Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

CYBERPOWER UPS (OLS1000E-EXL-1500E-EXL-2000E-EXL-3000E-EXL) User's Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

User’s Manual

OLS1000E/EXL
OLS1500E/EXL
OLS2000E/EXL
OLS3000E/EXL

CyberPower Systems Inc.


www.cyberpower.com

K01-C000243-02

 
 
  IMPORTANT SAFETY INSTRUCTIONS

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.

CAUTION! The UPS must be connected to a grounded AC cause damage to your equipment and cause fire hazards.
power outlet with fuse or circuit breaker protection. DO NOT
CAUTION! Wiring must be done by qualified personnel.
plug the UPS into an outlet that is not grounded. If you need to
power-drain this equipment, turn off and unplug the unit. CAUTION! DO NOT USE FOR MEDICAL OR LIFE
SUPPORT EQUIPMENT! Under no circumstances this unit
CAUTION! The battery can power hazardous components
should be used for medical applications involving life support
inside the unit, even when the AC input power is disconnected.
equipment and/or patient care.
CAUTION! The UPS should be placed near the connected
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!
equipment and easily accessible.
To reduce the risk of fire, do not use with or near aquariums.
CAUTION! To prevent the risk of fire or electric shock, install Condensation from the aquarium can come in contact with
in a temperature and humidity controlled indoor area, free of metal electrical contacts and cause the machine to short out.
conductive contaminants. (Please see specifications for
CAUTION! Do not dispose of batteries in fire as the battery
acceptable temperature and humidity range).
may explode.
CAUTION! (No User Serviceable Parts): Risk of electric
CAUTION! Do not open or mutilate the battery, released
shock, do not remove cover. No user serviceable parts inside.
electrolyte is harmful to the skin and eyes.
Refer servicing to qualified service personnel.
CAUTION! A battery can present a risk of electric shock and
CAUTION! (Non-Isolated Battery Supply): Risk of electric
high short circuit current. The following precaution should be
shock, battery circuit is not isolated from AC power source;
observed when working on batteries
hazardous voltage may exist between battery terminals and
ground. Test before touching. 1. Remove watches, rings or other metal objects.
CAUTION! To reduce the risk of fire, connect the UPS to a 2. Use tools with insulated handles.
branch circuit with 10 amperes (OLS1000 / OLS1500) / 16
CAUTION! The unit has a dangerous amount of voltage.
amperes (OLS2000/ OLS3000) maximum over-current
When the UPS indicators is on, the units may continue to
protection in accordance to CE requirement.
supply power thus the unit’s outlets may have a dangerous
CAUTION! The AC outlet where the UPS is connected should amount of voltage even when it’s not plugged in to the wall
be close to the unit and easily accessible. outlet.
CAUTION! Please use only VDE-tested, CE-marked mains CAUTION! Make sure everything is turned off and
cable, (e.g. the mains cable of your equipment), to connect the disconnected completely before conducting any maintenance,
UPS to the AC outlet. repairs or shipment.
CAUTION! Please use only VDE-tested, CE-marked power CAUTION! Connect the Protection Earth (PE) safety
cables to connect any equipment to the UPS. conductor before any other cables are connected.
CAUTION! When installing the equipment, ensure that the WARNING! (Fuses): To reduce the risk of fire, replace only
sum of the leakage current of the UPS and the connected with the same type and rating of fuse.
equipment does not exceed 3.5mA.
DO NOT INSTALL THE UPS WHERE IT WOULD BE
CAUTION! The OLS1000 / OLS1500 / OLS2000 / OLS3000 / EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG
Battery module models are only qualified maintenance HEAT SOURCE!
personnel may carry out installations.
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND
CAUTION! Do not unplug the unit from AC Power during THE HOUSING!
operation, as this will invalidate the protective ground
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS
insulation.
HAIR DRYERS TO UPS OUTPUT SOCKETS!
CAUTION! To avoid electric shock, turn off and unplug the
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
unit before installing the input/output power cord with a ground
SUPERVISED BY PERSONNEL KNOWLEDGE OF
wire. Connect the ground wire prior to connecting the line
BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP
wires!
UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
CAUTION! Do not use an improper size power cord as it may

 
1
  UNPACKING

USB communication cable

Input power cord


UPS PS: The input powercord of OLS2000E can not be used for
other products.

