Wind Load Calculation ASC (Two Methods)
Wind Load Calculation ASC (Two Methods)
Basic wind speed in U.S. is shown in Figure 6.1. The basic wind speed is basic on statistical data
collected from airport across U.S. The wind speeds correspond to 3-second gust speeds at 33 ft above
ground for exposure C category. The wind speeds represent 50-year return period.
Exposure to wind:
Change from ASCE 7-98 to 02 & 05. Exposure A is deleted. A distinction was made surface roughness
categories and exposure categories. Interpolation between exposure categories is permitted by rational
analysis. Wind is to be evaluated in the worst case of the two 45-degree sectors either side of the wind
direction.
Surface roughness B: Urban and suburban areas, wooded areas or other terrain with numerous
closely spaced obstructions having the size of single-family dwellings or larger.
Surface roughness C: Open terrain with scattered obstructions having heights generally less than
30 ft. including flat open country, grasslands, and all water surfaces in hurricane-prone regions.
Surface roughness D: Flat, unobstructed areas and water surfaces outside hurricane-prone
regions including smooth mud flats, salt flats, and unbroken ice.
Exposure categories:
Exposure B: Surface roughness B in upwind direction for 2630 ft or 10 times the height of the
buildings. For buildings with mean roof height 30 ft or less, the upwind distance is reduced to
1500 ft.
Exposure D: Surface roughness D in upwind direction for 500 ft or 10 times the height of the
buildings. Expose D shall extend inland from the shoreline for a distance of 600 ft or 10 times the
height of the building.
Note: This also allow the building to be designed in different exposure in different direction. A building
located at edge of city or sea shore may be designed for exposure category in one direction and other
exposure in other direction.
Important factor, I for wind load
Building category Non-Hurricane prone regions and Hurricane prone regions with
Hurricane prone regions with V =
80-100 mph and Alaska V > 100 mph
II (all others) 1 1
Building classifications
Building enclosure and openings and protection:
1. Ao > 1.10Aoi
Wind-Borne Debris:
Buildings in standard, essential and substantial hazard categories located in wind-borne debris regions
shall be protected with impact-resistant covering or glazings (windows) at (1) below 60 ft (2) at 30 ft from
roof with aggregate surface within 1500 ft of the building.
Low-rise building:
Building 60 ft or lower and height does not exceed least horizontal dimension.
Minimum design wind load: 10 lb/ft2 for vertical projection of building or components and cladding.
Ps = I Ps30
= Adjustment factor for building height and exposure from Figure 6.2 of ASCE 7-02.
I = Important factor
Ps30 = simplified design wind pressure for exposure B at h = 30 ft and I = 1 from Figure 6-2.
Notes:
1. Figure 6.2 includes Ps30 for basic wind speed from 85 to 170 mph and roof angle from 0 t 0
45 degree. Examples for basic wind speed of 90 mph from 15 to 45 degree are shown below.
A B C D E F G H ECH GCH
15 1 16.1 -5.4 10.7 -3.0 -15.4 -10.1 -10.7 -7.7 -21.6 -16.9
90
mph 20 1 17.8 -4.7 11.9 -2.6 -15.4 -10.7 -10.7 -8.1 -21.6 -16.9
2 - - -5.3 -3.4 - -
30-45 1 14.4 9.9 11.5 7.9 1.1 -8.8 0.4 -7.5 -5.1 -5.8
2 14.4 9.9 11.5 7.9 5.6 -4.3 4.8 -3.4 -5.1 -5.8
2. Wind shall be calculated for horizontal pressure for zone A, B, C, D; vertical pressure for zone E,
F, G, H; and overhang pressure, Ech, Gch as follows:
A End zone of wall. E End zone of windward roof Ech On vertical projection of
end zone overhang
C Interior zone of wall G Interior zone of windward roof Gch On vertical projection of
interior zone overhang
3. Pressures shown are net pressure from windward, leeward and interior pressure and shall be
applied to the horizontal and vertical projections of the building.
4. There are two cases shown in Figure 6.2: Case 1: transverse direction, and Case 2: longitudinal
direction. Both cases shall be checked for roof slope, 25 < 45
5. The length of end zone X=2a. The length, a shall be 10% of least dimension or 0.4h, whichever
is smaller, but not less than 8% of least horizontal dimension or 6 ft.
6. For flat roof, the length of E/F and G/H shall be 1/2 length of the building.
Component and cladding:
Pnet = I Pnet30
= Adjustment factor for building height and exposure from Figure 6.3 of ASCE 7-02.
I = Important factor
Pnet30 = simplified design wind pressure for exposure B at h = 30 ft and I = 1 from Figure 6-3.
In general, wind pressures for components and cladding are higher than those in main wind force
resisting system. Wind pressures show in Figure 6-3 are broken down to effective areas of 10, 50, and
200 square foot to account for localized effect.
Notes:
Figure 6-3 shows Pnet30 for flat roof, hip roof, and gable roof. Wind pressures on roof are divided to
three zones: (1) interior zone, (2) end zone and (3) corner zone. Wind pressures on walls are divided to
two zones: (4) interior zone and (5) end zone. Example of wind zones for gable roof with roof angle from
7 to 45 degree is shown in the figure below. The width of end zone is “a” instead of “2a”. Wind pressures
for wall, roof, and roof overhang are shown in several tables.
