

DNP UNSOL RESPONSE Range: 0 to 65519 in steps of 1


 DEST ADDRESS: 1

DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000

DNP VOLTAGE SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000
5 DNP POWER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000

DNP ENERGY SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000

DNP PF SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000

DNP OTHER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
 FACTOR: 1 100000, 1000000, 10000000, 100000000

DNP CURRENT DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP VOLTAGE DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP POWER DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP ENERGY DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP PF DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1


 DEADBAND: 30000

DNP TIME SYNC IIN Range: 1 to 10080 min. in steps of 1


 PERIOD: 1440 min

DNP MESSAGE FRAGMENT Range: 30 to 2048 in steps of 1


 SIZE: 240

DNP OBJECT 1 Range: 1, 2


 DEFAULT VARIATION: 2

5-56 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

DNP OBJECT 2 Range: 1, 2, 3


 DEFAULT VARIATION: 2

DNP OBJECT 20 Range: 1, 2, 5, 6


 DEFAULT VARIATION: 1

DNP OBJECT 21 Range: 1, 2, 9, 10


 DEFAULT VARIATION: 1

DNP OBJECT 22 Range: 1, 2, 5, 6


 DEFAULT VARIATION: 1

DNP OBJECT 23 Range: 1, 2, 5, 6


 DEFAULT VARIATION: 1

DNP OBJECT 30 Range: 1, 2, 3, 4, 5


 DEFAULT VARIATION: 1

DNP OBJECT 32 Range: 1, 2, 3, 4, 5, 7


 DEFAULT VARIATION: 1

DNP NUMBER OF PAIRED Range: 0 to 32 in steps of 1


 CONTROL POINTS: 0

DNP TCP CONNECTION Range: 10 to 7200 s in steps of 1


 TIMEOUT: 120 s

DNP EVENT TIME BASE: Range: UTC, LOCAL


 LOCAL

The Distributed Network Protocol (DNP) allows for the optimization of control and data acquisition between the equipment
in the substation and the central control center. The protocol is scalable; that is, it is designed to be compatible with the
latest high speed LAN technology yet still be implemented over slower speed serial links. 5
The DNP improves upon many master-slave protocols by improving overall communication performance requirements
and provides time-stamping with millisecond accuracy.
The F60 supports DNP version 3.0.
DNP is enabled when the SETTINGS  PRODUCT SETUP  COMMUNICATIONS  PROTOCOL setting is set to DNP 3.0. The F60
can be used as a DNP slave device connected to multiple DNP masters (usually an RTU or a SCADA master station). Since
the F60 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively
communicate with the F60 at one time.
DNP is not available using the USB port on the graphical front panel.
See the UR Family Communications Guide for more information on DNP.

For any change to DNP settings, restart the relay.

The DNP Channels sub-menu is shown.


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP CHANNELS
 DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
  NONE PANEL - RS232, NETWORK - TCP, NETWORK - UDP

DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
 NONE PANEL - RS232, NETWORK - TCP

The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the DNP CHANNEL 1(2) PORT setting is set to “Network - TCP,” the channel 1(2) DNP

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-57


PRODUCT SETUP CHAPTER 5: SETTINGS

protocol can be used over TCP/IP on the Ethernet ports. When this value is set to “Network - UDP,” the DNP protocol can be
used over UDP/IP on channel 1 only. The "Front Panel - RS232" setting does not apply to the graphical front panel; when
selected the DNP client cannot establish a connection on a USB port.

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.

The DNP ADDRESS setting is the DNP slave address. This number identifies the F60 on a DNP communications link. Assign a
unique address to each DNP slave.

The F60 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the F60 can connect. The settings follow.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES
 DNP NETWORK CLIENT ADDRESS 1: Range: standard IP address
 CLIENT ADDRESSES  0.0.0.0

CLIENT ADDRESS 5: Range: standard IP address
 0.0.0.0

The DNP TCP/UDP PORT NUMBER setting is for normal DNP operation. To close the port, set the port number to 0.
The DNP UNSOL RESPONSE FUNCTION is set to “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the F60 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the F60 retransmits an
5 unsolicited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP
UNSOL RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which
solicited responses are sent is determined by the F60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the F60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000,”
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the F60 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10 times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the F60 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger
unsolicited responses from the F60 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
is set to “15.” Note that these settings are the deadband default values. DNP object 34 points can be used to change
deadband values, from the default, for each individual DNP analog input point.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the F60.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to
be necessary, which provides more robust data transfer over noisy communication channels.

Check the “DNP Points Lists” F60 web page to view the analog inputs and/or binary inputs points lists. This page
can be viewed with a web browser by entering the IP address of the F60 Ethernet port employed to access the F60
Main Menu, then by clicking the Device Information Menu item, then the DNP Points Lists item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings select the DNP default variation
number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation
0 is requested and/or in class 0, 1, 2, or 3 scans. See the DNP Implementation section in the UR Family Communications
Guide.

5-58 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the F60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The F60 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED
CONTROL POINTS setting allows configuration of 0 to 32 binary output paired controls. Points not configured as paired
operate on a one-to-one basis.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection is
aborted by the F60. This frees up the connection to be re-used by a client.

For any change to DNP settings, restart the relay.

5.3.5.11 DNP / IEC 60870-5-104 point lists


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP / IEC104 POINT LISTS
 DNP / IEC104  BINARY INPUT / MSP See below
 POINT LISTS   POINTS

 ANALOG INPUT / MME See below


  POINTS

Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic 5
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP / IEC104 POINT LISTS  BINARY INPUT / MSP POINTS
 BINARY INPUT / MSP Point: 0 Range: FlexLogic operand
 POINTS  Off

Point: 1 Range: FlexLogic operand


 Off

Point: 255 Range: FlexLogic operand
 Off

Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F60 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP / IEC104 POINT LISTS  ANALOG INPUT / MME
POINTS
 ANALOG INPUT / MME Point: 0 Range: any FlexAnalog parameter
 POINTS  Off

Point: 1 Range: any FlexAnalog parameter


 Off

Point: 255 Range: any FlexAnalog parameter
 Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-59


PRODUCT SETUP CHAPTER 5: SETTINGS

Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F60 is restarted.

The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.

5.3.5.12 IEC 61850 protocol

The F60 is provided with optional IEC 61850 communications, specified as a software option at the time of
ordering.

The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850 or Settings > IEC 61850. The settings are not
accessible from the front panel of the device.

IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing IEC 61850 messaging,
route IEC 61850 traffic on a separate port from SCADA communications, or use redundant, independent ports, and
a high-speed network recovery method, such as PRP.

Overview
5 IEC 61850 is a series of international standards and technical reports applicable to power utility automation systems. It
includes semantics, abstract communication services, specific communication services, performance specifications,
network engineering guidelines, configuration description methodologies, and engineering processes. The standard
enables interoperability among intelligent electronic devices (IEDs) from different suppliers and interoperability among
software configuration tools from different suppliers. Interoperability in this case is the ability for IEDs to operate on the
same network or communication path sharing information and commands, and for configuration tools to understand
each other's configuration files.
The UR family supports a large subset of IEC 61850 features. These are detailed in the UR Family Communications Guide
and include the information model, GOOSE publish, GOOSE subscribe, buffered report server, unbuffered report server, and
Manufacturing Message Specification (MMS) query, read, write, and control services. In addition, the URs and their
EnerVista UR Setup software support IEC 61850 Substation Configuration Language (SCL) file import/export and merging.
Many settings of UR protection, control, and monitoring elements, that is to say elements that are not concerned with the
IEC 61850 protocol, can nevertheless be accessed via IEC 61850. These settings are documented elsewhere in this Settings
chapter. This section of the Settings chapter deals solely with the settings that configure the IEC 61850 protocol itself.
The maximum number of simultaneous clients supported by the UR family is five.

IEC 61850 Editions 1 and 2


This release supports IEC 61850 Edition 1 and Edition 2. The default is Edition 2.
Select IEC 61850 Edition 1 or Edition 2 under Settings > Product Setup > Communications > Protocol. When a non-
HardFiber Process Bus Module is present, only Edition 2 is used. Switching defaults the IEC 61850 settings, except GGIO1,
GGIO2, GGIO4, and those for the graphical front panel. When a message displays that a reboot is required, use
Maintenance > Reboot Relay Command.
Edition 2.0 is used with certain modifications according to IEC/TR 61850-90-5. Only edition 2.0 61850 configuration tools
can interoperate with Edition 2.0 devices, such as the UR 7.3x, 7.4x, or 7.6x release. When using Edition 2, the UR release
uses Edition 2.0 SCL, which differs from Edition 1.0 SCL.
Fixed GOOSE, GSSE, and Edition 1 report services are not supported beyond version 7.2x. Configure UR devices using these
features to use configurable GOOSE to communicate with a 7.3x or later device.

5-60 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

When set to Edition 1


• The test flag in the Tx GOOSE message header is set to TRUE when the TEST MODE FUNCTION is set to Test or Test
Blocked
• The test flag in the received GOOSE message header is not validated
• Routable GOOSE is not supported
• Process Bus Module is not supported (order code 85, 86, or 87)
• Process Bus GOOSE is not supported
• The FlexLogic category does not display in the IEC 61850 panels in the EnerVista UR Setup software
• With SCL file import, for Edition 1 the IP address in the ConnectedAP element must match one IP address of the device,
while for Edition 2 one of the three IP addresses in the ConnectedAP element must match
The fields that display in the software depend on the Edition selected and the F60. Differences are noted in the sections
that follow. If required, consult the Model Implementation Conformance Statement (MICS) section of the UR Family
Communications Guide to understand what applies to your setup.

EnerVista setup for IEC 61850


The EnerVista UR Setup software provides the interface to configure F60 for the IEC 61850 protocol. This section describes
the interface. The software also supports import/export and merging of IEC 61850 Substation Configuration Language
(SCL) files as documented in the UR Family Communications Guide.
The IEC 61850 settings cannot be accessed through the UR front panel and are instead accessible with the UR EnerVista
Setup software, via MMS query, read, and write services, or via 61850 SCL file transfer. Accordingly, whereas other settings
are presented in this manual as they appear on the front panel, IEC 61850 settings are presented as they appear in the
software. See the UR Family Communications Guide for MMS and SCL access. Note that if you update the IEC 61850
settings in the EnerVista software by writing to them by MMS while the corresponding IEC 61850 panel is open in EnerVista,
you need to close then open the panel in EnerVista for the correct readings to display.
5
The IEC 61850 protocol settings are accessed through software panels that are selected either in the Online Window area
(see figure) or the Offline Window area in the EnerVista software.
The EnerVista software also includes an interface that is compatible with firmware versions 5.0 to 7.2 to configure
subscribers. Use the Simplified GOOSE Configurator in the Offline Window area.
Figure 5-18: IEC 61850 panel example in EnerVista software (Edition 2)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-61


PRODUCT SETUP CHAPTER 5: SETTINGS

The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
The content displayed varies with UR firmware version. For example the version 7.4 fields shown differ from the version 7.9
fields.
Figure 5-19: IEC 61850 panel (Edition 2)

Opening the IEC 61850 window while online causes the EnerVista UR Setup software to retrieve and import an SCL file from
the F60. This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request,
both those that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in
the model (that is, the "private" section). The software imports all of these settings into the current session, not just those in
the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the current session, all
other panels for the F60 must be closed before the IEC 61850 panel opens, and the software prompts for this when
required. Panels for other devices can be open concurrently to facilitate parameter coordination.
When CyberSentry security is enabled, editable settings depend on the user role logged in. For example, an Administrator
and Engineer can change settings. If prompted for a "Settings password," it means the Administrator or Engineer
password.
The Restore button restores settings in the window to their last saved values. The Default button reverts settings in the
window to factory default values on th current view or Oscillography, Data Logger, or FlexLogic Equation Editor pre-
configured values. The Reset button reverts all IEC 61850 settings to the factory default values, not just the current
window. (In other settings windows, the button reverts settings in the window to factory default values.)
When a setting is enabled, its panel continues to read Disabled until relaunched. There is no polling capability to update
automatically the IEC 61850 readings, so the panel needs to be closed then opened for the correct status to display. Good
practice is to close any panel not in use because changes being made by other users are reflected only upon relaunch of
the panel.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and can result in differences shown on a settings comparison
report.

5-62 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Create CID and settings files


A configured IED description (CID) file is created when settings are sent to the device, for example from the Offline Window
area. A CID file can be created by right-clicking a device in the Offline Window area and selecting the Save As option.
When the Save button is clicked in the online IEC 61850 window, the software prepares a CID file containing all the settings
of the device and sends the CID file to the device. Upon receipt, the F60 checks the CID file for correctness, going out of
service, then back into service when the CID file is accepted. The software displays a message when the F60 is running the
new settings, confirming successful transfer. This process can take a minute or so due to the amount of processing
required by the software and the F60.
When the Save button is clicked in the offline IEC 61850 window, the software saves to local storage, for example the hard
drive, a .urs file containing all settings of the device.

View IID/CID files


The file types are described as follows:
• IID — Instantiated IED capability description file — Actual settings on UR
• CID — Configured IED description file — Settings sent to the UR (may or may not contain the present settings)
The IID file type applies to IEC 61850 Edition 2 only.
IID and CID files are viewable. For example, after modifying settings in the IEC 61850 panels and clicking Developer IID/
CID Viewer in the software, a CID file generates and an SCL Viewer shows the updated CID file content. There are no edit
or save functions; use instead the Back Up and Restore Settings instructions later in this document to save the files.
Searches are case insensitive.
Figure 5-20: View CID settings file (Edition 2)

Server configuration
The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting. The settings vary with firmware version, IEC 61850 edition, and device capability.
IED NAME
Range: 1 to 58 VisibleString characters
Default: TEMPLATE
The value entered sets the name used by IEC 61850 for the F60. An IED name unique within the network must be entered
for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-63


PRODUCT SETUP CHAPTER 5: SETTINGS

The IED NAME and the Product LD inst name comprise the <LDName> for a product. The longest LD inst are "Master"
and "System" at six characters, with Master being fixed and the others configurable with the configurable Logical device
feature. So the IED NAME is restricted to 58 characters to meet a 64 character limit.
SUBNETWORK1(5) NAME
Range: 0 to 255 ASCII characters
Default: W1, W2, W3, W4, W5
Subnetworks 1 to 3 display for Editions 1 and 2. Subnetworks 4 and 5 display for Edition 2 with Process Bus Module.
When importing an SCL file:
– Subnetwork 1 to 3 names are identified by the contained ConnectedAP element of the target IED
– If a ConnectedAP element is missing, the respective subnetwork name uses the default value
– When the IEC 61850 server Edition is set to 1 (under Product Setup > Communications > Protocol), one
ConnectedAP is available in the SCL file. Only the respective subnetwork name is populated and editable. The rest
of the subnetwork names are read-only with default values. After importing an Edition 1 SCL file, you can select
the Access Point that needs to be populated from the Edition 1 SCL file and you can edit the subnetwork name in
the EnerVista UR Setup software.
– Subnetwork 1 to 3 names need to be unique
When exporting an SCL file:
– Subnetwork 1 to 3 names are preserved
– When the IEC 61850 server Edition is set to 1, the selected Access Point and respective subnetwork names are
populated
Access Point
Range: S1, S2, S3
5 Default: S1
This setting applies to IEC 61850 Edition 1. It is the subnetwork.
Location
Range: 0 to 255 ASCII characters
Default: Location
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.location. This data attribute is
provided by the protocol to allow the user to declare where the equipment is installed.
Latitude
Range: -90.000 to 90.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.latitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates -latitude. Negative values
indicate a southern latitude. WGS refers to the world geodetic system, which is used in global positioning systems (GPS),
and 84 is the current version of the standard.
Longitude
Range: -180.000 to 180.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.longitude. This data attribute is
provided by the protocol to declare the geographical position of the device in WGS84 coordinates -longitude. Negative
values indicate a western longitude.
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0.000 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates - altitude.

5-64 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Prefix for GGIO1


Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexLogic operand interface logical node GGIO1 that is described in the GGIO1
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. The software does not allow entry of a prefix that duplicates any other GGIO1 prefix that is
used by the product, such as ConIn and ConOut.
Prefix for GGIO2
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the Virtual Inputs Interface logical node GGIO2 that is described in the GGIO2 section
later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must
be a letter. The software does not allow entry of a prefix that duplicates any other GGIO2 prefix that is used by the
product.
Prefix for GGIO4
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexAnalog operand interface logical node GGIO4 that is described in the GGIO4
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. The software does not allow entry of a prefix that duplicates any other GGIO4 prefix that is
used by the product. 5
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION / IED MODE of the F60.
An "on" control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, a test control changes it to Test, and
a test/blocked control changes it to Test Blocked.
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting is read only. It specifies the method used to describe GOOSE subscription configuration in SCL. See the UR
Family Communications Guide for details. In the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode. The set value is for the entire EnerVista installation and is
preserved between sessions. To change this global field, click File > Preferences and access the IEC 61850 panel; the
device does not need to be connected.

Logical devices
The Edit Data Model panel contains IEC 61850 settings relevant to the configurable logical devices feature, wherein logical
device naming can be reconfigured and logical nodes re-assigned.
The path is Settings > Product Setup > Communications > IEC 61850 > Edit Data Model.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-65


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-21: Default panel with devices middle and nodes right (Edition 2)

To configure logical devices and nodes:


1. Right-click one or more entries and edit an existing device, add a new one, or move a logical node. Depending on
selection, the prefix and instance number of a node are editable, for example prefix CBArc0 and instance 30 can be
edited in CBArc0SCBR30. Nodes that are not editable are greyed-out.
5 The rest of this section explains the functions.

The default logical device categories are as follows:


• Master — Communications, including GOOSE, reports, Remote I/O, Virtual Inputs, Modbus, DNP, and setting group
control
• System — Power system devices: breakers, switches, CTs, VTs, and so on, including interfaces to these, such as AC
inputs, contact I/O, transducer I/O, HardFiber I/O
• Prot — Protection and protection-related functions
• Ctrl — Control and monitoring functions
• Meter — Metering and measurement functions
• Gen — FlexLogic, Virtual Outputs, non-volatile latches, FlexElements, recording (for example oscillography), security,
front panel, clock
• PBus — UR Process Bus Module functions, such as SV subscription, AC Banks, and process bus Time Synchronization.
Displays when order code includes a Process Bus Module. Logical device is read-only.

For the Master logical device, the following logical nodes are read-only:
• The LLN0 in the Master logical device, which includes setting group, GOOSE and report control blocks, and datasets
• LPHD1 — Models common issues for physical devices
• GGIO1 — For unmapped FlexLogic operands
• GGIO2 — For Virtual Input control
• GGIO3 — For RxGOOSE Inputs
• GGIO4 — For unmapped FlexAnalog operands
• LGOS logical nodes — For GOOSE subscription
• Process Bus Module logical nodes

5-66 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The Edit Data Model panel has middle and right panes. The middle pane has a list of the instantiated logical devices in the
sequence that they appear in SCL, with one device selected. The right pane has a list of the logical nodes presently
assigned to the selected logical device in lexicographic order by logical node name.
In the middle pane logical devices are shown with their product-related name, followed in brackets by their function-
related ldName, and followed by the value of their confRev. In the following example, by right-clicking and editing, the
Protection logical device has been set to instance name "Prot," the function-related name "Feeder1Prot" and the
configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The
next paragraphs explain how to do this setup.
Figure 5-22: Protection logical node selected

Right-clicking a logical device displays the menu that allows insertion of a new logical device immediately below the
selected one, deletion of the selected logical device, or editing the selected logical device's parameters. The insert option is
disabled and greyed-out if there are already 16 logical devices instantiated. The delete option is disabled and greyed-out if
the selected logical device is Master or it contains any logical nodes other than LLN0.
Figure 5-23: Menu for logical node

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-67


PRODUCT SETUP CHAPTER 5: SETTINGS

The Default LN Name(s) in this LD option resets logical names to default values. When the logical node name is edited, the
logical nodes pane displays the edited name followed by the default logical node name in brackets. The right-click menu at
the IED, logical device, and logical node level provides an option to default the logical node name(s) within the scope of
selection. That means that the defaulting logical node names at the IED level defaults all the logical node names in that IED
and defaulting logical node names at the logical device level defaults the logical node names in that logical device.If the
insert option is selected, or the edit option is selected for other than the Master logical device, a logical device parameters
edit dialog opens.
Figure 5-24: Insert new logical node (Edition 2)

5
If the edit option is selected for the Master logical device, the Product LD inst name setting is not editable.
Figure 5-25: Edit logical node

When the Ok button is clicked, the entered values for Product LD inst name and Functional ldName are checked for
uniqueness within the UR, and they are updated in the pane.

The settings are explained as follows, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting. When adding or editing a logical device entry, these are the fields that need to be completed.

Customized logical nodes are not saved in the URS file.

5-68 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Product LD inst name


Range: 1 to 64 VisibleString characters
Default: as per the following table
Each logical device has this setting. The value is fixed at "Master" in the first logical device and configurable in all others.
Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must be a
letter. The entered value sets the logical device inst name. Each logical device inst name is required to be unique within
the device, and it cannot be blank. Also, if the corresponding functional ldName setting is blank, the concatenation of the
IED name and the logical device inst name must form an LDName that is unique within the network for proper operation.
It is recommended that the length of the IED NAME plus the length of this setting be not greater than 64 to respect the
requirements of IEC 61850 7 2:2010 22.2 for LDName.
The factory default configuration is for six logical devices with Product LD inst name settings and logical node
assignments as per the following table.
Table 5-10: Factory default logical nodes
Default logical Contains logical nodes modeling...
device inst name
Master communications, including GOOSE, reports, Remote I/O, Virtual Inputs, Modbus, DNP, and so on.
(root logical device; Setting group control.
name is fixed) This is the root logical device.
To comply with IEC 61850 7 1 Ed2 clause 6.4.5.1, all group L logical nodes (logical nodes with class names
begin with "L"), except LLN0, belonging to this IED are in this logical device.
Protection (Prot) protection functions
Control (Ctrl) control and monitoring functions
System power system devices: breakers, switches, CTs, VTs, and so on, including interface to these such as AC inputs,
contact I/O, transducer I/O, HardFiber I/O
Metering (Meter)
General (Gen)
metering and measurement (other than PMU), including Signal Sources
FlexLogic, virtual outputs, non-volatile latches, FlexElements, FlexMath, recording (for example oscillography),
5
security, front panel, clock
Process Bus (PBus) non-HardFiber Process Bus Module when present

Functional ldName
Range: 0 to 64 VisibleString characters
Default: empty string
Each logical device has this setting. The value is configurable in all logical devices. Valid characters are upper and
lowercase letters, digits, and the underscore (_) character. If the number of characters entered is greater than zero, the
setting sets the value of the function-related name used in communications. If an ldName is entered, it must form an
LDName that is unique within the network for proper operation. The standard recommends choosing this name
according to IEC 81346-1. If the number of characters entered is zero, no function-related name is defined.

Throughout the remainder of this IEC 61850 section, <LDName> is a syntactic variable representing the present
LDName of the master logical device. In other contexts LDName can refer to some other logical device. Depending
on its context, <LDName> can be a product-related name or a function-related name.
configRev
Range: 0 to 255 ASCII characters
Default:
This data attribute is provided by the protocol to declare changes to the semantic of the data model of the UR. The intent
is that the user changes Master configRev each time that the semantic or data model changes, so that clients can
readily detect the change. A semantic change is a logical node getting a new semantic use; for example, an instance of
logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now used for
another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes, or
instance names.
The scope of Maser configRev is the entire relay configuration, as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-69


PRODUCT SETUP CHAPTER 5: SETTINGS

paramRev
Range: -2,147,483,648 to 2,147,483,647
Default: 0
The configurable data attribute paramRev has a scope that includes the entire device, and thus is modified whenever
any setting in the device changes. The UR increments the value of paramRev by one whenever one or multiple setting
changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file
download. Incrementing occurs whether or not the setting is represented in the information model. When a UR device or
EnerVista UR Setup accepts an SCL file, paramRev is set to the value in that SCL file. When EnerVista UR Setup changes
one or more settings, and prepares an SCL file, it increments paramRev to the next higher multiple of 10 000.

Each logical device has a name: LDName. (Note the upper case LD.) LDName has both a product-related form and
a function-related form as per IEC 61850 6:2009 8.5.3.
SCL files invariably use the product-related form of LDName. The product-related form is the concatenation of the
IED name of the device and the individual logical device's inst name. The IED name is the value of the "IED NAME"
setting on the Server Configuration panel, and the logical device inst names are each the value of the
corresponding "Product LD inst name" setting here. The "Product LD inst name" of the first logical device is fixed at
"Master."
Communications use the function-related form of LDName if a function-related name is defined, otherwise
communications use the product-related name. The function-related name is the value of the corresponding
"Functional ldName" setting if this setting is not empty, if empty the function-related name is not defined.
In SCL, the function-related name is specified by the LDevice element attribute ldName (note the lower case ld).
Absence of this attribute indicates the function-related name is not defined. In SCL the product-related name is
specified by the name attribute of the IED element and the inst attribute of the LDevice element.

5 In the right pane, logical nodes assigned permanently to the Master logical device and LLN0 in all logical devices are
greyed-out as shown earlier. These are not movable. Any other logical node can be dragged to any of the logical devices in
the middle pane, which causes that logical device to be re-assigned to that logical device. Right-clicking a logical node
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
Figure 5-26: Move logical node (Edition 2)

5-70 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

GOOSE
GOOSE, Routable GOOSE, and Process Bus GOOSE are supported, depending on hardware and software options.
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.

Support for Routable GOOSE


Routable GOOSE (R-GOOSE) is supported in firmware release 7.4 and later for IEC 61850 Edition 2. Routable GOOSE allows
UR and other devices to be located in separate networks. Encryption/decryption of messages is performed by a separate
gateway device. Messages are routed using a separate router, using IP addresses.
Note the following behavior, using version 7.4 as an example:
• A v7.4 device can send an R-GOOSE message to another v7.4 device when both have R-GOOSE active as the protocol
• A v7.4 device can send a GOOSE message to another v7.4 device when both have GOOSE active as the protocol
• A v7.4 device cannot send an R-GOOSE message to non-R-GOOSE devices, such as a v7.3 or v5.9 UR device
• UR devices with firmware below v7.3 can send a GOOSE message to a v7.4 device that has GOOSE as the active
protocol

R-GOOSE is available through the IEC 61850 software option. If R-GOOSE security is required, the CyberSentry
software option also is required.

GOOSE and Process Bus Modules


A Process Bus Module (order code 85, 86, or 87) is supported to subscribe to sampled value (SV) messages on the process
bus. GOOSE functionality is supported on the module, which allows both reception and transmission of GOOSE messages
in the process bus.
GOOSE publishing (TxGOOSE) on the Process Bus Module has the following limitations:
5
• A maximum of two GoCBs can be assigned to Process Bus Module ports and only the fast datasets (that are prefixed
with TT6) can be assigned to the Process Bus Module GOOSE messages
• A maximum of 64 data attributes can be published with two TT6 datasets on the Process Bus Module
• Publishing Routable GOOSE messages on a Process Bus Module is not supported
• Dynamic priority is not supported
GOOSE reception (RxGOOSE) on the Process Bus Module has the following limitations:
• A GOOSE message can be subscribed using main CPU or Process Bus Module, but the same message cannot be
subscribed from both
• For GOOSE subscription, a functional constraint data attribute (FCDA) in a given dataset cannot be subscribed more
than once
• Subscribing to Routable GOOSE messages on a Process Bus Module is not supported
On a request to save in the IEC 61850 panel in the EnerVista software, an error message displays if any of the above rules
fail. When a SCL file is imported and the validation against the above rules fail, the SCL file is rejected with an appropriate
error message in the software and UR SCL log.

TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. A TxGOOSE is a UR element implementing a single IEC 61850
GOOSE message publishing service. The subscribing function in URs is performed by RxGOOSE elements, as described in
the next section. Each UR with an IEC 61850 order code option has 16 TxGOOSE elements. Each TxGOOSE can either use
the original format specified in IEC 61850 8 1:2011 or the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified
in IEC TR 61850-90-5:2012. Each TxGOOSE element can publish the values of up to 64 attributes of the IEC 61850 nodes in
the UR.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-71


PRODUCT SETUP CHAPTER 5: SETTINGS

Published TxGOOSE messages configured in the EnerVista UR Setup software can be subscribed by and the published
operand values understood by other UR devices. Furthermore, they can be subscribed to and understood by any device of
any manufacturer that implements the IEC 61850 Edition 1.0 or 2.0 GOOSE subscription mechanism. The messages are
published with a multicast address so that the network sends the messages to all devices; any number of devices that
want to subscribe can.
For wide-area protection, control, and monitoring schemes, R-GOOSE wraps the original format GOOSE in IP/UDP to
multicast (or unicast) the data over a Wide Area Network (WAN). Sample applications are Wide area Remedial Action
Scheme (RAS) and Under Voltage / Frequency Load Shedding Schemes (UVLS/UFLS). R GOOSE uses IGMPv3 (Internet Group
Management Protocol version-3, RFC 3376) for multicasting.
The entity, device, or operand values that are published in GOOSE messages are known as members. The members are
itemized in an ordered list known as a data set. Each TxGOOSE can use any one of the configured data sets. (See the
DataSets section later for details.) The performance of a TxGOOSE is determined by its dataset. Booleans in fast GOOSE
datasets are designed for the TT6 transfer time class (3 ms), while Booleans in the Normal datasets are designed for the
TT3 class (100 ms). Due to the significant amount of CPU time required to compose a TT6 TxGOOSE message and the
limited amount of time allowed by the TT6 class, at most four of these can be configured in a given UR. So only four fast
GOOSE are allowed to be configured, and the UR software has a check to disallow the use of more than four fast datasets
in GOOSE. If six fast datasets are configured outside of UR software and the file sent directly to the relay, the relay rejects
the file. The design does allow six fast datasets to be used in report control blocks, which allows fast scanned data in
reports.
Each enabled TxGOOSE transmits its message whenever a value change is detected in one or more of its members. If the
changed value is a Boolean in a fast dataset, then the change detection occurs in the TT6 detection time of 3 ms or less. If
the member is an analog value in a fast dataset, the change detection occurs in the TT3 time of 100 ms. In Normal GOOSE
Datasets, change detection for all dataset members occurs in the TT3 time of 100 ms. To guard against the possibility that
such a message is lost in the network before it reaches all subscribers, the message is retransmitted quickly several times.
5 To allow subscribers to verify that their link to the publisher and the publisher itself are healthy, each message is also
retransmitted periodically even while the values are unchanging. These latter messages are known as heartbeat
messages, while the former are known as event messages. Heartbeat messages also enable a subscriber newly online to
receive the published values in the absence of an event.
The details of TxGOOSE message construction are contained in the UR Family Communications Guide. Knowledge of these
details is not required to configure GOOSE.
The UR does not implement the fixed-length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause A.3;
the UR always uses the ASN.1 Basic Encoding Rules (specified in ISO/IEC 8825-1) as specified in IEC 61850 Edition 1.0 and
optional in IEC 61850 Edition 2.0.

Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the
settings for the first TxGOOSE. The settings and functionality for the other entries are similar.

5-72 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-27: IEC 61850 TxGOOSE panel (Edition 2 and with Process Bus Module)

A data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.
When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottom
right of the window.
TxGOOSE1 MODE
Range for Edition 2: Disabled, GOOSE, R-GOOSE
Range for Edition 1: Disabled, GOOSE
Default: Disabled
When set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are published
in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSE
format according to IEC 61850 90-5, and the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed.
TxGOOSE1 GoCB name
Range: 0 up to 32 VisibleString characters
Default: GoCB01
The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.
An ObjectReference to the control block, which consists of the concatenation of the string "<LDName>/LLN0." and the
control block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-73


PRODUCT SETUP CHAPTER 5: SETTINGS

TxGOOSE1 GoID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate
the TxGOOSE1 messages from other GOOSE messages. Special characters are not allowed, such as <, >, &, ’, and ".
TxGOOSE1 DatSet
Range: None, TT6DataSet1,TT6 DataSet2, … TT3DataSet01,TT3 DataSet02, …
Default: None
This setting selects the published data set using the UR Setup software designator for the data set. If None is selected,
no TxGOOSE1 messages are sent.
The IEC 61850 name of the data sets are configured in the Datasets panel, as described later.
Some datasets are designed for the TT6 transfer time class (3 ms), while others are designed for the TT3 class (100 ms).
The performance of a TxGOOSE is determined by its dataset. Use TT6 datasets for trips and blocking applications, TT3
datasets for slow automatic interactions. The 61850 name of the datasets are configured in the Datasets panel.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0." and the data
set name, is published in the datSet field of TxGOOSE1 messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
To configure a DataSet, select it at the top of the window from the drop-down list. In the lower part of the window, drag
and drop configuration items to the right side. Dataset members configured here affect other Report or TxGOOSE
control blocks that use the same DataSet.
5 The performance of the TxGOOSE is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
TxGOOSE1 DST MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00 when TxGOOSE1 MODE is set to GOOSE, 00-00-00-00-00-00 when TxGOOSE1 MODE is set to
R-GOOSE
When the TxGOOSE1 MODE is set to R-GOOSE, the value of this setting is not used. If R-TxGOOSE1 DST IP is set to
multicast, the destination MAC address is derived from the configured multicast IP address. If R-TxGOOSE1 DST IP is set
to unicast IP, the UR resolves the destination MAC address using the ARP protocol. If R-TxGOOSE1 DST IP is in the range
of any of the configured static routes (first usable static route), the UR uses the gateway IP of that static route for
resolving the destination MAC. Otherwise, the UR uses the default gateway. The same is repeated on all the configured
ports of the TxGOOSE1 CPU PORT ASSIGNMENT setting.
When the TxGOOSE1 MODE setting is GOOSE, the value entered here sets the Ethernet destination MAC address in
published TxGOOSE1 messages. As the standard requires that the address have the multicast bit set TRUE, that is to say
the second digit is set to an odd number, messages transmitted have the multicast bit set TRUE no matter its value in
this setting.
The destination MAC address can be used by the network to restrict message delivery to selected devices that need to
receive them, reducing network load. This address also can be used by hardware in receiving devices to filter out
messages that are of no interest to them, reducing processor burden. Different filtering algorithms are implemented by
different devices. The standard recommends that the algorithm used by hardware of the receiving device be considered
when assigning destination multicast addresses.
Subscribers can use this address to discriminate TxGOOSE1 messages from other GOOSE messages.
After relay startup, ARP requests are sent to the gateway address (approximately within 30 seconds after relay startup).
When the ARP response is received, the ARP table is updated, and the unicast R-GOOSE messages are published with the
resolved MAC address. Every 20 minutes, the UR flushes the ARP table and rebuilds the ARP table by sending the ARP
requests.
• If the gateway router is offline, the UR retransmits the ARP requests at one second intervals for 10 seconds, and the
same sequence is repeated at approximately six minutes until the ARP response is received

5-74 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

• When the network link is disconnected, at the connection, the UR transmits the ARP messages to rebuild the ARP table
and when the ARP table is updated, the UR publishes the unicast messages. The recovery time could be up to five
minutes for publishing the unicast messages.
• Whenever a change in static route configuration, the UR transmits the ARP requests to the new gateway address
approximately after 70 seconds of static route configuration change
The resolved MAC addresses are displayed in the UR web page.
When using a Process Bus Module (order code 85, 86, or 87) and configuring multiple TxGOOSE to publish, ensure that
the MAC addresses differ. When the MAC addresses are the same, a message displays to change them, for example
"TxGOOSE1 & TxGOOSE2 assigned to PBM have the same DstMAC address. Unique DstMAC addresses are required
between the TxGOOSE for ’PB Port Assignment’ to work correctly."
TxGOOSE1 VLAN PRIORITY
Range: 0, 1, 2, 3, 4, 5, 6, 7, 5-4, 6-4, 6-5, 7-4, 7-5, 7-6
Default: 4
When the value entered is 0, 1, 2, 3, 4, 5, 6, or 7, the User Priority value in the IEEE 802.1Q VLAN tag included in published
TxGOOSE1 messages is set to that value. When one of the two-digit values is entered, the dynamic priority feature is
selected: the first event message has the User Priority value of the first digit, and User Priority is decremented in each
following message until reaching the value of the second digit. For instance, if the selected value is 7-5, then the User
Priority values in successive messages beginning with the message triggered by an event is 7, 6, 5, 5, 5, 5, 5, and so on.
Do not make a dynamic priority selection when standard behavior is required.
Network devices can forward a message with a higher priority value before a message with a lower priority value, which
speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority
messages, such as GOOSE, have priority values in the range of 4 to 7.
TxGOOSE1 VLAN ID
Range: 0 to 4095 in steps of 1
Default: 0
5
The value entered sets the VID value in the IEEE 802.1Q VLAN tag included in published TxGOOSE1 messages. VID can be
used by network devices to direct messages to only selected devices, reducing network burden. VID values of 0 and 1
are assigned by IEEE 802.1Q to other functions and are not to be used for GOOSE.
TxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
The value entered sets the APPID value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages.
The standard reserves the value range 0 to 16383 for GOOSE Type 1 (Fast messages), and reserves the value range
32768 to 41151 for GOOSE Type 1A (Trip messages). Some subscribers can process messages in the Type 1A range
faster than messages in the Type 1 range. The standard reserves the default value (0) to indicate lack of configuration.
The standard strongly recommends unique, source-orientated APPIDs within a given system.
TxGOOSE1 CONFREV
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE messages of the expected configuration revision from messages of a different revision. The standard requires
that CONFREV be incremented each time the members or the order of the members published is changed. The standard
states that the value of 0 is reserved.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-75


PRODUCT SETUP CHAPTER 5: SETTINGS

TxGOOSE1 MIN TIME


Range: 0 to 100 ms in steps of 1 ms
Default: 4 ms
If the entered time is non-zero, when a member value change is detected, four event transmissions are sent, then
heartbeat transmissions resume. The interval between the first and second event transmissions, and between the
second and third, is the time set here. The interval between the third and the fourth event transmission is double the set
time. If the entered time is zero, only a single event transmission occurs, then heartbeat transmissions resume.
TxGOOSE1 MAX TIME
Range: 1 to 59 s in steps of 1 s
Default: 10 s
This setting specifies the time interval between heartbeat messages, meaning messages that are sent periodically while
no events are detected.
TxGOOSE1 TIME ALLOWED TO LIVE
Range: 1 to 60 s in steps of 1 s
Default: 20 s
The value entered sets the timeAllowedtoLive value in published TxGOOSE1 messages. The standard requires
subscribers to assume a failure has occurred when another TxGOOSE1 message is not received within the published
timeAllowedtoLive time.
Base this setting on the TxGOOSE MAX TIME and the tolerable number of contiguous message delivery misses. For
example, if the heartbeat time is 10 s, and missing up to three successive messages is tolerable, make the setting
10 * 3 + 1 = 31 s. The extra second is to ensure that arrival of the third heartbeat transmission beats the
timeAllowedtoLive timer.
In the imported CID file, if the TxGOOSE1 TIME ALLOWED TO LIVE is greater than 60 seconds, clamp the setting value to
5 60 seconds and an information log is provided in SCL log.
TxGOOSE1 CPU PORT ASSIGNMENT
Range: Disabled, Port-1; Port-2; Port-3; Ports-1,2; Ports-2,3; Ports-1,3; Ports-1,2,3
Default: Ports-1,2,3
This setting applies to IEC 61850 Edition 2.
This setting specifies the Ethernet ports for transmission of TxGOOSE1. When set to disabled, TxGOOSE1 messages are
not transmitted on any port no matter the state of GoEna. When set to Port-1, TxGOOSE1 is published over Ethernet
Port-1 only; while selecting Ports-1, 3 option, the same TxGOOSE1 is published to both Ports 1 and 3; and similarly if set
to Ports-1, 2, 3, all ports publish TxGOOSE1.

When setting PRT2 REDUNDANCY to Failover or to PRP, the TxGOOSE 1 CPU PORT ASSIGNMENT needs to be set to
ports 2 and 3 (Ports-2,3).
Also, Port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP elements has no meaning, as ports 2
and 3 use the port 2 MAC address, IP address, and mask.
TxGOOSE1 PB PORT ASSIGNMENT
Range: Individual ports may or may not be checked (PB Port-1…PB Port-8)
Default: None of the ports are selected
This setting displays when the order code includes a non-HardFiber Process Bus Module.
When using a UR Process Bus Module, this setting specifies the Ethernet ports on the Process Bus Module for
transmission of TxGOOSE1. When none of the ports are selected, a TxGOOSE1 message is not transmitted on any port no
matter the state of GoEna. When set to PB Port-1, TxGOOSE1 is published over Process Bus Module Port-1 only. Similarly,
if all ports are selected (PB Port-1 to PB Port-8) all Process Bus Module ports publish TxGOOSE1.
When the TxGOOSE1 Mode is set to R-GOOSE, the setting is read-only.
A maximum of 64 data attributes (in one or more datasets) are allowed to transmit on all TxGOOSE messages that are
configured to transmit on the Process Bus Module.

5-76 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

R-TxGOOSE1 IP CLASS
Range: 0 to 256 in steps of 1
Default: 46
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
selects the IPv4 Differentiated Services Code Point-DSCP (formerly called TypeOfService-TOS) value. This value provides
priority routing, when supported in the routers. The default value is for Expedited Forwarding (101110B, 46 or 2EH).
R-TxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
specifies destination IP address for the R-TXGOOSE1 that is entered in Standard IPV4 address format. The destination IP
address needs to be a valid multicast or unicast IP address. The value specified in this setting is mapped to IPv4 header
32 bit field for Destination IP Address while publishing R-GOOSE1.
The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
The source IP address is that of the UR port from which the R-GOOSE messages are transmitted.
R-TxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies level of security (authentication/encryption) used for TxGOOSE1. None specifies no security
mechanisms are to be used. Signature specifies only signature (no encryption) is to be used. SignatureAndEncryption
specifies that both signature and encryption are to be used.
5

RxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages.
GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. An RxGOOSE is a UR element implementing a single IEC 61850
GOOSE message subscribing service. The publishing function in URs is performed by TxGOOSE elements, as described in
the previous section.
Each UR with an IEC 61850 order code option has 64 RxGOOSE elements. Each RxGOOSE element can subscribe to GOOSE
messages from a specified publisher. Each RxGOOSE can either use the original format specified in IEC 61850 8 1:2011 or
the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in IEC TR 61850-90-5:2012. Subscribed message
members can be DataObjects, SubDataObjects, DataAttributes, or SubAttributes. In E2-2.0 mode, members are restricted
to basic types BOOLEAN, FLOAT32, INT32, Dbpos, TimeStamp, or Quality. Each subscribed message can contain up to 64
values. A member can be a structure containing several values; note that it is the number of values rather than the number
of members that are limited to 64.
GOOSE messages from any device of any manufacturer that implements the IEC 61850 Edition 1.0 or 2.0 GOOSE publish
service or the 61850-90-5 R-GOOSE service (IEC 61850 Edition 2) can be subscribed to. The UR accepts both the variable-
length encoded GOOSE messages specified in IEC 61850 8 1:2004 and the fixed-length encoded GOOSE messages as
specified in IEC 61850 8 1:2011 clause A.3.
Each enabled RxGOOSE monitors for interruption of the GOOSE messages it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. An RxGOOSE connection is also considered lost after the UR finishes restart until a
message is received. While any RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test is activated.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-77


PRODUCT SETUP CHAPTER 5: SETTINGS

Messages that contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the
simulation field (test field in Edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to Test
or Test Blocked.
RxGOOSE messages can be received through a UR CPU module Ethernet port or a UR Process Bus Module Ethernet port. A
maximum of eight RxGOOSE messages can be received from the Process Bus Module.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages to accept. Most of these settings are configured automatically by the EnerVista UR Setup
software when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made
as described in the following sections. For IEC 61850 Edition 2, settings R-RxGOOSE1 RECEPTION MODE, R-RxGOOSE1
SECURITY, and R-RxGOOSE SRC IP need to be completed manually as the information is not contained in publisher SCL.
Read-only settings are grey.
Figure 5-28: IEC 61850 RxGOOSE Messages panel (Edition 2)

RxGOOSE1 MODE
For Ed2: Main CPU GOOSE, Main CPU R-GOOSE, Process Bus Module GOOSE
For Ed1: GOOSE
Default: Main CPU GOOSE
When set to "Main CPU GOOSE," the relay subscribes to RxGOOSE1 messages if received on any of the three main CPU
ports and if they comply with IEC 61850-8-1:2011 GOOSE format.
When set to "Main CPU R-GOOSE," the relay subscribes to RxGOOSE1 messages if received on any of the three main CPU
ports and if they comply with the R-GOOSE format according to IEC 61850-90-5.
When set to "Process Bus Module GOOSE," the relay subscribes to RxGOOSE1 messages if received on any of the eight
UR Process Bus Module ports and if they comply with IEC 61850-8-1:2011 GOOSE format.
RxGOOSE1 goID
Range: 0 to 129 VisibleString characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field. Special characters are not allowed, such as <, >, &, ’, and ".
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting.

5-78 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

RxGOOSE1 Dst MAC


Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the RxGOOSE1 MODE setting is R-GOOSE, the value of this setting is not used, the destination Media Access
Control (MAC) address for RxGOOSE1 messages is calculated based on the RxGOOSE DST IP address. Otherwise, set this
setting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this value
are accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPID
setting.
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if the logical device containing the publishing control block has "ldName"
5
configured, otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing
control block.
The F60 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName
setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the
publisher is a UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for
example "GoCB01". If the publisher is a UR 7.40 series device, <GoCBName> is as specified earlier in the TxGOOSE
section of this chapter.
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default: empty string
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting. If the publisher is a UR 7.40
series device, datSet is as specified in the DataSets section of this chapter.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-79


PRODUCT SETUP CHAPTER 5: SETTINGS

R-RxGOOSE1 RECEPTION MODE


Range: SSM, ASM, Unicast
Default: SSM
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE the value of this setting is not used. Otherwise it selects the
R-GOOSE reception mode.
R-RxGOOSE RECEPTION MODE specifies the R-RxGOOSE DST IP range. When set to SSM, R-RxGOOSE DST IP must be in
the range of 232.0.0.1 to 232.255.255.255. When set to ASM, R-RxGOOSE DST IP must be in the range of 224.0.0.1 to
239.255.255.255, excluding the SSM range. Note that the SSM range is inside the ASM range and therefore the ASM use
excludes the SSM range. The default destination IP address 224.0.0.0 is reserved, and hence not a valid multicast IP
address.
The reception modes are related to Layer-3 R-GOOSE reception from routers/WAN. The subscription to multicasting of R-
GOOSE is supported using IGMP Protocol Independent Multicast (PIM). It is made available in either Source Specific
Multicast (SSM) mode or Any Source Multicast (ASM) mode. Unicast (over UDP) mode can also be used. In case of
multicasting (IGMPv3 based SSM or ASM), the R-GOOSE subscriber device requests the Last Hop Router (LHR) to
subscribe to a specific multicasting group.
If the publisher is using a unicast destination IP address for this R-GOOSE, then set R-RxGOOSE1 RECEPTION MODE to
Unicast. Otherwise set R-RxGOOSE1 RECEPTION MODE to the SSM or ASM mode used by the local routers/firewalls.

When the R-RxGOOSE1 RECEPTION MODE is set to SSM or ASM, the F60 sends the IGMP join group report (source
specific in case of SSM) every 60 seconds and responds to IGMP general queries issued by the router.

5 R-RxGOOSE1 SRC IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 127.0.0.1
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. When the RxGOOSE1
MODE setting is R-GOOSE and the R-RxGOOSE RECEPTION MODE setting is ASM, the value of this setting is not used.
Otherwise the Source IP Address field of incoming R-GOOSE messages must exactly match this value for the message to
be accepted as a valid RxGOOSE1 message. Set this setting to the value of the source IP address used by the publisher.
For UR publishers, this value is in setting PRT# IP ADDRESS.
The UR does not validate the address entered. The default IP address 127.0.0.1 is a reserved, not a valid IP address. Enter
a valid IP source address.
R-RxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise the
Destination IP Address field of incoming R GOOSE messages must exactly match this value for the message to be
accepted as a valid RxGOOSE1 message. Set this setting to the same value as the R-GOOSE publisher's Destination IP
Address. For UR publishers, this value is in setting R-TxGOOSE# DST IP.
The destination IP address needs to be a valid multicast or unicast IP address. The UR does not validate the address
entered. The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
R-RxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.

5-80 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

This setting specifies the level of security (authentication/encryption) used for RxGOOSE1. None indicates no security
mechanisms are in use. Signature indicates only signature (no encryption) is in use. SignatureAndEncryption indicates
that both signature and encryption are in use. Normally this setting is set to match the GOOSE publisher's security
method.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, INT8U, INT16U, INT32U, FLOAT32, INT32, Dbpos (DPS), Quality, TimeStamp, ENUM, STRUCT
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the up to 64 members that the UR is able
to subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the
last member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the
publisher's data set selected by the publisher's TxGOOSE datSet setting.
If the publisher dataset includes members with structured data, that is, data attributes, sub-data objects, and/or data
attributes with sub-data attributes, configuration must use one of the new 7.40 UR Setup RxGOOSE Inputs pages. In this
case the Member setting displays as the product-related name used by the publishing IED of the data object or data
attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal).
Note that a dataset can hold at most 64 basic data attribute values, and that a single structured data object or attribute
can contain multiple basic data attribute values. UR Setup software does not allow more that 64 basic data attribute
values to be entered, in which case the last several members settings cannot be changed from End of List.
Note that the publisher's name alone does not contain all the information required for subscription, additional publisher
information model information is stored elsewhere. For this reason, manual entry of the name is not supported.

When this setting is configured manually, "Struct" and "Enum" are not allowed for selection. However, those two
values are placeholders in the software, when the RxGOOSE1 Members are configured using the ADD IED (via
5
publisher SCL file) option in the RxGOOSE Boolean/DPS/Analog Inputs screen.

RxGOOSE inputs
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean value received by a specified RxGOOSE to a FlexLogic
operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) value to four FlexLogic
operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a specified
FLOAT32, INT8U, INT16U, INT32U, INT32 and ENUM value to a FlexAnalog operand. Each of these operands reverts to its
default state when the RxGOOSE connectivity is lost. Other types of values can be present in subscribed GOOSE messages
but cannot be converted to operands.
When an RxGOOSE Input is mapped to a value in the GOOSE message, the associated q value is validated, if the q value is
included in that GOOSE message as part of the data object or if it is part of the same dataset. For such automatic mapping,
the index of associated quality value can be seen in the RxGOOSE Member field as read-only.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This allows reading of their values via MMS and allows references to them in SCL files. GGIO3
has no settings, nor is it visible in the EnerVista UR Setup software. See the UR Family Communications Guide for more
information on GGIO3.
For each configured RxGOOSE Input, the UR monitors the associated quality attribute if available. An RxGOOSE Input
reverts to its configured default value as follows:
• If the validity bits of the quality attribute (q.validity) are invalid
• If the validity bits of the quality attribute are questionable
• If the test bit of the quality attribute is set and IED Mode is other than Test or Test-Blocked
When the IED Mode setting is Test or Test-Blocked, the q.test bit is not validated. That is, when the relay is in test or test-
blocked mode, the q.test = False is treated same as q.test = True.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-81


PRODUCT SETUP CHAPTER 5: SETTINGS

When an RxGOOSE Boolean/DPS/Analog Input is mapped to a remote GOOSE message input using the publisher SCL file,
the UR automatically maps and monitors the associated quality member as follows:
• If the publisher dataset includes members with structured data
• If the publisher dataset includes data attributes and associated quality attribute is available in the same dataset (in
any sequence)
If the publisher dataset member that is mapped to RxGOOSE input is structured data, the quality attribute is embedded in
the same structure.
If the publisher dataset member that is mapped to RxGOOSE input is a data attribute, the UR scans the rest of the
attributes in that publisher dataset for a matching quality attribute.

Set up subscriptions
Subscriptions are configured in the RxGOOSE Boolean Inputs, DPS Inputs, and Analog Inputs panels.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). With SCL file import, for Edition 1 the IP address in the ConnectedAP element must
match one IP address of the device, while for Edition 2 one of the three IP addresses in the ConnectedAP element must
match. When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The
figure shows a selection being made by importing a CID file using the Add IED function.
The "Do NOT default Remote Input ID..." check box applies when configuring GOOSE subscription. It determines if the ID
field is retained or defaulted. When enabled, the ID is retained. When disabled, the ID is defaulted. For example, you
change the ID field from "RxG Bool1" to RxG Bool1west," and the change is retained when the check box is enabled. The
check box applies on drag-and-drop, manual configuration, manual deletion, deletion using the Remove IED button, and
when clicking the Default button in the RxGOOSE message panel. The Default and Reset buttons in the RxGOOSE Boolean
5 Inputs, DPS Inputs, and Analog Inputs panels default all settings in the panel, including the ID, regardless of the check box.
The check box is available for to UR version 7.4x and later devices.
To subscribe:
1. Click the Add IED button and import a file.
2. Expand the entries by clicking the + box.
3. Drag-and-drop an entry into a Subscribed to field. The software checks for duplicates.
Most of the settings are configured by drag-and-drop. Enter manually the ID, DEFAULT STATE, and EVENTS settings when
the factory default values are not acceptable.
In the example shown, all of the entries at the bottom of the screen have been added to the subscription column.

5-82 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-29: RxGOOSE subscription

RxGOOSE Boolean inputs


Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Boolean Inputs.
The number of RxGOOSE Boolean (remote inputs) is 256.
5
Figure 5-30: RxGOOSE Boolean Input panel (Edition 2)

As outlined earlier, most of the settings are configured by drag-and-drop. Enter manually the ID, DEFAULT STATE, and
EVENTS settings when the factory default values are not acceptable.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-83


PRODUCT SETUP CHAPTER 5: SETTINGS

RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". The basic and enhanced front panels display the first 17
characters of this setting plus " On" to fit the 20 character display.
The setting value is auto-populated and read-only for quality mapped to a configured remote input.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
The setting value is auto-populated and read-only for quality mapped to a configured remote input.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member which does not contain a BOOLEAN results in the
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular
Boolean subscribed to even if the member is a structure containing more than one Boolean.
The setting value is auto-populated and read-only for quality mapped to a configured remote input.
5 RxGOOSE Boolean1 DEFAULT STATE
Range: On, Off, Latest/On, Latest/Off
Default: Off
This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and
the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the
publisher. The following choices are available:
– "On" value defaults the input to logic 1
– "Off" value defaults the input to logic 0
– "Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
– "Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
RxGOOSE Boolean1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE Boolean1 FlexLogic operand are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.

RxGOOSE DPS inputs


Navigate to Settings > Product Setup > Communications > IEC 618560 > GOOSE > RxGOOSE > RxGOOSE DPS Inputs.

5-84 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-31: RxGOOSE DPS Inputs panel (Edition 2)

As outlined earlier, most of the settings are configured by drag-and-drop. Enter manually the ID, DEFAULT STATE, and
EVENTS settings when the factory default values are not acceptable.
RxGOOSE DPS1 ID
5
Range: 0 to 20 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Interm," "On," "Off," or "Bad." The basic and enhanced front
panels display the first 13 characters of this setting plus the state suffix to fit the 20 character display.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to
None, the RxGOOSE DPS1 FlexLogic operand assumes its default state.
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state. In the case that the member is a structure containing more than one Dbpos, the Subscribed
to column identifies the particular Dbpos subscribed to.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-85


PRODUCT SETUP CHAPTER 5: SETTINGS

RxGOOSE DPS1 DEFAULT STATE


Range: Intermediate-state, Off, On, Bad-state, Latest
Default: Latest
This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal and the DPS FlexLogic operands
when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and when the
RxGOOSE has lost its connection with the publisher. When this setting is selected to Latest, the value of @Master/
GGIO3.IndPosψψ.stVal is Intermediate-state when the UR has just completed start-up and the selected RxGOOSE has
not yet received a message, and the latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.

RxGOOSE analog inputs


Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Analog Inputs.
There are 32 RxGOOSE analog inputs.
Figure 5-32: RxGOOSE Analog Inputs panel (Edition 2)

As outlined earlier, most of the settings are configured by drag-and-drop. Enter manually the ID, DEFAULT STATE, and
EVENTS settings when the factory default values are not acceptable.
RxGOOSE Analog1 ID
Range: 0 to 20 characters
Default: RxG Analog1
This setting allows the user to assign descriptive text to RxGOOSE Analog1. Unlike RxGOOSE Booleans and RxGOOSE
DPS, the RxGOOSE Analog operands have fixed names, for example RxGOOSE Analog1.

5-86 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

RxGOOSE Analog1 RxGOOSE


Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message that drives the RxGOOSE Analog1 FlexAnalog operand. If set to None, the
RxGOOSE Analog1 FlexAnalog operand assumes its default state.
RxGOOSE Analog1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Analog1 FlexAnalog operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member that does not contain a FLOAT32, INT8U, INT16U,
INT32U, INT32, or ENUM results in the RxGOOSE Analog1 FlexAnalog operand assuming its default state. The Subscribed
to column identifies the particular FLOAT32 subscribed to even if the member is a structure containing more than one
FLOAT32.
RxGOOSE Analog1 DEFAULT
Range: -1000000.000 to 1000000.000 in steps of 0.001
Default: 1000.000
This setting specifies the value of the GOOSE analog input when the selected RxGOOSE has lost its connectivity with the
publisher and the RxGOOSE Analog1 DEFAULT MODE is set to "Default Value." Otherwise this setting has no effect. This
setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all
possible values can be stored. Some values can be rounded to the closest possible floating point number.
RxGOOSE Analog1 DEFAULT MODE
Range: Default Value, Last Known
Default: Default Value 5
When the selected RxGOOSE has lost its connectivity with the publisher and this setting is "Last Known," the value of the
RxGOOSE Analog1 FlexLogic operand remains at the last received value. When the selected RxGOOSE has lost its
connectivity with the publisher and this setting value is "Default Value," then the RxGOOSE Analog1 FlexLogic operand is
defined by the RxGOOSE Analog1 DEFAULT setting. After restart, until a message is received, the operand value is the
default value.
RxGOOSE Analog1 UNITS
Range: up to 4 characters
Default: empty string
This setting specifies a four-character string that is used in the actual values display of RxGOOSE Analog1.
RxGOOSE Analogs are floating-point values, with no units. The RxGOOSE UNIT and PU base settings allow the user to
configure RxGOOSE Analog, so that it can be used in a FlexElement.
RxGOOSE Analogs that represent current, voltage, power, frequency, angles, or power factor can be used in a
FlexElement. The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA,
Hz, deg, and no text (blank setting) for power factor.
RxGOOSE Analogs can be compared to other RxGOOSE Analogs with any character string or no string.
RxGOOSE Analog1 PU Base in kilo
Range: 0.000 to 1000000000.000 in steps of 0.001
Default: 1.000
This setting specifies the per-unit base value for other F60 features to use with the RxGOOSE Analog 1 FlexAnalog
operand. A FlexElement for instance subtracts two quantities after converting their values to integers rescaled to a
common base, the common base being the largest of the base values of the two quantities. If one of quantities is
RxGOOSE Analog1 and its per-unit base value is not appropriate, the rescaling operation can result in unnecessary loss
of precision or overflow in the integer result. The FlexElement Base Units table in the Settings > FlexLogic > FlexElements
section later, which tabulates the per-unit base value used by its pickup setting and implies the per-unit base used by
other FlexAnalogs, can be of use in selecting a value for the RxGOOSE Analog1 PU setting.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-87


PRODUCT SETUP CHAPTER 5: SETTINGS

Some UR elements have requirements for the type of input operands, for instance current type or voltage type. These
elements assume that RxGOOSE Analog operands are of whatever type is necessary to meet these requirements.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and a
PU base of 0.001 is 1.
When using RxGOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexElement
actual values is 2,140,000.000.
RxGOOSE Analog1 Expression
Range: None, Equal to, Not Equal to, Greater than, Less than
Default: None
This setting specifies the expression type to be used with the RxGOOSE Analog In1 FlexAnalog operand. The result of the
expression is converted into Boolean status and assigned to the RxGOOSE Analog1 Expn St operand. When the
expression result is true, RxGOOSE Analog1 Expn St operand is set. When the expression set to None, no expression is
assigned and RxGOOSE Analog1 Expn St is always in reset state.
When the expression is set to other than "None", RxGOOSE Analog In1 is compared with the configured Expression value
based on the selected Expression type.

When the remote signal type is "Float," the "Equal to" and "Not Equal to" expressions may not give accurate results
due to precision errors in decimals.

RxGOOSE Analog1 Expression Value


Range: -1000000.000 to 1000000 in steps of 1
Default: 1

5 This setting specifies the Expression value for comparison.

Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.

Report settings
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.

5-88 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.

Buffered and unbuffered reports


Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or Unbuffered
Reports.
Figure 5-33: IEC 61850 buffered report panel

An IEC 61850 Report server is an efficient method to deliver generic substation event information from a single server to a
single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-11: Number of report elements
Number
Buffered reports 30
Unbuffered reports 18

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-89


PRODUCT SETUP CHAPTER 5: SETTINGS

When using IEC 61850 Edition 2, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 or 2.0 report client requirements.
When using IEC 61850 Edition 1, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
read and acknowledged by the client to be retransmitted.
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the F60 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
Buffered Report1 RptID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the
client to discriminate Buffered Report1 messages from other messages. If the number of characters entered is zero, the
value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$BR$"BRCB01".
5 Buffered Report1 Name
Range: 0 to 32 VisibleString characters
Default: BRCB01
The entered value sets the report control block name value for Buffered Report1.
Buffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
To configure a DataSet, select it at the top of the window from the drop-down list, for example DataSet02 shown in the
previous figure. In the lower part of the window, drag and drop configuration items to the right side. For example select
the ST Ind001 stVal item and drag it to DataSet Member 1. Dataset members configured here affect other Report or
TxGOOSE control blocks that use the same DataSet.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.

5-90 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Buffered Report1 OptFlds


Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits enabled/ true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits. To reduce message size, uncheck any fields that are not needed.
Figure 5-34: Options for buffered report messages (Edition 2)

Buffered Report1 BufTm


Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the time interval in milliseconds for the buffering of events for inclusion in a single report.
Buffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits enabled / true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows. Uncheck any trigger conditions that are not needed. 5
– data-change
– quality-change
– integrity
– general interrogation (IEC 61850 Edition 2)
Buffered Report1 IntgPd
Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the period in milliseconds for generating Buffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.

Each unbuffered report has the following settings.


Unbuffered Report1 RptID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Unbuffered Report1 messages, and it can be used by
the client to discriminate Unbuffered Report1 messages from other messages. If the number of characters entered is
zero, the value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$RP$"URCB01".
Unbuffered Report1 Name
Range: 0 up to 32 VisibleString characters
Default: URCB01
The entered value sets the report control block name value for Unbuffered Report1.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-91


PRODUCT SETUP CHAPTER 5: SETTINGS

Unbuffered Report1 DatSet


Range: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Unbuffered
Report1 messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
Unbuffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Unbuffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Unbuffered Report1 OptFlds
Range: The check box for an individual bit can be enabled or not
Default: All bits enabled / true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The options are
as follows. To reduce message size, uncheck any fields that are not needed.
5 – sequence-number
– report-time-stamp
– reason-for-inclusion
– data-set-name
– data-reference
– conf-revision
For IEC 61850 Edition 2, the OptFlds bits buffer-overflow and entryID also listed are not applicable to unbuffered reports
even though the bits exist in the protocol. They are unchecked by default.
For IEC 61850 Edition 1, the entryID also listed is not applicable to unbuffered reports even though the bits exist in the
protocol. It is unchecked by default.
Unbuffered Report1 BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the time interval in milliseconds for the buffering of events for inclusion into a single report.
Unbuffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits enabled / true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows. Uncheck any trigger conditions that are not needed.
– data-change
– quality-change
– integrity
– general interrogation (IEC 61850 Edition 2)

5-92 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Unbuffered Report1 IntgPd


Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the period in milliseconds for generating Unbuffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.

DataSets
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As outlined, the members whose values are communicated by these services are itemized in an ordered list known as a
data set. Each UR with the IEC 61850 option has 18 data sets (six fast and 12 slow). Each data set can contain as many as
64 members. Any data set can be used simultaneously by any number of TxGOOSE elements and/or by any number of
Configurable Report elements. The UR software can configure any FlexLogic operands and any FlexAnalog operands as
members.
Figure 5-35: IEC 61850 DataSets (Edition 2)

UR Setup software requires data set members to be IEC 61850 data objects or data attributes with Functional Constraint
ST or MX. Certain FlexLogic and FlexAnalog operands have factory-assigned data attributes as tabulated in the UR Family
Communications Guide. All FlexLogic and FlexAnalog operands can be user-assigned to GGIO1 or GGIO4 data attributes,
so that operands without factory-assigned data attributes can still have their values published. See the GGIO1 and GGIO4
sections later for details.
Datasets used by TxGOOSE1, TxGOOSE2, and/or by reports also provide a chatter suppression service for their Boolean
members. Oscillation in a value, also known as chatter, can be caused by errors in logic programming, inadequate
hysteresis (deadband) on a threshold, or a failed station component. Chatter can flood a communications network with
GOOSE messages, degrading response time for all users. If chatter is detected in a Boolean member, TxGOOSE suspends
GOOSE event message triggering and report message triggering from that member for as long as the condition exists, and
for a minimum period of one second. While sending is suspended, a self-test message identifying the specific data item
detected as oscillating is activated.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-93


PRODUCT SETUP CHAPTER 5: SETTINGS

For a summary of the panels in which the data sets are used, the path is Settings > Product Setup > Communications >
IEC 61850 > DataSets > Summary.
For the settings, navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets > TT6DataSet1 for the
first data set.
Copy and paste functions are available when right-clicking a DataSet. They allow the target dataset to be configured
based on its order code. If some dataset items are not supported, they are not pasted, and a warning message shows a list
of dataset items that were not supported and not pasted. The DataSet name is not copied or pasted. In short, use this
feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples.
Figure 5-36: Member right-click

DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. The
value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fast
datasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSE
datasets are allowed.
An ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the
DataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,
and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An
ObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 shared by
Range: 0 to 32 VisibleString characters
Default:
Names of all control blocks that use this DataSet. Read-only field.

5-94 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.

Product setup
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup.

Security
This setting applies to IEC 61850 Edition 2.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Security.
Figure 5-37: IEC 61850 Security

SecGSAL1.SecDataClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to
SecGSAL1.SecDataClr. "sbo" here is select-before-operate.
SecGSAL1.OpCntRs ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to SecGSAL1.OpCntRs.
"sbo" here is select-before-operate.

Demand
Deadband parameters of measured values related to the Demand metering are configured here.

Energy
Deadband parameters of measured values related to the Energy metering are configured here.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-95


PRODUCT SETUP CHAPTER 5: SETTINGS

Real Time Clock


This setting applies to IEC 61850 Edition 2.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Real Time Clock.
Figure 5-38: IEC 61850 Real Time Clock

TmClkLTMS1.TmnsDelta.db
Range: 0.000 to 100.000 %
5 Default: 0.000 %
This setting is a deadband setting and is used by the relay to determine when to update the "mag" and "cVal" values
from the associated "instMag" and "instCVal" values. The value shall represent the percentage of difference between
maximum and minimum in units of 0.001%. The minimum and maximum values for TmnsDelta data object are
-500000000 ns and 500000000 ns respectively and for example, a setting value of 0.002% results in the dead banded
value of (500000000 - (-500000000)) * 0.002 / 100 = 20000 ns. The default setting value of 0.000% does not update the
"mag" and "cVal" values.

Deadband settings
A deadband is a range in which no action occurs, usually expressed as a percentage.
The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: Product Setup > Real Time
Clock, FlexLogic, Control Elements, and GGIO4. Each panel is not outlined here. The FlexLogic category applies to IEC 61850
Edition 2.
Deadband setting names all end either with "DB" or .db. As they all work the same way, but each on a different analog
value, a single description applicable to all deadband settings is given here. The analog value that each deadband setting
applies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associated
deadband setting can be found in the UR Family Communications Guide.

5-96 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-39: Deadband settings with .db suffix (Edition 2)

GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
5
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Figure 5-40: Deadband settings

Deadband settings are entered in UR Setup software in units of percent of the difference between the "max." and "min." of
the associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings
is 0.000 to 100.000% in steps of 0.001. The default value is 0.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
• Phase current — 46 x phase CT primary setting
• Neutral current — 46 x ground CT primary setting
• Ground current (sensitive ground CT) — 4.6 x sensitive ground CT primary setting
• Phase, phase-to-phase, and sequence voltage — 275 x phase VT ratio setting
• Auxiliary voltage — 275 x auxiliary VT ration setting
• Power (real, reactive, apparent, 3-phase, and 1-phase) — 4 × phase CT primary setting × 1.5 × VT Secondary setting ×
VT ratio setting

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-97


PRODUCT SETUP CHAPTER 5: SETTINGS

• Energy (real or imaginary) — 4 × phase CT primary setting × 1.5 × VT Secondary setting × VT ratio setting x 1 hour
• Frequency — 90 Hz
• Frequency rate of change — 90 Hz/s
• Power factor — 2
• Angle — 360 degrees
Select the deadband settings from knowledge of the characteristics of the power system quantity measured and
knowledge of the demands of the applications receiving the measurement via GOOSE or report such that changes of
significance to the application are promptly reported, yet the network is not overly burdened with event messages.

Signal sources
Deadband parameters of measured values related to the signal sources are configured here.

Breakers
The UR breaker control and status monitoring elements have certain settings that configure how the IEC 61850 protocol
interacts with these elements. These settings are described in this section. See the Breakers section in the System Setup
section of this chapter for details on the operation of breaker control elements.
Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that
configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and
functionality for the others are similar.
Figure 5-41: IEC 61850 Breaker panel (Edition 2)

XCBR1 TagOn ctlModel


Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for the TagOn data object in the XCBR logical
node. The IEC 61850 client must issue the control request on TagOn data object as per the selected control mode, in
order to tag/remove the tag on respective breaker element.

5-98 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

XCBR1 Pos ctlModel


Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-enhanced-security
This setting selects the control model clients must use to successfully control the breaker 1 signals marked
Bkr0XCBR1.PosOpn.ctlVal and Bkr0XCBR1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in the
Settings > System Setup section later in this chapter. These signals force a breaker 1 three-phase trip or close control
while the operand selected by setting XCBR1 ST.LOC OPERAND is not active.
"sbo" here is select-before-operate. Enhanced security means that the UR reports to the client the breaker 1 position at
the end of the command sequence.
XCBR1 Pos sboTimeout
Range: 2 to 60 s in steps of 1 s
Default: 30 s
This setting specifies the maximum time between a select and an operate command to breaker 1 signals marked
Bkr0XCBR1.PosOpn.ctlVal and Bkr0XCBR1.PosCls.ctlVal in order for the operand to be successful. This setting is only
relevant when XCBR1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.
XCBR1 BlkOpn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signal marked
Bkr0XCBR1.BlkOpn.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setup
section later. This signal when true blocks breaker 1 trip control while the operand selected by setting XCBR1 ST.LOC
OPERAND is not active.
XCBR1 BlkCls ctlModel 5
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signal marked
Bkr0XCBR1.BlkCls.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setup section
later. This signal when true blocks breaker 1 close control while the operand selected by setting XCBR1 ST.LOC OPERAND
is not active.
CSWI1 CmdBlk ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for CmdBlk DataObjects in the CSWI logical
node.
CSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signals marked
BkrCSWI1.PosOpn.ctlVal and BkrCSWI1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings >
System Setup section earlier. These signals force a breaker 1 three-phase trip or close control while the operand selected
by setting XCBR1 ST.LOC OPERAND is not active.
CSWI1 Pos sboTimeout
Range: 2 to 60 s in steps of 1 s
Default: 30 s
This setting specifies the maximum time between a select and an operate command to breaker 1 via BkrCSWI1.Pos in
order for the operand to be successful. This setting is only relevant when CSWI1 Pos ctlModel is sbo-with-normal-
security or sbo-with-enhanced-security.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-99


PRODUCT SETUP CHAPTER 5: SETTINGS

CSWI1 Pos operTimeout


Range: 0.000 to 2.000 s in steps of 0.001s
Default: 0.100 s
This setting applies to IEC 61850 Edition 2.
This setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos until
BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in
the set time.
CSWI1 BlkOpn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for BlkOpn DataObjects in the CSWI logical
node.
CSWI1 BlkCls ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for BlkCls DataObjects in the CSWI logical
node.
CSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signals marked
5 BkrCSWI1.PosOpn.ctlVal and BkrCSWI1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings >
System Setup section earlier. These signals force a breaker 1 three-phase trip or close control while the operand selected
by setting XCBR1 ST.LOC OPERAND is not active.
CSWI1 TagOn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for the TagOn data object in the CSWI logical
node. The IEC 61850 client must issue the control request on TagOn data object as per the selected control mode, in
order to tag/remove the tag on respective breaker element.

Switches
The UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850
protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >
Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.
Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to access
the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring
element. The settings and functionality for the others are similar.

5-100 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-42: Switch panel

Disc0XSWI1 TagOn ctlModel


Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for the TagOn data object in the XSWI logical 5
node. The IEC 61850 client must issue the control request on TagOn data object as per the selected control mode, in
order to tag/remove the tag on respective switch element.
XSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-enhanced-security
This setting selects the control model that clients must use to successfully control the disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings
> System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by
setting XSWI1 ST.LOC OPERAND is not active.
"sbo" here is select-before-operate. Enhanced security means that the F60 reports to the client the disconnect switch 1
position the end of the command sequence.
XSWI1 Pos sboTimeout
Range: 2 to 60 s in steps of 1 s
Default: 30 s
This setting specifies the maximum time between a select and an operate command to disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal in order for the operand to be successful. This setting is
only relevant when XSWI1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.
Disc0XSWI1 BlkOpn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signal marked
DiscCSWI1.BlkOpn.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. This
signal when true blocks disconnect switch 1 trip control while the operand selected by setting XSWI1 ST.LOC OPERAND is
not active.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-101


PRODUCT SETUP CHAPTER 5: SETTINGS

Disc0XSWI1 BlkCls ctlModel


Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signal marked
DiscCSWI1.BlkCls.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. This
signal when true blocks disconnect switch 1 close control while the operand selected by setting XSWI1 ST.LOC OPERAND
is not active.
Disc0CSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signals marked
DiscCSWI1.PosOpn.ctlVal and DiscCSWI1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings > System
Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting
XSWI1 ST.LOC OPERAND is not active.
Disc0CSWI1 Pos sboTimeout
Range: 2 to 60 s in steps of 1 s
Default: 30 s
This setting specifies the maximum time between a select and an operate command to disconnect switch 1 via
BkrCSWI1.Pos in order for the operand to be successful. This setting is only relevant when CSWI1 Pos ctlModel is sbo-
with-normal-security or sbo-with-enhanced-security.
Disc0CSWI1 Pos operTimeout
Range: 0.000 to 65.535 s in steps of 0.001s
5 Default: 5.000 s
This setting specifies the maximum time between an operate command to disconnect switch 1 via BkrCSWI1.Pos until
BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in
the set time.
Disc0CSWI1 TagOn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting determines the initial IEC 61850 control model (ctlModel) values for the TagOn data object in the CSWI logical
node. The IEC 61850 client must issue the control request on TagOn data object as per the selected control mode, in
order to tag/remove the tag on respective switch element.

Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.

5-102 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-43: Setting Groups panel (Edition 2)

Initial Setting Group


Range: 1 to 6 in steps of 1
Default: 1
The entered value sets the initial value of the non-volatile register normally controlled by the service SelectActiveSG. This
initialization occurs only on the UR reboot immediately following the receipt of a valid CID file.
This setting is not mapped into the IEC 61850 information model, but sets the value of SettingControl element attribute
actSG in SCL files.
5
The Initial Setting Group value is initialized when Control Elements > Setting Groups > Control Mode is set to
"IEC61850 Client." When Control Elements > Setting Groups > Control Mode is set to "Local," the Initial Setting Group
value is ignored, and the priority scheme selects the Active setting group immediately after initialization.

Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings
that configure the IEC 61850 protocol interface for record clear commands. The content varies with relay capability.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-103


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-44: Commands panel (Edition 2)

UFltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
5 here is select-before-operate. Enhanced security means that the F60 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
LPHD1.Sim.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This is a command that can be issued via MMS client to enable simulation mode in the relay.
Enabling the SIM CTRL VIA MMS setting allows this MMS command to be accepted by the relay.
LPHD1.TxGoSim.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This MMS command enables TxGOOSE sim Mode.
The sim attribute is set to TRUE in the published GOOSE frames from the relay so that the UR plays the simulator role
during the testing and commissioning phases.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.

5-104 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.
DatLogRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.
CBArc0SCBR1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ARC AMPS 1.
DmdMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DEMAND.
EnrMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ENERGY.

GGIO1
GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information model
5
data attributes.
For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1.
Figure 5-45: IEC 61850 GGIO1 panel (Edition 2)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-105


PRODUCT SETUP CHAPTER 5: SETTINGS

GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.

GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
Figure 5-46: GGIO2 panel (Edition 2)

GGIO2 CF SPCSO 1 CTLMODEL


Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control Virtual Input 1. "sbo" here is select-before-
operate.
GGIO2 CF SPCSO 2 CTLMODEL
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
Selects the control model for Virtual Input 2, and so on.

GGIO4
GGIO4 is a UR feature that allows up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information model
data attribute.
For the value of a FlexAnalog operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO4 allows those FlexAnalog operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.

5-106 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the
settings for the first GGIO4 value. The settings and functionality for the others are similar.
Figure 5-47: GGIO4 panel (Edition 2)

ANALOG IN 1 VALUE
Range: any FlexAnalog operand
Default: OFF
This setting selects the FlexAnalog operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO4.AnIn01.instMag.f. The value of the FlexAnalog operand is converted automatically to the format and 5
scaling required by the standard, that is to say primary amperes, primary volts, and so on. See Appendix A for a list of
FlexAnalog operands.
ANALOG IN 1 DB
Range: 0.000 to 100.000% in steps of 0.001
Default: 0.000%
This setting specifies the deadband for the ANALOG IN 1 VALUE. The deadband is used to determine when to update the
deadbanded magnitude from the instantaneous magnitude. The deadband is a percentage of the difference between
the "max." and "min." values. Here, the "max." and "min." are as specified by the settings ANALOG IN 1 MAX and ANALOG IN
1 MIN.
See the Deadband Settings section earlier for a description of deadbanded values.
ANALOG IN 1 MIN
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
This setting specifies the "min." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
ANALOG IN 1 MAX
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 1000000.000
This setting specifies the "max." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-107


PRODUCT SETUP CHAPTER 5: SETTINGS

File transfer by IEC 61850


The F60 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an
example.
1. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
2. Select the Remote AR Name from the drop-down list. Available files appear in the File Specification area on the right
side of the window.
3. With the Copy option active, select a file to transfer and click the Go button. The file is copied and displays in the Local
list on the left side of the window.
4. Repeat the process to transfer any other files.
Figure 5-48: File transfer by IEC 61850

5.3.5.13 Web server HTTP protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  WEB SERVER HTTP PROTOCOL
 WEB SERVER HTTP TCP PORT Range: 0 to 65535 in steps of 1
 HTTP PROTOCOL  NUMBER(80): 80

The F60 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the F60 “Main Menu.” Web pages are read-only and are available
showing IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the F60 and a
computer to an Ethernet network, then enter the IP address of the F60 Ethernet port in a web browser.
To close the port, set the port number to 0.
Any change takes effect when the F60 is restarted.

5-108 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-49: Example of UR web page showing event records

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.

5.3.5.14 TFTP protocol


5
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  TFTP PROTOCOL
 TFTP PROTOCOL TFTP MAIN UDP PORT Range: 0 to 65535 in steps of 1
  NUMBER(69): 69

TFTP DATA UDP PORT 1 Range: 0 to 65535 in steps of 1


 NUMBER: 0

TFTP DATA UDP PORT 2 Range: 0 to 65535 in steps of 1


 NUMBER: 0

The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F60 over a network. The F60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained
from the F60 contains a list and description of all available files, for example event records and oscillography.
The "put" function is not for security reasons. You can enter a "get" command but not a "put" command.
TFTP MAIN UDP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the F60 is
restarted.

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.

5.3.5.15 IEC 60870-5-104 protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-104 PROTOCOL
 IEC 60870-5-104 IEC TCP PORT Range: 0 to 65535 in steps of 1
 PROTOCOL  NUMBER(2404): 2404

 IEC NETWORK See below


  CLIENT ADDRESSES

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-109


PRODUCT SETUP CHAPTER 5: SETTINGS

IEC COMMON ADDRESS Range: 0 to 65535 in steps of 1


 OF ASDU: 0

IEC CYCLIC DATA Range: 1 to 65535 s in steps of 1


 PERIOD: 60 s

IEC CURRENT DEFAULT Range: 0 to 100000000 in steps of 1


 THRESHOLD: 30000

IEC VOLTAGE DEFAULT Range: 0 to 100000000 in steps of 1


 THRESHOLD: 30000

IEC POWER DEFAULT Range: 0 to 100000000 in steps of 1


 THRESHOLD: 30000

IEC ENERGY DEFAULT Range: 0 to 100000000 in steps of 1


 THRESHOLD: 30000

IEC PF DEFAULT Range: 0.00 to 1.00


 THRESHOLD: 1.00

IEC OTHER DEFAULT Range: 0 to 100000000 in steps of 1


 THRESHOLD: 30000

IEC REDUNDANCY Range: No, Yes


 ENABLED: No

IEC EVENT TIME BASE: Range: Local, UTC


 LOCAL

IEC 60870-5-104 is a transmission protocol for network access, specifically for communication between a control station
and substation over a TCP/IP network.
5 The F60 supports the IEC 60870-5-104 protocol. This protocol is enabled when the SETTINGS  PRODUCT SETUP 
COMMUNICATIONS  PROTOCOL setting is set to IEC 60870-5-104. The F60 can be used as an IEC 60870-5-104 slave device
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F60 maintains two
sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the F60 at one
time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the F60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the F60 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD
setting is set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured
value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the F60, the default thresholds are in effect.
The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
IEC TCP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the F60 is restarted.
IEC COMMON ADDRESS OF ASDU — The change takes effect when the F60 is restarted.
IEC CYCLIC DATA PERIOD — The change takes effect when the F60 is restarted.

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.

SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-104 PROTOCOL  IEC NETWORK CLIENT
ADDRESSES
 IEC NETWORK CLIENT ADDRESS 1: Range: standard IPV4 address format
 CLIENT ADDRESSES  0.0.0.0

5-110 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

CLIENT ADDRESS 5: Range: standard IPV4 address format


 0.0.0.0

The F60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the F60 can connect. A maximum of two simultaneous connections are supported at any given time.

5.3.5.16 EGD protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL
 EGD PROTOCOL  FAST PROD EXCH 1 See below
   CONFIGURATION

 SLOW PROD EXCH 1 See below


  CONFIGURATION

 SLOW PROD EXCH 2 See below


  CONFIGURATION

The F60 is provided with optional Ethernet Global Data (EGD) communications capability, specified as a
software option at the time of ordering.

Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD data
exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
The relay supports one fast EGD exchange and two slow EGD exchanges. There are 20 data items in the fast-produced
EGD exchange and 50 data items in each slow-produced exchange. 5
EGD cannot be used to transfer data between UR series relays. The relay supports EGD production only. An EGD exchange
is not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid
Modbus register address. The default setting value of “0” is considered invalid.
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The F60 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the fast EGD exchange follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL FAST PROD EXCH 1 CONFIGURATION
 FAST PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable
 CONFIGURATION  Disable

EXCH 1 DESTINATION: Range: standard IP address


 0.0.0.0

EXCH 1 DATA RATE: Range: 50 to 1000 ms in steps of 1


 1000 ms

EXCH 1 DATA ITEM 1: Range: 0 to 4294967295 in steps of 1 (Modbus


 0 register address range)

EXCH 1 DATA ITEM 20: Range: 0 to 4294967295 in steps of 1 (Modbus
 0 register address range)

The settings menu for the slow EGD exchanges follows.


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL SLOW PROD EXCH 1(2) CONFIGURATION
 SLOW PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable
 CONFIGURATION  Disable

EXCH 1 DESTINATION: Range: standard IP address


 0.0.0.0

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-111


PRODUCT SETUP CHAPTER 5: SETTINGS

EXCH 1 DATA RATE: Range: 50 to 1000 ms in steps of 1


 1000 ms

EXCH 1 DATA ITEM 1: Range: 0 to 4294967295 in steps of 1 (Modbus


 0 register address range)

EXCH 1 DATA ITEM 50: Range: 0 to 4294967295 in steps of 1 (Modbus
 0 register address range)

Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are as follows.
EXCH 1 DESTINATION — This setting specifies the destination IP address of the produced EGD exchange. This is usually
unicast or broadcast.
EXCH 1 DATA RATE — This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms, the
exchange data is updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data is updated and sent
once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a setting range of 500 to
1000 ms.
EXCH 1 DATA ITEM 1 to 20/50 — These settings specify the data items that are part of this EGD exchange. Almost any data
from the F60 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus
register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications
Guide for the addresses. To convert a hexadecimal address to decimal, add a 4 before it for an actual values address and a
3 before a settings address. For example, hexadecimal actual value 82A0 becomes 482A0, which converts to 295584
decimal.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.

5 That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values), only the
first Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus addresses
and the fourth is 0, the produced EGD exchange contains three data items.

5.3.5.17 IEC 60870-5-103 protocol


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103
 IEC103 IEC103 COMMON Range: 0 to 254 in steps of 1
 PROTOCOL  ADDRESS OF ASDU: 0

IEC103 SYNC TIMEOUT: Range: 1 to 1440 min in steps of 1


 1

 IEC103 INPUTS See below


  BINARY

 IEC103 INPUTS See below


  MEASURANDS

 IEC103 COMMANDS See below


 

The F60 is provided with optional IEC 60870-5-103 communications capability, specified as a software option
at the time of ordering.

IEC 60870-5-103 is a companion standard to the IEC 60870-5 suite of standards for transmission protocols. It defines
messages and procedures for interoperability between protection equipment and devices of a control system in a
substation for communicating on a serial line.
The IEC 60870-5-103 protocol is enabled when the SETTINGS  PRODUCT SETUP  COMMUNICATIONS  PROTOCOL setting
is set to IEC 60870-5-103.

5-112 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication, exchanging
information with a control system. In the context of this protocol, the protection equipment is the slave and the control
system is the master. The communication is based on a point-to-point principle. The master must be able to interpret the
IEC 60870-5-103 communication messages.
The UR implementation of IEC 60870-5-103 consists of the following functions:
• Report binary inputs
• Report analog values (measurands)
• Commands
• Time synchronization
The RS485 port supports IEC 60870-5-103.
The UR Family Communications Guide contains more information on the protocol.
IEC103 COMMON ADDRESS OF ASDU — This setting uniquely defines this F60 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is
recommended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range
of 254 addresses is never exhausted.
IEC103 SYNC TIMEOUT — This setting defines the time that the F60 waits for a synchronization message. The F60
synchronizes its clock using all available sources, with the source synching more frequently overwriting the time of the
other sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B,
PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs
and none of IRIG-B, PTP, or SNTP is active, the F60 sets the invalid bit in the time stamp of a time-tagged message.
The settings for the remaining menus are outlined as follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 INPUTS BINARY
 IEC103 INPUTS
  POINT 0 See below 5
 BINARY 

 POINT 1 See below


 

 POINT 95 See below
 

 POINT 0 POINT 0 FUN Range: 0 to 255 in steps of 1


  0

POINT 0 INF Range: 0 to 255 in steps of 1


 0

POINT 0 Input Range: FlexLogic operand


 Off

 POINT 95 POINT 95 FUN Range: 0 to 255 in steps of 1
  0

POINT 95 INF Range: 0 to 255 in steps of 1


 0

POINT 95 Input Range: FlexLogic operand


 Off

The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-113


PRODUCT SETUP CHAPTER 5: SETTINGS

For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the F60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
For any change to take effect, restart the relay.

SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 INPUTS MEASURANDS


 IEC103 INPUTS  ASDU 1 See below
 MEASURANDS  

 ASDU 4
 

 ASDU 1 ASDU 1 TYP: Range: 3 or 9


  9

ASDU 1 FUN: Range: 0 to 255 in steps of 1


 0

ASDU 1 INF: Range: 0 to 255 in steps of 1


 0

5  ASDU 1 SCAN TOUT:


0
Range: 0 to 1000 s in steps of 1

ASDU 1 ANALOG 1 Range: FlexAnalog parameter


 Off

ASDU 1 ANALOG 1 Range: 0.000 to 65.535 in steps of 0.001


 FACTOR: 1.000

ASDU 1 ANALOG 1 Range: -32768 to 32767 in steps of 1


 OFFSET: 0

ASDU 1 ANALOG 9 Range: FlexAnalog parameter
 Off

ASDU 1 ANALOG 9 Range: 0.000 to 65.535 in steps of 0.001


 FACTOR: 1.000

ASDU 1 ANALOG 9 Range: -32768 to 32767 in steps of 1


 OFFSET: 0

 ASDU 4 ASDU 4 TYP: Range: 3 or 9
  9

ASDU 4 FUN: Range: 0 to 255 in steps of 1


 0

ASDU 4 INF: Range: 0 to 255 in steps of 1


 0

ASDU 4 SCAN TOUT: Range: 0 to 1000 s in steps of 1


 0

ASDU 4 ANALOG 1 Range: FlexAnalog parameter


 Off

5-114 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

ASDU 4 ANALOG 1 Range: 0.000 to 65.535 in steps of 0.001


 FACTOR: 1.000

ASDU 4 ANALOG 1 Range: -32768 to 32767 in steps of 1


 OFFSET: 0

ASDU 4 ANALOG 9 Range: FlexAnalog parameter
 Off

ASDU 4 ANALOG 9 Range: 0.000 to 65.535 in steps of 0.001


 FACTOR: 1.000

ASDU 4 ANALOG 9 Range: -32768 to 32767 in steps of 1


 OFFSET: 0

The configuration menu allows a maximum of four ASDUs containing measurands.


Measurands are sent as a response to Class 2 requests, which are cyclic requests coming from the master.
TYPE IDENTIFICATION (TYP) — The configuration field TYP indicates how many measurands are present in the corresponding
ASDU. Each ASDU can take either 4 or 9 measurands maximum, depending on the type identification (3 respectively 9). For
any change to take effect, restart the relay.
FUNCTION TYPE (FUN) and INFORMATION NUMBER (INF) — These two fields form the Information Object Identifier of the ASDU
as defined in IEC 60870-103. For any change to take effect, restart the relay.
SCAN TIMEOUT (SCAN TOUT) — This is the cyclic period used by the F60 to decide when a measurand ASDU is included in a
response. The measurand is sent as response to a Class 2 request when the corresponding timeout expires. The default
value 0 means 500 ms.
ANALOG # — This field contains the actual measurand to be sent in the response to the master. The measurands can be
mapped using elements from a list of FlexAnalog operands. The measurands sent are voltage, current, power, power 5
factor, and frequency. If any other FlexAnalog is chosen, the F60 sends 0 instead of its value. Note that the power is
transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I,
respectively measurands II).
Each IEC 60870-5-103 measurands list ends at the first unconfigured ("Off") value. Any measurand assigned after the first
"Off" value is ignored.
At least one measurand per ASDU must be configured in order to configure the following ASDU. For example, the user can
configure only one measurand for each ASDU, but the user is not allowed to skip ASDU 2 and configure measurands in
ASDU 3.
For any change to take effect, restart the relay.
ANALOG # FACTOR and OFFSET — For each measurand included in the ASDU, a factor and offset also can be configured. The
factor and offset allow for scaling to be performed on measurands. The final measurement sent to the IEC 60870-103
master is then "a*x + b," where x is the measurand, a is the multiplying factor and b is the offset. The master has to perform
the reversed operation in order to retrieve the actual value if such scaling is done. By default a = 1 and b = 0, so no scaling
is done if these values are left at their defaults. Examples of when scaling is appropriate are as follows:
• If the measured value contains decimals and it is important to preserve the resolution. Since the format for
transmitting the measurand does not permit decimals, a factor a>1 can be applied before transmission. For example,
a frequency F=59.9Hz can be transmitted as Ft = 10 * F = 10 * 59.9 = 599. In this case a = 10, b = 0. The master receives
599 and has to divide by 10 to retrieve the real value 59.9.
• If the measured value is larger than what fits in the format defined in IEC 103. The format defined in the standard
allows for signed integers up to 4095. By offsetting, unsigned integers up to 4096 + 4095 = 8191 are supported.
Scaling using factors <1 can be required in such cases. The calculation is outlined in the IEC 60870-5-103 chapter of
the UR Family Communications Guide. Two examples follow, where you decide factors a and b.
Example 1: Nominal power Pn = 100 MW = 100000 KW (power is transmitted in KW)
Since P can be both positive and negative:
Transmitted power Pt = (4095/(Pn*2.4)) * P = (4095/(100000 * 2.4) ) * P
= 0.017 * P

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-115


PRODUCT SETUP CHAPTER 5: SETTINGS

a = 0.017
b=0
Pt = 0.017 * P
For a max power 100000 KW * 2.4 = 240000 KW, we transmit
Pt = 0.017 * 240000 = 4080
A value above 240 MW is indicated by overflow.

Example 2: Nominal voltage Vn = 500000 V


Since RMS voltage V can be only positive:
Transmitted voltage Vt = (8191/(Vn*2.4)) * V - 4096 =
= (8191/(500000 * 2.4) ) * V - 4096 = 0.0068 * V - 4096
a = 0.0068
Since the step is in increments of 0.001, we round it at:
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000 V * 2.4 = 1200000 V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104

SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 COMMANDS


5  IEC103 COMMANDS
   COMMAND 0

See below

 COMMAND 1
 

 COMMAND 31
 

 COMMAND 0 COMMAND 0 FUN: Range: 0 to 255 in steps of 1


  0

COMMAND 0 INF: Range: 0 to 255 in steps of 1


 0

COMMAND 0 ON: Range: Virtual input


 Off

COMMAND 0 OFF: Range: Virtual input


 Off

 COMMAND 31 COMMAND 31 FUN: Range: 0 to 255 in steps of 1
  0

COMMAND 31 INF: Range: 0 to 255 in steps of 1


 0

COMMAND 31 ON: Range: Virtual input


 Off

COMMAND 31 OFF: Range: Virtual input


 Off

5-116 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the F60. This includes 128 virtual inputs (see the following table). The ON and
OFF for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
Description Value
Off 0
Virtual Input 1 1
Virtual Input 2 2
... ...
Virtual Input 128 128

For any change to take effect, restart the relay.

5.3.5.18 USB port


SETTINGS  PRODUCT SETUP  COMMUNICATIONS  USB 2.0
 USB 2.0 USB DEVICE PORT Range: Disabled, Enabled
  FUNCTION: Enabled

This setting applies to the USB port on the graphical front panel. 5
This setting enables/disables the USB port on the graphical front panel. When the port function is "Enabled," a standard
USB serial cable allows a computer running the EnerVista UR Setup software to retrieve, display, and write settings either
individually or collectively, to display status and actual values, to initiate controls, and to retrieve and display event records,
oscillography records, data logger records, and disturbance records. Installation of the EnerVista software automatically
installs the drivers required to use this USB port.
DNP is not available using the USB port on the graphical front panel.

5.3.6 Modbus user map


SETTINGS  PRODUCT SETUP  MODBUS USER MAP
 MODBUS USER MAP ADDR 1: 0 Range: 0 to 65535 in steps of 1
  VALUE: 0

ADDR 256: 0 Range: 0 to 65535 in steps of 1
 VALUE: 0

The Modbus user map provides read-only access for up to 256 registers. The memory map can be read from the front
panel, the UR Family Communications Guide, or in a web browser. For the web browser, enter the IP address of the F60 and
click a Modbus Memory Map option.
On the front panel, the address to read a specific Modbus register depends on whether the requested value is a setting or
an actual value.
Up to firmware version 7.8x, the settings and actual values are in the same Modbus table. To obtain a memory map value,
enter its address on the front panel.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-117


PRODUCT SETUP CHAPTER 5: SETTINGS

Starting in firmware version 7.90, the settings have their own Modbus memory table and the actual values are in their own
table. To obtain a memory map value, use the following sequence:
1. Obtain the hexadecimal Modbus address of the data item. It must have four digits, such as 024A.
2. Prefix the address by 3 for settings or by 4 for actual values.
3. Convert the resulting hexadecimal number to decimal.
4. Enter the resulting number in the first column of the Modbus user map. The corresponding value (if programmed)
displays in second column (VALUE). A value of "0" in subsequent register lines automatically returns values of Modbus
registers having the address of the previous line incremented by 1. These subsequent addresses are all in the same
Modbus table (settings or actual values) as the address that was entered.
An address value of "0" in the initial register means "none" and values of "0" display for all registers.
Different address values can be entered as required in any of the register positions.
Here are two examples of how to add a setting or actual value to the front panel Modbus user map.
To add the setting "Phase TOC 1 Pickup" to the Modbus user map:
1. Find the address of the setting "Phase TOC 1 Pickup," which is 334Eh (334E in hexadecimal format).
2. Prefix this address by 3 to obtain 3334Eh.
3. Convert this value to decimal to obtain 209742 and enter it on the front panel.
To add the actual value "SRC 1 Frequency" to the Modbus user map:
1. Find the address of the actual value "SRC 1 Frequency," which is 1D80h.
2. Prefix this address by 4 to obtain 41D80h.
3. Convert this value to decimal to obtain 269696 and enter it on the front panel.

5 5.3.7 Real-time clock

5.3.7.1 Menu
SETTINGS  PRODUCT SETUP  REAL TIME CLOCK
 REAL TIME SYNCRONIZING SOURCE: Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
 CLOCK  None Other, PP/PTP/IRIG-B/Other, PBM Clock

REAL TIME CLOCK EVENTS: Range: Enabled, Disabled


 Disabled

IRIG-B SIGNAL TYPE: Range: None, DC Shift, Amplitude Modulated


 None

 PRECISION TIME See below


  PROTOCOL (1588)

 SNTP PROTOCOL See below


 

 LOCAL TIME See below


 

 PBM PTP See below


 

The relay contains a real time clock (RTC) to create time stamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
time delivered to the relay. While the RTC is not synchronized via PTP or IRIG-B, or the relay determines that it has an offset
possibly greater than 10 µs from the international time standard, the CLOCK UNSYNCHRONIZED FlexLogic operand is
activated.

5-118 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The SYNCHRONIZING SOURCE setting displays in the software when the relay includes the IEEE 1588 software option. The
setting configures the priority sequence of the time synchronization source, to determine which of the available external
time sources to use for time synchronization. A setting of None causes the RTC and the synchrophasor clock to free-run,
and the clock can be changed from the front panel or from communications protocols. A setting of PP/IRIG-B/PTP/Other,
IRIG-B/PP/PTP/Other, or PP/PTP/IRIG-B/Other causes the relay to track the first source named that is enabled and
operational, or free-run if none of these are available. Here, PP means a time source that is strictly compliant with PP, PTP
means a time source that is not strictly compliant with PP, and Other means any less precise source (SNTP, IEC 103, IEC 104,
Modbus, or DNP). When a time source fails or recovers, the relay automatically transfers synchronization as required by
this setting.
Selecting “PBM Clock” causes the relay to use the time source from any non-HardFiber Process Bus Module clock. If the
Process Bus Module PTP FUNCTION setting is enabled and PTP grandmaster is available in the process bus network, the
Process Bus Module clock is synchronized to the PTP grandmaster, else the Process Bus Module clock free-runs. A UR can
use a synchronizing source either from the real-time clock (main CPU) or a Process Bus Module, as outlined in Settings >
Product Setup > Real Time Clock > PBM PTP.
Note that a UR does not need to be time synchronized to accept the sampled values. All the elements (protection, control,
monitoring, logic, and so on) in the UR (except Line Current Differential element) remain fully functional without requiring
any external synchronizing source for the UR, as long as all the sampled values subscribed by the relay are synchronized
according to the Settings > Process Bus Module > General > SmpSynch Check setting and pass the other acceptance
criteria as defined in Settings > Process Bus Module > SV Stream Config > Logic.

Some UR applications like oscillography, event recorder, and datalogger use the real-time clock for time-stamping.

When the relay does not have the IEEE 1588 software option and this setting does not display, it uses IRIG-B when enabled
and operational, then failing that SNTP when configured and operational, and otherwise it free-runs unless the clock is
changed from the front panel or from communications protocols.
5
Setup for IRIG-B is illustrated in the Installation chapter.
For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the F60
clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time
synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP,
are active in the system. If IRIG-B or PTP is used to update the relay clock, the other protocols (such as SNTP) are not
allowed to update, even if active.
See the COMMANDS  SET DATE AND TIME menu section of this manual to manually set the RTC.

When 1 ms accuracy is required for events, oscillography, time stamping, synchrophasors, and 87L asymmetry
with respect to the master clock, the PTP clock needs to be connected to the CPU of a relay. The 1 ms accuracy
cannot be maintained if the CPU of the relay is synchronized through the Process Bus Module due to a delay up to 2
ms in transmitting a time stamp from the Process Bus Module to a CPU.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment. A Date/Time Changed event is generated when:
• The real time clock changed from SNTP/PTP/IRIG-B and the time difference is more than one second
• The real time clock changed from the front panel or via Modbus register. The relay always generates this event
regardless of the time difference.
• The Daylight Saving Time (DST) setting gets enabled and the current relay time is already in the DST zone
• The real time clock enters or leaves DST
To enable IRIG-B synchronization, the input IRIG-B SIGNAL TYPE must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None. When IRIG-B is enabled and active, clock synchronization by
communication protocols. (DNP, IEC 60870-5-103, IEC 60870-5-104) is blocked, and clock synchronization from the front
panel and over Modbus is always enabled.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-119


PRODUCT SETUP CHAPTER 5: SETTINGS

Clocks can be synchronized locally among several relays using the computer time. When using a time source, such as IRIG-
B, the time is overwritten eventually by the time source. To synchronize clocks among UR devices:
1. In the EnerVista software, expand the main menu in the Online Window area and select the Synchronize Devices
entry. The window opens. The software prompts to acknowledge any offline devices.
2. Click the Synchronize Devices button at the top of the window, and confirm the action at the prompt. The devices
assume the time of the computer being used.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use the
following sections.

5.3.7.2 Precision time protocol (1588)


SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  PRECISION TIME PROTOCOL (1588)
 PRECISION TIME STRICT POWER PROFILE: Range: Enabled, Disabled
 PROTOCOL (1588)  Disabled

PTP DOMAIN NUMBER: Range: 0 to 255


 0

PTP VLAN PRIORITY: Range: 0 to 7


 4

PTP VLAN ID: Range: 0 to 4095


 0

 PTP PORT 1 See below


 

5   PTP PORT 3

SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  PRECISION TIME PROTOCOL (1588)  PTP PORT 1(3)
 PTP PORT 1 PORT 1 PTP FUNCTION: Range: Enabled, Disabled
  Disabled

PORT 1 PATH DELAY ADDER: Range: 0 to 60000 ns in steps of 1


 0 ns

PORT 1 PATH DELAY ASYMMETRY: Range: –1000 to +1000 ns in steps of 1


 0 ns

The F60 is provided with optional Precision Time Protocol capability. This feature is specified as the IEEE 1588
software option at the time of ordering.

The F60 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in
IEEE Std C37.238 2017. This enables the relay to synchronize to the international time standard over an Ethernet network
that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include:
• Missing declaration of PP compliance in the messages
• Connection to a network device that does not support the PTP peer delay mechanism
• Jitter substantially greater than 1 µs in received event messages
• Certain non-compliant announce and sync message update rates
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes referred to as
version 2 PTP. It does not support the previous version of the standard (version 1).

5-120 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

PTP is a protocol that allows multiple clocks in a network to synchronize with one another. It permits synchronization
accuracies better than 1 ns, but this requires that each and every component in the network achieve very high levels of
accuracy and a very high baud rate, faster than normally used for relay communications. When operating over a generic
Ethernet network, time error can amount to 1 ms or more. PP is a profile of PTP which specifies a limited subset of PTP
suitable for use in power system protection, control, automation, and data communication applications, and thereby
facilitates interoperability between different vendor’s clocks and switches. PP specifies a worst-case delivered time error of
less than 1 µs over a 16-hop network.
In a PTP system and in a PP system, the clocks automatically organize themselves into a master-slave synchronization
hierarchy with the “best” clock available making itself the “grandmaster” at the top of the hierarchy; all others make
themselves “slaves” and track the grandmaster. Typically the grandmaster clock receives its time from GPS satellites or
some other link to the international time standard. If the grandmaster fails, the next “best” clock available in the domain
assumes the grandmaster role. When a clock on start-up discovers that it is “better” than the present grandmaster, it
assumes the grandmaster role and the previous grandmaster reverts to slave. The F60 qualification mechanism accepts a
potential master clock as a new grandmaster, when in a four-second interval it has received three announce messages
from it, all better than the present grandmaster clock and better than any other announce in this interval.
Time messages issued by the grandmaster are delayed as they pass through the network both due to the finite speed of
the signal in the interconnecting fiber or wire, and due to processing delays in the Ethernet switches. Each clock and switch
implementing PP measures the propagation delay to each of its PP neighbors, and compensates for these delays in the
time received. Each network device implementing PP measures the processing delay it introduces in each time message
and compensates for this delay in the time it transmits. As a result, the time delivered to end-devices such as the UR are
virtually identical to the grandmaster time. If one of the network devices in the hierarchy does not fully implement PP, the
associated propagation delay and/or latency may not be compensated for, and the time received at the end-device can be
in error by more than 100 µs.
See the preceding Real Time Clock section for a description of when time values received via PTP are used to update the
relay’s real time clock.
The following settings are available for configuring the relay for PTP. The PTP menu displays only when the option was
5
purchased.
STRICT POWER PROFILE — Power profile (IEEE Std C37.238 2017) requires that the relay only select a power profile compliant
clock as a grandmaster, that the delivered time have worst-case error of ±1 µs, and that the peer delay mechanism be
implemented. With the strict power profile setting enabled, the relay only selects as master the clocks displaying the
IEEE_C37_238 identification codes. It uses a port only when the peer delay mechanism is operational. With the strict power
profile setting disabled, the relay uses clocks without the power profile identification when no power profile clocks are
present, and uses ports even if the peer delay mechanism is non-operational. This setting applies to all of the relay’s PTP
capable ports.
PTP DOMAIN NUMBER — Set this setting to the domain number of the grandmaster-capable clock(s) to be synchronized to. A
network can support multiple time distribution domains, each distinguished with a unique domain number. More
commonly, there is a single domain using the default domain number zero.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN PRIORITY — This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued
by the relay’s peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that it be
set to 7 in accordance with PTP. Depending on the characteristics of the device to which the relay is linked directly, VLAN
Priority can have no effect.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN ID — This setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. It is provided in compliance with PP. As these messages have a destination address that indicates
they are not to be bridged, their VLAN ID serves no function, and so can be left at its default value. Depending on the
characteristics of the device to which the relay is linked directly, VLAN ID can have no effect. This setting applies to all of
the relay’s PTP capable ports.
PORT 1 ... 3 FUNCTION — While this port setting is selected to disabled, PTP is disabled on this port. The relay does not
generate or listen to PTP messages on this port.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-121


PRODUCT SETUP CHAPTER 5: SETTINGS

PORT 1 ... 3 PATH DELAY ADDER — The time delivered by PTP is advanced by the time value in this setting prior to the time
being used to synchronize the relay’s real time clock. This is to compensate to the extent practical for time delivery delays
not compensated for in the network. In a fully compliant PP network, the peer delay and the processing delay mechanisms
compensate for all the delays between the grandmaster and the relay. In such networks, make this setting zero.
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay is later than the time indicated in the message. This
setting can be used to approximately compensate for this delay. However, as the relay is not aware of network switching
that dynamically changes the amount of uncompensated delay, there is no setting that always and completely corrects
for uncompensated delay. A setting can be chosen that reduces the worst-case error to half of the range between
minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASSYMMETRY — This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two directions of a link. Except in
unusual cases, the two fibers are of essentially identical length and composition, so make this setting zero.
In unusual cases where the length of the link is different in different directions, set this setting to the number of
nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and from
the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the fibers that
the delay from the relay to the Ethernet switch it is connected to is 9000 ns and that the delay from the switch to the relay
is 11000 ns, then the mean delay is 10000 ns, and the path delay asymmetry is 11000 - 10000 = +1000 ns.

5.3.7.3 SNTP protocol


SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  SNTP PROTOCOL
 SNTP PROTOCOL SNTP FUNCTION: Range: Enabled, Disabled
  Disabled

5  SNTP SERVER1 IP
ADDR: 127.0.0.1
Range: standard IP address format

SNTP SERVER2 IP Range: standard IP address format


 ADDR: 127.0.0.1

SNTP SERVER1 UDP Range: 0 to 65535 in steps of 1


 PORT: 123

SNTP SERVER2 UDP Range: 0 to 65535 in steps of 1


 PORT: 123

The F60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the F60 can obtain clock time over
an Ethernet network. The F60 acts as an SNTP client to receive time values from redundant SNTP/NTP servers, usually a
dedicated product using a GPS receiver to provide an accurate time. One or two SNTP servers can be used; use of both
servers for redundancy is recommended but not required.
To use SNTP, enable the function and set SNTP SERVER1 IP ADDR and/or SNTP SERVER2 IP ADDR to the SNTP/NTP server IP
addresses. The F60 attempts to obtain time values from the SNTP SERVER1 SNTP/NTP server. If SERVER1 is not available/
reachable, the F60 switches to the SNTP SERVER2 to get the time value and vice versa.
Since many time values are obtained and averaged, it generally takes three to four minutes until the F60 clock is closely
synchronized with the SNTP/NTP server. It can take up to 20 minutes for the F60 to signal an SNTP self-test error if the
server is offline, depending on the number and SNTP server modes. Broadcast mode timeout is 10 minutes and unicast
timeout is 80 seconds (corresponds to three unicast request retries).
SNTP FUNCTION — Enables or disables the SNTP feature on the F60.
SNTP SERVER1 IP ADDR — The F60 uses the SERVER1 address to contact an SNTP/NTP server to obtain time values. When the
SNTP FUNCTION setting is set to enabled or on startup if the setting is enabled, the F60 SNTP client requests SERVER1 for the
time value. If the SERVER1 channel fails or is not reachable, the F60 switches to SERVER2 SNTP/NTP server.
If SERVER1 SNTP server is set to 127.0.0.1, the F60 considers the SERVER1 SNTP server to be unconfigured.

5-122 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

To use SERVER1 SNTP in broadcast mode, set the SNTP SERVER1 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The F60 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The F60 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER2 IP ADDR — The F60 uses this address to contact an SNTP/NTP server if SERVER1 channel fails or is not
reachable. If SERVER2 SNTP server is set to 127.0.0.1, the F60 considers the SERVER2 SNTP server to be unconfigured.
To use SERVER2 SNTP in broadcast mode, set the SNTP SERVER2 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The F60 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The F60 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER1 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER1 SNTP is not required, close the port by
changing this setting to zero.
SNTP SERVER2 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER2 SNTP is not required, close the port by
changing this setting to zero.

Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
If SERVER1 IP ADDR and UDP PORT settings match the SERVER2 IP ADDR and UDP PORT settings, the F60 considers only
the SERVER1 SNTP server as being configured and an SNTP Failure error message generates. The failure message
also displays when both servers are unavailable.

5.3.7.4 Local time


SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  LOCAL TIME
 LOCAL TIME
 LOCAL TIME OFFSET FROM UTC: Range: –24.0 to 24.0 hr in steps of 0.5
5
 0.0 hr

DAYLIGHT SAVINGS TIME: Range: Disabled, Enabled


 Disabled

DST START MONTH: Range: January to December (all months)


 January

DST START DAY: Range: Sunday to Saturday (all days of the week)
 Sunday

DST START DAY INSTANCE: Range: First, Second, Third, Fourth, Last
 First

DST START HOUR: Range: 0:00 to 23:00 in steps of one hour


 2:00

DST STOP MONTH: Range: January to December (all months)


 January

DST STOP DAY: Range: Sunday to Saturday (all days of the week)
 Sunday

DST STOP DAY INSTANCE: Range: First, Second, Third, Fourth, Last
 First

DST STOP HOUR: Range: 0:00 to 23:00 in steps of one hour


 2:00

The F60 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-123


PRODUCT SETUP CHAPTER 5: SETTINGS

LOCAL TIME OFFSET FROM UTC — Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME and DST — Can be used to allow the relay to follow the DST rules of the local time zone. Note that
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored. Note that the following items do not include the DST: Time of Day Timer Start Time; Time of
Day Timer Stop Time; Event Recorder Last Cleared Date; Source x Demand VAR Maximum Date; Source x Demand WATT
Maximum Date; Source x Demand VA Maximum Date; Source x Demand Ia Maximum Date; Source x Demand Ib Maximum
Date; Source x Demand Ic Maximum Date; PMU x Last Cleared Date; PMU One-Shot Time; Data Logger Newest Time; Data
Logger Oldest Time; Oscillography Last Cleared Date; Last Settings Change Date; User Programmable Fault Report Cleared
Date; Digital Counter x Frozen Time Stamp; HIZ RMS Capture x Time; and HIZ Capture x Time.

5.3.7.5 PBM PTP


SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  PBM PTP
 PBM PTP PTP FUNCTION: Range: Disabled, Master-Slave, Slave-only
  Disabled

PTP PROFILE: Range: Power Utility Profil, Power Profile


 Power Utility Profil

PTP DOMAIN NUMBER: Range: 0 to 255



5 93

PTP VLAN PRIORITY: Range: 0 to 7


 4

PTP VLAN ID: Range: 0 to 4094


 0

PTP MASTER PRIO1: Range: 0 to 255


 128

PTP MASTER PRIO2: Range: 0 to 255


 128

 Port 1a See below


 

 Port 1b
 

 Port 4a
 

 Port 4b
 

The time synchronizing source for the relay is set using SETTINGS  PRODUCT SETUP  REAL TIME CLOCK. Another time
source is set for the Process Bus Module.
The Process Bus Module supports the Precision Time Protocol (PTP) as PTP master and slave functionality.
The PTP state of each port is determined by the PTP settings and grandmaster clock availability on the local network.
Time synchronization supports IEEE 1588 PTPv2.

5-124 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

PBM PTP configuration


The F60 supports IEEE 1588 PTPv2 as PTP Slave or PTP Master on its Process Bus Module ports. It can be supplied with an
external RTC clock from the main CPU ports (station bus ports), the Process Bus Module ports, or both. It utilizes one of the
two clocks depending upon the configuration of the SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > SYNCRONIZING SOURCE
and SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > PBM PTP > PTP FUNCTION settings, as follows:
• To use an external PTP Grand Master clock from the Process Bus Module port (UR acts as PTP Slave only), configure the
following settings:
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > SYNCRONIZING SOURCE = PBM clock
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > PBM PTP > PTP FUNCTION = Slave-only
With this configuration, the relay RTC will use the clock from the Process Bus Module port.
If the SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > SYNCRONIZING SOURCE setting is “PBM clock” and the SETTINGS >
PRODUCT SETUP > REAL TIME CLOCK > PBM PTP > PTP FUNCTION setting is “Disabled”, the RTC clock free-runs.
• To use an external PTP Grand Master clock from the Process Bus Module port (UR in PTP Slave mode) or to enable the
F60 as PTP Master on its Process Bus Module ports, configure the following settings:
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > SYNCRONIZING SOURCE = PBM clock
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > PBM PTP > PTP FUNCTION = Master-Slave
With this configuration, the relay RTC uses the clock from the Process Bus Module port.
• To use an external clock through a main CPU port (PTP Slave, IRIG-B, other source) and to enable the F60 as PTP
Master on its Process Bus Module ports, configure the following settings:
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > SYNCRONIZING SOURCE = PP/IRIG-B/PTP/Other, or IRIG-B/PP/PTP/
Other, or PP/PTP/IRIG-B/Other
– SETTINGS > PRODUCT SETUP > REAL TIME CLOCK > PBM PTP > PTP FUNCTION = Master-Slave, or Slave, or Disabled
With this configuration, the relay RTC uses the clock from the main CPU port. 5

Some UR applications like oscillography, event recorder, and datalogger use the real-time clock for time-stamping.

Note that in all of these scenarios, when the Grand Master clock is not available through a CPU port and/or Process Bus
Module, all the elements (protection, control, monitoring, logic, and so on) in the F60, except the Line Current Differential
element, remain functional without requiring any external synchronizing source for the F60, as long as all the sampled
values subscribed by the relay are synchronized according to the setting definition of SMPSYNCH CHECK (SETTINGS >
PROCESS BUS MODULE > GENERAL > SMPSYNCH CHECK) and pass the other acceptance criteria.
PTP FUNCTION — Sets the source for time synchronization for the Process Bus Module.
When set to Disabled, PTP is disabled on all ports of the Process Bus Module.
When set to Master-Slave, the Process Bus Module acts as a PTP slave when a grandmaster clock is available in the
communication path. If no better clock than its own clock is available in the communication path, the module switches to
master mode and provides the grandmaster functionality by sending Announce frames and other supporting PTP Master
frames.
When set to Slave-only, the Process Bus Module acts as a PTP slave ordinary clock if a grandmaster clock is available in the
network. If no grandmaster clock is available in the communication path, the module continues to wait for the Announce
messages.
When PTP is enabled but no grand master is available on any of the Process Bus Module ports, “PB PTP Failure” events are
generated.
To view the synchronizing source, see ACTUAL VALUES  PB MODULE  TIME SYNC  SYNC SOURCE.
PTP PROFILE — Specifies the profile to be used for PTP Master communication. The Power Utility Profile option relates to IEC
61850-9-3, while the Power Profile option relates to IEEE C37.238 2017.
When the Process Bus Module PTP is in the slave state, this setting has no effect. As a slave, the Process Bus Module
accepts both the Power Profile and the Power Utility Profile.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-125


PRODUCT SETUP CHAPTER 5: SETTINGS

PTP DOMAIN NUMBER — Set this to the domain number of the grandmaster-capable clock(s) to synchronize to. A network
can support multiple time distribution domains, each distinguished with a unique domain number. The Power Utility Profile
recommends 93 as the value for the domain number.
PTP VLAN PRIORITY — This setting selects the value of the priority field in the 802.1Q VLAN tag in PTP request messages
issued by the relay.
PTP VLAN ID — This setting selects the value of the ID field in the 802.1Q VLAN tag in PTP request messages issued by the
relay. As these messages have a destination address that indicates they are not to be bridged, their VLAN ID serves no
function, and so the setting can be left at its default value. Depending on the characteristics of the device to which the
relay is directly linked, VLAN ID can have no effect.
PTP MASTER PRIO1 — Priority1 is used in the execution of the best master clock algorithm and lower values take precedence.
The operation of the best master clock algorithm selects clocks from a set with a lower value of priority1 over clocks from
a set greater than priority1.
The setting values Priority1 and Priority2 decide when the UR Process Bus Module ports are selected as grandmaster clock.
In a single LAN, GE recommends the following:
• Set the Priority1 of the UR larger than the actual grandmaster, so that the grandmaster(s) takes precedence over UR
• Set the same Priority1 for all the UR Process Bus Module ports participating in one communication path
• Use Priority2 to further prioritize the UR Process Bus Module ports in the network. The UR with lower value of Priority2
is selected as best master when Priority1, clockClass, clockAccuracy, and scaledOffsetLogVariance are the same.
The setting is editable in the software when the PTP FUNCTION setting is Master-Slave.
PTP MASTER PRIO2 — Priority2 is used in the execution of the best master clock algorithm and lower values take precedence.
If the operation of the best master clock algorithm fails to order the clocks based on the values of priority1, clockClass,
clockAccuracy, and scaledOffsetLogVariance, the priority2 attribute allows the creation of up to 256 priorities to further

5 fine-tune the selection of best clocks.


If Priority2 is configured the same for two URs in the same communication path, best master clock algorithm uses
clockIdentity to resolve the tie-breaker.
The setting is editable in the software when the PTP FUNCTION setting is Master-Slave.

Independent of the NETWORK CONFIG and PTP FUNCTION settings, the enabled transceiver ports on the Process Bus
Module operate in stateless transparent clock mode. GE recommends always setting the NETWORK CONFIG setting
to match with the network topology to avoid unnecessary data storms. For example, if the PRP network has
multiple URs connected on PRP LAN and if the UR’s NETWORK CONFIG setting is misconfigured to “Independent” PTP
messages other than PDelay messages are forwarded between the connected ports, which can create a PTP data
storm.

Ports
SETTINGS  PRODUCT SETUP  REAL-TIME CLOCK  PBM PTP  Port 1a(4b)
 Port 1a PATH DELAY ADDER: Range: 0 to 60000 ns in steps of 1
  0 ns

PATH DELAY ASYMMETRY: Range: -1000 to +1000 ns in steps of 1


 0 ns

These setting are editable in the software when the PTP FUNCTION setting is not Disabled.
Up to eight ports display here, depending on the Process Bus Module.
Default port assignments for the Process Bus Module are as follows:
• Parallel Redundancy Protocol (PRP) — Ports 1a and 1b are enabled
• High-Availability Seamless Redundancy (HSR) — Ports 1a and 1b are enabled
• Dual HSR — Ports 1a and 1b support HSR-1, and ports 3a and 3b support HSR-2
• INDEPENDENT — Ports 1a to 4b are enabled
Port availability by order code is as follows:

5-126 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

• 85 — Ports 1a and 1b, or 3a and 3b


• 86 — All eight ports
• 87 — All eight ports
For the following two settings, there is no dependency with the NETWORK CONFIG setting. For order code 85, ports 1a, 1b,
3a, and 3b settings are available. For order codes 86 and 87, all the port settings are available. Configure these settings as
per your network. For example, for order code 85, while ports 1a, 1b, 3a, and 3b settings display, configure ports 1a and 1b
when your network uses these two ports.
PATH DELAY ADDER — The time delivered by PTP is advanced by the time in this setting prior to the time being used to
synchronize the relay's real-time clock. This is to compensate for time delivery delays not compensated for in the network.
In a fully compliant power utility network, the peer delay and the processing delay mechanisms compensate for all the
delays between the grandmaster and the relay. In such networks, use 0 ns for this setting.
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated for, so the time of message arrival at the relay is later than the time indicated in the message. This
setting can be used to approximately compensate for this delay. However, as the relay is not aware of network switching
that changes dynamically the amount of uncompensated delay, there is no setting that always corrects completely for
uncompensated delay. A setting can be chosen that reduces worst-case error to half of the range between minimum and
maximum uncompensated delay, if these values are known.
Restart the relay after changing this setting, for example using Maintenance > Reboot Relay.
PATH DELAY ASYMMETRY — This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two directions of a link. Except in
unusual cases, the two fiber cables are of essentially identical length and composition, so use 0 ns for this setting.
In unusual cases where the length of the link is different in different directions, make this setting the number of
nanoseconds that the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and
from the relay. For example, if it is known from the physical length of the fiber cable and the propagation speed in the fiber 5
that the delay from the relay to the Ethernet switch it is connected to is 9 000 ns and that the delay from the switch to the
relay is 11 000 ns, then the mean delay is 10 000 ns, and the path delay asymmetry is +1 000 ns.

5.3.8 Fault reports


SETTINGS  PRODUCT SETUP  FAULT REPORTS  FAULT REPORT 1(3)
 FAULT REPORT 1 FAULT REPORT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
  SOURCE: SRC 1

FAULT REPORT 1 TRIG: Range: FlexLogic operand


 Off

FAULT REPORT 1 Z1 Range: 0.01 to 250.00 ohms in steps of 0.01


 MAG: 3.00 Ω

FAULT REPORT 1 Z1 Range: 25 to 90° in steps of 1


 ANGLE: 75°

FAULT REPORT 1 Z0 Range: 0.01 to 650.00 ohms in steps of 0.01


 MAG: 9.00 Ω

FAULT REPORT 1 Z0 Range: 25 to 90° in steps of 1


 ANGLE: 75°

FAULT REPORT 1 Z0M Range: 0.00 to 650.00 ohms in steps of 0.01


 MAG: 0.00 Ω

FAULT REPORT 1 Z0M Range: 25 to 90° in steps of 1


 ANGLE: 75°

FAULT REPORT 1 LINE Range: km, miles


 LENGTH UNITS: km

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-127


PRODUCT SETUP CHAPTER 5: SETTINGS

FAULT REP 1 LENGTH Range: 0.0 to 2000.0 in steps of 0.1


 (km ): 100.0

FAULT REPORT 1 VT Range: None, I0, V0


 SUBSTITUTION: None

FAULT REP 1 SYSTEM Range: 0.01 to 650.00 ohms in steps of 0.01


 Z0 MAG: 2.00 Ω

FAULT REP 1 SYSTEM Range: 25 to 90° in steps of 1


 Z0 ANGLE: 75°

FAULT REPORT 1 Z0M Range: 0.00 to 650.00 ohms in steps of 0.01


 MAG: 0.00 Ω

The F60 relay supports one fault report and an associated fault locator per CT bank to a maximum of three. The signal
source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
• Fault report number
• Name of the relay, programmed by the user
• Firmware revision of the relay
• Date and time of trigger
• Name of trigger (specific operand)
• Line or feeder ID via the name of a configured signal source
• Active setting group at the time of trigger
5 • Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report
source or the trigger operate). Once a disturbance is detected, pre-fault phasors hold for three seconds waiting for the
fault report trigger. If trigger does not occur within this time, the values are cleared to prepare for the next disturbance.
• Fault current and voltage phasors (one cycle after the trigger)
• Elements operated at the time of triggering
• Events — Nine before trigger and seven after trigger (only available via the relay web page)
• Fault duration times for each breaker (created by the breaker arcing current feature)
The captured data also includes the fault type, the distance to the fault location, distance to the fault location, fault loop
impedance, as well as the reclose shot number (when applicable). To include fault duration times in the fault report, enable
and configure the breaker arcing current feature for each of the breakers. Fault duration is reported on a per-phase basis.
The relay allows locating faults, including ground faults, from delta-connected VTs. In this case, the missing zero-sequence
voltage is substituted either by the externally provided neutral voltage (broken delta VT) connected to the auxiliary voltage
channel of a VT bank, or by the zero-sequence voltage approximated as a voltage drop developed by the zero-sequence
current, and user-provided zero-sequence equivalent impedance of the system behind the relay.
The trigger can be any FlexLogic operand, but in most applications it is expected to be the same operand, usually a virtual
output, that is used to drive an output relay to trip a breaker. To prevent the overwriting of fault events, do not use the
disturbance detector to trigger a fault report. A FAULT RPT TRIG event is automatically created when the report is triggered.
If a number of protection elements are ORed to create a fault report trigger, the first operation of any element causing the
OR gate output to become high triggers a fault report. However, If other elements operate during the fault and the first
operated element has not been reset (the OR gate output is still high), the fault report is not triggered again. Considering
the reset time of protection elements, there is very little chance that a fault report can be triggered twice in this manner. As
the fault report must capture a usable amount of pre and post-fault data, it cannot be triggered faster than every 20 ms.
Each fault report is stored as a file; the relay capacity is 15 files. A 16th trigger overwrites the oldest file.
Individual fault report features store their files in the same memory space. The sixteenth report overwrites the first one
regardless of which fault report feature produced the sixteenth and the first records.
The EnerVista software is required to view all captured data. The relay faceplate display can be used to view the date and
time of trigger, the fault type, the distance location of the fault, and the reclose shot number.

5-128 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The FAULT REPORT 1 SOURCE setting selects the source for input currents and voltages and disturbance detection. For the
application of entirely parallel lines, the fault report can be programmed to apply compensation for the zero sequence
mutual coupling between parallel lines when calculating fault resistance and fault loop impedance. If this compensation is
required, the ground current (3I_0) from the parallel line must be connected to the ground input CT of the CT bank
configured under the FAULT REPORT 1 SOURCE with the same polarity as the phase current input configured in the same
source.
The FAULT 1 REPORT TRIG setting assigns the FlexLogic operand representing the protection element/elements requiring
operational fault location calculations. The distance to fault calculations are initiated by this signal. The FAULT REPORT 1 Z1
MAG, FAULT REPORT 1 Z0 MAG, and FAULT REPORT 1 Z0M MAG impedances are entered in secondary ohms.
For the application of entirely parallel lines, Z0M MAG/ANG is the mutual zero-sequence impedance for the whole line,
required to compensate the calculation of fault resistance and fault loop impedance.
The FAULT REPORT 1 VT SUBSTITUTION setting is set to “None” if the relay is fed from wye-connected VTs. If delta-connected
VTs are used, and the relay is supplied with the neutral (3V0) voltage, this setting is set to “V0”. The method is still exact, as
the fault locator combines the line-to-line voltage measurements with the neutral voltage measurement to re-create the
line-to-ground voltages. See the ACTUAL VALUES  RECORDS  FAULT REPORTS menu for details. It is required to configure
the delta and neutral voltages under the source indicated as input for the fault report. Also, the relay checks if the auxiliary
signal configured is marked as “Vn” by the user (under VT setup) and inhibits the fault location if the auxiliary signal is
labeled differently.
If the broken-delta neutral voltage is not available to the relay, an approximation is possible by assuming the missing zero-
sequence voltage to be an inverted voltage drop produced by the zero-sequence current and the user-specified
equivalent zero-sequence system impedance behind the relay: V0 = –Z0 × I0. In order to enable this mode of operation, the
FAULT REPORT 1 VT SUBSTITUTION setting is set to “I0”.
The FAULT REP 1 SYSTEM Z0 MAG and FAULT REP 1 SYSTEM Z0 ANGLE settings are used only when the VT SUBSTITUTION setting
value is “I0”. The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent behind
the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder 5
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault.
If the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-
ground faults is trusted accordingly. Keep in mind that grounding points in the vicinity of the installation impact the system
zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, and so on).

5.3.9 Oscillography

5.3.9.1 Menu
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY
 OSCILLOGRAPHY NUMBER OF RECORDS: Range: 3 to 64 in steps of 1
  5

TRIGGER MODE: Range: Automatic Overwrite, Protected


 Automatic Overwrite

TRIGGER POSITION: Range: 0 to 100% in steps of 1


 50%

TRIGGER SOURCE: Range: FlexLogic operand


 Off

AC INPUT WAVEFORMS: Range: Off, 8, 16, 32, 64 samples/cycle


 64 samples/cycle

 DIGITAL CHANNELS See below


 

 ANALOG CHANNELS See below


 

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-129


PRODUCT SETUP CHAPTER 5: SETTINGS

Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records can be captured
simultaneously.
To retrieve an Oscillography record from a relay:
1. If not yet set up for oscillography, configure settings under Settings > Product Setup > Oscillography in the EnerVista
software.
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display.
5. In the waveform window that opens, you can save the file, for example with the CFG extension.
When EnerVista UR Setup creates a new settings file, a Smart defaults feature automatically enters a basic oscillography
configuration. The basic configuration changes the factory default values to make the number of samples per cycle 32,
adds a selection of digital and analog channels that are often of interest, and adds a FlexLogic equation to trigger
oscillography. Review and update this basic configuration as required for the application at hand.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors, such as sample rate and the number of operational modules. There is a fixed amount of data storage for
oscillography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES 
RECORDS  OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sample
configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
Table 5-13: Oscillography cycles/record example
5 Records CT/VTs Sample rate Digital
channels
Analog
channels
Cycles per
record
3 1 32 32 16 2399
3 1 64 32 16 1450
16 1 32 32 16 666
16 1 64 32 16 402
32 1 32 32 16 352
32 1 64 32 16 213
3 2 32 32 16 1516
3 2 64 32 16 851
16 2 32 32 16 421

TRIGGER MODE — A new record automatically overwrites an older record when TRIGGER MODE is set to “Automatic
Overwrite.”
TRIGGER POSITION — Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
position of 25% consists of 25% pre- and 75% post-trigger data.
TRIGGER SOURCE — Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS — Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.

When changes are made to the oscillography settings, all existing oscillography records are cleared.

5-130 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

5.3.9.2 Digital channels


SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  DIGITAL CHANNELS
 DIGITAL CHANNELS DIGITAL CHANNEL 1 Range: FlexLogic operand
  Off

DIGITAL CHANNEL 127 Range: FlexLogic operand
 Off

DIGITAL 1(127) CHANNEL — This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
There are 127 channels and one trigger, for a total of 128.
To populate quickly the rows in the Offline Window, use Ctrl C/V to copy/paste, or click then double-click a row to display a
quick selection window.
Figure 5-50: Quick selection window

5.3.9.3 Analog channels 5


SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  ANALOG CHANNELS
 ANALOG CHANNELS ANALOG CHANNEL 1: Range: Off, any FlexAnalog/actual value parameter
  Off See Appendix A for list

ANALOG CHANNEL 32: Range: Off, any FlexAnalog/actual value parameter
 Off See Appendix A for list

These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay depend on
• the type of relay,
• the type and number of CT/VT hardware modules installed, and
• the type and number of analog input hardware modules installed
A list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog Parameters.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB
designates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces appear in the file; only the digital traces appear.
The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond directly
to the to the 2nd to 25th harmonics in the relay as follows:
Analog channel 0 ↔ 2nd harmonic
Analog channel 1 ↔ 3rd harmonic
...
Analog channel 23 ↔ 25th harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-131


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.10 Data logger


SETTINGS  PRODUCT SETUP  DATA LOGGER
 DATA LOGGER DATA LOGGER MODE: Range: Continuous, Trigger
  Continuous

DATA LOGGER TRIGGER: Range: FlexLogic operand


 Off

DATA LOGGER RATE: Range: 15 to 3600000 ms in steps of 1


 60000 msec

DATA LOGGER CHNL 1: Range: Off, any FlexAnalog/actual value parameter


 Off See Appendix A for list

DATA LOGGER CHNL 16: Range: Off, any FlexAnalog/actual value parameter
 Off See Appendix A for list

DATA LOGGER CONFIG: Range: Not applicable - shows computed data only
 0 CHNL x 0.0 DAYS

The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data can
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, so the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. The
following table outlines examples of storage capacities for a system frequency of 60 Hz.
5 Table 5-14: Data logger storage capacity example
Sampling rate Channels Days Storage capacity
15 ms 1 0.1 482 s
8 0.1 60 s
9 0.1 54 s
16 0.1 30 s
1000 ms 1 0.3 32729 s
8 0.1 4091 s
9 0.1 3637 s
16 0.1 2046 s
60000 ms 1 22.7 1963710 s
8 2.8 245460 s
9 2.5 218190 s
16 1.4 127230 s
3600000 ms 1 1362.1 117822600 s
8 170.2 14727600 s
9 151.3 13091400 s

Changing any setting affecting data logger operation clears data in the log.

DATA LOGGER MODE — This setting configures the mode in which the data logger operates. When set to “Continuous,” the
data logger actively records any configured channels at the rate as defined by the DATA LOGGER RATE. The data logger is
idle in this mode when no channels are configured. When set to “Trigger,” the data logger records any configured channels
at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic operand. The data logger ignores all

5-132 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

subsequent triggers and continues to record data until the active record is full. Once the data logger is full, a CLEAR DATA
LOGGER command is required to clear the data logger record before a new record can be started. Performing the CLEAR
DATA LOGGER command also stops the current record and resets the data logger to be ready for the next trigger.
DATA LOGGER TRIGGER — This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic
operand can be used as the trigger source. This setting only applies when the mode is set to “Trigger.”
DATA LOGGER RATE — This setting selects the time interval at which the actual value data is recorded.
DATA LOGGER CHNL 1(16) — This setting selects the metering actual value that is to be recorded in Channel 1(16) of the data
log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/VT hardware
modules installed, and the type and number of Analog Input hardware modules installed. Upon startup, the relay
automatically prepares the parameter list. A list of all possible analog metering actual value parameters is shown in
Appendix A: FlexAnalog Parameters.
DATA LOGGER CONFIG — This display presents the total amount of time that the Data Logger can record the channels not
selected to “Off” without overwriting old data.

5.3.11 Demand
SETTINGS  PRODUCT SETUTP  DEMAND
 DEMAND CRNT DEMAND METHOD: Range: Thermal Exponential, Block Interval, Rolling
  Thermal Exponential Demand

POWER DEMAND METHOD: Range: Thermal Exponential, Block Interval, Rolling


 Thermal Exponential Demand

DEMAND INTERVAL: Range: 5, 10, 15, 20, 30, 60 minutes


 15 MIN

DEMAND TRIGGER: Range: FlexLogic operand


5
 Off Note: for calculation using method 2a

The relay measures current demand on each phase, and three-phase demand for real, reactive, and apparent power.
Current and Power methods can be chosen separately for the convenience of the user. Settings are provided to allow the
user to emulate common electrical utility demand measuring techniques, for statistical or control purposes. If the CRNT
DEMAND METHOD is set to "Block Interval" and the DEMAND TRIGGER is set to “Off,” Method 2 is used as follows. If DEMAND
TRIGGER is assigned to any other FlexLogic operand, Method 2a is used as follows.
The relay can be set to calculate demand by any of the following three methods.

5.3.11.1 Calculation method 1: Thermal exponential


This method emulates the action of an analog peak-recording thermal demand meter. The relay measures the quantity
(RMS current, real power, reactive power, or apparent power) on each phase every second and assumes that the circuit
quantity remains at this value until updated by the next measurement. It calculates the 'thermal demand equivalent'
based on the following equation:
– kt
d t = D 1 – e Eq. 5-6

where
d = demand value after applying input quantity for time t (in minutes)
D = input quantity (constant)
k = 2.3 / thermal 90% response time
The figure shows the 90% thermal response time characteristic of 15 minutes. A setpoint establishes the time to reach
90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the
response time indicates 99% of the value.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-133


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-51: Thermal demand characteristic

Demand (%)

Time (minutes) 842787A1.CDR

5.3.11.2 Calculation method 2: Block interval


This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, starting daily at 00:00:00 (that is, 12:00 am). The 1440 minutes per day is divided
into the number of blocks as set by the programmed time interval. Each new value of demand becomes available at the
end of each time interval.

5.3.11.3 Calculation method 2a: Block interval (with start demand interval logic trigger)
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the interval between successive Start Demand Interval logic input pulses. Each new value of demand becomes available at
the end of each pulse. Assign a FlexLogic operand to the DEMAND TRIGGER setting to program the input for the new
demand interval pulses.

5 If no trigger is assigned in the DEMAND TRIGGER setting and the CRNT DEMAND METHOD is "Block Interval," use
calculation method 2. If a trigger is assigned, the maximum allowed time between two trigger signals is 60 minutes.
If no trigger signal appears within 60 minutes, demand calculations are performed and available, and the algorithm
resets and starts the new cycle of calculations. The minimum required time for trigger contact closure is 20 µs.

5.3.11.4 Calculation method 3: Rolling demand


This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and
indicates the demand over the time interval just preceding the time of update.

5.3.12 User-programmable LEDs

5.3.12.1 Menu - Enhanced and basic front panels


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS
 USER-PROGRAMMABLE  LED TEST See below
 LEDS  

 TRIP & ALARM LEDS See page 5-137


 

 USER-PROGRAMMABLE See page 5-137


  LED 1

 USER-PROGRAMMABLE
  LED 48

5-134 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

5.3.12.2 Menu - Graphical front panel


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS
 USER-PROGRAMMABLE  LED TEST See below
 LEDS  

 TRIP & ALARM LEDS See page 5-137


 

 EVENT CAUSE LED 1 See page 5-138


 

 EVENT CAUSE LED 9
 

The LEDs can be customized to illuminate when a selected FlexLogic operand is in the logic 1 state. The trip and alarm
LEDs can also be customized in a similar manner. To ensure correct functionality of all LEDs, an LED test feature is also
provided.

5.3.12.3 LED test


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST
 LED TEST LED TEST FUNCTION: Range: Disabled, Enabled
  Disabled

LED TEST CONTROL: Range: FlexLogic operand


 Off

When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user- 5
programmable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all
LEDs, including the LEDs of the optional user-programmable pushbuttons.
For the enhanced and basic front panels, the test consists of the following three stages:
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned.” This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on for one second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for one second, then back on. The test routine starts at the top
left panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to
more than one LED being turned off from a single logic point. This stage can be interrupted at any time.
For the graphical front panel, the test consists of the following stages:
1. All 22 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is "burned." This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on with the orange color for one second, then back off.
The test routine starts at the top left panel, moving from the top to bottom for all 14 LEDs. Then the eight pushbutton
LEDs are tested in the same manner. This test checks for hardware failures that lead to more than one LED being
turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on with the orange color. One LED at a time turns off for one second, then back on. The test
routine starts at the top left panel moving from top to bottom for all 14 LEDs. Then the eight pushbutton LEDs are
tested in the same manner. This test checks for hardware failures that lead to more than one LED being turned off
from a single logic point. This stage can be interrupted at any time.
4. Additionally, stages 2 and 3 are repeated twice for the five device status LEDs and nine event cause LEDs, one time
with green color on and the other with red color on.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-135


PRODUCT SETUP CHAPTER 5: SETTINGS

When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and
monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay
and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting
from relay response during testing. The reset pushbutton does not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is
initiated, the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL
setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is
executed.
Figure 5-52: LED test sequence

READY TO TEST

Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input

Start the software image of Restore the LED states


the LEDs from the software image

Set the
LED TEST IN PROGRESS
operand

control input is on

5 STAGE 1
(all LEDs on)
time-out
(1 minute)

dropping edge of the


control input

rising edge of the


Wait 1 second
control input

STAGE 2 rising edge of the


(one LED on at a time) control input

rising edge of the


Wait 1 second
control input

rising edge
STAGE 3
of the control
(one LED off at a time) input

842011A1.CDR

Application example 1
Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS  PRODUCT SETUP  USER-
PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 menu. (The option does not display when not purchased.)
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.10 s”
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS 
PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST menu:
LED TEST FUNCTION: “Enabled”
LED TEST CONTROL: “PUSHBUTTON 1 ON”

5-136 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.

Application example 2
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.

5.3.12.4 Trip and alarm LEDs


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  TRIP & ALARMS LEDS
 TRIP & ALARM LEDS TRIP LED INPUT: Range: FlexLogic operand
  Off

ALARM LED INPUT: Range: FlexLogic operand


 Off

The trip and alarm LEDs are in the first LED column (enhanced and graphical front panels) and on LED panel 1 (basic front
panel). Each LED can be programmed to turn on when the selected FlexLogic operand is in the logic 1 state.

5.3.12.5 User-programmable LED 1(48)


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  USER-PROGRAMMABLE LED 1(48)
 USER-PROGRAMMABLE LED 1 OPERAND: Range: FlexLogic operand
5
 LED 1  Off

LED 1 TYPE: Range: Self-Reset, Latched


 Self-Reset

For the enhanced and basic front panels, there are 48 amber LEDs across the relay LED panels. Each of these indicators
can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state.
For the basic front panel, the LEDs are located as follows:
• LED Panel 2 — User-programmable LEDs 1 through 24
• LED Panel 3 — User programmable LEDs 25 through 48
For the enhanced front panel, the LEDs are located as follows:
• LED column 2 — User-programmable LEDs 1 through 12
• LED column 3 — User-programmable LEDs 13 through 24
• LED column 4 — User-programmable LEDs 25 through 36
• LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is “Self-
Reset” (the default setting), the LED illumination tracks the state of the selected LED operand. If the LED 1 TYPE setting is
“Latched,” the LED, once lit, remains so until reset by the front panel RESET button, from a remote device via a
communications channel, or from any programmed operand, even if the LED operand state de-asserts.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-137


PRODUCT SETUP CHAPTER 5: SETTINGS

Table 5-15: Recommended settings for user-programmable LEDs


Setting Parameter Setting Parameter
LED 1 operand SETTING GROUP ACT 1 LED 13 operand Off
LED 2 operand SETTING GROUP ACT 2 LED 14 operand BREAKER 2 OPEN
LED 3 operand SETTING GROUP ACT 3 LED 15 operand BREAKER 2 CLOSED
LED 4 operand SETTING GROUP ACT 4 LED 16 operand BREAKER 2 TROUBLE
LED 5 operand SETTING GROUP ACT 5 LED 17 operand SYNC 1 SYNC OP
LED 6 operand SETTING GROUP ACT 6 LED 18 operand SYNC 2 SYNC OP
LED 7 operand Off LED 19 operand Off
LED 8 operand Off LED 20 operand Off
LED 9 operand BREAKER 1 OPEN LED 21 operand AR ENABLED
LED 10 operand BREAKER 1 CLOSED LED 22 operand AR DISABLED
LED 11 operand BREAKER 1 TROUBLE LED 23 operand AR RIP
LED 12 operand Off LED 24 operand AR LO

See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.