User’s manual Output power cords x2pcs

PowerPanel® Business Edition software is available on our


website. Please visit www.cyberpower.com and go to the
Software Section for free download.
Phone line

 
2
  INSTALLING YOUR UPS SYSTEM

SYSTEM BLOCK DIAGRAM

HARDWARE INSTALLATION GUIDE


1. Battery charge loss may occur during shipping and storage. 7. To maintain an optimal battery charge, leave the UPS
Before using the UPS, it’s strongly recommended to charge plugged into an AC outlet at all times.
batteries for four hours to ensure the batteries’ maximum
8. Before storing the UPS for an extended period of time, turn
charge capacity. To recharge the batteries, simply plug the UPS
the unit OFF. Then cover it and store it with the batteries fully
into an AC outlet.
charged. Recharge the batteries every three months to ensure
2. When using the included software, connect either the serial good battery capacity and long battery life. Maintaining a good
or the USB cable between the computer and the corresponding battery charge will help prevent possible damage to the unit
port on the UPS. Note: If the USB port is used, the serial port from battery leakage.
will be disabled. They cannot be used simultaneously.
9. The UPS has one USB port (default) and one Serial port that
3. Connect your computer, monitor, and any allows connection and communication between the UPS and
externally-powered data storage device (Hard drive, Tape drive, any attached computer running the PowerPanel® Business
etc.) into the outlets only when the UPS is off and unplugged. Edition Agent software. The UPS can control the computer’s
DO NOT plug a laser printer, copier, space heater, vacuum, shutdown during a power outage through the connection while
paper shredder or other large electrical device into the UPS. the computer can monitor the UPS and alter various
The power demands of these devices will overload and programmable parameters. Note: Only one communication port
possibly damage the unit. can be used at a time. The port not in use will automatically
become disabled or the serial port will be disabled if both ports
4. To protect a fax machine, telephone, modem line or network
are attached.
cable, connect the telephone or network cable from the wall
jack outlet to the jack marked “IN” on the UPS and connect a 10. EPO (Emergency Power Off) / ROO(Remote on/off) Port:
telephone cable or network cable from the jack marked “OUT” EPO/ROO ports allow administrators the capability to connect
on the UPS to the modem, computer, telephone, fax machine, the UPS unit to customer-supplied EPO/ROO switches. If EPO
or network device. is enabled, these installations give operators a single access
5. Press the ON switch to turn the UPS on. If an overload is point to immediately power-off all equipment connected to the
detected, an audible alarm will sound and the UPS will UPS during an emergency. If ROO is enabled, these
continuously emit one beep per second. For resetting the unit, installations give operators a access point to turn on/off UPS
unplug some equipment from the outlets. Make sure your remotely.
equipment carries a load current within the unit’s safe range,
11. To avoid electric shock, turn the unit OFF and disconnect
(refer to the technical specifications).
the unit from utility power before hardwiring the UPS (in/out
6. This UPS is equipped with an auto-charge feature. When the power cord). The in/out power cord MUST be grounded.
UPS is plugged into an AC outlet, the battery will automatically
charge, even when the unit is switched off.