Example
Example 1: Wind load on a small office building in suburb using simplified procedure
Design data:
Eve height: 30 ft
Length of building: L = 100 ft
Width of building, B = 50 ft
Roof angle: 20 degree
Location: suburb of Chicago
Topographic feature: flat land
Requirement: Determine wind load for main wind force resisting system
Solution:
1. Determine basic wind speed from Figure 6.1., V = 90 mph
2. Determine Building cateorgy from Table 1.1, and important factor from Table 6.1, I =1
3. Determine Exposure category from Section 6.5.6, Exposure B
4. Determine wind pressure, Ps30 and adjustment coefficient, l from Figure 6-2
Mean roof height: h = 30 ft + (B/2)tan (20 degree) = 39.1 ft
Use 40 ft for adjustment factor
Wind pressure Ps30
Horizontal pressure:
Zone A: Ps30A = 17.8 psf
Zone B: Ps30B = -4.7 psf
Zone C: Ps30C = 11.9 psf
Zone D: Ps30D = -2.6 psf
Vertical pressure:
Zone E: Ps30E = -15.4 psf
Zone F: Ps30F = -10.7 psf
Zone G: Ps30G = -10.7 psf
Zone H: Ps30H = -8.1 psf
Adjustment factor: = 1.09
Design wind pressure:
Horizontal pressure:
Zone A: PA = Ps30A I = 19.4 psf
Zone B: PB = Ps30B I = -5.1 psf
Zone C: PC = Ps30C I =13 psf
Zone D: PD = Ps30D I = -2.8 psf
Vertical pressure:
Zone E: PE = Ps30E I = -16.8 psf
Zone F: PF = Ps30F I = -11.7 psf
Zone G: PG = Ps30G I = -11.7 psf
Zone H: PH = Ps30H I = -8.8 psf
Length of end zone, X = 2 a
a is smaller of 0.4h = 15.64 ft, 0.1B=5 ft, but not less than 3 ft
X = 10 ft
Method 2: Analytical procedure
Apply to all buildings and other structures.
Velocity pressure:
where V is basic wind speed, I is important factor, K d is wind directionality factor, Kzt is topographic factor,
and Kz is velocity pressure exposure coefficient.
Velocity pressure exposure factors are listed Table 6-3 of ASCE 7-02 or can be calculated as
Kz = 2.01 (z/zg)2/.
z is height above ground, z shall not be less than 15 ft. except that z shall not be less than 30 ft for
exposure B for low rise building and for component and cladding.
Exposure zg (ft)
B 7.0 1200
C 9.5 900
D 11.5 700
Topographic Factor,
Kzt = (1+K1+K2+K3)2
where K1, K2, K3 are determined from Figure 6-4 of ASCE 7-02 based on hill, ridge or escarpment.
P = q G Cp – qi (GCpi)
Where
Figure 6.6 is for gable, hip roof, monoslope roof, and mansard roof
Figure 6.7 is for dome roof
Figure 6.8 is for arched roof
GCpi is internal pressure coefficient from Figure 6.5 of ASCE 7-02.
Enclosed building: qi = qh evaluated at mean roof height for windward, leeward, and side walls,
and roof.
Partial enclosed building: qi = qh for negative internal pressure, qi = qz for positive internal pressure
at height z at the level of highest opening.
Note: The internal pressure shall be applied simultaneously on windward and leeward
walls and both positive and negative pressures need to be considered. Therefore, it
cancels each other for enclosed building except for roof. For partially enclosed
building, internal pressure shall be added to leeward wall at the height of opening.
Wall pressure coefficient Cp for Gable, Hip roof (from figure 6.6 of ASCE 7-02):
0-1 -0.5
4 -0.2
Low-rise building.
Where
Note: For wind pressures at edges and corners of walls and roof are higher than interior zone. Wind
pressure at each zone needs to be calculated seperatly.
0-5 0.4 -0.69 -0.37 -0.29 -0.45 -0.45 0.61 -1.07 -0.53 -0.43
20 0.53 -0.69 -0.48 -0.43 -0.45 -0.45 0.8 -1.07 -0.69 -0.64
30-45 0.56 0.21 -0.43 -0.37 -0.45 -0.45 0.69 0.27 -0.53 -0.48
90 0.56 0.56 -0.37 -0.37 -0.45 -0.45 0.69 0.69 -0.48 -0.48
Parapets
The design wind pressure shall be calculated as
Pp = qp GCpn
Where
GCpn is combined net pressure coefficient, +1.8 for windward, -1.1 for leeward.
Case 2: 75% wind loads in two perpendicular directions with 15% eccentricity
considered separately.
Building 60 ft or lower
The design wind pressure shall be calculated as
Where
GCp is external pressure coefficient from Figure 6.11 to 6.16 of ASCE 7-02.
P = q (GCp) – qi (GCpi)
Where
q = qh for Leeward walls, side walls, and roof evaluated at mean roof height h above ground.
Enclosed building: qi = qh evaluated at mean roof height for windward, leeward, and side walls,
and roof.
Partial enclosed building: qi = qh for negative internal pressure, qi = qz for positive internal pressure
at height z at the level of highest opening.
GCp is external pressure coefficient from Figure 6.11 to 6.17 of ASCE 7-02.
Note: The internal pressure shall be applied simultaneously on windward and leeward
walls and both positive and negative pressures need to be considered. Therefore, it
cancels each other for enclosed building except for roof. For partially enclosed
building, internal pressure shall be added to leeward wall at the height of opening.
P = qp (GCp) – qi (GCpi)
Where
GCpi is internal pressure coefficient from Figure 6.5 based on porosity of the parapet envelope.
P = qz G Cf Af
Where
Design Data:
Dimension of sign: 20 ft by 15 ft
Exposure category: B
Requirement: Determine design wind load on billboard to be used with load combination
Solution
1.Determine basic wind speed from Figure 6.1 and directionality factor Kd from Table 6-6, V = 90 mph,
Kd = 0.85
2. Determine Important factor from Table 6-1: I = 1
3. Determine Exposure category from section 6.5.6 and velocity exposure coefficient K z and Kh from Table
6.5.
Kzt = (1+K1K2K3) = 1