API Sizing KIM - XLSM
API Sizing KIM - XLSM
API Sizing KIM - XLSM
Location
RESULTS mm
Width of separator in feet 1.50 457
Depth of separator in feet 2.00 610
Length of separator in feet 10.63 3240
Minimum Maximum
Allowable Design Allowable
Result Result
terminal velocity (in cm/s) 0.36 0.36 0.36
terminal velocity (in ft/min) 0.72 0.72 0.72
Minimum cross sectional area needed (in ft) 2.90 2.90 2.90
Cross Sectional Area (in square feet) 2.90 3.00 160.00
maximum horizontal velocity (15*vt, but must be <=3) 3.00 3.00 3.00
horizontal velocity (in ft/min) 3.00 2.90 0.05
vh/vt 4.19 4.05 0.08
short-circuiting factor 1.32 1.31 1.17
Length of unit (must be at least 5X of width) (in ft) 5.00 10.63 100.00
length/width 5.00 7.09 5.00
minimum horizontal area 16.00 15.94 14.25
Width of channel (in feet) (must be 6 to 20) 1.00 1.50 20.00
Depth (in feet) 0.30 2.00 10.00
Depth/Width Ratio (must be .3 to .5) 0.30 1.33 0.50
Step 1:
Adjust the width and depth of the chanel until you
achieve a horizontal velocity <=3. Ideal horizontal
velocity should be in the <=2 range at average flow.
Make sure that you maintain a depth/width ratio of .3 to
.5