 
3
  BASIC OPERATION

POWER MODULE FRONT/REAR PANEL DESCRIPTION


1. Power On/Off Button
Master ON/OFF for the UPS.
2. Function Buttons
Scroll up, scroll down, select and cancel LCD
menu.
3. Multifunction LCD Readout
Indicate status information, settings and events.
4. Input Circuit Breaker
Provide input overload and fault protection.
5. Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection.
They ensure power is provided to connected
OLS1000E/EXL, OLS1500E/EXL OLS1000E/EXL, OLS1500E/EXL
equipment over a period of time during a power
failure.
6. Serial Port
Serial port provides communication between the
UPS and the computer. The UPS can control the
computer’s shutdown during a power outage
through the connection while the computer can
monitor the UPS and alter its various
programmable parameters.
7. USB port
This is a connectivity port which allows
communication and control between the UPS
and the connected computer. It is recommended
to install the PowerPanel® Business Edition
Agent software on the PC/Server connected
with the USB cord.
8. Surge Protected Communication Ports
RJ-45/RJ-11 OLS2000E/EXL, OLS3000E/EXL OLS2000E/EXL
These ports are used to protect standard
RJ-45/RJ-11 based products (ADSL, LAN,
Phone/ Modem-Lines) and cabling systems from
surges.
9. SNMP/HTTP Network slot
Slot to install the optional SNMP card for remote
network control and monitoring.
10. Extended Runtime Battery Module
Connector
Connect to additional external battery modules.
11. EPO (Emergency Power Off) Connector
Enable Power-Off in emergency from a remote
location.
12. AC Input Inlet
Connect the AC Power cord to a properly wired
and grounded outlet.
OLS3000E/EXL
13. Output Terminal Block
Connect to your equipment.

 
4
  BASIC OPERATION

BATTERY MODULE FRONT/REAR PANEL DESCRIPTION


1. Input Connector
Use this input connector to daisy chain the next
Battery module. Remove the connector cover
for access.
2. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear
panel. It must be done by qualified personnel.
3. Output Connector
Use this output Connector to connect the
Battery module to the Power module or to the
next Battery module.

BPSE36V45A

BPSE72V45A

 
5
  BASIC OPERATION

CONNECTION #1 : POWER MODULE WITH ONE BATTERY MODULE


Step 1: Loosen the two screws to remove the battery
cable retention bracket of the power module.

Step 2: Use the battery cable of the Battery module to


connect the Battery module to the Power
module.

Step 3: Rotate the battery cable retention bracket and


tighten the two screws to fix battery cable.

 
6
  BASIC OPERATION

CONNECTION #2 : POWER MODULE WITH MULTIPLE BATTERY MODULES


Step 1: Connect the 1st Battery module to the Power
module using battery cable.

Step 2: Loosen the two screws to remove the battery


cable retention bracket of the 1st battery module.

Step 3: Use the battery cable to connect the 2nd Battery


module to the 1st Battery module.

Step 4: Rotate the battery cable retention bracket and


tighten the two screws to fix battery cable.

 
7
  BASIC OPERATION

LCD SCREEN – UPS STATUS

LCD Screen UPS Status Description

UPS is operating in Line Mode.

UPS is operating in Battery Mode.

UPS is operating in Bypass Mode.

UPS is operating in ECO (Economy) Mode.*

UPS is operating in Converter Mode when this icon blinking**.

*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode, but transfer time should not be 0ms
**) When operating in Converter Mode, the frequency of output should be always 50Hz or 60Hz, but load capacity will be
derated.

DEFINITIONS FOR OTHER ICONS

LCD Screen Description

LOAD capacity: This meter displays the approximate output


load level (in 20% increments) of the UPS outlets.

BATTERY capacity: This meter displays the approximate


charge level (in 20% increments) of the UPS’s internal
battery. During a blackout or severe brownout, the UPS
switches to battery power, the BATTERY icon appears, and
the charge level decreases.
MUTE: This icon appears whenever the UPS is in silent
mode. The alarm does not beep during silent mode until the
battery reaches low capacity.
SCHEDULE: Users can setup the schedule to turn on and
shut down the computer and UPS through PowerPanel®
Personal Edition software. The LCD display will show how
much time is left before the UPS will turn back on or shut
down.
OVER LOAD: This icon appears and an alarm sounds to
indicate the outlets are overloaded. To clear the overload,
unplug some of your equipment from the battery-supplied
outlets until the icon turns off and the alarm stops.

FAULT: This icon appears if there is a problem with the UPS.


Please refer to “Event ID Descriptions”.

 
8
  BASIC OPERATION

REPLACE: This icon appears if the batteries need to be


replaced.