5.3.12.6 Event cause LED 1(9)


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  EVENT CAUSE LED 1(9)
 EVENT CAUSE LED 1 OPERAND: Range: FlexLogic operand
 LED 1  LED PICKUP
5 LED 1 COLOR: Range: Red, Green, Orange
 Green

LED 1 TYPE: Range: Self-Reset, Latched


 Self-Reset

For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
LED 1 TYPE — If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel RESET button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-16: Default input and output operand for event cause LEDs
LED Default input operand Output operand Default color
Event Cause LED 1 LED PICKUP EVENT CAUSE LED 1 Green
Event Cause LED 2 LED VOLTAGE EVENT CAUSE LED 2 Orange
Event Cause LED 3 LED CURRENT EVENT CAUSE LED 3 Orange
Event Cause LED 4 LED FREQUENCY EVENT CAUSE LED 4 Orange
Event Cause LED 5 LED OTHER EVENT CAUSE LED 5 Orange
Event Cause LED 6 LED PHASE A EVENT CAUSE LED 6 Orange
Event Cause LED 7 LED PHASE B EVENT CAUSE LED 7 Orange
Event Cause LED 8 LED PHASE C EVENT CAUSE LED 8 Orange
Event Cause LED 9 LED NEUTRAL/GROUND EVENT CAUSE LED 9 Orange

5-138 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

5.3.13 User-programmable self-tests


SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE SELF TESTS
 USER-PROGRAMMABLE DIRECT RING BREAK Range: Disabled, Enabled. Valid for units equipped
 SELF TESTS  FUNCTION: Enabled with Direct Input/Output module.

DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped
 FUNCTION: Enabled with Direct Input/Output module.

RxGOOSE OFF Range: Disabled, Enabled


 FUNCTION: Enabled

FIRST ETHERNET FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

SEC. ETHERNET FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

THIRD ETHERNET FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

SFP MODULE FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

BATTERY FAIL Range: Disabled, Enabled


 FUNCTION: Enabled

SNTP FAIL Range: Disabled, Enabled


 FUNCTION: Enabled

IRIG-B FAIL Range: Disabled, Enabled


 FUNCTION: Enabled

PTP FAIL Range: Disabled, Enabled


5
 FUNCTION: Enabled

SV STREAM TROUBLE Range: Disabled, Enabled


 FUNCTION: Enabled

PB ETH PORT 1a FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

PB ETH PORT Port 4b FAIL Range: Disabled, Enabled
 FUNCTION: Disabled

PB SFP MODUL 1a FAIL Range: Disabled, Enabled


 FUNCTION: Disabled

PB SFP MODUL 4b FAIL Range: Disabled, Enabled
 FUNCTION: Disabled

All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
This settings menu allows enabling and disabling of most minor self-test alarms.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
When using the graphical front panel and setting annunciator alarms, the function needs to be enabled here too, else the
alarm is not triggered.
PB SFP MODUL # FAIL FUNCTION — For order code H85, ports 2a, 2b, 4a, 4b are not available.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-139


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.14 Control pushbuttons


SETTINGS  PRODUCT SETUP  CONTROL PUSHBUTTONS  CONTROL PUSHBUTTON 1(7)
 CONTROL CNTRL PUSHBUTTN 1 ID Range: up to 20 alphanumeric characters
 PUSHBUTTON 1  CTRL PB 1

CONTROL PUSHBUTTON 1 Range: Disabled, Enabled


 FUNCTION: Disabled

CONTROL PUSHBUTTON 1 Range: Disabled, Enabled


 EVENTS: Disabled

This feature is supported with enhanced and basic front panels.


There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the basic and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained—if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-
programmable control pushbuttons.
The locations of the control pushbuttons are shown in the following figures.
Figure 5-53: Control pushbuttons (enhanced front panel)

Control pushbuttons
842813A1.CDR

An additional four control pushbuttons are included on the basic front panel when the F60 is ordered with the 12 user-
programmable pushbutton option.
Figure 5-54: Control pushbuttons (basic front panel)

67$786 (9(17&$86(
,16(59,&( 92/7$*(
7528%/( &855(17 5(6(7
7(6702'( )5(48(1&<
75,3 27+(5 86(5 7+5((
$/$50 3+$6($ 67$1'$5'
3,&.83 3+$6(% 86(5
3+$6(&
&21752/
1(875$/*5281' 86(5 386+%877216

86(5

86(5 )285(;75$
237,21$/
86(5
&21752/
86(5 386+%877216

($"'##1"34B

Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.

5-140 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to perform
the required function. Each operand remains asserted as long as the pushbutton is pressed and resets when the
pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognized
by various features that can use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The front panel keys (including control keys) cannot be operated simultaneously—a given key
must be released before the next one can be pressed.
The control pushbuttons become user-programmable only if the breaker control feature is not configured for manual
control via the USER 1 through 3 pushbuttons as shown. If configured for manual control, breaker control typically uses the
larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications.
Figure 5-55: Control pushbutton logic

6(77,1*
&21752/386+%87721
)81&7,21
(QDEOHG 

6(77,1*6

^
6<67(06(783
!%5($.(56
!%5($.(5
!%5($.(53%&21752/
$1' 581
:KHQDSSOLFDEOH

2II 
2)) 7,0(5
6<67(06(783 )/(;/2*,&23(5$1'
!%5($.(56 21  &21752/386+%7121
!%5($.(5 PVHF
!%5($.(53%&21752/

2II 
$&'5 5
5.3.15 User-programmable pushbuttons
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1(48)
 USER PUSHBUTTON 1 PUSHBUTTON 1 Range: Self-Reset, Latched, Disabled
  FUNCTION: Disabled

PUSHBTN 1 ID TEXT: Range: up to 20 alphanumeric characters


 USER PB 1

PUSHBTN 1 ON TEXT: Range: up to 20 alphanumeric characters


 PUSHBTN 1 ON

PUSHBTN 1 OFF TEXT: Range: up to 20 alphanumeric characters


 PUSHBTN 1 OFF

PUSHBTN 1 HOLD: Range: 0.0 to 10.0 s in steps of 0.1


 0.1 s

PUSHBTN 1 SET: Range: FlexLogic operand


 Off

PUSHBTN 1 RESET: Range: FlexLogic operand


 Off

PUSHBTN 1 AUTORST: Range: Disabled, Enabled


 Disabled

PUSHBTN 1 AUTORST Range: 0.2 to 600.0 s in steps of 0.1


 DELAY: 1.0 s

PUSHBTN 1 REMOTE: Range: FlexLogic operand


 Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-141


PRODUCT SETUP CHAPTER 5: SETTINGS

PUSHBTN 1 LOCAL: Range: FlexLogic operand


 Off

PUSHBTN 1 DROP-OUT Range: 0 to 60.00 s in steps of 0.05


 TIME: 0.00 s

PUSHBTN 1 LED CTL: Range: FlexLogic operand


 Off

PUSHBTN 1 MESSAGE: Range: Disabled, Normal, High Priority


 Disabled

PUSHBUTTON 1 Range: Disabled, Enabled


 EVENTS: Disabled

This feature is optional, specified at the time of ordering.


a

User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
• Enhanced horizontal front panel — 16 user-programmable pushbuttons
• Enhanced vertical front panel — 6 user-programmable pushbuttons
• Basic horizontal front panel — 12 user-programmable pushbuttons
• Graphical front panel — 48 user-programmable pushbuttons (eight physical pushbuttons, 40 graphical interface
pushbuttons)

5 User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under Maintenance > Change Front Panel.

The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.

Example
To clear event records using pushbutton 1, set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 1 ON. Then program the pushbutton by setting Settings > Product Setup > User-
Programmable Pushbuttons > Pushbutton 1 Function to "Self-reset." For a graphical front panel, to use a side
pushbutton to clear the event records, it also needs to be programmed in a single-line diagram.
The figures show user-configurable pushbuttons for the front panels.
Figure 5-56: User-programmable pushbuttons (enhanced front panel)
USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16

842814A1.CDR

5-142 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-57: User-programmable pushbuttons (basic front panel)

1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL

2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL

842779A1.cdr

Figure 5-58: User-programmable pushbuttons (graphical front panel)

3URJUDPDQ\EXWWRQVIRUSXVKEXWWRQVWR 3XVKEXWWRQVWR

 

 

 

 

5(6(7 (6&
(17(5
5
=e\dY\Y^>& >Udg_b[CdQRY\YdiQ^TCi^SXb_`XQc_b=UQcebU]U^dCicdU]

$&'5

Front panel pushbuttons and LEDs can be custom labeled as outlined in the Front Panel Labeling section in the previous
chapter.
Each pushbutton asserts its own “On” and “Off” FlexLogic operands (for example, PUSHBUTTON 1 ON and
PUSHBUTTON 1 OFF). These operands are available for each pushbutton and are used to program specific actions. If any
pushbutton is active, the ANY PB ON operand is asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the
corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the
PUSHBTN 1 LED CTL setting.
The activation and deactivation of user-programmable pushbuttons depends on whether latched or self-reset mode is
programmed.
• Latched mode — In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSHBTN 1 SET setting, by directly pressing the associated front panel pushbutton, or with the graphical front panel
interface. The state of each pushbutton is stored in non-volatile memory and maintained through a loss of control
power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET
setting, by directly pressing the active front panel pushbutton, or with the graphical front panel interface.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY
settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if
control is not executed within a specified time period.
• Self-reset mode — In self-reset mode, a user-programmable pushbutton can be set (activated) by asserting the
operand assigned to the PUSHBTN 1 SET setting, by pressing the front panel pushbutton, or by the graphical front panel

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-143


PRODUCT SETUP CHAPTER 5: SETTINGS

interface. A pushbutton remains active for the time it is pressed physically or pressed in the graphical front panel
interface, plus the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via
FlexLogic, the pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand assigned to the
PUSHBTN 1 SET setting remains On has no effect on the pulse duration.

The pulse duration of the remote set or local front panel pushbutton must be at least 56 ms for a 60 Hz system or
60 ms for a 50 Hz system to operate the pushbutton. This allows the user-programmable pushbuttons to properly
operate during power cycling events and various system disturbances that can cause transient assertion of the
operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL
and PUSHBTN 1 REMOTE settings. If local inhibit is applied, the pushbutton ignores set and reset commands executed
through the front panel pushbuttons. If remote inhibit is applied, the pushbutton ignores set and reset commands
executed through FlexLogic operands.
The inhibit functions are not applied to the autoreset feature. The inhibit function can be used in SBO control operations to
prevent user-programmable pushbutton activation and ensuring “one-at-a-time” select operation.
The inhibit functions can also be used to prevent pushbutton activation from the accidental pressing of the front panel
pushbuttons. The separate inhibit of the local and remote operation simplifies the implementation of local/remote control
supervision.
Pushbutton states can be logged by the event recorder. User-defined messages can also be associated with each
pushbutton and displayed on basic and enhanced front panels when the user-programmable pushbutton is activated, and
when in the latched mode when the user-programmable pushbutton is deactivated. With the graphical front panel
interface, instead of messages, the status of user-programmable pushbuttons can display on a single-line diagram and
can also display in annunciator page windows and in actual values page cells.

5 For the graphical front panel, the pushbuttons 1 to 8 are linked to the eight physical pushbuttons, and pushbuttons 9 and
above are mapped to the graphical interface pushbuttons. To set the buttons for pushbuttons 9 and above, access
Settings > Product Setup > Graphical Panel > Single Line Diagram Editor, click the PB symbol in the toolbox, then
configure pushbuttons 9 and above.
PUSHBUTTON 1 FUNCTION — This setting selects the mode of the pushbutton (Self-Reset, Latched, Disabled). If set to
“Disabled,” the pushbutton is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If
set to “Latched”, the pushbutton remains on until reset.
PUSHBTN 1 ID TEXT — This setting specifies the top 20-character line of the user-programmable pushbutton message and is
intended to provide ID information of the pushbutton. For example, the text displays in the Event Record. See the User-
definable Displays section in this chapter for instructions on how to enter alphanumeric characters from the keypad. On a
graphical front panel, this setting instead controls the label of the user-programmable pushbutton component on single-
line diagrams.
PUSHBTN 1 ON TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and is displayed when the pushbutton is in the “on” position. See the User-definable Displays section for instructions on
entering alphanumeric characters from the keypad. On a graphical front panel, this setting instead controls the on status
text of the user-programmable pushbutton component on single-line diagrams. This setting is not applied to the physical
pushbuttons on the graphical front panel.
PUSHBTN 1 OFF TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and displays when the pushbutton is deactivated and the PUSHBUTTON 1 FUNCTION is “Latched.” A message does not
display when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand status is implied to be “Off” upon its
release. The length of the “Off” message is configured with the PRODUCT SETUP  DISPLAY PROPERTIES  FLASH MESSAGE
TIME setting. On a graphical front panel, this setting instead controls the off status text of the user-programmable
pushbutton component on single-line diagrams. This setting is not applied to the physical pushbuttons on the graphical
front panel.
PUSHBTN 1 HOLD — This setting specifies the time required for a front panel pushbutton to be pressed before it is deemed
active. This timer is reset upon release of the pushbutton. Note that user-programmable pushbutton operation requires the
front panel pushbutton to be pressed a minimum of 56 ms for a 60 Hz system or 60 ms for a 50 Hz system. This minimum
time is required prior to activating the user-programmable pushbutton hold timer.

5-144 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

PUSHBTN 1 SET — This setting assigns the FlexLogic operand serving to activate the user-programmable pushbutton
element. The duration of the incoming set signal must be at least 56 ms for a 60 Hz system or 60 ms for a 50 Hz system.
PUSHBTN 1 RESET — This setting assigns the FlexLogic operand serving to deactivate the user-programmable pushbutton
element. This setting is applicable only if the user-programmable pushbutton is in “Latched” mode.
PUSHBTN 1 AUTORST — This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in “Latched” mode.
PUSHBTN 1 AUTORST DELAY — This setting specifies the time delay for automatic reset of the pushbutton when in “Latched”
mode.
PUSHBTN 1 REMOTE — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
PUSHBTN 1 LOCAL — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME — This setting applies only to “Self-Reset” mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by PUSHBTN 1 SET remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL — This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the PUSHBUTTON 1 ON operand. This setting is not applied to
Pushbuttons 9 and above on the graphical front panel, where the label background shows the orange glow color for the
“on” state.
PUSHBTN 1 MESSAGE — This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the PUSHBTN 1 ID and PUSHBTN 1 OFF TEXT settings. This settings has no effect on the
graphical front panel. 5
When set to “Disabled” user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the “Latched” mode the off message displays
when the user-programmable pushbutton becomes deactivated.
When set to “Normal”, the duration the message displays is as specified by the FLASH MESSAGE TIME setting.
When set to “High Priority”, the duration of the off message is as specified by the FLASH MESSAGE TIME setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
suppressed for 10 seconds.
PUSHBUTTON 1 EVENTS — If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
The figures show the user-programmable pushbutton logic.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-145


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-59: User-programmable pushbutton logic (Sheet 1 of 2)


6(77,1*
386+%87721)81&7,21
(QDEOHG
/DWFKHG /$7&+(' 7RXVHUSURJUDPPDEOH
6HOI5HVHW SXVKEXWWRQVORJLF
VKHHW
25 )URPIURQWSDQHO
6(77,1* 6(77,1*
386+%71/2&$/ 386+%71+2/'
2II  73.3
)URPIURQWSDQHO $1'

$1'
25 7,0(5
)URPJUDSKLFDOIURQWSDQHO
PV

6(77,1*  25
386+%716(7 PV +]
2II  7,0(5
1RQYRODWLOHODWFK
PV
6(77,1* $1' 6
$1'
386+%715(027(  /DWFK
2II  PV +] 5
7,0(5
)/(;/2*,&23(5$1' PV
386+%877212))


6(77,1*
386+%715(6(7 $1'
2II 

25 7RXVHUSURJUDPPDEOH
6(77,1* 25 386+%8772121 SXVKEXWWRQVORJLF
6(77,1* VKHHW
386+%71$872567'(/$<
386+%71$872567
73.3
(QDEOHG
$1'

5
'LVDEOHG $1'


7,0(5
)/(;/2*,&23(5$1' PV 25
386+%8772121


6(77,1*
$1' 386+%71'5232877,0(

25
7567
$1'
$FGU

5-146 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-60: User-programmable pushbutton logic (Sheet 2 of 2)

OFF MESSAGE
ENGAGE MESSAGE
SETTING
LATCHED FLASH MESSAGE TIME
SETTINGS
0 PUSHBTN ID TEXT
AND
OR TRST = XXXXXXXXXX
PUSHBTN OFF TEXT
= XXXXXXXXXX
Instantaneous
From user-programmable reset * Enhanced and standard front panels
pushbuttons logic sheet 1

FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF

FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON

ON MESSAGE
SETTING ENGAGE MESSAGE
PUSHBTN 1 MESSAGE
AND
= Disabled
= High Priority SETTINGS
= Normal PUSHBTN ID TEXT
= XXXXXXXXXX
OR
PUSHBTN ON TEXT
SETTING
= XXXXXXXXXX
FLASH MESSAGE TIME
0 Enhanced and standard front panels
AND
TRST The message is temporarily removed if

5
any keypad button is pressed. Ten
seconds of keypad inactivity restores
Instantaneous
Instantaneous reset is executed if any reset * the message.
front panel button is pressed or any new
target or message becomes active.

PUSHBUTTON 1 LED LOGIC


1. If pushbutton 1 LED control is set to off.
Pushbutton 1
FLEXLOGIC OPERAND FLEXLOGIC OPERAND LED
PUSHBUTTON 1 ON PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON 2. If pushbutton 1 LED control is not set to off.
OR ANY PB ON
SETTING Pushbutton 1
LED
PUSHBTN 1 LED CTL
PUSHBUTTON 16 ON = any FlexLogic operand
The enhanced front panel has 16 operands;
the standard front panel has 12
842239A1.CDR

5.3.16 Flex state parameters


SETTINGS  PRODUCT SETUP  FLEX STATE PARAMETERS
 FLEX STATE PARAMETER 1: Range: FlexLogic operand
 PARAMETERS  Off

PARAMETER 256: Range: FlexLogic operand
 Off

This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256
state bits.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-147


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.17 User-definable displays

5.3.17.1 Menu
SETTINGS  PRODUCT SETUP  USER-DEFINABLE DISPLAYS
 USER-DEFINABLE INVOKE AND SCROLL: Range: FlexLogic operand
 DISPLAYS  Off

 USER DISPLAY 1 See below


 

 USER DISPLAY 16
 

This feature is supported with enhanced and basic front panels.


This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient
viewing sequence in the USER DISPLAY menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus
facilitate text entry and Modbus register data pointer options for defining the user display content.
This feature is not supported with the optional graphical front panel.
Once programmed, the user-definable displays can be viewed in two ways.
• Keypad — Use the MENU key to select the USER DISPLAY menu item to access the first user-definable display (note that
only the programmed screens are displayed). The screens can be scrolled using the up and down arrow keys. The
display disappears after the default message time-out period specified by the PRODUCT SETUP  DISPLAY PROPERTIES
 DEFAULT MESSAGE TIMEOUT setting.
5 • User-programmable control input — The user-definable displays also respond to the INVOKE AND SCROLL setting. Any
FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the
programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the
first one. The INVOKE AND SCROLL input and the down arrow key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay starts to cycle through the user
displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user display, not
at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.

5.3.17.2 User display 1(16)


SETTINGS  PRODUCT SETUP  USER-DEFINABLE DISPLAYS  USER DISPLAY 1(16)
 USER DISPLAY 1 DISP 1 TOP LINE: Range: up to 20 alphanumeric characters
 
DISP 1 BOTTOM LINE: Range: up to 20 alphanumeric characters

DISP 1 ITEM 1: Range: 0 to 65535 in steps of 1
 0

DISP 1 ITEM 5: Range: 0 to 65535 in steps of 1
 0

Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display then prompts with ADD TO USER DISPLAY LIST? After selecting “Yes,” a message
indicates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus
are automatically configured with the proper content—this content can be edited subsequently.

5-148 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user
display. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the
start of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered
in a user display – the nth tilde (~) refers to the nth item.
A user display can be entered from the front panel keypad or the EnerVista interface (preferred for convenience). The
following procedure shows how to enter text characters in the top and bottom lines from the front panel keypad. Press the
HELP key at any time for context sensitive help information.
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the front panel
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected
system display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the
Modbus address, then manually convert it to decimal form before entering it (EnerVista usage conveniently facilitates this
conversion). See the Modbus Memory Map section earlier in this chapter for information on how to calculate the decimal
value to enter on the front panel.
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option
to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
An example of user display setup and result is shown as follows.
5
 USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first tilde marker
  Current X ~ A

DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker
 Current Y ~ A

DISP 1 ITEM 1: Shows decimal form of user-selected Modbus register


 6016 address, corresponding to first tilde marker

DISP 1 ITEM 2: Shows decimal form of user-selected Modbus register


 6357 address, corresponding to second tilde marker

DISP 1 ITEM 3: This item is not being used. There is no corresponding


 0 tilde marker in top or bottom lines.

DISP 1 ITEM 4: This item is not being used. There is no corresponding


 0 tilde marker in top or bottom lines.

DISP 1 ITEM 5: This item is not being used. There is no corresponding


 0 tilde marker in top or bottom lines.

USER DISPLAYS Current X 0.850 Shows the resultant display content


 Current Y 0.327 A

If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom
line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-149


PRODUCT SETUP CHAPTER 5: SETTINGS

5.3.18 Direct inputs and outputs

5.3.18.1 Menu
SETTINGS  PRODUCT SETUP  DIRECT I/O
 DIRECT I/O DIRECT OUTPUTS Range: 1 to 16 in steps of 1
  DEVICE ID: 1

DIRECT I/O CH1 RING Range: Yes, No


 CONFIGURATION: Yes

DIRECT I/O CH2 RING Range: Yes, No


 CONFIGURATION: Yes

DIRECT I/O DATA Range: 64 kbps, 128 kbps


 RATE: 64 kbps

DIRECT I/O CHANNEL Range: Disabled, Enabled


 CROSSOVER: Disabled

 CRC ALARM CH1 See page 5-155


 

 CRC ALARM CH2


 

 UNRETURNED See page 5-156


  MESSAGES ALARM CH1

 UNRETURNED

5  MESSAGES ALARM CH2

This option is available when an Inter-Relay Communications card is specified at the time of ordering. With the
option, direct inputs/outputs display by default. When you enable the teleprotection feature, direct I/O is not
visible.
Direct inputs and outputs exchange status information (inputs and outputs) between UR-series relays connected directly
via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GOOSE, except that communications
takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that support two channels,
direct output messages are sent from both channels simultaneously. This effectively sends direct output messages both
ways around a ring configuration. On type 7 cards that support one channel, direct output messages are sent only in one
direction. Messages are resent (forwarded) when it is determined that the message did not originate at the receiver.
Direct Inputs and Outputs are initiated automatically and start running once at least one Direct Output in the given UR is
set to anything but Off.
For the direct I/Os to function properly, all UR devices sending I/Os using an Inter-Relay Communications card must have
identical firmware revisions.

Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are disabled, and
vice versa.
Direct output message timing is similar to GOOSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic operands:
• DIRECT RING BREAK (direct input/output ring break) — Indicates that direct output messages sent from a UR-series
relay are not being received back by the relay
• DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline) — Indicate that direct output messages
from at least one direct device are not being received

5-150 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID setting, which identifies the relay in all direct output
messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of
the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages are received back. If not, the direct input/output ring break
self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel
communications cards apply the same data rate to both channels. Delivery time for direct input and output messages is
approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each "bridge."
Table 5-17: Direct input and output data rates
Module Supported data rates
2A, 2B 64 kbps
2E, 2F (legacy modules) 64 kbps
2G, 2H 128 kbps
2I, 2J 64 kbps, 128 kbps
72, 73 64 kbps, 128 kbps
74, 75 64 kbps
76, 77 64 kbps
7A, 7B, 7C, 7D 64 kbps, 128 kbps
7E, 7F, 7G 64 kbps
7H, 7I, 7J, 7K 64 kbps, 128 kbps 5
7L, 7M, 7N, 7P, 7Q 64 kbps
7R, 7S 64 kbps
7T, 7W 64 kbps

The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.

The DIRECT I/O CHANNEL CROSSOVER setting applies to a F60 with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputs
and Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.

Example 1: Extending the input/output capabilities of a UR-series relay


Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable
logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED,
such as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are
connected via single-channel digital communication cards as shown in the figure.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-151


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-61: Input and output extension via direct inputs and outputs

TX1
UR IED 1
RX1

TX1
UR IED 2
RX1

842711A1.CDR

In this application, apply the following settings. For UR-series IED 1:


DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O DATA RATE: “128 kbps”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “2”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O DATA RATE: “128 kbps”
The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and
from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection
(for example: fiber, G.703, or RS422).

Example 2: Interlocking busbar protection


5 A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream
devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown.
Figure 5-62: Sample interlocking busbar protection scheme

85,(' %/2&.

85,(' 85,(' 85,('

($"'!"1!34B

For increased reliability, a dual-ring configuration (shown as follows) is recommended for this application.
Figure 5-63: Interlocking bus protection scheme via direct inputs/outputs

7; 5;
85,('
5; 7;

5; 7; 5; 7;


85,(' 85,('
7; 5; 7; 5;

7; 5;
85,('
5; 7;
($"'!&1!34B

5-152 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

In this application, apply the following settings. For UR-series IED 1:


DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “2”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “3”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 4:
DIRECT OUTPUT DEVICE ID: “4”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
Message delivery time is approximately 0.2 of power system cycle (at 128 kbps) times number of ‘bridges’ between the
origin and destination. Dual-ring configuration effectively reduces the maximum ‘communications distance’ by a factor of
two.
In this configuration the following delivery times are expected (at 128 kbps) if both rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.2 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle 5
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
If one ring is broken (say TX2-RX2) the delivery times are as follows:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.6 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
A coordinating timer for this bus protection scheme could be selected to cover the worst case scenario (0.4 of a power
system cycle). Upon detecting a broken ring, the coordination time is adaptively increased to 0.6 of a power system cycle.
The complete application requires addressing a number of issues, such as failure of both the communications rings, failure
or out-of-service conditions of one of the relays, and so on. Self-monitoring flags of the direct inputs and outputs feature
primarily are used to address these concerns.

Example 3: Pilot-aided schemes


Consider the three-terminal line protection application shown.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-153


PRODUCT SETUP CHAPTER 5: SETTINGS

Figure 5-64: Three-terminal line application

85,(' 85,('

85,(' ($"'!#1!34B

A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2
constitute a first ring, while IEDs 2 and 3 constitute a second ring).
Figure 5-65: Single-channel open loop configuration

7; 5; 5;


85,(' 85,('
5; 7; 7;

5 85,('
5;

7;
($"'!$1!34B

In this application, apply the following settings. For UR-series IED 1:


DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “2”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “3”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
In this configuration the following delivery times are expected (at 128 kbps):
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.5 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
In this scheme, IEDs 1 and 3 do not communicate directly. IED 2 must be configured to forward the messages as explained
in the Inputs and Outputs section. Implement a blocking pilot-aided scheme with more security and, ideally, faster
message delivery time. This is accomplished using a dual-ring configuration as shown here.

5-154 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

Figure 5-66: Dual-channel closed loop (dual-ring) configuration

7; 7; 5; 5;


85,(' 85,('
5; 5; 7; 7;

7; 5;
85,('
5; 7;
($"'!%1!34B

In this application, apply the following settings. For UR-series IED 1:


DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “2”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “3”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes” 5
In this configuration the following delivery times are expected (at 128 kbps) if both the rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.2 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
The two communications configurations can be applied to both permissive and blocking schemes. Take speed, reliability,
and cost into account when selecting the required architecture.

5.3.18.2 CRC alarm CH1(2)


SETTINGS  PRODUCT SETUP  DIRECT I/O  CRC ALARM CH1(2)
 CRC ALARM CH1 CRC ALARM CH1 Range: Enabled, Disabled
  FUNCTION: Disabled

CRC ALARM CH1 Range: 100 to 10000 in steps of 1


 MESSAGE COUNT: 600

CRC ALARM CH1 Range: 1 to 1000 in steps of 1


 THRESHOLD: 10

CRC ALARM CH1 Range: Enabled, Disabled


 EVENTS: Disabled

The F60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter
adds up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the
CRC ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC
ALARM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT
setting, both the counters reset and the monitoring process is restarted.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-155


PRODUCT SETUP CHAPTER 5: SETTINGS

Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions—if required—are programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES  STATUS  DIRECT INPUTS  CRC FAIL COUNT CH1 actual value.
• Message count and length of the monitoring window — To monitor communications integrity, the relay sends 1
message per second (at 64 kbps) or 2 messages per second (at 128 kbps) even if there is no change in the direct
outputs. For example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000,” corresponds a time window of about 160
minutes at 64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity,
the monitoring time interval shortens. Take this into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT is set to 10 × 60 × 1 = 600.
• Correlation of failed CRC and bit error rate (BER) — The CRC check can fail if one or more bits in a packet are
corrupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain
assumptions an approximation can be made as follows. A direct input and output packet containing 20 bytes results
in 160 bits of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4
implies 1 bit error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet,
having 1 failed packet for every 63 received is about equal to a BER of 10–4.

5.3.18.3 Unreturned messages alarm CH1(2)


SETTINGS  PRODUCT SETUP  DIRECT I/O  UNRETURNED MESSAGES ALARM CH1(2)
 UNRETURNED UNRET MSGS ALARM CH1 Range: Enabled, Disabled
 MESSAGES ALARM CH1  FUNCTION: Disabled

UNRET MSGS ALARM CH1 Range: 100 to 10000 in steps of 1



5 MESSAGE COUNT: 600

UNRET MSGS ALARM CH1 Range: 1 to 1000 in steps of 1


 THRESHOLD: 10

UNRET MSGS ALARM CH1 Range: Enabled, Disabled


 EVENTS: Disabled

The F60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of
unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have
failed to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS
ALARM CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1
UNRET ALM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions, if required, are programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES  STATUS  DIRECT INPUTS
 UNRETURNED MSG COUNT CH1 actual value.

5.3.19 Teleprotection
SETTINGS  PRODUCT SETUP  TELEPROTECTION
 TELEPROTECTION TELEPROTECTION Range: Disabled, Enabled
  FUNCTION: Disabled

NUMBER OF TERMINALS: Range: 2, 3


 2

5-156 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PRODUCT SETUP

NUMBER OF COMM Range: 1, 2


 CHANNELS: 1

LOCAL RELAY ID Range: 0 to 63 in steps of 1


 NUMBER: 0

TERMINAL 1 RELAY ID Range: 0 to 63 in steps of 1


 NUMBER: 0

TERMINAL 2 RELAY ID Range: 0 to 63 in steps of 1


 NUMBER: 0

This option is available when an Inter-Relay Communications card is specified at the time of ordering. With the
option, direct inputs/outputs display by default. When you enable the teleprotection feature, direct I/O is not
visible.
Digital teleprotection transfers protection commands between two or three relays in a secure, fast, dependable, and
deterministic way. Possible applications are permissive or blocking pilot schemes and direct transfer trip (DTT).
Teleprotection can be applied over any analog or digital channels and any communications media, such as direct fiber,
copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted
continuously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel
data is achieved by using CRC-32 on the data packet.

Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and
vice versa.
NUMBER OF TERMINALS — Specifies whether the teleprotection system operates between two peers or three peers.
5
NUMBER OF CHANNELS — Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal system),
set the NUMBER OF CHANNELS to “2.” For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or “2” (redundant
channels).
LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER — In installations that use
multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line is from the correct
relays. The teleprotection function performs this check by reading the message ID sent by transmitting relays and
comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inadvertently set to
loopback mode or data is being received from a wrong relay by checking the ID on a received channel. If an incorrect ID is
found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL FlexLogic
operand is set, driving the event with the same name and blocking the teleprotection inputs. For commissioning purposes,
the result of channel identification is also shown in the STATUS  CHANNEL TESTS  VALIDITY OF CHANNEL
CONFIGURATION actual value. The default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID is not to be
checked. On two- terminals two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over both channels; as
such, only the TERMINAL 1 ID NUMBER has to be programmed on the receiving end.

5.3.20 Installation
SETTINGS  PRODUCT SETUP  INSTALLATION
 INSTALLATION RELAY SETTINGS: Range: Not Programmed, Programmed
  Not Programmed

RELAY NAME: Range: up to 20 alphanumeric characters


 Relay-1

RELAY SETTINGS — To safeguard against the installation of a relay without any entered settings, the unit does not allow
signaling of any output relay until RELAY SETTINGS is set to "Programmed." This setting is "Not Programmed" by default. The
UNIT NOT PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
RELAY NAME — This setting allows the user to uniquely identify a relay. This name appears on generated reports.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-157


REMOTE RESOURCES CHAPTER 5: SETTINGS

5.4 Remote resources


5.4.1 Remote resources configuration
When the F60 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources
menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
Figure 5-67: Remote Resources configuration menu

5
The remote resources settings configure a F60 with a Process Bus Module to work with HardFiber Bricks. Remote resources
configuration is only available through the EnerVista software, and is not available through the F60 front panel. A Brick
provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to be the remote
interface to field equipment such as circuit breakers and transformers. The F60 with a Process Bus Module has access to
all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection between
specific fiber optic ports on the F60 process card and specific Brick. The relay is then configured to measure specific
currents, voltages and contact inputs from those Bricks, and to control specific outputs.
The configuration process for remote resources is straightforward and consists of the following steps.
• Configure the field units. This establishes the point-to-point connection between a specific port on the relay Process
Bus Module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus
relay.
• Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages. AC
bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful
reliability improvement possible with process bus.
• Configure signal sources. This functionality of the F60 has not changed other than the requirement to use currents
and voltages established by AC bank configuration under the remote resources menu.
• Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's
functionality. These inputs and outputs are the physical interface to circuit breakers, transformers, and other
equipment. They replace the traditional contact inputs and outputs located at the relay to virtually eliminate copper
wiring.
• Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are
distinct binary channels that provide high-speed protection quality signaling between relays through a Brick.
For additional information on how to configure a relay with a Process Bus Module, see the HardFiber Process Bus System
Instruction Manual.

5-158 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

5.5 System setup


5.5.1 AC inputs

5.5.1.1 Current banks


SETTINGS  SYSTEM SETUP  AC INPUTS  CURRENT BANK F1(M5)
 CURRENT BANK F1 PHASE CT F1 Range: 1 to 65000 A in steps of 1
  PRIMARY: 1 A

PHASE CT F1 Range: 1 A, 5 A
 SECONDARY: 1 A

GROUND CT F1 Range: 1 to 65000 A in steps of 1


 PRIMARY: 1 A

GROUND CT F1 Range: 1 A, 5 A
 SECONDARY: 1 A

Because energy parameters are accumulated, record these values and then reset immediately prior to changing CT
characteristics.
Two banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M} and a = {1, 5}
See the Introduction to AC Sources section at the beginning of this chapter for details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
5
ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3I0) is used as the input
for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor can also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input can be used. In this
case, the sensitive ground CT primary rating must be entered. See chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct operation,
the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given the
following current banks:
• F1: CT bank with 500:1 ratio
• F5: CT bank with 1000:1 ratio
• M1: CT bank with 800:1 ratio
The following rule applies:
SRC 1 = F1 + F5 + M1 Eq. 5-7
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 and 800:1 ratio
CTs are adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1
currents, then a pickup level of 1 pu operates on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).

5.5.1.2 Voltage banks


SETTINGS  SYSTEM SETUP  AC INPUTS  VOLTAGE BANK F5(M5)
 VOLTAGE BANK F5 PHASE VT F5 Range: Wye, Delta
  CONNECTION: Wye

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-159


SYSTEM SETUP CHAPTER 5: SETTINGS

PHASE VT F5 Range: 25.0 to 240.0 V in steps of 0.1


 SECONDARY: 66.4 V

PHASE VT F5 Range: 1.00 to 24000.00 in steps of 0.01


 RATIO: 1.00 :1

AUXILIARY VT F5 Range: Vn, Vag, Vbg, Vcg, Vab, Vbc, Vca


 CONNECTION: Vag

AUXILIARY VT F5 Range: 25.0 to 240.0 V in steps of 0.1


 SECONDARY: 66.4 V

AUXILIARY VT F5 Range: 1.00 to 24000.00 in steps of 0.01


 RATIO: 1.00 :1

Because energy parameters are accumulated, these values should be recorded and then reset immediately prior to
changing VT characteristics.
One bank of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M} and a = {5}
See the Introduction to AC Sources section at the beginning of this chapter for details.
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5
CONNECTION made to the system as “Wye” or “Delta.” An open-delta source VT connection is entered as “Delta.”

The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta
5 connection, the secondary voltage is 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage, which is 115 / 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered is 120; that is, 14400 / 120.

If the PHASE VT F5 CONNECTION is set to “Delta”, the relay does not calculate voltage harmonics.

5.5.2 Power system


SETTINGS  SYSTEM SETUP  POWER SYSTEM
 POWER SYSTEM NOMINAL FREQUENCY: Range: 25 to 60 Hz in steps of 1
  60 Hz

PHASE ROTATION: Range: ABC, ACB


 ABC

FREQUENCY AND PHASE Range: SRC 1, SRC 2, SRC 3, SRC 4


 REFERENCE: SRC 1

SIGNAL TO TRACK: Range: Auto, 3-ph VT, 1-ph VT, 3-ph CT, 1-ph CT
 Auto

ALTERNATE FREQ AND PHS Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
 REFERENCE: None

ALT SIGNAL TO TRACK: Range: 3-ph VT, 1-ph VT, 3-ph CT, 1-ph CT
 3-ph VT

FREQUENCY TRACKING: Range: Disabled, Enabled


 Enabled

5-160 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

NOMINAL FREQUENCY — The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if
the system frequency cannot be measured from available signals. This can happen if the signals are not present or are
heavily distorted. Before reverting to the nominal frequency, the frequency tracking algorithm holds the last valid
frequency measurement for a safe period of time while waiting for the signals to reappear or for the distortions to decay.
When using a Process Bus Module and SV streams, the SV streams need to be defaulted before changing this setting,
under Settings > Process Bus Module > SV Stream Config. After changing the NOMINAL FREQUENCY, restart the relay using
Maintenance > Reboot Relay Command.
PHASE ROTATION — The phase sequence of the power system is required to properly calculate sequence components and
power parameters. The PHASE ROTATION setting matches the power system phase sequence and informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be connected
to system phases A, B, and C for correct operation.
FREQUENCY AND PHASE REFERENCE — This setting determines which signal source is used for frequency tracking and phase
angle reference. Within this source, a specific signal shall be selected for tracking frequency calculation and for the phase
angle reference, and such selection will be determined by SIGNAL TO TRACK setting below.
SIGNAL TO TRACK — This setting specifies the signal in a source to be used for tracking frequency calculation and for phase
angle reference.
When Auto is selected, the AC signal to be used in a source is prioritized based on the AC inputs configuration in this
source, in which phase voltages takes precedence, followed by the auxiliary voltage, then phase currents, and finally
ground current, as it was in legacy UR f/w releases. With the Auto setting, the signal selection is static rather than dynamic,
i.e. AC signals are selected based upon the source configuration only, regardless of whether a particular signal is applied to
the relay or not. If VT or CT is selected (3-ph VT, 1-ph VT, 3-ph CT, 1-ph CT), the AC signal to be used is directly based on this
selection and will revert to nominal frequency if selected signal is below 0.06pu.
For the three-phase selection, phase A is used for angle referencing (ANGLE REF = VA or IA), while Clarke transformation of
the phase signals is used for frequency metering and tracking (VFREQUENCY = (2VA - VB - VC) / 3) for better performance
during fault, open pole, and VT and CT fail conditions. 5
Phase angle of the reference signal always displays zero degrees and all other phase angles are relative to this signal. If the
pre-selected reference signal is not measurable at a given time, the phase angles are not referenced to any external AC
signal and are referenced to the internal reference to continue maintaining proper phase relationship between all other
measured AC signal.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of phase angle indications between different UR-
series relays.
ALTERNATE FREQ AND PHS REFERE — This setting determines the alternative source for frequency tracking and phase angle
reference. If the signal specified by the main FREQUENCY AND PHASE REFERENCE setting is lost, the reference will be
switched to this alternative reference.
The switching between the main reference and the alternative reference shall be allowed (activated) only if the following
conditions are true,
1. Frequency tracking is enabled, AND
2. The alternative reference is set to a source other than None, AND
3. The selected signals between main and alternative FREQUENCY AND PHASE REFERENCE are different.
Note that even the same source is selected in the main and in the alternative FREQUENCY AND PHASE REFERENCE, but
different signals are selected in the main and the alternative SIGNAL TO TRACK, the switching is also allowed (activated).
When main source signal becomes available again, relay will switch back to the main source.
ALT SIGNAL TO TRACK — Same as the SIGNAL TO TRACK setting in the main FREQUENCY AND PHASE REFERENCE, but the
signal defined here is used for the ALTERNATE FREQ AND PHS REFERENCE. When the same source is selected in both main
REFERENCE and alternate REFERENCE, the signal selected in this setting must be different from the signal selected in the
main REFERENCE, otherwise no switching is performed.
If neither main nor alternate signals are available, tracking frequency is reverting to nominal until either main or alternate
signals are available and measurable.
FREQUENCY TRACKING — Set it to “Disabled” only in unusual circumstances; consult GE Grid Solutions for special variable-
frequency applications.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-161


SYSTEM SETUP CHAPTER 5: SETTINGS

The frequency tracking feature functions only when the F60 is in the “Programmed” mode. If the F60 is “Not
Programmed,” then metering values are available but can exhibit significant errors.

5.5.3 Signal sources


SETTINGS  SYSTEM SETUP  SIGNAL SOURCES  SOURCE 1(4)
 SOURCE 1 SOURCE 1 NAME: Range: up to 20 alphanumeric characters
  SRC 1

SOURCE 1 PHASE CT: Range: None, F1,... up to any 6 CTs. Only Phase CT
 None inputs are displayed.

SOURCE 1 GROUND CT: Range: None, F1,... up to any 6 CTs. Only Ground CT
 None inputs are displayed.

SOURCE 1 PHASE VT: Range: None, F5, M5


 None Only phase voltage inputs are displayed

SOURCE 1 AUX VT: Range: None, F5, M5


 None Only auxiliary voltage inputs are displayed

SRC 1 ALT PHASE CT: Range: None, F1,... up to any 6 CTs


 None

SRC 1 ALT GROUND CT: Range: None, F1,... up to any 6 CTs


 None
5  SWITCH TO ALT CT: Range: FlexLogic operand
Off

SRC 1 ALT PHASE VT: Range: None, F5, M5


 None

SRC 1 ALT AUX VT: Range: None, F5, M5


 None

SRC 1 SWITCH ALT VT: Range: FlexLogic operand


 Off

Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter
represents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called
“5” in a particular CT/VT module. See the Introduction to AC Sources section at the beginning of this chapter for details.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others are referred.
For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5,” scaled to whichever CT
has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio
and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs are summed together.

When the F60 is equipped with a type 8Z CT/VT module for high impedance fault detection, do not assign the CT
bank of this module to a source that is used by any conventional protection element. The type 8Z module CT bank
is used solely by the high impedance fault detection algorithm.

5-162 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

5.5.3.1 User selection of AC parameters for comparator elements


CT/VT modules automatically calculate all current and voltage parameters from the available inputs. Users must select the
specific input parameters to be measured by every element in the relevant settings menu. The internal design of the
element specifies which type of parameter to use and provides a setting for source selection. In elements where the
parameter can be either fundamental or RMS magnitude, such as phase time overcurrent, two settings are provided. One
setting specifies the source, the second setting selects between fundamental phasor and RMS.

5.5.3.2 AC input actual values


The calculated parameters associated with the configured voltage and current inputs are displayed in the current and
voltage sections of actual values. Only the phasor quantities associated with the actual AC physical input channels display
here. All parameters contained within a configured source are displayed in the sources section of the actual values.

5.5.3.3 Disturbance detectors (internal)


The disturbance detector (ANSI 50DD) element is a sensitive current disturbance detector that detects any disturbance on
the protected system. The 50DD function is used directly in some elements in the relay, for example VT Fuse Failure
detector or Fault Report. It can also be used to supervise current-based elements to prevent maloperation as a result of
the wrong settings or external CT wiring problem. A disturbance detector is provided for each source.
The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector logic is as
follows.
Figure 5-68: Disturbance detector logic (example using six sources)
6(77,1*

352'8&76(783',63/$<
$&78$/

5
3523(57,(6&855(17
6285&( &872))/(9(/
&855(173+$625
7,0(5
,B __,B_ _,B
_ _ ! &87 2)) )/(;/2*,&23(5$1'

,B __,B_ _,B
_ _ ! &87 2)) 25 F\F 65&''23
,B __,B_ _,B
_ _ ! &87 2))
:KHUH,·LVF\FOHVROG

6(77,1*

352'8&76(783',63/$<
$&78$/
3523(57,(6&855(17
6285&( &872))/(9(/
&855(173+$625
7,0(5
,B __,B_ _,B
_ _ ! &87 2)) )/(;/2*,&23(5$1'

,B __,B_ _,B
_ _ ! &87 2)) 25 F\F 65&''23
,B __,B_ _,B
_ _ ! &87 2))
:KHUH,·LVF\FOHVROG

6(77,1*

352'8&76(783',63/$<
$&78$/
3523(57,(6&855(17
6285&( &872))/(9(/
&855(173+$625
7,0(5
,B __,B_ _,B
_ _ ! &87 2)) )/(;/2*,&23(5$1'

,B __,B_ _,B
_ _ ! &87 2)) 25 F\F 65&''23
,B __,B_ _,B
_ _ ! &87 2))
:KHUH,·LVF\FOHVROG
$FGU

The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL) controls the sensitivity of the disturbance detector
accordingly.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-163


SYSTEM SETUP CHAPTER 5: SETTINGS

5.5.3.4 Example for use of sources


An example of the use of sources is shown in the following figure. A relay can have the following hardware configuration:
Increasing slot position letter -->
UR CT/VT module 1 CT/VT module 2 CT/VT module 3
B30, B90, C70, F35, N60, T35 8 CTs 4 CTs, 4 VTs 4 CTs, 4 VTs
C60, C95, D60, G30, G60, L30, L90, M60, T60 CTs VTs not applicable

This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
Figure 5-69: Example of use of sources

F1 DSP Bank

F5
Source 1 Source 2
Amps Amps

Source 3
51BF-1 51BF-2
U1 Volts Amps
5 A W Var 87T

A W Var 51P

Volts Amps
M1

M1 Source 4

UR Relay
M5
827794A1.CDR

Y LV D HV AUX
SRC 1 SRC 2 SRC 3
Phase CT M1 F1+F5 None
Ground CT M1 None None
Phase VT M5 None None
Aux VT None None U1

5-164 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

5.5.3.5 Source switching


The F60 supports providing current and voltage signals input from both main and alternate CTs and VTs with a user-
defined switching between them. This is beneficial in applications, where the F60 can provide protection when main CT or
VT are not available due to station re-configuration. Some application examples are shown as follows.
Figure 5-70: Examples of VTs (a) and CTs (b) switching from the main to alternate

Bus 1 Main bus


VT 1 VT 2 Transfer VT 1
Bus 2 bus

CT 1 CT 2

CT 1 UR UR

a) b)
859791A1.vsdx

This figure depicts examples of VT switching from VT1 to VT2 when Bus 1 is de-energized, and the line is energized via Bus
2. CT switching example (b) depicts connecting bus transfer breaker CT to the line relay when main line breaker is taken for
maintenance and the line is energized via transfer bus, in this case the UR senses current from either CT 1 when line is
energized via main line breaker or via CT 2 when the line is energized via transfer bus breaker.
Figure 5-71: Logic diagram of switching CTs and VTs from the main to alternate banks 5
SETTINGS SETTINGS

SOURCE 1 PHASE CT: SOURCE 1 PHASE VT:

None None

SOURCE 1 GROUND CT: SOURCE 1 AUX VT:

None None
To SOURCE 1 To SOURCE 1
SRC 1 ALT PHASE CT: currents phasor SRC 1 ALT PHASE VT: voltage phasor
calculations calculations
None None

SRC 1 ALT GROUND CT: SRC 1 ALT AUX VT:

None None

SRC 1 SWITCH ALT CT: SRC 1 SWITCH ALT VT:


FLEXLOGIC OPERAND FLEXLOGIC OPERAND
Off 0c SRC1 CT SW PROT BLK Off 0c SRC1 VT SW PROT BLK
2c 2c

FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SRC1 CT ALT BANK ON
SRC1 VT ALT BANK ON

859825A1.vsdx

When a FlexLogic operand assigned to SRC 1 SWITCH ALT CT/VT is logical "0," the analog data is processed from the main CT
and VT analog data banks. When this operand is logical "1," the analog data is processed from the alternate CT and VT
analog data banks.
Note that
• Banks assigned to the same function for the main and alternate input data have to have the same CTs and VTs
nominals and connections, otherwise a warning is generated and switching functionality is prohibited. For example,
banks assigned to the PHASE CT and ALT PHASE CT have to have same primary and secondary CT values. Ground CT
input has to be same type (cannot be one regular and another sensitive ground CT input).

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-165


SYSTEM SETUP CHAPTER 5: SETTINGS

• During switching from the main CT/VT input data to alternate input data and vice versa, all relay functions are blocked
for two power cycles and metering data does not update
• CT bank switching is allowed if both main and alternate CT banks have the exact same combination for CTs
summation
• When it is required that switching state from the main to alternate be memorized in case of F60 restart or when the
switching signal is a pulse by nature, such as a pushbutton or IEC 61850 GOOSE, use Non-volatile Latches
• Since switching occurs in both the Phase and Ground CT (Phase and Aux VT), it is possible to keep the same set, for
example phase bank under both the main source and alternate source, but different set for ground/aux signal

5.5.4 Breakers
SETTINGS  SYSTEM SETUP  BREAKERS  COMMON SETTINGS
 COMMON SETTINGS BKR INTERM & BAD ST Range: Common, Distinct
  TIMERS: Common

SETTINGS  SYSTEM SETUP  BREAKERS  BREAKER 1(4)


 BREAKER 1 BREAKER 1 Range: Disabled, Enabled
  FUNCTION: Disabled

BREAKER 1 NAME: Range: up to six alphanumeric characters


 Bkr 1

BREAKER 1 MODE: Range: 3-Pole, 1-Pole


 3-Pole
5 BREAKER1 ΦA/3P OPND: Range: FlexLogic operand
 Off

BREAKER1 ΦA/3P CLSD: Range: FlexLogic operand


 Off

BREAKER 1 ΦB OPENED: Range: FlexLogic operand


 Off

BREAKER 1 ΦB CLOSED: Range: FlexLogic operand


 Off

BREAKER 1 ΦC OPENED: Range: FlexLogic operand


 Off

BREAKER 1 ΦC CLOSED: Range: FlexLogic operand


 Off

BREAKER 1 ALARM PDisc DELAY: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

BREAKER 1 EXT ALARM: Range: FlexLogic operand


 Off

BREAKER 1 RACKED-IN: Range: FlexLogic operand


 Off

BREAKER 1 OUT OF SV: Range: FlexLogic operand


 Off

BREAKER 1 OPEN CMD: Range: FlexLogic operand


 Off

BRK1 COMMS OPEN CMD: Range: FlexLogic operand


 Off

BREAKER 1 CLOSE CMD: Range: FlexLogic operand


 Off

5-166 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

BRK1 COMMS CLS CMD: Range: FlexLogic operand


 Off

BREAKER1 PB CONTROL: Range: FlexLogic operand


 Off

BREAKER1 TOPERATE: Range: 0 to 65535 ms in steps of 1


 70 ms

BREAKER 1 BAD ST TSUPPRESS: Range: 0 to 65535 ms in steps of 1


 0 ms

MANUAL CLOSE RECAL1 TIME: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

BREAKER 1 OPEN SEAL-IN: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

BREAKER 1 AR BLOCK: Range: Disabled, Enabled


 Disabled

BREAKER 1 BLK OPEN: Range: FlexLogic operand


 Off

BREAKER 1 BLK CLOSE: Range: FlexLogic operand


 Off

BRK1 BLK BYPASS: Range: Disabled, Enabled


 Disabled

BREAKER 1 TAGGING: Range: Disabled, Enabled


 Disabled

 BREAKER 1 SUBSTITUTN:
Disabled
Range: Disabled, Enabled 5
BREAKER 1 EVENTS: Range: Disabled, Enabled
 Disabled

BRK1 CILO INTRLK TO LOCAL Range: Disabled, Enabled


 CTRL: Disabled

BRK1 CILO INTERLOCK GFP Range: Disabled, Enabled


 BYPASS: Disabled

BREAKER 1 LOCAL: Range: FlexLogic operand


 Off

BRK1 BLK ML CMD IN LOCAL: Range: Disabled, Enabled


 Disabled

BRK1 CSWI LOC STAT: Range: FlexLogic operand


 Off

BRK1 STATION AUTHOR: Range: FlexLogic operand


 Off

BREAKER 1 OPEN INTERLOCK: Range: FlexLogic operand


 Off

BREAKER 1 CLOSE INTERLOCK: Range: FlexLogic operand


 Off

BREAKER 1 SYNCCHECK CLOSE: Range: FlexLogic operand


 Off

BREAKER 1 POS-REACHED Range: Enabled, Disabled


 CHECK: Enabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-167


SYSTEM SETUP CHAPTER 5: SETTINGS

The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that trip and close the breaker to use FlexLogic operands BREAKER 1
OFF CMD (or BREAKER 1 TRIP A/B/C in the case of single-pole tripping) and BREAKER 1 ON CMD, and configure the
breaker control element inputs as described here.
A description of the operation of the breaker control and status monitoring features from the front panel is provided in
chapter 4.
BKR INTERM & BAD ST TIMERS — When set to “Common”, the breaker element considers both “00” and “11” states of 52a and
52b as an intermediate state and when the Toperate timer expires, declares the breaker as bad status. When set to
“Distinct”, the breaker element considers “00” state of 52a and 52b as an intermediate state and “11” as bad status. When
the breaker status detected is 00, the breaker element waits for the Toperate timer to expire before declaring the
intermediate state. When the breaker status detected is 11, the breaker element waits for the Bad ST Tsuppress timer to
expire before declaring the bad state. See breaker logic diagrams 2 and 4.
The following settings are available for each breaker control element.
BREAKER 1 FUNCTION — This setting enables and disables the operation of the breaker 1 control feature.
BREAKER 1 NAME — Assign a user-defined name (up to six characters) to the breaker. This name is used in flash messages
related to breaker 1.
BREAKER 1 MODE — Selects “3-Pole” mode, where all breaker poles are operated simultaneously, or selects “1-Pole” mode
where all breaker poles are operated either independently or simultaneously.
BREAKER1 ΦA/3P OPND — Selects an operand, usually a contact input, that is for a normally-closed 52/b status input that
creates a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted 52/a status
5 signal or the inverted BREAKER 1 CLOSED status signal can be used.
BREAKER1 ΦA/3P CLSD — Selects an operand, usually a contact input connected to a breaker auxiliary position tracking
mechanism. This input is for a normally-open 52/a status input that creates a logic 1 when the breaker is closed. If the
BREAKER 1 MODE setting is selected as “3-Pole” this setting selects a single 52/a input as the operand used to track the
breaker open or closed position. If the mode is selected as “1-Pole” the input mentioned is used to track phase A and the
BREAKER 1 ΦB and BREAKER 1 ΦC settings select operands to track phases B and C, respectively.
BREAKER1 ΦB OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER1 ΦB CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER1 ΦC OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER1 ΦC CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1 ALARM PDisc DELAY — This setting specifies the delay interval during which a disagreement of status among the
pole position tracking operands does not declare a pole discrepancy. This allows for non-simultaneous operation of the
poles.
If single-pole tripping and reclosing is used, the breaker can trip unsymmetrically for faults. In this case, the minimum
alarm delay setting must exceed the maximum time required for fault clearing and reclosing by a suitable margin.
BREAKER 1 EXT ALARM — This setting selects an operand, usually an external contact input connected to a breaker alarm
reporting contact. While the selected operand is active, the BREAKER 1 TROUBLE operand is activated.
BREAKER 1 RACKED-IN — This setting selects a contact input to show whether the breaker is racked-in or racked-out. The
racked-in or racked-out status is used to indicate dynamically the status of breaker symbol, only applied in the single-line
diagram on the graphical front panel. If this setting is set to Off, the racked status is not considered.
BREAKER 1 OUT OF SV — Selects an operand indicating that breaker 1 is out-of-service.

5-168 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

BREAKER 1 OPEN CMD — Selects an operand that initiates Breaker 1 open/trip command. Open command is not executed
when blocked by the operand assigned to BREAKER 1 BLK OPEN setting.
BRK1 COMMS OPEN CMD — Selects an operand that initiates Breaker 1 open command. The setting is intended for
commands received via communication protocols (DNP3, IEC104 and Modbus) to be supervised by IED Local/Remote
status. The open command is not executed if IED is in the local mode or blocked by the operand assigned to BREAKER 1 BLK
OPEN setting.
BREAKER 1 CLOSE CMD — Selects an operand that initiates Breaker 1 close command. Close command is not executed when
blocked by operand assigned to BREAKER 1 BLK CLOSE setting.
BKR 1 COMMS CLS CMD — Selects an operand that initiates Breaker 1 close command. The setting is intended for commands
received via communication protocols (DNP3, IEC104 and Modbus) to be supervised by IED Local/Remote status. The close
command is not executed if the IED is in local mode or blocked by the operand assigned to BREAKER 1 BLK CLOSE setting.
BREAKER 1 PB CONTROL — Local breaker control operations (that is, open/close) are allowed from front panel pushbuttons
when the selected operand value is high.
BREAKER 1 TOPERATE — This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS FlexLogic operand is asserted for alarm or blocking purposes.
BREAKER 1 BAD ST TSUPPRESS — When the BKR INTERM & BAD ST TIMERS setting is set to “Distinct” this setting specifies the
required interval to overcome the transient state of 11 during the breaker operation. If the 11 state still exists after this
time, the BREAKER 1 BAD STATUS FlexLogic operand is asserted. When the BKR INTERM & BAD ST TIMERS setting is set to
“Common” this setting is not used.
MANUAL CLOSE RECAL1 TIME — This setting specifies the seal-in time of the close commands due to an operator-initiated
manual close command to the circuit breaker.
BREAKER 1 OPEN SEAL-IN — This setting specifies the seal-in time of the three-pole open command initiated by either the
Trip Out element or a manual open command to the circuit breaker. 5
BREAKER 1 AR BLOCK —Set to “Enable” to block the Autoreclose element.
The Autoreclose element is not automatically inhibited by BLOCK AR from the front panel. If the autoreclose scheme needs
to be inhibited, set setting AR BLOCK in the corresponding Autoreclose element with the BREAKER 1 BLK RCLS operand.
BREAKER 1 BLK OPEN — Selects an operand that prevents initiation of Breaker 1 open and individual phase trip commands.
This setting can be used for blocking circuit breaker tripping for instance when breaker monitoring detects conditions such
as low SF6 gas density during which breaker opening can cause damage.
BREAKER 1 BLK CLOSE — Selects an operand that prevents initiation of Breaker 1 close commands. This setting can be used
for blocking circuit breaker closing, for instance to prevent closing into a closed ground switch.
BRK1 BLK BYPASS — Set to “Enable” to allow the graphical front panel to bypass breaker 1 blocking. When asserted, BREAKER
1 BLK OPEN and BREAKER 1 BLK CLOSE settings are bypassed. This setting is only available if the order code includes GFP.
BREAKER 1 TAGGING — Breaker tagging is used to block certain operation when it is tagged for safety purposes. No other
action is needed after enabling the function; it is handled internally where certain functions are blocked.
Set to “Enable No Override” to allow the graphical front panel or IEC 61850 MMS control to tag breaker 1. When tagged
from the graphical front panel, tagging can be removed only from the graphical front panel, and an attempt to remove
tagging using IEC 61850 MMS control results in a negative response (-Rsp). When tagged from IEC 61850 MMS control,
tagging can be removed only by MMS control.
Set to “Enable With Override” to allow the graphical front panel or IEC 61850 MMS control to tag breaker 1. When tagged
from the graphical front panel, tagging can be removed only from the graphical front panel, and an attempt to remove
tagging using IEC 61850 MMS control results in a negative response (-Rsp). When tagged from IEC 61850 MMS control,
tagging can be removed by MMS control or from the graphical front panel. That is, the graphical front panel has an
override function.
When tagged, the following operations are disabled: pushbutton open/close, IEC 61850 open/close, and close command
initiated by BREAKER 1 CLOSE setting. The trip command issued by the Trip Out element or BREAKER 1 OPEN setting is not
affected. This setting is only available if the order code includes GFP.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-169


SYSTEM SETUP CHAPTER 5: SETTINGS

BREAKER1 SUBSTITUTN — Set to “Enable” to allow the graphical front panel/IEC 61850 to substitute breaker 1 status. When
substituted, breaker 1 control open/close status is forced to the substituted value. This setting is only available if the order
code includes GFP.
BRK1 CILO INTRLK TO LOCAL CTRL — Set to “Enable” to allow CILO interlock to apply to front panel and FlexLogic operand
controls. This setting is available only if the order code includes IEC 61850.
BRK1 CILO INTERLOCK GFP BYPASS — Set to “Enable” to allow the graphical front panel to bypass the CILO interlock for front
panel and FlexLogic operand controls. This setting is available only if the order code includes IEC 61850 and GFP.
BREAKER 1 LOCAL — Set in the EnerVista software or via SCL file. It selects an operand that indicates the Breaker in the
switch yard is in Local or Remote mode. When the operand value is set, it indicates that the Breaker is in Local mode. For
the IEC 61850 order code option, refer to the below Control Authority table for control behavior.
BRK1 BLK MNL CMD IN LOCAL — When set to “Enabled” and the BREAKER 1 LOCAL operand state is logic “1” (i.e. the Breaker is
in Local mode and Bkr0XCBR1.Loc is TRUE), manual commands originating from the front panel pushbuttons, graphical
front panel and BREAKER 1 OPEN/CLOSE CMD are blocked. When set to “Disabled”, manual commands originating from relay
are allowed even when the Breaker is in Local mode (BREAKER 1 LOCAL operand state is logic “1”). Please refer to the Control
Authority table below for control behavior. This setting is available only if the order code includes IEC 61850.
BKR1 CSWI LOC STAT — Selects an operand that indicates the breaker residing in that bay is in Local or Remote mode. When
the operand state is logic “1”, the bay is considered in Local mode and when the operand state is “0”, the bay is considered
in Remote mode. The operand status is modeled in the IEC 61850 server using the respective breaker’s CSWI Loc data
object and the user should refer to the operand status in the Control Authority table below to determine the control
authority for different levels. This setting is available only if the order code includes IEC 61850.
BKR1 STATION AUTHOR — Selects an operand that indicates the Station level authority status. The operand status is modeled
in the IEC 61850 server using the respective breaker’s CSWI LocSta data object the user should refer to the operand status
in the Control Authority table below to determine the control authority for different levels. This setting is available only if the
5 order code includes IEC 61850.
BREAKER 1 OPEN INTERLOCK — Selects an operand that indicates the interlock status for the Breaker Open commands. This
operand state is mapped directly to the IEC 61850 BkrCILO1.EnaOpn.stVal, which is used to reject the IEC 61850 open
command when the selected operand state is at logic “0” (BkrCILO1.EnaOpn.stVal is set to false). However, the IEC 61850
client can select to check or skip the interlock condition to execute the command using the “Check” parameter in control
command.
Additionally, the interlock condition can be applied to the local commands as well, which can originate from the front local
HMI, front panel push buttons, graphical front panel (GFP) and FlexLogic Operands assigned to BREAKER 1 OPEN CMD
setting. This is achieved by selecting setting BRK1 CILO INTRLK TO LOCAL CTRL as “Enabled”. This setting is available only if the
order code includes IEC 61850.
BREAKER 1 CLOSE INTERLOCK — Selects an operand that indicates the interlock status for the Breaker Open commands. This
operand state is mapped directly to the IEC 61850 BkrCILO1.EnaCls.stVal, which is used to reject the IEC 61850 close
command when the selected operand state is at logic “0” (BkrCILO1.EnaCls.stVal is set to false). However, the IEC 61850
client can select to check or skip the interlock condition to execute the command using the “Check” parameter in control
command.
Additionally, the interlock condition can be applied to the local commands as well, which can originate from the front local
HMI, front panel push buttons, graphical front panel (GFP) and FlexLogic Operands assigned to BREAKER 1 CLOSE CMD
setting. This is achieved by selecting setting BRK1 CILO INTRLK TO LOCAL CTRL as “Enabled”. This setting is available only if the
order code includes IEC 61850.
BREAKER 1 SYNCCHECK CLOSE - Selects an operand that indicates the status of the synchrocheck function of the Breaker.
When the operand value is set, the remote commands from IEC 61850 client are rejected if the IEC 61850 client set the
synchrocheck bit in the “Check” parameter of the control command. This setting is only available if the order code includes
IEC 61850.
BREAKER 1 POS-REACHED CHECK — When “Enabled”, the IEC 61850 control value is checked for current Breaker status and is
rejected if the command value (Open/Close) from IEC 61850 client match with the present Breaker status. When “Disabled”,
the current Breaker status is not verified to accept the control. This setting is only available if the order code includes IEC
61850.

5-170 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Before software release version 7.90, ST.LOC OPERAND, INTERLOCK OPN, INTERLOCK CLS and SYNCCHECK CLOSE
settings were available in IEC 61850 configurator under System Setup > Breaker. From version 7.90 onwards, the
above mentioned settings were removed from the IEC 61850 configurator and merged with the Breaker settings
screen under Settings > System Setup > Breakers (outside the IEC 61850 configurator). Also, the name of the setting
ST.LOC OPERAND has been changed to LOCAL.
BREAKER 1 LOCAL, INTERLOCK OPEN, INTERLOCK CLOSE, SYNCCHECK CLOSE settings are not available on the front panel
and can be configured either from EnerVista Software or via SCL files. Refer to the MICS document online for
respective settings modeling in SCL files. BREAKER 1 POS-REACHED CHECK is only configurable via EnerVista
software.

Control authority
Within the substation, control commands to the primary equipment, such as the breaker or disconnect switch, can be
originated from one of three levels - Bay, Station or Remote. Station level commands are those originating from either the
substation gateway or from the station HMI and Remote commands are from the remote Network Control Center (NCC).
Bay level commands, however, are commands originating from bay devices such as bay controllers (e.g. C264) or IEDs
(protection relays), either using 61850 control services or using non-61850 control methods (front panel pushbuttons,
graphical front panel or commands initiated through FlexOperands).
Under certain operational conditions, such as during maintenance, it is necessary to block commands from one or more of
these levels. The local/remote control feature (described in IEC61850 7-4: Annex B) allows users to enable or disable control
authority from one or more of the three levels, as illustrated in the below table. IEC61850 commands originating from the
various levels are differentiated using the Origin.OrCat attribute value in the 61850 command. The IEC61850 7-4 Local/
Remote table is extended with Bay level non-61850 commands and those commands are only allowed when the Bay level
has the control authority.

Table 5-18: Control Authority 5


Switch Bay Control Command from
Bay Station NCC
Mode of Local Control Manual orCat
switching Control Authority At Control at
authority for Behavior Station Level Switch
local control (process)
BKR1 BLK XCBR.LocX LLN0.MltLev CSWI.Loc CSWI.LocSta Non Local Station Remote
MNL CMD IN SWI.Loc 61850 Bay Ctl
LOCAL Control (Bay)
Enabled T F n.a. n.a. AA NA NA NA NA
Disabled T F n.a. n.a. AA AA NA NA NA
n.a. F F T n.a. AA AA AA NA NA
n.a. F F F T AA NA NA AA NA
n.a. F F F F AA NA NA NA AA
Enabled T T n.a. n.a. AA NA NA NA NA
Disabled T T n.a. n.a. AA AA NA NA NA
n.a. F T T n.a. AA AA AA NA NA
n.a. F T F T AA AA AA AA NA
Default n.a. F T F F AA AA AA AA AA

n.a. - not applicable


AA - Always Allowed
NA - Not Allowed
Non-61850 Bay Control - Any manual control from the relay, i.e. from the front panel, the relay push buttons or a FlexOperand initiated
command.
Manual Control at Switch (process) - Control external to the IED, e.g. the breaker may be controlled directly from the control panel.
Cells highlighted in gray are not defined in the standard and reflect UR’s commitment to maintaining backwards compatibility.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-171


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-72: Dual breaker control logic (Sheet 1 of 4)


6(77,1*
%5($.(5)81&7,21
(QDEOHG 
6(77,1* %NU&,/2 (QD2SQ VW9DO
)/(;/2*,&23(5$1'
%5.&,/2,175/.
%5($.(57$*21
72/2&$/&75/ (QDEOHG 
6(77,1* )/(;/2*,&23(5$1'
)/(;/2*,&23(5$1'
%5($.(5386+%87721 %5./2&$/23(1&,/2
&21752/ %5. &,/2%<3$6621 $1'
2Ⱥ 
$1' 6(77,1*
86(52))21
%UHDNHU2SHQ,QWHUORFN
7RRSHQ%.5  QDPH )/(;/2*,&23(5$1'
25 2Ⱥ 
$1' %5. /2&$/$87+2521
%UHDNHU2SHQ 25
)URPJUDSKLFDO IURQWSDQHO C
%NU&6:,/RF6WDFWO9DO )/(;/2*,&23(5$1'
$1' $1' %5. 5(0$87+2521
6(77,1*
25
%5.67$7,21$87+25 $1'
)/(;/2*,&23(5$1'
2Ⱥ  25
$1' $1' %5. 67$71$87+2521
6(77,1* $1'
%5.&6:,/2&67$7 $1' )/(;/2*,&23(5$1'
2Ⱥ  $1' 25 %5. %$<$87+2521
$1'
6(77,1*
0XOWL/HYHO&RQWURO
$1' $1' %NU&6:,2S2SQJHQHUD
(1$%/(' 
O
6(77,1* $1' )/(;/2*,&23(5$1'
%5.%/.01/&0',1/2&$/
(1$%/('  $1' %5($.(501/23(1
$1'
6(77,1*
%UHDNHU/RFDO 25
2Ⱥ 
$1' )/(;/2*,&23(5$1'
%NUR;&%53RVFWO9DO RȺ $1' 25 $1' %5($.(52))&0'
%NU&6:,3RVFWO9DO RȺ 25
6(77,1*
)URP ,(&SURWRFRO $1'
%5($.(523(1
25 6($/,1
)URPVKHHW RI )/(;/2*,&23(5$1'
7 3.3 25
%UHDNHU2SHQFRPPDQG $1' %5($.(575,3$
 $1'
)/(;/2*,&23(5$1'6
75,3 32/(
)/(;/2*,&23(5$1'
75,33+$6($
25 $1' %5($.(575,3%
75,33+$6(%
75,33+$6(&

5
2Q'/ /IURP7ULS
2XWSXWRQO\RQEUHDNHU )/(;/2*,&23(5$1'
)URP ,(&SURWRFRO $1' 25 $1' %5($.(575,3&
%NU&6:,%ON2SQFWO9DO RQ

%NU;&%5 %ON2SQFWO9DO RQ


$1'
6(77,1* %NU&6:,%ON2SQVW9DO
%5($.(5%/.23(1 25 7RSURWRFRO
2Ⱥ 
%NU;&%5%ON2SQVW9DO
)/(;/2*,&23(5$1' $1'
%5. %/.%<3$6621 %NU&,/2 (QD&OV VW9DO
)URP ,(&SURWRFRO %NU&6:,&PG%ONVW9DO
$1'
%NU&6:,&PG%ONFWO9DO RQ
7RSURWRFRO
6(77,1*
$1'
%UHDNHU&ORVH,QWHUORFN
$1' %NU&6:,%ONVW9DO
2Ⱥ 
$1' 7RSURWRFRO
86(52))21 $1'
7RFORVH%.5  QDPH
25
25 )/(;/2*,&23(5$1'
%UHDNHU&ORVH
%5./2&$/&/6&,/2
)URP JUDSKLFDO IURQW SDQHO $1'

)URP ,(&SURWRFRO $1'


%NU;&%53RVFWO9DO RQ
25 $1' )/(;/2*,&23(5$1'
%NU&6:,3RVFWO9DO RQ
$1' $1' %5($.(501/&/6
25
25
)URPVKHHW RI 6(77,1*
$1' 0$18$/&/26(
%UHDNHU &ORVH FRPPDQG $1'
5(&$/7,0( %NU&6:,2S&OVJHQHUDO
7 3.3

)/(;/2*,&23(5$1'
)/(;/2*,&23(5$1' 25 $1' %5($.(521&0'
%5($.(5(1$5&/6 $1'

)/(;/2*,&23(5$1'
$5&/26(%.5 
2Q&'/ /EUHDNHU $1'
PV 25
DQGIURP$XWRUHFORVH 25
)URP ,(&SURWRFRO $1'
%NU&6:,%ON&OVFWO9DO RQ

%NU;&%5%ON&OVFWO9DO RQ %NU&6:,%ON&OVVW9DO


$1'
6(77,1* 25 %NU;&%5%ON&OVVW9DO
%5($.(5%/.&/26(
$1' 7RSURWRFRO
2Ⱥ 
(QDEOH
WRVKHHW
&6:,FPG %.5
%ONWR /2&$/WR
VKHHW VKHHW
$FGU

5-172 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-73: Dual breaker control logic (Sheet 2 of 4)


from sheet 1
SETTING
Enable
BKR INTERM & BAD ST TIMERS
= COM MON
SETTING
= DIS TINCT to shee t 4
BRE AKER 1 M ODE
= 1-Pole
= 3-Pole

FLEXLOGIC OPERANDS
BRE AKER 1 SU BD CLSD
FLEXLOGIC OPERAND
BRE AKER 1 SU BD OPEN BKR1 A CLOS ED AND BRE AKER 1 ΦA CLS D
AND
SETTING
FLEXLOGIC OPERAND
BRE AKER 1 ΦA/3P CLSD
OR BKR1 A OPENED AND BRE AKER 1 ΦA OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
BRE AKER 1 ΦA/3P OPND SETTING AND BRE AKER 1 ΦA INTERM
OR AND
= Off AND BRE AKER 1 TOPERATE FLEXLOGIC OPERAND
OR T P KP BRE AKER 1 ΦA BAD S T
AND
AND 0

FLEXLOGIC OPERAND
BKR1 B CLOS ED AND BRE AKER 1 ΦB CLS D
AND
SETTING
BRE AKER 1 ΦB CLS D FLEXLOGIC OPERAND
OR BKR1 B OPENED AND BRE AKER 1 ΦB OPEN
= Off AND
AND
SETTING
FLEXLOGIC OPERAND
BRE AKER 1 ΦB OPENE D
OR AND AND BRE AKER 1 ΦB INTERM
= Off AND
OR SETTING
BRE AKER 1 TOPERATE FLEXLOGIC OPERAND
AND AND BRE AKER 1 ΦB BAD S T
T P KP
0

FLEXLOGIC OPERAND
BKR1 C CLOS ED AND BRE AKER 1 ΦC CLS D
AND
SETTING
BRE AKER 1 ΦC CLS D FLEXLOGIC OPERAND
OR BKR1 C OPENED AND BRE AKER 1 ΦC OPEN
= Off AND

5
AND
SETTING
FLEXLOGIC OPERAND
BRE AKER 1 ΦC OPENE D AND
OR AND BRE AKER 1 ΦC INTERM
= Off AND
OR SETTING
BRE AKER 1 TOPERATE FLEXLOGIC OPERAND
AND AND BRE AKER 1 ΦC BAD ST
T P KP
0

FLE XLOGIC OPERAND


OR BRE AKER 1 BAD STATUS

SETTING
FLEXLOGIC OPERAND
BRE AKER 1 EXT ALARM
AND BRE AKER 1 TROU BLE
= Off OR

AND FLEXLOGIC OPERAND


BKR1 A CLOS ED AND BRE AKER 1 CLOS ED
OR
BKR1 B CLOS ED
When the BKR INTERM & BAD AND
BKR1 C CLOS ED SETTING
ST TIMERS setting is BRE AKER 1 ALARM DELAY
FLEXLOGIC OPERAND
“Common,” breaker element AND BRE AKER 1 D ISCREP
T P KP
uses the logic highlighted in AND
0
dashed box for Breaker 1 ΦA/
ΦB/ΦC INTERM and BAD ST BKR1 A OPENED
AND FLEXLOGIC OPERAND
FlexLogic operands BKR1 B OPENED
AND BRE AKER 1 OPEN
BKR1 C OPENED OR

AND
FLEXLOGIC OPERAND
BKR1 A CLOS ED AND BRE AKER 1 ANY P OPEN
BKR1 B CLOS ED AND
BKR1 C CLOS ED
FLEXLOGIC OPERAND
AND BRE AKER 1 1P OPEN
XOR
SETTING
BRE AKER 1 OUT OF S V FLEXLOGIC OPERAND
= Off AND BRE AKER 1 OOS

Enable
to shee t 3
859814A1.vsdx

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-173


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-74: Dual breaker / graphical front panel control logic (Sheet 3 of 4)
IURPVKHHW  IURPVKHHW 
&6:,FPG %.5
6(77,1*  %ON /2&$/
%5($.(57$**,1*
(QDEOH1R2YHUULGH 25
(QDEOHZLWK2YHUULGH
IURPVKHHW
$1' (QDEOH
%NU&6:,7DJ 2QFWO9DO 2Q $1'
25
%NU;&%57DJ 2QFWO9DO 2Q 1RQYRODWLOH
25 5HVHWGRPLQDQW
%UHDNHU7DJ 6 )/(;/2*,&23(5$1'
)URPJUDSKLFDOIURQWSDQHO /DWFK %5($.(57$*21
$1' %5($.(57$*2))
25 5
25

$1'
%UHDNHU5HPRYH7DJ
25
%NU&6:,7DJ 2QFWO9DO 2Ⱥ $1'
$1'
25
%NU;&%57DJ 2QFWO9DO 2Ⱥ

6(77,1*
%5($.(568%67,7871
1RQYRODWLOH
(QDEOHG 
5HVHWGRPLQDQW
%UHDNHU6XEVWLWXWH2SHQ 6 )/(;/2*,&23(5$1'
/DWFK %5($.(568%'23(1
%UHDNHU5HPRYH6XEVWLWXWLRQ
25 5
)URPJUDSKLFDOIURQWSDQHO

%UHDNHU6XEVWLWXWH&ORVHG 6 )/(;/2*,&23(5$1'
/DWFK %5($.(568%'&/6'
25 5

6(77,1*
%5($.(5 %/.%<3$66
(QDEOHG  1RQYRODWLOH
5HVHWGRPLQDQW

5
%UHDNHU %ON%\SDVV 6 )/(;/2*,&23(5$1'
/DWFK %5. %/.%<3$6621
%UHDNHU5HPRYH %ON%\SDVV
)URP JUDSKLFDO IURQWS DQHO 25 5 %5. %/.%<3$662))

)RUUHOD\VZLWK$5HOHPHQW
6(77,1*
%5($.(5$5%/2&.
(QDEOHG  1RQYRODWLOH
5HVHWGRPLQDQW
%UHDNHU%ORFN$XWRUHFORVH 6 )/(;/2*,&23(5$1'
/DWFK %5($.(5%/.5&/6
%UHDNHU8QEORFN$XWRUHFORVH
25 5 %5($.(5(1$5&/6
)URPJUDSKLFDOIURQWSDQHO

6(77,1*
%5.&,/2,17(5/2&.*)3
%<3$66 (QDEOHG  1RQYRODWLOH
5HVHWGRPLQDQW
%UHDNHU ,QWHUORFN%\SDVV 6 )/(;/2*,&23(5$1'
%5.&,/2 %<3$6621
/DWFK
%UHDNHU 5HPRYH ,QWHUORFN %\SDVV %5.&,/2 %<3$662))
)URPJUDSKLFDOIURQWSDQHO 5
25

$FGU
Settings marked “**” are only available in order codes that include IEC 61850 and GFP.
Settings marked “***” are only available in order codes that include GFP.

The breaker element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each breaker, using either CSWI or XCBR IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking of open/close commands are provided. Note
that the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/
open command for a certain time, do so by setting the seal-in timers BREAKER 1 OPEN SEAL-IN and MANUAL CLOSE RECAL1
TIME, on the contact outputs using the “Seal-in” setting, in the Trip Output element, and/or in FlexLogic.

5-174 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-75: Dual breaker control logic (Sheet 4 of 4)


BKR INTERM & BAD ST TIMERS = D istinct
from sheet 2 1-Pole Enable

SETTING
BRE AKER1 BAD ST
FLEXLOGIC OPERAND
TSU PPRESS
T P KP AND BRE AKER 1 ΦA BAD ST
AND 0

SETTING
BRE AKER 1 TOPERATE FLEXLOGIC OPERAND
AND T P KP AND BRE AKER 1 ΦA INTERM
0

1-Pole Enable

When the BKR INTERM & BAD ST SETTING


TIMERS setting is "Distinct," breaker BRE AKER1 BAD ST
FLEXLOGIC OPERAND
element replaces the sheet 2 TSU PPRESS
AND BRE AKER 1 Φ Θ BAD ST
highlighted logic in dashed box with AND T P KP
0
logic shown here for Breaker 1 ΦA/
ΦB/ ΦC INTERM and BAD ST
SETTING
FlexLogic operands
BRE AKER 1 TOPERATE FLEXLOGIC OPERAND
AND T P KP AND BRE AKER 1 ΦΘINTERM
0

Where Θ is B and C

859815A1.vsdx

5.5.5 Disconnect switch control


SETTINGS  SYSTEM SETUP  SWITCHES  COMMON SETTINGS 5
 COMMON SETTINGS SW INTERM & BAD ST Range: Common, Distinct
  TIMERS: Common

SETTINGS  SYSTEM SETUP  SWITCHES  SWITCH 1(16)


 SWITCH 1 SWITCH 1 FUNCTION: Range: Disabled, Enabled
  Disabled

SWITCH 1 NAME: Range: up to six alphanumeric characters


 SW 1

SWITCH 1 MODE: Range: 3-Pole, 1-Pole


 3-Pole

SWTCH 1 ΦA/3P OPND: Range: FlexLogic operand


 Off

SWTCH 1 ΦA/3P CLSD: Range: FlexLogic operand


 Off

SWITCH 1 ΦB OPENED: Range: FlexLogic operand


 Off

SWITCH 1 ΦB CLOSED: Range: FlexLogic operand


 Off

SWITCH 1 ΦC OPENED: Range: FlexLogic operand


 Off

SWITCH 1 ΦC CLOSED: Range: FlexLogic operand


 Off

SWITCH 1 ALARM PDisc DELAY: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-175


SYSTEM SETUP CHAPTER 5: SETTINGS

SWITCH 1 OPEN CMD: Range: FlexLogic operand


 Off

SW1 COMMS OPEN CMD: Range: FlexLogic operand


 Off

SWITCH 1 CLOSE CMD: Range: FlexLogic operand


 Off

SW1 COMMS CLS CMD: Range: FlexLogic operand


 Off

SWITCH 1 PB CONTROL: Range: FlexLogic operand


 Off

SWITCH 1 TOPERATE: Range: 0 to 65535 ms in steps of 1


 70 ms

SWITCH 1 BAD ST TSUPPRESS: Range: 0 to 65535 ms in steps of 1


 0 ms

SWITCH 1 OPEN SEAL-IN: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

SWITCH 1 CLOSE SEAL-IN: Range: 0.000 to 65.535 s in steps of 0.001


 0.000 s

SWITCH 1 BLK OPEN: Range: FlexLogic operand


 Off

SWITCH 1 BLK CLOSE: Range: FlexLogic operand


 Off

5  SWITCH 1 BLK BYPASS:


Disabled
Range: Disabled, Enabled

SWITCH 1 TAGGING: Range: Disabled, Enable No Override, Enable with


 Disabled Override

SWITCH 1 SUBSTITUTN: Range: Disabled, Enabled


 Disabled

SWITCH 1 EVENTS: Range: Disabled, Enabled


 Disabled

SW1 CILO INTRLK TO LOCAL Range: Disabled, Enabled


 CTRL: Disabled

SW1 CILO INTERLOCK GFP Range: Disabled, Enabled


 BYPASS: Disabled

SWITCH 1 LOCAL: Range: FlexLogic operand


 Off

SW1 BLK MNL CMD IN LOCAL: Range: Disabled, Enabled


 Disabled

SW1 CSWI LOC STAT: Range: FlexLogic operand


 Off

SW1 STATION AUTHOR: Range: FlexLogic operand


 Off

SWITCH 1 OPEN INTERLOCK: Range: FlexLogic operand


 Off

SWITCH 1 CLOSE INTERLOCK: Range: FlexLogic operand


 Off

SWITCH 1 POS-REACHED CHECK: Range: Enabled, Disabled


 Enabled

5-176 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

The disconnect switch control element contains the auxiliary logic for status and serves as the interface for opening and
closing of disconnect switches from SCADA or through the front panel interface. The disconnect switch control element
can be used to create interlocking functionality. For greater security in determination of the switch pole position, both the
89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that open and close the disconnect switch to use FlexLogic operands
SWITCH 1 OFF CMD and SWITCH 1 ON CMD, and configure the disconnect switch control element's inputs as outlined
here.
SW INTERM & BAD ST TIMERS — When set to “Common” the switch element considers both “00” and “11” states of 89/a and
89/b as intermediate state and when the Toperate timer expires, declares the switch as bad status. When set to “Distinct”
the switch element considers “00” state of 89/a and 89/b as intermediate state and “11” as bad status. When the switch
status detected is 00, the switch element waits for Toperate timer to expire before declaring the intermediate state. When
the switch status detected is 11, the switch element waits for Bad ST Tsuppress timer to expire before declaring the bad
state. See the switch logic diagrams 2 and 4.
SWITCH 1 FUNCTION — This setting enables and disables operation of the disconnect switch element.
SWITCH 1 NAME — Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
messages related to disconnect switch 1.
SWITCH 1 MODE — This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
SWTCH 1 ΦA/3P OPND — This setting selects an operand, usually a contact input, that is for a normally-closed 89/b status
input that creates a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an
inverted 89/a status signal can be used.
SWTCH 1 ΦA/3P CLSD — This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
position tracking mechanism. This input is for a normally-open 89/a status input that creates a logic 1 when the
disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole,” this setting selects a single 89/a input as
the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole,” the input
5
mentioned is used to track phase A and the SWITCH 1 ΦB and SWITCH 1 ΦC settings select operands to track phases B and
C, respectively.
SWITCH 1 ΦB OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
SWITCH 1 ΦB CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1 ΦC OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 ΦC CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1 ALARM PDisc DELAY — This setting specifies the delay interval during which a disagreement of status among the
pole position tracking operands do not declare a pole discrepancy. This allows for non-simultaneous operation of the
poles.
SWITCH 1 OPEN CMD — Selects an operand that initiates Switch 1 open command. Open command is not executed when
blocked by the operand assigned to SWITCH 1 BLK OPEN setting.
SW1 COMMS OPEN CMD — Selects an operand that initiates Switch 1 open command. The setting is intended for commands
received via communication protocols (DNP3, IEC104 and Modbus) to be supervised by IED Local/Remote status. The open
command is not executed if the IED is in local mode or blocked by the operand assigned to SWITCH 1 BLK OPEN setting.
SWITCH 1 CLOSE CMD — Selects an operand that initiates Switch 1 close command. Close command is not executed when
blocked by operand assigned to SWITCH 1 BLK CLOSE setting.
SW1 COMMS CLS CMD — Selects an operand that initiates Switch 1 close command. The setting is intended for commands
received via communication protocols (DNP3, IEC104 and Modbus) to be supervised by IED Local/Remote status. The close
command is not executed if the IED is in local mode or blocked by the operand assigned to SWITCH 1 BLK CLOSE setting.
SWITCH 1 PB CONTROL — Local disconnect switch control operations (for example, open/close) are allowed from front panel
pushbuttons when the selected FlexLogic operand value is high.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-177


SYSTEM SETUP CHAPTER 5: SETTINGS

SWITCH 1 TOPERATE — This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic operand is asserted for alarm or blocking purposes.
SWITCH 1 BAD ST TSUPPRESS — When the SW INTERM & BAD ST TIMERS setting is set to “Distinct” this setting specifies the
required interval to overcome the transient state of 11 during the switch operation. If the 11 state still exists after this time,
the SWITCH 1 BAD STATUS FlexLogic operand is asserted. When the SW INTERM & BAD ST TIMERS setting is set to
“Common” this setting is not used.
SWITCH 1 OPEN SEAL-IN — This setting specifies the seal-in time of the open command due to an operator-initiated manual
open command to the disconnect switch.
SWITCH 1 CLOSE SEAL-IN — This setting specifies the seal-in time of the close command due to an operator-initiated manual
close command to the disconnect switch.
SWITCH 1 BLK OPEN — This setting selects an operand that prevents initiation of the disconnect Switch 1 command. This
setting can be used to block the disconnect switch from opening, for instance when switch yard monitoring indicates that
current exceeding the switch's interrupting rating can be flowing through the switch.
SWITCH 1 BLK CLOSE — This setting selects an operand that prevents initiation of disconnect Switch 1 close commands. This
setting can be used to block the disconnect switch from closing, for instance to prevent closing into a closed ground
switch.
SWITCH 1 BLK BYPASS —Set to “Enable” to allow the graphical front panel to bypass switch 1 interlocking. When asserted,
SWITCH 1 BLK OPEN and SWITCH 1 BLK CLOSE settings are bypassed. This setting is available only if the order code includes
GFP.
SWITCH 1 TAGGING — Switch tagging is used to block certain operation when it is tagged for safety purposes. No other
action is needed after enabling the function; it is handled internally where certain functions are blocked.
Set to “Enable No Override” to allow the graphical front panel or IEC 61850 MMS control to tag switch 1. When tagged from
5 the graphical front panel, tagging can be removed only from the graphical front panel, and an attempt to remove tagging
using IEC 61850 MMS control results in a negative response (-Rsp). When tagged using IEC 61850 MMS control, tagging can
be removed only by MMS control.
Set to “Enable With Override” to allow the graphical front panel or IEC 61850 MMS control to tag switch 1. When tagged
from the graphical front panel, tagging can be removed only from the graphical front panel, and an attempt to remove
tagging using IEC 61850 MMS control results in a negative response (-Rsp). When tagged from IEC 61850 MMS control,
tagging can be removed by MMS control or from the graphical front panel. That is, the graphical front panel has an
override function.
When tagged, the following operations are disabled:
• Pushbutton open/close
• IEC 61850 open/close
• Open command initiated by SWITCH 1 OPEN setting
• Close command initiated by SWITCH 1 CLOSE setting
This setting is available only if the order code includes GFP.
SWITCH 1 SUBSTITUTN — Set to “Enable” to allow the graphical front panel to substitute switch 1 status. When substituted,
switch 1 control open/close status is forced to the substituted value. This setting is available only if the order code includes
GFP.
SWITCH 1 LOCAL — Set in the EnerVista software or via SCL file. It selects an operand that indicates the Switch control
behavior from an IEC 61850 client. When the operand value is set, it indicates the Switch in Local mode and the remote
commands from IEC 61850 client are blocked.
SW1 BLK MNL CMD IN LOCAL — When set to “Enabled” and the SWITCH 1 LOCAL operand state is logic “1” (i.e. the Switch is in
Local mode and Disc0XSWI1.Loc is TRUE), manual commands originating from the front panel pushbuttons, graphical front
panel and SWITCH 1 OPEN/CLOSE CMD are blocked. When set to “Disabled”, manual commands originating from relay are
allowed even when the Switch is in Local mode (SWITCH 1 LOCAL operand state is logic “1”). Please refer to the table in the
Control Authority section above for further information on control behavior. This setting is available only if the order code
includes IEC 61850.

5-178 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

SW1 CSWI LOC STAT — Selects an operand, that indicates the switch residing in that bay is in Local or Remote mode. When
the operand state is logic “1”, the bay is considered in Local mode and when the operand state is “0”, the bay is considered
in remote mode. The operand status is modeled in IEC 61850 server using respective Switch CSWI Loc data object and the
user should refer to the operand status in the table in the Control Authority section above to determine the control
authority for different levels. This setting is available only if the order code includes IEC 61850.
SW1 STATION AUTHOR — Selects an operand, that indicates the Station level authority status. The operand status is modeled
in IEC 61850 server using respective breaker’s CSWI LocSta data object and the user should refer to the operand status in
the table in the Control Authority section above to determine the control authority for different levels. This setting is
available only if the order code includes IEC 61850.
SWITCH 1 OPEN INTERLOCK — Selects an operand that indicates the interlock status for the Switch Open commands. This
operand state is mapped directly to the IEC 61850 DiscCILO1.EnaOpn.stVal, which is used to reject the IEC 61850 open
command when the selected operand state is at logic “0” (DiscCILO1.EnaOpn.stVal is set to false). However, the IEC 61850
client can select to check or skip the interlock condition to execute the command using the “Check” parameter in control
command.
Additionally, the interlock condition can be applied to the local commands as well, which can originate from the front local
HMI, front panel push buttons, graphical front panel (GFP) and FlexLogic Operands assigned to SWITCH 1 OPEN CMD setting.
This is achieved by selecting setting SW1 CILO INTRLK TO LOCAL CTRL as “Enabled”. This setting is available only if the order
code includes IEC 61850.
SWITCH 1 INTERLOCK CLOSE — Selects an operand that indicates the interlock status for the Switch Close commands. This
operand state is mapped directly to the IEC 61850 DiscCILO1.EnaCls.stVal, which is used to reject the IEC 61850 close
command when the selected operand state is at logic “0” (DiscCILO1.EnaCls.stVal is set to false). However, the IEC 61850
client can select to check or skip the interlock condition to execute the command using the “Check” parameter in control
command.
Additionally, the interlock condition can be applied to the local commands as well, which can originate from the front local
HMI, front panel push buttons, graphical front panel (GFP) and FlexLogic Operands assigned to SWITCH 1 CLOSE CMD
setting. This is achieved by selecting setting SW1 CILO INTRLK TO LOCAL CTRL as “Enabled”. This setting is available only if the 5
order code includes IEC 61850.
SWITCH 1 POS-REACHED CHECK — Set in the EnerVista software. When “Enabled”, the IEC 61850 control value is checked for
current Switch status and is rejected if the command value (Open/Close) from IEC 61850 client match with the present
Switch status. When “Disabled”, the current Switch status is not verified to accept the control. This setting is only available
if the order code includes IEC 61850.

Before software release version 7.90, ST.LOC OPERAND, INTERLOCK OPN and INTERLOCK CLS settings were available in
IEC 61850 configurator under System Setup > Switches. From version 7.90 onwards, the above mentioned settings
were removed from the IEC 61850 configurator and merged with the Breaker settings screen under Settings >
System Setup > Switches (outside the IEC 61850 configurator). Also, the name of the setting ST.LOC OPERAND has
been changed to LOCAL.
SWITCH 1 LOCAL, INTERLOCK OPEN, INTERLOCK CLOSE and SYNCCHECK CLOSE settings are not available on the front
panel and can be configured either from EnerVista Software or via SCL files. Refer to the MICS document online for
respective settings modeling in SCL files. SWITCH 1 POS-REACHED CHECK is only configurable via EnerVista software
The switch element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagrams. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking open/close commands are provided. Note that
the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain close/open
command for a certain time, do so using the seal-in timers SWITCH 1 OPEN SEAL-IN and SWITCH 1 CLOSE SEAL-IN, on the
contact outputs using the setting, or in FlexLogic.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-179


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-76: Disconnect switch control logic (sheet 1 of 4)


SETTING
SW ITCH 1 FU NCTION
= E nabled

FLEXLOGIC OPERAND
SW ITCH 1 TAG ON

SETTING
SW ITCH 1 PB CONTROL
=Off
AND
SW ITCH 1 Ope n
From graphical front panel

SETTING (on 61850 page ) DiscCSWI1.OpOpn.general


SW ITCH1 LOCAL To IEC 61850 protocol
= Off
AND OR
Disc0XSWI1.Pos.ctlVal = off
OR FLEXLOGIC OPERAND
DiscCSWI1.Pos.ctlVal = off SE TTI NG
AND OR AND SW ITCH 1 OFF CMD
From IEC 61850 protocol SW ITCH 1 OPEN SEAL-IN
T P KP
SETTING 0 AND
SW ITCH 1 OPEN
AND
= Off

AND
DiscCSW I1.BlkOpn.ctlVal = on
OR To IEC 61850 protocol
Disc0XS WI1.BlkOpn.ctlVal = on AND DiscCSWI1.BlkOpn.stVal
From IEC 61850 protocol
SETTING
SW ITCH 1 BLOCK OPEN OR Disc0XSWI1.BlkOpn.stVal
= Off To IEC 61850 protocol

AND
FLEXLOGIC OPERAND
SW ITCH 1 BYPAS S ON
To IEC 61850 protocol
AND DiscCSWI1.CmdBlk.stVal
DiscCSWI1.CmdBlk.ctlVal = on

AND To IEC 61850 protocol

5
SW ITCH 1 Close AND DiscCSWI1.Blk.stVal
From graphical front panel

AND
OR
Disc0XSWI1.Pos.ctlVal = on
OR FLEXLOGIC OPERAND
DiscCSWI1.Pos.ctlVal = on SE TTI NG
AND OR AND SW ITCH 1 ON CMD
From IEC 61850 protocol SW ITCH 1 CLOS E SEAL-IN
T P KP
SETTING 0 AND DiscCSWI1.OpCls.gene ral
SW ITCH 1 CLOS E
AND To IEC 61850 protocol
= Off
From IEC 61850 protocol
AND DiscCSWI1.BlkCls.stVal
DiscCSWI1.BlkCls.ctlVal = on AND
OR
Disc0XS WI1.BlkCls.ctlVal = on
OR Disc0XSWI1.BlkCls.stVal
SETTING To 61850 protocol
SW ITCH 1 BLK CLOSE AND Enable
= Off to shee t 2

CSWI cmd Switch 1


Blk to Local
Sheet 3 to Sheet 3
859828A1.vsdx

5-180 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-77: Disconnect switch control status logic (sheet 2 of 4)


from sheet 1
SETTING Enable
SW INTERM & BAD ST TIM ERS
SETTING = COM MON
SW ITCH 1 M ODE = DIS TINCT to shee t 4
= 1-Pole
= 3-Pole

FLEXLOGIC OPERANDS
SW ITCH 1 SU BD CLSD
SW ITCH 1 SU BD OPEN FLEXLOGIC OPERAND
SW 1 A CLOSED AND SW ITCH 1 ΦA CLS D
SETTING AND
SW ITCH 1 ΦA/3P CLSD FLEXLOGIC OPERAND
OR SW 1 A OPENE D AND SW ITCH 1 ΦA OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
SW ITCH 1 ΦA/3P OPND AND SW ITCH 1 ΦA INTERM
OR AND SETTING
= Off AND
SW ITCH 1 TOPERATE FLEXLOGIC OPERAND
OR
T P KP AND SW ITCH 1 ΦA BAD S T
AND 0

SW 1 B CLOSED FLEXLOGIC OPERAND


AND
AND SW ITCH 1 ΦB CLS D
SETTING
SW ITCH 1 ΦB CLS D FLEXLOGIC OPERAND
OR SW 1 B OPENED AND SW ITCH 1 ΦB OPEN
= Off AND
AND
SETTING
SW ITCH 1 ΦB OP ENE D FLEXLOGIC OPERAND
OR AND AND SW ITCH 1 ΦB INTERM
= Off AND
SETTING
OR FLEXLOGIC OPERAND
SW ITCH 1 TOPERATE
AND AND SW ITCH 1 ΦB BAD S T
T P KP
0

FLEXLOGIC OPERAND
SW 1 C CLOSED AND SW ITCH 1 ΦC CLS D
AND
SETTING
SW ITCH 1 ΦC CLS D FLEXLOGIC OPERAND
OR SW 1 C OPENE D AND SW ITCH 1 ΦC OPEN

5
= Off AND
AND
SETTING
SW ITCH 1 ΦC OPENE D FLEXLOGIC OPERAND
OR AND AND
= Off AND SW ITCH 1 ΦC INTERM
OR SETTING
FLEXLOGIC OPERAND
SW ITCH 1 TOPERATE
AND AND SW ITCH 1 ΦC BAD ST
T P KP
0

When the SW INTERM & BAD ST TIMERS setting is FLEXLOGIC OPERAND


“Common,” switch element uses the logic OR SW ITCH 1 BAD STATUS
highlighted in dashed boxes for SWITCH1 ΦA/ΦB/
ΦC INTERM and BAD ST FlexLogic operands.
FLEXLOGIC OPERAND
AND SW ITCH 1 TROU BLE
OR

AND FLEXLOGIC OPERAND


SW 1 A CLOSED AND SW ITCH 1 CLOS ED
OR
SW 1 B CLOSED
AND
SW 1 C CLOSED SE TTING
FLEXLOGIC OPERAND
SW ITCH 1 ALARM DELAY
AND SW ITCH 1 D ISCREP
T P KP
AND
0

SW 1 A OPENE D
AND FLEXLOGIC OPERAND
SW 1 B OPENED
AND SW ITCH 1 OPEN
SW 1 C OPENE D OR

AND
Enable
to shee t 3 859812A1.vsdx

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-181


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-78: Disconnect switch control graphical front panel logic (sheet 3 of 4)
from sheet 1 from sheet 1
CSWI cmd Switch 1
SETTING Blk LOCAL
SW ITCH 1 TAGG ING
= Enable No Override OR
= Enable with Override
from sheet 2
AND Enable
DiscCSWI1.TagOn.ctlVal=On AND
OR
Disc0XS WI1.TagOn.ctlVal=On Non-volatile,
OR Reset-dominant
SW ITCH 1 Tag S FLEXLOGIC OPERAND
From graphical front panel Latch SW ITCH 1 TAG ON
AND SW ITCH 1 TAG OFF
OR R
OR

AND
SW ITCH 1 Remove Tag
OR
DiscCSWI1.TagOn.ctlVal=Off AND
AND
OR
Disc0XS WI1.TagOn.ctlVal=Off

SETTING
SW ITCH 1 SU BSTITUTN
= E nabled Non-volatile,
Reset-dominant
SW ITCH 1 Substitute Open S FLEXLOGIC OPERAND
Latch SW ITCH 1 SU BD OPEN
SW ITCH 1 Remove Substitution
OR R

SW ITCH 1 Substitute Closed S FLEXLOGIC OPERAND


From graphical front panel Latch SW ITCH 1 SU BD CLSD
OR R

SETTING

5
SW ITCH 1 BYPAS S
= E nabled Non-volatile,
Reset-dominant
SW ITCH 1 Bypass S FLEXLOGIC OPERAND
SW ITCH 1 Remove Bypass Latch SW ITCH 1 BYPAS S ON
From graphical front panel OR R SW ITCH 1 BYPAS S OFF

859829A1.vsdx

Figure 5-79: Disconnect switch control status logic (sheet 4 of 4)


SW INTERM & BAD ST TIM ERS = DIS TI NCT
from sheet 2 1-Pole Enable

SETTING
SW ITCH1 BAD ST TSUPPRESS FLEXLOGIC OPERAND
T P KP AND SW ITCH1 ΦA BAD ST
AND 0

SETTING
SW ITCH1 TOPERATE FLEXLOGIC OPERAND
AND T P KP AND SW ITCH1 ΦA INTERM
0

1-Pole Enable

When the SW INTERM & BAD ST TIMERS


SETTING
setting is “Distinct,” switch element FLEXLOGIC OPERAND
SW ITCH1 BAD ST TSUPPRESS
replaces the sheet 2 highlighted logic in AND SW ITCH1 Φ Θ BAD ST
AND T P KP
dashed box with sheet 4 logic for 0
SWITCH1 ΦA/ΦB/ΦC INTERM and BAD
ST FlexLogic operands SETTING
SW ITCH1 TOPERATE FLEXLOGIC OPERAND
AND T P KP AND SW ITCH1 ΦΘINTERM
0

Where Θ is B and C

859813A1.vsdx

5-182 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

5.5.6 FlexCurves

5.5.6.1 Settings
SETTINGS  SYSTEM SETUP  FLEXCURVES  FLEXCURE A(D)
 FLEXCURVE A FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1
  0.00 xPKP: 0 ms

FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1


 0.05 xPKP: 0 ms

FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1
 20.00xPKP: 0 ms

FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter
a custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE up/down keys) for the required protection curve (A, B, C, or D).

Table 5-19: FlexCurve table


Reset Time Reset Time Operate Time Operate Time Operate Time Operate Time
ms ms ms ms ms ms
0.00 0.68 1.03 2.9 4.9 10.5
0.05 0.70 1.05 3.0 5.0 11.0
0.10 0.72 1.1 3.1 5.1 11.5
0.15 0.74 1.2 3.2 5.2 12.0 5
0.20 0.76 1.3 3.3 5.3 12.5
0.25 0.78 1.4 3.4 5.4 13.0
0.30 0.80 1.5 3.5 5.5 13.5
0.35 0.82 1.6 3.6 5.6 14.0
0.40 0.84 1.7 3.7 5.7 14.5
0.45 0.86 1.8 3.8 5.8 15.0
0.48 0.88 1.9 3.9 5.9 15.5
0.50 0.90 2.0 4.0 6.0 16.0
0.52 0.91 2.1 4.1 6.5 16.5
0.54 0.92 2.2 4.2 7.0 17.0
0.56 0.93 2.3 4.3 7.5 17.5
0.58 0.94 2.4 4.4 8.0 18.0
0.60 0.95 2.5 4.5 8.5 18.5
0.62 0.96 2.6 4.6 9.0 19.0
0.64 0.97 2.7 4.7 9.5 19.5
0.66 0.98 2.8 4.8 10.0 20.0

The relay using a given FlexCurve applies linear approximation for times between the user-entered points. Take
care when setting the two points that are close to the multiple of pickup of 1; that is, 0.98 pu and 1.03 pu. It is
recommended to set the two times to a similar value, otherwise the linear approximation can result in undesired
behavior for the operating quantity that is close to 1.00 pu.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-183


SYSTEM SETUP CHAPTER 5: SETTINGS

5.5.6.2 FlexCurve configuration with EnerVista software


The EnerVista software allows for easy configuration and management of FlexCurves and their associated data points.
Prospective FlexCurves can be configured from a selection of standard curves to provide the best approximate fit, then
specific data points can be edited afterwards. Alternately, curve data can be imported from a specified file (.csv format) by
selecting the EnerVista Import Data From setting (Settings > System Setup > FlexCurves > FlexCurve).
Curves and data can be exported, viewed, and cleared by clicking the appropriate buttons. FlexCurves are customized by
editing the operating time (ms) values at pre-defined per-unit current multiples. Note that the pickup multiples start at zero
(implying the "reset time"), operating time below pickup, and operating time above pickup.

5.5.6.3 Recloser curve editing


Recloser curve selection is special in that recloser curves can be shaped into a composite curve with a minimum response
time and a fixed time above a specified pickup multiples. There are 41 recloser curve types supported. These definite
operating times are useful to coordinate operating times, typically at higher currents and where upstream and
downstream protective devices have different operating characteristics. The recloser curve configuration window shown
here appears when the Initialize From setting in the EnerVista software is set to “Recloser Curve” and the Initialize
FlexCurve button is clicked.
Figure 5-80: Recloser curve initialization

0XOWLSOLHU6FDOHV PXOWLSOLHV WKHFXUYHRSHUDWLQJWLPHV

$GGU$GGVWKHWLPHVSHFLILHGLQWKLVILHOG LQPV WRHDFK


FXUYHRSHUDWLQJWLPHYDOXH

5
0LQLPXP5HVSRQVH7LPH 057 ,IHQDEOHGWKH057VHWWLQJ
GHILQHVWKHVKRUWHVWRSHUDWLQJWLPHHYHQLIWKHFXUYHVXJJHVWV
DVKRUWHUWLPHDWKLJKHUFXUUHQWPXOWLSOHV$FRPSRVLWHRSHUDWLQJ
FKDUDFWHULVWLFLVHIIHFWLYHO\GHILQHG)RUFXUUHQWPXOWLSOHVORZHU
WKDQWKHLQWHUVHFWLRQSRLQWWKHFXUYHGLFWDWHVWKHRSHUDWLQJWLPH
RWKHUZLVHWKH057GRHV$QLQIRUPDWLRQPHVVDJHDSSHDUV
ZKHQDWWHPSWLQJWRDSSO\DQ057VKRUWHUWKDQWKHPLQLPXP
FXUYHWLPH

+LJK&XUUHQW7LPH$OORZVWKHXVHUWRVHWDSLFNXSPXOWLSOH
IURPZKLFKSRLQWRQZDUGVWKHRSHUDWLQJWLPHLVIL[HG7KLVLV
QRUPDOO\RQO\UHTXLUHGDWKLJKHUFXUUHQWOHYHOV7KH+&75DWLR
GHILQHVWKHKLJKFXUUHQWSLFNXSPXOWLSOHWKH+&7GHILQHVWKH
RSHUDWLQJWLPH
($"'"!1!34B

The Multiplier and Adder settings only affect the curve portion of the characteristic and not the MRT and HCT
settings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.

5.5.6.4 Example
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight times pickup with an operating time of 30 ms. At approximately four times pickup, the curve operating
time is equal to the MRT and from then onwards the operating time remains at 200 ms.

5-184 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-81: Composite recloser curve with HCT disabled

($"'!)1!34B

With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup.
Figure 5-82: Composite recloser curve with HCT enabled

($"'" 1!34B

Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If
this is attempted, the EnerVista software generates an error message and discards the proposed changes.

5.5.6.5 Standard recloser curves


The following graphs display standard recloser curves available for the F60.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-185


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-83: Recloser curves GE101 to GE106

 (&




5*.& TFD

(&

(& (&



(& (&




               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"#1!34B

5
Figure 5-84: Recloser curves GE113, GE120, GE138, and GE142



 (&




(&
5*.& TFD

 (&
(&







               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"%1!34B

5-186 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-85: Recloser curves GE134, GE137, GE140, GE151, and GE201






(&
5*.& TFD

(&


(& (&

(&



               


$633&/5 NVMUJQMFPGQJDLVQ
($"'# 1!34B

5
Figure 5-86: Recloser curves GE131, GE141, GE152, and GE200



(&


5*.& TFD

(&


(&


(&


               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"(1!34B

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-187


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-87: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165




(&



5*.& TFD

(&



(&

(&



(&
 (&


               
$633&/5 NVMUJQMFPGQJDLVQ
($"'")1!34B

5 Figure 5-88: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139

(&



5*.& TFD

 (&


(&

(&

(& (&




               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"&1!34B

5-188 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Figure 5-89: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122





(&



5*.& TFD


(&

(&
(&


 (& (&


(&




               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"$1!34B

5
Figure 5-90: Recloser curves GE119, GE135, and GE202




(&

5*.& TFD

(&
 (&




               
$633&/5 NVMUJQMFPGQJDLVQ
($"'"'1!34B

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-189


SYSTEM SETUP CHAPTER 5: SETTINGS

5.5.7 Phasor Measurement Unit

5.5.7.1 Menu
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT
 PHASOR MEASUREMENT  PHASOR MEASUREMENT See below
 UNIT   UNIT 1

 PMU AGGREGATOR 1 See page 5-207


 

 IEC 90-5 MSVCB See page 5-209


  CONFIGURATION

The F60 is provided with an optional Phasor Measurement Unit (PMU) feature, specified as a software option at
the time of ordering. The number of PMUs available depends on the option.

5.5.7.2 Synchrophasor implementation


Phasors are used in protection relays. When these phasors are referenced to a common time base, they are referred to as
synchrophasors. A vastly improved method for tracking power system dynamic phenomena for power system monitoring,
protection, operation, and control can be realized when synchrophasors from different locations within the power system
are networked to a central location.
The F60 offers PMU features over two communication standards, IEC 61850-90-5 and IEEE C37.118. The figure shows

5 complete synchrophasor implementation.


Figure 5-91: Synchrophasor implementation

5.5.7.3 Implementation of IEC 61850-90-5


Synchrophasor data as measured and calculated by PMUs is used to assess the condition of the electrical power network.
The IEEE C37.118 standards define synchrophasors and related message formats to transmit synchrophasor data.
Synchrophasor streaming via IEEE C37.118 has proven to work but the need to have a communication mechanism that is
compliant with the concept of IEC 61850 has led to the development of IEC 61850-90-5. The IEC 61850-90-5 technical
report defines the packet structure for multicast routing of streamed Sampled Value (SV) known as R-SV.

5-190 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

UR firmware versions 7.0 and above have a 90-5 based R-SV implementation equivalent in structure and configuration to
that of the existing IEEE C37.118 implementation of firmware version 6.0, that is, synchrophasor data at rates up to 60 Hz
for metering and 120 Hz for protection class synchrophasors. The following two figures depict the general data flow for the
generation of synchrophasor data for IEC 61850-90-5. In the first figure, when IEC 61850-90-5 is selected all real and
virtual sources are available for the IEC 61850-90-5 PMUs.
The number of PMUs and aggregators vary by product, as outlined in the table.
Table 5-20: PMU implementation by UR device
UR device Number of PMUS Number of aggregators Comment
N60 1, 2, 4, or 6 1 with 1 PMU Number of PMUs is ordered using software options
2 with 2 or 4 PMUs
4 with 6 PMUs
C60, C95 2 2
D60, F60, G60, L30, L90, T60 1 1

The figure shows an example of an N60 using four Logical Device PMUs (Logical Device 2 through 5) and four aggregators.
The control blocks for the aggregators are located in LD1. A 64 character LDName setting is provided.
Figure 5-92: N60 example for four logical device PMUs

Precise time input to the relay from the international time standard, via either IRIG-B or PTP, is vital for correct
synchrophasor measurement and reporting. For IRIG-B, a DC level shift IRIG-B receiver must be used for the PMU to
output proper synchrophasor values.
Depending on the applied filter, the synchrophasors that are produced by PMUs are classified as either P (protection) or M
(Measurement) class synchrophasors. Synchrophasors available within the UR that have no filtering applied are classified
as NONE, which within the standard is classified as PRES OR UNKNOWN under the Calculation Method - ClcMth. Each
Logical Device PMU supports one MxxMMXU, MxxMSQI, PxxxMMXU, PxxxMSQI, NxxMMXU, and one NxxMSQI logical node.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-191


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-93: Logical nodes supported in each logical device

The following is a summary of LNs that are in each Logical Device (LD2 through LD7):
• PxxxMMXU1 ClcMth = P-Class (Note Vaux is mapped to Vneut of MMXU)
• PxxxMSQI1 ClcMth = P-CLASS
• MxxMMXU1 ClcMth = M-Class (Note Vaux is mapped to Vneut of MMXU)
• MxxMSQI1 ClcMth = M-CLASS
• NxxMMXU1 ClcMth = M-Class (Note Vaux is mapped to Vneut of MMXU)

5 •

NxxMSQI1 ClcMth = M-CLASS
GGIO1, which contains 16 digital status indication points and 16 analog points. The Analog GGIO values are selectable
from any FlexAnalog value in the UR.

The Synchro Logical Nodes in an LD report at the same rate as set in the PMUn Basic Configuration setting. This is
reflected in the instantiation of the Data Object – SmpRate in the msvcb## of LLN0 in the LD1. SmpRate is a Read
Only Integer Status (INS).
When the first PMU from any LD is mapped into an aggregator, the aggregator inherits the Sample Rate (SmpRate) and
IEEE C37.118 Class (P or M) of that PMU. The value of the SmpRate DO in the Report Control Block is set based on the value
of the Sample Rate in the PMU. The Class of the Dataset are mapped into the MSVID of the Dataset (see text that follows for
the overall name of the MSVID). If other PMUs are mapped into the same aggregator with different Sample Rates or from
different classes, then a Self-Test error (DatSetErr) is set and dataset transmission is blocked.
A setting value — MSVID — is created with a maximum input range of 56 characters (=64 less 6 for the IDCode less 2 for the
Class).
The value of MSVID in the dataset is a concatenation of the aggregator IDCode and the MSVID setting value in the format:
MSVID-AggregatorIDCode-CLASS where CLASS is P, M, or N (for None) – depending on the Class of the first PMU included in
the Aggregator.

Synchrophasor Rectangular Format and Integer data types are NOT supported in IEC 61850-90-5 (only supported
with IEEE C37.118) and not to set — GGIO1 that contains 16 digital status indication points — aggregated as a 16 bit
bitstring and 16 analog points. The Analog GGIO values are selectable from any FlexAnalog value in the UR. For
firmware versions 7.0 and later, the description fields for the phasors, analog, and digital channels are populated
with the 16 character name field provided within the Basic Configuration menu. Additionally, the names of the 16
binary points are implemented as numbered descriptions — d1, d2, d3, and so on. The number of descriptions are
equal to the number of bits configured in the 16 bit digital status word.
All bitstrings less than or equal to 32 bits in length map into a 32 bit bitstring in an IEC 61850-90-5 dataset.
The Value of the Nominal Frequency of the chassis is instantiated as a DO in LPHD of LD1. The value is named
HzNom and is an Integer Status (INS).

5-192 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

The UR also supports the option to apply no filtering to the synchrophasors. If no filtering is applied (PMU Class = None),
according to the standard, the ClcMth attribute is PRES. The semantic of the ClcMth used is not carried in the individual DO
and so it is recommended that one of letters of the prefix on the instantiated LNs be set to “P” or “M” accordingly in order
to differentiate. For firmware versions 7.0 and later, only FCDA data is supported. The PMU Implementation by UR Device
table earlier indicates the maximum size of each PMU data set for version 7.2 and later using FCDA data (non-structured
data).

5.5.7.4 Example: Protection synchrophasors data set with reporting rate 60 frames/second
This example gives the protection synchrophasors data set with a reporting rate of 60 frames per second (P60MMXU1). See
the figure earlier, Logical Nodes Supported in Each Logical Device. This data or list of items, as shown in the following
figure, is not available to the UR setup program but is available to be mapped by the user into a selected aggregator or
aggregators dataset. The logical device name (LDName) of each PMU LD is a 64 character user setting. The IEEE C37.118
STN and IDCode is to be mapped as a concatenated value in the (d)escription field of LPL CDC of the NamPlt DO in LLN0.
The mapping is implemented as STN-IDCode (text string).
From each PMU, the user selects the phasor information of interest that is mapped into the selected aggregator datset(s).
For version 7.0 and later, only FCDA data is supported.
Figure 5-94: Data set created from user-selected internal items

5.5.7.5 Example: Creation of different data sets


The aggregators allow the aggregation of phasors from multiple PMUs (with the same reporting rate) into a single custom
data set to optimize bandwidth when streaming.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-193


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-95: Example of aggregator data sets

5.5.7.6 Configuration example: CFG-2 based configuration (using IEC 61850-90-5)


The F60 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor
5 devices (for example, P30) without stopping R-SV multicasting, as shown in the following figure. The primary domain
controller (PDC) does not need to use a stop/start data stream command if the UR protocol is set to IEC 61850-90-5 prior to
requesting the configuration via CFG-2 (IEEE C37.118 config. file). The CFG-2 request from the P30 can be on TCP/IP or
UDP/IP, however, R-SV data streaming is only UDP multicasts (not TCP).
Figure 5-96: CFG-2 based configuration solution

5-194 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

5.5.7.7 Modification of SYNC word in CFG-2 for TR 90-5 data sets


In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets).  In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which is set presently to 2) is set as follows:
Value (decimal) Number of ASDUs
 11  1
12 2
 13 3
 14  4

5.5.7.8 Settings
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1
 PHASOR MEASUREMENT  PMU 1 BASIC See below
 UNIT 1   CONFIGURATION

 PMU 1 See page 5-199


  CALIBRATION

 PMU 1 See page 5-200


  TRIGGERING

 PMU 1 See page 5-206


  RECORDING

5.5.7.9 Basic configuration 5


SETTINGS  SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASURMENT UNIT1 
PMU 1 BASIC CONFIGURATION 
 PMU 1 BASIC PMU 1 Range: Enabled, Disabled
 CONFIGURATION  FUNCTION: Disabled

PMU 1 IDCODE: Range: 1 to 65534 in steps of 1


 1

PMU 1 STN: Range: 32-character ASCII string truncated to 16


 GE-UR-PMU characters if mapped into C37.118 Default: GE-UR-PMU

PMU 1 SIGNAL SOURCE: Range: available signal sources


 SRC 1

PMU 1 CLASS: Range: None, M-CLASS, P-CLASS


 M-CLASS

PMU 1 FORMAT: Range: Integer, Floating-point


 Integer

PMU 1 STYLE: Range: Polar, Rectangular


 Polar

PMU 1 RATE: Range: 1, 2, 4, 5, 10, 12, 15,20, 25, 30,50, 60, 100, 120
 10/sec /sec

PMU 1 f & df/dt Range: None, 10Hz/s <10Hz, 10Hz/s <20Hz, 20Hz/s
 FILTER: None <10Hz, 20Hz/s <20Hz

 C37.118 PMU 1 See below


  CONFIGURATION

PMU 1 PHS- 1: Range: available synchrophasor values


 Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-195


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 PHS-14: Range: available synchrophasor values


 Off

PMU 1 PHS- 1: Range: 16-character ASCII string


 NM: GE-UR-PMU-PHS 1

PMU 1 PHS-14: Range: 16-character ASCII string
 NM: GE-UR-PMU-PHS 14

PMU 1 A-CH- 1: Range: available FlexAnalog values


 Off

PMU 1 A-CH-8: Range: available FlexAnalog values
 Off

PMU 1 A-CH- 1: Range: 16-character ASCII string


 NM: AnalogChannel 1

PMU 1 A-CH-8: Range: 16-character ASCII string
 NM: AnalogChannel 8

PMU 1 D-CH- 1: Range: available FlexLogic operands


 Off

PMU 1 D-CH-16: Range: available FlexLogic operands
 Off

5  PMU 1 D-CH- 1
NM: Dig Channel 1
Range: 16-character ASCII string


PMU 1 D-CH-16 Range: 16-character ASCII string
 NM: Dig Channel 16

PMU 1 D-CH- 1 Range: Off, On


 NORMAL STATE: Off

PMU 1 D-CH-16: Range: Off, On
 NORMAL STATE: Off

 90-5 PMU 1 See below


  CONFIGURATION

This section contains basic Phasor Measurement Unit (PMU) data, such as functions, source settings, and names.
PMU 1 FUNCTION — This setting enables the LOGICAL Device PMU 1 functionality. Use this setting to permanently enable or
disable the feature.
PMU 1 IDCODE — This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data,
configuration, header, and command frames of the IEEE C37.118 protocol. The PMU uses this value when sending data,
configuration, and header frames; and it responds to this value when receiving the command frame. This is used when
only data from one PMU is present.
PMU 1 STN — This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the
configuration frame of the IEEE C37.118 protocol. This value is a 16-character ASCII string as per the IEEE C37.118
standard.
PMU 1 SIGNAL SOURCE — This setting specifies one of the available F60 signal sources for processing in the PMU. Any
combination of voltages and currents can be configured as a source. The current channels can be configured as sums of
physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and similar arrangements.
The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and current (A, B, C, and ground)

5-196 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

channels of the source, as well as symmetrical components (0, 1, and 2) of both voltages and currents. When configuring
communication and recording features of the PMU, the user can select, from the above superset, the content to be sent
out or recorded. When one source is selected by one PMU, it cannot be selected by another PMU.
PMU 1 CLASS (Range P, M, None) — This setting selects the synchrophasor class. A reporting rate of 100 or 120 can only be
selected for class P synchrophasors and if the system frequency is 50 or 60 Hz, respectively.
PMU 1 NETWORK REPORTING FORMAT — This setting selects between reporting synchrophasors as 16-bit integer or 32-bit
IEEE floating point numbers. This setting complies with bit-1 of the FORMAT field of the C37.118 configuration frame. Note
that this setting applies to synchrophasors only; the user-selectable FlexAnalog channels are always transmitted as 32-bit
integer values.
PMU 1 NETWORK REPORTING STYLE — This setting selects between reporting synchrophasors in rectangular (real and
imaginary) or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the
C37.118 configuration frame.
PMU 1 RATE — This setting specifies the reporting rate for the network (Ethernet) port. This value applies to all PMU streams
of the device that are assigned to transmit over this aggregator. For a system frequency of 60 Hz (50 Hz), the F60 generates
a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz,
25 Hz, 50 Hz, or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software; and the F60 stops
the transmission of reports. Note that 4 Hz is not allowed for an M-class 50 Hz system.
PMU 1 f & df/dt FILTER — This setting allows applying post-filtering to the frequency and rate-of-change of-frequency to
avoid reporting erroneous values, which can possibly happen during fault, switching, and other system disturbances. For
example, choosing 20Hz/s <10Hz setting ensures that if rate-of-change of-frequency between current reporting instance
and previous one exceeds 20Hz/s or frequency deviation from the nominal frequency exceeds 10Hz, then new frequency
and rate-of-change of-frequency value are invalidated. If this happens, the previous valid value of the frequency is
maintained and rate-of-change of-frequency value is forced to 0 at this reporting instance.
PMU 1 PHS-1 to PMU 1 PHS-14 — These settings specify synchrophasors to be transmitted from the superset of all
synchronized measurements. The table outlines available synchrophasor values.
5
Table 5-21: Synchrophaser settings
Selection Meaning
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current

These settings allow for optimizing the frame size and maximizing transmission channel usage, depending on a given
application. Select “Off” to suppress transmission of a given value.
PMU 1 PHS-1 NM to PMU 1 PHS-14 NM — These settings allow for custom naming of the synchrophasor channels. Sixteen-
character ASCII strings are allowed as in the CHNAM field of the configuration frame. These names are typically based on
station, bus, or breaker names.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-197


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 A-CH-1 to PMU 1 A-CH-16 — These settings specify any analog data measured by the relay to be included as a user-
selectable analog channel of the data frame. Up to eight analog channels can be configured to send any FlexAnalog value
from the relay. Examples include frequency, rate of frequency change, active and reactive power, per phase or three-phase
power, power factor, temperature via RTD inputs, and THD. The configured analog values are sampled concurrently with
the synchrophasor instant and sent as 32-bit floating-point values scaled to Engineering units.
PMU 1 A-CH-1 NM to PMU 1 A-CH-16 NM — These settings allow for custom naming of the analog channels. Sixteen-character
ASCII strings are allowed as in the CHNAM field of the configuration frame.
PMU 1 D-CH-1 to PMU 1 D-CH-16 — These settings specify any digital flag measured by the relay to be included as a user-
selectable digital channel of the data frame. Up to 16 digital channels can be configured to send any FlexLogic operand
from the relay. The configured digital flags are sampled concurrently with the synchrophasor instant. These values are
mapped into a two-byte integer number, with byte 1 LSB corresponding to the digital channel 1 and byte 2 MSB
corresponding to digital channel 16.
PMU 1 D-CH-1 NM to PMU 1 D-CH-16 NM — These settings allow for custom naming of the digital channels. Sixteen-character
ASCII strings are allowed as in the CHNAM field of the configuration frame.
PMU 1 D-CH-1 NORMAL STATE to PMU 1 D-CH-16 NORMAL STATE — These settings allow for specifying a normal state for each
digital channel. These states are transmitted in configuration frames to the data concentrator.

C37.118 PMU 1 configuration


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASURMENT UNIT1  PMU 1 BASIC
CONFIGURATION  C37.118 PMU 1 CONFIGURATION
 C37.118 PMU 1 PMU 1 FORMAT: Range: Integer, Floating-point
 CONFIGURATION  Integer

5  PMU 1 FREQ FORMAT:


Integer
Range: Integer, Floating-point

PMU 1 STYLE: Range: Polar, Rectangular


 Polar

PMU 1 FORMAT — This setting selects whether synchrophasors are reported as 16-bit integers or 32-bit IEEE floating point
numbers. This setting complies with bit-1 of the FORMAT field of the IEEE C37.118 configuration frame. This setting applies
to synchrophasors only; user-selectable FlexAnalog channels are always transmitted as 16-bit integer values.
PMU 1 FREQ FORMAT — This setting selects between reporting frequency and rate-of-change-of-frequency as 16-bit integer
or 32-bit IEEE floating point numbers. This setting complies with bit 3 of the FORMAT field of the C37.118 configuration
frame.
PMU 1 STYLE — This setting selects whether synchrophasors are reported in rectangular (real and imaginary) coordinates or
in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118
configuration frame.

With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850-90-5
technical report.

IEC 61850–90–5 PMU 1 configuration


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASURMENT UNIT1  PMU 1 BASIC
CONFIGURATION  90-5 PMU 1 CONFIGURATION
 90-5 PMU 1 PMU 1 LDINST: Range: 64 char ASCII text
 CONFIGURATION  PMU1

PMU1 LDINST — A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
logical device.

5-198 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64
characters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.

5.5.7.10 PMU calibration


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
CALIBRATION
 PMU 1 PMU 1 VA CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
 CALIBRATION  ANGLE: 0.00°

PMU 1 VA CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 VB CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 VB CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 VC CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 VC CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 VX CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

 PMU 1 VX CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
5
PMU 1 IA CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
 ANGLE: 0.00°

PMU 1 IA CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 IB CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 IB CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 IC CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 IC CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 IG CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 IG CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%


 MAG: 100.0%

PMU 1 SEQ VOLT SHIFT Range: –180 to 180° in steps of 30


 ANGLE: 0°

PMU 1 SEQ CURR SHIFT Range: –180 to 180° in steps of 30


 ANGLE: 0°

This menu contains user angle and magnitude calibration data for the Phasor Measurement Unit (PMU). This data is
combined with the factory adjustments to shift the phasors for better accuracy.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-199


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 VA... IG CALIBRATION ANGLE — These settings recognize applications with protection class voltage and current
sources, and they allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a
positive correction when the secondary signal lags the true signal and a negative value when the secondary signal leads
the true signal.
PMU 1 VA... IG CALIBRATION MAGNITUDE — These settings recognize applications with protection class voltage and current
sources, and they allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs. The setting values are effectively a multiplier of the measured magnitudes. Therefore, entering a
multiplier greater than 100% of the secondary signal increases the true signal, and a multiplier less than 100% value of the
secondary signal reduces the true signal.
PMU 1 SEQ VOLT SHIFT ANGLE — This setting allows correcting positive- and negative-sequence voltages for vector groups of
power transformers located between the PMU voltage point and the reference node. This angle is effectively added to the
positive-sequence voltage angle and subtracted from the negative-sequence voltage angle. Note that:
• When this setting is not “0°”, the phase and sequence voltages do not agree. Unlike sequence voltages, the phase
voltages cannot be corrected in a general case and therefore are reported as measured.
• When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
• This setting applies to PMU data only. The F60 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
• When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
PMU 1 SEQ CURR SHIFT ANGLE — This setting allows correcting positive and negative-sequence currents for vector groups of
power transformers located between the PMU current point and the reference node. The setting has the same meaning for
5 currents as the PMU 1 SEQ VOLT SHIFT ANGLE setting has for voltages. Normally, the two correcting angles are set identically,
except rare applications when the voltage and current measuring points are located at different windings of a power
transformer.

5.5.7.11 PMU triggering overview


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING
 PMU 1  PMU 1 USER See below
 TRIGGERING   TRIGGER

 PMU 1 FREQUENCY See page 5-201


  TRIGGER

 PMU 1 VOLTAGE See page 5-202


  TRIGGER

 PMU 1 CURRENT See page 5-203


  TRIGGER

 PMU 1 POWER See page 5-204


  TRIGGER

 PMU 1 df/dt See page 5-205


  TRIGGER

Each Phasor Measurement Unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated PMU
recorder, or cross-triggering of other PMUs in the system. They are
• Overfrequency and underfrequency
• Overvoltage and undervoltage
• Overcurrent
• Overpower
• High rate of change of frequency

5-200 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

The pre-configured triggers can be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
Figure 5-97: STAT bits logic
6(77,1*
8VHU7ULJJHU
2II 

)/(;/2*,&23(5$1'6 )/(;/2*,&23(5$1'
308)5(475,**(5 25 ELWELW 30875,**(5('
25 ELW
30852&2)75,**(5
30892/775,**(5
25 ELW
308&85575,**(5 308UHFRUGHU
30832:(575,**(5 ELW
$&'5

The trigger reset (drop-off) timer is available for all five triggering functions (FREQ, ROCOF, VOLT, CURR, POWER) in individual
trigger settings under the TRIGGER DPO TIME setting. This asserts individual trigger operand and overall PMU x
TRIGGERED operand with stat bits 3 and 11 for a fixed interval defined by this setting. If it is required that PMU x
TRIGGERED operand with stat bits 3 and 11 stay longer than the individual reset timer, then use the PMU x USER TRIGGER
setting assigned with appropriate elements and FlexLogic. In short, in case of USER TRIGGER, the drop-off time needs to be
implemented using FlexLogic.

5.5.7.12 User triggering 5


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 USER TRIGGER
 PMU 1 USER PMU 1 USER TRIGGER: Range: FlexLogic operand
 TRIGGER  Off

The user trigger allows customized triggering logic to be constructed from FlexLogic. The entire triggering logic is refreshed
every two power system cycles.

5.5.7.13 Frequency triggering


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 FREQUENCY TRIGGER
 PMU 1 FREQUENCY PMU 1 FREQ TRIGGER Range: Enabled, Disabled
 TRIGGER  FUNCTION: Disabled

PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01


 LOW-FREQ: 49.00 Hz

PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01


 HIGH-FREQ: 61.00 Hz

PMU 1 FREQ TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 PKP TIME: 0.10 s

PMU 1 FREQ TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 DPO TIME: 1.00 s

PMU 1 FREQ TRIG BLK: Range: FlexLogic operand


 Off

PMU 1 FREQ TRIGGER Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-201


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 FREQ TRIGGER Range: Enabled, Disabled


 EVENTS: Disabled

The trigger responds to the frequency signal of the Phasor Measurement Unit (PMU) source. The frequency is calculated
from among phase voltages, auxiliary voltage, phase currents, and ground current, in this hierarchy, depending on the
source configuration as per F60 standards. This element requires that the frequency be above the minimum measurable
value. If the frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
PMU 1 FREQ TRIGGER LOW-FREQ — Specifies the low threshold for the abnormal frequency trigger. The comparator applies a
0.02 Hz hysteresis.
PMU 1 FREQ TRIGGER HIGH-FREQ — Specifies the high threshold for the abnormal frequency trigger. The comparator applies
a 0.02 Hz hysteresis.
PMU 1 FREQ TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.
PMU 1 FREQ TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is of importance
when using the recorder in the forced mode (recording as long as the triggering condition is asserted).
Figure 5-98: Frequency trigger logic
FLEXLOGIC OPERANDS
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER

SETTINGS PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND

OR
PMU 1 TRIGGERED
PMU 1 FREQ TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND

PMU 1 FREQ TRIG BLK:


Off = 0
SETTINGS
to STAT bits of

5 SETTING

PMU 1 SIGNAL
SOURCE:
PMU 1 FREQ TRIGGER LOW-FREQ:
PMU 1 FREQ TRIGGER HIGH-FREQ:
RUN
0< f < LOW-FREQ
SETTINGS
PMU 1 FREQ TRIGGER PKP TIME:

tPKP
SETTINGS
PMU 1 FREQ TRIGGER DPO TIME:

0
the data frame

FLEXLOGIC OPERAND

OR PMU 1 FREQ TRIGGER


FREQUENCY, f f > HIGH-FREQ tDPO
0
847008A1.CDR

5.5.7.14 Voltage triggering


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 VOLTAGE TRIGGER
 PMU 1 VOLTAGE PMU 1 VOLT TRIGGER Range: Enabled, Disabled
 TRIGGER  FUNCTION: Disabled

PMU 1 VOLT TRIGGER Range: 0.250 to 1.250 pu in steps of 0.001


 LOW-VOLT: 0.800 pu

PMU 1 VOLT TRIGGER Range: 0.750 to 1.750 pu in steps of 0.001


 HIGH-VOLT: 1.200 pu

PMU 1 VOLT TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 PKP TIME: 0.10 s

PMU 1 VOLT TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 DPO TIME: 1.00 s

PMU 1 VOLT TRIG BLK: Range: FlexLogic operand


 Off

PMU 1 VOLT TRIGGER Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PMU 1 VOLT TRIGGER Range: Enabled, Disabled


 EVENTS: Disabled

5-202 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

This element responds to abnormal voltage. Separate thresholds are provided for low and high voltage. In terms of
signaling its operation, the element does not differentiate between the undervoltage and overvoltage events. The trigger
responds to the phase voltage signal of the Phasor Measurement Unit (PMU) source. All voltage channels (A, B, and C or AB,
BC, and CA) are processed independently and can trigger the recorder. A minimum voltage supervision of 0.1 pu is
implemented to prevent pickup on a de-energized circuit, similarly to the undervoltage protection element.
PMU 1 VOLT TRIGGER LOW-VOLT — Specifies the low threshold for the abnormal voltage trigger, in per-unit of the PMU
source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The comparator applies a
1% hysteresis.
PMU 1 VOLT TRIGGER HIGH-VOLT — Specifies the high threshold for the abnormal voltage trigger, in per-unit of the PMU
source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The comparator applies a
1% hysteresis.
PMU 1 VOLT TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.
PMU 1 VOLT TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is of importance
when using the recorder in the forced mode (recording as long as the triggering condition is asserted).
Figure 5-99: Voltage trigger logic
FLEXLOGIC OPERANDS
SETTINGS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER PMU 1 CURR TRIGGER
FUNCTION:
PMU 1 POWER TRIGGER
Enabled = 1
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
AND

PMU 1 VOLT TRIG BLK:

OR
PMU 1 TRIGGERED
Off = 0 SETTING

SETTINGS PMU 1 USER TRIGGER:


SETTINGS PMU 1 VOLT TRIGGER LOW-VOLT: Off = 0

PMU 1 SIGNAL PMU 1 VOLT TRIGGER HIGH-VOLT:


SOURCE:
RUN
VT CONNECTION: SETTINGS to STAT bits of

5
(0.1pu < V < LOW-VOLT) OR SETTINGS
the data frame
WYE DELTA (V > HIGH-VOLT) PMU 1 FREQ TRIGGER PKP TIME: PMU 1 VOLT TRIGGER DPO TIME:
VA VAB (0.1pu < V < LOW-VOLT) OR FLEXLOGIC OPERAND
OR

(V > HIGH-VOLT) tPKP 0


VB VBC PMU 1 VOLT TRIGGER
(0.1pu < V < LOW-VOLT) OR
VC VCA (V > HIGH-VOLT) 0 tDPO
847009A1.CDR

5.5.7.15 Current triggering


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 CURRENT TRIGGER
 PMU 1 CURRENT PMU 1 CURR TRIGGER Range: Enabled, Disabled
 TRIGGER  FUNCTION: Disabled

PMU 1 CURR TRIGGER Range: 0.100 to 30.000 pu in steps of 0.001


 PICKUP: 1.800 pu

PMU 1 CURR TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 PKP TIME: 0.10 s

PMU 1 CURR TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 DPO TIME: 1.00 s

PMU 1 CURR TRIG BLK: Range: FlexLogic operand


 Off

PMU 1 CURR TRIGGER Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PMU 1 CURR TRIGGER Range: Enabled, Disabled


 EVENTS: Disabled

This element responds to elevated current. The trigger responds to the phase current signal of the Phasor Measurement
Unit (PMU) source. All current channel (A, B, and C) are processed independently and can trigger the recorder.
PMU 1 CURR TRIGGER PICKUP — Specifies the pickup threshold for the overcurrent trigger, in per unit of the PMU source. A
value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
PMU 1 CURR TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-203


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 CURR TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is of
importance when using the recorder in the forced mode (recording as long as the triggering condition is asserted).
Figure 5-100: Current trigger logic
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
SETTINGS
PMU 1 POWER TRIGGER
PMU 1 CURR TRIGGER
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
FUNCTION:

OR
PMU 1 TRIGGERED
Enabled = 1 SETTING
AND

PMU 1 CURR TRIG BLK: PMU 1 USER TRIGGER:


Off = 0 Off = 0

SETTINGS
SETTINGS
PMU 1 CURR TRIGGER PICKUP:
PMU 1 SIGNAL SETTINGS SETTINGS
to STAT bits of
RUN the data frame
SOURCE: PMU 1 CURR TRIGGER PKP TIME: PMU 1 CURR TRIGGER DPO TIME:
IA I > PICKUP FLEXLOGIC OPERAND
tPKP 0

OR
IB I > PICKUP PMU 1 CURR TRIGGER
IC I > PICKUP 0 tDPO
847010A1.CDR

5.5.7.16 Power triggering


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 POWER TRIGGER
 PMU 1 POWER PMU 1 POWER TRIGGER Range: Enabled, Disabled
 TRIGGER  FUNCTION: Disabled

PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001


 ACTIVE: 1.250 pu

5  PMU 1 POWER TRIGGER


REACTIVE: 1.250 pu
Range: 0.250 to 3.000 pu in steps of 0.001

PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001


 APPARENT: 1.250 pu

PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 PKP TIME: 0.10 s

PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 DPO TIME: 1.00 s

PMU 1 PWR TRIG BLK: Range: FlexLogic operand


 Off

PMU 1 POWER TRIGGER Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PMU 1 POWER TRIGGER Range: Enabled, Disabled


 EVENTS: Disabled

This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation, the element does not differentiate among the three types of power. The trigger responds
to the single-phase and three-phase power signals of the Phasor Measurement Unit (PMU) source.
PMU 1 POWER TRIGGER ACTIVE — Specifies the pickup threshold for the active power of the source. For single-phase power,
1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the
nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.
PMU 1 POWER TRIGGER REACTIVE — Specifies the pickup threshold for the reactive power of the source. For single-phase
power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and
the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.

