CYBERPOWER UPS (OLS1000E-EXL-1500E-EXL-2000E-EXL-3000E-EXL) User's Manual
CYBERPOWER UPS (OLS1000E-EXL-1500E-EXL-2000E-EXL-3000E-EXL) User's Manual
CYBERPOWER UPS (OLS1000E-EXL-1500E-EXL-2000E-EXL-3000E-EXL) User's Manual
OLS1000E/EXL
OLS1500E/EXL
OLS2000E/EXL
OLS3000E/EXL
K01-C000243-02
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC cause damage to your equipment and cause fire hazards.
power outlet with fuse or circuit breaker protection. DO NOT
CAUTION! Wiring must be done by qualified personnel.
plug the UPS into an outlet that is not grounded. If you need to
power-drain this equipment, turn off and unplug the unit. CAUTION! DO NOT USE FOR MEDICAL OR LIFE
SUPPORT EQUIPMENT! Under no circumstances this unit
CAUTION! The battery can power hazardous components
should be used for medical applications involving life support
inside the unit, even when the AC input power is disconnected.
equipment and/or patient care.
CAUTION! The UPS should be placed near the connected
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!
equipment and easily accessible.
To reduce the risk of fire, do not use with or near aquariums.
CAUTION! To prevent the risk of fire or electric shock, install Condensation from the aquarium can come in contact with
in a temperature and humidity controlled indoor area, free of metal electrical contacts and cause the machine to short out.
conductive contaminants. (Please see specifications for
CAUTION! Do not dispose of batteries in fire as the battery
acceptable temperature and humidity range).
may explode.
CAUTION! (No User Serviceable Parts): Risk of electric
CAUTION! Do not open or mutilate the battery, released
shock, do not remove cover. No user serviceable parts inside.
electrolyte is harmful to the skin and eyes.
Refer servicing to qualified service personnel.
CAUTION! A battery can present a risk of electric shock and
CAUTION! (Non-Isolated Battery Supply): Risk of electric
high short circuit current. The following precaution should be
shock, battery circuit is not isolated from AC power source;
observed when working on batteries
hazardous voltage may exist between battery terminals and
ground. Test before touching. 1. Remove watches, rings or other metal objects.
CAUTION! To reduce the risk of fire, connect the UPS to a 2. Use tools with insulated handles.
branch circuit with 10 amperes (OLS1000 / OLS1500) / 16
CAUTION! The unit has a dangerous amount of voltage.
amperes (OLS2000/ OLS3000) maximum over-current
When the UPS indicators is on, the units may continue to
protection in accordance to CE requirement.
supply power thus the unit’s outlets may have a dangerous
CAUTION! The AC outlet where the UPS is connected should amount of voltage even when it’s not plugged in to the wall
be close to the unit and easily accessible. outlet.
CAUTION! Please use only VDE-tested, CE-marked mains CAUTION! Make sure everything is turned off and
cable, (e.g. the mains cable of your equipment), to connect the disconnected completely before conducting any maintenance,
UPS to the AC outlet. repairs or shipment.
CAUTION! Please use only VDE-tested, CE-marked power CAUTION! Connect the Protection Earth (PE) safety
cables to connect any equipment to the UPS. conductor before any other cables are connected.
CAUTION! When installing the equipment, ensure that the WARNING! (Fuses): To reduce the risk of fire, replace only
sum of the leakage current of the UPS and the connected with the same type and rating of fuse.
equipment does not exceed 3.5mA.
DO NOT INSTALL THE UPS WHERE IT WOULD BE
CAUTION! The OLS1000 / OLS1500 / OLS2000 / OLS3000 / EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG
Battery module models are only qualified maintenance HEAT SOURCE!
personnel may carry out installations.
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND
CAUTION! Do not unplug the unit from AC Power during THE HOUSING!
operation, as this will invalidate the protective ground
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS
insulation.
HAIR DRYERS TO UPS OUTPUT SOCKETS!
CAUTION! To avoid electric shock, turn off and unplug the
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
unit before installing the input/output power cord with a ground
SUPERVISED BY PERSONNEL KNOWLEDGE OF
wire. Connect the ground wire prior to connecting the line
BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP
wires!
UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
CAUTION! Do not use an improper size power cord as it may
1
UNPACKING
2
INSTALLING YOUR UPS SYSTEM
3
BASIC OPERATION
4
BASIC OPERATION
BPSE36V45A
BPSE72V45A
5
BASIC OPERATION
6
BASIC OPERATION
7
BASIC OPERATION
*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode, but transfer time should not be 0ms
**) When operating in Converter Mode, the frequency of output should be always 50Hz or 60Hz, but load capacity will be
derated.
8
BASIC OPERATION
Event ID Descriptions
BUTTON OPERATION
*) If utility power is connected,UPS will keep charging but cut off output.
9
LCD SETUP FUNCTIONS
OUTPUT XXX% VA Displays the Output Load Percentage of Maximum Apparent Power
OUTPUT XXX% W Displays the Output Load Percentage of Maximum Active Power
10
LCD SETUP FUNCTIONS
[0bP]/[1bP]/[2bP]/[3bP]/[4bP]/[5bP]/[6bP]/[7bP]/[8bP]/[9bP]
EBM Number**** /[AbP]
0(for –E models) / 1 (for –EXL models)
11
MAINTENANCE
Storage CAUTION! To avoid electric shock, turn off and unplug the
To store your UPS for an extended period, cover it and store UPS from the wall receptacle before servicing the battery.
with the battery fully charged. Recharge the battery every CAUTION! Only use tools with insulated handles. Do not
three months to ensure battery life. lay tools or metal parts on top of the UPS or battery terminals.
Safety Precautions Replacement Batteries
CAUTION! Only use replacement batteries which are Please refer to the front side of the UPS for the model
certified by CyberPower Systems. Use of incorrect battery number of the correct replacement batteries. For battery
type is an electrical hazard that could lead to explosion, fire, procurement, log onto www.cyberpower.com, or contact your
electric shock, or short circuit. local dealer.
CAUTION! Batteries contain an electrical charge that can
Battery Disposal
cause severe burns. Before servicing batteries, please
Batteries are considered hazardous waste and must be
remove any conductive materials such as jewelry, chains,
disposed of properly. Contact your local government for more
wrist watches, and rings.
information about proper disposal and recycling of batteries.
Do not dispose of batteries in fire.
CAUTION! Do not open or mutilate the batteries.
Electrolyte fluid is harmful to the skin/eyes and may be toxic.
12
TECHNICAL SPECIFICATIONS
Battery
(3) 12V/7AH (3) 12V/9AH (6) 12V/7AH (6) 12V/9AH
Specifications
For -EXL Models, NO Battery Inside.
Recharge Time (Typically) 4 Hours (inside batteries)
Sealed, Maintenance Free Yes
Status Indicators
LCD Screen Graphic LCD
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Audible Alarms Charger Failure /Over Charged, Fan failure, EPO active
Environment
Operating Temperature 32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity 20 to 90% Non-Condensing
Management
On-Device Features Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports (1) Serial Port (RS232), (1) USB Port,
SNMP/HTTP Capable (1) Expansion Port (With optional RMCARD 205)
13
TECHNICAL SPECIFICATIONS
Software
Power Management
Software PowerPanel® Business Edition
Physical
D×W×H = 15.51 x 5.94 x 8.86in. D×W×H = 16.38 x 7.72 x 13.28in.
Dimensions
(394×151×225 mm) (416×196×337 mm)
28.9/17.0lbs 33.7/17.2lbs 52.5/26.9lbs 62.2/27.8lbs
Net Weight
(13.1/7.7Kg) (15.3/7.8Kg) (23.8/12.2Kg) (28.2/12.6Kg)
Safety
Conformance Approvals CE
*) Within 50/60Hz±8% by default, the output frequency is synchronization with input mains. User can adjust the acceptable range for
output frequency (±1, 2, 3, 4, 5, 6, 7, 8, 9, 10%). When input frequency is out of synchronization window but within 40-70Hz, UPS
can stay in line mode and output frequency is regulated at 50/60Hz+0.5% with load derating by 40%.
14
TROUBLE SHOOTING
EPO OFF Missing the EPO connection. Check the EPO connection.
Fault
1. Shut down UPS. Restart UPS to Check the
fan for operation and if the ventilation hole has
Over Temperature High ambient temperature.
been covered
2. Contact CyberPower for repair.
15