Event ID Descriptions

Event ID Description of Cause

1 Bus Start Fail: DC-DC converter or bus sensing circuit failed.


2 Bus Volt High: DC-DC converter failed.
3 Bus Volt Low: DC-DC converter failed.
4 Bus Unbalanced: DC-DC converter failed.
5 INV Start Fail: Inverter circuit failed.
INV Volt High: Inverter circuit or output voltage sensing
6 circuit failed.
INV Volt Low: The load may be too heavy or inverter circuit
7 failed.
8 INV Short: The inverter circuit failed.
Bat Volt High: The external battery module connection is
9 wrong, or the charger failed.
10 Bat Volt Low: Batteries failed.
Over Temperature: High ambient temperature, or the
11 ventilation hole has been covered.
12 Over Load: UPS is overloaded.
High Temperature: High ambient temperature, or the
54 ventilation hole has been covered. This is shown only when
start up UPS.
55 Bat Low: Battery voltage is too low to DC start UPS.
57 EPO Off: Missing the EPO connection
Fan Fail: The ventilation hole has been covered, or the fans
58 can’t work.
59 Bat Bad: Battery failed.

BUTTON OPERATION

Button Operation Description

ON Press this button to turn on UPS.


OFF Press this button to turn off UPS.*
Press this button to scroll up in the LCD menu.
Press this button simultaneously for 5 seconds to disable or
enable the alarm system while in battery mode.
Press this button simultaneously for 5 seconds to enter UPS
ENTER/▲ self-testing while in AC mode, ECO mode, or converter mode.
In setting mode, press this button to confirm selection, or
press this button for long time to exit setting mode and saving
changes.
Press this button to scroll down in the LCD menu.
Press this button for long time to get into setting mode
ESC/▼ In setting mode, press this button to display next selection, or
press this button for long time to exit setting mode without
saving changes.
Switch to bypass mode: When the main power is normal,
ENTER/▲ + ESC/▼ press these two buttons simultaneously for 5 seconds, then
UPS will enter to bypass mode.

*) If utility power is connected,UPS will keep charging but cut off output.

 
9
  LCD SETUP FUNCTIONS

LCD INFORMATION READOUT


There are 12 types of UPS information available for display on digit area.
Information Submenu Description

OUTPUT XXX V Displays the Output Voltage

OUTPUT XX.XHz Displays the Output Frequency

OUTPUT XXX (k)VA Displays the Output VA

OUTPUT XXX% VA Displays the Output Load Percentage of Maximum Apparent Power

OUTPUT XXX (k)W Displays the Output Wattage

OUTPUT XXX% W Displays the Output Load Percentage of Maximum Active Power

INPUT XXX V Displays the Input Voltage

EVENT XXX Displays the Event ID


ESTIMATED RUN TIME
Displays the Estimated Percentage of Battery Capacity
%
ESTIMATED RUN TIME
Displays the Estimated Run Time with battery
XX(.)X [Min][Hr]
TIME TO SHUT DOWN
Displays the Time Delay to Shutdown UPS
XX(.)X [Min][Hr]
TIME TO TURN ON
Displays the Time Delay to Restart UPS
XX(.)X [Min][Hr]

LCD SETTINGS CONFIGURATION


There are 8 UPS settings that can be configured by the user.
1. Press the “ESC” button simultaneously for 5 seconds to activate the setting mode.
The first configuration parameter will be displayed on the LCD screen.
Note: The manual settings programming mode can ONLY be invoked while UPS is in Bypass mode or Standby mode. To
make UPS on Standby mode or Bypass mode, connect utility power to UPS and do not turn on UPS.
2. Press the “ENTER” button to select the setting you want to configure.
3. Press the “▼” buttons to scroll through the different parameters.
Press the “ENTER” button to select the parameter you want.
4. Press the “ESC” button simultaneously for 5 seconds to cancel and exit setting mode. Press the “ENTER” button
simultaneously for 5 seconds to save all the settings you just do and exit setting mode.