5-204 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

PMU 1 POWER TRIGGER APPARENT — Specifies the pickup threshold for the apparent power of the source. For single-phase
power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and
the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.
PMU 1 POWER TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.
PMU 1 POWER TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is of
particular importance when using the recorder in the forced mode (recording as long as the triggering condition is
asserted).
Figure 5-101: Power trigger logic

6(77,1*6

30832:(5
75,**(5)81&7,21 )/(;/2*,&23(5$1'6
(QDEOHG  308)5(475,**(5
$1'

3083:575,*%/. 30892/775,**(5
6(77,1*6
2II  308&85575,**(5
30832:(575,**(5$&7,9(
30852&2)75,**(5 )/(;/2*,&23(5$1'
30832:(575,**(55($&7,9(

25
30875,**(5('
30832:(575,**(5$33$5(17 6(77,1*
6(77,1*6
581 30886(575,**(5
3086,*1$/6285&(
2II 
$&7,9(32:(53$ DEV 3 !$&7,9(3,&.83
$&7,9(32:(53% DEV 3 !$&7,9(3,&.83
$&7,9(32:(53& DEV 3 !$&7,9(3,&.83 WR67$7ELWVRI
6(77,1*6 6(77,1*6 WKHGDWDIUDPH
3$&7,9(32:(53 DEV 3 ! $&7,9(3,&.83
30832:(575,**(53.37,0( 30832:(575,**(5'327,0(
5($&7,9(32:(54$ DEV 4 !5($&7,9(3,&.83
)/(;/2*,&23(5$1'
5($&7,9(32:(54% DEV 4 !5($&7,9(3,&.83 W3.3 
25

30832:(575,**(5
5($&7,9(32:(54& DEV 4 !5($&7,9(3,&.83
 W'32
35($&7,9(32:(54 DEV 4 ! 5($&7,9(3,&.83
$33$5(1732:(56$ 6!$33$5(173,&.83
$33$5(1732:(56% 6!$33$5(173,&.83
$33$5(1732:(56& 6!$33$5(173,&.83
3$33$5(1732:(56 6! $33$5(173,&.83
$&'5
5
5.5.7.17 df/dt triggering
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1
TRIGGERING  PMU 1 df/dt TRIGGER
 PMU 1 df/dt PMU 1 df/dt TRIGGER Range: Enabled, Disabled
 TRIGGER  FUNCTION: Disabled

PMU 1 df/dt TRIGGER Range: 0.10 to 15.00 Hz/s in steps of 0.01


 RAISE: 0.25 Hz/s

PMU 1 df/dt TRIGGER Range: 0.10 to 15.00 Hz/s in steps of 0.01


 FALL: 0.25 Hz/s

PMU 1 df/dt TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 PKP TIME: 0.10 s

PMU 1 df/dt TRIGGER Range: 0.00 to 600.00 s in steps of 0.01


 DPO TIME: 1.00 s

PMU 1 df/dt TRG BLK: Range: FlexLogic operand


 Off

PMU 1 df/dt TRIGGER Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PMU 1 df/dt TRIGGER Range: Enabled, Disabled


 EVENTS: Disabled

This element responds to frequency rate of change. Separate thresholds are provided for rising and dropping frequency.
The trigger responds to the rate of change of frequency (df/dt) of the Phasor Measurement Unit (PMU) source.
PMU 1 df/dt TRIGGER RAISE — Specifies the pickup threshold for the rate of change of frequency in the raising direction
(positive df/dt). The comparator applies a 4% hysteresis.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-205


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU 1 df/dt TRIGGER FALL — Specifies the pickup threshold for the rate of change of frequency in the falling direction
(negative df/dt). The comparator applies a 4% hysteresis.
PMU 1 df/dt TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.
PMU 1 df/dt TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is of importance
when using the recorder in the forced mode (recording as long as the triggering condition is asserted).
Figure 5-102: Rate of change of frequency trigger logic
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER

SETTINGS PMU 1 POWER TRIGGER FLEXLOGIC OPERAND

OR
PMU 1 TRIGGERED
PMU 1 df/dt TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND

PMU 1 df/dt TRG BLK:


Off = 0
SETTINGS SETTINGS
to STAT bits of
PMU 1 df/dt TRIGGER RAISE: PMU 1 df/dt TRIGGER PKP TIME: the data frame
SETTING
PMU 1 df/dt TRIGGER FALL: PMU 1 df/dt TRIGGER DPO TIME:
PMU 1 SIGNAL FLEXLOGIC OPERAND
RUN
SOURCE: df/dt > RAISE tPKP
OR PMU 1 ROCOF TRIGGER
ROCOF, df/dt –df/dt > FALL tDPO
847000A1.CDR

5 5.5.7.18 PMU recording


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  RECORDING
PMU 1
 PMU 1 PMU 1 FUNCTION: Range: Enabled, Disabled
 RECORDING  Disabled

PMU 1 NO OF TIMED Range: 2 to 128 in steps of 1


 RECORDS: 10

PMU 1 TRIGGER MODE: Range: Automatic Overwrite, Protected


 Automatic Overwrite

PMU 1 TIMED TRIGGER Range: 1 to 50% in steps of 1


 POSITION: 10%

The length of the PMU record is variable and depends on some settings and configuration, such as PMU 1 NO OF TIMED
RECORDS, PMU 1 RATE, number of Synchrophasors, Analogs and Digitals configured in each PMU. There is a fixed amount of
data storage for PMU recording; the more records captured, the less the recording length captured per record. See the
ACTUAL VALUES  RECORDS  PMU RECORDS  PMU 1 RECORDING menu to view the actual PMU record length captured per
record. The following table provides sample configurations with corresponding seconds per record. The minimum number
of PMU records is two. The third to fifth columns is the number of configured values recorded in each record.
Table 5-22: PMU record length example
Records Frames per Synchrophasors Analogs Digitals Record length
second (seconds)
3 30 14 8 16 590.4
16 30 14 8 16 138.9
32 30 14 8 16 71.5
64 30 14 8 16 36.3
3 60 14 8 16 295.2
16 60 14 8 16 69.4

5-206 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

Records Frames per Synchrophasors Analogs Digitals Record length


second (seconds)
32 60 14 8 16 35.7
64 60 14 8 16 18.1

PMU 1 FUNCTION — This setting enables or disables the recorder for PMU 1. The rate is fixed at the reporting rate set within
the aggregator (that is, Aggregator 1).
PMU 1 NO OF TIMED RECORDS — Specifies the number of timed records that are available for a given logical PMU 1. The
length of each record is equal to the available memory divided by the content size and number of records. As the number
of records is increased, the available storage for each record is reduced. The relay supports a maximum of 128 records in
either timed or forced mode.
PMU 1 TRIGGER MODE — Specifies what happens when the recorder uses its entire available memory storage. With
“Automatic Overwrite,” the last record is erased to facilitate new recording, when triggered. Under the “Protected”
selection, the recorder stops creating new records when the entire memory is used up by the old uncleared records.
PMU 1 TIMED TRIGGER POSITION — Specifies the amount of pre-trigger data as a percent of the entire record. This setting
applies only to the timed mode of recording.

5.5.7.19 Aggregator
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1
 PMU AGGREGATOR 1 PMU AGGREGATOR 1 Range: NONE, 37.118, 90-5
  PROTOCOL: NONE

PMU AGGREGATOR 1 Range: 1 to 65534 in steps of 1


 IDCODE: 1

 PMU AGGREGATOR 1 Range: No, Yes 5


INCLUDE PMU1: No

 C37.118 AGGR 1 See below


  CONFIGURATION

 90-5 AGGR 1 See below


  CONFIGURATION

When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None are
set to the last protocol saved (that is, IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118 and
IEC 61850-90-5 simultaneous streaming is not possible.
PMU AGGREGATOR1 PROTOCOL — Selects if the IEEE C37.118 or IEC 61850-90-5 technical report is used. Because one
protocol is supported at a time in a device, this setting applies to all PMU aggregators.
PMU AGGREGATOR1 IDCODE — Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output stream, this
identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggregator.
PMU AGGREGATOR1 PMU1 — If set to “Yes,” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 does not include PMU1 data set in the report if set to “No.”

Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.

SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1  C37.118 AGGR 1
CONFIGURATION
 C37.118 AGGR 1 PMU AGGREGATOR 1 Range: 0 to 65534
 CONFIGURATION  TCP PORT: 4712

PMU AGGREGATOR 1: Range: 0 to 65534


 UDP PORT: 4713

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-207


SYSTEM SETUP CHAPTER 5: SETTINGS

PMU AGGREGATOR 1: Range: Disabled, Enabled


 PDC CONTROL: Disabled

PMU AGGREGATOR 1 TCP PORT — Selects the TCP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 UDP PORT — Selects the UDP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 PDC CONTROL — The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first word
of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator supports 16 FlexLogic
operands, as shown in the table. The operands are asserted for five seconds following reception of the command frame. If
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
Table 5-23: FlexLogic operands supported by aggregator
Operand type Operand syntax Operand description
ELEMENT: AGTR1 PDC CNTRL 1 Phasor data concentrator asserts control bit 1, as
Synchrophasor, phasor data, received via the network
concentrator
as above AGTR1 PDC CNTRL 2 Phasor data concentrator asserts control bit 2 as
received via the network
as above AGTR1 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as
received via the network

5 as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as
received via the network
as above AGTR2 PDC CNTRL 1 Phasor data concentrator asserts control bit 1 as
received via the network
as above AGTR2 PDC CNTRL 2 Phasor data concentrator asserts control bit 2 as
received via the network
as above AGTR2 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as
received via the network

as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as
received via the network

SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1  90-5 AGGR 1
CONFIGURATION
 90-5 AGGR 1 PMU AGGREGATOR 1 Range: 56-character ASCII text (blank by default)
 CONFIGURATION  NAME:

PMU AGGREGATOR 1 Range: 1, 2, 3


 PORT: 1

PMU AGGREGATOR 1 Range: 0 to 65534 in steps of 1


 UDP PORT: 102

PMU AGGREGATOR 1 Range: 1 to 4


 NUMBER OF ASDUs: 1

PMU AGGREGATOR 1 NAME — A user-defined visible string of characters (maximum 56) to identify the source of the stream.
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT — This setting determines the physical ports through which the synchrophasor traffic is
transmitted. The range is 1, 2, 3.

5-208 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SYSTEM SETUP

PMU AGGREGATOR 1: UDP PORT — This setting selects the UDP port number that is used by this dataset for network reporting.
A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR 1: NUMBER OF ASDUs — This setting sets the number of Application Service Data Units (ASDUs) from 1
through to 4.
Table 5-24: Number of ASDUs
Settings for Transmission
ASDU
1 ASDU at T0 (current values)
2 ASDU at T-1 (previous values) + ASDU at T0 (current values)
3 ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4 ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)

5.5.7.20 Control blocks


SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  90–5 R-SV CB 1 CONFIGURATION
 90-5 R-SV CB 1 R-SV CB1 SVENA: Range: FlexLogic operand
 CONFIGURATION  Off

R-SV CB1 CLIENT CTRL: Range: FlexLogic operand


 Off

R-SV CB1 SVENA DFLT: Range: FlexLogic operand


 Off

R-SV CB1 CONFREV: Range: 1 to 4294967295


 1

R-SV CB1 PRIORITY: Range: 0 to 7


5
 4

R-SV CB1 CSCP CLASS: Range: None, Expedited Forwarding


 Expedited Forwarding

R-SV CB1 VLAN ID: Range: 0 to 4095


 0

R-SV CB1 APPID: Range: 0 to 16383


 0

R-SV CB1 DEST IP: Range: 0 to 255.255.255.255


 224.0.0.0

R-SV CB1 SECURITY: Range: 0 to 2


 0

R-SV CB1 SVENA — The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where “1”= Enabled and “0”=Disabled. The figure shows the logic for setting the SvEna control bit.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-209


SYSTEM SETUP CHAPTER 5: SETTINGS

Figure 5-103: Logic for setting SvEna control bit

Toggle Function

SvEna
Status Write “0”
AND to SvEna

Pushbutton/ Positive
FlexOperand One-Shot
(Momentary)

Write “1”
AND
to SvEna

859739A1.cdr

R-SV CB1 CLIENT CONTRL — This setting determines if a client can write to the reserve bit. When the assigned FlexLogic
operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. When the FlexLogic operand
is a logic 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative response with
the appropriate Service Error is returned to the client.
5 R-SV CB1 SVENA DFLT — This setting sets the default state of the stream (On or Off) on power-up or restart.
R-SV CB1 CONFREV — The relay increments the Configuration revision every time the configuration is changed. This setting
allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
R-SV CB1 PRIORITY — A value from 0 through 7. The default value is 4.
R-SV CB1 DSCP CLASS — The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when supported in
the routers.
R-SV CB1 VLAN ID — A range of values limited from 0 to 4095.
R-SV CB1 APPID — This setting allows the selection of a specific application ID for each sending device.
R-SV CB1 DEST IP — This is the destination multicast IP address that is entered in Standard IPV4 address format. The valid
range for IPv4 is from 224.0.0.0 to 239.255.255.255. The UR does not test the address entered.
R-SV CB1 SECURITY — This setting selects the level of security and authentication used, as outlined in the following table,
and is in the form of an enumeration as per standard. The range is 0 to 2.

Shaded settings in the table are not supported in firmware 7.0.

Table 5-25: Security


Enumeration Authentication Encryption
0 No No
1 Yes No
2 Yes Yes

5-210 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

5.6 Process Bus Module


This feature requires a Process Bus Module (order code 85, 86, or 87).
Process Bus GOOSE requires IEC 61850 and IEEE 1588 software options.

The UR provides a digital process bus by use of a Process Bus Module. A digital process bus enables digital transmission of
data between the switchyard and relays in a control house using communication cables instead of hard-wired
connections.
The Process Bus Module supports the IEC 61850-9-2LE and IEC 61869 protocols, switched networks, and two redundancy
protocols (Parallel Redundancy Protocol and High-Availability Seamless Redundancy). The module is used to transfer data
streams in protection and control networks, including dataset samples referred to as sampled values (SVs), with the
stability of redundancy.
A Process Bus Module with order code 85, 86, or 87 is distinct from the HardFiber Process Bus Module with order code 81.
This section does not apply to the HardFiber module.
Configuration includes that for redundancy and synchronization of time-clock sources because data transfer occurs
among multiple devices.

For any device that is connected to a copper SFP of the Process Bus Module, set its port speed to Auto Negotiate.
The copper SFP supports 100 Mbps and 1 Gbps speeds in auto-negotiate mode. If the device connecting to the
Process Bus Module has a fixed port speed, does not support auto-negotiation, or its auto-negotiate is disabled,
then the link speed of the copper SFP is fixed at 1 Gbps and it communicates only with a device that supports 1
Gbps.
5
5.6.1 Parallel Redundancy Protocol (PRP)
PRP enables seamless switchover and zero recovery time during a single network failure in substation automation
networks. It ensures that critical data, such as GOOSE and sampled value (SV) data, are transmitted without delay in case
of local area network (LAN) defects. In other words, with PRP functionality, the Process Bus Module can be connected to
redundant LANs and work with zero recovery time.
PRP is supported to the IEC 62439-3:2012 standard, Clause 4.
The figure shows that PRP achieves redundancy by using a combination of frame and LAN duplication. Identical frames,
here labeled frames A and B, are sent on two independent networks that connect source and destination. The frames carry
GOOSE or supervisory data. Under normal circumstances, both frames reach the destination and one of them is sent up
the stack to the destination application, while the other frame is discarded. If an error occurs in one of the networks and
traffic is prevented from flowing on that path, connectivity is provided by the other network to ensure continuous
communication. When designing this network care was taken to ensure that there is no single point of failure in the two
LANs, such as a common power supply, as such scenarios can bring down simultaneously both LANs.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-211


PROCESS BUS MODULE CHAPTER 5: SETTINGS

Figure 5-104: PRP redundant network example

RedBox Gateway
SAN

LAN A LAN B

Bridges / switches Bridges / switches


Merging
Units

A-frame B-frame
B-frame A-frame
1a 1b

1b 1a

5 UR DANP (Source) UR DANP (Destination) 859778A1.ppt

PRP implements redundancy in the nodes rather than in the network by using specialized nodes called Doubly Attached
Nodes Running PRP (DANP) for handling the duplicated frames. The figure shows an example. Each DANP node has two
ports that are connected to the two independent LANs with similar (but not necessarily identical) topology. A source DANP
sends identical frames over both LANs and a destination DANP receives both frames from the two LANs within a certain
time period, consumes the first frame, and discards the duplicate frame.
Each UR device in this example implements PRP on ports 1a and 1b of the Process Bus Module. Both URs require a Process
Bus Module. Ports 1a and 1b act as DANP in the PRP network. With two ports required, Process Bus Modules with order
code 85, 86, or 87 can be used. While this example shows a UR as receiving the frames, the receiver can be a merging unit
or UR.
A device with only one port, such as a printer or computer, is called a Singly Attached Node (SAN). It is a node with non-
redundant network adapters. A SAN can communicate with other SANs and DANPs on the same LAN. When a SAN is
attached to a redundant LAN by a Redundancy Box (RedBox) device, the SAN can communicate with all DANPs and SANs
in both LANs. In other words, if redundancy for a SAN is required, the SAN is connected to both LANs through a RedBox.
A merging unit (MU), such as the GE MU320, is an interface between analog and digital worlds. With an MU, the analog
signals from the CTs and VTs in the yard are converted to digital signals and transmitted via the sampled value (SV)
network communication protocol.
The bridges shown are network switches that connect devices participating in the PRP network and otherwise do not have
an active role in PRP.

5.6.2 High-availability seamless redundancy (HSR)


Similar to PRP, High-Availability Seamless Redundancy (HSR) enables seamless switchover and zero recovery time during a
single network failure in substation automation networks. It ensures that critical data, such as GOOSE and SV data, are
transmitted without delay in case of LAN defects.
HSR is supported to IEC 62439-3, Clause 5. SV data can be received from merging units meeting IEC 61869-9.

5-212 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

HSR is used in network topology with rings and rings of rings. All nodes in the ring are doubly attached. The figure shows an
example. The Doubly Attached Node with HSR (DANH) is a node that has two ports interconnected by full-duplex links and
participates in the HSR ring. The source node receives a frame from its upper layer, inserts an HSR tag to identify
duplicates, and sends it over its two ports in different directions, shown by the red and blue arrows. In a normal, fault-free
state, the identical frames reach the destination DANH within a certain interval, the destination DANH removes the HSR
tag, sends the first frame up the stack to the destination application and discards the second frame. If an error occurs in
one of the network nodes and traffic cannot flow on that path, connectivity is provided through the other direction and
ensures continuous communication.
Figure 5-105: HSR single-ring configuration example

UR DANH (Source) UR DANH


SAN

1a 1b 1b 1a

UR DANH (Destination)
RedBox
5

Merging Unit Merging Unit Merging Unit


859776A1.ppt

A Singly Attached Node, or SAN, such as a computer or printer, is a node with non-redundant network adapters. It uses a
redundancy box (RedBox) to connect to the ring.
A merging unit (MU), such as the GE MU320, is an interface between analog and digital worlds. With an MU, the analog
signals from the CTs and VTs in the yard are converted to digital signals and transmitted via the sampled value (SV)
network communication protocol.
A UR with the Process Bus Module implements either single or dual HSR capability. It supports hierarchical ring topologies,
such as connected rings, mesh topology, and an HSR ring in a PRP network.
In single HSR configuration, ports 1a and 1b of the Process Bus Module act as DANH, and any other ports on the Process
Bus Module are disabled. Point-to-point configuration is not available. For single HSR, Process Bus Module 85, 86, or 87 can
be used.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-213


PROCESS BUS MODULE CHAPTER 5: SETTINGS

In dual HSR configuration, the UR to connect to two independent HSR rings. Ports 1a and 1b form one DANH node, and
ports 3a and 3b form the second DANH node. Any other ports on the module are disabled. Traffic from HSR-1 ring is not
forwarded to the HSR-2 ring and vice versa. The UR does not facilitate any message communication between the two
independent HSR rings. In dual HSR, with four ports required, a Process Bus Module with order code 86 or 87 can be used.
While the UR does not provide RedBox functionality, an HSR ring can be connected to a PRP network using two RedBoxes,
one for each redundant LAN of the PRP network. The RedBoxes are configured to handle PRP frames on the interlinks and
HSR frames on the HSR ring. As per the IEC 62439-3:2016 standard, up to seven PRP networks can be connected to the
same HSR ring.
While the UR does not provide QuadBox functionality, a QuadBox can be added to interconnect two HSR rings, which is
beneficial when traffic on a single ring exceeds the ring’s capability.
Figure 5-106: Dual HSR, double-ring configuration example

UR DANH (Source)

1a 3a
1b 3b
HSR Ring 1 HSR Ring 2

HSR 1 Nodes HSR 2 Nodes

UR DANH UR DANH

Merging Unit Merging Unit


859777A1.ppt

5.6.3 General
SETTINGS  PROCESS BUS MODULE  GENERAL
 GENERAL NETWORK CONFIG: Range: INDEPENDENT, PRP, HSR, Dual HSR
  INDEPENDENT

PRP SUPV MCST ADDR: Range: 01 15 4E 00 01 00 to 01 15 4E 00 01 FF


 01154E000100

HSR-1 SUPV MCST ADDR: Range: 01 15 4E 00 01 00 to 01 15 4E 00 01 FF


 01154E000100

HSR-2 SUPV MCST ADDR: Range: 01 15 4E 00 01 00 to 01 15 4E 00 01 FF


 01154E000101

5-214 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

PORT 1a FUNCTION: Range: Disabled, Enabled


 Enabled

PORT 4b FUNCTION: Range: Disabled, Enabled
 Enabled

SV TRBL PRT BLOCK: Range: Global, Partial


 Global

SV TRBL CONT OP BLK: Range: FlexLogic operand


 Off

SV DELAY ALARM: Range: 1.0 ms to 10.0 ms in steps of 0.1 ms


 6.0 ms

QUALITY CHECK: Range: Reject Questionable, Accept Questionable


 Reject Questionable

ANTI-ALIASING FILTER: Range: Disabled, Enabled


 Disabled

SMPSYNCH CHECK: Range: Global, Local, Local-87L, Any


 Global

TARGET: Click to view or Range: List of available Targets. Access in EnerVista.


 edit selected Targets

EVENTS: Click to view or Range: List of available FlexLogic operand types


 edit selected Events from SV Stream Processing. Access in EnerVista.

Restart the relay after changing these settings, under Maintenance > Reboot Relay Command.
NETWORK CONFIG — This setting specifies the network configuration and redundancy for the Process Bus Module. 5
If set to INDEPENDENT, all ports on the Process Bus Module are enabled, and the Process Bus Module can be connected
directly to merging units (MUs) or to a switch without redundancy. To enable and disable individual ports on the Process
Bus Module in a point-to-point (PPP) network, use the PORT x FUNCTION settings.
If set to PRP or HSR, ports 1a and 1b are enabled. The PORT 1a FUNCTION and PORT 1b FUNCTION settings change.
If set to Dual HSR, ports 1a and 1b are enabled for one HSR ring, and when using a Process Bus Module with order codes
86 or 87 then ports 3a and 3b are enabled for another HSR ring. The PORT x FUNCTION settings change.
PRP SUPV MCST ADDR — This setting changes the multicast address used by the Parallel Redundancy Protocol (PRP)
supervision frames. Configure all DANP devices in the PRP network with the same multicast address for the network
supervision to operate properly. This setting is editable when the NETWORK CONFIG setting is set to PRP.
HSR-1 SUPV MCST ADDR — This setting changes the multicast address used by High-Availability Seamless Redundancy ring
one (HSR-1 ports 1a and 1b) supervision frames, for single HSR configuration. Configure all DANH devices in the HSR
network with the same multicast address for the network supervision to operate properly. This setting is editable when the
NETWORK CONFIG setting is set to HSR or Dual HSR.
HSR-2 SUPV MCST ADDR — This setting changes the multicast address used by the HSR-2 (ports 3a and 3b) supervision
frames for the second DANH in a Dual HSR configuration. Configure all DANH devices in the HSR network with the same
multicast address for the network supervision to operate properly. This setting is editable when the NETWORK CONFIG
setting is set to Dual HSR.
PORT 1a to 4b FUNCTION — These settings manually enable and disable Process Bus Module Ethernet ports. Typically,
Process Bus Module ports are order-code dependent, and the INDEPENDENT network configuration enables all the ports
by default, changing the settings shown here. These settings allow individual ports to be enabled and disabled. For
example, to connect only a few of the ports, other ports can be disabled to avoid a PBEthPort-# Offline self-test error.
The fields active depend on order code and NETWORK CONFIG setting. For order code 85, ports 1a, 1b, 3a, and 3b are
available to be turned on or off. For order codes 86 and 87, all eight ports can be available to be turned on or off.
When a port is disabled, all transmitting and receiving traffic on the port is blocked.
Relay restart is not required when changing these port function fields.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-215


PROCESS BUS MODULE CHAPTER 5: SETTINGS

SV TRBL PRT BLOCK — In case of loss of any subscribed SV streams or due to bad quality of any subscribed SV frames, the
protection functions of the relay need to be blocked to avoid undesired operation. This setting specifies the type of
blocking applied.
When set to Global, all the protection functions that utilize the sampled values are blocked. Communications, data logging,
and oscillography remain functional. Availability of switchgear control is determined by the SV TRBL CONT OP BLK operand.
When set to Partial, only those protection functions are blocked that utilize the sampled values from the affected SV
stream. All other protection functions remain operational. Communications, data logging, and oscillography remain
functional. Availability of switchgear control is determined by the SV TRBL CONT OP BLK operand.
SV TRBL CONT OP BLK — Selects a FlexLogic operand that determines if the contact outputs are blocked or not. When the
state of the operand is low, the contact outputs are not blocked when there is a loss of any SV stream or received SV
frames have bad quality. The user can execute control action, thus, enabling switchgear control through contact outputs
during SV stream trouble.
When the operand is high, the contact outputs are blocked when there is a loss of any SV stream or received SV frames
have bad quality. The switchgear control is not available through contact outputs during SV stream trouble.
SV DELAY ALARM — The sampled value (SV) frames can arrive with a delay from the MUs, which can be due to the MU
performance or different network path delays. This setting specifies the maximum delay expected between the time a
sample is taken at the MU and the time of arrival of that SV message, where sampling time is estimated based on the UR
Process Bus Module clock and the sampling rate. If the calculated frame delay is more than this setting value, the RxSV#
Delay Alm On FlexLogic operand asserts. The setting value needs to be calibrated and set at the commissioning time for
the given network topology. An alarm in runtime indicates the network performance is degrading over the time. In short,
this setting specifies how long the UR waits to declare that a sample is delayed. Protection is not blocked by this setting.
QUALITY CHECK — Flags are used to assess quality of sampled value data to ensure protection. This setting specifies how
the sampled values are processed by the UR when the associated q.validity is set to Questionable. Quality is checked per
5 AC bank, not per SV stream.
When set to Reject Questionable, the questionable data is treated the same as Invalid and the frame is rejected. Only Good
quality data is accepted.
Set it to Accept Questionable only if it is absolutely known that questionable quality from a MU is not compromising the
quality of the data for various applications. When set to Accept Questionable, the Good and Questionable quality data are
accepted.
ANTI-ALIASING FILTER — This setting activates or deactivates the anti-aliasing filter, which conditions the sampled values
from the Process Bus network.
If Merging Unit providing sampled values is applying anti-aliasing filter, then this setting has to be set to Disabled.
Otherwise, it can be set to Enabled to apply filtering for the received sampled values. When Enabled, the device applies a
low-pass-filter attenuating all the harmonics above the 15th order harmonics. Refer the Product Specifications chapter for
measurement accuracy for the higher harmonics.
SMPSYNCH CHECK — This setting is a time synchronization check. It specifies the time synchronization source of an SV
stream (SmpSynch attribute value in an SV message header) expected by the UR Process Bus Module.
When set to “Global”, only the SV streams with SmpSynch indicating a Global (2) value are accepted. A stream with a
SmpSynch value other than Global (2) is rejected.
When set to “Local” or “Local-87L”, all SV streams with SmpSynch indicating a Local (1) or Global (2) area clock are
accepted.
When set to “Any”, any SmpSynch value in the range of 0 to 254 is acceptable (0 to 127 for UR 7.80), and streams outside
the range are rejected.
TARGET — This setting is available in the EnerVista software, where the user can select the target messages of the affected
SV stream(s) to be displayed on the front panel. The target gets self-reset once the issue with the SV stream is resolved.
Note that a selected target message applies to all the configured SV streams. For example, if target message 'RxSV DELAY
ALM ON' is selected, then a target displays when any of the configured SV streams has an active SV Delay Alarm. When set
to Disabled, no target message displays on the front panel.

5-216 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

Figure 5-107: FlexLogic operand target selection

5
EVENTS — This setting is available in the EnerVista software, where user can select the flexlogic operands which will
generate the events of the affected SV stream(s), to be recorded in the event recorder. Note that a selected event from the
menu applies to all the configured SV streams. When set to Disabled, no event is recorded in the event recorder.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-217


PROCESS BUS MODULE CHAPTER 5: SETTINGS

Figure 5-108: FlexLogic operand event selection

5
Choose carefully the events to be recorded in the event recorder. If an SV stream is noisy, there is risk of event
recorder overflow. Apart from testing, select a minimal number of events following relay commissioning.

5.6.4 SV Stream Config


The UR platform can subscribe up to eight sampled value (SV) streams. Up to six banks and up to six sources can be used
for protection.
Reception of a sampled value (RxSV) can be enabled in the IEC 61850-9-2LE or IEC 61869-9/13 format.
These settings are available in the software only. They also can be configured in the software using a CID file.
The path is Settings > Process Bus Module > SV Stream Config. If a message displays that the data cannot be opened, it
can mean that access timed out; try again.

5-218 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

Figure 5-109: Example of sampled values configuration

The configuration window is explained as follows:


• The four areas of the window (Common Setting, RxSV Streams, Advanced Config, AC Banks, and Sources) collapse and
expand by clicking their buttons
• A column collapses and expands by clicking its heading
• The Show Enabled button toggles active/configured content
• The Show Custom Layout button toggles changes made to formatting, such as column width. Such changes can be
made with or without the button active, and they are retained when the panel is closed.
• There are up to eight RxSV, eight AC Bank, and six Source columns. A B30 can have up to 24 RxSV, 30 AC Bank (24 CT
and six VT), and 30 Source columns.
• With IEC 61869-9, the Advanced Config fields populate and are read-only when importing a file
• Rules are enforced and the configuration cannot be saved until the rules are followed. For example, Neutral Origin 1
and Neutral Origin 2 cannot be mapped to the same SV stream. See the troubleshooting section that follows.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-219


PROCESS BUS MODULE CHAPTER 5: SETTINGS

• The window is configured based on the separate areas and not based on columns. For example, stream RxSV1 is
configured in the SV Messages area of the window, not the first column in the entire window. Or for example, Source1
in the first column can be configured to use AC Bank B2 in the second column.
• The following example shows that Source1 at the bottom of the window is set to map to AC Bank B2, which is mapped
to the first stream (RxSV1) and its available VT1 phase voltage and VT2 neutral voltage.
Figure 5-110: Understanding SV configuration

• The UR allows switching AC banks (essentially streams) from the main measuring MU to the alternate measuring MU.
Once an operand assigned to the SWITCH ALT CT/VT setting is logical "1," the input data to this source is switched from
the banks assigned to PHASE CT/GROUND CT to the banks assigned to ALT PHASE CT/ALT GROUND CT settings for
current transformers. This is similar for voltage transformers.
• Banks assigned to the same function for the main and alternate input data have to have the same CT and VT
nominals and connections, otherwise a warning is generated and switching functionality is prohibited. For example,
banks assigned to the PHASE CT and ALT PHASE CT have to have same primary and secondary CT values.
• During switching from the main CT/VT input data to alternate input data and vice versa, all relay functions are blocked
for two power cycles and metering data does not update
• See the Source Switching section under SETTINGS > SYSTEM SETUP > SIGNAL SOURCES in this manual for application
examples of AC bank switching

5-220 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

An example of the configuration process is as follows:


1. Configure SV streams by importing an MU CID file. This populates the SV Messages area of the window.
2. Configure the Sources fields.
3. Map the AC Bank fields to the RxSV Stream fields.
4. Troubleshoot using the messages displayed during configuration and/or upon save so that the rules are followed.
Saving frequently during configuration helps to deal with issues early.
5. Restart the relay for the changes to take effect.
The table outlines mapping examples using CT channels. VT channels are similar.
Table 5-26: CT configuration mapping examples
Scenario AC Bank configuration Advanced Config configuration
No CT signal in the SV stream --- ---
One neutral Neutral Origin 1 = RxSV1-CT1/NTR CT1-N maps to AC1
Two neutrals Neutral Origin 1 = RxSV1-CT1/NTR CT1-N maps to AC1
Neutral Origin 2 = RxSV2-CT2/NTR CT2-N maps to AC2
Three phases Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C map to AC1, 2, 3
Three phases followed by one neutral Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C, N map to AC1, 2, 3, 4
Neutral Origin 1 = RxSV1-CT1/NTR
One neutral followed by three phases Neutral Origin 1 = RxSV1-CT1/NTR CT1-N maps to AC1
Phase Origin 1 = RxSV1-CT2/PHS CT2-A, B, C map to AC2, 3, 4
One neutral followed by three phases, then Neutral Origin 1 = RxSV1-CT1/NTR CT1-N maps to AC1
followed by one neutral Phase Origin 1 = RxSV1-CT2/PHS CT2-A, B, C, N map to AC2, 3, 4, 5
Neutral Origin 2 = RxSV2-CT2/NTR
Three phases followed by one neutral, then
another neutral
Phase Origin 1 = RxSV1-CT1/PHS
Neutral Origin 1 = RxSV1-CT1/NTR
CT1-A, B, C, N map to AC1, 2, 3, 4
CT2-N maps to AC5 5
Neutral Origin 2 = RxSV2-CT2/NTR
Two three-phases Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C map to AC1, 2, 3
Phase Origin 2 = RxSV2-CT2/PHS CT2-A, B, C map to AC4, 5, 6
Three phases followed by one neutral, then Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C, N map to AC1, 2, 3, 4
another three phases Neutral Origin 1 = RxSV1-CT1/NTR CT2-A, B, C map to AC5, 6, 7
Phase Origin 2 = RxSV2-CT2/PHS
Three phases followed by another three phases, Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C map to AC1, 2, 3
then one neutral Phase Origin 2 = RxSV2-CT2/PHS CT2-A, B, C, N map to AC4, 5, 6, 7
Neutral Origin 2 = RxSV2-CT2/NTR
Three phases, one neutral, then another three Phase Origin 1 = RxSV1-CT1/PHS CT1-A, B, C, N map to AC1, 2, 3, 4
phases and one neutral. Neutral Origin 1 = RxSV1-CT1/NTR CT2-A, B, C, N map to AC5, 6, 7, 8
See the following figure. Phase Origin 2 = RxSV2-CT2/PHS
Neutral Origin 2 = RxSV2-CT2/NTR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-221


PROCESS BUS MODULE CHAPTER 5: SETTINGS

Figure 5-111: Example three phases, one neutral, then three phases and one neutral

5.6.4.1 Logic
The logic diagram follows.

5-222 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

Figure 5-112: SV stream logic diagram


FLEXLOGIC OPERAND
Dlyd Processing Off

FLEXLOGIC OPERAND
RxSV# D elay Alm Off

FLEXLOGIC OPERAND
SE TTINGS
RxSV# SimBit Off
SV Delay Alarm:
Accept Sim SV
FLEXLOGIC OPERAND
SmpSynch Check:
RxSV# SynChk OK
Test M ode Function
From other SV
Quality Check
streams
(|PM Clock – estimate d OR FLEXLOGI C OPERAND
Sampling time|)>S VD elay 4 samp Dlyd Processing On
Alarm duration+1.2PP 1/8 cyc
(|PM Clock – estimate d FLEXLOGIC OPERAND
Sampling time|) > SV De lay 4 samp RxSV# D elay Alm On
alarm duration 1/8 cyc
Sim bit == TRUE && FLEXLOGI C OPERAND
“Accept Sim GOOS E&SV” 4 samp RxSV# SimBit On
== Enabled 1/8 cyc
SV# Time Sync source FLEXLOGI C OPERAND
SETTING doesn’t match SmpSynch 4 samp RxSV# SynChk Fail
Che ck 1/8 cyc
svID
“xxxx” (not null) Analog#.q.validity == FLEXLOGIC OPERAND
Invalid 4 samp
1/8 cyc RxSV# QualChk OK
SETTING
Analog# q.validity ==
Dst MAC quest. && Quality Check = 4 samp FLEXLOGIC OPERAND
OR
Reject Quest. 1/8 cyc
01-0C-CD-04-YY-YY RxSV# QualChk Fail
= Analog# q.test == set &&
Test M ode Function == 4 samp
SETTING FLEXLOGIC OPERAND
Disabled 1/8 cyc
ConfRev RxSV# Lost Off
No frame received for
“Z” time > (SV Delay alarm 2 cyc
= AND duration+1.2PP) FLEXLOGIC OPERAND
2 cyc
RxSV# Lost On
SETTING

5
SV Stream FLEXLOGIC OPERAND
= OR RxSV# Off
svID
Dst MAC
ConfRev
Sim Bit FLEXLOGI C OPERAND
SmpCnt RxSV# On
MU X
SmpSync (Align frames
Analog1 (instM ag.i) using
time stamp) + Success = 0 FLEXLOGIC OPERAND
Analog1 (q)
Quality Check + OR SV# Proce ssing Fail
...
SimBit Che ck + Fail = 1
…. Advance d Miss
Analog16 (instMag.i) Sample FLEXLOGIC OPERAND
Analog16 (q) Algorithm
SV# Proce ssing OK
* Note: RxSV# SimBit On and RxS V# SynChk Fail and RxSV#
QualChk Fail re se t (i.e . drop out) whe n RxSV# Lost On
operand is asserted (no frame received for 2 cycles)
859834A1.vsdx

SV streams are accepted based on the following settings that need to match the MU:
• SmpSynch Check — Time synchronization check as outlined earlier in the General section
• Quality Check — Outlined earlier
• svID — Multicast Sampled Value Identification of a stream
• Dst MAC — Destination Media Access Control address in the header of the SV message
• ConfRev — When the configuration revision is non-zero, the UR accepts the frame when it matches its configured
value

The relay decodes an SV stream when the DstMAC attribute of the injected SV stream matches any of the
configured SV stream subscriptions.

Each qualified SV stream (that is, with matching svID, Dst MAC, and ConfRev) that is mapped to any of the AC Banks is
checked for the SV delay, matching Sim bit, time synchronization source, and quality checks.
When four samples in 1/8th of power cycle duration fail any of these checks, a corresponding FlexLogic operand is
asserted, with a drop-out timer of one protection pass. The drop-out timer is retriggered each time that the check fails.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-223


PROCESS BUS MODULE CHAPTER 5: SETTINGS

The RxSV# Lost FlexLogic operand is set when consecutive 160 samples (two cycles) are lost following the assertion of SV
DELAY ALARM. The time accuracy for the assertion of this operand can be up to two protection passes.
The RxSV# Off FlexLogic operand is set when the "Miss Sample Algorithm" fails (for example, due to temporary loss of
stream or stream rejected due to any condition check failure) or the stream is lost, with a drop-out time of 17 protection
passes. Every "Miss Sample Algorithm" fail condition for that RxSV# stream retriggers the drop-out timer for the RxSV# Off
operand.

5.6.4.2 Message troubleshooting


Examples for messages displayed are as follows:
• The SvID attribute of RxSV1 is empty — Type a name for the stream in the svID field
• The number of channels being selected for CT2-N...exceed the total allowable 7 CT channels — Set the CT2-N field to
None, or increase the CT Channels field to 8
• The number of channels being selected for CT inputs...exceeds the total allowable 4 CT channels — The CT Channels
field is set at 4 and there are entries in the CT2-A/B/C/N fields. Set the latter fields to None or increase the number of
channels.
• The selected ’RxSV3’ stream is disabled. Configure stream before assigning to AC Bank Phase Origin — Enable the
RxSV3 stream in its SV Stream field
• The AC Bank 2 assigned to Source 1 is not configured — B2 is set in a Source1 field at the bottom of the window. In the
AC BANKS area of the window, go to the B2 column, and set one of the fields.
• The AC Bank 2 is a Voltage channel and is assigned to Phase CT of Source 1 — In the Source area of the window,
change the B2 assignment from Phase CT to VT
• The AC Bank x assigned...is not configured.., — Configure the AC Banks section in the software window before setting
the field
5 • The CT channels set of the selected ’RxSV1-CT1’ are not configured — In the Advanced Config section, set the CT fields

5.6.4.3 SV quality processing


• Any degradation in the measurement or sampled value data of the merging unit inhibits the protection functions of
the IED. IEC 61850 assigns quality attributes to each sampled value channel, to identify the data validity. The UR
Process Bus Module interface uses the quality flags of subscribed analog channels to enable or inhibit the protection
functions
• Quality is checked per channel in an ASDU/frame. For example, if A-phase current has invalid quality, but other current
channels have good quality, the frames with good quality are still accepted and values are displayed in the metering.
However, if any channel in the AC Bank has invalid quality, protection functions using this AC bank are blocked until all
four channels have good quality.
• For protection functions to work correctly, q.validity needs to be good. Samples with invalid quality can result in
unacceptable behavior from the protection functions. An SV analog quantity with q.validity = invalid is ignored.
• When “Quality Check” is set to 'Accept questionable' data, the data with q.validity = questionable is valid. When
“Quality Check” is set to 'Reject questionable' data, the data with q.validity = questionable is ignored.
• When the relay is in-service, or test function is Disabled, the data with q.test set to TRUE is processed as invalid
• When the relay test function is forced or isolated, the data with q.test set to TRUE and q.test set to FALSE is valid.
• If any channel value within a sampled value stream is rejected due to a quality check, the device sets a FlexLogic
operand “RxSV# QualChk Fail” for the duration of the quality check failure.

5.6.4.4 SV simulation processing


When received SV frames have Sim Bit TRUE, the frame is ignored unless the value of @Master/LPHD1.Sim.stVal is true
(@Master/LPHD1.Sim.stVal is true when Settings > Simulation > Subscribe to Simulated Values > Simulation Mode is
Enabled). When @Master/LPHD1.Sim.stVal is TRUE
• Once subscribed SV messages with simulation bit TRUE are accepted, subscribed SV messages with simulation bit
FALSE are ignored and the received SV messages with the simulation bit TRUE are used in place of the actual SV
messages until @Master/LPHD1.Sim.stVal is set to FALSE

5-224 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

• When a SV frame is received with simulation bit TRUE, the FlexLogic operand for the corresponding stream is set as
RxSV# SimBit On. After the latest change in simulation bit as recorded by the "Latest Sim Bit Change" time stamp, the
relay takes 4 to 8 msec to process and assert the RxSV# SimBit On FlexLogic operand.
• If SV messages with simulation bit TRUE are not received, the RxSv# continues to use the actual SV frames
• When the value of @Master/LPHD1.Sim.stVal changes from TRUE to FALSE
– Subscribed SV messages with simulation bit TRUE are ignored immediately after this change
– Only subscribed SV messages with simulation bit FALSE are accepted

5.6.4.5 Settings
The following settings are available.
RxSV Format
Range: IEC 61850-9-2LE r2-1, IEC 61869-9 ed1.0
Default: IEC 61850-9-2LE r2-1
This setting selects the SV frame format, or protocol.
When set to “IEC 61850-9-2LE r2-1”, the IED assumes that the received SV frame references datasets that comply with
IEC 61850-9-2LE, Table 6: Dataset (PhsMeas1). The IED must be configured with a system frequency of 50 or 60 Hz for
correct operation.
When set to “IEC 61869-9 ed1.0”, the IED assumes that the dataset rules comply with IEC 61869-9 ed1.0 and that the
number of Application-layer Service Data Units (ASDUs) are user-configurable.

When a file using a single SV stream (either IEC 61850-9-2LE r2-1 or IEC 61869-9 ed1.0) is converted from firmware
version 8.2x and below to firmware versions 8.3x and above, the conversion will complete with no errors and the
RxSV Format setting will have the same value as the original file. 5
If there is a mix of SV streams in the original file, then the user will be notified of this error and all configured SV
streams will be set to the SV Stream default; “Disabled”. The RxSV Format setting will also default to “IEC 61850-9-2LE
r2-1”.
SV Stream
Range: Disabled, Enabled
Default: Disabled
This setting enables an SV stream. When set to “Disabled”, all other RxSV# settings are not editable and set to default.
svID
Range: 1 up to 129 Visible String characters
Default: empty string
svID refers to the name of the sampled value packet. The svID field of incoming SV messages must exactly match this
value for the message to be accepted as a valid RxSV# message. The svID field of the sampled value frame must be
unique within the system/substation.
Dst MAC
Range: any valid multicast MAC (12-digit hexadecimal number)
Default: 01-0C-CD-04-00-00
Only received SV messages having a destination Media Access Control (MAC) address equal to this value are accepted as
valid RxSV# messages. Each address must be unique.
The destination MAC increases the overall performance of multicast message reception by filtering only the configured
messages for processing. For a received SV message, the Dst MAC is validated if it matches with any of the configured
RxSV# Dst MAC. If validation is successful, the message is forwarded for further checks. There is no explicit check for the
configured Dst MAC versus the SvID for a received SV message.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-225


PROCESS BUS MODULE CHAPTER 5: SETTINGS

ConfRev
Range: 0 to 2147483647 in steps of 1
Default: 0
ConfRev refers to configuration revision, which is a count of configuration changes in the SV control block. If the value
entered here is non-zero, the ConfRev field of incoming SV messages must match this value for the message to be
accepted as a valid RxSV# message. If the setting is zero, RxSV# does not check the value received in the ConfRev field.
Stream Status
This is an LED status indicator for the reception of an SV stream (RxSV#).
A green LED reflects the RxSV# On FlexLogic operand, meaning that the SV stream is online.
A red LED reflects the RxSV# Off FlexLogic operand, meaning that the SV stream is offline.
When the EnerVista UR Setup software is not online or the stream is disabled, the LED is greyed-out with Not Available,
or "-NA-" status.

Advanced Configuration
Click the button to display or hide the fields.
These are settings to import an MU CID file and/or support IEC 61869-9 based SV streams, as per Table 902 on Standard
sample rates. IEC 61869-9 allows flexibility on numbers of current and voltage channels. It can be in one of these
sequences: A, B, C, N or A, AB, B, BC, C, CA, N. The UR supports up to eight CT channels and up to eight VT channels and
one or two ASDUs for protection applications. The following settings are active when the SV Stream field is set to IEC
61869-9, and they also depend on the MU Variant Code.
MU SCL Import

5 Use this feature to configure SV streams by importing an MU CID file. The setting file comparison with IEC 61869-9-2LE
configuration is not available. The IEC 61850 Merge feature with IEC 61869-9-2LE is not available.
Upon clicking the Import button and selecting a .cid file, a window appears from which to select the stream to import.
Figure 5-113: Selecting a stream to import from a merging unit CID file

Rules for accepting a CID file include


• The same remote channel cannot be mapped to more than one AC bank channel
• An AC bank channel cannot be mapped to more than one remote channel
• For each AC bank, there are three phase inputs from the same SV control block and all three inputs are configured
• Phase 1 and Phase 2 inputs are not from the same SV control block
• Phase 1 and Phase 2 aux inputs are not from the same SV control block
• A configured Phase consumes three analog channels and Aux consumes one analog channel, with a maximum of 24
channels

5-226 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

SvCBRef
Range: 0 up to 129 alphanumeric, underscore, slash, and period characters, beginning with an alpha character
Default: empty string
This field is read-only. When imported, the MU SCL file populates this field. The value is an ObjectReference to the
publishing control block in the format:
<LDName>/LLN0.<SvCBName>
where <LDName> is the function-related name, if any, of the logical device containing the publishing control block,
otherwise the product-related name of that logical device, and <SvCBName> is the name of the publishing control block.
When RxSV# is configured manually, the field is empty.
CT Channels
Range: 0 to 8
Default: 4
This setting specifies the number of CT channels available in the subscribed RxSV# message from the publisher MU. The
CT-1 fields reflect the number selected here. The number of current quantities matches the number specified by the
Variant Code of the MU.
Typically, a CT channel includes four current channels (three phase-ground currents and one ground/neutral/earth
current). A current channel is the combination of the current sample value attribute (AmpSv.instMag.i) and the
subsequent quality attribute (AmpSv.q).
If CT Channels is 4, CT1-A/B/C/N are supported for the stream.
If CT Channels is 8, CT2-A/B/C/N also are supported for the stream.
If CT Channels is 0, no CT channels display for AC input selection.
This setting is read-only and fixed at 4 when an SV Stream is set to IEC 61850-9-2LE.
If a message displays that "the number of channels being selected for CT inputs...exceeds the total allowable 4 CT 5
channels," it means that the CT Channels field is set at 4 and there are entries in the CT2-A/B/C/N fields. Set the latter
fields to None or increase the number of channels.
VT Channels
Range: 0 to 8
Default: 4
This setting specifies the number of VT channels in the subscribed RxSV# message from the publisher MU. Typically, VT
channels include four voltage channels (three phase-ground voltages and auxiliary voltage). This setting specifies the
number of voltage channels in the subscribed RxSV# message. The voltage channel is the combination of voltage
sample value attribute (VolSv.instMag.i) and the corresponding quality attribute (VolSv.q). The VT-1 fields reflect the
number selected here. The number of voltage quantities matches the number specified by the Variant Code of the
dataset.
If VT Channels is 4, VT1-A/B/C/N are supported for the stream.
If VT Channels is 8, VT2-A/B/C/ also are supported for the stream.
If VT Channels is 0, no VT channels display for AC input selection.
This setting is read-only and fixed at 4 when an SV Stream is set to IEC 61850-9-2LE.
If a message displays that "the number of channels being selected for VI inputs...exceeds the total allowable 2 VT
channels," it means that the VT Channels field is set at 2 and there are more than two entries in the VT1-A/B/C/N fields.
The number of configured VT1 fields needs to match the VT Channels field.
ASDUs
Range: 1, 2
Default: 1
This setting specifies the number of Application-layer Service Data Units (ASDUs) concatenated in one Application
Protocol Data Unit (APDU) in the subscribed RxSV# message. When concatenating several ASDUs into one frame, the
ASDU with the oldest samples is the first one in the frame.
This setting is read-only and set at the default when an SV Stream is set to IEC 61850-9-2LE.
Recycle power to the relay when changing this setting.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-227


PROCESS BUS MODULE CHAPTER 5: SETTINGS

Variant Code
The EnerVista software auto-populates the Variant Code for the RxSV# message based on the settings Sample Rate, the
number of ASDUs, the number of CT Channels, and the number of VT Channels configured.
For example, F4800S2I8U0 describes sampled values with 4800 samples per second, two ASDU (samples) per message,
8 currents, and no voltages.
As another example, F4800S1I8U4 means sampled values with 4800 samples per second, 1 ASDU per message, 8 CT
channels, and 4 VT channels.
This field is read-only as per IEC 61869-9: 2016, Clause-6.903.2.
The number of samples (sample rate) in the variant code is set based on the SETTINGS  SYSTEM SETUP  POWER
SYSTEM  NOMINAL FREQUENCY setting. This value displays 4000 Hz for 50 Hz nominal frequency. This value displays
4800 Hz for 60 Hz nominal frequency or any other nominal frequency except 50 Hz. IEC 61869-9 suggests the 4800 Hz
sample rate for general measuring and protective applications, regardless of the power system frequency.
CT1-A/B/C
Range: None, AC1 to AC16
Default: AC1/AC2/AC3
This setting specifies the sequence of Analog Channel (per phase) that is mapped to the CT-1 of the corresponding
stream. An origin to CT Phase input defines the physical measurement input to the CT bank by mapping specific AC
inputs from that merging unit (or SV message).
The fields are active when the SV Stream field is set to IEC 61869-9. The CT1 phases are available if the number of CT
Channels is 4 or below. CT2 is added if CT Channels is 5 or higher.
The fields are set to the defaults and are read-only when the SV Stream field is set to IEC 61850-9-2LE.
CT1- N
5 Range: None, AC1 to AC16
Default: AC4
This setting specifies the Analog Channel that is mapped to the CT ground/neutral input. An origin to CT1-N input
defines the physical measurement input to the CT bank by mapping specific AC inputs from that MU (or SV message). If
the MU does not publish any CT1-N inputs, configure the setting as None.
In the EnerVista software, the CT Aux input setting only populates the current channels of that RxSV#.
This CT Aux input setting is active when the SV Stream field is set to IEC 61869-9.
This CT Aux input setting is set to AC4 and is read-only when the SV Stream is set to IEC 61850-9-2LE.
VT1-A/B/C
Range: None, AC1 to AC16
Default: AC5/AC6/AC7
This setting specifies the Analog Channel (per phase) that is mapped to the VT1- phase inputs. An origin to VT Phase
input defines the physical measurement input to the VT bank by mapping specific AC inputs from that MU (or SV
message). If the MU does not publish any VT channels, configure the setting as None.
The VT1 phase fields are active when the SV Stream field is set to IEC 61869-9. The VT1 phases are available if the
number of VT Channels is 4 or below. VT2 is added if VT Channels is 5 or higher.
The fields are set to the defaults and are read-only when the SV Stream field is set to IEC 61850-9-2LE.
VT1-N
Range: None, AC1 to AC16
Default: AC8
This setting specifies the Analog Channel that is mapped to the VT Aux/neutral input. An origin to VT input defines the
physical measurement input to the VT bank by mapping specific AC inputs from that MU (or SV message). If the MU does
not publish any VT1-N inputs, configure the setting as None.
In the EnerVista software, the VT Aux input setting only populates the voltage channels of that RxSV#.
The VT1-N input setting is active when the SV Stream field is set to IEC 61869-9.
The VT1-N input setting is set to the default and is read-only when the SV Stream field is set to IEC 61850-9-2LE.

5-228 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

AC BANKS
The UR platform supports up to six AC Banks. They can be CT or VT banks (similar to SETTINGS  SYSTEM SETUP  AC
INPUTS  CURRENT/VOLTAGE BANK). That is, each AC Bank can be configured either as current or voltage (not both). If
configured as current, inapplicable voltage settings (such as VT ratio, VT secondary) are inactive. Similarly, if a bank is
configured as voltage, current settings (such as CT primary, CT secondary) are inactive. In addition, bank level
redundancy (that is, Origin-1 and Origin-2) is supported using crosschecking of each channel signal received from two
different SV streams that are connected to the same electrical point on the primary power system. A maximum 24
channels can be configured to the AC Banks.
Click the button to display or hide the fields.
The following settings are available for each AC bank.
Each Phase Origin setting consumes three phase channels Ia/Va, Ib/Vb, or Ic/Vc, and a Neutral Origin setting consumes
one ground or Aux Channel In/Vn, which means that
– An AC Bank with Phase Origin1 and Neutral Origin1 settings configured consumes four channels
– An AC Bank with both Phase Origin 1 and Phase Origin 2 and both Neutral Origin 1 and Neutral Origin 2 settings
configured consumes eight channels
A maximum of 24 channels can be configured to the AC Banks.
For changes in this section, restart the relay, for example using Maintenance > Reboot Relay Command.
Phase Origin 1, 2
Range: None, RxSV1-CT1/PHS, RxSV1-VT1/PHS to RxSV8-CT1/PHS, RxSV8-VT1/PHS
Default: None
An origin to an AC bank defines the physical measurement input to the bank by mapping specific AC inputs from a
specific MU to the bank. 5
The UR Process Bus Module provides for the reliability of AC values for protection, metering, and oscillography by
allowing duplicate origins of AC data. An origin is considered unavailable when set to None. If origin 1 is available, the
relay uses the values from origin 1 for protection, metering, and oscillography. Otherwise if origin 2 is available, the relay
uses the values from origin 2. If both origins are unavailable, then the bank AC values are forced to zero to prevent
ambiguity of measurement.
With crosschecking, the relay can use different origins. See the Crosschecking setting for information regarding
automatic protection blocking possibilities on loss of one or both origins.
The two-phase origins in an AC bank must be of the same type and connected to the same electrical point in the primary
power system. The two origins must be two currents with the same CT settings, or two voltages with the same VT
settings. The current/voltage type of the phase and auxiliary origins must also match on each AC bank. It is intended
that the origin AC inputs measure the same primary quantity with the same ratio. The same ratio and connection
settings are applied to both origins.
Neutral Origin 1, 2
Range: None, RxSV1-CT1/NTR, RxSV1-VT1/ NTR to RxSV8-CT1/NTR, RxSV8-VT1/ NTR
Default: None
These settings specify the field units that are the origins of the auxiliary input IN or VN. Duplicate auxiliary origins are
supported in the same way as phase origins.
The two auxiliary origins in an AC bank must be of the same type. The two origins must be two currents with the same CT
secondary setting, or two voltages. The current/voltage type of the phase and auxiliary origins also must match on each
AC bank. It is intended that the origin AC inputs measure the same primary quantity with the same ratio. The same ratio
and connection settings are applied to both origins.
Crosschecking
Range: None, Depend Origin-1 Pref, Depend Origin-2 Pref
Default: None
The crosschecking feature allows application-level redundancy by checking between two independent SV streams from
the same electrical connection of the instrument transformers. In addition to the network redundancy provided by PRP/
HSR, the UR Process Bus Module allows the relay to communicate with redundant merging units.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-229


PROCESS BUS MODULE CHAPTER 5: SETTINGS

When set to None, crosschecking is disabled. Use this on a non-protection-critical AC bank, such as one used for a
synchrocheck voltage. GE strongly recommends setting it to None when redundancy is not supported at the merging
unit level; otherwise the "ACBank# Orig1(2) In Use" operand status is inaccurate.
Origin preference is supported in case of discrepancy in dependability mode. This allows testing (secondary injection) or
replacement of an MU that is configured to non-preferred origin without affecting protection functions since these
functions are using a preferred origin stream when online. As such, dependability with Origin-1 preference allows
continued use of Origin-1 in case of discrepancy between both online origin stream sampled values. Similarly,
dependability with Origin-2 preference allows continued use of Origin-2 in case of discrepancy between both online
origin stream sampled values.
The table shows how the Crosschecking setting, the availability of AC bank origins, and discrepancy checks determine
whether protection is blocked. Blocked here means only protection elements. It does not inhibit metering, actual values,
oscillography, or other functions.
When set to Depend Origin-1 Pref, protection is blocked if there is no good signal from both the Origin-1 and Origin-2
sources. When both the merging unit sources are good, the preference is given always for Origin-1. When the preferred
MU sources fails, the alternate MU source is used for protection and measurement.
When set to Depend Origin-2 Pref, protection is blocked if there is no good signal from both the Origin-1 and Origin-2
sources. When both the merging unit sources are good, the preference is given always for Origin-2. When the preferred
MU sources fails, the alternate MU source is used for protection and measurement.

While switching from a preferred to non-preferred channel, the protection functions are delayed for two cycles.
While switching back to a preferred channel, the protection functions are delayed for one cycle.

Table 5-27: Crosschecking and protection behavior

5 Crosschecking
setting
Origin-1 RxSV stream Origin-2 RxSV
status stream status
Discrepancy check Protection operation

None Not relevant Not relevant No check Normal


Depend Origin-1 Not mapped Not mapped No check Normal
Pref
Online Online OK / discrepant Normal using Origin-1 stream
Online Offline No check Normal using Origin-1 stream
Offline Online No check Normal using Origin-2 stream
Offline Offline No check Blocked
Depend Origin-2 Not mapped Not mapped No check Normal
Pref
Online Online OK / discrepant Normal using Origin-2 stream
Online Offline No check Normal using Origin-1 stream
Offline Online No check Normal using Origin-2 stream
Offline Offline No check Blocked

Origin1 becomes offline and switches to Origin2 for the following reasons:
• When more than three of five frame samples received are invalid or a frame with sequence number is received after
three consecutive missed frames for any channel of origin.
The reason for invalid frames can be any of the following reasons:
– If one or more AmpSv.q or VolSv.q attribute(s) are invalid from the assigned SV frame channels to the AC bank
origin
– When "Quality Check" is set to 'Reject questionable' data, the data with q.validity = questionable is processed as
invalid
– When the relay is in-service or the test function is Disabled, the SV data with q.test set to TRUE is processed invalid
– When received SV frames with Sim Bit TRUE, the frame is invalid unless the value of @Master/LPHD1.Sim.stVal is
true (that is Settings > Simulation > GOOSE/SV > Accept Sim GOOSE&SV or Settings > Simulation > Subscribe
to Simulated Values > Simulation Mode is set to Enabled)

5-230 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS PROCESS BUS MODULE

– If the value of @Master/LPHD1.Sim.stVal is TRUE, once a subscribed SV messages with simulation bit TRUE are
received, subscribed SV messages with simulation bit FALSE are invalid until @Master/LPHD1.Sim.stVal is set to
FALSE
– SV streams with "SmpSync" value out of the following specified ranges are rejected:
i. When the "SmpSynch Check" is set to "Global" (2), SV streams with "SmpSynch" value set to Global (2) are
accepted
ii. When the "SmpSynch Check" is set to "Local" (1), SV streams with "SmpSynch" value set to Global (2) or Local (1)
are accepted
iii. When the "SmpSynch Check" is set to "Any" (0 to 254), SV streams with "SmpSynch" value set in the range of 0
to 254 are accepted. For 7.80 version, the accepted range is 0 to 127.
• SV frames are delayed/not received for more than 1.9 power system cycles
The selected Origin quality will be the quality of the AC Bank.
If both Origins have invalid quality, then the AC Bank data is marked as invalid and does not participate in protection.
Phase/Ground CT Primary
Range: 1 to 65000 A insteps of 1
Default: 1
Enter the rated CT primary current value in Amperes. For 1000:5 and 1000:1 CTs, enter 1000.
Phase/Ground CT Secondary
Range: 1A, 5A
Default: 1A
Enter the rated CT secondary current value in Amperes. For correct operation, the CT secondary rating must match the
setting (that must also correspond to the specific CT connections used).
5
SIGNAL SOURCES
Click the button to display or hide the fields. The first six Sources are the platform sources and can accept both current
banks and voltage banks and are associated with AC bank 1 to 6. The first six sources allow current summation for
phase and auxiliary CTs.
Recycle power to the relay when changing a source.
Name
Range: up to 20 alphanumeric characters
Default: SRC 1
This setting specifies an alphanumeric name for the source.
Phase CT
Range: None, B1, B2, B3, B4, B5, B6, B1+B2, ... B1+B2+B3+B4+B5+B6 or B7...B28
Default: None
This setting selects the phase CTs of an AC bank or the sum of the phase CTs of multiple AC banks to be the phase
current of the source. That is, it select the AC Banks section above in the window.
If you see the message "the AC Bank x assigned...is not configured..," it means that you need to configure the AC Banks
section in the software window before setting this field. The AC Bank selected can match the Origins fields and Sources,
such as a Phase CT set at B1 with Phase Origin 1 RxSV1-CT1/PHS and source SRC1. Another example is to use Phase CT
set at B2 with Phase Origin 1 RxSV2-CT1/PHS and source SRC2.
Ground CT
Range: None, B1, B2, B3, B4, B5, B6, B1+B2, ... B1+B2+B3+B4+B5+B6 or B7...B28
Default: None
This setting selects the ground CTs of an AC bank or the sum of the ground CTs of multiple AC banks to be the ground
current of the source. That is, it selects the AC Banks section above in the window.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-231


FLEXLOGIC CHAPTER 5: SETTINGS

Phase VT
Range: None, B1, B2, B3, B4, B5, B6
Default: None
This setting selects the phase VTs of an AC bank to be the phase voltages of the source.
Aux VT
Range: None, B1, B2, B3, B4, B5, B6
Default: None
This setting selects the auxiliary VT input of an AC bank to be the auxiliary voltage of the source.
Alt Phase CT
Range: None, B1, B2, B3, B4, B5, B6, B1+B2, ... B1+B2+B3+B4+B5+B6 or B7...B28
Default: None
This setting is for switching between main and alternate sources. It selects the alternate phase CTs of an AC bank or the
sum of the phase CTs of multiple AC banks to be the phase current of the source.
Alt Ground CT
Range: None, B1, B2, B3, B4, B5, B6, B1+B2, ... B1+B2+B3+B4+B5+B6 or B7...B28
Default: None
This setting is for switching between main and alternate sources. It selects the ground CTs of an AC bank or the sum of
the ground CTs of multiple AC banks to be the ground current of the source.
Switch Alt CT
Range: FlexLogic operand
Default: Off

5 This setting is for switching the alternate source on or off.


Alt Phase VT
Range: None, B1, B2, B3, B4, B5, B6
Default: None
This setting is for switching between main and alternate sources. It selects the phase VTs of an AC bank to be the phase
voltages of the source.
Alt Aux VT
Range: None, B1, B2, B3, B4, B5, B6
Default: None
This setting is for switching between main and alternate sources. It selects the auxiliary VT input of an AC bank to be the
auxiliary voltage of the source.
Switch Alt VT
Range: FlexLogic operand
Default: Off
This setting is for switching the alternate source on or off.

5.7 FlexLogic
5.7.1 FlexLogic operands
For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.

5-232 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Figure 5-114: UR architecture overview

CTs DSP
VTs (A/D) FlexLogic™ Virtual
equations outputs
Calculate
DCmA parameters Measuring
Analog and
or
input decision Digital Flags
RTD
(A/D) elements elements
inputs
V I
Contact Form-A and
inputs FlexLogic™ SCR only
Block counters
operation Contact
(each outputs
element)
Keypad
Virtual Remote
inputs (FlexLogic operands) outputs
OR

Remote Display
inputs Control and LEDs
(GOOSE) and Display
monitoring
features
fiber Analog
Direct output (D/A)
G.703 inputs
RS422 (dcmA)

5
(Status) Fiber
Direct
G.703
outputs
RS422
(Actual values) (Status)

EnerVista UR Setup and LAN communications

827022A7.cdr

The states of all digital signals used in the F60 are represented by flags (or FlexLogic operands, which are described later in
this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an
element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output. The state
of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple
scheme where a contact input is used to block an element is wanted, this selection is made when programming the
element. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes,
and human operators.
If more complex logic than shown in the figure is required, it is implemented via FlexLogic. For example, to have the closed
state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase
time overcurrent element, the two control input states are programmed in a FlexLogic equation. This equation ANDs the
two control inputs to produce a virtual output that is then selected when programming the phase time overcurrent to be
used as a blocking input. Virtual outputs can only be created by FlexLogic equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or
supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the requirement for
auxiliary components and wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes, and outputs is field-programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is
available internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes, and outputs. The operators are logic gates, timers, and latches (with
set and reset inputs). A system of sequential operations allows any combination of operands to be assigned as inputs to

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-233


FLEXLOGIC CHAPTER 5: SETTINGS

specified operators to create an output. The final output of an equation is a numbered register called a virtual output.
Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of
parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, or flag set) or 0
(=OFF, or flag not set). Each equation is evaluated at least four times every power system cycle.
Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the front panel display. The table lists characteristics
of the different types of operands.
Table 5-28: F60 FlexLogic operand types
Operand type State Example of format Characteristics
[Input Is ‘1’ (= ON) if...]
Contact Input On Cont Ip On Voltage is applied presently to the input (external contact
closed)
Off Cont Ip Off Voltage is not applied presently to the input (external
contact open)
Contact Output Contact Closed Cont Op 1 Closed Contact output is closed
(type Form-A contact
Current On Cont Op 1 Ion Current is flowing through the contact
only)
Voltage On Cont Op 1 VOn Voltage exists across the contact
Voltage Off Cont Op 1 VOff Voltage does not exist across the contact
Direct Input On DIRECT INPUT 1 On The direct input is presently in the ON state
Element Pickup PHASE TOC1 PKP The tested parameter is presently above the pickup setting
5 (Analog) of an element that responds to rising values or below the
pickup setting of an element that responds to falling values
Dropout PHASE TOC1 DPO This operand is the logical inverse of the above PKP
operand
Operate PHASE TOC1 OP The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing
Block PHASE TOC1 BLK The output of the comparator is set to the block function
Element Pickup Dig Element 1 PKP The input operand is at logic 1
(Digital)
Dropout Dig Element 1 DPO This operand is the logical inverse of the above PKP
operand
Operate Dig Element 1 OP The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing
Element Higher than Counter 1 HI The number of pulses counted is above the set number
(Digital Counter)
Equal to Counter 1 EQL The number of pulses counted is equal to the set number
Lower than Counter 1 LO The number of pulses counted is below the set number
Fixed On On Logic 1
Off Off Logic 0
RxGOOSE Boolean On RxGOOSE Boolean 1 On The RxGOOSE Boolean is presently in the ON state
Virtual Input On Virt Ip 1 On The virtual input is presently in the ON state
Virtual Output On Virt Op 1 On The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")

The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.

5-234 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Any FlexLogic operands that are visible online but not listed below, are intended for factory use.

Table 5-29: F60 FlexLogic operands


Operand type Operand syntax Operand description
ANNUNCIATOR ANY ANCTR ABNORMAL On for one second when any annunciator window state changes from
Graphical front panel normal to abnormal
ANY ANCTR ALARMED On while any annunciator window state is abnormal
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
Enhanced and basic CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
front panels CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
CYBERSENTRY ROLE ADMIN ACT Administrator role is active and is set to true when that is the case
ROLE SUPERVISOR ACT Supervisor role is active and is set to true when that is the case
ROLE ENGINEER ACT Engineer role is active and is set to true when that is the case
ROLE OPERATOR ACT Operator role is active and is set to true when that is the case
ROLE OBSERVER ACT Observer role is active and is set to true when that is the case
AUTHENTICATION FAIL Operand set for Failed Authentication self-test and alarm
UNAUTH FW ATTEMPT Operand set for firmware lock self-test and alarm
UNAUTH SETTING WRITE Operand set for settings lock self-test and alarm
FACTORY MODE ACTIVE Factory mode is enabled and set to true
ROLE M2M ACT Machine to machine role is active (CyberSecurity)
DIRECT DEVICES DIRECT DEVICE 1On Flag is set, logic=1
↓ ↓
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
Flag is set, logic=1
Flag is set, logic=1
5
↓ ↓
DIRECT DEVICE 16Off Flag is set, logic=1
DIRECT INPUT/ DIR IO CH1 CRC ALARM The rate of direct input messages received on channel 1 and failing the CRC
OUTPUT CHANNEL exceeded the user-specified level
MONITORING DIR IO CH2 CRC ALARM The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
DIR IO CH1 UNRET ALM The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
DIR IO CH2 UNRET ALM The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
ELEMENT: SRC 1 CT SW PROT BLK Protection blocked due to Source 1 CT switching
AC sources switching SRC 1 VT SW PROT BLK Protection blocked due to Source 1 VT switching
SRC1 CT ALT BANK ON Source 1 switched CT input from Main to Alternate
SRC1 CT ALT BANK OFF Source 1 switched CT input from Alternate to Main
SRC1 VT ALT BANK ON Source 1 switched VT input from Main to Alternate
SRC1 VT ALT BANK OFF Source 1 switched VT input from Alternate to Main
SRC 1 to 4 Same set of operands as shown for SRC 1
ELEMENT: AR1 ENABLED Autoreclose 1 is enabled
Autoreclose AR1 RIP Autoreclose 1 is in progress
(per CT bank) AR1 LO Autoreclose 1 is locked out
AR1 BLK FROM MAN CLS Autoreclose 1 is temporarily disabled
AR1 CLOSE Autoreclose 1 close command is issued
AR1 SHOT CNT=0 Autoreclose 1 shot count is 0
AR1 SHOT CNT=1 Autoreclose 1 shot count is 1
AR1 SHOT CNT=2 Autoreclose 1 shot count is 2
AR1 SHOT CNT=3 Autoreclose 1 shot count is 3
AR1 SHOT CNT=4 Autoreclose 1 shot count is 4
AR1 DISABLED Autoreclose 1 is disabled
AR2 to 4 Same set of operands as shown for AR1
ELEMENT: AUX OV1 PKP Auxiliary overvoltage element has picked up
Auxiliary overvoltage AUX OV1 DPO Auxiliary overvoltage element has dropped out
AUX OV1 OP Auxiliary overvoltage element has operated
AUX OV2 Same set of operands as shown for AUX OV1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-235


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


ELEMENT: AUX UV1 PKP Auxiliary undervoltage element has picked up
Auxiliary AUX UV1 DPO Auxiliary undervoltage element has dropped out
undervoltage AUX UV1 OP Auxiliary undervoltage element has operated
AUX UV2 to 3 Same set of operands as shown for AUX UV1
ELEMENT: BKR 1 FLSHOVR PKP A Breaker 1 flashover element phase A has picked up
Breaker flashover BKR 1 FLSHOVR PKP B Breaker 1 flashover element phase B has picked up
BKR 1 FLSHOVR PKP C Breaker 1 flashover element phase C has picked up
BKR 1 FLSHOVR PKP Breaker 1 flashover element has picked up
BKR 1 FLSHOVR OP A Breaker 1 flashover element phase A has operated
BKR 1 FLSHOVR OP B Breaker 1 flashover element phase B has operated
BKR 1 FLSHOVR OP C Breaker 1 flashover element phase C has operated
BKR 1 FLSHOVR OP Breaker 1 flashover element has operated
BKR 1 FLSHOVR DPO A Breaker 1 flashover element phase A has dropped out
BKR 1 FLSHOVR DPO B Breaker 1 flashover element phase B has dropped out
BKR 1 FLSHOVR DPO C Breaker 1 flashover element phase C has dropped out
BKR 1 FLSHOVR DPO Breaker 1 flashover element has dropped out
BKR 2 FLSHOVR Same set of operands as shown for BKR 1 FLSHOVR
ELEMENT: BKR ARC 1 OP Breaker arcing current 1 has operated
Breaker arcing BKR ARC 1 DPO Breaker arcing current 1 has dropped out
BKR ARC 1 MAX OP Breaker arcing current 1 max interrupting current has operated
BKR ARC 1 MAX DPO Breaker arcing current 1 max interrupting current has dropped out
BKR ARC 2 OP Breaker arcing current 2 has operated
BKR ARC 2 DPO Breaker arcing current 2 has dropped out
BKR ARC 2 MAX OP Breaker arcing current 2 max interrupting current has operated
BKR ARC 2 MAX DPO Breaker arcing current 2 max interrupting current has dropped out
ELEMENT: BKR FAIL 1 RETRIP A Breaker failure 1 re-trip phase A (only for 1-pole schemes)
Breaker failure BKR FAIL 1 RETRIP B Breaker failure 1 re-trip phase B (only for 1-pole schemes)
BKR FAIL 1 RETRIP C Breaker failure 1 re-trip phase C (only for 1-pole schemes)
5 BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
Breaker failure 1 re-trip 3-phase
Breaker failure 1 timer 1 is operated
BKR FAIL 1 T2 OP Breaker failure 1 timer 2 is operated
BKR FAIL 1 T3 OP Breaker failure 1 timer 3 is operated
BKR FAIL 1 TRIP OP Breaker failure 1 trip is operated
BKR FAIL 2 to 4 Same set of operands as shown for BKR FAIL 1
ELEMENT: BRK RESTRIKE 1 OP Breaker restrike detected in any phase of the breaker control 1 element
Breaker restrike BRK RESTRIKE 1 OP A Breaker restrike detected in phase A of the breaker control 1 element
BRK RESTRIKE 1 OP B Breaker restrike detected in phase B of the breaker control 1 element
BRK RESTRIKE 1 OP C Breaker restrike detected in phase C of the breaker control 1 element

5-236 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Operand type Operand syntax Operand description


ELEMENT: BREAKER 1 OFF CMD Breaker 1 3-pole open command/trip initiated
Breaker control BREAKER 1 ON CMD Breaker 1 close command initiated
BREAKER 1 ΦA BAD ST Breaker 1 phase A bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦA INTERM Breaker 1 phase A intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦA CLSD Breaker 1 phase A is closed
BREAKER 1 ΦA OPEN Breaker 1 phase A is open
BREAKER 1 ΦB BAD ST Breaker 1 phase B bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦB INTERM Breaker 1 phase B intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦB CLSD Breaker 1 phase B is closed
BREAKER 1 ΦB OPEN Breaker 1 phase B is open
BREAKER 1 ΦC BAD ST Breaker 1 phase C bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦC INTERM Breaker 1 phase C intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦC CLSD Breaker 1 phase C is closed
BREAKER 1 ΦC OPEN Breaker 1 phase C is open
BREAKER 1 BAD STATUS Breaker 1 bad status is detected on any pole
BREAKER 1 CLOSED Breaker 1 is closed
BREAKER 1 OPEN Breaker 1 is open
BREAKER 1 DISCREP Breaker 1 has discrepancy
BREAKER 1 TROUBLE Breaker 1 trouble alarm
BREAKER 1 MNL OPEN Breaker 1 manual open
BREAKER 1 MNL CLS Breaker 1 manual close
BREAKER 1 TRIP A Breaker 1 trip phase A command
BREAKER 1 TRIP B Breaker 1 trip phase B command
BREAKER 1 TRIP C Breaker 1 trip phase C command
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
5
BREAKER 1 TAG ON Breaker 1 tagged so manual trip and close and autoreclose are blocked
BREAKER 1 TAG OFF Breaker 1 not tagged
BREAKER 1 SUBD CLSD Breaker 1 status manually substituted to closed
BREAKER 1 SUBD OPEN Breaker 1 status manually substituted to open
BREAKER 1 BYPASS ON Breaker 1 control interlocking is manually bypassed
BREAKER 1 BYPASS OFF Breaker 1 control interlocking is not manually bypassed
BREAKER 1 BLK RCLS Breaker 1 command to manually block autoreclose
BREAKER 1 ENA RCLS Breaker 1 command to manually enable autoreclose
BREAKER 1 BAY AUTHOR ON Breaker 1 Bay Level authority is on
BREAKER 1 STATN AUTHOR ON Breaker 1 Station Level authority is on
BREAKER 1 REM AUTHOR ON Breaker 1 Remote Level Authority is on
BREAKER 1 LOCAL AUTHOR ON Breaker 1 Local Control Authority is on
BREAKER 2 to 4 Same set of operands as shown for BREAKER 1
ELEMENT: BROKEN CONDUCT 1 OP Asserted when the broken conductor 1 element operates
Broken conductor BROKEN CONDUCT 1 PKP Asserted when the broken conductor 1 element picks up
BROKEN CONDUCT 2 Same set of operands as shown for BROKEN CONDUCTOR 1
ELEMENT: COLD LOAD 1 OP Cold load pickup element 1 has operated
Cold load pickup
COLD LOAD 2 Same set of operands as shown for COLD LOAD 1
ELEMENT: CT FAIL 1 PKP CT fail has picked up
CT fail CT FAIL 1 OP CT fail has dropped out
CT FAIL 2 to 4 Same set of operands as per CT FAIL 1
ELEMENT: Counter 1 HI Digital counter 1 output is ‘more than’ comparison value
Digital counters Counter 1 EQL Digital counter 1 output is ‘equal to’ comparison value
Counter 1 LO Digital counter 1 output is ‘less than’ comparison value
Counter 2 to 8 Same set of operands as shown for Counter 1
ELEMENT: DCB3 TX INIT Directional blocking signal is initiated
Directional DCB3 TX STOP Directional blocking scheme de-asserts transmit signal
comparison blocking DCB3 OP Directional blocking scheme has operated
scheme (DCB3)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-237


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


ELEMENT: Dig Element 1 PKP Digital Element 1 is picked up
Digital elements Dig Element 1 OP Digital Element 1 is operated
Dig Element 1 DPO Digital Element 1 is dropped out
Dig Element 2 to 96 Same set of operands as shown for Dig Element 1
ELEMENT: DIR POWER 1 STG1 PKP Stage 1 of the directional power element 1 has picked up
Sensitive directional DIR POWER 1 STG2 PKP Stage 2 of the directional power element 1 has picked up
power DIR POWER 1 STG1 DPO Stage 1 of the directional power element 1 has dropped out
DIR POWER 1 STG2 DPO Stage 2 of the directional power element 1 has dropped out
DIR POWER 1 STG1 OP Stage 1 of the directional power element 1 has operated
DIR POWER 1 STG2 OP Stage 2 of the directional power element 1 has operated
DIR POWER 1 PKP The directional power element has picked up
DIR POWER 1 DPO The directional power element has dropped out
DIR POWER 1 OP The directional power element has operated
DIR POWER 2 Same set of operands as DIR POWER 1
ELEMENT: FREQ RATE 1 PKP The frequency rate of change 1 element has picked up
Frequency rate of FREQ RATE 1 DPO The frequency rate of change 1 element has dropped out
change FREQ RATE 1 OP The frequency rate of change 1 element has operated
FREQ RATE 2 to 4 Same set of operands as shown for FREQ RATE 1
ELEMENT: FxE 1 PKP FlexElement 1 has picked up
FlexElements FxE 1 OP FlexElement 1 has operated
FxE 1 DPO FlexElement 1 has dropped out
FxE 2 to 16 Same set of operands as shown for FxE 1
ELEMENT: GROUND IOC1 PKP Ground instantaneous overcurrent 1 has picked up
Ground GROUND IOC1 OP Ground instantaneous overcurrent 1 has operated
instantaneous GROUND IOC1 DPO Ground instantaneous overcurrent 1 has dropped out
overcurrent

5 ELEMENT:
GROUND IOC2 to 6
GROUND TOC1 PKP
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time GROUND TOC1 OP Ground time overcurrent 1 has operated
overcurrent GROUND TOC1 DPO Ground time overcurrent 1 has dropped out
GROUND TOC2 to 4 Same set of operands as shown for GROUND TOC1
Element: HARMONIC DET 1 PKP At least one phase (or the average current) of HARMONIC DET 1 has picked up
Harmonic detection HARMONIC DET 1 PKP A HARMONIC DET 1 has picked up in phase A
HARMONIC DET 1 PKP B HARMONIC DET 1 has picked up in phase B
HARMONIC DET 1 PKP C HARMONIC DET 1 has picked up in phase C
HARMONIC DET 1 PKP G HARMONIC DET 1 has picked up in Ground channel
HARMONIC DET 1 OP HARMONIC DET 1 has operated per Phases for Operation selection
HARMONIC DET 1 OP A Phase A of HARMONIC DET 1 has operated
HARMONIC DET 1 OP B Phase B of HARMONIC DET 1 has operated
HARMONIC DET 1 OP C Phase C of HARMONIC DET 1 has operated
HARMONIC DET 1 OP G HARMONIC DET 1 has operated in Ground channel
ELEMENT: HI-Z ARC DETECTED The high impedance fault detection element has operated
High impedance fault HI-Z ARC DETECTED-A The high impedance fault detection phase A element has operated
detection HI-Z ARC DETECTED-B The high impedance fault detection phase B element has operated
(Hi-Z) HI-Z ARC DETECTED-C The high impedance fault detection phase C element has operated
HI-Z ARC DETECTED DPO No arcing has been detected
HI-Z ARMED The high impedance fault detection element is in the armed state
HI-Z DISARMED The high impedance fault detection element is in the disarmed state
HI-Z DOWNED COND The high impedance fault downed conductor element has operated
HI-Z DOWNED COND-A The high impedance fault downed conductor phase A element has operated
HI-Z DOWNED COND-B The high impedance fault downed conductor phase B element has operated
HI-Z DOWNED COND-C The high impedance fault downed conductor phase C element has operated
HI-Z ARC SUSPECTED The high impedance fault detection arcing suspected element has operated
HI-Z ARC SUSPECTED-A The high impedance fault arcing suspected phase A element has operated
HI-Z ARC SUSPECTED-B The high impedance fault arcing suspected phase B element has operated
HI-Z ARC SUSPECTED-C The high impedance fault arcing suspected phase C element has operated
HI-Z ARC SUSPECTED-N The high impedance fault arcing suspected neutral element has operated
HI-Z IOC A The high impedance instantaneous overcurrent A element has operated
HI-Z IOC B The high impedance instantaneous overcurrent B element has operated
HI-Z IOC C The high impedance instantaneous overcurrent C element has operated
HI-Z LOSS OF LOAD-A The high impedance fault phase A loss of load element has operated
HI-Z LOSS OF LOAD-B The high impedance fault phase B loss of load element has operated
HI-Z LOSS OF LOAD-C The high impedance fault phase C loss of load element has operated

5-238 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Operand type Operand syntax Operand description


ELEMENT: IED BEH TEST Relay in Test mode
IED mode IED BEH TEST-BLOCKED Relay in Test Blocked mode
IED BEH ON Relay mode is On
ELEMENT: INCIPNT FLT 1 OP Asserted when incipient cable fault detector 1 operates in any phase
Incipient cable fault INCIPNT FLT 1 OP A Asserted when incipient cable fault detector 1 operates in phase A
detection INCIPNT FLT 1 OP B Asserted when incipient cable fault detector 1 operates in phase B
INCIPNT FLT 1 OP C Asserted when incipient cable fault detector 1 operates in phase C
INCIPNT FLT 1 PKP Asserted when incipient cable fault detector 1 picks up in any phase
INCIPNT FLT 1 PKP A Asserted when incipient cable fault detector 1 picks up in phase A
INCIPNT FLT 1 PKP B Asserted when incipient cable fault detector 1 picks up in phase B
INCIPNT FLT 1 PKP C Asserted when incipient cable fault detector 1 picks up in phase C
INCIPNT FLT 2 Same set of operands as shown for INCIPNT FLT 1
ELEMENT: LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16 Same set of operands as shown for LATCH 1
ELEMENT: LOAD ENCHR PKP Load encroachment has picked up
Load encroachment LOAD ENCHR OP Load encroachment has operated
LOAD ENCHR DPO Load encroachment has dropped out
ELEMENT: NEG SEQ DIR OC1 FWD Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence NEG SEQ DIR OC1 REV Negative-sequence directional overcurrent 1 reverse has operated
directional NEG SEQ DIR OC2 FWD Negative-sequence directional overcurrent 2 forward has operated
overcurrent NEG SEQ DIR OC2 REV Negative-sequence directional overcurrent 2 reverse has operated
ELEMENT: NEG SEQ IOC1 PKP Negative-sequence instantaneous overcurrent 1 has picked up
Negative-sequence NEG SEQ IOC1 OP Negative-sequence instantaneous overcurrent 1 has operated
instantaneous NEG SEQ IOC1 DPO Negative-sequence instantaneous overcurrent 1 has dropped out
overcurrent

ELEMENT:
NEG SEQ IOC2
NEG SEQ OV1 PKP
Same set of operands as shown for NEG SEQ IOC1
Negative-sequence overvoltage element has picked up
5
Negative-sequence NEG SEQ OV1 DPO Negative-sequence overvoltage element has dropped out
overvoltage NEG SEQ OV1 OP Negative-sequence overvoltage element has operated
NEG SEQ OV2 to 3 Same set of operands as shown for NEG SEQ OV1
ELEMENT: NEG SEQ TOC1 PKP Negative-sequence time overcurrent 1 has picked up
Negative-sequence NEG SEQ TOC1 OP Negative-sequence time overcurrent 1 has operated
time overcurrent NEG SEQ TOC1 DPO Negative-sequence time overcurrent 1 has dropped out
NEG SEQ TOC2 Same set of operands as shown for NEG SEQ TOC1
ELEMENT: NEUTRAL IOC1 PKP Neutral instantaneous overcurrent 1 has picked up
Neutral NEUTRAL IOC1 OP Neutral instantaneous overcurrent 1 has operated
instantaneous NEUTRAL IOC1 DPO Neutral instantaneous overcurrent 1 has dropped out
overcurrent
NEUTRAL IOC2 to 8 Same set of operands as shown for NEUTRAL IOC1
ELEMENT: NEUTRAL OV1 PKP Neutral overvoltage element 1 has picked up
Neutral overvoltage NEUTRAL OV1 DPO Neutral overvoltage element 1 has dropped out
NEUTRAL OV1 OP Neutral overvoltage element 1 has operated
NEUTRAL OV2 to 3 Same set of operands as shown for NEUTRAL OV1
ELEMENT: NEUTRAL TOC1 PKP Neutral time overcurrent 1 has picked up
Neutral time NEUTRAL TOC1 OP Neutral time overcurrent 1 has operated
overcurrent NEUTRAL TOC1 DPO Neutral time overcurrent 1 has dropped out
NEUTRAL TOC2 to 6 Same set of operands as shown for NEUTRAL TOC1
ELEMENT: NTRL DIR OC1 FWD Neutral directional overcurrent 1 forward has operated
Neutral directional NTRL DIR OC1 REV Neutral directional overcurrent 1 reverse has operated
overcurrent
NTRL DIR OC2 Same set of operands as shown for NTRL DIR OC1
ELEMENT: OVERFREQ 1 PKP Overfrequency 1 has picked up
Overfrequency OVERFREQ 1 OP Overfrequency 1 has operated
OVERFREQ 1 DPO Overfrequency 1 has dropped out
OVERFREQ 2 to 4 Same set of operands as shown for OVERFREQ 1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-239


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


ELEMENT: PDC NETWORK CNTRL 1 Phasor data concentrator asserts control bit 1 as received via the network
Synchrophasor PDC NETWORK CNTRL 2 Phasor data concentrator asserts control bit 2 as received via the network
phasor data ↓ ↓
concentrator PDC NETWORK CNTRL 16 Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT: PH DIR1 BLK A Phase A directional 1 block
Phase directional PH DIR1 BLK B Phase B directional 1 block
overcurrent PH DIR1 BLK C Phase C directional 1 block
PH DIR1 BLK Phase directional 1 block
PH DIR2 Same set of operands as shown for PH DIR1
ELEMENT: PHASE IOC1 PKP At least one phase of phase instantaneous overcurrent 1 has picked up
Phase instantaneous PHASE IOC1 OP At least one phase of phase instantaneous overcurrent 1 has operated
overcurrent PHASE IOC1 DPO All phases of phase instantaneous overcurrent 1 have dropped out
PHASE IOC1 PKP A Phase A of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP B Phase B of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP C Phase C of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 OP A Phase A of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP B Phase B of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP C Phase C of phase instantaneous overcurrent 1 has operated
PHASE IOC1 DPO A Phase A of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO B Phase B of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO C Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 to 8 Same set of operands as shown for PHASE IOC1
ELEMENT: PHASE OV1 PKP At least one phase of overvoltage 1 has picked up
Phase overvoltage PHASE OV1 OP At least one phase of overvoltage 1 has operated
PHASE OV1 DPO All phases of overvoltage 1 have dropped out
PHASE OV1 PKP A Phase A of overvoltage 1 has picked up
PHASE OV1 PKP B Phase B of overvoltage 1 has picked up
PHASE OV1 PKP C Phase C of overvoltage 1 has picked up
5 PHASE OV1 OP A
PHASE OV1 OP B
Phase A of overvoltage 1 has operated
Phase B of overvoltage 1 has operated
PHASE OV1 OP C Phase C of overvoltage 1 has operated
PHASE OV1 DPO A Phase A of overvoltage 1 has dropped out
PHASE OV1 DPO B Phase B of overvoltage 1 has dropped out
PHASE OV1 DPO C Phase C of overvoltage 1 has dropped out
PHASE OV2 to 3 Same set of operands as shown for PHASE OV1
ELEMENT: PHASE TOC1 PKP At least one phase of phase time overcurrent 1 has picked up
Phase time PHASE TOC1 OP At least one phase of phase time overcurrent 1 has operated
overcurrent PHASE TOC1 DPO All phases of phase time overcurrent 1 have dropped out
PHASE TOC1 PKP A Phase A of phase time overcurrent 1 has picked up
PHASE TOC1 PKP B Phase B of phase time overcurrent 1 has picked up
PHASE TOC1 PKP C Phase C of phase time overcurrent 1 has picked up
PHASE TOC1 OP A Phase A of phase time overcurrent 1 has operated
PHASE TOC1 OP B Phase B of phase time overcurrent 1 has operated
PHASE TOC1 OP C Phase C of phase time overcurrent 1 has operated
PHASE TOC1 DPO A Phase A of phase time overcurrent 1 has dropped out
PHASE TOC1 DPO B Phase B of phase time overcurrent 1 has dropped out
PHASE TOC1 DPO C Phase C of phase time overcurrent 1 has dropped out
PHASE TOC2 to 6 Same set of operands as shown for PHASE TOC1
ELEMENT: PHASE UV1 PKP At least one phase of phase undervoltage 1 has picked up
Phase undervoltage PHASE UV1 OP At least one phase of phase undervoltage 1 has operated
PHASE UV1 DPO All phases of phase undervoltage 1 have dropped out
PHASE UV1 PKP A Phase A of phase undervoltage 1 has picked up
PHASE UV1 PKP B Phase B of phase undervoltage 1 has picked up
PHASE UV1 PKP C Phase C of phase undervoltage 1 has picked up
PHASE UV1 OP A Phase A of phase undervoltage 1 has operated
PHASE UV1 OP B Phase B of phase undervoltage 1 has operated
PHASE UV1 OP C Phase C of phase undervoltage 1 has operated
PHASE UV1 DPO A Phase A of phase undervoltage 1 has dropped out
PHASE UV1 DPO B Phase B of phase undervoltage 1 has dropped out
PHASE UV1 DPO C Phase C of phase undervoltage 1 has dropped out
PHASE UV2 to 3 Same set of operands as shown for PHASE UV1

5-240 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Operand type Operand syntax Operand description


ELEMENT: PMU Agg 1 SvEng On SvEng data item in associated control block is on
Synchrophasor PMU 1 CURR TRIGGER Overcurrent trigger of phasor measurement unit 1 has operated
Phasor Measurement PMU 1 FREQ TRIGGER Abnormal frequency trigger of phasor measurement unit 1 has operated
Unit (PMU) PMU 1 POWER TRIGGER Overpower trigger of phasor measurement unit 1 has operated
PMU 1 ROCOF TRIGGER Rate of change of frequency trigger of phasor measurement unit 1 has
operated
PMU 1 VOLT TRIGGER Abnormal voltage trigger of phasor measurement unit 1 has operated
PMU 1 TRIGGERED Phasor measurement unit 1 triggered; no events or targets are generated by
this operand
PMU 1 REC OUT OF MEM Recorder for PMU 1 out of memory (if the trigger mode is protected)
PMU 1 REC STOPPED Recorder for PMU 1 stopped
ELEMENT: PMU ONE-SHOT EXPIRED Indicates the one-shot operation has been executed, and the present time is
Synchrophasor one- at least 30 seconds past the scheduled one-shot time
shot PMU ONE-SHOT OP Indicates the one-shot operation and remains asserted for 30 seconds
afterwards
PMU ONE-SHOT PENDING Indicates the one-shot operation is pending; that is, the present time is before
the scheduled one-shot time
ELEMENT: POTT3 OP Permissive over-reaching transfer trip has operated
POTT3 POTT3 TX Permissive over-reaching transfer trip signal sent
(Permissive
overreach transfer
trip three pole)
ELEMENT: RESTD GND FT1 PKP Restricted ground fault 1 has picked up
Restricted ground RESTD GND FT1 OP Restricted ground fault 1 has operated
fault RESTD GND FT1 DPO Restricted ground fault 1 has dropped out
RESTD GND FT2 to 4 Same set of operands as shown for RESTD GND FT1
ELEMENT: SELECTOR 1 POS Y Selector switch 1 is in Position Y (mutually exclusive operands)
Selector switch SELECTOR 1 BIT 0 First bit of the 3-bit word encoding position of selector 1
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
5
SELECTOR 1 STP ALARM Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
SELECTOR 1 BIT ALARM Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
SELECTOR 1 ALARM Position of selector 1 has been pre-selected but not acknowledged
SELECTOR 1 PWR ALARM Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
SELECTOR 2 Same set of operands as shown for SELECTOR 1
ELEMENT: SETTING GROUP ACT 1 Setting group 1 is active
Setting group SETTING GROUP ACT 2 Setting group 2 is active
SETTING GROUP ACT 3 Setting group 3 is active
SETTING GROUP ACT 4 Setting group 4 is active
SETTING GROUP ACT 5 Setting group 5 is active
SETTING GROUP ACT 6 Setting group 6 is active
ELEMENT: SRC1 50DD OP Source 1 disturbance detector has operated
Disturbance detector SRC2 50DD OP Source 2 disturbance detector has operated
SRC3 50DD OP Source 3 disturbance detector has operated
SRC4 50DD OP Source 4 disturbance detector has operated
ELEMENT: SRC1 VT FF OP Source 1 VT fuse failure detector has operated
VTFF (Voltage SRC1 VT FF DPO Source 1 VT fuse failure detector has dropped out
transformer fuse SRC1 VT FF VOL LOSS Source 1 has lost voltage signals (V2 below 10% and V1 below 5% of nominal)
failure) SRC1 VT FF ALARM Source 1 has triggered a VT fuse failure alarm
SRC1 VT NEU WIRE OPEN Source 1 VT neutral wire open detected. When the VT is connected in Delta,
do not enable this function because there is no neutral wire for Delta
connected VT.
SRC2 VT FUSE FAIL to SRC4 Same set of operands as shown for SRC1 VT FF

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-241


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated
Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated
SWITCH 1 CLOSED Disconnect switch 1 is closed
SWITCH 1 OPEN Disconnect switch 1 is open
SWITCH 1 DISCREP Disconnect switch 1 has discrepancy
SWITCH 1 TROUBLE Disconnect switch 1 trouble alarm
SWITCH 1 ΦA CLSD Disconnect switch 1 phase A is closed
SWITCH 1 ΦA OPEN Disconnect switch 1 phase A is open
SWITCH 1 ΦA BAD ST Disconnect switch 1 phase A bad status is detected (discrepancy between
the 89/a and 89/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦB CLSD Disconnect switch 1 phase B is closed
SWITCH 1 ΦB OPEN Disconnect switch 1 phase B is open
SWITCH 1 ΦB BAD ST Disconnect switch 1 phase B bad status is detected (discrepancy between
the 89/a and 89/b contacts)
SWITCH 1 ΦB INTERM Disconnect switch 1 phase B intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦC CLSD Disconnect switch 1 phase C is closed
SWITCH 1 ΦC OPEN Disconnect switch 1 phase C is open
SWITCH 1 ΦC BAD ST Disconnect switch 1 phase C bad status is detected (discrepancy between
the 89/a and 89/b contacts)
SWITCH 1 ΦC INTERM Disconnect switch 1 phase C intermediate status is detected (transition from
one position to another)
SWITCH 1 BAD STATUS Disconnect switch 1 bad status is detected on any pole
SWITCH 1 TAG ON Switch 1 tagged so manual trip and close is blocked
SWITCH 1 TAG OFF Switch 1 not tagged
SWITCH 1 SUBD CLSD Switch 1 status manually substituted to closed
SWITCH 1 SUBD OPEN Switch 1 status manually substituted to open
SWITCH 1 BYPASS ON Switch 1 control interlocking is bypassed manually

5 SWITCH 1 BYPASS OFF


SWITCH 2 to 16
Switch 1 control interlocking is not bypassed manually
Same set of operands as shown for SWITCH 1
ELEMENT: SYNC1 DEAD S OP Synchrocheck 1 dead source has operated
Synchrocheck SYNC1 DEAD S DPO Synchrocheck 1 dead source has dropped out
SYNC1 SYNC OP Synchrocheck 1 in synchronization has operated
SYNC1 SYNC DPO Synchrocheck 1 in synchronization has dropped out
SYNC1 CLS OP Synchrocheck 1 close has operated
SYNC1 CLS DPO Synchrocheck 1 close has dropped out
SYNC1 V1 ABOVE MIN Synchrocheck 1 V1 is above the minimum live voltage
SYNC1 V1 BELOW MAX Synchrocheck 1 V1 is below the maximum dead voltage
SYNC1 V2 ABOVE MIN Synchrocheck 1 V2 is above the minimum live voltage
SYNC1 V2 BELOW MAX Synchrocheck 1 V2 is below the maximum dead voltage
SYNC1 S-CLOSE OP Synchrocheck 1 S-CLOSE has operated
SYNC1 S-CLOSE OP DPO Synchrocheck 1 S-CLOSE has dropped out
SYNC1 S-CLOSE ARMD Synchrocheck 1 S-CLOSE has been armed
SYNC 2 to 4 Same set of operands as shown for SYNC 1
ELEMENT: TELEPRO CH1 FAIL Channel 1 failed
Teleprotection TELEPRO CH2 FAIL Channel 2 failed
channel tests TELEPRO CH1 ID FAIL The ID check for a peer relay on channel 1 has failed
TELEPRO CH2 ID FAIL The ID check for a peer relay on channel 2 has failed
TELEPRO CH1 CRC FAIL CRC detected packet corruption on channel 1
TELEPRO CH2 CRC FAIL CRC detected packet corruption on channel 2
TELEPRO CH1 PKT LOST CRC detected lost packet on channel 1
TELEPRO CH2 PKT LOST CRC detected lost packet on channel 2
ELEMENT: TELEPRO INPUT 1-1 On Flag is set, Logic =1
Teleprotection ↓ ↓
inputs/outputs TELEPRO INPUT 1-16 On Flag is set, Logic =1
TELEPRO INPUT 2-1 On Flag is set, Logic =1
↓ ↓
TELEPRO INPUT 2-16 On Flag is set, Logic =1
ELEMENT: THERMAL PROT 1 PKP Thermal overload protection 1 picked up
Thermal overload THERMAL PROT 1 OP Thermal overload protection 1 operated
protection THERMAL PROT 1 ALARM Thermal protection 1 has reached the selected alarm level
THERMAL PROT 2 Same set of operands as shown for THERMAL PROT 1
ELEMENT: TRIP BUS 1 PKP Asserted when the trip bus 1 element picks up
Trip bus TRIP BUS 1 OP Asserted when the trip bus 1 element operates

5-242 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Operand type Operand syntax Operand description


TRIP BUS 2 to 6 Same set of operands as shown for TRIP BUS 1
ELEMENT: UNDERFREQ 1 PKP Underfrequency 1 has picked up
Underfrequency UNDERFREQ 1 OP Underfrequency 1 has operated
UNDERFREQ 1 DPO Underfrequency 1 has dropped out
UNDERFREQ 2 to 6 Same set of operands as shown for UNDERFREQ 1
ELEMENT: WATTMETRIC 1 PKP Wattmetric directional element 1 has picked up
Wattmetric zero- WATTMETRIC 1 OP Wattmetric directional element 1 has operated
sequence directional
WATTMETRIC 2 Same set of operands as per WATTMETRIC 1
ELEMENT: TGFD 1 FORWARD Transient ground fault detector 1 has picked forward transient ground fault
Transient ground TGFD 1 REVERSE Transient ground fault detector 1 has picked reverse transient ground fault
fault detection TGFD 1 START Transient ground fault detector 1 has started
TGFD 2 to 4 Same set of operands as per TGFD 1
FIXED OPERANDS Off Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS: Cont Ip 1 On (does not appear unless ordered)
Contact inputs Cont Ip 2 On (does not appear unless ordered)
↓ ↓
Cont Ip 1 Off (does not appear unless ordered)
Cont Ip 2 Off (does not appear unless ordered)
↓ ↓
Cont Ip 120 On (does not appear unless ordered)
Cont Ip 120 Off (does not appear unless ordered)
INPUTS/OUTPUTS: Cont Op 1 IOn (does not appear unless ordered)
Contact outputs,
current
(from detector on
Cont Op 2 IOn

Cont Op 72 IOn
(does not appear unless ordered)

(does not appear unless ordered)
5
form-A output only)
INPUTS/OUTPUTS: Cont Op 1 VOn (does not appear unless ordered)
Contact outputs, Cont Op 2 VOn (does not appear unless ordered)
voltage ↓ ↓
(from detector on Cont Op 72 VOn (does not appear unless ordered)
form-A output only)
Cont Op 1 VOff (does not appear unless ordered)
Cont Op 2 VOff (does not appear unless ordered)
↓ ↓
Cont Op 72 VOff (does not appear unless ordered)
INPUTS/OUTPUTS: DIRECT INPUT 1 On Flag is set, logic=1
Direct inputs ↓ ↓
DIRECT INPUT 32 On Flag is set, logic=1
INPUTS/OUTPUTS: RxG DPS 1 BAD Asserted while the RxGOOSE double-point status input is in the bad state
RxGOOSE DPS RxG DPS 1 INTERM Asserted while the RxGOOSE double-point status input is in the intermediate
state
RxG DPS 1 OFF Asserted while the RxGOOSE double-point status input is off
RxG DPS 1 ON Asserted while the RxGOOSE double-point status input is on
RxG DPS 2 to 16 Same set of operands as per RxG DPS 1
INPUTS/OUTPUTS: RxG Bool 1 On Flag is set, logic=1
RxGOOSE Booleans RxG Bool 2 On Flag is set, logic=1
RxG Bool 3 On Flag is set, logic=1
↓ ↓
RxG Bool 256 On Flag is set, logic=1
INPUTS/OUTPUTS: Virt Ip 1 On Flag is set, logic=1
Virtual inputs Virt Ip 2 On Flag is set, logic=1
Virt Ip 3 On Flag is set, logic=1
↓ ↓
Virt Ip 128 On Flag is set, logic=1
INPUTS/OUTPUTS: Virt Op 1 On Flag is set, logic=1
Virtual outputs Virt Op 2 On Flag is set, logic=1
Virt Op 3 On Flag is set, logic=1
↓ ↓
Virt Op 256 On Flag is set, logic=1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-243


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on
Enhanced and basic LED TROUBLE Asserted when the front panel TROUBLE LED is on
front panels LED TEST MODE Asserted when the front panel TEST MODE LED is on
LED TRIP Asserted when the front panel TRIP LED is on
LED ALARM Asserted when the front panel ALARM LED is on
LED PICKUP Asserted when an element picks up and to turn PICKUP LED on
LED VOLTAGE Asserted when a voltage element involved and to turn VOLTAGE LED on
LED CURRENT Asserted when a current element involved and to turn CURRENT LED on
LED FREQUENCY Asserted when a frequency element involved and to turn FREQUENCY LED on
LED OTHER Asserted when a composite element involved and to turn OTHER LED on
LED PHASE A Asserted when phase A involved and to turn PHASE A LED on
LED PHASE B Asserted when phase B involved and to turn PHASE B LED on
LED PHASE C Asserted when phase C involved and to turn PHASE C LED on
LED NEUTRAL/GROUND Asserted when a neutral or ground element involved and to turn NEUTRAL/
GROUND LED on
LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on
Graphical front panel LED TROUBLE Asserted when the front panel TROUBLE LED is on
LED TEST MODE Asserted when the front panel TEST MODE LED is on
LED TRIP Asserted when the front panel TRIP LED is on
LED ALARM Asserted when the front panel ALARM LED is on
LED PICKUP Asserted when an element picks up and to turn Event Cause LED 1 on by
default
LED VOLTAGE Asserted when a voltage element involved and to turn Event Cause LED 2 on
by default
LED CURRENT Asserted when a current element involved and to turn Event Cause LED 3 on
by default
LED FREQUENCY Asserted when a frequency element involved and to turn Event Cause LED 4
on by default
LED OTHER Asserted when a composite element involved and to turn Event Cause LED 5
on by default
5 LED PHASE A
LED PHASE B
Asserted when phase A involved and to turn Event Cause LED 6 on by default
Asserted when phase B involved and to turn Event Cause LED 7 on by default
LED PHASE C Asserted when phase C involved and to turn Event Cause LED 8 on by default
LED NEUTRAL/GROUND Asserted when a neutral or ground element involved and to turn Event Cause
LED 9 on by default
LED INDICATORS: LED TEST IN PROGRESS An LED test has been initiated and has not finished
LED test
LED INDICATORS: LED USER 1 Asserted when user-programmable LED 1 is on
User-programmable
LEDs
Enhanced and basic
front panels
LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48
LED INDICATORS: EVENT CAUSE LED 1 Asserted when event cause LED 1 is on
User-programmable
EVENT CAUSE LED 2 to 9 Same operand as EVENT CAUSE LED 1
LEDs
Graphical front panel
PASSWORD ACCESS LOC SETG OFF Asserted when local setting access is disabled
SECURITY ACCESS LOC SETG ON Asserted when local setting access is enabled
ACCESS LOC CMND OFF Asserted when local command access is disabled
ACCESS LOC CMND ON Asserted when local command access is enabled
ACCESS REM SETG OFF Asserted when remote setting access is disabled
ACCESS REM SETG ON Asserted when remote setting access is enabled
ACCESS REM CMND OFF Asserted when remote command access is disabled
ACCESS REM CMND ON Asserted when remote command access is enabled
UNAUTHORIZED ACCESS Asserted when a password entry fails while accessing a password protected
level of the F60
UNAUTH FW ATTEMPT Firmware upgrade attempted when LOCK FIRMWARE setting is Enabled
LOC SET ACCS AUT OFF Dual-Permission local access settings authorization is off
LOC SET ACCS AUT ON Dual-Permission local access settings authorization is on
REM SET ACCS AUT OFF Dual-Permission remote access settings authorization is off
REM SET ACCS AUT ON Dual-Permission remote access settings authorization is on

5-244 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Operand type Operand syntax Operand description


PROCESS BUS PBEthPort-1 Offline Process Bus Module port 1 failure
MODULE RxSV1 On RxSV1 stream is online (messages are received and accepted)
(order code 85, 86, RxSV1 Off RxSV1 stream is offline (SV are received but not accepted or SV frames are
87) not received)
RxSV1 Lost On RxSV1 stream is completely lost (SV stream frames are not received)
RxSV1 Lost Off RxSV1 stream message delay is below the configured delay
RxSV1 Delay Alarm On RxSV1 stream message that delay exceeds the configured delay
RxSV1 Delay Alarm Off RxSV1 stream message that delay is below the configured delay
RxSV1 SimBit On RxSV1 messages are received with simulation bit TRUE, while "Accept Sim
GOOSE&SV" setting is Enabled
RxSV1 SimBit Off RxSV1 messages are received with Sim bit FALSE, or "Accept Sim GOOSE&SV"
is set to Disabled
RxSV1 SynChk Fail RxSV1 message that the synchronization source check failed
RxSV1 SynChk OK RxSV1 message synchronization source check successful
RxSV1 QualChk Fail RxSV1 message that at least one channel quality check failed
RxSV1 QualChk OK RxSV1 message that the quality check of all channels successful
Dlyd Processing On Analog data from at least one of the SV streams is delayed in oscillography
record
Dlyd Processing Off Analog data from none of the SV streams is delayed in Oscillography record
SV1 Processing Fail No frame received from RxSV1 stream or received sample processing failed
SV1 Processing OK Frame received from RxSV1 stream and sample successfully processed
ACBank1 Orig1 in Use ACBank1 is using Origin1 SV stream
ACBank1 Orig2 in Use ACBank1 is using Origin2 SV stream
SV TRBL PARTIAL BLK Partial blocking of UR elements applied due to SV stream trouble
SV TRBL GLOBAL BLK Global blocking of UR elements applied due to SV stream trouble
SV TRBL Cont Op BLKD Contact outputs are blocked due to SV stream trouble
RxGOOSE RxGOOSE 1 On Flag is set, logic=1
↓ ↓
RxGOOSE 64 On Flag is set, logic=1
RxGOOSE 1 Off

RxGOOSE 64 Off
Flag is set, logic=1

Flag is set, logic=1
5
<RxGOOSE Boolean1 ID> On Replace bracketed text with RxGOOSE Boolean1 status of "true"
<RxGOOSE DPS1 ID> Bad Replace bracketed text with RxGOOSE DPS1 status of "bad-state"
<RxGOOSE DPS1 ID> Interm Replace bracketed text with RxGOOSE DPS1 status is "intermediate-state"
<RxGOOSE DPS1 ID> Off Replace bracketed text with RxGOOSE DPS1 status is "off"
<RxGOOSE DPS1 ID> On Replace bracketed text with RxGOOSE DPS1 status is "on"
RxGOOSE Analog1 Expn St RxGOOSE Analog In1 Expression status
RxGOOSE INVLD ON One or more Rx GOOSE Inputs are received with Invalid quality
RxGOOSE QUES ON One or more Rx GOOSE Inputs are received with questionable quality
RESETTING RESET OP Reset command is operated (set by all three operands below)
RESET OP (COMMS) Communications source of the reset command
RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS  RESETTING menu) source of
the reset command
RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command
RESET ANCTR OP Reset annunciator command is operated (set by any operands below)
RESET ANCTR OP(OPRD) Reset operand (assigned in INPUTS/OUTPUTS  RESETTING
ANNUNCIATOR menu) source of the reset annunciator command
RESET ANCTR OP(MNUL) Reset manual (pushbutton or EnerVista software) source of the reset
annunciator command
GRAPHICAL FRONT ENABLE CTRL FROM GFP Controls enabled when operand assigned to Enable Controls From GFP
PANEL setting is ON. An Enable Control side pushbutton displays, which displays
other side pushbuttons.
Disabled otherwise, and Enable Control side pushbutton does not display.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-245


FLEXLOGIC CHAPTER 5: SETTINGS

Operand type Operand syntax Operand description


SELF-DIAGNOSTICS ANY MAJOR ERROR Any of the major self-test errors generated (major error)
(See Relay Self-tests ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
descriptions in ANY SELF-TESTS Any self-test errors generated (generic, any error)
Chapter 7: BATTERY FAIL The battery is weak or not functioning. Replace as outlined in the
Commands and Maintenance chapter.
Targets) CLOCK UNSYNCHRONIZED Relay is not synchronized to the international time standard
DIRECT DEVICE OFF A direct device is configured but not connected
DIRECT RING BREAK The Direct I/O settings is for a connection that is not in a ring
EQUIPMENT MISMATCH The configuration of modules does not match the stored order code
FLEXLOGIC ERR TOKEN A FlexLogic equation is incorrect
IRIG-B FAILURE "Bad IRIG-B Signal" self-test. See Chapter 7: Commands and Targets.
LATCHING OUT ERROR A difference is detected between the desired and actual latch contact state
MAINTENANCE ALERT A subset of the minor self-test errors generated, see Chapter 7
FIRST ETHERNET FAIL Link failure detected. See description in Chapter 7: Commands and Targets.
PROCESS BUS FAILURE See description in Chapter 7: Commands and Targets
PTP FAILURE “Bad PTP Signal” self-test as described in Chapter 7
RxGOOSE OFF One or more GOOSE messages are not being received
RRTD COMM FAIL See description in Chapter 7: Commands and Targets
SECOND ETHERNET FAIL See description in Chapter 7: Commands and Targets
THIRD ETHERNET FAIL See description in Chapter 7: Commands and Targets
SNTP FAILURE SNTP server is not responding
SYSTEM EXCEPTION See description in Chapter 7: Commands and Targets
TEMP MONITOR Monitors ambient temperature and maximum operating temperature
UNIT NOT PROGRAMMED The product SETUP > INSTALLATION > RELAYS SETTINGS setting is not
programmed
SETTING CHANGED Any device settings changed over any available interface; operand is
asserted for at least one second and then self-reset
PROCESS BUS PTP FAILURE No grandmaster clock available on any of the Process Bus Module ports
PB-CPU CLK MISMATCH Process Bus Module and main CPU clocks are free-running independently
and the clocks are deviating more than 100 micro seconds. Resets when the

5 PB CLOCK UNSYNCD
deviation is below 100 micro seconds.
Process Bus Module clock is free-running, that is, when both PTP
grandmaster clock on Process Bus Module and one pulse per second (PPS)
from main CPU are not available. Resets when any of the references is
available.
SIMULATION TxGOOSE SIM ON Sim bit enabled in all Tx GOOSE
IED IN SIM MODE ON Relay is in simulation mode and accepts simulated GOOSE and SV values
IED IN SIM MODE OFF Relay is not in simulation mode and does not accept simulated GOOSE and
SV values
TEMPERATURE TEMP MONITOR Asserted while the ambient temperature is greater than the maximum
MONITOR operating temperature (80°C)
USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position
PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position
PUSHBUTTONS ANY PB ON Any of 12 pushbuttons is in the “On” position
PUSHBUTTON 2 to 6, 12, 16, or 48 Same set of operands as PUSHBUTTON 1
depending on front panel

Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-30: FlexLogic gate characteristics
Gates Number of inputs Output is ‘1’ (= ON) if...
NOT 1 input is ‘0’
OR 2 to 16 any input is ‘1’
AND 2 to 16 all inputs are ‘1’
NOR 2 to 16 all inputs are ‘0’
NAND 2 to 16 any input is ‘0’
XOR 2 only one input is ‘1’

5-246 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Table 5-31: FlexLogic operators


Type Syntax Description Notes
Editor INSERT Insert a parameter in an equation list
DELETE Delete a parameter from an equation list
End END The first END encountered signifies the last entry in
the list of processed FlexLogic parameters
One-shot POSITIVE ONE SHOT One shot that responds to a positive going edge A ‘one shot’ refers to a single input gate that
generates a pulse in response to an edge on
NEGATIVE ONE SHOT One shot that responds to a negative going edge
the input. The output from a ‘one shot’ is
DUAL ONE SHOT One shot that responds to both the positive and True (positive) for only one pass through the
negative going edges FlexLogic equation. There is a maximum of
64 ‘one shots.’
Logic NOT Logical NOT Operates on the previous parameter
gate
OR(2) 2 input OR gate Operates on the 2 previous parameters
↓ ↓ ↓
OR(16) 16 input OR gate Operates on the 16 previous parameters
AND(2) 2 input AND gate Operates on the 2 previous parameters
↓ ↓ ↓
AND(16) 16 input AND gate Operates on the 16 previous parameters
NOR(2) 2 input NOR gate Operates on the 2 previous parameters
↓ ↓ ↓
NOR(16) 16 input NOR gate Operates on the 16 previous parameters
NAND(2) 2 input NAND gate Operates on the 2 previous parameters
↓ ↓ ↓
NAND(16) 16 input NAND gate Operates on the 16 previous parameters
XOR(2) 2 input Exclusive OR gate Operates on the 2 previous parameters
LATCH (S,R) Latch (set, reset): reset-dominant The parameter preceding LATCH(S,R) is the
reset input. The parameter preceding the
5
reset input is the set input.
Timer TIMER 1 Timer set with FlexLogic timer 1 settings The timer is started by the preceding
↓ ↓ parameter. The output of the timer is
TIMER 32 Timer set with FlexLogic timer 32 settings TIMER #.
Assign = Virt Op 1 Assigns previous FlexLogic operand to virtual The virtual output is set by the preceding
virtual ↓ output 1 parameter
output = Virt Op 256 ↓
Assigns previous FlexLogic operand to virtual
output 256

5.7.2 FlexLogic rules


When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules:
1. Operands must precede the operator that uses the operands as inputs.
2. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3. Assigning the output of an operator to a virtual output terminates the equation.
4. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once
only. If this rule is broken, a syntax error is declared.

5.7.3 FlexLogic evaluation


Each equation is evaluated in the ascending order in which the parameters have been entered.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-247


FLEXLOGIC CHAPTER 5: SETTINGS

FlexLogic provides built-in latches that by definition have a memory action, remaining in the set state after the set
input has been asserted. These built-in latches are reset dominant, meaning that if logical "1" is applied to both set
and reset entries simultaneously, then the output of the latch is logical "0." However, they are volatile, meaning that
they reset upon removal of control power.
When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any
new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically.
To implement FlexLogic using a graphical user interface, see the FlexLogic Design and Monitoring using Engineer
section in the previous chapter.

5.7.4 FlexLogic example


This section provides an example of logic implementation for a typical application. The sequence of steps is important to
minimize the work to develop the relay settings. Note that the example in the following figure demonstrates the procedure,
not to solve a specific application situation.
Note that there is also a graphical interface with which to draw logic and populate FlexLogic equation entries. See the
Engineer content at the end of the previous chapter.
In the example, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only a
part of the full set of equations used. When using FlexLogic, it is important to make a note of each virtual output used; a
virtual output designation (1 to 256) can be assigned only once.
Figure 5-115: Logic example

9LUWXDORXWSXW
VWDWH 2Q

5 9LUWXDORXWSXW
6HW
VWDWH 2Q
/DWFK
9LUWXDOLQSXW 25 5HVHW
VWDWH 2Q
;25
'LJLWDOHOHPHQW 7LPHU
VWDWH 3LFNXS 7LPH'HOD\ 2SHUDWHRXWSXW
25
RQGURSRXW UHOD\+
'LJLWDOHOHPHQW 7LPHU
PV
VWDWH 2SHUDWHG 7LPHGHOD\
$1' RQSLFNXS
PV
&RQWDFWLQSXW+F
VWDWH &ORVHG
$&'5

1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic
operators. If this is not possible, the logic must be altered until this condition is satisfied. Once done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If
the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25
inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs
from these two gates to AND(2).
Inspect each operator between the initial operands and final virtual outputs to determine if the output from the
operator is used as an input to more than one following operator. If so, the operator output must be assigned as a
virtual output.
For the example shown, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must therefore
be made a virtual output and assigned the next available number (that is, Virtual Output 3). The final output must also
be assigned to a virtual output as virtual output 4, which is programmed in the contact output section to operate relay
H1 (that is, contact output H1).
Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and
virtual output 4, shown as follows.

5-248 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Figure 5-116: Logic example with virtual outputs

Virtual output 1
state = On

Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
Digital element 1 OR #2 Virtual output 4
on dropout
state = Pickup
(200 ms)

Digital element 1 Timer 1


state = Operated Time delay
AND on pickup
(800 ms)
Contact input H1c
state = Closed Virtual output 3

827026A2.CDR

2. Prepare a logic diagram for the equation to produce virtual output 3, as this output is used as an operand in the virtual
output 4 equation (create the equation for every output that is used as an operand first, so that when these operands
are required they already have been evaluated and assigned to a specific virtual output). The logic for virtual output 3
is shown as follows with the final output assigned.
Figure 5-117: Logic for virtual output 3

Digital element 2 5
state= Operated

AND(2) Virtual output 3

Contact input H1c


state = Closed
827027A2.CDR

3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as
virtual output 3, shown as follows.
Figure 5-118: Logic for virtual output 4

9LUWXDORXWSXW
VWDWH 2Q

9LUWXDORXWSXW
6HW
VWDWH 2Q
/DWFK
25 5HVHW
9LUWXDOLQSXW
VWDWH 2Q 7LPHU
;25 7LPHGHOD\
25 9LUWXDORXWSXW
'LJLWDOHOHPHQW RQGURSRXW
VWDWH 3LFNXS
PV

7LPHU
9LUWXDORXWSXW 7LPHGHOD\
VWDWH 2Q RQSLFNXS
PV
&RQWDFWLQSXW+F
VWDWH &ORVHG
$&'5

4. Program the FlexLogic equation for virtual output 3 by translating the logic into available FlexLogic parameters. The
equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-249


FLEXLOGIC CHAPTER 5: SETTINGS

output end of the equation and work back towards the input, as shown in the following steps. It is also recommended
to list operator inputs from bottom to top. For demonstration, the final outputs are arbitrarily identified as parameter
99, and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic, it is suggested
that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared shown as follows.
Figure 5-119: FlexLogic worksheet

01
02
03
04
05

.....
97
98
99
827029A1.VSD

5. Following the procedure outlined, start with parameter 99, as follows:


– 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This
parameter is therefore "= Virt Op 3".
5 – 98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a
2-input AND so the parameter is “AND(2)”. Note that FlexLogic rules require that the number of inputs to most
types of operators must be specified to identify the operands for the gate. As the 2-input AND operates on the
two operands preceding it, these inputs must be specified, starting with the lower.
– 97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next
parameter is “NOT”. The NOT operator acts upon the operand immediately preceding it, so specify the inverter
input next.
– 96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to
be set when the contact is either open or closed. Assume for this example that the state is to be ON for a closed
contact. The operand is therefore “Cont Ip H1c On”.
– 95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital
element 2. This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order forms the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters produces the required logic by converting the set of
parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for
virtual output 3 diagram as a check.

5-250 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Figure 5-120: FlexLogic equation for virtual output 3

FlexLogic entry:
95
Dig Element 2 (DE2) OP
AND Virtual output 3
FlexLogic entry:
96
Cont Ip 2 On (H1c)
FlexLogic entry:
97
NOT
FlexLogic entry:
98
AND (2)
FlexLogic entry:
99
= Virt Op 3 (VO3)
827030A2.CDR

6. Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4.
– 99: The final output of the equation is virtual output 4, which is parameter “= Virt Op 4".
– 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for
the timer are established in the timer programming section.
– 97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
– 96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
– 95: The center input to OR #2 is operand “TIMER 1".
– 94: The input to timer 1 is operand “Virt Op 3 On".
– 93: The upper input to OR #2 is operand “LATCH (S,R)”.
– 92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR,
which is parameter “OR(4)”.
– 91: The lowest input to OR #1 is operand “Virt Op 3 On".
– 90: The input just above the lowest input to OR #1 is operand “XOR(2)”. 5
– 89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
– 88: The upper input to the XOR is operand “Virt Ip 1 On".
– 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
– 86: The upper input to OR #1 is operand “Virt Op 1 On".
– 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
Now check that the selection of parameters produce the required logic by converting the set of parameters into a
logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-251


FLEXLOGIC CHAPTER 5: SETTINGS

Figure 5-121: FlexLogic equation for virtual output 4


)OH[/RJLFHQWU\
 9LUW2S2Q 92
)OH[/RJLFHQWU\
 9LUW2S2Q 92
)OH[/RJLFHQWU\
 9LUW2S2Q 92
)OH[/RJLFHQWU\ 6HW
 /DWFK
9LUW,S2Q 9,
;25 25 5HVHW
)OH[/RJLFHQWU\
 'LJ(OHPHQW '( 3.3
)OH[/RJLFHQWU\
 ;25 ,QSXW
)OH[/RJLFHQWU\
 9LUW2S2Q 92
25 7 9LUWXDORXWSXW
)OH[/RJLFHQWU\
 25 ,QSXW
)OH[/RJLFHQWU\
 /DWFK 6HW5HVHW
)OH[/RJLFHQWU\
 9LUW2S2Q 92 7
)OH[/RJLFHQWU\
 7LPHU
)OH[/RJLFHQWU\
 &RQW,S2Q +F
)OH[/RJLFHQWU\
 25 ,QSXW
)OH[/RJLFHQWU\
 7LPHU
)OH[/RJLFHQWU\
 9LUW2S 92
$&'5

5 7. Now write the complete FlexLogic expression required to implement the logic, making an effort to assemble the
equation in an order where Virtual Outputs that are used as inputs to operators are created before needed. In cases
where a lot of processing is required to perform logic, this can be difficult to achieve, but in most cases does not cause
problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by
sequential processing emphasizes the necessity to test the performance of FlexLogic before it is placed in service.
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the following
order:
DIG ELEM 2 OP
Cont Ip H1c On
NOT
AND(2)
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In this expression, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of
feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up

5-252 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

to the first "END" operator.


The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.

5.7.5 FlexLogic equation editor


SETTINGS  FLEXLOGIC  FLEXLOGIC EQUATION EDITOR
 FLEXLOGIC FLEXLOGIC ENTRY 1 Range: FlexLogic operands
 EQUATION EDITOR  END

FLEXLOGIC ENTRY 1024 Range: FlexLogic operands
 END

There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a “Disabled”
element is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
There are two ways to create, edit and maintain the FlexLogic equations:
1. Using the FlexLogic Equation Editor available at FlexLogic > FlexLogic Equation Editor
2. Using the Logic Designer available at Engineer > Logic Designer

EnerVista Engineer is only available through the offline window of the EnerVista UR Setup.
FlexLogic Equation Editor and Logic Designer are designed to be mutually exclusive as using them interchangeably
to create, edit and maintain the FlexLogic equations may cause inconsistencies in the resulting equations. The user
is recommended to use only one of the two methods throughout the process. 5
Please refer to the FlexLogic design using Engineer section in the Interfaces chapter for more information.

5.7.6 FlexLogic timers


SETTINGS  FLEXLOGIC  FLEXLOGIC TIMERS  FLEXLOGIC TIMER 1(64)
 FLEXLOGIC TIMER 1 Range: millisecond, second, minute
 TIMER 1  TYPE: millisecond

TIMER 1 PICKUP Range: 0 to 60000 in steps of 1


 DELAY: 0

TIMER 1 DROPOUT Range: 0 to 60000 in steps of 1


 DELAY: 0

There are 64 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE — Selects the time measurement unit.
TIMER 1 PICKUP DELAY — Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY — Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."

5.7.7 FlexElements
SETTINGS  FLEXLOGIC  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1 FLEXELEMENT 1 Range: Disabled, Enabled
  FUNCTION: Disabled

FLEXELEMENT 1 NAME: Range: up to six alphanumeric characters


 FxE 1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-253


FLEXLOGIC CHAPTER 5: SETTINGS

FLEXELEMENT 1 +IN: Range: Off, any analog actual value parameter


 Off

FLEXELEMENT 1 -IN: Range: Off, any analog actual value parameter


 Off

FLEXELEMENT 1 INPUT Range: SIGNED, ABSOLUTE


 MODE: SIGNED

FLEXELEMENT 1 COMP Range: LEVEL, DELTA


 MODE: LEVEL

FLEXELEMENT 1 Range: OVER, UNDER


 DIRECTION: OVER

FLEXELEMENT 1 Range: –90.000 to 90.000 pu in steps of 0.001


 PICKUP: 1.000 pu

FLEXELEMENT 1 Range: 0.1 to 50.0% in steps of 0.1


 HYSTERESIS: 3.0%

FLEXELEMENT 1 dt Range: Milliseconds, Seconds, Minutes


 UNIT: Milliseconds

FLEXELEMENT 1 dt: Range: 20 to 86400 in steps of 1


 20

FLEXELEMENT 1 PKP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

FLEXELEMENT 1 RST Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

5  FLEXELEMENT 1 BLK:
Off
Range: FlexLogic operand

FLEXELEMENT 1 Range: Self-reset, Disabled, Latched


 TARGET: Self-reset

FLEXELEMENT 1 Range: Disabled, Enabled


 EVENTS: Disabled

A FlexElement is a universal comparator used to monitor any analog actual value calculated by the relay or a net
difference of any two analog actual values of the same type. The effective operating signal can be treated as a signed
number or its absolute value can be used.
FlexElements run every half power cycle (every four protection passes).
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold, as
per your choice.

5-254 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Figure 5-122: FlexElement logic

6(77,1*
6(77,1*
)/(;(/(0(17
)81&7,21 )/(;(/(0(17,1387
02'(
(QDEOHG  )/(;(/(0(17&203
02'(
)/(;(/(0(17
',5(&7,21
6(77,1*
)/(;(/(0(173,&.83
)/(;(/(0(17%/. )/(;(/(0(17,1387
$1' +<67(5(6,6
2II 
)/(;(/(0(17GW81,7 6(77,1*
6(77,1* )/(;(/(0(173.3
)/(;(/(0(17GW '(/$<
)/(;(/(0(17,1 )/(;(/(0(17567
581 '(/$<
$FWXDO9DOXH )/(;/2*,&23(5$1'
 W3.3
)/(;(/(0(17,1 )[(23
 W567
$FWXDO9DOXH )[('32
)[(3.3

$&78$/9$/8(
)OH[(OHPHQW2S6LJ
$&'5

FLEXELEMENT 1 +IN — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if
this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element
does not assert its output operands.

Filter the InputPlus or InputMinus field in the software by double-clicking it, then entering a value.
5

FLEXELEMENT 1 –IN — Specifies the second (inverted) input to the FlexElement. Zero is assumed as the input if this setting is
set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not
assert its output operands. This input is used to invert the signal if needed for convenience, or to make the element
respond to a differential signal, such as for a top-bottom oil temperature differential alarm. The element does not operate
if the two input signals are of different types, for example if one tries to use active power and phase angle to build the
effective operating signal.
The element responds directly to the differential signal if the FLEXELEMENT 1 INPUT MODE setting is set to “Signed” The
element responds to the absolute value of the differential signal if this setting is set to “Absolute.” Sample applications for
the “Absolute” setting include monitoring the angular difference between two phasors with a symmetrical limit angle in
both directions, monitoring power regardless of its direction, or monitoring a trend.
The element responds directly to its operating signal—as defined by the FLEXELEMENT 1 +IN, FLEXELEMENT 1 –IN and
FLEXELEMENT 1 INPUT MODE settings—if the FLEXELEMENT 1 COMP MODE setting is set to “Level.” The element responds to the
rate of change of its operating signal if the FLEXELEMENT 1 COMP MODE setting is set to “Delta.” In this case, the
FLEXELEMENT 1 dt UNIT and FLEXELEMENT 1 dt settings specify how the rate of change is derived.
FLEXELEMENT 1 DIRECTION — Enables the relay to respond to either high or low values of the operating signal. The following
figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP, and FLEXELEMENT 1 HYSTERESIS
settings.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-255


FLEXLOGIC CHAPTER 5: SETTINGS

Figure 5-123: FlexElement direction, pickup, and hysteresis

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 2YHU

+<67(5(6,6 RI3,&.83

3,&.83
)OH[(OHPHQW  6LJ2S

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 8QGHU

+<67(5(6,6 RI3,&.83

)OH[(OHPHQW  6LJ2S
3,&.83

$&'5

In conjunction with the FLEXELEMENT 1 INPUT MODE setting, the element can be programmed to provide two extra
characteristics, as shown in the following figure.

5-256 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

Figure 5-124: FlexElement input mode setting

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 2YHU
)/(;(/(0(17,1387
02'( 6LJQHG

)OH[(OHPHQW2S6LJ

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 2YHU
)/(;(/(0(17,1387
02'( $EVROXWH

)OH[(OHPHQW2S6LJ

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 8QGHU
)/(;(/(0(17,1387
02'( 6LJQHG 5
)OH[(OHPHQW2S6LJ

)/(;(/(0(173.3

)/(;(/(0(17
',5(&7,21 8QGHU
)/(;(/(0(17,1387
02'( $EVROXWH

)OH[(OHPHQW2S6LJ
$&'5

FLEXELEMENT 1 PICKUP — This setting specifies the operating threshold for the effective operating signal of the element. If
set to “Over,” the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under,” the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
When using FlexElements for Voltage Elements, 1 pu is always equal to phase to ground voltage nominal secondary
voltage, even if you select a phase to phase voltage as an operating quantity.
FLEXELEMENT 1 HYSTERESIS — This setting controls the element dropout. Notice that both the operating signal and the
pickup threshold can be negative, facilitating applications such as reverse power alarm protection. The FlexElement can be
programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP setting is entered in
per-unit values using the following definitions of the base units.
Table 5-32: FlexElement base units
Unit Description
BREAKER ACC ARCING AMPS BASE = 2000 kA2 × cycle
(Brk X Acc Arc Amp A, B, and C)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-257


FLEXLOGIC CHAPTER 5: SETTINGS

Unit Description
BREAKER ARCING AMPS BASE = 1 kA2 × cycle
(Brk X Arc Amp A, B, and C)
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs
DELTA TIME BASE = 1 µs
FAULT LOCATION BASE = Line Length as specified in Fault Report
FREQUENCY fBASE = 1 Hz
FREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/s
PHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SENSITIVE DIR POWER PBASE = maximum value of 3 × VBASE × IBASE for the +IN and –IN inputs of the sources configured
(Sns Dir Power) for the sensitive power directional element(s).
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE × IBASE for the +IN and –IN inputs
SOURCE THD & HARMONICS BASE = 1%
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)

5 FLEXELEMENT 1 HYSTERESIS — This setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement Direction, Pickup, and Hysteresis diagram.
FLEXELEMENT 1 dt UNIT — Specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 dt — Specifies duration of the time interval for the rate of change mode of operation. This setting is
applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 PKP DELAY — Specifies the pickup delay of the element.
FLEXELEMENT 1 RST DELAY — Specifies the reset delay of the element.

5.7.8 Non-volatile latches

SETTINGS  FLEXLOGIC  NON-VOLATILE LATCHES


 NON-VOLATILE  LATCH 1
 LATCH  

 LATCH 2
 

 ...
 

  LATCH 16

SETTINGS  FLEXLOGIC  NON-VOLATILE LATCHES  LATCH 1 (16)


 LATCH 1 LATCH 1 Range: Disabled, Enabled
  FUNCTION: Disabled

LATCH 1 ID: Range: up to 20 alphanumeric characters


 NV Latch 1

5-258 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS FLEXLOGIC

LATCH 1 TYPE: Range: Reset Dominant, Set Dominant


 Reset Dominant

LATCH 1 SET: Range: FlexLogic operand


 Off

LATCH 1 RESET: Range: FlexLogic operand


 Off

LATCH 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

LATCH 1 Range: Disabled, Enabled


 EVENTS: Disabled

The non-volatile latches provide a permanent logical flag that is stored safely and do not reset upon restart after the relay
is powered down. Typical applications include sustaining operator commands or permanently blocking relay functions,
such as Autorecloser, until a deliberate interface action resets the latch.
LATCH 1 TYPE — This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET — If asserted, the specified FlexLogic operands 'sets' Latch 1.
LATCH 1 RESET — If asserted, the specified FlexLogic operand 'resets' Latch 1.

Figure 5-125: Non-volatile latch operation table (N = 1 to 16) and logic


6(77,1* 6(77,1*

/$7&+)81&7,21 /$7&+7<3(

(QDEOHG  581

6(77,1*
5
/$7&+6(7
)/(;/2*,&23(5$1'
2II  6(7 /$7&+21
/$7&+2))
6(77,1*

/$7&+5(6(7

2II  5(6(7 $&'5

Latch n type Latch n set Latch n reset Latch n on Latch n off


Reset Dominant ON OFF ON OFF
OFF OFF Previous State Previous State
ON ON OFF ON
OFF ON OFF ON
Set Dominant ON OFF ON OFF
ON ON ON OFF
OFF OFF Previous State Previous State
OFF ON OFF ON

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-259


GROUPED ELEMENTS CHAPTER 5: SETTINGS

5.8 Grouped elements


5.8.1 Overview
Each protection element can be assigned up to six sets of settings with designations 1 to 6. The performance of these
elements is defined by the active setting group at a given time. Multiple setting groups allow the user to conveniently
change protection settings for different operating situations (for example, altered power system configuration or season of
the year). The active setting group can be preset or selected in the SETTING GROUPS menu (see the Control Elements section
later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.

5.8.2 Setting group 1


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)
 SETTING GROUP 1  LOAD ENCROACHMENT See below
  

 PHASE CURRENT See page 5-262


 

 NEUTRAL CURRENT See page 5-275


 

 WATTMETRIC See page 5-288


  GROUND FAULT

 GROUND CURRENT See page 5-292


5  

 NEGATIVE SEQUENCE See page 5-302


  CURRENT

 BREAKER FAILURE See page 5-308


 

 VOLTAGE ELEMENTS See page 5-317


 

 POWER See page 5-327


 

Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.

5.8.3 Load encroachment


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  LOAD ENCROACHMENT
 LOAD ENCROACHMENT LOAD ENCROACHMENT Range: Disabled, Enabled
  FUNCTION: Disabled

LOAD ENCROACHMENT Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

LOAD ENCROACHMENT Range: 0.004 to 3.000 pu in steps of 0.001


 MIN VOLT: 0.250 pu

LOAD ENCROACHMENT Range: 0.02 to 250.00 ohms in steps of 0.01


 REACH: 1.00 Ω

5-260 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

LOAD ENCROACHMENT Range: 5 to 50° in steps of 1


 ANGLE: 30°

LOAD ENCROACHMENT Range: 0.000 to 65.535 s in steps of 0.001


 PKP DELAY: 0.000 s

LOAD ENCROACHMENT Range: 0.000 to 65.535 s in steps of 0.001


 RST DELAY: 0.000 s

LOAD ENCRMNT BLK: Range: FlexLogic operand


 Off

LOAD ENCROACHMENT Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

LOAD ENCROACHMENT Range: Disabled, Enabled


 EVENTS: Disabled

The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic as
shown in the figure.
Figure 5-126: Load encroachment characteristic

1>7<5
5
B5138 B5138

B
1>7<5
<?145>3B?138=5>D <?145>3B?138=5>D
?@5B1D5 ?@5B1D5

("'($&1!34B

The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements, such as distance or phase overcurrent. The following figure shows an effect of
the load encroachment characteristics used to block the quadrilateral distance element.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-261


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Figure 5-127: Load encroachment applied to distance element

(#''#!1!34B

LOAD ENCROACHMENT MIN VOLT — This setting specifies the minimum positive-sequence voltage required for operation of
the element. When the voltage is below this threshold, a blocking signal is not asserted by the element. When selecting
this setting, remember that the F60 measures the phase-to-ground sequence voltages regardless of the VT connection.
The nominal VT secondary voltage as specified with the SYSTEM SETUP  AC INPUTS  VOLTAGE BANK X5  PHASE VT
SECONDARY setting is the per-unit base for this setting.
LOAD ENCROACHMENT REACH — This setting specifies the resistive reach of the element as shown in the Load

5 Encroachment Characteristic diagram. Enter this setting in secondary ohms and calculate it as the positive-sequence
resistance seen by the relay under maximum load conditions and unity power factor.
LOAD ENCROACHMENT ANGLE — This setting specifies the size of the blocking region as shown on the Load Encroachment
Characteristic diagram and applies to the positive-sequence impedance.
Figure 5-128: Load encroachment logic
SETTING
LOAD ENCROACHMENT
FUNCTION:
Enabled=1 SETTINGS
LOAD ENCROACHMENT
SETTING REACH:
SETTINGS
LOAD ENCROACHMENT
LOAD ENCRMNT BLK:
ANGLE: LOAD ENCROACHMENT
Off=0 RUN PKP DELAY:
AND FLEXLOGIC OPERANDS
LOAD ENCROACHMENT
LOAD ENCHR PKP
RST DELAY:
SETTING SETTING LOAD ENCHR DPO
Load Encroachment t PKP
LOAD ENCROACHMENT LOAD ENCROACHMENT t RST LOAD ENCHR OP
SOURCE: MIN VOLT: Characteristic
Pos Seq Voltage (V_1) V_1 > Pickup
Pos Seq Current (I_1)
827847A3.CDR

5.8.4 Phase current

5.8.4.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT
 PHASE CURRENT  PHASE TOC1 See page 5-268
  

5-262 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

 PHASE TOC6
 

 PHASE IOC1 See page 5-270


 

 PHASE IOC8
 

 PHASE See page 5-271


  DIRECTIONAL 1

 PHASE
  DIRECTIONAL 2

5.8.4.2 Inverse TOC curve characteristics


The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I2t standard
curve shapes. This allows for simplified coordination with downstream devices.
If none of these curve shapes is adequate, FlexCurves can be used to customize the inverse time curve characteristics. The
definite time curve is also an option that can be appropriate if only simple protection is required.
Table 5-33: Overcurrent curve types
IEEE IEC GE type IAC Other
IEEE Extremely Inverse IEC Curve A (BS142) IAC Extremely Inverse I2t
IEEE Very Inverse IEC Curve B (BS142) IAC Very Inverse FlexCurves A, B, C, and D
IEEE Moderately Inverse IEC Curve C (BS142)
IEC Short Inverse
IAC Inverse
IAC Short Inverse
Recloser Curves
Definite Time
5
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed.” The
“Instantaneous” selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the
relay must coordinate with electromechanical relays.
The URs calculate operate time corresponding to the values in the range of 1.03 to 20 multiples of the pickup current.
Above 20 multiples of the pickup current, URs clamp the operate time to the value at a multiple of 20, resulting in the flat
part of the characteristics. Reset time is calculated in the range of 0 to 0.97 multiples of the pickup current.

IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse curves. The IEEE curves are derived from the operate and reset time equations.

A tr
------------------------------- + B -------------------------------
-
T = TDM u § --------------· p – 1
I , T RESET = TDM u I 2 Eq. 5-8
© I pickup¹ 1 – §© -------------- ·¹
I pickup

where

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-263


GROUPED ELEMENTS CHAPTER 5: SETTINGS

T = operate time (in seconds)


TDM = Multiplier setting
I = input current
Ipickup = Pickup Current setting
A, B, p = constants defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
tr = characteristic constant defined in the table
Table 5-34: IEEE inverse time curve constants
IEEE curve shape A B p tr
IEEE Extremely Inverse 28.2 0.1217 2.0000 29.1
IEEE Very Inverse 19.61 0.491 2.0000 21.6
IEEE Moderately Inverse 0.0515 0.1140 0.02000 4.85

Table 5-35: IEEE curve trip times (in seconds)


Multiplier Current ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IEEE Extremely Inverse
0.5 11.341 4.761 1.823 1.001 0.648 0.464 0.355 0.285 0.237 0.203
1.0 22.682 9.522 3.647 2.002 1.297 0.927 0.709 0.569 0.474 0.407
2.0 45.363 19.043 7.293 4.003 2.593 1.855 1.418 1.139 0.948 0.813
4.0 90.727 38.087 14.587 8.007 5.187 3.710 2.837 2.277 1.897 1.626
6.0 136.090 57.130 21.880 12.010 7.780 5.564 4.255 3.416 2.845 2.439
5 8.0 181.454 76.174 29.174 16.014 10.374 7.419 5.674 4.555 3.794 3.252
10.0 226.817 95.217 36.467 20.017 12.967 9.274 7.092 5.693 4.742 4.065
IEEE Very Inverse
0.5 8.090 3.514 1.471 0.899 0.654 0.526 0.450 0.401 0.368 0.345
1.0 16.179 7.028 2.942 1.798 1.308 1.051 0.900 0.802 0.736 0.689
2.0 32.358 14.055 5.885 3.597 2.616 2.103 1.799 1.605 1.472 1.378
4.0 64.716 28.111 11.769 7.193 5.232 4.205 3.598 3.209 2.945 2.756
6.0 97.074 42.166 17.654 10.790 7.849 6.308 5.397 4.814 4.417 4.134
8.0 129.432 56.221 23.538 14.387 10.465 8.410 7.196 6.418 5.889 5.513
10.0 161.790 70.277 29.423 17.983 13.081 10.513 8.995 8.023 7.361 6.891
IEEE Moderately Inverse
0.5 3.220 1.902 1.216 0.973 0.844 0.763 0.706 0.663 0.630 0.603
1.0 6.439 3.803 2.432 1.946 1.688 1.526 1.412 1.327 1.260 1.207
2.0 12.878 7.606 4.864 3.892 3.377 3.051 2.823 2.653 2.521 2.414
4.0 25.756 15.213 9.729 7.783 6.753 6.102 5.647 5.307 5.041 4.827
6.0 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241
8.0 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654
10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068

5-264 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

IEC curves
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The IEC curves are derived by the operate and reset time
equations.

K tr
----------------------------------- ----------------------------------
-
T = TDM u I e I pickup E – 1 , T RESET = TDM u 1 – I e I 2 Eq. 5-9
pickup

where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
Ipickup = Pickup Current setting
K, E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-36: IEC (BS) inverse time curve constants
IEC (BS) curve shape K E tr
IEC Curve A (BS142) 0.140 0.020 9.7
IEC Curve B (BS142) 13.500 1.000 43.2
IEC Curve C (BS142) 80.000 2.000 58.2
IEC Short Inverse 0.050 0.040 0.500

Table 5-37: IEC curve trip times (in seconds)


5
Multiplier Current ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IEC Curve A
0.05 0.860 0.501 0.315 0.249 0.214 0.192 0.176 0.165 0.156 0.149
0.10 1.719 1.003 0.630 0.498 0.428 0.384 0.353 0.330 0.312 0.297
0.20 3.439 2.006 1.260 0.996 0.856 0.767 0.706 0.659 0.623 0.594
0.40 6.878 4.012 2.521 1.992 1.712 1.535 1.411 1.319 1.247 1.188
0.60 10.317 6.017 3.781 2.988 2.568 2.302 2.117 1.978 1.870 1.782
0.80 13.755 8.023 5.042 3.984 3.424 3.070 2.822 2.637 2.493 2.376
1.00 17.194 10.029 6.302 4.980 4.280 3.837 3.528 3.297 3.116 2.971
IEC Curve B
0.05 1.350 0.675 0.338 0.225 0.169 0.135 0.113 0.096 0.084 0.075
0.10 2.700 1.350 0.675 0.450 0.338 0.270 0.225 0.193 0.169 0.150
0.20 5.400 2.700 1.350 0.900 0.675 0.540 0.450 0.386 0.338 0.300
0.40 10.800 5.400 2.700 1.800 1.350 1.080 0.900 0.771 0.675 0.600
0.60 16.200 8.100 4.050 2.700 2.025 1.620 1.350 1.157 1.013 0.900
0.80 21.600 10.800 5.400 3.600 2.700 2.160 1.800 1.543 1.350 1.200
1.00 27.000 13.500 6.750 4.500 3.375 2.700 2.250 1.929 1.688 1.500
IEC Curve C
0.05 3.200 1.333 0.500 0.267 0.167 0.114 0.083 0.063 0.050 0.040
0.10 6.400 2.667 1.000 0.533 0.333 0.229 0.167 0.127 0.100 0.081
0.20 12.800 5.333 2.000 1.067 0.667 0.457 0.333 0.254 0.200 0.162
0.40 25.600 10.667 4.000 2.133 1.333 0.914 0.667 0.508 0.400 0.323
0.60 38.400 16.000 6.000 3.200 2.000 1.371 1.000 0.762 0.600 0.485

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-265


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Multiplier Current ( I / Ipickup)


(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
0.80 51.200 21.333 8.000 4.267 2.667 1.829 1.333 1.016 0.800 0.646
1.00 64.000 26.667 10.000 5.333 3.333 2.286 1.667 1.270 1.000 0.808
IEC Short Inverse
0.05 0.153 0.089 0.056 0.044 0.038 0.034 0.031 0.029 0.027 0.026
0.10 0.306 0.178 0.111 0.088 0.075 0.067 0.062 0.058 0.054 0.052
0.20 0.612 0.356 0.223 0.175 0.150 0.135 0.124 0.115 0.109 0.104
0.40 1.223 0.711 0.445 0.351 0.301 0.269 0.247 0.231 0.218 0.207
0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311
0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415
1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518

IAC curves
The curves for the General Electric type IAC relay family are derived from the formulae:

§ B D E ·
T = TDM u ¨ A + --------------------------- + ---------------------------------2 + ---------------------------------3¸ tr
, T RESET = TDM u ---------------------------- Eq. 5-10
I e I – C I e I pkp – C I e I pkp – C ¹ -
© pkp 2
1 – I e I pkp

where
T = operate time (in seconds)
5 TDM = Multiplier setting
I = Input current
Ipkp = Pickup Current setting
A to E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-38: GE type IAC inverse time curve constants
IAC curve shape A B C D E tr
IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse 0.0900 0.7955 0.1000 –1.2885 7.9586 4.678
IAC Inverse 0.2078 0.8630 0.8000 –0.4180 0.1947 0.990
IAC Short Inverse 0.0428 0.0609 0.6200 –0.0010 0.0221 0.222

Table 5-39: GE type IAC curve trip times


Multiplier Current ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IAC Extremely Inverse
0.5 1.699 0.749 0.303 0.178 0.123 0.093 0.074 0.062 0.053 0.046
1.0 3.398 1.498 0.606 0.356 0.246 0.186 0.149 0.124 0.106 0.093
2.0 6.796 2.997 1.212 0.711 0.491 0.372 0.298 0.248 0.212 0.185
4.0 13.591 5.993 2.423 1.422 0.983 0.744 0.595 0.495 0.424 0.370
6.0 20.387 8.990 3.635 2.133 1.474 1.115 0.893 0.743 0.636 0.556
8.0 27.183 11.987 4.846 2.844 1.966 1.487 1.191 0.991 0.848 0.741
10.0 33.979 14.983 6.058 3.555 2.457 1.859 1.488 1.239 1.060 0.926
IAC Very Inverse
0.5 1.451 0.656 0.269 0.172 0.133 0.113 0.101 0.093 0.087 0.083

5-266 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Multiplier Current ( I / Ipickup)


(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
1.0 2.901 1.312 0.537 0.343 0.266 0.227 0.202 0.186 0.174 0.165
2.0 5.802 2.624 1.075 0.687 0.533 0.453 0.405 0.372 0.349 0.331
4.0 11.605 5.248 2.150 1.374 1.065 0.906 0.810 0.745 0.698 0.662
6.0 17.407 7.872 3.225 2.061 1.598 1.359 1.215 1.117 1.046 0.992
8.0 23.209 10.497 4.299 2.747 2.131 1.813 1.620 1.490 1.395 1.323
10.0 29.012 13.121 5.374 3.434 2.663 2.266 2.025 1.862 1.744 1.654
IAC Inverse
0.5 0.578 0.375 0.266 0.221 0.196 0.180 0.168 0.160 0.154 0.148
1.0 1.155 0.749 0.532 0.443 0.392 0.360 0.337 0.320 0.307 0.297
2.0 2.310 1.499 1.064 0.885 0.784 0.719 0.674 0.640 0.614 0.594
4.0 4.621 2.997 2.128 1.770 1.569 1.439 1.348 1.280 1.229 1.188
6.0 6.931 4.496 3.192 2.656 2.353 2.158 2.022 1.921 1.843 1.781
8.0 9.242 5.995 4.256 3.541 3.138 2.878 2.695 2.561 2.457 2.375
10.0 11.552 7.494 5.320 4.426 3.922 3.597 3.369 3.201 3.072 2.969
IAC Short Inverse
0.5 0.072 0.047 0.035 0.031 0.028 0.027 0.026 0.026 0.025 0.025
1.0 0.143 0.095 0.070 0.061 0.057 0.054 0.052 0.051 0.050 0.049
2.0 0.286 0.190 0.140 0.123 0.114 0.108 0.105 0.102 0.100 0.099
4.0 0.573 0.379 0.279 0.245 0.228 0.217 0.210 0.204 0.200 0.197
6.0
8.0
0.859
1.145
0.569
0.759
0.419
0.559
0.368
0.490
0.341
0.455
0.325
0.434
0.314
0.419
0.307
0.409
0.301
0.401
0.296
0.394
5
10.0 1.431 0.948 0.699 0.613 0.569 0.542 0.524 0.511 0.501 0.493

I2t curves
The I2t curves are derived as follows:

100 100
----------------------- -------------------------
I · 2 , T RESET = TDM u § I · –2
T = TDM u § ------------- Eq. 5-11
- --------------
© I pickup ¹ © I pickup ¹

where
T = Operate time (in seconds)
TDM = Multiplier setting
I = Input current
Ipickup = Pickup Current setting
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)

Table 5-40: I2t curve trip times


Multiplier Current ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
0.01 0.44 0.25 0.11 0.06 0.04 0.03 0.02 0.02 0.01 0.01
0.10 4.44 2.50 1.11 0.63 0.40 0.28 0.20 0.16 0.12 0.10
1.00 44.44 25.00 11.11 6.25 4.00 2.78 2.04 1.56 1.23 1.00
10.00 444.44 250.00 111.11 62.50 40.00 27.78 20.41 15.63 12.35 10.00
100.00 4444.4 2500.0 1111.1 625.00 400.00 277.78 204.08 156.25 123.46 100.00
600.00 26666.7 15000.0 6666.7 3750.0 2400.0 1666.7 1224.5 937.50 740.74 600.00

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-267


GROUPED ELEMENTS CHAPTER 5: SETTINGS

FlexCurves
FlexCurves are described in the FlexCurves section later in this chapter. The curve shapes for the FlexCurves are derived
from the formulae:

I I
T = TDM u FlexCurve Time at §© --------------·¹ when § --------------· t 1.00
© I pickup¹
I pickup Eq. 5-12

I I
T RESET = TDM u FlexCurve Time at §© --------------·¹ when § --------------· d 0.98
© I pickup¹
I pickup Eq. 5-13

where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)

Definite time curve


The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from
instantaneous to 600.00 seconds in steps of 10 ms. The definite time curve shapes are defined as follows:

T = TDM in seconds, when I > I pickup Eq. 5-14


5
T RESET = TDM in seconds Eq. 5-15

where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)

Recloser curves
The F60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section
earlier in this chapter for details.

5.8.4.3 Phase time overcurrent (ANSI 51P, IEC PTOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE TOC1(6)
 PHASE TOC 1 PHASE TOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

PHASE TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

PHASE TOC1 Range: Phasor, RMS


 INPUT: Phasor

PHASE TOC1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

PHASE TOC1 Range: see Overcurrent Curve Types table


 CURVE: IEEE Mod Inv

5-268 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

PHASE TOC1 Range: 0.00 to 600.00 in steps of 0.01


 TD MULTIPLIER: 1.00

PHASE TOC1 Range: Instantaneous, Timed


 RESET: Instantaneous

PHASE TOC1 VOLTAGE Range: Disabled, Enabled


 RESTRAINT: Disabled

PHASE TOC1 BLOCK A: Range: FlexLogic operand


 Off

PHASE TOC1 BLOCK B: Range: FlexLogic operand


 Off

PHASE TOC1 BLOCK C: Range: FlexLogic operand


 Off

PHASE TOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PHASE TOC1 Range: Disabled, Enabled


 EVENTS: Disabled

The phase time overcurrent element can provide a specified time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental
phasor magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times, and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator clears immediately.
5
The PHASE TOC1 PICKUP setting can be reduced dynamically by a voltage restraint feature (when enabled). This is
accomplished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic
curve (see the figure); the pickup level is calculated as Mvr times the PHASE TOC1 PICKUP setting. If the voltage restraint
feature is disabled, the pickup level always remains at the setting value.
Figure 5-129: Phase time overcurrent voltage restraint characteristic
Multiplier for Pickup Current

1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
VOLTAGE RESTRAINT CHARACTERISTIC FOR PHASE TIME O/C
818784A4.CDR

FUNCTION — This setting enables and disables the phase time overcurrent protection element.
SIGNAL SOURCE — Selects the signal source for the phase time overcurrent protection element.
INPUT — Selects how phase current input quantities are interpreted by the F60. Inputs can be selected as fundamental
phasor magnitudes or total waveform RMS magnitudes as required by the application.
PICKUP — Specifies the phase time overcurrent pickup level in per-unit values.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-269


GROUPED ELEMENTS CHAPTER 5: SETTINGS

CURVE — Selects the time inverse overcurrent curve style.


TD MULTIPLIER — When TOC1 CURVE setting is set to Definite Time, this setting defines time delay to element pickup. When
TOC1 CURVE setting is set to any inverse time curve, this setting defines inverse curve multiplier, used in the chosen curve
equation.
RESET — The “Instantaneous” reset method is intended for applications with other relays, such as most static relays, which
set the energy capacity directly to zero when the current falls below the reset threshold. The “Timed” reset method can be
used where the relay must coordinate with electromechanical relays.
VOLTAGE RESTRAINT — Enables and disables the phase time overcurrent voltage restraint feature.
BLOCK A — Assertion of the operand assigned to this setting blocks phase A of the phase time overcurrent element.
EVENTS — Enables and disables the logging of phase time overcurrent events in the sequence of events recorder.

Figure 5-130: Phase time overcurrent 1 logic


SETTING
PHASE TOC1
FUNCTION:
Enabled=1

SETTING
PHASE TOC1
BLOCK-A :
Off=0

SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:

5
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled

AND PHASE TOC1 DPO

827072A5.CDR

5.8.4.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE IOC 1(8)
 PHASE IOC 1 PHASE IOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

PHASE IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

PHASE IOC1 Range: 0.005 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

PHASE IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

5-270 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

PHASE IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

PHASE IOC1 BLOCK A: Range: FlexLogic operand


 Off

PHASE IOC1 BLOCK C: Range: FlexLogic operand
 Off

PHASE IOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PHASE IOC1 Range: Disabled, Enabled


 EVENTS: Disabled

The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude.
FUNCTION — This setting enables and disables the phase instantaneous overcurrent protection element.
SOURCE — Selects the signal source for the phase instantaneous overcurrent protection element.
PICKUP — Specifies the phase instantaneous overcurrent pickup level in per-unit values.
DELAY —Delays the assertion of the PHASE IOC OP operands. It is used to achieve timing coordination with other
elements and relays.
RESET DELAY — Specifies a delay for the reset of the phase instantaneous overcurrent element between the operate output
state and the return to logic 0 after the input passes outside the defined pickup range. This setting is used to ensure that
the relay output contacts are closed long enough to ensure reception by downstream equipment.
BLOCK A — Assertion of the operand assigned to this setting block’s phase A of the phase instantaneous overcurrent
element.
5
EVENTS — Enables and disables the logging of phase instantaneous overcurrent events in the sequence of events recorder.

Figure 5-131: Phase instantaneous overcurrent 1 logic

SETTINGS FLEXLOGIC OPERANDS


SETTING
SETTING Pickup Delay PHASE IOC1 A PKP
Function
Pickup Reset Delay PHASE IOC1 A DPO
AND RUN TPKP PHASE IOC1 B PKP
1 = Enabled
IA > Pickup PHASE IOC1 B DPO
TRST PHASE IOC1 C PKP
AND RUN TPKP PHASE IOC1 C DPO
SETTING
Source IB > Pickup
TRST
= IA FLEXLOGIC OPERANDS
AND RUN TPKP
= IB PHASE IOC1 A OP
IC > Pickup PHASE IOC1 B OP
= IC TRST
PHASE IOC1 C OP

SETTINGS FLEXLOGIC OPERAND


Block A OR PHASE IOC1 PKP
= Off
FLEXLOGIC OPERAND
Block B
OR PHASE IOC1 OP
= Off
Block C FLEXLOGIC OPERAND
= Off AND PHASE IOC1 DPO
827033A8.CDR

5.8.4.5 Phase directional overcurrent (ANSI 67P, IEC PDOC/PTOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE DIRECTIONAL 1(2)
 PHASE PHASE DIR 1 Range: Disabled, Enabled
 DIRECTIONAL 1  FUNCTION: Disabled

PHASE DIR 1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-271


GROUPED ELEMENTS CHAPTER 5: SETTINGS

PHASE DIR 1 BLOCK: Range: FlexLogic operand


 Off

PHASE DIR 1 Range: 0 to 359° in steps of 1


 ECA: 30°

PHASE DIR POL V1 Range: 0.004 to 3.000 pu in steps of 0.001


 THRESHOLD: 0.700 pu

PHASE DIR 1 BLOCK Range: No, Yes


 WHEN V MEM EXP: No

PHASE DIR 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PHASE DIR 1 Range: Disabled, Enabled


 EVENTS: Disabled

The TARGET setting is not user-selectable and forced to "Disabled". If Targets are required from directional
elements, it can be achieved by assigning directional element output to a digital element, where targets selection
can be used as required.
The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs
of these elements.
Figure 5-132: Phase A directional polarization

TS 0
TPU

5
OU
-90o

VAG(Unfaulted) Fault angle


set @ 60 o Lag

VPol

VAG(Faulted) IA
ECA
set @ 30 o

VBC

VBC
VCG VBG +90o

Phasors for Phase A Polarization:

VPol = VBC*(1/_ECA) = polarizing voltage


IA = operating current
o
ECA = Element Characteristic Angle @ 30

827800A2.CDR

5-272 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

This element is intended to apply a block signal to an overcurrent element to prevent an operation when current is flowing
in a particular direction. The direction of current flow is determined by measuring the phase angle between the current
from the phase CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a
requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie
breaker, program two phase directional elements with opposite element characteristic angle (ECA) settings.
To increase security for three phase faults very close to the VTs used to measure the polarizing voltage, a voltage memory
feature is incorporated. This feature stores the polarizing voltage the moment before the voltage collapses, and uses it to
determine direction. The voltage memory remains valid for one second after the voltage has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating signal
(phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA).
The table shows the operating and polarizing signals used for phase directional control.
Table 5-41: Operating and polarizing signals
Phase Operating signal Polarizing signal Vpol
ABC phase sequence ACB phase sequence
A angle of IA angle of VBC × (1∠ECA) angle of VCB × (1∠ECA)
B angle of IB angle of VCA × (1∠ECA) angle of VAC × (1∠ECA)
C angle of IC angle of VAB × (1∠ECA) angle of VBA × (1∠ECA)

Mode of operation
• When the function is “Disabled” or the operating current is below 5% × CT nominal, the element output is logic “0”
• When the function is “Enabled,” the operating current is above 5% × CT nominal, and the polarizing voltage is above
the PRODUCT SETUP  DISPLAY PROPERTIES  VOLTAGE CUT-OFF LEVEL value, the element output is dependent on the
phase angle between the operating and polarizing signals: 5
– The element output is logic “0” when the operating current is within polarizing voltage ±90°
– For all other angles, the element output is logic “1”
• Once the voltage memory has expired, the phase overcurrent elements under directional control can be set to block or
trip on overcurrent as follows:
– When BLOCK WHEN V MEM EXP is set to “Yes,” the directional element blocks the operation of any phase
overcurrent element under directional control when voltage memory expires
– When BLOCK WHEN V MEM EXP is set to “No,” the directional element allows tripping of phase overcurrent elements
under directional control when voltage memory expires
In all cases, directional blocking is permitted to resume when the polarizing voltage becomes greater than the polarizing
voltage threshold.

Settings
PHASE DIR 1 FUNCTION — This setting enables and disables the phase directional overcurrent protection element.
PHASE DIR 1 SIGNAL SOURCE — This setting is used to select the source for the operating and polarizing signals. The
operating current for the phase directional element is the phase current for the selected current source. The polarizing
voltage is the line voltage from the phase VTs, based on the 90° or quadrature connection and shifted in the leading
direction by the element characteristic angle (ECA).
PHASE DIR 1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the phase directional
overcurrent element.
PHASE DIR 1 ECA — This setting specifies the element characteristic angle, that is, the angle by which the polarizing voltage
is shifted in the leading direction to achieve dependable operation. In the design of the UR-series elements, a block is
applied to an element by asserting logic 1 at the blocking input. Program the phase directional overcurrent element using
this setting so that the output is logic 1 for current in the non-tripping direction.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-273


GROUPED ELEMENTS CHAPTER 5: SETTINGS

PHASE DIR 1 POL V THRESHOLD — This setting is used to establish the minimum level of voltage for which the phase angle
measurement is healthy and reliable. Do not set this setting too low because the element can continue using the actual
voltage already distorted by the fault instead of using healthy memory voltage—this can cause wrong directional
discrimination.
PHASE DIR 1 BLOCK WHEN V MEM EXP — This setting is used to select the required operation upon expiration of voltage
memory. When set to "Yes," the directional element blocks the operation of any phase overcurrent element under
directional control, when voltage memory expires. When set to "No," the directional element allows tripping of phase
overcurrent elements under directional control.
PHASE DIR 1 EVENTS — This setting enables and disables the logging of phase directional overcurrent events in the
sequence of events recorder.

The phase directional element responds to the forward load current. In the case of a following reverse fault, the
element needs some time—in the order of 8 ms—to establish a blocking signal. Some protection elements, such as
instantaneous overcurrent, respond to reverse faults before the blocking signal is established. Therefore, a
coordination time of at least 10 ms must be added to all the instantaneous protection elements under the
supervision of the phase directional element. If current reversal is of concern, a longer delay—in the order of 20
ms—is needed.
Figure 5-133: Phase directional logic
6(77,1*
3+$6(',5
)81&7,21
(QDEOHG 

6(77,1*
$1'
3+$6(',5

5 %/2&.
2II 
6(77,1*

6(77,1* 3+$6(',5(&$

3+$6(',56285&( ,SX $1' 581 


,$ 9SRO
 )/(;/2*,&23(5$1'
6HT $%& 6HT $&% , 25 3+',5%/.
6(77,1*
9%& 9&%
3+$6(',532/9
7+5(6+2/' )/(;/2*,&23(5$1'
25 3+',5%/.$
8VH9ZKHQ90LQ
8VH9PHPRU\ZKHQ
0(025<7,0(5
90LQ
90,1,080 F\FOH
VHF
$1'

6(77,1* 86($&78$/92/7$*(
3+$6(',5%/2&.2&
:+(190(0(;3 86(0(025,=('92/7$*(
1R
<HV

)/(;/2*,&23(5$1'
3+$6(%/2*,&6,0,/$5723+$6($ 3+',5%/.%

)/(;/2*,&23(5$1'
3+$6(&/2*,&6,0,/$5723+$6($ 3+',5%/.&

$&'5

5-274 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

5.8.5 Neutral current

5.8.5.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT
 NEUTRAL CURRENT  NEUTRAL TOC 1 See below
  

 NEUTRAL TOC 6
 

 NEUTRAL IOC 1 See page 5-276


 

 NEUTRAL IOC 8
 

 NEUTRAL See page 5-278


  DIRECTIONAL OC1

 NEUTRAL
  DIRECTIONAL OC2

 TRANSIENT GROUND See page 5-283


  FAULT 1

  TRANSIENT GROUND
 FAULT 4 5
5.8.5.2 Neutral time overcurrent (ANSI 51N, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL TOC1(6)
 NEUTRAL TOC 1 NEUTRAL TOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEUTRAL TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEUTRAL TOC1 Range: Phasor, RMS


 INPUT: Phasor

NEUTRAL TOC1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

NEUTRAL TOC1 Range: see Overcurrent Curve Types table


 CURVE: IEEE Mod Inv

NEUTRAL TOC1 Range: 0.00 to 600.00 in steps of 0.01


 TD MULTIPLIER: 1.00

NEUTRAL TOC1 Range: Instantaneous, Timed


 RESET: Instantaneous

NEUTRAL TOC1 BLOCK: Range: FlexLogic operand


 Off

NEUTRAL TOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

NEUTRAL TOC1 Range: Disabled, Enabled


 EVENTS: Disabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-275


GROUPED ELEMENTS CHAPTER 5: SETTINGS

The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3I0 from the phase
currents and can be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section for details on curve setup, trip times, and reset operation). When the element is blocked, the time accumulator
resets according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator clears immediately.
NEUTRAL TOC1 FUNCTION — This setting enables and disables the neutral time overcurrent protection element.
NEUTRAL TOC1 SIGNAL SOURCE — This setting selects the signal source for the neutral time overcurrent protection element.
NEUTRAL TOC1 INPUT — This setting selects how neutral current input quantities are interpreted by the F60. Inputs can be
selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
NEUTRAL TOC1 PICKUP — This setting specifies the neutral time overcurrent pickup level in per-unit values.
NEUTRAL TOC1 CURVE — This setting selects the inverse time overcurrent curve style.
NEUTRAL TOC1 TD MULTIPLIER — This setting specifies a multiple of the base curve shape specified by the CURVE setting.
Programming this value to zero results in an instantaneous response to all current levels above pickup.
NEUTRAL TOC1 RESET — The “Instantaneous” reset method is intended for applications with other relays, such as most static
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The “Timed” reset
method can be used where the relay must coordinate with electromechanical relays.
NEUTRAL TOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the neutral time overcurrent
element.
NEUTRAL TOC1 EVENTS — This setting enables and disables the logging of neutral time overcurrent events in the sequence
5 of events recorder.
Figure 5-134: Neutral time overcurrent 1 logic

SETTING
NEUTRAL TOC1
INPUT
SETTING NEUTRAL TOC1
NEUTRAL TOC1 PICKUP
FUNCTION NEUTRAL TOC1
Enabled = 1 CURVE
NEUTRAL TOC1
TD MULTIPLIER
NEUTRAL TOC 1 FLEXLOGIC OPERAND
SETTING
RESET NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN ≥ PICKUP NEUTRAL TOC1 DPO
SOURCE
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK
Off = 0 827034A4.VSD

5.8.5.3 Neutral instantaneous overcurrent (ANSI 50N, IEC PIOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL IOC1(8)
 NEUTRAL IOC 1 NEUTRAL IOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEUTRAL IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEUTRAL IOC1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

5-276 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

NEUTRAL IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

NEUTRAL IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

NEUTRAL IOC1 BLOCK: Range: FlexLogic operand


 Off

NEUTRAL IOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

NEUTRAL IOC1 Range: Disabled, Enabled


 EVENTS: Disabled

The neutral instantaneous overcurrent element can be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency
phasor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when
forming the operating quantity of the element as follows:
Iop = 3 x (|I_0| - K x |I_1|) where K = 1/16 Eq. 5-16
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults
• Switch-off transients during double-line and three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay, where single-phase injection is 5
Iop = 0.9375 x Iinjected and three-phase pure zero-sequence injection is Iop = 3 x Iinjected
NEUTRAL IOC1 FUNCTION — This setting enables and disables the neutral instantaneous overcurrent protection element.
NEUTRAL IOC1 SIGNAL SOURCE — This setting selects the signal source for the neutral instantaneous overcurrent protection
element.
NEUTRAL IOC1 PICKUP — This setting specifies the neutral instantaneous overcurrent pickup level in per-unit values.
NEUTRAL IOC1 PICKUP DELAY — This setting delays the assertion of the NEUTRAL IOC OP operands. It is used to achieve
timing coordination with other elements and relays.
NEUTRAL IOC1 RESET DELAY — This setting specifies a delay for the reset of the neutral instantaneous overcurrent element
between the operate output state and the return to logic 0 after the input passes outside the defined pickup range. This
setting is used to ensure that the relay output contacts are closed long enough to ensure reception by downstream
equipment.a
NEUTRAL IOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the neutral instantaneous
overcurrent element.
NEUTRAL IOC1 EVENTS — This setting enables and disables the logging of neutral instantaneous overcurrent events in the
sequence of events recorder.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-277


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Figure 5-135: Neutral IOC1 logic

6(77,1*
6(77,1*6
1(875$/,2&)81&7,21 1(875$/,2&
6(77,1* 3,&.83'(/$<
(QDEOHG  )/(;/2*,&23(5$1'
1(875$/,2&
1(875$/,2&3,&.83 1(875$/,2&3.3
5(6(7'(/$<
6(77,1* 1(875$/,2&'32
$1' 581 W3.3
W567 1(875$/,2&23
1(875$/,2&%/2&.  _,B_._,B_ 3,&.83

2II 

6(77,1*

1(875$/,2&6285&(

,B
$&'5

5.8.5.4 Neutral directional overcurrent (ANSI 67N, IEC PDEF/PTOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL DIRECTIONAL
OC1(2)
 NEUTRAL NEUTRAL DIR OC1 Range: Disabled, Enabled
 DIRECTIONAL OC1  FUNCTION: Disabled

NEUTRAL DIR OC 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

5  NEUTRAL DIR OC1


POLARIZING: Voltage
Range: Voltage, Current, Dual, Dual-V, Dual-I

NEUTRAL DIR OC1 POL Range: Calculated V0, Measured VX


 VOLT: Calculated V0

NEUTRAL DIR OC1 OP Range: Calculated 3I0, Measured IG


 CURR: Calculated 3I0

NEUTRAL DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001


 SEQ RESTRAINT: 0.063

NEUTRAL DIR OC1 Range: 0.00 to 250.00 Ω in steps of 0.01


 OFFSET: 0.00 Ω

NEUTRAL DIR OC1 FWD Range: –90 to 90° in steps of 1


 ECA: 75° Lag

NEUTRAL DIR OC1 FWD Range: 40 to 90° in steps of 1


 LIMIT ANGLE: 90°

NEUTRAL DIR OC1 FWD Range: 0.006 to 30.000 pu in steps of 0.001


 PICKUP: 0.050 pu

NEUTRAL DIR OC1 REV Range: 40 to 90° in steps of 1


 LIMIT ANGLE: 90°

NEUTRAL DIR OC1 REV Range: 0.006 to 30.000 pu in steps of 0.001


 PICKUP: 0.050 pu

NEUTRAL DIR OC1 BLK: Range: FlexLogic operand


 Off

NEUTRAL DIR OC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

NEUTRAL DIR OC1 Range: Disabled, Enabled


 EVENTS: Disabled

5-278 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

The neutral directional overcurrent element provides both forward and reverse fault direction indications for the
NEUTRAL DIR OC1 FWD and NEUTRAL DIR OC1 REV operands, respectively. The output operand is asserted if the
magnitude of the operating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or
reverse, respectively (directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of either the neutral current
calculated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better
performance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the
zero-sequence current magnitude when forming the operating quantity.
Iop = 3 x (|I_0| - K x |I_1|) Eq. 5-17
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults
• Switch-off transients during double-line and three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
Iop = (1 – K) × Iinjected ; three-phase pure zero-sequence injection: Iop = 3 × Iinjected.
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant K to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and can
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. Both zero-sequence current (I_0) and ground current (IG) must be greater than the PRODUCT SETUP  DISPLAY 5
PROPERTIES  CURRENT CUT-OFF LEVEL setting value to be validated as the operating quantity for directional current. The
following tables define the neutral directional overcurrent element. V_0 is the zero-sequence voltage, I_0 is the zero-
sequence current, ECA is the element characteristic angle, and IG is the ground current.
Table 5-42: Quantities for "calculated 3I0" configuration
Directional unit quantities Overcurrent unit quantities
Polarizing mode Direction Compared phasors
Voltage Forward –V_0 + Z_offset × I_0 I_0 × 1∠ECA Iop = 3 × (|I_0| – K × |I_1|) if |I1| > 0.8 pu
Iop = 3 × (|I_0|) if |I1| ≤ 0.8 pu
Reverse –V_0 + Z_offset × I_0 –I_0 × 1∠ECA
Current Forward IG I_0
Reverse IG –I_0
Dual, Dual-V, Dual-I Forward –V_0 + Z_offset × I_0 I_0 × 1∠ECA
or
IG I_0
Reverse –V_0 + Z_offset × I_0 –I_0 × 1∠ECA
or
IG –I_0

Table 5-43: Quantities for "measured IG" configuration


Directional unit quantities Overcurrent unit quantities
Polarizing mode Direction Compared phasors
Voltage Forward –V_0 + Z_offset × IG/3 IG × 1∠ECA Iop = |IG|
Reverse –V_0 + Z_offset × IG/3 –IG × 1∠ECA

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-279


GROUPED ELEMENTS CHAPTER 5: SETTINGS

where
1
V_0 = --- VAG + VBG + VCG = zero sequence voltage
3

1 1
I_0 = --- IN = --- IA + IB + IC = zero sequence current
3 3
ECA = element characteristic angle
IG = ground current
Z_offset is the offset impedance, for which magnitude is the OFFSET setting and angle is the FWD ECA
When NEUTRAL DIR OC1 POL VOLT is set to “Measured VX,” one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
• ECA = 90° (element characteristic angle = centerline of operating characteristic)
• FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
• REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic. If the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication is delayed by 1.5 of a power system cycle. The element is designed to emulate an
electromechanical directional device. Larger operating and polarizing signals results in faster directional discrimination
bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore is
to be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and is to be used for the blocking direction. This allows for better protection coordination.
Take the bias into account when using the neutral directional overcurrent element to directionalize other protection
5 elements.

5-280 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-136: Neutral directional voltage-polarized characteristics

#FO \Y^U
B5F<1 6G4<1
\Y^U \Y^U
F17
bUVUbU^SU

B5F?`UbQdY^W 6G4?`UbQdY^W
BUWY_^ BUWY_^

<1 <1

#9O \Y^U
531

531\Y^U

531\Y^U

#9O \Y^U <1

F37 <1

F27

5
B5F<1 6G4<1
\Y^U \Y^U
#FO \Y^U
("'( %1!34B

NEUTRAL DIR OC1 POLARIZING — This setting selects the polarizing mode for the directional unit.
• If “Voltage” polarizing is selected, the element uses the zero-sequence voltage angle for polarization. The user can use
either the zero-sequence voltage V_0 calculated from the phase voltages, or the zero-sequence voltage supplied
externally as the auxiliary voltage V_X, both from the NEUTRAL DIR OC1 SOURCE.
The calculated V_0 can be used as polarizing voltage only if the voltage transformers are connected in Wye. The
auxiliary voltage can be used as the polarizing voltage provided SYSTEM SETUP  AC INPUTS  VOLTAGE BANK 
AUXILIARY VT CONNECTION is set to “Vn” and the auxiliary voltage is connected to a zero-sequence voltage source
(such as broken delta connected secondary of VTs).
The zero sequence voltage V_0 must be greater than PRODUCT SETUP  DISPLAY PROPERTIES  VOLTAGE CUT-OFF
LEVEL to be validated for use as polarizing signal. Additionally, when offset impedance is applied and zero-sequence
current is above 0.2 pu, compensated zero-sequence voltage -V_0 + Z_offset x I_0 has to be above 0.02 pu in order to
discriminate fault direction; otherwise when zero-sequence current is less than 0.2 pu, -V_0 is then used as the
polarizing signal. If the polarizing signal is invalid, neither forward nor reverse indication is given.
• If “Current” polarizing is selected, the element uses the ground current angle connected externally and configured
under NEUTRAL OC1 SOURCE for polarization. The ground CT must be connected between the ground and neutral point
of an adequate local source of ground current. The ground current must be greater than PRODUCT SETUP  DISPLAY
PROPERTIES  CURRENT CUT-OFF LEVEL to be validated as a polarizing signal. If the polarizing signal is not valid,
neither forward nor reverse indication is given. In addition, the zero-sequence current (I_0) must be greater than the
PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL setting value.
For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral current as a
polarizing source, ensure that a reversal of the ground current does not occur for a high-side fault. Assume that the

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-281


GROUPED ELEMENTS CHAPTER 5: SETTINGS

low-side system impedance is minimal when checking for this condition. A similar situation arises for a wye/delta/wye
transformer, where current in one transformer winding neutral can reverse when faults on both sides of the
transformer are considered.
• If “Dual” polarizing is selected, the element performs both directional comparisons as described. A given direction is
confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward and reverse)
indication occurs, the forward direction overrides the reverse direction.
• If "Dual-V" polarizing is selected, "Voltage" polarizing is performed and "Current" polarizing is ignored if the voltage
polarizing signal is valid; otherwise "Current" polarizing is performed if the current polarizing signal is valid. If neither of
them is valid, neither forward nor reverse indication is given.
• If "Dual-I" polarizing is selected, "Current" polarizing is performed and "Voltage" polarizing is ignored if the current
polarizing signal is valid; otherwise "Voltage" polarizing is performed if the voltage polarizing signal is valid. If neither of
them is valid, neither forward nor reverse indication is given.
NEUTRAL DIR OC1 POL VOLT — Selects the polarizing voltage used by the directional unit when "Voltage," "Dual," "Dual-V," or
"Dual-I" polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence voltage
calculated from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX").
NEUTRAL DIR OC1 OP CURR — This setting indicates whether the 3I_0 current calculated from the phase currents, or the
ground current is used by this protection. This setting acts as a switch between the neutral and ground modes of operation
(ANSI devices 67N and 67G). If set to “Calculated 3I0,” the element uses the phase currents and applies the positive-
sequence restraint. If set to “Measured IG,” the element uses ground current supplied to the ground CT of the CT bank
configured as NEUTRAL DIR OC1 SOURCE. If this setting is “Measured IG,” then the NEUTRAL DIR OC1 POLARIZING setting must
be “Voltage”, as it is not possible to use the ground current as an operating and polarizing signal simultaneously. IG current
has to be above PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL to be used as an operate quantity.
NEUTRAL DIR OC1 POS-SEQ RESTRAINT — This setting controls the amount of the positive-sequence restraint. Set it to 0.063

5 for backward compatibility with firmware revision 3.40 and older. Set it to zero to remove the restraint. Set it higher if large
system unbalances or poor CT performance are expected.
NEUTRAL DIR OC1 OFFSET — This setting specifies the offset impedance used by this protection. The primary application for
the offset impedance is to guarantee correct identification of fault direction on series compensated lines. In regular
applications, the offset impedance ensures proper operation even if the zero-sequence voltage at the relaying point is very
small. If this is the intent, the offset impedance is not to be larger than the zero-sequence impedance of the protected
circuit. Practically, it shall be several times smaller. Enter the offset impedance in secondary ohms.
NEUTRAL DIR OC1 FWD ECA — This setting defines the characteristic angle (ECA) for the forward direction in the "Voltage"
polarizing mode. The "Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is the angle set for
the forward direction shifted by 180°.
NEUTRAL DIR OC1 FWD LIMIT ANGLE — This setting defines a symmetrical (in both directions from the ECA) limit angle for the
forward direction.
NEUTRAL DIR OC1 FWD PICKUP — This setting defines the pickup level for the overcurrent unit of the element in the forward
direction. When selecting this setting, keep in mind that the design uses a positive-sequence restraint technique for the
“Calculated 3I0” mode of operation.
NEUTRAL DIR OC1 REV LIMIT ANGLE — This setting defines a symmetrical (in both directions from the ECA) limit angle for the
reverse direction.
NEUTRAL DIR OC1 REV PICKUP — This setting defines the pickup level for the overcurrent unit of the element in the reverse
direction. When selecting this setting, keep in mind that the design uses a positive-sequence restraint technique for the
“Calculated 3I0” mode of operation.

5-282 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-137: Neutral directional overcurrent logic


SETTINGS
NEUTRAL DIR OC1 F WD
PICKU P:

NEUTRAL DIR OC1 OP


CURR:

NEUTRAL DIR OC1 POS-


SE Q RESTRAINT:

SE TTINGS RUN

NEUTRAL DIR OC1 3( I_0 - K I_1 ) PICKUP


FU NCTION: OR
Enabled=1 IG PICKU P AND

SE TTINGS
AND SETTINGS
NEUTRAL DIR OC1 BLK: AND
NEUTRAL DIR OC1 F WD
ECA:
Off=0
NEUTRAL DIR OC1 F WD FLEXLOGIC OPERAND
LIMIT ANGLE:
SE TTINGS AND NEUTRAL DIR OC1 F WD
NEUTRAL DIR OC1 NEUTRAL DIR OC1 REV
SOURCE: LIMIT ANGLE:

NEUTRAL DIR OC1 P OL NEUTRAL DIR OC1


VOLT: OFFSET:
RUN
NEUTRAL DIR OC1 OP
CURR:
FW D
Me asure d VX OR
V V_cutoff FW D
Calculated V_ 0 1.25 cy
-3V_0 AND
Ze ro Seq Crt (I_0) I0 I_cutoff 1.5 cy
Ground Crt (IG) REV
IG I_cutoff 3I_ 0 REV

Voltage Polarization

SE TTINGS IG 0.05 pu AND RUN


NEUTRAL DIR OC1 FW D
POLARIZ ING :
Voltage OR Current Polarization
Current
Dual, Dual-V, D ual-I OR
REV
OR
5
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RE LAY S WITH
THE GROU ND CURRE NT INPU TS CONNE CTE D TO
AN AD EQU ATE CURRE NT POLARI ZING SOURCE SETTINGS
NEUTRAL DIR OC1 REV
2) G ROUND CURRENT CAN NOT BE USE D FOR POLARIZATION PICKU P:
AND OPERATION SIMU LTANEOUSLY AND FLEXLOGIC OPERAND
NEUTRAL DIR OC1 OP
CURR: NEUTRAL DIR OC1 REV
3) POSITI VE S EQU ENCE RE STRAINT IS NOT APPLIED W HE N
I_1 IS BELOW 0.8pu
NEUTRAL DIR OC1 POS -
SE Q RESTRAINT:
RUN
3( I_0 - K I_1 ) PICKUP
OR
IG P ICKU P
827195A1.vsdx

5.8.5.5 Transient ground fault detection


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  TRANS GND FLT 1(4)
 TRANS GND FLT 1 TRANSIENT GND FLT 1 Range: Disabled, Enabled
  FUNCTION: Disabled

TRANSIENT GND FLT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

TRANSIENT GND FLT 1 Range: Calculated VN, Measured VX


 VOLT: Measured VX

TRANSIENT GND FLT 1 Range: Calculated IN, Measured IG


 AMP: Measured IG

TRANSIENT GND FLT 1 Range: 0.0 to 100.0 W in steps of 0.01


 PWR THLD: 3.0

TRANSIENT GND FLT 1 Range: 0.00 to 1.50 pu in steps of 0.01


 VOLT PKP: 0.10

TRANSIENT GND FLT 1 Range: Off, On, FlexLogic operand


 BLOCK: Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-283


GROUPED ELEMENTS CHAPTER 5: SETTINGS

TRANSIENT GND FLT 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

TRANSIENT GND FLT 1 Range: Disabled, Enabled


 EVENTS: Disabled

For a solid single phase to ground fault in an ungrounded three-phase system, the voltage of the faulted phase becomes
equal to the earth potential (zero) while that of healthy phases become 3 times the nominal value. The fault current in
ungrounded systems is equal to the sum of the charging currents drawn by the healthy phases, which is three times the
normal charging current. The higher charging current can lead to arcing at the fault point and this arcing might not be self-
extinguishing due to significant amount of fault (charging) current. Therefore, Petersen's coil, which is an inductive coil, is
placed in the neutral of the three-phase system to compensate for the capacitive charging currents, which in turn reduces
or eliminates the fault current.
Depending on the level of compensation of the Petersen's coil, three conditions can arise:
• Over compensation (inductive fault current)
• Under (capacitive fault current) compensation
• Resonant compensation (no fault current)
The figure shows an ungrounded system. The zero-sequence current in the healthy feeder the current is capacitive in
nature, while the zero-sequence current in faulted phase is inductive in nature. This observation can be utilized to identify
and isolate the faulty feeder in ungrounded systems.
Figure 5-138: Single-phase to ground fault in ungrounded system

5
Capacitive

Inductive

859810A1.vsdx

However, in the case of Petersen's coil grounded system, zero-sequence current of a faulty feeder can become capacitive,
inductive, resistive, or altogether disappear, depending upon the level of compensation, the charging current of the
system, or the fault impedance. For example, the next figure shows the single-phase to ground fault in Petersen's coil
grounded network with 100% compensation (resonant compensation). It can be observed that all of the charging current
is supplied via neutral of the compensated system, thus making the current at the fault point equal to 0. Consequently, the
zero-sequence current of the faulty feeder like a healthy feeder also becomes capacitive in nature. Thus, the standard
directional protection cannot be applied to systems grounded through Petersen coil.

5-284 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-139: Single-phase to ground fault in Petersen coil grounded system with 100% compensation

Capacitive

Capacitive

859811A1.vsdx

To overcome this challenge, a patented algorithm is used, which does not require special hardware or high acquisition
frequency, to precisely determine the fault direction. The algorithm utilizes the concept of transient reactive power to
identify the direction of the fault. The algorithm also applies to high-resistive grounded and ungrounded systems. The
5
technique involves the application of band pass filters to measured residual voltage (VN) and current signals (IN). The center
frequency of the band pass filters is 220 Hz and 264 Hz for nominal frequencies of 50 and 60 Hz respectively. Band pass
filters remove the fundamental frequency component and introduce a 90° shift in anti-clockwise direction in the voltage
signal. The outputs of voltage and current band pass filters are denoted by V'N and I'N respectively. The transient reactive
power is obtained by multiplying V'N and I'N.
If the feeder has a fault, the circuit is inductive in the frequency range of the interest. Consequently, the transient reactive
power is negative as V'N. and I'N are in phase opposition (figure a). On the other hand, if the feeder is healthy the circuit is
capacitive in nature, thereby making the transient reactive power positive (figure b). Note that the phasors shown in the
figure represent the voltage and current relationship surrounding the frequencies 220 Hz and 264 Hz for 50 and 60 Hz
systems respectively.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-285


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Figure 5-140: Transient ground fault

V’ N V’ N

I’N IN

90o 90o
VN VN

I’N IN Faulty Feeder Healthy Feeder


(a) (b)
Figure shows the phase relationship of the frequency components of V N, IN, V’N, and I’N
in the region surrounding 220 Hz in 50 Hz system or 264 Hz for 60 Hz system
859799A1.vsdx

Similarly, the decision about the direction of the fault can also be made using transient active power. In case the minimum
threshold of transient reactive power is not met, the direction of the fault can be identified using transient active power.

5 TRANSIENT GND FLT 1 FUNCTION — This setting enables and disables the Transient Ground Fault Detection function.
TRANSIENT GND FLT 1 SOURCE — This setting selects the signal source for Transient Ground Fault Detection function.
TRANSIENT GND FLT 1 VOLT — The element uses neutral voltage (that is, three times the zero-sequence voltage). This setting
allows selecting between the internally calculated neutral voltage or the externally supplied voltage (broken delta VT
connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel must be
identified by the user as a neutral voltage under the VT bank settings. This element operates when the auxiliary voltage is
configured as neutral.
TRANSIENT GND FLT 1 AMP — The element responds to the neutral current (that is, three times zero-sequence current), either
calculated internally from the phase currents or supplied externally via the ground CT input from more accurate sources
such as the core balanced CT. This setting allows selecting the source of the operating current.
TRANSIENT GND FLT 1 PWR THLD — This setting is used to calculate dynamic power threshold which in turn is used to
determine residual fault direction. Increasing the value of this setting increases the security and decreases the sensitivity
of the element. The minimum value that can be applied to this setting to avoid overlap with "small P/Q" area is 3 W. As
shown in the next figure, "small P/Q" area refers to the condition when the calculated transient reactive or active power is
small enough to introduce ambiguity in sensing the direction of the fault. This setting is given in secondary value.

5-286 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-141: Transient ground fault power threshold

Reactive Power selected Active Power selected

Average Reactive Average Reactive


Power Power

Dynamic Threshold P Positive


Dynamic Threshold P Negative
Dynamic Threshold Q Positive
2 5 2 5
-5 -2 -5 -2
Average Active Average Active
Power Power

Dynamic Threshold Q Negative

Reverse Should never happen

Forward Should never happen


859801A1.vsdx 5
TRANSIENT GND FLT 1 VOLT PKP — Voltage pickup threshold that is used to determine if Transient Ground Fault Detection
element starts or not. If the measured neutral voltage is above this setting the element Transient Ground Fault Detection
starts. Typical value of this setting is 0.10 pu.
TRANSIENT GND FLT 1 BLOCK — Assertion of the FlexLogic operand assigned to this setting blocks operation of Transient
Ground Fault Detection element.
TRANSIENT GND FLT 1 EVENTS — This setting enables and disables the logging of Transient Ground Fault Detection events in
the event recorder.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-287


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Figure 5-142: Transient ground fault detection logic


SETTING
NOMINAL FREQUENCY:
=60Hz
Available at: SETTINGS > SYSTEM RUN RUN RUN
SETUP > POWER SYSTEM RUN
Voltage band- V’N Calculate dynamic threshold
SETTING pass Filter (90o Q, max average Q and
Average Transient Q
shift) evaluate Positive/Negative Q
TRANSIENT GND FLT 1 SOURCE: I’N FLEXLOGIC OPERAND
Current band-
pass Filter TGFD 1 REVERSE
TRANSIENT GND FLT 1 AMP:
Center frequency of the filters:
Calculated IN Measured IG 50 Hz System: 220 Hz RUN
Directional logic
60 Hz System: 264 Hz
RUN Calculate dynamic threshold
TRANSIENT GND FLT 1 VOLT:
P, max average P and
Calculated VN Measured VX Average Transient P evaluate Positive/Negative P FLEXLOGIC OPERAND
V1 TGFD 1 FORWARD

SETTING
TRANSIENT GND FLT 1 PWR
THLD: RUN
3.00W

Select Power P or Q
Only applicable when setting
TRANSIENT GND FLT 1
VOLT=Calculated VN SETTING

TIMER TRANSIENT GND FLT 1 VOLT


PKP:
2cyc
|V1|> 0.8 pu RUN
1 cyc TIMER
Activate TGFD: 0
RMS V N > Setting
300 ms
SETTING
TRNST GND FLT 1 BLK: FLEXLOGIC OPERAND
Off=0 AND TGFD 1 START

SETTING
TRANSIENT GND FLT 1
FUNCTION:

Enabled=1 859800A3.vsdx

5
5.8.6 Wattmetric ground fault

5.8.6.1 Wattmetric zero-sequence directional (ANSI 32N, IEC PSDE)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  WATTMETRIC...  WATTMETRIC GROUND FAULT 1(2)
 WATTMETRIC WATTMETRIC GND FLT 1 Range: Disabled, Enabled
 GROUND FAULT 1  FUNCTION: Disabled

WATTMETRIC GND FLT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

WATTMETRIC GND FLT 1 Range: Calculated VN, Measured VX


 VOLT: Calculated VN

WATTMETRIC GND FLT 1 Range: 0.02 to 3.00 pu in steps of 0.01


 OV PKP: 0.20 pu

WATTMETRIC GND FLT 1 Range: Calculated IN, Measured IG


 CURR: Calculated IN

WATTMETRIC GND FLT 1 Range: 0.002 to 30.000 pu in steps of 0.001


 OC PKP: 0.060 pu

WATTMETRIC GND FLT 1 Range: 0.00 to 600.00 s in steps of 0.01


 OC PKP DEL: 0.20 s

WATTMETRIC GND FLT 1 Range: 0.001 to 1.200 pu in steps of 0.001


 PWR PKP: 0.100 pu

WATTMETRIC GND FLT 1 Range: 0.001 to 1.200 pu in steps of 0.001


 REF PWR: 0.500 pu

WATTMETRIC GND FLT 1 Range: 0 to 360° Lag in steps of 1


 ECA: 0° Lag

5-288 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

WATTMETRIC GND FLT 1 Range: 0.00 to 600.00 s in steps of 0.01


 PWR PKP DEL: 0.20 s

WATTMETRIC GND FLT 1 Range: Definite Time, Inverse, FlexCurves A through


 CURVE: Definite Time D

WATTMETRIC GND FLT 1 Range: 0.01 to 2.00 s in steps of 0.01


 MULTIPLIER: 1.00 s

WATT GND FLT 1 BLK: Range: FlexLogic operand


 Off

WATTMETRIC GND FLT 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

WATTMETRIC GND FLT 1 Range: Disabled, Enabled


 EVENTS: Disabled

The wattmetric zero-sequence directional element responds to power derived from zero-sequence voltage and current in
a direction specified by the element characteristic angle. The angle can be set within all four quadrants, and the power can
be active or reactive. Therefore, the element can be used to sense either forward or reverse ground faults in either
inductive, capacitive, or resistive networks. The inverse time characteristic allows time coordination of elements across the
network.
Typical applications include ground fault protection in solidly grounded transmission networks, grounded/ungrounded/
resistor-grounded/resonant-grounded distribution networks, or for directionalizing other non-directional ground elements.
WATTMETRIC GND FLT 1 VOLT — The element uses neutral voltage (that is, three times the zero-sequence voltage). This
setting allows selecting between the internally calculated neutral voltage or the externally supplied voltage (broken delta
VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel must be
identified by the user as a neutral voltage under the VT bank settings. This element operates when the auxiliary voltage is
configured as neutral. 5
WATTMETRIC GND FLT 1 OV PKP — This setting specifies the minimum zero sequence voltage supervising the directional
power measurement. Set this threshold higher than possible unbalance during normal operation of the system. Typically,
this setting is at 0.1 to 0.2 pu for the ungrounded or resonant grounded systems and at 0.05 to 0.1 pu for solidly or resistor-
grounded systems. When using externally supplied voltage via the auxiliary voltage channel, 1 pu is the nominal voltage of
this channel as per VT bank settings. When using internally calculated neutral voltage, 1 pu is the nominal phase to ground
voltage as per the VT bank settings.
WATTMETRIC GND FLT 1 CURR — The element responds to the neutral current (that is, three times zero-sequence current),
either calculated internally from the phase currents or supplied externally via the ground CT input from more accurate
sources such as the core balanced CT. This setting allows selecting the source of the operating current.
WATTMETRIC GND FLT 1 OC PKP — This setting specifies the current supervision level for the measurement of the zero-
sequence power.
WATTMETRIC GND FLT 1 OC PKP DEL — This setting specifies delay for the overcurrent portion of this element. The delay
applies to the WATTMETRIC 1 PKP operand driven from the overcurrent condition.
WATTMETRIC GND FLT 1 PWR PKP — This setting specifies the operating point of the element. A value of 1 pu is a product of
the 1 pu voltage as specified for the overvoltage condition of this element, and 1 pu current as specified for the
overcurrent condition of this element.
WATTMETRIC GND FLT 1 REF PWR — This setting is used to calculate the inverse time characteristic delay (defined by Sref in
the following equations). A value of 1 pu represents the product of a 1 pu voltage (as specified in the overvoltage condition
for this element) and a 1 pu current (as specified in the overcurrent condition for this element.
WATTMETRIC GND FLT 1 ECA — This setting adjusts the maximum torque angle of the element. The operating power is
calculated as:
S_op = Re(Vn(In x 1∠ECA)*) Eq. 5-18
where
* indicates complex conjugate

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-289


GROUPED ELEMENTS CHAPTER 5: SETTINGS

By varying the element characteristic angle (ECA), the element can be made to respond to forward or reverse direction in
inductive, resistive, or capacitive networks as shown in the Wattmetric Characteristic Angle Response diagram.
WATTMETRIC GND FLT 1 PWR PKP DEL — This setting defines a definite time delay before the inverse time characteristic is
activated. If the curve selection is set as “Definite Time”, the element operates after this security time delay. If the curve
selection is “Inverse” or one of the FlexCurves, the element uses both the definite and inverse time timers simultaneously.
The definite time timer, specified by this setting, is used and when expires it releases the inverse time timer for operation
(torque control).
WATTMETRIC GND FLT 1 CURVE — Choose one of three methods to delay the operate signal once all conditions are met to
discriminate fault direction.
The “Definite Time” selection allows for a fixed time delay defined by the WATTMETRIC GND FLT 1 PWR PKP DEL setting.
The “Inverse” selection allows for inverse time characteristics delay defined by the following formula:

S ref
t = m u -------- Eq. 5-19
S op

where
m is a multiplier defined by the multiplier setting
Sref is the multiplier setting
Sop is the operating power at the time
This timer starts after the definite time timer expires.
The four FlexCurves allow for custom user-programmable time characteristics. When working with FlexCurves, the
element uses the operate to pickup ratio, and the multiplier setting is not applied:

5 S op
t = FlexCurve §© --------·¹
S ref Eq. 5-20

Again, the FlexCurve timer starts after the definite time timer expires.

5-290 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-143: Wattmetric characteristic angle response


FORWARD FAULT REVERSE FAULT

ECA = 180 to 270° ECA = 0 to 90°

INDUCTIVE NETWORK
Vn Vn

In In
RESISTIVE NETWORK

ECA = 180° ECA = 0°

Vn Vn

In In

5
In In
CAPACITIIVE NETWORK

Vn Vn

ECA = 90 to 180° ECA = 270 to 360°

837804A1.CDR

WATTMETRIC GND FLT 1 MULTIPLIER — This setting is applicable if the WATTMETRIC GND FLT 1 CURVE is set to Inverse and
defines the multiplier factor for the inverse time delay.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-291


5

5-292
5.8.7.1 Menu
GROUPED ELEMENTS

 GROUND CURRENT
5.8.7 Ground current

 
6(77,1*6 6(77,1*6
:$770(75,&*1')/7 :$770(75,&*1')/7
6285&( 3:53,&.83
:$770(75,&*1')/7 :$770(75,&*1')/7
&855(17 6(77,1* 6(77,1*6
2&3,&.83
&DOFXODWHG 0HDVXUHG :$770(75,&*1')/7 :$770(75,&*1')/7
:$770(75,&*1')/7
1HXWUDO,Q *URXQG,J (&$ 293,&.83 &859(
6(77,1*


:$770(75,&*1')/7 :$770(75,&*1')/7

 GROUND TOC1
92/7$*( 6 9 FRQM , H[S M (&$ 623!3:53,&.83 :$770(75,&*1')/7 5()3:5
&DOFXODWHG 0HDVXUHG 3:53.3'(/
:$770(75,&*1')/7
1HXWUDO9Q $X[LOLDU\9[ 08/7,3/,(5
90$*!293,&.83
W3.3 581
$1'  )/(;/2*,&23(5$1'
,0$*!2&3,&.83 65()
6(77,1*6 W P˜ :$770(75,&23
623
:$770(75,&*1')/7 $1' 6(77,1*
)81&7,21
:$770(75,&*1')/7
(QDEOHG 
2&3.3'(/
:$77*1')/7%/.

$1'
)/(;/2*,&23(5$1'
2II 
W3.3 :$770(75,&3.3


See below
$&'5

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT


Figure 5-144: Wattmetric zero-sequence directional logic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
CHAPTER 5: SETTINGS GROUPED ELEMENTS

 GROUND TOC4
 

 GROUND IOC1 See page 5-294


 

 GROUND IOC6
 

 RESTRICTED GROUND See page 5-295


  FAULT 1

 RESTRICTED GROUND
  FAULT 4

For information on the Ground Time Overcurrent curves, see the Inverse Time Overcurrent Characteristics section earlier.

5.8.7.2 Ground time overcurrent (ANSI 50G, IEC PIOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND TOC1(4)
 GROUND TOC1 GROUND TOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

GROUND TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

GROUND TOC1 Range: Phasor, RMS


 INPUT: Phasor

GROUND TOC1 Range: 0.020 to 30.000 pu in steps of 0.001


5
 PICKUP: 1.000 pu

GROUND TOC1 Range: see the Overcurrent Curve Types table


 CURVE: IEEE Mod Inv

GROUND TOC1 Range: 0.00 to 600.00 in steps of 0.01


 TD MULTIPLIER: 1.00

GROUND TOC1 Range: Instantaneous, Timed


 RESET: Instantaneous

GROUND TOC1 BLOCK: Range: FlexLogic operand


 Off

GROUND TOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

GROUND TOC1 Range: Disabled, Enabled


 EVENTS: Disabled

This element can provide a required time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the
fundamental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous”
(see the Inverse TOC Curve Characteristics section for details). When the element is blocked, the time accumulator resets
according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and the
element is blocked, the time accumulator clears immediately.
GROUND TOC1 FUNCTION — This setting enables and disables the ground time overcurrent protection element.
GROUND TOC1 SIGNAL SOURCE — This setting selects the signal source for the ground time overcurrent protection element.
GROUND TOC1 INPUT — This setting selects how ground current input quantities are interpreted by the F60. Inputs can be
selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-293


GROUPED ELEMENTS CHAPTER 5: SETTINGS

GROUND TOC1 PICKUP — This setting specifies the ground time overcurrent pickup level in per-unit values. With a Process
Bus Module, accuracy of the element is determined by the sum of the relay internal processing errors and input signal from
the merging unit errors, which can be significant depending on the merging unit design. For low level pickup settings,
especially less than 0.020 pu with a Process Bus Module, ensure that the selected merging unit meets given application
accuracy requirements.
GROUND TOC1 CURVE — This setting selects the inverse time overcurrent curve style.
GROUND TOC1 TD MULTIPLIER — This setting specifies a multiple of the base curve shape specified by the CURVE setting.
Programming this value to zero results in an instantaneous response to all current levels above pickup.
GROUND TOC1 RESET — The “Instantaneous” reset method is intended for applications with other relays, such as most static
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The “Timed” reset
method can be used where the relay must coordinate with electromechanical relays.
GROUND TOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the ground time overcurrent
element.

These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.

This channel can be also equipped with a sensitive input. The conversion range of a sensitive channel is from 0.002
to 4.6 times the CT rating.

Figure 5-145: Ground TOC1 logic

5 SETTINGS
GROUND TOC1
INPUT:
SETTING GROUND TOC1
GROUND TOC1 PICKUP:
FUNCTION: GROUND TOC1
Enabled = 1 CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: GROUND TOC1 PKP
GROUND TOC1
AND RUN IG PICKUP GROUND TOC1 DPO
SOURCE:
GROUND TOC1 OP
IG t
I
SETTING
GROUND TOC1
BLOCK:
827036A4.VSD
Off = 0

5.8.7.3 Ground instantaneous overcurrent (ANSI 50G, IEC PIOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND IOC1(6)
 GROUND IOC1 GROUND IOC 1 Range: Disabled, Enabled
  FUNCTION: Disabled

GROUND IOC 1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

GROUND IOC 1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

GROUND IOC 1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

GROUND IOC 1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

5-294 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

GROUND IOC 1 BLOCK: Range: FlexLogic operand


 Off

GROUND IOC 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

GROUND IOC 1 Range: Disabled, Enabled


 EVENTS: Disabled

The ground instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
GROUND IOC1 FUNCTION — This setting enables and disables the element.
GROUND IOC1 SIGNAL SOURCE — This setting selects the signal source for the element.
GROUND IOC1 PICKUP — This setting specifies the pickup level in per-unit values. With a Process Bus Module, accuracy of
the element is determined by the sum of the relay internal processing errors and input signal from the merging unit errors,
which can be significant depending on the merging unit design. For low level pickup settings, especially less than 0.020 pu
with a Process Bus Module, ensure that the selected merging unit meets the given application accuracy requirements.
GROUND IOC1 PICKUP DELAY — This setting specifies the definite time delay after which the operate signal asserts.
GROUND IOC1 RESET DELAY — This setting specifies the reset time delay.
GROUND IOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the element.

These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.

5
This channel can be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.

Figure 5-146: Ground IOC1 logic

FLEXLOGIC OPERANDS
GROUND IOC1 PKP
SETTING GROUND IOIC DPO
GROUND IOC1
SETTINGS GROUND IOC1 OP
FUNCTION:
Enabled = 1 GROUND IOC1 PICKUP
SETTING DELAY:
GROUND IOC1 GROUND IOC1 RESET
SETTING
PICKUP: DELAY:
GROUND IOC1
AND RUN tPKP
SOURCE:
IG
IG PICKUP tRST
SETTING
GROUND IOC1
BLOCK:
827037A5.VSD
Off = 0

5.8.7.4 Restricted ground fault (ANSI 87RGF, IEC PNDF)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  RESTRICTED GROUND FAULT
1(4)
 RESTRICTED GROUND RESTD GND FT1 Range: Disabled, Enabled
 FAULT 1  FUNCTION: Disabled

RESTD GND FT1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-295


GROUPED ELEMENTS CHAPTER 5: SETTINGS

RESTD GND FT1 Range: 0.005 to 30.000 pu in steps of 0.001


 PICKUP: 0.080 pu

RESTD GND FT1 Range: 0 to 100% in steps of 1


 SLOPE: 40%

RESTD GND FT1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.03 s

RESTD GND FT1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

RESTD GND FT1 BLOCK: Range: FlexLogic operand


 Off

RESTD GND FT1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

RESTD GND FT1 Range: Disabled, Enabled


 EVENTS: Disabled

Restricted ground fault (RGF) protection provides sensitive ground fault detection for low-magnitude fault currents,
primarily faults close to the neutral point of a wye-connected winding. An internal ground fault on an impedance grounded
wye winding produces a fault current dependent on the ground impedance value and the fault position on the winding
with respect to the neutral point. The resultant primary current is negligible for faults on the lower 30% of the winding since
the fault voltage is not the system voltage, but rather the result of the transformation ratio between the primary windings
and the percentage of shorted turns on the secondary. Therefore, the resultant differential currents can be below the slope
threshold of the main differential element and the fault can go undetected. Application of the restricted ground fault
protection extends the coverage towards the neutral point (see the following figure).

5 Figure 5-147: RGF and percent differential zones of protection


G9>49>7

#%

B76 49665B5>D91<J?>5
BW
J?>5

($"'#!1!34B

This protection is often applied to transformers having impedance-grounded wye windings. The element can also be
applied to the stator winding of a generator having the neutral point grounded with a CT installed in the grounding path, or
the ground current obtained by external summation of the neutral-side stator CTs. The following figure shows the basic
application and wiring rules.

5-296 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-148: Typical applications of RGF protection


D ) )
7UDQVIRUPHU:LQGLQJ F 6WDWRU:LQGLQJ
,$ ,$

,% ,%

,& ,&

) ,* ) ,*

  
0
E 7UDQVIRUPHU:LQGLQJ ,$ ,% ,& G 6WDWRU:LQGLQJ
) ,$
,$

,%
,%

,&
,&

5
) ,* ,$ ,% ,& 0
,*
  

  
H
$XWRWUDQVIRUPHU:LQGLQJ ,$ ,% ,& )

) ,* ,$ ,% ,& 0
  

$&'5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-297


GROUPED ELEMENTS CHAPTER 5: SETTINGS

The next figures show distribution of the ground fault current through the grounded neutral point of the wye winding and
primary delta winding as a function of the fault location as a percentage of the whole wye winding. Magnitude of the
transformer winding fault is controlled by several factors, such as supply source impedance, wye winding neutral
grounding impedance, transformer leakage reactance, fault voltage windings connection and position of the fault on the
winding with respect to the neutral point.
Figure 5-149: Fault current through transformer neutral against primary current
(left is resistance-ground neutral, right is solidly grounded neutral)

5
Figure 5-150: Fault current through transformer neutral against primary current (winding current flow during ground
fault)

IP

IP

RG
IF
859819A1.vsdx

The settings are as follows.


RESTD GND FT1 SOURCE — Identifies the signal source for the restricted ground fault (RGF) function. It is important that
source includes a set of three-phase CTs on the line side of the wye winding of the transformer assigned to the Phase CT
setting of this source and a neutral point CT assigned to the Ground CT setting of this source. In case of more breaker-and-
a-half connections on the line side of the transformer or autotransformer application, Phase CT arrangement need to
include the sum of CT banks contributing to the differential signal. When the summed CTs have a different ratio, the relay
automatically re-scales to the maximum CT primary nominal value.
RESTD GND FT1 PICKUP — Defines the minimum ground differential current required for operation. The relay automatically
matches the CT ratios between the phase and ground CTs by re-scaling the ground CT to the phase CT level, which
becomes a base value for the differential and restraint currents. For example, for 10 MVA, 33 kV to 11 kV transformer, 10%
impedance, D / Y-1, RG = 6.3Ω, with Phase CT ratio = 600 / 1 A.

5-298 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Maximum phase-to-ground fault current IGMAX = 11 kV / ( 3 × 6.3Ω) = 1000 A primary.


For a winding fault point at 5% distance from the neutral:
IGPKP = 0.05 x IGMAX = 0.05 x 1000 = 50 A primary. The pickup setting is chosen as PKP = 50 A / 600 A = 0.083 pu
Note that for correct operation of the element, the CURRENT CUTOFF setting under Display Properties has to be set at least
two times less than the PICKUP setting.
RESTD GND FT1 SLOPE — Defines the restrain characteristics for this element. Set the slope to provide extra restraint for
external faults, but not prevent operation for the winding fault during heavy transformer load. Transformer nominal
winding current is IN(W) = 10 MVA / ( 3 × 11 kV) = 525 A = 525 A / 600 A = 0.875 pu. Considering that RGF algorithm
restraint is defined by the positive-sequence current during load, and for currents below 2 pu restraint is equal to I1/8,
slope can be estimated as follows:
Slope = PKP / (1.2 x IN(W) / 8) x 100% = 0.083 pu / (1.2 x 0.875 / 8) x 100% = 63%
where 1.2 factor accounts for 20% temporary overload of the transformer
Because the final slope has to be set lower than this calculated value to have some safety margin, the final setting can be
selected as 43%.
RESTD GND FT1 PICKUP DELAY — Defines element delay from the pickup to assertion of the RESTD GND FT1 OP operand.
GE recommends a short time delay to overcome spurious zero-sequence current due to switch-off transients for this
sensitive protection.
RESTD GND FT1 RESET DELAY — Defines how long the RESTD GND FT1 OP operand stays asserted after pickup conditions
disappear.

The relay incorporates low-impedance restricted ground fault protection. This low-impedance form of protection faces
potential stability problems. An external phase-to-phase fault is an ultimate case. Ideally, there is neither ground (IG) nor
neutral (IN = IA + IB + IC) current present. If one or more of the phase CTs saturate, a spurious neutral current is seen by the 5
relay. This is similar to a single infeed situation and can be mistaken for an internal fault. Similar difficulties occur in a
breaker-and-a-half application of the restricted ground fault, where any through fault with a weak infeed from the winding
itself can cause problems.
The UR uses a novel definition of the restraining signal to cope with the above stability problems while providing fast and
sensitive protection. Even with the improved definition of the restraining signal, the breaker-and-a-half application of the
restricted ground fault must be approached with care, and is not recommended unless the settings are carefully selected
to avoid maloperation due to CT saturation.
The differential current is produced as an unbalance current between the ground current of the neutral CT (IG) and the
neutral current derived from the phase CTs (IN = IA + IB + IC):
Igd = |IG + IN| = |IG + IA + IB + IC| Eq. 5-21
The restraining signal ensures stability of protection during CT saturation conditions and is produced as a maximum value
among three components related to zero, negative, and positive-sequence currents of the three phase CTs as follows:
Irest = max(IR0, IR1, IR2) Eq. 5-22
The zero-sequence component of the restraining signal (IR0) is meant to provide maximum restraint during external
ground faults, and therefore is calculated as a vectorial difference of the ground and neutral currents:
IR0 = |IG - IN| = |IG - (IA + IB + IC)| Eq. 5-23
The equation above brings an advantage of generating the restraining signal of twice the external ground fault current,
while reducing the restraint below the internal ground fault current. The negative-sequence component of the restraining
signal (IR2) is meant to provide maximum restraint during external phase-to-phase faults and is calculated as follows:
IR2 = |I_2| or IR2 = 3 x |I_2| Eq. 5-24
Following complete de-energization of the windings (all three phase currents below 5% of nominal for at least five cycles),
the relay uses a multiplier of 1 in preparation for the next energization. The multiplier of 3 is used during normal operation;
that is, two cycles after the winding has been energized. The lower multiplier is used to ensure better sensitivity when
energizing a faulty winding.
The positive-sequence component of the restraining signal (IR1) is adaptive and provides restraint during symmetrical
conditions, either symmetrical faults or load.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-299


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Additionally, the algorithm detects a long-lasting DC during energization, which can saturate line CTs and increase IR1.
Long lasting DC in phase A (same in other two phases) is estimated with the following condition:
DC_A = |I_ARMS - 9 x I_AMAG / 8| > 0 Eq. 5-25
When this condition is satisfied in any phase for three cycles, DCACTIVE is set and is reset in 60 cycles once the condition
disappears. Overall IR1 is calculated according to the following algorithm:
IF |I_1| > 2 pu AND |I_1| > |I_0|, THEN IR1 = 3 × (I_1MAG - I_0MAG)
IF DCACTIVE THEN IR1 = I_1MAG / 2
OTHERWISE IR1 = I_1MAG / 8
During an external fault involving ground when positive-sequence current exceeds 200% of the phase CT nominal and
positive-sequence current exceeds zero-sequence current, IR1 restraint is set to the maximum value. During energization
with the long-lasting DC, IR1 is set to half of the positive-sequence current to ensure extra restraint. If none of two
conditions are present, then IR1 is set to the minimum value of the 1/8 of the positive-sequence current to ensure
sensitivity during load conditions.
The raw restraining signal (Irest) is further post-filtered for better performance during external faults with heavy CT
saturation and for better switch-off transient control:
Igr(k) = max(Irest(k), α x Igr(k - 1)) Eq. 5-26
where
k represents a present sample
k – 1 represents the previous sample
α is a factory constant (α < 1)
The equation above introduces a decaying memory to the restraining signal. Should the raw restraining signal (Irest)

5 disappear or drop significantly, such as when an external fault gets cleared or a CT saturates heavily, the actual
restraining signal (Igr(k)) does not reduce instantly but keeps decaying decreasing its value by 50% each 15.5 power
system cycles.
For additional security, the element applies a ground current of the transformer neutral CT (IG) supervision by allowing
element pickup and operation when the IG magnitude is above 0.8 x Pickup setting.
Having the differential and restraining signals developed, the element applies a single slope differential characteristic with
a minimum pickup as shown in the following logic diagram.

5-300 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-151: Restricted ground fault logic

6(77,1*
5(67'*1')7
)81&7,21 6(77,1*
(QDEOHG  5(67'*1')7
3,&.83
6(77,1*6
6(77,1* 581
$1' ,JG!3,&.83 5(67'*1')73,&.83
5(67'*1')7 '(/$<
%/2&. )/(;/2*,&23(5$1'6
5(67'*1')75(6(7
2II  581 5(67'*1')73.3
'(/$<
,*![3,&.83 $1' 5(67'*1')7'32
W 3.3 5(67'*1')723
6(77,1* W 567
5(67'*1')7 6(77,1*
6285&(
5(67'*1')7
,* 6/23(
,1 'LIIHUHQWLDO 581
DQG
,B
5HVWUDLQLQJ
,B &XUUHQWV 
,JG х6/23([ _,JU_
,B $&78$/9$/8(6
5*),JG0DJ
5*),JU0DJ

$FGU

The following examples explain how the restraining signal is created for maximum sensitivity and security. These examples
clarify the operating principle and provide guidance for testing of the element. 5
Example 1: External single-line-to-ground fault
Given the following inputs: IA = 1 pu ∠0°, IB = 0, IC = 0, and IG = 1 pu ∠180°
The relay calculates the following values:

1 1 1e3
Igd = 0, IR0 = abs §© 3 u -- – – 1 ·¹ = 2 pu , IR2 = 3 u -- = 1 pu , IR1 = --------- = 0.042 pu , and Igr = 2 pu
3 3 8

The restraining signal is twice the fault current. This gives extra margin if the phase or neutral CT saturates.

Example 2: External high-current SLG fault


Given the following inputs: IA = 10 pu ∠0°, IB = 0, IC = 0, and IG = 10 pu ∠–180°
The relay calculates the following values:

§ 1 10 10 10
Igd = 0, IR0 = abs © 3 u -- – – 10 · = 20 pu , IR2 = 3 u ----- = 10 pu , IR1 = 3 u § ----- – -----· = 0 , and Igr = 20 pu
3 ¹ 3 ©3 3¹

Example 3: External high-current three-phase symmetrical fault


Given the following inputs: IA = 10 pu ∠0°, IB = 10 pu ∠–120°, IC = 10 pu ∠120°, and IG = 0 pu
The relay calculates the following values:

Igd = 0, IR0 = abs 3 u 0 – 0 = 0 pu , IR2 = 3 u 0 = 0 pu , IR1 = 3 u § 10


----- – 0· = 10 pu , and Igr = 10 pu
©3 ¹

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-301


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Example 4: Internal low-current single-line-to-ground fault under full load


Given the following inputs: IA = 1.10 pu ∠0°, IB = 1.0 pu ∠–120°, IC = 1.0 pu ∠120°, and IG = 0.05 pu ∠0°
The relay calculates the following values:
I_0 = 0.033 pu ∠0°, I_2 = 0.033 pu ∠0°, and I_1 = 1.033 pu ∠0°
Igd = abs(3 × 0.0333 + 0.05) = 0.15 pu, IR0 = abs(3 × 0.033 – (0.05)) = 0.05 pu, IR2 = 3 × 0.033 = 0.10 pu,
IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu
Despite very low fault current level, the differential current is above 100% of the restraining current.

5.8.8 Negative sequence current

5.8.8.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT
 NEGATIVE SEQUENC  NEG SEQ TOC1 See below
 CURRENT  

 NEG SEQ TOC2


 

 NEG SEQ IOC1 See page 5-303


 

 NEG SEQ IOC2


 

5   NEG SEQ DIR OC1



See page 5-304

 NEG SEQ DIR OC2


 

The F60 provides two negative-sequence time overcurrent elements, two negative-sequence instantaneous overcurrent
elements, and two negative-sequence directional overcurrent elements. For information on the negative sequence time
overcurrent curves, see the Inverse TOC Curve Characteristics section earlier.

5.8.8.2 Negative sequence time overcurrent (ANSI 51Q, IEC PTOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ TOC1(2)
 NEG SEQ TOC1 NEG SEQ TOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEG SEQ TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEG SEQ TOC1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

NEG SEQ TOC1 Range: see Overcurrent Curve Types table


 CURVE: IEEE Mod Inv

NEG SEQ TOC1 Range: 0.00 to 600.00 in steps of 0.01


 TD MULTIPLIER: 1.00

NEG SEQ TOC1 Range: Instantaneous, Timed


 RESET: Instantaneous

NEG SEQ TOC1 BLOCK: Range: FlexLogic operand


 Off

NEG SEQ TOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

5-302 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

NEG SEQ TOC1 Range: Disabled, Enabled


 EVENTS: Disabled

The negative-sequence time overcurrent element can be used to determine and clear unbalance in the system. The input
for calculating negative-sequence current is the fundamental phasor value.
Two methods of resetting operation are available; “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator clears immediately.
Figure 5-152: Negative sequence TOC1 logic
SETTING

NEG SEQ TOC1 INPUT:

NEG SEQ TOC1 PICKUP:

SETTING NEG SEQ TOC1 CURVE:

NEG SEQ TOC1 FUNCTION:


NEG SEQ TOC1 TD MULTIPLIER:
Enabled=1
FLEXLOGIC OPERANDS
NEG SEQ TOC1 RESET:
NEG SEQ TOC1 PKP
SETTING
AND RUN NEG SEQ < PICKUP NEG SEQ TOC1 DPO
NEG SEQ TOC1 BLOCK: NEG SEQ TOC1 OP

Off=0
t

SETTING

NEG SEQ TOC1 SOURCE: 5


Neg Seq 827057A5.CDR

5.8.8.3 Negative sequence instantaneous overcurrent (ANSI 50Q, IEC PIOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ OC1(2)
 NEG SEQ IOC1 NEG SEQ IOC1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEG SEQ IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEG SEQ IOC1 Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.000 pu

NEG SEQ IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

NEG SEQ IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

NEG SEQ IOC1 BLOCK: Range: FlexLogic operand


 Off

NEG SEQ IOC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

NEG SEQ IOC1 Range: Disabled, Enabled


 EVENTS: Disabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-303


GROUPED ELEMENTS CHAPTER 5: SETTINGS

The negative-sequence instantaneous overcurrent element can be used as an instantaneous function with no intentional
delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency
phasor magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance:
a small portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current
magnitude when forming the operating quantity.
Iop = |I_2| - K x |I_1| where K = 1/8 Eq. 5-27
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence
currents resulting from
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during three-phase faults
• Fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how the test currents are injected into the relay (single-phase injection:
Iop = 0.2917 x Iinjected; three-phase injection, opposite rotation: Iop = Iinjected).
Figure 5-153: Negative sequence IOC1 logic

SETTING
SETTING
NEG SEQ IOC1 FUNCTION: NEG SEQ IOC1
SETTING PICKUP DELAY:
Enabled=1 FLEXLOGIC OPERANDS
NEG SEQ IOC1
NEG SEQ IOC1 PICKUP: NEG SEQ IOC1 PKP
RESET DELAY:
SETTING NEG SEQ IOC1 DPO
AND RUN tPKP
tRST NEG SEQ IOC1 OP
NEG SEQ IOC1 BLOCK: I_2 - K I_1 PICKUP

5 Off=0

SETTING

NEG SEQ IOC1 SOURCE:

I_2 827058A6.CDR

5.8.8.4 Negative sequence directional overcurrent (ANSI 67Q, IEC PDEF/PTOC)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ DIR
OC1(2)
 NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEG SEQ DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEG SEQ DIR OC1 Range: 0.00 to 250.00 ohms in steps of 0.01
 OFFSET: 0.00 Ω

NEG SEQ DIR OC1 Range: Neg Sequence, Zero Sequence


 TYPE: Neg Sequence

NEG SEQ DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
 SEQ RESTRAINT: 0.063

NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1


 ECA: 75° Lag

NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1


 LIMIT ANGLE: 90°

NEG SEQ DIR OC1 FWD Range: 0.015 to 30.000 pu in steps of 0.005
 PICKUP: 0.050 pu

5-304 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

NEG SEQ DIR OC1 REV Range: 40 to 90° in steps of 1


 LIMIT ANGLE: 90°

NEG SEQ DIR OC1 REV Range: 0.015 to 30.000 pu in steps of 0.005
 PICKUP: 0.050 pu

NEG SEQ DIR OC1 BLK: Range: FlexLogic operand


 Off

NEG SEQ DIR OC1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

NEG SEQ DIR OC1 Range: Disabled, Enabled


 EVENTS: Disabled

There are two negative-sequence directional overcurrent protection elements available. The element provides both
forward and reverse fault direction indications through its output operands NEG SEQ DIR OC1 FWD and NEG SEQ DIR
OC1 REV, respectively. The output operand is asserted if the magnitude of the operating current is above a pickup level
(overcurrent unit) and the fault direction is seen as forward or reverse, respectively (directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a fundamental frequency phasor of either the
negative-sequence or neutral current as per user selection.
A positive-sequence restraint is applied for better performance: a small user-programmable portion of the positive-
sequence current magnitude is subtracted from the negative or zero-sequence current magnitude, respectively, when
forming the element operating quantity.
Iop = |I_2| - K x |I_1| or Iop = 3 x (|I_0| - K x |I_1|) Eq. 5-28
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and
zero-sequence currents resulting from
• System unbalances under heavy load conditions 5
• Transformation errors of current transformers (CTs)
• Fault inception and switch-off transients
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant K to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The operating quantity depends on the way the test currents are injected into the F60. For single phase injection
• Iop = ⅓ × (1 – K) × Iinjected for I_2 mode
• Iop = (1 – K) × Iinjected for I_0 mode if I_1 > 0.8 pu
The directional unit uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5-44: Negative-sequence directional overcurrent unit
Mode Operating current
Negative-sequence Iop = |I_2| – K × I_1|
Zero-sequence Iop = 3 × (|I_0| – K × |I_1|) if |I_1| > 0.8 pu
Iop = 3 × |I_0| if |I_1| ≤ 0.8 pu

Table 5-45: Negative-sequence directional unit


Direction Compared phasors
Forward –V_2 + Z_offset × I_2 I_2 × 1∠ECA
Reverse –V_2 + Z_offset × I_2 –(I_2 × 1∠ECA)

Z_offset is the offset impedance, for which magnitude is the OFFSET setting and angle is the FWD ECA.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-305


GROUPED ELEMENTS CHAPTER 5: SETTINGS

The negative-sequence voltage must be greater than PRODUCT SETUP  DISPLAY PROPERTIES  VOLTAGE CUT-OFF LEVEL
to be validated for use as polarizing signal. Additionally, when offset impedance is applied and negative-sequence current
is above 0.2 pu, compensated negative-sequence voltage -V_2 + Z_offset x I_2 has to be above 0.02 pu in order to
discriminate fault direction; otherwise when negative-sequence current is less than 0.2 pu, -V_2 is then used as the
polarizing signal. If the polarizing signal is not validated, neither forward nor reverse indication is given. The following figure
explains the usage of the voltage polarized directional unit of the element. It shows the phase angle comparator
characteristics for a phase A to ground fault, with settings of
ECA = 75° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA = 80° (reverse limit angle = ± the angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication is delayed by 1.5 of a power system cycle. The element emulates an
electromechanical directional device. Larger operating and polarizing signals result in faster directional discrimination,
bringing more security to the element operation.
Figure 5-154: Negative-sequence directional characteristic

FO"\Y^U

B5F 6G4
<1 <1 F17bUVUbU^SU

B5F?`UbQdY^W
BUWY_^

5 <1

531\Y^U
<1 531

9O"\Y^U

9O"\Y^U <1
6G4?`UbQdY^W
BUWY_^
531\Y^U

<1

F37 F27

B5F 6G4
<1 <1
FO"\Y^U ("'( &1"34B

The forward-looking function is designed to be more secure compared to the reverse-looking function, so use the forward-
looking function for the tripping direction. The reverse-looking function is faster compared to the forward-looking function,
so use the reverse-looking function for the blocking direction. This allows for better protection coordination. Take this bias
into account when using the negative-sequence directional overcurrent element to directionalize other protection
elements. The negative-sequence current must be greater than the PRODUCT SETUP  DISPLAY PROPERTIES CURRENT
CUT-OFF LEVEL setting value.

5-306 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Settings
NEG SEQ DIR OC1 OFFSET — Specifies the offset impedance used by this protection. The primary application for the offset
impedance is to guarantee correct identification of fault direction on series compensated lines (see the Application of
Settings chapter for information on how to calculate this setting). In regular applications, the offset impedance ensures
proper operation even if the negative-sequence voltage at the relaying point is very small. If this is the intent, the offset
impedance shall not be larger than the negative-sequence impedance of the protected circuit. Practically, it is several
times smaller. Enter the offset impedance in secondary ohms.
NEG SEQ DIR OC1 TYPE — Selects the operating mode for the overcurrent unit of the element. The choices are “Neg
Sequence” and “Zero Sequence.” In some applications it is advantageous to use a directional negative-sequence
overcurrent function instead of a directional zero-sequence overcurrent function as inter-circuit mutual effects are
minimized.
NEG SEQ DIR OC1 POS-SEQ RESTRAINT — Controls the positive-sequence restraint. Set it to 0.063 (in “Zero Sequence” mode)
or 0.125 (in “Neg Sequence” mode) for backward compatibility with revisions 3.40 and earlier. Set it to zero to remove the
restraint. Set it higher if large system unbalances or poor CT performance are expected.
NEG SEQ DIR OC1 FWD ECA — Select the element characteristic angle (ECA) for the forward direction. The element
characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°.
NEG SEQ DIR OC1 FWD LIMIT ANGLE — Defines a symmetrical limit angle (in both directions from the ECA) for the forward
direction.
NEG SEQ DIR OC1 FWD PICKUP — Defines the pickup level for the overcurrent unit in the forward direction. This pickup
threshold applies to zero-sequence or negative-sequence current based on the NEG SEQ DIR OC1 TYPE setting. When
specifying this setting, keep in mind that the design uses a positive-sequence restraint technique.
NEG SEQ DIR OC1 REV LIMIT ANGLE — Defines a symmetrical limit angle (in both directions from the ECA) for the reverse
direction.
NEG SEQ DIR OC1 REV PICKUP — Defines the pickup level for the overcurrent unit in the reverse direction. This pickup 5
threshold applies to zero-sequence or negative-sequence current based on the NEG SEQ DIR OC1 TYPE setting. When
selecting this setting, keep in mind that the design uses a positive-sequence restraint technique.
Figure 5-155: Negative-sequence directional OC1 logic
SETTINGS
Forward Pickup
Positive-Sequence Restraint
AND RUN
( |3I_0| –K × |I_1| ) = Pickup
OR
AND RUN
( |I_2| –K × |I_1| ) = Pickup AND
SETTING
Function FLEXLOGIC OPERAND
Enabled = 1 SETTINGS AND NEG SEQ DIR OC1 FWD
Forward ECA
SETTING AND Forward Limit Angle
Block Reverse Limit Angle
Off = 0 Offset
TIMER
RUN 1.25 cycles
Forward Forward AND
ACTUAL VALUES 1.5 cycles
V_2 V2 V_cutoff Reverse
I_2 I2 I_cutoff
I_0 V_2pol Reverse
I0 I_cutoff
NOTE: Voltage Polarization
V_2 is negative-sequence voltage
I_2 is negative-sequence current
I_0 is zero-sequence current
SETTINGS
Reverse Pickup
Pos Seq Restraint AND
AND RUN
SETTING
Type ( |I_2| –K × |I_1| ) = Pickup
= Neg Sequence OR FLEXLOGIC OPERAND
AND RUN
= Zero Sequence NEG SEQ DIR OC1 REV
( |3I_0| –K × |I_1| ) = Pickup
827196A1.vsdx

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-307


GROUPED ELEMENTS CHAPTER 5: SETTINGS

5.8.9 Breaker failure (ANSI 50BF)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  BREAKER FAILURE  BREAKER FAILURE 1(4)
 BREAKER FAILURE 1 BF1 FUNCTION: Range: Disabled, Enabled
  Disabled

BF1 MODE: Range: 3-Pole, 1-Pole


 3-Pole

BF1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

BF1 USE AMP SUPV: Range: Yes, No


 Yes

BF1 USE SEAL-IN: Range: Yes, No


 Yes

BF1 3-POLE INITIATE: Range: FlexLogic operand


 Off

BF1 BLOCK: Range: FlexLogic operand


 Off

BF1 RETRIP PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.033 s

BF1 PH AMP SUPV Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.050 pu

BF1 N AMP SUPV Range: 0.020 to 30.000 pu in steps of 0.001



5 PICKUP: 1.050 pu

BF1 USE TIMER 1: Range: Yes, No


 Yes

BF1 TIMER 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BF1 USE TIMER 2: Range: Yes, No


 Yes

BF1 TIMER 2 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BF1 USE TIMER 3: Range: Yes, No


 Yes

BF1 TIMER 3 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BF1 BKR POS1 φA/3P: Range: FlexLogic operand


 Off

BF1 BKR POS2 φA/3P: Range: FlexLogic operand


 Off

BF1 BKR TEST ON: Range: FlexLogic operand


 Off

BF1 PH AMP HISET Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.050 pu

BF1 N AMP HISET Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.050 pu

BF1 PH AMP LOSET Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.050 pu

BF1 N AMP LOSET Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 1.050 pu

5-308 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

BF1 LOSET TIME Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BF1 TRIP DROPOUT Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BF1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

BF1 EVENTS: Range: Disabled, Enabled


 Disabled

BF1 PH A INITIATE: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 PH B INITIATE: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 PH C INITIATE: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 BKR POS1 φB: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 BKR POS1 φC: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 BKR POS2 φB: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes

BF1 BKR POS2 φC: Range: FlexLogic operand


 Off Valid only for 1-Pole breaker failure schemes
5
A breaker failure scheme determines that a breaker signaled to trip has not cleared a fault within a definite time, so further
tripping action must be performed. Tripping from the breaker failure scheme trips all breakers, both local and remote, that
can supply current to the faulted zone. Usually operation of a breaker failure element causes clearing of a larger section of
the power system than the initial trip. Because breaker failure can result in tripping a large number of breakers and this
affects system safety and stability, a very high level of security is required.
Two schemes are provided: one for three-pole tripping only (identified by the name “3BF”) and one for three pole plus
single-pole operation (identified by the name “1BF”). The philosophy used in these schemes is identical. The operation of a
breaker failure element includes three stages: initiation, determination of a breaker failure condition, and output.

5.8.9.1 Stage 1: Initiation


A FlexLogic operand representing the protection trip signal initially sent to the breaker must be selected to initiate the
scheme. The initiating signal is sealed-in if primary fault detection can reset before the breaker failure timers have finished
timing. The seal-in is supervised by current level, so it is reset when the fault is cleared. If desired, an incomplete sequence
seal-in reset can be implemented by using the initiating operand to also initiate a FlexLogic timer, set longer than any
breaker failure timer, whose output operand is selected to block the breaker failure scheme.
Schemes can be initiated either directly or with current level supervision. It is particularly important in any application to
decide if a current-supervised initiate is to be used. The use of a current-supervised initiate results in the breaker failure
element not being initiated for a breaker that has very little or no current flowing through it, which can be the case for
transformer faults. For those situations where it is required to maintain breaker fail coverage for fault levels below the BF1
PH AMP SUPV PICKUP or the BF1 N AMP SUPV PICKUP setting, do not use a current supervised initiate. Utilize this feature for
those situations where coordinating margins can be reduced when high speed reclosing is used. Thus, if this choice is
made, fault levels must always be above the supervision pickup levels for dependable operation of the breaker fail scheme.
This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes into a fault; the
protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of closing, but does
not yet have current flowing through it.
When the scheme is initiated, it sends a trip signal after a pickup delay to the breaker initially signaled to trip (this feature is
usually described as re-trip). This reduces the possibility of widespread tripping that results from a declaration of a failed
breaker.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-309


GROUPED ELEMENTS CHAPTER 5: SETTINGS

5.8.9.2 Stage 2: Determination of a breaker failure condition


The schemes determine a breaker failure condition via three paths. Each of these paths is equipped with a time delay, after
which a failed breaker is declared and trip signals are sent to all breakers required to clear the zone. The delayed paths are
associated with breaker failure Timers 1, 2, and 3, which are intended to have delays increasing with increasing timer
numbers. These delayed paths are individually enabled to allow for maximum flexibility.
Timer 1 logic (early path) is supervised by a fast-operating breaker auxiliary contact. If the breaker is still closed (as
indicated by the auxiliary contact) and fault current is detected after the delay interval, an output is issued. Operation of
the breaker auxiliary switch indicates mechanical operation of breaker. The continued presence of current indicates that
the breaker has failed to interrupt the circuit.
Timer 2 logic (main path) is not supervised by a breaker auxiliary contact. If fault current is detected after the delay
interval, an output is issued. This path is intended to detect a breaker that opens mechanically but fails to interrupt fault
current; the logic therefore does not use a breaker auxiliary contact.
The Timer 1 and 2 paths provide two levels of current supervision, HISET and LOWSET, that allow the supervision level to
change from a current that flows before a breaker inserts an opening resistor into the faulted circuit to a lower level after
resistor insertion. The HISET detector is enabled after timeout of Timer 1 or 2, along with a timer that enables the LOWSET
detector after its delay interval. The delay interval between HISET and LOWSET is the expected breaker opening time. Both
current detectors provide a fast operating time for currents at small multiples of the pickup value. The overcurrent
detectors are required to operate after the breaker failure delay interval in case current still flows through the breaker, and
they are supervised by a fast reset element described as follows.
The BFx LOSET TIME DELAY is based on the time that breaker resistor limited current can flow through the circuit after the
breaker interruption time. Both current detectors provide fast operating time for small multiples of the pickup setting.
Timer 3 logic (slow path) is supervised by a breaker auxiliary contact and a control switch contact used to indicate that the
breaker is in or out-of-service, disabling this path when the breaker is out-of-service for maintenance. There is no current
5 level check in this logic as it is intended to detect low magnitude faults and it is therefore the slowest to operate.

5.8.9.3 Stage 3: Output


The outputs from the schemes are:
• FlexLogic operands that report on the operation of portions of the scheme
• FlexLogic operand used to re-trip the protected breaker
• FlexLogic operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an
adjustable period.
• Target message indicating a failed breaker has been declared
• Illumination of the front panel Trip LED (and the Phase A, B, or C LED, if applicable)

5.8.9.4 Main path sequence


Figure 5-156: Breaker failure main path sequence
ACTUAL CURRENT MAGNITUDE
FAILED INTERRUPTION
0
AMP CALCULATED CURRENT MAGNITUDE
CORRECT INTERRUPTION
Rampdown
0
PROTECTION OPERATION BREAKER INTERRUPTING TIME
(ASSUMED 1.5 cycles) (ASSUMED 3 cycles)
MARGIN BACKUP BREAKER OPERATING TIME
(Assumed 2 Cycles) (Assumed 3 Cycles)

BREAKER FAILURE TIMER No. 2 (±1/8 cycle)


INITIATE (1/8 cycle)

BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle)


BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle)

FAULT cycles
OCCURS
0 1 2 3 4 5 6 7 8 9 10 11

827083A6.CDR

The current supervision elements reset in less than 0.7 of a power cycle for any multiple of pickup current as shown in the
following figure.

5-310 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-157: Breaker failure overcurrent supervision reset time

0.8
Margin
Maximum

Breaker failure reset time (cycles)


Average
0.6

0.4

0.2

0
0 20 40 60 80 100 120 140
MulWLple of pickup fault current
threshold setting 836769A4.CDR

5.8.9.5 Settings
BF1 MODE — This setting is used to select the breaker failure operating mode: single or three pole.
BF1 USE AMP SUPV — If set to “Yes” the element is initiated if current flowing through the breaker is above the supervision
pickup level. 5
BF1 USE SEAL-IN — If set to “Yes” the element is sealed-in if current flowing through the breaker is above the supervision
pickup level.
BF1 3-POLE INITIATE — This setting selects the FlexLogic operand that initiates three-pole tripping of the breaker.
BF1 RETRIP PICKUP DELAY — This setting specifies a pickup delay for the re-trip command. Set this delay longer than the
possible spurious contact input activation duration due to transients or temporary DC grounds, taking into account the
contact input de-bounce time to avoid re-trip operation for such transients.
BF1 PH AMP SUPV PICKUP — This setting is used to set the phase current initiation and seal-in supervision level. Generally this
setting detects the lowest expected fault current on the protected breaker. It can be set as low as necessary (lower than
breaker resistor current or lower than load current)—HISET and LOWSET current supervision guarantee correct operation.
BF1 N AMP SUPV PICKUP — This setting is used to set the neutral current initiate and seal-in supervision level. Generally this
setting detects the lowest expected fault current on the protected breaker. Neutral current supervision is used only in the
three phase scheme to provide increased sensitivity. This setting is valid only for three-pole tripping schemes.
BF1 USE TIMER 1 — If set to “Yes” the early path is operational.
BF1 TIMER 1 PICKUP DELAY — Timer 1 is set to the shortest time required for breaker auxiliary contact Status-1 to open, from
the time the initial trip signal is applied to the breaker trip circuit, plus a safety margin.
BF1 USE TIMER 2 — If set to “Yes” the main path is operational.
BF1 TIMER 2 PICKUP DELAY — Timer 2 is set to the expected opening time of the breaker, plus a safety margin. This safety
margin was historically intended to allow for measuring and timing errors in the breaker failure scheme equipment. In
microprocessor relays this time is not significant. In F60 relays, which use a Fourier transform, the calculated current
magnitude ramps-down to zero one power frequency cycle after the current is interrupted, however this lag does not need
to be included in the overall margin duration due to a novel current supervision reset element, as it occurs after current
interruption. As shown in the previous figure, this current supervision reset element guarantees breaker failure reset in less
than 0.7 power cycles for any subsidence current and irrespective of the magnitude of the fault current.
Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be
significantly longer than the normal interrupting time.
BF1 USE TIMER 3 — If set to “Yes” the Slow Path is operational.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-311


GROUPED ELEMENTS CHAPTER 5: SETTINGS

BF1 TIMER 3 PICKUP DELAY — Timer 3 is set to the same interval as Timer 2, plus an increased safety margin. Because this
path is intended to operate only for low level faults, the delay can be in the order of 300 to 500 ms.
BF1 BKR POS1 φA/3P — This setting selects the FlexLogic operand that represents the protected breaker early-type auxiliary
switch contact (52/a). When using the single-pole breaker failure scheme, this operand represents the protected breaker
early-type auxiliary switch contact on pole A. This is normally a non-multiplied form-A contact. The contact can even be
adjusted to have the shortest possible operating time.
BF1 BKR POS2 φA/3P — This setting selects the FlexLogic operand that represents the breaker normal-type auxiliary switch
contact (52/a). When using the single-pole breaker failure scheme, this operand represents the protected breaker auxiliary
switch contact on pole A. This can be a multiplied contact.
BF1 BKR TEST ON — This setting is used to select the FlexLogic operand that represents the breaker in-service/out-of-service
switch set to the out-of-service position.
BF1 PH AMP HISET PICKUP — This setting sets the phase current output supervision level. Generally this setting is to detect
the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted.
BF1 N AMP HISET PICKUP — This setting sets the neutral current output supervision level. Generally this setting is to detect
the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted. Neutral current
supervision is used only in the three pole scheme to provide increased sensitivity. This setting is valid only for three-pole
breaker failure schemes.
BF1 PH AMP LOSET PICKUP — This setting sets the phase current output supervision level. Generally this setting is to detect
the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted (approximately 90%
of the resistor current).
BF1 N AMP LOSET PICKUP — This setting sets the neutral current output supervision level. Generally this setting is to detect
the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted (approximately 90%
of the resistor current). This setting is valid only for three-pole breaker failure schemes.
5 BF1 LOSET TIME DELAY — Sets the pickup delay for current detection after opening resistor insertion.
BF1 TRIP DROPOUT DELAY — This setting is used to set the period of time for which the trip output is sealed-in. This timer
must be coordinated with the automatic reclosing scheme of the failed breaker, to which the breaker failure element sends
a cancel reclosure signal. Reclosure of a remote breaker can also be prevented by holding a transfer trip signal on longer
than the reclaim time.
BF1 PH A INITIATE / BF1 PH B INITIATE / BF1 PH C INITIATE — These settings select the FlexLogic operand to initiate phase A, B,
or C single-pole tripping of the breaker and the phase A, B, or C portion of the scheme, accordingly. This setting is only valid
for single-pole breaker failure schemes.
BF1 BKR POS1 φB / BF1 BKR POS 1 φC — These settings select the FlexLogic operand to represents the protected breaker
early-type auxiliary switch contact on poles B or C, accordingly. This contact is normally a non-multiplied Form-A contact.
The contact can even be adjusted to have the shortest possible operating time. This setting is valid only for single-pole
breaker failure schemes.
BF1 BKR POS2 φB — Selects the FlexLogic operand that represents the protected breaker normal-type auxiliary switch
contact on pole B (52/a). This can be a multiplied contact. This setting is valid only for single-pole breaker failure schemes.
BF1 BKR POS2 φC — This setting selects the FlexLogic operand that represents the protected breaker normal-type auxiliary
switch contact on pole C (52/a). This can be a multiplied contact. For single-pole operation, the scheme has the same
overall general concept except that it provides re-tripping of each single pole of the protected breaker. The approach
shown in the following single pole tripping diagram uses the initiating information to determine which pole is supposed to
trip. The logic is segregated on a per-pole basis. The overcurrent detectors have ganged settings. This setting is valid only
for single-pole breaker failure schemes.
Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command needs to be
given via output operand BKR FAIL 1 TRIP OP.

5-312 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

5.8.9.6 Logic
Figure 5-158: Single-pole breaker failure, initiate logic
SETTINGS
Function
Enabled = 1
AND
Block
Off = 0

FLEXLOGIC OPERAND
TRIP PHASE A
from the trip output element
OR Initiated
SETTING To breaker failure
Phase A Initiate single-pole logic sheet 2
Off = 0 OR SETTING
BF1 RETRIP PICKUP
DELAY FLEXLOGIC OPERAND
FLEXLOGIC OPERAND OR
TRIP 3-POLE AND BKR FAIL 1 RETRIP A
0
from the trip output element

OR Initiated phase A
SETTING
Three-Pole Initiate To breaker failure
Off = 0 single-pole logic sheet 2

SETTING
AND
Use Seal-In
Yes = 1
Seal-in path
No = 0

AND OR
SETTING OR
Use Current Supervision
Yes = 1 SETTING
No = 0 OR BF1 RETRIP PICKUP
AND DELAY FLEXLOGIC OPERAND
FLEXLOGIC OPERAND AND BKR FAIL 1 RETRIP B
Seal-in path 0
TRIP PHASE B
from the trip output element
Initiated phase B
OR OR

5
SETTING To breaker failure
single-pole logic sheet 2
Phase B Initiate
Off = 0

OR
FLEXLOGIC OPERAND
AND
TRIP PHASE C SETTING
from the trip output element BF1 RETRIP PICKUP
OR DELAY FLEXLOGIC OPERAND
Seal-in path AND BKR FAIL 1 RETRIP C
SETTING 0
Phase C Initiate SETTING
Off = 0 Phase Current Initiated phase C
Supervision Pickup
RUN To breaker failure
IA = Pickup single-pole logic sheet 2
SETTING
SETTING
Source RUN OR
IA IB = Pickup
IB RUN
IC IC = Pickup

IC
to breaker failure
IB
single-pole logic sheet 3
IA
859773A1.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-313


5

5-314
)/(;/2*,&23(5$1'
25 %.5)$,/723
6(77,1*6
%UHDNHU3RV3KDVH$3 )/(;/2*,&23(5$1'
2II  25 %.5)$,/723
8VH7LPHU 6(77,1* 6(77,1*
1R  7LPHU3LFNXS'HOD\ $1' 3KDVH&XUUHQW+L6HW3LFNXS
<HV 
GROUPED ELEMENTS

581
25
$1' ,$ 3LFNXS

,QLWLDWHGSKDVH$
IURPVLQJOHSROHEUHDNHU 6(77,1*
IDLOXUHORJLFVKHHW 6(77,1*
7LPHU3LFNXS'HOD\ /R6HW7LPH'HOD\ 6(77,1*
3KDVH&XUUHQW/R6HW3LFNXS
6(77,1*
$1' 581
8VH7LPHU
 
<HV  ,$ 3LFNXS
1R 

6(77,1*
6(77,1*6
7LPHU3LFNXS'HOD\ $1' 6(77,1*
%UHDNHU3RV3KDVH%
3KDVH&XUUHQW+L6HW3LFNXS
2II 
$1' 25 581

,QLWLDWHGSKDVH% ,% 3LFNXS
IURPVLQJOHSROHEUHDNHU 6(77,1*
IDLOXUHORJLFVKHHW 6(77,1*
6(77,1* 7ULS'URSRXW'HOD\
7LPHU3LFNXS'HOD\
/R6HW7LPH'HOD\ 6(77,1*  )/(;/2*,&23(5$1'
3KDVH&XUUHQW/R6HW3LFNXS 25 %.5)$,/75,323
$1'
6(77,1*6 581

%UHDNHU3RV3KDVH% 
,% 3LFNXS
2II 
6(77,1*
6(77,1*
$1' 3KDVH&XUUHQW+L6HW3LFNXS
7LPHU3LFNXS'HOD\
581

$1' 25 ,& 3LFNXS



,QLWLDWHGSKDVH&
IURPVLQJOHSROHEUHDNHU 6(77,1*
IDLOXUHORJLFVKHHW 6(77,1* /R6HW7LPH'HOD\ 6(77,1*
7LPHU3LFNXS'HOD\
3KDVH&XUUHQW/R6HW3LFNXS
581
$1' 
 ,& 3LFNXS

,$
,%
Figure 5-159: Single-pole breaker failure, timers logic

,&

6(77,1*6
8VH7LPHU
<HV 
%UHDNHU3RV3KDVH$3
2II  6(77,1*
%UHDNHU3RV3KDVH% 7LPHU3LFNXS'HOD\
2II  )/(;/2*,&23(5$1'
%UHDNHU3RV3KDVH& $1' %.5)$,/723
2II  
%UHDNHU7HVW2Q
2II 

,QLWLDWHG
IURPVLQJOHSROHEUHDNHUIDLOXUHORJLFVKHHW $&'5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-160: Three-pole breaker failure, initiate logic

SETTING
BF1 FUNCTION:

Disable=0
Enable=1

SETTING AND
BF1 BLOCK:

Off=0

SETTING
BF1 INITIATE: SETTING
FLEXLOGIC OPERAND
BF1 RETRIP PICKUP
DELAY
BKR FAIL 1 RETRIP
Off=0
OR 0

AND
TO SHEET 2 OF 2
SETTING (Initiated)
BF1 USE SEAL-IN:

YES=1
NO=0
AND

Seal In Path
AND
OR

SETTING
BF1 USE AMP SUPV:

YES=1
NO=0 OR

SETTINGS
BF1 PH AMP SUPV
5
PICKUP:

SETTING BF1 N AMP SUPV


BF1 SOURCE: PICKUP:

RUN
IA ³ PICKUP
IA

RUN

IB IB ³ PICKUP
OR
RUN

IC IC ³ PICKUP

RUN
IN ³ PICKUP
IN

TO SHEET 2 OF 2
(827068.cdr)

859775A1.cdr

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-315


5
)5206+((72)
,QLWLDWHG

5-316
6(77,1*
6(77,1* %)7,0(53,&.83
%)86(7,0(5 '(/$< )/(;/2*,&23(5$1'

<(6  $1'  %.5)$,/723


12 
GROUPED ELEMENTS

6(77,1*
%)%.5326Ů$3
)/(;/2*,&23(5$1'

2II  %.5)$,/723

6(77,1*
%)7,0(53,&.83
6(77,1* '(/$<
25
%)86(7,0(5
$1' 
<(6 
12 
6(77,1*6
%)3+$03+,6(7
3,&.83

%)1$03+,6(7
)5206+((72)
3,&.83
,QLWLDWHG
581
,$
,$ t3,&.83

581
,%
,% t3,&.83

581
,&
,& t3,&.83

581
,1
,1 t3,&.83

6(77,1*6
%)3+$03/26(7 6(77,1*
6(77,1* 3,&.83
6(77,1* %)75,3'523287
%)/26(77,0( 7,0('(/$<
%)1$03/26(7 )/(;/2*,&23(5$1'
%)86(7,0(5 '(/$<
3,&.83
25  %.5)$,/75,323
<(6   581
Figure 5-161: Three-pole breaker failure, timers logic

12 
,$ t3,&.83

581
,% t3,&.83
6(77,1*
%)%.5326Ů$3 581
,& t3,&.83

2II  581

6(77,1* ,1 t3,&.83

6(77,1* %)7,0(53,&.83
'(/$<
%)%5($.(57(6721
)/(;/2*,&23(5$1'
$1' 
2II 
%.5)$,/723

$FGU

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
CHAPTER 5: SETTINGS GROUPED ELEMENTS

5.8.10 Voltage elements

5.8.10.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS
 VOLTAGE ELEMENTS  PHASE See below
   UNDERVOLTAGE1

 PHASE
  UNDERVOLTAGE3

 PHASE See page 5-321


  OVERVOLTAGE1

 PHASE
  OVERVOLTAGE3

 NEUTRAL OV1 See page 5-322


 

 NEUTRAL OV3
 

 NEG SEQ OV 1 See page 5-323


 

 NEG SEQ OV 3
5
 

 AUXILIARY UV1 See page 5-324


 

 AUXILIARY UV3
 

 AUXILIARY OV1 See page 5-326


 

 AUXILIARY OV2
 

5.8.10.2 Application of voltage elements


These protection elements can be used for a variety of applications, such as
• Undervoltage protection — For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current, which can cause dangerous overheating in the motor. The undervoltage protection feature can be
used to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a
specified time delay.
• Overvoltage protection — Overvoltage elements can be used to protect voltage sensitive loads and system
components against sustained overvoltage conditions
• Permissive functions — The undervoltage/overvoltage features can be used to block the functioning of external
devices by operating an output relay when the voltage falls below/exceeds the specified voltage setting. The
undervoltage/overvoltage features can also be used to block the functioning of other elements through the block
feature of those elements.
• Source transfer schemes — In the event of undervoltage/overvoltage, a transfer signal can be generated to transfer
a load from its normal source to a standby or emergency power source

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-317


GROUPED ELEMENTS CHAPTER 5: SETTINGS

5.8.10.3 Undervoltage inverse time curves


The undervoltage elements can be programmed to have an inverse time delay characteristic. If in the respective element
the CURVE setting is set to Inverse Time, the undervoltage delay setting establishes the operating curve of the element as
follows:

D
T = ------------------------------
V ·
§ 1 – --------------- - Eq. 5-29
© V pickup¹

where
T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
Vpickup = pickup level
For reset time, see the settings section of the applicable element.
Figure 5-162: Inverse time undervoltage curves
Time (seconds)

% of voltage pickup
842788A1.CDR

At 0% of pickup, the operating time equals the corresponding undervoltage element DELAY setting.

5.8.10.4 Overvoltage inverse time curves


The overvoltage elements can be programmed to have an inverse time delay characteristic. If in the respective element
the CURVE setting is set to Inverse Time, the overvoltage pickup delay setting establishes the operating curve of the
element as follows:
T= D/ (V/Vpickup -1) Eq. 5-30
where
T = operate time
D = overvoltage pickup delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
Vpickup = pickup level
For reset time, see the settings section of the applicable element.

5-318 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-163: Inverse time overvoltage curve









7LPH VHFRQGV





' 

' 


' 


          

5
RIYROWDJHSLFNXS
$&'5

5.8.10.5 Phase undervoltage (ANSI 27P, IEC PTUV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  PHASE UNDERVOLTAGE1(3)
 PHASE PHASE UV1 Range: Disabled, Enabled
 UNDERVOLTAGE1  FUNCTION: Disabled

PHASE UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

PHASE UV1 MODE: Range: Phase to Ground, Phase to Phase


 Phase to Ground

PHASE UV1 Range: 0.004 to 3.000 pu in steps of 0.001


 PICKUP: 1.000 pu

PHASE UV1 Range: Definite Time, Inverse Time, FlexCurves A


 CURVE: Definite Time through D

PHASE UV1 Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

PHASE UV1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

PHASE UV1 MINIMUM Range: 0.000 to 3.000 pu in steps of 0.001


 VOLTAGE: 0.100 pu

PHASE UV1 BLOCK: Range: FlexLogic operand


 Off

PHASE UV1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PHASE UV1 Range: Disabled, Enabled


 EVENTS: Disabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-319


GROUPED ELEMENTS CHAPTER 5: SETTINGS

This element is used to give a time-delay operating characteristic versus the applied fundamental voltage.
PHASE UV1 SIGNAL SOURCE — Selects the signal source for the phase undervoltage protection element.
PHASE UV1 MODE — This setting defines the mode of operation that can be Phase-to-Phase or Phase-to-Ground voltage.
Phase-to-ground or phase-to-phase voltages can be applied for wye VT connection, while phase-to-phase voltages can be
applied for delta VT connections only.
PHASE UV1 PICKUP — This setting specifies the phase undervoltage protection element pickup level.
PHASE UV1 CURVE — This setting defines the timing characteristic of the element, which can be Definite Time, Inverse Time
(per the curves described earlier in the Voltage Elements > Undervoltage Inverse Time Curves section), or FlexCurves A
through D. The timing characteristic depends on this setting and the Delay setting that follows.
PHASE UV1 DELAY — This setting defines the operation time of the element.
When the PHASE UV1 CURVE setting is set to Definite Time, the PHASE UV1 DELAY setting defines definite time delay for
element operation.
When the PHASE UV1 CURVE setting is set to Inverse Time, the PHASE UV1 DELAY setting defines the inverse curve time delay
multiplier (D) that is used in the curve equation explained in the Voltage Elements > Undervoltage Inverse Time Curves
section.
When the PHASE UV1 CURVE setting is set to one of the FlexCurves, the PHASE UV1 DELAY setting defines the FlexCurve time
delay multiplier (D) that is used in the following curve equation:
T = D × FlexCurve time at (Vpkp/V) Eq. 5-31
For FlexCurves configuration instructions, see the System Setup > FlexCurves section.
PHASE UV1 RESET DELAY — When the Curve setting is set to Definite Time or Inverse Time, the element resets when applied
voltage exceeds the dropout voltage for the duration of the selected RESET DELAY setting.

5 When the Curve setting is set to one of the FlexCurves, the element reset is based on the equation and not the PHASE UV1
RESET DELAY setting.
As shown in the equation, because the element is supposed to operate in undervoltage condition, the multiple of pickup
value that defines the point on the FlexCurve characteristic is derived from the ratio of the set pickup value to the
measured voltage (and not the reverse). For example, if Pickup is set to 0.9 pu, when measured voltage is 0.82 pu, the ratio
is 0.9/0.82 = 1.1. Therefore, in FlexCurve, the corresponding operate time is at 1.1 x PKP (not at 0.82 x PKP). On the other
hand, when measured voltage is 1 pu, the ratio is 0.9/1 = 0.9. Therefore, in FlexCurve, the corresponding reset time is at
0.9 x PKP.
PHASE UV1 MINIMUM VOLTAGE — This setting selects the operating voltage below which the element is blocked (a setting of
"0" allows a dead source to be considered a fault condition).

5-320 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-164: Phase undervoltage1 logic


SETTING
PHASE U V1 PICKUP:

SETTING PHASE U V1 CURVE:


PHASE U V1
FUNCTION:
PHASE U V1 DELAY:
Enabled = 1
PHASE U V1 RESET DELAY:
SETTING FLEXLOGIC OPERANDS
AND
PHASE U V1 AND RUN VAG or VAB PICKUP PHASE U V1 A PKP
BLOCK: t PHASE U V1 A DPO
Off = 0 PHASE U V1 A OP
V TRST
FLEXLOGIC OPERANDS
SETTING
SETTING AND RUN VBG or VBC PICKUP PHASE U V1 B PKP
PHASE U V1
t PHASE U V1 B DPO
PHASE U V1 SOURCE: MINIMUM VOLTAGE:
PHASE U V1 B OP
VAG or VAB ≥ Minimum V TRST
Source VT = Delta Minimu FLEXLOGIC OPERANDS
VBG or VBC ≥
VAB m AND RUN VCG or VCA PICKUP PHASE U V1 C PKP
VCG or VCA ≥ Minimum
VBC t PHASE U V1 C DPO
VCA PHASE U V1 C OP
V TRST
Source VT = Wye
FLEXLOGIC OPERAND
SETTING OR PHASE U V1 PKP

PHASE U V1 MODE:

Ph ase to Grou nd Ph ase to Pha se FLEXLOGIC OPERAND


VAG VAB OR PHASE U V1 OP
VBG VBC
VCG VCA
FLEXLOGIC OPERAND
AND PHASE U V1 DPO

859824A1.vsdx

5.8.10.6 Phase overvoltage (ANSI 59P, IEC PTOV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  PHASE OVERVOLTAGE1(3)
 PHASE
 PHASE OV1 Range: Disabled, Enabled 5
 OVERVOLTAGE1 FUNCTION: Disabled

PHASE OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

PHASE OV1 MODE: Range: Phase to Ground, Phase to Phase


 Phase to Phase

PHASE OV1 Range: 0.004 to 3.000 pu in steps of 0.001


 PICKUP: 1.000 pu

PHASE OV1 CURVE: Range: Definite Time, Inverse Time, FlexCurves A


 Definite Time through D

PHASE OV1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

PHASE OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

PHASE OV1 BLOCK: Range: FlexLogic Operand


 Off

PHASE OV1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

PHASE OV1 Range: Disabled, Enabled


 EVENTS: Disabled

This element gives a time-delay operating characteristic versus the applied fundamental voltage.
PHASE OV1 SIGNAL SOURCE — Selects the signal source for the phase overvoltage protection element.
PHASE OV1 MODE — This setting defines the mode of operation, which can be Phase-to-Phase or Phase-to-Ground voltage.
Phase-to-ground or phase-to-phase voltages can be applied for wye VT connection, while phase-to-phase voltages can be
applied for delta VT connections only.
PHASE OV1 PICKUP — This setting specifies phase overvoltage protection element pickup level.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-321


GROUPED ELEMENTS CHAPTER 5: SETTINGS

PHASE OV1 CURVE — This setting defines the timing characteristic of the element, which can be: Definite Time, Inverse Time
(per the curves described in the Voltage Elements > Overvoltage Inverse Time Curves section), FlexCurves A through D. The
timing characteristic depends on this setting and the Pickup Delay setting that follows.
PHASE OV1 PICKUP DELAY — This setting defines the operation time of the element.
When the PHASE OV1 CURVE setting is set to Definite Time, the PHASE OV1 PICKUP DELAY setting defines definite time delay
for element operation.
When the PHASE OV1 CURVE setting is set to Inverse Time, the PHASE OV1 PICKUP DELAY setting defines the inverse curve
time delay multiplier (D) that is used in the Voltage Elements > Overvoltage Inverse Time Curves section.
When the PHASE OV1 CURVE setting is set to one of the FlexCurves, the PHASE OV1 PICKUP DELAY setting defines the
FlexCurve time delay multiplier (D) that is used in the following curve equation:
T= D × FlexCurve time at (V/Vpkp) Eq. 5-32
For FlexCurves configuration instructions, see the System Setup > FlexCurves section.
PHASE OV1 RESET DELAY — When the Curve setting is set to Definite Time or Inverse Time, the element resets when applied
voltage goes below the dropout voltage for the duration of the selected RESET DELAY setting.
When the Curve setting is set to one of the FlexCurves, the element reset is based on the equation and not the PHASE OV1
RESET DELAY setting.
As shown in the equation, the multiple of pickup value that defines the point on the FlexCurve characteristic is derived from
the ratio of the measured voltage to the set pickup. For example, if Pickup is set to 1.1 pu when the measured voltage is 1.3
pu, the ratio is 1.3/1.1 = 1.2. Therefore, in FlexCurve, the corresponding operate time is at 1.2 x PKP (not at 1.3 x PKP). On the
other hand, when measured voltage is 1 pu, the ratio is 1/1.1 = 0.9. Therefore, in FlexCurve, the corresponding reset time is
at 0.9 x PKP.
Figure 5-165: Phase overvoltage logic
5 SETTING

PHASE OV1 CURVE:

PHASE OV1 PICKUP


DELAY:
SET TING PHASE OV1 RESET
SET TING
PHAS E OV1 DELAY: FLEXLOGIC OPERANDS
PHAS E OV1
FUNCTION: PHAS E OV1 A PKP
PICKUP:
t
Enabled = 1 PHAS E OV1 A DPO
RUN V TRST PHAS E OV1 A OP
VAG or VAB ≥ PICKUP
PHAS E OV1 B PKP
SET TING t
AND
PHAS E OV1 B DPO
PHAS E OV1 V TRST
VBG or VBC ≥ PICKUP PHAS E OV1 B OP
BLOCK:
PHAS E OV1 C PKP
Off = 0 t
PHAS E OV1 C D PO
VCG or VCA ≥ PICKUP V TRST PHAS E OV1 C OP

SETTING

PHASE OV1 SOURCE:


FLEXLOGIC OPERAND
Source VT = Delta OR PHAS E OV1 OP
VAB
VBC
FLEXLOGIC OPERAND
VCA
Source VT = Wye AND PHAS E OV1 DPO

SETTING FLEXLOGIC OPERAND


OR PHAS E OV1 PKP
PHASE OV1 MODE:

Ph ase to Grou nd Ph ase to Pha se


859823A1.vsdx
VAG VAB
VBG VBC
VCG VCA

5.8.10.7 Neutral overvoltage (ANSI 59N, IEC PTOV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  NEUTRAL OV1(3)
 NEUTRAL OV1 NEUTRAL OV1 Range: Disabled, Enabled
  FUNCTION: Disabled

5-322 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

NEUTRAL OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEUTRAL OV1 PICKUP: Range: 0.004 to 3.000 pu in steps of 0.001


 0.300 pu

NEUTRAL OV1 CURVE: Range: Definite Time, FlexCurve A, FlexCurve B,


 Definite Time FlexCurve C

NEUTRAL OV1 PICKUP: Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

NEUTRAL OV1 RESET: Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

NEUTRAL OV1 BLOCK: Range: FlexLogic operand


 Off

NEUTRAL OV1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

NEUTRAL OV1 EVENTS: Range: Disabled, Enabled


 Disabled

The neutral overvoltage element is used to detect asymmetrical system voltage condition due to a ground fault or to the
loss of one or two phases of the source. The element responds to the system neutral voltage (3V_0), calculated from the
phase voltages. The nominal secondary voltage of the phase voltage channels entered under SETTINGS  SYSTEM SETUP
 AC INPUTS  VOLTAGE BANK  PHASE VT SECONDARY is the p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The NEUTRAL OV1 PICKUP DELAY setting applies only if the
NEUTRAL OV1 CURVE setting is “Definite Time.” The source assigned to this element must be configured for a phase VT.
5
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5-166: Neutral overvoltage1 logic

SETTING
NEUTRAL OV1
FUNCTION:
SETTING SETTING
Enabled=1
NEUTRAL OV1 PICKUP
NEUTRAL OV1 PICKUP: DELAY :
SETTING
AND RUN NEUTRAL OV1 RESET
DELAY :
NEUTRAL OV1 BLOCK:
NEUTRAL OV1 CURVE :
Off=0
FLEXLOGIC OPERANDS
3V_0< Pickup tPKP
t NEUTRAL OV1 OP
SETTING tRST
NEUTRAL OV1 DPO
NEUTRAL OV1 SIGNAL
SOURCE: NEUTRAL OV1 PKP
ZERO SEQ VOLT (V_0)
827848A3.CDR

5.8.10.8 Negative sequence overvoltage (ANSI 59Q, IEC PTOV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  NEG SEQ OV 1(3)
 NEG SEQ OV 1 NEG SEQ OV 1 Range: Disabled, Enabled
  FUNCTION: Disabled

NEG SEQ OV 1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

NEG SEQ OV 1 PICKUP: Range: 0.004 to 1.250 pu in steps of 0.001


 0.300 pu

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-323


GROUPED ELEMENTS CHAPTER 5: SETTINGS

NEG SEQ OV 1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.50 s

NEG SEQ OV 1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.50 s

NEG SEQ OV 1 BLOCK: Range: FlexLogic operand


 Off

NEG SEQ OV 1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

NEG SEQ OV 1 EVENTS: Range: Disabled, Enabled


 Disabled

There are three negative-sequence overvoltage elements available.


Use the negative-sequence overvoltage element to detect loss of one or two phases of the source, a reversed phase
sequence of voltage, or a non-symmetrical system voltage condition.
Figure 5-167: Negative-sequence overvoltage logic
SETTING
NEG SEQ OV1
FUNCTION:
SETTING
Enabled = 1
NEG SEQ OV1 PICKUP: SETTINGS
SETTING NEG SEQ OV1 PICKUP
AND RUN DELAY:
NEG SEQ OV1 BLOCK: FLEXLOGIC OPERANDS
NEG SEQ OV1 RESET
NEG SEQ OV1 PKP

5
DELAY:
Off = 0 NEG SEQ OV1 DPO
t PKP
t RST NEG SEQ OV1 OP
SETTING V_2 > PICKUP
NEG SEQ OV1 SIGNAL
SOURCE:
NEG SEQ VOLTAGE V_2

827839A4.CDR

5.8.10.9 Auxiliary undervoltage (ANSI 27X, IEC PTUV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  AUXILIARY UV1(3)
 AUXILIARY UV1 AUX UV1 Range: Disabled, Enabled
  FUNCTION: Disabled

AUX UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

AUX UV1 PICKUP: Range: 0.004 to 3.000 pu in steps of 0.001


 0.700 pu

AUX UV1 CURVE: Range: Definite Time, Inverse Time, FlexCurves A


 Definite Time through D

AUX UV1 DELAY: Range: 0.00 to 600.00 s in steps of 0.01


 1.00 s

AUX UV1 RESET DELAY: Range: 0.00 to 600.00 s in steps of 0.01


 1.00 s

AUX UV1 MINIMUM: Range: 0.000 to 3.000 pu in steps of 0.001


 VOLTAGE: 0.100 pu

AUX UV1 BLOCK: Range: FlexLogic operand


 Off

5-324 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

AUX UV1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

AUX UV1 EVENTS: Range: Disabled, Enabled


 Disabled

This element monitors undervoltage conditions of the auxiliary voltage.


AUX UV1 SIGNAL SOURCE — Selects the signal source for the auxiliary undervoltage protection element.
AUX UV1 PICKUP — This setting specifies auxiliary undervoltage protection element pickup level in per unit values. The
nominal secondary voltage of the auxiliary voltage channel entered under SETTINGS  SYSTEM SETUP  AC INPUTS 
VOLTAGE BANK X5  AUXILIARY VT X5 SECONDARY is the per-unit base used when setting the pickup level.
AUX UV1 CURVE — This setting defines the timing characteristic of the element, which can be: Definite Time, Inverse Time
(per the curves described in the Voltage Elements > Undervoltage Inverse Time Curves section), FlexCurves A through D.
The timing characteristic depends on this setting and the Delay setting that follows.
AUX UV1 DELAY — This setting defines the operation time of the element.
When the AUX UV1 CURVE setting is set to Definite Time, the AUX UV1 DELAY setting defines definite time delay for element
operation.
When the AUX UV1 CURVE setting is set to Inverse Time curve, the AUX UV1 DELAY setting defines the inverse curve time
delay multiplier (D) that is used in the curve equation explained in the Voltage Elements > Undervoltage Inverse Time
Curves section.
When the AUX UV1 CURVE setting is set to one of the FlexCurves, the AUX UV1 DELAY setting defines FlexCurve time delay
multiplier (D), that is used in the following curve equation:
T= D × FlexCurve time at (Vpkp / V) Eq. 5-33
For FlexCurves configuration instructions, see the System Setup > FlexCurves section.
AUX UV1 RESET DELAY — When the Curve setting is set to Definite Time or Inverse Time, the element resets when applied
5
voltage exceeds the dropout voltage for the duration of the selected RESET DELAY setting.
When the Curve setting is set to one of the FlexCurves, the element reset is based on the equation and not the AUX UV1
RESET DELAY setting.
As shown in the equation, because the element is supposed to operate in undervoltage condition, the multiple of pickup
value that defines the point on the FlexCurve characteristic is derived from the ratio of the set pickup value to the
measured voltage (and not the reverse). For example, if the Pickup is set to 0.9 pu, when the measured voltage is 0.82 pu,
the ratio is 0.9/0.82 = 1.1. Therefore, in the FlexCurve, the corresponding operate time is at 1.1 x PKP (not at 0.82 x PKP). On
the other hand, when measured voltage is 1 pu, the ratio is 0.9/1 = 0.9. Therefore, in the FlexCurve, the corresponding reset
time is at 0.9 x PKP.
AUX UV1 DELAY — Selects the minimum operating time of the auxiliary undervoltage element.
AUX UV1 RESET DELAY — The element resets if the applied voltage exceeds the dropout voltage for the duration of the
selected RESET DELAY setting.
AUX UV1 MINIMUM VOLTAGE — Selects the operating voltage below which the element is blocked.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-325


GROUPED ELEMENTS CHAPTER 5: SETTINGS

Figure 5-168: Auxiliary undervoltage logic

SETTING
AUX UV1 SETTING
FUNCTION:
AUX UV1 PICKUP:
Enabled=1

AUX UV1 CURVE:


SETTING

AUX UV1 BLOCK: AUX UV1 DELAY:

Off=0 AND
AUX UV1 RESET DELAY:
SETTING FLEXLOGIC OPERANDS
SETTING RUN Vx Pickup AUX UV1 PKP
AUX UV1 MINIMUM
AUX UV1 SIGNAL VOLTAGE: t AUX UV1 DPO
SOURCE:
AUX UV1 OP
AUX VOLT Vx Vx Minimum
V
TRST

859822A1.vsdx

5.8.10.10 Auxiliary overvoltage (ANSI 59X, IEC PTOV)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  AUXILIARY OV1(2)
 AUXILIARY OV1 AUX OV1 Range: Disabled, Enabled
  FUNCTION: Disabled

AUX OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

AUX OV1 PICKUP: Range: 0.004 to 3.000 pu in steps of 0.001


5  0.300 pu

AUX OV1 CURVE: Range: Definite Time, Inverse Time, FlexCurves A


 Definite Time through D

AUX OV1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

AUX OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 1.00 s

AUX OV1 BLOCK: Range: FlexLogic operand


 Off

AUX OV1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

AUX OV1 EVENTS: Range: Disabled, Enabled


 Disabled

This element is intended for monitoring overvoltage conditions of the auxiliary voltage. Monitoring the neutral voltage
supplied from an open-delta VT connection is a typical application for this element. Another typical application is
monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta VT connection.
AUX OV1 SIGNAL SOURCE — Selects the signal source for the auxiliary overvoltage protection element.
AUX OV1 PICKUP — This setting specifies auxiliary overvoltage protection element pickup level in per-unit values.
The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM SETUP  AC INPUTS  VOLTAGE
BANK X5  AUXILIARY VT SECONDARY is the per-unit base used when setting the pickup level.
AUX OV1 CURVE — This setting defines the timing characteristic of the element, which can be: Definite Time, Inverse Time
(per the curves described in the Voltage Elements > Overvoltage Inverse Time Curves section), FlexCurves A through D. The
timing characteristic depends on this setting and the Pickup Delay setting that follows.
AUX OV1 PICKUP DELAY — This setting defines the operation time of the element.
When the AUX OV1 CURVE setting is set to Definite Time, the AUX OV1 PICKUP DELAY setting defines definite time delay for
element operation.

5-326 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

When the AUX OV1 CURVE setting is set to Inverse Time, the AUX OV1 PICKUP DELAY setting defines inverse curve time delay
multiplier (D), that is used in the Voltage Elements > Overvoltage Inverse Time Curves section.
When the AUX OV1 CURVE setting is set to one of the FlexCurves, the AUX OV1 PICKUP DELAY setting defines the FlexCurve
time delay multiplier (D) that is used in the following equation:
T = D × FlexCurve time at (V/Vpkp) Eq. 5-34
For FlexCurves configuration instructions, see the System Setup > FlexCurves section.
AUX OV1 RESET DELAY — When the Curve setting is set to Definite Time or Inverse Time, the element resets when applied
voltage goes below the dropout voltage for the duration of the selected RESET DELAY setting.
When the Curve setting is set to one of the FlexCurves, the elements reset is based on the equation and not the AUX OV1
RESET DELAY setting.
As shown in the equation, the multiple of pickup value that defines the point on the FlexCurve characteristic is derived from
the ratio of the measured voltage to the set pickup. For example, if Pickup is set to 1.1 pu, when measured voltage is 1.3 pu,
the ratio is 1.3/1.1 = 1.2. Therefore, in the FlexCurve, the corresponding operate time is at 1.2 x PKP (not at 1.3 x PKP). On the
other hand, when measured voltage is 1 pu, the ratio is 1/1.1 = 0.9. Therefore, in the FlexCurve, the corresponding reset
time is at 0.9 x PKP.
Figure 5-169: Auxiliary overvoltage logic

SETTING
AUX OV1
FUNCTION:
Enabled=1 SETTING
SETTING
AUX OV1 CURVE:
SETTING AUX OV1 PICKUP:
AND

5
AUX OV1 PICKUP DELAY:
AUX OV1 BLOCK: RUN

Off=0 AUX OV1 RESET DELAY:

t
SETTING
Vx ≥ Pickup V FLEXLOGIC OPERANDS
AUX OV1 SIGNAL
SOURCE: TRST AUX OV1 OP
AUX OV1 DPO
AUXILIARY VOLT (Vx)
AUX OV1 PKP
859821A1.vsdx

5.8.11 Sensitive directional power (ANSI 32)


SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER  SENSITIVE DIRECTIONAL POWER 
DIRECTIONAL POWER 1(2)
 DIRECTIONAL DIR POWER 1 Range: Disabled, Enabled
 POWER 1  FUNCTION: Disabled

DIR POWER 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

DIR POWER 1 Range: 0 to 359° in steps of 1


 RCA: 0°

DIR POWER 1 Range: 0 to 0.95° in steps of 0.05


 CALIBRATION: 0.00°

DIR POWER 1 STG1 Range: –3.300 to 3.300 pu in steps of 0.001


 SMIN: 0.100 pu

DIR POWER 1 STG1 Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.50 s

DIR POWER 1 STG2 Range: –3.300 to 3.300 pu in steps of 0.001


 SMIN: 0.100 pu

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-327


GROUPED ELEMENTS CHAPTER 5: SETTINGS

DIR POWER 1 STG2 Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 20.00 s

DIR POWER 1 BLK: Range: FlexLogic operand


 Off

DIR POWER 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

DIR POWER 1 Range: Disabled, Enabled


 EVENTS: Disabled

The sensitive directional power element responds to three-phase directional power and is designed for reverse power and
low forward power applications for synchronous machines or interconnections involving co-generation. The relay
measures the three-phase power from either a full set of wye-connected VTs or a full set of delta-connected VTs. In the
latter case, the two-wattmeter method is used. See the UR-series Metering Conventions section in chapter 6 for details
regarding the active and reactive powers used by the sensitive directional power element.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional Power
Characteristic diagram that follows. The element responds to the following condition:
P cos θ + Q sin θ > SMIN Eq. 5-35
where
P and Q are active and reactive powers as measured per the UR metering convention
θ is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR POWER 1 CALIBRATION) angles
SMIN is the minimum operating power
The operating quantity is displayed in the ACTUAL VALUES  METERING  SENSITIVE DIRECTIONAL POWER 1(2) actual value.
The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively.
5 Figure 5-170: Directional power characteristic
A
^
SdY_
bU
4Y

?@5B1D5
B31
31<92B1D9?>
C=9>
@

B5CDB19>


($"' !1!34B

By making the characteristic angle adjustable and providing for both negative and positive values of the minimum
operating power, a variety of operating characteristics can be achieved as presented in the following figure. For example,
section (a) in the figure shows settings for reverse power, while section (b) shows settings for low forward power
applications.

5-328 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS GROUPED ELEMENTS

Figure 5-171: Directional power element sample applications

D 4 E 4

5(675$,1
23(5$7( 5(675$,1 23(5$7(
3 3

5&$ R 5&$ R


60,1! 60,1

F 4 G 4

23(5$7( 23(5$7(

3 3

5(675$,1 5(675$,1
5&$ R 5&$ R
60,1 60,1!

H 4
23(5$7(
I 4
5(675$,1

5(675$,1 23(5$7(

3 3

5&$ R 5&$ R


60,1! 60,1

($"' "1!34B

DIR POWER 1 RCA — Specifies the relay characteristic angle (RCA) for the sensitive directional power function. Application of
this setting is threefold:
• It allows the element to respond to active or reactive power in any direction (active overpower/underpower, and so on)
• Together with a precise calibration angle, it allows compensation for any CT and VT angular errors to permit more
sensitive settings
• It allows for required direction in situations when the voltage signal is taken from behind a delta-wye connected
power transformer and the phase angle compensation is required
For example, the active overpower characteristic is achieved by setting DIR POWER 1 RCA to “0°,” reactive overpower by
setting DIR POWER 1 RCA to “90°,” active underpower by setting DIR POWER 1 RCA to “180°,” and reactive underpower by
setting DIR POWER 1 RCA to “270°.”

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-329


CONTROL ELEMENTS CHAPTER 5: SETTINGS

DIR POWER 1 CALIBRATION — This setting allows the relay characteristic angle to change in steps of 0.05°. This is useful
when a small difference in VT and CT angular errors is to be compensated to permit more sensitive settings. This setting
virtually enables calibration of the directional power function in terms of the angular error of applied VTs and CTs. The
element responds to the sum of the DIR POWER 1 RCA and DIR POWER 1 CALIBRATION settings.
DIR POWER 1 STG1 SMIN — This setting specifies the minimum power as defined along the relay characteristic angle (RCA)
for the stage 1 of the element. The positive values imply a shift towards the operate region along the RCA line; the negative
values imply a shift towards the restrain region along the RCA line. See the Directional Power Sample Applications figure
for details. Together with the RCA, this setting enables a wide range of operating characteristics. This setting applies to
three-phase power and is entered in per-unit (pu) values. The base quantity is 3 x VT pu base x CT pu base for wye
connected VTs, and 3 x VT pu base x CT pu base for delta connected VTs.
For example, a setting of 2% for a 200 MW machine is 0.02 × 200 MW = 4 MW. If 13.8kV is line voltage and 10 kA is a
primary CT current, the source pu quantity is 239 MVA, and thus, SMIN needs to be set at 4 MW / 239 MVA = 0.0167 pu ≈
0.017 pu. If the reverse power application is considered, RCA = 180° and SMIN = 0.017 pu.
The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops below the
cutoff level.
DIR POWER 1 STG1 DELAY — This setting specifies a time delay for stage 1. For reverse power or low forward power
applications for a synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
Figure 5-172: Sensitive directional power logic
SETTING
DIR POWER 1
FUNCTION:
Enabled = 1
SETTINGS SETTING

5
SETTING DIR POWER 1 RCA: DIR POWER 1 STG1
DIR POWER 1 BLK: DELAY:
AND

DIR POWER 1 tPKP


CALIBRATION:
Off = 0
DIR POWER 1 STG1 100 ms
SMIN:
FLEXLOGIC OPERANDS
DIR POWER 1 STG2 FLEXLOGIC™ OPERANDS
SETTING SMIN: DIR POWER 1 STG1 OP
RUN DIR POWER 1 STG1 DPO
DIR POWER 1 SOURCE: DIR POWER 1 DPO
DIR POWER 1 STG1 PKP
OR

DIRECTIONAL POWER DIR POWER 1 PKP


Three-phase active power (P)
CHARACTERISTICS DIR POWER 1 STG2 PKP
OR

DIR POWER 1 OP
Three-phase reactive power (Q)
DIR POWER 1 STG2 DPO
DIR POWER 1 STG2 OP

SETTING
DIR POWER 1 STG2
DELAY:
tPKP

100 ms
842003A3.CDR

5.9 Control elements


5.9.1 Overview
Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of
this chapter for information.

5-330 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

5.9.2 Trip bus


SETTINGS  CONTROL ELEMENTS  TRIP BUS  TRIP BUS 1(6)
 TRIP BUS 1 TRIP BUS 1 Range: Enabled, Disabled
  FUNCTION: Disabled

TRIP BUS 1 BLOCK: Range: FlexLogic operand


 Off

TRIP BUS 1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

TRIP BUS 1 RESET Range: 0.00 to 600.00 s in steps of 0.01


 DELAY: 0.00 s

TRIP BUS 1 INPUT 1: Range: FlexLogic operand


 Off

TRIP BUS 1 INPUT 16: Range: FlexLogic operand
 Off

TRIP BUS 1 Range: Enabled, Disabled


 LATCHING: Disabled

TRIP BUS 1 RESET: Range: FlexLogic operand


 Off

TRIP BUS 1: Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

 TRIP BUS 1
EVENTS: Disabled
Range: Enabled, Disabled
5
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista software under Settings > Protection
Summary. Navigate to a specific protection or control protection element and check the bus box by hovering over the
blank check box and selecting an option that displays. Once the required element is selected for a specific bus, a list of
element operate-type operands are displayed and can be assigned to a trip bus. If more than one operate-type operand is
required, it can be assigned directly from the trip bus menu.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-331


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-173: Trip bus fields in the protection summary

The following settings are available.


TRIP BUS 1 BLOCK — The trip bus output is blocked when the operand assigned to this setting is asserted.
TRIP BUS 1 PICKUP DELAY — This setting specifies a time delay to produce an output depending on how output is used.
TRIP BUS 1 RESET DELAY — This setting specifies a time delay to reset an output command. Set the time delay long enough
5 to allow the breaker or contactor to perform a required action.
TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16 — These settings select a FlexLogic operand to be assigned as an input to the trip
bus.
TRIP BUS 1 LATCHING — This setting enables or disables latching of the trip bus output. This is typically used when lockout is
required or user acknowledgement of the relay response is required.
TRIP BUS 1 RESET — The trip bus output is reset when the operand assigned to this setting is asserted. Note that the RESET
OP operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via
communications resets the trip bus output.

5-332 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

Figure 5-174: Trip bus logic


SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
*** OR set-dominant
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R

SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off

SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR

FLEXLOGIC OPERAND
RESET OP 842023A1.CDR

5.9.3 Setting groups 5


SETTINGS  CONTROL ELEMENTS  SETTING GROUPS
 SETTING GROUPS SETTING GROUPS Range: Disabled, Enabled
  FUNCTION: Disabled

Control Mode: Range: Local, IEC61850 Client


 Local

SETTING GROUPS BLK: Range: FlexLogic operand


 Off

GROUP 2 ACTIVATE ON: Range: FlexLogic operand


 Off

GROUP 6 ACTIVATE ON: Range: FlexLogic operand
 Off

GROUP 1 NAME: Range: up to 16 alphanumeric characters




GROUP 6 NAME: Range: up to 16 alphanumeric characters

SETTING GROUP Range: Disabled, Enabled
 EVENTS: Disabled

The setting groups menu controls the activation and deactivation of up to six groups of settings in the GROUPED ELEMENTS
settings menu. The active setting group can be indicated on the front display of the F60 by configuring User-
Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.
On a setting group change, protection elements are blocked temporarily to allow the relay to re-initialize with the new
settings. The duration of the block depends on relay configuration and can last up to four cycles. The actual block duration
on the group switching can be verified by the PROTSUPV operand.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-333


CONTROL ELEMENTS CHAPTER 5: SETTINGS

SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. When Disabled, the default setting group is forced active. When changed from Disabled to Enabled, it resets the
active setting group to 1 independent of the Control Mode setting.
Control Mode — This setting displays when IEC 61850 is used by the F60. It selects the active setting group selection control
mode. When set to "Local," active setting group selection is based on the FlexLogic operand states selected by GROUP
ACTIVATE ON settings and the SelectActiveSG request from an IEC 61850 client generates a negative response. When set to
"IEC61850 Client," the SelectActiveSG request from an IEC 61850 client selects the active setting group and the FlexLogic
operand states of the GROUP ACTIVATE ON settings are ignored/not used.
The logic diagram shows the active setting group selection behavior based on the Control Mode setting.
When the Control Mode is "Local," the priority scheme makes active the highest numbered group selected by the GROUP
ACTIVATE ON settings. The most recent active group selection is preserved while the F60 is powered down or reset.
When the Control Mode is "IEC61850 Client," the SelectActiveSG selection has an initial value that can be set on a CID file
download by the IEC 61850 setting Initial Setting Group. See the Settings > Product Setup > Communications > IEC 61850
protocol > Setting Groups section earlier for details. The most recent SelectActiveSG selection is preserved while the F60 is
powered down or reset. If it becomes necessary to cancel the SelectActiveSG selection without using a SelectActiveSG
service request, change the SETTING GROUPS FUNCTION setting to Disabled. This resets the SelectActiveSG selection to 1.
When the Control Mode is changed, the current active setting group selection is preserved.
Figure 5-175: Logic diagram for Control Mode setting
SETT ING
SETTING GROUPS FUNCTION
= Enabled

5
SETT ING
SETTING GROUPS BLK
= Off AND RUN

Priority Scheme
SETT ING
Group # Activate On
= FlexLogic operand

SETT ING Local Setting Group


S

Control M ode A
Active setting group
= Local / IEC61850 Client
se lection

IEC 61850 Client

AND RUN

IEC 61850 SG
se rvice processing
<MasterLD>/LLN0.ActSG

From IEC 61850 client 859788A1.vsd

Active setting group selection can be made either by IEC 61850 MMS SelectActiveSG service or Local by the
FlexLogic operand states selected by GROUP # ACTIVATE ON settings. Simultaneous setting group control is not
permissible.
SETTING GROUPS BLK — Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON — Selects a FlexLogic operand which, when set, makes the particular setting
group active for use by any grouped element. A priority scheme ensures that only one group is active at a given time — the
highest-numbered group that is activated by its ACTIVATE ON parameter takes priority over the lower-numbered groups.
There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes active if no
other group is active.