 
10
  LCD SETUP FUNCTIONS

Configure Submenu Available Settings Default Setting

Output Voltage = [208V] [220V] [230V] [240V] 230V

Output Frequency = [50Hz][60Hz] 50Hz

ECO Mode * [0%] (Disable) [10%][15%] (Enable) 0%

Bypass Mode ** [DIS] (Disable) [ENA] (Enable) Enable

Converter Mode [DIS] (Disable) [ENA] (Enable) Disable

EPO/ROO*** [EPo] [Roo] EPO

[0bP]/[1bP]/[2bP]/[3bP]/[4bP]/[5bP]/[6bP]/[7bP]/[8bP]/[9bP]
EBM Number**** /[AbP]
0(for –E models) / 1 (for –EXL models)

Bypass when UPS


[F1d](Disable) [F1E](Enable) Disable
is Off
*) This function would be set as 0% when Converter Mode is enabled. icon is lighting during setting ECO mode.
**) UPS has no bypass when Converter Mode is enabled. icon is lighting during setting bypass mode.
*** ROO (Remote On/Off): If ROO is enabled, UPS can be turn on/off by the ROO port. If ROO port is disconnected, UPS
will be turned off. If ROO port is connected, UPS will be turned on when the utility is normal
****) 1. UPS cannot detect the numbers of external battery automatically, so manual input from user is necessary.
2. For –E models, the maximum number is 3. Option [AbP] means 10.

SILENCING AUDIBLE ALARMS


Press the “ENTER” button on simultaneously for 5 seconds to disable or enable the alarm system while in battery mode.
Note: Some audible alarms (Over Temperature, Fan Fail, etc.) can’t be silenced.

MANUAL BATTERY TEST


Press the “ENTER” button simultaneously for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or
converter mode.

 
11
  MAINTENANCE

Storage CAUTION! To avoid electric shock, turn off and unplug the
To store your UPS for an extended period, cover it and store UPS from the wall receptacle before servicing the battery.
with the battery fully charged. Recharge the battery every CAUTION! Only use tools with insulated handles. Do not
three months to ensure battery life. lay tools or metal parts on top of the UPS or battery terminals.
Safety Precautions Replacement Batteries
CAUTION! Only use replacement batteries which are Please refer to the front side of the UPS for the model
certified by CyberPower Systems. Use of incorrect battery number of the correct replacement batteries. For battery
type is an electrical hazard that could lead to explosion, fire, procurement, log onto www.cyberpower.com, or contact your
electric shock, or short circuit. local dealer.
CAUTION! Batteries contain an electrical charge that can
Battery Disposal
cause severe burns. Before servicing batteries, please
Batteries are considered hazardous waste and must be
remove any conductive materials such as jewelry, chains,
disposed of properly. Contact your local government for more
wrist watches, and rings.
information about proper disposal and recycling of batteries.
Do not dispose of batteries in fire.
CAUTION! Do not open or mutilate the batteries.
Electrolyte fluid is harmful to the skin/eyes and may be toxic.

 
12
  TECHNICAL SPECIFICATIONS

Model OLS1000E/EXL OLS1500E/EXL OLS2000E/EXL OLS3000E/EXL


Configuration
Capacity (VA) 1000VA 1500VA 2000VA 3000VA
Capacity (Watts) 900W 1350W 1800W 2700W
Form Factor Tower
Energy-saving Technology Yes, ECO Mode Efficiency ≧95%
Input
110~130Vac± 5% for 1000 / 1500 / 2000 VA model
@ 0~50% Load ± 5%
110~140Vac± 5% for 3000 VA only
120~140Vac± 5% for 1000 / 1500 / 2000 VA model
@ 0~60% Load± 5%
140~160Vac± 5% for 3000 VA only
Input Voltage Range
140~160Vac± 5% for 1000 / 1500 / 2000 VA model
@ 0~80% Load± 5%
160~190Vac± 5% for 3000 VA only
160~300Vac± 5% for 1000 / 1500 / 2000 VA model
@ 0~100% Load± 5%
190~300Vac± 5% for 3000 VA only
Input Frequency Range 40~70Hz
Input Power Factor 0.98
Cold Start Yes
Output
Output Waveform Pure Sine Wave
Output Voltage 208, 220, 230, 240Vac ±1%
Output Frequency 50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz *
Transfer Time (Typically) 0ms
Rated Power Factor 0.9
Harmonic Distortion THD < 3% at Linear Load, < 5% at Non-linear Load @ Nominal Input
Crest Factor 3:1
ECO Mode Voltage
±10%, ±15% (Configurable)
Regulation
(2+2) IEC C13
(2+2) IEC C13
UPS Outlets (4) IEC C13 (1) IEC C19
(1) Terminal Block
(1) Terminal Block
Protection
Surge Protection IEC 61000-4-5 Level 4
Phone / Network Protection RJ11/RJ45 (One In/One Out)
Line Mode: 105~110% Overload warning only (No shutdown)
, 110~120% Warning, transfer to bypass after 60s
>120% Transfer to bypass immediately
Overload Protection
Battery Mode: 105~110% Overload warning only (No shutdown)
, 110~120% Warning, shutdown after 10s
>120% Shutdown immediately
Short Circuit Protection UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection

Battery
(3) 12V/7AH (3) 12V/9AH (6) 12V/7AH (6) 12V/9AH
Specifications
For -EXL Models, NO Battery Inside.
Recharge Time (Typically) 4 Hours (inside batteries)
Sealed, Maintenance Free Yes
Status Indicators
LCD Screen Graphic LCD
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Audible Alarms Charger Failure /Over Charged, Fan failure, EPO active
Environment
Operating Temperature 32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity 20 to 90% Non-Condensing
Management
On-Device Features Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports (1) Serial Port (RS232), (1) USB Port,
SNMP/HTTP Capable (1) Expansion Port (With optional RMCARD 205)

 
13
  TECHNICAL SPECIFICATIONS

Software
Power Management
Software PowerPanel® Business Edition
Physical
D×W×H = 15.51 x 5.94 x 8.86in. D×W×H = 16.38 x 7.72 x 13.28in.
Dimensions
(394×151×225 mm) (416×196×337 mm)
28.9/17.0lbs 33.7/17.2lbs 52.5/26.9lbs 62.2/27.8lbs
Net Weight
(13.1/7.7Kg) (15.3/7.8Kg) (23.8/12.2Kg) (28.2/12.6Kg)
Safety
Conformance Approvals CE

*) Within 50/60Hz±8% by default, the output frequency is synchronization with input mains. User can adjust the acceptable range for
output frequency (±1, 2, 3, 4, 5, 6, 7, 8, 9, 10%). When input frequency is out of synchronization window but within 40-70Hz, UPS
can stay in line mode and output frequency is regulated at 50/60Hz+0.5% with load derating by 40%.

 
14
  TROUBLE SHOOTING

Problem Possible Cause Solution


Warning
Your equipment requires more power than the
Shut off non-essential equipment. If this solves
UPS can provide. If the UPS is in Line Mode
O/P Overload the overload problem, the UPS will transfer to
then it will transfer to Bypass Mode; if the UPS is
normal operation.
in Battery Mode it will shutdown.

Save your data and perform a controlled-


Battery Mode UPS is operating on battery power.
shutdown.
UPS is operating on battery power and will be
UPS will restart automatically when acceptable
Battery Low shutting down soon due to extremely low battery
utility power returns.
voltage.

Check battery connector when use battery


Missing battery power.
BAT Disconnected/ packages.
Battery Replace
UPS has failed in Battery Test. Contact technical support to replace the battery.

1. Shut down UPS and turn off AC input.


Charger Failure Charger has failed.
2. Contact CyberPower for repair.

EPO OFF Missing the EPO connection. Check the EPO connection.

Fault
1. Shut down UPS. Restart UPS to Check the
fan for operation and if the ventilation hole has
Over Temperature High ambient temperature.
been covered
2. Contact CyberPower for repair.

1. Shut down UPS


Output Short Output short circuit. 2. Your attached equipment may have problems,
please remove them and check again.

High O/P V Output voltage is too high.


1. Shut down UPS
Low O/P V Output voltage is too low.
2. Contact CyberPower for repair.
Bus Fault Internal DC bus voltage is too high or too low.
Other
1. Restart UPS and press the “▼” button to
High temperature, or fan fail, or battery low, or view the warning event. Then refer to the solution
Startup fail
EPO off.. for the warning.
2. Contact CyberPower for repair.

CyberPower Systems Inc.


www.cyberpower.com
6F, No. 32, Sec. 1, Chenggong Rd., Nangang District, Taipei 115, Taiwan
Entire contents copyright© 2016 CyberPower Systems Inc., All rights reserved. Reproduction in whole or in part without
permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal Edition are trademarks of
CyberPower Systems Inc.

 
15

You might also like