5-334 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

The settings are read-only with default values when the Control Mode setting is set to "IEC61850 Client."
A setting group selection can also be made by the IEC 61850 MMS service SelectActiveSG to the control block @Master/
LLN0.SGCB. An active group selection can be done either by SelectActiveSG service from a IEC 61850 client or by GROUP
ACTIVATE ON settings, but mixed operation is not allowed.
An initial setting group value is initialized to the GROUP ACTIVATE ON setting value on F60 reboot immediately following the
receipt of a valid CID file.
SETTING GROUP 1 NAME to SETTING GROUP 6 NAME — Allows the user to assign a name to each of the six settings groups.
Once programmed, this name appears on the second line of the GROUPED ELEMENTS  SETTING GROUP 1(6) menu display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic equation (see the following figure) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of
a particular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the
particular settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular
settings group.
Figure 5-176: Example of FlexLogic control of a setting group

 9,57,321 9,
25 
 &217,321 +$

 25 
$1'  9,5723 92
 3+$6(72&3.3

 127

5
 3+$6(72&3.3

 127

 $1' 

 9,5723 92

 (1'
$&'5

5.9.4 Selector switch


SETTINGS  CONTROL ELEMENTS  SELECTOR SWITCH  SELECTOR SWITCH 1(2)
 SELECTOR SWITCH 1 SELECTOR 1 FUNCTION: Range: Disabled, Enabled
  Disabled

SELECTOR 1 FULL Range: 1 to 7 in steps of 1


 RANGE: 7

SELECTOR 1 TIME-OUT: Range: 3.0 to 60.0 s in steps of 0.1


 5.0 s

SELECTOR 1 STEP-UP: Range: FlexLogic operand


 Off

SELECTOR 1 STEP-UP Range: Time-out, Acknowledge


 MODE: Time-out

SELECTOR 1 ACK: Range: FlexLogic operand


 Off

SELECTOR 1 3BIT A0: Range: FlexLogic operand


 Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-335


CONTROL ELEMENTS CHAPTER 5: SETTINGS

SELECTOR 1 3BIT A1: Range: FlexLogic operand


 Off

SELECTOR 1 3BIT A2: Range: FlexLogic operand


 Off

SELECTOR 1 3BIT Range: Time-out, Acknowledge


 MODE: Time-out

SELECTOR 1 3BIT ACK: Range: FlexLogic operand


 Off

SELECTOR 1 POWER-UP Range: Restore, Synchronize, Sync/Restore


 MODE: Restore

SELECTOR 1 TARGETS: Range: Self-reset, Latched, Disabled


 Self-reset

SELECTOR 1 EVENTS: Range: Disabled, Enabled


 Disabled

The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows
setting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after
time-out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile
memory. Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word
5 (user setting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input
being out of range.
A selector switch runs every two power cycles.
SELECTOR 1 FULL RANGE — This setting defines the upper position of the selector. When stepping up through available
positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-bit control
word for programming the selector to a desired position, the change would take place only if the control word is within the
range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established by setting the
SELECTOR ALARM FlexLogic operand for three seconds.
SELECTOR 1 TIME-OUT — This setting defines the time-out period for the selector. This value is used by the relay in the
following two ways. When the SELECTOR STEP-UP MODE is “Time-out,” the setting specifies the required period of inactivity
of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-UP MODE is
“Acknowledge,” the setting specifies the period of time for the acknowledging input to appear. The timer is re-started by
any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT timer expires;
otherwise, the change does not take place and an alarm is set.
SELECTOR 1 STEP-UP — This setting specifies a control input for the selector switch. The switch is shifted to a new position at
each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1 FULL RANGE) to
the first (position 1). Consecutive pulses of this control operand must not occur faster than every 50 ms. After each rising
edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1: POS Z CHNG INITIATED target
message is displayed, where Z the pre-selected position. The message is displayed for the time specified by the FLASH
MESSAGE TIME setting. The pre-selected position is applied after the selector times out (“Time-out” mode), or when the
acknowledging signal appears before the element times out (“Acknowledge” mode). When the new position is applied, the
relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is
configured as the stepping up control input.
SELECTOR 1 STEP-UP MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge,” the selector
changes its position only after the intent is confirmed through a separate acknowledging signal. If the acknowledging
signal does not appear within a pre-defined period of time, the selector does not accept the change and an alarm is
established by setting the SELECTOR STP ALARM output FlexLogic operand for three seconds.

5-336 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

SELECTOR 1 ACK — This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the last
activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
SELECTOR 1 3BIT A0, A1, and A2 — These settings specify a three-bit control input of the selector. The three-bit control word
pre-selects the position using the following encoding convention:
A2 A1 A0 Position
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6
1 1 1 7

The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the three-
bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out,” the pre-selected position is applied in
SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is “Acknowledge,”
the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2) lock-out
mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit control
sequence is initiated, the stepping up input is inactive.
SELECTOR 1 3BIT MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector changes 5
its position after a pre-defined period of inactivity at the control input. The change is automatic and does not require
explicit confirmation to change the selector position. When set to “Acknowledge,” the selector changes its position only
after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a pre-defined
period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT ALARM
FlexLogic operand for three seconds.
SELECTOR 1 3BIT ACK — This setting specifies an acknowledging input for the three-bit control input. The pre-selected
position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the
“Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR TIME-
OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and three-bit
control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accordingly).
SELECTOR 1 POWER-UP MODE — This setting specifies the element behavior on power up of the relay.
When set to “Restore,” the last position of the selector (stored in the non-volatile memory) is restored after powering up the
relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and an alarm
is set (SELECTOR 1 PWR ALARM).
When set to “Synchronize,” the selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range), then the selector
switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR ALARM).
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch attempts to restore the position stored in the relay memory. The “Synch/
Restore” mode is useful for applications where the selector switch is employed to change the setting group in redundant
(two relay) protection schemes.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-337


CONTROL ELEMENTS CHAPTER 5: SETTINGS

SELECTOR 1 EVENTS — If enabled, the following events are logged:

Event name Description


SELECTOR 1 POS Z Selector 1 changed its position to Z
SELECTOR 1 STP ALARM The selector position pre-selected via the stepping up control input has not been confirmed before the
time out
SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time
out

The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.

5-338 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

Figure 5-177: Time-out mode

TIME OUT MODE OF OPERATION

pre-existing changed to 4 with changed to 1 with changed to 2 with a changed to 7 with


position 2 a pushbutton a 3-bit input pushbutton a 3-bit input

STEP-UP

T T

3BIT A0

3BIT A1

3BIT A2
T T

POS 1

POS 2

POS 3
5
POS 4

POS 5

POS 6

POS 7

BIT 0

BIT 1

BIT 2

STP ALARM

BIT ALARM

ALARM
842737A1.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-339


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-178: Acknowledge mode

ACKNOWLEDGE MODE OF OPERATION

pre-existing changed to 4 with changed to 1 with changed to 2 with


position 2 a pushbutton a 3-bit input a pushbutton

STEP-UP

ACK

3BIT A0

3BIT A1

3BIT A2

3BIT ACK

POS 1

POS 2

5 POS 3

POS 4

POS 5

POS 6

POS 7

BIT 0

BIT 1

BIT 2

STP ALARM

BIT ALARM

ALARM
842736A1.CDR

Application example
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group is to be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity
of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input.

5-340 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

Make the following changes to setting group control in the SETTINGS  CONTROL ELEMENTS  SETTING GROUPS menu:
FUNCTION: “Enabled”
Block: “Off”
GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2"
GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"
GROUP 4 ACTIVATE ON: “SELECTOR 1 POS 4"
GROUP 5 ACTIVATE ON: “Off”
GROUP 6 ACTIVATE ON: “Off”
Make the following changes to selector switch element in the SETTINGS  CONTROL ELEMENTS  SELECTOR SWITCH 
SELECTOR SWITCH 1 menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
SELECTOR 1 FUNCTION: “Enabled”
SELECTOR 1 FULL-RANGE: “4”
SELECTOR 1 STEP-UP MODE: “Time-out”
SELECTOR 1 TIME-OUT: “5.0 s”
SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON”
SELECTOR 1 ACK: “Off”
SELECTOR 1 3BIT A0: “CONT IP 1 ON”
SELECTOR 1 3BIT A1: “CONT IP 2 ON”
SELECTOR 1 3BIT A2: “CONT IP 3 ON”
SELECTOR 1 3BIT MODE: “Time-out”
SELECTOR 1 3BIT ACK: “Off”
SELECTOR 1 POWER-UP MODE: “Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT OUTPUTS menu:
OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
5
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS  PRODUCT
SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”
The figure shows the logic for the selector switch.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-341


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-179: Selector switch logic

6(77,1*6
6(/(&725)8//5$1*(

6(/(&72567(38302'(

6(/(&725%,702'(

6(/(&7257,0(287 $&78$/9$/8(
6(77,1*6
6(/(&725326,7,21
6(/(&725)81&7,21 6(/(&72532:(58302'(
(QDEOHG  581
6(/(&72567(383 )/(;/2*,&Œ23(5$1'6
2II  VWHSXS 6(/(&725326

6(/(&725$&.  6(/(&725326

2II  DFNQRZOHGJH 6(/(&725326
6(/(&725%,7$ 
6(/(&725326
WKUHHELWFRQWUROLQSXW

2II  6(/(&725326
21
6(/(&725%,7$  
6(/(&725326
2II  
6(/(&725326
6(/(&725%,7$
2II  )/(;/2*,&Œ23(5$1'6
6(/(&725%,7$&.
6(/(&725673$/$50
2II  ELWDFNQRZOHGJH
6(/(&725%,7$/$50
ELWSRVLWLRQRXW

25
6(/(&725$/$50
6(/(&7253:5$/$50
6(/(&725%,7
6(/(&725%,7

5 6(/(&725%,7
$&'5

5.9.5 Underfrequency (ANSI 81U)


SETTINGS  CONTROL ELEMENTS  UNDERFREQUENCY  UNDERFREQUENCY 1(6)
 UNDERFREQUENCY 1 UNDFREQ 1 FUNCTION: Range: Disabled, Enabled
  Disabled

UNDERFREQ 1 BLOCK: Range: FlexLogic operand


 Off

UNDERFREQ 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

UNDERFREQ 1 MIN Range: 0.10 to 1.25 pu in steps of 0.01


 VOLT/AMP: 0.10 pu

UNDERFREQ 1 PICKUP: Range: 20.00 to 65.00 Hz in steps of 0.01


 59.50 Hz

UNDERFREQ 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 2.000 s

UNDERFREQ 1 RESET Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 2.000 s

UNDERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

UNDERFREQ 1 EVENTS: Range: Disabled, Enabled


 Disabled

The steady-state frequency of a power system is a certain indicator of the existing balance between the generated power
and the load. Whenever this balance is disrupted through the loss of an important generating unit or the isolation of part
of the system from the rest of the system, the effect is a reduction in frequency. If the control systems of the system

5-342 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

generators do not respond fast enough, the system can collapse. A reliable method to quickly restore the balance between
load and generation is to automatically disconnect selected loads, based on the actual system frequency. This technique,
called “load-shedding,” maintains system integrity and minimize widespread outages. After the frequency returns to
normal, the load can be restored automatically or manually.
UNDERFREQ 1 SOURCE — This setting is used to select the source for the signal to be measured. The element first checks for
a live phase voltage available from the selected source. If voltage is not available, the element attempts to use a phase
current. If neither voltage nor current is available, the element does not operate, as it does not measure a parameter
below the minimum voltage/current setting.
UNDERFREQ 1 MIN VOLT/AMP — Selects the minimum per unit voltage or current level required to allow the underfrequency
element to operate. This threshold is used to prevent an incorrect operation because there is no signal to measure.
UNDERFREQ 1 PICKUP — Selects the level at which the underfrequency element is to pickup. For example, if the system
frequency is 60 Hz and the load shedding is required at 59.5 Hz, the setting is 59.50 Hz.
Figure 5-180: Underfrequency logic
SETTING

UNDERFREQ 1 FUNCTION:

Enabled=1

SETTING SETTING SETTING


UNDERFREQ 1 UNDERFREQ 1
UNDERFREQ 1 BLOCK: PICKUP : PICKUP DELAY :
AND RUN FLEXLOGIC OPERANDS
Off = 0 UNDERFREQ 1
UNDERFREQ 1 PKP
RESET DELAY :
SETTING UNDERFREQ 1 DPO
SETTING tPKP
UNDERFREQ 1 0 < f < PICKUP tRST UNDERFREQ 1 OP
UNDERFREQ 1 SOURCE: ACTUAL VALUES MIN VOLT / AMP:
Level < Min
VOLT / AMP 827079A9.CDR
Frequency

5
5.9.6 Overfrequency (ANSI 81O)
SETTINGS  CONTROL ELEMENTS  OVERFREQUENCY  OVERFREQUENCY 1(4)
 OVERFREQUENCY 1 OVERFREQ 1 FUNCTION: Range: Disabled, Enabled
  Disabled

OVERFREQ 1 BLOCK: Range: FlexLogic operand


 Off

OVERFREQ 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

OVERFREQ 1 PICKUP: Range: 20.00 to 65.00 Hz in steps of 0.01


 60.50 Hz

OVERFREQ 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.500 s

OVERFREQ 1 RESET Range: 0.000 to 65.535 s in steps of 0.001


 DELAY : 0.500 s

OVERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

OVERFREQ 1 EVENTS: Range: Disabled, Enabled


 Disabled

There are four overfrequency elements, numbered 1 through 4.


A frequency calculation for a given source is made on the input of a voltage or current channel, depending on which is
available. The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage
channel, current channel A, and ground current channel. The first available signal is used for frequency calculation.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-343


CONTROL ELEMENTS CHAPTER 5: SETTINGS

The steady-state frequency of a power system is an indicator of the existing balance between the generated power and
the load. Whenever this balance is disrupted through the disconnection of significant load or the isolation of a part of the
system that has a surplus of generation, the effect is an increase in frequency. If the control systems of the generators do
not respond fast enough, to quickly ramp the turbine speed back to normal, the overspeed can lead to the turbine trip. The
overfrequency element can be used to control the turbine frequency ramp down at a generating location. This element
can also be used for feeder reclosing as part of the "after load shedding restoration."
The OVERFREQ 1 SOURCE setting selects the source for the signal to be measured.
The OVERFREQ 1 PICKUP setting selects the level at which the overfrequency element is to pickup.
Figure 5-181: Overfrequency logic
SETTING

OVERFREQ 1 FUNCTION:
SETTING
Enabled = 1
OVERFREQ 1 PICKUP : SETTING
SETTING OVERFREQ 1 PICKUP
AND RUN DELAY :
OVERFREQ 1 BLOCK: FLEXLOGIC OPERANDS
OVERFREQ 1 RESET
OVERFREQ 1 PKP
DELAY :
Off = 0 OVERFREQ 1 DPO
tPKP
tRST OVERFREQ 1 OP
SETTING f ≡ PICKUP
OVERFREQ 1 SOURCE:

Frequency 827832A6.CDR

5 5.9.7 Frequency rate of change (ANSI 81R)


SETTINGS  CONTROL ELEMENTS  FREQUENCY RATE OF CHANGE  FREQUENCY RATE OF CHANGE 1(4)
 FREQUENCY RATE FREQ RATE 1 Range: Disabled, Enabled
 OF CHANGE 1  FUNCTION: Disabled

FREQ RATE 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

FREQ RATE 1 TREND: Range: Increasing, Decreasing, Bi-directional


 Increasing

FREQ RATE 1 PICKUP: Range: 0.10 to 15.00 Hz/sec in steps of 0.01


 0.50 Hz/sec

FREQ RATE 1 OV SUPV Range: 0.100 to 3.000 pu in steps of 0.001


 PICKUP: 0.700 pu

FREQ RATE 1 OC SUPV Range: 0.020 to 30.000 pu in steps of 0.001


 PICKUP: 0.200 pu

FREQ RATE 1 MIN Range: 20.00 to 80.00 Hz in steps of 0.01


 FREQUENCY: 45.00 Hz

FREQ RATE 1 MAX Range: 20.00 to 80.00 Hz in steps of 0.01


 FREQUENCY: 65.00 Hz

FREQ RATE 1 PICKUP Range: 0 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

FREQ RATE 1 RESET Range: 0 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

FREQ RATE 1 BLOCK: Range: FlexLogic operand


 Off

5-344 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

FREQ RATE 1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

FREQ RATE 1 EVENTS: Range: Disabled, Enabled


 Disabled

The element responds to rate of change of frequency with voltage, current and frequency supervision.
FREQ RATE 1 TREND — This setting configures the element to respond to increasing or decreasing frequency, or to frequency
change in either direction.
FREQ RATE 1 PICKUP — This setting specifies an intended df/dt pickup threshold. For applications monitoring a decreasing
trend, set FREQ RATE 1 TREND to “Decreasing” and specify the pickup threshold accordingly. The operating condition is:
-df/dt > Pickup.
For applications monitoring an increasing trend, set FREQ RATE 1 TREND to “Increasing” and specify the pickup threshold
accordingly. The operating condition is: df/dt > Pickup.
For applications monitoring rate of change of frequency in any direction set FREQ RATE 1 TREND to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is: abs (df/dt) > Pickup.
FREQ RATE 1 OV SUPV PICKUP — This setting defines the minimum voltage level required for operation of the element. The
supervising function responds to the positive-sequence voltage. Use overvoltage supervision to prevent operation under
specific system conditions, such as faults.
FREQ RATE 1 OC SUPV PICKUP — This setting defines minimum current level required for operation of the element. The
supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup
threshold to 0.020 if no overcurrent supervision is required.
FREQ RATE 1 MIN FREQUENCY — This setting defines the minimum frequency level required for operation of the element. The
setting can be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, set this setting to the required frequency level. 5
FREQ RATE 1 MAX FREQUENCY — This setting defines the maximum frequency level required for operation of the element.
The setting can be used to effectively block the feature based on frequency. For example, if the intent is to monitor a
decreasing trend but only if the frequency is already below a certain level (such as for load shedding), set this setting to the
required frequency level.

If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.

Figure 5-182: Frequency rate of change logic


6(77,1*6
6(77,1*
)5(45$7()81&7,21
)5(45$7(296839
(QDEOHG  3,&.83
$1'

)5(45$7(%/2&. 581
2II
_9B_!3,&.83
6(77,1*6
6(77,1* )5(45$7(3,&.83
6(77,1*6
'(/$<
6(77,1* )5(45$7(2&6839 )5(45$7(75(1'
3,&.83 )5(45$7(5(6(7
)5(45$7(6285&( '(/$<
)5(45$7(3,&.83
581
W3.3 )/(;/2*,&23(5$1'6
$1'

3RVVHTYROWDJH 9B 581


3RVVHTFXUUHQW ,B _,B_!3,&.83 )5(45$7(23
)UHTXHQF\ ) GIGW!3,&.83 W567
)5(45$7('32
6(77,1*6
)5(45$7(3.3
)5(45$7(0,1
)5(48(1&<

)5(45$7(0$;
)5(48(1&<
581

)!0,1 )0$;

581

&DOFXODWHGIGW
(#" "#1"34B

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-345


CONTROL ELEMENTS CHAPTER 5: SETTINGS

5.9.8 Synchrocheck (ANSI 25)


SETTINGS  CONTROL ELEMENTS  SYNCHROCHECK  SYNCHROCHECK 1(4)
 SYNCHROCHECK 1 SYNCHK1 FUNCTION: Range: Disabled, Enabled
  Disabled

SYNCHK1 BLOCK: Range: FlexLogic operand


 Off

SYNCHK1 V1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

SYNCHK1 V2 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 2

SYNCHK1 PHASE Range: Auto, Vag, Vbg, Vcg, Vab, Vbc, Vca
 SELECT: Auto

SYNCHK1 MAX VOLT Range: 0 to 400000 V in steps of 1


 DIFF: 10000 V

SYNCHK1 MAX ANGLE Range: 0 to 100° in steps of 1


 DIFF: 30

SYNCHK1 MAX FREQ Range: 0.005 to 2.000 Hz in steps of 0.001


 DIFF: 0.100 Hz

SYNCHK1 MAX FREQ Range: 0.000 to 0.100 Hz in steps of 0.001


 HYSTERESIS: 0.060 Hz

SYNCHK1 SYNC CLOSE: Range: FlexLogic operand



5 Off

SYNCHK1 S-CLS MAX Range: 0.100 to 10.000 Hz in steps of 0.001


 dF: 0.500 Hz

SYNCHK1 S-CLS MIN Range: 0.005 to 1.000 Hz in steps of 0.001


 dF: 0.100 Hz

SYNCHK1 S-CLS ANG: Range: 0 to 100° in steps of 1


 1

SYNCHK1 S-CLS BRK Range: 0.010 to 0.500 s in steps of 0.001


 TIME: 0.035 s

SYNCHK1 V2 MAG CORR Range: 0.10 to 10.00 in steps of 0.01


 FACTOR: 1.00

SYNCHK1 V2 ANGLE Range: -180 to +180 degrees in steps of 1


 SHIFT: 0

SYNCHK1 DEAD SOURCE Range: None, LV1 and DV2, DV1 and LV2, DV1 or DV2,
 SELECT: LV1 and DV2 DV1 Xor DV2, DV1 and DV2

SYNCHK1 DEAD V1 Range: 0.04 to 1.25 pu in steps of 0.01


 MAX VOLT: 0.30 pu

SYNCHK1 DEAD V2 Range: 0.04 to 1.25 pu in steps of 0.01


 MAX VOLT: 0.30 pu

SYNCHK1 LIVE V1 Range: 0.04 to 1.25 pu in steps of 0.01


 MIN VOLT: 0.70 pu

SYNCHK1 LIVE V2 Range: 0.04 to 1.25 pu in steps of 0.01


 MIN VOLT: 0.70 pu

SYNCHK1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

SYNCHK1 EVENTS: Range: Disabled, Enabled


 Disabled

5-346 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

The synchronism check function supervises the paralleling of two parts of a system that are to be joined by the closure of
a circuit breaker. The synchrocheck elements are typically used at locations where the two parts of the system are
interconnected through at least one other point in the system.
Synchrocheck verifies that the voltages (V1 and V2) on the two sides of the supervised circuit breaker are within set limits
of magnitude, angle, and frequency differences. The time that the two voltages remain within the admissible angle
difference is determined by the setting of the phase angle difference ΔΦ and the frequency difference ΔF (slip frequency). It
can be defined as the time it takes the voltage phasor V1 or V2 to traverse an angle equal to 2 × ΔΦ at a frequency equal
to the frequency difference ΔF. This time is calculated by:

1
T = -----------------------------
360q Eq. 5-36
---------------- u 'F
2 u ')

where
ΔΦ is phase angle difference in degrees
ΔF is frequency difference in Hz
If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using
undervoltage control to bypass the synchrocheck measurements (dead source function).
SYNCHK1 V1 SOURCE — This setting selects the source for voltage V1 (see the Notes section that follows).
SYNCHK1 V2 SOURCE — Selects the source for voltage V2. V1 and V2 can have different sources or they can be the same (see
the table in the next section).
If V1 and V2 are assigned to “SRC 1", for example, then in Settings > System Setup > Power System, the below settings should
have the following values:
• FREQUENCY AND PHASE REFERENCE: “SRC 1"
• ALTERNATE FREQ AND PHS REFERENCE: “SRC 1" 5
• SIGNAL TO TRACK: “Auto” or “3PH_VT”
• ALT SIGNAL TO TRACK: “1PH_VT”
SYNCHK1 PHASE SELECT — This setting selects the source voltage (see the table in the next section) used by the
synchrocheck element and is applicable when
• Both V1 and V2 assigned signal sources differ, and
• Both V1 and V2 assigned signal sources both have three-phase VT banks configured
SYNCHK1 MAX VOLT DIFF — Selects the maximum primary voltage difference in volts between the two sources. A primary
voltage magnitude difference between the two input voltages below this value is within the permissible limit for
synchronism.
SYNCHK1 MAX ANGLE DIFF — Selects the maximum angular difference in degrees between the two sources. An angular
difference between the two input voltage phasors below this value is within the permissible limit for synchronism.
SYNCHK1 MAX FREQ HYSTERESIS — This setting specifies the required hysteresis for frequency difference condition.
• SYNCHK1 MAX FREQ DIFF — The condition becomes satisfied when the frequency difference becomes lower than
SYNCHK1 MAX FREQ DIFF. Once the Synchrocheck element has operated, the frequency difference must increase above
the SYNCHK1 MAX FREQ DIFF + SYNCHK1 MAX FREQ HYSTERESIS sum to drop out (assuming the other two conditions,
voltage and angle, remain satisfied).
• SYNCHK1 S-CLS MAX dF — The condition becomes satisfied when the frequency difference becomes lower than
SYNCHK1 S-CLS MAX dF. Once the Synchrocheck element has operated, the frequency difference must increase above
the SYNCHK1 S-CLS MAX dF + SYNCHK1 MAX FREQ HYSTERESIS sum to drop out.
• SYNCHK1 S-CLS MIN dF — The condition becomes satisfied when the frequency difference becomes higher than
SYNCHK1 S-CLS MIN dF. Once the Synchrocheck element has operated, the frequency difference must decrease below
the SYNCHK1 S-CLS MIN dF - SYNCHK1 MAX FREQ HYSTERESIS sum to drop out.
SYNCHK1 SYNC CLOSE — Enables the dynamic mode of synchrocheck. When it is enabled, the location of where the present
V2 vector will be arriving to synchronize (shown as V2' in the figures here) with breaker close time being taken into account
will be predicted based on the measured slip frequency so that breaker close command can be issued in advance to
ensure the synchronism at the time when the breaker is actually closed.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-347


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-183: Synchrocheck plot for slip > 0 (slip = F2-F1)

V1 V2'

Limit Angle Limit Angle

V2

ϕ2'
ϕ2
ϕ1
859746A1.vsd

Figure 5-184: Synchrocheck plot for slip < 0 (slip = F2-F1)

V2' V1

Limit Angle Limit Angle

V2

ϕ2'
ϕ2
5 ϕ1
859747A1.vsd

SYNCHK1 S-CLS MAX dF — Specifies the maximum slip frequency allowed in Hz in the dynamic mode. The dynamic mode is
disarmed when the slip frequency exceeds this setting. Setting more than 2 Hz is not recommended as it is expected to
have significant errors in phasor estimation, so apply them with caution.
SYNCHK1 S-CLS MIN dF — Specifies the minimum slip frequency allowed in Hz in the dynamic mode. The dynamic mode is
disarmed when the slip frequency drops below this setting.
SYNCHK1 S-CLS ANG — This setting specifies the maximum angular difference in degrees between the two voltage phasors
V1 and projected V2, that is, V2'.
SYNCHK1 S-CLS BRK TIME — Specifies the breaker closing time in seconds.
SYNCHK1 V2 MAG CORR FACTOR — Specifies the magnitude correction factor of source V2. This setting is used for V2
magnitude compensation so that V2 magnitude can be directly compared with V1 magnitude. For example, when V1 and
V2 are taken from 2 different windings of the transformer and at different voltage levels, the magnitude compensation
must be performed before starting magnitude comparison in synchrocheck element.
SYNCHK1 V2 ANGLE SHIFT — Specifies the angle of source V2 that needs to be shifted so that V2 angle can be directly
compared with V1 angle. For example, when V1 and V2 are taken from two different windings of the transformer and with
different angle shift due to winding connections, the angle shift compensation must be performed before starting angle
comparison in synchrocheck element.
SYNCHK1 DEAD SOURCE SELECT — Selects the combination of dead and live sources that bypass the synchronism check
function and permit the breaker to be closed when one or both of the two voltages (V1 or/and V2) are below the maximum
voltage threshold. A dead or live source is declared by monitoring the voltage level. Six options are available:
None — Dead Source function is disabled
LV1 and DV2 — Live V1 and Dead V2
DV1 and LV2 — Dead V1 and Live V2
DV1 or DV2 — Dead V1 or Dead V2
DV1 Xor DV2 — Dead V1 exclusive-or Dead V2 (one source is Dead and the other is Live)
DV1 and DV2 — Dead V1 and Dead V2

5-348 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

SYNCHK1 DEAD V1 MAX VOLT — Establishes a maximum voltage magnitude for V1 in 1 ‘pu’. Below this magnitude, the V1
voltage input used for synchrocheck is considered “Dead” or de-energized.
SYNCHK1 DEAD V2 MAX VOLT — Establishes a maximum voltage magnitude for V2 in ‘pu’. Below this magnitude, the V2
voltage input used for synchrocheck is considered “Dead” or de-energized.
SYNCHK1 LIVE V1 MIN VOLT — Establishes a minimum voltage magnitude for V1 in ‘pu’. Above this magnitude, the V1 voltage
input used for synchrocheck is considered “Live” or energized.
SYNCHK1 LIVE V2 MIN VOLT — This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this magnitude,
the V2 voltage input used for synchrocheck is considered “Live” or energized.

5.9.8.1 Notes on the synchrocheck function


1. The selected sources for synchrocheck inputs V1 and V2 can include both a three-phase and an auxiliary voltage. The
relay automatically selects the specific voltages to be used by the synchrocheck element in accordance with the
following tables.
Table 5-46: V1 and V2 assigned with different signal source
Number V1 or V2 (source Y) V1 or V2 (source Z) Auto-selected combination SYNCHK Selected
PHASE Voltage for
Source Y Source Z
SELECT comparison
1 3 Phase VT bank with 3 Phase VT bank with 3 Phase VT bank 3 Phase VT bank Auto Vab
or without Auxiliary or without Auxiliary
VT VT
2 3 Phase VT bank with 3 Phase VT bank with 3 Phase VT bank 3 Phase VT bank Vag or Vbg or As set for
or without Auxiliary VT or without Auxiliary Vcg or Vab or SYNCHK PHASE
VT Vbc or Vca SELECT
3 3 Phase VT bank with Auxiliary VT
or without Auxiliary VT
3 Phase VT bank Auxiliary VT Not
applicable
V auxiliary (as
set for Source Z) 5
4 Auxiliary VT Auxiliary VT Auxiliary VT Auxiliary VT Not V auxiliary (as
applicable set for selected
sources)

The voltages V1 and V2 are matched automatically so that the corresponding voltages from the two sources are used
to measure conditions. A phase to phase voltage is used if available in both sources; if one or both of the Sources have
only an auxiliary voltage, this voltage is used. For example, if an auxiliary voltage is programmed to VAG, the
synchrocheck element automatically selects VAG from the other source. If the comparison is required on a specific
voltage, the user has the following two options:
– Select the preferred phase to ground or phase to phase voltage using the SYNCHK PHASE SELECT setting when both
Source 1 and Source 2 have phase VTs
– Externally connect that specific voltage to auxiliary voltage terminals and then use this "Auxiliary Voltage" to
check the synchronism conditions. If using a single CT/VT module with both phase voltages and an auxiliary
voltage, ensure that only the auxiliary voltage is programmed in one of the sources to be used for synchrocheck.
An exception is that synchronism cannot be checked between Delta connected phase VTs and a Wye connected
auxiliary voltage.
Table 5-47: V1 and V2 assigned with same signal source
Number V1 or V2 (source Y) Auto-selected combination Selected Voltage for comparison
V1 V2
1 3 Phase VT bank with Auxiliary VT 3 Phase VT bank Auxiliary VT V auxiliary (as set for Source Y)

When both V1 and V2 are assigned with the same source, the relay automatically assigns the three Phase VT bank to
V1 and Auxiliary VT to V2 and as programmed per setting "Auxiliary VT connection" used for Synchrocheck. For
example, if "Auxiliary VT connection" is programmed to VAG, the synchrocheck element automatically selects VAG
from the 3 Phase VT bank of the same source.
Exception: Synchronism cannot be checked between Delta-connected phase VTs and a Wye-connected auxiliary
voltage.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-349


CONTROL ELEMENTS CHAPTER 5: SETTINGS

2. The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the
configuration of input channels to the source. The relay uses the phase channel of a three-phase set of voltages if
programmed as part of that source. The relay uses the auxiliary voltage channel only if that channel is programmed
as part of the Source and a three-phase set is not.
Figure 5-185: Synchrocheck logic
FLEXLOGIC OPERAND
AND SYNC1 V2 ABOVE MIN

FLEXLOGIC OPERAND
AND SYNC1 V1 ABOVE MIN

FLEXLOGIC OPERAND
AND SYNC1 V1 BELOW MAX

SETTINGS FLEXLOGIC OPERAND


Function AND SYNC1 V2 BELOW MAX

Enabled = 1
Block AND
Off = 0
AND
FLEXLOGIC OPERANDS
AND SYNC1 DE AD S OP
AND SYNC1 DE AD S DPO
SETTING
De ad Source Select FLEXLOGIC OPERANDS
AND OR SYNC1 CLS OP
None
LV1 and D V2 SYNC1 CLS DPO
DV1 and LV2 OR
DV1 or DV2 AND
AND
DV1 xor D V2
DV1 and DV2
AND
SETTING
De ad V1 Max Volt

V1 dMaximum
XOR

SETTING
De ad V2 Max Volt
OR
V2 dMaximum

SETTING

5 Live V1 Min Volt

V1 tMinimum
AND

SETTING
Live V2 Min Volt
AND
V2 tMinimum

SETTING
CALCULATE Max Volt D iff
SETTING SETTING Magnitude V1 Calculate
Angle Φ1 I V1 – V2C I = ΔV ΔV ≤ Maximum
V1 Source Phase Select
= S RC 1 Frequency F 1 FLEXLOGIC OPERANDS
AND SYNC1 SY NC OP
SETTING
Auto SYNC1 SY NC DPO
SETTINGS Max Angle Diff
Vag
V2 Mag COR Factor MC
Vbg Calculate
ΔΦ ≤ Maximum
Vcg V2C = V2*MC I Φ1 – Φ2C I = ΔΦ
Vab
Vbc SETTINGS SYNCHROCHECK 1
Vca CALCU LATE Max Freq D iff
SETTING Magnitude V2 Freq Hysteresis
V2 Source Angle Φ2 Calculate
ΔF ≤ Maximum
= S RC 2 Frequency F 2 I F1 – F2 I = ΔF
ACTUAL VALUES
Synchrocheck 1 ΔF
SETTINGS Synchrocheck 1 ΔΦ
V2 Angle Shift AS Synchrocheck 1 ΔV
Φ2C = Φ2 + AS Synchrocheck 1 ΔΦ’
Synchrocheck 1 V1 MAG
Synchrocheck 1 V1 ANGLE
Synchrocheck 1 V2 MAG
Synchrocheck 1 V2 ANGLE
Synchrocheck 1 V2' MAG
SETTING Synchrocheck 1 V2' ANGLE
SYN-CLOSE :
OFF=0
AND
SETTINGS
S-CLS MAX dF FLEXLOGIC OPERANDS
Freq Hysteresis
AND SYNC1 S-CLOSE OP
|F1 - F2|≤ MAX dF SYNC1 S-CLOSE DPO
SETTINGS
S-CLS MIN dF
Freq Hysteresis

|F1 - F2| ≥ MIN dF FLE XLOGIC OPERANDS


SYNC1 S-CLOSE ARMD

SE TTI NGS SETTING


S-CLS BRK t S-CLS ANG
RUN ΔΦ’ ≤ Maximum
| Φ2 ' - Φ 1 | = ΔΦ’

Φ2' = Φ2C+ΔΦpr edict ed


Where Φ2' is the projected
V2 angle after BRK t,
ΔΦ pr edict ed is the predicted angle
shift after BRK t
827197A1.vsdx

5-350 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

5.9.9 Autoreclose (ANSI 79)


SETTINGS  CONTROL ELEMENTS  AUTORECLOSE  AUTORECLOSE 1(4)
 AUTORECLOSE 1 AR1 FUNCTION: Range: Disabled, Enabled
  Disabled

AR1 INITIATE: Range: FlexLogic operand


 Off

AR1 BLOCK: Range: FlexLogic operand


 Off

AR1 MAX NUMBER OF Range: 1, 2, 3, 4


 SHOTS: 1

AR1 REDUCE MAX TO 1: Range: FlexLogic operand


 Off

AR1 REDUCE MAX TO 2: Range: FlexLogic operand


 Off

AR1 REDUCE MAX TO 3: Range: FlexLogic operand


 Off

AR1 MANUAL CLOSE: Range: FlexLogic operand


 Off

AR1 MNL RST FRM LO: Range: FlexLogic operand


 Off

AR1 RESET LOCKOUT IF Range: Off, On


 BREAKER CLOSED: Off

AR1 RESET LOCKOUT ON Range: Off, On


5
 MANUAL CLOSE: Off

AR1 BKR CLOSED: Range: FlexLogic operand


 Off

AR1 BKR OPEN: Range: FlexLogic operand


 Off

AR1 BLK TIME UPON Range: 0.00 to 655.35 s in steps of 0.01


 MNL CLS: 10.000 s

AR1 DEAD TIME 1: Range: 0.00 to 655.35 s in steps of 0.01


 1.000 s

AR1 DEAD TIME 2: Range: 0.00 to 655.35 s in steps of 0.01


 2.000 s

AR1 DEAD TIME 3: Range: 0.00 to 655.35 s in steps of 0.01


 3.000 s

AR1 DEAD TIME 4: Range: 0.00 to 655.35 s in steps of 0.01


 4.000 s

AR1 ADD DELAY 1: Range: FlexLogic operand


 Off

AR1 DELAY 1: Range: 0.00 to 655.35 s in steps of 0.01


 0.000 s

AR1 ADD DELAY 2: Range: FlexLogic operand


 Off

AR1 DELAY 2: Range: 0.00 to 655.35 s in steps of 0.01


 0.000 s

AR1 RESET LOCKOUT Range: 0.00 to 655.35 s in steps of 0.01


 DELAY: 60.000

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-351


CONTROL ELEMENTS CHAPTER 5: SETTINGS

AR1 RESET TIME: Range: 0.00 to 655.35 s in steps of 0.01


 60.000 s

AR1 INCOMPLETE SEQ Range: 0.00 to 655.35 s in steps of 0.01


 TIME: 5.000 s

AR1 EVENTS: Range: Disabled, Enabled


 Disabled

The F60 is provided with this optional feature, specified at the time of ordering.

The maximum number of autoreclosure elements available is equal to the number of installed CT banks.
The autoreclosure feature is intended for use with transmission and distribution lines, in three-pole tripping schemes for
single breaker applications. Up to four selectable reclosures "shots" are possible prior to locking out. Each shot has an
independently settable dead time. The protection settings can be changed between shots if required, using FlexLogic.
Logic inputs are available for disabling or blocking the scheme.
Faceplate panel LEDs indicate the state of the autoreclose scheme as follows:
• Reclose Enabled — The scheme is enabled and can reclose if initiated
• Reclose Disabled — The scheme is disabled
• Reclose In Progress — An autoreclosure has been initiated but the breaker has not yet been signaled to close
• Reclose Locked Out — The scheme has generated the maximum number of breaker closures allowed and, as the fault
persists, does not close the breaker again; known as "Lockout." The scheme can also be sent in "Lockout" when the
incomplete sequence timer times out or when a block signal occurs while in "reclose in progress." The scheme must be
5 reset from Lockout in order to perform reclose for further faults.
The reclosure scheme is considered enabled when all of the following conditions are true:
• The AR1 FUNCTION is set to “Enabled”
• The scheme is not in the "Lockout" state
• The "Block" input is not asserted
• The AR1 BLK TIME UPON MNL CLS timer is not active
The autoreclose scheme is initiated by a trip signal from any selected protection feature operand. The scheme is initiated
provided the circuit breaker is in the closed state before protection operation.
The reclose-in-progress (RIP) is set when a reclosing cycle begins following a reclose initiate signal. Once the cycle is
successfully initiated, the RIP signal seals-in and the scheme continues through its sequence until one of the following
conditions is satisfied:
• The close signal is issued when the dead timer times out, or
• The scheme goes to lockout
While RIP is active, the scheme checks that the breaker is open and the shot number is below the limit, and then begins
measuring the dead time.
Each of the four possible shots has an independently settable dead time. Two additional timers can be used to increase the
initial set dead times 1 to 4 by a delay equal to AR1 DELAY 1 or AR1 DELAY 2 or the sum of these two delays depending on the
selected settings. This offers enhanced setting flexibility using FlexLogic operands to turn the two additional timers “on”
and “off.” These operands can possibly include AR1 SHOT CNT =n, SETTING GROUP ACT 1, and so on. The autoreclose
provides up to maximum 4 selectable shots. Maximum number of shots can be dynamically modified through the settings
AR1 REDUCE MAX TO 1 (2, 3), using the appropriate FlexLogic operand.
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs:
• The maximum shot number was reached
• A "Block" input is in effect (for instance, Breaker Failure or bus differential protection operated)
• The "Incomplete Sequence" timer times out

5-352 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

The recloser is latched in the Lockout state until a "reset from lockout" signal is asserted, either from a manual close of the
breaker or from a manual reset command (local or remote). The reset from lockout can be accomplished by operator
command, by manually closing the breaker, or whenever the breaker has been closed and stays closed for a preset time.
After the dead time elapses, the scheme issues the close signal. The close signal is latched until the breaker closes or the
scheme goes to Lockout.
A reset timer output resets the recloser following a successful reclosure sequence. The reset time is based on the breaker
"reclaim time," which is the minimum time required between successive reclose sequences.

5.9.9.1 Settings
AR1 INITIATE — Selects the FlexLogic operand that initiates the scheme, typically the trip signal from protection.
AR1 BLOCK — Selects the FlexLogic operand that blocks the autoreclosure initiate (it can be from the breaker failure, bus
differential protection, and so on).
AR1 MAX NUMBER OF SHOTS — Specifies the number of reclosures that can be attempted before reclosure goes to “Lockout”
because the fault is permanent.
AR1 REDUCE MAX TO 1(3) — Selects the FlexLogic operand that changes the maximum number of shots from the initial
setting to 1, 2, or 3, respectively.
AR1 MANUAL CLOSE — Selects the logic input set when the breaker is manually closed.
AR1 MNL RST FRM LO — Selects the FlexLogic operand that resets the autoreclosure from Lockout condition. Typically this is
a manual reset from lockout, local or remote.
AR1 RESET LOCKOUT IF BREAKER CLOSED — This setting allows the autoreclose scheme to reset from Lockout if the breaker
has been manually closed and stays closed for a preset time. In order for this setting to be effective, disable the next
setting (AR1 RESET LOCKOUT ON MANUAL CLOSE).
AR1 RESET LOCKOUT ON MANUAL CLOSE — This setting allows the autoreclose scheme to reset from Lockout when the 5
breaker is manually closed regardless if the breaker remains closed or not. This setting overrides the previous setting (AR1
RESET LOCKOUT IF BREAKER CLOSED).
AR1 BLK TIME UPON MNL CLS — The autoreclose scheme can be disabled for a programmable time delay after the
associated circuit breaker is manually closed. This prevents reclosing onto a fault after a manual close. This delay must be
longer than the slowest expected trip from any protection not blocked after manual closing. If no overcurrent trips occur
after a manual close and this time expires, the autoreclose scheme is enabled.
AR1 DEAD TIME 1 to AR1 DEAD TIME 4 — These are the intentional delays before first, second, third, and fourth breaker
automatic reclosures (1st, 2nd, and 3rd shots), respectively. Set them longer than the estimated deionizing time following a
three pole trip.
AR1 ADD DELAY 1 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 1) to the initial set
Dead Time (1 to 4). When this setting is “Off,” Delay 1 is by-passed.
AR1 DELAY 1 — This setting establishes the extent of the additional dead time Delay 1.
AR1 ADD DELAY 2 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 2) to the initial set
Dead Time (1 to 4). When this setting is “Off”, Delay 2 is by-passed.
AR1 DELAY 2 — This setting establishes the extent of the additional dead time Delay 2.
AR1 RESET LOCKOUT DELAY — This setting establishes how long the breaker stays closed after a manual close command, in
order for the autorecloser to reset from Lockout.
AR1 RESET TIME — A reset timer output resets the recloser following a successful reclosure sequence. The setting is based
on the breaker "reclaim time," which is the minimum time required between successive reclose sequences.
AR1 INCOMPLETE SEQ TIME — This timer defines the maximum time interval allowed for a single reclose shot. It is started
whenever a reclosure is initiated and is active when the scheme is in the "reclose-in-progress" state. If all conditions
allowing a breaker closure are not satisfied when this time expires, the scheme goes to Lockout.

This timer must be set to a delay less than the reset timer.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-353


5

5-354
FLEXLOGIC OPERAND
AR1 BLK FROM MAN CLS
CONTROL ELEMENTS

FLEXLOGIC OPERAND
Enabled
AR1 ENABLED (Default)
SETTING

AR1 FUNCTION: FLEXLOGIC OPERAND


Disabled
AR1 DISABLED (Default)
Enable=1

FLEXLOGIC OPERAND SETTING


SETTING
AR1 RIP
AR1 BLOCK: Shot cnt = 3 AR1 DEAD TIME 4:
In progress
Off = 0 (Default)
AND O
AND
SETTING SETTING
SETTING SETTING
AR1 BLK TIME UPON SETTING
AR1 MANUAL CLOSE: MNL CLOSE : AR1 ADD DELAY 1: AR1 DELAY 1:
Shot cnt = 2 AR1 DEAD TIME 3:
Off = 0 O Off = 0
AND O
From AND
LO Sheet 2 O
SETTING OR
AND
AR1 INITIATE: SETTING AND
OR
Off = 0 AR1 DEAD TIME 2:
Shot cnt = 1

SETTING AND SETTING SETTING


OR O
AR1 BKR CLOSED: AR1 ADD DELAY 2: AR1 DELAY 2:
Off = 0 SETTING Off = 0
AND O
Shot cnt = 0 AR1 DEAD TIME 1:
AND Close
AND OR
SETTING
AND O AND
AR1 BKR OPEN:

Off = 0

AR Initiate

Bkr Is Closed
Shot cnt = Max

AND FLEXLOGIC OPERAND


AR1 LO
AND
Locked out
Figure 5-186: Autorecloser logic (Sheet 1 of 2)

SETTING (Default)
To sheet 2

SETTING
AR1 INCOMPLETE SEQ
SETTING AR1 RESET LOCKOUT TIME:
AR1 RESET LOCKOUT IF DELAY:
OR LO
BREAKER CLOSED: OR
AND LO
O
On=1 0 AND

SETTING
AR1 RESET LOCKOUT ON
MANUAL CLOSE:
AND OR
On=1 AND

SETTING
Reset From LO
AR1 MNL RST FROM LO:
827081AE.CDR
Off = 0

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
13DE1<F1<E5
1ED?B53<?C5!
C8?D3?E>D* !"#$ D_
CXUUd!
CHAPTER 5: SETTINGS

C
6<5H<?793?@5B1>4
<QdSX 1B!3<?C5
C8?D3?E>D5B
6<5H<?793?@5B1>4C
?B B
CX_dS^d-$ 1B!C8?D3>D-$
3\_cU 9^SbU]U^d
cX_d CX_dS^d-# 1B!C8?D3>D-#

2[bYc3\_cUT S_e^dUb CX_dS^d-" 1B!C8?D3>D-"


CX_dS^d-! 1B!C8?D3>D-!
D_ ! ]c BUcUdcX_d
1B9^YdYQdU C5DD9>7 ?B S_e^dUb CX_dS^d- 6<5H<?793?@5B1>4
CXUUd!
1>4 ?B 1B!C8?D3>D-
<? 1B!B5C5DD9=5*

BUcUdVb_]<? ?B
1>4 ?

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


C5DD9>7
1B!=1H>E=25B 1>4
?6C8?DC*

=1H-! 1>4
?B 1>4

=1H-" ?B CX_d3_e^d-=1H
?B
1>4
1>4
=1H-#
?B

=1H-$
1>4
Figure 5-187: Autorecloser logic (Sheet 2 of 2)

1>4
C5DD9>7

1B!B54E35=1HD?!*

?VV-

C5DD9>7

1B!B54E35=1HD?"*

?VV-

C5DD9>7

1B!B54E35=1HD?#*

?VV-
("' ("1'34B

5-355
CONTROL ELEMENTS

5
5

5-356
CONTROL ELEMENTS

2B51;5B
CD1DEC

61E<D DB9@ 3?>D13DC 1B3 3<?C5 3?>D13DC DB9@ 3?>D13DC 1B3


?33EBC 3?==1>4 C5@1B1D5 5HD9>7E9C85C 3?==1>4 3<?C5 3?==1>4 C5@1B1D5 5HD9>7E9C85C

@B?DD9=5 ?@5>9>7D9=5 3<?C9>7D9=5 @B?DD9=5 ?@5>9>7D9=5

2;B3<?C54

2;B?@5>

61E<D4EB1D9?> 61E<D4EB1D9?>

1B7?5CD? B5C5D6B?=<?3;?ED
<?3;?ED* 1B5>12<54
1B5>12<54 1B9>9D91D5 2;B?@5> 3<?C543?==1>4 2;B3<?C54 1B9>9D91D5 C8?D3?E>D-=1H

B53<?C59>@B?7B5CC B9@ <?3;?ED

1ED?B53<?C5

4514D9=5

9>3?=@<5D5C5AE5>359CD9=9>7 9>3?=@<C5AD9=9>7
Figure 5-188: Single shot autoreclosing sequence - permanent fault

B5C5DD9=5B9CD9=9>7
("'( "1"34B

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
CHAPTER 5: SETTINGS CONTROL ELEMENTS

5.9.10 Digital elements


SETTINGS  CONTROL ELEMENTS  DIGITAL ELEMENTS  DIGITAL ELEMENT 1(96)
 DIGITAL ELEMENT 1 DIGITAL ELEMENT 1 Range: Disabled, Enabled
  FUNCTION: Disabled

DIG ELEM 1 NAME: Range: up to 16 alphanumeric characters


 Dig Element 1

DIG ELEM 1 INPUT: Range: FlexLogic operand


 Off

DIG ELEM 1 PICKUP Range: 0.000 to 999999.999 s in steps of 0.001


 DELAY: 0.000 s

DIG ELEM 1 RESET Range: 0.000 to 999999.999 s in steps of 0.001


 DELAY: 0.000 s

DIGITAL ELEMENT 1 Range: Disabled, Enabled


 PICKUP LED: Enabled

DIG ELEM 1 BLOCK: Range: FlexLogic operand


 Off

DIGITAL ELEMENT 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

DIGITAL ELEMENT 1 Range: Disabled, Enabled


 EVENTS: Disabled

Digital elements run once per power system cycle.


As such they can easily fail to react to an input signal or a block signal with a duration less than one power system
5
cycle. This also means that digital element output can react up to one power system cycle later than the pickup
and reset delay settings indicate.
Do not use digital elements with transient signals, such as communications commands. Do not use digital
elements where random delays of up to one cycle cannot be tolerated, such as in high speed protection.
There are 96 identical digital elements available, numbered 1 to 96. A digital element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name to be referenced in any target message, a blocking input from any selected FlexLogic operand,
and a timer for pickup and reset delays for the output operand.
DIGITAL ELEMENT 1 INPUT — Selects a FlexLogic operand to be monitored by the digital element.
DIGITAL ELEMENT 1 PICKUP DELAY — Sets the required time delay from element pickup to element operation. If a pickup delay
is not required, set to "0," To avoid nuisance alarms, set the delay greater than the operating time of the breaker.
DIGITAL ELEMENT 1 RESET DELAY — Sets the time delay to reset. If a reset delay is not required, set to “0.”
DIGITAL ELEMENT 1 PICKUP LED — This setting enables or disabled the digital element pickup LED. When set to “Disabled,” the
operation of the pickup LED is blocked.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-357


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-189: Digital element logic

SETTING
DIGITAL ELEMENT 01
FUNCTION: SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY: DIG ELEM 01 DPO
DIGITAL ELEMENT 01
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0
827042A2.VSD

Circuit monitoring applications


Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts.
The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A).
As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the Cont
Op 1 VOn FlexLogic operand is set (for contact input 1—corresponding operands exist for each contact output). If the
output circuit has a high resistance or the DC current is interrupted, the trickle current drops below the threshold and the
Cont Op 1 VOff FlexLogic operand is set. Consequently, the state of these operands can be used as indicators of the
integrity of the circuits in which form-A contacts are inserted.

5 Example 1: Breaker trip circuit integrity monitoring


In many applications it is desired to monitor the breaker trip circuit integrity so that problems can be detected before a trip
operation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output
contact detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high
resistance, the trickle current falls below the monitor threshold, and an alarm is declared.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact that is open when the
breaker is open (see figure). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the
breaker position.
Figure 5-190: Trip circuit example 1
UR-series device
with form-A contacts

H1a
I

H1b DC–

V DC+
H1c 52a Trip coil

I = current monitor
V = voltage monitor 827073A2.CDR

5-358 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

Assume the output contact H1 is a trip contact. Using the contact output settings, this output is given an ID name; for
example, “Cont Op 1." Assume a 52a breaker auxiliary contact is connected to contact input H5a to monitor breaker status.
Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is
closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown).

Example 2: Breaker trip circuit integrity monitoring


If it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method to
maintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the
following figure). This can be achieved by connecting a suitable resistor (see figure) across the auxiliary contact in the trip
circuit. In this case, it is not required to supervise the monitoring circuit with the breaker position – the BLOCK setting is
selected to “Off.” In this case, the settings are as follows (EnerVista example shown). 5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-359


CONTROL ELEMENTS CHAPTER 5: SETTINGS

Figure 5-191: Trip circuit example 2


UR-series device
with form-A contacts

Values for resistor “R”


H1a
Power supply Resistance Power
I
24 V DC 1000 O 2W
H1b DC– 30 V DC 5000 O 2W
48 V DC 10000 O 2W
V DC+
110 V DC 25000 O 5W
H1c 52a Trip coil
125 V DC 25000 O 5W
R
250 V DC 50000 O 5W
Bypass
I = current monitor resistor
V = voltage monitor 827074A3.CDR

The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.

5.9.11 Digital counters


SETTINGS  CONTROL ELEMENTS  DIGITAL COUNTERS  COUNTER 1(8)
 COUNTER 1 COUNTER 1 Range: Disabled, Enabled
5   FUNCTION: Disabled

COUNTER 1 NAME: Range: up to 12 alphanumeric characters


 Counter 1

COUNTER 1 UNITS: Range: up to six alphanumeric characters



COUNTER 1 PRESET: Range: –2,147,483,648 to +2,147,483,647
 0

COUNTER 1 COMPARE: Range: –2,147,483,648 to +2,147,483,647


 0

COUNTER 1 UP: Range: FlexLogic operand


 Off

COUNTER 1 DOWN: Range: FlexLogic operand


 Off

COUNTER 1 BLOCK: Range: FlexLogic operand


 Off

CNT1 SET TO PRESET: Range: FlexLogic operand


 Off

COUNTER 1 RESET: Range: FlexLogic operand


 Off

COUNT1 FREEZE/RESET: Range: FlexLogic operand


 Off

COUNT1 FREEZE/COUNT: Range: FlexLogic operand


 Off

There are eight identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions
from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of
an external contact (for example, breaker auxiliary switch), or pulses from a watt-hour meter.

5-360 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS CONTROL ELEMENTS

COUNTER 1 UNITS — Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted. The
units label appears in the corresponding actual values status.
COUNTER 1 PRESET — Sets the count to a required preset value before counting operations begin, as in the case where a
substitute relay is to be installed in place of an in-service relay, or while the counter is running.
COUNTER 1 COMPARE — Sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set value.
COUNTER 1 UP — Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when the
accumulated value is at the limit of +2,147,483,647 counts, the counter rolls over to –2,147,483,648.
COUNTER 1 DOWN — Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is received
when the accumulated value is at the limit of –2,147,483,648 counts, the counter rolls over to +2,147,483,647.
COUNTER 1 BLOCK — Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked.
CNT1 SET TO PRESET — Selects the FlexLogic operand used to set the count to the preset value. The counter sets to the
preset value in the following situations:
• When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled and
CNT1 SET TO PRESET operand is 0, the counter sets to 0)
• When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO PRESET
changing from 1 to 0 while the counter is running has no effect on the count)
• When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 1
(when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 0, the
counter sets to 0)
COUNTER 1 RESET — Selects the FlexLogic operand for setting the count to either “0” or the preset value depending on the
state of the CNT1 SET TO PRESET operand.
COUNTER 1 FREEZE/RESET — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a 5
separate register with the date and time of the operation, and resetting the count to “0.”
COUNTER 1 FREEZE/COUNT — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a
separate register with the date and time of the operation, and continuing counting. The present accumulated value and
captured frozen value with the associated date/time stamp are available as actual values. If control power is interrupted,
the accumulated and frozen values are saved into non-volatile memory during the power-down operation.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-361


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Figure 5-192: Digital counter logic


SETTING
COUNTER 1 FUNCTION:
Enabled = 1 SETTINGS
COUNTER 1 NAME:
SETTING AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
COUNTER 1 UP:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: Count equal to Comp.
VALUE COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO

SETTING
COUNTER 1 BLOCK:
SET TO PRESET VALUE
Off = 0
SET TO ZERO
SETTING ACTUAL VALUE
CNT 1 SET TO PRESET: COUNTER 1 ACCUM:
OR
Off = 0
AND

SETTING AND ACTUAL VALUE


COUNTER 1 RESET:
COUNTER 1 FROZEN:
Off = 0 OR
STORE DATE & TIME Date & Time
SETTING
COUNT1 FREEZE/RESET:
Off = 0
OR
SETTING

5 COUNT1 FREEZE/COUNT:
Off = 0
827065A4.VSD

5.10 Monitoring elements


5.10.0.1 Menu
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS
 MONITORING  HI-Z See below
 ELEMENTS  

 BREAKER 1 See page 5-368


  ARCING CURRENT

 BREAKER 2
  ARCING CURRENT

 BREAKER See page 5-372


  FLASHOVER 1

 BREAKER
  FLASHOVER 2

 BREAKER RESTRIKE 1 See page 5-377


 

 BREAKER RESTRIKE 3
 

 CT FAILURE See page 5-379


  DETECTOR 1

5-362 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

 CT FAILURE
  DETECTOR 1

 INCIPIENT FAULT 1 See page 5-381


 

 INCIPIENT FAULT 2
 

 VT FUSE FAILURE 1 See page 5-383


 

 VT FUSE FAILURE 4
 

 THERMAL OVERLOAD See page 5-385


  PROTECTION

 BROKEN CONDUCTOR See page 5-389


 

 HARMONIC See page 5-391


  DETECTION

5.10.0.2 High-impedance fault detection


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  HI-Z
 HI-Z HI-Z FUNCTION: Range: Disabled, Enabled
  Disabled

 HI-Z SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4 5
HI-Z ARCING Range: 1 to 10 in steps of 1
 SENSITIVITY: 5

HI-Z ARCING DET SOE Range: 0.0 to 6000.0 s in steps of 0.1


 RESET TIME: 0.0 s

HI-Z PHASE EVENT Range: 10 to 250 in steps of 1


 COUNT: 30

HI-Z GROUND EVENT Range: 10 to 500 in steps of 1


 COUNT: 30

HI-Z EVENT COUNT Range: 5 to 180 min. in steps of 1


 TIME: 15 min

HI-Z OC PROTECTION Range: 10 to 200 s in steps of 1


 COORD TIMEOUT: 15 s

HI-Z PHASE OC MIN Range: 0.01 to 10.00 pu in steps of 0.01


 PICKUP: 1.50 pu

HI-Z NEUTRAL OC MIN Range: 0.01 to 10.00 pu in steps of 0.01


 PICKUP: 1.00 pu

HI-Z PHASE RATE OF Range: 1 to 999 A/2cycle in steps of 1


 CHANGE: 150 A/2cycle

HI-Z NEUTRAL RATE OF Range: 1 to 999 A/2cycle in steps of 1


 CHANGE: 150 A/2cycle

HI-Z LOSS OF LOAD Range: 5 to 100% in steps of 1


 THRESHOLD: 15%

HI-Z 3-PHASE EVENT Range: 1 to 1000 A in steps of 1


 THRESHOLD: 25 A

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-363


MONITORING ELEMENTS CHAPTER 5: SETTINGS

HI-Z BLOCK: Range: Flexlogic Operand


 Off

HI-Z VOLTAGE SUPV Range: 0 (off) to 100% in steps of 1


 THRESHOLD: 5%

HI-Z VOLTAGE SUPV Range: 0 to 300 cycles in steps of 2


 DELAY: 60 cycles

HI-Z EVEN HARMONIC Range: 0 to 100% in steps of 1


 RESTRAINT: 20%

HI-Z TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

HI-Z EVENTS: Range: Disabled, Enabled


 Disabled

Some faults in overhead distribution feeders are characterized by low fault current due to high ground resistance. If the
fault current is in the order of expected unbalance load or less, it cannot be reliably detected by conventional overcurrent
protection. These faults are classified as high-impedance (Hi-Z) faults. Since a Hi-Z fault is not accompanied by excessive
current, it is generally not dangerous to the electrical installation except for some damage to the overhead conductor at
the fault location. However, an undetected Hi-Z fault is a risk to people and property as well as having potential to evolve
into a full-blown fault.
The following event types are associated with Hi-Z faults. It is assumed that for all cases that ground is involved.
• High impedance fault — A fault with fault impedance sufficiently high such that it is not detected by conventional
overcurrent protection and contact with a ground is not confirmed by the algorithm. Output of the Hi-Z algorithm for
such a fault is the HI-Z ARC DETECTED operand, where prolonged arcing presence is confirmed by the Expert Arc

5 Detector (EAD) algorithm with a chosen "Arcing Sensitivity" setting. This operand can be used to initiate feeder de-
energization either immediately or for greater security after a few assertions of the operand over a period of time.
• High impedance, downed conductor fault — A high impedance fault for which the primary conductor is no longer
intact on pole top insulators, but instead is in contact with earth or a grounded object. Output of the Hi-Z algorithm for
such a fault is the HI-Z DOWNED COND operand, where prolonged arcing presence along with conductor contact to
the ground is confirmed by the EAD algorithm with a chosen HI-Z ARCING SENSITIVITY setting. This operand can be used
to initiate feeder de-energization immediately.
• Arcing event — Any event (which can develop into fault) that exhibits excessive arcing, but cannot be confirmed as a
fault by the EAD. Output of the Hi-Z algorithm for such an event is the HI-Z ARC SUSPECTED operand, which is an
indication that significant and unusual harmonics content is present and can be used as an alarm for further
investigation or action.
Combinations of these events are possible: for example, an arcing high impedance, downed conductor fault. The Hi-Z
element is intended to detect high impedance faults that arc and to differentiate those that are downed conductors from
those that are not. It should be noted that no known technology can detect all Hi-Z faults. Although the percentage of the
correct operations of the Hi-Z element is very high, very rarely and under some unusual conditions the Hi-Z algorithm can
fail to detect a Hi-Z fault or issue nuisance output.
The Hi-Z element was primarily designed for solidly grounded systems. The similar Hi-Z element in the F60 predecessor
DFM200 relay has been tested with some success on impedance grounded systems as well. However, there are no
guarantees of certain operation of the Hi-Z element on non-solidly grounded systems.
The Hi-Z data collection consists of RMS Data Capture and Hi-Z Data capture:
• RMS Data Capture — The RMS data captures are triggered by two-cycle Hi-Z overcurrent conditions, loss of load
conditions, and high arc confidence conditions. Captures triggered by loss of load and high arc confidence conditions
are saved to a temporary capture table, and deleted if the event does not result in an Arcing or Downed Conductor
condition. The relay maintains a history of four captures and utilizes a combination of age, priority and access for
determining which capture to save.
The RMS data capture contains the two-cycle RMS values for the voltage and current for each of the phases and
current for the neutral channel. The capture frequency is half the system frequency. Each capture contains 1800
points.

5-364 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

• High-Z Data Capture — Hi-Z Data Captures are triggered and maintained in an identical manner as RMS Data
Captures. The relay maintains four captures of 300 records each. The capture frequency is 1 Hz and the data collected
is defined in the following two tables.
Table 5-48: Hi-Z specific data
# Name Description
0 EadCounts Total number of EAD counts for the phase
1 ArcConfidence ArcConfidence for the phase
2 AccumArcConf Accumulated ArcConfidence for the phase
3 RmsCurrent The 2-cycle RMS current for the phase
4 HighROC Flag indicating a high rate of change was detected
5 IOC Flag indicating an instantaneous 2-cycle overcurrent was detected
6 LossOfLoad Flag indicating a loss of load was detected
7 EadZeroed Flag indicating that this phase’s EAD table was cleared
8 HighZArmed Flag indicating that this phase is armed for a high-Z detection
9 VoltageDip Flag indicating that a voltage dip was detected on this phase
10 HighEad Flag indicating that a high arc confidence occurred on this phase
11 ArcBurst Flag indicating that an arc burst was identified on this phase
12 VDisturbanceCc Cycle-to-cycle voltage disturbance
13 VDisturbanceAbs Absolute voltage disturbance
14 HarmonicRestraint Harmonic Restraint

Table 5-49: Hi-Z capture data


# Name Description
5
1 StatusMask Bit-mask of the algorithm state (16 bits)
BIT_ARCING
BIT_DOWNED_COND
BIT_ARC_TREND
BIT_PHASE_A

BIT_PHASE_B
BIT_PHASE_C
BIT_PHASE_N
BIT_IOC_A

BIT_IOC_B
BIT_IOC_C
BIT_IOC_N
BIT_LOL_A

BIT_LOL_B
BIT_LOL_C
BIT_I_DISTURBANCE
BIT_V_DISTURBANCE
2 AlgorithmState Present value of the High-Z output state machine: Normal = 0, Coordination Timeout = 1,
Armed = 2, Arcing = 5, Downed Conductor = 9
3 EadZeroedFlag Flag indicating the EAD table was cleared
4 SpectralFlag Flag indicating the Spectral algorithm has found a match
5 ThreePhaseFlag Flag indicating a three phase event was detected
6 PhaseInfo[4] Phase specific information for the three phase currents and the neutral (see table below)

The algorithm is in “Normal” state when it detects no abnormal activity on the power system. While in the “Normal” state,
any one of several power system events (a high output of the Expert Arc Detector, a significant loss of load, or a Hi-Z
overcurrent) cause the algorithm to move to the “Coordination Timeout” state, where it remains for the time specified by
the OC Protection Coord Timeout setting. Following this interval, the algorithm moves into its “Armed” state. The criteria for
detecting arcing or a downed conductor are:

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-365


MONITORING ELEMENTS CHAPTER 5: SETTINGS

• The Expert Arc Detector Algorithm's output reaches a high level enough times, and
• Its high level was last reached when the algorithm's state was “Armed”
The “Arcing Sensitivity” setting determines what level constitutes a “high” output from the Expert Arc Detector Algorithm,
and the number that constitutes what “enough times” means. If these criteria are met, the algorithm temporarily moves to
either the “Arcing” state or the “Downed Conductor” state, the difference being determined by whether or not there was a
significant, precipitous loss of load (as determined by the LOSS OF LOAD THRESHOLD setting) or a Hi-Z overcurrent (as
determined by the PHASE OC MIN PICKUP and NEUTRAL OC MIN PICKUP settings). If either of these caused the algorithm to
move from its “Normal” state to its “Coordination Timeout” state, then the algorithm moves to the “Downed Conductor”
state temporarily. Otherwise, it temporarily moves to the “Arcing” state. After pulsing either of these outputs, the
algorithm's state returns to “Normal”. Also, if two minutes pass without high levels from the Expert Arc Detector Algorithm
while the algorithm is in its Armed state, then it moves from the “Armed” state directly back to the “Normal” state.
Two FlexLogic operands, HI-Z ARMED and HI-Z DISARMED, are created to represent the armed state of the Hi-Z
element. The HI-Z ARMED operand is on when the algorithm is in the armed state, whereas the HI-Z DISARMED
operand is on when the algorithm is not in the armed state. When the algorithm is armed, this also includes the arcing and
downed conductor states. When the algorithm is disarmed, this also includes the normal and coordination timeout states
(as defined by Modbus format F187 as described in the Modbus memory map in the UR Series Communications Guide).
The Hi-Z settings are as follows.
HI-Z SOURCE — Selects the source for the RMS currents and voltages used in Hi-Z algorithms. The source should include
currents from the 8F/8G CT module and appropriate voltages. If the source does not include voltages, Voltage Supervision
is disabled.
HI-Z ARCING SENSITIVITY — Establishes the belief-in-arcing confidence level at which the Hi-Z element recognizes arcing
and the number of times the algorithm must conform its belief in arcing before it produces an output. The range is 1 to 10,
where 10 is the most sensitive and 1 is the least sensitive setting.
5 A higher setting is suitable for a very quiet, well-behaved power system. An initial setting of 5 is suggested if the user has
no previous experience with the Hi-Z element.
HI-Z ARCING DET SOE RESET TIME — An ARCING DETECTED event is created upon the detection of arcing by the expert arc
detector algorithm. This setting defines the amount of time to hold creation of any new arcing detected events. Any
subsequent arcing detection during this time restarts the hold timer. An ARCING DETECTED DPO event is generated upon
the expiration of this reset time. The state of the expert arc detector algorithm is unaffected by this timer. The HI-Z ARC
DETECTED DPO operand is set to “On” when the ARCING DETECTED DPO event is created, and remains on until an
ARCING DETECTED event is created.
HI-Z PHASE EVENT COUNT — Specifies how many individual belief-in-arcing indications for a phase current must be counted
in a specified time period before it is determined that an arcing-suspected event exists. These belief-in-arcing indications
are detected by arc detection algorithms (energy and randomness) for a specific set of non-fundamental frequency
component energies. This setting affects only the Hi-Z Arcing Suspected outputs.
HI-Z GROUND EVENT COUNT — Specifies how many individual belief-in-arcing indications for a ground/neutral current must
be counted in a specified time period before it is determined that an arcing-suspected event exists. These belief-in-arcing
indications are detected by arc detection algorithms (energy and randomness) for a specific set of non-fundamental
frequency component energies. This setting affects only the Hi-Z Arcing Suspected outputs.
HI-Z EVENT COUNT TIME — Specifies the time (in minutes) over which the relay monitors long-term, sporadic, arcing events
for determination of an arcing-suspected event. This setting affects only the Hi-Z Arcing Suspected outputs.
HI-Z OC PROTECTION COORD TIMEOUT — Coordinates between the Hi-Z element and conventional feeder overcurrent
protection. A downed conductor or an arcing, intact conductor is not indicated before the expiration of this timeout, which
begins when the Hi-Z element detects a trigger condition (such as loss of load, high rate of change, overcurrent, breaker
open, or high belief-in-arcing confidence). Note that this is a minimum operating time; the actual operating time depends
on the fault characteristics and is likely significantly longer than this setting.
Set the value such that the conventional feeder overcurrent protection is given an opportunity to operate before the
timeout expires. It is recommended that this timeout value not exceed 30 seconds, because arcing fault current often
diminishes as the fault progresses, making the fault more difficult to detect with increasing time. After the timeout has
expired, at least one additional arc burst must occur in order for the Hi-Z element to proceed with its analysis.

5-366 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

HI-Z PHASE OC MIN PICKUP — Phase overcurrent minimum pickup indicates the level at which the Hi-Z element considers a
phase current to be an overcurrent condition. The Hi-Z detection algorithms ignore all data as long as an overcurrent
condition exists on the system, because it is assumed that conventional feeder overcurrent protection clears an
overcurrent fault. It is recommended that this setting be above the maximum load current.
HI-Z NEUTRAL OC MIN PICKUP — Neutral overcurrent minimum pickup indicates the level at which the Hi-Z element
considers a neutral current to be an overcurrent condition. The Hi-Z detection algorithms ignore all data as long as an
overcurrent condition exists on the system, because it is assumed that conventional feeder overcurrent protection clears
an overcurrent fault. It is recommended that this setting is above the maximum 3I0 (residual) current due to unbalanced
loading.
HI-Z PHASE RATE OF CHANGE — Establishes a threshold for determining when a high rate-of-change event occurs on a
phase RMS current. An extremely high rate of change is not characteristic of most high impedance faults; it is more
indicative of a low impedance fault or of the inrush of breaker closing. The inrush current produces substantial variations in
the harmonics used by the high impedance algorithms. Therefore these algorithms ignore all data for several seconds
following a high rate-of-change event that exceeds this setting.
The RMS currents in the Hi-Z algorithms are calculated over a two-cycle time window. The rate-of-change is calculated as
the difference between two consecutive two-cycle RMS readings. The recommended setting is 150 A per two-cycle
interval. The setting is given in primary amperes.
HI-Z NEUTRAL RATE OF CHANGE — Establishes a threshold for determining when a high rate-of-change event occurs on a
neutral RMS current. An extremely high rate of change is not characteristic of most high impedance faults; it is more
indicative of a breaker closing, causing associated inrush. The inrush current produces substantial variations in the
harmonics used by the high impedance algorithms. Therefore, these algorithms ignore all data for several seconds
following a high rate-of-change event exceeding this setting.
The RMS currents in the Hi-Z algorithms are calculated over a two-cycle time window. The rate-of-change is calculated as
the difference between two consecutive two-cycle RMS readings. The recommended setting is 150 A per two-cycle
interval. The setting is given in primary amperes. 5
HI-Z LOSS OF LOAD THRESHOLD — Establishes the loss of load level used as an indication of a downed conductor. A Loss of
Load flag is set if the Hi-Z algorithms detect a percentage drop in phase current between two successive two-cycle RMS
values that equals or exceeds the Loss of Load Threshold. The amount the phase current must decrease between
successive two-cycle RMS values is based on this setting times the recent average phase current level. The range is 5 to
100%; 5% being the most sensitive.
HI-Z 3-PHASE EVENT THRESHOLD — Establishes the level at which the Hi-Z element characterizes a sudden three-phase
current increase as a three-phase event. The Hi-Z detection algorithms ignore the data generated by a large three-phase
event. The recommended setting is 25 A (primary).
HI-Z BLOCK — Assertion of the FlexLogic operand assigned to this setting blocks operation of Hi-Z element.
HI-Z VOLTAGE SUPV THRESHOLD — In the event that a fault simultaneously occurs on two adjacent feeders (line voltage from
the same bus), the drop in line voltage causes a subsequent drop in load current. This function blocks the Loss of Load flag
from being set while the voltage is depressed. Thus, if the voltage level drops by a percentage greater than this threshold in
successive two-cycle RMS samples, the Loss of Load flag is blocked. If the setting is “0”, the voltage supervision function is
disabled.
HI-Z VOLTAGE SUPV DELAY — This setting adds time delay to the voltage supervision function. Specifically, the Loss of Load
flag continues to be blocked for the number of cycles specified by this setting.
HI-Z EVEN HARMONIC RESTRAINT — This setting determines the level of the even harmonic at which the setting of the
overcurrent flags is inhibited. The even harmonic content is evaluated on each phase current as a percentage of that
phase's RMS current. The intent is to inhibit the setting of the overcurrent flags if the overcurrent is simply a surge caused
by cold-load pickup or other inrush event.

IMPORTANT NOTE REGARDING INSTALLATION — The F60 Hi-Z algorithm is adaptive in nature. The algorithm’s
internal thresholds gradually adapt to background “noise” on circuits with a moderate to high level of transient
activity. For the first three to five days after installation (or after being out-of-service for a significant period), the
F60 can identify some of this noise as arcing. Take this into account when responding to alarms during these
operating periods.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-367


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Figure 5-193: Hi-Z logic


SETTINGS
HI-Z PHASE EVENT
COUNT:
HI-Z GROUND EVENT
COUNT:
HI-Z EVENT COUNT
TIME: FLEXLOGIC OPERANDS
COUNT PH A > PH COUNT
HI-Z ARC SUSPECTED-A
in COUNT TIME

SETTING SETTING COUNT PH B > PH COUNT


HI-Z ARC SUSPECTED-B
in COUNT TIME
HI-Z FUNCTION: HI-Z ARCING SENSITIVITY:
COUNT PH C > PH COUNT
HI-Z ARC SUSPECTED-C
in COUNT TIME
Enabled=1 RUN
COUNT G > GND COUNT
AND HI-Z ARC SUSPECTED-N
in COUNT TIME
SETTING
ENERGY ALGORITHM HI-Z ARC SUSPECTED
HI-Z BLOCK: LOAD ANALYSIS ALGORITHM
RUN
PH A SETTINGS
Off=0
PH B HI-Z OC PROTECTION
COORD TIMEOUT:
PH C
GND INDIRECT SETTING
EAD COUNT LIMIT:

RANDOMNESS ALGORITHM INDIRECT SETTING FLEXLOGIC OPERANDS


RUN EXPERT ARC DETECTOR EAD THRESHOLD: HI-Z ARC DETECTED

HI-Z MODULE PH A Arcing Confidence Ph A HIGH EADs (A) > LIMIT HI-Z ARC DETECTED-A
PH B Arcing Confidence Ph B HIGH EADs (B) > LIMIT HI-Z ARC DETECTED-B
EVEN, ODD AND PHASE
NON HARMONICS PH C Arcing Confidence Ph C HIGH EADs (C) > LIMIT SELECTION HI-Z ARC DETECTED-C
CT
SATURATION GND Arcing Confidence G HIGH EADs (G) > LIMIT LOGIC AND HI-Z DOWNED COND
DETECTOR Zero Confidence Level ARC ALARM HI-Z DOWNED COND-A
(Selects Any CL > EAD Thresh. VS. DOWNED
SETTING the HI-Z DOWNED COND-B
LOAD EVENT DETECTOR ALGORITHM CONDUCTOR
source DISCRIMINATOR HI-Z DOWNED COND-C
of SETTING HiZ STATE=NORMAL
HI-Z SOURCE:
harmonic HI-Z 3-PHASE EVENT
signals)
EVEN, ODD AND THRESHOLD:
FROM IG
NON HARMONICS RUN SOURCE IG-FFT
IA RMS IA > Threshold
IB RMS IB > Threshold AND
IC RMS IC > Threshold
IG RMS OR
VA RMS SETTING
VB RMS HI-Z PHASE RATE OF
VC RMS CHANGE:
HI-Z NEUTRAL RATE OF
CHANGE:
RUN
IA > Threshold
IB > Threshold
OR
IC > Threshold
IG > Threshold

SETTING
HI-Z PHASE OC MIN FLEXLOGIC OPERANDS
PICKUP: HI-Z IOC-A

HI-Z NEUTRAL OC MIN HI-Z IOC-B


PICKUP: HI-Z IOC-C
RUN HI-Z IOC-N

5
IA > PKP
IB > PKP
OR
IC > PKP LATCH O/C
AND VALUES
IG > PKP

SETTING
HI-Z LOSS OF LOAD OR
LATCH LOL
THRESHOLD: AND VALUES
RUN
OR
IA% > Threshold
FLEXLOGIC OPERAND
IB% > Threshold
AND HI-Z LOSS OF LOAD-A
IC% > Threshold

RUN
IA < 0.02 pu
IB < 0.02 pu OR
FLEXLOGIC OPERAND
IC < 0.02 pu HI-Z LOSS OF LOAD-B
AND

LOAD ANALYSIS ALG.


RUN
EVEN HARM RESTR. ALG. LOAD ANALYSIS IN
SETTING NORMAL STATE
HI-Z EVEN HARMONIC FLEXLOGIC OPERAND
RESTRAINT:
AND HI-Z LOSS OF LOAD-C
RUN
IA EVEN % > PKP > 0
IB EVEN % > PKP > 0 OR 0
1 sec
IC EVEN % > PKP > 0

VOLTAGE SUPERVISION ALG.


SETTING
827838A9.CDR
HI-Z VOLTAGE SUPV
THRESHOLD: SETTING
OR
RUN
HI-Z VOLTAGE SUPV
VA % > PKP DELAY:
VB % > PKP
0
VC % > PKP

0
RUN OR
|VA| < 0.8 pu
|VB| < 0.8 pu 0
OR
|VC| < 0.8 pu

5.10.0.3 Breaker arcing current


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  BREAKER 1(4) ARCING CURRENT
 BREAKER 1 BKR 1 ARC AMP Range: Disabled, Enabled
 ARCING CURRENT  FUNCTION: Disabled

BKR 1 ARC AMP Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

5-368 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

BKR 1 ARC AMP INT-A: Range: FlexLogic operand


 Off

BKR 1 ARC AMP INT-C: Range: FlexLogic operand
 Off

BKR 1 ARC AMP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

BKR 1 ARC AMP LIMIT: Range: 0 to 50000 kA2-cycle in steps of 1


 1000 kA2-cyc

BKR 1 INTERRUPTION Range: 0.0 to 100.0 kA in steps of 0.1


 RATING: 31.5 kA

BKR 1 CLR ARC AMPS: Range: FlexLogic operand


 Off

BKR 1 ARC AMP BLOCK: Range: FlexLogic operand


 Off

BKR 1 ARC AMP Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

BKR 1 ARC AMP Range: Disabled, Enabled


 EVENTS: Disabled

There is one breaker arcing current element available per CT bank, with a minimum of two elements.
This element calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the
current squared passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals
for each phase and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay 5
can set an output operand to “1.” The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays, and the breaker mechanism. For maximum measurement accuracy, measure the interval between change-of-state
of the operand (from 0 to 1) and contact separation for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function.
Correction is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES  RECORDS  MAINTENANCE 
BREAKER 1(4) menus.
BKR 1 ARC AMP INT-A(C) — Select the same output operands that are configured to operate the output relays used to trip the
breaker. In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A,
B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations
for the poles that are actually tripped.
BKR 1 ARC AMP DELAY — This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
BKR 1 ARC AMP LIMIT — Selects the threshold value above which the output operand is set.
BKR 1 CLR ARC AMPS — Selects a FlexLogic Operand to clear the accumulated I2t values (kA2-cycle), reset fault duration
items (breaker operating time), clear ARCING AMPS (kA2-cycle) and AMP MAX (kA) values of the last event.
BKR 1 INTERUPTION RATING — This setting specifies the maximum symmetrical interruption rating of the circuit breaker.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-369


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Figure 5-194: Arcing current measurement


Breaker
Contacts Arc
Initiate Part Extinguished

Total Area =
Breaker
Arcing
Current
(kA cycle)

Programmable
Start Delay 100 ms
Start Stop
Integration Integration
827792A1.CDR

5-370 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


SETTING

BREAKER 1 ARCING SETTING


AMP FUNCTION :
AND BREAKER 1 ARCING
Enabled = 1
AMP DELAY :
100ms
SETTING OR 0
AND 0
CHAPTER 5: SETTINGS

BREAKER 1 ARCING AND


AMP BLOCK :
Off = 0

SETTING

AND BREAKER 1 ARCING


SETTINGS
AMP DELAY :
100ms
BREAKER 1 ARCING
AMP INIT - A: OR 0
0
Off = 0 AND

BREAKER 1 ARCING
AMP INIT - B:
Off = 0
BREAKER 1 ARCING SETTING ACTUAL VALUES
AMP INIT - C :
AND BREAKER 1 ARCING BKR 1 AMP MAX FA
Off = 0 AMP DELAY: BKR 1 AMP MAX FB
100 ms

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


BKR 1 AMP MAX FC
OR 0 CALCULATE CALCULATE
0 SETTING
AND OR RUN Interruption Rating
Select greatest FLEXLOGIC OPERANDS
value RUN
Imax > Interruption Rating BKR ARC 1 MAX OP
BKR ARC 1 MAX DPO
Calculate Imax

RUN

SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE : RUN Accumulator BREAKER 1 ARCING
2
IA IA - Cycle AMP LIMIT : FLEXLOGIC OPERANDS
Select
2 2
Figure 5-195: Breaker arcing current logic

IB Integrate IB - Cycle Highest KA * Cycle Limit BKR 1 ARC OP


2 Value
IC IC - Cycle BKR 1 ARC DPO
RUN
COMMAND

CLEAR BREAKER 1 Integrate ACTUAL VALUE


ARCING AMPS :
Set All To Zero BKR 1 ACC ARCING AMP FA
NO = 0
BKR 1 ACC ARCING AMP FB
YES = 1
OR BKR 1 ACC ARCING AMP FC
SETTING BKR 1 OPERATING TIME FA
BKR 1 CLR ARC AMPS BKR 1 OPERATING TIME FB
Off=0
BKR 1 OPERATING TIME FC
BKR 1 OPERATING TIME .

ACTUAL VALUES
BKR 1 ARCING AMP FA
BKR 1 ARCING AMP FB
BKR 1 ARCING AMP FC
827071A5CDR

5-371
MONITORING ELEMENTS

5
MONITORING ELEMENTS CHAPTER 5: SETTINGS

5.10.0.4 Breaker flashover


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  BREAKER FLASHOVER 1(2)
 BREAKER BRK 1 FLSHOVR Range: Disabled, Enabled
 FLASHOVER 1  FUNCTION: Disabled

BRK 1 FLSHOVR SIDE 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC: SRC 1

BRK 1 FLSHOVR SIDE 2 Range: None, SRC 1, SRC 2, SRC 3, SRC 4


 SRC: None

BRK 1 STATUS CLSD A: Range: FlexLogic operand


 Off

BRK 1 STATUS CLSD C: Range: FlexLogic operand
 Off

BRK 1 FLSHOVR V PKP: Range: 0.004 to 1.500 pu in steps of 0.001


 0.850 pu

BRK 1 FLSHOVR DIFF V Range: 0 to 100000 V in steps of 1


 PKP: 1000 V

BRK 1 FLSHOVR AMP Range: 0.020 to 1.500 pu in steps of 0.001


 PKP: 0.600 pu

BRK 1 FLSHOVR PKP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.100 s

5  BRK 1 FLSHOVR SPV A:


Off
Range: FlexLogic operand


BRK 1 FLSHOVR SPV C: Range: FlexLogic operand
 Off

BRK 1 FLSHOVR BLOCK: Range: FlexLogic operand


 Off

BRK 1 FLSHOVR Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

BRK 1 FLSHOVR Range: Disabled, Enabled


 EVENTS: Disabled

The detection of the breaker flashover is based on the following conditions:


• Breaker open,
• When phase voltage measured from either side of the breaker is greater than the setting,
• Measured current through the breaker is greater than the pickup setting, and
• Voltage difference across the breaker drops below the pickup setting (only applicable to six VTs application)
Furthermore, the scheme is applicable for cases where one or two sets of three-phase voltages are available across the
breaker, as follows:
• One set of three-phase voltages is available across the breaker (three VTs application)
• Two sets of three-phase voltages are available across the breaker (six VTs application)

Three VT breaker flashover application


When only one set of VTs is available across the breaker, set the BRK 1 FLSHOVR SIDE 2 SRC setting to “None.”

5-372 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

Voltages must be present prior to flashover conditions. If the three VTs are placed after the breaker on the line (or
feeder), and the downstream breaker is open, the measured voltage is zero and the flashover element is not
initiated.
The flashover detection resets if the current drops below BRK 1 FLSHOVR AMP PKP, the breaker closes, or the FlexLogic
operand selected by BRK 1 FLSHOVR SPV A changes to high. It is recommended to use the supervision BRK 1 FLSHOVR SPV A
setting, and select a trip operand that does not allow the flashover element to pick up prior to the trip.
The flashover detection can be used for external alarm, re-tripping the breaker, or energizing the lockout relay.
Consider the following configuration:

Bus
CTs Breaker
Line/Feeder

Bus VTs
842746A1.CDR

The source 1 (SRC1) phase currents are feeder CTs and phase voltages are bus VTs, and Contact Input 1 is set as Breaker
52a contact. The conditions prior to flashover detection are:
• 52a status = 0
• VAg is greater than the BRK 1 FLSHOVR V PKP setting 5
• IA is below BRK 1 FLSHOVR AMP PKP (ideally, IA = 0)
The conditions at flashover detection are:
• 52a status = 0
• VAg is greater or lesser than the BRK 1 FLSHOVR V PKP setting
• IA is greater than the BRK 1 FLSHOVR AMP PKP setting

Six VT breaker flashover application


In a six-VT application, the VTs located on both sides of a breaker are available. When the breaker is open, the voltage
difference across the breaker is the rated voltage if the line is not energized from the remote end, or it can be two times the
rated voltage at the time of synchronization if the line is energized from the remote. At the occurrence of breaker flashover,
the voltage difference across breaker drops and current greater than BRK 1 FLSHOVR AMP PKP starts flowing through the
breaker. These conditions are also true for a normal closed operation of a breaker where the voltage difference across
breaker is practically zero and load current flows through the breaker. To distinguish between breaker flashover and
normal closed operation of breaker, the Breaker Status is utilized.
In a six-VT configuration, if the voltages from VTs located on one of the sides of breaker disappear due to VT fuse failure or
other reason, a three-VT configuration can provide the breaker flashover detection. If however, the blocking of breaker
flashover detection is wanted under voltage loss on one side condition, then it can be done by applying the appropriate
FlexLogic operand to the BRK FLSHOVR BLOCK setting.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-373


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Consider the following configuration:

Bus
CTs Breaker
Line/Feeder

VTs

VTs
842745A1.CDR

The source 1 (SRC1) phase currents are CTs and phase voltages are bus VTs. The source 2 (SRC2) phase voltages are line
VTs. Contact input 1 is set as the breaker 52a contact (optional).
The conditions prior to flashover detection are:
• 52a status = 0
• VAg or Vag greater than the BRK 1 FLSHOVR V PKP setting
• IA is below BRK 1 FLSHOVR AMP PKP (ideally, IA = 0)
• ΔVA is greater than the BRK 1 FLSHOVR DIFF V PKP setting
The conditions at flashover detection are:
• 52a status = 0
• VAg or Vag greater or lesser than the BRK 1 FLSHOVR V PKP setting
5 • IA is greater than the BRK 1 FLSHOVR AMP PKP setting
• ΔVA is less than the BRK 1 FLSHOVR DIFF V PKP setting

The element operates only when phase-to-ground voltages are connected to relay terminals. The flashover
element does not operate if delta voltages are applied.

Settings
BRK 1 FLSHOVR SIDE 1 SRC — This setting specifies a signal source used to provide three-phase voltages and three-phase
currents from one side of the current breaker. The source selected as a setting and must be configured with breaker phase
voltages and currents, even if only three VTs are available across the breaker.
BRK 1 FLSHOVR SIDE 2 SRC — This setting specifies a signal source used to provide another set of three phase voltages
whenever six VTs are available across the breaker. For a three-VT application, set this setting to "None."
BRK 1 STATUS CLSD A to BRK 1 STATUS CLSD C — These settings specify FlexLogic operands to indicate the closed status of the
breaker. A separate FlexLogic operand can be selected to detect individual breaker pole status and provide flashover
detection. The recommended setting is 52a breaker contact or another operand defining the breaker poles closed status.

Leaving this setting off, meaning not configuring any FlexLogic to indicated Closed Breaker leads to maloperation
of the element.

BRK 1 FLSHOVR V PKP — This setting specifies a pickup level for the phase voltages from one or both sides of the breaker. If
six VTs are available, opening the breaker leads to two possible combinations – live voltages from only one side of the
breaker, or live voltages from both sides of the breaker. The detection of voltage above the selected value on either side of
the breaker sets the scheme ready for flashover detection. Set BRK FLSHOVR V PKP to 85 to 90% of the nominal voltage.
BRK 1 FLSHOVR DIFF V PKP — This setting specifies a pickup level for the phase voltage difference when two VTs per phase
are available across the breaker. Set this setting to be lower than the monitored voltage difference that is observed when
closed or opened breaker resistors are left in service. The setting is selected as primary volts difference between the
sources.

5-374 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

BRK 1 FLSHOVR AMP PKP — This setting specifies the normal load current which can flow through the breaker. Depending on
the flashover protection application, the flashover current can vary from levels of the charging current when the line is not
loaded to well above the maximum line (feeder) load (line/feeder connected to load).
BRK 1 FLSHOVR SPV A to BRK 1 FLSHOVR SPV C — These settings specify FlexLogic operands (per breaker pole) that supervise
the operation of the element per phase. Supervision can be provided by operation of other protection elements, breaker
failure, and close and trip commands. A six-cycle time delay applies after the selected FlexLogic operand resets.
BRK FLSHOVR PKP DELAY — This setting specifies the time delay to operate after a pickup condition is detected. Do not set it
too long else the flashover current can disappear before its detection.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-375


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Figure 5-196: Breaker flashover logic

5-376 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

5.10.0.5 Breaker restrike


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  BREAKER RESTRIKE 1(3)
 BREAKER RESTRIKE 1 BREAKER RESTRIKE 1 Range: Disabled, Enabled
  FUNCTION: Disabled

BRK RESTRIKE 1 Range: FlexLogic operand


 BLOCK: Off

BREAKER RESTRIKE 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

BREAKER RESTRIKE 1 Range: 0.10 to 2.00 pu in steps of 0.01


 PICKUP: 0.50 pu

BREAKER RESTRIKE 1 Range: 0.000 to 65.535 s in steps of 0.001


 RST DELAY: 0.100 s

BREAKER RESTRIKE 1 Range: Disabled, Enabled


 HF DETECT: Enabled

BRK RSTR 1 BRK OPEN: Range: FlexLogic operand


 Off

BRK RSTR 1 OPEN CMD: Range: FlexLogic operand


 Off

BRK RSTR 1 CLS CMD: Range: FlexLogic operand


 Off

BREAKER RESTRIKE 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

 BREAKER RESTRIKE 1 Range: Disabled, Enabled


5
EVENTS: Disabled

One breaker restrike element is provided for each DSP in the F60.
According to IEEE standard C37.100 entitled IEEE Standard Definitions for Power Switchgear, restrike is defined as “a
resumption of current between the contacts of a switching device during an opening operation after an interval of zero
current of ¼ cycle at normal frequency or longer.”
Figure 5-197: Typical restrike waveform and detection flag

10
8
6
4
current (amps)

2
0.01 0.03
0 time (ms)
0.02 0.05
–2
–4
–6
–8
OPERATE
–10
834764A1.CDR

The breaker restrike algorithm responds to a successful interruption of the phase current following a declaration of
capacitor bank offline as per the breaker pole indication. If a high-frequency or system frequency current with a
magnitude greater than the threshold is resumed at least ¼ of a cycle later than the phase current interruption, then a

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-377


MONITORING ELEMENTS CHAPTER 5: SETTINGS

breaker restrike condition is declared in the corresponding phase and the BRK RESTRIKE 1 OP operand asserts for a
short period of time. The user can add counters and other logic to facilitate the decision making process as to the
appropriate actions upon detecting a single restrike or a series of consecutive restrikes.
A restrike event (FlexLogic operand) is declared if all of the following hold:
• The current is initially interrupted
• The breaker status is open
• An elevated high frequency current condition occurs (if the BREAKER RESTRIKE 1 HF DETECT setting is Enabled, otherwise
the condition is bypassed), and
• The current subsequently drops out again
The algorithm is illustrated in the following state machine diagram.
Figure 5-198: Algorithm illustration of state machine to detect restrike

Breaker open
command or breaker
open state
Capacitor bank
offline
Breaker
close

Current
Capacitor bank
interruption
Breaker online
(overcurrent)
close

5 High-frequency
elevated current Breaker close
(if enabled)

Current
interruption
(overcurrent)

Restrike detected:
OP state asserted
834768A2.CDR

In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes is picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
BREAKER RESTRIKE 1 FUNCTION — Enables and disables operation of the breaker restrike detection element.
BRK RESTRIKE 1 BLOCK — Blocks operation of the breaker restrike detection element.
BREAKER RESTRIKE 1 SOURCE — Selects the source of the current for this element. This source must have a valid CT bank
assigned.
BREAKER RESTRIKE 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of CT nominal
current.
BREAKER RESTRIKE 1 RST DELAY — Specifies the reset delay for this element. When set to “0 ms,” then FlexLogic operand is
picked up for only 1/8th of the power cycle.

5-378 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

BREAKER RESTRIKE 1 HF DETECT — Enables/disables high-frequency (HF) pattern detection when breaker restrike occurs.
High-frequency pattern is typical for capacitor bank, cables, and long transmission lines applications.
BRK RSTR 1 BRK OPEN — Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic “1” when
the breaker is open. It is important to assign either 52 contact with this setting or breaker close command with BRK RSTR 1
CLS CMD setting to give clear indication to the relay about breaker status.
BRK RSTR 1 OPEN CMD — Assigns a FlexLogic operand indicating a breaker open command. It must be logic “1” when the
breaker is opened, either manually or from protection logic.
BRK RSTR 1 CLS CMD — Assigns a FlexLogic operand indicating a breaker close command. It must be logic “1” when the
breaker is closed.
Figure 5-199: Breaker restrike logic
6(77,1*
%5($.(55(675,.(
)81&7,21
(QDEOHG

6(77,1* $1' 6(77,1*


%.55675%/. %5($.(55(675,.(3,&.83
2II %5($.(55(675,.( 6(77,1*
+)'(7(&7 %5($.(55(675,.(
581 5(6(7'(/$<
6(77,1* 
%5($.(55(675,.( 581 5HVWULNHGHWHFWLRQORJLF
6285&( $50(' 7567
&XUUHQWLQWHUUXSWLRQ
,$ GHWHFWLRQORJLF 
)/(;/2*,&23(5$1'6
,%
,PDJSX 7567 %.55(675,.(23$
,&
IRUW!óF\FOH  %.55(675,.(23%
%.55(675,.(23&
6(77,1* 5(6(7 7567
%.55675%.523(1
2II
)/(;/2*,&23(5$1'

6(77,1*
%.5567523(1&0'
2II
25
25 %.55(675,.(23

5
$1'

6(77,1*
%.55675&/6&0'
2II
$&'5

5.10.0.6 CT failure detector


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  CT FAILURE DETECTOR 1(4)
 CT FAILURE CT FAIL 1 FUNCTION: Range: Disabled, Enabled
 DETECTOR 1  Disabled

CT FAIL 1 BLOCK: Range: FlexLogic operand


 Off

CT FAIL 1 3I0 INP 1: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

CT FAIL 1 3I0 INP 1 Range: 0.1 to 2.0 pu in steps of 0.1


 PKP: 0.2 pu

CT FAIL 1 3I0 INP 2: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 2

CT FAIL 1 3I0 INP 2 Range: 0.1 to 2.0 pu in steps of 0.1


 PKP: 0.2 pu

CT FAIL 1 3V0 INPUT: Range: SRC 1, SRC 2, SRC 3, SRC 4


 SRC 1

CT FAIL 1 3V0 INPUT Range: 0.04 to 2.00 pu in steps of 0.01


 PKP: 0.20 pu

CT FAIL 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 1.000 s

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-379


MONITORING ELEMENTS CHAPTER 5: SETTINGS

CT FAIL 1 TARGET: Range: Self-reset, Latched, Disabled


 Self-reset

CT FAIL 1 EVENTS: Range: Disabled, Enabled


 Disabled

The CT failure function detects problems with system current transformers used to supply current to the relay. This logic
detects the presence of a zero-sequence current at the supervised source of current without a simultaneous zero-
sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see later) is based on the presence of the zero-sequence current in the supervised CT source and the
absence of one of three or all of the three following conditions:
• Zero-sequence current at different source current (can be different set of CTs or different CT core of the same CT)
• Zero-sequence voltage at the assigned source
• Appropriate protection element or remote signal
Settings are described as follows.
CT FAIL 1 FUNCTION — Enables or disables operation of the CT failure element.
CT FAIL 1 BLOCK — Selects a FlexLogic operand to block operation of the element during some condition (for example, an
open pole in process of the single pole tripping-reclosing). Local signals or remote signals representing operation of some
remote current protection elements via communication channels can also be chosen.
CT FAIL 1 3I0 INPUT 1 — Selects the current source for input 1. The most critical protection element should also be assigned
to the same source.
CT FAIL 1 3I0 INPUT 1 PICKUP — Selects the 3I_0 pickup value for input 1 (the main supervised CT source).
CT FAIL 1 3I0 INPUT 2 — Selects the current source for input 2. Input 2 should use a different set of CTs or a different CT core
5 of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
CT FAIL 1 3I0 INPUT 2 PICKUP — Selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
CT FAIL 1 3V0 INPUT — Selects the voltage source.
CT FAIL 1 3V0 INPUT PICKUP — Specifies the pickup value for the 3V_0 source.
CT FAIL 1 PICKUP DELAY — Specifies the pickup delay of the CT failure element.

5-380 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

Figure 5-200: CT failure detector logic

6(77,1*

&7)$,/)81&7,21

(QDEOHG 

6(77,1*

&7)$,/%/2&.

2II  6(77,1*

6(77,1* 6(77,1* &7)$,/3,&.83'(/$<


)/(;/2*,&23(5$1'6
&7)$,/,2,1387 &7)$,/,2,13873.3 $1'  &7)$,/23
65& 581 ,2!3,&.83
&7)$,/3.3
6(77,1* 6(77,1*

&7)$,/,2,1387 &7)$,/,2,13873.3

65& 581 ,2!3,&.83

6(77,1* 6(77,1*
25
&7)$,/92,1387 &7)$,/92,1387

65& 581 92!3,&.83 $&'5

5.10.0.7 Incipient fault detector 5


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  INCIPIENT FAULT 1(2)
 INCIPIENT FAULT 1 INCIPIENT FAULT 1 Range: Disabled, Enabled
  FUNCTION: Disabled

INCIPNT FLT 1 BLOCK: Range: FlexLogic operand


 Off

INCIPIENT FAULT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

INCIPIENT FAULT 1 Range: 0.10 to 10.00 pu in steps of 0.01


 PICKUP: 0.50 pu

INCIPNT FLT 1 MODE: Range: Number of counts, Counts per window


 Number of counts

INCIPIENT FLT 1 TRIP Range: 1 to 10 in steps of 1


 COUNTS NUMBER: 2

INCIPNT FLT 1 DETECT Range: 0.00 to 1000.00 s in steps of 0.01


 WINDOW: 10.00 s

INCIPIENT FAULT 1 Range: 0.000 to 65.535 s in steps of 0.001


 RESET DELAY: 0.100 s

INCIPIENT FAULT 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

INCIPIENT FAULT 1 Range: Disabled, Enabled


 EVENTS: Disabled

There are two incipient cable fault detection elements in the relay.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-381


MONITORING ELEMENTS CHAPTER 5: SETTINGS

Before a permanent cable fault occurs, there are usually signs of degrading insulation manifesting itself as a short, mostly
half-cycle spikes asserting at the phase voltage peak. Due to shortness of such spikes, they are not usually detected by the
instantaneous protection of the feeder, which operates on the RMS or fundamental component of the phase current with a
relatively high pickup.
The number of detected incipient faults in each phase is counted and available in the ACTUAL VALUES  STATUS 
INCIPIENT FAULT menus. The counters can be reset with the COMMANDS  CLEAR RECORDS  CLEAR INCIPENT FAULT
COUNTERS command.

Changes to any of the incipient cable fault detector settings resets of the number of the incipient faults detected to
zero.
To provide a clear timing indication when the incipient fault occurred, the incipient fault event is time-stamped with
the time the fault actually occurred. However, the FlexLogic operand is asserted four cycles later, when the incipient
fault pattern is confirmed and therefore detected.
The figure illustrates a recorded field case of an incipient phase B fault. The top portion of the figure shows the raw A, B,
and C currents. The bottom portion shows the neutral current (blue) and reveals the fault period from under the load and
the superimposed phase B current (red). The superimposed current shows two fault current blips as the data slides through
the two-cycle memory window. During the actual fault, the neutral current and the superimposed phase B currents closely
correspond, confirming the incipient fault hypothesis and identifying the affected phase.
Figure 5-201: Illustration of the incipient fault detector algorithm

Incipient phase B fault PHASE CURRENTS


2.0
Current (amps)

5 1.0

Phase C
0 Phase A
Phase B
–0.5
0.62 0.64 0.66 0.68 0.70 0.72 0.74

CALCULATED NEUTRAL AND


2.0 IN (neutral current) SUPERIMPOSED PHASE B CURRENT
Current (amps)

1.0

–1.0
IFB
–2.0
0.62 0.64 0.66 0.68 0.7 0.72 0.74
832774A1.CDR

The following settings are available for each incipient cable fault detector.
INCIPIENT FAULT 1 FUNCTION — This setting enables and disables operation of the incipient fault detection element.
INCIPNT FLT 1 BLOCK — Blocks operation of the incipient cable fault detector element. Assertion of the FlexLogic operand
assigned to this setting blocks operation.
INCIPIENT FAULT 1 SOURCE — Selects a current source for the incipient cable fault detector element. This source must be
assigned a valid CT bank.
INCIPIENT FAULT 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of the CT nominal
current.

5-382 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

INCIPNT FLT 1 MODE — There are two modes of operation available for the incipient cable fault detector element. In the
“Number of counts” mode, a trip is initiated only after the selected number of faults is detected. In the “Counts per window”
mode, a trip is initiated only after the selected number of faults is detected within the time specified by the INCIPNT FLT 1
DETECT WINDOW setting.
INCIPIENT FLT 1 TRIP COUNTS NUMBER — Selects the number of faults required to initiate a trip.
INCIPNT FLT 1 DETECT WINDOW — Specifies a time window for “Counts per window” mode of operation.
INCIPIENT FAULT 1 RESET DELAY — Specifies a reset time for the output after the trip is initiated.

Figure 5-202: Incipient cable fault detector logic


SETTING
INCIPIENT FAULT 1 FUNCTION
= Enabled SETTINGS
= Disabled INCIPNT FLT 1 MODE
INCIPIENT FLT 1 TRIP SETTINGS
AND COUNTS NUMBER
SETTING INCIPIENT FAULT 1
SETTING INCIPNT FLT 1 DETECT RESET DELAY
INCIPIENT FAULT 1 BLOCK
INCIPIENT FAULT 1 WINDOW FLEXLOGIC OPERANDS
= OFF 0
PICKUP RUN INCIPNT FLT 1 OP A
RUN Detection logic TRST INCIPNT FLT 1 OP B
SETTING
0 INCIPNT FLT 1 OP C
INCIPIENT FAULT 1 SOURCE
INCIPNT FLT 1 OP
= IA TWINDOW TRST OR

= IB 0
= IC
Imag – Imag
´ > PICKUP TRST
= IN FLEXLOGIC OPERANDS
where Imag
´ is 2 cycles old
INCIPNT FLT 1 PKP A
INCIPNT FLT 1 PKP B
INCIPNT FLT 1 PKP C
OR INCIPNT FLT 1 PKP

ACTUAL VALUES
INCIPIENT FAULT 1 PH A

5
FAULTS
INCIPIENT FAULT 1 PH B
FAULTS
COMMAND INCIPIENT FAULT 1 PH C
CLEAR INCIPIENT FAULT FAULTS
COUNTERS
RESET
= Yes
832028A1.CDR

5.10.0.8 VT fuse failure


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  VT FUSE FAILURE 1(4)
 VT FUSE FAILURE 1 VT FUSE FAILURE 1 Range: Disabled, Enabled
  FUNCTION: Disabled

VT FUSE FAILURE 1 Range: 0.000 to 65.535 s in steps of 0.001


 ALARM DELAY: 1.000 s

NEUTRAL WIRE OPEN 1 Range: Disabled, Enabled


 DETECTION: Disabled

NEUTRAL WIRE OPEN 1 Range: 0.004 to 3.000 pu in steps of 0.001


 3 HARM PKP: 0.100 pu

Every signal source includes a fuse failure scheme. A signal source must have a three-phase VT bank and a three-phase CT
bank assigned to it, in order for the fuse failure scheme to operate.
The VT fuse failure detector is used to raise an alarm and/or block elements that operate incorrectly for a full or partial loss
of AC potential caused by one or more blown fuses. Some elements that can be blocked (via the BLOCK input) are distance,
voltage restrained overcurrent, and directional current.
There are two classes of fuse failure that occur:
• Class A — Loss of one or two phases
• Class B — Loss of all three phases
Different means of detection are required for each class. An indication of class A failures is a significant level of negative-
sequence voltage, whereas an indication of class B failures is when positive sequence current is present and there is an
insignificant amount of positive sequence voltage. Also, a rapid decrease in the phase voltages magnitude from a healthy

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-383


MONITORING ELEMENTS CHAPTER 5: SETTINGS

voltage level without disturbance in current can indicate VT fuse fail conditions. These noted indications of fuse failure can
also be present when faults are present on the system, so a means of detecting faults and inhibiting fuse failure
declarations during these events is provided.
Once the fuse failure condition is declared, it is sealed-in until the cause that generated it disappears.
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized;
positive-sequence voltage and current are both below threshold levels.
VT FUSE FAILURE 1 FUNCTION — Enables and disables the fuse failure feature for Source 1 VT Fuse Fail.
NEUTRAL WIRE OPEN 1 DETECTION — Enables and disables the VT neutral wire open detection function. When the VT is
connected in Delta, do not enable this function because there is no neutral wire for Delta connected VT.
NEUTRAL WIRE OPEN 1 3 HRAM PKP — Specifies the pickup level of 3rd harmonic of 3V0 signal for the NEUTRAL WIRE OPEN
DETECTION logic to pick up.
Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/ 3 in case
of DELTA VTs. The setting is found under SETTINGS 
ÖØ SYSTEM SETUP  Ö AC INPUTS 
ÖØ VOLTAGE BANK  Ö PHASE VT SECONDARY.

Figure 5-203: VT fuse fail logic


SE TTIN G V A’, V B’ a nd V C’ a re the
Fu ncti on vo ltag e ma gn itud e of on e OR
En ab led = 1 cy cle be fore
AND
COMP ARAT ORS FAULT
R un
|V A’|-|VA| > 0.2 pu
& |V A’| > 0 .8 pu
R un
|V B’|-|VB | > 0.2 pu OR
SO URCE 1 & |V B’| > 0 .8 pu SETTING
VA R un V T FUS E F AILUR E 1
|V C’|-|VC| > 0.2 pu ALAR M DE LAY
VB & |V C’| > 0 .8 pu FLE XLO GIC O PE RAN D
tPK P
VC R un SR C1 V T FF ALARM
0

5
V _2 V _2 > 0.1 p u OR

V _1 R un
V _1 < 0.0 5 pu
I_1
AND FUS E
R un
FAIL
I_1 > 0.0 75 pu
TIMER
R un 2 c ycles SET
TIME R AND OR
V _1 < 0.8 0 pu 0
2 cy cles
FLE XLO GIC O PE RAN DS
R un AND
I_1 < 0.0 5 pu La tch SR C1 V T FUSE FAIL OP
20 cy cle s
SR C1 V T FUSE FAIL DPO
FLE XLO GIC O PE RAN DS
SR C1 5 0DD OP
OP EN POLE OP
Th e O PEN PO LE O P op eran d ap pl ies
to th e C60 , C9 5, D60 , L60, L9 0, an d N60 AND
TIMER
OR 30 cyc les RESET
AND 0
R eset-d omi na nt

FLE XLO GIC O PE RAN D


AND SR C1 V T FUSE FAIL VO L LOS S

TIME R
SE TTIN G 5 cy cles
AND
3 HARM P KP
0
AND R un FLE XLO GIC O PE RAN D
SE TTIN G 3V _0 3 rd Har m >settin g OR SR C1 V T NEU WIR E O PEN
TIME R
Ne utra l Wi re Ope n Detect
0
En ab led = 1
AND 20 cy cle s

SO URCE 1 FLE X-ANALO G


3V _0 (3 rd Ha rmo ni c) SR C1 3 V0 3 nd H arm on ic

859808 A1.vsd

5-384 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

5.10.0.9 Thermal overload protection (ANSI 49)


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  THERMAL OVERLOAD PROTECTION  THERMAL
PROTECTION 1(2)
 THERMAL THERMAL PROTECTION 1 Range: Disabled, Enabled
 PROTECTION 1  FUNCTION: Disabled

THERMAL PROTECTION 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC1

THERMAL PROTECTION 1 Range: 3-Phase, 1-Phase


 MODE: 3-PHASE

THERMAL PROTECTION 1 Range: 0.20 to 3.00 pu in steps of 0.01


 BASE CURR: 0.80 pu

THERMAL PROTECTION 1 Range: 0.20 to 4.00 in steps of 0.05


 k FACTOR: 1.10

THERMAL PROTECTION 1 Range: 0.2 to 1.0 pu in steps of 0.1


 ALARM LEVEL: 0.5 pu

THERM PROT 1 TRIP Range: 0.0 to 999.0 minutes in steps of 0.1


 TIME CONST: 45.0 min

THERM PROT 1 RESET Range: 0.0 to 999.0 minutes in steps of 0.1


 TIME CONST: 45.0 min

THERM PROT 1 MINIM Range: 0.0 to 999.0 minutes in steps of 0.1


 RESET TIME: 20.0 min

THERM PROT 1 RESET: Range: FlexLogic operand


 Off 5
THERM PROT 1 BLOCK: Range: FlexLogic operand
 Off

THERMAL PROTECTION 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

THERMAL PROTECTION 1 Range: Disabled, Enabled


 EVENTS: Disabled

The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect
different elements of the power system.
The cold curve characteristic is applied when the estimated Ip current is less than 10% of the base current. If Ip current is
greater or equal than 10% than the base current, then the hot curve characteristic is applied. The Ip current is estimated
with a fixed time constant for both cooling and heating that reaches to the final value in two seconds on a step change
(either step up or step down) signal.
The IEC255-8 cold curve is defined as follows:

§ 2 ·
I
t op = W op u ln ¨ ---------------------------
2

2 Eq. 5-37
© I – k u IB ¹

The IEC255-8 hot curve is defined as follows:

2 2
§ I – Ip ·
t op = W op u ln ¨ ---------------------------
-¸ Eq. 5-38
© I 2 – k u I B 2¹

where

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-385


MONITORING ELEMENTS CHAPTER 5: SETTINGS

top = time to operate


τop = thermal protection trip time constant
I = measured overload RMS current
Ip = measured load RMS current before overload occurs
k = IEC 255-8 k-factor applied to IB, defining maximum permissible current above nominal current. A typical value range
for this k factor is 1.0 to 1.5 per the standard.
IB = protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x IB) is limited to 8, even when
realistically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
2
§ k u IB ·
t rst = W rst u ln ¨ ------------------------------
-¸ + T min
2
© I – k u IB ¹ 2 Eq. 5-39

where
τrst = thermal protection trip time constant
Tmin = a minimum reset time setting

5-386 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

Figure 5-204: IEC 255-8 sample operate and reset curves


100

Tmin = 10

10

τrst = 30
τop = 30
t (min)

0.1
5

0.01
0.1 1 10 100
I / Ipkp
827724A1.CDR

The thermal overload protection element estimates accumulated thermal energy E using the following equations
calculated each power cycle. When current is greater than the pickup level, In > k × IB, element starts increasing the
thermal energy:

't
E n = E n – 1 + --------------
t op In Eq. 5-40

When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:

't
E n = E n – 1 – -------------- Eq. 5-41
t rst In

where
∆t is the power cycle duration
n is the power cycle index
top(In) is the trip time calculated at index n as per the IEC255-8 cold curve or hot curve equations
trst(In) is the reset time calculated at index n as per the reset time equation

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-387


MONITORING ELEMENTS CHAPTER 5: SETTINGS

In is the measured overload RMS current at index n


En is the accumulated energy at index n
En – 1 is the accumulated energy at index n – 1
The thermal overload protection element removes the THERMAL PROT 1 OP and THERMAL PROT 1 ALARM output
operand when E < 0.05. In case of emergency, the thermal memory and as a result THERMAL PROT 1 OP and
THERMAL PROT 1 ALARM output operands can be reset using THERM PROT 1 RESET setting.
The calculations are performed per the selected mode (three-phase or single-phase). For three-phase, calculations are
performed per phase. If the accumulated energy reaches value 1 pu in any phase, the thermal overload protection
element operates and only resets when energy is less than 0.05 in all three phases. The THERMAL PROT 1 ALARM
operand asserts if accumulated energy reaches the selected THERMAL PROTECTION 1 ALARM LEVEL setting in any phase an
resets only when energy is below 0.05 in all three phases.
In single-phase mode, the thermal energy of only the ground channel IG of the assigned source is accumulated.

Table 5-50: Typical time constants


Protected equipment Time constant Minimum reset time
Capacitor bank 10 minutes 30 minutes
Overhead line 10 minutes 20 minutes
Air-core reactor 40 minutes 30 minutes
Busbar 60 minutes 20 minutes
Underground cable 20 to 60 minutes 60 minutes

The figure shows the logic for the thermal overload protection element.
5 Figure 5-205: Thermal overload protection logic
SETTINGS

THERMAL PROTECTION 1
FUNCTION:
Enabled = 1
FLEXLOGIC OPERAND
AND

THERM PROT 1 BLOCK:


Off = 0 THERMAL PROT 1 PKP

SETTINGS

THERMAL PROTECTION 1
MODE: SETTINGS
AND

THERMAL PROTECTION 1 THERMAL PROTECTION 1


SETTINGS BASE CURR: ALARM LEVEL:
S FLEXLOGIC OPERAND

THERMAL PROTECTION 1 THERMAL PROTECTION 1 THERM PROT 1 TRIP LATCH THERMAL PROT 1 ALARM
SOURCE: k FACTOR: TIME CONST:
IA RMS IA > k * Ib R
RUN
IB RMS IB > k * Ib E =>ALRM Reset dominant
OR

IC RMS IC > k * Ib FLEXLOGIC OPERAND


IG RMS IG > k * Ib S
E =>1 THERMAL PROT 1 OP
LATCH

R
Reset dominant

LOAD CURRENT ES TIMATION


THERM PROT 1 RESET
IApn
IBpn TIME CONST:
ICpn THERM PROT 1 MINIM
IGp n RESET TIME:

RUN

SETTINGS
E < 0.05

THERM PROT 1 RESET:

Off = 0 Reset E to 0
827014A1.vsdx

5-388 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

5.10.0.10 Broken conductor detection


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  BROKEN CONDUCTOR 1(2)
 BROKEN CONDUCTOR 1 BROKEN CONDUCTOR 1 Range: Disabled, Enabled
  FUNCTION: Disabled

BROKEN CONDUCTOR 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

BROKEN CONDUCTOR 1 Range: 20.0% to 100.0% in steps of 0.1%


 I2/I1 RATIO: 20%

BROKEN CONDUCTOR 1 Range: 0.05 to 1.00 pu in steps of 0.01


 I1 MIN: 0.10 pu

BROKEN CONDUCTOR 1 Range: 0.05 to 5.00 pu in steps of 0.01


 I1 MAX: 1.50 pu

BROKEN CONDUCTOR 1 Range: 0.000 to 65.535 s in steps of 0.001


 PKP DELAY: 20.000 s

BROKEN CONDCT 1 BLK: Range: FlexLogic operand


 Off

BROKEN CONDUCTOR 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

BROKEN CONDUCTOR 1 Range: Disabled, Enabled


 EVENTS: Disabled

The broken conductor function detects a transmission line broken conductor condition or a single-pole breaker
malfunction condition by checking the phase current input signals and the I_2 / I_1 ratio. The intent is to detect a single-
phase broken conductor only. As such, two-phase or three-phase broken conductors cannot be detected.
5
To distinguish between single-phase disappearance and system disturbance in all three phases (such as load change and
switching), the broken conductor element monitors the change in all three phase currents at the present instance and at
four cycles previous. It also monitors changes in the I_2 / I_1 ratio, I_1 minimum, and I_1 maximum.
Do not use the broken conductor function to respond to fault transients and single-pole tripping/reclosing conditions.
Therefore, program the time delay to a sufficient length to ensure coordination with the breaker dead time of the recloser
function.
BROKEN CONDUCTOR 1 FUNCTION — This setting enables and disables the broken conductor function.
BROKEN CONDUCTOR 1 SOURCE — Selects a signal source used to provide three-phase current inputs to this function.
BROKEN CONDUCTOR 1 I2/I1 RATIO — This setting specifies the ratio of negative-sequence current to positive-sequence
current. When one phase conductor is broken, the I_2 / I_1 ratio with a balanced remaining two phases is 50%. So
normally you this setting below 50% (for example, to 30%).
BROKEN CONDUCTOR 1 I1 MIN — This setting specifies the minimum positive-sequence current supervision level. Ensure this
setting is programmed to a sufficient level to prevent I_2 / I_1 from erratic pickup due to a low I_1 signal. However, do not
set this setting too high, since the broken conductor condition cannot be detected under light load conditions when I_1 is
less than the value specified by this setting.
BROKEN CONDUCTOR 1 I1 MAX — This setting specifies the maximum I_1 level allowed for the broken conductor function to
operate. When I_1 exceeds this setting, this it is considered a fault. In order for this function to not respond to any fault
conditions, set this setting to less than the maximum load current.
BROKEN CONDUCTOR 1 PKP DELAY — This setting specifies the pickup time delay for this function to operate after assertion
of the broken conductor pickup FlexLogic operand.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-389


5

5-390
MONITORING ELEMENTS

SETTINGS
BROKEN CONDUCTOR 1
FUNCTION:
Enabled = 1
BROKEN CONDCT 1 BLK: AND
SETTINGS
Off = 0
BROKEN CONDUCTOR 1
I1 MAX:

BROKEN CONDUCTOR 1
SETTING I2/I1 RATIO:
SETTINGS
BROKEN CONDUCTOR 1 Run
BROKEN CONDUCTOR 1
SOURCE: I1 MIN:
|I1 | < I1 MAX SETTING
I2 Run |I2| / |I1| > RATIO
BROKEN CONDUCTOR 1
I1 |I1 > I1 MIN I1 MAX:
Ia |Ia| < I1 MIN FLEXLOGIC OPERAND
tPKP
|Ib| < I1 MIN AND BROKEN CONDUCT 1 OP
Ib AND
0
Ic |Ic| < I1 MIN
|Ia’| - |Ia| > 0.05 pu
Ic
|Ib’| - |Ib| > 0.05 pu 2 cyc
AND OR
|Ic’| - |Ic| > 0.05 pu
0 OR
Where I’ is four cycles old
FLEXLOGIC OPERAND
BROKEN CONDUCT 1 PKP
AND
Figure 5-206: Broken conductor detection logic

One phase current


loss detection 832030A1.cdr

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS
CHAPTER 5: SETTINGS MONITORING ELEMENTS

5.10.0.11 Harmonic detection


SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  HARMONIC DETECTION  HARMONIC DET 1(6)
 HARMONIC DET 1 HARMONIC DET 1 Range: Disabled, Enabled
  FUNCTION: Disabled

HARMONIC DET 1 Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

HARMONIC DET 1 Range: DC, 2nd, 3rd, 4th, 5th, THD


 HARMONIC: 2nd

HARMONIC DET 1 MIN Range: 0.1 to 1.0 pu in steps of 0.01


 PHS CUR: 0.2 pu

HARMONIC DET 1 MAX Range: 1.0 to 30 pu in steps of 0.01


 PHS CUR: 5.0 pu

HARMONIC DET 1 PHASE Range: ANY ONE, ANY TWO, ALL THREE, AVERAGE
 FOR OPER: ANY ONE

HARMONIC DET 1 PHS Range: 2.0 to 100% in steps of 0.1


 PICKUP: 20%

HARMONIC DET 1 MIN Range: 0.1 to 1.0 pu in steps of 0.01


 GND CUR: 0.2 pu

HARMONIC DET 1 MAX Range: 1.0 to 30 pu in steps of 0.01


 GND CUR: 1.0 pu

HARMONIC DET 1 GND Range: 0.1 to 100% in steps of 0.1


 PICKUP: 20%

 HARMONIC DET 1 PKP Range: 0.00 to 600 s in steps of 0.01


5
DELAY: 0 s

HARMONIC DET 1 BLK: Range: Off, On, FlexLogic operand


 Off

HARMONIC DET 1 Range: Self-reset, Latched, Disabled


 TARGET: Self-reset

HARMONIC DET 1: Range: Disabled, Enabled


 EVENTS: Disabled

Transformer energization, voltage recovery following a clearance of external faults, startup or shutdown of generators
connected to transformers, or following a load injection can cause excessive magnetizing inrush current. The nature of the
magnetizing inrush current contains significant harmonics. The fundamental magnitude of this magnetizing inrush current
can be several times of the rated transformer overload current. Depending on the sensitivity of the feeder or line
overcurrent protection elements, magnetizing inrush current can cause an undesired operation on these overcurrent
protection elements.
In addition, DC offset can cause saturation in current transformers as well as in the input current transformers of
protective relays and can also result in undesired operation on some sensitive protection elements, such as differential
protection, restricted earth fault protection, or sequence overcurrent protection elements.
The Harmonic Detection element monitors one of the selected quantities, including DC offset, 2nd to 5th harmonic, or
Total Harmonics Distortion (THD), that are present in the phase currents and ground current. It adds delay or blocking to
prevent undesired operation. Harmonics are calculated and presented as a percent value relative to the fundamental
frequency phasor magnitude.

When the output of this element is used for blocking protection functions, apply it directly (combination with other
FlexLogic operands adds delay to the blocking).

HARMONIC DET 1 FUNCTION — This setting enables and disables the Harmonic Detection element.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-391


MONITORING ELEMENTS CHAPTER 5: SETTINGS

HARMONIC DET 1 SOURCE — Indicates the signal source for this element. Phase currents are taken from the three-phase CT
bank assigned to this source. Ground current is taken from the same source from the ground CT channel.
HARMONIC DET 1 HARMONIC — This setting selects DC, harmonic (2nd to 5th), or THD as the input quantity to be compared
against the pickup threshold in this element. Note that DC, harmonic, and THD are expressed in percent relative to the
fundamental magnitude. This setting applies to all four channels of the selected source. If detection of another harmonic is
required, then set up a separate Harmonic Detection element.
This setting applies to all four channels of the selected source, if detection of another harmonic is required, then set up a
separate Harmonic Detection element.
HARMONIC DET 1 MIN PHS CUR — This setting defines the minimum fundamental frequency current phasor magnitude
required to allow the respective (phase) logic in the harmonic detection element to operate.
HARMONIC DET 1 MAX PHS CUR — This setting defines the maximum fundamental frequency current phasor magnitude of
the phases above which the harmonic detection phase output is inhibited.
HARMONIC DET 1 PHASE FOR OPER — This setting defines the phases required for assertion of the HARMONIC DET 1 OP
operand (except ground current channel). Options are as follows:
ANY ONE — At least one phase picked up (DEFAULT)
ANY TWO — Two or more phases picked up
ALL THREE — All three phases picked up
AVERAGE — The average of three-phase harmonics or THDs picked up
If set to AVERAGE, the relay calculates the average level of the selected harmonic and compares this level against the
pickup setting. Averaging of the selected harmonic follows an adaptive algorithm depending on the fundamental current
magnitude per-phase. If the fundamental magnitude on any of the three phases falls outside of the defined range based
on the MIN PHS CUR and the MAX PHS CUR settings, the selected harmonic current from that phase is dropped (zeroed)
5 from the equation for averaging, and the divider is decreased from 3 to 2. The same happens if the magnitude of the
fundamental phasor on one of the remaining two phases falls out of the defined range based on the MIN PHS CUR and
MAX PHS CUR settings. In this case, the selected harmonic on this phase is dropped from summation, and the divider is
decreased to 1.
HARMONIC DET 1 PHS PICKUP — This setting defines the pickup setting for the phase harmonic detection comparator of this
element.
HARMONIC DET 1 MIN GND CUR — This setting defines the minimum fundamental frequency ground current phasor
magnitude required to allow the respective (ground) logic in this harmonic detection element to operate.
HARMONIC DET 1 MAX GND CUR — This setting defines the maximum fundamental frequency ground current phasor
magnitude above which the harmonic detection ground output is inhibited.
HARMONIC DET 1 GND PICKUP — This setting defines the pickup setting for ground harmonic detection comparator of this
element.
The ground harmonic detection comparator of this element is connected to the ground channel of a CT module. For
standard channels, the conversion range is from 0.02 to 46 times the CT rating. For sensitive channels (sensitive ground CT
types), the conversion range is from 0.002 to 4.6 times the CT rating.
HARMONIC DET 1 PKP DELAY — This setting defines the pickup delay setting for this element.
HARMONIC DET 1 BLK — Assertion of the operand assigned to this setting blocks operation of the Harmonic Detection
element.
HARMONIC DET 1 EVENTS — This setting enables and disables the logging of Harmonic Detection events in the event
recorder.

5-392 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

Figure 5-207: Harmonic detection logic


SETTINGS
HARMONIC DET 1 MAX
PHS CUR:
RUN
IA > MAX PHS CUR AND
RUN
IB > MAX PHS CUR AND FLEXLOGIC OPERANDS
SETTING O HARMONIC DET 1 PKP
RUN R
HARMONIC DET 1
FUNCTION: IC > MAX PHS CUR
AND
Enabled = 1 RUN
AND FLEXLOGIC OPERANDS
IAVG > MAX PHS CUR
SETTING AND HARMONIC DET 1 PKP A
HARMONIC DET 1 HARMONIC DET 1 PKP B
BLOCK: HARMONIC DET 1 PKP C
SETTINGS
Off = 0 SETTINGS FLEXLOGIC OPERANDS
HARMONIC DET 1 MIN SETTINGS
PHS CUR: HARMONIC DET HARMONIC DET 1 HARMONIC DET 1 OP A
SETTING RUN 1 PHS PICKUP: PICKUP DELAY: HARMONIC DET 1 OP B
HARMONIC DET 1 RUN HARMONIC DET 1 OP C
SOURCE: IA > MIN PHS CUR TPKP
RUN HARM IA > PHS Pickup 20 ms
IA
IB IB > MIN PHS CUR RUN
TPKP SETTINGS
IC RUN HARM IB > PHS Pickup 20 ms
IAVG PHASES FOR
IC > MIN PHS CUR RUN TPKP OPERATION
IG HARM IC > PHS Pickup 20 ms
THD IA RUN
RUN FLEXLOGIC OPERAND
Harm IA [0, 2, 3, 4, 5] IAVG > MIN PHS CUR TPKP ANY ONE
HARM AVG > PHS Pickup 20 ms HARMONIC DET 1 OP
THD IB
Harm IB [0, 2, 3, 4, 5] SETTING ANY TWO
THD IC HARMONIC DET 1
Harm IC [0, 2, 3, 4, 5] HARMONIC: ALL THREE
THD IAVG PHASE A HARM# SELECT AVERAGE
Harm IAVG [0, 2, 3, 4, 5]
THD IG PHASE B HARM# SELECT
Harm IG [0, 2, 3, 4, 5] PHASE C HARM# SELECT
AVG HARM# SELECT

GND HARM# SELECT FLEXLOGIC OPERANDS


HARMONIC DET 1 PKP G

SETTINGS
HARMONIC DET 1 MAX
GND CUR:
SETTINGS
HARMONIC DET 1
GND PICKUP:
SETTINGS
HARMONIC DET 1
PICKUP DELAY:
5
RUN FLEXLOGIC OPERANDS
AND RUN TPKP
IG > MAX GND CUR HARMONIC DET 1 OP G
HARM IG > GND Pickup 20 ms

SETTINGS
HARMONIC DET 1 MIN
GND CUR:
RUN
IG > MIN GND CUR
859807A1.vsdx

5.10.1 Cold load pickup


SETTINGS  CONTROL ELEMENTS  COLD LOAD PICKUP  COLD LOAD PICKUP 1(2)
 COLD LOAD PICKUP 1 COLD LOAD 1 Range: Disabled, Enabled
  FUNCTION: Disabled

COLD LOAD 1 PICKUP Range: SRC 1, SRC 2, SRC 3, SRC 4


 SOURCE: SRC 1

COLD LOAD 1 INIT: Range: FlexLogic operand


 Off

COLD LOAD 1 BLK: Range: FlexLogic operand


 Off

OUTAGE TIME BEFORE Range: 0 to 1000 s in steps of 1


 COLD LOAD1: 1000 s

ON-LOAD TIME BEFORE Range: 0.000 to 1000 000.000 s in steps of 0.001


 RESET1: 100.000

Cold load is the restoration of current into the system after being off. A cold load condition can be caused by a prolonged
outage of the load, by opening of the circuit breaker, or by a loss of supply even if the breaker remains closed. Upon the
return of the source, the circuit experiences inrush current into connected transformers, accelerating currents into motors,
and simultaneous demand from many other loads because the normal load diversity has been lost.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-393


MONITORING ELEMENTS CHAPTER 5: SETTINGS

This feature can be used to change protection element settings when (by changing to another settings group) a cold load
condition is expected to occur. During the cold load condition, the current level can be above the pickup setting of some
protection elements, so this feature can be used to prevent the tripping that is otherwise caused by the normal settings.
Without historical data on a particular feeder, some utilities assume an initial cold load current of about 500% of normal
load, decaying to 300% after 1 second, 200% after 2 seconds, and 150% after 3 seconds.
Figure 5-208: Typical cold load pickup characteristics


$VSSFOU PGOPSNBM




/03."-53*14&55*/(

9
1*$,61 1*$,61

065"(&

       
UJNF TFDPOET

-0"%&/&3(*;&% (#"'& 1!34B

There are two methods to initiate operation of this feature.


The first initiation method is automatic response to a loss of the source to the feeder, by detecting that all phase currents
have declined to zero for some time. When zero current on all phases has been detected, a timer starts. This timer is set to
an interval after which it is expected the normal load diversity has been lost, so setting groups are not changed for short
5 duration outages. After the delay interval, the output operand is set.
The second initiation method is automatic response to an event that sets an operand, such as an operator-initiated virtual
input. This second method of initiation sets the output operand immediately.
Both initiating inputs can be inhibited by a blocking input. Once cold load pickup is in operation, the output operand
remains set until at least one phase of the load has returned to a level above 2% of CT nominal for the interval
programmed by the ON-LOAD TIME BEFORE RESET setting has expired. The reset delay interval is intended to be set to a
period until the feeder load has decayed to normal levels, after which other features can be used to switch setting groups.

5-394 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

Figure 5-209: Cold load pickup logic

6(77,1*
&2/'/2$'3,&.83
$1'
)81&7,21
(QDEOHG

6(77,1*
$1'
&2/'/2$'3,&.83
%/.
2II

6(77,1* 25

&2/'/2$'3,&.83
6285&(
581
6(77,1*
,$ ,$120,1$/&7 287$*(7,0(%()25(
&2/'/2$'
581
,% ,%120,1$/&7 $1' 

581 )/(;/2*,&23(5$1'
,& ,&120,1$/&7
25 &/'/2$'23

6(77,1*
&2/'/2$'3,&.83
$1' 6(77,1*
,1,7 581
,$!120,1$/&7 21/2$'7,0(%()25(
2II
5(6(7
581
25 
,%!120,1$/&7
581
,&!120,1$/&7
$&'5

5.10.2 Pilot schemes 5


SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES
 PILOT SCHEMES  POTT3 SCHEME See below
  

 DCB3 SCHEME See page 5-397


 

5.10.2.1 Permissive over-reaching transfer trip (POTT3)


SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  POTT3 SCHEME
 POTT3 SCHEME POTT3 SCHEME Range: Disabled, Enabled
  FUNCTION: Disabled

POTT3 SCHEME BLOCK: Range: FlexLogic operand


 Off

POTT3 PERMISSIVE Range: Disabled, Enabled


 ECHO: Disabled

POTT3 RX PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.000 s

TRANS BLOCK PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.020 s

TRANS BLOCK RESET Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.090 s

ECHO DURATION: Range: 0.000 to 65.535 s in steps of 0.001


 0.100 s

ECHO LOCKOUT: Range: 0.000 to 65.535 s in steps of 0.001


 0.250 s

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-395


MONITORING ELEMENTS CHAPTER 5: SETTINGS

LINE END OPEN PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.050 s

LINE END OPEN: Range: FlexLogic operand


 Off

POTT3 SEAL-IN Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.400 s

POTT3 DIR FWD1: Range: FlexLogic operand


 Off

POTT3 DIR FWD2: Range: FlexLogic operand


 Off

POTT3 DIR FWD3: Range: FlexLogic operand


 Off

POTT3 RX: Range: FlexLogic operand


 Off

POTT3 SCHEME TARGET: Range: Self-Reset, Latched, Disabled


 Self-Reset

POTT3 SCHEME EVENTS: Range: Disabled, Enabled


 Disabled

This scheme is for two-terminal line applications only. It uses over-reaching directional protection elements (such as
directional overcurrent functions) to essentially compare the direction to a fault at both the ends of the line. The Line End
Open input field needs to be properly set to indicate line-end-open (LEO) / weak-infeed conditions.
POTT3 SCHEME BLOCK — This setting allows any FlexLogic operand to be assigned to block the scheme. Contact inputs from
5 a pilot cut-out switch are used typically for this purpose.
POTT3 PERMISSIVE ECHO — If this setting is set to "Enabled," the scheme sends a permissive echo signal to the remote end(s).
The echo is sent only once and then the logic locks out for the time specified by the ECHO LOCKOUT. The duration of the
echo pulse is settable as ECHO DURATION.
POTT3 RX PICKUP DELAY — This setting enables the relay to cope with spurious receive signals. Set the delay longer than the
longest spurious TX signal that can be received simultaneously with the protection function pickup specified in POTT3 DIR
FWD1-3 fields. The selected delay increases the response time of the scheme.
TRANS BLOCK PICKUP DELAY — This setting defines a transient blocking mechanism embedded in the POTT3 scheme to cope
with exposure of the directional overcurrent function. Upon receiving the POTT3 RX signal, the transient blocking
mechanism allows the RX signal to be passed and aligned with the DIR FWD1-3 indication for a period of time set by TRANS
BLOCK PICKUP DELAY. After that the ground directional overcurrent path is virtually disabled for the time specified as TRANS
BLOCK RESET DELAY.
Set this TRANS BLOCK PICKUP DELAY long enough to give the selected directional overcurrent function time to operate, but
not longer than the fastest possible operation time of the protection system that can create current reversal conditions
within the reach of the selected directional overcurrent function.
TRANS BLOCK RESET DELAY — This setting defines a transient blocking mechanism embedded in the POTT3 scheme to cope
with exposure of the directional overcurrent function to current reversal conditions (see the TRANS BLOCK PICKUP DELAY). Set
this delay long enough to cope with transient conditions including not only current reversals but also spurious negative-
and zero-sequence currents occurring during breaker operations.
ECHO DURATION — This setting defines the guaranteed and exact duration of the echo pulse. The duration does not depend
on the duration and shape of the received RX signal. This setting enables the relay to avoid a permanent lock-up of the
transmit/receive loop.
ECHO LOCKOUT — This setting defines the lockout period for the echo logic after sending the echo pulse.
LINE END OPEN PICKUP DELAY — This setting defines the pickup delay of the line end open conditions. The validated line end
open condition is a requirement for the POTT3 scheme to return a received echo signal (if the echo feature is enabled).
POTT3 LINE END OPEN — This setting allows the user to select the FlexLogic operand to represent the Line End Open
condition, such as breaker open status, or under voltage and under current conditions.

5-396 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

POTT3 SEAL-IN DELAY — The output FlexLogic operand (POTT3 OP) is produced according to the POTT3 scheme logic. A
seal-in time delay is applied to this operand for coping with noisy communication channels. The POTT SEAL-IN DELAY
defines a minimum guaranteed duration of the POTT3 OP pulse.
POTT3 DIR FWD1-3 — This setting defines the FlexLogic operand of a protection element to identify forward faults on the
protected line, and thus, for initiating operation of the scheme. Good directional integrity is the key requirement for an
over-reaching forward-looking protection element.
Even though any FlexLogic operand can be used as DIR FWD, enabling the user to combine responses of various
protection elements or to apply extra conditions through FlexLogic equations, DIR FWD entries are primarily meant to be
the output operand from the Negative-Sequence Directional FWD IOC and Neutral Directional FWD IOC.
POTT3 RX — This setting selects the FlexLogic operands to represent the permission receive signals for the scheme. Contact
inputs interfacing with a signaling system(s) are used typically.
Figure 5-210: POTT3 scheme logic
SETTING

POTT3 SCHEME FUNCTION:

Disabled = 0
Enabled = 1

SETTING
POTT3 SCHEME BLOCK: AND

OFF = 0

SETTING

POTT3 DIR FWD1:


Off = 0
POTT3 DIR FWD2: AND
Off = 0

POTT3 DIR FWD3:


OR
SETTING 5
Off = 0 SETTING POTT3 SEAL-IN DELAY:
FLEXLOGIC OPERAND
POTT3 RX PICKUP DELAY:
0 POTT3 OP
AND t RST
FLEXLOGIC OPERAND
t PKP
POTT3 RX: AND
0
Off = 0
SETTINGS
TRANS BLOCK PICKUP AND
DELAY:

TRANS BLOCK RESET


DELAY:
t PKP
t RST

0 FLEXLOGIC OPERAND

100ms OR POTT3 TX
SETTING
SETTING
AND
POTT3 LINE END OPEN: LINE END OPEN PICKUP Echo duration and
DELAY: lockout logic
Off = 0 t PKP
SETTING SETTING
0 AND
ECHO DURATION ECHO LOCKOUT
SETTING AND
0 0
POTT3 PERMISSIVE ECHO:

Disabled = 0
Enabled = 1

837044A1.vsd

5.10.2.2 Directional comparison blocking 3 (DCB3)


SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  DCB3 SCHEME
 BLOCKING3 SCHEME DCB3 SCHEME Range: Disabled, Enabled
  FUNCTION: Disabled

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-397


MONITORING ELEMENTS CHAPTER 5: SETTINGS

DCB3 SCHEME BLOCK: Range: FlexLogic operand


 Off

DCB3 RX CO-ORD PKP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.010 s

TRANS BLOCK PICKUP Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.030 s

TRANS BLOCK RESET Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.090 s

DCB3 SCHEME SEAL-IN Range: 0.000 to 65.535 s in steps of 0.001


 DELAY: 0.010 s

DCB3 SCHME DIR FWD1: Range: FlexLogic operand


 Off

DCB3 SCHME DIR FWD2: Range: FlexLogic operand


 Off

DCB3 SCHME DIR FWD3: Range: FlexLogic operand


 Off

DCB3 SCHME DIR REV1: Range: FlexLogic operand


 Off

DCB3 SCHME DIR REV2: Range: FlexLogic operand


 Off

DCB3 SCHME DIR REV3: Range: FlexLogic operand


 Off

5  DCB3 FORCE TX STOP1:


Off
Range: FlexLogic operand

DCB3 FORCE TX STOP2: Range: FlexLogic operand


 Off

DCB3 RX: Range: FlexLogic operand


 Off

DCB3 SCHEME TARGET: Range: Self-Reset, Latched, Disabled


 Self-Reset

DCB3 SCHEME EVENTS: Range: Disabled, Enabled


 Disabled

The scheme compares the direction to a fault at all terminals of the line. Unlike the permissive schemes, the absence of a
blocking signal permits operation of the scheme. Consequently, the scheme is biased toward dependability and requires
an "on/off" type of signaling.
The scheme generates output operands (DIR BLOCK TX INIT and DIR BLOCK TX STOP) that control the transmission
of signals to the remote end(s). When used with telecommunications facilities, assign the output operands to operate
output contacts connected to key the transmitter at the interface.
DCB3 SCHEME BLOCK — This setting allows any FlexLogic operand to be assigned to block the scheme. Contact inputs from
a pilot cut-out switch are used typically for this purpose.
DCB3 RX CO-ORD PKP DELAY — This setting defines a delay for the forward-looking protection elements used by the scheme
for coordination with the blocking response from the remote end(s). In this setting, include both the response time of the
protection elements used to establish a blocking signal and the total transmission time of that signal including the relay
communications equipment interfacing and the communications channel itself.
TRANS BLOCK PICKUP DELAY — This setting defines a transient blocking mechanism embedded in the blocking scheme for
coping with the exposure of directional overcurrent function to current reversal conditions.
The transient blocking logic applies to the send path only. Identifying the fault as a reverse fault establishes the blocking
signal. If the reverse fault condition prevails for TRANS BLOCK PICKUP DELAY, the blocking operation is extended by the
transient blocking timer for TRANS BLOCK RESET DELAY. This allows riding through current reversal conditions. However, if

5-398 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS MONITORING ELEMENTS

internal faults on the protected line are identified, the blocking action can be removed through FORCE TX STOP1-2 inputs.
This is done to cope with evolving faults when an external fault is followed by an internal fault. Do not set the TRANS BLOCK
PICKUP DELAY longer than the fastest possible trip time for faults on an adjacent line so that the extended blocking action
can be established. Take into account the pickup time of the reverse-looking elements of the scheme. Do not set the delay
too short, in order to avoid locking up a spurious reverse fault indication that can occur during internal fault conditions.
TRANS BLOCK RESET DELAY — This setting defines a transient blocking mechanism embedded in the blocking scheme for
coping with the exposure of the overreaching protection functions to current reversal conditions (see also the TRANS BLOCK
PICKUP DELAY). Set this delay long enough to cope with transient conditions including not only current reversals but also
spurious negative and zero-sequence currents occurring during breaker operations.
DCB3 SEAL-IN DELAY — The output FlexLogic operand (DCB3 OP) is produced according to the Blocking scheme logic. The
DCB3 SEAL-IN DELAY defines a minimum guaranteed duration of the DCB3 OP pulse.
DCB3 DIR FWD1-3 — This setting defines the FlexLogic operand of a protection element to identify forward faults on the
protected line, and thus, for initiating operation of the scheme. Good directional integrity is the key requirement for an
over-reaching forward-looking protection element.
Even though any FlexLogic operand can be used as DIR FWD, enabling the user to combine responses of various
protection elements or to apply extra conditions through FlexLogic equations, DIR FWD entries are primarily meant to be
the output operand from the Negative-Sequence Directional FWD IOC, Neutral Directional FWD IOC, and the forward-
looking distance over-reaching elements.
DCB3 DIR REV1-3 — This setting defines the FlexLogic operand of a protection element to identify reverse faults, and thus, to
initiate the blocking signal. Reverse-looking directional overcurrent protection elements or reverse-looking distance
elements can be used as DIR REV.
Even though any FlexLogic operand can be used as DIR REV, enabling the user to combine responses of various protection
elements or to apply extra conditions through FlexLogic equations, DIR REV entries are primarily meant to be the output
operand from the Negative-Sequence Directional REV IOC, Neutral Directional REV IOC, non-directional IOC, or reverse-
looking distance elements.
5
The selected protection element (or elements in combination) need to be coordinated with the selection of DIR FWD. For all
the forward external faults seen by an element used as DIR FWD at one end of the line, the reverse-looking element used
as DIR REV at the other end needs to pick up and provide a blocking signal.
DCB3 FORCE TX STOP1-2 — This setting defines the FlexLogic operand of a protection element that is used to identify internal
faults on the protected line, and thus, to stop the blocking signal. Typically, forward-looking under-reach protection
elements are used as FORCE TX STOP.
DCB3 RX — This setting selects the FlexLogic operands to represent the receive signals for the scheme. Contact inputs
interfacing with a signaling system(s) are used typically.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-399


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

Figure 5-211: DCB3 scheme logic


SETTING
DCB3 SCHEME
FUNCTION:
Disabled=0
Enabled=1
AND

SETTING
DCB3 SCHEME BLOCK:
OFF = 0
SETTING
DCB3 RX CO-ORD PKP
DELAY:
SETTING

DCB3 DIR FWD1: AND t PKP


0
Off = 0

DCB3 DIR FWD2:


Off = 0 OR

DCB3 DIR FWD3: SETTING


AND
Off = 0 DCB3 SCHEME
SEAL-IN DELAY:
FLEXLOGIC OPERAND
0 DCB3 OP
t RST
SETTING

DCB3 RX:
AND
Off = 0

FLEXLOGIC OPERANDS
SETTING AND DCB3 TX STOP
DCB3 DIR REV1:

Off = 0

DCB3 DIR REV2: AND


Off = 0 OR
SETTINGS
DCB3 DIR REV3:
TRANS BLOCK PICKUP FLEXLOGIC OPERAND
Off = 0
DELAY: DCB3 TX INIT

5
OR
TRANS BLOCK RESET
SETTING DELAY:
DCB3 FORCE TX STOP1 t PKP
t RST
Off = 0 OR

DCB3 FORCE TX STOP2 OR

Off = 0 837045A1vsd

5.11 Inputs/outputs
5.11.1 Contact inputs
SETTINGS  INPUTS / OUTPUTS  CONTACT INPUTS
 CONTACT INPUTS

 CONTACT INPUT H5a


 

CONTACT INPUT H5a ID: Range: up to 20 alphanumeric


 Cont Ip 1 characters

CONTACT INPUT H5a Range: 0.0 to 16.0 ms in steps of 0.5


 DEBNCE TIME: 6.0 ms

CONTACT INPUT H5a Range: Disabled, Enabled


 EVENTS: Disabled

 CONTACT INPUT xxx
 

 CONTACT INPUT
  THRESHOLDS

5-400 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

Ips H5a,H5c,H6a,H6c Range: 17, 33, 84, 166 Vdc


 THRESHOLD: 33 Vdc

Ips H7a,H7c,H8a,H8c Range: 17, 33, 84, 166 Vdc


 THRESHOLD: 33 Vdc

Ips xxx,xxx,xxx,xxx Range: 17, 33, 84, 166 Vdc
 THRESHOLD: 33 Vdc

Contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each
group of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules)
which contact inputs are available and then display settings for only those inputs.
An alphanumeric ID can be assigned to a contact input for diagnostic, setting, and event recording purposes. The
CONTACT IP X On (Logic 1) FlexLogic operand corresponds to contact input “X” being closed, while CONTACT IP X Off
corresponds to contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to
overcome ‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a
maximum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If
CONTACT INPUT EVENTS is set to “Enabled,” every change in the contact input state triggers an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the following
figure. The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a
user-settable debounce time in order for the Product to validate the new contact state. In the following figure, the
debounce time is set at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram).
Once validated (de-bounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user
setting.
5
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the
contact input into the Event Recorder (mark no. 2 in the figure).
Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the
figure that follows). The update is performed at the beginning of the protection pass so all protection and control functions,
as well as FlexLogic equations, are fed with the updated states of the contact inputs.
The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration
of the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically
a delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1 ms.
For example, eight protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a
contact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 ms accuracy using the
time of the first scan corresponding to the new state (mark no. 2 shown). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the
debounce timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the
change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure) and HIGH-LOW (marks no. 5, 6, 7, and 8) transitions.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-401


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

92/7$*(
Figure 5-212: Input contact debouncing mechanism and time stamp sample timing
,1387

86(5352*5$00$%/(7+5(6+2/'


   
7LPHVWDPSRIWKHILUVW
7LPHVWDPSRIWKHILUVW $WWKLVWLPHWKH 7KH)OH[/RJLF70 VFDQFRUUHVSRQGLQJWRWKH
$WWKLVWLPHWKHQHZ
VFDQFRUUHVSRQGLQJWR QHZ +,*+ RSHUDQGLVJRLQJWR QHZYDOLGDWHGVWDWHLV
/2: FRQWDFWVWDWHLV
WKHQHZYDOLGDWHGVWDWHLV FRQWDFWVWDWHLV EHDVVHUWHGDWWKLV ORJJHGLQWKH62(UHFRUG
YDOLGDWHG
ORJJHGLQWKH62(UHFRUG YDOLGDWHG SURWHFWLRQSDVV


5$: &217$&7

7KH)OH[/RJLF70
RSHUDQGLVJRLQJWREH
67$7(

GHDVVHUWHGDWWKLV
SURWHFWLRQSDVV
'(%281&(7,0(
XVHUVHWWLQJ


7KH)OH[/RJLF70RSHUDQG
'(%281&(7,0(
7KH)OH[/RJLF70RSHUDQG FKDQJHVUHIOHFWLQJWKH
6&$17,0( XVHUVHWWLQJ
FKDQJHVUHIOHFWLQJWKH YDOLGDWHGFRQWDFWVWDWH
)/(;/2*,&70

PVHF YDOLGDWHGFRQWDFWVWDWH
23(5$1'

3527(&7,213$66
WLPHVDF\FOHFRQWUROOHGE\WKH
IUHTXHQF\WUDFNLQJPHFKDQLVP
$FGU

5 Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value is selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V sources
and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it
in the Event Records menu, make the following settings changes:
CONTACT INPUT H5a ID: "Breaker Closed (52b)"
CONTACT INPUT H5a EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.

5.11.2 Virtual inputs


SETTINGS  INPUTS/OUTPUTS  VIRTUAL INPUTS  VIRTUAL INPUT 1(128)
 VIRTUAL INPUT 1 VIRTUAL INPUT 1 Range: Disabled, Enabled
  FUNCTION: Disabled

VIRTUAL INPUT 1 ID: Range: up to 20 alphanumeric characters


 Virt Ip 1

VIRTUAL INPUT 1 Range: Self-Reset, Latched


 TYPE: Latched

VIRTUAL INPUT 1 Range: Disabled, Enabled


 EVENTS: Disabled

The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
The virtual inputs can be individually programmed to respond to input signals from the keypad (via the COMMANDS menu)
and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the appropriate input signal
is received.

5-402 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

If the VIRTUAL INPUT x FUNCTION is to “Disabled,” the input is forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled,” the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x type is “Self-Reset,” when the input signal
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched,” the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
Figure 5-213: Virtual inputs logic

SETTING
VIRTUAL INPUT 1
FUNCTION:
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND

5
Self - Reset 827080A3.CDR

5.11.3 Contact outputs

5.11.3.1 Digital outputs


SETTINGS  INPUTS/OUTPUTS  CONTACT OUTPUTS  CONTACT OUTPUT H1(H72)
 CONTACT OUTPUT H1 CONTACT OUTPUT H1 ID Range: up to 20 alphanumeric characters
  Cont Op 1

OUTPUT H1 OPERATE: Range: FlexLogic operand


 Off

OUTPUT H1 SEAL-IN: Range: FlexLogic operand


 Off

CONTACT OUTPUT H1 Range: Disabled, Enabled


 EVENTS: Enabled

A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
Upon startup of the relay, the main processor determines from an assessment of the modules installed in the chassis
which contact outputs are available and then presents the settings for only these outputs. Where the contact input is non-
latching, the settings are as shown.
An ID can be assigned to each contact output. The signal that can OPERATE a contact output can be any FlexLogic
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic operand can be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A
contacts (see the trip circuit example in the Digital Elements section). The monitor sets a flag (see the specifications for
Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, Cont OP 1 IOn.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-403


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect
operation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in
the trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the
tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized using the Cont OP 1 IOn FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”

Figure 5-214: Contact input/output module type 6A contact 1 logic


SETT ING
CONTACT OUTPU T H1 OPERATE
FLEXLOGIC OPERAND
= On
OR Cont Op 1 Closed
Cont Op 1 Ion
Cont Op 1 Von
Cont Op 1 Voff

SETT ING
CONTACT OUTPU T H1 SEAL-IN H1a
AND
= On

H1b

5 H1c

859743A1.vsd

5.11.3.2 Latching outputs


SETTINGS  INPUTS/OUTPUTS  CONTACT OUTPUTS  CONTACT OUTPUT H1a
 CONTACT OUTPUT H1a CONTACT OUTPUT H1a ID Range: up to 20 alphanumeric characters
  L-Cont Op 1

OUTPUT H1a OPERATE: Range: FlexLogic operand


 Off

OUTPUT H1a RESET: Range: FlexLogic operand


 Off

OUTPUT H1a SEAL-IN: Range: FlexLogic operand


 Off

OUTPUT H1a TYPE: Range: Operate-dominant, Reset-dominant


 Operate-dominant

CONTACT OUTPUT H1a Range: Disabled, Enabled


 EVENTS: Disabled

The latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and
populates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic).
The latching output modules, either as part of the relay or as individual modules, are shipped from the factory with all
latching contacts open. It is highly recommended to double-check the programming and positions of the latching contacts
when replacing a module.

5-404 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring
capabilities for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test
error is declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message.
Settings shown use H1a as an example. The menu varies; not all fields shown display.
OUTPUT H1a OPERATE — This setting specifies a FlexLogic operand to operate the ‘close coil’ of the contact. The relay seals-
in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off), any activity of the
OPERATE input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active
(logic 1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a RESET or SEAL-IN — This setting specifies a FlexLogic operand to operate the ‘trip coil’ of the contact. The relay
seals-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any activity
of the RESET input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs
active (logic 1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a TYPE — This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact closes if set to
“Operate-dominant” and opens if set to “Reset-dominant.”
Figure 5-215: Contact input/output module type 4L contact 1 logic
SETTING
CONTACT OUTPUT H1a OPERATE Non-volatile,
= On Set-dominant
AND S
SETTING OR Latch On
CONTACT OUTPUT H1a TYPE Close
= Operate-dominant R
H1b
= Reset-dominant
Non-volatile,
SETTING OR Set-dominant
H1a
CONTACT OUTPUT H1a RESET
= On
AND S
Latch
Open
5
R

FLEXLOGIC OPERAND
Cont Op 1 Closed

859744A1.vsd

Application example 1
A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings are applied.
Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT
OUTPUTS  CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “PUSHBUTTON 1 ON”
OUTPUT H1a RESET: “PUSHBUTTON 2 ON”
Program the pushbuttons by making the following changes in the PRODUCT SETUP  USER-PROGRAMMABLE PUSHBUTTONS
 USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.00 s”
PUSHBUTTON 2 FUNCTION: “Self-reset”
PUSHBTN 2 DROP-OUT TIME: “0.00 s”

Application example 2
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT
OUTPUTS  CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-405


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

OUTPUT H1a OPERATE: “VO1”


OUTPUT H1a RESET: “VO2”
OUTPUT H1c OPERATE: “VO2”
OUTPUT H1c RESET: “VO1”
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they do not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time can occur.
Therefore, a pair of contacts programmed to be a multi-contact relay do not guarantee any specific sequence of operation
(such as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the
control inputs as shown in the next application example.

Application example 3
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality.
Write the following FlexLogic equation (EnerVista example shown).

5
Set both timers (Timer 1 and Timer 2) to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT
OUTPUTS  CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO4”
OUTPUT H1c OPERATE: “VO2”
OUTPUT H1c RESET: “VO3”

Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista example shown).

Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT
OUTPUTS  CONTACT OUTPUT H1a menu (assuming an H4L module):

5-406 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

OUTPUT H1a OPERATE: “VO1”


OUTPUT H1a RESET: “VO2”

5.11.4 Virtual outputs


SETTINGS  INPUTS/OUTPUTS  VIRTUAL OUTPUTS  VIRTUAL OUTPUT 1(256)
 VIRTUAL OUTPUT 1 VIRTUAL OUTPUT 1 ID Range: up to 20 alphanumeric characters
  Virt Op 1

VIRTUAL OUTPUT 1 Range: Disabled, Enabled


 EVENTS: Disabled

The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
The virtual outputs can be assigned using FlexLogic. If not assigned, the output is forced to ‘OFF’ (Logic 0). An ID also can be
assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the FlexLogic
equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID: "Trip"
VIRTUAL OUTPUT 1 EVENTS: "Disabled"

5.11.5 Resetting
5
5.11.5.1 Enhanced and basic front panels
SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING RESET OPERAND: Range: FlexLogic operand
  Off

5.11.5.2 Graphical front panel


SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING RESET OPERAND: Range: FlexLogic operand
  Off

RESET ANNUNCIATOR: Range: FlexLogic operand


 Off

Some events can be programmed to latch the front panel LED event indicators, target messages, and/or graphical front
panel annunciator windows. Once set, the latching mechanism holds the latched indicators, messages, or windows in the
set state after the initiating condition has cleared until a RESET command is received to return these latches (not including
FlexLogic latches) to the reset state where the initiating condition has cleared. The RESET command can be sent from the
front panel RESET button, a remote device via a communications channel, or any selected operand. The Modbus execute
function 05h with operation code 1 command is also available to perform the same function as the front panel RESET key.
RESET OPERAND — The three sources of RESET commands each activates the RESET OP FlexLogic operand. Each individual
source of a RESET command also activates its individual operand RESET OP (PUSHBUTTON), RESET OP (COMMS), or
RESET OP (OPERAND) to identify the source of the command. Each of these three operands generates an event in the
event record when activated. The RESET OPERAND setting here selects the operand that activates the RESET OP
(OPERAND) operand.
RESET ANNUNCIATOR — Used to select a FlexLogic operand that when activated acknowledges/resets all annunciator
windows on the graphical front panel. The other methods to acknowledge/reset annunciator windows include:

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-407


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

• On the displayed page, press the RESET pushbutton with none of the annunciator windows selected to acknowledge/
reset all annunciator windows on that page
• To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the RESET or ENTER pushbutton
• All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the RESET ANNUNCIATOR setting. Then the Modbus execute function 05h with operation code 1000h command
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the RESET ANNUNCIATOR setting, the RESET ANCTR OP FlexLogic operand is activated by the two sources of RESET
command, operand source and manual source. Each individual source of a RESET ANNUNCIATOR command also activates
its individual operand RESET OP (OPRD) or RESET ANCTR OP (MNUL) to identify the source of the command. Each of
these two operands generates an event in the event record when activated. The setting here selects the operand that
activates the RESET ANCTR OP (OPRD) operand. The RESET pushbutton on the front panel or the reset command from
the software activates the RESET ANCTR OP (MNUL) operand.

5.11.6 Direct inputs and outputs

5.11.6.1 Direct inputs


SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1 DIRECT INPUT 1 Range: up to 12 alphanumeric characters
  NAME: Dir Ip 1

DIRECT INPUT 1 Range: 0 to 16


 DEVICE ID: 0

5  DIRECT INPUT 1
BIT NUMBER: 0
Range: 0 to 32

DIRECT INPUT 1 Range: On, Off, Latest/On, Latest/Off


 DEFAULT: Off

DIRECT INPUT 1 Range: Enabled, Disabled


 EVENTS: Disabled

These settings specify how the direct input information is processed.


DIRECT INPUT 1 NAME — This setting allows the user to assign a descriptive name to the direct input.
DIRECT INPUT 1 DEVICE ID — Represents the source of direct input 1. The specified direct input is driven by the device
identified here.
DIRECT INPUT 1 BIT NUMBER — The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device.
DIRECT INPUT 1 DEFAULT STATE — Represents the state of the direct input when the associated direct device is offline. The
following choices are available:
• On — Defaults the input to Logic 1
• Off — Defaults the input to Logic 0
• Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
• Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.

5-408 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

5.11.6.2 Direct outputs


SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(32)
 DIRECT OUTPUT 1 DIR OUT 1 NAME: Range: up to 12 alphanumeric characters
  Dir Out 1

DIR OUT 1 OPERAND: Range: FlexLogic operand


 Off

DIRECT OUTPUT 1 Range: Enabled, Disabled


 EVENTS: Disabled

DIR OUT 1 NAME — This setting allows the user to assign a descriptive name to the direct output.
DIR OUT 1 OPERAND — This sets the FlexLogic operand that determines the state of this direct output.

5.11.6.3 Application examples


The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued
here to illustrate usage of the direct inputs and outputs.

Example 1: Extending input/output capabilities of a UR relay


Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable
logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED,
such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The figure shows that two
IEDs are connected via single-channel digital communication cards.
Figure 5-216: Input and output extension via direct inputs and outputs

TX1
5
UR IED 1
RX1

TX1
UR IED 2
RX1

842711A1.CDR

Assume that contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings are applied (Direct Input 5 and
bit number 12 are used, as an example).
UR IED 1:
DIRECT INPUT 5 DEVICE ID = “2”
DIRECT INPUT 5 BIT NUMBER = “12”
UR IED 2:
DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.

Example 2: Interlocking busbar protection


A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-409


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

Figure 5-217: Sample interlocking busbar protection scheme

85,(' %/2&.

85,(' 85,(' 85,('

($"'!"1!34B

Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
trips the bus upon detecting a fault and applying a short coordination time delay.
The following settings are applied (assume Bit 3 is used by all 3 devices to send the blocking signal and Direct Inputs 7, 8,
and 9 are used by the receiving device to monitor the three blocking signals).
UR IED 2:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 3:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 4:
5 DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 1:
DIRECT INPUT 7 DEVICE ID: "2"
DIRECT INPUT 7 BIT NUMBER: "3"
DIRECT INPUT 7 DEFAULT STATE: select "On" for security, select "Off" for dependability

DIRECT INPUT 8 DEVICE ID: "3"


DIRECT INPUT 8 BIT NUMBER: "3"
DIRECT INPUT 8 DEFAULT STATE: select "On" for security, select "Off" for dependability

DIRECT INPUT 9 DEVICE ID: "4"


DIRECT INPUT 9 BIT NUMBER: "3"
DIRECT INPUT 9 DEFAULT STATE: select "On" for security, select "Off" for dependability
Now the three blocking signals are available in UR IED 1 as DIRECT INPUT 7 ON, DIRECT INPUT 8 ON, and DIRECT
INPUT 9 ON. Upon losing communications or a device, the scheme is inclined to block (if any default state is set to “On”), or
to trip the bus on any overcurrent condition (all default states set to “Off”).

Example 3: Pilot-aided schemes


Consider a three-terminal line protection application shown in the following figure.

5-410 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

Figure 5-218: Three-terminal line application

85,(' 85,('

85,(' ($"'!#1!34B

Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown as
follows. The scheme output operand HYB POTT TX1 is used to key the permission.
Figure 5-219: Single-channel open-loop configuration

7; 5; 5;


85,(' 85,('
5; 7; 7;

85,('
5; 5
7;
($"'!$1!34B

In this architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a "bridge." The following
settings are applied:
UR IEC 1:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "4" (effectively, this is a message from IED 3)
UR IED 3:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "3" (effectively, this is a message from IED 1)
UR IED 2:
DIRECT INPUT 5 DEVICE ID: "1"
DIRECT INPUT 5 BIT NUMBER: "2"
DIRECT INPUT 6 DEVICE ID: "3"
DIRECT INPUT 6 BIT NUMBER: "2"
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT OUT 3 OPERAND: "DIRECT INPUT 5" (forward a message from 1 to 3)
DIRECT OUT 4 OPERAND: "DIRECT INPUT 6" (forward a message from 3 to 1)
The figure shows the signal flow among the three IEDs.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-411


INPUTS/OUTPUTS CHAPTER 5: SETTINGS

Figure 5-220: Signal flow for direct input and output

85,(' 85,('
',5(&7287 +<%32777; ',5(&7,1387
',5(&7,1387 ',5(&7287 +<%32777;
',5(&7,1387 ',5(&7287 ',5(&7,1387
',5(&7287 ',5(&7,1387
',5(&7,1387

85,(' ',5(&7,1387
',5(&7,1387
',5(&7287 +<%32777;
($"'!'1!34B

In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1
setting).

5.11.7 Teleprotection

5 5.11.7.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
distributed protection and control schemes via dedicated communications channels. Some examples are directional
comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect
teleprotection functionality. The teleprotection function must be enabled to utilize the inputs.

5.11.7.2 Teleprotection inputs


SETTINGS  INPUTS/OUTPUTS  TELEPROTECTION  TELEPROT INPUTS
 TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On
  DEFAULT: Off

TELEPROT INPUT 1-16 Range: Off, On, Latest/Off, Latest/On
 DEFAULT: Off

TELEPROT INPUT 2-1 Range: Off, On, Latest/Off, Latest/On


 DEFAULT: Off

TELEPROT INPUT 2-16 Range: Off, On, Latest/Off, Latest/On
 DEFAULT: Off

Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/
On” and logic 0 for “Latest/Off.”

5-412 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS INPUTS/OUTPUTS

5.11.7.3 Teleprotection outputs


SETTINGS  INPUTS/OUTPUTS  TELEPROTECTION  TELEPROT OUTPUTS
 TELEPROT OUTPUTS TELEPROT OUTPUT 1-1: Range: FlexLogic operand
  Off

TELEPROT OUTPUT 1-16: Range: FlexLogic operand
 Off

TELEPROT OUTPUT 2-1: Range: FlexLogic operand


 Off

TELEPROT OUTPUT 2-16: Range: FlexLogic operand
 Off

As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of
communication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each
channel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand
on both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end).
On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of
channel failure between any pair of relays.
Figure 5-221: Teleprotection input/output processing

EB! EB"
13DE1<F1<E5C C5DD9>7

C5DD9>7

D5<5@B?D?ED@ED!!*
381>>5<!CD1DEC* D5<5@B?D9>@ED!!
4561E<D*
cQ]UV_b!"!!& 5
cQ]UV_b!"!!& ?^ 6<5H<?793?@5B1>4
6QY\
?VV6\Uh\_WYS?`UbQ^T ?VV D5<5@B?9>@ED!!?^
?; ?B
cQ]UV_b!"!!&

13DE1<F1<E5C
C5DD9>7
381>>5<!CD1DEC*
D5<5@B?D9>@ED!! 3_]]e^YSQdY_^SXQ^^U\!
4561E<D*
cQ]UV_b!"!!& DU\U`b_dUSdY_^9?5^QR\UT C5DD9>7
6<5H<?793?@5B1>4 D5<5@B?D?ED@ED!!*
?^ cQ]UV_b!"!!&
6QY\
D5<5@B?9>@ED!!?^ ?VV
?B ?; ?VV6\Uh\_WYS?`UbQ^T
cQ]UV_b!"!!&

EB"_bEB#
13DE1<F1<E5C C5DD9>7
381>>5<"CD1DEC* D5<5@B?D9>@ED"!
4561E<D*
C5DD9>7 cQ]UV_b"""!&
D5<5@B?D?ED@ED"!*
cQ]UV_b!"!!& ?^ 6<5H<?793?@5B1>4
6QY\
?VV D5<5@B?9>@ED"!?^
?VV6\Uh\_WYS?`UbQ^T ?; ?B
cQ]UV_b"""!&

13DE1<F1<E5C
C5DD9>7
381>>5<"CD1DEC*
D5<5@B?D9>@ED"! 3_]]e^YSQdY_^SXQ^^U\"
4561E<D*
cQ]UV_b!"!!& ?^#dUb]Y^Q\cicdU]_b"dUb]Y^Q\ C5DD9>7
6<5H<?793?@5B1>4
gYdXbUTe^TQ^dSXQ^^U\
D5<5@B?D?ED@ED"!*
?^ cQ]UV_b"""!&
6QY\
D5<5@B?9>@ED"!?^ ?VV
?B ?; ?VV6\Uh\_WYS?`UbQ^T
cQ]UV_b!"!!&

($"'% 1"34B


F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-413


TRANSDUCER INPUTS/OUTPUTS CHAPTER 5: SETTINGS

5.12 Transducer inputs/outputs


5.12.1 DCmA inputs
SETTINGS  TRANSDUCER I/O  DCMA INPUTS  DCMA INPUT H1(W8)
 DCMA INPUT H1 DCMA INPUT H1 Range: Disabled, Enabled
  FUNCTION: Disabled

DCMA INPUT H1 ID: Range: up to 20 alphanumeric characters


 DCMA Ip 1

DCMA INPUT H1 Range: six alphanumeric characters


 UNITS: μA

DCMA INPUT H1 Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5


 RANGE: 0 to -1 mA mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m

DCMA INPUT H1 MIN Range: –9999.999 to +9999.999 in steps of 0.001


 VALUE: 0.000

DCMA INPUT H1 MAX Range: –9999.999 to +9999.999 in steps of 0.001


 VALUE: 0.000

The F60 is provided with optional DCmA capability, specified at the time of ordering.

5 Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
Before the DCmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
DCmA input channels are arranged in a manner similar to CT and VT channels. Configure the individual channels with the
settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are generated automatically for every channel available in the specific relay as shown above for the first channel
of a type 5F transducer module installed in slot H.
The function of the channel can be “Enabled” or “Disabled.” If “Disabled,” no actual values are created for the channel. An
alphanumeric “ID” is assigned to each channel; this ID is included in the channel actual value, along with the programmed
units associated with the parameter measured by the transducer, such as volts, °C, megawatts, and so on. This ID is also
used to reference the channel as the input parameter to features designed to measure this type of parameter. The DCMA
INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250 °C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250.” Another example is a watts transducer with a span
from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value is “–20” and the DCMA INPUT H1 MAX VALUE value is
“180.” Intermediate values between the minimum and maximum values are scaled linearly.

5-414 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TRANSDUCER INPUTS/OUTPUTS

5.12.2 RTD inputs


SETTINGS  TRANSDUCER I/O  RTD INPUTS  RTD INPUT H1(W8)
 RTD INPUT H1 RTD INPUT H1 Range: Disabled, Enabled
  FUNCTION: Disabled

RTD INPUT H1 ID: Range: up to 20 alphanumeric characters


 RTD Ip 1

RTD INPUT H1 TYPE: Range: 100Ω Nickel, 10Ω Copper, 100Ω Platinum,
 100Ω Platinum 120Ω Nickel

Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either “Enabled” or “Disabled.” If “Disabled,” there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
5
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-415


TRANSDUCER INPUTS/OUTPUTS CHAPTER 5: SETTINGS

Table 5-51: RTD temperature vs. resistance


Temperature Resistance (in ohms)
°C °F 100 Ω Pt 120 Ω Ni 100 Ω Ni 10 Ω Cu
(DIN 43760)
–50 –58 80.31 86.17 71.81 7.10
–40 –40 84.27 92.76 77.30 7.49
–30 –22 88.22 99.41 82.84 7.88
–20 –4 92.16 106.15 88.45 8.26
–10 14 96.09 113.00 94.17 8.65
0 32 100.00 120.00 100.00 9.04
10 50 103.90 127.17 105.97 9.42
20 68 107.79 134.52 112.10 9.81
30 86 111.67 142.06 118.38 10.19
40 104 115.54 149.79 124.82 10.58
50 122 119.39 157.74 131.45 10.97
60 140 123.24 165.90 138.25 11.35
70 158 127.07 174.25 145.20 11.74
80 176 130.89 182.84 152.37 12.12
90 194 134.70 191.64 159.70 12.51
100 212 138.50 200.64 167.20 12.90
110 230 142.29 209.85 174.87 13.28
120 248 146.06 219.29 182.75 13.67
5 130 266 149.82 228.96 190.80 14.06
140 284 153.58 238.85 199.04 14.44
150 302 157.32 248.95 207.45 14.83
160 320 161.04 259.30 216.08 15.22
170 338 164.76 269.91 224.92 15.61
180 356 168.47 280.77 233.97 16.00
190 374 172.46 291.96 243.30 16.39
200 392 175.84 303.46 252.88 16.78
210 410 179.51 315.31 262.76 17.17
220 428 183.17 327.54 272.94 17.56
230 446 186.82 340.14 283.45 17.95
240 464 190.45 353.14 294.28 18.34
250 482 194.08 366.53 305.44 18.73

5.12.3 DCmA outputs


SETTINGS  TRANSDUCER I/O  DCMA OUTPUTS  DCMA OUTPUT H1(W8)
 DCMA OUTPUT H1 DCMA OUTPUT H1 Range: Off, any analog actual value parameter
  SOURCE: Off

DCMA OUTPUT H1 Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA


 RANGE: –1 to 1 mA

DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001


 MIN VAL: 0.000 pu

DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001


 MAX VAL: 1.000 pu

5-416 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TRANSDUCER INPUTS/OUTPUTS

Hardware and software is provided to generate DCmA signals that allow interfacing with external equipment. Hardware
details are contained in chapter 3. The DCmA output channels are arranged in a manner similar to transducer input or CT
and VT channels. The user configures individual channels with the settings as follows.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an
example for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The
following equation is applied:

­ I min if x < MIN VAL


°
I out = ® I max if x > MAX VAL Eq. 5-42
°
¯ k x – MIN VAL + I min otherwise

where
x is a driving signal specified by the SOURCE setting
Imin and Imax are defined by the RANGE setting
k is a scaling constant calculated as:

I max – I min
k = -------------------------------------------
- Eq. 5-43
MAX VAL – MIN VAL

The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, for example when MAX VAL
5
– MIN VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure.
Figure 5-222: DCmA output characteristic

9]Qh
?ED@ED3EBB5>D

9]Y^
4B9F9>7C97>1<
($"'#)1!34B =9>F1< =1HF1<

Settings
DCMA OUTPUT H1 SOURCE — This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving DCmA outputs. See Appendix A for a list of FlexAnalog parameters.
DCMA OUTPUT H1 RANGE — This setting allows selection of the output range. Each DCmA channel can be set independently
to work with different ranges. The three most commonly used output ranges are available.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-417


TRANSDUCER INPUTS/OUTPUTS CHAPTER 5: SETTINGS

DCMA OUTPUT H1 MIN VAL — This setting allows setting the minimum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.
DCMA OUTPUT H1 MAX VAL — This setting allows setting the maximum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.

The DCMA OUTPUT H1 MIN VAL and DCMA OUTPUT H1 MAX VAL settings are ignored for power factor base units (i.e. if
the DCMA OUTPUT H1 SOURCE is set to FlexAnalog value based on power factor measurement).

Three application examples follow.

Example: Power monitoring


A three phase active power on a 13.8 kV system measured via UR-series relay source 1 is to be monitored by the DCmA H1
output of the range of –1 to 1 mA. The following settings are applied on the relay: CT ratio = 1200:5, VT secondary 115, VT
connection is delta, and VT ratio = 120. The nominal current is 800 A primary and the nominal power factor is 0.90. The
power is to be monitored in both importing and exporting directions and allow for 20% overload compared to the nominal.
The nominal three-phase power is:

P = 3 u 13.8 kV u 0.8 kA u 0.9 = 17.21 MW Eq. 5-44

The three-phase power with 20% overload margin is:

P max = 1.2 u 17.21 MW = 20.65 MW Eq. 5-45


5 The base unit for power (refer to the FlexElements section in this chapter for additional details) is:

P BASE = 115 V u 120 u 1.2 kA = 16.56 MW Eq. 5-46

The minimum and maximum power values to be monitored (in pu) are:

– 20.65 MW 20.65 MW
minimum power = -------------------------- = – 1.247 pu, maximum power = ----------------------- = 1.247 pu Eq. 5-47
16.56 MW 16.56 MW

The following settings are entered:


DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAl: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ±0.005 x (1-(-1)) x 20.65 MW = ±0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 × 20 MW + 0.207 MW = 0.407 MW.

Example: Current monitoring


The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current is to be monitored from 0 A upwards, allowing
for 50% overload.
The phase current with the 50% overload margin is:

I max = 1.5 u 4.2 kA = 6.3 kA Eq. 5-48

5-418 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TRANSDUCER INPUTS/OUTPUTS

The base unit for current (see the FlexElements section in this chapter for additional details) is:

I BASE = 5 kA Eq. 5-49

The minimum and maximum power values to be monitored (in pu) are:

0 kA 6.3 kA
minimum current = ---------- = 0 pu, maximum current = -------------- = 1.26 pu Eq. 5-50
5 kA 5 kA

The following settings are entered:


DCMA OUTPUT H2 SOURCE: “SRC 1 Ia RMS”
DCMA OUTPUT H2 RANGE: “4 to 20 mA”
DCMA OUTPUT H2 MIN VAL: “0.000 pu”
DCMA OUTPUT H2 MAX VAL: “1.260 pu”
The worst-case error for this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ±0.005 x (20 - 4) x 6.3 kA = ±0.504 kA
• ±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 × 4.2 kA, 0.001 × 5 kA) + 0.504 kA = 0.515 kA.

Example: Voltage monitoring


A positive-sequence voltage on a 400 kV system measured via source 2 is to be monitored by the DCmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is “Delta.”
The voltage is to be monitored in the range from 70% to 110% of nominal.
The minimum and maximum positive-sequence voltages to be monitored are:

400 kV 400 kV
5
V min = 0.7 u ---------------- = 161.66 kV, V max = 1.1 u ---------------- = 254.03 kV
3 3 Eq. 5-51

The base unit for voltage (see the FlexElements section in this chapter for additional details) is:

V BASE = 0.0664 kV u 6024 = 400 kV Eq. 5-52

The minimum and maximum voltage values to be monitored (in pu) are:

161.66 kV 254.03 kV
minimum voltage = ----------------------- = 0.404 pu, maximum voltage = ----------------------- = 0.635 pu Eq. 5-53
400 kV 400 kV
The following settings are entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”
The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (see the Metering Conventions section in
chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in this
example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 x (1-0) x 254.03 kV = ±1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 × 230.94 kV + 1.27 kV = 2.42 kV.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-419


TESTING CHAPTER 5: SETTINGS

5.13 Testing
5.13.1 IED mode config
SETTINGS  TESTING  IED MODE CONFIG
 IED MODE CONFIG IED MODE: Range: On, Test, Test Blocked
  On

TEST MODE INPUT: Range: FlexLogic operand


 Off

TEST-BLK MODE INPUT: Range: FlexLogic operand


 Off

MODE CTRL VIA MMS: Range: FlexLogic operand


 On (displays with IEC 61850)

CONTACT I/O FORCING: Range: FlexLogic operand


 On

IED MODE TARGET: Range: Enabled, Disabled


 ENABLED

IED BEHAVIOR: Range: On, Test, Test Blocked


 On

The F60 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions
and the Phasor Measurement Unit (PMU, where applicable), using simulated conditions. It is accessible in the software and
5 graphical front panel.
IED MODE — Can be in one of three states: On, Test, or Test Blocked. In UR 7.7 and later, as outlined in the Simulation section
that follows, the UR test mode and GOOSE simulation mode are isolated, and they no longer depend on the mode setting
here.
The On mode is for normal in service operation; the relay protection, control, and communication function is normal. Test
features are disabled, except channel tests and PMU tests remain usable when provided. In On mode, the front panel Test
Mode LED is off.
The Test Blocked mode allows the relay to be placed quickly in a state where the relay cannot negatively impact the power
system or other parts of the substation automation system. This is to allow changing settings, loading new firmware,
changing hardware modules, and changing communication connections. As far as practical all relay output signals are
blocked. Contact outputs are de-energized, latching outputs are frozen. Commands to HardFiber Bricks are blocked. The
test bit of quality attribute of values that can be output via IEC 61850 services is set to "TRUE." The validity bit of the quality
attribute of the data sent via IEC 61850 services is set to "GOOD" if no major error is active. Direct I/O channel tests and
PMU tests are usable on applicable models. In Test Blocked mode, the front panel Test Mode LED is on.
The Test mode is for testing involving forcing relay operation by test signal injection and verifying correct relay output. This
mode is also for tests to verify the relay outputs (both contact and communications) have the intended impact on specific
power system devices or on specific other substation automation devices. Contact outputs can be selectively enabled or
forced as described in the Force Contact Inputs and Force Contact Outputs sections that follow. Shared outputs to Bricks
have their test mode flag raised, which results in their value only being accepted by relays also in forcible Test mode. The
test bit and validity bit of the quality attribute of data sent via IEC 61850 services are set as "TRUE" and "GOOD"
respectively. In Test mode, the front panel Test Mode LED flashes.
Otherwise, the UR remains fully operational while in the Test mode, allowing for various testing procedures. In particular,
the protection and control elements, and FlexLogic function normally. Other than the IEC 61850 protocol, communications
based inputs and outputs remain fully operational. The test procedure must take this into account. Direct I/O channel tests
and PMU tests are usable on applicable models.
When set to Test mode and the operand selected by the CONTACT I/O FORCING setting is "On"
• If the FORCE Cont Ip # setting is set to Open or Closed, the respective quality attribute of the data sent via IEC 61850
services is set to q.source = "substituted"

5-420 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TESTING

• If the FORCE Cont Op # setting is set to Energized, De-energized, or Freeze, the respective quality attribute of the data
sent via IEC 61850 services is set to q.source = "substituted"
When the Breaker Status is substituted manually from a graphical front panel, the respective quality attribute of the
breaker position data sett via IEC 61850 services is set to q.source = "substituted."
The IED MODE setting can be selected through
• Front panel
• EnerVista UR Setup software
• FlexLogic operands
• IEC 61850 control to LLN0.Mod
• "INITIATE TEST MODE ON SIM" setting (under SIMULATION > SUBSCRIBE TO SIMULATED VALUES menu)
TEST MODE INPUT — This setting selects a FlexLogic operand that can put the UR into Test mode as per the logic diagram.
Any FlexLogic operand can be assigned to enable forcible Test mode, that is driven by any remote inputs, logic outputs,
front panel (user-programmable push buttons), and so on.
TEST-BLK MODE INPUT — This setting selects a FlexLogic operand that can put the UR into Test Blocked mode as per the
logic diagram. Any FlexLogic operand can be assigned to enable test isolated mode, that is driven by any remote inputs,
logic outputs, front panel (user-programmable push buttons) and so on.
MODE CTRL VIA MMS — This setting selects a FlexLogic operand for an IEC 61850 client to control the IED mode. When the
operand is low/off, IED mode control from the IEC 61850 client is disabled, and the control request to LLN0.Mod.ctlVal
returns return a negative response. When high/on, IED mode control by an IEC 61850 client is accepted.
CONTACT I/O FORCING — When in Test mode, the operand selected by this setting dictates further response of the UR to
testing conditions, as described in the Force Contact Inputs and Force Contact Outputs sections that follow. When no
operand is specified in this setting, forcing of inputs and outputs during Test mode are not available.
The test mode state is indicated on the relay front panel by a combination of the Test Mode LED indicator, the In-Service 5
LED indicator, and by the critical fail relay, as shown in the table.
IED MODE TARGET — When this setting is Enabled, the corresponding target message of IED Mode Config is displayed on
the front panel when the relay behavior is either TEST or TEST BLOCKED. The target message gets self-reset when the relay
behavior is ON.
When this setting is Disabled, target message is not displayed when the relay behavior is either TEST or TEST BLOCKED.
Table 5-52: Test mode operation
IED MODE In-Service LED Test Mode LED Critical fail relay CONTACT I/O Contact input and output
setting FORCING setting behavior
On Unaffected Off Normal No effect Normal
Test Blocked Off On De-energized No effect Contact outputs disabled
Test Off Flashing De-energized Off Normal
On Controlled by forcing
features

Following a restart or power-up, the CONTACT I/O FORCING setting remains at the last value before restart, but force
contact input and force contact output settings revert to Normal state.
Before uploading settings to the Online Window from the Offline Window of the software, ensure that the settings
in this panel in the Offline Window have been set to required values. Otherwise, undesired relay operation can
occur.

IED BEHAVIOR — Displays the actual behavior of the IED based on different inputs to control the IED MODE. Note that the test
mode can be changed through the front panel, EnerVista software, FlexLogic operands, IEC 61850 control to LLN0.Mod,
and INITIATE TEST MODE ON SIM setting, with the following behavior.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-421


TESTING CHAPTER 5: SETTINGS

Table 5-53: IED fields based on input


Change to IED MODE Behavior
Using front panel IED MODE and IED BEHAVIOR change in software
Using software IED MODE and IED BEHAVIOR change on front panel
Using operand IED MODE does not change in software or front panel, IED BEHAVIOR reflects change
Using INITIATE TEST MODE ON SIM setting IED MODE and IED BEHAVIOR do not change in software or front panel

5.13.1.1 IED mode process


The IED MODE setting is changed to Test or Test Blocked (depending upon the selected setting value for "INITIATE TEST
MODE ON SIM") when the relay is put into simulation mode. After this, the IED MODE is controlled by the TESTING  IED MODE
CONFIG menu.
The IED MODE selection is illustrated in the logic diagram.
The SR Latch that drives the UR into Test mode or On mode are reset-dominant, which means that Test Blocked mode has
the highest priority over Test and On modes, when simultaneous commands are active. For example, if both the FlexLogic
operands assigned to the TEST MODE INPUT and TEST-BLK MODE INPUT settings are ON, then the IED MODE is Test Blocked.
If Any Major error FlexLogic operand is set, then IED MODE is set to Test Blocked.
Following UR restart or power-up, the IED MODE remains latched at the last value, until change is trigged by another input/
command.
When the relay simulation mode is enabled (LPHD.Sim.stVal = TRUE), the "INITIATE TEST MODE ON SIM" setting triggers
respective test mode. If the relay is already in Test or Test Blocked mode, the priority scheme defined in the IED MODE
processing logic decides the resulting IED mode.

5 In summary, enabling the Test or Test Blocked mode in the TESTING  IED MODE CONFIG menu has no impact on the
simulation mode. However, enabling the simulation mode triggers the respective test mode selected by the "INITIATE TEST
MODE ON SIM" setting and the resulting IED mode is decided by the IED MODE process logic diagram. Once the simulation
mode is enabled, the user can switch independently among IED modes using the IED MODE CONFIG settings while the
simulation mode continues.
As shown in the logic diagram, the "INITIATE TEST MODE ON SIM" setting triggers the respective IED mode only when the
relay is entering into simulation mode (meaning on the positive edge trigger of RLY IN SIM MODE FlexLogic operand) or
there is a change in the "INITIATE TEST MODE ON SIM" setting value. Once simulation mode is enabled, any command to
change the IED Mode triggers the respective IED mode. When the simulation mode is disabled, the test mode initiated by
"INITIATE TEST MODE ON SIM" setting resets.

5-422 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TESTING

Figure 5-223: IED mode processing logic


IEC 618 50 protocol
LLN0.Mod.ctlVal = Test
AND

SETTINGS A’’

TEST MODE INPU T: LLN0.Mod.stVal= Test


A
Off=0 SET
OR OR
OR A’ LLN0.Beh.stVal= Test
AND FLEXLOGIC OPERAND
SETTINGS IED Beh Test
IED MODE: SET
OR RES ET
(From front panel o r EnerVista) A’ AND
A
Re set dominant
Test FLEXLOGIC OPERAND
IED Beh Test RES ET
Test-Blo cked FLEXLOGIC OPERAND
Set dominant
IED Beh Test-Blocked
On C

D
OR SIM_Test_Q AND
C’’
A’
D’’

FLEXLOGIC OPERAND
ANY MAJOR ERROR

LLN0.Mod.stVal= Test-Blocked
SETTINGS

TEST-BLK MODE INP UT: C


C’
OR SET LLN0.Beh.stVal= Test-Blo cked
Off=0 OR
FLEXLOGIC OPERAND
AND IED Beh Test-Blo cked
OR
IEC 618 50 protocol OR
LLN0.Mod.ctlVal = Test-Blocked C’’ RES ET
AND Re set dominant
SET

C’ AND
FLEXLOGIC OPERAND
IED Beh Test-Blocked RES ET
Set dominant
A

D AND
OR SIM_Test_Blk_Q
C’
A’’
D’’
IEC 618 50 protocol D LLN0.Beh.stVal= On
LLN0.Mod.ctlVal = On OR SET FLEXLOGIC OPERAND
A
AND D’’ IED Beh On
FLEXLOGIC OPERAND

5
SETTINGS
IED Beh Test-Blocked
MOD E CTRL VIA MMS: OR
FLEXLOGIC OPERAND RES ET
(From front panel o r EnerVista)
IED Beh Test Re set dominant
Off=0

A’’ OR
C’’
FLEXLOGIC OPERAN D
D’’
IED IN SIM MOD E SET
AND

SETTINGS SIM_Test_Q
RES ET
INITIATE TEST MODE ON SIM:
Set dominant
(From front panel o r EnerVista)
Disabled SET

Test SIM_Test_Blk_Q
AND
Test-Blocked RES ET
Set dominant
Legend:
FLEXLOGIC OPERAN D OR Rising edge trigger.
IED IN SIM MOD E Ho lds state for one pass.

859 785A1.vsdx

5.13.2 Force contact inputs


SETTINGS  TESTING  FORCE CONTACT INPUTS
 FORCE CONTACT FORCE Cont Ip 1 Range: Normal, Open, Closed
 INPUTS  Normal

FORCE Cont Ip 2 Range: Normal, Open, Closed


 Normal

FORCE Cont Ip xx Range: Normal, Open, Closed
 Normal

The force contact inputs feature provides a method of performing checks on the function of all contact inputs.
While in Test mode, the relay contact inputs can be pre-programmed to respond in the following ways:

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-423


TESTING CHAPTER 5: SETTINGS

• If set to “Normal,” the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. Select this value if a given input must be operational during the test. This
includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open,” the input is forced to report as opened (Logic 0) while the operand selected by CONTACT I/O FORCING
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
• If set to “Closed,” the input is forced to report as closed (Logic 1) while the operand selected by CONTACT I/O FORCING
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.

Following a restart or power-up, the CONTACT I/O FORCING setting remains at the last value before restart, but force
contact input and force contact output settings revert to Normal state.

5.13.3 Force contact outputs


SETTINGS  TESTING  FORCE CONTACT OUTPUTS
 FORCE CONTACT FORCE Cont Op 1 Range: Normal, Energized, De-energized, Freeze
 OUTPUTS  Normal

FORCE Cont Op 2 Range: Normal, Energized, De-energized, Freeze


 Normal

FORCE Cont Op xx Range: Normal, Energized, De-energized, Freeze

5 Normal

The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
While in Test mode, the relay contact outputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the contact output remains fully operational. It operates when its control operand is logic 1 and
resets when its control operand is logic 0.
• If set to “Energized,” the output closes and remains closed while the operand selected by the CONTACT I/O FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “De-energized,” the output opens and remains opened while the operand selected by the CONTACT I/O
FORCING setting is On, regardless of the status of the operand configured to control the output contact. While the
selected operand is Off, the output behaves as it does when in service.
• If set to “Freeze,” the output retains its position at the instant before the IED MODE was Test and the operand selected
by the CONTACT I/O FORCING setting was On, regardless of later changes in the status of the operand configured to
control the output contact. While the selected operand is Off, the output behaves as it does when in service.

Following a restart or power-up, the CONTACT I/O FORCING setting remains at the last value before restart, but force
contact input and force contact output settings revert to Normal state.

5.13.4 Phasor Measurement Unit test values


SETTINGS  TESTING  PMU TEST VALUES  PMU 1 TEST VALUES
 PMU 1 PMU 1 TEST Range: Enabled, Disabled
 TEST VALUES  FUNCTION: Disabled

PMU 1 VA TEST Range: 0.00 to 700.00 kV in steps of 0.01


 MAGNITUDE: 500.00 kV

5-424 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS TESTING

PMU 1 VA TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 VB TEST Range: 0.00 to 700.00 kV in steps of 0.01


 MAGNITUDE: 500.00 kV

PMU 1 VB TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: –120.00°

PMU 1 VC TEST Range: 0.00 to 700.00 kV in steps of 0.01


 MAGNITUDE: 500.00 kV

PMU 1 VC TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: 120.00°

PMU 1 VX TEST Range: 0.00 to 700.00 kV in steps of 0.01


 MAGNITUDE: 500.00 kV

PMU 1 VX TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 IA TEST Range: 0.000 to 9.999 kA in steps of 0.001


 MAGNITUDE: 1.000 kA

PMU 1 IA TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: –10.00°

PMU 1 IB TEST Range: 0.000 to 9.999 kA in steps of 0.001


 MAGNITUDE: 1.000 kA

PMU 1 IB TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: –130.00°

 PMU 1 IC TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001 5
PMU 1 IC TEST Range: –180.00 to 180.00° in steps of 0.05
 ANGLE: 110.00°

PMU 1 IG TEST Range: 0.000 to 9.999 kA in steps of 0.001


 MAGNITUDE: 0.000 kA

PMU 1 IG TEST Range: –180.00 to 180.00° in steps of 0.05


 ANGLE: 0.00°

PMU 1 TEST Range: 20.000 to 70.000 Hz in steps of 0.001


 FREQUENCY: 60.000 Hz

PMU 1 TEST Range: –10.00 to 10.00 Hz/s in steps of 0.01


 df/dt: 0.00 Hz/s

The relay must be in test mode to use the PMU test mode. That is, the TESTING  TEST MODE FUNCTION setting must be
“Enabled,” and the TESTING  TEST MODE INITIATE initiating signal must be “On.”
During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of
frequency are substituted with user values, while the symmetrical components are calculated from the physical channels.
The test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-
programmable digital channels to signal the IEEE C37.118 client that test values are being sent in place of the real
measurements.
The UR Synchrophasor Implementation defines a test mode that sends a pre-defined set of synchrophasors out over the
communication channel when the test mode function setting is enabled. In test mode, the following actions take place:
• The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set
• The Sim bit in all output datasets is set

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-425


SIMULATION CHAPTER 5: SETTINGS

5.14 Simulation
SETTINGS  SIMULATION
 SETTINGS  SUBSCRIBE TO See below
 SIMULATION   SIMULATED VALUES

 PUBLISH See page 5-428


  SIMULATED VALUES

5.14.1 Subscribe to simulated values


SETTINGS  SIMULATION  SUBSCRIBE TO SIMULATED VALUES
 SUBSCRIBE TO SIMULATION MODE: Range: Disabled, Enabled
 SIMULATED VALUES  Disabled

SIM MODE INPUT: Range: FlexLogic operand


 Off

SIM CTRL VIA MMS: Range: FlexLogic operand


 On

INITIATE TEST MODE Range: Disabled, Test, Test-Blocked


 ON SIM: Test-Blocked

SIM MODE TARGET: Range: Enabled, Disabled


 Enabled

5  SIM MODE EVENTS:


Disabled
Range: Disabled, Enabled

SIMULATION MODE Range: Disabled, Enabled


 STATUS: Disabled

The F60 is provided with optional IEC 61850 communications that include simulation. The option is specified at
the time of ordering. The field reads "Unavailable" when IEC 61850 is not present.

Prior to UR 7.7, when the UR TEST MODE FUNCTION is set to "Test Blocked" or "Test," the sim bit in the header of all
transmitted GOOSE messages is set to "TRUE," so that the UR plays the simulator role during the testing and
commissioning phases. The "Sim" data attribute in the relay is set (<MasterLD>/LPHD1.Sim.stVal = TRUE), so that if GOOSE
messages are received with the "simulation" flag set, these are used in place of the normal messages. The quality attribute
values that are transmitted via GOOSE services are set to "valid" + "test."
In UR 7.7 and later, the UR test mode and GOOSE simulation mode are isolated. The sim bit in the transmitted GOOSE
messages and the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.stVal) are controlled via new Modbus settings and MMS
control requests. They no longer depend on the UR TEST MODE FUNCTION or IED MODE.
The settings also display in the software when the F60 is set to IEC 61850 Edition 2. When using IEC 61850 Edition 1, the
settings are read-only.
SIMULATION MODE — When set to Disabled, the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.StVal) is set to False and the
GOOSE/SV messages received with simulation flag/bit set are ignored.
When set to Enabled, the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.StVal) is set to True, so that if GOOSE/SV messages
are received with the "simulation" flag/bit set, these are used in place of the normal messages.
SV messages has a simulation bit in the Reserved 1 field.
SIM MODE INPUT — This setting selects a FlexLogic operand. When set, the relay Simulation mode is enabled and, if the
messages (either GOOSE or SV) are received with the simulation bit true, messages from simulation devices are used in
place of actual messages. Any FlexLogic operand can be assigned to enable simulation mode, that is, driven by any
remote inputs, logic outputs, front panel (user-programmable pushbuttons), and so on.

5-426 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 5: SETTINGS SIMULATION

SIM CTRL VIA MMS — This setting selects a FlexLogic operand for the IEC 61850 client to control the simulation mode.
When set to Off, simulation mode selection via IEC 61850 client is disabled and control request to LPHD.Sim.ctlVal returns
return negative response.
When set to On, simulation mode selection via IEC 61850 client is accepted.
This setting can be set from the front panel, EnerVista UR Setup software, FlexLogic operand, and IEC61850 control to
LPHD.Sim.ctlVal.
INITIATE TEST MODE ON SIM — This setting initiates the selected test mode when simulation mode is enabled.
When set to Disabled, any command (from an IEC 61850 client, front panel, or Flex Operand) to set the simulation mode
enables the Sim mode irrespective of the current IED mode.
When set to Test or Test-Blocked, any command to set the simulation mode selects respective test mode, if the relay is not
already in Test or Test-Blocked mode. If the relay is already in Test or Test-Blocked mode by any user command (from IEC
61850 client, front panel, or Flex Operand), the respective priority defined in test mode processing decides the resultant
test mode.
In summary, enabling the Test or Test-Blocked mode via the IED MODE setting (from front panel or EnerVista), via a
IEC61850 client command to LLN0.Mod.ctlVal, or via TEST MODE INPUT and TEST-BLK MODE INPUT settings (FlexLogic
operands) has no impact on the simulation mode. However, enabling the simulation mode using the SIMULATION MODE
setting (from front panel or EnerVista), via an IEC61850 client command to LPHD.Sim.ctlVal, or via SIM MODE INPUT setting
(FlexLogic operand) enables the selected test mode by the INITIATE TEST MODE ON SIM setting. A user can independently
disable the test or test-blocked mode by any specified command type, but the relay simulation mode continues and
accepts the simulated values in place of actual values until the simulation mode is disabled.
SIM MODE TARGET — When this setting is Enabled, a target message ‘IED IN SIM MODE’ is displayed on the front panel when
the relay is in Simulation mode. The target message gets self-reset when the relay exits the Simulation mode.
When this setting is Disabled, target message is not displayed when the relay is in Simulation mode.
SIM MODE EVENT — This setting is used to control whether the change in Simulation mode of relay is recorded in the event
5
recorder. When this setting is Enabled, the event showing the change in the status of Simulation is recorded. If this setting
is Disabled, the events related to Simulation mode are not recorded.
SIMULATION MODE STATUS — This is an actual value that indicates the present simulation mode of the relay.

Figure 5-224: Simulation mode logic


SETTINGS
SIMULATION MODE:
(From front panel or EnerVista)

Enabled=1

A
OR
SETTINGS
SIM MODE INPUT:
FLEXLOGIC OPERAND
Off=0 IED IN SIM MODE OFF

FLEXLOGIC OPERAND
OR IED IN SIM MODE ON
From IEC 61850 protocol
LPHD1.Sim.ctlVal = TRUE
LPHD1.Sim.stVal

SETTINGS
AND SET
SIM CTRL VIA MMS:
(From front panel or EnerVista)
A
Enabled=1 RESET
OR
Set dominant

From IEC 61850 protocol AND


LPHD1.Sim.ctlVal = FALSE
859831A1.vsdx

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-427


SIMULATION CHAPTER 5: SETTINGS

5.14.2 Publish simulated values


SETTINGS  SIMULATION  PUBLISH SIMULATED VALUES
 PUBLISH TxGOOSE SIM MODE: Range: Disabled, Enabled
 SIMULATED VALUES  Disabled

SIM Q.VALIDITY: Range: NONE, GOOD, INVALID, QUESTIONABLE


 NONE

SIM Q.TEST: Range: NONE, TRUE, FALSE


 NONE

TxGOOSE SIM MODE — When set to Disabled, the sim bits in all transmitted GOOSE messages are set to FALSE.
When set to Enabled, the sim bits in all transmitted GOOSE messages are set to TRUE.
This setting can be modified through the front panel, EnerVista UR Setup software, IEC 61850 client control to <MasterLD>/
LPHD1.TxGoSim.
SIM Q.VALIDITY — This setting simulates the validity bits of the quality attribute values included in all transmitted GOOSE
messages. When set to NONE, the q.Validity bits are set based on the logical node behavior value. When set to any other
value, the q.Validity bits of quality attributes included in all transmitted GOOSE messages are set to the selected value.
This setting is used when TxGOOSE SIM MODE is set to Enabled. It can be modified through the front panel and EnerVista UR
Setup software.
SIM Q.TEST — This setting simulates the Test bit of the quality attribute values included in all transmitted GOOSE messages.
When set to NONE, the q.Test bit is set based on the relay TEST MODE FUNCTION / IED MODE. When set to any other value,
the q.Test bit of quality attributes included in all transmitted GOOSE messages is set to the selected value.
This setting is used when TxGOOSE SIM MODE is set to Enabled. It can be modified through the front panel and EnerVista UR
5 Setup software.

5-428 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 6: Actual values

Actual values

This chapter outlines viewing of data on the front panel, software, and/or web browser.

6.1 Actual Values menu

 ACTUAL VALUES  Access in EnerVista


 FRONT PANEL   See page 6-4

 ACTUAL VALUES  IED See page 6-5
 STATUS  

 CONTACT INPUTS See page 6-5


  

 VIRTUAL INPUTS See page 6-5


 

 RxGOOSE BOOLEANS See page 6-6


 

 RxGOOSE DPS See page 6-6


 

 TELEPROTECTION See page 6-6


  INPUTS

 CONTACT OUTPUTS See page 6-7


 

 VIRTUAL OUTPUTS See page 6-7


 

 AUTORECLOSE See page 6-8


 

 RxGOOSE STATUS See page 6-7


 

 RxGOOSE See page 6-7


  STATISTICS

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-1


ACTUAL VALUES MENU CHAPTER 6: ACTUAL VALUES

 DIGITAL COUNTERS See page 6-8


 

 BREAKER STATUS See page 6-8


 

 SELECTOR SWITCHES See page 6-9


 

 FLEX STATES See page 6-9


 

 ETHERNET See page 6-9


 

 REAL TIME CLOCK See page 6-10


  SYNCHRONIZING

 HIZ STATUS See page 6-11


 

 DIRECT INPUTS See page 6-11


 

 DIRECT DEVICES See page 6-11


  STATUS

 EGD PROTOCOL See page 6-12


  STATUS

 TELEPROT CH TESTS See page 6-12


 

 INCIPIENT FAULT See page 6-13


 

 COMM STATUS See page 6-13


  REMAINING CONNECT

 PRP STATUS See page 6-13



6 

 TxGOOSE STATUS See page 6-14


 

 PROTOCOL See page 6-14


  

 ACTUAL VALUES  SOURCE SRC 1 See page 6-19


 METERING  
 
 SOURCE SRC 4
 

 SENSITIVE See page 6-25


  DIRECTIONAL POWER

 SYNCHROCHECK See page 6-25


 

 TRACKING FREQUENCY See page 6-26


 

 FREQUENCY RATE See page 6-26


  OF CHANGE 1

 FREQUENCY RATE
  OF CHANGE 2

6-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES ACTUAL VALUES MENU

 FLEXELEMENTS See page 6-26


 

 RxGOOSE Analogs See page 6-27


 

 WATTMETRIC See page 6-27


  GROUND FAULT 1

 WATTMETRIC
  GROUND FAULT 2

 PHASOR MEASUREMENT See page 6-27


  UNIT

 PMU AGGREGATOR See page 6-28


 

 RESTRICTED GROUND See page 6-28


  FAULT CURRENTS

 TRANSDUCER I/O See page 6-29


  DCMA INPUTS

 TRANSDUCER I/O See page 6-29


  RTD INPUTS

 HARMONIC See page 6-29


   DETECTION

 ACTUAL VALUES  FIELD UNIT U1 See page 6-29


 REMOTE RESOURCES   ID: U 1

 FIELD UNIT U8
   ID: U 8

 ACTUAL VALUES  GENERAL STATUS See page 6-30


 PB MODULE  

   RxSV Status

See page 6-30 6
 TIME SYNC See page 6-31
  

 ACTUAL VALUES  FAULT REPORT See page 6-33


 RECORDS  

 EVENT RECORDS See page 6-34


  

 OSCILLOGRAPHY See page 6-36


 

 DATA LOGGER See page 6-36


 

 PMU See page 6-37


  RECORDS

 MAINTENANCE See page 6-37


 

 HIZ RECORDS See page 6-38


  

 ACTUAL VALUES  MODEL INFORMATION See page 6-39


 PRODUCT INFO  

 FIRMWARE REVISIONS See page 6-39


 

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-3


FRONT PANEL CHAPTER 6: ACTUAL VALUES

For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.

6.2 Front panel


6.2.1 Enhanced and basic front panels
The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the
front panel. Settings cannot be changed in this interface.
To view the front panel in EnerVista software:
1. Click Actual Values > Front Panel.
2. Click the pushbutton or LCD area to enlarge it.
Figure 6-1: Front panel use in the software (C60 shown)

6.2.2 Graphical front panel


The graphical front panel is a hardware option.

Annunciator alarms can be acknowledged and reset, and LEDs and pushbuttons can be viewed.
To view alarms for the graphical front panel in EnerVista:
1. Access Actual Values > Graphical Panel > Annunciator Panel. Alarms are listed, allowing remote acknowledgement/
reset.
2. Click the Acknowledge or Reset button for an alarm.

6-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES STATUS

Figure 6-2: Annunciator alarms displayed in the software)

To view LEDs and pushbuttons on the graphical front panel in EnerVista:


1. Access Actual Values > Graphical Panel > LEDs or Pushbuttons. The window displays.

6.3 Status
6.3.1 IED
ACTUAL VALUES  STATUS  IED
 IED IED BEHAVIOUR: Range: On, Test, Test Blocked
  On

SIMULATION MODE Range: Disabled, Enabled


 STATUS: Disabled Displays with IEC 61850

IED BEHAVIOUR — Displays the SETTINGS  TESTING  IED MODE CONFIG  IED MODE value.
SIMULATION MODE STATUS — Displays the SETTINGS  SIMULATION  SUBSCRIBE TO SIMULATED VALUES  SIMULATION MODE
value, meaning if simulation mode is enabled or disabled on a device.

6
6.3.2 Contact inputs
ACTUAL VALUES  STATUS  CONTACT INPUTS
 CONTACT INPUTS Cont Ip 1 Range: On, Off
  Off

Cont Ip xx Range: On, Off
 Off

The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.

6.3.3 Virtual inputs


ACTUAL VALUES  STATUS  VIRTUAL INPUTS
 VIRTUAL INPUTS Virt Ip 1 Range: On, Off
  Off

Virt Ip 128 Range: On, Off
 Off

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-5


STATUS CHAPTER 6: ACTUAL VALUES

The present status of the 128 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.

6.3.4 RxGOOSE boolean inputs


ACTUAL VALUES  STATUS  RxGOOSE BOOLEANS
 RxGOOSE BOOLEANS RxGOOSE BOOLEAN 1 Range: On, Off
  STATUS: Off

RxGOOSE BOOLEAN 256 Range: On, Off
 STATUS: Off

This menu displays when the product includes an IEC 61850 software option.

6.3.5 RxGOOSE DPS inputs


ACTUAL VALUES  STATUS  RxGOOSE DPS
 RxGOOSE DPS RxGOOSE DPS 1 Range: On, Off, intermediate, Bad
  Status: intermediate

RxGOOSE DPS 16 Range: On, Off, intermediate, Bad
 Status: intermediate

This menu displays when the product includes an IEC 61850 software option.
6
6.3.6 Teleprotection inputs
ACTUAL VALUES  STATUS  TELEPROTECTION INPUTS
 TELEPROTECTION TELEPROTECTION Range: On, Off
 INPUTS  INPUT 1-1: Off

TELEPROTECTION Range: On, Off
 INPUT 1-16: Off

TELEPROTECTION Range: On, Off


 INPUT 2-1: Off

TELEPROTECTION Range: On, Off
 INPUT 2-16: Off

The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed is
that of corresponding remote output unless the channel is declared failed.

6-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES STATUS

6.3.7 Contact outputs


ACTUAL VALUES  STATUS  CONTACT OUTPUTS
 CONTACT OUTPUTS Cont Op 1 Range: On, Off, VOff, VOn, IOn, IOff
  Off

Cont Op xx Range: On, Off, VOff, VOn, IOn, IOff
 Off

The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.

6.3.8 Virtual outputs


ACTUAL VALUES  STATUS  VIRTUAL OUTPUTS
 VIRTUAL OUTPUTS Virt Op 1 Range: On, Off
  Off

Virt Op 256 Range: On, Off
 Off

The present state of each virtual output displays here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.

6.3.9 RxGOOSE status


ACTUAL VALUES  STATUS  RxGOOSE STATUS
6
 RxGOOSE All RxGOOSE Online: Range: Yes, No
 STATUS  Yes

RxGOOSE 1 Status: Range: Online, Offline


 Offline

RxGOOSE 64 Status: Range: Online, Offline
 Offline

This menu displays when the product includes an IEC 61850 software option.

The All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.

6.3.10 RxGOOSE statistics


ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
 RxGOOSE 1 RxGOOSE 1 Range: 0 up to 4,294,967,295
  stNum 0

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-7


STATUS CHAPTER 6: ACTUAL VALUES

RxGOOSE 1 Range: 0 up to 4,294,967,295


 sqNum 0

This menu displays when the product includes an IEC 61850 software option.

stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.

6.3.11 Autoreclose
ACTUAL VALUES  STATUS  AUTORECLOSE  AUTORECLOSE 1(4)
 AUTORECLOSE 1 AUTORECLOSE 1 Range: 0, 1, 2, 3, 4
  SHOT COUNT: 0

This menu displays the reclosure shot count.

6.3.12 Digital counters


ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS Counter 1 ACCUM:
 Counter 1  0

Counter 1 FROZEN:
 0

6  Counter 1 FROZEN:
1970/01/01 00:00:00
Range: YYYY/MM/DD HH:MM:SS

Counter 1 MICROS: Range: 0 to 4294967295 in steps of 1


 0

The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.

6.3.13 Breaker status


ACTUAL VALUES  STATUS  BREAKERS
 BREAKERS BREAKER 1 ΦA/3P STATE: Range: N/A, Opened, Closed, Alert
  N/A

BREAKER 1 ΦB STATE: Range: N/A, Opened, Closed, Alert


 N/A

BREAKER 1 ΦC STATE: Range: N/A, Opened, Closed, Alert


 N/A

BREAKER x ΦA/3P STATE: Range: N/A, Opened, Closed, Alert
 N/A

BREAKER x ΦB STATE: Range: N/A, Opened, Closed, Alert


 N/A

6-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES STATUS

BREAKER 1 ΦC STATE: Range: N/A, Opened, Closed, Alert


 N/A

“N/A” is shown when BREAKER 1 FUNCTION is “Disabled”.


“Closed” is shown when the breaker is closed.
“Opened” is shown when the breaker is opened.
“Alert” is the state that represents one of the following breaker conditions:
– Bad
– Intermediate
– Racked-out
– Out of Service
– Pole Discrepancy
– Trouble

6.3.14 Selector switches


ACTUAL VALUES  STATUS  SELECTOR SWITCHES
 SELECTOR SWITCHES SELECTOR SWITCH 1 Range: Current Position / 7
  POSITION: 0/7

SELECTOR SWITCH 2 Range: Current Position / 7


 POSITION: 0/7

The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.

6.3.15 Flex States


ACTUAL VALUES  STATUS  FLEX STATES
 FLEX STATES PARAM 1: Off Range: On, Off
6
  Off

PARAM 256: Off Range: On, Off
 Off

There are 256 FlexStateTM bits available. The second line value indicates the state of the given FlexState bit.

6.3.16 Ethernet
ACTUAL VALUES  STATUS  ETHERNET
 ETHERNET ETHERNET PRI LINK Range: Fail, OK
  STATUS: Fail

ETHERNET SEC LINK Range: Fail, OK


 STATUS: OK

ETHERNET TER LINK Range: Fail, OK


 STATUS: Fail

These values indicate the status of the first, second, and third Ethernet ports.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-9


STATUS CHAPTER 6: ACTUAL VALUES

6.3.17 Real time clock synchronizing


ACTUAL VALUES  PROCESS BUS MODULE  TIME SYNC
 REAL TIME CLOCK RTC SYNC SOURCE: Range: None, Port 1(3) PTP Clock, IRIG-B, Other,
 SYNCHRONIZING  None Process Bus Module Clock, SNTP1, SNTP2

GRANDMASTER ID: Range: any 8 octet value


 0000000000000000

ACCURACY: Range: 0 to 999,999,999 ns


 999999999 ns

PBM SW1 PTP State: Range: Disabled, No Signal, Calibrating, Synchro-


 DISABLED nized, Qualifying, Idea, Master

PBM SW2 PTP State: Range: Disabled, No Signal, Calibrating, Synchro-


 DISABLED nized, Qualifying, Idea, Master

PORT 1 PTP STATE: Range: Disabled, No Signal, Calibrating, Synch’d (No


 No Signal Pdelay), Synchronized

PORT 2 PTP STATE: Range: Disabled, No Signal, Calibrating, Synch’d (No


 No Signal Pdelay), Synchronized

PORT 3 PTP STATE: Range: Disabled, No Signal, Calibrating, Synch’d (No


 No Signal Pdelay), Synchronized

PTP - IRIG-B DELTA: Range: -500,000,000 to +500,000,000 ns


 500000000 ns

This menu displays when the product includes an IEEE 1588 software option.

RTC SYNC SOURCE — The time synchronizing source the relay is using at present. Possible sources include Port 1 PTP Clock
to Port 3 PTP Clock. A value of Other means a less precise source (IEC 103, IEC 104, Modbus, DNP). An actual value displays
6 when the relay includes the IEEE 1588 software option.
GRANDMASTER ID — The grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
ACCURACY — The estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE — The present state of the port’s PTP clock. The PTP clock state is:
• Disabled if the port’s function setting is Disabled
• No Signal if enabled but no signal from an active master has been found and selected
• Calibrating if an active master has been selected but lock is not at present established
• Synch’d (No Pdelay) if the port is synchronized, but the peer delay mechanism is non-operational
• Synchronized if synchronized
PTP - IRIG-B DELTA — The time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-
B time.

6-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES STATUS

6.3.18 Hi-Z status


ACTUAL VALUES  STATUS  HIZ STATUS
 HIZ STATUS HIZ STATUS: Range: Normal, Coordination Timeout, Armed,
  NORMAL Arcing, Down Conductor

ARC CONFIDENCE A:100


 B:100 C:100 N:100 %

The current status of high-impedance fault detection element displayS here. The arc fault detection confidence also
displays.

6.3.19 Direct inputs


ACTUAL VALUES  STATUS  DIRECT INPUTS
 DIRECT INPUTS AVERAGE MSG RETURN
  TIME CH1: 0 ms

UNRETURNED MSG
 COUNT CH1: 0

CRC FAIL COUNT


 CH1: 0

AVERAGE MSG RETURN


 TIME CH2: 0 ms

UNRETURNED MSG
 COUNT CH2: 0

CRC FAIL COUNT


 CH2: 0

DIRECT INPUT 1
 On
 6
DIRECT INPUT 32
 On

The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts can indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT values represent the state of each direct input.

6.3.20 Direct devices status


ACTUAL VALUES  STATUS  DIRECT DEVICES STATUS
 DIRECT DEVICES DIRECT DEVICE 1 Range: Offline, Online
 STATUS  STATUS: Offline

DIRECT DEVICE 16 Range: Offline, Online
 STATUS: Offline

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-11


STATUS CHAPTER 6: ACTUAL VALUES

These actual values represent the state of direct devices 1 through 16.

6.3.21 EGD protocol status

6.3.21.1 Fast exchange


ACTUAL VALUES  STATUS  EGD PROTOCOL STATUS  PRODUCER STATUS  FAST EXCHANGE 1
 FAST EXCHANGE 1 FAST EXCHANGE 1
  SIGNATURE: 0

FAST EXCHANGE 1
 DATA LENGTH: 0

These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet size
for the fast EGD exchange display.

6.3.21.2 Slow exchange


ACTUAL VALUES  STATUS  EGD PROTOCOL STATUS  PRODUCER STATUS  SLOW EXCHANGE 1(2)
 SLOW EXCHANGE 1 SLOW EXCHANGE 1
  SIGNATURE: 0

SLOW EXCHANGE 1
 DATA LENGTH: 0

These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD
exchanges display.

6.3.22 Teleprotection channel tests


ACTUAL VALUES  STATUS  TELEPROT CH TESTS

6  TELEPROT CH TESTS
  CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK

CHANNEL 1 LOST Range: 1 to 65535 in steps of 1


 PACKETS: 1

CHANNEL 2 Range: n/a, FAIL, OK


 STATUS: n/a

CHANNEL 2 LOST Range: 1 to 65535 in steps of 1


 PACKETS: 1

VALIDITY OF CHANNEL Range: n/a, FAIL, OK


 CONFIGURATION: FAIL

The status information for two channels is shown here.


CHANNEL 1 STATUS — This represents the receiver status of each channel. If the value is “OK,” teleprotection is enabled and
data is being received from the remote terminal; If the value is “FAIL,” teleprotection enabled and data is not being received
from the remote terminal. If “n/a,” teleprotection is disabled.
CHANNEL 1 LOST PACKETS — Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle.
The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS  CLEAR RECORDS menu.
VALIDITY OF CHANNEL CONFIGURATION — This value displays the current state of the communications channel identification
check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the “FAIL” message
displays. The “N/A” value appears if the local relay ID is set to a default value of “0,” the channel is failed, or if the
teleprotection inputs/outputs are not enabled.

6-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES STATUS

6.3.23 Incipient fault detector


ACTUAL VALUES  STATUS  INCIPIENT FAULT  INCIPIENT FAULT 1(2)
 INCIPIENT FAULT 1 INCIPIENT FAULT 1 Range: 0 to 65535 in steps of 1
  PH A FAULTS: 0

INCIPIENT FAULT 1 Range: 0 to 65535 in steps of 1


 PH B FAULTS: 0

INCIPIENT FAULT 1 Range: 0 to 65535 in steps of 1


 PH C FAULTS: 0

The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the COMMANDS  CLEAR RECORDS  CLEAR INCIPENT FAULT COUNTERS command.

6.3.24 Remaining connection status


ACTUAL VALUES  STATUS  COMM STATUS REMAINING CONNECT
 COMM STATUS MMS TCP (max 5) Range: 0 to 5
 REMAINING CONNECT  5

Modbus TCP (max 4) Range: 0 to 4


 4

DNP TCP (max 2) Range: 0 to 2


 2

IEC-104 TCP (max 2) Range: 0 to 2


 2

PMU TCP Range: 1 to 4


 1

SFTP (max 4) Range: 0 to 4


 4

These values specify the remaining number of TCP connections still available for each protocol. The display depends on the 6
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
MMS TCP — The number of IEC 61850 connections remaining.
PMU TCP — The maximum number of PMU TCP connections matches the number of aggregators. The maximum number of
aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with a
PMU. The remaining number of aggregators displays here.

6.3.25 Parallel Redundancy Protocol (PRP)


The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES  STATUS  PRP STATUS
 PRP STATUS Total Rx Port A: Range: 0 to 4G, blank if PRP disabled
  0

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-13


STATUS CHAPTER 6: ACTUAL VALUES

Total Rx Port B: Range: 0 to 4G, blank if PRP disabled


 0

Mismatches Port A: Range: 0 to 4G, blank if PRP disabled


 0

Mismatches Port B: Range: 0 to 4G, blank if PRP disabled


 0

Total Errors: Range: 0 to 4G, blank if PRP disabled


 0

This menu displays when the product includes a PRP software option.

Total Received Port A is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).

6.3.26 TxGOOSE status


ACTUAL VALUES  STATUS  TxGOOSE STATUS
 TxGOOSE STATUS R-TxGOOSE 1 Range: On, Off
  ARP: Off

6  R-TxGOOSE 16
ARP: Off
Range: On, Off

This menu displays when the product includes an IEC 61850 software option.

This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
ARP — The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.

6.3.27 Protocol
ACTUAL VALUES  STATUS  PROTOCOL
 PROTOCOL IEC61850 EDITION: Range: Edition1, Edition2
  Edition2

6-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

This menu displays when the product includes an IEC 61850 software option.

Displays the IEC 61850 edition currently being used, as set under Settings > Product Setup > Communications > Protocol
> IEC61850 SCL Edition. This value displays only on the front panel.

6.4 Metering
6.4.1 Metering conventions

6.4.1.1 UR convention for measuring power and energy


The figure illustrates the conventions established for use in UR devices.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-15


METERING CHAPTER 6: ACTUAL VALUES

Figure 6-3: Flow direction of signed values for watts and VARs
PER IEEE CONVENTIONS
Generator
Parameters as seen by
G the UR-series relays

Voltage +Q
VCG
Watts = Positive IC
PF = Lead PF = Lag
Vars = Positive
PF = Lag IA
VAG –P +P
Current IB IA
PF = Lag PF = Lead
UR-SERIES IED
VBG
–Q
M LOAD –Θ1°
Inductive Resistive S=VI

Generator
G

VCG +Q
Voltage
PF = Lead PF = Lag
Watts = Positive IA
Vars = Negative IC
PF = Lead VAG –P +P
IA
Current
PF = Lag PF = Lead
IB
UR-SERIES IED
VBG –Q

S=VI
LOAD
–Θ2°
Resistive

Inductive Resistive
M LOAD

VCG +Q

Voltage PF = Lead PF = Lag


IB
IA
Watts = Negative
Vars = Negative VAG –P +P
PF = Lag

6
IA
IC PF = Lag PF = Lead
Current
VBG
–Q
UR-SERIES IED
G S=VI
–Θ3°
Generator
Resistive
LOAD

+Q
VCG
Voltage IB
PF = Lead PF = Lag
Watts = Negative IA
Vars = Positive VAG –P +P
PF = Lead
IA IC

Current PF = Lag PF = Lead


VBG
UR-SERIES IED –Q
G S=VI
–Θ4°
Generator 827239AC.CDR

6.4.1.2 UR convention for measuring phase angles


All phasors calculated by URs and used for protection, control and metering functions are rotating phasors that maintain
the correct phase angle relationships with each other at all times.
For display and oscillography purposes, all phasor angles in a given relay are referred to an AC input channel pre-selected
by the SETTINGS  SYSTEM SETUP  POWER SYSTEM  FREQUENCY AND PHASE REFERENCE setting. This setting defines a
particular AC signal source to be used as the reference.

6-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

The relay first determines if any “Phase VT” bank is indicated in the source. If it is, voltage channel VA of that bank is used
as the angle reference. Otherwise, the relay determines if any “Aux VT” bank is indicated; if it is, the auxiliary voltage
channel of that bank is used as the angle reference. If neither of the two conditions is satisfied, then two more steps of this
hierarchical procedure to determine the reference signal include “Phase CT” bank and “Ground CT” bank.
If the AC signal pre-selected by the relay upon configuration is not measurable, the phase angles are not referenced. The
phase angles are assigned as positive in the leading direction, and are presented as negative in the lagging direction, to
more closely align with power system metering conventions. The figure illustrates this.
Figure 6-4: UR phase angle measurement convention
-270o

-225o -315o

positive
angle
direction

-180o 0o
UR phase angle
reference

-135o -45o

-90o
827845A1.CDR

6.4.1.3 UR convention for symmetrical components


The URs calculate voltage symmetrical components for the power system phase A line-to-neutral voltage, and
symmetrical components of the currents for the power system phase A current. Owing to the above definition, phase 6
angle relations between the symmetrical currents and voltages stay the same irrespective of the connection of instrument
transformers. This is important for setting directional protection elements that use symmetrical voltages.
For display and oscillography purposes the phase angles of symmetrical components are referenced to a common
reference as described in the previous sub-section.

WYE-connected instrument transformers


• ABC phase rotation: • ACB phase rotation:

1 1
V_0 = -- V AG + V BG + V CG V_0 = -- V AG + V BG + V CG
3 3
1 2 1 2
V_1 = -- V AG + aV BG + a V CG V_1 = -- V AG + a V BG + aV CG
3 3
1 2 1 2
V_2 = -- V AG + a V BG + aV CG V_2 = -- V AG + aV BG + a V CG
3 3

The above equations apply to currents as well.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-17


METERING CHAPTER 6: ACTUAL VALUES

DELTA-connected instrument transformers


• ABC phase rotation: • ACB phase rotation:

V_0 = N/A V_0 = N/A


1 ‘– 30 q 2 1 ‘30q 2
V_1 = ------------------ V AB + aV BC + a V CA V_1 = --------------- V AB + a V BC + aV CA
3 3 3 3
1 ‘30q 2 1 ‘– 30 q 2
V_2 = --------------- V AB + a V BC + aV CA V_2 = ------------------ V AB + aV BC + a V CA
3 3 3 3

The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6-1: Symmetrical components calculation example
SYSTEM VOLTAGES, sec. V * VT conn. relay INPUTS, sec. V SYMM. COMP, sec. V
VAG VBG VCG VAB VBC VCA F5ac F6ac F7ac V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
∠0° ∠–125° ∠–250° ∠–313° ∠–97° ∠–241° ∠0° ∠–125° ∠–250° ∠–192° ∠–7° ∠–187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) ∠0° ∠–144° ∠–288° ∠0° ∠–144° ∠–288° ∠–54° ∠–234°

* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the F60 displays are always referenced as specified under SETTINGS 
SYSTEM SETUP  POWER SYSTEM  FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
Figure 6-5: Measurement convention for symmetrical components
System voltages Symmetrical
components
UR-series phase
angle reference

6
UR-series phase
angle reference

1
A

Wye VTs

C
B
0
2
UR
an -s
gl eri
e es
re p
fe ha
re s
nc e
e
U 1
A an R-s
gl eri
e es
re p
fe ha
re s
Delta VTs nc e
e

C
B
2
827844A1.CDR

6-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

6.4.2 Sources

6.4.2.1 Menu
ACTUAL VALUES  METERING  SOURCE SRC 1
 SOURCE SRC 1  PHASE CURRENT See below
   SRC 1

 GROUND CURRENT See page 6-20


  SRC 1

 PHASE VOLTAGE See page 6-20


  SRC 1

 AUXILIARY VOLTAGE See page 6-21


  SRC 1

 POWER See page 6-21


  SRC 1

 ENERGY See page 6-22


  SRC 1

 DEMAND See page 6-22


  SRC 1

 FREQUENCY See page 6-23


  SRC 1

 CURRENT HARMONICS See page 6-24


  SRC 1

 VOLTAGE HARMONICS See page 6-24


  SRC 1

This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power 6
values are unavailable.

6.4.2.2 Phase current metering


ACTUAL VALUES  METERING  SOURCE SRC 1  PHASE CURRENT
 PHASE CURRENT SRC 1 RMS Ia: 0.000
 SRC 1  b: 0.000 c: 0.000 kA

SRC 1 RMS Ia:


 0.000 kA

SRC 1 RMS Ib:


 0.000 kA

SRC 1 RMS Ic:


 0.000 kA

SRC 1 RMS In:


 0.000 kA

SRC 1 PHASOR Ia:


 0.000 kA 0.0°

SRC 1 PHASOR Ib:


 0.000 kA 0.0°

SRC 1 PHASOR Ic:


 0.000 kA 0.0°

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-19


METERING CHAPTER 6: ACTUAL VALUES

SRC 1 PHASOR In:


 0.000 kA 0.0°

SRC 1 ZERO SEQ I0:


 0.000 kA 0.0°

SRC 1 POS SEQ I1:


 0.000 kA 0.0°

SRC 1 NEG SEQ I2:


 0.000 kA 0.0°

The metered phase current values are displayed in this menu. The "SRC 1" text gets replaced by whatever name was
programmed by the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).

6.4.2.3 Ground current metering


ACTUAL VALUES  METERING  SOURCE SRC 1  GROUND CURRENT
 GROUND CURRENT SRC 1 RMS Ig:
 SRC 1  0.0 A

SRC 1 PHASOR Ig:


 0.0 A 0.0°

SRC 1 PHASOR Igd:


 0.000 kA 0.0°

The metered ground current values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).

6.4.2.4 Phase voltage metering


ACTUAL VALUES  METERING  SOURCE SRC 1  PHASE VOLTAGE
 PHASE VOLTAGE SRC 1 RMS Vag:
 SRC 1  0.0 V
6  SRC 1 RMS Vbg:
0.0 V

SRC 1 RMS Vcg:


 0.0 V

SRC 1 PHASOR Vag:


 0.0 V 0.0°

SRC 1 PHASOR Vbg:


 0.0 V 0.0°

SRC 1 PHASOR Vcg:


 0.0 V 0.0°

SRC 1 RMS Vab:


 0.0 V

SRC 1 RMS Vbc:


 0.0 V

SRC 1 RMS Vca:


 0.0 V

SRC 1 PHASOR Vab:


 0.0 V 0.0°

SRC 1 PHASOR Vbc:


 0.0 V 0.0°

6-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

SRC 1 PHASOR Vca:


 0.0 V 0.0°

SRC 1 ZERO SEQ V0:


 0.0 V 0.0°

SRC 1 POS SEQ V1:


 0.0 V 0.0°

SRC 1 NEG SEQ V2:


 0.0 V 0.0°

The metered phase voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).

6.4.2.5 Auxiliary voltage metering


ACTUAL VALUES  METERING  SOURCE SRC 1  AUXILIARY VOLTAGE
 AUXILIARY VOLTAGE SRC 1 RMS Vx:
 SRC 1  0.00 V

SRC 1 PHASOR Vx:


 0.00 V 0.0°

The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).

6.4.2.6 Power metering


ACTUAL VALUES  METERING  SOURCE SRC 1  POWER
 POWER SRC 1 REAL POWER
 SRC 1  3φ: 0.000 kW

SRC 1 REAL POWER


 φa: 0.000 kW

 SRC 1 REAL POWER 6


φb: 0.000 kW

SRC 1 REAL POWER


 φc: 0.000 kW

SRC 1 REACTIVE PWR


 3φ: 0.000 kvar

SRC 1 REACTIVE PWR


 φa: 0.000 kvar

SRC 1 REACTIVE PWR


 φb: 0.000 kvar

SRC 1 REACTIVE PWR


 φc: 0.000 kvar

SRC 1 APPARENT PWR


 3φ: 0.000 kVA

SRC 1 APPARENT PWR


 φa: 0.000 kVA

SRC 1 APPARENT PWR


 φb: 0.000 kVA

SRC 1 APPARENT PWR


 φc: 0.000 kVA

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-21


METERING CHAPTER 6: ACTUAL VALUES

SRC 1 POWER FACTOR


 3φ: 1.000

SRC 1 POWER FACTOR


 φa: 1.000

SRC 1 POWER FACTOR


 φb: 1.000

SRC 1 POWER FACTOR


 φc: 1.000

This menu displays metered values for real, reactive, and apparent power, as well as power factor. The "SRC 1" text is
replaced by the name programmed by the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL
SOURCES).
When VTs are configured in wye, the F60 calculates power in each phase and three-phase power is measured as
S = VA x ÎA + VB x ÎB + VC x ÎC Eq. 6-1
When VTs are configured in delta, the F60 does not calculate power in each phase and three-phase power is measured as
S = VAB x ÎA + VCB x ÎC Eq. 6-2
where
S is the apparent power
VA, VB, VC, IA, IB, IC are phase voltage and phase current phasors
VAB and VCB are phase-to-phase voltage phasors
Î is the conjugate of I

6.4.2.7 Energy metering


ACTUAL VALUES  METERING  SOURCE SRC 1  ENERGY
 ENERGY SRC 1 POS WATTHOUR:
 SRC 1  0.000 MWh
6  SRC 1 NEG WATTHOUR:
0.000 Wh

SRC 1 POS VARHOUR:


 0.000 varh

SRC 1 NEG VARHOUR:


 0.000 mvarh

This menu displays metered values for real and reactive energy. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES). Because energy values are
accumulated, record them and then reset them immediately prior to changing CT or VT characteristics.

6.4.2.8 Demand metering


ACTUAL VALUES  METERING  SOURCE SRC 1  DEMAND
 DEMAND SRC 1 DMD IA:
 SRC 1  0.000 kA

SRC 1 DMD IA MAX:


 0.000 kA

SRC 1 DMD IA DATE:


 2020/07/31 16:30:07

SRC 1 DMD IB:


 0.000 kA

6-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

SRC 1 DMD IB MAX:


 0.000 kA

SRC 1 DMD IB DATE:


 2020/07/31 16:30:07

SRC 1 DMD IC:


 0.000 kA

SRC 1 DMD IC MAX:


 0.000 kA

SRC 1 DMD IC DATE:


 2020/07/31 16:30:07

SRC 1 DMD W:
 0.000 kW

SRC 1 DMD W MAX:


 0.000 kW

SRC 1 DMD W DATE:


 2020/07/31 16:30:07

SRC 1 DMD VAR:


 0.000 kvar

SRC 1 DMD VAR MAX:


 0.000 kvar

SRC 1 DMD VAR DATE:


 2020/07/31 16:30:07

SRC 1 DMD VA:


 0.000 kVA

SRC 1 DMD VA MAX:


 0.000 kVA

SRC 1 DMD VA DATE:


 2020/07/31 16:30:07
6
This menu displays metered values for current and power demand. The "SRC 1" text is replaced by the name programmed
by the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).
The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the SETTINGS  PRODUCT SETUP
 DEMAND menu. For each quantity, the relay displays the demand over the most recent demand time interval, the
maximum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value.
Maximum demand quantities can be reset to zero with the CLEAR RECORDS  CLEAR DEMAND RECORDS command.

6.4.2.9 Frequency metering


ACTUAL VALUES  METERING  SOURCE SRC 1  FREQUENCY
 FREQUENCY SRC 1 FREQUENCY:
 SRC 1  0.000 Hz

The metered frequency values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by the
user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP  POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The final
frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-23


METERING CHAPTER 6: ACTUAL VALUES

6.4.2.10 Current harmonics and THD metering


ACTUAL VALUES  METERING  SOURCE SRC 1  CURRENT HARMONICS
 CURRENT HARMONICS SRC 1 THD Ia: 0.0
 SRC 1  Ib: 0.0 Ic: 0.0%

SRC 1 2ND Ia: 0.0


 Ib: 0.0 Ic: 0.0%

SRC 1 3RD Ia: 0.0


 Ib: 0.0 Ic: 0.0%

SRC 1 25TH Ia: 0.0
 Ib: 0.0 Ic: 0.0%

This menu displays metered current harmonics values. The "SRC 1" text is replaced by the name was programmed for the
associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES). Current harmonics are measured for each source
for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.

6.4.2.11 Voltage harmonics and THD metering


ACTUAL VALUES  METERING  SOURCE SRC 1  VOLTAGE HARMONICS
 VOLTAGE HARMONICS SRC 1 THD Va: 0.0
 SRC 1  Vb: 0.0 Vc: 0.0%

SRC 1 2ND Va: 0.0


 Vb: 0.0 Vc: 0.0%

SRC 1 3RD Va: 0.0


 Vb: 0.0 Vc: 0.0%

SRC 1 25TH Va: 0.0
 Vb: 0.0 Vc: 0.0%

6 This menu displays metered voltage harmonics values. The “SRC 1” text is replaced by the programmed name for the
associated source (see the SETTINGS  SYSTEM SETUP  SIGNAL SOURCES menu).
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
ω0 = 2πf is the angular frequency based on the system frequency (50 or 60 Hz)
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:

2
F real m, h = --- ¦ f m – k ˜ cos h ˜ Z 0 ˜ t k
N
k
2
F imag m, h = --- ¦ f m – k ˜ sin h ˜ Z 0 ˜ t k
N
k
2 2
F ampl m, h = F real m, h + F imag m, h Eq. 6-3

The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental
amplitude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the
fundamental:

2 2 2
THD = F 2 + F 3 + } + F 25 Eq. 6-4

6-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

Voltage harmonics are not available on F60 relays configured with the high-impedance fault detection (Hi-Z)
feature.

Voltage harmonics are calculated only for Wye connected phase VTs. Ensure that the SYSTEM SETUP  AC INPUTS
 VOLTAGE BANK F5  PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics metering.

6.4.3 Sensitive directional power


ACTUAL VALUES  METERING  SENSITIVE DIRECTIONAL POWER  DIRECTIONAL POWER 1(2)
 DIRECTIONAL DIRECTIONAL POWER 1
 POWER 1  3Φ: 0.0 kW

The effective operating quantities of the sensitive directional power elements display here. The display is useful to calibrate
the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION settings.

6.4.4 Synchrocheck
ACTUAL VALUES  METERING  SYNCHROCHECK  SYNCHROCHECK1(4)
 SYNCHROCHECK1 SYNCHROCHECK 1 DELTA
  VOLT: 0.000 kV

SYNCHROCHECK 1 DELTA
 FREQ: 0.000 Hz

SYNCHROCHECK 1 DELTA
 PHASE: 0.0°

SYNCHROCHECK 1
 SYNSCP D_PH: 0.0°

 SYNCHROCHECK 1 6
V1 MAG: 0.0 V

SYNCHROCHECK 1
 V1 ANG: 0.0°

SYNCHROCHECK 1
 V2 MAG: 0.0 V

SYNCHROCHECK 1
 V2 ANG: 0.0°

SYNCHROCHECK 1 PROJ
 V2 MAG: 0.0 V

SYNCHROCHECK 1 PROJ
 V2 ANG: 0.0°

SYNCHROCHECK 1 PROJ
 DELTA PHASE: 0.0°

SYNCHROCHECK 1 PROJ
 SYNSCP D_PH: 0.0°

If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-25


METERING CHAPTER 6: ACTUAL VALUES

6.4.5 Tracking frequency


ACTUAL VALUES  METERING  TRACKING FREQUENCY
 TRACKING FREQUENCY TRACKING FREQUENCY:
  60.00 Hz

ACTIVE FREQ AND PHS REF:


 MAIN

MAIN REF FREQUENCY:


 60.00 Hz

ALT REF FREQUENCY:


 60.00 Hz

The Tracking Frequency and the Active Frequency and Phase Reference are metered as shown here. The tracking
frequency is calculated from the signals defined in the Active Frequency and Phase Reference. Note that based on the
signal availability and the settings defined in the Main and Alternate Frequency and Phase Reference, the Active Frequency
and Phase Reference might be switched between main and alternate frequency reference in runtime.
The frequency calculated in main and alternate reference respectively are also metered as shown here. They will be
displayed as 0 if the signal in this reference is lost or it’s not configured.

6.4.6 Frequency rate of change


ACTUAL VALUES  METERING  FREQUENCY RATE OF CHANGE 1(4)
 FREQUENCY RATE FREQUENCY RATE OF
 OF CHANGE 1  CHANGE1: 0.00 Hz/s

The metered frequency rate of change for the frequency rate of change elements is shown here.

6.4.7 FlexElements
6 ACTUAL VALUES  METERING  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1 FLEXELEMENT 1
  OpSig: 0.000

The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit Description
BREAKER ACC ARCING AMPS BASE = 2000 kA2 × cycle
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS BASE = 1 kA2 × cycle
(Brk X Arc Amp A, B, and C)
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FAULT LOCATION BASE = Line Length as specified in Fault Report
FREQUENCY fBASE = 1 Hz
FREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/s
PHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SENSITIVE DIR POWER PBASE = maximum value of 3 × VBASE × IBASE for the +IN and –IN inputs of the sources configured
(Sns Dir Power) for the sensitive power directional element(s).
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs

6-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES METERING

Base unit Description


SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE × IBASE for the +IN and –IN inputs
SOURCE THD & HARMONICS BASE = 1%
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)

6.4.8 RxGOOSE analogs


ACTUAL VALUES  METERING  RxGOOSE Analogs
 RxGOOSE RxGOOSE Analog 1
 Analogs  0.000

RxGOOSE Analog 32
 0.000

RxGOOSE An1 ExpnSt:


 Off

This menu displays when the product includes an IEC 61850 software option.

The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.

6.4.9 Wattmetric ground fault 6


ACTUAL VALUES  METERING  WATTMETRIC GROUND FAULT 1(2)
 WATTMETRIC WATT GND FLT 1:
 GROUND FAULT 1  0.000 W

This menu displays the wattmetric zero-sequence directional element operating power values.

6.4.10 Phasor Measurement Unit


ACTUAL VALUES  METERING  PHASOR MEASURMENT UNIT  PMU 1
 PMU 1 PMU 1 VA: Range: Va or Vab per VT bank connection
  0.000 V 0.00°

PMU 1 VB: Range: Va or Vab per VT bank connection


 0.000 V 0.00°

PMU 1 VC: Range: Va or Vab per VT bank connection


 0.000 V 0.00°

PMU 1 VX:
 0.000 V 0.00°

PMU 1 V1:
 0.000 V 0.00°

PMU 1 V2:
 0.000 V 0.00°

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-27


METERING CHAPTER 6: ACTUAL VALUES

PMU 1 V0: Range: Substituted with zero if delta-connected VTs


 0.000 V 0.00°

PMU 1 IA:
 0.000 A 0.00°

PMU 1 IB:
 0.000 A 0.00°

PMU 1 IC:
 0.000 A 0.00°

PMU 1 IG:
 0.000 A 0.00°

PMU 1 I1:
 0.000 A 0.00°

PMU 1 I2:
 0.000 A 0.00°

PMU 1 I0:
 0.000 A 0.00°

PMU 1 FREQUENCY:
 0.000 Hz

PMU 1 df/dt:
 0.00 Hz/s

PMU 1 CONFIG CHANGE Range: 0 to 65535


 COUNTER: 0

These actual values display without the corresponding time stamp as they become available per the recording rate
setting. Also, the recording post-filtering setting is applied to these values.

6.4.11 PMU aggregator


6 ACTUAL VALUES  METERING  PHASOR MEASURMENT UNIT  PMU AGGREGATOR 1
 PMU AGGREGATOR 1 PMU AGGREGATOR 1
  PDU SIZE: 0

Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.

6.4.12 Restricted ground fault


ACTUAL VALUES  METERING  RESTRICTED GROUND FAULT CURRENTS  RESTRICTED GROUND FAULT 1(4)
 RESTRICTED RGF 1 DIFF Igd:
 GROUND FAULT 1  0.000 kA

RGF 1 RESTR Igr:


 0.000 kA

This menu displays the differential and restraint current values for the restricted ground fault element.

6-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES REMOTE RESOURCES

6.4.13 Transducer inputs and outputs


ACTUAL VALUES  METERING  TRANSDUCER I/O DCMA INPUTS  DCMA INPUT xx
 DCMA INPUT xx DCMA INPUT xx
  0.000 mA

Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES  METERING  TRANSDUCER I/O RTD INPUTS  RTD INPUT xx
 RTD INPUT xx RTD INPUT xx
  -50 °C

Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.

6.4.14 Harmonic detection


ACTUAL VALUES  METERING  HARMONIC DETECTION  HARMONIC DETECTOR 1(6)
 HARMONIC DET 1 HARMONIC DET 1
  IA: 0.0%

HARMONIC DET 1
 IB: 0.0%

HARMONIC DET 1
 IC: 0.0%

HARMONIC DET 1
 IAVG: 0.0%

HARMONIC DET 1
 IG: 0.0%

6.5 Remote resources


6.5.1 Field unit
ACTUAL VALUES  REMOTE RESOURCES  FIELD UNIT U1(U8)
 FIELD UNIT U1 FIELD UNIT STATUS: Range: Disabled, Enabled
 ID: U 1  DISABLED

BRICK SERIAL NUMBER:



BRICK ORDER CODE:
 CC-55

BRICK DIGITAL CORE:


 0

LOCAL TRANSCEIVER:
 TX POWER: 0.0 dBm

BRICK TRANSCEIVER
 RX POWER: 0.0 dBm

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-29


PROCESS BUS MODULE CHAPTER 6: ACTUAL VALUES

BRICK TRANSCEIVER
 TX POWER: 0.0 dBm

LOCAL TRANSCEIVER
 RX POWER: 0.0 dBm

This menu displays when using a Process Bus Module for a HardFiber Brick.

6.6 Process Bus Module


6.6.1 General status
ACTUAL VALUES  PB MODULE  GENERAL STATUS
 GENERAL STATUS NETWORK CONFIG: Range: INDEPENDENT, PRP, HSR, Dual HSR
  INDEPENDENT

Port 1a Status: Range: Disabled, Enabled, Active


 Disabled

Port 4b Status: Range: Disabled, Enabled, Active
 Disabled

These menus display when the product includes a Process Bus Module with order code 85, 86, or 87. The
actual values display on the front panel and software. Additional values display in a web browser; enter the IP
address of the relay and access the Process Card Menu.
Ports applicable to the Process Bus Module display. The example shows all eight ports.
The information also displays in a web browser under Process Card Menu > Process Card Port Information.

6 6.6.2 RxSV status


ACTUAL VALUES  PB MODULE  RxSV Status
 RxSV Status All RxSV Online: Range: Yes, No
  No

 RxSV 1 See below


 

 RxSV 8
 

ACTUAL VALUES  PB MODULE  RxSV Status  RxSV1(8)


 RxSV 1 SV 1 Status: Range: Off, On, Not Configured
  Off

SV 1 Sync Status: Range: Local, Global, No Sync


 No Sync

SV 1 Sim Flag: Range: Off, On


 Off

SV 1 Delay: Range: µs
 0 µs

SV 1 Missed Frames: Range: Yes, No


 No

6-30 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES PROCESS BUS MODULE

SV 1 Ch 1 Quality: Range: 0000000000000


 0

SV 1 Ch16 Quality:
 0

Additional actual values for sampled values display in a web browser. Enter the IP address of the relay and access Process
Card Menu > Process Card Diagnostics, for which the following fields are explained.
All SV diagnostics are volatile and are cleared when power is cycled.
Sample Value processing delay...Min Delay — The minimum time delay in received sample values. The accuracy threshold of
this diagnostics is within 1/8 of a power system cycle.
Sample Value processing delay...Max Delay — The maximum time delay in received sample values. The accuracy threshold of
this diagnostics is within 1/8 of a power system cycle.
Sample Value processing delay...Avg Delay — The average time delay for received sample values. A delay up to about 1.5
milliseconds (1500 µsec) is normal. The accuracy threshold of this diagnostics is within 1/8 of a power system cycle.
SV Delay Alarm Counter — The number of times that sampled values from a configured SV stream are delayed for more than
the Settings > Process Bus Module > General > SV Delay Alarm setting. Counters wrap around when they reach 4294967295.
Sample Estimation Counter — The number of times that the relay used an internal estimation algorithm to substitute a
missing sample value. Counters wrap around when they reach 4294967295.
Stream Status — The status of a configured SV stream. If the Settings > Process Bus Module > SV Stream Config > SV Stream
setting is set to Disabled, this value is shown as Disabled. If the setting is set to IEC 61850-9-2LE or IEC 61869-9 and
received sample values are accepted by the relay, this value is shown as Online. If received sample values are rejected, or
sample values are lost (frames not received), stream status changes to Offline.
Latest Unacceptable Quality — Time stamp of the latest sample value with unacceptable quality, in any data item in a
dataset. This time stamp has 1/8 of a power system cycle accuracy threshold.
Latest Sim Bit Change — The time stamp of latest change in simulation bit status of the received RxSV# messages. This time
stamp has 1/8 of a power system cycle accuracy threshold.
SmpSync Latest Update Time — The time stamp of the latest sample value for which the SmpSync attribute was different
from the previous samples. This value determines when the time source that sample value stream is synchronized to has 6
changed. This time stamp has 1/8 of a power system cycle accuracy threshold.
SmpSync Changes in Past 24hrs — The number of times the SmpSync attribute in the sample value messages from this
stream has changed in the past 24 hours. This counter is updated every hour. Counters wrap around when they reach
4294967295. The accuracy of this metric is 1.5 hours over a 24-hour period.
Sample Estimate Fail-Last 10s — The number of times that three or more out of five consecutive samples has been lost in the
last 10 seconds. This counter is updated every second. Counters wrap around when they reach 4294967295.
Sample Value Trouble Counter — The number of times that the SV Stream Trouble On minor self-test error is detected by the
Process Bus Module. Counters wrap around when they reach 4294967295.

6.6.3 Clock synchronizing


ACTUAL VALUES  PB MODULE  TIME SYNC
 TIME SYNC Sync Source: Range: CPU Clock, PBM PTP Clock, PBM Internal
  None Clock, None

Grandmaster ID: Range: any 8 octet value


 00000000000000000

Accuracy: Range: 0 to 999,999,999 ns


 0 ns

Additional actual values for time are available under Actual Values > Status > Real Time Clock Synchronizing.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-31


PROCESS BUS MODULE CHAPTER 6: ACTUAL VALUES

Sync Source — This is the time synchronizing source that the UR Process Bus Module is using at present. It displays CPU
Clock when the 1 pulse per second (PPS) signal from the main CPU drives the Process Bus Module clock. It displays None
when the Process Bus Module clock free runs. It displays SV Sync Stream when the Process Bus Module clock is
synchronized to the configured reference stream. It displays PBM Clock when the Process Bus Module clock is
synchronized to a PTP grandmaster clock. The time synchronizing source itself is set using SETTINGS  PRODUCT SETUP 
REAL TIME CLOCK and SETTINGS  PROCESS BUS MODULE  PBM PTP  PTP FUNCTION. If the latter is not set, then the Sync
Source displays None even when the REAL TIME CLOCK setting is configured.
Grandmaster ID — This is the grandmaster clock (grandmasterIdentity) of the present PTP network if any. When the UR
Process Bus Module is not using any PTP grandmaster, this actual value is set to the ID of that relay and the relay is acting
as grandmaster in the network. The ID code is specified by PTP to be globally unique, so one can always know which clock
is grandmaster in a system with multiple grandmaster-capable clocks.
Accuracy — This is the estimated time error based on the clockAccuracy information embedded in the received time signal.
This actual value indicates the grandmaster clock accuracy. The clockAccuracy enumeration information received from
the grandmaster is translated into nanoseconds as specified in the following table. The value 999,999,999 indicates that
the magnitude of the estimated error is one second or more, or that the error cannot be estimated. The value 999,999,999
is used if the clockAccuracy received from grandmaster is in the ranges: 00 - 1F and 2F - FF. If the relay is the grandmaster,
the actual value indicates the estimated accuracy of the local clock and the same information is embedded in the
transmitted PTP messages. See defaultDS.clockQuality.clockAccuracy for more information.
Table 6-3: Clock accuracy
Value (hex) Specification
00-1F Reserved
20 The time is accurate to within 25 ns
21 The time is accurate to within 100 ns
22 The time is accurate to within 250 ns
23 The time is accurate to within 1 µs
24 The time is accurate to within 2.5 µs
25 The time is accurate to within 10 µs
26 The time is accurate to within 25 µs
6 27 The time is accurate to within 100 µs
28 The time is accurate to within 250 µs
29 The time is accurate to within 1 ms
2A The time is accurate to within 2.5 ms
2B The time is accurate to within 10 ms
2C The time is accurate to within 25 ms
2D The time is accurate to within 100 ms
2E The time is accurate to within 250 ms
2F The time is accurate to within 1 s
30 The time is accurate to within 10 s
31 The time is accurate to greater than 10 s
32-7F Reserved
80-FD For use by alternate PTP profiles
FE Unknown
FF Reserved

6.6.4 PRP
Actual values for the Parallel Redundancy Protocol (PRP) display in a web browser. Enter the IP address of the relay and
access the Process Card Menu > Process Card PRP Statistics, which displays only when PRP is used.
PRP Status — PRP is Enabled if Settings > Process Bus Module > General > Network Config is set to PRP, else it is Disabled.

6-32 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES RECORDS

Total Rx Port A — Counter indicating the number of frames received on port A, for example port 1a.
Total Rx Port B — Counter indicating the number of frames received on port B, for example port 1b.
Total Tx Port A — Counter indicating the number of frames sent on port A, for example port 1a.
Total Tx Port B — Counter indicating the number of frames sent on port B, for example port 1b.
Mismatches Port A — Counter indicating the number of erroneous frames received on port A, for example port 1a.
Mismatches Port B — Counter indicating the number of erroneous frames received on port B, for example port 1b.
Duplicates Removed Port A — Number of PRP duplicate frames received from port A and discarded, for example port 1a.
Duplicates Removed Port B — Number of PRP duplicate frames received from port B and discarded, for example port 1b.

6.6.5 HSR
Actual values for High-Availability Seamless Redundancy (HSR) display in a web browser. Enter the IP address of the relay
and access the Process Card Menu > Process Card HSR Statistics, which displays only when HSR is used.
HSR1 Status — Status of the first ring, either enabled or disabled. Enabled when redundancy is set to HSR or Dual-HSR.
HSR2 Status — Status of the second ring, either enabled or disabled. Enabled when redundancy is set to HSR or Dual-HSR.
Total Rx Port A — Counter indicating the number of frames received on port A, for example port 1a.
Total Rx Port B — Counter indicating the number of frames received on port B for example port 1b.
Total Tx Port A — Counter indicating the number of frames sent on port A, for example port 1a.
Total Tx Port B — Counter indicating the number of frames sent on port B, for example port 1b.
Duplicates Removed Port A — Number of HSR duplicate frames received from port A and discarded, for example port 1a.
Duplicates Removed Port B — Number of HSR duplicate frames received from port B and discarded, for example port 1b.

6.7 Records
6.7.1 Fault reports
6
ACTUAL VALUES  RECORDS  FAULT REPORTS  FAULT REPORT 1(15)
NO FAULTS TO REPORT

or
 FAULT REPORT 1 FAULT 1 Range: SRC 1, SRC 2
  LINE ID: SRC 1

FAULT 1 DATE: Range: YYYY/MM/DD


 2000/08/11

FAULT 1 TIME: Range: HH:MM:SS.ssssss


 00:00:00.000000

FAULT 1 TYPE: Range: not available if the source VTs are in the
 ABG “Delta” configuration

FAULT 1 LOCATION Range: not available if the source VTs are in the
 00.0 km “Delta” configuration

FAULT 1 RECLOSE Range: where applicable


 SHOT: 0

FAULT 1 LOOP Range: 0 to 327.67 Ohms


 RESIST: 0.00 Ohms

FAULT 1 LOOP Range: -327.67 to 327.67 Ohms


 REACT: 0.00 Ohms

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-33


RECORDS CHAPTER 6: ACTUAL VALUES

The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS  PRODUCT
SETUP  FAULT REPORTS menu for assigning the source and trigger for fault calculations. See the COMMANDS  CLEAR
RECORDS menu for manual clearing of the fault reports and to the SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
menu for automated clearing of the fault reports.
The FAULT 1 LOOP RESISTANCE and REACTANCE are expressed in secondary ohms, which are calculated as per the following
equation.
Zloop = Vloop / Iloop Eq. 6-5
The table defines the loop voltage and current.
Table 6-4: Quantities used to calculate fault loop impedances
Fault type Vloop Iloop
AG VA IA + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
BG VB IB + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
CG VC IC + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
AB, ABG VA – VB IA - IB
BC, BCG VB – VC IB - IC
CA, CAG VC – VA IC - IA
ABC Average of AB, BC, CA loop impedances

Where VA, VB, VC are phase voltage phasors in secondary volts; IA, IB, IC are current phasors in secondary amps, I0 is the
zero sequence current phasors in secondary amps; and IG is the ground current from the parallel line scaled to the source
phase CT in secondary amps. Z0/Z1 is the zero sequence impedance to positive sequence impedance ratio, and Z0M/Z1 is
mutual zero sequence impedance to positive sequence impedance ratio.

VTs of the FAULT REPORT 1 SOURCE must be connected in Wye or VT SUBSTITUTION must be set correctly for the Delta
connected VT to display the loop impedance and fault resistance for single phase-to-ground faults.
For the application of partially parallel circuits and in the case of single phase-to-ground faults, the reported fault
6 resistance and fault loop impedance may not be accurate even the compensation method is applied.

6.7.2 Event records

6.7.2.1 Enhanced and basic front panels


ACTUAL VALUES  RECORDS  EVENT RECORDS
 EVENT RECORDS EVENT: XXX
  XXX
 Date and time stamps

EVENT: 3 EVENT 3
 POWER ON   DATE: 2020/07/14

EVENT: 2 EVENT 3
 POWER OFF  TIME: 14:53:00.03405

EVENT: 1
 EVENTS CLEARED

The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the COMMANDS  CLEAR RECORDS menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.

6-34 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES RECORDS

See also the system log (syslog) information in the previous chapter.
The event records are viewable in the software and in a web browser. The figure shows the event records in the software.
Figure 6-6: Event records viewed in EnerVista software

To view events in a web browser:


1. Enter the IP address of the device.
To download an oscillography waveform:
1. Click the Oscillography icon in the Data column (not shown in the figure).

6.7.2.2 Graphical front panel


6
To display the event records page, press the Home pushbutton then the Event Record Tab pushbutton.
The newest event is always at the top.
Up and Down pushbuttons move the event selector up and down. When the selector is at the bottom of the display, the
Down pushbutton also scrolls the page, and similarly when the active selector is at the top of the display the Up
pushbutton scroll the page.
A selected event is highlighted in yellow and becomes active by pressing the Up or Down pushbutton.
There are two event markers, one green, the other cyan. To mark some an event, use the Up and Down pushbuttons to
select it (highlight in yellow), then press the green or cyan Mark Event Tab pushbutton. The mark color hides the selector
until the selector is moved. A field at the top of the page shows the interval between the two marks.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-35


RECORDS CHAPTER 6: ACTUAL VALUES

Figure 6-7: Event record

6.7.3 Oscillography

6.7.3.1 Enhanced and basic front panels


ACTUAL VALUES  RECORDS  OSCILLOGRAPHY
 OSCILLOGRAPHY FORCE TRIGGER? Range: No, Yes
  No

NUMBER OF TRIGGERS:
 0

AVAILABLE RECORDS:
 0

CYCLES PER RECORD:



6 0

LAST CLEARED DATE:


 2019/07/14 15:40:16

This menu allows the user to view the number of triggers involved and number of oscillography traces available. The cycles
per record value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography
section of chapter 5 for details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. See the COMMANDS  CLEAR
RECORDS menu for information on clearing the oscillography records.
To view a waveform:
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display.
5. In the waveform window that opens, you can save the file, for example with the CFG extension.

6.7.4 Data logger


ACTUAL VALUES  RECORDS  DATA LOGGER
 DATA LOGGER OLDEST SAMPLE TIME:
  2020/01/14 13:45:51

6-36 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES RECORDS

NEWEST SAMPLE TIME:


 2020/01/14 15:21:19

The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It is static until the log gets
full, at which time it starts counting at the defined sampling rate.
The NEWEST SAMPLE TIME represents the time the most recent samples were taken. It counts up at the defined sampling
rate. If the data logger channels are defined, then both values are static.
See the COMMANDS  CLEAR RECORDS menu for clearing data logger records.

6.7.5 Phasor Measurement Unit records


ACTUAL VALUES  RECORDS  PMU RECORDS
 PMU NUMBER OF TRIGGERS: Range: 0 to 65535 in steps of 1
 RECORDS  0

 PMU 1 See below


  RECORDING

The number of triggers applicable to the Phasor Measurement Unit recorder is indicated by the NUMBER OF TRIGGERS value.
The status of the phasor measurement unit recorder is indicated as follows.
ACTUAL VALUES  RECORDS  PMU RECORDS  PMU 1 RECORDING
 PMU 1 PMU 1 FORCE TRIGGER: Range: No, Yes
 RECORDING  No

PMU 1 AVAILABLE Range: 0 to 65535 in steps of 1


 RECORDS: 0

PMU 1 SECONDS PER Range: 0 to 6553.5 in steps of 0.1


 RECORD: 0.0

PMU 1 LAST CLEARED: Range: YYYY/MM/DD HH:MM:SS


 2013/07/14 15:40:16

6
6.7.6 Breaker maintenance
ACTUAL VALUES  RECORDS  MAINTENANCE  BREAKER 1(2)(4)
 BREAKER 1 BKR 1 ACC ARCING AMP
  φA: 0.00 kA2-cyc

BKR 1 ACC ARCING AMP


 φB: 0.00 kA2-cyc

BKR 1 ACC ARCING AMP


 φC: 0.00 kA2-cyc

BKR 1 OPERATING TIME


 φA: 0 ms

BKR 1 OPERATING TIME


 φB: 0 ms

BKR 1 OPERATING TIME


 φC: 0 ms

BKR 1 OPERATING
 TIME: 0 ms

BKR 1 ARCING AMP φA:


 0.00 kA2-cyc

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-37


RECORDS CHAPTER 6: ACTUAL VALUES

BKR 1 ARCING AMP φB:


 0.00 kA2-cyc

BKR 1 ARCING AMP φC:


 0.00 kA2-cyc

BKR 1 AMP MAX φA:


 0.00 kA

BKR 1 AMP MAX φB:


 0.00 kA

BKR 1 AMP MAX φC:


 0.00 kA

There is an identical menu for each of the breakers.


The BKR 1 ACC ARCING AMP values are in units of kA2-cycles. See the COMMANDS  CLEAR RECORDS menu for clearing
breaker arcing current records.
The BREAKER OPERATING TIME is defined as the slowest operating time of breaker poles that were initiated to open.
All of the values are stored in non-volatile memory and retained with power cycling.

6.7.7 Hi-Z records


ACTUAL VALUES  RECORDS  HIZ RECORDS
 HIZ RECORDS FORCE TRIGGER:
  No

HIZ 1:NONE
 1970/01/01 00:00:00

HIZ 2:NONE
 1970/01/01 00:00:00

HIZ 3:NONE

6 1970/01/01 00:00:00

HIZ 4:NONE
 1970/01/01 00:00:00

RMS 1:NONE
 1970/01/01 00:00:00

RMS 2:NONE
 1970/01/01 00:00:00

RMS 3:NONE
 1970/01/01 00:00:00

RMS 4:NONE
 1970/01/01 00:00:00

Two types of high impedance fault detection element records are stored in non-volatile memory and available from this
menu. If the element is triggered by a high impedance overcurrent condition, then the records display in the RMS 1 to RMS
4 actual values. If the element is triggered by high impedance fault detection arcing algorithm, then the records display in
the HIZ 1 to HIZ 4 actual values. See the High-Impedance Fault Detection (Hi-Z) section near the end of chapter 5 for
information.

6-38 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 6: ACTUAL VALUES PRODUCT INFORMATION

6.8 Product information


6.8.1 Model information
ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION
 MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE order code format
  F60-A00-AAA-A0A-A0A-

ORDER CODE LINE 2: Range: up to 20 alphanumeric characters


 A0A-A0A-A0A

ORDER CODE LINE 3: Range: up to 20 alphanumeric characters



ORDER CODE LINE 4: Range: up to 20 alphanumeric characters

SERIAL NUMBER: Range: standard GE serial number format

ETHERNET MAC ADDRESS Range: standard Ethernet MAC address format
 000000000000

MANUFACTURING DATE: Range: YYYY/MM/DD HH:MM:SS



OPERATING TIME: Range: HH:MM:SS
 0:00:00

PMU FEATURE ACTIVE: Range: Yes, No


 No

CT/ VT ADVANCED DIAG Range: Yes, No


 ACTIVE: No

LAST SETTING CHANGE: Range: YYYY/MM/DD HH:MM:SS


 2019/01/01 23:11:19
6
PBM MAC ADDRESS: Range: YYYY/MM/DD HH:MM:SS
 664422113344

The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information. The information is read-only in the software and modifiable on
the front panel. For example, the order code can be corrected using the front panel.
ETHERNET MAC ADDRESS — UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.
PBM MAC ADDRESS — The MAC address for the Process Bus Module.

6.8.2 Firmware revisions


6.8.2.1 Enhanced and basic front panels
ACTUAL VALUES  PRODUCT INFO  FIRMWARE REVISIONS
 FIRMWARE REVISIONS F60 Range: 0.00 to 655.35
  REVISION: 7.9x Revision number of the application firmware.

MODIFICATION FILE Range: 0 to 65535 (ID of the MOD FILE)


 NUMBER: 0 Value is 0 for each standard firmware release.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-39


PRODUCT INFORMATION CHAPTER 6: ACTUAL VALUES

BOOT PROGRAM Range: 0.00 to 655.35


 REVISION: 7.06 Revision number of the boot program firmware.

FRONT PANEL PROGRAM Range: 0.00 to 655.35


 REVISION: 2.01 Revision number of front panel program firmware.

COMPILE DATE: Range: YYYY/MM/DD HH:MM:SS


 2021/04/09 04:55:16 Date and time when product firmware was built.

BOOT DATE: Range: YYYY/MM/DD HH:MM:SS


 2021/02/23 16:41:32 Date and time when the boot program was built.

PROCESS BUS BOOT Range: 0.00 to 655.35


 REVISION: 0.00

PB BOOT DATE: Range: YYYY/MM/DD HH:MM:SS


 2018/09/15 04:55:16

PROCESS BUS Range: 0.00 to 655.35


 REVISION: 7.9x

PROCESS BUS DATE: Range: YYYY/MM/DD HH:MM:SS


 2018/09/15 04:55:16

PB CVSOC FPGA Range: 0.00 to 655.35


 REVISION: 0.00

PB CVFPGA FPGA Range: 0.00 to 655.35


 REVISION: 0.00

PB CVFPGA SIGN: Range:


 33272

FPGA PROGRAM Range: 0.00 to 655.35


 REVISION: 02.02 Revision number for FPGA.

FPGA DATE: Range: YYYY/MM/DD HH:MM:SS


 2016/09/15 16:41:32 Date and time when the FPGA was built.

The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
6 installed. PB and process bus refer to the Process Bus Module.

6.8.2.2 Graphical front panel


With a graphical front panel (GFP), the following additional items display in the software.
GFP PROGRAM Range: 0.00 to 655.35
 REVISION: 7.80

GFP COMPILE DATE: Range: YYYY/MM/DD HH:MM:SS


 2018/09/15 04:55:16

GFP BOOT PROGRAM Range: 0.00 to 655.35


 REVISION: 655.35

GFP BOOT COMP. DATE: Range: YYYY/MM/DD HH:MM:SS


 2016/09/15 04:55:16

6-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 7: Commands and targets

Commands and targets

This chapter outlines the Commands and Targets menus and self-tests/error messages. Commands related to the IEC
61850 protocol are outlined in the IEC 61850 section of the Settings chapter. Log/error messages for IEC 61850 are
outlined in the UR Family Communications Guide.

7.1 Commands menu

COMMANDS


 COMMANDS
  VIRTUAL INPUTS

 COMMANDS
  CLEAR RECORDS

 COMMANDS
  SET DATE AND TIME

 COMMANDS
  RELAY MAINTENANCE

 COMMANDS
  PMU ONE-SHOT

 COMMANDS
  SECURITY

The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash
message appears after successfully command entry.
COMMAND
EXECUTED

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-1


COMMANDS MENU CHAPTER 7: COMMANDS AND TARGETS

7.1.1 Virtual inputs


COMMANDS  VIRTUAL INPUTS
 COMMANDS Virt Ip 1 Range: Off, On
 VIRTUAL INPUTS  Off

Virt Ip 2 Range: Off, On


 Off

Virt Ip 128 Range: Off, On
 Off

The states of up to 128 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).

7.1.2 Clear records


COMMANDS  CLEAR RECORDS
 COMMANDS CLEAR FAULT REPORTS? Range: No, Yes
 CLEAR RECORDS  No

CLEAR EVENT RECORDS? Range: No, Yes


 No

CLEAR OSCILLOGRAPHY? Range: No, Yes


 No

CLEAR DATA LOGGER? Range: No, Yes


 No

CLEAR BREAKER 1 Range: No, Yes


 ARCING AMPS? No

CLEAR BREAKER 2 Range: No, Yes


 ARCING AMPS? No

CLEAR DEMAND Range: No, Yes


 RECORDS? No

CLEAR ENERGY? Range: No, Yes


 No
7  CLEAR HIZ RECORDS?
No
Range: No, Yes

CLEAR UNAUTHORIZED Range: No, Yes


 ACCESS? No

CLEAR DIRECT I/O Range: No, Yes.


 COUNTERS? No Valid only for units with Direct Input/Output module.

CLEAR PMU 1 RECORDS? Range: No, Yes


 No

CLEAR PMU 1 CONFIG Range: No, Yes


 CHANGE COUNTER? No

CLEAR TELEPROTECT Range: No, Yes


 COUNTERS? No

CLEAR INCIPIENT Range: No, Yes


 FAULT COUNTERS? No

 CLEAR IEC61850 See below


  XWSI OPCNT

7-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS COMMANDS MENU

 CLEAR IEC61850 See below


  XCBR OPCNT

CLEAR SV Range: No, Yes


 DIAGNOSTICS? No

CLEAR ALL RELAY Range: No, Yes


 RECORDS? No

This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to
“No.”
CLEAR SV DIAGNOSTICS — Clears the sampled value diagnostics information for a non-HardFiber Process Bus Module. All
other Process Bus Module diagnostics information is reset up relay power cycling, such as HSR and PTP.
COMMANDS  CLEAR RECORDS  CLEAR IEC61850 XWSI OPCNT
 CLEAR IEC61850 CLEAR XSWI 1 Range: No, Yes
 XWSI OPCNT  OpCnt? No

CLEAR XSWI 24 Range: No, Yes
 OpCnt? No

COMMANDS  CLEAR RECORDS  CLEAR IEC61850 XCBR OPCNT


 CLEAR IEC61850 CLEAR XCBR 1 Range: No, Yes
 XCBR OPCNT  OpCnt? No

CLEAR XCBR 8 Range: No, Yes
 OpCnt? No

The Clear XSWI commands clear the disconnect operation counters for each phase and the three-phase counter. Similarly,
the Clear XCBR commands clear the circuit breaker operation counters for each phase and the three-phase counter.

7.1.3 Set date and time


COMMANDS  SET DATE AND TIME
 COMMANDS
 SET DATE AND TIME  SET DATE AND TIME:
2020/01/14 13:47:03
Range: YYYY/MM/DD HH:MM:SS
7
The date and time can be entered on the front panel keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
The clock also can be synchronized to the local computer time among several UR devices. Use the Synchronize Devices
entry in the Online Window area of the EnerVista software. (Click the button at the top of the window that opens.)
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time or the
manually synchronized time is over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.

7.1.4 Relay maintenance


COMMANDS  RELAY MAINTENANCE
 COMMANDS PERFORM LAMP TEST? Range: No, Yes
 RELAY MAINTENANCE  No

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-3


COMMANDS MENU CHAPTER 7: COMMANDS AND TARGETS

PERFORM LCD TEST? Range: Off, Red, Green, Blue, White & Text Pattern,
 Off Black & Text Pattern, TV Test Pattern

PERFORM PUSHBUTTON Range: No, Yes


 TEST? No

UPDATE ORDER CODE? Range: No, Yes


 No

REBOOT RELAY? Range: No, Yes


 No

SERVICE COMMAND Range: 0, 101, 20511


 0

SAVE VOLATILE DATA? Range: No, Yes


 No

This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the ENTER key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the ENTER key.
Not all commands display in the software; use the front panel when required.
PERFORM LAMP TEST — Turns on all front panel LEDs and display pixels for a short duration.
PERFORM LCD TEST — This command detects either stuck-ON or stuck-OFF pixels (dead pixels) in the display screen on the
graphical front panel. RED/GREEN/BLUE is to display the solid background color in the whole screen. WHITE & TEXT
PATTERN shows the white background and black texts. BLACK & TEXT PATTERN shows the black background and white
texts. TV TEST PATTERN displays a standard television test pattern (SMPTE color bars). The test screen can be canceled by
pressing any pushbutton or after 30 seconds of inactivity.
PERFORM PUSHBUTTON TEST — This command tests the pushbuttons on the graphical front panel. During testing, press the
corresponding pushbutton according to the prompt text. A failure message is given if the expected action is not detected
in one minute. Holding the ESCAPE button for five seconds to interrupt the test sequence. The designated function of a
specific pushbutton is bypassed in the test.
UPDATE ORDER CODE — Use this command to read and update the order code, for example when hardware modules have
been changed inside the relay. It causes the relay to scan the backplane for the modules and update the order code to
match. All settings are defaulted with an update. When an update occurs, the following message displays and the relay
restarts.

UPDATING...
PLEASE WAIT
7 There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
REBOOT RELAY — Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
made to the configuration settings these changes do not take effect unless the relay is rebooted.

With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.

SERVICE COMMAND — Performs specific F60 service actions. Presently, there are two service actions available. Code "20511"
returns all settings to their factory default value and restarts the relay (then you re-enter IP address, restart, set unit to
"Programmed"). Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code
other than these two is entered, the command is ignored and no action is taken. Various self-checking diagnostics are
performed in the background while the F60 is running, and diagnostic information is stored on the non-volatile memory
from time to time based on the self-checking result. Although the diagnostic information is cleared before the F60 is
shipped from the factory, the user can want to clear the diagnostic information for themselves under certain
circumstances. For example, you clear diagnostic information after replacement of hardware. Once the diagnostic
information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from scratch.

7-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS COMMANDS MENU

SAVE VOLATILE DATA — Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.

7.1.5 Phasor Measurement Unit one-shot


COMMANDS  PMU ONE-SHOT
 COMMANDS PMU ONE-SHOT Range: Enabled, Disabled
 PMU ONE-SHOT  FUNCTION: Disabled

PMU ONE-SHOT Range: 0 to 99 in steps of 1


 FRACTIONAL SEC: 0

PMU ONE-SHOT TIME: Range: YYYY/MM/DD HH:MM:SS


 2020/06/14 7:58:35

This feature allows pre-scheduling of a PMU measurement at a specific point in time. It can be used to test for accuracy of
the PMU and for manual collection of synchronized measurements through the system, as explained here.
When enabled, the function continuously compares the present time with the pre-set PMU ONE-SHOT TIME. When the two
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set PMU
ONE-SHOT FRACTIONAL SEC. When the two numbers match, the function freezes the synchrophasor actual values and the
corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the pre-
set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus or
DNP, and the EnerVista UR Setup software).
When freezing the actual values, the function also asserts a PMU ONE-SHOT OP FlexLogic operand. This operand can be
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to
verify the accuracy of the PMU under test.
With reference to the following figure, the PMU one-shot function (when enabled) controls three FlexLogic operands:
• The PMU ONE-SHOT EXPIRED operand indicates that the one-shot operation has been executed, and the present
time is at least 30 seconds past the scheduled one-shot time
• The PMU ONE-SHOT PENDING operand indicates that the one-shot operation is pending; that is, the present time is
before the scheduled one-shot time
• The PMU ONE-SHOT OP operand indicates the one-shot operation and remains asserted for 30 seconds afterwards
When the function is disabled, all three operands are de-asserted.
The one-shot function applies to all logical PMUs of a given F60 relay.
Figure 7-1: PMU one-shot FlexLogic operands
7

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-5


COMMANDS MENU CHAPTER 7: COMMANDS AND TARGETS

7.1.5.1 Testing accuracy of the PMU


The one-shot feature is used to test accuracy of the synchrophasor measurement. GPS-synchronized tests sets perform a
similar function to PMUs; instead of measuring the phasor from physical signals with respect to the externally provided
time reference, they produce the physical signals with respect to the externally provided time reference, given the desired
phasor values. Therefore the GPS-synchronized test sets cannot be automatically assumed more accurate than the PMUs
under test. This calls for a method to verify both the measuring device (PMU) and the source of signal (test set).
With reference to the following figure, the one-shot feature can be configured to trigger a high-accuracy scope to capture
both the time reference signal (rising edge of the 1 pps signal of the IRIG-B time reference) and the measured waveform.
The high-accuracy high-sampling rate record of the two signals captured by the scope can be processed using digital
tools to verify the magnitude and phase angle with respect to the time reference signal. As both the time reference and the
measured signals are raw inputs to the PMU under test, their independently captured record, processed using third-party
software, is a good reference point for accuracy calculations. Such a record proves useful when discussing the test results,
and can be retained as a part of the testing documentation.
Figure 7-2: Using the PMU one-shot feature to test synchrophasor measurement accuracy

7.1.5.2 Collecting synchronized measurements ad hoc


The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMUs
can be pre-scheduled to freeze their measurements at the same time. When frozen, the measurements can be collected
7 using the EnerVista software or a protocol client.

7.1.6 Security
COMMANDS  SECURITY
 SECURITY ADMINISTRATOR Range: Yes, No
  LOGOFF: No

ENGINEER Range: Yes, No


 LOGOFF: No

OPERATOR Range: Yes, No


 LOGOFF: No

CLEAR SECURITY DATA: Range: Yes, No


 No

With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.
ENGINEER LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.

7-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

OPERATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.
CLEAR SECURITY DATA — Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.

7.2 Targets menu

TARGETS


PHASE TOC4 Displayed only if targets for this element are active.
 OP: A B - Example shown.

DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
 LATCHED Example shown.


A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target
messages of all the devices inserted into that site.
Each F60 element with a TARGET setting has a target message that when activated by its element is displayed in sequence
with any other currently active target messages in the TARGETS menu. In the example shown, the Phase TOC4 and Digital
Element 48 target settings are active and so have their targets displayed. The down arrow below the two elements
indicates that there can be other active elements beyond these two.
For more information, see the description of target messages in the next section, and the Introduction to Elements section
in the Settings chapter for instructions on TARGET setting.
When no targets are active, the display reads NO ACTIVE TARGETS.

7.2.1 Target messages


When there are no active targets, the first target to become active causes the display to immediately default to that
message. If there are active targets and the user is navigating through other messages, and when the default message
timer times out (i.e. the keypad has not been used for a determined period of time), the display again defaults back to the
target message. 7
The range of variables for the target messages is described below. Phase information is included if applicable. If a target
message status changes, the status with the highest priority displays.
Table 7-1: Target message priority status
Priority Active status Description
1 OP element operated and still picked up
2 PKP element picked up and timed out
3 LATCHED element had operated but has dropped out

If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-7


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

7.2.2 Relay self-tests

7.2.2.1 Description
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major
and minor) are listed in the following tables. When either type of error occurs, the Trouble LED Indicator turns on and a
target message displays. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module de-energizes
• All other output relays de-energize and are prevented from further operation
• The front panel In Service LED indicator turns off
• A RELAY OUT OF SERVICE event is recorded
To view error messages in EnerVista software:
1. Access Actual Values > Records > Event Records.

Messages display on the front panel with one or two lines of text. An example is as follows. In the tables that follow,
messages are grouped using the first line of text. For example, MAINTENANCE ALERT, then a row for 4L Discrepancy, then a
row for Bad IRIG-B Signal.

MAINTENANCE ALERT:
4L Discrepancy

MAINTENANCE ALERT:
Bad IRIG-B Signal

7.2.2.2 Major self-test error messages


The major self-test errors are outlined in this section.
Table 7-2: Major self-test errors
Error Latched? Description Test frequency Action
DIAGNOSTIC FAILURE ___:

7 Self Test Error No Internal recovery failure


detected
Upon recovery Extract a Service Report through UR
Setup software. Contact technical
support and supply details of the
failure code on the display.
EQUIPMENT MISMATCH:
2nd line detail No The number or type of On power up. Check all modules against the order
installed hardware modules Afterwards, the code, ensure they are inserted
does not match the order backplane is properly, and cycle control power. If a
code stored in the F60. An checked for missing module has intentionally been added
example is when a basic front cards every five or removed, refresh the order code
panel is installed and the seconds under Device Setup. If the problem
order code on the F60 persists, contact the factory.
expects a graphical front
panel. As another example,
"Card F8L Missing" means
that hardware module 8L is
missing from slot F inside the
UR device.
FLEXLOGIC ERROR:
2nd line detail No A FlexLogic equation is Event driven, Finish all equation editing and use self
incorrect performed whenever tests to debug any errors.
FlexLogic equations
are modified

7-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

Error Latched? Description Test frequency Action


RAM FILESYSTEM FAIL:
Self-Test Error Yes The relay failed to create the On relay startup Contact factory service
RAM file system
SYSTEM FAILURE ___:
2nd line detail Yes Relay system failure detected Continuous Extract a Service Report through UR
Setup software. Contact technical
support and supply details of the
failure code on the display.
SYSTEM FAILURE:
Card F8L Yes This is an indication that the The recommendation is to replace this
DSP module has failed. The DSP. Extract a Service Report through
slot and DSP type are UR Setup software and provide it to GE
indicated in the message. customer service.
TO INSTALL SETTINGS:
CHECK LOG AND REBOOT Yes Certain settings require a A new CID is sent Restart relay
reboot to be applied, for and it includes
example DNP settings, IEC changes in settings
104 settings. After a CID file that require a reboot
was send to the relay, a to be
manual reboot of the relay is applied
required to apply those
settings that require a
reboot
UNIT NOT PROGRAMMED:
Check Settings No The PRODUCT SETUP  On power up and Program all settings and then set
INSTALLATION  RELAY whenever the PRODUCT SETUP  INSTALLATION
SETTINGS setting indicates PRODUCT SETUP  RELAY SETTINGS to “Programmed”
the F60 is not programmed  INSTALLATION
 RELAY SETTINGS
setting is altered

7.2.2.3 Minor self-test error messages


Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
Table 7-3: Minor self-test errors
Error Latched? Description Test frequency Action
AGGREGATOR ERROR: No The second line of this self-
test error indicates the
problem with the PMU
Each time a PMU’s
related settings is
changed
Correct the problem indicated in the
second line or contact the factory 7
Aggregator
DIAGNOSTIC ALARM COP:
Self-test Error Yes This is a preliminary warning Module or feature Extract a Service Report through UR
that transient errors were dependent Setup software and provide it to GE
detected in the coprocessor. customer service
The relay remains operational
but some elements can
operate slightly delayed.
DIAGNOSTIC ALARM DSP:
Card F8L Yes This is a preliminary warning Every protection Extract a Service Report through UR
that there is something wrong pass Setup software and provide it to GE
with a DSP. The slot and DSP customer service
type is indicated in the
message.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-9


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

Error Latched? Description Test frequency Action


DIAGNOSTICS FAILURE Yes This is a warning that there is Every protection Extract a Service Report through UR
something wrong with the pass Setup software and provide it to GE
DSP/coprocessor subsystem. customer service
The source of the problem is
unknown as there are
multiple contributors.
DIRECT DEVICE OFF:
COMM Path Incomplete No A direct device is configured Every second Check direct input and output
but not connected configuration and wiring
DOS PARTITION ALARM:
SELF-TEST ERROR There is a problem with the On relay power-up Contact the factory
Compact Flash memory in the and afterwards once
CPU module every 24 hours
FACTORY MODE ACTIVE No Factory Mode is active This is a reminder for the Supervisor (if
enabled) or Administrator to disable
Settings > Product Setup > Security >
Supervisory > Factory Service Mode
as soon as it is not needed
LOW ON MEMORY:
with 2nd line detail Yes The relay periodically checks Every five seconds Contact the factory
the amount of free RAM
memory available and the
amount of free stack
available for each task
against pre-defined
thresholds. The second line of
the self-test indicates which
of the tests failed. It asserts
this self-test if those tests fail.
MAINTENANCE ALERT:
4L Discrepancy No A discrepancy has been Upon initiation of a Verify the state of the output contact
detected between the actual contact output state and contact the factory if the problem
and desired state of a change persists
latching contact output of an
installed type “4L” module
Bad IRIG-B Signal No A bad IRIG-B input signal has Monitored whenever Ensure the following:
been detected an IRIG-B signal is - The IRIG-B cable is properly
received connected.
- Proper cable functionality (that is,
check for physical damage or perform
7 a continuity test).
- The IRIG-B receiver is functioning.
- Check the input signal level (it can be
less than specification).
If none of these apply, then contact the
factory.
Bad PB PTP Signal No No PTP enabled port has Activated when no Ensure the following:
Bad PTP Signal good PTP signal input acceptable signal is - The Ethernet cable(s) are properly
being received connected.
- At least one PTP grandmaster-
capable clock is functioning.
- If a strict power profile (PP) is enabled,
that entire network is PP compliant.
- The network is delivering PTP
messages to the relay.
Direct Ring Break No Direct input and output Every second Check direct input and output
settings are configured for a configuration and wiring
ring, but the connection is not
in a ring

7-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

Error Latched? Description Test frequency Action


FIRST ETHERNET FAIL Yes A link loss detection on an Check the connection
SECOND ETHERNET FAIL Ethernet port. The link loss is
THIRD ETHERNET FAIL due to unplugging the cable
or the switch port being
down.
Front Panel Trouble No The graphical front panel is Every second Contact the factory
not responsive for more than
five seconds. The relay is still
protecting, and the main CPU
is not affected by this self-
test.
GFP Version Mismatch No The graphical front panel Whenever Perform a UR firmware upgrade with
firmware revision is not connection is the graphical front panel connected to
synchronized with that of the established between the CPU module in the relay. It can be
CPU module in the relay the graphical front done using any communication
panel and the CPU interface (Ethernet or USB). This
module in the relay synchronizes the graphical firmware
revision with that of the relay. If trouble
persists, contact the factory.
Oscillatory GOOSE No A data item in a configurable Upon scanning of Evaluate all logic pertaining to this item
GOOSE data set is oscillating each configurable
GOOSE data set
Replace Battery Yes The battery is weak or not Every five seconds. Replace the battery as outlined in the
functioning. It powers the real The error message Maintenance chapter. To minimize the
time clock. This message displays after 60 disruption until battery replacement,
displays as Battery Fail in the seconds if the temporarily disable the battery fail
event records. When the problem persists. function under Settings > Product
battery weakness reaches a Setup > User-Programmable Self
critical level, the message Tests.
displays persistently on the
front panel and no front panel
key navigation is possible.
SFP MODULE # FAIL No A faulty small form-factor The web page "SFP Transceiver
pluggable port (SFP) or Information" described in the previous
unplugging of the SFP row applies for this self test as well. The
generates this self test "SFP Module Fail" has higher priority
message and it suppresses the "Ethernet Fail"
target message. The "SFP MODULE FAIL
FUNCTION" setting enables/disables
this self test. The target for this self test
is priority-based, with the third one
being the highest priority. For example,
if all three SFP modules fail, then the
third SFP target is activated. If the third
SFP module failure resolves, then the
7
second SFP target is activated.
SNTP Failure No The SNTP server is not Every 10 to 60 Check that Ethernet cable(s) are
responding seconds properly connected. Check that
configuration for the SNTP server
corresponds to the actual server
settings. Check connectivity to the
server (ping the server IP address).
Check that UR settings for both SNTP
servers are configured with different IP
addresses and port numbers.
PBEthPort-# Offline Process Bus Module Ethernet Every five seconds Check connection to network switch/
port failure. Merging Unit and network switch
Error registers when an
enabled port fails.
PB SFP Module # Fail Small form-factor pluggable Every five seconds Connect or replace with same SFP type
port (SFP) at back of Process
Bus Module is faulty or
unplugged

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-11


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

Error Latched? Description Test frequency Action


PROTOTYPE FIRMWARE:
Self Test Error Seen until the build is tagged Seen on startup and Update firmware to either of these
as being 'release candidate' then continuous builds
or 'gold' build
RRTD COMM FAIL:
Self Test Error No Communications with remote Runs only if "Com2 Check COM2 port settings, check
RTD unit (RRTD) or GPM-F Usage" is set to RRTD RS485 cables
failed for longer than 10 or RRTD&GPM-F.
seconds Checked every five
seconds.
RxGOOSE FAIL:
Missing messages No One or more RxGOOSE The self-test is Check GOOSE setup
messages are not being activated when no
received message is received
within the expected
time interval, which
is the time-to-live
time in the previous
message. This time
can be from
milliseconds to
minutes.
RxGOOSE OFFLINE:
COMM Path Incomplete No One or more RxGOOSE Event driven. The test Check GOOSE setup
messages are not responding is performed when a
device programmed
to receive GOOSE
messages stops
receiving. This can be
from 1 to 60
seconds, depending
on GOOSE packets.
SETTINGS SAVE ERROR:
Contact Factory Yes The relay failed to store the When a setting is Contact the factory
settings to the flash memory changed
STORAGE MEDIA ALARM:
Self Test Error No The CPU module fails to read On power up. Contact the factory
from or write to the Compact Afterwards, every
Flash (CF) card inside the time the CPU
module. The CF card stores accesses the CF card
7 certain non-volatile data,
such as event records,
for reading or writing

oscillography and datalogger


records, fault report values,
and non-volatile actual
values. Settings are not stored
in CF and hence are
unaffected by this self-test.

7-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

Error Latched? Description Test frequency Action


SV# STREAM TROUBLE ON Yes Asserted when Every protection Check:
1. “3 out of 5 lost” errors are pass 1. Connection between Merging Unit
detected (MU) and relay
2. No sampled values have 2. SV stream configuration in the relay
been received for ~2 power is matching the SV stream, for example
cycles check svID and confRev fields
3. Mismatch of test mode or 3. Check the Actual Values > PB
simulation bit between UR Module > RXSV status> rxsv1(16) page
and subscribed SV streams in the EnerVista software to verify the
4. Merging units subscribed Sync Status, Quality, and delays of the
by UR are not synchronized to received sampled values and
the same grandmaster and troubleshoot accordingly
the drift is ~2 power cycles 4. Check that all merging units
5. Sampled values subscribed subscribed by the UR are synchronized
by the relay are not according to the SMPSYNCH CHECK
synchronized according to setting
the SMPSYNCH CHECK
setting defined in the relay
6. Quality of the received
sampled values is not
acceptable (either the quality
is invalid, or questionable with
Quality Check = Reject
Questionable)
SYSTEM EXCEPTION:
Press RESET key Yes Abnormal restart from Event driven Contact the factory
modules being removed or
inserted while the F60 is
powered-up, when there is an
abnormal DC supply, or as a
result of internal relay failure.
TEMP MONITOR:
OVER TEMPERATURE Yes The ambient temperature is Every hour Remove the F60 from service and
greater than the maximum install in a location that meets
operating temperature operating temperature standards
(+80°C)
UNIT NOT CALIBRATED:
with 2nd line DSP slot number Yes DSP module is not calibrated On relay startup The respective DSP module has to be
detail or calibration data is out of replaced, contact factory service
range
VOLTAGE MONITOR:
with 2nd line detail Yes The relay detected a problem Every five seconds
with the internal voltage rails
Contact GE customer service
7
Power Supply 12V Low for longer than 25 seconds
Power Supply 12V High
Power Supply 5V Low
Power Supply 5V High

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-13


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

Error Latched? Description Test frequency Action


WRONG TRANSCEIVER:
Self Test Error Yes The type of SFP does not A web page "SFP Transceiver
match the CPU type. The SFP Information" is provided. This page
is a silver device that plugs displays the type of the SFP in it. This
into the rear of the CPU data is to be used with the CPU type to
module. know the cause of the problem.

T-type CPU = All ports support


fiber SFPs only
U-type CPU = Maintenance
port needs RJ45 SFP and the
other two ports fiber SFPs
V-type CPU = All ports support
RJ45 SFPs only

The consequence of an
incorrect SFP can range from
damage to the F60 to no
power information for the F60
on its web page (enter IP
address in a web browser,
then click the SFP
Transceiver Information —
only the type of SFP displays
and not power data).

7.2.2.4 Instantaneous protection elements trip security


Some self-tests are not fast enough to detect erroneous data and block protection elements, requiring additional
measures. A bit-flip in program memory is typically detected during a memory scan, which may be too late to inhibit
instantaneous protection element. To secure instantaneous elements, in addition to the self-tests described, there are
supervising elements that validate “fault” conditions and release IOC and differential elements operation.
These trip security elements use currents samples and phasors from the same sources as supervised protection elements
to detect independently true “fault” conditions from IOC or differential. Trip security elements do not have any user settings
and are enabled as soon as corresponding instantaneous elements are enabled. During laboratory testing, these elements
can be disabled by activating any IED test mode via the SETTINGS  TESTING  IED MODE CONFIG menu by setting IED
MODE to anything except “On.”
Trip security elements do not affect protection performance in any way.

Instantaneous Overcurrent
7 All enabled Phase IOC, Negative-Sequence, and Neutral IOCs in the active setting group are supervised by the trip security
element. The goals of the IOC trip security are as follows:
• Detect erroneous operate current due to wiring or data acquisition problem resulting in one phase current dropping to
zero, resulting in erroneous negative-sequence and neutral currents
• Justify current phasor magnitude increase with simultaneous current changes from samples
This is achieved by comparing current values of the current phasors and samples change with the values taken two cycles
before. Additionally, trip security elements monitor "pre-fault" current to detect if operate condition is happening as a
result of current decrease instead of increase.
The element is armed when there are no disturbances in currents for five cycles.

Differential elements (bus, transformer, stator, if applicable to the product)


Differential trip security runs for each differential zone. It monitors if differential current increase above the pickup setting
is confirmed by the disturbance detectors 50DD for each differential zone input. When a differential zone fault occurs and
at least two zone inputs carry some load, at least two disturbance detectors have to be activated. Or when there is no load
at any zone inputs (zone is energized but does not carry any load), at least one disturbance detector has to be activated.
Consequently:

7-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

• If there is not any disturbance detector activation in at least one zone input — Differential trip is inhibited
• If there is just one zone input disturbance detector activation but load is present in at least two zone inputs prior to the
“fault” — Differential trip is inhibited
• If there is more than one disturbance detector zone input activation — Differential trip is allowed (normal scenario)
• If differential trip is inhibited by the trip security element —active setting group change is not allowed
Activation of the 50DDs is essential especially when there is load in at least two zone inputs prior to the zone fault.
Sensitivity of the 50DD is defined by the SETTINGS  PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL
setting with a range of 0.002pu to 0.02pu of the zone input CT. In case of the high-resistive zone fault there may be enough
current change in the source zone input causing sufficient differential current, but small change in the load zone input-this
situation can be addressed by reducing CURRENT CUTOFF LEVEL setting to the sufficient sensitivity level. 50DD operates if
there is a change at least 2 x CUTOFF in either positive-sequence, or negative sequence or zero-sequence currents.

7.2.2.5 HardFiber major self-test error messages


In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95Plus, see that product’s instruction manual.
Table 7-4: HardFiber major self-test errors
Error Description Severity Action
EQUIPMENT MISMATCH The number or type of installed Protection is not Check all modules against the order code. Ensure
hardware modules does not available and all they are inserted properly, and cycle the control
match the order code stored in contact outputs and power. If a module has intentionally been added
the CPU. The standard UR-series shared outputs are de- or removed use the Update Order Code
Equipment Mismatch self-test is asserted command to notify the relay that the current
extended to cover the possible module configuration is correct.
presence of a Process Card.
MODULE FAILURE UR-series device module Protection is not Contact the factory and supply the failure code
hardware failure detected available and all noted in the display. Text in the message
contact outputs and identifies the failed module (for example, H81). If
shared outputs are de- operated on a Process Card failure, the Module
asserted Fail self-test seals-in (latches) till the UR-series
device is restarted.
PROCESS BUS FAILURE Mission critical data is not Protection is not First rectify any Process Bus Trouble and Brick
available via the process bus. An available and all Trouble self-test errors. Check the actual value of
AC quantity is considered critical contact outputs and the operand referenced by the Process Bus
if both AC bank origins and the shared outputs are de- Failure Operand setting, and if “On,” determine
crosschecking settings are other asserted the cause and rectify.
than None. This self-test is also
initiated by an AC input
discrepancy being detected. See
If the problem persists with the foregoing all clear,
the cause must be an AC input discrepancy, 7
the description in the which is typically the result of problems in the
Crosschecking setting in the input signals to the Bricks, or faults in the Brick
HardFiber manual for further input conditioning hardware. If the error was
information. In addition, this self- annunciated the first time significant signal was
test can be initiated by user logic encountered, suspect the former cause and
responding to loss of critical check the copper connections external to the
contact input/output or other Brick. Where multiple UR-series devices have
data using the Process Bus self-test errors, look for common causes.
Failure Operand user-
programmable self-test setting. To further isolate AC input discrepancy errors, put
This setting is located in the the relay in test-isolated mode, then one by one,
Settings > Product Setup > temporally change an AC bank Crosschecking
User-Programmable Self Test setting to None, until the Process Bus Failure
menu. clears. Once the problem AC bank has been
identified, the values from each of the two Bricks
can be examined individually by temporarily
mapping each to an AC bank with a single origin.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-15


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

7.2.2.6 HardFiber minor self-test error messages

Table 7-5: HardFiber minor self-test errors


Error Description Severity Action
BRICK TROUBLE Brick internal self-testing has This self-test error does Check the Brick environment for over/under
detected trouble internal to the not directly inhibit temperatures and the voltage of its power
Brick protection. However, source. If the ambient temperature and supply
some or all of the voltage are within Brick specifications, consult
affected Brick inputs/ the factory. Troubles resulting from a Brick output
outputs may not be failing to respond to an output command can
available to the UR only be detected while the command is active,
device. and so in this case the target is latched. A latched
target can be unlatched by pressing the front
panel reset key if the command has ended,
however the output can still be non-functional.
PROCESS BUS TROUBLE Communications problems with This self-test error does Check the field unit actual values. An indication of
one or more Bricks. The text of not directly inhibit equipment mismatch means that messages are
the message identifies the protection. However, being received from a Brick, but there is a
affected field units. This self-test the affected Brick discrepancy between the settings and the actual
is initiated by low received signal inputs/outputs may Brick serial number, order code, and/or core
levels at either the Brick or not be available to the number.
Process Card end, and by the UR device.
sustained failure to receive poll Check that the correct core on the correct Brick is
responses from the proper Brick. patched through to the correct Process Card
port, and that the field unit settings are correct.
An indication of communications loss means that
no messages are being received.

Check that the patching is correct, and that the


Brick has power. If that is not the problem, use a
professional optical fiber connector cleaning kit
to clean both sides of all optical fiber connections
from the Process Card through to the affected
Brick. If the problem continues after cleaning,
consult the factory.
RTD TROUBLE:
Self Test Error The Brick is reporting that the Not latched Check field RTD settings and connections
sensed RTD field connection
does not match that of an RTD or
the reported DC input value is
outside of the RTD temperature
range, greater than 250°C (likely
7 open sensor circuit fault) or less
than -50°C (likely shorted sensor
fault).
TDR TROUBLE:
Self Test Error The Brick is reporting that the Not latched Check field transducer settings and connections
sensed transducer field
connection does not match that
of a transducer, or the reported
DC input value is outside of the
set transducer input range, or
the minimum value setting is
equal to the maximum value
setting.

7.2.2.7 Instantaneous protection elements trip security


Some self-tests are not fast enough to detect erroneous data and block protection elements, requiring additional
measures. A bit-flip in program memory is typically detected during a memory scan, which may be too late to inhibit
instantaneous protection element. To secure instantaneous elements, in addition to the self-tests described, there are
supervising elements that validate “fault” conditions and release IOC and differential elements operation.

7-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 7: COMMANDS AND TARGETS TARGETS MENU

These trip security elements use currents samples and phasors from the same sources as supervised protection elements
to detect independently true “fault” conditions from IOC or differential. Trip security elements do not have any user settings
and are enabled as soon as corresponding instantaneous elements are enabled. During laboratory testing, these elements
can be disabled by activating any IED test mode via the SETTINGS  TESTING  IED MODE CONFIG menu by setting IED
MODE to anything except “On.”
Trip security elements do not affect protection performance in any way.

Instantaneous Overcurrent
All enabled Phase IOC, Negative-Sequence, and Neutral IOCs in the active setting group are supervised by the trip security
element. The goals of the IOC trip security are as follows:
• Detect erroneous operate current due to wiring or data acquisition problem resulting in one phase current dropping to
zero, resulting in erroneous negative-sequence and neutral currents
• Justify current phasor magnitude increase with simultaneous current changes from samples
This is achieved by comparing current values of the current phasors and samples change with the values taken two cycles
before. Additionally, trip security elements monitor "pre-fault" current to detect if operate condition is happening as a
result of current decrease instead of increase.
The element is armed when there are no disturbances in currents for five cycles.

Differential elements (bus, transformer, stator, if applicable to the product)


Differential trip security runs for each differential zone. It monitors if differential current increase above the pickup setting
is confirmed by the disturbance detectors 50DD for each differential zone input. When a differential zone fault occurs and
at least two zone inputs carry some load, at least two disturbance detectors have to be activated. Or when there is no load
at any zone inputs (zone is energized but does not carry any load), at least one disturbance detector has to be activated.
Consequently:
• If there is not any disturbance detector activation in at least one zone input — Differential trip is inhibited
• If there is just one zone input disturbance detector activation but load is present in at least two zone inputs prior to the
“fault” — Differential trip is inhibited
• If there is more than one disturbance detector zone input activation — Differential trip is allowed (normal scenario)
• If differential trip is inhibited by the trip security element —active setting group change is not allowed
Activation of the 50DDs is essential especially when there is load in at least two zone inputs prior to the zone fault.
Sensitivity of the 50DD is defined by the SETTINGS  PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL
setting with a range of 0.002pu to 0.02pu of the zone input CT. In case of the high-resistive zone fault there may be enough
current change in the source zone input causing sufficient differential current, but small change in the load zone input-this
situation can be addressed by reducing CURRENT CUTOFF LEVEL setting to the sufficient sensitivity level. 50DD operates if 7
there is a change at least 2 x CUTOFF in either positive-sequence, or negative sequence or zero-sequence currents.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-17


TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS

7-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 8: Commissioning

Commissioning

This chapter outlines how to test frequency timing.

8.1 Testing
8.1.1 Testing underfrequency and overfrequency elements
Underfrequency and overfrequency protection requires techniques with subtle testing implications. Whereas most
protection is designed to detect changes from normal to fault conditions that occur virtually instantaneously, power
system inertia requires frequency protection to pick up while the frequency is changing slowly. Frequency measurement is
inherently sensitive to noise, making high precision in combination with high speed challenging for both relays and test
equipment.
Injection to a particular F60 frequency element must be to its configured source and to the channels that the source uses
for frequency measurement. For frequency measurement, a source uses the first quantity configured in the following
order:
1. Phase voltages
2. Auxiliary voltage
3. Phase currents
4. Ground current
For example, if auxiliary voltage and phase currents are configured, the source uses the auxiliary voltage, not the phase
voltages or any of the currents.
When phase voltages or phase currents are used, the source applies a filter that rejects the zero-sequence component. As
such, the same signal must not be injected to all three phases, or the injected signal is completely filtered out. For an
underfrequency element using phase quantities, the phase A signal must be above the MIN VOLT/AMP setting value.
Therefore, either inject into phase A only, or inject a balanced three-phase signal.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 8-1


TESTING CHAPTER 8: COMMISSIONING

Figure 8-1: Typical underfrequency element test timing

Frequency Injection frequency

Source frequency

Tracking frequency

Pickup
frequency

Relay conditioning time

Source frequency calculation delay

Time
Underfrequency element detection time

Underfrequency element pickup


set “pickup delay”

Underfrequency element operate


831771A1.CDR

The static accuracy of the frequency threshold is determined by slowly adjusting the frequency of the injected signal about
the set pickup. If the F60 frequency metering feature is used to determine the injected frequency, verify the metering
accuracy by checking it against a known standard (for example, the power system).
To accurately measure the time delay of a frequency element, a test emulating realistic power system dynamics is
required. Let the injected frequency ramp smoothly through the set threshold, with the ramp starting frequency sufficiently
outside the threshold so that the relay becomes conditioned to the trend before operation. For typical interconnected
power systems, the recommended testing ramp rate is 0.20 Hz/s.
The required delay time is the interval from the point the frequency crosses the set threshold to the point that the element
operates. Some test sets can measure only the time from the ramp start to element operation, necessitating the
subtraction of the pre-threshold ramp time from the reading. For example, with a ramp rate of 0.20 Hz/s, start the ramp
0.20 Hz before the threshold and subtract 1 second from the test set time reading of ramp start to relay operation.
Note that the F60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time
taken by the frequency responding component to pickup.
F60 oscillography can be used to measure the time between the calculated source frequency crossing the threshold and
8 element operation; however, this method omits the delay in the calculated source frequency. The security features of the
source frequency measurement algorithm result in the calculated frequency being delayed by two to four cycles (or longer
with noise on the input). In addition, oscillography resolution is 0.004 Hz, which at 0.20 Hz/s corresponds to a delay of 20
ms. Do not use the tracking frequency in timing measurements, as its algorithm involves phase locking, which purposely
sets its frequency high or low to allow the F60 sample clock to catch-up or wait as necessary to reach synchronism with
the power system.

8-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 9: Theory of operation

Theory of operation

This chapter outlines advanced information on operation.

9.1 High-impedance (Hi-Z) fault detection


9.1.1 Description
The Hi-Z element accomplishes high-impedance fault detection using a variety of algorithms, all coordinated by an expert
system. At the heart of the high-impedance fault-detection system is the identification of arcing on a feeder. If the Hi-Z
element detects arcing, it then determines whether or not the arcing persists for a significant period of time. If it does, the
Hi-Z element determines whether the persistent arcing is from a downed conductor or from an intact conductor and then
generates an output to indicate either the detection of a downed conductor or the detection of arcing, respectively.
Distinction between an arcing intact conductor and an arcing downed conductor is determined by looking at patterns in
the load current at the beginning of the fault. A downed conductor is indicated when a precipitous loss of load or an
overcurrent condition precedes arcing detection. Otherwise, the Hi-Z element assumes that the line is intact, even if arcing
is present. In such a case, if the detected arcing can be classified as persistent, and an output contact is configured for
'arcing detected,' the Hi-Z element closes that contact.
In some cases, arcing is determined to be present, but not persistent. For example, when it is caused by tree limb contact
or insulator degradation, arcing typically is present intermittently with relatively long periods of inactivity (such as minutes)
interspersed. In such cases, arcing can be affected by such factors as the motion of a tree limb or the moisture and
contamination on an insulator. Conditions such as these, characterized by a high number of brief occurrences of arcing
over an extended period of time (for example from a fraction of an hour to one or two hours), lead the Hi-Z element to
recognize and flag an “arcing suspected” event. None of these brief occurrences of arcing, if taken individually, are
sufficient to indicate detection of a downed conductor or to set off an alarm indicating that persistent arcing has been
detected. When considered cumulatively, however, they do indicate a need for attention. If an output contact is configured
to indicate 'arcing suspected,' the Hi-Z element recognition of such sporadic arcing closes that contact and appropriate
actions can be taken.
If the Hi-Z element determines that a downed conductor exists, oscillography and fault data are captured. In addition,
target messages and appropriate LEDs are activated on the relay faceplate.
The detection of a downed conductor or arcing condition is accomplished through the following algorithms:
• Energy algorithm
• Randomness algorithm
• Expert Arc Detector algorithm

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 9-1


HIGH-IMPEDANCE (HI-Z) FAULT DETECTION CHAPTER 9: THEORY OF OPERATION

• Load Event Detector algorithm


• Load Analysis algorithm
• Load Extraction algorithm
• Arc Burst Pattern Analysis algorithm
• Spectral Analysis algorithm
• Arcing-Suspected Identifier algorithm
• Even Harmonic Restraint algorithm
• Voltage Supervision algorithm
The following sections explain the algorithms.

9.1.2 Energy algorithm


The Energy algorithm monitors a specific set of non-fundamental frequency component energies of phase and neutral
current. After establishing an average value for a given component energy, the algorithm indicates arcing if it detects a
sudden, sustained increase in the value of that component. The Hi-Z element runs the Energy algorithm on each of the
following parameters for each phase current and for the neutral:
• Even harmonics
• Odd harmonics
• Non-harmonics
On a 60 Hz system, the non-harmonic component consists of a sum of the 30, 90, 150,..., 750 Hz components, while on a 50
Hz system, it consists of a sum of the 25, 75, 125,..., 625 Hz components. If the Energy algorithm detects a sudden,
sustained increase in one of these component energies, it reports this to the Expert Arc Detector algorithm, resets itself,
and continues to monitor for another sudden increase.

9.1.3 Randomness algorithm


The Randomness algorithm monitors the same set of component energies as the Energy algorithm but differs slightly.
Rather than checking for a sudden, sustained increase in the value of the monitored component energy, it looks for a
sudden increase in a component followed by highly erratic behavior. This type of highly erratic behavior is indicative of
many arcing faults. Just as with the Energy algorithm, if the Randomness algorithm detects a suspicious event in one of its
monitored components, it reports it to the Expert Arc Detector algorithm, resets itself, and continues to monitor for another
suspicious event.

9.1.4 Expert Arc Detector algorithm


The Expert Arc Detector algorithm assimilates the outputs of the basic arc detection algorithms into one "arcing
confidence" level per phase. Note that there are actually 24 independent basic arc detection algorithms, since both the
Energy algorithm and the Randomness algorithm are run for the even harmonics, odd harmonics, and non-harmonics for
each phase current and for the neutral. The assimilation performed by the Expert Arc Detector algorithm, then, is
accomplished by counting the number of arcing indications determined by any one of the 24 algorithms over a short
period of time (for example the last 30 seconds). Also taken into account is the number of different basic algorithms that
indicate arcing.
In the Expert Arc Detector algorithm, the arcing confidence level for each phase increases as the number of basic
algorithms that indicate arcing (per phase) increases. It also increases with increasing numbers of indications from any
9 one basic algorithm. These increases in confidence levels occur because multiple, consecutive indications from a given
algorithm and indications from multiple independent algorithms are more indicative of the presence of arcing than a
single algorithm giving a single indication.

9-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 9: THEORY OF OPERATION HIGH-IMPEDANCE (HI-Z) FAULT DETECTION

9.1.5 Spectral Analysis algorithm


The Spectral Analysis algorithm is the third and final confirmation algorithm performed only when a high impedance
condition is suspected.
The Spectral Analysis algorithm receives five seconds of averaged non-harmonic residual current spectrum data and
compares it to an ideal 1 / f curve. Depending on the result, three percent can be added to the arcing confidence level
generated by the Expert Arc Detector algorithm.

9.1.6 Load Event Detector algorithm


The Load Event Detector algorithm examines, on a per-phase basis, one reading of RMS values per two-cycle interval for
each phase current and the neutral. It then sets flags for each phase current and for the neutral based on the following
events:
• An overcurrent condition
• A precipitous loss of load
• A high rate-of-change
• A significant three-phase event
• A breaker open condition
These flags are examined by the Load Analysis algorithm. Their states contribute to that algorithm's differentiation
between arcing downed conductors and arcing intact conductors, and inhibit the Expert Arc Detector algorithm from
indicating the need for an arcing alarm for a limited time following an overcurrent or breaker open condition.
Any of these five flags zero the Expert Arc Detector buffer, since the power system is in a state of change and the values
being calculated for use by the Energy and Randomness algorithms are probably not valid.
An extremely high rate of change is not characteristic of most high impedance faults and is more indicative of a breaker
closing, causing associated inrush. Since this type of inrush current causes substantial variations in the harmonics used by
the high impedance algorithms, these algorithms ignore all data for several seconds following a high rate-of-change event
that exceeds the associated rate-of-change threshold, in order to give the power system a chance to stabilize.

9.1.7 Load Analysis algorithm


The Load Analysis algorithm differentiates between arcing downed conductors and arcing intact conductors by looking for
a precipitous loss of load and/or an overcurrent disturbance at the beginning of an arcing episode. The presence of arcing
on the system is determined based on the output of the Expert Arc Detector algorithm. If the Hi-Z element finds persistent
arcing on the power system, the Load Analysis algorithm then considers the type of incident that initiated the arcing and
classifies the arcing conductor as either downed or intact. Another function of the algorithm is to provide coordination
between the Hi-Z element and the power system's conventional overcurrent protection by observing a timeout, via the HI-
Z OC PROTECTION COORD TIMEOUT setting from the beginning of the arcing before giving an indication of arcing.
If the Load Analysis algorithm determines that a downed conductor or arcing exists, it attempts to determine the phase on
which the high impedance fault condition exists. It does this in a hierarchical manner. First, if a significant loss of load
triggered the Load Analysis algorithm, and if there was a significant loss on only one phase, that phase is identified. If there
was not a single phase loss of load, and if an overcurrent condition on only one phase triggered the algorithm, that phase
is identified. If both of these tests fail to identify the phase, the phase with a significantly higher confidence level (for
example higher than the other two phases by at least 25%) is identified. Finally, if none of these tests provides phase
identification, the result of the Arc Burst Pattern Analysis algorithm is checked. If that test fails, the phase is not identified.

9.1.8 Load Extraction algorithm 9


The Load Extraction algorithm attempts to find a quiescent period during an arcing fault so that it can determine the
background load current level in the neutral current. If it is successful in doing so, it then removes the load component
from the total measured current, resulting in a signal that consists only of the fault component of the neutral current. This
information is then provided as input to the Arc Burst Pattern Analysis algorithm.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 9-3


FAULT LOCATOR CHAPTER 9: THEORY OF OPERATION

9.1.9 Arc Burst Pattern Analysis algorithm


The Arc Burst Pattern Analysis algorithm attempts to provide faulted phase identification information based on a
correlation between the fault component of the measured neutral current and the phase voltages. The phase identified is
the one whose phase voltage peak lines up with the neutral current burst. The fault component is received from the Load
Extraction algorithm. The result of the analysis is checked by the Load Analysis algorithm if its other phase identification
methods prove unsuccessful.

9.1.10 Arcing Suspected algorithm


The purpose of the Arcing Suspected algorithm is to detect multiple, sporadic arcing events. If taken individually, such
events are not sufficient to warrant an arcing alarm. When taken cumulatively, however, these events do warrant an alarm
to system operators so that the cause of the recurrent arcing can be investigated.

9.1.11 Overcurrent disturbance monitoring


This function is part of High Impedance Fault Detection and is not be confused with conventional overcurrent protection.
The Hi-Z element monitors for an overcurrent condition on the feeder by establishing overcurrent thresholds for the
phases and for the neutral and then checking for a single two-cycle RMS current that exceeds those thresholds.
Oscillography and fault data are captured if it is determined that an overcurrent condition exists.

9.1.12 Hi-Z Even Harmonic Restraint algorithm


Every two-cycle interval, the algorithm evaluates the even harmonic content of each phase current. The even harmonic
content is evaluated as a percentage of the phase RMS current. If for any phase the percentage is greater than the HI-Z
EVEN HARMONIC RESTRAINT setting, the algorithm inhibits setting of the overcurrent flags. This is to prevent a cold-load
pickup event from starting the Hi-Z logic sequence (which requires the overcurrent flag or the loss-of-load flag to be set at
the beginning of an arcing event). The duration over which the algorithm inhibits the setting of the overcurrent flag(s) is
from the time the even-harmonic level (as a percentage of RMS) increases above the threshold until one second after it
falls back below the threshold.

9.1.13 Hi-Z Voltage Supervision algorithm


This algorithm was implemented to minimize the probability of a false Hi-Z indication due to bus voltage dips, for example
from parallel feeder faults. A fault on a parallel line can cause voltage dips that produce a decrease in the line load that
can be mistaken by the Hi-Z element as Loss of Load.
Every two cycles, the voltage on each phase is checked against the HI-Z V SUPV THRESHOLD. If the voltage on any phase has
dropped by a percentage greater than or equal to this setting, the Loss of Load flag is blocked. The blocking is not done on
a per-phase basis. If one phase voltage shows a dip, the block is applied for all phases. Also the High Impedance
Oscillography records that a voltage dip was experienced. The Oscillography record is phase-specific.

9.2 Fault locator


9.2.1 Fault type determination
9 Fault type determination is required for calculation of fault location. The algorithm uses the angle between the negative
and positive sequence components of the relay currents. To improve accuracy and speed of operation, the fault
components of the currents are used; that is, the pre-fault phasors are subtracted from the measured current phasors. In
addition to the angle relationships, certain extra checks are performed on magnitudes of the negative and zero-sequence
currents.
The single-ended fault location method assumes that the fault components of the currents supplied from the local (A) and
remote (B) systems are in phase. The figure shows an equivalent system for fault location.

9-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 9: THEORY OF OPERATION FAULT LOCATOR

Figure 9-1: Equivalent system for fault location

distance to fault
Remote
Local bus bus
ZA IA mZ (1-m)Z IB ZB

IF

EA VF RF EB
VA VB

842780A2.CDR

The following equations hold true for this equivalent system.

VA = m ˜ Z ˜ IA + RF ˜ I F Eq. 9-1

where
m = sought pu distance to fault
Z = positive sequence impedance of the line
IF = fault current flowing through the fault point
The fault network during a fault can be decomposed into a pre-fault and a pure-fault network. Therefore, the fault current
IF is calculated as follows by using the current division rule in the pure-fault network.

ZA + Z + ZB 1
I F = --------------------------------
- ˜ I = --- ˜ I
1 – m Z + Z B AF d AF Eq. 9-2

where
d is the current distribution factor, which is a complex value
Substituting the second equation into the first equation and multiplying both sides by the complex conjugate of IAF,

1
V A ˜ I AF = m ˜ Z ˜ I A ˜ I AF + R F ˜ --- ˜ I AF 2 Eq. 9-3
d

where
* denotes complex conjugate
Assuming the system is homogeneous, d is then a real number. The fault resistance does not have any imaginary part. The
preceding equation solved for the unknown m yields the following fault location algorithm:

Im V A ˜ I AF
m = -------------------------------------
- Eq. 9-4
Im Z ˜ I A ˜ I AF

where
Im( ) stands for the imaginary part of a complex number
Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before 9
applying the preceding equation (the superscripts denote phases, the subscripts denote stations).
For AG faults:

A A A A
VA = VA , I A = I A + K 0 ˜ I 0A + Z 0M e Z ˜ I 0M , I AF = I A – I Apre Eq. 9-5

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 9-5


FAULT LOCATOR CHAPTER 9: THEORY OF OPERATION

For BG faults:

B B B B
VA = VA , I A = I A + K 0 ˜ I 0A + Z 0M e Z ˜ I 0M , I AF = I A – I Apre Eq. 9-6

For CG faults:

C C C C
VA = VA , I A = I A + K 0 ˜ I 0A + Z 0M e Z Þ I 0M , I AF = I A – I Apre Eq. 9-7

For AB and ABG faults:

A B A B A B A B
VA = VA – VA , IA = IA – IA , I AF = I A – I A – I Apre – I Apre Eq. 9-8

For BC and BCG faults:

B C B C B C B C
VA = VA – VA , IA = IA – IA , I AF = I A – I A – I Apre – I Apre Eq. 9-9

For CA and CAG faults:

C A C A C A C A
VA = VA – VA , IA = IA – IA , I AF = I A – I A – I Apre – I Apre Eq. 9-10

where K0 is the zero sequence compensation factor (for the first six equations)
Z0M is the mutual zero sequence impedance
I0M = IG/3 and IG is the ground current of the adjacent line. The I0M compensation term is applied for the entirely parallel
line.
For ABC faults, all three AB, BC, and CA loops are analyzed and the final result is selected based upon consistency of the
results.
The element calculates the distance to the fault (with m in miles or kilometers) and the phases involved in the fault.
The relay allows locating faults from delta-connected VTs. If the FAULT REPORT 1 VT SUBSTITUTION setting is set to “None,”
and the VTs are connected in wye, the fault location is performed based on the actual phase to ground voltages. If the VTs
are connected in delta, fault location is suspended.
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “V0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and externally supplied neutral voltage:

1
V A = -- V N + V AB – V CA
3
1
V B = -- V N + V BC – V AB
3
1
V B = -- V N + V CA – V BC Eq. 9-11
3
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “I0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and zero-sequence voltage approximated based on the zero-sequence
current:
9 1
V A = -- V AB – V CA – Z SYS0 I 0
3
1
V B = -- V BC – V AB – Z SYS0 I 0
3
1
V B = -- V CA – V BC – Z SYS0 I 0 Eq. 9-12
3

9-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 9: THEORY OF OPERATION FAULT LOCATOR

where ZSYS0 is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu.
Figure 9-2: Fault locator scheme

SETTINGS
FAULT REPORT 1 Z1
MAG:
FAULT REPORT 1 Z1
ANGLE:
FAULT REPORT 1 Z0
MAG:
FAULT REPORT 1 Z0
ANGLE:
FAULT REPORT 1
LENGTH UNITS:
FAULT REPORT 1
LENGTH:

SETTING FAULT REPORT 1 VT


SUBSTITUTION:
FAULT REPORT
TRIG: FAULT REP 1
SYSTEM Z0 MAG:
Off=0
FAULT REP 1
SYSTEM Z0 ANGLE:
SETTINGS
AND RUN
FAULT REPORT
SOURCE: ACTUAL VALUES
0 FAULT REPORT #
SRC X 50DD OP
3 SEC
IA DATE
IB TIME
IC FAULT TYPE
FAULT
3I_0 LOCATOR 1 FAULT LOCATION
VA or VAB FAULT LOOP RESISTANCE
VB or VBC FAULT LOOP REACTANCE
VC or VCA FAULT# RECLOSE SHOT
Vn or V_0

SHOT # FROM
AUTO RECLOSURE
859748A1.CDR

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 9-7


FAULT LOCATOR CHAPTER 9: THEORY OF OPERATION

9-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Chapter 10: Maintenance

Maintenance

This chapter outlines monitoring, maintenance, repair, storage, and disposal of the hardware and software.

10.1 Monitoring
Devices and data can be monitored.

10.1.1 Devices with Site Targets


To view an overview of devices:
1. Access the Site Targets item in the Online Window area, below the list of devices. It can take a few minutes for all
devices to be read.
2. Acknowledge any messages for unaccessible devices. The Site Targets window opens when done.
Figure 10-1: Site Targets window

10.1.2 Data with Modbus Analyzer


Use the Modbus Analyzer under Maintenance > Modbus Analyzer to monitor the values of the UR device. Use the Modbus
memory map addresses outlined in the UR Family Communications Guide for the entries.
The upper part of the window displays values. The lower part of the window is for factory service use.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-1


MONITORING CHAPTER 10: MAINTENANCE

The first row in the figure shows that Contact Output 1 operation is being monitored. Its Modbus address is CAFA. The
actual value read from the device is 0, which means that it is off.
The second row in the figure shows the Contact Output 1 Name. It has a Modbus address of CAF0 and a default value of
"Cont Op 1." None of Selection column settings render this value because they present the information based on
numbering systems.
Figure 10-2: Modbus Analyzer used to monitor actual values on a UR

Address (HEX) — Modbus address in hexadecimal. See the Modbus memory map in the UR Family Communications Guide
or in the web interface (enter IP address of UR device in a web browser). Convert the decimal address in the Modbus
memory map to hexadecimal.
Modbus Type
Actual Value — To read the data in the UR device
Setting — To read a setting in the UR device
Coil — To read a command in the UR device
# of — Element, input, or output to read. An example is 1 for Contact Output 1.
Selection (examples demonstrate various ways to represent 0)
Hex — A decimal numbering system based on 16 possible values, from 0 to 9 and A to F. An example is 0x0000.
Char — A single unicode character, such as C. An example is 0.
Int — A 32-bit number, either positive or negative. An example is 0.
UInt — Unsigned 32-bit integer, which means that it cannot be negative but can be twice as large as a signed integer. An
example is 0.
Long — A 64-bit number, either positive or negative. An example is 0.
ULong — Unsigned 64-bit number, which means that it cannot be negative but can be twice as large as a signed 64-bit
number. An example is 0.
Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000.
Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000.

Entries are not saved when closing the window.

10

10-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE GENERAL MAINTENANCE

10.2 General maintenance


The F60 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time.
Expected service life is 20 years for UR devices manufactured June 2014 or later when applied in a controlled indoor
environment and electrical conditions within specification.
While the F60 performs continual self-tests, it is recommended that maintenance be scheduled with other system
maintenance. This maintenance can involve in-service, out-of-service, or unscheduled maintenance.

10.2.1 In-service maintenance


1. Visual verification of the analog values integrity, such as voltage and current (in comparison to other devices on the
corresponding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.

10.2.2 Out-of-service maintenance


1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against
relay settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.

To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.

10.2.3 Unscheduled maintenance (system interruption)


View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.

10.3 Retrieve files


Data, oscillography, log, events, routing, ARP, and other files can be transferred using the EnerVista software to a computer
or to a USB flash drive when using the graphical front panel. These files can be requested by technical support staff.
To retrieve a file using EnerVista software:
1. If the CyberSentry option is enabled, log in to the EnerVista software using the Administrator role.
2. In the Online Window area of EnerVista, access Maintenance > Retrieve File. The window opens.
3. Note the destination folder to which the file is to be saved at the top and change it if required. You can copy the path
or open the folder for convenience at this time.
4. Select the file to download from the UR device. 10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-3


RETRIEVE FILES CHAPTER 10: MAINTENANCE

5. Click the Read File button. The file is saved to the destination folder. The EnerVista window remains open to download
additional files.

10.3.1 CyberSentry security event files


CyberSentry security events are available in the following two files: SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG.

10.3.1.1 Security events file


The figure shows the content for the SECURITY_EVENTS.CSV file.
Figure 10-3: Security events file

Time — Local time.


Activity — The actual security event.
1 = Authentication Failed
2 = User Lockout
3 = FW Upgrade
4 = FW Lock
5 = Settings Lock
6 = Settings Change, this can fill the entire event log. Hence it is supported by the already existing
SETTINGS_CHANGE.LOG file. This event is not required.
7 = Clear Oscillography command
8 = Clear Data Logger command
9 = Clear Demand Records command
10 = Clear Energy command
11 = Reset Unauthorized Access
12 = Clear Teleprotection Counters
13 = Clear All Records
14 = Role Log out
15 = Role Log in
16 = Factory Mode enabled
17 = Factory Mode disabled
Change Method — Format code F229 for the settings control change method.
0 = None
1 = Keypad
2 = Front port
3 = COM1 (not used)
4 = COM2 (RS485)
5 = Ethernet

10

10-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE CONVERT DEVICE SETTINGS

10.3.1.2 Setting changes file


The SETTING_CHANGES.LOG file stores all the setting changes. A total of 1024 events are stored in a circular buffer in
volatile memory.
Figure 10-4: Setting changes file

10.4 Convert device settings


Settings files can be upgraded or downgraded to other firmware versions. For example, version 7.4 settings can be
upgraded to version 7.6.
Settings are reset to factory default upon conversion. For a graphical front panel, for example when upgrading from
version 7.6 to 7.7, single-line diagrams and cells configured for the Metering Editor are defaulted, while other graphical
front panel settings are retained.
When converting a settings file from version 7.20 or earlier to 7.70 or later, any IEC 61850 settings are defaulted, and
Edition 2 is used.
When converting a settings file from version since 7.30 inclusive to 7.70 or later, any IEC 61850 settings are converted and
Edition 2 is used.
When converting a settings file with IEC 61850 Edition 1 to version 7.80 or later with a non-HardFiber Process Bus Module
(order code 85, 86, or 87), conversion does not take place and an error message displays. The Process Bus Module does not
support Edition 1.
Conversions between PBM and non-PBM order codes are not permitted.
With version 8.00 and later, when a file is converted between order codes, the logical node prefix names and instance
numbers are defaulted and the respective dataset member references are removed.
To convert settings:
1. If not already in the Offline Window area, right-click the online device in the EnerVista software and select the Add
Device to Offline Window option. This copies the settings to the Offline Window area. Any message about file repair
usually means that settings were missing in the original file and have been added with default values to the new file.
2. Make a copy of the settings file in the Offline Window area by right-clicking the file and selecting Duplicate Device. A
copy of the file is made and the file name start with “Copy of”. Optionally rename the file by right-clicking it and
selecting the Rename Device option.
3. Convert the settings by right-clicking one of the files in the Offline Window and selecting the Convert Device Settings
option.
If the option does not display, click the Admin > User Management menu item and enable the Update Info check box
for the user. Save.
Or if the option does not display, click the Admin > User Management menu item and enable the Enable Security
check box. Save. Select the Admin > User Login menu item. Enter "Administrator" for the user and enter the password.
(Contact GE Grid Solutions if you do not know the default password.)
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-5


CONVERT DEVICE SETTINGS CHAPTER 10: MAINTENANCE

GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to
7.0 then 7.4 in order to follow embedded conversion rules and keep settings.
The settings convert and a report generates.
Figure 10-5: Upgrade settings

4. Review the conversion report. The values of all settings that have been defaulted during conversion are not listed in
the conversion report; to find the value of a setting before conversion, inspect the device backup file made before
conversion.
In the example shown here, settings have been reset to factory defaults and several settings are new in firmware
version 7.6 under Settings > System Setup > Switches and Breakers.
Figure 10-6: Conversion report

5. Change settings in the new file, for example by looking at the original file.
6. Write the converted file to the device, for example by dragging and dropping from the Offline Window to the Online
Window.
7. Check settings and operation.

10

10-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE COPY SETTINGS TO OTHER DEVICE

10.5 Copy settings to other device


Settings from one F60 device can be copied to another F60 device for rapid deployment. The order codes and IEC 61850
edition must match. See the Settings File section at the beginning of the Interfaces chapter for a list of settings not
deployed.
1. Right-click the device in the Online window and select the Add Device to Offline Window option. A window opens.
2. Check the file path and name the file, then click the Receive button. An example is to save the files in
D:\Users\Public\Public Documents\GE Power Management\URPC\Data\ and to name the source device
F60_Deployment. At the prompt, confirm the action. The settings are saved in .cid, .icd, and .urs files, and the entry
displays in the Offline window area.
3. Right-click the device in the Offline window area and select the Duplicate Device option. The device is copied with a
prefix of "Copy of." Multiple duplicates results in files being named "Copy of Copy of" for example, which can be
avoided by deleting the folder copies from the path shown on mouse-over.
4. Right-click the copied device and rename it.
5. Right-click the copied device and select the Edit Device Properties option. Make the changes for the new device.
6. Send the file to new device by dragging and dropping it into the Online Window area. Or right-click and select the
Write Settings to Device option.
7. Update the remaining settings, such as IP address.

10.6 Export settings


All or specific groups of settings are exportable.
1. Right-click a device in the Offline Window area and select the Export Settings option. A window opens. When the
Export All Settings option is enabled, the individual settings groups are inactive.
Figure 10-7: Export settings

2. For groups of settings, enable the Export Selected Settings option, then enable the check boxes of the options to
export. The example shows that FlexLogic equations are to be exported.
3. Click the OK button, and specify a file name in the window that opens. The format is XML. Click the button to start the
export, which takes a minute or two.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-7


COMPARE SETTINGS CHAPTER 10: MAINTENANCE

If prompted about a file being repaired, review the report. The path to the file displays, and otherwise it sits with the
URS, CID, and ICD files of the device with a file name of _Repair_Report.txt, such as B30 81x_Repair_Report.txt. The
example shows that some settings were added at default values. The explanation is that the EnerVista software was
updated, but the offline file predates the update.
Figure 10-8: Settings report

10.7 Compare settings


Settings are comparable against default values and between two UR devices.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and for example results in differences shown on a settings
comparison report.
When comparing two settings files with the graphical front panel, all graphical front panel features are compared except
for the single-line diagrams.

10.7.1 Compare against defaults


1. Right-click the device in the Offline Window area and select Compare Settings With Defaults. The file generates and
the number of differences displays.
2. To save the report, click File > Save As, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
In the figure, the first entry is from the device, while the second is the default value.
Figure 10-9: Device settings compared with default values

10.7.2 Compare two devices


Preferences are set under File > Preferences as follows:
• Comparison Report: Sequential File 1, File 2 Layout — When disabled (default), the report shows only what differs, as
shown in the previous figure. When enabled, the report indicates differences by device.

10

10-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE BACK UP AND RESTORE SETTINGS

Figure 10-10: Device settings compared between two devices, displayed sequentially

There are two ways to compare devices: devices in the Offline area or between Online and Offline devices.
To compare settings of two devices in the Offline Window area:
1. Right-click a first device in the Offline Window area and select Compare Two Devices.
2. In the window that opens, select a second device and click the OK button. The file generates and the number of
differences displays.
Alternatively, in the window that opens, enter a path/file name at the bottom of the window; users can select either a
URS or a CID file. When selecting URS files users should be aware that for IEC 61850 order codes the information in a
URS data file is incomplete and therefore a comparison with an IEC 61850-enabled device will show many differences.
3. To save the report, click File > Save As, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.

To compare settings between Online and Offline devices:


1. Right-click a device in the Online Window area and select Compare with Device.
2. In the window that opens, select an offline device and click the OK button. The file generates and the number of
differences displays.
Alternatively, in the window that opens, enter a path/file name at the bottom of the window; users can select either a
URS or a CID file. When selecting URS files users should be aware that for IEC 61850 order codes the information in a
URS data file is incomplete and therefore a comparison with an IEC 61850-enabled device will show many differences.
3. Click the OK button. The file generates, and the differences are highlighted in red, which is for the first device.

10.8 Back up and restore settings


Back up a copy of the in-service settings for each commissioned UR device, so as to revert to the commissioned settings
after inadvertent, unauthorized, or temporary setting changes are made, after the settings defaulted due to firmware
upgrade, or when the device has to be replaced. This section describes how to backup settings to a file and how to use
that file to restore the settings to the original relay or to a replacement relay.
For reference, settings can saved with Online > Print Device Information and Online > Export Device Information. They
cannot be restored using these options.

10.8.1 Back up settings


The following file types can be saved:
• URS — UR settings file — When the IEC 61850 option is not present
• IID — Instantiated IED capability description file — Actual settings on UR
• ICD — IED Capability Description file — Default settings on UR
• CID — Configured IED description file — Settings sent to the UR (may or may not contain the present settings)
UR device settings can be saved in a backup URS file using the EnerVista UR Setup software. The URS file is the standard
UR settings file. For an introduction to settings files in the URS format, see the beginning of the Interfaces chapter.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-9


BACK UP AND RESTORE SETTINGS CHAPTER 10: MAINTENANCE

When the IEC 61850 option is present, the settings can be saved alternatively in a backup IID file either using the EnerVista
UR Setup software in online mode or by using any of the supported file transfer protocols. The IID file is one of several IEC
61850 Substation Configuration Language (SCL) file types; see the IEC 61850 chapter in the UR Series Communications
Guide for an introduction to SCL.
"TBD" displays when a setting in a modeled element is configured with a non-modeled operand. For example, Phase IOC is
modeled in a firmware release, while the LED operands are not modeled. If the block setting of the Phase IOC is configured
with LED operands, its displays as TBD in IID and CID files, the web interface, or in an MMS client.
The options that display in the EnerVista software when right-clicking depend on device options.
Preferences are set in the File > Preferences > IEC 61850 menu. There are two options as follows:
• Preserve custom attributes when importing SCD/CID files — Applies to the Add Device to Offline Window option.
When enabled, the IID file also is to be copied to the computer. The IID file that is retrieved from the relay is therefore
assumed to be in synchronization with the resulting .urs file, and in fact in this situation the IID file on the computer is
a copy of the IID file that was read from the online device. When disabled, the IID file on the computer is to be left
unchanged. The location of the IID file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
• Do not update IID file when updating SCL files — When enabled (default), an IID file is not to be created on the
computer and if one is already present there, it is neither removed nor updated. Have this option enabled when you
want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE
Power Management\urpc\Offline, for example.
An Environment backup stores a list of sites and devices in the Online and Offline Window areas. Settings files are not
contained within the environment file. If a settings file is moved, renamed, or deleted after the backup, it is removed from
the Offline Window during the restore.

To save a settings file in the URS format in EnerVista Online Window:


1. In EnerVista, connect to the device in the Online Window area.
2. Right-click the device name in the Online Window area and select Add Device to Offline Window. A window opens.
3. Select or enter a file name and location, and click the Receive button. A .urs file is created in the Offline Window area.

To create a new settings file in the URS format in EnerVista Offline Window:
1. In EnerVista, right-click in the Offline Window area and select New Device. A window opens.
2. Change the file name at the end of the Path field, keeping the .urs extension.
3. From the Associate File with Device drop-down list, select the UR device. Other fields complete automatically.
Otherwise, when you do not select a device from the drop-down list, all fields need to be completed manually and
only devices that match the entered order code and version display in the list.
4. The Serial # Lock field is the serial number of the intended device. It ensures that the settings file is sent only to the
specific relay that matches the serial number.
5. Click the OK button to create the .urs file in the Offline Window area.

To save settings in the IID format in EnerVista Online Window:


1. In EnerVista, connect to the device in the Online Window area.
2. Right-click the device name in the Online Window area and select Read IID File. The option is not present when the
device does not have the IEC 61850 option. A window opens when successful.
3. Select or enter a file name and location, and click the Receive button. A .iid file is created.

To save settings in the IID format in EnerVista Offline Window:


1. In EnerVista, right-click the device in the Offline Window area.

10 2. Select the Create IID File option for firmware below 7.3. The option is not always available. Select the Save As option
for firmware 7.3 and later, and select the IID option from drop-down list.

10-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE BACK UP AND RESTORE SETTINGS

No file is generated. The IID file on the computer is copied to the location specified.
3. If the Do not update IID file when updating SCL files preference is enabled under File > Preferences > IEC 61850,
then a message displays to that effect. This means that there is no IID file available on the computer to be copied, so
a new one is generated.

To save settings in the IID format using TFTP:


1. On a computer on the same subnetwork as the UR device, open a command window.
2. Enter
TFTP <IP address> GET ur.iid <destination>
where
<IP address> is the IP address of the UR device
ur.iid is the internal name of the IID file in the UR device
<destination> is the path and file name of the IID file. If omitted, the file is saved as ur.iid in the command window
default directory.
An example is
TFTP 192.168.1.101 GET ur.iid Feeder1.iid

To save settings in the ICD format in EnerVista Online Window:


1. In EnerVista, right-click the device in the Online Window area.
2. Select the Read ICD File option. A window opens.
3. Enter a path/name for the file, and click the Save button.

To save settings in the ICD format in EnerVista Offline Window:


1. In EnerVista, right-click the device in the Offline Window area.
2. Select the Create ICD File option. Or select the Save As option, and select the ICD option from drop-down list.
You can be prompted to specify if the file is for firmware version 7.12 or later.
The file is saved to the location specified.

To save settings in the CID format in EnerVista Online Window:


1. In EnerVista, right-click the device in the Online Window area.
2. Select the Read ICD File option. A window opens.
3. Enter a path/name for the file, and click the Save button.

To save settings in the CID format in EnerVista Offline Window:


1. In EnerVista, right-click the device in the Offline Window area.
2. Select the Save As option, which displays for firmware 7.3 and later, and select the CID option from the drop-down list.
The file is copied from the computer to the location specified.

To save list of sites and devices with an Environment backup:


1. In EnerVista, click File > Environment > Backup. A window opens.
2. Name and save the .ENV file.

10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-11


BACK UP AND RESTORE SETTINGS CHAPTER 10: MAINTENANCE

10.8.2 Restore settings


UR device settings can be restored to the values they were at when a URS backup file was created using the EnerVista UR
Setup software. When the IEC 61850 option is present, the settings can alternatively be to the values they were at when an
IID type backup was created either using the EnerVista UR Setup software in online mode or by using any of the supported
file transfer protocols. Note that TFTP cannot be used here, as TFTP "put" mode is disabled for security reasons.
To restore completely, a few settings need to be entered manually either via EnerVista UR Setup or via the UR device front
panel. If the restore operation is to be via Ethernet, first the UR device must have its IP address settings entered via the
front panel. These are located at SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK 1(3) and SETTINGS 
PRODUCT SETUP  COMMUNICATIONS  IPv4 ROUTE TABLE 1(6)  DEFAULT IPv4 ROUTE  GATEWAY ADDRESS.
When importing a file, it cannot have a blank numeric value. All numeric values must be non-blank, otherwise the file is
rejected.
URS and IID procedures are outlined here.
To restore settings from a URS file:
1. In EnerVista, connect to the device in the Online Window area.
2. Right-click the .urs file in the Offline Window area and select Add Device from File to locate a file, and/or drag-and-
drop the file from the Offline Window area to the device in the Online Window area.
Figure 10-11: Restoring a URS settings file

3. Two prompts are possible, first that the URS file does not include the complete IEC 61850 configuration and that it
needs to be recreated if you continue. This means that the URS file is from UR version 7.30 or higher, has the IEC 61850
software option in the order code, but any IEC 61850 content will be compromised and will need to be configured.
Second, a message can display that the URS file is part of a device folder and to use the device’s CID file. This means
that the URS file is from UR version 7.3 or higher, has the IEC 61850 software option in the order code, and is part of the
device folder. The user is trying to add a URS file from inside a device’s folder. Instead, the user needs to use the CID file
from the device folder.

10 These messages display because the roles of the protection engineer and network engineer can be separate. The
former can require a URS file, while the latter can require stored Modbus settings and protection schemes.

10-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE BACK UP AND RESTORE SETTINGS

4. Manually copy the remaining settings, outlined as follows.

To restore settings from an IID file using EnerVista software:


1. In Windows, make a copy of the .iid backup file, and change the extension to .cid on the new copy.
2. In the Online Window area of the UR EnerVista Setup software, connect to the device to establish communication.
3. In the Offline Window area, right-click Devices and select Import Devices from SCD.
Figure 10-12: Importing an SCD or CID file

4. Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URS
file. The URS file is added to the Offline Window area.
5. Drag the imported file in the Offline Window to the device in the Online Window. Note that the RELAY SETTINGS value
also is written to a device, and the accepting relay is put into "Programmed" or "Not Programmed" mode as
configured in the offline file.
6. Manually copy the remaining settings, outlined as follows.

To restore settings from an IID using SFTP:


1. Verify that transfer by SFTP is enabled under SETTINGS  PRODUCT SETUP  COMMUNICATIONS 
PROTOCOL SFTP PROTOCOL.
2. Close EnerVista UR Setup software.
3. In Windows, make a copy of the .iid backup file, and change the extension to .cid on the new copy.
4. On a computer on the same subnetwork as the UR device, open an SFTP client application, such as WinSCP. Note that
TFTP cannot be used here.
5. Use the device's IP address as the host name.
6. If the device has the CyberSentry option, use the User Name of "Administrator" or "Engineer," and the password
programmed for the selected role. The default password is "ChangeMe1#" (without quotation marks). Log in to the
device.
7. If the device does not have the CyberSentry option, use the User Name of "Setting," and the password programmed for
the Setting role. The default password is "ChangeMe1#" (without quotation marks). Log in to the device.
8. Upload the backup file copy with the .cid extension. WinSCP uses drag-and-drop or copy-and-paste for this file
transfer.
9. Manually copy the remaining settings, outlined as follows.

To manually copy remaining settings:


1. Settings listed in section 4.1.2 Settings Files are not transferred to the UR device with settings files. Enter them
manually either via the front panel or via EnerVista UR Setup software. The values that these settings had at the time
the backup was created are contained within the backup file, accessed through EnerVista UR Setup software.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-13


UPGRADE SOFTWARE CHAPTER 10: MAINTENANCE

To restore the list of sites and devices from an Environment backup:


1. In EnerVista, click File > Environment > Restore. A window opens.
2. Select the .ENV file to restore.

10.9 Upgrade software


In general, the latest releases of the EnerVista software can be used with all firmware versions. For example, EnerVista
software released for UR 8.2 can be used to access multiple UR devices that have version 8.2x, 7.4x, and 6.0x firmware
installed.
Existing installations do not need to be uninstalled before upgrade.
You can also downgrade the software; use the same procedure.
Silent installation also is possible.
When upgrading on a computer with Windows Server 2012, its Release 2 needs the KB2919355 update first. Follow the
instructions described in the link, which works in Internet Explorer, not Chrome.
https://www.microsoft.com/en-US/download/details.aspx?id=42334

To upgrade the EnerVista software:


1. If a beta version of the EnerVista UR Setup software is installed, uninstall it, for example using the Windows Control
Panel.
2. For Windows 10, disconnect any USB cable to the F60, else the UR USB drivers do no install correctly.
3. Download the latest EnerVista software and/or firmware from
http://www.gegridsolutions.com/app/ViewFiles.aspx?prod=urfamily&type=7
4. Double-click the file and complete the wizard. The software installs.
5. Access the software.
The prompt "Do you want to create device folders for all your pre-existing off line devices" determines the folder
structure on the computer. Clicking Yes means that CID, ICD, and URS files are to be grouped together in a folder, and
the URS file is also one level above. Clicking No leaves folder structure unchanged.
6. Check the version number under Help > About. If the new version does not display, try uninstalling the software and
reinstalling the new version.
7. For Windows 10, to finish installing the UR USB driver, open Device Manager > Ports, then plug in the USB cable (to
connect the relay and computer). A new port starting with "GE Virtual Serial Port" is available. If available, click the OK
button to complete the installation.
If not available, uninstall the existing GE USB driver in the Device Manager > Ports. (Right-click and "Uninstall.")
When complete, unplug and re-plug the USB cable connecting the UR device. The "GE Virtual Serial Port" driver is now
available.
A message can display about a version not being supported. An example is when upgrading from version 7.12K to 7.4x.
The 7.12K entry is removed from the Offline Window area.
A message can display in the EnerVista software upon launch that "a device from the environment was not recognized."
This means that a device is online and its firmware version conflicts with the software version. In the example shown, a
C60 with firmware version 7.5x is online, but the software version is 7.3x. Updating removed incompatible files and
changed the device to version 7.3x, after which you need to make the order codes consistent as outlined next.

10

10-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE UPGRADE FIRMWARE

Figure 10-13: Mismatch in order code between software and device

To make the order codes consistent:


1. In EnerVista, click the Device Setup button. The window opens.
2. Expand the entry for the UR device.
3. Click the Read Order Code button. The order code and version of the device are populated to the software.
4. Click the OK button to save the change.

The silent installation is not truly silent because it invokes the user interface. The installation is silent at step 5. Double-
clicking on the .exe file for installation is faster.
To install the software silently:
1. Uninstall any existing EnerVista UR Setup software.
2. In a command line window, run the executable file, such as entering URPC810.exe -r
3. Follow the prompts to install the software using the wizard. The action creates a setup.iss file in the C:\WINNT,
C:\Windows\Setup, or other folder that records user inputs.
4. Copy the .exe and .iss files to the same folder.
5. In a command line window, enter URPC810.exe /s, where URPC810.exe is the executable file name. The software
installs and generates a setup.log file in the same folder. A result code of "0" at the end the log file means that the
installation succeeded.

10.10 Upgrade firmware


If upgrading both firmware and EnerVista software, upgrade the software first.
The firmware of the F60 device can be upgraded locally or remotely, using the EnerVista software.
Upgrades are possible for the same release (such as 8.01 to 8.02) and from one firmware version to another (such as 7.2 to
7.3). When upgrading to another firmware version, check the release notes on the GE Multilin website for compatibility.
If you are upgrading from version 7.0 or 7.1 to 7.2 or later, some CPU modules require a new boot version. Update this first.
Address any equipment mismatch error before upgrade. For example, if you have a basic front panel attached and the
order code in the device is for a graphical front panel, the upgrade only works with a graphical front panel.
You can also downgrade firmware; use the same procedure.
Upgrading the firmware takes the relay out of service. At the end of the upgrade, the relay restores the "In Service" state
that existed before the upgrade.
Any DSP manufactured between 1 January 2013 and 1 December 2015 with versions 7.27, 7.28, or 7.60 and up must be
sent back to the factory for updates before updating the firmware.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-15


UPGRADE FIRMWARE CHAPTER 10: MAINTENANCE

To upgrade the firmware using EnerVista software:


1. If required, download the bootcode file and/or firmware from
http://www.gegridsolutions.com/app/ViewFiles.aspx?prod=urfamily&type=7
The firmware is a .SFD file. The boot file is a .000 file. Bootcode files 7.03 and later are for CPUs T, U, V, or W, which have
9T, 9U, 9V, or 9W on the label.
2. Navigate to Settings > Product Setup > Security and ensure that the Remote Setting Authorized and Local Setting
Authorized settings are "ON." On the front panel of the device, the path is SETTINGS  PRODUCT SETUP  SECURITY 
DUAL PERMISSION SECURITY ACCESS.
3. Under Settings > Product Setup > Security > Access Supervision or Settings > Product Setup > Security >
Supervisory, the Lock Firmware setting needs to be disabled. When using CyberSentry, a Supervisor role is required,
or Administrator when there is no Supervisor.
4. In EnerVista, back up the device settings by right-clicking the device and selecting Add Device to Offline Window. In
the window that displays, select an existing file to overwrite, or enter a name for a new settings file and optionally a
location for the new file. Click the Receive button to start the backup.
If an "Incompatible device order codes or versions" message displays, it means that you are trying to overwrite a file
for another product. You access the Convert Device Settings option by right-clicking the file in the Offline Window
area at the lower left. GE recommends converting settings in firmware steps, for example when converting from 6.0 to
7.4x, convert first to 7.0 then 7.4 in order to follow embedded conversion rules and keep settings. Note that the values
of all settings that have been defaulted during conversion are not listed in the conversion report; to find the value of a
setting before conversion, inspect the device backups made before conversion.
5. In EnerVista, navigate to Maintenance > Update Firmware.
First select the boot file, if applicable, locating the .000 file, and proceed with the update. Note that settings are not
lost during this update. When done, the relay restarts automatically; continue with the next step.

When updating the boot file, ensure that power is not lost, else the relay must be returned to the
factory for repair.
To update the firmware, select the firmware update by locating the .SFD file, and proceed with the update.
When asked if upgrading over the Internet, the difference is the flash memory buffer size each time the software
sends data to the relay. Yes means that the flash memory buffer size is 256 bytes. No means that it is 1024 bytes,
which is faster.
If a warning message displays about the firmware not being supported by the EnerVista software, it means that the
firmware is a later version than the software. Upgrade the software to the same or later version as the firmware, then
try again.
If an "Unable to put relay in flash mode" message displays, set the Settings > Product Setup > Security > Dual
Permission Security Access > Remote Setting Authorized and Local Setting Authorized settings to "ON" and try
again.
When the update is finished, the relay restarts automatically. The upgrade process takes about 20 minutes when
using a graphical front panel because of writing to the front panel.
6. Restart the EnerVista software, and refresh the order code in EnerVista under the Device Setup button.
7. Verify the boot and firmware version while the device is starting up or in EnerVista under Actual Values > Product Info
> Firmware Revisions. The Revision is the firmware version, for example, revision 8.20 is UR firmware release 8.20.
The Boot Program Revision is the bootloader release.

10

10-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE REPLACE MODULE

Figure 10-14: Check upgrades

8. Set the device to "programmed" under Settings > Product Setup > Installation. A self-test error displays on the device
until this is done.
9. If you changed the Remote Setting Authorized, the Local Setting Authorized settings, or relay lock settings, return
them to their previous settings.
10. If you changed the Lock Firmware setting, enable it again.
11. To apply any previously saved settings, right-click the saved settings file in the Offline Window area and select Write
to Device. Optionally convert the saved settings to the new firmware version before writing to the device by right-
clicking and selecting Convert Device Settings.

The field-programmable gate array (FPGA) can be upgraded under Maintenance > Update FPGA when the device
is connected via serial cable and the firmware revision is 7.0 or higher.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of
firmware. The addresses are rearranged when new features are added or existing features are enhanced or
modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable,
self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware.
This message does not signal any problems when appearing after firmware upgrades.

10.11 Replace module


This section outlines how to replace a module.

Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.

To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
Two procedures follow: replace a module with the same module, and upgrade a module.
To replace a module with the same module:
1. Open the enhanced front panel to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the F60.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-17


REPLACE MODULE CHAPTER 10: MAINTENANCE

Figure 10-15: Modules inside relay with front cover open (enhanced front panel)

The basic front panel can be opened to the left once the black plastic sliding latch on the right side has been pushed
up, as shown below.
Figure 10-16: Removing module (basic front panel)

2. With power to the unit off, disconnect individually the connections at the front and back of the module before
removing the module from the chassis.
For any Process Bus Module in slot H for use with a HardFiber Brick, also remove the two screws at the back that
attach the module to the chassis.
3. To properly remove a module, pull simultaneously the ejector/inserter clips, located at the top and bottom of the
module. Record the original location of the module to ensure that the same or replacement module is inserted into the
correct slot. While modules with current input provide automatic shorting of external CT circuits, for CT/VT modules it
is recommended to short/isolate external circuits accordingly for maximum safety.
4. To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module
is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips
simultaneously. When the clips have locked into position, the module is fully inserted.

When adding a module (versus replacing a module), check that settings have not changed. Depending on the
module, settings can reset to default values.

10

10-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE BATTERY

The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and a
DSP ERROR or HARDWARE MISMATCH error displays.
An upgrade example is replacing the CPU module with a more recent one, such as swapping 9G/9H/9N with 9T/9U/9V/9W.
A power supply module upgrade does not affect an order code.
To upgrade a module:
1. Back up settings by sending the device to the Offline Window area. Convert the settings to the new order code by
right-clicking in the Offline Window area. Replace the module as outlined in the previous procedure. In the Online
Window area, reset all settings to factory defaults and read the new order code from the device using Commands >
Relay Maintenance > Update Order Code. Send the saved settings from the Offline Window area to the online device.
Refresh the order code in the Device Setup window and set the device to "Programmed" under Settings > Product
Setup > Installation.

10.12 Battery
A battery powers the real time clock on startup of the device.
When required, the battery can be replaced. The battery type is 3 V cylindrical.
The power supply module contains the battery. The power supply modules were upgraded in 2014 to SH/SL from RH/RL,
but the order code when purchasing a UR with redundant power supply remained as RH/RL so that customers can
continue to use the same order codes. The order code can read RH or RL, while the module inside the unit reads SH or SL.
The order code for replacement redundant power supply modules was changed to SH/SL.

10.12.1 Replace battery


When required, the battery can be replaced. The power supply module contains the battery.

To avoid injury, ensure that the unit has been powered off for a minimum of three minutes before
replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
1. Turn off the power to the unit.
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the plastic latch on the right side of the front panel
(basic front panel) or unscrewing the panel (enhanced front panel).
4. For the basic front panel, it needs to be removed in order to access the power supply module, which is typically in the
first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew the bracket on
the left side of the unit.
5. Remove the power supply module by simultaneously pulling the ejector clips at the top and bottom of the module and
sliding it out.
6. Unscrew all four screws (not three) that attach the metal cover to the module. The fourth screw is at the back end of
the module, on the opposite side from the clips, beside the white electronics part (see figure).
7. Slide the metal cover away from the clips about 0.5 cm (1/8 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides—pull the plastic away from the battery. Use a flat-head screwdriver if you cannot unclip the plastic with your
fingers.
9. Replace the battery with the identical make and model. For example, do not use a rechargeable battery. Observe the
+ and - polarity of the battery and replace it with the same polarity as marked on the battery holder.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-19


BATTERY CHAPTER 10: MAINTENANCE

Figure 10-17: Battery location on power supply module

10. Reinstall the battery holder and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.

10.12.2 Dispose of battery

10.12.2.1 EN Battery disposal


This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union. See the
product documentation for specific battery information. The battery is marked with this symbol, which may include
lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling return the battery to your supplier or to a
designated collection point. For more information see: www.recyclethis.info.

10.12.2.2 CS Nakládání s bateriemi


Tento produkt obsahuje baterie, které nemohou být zneškodněny v Evropské unii jako netříděný komunální odpadu. Viz
dokumentace k produktu pro informace pro konkrétní baterie. Baterie je označena tímto symbolem, který může zahrnovat
i uvedena písmena, kadmium (Cd), olovo (Pb), nebo rtuť (Hg). Pro správnou recyklaci baterií vraťte svémudodavateli nebo
na určeném sběrném místě. Pro více informací viz: www.recyclethis.info.

10.12.2.3 DA Batteri affald


Dette produkt indeholder et batteri som ikke kan bortskaffes sammen med almindeligt husholdningsaffald i Europa. Se
produktinformation for specifikke informationer om batteriet. Batteriet er forsynet med indgraveret symboler for hvad
batteriet indeholder: kadmium (Cd), bly (Pb) og kviksølv (Hg). Europæiske brugere af elektrisk udstyr skal aflevere kasserede
produkter til genbrug eller til leverandøren. Yderligere oplysninger findes på webstedet www.recyclethis.info.

10

10-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE BATTERY

10.12.2.4 DE Entsorgung von Batterien


Dieses Produkt beinhaltet eine Batterie, die nicht als unsortierter städtischer Abfall in der europäischen Union entsorgt
werden darf. Beachten Sie die spezifischen Batterie-informationen in der Produktdokumentation. Die Batterie ist mit
diesem Symbol gekennzeichnet, welches auch Hinweise auf möglicherweise enthaltene Stoffe wie Kadmium (Cd), Blei (Pb)
oder Quecksilber (Hektogramm) darstellt. Für die korrekte Wiederverwertung bringen Sie diese Batterie zu Ihrem lokalen
Lieferanten zurück oder entsorgen Sie das Produkt an den gekennzeichneten Sammelstellen. Weitere Informationen
hierzu finden Sie auf der folgenden Website: www.recyclethis.info.

10.12.2.5 EL Απόρριψη μπαταριών


Αυτό το προϊόν περιέχει μια μπαταρία που δεν πρέπει να απορρίπτεται σε δημόσια συστήματα απόρριψης στην
Ευρωπαϊκή Κοινότητα. ∆είτε την τεκμηρίωση του προϊόντος για συγκεκριμένες πληροφορίες που αφορούν τη μπαταρία.
Η μπαταρία είναι φέρει σήμανση με αυτό το σύμβολο, το οποίο μπορεί να περιλαμβάνει γράμματα για να δηλώσουν το
κάδμιο (Cd), τον μόλυβδο (Pb), ή τον υδράργυρο (Hg). Για την κατάλληλη ανακύκλωση επιστρέψτε την μπαταρία στον
προμηθευτή σας ή σε καθορισμένο σημείο συλλογής. Για περισσότερες πληροφορίες δείτε: www.recyclethis.info.

10.12.2.6 ES Eliminacion de baterias


Este producto contiene una batería que no se pueda eliminar como basura normal sin clasificar en la Unión Europea.
Examine la documentación del producto para la información específica de la batería. La batería se marca con este
símbolo, que puede incluir siglas para indicar el cadmio (Cd), el plomo (Pb), o el mercurio (Hg ). Para el reciclaje apropiado,
devuelva este producto a su distribuidor ó deshágase de él en los puntos de reciclaje designados. Para mas información :
wwwrecyclethis.info.

10.12.2.7 ET Patareide kõrvaldamine


Käesolev toode sisaldab patareisid, mida Euroopa Liidus ei tohi kõrvaldada sorteerimata olmejäätmetena. Andmeid
patareide kohta vaadake toote dokumentatsioonist. Patareid on märgistatud käesoleva sümboliga, millel võib olla
kaadmiumi (Cd), pliid (Pb) või elavhõbedat (Hg) tähistavad tähed. Nõuetekohaseks ringlusse võtmiseks tagastage patarei
tarnijale või kindlaksmääratud vastuvõtupunkti. Lisainformatsiooni saab Internetist aadressil: www.recyclethis.info.

10.12.2.8 FI Paristoje ja akkujen hävittäminen


Tuote sisältää pariston, jota ei saa hävittää Euroopan Unionin alueella talousjätteen mukana. Tarkista tuoteselosteesta
tuotteen tiedot. Paristo on merkitty tällä symbolilla ja saattaa sisältää cadmiumia (Cd), lyijyä (Pb) tai elohopeaa (Hg). Oikean
kierrätystavan varmistamiseksi palauta tuote paikalliselle jälleenmyyjälle tai palauta se paristojen keräyspisteeseen.
Lisätietoja sivuilla www.recyclethis.info.

10.12.2.9 FR Élimination des piles


Ce produit contient une batterie qui ne peuvent être éliminés comme déchets municipaux non triés dans l'Union
européenne. Voir la documentation du produit au niveau des renseignements sur la pile. La batterie est marqué de ce
symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la
batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info.

10.12.2.10 HU Akkumulátor hulladék kezelése


Ezen termék akkumulátort tartalmaz, amely az Európai Unión belül csak a kijelölt módon és helyen dobható ki. A terméken
illetve a mellékelt ismertetőn olvasható a kadmium (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék
akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai
hulladékudvarokban. További információ a www.recyclethis.info oldalon.

10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-21


BATTERY CHAPTER 10: MAINTENANCE

10.12.2.11 IT Smaltimento batterie


Questo prodotto contiene una batteria che non può essere smaltita nei comuni contenitori per lo smaltimento rifiuti, nell'
Unione Europea. Controllate la documentazione del prodotto per le informazioni specifiche sulla batteria. La batteria è
contrassegnata con questo simbolo e può includere alcuni caratteri ad indicare la presenza di cadmio (Cd), piombo (Pb)
oppure mercurio (Hg). Per il corretto smaltimento, potete restituirli al vostro fornitore locale, oppure rivolgervi e consegnarli
presso i centri di raccolta preposti. Per maggiori informazioni vedere: ww.recyclethis.info.

10.12.2.12 LT Baterijų šalinimas


Šios įrangos sudėtyje yra baterijų, kurias draudžiama šalinti Europos Sąjungos viešose nerūšiuotų atliekų šalinimo
sistemose. Informaciją apie baterijas galite rasti įrangos techninėje dokumentacijoje. Baterijos žymimos šiuo simboliu,
papildomai gali būti nurodoma kad baterijų sudėtyje yra kadmio (Cd), švino (Pb) ar gyvsidabrio (Hg). Eksploatavimui
nebetinkamas baterijas pristatykite į tam skirtas surinkimo vietas arba grąžinkite jas tiesioginiam tiekėjui, kad jos būtų
tinkamai utilizuotos. Daugiau informacijos rasite šioje interneto svetainėje: www.recyclethis.info.

10.12.2.13 LV Bateriju likvidēšana


Šis produkts satur bateriju vai akumulatoru, kuru nedrīkst izmest Eiropas Savienībā esošajās sadzīves atkritumu sistēmās.
Sk. produkta dokumentācijā, kur ir norādīta konkrēta informācija par bateriju vai akumulatoru. Baterijas vai akumulatora
marķējumā ir šis simbols, kas var ietvert burtus, kuri norāda kadmiju (Cd), svinu (Pb) vai dzīvsudrabu (Hg). Pēc
ekspluatācijas laika beigām baterijas vai akumulatori jānodod piegādātājam vai specializētā bateriju savākšanas vietā.
Sīkāku informāciju var iegūt vietnē: www.recyclethis.info.

10.12.2.14 NL Verwijderen van baterijen


Dit product bevat een batterij welke niet kan verwijdert worden via de gemeentelijke huisvuilscheiding in de Europese
Gemeenschap. Gelieve de product documentatie te controleren voor specifieke batterij informatie. De batterijen met deze
label kunnen volgende indictaies bevatten cadium (Cd), lood (Pb) of kwik (Hg). Voor correcte vorm van kringloop, geef je de
producten terug aan jou locale leverancier of geef het af aan een gespecialiseerde verzamelpunt. Meer informatie vindt u
op de volgende website: www.recyclethis.info.

10.12.2.15 NO Retur av batteri


Dette produkt inneholder et batteri som ikke kan kastes med usortert kommunalt søppel i den Europeiske Unionen. Se
produktdokumentasjonen for spesifikk batteriinformasjon. Batteriet er merket med dette symbolet som kan inkludere
symboler for å indikere at kadmium (Cd), bly (Pb), eller kvikksølv (Hg) forekommer. Returner batteriet til leverandøren din
eller til et dedikert oppsamlingspunkt for korrekt gjenvinning. For mer informasjon se: www.recyclethis.info.

10.12.2.16 PL Pozbywanie się zużytych baterii


Ten produkt zawiera baterie, które w Unii Europejskiej mogą być usuwane tylko jako posegregowane odpady komunalne.
Dokładne informacje dotyczące użytych baterii znajdują się w dokumentacji produktu. Baterie oznaczone tym symbolem
mogą zawierać dodatkowe oznaczenia literowe wskazujące na zawartość kadmu (Cd), ołowiu (Pb) lub rtęci (Hg). Dla
zapewnienia właściwej utylizacji, należy zwrócić baterie do dostawcy albo do wyznaczonego punktu zbiórki. Więcej
informacji można znaleźć na stronie internetowej www.recyclethis.info.

10.12.2.17 PT Eliminação de Baterias


Este produto contêm uma bateria que não pode ser considerado lixo municipal na União Europeia. Consulte a
documentação do produto para obter informação específica da bateria. A bateria é identificada por meio de este símbolo,
que pode incluir a rotulação para indicar o cádmio (Cd), chumbo (Pb), ou o mercúrio (hg). Para uma reciclagem apropriada
envie a bateria para o seu fornecedor ou para um ponto de recolha designado. Para mais informação veja:
www.recyclethis.info.

10

10-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE CLEAR FILES AND DATA AFTER UNINSTALL

10.12.2.18 RU Утилизация батарей


Согласно европейской директиве об отходах электрического и электронного оборудования, продукты, содержащие
батареи, нельзя утилизировать как обычные отходы на территории ЕС. Более подробную информацию вы найдете в
документации к продукту. На этом символе могут присутствовать буквы, которые означают, что батарея собержит
кадмий (Cd), свинец (Pb) или ртуть (Hg). Для надлежащей утилизации по окончании срока эксплуатации пользователь
должен возвратить батареи локальному поставщику или сдать в специальный пункт приема. Подробности можно
найти на веб-сайте: www.recyclethis.info.

10.12.2.19 SK Zaobchádzanie s batériami


Tento produkt obsahuje batériu, s ktorou sa v Európskej únii nesmie nakladať ako s netriedeným komunálnym odpadom.
Dokumentácia k produktu obsahuje špecifické informácie o batérii. Batéria je označená týmto symbolom, ktorý môže
obsahovať písmená na označenie kadmia (Cd), olova (Pb), alebo ortuti (Hg). Na správnu recykláciu vráťte batériu vášmu
lokálnemu dodávateľovi alebo na určené zberné miesto. Pre viac informácii pozrite: www.recyclethis.info.

10.12.2.20 SL Odlaganje baterij


Ta izdelek vsebuje baterijo, ki je v Evropski uniji ni dovoljeno odstranjevati kot nesortiran komunalni odpadek. Za posebne
informacije o bateriji glejte dokumentacijo izdelka. Baterija je označena s tem simbolom, ki lahko vključuje napise, ki
označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na
določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info.

10.12.2.21 SV Kassering av batteri


Denna produkt innehåller ett batteri som inte får kastas i allmänna sophanteringssytem inom den europeiska unionen. Se
produktdokumentationen för specifik batteriinformation. Batteriet är märkt med denna symbol, vilket kan innebära att det
innehåller kadmium (Cd), bly (Pb) eller kvicksilver (Hg). För korrekt återvinning skall batteriet returneras till leverantören eller
till en därför avsedd deponering. För mer information, se: www.recyclethis.info.

10.12.2.22 TR Pil Geri Dönüşümü


Bu ürün Avrupa Birliği genel atık sistemlerine atılmaması gereken pil içermektedir. Daha detaylı pil bilgisi için ürünün
kataloğunu inceleyiniz. Bu sembolle işaretlenmiş piller Kadmiyum(Cd), Kurşun(Pb) ya da Civa(Hg) içerebilir. Doğru geri
dönüşüm için ürünü yerel tedarikçinize geri veriniz ya da özel işaretlenmiş toplama noktlarına atınız. Daha fazla bilgi için:
www.recyclethis.info.

10.12.2.23 Global contacts


North America 905-294-6222
Latin America +55 11 3614 1700
Europe, Middle East, Africa +(34) 94 485 88 00
Asia +86-21-2401-3208
India +91 80 41314617

From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574.

10.13 Clear files and data after uninstall


The unit can be decommissioned by turning off power to the unit and disconnecting the wires to it.
To clear files and settings in the UR:
1. On the UR front panel, navigate to COMMANDS  RELAY MAINTENANCE  SERVICE COMMAND, enter the value 20511,
and press the ENTER key. The relay restarts and clears the UR.
2. Clear the flash memory using the SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS command.
10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-23


REPAIRS CHAPTER 10: MAINTENANCE

To clear files and settings on the computer:


1. Uninstall the EnerVista UR Setup software.
2. Find and delete the following UR files:
– .URS, .CID, and .ICD settings
– .EVT event records
– .CFG and .DAT COMTRADE

10.14 Repairs
The battery and modules inside the case can be replaced without return of the device to the factory. The firmware and
software can be upgraded without return of the device to the factory.
Fuses in the power supply module are not field-replaceable.
Files can be requested for use by technical support staff, for example the Service Report (click the icon in the software or
connect a USB drive to the graphical front panel) or under Maintenance > Retrieve File, as outlined elsewhere in this
document.
For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows:
• Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter.
• Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
• Verify that the RMA and Commercial Invoice received have the correct information.
• Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to cushion
the item(s). You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of
cushioning material.
• Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory.

GE GRID SOLUTIONS
650 MARKLAND STREET
MARKHAM, ONTARIO
CANADA L6C 0M1
ATTN: SERVICE DEPT.
RMA# : ______________

Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty.
• Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098.
Use the detailed return procedure outlined at
https://www.gegridsolutions.com/multilin/support/ret_proc.htm
The current warranty and return information are outlined at
https://www.gegridsolutions.com/multilin/warranty.htm

10.15 Storage
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range
outlined in the Specifications.

10

10-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


CHAPTER 10: MAINTENANCE DISPOSAL

To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.

10.16 Disposal
Other than the battery, there are no special requirements for disposal of the unit at the end its service life. For customers
located in the European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove
the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. See the UR Family Recycling and
Disposal Instructions (GET-20096).

10

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-25


DISPOSAL CHAPTER 10: MAINTENANCE

10

10-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Appendix A: FlexAnalog operands

Appendices
FlexAnalog operands

This appendix outlines FlexAnalog parameters.

A.1 FlexAnalog items


A FlexAnalog parameter is an analog parameter.
FlexAnalog items specific to your device are viewable in a web browser. Enter the IP address of the UR, access the Device
Information Menu option, then the FlexAnalog Parameter Listing option. Entries displayed online depend on order code.
Each FlexAnalog address is the Modbus memory map address prefixed with 0004. For example, with Modbus address of
1638, the FlexAnalog address is 00041638.
Table A-1: F60 FlexAnalog data items
Hex address FlexAnalog name Units Description
00041680 Sns Dir Power 1 Watts Sensitive directional power 1 actual value
00041682 Sns Dir Power 2 Watts Sensitive directional power 2 actual value
000416A0 RGF 1 Igd Mag Amps Restricted ground fault 1 differential ground current magnitude
000416A2 RGF 1 Igr Mag Amps Restricted ground fault 1 restricted ground current magnitude
000416A4 RGF 2 Igd Mag Amps Restricted ground fault 2 differential ground current magnitude
000416A6 RGF 2 Igr Mag Amps Restricted ground fault 2 restricted ground current magnitude
000416A8 RGF 3 Igd Mag Amps Restricted ground fault 3 differential ground current magnitude
000416AA RGF 3 Igr Mag Amps Restricted ground fault 3 restricted ground current magnitude
000416AC RGF 4 Igd Mag Amps Restricted ground fault 4 differential ground current magnitude
000416AE RGF 4 Igr Mag Amps Restricted ground fault 4 restricted ground current magnitude
000416C0 Field RTD 1 Value --- Field RTD 1 value
000416C1 Field RTD 2 Value --- Field RTD 2 value
000416C2 Field RTD 3 Value --- Field RTD 3 value
000416C3 Field RTD 4 Value --- Field RTD 4 value
000416C4 Field RTD 5 Value --- Field RTD 5 value
000416C5 Field RTD 6 Value --- Field RTD 6 value
000416C6 Field RTD 7 Value --- Field RTD 7 value
000416C7 Field RTD 8 Value --- Field RTD 8 value
000416C8 Field TDR 1 Value --- Field TDR 1 value

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-1


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


000416CA Field TDR 2 Value --- Field TDR 2 value
A 000416CC Field TDR 3 Value --- Field TDR 3 value
000416CE Field TDR 4 Value --- Field TDR 4 value
000416D0 Field TDR 5 Value --- Field TDR 5 value
000416D2 Field TDR 6 Value --- Field TDR 6 value
000416D4 Field TDR 7 Value --- Field TDR 7 value
000416D6 Field TDR 8 Value --- Field TDR 8 value
000416E0 Freq Rate 1 Value Hz/s Frequency rate of change 1 actual value
000416E4 Freq Rate 2 Value Hz/s Frequency rate of change 2 actual value
000416E8 Freq Rate 3 Value Hz/s Frequency rate of change 3 actual value
000416EC Freq Rate 4 Value Hz/s Frequency rate of change 4 actual value
00041A00 SRC 1 Vag RMS Volts Source 1 phase AG voltage RMS
00041A02 SRC 1 Vbg RMS Volts Source 1 phase BG voltage RMS
00041A04 SRC 1 Vcg RMS Volts Source 1 phase CG voltage RMS
00041A06 SRC 1 Vag Mag Volts Source 1 phase AG voltage magnitude
00041A08 SRC 1 Vag Angle Degrees Source 1 phase AG voltage angle
00041A09 SRC 1 Vbg Mag Volts Source 1 phase BG voltage magnitude
00041A0B SRC 1 Vbg Angle Degrees Source 1 phase BG voltage angle
00041A0C SRC 1 Vcg Mag Volts Source 1 phase CG voltage magnitude
00041A0E SRC 1 Vcg Angle Degrees Source 1 phase CG voltage angle
00041A0F SRC 1 Vab RMS Volts Source 1 phase AB voltage RMS
00041A11 SRC 1 Vbc RMS Volts Source 1 phase BC voltage RMS
00041A13 SRC 1 Vca RMS Volts Source 1 phase CA voltage RMS
00041A15 SRC 1 Vab Mag Volts Source 1 phase AB voltage magnitude
00041A17 SRC 1 Vab Angle Degrees Source 1 phase AB voltage angle
00041A18 SRC 1 Vbc Mag Volts Source 1 phase BC voltage magnitude
00041A1A SRC 1 Vbc Angle Degrees Source 1 phase BC voltage angle
00041A1B SRC 1 Vca Mag Volts Source 1 phase CA voltage magnitude
00041A1D SRC 1 Vca Angle Degrees Source 1 phase CA voltage angle
00041A1E SRC 1 Vx RMS Volts Source 1 auxiliary voltage RMS
00041A20 SRC 1 Vx Mag Volts Source 1 auxiliary voltage magnitude
00041A22 SRC 1 Vx Angle Degrees Source 1 auxiliary voltage angle
00041A23 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude
00041A25 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle
00041A26 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude
00041A28 SRC 1 V_1 Angle Degrees Source 1 positive-sequence voltage angle
00041A29 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude
00041A2B SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle
00041A40 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS
00041A42 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
00041A44 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
00041A46 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
00041A48 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
00041A49 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
00041A4B SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
00041A4C SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
00041A4E SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle

A-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00041A4F SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
00041A51 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
00041A53 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
00041A55 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
00041A57 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
00041A58 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
00041A5A SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
00041A5B SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
00041A5D SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
00041A5E SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
00041A60 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
00041A62 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
00041A63 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
00041A65 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
00041A66 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
00041A68 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
00041A69 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
00041A6B SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
00041A80 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
00041A82 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
00041A84 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS
00041A86 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude
00041A88 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle
00041A89 SRC 3 Vbg Mag Volts Source 3 phase BG voltage magnitude
00041A8B SRC 3 Vbg Angle Degrees Source 3 phase BG voltage angle
00041A8C SRC 3 Vcg Mag Volts Source 3 phase CG voltage magnitude
00041A8E SRC 3 Vcg Angle Degrees Source 3 phase CG voltage angle
00041A8F SRC 3 Vab RMS Volts Source 3 phase AB voltage RMS
00041A91 SRC 3 Vbc RMS Volts Source 3 phase BC voltage RMS
00041A93 SRC 3 Vca RMS Volts Source 3 phase CA voltage RMS
00041A95 SRC 3 Vab Mag Volts Source 3 phase AB voltage magnitude
00041A97 SRC 3 Vab Angle Degrees Source 3 phase AB voltage angle
00041A98 SRC 3 Vbc Mag Volts Source 3 phase BC voltage magnitude
00041A9A SRC 3 Vbc Angle Degrees Source 3 phase BC voltage angle
00041A9B SRC 3 Vca Mag Volts Source 3 phase CA voltage magnitude
00041A9D SRC 3 Vca Angle Degrees Source 3 phase CA voltage angle
00041A9E SRC 3 Vx RMS Volts Source 3 auxiliary voltage RMS
00041AA0 SRC 3 Vx Mag Volts Source 3 auxiliary voltage magnitude
00041AA2 SRC 3 Vx Angle Degrees Source 3 auxiliary voltage angle
00041AA3 SRC 3 V_0 Mag Volts Source 3 zero-sequence voltage magnitude
00041AA5 SRC 3 V_0 Angle Degrees Source 3 zero-sequence voltage angle
00041AA6 SRC 3 V_1 Mag Volts Source 3 positive-sequence voltage magnitude
00041AA8 SRC 3 V_1 Angle Degrees Source 3 positive-sequence voltage angle
00041AA9 SRC 3 V_2 Mag Volts Source 3 negative-sequence voltage magnitude
00041AAB SRC 3 V_2 Angle Degrees Source 3 negative-sequence voltage angle
00041AC0 SRC 4 Vag RMS Volts Source 4 phase AG voltage RMS
00041AC2 SRC 4 Vbg RMS Volts Source 4 phase BG voltage RMS

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-3


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00041AC4 SRC 4 Vcg RMS Volts Source 4 phase CG voltage RMS
A 00041AC6 SRC 4 Vag Mag Volts Source 4 phase AG voltage magnitude
00041AC8 SRC 4 Vag Angle Degrees Source 4 phase AG voltage angle
00041AC9 SRC 4 Vbg Mag Volts Source 4 phase BG voltage magnitude
00041ACB SRC 4 Vbg Angle Degrees Source 4 phase BG voltage angle
00041ACC SRC 4 Vcg Mag Volts Source 4 phase CG voltage magnitude
00041ACE SRC 4 Vcg Angle Degrees Source 4 phase CG voltage angle
00041ACF SRC 4 Vab RMS Volts Source 4 phase AB voltage RMS
00041AD1 SRC 4 Vbc RMS Volts Source 4 phase BC voltage RMS
00041AD3 SRC 4 Vca RMS Volts Source 4 phase CA voltage RMS
00041AD5 SRC 4 Vab Mag Volts Source 4 phase AB voltage magnitude
00041AD7 SRC 4 Vab Angle Degrees Source 4 phase AB voltage angle
00041AD8 SRC 4 Vbc Mag Volts Source 4 phase BC voltage magnitude
00041ADA SRC 4 Vbc Angle Degrees Source 4 phase BC voltage angle
00041ADB SRC 4 Vca Mag Volts Source 4 phase CA voltage magnitude
00041ADD SRC 4 Vca Angle Degrees Source 4 phase CA voltage angle
00041ADE SRC 4 Vx RMS Volts Source 4 auxiliary voltage RMS
00041AE0 SRC 4 Vx Mag Volts Source 4 auxiliary voltage magnitude
00041AE2 SRC 4 Vx Angle Degrees Source 4 auxiliary voltage angle
00041AE3 SRC 4 V_0 Mag Volts Source 4 zero-sequence voltage magnitude
00041AE5 SRC 4 V_0 Angle Degrees Source 4 zero-sequence voltage angle
00041AE6 SRC 4 V_1 Mag Volts Source 4 positive-sequence voltage magnitude
00041AE8 SRC 4 V_1 Angle Degrees Source 4 positive-sequence voltage angle
00041AE9 SRC 4 V_2 Mag Volts Source 4 negative-sequence voltage magnitude
00041AEB SRC 4 V_2 Angle Degrees Source 4 negative-sequence voltage angle
00041C00 SRC 1 P Watts Source 1 three-phase real power
00041C02 SRC 1 Pa Watts Source 1 phase A real power
00041C04 SRC 1 Pb Watts Source 1 phase B real power
00041C06 SRC 1 Pc Watts Source 1 phase C real power
00041C08 SRC 1 Q Vars Source 1 three-phase reactive power
00041C0A SRC 1 Qa Vars Source 1 phase A reactive power
00041C0C SRC 1 Qb Vars Source 1 phase B reactive power
00041C0E SRC 1 Qc Vars Source 1 phase C reactive power
00041C10 SRC 1 S VA Source 1 three-phase apparent power
00041C12 SRC 1 Sa VA Source 1 phase A apparent power
00041C14 SRC 1 Sb VA Source 1 phase B apparent power
00041C16 SRC 1 Sc VA Source 1 phase C apparent power
00041C18 SRC 1 PF --- Source 1 three-phase power factor
00041C19 SRC 1 Phase A PF --- Source 1 phase A power factor
00041C1A SRC 1 Phase B PF --- Source 1 phase B power factor
00041C1B SRC 1 Phase C PF --- Source 1 phase C power factor
00041C20 SRC 2 P Watts Source 2 three-phase real power
00041C22 SRC 2 Pa Watts Source 2 phase A real power
00041C24 SRC 2 Pb Watts Source 2 phase B real power
00041C26 SRC 2 Pc Watts Source 2 phase C real power
00041C28 SRC 2 Q Vars Source 2 three-phase reactive power
00041C2A SRC 2 Qa Vars Source 2 phase A reactive power

A-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00041C2C SRC 2 Qb Vars Source 2 phase B reactive power
00041C2E SRC 2 Qc Vars Source 2 phase C reactive power
00041C30 SRC 2 S VA Source 2 three-phase apparent power
00041C32 SRC 2 Sa VA Source 2 phase A apparent power
00041C34 SRC 2 Sb VA Source 2 phase B apparent power
00041C36 SRC 2 Sc VA Source 2 phase C apparent power
00041C38 SRC 2 PF --- Source 2 three-phase power factor
00041C39 SRC 2 Phase A PF --- Source 2 phase A power factor
00041C3A SRC 2 Phase B PF --- Source 2 phase B power factor
00041C3B SRC 2 Phase C PF --- Source 2 phase C power factor
00041C40 SRC 3 P Watts Source 3 three-phase real power
00041C42 SRC 3 Pa Watts Source 3 phase A real power
00041C44 SRC 3 Pb Watts Source 3 phase B real power
00041C46 SRC 3 Pc Watts Source 3 phase C real power
00041C48 SRC 3 Q Vars Source 3 three-phase reactive power
00041C4A SRC 3 Qa Vars Source 3 phase A reactive power
00041C4C SRC 3 Qb Vars Source 3 phase B reactive power
00041C4E SRC 3 Qc Vars Source 3 phase C reactive power
00041C50 SRC 3 S VA Source 3 three-phase apparent power
00041C52 SRC 3 Sa VA Source 3 phase A apparent power
00041C54 SRC 3 Sb VA Source 3 phase B apparent power
00041C56 SRC 3 Sc VA Source 3 phase C apparent power
00041C58 SRC 3 PF --- Source 3 three-phase power factor
00041C59 SRC 3 Phase A PF --- Source 3 phase A power factor
00041C5A SRC 3 Phase B PF --- Source 3 phase B power factor
00041C5B SRC 3 Phase C PF --- Source 3 phase C power factor
00041D00 SRC 1 Pos Watthour kWh Source 1 positive Watthour
00041D02 SRC 1 Neg Watthour Wh Source 1 negative Watthour
00041D04 SRC 1 Pos varh varh Source 1 positive varhour
00041D06 SRC 1 Neg varh varh Source 1 negative varhour
00041D10 SRC 2 Pos Watthour kWh Source 2 positive Watthour
00041D12 SRC 2 Neg Watthour Wh Source 2 negative Watthour
00041D14 SRC 2 Pos varh varh Source 2 positive varhour
00041D16 SRC 2 Neg varh varh Source 2 negative varhour
00041D20 SRC 3 Pos Watthour kWh Source 3 positive Watthour
00041D22 SRC 3 Neg Watthour kWh Source 3 negative Watthour
00041D24 SRC 3 Pos varh varh Source 3 positive varhour
00041D26 SRC 3 Neg varh varh Source 3 negative varhour
00041D80 SRC 1 Frequency Hz Source 1 frequency
00041D82 SRC 2 Frequency Hz Source 2 frequency
00041D84 SRC 3 Frequency Hz Source 3 frequency
00041E00 SRC 1 Demand Ia Amps Source 1 phase A current demand
00041E02 SRC 1 Demand Ib Amps Source 1 phase B current demand
00041E04 SRC 1 Demand Ic Amps Source 1 phase C current demand
00041E06 SRC 1 Demand Watt Watts Source 1 real power demand
00041E08 SRC 1 Demand var Vars Source 1 reactive power demand
00041E0A SRC 1 Demand VA VA Source 1 apparent power demand

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-5


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00041E10 SRC 2 Demand Ia Amps Source 2 phase A current demand
A 00041E12 SRC 2 Demand Ib Amps Source 2 phase B current demand
00041E14 SRC 2 Demand Ic Amps Source 2 phase C current demand
00041E16 SRC 2 Demand Watt Watts Source 2 real power demand
00041E18 SRC 2 Demand var Vars Source 2 reactive power demand
00041E1A SRC 2 Demand VA VA Source 2 apparent power demand
00041E20 SRC 3 Demand Ia Amps Source 3 phase A current demand
00041E22 SRC 3 Demand Ib Amps Source 3 phase B current demand
00041E24 SRC 3 Demand Ic Amps Source 3 phase C current demand
00041E26 SRC 3 Demand Watt Watts Source 3 real power demand
00041E28 SRC 3 Demand var Vars Source 3 reactive power demand
00041E2A SRC 3 Demand VA VA Source 3 apparent power demand
00041F80 SRC 1 Va THD % Source 1 phase A voltage total harmonic distortion (THD)
00041F81 SRC 1 Va Harm[2] % Source 1 phase A voltage second harmonic
00041F82 SRC 1 Va Harm[3] % Source 1 phase A voltage third harmonic
00041F83 SRC 1 Va Harm[4] % Source 1 phase A voltage fourth harmonic
00041F84 SRC 1 Va Harm[5] % Source 1 phase A voltage fifth harmonic
00041F85 SRC 1 Va Harm[6] % Source 1 phase A voltage sixth harmonic
00041F86 SRC 1 Va Harm[7] % Source 1 phase A voltage seventh harmonic
00041F87 SRC 1 Va Harm[8] % Source 1 phase A voltage eighth harmonic
00041F88 SRC 1 Va Harm[9] % Source 1 phase A voltage ninth harmonic
00041F89 SRC 1 Va Harm[10] % Source 1 phase A voltage tenth harmonic
00041F8A SRC 1 Va Harm[11] % Source 1 phase A voltage eleventh harmonic
00041F8B SRC 1 Va Harm[12] % Source 1 phase A voltage twelfth harmonic
00041F8C SRC 1 Va Harm[13] % Source 1 phase A voltage thirteenth harmonic
00041F8D SRC 1 Va Harm[14] % Source 1 phase A voltage fourteenth harmonic
00041F8E SRC 1 Va Harm[15] % Source 1 phase A voltage fifteenth harmonic
00041F8F SRC 1 Va Harm[16] % Source 1 phase A voltage sixteenth harmonic
00041F90 SRC 1 Va Harm[17] % Source 1 phase A voltage seventeenth harmonic
00041F91 SRC 1 Va Harm[18] % Source 1 phase A voltage eighteenth harmonic
00041F92 SRC 1 Va Harm[19] % Source 1 phase A voltage nineteenth harmonic
00041F93 SRC 1 Va Harm[20] % Source 1 phase A voltage twentieth harmonic
00041F94 SRC 1 Va Harm[21] % Source 1 phase A voltage twenty-first harmonic
00041F95 SRC 1 Va Harm[22] % Source 1 phase A voltage twenty-second harmonic
00041F96 SRC 1 Va Harm[23] % Source 1 phase A voltage twenty-third harmonic
00041F97 SRC 1 Va Harm[24] % Source 1 phase A voltage twenty-fourth harmonic
00041F98 SRC 1 Va Harm[25] % Source 1 phase A voltage twenty-fifth harmonic
00041F99 SRC 1 Vb THD % Source 1 phase B voltage total harmonic distortion (THD)
00041F9A SRC 1 Vb Harm[2] % Source 1 phase B voltage second harmonic
00041F9B SRC 1 Vb Harm[3] % Source 1 phase B voltage third harmonic
00041F9C SRC 1 Vb Harm[4] % Source 1 phase B voltage fourth harmonic
00041F9D SRC 1 Vb Harm[5] % Source 1 phase B voltage fifth harmonic
00041F9E SRC 1 Vb Harm[6] % Source 1 phase B voltage sixth harmonic
00041F9F SRC 1 Vb Harm[7] % Source 1 phase B voltage seventh harmonic
00041FA0 SRC 1 Vb Harm[8] % Source 1 phase B voltage eighth harmonic
00041FA1 SRC 1 Vb Harm[9] % Source 1 phase B voltage ninth harmonic
00041FA2 SRC 1 Vb Harm[10] % Source 1 phase B voltage tenth harmonic

A-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00041FA3 SRC 1 Vb Harm[11] % Source 1 phase B voltage eleventh harmonic
00041FA4 SRC 1 Vb Harm[12] % Source 1 phase B voltage twelfth harmonic
00041FA5 SRC 1 Vb Harm[13] % Source 1 phase B voltage thirteenth harmonic
00041FA6 SRC 1 Vb Harm[14] % Source 1 phase B voltage fourteenth harmonic
00041FA7 SRC 1 Vb Harm[15] % Source 1 phase B voltage fifteenth harmonic
00041FA8 SRC 1 Vb Harm[16] % Source 1 phase B voltage sixteenth harmonic
00041FA9 SRC 1 Vb Harm[17] % Source 1 phase B voltage seventeenth harmonic
00041FAA SRC 1 Vb Harm[18] % Source 1 phase B voltage eighteenth harmonic
00041FAB SRC 1 Vb Harm[19] % Source 1 phase B voltage nineteenth harmonic
00041FAC SRC 1 Vb Harm[20] % Source 1 phase B voltage twentieth harmonic
00041FAD SRC 1 Vb Harm[21] % Source 1 phase B voltage twenty-first harmonic
00041FAE SRC 1 Vb Harm[22] % Source 1 phase B voltage twenty-second harmonic
00041FAF SRC 1 Vb Harm[23] % Source 1 phase B voltage twenty-third harmonic
00041FB0 SRC 1 Vb Harm[24] % Source 1 phase B voltage twenty-fourth harmonic
00041FB1 SRC 1 Vb Harm[25] % Source 1 phase B voltage twenty-fifth harmonic
00041FB2 SRC 1 Vc THD % Source 1 phase C voltage total harmonic distortion (THD)
00041FB3 SRC 1 Vc Harm[2] % Source 1 phase C voltage second harmonic
00041FB4 SRC 1 Vc Harm[3] % Source 1 phase C voltage third harmonic
00041FB5 SRC 1 Vc Harm[4] % Source 1 phase C voltage fourth harmonic
00041FB6 SRC 1 Vc Harm[5] % Source 1 phase C voltage fifth harmonic
00041FB7 SRC 1 Vc Harm[6] % Source 1 phase C voltage sixth harmonic
00041FB8 SRC 1 Vc Harm[7] % Source 1 phase C voltage seventh harmonic
00041FB9 SRC 1 Vc Harm[8] % Source 1 phase C voltage eighth harmonic
00041FBA SRC 1 Vc Harm[9] % Source 1 phase C voltage ninth harmonic
00041FBB SRC 1 Vc Harm[10] % Source 1 phase C voltage tenth harmonic
00041FBC SRC 1 Vc Harm[11] % Source 1 phase C voltage eleventh harmonic
00041FBD SRC 1 Vc Harm[12] % Source 1 phase C voltage twelfth harmonic
00041FBE SRC 1 Vc Harm[13] % Source 1 phase C voltage thirteenth harmonic
00041FBF SRC 1 Vc Harm[14] % Source 1 phase C voltage fourteenth harmonic
00041FC0 SRC 1 Vc Harm[15] % Source 1 phase C voltage fifteenth harmonic
00041FC1 SRC 1 Vc Harm[16] % Source 1 phase C voltage sixteenth harmonic
00041FC2 SRC 1 Vc Harm[17] % Source 1 phase C voltage seventeenth harmonic
00041FC3 SRC 1 Vc Harm[18] % Source 1 phase C voltage eighteenth harmonic
00041FC4 SRC 1 Vc Harm[19] % Source 1 phase C voltage nineteenth harmonic
00041FC5 SRC 1 Vc Harm[20] % Source 1 phase C voltage twentieth harmonic
00041FC6 SRC 1 Vc Harm[21] % Source 1 phase C voltage twenty-first harmonic
00041FC7 SRC 1 Vc Harm[22] % Source 1 phase C voltage twenty-second harmonic
00041FC8 SRC 1 Vc Harm[23] % Source 1 phase C voltage twenty-third harmonic
00041FC9 SRC 1 Vc Harm[24] % Source 1 phase C voltage twenty-fourth harmonic
00041FCA SRC 1 Vc Harm[25] % Source 1 phase C voltage twenty-fifth harmonic
00041FCB SRC 2 Va THD % Source 2 phase A voltage total harmonic distortion (THD)
00041FCC SRC 2 Va Harm[2] % Source 2 phase A voltage second harmonic
00041FCD SRC 2 Va Harm[3] % Source 2 phase A voltage third harmonic
00041FCE SRC 2 Va Harm[4] % Source 2 phase A voltage fourth harmonic
00041FCF SRC 2 Va Harm[5] % Source 2 phase A voltage fifth harmonic
00041FD0 SRC 2 Va Harm[6] % Source 2 phase A voltage sixth harmonic
00041FD1 SRC 2 Va Harm[7] % Source 2 phase A voltage seventh harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-7


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00041FD2 SRC 2 Va Harm[8] % Source 2 phase A voltage eighth harmonic
A 00041FD3 SRC 2 Va Harm[9] % Source 2 phase A voltage ninth harmonic
00041FD4 SRC 2 Va Harm[10] % Source 2 phase A voltage tenth harmonic
00041FD5 SRC 2 Va Harm[11] % Source 2 phase A voltage eleventh harmonic
00041FD6 SRC 2 Va Harm[12] % Source 2 phase A voltage twelfth harmonic
00041FD7 SRC 2 Va Harm[13] % Source 2 phase A voltage thirteenth harmonic
00041FD8 SRC 2 Va Harm[14] % Source 2 phase A voltage fourteenth harmonic
00041FD9 SRC 2 Va Harm[15] % Source 2 phase A voltage fifteenth harmonic
00041FDA SRC 2 Va Harm[16] % Source 2 phase A voltage sixteenth harmonic
00041FDB SRC 2 Va Harm[17] % Source 2 phase A voltage seventeenth harmonic
00041FDC SRC 2 Va Harm[18] % Source 2 phase A voltage eighteenth harmonic
00041FDD SRC 2 Va Harm[19] % Source 2 phase A voltage nineteenth harmonic
00041FDE SRC 2 Va Harm[20] % Source 2 phase A voltage twentieth harmonic
00041FDF SRC 2 Va Harm[21] % Source 2 phase A voltage twenty-first harmonic
00041FE0 SRC 2 Va Harm[22] % Source 2 phase A voltage twenty-second harmonic
00041FE1 SRC 2 Va Harm[23] % Source 2 phase A voltage twenty-third harmonic
00041FE2 SRC 2 Va Harm[24] % Source 2 phase A voltage twenty-fourth harmonic
00041FE3 SRC 2 Va Harm[25] % Source 2 phase A voltage twenty-fifth harmonic
00041FE4 SRC 2 Vb THD % Source 2 phase B voltage total harmonic distortion (THD)
00041FE5 SRC 2 Vb Harm[2] % Source 2 phase B voltage second harmonic
00041FE6 SRC 2 Vb Harm[3] % Source 2 phase B voltage third harmonic
00041FE7 SRC 2 Vb Harm[4] % Source 2 phase B voltage fourth harmonic
00041FE8 SRC 2 Vb Harm[5] % Source 2 phase B voltage fifth harmonic
00041FE9 SRC 2 Vb Harm[6] % Source 2 phase B voltage sixth harmonic
00041FEA SRC 2 Vb Harm[7] % Source 2 phase B voltage seventh harmonic
00041FEB SRC 2 Vb Harm[8] % Source 2 phase B voltage eighth harmonic
00041FEC SRC 2 Vb Harm[9] % Source 2 phase B voltage ninth harmonic
00041FED SRC 2 Vb Harm[10] % Source 2 phase B voltage tenth harmonic
00041FEE SRC 2 Vb Harm[11] % Source 2 phase B voltage eleventh harmonic
00041FEF SRC 2 Vb Harm[12] % Source 2 phase B voltage twelfth harmonic
00041FF0 SRC 2 Vb Harm[13] % Source 2 phase B voltage thirteenth harmonic
00041FF1 SRC 2 Vb Harm[14] % Source 2 phase B voltage fourteenth harmonic
00041FF2 SRC 2 Vb Harm[15] % Source 2 phase B voltage fifteenth harmonic
00041FF3 SRC 2 Vb Harm[16] % Source 2 phase B voltage sixteenth harmonic
00041FF4 SRC 2 Vb Harm[17] % Source 2 phase B voltage seventeenth harmonic
00041FF5 SRC 2 Vb Harm[18] % Source 2 phase B voltage eighteenth harmonic
00041FF6 SRC 2 Vb Harm[19] % Source 2 phase B voltage nineteenth harmonic
00041FF7 SRC 2 Vb Harm[20] % Source 2 phase B voltage twentieth harmonic
00041FF8 SRC 2 Vb Harm[21] % Source 2 phase B voltage twenty-first harmonic
00041FF9 SRC 2 Vb Harm[22] % Source 2 phase B voltage twenty-second harmonic
00041FFA SRC 2 Vb Harm[23] % Source 2 phase B voltage twenty-third harmonic
00041FFB SRC 2 Vb Harm[24] % Source 2 phase B voltage twenty-fourth harmonic
00041FFC SRC 2 Vb Harm[25] % Source 2 phase B voltage twenty-fifth harmonic
00041FFD SRC 2 Vc THD % Source 2 phase C voltage total harmonic distortion (THD)
00041FFE SRC 2 Vc Harm[2] % Source 2 phase C voltage second harmonic
00041FFF SRC 2 Vc Harm[3] % Source 2 phase C voltage third harmonic
00042000 SRC 2 Vc Harm[4] % Source 2 phase C voltage fourth harmonic

A-8 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042001 SRC 2 Vc Harm[5] % Source 2 phase C voltage fifth harmonic
00042002 SRC 2 Vc Harm[6] % Source 2 phase C voltage sixth harmonic
00042003 SRC 2 Vc Harm[7] % Source 2 phase C voltage seventh harmonic
00042004 SRC 2 Vc Harm[8] % Source 2 phase C voltage eighth harmonic
00042005 SRC 2 Vc Harm[9] % Source 2 phase C voltage ninth harmonic
00042006 SRC 2 Vc Harm[10] % Source 2 phase C voltage tenth harmonic
00042007 SRC 2 Vc Harm[11] % Source 2 phase C voltage eleventh harmonic
00042008 SRC 2 Vc Harm[12] % Source 2 phase C voltage twelfth harmonic
00042009 SRC 2 Vc Harm[13] % Source 2 phase C voltage thirteenth harmonic
0004200A SRC 2 Vc Harm[14] % Source 2 phase C voltage fourteenth harmonic
0004200B SRC 2 Vc Harm[15] % Source 2 phase C voltage fifteenth harmonic
0004200C SRC 2 Vc Harm[16] % Source 2 phase C voltage sixteenth harmonic
0004200D SRC 2 Vc Harm[17] % Source 2 phase C voltage seventeenth harmonic
0004200E SRC 2 Vc Harm[18] % Source 2 phase C voltage eighteenth harmonic
0004200F SRC 2 Vc Harm[19] % Source 2 phase C voltage nineteenth harmonic
00042010 SRC 2 Vc Harm[20] % Source 2 phase C voltage twentieth harmonic
00042011 SRC 2 Vc Harm[21] % Source 2 phase C voltage twenty-first harmonic
00042012 SRC 2 Vc Harm[22] % Source 2 phase C voltage twenty-second harmonic
00042013 SRC 2 Vc Harm[23] % Source 2 phase C voltage twenty-third harmonic
00042014 SRC 2 Vc Harm[24] % Source 2 phase C voltage twenty-fourth harmonic
00042015 SRC 2 Vc Harm[25] % Source 2 phase C voltage twenty-fifth harmonic
00042016 SRC 3 Va THD % Source 3 phase A voltage total harmonic distortion (THD)
00042017 SRC 3 Va Harm[2] % Source 3 phase A voltage second harmonic
00042018 SRC 3 Va Harm[3] % Source 3 phase A voltage third harmonic
00042019 SRC 3 Va Harm[4] % Source 3 phase A voltage fourth harmonic
0004201A SRC 3 Va Harm[5] % Source 3 phase A voltage fifth harmonic
0004201B SRC 3 Va Harm[6] % Source 3 phase A voltage sixth harmonic
0004201C SRC 3 Va Harm[7] % Source 3 phase A voltage seventh harmonic
0004201D SRC 3 Va Harm[8] % Source 3 phase A voltage eighth harmonic
0004201E SRC 3 Va Harm[9] % Source 3 phase A voltage ninth harmonic
0004201F SRC 3 Va Harm[10] % Source 3 phase A voltage tenth harmonic
00042020 SRC 3 Va Harm[11] % Source 3 phase A voltage eleventh harmonic
00042021 SRC 3 Va Harm[12] % Source 3 phase A voltage twelfth harmonic
00042022 SRC 3 Va Harm[13] % Source 3 phase A voltage thirteenth harmonic
00042023 SRC 3 Va Harm[14] % Source 3 phase A voltage fourteenth harmonic
00042024 SRC 3 Va Harm[15] % Source 3 phase A voltage fifteenth harmonic
00042025 SRC 3 Va Harm[16] % Source 3 phase A voltage sixteenth harmonic
00042026 SRC 3 Va Harm[17] % Source 3 phase A voltage seventeenth harmonic
00042027 SRC 3 Va Harm[18] % Source 3 phase A voltage eighteenth harmonic
00042028 SRC 3 Va Harm[19] % Source 3 phase A voltage nineteenth harmonic
00042029 SRC 3 Va Harm[20] % Source 3 phase A voltage twentieth harmonic
0004202A SRC 3 Va Harm[21] % Source 3 phase A voltage twenty-first harmonic
0004202B SRC 3 Va Harm[22] % Source 3 phase A voltage twenty-second harmonic
0004202C SRC 3 Va Harm[23] % Source 3 phase A voltage twenty-third harmonic
0004202D SRC 3 Va Harm[24] % Source 3 phase A voltage twenty-fourth harmonic
0004202E SRC 3 Va Harm[25] % Source 3 phase A voltage twenty-fifth harmonic
0004202F SRC 3 Vb THD % Source 3 phase B voltage total harmonic distortion (THD)

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-9


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00042030 SRC 3 Vb Harm[2] % Source 3 phase B voltage second harmonic
A 00042031 SRC 3 Vb Harm[3] % Source 3 phase B voltage third harmonic
00042032 SRC 3 Vb Harm[4] % Source 3 phase B voltage fourth harmonic
00042033 SRC 3 Vb Harm[5] % Source 3 phase B voltage fifth harmonic
00042034 SRC 3 Vb Harm[6] % Source 3 phase B voltage sixth harmonic
00042035 SRC 3 Vb Harm[7] % Source 3 phase B voltage seventh harmonic
00042036 SRC 3 Vb Harm[8] % Source 3 phase B voltage eighth harmonic
00042037 SRC 3 Vb Harm[9] % Source 3 phase B voltage ninth harmonic
00042038 SRC 3 Vb Harm[10] % Source 3 phase B voltage tenth harmonic
00042039 SRC 3 Vb Harm[11] % Source 3 phase B voltage eleventh harmonic
0004203A SRC 3 Vb Harm[12] % Source 3 phase B voltage twelfth harmonic
0004203B SRC 3 Vb Harm[13] % Source 3 phase B voltage thirteenth harmonic
0004203C SRC 3 Vb Harm[14] % Source 3 phase B voltage fourteenth harmonic
0004203D SRC 3 Vb Harm[15] % Source 3 phase B voltage fifteenth harmonic
0004203E SRC 3 Vb Harm[16] % Source 3 phase B voltage sixteenth harmonic
0004203F SRC 3 Vb Harm[17] % Source 3 phase B voltage seventeenth harmonic
00042040 SRC 3 Vb Harm[18] % Source 3 phase B voltage eighteenth harmonic
00042041 SRC 3 Vb Harm[19] % Source 3 phase B voltage nineteenth harmonic
00042042 SRC 3 Vb Harm[20] % Source 3 phase B voltage twentieth harmonic
00042043 SRC 3 Vb Harm[21] % Source 3 phase B voltage twenty-first harmonic
00042044 SRC 3 Vb Harm[22] % Source 3 phase B voltage twenty-second harmonic
00042045 SRC 3 Vb Harm[23] % Source 3 phase B voltage twenty-third harmonic
00042046 SRC 3 Vb Harm[24] % Source 3 phase B voltage twenty-fourth harmonic
00042047 SRC 3 Vb Harm[25] % Source 3 phase B voltage twenty-fifth harmonic
00042048 SRC 3 Vc THD % Source 3 phase C voltage total harmonic distortion (THD)
00042049 SRC 3 Vc Harm[2] % Source 3 phase C voltage second harmonic
0004204A SRC 3 Vc Harm[3] % Source 3 phase C voltage third harmonic
0004204B SRC 3 Vc Harm[4] % Source 3 phase C voltage fourth harmonic
0004204C SRC 3 Vc Harm[5] % Source 3 phase C voltage fifth harmonic
0004204D SRC 3 Vc Harm[6] % Source 3 phase C voltage sixth harmonic
0004204E SRC 3 Vc Harm[7] % Source 3 phase C voltage seventh harmonic
0004204F SRC 3 Vc Harm[8] % Source 3 phase C voltage eighth harmonic
00042050 SRC 3 Vc Harm[9] % Source 3 phase C voltage ninth harmonic
00042051 SRC 3 Vc Harm[10] % Source 3 phase C voltage tenth harmonic
00042052 SRC 3 Vc Harm[11] % Source 3 phase C voltage eleventh harmonic
00042053 SRC 3 Vc Harm[12] % Source 3 phase C voltage twelfth harmonic
00042054 SRC 3 Vc Harm[13] % Source 3 phase C voltage thirteenth harmonic
00042055 SRC 3 Vc Harm[14] % Source 3 phase C voltage fourteenth harmonic
00042056 SRC 3 Vc Harm[15] % Source 3 phase C voltage fifteenth harmonic
00042057 SRC 3 Vc Harm[16] % Source 3 phase C voltage sixteenth harmonic
00042058 SRC 3 Vc Harm[17] % Source 3 phase C voltage seventeenth harmonic
00042059 SRC 3 Vc Harm[18] % Source 3 phase C voltage eighteenth harmonic
0004205A SRC 3 Vc Harm[19] % Source 3 phase C voltage nineteenth harmonic
0004205B SRC 3 Vc Harm[20] % Source 3 phase C voltage twentieth harmonic
0004205C SRC 3 Vc Harm[21] % Source 3 phase C voltage twenty-first harmonic
0004205D SRC 3 Vc Harm[22] % Source 3 phase C voltage twenty-second harmonic
0004205E SRC 3 Vc Harm[23] % Source 3 phase C voltage twenty-third harmonic

A-10 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
0004205F SRC 3 Vc Harm[24] % Source 3 phase C voltage twenty-fourth harmonic
00042060 SRC 3 Vc Harm[25] % Source 3 phase C voltage twenty-fifth harmonic
00042061 SRC 4 Va THD % Source 4 phase A voltage total harmonic distortion (THD)
00042062 SRC 4 Va Harm[2] % Source 4 phase A voltage second harmonic
00042063 SRC 4 Va Harm[3] % Source 4 phase A voltage third harmonic
00042064 SRC 4 Va Harm[4] % Source 4 phase A voltage fourth harmonic
00042065 SRC 4 Va Harm[5] % Source 4 phase A voltage fifth harmonic
00042066 SRC 4 Va Harm[6] % Source 4 phase A voltage sixth harmonic
00042067 SRC 4 Va Harm[7] % Source 4 phase A voltage seventh harmonic
00042068 SRC 4 Va Harm[8] % Source 4 phase A voltage eighth harmonic
00042069 SRC 4 Va Harm[9] % Source 4 phase A voltage ninth harmonic
0004206A SRC 4 Va Harm[10] % Source 4 phase A voltage tenth harmonic
0004206B SRC 4 Va Harm[11] % Source 4 phase A voltage eleventh harmonic
0004206C SRC 4 Va Harm[12] % Source 4 phase A voltage twelfth harmonic
0004206D SRC 4 Va Harm[13] % Source 4 phase A voltage thirteenth harmonic
0004206E SRC 4 Va Harm[14] % Source 4 phase A voltage fourteenth harmonic
0004206F SRC 4 Va Harm[15] % Source 4 phase A voltage fifteenth harmonic
00042070 SRC 4 Va Harm[16] % Source 4 phase A voltage sixteenth harmonic
00042071 SRC 4 Va Harm[17] % Source 4 phase A voltage seventeenth harmonic
00042072 SRC 4 Va Harm[18] % Source 4 phase A voltage eighteenth harmonic
00042073 SRC 4 Va Harm[19] % Source 4 phase A voltage nineteenth harmonic
00042074 SRC 4 Va Harm[20] % Source 4 phase A voltage twentieth harmonic
00042075 SRC 4 Va Harm[21] % Source 4 phase A voltage twenty-first harmonic
00042076 SRC 4 Va Harm[22] % Source 4 phase A voltage twenty-second harmonic
00042077 SRC 4 Va Harm[23] % Source 4 phase A voltage twenty-third harmonic
00042078 SRC 4 Va Harm[24] % Source 4 phase A voltage twenty-fourth harmonic
00042079 SRC 4 Va Harm[25] % Source 4 phase A voltage twenty-fifth harmonic
0004207A SRC 4 Vb THD % Source 4 phase B voltage total harmonic distortion (THD)
0004207B SRC 4 Vb Harm[2] % Source 4 phase B voltage second harmonic
0004207C SRC 4 Vb Harm[3] % Source 4 phase B voltage third harmonic
0004207D SRC 4 Vb Harm[4] % Source 4 phase B voltage fourth harmonic
0004207E SRC 4 Vb Harm[5] % Source 4 phase B voltage fifth harmonic
0004207F SRC 4 Vb Harm[6] % Source 4 phase B voltage sixth harmonic
00042080 SRC 4 Vb Harm[7] % Source 4 phase B voltage seventh harmonic
00042081 SRC 4 Vb Harm[8] % Source 4 phase B voltage eighth harmonic
00042082 SRC 4 Vb Harm[9] % Source 4 phase B voltage ninth harmonic
00042083 SRC 4 Vb Harm[10] % Source 4 phase B voltage tenth harmonic
00042084 SRC 4 Vb Harm[11] % Source 4 phase B voltage eleventh harmonic
00042085 SRC 4 Vb Harm[12] % Source 4 phase B voltage twelfth harmonic
00042086 SRC 4 Vb Harm[13] % Source 4 phase B voltage thirteenth harmonic
00042087 SRC 4 Vb Harm[14] % Source 4 phase B voltage fourteenth harmonic
00042088 SRC 4 Vb Harm[15] % Source 4 phase B voltage fifteenth harmonic
00042089 SRC 4 Vb Harm[16] % Source 4 phase B voltage sixteenth harmonic
0004208A SRC 4 Vb Harm[17] % Source 4 phase B voltage seventeenth harmonic
0004208B SRC 4 Vb Harm[18] % Source 4 phase B voltage eighteenth harmonic
0004208C SRC 4 Vb Harm[19] % Source 4 phase B voltage nineteenth harmonic
0004208D SRC 4 Vb Harm[20] % Source 4 phase B voltage twentieth harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-11


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


0004208E SRC 4 Vb Harm[21] % Source 4 phase B voltage twenty-first harmonic
A 0004208F SRC 4 Vb Harm[22] % Source 4 phase B voltage twenty-second harmonic
00042090 SRC 4 Vb Harm[23] % Source 4 phase B voltage twenty-third harmonic
00042091 SRC 4 Vb Harm[24] % Source 4 phase B voltage twenty-fourth harmonic
00042092 SRC 4 Vb Harm[25] % Source 4 phase B voltage twenty-fifth harmonic
00042093 SRC 4 Vc THD % Source 4 phase C voltage total harmonic distortion (THD)
00042094 SRC 4 Vc Harm[2] % Source 4 phase C voltage second harmonic
00042095 SRC 4 Vc Harm[3] % Source 4 phase C voltage third harmonic
00042096 SRC 4 Vc Harm[4] % Source 4 phase C voltage fourth harmonic
00042097 SRC 4 Vc Harm[5] % Source 4 phase C voltage fifth harmonic
00042098 SRC 4 Vc Harm[6] % Source 4 phase C voltage sixth harmonic
00042099 SRC 4 Vc Harm[7] % Source 4 phase C voltage seventh harmonic
0004209A SRC 4 Vc Harm[8] % Source 4 phase C voltage eighth harmonic
0004209B SRC 4 Vc Harm[9] % Source 4 phase C voltage ninth harmonic
0004209C SRC 4 Vc Harm[10] % Source 4 phase C voltage tenth harmonic
0004209D SRC 4 Vc Harm[11] % Source 4 phase C voltage eleventh harmonic
0004209E SRC 4 Vc Harm[12] % Source 4 phase C voltage twelfth harmonic
0004209F SRC 4 Vc Harm[13] % Source 4 phase C voltage thirteenth harmonic
000420A0 SRC 4 Vc Harm[14] % Source 4 phase C voltage fourteenth harmonic
000420A1 SRC 4 Vc Harm[15] % Source 4 phase C voltage fifteenth harmonic
000420A2 SRC 4 Vc Harm[16] % Source 4 phase C voltage sixteenth harmonic
000420A3 SRC 4 Vc Harm[17] % Source 4 phase C voltage seventeenth harmonic
000420A4 SRC 4 Vc Harm[18] % Source 4 phase C voltage eighteenth harmonic
000420A5 SRC 4 Vc Harm[19] % Source 4 phase C voltage nineteenth harmonic
000420A6 SRC 4 Vc Harm[20] % Source 4 phase C voltage twentieth harmonic
000420A7 SRC 4 Vc Harm[21] % Source 4 phase C voltage twenty-first harmonic
000420A8 SRC 4 Vc Harm[22] % Source 4 phase C voltage twenty-second harmonic
000420A9 SRC 4 Vc Harm[23] % Source 4 phase C voltage twenty-third harmonic
000420AA SRC 4 Vc Harm[24] % Source 4 phase C voltage twenty-fourth harmonic
000420AB SRC 4 Vc Harm[25] % Source 4 phase C voltage twenty-fifth harmonic
00042250 HIZ Status --- High impedance fault detection status
00042251 HIZ Phase A Arc Conf --- High impedance fault detection phase A arc confidence
00042252 HIZ Phase B Arc Conf --- High impedance fault detection phase B arc confidence
00042253 HIZ Phase C Arc Conf --- High impedance fault detection phase C arc confidence
00042254 HIZ Neutral Arc Conf --- High impedance fault detection neutral arc confidence
00042340 Prefault Ia Mag [1] Amps Fault 1 pre-fault phase A current magnitude
00042342 Prefault Ia Ang [1] Degrees Fault 1 pre-fault phase A current angle
00042343 Prefault Ib Mag [1] Amps Fault 1 pre-fault phase B current magnitude
00042345 Prefault Ib Ang [1] Degrees Fault 1 pre-fault phase B current angle
00042346 Prefault Ic Mag [1] Amps Fault 1 pre-fault phase C current magnitude
00042348 Prefault Ic Ang [1] Degrees Fault 1 pre-fault phase C current angle
00042349 Prefault Va Mag [1] Volts Fault 1 pre-fault phase A voltage magnitude
0004234B Prefault Va Ang [1] Degrees Fault 1 pre-fault phase A voltage angle
0004234C Prefault Vb Mag [1] Volts Fault 1 pre-fault phase B voltage magnitude
0004234E Prefault Vb Ang [1] Degrees Fault 1 pre-fault phase B voltage angle
0004234F Prefault Vc Mag [1] Volts Fault 1 pre-fault phase C voltage magnitude
00042351 Prefault Vc Ang [1] Degrees Fault 1 pre-fault phase C voltage angle

A-12 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042352 Fault Ia Mag [1] Amps Fault 1 post-fault phase A current magnitude
00042354 Fault Ia Ang [1] Degrees Fault 1 post-fault phase A current angle
00042355 Fault Ib Mag [1] Amps Fault 1 post-fault phase B current magnitude
00042357 Fault Ib Ang [1] Degrees Fault 1 post-fault phase B current angle
00042358 Fault Ic Mag [1 Amps Fault 1 post-fault phase C current magnitude
0004235A Fault Ic Ang [1] Degrees Fault 1 post-fault phase C current angle
0004235B Fault Va Mag [1] Volts Fault 1 post-fault phase A voltage magnitude
0004235D Fault Va Ang [1] Degrees Fault 1 post-fault phase A voltage angle
0004235E Fault Vb Mag [1] Volts Fault 1 post-fault phase B voltage magnitude
00042360 Fault Vb Ang [1] Degrees Fault 1 post-fault phase B voltage angle
00042361 Fault Vc Mag [1] Volts Fault 1 post-fault phase C voltage magnitude
00042363 Fault Vc Ang [1] Degrees Fault 1 post-fault phase C voltage angle
00042364 Fault Type [1] --- Fault 1 type
00042365 Fault Location [1] --- Fault 1 location
00042366 Prefault Ia Mag [2] Amps Fault 2 pre-fault phase A current magnitude
00042368 Prefault Ia Ang [2] Degrees Fault 2 pre-fault phase A current angle
00042369 Prefault Ib Mag [2] Amps Fault 2 pre-fault phase B current magnitude
0004236B Prefault Ib Ang [2] Degrees Fault 2 pre-fault phase B current angle
0004236C Prefault Ic Mag [2] Amps Fault 2 pre-fault phase C current magnitude
0004236E Prefault Ic Ang [2] Degrees Fault 2 pre-fault phase C current angle
0004236F Prefault Va Mag [2] Volts Fault 2 pre-fault phase A voltage magnitude
00042371 Prefault Va Ang [2] Degrees Fault 2 pre-fault phase A voltage angle
00042372 Prefault Vb Mag [2] Volts Fault 2 pre-fault phase B voltage magnitude
00042374 Prefault Vb Ang [2] Degrees Fault 2 pre-fault phase B voltage angle
00042375 Prefault Vc Mag [2] Volts Fault 2 pre-fault phase C voltage magnitude
00042377 Prefault Vc Ang [2] Degrees Fault 2 pre-fault phase C voltage angle
00042378 Fault Ia Mag [2] Amps Fault 2 post-fault phase A current magnitude
0004237A Fault Ia Ang [2] Degrees Fault 2 post-fault phase A current angle
0004237B Fault Ib Mag [2] Amps Fault 2 post-fault phase B current magnitude
0004237D Fault Ib Ang [2] Degrees Fault 2 post-fault phase B current angle
0004237E Fault Ic Mag [2] Amps Fault 2 post-fault phase C current magnitude
00042380 Fault Ic Ang [2] Degrees Fault 2 post-fault phase C current angle
00042381 Fault Va Mag [2] Volts Fault 2 post-fault phase A voltage magnitude
00042383 Fault Va Ang [2] Degrees Fault 2 post-fault phase A voltage angle
00042384 Fault Vb Mag [2] Volts Fault 2 post-fault phase B voltage magnitude
00042386 Fault Vb Ang [2] Degrees Fault 2 post-fault phase B voltage angle
00042387 Fault Vc Mag [2] Volts Fault 2 post-fault phase C voltage magnitude
00042389 Fault Vc Ang [2] Degrees Fault 2 post-fault phase C voltage angle
0004238A Fault Type [2] --- Fault 2 type
0004238B Fault Location [2] --- Fault 2 location
0004256D PMU 1 Va Mag Volts Phasor measurement unit 1 phase A voltage magnitude
0004256F PMU 1 Va Angle Degrees Phasor measurement unit 1 phase A voltage angle
00042570 PMU 1 Vb Mag Volts Phasor measurement unit 1 phase B voltage magnitude
00042572 PMU 1 Vb Angle Degrees Phasor measurement unit 1 phase B voltage angle
00042573 PMU 1 Vc Mag Volts Phasor measurement unit 1 phase C voltage magnitude
00042575 PMU 1 Vc Angle Degrees Phasor measurement unit 1 phase C voltage angle
00042576 PMU 1 Vx Mag Volts Phasor measurement unit 1 auxiliary voltage magnitude

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-13


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00042578 PMU 1 Vx Angle Degrees Phasor measurement unit 1 auxiliary voltage angle
A 00042579 PMU 1 V1 Mag Volts Phasor measurement unit 1 positive-sequence voltage magnitude
0004257B PMU 1 V1 Angle Degrees Phasor measurement unit 1 positive-sequence voltage angle
0004257C PMU 1 V2 Mag Volts Phasor measurement unit 1 negative-sequence voltage magnitude
0004257E PMU 1 V2 Angle Degrees Phasor measurement unit 1 negative-sequence voltage angle
0004257F PMU 1 V0 Mag Volts Phasor measurement unit 1 zero-sequence voltage magnitude
00042581 PMU 1 V0 Angle Degrees Phasor measurement unit 1 zero-sequence voltage angle
00042582 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude
00042584 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle
00042585 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude
00042587 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle
00042588 PMU 1 Ic Mag Amps Phasor measurement unit 1 phase C current magnitude
0004258A PMU 1 Ic Angle Degrees Phasor measurement unit 1 phase C current angle
0004258B PMU 1 Ig Mag Amps Phasor measurement unit 1 ground current magnitude
0004258D PMU 1 Ig Angle Degrees Phasor measurement unit 1 ground current angle
0004258E PMU 1 I1 Mag Amps Phasor measurement unit 1 positive-sequence current magnitude
00042590 PMU 1 I1 Angle Degrees Phasor measurement unit 1 positive-sequence current angle
00042591 PMU 1 I2 Mag Amps Phasor measurement unit 1 negative-sequence current magnitude
00042593 PMU 1 I2 Angle Degrees Phasor measurement unit 1 negative-sequence current angle
00042594 PMU 1 I0 Mag Amps Phasor measurement unit 1 zero-sequence current magnitude
00042596 PMU 1 I0 Angle Degrees Phasor measurement unit 1 zero-sequence current angle
00042597 PMU 1 Freq Hz Phasor measurement unit 1 frequency
00042599 PMU 1 df dt Hz/s Phasor measurement unit 1 rate of change of frequency
0004259A PMU 1 Conf Ch --- Phasor measurement unit 1 configuration change counter
00042800 SRC 1 Ia THD % Source 1 phase A current total harmonic distortion
00042801 SRC 1 Ia Harm[2] % Source 1 phase A current second harmonic
00042802 SRC 1 Ia Harm[3] % Source 1 phase A current third harmonic
00042803 SRC 1 Ia Harm[4] % Source 1 phase A current fourth harmonic
00042804 SRC 1 Ia Harm[5] % Source 1 phase A current fifth harmonic
00042805 SRC 1 Ia Harm[6] % Source 1 phase A current sixth harmonic
00042806 SRC 1 Ia Harm[7] % Source 1 phase A current seventh harmonic
00042807 SRC 1 Ia Harm[8] % Source 1 phase A current eighth harmonic
00042808 SRC 1 Ia Harm[9] % Source 1 phase A current ninth harmonic
00042809 SRC 1 Ia Harm[10] % Source 1 phase A current tenth harmonic
0004280A SRC 1 Ia Harm[11] % Source 1 phase A current eleventh harmonic
0004280B SRC 1 Ia Harm[12] % Source 1 phase A current twelfth harmonic
0004280C SRC 1 Ia Harm[13] % Source 1 phase A current thirteenth harmonic
0004280D SRC 1 Ia Harm[14] % Source 1 phase A current fourteenth harmonic
0004280E SRC 1 Ia Harm[15] % Source 1 phase A current fifteenth harmonic
0004280F SRC 1 Ia Harm[16] % Source 1 phase A current sixteenth harmonic
00042810 SRC 1 Ia Harm[17] % Source 1 phase A current seventeenth harmonic
00042811 SRC 1 Ia Harm[18] % Source 1 phase A current eighteenth harmonic
00042812 SRC 1 Ia Harm[19] % Source 1 phase A current nineteenth harmonic
00042813 SRC 1 Ia Harm[20] % Source 1 phase A current twentieth harmonic
00042814 SRC 1 Ia Harm[21] % Source 1 phase A current twenty-first harmonic
00042815 SRC 1 Ia Harm[22] % Source 1 phase A current twenty-second harmonic
00042816 SRC 1 Ia Harm[23] % Source 1 phase A current twenty-third harmonic

A-14 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042817 SRC 1 Ia Harm[24] % Source 1 phase A current twenty-fourth harmonic
00042818 SRC 1 Ia Harm[25] % Source 1 phase A current twenty-fifth harmonic
00042821 SRC 1 Ib THD % Source 1 phase B current total harmonic distortion
00042822 SRC 1 Ib Harm[2] % Source 1 phase B current second harmonic
00042823 SRC 1 Ib Harm[3] % Source 1 phase B current third harmonic
00042824 SRC 1 Ib Harm[4] % Source 1 phase B current fourth harmonic
00042825 SRC 1 Ib Harm[5] % Source 1 phase B current fifth harmonic
00042826 SRC 1 Ib Harm[6] % Source 1 phase B current sixth harmonic
00042827 SRC 1 Ib Harm[7] % Source 1 phase B current seventh harmonic
00042828 SRC 1 Ib Harm[8] % Source 1 phase B current eighth harmonic
00042829 SRC 1 Ib Harm[9] % Source 1 phase B current ninth harmonic
0004282A SRC 1 Ib Harm[10] % Source 1 phase B current tenth harmonic
0004282B SRC 1 Ib Harm[11] % Source 1 phase B current eleventh harmonic
0004282C SRC 1 Ib Harm[12] % Source 1 phase B current twelfth harmonic
0004282D SRC 1 Ib Harm[13] % Source 1 phase B current thirteenth harmonic
0004282E SRC 1 Ib Harm[14] % Source 1 phase B current fourteenth harmonic
0004282F SRC 1 Ib Harm[15] % Source 1 phase B current fifteenth harmonic
00042830 SRC 1 Ib Harm[16] % Source 1 phase B current sixteenth harmonic
00042831 SRC 1 Ib Harm[17] % Source 1 phase B current seventeenth harmonic
00042832 SRC 1 Ib Harm[18] % Source 1 phase B current eighteenth harmonic
00042833 SRC 1 Ib Harm[19] % Source 1 phase B current nineteenth harmonic
00042834 SRC 1 Ib Harm[20] % Source 1 phase B current twentieth harmonic
00042835 SRC 1 Ib Harm[21] % Source 1 phase B current twenty-first harmonic
00042836 SRC 1 Ib Harm[22] % Source 1 phase B current twenty-second harmonic
00042837 SRC 1 Ib Harm[23] % Source 1 phase B current twenty-third harmonic
00042838 SRC 1 Ib Harm[24] % Source 1 phase B current twenty-fourth harmonic
00042839 SRC 1 Ib Harm[25] % Source 1 phase B current twenty-fifth harmonic
00042842 SRC 1 Ic THD % Source 1 phase C current total harmonic distortion
00042843 SRC 1 Ic Harm[2] % Source 1 phase C current second harmonic
00042844 SRC 1 Ic Harm[3] % Source 1 phase C current third harmonic
00042845 SRC 1 Ic Harm[4] % Source 1 phase C current fourth harmonic
00042846 SRC 1 Ic Harm[5] % Source 1 phase C current fifth harmonic
00042847 SRC 1 Ic Harm[6] % Source 1 phase C current sixth harmonic
00042848 SRC 1 Ic Harm[7] % Source 1 phase C current seventh harmonic
00042849 SRC 1 Ic Harm[8] % Source 1 phase C current eighth harmonic
0004284A SRC 1 Ic Harm[9] % Source 1 phase C current ninth harmonic
0004284B SRC 1 Ic Harm[10] % Source 1 phase C current tenth harmonic
0004284C SRC 1 Ic Harm[11] % Source 1 phase C current eleventh harmonic
0004284D SRC 1 Ic Harm[12] % Source 1 phase C current twelfth harmonic
0004284E SRC 1 Ic Harm[13] % Source 1 phase C current thirteenth harmonic
0004284F SRC 1 Ic Harm[14] % Source 1 phase C current fourteenth harmonic
00042850 SRC 1 Ic Harm[15] % Source 1 phase C current fifteenth harmonic
00042851 SRC 1 Ic Harm[16] % Source 1 phase C current sixteenth harmonic
00042852 SRC 1 Ic Harm[17] % Source 1 phase C current seventeenth harmonic
00042853 SRC 1 Ic Harm[18] % Source 1 phase C current eighteenth harmonic
00042854 SRC 1 Ic Harm[19] % Source 1 phase C current nineteenth harmonic
00042855 SRC 1 Ic Harm[20] % Source 1 phase C current twentieth harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-15


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00042856 SRC 1 Ic Harm[21] % Source 1 phase C current twenty-first harmonic
A 00042857 SRC 1 Ic Harm[22] % Source 1 phase C current twenty-second harmonic
00042858 SRC 1 Ic Harm[23] % Source 1 phase C current twenty-third harmonic
00042859 SRC 1 Ic Harm[24] % Source 1 phase C current twenty-fourth harmonic
0004285A SRC 1 Ic Harm[25] % Source 1 phase C current twenty-fifth harmonic
00042863 SRC 2 Ia THD % Source 2 phase A current total harmonic distortion
00042864 SRC 2 Ia Harm[2] % Source 2 phase A current second harmonic
00042865 SRC 2 Ia Harm[3] % Source 2 phase A current third harmonic
00042866 SRC 2 Ia Harm[4] % Source 2 phase A current fourth harmonic
00042867 SRC 2 Ia Harm[5] % Source 2 phase A current fifth harmonic
00042868 SRC 2 Ia Harm[6] % Source 2 phase A current sixth harmonic
00042869 SRC 2 Ia Harm[7] % Source 2 phase A current seventh harmonic
0004286A SRC 2 Ia Harm[8] % Source 2 phase A current eighth harmonic
0004286B SRC 2 Ia Harm[9] % Source 2 phase A current ninth harmonic
0004286C SRC 2 Ia Harm[10] % Source 2 phase A current tenth harmonic
0004286D SRC 2 Ia Harm[11] % Source 2 phase A current eleventh harmonic
0004286E SRC 2 Ia Harm[12] % Source 2 phase A current twelfth harmonic
0004286F SRC 2 Ia Harm[13] % Source 2 phase A current thirteenth harmonic
00042870 SRC 2 Ia Harm[14] % Source 2 phase A current fourteenth harmonic
00042871 SRC 2 Ia Harm[15] % Source 2 phase A current fifteenth harmonic
00042872 SRC 2 Ia Harm[16] % Source 2 phase A current sixteenth harmonic
00042873 SRC 2 Ia Harm[17] % Source 2 phase A current seventeenth harmonic
00042874 SRC 2 Ia Harm[18] % Source 2 phase A current eighteenth harmonic
00042875 SRC 2 Ia Harm[19] % Source 2 phase A current nineteenth harmonic
00042876 SRC 2 Ia Harm[20] % Source 2 phase A current twentieth harmonic
00042877 SRC 2 Ia Harm[21] % Source 2 phase A current twenty-first harmonic
00042878 SRC 2 Ia Harm[22] % Source 2 phase A current twenty-second harmonic
00042879 SRC 2 Ia Harm[23] % Source 2 phase A current twenty-third harmonic
0004287A SRC 2 Ia Harm[24] % Source 2 phase A current twenty-fourth harmonic
0004287B SRC 2 Ia Harm[25] % Source 2 phase A current twenty-fifth harmonic
00042884 SRC 2 Ib THD % Source 2 phase B current total harmonic distortion
00042885 SRC 2 Ib Harm[2] % Source 2 phase B current second harmonic
00042886 SRC 2 Ib Harm[3] % Source 2 phase B current third harmonic
00042887 SRC 2 Ib Harm[4] % Source 2 phase B current fourth harmonic
00042888 SRC 2 Ib Harm[5] % Source 2 phase B current fifth harmonic
00042889 SRC 2 Ib Harm[6] % Source 2 phase B current sixth harmonic
0004288A SRC 2 Ib Harm[7] % Source 2 phase B current seventh harmonic
0004288B SRC 2 Ib Harm[8] % Source 2 phase B current eighth harmonic
0004288C SRC 2 Ib Harm[9] % Source 2 phase B current ninth harmonic
0004288D SRC 2 Ib Harm[10] % Source 2 phase B current tenth harmonic
0004288E SRC 2 Ib Harm[11] % Source 2 phase B current eleventh harmonic
0004288F SRC 2 Ib Harm[12] % Source 2 phase B current twelfth harmonic
00042890 SRC 2 Ib Harm[13] % Source 2 phase B current thirteenth harmonic
00042891 SRC 2 Ib Harm[14] % Source 2 phase B current fourteenth harmonic
00042892 SRC 2 Ib Harm[15] % Source 2 phase B current fifteenth harmonic
00042893 SRC 2 Ib Harm[16] % Source 2 phase B current sixteenth harmonic
00042894 SRC 2 Ib Harm[17] % Source 2 phase B current seventeenth harmonic

A-16 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042895 SRC 2 Ib Harm[18] % Source 2 phase B current eighteenth harmonic
00042896 SRC 2 Ib Harm[19] % Source 2 phase B current nineteenth harmonic
00042897 SRC 2 Ib Harm[20] % Source 2 phase B current twentieth harmonic
00042898 SRC 2 Ib Harm[21] % Source 2 phase B current twenty-first harmonic
00042899 SRC 2 Ib Harm[22] % Source 2 phase B current twenty-second harmonic
0004289A SRC 2 Ib Harm[23] % Source 2 phase B current twenty-third harmonic
0004289B SRC 2 Ib Harm[24] % Source 2 phase B current twenty-fourth harmonic
0004289C SRC 2 Ib Harm[25] % Source 2 phase B current twenty-fifth harmonic
000428A5 SRC 2 Ic THD % Source 2 phase C current total harmonic distortion
000428A6 SRC 2 Ic Harm[2] % Source 2 phase C current second harmonic
000428A7 SRC 2 Ic Harm[3] % Source 2 phase C current third harmonic
000428A8 SRC 2 Ic Harm[4] % Source 2 phase C current fourth harmonic
000428A9 SRC 2 Ic Harm[5] % Source 2 phase C current fifth harmonic
000428AA SRC 2 Ic Harm[6] % Source 2 phase C current sixth harmonic
000428AB SRC 2 Ic Harm[7] % Source 2 phase C current seventh harmonic
000428AC SRC 2 Ic Harm[8] % Source 2 phase C current eighth harmonic
000428AD SRC 2 Ic Harm[9] % Source 2 phase C current ninth harmonic
000428AE SRC 2 Ic Harm[10] % Source 2 phase C current tenth harmonic
000428AF SRC 2 Ic Harm[11] % Source 2 phase C current eleventh harmonic
000428B0 SRC 2 Ic Harm[12] % Source 2 phase C current twelfth harmonic
000428B1 SRC 2 Ic Harm[13] % Source 2 phase C current thirteenth harmonic
000428B2 SRC 2 Ic Harm[14] % Source 2 phase C current fourteenth harmonic
000428B3 SRC 2 Ic Harm[15] % Source 2 phase C current fifteenth harmonic
000428B4 SRC 2 Ic Harm[16] % Source 2 phase C current sixteenth harmonic
000428B5 SRC 2 Ic Harm[17] % Source 2 phase C current seventeenth harmonic
000428B6 SRC 2 Ic Harm[18] % Source 2 phase C current eighteenth harmonic
000428B7 SRC 2 Ic Harm[19] % Source 2 phase C current nineteenth harmonic
000428B8 SRC 2 Ic Harm[20] % Source 2 phase C current twentieth harmonic
000428B9 SRC 2 Ic Harm[21] % Source 2 phase C current twenty-first harmonic
000428BA SRC 2 Ic Harm[22] % Source 2 phase C current twenty-second harmonic
000428BB SRC 2 Ic Harm[23] % Source 2 phase C current twenty-third harmonic
000428BC SRC 2 Ic Harm[24] % Source 2 phase C current twenty-fourth harmonic
000428BD SRC 2 Ic Harm[25] % Source 2 phase C current twenty-fifth harmonic
000428C6 SRC 3 Ia THD % Source 3 phase A current total harmonic distortion
000428C7 SRC 3 Ia Harm[2] % Source 3 phase A current second harmonic
000428C8 SRC 3 Ia Harm[3] % Source 3 phase A current third harmonic
000428C9 SRC 3 Ia Harm[4] % Source 3 phase A current fourth harmonic
000428CA SRC 3 Ia Harm[5] % Source 3 phase A current fifth harmonic
000428CB SRC 3 Ia Harm[6] % Source 3 phase A current sixth harmonic
000428CC SRC 3 Ia Harm[7] % Source 3 phase A current seventh harmonic
000428CD SRC 3 Ia Harm[8] % Source 3 phase A current eighth harmonic
000428CE SRC 3 Ia Harm[9] % Source 3 phase A current ninth harmonic
000428CF SRC 3 Ia Harm[10] % Source 3 phase A current tenth harmonic
000428D0 SRC 3 Ia Harm[11] % Source 3 phase A current eleventh harmonic
000428D1 SRC 3 Ia Harm[12] % Source 3 phase A current twelfth harmonic
000428D2 SRC 3 Ia Harm[13] % Source 3 phase A current thirteenth harmonic
000428D3 SRC 3 Ia Harm[14] % Source 3 phase A current fourteenth harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-17


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


000428D4 SRC 3 Ia Harm[15] % Source 3 phase A current fifteenth harmonic
A 000428D5 SRC 3 Ia Harm[16] % Source 3 phase A current sixteenth harmonic
000428D6 SRC 3 Ia Harm[17] % Source 3 phase A current seventeenth harmonic
000428D7 SRC 3 Ia Harm[18] % Source 3 phase A current eighteenth harmonic
000428D8 SRC 3 Ia Harm[19] % Source 3 phase A current nineteenth harmonic
000428D9 SRC 3 Ia Harm[20] % Source 3 phase A current twentieth harmonic
000428DA SRC 3 Ia Harm[21] % Source 3 phase A current twenty-first harmonic
000428DB SRC 3 Ia Harm[22] % Source 3 phase A current twenty-second harmonic
000428DC SRC 3 Ia Harm[23] % Source 3 phase A current twenty-third harmonic
000428DD SRC 3 Ia Harm[24] % Source 3 phase A current twenty-fourth harmonic
000428DE SRC 3 Ia Harm[25] % Source 3 phase A current twenty-fifth harmonic
000428E7 SRC 3 Ib THD % Source 3 phase B current total harmonic distortion
000428E8 SRC 3 Ib Harm[2] % Source 3 phase B current second harmonic
000428E9 SRC 3 Ib Harm[3] % Source 3 phase B current third harmonic
000428EA SRC 3 Ib Harm[4] % Source 3 phase B current fourth harmonic
000428EB SRC 3 Ib Harm[5] % Source 3 phase B current fifth harmonic
000428EC SRC 3 Ib Harm[6] % Source 3 phase B current sixth harmonic
000428ED SRC 3 Ib Harm[7] % Source 3 phase B current seventh harmonic
000428EE SRC 3 Ib Harm[8] % Source 3 phase B current eighth harmonic
000428EF SRC 3 Ib Harm[9] % Source 3 phase B current ninth harmonic
000428F0 SRC 3 Ib Harm[10] % Source 3 phase B current tenth harmonic
000428F1 SRC 3 Ib Harm[11] % Source 3 phase B current eleventh harmonic
000428F2 SRC 3 Ib Harm[12] % Source 3 phase B current twelfth harmonic
000428F3 SRC 3 Ib Harm[13] % Source 3 phase B current thirteenth harmonic
000428F4 SRC 3 Ib Harm[14] % Source 3 phase B current fourteenth harmonic
000428F5 SRC 3 Ib Harm[15] % Source 3 phase B current fifteenth harmonic
000428F6 SRC 3 Ib Harm[16] % Source 3 phase B current sixteenth harmonic
000428F7 SRC 3 Ib Harm[17] % Source 3 phase B current seventeenth harmonic
000428F8 SRC 3 Ib Harm[18] % Source 3 phase B current eighteenth harmonic
000428F9 SRC 3 Ib Harm[19] % Source 3 phase B current nineteenth harmonic
000428FA SRC 3 Ib Harm[20] % Source 3 phase B current twentieth harmonic
000428FB SRC 3 Ib Harm[21] % Source 3 phase B current twenty-first harmonic
000428FC SRC 3 Ib Harm[22] % Source 3 phase B current twenty-second harmonic
000428FD SRC 3 Ib Harm[23] % Source 3 phase B current twenty-third harmonic
000428FE SRC 3 Ib Harm[24] % Source 3 phase B current twenty-fourth harmonic
000428FF SRC 3 Ib Harm[25] % Source 3 phase B current twenty-fifth harmonic
00042908 SRC 3 Ic THD % Source 3 phase C current total harmonic distortion
00042909 SRC 3 Ic Harm[2] % Source 3 phase C current second harmonic
0004290A SRC 3 Ic Harm[3] % Source 3 phase C current third harmonic
0004290B SRC 3 Ic Harm[4] % Source 3 phase C current fourth harmonic
0004290C SRC 3 Ic Harm[5] % Source 3 phase C current fifth harmonic
0004290D SRC 3 Ic Harm[6] % Source 3 phase C current sixth harmonic
0004290E SRC 3 Ic Harm[7] % Source 3 phase C current seventh harmonic
0004290F SRC 3 Ic Harm[8] % Source 3 phase C current eighth harmonic
00042910 SRC 3 Ic Harm[9] % Source 3 phase C current ninth harmonic
00042911 SRC 3 Ic Harm[10] % Source 3 phase C current tenth harmonic
00042912 SRC 3 Ic Harm[11] % Source 3 phase C current eleventh harmonic

A-18 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042913 SRC 3 Ic Harm[12] % Source 3 phase C current twelfth harmonic
00042914 SRC 3 Ic Harm[13] % Source 3 phase C current thirteenth harmonic
00042915 SRC 3 Ic Harm[14] % Source 3 phase C current fourteenth harmonic
00042916 SRC 3 Ic Harm[15] % Source 3 phase C current fifteenth harmonic
00042917 SRC 3 Ic Harm[16] % Source 3 phase C current sixteenth harmonic
00042918 SRC 3 Ic Harm[17] % Source 3 phase C current seventeenth harmonic
00042919 SRC 3 Ic Harm[18] % Source 3 phase C current eighteenth harmonic
0004291A SRC 3 Ic Harm[19] % Source 3 phase C current nineteenth harmonic
0004291B SRC 3 Ic Harm[20] % Source 3 phase C current twentieth harmonic
0004291C SRC 3 Ic Harm[21] % Source 3 phase C current twenty-first harmonic
0004291D SRC 3 Ic Harm[22] % Source 3 phase C current twenty-second harmonic
0004291E SRC 3 Ic Harm[23] % Source 3 phase C current twenty-third harmonic
000429!F SRC 3 Ic Harm[24] % Source 3 phase C current twenty-fourth harmonic
00042920 SRC 3 Ic Harm[25] % Source 3 phase C current twenty-fifth harmonic
00042929 SRC 4 Ia THD % Source 4 phase A current total harmonic distortion
0004292A SRC 4 Ia Harm[2] % Source 4 phase A current second harmonic
0004292B SRC 4 Ia Harm[3] % Source 4 phase A current third harmonic
0004292C SRC 4 Ia Harm[4] % Source 4 phase A current fourth harmonic
0004292D SRC 4 Ia Harm[5] % Source 4 phase A current fifth harmonic
0004292E SRC 4 Ia Harm[6] % Source 4 phase A current sixth harmonic
0004292F SRC 4 Ia Harm[7] % Source 4 phase A current seventh harmonic
00042930 SRC 4 Ia Harm[8] % Source 4 phase A current eighth harmonic
00042931 SRC 4 Ia Harm[9] % Source 4 phase A current ninth harmonic
00042932 SRC 4 Ia Harm[10] % Source 4 phase A current tenth harmonic
00042933 SRC 4 Ia Harm[11] % Source 4 phase A current eleventh harmonic
00042934 SRC 4 Ia Harm[12] % Source 4 phase A current twelfth harmonic
00042935 SRC 4 Ia Harm[13] % Source 4 phase A current thirteenth harmonic
00042936 SRC 4 Ia Harm[14] % Source 4 phase A current fourteenth harmonic
00042937 SRC 4 Ia Harm[15] % Source 4 phase A current fifteenth harmonic
00042938 SRC 4 Ia Harm[16] % Source 4 phase A current sixteenth harmonic
00042939 SRC 4 Ia Harm[17] % Source 4 phase A current seventeenth harmonic
0004293A SRC 4 Ia Harm[18] % Source 4 phase A current eighteenth harmonic
0004293B SRC 4 Ia Harm[19] % Source 4 phase A current nineteenth harmonic
0004293C SRC 4 Ia Harm[20] % Source 4 phase A current twentieth harmonic
0004293D SRC 4 Ia Harm[21] % Source 4 phase A current twenty-first harmonic
0004293E SRC 4 Ia Harm[22] % Source 4 phase A current twenty-second harmonic
0004293F SRC 4 Ia Harm[23] % Source 4 phase A current twenty-third harmonic
00042940 SRC 4 Ia Harm[24] % Source 4 phase A current twenty-fourth harmonic
00042941 SRC 4 Ia Harm[25] % Source 4 phase A current twenty-fifth harmonic
0004294A SRC 4 Ib THD % Source 4 phase B current total harmonic distortion
0004294B SRC 4 Ib Harm[2] % Source 4 phase B current second harmonic
0004294C SRC 4 Ib Harm[3] % Source 4 phase B current third harmonic
0004294D SRC 4 Ib Harm[4] % Source 4 phase B current fourth harmonic
0004294E SRC 4 Ib Harm[5] % Source 4 phase B current fifth harmonic
0004294F SRC 4 Ib Harm[6] % Source 4 phase B current sixth harmonic
00042950 SRC 4 Ib Harm[7] % Source 4 phase B current seventh harmonic
00042951 SRC 4 Ib Harm[8] % Source 4 phase B current eighth harmonic

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-19


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00042952 SRC 4 Ib Harm[9] % Source 4 phase B current ninth harmonic
A 00042953 SRC 4 Ib Harm[10] % Source 4 phase B current tenth harmonic
00042954 SRC 4 Ib Harm[11] % Source 4 phase B current eleventh harmonic
00042955 SRC 4 Ib Harm[12] % Source 4 phase B current twelfth harmonic
00042956 SRC 4 Ib Harm[13] % Source 4 phase B current thirteenth harmonic
00042957 SRC 4 Ib Harm[14] % Source 4 phase B current fourteenth harmonic
00042958 SRC 4 Ib Harm[15] % Source 4 phase B current fifteenth harmonic
00042959 SRC 4 Ib Harm[16] % Source 4 phase B current sixteenth harmonic
0004295A SRC 4 Ib Harm[17] % Source 4 phase B current seventeenth harmonic
0004295B SRC 4 Ib Harm[18] % Source 4 phase B current eighteenth harmonic
0004295C SRC 4 Ib Harm[19] % Source 4 phase B current nineteenth harmonic
0004295D SRC 4 Ib Harm[20] % Source 4 phase B current twentieth harmonic
0004295E SRC 4 Ib Harm[21] % Source 4 phase B current twenty-first harmonic
0004295F SRC 4 Ib Harm[22] % Source 4 phase B current twenty-second harmonic
00042960 SRC 4 Ib Harm[23] % Source 4 phase B current twenty-third harmonic
00042961 SRC 4 Ib Harm[24] % Source 4 phase B current twenty-fourth harmonic
00042962 SRC 4 Ib Harm[25] % Source 4 phase B current twenty-fifth harmonic
0004296B SRC 4 Ic THD % Source 4 phase C current total harmonic distortion
0004296C SRC 4 Ic Harm[2] % Source 4 phase C current second harmonic
0004296D SRC 4 Ic Harm[3] % Source 4 phase C current third harmonic
0004296E SRC 4 Ic Harm[4] % Source 4 phase C current fourth harmonic
0004296F SRC 4 Ic Harm[5] % Source 4 phase C current fifth harmonic
00042970 SRC 4 Ic Harm[6] % Source 4 phase C current sixth harmonic
00042971 SRC 4 Ic Harm[7] % Source 4 phase C current seventh harmonic
00042972 SRC 4 Ic Harm[8] % Source 4 phase C current eighth harmonic
00042973 SRC 4 Ic Harm[9] % Source 4 phase C current ninth harmonic
00042974 SRC 4 Ic Harm[10] % Source 4 phase C current tenth harmonic
00042975 SRC 4 Ic Harm[11] % Source 4 phase C current eleventh harmonic
00042976 SRC 4 Ic Harm[12] % Source 4 phase C current twelfth harmonic
00042977 SRC 4 Ic Harm[13] % Source 4 phase C current thirteenth harmonic
00042978 SRC 4 Ic Harm[14] % Source 4 phase C current fourteenth harmonic
00042979 SRC 4 Ic Harm[15] % Source 4 phase C current fifteenth harmonic
0004297A SRC 4 Ic Harm[16] % Source 4 phase C current sixteenth harmonic
0004297B SRC 4 Ic Harm[17] % Source 4 phase C current seventeenth harmonic
0004297C SRC 4 Ic Harm[18] % Source 4 phase C current eighteenth harmonic
0004297D SRC 4 Ic Harm[19] % Source 4 phase C current nineteenth harmonic
0004297E SRC 4 Ic Harm[20] % Source 4 phase C current twentieth harmonic
0004297F SRC 4 Ic Harm[21] % Source 4 phase C current twenty-first harmonic
00042980 SRC 4 Ic Harm[22] % Source 4 phase C current twenty-second harmonic
00042981 SRC 4 Ic Harm[23] % Source 4 phase C current twenty-third harmonic
00042982 SRC 4 Ic Harm[24] % Source 4 phase C current twenty-fourth harmonic
00042983 SRC 4 Ic Harm[25] % Source 4 phase C current twenty-fifth harmonic
00042A60 Synchchk 1 Delta V Volts Synchrocheck 1 delta voltage
00042A62 Synchchk 1 Delta Phs Degrees Synchrocheck 1 delta phase
00042A63 Synchchk 1 SSCP DPh Degrees Synchrocheck 1 synchscope
00042A64 Synchchk 1 Delta F Hz Synchrocheck 1 delta frequency
00042A65 Synchchk 1 V1 Mag Volts Synchrocheck 1 V1 mag

A-20 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00042A67 Synchchk 1 V1 Ang Degrees Synchrocheck 1 V1 angle
00042A68 Synchchk 1 V2 Mag Volts Synchrocheck 1 V2 mag
00042A6A Synchchk 1 V2 Ang Degrees Synchrocheck 1 V2 angle
00042A6B Synchchk 1 V2’ Mag Volts Synchrocheck 1 V2_mag
00042A6D Synchchk 1 V2’ Ang Degrees Synchrocheck 1 V2_angle
00042A6E Synchchk 1 Delta’ Phs Degrees Synchrocheck 1 delta_phase
00042A6F Synchchk 1 SSCP DPh’ Degrees Synchrocheck 1 _synchscope
00042A70 Synchchk 2 Delta V Volts Synchrocheck 2 delta voltage
00042A72 Synchchk 2 Delta Phs Degrees Synchrocheck 2 delta phase
00042A73 Synchchk 2 SSCP DPh Degrees Synchrocheck 2 synchscope
00042A74 Synchchk 2 Delta F Hz Synchrocheck 2 delta frequency
00042A75 Synchchk 2 V1 Mag Volts Synchrocheck 2 V1 mag
00042A77 Synchchk 2 V1 Ang Degrees Synchrocheck 2 V1 angle
00042A78 Synchchk 2 V2 Mag Volts Synchrocheck 2 V2 mag
00042A7A Synchchk 2 V2 Ang Degrees Synchrocheck 2 V2 angle
00042A7B Synchchk 2 V2’ Mag Volts Synchrocheck 2 V2_mag
00042A7D Synchchk 2 V2’ Ang Degrees Synchrocheck 2 V2_angle
00042A7E Synchchk 2 Delta’ Phs Degrees Synchrocheck 2 delta_phase
00042A7F Synchchk 2 SSCP DPh’ Degrees Synchrocheck 2 _synchscope
00042A80 Synchchk 3 Delta V Volts Synchrocheck 3 delta voltage
00042A82 Synchchk 3 Delta Phs Degrees Synchrocheck 3 delta phase
00042A83 Synchchk 3 SSCP DPh Degrees Synchrocheck 3 synchscope
00042A84 Synchchk 3 Delta F Volts Synchrocheck 3 delta frequency
00042A85 Synchchk 3 V1 Mag Volts Synchrocheck 3 V1 mag
00042A87 Synchchk 3 V1 Ang Degrees Synchrocheck 3 V1 angle
00042A88 Synchchk 3 V2 Mag Volts Synchrocheck 3 V2 mag
00042A8A Synchchk 3 V2 Ang Degrees Synchrocheck 3 V2 angle
00042A8B Synchchk 3 V2’ Mag Volts Synchrocheck 3 V2_mag
00042A8D Synchchk 3 V2’ Ang Degrees Synchrocheck 3 V2_angle
00042A8E Synchchk 3 Delta’ Phs Degrees Synchrocheck 3 delta_phase
00042A8F Synchchk 3 SSCP DPh’ Degrees Synchrocheck 3 _synchscope
00042A90 Synchchk 4 Delta V Volts Synchrocheck 4 delta voltage
00042A92 Synchchk 4 Delta Phs Degrees Synchrocheck 4 delta phase
00042A93 Synchchk 4 SSCP DPh Degrees Synchrocheck 4 synchscope
00042A94 Synchchk 4 Delta F Hz Synchrocheck 4 delta frequency
00042A95 Synchchk 4 V1 Mag Volts Synchrocheck 4 V1 mag
00042A97 Synchchk 4 V1 Ang Degrees Synchrocheck 4 V1 angle
00042A98 Synchchk 4 V2 Mag Volts Synchrocheck 4 V2 mag
00042A9A Synchchk 4 V2 Ang Degrees Synchrocheck 4 V2 angle
00042A9B Synchchk 4 V2’ Mag Volts Synchrocheck 4 V2_mag
00042A9D Synchchk 4 V2’ Ang Degrees Synchrocheck 4 V2_angle
00042A9E Synchchk 4 Delta’ Phs Degrees Synchrocheck 4 delta_phase
00042A9F Synchchk 4 SSCP DPh’ Degrees Synchrocheck 4 _synchscope
00043012 Oscill Num Triggers --- Oscillography number of triggers
000436D0 Harmonic Det 1 IA % Harmonic Detection 1 A-phase quantity
000436D1 Harmonic Det 1 IB % Harmonic Detection 1 B-phase quantity
000436D2 Harmonic Det 1 IC % Harmonic Detection 1 C-phase quantity

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-21


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


000436D3 Harmonic Det 1 IAVG % Harmonic Detection 1 average of phases quantity
A 000436D4 Harmonic Det 1 IG % Harmonic Detection 1 ground quantity
000436D5 Harmonic Det 2 IA % Harmonic Detection 2 A-phase quantity
000436D6 Harmonic Det 2 IB % Harmonic Detection 2 B-phase quantity
000436D7 Harmonic Det 2 IC % Harmonic Detection 2 C-phase quantity
... …… ….
000436E9 Harmonic Det 6 IA % Harmonic Detection 6 A-phase quantity
000436EA Harmonic Det 6 IB % Harmonic Detection 6 B-phase quantity
000436EB Harmonic Det 6 IC % Harmonic Detection 6 C-phase quantity
000436EC Harmonic Det 6 IAVG % Harmonic Detection 6 average of phases quantity
000436ED Harmonic Det 6 IG % Harmonic Detection 6 ground quantity
000434C0 DCmA Ip 1 mA DCmA input 1 actual value
000434C2 DCmA Ip 2 mA DCmA input 2 actual value
000434C4 DCmA Ip 3 mA DCmA input 3 actual value
000434C6 DCmA Ip 4 mA DCmA input 4 actual value
000434C8 DCmA Ip 5 mA DCmA input 5 actual value
000434CA DCmA Ip 6 mA DCmA input 6 actual value
000434CC DCmA Ip 7 mA DCmA input 7 actual value
000434CE DCmA Ip 8 mA DCmA input 8 actual value
000434D0 DCmA Ip 9 mA DCmA input 9 actual value
000434D2 DCmA Ip 10 mA DCmA input 10 actual value
000434D4 DCmA Ip 11 mA DCmA input 11 actual value
000434D6 DCmA Ip 12 mA DCmA input 12 actual value
000434D8 DCmA Ip 13 mA DCmA input 13 actual value
000434DA DCmA Ip 14 mA DCmA input 14 actual value
000434DC DCmA Ip 15 mA DCmA input 15 actual value
000434DE DCmA Ip 16 mA DCmA input 16 actual value
000434E0 DCmA Ip 17 mA DCmA input 17 actual value
000434E2 DCmA Ip 18 mA DCmA input 18 actual value
000434E4 DCmA Ip 19 mA DCmA input 19 actual value
000434E6 DCmA Ip 20 mA DCmA input 20 actual value
000434E8 DCmA Ip 21 mA DCmA input 21 actual value
000434EA DCmA Ip 22 mA DCmA input 22 actual value
000434EC DCmA Ip 23 mA DCmA input 23 actual value
000434EE DCmA Ip 24 mA DCmA input 24 actual value
000434F0 RTD Ip 1 --- RTD input 1 actual value
000434F1 RTD Ip 2 --- RTD input 2 actual value
000434F2 RTD Ip 3 --- RTD input 3 actual value
000434F3 RTD Ip 4 --- RTD input 4 actual value
000434F4 RTD Ip 5 --- RTD input 5 actual value
000434F5 RTD Ip 6 --- RTD input 6 actual value
000434F6 RTD Ip 7 --- RTD input 7 actual value
000434F7 RTD Ip 8 --- RTD input 8 actual value
000434F8 RTD Ip 9 --- RTD input 9 actual value
000434F9 RTD Ip 10 --- RTD input 10 actual value
000434FA RTD Ip 11 --- RTD input 11 actual value
000434FB RTD Ip 12 --- RTD input 12 actual value

A-22 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
000434FC RTD Ip 13 --- RTD input 13 actual value
000434FD RTD Ip 14 --- RTD input 14 actual value
000434FE RTD Ip 15 --- RTD input 15 actual value
000434FF RTD Ip 16 --- RTD input 16 actual value
00043500 RTD Ip 17 --- RTD input 17 actual value
00043501 RTD Ip 18 --- RTD input 18 actual value
00043502 RTD Ip 19 --- RTD input 19 actual value
00043503 RTD Ip 20 --- RTD input 20 actual value
00043504 RTD Ip 21 --- RTD input 21 actual value
00043505 RTD Ip 22 --- RTD input 22 actual value
00043506 RTD Ip 23 --- RTD input 23 actual value
00043507 RTD Ip 24 --- RTD input 24 actual value
00043508 RTD Ip 25 --- RTD input 25 actual value
00043509 RTD Ip 26 --- RTD input 26 actual value
0004350A RTD Ip 27 --- RTD input 27 actual value
0004350B RTD Ip 28 --- RTD input 28 actual value
0004350C RTD Ip 29 --- RTD input 29 actual value
0004350D RTD Ip 30 --- RTD input 30 actual value
0004350E RTD Ip 31 --- RTD input 31 actual value
0004350F RTD Ip 32 --- RTD input 32 actual value
00043510 RTD Ip 33 --- RTD input 33 actual value
00043511 RTD Ip 34 --- RTD input 34 actual value
00043512 RTD Ip 35 --- RTD input 35 actual value
00043513 RTD Ip 36 --- RTD input 36 actual value
00043514 RTD Ip 37 --- RTD input 37 actual value
00043515 RTD Ip 38 --- RTD input 38 actual value
00043516 RTD Ip 39 --- RTD input 39 actual value
00043517 RTD Ip 40 --- RTD input 40 actual value
00043518 RTD Ip 41 --- RTD input 41 actual value
00043519 RTD Ip 42 --- RTD input 42 actual value
0004351A RTD Ip 43 --- RTD input 43 actual value
0004351B RTD Ip 44 --- RTD input 44 actual value
0004351C RTD Ip 45 --- RTD input 45 actual value
0004351D RTD Ip 46 --- RTD input 46 actual value
0004351E RTD Ip 47 --- RTD input 47 actual value
0004351F RTD Ip 48 --- RTD input 48 actual value
00043520 Ohm Inputs 1 Value Ohms Ohm inputs 1 value
00043521 Ohm Inputs 2 Value Ohms Ohm inputs 2 value
0004376D PTP–IRIG-B Delta ns PTP time minus IRIG-B time
00044F60 SRC 1 Ia RMS Amps Source 1 phase A current RMS
00044F62 SRC 1 Ib RMS Amps Source 1 phase B current RMS
00044F64 SRC 1 Ic RMS Amps Source 1 phase C current RMS
00044F66 SRC 1 In RMS Amps Source 1 neutral current RMS
00044F68 SRC 1 Ia Mag Amps Source 1 phase A current magnitude
00044F6A SRC 1 Ia Angle Degrees Source 1 phase A current angle
00044F6B SRC 1 Ib Mag Amps Source 1 phase B current magnitude
00044F6D SRC 1 Ib Angle Degrees Source 1 phase B current angle

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-23


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00044F6E SRC 1 Ic Mag Amps Source 1 phase C current magnitude
A 00044F70 SRC 1 Ic Angle Degrees Source 1 phase C current angle
00044F71 SRC 1 In Mag Amps Source 1 neutral current magnitude
00044F73 SRC 1 In Angle Degrees Source 1 neutral current angle
00044F74 SRC 1 Ig RMS Amps Source 1 ground current RMS
00044F76 SRC 1 Ig Mag Amps Source 1 ground current magnitude
00044F78 SRC 1 Ig Angle Degrees Source 1 ground current angle
00044F79 SRC 1 I_0 Mag Amps Source 1 zero-sequence current magnitude
00044F7B SRC 1 I_0 Angle Degrees Source 1 zero-sequence current angle
00044F7C SRC 1 I_1 Mag Amps Source 1 positive-sequence current magnitude
00044F7E SRC 1 I_1 Angle Degrees Source 1 positive-sequence current angle
00044F7F SRC 1 I_2 Mag Amps Source 1 negative-sequence current magnitude
00044F81 SRC 1 I_2 Angle Degrees Source 1 negative-sequence current angle
00044F82 SRC 1 Igd Mag Amps Source 1 differential ground current magnitude
00044F84 SRC 1 Igd Angle Degrees Source 1 differential ground current angle
00044FA0 SRC 2 Ia RMS Amps Source 2 phase A current RMS
00044FA2 SRC 2 Ib RMS Amps Source 2 phase B current RMS
00044FA4 SRC 2 Ic RMS Amps Source 2 phase C current RMS
00044FA6 SRC 2 In RMS Amps Source 2 neutral current RMS
00044FA8 SRC 2 Ia Mag Amps Source 2 phase A current magnitude
00044FAA SRC 2 Ia Angle Degrees Source 2 phase A current angle
00044FAB SRC 2 Ib Mag Amps Source 2 phase B current magnitude
00044FAD SRC 2 Ib Angle Degrees Source 2 phase B current angle
00044FAE SRC 2 Ic Mag Amps Source 2 phase C current magnitude
00044FB0 SRC 2 Ic Angle Degrees Source 2 phase C current angle
00044FB1 SRC 2 In Mag Amps Source 2 neutral current magnitude
00044FB3 SRC 2 In Angle Degrees Source 2 neutral current angle
00044FB4 SRC 2 Ig RMS Amps Source 2 ground current RMS
00044FB6 SRC 2 Ig Mag Amps Source 2 ground current magnitude
00044FB8 SRC 2 Ig Angle Degrees Source 2 ground current angle
00044FB9 SRC 2 I_0 Mag Amps Source 2 zero-sequence current magnitude
00044FBB SRC 2 I_0 Angle Degrees Source 2 zero-sequence current angle
00044FBC SRC 2 I_1 Mag Amps Source 2 positive-sequence current magnitude
00044FBE SRC 2 I_1 Angle Degrees Source 2 positive-sequence current angle
00044FBF SRC 2 I_2 Mag Amps Source 2 negative-sequence current magnitude
00044FC1 SRC 2 I_2 Angle Degrees Source 2 negative-sequence current angle
00044FC2 SRC 2 Igd Mag Amps Source 2 differential ground current magnitude
00044FC4 SRC 2 Igd Angle Degrees Source 2 differential ground current angle
00044FE0 SRC 3 Ia RMS Amps Source 3 phase A current RMS
00044FE2 SRC 3 Ib RMS Amps Source 3 phase B current RMS
00044FE4 SRC 3 Ic RMS Amps Source 3 phase C current RMS
00044FE6 SRC 3 In RMS Amps Source 3 neutral current RMS
00044FE8 SRC 3 Ia Mag Amps Source 3 phase A current magnitude
00044FEA SRC 3 Ia Angle Degrees Source 3 phase A current angle
00044FEB SRC 3 Ib Mag Amps Source 3 phase B current magnitude
00044FED SRC 3 Ib Angle Degrees Source 3 phase B current angle
00044FEE SRC 3 Ic Mag Amps Source 3 phase C current magnitude

A-24 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
00044FF0 SRC 3 Ic Angle Degrees Source 3 phase C current angle
00044FF1 SRC 3 In Mag Amps Source 3 neutral current magnitude
00044FF3 SRC 3 In Angle Degrees Source 3 neutral current angle
00044FF4 SRC 3 Ig RMS Amps Source 3 ground current RMS
00044FF6 SRC 3 Ig Mag Amps Source 3 ground current magnitude
00044FF8 SRC 3 Ig Angle Degrees Source 3 ground current angle
00044FF9 SRC 3 I_0 Mag Amps Source 3 zero-sequence current magnitude
00044FFB SRC 3 I_0 Angle Degrees Source 3 zero-sequence current angle
00044FFC SRC 3 I_1 Mag Amps Source 3 positive-sequence current magnitude
00044FFE SRC 3 I_1 Angle Degrees Source 3 positive-sequence current angle
00044FFF SRC 3 I_2 Mag Amps Source 3 negative-sequence current magnitude
00045001 SRC 3 I_2 Angle Degrees Source 3 negative-sequence current angle
00045002 SRC 3 Igd Mag Amps Source 3 differential ground current magnitude
00045004 SRC 3 Igd Angle Degrees Source 3 differential ground current angle
00045020 SRC 4 Ia RMS Amps Source 4 phase A current RMS
00045022 SRC 4 Ib RMS Amps Source 4 phase B current RMS
00045024 SRC 4 Ic RMS Amps Source 4 phase C current RMS
00045026 SRC 4 In RMS Amps Source 4 neutral current RMS
00045028 SRC 4 Ia Mag Amps Source 4 phase A current magnitude
0004502A SRC 4 Ia Angle Degrees Source 4 phase A current angle
0004502B SRC 4 Ib Mag Amps Source 4 phase B current magnitude
0004502D SRC 4 Ib Angle Degrees Source 4 phase B current angle
0004502E SRC 4 Ic Mag Amps Source 4 phase C current magnitude
00045030 SRC 4 Ic Angle Degrees Source 4 phase C current angle
00045031 SRC 4 In Mag Amps Source 4 neutral current magnitude
00045033 SRC 4 In Angle Degrees Source 4 neutral current angle
00045034 SRC 4 Ig RMS Amps Source 4 ground current RMS
00045036 SRC 4 Ig Mag Amps Source 4 ground current magnitude
00045038 SRC 4 Ig Angle Degrees Source 4 ground current angle
00045039 SRC 4 I_0 Mag Amps Source 4 zero-sequence current magnitude
0004503B SRC 4 I_0 Angle Degrees Source 4 zero-sequence current angle
0004503C SRC 4 I_1 Mag Amps Source 4 positive-sequence current magnitude
0004503E SRC 4 I_1 Angle Degrees Source 4 positive-sequence current angle
0004503F SRC 4 I_2 Mag Amps Source 4 negative-sequence current magnitude
00045041 SRC 4 I_2 Angle Degrees Source 4 negative-sequence current angle
00045042 SRC 4 Igd Mag Amps Source 4 differential ground current magnitude
00045044 SRC 4 Igd Angle Degrees Source 4 differential ground current angle
00045F7F Active Setting Group --- Current setting group
00046FD1 Tracking Frequency Hz Terminal tracking frequency
00049900 FlexElement 1 Value --- FlexElement 1 actual value
00049902 FlexElement 2 Value --- FlexElement 2 actual value
00049904 FlexElement 3 Value --- FlexElement 3 actual value
00049906 FlexElement 4 Value --- FlexElement 4 actual value
00049908 FlexElement 5 Value --- FlexElement 5 actual value
0004990A FlexElement 6 Value --- FlexElement 6 actual value
0004990C FlexElement 7 Value --- FlexElement 7 actual value
0004990E FlexElement 8 Value --- FlexElement 8 actual value

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-25


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


00049910 FlexElement 9 Value --- FlexElement 9 actual value
A 00049912 FlexElement 10 Value --- FlexElement 10 actual value
00049914 FlexElement 11 Value --- FlexElement 11 actual value
00049916 FlexElement 12 Value --- FlexElement 12 actual value
00049918 FlexElement 13 Value --- FlexElement 13 actual value
0004991A FlexElement 14 Value --- FlexElement 14 actual value
0004991C FlexElement 15 Value --- FlexElement 15 actual value
0004991E FlexElement 16 Value --- FlexElement 16 actual value
0004A0B2 V0 3rd Harmonic 1 Volts VTFF 1 V0 3rd Harmonic
0004A0B4 V0 3rd Harmonic 2 Volts VTFF 2 V0 3rd Harmonic
0004A0B6 V0 3rd Harmonic 3 Volts VTFF 3 V0 3rd Harmonic
0004A0B8 V0 3rd Harmonic 4 Volts VTFF 4 V0 3rd Harmonic
0004B210 RxGOOSE Analog 1 --- RxGOOSE analog input 1
0004B212 RxGOOSE Analog 2 --- RxGOOSE analog input 2
0004B214 RxGOOSE Analog 3 --- RxGOOSE analog input 3
0004B216 RxGOOSE Analog 4 --- RxGOOSE analog input 4
0004B218 RxGOOSE Analog 5 --- RxGOOSE analog input 5
0004B21A RxGOOSE Analog 6 --- RxGOOSE analog input 6
0004B21C RxGOOSE Analog 7 --- RxGOOSE analog input 7
0004B21E RxGOOSE Analog 8 --- RxGOOSE analog input 8
0004B220 RxGOOSE Analog 9 --- RxGOOSE analog input 9
0004B222 RxGOOSE Analog 10 --- RxGOOSE analog input 10
0004B224 RxGOOSE Analog 11 --- RxGOOSE analog input 11
0004B226 RxGOOSE Analog 12 --- RxGOOSE analog input 12
0004B228 RxGOOSE Analog 13 --- RxGOOSE analog input 13
0004B22A RxGOOSE Analog 14 --- RxGOOSE analog input 14
0004B22C RxGOOSE Analog 15 --- RxGOOSE analog input 15
0004B22E RxGOOSE Analog 16 --- RxGOOSE analog input 16
0004B230 RxGOOSE Analog 17 --- RxGOOSE analog input 17
0004B232 RxGOOSE Analog 18 --- RxGOOSE analog input 18
0004B234 RxGOOSE Analog 19 --- RxGOOSE analog input 19
0004B236 RxGOOSE Analog 20 --- RxGOOSE analog input 20
0004B238 RxGOOSE Analog 21 --- RxGOOSE analog input 21
0004B23A RxGOOSE Analog 22 --- RxGOOSE analog input 22
0004B23C RxGOOSE Analog 23 --- RxGOOSE analog input 23
0004B23E RxGOOSE Analog 24 --- RxGOOSE analog input 24
0004B240 RxGOOSE Analog 25 --- RxGOOSE analog input 25
0004B242 RxGOOSE Analog 26 --- RxGOOSE analog input 26
0004B244 RxGOOSE Analog 27 --- RxGOOSE analog input 27
0004B246 RxGOOSE Analog 28 --- RxGOOSE analog input 28
0004B248 RxGOOSE Analog 29 --- RxGOOSE analog input 29
0004B24A RxGOOSE Analog 30 --- RxGOOSE analog input 30
0004B24C RxGOOSE Analog 31 --- RxGOOSE analog input 31
0004B24E RxGOOSE Analog 32 --- RxGOOSE analog input 32
0004D000 Brk 1 Acc Arc Amp A kA2-cyc Breaker 1 Acc arcing amp phase A
0004D002 Brk 1 Acc Arc Amp B kA2-cyc Breaker 1 Acc arcing amp phase B
0004D004 Brk 1 Acc Arc Amp C kA2-cyc Breaker 1 Acc arcing amp phase C

A-26 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX A: FLEXANALOG OPERANDS FLEXANALOG ITEMS

Hex address FlexAnalog name Units Description

A
0004D006 Brk 1 Op Time A ms Breaker 1 operating time phase A
0004D007 Brk 1 Op Time B ms Breaker 1 operating time phase B
0004D008 Brk 1 Op Time C ms Breaker 1 operating time phase C
0004D009 Brk 1 Op Time ms Breaker 1 operating time
0004D00A Brk 1 Arc Amp A kA2-cyc Breaker 1 arcing amp phase A
0004D00C Brk 1 Arc Amp B kA2-cyc Breaker 1 arcing amp phase B
0004D00E Brk 1 Arc Amp C kA2-cyc Breaker 1 arcing amp phase C
0004D010 Brk 1 Amp Max A kA Breaker 1 amp max phase A
0004D012 Brk 1 Amp Max B kA Breaker 1 amp max phase B
0004D014 Brk 1 Amp Max C kA Breaker 1 amp max phase C
0004D016 Brk 2 Acc Arc Amp A kA2-cyc Breaker 2 Acc arcing amp phase A
0004D018 Brk 2 Acc Arc Amp B kA2-cyc Breaker 2 Acc arcing amp phase B
0004D01A Brk 2 Acc Arc Amp C kA2-cyc Breaker 2 Acc arcing amp phase C
0004D01C Brk 2 Op Time A ms Breaker 2 operating time phase A
0004D01D Brk 2 Op Time B ms Breaker 2 operating time phase B
0004D01E Brk 2 Op Time C ms Breaker 2 operating time phase C
0004D01F Brk 2 Op Time ms Breaker 2 operating time
0004D020 Brk 2 Arc Amp A kA2-cyc Breaker 2 arcing amp phase A
0004D022 Brk 2 Arc Amp B kA2-cyc Breaker 2 arcing amp phase B
0004D024 Brk 2 Arc Amp C kA2-cyc Breaker 2 arcing amp phase C
0004D026 Brk 2 Amp Max A kA Breaker 2 amp max phase A
0004D028 Brk 2 Amp Max B kA Breaker 2 amp max phase B
0004D02A Brk 2 Amp Max C kA Breaker 2 amp max phase C
0004D02C Brk 3 Acc Arc Amp A kA2-cyc Breaker 3 Acc arcing amp phase A
0004D02E Brk 3 Acc Arc Amp B kA2-cyc Breaker 3 Acc arcing amp phase B
0004D030 Brk 3 Acc Arc Amp C kA2-cyc Breaker 3 Acc arcing amp phase C
0004D032 Brk 3 Op Time A ms Breaker 3 operating time phase A
0004D033 Brk 3 Op Time B ms Breaker 3 operating time phase B
0004D034 Brk 3 Op Time C ms Breaker 3 operating time phase C
0004D035 Brk 3 Op Time ms Breaker 3 operating time
0004D036 Brk 3 Arc Amp A kA2-cyc Breaker 3 arcing amp phase A
0004D038 Brk 3 Arc Amp B kA2-cyc Breaker 3 arcing amp phase B
0004D03A Brk 3 Arc Amp C kA2-cyc Breaker 3 arcing amp phase C
0004D03C Brk 3 Amp Max A kA Breaker 3 amp max phase A
0004D03E Brk 3 Amp Max B kA Breaker 3 amp max phase B
0004D040 Brk 3 Amp Max C kA Breaker 3 amp max phase C
0004D042 Brk 4 Acc Arc Amp A kA2-cyc Breaker 4 Acc arcing amp phase A
0004D044 Brk 4 Acc Arc Amp B kA2-cyc Breaker 4 Acc arcing amp phase B
0004D046 Brk 4 Acc Arc Amp C kA2-cyc Breaker 4 Acc arcing amp phase C
0004D048 Brk 4 Op Time A ms Breaker 4 operating time phase A
0004D049 Brk 4 Op Time B ms Breaker 4 operating time phase B
0004D04A Brk 4 Op Time C ms Breaker 4 operating time phase C
0004D04B Brk 4 Op Time ms Breaker 4 operating time
0004D04C Brk 4 Arc Amp A kA2-cyc Breaker 4 arcing amp phase A
0004D04E Brk 4 Arc Amp B kA2-cyc Breaker 4 arcing amp phase B
0004D050 Brk 4 Arc Amp C kA2-cyc Breaker 4 arcing amp phase C
0004D052 Brk 4 Amp Max A kA Breaker 4 amp max phase A

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL A-27


FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS

Hex address FlexAnalog name Units Description


0004D054 Brk 4 Amp Max B kA Breaker 4 amp max phase B
A 0004D056 Brk 4 Amp Max C kA Breaker 4 amp max phase C
0004EFFF PMU Num Triggers --- Phasor measurement unit recording number of triggers

A-28 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Appendix B: RADIUS server configuration

RADIUS server configuration

This appendix outlines how to set up a RADIUS server for user authentication.

B.1 RADIUS server configuration


The following procedure is an example of how to set up a simple RADIUS server. You install the RADIUS server software on
a separate computer. In this example, we use FreeRADIUS third-party software.
1. Download and install FreeRADIUS from www.freeradius.org as the RADIUS server. This is a Windows 32-bit installation
that is known to work. If you try another third-party tool and it does not work, use the FreeRADIUS software.
2. Open the radiusd.conf file in the <Path_to_Radius>\etc\raddb folder, locate the "bind_address" field, and enter your
RADIUS server IP address. An example is
bind_address = 10.14.61.122
Text editor software that supports direct editing and saving of UNIX text encodings and line breaks, such as EditPad
Lite, is needed for this editing.
3. In the users.conf file in the <Path_to_Radius>\etc\raddb folder, add the following text to configure a user "Tester" with
an Administrator role.
Tester User-Password == "TesterPw1#"
GE-UR-Role = Administrator
4. In the clients.conf file in the <Path_to_Radius>\etc\raddb folder, add the following text to define the UR as a RADIUS
client, where in this example the client IP address is 10.14.61.132, the shared secret specified here is also configured
on the UR device for successful authentication, and the shortname is a short, optional alias that can be used in place
of the IP address.
client 10.14.61.132 {
secret = Testing!123
shortname = ur1-test
}
Alternatively, you may specify one secret for a network of clients, where in the example below the clients are all within
the 10.14.61.0/24 subnet and the shared secret specified here is also configured on all the UR devices in the subnet for
successful authentication.
client 10.14.61.0/24 {
secret = Testing!123
shortname = net1-test
}
5. In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL B-1


RADIUS SERVER CONFIGURATION APPENDIX B: RADIUS SERVER CONFIGURATION

# ##########################################################
# GE VSAs
############################################################

VENDOR GE 2910

# Management authorization
BEGIN-VENDOR GE

B # Role ID
ATTRIBUTE GE-UR-Role 1 integer

# GE-UR-ROLE values
VALUE GE-UR-Role Administrator 1
VALUE GE-UR-Role Supervisor 2
VALUE GE-UR-Role Engineer 3
VALUE GE-UR-Role Operator 4
VALUE GE-UR-Role Observer 5

END-VENDOR GE
#############################################################
6. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
For example, the file can look like the following:
$INCLUDE ../share/freeradius/dictionary
$INCLUDE dictionary.ge
7. For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors.
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS parameters on the UR as follows.
8.1. If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default
password is "ChangeMe1#".
8.2. Access Settings > Product Setup > Security. Configure the IP address (10.14.61.122 in this example) and ports
(default values in this example) for the RADIUS server. Leave the GE vendor ID field at the default of 2910.
Update the RADIUS shared secret (Testing!123 in this example) as specified in the clients.conf file. Restart the
relay for the IP address and port changes to take effect.
9. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "TesterPw1#"). Check that the RADIUS
server log file shows the access with an "Access-Accept" entry.

B-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Appendix C: Command line interface

Command line interface

This appendix outlines command line access to the software.

C.1 Command line interface


SetupCLI is a command line interface to communicate with the EnerVista UR Setup software. Commands can be sent from
a DOS prompt or a Windows batch file.
The interface is installed with the EnerVista software. Its default location is similar to
C:\Program Files\EnerVista\Tools\SetupCLI
The EnerVista software needs to be installed on a computer to run the command line interface. The command line
interface does not provide a remote connection to a computer running the EnerVista software.
Items to note are as follows:
• Works with EnerVista UR Setup version 6.10 and later
• Available in English only
• The graphical user interface of the software is not available concurrently with the command line interface
• It does not support concurrent commands
• It has limited functionality with CyberSentry
• It does not interface with UR Engineer
• It does not work when EnerVista UR Setup security is enabled, meaning when login is required
Command syntax is as follows:
• Options enclosed in [ ] are optional
• Values enclosed in < > are replaced with your own values
• <Application> is replaced with the EnerVista software to receive the command. Use "URPC" for EnerVista UR Setup.
• <device> is the UR device name, as displayed in the Device Name field of the Device Setup window and listed in the
Online Window. Use quotes with spaces, such as "B30 Belfort".
• "-s" can be used with any command to suppress error messages
• All commands, their return codes, and error description are logged in the file
C:\ProgramData\EnerVista\Tools\SetupCLI\SetupCLI.log
• When the Supervisor account is enabled, the LOCK SETTINGS setting must be disabled (default) before the putsettings,
inservice, or reboot command can be used. This setting cannot be changed using the command line interface.
• Use quotes ("") to enclose any parameter containing a space

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL C-1


COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE

• Commands, options, and parameters are case sensitive


• All commands have a return code of 0-255. 0 indicates success and 1-255 indicate different errors
• If SetupCLI is automated (in a batch file), make sure that only a single batch is running at a time. SetupCLI does not
support concurrent operations.

To run the command line interface:


1. In Windows, click the Start button, enter cmd, and press the Enter key. After prompting for permission, the Windows
command window opens.
2. Enter SetupCLI followed by the action to execute. An example of use is to enter "SetupCLI -h" to display help,
specifically the commands and explanations outlined here.
Figure C-1: Command line interface run in the command window
C

SetupCLI -h
Display help.
It displays the content outline here.

SetupCLI <Application> start [-c] [-s]


Launch application with name <Application>.
To start in client mode, which is the graphical user interface, include option '-c'. Before use, the software must be idle
without any windows open. Any activity or open windows can cause unexpected behavior. When in client mode, do not
use Launchpad's Site Management feature.
To suppress errors, include option -s.
Example: SetupCLI URPC start -c

SetupCLI <Application> exit [-s]


Exit application with name <Application>.
Example: SetupCLI URPC exit

SetupCLI <Application> login -d <device> [-A <authentication type>] [-a <account>] -w <password> [-s]
Authenticate with device <device> using password <password>.
For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to
"traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is
used.
Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1

C-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX C: COMMAND LINE INTERFACE COMMAND LINE INTERFACE

Example of a batch file that checks for an error (this batch file uses standard batch file operations to check the return
code (ERRORLEVEL) and jump to an error handler):
SetupCLI URPC start
SetupCLI URPC login -d demoDevice -a SETTINGS -w WrongPassword -A traditional
IF NOT ERRORLEVEL 0 GOTO FAILED
SetupCLI URPC putsettings -d demoDevice -f "example file.urs"
SetupCLI URPC inservice -d demoDevice
SetupCLI URPC reboot -d demoDevice
SetupCLI URPC exit
exit

:FAILED
echo Please try again C
exit

For CyberSentry devices with local authentication — Set <authentication type> to "local". Set <account> to
"Supervisor", "Administrator", "Engineer", "Operator", or "Observer".
For CyberSentry devices with RADIUS authentication — Set <authentication type> to "radius". Set <account> to the
user's account on the RADIUS server.

SetupCLI <Application> logout -d <device> [-s]


Log out of device <device>.
Example: SetupCLI URPC logout -d C30

SetupCLI <Application> getsettings -d <device> -f <File> [-s]


Read settings from device <device> and save them to the .urs file <File>. The <File> must not already exist. The default
path to the output file is C:\Users\Public\Public Documents\GE Power Management\URPC\Data
Example: SetupCLI URPC getsettings -d C30 -f "C30 Markham.urs"
Example of a batch file to retrieve a settings file:
SetupCLI URPC start
SetupCLI URPC getsettings -d demoDevice -f C:\example.urs
SetupCLI URPC exit
Example of a batch file to retrieve a settings file from a relay that requires RADIUS authentication:
SetupCLI URPC start
SetupCLI URPC login -d demoDevice -a %1 -w %2 -A radius
SetupCLI URPC getsettings -d demoDevice -f "example file.urs"
SetupCLI URPC logout -d demoDevice
SetupCLI URPC exit
Although a user name and password could have been entered in this batch file, it would have created a security risk.
Batch files allow you to pass in runtime parameters and refer to them in your script as %1, %2, and so on. For example,
if this file is called example.bat, one calls it as follows: "example.bat MyUserName MyPassword"

SetupCLI <Application> putsettings -d <device> -f <File> [-s]


Write the settings file <File> to the device <device>.
For CyberSentry devices, putsettings is only supported for users with the "Administrator" role.
Example: SetupCLI URPC putsettings -d C30 -f "C30 Markham.urs"

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL C-3


COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE

SetupCLI <Application> compare -f <File1> -r <File2> -o <OutputFile> [-s]


Compare settings files <File1> and <File2>, and save output to <OutputFile>.
Example: SetupCLI URPC compare -f may.urs -r september.urs -o compared.txt
Batch file example that retrieves a settings file, compares it with an existing settings file, and opens the resulting
comparison file:
SetupCLI URPC start
SetupCLI URPC getsettings -d demoDevice -f devicefile.urs
SetupCLI URPC compare -f existingfile.urs -r devicefile.urs -o output.txt

The output is similar to the following:


Comparing settings file aaa.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ with bbb.urs
: C:\Users\Public\Public Documents\GE Power Management\URPC\Data\
C
# Setting Name (Group,Module,Item) Value

1 + Default Message Timeout (1,1,1) = 299 s


2 - Default Message Timeout (1,1,1) = 300 s
3 + Flash Message Time (1,1,1) = 0.9 s
4 - Flash Message Time (1,1,1) = 1.0 s

SetupCLI <Application> inservice -d <device> [-n] [-s]


Put the device in service. Include option -n to take the device out of service.
Example: SetupCLI URPC inservice -d C30

SetupCLI <Application> reboot -d <device> [-s]


Reboot the relay <device>. This is necessary after changing IEC 61850 settings and aggregator source settings.
Example: SetupCLI URPC reboot -d "C30_Instanbul"

SetupCLI <Application> adddevice -I <IP Address> -S <Slave Address> -P <Modbus Port>


Connect to a device using its IP address, slave address, and Modbus port. Show the device in the EnerVista interface
under the SetupCLI Site as DEV@SETUP_CLI.
EnerVista UR Setup 7.30 or higher supports this command.
Figure C-2: Device added using IP address

The device is named as DEV@SETUP_CLI, which is used as the device name required by the <device> parameter of other
SetupCLI commands.

C-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX C: COMMAND LINE INTERFACE COMMAND LINE INTERFACE

The device name DEV@SETUP_CLI is always assigned to the device that is connected most recently by performing
'adddevice' command. It means that the Application only keeps up to one device named as DEV@SETUP_CLI, the
'adddevice' command disconnects/deletes the device DEV@SETUP _CLI that was connected previously by performing
'adddevice' command.
The device name DEV@SETUP_CLI is never used to configure/connect to a device through the graphical user interface.
Example of a batch file using a device IP address to retrieve its settings file:
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f C:\example.urs
SetupCLI URPC exit
After connecting the device using IP address, the device name DEV@SETUP_CLI is used to identify this device in
'getsettings' command.
Example of a batch file using a device IP address to retrieve a settings file when RADIUS authentication is required: C
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC login -d DEV@SETUP_CLI -a %1 -w %2 -A radius
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs"
SetupCLI URPC logout -d DEV@SETUP_CLI
SetupCLI URPC exit
DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command.

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL C-5


COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE

C-6 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Appendix D: Miscellaneous

Miscellaneous

This chapter provides the warranty, revision history, and open source information.

D.1 Warranty
For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years.
For warranty details including any limitations and disclaimers, see the Terms and Conditions at
http://www.gegridsolutions.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.

D.2 Revision history


The tables outline the releases and revision history of this document.
Table D-1: Revision history (English)
Manual P/N F60 revision Release date ECO
1601-0093-A1 1.5x 23 March 1999 N/A
1601-0093-A2 1.6x 10 August 1999 URF-012
1601-0093-A3 1.8x 29 October 1999 URF-014
1601-0093-A4 1.8x 15 November 1999 URF-015
1601-0093-A5 2.0x 17 December 1999 URF-016
1601-0093-A6 2.2x 12 May 2000 URF-017
1601-0093-A7 2.2x 14 June 2000 URF-020
1601-0093-A7a 2.2x 28 June 2000 URF-020a
1601-0093-B1 2.4x 08 September 2000 URF-022
1601-0093-B2 2.4x 03 November 2000 URF-024
1601-0093-B3 2.6x 09 March 2001 URF-025
1601-0093-B4 2.8x 28 September 2001 URF-027
1601-0093-B5 2.9x 03 December 2001 URF-030
1601-0093-B6 2.6x 27 February 2004 URX-120
1601-0093-C1 3.0x 02 July 2002 URF-032

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL D-1


REVISION HISTORY APPENDIX D: MISCELLANEOUS

Manual P/N F60 revision Release date ECO


1601-0093-C2 3.1x 30 August 2002 URF-034
1601-0093-C3 3.0x 18 November 2002 URF-036
1601-0093-C4 3.1x 18 November 2002 URF-038
1601-0093-C5 3.0x 11 February 2003 URF-040
1601-0093-C6 3.1x 11 February 2003 URF-042
1601-0093-D1 3.2x 11 February 2003 URF-044
1601-0093-D2 3.2x 02 June 2003 URX-084
1601-0093-E1 3.3x 01 May 2003 URX-080
1601-0093-E2 3.3x 29 May 2003 URX-083
1601-0093-F1 3.4x 10 December 2003 URX-111
1601-0093-F2 3.4x 09 February 2004 URX-115
1601-0093-G1 4.0x 23 March 2004 URX-123
1601-0093-G2 4.0x 17 May 2004 URX-136
1601-0093-H1 4.2x 30 June 2004 URX-145
1601-0093-H2 4.2x 23 July 2004 URX-151

D 1601-0093-J1
1601-0093-K1
4.4x
4.6x
15 September 2004
15 February 2005
URX-156
URX-176
1601-0093-L1 4.8x 05 August 2005 URX-202
1601-0093-M1 4.9x 15 December 2005 URX-208
1601-0093-M2 4.9x 27 February 2006 URX-214
1601-0093-N1 5.0x 31 March 2006 URX-217
1601-0093-N2 5.0x 26 May 2006 URX-220
1601-0093-P1 5.2x 23 October 2006 URX-230
1601-0093-P2 5.2x 24 January 2007 URX-232
1601-0093-R1 5.4x 26 June 2007 URX-242
1601-0093-R2 5.4x 31 August 2007 URX-246
1601-0093-R3 5.4x 17 October 2007 URX-251
1601-0093-S1 5.5x 7 December 2007 URX-253
1601-0093-S2 5.5x 22 February 2008 URX-258
1601-0093-S3 5.5x 12 March 2008 URX-260
1601-0093-T1 5.6x 27 June 2008 08-0390
1601-0093-U1 5.7x 29 May 2009 09-0938
1601-0093-U2 5.7x 30 September 2009 09-1165
1601-0093-V1 5.8x 29 May 2010 09-1457
1601-0093-V2 5.8x 04 January 2011 11-2237
1601-0093-W1 5.9x 12 January 2011 11-2227
1601-0093-X1 6.0x 21 December 2011 11-2840
1601-0093-X2 6.0x 5 April 2012 12-3254
1601-0093-Y1 7.0x 30 September 2012 12-3529
1601-0093-Y2 7.0x 11 November 2012 12-3601
1601-0093-Z1 7.1x 30 March 2013 13-0126
1601-0093-AA1 7.2x 1 August 2013 13-0401
1601-0093-AB1 7.3x 7 November 2014 14-1408
1601-0093-AB2 7.3x 1 September 2015 15-2215
1601-0093-AC1 7.40x 8 December 2016 16-3319
1601-0093-AE1 7.41x 31 January 2017 17-3427
1601-0093-AE3 7.4x 28 April 2017 17-3561

D-2 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


APPENDIX D: MISCELLANEOUS OPEN SOURCE LICENSES

Manual P/N F60 revision Release date ECO


1601-0093-AF1 7.6x 30 June 2017 17-3779
1601-0093-AF2 7.6x 31 October 2017 17-3935
1601-0093-AG1 7.7x 31 March 2018 18-4430
1601-0093-AG2 7.7x 4 May 2018 18-4517
1601-0093-AH1 7.8x 17 December 2018 18-4703
1601-0093-AI1 7.9x 24 October 2019 19-5181
1601-0093-AJ1 8.0x 30 October 2019 19-5182
1601-0093-AJ2 8.0x 12 June 2020 20-5580
1601-0093-AK1 8.1x 20 November 2020 20-6096
1601-0093-AL1 8.2x 16 February 2021 21-6228
1601-0093-AL2 8.2x 23 July 2021 21-6482
1601-0093-AM1 8.3x 6 May 2022 22-6815
1601-0093-AM2 8.3x 14 October 2022 22-7224

D.2.1 Major changes


For information on the updates included in this release of the F60 Feeder Protection System manual, please refer to the
latest release notes for the UR F60 8.3x version online.
D

D.3 Open source licenses


The optional IEC 61850-9-2LE/IEC 61869 Process Bus Modules include open source code. See the UR-OpenSourceLicense
folder installed at the root level with the software, such as at C:\Program Files (x86)\GE Power Management\URPC\

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL D-3


OPEN SOURCE LICENSES APPENDIX D: MISCELLANEOUS

D-4 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


Glossary

F60 Feeder Protection System

Abbreviations

CONN Connection
Abbreviations

A Ampere
AC Alternating Current CONT Continuous, Contact
A/D Analog to Digital CO-ORD Coordination
AE Accidental Energization, Application Entity CPU Central Processing Unit
AMP Ampere CRC Cyclic Redundancy Code/Check
ANG Angle CRL Certificate Revocation List
ANSI American National Standards Institute CRT, CRNT Current
APDU Application Protocol Data Unit CSA Canadian Standards Association
AR Automatic Reclosure CT Current Transformer
ARP Address Resolution Protocol CVT Capacitive Voltage Transformer
ASDU Application-layer Service Data Unit
ASYM Asymmetry D/A Digital to Analog
AUTO Automatic DA Data Attribute
AUX Auxiliary DANH Doubly Attached Node with HSR
AVG Average DANP Doubly Attached Node with DANP
AWG American Wire Gauge DC (dc) Direct Current
DCE Data Communications Equipment
BCD Binary-Coded Decimal DCS Distributed Control System
BCS Best Clock Selector DD Disturbance Detector
BER Bit Error Rate DFLT Default
BF Breaker Fail DGNST Diagnostics
BFI Breaker Failure Initiate DIFF Differential
BKR Breaker DIR Directional
BLK Block DISCREP Discrepancy
BLKG Blocking DIST Distance
BNC Bayonet Neill-Concelman DMD Demand
BPNT Breakpoint of a characteristic DNP Distributed Network Protocol
BRKR Breaker DPO Dropout
DPS Double-Point Status
CA Certificate Authority DSP Digital Signal Processor
CAP Capacitor DST Daylight Savings Time
CC Coupling Capacitor dt Rate of Change
CCVT Coupling Capacitor Voltage Transformer DTT Direct Transfer Trip
CFG Configure / Configurable DUTT Direct Under-reaching Transfer Trip
.CFG Filename extension for oscillography files
CHK Check EAD Expert Arc Detector
CHNL Channel EGD Ethernet Global Data
CID Configured IED Description ENCRMNT Encroachment
CLS Close EPRI Electric Power Research Institute
CLSD Closed .EVT Filename extension for event recorder files
CMND Command EXT Extension, External
CMPRSN Comparison
CO Contact Output F Field
COM Communication FAIL Failure
COMM Communications FCDA Functional Constraint Data Attributes
COMP Compensated, Comparison FD Fault Detector
ConfRev Configuration Revision FDH Fault Detector high-set
FDL Fault Detector low-set

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL i


ABBREVIATIONS

FIR Finite Impulse Response LDBN Bias Neutral Level Detector


FLA Full Load Current LED Light Emitting Diode
FO Fiber Optic LEO Line End Open
FPGA Field-programmable Gate Array LFT BLD Left Blinder
FREQ Frequency LOOP Loopback
FSK Frequency-Shift Keying LPU Line Pickup
FTP File Transfer Protocol LRA Locked-Rotor Current
FxE FlexElement™ LTC Load Tap-Changer
FWD Forward LV Low Voltage

G Generator M Machine
GCM Galois Counter Mode M2M Machine to Machine
GDOI Group Domain of Interpretation mA MilliAmpere
GE General Electric MAG Magnitude
GFP Graphical Front Panel MAN Manual / Manually
GIS Gas Insulated Switchgear MAX Maximum
GND Ground Mb Megabit
GNTR Generator MIC Model Implementation Conformance
GoCB GOOSE Control Block MIN Minimum, Minutes
GOOSE General Object Oriented Substation Event MMI Man Machine Interface
GPS Global Positioning System MMS Manufacturing Message Specification
GSU Generator Step-Up MRT Minimum Response Time
MSG Message
HARM Harmonic / Harmonics MTA Maximum Torque Angle
HCT High Current Time MTR Motor
HGF High-Impedance Ground Fault (CT) MU Merging Unit
HIZ High-Impedance and Arcing Ground MVA MegaVolt-Ampere (total 3-phase)
HMI Human-Machine Interface MVA_A MegaVolt-Ampere (phase A)
HSR High-availability Seamless Redundancy MVA_B MegaVolt-Ampere (phase B)
HTTP Hyper Text Transfer Protocol MVA_C MegaVolt-Ampere (phase C)
HV High Voltage MVAR MegaVar (total 3-phase)
HYB Hybrid MVAR_A MegaVar (phase A)
Hz Hertz MVAR_B MegaVar (phase B)
MVAR_C MegaVar (phase C)
I Instantaneous MVARH MegaVar-Hour
I_0 Zero Sequence current MW MegaWatt (total 3-phase)
I_1 Positive Sequence current MW_A MegaWatt (phase A)
I_2 Negative Sequence current MW_B MegaWatt (phase B)
IA Phase A current MW_C MegaWatt (phase C)
IAB Phase A minus B current MWH MegaWatt-Hour
IB Phase B current
IBC Phase B minus C current N Neutral
IC Phase C current N/A, n/a Not Applicable
ICA Phase C minus A current NCIT Non-conventional instrument transformer
ICD IED Capability Description NEG Negative
ID Identification NMPLT Nameplate
IED Intelligent Electronic Device NOM Nominal
IEC International Electrotechnical Commission NTR Neutral
IEEE Institute of Electrical and Electronic Engineers
IG Ground (not residual) current O Over
Igd Differential Ground current OC, O/C Overcurrent
IGMP Internet Group Management Protocol OCSP Online Certificate Status Protocol
IID Instantiated IED Capability Description OF Overload Factor
IN CT Residual Current (3I0) or Input O/P, Op Output
INC SEQ Incomplete Sequence OP Operate
INIT Initiate OPER Operate
INST Instantaneous OPERATG Operating
INV Inverse O/S Operating System
I/O Input/Output OSI Open Systems Interconnect
IOC Instantaneous Overcurrent OSB Out-of-Step Blocking
IOV Instantaneous Overvoltage OUT Output
IRC Inter-Relay Communication OV Overvoltage
IRIG Inter-Range Instrumentation Group OVERFREQ Overfrequency
ISO International Standards Organization OVLD Overload
IUV Instantaneous Undervoltage
P Phase
K0 Zero Sequence Current Compensation PB Process Bus
kA kiloAmpere PBM Process Bus Module
KDC Key Distribution Center PC Phase Comparison, Personal Computer
kV kiloVolt PCNT Percent
PF Power Factor (total 3-phase)
LCD Liquid Crystal Display PF_A Power Factor (phase A)

ii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


ABBREVIATIONS

PF_B Power Factor (phase B) SSB Single Side Band


PF_C Power Factor (phase C) SSEL Session Selector
PFLL Phase and Frequency Lock Loop STATS Statistics
PHS Phase SUPN Supervision
PICS Protocol Implementation & Conformance SUPV Supervise / Supervision
Statement SV Supervision, Service, Sampled Value
PKI Public Key Infrastructure SYNC Synchrocheck
PKP Pickup SYNCHCHK Synchrocheck
PLC Power Line Carrier
POS Positive T Time, transformer
POTT Permissive Over-reaching Transfer Trip TC Thermal Capacity
PP Power Profile TCP Transmission Control Protocol
PPP Point-to-Point TCU Thermal Capacity Used
PPS Pulse per Second TD MULT Time Dial Multiplier
PRESS Pressure TEMP Temperature
PRI Primary TFTP Trivial File Transfer Protocol
PROT Protection TGFD Transient Ground Fault Detection
PRP Parallel Redundancy Protocol THD Total Harmonic Distortion
PSEL Presentation Selector TMR Timer
PTP Precision Time Protocol TOC Time Overcurrent
pu Per Unit TOV Time Overvoltage
PUIB Pickup Current Block TRANS Transient
PUIT Pickup Current Trip TRANSF Transfer
PUSHBTN Pushbutton TSEL Transport Selector
PUTT Permissive Under-reaching Transfer Trip TUC Time Undercurrent
PWM Pulse Width Modulated TUV Time Undervoltage
PWR Power TX (Tx) Transmit, Transmitter

QUAD Quadrilateral U Under


UC Undercurrent
R Rate, Reverse UCA Utility Communications Architecture
RA Registration Authority UDP User Datagram Protocol
RCA Reach Characteristic Angle UL Underwriters Laboratories
RedBox Redundancy Box UNBAL Unbalance
REF Reference UR Universal Relay
REM Remote URC Universal Recloser Control
REV Reverse .URS Filename extension for settings files
R-GOOSE Routable GOOSE UV Undervoltage
RI Reclose Initiate
RIP Reclose In Progress V/Hz Volts per hertz
RGT BLD Right Blinder V_0 Zero Sequence voltage
RMA Return Materials Authorization V_1 Positive Sequence voltage
RMS Root Mean Square V_2 Negative Sequence voltage
ROCOF Rate of Change of Frequency VA Phase A voltage
ROD Remote Open Detector VAB Phase A to B voltage
RRTD Remote Resistance Temperature Detector VAG Phase A to Ground voltage
RST Reset VARH Var-hour voltage
RSTR Restrained VB Phase B voltage
RTD Resistance Temperature Detector VBA Phase B to A voltage
RTU Remote Terminal Unit VBG Phase B to Ground voltage
RX (Rx) Receive, Receiver VC Phase C voltage
VCA Phase C to A voltage
s second VCG Phase C to Ground voltage
S Sensitive VF Variable Frequency
SAN Singly Attached Node VIBR Vibration
SAT CT Saturation VT Voltage Transformer
SBO Select Before Operate VTFF Voltage Transformer Fuse Failure
SCADA Supervisory Control and Data Acquisition VTLOS Voltage Transformer Loss Of Signal
SCC Serial Communication Controller
SCD System Configuration Description WDG Winding
SCL Substation Configuration Language WH Watt-hour
SCEP Simple Certificate Enrollment Protocol w/ opt With Option
SEC Secondary WGS World Geodetic System
SEL Select / Selector / Selection WRT With Respect To
SENS Sensitive
SEQ Sequence X Reactance
SFTP Secure Shell (SSH) File Transfer Protocol, Secure XDUCER Transducer
File Transfer Protocol XFMR Transformer
SIR Source Impedance Ratio
SmpSynch Samples Synchronized Z Impedance, Zone
SNTP Simple Network Time Protocol
SRC Source

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL iii


ABBREVIATIONS

iv F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


F60 Feeder Protection System

Index

Index

Administrator
Symbols add user account ............................................................................. 5-15
........................................................................................................................5-75 command to force logoff ................................................................7-6
no automatic logout from front panel ................................... 5-22
role for CyberSentry ...........................................................................2-4
Aggregator
Numerics actual values ...................................................................................... 6-28
10BASE-F settings ...............................................................................5-47 error message ......................................................................................7-9
4L Discrepancy message ................................................................7-10 settings ...............................................................................................5-207
7R module ................................................................................................3-45 Alarm LEDs ............................................................................................5-137
7S module ................................................................................................3-44 Alarms
acknowledge .............................................................................4-35, 6-4
add .............................................................................................. 4-36, 5-38
A messages ................................................................................................7-8
AC Bank assigned is not configured ......................................5-231 overview ............................................................................................... 4-33
AC current inputs reset ...............................................................................................4-35, 6-4
explained ..............................................................................................3-18 AND gate explained ........................................................................... 4-85
settings ...............................................................................................5-159 Annunciator editor ............................................................................. 4-36
specifications ......................................................................................2-30 ANSI device numbers ...........................................................................2-2
AC voltage input specifications ...................................................2-30 Apparent power
Accents ......................................................................................................4-57 actual values ...................................................................................... 6-21
Access Violation message ..............................................................3-72 specifications ..................................................................................... 2-29
Acknowledge alarm ............................................................................. 6-4 Application examples
Activate relay .........................................................................................3-57 breaker trip circuit integrity .......................................................5-359
Active setting group ........................................................................5-260 contact inputs ..................................................................................5-402
Actual values ............................................................................................ 6-1 direct inputs and outputs ...........................................................5-409
alarms for graphical front panel ................................................. 6-4 latching outputs ..............................................................................5-405
display on graphical front panel ...................................4-36, 4-37 sensitive directional power .......................................................5-328
monitor with Modbus Analyzer ..................................................10-1 Apply settings to other device ..................................................... 10-7
not activated graphical front panel .........................................4-54 Approvals ................................................................................................. 2-40
Add Device from File option Arc Burst Pattern Analysis algorithm for Hi-Z .......................9-4
restore settings to online device ............................................10-12 Architecture, relay ............................................................................5-232
save to Offline Window ..................................................................3-80 Arcing current .....................................................................................5-368
Add Device to Offline Window preferences ......................10-10 Arcing Suspected algorithm for Hi-Z ..........................................9-4
Add module, check settings not defaulted ........................10-18 Audit list of port numbers ............................................................... 5-47
Add relay ...................................................................................................3-62 Authentication by device or server ........................................... 5-17
Automatic discovery of UR devices .......................................... 3-71

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL i


INDEX

Autoreclose Baud rate ................................................................................................. 5-44


actual values ......................................................................................... 6-8 Blinking alarm ....................................................................................... 4-35
FlexLogic operands .......................................................................5-235 Block setting ..............................................................................................5-5
logic diagram ...................................................................................5-354 Blocking scheme
settings ...............................................................................................5-351 FlexLogic operands ...................................................................... 5-237
single shot sequence ...................................................................5-356 Bootloader upgrade ....................................................................... 10-15
specifications ..................................................................................... 2-25 Breaker arcing current
Auxiliary overvoltage actual values ...................................................................................... 6-37
FlexLogic operands .......................................................................5-235 clearing ........................................................................................5-43, 7-2
logic ......................................................................................................5-327 FlexAnalogs .........................................................................................A-26
settings ...............................................................................................5-326 FlexLogic operands ...................................................................... 5-236
specifications ..................................................................................... 2-23 logic diagram .................................................................................. 5-371
Auxiliary undervoltage measurement ................................................................................. 5-370
FlexLogic operands .......................................................................5-236 settings ............................................................................................... 5-368
logic diagram ...................................................................................5-326 specifications ..................................................................................... 2-24
settings ...............................................................................................5-324 Breaker control
specifications ..................................................................................... 2-22 control of two breakers ................................................................. 4-60
Auxiliary voltage channel ............................................................... 3-18 dual breaker logic ......................................................................... 5-172
Auxiliary voltage metering ............................................................ 6-21 FlexLogic operands ...................................................................... 5-237
AWG wire size ....................................................................................... 3-51 settings ............................................................................................... 5-166
CT/VT ...................................................................................................... 3-18 with IEC 61850 ................................................................................... 5-98
F485 converter .................................................................................. 3-59 Breaker failure
G.703 interface .................................................................................. 3-44 description ........................................................................................ 5-309
module 7S ........................................................................................... 3-44 FlexLogic operands ...................................................................... 5-236
modules 6X, 6W ................................................................................ 3-23 logic diagram ....................................................................5-313, 5-314
modules 7E, 7F, 7G, 7Q, 75 .......................................................... 3-51 settings ............................................................................................... 5-308
modules 7L, 7M, 7N, 7P, 74 ......................................................... 3-50 specifications ..................................................................................... 2-24
modules 7T, 7W ................................................................................ 3-48 Breaker flashover
RS422 and fiber interface ............................................................ 3-50 FlexLogic operands ...................................................................... 5-236
logic diagram .................................................................................. 5-376
settings ............................................................................................... 5-372
B specifications ..................................................................................... 2-24
Back up settings ...................................................................... 5-63, 10-9 Breaker restrike
Bad IRIG-B Signal message .......................................................... 7-10 FlexLogic operands ...................................................................... 5-236
Bad PTP Signal message ................................................................ 7-10 logic diagram .................................................................................. 5-379
settings ............................................................................................... 5-377
Banks ............................................................................................. 5-7, 5-159
specifications ..................................................................................... 2-25
Basic front panel
Breaker-and-a-half scheme ............................................................5-6
dimensions ............................................................................................. 3-2
FlexLogic ............................................................................................5-235
Brick
interface module described ........................................................ 3-20
interface ............................................................................................... 4-16
remote resources actual values ............................................... 6-29
IP rating ................................................................................................ 2-38
remote resources settings ........................................................ 5-158
keypad .................................................................................................. 4-39
self-test errors ................................................................................... 7-15
labels ...................................................................................................... 4-49
Trouble message .............................................................................. 7-16
LEDs ..........................................................................................4-41, 5-137
navigation ........................................................................................... 4-51 Brightness ................................................................................................ 5-28
order code over two lines ............................................................ 4-39 Broken conductor
order codes ............................................................................................ 2-7 FlexLogic operands ...................................................................... 5-237
pushbuttons .....................................................................................5-141 settings ............................................................................................... 5-389
specifications ..................................................................................... 2-27
use, change setting ......................................................................... 4-53
Battery C
disposal ..............................................................................................10-20 C37.94 communications ..................................................... 3-52, 3-55
monitor with annunciator alarm .............................................. 4-36 Cannot log in .............................................................................................2-4
monitor with Engineer ................................................................... 4-77 Caution symbol in Offline Window ............................................ 4-71
monitor with FlexLogic ................................................................5-246 CE certification ...................................................................................... 2-40
monitor with metering window ................................................. 4-37 Certification ............................................................................................ 2-40
monitor with self-test alarm .....................................................5-139 Changes ...................................................................................................... D-1
replace ................................................................................................10-19

ii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Channel Communications
banks ...................................................................................................5-159 10BASE-F .............................................................................................. 5-47
tests .........................................................................................................6-12 connecting to the UR .......................................................... 3-69, 3-72
Check Settings message ................................................................... 7-9 DNP ......................................................................................................... 5-56
Chinese limited to 10 character input .....................................5-28 EGD .......................................................................................................5-111
CID file, SCD file .....................................................................................5-82 HTTP .....................................................................................................5-108
CID files IEC 60870-5-10 ...............................................................................5-112
create .....................................................................................................5-63 IEC 60870-5-104 .............................................................................5-109
explained ..............................................................................................3-80 inter-relay specifications .............................................................. 2-36
import ......................................................................................3-80, 10-13 Modbus registers ............................................................................5-117
import preferences .......................................................................10-10 Modbus settings ............................................................................... 5-53
view .........................................................................................................5-63 modem .................................................................................................. 3-70
Circuit monitoring applications ................................................5-358 Protocol selection ..................................................5-54, 5-55, 10-13
Cleaning ....................................................................................................2-40 RS232 ......................................................................................... 3-35, 5-44
Clear RS485 ......................................................................................... 3-38, 5-44
files and records .............................................................................10-23 settings ..................................................................................... 5-47, 5-56
LEDs .....................................................................................................5-407 specifications ......................................................................... 2-35, 2-36
relay records using IEC 61850 .................................................5-103 web server .........................................................................................5-108
relay records using settings ........................................................5-43 Compare settings ................................................................................ 10-8
security logs .......................................................................................... 7-6 Comparison Report button ............................................................ 3-79
Clock Compliance ............................................................................................. 2-40
graphical front panel format .......................................................5-32 COMTRADE files, view ....................................................................... 4-82
IRIG-B ......................................................................................................3-39 Conducted RFI specifications ....................................................... 2-39
PTP ........................................................................................................5-120 Connect, unable to ................................................................. 3-72, 5-48
set .............................................................................................................. 7-3 Connectors, LC and ST ..................................................................... 3-13
settings .................................................................... 5-118, 5-124, 6-32 Contact inputs
settings with Process Bus Module .............. 5-124, 5-214, 6-32 actual values .........................................................................................6-5
synchronize several devices .....................................................5-120 FlexLogic operands .......................................................................5-243
Close settings ...............................................................................................5-400
HTTP port ...........................................................................................5-108 specifications ..................................................................................... 2-31
IEC 60870-5-104 port ..................................................................5-110 thresholds ..........................................................................................5-400
Modbus port ........................................................................................5-53 wet and dry connections .............................................................. 3-28
TFTP port ............................................................................................5-109 Contact outputs
Web access port ............................................................................5-108 actual values .........................................................................................6-7
Cold load pickup explained ............................................................................................5-403
explained ...........................................................................................5-393 FlexLogic operands .......................................................................5-243
FlexLogic operands .......................................................................5-237 settings ...............................................................................................5-403
logic diagram ...................................................................................5-395 Control elements ...............................................................................5-330
settings ...............................................................................................5-393 Control power
COMM Path Incomplete message .................................7-10, 7-12 description ........................................................................................... 3-16
Comm status remaining connections .....................................6-13 specifications ..................................................................................... 2-34
Command line interface to software ......................................... C-1 Control pushbuttons
Command password .................................................4-61, 5-10, 5-11 FlexLogic operands .......................................................................5-235
Commands logic diagram ...................................................................................5-141
control user accounts .....................................................................5-15 settings ...............................................................................................5-140
menu ......................................................................................................... 7-1 specifications ..................................................................................... 2-27
with IEC 61850 ................................................................................5-103 Convert device settings ................................................................... 10-5
Commissioning ....................................................................................... 8-1 Copper SFP cable length ................................................................. 3-11
Copy of Copy of .................................................................................... 10-7
Copy settings for upgrading ......................................................... 10-5
Copy settings to other device ...................................................... 10-7
Counters
actual values .........................................................................................6-8
settings ...............................................................................................5-360
CPU module diagram ....................................................................... 3-12
CPU wiring ............................................................................................... 3-36
CRC alarm ..............................................................................................5-155
Create device folders prompt ....................................................10-14

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL iii


INDEX

Critical failure relay specifications ............................................ 2-33 DCmA inputs .......................................................................................... 6-29
CSA certification .................................................................................. 2-40 actual values ...................................................................................... 6-29
CT bank settings ................................................................................5-159 FlexAnalogs .........................................................................................A-22
CT failure settings ............................................................................................... 5-414
FlexLogic operands .......................................................................5-237 specifications ..................................................................................... 2-31
logic diagram ...................................................................................5-381 DCmA outputs
settings ...............................................................................................5-379 description ........................................................................................... 3-33
CT inputs .......................................................................... 3-17, 5-7, 5-159 settings ............................................................................................... 5-416
CT wiring .................................................................................................. 3-18 specifications ..................................................................................... 2-34
Current bank ........................................................................................5-159 Decommission ................................................................................... 10-23
Current demand ................................................................................5-133 Default password ................................................................................ 5-15
Current harmonics specifications ............................................. 2-29 Default settings ........................................................................ 10-8, 10-9
Current metering actual values ................................................. 6-19 Default settings to factory default ...............................................7-3
Curves Definite time curve .......................................................................... 5-268
definite time .....................................................................................5-268 Delete files and records .................................................... 5-43, 10-23
FlexCurves .......................................................................... 5-183, 5-268 Demand metering
IAC .........................................................................................................5-266 actual values ...................................................................................... 6-22
IEC .........................................................................................................5-265 specifications ..................................................................................... 2-30
IEEE .......................................................................................................5-263 Demand records, clearing ....................................................5-43, 7-2
types ....................................................................................................5-263 Demand, current .............................................................................. 5-133
Cutout, panel ............................................................................................ 3-2 Deploy relay ..............................................................................................8-1
CyberSentry Deploy settings ..................................................................................... 10-7
FlexLogic operands .......................................................................5-235 Device authentication ...................................................................... 5-17
installation ............................................................................... 3-75, 5-25 Device Connectivity Report in Engineer ................................. 4-78
RS485 port limitation ...................................................................... 5-18 Device information files ..........................................................1-2, 4-78
security commands ........................................................................... 7-6 Device overview ................................................................................... 10-1
security overview ................................................................................ 2-4 Device setup ........................................................................................... 3-71
software options .............................................................................. 2-37 Diagnostic Alarm COP message ....................................................7-9
specifications ..................................................................................... 2-37 Diagnostic Alarm DSP message ....................................................7-9
system logs ......................................................................................... 5-26 Diagnostic Failure message .............................................................7-8
Diagnostics Failure message ....................................................... 7-10
Dielectric strength .............................................................................. 3-15
D Digital counters
D400 connection ................................................................................. 3-81 actual values .........................................................................................6-8
Dark graphical front panel ............................................................ 5-34 FlexLogic operands ...................................................................... 5-237
Data logger logic diagram .................................................................................. 5-362
actual values ...................................................................................... 6-36 settings ............................................................................................... 5-360
clearing ........................................................................................ 5-43, 7-2 Digital elements
settings ...............................................................................................5-132 application example .................................................................... 5-359
specifications ..................................................................................... 2-28 FlexLogic operands ...................................................................... 5-238
Data set logic diagram .................................................................................. 5-358
defined .................................................................................................. 5-72 settings ............................................................................................... 5-357
Data, reading values ............................................................................ 6-1 Digital outputs
Dataset member is empty message ....................................... 5-73 see Contact outputs
Date Dimensions ................................................................................................3-2
firmware ............................................................................................... 6-39 Direct Device Off message ............................................................ 7-10
last cleared oscillography date ................................................. 6-36 Direct devices
last PMU cleared date ................................................................... 6-37 settings ............................................................................................... 5-408
last settings change ....................................................................... 6-39 status ..................................................................................................... 6-11
manufacturing date ....................................................................... 6-39 Direct I/O
set ..........................................................5-30, 5-118, 5-124, 6-32, 7-3 application example .................................................................... 5-409
DCB3 configuration examples ............................................................. 5-151
FlexLogic operands .......................................................................5-237 settings ............................................................................................... 5-408
logic diagram ...................................................................................5-400
settings ...............................................................................................5-397

iv F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Direct inputs EGD protocol


actual values .......................................................................................6-11 actual values ...................................................................................... 6-12
application example .....................................................................5-409 install software .................................................................................. 3-61
clearing counters ................................................................................ 7-2 settings ...............................................................................................5-111
FlexLogic operands .......................................................................5-243 Electrostatic discharge specifications .................................... 2-39
settings ...............................................................................................5-408 Elements ......................................................................................................5-4
specifications ......................................................................................2-31 Enable Controls from GFP .............................................................. 5-32
Direct outputs End of life ...............................................................................................10-25
application example .....................................................................5-409 Energy algorithm for Hi-Z ..................................................................9-2
clearing counters ................................................................................ 7-2 Energy metering
settings ...............................................................................................5-409 actual values ...................................................................................... 6-22
specifications ......................................................................................2-34 clearing ........................................................................................5-43, 7-2
Direct Ring Break message ............................................................7-10 specifications ..................................................................................... 2-29
Directional comparison blocking 3 Energy metering, clearing .....................................................5-43, 7-2
FlexLogic operands .......................................................................5-237 EnerVista UR setup
logic diagram ...................................................................................5-400 command line interface ...................................................................C-1
settings ...............................................................................................5-397 drag and drop files .............................................................................4-3
Directional overcurrent event recorder ......................................................................................4-2
see Phase, Ground, and Neutral directional firmware upgrade or downgrade ..........................................10-15
Directional polarization .................................................................5-271 installation ........................................................................................... 3-60
Directional power, sensitive actual values ...........................6-25 oscillography .........................................................................................4-2
Directional power, sensitive specifications ..........................2-22 requirements ...................................................................................... 3-59
Disconnect switch restart relay ...........................................................................................5-1
FlexLogic operands .......................................................................5-242 Engineer
logic ......................................................................................................5-180 command to force user logoff ......................................................7-6
settings ...............................................................................................5-175 create logic diagram ...................................................................... 4-64
Discover button ....................................................................................3-71 Error messages ................................................................................. 4-72
Disk space required ............................................................................3-59 toolbar ................................................................................................... 4-82
Display settings .....................................................................................5-28 Warning messages ......................................................................... 4-73
Disposal ..................................................................................................10-25 Enhanced front panel
Dispose of battery ............................................................................10-20 FlexLogic ............................................................................................5-235
Disturbance detector interface ............................................................................................... 4-16
FlexLogic operands .......................................................................5-241 IP rating ................................................................................................ 2-38
DNP keypad ................................................................................................... 4-39
connections remaining ..................................................................6-13 labels ...................................................................................................... 4-45
select protocol ........................................................5-54, 5-55, 10-13 LEDs ..........................................................................................4-40, 5-137
settings ..................................................................................................5-56 navigation ............................................................................................ 4-51
view Points List in web browser .................................................5-58 order codes ............................................................................................2-7
Do not default Remote Input ID check box ..........................5-82 pushbuttons .....................................................................................5-141
Do you want to create device folders ...................................10-14 Rev. 1 and 2 explained .....................................................................3-2
DOS Partition Alarm message ......................................................7-10 specifications ..................................................................................... 2-27
Downed conductor ....................................................... 2-29, 6-11, 9-1 use, change setting ......................................................................... 4-53
Downgrade Environment backup .......................................................................10-10
firmware .............................................................................................10-15 Equations
software .............................................................................................10-14 definite time curve .........................................................................5-268
Download FlexCurves .........................................................................................5-268
files from relay ...................................................................................10-3 FlexLogic ............................................................................................5-253
settings to relay .................................................................................10-7 FlexLogic, protect ............................................................................. 4-10
IAC curves ..........................................................................................5-266
Drag and drop files ............................................................................... 4-3
IEC curves ..........................................................................................5-265
Duplicate
IEEE curves ........................................................................................5-263
device settings ...................................................................................10-7
Equipment Mismatch message .........................................7-8, 7-15
settings for upgrading ....................................................................10-5
Error messages .......................................................................................7-8
device not recognized ..................................................................10-14
in Engineer ........................................................................................... 4-72
E
Edit data model .....................................................................................5-65
Edition 1 and 2 IEC 61850 ...............................................................5-60

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL v


INDEX

Ethernet Filter software fields using double-click ............................. 5-255


actual values ......................................................................................... 6-9 Firmware
configuration ..................................................................................... 3-69 lock ...................................................................... 3-75, 5-11, 5-23, 5-25
port failure monitoring .................................................................. 5-40 Firmware not supported by EnerVista ................................. 10-16
port settings ....................................................................................... 5-47 Firmware revision ............................................................................... 6-39
port, turn on or off ........................................................................... 5-47 Firmware upgrade or downgrade .......................................... 10-15
ports on rear panel ......................................................................... 3-12 Firmware version does not match EnerVista ................... 10-14
Quick Connect ................................................................................... 3-74 First Ethernet Fail
Ethernet Global Data error message ................................................................................... 7-11
install software ................................................................................. 3-61 set alarm .............................................................................................. 5-40
settings ...............................................................................................5-111 Flash memory .................................................................................... 10-23
Event cause indicators .................................................................... 4-40 Flash memory data storage ......................................................... 3-17
Event Cause LEDs ............................................................................... 4-42 Flash messages .................................................................................... 5-28
Event recorder Flex State parameters
actual values ...................................................................................... 6-34 actual values .........................................................................................6-9
clearing ........................................................................................ 5-43, 7-2 settings ............................................................................................... 5-147
records explained ............................................................................... 4-2 specifications ..................................................................................... 2-27
specifications ..................................................................................... 2-28 FlexAnalog parameters ......................................................................A-1
system logs ......................................................................................... 5-26 FlexCurves
via EnerVista software ...................................................................... 4-2 equation ............................................................................................ 5-268
view event records .......................................................................... 6-34 settings ............................................................................................... 5-183
Events setting ........................................................................................... 5-5 specifications ..................................................................................... 2-26
Expert Arc Detector algorithm for Hi-Z ..................................... 9-2 table ..................................................................................................... 5-183
Export settings ...................................................................................... 10-9 FlexElements
actual values ...................................................................................... 6-26
direction ............................................................................................. 5-255
F FlexAnalogs .........................................................................................A-25
F485 ............................................................................................................ 3-59 FlexLogic operands ...................................................................... 5-238
Factory default reset ......................................................5-8, 5-23, 7-3 hysteresis .......................................................................................... 5-255
Far-End Fault Indication ................................................................. 5-49 logic diagram .................................................................................. 5-255
Fast form-C relay specifications ................................................ 2-33 pickup ................................................................................................. 5-255
Fast transient testing specifications ........................................ 2-39 settings ............................................................................................... 5-253
specifications ..................................................................................... 2-27
Fault locator
logic diagram ........................................................................................ 9-7
FlexLogic
create logic diagram with Engineer ........................................ 4-64
operation ................................................................................................ 9-4
edit with equation editor ........................................................... 5-253
specifications ..................................................................................... 2-28
equation editor ............................................................................... 5-253
Fault report
equation example ......................................................................... 5-335
actual values ...................................................................................... 6-33
error message ......................................................................................7-8
clearing ........................................................................................ 5-43, 7-2
evaluation ......................................................................................... 5-247
settings ...............................................................................................5-127
example ............................................................................................. 5-248
Fault, ground detection .................................................................5-283
export ..................................................................................................... 10-7
Features ...................................................................................................... 2-1
gate characteristics ..................................................................... 5-246
Feeder import operands ............................................................................... 3-76
single-line diagram ......................................................................... 4-22
lock equations ................................................................................... 4-10
Fiber signal loss detection ............................................................. 5-49 lock equations to serial number ............................................... 4-12
File transfer by IEC 61850 ............................................................5-108 operands ........................................................................................... 5-234
File transfer by TFTP ........................................................................5-109 operators ........................................................................................... 5-246
File transfer SFTP disable ............................................................... 5-55 rules ..................................................................................................... 5-247
Files security .................................................................................................. 4-10
delete ...................................................................................................10-23 specifications ..................................................................................... 2-26
download from relay ...................................................................... 10-3 status in single-line diagram of graphical front panel ... 4-33
drag and drop ...................................................................................... 4-3 timer settings .................................................................................. 5-253
protect FlexLogic with password ............................................. 4-10 worksheet ......................................................................................... 5-250
protect with password ..................................................................... 4-8 Force contact inputs ...................................................................... 5-423
repaired ................................................................................................ 10-7 Force contact outputs ...................................... 5-424, 5-426, 5-428
transfer from relay .......................................................................... 4-18
transfer to relay ....................................................................... 4-1, 4-18

vi F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Foreign language
keyboard ...............................................................................................4-57 G
setting ....................................................................................................5-28 G.703 .......................................................................................................... 3-44
Form-A relay wire size ................................................................................................ 3-44
actual values ......................................................................................... 6-7 Gates, logic explained ...................................................................... 4-85
high-impedance circuits ...............................................................3-22 Gateway address .................................................................... 3-63, 5-50
outputs ..................................................................................................3-21 GE type IAC curves ...........................................................................5-266
specifications ......................................................................................2-33 Getting help ...............................................................................................1-2
Form-C GFP Version Mismatch message ................................................ 7-11
actual values ......................................................................................... 6-7 GOOSE
critical failure relay ..........................................................................3-16 actual values ...................................................................................... 6-27
order codes ........................................................................................... 2-7 FlexAnalogs ......................................................................................... A-26
outputs ..................................................................................................3-21 Process Bus Module limitations ................................................. 5-71
replacement modules ....................................................................2-15 Process Bus requires module and software options ..........2-7
specifications ......................................................................................2-33 Process Bus with IEC 61850 Ed 2 .............................................. 5-61
FPGA settings ................................................................................................. 5-71
revision ..................................................................................................6-39 simulation operands .....................................................................5-246
upgrade ..............................................................................................10-17 simulation settings ........................................................................5-426
Frequency metering GOOSE & SV simulation settings ..............................................5-426
actual values .......................................................................................6-23 Graphical front panel
specifications ......................................................................................2-30 actual value menu not activated ............................................. 4-54
Frequency rate of change actual values, phasors ................................................................... 4-58
actual values .......................................................................................6-26 alarm acknowledge, reset ..................................................4-35, 6-4
FlexAnalogs ........................................................................................... A-2 alarm setup ......................................................................................... 5-38
FlexLogic operands .......................................................................5-238 annunciator editor ........................................................................... 4-36
logic diagram ...................................................................................5-345 date and time .................................................................................... 5-32
settings ...............................................................................................5-344 explained .............................................................................................. 4-19
specifications ......................................................................................2-24 FlexLogic ............................................................................................5-235
Frequency specifications ................................................................2-31 Home page configuration ............................................................ 5-30
Frequency testing .................................................................................. 8-1 interface ............................................................................................... 4-18
Frequency tracking .............................................................................6-26 IP rating ................................................................................................ 2-38
Frequency, nominal .........................................................................5-160 labels ...................................................................................................... 4-50
Front panel ................................................................................................ 3-2 LEDs ..........................................................................................4-44, 5-137
clear .....................................................................................................5-407 Metering Editor .................................................................................. 4-37
custom labels .....................................................................................4-45 navigation ............................................................................................ 4-52
dimensions ............................................................................................. 3-2 navigation keys ................................................................................. 4-39
interface ................................................................................................4-16 no display ............................................................................................. 5-34
keypad ...................................................................................................4-39 order codes ............................................................................................2-7
labels ......................................................................................................4-45 phasor diagram .................................................................... 4-58, 5-34
language ...............................................................................................5-28 pushbutton testing .............................................................................7-3
LEDs ........................................................................................................4-40 pushbuttons .........................................................................5-32, 5-141
number of characters .....................................................................4-18 pushbuttons 9 to 16 ........................................................................ 4-31
order code with two lines on basic panel .............................4-39 settings ................................................................................................. 5-30
password change .............................................................................4-60 settings, breaker .............................................................................5-169
pushbuttons .....................................................................................5-141 settings, switch ................................................................................5-178
specifications ......................................................................................2-37 single-line diagrams ....................................................................... 4-21
switch between enhanced and basic .....................................3-60 specifications ......................................................................... 2-35, 2-37
trouble message ...............................................................................7-11 time ......................................................................................................... 5-32
types .......................................................................................................4-16 USB port ..............................................................................................5-117
use ...........................................................................................................4-16 use, change setting ......................................................................... 4-54
use in EnerVista ....................................................................... 4-18, 6-4 view LEDs and pushbuttons in software ..................................6-4
Function setting ...................................................................................... 5-5 Ground current metering ............................................................... 6-20
Fuse failure ...........................................................................................5-383 Ground fault
Fuse specifications .............................................................................2-32 detection ............................................................................................5-283
Fuses not field-replaceable ........................................................10-24

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL vii


INDEX

Ground IOC Home page configuration .............................................................. 5-30


FlexLogic operands .......................................................................5-238 HSR
logic diagram ...................................................................................5-295 actual values ...................................................................................... 6-33
settings ...............................................................................................5-294 explained ........................................................................................... 5-212
specifications ..................................................................................... 2-20 support .....................................................................................................2-2
Ground TOC HTTP ......................................................................................................... 5-108
FlexLogic operands .......................................................................5-238 port, close ......................................................................................... 5-108
logic diagram ...................................................................................5-294 Humidity specifications ................................................................... 2-38
settings ...............................................................................................5-293 Hysteresis ............................................................................................. 5-255
specifications ..................................................................................... 2-20
Group 1 switch after powerup ..................................................5-260
Grouped elements ............................................................................5-260 I
Guarantee ..................................................................................................D-1
IAC curves ............................................................................................. 5-266
ICD file ........................................................................................................ 5-82
IEC 60870-5-103 protocol
H explained ........................................................................................... 5-112
HardFiber select protocol ........................................................ 5-54, 5-55, 10-13
Brick Trouble message .................................................................. 7-16 settings ............................................................................................... 5-112
interface module described ........................................................ 3-20 IEC 60870-5-104 protocol
order codes for compatible URs .................................................. 2-7 connections remaining .................................................................. 6-13
remote resources actual values ............................................... 6-29 port, close ......................................................................................... 5-110
remote resources settings .........................................................5-158 select protocol ........................................................ 5-54, 5-55, 10-13
self-test errors ................................................................................... 7-15 settings ............................................................................................... 5-109
Harmonic content .............................................................................. 6-24 IEC 61850 protocol
Harmonic detection DstMAC addresses message ...................................................... 5-75
actual values ...................................................................................... 6-29 Edition 1 and 2 support ................................................................. 5-60
FlexLogic operands .......................................................................5-238 explained .............................................................................................. 5-60
settings ...............................................................................................5-391 file transfer ....................................................................................... 5-108
specifications ..................................................................................... 2-26 heartbeat messages ........................................................... 5-72, 5-76
Harmonics IID file ..................................................................................................... 10-9
actual values ...................................................................................... 6-24 settings in EnerVista ....................................................................... 5-60
FlexAnalogs ...........................................................................................A-6 specifications ..................................................................................... 2-35
specifications ......................................................................... 2-29, 2-30 IEC 61850-90-5 protocol
Heartbeat messages ............................................................ 5-72, 5-76 actual values ...................................................................................... 6-28
Help, getting .............................................................................................. 1-2 explained ........................................................................................... 5-190
Hexadecimal conversion to decimal .....................................5-112 settings ............................................................................................... 5-195
Hexadecimal convert to decimal ............................................5-118 IEC CID files ............................................................................................. 5-63
Hi-Z IED setup .................................................................................................. 3-60
actual values .......................................................................... 6-11, 6-38 IEEE C37.94 communications .......................................... 3-52, 3-55
Arc Burst Pattern Analysis .............................................................. 9-4 IEEE curves ........................................................................................... 5-263
Arcing Suspected algorithm .......................................................... 9-4 IID file .................................................................................. 3-80, 5-63, 10-9
CT/VT module .................................................................................... 3-19 import preferences ....................................................................... 10-10
data collection .................................................................................5-364 Import SCL file when using Process Bus Module .............. 5-71
Energy algorithm ................................................................................ 9-2 Import settings file .............................................................................. 3-76
Even Harmonic Restraint algorithm .......................................... 9-4 Import settings from SCD or CID file ..................................... 10-13
Expert Arc Detector algorithm ...................................................... 9-2 In service indicator ................................................................................7-8
explained ................................................................................................ 9-1 In Service LED ........................................................................................ 3-57
FlexAnalogs ........................................................................................ A-12 Incipient cable fault detector
Load Analysis algorithm .................................................................. 9-3 actual values ...................................................................................... 6-13
Load Event Detector algorithm .................................................... 9-3 clear counter .........................................................................................7-2
Load Extraction algorithm .............................................................. 9-3 FlexLogic operands ...................................................................... 5-239
logic diagram ...................................................................................5-368 logic diagram .................................................................................. 5-383
Randomness algorithm ................................................................... 9-2 settings ............................................................................................... 5-381
settings ...............................................................................................5-363 specifications ..................................................................................... 2-25
specifications ..................................................................................... 2-29 Incompatible device order codes or versions ................. 10-16
Spectral Analysis algorithm ........................................................... 9-3
Voltage Supervision algorithm ..................................................... 9-4

viii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Inputs
AC current specifications ..............................................................2-30 K
AC currents .......................................................................................5-159 Keyboard .................................................................................................. 4-57
AC voltage .........................................................................................5-159 Keypad ...................................................................................................... 4-39
AC voltage specifications ..............................................................2-30
contact input specifications ........................................................2-31
contact inputs .................................................................. 5-400, 5-423
DCmA input specifications ...........................................................2-31
L
DCmA inputs .......................................................................................3-33 Labels, front panel .................................................................. 4-45, 4-78
direct input specifications ............................................................2-31 Lamp test ....................................................................................................7-3
IRIG-B ......................................................................................................3-39 Language setting ................................................................................ 5-28
IRIG-B specifications .......................................................................2-31 Laser module ......................................................................................... 3-43
RTD input specifications ................................................................2-31 Latching outputs
RTD inputs ............................................................................................3-33 application examples ...................................................................5-405
virtual ..................................................................................................5-402 settings ...............................................................................................5-404
Installation ................................................................................................. 3-2 specifications ..................................................................................... 2-33
activate relay ......................................................................................3-57 LC fiber .............................................................................................2-7, 3-12
add UR devices with auto discovery .......................................3-71 LC fiber connector .............................................................................. 3-13
communications ...............................................................................3-36 LED test
CT inputs ...............................................................................................3-18 commands .............................................................................................7-3
EGD software ......................................................................................3-61 FlexLogic operand .........................................................................5-244
RS485 .....................................................................................................3-38 settings ...............................................................................................5-135
set relay to Programmed ..............................................................3-57 specifications ..................................................................................... 2-27
settings ...............................................................................................5-157 LEDs
silent .....................................................................................................10-15 clear ......................................................................................................5-407
Instantaneous overcurrent custom labels ..................................................................................... 4-45
see Phase, Ground, and Neutral IOCs explained .............................................................................................. 4-40
Interface In Service .............................................................................................. 3-57
front panel ...........................................................................................4-16 power supply module .................................................................... 3-17
software .................................................................................................. 4-1 settings ...............................................................................................5-137
Internet access ..................................................................................5-108 Trouble .................................................................................................. 3-57
Inter-relay communication specifications ............................2-36 view in software for graphical front panel ..............................6-4
IOC License
see Phase, Ground, and Neutral IOCs open source .......................................................................................... D-3
IP address single user ........................................................................................... 3-60
enter in software ...............................................................................5-47 Link power budget .............................................................................. 2-36
enter on front panel ............................................................3-63, 4-39 Load Analysis algorithm for Hi-Z ...................................................9-3
gateway ................................................................................................5-50 Load encroachment
rules .........................................................................................................3-62 FlexLogic operands .......................................................................5-239
view .........................................................................................................5-47 logic diagram ...................................................................................5-262
IP address migration ..........................................................................3-80 settings ...............................................................................................5-260
IP rating .....................................................................................................2-38 specifications ..................................................................................... 2-25
IP54 for enhanced front panel ..................................................... 3-2 Load Event Detector algorithm for Hi-Z ....................................9-3
IRIG-B Load Extraction algorithm for Hi-Z ..............................................9-3
connection on rear panel .............................................................3-12 Load shedding .....................................................................5-342, 5-345
CPU wiring ............................................................................................3-36 Local access denied message ......................................... 4-62, 5-22
explained ..............................................................................................3-39 Local access, explained ......................................................................5-9
port on rear panel ............................................................................3-12 Local Setting Authorization .........................................................10-16
specifications ......................................................................................2-31 Lock
ISO standards ........................................................................................2-40 firmware ........................................................... 3-75, 5-11, 5-23, 5-25
settings ......................................................................... 3-75, 5-23, 5-25
Lockout from software .................................................................... 5-15
J Log in with password ................................................ 3-75, 5-10, 5-11
Japanese limited to 10 character input .................................5-28 Log in, multiple users cannot ..........................................................2-4
Log out
Administrator manually from front panel ............................ 5-22
users forcefully .....................................................................................7-3

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL ix


INDEX

Logic diagram Modbus


create .................................................................................................... 4-64 connections remaining .................................................................. 6-13
explained ............................................................................................. 4-63 enter values in Modbus Analyzer .............................................. 10-1
Logic gates, FlexLogic ........................................................4-85, 5-247 Flex State parameters ................................................................. 5-147
Logical node or device ..................................................................... 5-65 Modbus Analyzer window ............................................................ 10-1
Logs, system .......................................................................................... 5-26 port, close ............................................................................................ 5-53
Lost password ......................................................................................... 5-8 register entry ................................................................................... 5-117
Low on Memory message ............................................................. 7-10 settings .................................................................................................. 5-53
user map ........................................................................................... 5-117
Model information, view .................................................................. 6-39
Model number ..........................................................................................3-1
M Modem connection ............................................................................ 3-70
MAC address
Modification file number ................................................................. 6-39
actual values ...................................................................................... 6-39
Module 7R ................................................................................................ 3-45
examples ............................................................................................. 5-46
Module 7S ................................................................................................ 3-44
RxGOOSE .............................................................................................. 5-79
settings for redundancy ............................................................... 5-48
Module Failure message ................................................................. 7-15
TxGOOSE .............................................................................................. 5-74 Modules
Maintenance add and check settings not defaulted ................................ 10-18
communications ............................................................................... 3-36
actual values ...................................................................................... 6-37
CT/VT .............................................................................................3-17, 5-7
alert error message ........................................................................ 7-10
Hi-Z .......................................................................................................... 3-19
battery replacement ....................................................................10-19
order codes ......................................................................................... 2-15
cleaning ................................................................................................ 2-40
power supply ...................................................................................... 3-16
commands ............................................................................................. 7-3
replace ............................................................................................... 10-17
module replacement ....................................................................10-17
transducer I/O .................................................................................... 3-34
upgrade or downgrade ...............................................................10-15
Manufacturing date .......................................................................... 6-39 Monitor
actual values ...................................................................................... 10-1
Maximum 6X, 6X wire size ............................................................. 3-23
actual values with Metering Editor .......................................... 5-34
Maximum CT/VT wire size .............................................................. 3-18
devices .................................................................................................. 10-1
Measurements of UR and panel cutout .................................... 3-2
use alarms ........................................................................................... 5-38
Media storage alarm message ................................................... 7-12
Monitoring elements settings ................................................... 5-362
Memory low message ...................................................................... 7-10
Mounting .....................................................................................................3-2
Memory requirements ..................................................................... 3-59
Menu navigation ................................................................................. 4-51
Message about upgrade over Internet ................................10-16
Messages N
clear front panel .............................................................................5-407 Nameplate, rear ......................................................................................3-1
error .......................................................................................................... 7-8 NAND gate explained ....................................................................... 4-85
errors and warnings in Engineer .............................................. 4-71 Navigation keys .................................................................................... 4-39
Metering Negative sequence directional overcurrent
conventions ............................................................................ 6-15, 6-16 characteristics ................................................................................ 5-306
demand specifications .................................................................. 2-30 FlexLogic operands ...................................................................... 5-239
editor in graphical front panel ................................................... 4-37 logic diagram .................................................................................. 5-307
frequency specifications .............................................................. 2-30 settings ............................................................................................... 5-304
power specifications ...................................................................... 2-29 specifications ..................................................................................... 2-22
THD specifications ........................................................................... 2-30 Negative sequence IOC
voltage specifications .................................................................... 2-29 FlexLogic operands ...................................................................... 5-239
Microsoft Windows requirement ............................................... 3-59 logic diagram .................................................................................. 5-304
Mimic diagrams ................................................................................... 4-21 settings ............................................................................................... 5-303
Missing messages, RxGOOSE fail ............................................... 7-12 specifications ..................................................................................... 2-21
MMS connections remaining ....................................................... 6-13 Negative sequence overvoltage
FlexLogic operands ...................................................................... 5-239
logic diagram .................................................................................. 5-324
settings ............................................................................................... 5-323
specifications ..................................................................................... 2-23

x F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Negative sequence TOC Oscillatory GOOSE maintenance message .......................... 7-11


FlexLogic operands .......................................................................5-239 Oscillatory transient testing specifications .......................... 2-39
logic diagram ...................................................................................5-303 Oscillography
settings ...............................................................................................5-302 actual values ...................................................................................... 6-36
specifications ......................................................................................2-21 clearing ........................................................................................5-43, 7-2
Network settings migration ...........................................................3-76 how to ..................................................................................................5-130
Neutral directional overcurrent settings ...............................................................................................5-129
FlexLogic operands .......................................................................5-239 specifications ..................................................................................... 2-28
logic diagram ...................................................................................5-283 via EnerVista software ......................................................................4-2
polarization .......................................................................................5-281 view waveform in actual values window ............................. 6-36
settings ................................................................................ 5-278, 5-283 view waveform in event record ................................................. 6-34
specifications ......................................................................................2-21 Out of service ...........................................................................................5-1
Neutral IOC Outputs
FlexLogic operands .......................................................................5-239 contact outputs ..............................................................................5-403
logic diagram ...................................................................................5-278 control power specifications ...................................................... 2-34
settings ...............................................................................................5-276 critical failure relay specifications ............................................ 2-33
specifications ......................................................................................2-20 Fast form-C relay specifications ............................................... 2-33
Neutral overvoltage Form-A relay ........................................................................... 2-33, 3-21
FlexLogic operands .......................................................................5-239 Form-C relay ....................................................................................... 3-21
logic diagram ...................................................................................5-323 Form-C relay specifications ........................................................ 2-33
settings ...............................................................................................5-322 latching output specifications ................................................... 2-33
specifications ......................................................................................2-23 latching outputs ..............................................................................5-404
Neutral TOC virtual outputs .................................................................................5-407
FlexLogic operands .......................................................................5-239 Over Temperature message ......................................................... 7-13
logic diagram ...................................................................................5-276 Overcurrent curves
settings ...............................................................................................5-275 FlexCurves .........................................................................................5-268
specifications ......................................................................................2-20 IAC .........................................................................................................5-266
No connection .......................................................................................5-48 IEC .........................................................................................................5-265
Non-volatile data storage ..............................................................3-17 types .....................................................................................................5-263
Non-volatile latches Overfrequency
FlexLogic operands .......................................................................5-239 FlexLogic operands .......................................................................5-239
settings ...............................................................................................5-258 logic diagram ...................................................................................5-344
specifications ......................................................................................2-27 settings ...............................................................................................5-343
NOR gate explained ...........................................................................4-85 specifications ..................................................................................... 2-24
NOT gate explained ............................................................................4-85 testing .......................................................................................................8-1
Number of channels exceeds total allowable, SV Stream Overvoltage
Config ............................................................................................5-227 auxiliary ..................................................................................2-23, 5-326
negative sequence ........................................................................5-323
negative-sequence ......................................................................... 2-23
neutral .....................................................................................2-23, 5-322
O phase ........................................................................2-23, 5-240, 5-321
Obtain list of port numbers ............................................................5-47
One-shot
commands menu, PMU ................................................................... 7-5
error compiling in Engineer ..........................................................4-72 P
FlexLogic operators ......................................................................5-247 Panel cutout ..............................................................................................3-2
Open source licenses ..........................................................................D-3 Parallel Redundancy Protocol
Operating system actual values ...................................................................................... 6-13
language ...............................................................................................3-60 explained .............................................................................................. 5-49
requirements ......................................................................................3-59 settings ................................................................................................. 5-47
Operating temperature ....................................................................2-38 settings with Process Bus Module ..........................................5-211
Operating times ....................................................................................2-20 specifications ..................................................................................... 2-35
Operator command to force logoff ............................................. 7-6 Parity .......................................................................................................... 5-44
OR gate explained ...............................................................................4-85 Part numbering .......................................................................................2-7
Order codes .............................................................................................. 2-7
two lines on basic front panel ....................................................4-39
update .......................................................................................... 3-70, 7-3
view as actual values ......................................................................6-39

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL xi


INDEX

Passwords PMU
authentication by device or server .......................................... 5-17 actual values .............................................................. 6-27, 6-28, 6-37
bypass authentication ................................................................... 5-24 clear records .........................................................................................7-2
change .................................................................................................. 4-60 connections remaining .................................................................. 6-13
change after installation .............................................................. 3-75 explained ........................................................................................... 5-190
change does not take relay out of service ............................. 5-1 FlexAnalogs .............................................................................A-13, A-28
command .................................................................... 4-61, 5-10, 5-11 number in UR device ................................................................... 5-191
default ................................................................................................... 5-15 see Synchrophasor
explained ................................................................................................ 2-3 settings, aggregator .................................................................... 5-207
FlexLogic operands .......................................................................5-244 settings, recording ........................................................................ 5-206
lockout ...................................................................................... 4-62, 5-15 settings, tests .................................................................................. 5-424
lost password ....................................................................................... 5-8 specifications ..................................................................................... 2-29
requirements ........................................................................................ 5-8 status of activation .......................................................................... 6-39
reset to factory defaults .................................................................. 5-8 Points List, view DNP ......................................................................... 5-58
rules ........................................................................................................... 5-8 Port
settings ......................................................................... 4-61, 5-10, 5-11 Ethernet, turn on or off .................................................................. 5-47
settings templates .............................................................................. 4-8 failure monitoring ............................................................................ 5-40
wrong entry ........................................................................................ 4-62 HTTP, close ....................................................................................... 5-108
PBM PTP settings ................................................................ 5-124, 5-214 IEC 60870-5-104, close ............................................................... 5-110
Permissive functions .......................................................................5-317 Modbus, close .................................................................................... 5-53
Per-unit quantity .................................................................................... 5-4 on rear panel ...................................................................................... 3-12
Phase angle metering ...................................................................... 6-16 settings for Process Bus Module ............................................ 5-126
Phase current metering .................................................................. 6-19 TFTP, close ........................................................................................ 5-109
Phase directional overcurrent USB .......................................................................................................... 4-18
FlexLogic operands .......................................................................5-240 Port number
logic diagram ...................................................................................5-274 combinations with protocols ...................................................... 5-54
phase A polarization .....................................................................5-272 connectivity report of those used ............................................ 4-78
settings ...............................................................................................5-271 DNP ......................................................................................................... 5-56
specifications ..................................................................................... 2-21 HTTP ..................................................................................................... 5-108
Phase IOC IEC 60870-5-104 ............................................................................ 5-109
FlexLogic operands .......................................................................5-240 list of ....................................................................................................... 5-47
logic diagram ...................................................................................5-271 Modbus ................................................................................................. 5-53
settings ...............................................................................................5-270 Modbus during installation .......................................................... 3-70
specifications ..................................................................................... 2-20 RADIUS .................................................................................................. 5-19
Phase overvoltage SNTP .................................................................................................... 5-122
FlexLogic operands .......................................................................5-240 speed for Process Bus Module ................................................... 3-13
logic diagram ...................................................................................5-322 system log ............................................................................... 5-20, 5-21
settings ...............................................................................................5-321 TFTP ..................................................................................................... 5-109
specifications ..................................................................................... 2-23 POTT3
Phase rotation ....................................................................................5-160 FlexLogic operands ...................................................................... 5-241
Phase TOC logic diagram .................................................................................. 5-397
FlexLogic operands .......................................................................5-240 settings ............................................................................................... 5-395
logic diagram ...................................................................................5-270 Power metering
settings ...............................................................................................5-268 specifications ..................................................................................... 2-29
specifications ..................................................................................... 2-20 values ..................................................................................................... 6-21
Phase undervoltage Power off, save data first ................................................................ 3-17
FlexLogic operands .......................................................................5-240 Power supply
logic diagram ...................................................................................5-321 description ........................................................................................... 3-16
settings ...............................................................................................5-319 diagram ................................................................................................ 3-12
specifications ..................................................................................... 2-22 LED on module .................................................................................. 3-17
Phasor display graphical front panel .......................... 4-58, 5-34 removal to replace battery ....................................................... 10-19
Phasor explained ..............................................................................5-190 RH/RL vs SH/SL ............................................................................... 10-19
Pilot schemes specifications ..................................................................................... 2-32
DCB3 ....................................................................................................5-397 wire size ................................................................................................ 3-16
Directional comparison blocking 3 ........................................5-397 Power system settings .................................................................. 5-160
POTT3 ..................................................................................................5-395
specifications ..................................................................................... 2-25
Ping test times out ............................................................................. 5-48

xii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Precision Time Protocol pu quantity .................................................................................................5-4


clock settings ........................................................ 5-118, 5-124, 6-32 Pushbuttons
port behavior ......................................................................................5-48 control FlexLogic ............................................................................5-235
settings ...............................................................................................5-120 control logic diagram ...................................................................5-141
settings with Process Bus Module .............. 5-124, 5-214, 6-32 control settings ...............................................................................5-140
specifications ......................................................................................2-35 control specifications ..................................................................... 2-27
Preferences enable for graphical front panel ............................................... 5-32
comparing settings ..........................................................................10-8 testing .......................................................................................................7-3
Engineer ................................................................................................4-79 user-programmable FlexLogic ................................................5-246
IEC 61850 ..............................................................................................5-65 user-programmable logic diagrams .....................................5-146
import file ..........................................................................................10-10 user-programmable settings ...................................................5-141
Preserve custom attributes importing SCD/CID files ...10-10 user-programmable specifications ......................................... 2-27
Press Reset Key message ...............................................................7-13 view in software for graphical front panel ..............................6-4
Print front panel labels .........................................................4-45, 4-78
Process bus
error messages ..................................................................................7-15 Q
order codes for compatible URs .................................................. 2-7 Quick Connect ........................................................................... 3-73, 3-74
overview ................................................................................................3-20
Process Bus Failure message .......................................................7-15
Process Bus GOOSE
requires module and software options .................................... 2-7 R
works with IEC 61850 Ed 2 ...........................................................5-61 RADIUS server
Process Bus Module authentication ................................................................................... 5-17
actual values .......................................................................................6-30 explained ........................................................................................2-4, 2-7
FlexLogic operands .......................................................................5-245 setup .........................................................................................................B-1
GOOSE limitations ............................................................................5-71 RAM Filesystem Fail message .........................................................7-9
not supported in IEC 61850 Ed. 1 ..............................................5-61 RAM required ......................................................................................... 3-59
PBM PTP settings ............................................................. 5-124, 5-214 Randomness algorithm for Hi-Z ....................................................9-2
port speeds ..........................................................................................3-13 Reactive power
ports .....................................................................................................5-126 actual values ...................................................................................... 6-21
PRP ........................................................................................................5-211 specifications ..................................................................................... 2-29
remote resources actual values ................................................6-29 Real power .............................................................................................. 6-21
SV Stream Config settings .........................................................5-218 Real power specifications .............................................................. 2-29
Time Sync settings ...........................................................................6-32 Real-time clock
time with PTP ........................................................ 5-124, 5-214, 6-32 settings ....................................................................5-118, 5-124, 6-32
Process Bus Trouble message .....................................................7-16 settings with Process Bus Module ...............5-124, 5-214, 6-32
Product information Reboot relay
actual values .......................................................................................6-39 using EnerVista ....................................................................................5-1
Device Connectivity Report in Engineer .................................4-78 using relay ..............................................................................................7-3
firmware revision ..............................................................................6-39 Recloser curves ...................................................................5-185, 5-268
Programmed mode ............................................................................3-57 Recycling ................................................................................................10-25
Protection elements ............................................................................. 5-4 Redundancy
Protection Summary interface .............................3-73, 4-5, 5-331 HSR support ...........................................................................................2-2
Protocol selection .....................................................5-54, 5-55, 10-13 power supply ....................................................................................10-19
Prototype Firmware message ......................................................7-12 PRP actual values ............................................................................. 6-13
PRP PRP explained .................................................................................... 5-49
actual values .......................................................................................6-13 settings ................................................................................................. 5-47
explained ..............................................................................................5-49 SNTP .....................................................................................................5-122
Process Bus Module .....................................................................5-211 specifications ..................................................................................... 2-35
settings ..................................................................................................5-47 Relay architecture ............................................................................5-232
settings with Process Bus Module .........................................5-211 Relay maintenance ...............................................................................7-3
specifications ......................................................................................2-35 Relay name ...........................................................................................5-157
PTP Release Notes .....................................................................................10-15
clock settings ........................................................ 5-118, 5-124, 6-32 Remote access of front panel in EnerVista .................4-18, 6-4
port behavior ......................................................................................5-48 Remote access, explained ................................................................5-9
settings ...............................................................................................5-120 Remote devices
settings with Process Bus Module .............. 5-124, 5-214, 6-32 actual values ...................................................................................... 6-29
specifications ......................................................................................2-35 Remote Input ID check box ........................................................... 5-82

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL xiii


INDEX

Remote resources RTD inputs


settings ...............................................................................................5-158 actual values ...................................................................................... 6-29
Remote Setting Authorization ...................................................10-16 FlexAnalogs ............................................................................... A-1, A-22
Rename logical node or device .................................................. 5-66 settings ............................................................................................... 5-415
Repair ....................................................................................1-2, 10-24, D-1 specifications ..................................................................................... 2-31
Repaired file message ...................................................................... 10-7 RTD Trouble message ....................................................................... 7-16
Replace battery ..................................................................................10-19 Rules for passwords .............................................................................5-8
Replace Battery message .............................................................. 7-11 RxGOOSE
Replacement modules .......................................................2-15, 10-17 actual values ...................................................................................... 6-27
Requirements for installation ...................................................... 3-59 FlexAnalogs .........................................................................................A-26
Reserved settings .................................................................................. 4-4 settings .................................................................................................. 5-77
Reset alarm ............................................................................................... 6-4 RxGOOSE Fail message ................................................................... 7-12
Reset to factory defaults ....................................................... 5-8, 5-23 RxGOOSE Offline message ............................................................. 7-12
Resetting
FlexLogic operands .......................................................................5-245
setting to clear LEDs and messages .....................................5-407 S
to factory defaults .....................................................................5-8, 7-3 Sampled value explained ............................................................ 5-211
Restart relay Save settings .............................................................................................4-1
using EnerVista .................................................................................... 5-1 Saving setting does not take relay out of service ...............5-1
using relay .............................................................................................. 7-3 SCADA protocol selection .................................... 5-54, 5-55, 10-13
Restore settings ................................................................................... 10-9 SCD file
Restricted ground fault import ................................................................................................. 10-13
actual values ...................................................................................... 6-28 import preferences ....................................................................... 10-10
FlexAnalogs ...........................................................................................A-1 SCL compatible ..................................................................................... 5-60
FlexLogic operands .......................................................................5-241 SCL file import ....................................................................................... 5-82
logic diagram ...................................................................................5-301 Edition 1 versus 2 ............................................................................. 5-60
settings ...............................................................................................5-295 preferences ...................................................................................... 10-10
specifications ..................................................................................... 2-20 Process Bus Module and GOOSE error ................................... 5-71
Revision history .......................................................................................D-1 Second Ethernet Fail
RF immunity specifications ........................................................... 2-39 error message ................................................................................... 7-11
RFI, conducted specifications ...................................................... 2-39 set alarm .............................................................................................. 5-40
RH/RL power supply module ......................................................10-19 Security
RJ-45 ................................................................................................. 2-7, 3-12 commands .............................................................................................7-6
RMS voltage specifications ........................................................... 2-29 delete files and records .............................................................. 10-23
Roles for login .......................................................................................... 2-4 EnerVista and UR secure with SSH .............................................2-4
Rolling demand ..................................................................................5-134 failed authentication lockout ...................................................... 5-23
RRTD Comm Fail message ............................................................ 7-12 forceful user logout ............................................................................7-3
RS232 lock FlexLogic equations .............................................................. 4-10
baud rate ............................................................................................. 5-44 lock settings ...........................................................................................4-6
configuration ..................................................................................... 3-73 password for settings template ...................................................4-8
specifications ..................................................................................... 2-35 passwords for settings and commands ........ 4-61, 5-10, 5-11
wiring ..................................................................................................... 3-35 RADIUS server for user authentication .....................................B-1
RS422 role-based user access ....................................................................2-4
configuration ..................................................................................... 3-48 settings .................................................................................................. 5-21
timing .................................................................................................... 3-49 software options ............................................................................... 2-37
two-channel application .............................................................. 3-48 specifications ..................................................................................... 2-37
with fiber interface .......................................................................... 3-50 system and event logs ................................................................... 5-26
RS485 Security audit list of port numbers ............................................ 5-47
description .......................................................................................... 3-38 Selector switch
limitation with CyberSentry ......................................................... 5-18 actual values .........................................................................................6-9
port on rear panel ............................................................................ 3-12 application example .................................................................... 5-340
settings ................................................................................................. 5-44 FlexLogic operands ...................................................................... 5-241
specifications ..................................................................................... 2-35 logic diagram .................................................................................. 5-342
settings ............................................................................................... 5-335
specifications ..................................................................................... 2-27
timing .................................................................................................. 5-339

xiv F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Self-tests Settings templates


description ............................................................................................. 7-8 description ..............................................................................................4-6
error messages .................................................................................... 7-8 edit .............................................................................................................4-7
FlexLogic operands .......................................................................5-246 enable .......................................................................................................4-6
user-programmable .....................................................................5-139 password protection .........................................................................4-8
Sensitive directional power remove .................................................................................................. 4-10
actual values .......................................................................................6-25 view ...........................................................................................................4-8
characteristic ...................................................................................5-328 SFP
FlexAnalogs ........................................................................................... A-1 explained .............................................................................................. 3-11
FlexLogic operands .......................................................................5-238 maximum cable length ................................................................. 3-11
logic diagram ...................................................................................5-330 module fail message ...................................................................... 7-11
settings ...............................................................................................5-327 SFTP
specifications ......................................................................................2-22 enable or disable .............................................................................. 5-55
Serial number ................................................................... 3-1, 4-12, 6-39 transfer settings .............................................................................10-13
Serial ports SH/SL power supply module ......................................................10-19
device setup with ..............................................................................3-68 Show Custom Layout button .....................................................5-219
location ..................................................................................................4-16 Show Enabled button .....................................................................5-219
settings ..................................................................................................5-44 Signal loss detection for fiber ...................................................... 5-49
specifications ......................................................................................2-35 Signal sources
wiring ......................................................................................................3-50 description ..............................................................................................5-6
Server authentication .......................................................................5-17 metering ............................................................................................... 6-19
Service life expected ..........................................................................10-3 settings ...............................................................................................5-162
Service Report ......................................................................................... 1-2 Silent software installation ..........................................................10-15
Setting groups ..................................................................... 5-260, 5-333 Simulation
active setting group .....................................................................5-260 operands ............................................................................................5-246
FlexLogic operands .......................................................................5-241 settings ...............................................................................................5-426
troubleshooting ..............................................................................5-260 Simulation bit .......................................................................................5-420
Settings ........................................................................................................ 5-1 Single-line diagram ...............................................................................2-2
back up ......................................................................................5-63, 10-9 create, explained .............................................................................. 4-21
change ...................................................................................................4-53 save as separate file ....................................................................... 4-26
change does not take relay out of service ............................. 5-1 T means tagged breaker .............................................................. 4-25
compare ................................................................................................10-8 Site Targets ............................................................................................. 10-1
control user accounts .....................................................................5-15 Size of UR and panel cutout .............................................................3-2
convert ...................................................................................................10-5 Smart defaults ....................................................................................5-130
default to factory defaults .............................................................. 7-3 SNTP Failure message ...................................................................... 7-11
edit ...........................................................................................................4-53 SNTP protocol
export .........................................................................................10-7, 10-9 accuracy specifications ................................................................ 2-35
import .....................................................................................................3-76 redundant source ..........................................................................5-122
lock ........................................................................ 3-75, 4-6, 5-23, 5-25 settings ...............................................................................................5-122
not updated automatically among computers ..................3-72 Software
read from device with Modbus Analyzer ...............................10-1 install EGD ............................................................................................ 3-61
restore ....................................................................................................10-9 installation ........................................................................................... 3-60
upgrade .................................................................................................10-5 interface explained ............................................................................4-1
write to device with Modbus Analyzer ....................................10-1 language .............................................................................................. 5-28
Settings file ..............................................................................................5-63 license .................................................................................................... 3-60
description ............................................................................................. 4-1 silent installation ............................................................................10-15
import .....................................................................................................3-76 system requirements ..................................................................... 3-59
takes relay out of service when loaded ................................... 4-2 update or downgrade ..................................................................10-14
traceability ...........................................................................................4-13 Source frequency ................................................................................ 6-23
transfer with USB stick ...................................................................4-18
Source transfer schemes .............................................................5-317
Settings password .......................................................4-61, 5-10, 5-11
Sources
Settings Save Error message ........................................................7-12 description ..............................................................................................5-6
example of use ................................................................................5-164
FlexAnalogs ......................................................................................... A-23
metering ............................................................................................... 6-19
settings ...............................................................................................5-162
Special characters .............................................................................. 4-57
Specifications ........................................................................................ 2-19

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL xv


INDEX

Spectral Analysis algorithm for Hi-Z ........................................... 9-3 Targets


ST fiber ............................................................................................. 2-7, 3-12 defined .................................................................................................. 4-20
ST fiber connector .............................................................................. 3-13 menu .........................................................................................................7-7
Standards, certification ................................................................... 2-40 messages ................................................................................................7-7
Status LEDs ................................................................................. 4-42, 4-44 overview by device .......................................................................... 10-1
Stop blinking alarm ............................................................................ 4-35 settings .....................................................................................................5-5
Storage Media Alarm message .................................................. 7-12 TBD ........................................................................................................... 10-10
Storage, UR ...........................................................................................10-24 TCP port number for web access ............................................ 5-108
Substation D400 .................................................................................. 3-81 TDR Trouble message ....................................................................... 7-16
Support, technical ................................................................................. 1-2 Technical support ..................................................................................1-2
Surge immunity specifications .................................................... 2-39 files .................................................................................................1-2, 10-3
SV simulation settings ....................................................................5-426 Teleprotection
SV Stream Config message troubleshooting ....................5-224 actual values .........................................................................................6-6
SV Stream Config settings ...........................................................5-218 clearing counters ................................................................................7-2
stream filtering criteria ................................................................5-223 FlexLogic operands ...................................................................... 5-242
SV Stream Trouble On message ................................................ 7-13 logic diagram .................................................................................. 5-413
overview ............................................................................................ 5-412
Switch
settings .................................................................. 5-156, 5-412, 5-413
actual values ......................................................................................... 6-9
specifications ..................................................................................... 2-32
control with IEC 61850 ................................................................5-100
IEC 61850 Edition 1 and 2 ............................................................ 5-60
Temp Monitor message ................................................................... 7-13
settings ................................................................................ 5-175, 5-335 Temperature
Synchrocheck FlexLogic monitor operand ...................................................... 5-246
actual values ...................................................................................... 6-25 operating .............................................................................................. 2-38
FlexAnalogs ........................................................................................ A-20 Test voltages .......................................................................................... 3-15
FlexLogic operands .......................................................................5-242 Testing
logic diagram ...................................................................................5-350 force contact inputs ..................................................................... 5-423
settings ...............................................................................................5-346 force contact outputs .................................... 5-424, 5-426, 5-428
specifications ..................................................................................... 2-25 lamp test .................................................................................................7-3
Synchronize LEDs ...........................................................................................................7-3
clock using time source ................................... 5-118, 5-124, 6-32 over/underfrequency ........................................................................8-1
clocks of UR devices to local computer ..............................5-120 pushbuttons ..........................................................................................7-3
files between offline and online ................................................ 4-71 self-test error messages ..................................................................7-8
Synchronize Devices setting for clocks ...............................5-120 settings ............................................................................................... 5-420
Synchrophasors synchrophasors ............................................................................. 5-424
actual values .......................................................................... 6-27, 6-37 TFTP
clearing PMU records ........................................................................ 7-2 port, close ......................................................................................... 5-109
commands ............................................................................................. 7-5 put cannot be done ...................................................................... 5-109
explained ...........................................................................................5-190 settings ............................................................................................... 5-109
FlexLogic operands ........................................................ 5-240, 5-241 THD metering ........................................................................................ 6-24
phasor measurement configuration ...... 5-195, 5-207, 5-209 analog channel correspondence .......................................... 5-131
phasor measurement unit calibration .................................5-199 FlexAnalogs .........................................................................................A-14
phasor measurement unit recording ...................................5-206 specifications ..................................................................................... 2-30
test values .........................................................................................5-424 The URS file is part of a device folder ................................... 10-12
Syslog ......................................................................................................... 5-26 Thermal demand characteristic .............................................. 5-133
System and device information ................................................. 4-78 Thermal overload protection
System Exception message .......................................................... 7-13 logic diagram .................................................................................. 5-388
System Failure message .................................................................... 7-9 settings ............................................................................................... 5-385
System frequency .............................................................................5-160 specifications ..................................................................................... 2-25
System logs ............................................................................................ 5-26 Third Ethernet Fail
error message ................................................................................... 7-11
System requirements ....................................................................... 3-59
set alarm .............................................................................................. 5-40
System setup .......................................................................................5-159
Tilda on front panel ............................................................................ 4-18

T
T in single-line diagram ................................................................... 4-25
Tagged breaker in single-line diagram .................................. 4-25
Target Device Report button ........................................................ 3-79

xvi F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Time TxGOOSE
actual values ...........................................................................6-36, 6-37 actual values ...................................................................................... 6-14
FlexLogic timer settings ..............................................................5-253 settings ................................................................................................. 5-71
graphical front panel format .......................................................5-32 TxGOOSEa & TxGOOSEb assigned to PBM message ...... 5-75
operating ..............................................................................................6-39
overwritten by external source .................................................... 7-3
set .........................................................5-30, 5-118, 5-124, 6-32, 7-3 U
synchronize ........................................................... 5-118, 5-124, 6-32
UDP for TFTP ........................................................................................5-109
Time overcurrent
UL certification ..................................................................................... 2-40
see Phase, Neutral, and Ground TOCs
Unable to connect to relay ................................................ 3-72, 5-48
Time Sync settings ..............................................................................6-32
Unable to put relay in flash mode ...........................................10-16
To Install Settings message ............................................................. 7-9
Unauthorized access
TOC
commands .......................................................................................... 5-43
ground ................................................................................................5-293
resetting .........................................................................................7-2, 7-3
neutral .................................................................................................5-275
phase ...................................................................................................5-268
Underfrequency
FlexLogic operands .......................................................................5-243
specifications ......................................................................................2-20
logic diagram ...................................................................................5-343
Toolbar .......................................................................................................4-82
settings ...............................................................................................5-342
Torque for screws ........................................................2-40, 3-12, 3-23
specifications ..................................................................................... 2-23
Total harmonic distortion .............................................................. A-14
testing .......................................................................................................8-1
Traceability
Undervoltage
data .........................................................................................................4-14
auxiliary ................................................................................................ 2-22
overview ................................................................................................4-13
characteristics .................................................................................5-317
rules .........................................................................................................4-15
phase .......................................................................................2-22, 5-319
view data ..............................................................................................4-15
settings ...............................................................................................5-319
Tracking frequency .............................................................................6-26
Uninstall ..................................................................................................10-23
Transducer I/O
Unit Not Calibrated message ....................................................... 7-13
actual values .......................................................................................6-29
Unit not programmed .......................................................... 5-157, 7-9
settings ...............................................................................................5-414
Unpacking the relay .............................................................................3-1
specifications ......................................................................................2-31
wiring ......................................................................................................3-34
Unreturned messages alarm .....................................................5-156
Transfer files to relay .........................................................................10-7 Update SCL files prompt ................................................................. 4-71
Transfer files with USB drive ..........................................................4-18 Update settings with Convert Device Settings .................. 10-5
Transient ground fault detection Updates
bootloader .........................................................................................10-15
FlexLogic operands .......................................................................5-243
device not recognized ..................................................................10-14
settings ...............................................................................................5-283
firmware .............................................................................................10-15
specifications ......................................................................................2-26
firmware lock ................................................. 3-75, 5-11, 5-23, 5-25
Triangle in Offline Window .............................................................4-71
FPGA .....................................................................................................10-17
Trip bus
instruction manual .............................................................................3-1
FlexLogic operands .......................................................................5-242
order code ..............................................................................................7-3
logic diagram ...................................................................................5-333
single-line diagrams not retained ............................................ 4-26
settings ...............................................................................................5-331
software .............................................................................................10-14
Trip LEDs ................................................................................................5-137
Upgrade device settings ................................................................. 10-5
Trouble indicator .................................................................................... 7-8
Upgrade over Internet message ..............................................10-16
Trouble LED .............................................................................................3-57
Upload settings to relay .................................................................. 10-7
Troubleshooting
URS file does not include IEC 61850 configuration .......10-12
access to device ................................................................................3-72
URS file is part of a device folder .............................................10-12
breaker not working .....................................................................5-357
connection ...........................................................................................5-48
URS settings file ........................................................... 3-80, 5-63, 10-9
dark graphical front panel ............................................................5-34 USB port
Engineer ....................................................................................4-72, 4-73 graphical front panel ........................................................4-18, 5-117
error messages .................................................................................... 7-8 Quick Connect ................................................................................... 3-74
setting not working .......................................................................5-357 specifications ..................................................................................... 2-35
SV Stream Config window .........................................................5-224 USB to serial converter .................................................................... 3-68
unit not programmed error ......................................................5-157
Turn off alarm ........................................................................................4-35

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL xvii


INDEX

User accounts VT fuse failure


add .......................................................................................................... 5-15 FlexAnalogs .........................................................................................A-26
authentication by device or server .......................................... 5-17 FlexLogic operands ...................................................................... 5-241
multiple login limitation CyberSentry ........................................ 2-4 logic diagram .................................................................................. 5-384
passwords for settings and commands ....... 4-61, 5-10, 5-11 settings ............................................................................................... 5-383
permissions by role ............................................................................ 2-4 VT inputs ............................................................... 3-17, 3-18, 5-7, 5-159
permissions, set ................................................................................ 5-15 VT wiring ................................................................................................... 3-18
User-definable displays VTFF .............................................................................................. 5-383, A-26
example ..............................................................................................5-149
invoking and scrolling ..................................................................5-148
settings ...............................................................................................5-148
W
specifications ..................................................................................... 2-27
Warning messages in Engineer .................................................. 4-73
User-programmable LEDs
custom labels .................................................................................... 4-45
Warning symbol in Offline Window .......................................... 4-71
defaults ................................................................................................. 4-43 Warning, firmware upload not supported ......................... 10-16
settings ...............................................................................................5-137 Warranty .................................................................................................... D-1
specifications ..................................................................................... 2-27 Watt-hour
User-programmable pushbuttons actual values ...................................................................................... 6-22
FlexLogic operands .......................................................................5-246 specifications ..................................................................................... 2-29
graphical front panel buttons 9 to 16 .................................... 4-31 Wattmetric zero-sequence directional
logic diagrams .................................................................................5-146 actual values ...................................................................................... 6-27
settings ...............................................................................................5-141 FlexLogic operands ...................................................................... 5-243
specifications ..................................................................................... 2-27 logic diagram .................................................................................. 5-292
testing ...................................................................................................... 7-3 settings ............................................................................................... 5-288
User-programmable self-test settings .................................5-139 specifications ..................................................................................... 2-22
Waveform
view in actual values window .................................................... 6-36
view in event record ....................................................................... 6-34
V Waveform files, view ......................................................................... 4-82
VAR hour Web access port ............................................................................... 5-108
actual values ...................................................................................... 6-22 Web server protocol ....................................................................... 5-108
specifications ..................................................................................... 2-29 Windows 10
Vibration testing specifications .................................................. 2-39 disconnect USB cable when upgrading ............................. 10-14
Virtual inputs driver for USB to serial cable ...................................................... 3-68
actual values ......................................................................................... 6-5 Windows requirement ...................................................................... 3-59
commands ............................................................................................. 7-2 Wire size
explained ...........................................................................................5-402 CT/VT ...................................................................................................... 3-18
FlexLogic operands .......................................................................5-243 F485 converter .................................................................................. 3-59
logic diagram ...................................................................................5-403 G.703 and fiber interface .............................................................. 3-51
settings ...............................................................................................5-402 G.703 interface .................................................................................. 3-44
Virtual outputs module 7S ............................................................................................ 3-44
actual values ......................................................................................... 6-7 modules 6X, 6W ................................................................................ 3-23
explained ...........................................................................................5-407 modules 7E, 7F, 7G, 7Q, 75 ........................................................... 3-51
FlexLogic operands .......................................................................5-243 modules 7L, 7M, 7N, 7P, 74 .......................................................... 3-50
settings ...............................................................................................5-407 modules 7T, 7W ................................................................................ 3-48
Voltage banks .....................................................................................5-159 power supply module ..................................................................... 3-16
Voltage deviation specifications ................................................ 2-39 RS422 and fiber interface ............................................................. 3-50
Voltage elements ..............................................................................5-317 RS422 interface ................................................................................. 3-48
FlexElement is phase to ground .............................................5-257 Wiring diagram ..................................................................................... 3-14
Voltage metering Withdraw UR from operation .................................................... 10-23
actual values ...................................................................................... 6-20 Wrong Transceiver message ....................................................... 7-14
specifications ..................................................................................... 2-29
Voltage Monitor message .............................................................. 7-13
Voltage restraint characteristic ................................................5-269
X
XOR gate explained ............................................................................ 4-85

xviii F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL


INDEX

Y
Yellow caution icon in Offline Window ....................................4-71

Z
Zero-sequence core balance ........................................................3-18

F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL xix


INDEX

xx F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL

You might also like